Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2023-10-16 10:41:44
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1413.93 | 292.43 | 292.43 |
Net Site Energy | 1413.93 | 292.43 | 292.43 |
Total Source Energy | 3867.81 | 799.94 | 799.94 |
Net Source Energy | 3867.81 | 799.94 | 799.94 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 292.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 59.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 134.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 138.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1121.03 | 292.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 292.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 59.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 134.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 6.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 131.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 25.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 292.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 59.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 134.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 138.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 25.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 46.34 | 60.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 231.85 | 60.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 46.34 | 60.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 231.85 | 60.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1121.028 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1121.028 | 100.00 |
Total On-Site and Utility Electric Sources | 1121.028 | 100.00 |
Total Electricity End Uses | 1121.028 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 51.00 |
Time Setpoint Not Met During Occupied Cooling | 2.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3015.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.61 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7186 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 15.0695 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 9.6875 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 11.2890 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 11.2890 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.7186 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 15.0695 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 9.6875 | 46.45 | 2.5587 | |
Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 11.2890 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUL-14:50 | 16-JAN-17:00 | - | - | - | - | - | - | - | - | - | - | 20-MAY-11:09 |
Heating | 0.00 | 183957.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 25050.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 12540.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1729.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 95625.95 | 183957.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 183957.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 25050.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 10235.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1729.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 188.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1974.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 424.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 438.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 82.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3550.30 | 317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 65.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 39.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 90.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 734.27 | 65.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 65.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 39.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 90.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 734.27 | 65.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.54 |
ZONE2 FINE STORAGE DIRECT AIR | 4.56 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 3.51 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 3.51 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 118054.50 |
PSZ-OFFICE HEATING COIL | 32471.49 |
PSZ-FINE STORAGE HEATING COIL | 119084.32 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 118054.50 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.54 | 1.54 | 1.54 | 1.54 | 1.54 | 1.54 | 1.00 | 1.00 | 1.54 |
PSZ-FINE STORAGE | 4.56 | 4.56 | 4.56 | 4.56 | 4.56 | 4.56 | 1.00 | 1.00 | 4.56 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.54 | 0.120335 |
PSZ-FINE STORAGE_OA_CONTROLLER | 4.56 | 0.353926 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.54 | 1683.22 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 4.56 | 8552.01 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.54 | 1.54 | 1.54 | 1.54 | 25457.36 | 32471.49 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 4.56 | 4.56 | 4.56 | 4.56 | 85601.83 | 119084.32 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.54 | 0.768939 | 1.54 | 25457.36 | 12728.69 | 25457.36 | 0.800660 | 0.800660 |
PSZ-FINE STORAGE COOLING COIL | 4.55 | 2.28 | 4.55 | 85601.83 | 44101.19 | 85601.83 | 0.800850 | 0.800850 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.719 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.792 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 15.069 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15.069 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 9.688 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 12.246 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2539.013 | 10.719 | 199.158 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2539.013 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 20997.932 | 15.069 | 699.931 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20997.932 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 31046.942 | 9.688 | 449.956 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 31046.942 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5959 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.7823 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.9295 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.9295 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.678 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.179 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9765 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9765 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53319041E-11 | 0.92099297E-16 | 0.18475806E-15 | 0.0000000 |
5 | 1 | -5.2159728 | 0.43155192E-04 | -0.26885250E-04 | 0.68722794E-11 |
6 | 0 | 5.8118483 | 0.59583229 | 0.59590233 | |
7 | 4 | 0.72249793E-12 | -0.16720573E-15 | 0.22015083E-14 | 0.12409536E-15 |
8 | 3 | -0.36459118E-03 | 0.53555631E-06 | -0.52695411E-04 | 0.13865996E-12 |
9 | 2 | 1.6915239 | 0.11971291E-01 | 1.1039557 | -0.69896550E-04 |
10 | 1 | -7.1930661 | 0.31446443 | -16.864389 | 0.32415671 |
11 | 0 | 6.0306730 | 0.20232993 | 16.289252 | |
12 | 4 | 0.69489933E-12 | 0.18569687E-15 | 0.39666878E-14 | 0.11858654E-15 |
13 | 3 | -0.35466159E-03 | 0.62784354E-06 | -0.51164218E-04 | 0.13336592E-12 |
14 | 2 | 1.6674989 | 0.14195866E-01 | 1.0857092 | -0.67991750E-04 |
15 | 1 | -7.2261037 | 0.37556877 | -16.746879 | 0.31952467 |
16 | 0 | 6.1915038 | 0.24277908 | 16.293766 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.39666878E-14 | 0.18569687E-15 | 0.69489933E-12 | 0.11858654E-15 |
85 | 3 | -0.51164218E-04 | 0.62784354E-06 | -0.35466159E-03 | 0.13336592E-12 |
86 | 2 | 1.0857092 | 0.14195866E-01 | 1.6674989 | -0.67991750E-04 |
87 | 1 | -16.746879 | 0.37556877 | -7.2261037 | 0.31952467 |
88 | 0 | 16.293766 | 0.24277908 | 6.1915038 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5726_SHGC_SOUTH_0.39 | 34 | 1 | VerySmooth | 3.256 | 3.256 | 1.000 | 0.391 | ||
2 | NONRESWINDOW_U_0.5726_SHGC_NORTH_0.39 | 35 | 1 | VerySmooth | 3.256 | 3.256 | 1.000 | 0.391 | ||
3 | NONRESWINDOW_U_0.5726_SHGC_EAST_0.39 | 36 | 1 | VerySmooth | 3.256 | 3.256 | 1.000 | 0.391 | ||
4 | NONRESWINDOW_U_0.5726_SHGC_WEST_0.39 | 37 | 1 | VerySmooth | 3.256 | 3.256 | 1.000 | 0.391 | ||
5 | SKYLIGHT_U_1.02_SHGC_0.49 | 38 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.491 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46589 | 0.46589 | 0.39000 | 0.13867 | 0.18233 | 0.00000 | 0.84000 | 0.84000 | 1.45195E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46589 | 0.46589 | 0.39000 | 0.13867 | 0.18233 | 0.00000 | 0.84000 | 0.84000 | 1.45195E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46589 | 0.46589 | 0.39000 | 0.13867 | 0.18233 | 0.00000 | 0.84000 | 0.84000 | 1.45195E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46589 | 0.46589 | 0.39000 | 0.13867 | 0.18233 | 0.00000 | 0.84000 | 0.84000 | 1.45195E-002 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.32532 | 0.12431 | 0.12431 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.849 | 0.366 | 0.255 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 0.153 | 6.473E-004 | 9.992E-004 | 0.546 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.780 | 5.598E-004 | 3.565E-004 | 0.951 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 3.433 | 1.071E-003 | 6.996E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 12812.84789 | 15375.41747 | 1.28157 | 1.53788 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 33.75000 | 5.69729E-003 | 236.87965 | 12.74874 | 0.12033 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 10877.66912 | 13053.20295 | 0.37137 | 0.44564 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.90000 | 2.34317E-003 | 236.87965 | 12.74874 | 0.12033 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 48687.54981 | 58425.05977 | 3.79583 | 4.55500 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 35.10000 | 5.69938E-003 | 1393.40969 | 30.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 38070.43379 | 45684.52055 | 1.09432 | 1.31319 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | -7.90000 | 2.34317E-003 | 1393.40969 | 30.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 35.10000 | 5.69938E-003 | 3204.84228 | 69.00000 | 0.81403 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 98378.75329 | 118054.50394 | 2.92236 | 3.50684 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 3204.84228 | 69.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 19401.07 | 1.53788 | 1.53788 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 11871.75 | 0.44564 | 0.44564 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 69599.13 | 4.55500 | 4.55500 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 40210.95 | 1.31319 | 1.31319 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.53788 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.55500 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 3.50684 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 3.50684 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 118054.49827 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 118054.50394 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.53788 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.53788 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.53788 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.53788 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.53788 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.53788 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.55500 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.55500 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.55500 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 4.55500 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.55500 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 4.55500 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.53788 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 4.55500 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.53788 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12033 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.53788 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1683.21684 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.53788 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.53788 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.53788 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.53788 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.53788 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.76894 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.53788 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25457.36000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 12728.68730 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 25457.36000 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25457.36000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32471.49046 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 32471.49046 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.55500 |
47 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.55500 |
49 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 8552.00559 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.55500 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.55500 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.55500 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.55500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.55500 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.27750 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.55500 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 85601.83000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 44101.19206 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 85601.83000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80085 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80085 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 85601.83000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 119084.32037 |
64 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
66 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 119084.32037 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 24264.0 | 10.70 | 10.08 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 82065.7 | 10.19 | 9.60 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1744599893 | 0.1649667777 | Pass | Pass | 1.8411353727 | 13.6901936346 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.4196875425 | 0.5027095081 | Pass | Pass | 0.5910701080 | 2.4831480176 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 5.4512869149E-002 | 6.6709736688E-002 | Pass | Pass | 4.1756351047E-002 | 0.1268267565 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 11270.65 | 667.79 | 0.00 | 91.16 | 420.45 | 12450.11 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 9.00 | 6 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 5.00 | 4 | |||
Nov | 9.00 | 7 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.816 | 0.929 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.816 | 0.929 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.816 | 0.929 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.551 | 0.596 | 3204.84 | 3170.23 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.760 | 0.929 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.760 | 0.929 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.5726_SHGC_WEST_0.39 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.256 | 0.391 | 0.391 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.5726_SHGC_WEST_0.39 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.256 | 0.391 | 0.391 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.5726_SHGC_NORTH_0.39 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.256 | 0.391 | 0.391 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.5726_SHGC_NORTH_0.39 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.256 | 0.391 | 0.391 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.27 | 4.939 | 0.497 | 0.498 | |||||||||||||||||
North Total or Average | 6.51 | 3.256 | 0.391 | 0.391 | |||||||||||||||||
Non-North Total or Average | 45.76 | 5.179 | 0.512 | 0.513 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.7186 | 236.88 | 2539.01 | LightsWired | LTG_SCH_OFFICE | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.86 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 15.0695 | 1393.41 | 20997.93 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 239.15 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 9.6875 | 3204.84 | 31046.94 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 353.60 |
Interior Lighting Total | 11.2890 | 4835.13 | 54583.89 | 623.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 8532.22 | AstronomicalClock | - | 83.71 | 83.71 | 134.07 | |
Exterior Lighting Total | 8532.22 | 134.07 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25457.36 | 20382.69 | 5074.67 | 0.80 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 85601.83 | 68554.23 | 17047.60 | 0.80 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 24264.0 | 10.70 | 10.08 | ||||
PSZ-FINE STORAGE COOLING COIL | 82065.7 | 10.19 | 9.60 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 118054.50 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 32471.49 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 119084.32 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 3.51 | 325.82 | 92.91 | 1.00 | 3.29 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 1.54 | 1683.22 | 1094.51 | 1.00 | 1.33 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.59 | 1110.54 | 4.56 | 8552.01 | 1877.50 | 1.00 | 1.15 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 12812.85 | 15375.42 | 64.91 | 1.282 | 1.538 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 23.90 | 23.90 | 0.00810 | 33.75 | 0.00570 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 48687.55 | 58425.06 | 41.93 | 3.796 | 4.555 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 26.70 | 26.70 | 0.00792 | 35.10 | 0.00570 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 0.00 | 35.35 | 0.00579 | 35.10 | 0.00570 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10877.67 | 13053.20 | 55.10 | 0.371 | 0.446 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00754 | -7.90 | 0.00234 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 38070.43 | 45684.52 | 32.79 | 1.094 | 1.313 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 15.56 | 15.55 | 0.00632 | -7.90 | 0.00234 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 98378.75 | 118054.50 | 36.84 | 2.922 | 3.507 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00566 | -7.90 | 0.00234 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.54 | 1.54 | 0.45 | 0.45 | 1.5379 | 1.5379 | 1.5379 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 4.56 | 4.56 | 1.31 | 1.31 | 4.5550 | 4.5550 | 4.5550 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 118054.498 | 118054.498 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 118054.50 | 118054.50 | 3.506836 | 10.00 | 6.26 | 0.00565851 | 43.33 | 19.83 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 10.00 | 0.00565851 | 61.1897 | 118054.50 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 25457.360 | 20382.690 | 1.537880 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 25457.36 | 25457.36 | 1.537880 | 25.77 | 14.50 | 0.00791316 | 12.00 | 9.45 | 0.00791316 | 33.93 | 0.00569757 | 15.40 | 7.8247 | 23.90 | 0.00810138 | 36.1090 | 12803.92 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 32471.490 | 32471.490 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 32471.49 | 32471.49 | 1.537879 | 18.78 | 11.35 | 0.00713200 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 7.8247 | 21.10 | 0.00753852 | 39.8720 | 10877.67 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 85601.830 | 68554.226 | 4.555000 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 85601.83 | 85601.83 | 4.555000 | 29.21 | 15.49 | 0.00774392 | 12.00 | 9.29 | 0.00774392 | 35.10 | 0.00569938 | 15.77 | 7.7701 | 26.70 | 0.00791617 | 29.8776 | 48687.55 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 119084.320 | 119084.320 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 119084.32 | 119084.32 | 4.555001 | 13.73 | 8.25 | 0.00600904 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 7.7701 | 15.55 | 0.00631788 | 47.4158 | 38070.43 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 118054.498 | 118054.498 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 3.506836 | 3.47320115 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 118054.50 | 118054.50 | 1.0000 | 3.47320115 | 3.506836 | 10.00 | 6.26 | 0.00565851 | 24302.1 | 43.33 | 19.83 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 118054.50 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 10.00 | 0.00565851 | 10.00 | 0.00565851 | 61.1897 | 118054.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25457.360 | 20382.690 | 1.537880 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5502 | 1004.8586 | 0.9904 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.537879 | 1.52312888 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | Sensible | 25457.36 | 25457.36 | 1.0000 | 1.52313003 | 1.537880 | 25.77 | 14.50 | 0.00791316 | 46062.9 | 12.00 | 9.45 | 0.00791316 | 32024.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25457.36 | 33.93 | 0.00569757 | 15.40 | 0.12033486 | 7.8247 | 23.90 | 0.00810138 | 23.90 | 0.00810138 | 36.1090 | 12803.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32471.490 | 32471.490 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.537879 | 1.52312888 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 32471.49 | 32471.49 | 1.0000 | 1.52312888 | 1.537879 | 18.78 | 11.35 | 0.00713200 | 36960.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32471.49 | -7.90 | 0.00234317 | -7.90 | 0.12033486 | 7.8247 | 21.05 | 0.00753852 | 21.10 | 0.00753852 | 39.8720 | 10877.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 85601.830 | 68554.226 | 4.555000 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2356 | 1004.8586 | 0.9904 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 4.555001 | 4.51131395 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 85601.83 | 85601.83 | 1.0000 | 4.51131251 | 4.555000 | 29.21 | 15.49 | 0.00774392 | 49142.0 | 12.00 | 9.29 | 0.00774392 | 31597.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 85601.83 | 35.10 | 0.00569938 | 15.77 | 0.35392606 | 7.7701 | 26.70 | 0.00791617 | 26.70 | 0.00791617 | 29.8776 | 48687.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 119084.320 | 119084.320 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 4.555001 | 4.51131395 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | Sensible | 119084.32 | 119084.32 | 1.0000 | 4.51131395 | 4.555001 | 13.73 | 8.25 | 0.00600904 | 28978.9 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 119084.32 | -7.90 | 0.00234317 | -7.90 | 0.35392606 | 7.7701 | 15.55 | 0.00631788 | 15.55 | 0.00631788 | 47.4158 | 38070.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.12 | 1.54 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.35 | 4.56 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2178.67 | 2228.00 | 1118.67 |
ZONE2 FINE STORAGE | 2859.33 | 2736.83 | 2102.00 |
ZONE3 BULK STORAGE | 3262.67 | 3292.83 | 3011.00 |
Facility | 3502.17 | 3434.67 | 3015.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 55.83 | 120.33 | 40.83 | 2.17 |
ZONE2 FINE STORAGE | 224.50 | 74.50 | 18.50 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 268.50 | 157.50 | 51.00 | 2.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 1.054 | 0.513 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1.113 | 0.409 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.172 | 0.000 | 0.633 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1203 | 0.120 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.3539 | 0.354 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 3204.84 | 0.814 | ||
Total Facility | 83.53 | 111.75 | 39241.41 | 4835.13 | 0.4743 | 1.288 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 4301994.47 | 0.00 | 4301994.47 | 3183433.94 | 7485428.41 | 3794880.16 | 5460.49 | 2058.10 | 1241.41 | 183.73 |
ZONE2 FINE STORAGE | 12022507.73 | 0.00 | 12022507.73 | 12008380.73 | 24030888.45 | 11161412.23 | 5633.50 | 2112.17 | 1014.34 | 28.99 |
ZONE3 BULK STORAGE | 0.00 | 0.12E+09 | 0.12E+09 | 47461795.20 | 0.17E+09 | 25671248.14 | 6722.50 | 53.54 | 1983.97 | 4974.47 |
Total Facility | 16324502.20 | 0.12E+09 | 0.14E+09 | 62653609.86 | 0.20E+09 | 40627540.53 | 7726.91 | 2437.83 | 3213.63 | 4980.28 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.2918 | 0.0000 | 0.2918 | 0.1425 | 0.4343 | 0.1203 | 508.13 | 2058.10 | 1069.77 |
ZONE2 FINE STORAGE | 0.8933 | 0.0000 | 0.8933 | 0.3306 | 1.2239 | 0.3539 | 538.49 | 2112.17 | 985.35 |
ZONE3 BULK STORAGE | 0.0000 | 5.9562 | 5.9562 | 1.6748 | 7.6310 | 0.8140 | 2560.74 | 16.83 | 1058.43 |
Total Facility | 1.1850 | 5.9562 | 7.1412 | 2.1480 | 9.2892 | 1.2883 | 2603.11 | 2401.13 | 2113.05 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 4219868.44 | 0.00 | 4219868.44 | 3794880.16 | 7518.59 | 2.97 | 1238.44 | 183.73 |
PSZ-FINE STORAGE | 11792995.38 | 0.00 | 11792995.38 | 11161412.23 | 7745.66 | 0.75 | 1013.59 | 28.99 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2862 | 0.0000 | 0.2862 | 0.1203 | 2566.23 | 2.97 | 1066.80 |
PSZ-FINE STORAGE | 0.8762 | 0.0000 | 0.8762 | 0.3539 | 2650.65 | 0.75 | 984.60 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2712.22 | 611.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2706.78 | 424.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2984 | 0.4755 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.9355 | 1.6072 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 383 |
Defaulted Fields | 319 |
Fields with Defaults | 1020 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1121.03 | 6718.26 | 01-JAN-09:20 | 95625.95 | 22-JUL-14:50 |
Electricity:Building | 769.77 | 6235.26 | 01-JAN-00:10 | 58611.10 | 19-MAY-12:10 |
Electricity:Zone:ZONE1 OFFICE | 62.81 | 1030.77 | 01-JAN-00:10 | 3867.54 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 762.90 | 6235.26 | 01-JAN-00:10 | 56305.80 | 02-JAN-09:10 |
InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 467.81 | 3104.69 | 01-JAN-00:10 | 36895.31 | 19-MAY-12:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 138.48 | 0.00 | 01-JAN-09:20 | 12540.52 | 19-MAY-14:00 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 6.87 | 0.00 | 01-JAN-00:10 | 2305.29 | 18-JUN-13:10 |
Ventilation (simple):Fans:Electricity | 6.87 | 0.00 | 01-JAN-00:10 | 2305.29 | 18-JUN-13:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 6.87 | 0.00 | 01-JAN-00:10 | 2305.29 | 18-JUN-13:10 |
ElectricityPurchased:Facility | 1121.03 | 6718.26 | 01-JAN-09:20 | 95625.95 | 22-JUL-14:50 |
ElectricityPurchased:Plant | 1121.03 | 6718.26 | 01-JAN-09:20 | 95625.95 | 22-JUL-14:50 |
Cogeneration:ElectricityPurchased | 1121.03 | 6718.26 | 01-JAN-09:20 | 95625.95 | 22-JUL-14:50 |
General:Cogeneration:ElectricityPurchased | 1121.03 | 6718.26 | 01-JAN-09:20 | 95625.95 | 22-JUL-14:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1121.03 | 6718.26 | 01-JAN-09:20 | 95625.95 | 22-JUL-14:50 |
ElectricityNet:Plant | 1121.03 | 6718.26 | 01-JAN-09:20 | 95625.95 | 22-JUL-14:50 |
Cogeneration:ElectricityNet | 1121.03 | 6718.26 | 01-JAN-09:20 | 95625.95 | 22-JUL-14:50 |
General:Cogeneration:ElectricityNet | 1121.03 | 6718.26 | 01-JAN-09:20 | 95625.95 | 22-JUL-14:50 |
Electricity:HVAC | 191.22 | 0.00 | 01-JAN-09:20 | 36498.25 | 22-JUL-15:10 |
General:Fans:Electricity | 131.61 | 0.00 | 01-JAN-09:20 | 10561.04 | 02-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 59.61 | 0.00 | 01-JAN-00:10 | 26263.03 | 22-JUL-15:10 |
General:Cooling:Electricity | 59.61 | 0.00 | 01-JAN-00:10 | 26263.03 | 22-JUL-15:10 |
ExteriorLights:Electricity | 134.07 | 0.00 | 01-JAN-07:20 | 8532.22 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 134.07 | 0.00 | 01-JAN-07:20 | 8532.22 | 01-JAN-00:10 |
Electricity:Plant | 25.97 | 483.00 | 23-JAN-06:30 | 2429.72 | 10-FEB-12:30 |
WaterSystems:Electricity | 25.97 | 483.00 | 23-JAN-06:30 | 2429.72 | 10-FEB-12:30 |
Water Heater:WaterSystems:Electricity | 25.97 | 483.00 | 23-JAN-06:30 | 2429.72 | 10-FEB-12:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 292.91 | 3750.00 | 29-APR-18:10 | 183957.76 | 16-JAN-18:00 |
NaturalGas:HVAC | 292.91 | 3750.00 | 29-APR-18:10 | 183957.76 | 16-JAN-18:00 |
Heating:NaturalGas | 292.91 | 3750.00 | 29-APR-18:10 | 183957.76 | 16-JAN-18:00 |
General:Heating:NaturalGas | 292.91 | 3750.00 | 29-APR-18:10 | 183957.76 | 16-JAN-18:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-MAY-11:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-MAY-11:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-MAY-11:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-MAY-11:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-MAY-11:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-MAY-11:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-MAY-11:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-MAY-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 664.51 | 0.00 | 01-JAN-09:20 | 281882.20 | 16-JAN-18:00 |
EnergyTransfer:Building | 335.28 | 0.00 | 01-JAN-09:20 | 142501.58 | 16-JAN-18:00 |
EnergyTransfer:Zone:ZONE1 OFFICE | 66.90 | 0.00 | 01-JAN-00:10 | 21412.70 | 17-JAN-07:20 |
Heating:EnergyTransfer | 163.73 | 0.00 | 01-JAN-09:20 | 142501.58 | 16-JAN-18:00 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 17.15 | 0.00 | 01-JAN-00:10 | 21412.70 | 17-JAN-07:20 |
General:Heating:EnergyTransfer | 163.73 | 0.00 | 01-JAN-09:20 | 142501.58 | 16-JAN-18:00 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 17.15 | 0.00 | 01-JAN-00:10 | 21412.70 | 17-JAN-07:20 |
Cooling:EnergyTransfer | 171.55 | 0.00 | 01-JAN-00:10 | 58662.76 | 22-JUL-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 49.74 | 0.00 | 01-JAN-00:10 | 13759.03 | 28-JUN-16:10 |
General:Cooling:EnergyTransfer | 171.55 | 0.00 | 01-JAN-00:10 | 58662.76 | 22-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 49.74 | 0.00 | 01-JAN-00:10 | 13759.03 | 28-JUN-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 193.21 | 0.00 | 01-JAN-00:40 | 48782.01 | 16-JAN-18:00 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 71.41 | 0.00 | 01-JAN-00:40 | 48782.01 | 16-JAN-18:00 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 71.41 | 0.00 | 01-JAN-00:40 | 48782.01 | 16-JAN-18:00 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 121.81 | 0.00 | 01-JAN-00:10 | 47153.98 | 22-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 121.81 | 0.00 | 01-JAN-00:10 | 47153.98 | 22-JUL-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 75.16 | 0.00 | 01-JAN-08:30 | 89089.24 | 14-DEC-04:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 75.16 | 0.00 | 01-JAN-08:30 | 89089.24 | 14-DEC-04:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 75.16 | 0.00 | 01-JAN-08:30 | 89089.24 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 329.23 | 0.00 | 01-JAN-09:20 | 139380.62 | 16-JAN-18:00 |
HeatingCoils:EnergyTransfer | 130.65 | 0.00 | 01-JAN-09:20 | 139380.62 | 16-JAN-18:00 |
CoolingCoils:EnergyTransfer | 198.58 | 0.00 | 01-JAN-00:10 | 74613.60 | 22-JUL-15:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 17.155 | -49.742 | 0.000 | 0.000 | 9.636 | 30.864 | 31.946 | 15.707 | 0.000 | 2.749 | 0.001 | 0.000 | -9.861 | 0.000 | -27.140 | -21.313 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 71.408 | -121.800 | 0.000 | 0.000 | 21.014 | 239.148 | 0.000 | 0.000 | 0.000 | 4.638 | 0.001 | 0.000 | 0.000 | 0.000 | -99.181 | -115.228 |
ZONE3 BULK STORAGE | 75.162 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 51.810 | 353.598 | 107.344 | 176.789 | 0.000 | 6.158 | 0.012 | 0.000 | -106.890 | 0.000 | -515.977 | -147.993 |
Total Facility | 75.162 | 0.000 | 88.563 | -171.542 | 0.000 | 0.000 | 82.459 | 623.610 | 139.290 | 192.496 | 0.000 | 13.545 | 0.013 | 0.000 | -116.752 | 0.000 | -642.298 | -284.534 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 11-JUN-23:01 | 0.00 | 0.00 | 0.00 | -28280.35 | 0.00 | 0.00 | 0.00 | 457.02 | 573.75 | 0.00 | 0.00 | 0.00 | 27958.89 | 0.00 | -452.28 | 0.00 | -257.03 | 0.00 |
ZONE2 FINE STORAGE | 17-SEP-12:01 | 0.00 | 0.00 | 0.00 | -82844.92 | 0.00 | 0.00 | 0.00 | 2099.79 | 0.00 | 0.00 | 0.00 | 0.00 | 82048.31 | 0.00 | -0.00 | 0.00 | -1303.18 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-AUG-21:41 | 0.00 | 0.00 | 0.00 | -104288.95 | 0.00 | 0.00 | 0.00 | 5661.51 | 2623.78 | 0.00 | 0.00 | 0.00 | 112024.28 | 0.00 | -5230.61 | 0.00 | -10790.01 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 17-JAN-06:21 | 0.00 | 0.00 | 33366.49 | 0.00 | 0.00 | 0.00 | 118.54 | 583.97 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -926.73 | 0.00 | -4514.71 | -29201.31 |
ZONE2 FINE STORAGE | 16-JAN-22:32 | 0.00 | 0.00 | 124592.80 | 0.00 | 0.00 | 0.00 | 0.00 | 2099.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -14792.40 | -111900.19 |
ZONE3 BULK STORAGE | 14-DEC-03:51 | 89094.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7945.73 | 0.00 | -84226.27 | -2076.75 |
Total Facility | 06-FEB-05:01 | 79855.89 | 0.00 | 144954.67 | 0.00 | 0.00 | 0.00 | 0.00 | 5661.51 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -10454.82 | 0.00 | -69475.51 | -153165.53 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.5379 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1203 | 1.5379 | 0.0782 | 1.0000 | Not calculated | 0.1203 | 0.0782 | ||
PSZ-FINE STORAGE | 4.5550 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.3539 | 4.5550 | 0.0777 | 1.0000 | Not calculated | 0.3539 | 0.0777 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.5379 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1203 | 1.5379 | 1.0000 | 1.0000 | Not calculated | 0.1203 | 0.0782 | ||
PSZ-FINE STORAGE | 4.5550 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.3539 | 4.5550 | 1.0000 | 1.0000 | Not calculated | 0.3539 | 0.0777 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5379 | 1.5379 | 1.5379 | No | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5550 | 4.5550 | 4.5550 | No | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.5379 | 1.5379 | 1.5379 | 1.5379 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 4.5550 | 4.5550 | 4.5550 | 4.5550 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5379 | 1.5379 | 1.5379 | No | 0.1203 | 0.2700 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5550 | 4.5550 | 4.5550 | No | 0.3539 | 0.2695 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.5379 | 1.5379 | 1.5379 | 1.5379 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 4.5550 | 4.5550 | 4.5550 | 4.5550 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 51.00 |
Number of hours cooling loads not met | 2.17 |
Number of hours not met | 53.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 292.91 | 183957.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 59.61 | 26263.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 623.61 | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 134.07 | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 6.87 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 131.61 | 10561.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 25.97 | 2429.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 1121.03 |
Natural Gas | 0.00 | 292.91 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 1413.93 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 128.97 |
Space Heating | 0.00 |
Space Cooling | 12.33 |
Fans (All) | 28.64 |
Service Water Heating | 5.37 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 231.85 |
Subtotal | 231.85 |
Natural Gas [MJ/m2] | |
Space Heating | 60.58 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 60.58 |
Subtotal | 60.58 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 44.10 |
Space Heating | 20.72 |
Space Cooling | 4.22 |
Fans (All) | 9.79 |
Service Water Heating | 1.84 |
Receptacle Equipment | 9.85 |
Miscellaneous | 9.48 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 3430. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8524.50 | 235.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8455.67 | 304.33 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 6326.00 | 2380.50 | 53.50 | 0.00 | 0.00 |
Min | 6326.00 | 235.50 | 0.00 | 0.00 | 0.00 |
Max | 8524.50 | 2380.50 | 53.50 | 0.00 | 0.00 |
Average | 7768.72 | 973.44 | 17.83 | 0.00 | 0.00 |
Sum | 23306.17 | 2920.33 | 53.50 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 77982.50 | 4736.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 123370.33 | 64988.50 | 2834.17 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 123370.33 | 64988.50 | 2834.17 | 0.00 | 0.00 |
Average | 78126.61 | 23241.67 | 944.72 | 0.00 | 0.00 |
Sum | 234379.83 | 69725.00 | 2834.17 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8566.33 | 193.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8301.33 | 458.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 6895.50 | 1864.50 | 0.00 | 0.00 | 0.00 |
Min | 6895.50 | 193.67 | 0.00 | 0.00 | 0.00 |
Max | 8566.33 | 1864.50 | 0.00 | 0.00 | 0.00 |
Average | 7921.06 | 838.94 | 0.00 | 0.00 | 0.00 |
Sum | 23763.17 | 2516.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 76464.00 | 6255.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 137977.17 | 53215.83 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 137977.17 | 53215.83 | 0.00 | 0.00 | 0.00 |
Average | 82489.39 | 19823.61 | 0.00 | 0.00 | 0.00 |
Sum | 247468.17 | 59470.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11922489.13 | 704.30 | 05-JAN-16:00 | 16.10 | 6.84 | 0.523154E+09 | 768.96 | 03-JAN-16:40 | 16.10 | 6.84 |
February | 0.128267E+09 | 3226.08 | 15-FEB-16:00 | 17.20 | 6.50 | 0.487648E+09 | 768.96 | 14-FEB-16:00 | 17.20 | 6.50 |
March | 0.369418E+09 | 3339.42 | 08-MAR-16:30 | 22.50 | 8.65 | 0.610088E+09 | 768.97 | 04-MAR-16:49 | 22.50 | 8.65 |
April | 0.234214E+10 | 24195.28 | 29-APR-19:21 | 20.85 | 7.69 | 0.613301E+09 | 768.97 | 20-APR-12:09 | 20.85 | 7.69 |
May | 0.462572E+10 | 26173.50 | 14-MAY-23:02 | 19.77 | 7.02 | 0.652430E+09 | 769.03 | 23-MAY-14:20 | 19.27 | 13.90 |
June | 0.902080E+10 | 28279.59 | 11-JUN-23:01 | 18.12 | 10.21 | 0.659204E+09 | 769.06 | 29-JUN-08:20 | 29.60 | 17.80 |
July | 0.108887E+11 | 26403.57 | 23-JUL-23:01 | 23.22 | 14.28 | 0.634287E+09 | 769.07 | 26-JUL-12:09 | 29.68 | 18.07 |
August | 0.108121E+11 | 26416.83 | 06-AUG-23:01 | 23.80 | 13.86 | 0.685284E+09 | 769.07 | 14-AUG-12:20 | 28.50 | 17.25 |
September | 0.752999E+10 | 26224.93 | 10-SEP-23:01 | 19.72 | 12.31 | 0.634476E+09 | 769.06 | 01-SEP-13:09 | 19.72 | 12.31 |
October | 0.356223E+10 | 26513.49 | 01-OCT-23:01 | 19.22 | 12.06 | 0.613664E+09 | 769.05 | 03-OCT-12:39 | 24.03 | 14.81 |
November | 0.383148E+09 | 3910.52 | 02-NOV-15:00 | 17.20 | 9.31 | 0.546536E+09 | 768.96 | 14-NOV-15:50 | 12.20 | 3.79 |
December | 69567065.91 | 1515.79 | 02-DEC-15:30 | 11.65 | 3.33 | 0.517792E+09 | 768.97 | 01-DEC-16:40 | 11.65 | 3.33 |
Annual Sum or Average | 0.497440E+11 | 0.717786E+10 | ||||||||
Minimum of Months | 11922489.13 | 704.30 | 11.65 | 3.33 | 0.487648E+09 | 768.96 | 11.65 | 3.33 | ||
Maximum of Months | 0.108887E+11 | 28279.59 | 23.80 | 14.28 | 0.685284E+09 | 769.07 | 29.68 | 18.07 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 | -1.2 | 0.101772E+10 | 1789.41 | 05-JAN-15:50 | 16.10 | 6.84 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.2 | -5.2 | 0.102192E+10 | 2236.64 | 15-FEB-15:39 | 17.20 | 6.56 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.8 | 0.143150E+10 | 2246.80 | 08-MAR-15:20 | 22.40 | 9.08 |
April | 0.267440E+10 | 71028.89 | 29-APR-17:33 | 24.27 | 9.18 | 0.167866E+10 | 2246.81 | 24-APR-15:50 | 24.27 | 9.18 |
May | 0.943441E+10 | 80290.19 | 26-MAY-17:41 | 22.98 | 11.72 | 0.185649E+10 | 2246.83 | 22-MAY-09:50 | 22.98 | 11.72 |
June | 0.242640E+11 | 81189.61 | 04-JUN-11:21 | 24.15 | 14.30 | 0.191680E+10 | 2247.01 | 24-JUN-10:00 | 27.20 | 17.13 |
July | 0.325002E+11 | 81851.26 | 22-JUL-00:31 | 23.33 | 13.05 | 0.185289E+10 | 2247.08 | 10-JUL-13:39 | 23.33 | 13.05 |
August | 0.297420E+11 | 82213.21 | 05-AUG-21:41 | 23.68 | 14.00 | 0.200004E+10 | 2247.07 | 11-AUG-13:09 | 27.38 | 17.10 |
September | 0.175312E+11 | 82848.49 | 17-SEP-12:01 | 22.07 | 13.93 | 0.184541E+10 | 2246.99 | 06-SEP-14:09 | 22.07 | 13.93 |
October | 0.565379E+10 | 79746.38 | 01-OCT-11:01 | 24.18 | 13.81 | 0.167333E+10 | 2246.96 | 02-OCT-10:30 | 23.05 | 14.65 |
November | 4658842.29 | 1068.52 | 02-NOV-14:20 | 16.13 | 9.06 | 0.125018E+10 | 2246.80 | 02-NOV-15:39 | 16.87 | 9.63 |
December | 1230682.41 | 599.15 | 21-DEC-08:55 | -5.0 | -6.3 | 0.100636E+10 | 1814.32 | 02-DEC-14:00 | -5.0 | -6.3 |
Annual Sum or Average | 0.121806E+12 | 0.185513E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -5.0 | -6.3 | 0.100636E+10 | 1789.41 | -5.0 | -6.3 | ||
Maximum of Months | 0.325002E+11 | 82848.49 | 24.27 | 14.30 | 0.200004E+10 | 2247.08 | 27.38 | 17.13 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 | -1.2 | 0.103981E+10 | 1928.48 | 05-JAN-15:09 | 16.10 | 6.84 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.2 | -5.2 | 0.109831E+10 | 2589.70 | 15-FEB-15:30 | 17.20 | 6.59 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.8 | 0.184793E+10 | 3037.85 | 13-MAR-15:09 | 21.32 | 7.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.84 | 0.291130E+10 | 5467.47 | 29-APR-13:20 | 23.53 | 9.38 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.92 | 0.415050E+10 | 6596.37 | 19-MAY-15:30 | 30.00 | 12.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.96 | 0.556245E+10 | 9097.65 | 26-JUN-14:00 | 36.70 | 15.17 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 | 14.90 | 0.578022E+10 | 9097.65 | 20-JUL-13:30 | 36.40 | 16.09 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 | 16.86 | 0.586675E+10 | 8675.40 | 01-AUG-15:50 | 35.00 | 16.30 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 | 14.47 | 0.486904E+10 | 7326.99 | 02-SEP-15:30 | 31.40 | 16.12 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.88 | 0.341945E+10 | 6416.55 | 02-OCT-14:20 | 26.87 | 15.40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.34 | 0.162121E+10 | 3379.45 | 02-NOV-14:30 | 16.40 | 9.13 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.84 | 0.102391E+10 | 2057.44 | 02-DEC-14:30 | 11.40 | 3.40 |
Annual Sum or Average | 0.00 | 0.391909E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.2 | -5.2 | 0.102391E+10 | 1928.48 | 11.40 | 3.40 | ||
Maximum of Months | 0.00 | 0.00 | 21.95 | 16.86 | 0.586675E+10 | 9097.65 | 36.70 | 16.30 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.453683E+10 | 33366.48 | 17-JAN-06:21 | -3.6 |
February | 0.350774E+10 | 32956.48 | 07-FEB-06:12 | -3.9 |
March | 0.209843E+10 | 32682.80 | 04-MAR-06:01 | -1.7 |
April | 0.505482E+09 | 32605.76 | 08-APR-05:01 | 2.62 |
May | 0.216640E+09 | 32000.81 | 05-MAY-05:01 | 5.68 |
June | 50661171.95 | 7914.39 | 07-JUN-05:50 | 20.32 |
July | 8687149.93 | 1846.93 | 26-JUL-06:05 | 20.28 |
August | 15544206.22 | 3091.80 | 19-AUG-05:10 | 19.22 |
September | 68140320.06 | 5207.31 | 15-SEP-05:40 | 18.90 |
October | 0.495856E+09 | 32647.25 | 26-OCT-05:01 | -2.5 |
November | 0.164986E+10 | 32737.97 | 28-NOV-06:01 | -2.1 |
December | 0.400107E+10 | 33061.87 | 22-DEC-06:22 | -6.1 |
Annual Sum or Average | 0.171550E+11 | |||
Minimum of Months | 8687149.93 | 1846.93 | -6.1 | |
Maximum of Months | 0.453683E+10 | 33366.48 | 20.32 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.191861E+11 | 124592.80 | 16-JAN-22:32 | -2.0 |
February | 0.140395E+11 | 124295.32 | 04-FEB-04:02 | -5.7 |
March | 0.714236E+10 | 117263.28 | 04-MAR-05:42 | -1.6 |
April | 0.256634E+10 | 8569.82 | 15-APR-06:25 | 13.30 |
May | 0.160494E+10 | 8643.99 | 04-MAY-07:00 | 6.70 |
June | 0.431055E+09 | 8512.74 | 01-JUN-06:25 | 15.55 |
July | 46381812.18 | 7395.64 | 15-JUL-06:02 | 19.45 |
August | 0.149345E+09 | 8359.42 | 28-AUG-06:25 | 16.40 |
September | 0.605953E+09 | 8586.37 | 08-SEP-06:25 | 14.45 |
October | 0.205456E+10 | 13442.33 | 26-OCT-04:15 | -2.8 |
November | 0.656584E+10 | 121909.45 | 26-NOV-06:52 | 0.00 |
December | 0.170157E+11 | 124487.67 | 14-DEC-03:12 | 0.03 |
Annual Sum or Average | 0.714081E+11 | |||
Minimum of Months | 46381812.18 | 7395.64 | -5.7 | |
Maximum of Months | 0.191861E+11 | 124592.80 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.292236E+11 | 88867.52 | 16-JAN-17:51 | -1.7 |
February | 0.177306E+11 | 81699.69 | 06-FEB-04:51 | -4.4 |
March | 0.966266E+09 | 30099.76 | 04-MAR-06:00 | -1.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.711885E+09 | 23250.10 | 28-NOV-04:53 | -1.1 |
December | 0.265304E+11 | 89094.67 | 14-DEC-03:51 | -1.1 |
Annual Sum or Average | 0.751627E+11 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.292236E+11 | 89094.67 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.258145E+10 | 1955.04 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.235440E+10 | 1955.04 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.269003E+10 | 1955.04 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.254196E+10 | 1955.04 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.263574E+10 | 1955.04 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.259625E+10 | 1955.04 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.258145E+10 | 1955.04 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.269003E+10 | 1955.04 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.254196E+10 | 1955.04 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.258145E+10 | 1955.04 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.248766E+10 | 1955.04 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.258145E+10 | 1955.04 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.308638E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.235440E+10 | 1955.04 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.269003E+10 | 1955.04 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.198922E+11 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.182065E+11 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.210336E+11 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.197108E+11 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.204629E+11 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.202815E+11 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.198922E+11 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.210336E+11 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.197108E+11 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.198922E+11 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.191400E+11 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.198922E+11 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.239148E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.182065E+11 | 17848.24 | 0.00 | 0.00 | |
Maximum of Months | 0.210336E+11 | 17848.24 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.294120E+11 | 26389.90 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.269196E+11 | 26389.90 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.310997E+11 | 26389.90 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.291438E+11 | 26389.90 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.302559E+11 | 26389.90 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.299876E+11 | 26389.90 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.294120E+11 | 26389.90 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.310997E+11 | 26389.90 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.291438E+11 | 26389.90 | 01-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.294120E+11 | 26389.90 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.282999E+11 | 26389.90 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.294120E+11 | 26389.90 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.353598E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.269196E+11 | 26389.90 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.310997E+11 | 26389.90 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409611E+10 |
February | 0.127628E+10 | 0.235440E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365524E+10 |
March | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347183E+10 |
April | 0.138726E+10 | 0.254196E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27674360.35 | 0.224929E+10 |
May | 0.144276E+10 | 0.263574E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145965E+09 | 0.177172E+10 |
June | 0.144276E+10 | 0.259625E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776985E+09 | 0.780390E+09 |
July | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.886797E+09 | 0.302068E+09 |
August | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627839E+09 | 0.521859E+09 |
September | 0.138726E+10 | 0.254196E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234364E+09 | 0.948246E+09 |
October | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49220447.37 | 0.218327E+10 |
November | 0.133177E+10 | 0.248766E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323984E+10 |
December | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392060E+10 |
Annual Sum or Average | 0.168137E+11 | 0.308638E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274884E+10 | 0.271405E+11 |
Minimum of Months | 0.127628E+10 | 0.235440E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302068E+09 |
Maximum of Months | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.886797E+09 | 0.409611E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127462E+11 |
February | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122086E+11 |
March | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120574E+11 |
April | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.921999E+10 |
May | 0.339505E+10 | 0.204629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152074E+09 | 0.798726E+10 |
June | 0.339505E+10 | 0.202815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143853E+10 | 0.431762E+10 |
July | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186503E+10 | 0.250313E+10 |
August | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961577E+09 | 0.357572E+10 |
September | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209507E+09 | 0.481573E+10 |
October | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11388571.09 | 0.810398E+10 |
November | 0.313390E+10 | 0.191400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102381E+11 |
December | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114068E+11 |
Annual Sum or Average | 0.395654E+11 | 0.239148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463811E+10 | 0.991805E+11 |
Minimum of Months | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250313E+10 |
Maximum of Months | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186503E+10 | 0.127462E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39885348.86 | 0.287031E+11 |
February | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179313E+09 | 0.279024E+11 |
March | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290692E+09 | 0.273483E+11 |
April | 0.750829E+10 | 0.291438E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282936E+09 | 0.255321E+11 |
May | 0.780862E+10 | 0.302559E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119698E+09 | 0.298812E+11 |
June | 0.780862E+10 | 0.299876E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95976016.24 | 0.206361E+11 |
July | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103331E+09 | 0.155599E+11 |
August | 0.810895E+10 | 0.310997E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10397681.89 | 0.199763E+11 |
September | 0.750829E+10 | 0.291438E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1662979.00 | 0.221409E+11 |
October | 0.750829E+10 | 0.294120E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47754368.90 | 0.283947E+11 |
November | 0.720796E+10 | 0.282999E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 185663.41 | 0.253471E+11 |
December | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1117633.07 | 0.266754E+11 |
Annual Sum or Average | 0.910005E+11 | 0.353598E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117295E+10 | 0.298097E+12 |
Minimum of Months | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 185663.41 | 0.155599E+11 |
Maximum of Months | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290692E+09 | 0.298812E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1955.04 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 13270.99 | 17-JAN-08:00 |
February | 1680.92 | 01-FEB-08:09 | 1955.04 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 11632.03 | 06-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 1955.04 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 10345.33 | 14-MAR-07:00 |
April | 1680.92 | 01-APR-07:10 | 1955.04 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 864.63 | 13-APR-17:00 | 7105.43 | 06-APR-06:25 |
May | 1680.92 | 01-MAY-07:10 | 1955.04 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2820.11 | 19-MAY-17:00 | 7554.25 | 05-MAY-07:00 |
June | 1680.92 | 01-JUN-07:10 | 1955.04 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4985.86 | 28-JUN-16:10 | 5278.29 | 09-JUN-06:03 |
July | 1680.92 | 01-JUL-07:10 | 1955.04 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4825.12 | 21-JUL-17:00 | 2126.79 | 28-JUL-06:03 |
August | 1680.92 | 01-AUG-07:10 | 1955.04 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4010.39 | 01-AUG-16:10 | 3726.99 | 31-AUG-06:03 |
September | 1680.92 | 01-SEP-07:10 | 1955.04 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2603.84 | 20-SEP-17:00 | 4454.02 | 27-SEP-06:03 |
October | 1680.92 | 02-OCT-07:10 | 1955.04 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.04 | 06-OCT-16:10 | 10323.47 | 24-OCT-17:00 |
November | 1680.92 | 01-NOV-07:10 | 1955.04 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 9227.87 | 27-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1955.04 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 11625.81 | 22-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2126.79 | |||||
Maximum of Months | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 4985.86 | 13270.99 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 26490.06 | 16-JAN-17:54 |
February | 3955.50 | 01-FEB-08:09 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 21057.85 | 05-FEB-01:03 |
March | 3955.50 | 01-MAR-08:09 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 21682.78 | 14-MAR-07:00 |
April | 3955.50 | 01-APR-07:10 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 30926.54 | 15-APR-15:02 |
May | 3955.50 | 01-MAY-07:10 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3807.72 | 19-MAY-15:10 | 19538.49 | 05-MAY-08:00 |
June | 3955.50 | 01-JUN-07:10 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9674.45 | 17-JUN-16:00 | 12591.22 | 01-JUN-17:00 |
July | 3955.50 | 01-JUL-07:10 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8713.01 | 04-JUL-14:56 | 7104.29 | 15-JUL-18:53 |
August | 3955.50 | 01-AUG-07:10 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5569.48 | 02-AUG-17:00 | 7619.63 | 25-AUG-19:55 |
September | 3955.50 | 01-SEP-07:10 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3659.40 | 03-SEP-17:00 | 9738.22 | 08-SEP-08:00 |
October | 3955.50 | 02-OCT-07:10 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1636.76 | 01-OCT-17:00 | 28120.22 | 24-OCT-15:02 |
November | 3955.50 | 01-NOV-07:10 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 22145.58 | 01-NOV-15:03 |
December | 3955.50 | 01-DEC-08:09 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 27954.61 | 14-DEC-03:54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7104.29 | ||||
Maximum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9674.45 | 30926.54 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 26389.90 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4016.48 | 01-JAN-15:00 | 60149.65 | 17-JAN-08:70 |
February | 9097.65 | 01-FEB-08:09 | 26389.90 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8094.33 | 14-FEB-17:00 | 47703.56 | 05-FEB-01:23 |
March | 9097.65 | 01-MAR-08:09 | 26389.90 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9714.97 | 08-MAR-17:00 | 52443.80 | 21-MAR-10:55 |
April | 9097.65 | 01-APR-07:10 | 26389.90 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8814.56 | 01-APR-17:00 | 80913.40 | 15-APR-12:05 |
May | 9097.65 | 01-MAY-07:10 | 26389.90 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4544.48 | 07-MAY-18:00 | 58095.66 | 05-MAY-08:00 |
June | 9097.65 | 01-JUN-07:10 | 26389.90 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1719.06 | 12-JUN-16:00 | 38775.29 | 08-JUN-12:10 |
July | 9097.65 | 01-JUL-07:10 | 26389.90 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2868.10 | 04-JUL-16:52 | 30976.94 | 15-JUL-18:53 |
August | 9097.65 | 01-AUG-07:10 | 26389.90 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 630.76 | 20-AUG-17:20 | 34650.13 | 22-AUG-20:55 |
September | 9097.65 | 01-SEP-07:10 | 26389.90 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 734.18 | 03-SEP-13:55 | 38525.23 | 07-SEP-15:00 |
October | 9097.65 | 02-OCT-07:10 | 26389.90 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5977.43 | 31-OCT-15:00 | 77222.95 | 24-OCT-15:00 |
November | 9097.65 | 01-NOV-07:10 | 26389.90 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.44 | 09-NOV-14:00 | 43501.45 | 03-NOV-21:00 |
December | 9097.65 | 01-DEC-08:09 | 26389.90 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 986.04 | 24-DEC-15:00 | 61956.69 | 14-DEC-03:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 309.44 | 30976.94 | |||||
Maximum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 9714.97 | 80913.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 704.30 | 05-JAN-16:00 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 576.72 |
February | 3226.08 | 15-FEB-16:00 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.99 |
March | 3339.42 | 08-MAR-16:30 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.59 |
April | 24195.28 | 29-APR-19:21 | 0.00 | 4570.22 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.54 |
May | 26173.50 | 14-MAY-23:02 | 0.00 | 2742.13 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.25 |
June | 28279.59 | 11-JUN-23:01 | 0.00 | 3199.16 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.03 |
July | 26403.57 | 23-JUL-23:01 | 0.00 | 4570.22 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.53 |
August | 26416.83 | 06-AUG-23:01 | 0.00 | 4570.22 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.18 |
September | 26224.93 | 10-SEP-23:01 | 0.00 | 3656.18 | 4590.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.07 |
October | 26513.49 | 01-OCT-23:01 | 0.00 | 3656.18 | 4590.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.40 |
November | 3910.52 | 02-NOV-15:00 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 526.46 |
December | 1515.79 | 02-DEC-15:30 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 704.30 | 0.00 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.54 | |
Maximum of Months | 28279.59 | 1680.92 | 4570.22 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 576.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 4199.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5751.20 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8456.04 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2099.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1683.35 |
April | 71028.89 | 29-APR-17:33 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 990.96 |
May | 80290.19 | 26-MAY-17:41 | 0.00 | 14698.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1366.40 |
June | 81189.61 | 04-JUN-11:21 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 555.64 |
July | 81851.26 | 22-JUL-00:31 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 923.65 |
August | 82213.21 | 05-AUG-21:41 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1041.36 |
September | 82848.49 | 17-SEP-12:01 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1303.18 |
October | 79746.38 | 01-OCT-11:01 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.26 |
November | 1068.52 | 02-NOV-14:20 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1565.63 |
December | 599.15 | 21-DEC-08:55 | 7911.00 | 31496.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 2099.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 82848.49 | 7911.00 | 31496.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8456.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 6209.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11655.74 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 12418.78 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20276.49 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3764.58 |
April | 0.00 | 01-APR-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5944.85 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13055.47 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13368.14 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 6209.39 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10565.82 |
August | 0.00 | 01-AUG-00:03 | 0.00 | 12418.78 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8600.15 |
September | 0.00 | 01-SEP-00:03 | 0.00 | 9314.08 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9868.72 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8893.48 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3429.72 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4616.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3429.72 | |
Maximum of Months | 0.00 | 0.00 | 12418.78 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20276.49 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.908151E+11 | 68634.82 | 17-JAN-11:09 | 0.730473E+11 | 183957.76 | 16-JAN-17:00 |
February | 0.819110E+11 | 69149.45 | 14-FEB-15:00 | 0.497133E+11 | 164062.99 | 06-FEB-04:49 |
March | 0.922812E+11 | 69373.08 | 08-MAR-15:00 | 0.163768E+11 | 89872.86 | 04-MAR-06:10 |
April | 0.864537E+11 | 76463.86 | 28-APR-14:50 | 0.101817E+11 | 18289.41 | 08-APR-05:10 |
May | 0.918139E+11 | 85202.44 | 19-MAY-14:00 | 0.101472E+11 | 11897.63 | 05-MAY-06:10 |
June | 0.101390E+12 | 95508.55 | 28-JUN-14:00 | 0.973002E+10 | 9203.29 | 07-JUN-05:49 |
July | 0.106267E+12 | 95625.95 | 22-JUL-14:50 | 0.100450E+11 | 4674.19 | 19-JUL-05:10 |
August | 0.108420E+12 | 91024.42 | 01-AUG-14:00 | 0.100481E+11 | 5910.88 | 19-AUG-05:10 |
September | 0.948320E+11 | 87862.60 | 02-SEP-14:00 | 0.972357E+10 | 7368.13 | 15-SEP-05:40 |
October | 0.901319E+11 | 84085.77 | 06-OCT-14:00 | 0.105825E+11 | 23614.07 | 26-OCT-05:30 |
November | 0.858127E+11 | 71481.78 | 30-NOV-16:00 | 0.162501E+11 | 74947.71 | 27-NOV-06:10 |
December | 0.908986E+11 | 71486.68 | 29-DEC-16:00 | 0.670608E+11 | 179120.59 | 14-DEC-03:00 |
Annual Sum or Average | 0.112103E+13 | 0.292906E+12 | ||||
Minimum of Months | 0.819110E+11 | 68634.82 | 0.972357E+10 | 4674.19 | ||
Maximum of Months | 0.108420E+12 | 95625.95 | 0.730473E+11 | 183957.76 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.518856E+11 | 0.133615E+11 | 0.115358E+11 | 0.00 | 0.117319E+11 | 0.00 | 0.00 | 2.05 | 0.00 | 0.00 | 0.00 | 0.230040E+10 | 0.00 |
February | 0.474804E+11 | 0.113803E+11 | 0.105871E+11 | 0.00 | 0.103597E+11 | 0.00 | 0.00 | 7126483.74 | 0.00 | 0.00 | 0.00 | 0.209631E+10 | 0.00 |
March | 0.548234E+11 | 0.116055E+11 | 0.123431E+11 | 0.00 | 0.111529E+11 | 0.00 | 0.00 | 14709829.93 | 0.00 | 0.00 | 0.00 | 0.234163E+10 | 0.00 |
April | 0.513965E+11 | 0.102131E+11 | 0.114862E+11 | 0.00 | 0.101624E+11 | 0.00 | 0.00 | 0.101698E+10 | 0.00 | 0.00 | 0.00 | 0.217859E+10 | 0.00 |
May | 0.533545E+11 | 0.968578E+10 | 0.119357E+11 | 0.00 | 0.108182E+11 | 0.00 | 0.00 | 0.382531E+10 | 0.00 | 0.00 | 0.00 | 0.219430E+10 | 0.00 |
June | 0.528654E+11 | 0.891276E+10 | 0.118862E+11 | 0.00 | 0.131611E+11 | 0.00 | 0.00 | 0.124763E+11 | 0.00 | 0.00 | 0.00 | 0.208852E+10 | 0.00 |
July | 0.518856E+11 | 0.945029E+10 | 0.115358E+11 | 0.00 | 0.140779E+11 | 0.00 | 0.00 | 0.172422E+11 | 0.00 | 0.00 | 0.00 | 0.207544E+10 | 0.00 |
August | 0.548234E+11 | 0.101619E+11 | 0.123357E+11 | 0.00 | 0.139937E+11 | 0.00 | 0.00 | 0.149894E+11 | 0.00 | 0.00 | 0.00 | 0.211640E+10 | 0.00 |
September | 0.513965E+11 | 0.108018E+11 | 0.114788E+11 | 0.00 | 0.111483E+11 | 0.00 | 0.00 | 0.796225E+10 | 0.00 | 0.00 | 0.00 | 0.204437E+10 | 0.00 |
October | 0.518856E+11 | 0.121942E+11 | 0.115432E+11 | 0.00 | 0.102892E+11 | 0.00 | 0.00 | 0.207854E+10 | 0.00 | 0.00 | 0.00 | 0.214122E+10 | 0.00 |
November | 0.499276E+11 | 0.126908E+11 | 0.110862E+11 | 0.00 | 0.997678E+10 | 0.00 | 0.00 | 2079.75 | 0.00 | 0.00 | 0.00 | 0.213124E+10 | 0.00 |
December | 0.518856E+11 | 0.136072E+11 | 0.115358E+11 | 0.00 | 0.116038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226624E+10 | 0.00 |
Annual Sum or Average | 0.623610E+12 | 0.134065E+12 | 0.139290E+12 | 0.00 | 0.138476E+12 | 0.00 | 0.00 | 0.596128E+11 | 0.00 | 0.00 | 0.00 | 0.259746E+11 | 0.00 |
Minimum of Months | 0.474804E+11 | 0.891276E+10 | 0.105871E+11 | 0.00 | 0.997678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204437E+10 | 0.00 |
Maximum of Months | 0.548234E+11 | 0.136072E+11 | 0.123431E+11 | 0.00 | 0.140779E+11 | 0.00 | 0.00 | 0.172422E+11 | 0.00 | 0.00 | 0.00 | 0.234163E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.730473E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.497133E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.163768E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.101817E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.101472E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.973002E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.100450E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.100481E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.972357E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.105825E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.162501E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.670608E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.292906E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.972357E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.730473E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 46193.18 | 02-JAN-09:09 | 8532.22 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 10561.04 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 46193.18 | 01-FEB-09:09 | 8532.22 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 10561.04 | 01-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 46193.18 | 01-MAR-09:09 | 8532.22 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 10561.04 | 04-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 46193.18 | 01-APR-08:09 | 8532.22 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 10235.22 | 26-APR-16:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 46193.18 | 01-MAY-08:09 | 8532.22 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 12540.52 | 19-MAY-13:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 46193.18 | 01-JUN-08:09 | 8532.22 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 12540.52 | 06-JUN-14:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 46193.18 | 01-JUL-08:09 | 8532.22 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 12540.52 | 05-JUL-09:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 46193.18 | 01-AUG-08:09 | 8532.22 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 12540.52 | 01-AUG-12:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 46193.18 | 01-SEP-08:09 | 8532.22 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 12540.52 | 01-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 46193.18 | 02-OCT-08:09 | 8532.22 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 12540.52 | 06-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 46193.18 | 01-NOV-08:09 | 8532.22 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 10561.04 | 27-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 46193.18 | 01-DEC-09:09 | 8532.22 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 10561.04 | 05-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 46193.18 | 8532.22 | 10112.62 | 0.00 | 10235.22 | 0.00 | 0.00 | |||||
Maximum of Months | 46193.18 | 8532.22 | 10112.62 | 0.00 | 12540.52 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 05-JAN-14:00 | 0.00 | 0.00 | 0.00 | 2425.98 | 31-JAN-12:09 | 0.00 |
February | 795.53 | 14-FEB-15:00 | 0.00 | 0.00 | 0.00 | 2429.72 | 10-FEB-12:30 | 0.00 |
March | 1024.09 | 08-MAR-15:00 | 0.00 | 0.00 | 0.00 | 2387.54 | 02-MAR-12:39 | 0.00 |
April | 8146.21 | 28-APR-14:50 | 0.00 | 0.00 | 0.00 | 2202.08 | 01-APR-11:00 | 0.00 |
May | 15178.74 | 19-MAY-15:09 | 0.00 | 0.00 | 0.00 | 1814.79 | 01-MAY-11:00 | 0.00 |
June | 26105.83 | 28-JUN-15:00 | 0.00 | 0.00 | 0.00 | 1787.84 | 01-JUN-11:09 | 0.00 |
July | 26263.03 | 22-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1768.51 | 01-JUL-11:39 | 0.00 |
August | 21348.84 | 01-AUG-15:50 | 0.00 | 0.00 | 0.00 | 1762.21 | 31-AUG-11:30 | 0.00 |
September | 17338.54 | 02-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1777.32 | 30-SEP-11:30 | 0.00 |
October | 13492.47 | 06-OCT-14:00 | 0.00 | 0.00 | 0.00 | 1801.64 | 31-OCT-11:09 | 0.00 |
November | 0.55 | 13-NOV-16:10 | 0.00 | 0.00 | 0.00 | 2073.18 | 29-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2311.47 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1762.21 | 0.00 | ||
Maximum of Months | 26263.03 | 0.00 | 0.00 | 0.00 | 2429.72 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 68634.82 | 17-JAN-11:09 | 46193.18 | 10112.62 | 0.00 | 0.00 | 10561.04 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 69149.45 | 14-FEB-15:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 10235.22 | 0.00 | 0.00 | 795.53 | 0.00 |
March | 69373.08 | 08-MAR-15:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 10235.22 | 0.00 | 0.00 | 1024.09 | 0.00 |
April | 76463.86 | 28-APR-14:50 | 46193.18 | 10112.62 | 0.00 | 0.00 | 10235.22 | 0.00 | 0.00 | 8146.21 | 0.00 |
May | 85202.44 | 19-MAY-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 12540.52 | 0.00 | 0.00 | 14594.55 | 0.00 |
June | 95508.55 | 28-JUN-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 12540.52 | 0.00 | 0.00 | 24924.85 | 0.00 |
July | 95625.95 | 22-JUL-14:50 | 46193.18 | 10112.62 | 0.00 | 0.00 | 12540.52 | 0.00 | 0.00 | 25050.57 | 0.00 |
August | 91024.42 | 01-AUG-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 12540.52 | 0.00 | 0.00 | 20449.91 | 0.00 |
September | 87862.60 | 02-SEP-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 12540.52 | 0.00 | 0.00 | 17285.16 | 0.00 |
October | 84085.77 | 06-OCT-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 12540.52 | 0.00 | 0.00 | 13492.47 | 0.00 |
November | 71481.78 | 30-NOV-16:00 | 40988.70 | 10112.62 | 8532.22 | 0.00 | 10235.22 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71486.68 | 29-DEC-16:00 | 40988.70 | 10112.62 | 8532.22 | 0.00 | 10235.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 68634.82 | 40988.70 | 10112.62 | 0.00 | 0.00 | 10235.22 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 95625.95 | 46193.18 | 10112.62 | 8532.22 | 0.00 | 12540.52 | 0.00 | 0.00 | 25050.57 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 183957.76 | 16-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 164062.99 | 06-FEB-04:49 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 89872.86 | 04-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 18289.41 | 08-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 11897.63 | 05-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 9203.29 | 07-JUN-05:49 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 4674.19 | 19-JUL-05:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 5910.88 | 19-AUG-05:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 7368.13 | 15-SEP-05:40 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 23614.07 | 26-OCT-05:30 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 74947.71 | 27-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 179120.59 | 14-DEC-03:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 4674.19 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 183957.76 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.17 | 17.39 | 9.33 | 18.08 | 0.00 | 18.08 | 0.00 | 18.08 |
February | 14.00 | 17.42 | 8.17 | 18.11 | 0.00 | 18.11 | 0.00 | 18.11 |
March | 6.50 | 19.83 | 6.50 | 19.83 | 0.00 | 19.83 | 0.00 | 19.83 |
April | 1.67 | 20.30 | 1.67 | 20.30 | 2.50 | 22.11 | 0.00 | 22.11 |
May | 0.17 | 20.34 | 0.17 | 20.34 | 9.83 | 24.54 | 0.00 | 24.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 28.33 | 24.92 | 0.67 | 24.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 33.83 | 25.14 | 0.33 | 25.14 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 30.17 | 24.99 | 0.50 | 24.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 24.71 | 0.67 | 24.70 |
October | 0.83 | 20.14 | 0.83 | 20.14 | 3.17 | 23.06 | 0.00 | 23.06 |
November | 4.67 | 19.61 | 4.50 | 19.70 | 0.00 | 19.70 | 0.00 | 19.70 |
December | 11.83 | 18.37 | 9.67 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 |
Annual Sum or Average | 55.83 | 18.21 | 40.83 | 18.73 | 120.33 | 22.18 | 2.17 | 22.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.08 | 0.00 | 18.08 |
Maximum of Months | 16.17 | 20.34 | 9.67 | 20.34 | 33.83 | 25.14 | 0.67 | 25.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 76.50 | 14.48 | 5.83 | 14.48 | 0.00 | 14.48 | 0.00 | 14.48 |
February | 50.00 | 14.47 | 4.50 | 14.47 | 0.00 | 14.47 | 0.00 | 14.47 |
March | 8.50 | 14.67 | 0.83 | 14.65 | 0.00 | 14.65 | 0.00 | 14.65 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.39 | 0.00 | 27.39 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 27.75 | 0.00 | 27.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 28.50 | 27.83 | 0.00 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 27.75 | 0.00 | 27.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.63 | 0.00 | 27.63 |
October | 0.17 | 15.00 | 0.00 | 15.00 | 1.17 | 25.99 | 0.00 | 25.99 |
November | 12.83 | 14.64 | 1.67 | 14.65 | 0.00 | 14.65 | 0.00 | 14.65 |
December | 76.50 | 14.57 | 5.67 | 14.55 | 0.00 | 14.55 | 0.00 | 14.55 |
Annual Sum or Average | 224.50 | 14.53 | 18.50 | 14.52 | 74.50 | 17.62 | 0.00 | 17.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 76.50 | 15.00 | 5.83 | 15.00 | 28.50 | 27.83 | 0.00 | 27.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.48 | 243.17 | 21.32 | 243.17 | 21.25 |
February | 276.00 | 21.64 | 210.67 | 21.42 | 210.67 | 21.33 |
March | 324.00 | 22.30 | 151.33 | 21.94 | 151.33 | 21.76 |
April | 271.50 | 23.16 | 47.33 | 22.86 | 47.33 | 22.65 |
May | 161.33 | 23.35 | 46.17 | 23.37 | 7.83 | 23.29 |
June | 35.83 | 23.36 | 201.83 | 23.82 | 0.00 | 23.82 |
July | 26.00 | 23.40 | 282.17 | 23.86 | 18.83 | 23.87 |
August | 22.33 | 23.51 | 303.83 | 23.88 | 17.17 | 23.88 |
September | 36.83 | 23.75 | 214.67 | 23.88 | 6.83 | 23.88 |
October | 188.00 | 22.95 | 94.50 | 22.96 | 32.50 | 22.77 |
November | 286.17 | 22.32 | 127.83 | 21.97 | 127.83 | 21.78 |
December | 300.00 | 21.40 | 255.17 | 21.27 | 255.17 | 21.23 |
Annual Sum or Average | 2228.00 | 22.29 | 2178.67 | 22.41 | 1118.67 | 22.18 |
Minimum of Months | 22.33 | 21.40 | 46.17 | 21.27 | 0.00 | 21.23 |
Maximum of Months | 324.00 | 23.75 | 303.83 | 23.88 | 255.17 | 23.88 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 18.97 | 257.83 | 18.69 | 257.83 | 18.59 |
February | 269.33 | 19.62 | 212.00 | 19.17 | 210.50 | 18.99 |
March | 290.33 | 21.10 | 148.33 | 20.32 | 143.33 | 19.88 |
April | 124.17 | 22.11 | 183.83 | 23.73 | 46.50 | 23.16 |
May | 91.50 | 23.78 | 234.83 | 25.61 | 37.17 | 25.50 |
June | 192.83 | 26.45 | 290.33 | 26.56 | 179.50 | 26.60 |
July | 262.50 | 26.68 | 300.00 | 26.66 | 262.50 | 26.67 |
August | 271.00 | 26.68 | 323.00 | 26.64 | 271.00 | 26.65 |
September | 207.00 | 26.48 | 278.00 | 26.55 | 193.00 | 26.59 |
October | 156.00 | 23.20 | 209.17 | 24.26 | 88.67 | 24.01 |
November | 272.17 | 21.20 | 143.17 | 20.59 | 133.17 | 20.19 |
December | 300.00 | 18.89 | 278.83 | 18.75 | 278.83 | 18.70 |
Annual Sum or Average | 2736.83 | 22.62 | 2859.33 | 23.06 | 2102.00 | 22.87 |
Minimum of Months | 91.50 | 18.89 | 143.17 | 18.69 | 37.17 | 18.59 |
Maximum of Months | 300.00 | 26.68 | 323.00 | 26.66 | 278.83 | 26.67 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 12.43 | 300.00 | 12.43 | 300.00 | 12.43 |
February | 276.00 | 13.31 | 276.00 | 13.31 | 276.00 | 13.31 |
March | 324.00 | 16.11 | 324.00 | 16.11 | 324.00 | 16.11 |
April | 262.00 | 20.67 | 169.17 | 20.32 | 149.33 | 19.95 |
May | 207.50 | 24.93 | 200.83 | 25.66 | 126.00 | 25.86 |
June | 254.83 | 30.41 | 296.83 | 30.12 | 246.00 | 30.30 |
July | 300.00 | 30.94 | 300.00 | 30.94 | 300.00 | 30.94 |
August | 317.67 | 30.04 | 324.00 | 30.00 | 317.67 | 30.01 |
September | 226.83 | 29.00 | 289.00 | 28.63 | 225.50 | 28.76 |
October | 236.00 | 22.52 | 198.00 | 22.76 | 161.67 | 22.67 |
November | 288.00 | 16.02 | 284.83 | 15.99 | 284.83 | 15.98 |
December | 300.00 | 12.36 | 300.00 | 12.36 | 300.00 | 12.36 |
Annual Sum or Average | 3292.83 | 21.26 | 3262.67 | 21.38 | 3011.00 | 21.29 |
Minimum of Months | 207.50 | 12.36 | 169.17 | 12.36 | 126.00 | 12.36 |
Maximum of Months | 324.00 | 30.94 | 324.00 | 30.94 | 324.00 | 30.94 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 7.36 | 2.05 | 0.33 | 7.36 | -0.0 | 0.00 | 0.00 | 05-JAN-15:00 | 0.00 | 01-JAN-00:05 | 0.01 | 05-JAN-15:00 | 0.01 | 05-JAN-15:00 | 0.00 | 14-JAN-15:40 | 0.00 | 05-JAN-15:00 | 0.00 | 01-JAN-00:05 |
February | 25946787.90 | 7126483.74 | 7.00 | 25946787.90 | 0.00 | 0.00 | 0.14 | 14-FEB-16:00 | 0.00 | 01-FEB-00:03 | 2918.63 | 14-FEB-16:00 | 2918.63 | 14-FEB-16:00 | 0.00 | 14-FEB-16:00 | 795.53 | 14-FEB-16:00 | 0.00 | 01-FEB-00:03 |
March | 53809370.63 | 14699720.57 | 18.92 | 53809370.63 | 0.00 | 0.00 | 0.18 | 08-MAR-16:00 | 0.00 | 01-MAR-00:10 | 3778.08 | 08-MAR-16:00 | 3778.08 | 08-MAR-16:00 | 0.00 | 08-MAR-15:30 | 1023.31 | 08-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.168703E+10 | 0.447790E+09 | 98.34 | 0.168703E+10 | -0.0 | 0.00 | 1.00 | 01-APR-17:13 | 0.00 | 01-APR-00:10 | 23418.35 | 12-APR-17:55 | 23418.35 | 27-APR-17:18 | 0.00 | 12-APR-17:55 | 5577.20 | 26-APR-17:43 | 0.00 | 01-APR-00:10 |
May | 0.420116E+10 | 0.113534E+10 | 196.21 | 0.417975E+10 | 21405733.58 | 0.00 | 1.00 | 02-MAY-17:11 | 0.00 | 01-MAY-00:10 | 24798.17 | 21-MAY-23:02 | 23965.27 | 27-MAY-17:41 | 3565.29 | 22-MAY-00:55 | 5940.56 | 19-MAY-17:06 | 0.00 | 01-MAY-00:10 |
June | 0.104560E+11 | 0.302486E+10 | 348.10 | 0.102545E+11 | 0.201557E+09 | 0.00 | 1.00 | 02-JUN-17:11 | 0.00 | 01-JUN-00:20 | 25976.27 | 24-JUN-00:25 | 24274.82 | 25-JUN-23:01 | 6112.98 | 24-JUN-05:55 | 6576.82 | 27-JUN-17:05 | 0.00 | 01-JUN-00:10 |
July | 0.146051E+11 | 0.411993E+10 | 406.30 | 0.129355E+11 | 0.166966E+10 | 0.00 | 1.00 | 01-JUL-00:05 | 0.00 | 01-JUL-00:10 | 27956.08 | 01-JUL-17:11 | 24423.53 | 04-JUL-23:04 | 13815.31 | 01-JUL-02:55 | 6595.82 | 21-JUL-17:04 | 0.00 | 01-JUL-00:05 |
August | 0.138288E+11 | 0.380741E+10 | 405.55 | 0.122576E+11 | 0.157118E+10 | 0.00 | 1.00 | 01-AUG-00:11 | 0.00 | 01-AUG-00:03 | 27533.20 | 13-AUG-23:01 | 25651.91 | 13-AUG-17:45 | 11957.00 | 14-AUG-05:15 | 6735.15 | 13-AUG-15:05 | 0.00 | 01-AUG-00:03 |
September | 0.814823E+10 | 0.219761E+10 | 289.02 | 0.758485E+10 | 0.563382E+09 | 0.00 | 1.00 | 01-SEP-00:31 | 0.00 | 01-SEP-00:03 | 25916.59 | 23-SEP-17:15 | 24235.52 | 02-SEP-20:23 | 9799.59 | 05-SEP-03:45 | 6289.81 | 02-SEP-17:05 | 0.00 | 01-SEP-00:03 |
October | 0.272421E+10 | 0.723798E+09 | 127.15 | 0.259408E+10 | 0.130126E+09 | 0.00 | 1.00 | 01-OCT-23:01 | 0.00 | 01-OCT-00:10 | 26182.99 | 02-OCT-17:11 | 24008.30 | 03-OCT-17:15 | 8514.00 | 02-OCT-17:16 | 6179.39 | 02-OCT-17:11 | 0.00 | 01-OCT-00:10 |
November | 2395.63 | 667.33 | 2.22 | 2395.63 | -0.0 | 0.00 | 0.00 | 13-NOV-16:10 | 0.00 | 01-NOV-00:10 | 1.97 | 13-NOV-16:10 | 1.97 | 13-NOV-16:10 | 0.00 | 03-NOV-09:50 | 0.55 | 13-NOV-16:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.557303E+11 | 0.154786E+11 | 1899.15 | 0.515730E+11 | 0.415731E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.146051E+11 | 0.411993E+10 | 406.30 | 0.129355E+11 | 0.166966E+10 | 0.00 | 1.00 | 0.00 | 27956.08 | 25651.91 | 13815.31 | 6735.15 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 33528.44 | 10109.36 | 4.17 | 33528.44 | -0.0 | 0.00 | 0.00 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 | 3.66 | 08-MAR-14:00 | 3.66 | 08-MAR-14:00 | 0.00 | 08-MAR-14:30 | 1.10 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.191482E+10 | 0.569185E+09 | 78.79 | 0.191482E+10 | 0.00 | 0.00 | 1.00 | 29-APR-17:33 | 0.00 | 01-APR-00:10 | 78658.55 | 29-APR-17:33 | 78658.55 | 29-APR-17:33 | 0.00 | 13-APR-14:10 | 20312.58 | 29-APR-17:33 | 0.00 | 01-APR-00:10 |
May | 0.899657E+10 | 0.268997E+10 | 144.63 | 0.899294E+10 | 3631041.32 | 0.00 | 1.00 | 09-MAY-17:15 | 0.00 | 01-MAY-00:10 | 84174.62 | 28-MAY-12:05 | 83820.05 | 28-MAY-13:01 | 7684.80 | 28-MAY-10:55 | 22477.24 | 21-MAY-16:25 | 0.00 | 01-MAY-00:10 |
June | 0.294075E+11 | 0.945140E+10 | 289.02 | 0.292709E+11 | 0.136603E+09 | 0.00 | 1.00 | 03-JUN-17:43 | 0.00 | 01-JUN-00:10 | 86479.26 | 23-JUN-22:23 | 85142.31 | 23-JUN-21:30 | 6872.73 | 25-JUN-07:42 | 25568.01 | 25-JUN-15:42 | 0.00 | 01-JUN-00:10 |
July | 0.419491E+11 | 0.131222E+11 | 355.03 | 0.398748E+11 | 0.207436E+10 | 0.00 | 1.00 | 01-JUL-17:11 | 0.00 | 01-JUL-00:05 | 95794.75 | 01-JUL-17:11 | 86143.78 | 13-JUL-18:23 | 36424.24 | 01-JUL-17:11 | 26095.53 | 23-JUL-14:02 | 0.00 | 01-JUL-00:05 |
August | 0.366806E+11 | 0.111820E+11 | 326.68 | 0.347948E+11 | 0.188579E+10 | 0.00 | 1.00 | 01-AUG-17:05 | 0.00 | 01-AUG-00:03 | 94147.26 | 13-AUG-09:01 | 85687.31 | 03-AUG-18:23 | 35364.77 | 13-AUG-08:63 | 25463.99 | 20-AUG-14:52 | 0.00 | 01-AUG-00:03 |
September | 0.193259E+11 | 0.576464E+10 | 212.64 | 0.188019E+11 | 0.524059E+09 | 0.00 | 1.00 | 01-SEP-17:11 | 0.00 | 01-SEP-00:03 | 89570.68 | 04-SEP-10:23 | 85169.27 | 03-SEP-16:55 | 20249.59 | 10-SEP-10:35 | 24629.89 | 03-SEP-13:32 | 0.00 | 01-SEP-00:03 |
October | 0.457972E+10 | 0.135474E+10 | 83.37 | 0.454267E+10 | 37054802.40 | 0.00 | 1.00 | 01-OCT-10:05 | 0.00 | 01-OCT-00:10 | 83743.77 | 01-OCT-11:41 | 83743.77 | 01-OCT-11:41 | 1787.65 | 11-OCT-11:00 | 22698.40 | 01-OCT-12:55 | 0.00 | 01-OCT-00:10 |
November | 4679.07 | 1412.42 | 1.67 | 4679.07 | -0.0 | 0.00 | 0.00 | 02-NOV-15:00 | 0.00 | 01-NOV-00:10 | 0.98 | 02-NOV-15:00 | 0.98 | 02-NOV-15:00 | 0.00 | 02-NOV-13:50 | 0.30 | 02-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.142854E+12 | 0.441342E+11 | 1495.98 | 0.138193E+12 | 0.466150E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.419491E+11 | 0.131222E+11 | 355.03 | 0.398748E+11 | 0.207436E+10 | 0.00 | 1.00 | 0.00 | 95794.75 | 86143.78 | 36424.24 | 26095.53 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 122.42 | 69.76 | 52.66 | 115.70 | 165.25 | 0.00 | 0.00 | 0.00 |
February | 157.18 | 90.62 | 66.56 | 160.55 | 147.27 | 0.00 | 0.00 | 0.00 |
March | 176.27 | 93.85 | 82.42 | 191.07 | 115.52 | 0.00 | 0.00 | 0.00 |
April | 224.57 | 119.35 | 105.22 | 257.27 | 86.60 | 0.00 | 0.00 | 0.00 |
May | 214.03 | 110.59 | 103.44 | 258.21 | 70.66 | 0.00 | 0.00 | 0.00 |
June | 228.15 | 127.14 | 101.01 | 316.86 | 50.52 | 0.00 | 0.00 | 0.00 |
July | 206.16 | 100.90 | 105.26 | 300.05 | 33.83 | 0.00 | 0.00 | 0.00 |
August | 210.42 | 97.15 | 113.27 | 293.87 | 39.03 | 0.00 | 0.00 | 0.00 |
September | 190.92 | 100.78 | 90.14 | 247.77 | 67.07 | 0.00 | 0.00 | 0.00 |
October | 173.92 | 108.04 | 65.89 | 199.22 | 111.49 | 0.00 | 0.00 | 0.00 |
November | 136.43 | 80.17 | 56.27 | 133.93 | 135.23 | 0.00 | 0.00 | 0.00 |
December | 118.02 | 73.94 | 44.07 | 108.06 | 172.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 179.89 | 97.65 | 82.25 | 215.40 | 99.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 118.02 | 69.76 | 44.07 | 108.06 | 33.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 228.15 | 127.14 | 113.27 | 316.86 | 172.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 122.42 | 69.76 | 52.66 | 115.70 | 165.25 | 0.00 | 0.00 | 0.00 |
February | 157.18 | 90.62 | 66.56 | 160.55 | 147.27 | 0.00 | 0.00 | 0.00 |
March | 176.27 | 93.85 | 82.42 | 191.07 | 115.52 | 0.00 | 0.00 | 0.00 |
April | 224.57 | 119.35 | 105.22 | 257.27 | 86.60 | 0.00 | 0.00 | 0.00 |
May | 214.03 | 110.59 | 103.44 | 258.21 | 70.66 | 0.00 | 0.00 | 0.00 |
June | 228.15 | 127.14 | 101.01 | 316.86 | 50.52 | 0.00 | 0.00 | 0.00 |
July | 206.16 | 100.90 | 105.26 | 300.05 | 33.83 | 0.00 | 0.00 | 0.00 |
August | 210.42 | 97.15 | 113.27 | 293.87 | 39.03 | 0.00 | 0.00 | 0.00 |
September | 190.92 | 100.78 | 90.14 | 247.77 | 67.07 | 0.00 | 0.00 | 0.00 |
October | 173.92 | 108.04 | 65.89 | 199.22 | 111.49 | 0.00 | 0.00 | 0.00 |
November | 136.43 | 80.17 | 56.27 | 133.93 | 135.23 | 0.00 | 0.00 | 0.00 |
December | 118.02 | 73.94 | 44.07 | 108.06 | 172.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 179.89 | 97.65 | 82.25 | 215.40 | 99.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 118.02 | 69.76 | 44.07 | 108.06 | 33.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 228.15 | 127.14 | 113.27 | 316.86 | 172.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.03 | 0.00 | 25.03 | 4.66 | 101.65 | 0.00 | 0.00 | 0.00 |
February | 31.28 | 0.00 | 31.28 | 10.57 | 89.93 | 0.00 | 0.00 | 0.00 |
March | 39.47 | 0.00 | 39.47 | 23.89 | 69.44 | 0.00 | 0.00 | 0.00 |
April | 50.17 | 0.52 | 49.64 | 36.61 | 50.37 | 0.00 | 0.00 | 0.00 |
May | 54.55 | 3.61 | 50.94 | 50.45 | 39.16 | 0.00 | 0.00 | 0.00 |
June | 61.86 | 10.16 | 51.70 | 83.57 | 26.80 | 0.00 | 0.00 | 0.00 |
July | 56.64 | 4.60 | 52.04 | 83.83 | 18.52 | 0.00 | 0.00 | 0.00 |
August | 52.86 | 1.38 | 51.48 | 69.54 | 21.44 | 0.00 | 0.00 | 0.00 |
September | 42.14 | 0.03 | 42.11 | 44.51 | 39.30 | 0.00 | 0.00 | 0.00 |
October | 31.42 | 0.00 | 31.42 | 17.79 | 67.18 | 0.00 | 0.00 | 0.00 |
November | 26.68 | 0.00 | 26.68 | 5.71 | 83.94 | 0.00 | 0.00 | 0.00 |
December | 21.30 | 0.00 | 21.30 | 1.15 | 108.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.15 | 1.69 | 39.46 | 36.16 | 59.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 21.30 | 0.00 | 21.30 | 1.15 | 18.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.86 | 10.16 | 52.04 | 83.83 | 108.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.03 | 0.00 | 25.03 | 4.66 | 101.65 | 0.00 | 0.00 | 0.00 |
February | 31.28 | 0.00 | 31.28 | 10.57 | 89.93 | 0.00 | 0.00 | 0.00 |
March | 39.47 | 0.00 | 39.47 | 23.88 | 69.44 | 0.00 | 0.00 | 0.00 |
April | 50.17 | 0.52 | 49.64 | 36.61 | 50.37 | 0.00 | 0.00 | 0.00 |
May | 54.55 | 3.61 | 50.94 | 50.45 | 39.16 | 0.00 | 0.00 | 0.00 |
June | 61.86 | 10.16 | 51.70 | 83.57 | 26.80 | 0.00 | 0.00 | 0.00 |
July | 56.63 | 4.60 | 52.03 | 83.83 | 18.51 | 0.00 | 0.00 | 0.00 |
August | 52.85 | 1.38 | 51.48 | 69.54 | 21.44 | 0.00 | 0.00 | 0.00 |
September | 42.14 | 0.03 | 42.11 | 44.50 | 39.30 | 0.00 | 0.00 | 0.00 |
October | 31.42 | 0.00 | 31.42 | 17.79 | 67.18 | 0.00 | 0.00 | 0.00 |
November | 26.68 | 0.00 | 26.68 | 5.71 | 83.94 | 0.00 | 0.00 | 0.00 |
December | 21.30 | 0.00 | 21.30 | 1.15 | 108.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.15 | 1.69 | 39.46 | 36.16 | 59.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 21.30 | 0.00 | 21.30 | 1.15 | 18.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.86 | 10.16 | 52.03 | 83.83 | 108.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 73.50 | 91.84 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 104.56 | 81.94 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 141.58 | 68.92 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 190.78 | 65.65 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 207.33 | 64.58 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 226.89 | 60.71 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 225.59 | 52.35 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 208.07 | 53.22 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 164.22 | 69.04 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 115.58 | 85.36 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 79.01 | 80.31 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 61.79 | 94.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 150.11 | 72.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 61.79 | 52.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 226.89 | 94.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 73.50 | 91.84 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 104.56 | 81.94 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 141.58 | 68.92 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 190.78 | 65.65 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 207.33 | 64.58 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 226.89 | 60.71 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 225.59 | 52.35 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 208.07 | 53.22 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 164.22 | 69.04 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 115.58 | 85.36 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 79.01 | 80.31 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 61.79 | 94.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 150.11 | 72.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 61.79 | 52.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 226.89 | 94.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 73.50 | 91.84 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 104.56 | 81.94 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 141.58 | 68.92 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 190.78 | 65.65 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 207.33 | 64.58 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 226.89 | 60.71 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 225.59 | 52.35 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 208.07 | 53.22 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 164.22 | 69.04 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 115.58 | 85.36 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 79.01 | 80.31 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 61.79 | 94.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 150.11 | 72.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 61.79 | 52.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 226.89 | 94.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 73.50 | 91.84 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 104.56 | 81.94 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 141.58 | 68.92 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 190.78 | 65.65 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 207.33 | 64.58 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 226.89 | 60.71 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 225.59 | 52.35 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 208.07 | 53.22 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 164.22 | 69.04 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 115.58 | 85.36 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 79.01 | 80.31 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 61.79 | 94.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 150.11 | 72.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 61.79 | 52.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 226.89 | 94.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 73.50 | 91.84 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 104.56 | 81.94 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 141.58 | 68.92 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 190.78 | 65.65 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 207.33 | 64.58 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 226.89 | 60.71 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 225.59 | 52.35 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 208.07 | 53.22 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 164.22 | 69.04 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 115.58 | 85.36 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 79.01 | 80.31 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 61.79 | 94.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 150.11 | 72.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 61.79 | 52.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 226.89 | 94.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 73.50 | 91.84 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 104.56 | 81.94 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 141.58 | 68.92 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 190.78 | 65.65 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 207.33 | 64.58 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 226.89 | 60.71 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 225.59 | 52.35 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 208.07 | 53.22 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 164.22 | 69.04 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 115.58 | 85.36 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 79.01 | 80.31 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 61.79 | 94.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 150.11 | 72.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 61.79 | 52.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 226.89 | 94.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 73.50 | 91.84 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 104.56 | 81.94 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 141.58 | 68.92 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 190.78 | 65.65 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 207.33 | 64.58 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 226.89 | 60.71 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 225.59 | 52.35 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 208.07 | 53.22 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 164.22 | 69.04 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 115.58 | 85.36 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 79.01 | 80.31 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 61.79 | 94.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 150.11 | 72.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 61.79 | 52.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 226.89 | 94.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 73.50 | 91.84 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 104.56 | 81.94 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 141.58 | 68.92 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 190.78 | 65.65 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 207.33 | 64.58 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 226.89 | 60.71 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 225.59 | 52.35 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 208.07 | 53.22 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 164.22 | 69.04 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 115.58 | 85.36 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 79.01 | 80.31 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 61.79 | 94.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 150.11 | 72.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 61.79 | 52.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 226.89 | 94.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 73.50 | 91.84 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 104.56 | 81.94 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 141.58 | 68.92 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 190.78 | 65.65 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 207.33 | 64.58 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 226.89 | 60.71 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 225.59 | 52.35 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 208.07 | 53.22 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 164.22 | 69.04 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 115.58 | 85.36 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 79.01 | 80.31 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 61.79 | 94.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 150.11 | 72.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 61.79 | 52.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 226.89 | 94.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.21 | 43.32 | 19.89 | 73.50 | 91.84 | 0.00 | 0.00 | 0.00 |
February | 85.39 | 60.76 | 24.63 | 104.56 | 81.94 | 0.00 | 0.00 | 0.00 |
March | 110.60 | 76.68 | 33.92 | 141.58 | 68.92 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 107.00 | 41.68 | 190.78 | 65.65 | 0.00 | 0.00 | 0.00 |
May | 161.40 | 121.69 | 39.71 | 207.33 | 64.58 | 0.00 | 0.00 | 0.00 |
June | 170.99 | 134.75 | 36.23 | 226.89 | 60.71 | 0.00 | 0.00 | 0.00 |
July | 166.35 | 125.07 | 41.28 | 225.59 | 52.35 | 0.00 | 0.00 | 0.00 |
August | 155.99 | 111.93 | 44.07 | 208.07 | 53.22 | 0.00 | 0.00 | 0.00 |
September | 127.07 | 92.82 | 34.25 | 164.22 | 69.04 | 0.00 | 0.00 | 0.00 |
October | 96.56 | 75.04 | 21.52 | 115.58 | 85.36 | 0.00 | 0.00 | 0.00 |
November | 68.64 | 48.48 | 20.16 | 79.01 | 80.31 | 0.00 | 0.00 | 0.00 |
December | 56.50 | 42.47 | 14.03 | 61.79 | 94.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.76 | 86.78 | 30.98 | 150.11 | 72.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.50 | 42.47 | 14.03 | 61.79 | 52.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.99 | 134.75 | 44.07 | 226.89 | 94.38 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.327893E+09 | 0.186848E+09 | 0.141045E+09 | 0.309879E+09 | 0.442606E+09 |
February | 0.380245E+09 | 0.219224E+09 | 0.161021E+09 | 0.388407E+09 | 0.356283E+09 |
March | 0.472115E+09 | 0.251361E+09 | 0.220754E+09 | 0.511770E+09 | 0.309409E+09 |
April | 0.582080E+09 | 0.309362E+09 | 0.272718E+09 | 0.666847E+09 | 0.224475E+09 |
May | 0.573257E+09 | 0.296193E+09 | 0.277064E+09 | 0.691599E+09 | 0.189243E+09 |
June | 0.591378E+09 | 0.329549E+09 | 0.261829E+09 | 0.821289E+09 | 0.130954E+09 |
July | 0.552171E+09 | 0.270243E+09 | 0.281928E+09 | 0.803656E+09 | 90621900.33 |
August | 0.563582E+09 | 0.260213E+09 | 0.303369E+09 | 0.787107E+09 | 0.104533E+09 |
September | 0.494864E+09 | 0.261216E+09 | 0.233649E+09 | 0.642231E+09 | 0.173850E+09 |
October | 0.465834E+09 | 0.289365E+09 | 0.176469E+09 | 0.533596E+09 | 0.298605E+09 |
November | 0.353635E+09 | 0.207792E+09 | 0.145842E+09 | 0.347147E+09 | 0.350513E+09 |
December | 0.316101E+09 | 0.198054E+09 | 0.118047E+09 | 0.289426E+09 | 0.460928E+09 |
Annual Sum or Average | 0.567316E+10 | 0.307942E+10 | 0.259374E+10 | 0.679295E+10 | 0.313202E+10 |
Minimum of Months | 0.316101E+09 | 0.186848E+09 | 0.118047E+09 | 0.289426E+09 | 90621900.33 |
Maximum of Months | 0.591378E+09 | 0.329549E+09 | 0.303369E+09 | 0.821289E+09 | 0.460928E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.327893E+09 | 0.186848E+09 | 0.141045E+09 | 0.309879E+09 | 0.442606E+09 |
February | 0.380245E+09 | 0.219224E+09 | 0.161021E+09 | 0.388407E+09 | 0.356283E+09 |
March | 0.472115E+09 | 0.251361E+09 | 0.220754E+09 | 0.511770E+09 | 0.309409E+09 |
April | 0.582080E+09 | 0.309362E+09 | 0.272718E+09 | 0.666847E+09 | 0.224475E+09 |
May | 0.573257E+09 | 0.296193E+09 | 0.277064E+09 | 0.691599E+09 | 0.189243E+09 |
June | 0.591378E+09 | 0.329549E+09 | 0.261829E+09 | 0.821289E+09 | 0.130954E+09 |
July | 0.552171E+09 | 0.270243E+09 | 0.281928E+09 | 0.803656E+09 | 90621900.33 |
August | 0.563582E+09 | 0.260213E+09 | 0.303369E+09 | 0.787107E+09 | 0.104533E+09 |
September | 0.494864E+09 | 0.261216E+09 | 0.233649E+09 | 0.642231E+09 | 0.173850E+09 |
October | 0.465834E+09 | 0.289365E+09 | 0.176469E+09 | 0.533596E+09 | 0.298605E+09 |
November | 0.353635E+09 | 0.207792E+09 | 0.145842E+09 | 0.347147E+09 | 0.350513E+09 |
December | 0.316101E+09 | 0.198054E+09 | 0.118047E+09 | 0.289426E+09 | 0.460928E+09 |
Annual Sum or Average | 0.567316E+10 | 0.307942E+10 | 0.259374E+10 | 0.679295E+10 | 0.313202E+10 |
Minimum of Months | 0.316101E+09 | 0.186848E+09 | 0.118047E+09 | 0.289426E+09 | 90621900.33 |
Maximum of Months | 0.591378E+09 | 0.329549E+09 | 0.303369E+09 | 0.821289E+09 | 0.460928E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 67040141.16 | 0.00 | 67040141.16 | 12474345.20 | 0.272258E+09 |
February | 75680308.70 | 0.00 | 75680308.70 | 25568324.61 | 0.217551E+09 |
March | 0.105719E+09 | 10310.35 | 0.105708E+09 | 63974854.59 | 0.185999E+09 |
April | 0.130035E+09 | 1357738.86 | 0.128677E+09 | 94885258.46 | 0.130560E+09 |
May | 0.146104E+09 | 9659468.83 | 0.136445E+09 | 0.135122E+09 | 0.104885E+09 |
June | 0.160353E+09 | 26335529.93 | 0.134018E+09 | 0.216615E+09 | 69466649.57 |
July | 0.151694E+09 | 12320278.95 | 0.139374E+09 | 0.224525E+09 | 49590697.91 |
August | 0.141568E+09 | 3692970.36 | 0.137876E+09 | 0.186259E+09 | 57433056.79 |
September | 0.109219E+09 | 65699.41 | 0.109153E+09 | 0.115359E+09 | 0.101858E+09 |
October | 84146868.98 | 0.00 | 84146868.98 | 47645681.80 | 0.179925E+09 |
November | 69155419.31 | 0.00 | 69155419.31 | 14791353.91 | 0.217581E+09 |
December | 57061290.17 | 0.00 | 57061290.17 | 3082207.43 | 0.291110E+09 |
Annual Sum or Average | 0.129778E+10 | 53441996.68 | 0.124433E+10 | 0.114030E+10 | 0.187822E+10 |
Minimum of Months | 57061290.17 | 0.00 | 57061290.17 | 3082207.43 | 49590697.91 |
Maximum of Months | 0.160353E+09 | 26335529.93 | 0.139374E+09 | 0.224525E+09 | 0.291110E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 67038315.63 | 0.00 | 67038315.63 | 12473438.33 | 0.272258E+09 |
February | 75678332.41 | 0.00 | 75678332.41 | 25566948.51 | 0.217550E+09 |
March | 0.105716E+09 | 10309.87 | 0.105706E+09 | 63972300.83 | 0.185998E+09 |
April | 0.130031E+09 | 1357675.22 | 0.128674E+09 | 94882183.70 | 0.130559E+09 |
May | 0.146100E+09 | 9659016.08 | 0.136441E+09 | 0.135118E+09 | 0.104884E+09 |
June | 0.160349E+09 | 26334295.55 | 0.134014E+09 | 0.216610E+09 | 69465709.59 |
July | 0.151690E+09 | 12319701.48 | 0.139370E+09 | 0.224520E+09 | 49589859.75 |
August | 0.141565E+09 | 3692797.26 | 0.137872E+09 | 0.186255E+09 | 57432267.48 |
September | 0.109216E+09 | 65696.33 | 0.109150E+09 | 0.115356E+09 | 0.101857E+09 |
October | 84144853.67 | 0.00 | 84144853.67 | 47644258.96 | 0.179924E+09 |
November | 69153575.73 | 0.00 | 69153575.73 | 14790229.47 | 0.217580E+09 |
December | 57059846.30 | 0.00 | 57059846.30 | 3081854.52 | 0.291109E+09 |
Annual Sum or Average | 0.129774E+10 | 53439491.79 | 0.124430E+10 | 0.114027E+10 | 0.187821E+10 |
Minimum of Months | 57059846.30 | 0.00 | 57059846.30 | 3081854.52 | 49589859.75 |
Maximum of Months | 0.160349E+09 | 26334295.55 | 0.139370E+09 | 0.224520E+09 | 0.291109E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.196858E+09 | 0.245983E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.252951E+09 | 0.198223E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.379221E+09 | 0.184606E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.494496E+09 | 0.170163E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.555322E+09 | 0.172977E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.588101E+09 | 0.157352E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.604210E+09 | 0.140214E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.557285E+09 | 0.142539E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.425667E+09 | 0.178946E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.309579E+09 | 0.228620E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.204807E+09 | 0.208160E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.165505E+09 | 0.252797E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.473400E+10 | 0.228058E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.165505E+09 | 0.140214E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.604210E+09 | 0.252797E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.196858E+09 | 0.245983E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.252951E+09 | 0.198223E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.379221E+09 | 0.184606E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.494496E+09 | 0.170163E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.555322E+09 | 0.172977E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.588101E+09 | 0.157352E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.604210E+09 | 0.140214E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.557285E+09 | 0.142539E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.425667E+09 | 0.178946E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.309579E+09 | 0.228620E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.204807E+09 | 0.208160E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.165505E+09 | 0.252797E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.473400E+10 | 0.228058E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.165505E+09 | 0.140214E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.604210E+09 | 0.252797E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.196858E+09 | 0.245983E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.252951E+09 | 0.198223E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.379221E+09 | 0.184606E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.494496E+09 | 0.170163E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.555322E+09 | 0.172977E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.588101E+09 | 0.157352E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.604210E+09 | 0.140214E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.557285E+09 | 0.142539E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.425667E+09 | 0.178946E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.309579E+09 | 0.228620E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.204807E+09 | 0.208160E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.165505E+09 | 0.252797E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.473400E+10 | 0.228058E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.165505E+09 | 0.140214E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.604210E+09 | 0.252797E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.196858E+09 | 0.245983E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.252951E+09 | 0.198223E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.379221E+09 | 0.184606E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.494496E+09 | 0.170163E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.555322E+09 | 0.172977E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.588101E+09 | 0.157352E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.604210E+09 | 0.140214E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.557285E+09 | 0.142539E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.425667E+09 | 0.178946E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.309579E+09 | 0.228620E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.204807E+09 | 0.208160E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.165505E+09 | 0.252797E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.473400E+10 | 0.228058E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.165505E+09 | 0.140214E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.604210E+09 | 0.252797E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.196858E+09 | 0.245983E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.252951E+09 | 0.198223E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.379221E+09 | 0.184606E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.494496E+09 | 0.170163E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.555322E+09 | 0.172977E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.588101E+09 | 0.157352E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.604210E+09 | 0.140214E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.557285E+09 | 0.142539E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.425667E+09 | 0.178946E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.309579E+09 | 0.228620E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.204807E+09 | 0.208160E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.165505E+09 | 0.252797E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.473400E+10 | 0.228058E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.165505E+09 | 0.140214E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.604210E+09 | 0.252797E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.196858E+09 | 0.245983E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.252951E+09 | 0.198223E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.379221E+09 | 0.184606E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.494496E+09 | 0.170163E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.555322E+09 | 0.172977E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.588101E+09 | 0.157352E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.604210E+09 | 0.140214E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.557285E+09 | 0.142539E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.425667E+09 | 0.178946E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.309579E+09 | 0.228620E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.204807E+09 | 0.208160E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.165505E+09 | 0.252797E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.473400E+10 | 0.228058E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.165505E+09 | 0.140214E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.604210E+09 | 0.252797E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.196858E+09 | 0.245983E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.252951E+09 | 0.198223E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.379221E+09 | 0.184606E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.494496E+09 | 0.170163E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.555322E+09 | 0.172977E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.588101E+09 | 0.157352E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.604210E+09 | 0.140214E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.557285E+09 | 0.142539E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.425667E+09 | 0.178946E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.309579E+09 | 0.228620E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.204807E+09 | 0.208160E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.165505E+09 | 0.252797E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.473400E+10 | 0.228058E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.165505E+09 | 0.140214E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.604210E+09 | 0.252797E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.196858E+09 | 0.245983E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.252951E+09 | 0.198223E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.379221E+09 | 0.184606E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.494496E+09 | 0.170163E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.555322E+09 | 0.172977E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.588101E+09 | 0.157352E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.604210E+09 | 0.140214E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.557285E+09 | 0.142539E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.425667E+09 | 0.178946E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.309579E+09 | 0.228620E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.204807E+09 | 0.208160E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.165505E+09 | 0.252797E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.473400E+10 | 0.228058E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.165505E+09 | 0.140214E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.604210E+09 | 0.252797E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.196858E+09 | 0.245983E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.252951E+09 | 0.198223E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.379221E+09 | 0.184606E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.494496E+09 | 0.170163E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.555322E+09 | 0.172977E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.588101E+09 | 0.157352E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.604210E+09 | 0.140214E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.557285E+09 | 0.142539E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.425667E+09 | 0.178946E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.309579E+09 | 0.228620E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.204807E+09 | 0.208160E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.165505E+09 | 0.252797E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.473400E+10 | 0.228058E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.165505E+09 | 0.140214E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.604210E+09 | 0.252797E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169310E+09 | 0.116031E+09 | 53279062.56 | 0.196858E+09 | 0.245983E+09 |
February | 0.206582E+09 | 0.146987E+09 | 59594788.10 | 0.252951E+09 | 0.198223E+09 |
March | 0.296238E+09 | 0.205374E+09 | 90863845.94 | 0.379221E+09 | 0.184606E+09 |
April | 0.385376E+09 | 0.277337E+09 | 0.108039E+09 | 0.494496E+09 | 0.170163E+09 |
May | 0.432281E+09 | 0.325923E+09 | 0.106358E+09 | 0.555322E+09 | 0.172977E+09 |
June | 0.443200E+09 | 0.349280E+09 | 93919918.52 | 0.588101E+09 | 0.157352E+09 |
July | 0.445554E+09 | 0.334996E+09 | 0.110558E+09 | 0.604210E+09 | 0.140214E+09 |
August | 0.417812E+09 | 0.299785E+09 | 0.118027E+09 | 0.557285E+09 | 0.142539E+09 |
September | 0.329356E+09 | 0.240585E+09 | 88771097.04 | 0.425667E+09 | 0.178946E+09 |
October | 0.258639E+09 | 0.200989E+09 | 57650826.00 | 0.309579E+09 | 0.228620E+09 |
November | 0.177922E+09 | 0.125662E+09 | 52260236.93 | 0.204807E+09 | 0.208160E+09 |
December | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.165505E+09 | 0.252797E+09 |
Annual Sum or Average | 0.371360E+10 | 0.273670E+10 | 0.976901E+09 | 0.473400E+10 | 0.228058E+10 |
Minimum of Months | 0.151333E+09 | 0.113755E+09 | 37578383.90 | 0.165505E+09 | 0.140214E+09 |
Maximum of Months | 0.445554E+09 | 0.349280E+09 | 0.118027E+09 | 0.604210E+09 | 0.252797E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 232.55 | 525.65 | 294.90 | 139.52 | 155.38 | 0.00 | 0.00 |
February | 335.47 | 467.63 | 376.92 | 181.24 | 195.68 | 0.00 | 0.00 |
March | 426.37 | 366.38 | 431.48 | 187.70 | 243.77 | 0.00 | 0.00 |
April | 585.30 | 271.49 | 549.47 | 239.75 | 309.72 | 0.00 | 0.00 |
May | 614.78 | 217.09 | 537.16 | 228.38 | 308.77 | 0.00 | 0.00 |
June | 794.82 | 148.62 | 580.04 | 274.60 | 305.44 | 0.00 | 0.00 |
July | 765.66 | 102.61 | 525.58 | 210.99 | 314.59 | 0.00 | 0.00 |
August | 725.36 | 119.47 | 526.54 | 197.06 | 329.48 | 0.00 | 0.00 |
September | 583.98 | 212.15 | 466.11 | 201.61 | 264.51 | 0.00 | 0.00 |
October | 430.01 | 353.31 | 410.68 | 216.07 | 194.60 | 0.00 | 0.00 |
November | 271.05 | 430.12 | 326.23 | 160.33 | 165.89 | 0.00 | 0.00 |
December | 203.70 | 546.84 | 278.65 | 147.89 | 130.76 | 0.00 | 0.00 |
Annual Sum or Average | 498.08 | 312.70 | 442.09 | 198.68 | 243.41 | 0.00 | 0.00 |
Minimum of Months | 203.70 | 102.61 | 278.65 | 139.52 | 130.76 | 0.00 | 0.00 |
Maximum of Months | 794.82 | 546.84 | 580.04 | 274.60 | 329.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2485.45 | 6214.10 | 632.13 | 433.21 | 198.92 | 0.00 | 0.00 |
February | 3566.85 | 5147.06 | 853.93 | 607.58 | 246.34 | 0.00 | 0.00 |
March | 5085.93 | 2968.35 | 1106.02 | 766.78 | 339.25 | 0.00 | 0.00 |
April | 6440.79 | 2361.27 | 1486.79 | 1069.97 | 416.82 | 0.00 | 0.00 |
May | 8067.49 | 2664.50 | 1613.95 | 1216.86 | 397.10 | 0.00 | 0.00 |
June | 9603.28 | 3878.77 | 1709.88 | 1347.53 | 362.35 | 0.00 | 0.00 |
July | 10928.35 | 4267.73 | 1663.51 | 1250.73 | 412.78 | 0.00 | 0.00 |
August | 10156.46 | 4155.19 | 1559.93 | 1119.27 | 440.66 | 0.00 | 0.00 |
September | 7850.77 | 4065.60 | 1270.66 | 928.18 | 342.48 | 0.00 | 0.00 |
October | 4380.58 | 3537.08 | 965.65 | 750.41 | 215.24 | 0.00 | 0.00 |
November | 2935.40 | 3527.14 | 686.43 | 484.81 | 201.62 | 0.00 | 0.00 |
December | 2077.69 | 5982.68 | 565.01 | 424.71 | 140.30 | 0.00 | 0.00 |
Annual Sum or Average | 6146.35 | 4061.86 | 1177.58 | 867.80 | 309.77 | 0.00 | 0.00 |
Minimum of Months | 2077.69 | 2361.27 | 565.01 | 424.71 | 140.30 | 0.00 | 0.00 |
Maximum of Months | 10928.35 | 6214.10 | 1709.88 | 1347.53 | 440.66 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.622874E+09 | 0.140790E+10 | 0.789864E+09 | 0.373696E+09 | 0.416168E+09 | 0.00 | 0.00 |
February | 0.811565E+09 | 0.113128E+10 | 0.911850E+09 | 0.438449E+09 | 0.473401E+09 | 0.00 | 0.00 |
March | 0.114198E+10 | 0.981307E+09 | 0.115566E+10 | 0.502743E+09 | 0.652921E+09 | 0.00 | 0.00 |
April | 0.151709E+10 | 0.703701E+09 | 0.142423E+10 | 0.621440E+09 | 0.802787E+09 | 0.00 | 0.00 |
May | 0.164663E+10 | 0.581445E+09 | 0.143872E+10 | 0.611705E+09 | 0.827014E+09 | 0.00 | 0.00 |
June | 0.206018E+10 | 0.385216E+09 | 0.150346E+10 | 0.711767E+09 | 0.791690E+09 | 0.00 | 0.00 |
July | 0.205075E+10 | 0.274822E+09 | 0.140773E+10 | 0.565125E+09 | 0.842600E+09 | 0.00 | 0.00 |
August | 0.194279E+10 | 0.319996E+09 | 0.141030E+10 | 0.527812E+09 | 0.882486E+09 | 0.00 | 0.00 |
September | 0.151367E+10 | 0.549902E+09 | 0.120816E+10 | 0.522563E+09 | 0.685601E+09 | 0.00 | 0.00 |
October | 0.115174E+10 | 0.946315E+09 | 0.109996E+10 | 0.578730E+09 | 0.521229E+09 | 0.00 | 0.00 |
November | 0.702562E+09 | 0.111487E+10 | 0.845579E+09 | 0.415585E+09 | 0.429994E+09 | 0.00 | 0.00 |
December | 0.545585E+09 | 0.146464E+10 | 0.746324E+09 | 0.396108E+09 | 0.350216E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.157074E+11 | 0.986140E+10 | 0.139418E+11 | 0.626572E+10 | 0.767611E+10 | 0.00 | 0.00 |
Minimum of Months | 0.545585E+09 | 0.274822E+09 | 0.746324E+09 | 0.373696E+09 | 0.350216E+09 | 0.00 | 0.00 |
Maximum of Months | 0.206018E+10 | 0.146464E+10 | 0.150346E+10 | 0.711767E+09 | 0.882486E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.665702E+10 | 0.166438E+11 | 0.169310E+10 | 0.116031E+10 | 0.532791E+09 | 0.00 | 0.00 |
February | 0.862892E+10 | 0.124518E+11 | 0.206582E+10 | 0.146987E+10 | 0.595948E+09 | 0.00 | 0.00 |
March | 0.136221E+11 | 0.795043E+10 | 0.296238E+10 | 0.205374E+10 | 0.908638E+09 | 0.00 | 0.00 |
April | 0.166945E+11 | 0.612041E+10 | 0.385376E+10 | 0.277337E+10 | 0.108039E+10 | 0.00 | 0.00 |
May | 0.216080E+11 | 0.713659E+10 | 0.432281E+10 | 0.325923E+10 | 0.106358E+10 | 0.00 | 0.00 |
June | 0.248917E+11 | 0.100538E+11 | 0.443200E+10 | 0.349280E+10 | 0.939199E+09 | 0.00 | 0.00 |
July | 0.292705E+11 | 0.114307E+11 | 0.445554E+10 | 0.334996E+10 | 0.110558E+10 | 0.00 | 0.00 |
August | 0.272031E+11 | 0.111293E+11 | 0.417812E+10 | 0.299785E+10 | 0.118027E+10 | 0.00 | 0.00 |
September | 0.203492E+11 | 0.105380E+11 | 0.329356E+10 | 0.240585E+10 | 0.887711E+09 | 0.00 | 0.00 |
October | 0.117329E+11 | 0.947371E+10 | 0.258639E+10 | 0.200989E+10 | 0.576508E+09 | 0.00 | 0.00 |
November | 0.760855E+10 | 0.914235E+10 | 0.177922E+10 | 0.125662E+10 | 0.522602E+09 | 0.00 | 0.00 |
December | 0.556489E+10 | 0.160240E+11 | 0.151333E+10 | 0.113755E+10 | 0.375784E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.193831E+12 | 0.128095E+12 | 0.371360E+11 | 0.273670E+11 | 0.976901E+10 | 0.00 | 0.00 |
Minimum of Months | 0.556489E+10 | 0.612041E+10 | 0.151333E+10 | 0.113755E+10 | 0.375784E+09 | 0.00 | 0.00 |
Maximum of Months | 0.292705E+11 | 0.166438E+11 | 0.445554E+10 | 0.349280E+10 | 0.118027E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.3 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.13 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.64 | -5.5 | 4.72 | -6.0 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.70 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.42 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.42 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.13 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.39 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.87 | 7.70 | 3.48 | 8.22 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.72 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.50 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.13 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.83 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.86 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.68 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.32 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.71 | -1.5 | 8.93 | 13.35 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.16 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.71 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.30 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.76 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.26 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.81 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 4.02 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 4.02 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.76 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.2 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.7 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.4 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -1.0 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.54 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.77 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.9 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.84 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.86 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.68 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.95 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.08 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.76 | 167.00 | 0.00 |
June | 18.19 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.21 | 31-JUL-14:00 | 32.80 | 12.80 | 6.20 | 22.98 | 264.50 | 624.50 |
August | 19.18 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.19 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.16 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.81 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.92 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.92 | 12.80 | -10.0 | 2.10 | -0.1 | 50.00 | 0.00 | |
Maximum of Months | 19.21 | 32.80 | 15.60 | 13.40 | 22.98 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.72 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.79 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.72 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.05 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.59 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.04 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.38 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.05 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.100721E+10 | -852328437.1 | 0.00 | 0.00 | 744.00 | 0.00 | -154882061.7 | 58.99 | 0.00 | 0.00 |
February | 0.927625E+09 | -789012645.0 | 0.00 | 0.00 | 672.00 | 0.00 | -138612176.7 | 58.99 | 0.00 | 0.00 |
March | 0.104746E+10 | -899304509.2 | 0.00 | 0.00 | 744.00 | 0.00 | -148151229.0 | 58.99 | 0.00 | 0.00 |
April | 0.926543E+09 | -791267816.1 | 0.00 | 0.00 | 720.00 | 0.00 | -135275341.2 | 58.99 | 0.00 | 0.00 |
May | 0.900498E+09 | -765533071.5 | 0.00 | 0.00 | 744.00 | 0.00 | -134965194.1 | 58.99 | 0.00 | 0.00 |
June | 0.836817E+09 | -707996028.5 | 0.00 | 0.00 | 720.00 | 0.00 | -128821003.7 | 59.00 | 0.00 | 0.00 |
July | 0.781256E+09 | -649622295.4 | 0.00 | 0.00 | 744.00 | 0.00 | -131633905.0 | 58.99 | 0.00 | 0.00 |
August | 0.822777E+09 | -690147431.0 | 0.00 | 0.00 | 744.00 | 0.00 | -132629207.4 | 58.99 | 0.00 | 0.00 |
September | 0.792194E+09 | -663833151.0 | 0.00 | 0.00 | 720.00 | 0.00 | -128360684.8 | 58.99 | 0.00 | 0.00 |
October | 0.847812E+09 | -710474445.6 | 0.00 | 0.00 | 744.00 | 0.00 | -137337245.0 | 58.99 | 0.00 | 0.00 |
November | 0.879262E+09 | -735516480.1 | 0.00 | 0.00 | 720.00 | 0.00 | -143745514.1 | 58.99 | 0.00 | 0.00 |
December | 0.971954E+09 | -817171541.7 | 0.00 | 0.00 | 744.00 | 0.00 | -154782188.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.107414E+11 | -0.907221E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.166920E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.781256E+09 | -899304509.2 | 0.00 | 0.00 | 672.00 | 0.00 | -154882061.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.104746E+10 | -649622295.4 | 0.00 | 0.00 | 744.00 | 0.00 | -128360684.8 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 301.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 282.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 381.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 378.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 412.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 395.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 359.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 329.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 284.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 265.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4149.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 265.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 412.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.448453E+10 | 32471.49 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.339620E+10 | 32471.49 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.172292E+10 | 32471.49 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.313226E+09 | 32471.49 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 69440945.25 | 32471.49 | 05-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6590219.77 | 7376.63 | 07-JUN-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 631681.25 | 594.19 | 19-JUL-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2644847.10 | 2826.11 | 19-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2354576.49 | 4802.44 | 15-SEP-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.347315E+09 | 32471.49 | 25-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143251E+10 | 32471.49 | 04-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.412751E+10 | 32471.49 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 631681.25 | 594.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.448453E+10 | 32471.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.141757E+11 | 119084.32 | 01-JAN-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.952874E+10 | 119084.32 | 01-FEB-02:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176547E+10 | 114566.68 | 04-MAR-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15719611.82 | 12605.60 | 26-OCT-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.239086E+10 | 119084.32 | 26-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126926E+11 | 119084.32 | 09-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.405690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.141757E+11 | 119084.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.288523E+11 | 88541.71 | 16-JAN-17:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.175329E+11 | 81373.93 | 06-FEB-04:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.942301E+09 | 29774.04 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.693152E+09 | 22924.29 | 28-NOV-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261538E+11 | 88768.86 | 14-DEC-03:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.741745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.288523E+11 | 88768.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 7.36 | 7.36 | 0.01 | 05-JAN-15:00 | 0.01 | 0.00 |
February | 0.00 | 0.00 | 25946787.90 | 25946787.90 | 2918.63 | 14-FEB-16:00 | 2918.63 | 0.00 |
March | 0.00 | 0.00 | 53809370.63 | 53809370.63 | 3778.08 | 08-MAR-16:00 | 3778.08 | 0.00 |
April | 0.00 | 0.00 | 0.168703E+10 | 0.168703E+10 | 23418.35 | 12-APR-17:55 | 23418.35 | 0.00 |
May | 0.00 | 0.00 | 0.420116E+10 | 0.417975E+10 | 24798.17 | 21-MAY-23:02 | 21916.56 | 0.00 |
June | 0.00 | 0.00 | 0.104560E+11 | 0.102545E+11 | 25976.27 | 24-JUN-00:25 | 21490.69 | 0.00 |
July | 0.00 | 0.00 | 0.146051E+11 | 0.129355E+11 | 27956.08 | 01-JUL-17:11 | 16279.74 | 0.00 |
August | 0.00 | 0.00 | 0.138288E+11 | 0.122576E+11 | 27533.20 | 13-AUG-23:01 | 19678.04 | 0.00 |
September | 0.00 | 0.00 | 0.814823E+10 | 0.758485E+10 | 25916.59 | 23-SEP-17:15 | 17329.61 | 0.00 |
October | 0.00 | 0.00 | 0.272421E+10 | 0.259408E+10 | 26182.99 | 02-OCT-17:11 | 17681.32 | 0.00 |
November | 0.00 | 0.00 | 2395.63 | 2395.63 | 1.97 | 13-NOV-16:10 | 1.97 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.557303E+11 | 0.515730E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.146051E+11 | 0.129355E+11 | 27956.08 | 23418.35 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 33528.44 | 33528.44 | 3.66 | 08-MAR-14:00 | 3.66 | 0.00 |
April | 0.00 | 0.00 | 0.191482E+10 | 0.191482E+10 | 78658.55 | 29-APR-17:33 | 78658.55 | 0.00 |
May | 0.00 | 0.00 | 0.899657E+10 | 0.899294E+10 | 84174.62 | 28-MAY-12:05 | 82846.71 | 0.00 |
June | 0.00 | 0.00 | 0.294075E+11 | 0.292709E+11 | 86479.26 | 23-JUN-22:23 | 81952.29 | 0.00 |
July | 0.00 | 0.00 | 0.419491E+11 | 0.398748E+11 | 95794.75 | 01-JUL-17:11 | 59370.51 | 0.00 |
August | 0.00 | 0.00 | 0.366806E+11 | 0.347948E+11 | 94147.26 | 13-AUG-09:01 | 62942.73 | 0.00 |
September | 0.00 | 0.00 | 0.193259E+11 | 0.188019E+11 | 89570.68 | 04-SEP-10:23 | 74831.54 | 0.00 |
October | 0.00 | 0.00 | 0.457972E+10 | 0.454267E+10 | 83743.77 | 01-OCT-11:41 | 83743.77 | 0.00 |
November | 0.00 | 0.00 | 4679.07 | 4679.07 | 0.98 | 02-NOV-15:00 | 0.98 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.142854E+12 | 0.138193E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.419491E+11 | 0.398748E+11 | 95794.75 | 83743.77 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.369391E+09 | 0.04 | 325.82 | 01-JAN-00:05 | 0.09 |
February | 0.196697E+09 | 0.02 | 325.82 | 01-FEB-00:03 | 0.09 |
March | 23784981.51 | 0.00 | 325.82 | 01-MAR-04:37 | 0.09 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 18571834.88 | 0.00 | 325.82 | 26-NOV-04:40 | 0.09 |
December | 0.374776E+09 | 0.04 | 325.82 | 03-DEC-18:53 | 0.09 |
Annual Sum or Average | 0.983221E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.374776E+09 | 0.04 | 325.82 | 0.09 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.174847E+10 | 0.55 | 1683.22 | 06-JAN-08:00 | 1.09 |
February | 0.159663E+10 | 0.53 | 1683.22 | 01-FEB-08:00 | 1.10 |
March | 0.183519E+10 | 0.48 | 1683.22 | 10-MAR-07:35 | 1.09 |
April | 0.169459E+10 | 0.44 | 1683.22 | 01-APR-13:20 | 1.10 |
May | 0.182064E+10 | 0.49 | 1683.22 | 13-MAY-08:00 | 1.09 |
June | 0.199429E+10 | 0.63 | 1683.22 | 03-JUN-09:10 | 1.08 |
July | 0.203537E+10 | 0.65 | 1683.22 | 06-JUL-07:30 | 1.08 |
August | 0.217978E+10 | 0.68 | 1683.22 | 03-AUG-09:25 | 1.08 |
September | 0.189732E+10 | 0.58 | 1683.22 | 01-SEP-11:45 | 1.08 |
October | 0.174797E+10 | 0.46 | 1683.22 | 18-OCT-17:00 | 1.09 |
November | 0.162797E+10 | 0.44 | 1683.22 | 06-NOV-07:20 | 1.09 |
December | 0.172741E+10 | 0.51 | 1683.22 | 07-DEC-11:30 | 1.09 |
Annual Sum or Average | 0.219056E+11 | 0.54 | |||
Minimum of Months | 0.159663E+10 | 0.44 | 1683.22 | 1.08 | |
Maximum of Months | 0.217978E+10 | 0.68 | 1683.22 | 1.10 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.961402E+10 | 1.42 | 8552.01 | 02-JAN-07:20 | 1.88 |
February | 0.856636E+10 | 1.29 | 8552.01 | 01-FEB-07:05 | 1.88 |
March | 0.929390E+10 | 0.90 | 8552.01 | 04-MAR-08:20 | 1.88 |
April | 0.846777E+10 | 0.72 | 8552.01 | 01-APR-14:20 | 1.88 |
May | 0.893323E+10 | 0.76 | 8552.01 | 01-MAY-09:40 | 1.87 |
June | 0.940647E+10 | 0.93 | 8552.01 | 01-JUN-12:50 | 1.86 |
July | 0.947906E+10 | 0.95 | 8552.01 | 01-JUL-06:52 | 1.84 |
August | 0.988635E+10 | 0.94 | 8552.01 | 01-AUG-07:10 | 1.86 |
September | 0.872955E+10 | 0.78 | 8552.01 | 01-SEP-08:30 | 1.85 |
October | 0.851158E+10 | 0.70 | 8552.01 | 02-OCT-11:20 | 1.86 |
November | 0.833024E+10 | 0.88 | 8552.01 | 02-NOV-14:20 | 1.86 |
December | 0.950164E+10 | 1.41 | 8552.01 | 05-DEC-07:10 | 1.88 |
Annual Sum or Average | 0.108720E+12 | 0.97 | |||
Minimum of Months | 0.833024E+10 | 0.70 | 8552.01 | 1.84 | |
Maximum of Months | 0.988635E+10 | 1.42 | 8552.01 | 1.88 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.174847E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.160376E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.184989E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.214238E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.295598E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.501915E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.615530E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.598719E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.409492E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.247177E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.162797E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.172741E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.373842E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.160376E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.615530E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.961402E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.856636E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.929391E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.903695E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.116232E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.188579E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.226013E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.210684E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.144942E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.986632E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.833024E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.950164E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.152854E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.833024E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.226013E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.174847E+10 | 7.36 | 0.448453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159663E+10 | 25946787.90 | 0.339620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183519E+10 | 53809370.63 | 0.172292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169459E+10 | 0.168703E+10 | 0.313226E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.182064E+10 | 0.420116E+10 | 69440945.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.199429E+10 | 0.104560E+11 | 6590219.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.203537E+10 | 0.146051E+11 | 631681.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.217978E+10 | 0.138288E+11 | 2644847.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189732E+10 | 0.814823E+10 | 2354576.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174797E+10 | 0.272421E+10 | 0.347315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.162797E+10 | 2395.63 | 0.143251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.172741E+10 | 0.00 | 0.412751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.219056E+11 | 0.557303E+11 | 0.159059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.159663E+10 | 0.00 | 631681.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.217978E+10 | 0.146051E+11 | 0.448453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.961402E+10 | 0.00 | 0.141757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.856636E+10 | 0.00 | 0.952874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.929390E+10 | 33528.44 | 0.176547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.846777E+10 | 0.191482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.893323E+10 | 0.899657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.940647E+10 | 0.294075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.947906E+10 | 0.419491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.988635E+10 | 0.366806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.872955E+10 | 0.193259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.851158E+10 | 0.457972E+10 | 15719611.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.833024E+10 | 4679.07 | 0.239086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.950164E+10 | 0.00 | 0.126926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108720E+12 | 0.142854E+12 | 0.405690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.833024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.988635E+10 | 0.419491E+11 | 0.141757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.174847E+10 | 0.00 | 0.00 | 0.00 | 2.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159663E+10 | 0.00 | 0.00 | 0.00 | 7126483.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183519E+10 | 0.00 | 0.00 | 0.00 | 14699720.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169459E+10 | 0.00 | 0.00 | 0.00 | 0.447790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.182064E+10 | 0.00 | 0.00 | 0.00 | 0.113534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.199429E+10 | 0.00 | 0.00 | 0.00 | 0.302486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.203537E+10 | 0.00 | 0.00 | 0.00 | 0.411993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.217978E+10 | 0.00 | 0.00 | 0.00 | 0.380741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189732E+10 | 0.00 | 0.00 | 0.00 | 0.219761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174797E+10 | 0.00 | 0.00 | 0.00 | 0.723798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.162797E+10 | 0.00 | 0.00 | 0.00 | 667.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.172741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.219056E+11 | 0.00 | 0.00 | 0.00 | 0.154786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.159663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.217978E+10 | 0.00 | 0.00 | 0.00 | 0.411993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.961402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.856636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.929390E+10 | 0.00 | 0.00 | 0.00 | 10109.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.846777E+10 | 0.00 | 0.00 | 0.00 | 0.569185E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.893323E+10 | 0.00 | 0.00 | 0.00 | 0.268997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.940647E+10 | 0.00 | 0.00 | 0.00 | 0.945140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.947906E+10 | 0.00 | 0.00 | 0.00 | 0.131222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.988635E+10 | 0.00 | 0.00 | 0.00 | 0.111820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.872955E+10 | 0.00 | 0.00 | 0.00 | 0.576464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.851158E+10 | 0.00 | 0.00 | 0.00 | 0.135474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.833024E+10 | 0.00 | 0.00 | 0.00 | 1412.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.950164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108720E+12 | 0.00 | 0.00 | 0.00 | 0.441342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.833024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.988635E+10 | 0.00 | 0.00 | 0.00 | 0.131222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.602519E+09 | 0.00 | 0.00 | 4002.00 | 0.00 | 0.125126E+10 | 20358204.65 | 0.00 | 0.15 |
February | 0.562777E+09 | 0.00 | 0.00 | 191228.88 | 0.00 | 0.938906E+09 | 0.293849E+09 | 0.00 | 0.20 |
March | 0.793872E+09 | 0.00 | 0.00 | 604799.34 | 0.00 | 0.364853E+09 | 0.949438E+09 | 0.00 | 0.31 |
April | 0.397740E+09 | 720365.07 | 0.00 | 3729137.90 | 0.00 | 10640412.42 | 0.221339E+10 | 0.00 | 0.61 |
May | 0.141162E+09 | 18670418.61 | 0.00 | 5973539.12 | 0.00 | 10919125.14 | 0.251111E+10 | 0.00 | 0.74 |
June | 20959758.66 | 0.296342E+09 | 0.00 | 5974568.18 | 0.00 | 0.00 | 0.143206E+10 | 0.00 | 0.67 |
July | 543054.30 | 0.894077E+09 | 0.00 | 3381307.70 | 886125.01 | 0.00 | 0.306948E+09 | 0.00 | 0.58 |
August | 22170377.35 | 0.651113E+09 | 0.00 | 5237917.50 | 6884.26 | 0.00 | 0.952280E+09 | 0.00 | 0.77 |
September | 27595818.43 | 0.115292E+09 | 0.00 | 8048230.24 | 0.00 | 0.00 | 0.203065E+10 | 0.00 | 0.83 |
October | 0.326372E+09 | 14069934.74 | 0.00 | 5471000.66 | 0.00 | 72986802.78 | 0.261550E+10 | 0.00 | 0.68 |
November | 0.840919E+09 | 0.00 | 0.00 | 551384.72 | 0.00 | 0.341788E+09 | 0.865794E+09 | 0.00 | 0.21 |
December | 0.675467E+09 | 0.00 | 0.00 | 31159.41 | 0.00 | 0.136815E+10 | 77201043.49 | 0.00 | 0.15 |
Annual Sum or Average | 0.441210E+10 | 0.199028E+10 | 0.00 | 39198275.64 | 893009.27 | 0.435950E+10 | 0.142686E+11 | 0.00 | 0.49 |
Minimum of Months | 543054.30 | 0.00 | 0.00 | 4002.00 | 0.00 | 0.00 | 20358204.65 | 0.00 | 0.15 |
Maximum of Months | 0.840919E+09 | 0.894077E+09 | 0.00 | 8048230.24 | 886125.01 | 0.136815E+10 | 0.261550E+10 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.429711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342420E+09 | 0.00 | 0.00 | 0.14 |
February | 0.406412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126977E+09 | 0.00 | 0.00 | 0.15 |
March | 0.414832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14714155.83 | 0.00 | 0.00 | 0.16 |
April | 0.300272E+10 | 0.00 | 0.00 | 4468489.80 | 0.00 | 0.00 | 0.455141E+10 | 0.00 | 0.56 |
May | 0.137699E+10 | 6302163.59 | 0.00 | 15555894.04 | 0.00 | 0.00 | 0.781944E+10 | 0.00 | 0.78 |
June | 0.267665E+09 | 0.291754E+09 | 0.00 | 19847341.92 | 0.00 | 0.00 | 0.547400E+10 | 0.00 | 0.68 |
July | 33386154.51 | 0.716337E+09 | 0.00 | 18441317.05 | 0.00 | 0.00 | 0.299715E+10 | 0.00 | 0.62 |
August | 0.121361E+09 | 0.368820E+09 | 0.00 | 30794306.59 | 0.00 | 0.00 | 0.541438E+10 | 0.00 | 0.82 |
September | 0.300240E+09 | 23809387.75 | 0.00 | 32353923.06 | 0.00 | 0.00 | 0.775855E+10 | 0.00 | 0.89 |
October | 0.246806E+10 | 1332326.69 | 0.00 | 11387923.97 | 0.00 | 0.00 | 0.632941E+10 | 0.00 | 0.60 |
November | 0.439596E+10 | 0.00 | 0.00 | 7764.24 | 0.00 | 0.00 | 75717546.73 | 0.00 | 0.15 |
December | 0.506313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267942E+09 | 0.00 | 0.00 | 0.14 |
Annual Sum or Average | 0.295391E+11 | 0.140835E+10 | 0.00 | 0.132857E+09 | 0.00 | 0.752052E+09 | 0.404201E+11 | 0.00 | 0.48 |
Minimum of Months | 33386154.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.506313E+10 | 0.716337E+09 | 0.00 | 32353923.06 | 0.00 | 0.342420E+09 | 0.781944E+10 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.568647E+12 | 0.574094E+11 | 0.00 | 0.651367E+10 | 0.255329E+11 |
February | 0.698383E+12 | 0.546410E+11 | 0.00 | 0.598682E+10 | 0.192885E+11 |
March | 0.930020E+12 | 0.544196E+11 | 0.00 | 0.627180E+10 | 0.120146E+11 |
April | 0.117330E+13 | 0.488766E+11 | 0.00 | 0.101845E+11 | 0.144873E+11 |
May | 0.126924E+13 | 0.549230E+11 | 0.00 | 0.119846E+11 | 0.271008E+11 |
June | 0.121688E+13 | 0.531373E+11 | 0.00 | 0.672862E+10 | 0.620632E+11 |
July | 0.124975E+13 | 0.672557E+11 | 0.00 | 0.174271E+10 | 0.838408E+11 |
August | 0.122403E+13 | 0.723105E+11 | 0.00 | 0.557120E+10 | 0.755442E+11 |
September | 0.991293E+12 | 0.490189E+11 | 0.00 | 0.102751E+11 | 0.451576E+11 |
October | 0.807609E+12 | 0.531819E+11 | 0.00 | 0.119316E+11 | 0.196020E+11 |
November | 0.608005E+12 | 0.496596E+11 | 0.00 | 0.652074E+10 | 0.117336E+11 |
December | 0.533493E+12 | 0.529589E+11 | 0.00 | 0.745192E+10 | 0.240868E+11 |
Annual Sum or Average | 0.112707E+14 | 0.667793E+12 | 0.00 | 0.911632E+11 | 0.420452E+12 |
Minimum of Months | 0.533493E+12 | 0.488766E+11 | 0.00 | 0.174271E+10 | 0.117336E+11 |
Maximum of Months | 0.126924E+13 | 0.723105E+11 | 0.00 | 0.119846E+11 | 0.838408E+11 |