Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2023-10-16 10:41:44
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1217.43 | 251.79 | 251.79 |
Net Site Energy | 1217.43 | 251.79 | 251.79 |
Total Source Energy | 3389.40 | 701.00 | 701.00 |
Net Source Energy | 3389.40 | 701.00 | 701.00 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 223.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 8.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 133.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 61.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 993.62 | 223.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 223.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 8.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 133.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 61.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 223.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 8.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 133.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 61.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 26.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 20.04 | 46.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 205.50 | 46.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 20.04 | 46.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 205.50 | 46.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 993.618 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 993.618 | 100.00 |
Total On-Site and Utility Electric Sources | 993.618 | 100.00 |
Total Electricity End Uses | 993.618 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 59.67 |
Time Setpoint Not Met During Occupied Cooling | 0.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2482.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.61 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7186 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 15.0695 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 9.6875 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 11.2890 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 11.2890 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.7186 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 15.0695 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 9.6875 | 46.45 | 2.5587 | |
Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 11.2890 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-14:00 | 19-FEB-06:49 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 160183.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 14521.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7078.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1762.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 79668.20 | 160183.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 160183.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 14521.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 4773.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1762.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 242.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 27.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1974.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 423.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 195.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 84.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3146.79 | 242.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 50.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 40.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 650.82 | 50.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 50.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 40.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 650.82 | 50.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.16 |
ZONE2 FINE STORAGE DIRECT AIR | 3.15 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 2.91 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 2.91 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 117504.73 |
PSZ-OFFICE HEATING COIL | 29383.84 |
PSZ-FINE STORAGE HEATING COIL | 101827.36 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 117504.73 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.00 | 1.00 | 1.16 |
PSZ-FINE STORAGE | 3.15 | 3.15 | 3.15 | 3.15 | 3.15 | 3.15 | 1.00 | 1.00 | 3.15 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.16 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 3.15 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.16 | 1326.69 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.15 | 3446.42 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.16 | 1.16 | 1.16 | 1.16 | 19262.52 | 29383.84 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 3.15 | 3.15 | 3.15 | 3.15 | 63463.37 | 101827.36 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.16 | 0.581824 | 1.16 | 19262.52 | 9907.92 | 19262.52 | 0.800660 | 0.800660 |
PSZ-FINE STORAGE COOLING COIL | 3.15 | 1.57 | 3.15 | 63463.37 | 31503.60 | 63463.37 | 0.772970 | 0.772970 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.719 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.792 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 15.069 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15.069 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 9.688 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 12.246 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2539.013 | 10.719 | 199.158 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2539.013 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 20997.932 | 15.069 | 699.931 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20997.932 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 31046.942 | 9.688 | 449.956 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 31046.942 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5959 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.7823 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.9295 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 8.517 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.9295 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.678 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.179 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9765 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1174 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9765 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53319041E-11 | 0.92099297E-16 | 0.18475806E-15 | 0.0000000 |
5 | 1 | -5.2159728 | 0.43155192E-04 | -0.26885250E-04 | 0.68722794E-11 |
6 | 0 | 5.8118483 | 0.59583229 | 0.59590233 | |
7 | 4 | 0.72249793E-12 | -0.16720573E-15 | 0.22015083E-14 | 0.12409536E-15 |
8 | 3 | -0.36459118E-03 | 0.53555631E-06 | -0.52695411E-04 | 0.13865996E-12 |
9 | 2 | 1.6915239 | 0.11971291E-01 | 1.1039557 | -0.69896550E-04 |
10 | 1 | -7.1930661 | 0.31446443 | -16.864389 | 0.32415671 |
11 | 0 | 6.0306730 | 0.20232993 | 16.289252 | |
12 | 4 | 0.69489933E-12 | 0.18569687E-15 | 0.39666878E-14 | 0.11858654E-15 |
13 | 3 | -0.35466159E-03 | 0.62784354E-06 | -0.51164218E-04 | 0.13336592E-12 |
14 | 2 | 1.6674989 | 0.14195866E-01 | 1.0857092 | -0.67991750E-04 |
15 | 1 | -7.2261037 | 0.37556877 | -16.746879 | 0.31952467 |
16 | 0 | 6.1915038 | 0.24277908 | 16.293766 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.5173945 | 8.5173945 | 8.5173945 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.39666878E-14 | 0.18569687E-15 | 0.69489933E-12 | 0.11858654E-15 |
85 | 3 | -0.51164218E-04 | 0.62784354E-06 | -0.35466159E-03 | 0.13336592E-12 |
86 | 2 | 1.0857092 | 0.14195866E-01 | 1.6674989 | -0.67991750E-04 |
87 | 1 | -16.746879 | 0.37556877 | -7.2261037 | 0.31952467 |
88 | 0 | 16.293766 | 0.24277908 | 6.1915038 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5246_SHGC_SOUTH_0.4 | 34 | 1 | VerySmooth | 2.983 | 2.983 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.5246_SHGC_NORTH_0.4 | 35 | 1 | VerySmooth | 2.983 | 2.983 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.5246_SHGC_EAST_0.4 | 36 | 1 | VerySmooth | 2.983 | 2.983 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.5246_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.983 | 2.983 | 1.000 | 0.401 | ||
5 | SKYLIGHT_U_1.02_SHGC_0.49 | 38 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.491 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.59453E-002 | 0.31435 | 0.46253 | 0.46253 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 9.64639E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.59453E-002 | 0.31435 | 0.46253 | 0.46253 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 9.64639E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.59453E-002 | 0.31435 | 0.46253 | 0.46253 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 9.64639E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.59453E-002 | 0.31435 | 0.46253 | 0.46253 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 9.64639E-002 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.32532 | 0.12431 | 0.12431 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.849 | 0.366 | 0.255 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 0.153 | 6.473E-004 | 9.992E-004 | 0.546 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.780 | 5.598E-004 | 3.565E-004 | 0.951 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 3.433 | 1.071E-003 | 6.996E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11618.42578 | 13942.11094 | 0.96971 | 1.16365 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 28.08267 | 8.81938E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 11142.98393 | 13371.58072 | 0.31731 | 0.38078 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -4.20000 | 2.69032E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 40331.74333 | 48398.09200 | 2.62403 | 3.14884 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40000 | 8.82150E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 38534.56104 | 46241.47324 | 0.92419 | 1.10903 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | -4.20000 | 2.69032E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 29.40000 | 8.82150E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 97920.61121 | 117504.73345 | 2.42702 | 2.91242 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 17037.16 | 1.16365 | 1.16365 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 11687.52 | 0.38078 | 0.38078 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 56573.24 | 3.14884 | 3.14884 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 42345.83 | 1.10903 | 1.10903 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.16365 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.14884 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.91242 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 2.91242 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 117504.72889 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 117504.73345 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.16365 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.16365 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.16365 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.16365 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.16365 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.16365 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.14884 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.14884 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.14884 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.14884 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.14884 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.14884 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.16365 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.14884 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.16365 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.16365 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1326.68739 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.16365 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.16365 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.16365 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.16365 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.16365 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.58182 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.16365 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 19262.52000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 9907.91574 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 19262.52000 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19262.52000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29383.83789 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 29383.83789 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.14884 |
47 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.14884 |
49 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3446.41964 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.14884 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.14884 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.14884 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.14884 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.14884 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.57442 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.14884 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 63463.37000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 31503.59732 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 63463.37000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.77297 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.77297 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 63463.37000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 101827.36029 |
64 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
66 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 101827.36029 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 18359.6 | 10.70 | 10.08 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 61018.2 | 10.47 | 9.86 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.2061744160 | 0.1859699023 | Pass | Pass | 0.4937525945 | 1.7725095001 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.5339712333 | 0.4961138292 | Pass | Pass | 0.6202580797 | 0.9851775842 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 3.8674308579E-005 | 5.4874458469E-005 | Pass | Pass | 6.0266861786E-002 | 7.5530729692E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7247.34 | 604.74 | 0.00 | 100.02 | 100.89 | 8053.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.816 | 0.929 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.816 | 0.929 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.816 | 0.929 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.551 | 0.596 | 3204.84 | 3170.23 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.760 | 0.929 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.760 | 0.929 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.5246_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.983 | 0.401 | 0.402 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.5246_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.983 | 0.401 | 0.402 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.5246_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.983 | 0.401 | 0.402 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.5246_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.983 | 0.401 | 0.402 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.27 | 4.847 | 0.500 | 0.501 | |||||||||||||||||
North Total or Average | 6.51 | 2.983 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 45.76 | 5.112 | 0.514 | 0.515 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.744 | 8.517 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.744 | 8.517 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.744 | 8.517 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.744 | 8.517 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.7186 | 236.88 | 2539.01 | LightsWired | LTG_SCH_OFFICE | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.86 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 15.0695 | 1393.41 | 20997.93 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 239.15 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 9.6875 | 3204.84 | 31046.94 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 353.60 |
Interior Lighting Total | 11.2890 | 4835.13 | 54583.89 | 623.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 8532.22 | AstronomicalClock | - | 83.55 | 83.55 | 133.81 | |
Exterior Lighting Total | 8532.22 | 133.81 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 19262.52 | 15422.73 | 3839.79 | 0.80 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 63463.37 | 49055.28 | 14408.09 | 0.77 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 18359.6 | 10.70 | 10.08 | ||||
PSZ-FINE STORAGE COOLING COIL | 61018.2 | 10.47 | 9.86 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 117504.73 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 29383.84 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 101827.36 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.91 | 270.59 | 92.91 | 1.00 | 3.37 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.16 | 1326.69 | 1140.11 | 1.00 | 1.33 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 3.15 | 3446.42 | 1094.51 | 1.00 | 1.23 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11618.43 | 13942.11 | 58.86 | 0.970 | 1.164 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 23.90 | 23.90 | 0.00830 | 28.08 | 0.00882 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 40331.74 | 48398.09 | 34.73 | 2.624 | 3.149 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.70 | 26.70 | 0.00837 | 29.40 | 0.00882 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 0.00 | 30.47 | 0.00888 | 29.40 | 0.00882 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11142.98 | 13371.58 | 56.45 | 0.317 | 0.381 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00718 | -4.20 | 0.00269 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 38534.56 | 46241.47 | 33.19 | 0.924 | 1.109 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 15.56 | 15.55 | 0.00588 | -4.20 | 0.00269 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 97920.61 | 117504.73 | 36.66 | 2.427 | 2.912 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00519 | -4.20 | 0.00269 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.16 | 1.16 | 0.38 | 0.38 | 1.1636 | 1.1636 | 1.1636 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.15 | 3.15 | 1.11 | 1.11 | 3.1488 | 3.1488 | 3.1488 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 117504.729 | 117504.729 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 117504.73 | 117504.73 | 2.912422 | 10.00 | 7.13 | 0.00518697 | 43.33 | 21.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 10.00 | 0.00518697 | 67.2747 | 117504.73 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 19262.520 | 15422.729 | 1.163650 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 19262.52 | 18195.40 | 1.163650 | 25.22 | 16.54 | 0.00834595 | 12.00 | 11.13 | 0.00800000 | 28.22 | 0.00881961 | 17.95 | 8.7900 | 23.90 | 0.00830029 | 44.3266 | 11614.82 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 29383.838 | 29383.838 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 29383.84 | 29383.84 | 1.163649 | 18.83 | 12.73 | 0.00678802 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 8.7900 | 21.10 | 0.00718292 | 45.5606 | 11142.98 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 63463.370 | 49055.281 | 3.148840 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 63463.37 | 59756.40 | 3.148840 | 27.97 | 17.55 | 0.00843324 | 12.00 | 11.13 | 0.00800000 | 29.40 | 0.00882150 | 18.34 | 13.4879 | 26.70 | 0.00837271 | 37.8498 | 40331.74 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 101827.360 | 101827.360 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 101827.36 | 101827.36 | 3.148837 | 12.89 | 8.79 | 0.00545113 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 13.4879 | 15.55 | 0.00588157 | 52.9429 | 38534.56 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 117504.729 | 117504.729 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 2.912422 | 3.45701773 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 117504.73 | 117504.73 | 1.0000 | 3.45701773 | 2.912422 | 10.00 | 7.13 | 0.00518697 | 23113.9 | 43.33 | 21.98 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 117504.73 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 10.00 | 0.00518697 | 10.00 | 0.00518697 | 67.2747 | 117504.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19262.520 | 15422.729 | 1.163650 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3547 | 1004.8586 | 1.1870 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.163649 | 1.38124028 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | Sensible | 19262.52 | 18195.40 | 1.0000 | 1.38124183 | 1.163650 | 25.22 | 16.54 | 0.00834595 | 46606.3 | 12.00 | 11.13 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19262.52 | 28.22 | 0.00881961 | 17.95 | 0.10228463 | 8.7900 | 23.90 | 0.00830029 | 23.90 | 0.00830029 | 44.3266 | 11614.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29383.838 | 29383.838 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.163649 | 1.38124028 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 29383.84 | 29383.84 | 1.0000 | 1.38124028 | 1.163649 | 18.83 | 12.73 | 0.00678802 | 36134.5 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29383.84 | -4.20 | 0.00269032 | -4.20 | 0.10228463 | 8.7900 | 21.05 | 0.00718292 | 21.10 | 0.00718292 | 45.5606 | 11142.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 63463.370 | 49055.281 | 3.148840 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5170 | 1004.8586 | 1.1870 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.148837 | 3.73764076 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 63463.37 | 59756.40 | 1.0000 | 3.73764406 | 3.148840 | 27.97 | 17.55 | 0.00843324 | 49631.3 | 12.00 | 11.13 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 63463.37 | 29.40 | 0.00882150 | 18.34 | 0.42471127 | 13.4879 | 26.70 | 0.00837271 | 26.70 | 0.00837271 | 37.8498 | 40331.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 101827.360 | 101827.360 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.148837 | 3.73764076 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | Sensible | 101827.36 | 101827.36 | 1.0000 | 3.73764076 | 3.148837 | 12.89 | 8.79 | 0.00545113 | 26713.9 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 101827.36 | -4.20 | 0.00269032 | -4.20 | 0.42471127 | 13.4879 | 15.55 | 0.00588157 | 15.55 | 0.00588157 | 52.9429 | 38534.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.16 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 3.15 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 1997.17 | 2797.67 | 1529.50 |
ZONE2 FINE STORAGE | 2845.50 | 2762.83 | 2092.83 |
ZONE3 BULK STORAGE | 2894.83 | 3065.67 | 2424.50 |
Facility | 3224.83 | 3181.17 | 2482.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 60.50 | 33.50 | 51.33 | 0.67 |
ZONE2 FINE STORAGE | 308.00 | 5.00 | 18.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 357.67 | 37.00 | 59.67 | 0.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.846 | 0.387 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.696 | 0.406 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.173 | 0.000 | 0.075 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.50 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.36 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.28 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 3191184.85 | 0.00 | 3191184.85 | 2621007.72 | 5812192.57 | 3225648.14 | 5638.95 | 1866.50 | 1254.55 | 72.83 |
ZONE2 FINE STORAGE | 7359102.41 | 0.00 | 7359102.41 | 11500225.77 | 18859328.18 | 13393694.68 | 5724.30 | 2397.17 | 638.53 | 5.20 |
ZONE3 BULK STORAGE | 0.00 | 18642141.83 | 18642141.83 | 46117433.81 | 64759575.64 | 30805497.77 | 8427.37 | 47.00 | 285.63 | 4996.00 |
Total Facility | 10550287.26 | 18642141.83 | 29192429.09 | 60238667.30 | 89431096.39 | 47424840.58 | 8582.43 | 2510.83 | 1611.01 | 4999.46 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.2327 | 0.0000 | 0.2327 | 0.1070 | 0.3397 | 0.1023 | 584.11 | 1866.33 | 1185.56 |
ZONE2 FINE STORAGE | 0.5591 | 0.0000 | 0.5591 | 0.3292 | 0.8883 | 0.4247 | 605.50 | 2397.17 | 633.33 |
ZONE3 BULK STORAGE | 0.0000 | 0.7281 | 0.7281 | 1.6964 | 2.4245 | 0.9768 | 3448.09 | 26.83 | 161.07 |
Total Facility | 0.7918 | 0.7281 | 1.5199 | 2.1326 | 3.6525 | 1.5038 | 3458.43 | 2490.50 | 1412.97 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 4496210.71 | 0.00 | 4496210.71 | 3225648.14 | 5633.31 | 0.17 | 3126.53 | 72.83 |
PSZ-FINE STORAGE | 10368586.14 | 0.00 | 10368586.14 | 13393694.68 | 5724.14 | 0.00 | 3035.86 | 5.20 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.3278 | 0.0000 | 0.3278 | 0.1023 | 580.14 | 0.17 | 3055.69 |
PSZ-FINE STORAGE | 0.7878 | 0.0000 | 0.7878 | 0.4247 | 605.33 | 0.00 | 3030.67 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2358.85 | 780.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2664.73 | 371.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.3347 | 0.5519 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.8467 | 1.6522 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 383 |
Defaulted Fields | 319 |
Fields with Defaults | 1020 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 993.62 | 6718.26 | 08-JAN-13:00 | 79668.20 | 10-AUG-15:00 |
Electricity:Building | 763.12 | 6235.26 | 01-JAN-00:10 | 58611.10 | 24-JUL-13:00 |
Electricity:Zone:ZONE1 OFFICE | 62.81 | 1030.77 | 01-JAN-00:10 | 3867.54 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 762.90 | 6235.26 | 01-JAN-00:10 | 56305.80 | 02-JAN-09:10 |
InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 461.17 | 3104.69 | 01-JAN-00:10 | 36895.31 | 24-JUL-13:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 61.65 | 0.00 | 02-JAN-18:40 | 7078.40 | 24-JUL-13:00 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.22 | 0.00 | 01-JAN-00:10 | 2305.29 | 08-AUG-17:10 |
Ventilation (simple):Fans:Electricity | 0.22 | 0.00 | 01-JAN-00:10 | 2305.29 | 08-AUG-17:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.22 | 0.00 | 01-JAN-00:10 | 2305.29 | 08-AUG-17:10 |
ElectricityPurchased:Facility | 993.62 | 6718.26 | 08-JAN-13:00 | 79668.20 | 10-AUG-15:00 |
ElectricityPurchased:Plant | 993.62 | 6718.26 | 08-JAN-13:00 | 79668.20 | 10-AUG-15:00 |
Cogeneration:ElectricityPurchased | 993.62 | 6718.26 | 08-JAN-13:00 | 79668.20 | 10-AUG-15:00 |
General:Cogeneration:ElectricityPurchased | 993.62 | 6718.26 | 08-JAN-13:00 | 79668.20 | 10-AUG-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 993.62 | 6718.26 | 08-JAN-13:00 | 79668.20 | 10-AUG-15:00 |
ElectricityNet:Plant | 993.62 | 6718.26 | 08-JAN-13:00 | 79668.20 | 10-AUG-15:00 |
Cogeneration:ElectricityNet | 993.62 | 6718.26 | 08-JAN-13:00 | 79668.20 | 10-AUG-15:00 |
General:Cogeneration:ElectricityNet | 993.62 | 6718.26 | 08-JAN-13:00 | 79668.20 | 10-AUG-15:00 |
Electricity:HVAC | 70.14 | 0.00 | 02-JAN-18:40 | 19382.11 | 10-AUG-15:10 |
General:Fans:Electricity | 61.43 | 0.00 | 02-JAN-18:40 | 5043.70 | 02-JAN-07:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 8.72 | 0.00 | 01-JAN-00:10 | 14609.01 | 10-AUG-15:10 |
General:Cooling:Electricity | 8.72 | 0.00 | 01-JAN-00:10 | 14609.01 | 10-AUG-15:10 |
ExteriorLights:Electricity | 133.81 | 0.00 | 01-JAN-08:10 | 8532.22 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 133.81 | 0.00 | 01-JAN-08:10 | 8532.22 | 01-JAN-00:10 |
Electricity:Plant | 26.54 | 483.00 | 28-FEB-06:10 | 2404.17 | 09-FEB-12:50 |
WaterSystems:Electricity | 26.54 | 483.00 | 28-FEB-06:10 | 2404.17 | 09-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 26.54 | 483.00 | 28-FEB-06:10 | 2404.17 | 09-FEB-12:50 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 223.81 | 0.00 | 02-JAN-18:40 | 160183.61 | 19-FEB-06:50 |
NaturalGas:HVAC | 223.81 | 0.00 | 02-JAN-18:40 | 160183.61 | 19-FEB-06:50 |
Heating:NaturalGas | 223.81 | 0.00 | 02-JAN-18:40 | 160183.61 | 19-FEB-06:50 |
General:Heating:NaturalGas | 223.81 | 0.00 | 02-JAN-18:40 | 160183.61 | 19-FEB-06:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 425.80 | 0.00 | 02-JAN-18:40 | 246357.49 | 19-FEB-06:50 |
EnergyTransfer:Building | 230.91 | 0.00 | 02-JAN-18:40 | 123632.69 | 19-FEB-06:50 |
EnergyTransfer:Zone:ZONE1 OFFICE | 43.13 | 0.00 | 01-JAN-00:40 | 19301.18 | 09-JAN-06:10 |
Heating:EnergyTransfer | 168.17 | 0.00 | 02-JAN-18:40 | 123632.69 | 19-FEB-06:50 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 22.35 | 0.00 | 01-JAN-00:40 | 19301.18 | 09-JAN-06:10 |
General:Heating:EnergyTransfer | 168.17 | 0.00 | 02-JAN-18:40 | 123632.69 | 19-FEB-06:50 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 22.35 | 0.00 | 01-JAN-00:40 | 19301.18 | 09-JAN-06:10 |
Cooling:EnergyTransfer | 62.74 | 0.00 | 01-JAN-00:10 | 39124.93 | 10-AUG-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 20.77 | 0.00 | 01-JAN-00:10 | 10523.32 | 14-AUG-19:10 |
General:Cooling:EnergyTransfer | 62.74 | 0.00 | 01-JAN-00:10 | 39124.93 | 10-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 20.77 | 0.00 | 01-JAN-00:10 | 10523.32 | 14-AUG-19:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 107.75 | 0.00 | 01-JAN-00:40 | 42813.74 | 19-FEB-08:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 65.78 | 0.00 | 01-JAN-00:40 | 42813.74 | 19-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 65.78 | 0.00 | 01-JAN-00:40 | 42813.74 | 19-FEB-08:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 41.97 | 0.00 | 01-JAN-00:10 | 30609.15 | 10-SEP-14:20 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 41.97 | 0.00 | 01-JAN-00:10 | 30609.15 | 10-SEP-14:20 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 80.04 | 0.00 | 02-JAN-08:10 | 82940.42 | 19-FEB-07:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 80.04 | 0.00 | 02-JAN-08:10 | 82940.42 | 19-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 80.04 | 0.00 | 02-JAN-08:10 | 82940.42 | 19-FEB-07:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 194.88 | 0.00 | 02-JAN-18:40 | 122724.80 | 19-FEB-06:50 |
HeatingCoils:EnergyTransfer | 163.26 | 0.00 | 02-JAN-18:40 | 122724.80 | 19-FEB-06:50 |
CoolingCoils:EnergyTransfer | 31.62 | 0.00 | 01-JAN-00:10 | 49949.41 | 10-AUG-15:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 22.353 | -20.774 | 0.000 | 0.000 | 9.924 | 30.864 | 31.946 | 9.558 | 0.000 | 0.228 | 0.000 | 0.000 | -8.691 | 0.000 | -30.792 | -44.616 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 65.780 | -41.965 | 0.000 | 0.000 | 24.293 | 239.148 | 0.000 | 0.000 | 0.000 | 0.262 | 0.002 | 0.000 | 0.000 | 0.000 | -117.192 | -170.326 |
ZONE3 BULK STORAGE | 80.041 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 63.416 | 353.598 | 107.344 | 88.752 | 0.000 | 2.112 | 0.000 | 0.000 | -69.476 | 0.000 | -422.689 | -203.097 |
Total Facility | 80.041 | 0.000 | 88.133 | -62.739 | 0.000 | 0.000 | 97.633 | 623.610 | 139.290 | 98.309 | 0.000 | 2.602 | 0.002 | 0.000 | -78.166 | 0.000 | -570.674 | -418.038 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 23-JUL-23:01 | 0.00 | 0.00 | 0.00 | -20748.13 | 0.00 | 0.00 | 0.00 | 457.02 | 573.75 | 0.00 | 0.00 | 0.00 | 20447.11 | 0.00 | -360.28 | 0.00 | -369.48 | 0.00 |
ZONE2 FINE STORAGE | 29-JUL-17:11 | 0.00 | 0.00 | 0.00 | -64262.70 | 0.00 | 0.00 | 0.00 | 2099.79 | 0.00 | 0.00 | 0.00 | 0.00 | 63804.45 | 0.00 | -0.00 | 0.00 | -1641.54 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 29-JUL-17:11 | 0.00 | 0.00 | 0.00 | -81624.28 | 0.00 | 0.00 | 0.00 | 5661.51 | 2623.78 | 6624.20 | 0.00 | 0.00 | 80472.07 | 0.00 | 0.00 | 0.00 | -13757.28 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 17-JAN-06:12 | 0.00 | 0.00 | 29940.11 | 0.00 | 0.00 | 0.00 | 118.54 | 583.97 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -631.17 | 0.00 | -1525.71 | -29059.50 |
ZONE2 FINE STORAGE | 19-FEB-08:62 | 0.00 | 0.00 | 104898.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2099.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -13153.50 | -93844.54 |
ZONE3 BULK STORAGE | 19-FEB-07:00 | 82939.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5748.31 | 0.00 | -48147.39 | -32148.56 |
Total Facility | 19-FEB-06:42 | 82622.01 | 0.00 | 104431.82 | 0.00 | 0.00 | 0.00 | 0.00 | 5661.51 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -10593.08 | 0.00 | -63908.15 | -118787.86 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1636 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.1636 | 0.0879 | 1.0000 | Not calculated | 0.1023 | 0.0879 | ||
PSZ-FINE STORAGE | 3.1488 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.1488 | 0.1349 | 1.0000 | Not calculated | 0.4247 | 0.1349 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1636 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.1636 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0879 | ||
PSZ-FINE STORAGE | 3.1488 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.1488 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1349 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1636 | 1.1636 | 1.1636 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.1488 | 3.1488 | 3.1488 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1636 | 1.1636 | 1.1636 | 1.1636 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.1488 | 3.1488 | 3.1488 | 3.1488 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1636 | 1.1636 | 1.1636 | No | 0.1023 | 0.2686 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.1488 | 3.1488 | 3.1488 | No | 0.4247 | 0.3830 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1636 | 1.1636 | 1.1636 | 1.1636 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.1488 | 3.1488 | 3.1488 | 3.1488 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 59.67 |
Number of hours cooling loads not met | 0.67 |
Number of hours not met | 60.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 223.81 | 160183.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 8.72 | 14609.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 623.61 | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 133.81 | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.22 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 61.43 | 5043.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.54 | 2404.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 993.62 |
Natural Gas | 0.00 | 223.81 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 1217.43 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 128.97 |
Space Heating | 0.00 |
Space Cooling | 1.80 |
Fans (All) | 12.75 |
Service Water Heating | 5.49 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 205.50 |
Subtotal | 205.50 |
Natural Gas [MJ/m2] | |
Space Heating | 46.29 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 46.29 |
Subtotal | 46.29 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 51.22 |
Space Heating | 18.38 |
Space Cooling | 0.72 |
Fans (All) | 5.06 |
Service Water Heating | 2.18 |
Receptacle Equipment | 11.44 |
Miscellaneous | 10.99 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 3430. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8721.00 | 39.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8441.83 | 318.17 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8336.33 | 423.67 | 0.00 | 0.00 | 0.00 |
Min | 8336.33 | 39.00 | 0.00 | 0.00 | 0.00 |
Max | 8721.00 | 423.67 | 0.00 | 0.00 | 0.00 |
Average | 8499.72 | 260.28 | 0.00 | 0.00 | 0.00 |
Sum | 25499.17 | 780.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 75532.00 | 7187.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 173297.83 | 17895.17 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 173297.83 | 17895.17 | 0.00 | 0.00 | 0.00 |
Average | 93952.28 | 8360.72 | 0.00 | 0.00 | 0.00 |
Sum | 281856.83 | 25082.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8724.83 | 35.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8334.17 | 425.83 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8272.67 | 487.33 | 0.00 | 0.00 | 0.00 |
Min | 8272.67 | 35.17 | 0.00 | 0.00 | 0.00 |
Max | 8724.83 | 487.33 | 0.00 | 0.00 | 0.00 |
Average | 8443.89 | 316.11 | 0.00 | 0.00 | 0.00 |
Sum | 25331.67 | 948.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 73343.50 | 9375.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 171423.83 | 19769.17 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 171423.83 | 19769.17 | 0.00 | 0.00 | 0.00 |
Average | 92598.11 | 9714.89 | 0.00 | 0.00 | 0.00 |
Sum | 277794.33 | 29144.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 830070.82 | 401.06 | 20-JAN-15:40 | 6.13 | 4.37 | 0.497351E+09 | 640.19 | 11-JAN-16:10 | 6.13 | 4.37 |
February | 15438039.16 | 814.74 | 27-FEB-15:50 | 19.50 | 12.39 | 0.466385E+09 | 768.96 | 27-FEB-16:00 | 18.90 | 12.17 |
March | 62640312.75 | 1470.47 | 18-MAR-16:00 | 20.60 | 10.43 | 0.565209E+09 | 768.96 | 10-MAR-14:00 | 20.60 | 10.43 |
April | 0.515928E+09 | 16811.88 | 29-APR-17:15 | 20.57 | 14.52 | 0.561202E+09 | 769.02 | 29-APR-15:09 | 20.57 | 14.52 |
May | 0.182375E+10 | 19879.87 | 03-MAY-18:11 | 20.53 | 12.93 | 0.637938E+09 | 769.03 | 05-MAY-14:30 | 24.40 | 16.80 |
June | 0.330568E+10 | 20135.03 | 01-JUN-18:35 | 17.40 | 10.68 | 0.652456E+09 | 769.02 | 21-JUN-12:50 | 21.52 | 14.98 |
July | 0.526520E+10 | 20748.69 | 23-JUL-23:01 | 19.90 | 14.45 | 0.633641E+09 | 769.05 | 27-JUL-15:09 | 25.18 | 18.01 |
August | 0.589427E+10 | 19547.43 | 14-AUG-20:51 | 19.90 | 13.40 | 0.684393E+09 | 769.05 | 30-AUG-15:39 | 23.13 | 16.43 |
September | 0.329735E+10 | 19442.16 | 02-SEP-17:51 | 19.40 | 13.52 | 0.629102E+09 | 769.04 | 14-SEP-15:39 | 24.23 | 17.01 |
October | 0.515124E+09 | 18258.58 | 04-OCT-17:25 | 19.20 | 10.80 | 0.569242E+09 | 768.97 | 25-OCT-15:00 | 15.00 | 11.00 |
November | 68332904.36 | 3161.16 | 04-NOV-16:00 | 20.00 | 15.91 | 0.494627E+09 | 769.00 | 04-NOV-15:39 | 20.00 | 15.91 |
December | 9438527.23 | 452.59 | 09-DEC-15:20 | 5.60 | 4.23 | 0.498108E+09 | 655.15 | 02-DEC-15:20 | 5.60 | 4.23 |
Annual Sum or Average | 0.207740E+11 | 0.688965E+10 | ||||||||
Minimum of Months | 830070.82 | 401.06 | 5.60 | 4.23 | 0.466385E+09 | 640.19 | 5.60 | 4.23 | ||
Maximum of Months | 0.589427E+10 | 20748.69 | 20.60 | 15.91 | 0.684393E+09 | 769.05 | 25.18 | 18.01 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144440E+10 | 5473.77 | 07-JAN-11:40 | -1.0 | -1.0 | 0.726279E+09 | 1205.25 | 11-JAN-14:30 | 14.40 | 10.49 |
February | 0.118662E+10 | 4414.62 | 08-FEB-09:30 | 1.40 | 0.22 | 0.756683E+09 | 1713.62 | 27-FEB-15:39 | 19.60 | 12.34 |
March | 0.141999E+10 | 4307.33 | 02-MAR-09:15 | 5.17 | 3.59 | 0.104897E+10 | 1799.97 | 18-MAR-15:09 | 20.10 | 10.35 |
April | 0.142958E+10 | 9136.97 | 27-APR-14:40 | 26.83 | 17.14 | 0.118600E+10 | 2246.85 | 27-APR-15:30 | 27.20 | 17.10 |
May | 0.261375E+10 | 14508.04 | 15-MAY-15:00 | 23.30 | 12.62 | 0.157468E+10 | 2246.91 | 05-MAY-13:20 | 23.30 | 12.62 |
June | 0.469754E+10 | 62545.75 | 22-JUN-17:11 | 24.23 | 16.24 | 0.176332E+10 | 2246.89 | 28-JUN-12:20 | 23.33 | 15.55 |
July | 0.100105E+11 | 64264.88 | 29-JUL-17:11 | 23.17 | 15.48 | 0.179557E+10 | 2247.00 | 31-JUL-13:30 | 27.75 | 18.58 |
August | 0.108835E+11 | 62253.66 | 11-AUG-17:11 | 21.50 | 15.95 | 0.194552E+10 | 2247.02 | 10-AUG-12:00 | 21.50 | 15.95 |
September | 0.480036E+10 | 61218.31 | 10-SEP-14:15 | 22.40 | 14.54 | 0.167607E+10 | 2246.98 | 15-SEP-12:30 | 21.40 | 16.47 |
October | 0.108453E+10 | 4036.44 | 04-OCT-14:40 | 21.50 | 11.47 | 0.119025E+10 | 2246.80 | 04-OCT-15:50 | 21.20 | 11.42 |
November | 0.111503E+10 | 4355.40 | 13-NOV-10:10 | 1.88 | 1.68 | 0.851832E+09 | 2020.75 | 04-NOV-14:39 | 1.88 | 1.68 |
December | 0.127977E+10 | 4486.00 | 06-DEC-09:30 | 1.55 | 1.43 | 0.757229E+09 | 1240.11 | 05-DEC-14:30 | 1.55 | 1.43 |
Annual Sum or Average | 0.419656E+11 | 0.152724E+11 | ||||||||
Minimum of Months | 0.108453E+10 | 4036.44 | -1.0 | -1.0 | 0.726279E+09 | 1205.25 | 1.55 | 1.43 | ||
Maximum of Months | 0.108835E+11 | 64264.88 | 26.83 | 17.14 | 0.194552E+10 | 2247.02 | 27.75 | 18.58 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 | 4.99 | 0.777746E+09 | 1424.85 | 11-JAN-15:09 | 14.40 | 10.49 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 | 6.66 | 0.874249E+09 | 2248.48 | 27-FEB-15:50 | 19.50 | 12.39 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 | 0.146654E+10 | 2605.01 | 18-MAR-15:09 | 20.10 | 10.35 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 | 0.184526E+10 | 4103.66 | 27-APR-15:20 | 27.20 | 17.16 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 | 0.287492E+10 | 4936.28 | 15-MAY-15:20 | 23.50 | 12.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.29 | 0.348932E+10 | 5870.96 | 28-JUN-15:20 | 26.10 | 15.79 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.22 | 0.412081E+10 | 6711.77 | 24-JUL-15:20 | 30.03 | 18.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.75 | 0.462910E+10 | 6899.11 | 10-AUG-15:00 | 31.20 | 18.74 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 | 0.353169E+10 | 5888.21 | 14-SEP-15:09 | 23.98 | 16.97 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.42 | 0.198867E+10 | 4004.90 | 04-OCT-14:00 | 21.70 | 11.49 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 | 8.04 | 0.114363E+10 | 2845.35 | 04-NOV-14:00 | 21.10 | 15.94 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 | 3.48 | 0.842525E+09 | 1435.29 | 05-DEC-14:30 | 10.30 | 6.71 |
Annual Sum or Average | 0.00 | 0.275845E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.40 | 3.48 | 0.777746E+09 | 1424.85 | 10.30 | 6.71 | ||
Maximum of Months | 0.00 | 0.00 | 17.17 | 13.75 | 0.462910E+10 | 6899.11 | 31.20 | 18.74 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.552773E+10 | 29940.05 | 17-JAN-06:12 | 1.30 |
February | 0.413021E+10 | 29923.10 | 13-FEB-06:12 | 2.40 |
March | 0.252487E+10 | 29855.34 | 06-MAR-06:12 | 6.70 |
April | 0.134115E+10 | 29756.29 | 11-APR-05:12 | 5.60 |
May | 0.387508E+09 | 29515.60 | 18-MAY-05:01 | 5.60 |
June | 0.143256E+09 | 15012.79 | 14-JUN-05:03 | 10.00 |
July | 75716837.66 | 1517.21 | 20-JUL-06:10 | 14.45 |
August | 71450446.64 | 1499.99 | 01-AUG-06:15 | 11.33 |
September | 0.118045E+09 | 4661.15 | 28-SEP-05:05 | 8.30 |
October | 0.966418E+09 | 29640.41 | 30-OCT-05:01 | 7.20 |
November | 0.268953E+10 | 29854.45 | 13-NOV-06:12 | 1.70 |
December | 0.437692E+10 | 29859.84 | 18-DEC-06:12 | 3.53 |
Annual Sum or Average | 0.223528E+11 | |||
Minimum of Months | 71450446.64 | 1499.99 | 1.30 | |
Maximum of Months | 0.552773E+10 | 29940.05 | 14.45 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.200455E+11 | 103423.96 | 15-JAN-05:22 | -2.5 |
February | 0.138805E+11 | 104897.90 | 19-FEB-08:62 | -4.7 |
March | 0.478241E+10 | 92937.24 | 30-MAR-05:11 | 4.23 |
April | 0.140280E+10 | 55868.85 | 11-APR-04:13 | 5.20 |
May | 0.256695E+09 | 3626.06 | 17-MAY-07:00 | 8.90 |
June | 0.255386E+09 | 3494.00 | 13-JUN-07:00 | 11.70 |
July | 0.230483E+09 | 3398.33 | 28-JUL-07:00 | 15.60 |
August | 0.254958E+09 | 3737.84 | 31-AUG-07:00 | 14.00 |
September | 0.243457E+09 | 3528.52 | 27-SEP-07:00 | 8.90 |
October | 0.669547E+09 | 61389.21 | 31-OCT-05:01 | 8.58 |
November | 0.770987E+10 | 101961.93 | 30-NOV-06:01 | 5.60 |
December | 0.160488E+11 | 102105.77 | 22-DEC-06:01 | 0.60 |
Annual Sum or Average | 0.657804E+11 | |||
Minimum of Months | 0.230483E+09 | 3398.33 | -4.7 | |
Maximum of Months | 0.200455E+11 | 104897.90 | 15.60 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.346341E+11 | 57021.73 | 15-JAN-02:00 | -1.7 |
February | 0.229337E+11 | 82940.42 | 19-FEB-07:00 | -5.0 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.186109E+10 | 26015.76 | 29-NOV-21:00 | 5.00 |
December | 0.206121E+11 | 43217.24 | 25-DEC-01:52 | 1.10 |
Annual Sum or Average | 0.800410E+11 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.346341E+11 | 82940.42 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.258145E+10 | 1955.04 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.235440E+10 | 1955.04 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.269003E+10 | 1955.04 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.254196E+10 | 1955.04 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.263574E+10 | 1955.04 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.259625E+10 | 1955.04 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.258145E+10 | 1955.04 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.269003E+10 | 1955.04 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.254196E+10 | 1955.04 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.258145E+10 | 1955.04 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.248766E+10 | 1955.04 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.258145E+10 | 1955.04 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.308638E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.235440E+10 | 1955.04 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.269003E+10 | 1955.04 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.198922E+11 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.182065E+11 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.210336E+11 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.197108E+11 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.204629E+11 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.202815E+11 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.198922E+11 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.210336E+11 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.197108E+11 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.198922E+11 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.191400E+11 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.198922E+11 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.239148E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.182065E+11 | 17848.24 | 0.00 | 0.00 | |
Maximum of Months | 0.210336E+11 | 17848.24 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.294120E+11 | 26389.90 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.269196E+11 | 26389.90 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.310997E+11 | 26389.90 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.291438E+11 | 26389.90 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.302559E+11 | 26389.90 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.299876E+11 | 26389.90 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.294120E+11 | 26389.90 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.310997E+11 | 26389.90 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.291438E+11 | 26389.90 | 01-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.294120E+11 | 26389.90 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.282999E+11 | 26389.90 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.294120E+11 | 26389.90 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.353598E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.269196E+11 | 26389.90 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.310997E+11 | 26389.90 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377455E+10 |
February | 0.127628E+10 | 0.235440E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323336E+10 |
March | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313995E+10 |
April | 0.138726E+10 | 0.254196E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13454356.23 | 0.275853E+10 |
May | 0.144276E+10 | 0.263574E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1218818.35 | 0.254043E+10 |
June | 0.144276E+10 | 0.259625E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9939739.55 | 0.209343E+10 |
July | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54968493.37 | 0.156704E+10 |
August | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147028E+09 | 0.141411E+10 |
September | 0.138726E+10 | 0.254196E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1654616.29 | 0.141597E+10 |
October | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261570E+10 |
November | 0.133177E+10 | 0.248766E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297246E+10 |
December | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326683E+10 |
Annual Sum or Average | 0.168137E+11 | 0.308638E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228264E+09 | 0.307923E+11 |
Minimum of Months | 0.127628E+10 | 0.235440E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141411E+10 |
Maximum of Months | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147028E+09 | 0.377455E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133671E+11 |
February | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115232E+11 |
March | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106365E+11 |
April | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36780985.05 | 0.102736E+11 |
May | 0.339505E+10 | 0.204629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106246E+11 |
June | 0.339505E+10 | 0.202815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320221.56 | 0.981390E+10 |
July | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61210667.61 | 0.818838E+10 |
August | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163315E+09 | 0.749801E+10 |
September | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549750E+10 |
October | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.920276E+10 |
November | 0.313390E+10 | 0.191400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961494E+10 |
December | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109518E+11 |
Annual Sum or Average | 0.395654E+11 | 0.239148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261627E+09 | 0.117192E+12 |
Minimum of Months | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549750E+10 |
Maximum of Months | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163315E+09 | 0.133671E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37987249.89 | 0.262564E+11 |
February | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191851E+09 | 0.231823E+11 |
March | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83942980.97 | 0.251566E+11 |
April | 0.750829E+10 | 0.291438E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.866298E+09 | 0.270157E+11 |
May | 0.780862E+10 | 0.302559E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336235E+11 |
June | 0.780862E+10 | 0.299876E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324238E+11 |
July | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 106916.83 | 0.317790E+11 |
August | 0.810895E+10 | 0.310997E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14426636.23 | 0.310415E+11 |
September | 0.750829E+10 | 0.291438E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205654E+11 |
October | 0.750829E+10 | 0.294120E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257505E+11 |
November | 0.720796E+10 | 0.282999E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72651615.22 | 0.199121E+11 |
December | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4732376.61 | 0.197272E+11 |
Annual Sum or Average | 0.910005E+11 | 0.353598E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127200E+10 | 0.316434E+12 |
Minimum of Months | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197272E+11 |
Maximum of Months | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.866298E+09 | 0.336235E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1955.04 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 7384.62 | 24-JAN-18:00 |
February | 1680.92 | 01-FEB-08:09 | 1955.04 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 7669.84 | 13-FEB-08:00 |
March | 1680.92 | 01-MAR-08:09 | 1955.04 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7712.93 | 24-MAR-06:10 |
April | 1680.92 | 01-APR-07:10 | 1955.04 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 945.67 | 27-APR-16:10 | 5870.61 | 11-APR-07:00 |
May | 1680.92 | 01-MAY-07:10 | 1955.04 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.63 | 05-MAY-16:10 | 5858.03 | 24-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 1955.04 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 800.98 | 28-JUN-17:00 | 4536.91 | 14-JUN-06:05 |
July | 1680.92 | 01-JUL-07:10 | 1955.04 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1563.83 | 24-JUL-16:10 | 3540.05 | 12-JUL-06:05 |
August | 1680.92 | 01-AUG-07:10 | 1955.04 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2213.65 | 08-AUG-17:00 | 3964.06 | 01-AUG-07:00 |
September | 1680.92 | 01-SEP-07:10 | 1955.04 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 315.58 | 14-SEP-17:00 | 4330.03 | 26-SEP-16:05 |
October | 1680.92 | 02-OCT-07:10 | 1955.04 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 5776.59 | 31-OCT-17:00 |
November | 1680.92 | 01-NOV-07:10 | 1955.04 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 7925.26 | 29-NOV-18:00 |
December | 1680.92 | 01-DEC-08:09 | 1955.04 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7074.18 | 26-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3540.05 | |||||
Maximum of Months | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 2213.65 | 7925.26 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 18176.39 | 28-JAN-08:00 |
February | 3955.50 | 01-FEB-08:09 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 15755.82 | 13-FEB-08:00 |
March | 3955.50 | 01-MAR-08:09 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 14680.26 | 04-MAR-16:03 |
April | 3955.50 | 01-APR-07:10 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2441.53 | 01-APR-17:20 | 13818.16 | 11-APR-15:05 |
May | 3955.50 | 01-MAY-07:10 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 18016.41 | 10-MAY-15:05 |
June | 3955.50 | 01-JUN-07:10 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.95 | 28-JUN-17:47 | 14080.54 | 13-JUN-15:05 |
July | 3955.50 | 01-JUL-07:10 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1827.15 | 24-JUL-15:10 | 10846.41 | 03-JUL-16:00 |
August | 3955.50 | 01-AUG-07:10 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3150.16 | 08-AUG-17:00 | 12285.61 | 02-AUG-15:10 |
September | 3955.50 | 01-SEP-07:10 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 11501.15 | 26-SEP-15:05 |
October | 3955.50 | 02-OCT-07:10 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 13020.27 | 02-OCT-15:05 |
November | 3955.50 | 01-NOV-07:10 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 17049.42 | 29-NOV-18:00 |
December | 3955.50 | 01-DEC-08:09 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 12624.12 | 22-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10846.41 | ||||
Maximum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3150.16 | 18176.39 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 26389.90 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4237.65 | 11-JAN-14:00 | 29103.49 | 14-JAN-19:52 |
February | 9097.65 | 01-FEB-08:09 | 26389.90 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4968.32 | 24-FEB-04:00 | 36656.49 | 13-FEB-11:00 |
March | 9097.65 | 01-MAR-08:09 | 26389.90 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6177.50 | 18-MAR-16:00 | 37916.06 | 22-MAR-09:00 |
April | 9097.65 | 01-APR-07:10 | 26389.90 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27130.87 | 01-APR-16:00 | 33360.39 | 18-APR-15:55 |
May | 9097.65 | 01-MAY-07:10 | 26389.90 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 45758.61 | 10-MAY-15:00 |
June | 9097.65 | 01-JUN-07:10 | 26389.90 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 45971.12 | 13-JUN-10:00 |
July | 9097.65 | 01-JUL-07:10 | 26389.90 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.88 | 24-JUL-15:00 | 32824.93 | 03-JUL-16:00 |
August | 9097.65 | 01-AUG-07:10 | 26389.90 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1216.10 | 29-AUG-18:00 | 42486.18 | 11-AUG-04:00 |
September | 9097.65 | 01-SEP-07:10 | 26389.90 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 31996.00 | 26-SEP-15:50 |
October | 9097.65 | 02-OCT-07:10 | 26389.90 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 27179.31 | 14-OCT-11:00 |
November | 9097.65 | 01-NOV-07:10 | 26389.90 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6881.98 | 27-NOV-02:55 | 28643.27 | 29-NOV-14:00 |
December | 9097.65 | 01-DEC-08:09 | 26389.90 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2730.85 | 14-DEC-12:00 | 37359.96 | 26-DEC-14:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27179.31 | |||||
Maximum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 27130.87 | 45971.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 401.06 | 20-JAN-15:40 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 867.23 |
February | 814.74 | 27-FEB-15:50 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.47 |
March | 1470.47 | 18-MAR-16:00 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 535.90 |
April | 16811.88 | 29-APR-17:15 | 0.00 | 914.04 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.52 |
May | 19879.87 | 03-MAY-18:11 | 0.00 | 4570.22 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.88 |
June | 20135.03 | 01-JUN-18:35 | 0.00 | 914.04 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.34 |
July | 20748.69 | 23-JUL-23:01 | 0.00 | 3199.16 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.48 |
August | 19547.43 | 14-AUG-20:51 | 0.00 | 4570.22 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.01 |
September | 19442.16 | 02-SEP-17:51 | 0.00 | 4570.22 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.96 |
October | 18258.58 | 04-OCT-17:25 | 0.00 | 914.04 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.19 |
November | 3161.16 | 04-NOV-16:00 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 452.59 | 09-DEC-15:20 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 389.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 401.06 | 0.00 | 914.04 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20748.69 | 1680.92 | 4570.22 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 867.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5473.77 | 07-JAN-11:40 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1950.84 |
February | 4414.62 | 08-FEB-09:30 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1763.55 |
March | 4307.33 | 02-MAR-09:15 | 7911.00 | 35696.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1711.23 |
April | 9136.97 | 27-APR-14:40 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.05 | 0.00 |
May | 14508.04 | 15-MAY-15:00 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 551.55 |
June | 62545.75 | 22-JUN-17:11 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1080.84 |
July | 64264.88 | 29-JUL-17:11 | 0.00 | 16798.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1641.54 |
August | 62253.66 | 11-AUG-17:11 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2041.27 |
September | 61218.31 | 10-SEP-14:15 | 0.00 | 4199.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 901.92 |
October | 4036.44 | 04-OCT-14:40 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1569.67 |
November | 4355.40 | 13-NOV-10:10 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1448.04 |
December | 4486.00 | 06-DEC-09:30 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1440.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4036.44 | 0.00 | 4199.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 64264.88 | 7911.00 | 35696.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.05 | 2041.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 12418.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13230.95 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 6209.39 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5123.30 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10670.09 |
April | 0.00 | 01-APR-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8173.44 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19485.09 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6470.13 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8915.05 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11669.56 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13911.70 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7423.66 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 6209.39 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9718.87 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 9314.08 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5489.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5123.30 | |
Maximum of Months | 0.00 | 0.00 | 12418.78 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19485.09 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.861996E+11 | 66297.56 | 18-JAN-16:00 | 0.807038E+11 | 124266.18 | 15-JAN-05:30 |
February | 0.773207E+11 | 63234.65 | 13-FEB-13:00 | 0.547804E+11 | 160183.61 | 19-FEB-06:49 |
March | 0.865335E+11 | 62949.10 | 01-MAR-13:09 | 0.101319E+11 | 47883.88 | 24-MAR-05:19 |
April | 0.797800E+11 | 68902.30 | 27-APR-14:00 | 0.327734E+10 | 37734.27 | 19-APR-05:10 |
May | 0.814455E+11 | 68171.56 | 06-MAY-13:30 | 0.351107E+09 | 12515.53 | 18-MAY-05:10 |
June | 0.802949E+11 | 71694.97 | 28-JUN-14:50 | 39484425.47 | 5177.50 | 14-JUN-05:10 |
July | 0.815000E+11 | 78248.33 | 24-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.882164E+11 | 79668.20 | 10-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.812146E+11 | 70787.10 | 14-SEP-14:39 | 18482931.54 | 3407.22 | 28-SEP-05:10 |
October | 0.830318E+11 | 63870.33 | 04-OCT-14:00 | 0.170574E+10 | 31296.10 | 30-OCT-05:10 |
November | 0.817296E+11 | 66022.86 | 30-NOV-16:49 | 0.172162E+11 | 73865.18 | 29-NOV-20:49 |
December | 0.863514E+11 | 66296.02 | 26-DEC-16:19 | 0.555896E+11 | 99459.26 | 26-DEC-06:49 |
Annual Sum or Average | 0.993618E+12 | 0.223814E+12 | ||||
Minimum of Months | 0.773207E+11 | 62949.10 | 0.00 | 0.00 | ||
Maximum of Months | 0.882164E+11 | 79668.20 | 0.807038E+11 | 160183.61 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.518856E+11 | 0.145491E+11 | 0.115358E+11 | 0.00 | 0.593029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229874E+10 | 0.00 |
February | 0.474804E+11 | 0.119946E+11 | 0.105871E+11 | 0.00 | 0.516469E+10 | 0.00 | 0.00 | 27.70 | 0.00 | 0.00 | 0.00 | 0.209386E+10 | 0.00 |
March | 0.548234E+11 | 0.117079E+11 | 0.123431E+11 | 0.00 | 0.530593E+10 | 0.00 | 0.00 | 282.74 | 0.00 | 0.00 | 0.00 | 0.235323E+10 | 0.00 |
April | 0.513965E+11 | 0.975233E+10 | 0.114862E+11 | 0.00 | 0.479089E+10 | 0.00 | 0.00 | 0.139691E+09 | 0.00 | 0.00 | 0.00 | 0.221442E+10 | 0.00 |
May | 0.533545E+11 | 0.866191E+10 | 0.119357E+11 | 0.00 | 0.493017E+10 | 0.00 | 0.00 | 0.308827E+09 | 0.00 | 0.00 | 0.00 | 0.225438E+10 | 0.00 |
June | 0.528654E+11 | 0.762269E+10 | 0.118862E+11 | 0.00 | 0.495628E+10 | 0.00 | 0.00 | 0.794380E+09 | 0.00 | 0.00 | 0.00 | 0.217006E+10 | 0.00 |
July | 0.518856E+11 | 0.822677E+10 | 0.115358E+11 | 0.00 | 0.495072E+10 | 0.00 | 0.00 | 0.273455E+10 | 0.00 | 0.00 | 0.00 | 0.216658E+10 | 0.00 |
August | 0.548234E+11 | 0.944517E+10 | 0.123357E+11 | 0.00 | 0.546699E+10 | 0.00 | 0.00 | 0.392995E+10 | 0.00 | 0.00 | 0.00 | 0.221525E+10 | 0.00 |
September | 0.513965E+11 | 0.106431E+11 | 0.114788E+11 | 0.00 | 0.477775E+10 | 0.00 | 0.00 | 0.794093E+09 | 0.00 | 0.00 | 0.00 | 0.212437E+10 | 0.00 |
October | 0.518856E+11 | 0.126294E+11 | 0.115432E+11 | 0.00 | 0.475553E+10 | 0.00 | 0.00 | 11760575.39 | 0.00 | 0.00 | 0.00 | 0.220631E+10 | 0.00 |
November | 0.499276E+11 | 0.136533E+11 | 0.110862E+11 | 0.00 | 0.489149E+10 | 0.00 | 0.00 | 4323733.59 | 0.00 | 0.00 | 0.00 | 0.216673E+10 | 0.00 |
December | 0.518856E+11 | 0.149229E+11 | 0.115358E+11 | 0.00 | 0.572967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227747E+10 | 0.00 |
Annual Sum or Average | 0.623610E+12 | 0.133809E+12 | 0.139290E+12 | 0.00 | 0.616504E+11 | 0.00 | 0.00 | 0.871757E+10 | 0.00 | 0.00 | 0.00 | 0.265414E+11 | 0.00 |
Minimum of Months | 0.474804E+11 | 0.762269E+10 | 0.105871E+11 | 0.00 | 0.475553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209386E+10 | 0.00 |
Maximum of Months | 0.548234E+11 | 0.149229E+11 | 0.123431E+11 | 0.00 | 0.593029E+10 | 0.00 | 0.00 | 0.392995E+10 | 0.00 | 0.00 | 0.00 | 0.235323E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.807038E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.547804E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.101319E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.327734E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.351107E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 39484425.47 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 18482931.54 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.170574E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.172162E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.555896E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.223814E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.807038E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 46193.18 | 02-JAN-09:09 | 8532.22 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 5043.70 | 02-JAN-07:19 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 46193.18 | 01-FEB-09:09 | 8532.22 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 5043.70 | 06-FEB-07:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 46193.18 | 01-MAR-09:09 | 8532.22 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 4773.11 | 02-MAR-07:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 46193.18 | 01-APR-08:09 | 8532.22 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 4773.11 | 11-APR-07:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 46193.18 | 01-MAY-08:09 | 8532.22 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 4773.11 | 03-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 46193.18 | 01-JUN-08:09 | 8532.22 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 4773.11 | 09-JUN-13:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 46193.18 | 01-JUL-08:09 | 8532.22 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 7078.40 | 24-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 46193.18 | 01-AUG-08:09 | 8532.22 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 7078.40 | 08-AUG-13:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 46193.18 | 01-SEP-08:09 | 8532.22 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 4773.11 | 08-SEP-13:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 46193.18 | 02-OCT-08:09 | 8532.22 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 4773.11 | 04-OCT-12:39 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 46193.18 | 01-NOV-08:09 | 8532.22 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 5043.70 | 29-NOV-17:19 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 46193.18 | 01-DEC-09:09 | 8532.22 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 5043.70 | 01-DEC-07:49 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 46193.18 | 8532.22 | 10112.62 | 0.00 | 4773.11 | 0.00 | 0.00 | |||||
Maximum of Months | 46193.18 | 8532.22 | 10112.62 | 0.00 | 7078.40 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2398.98 | 31-JAN-12:09 | 0.00 |
February | 0.02 | 27-FEB-14:39 | 0.00 | 0.00 | 0.00 | 2404.17 | 09-FEB-12:50 | 0.00 |
March | 0.11 | 18-MAR-13:50 | 0.00 | 0.00 | 0.00 | 2389.48 | 01-MAR-12:00 | 0.00 |
April | 6030.47 | 27-APR-14:00 | 0.00 | 0.00 | 0.00 | 2293.97 | 03-APR-11:00 | 0.00 |
May | 5343.75 | 06-MAY-13:30 | 0.00 | 0.00 | 0.00 | 2122.61 | 05-MAY-11:50 | 0.00 |
June | 9350.96 | 20-JUN-17:30 | 0.00 | 0.00 | 0.00 | 1961.60 | 01-JUN-11:00 | 0.00 |
July | 13131.28 | 24-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1806.77 | 01-JUL-11:09 | 0.00 |
August | 14609.01 | 10-AUG-15:09 | 0.00 | 0.00 | 0.00 | 1800.71 | 30-AUG-11:09 | 0.00 |
September | 7963.88 | 10-SEP-14:20 | 0.00 | 0.00 | 0.00 | 1836.87 | 30-SEP-11:00 | 0.00 |
October | 2097.83 | 04-OCT-17:30 | 0.00 | 0.00 | 0.00 | 2015.58 | 30-OCT-11:39 | 0.00 |
November | 576.76 | 04-NOV-14:00 | 0.00 | 0.00 | 0.00 | 2192.34 | 30-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2309.45 | 26-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1800.71 | 0.00 | ||
Maximum of Months | 14609.01 | 0.00 | 0.00 | 0.00 | 2404.17 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 66297.56 | 18-JAN-16:00 | 40988.70 | 10112.62 | 8532.22 | 0.00 | 5043.70 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 63234.65 | 13-FEB-13:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 5043.70 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 62949.10 | 01-MAR-13:09 | 46193.18 | 10112.62 | 0.00 | 0.00 | 4773.11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 68902.30 | 27-APR-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 4773.11 | 0.00 | 0.00 | 6030.47 | 0.00 |
May | 68171.56 | 06-MAY-13:30 | 46193.18 | 10112.62 | 0.00 | 0.00 | 4773.11 | 0.00 | 0.00 | 5343.75 | 0.00 |
June | 71694.97 | 28-JUN-14:50 | 46193.18 | 10112.62 | 0.00 | 0.00 | 4773.11 | 0.00 | 0.00 | 8847.55 | 0.00 |
July | 78248.33 | 24-JUL-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 7078.40 | 0.00 | 0.00 | 13100.67 | 0.00 |
August | 79668.20 | 10-AUG-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 7078.40 | 0.00 | 0.00 | 14521.73 | 0.00 |
September | 70787.10 | 14-SEP-14:39 | 46193.18 | 10112.62 | 0.00 | 0.00 | 4773.11 | 0.00 | 0.00 | 7942.77 | 0.00 |
October | 63870.33 | 04-OCT-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 4773.11 | 0.00 | 0.00 | 1020.05 | 0.00 |
November | 66022.86 | 30-NOV-16:49 | 40988.70 | 10112.62 | 8532.22 | 0.00 | 4773.11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 66296.02 | 26-DEC-16:19 | 40988.70 | 10112.62 | 8532.22 | 0.00 | 5043.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 62949.10 | 40988.70 | 10112.62 | 0.00 | 0.00 | 4773.11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 79668.20 | 46193.18 | 10112.62 | 8532.22 | 0.00 | 7078.40 | 0.00 | 0.00 | 14521.73 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 124266.18 | 15-JAN-05:30 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 160183.61 | 19-FEB-06:49 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 47883.88 | 24-MAR-05:19 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 37734.27 | 19-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 12515.53 | 18-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 5177.50 | 14-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 3407.22 | 28-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 31296.10 | 30-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 73865.18 | 29-NOV-20:49 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 99459.26 | 26-DEC-06:49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 160183.61 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.33 | 18.66 | 9.33 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
February | 11.83 | 18.03 | 7.83 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
March | 8.83 | 19.57 | 8.50 | 19.66 | 0.00 | 19.66 | 0.00 | 19.66 |
April | 5.33 | 20.09 | 5.33 | 20.09 | 0.17 | 20.16 | 0.00 | 20.16 |
May | 1.17 | 20.47 | 1.17 | 20.47 | 1.00 | 21.67 | 0.00 | 21.67 |
June | 0.17 | 20.52 | 0.17 | 20.52 | 4.00 | 24.27 | 0.00 | 24.27 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 24.63 | 0.17 | 24.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 24.64 | 0.50 | 24.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.51 | 0.00 | 24.51 |
October | 3.50 | 20.26 | 3.50 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
November | 7.33 | 19.59 | 6.83 | 19.75 | 0.00 | 19.75 | 0.00 | 19.75 |
December | 11.00 | 18.64 | 8.67 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
Annual Sum or Average | 60.50 | 19.04 | 51.33 | 19.37 | 33.50 | 20.58 | 0.67 | 20.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.65 | 0.00 | 18.65 |
Maximum of Months | 11.83 | 20.52 | 9.33 | 20.52 | 14.00 | 24.64 | 0.50 | 24.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 99.83 | 14.63 | 4.67 | 14.63 | 0.00 | 14.63 | 0.00 | 14.63 |
February | 63.50 | 14.58 | 3.50 | 14.58 | 0.00 | 14.58 | 0.00 | 14.58 |
March | 18.00 | 14.85 | 2.50 | 14.84 | 0.00 | 14.84 | 0.00 | 14.84 |
April | 3.50 | 14.93 | 0.50 | 14.93 | 0.00 | 14.93 | 0.00 | 14.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.38 | 0.00 | 27.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.44 | 0.00 | 27.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.00 | 27.26 |
October | 1.17 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
November | 38.33 | 14.85 | 2.17 | 14.84 | 0.00 | 14.84 | 0.00 | 14.84 |
December | 83.67 | 14.75 | 4.67 | 14.75 | 0.00 | 14.75 | 0.00 | 14.75 |
Annual Sum or Average | 308.00 | 14.70 | 18.00 | 14.70 | 5.00 | 14.89 | 0.00 | 14.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 99.83 | 14.98 | 4.67 | 14.98 | 2.67 | 27.44 | 0.00 | 27.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.05 | 300.00 | 21.05 | 300.00 | 21.05 |
February | 276.00 | 21.23 | 243.33 | 21.15 | 243.33 | 21.12 |
March | 324.00 | 21.53 | 240.17 | 21.36 | 240.17 | 21.28 |
April | 287.83 | 22.17 | 120.67 | 21.86 | 119.83 | 21.69 |
May | 266.83 | 23.10 | 38.33 | 23.00 | 21.33 | 22.87 |
June | 182.83 | 23.33 | 38.17 | 23.43 | 0.17 | 23.43 |
July | 69.50 | 23.62 | 149.83 | 23.81 | 0.00 | 23.81 |
August | 48.33 | 23.48 | 190.33 | 23.82 | 0.50 | 23.82 |
September | 155.67 | 23.43 | 72.50 | 23.57 | 0.33 | 23.57 |
October | 298.67 | 22.37 | 83.67 | 22.09 | 83.67 | 21.91 |
November | 288.00 | 21.39 | 220.17 | 21.25 | 220.17 | 21.20 |
December | 300.00 | 21.07 | 300.00 | 21.07 | 300.00 | 21.07 |
Annual Sum or Average | 2797.67 | 22.00 | 1997.17 | 21.89 | 1529.50 | 21.69 |
Minimum of Months | 48.33 | 21.05 | 38.17 | 21.05 | 0.00 | 21.05 |
Maximum of Months | 324.00 | 23.62 | 300.00 | 23.82 | 300.00 | 23.82 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 16.30 | 300.00 | 16.30 | 300.00 | 16.30 |
February | 276.00 | 17.24 | 265.00 | 17.14 | 265.00 | 17.10 |
March | 324.00 | 18.68 | 286.67 | 18.47 | 286.67 | 18.40 |
April | 272.83 | 20.03 | 182.67 | 19.78 | 159.00 | 19.42 |
May | 188.17 | 21.96 | 142.83 | 22.76 | 49.83 | 22.32 |
June | 114.33 | 23.19 | 201.17 | 25.06 | 28.83 | 25.04 |
July | 148.50 | 25.75 | 244.33 | 26.21 | 108.67 | 26.31 |
August | 149.83 | 25.84 | 275.50 | 26.24 | 114.00 | 26.34 |
September | 136.67 | 23.60 | 186.50 | 25.02 | 40.67 | 25.06 |
October | 267.50 | 20.09 | 189.67 | 19.85 | 170.33 | 19.56 |
November | 285.00 | 17.79 | 271.17 | 17.70 | 269.83 | 17.66 |
December | 300.00 | 16.60 | 300.00 | 16.60 | 300.00 | 16.60 |
Annual Sum or Average | 2762.83 | 19.65 | 2845.50 | 20.19 | 2092.83 | 19.78 |
Minimum of Months | 114.33 | 16.30 | 142.83 | 16.30 | 28.83 | 16.30 |
Maximum of Months | 324.00 | 25.84 | 300.00 | 26.24 | 300.00 | 26.34 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 10.89 | 300.00 | 10.89 | 300.00 | 10.89 |
February | 276.00 | 11.96 | 276.00 | 11.96 | 276.00 | 11.96 |
March | 324.00 | 14.43 | 324.00 | 14.43 | 324.00 | 14.43 |
April | 300.00 | 16.88 | 274.83 | 16.65 | 274.83 | 16.56 |
May | 286.00 | 20.60 | 128.33 | 20.26 | 113.17 | 19.92 |
June | 202.17 | 21.95 | 119.33 | 22.81 | 36.50 | 22.58 |
July | 156.33 | 26.10 | 216.17 | 26.58 | 92.50 | 26.93 |
August | 156.83 | 27.41 | 273.83 | 27.15 | 126.17 | 27.46 |
September | 176.33 | 22.70 | 138.50 | 23.84 | 37.50 | 23.84 |
October | 300.00 | 17.64 | 255.83 | 17.31 | 255.83 | 17.19 |
November | 288.00 | 13.43 | 288.00 | 13.43 | 288.00 | 13.43 |
December | 300.00 | 11.30 | 300.00 | 11.30 | 300.00 | 11.30 |
Annual Sum or Average | 3065.67 | 16.82 | 2894.83 | 16.95 | 2424.50 | 16.50 |
Minimum of Months | 156.33 | 10.89 | 119.33 | 10.89 | 36.50 | 10.89 |
Maximum of Months | 324.00 | 27.41 | 324.00 | 27.15 | 324.00 | 27.46 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 99.34 | 27.70 | 0.50 | 99.34 | 0.00 | 0.00 | 0.00 | 27-FEB-14:40 | 0.00 | 01-FEB-00:05 | 0.09 | 27-FEB-14:40 | 0.09 | 27-FEB-14:40 | 0.00 | 27-FEB-14:40 | 0.02 | 27-FEB-14:40 | 0.00 | 01-FEB-00:05 |
March | 1014.40 | 282.74 | 1.83 | 993.88 | 20.52 | 0.00 | 0.00 | 18-MAR-13:50 | 0.00 | 01-MAR-00:10 | 0.38 | 18-MAR-13:50 | 0.38 | 18-MAR-13:50 | 0.02 | 10-MAR-13:50 | 0.11 | 18-MAR-13:50 | 0.00 | 01-MAR-00:10 |
April | 0.331159E+09 | 89714066.99 | 23.47 | 0.317049E+09 | 14110128.36 | 0.00 | 1.00 | 26-APR-17:13 | 0.00 | 01-APR-00:10 | 19556.56 | 27-APR-18:35 | 18918.59 | 26-APR-17:13 | 2414.65 | 29-APR-17:15 | 4622.74 | 27-APR-18:35 | 0.00 | 01-APR-00:10 |
May | 0.745924E+09 | 0.194767E+09 | 50.50 | 0.670167E+09 | 75756847.46 | 0.00 | 1.00 | 03-MAY-17:15 | 0.00 | 01-MAY-00:10 | 20488.18 | 05-MAY-17:15 | 18937.99 | 04-MAY-17:11 | 5739.52 | 06-MAY-18:13 | 4812.31 | 05-MAY-17:15 | 0.00 | 01-MAY-00:10 |
June | 0.160786E+10 | 0.419647E+09 | 106.22 | 0.153444E+10 | 73416260.49 | 0.00 | 1.00 | 01-JUN-17:25 | 0.00 | 01-JUN-00:10 | 19816.02 | 22-JUN-17:43 | 19297.90 | 22-JUN-17:08 | 3984.53 | 29-JUN-17:25 | 4743.32 | 28-JUN-17:08 | 0.00 | 01-JUN-00:10 |
July | 0.418594E+10 | 0.109092E+10 | 193.87 | 0.362346E+10 | 0.562481E+09 | 0.00 | 1.00 | 05-JUL-17:15 | 0.00 | 01-JUL-00:10 | 20892.43 | 27-JUL-18:23 | 19445.85 | 19-JUL-17:08 | 6680.58 | 15-JUL-20:25 | 4917.57 | 31-JUL-17:06 | 0.00 | 01-JUL-00:10 |
August | 0.549119E+10 | 0.145303E+10 | 238.21 | 0.475879E+10 | 0.732405E+09 | 0.00 | 1.00 | 01-AUG-17:15 | 0.00 | 01-AUG-00:10 | 20663.93 | 26-AUG-17:11 | 19086.92 | 08-AUG-21:55 | 7667.02 | 26-AUG-03:23 | 5033.08 | 29-AUG-17:08 | 0.00 | 01-AUG-00:10 |
September | 0.164109E+10 | 0.423610E+09 | 93.84 | 0.136457E+10 | 0.276522E+09 | 0.00 | 1.00 | 01-SEP-17:15 | 0.00 | 01-SEP-00:10 | 20349.19 | 22-SEP-17:11 | 18675.00 | 08-SEP-17:11 | 6626.13 | 23-SEP-21:43 | 4784.95 | 22-SEP-17:11 | 0.00 | 01-SEP-00:10 |
October | 44031375.11 | 11760523.41 | 8.92 | 44031297.60 | 77.51 | 0.00 | 1.00 | 04-OCT-17:25 | 0.00 | 01-OCT-00:10 | 17719.68 | 04-OCT-17:25 | 17719.68 | 04-OCT-17:25 | 0.03 | 06-OCT-12:10 | 4195.66 | 04-OCT-17:25 | 0.00 | 01-OCT-00:10 |
November | 15810403.04 | 4323733.59 | 3.17 | 12018245.31 | 3792157.73 | 0.00 | 0.12 | 04-NOV-15:00 | 0.00 | 01-NOV-00:05 | 2117.43 | 04-NOV-15:00 | 1636.21 | 04-NOV-15:00 | 481.23 | 04-NOV-15:00 | 576.76 | 04-NOV-15:00 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.140630E+11 | 0.368777E+10 | 720.52 | 0.123245E+11 | 0.173848E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.549119E+10 | 0.145303E+10 | 238.21 | 0.475879E+10 | 0.732405E+09 | 0.00 | 1.00 | 0.00 | 20892.43 | 19445.85 | 7667.02 | 5033.08 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.167093E+09 | 49976481.04 | 6.00 | 0.162457E+09 | 4635920.87 | 0.00 | 0.23 | 27-APR-14:50 | 0.00 | 01-APR-00:10 | 13192.73 | 27-APR-14:50 | 12720.79 | 27-APR-14:50 | 504.62 | 27-APR-15:20 | 3944.91 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.394551E+09 | 0.114061E+09 | 18.50 | 0.360880E+09 | 33671258.00 | 0.00 | 0.19 | 04-MAY-15:00 | 0.00 | 01-MAY-00:10 | 11351.55 | 06-MAY-13:30 | 10599.84 | 04-MAY-15:00 | 2123.76 | 06-MAY-13:30 | 3227.33 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.131026E+10 | 0.374732E+09 | 37.69 | 0.127192E+10 | 38344684.60 | 0.00 | 1.00 | 11-JUN-14:35 | 0.00 | 01-JUN-00:10 | 65862.66 | 22-JUN-18:02 | 64500.58 | 28-JUN-17:11 | 6334.31 | 22-JUN-18:25 | 16877.90 | 28-JUN-17:11 | 0.00 | 01-JUN-00:10 |
July | 0.578793E+10 | 0.164363E+10 | 111.22 | 0.517196E+10 | 0.615969E+09 | 0.00 | 1.00 | 07-JUL-17:33 | 0.00 | 01-JUL-00:10 | 69519.77 | 27-JUL-18:45 | 64315.82 | 24-JUL-19:03 | 18991.92 | 15-JUL-18:03 | 17634.10 | 31-JUL-17:43 | 0.00 | 01-JUL-00:10 |
August | 0.859384E+10 | 0.247692E+10 | 130.02 | 0.772476E+10 | 0.869078E+09 | 0.00 | 1.00 | 06-AUG-14:05 | 0.00 | 01-AUG-00:10 | 68110.02 | 13-AUG-13:53 | 64699.81 | 07-AUG-17:43 | 13202.25 | 11-AUG-17:11 | 18084.75 | 10-AUG-17:06 | 0.00 | 01-AUG-00:10 |
September | 0.130300E+10 | 0.370484E+09 | 41.18 | 0.106983E+10 | 0.233177E+09 | 0.00 | 1.00 | 10-SEP-14:15 | 0.00 | 01-SEP-00:10 | 66929.64 | 14-SEP-17:11 | 60847.03 | 10-SEP-14:15 | 9074.35 | 14-SEP-17:11 | 16697.98 | 14-SEP-17:11 | 0.00 | 01-SEP-00:10 |
October | 175.80 | 51.98 | 0.33 | 175.80 | -0.0 | 0.00 | 0.00 | 04-OCT-12:40 | 0.00 | 01-OCT-00:10 | 0.29 | 04-OCT-12:40 | 0.29 | 04-OCT-12:40 | 0.00 | 01-OCT-00:10 | 0.09 | 04-OCT-12:40 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.175567E+11 | 0.502980E+10 | 344.95 | 0.157618E+11 | 0.179488E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.859384E+10 | 0.247692E+10 | 130.02 | 0.772476E+10 | 0.869078E+09 | 0.00 | 1.00 | 0.00 | 69519.77 | 64699.81 | 18991.92 | 18084.75 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.37 | 11.99 | 28.38 | 17.40 | 128.97 | 0.00 | 0.00 | 0.00 |
February | 71.72 | 26.71 | 45.01 | 52.02 | 110.29 | 0.00 | 0.00 | 0.00 |
March | 101.02 | 34.13 | 66.89 | 87.48 | 88.81 | 0.00 | 0.00 | 0.00 |
April | 153.35 | 58.51 | 94.84 | 157.14 | 74.46 | 0.00 | 0.00 | 0.00 |
May | 197.81 | 80.45 | 117.36 | 213.70 | 71.71 | 0.00 | 0.00 | 0.00 |
June | 190.18 | 73.85 | 116.33 | 205.73 | 61.34 | 0.00 | 0.00 | 0.00 |
July | 235.35 | 123.89 | 111.46 | 280.16 | 58.87 | 0.00 | 0.00 | 0.00 |
August | 194.28 | 99.10 | 95.18 | 234.18 | 58.40 | 0.00 | 0.00 | 0.00 |
September | 158.80 | 76.40 | 82.40 | 174.69 | 79.63 | 0.00 | 0.00 | 0.00 |
October | 90.44 | 37.00 | 53.44 | 82.42 | 87.56 | 0.00 | 0.00 | 0.00 |
November | 45.00 | 12.82 | 32.18 | 26.00 | 100.96 | 0.00 | 0.00 | 0.00 |
December | 38.18 | 13.39 | 24.79 | 21.62 | 129.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.71 | 54.23 | 72.48 | 129.89 | 87.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 38.18 | 11.99 | 24.79 | 17.40 | 58.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.35 | 123.89 | 117.36 | 280.16 | 129.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.37 | 11.99 | 28.38 | 17.40 | 128.97 | 0.00 | 0.00 | 0.00 |
February | 71.72 | 26.71 | 45.01 | 52.02 | 110.29 | 0.00 | 0.00 | 0.00 |
March | 101.02 | 34.13 | 66.89 | 87.48 | 88.81 | 0.00 | 0.00 | 0.00 |
April | 153.35 | 58.51 | 94.84 | 157.14 | 74.46 | 0.00 | 0.00 | 0.00 |
May | 197.81 | 80.45 | 117.36 | 213.70 | 71.71 | 0.00 | 0.00 | 0.00 |
June | 190.18 | 73.85 | 116.33 | 205.73 | 61.34 | 0.00 | 0.00 | 0.00 |
July | 235.35 | 123.89 | 111.46 | 280.16 | 58.87 | 0.00 | 0.00 | 0.00 |
August | 194.28 | 99.10 | 95.18 | 234.18 | 58.40 | 0.00 | 0.00 | 0.00 |
September | 158.80 | 76.40 | 82.40 | 174.69 | 79.63 | 0.00 | 0.00 | 0.00 |
October | 90.44 | 37.00 | 53.44 | 82.42 | 87.56 | 0.00 | 0.00 | 0.00 |
November | 45.00 | 12.82 | 32.18 | 26.00 | 100.96 | 0.00 | 0.00 | 0.00 |
December | 38.18 | 13.39 | 24.79 | 21.62 | 129.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.71 | 54.23 | 72.48 | 129.89 | 87.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 38.18 | 11.99 | 24.79 | 17.40 | 58.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.35 | 123.89 | 117.36 | 280.16 | 129.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.83 | 0.00 | 13.83 | 0.66 | 79.44 | 0.00 | 0.00 | 0.00 |
February | 21.52 | 0.00 | 21.52 | 4.85 | 68.35 | 0.00 | 0.00 | 0.00 |
March | 31.71 | 0.00 | 31.71 | 14.49 | 53.74 | 0.00 | 0.00 | 0.00 |
April | 44.95 | 0.22 | 44.73 | 30.42 | 43.28 | 0.00 | 0.00 | 0.00 |
May | 57.71 | 1.69 | 56.03 | 44.50 | 40.45 | 0.00 | 0.00 | 0.00 |
June | 60.71 | 3.99 | 56.72 | 49.73 | 33.71 | 0.00 | 0.00 | 0.00 |
July | 57.75 | 4.55 | 53.21 | 52.25 | 32.27 | 0.00 | 0.00 | 0.00 |
August | 46.91 | 1.43 | 45.48 | 43.17 | 32.24 | 0.00 | 0.00 | 0.00 |
September | 36.30 | 0.02 | 36.28 | 23.46 | 47.46 | 0.00 | 0.00 | 0.00 |
October | 24.86 | 0.00 | 24.86 | 10.74 | 52.51 | 0.00 | 0.00 | 0.00 |
November | 15.66 | 0.00 | 15.66 | 2.52 | 61.32 | 0.00 | 0.00 | 0.00 |
December | 11.75 | 0.00 | 11.75 | 0.41 | 78.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.38 | 1.00 | 34.38 | 23.21 | 51.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 11.75 | 0.00 | 11.75 | 0.41 | 32.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.71 | 4.55 | 56.72 | 52.25 | 79.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.83 | 0.00 | 13.83 | 0.66 | 79.44 | 0.00 | 0.00 | 0.00 |
February | 21.52 | 0.00 | 21.52 | 4.85 | 68.35 | 0.00 | 0.00 | 0.00 |
March | 31.71 | 0.00 | 31.71 | 14.49 | 53.74 | 0.00 | 0.00 | 0.00 |
April | 44.95 | 0.22 | 44.73 | 30.42 | 43.28 | 0.00 | 0.00 | 0.00 |
May | 57.71 | 1.69 | 56.03 | 44.49 | 40.45 | 0.00 | 0.00 | 0.00 |
June | 60.71 | 3.99 | 56.72 | 49.73 | 33.71 | 0.00 | 0.00 | 0.00 |
July | 57.75 | 4.55 | 53.21 | 52.25 | 32.27 | 0.00 | 0.00 | 0.00 |
August | 46.91 | 1.43 | 45.48 | 43.17 | 32.23 | 0.00 | 0.00 | 0.00 |
September | 36.30 | 0.02 | 36.28 | 23.46 | 47.45 | 0.00 | 0.00 | 0.00 |
October | 24.86 | 0.00 | 24.86 | 10.74 | 52.51 | 0.00 | 0.00 | 0.00 |
November | 15.66 | 0.00 | 15.66 | 2.52 | 61.32 | 0.00 | 0.00 | 0.00 |
December | 11.75 | 0.00 | 11.75 | 0.41 | 78.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.37 | 1.00 | 34.38 | 23.21 | 51.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 11.75 | 0.00 | 11.75 | 0.41 | 32.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.71 | 4.55 | 56.72 | 52.25 | 79.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.57 | 4.49 | 15.08 | 14.80 | 61.34 | 33.83 | 0.00 | 0.00 |
February | 34.87 | 12.49 | 22.39 | 36.29 | 56.31 | 34.33 | 0.00 | 0.00 |
March | 59.12 | 25.62 | 33.51 | 67.91 | 49.53 | 8.83 | 0.00 | 0.00 |
April | 93.00 | 47.13 | 45.87 | 116.65 | 44.88 | 4.83 | 0.00 | 0.00 |
May | 120.05 | 61.27 | 58.78 | 149.34 | 50.69 | 0.00 | 0.00 | 0.00 |
June | 131.08 | 76.11 | 54.97 | 162.43 | 47.47 | 0.00 | 0.00 | 0.00 |
July | 136.77 | 89.61 | 47.16 | 172.01 | 52.77 | 0.00 | 0.00 | 0.00 |
August | 110.34 | 69.86 | 40.49 | 136.46 | 57.63 | 0.00 | 0.00 | 0.00 |
September | 78.58 | 43.78 | 34.80 | 90.19 | 66.49 | 5.83 | 0.00 | 0.00 |
October | 47.22 | 22.59 | 24.63 | 51.98 | 56.01 | 13.83 | 0.00 | 0.00 |
November | 23.33 | 6.33 | 17.00 | 21.39 | 47.92 | 48.33 | 0.00 | 0.00 |
December | 17.12 | 4.83 | 12.29 | 13.13 | 60.99 | 62.33 | 0.00 | 0.00 |
Annual Sum or Average | 72.80 | 38.84 | 33.96 | 86.33 | 54.35 | 212.17 | 0.00 | 0.00 |
Minimum of Months | 17.12 | 4.49 | 12.29 | 13.13 | 44.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.77 | 89.61 | 58.78 | 172.01 | 66.49 | 62.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.57 | 4.49 | 15.08 | 14.80 | 61.34 | 33.83 | 0.00 | 0.00 |
February | 34.87 | 12.49 | 22.39 | 36.29 | 56.31 | 34.33 | 0.00 | 0.00 |
March | 59.12 | 25.62 | 33.51 | 67.91 | 49.53 | 8.83 | 0.00 | 0.00 |
April | 93.00 | 47.13 | 45.87 | 116.65 | 44.88 | 4.83 | 0.00 | 0.00 |
May | 120.05 | 61.27 | 58.78 | 149.34 | 50.69 | 0.00 | 0.00 | 0.00 |
June | 131.08 | 76.11 | 54.97 | 162.43 | 47.47 | 0.00 | 0.00 | 0.00 |
July | 136.77 | 89.61 | 47.16 | 172.01 | 52.77 | 0.00 | 0.00 | 0.00 |
August | 110.34 | 69.86 | 40.49 | 136.46 | 57.63 | 0.00 | 0.00 | 0.00 |
September | 78.58 | 43.78 | 34.80 | 90.19 | 66.49 | 5.83 | 0.00 | 0.00 |
October | 47.22 | 22.59 | 24.63 | 51.98 | 56.01 | 13.83 | 0.00 | 0.00 |
November | 23.33 | 6.33 | 17.00 | 21.39 | 47.92 | 48.33 | 0.00 | 0.00 |
December | 17.12 | 4.83 | 12.29 | 13.13 | 60.99 | 62.33 | 0.00 | 0.00 |
Annual Sum or Average | 72.80 | 38.84 | 33.96 | 86.33 | 54.35 | 212.17 | 0.00 | 0.00 |
Minimum of Months | 17.12 | 4.49 | 12.29 | 13.13 | 44.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.77 | 89.61 | 58.78 | 172.01 | 66.49 | 62.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.57 | 4.49 | 15.08 | 14.80 | 61.34 | 33.83 | 0.00 | 0.00 |
February | 34.87 | 12.49 | 22.39 | 36.29 | 56.31 | 34.33 | 0.00 | 0.00 |
March | 59.12 | 25.62 | 33.51 | 67.91 | 49.53 | 8.83 | 0.00 | 0.00 |
April | 93.00 | 47.13 | 45.87 | 116.65 | 44.88 | 4.83 | 0.00 | 0.00 |
May | 120.05 | 61.27 | 58.78 | 149.34 | 50.69 | 0.00 | 0.00 | 0.00 |
June | 131.08 | 76.11 | 54.97 | 162.43 | 47.47 | 0.00 | 0.00 | 0.00 |
July | 136.77 | 89.61 | 47.16 | 172.01 | 52.77 | 0.00 | 0.00 | 0.00 |
August | 110.34 | 69.86 | 40.49 | 136.46 | 57.63 | 0.00 | 0.00 | 0.00 |
September | 78.58 | 43.78 | 34.80 | 90.19 | 66.49 | 5.83 | 0.00 | 0.00 |
October | 47.22 | 22.59 | 24.63 | 51.98 | 56.01 | 13.83 | 0.00 | 0.00 |
November | 23.33 | 6.33 | 17.00 | 21.39 | 47.92 | 48.33 | 0.00 | 0.00 |
December | 17.12 | 4.83 | 12.29 | 13.13 | 60.99 | 62.33 | 0.00 | 0.00 |
Annual Sum or Average | 72.80 | 38.84 | 33.96 | 86.33 | 54.35 | 212.17 | 0.00 | 0.00 |
Minimum of Months | 17.12 | 4.49 | 12.29 | 13.13 | 44.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.77 | 89.61 | 58.78 | 172.01 | 66.49 | 62.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.57 | 4.49 | 15.08 | 14.80 | 61.34 | 33.83 | 0.00 | 0.00 |
February | 34.87 | 12.49 | 22.39 | 36.29 | 56.31 | 34.33 | 0.00 | 0.00 |
March | 59.12 | 25.62 | 33.51 | 67.91 | 49.53 | 8.83 | 0.00 | 0.00 |
April | 93.00 | 47.13 | 45.87 | 116.65 | 44.88 | 4.83 | 0.00 | 0.00 |
May | 120.05 | 61.27 | 58.78 | 149.34 | 50.69 | 0.00 | 0.00 | 0.00 |
June | 131.08 | 76.11 | 54.97 | 162.43 | 47.47 | 0.00 | 0.00 | 0.00 |
July | 136.77 | 89.61 | 47.16 | 172.01 | 52.77 | 0.00 | 0.00 | 0.00 |
August | 110.34 | 69.86 | 40.49 | 136.46 | 57.63 | 0.00 | 0.00 | 0.00 |
September | 78.58 | 43.78 | 34.80 | 90.19 | 66.49 | 5.83 | 0.00 | 0.00 |
October | 47.22 | 22.59 | 24.63 | 51.98 | 56.01 | 13.83 | 0.00 | 0.00 |
November | 23.33 | 6.33 | 17.00 | 21.39 | 47.92 | 48.33 | 0.00 | 0.00 |
December | 17.12 | 4.83 | 12.29 | 13.13 | 60.99 | 62.33 | 0.00 | 0.00 |
Annual Sum or Average | 72.80 | 38.84 | 33.96 | 86.33 | 54.35 | 212.17 | 0.00 | 0.00 |
Minimum of Months | 17.12 | 4.49 | 12.29 | 13.13 | 44.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.77 | 89.61 | 58.78 | 172.01 | 66.49 | 62.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.57 | 4.49 | 15.08 | 14.80 | 61.34 | 33.83 | 0.00 | 0.00 |
February | 34.87 | 12.49 | 22.39 | 36.29 | 56.31 | 34.33 | 0.00 | 0.00 |
March | 59.12 | 25.62 | 33.51 | 67.91 | 49.53 | 8.83 | 0.00 | 0.00 |
April | 93.00 | 47.13 | 45.87 | 116.65 | 44.88 | 4.83 | 0.00 | 0.00 |
May | 120.05 | 61.27 | 58.78 | 149.34 | 50.69 | 0.00 | 0.00 | 0.00 |
June | 131.08 | 76.11 | 54.97 | 162.43 | 47.47 | 0.00 | 0.00 | 0.00 |
July | 136.77 | 89.61 | 47.16 | 172.01 | 52.77 | 0.00 | 0.00 | 0.00 |
August | 110.34 | 69.86 | 40.49 | 136.46 | 57.63 | 0.00 | 0.00 | 0.00 |
September | 78.58 | 43.78 | 34.80 | 90.19 | 66.49 | 5.83 | 0.00 | 0.00 |
October | 47.22 | 22.59 | 24.63 | 51.98 | 56.01 | 13.83 | 0.00 | 0.00 |
November | 23.33 | 6.33 | 17.00 | 21.39 | 47.92 | 48.33 | 0.00 | 0.00 |
December | 17.12 | 4.83 | 12.29 | 13.13 | 60.99 | 62.33 | 0.00 | 0.00 |
Annual Sum or Average | 72.80 | 38.84 | 33.96 | 86.33 | 54.35 | 212.17 | 0.00 | 0.00 |
Minimum of Months | 17.12 | 4.49 | 12.29 | 13.13 | 44.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.77 | 89.61 | 58.78 | 172.01 | 66.49 | 62.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.57 | 4.49 | 15.08 | 14.80 | 61.34 | 33.83 | 0.00 | 0.00 |
February | 34.87 | 12.49 | 22.39 | 36.29 | 56.31 | 34.33 | 0.00 | 0.00 |
March | 59.12 | 25.62 | 33.51 | 67.91 | 49.53 | 8.83 | 0.00 | 0.00 |
April | 93.00 | 47.13 | 45.87 | 116.65 | 44.88 | 4.83 | 0.00 | 0.00 |
May | 120.05 | 61.27 | 58.78 | 149.34 | 50.69 | 0.00 | 0.00 | 0.00 |
June | 131.08 | 76.11 | 54.97 | 162.43 | 47.47 | 0.00 | 0.00 | 0.00 |
July | 136.77 | 89.61 | 47.16 | 172.01 | 52.77 | 0.00 | 0.00 | 0.00 |
August | 110.34 | 69.86 | 40.49 | 136.46 | 57.63 | 0.00 | 0.00 | 0.00 |
September | 78.58 | 43.78 | 34.80 | 90.19 | 66.49 | 5.83 | 0.00 | 0.00 |
October | 47.22 | 22.59 | 24.63 | 51.98 | 56.01 | 13.83 | 0.00 | 0.00 |
November | 23.33 | 6.33 | 17.00 | 21.39 | 47.92 | 48.33 | 0.00 | 0.00 |
December | 17.12 | 4.83 | 12.29 | 13.13 | 60.99 | 62.33 | 0.00 | 0.00 |
Annual Sum or Average | 72.80 | 38.84 | 33.96 | 86.33 | 54.35 | 212.17 | 0.00 | 0.00 |
Minimum of Months | 17.12 | 4.49 | 12.29 | 13.13 | 44.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.77 | 89.61 | 58.78 | 172.01 | 66.49 | 62.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.57 | 4.49 | 15.08 | 14.80 | 61.34 | 33.83 | 0.00 | 0.00 |
February | 34.87 | 12.49 | 22.39 | 36.29 | 56.31 | 34.33 | 0.00 | 0.00 |
March | 59.12 | 25.62 | 33.51 | 67.91 | 49.53 | 8.83 | 0.00 | 0.00 |
April | 93.00 | 47.13 | 45.87 | 116.65 | 44.88 | 4.83 | 0.00 | 0.00 |
May | 120.05 | 61.27 | 58.78 | 149.34 | 50.69 | 0.00 | 0.00 | 0.00 |
June | 131.08 | 76.11 | 54.97 | 162.43 | 47.47 | 0.00 | 0.00 | 0.00 |
July | 136.77 | 89.61 | 47.16 | 172.01 | 52.77 | 0.00 | 0.00 | 0.00 |
August | 110.34 | 69.86 | 40.49 | 136.46 | 57.63 | 0.00 | 0.00 | 0.00 |
September | 78.58 | 43.78 | 34.80 | 90.19 | 66.49 | 5.83 | 0.00 | 0.00 |
October | 47.22 | 22.59 | 24.63 | 51.98 | 56.01 | 13.83 | 0.00 | 0.00 |
November | 23.33 | 6.33 | 17.00 | 21.39 | 47.92 | 48.33 | 0.00 | 0.00 |
December | 17.12 | 4.83 | 12.29 | 13.13 | 60.99 | 62.33 | 0.00 | 0.00 |
Annual Sum or Average | 72.80 | 38.84 | 33.96 | 86.33 | 54.35 | 212.17 | 0.00 | 0.00 |
Minimum of Months | 17.12 | 4.49 | 12.29 | 13.13 | 44.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.77 | 89.61 | 58.78 | 172.01 | 66.49 | 62.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.57 | 4.49 | 15.08 | 14.80 | 61.34 | 33.83 | 0.00 | 0.00 |
February | 34.87 | 12.49 | 22.39 | 36.29 | 56.31 | 34.33 | 0.00 | 0.00 |
March | 59.12 | 25.62 | 33.51 | 67.91 | 49.53 | 8.83 | 0.00 | 0.00 |
April | 93.00 | 47.13 | 45.87 | 116.65 | 44.88 | 4.83 | 0.00 | 0.00 |
May | 120.05 | 61.27 | 58.78 | 149.34 | 50.69 | 0.00 | 0.00 | 0.00 |
June | 131.08 | 76.11 | 54.97 | 162.43 | 47.47 | 0.00 | 0.00 | 0.00 |
July | 136.77 | 89.61 | 47.16 | 172.01 | 52.77 | 0.00 | 0.00 | 0.00 |
August | 110.34 | 69.86 | 40.49 | 136.46 | 57.63 | 0.00 | 0.00 | 0.00 |
September | 78.58 | 43.78 | 34.80 | 90.19 | 66.49 | 5.83 | 0.00 | 0.00 |
October | 47.22 | 22.59 | 24.63 | 51.98 | 56.01 | 13.83 | 0.00 | 0.00 |
November | 23.33 | 6.33 | 17.00 | 21.39 | 47.92 | 48.33 | 0.00 | 0.00 |
December | 17.12 | 4.83 | 12.29 | 13.13 | 60.99 | 62.33 | 0.00 | 0.00 |
Annual Sum or Average | 72.80 | 38.84 | 33.96 | 86.33 | 54.35 | 212.17 | 0.00 | 0.00 |
Minimum of Months | 17.12 | 4.49 | 12.29 | 13.13 | 44.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.77 | 89.61 | 58.78 | 172.01 | 66.49 | 62.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.57 | 4.49 | 15.08 | 14.80 | 61.34 | 33.83 | 0.00 | 0.00 |
February | 34.87 | 12.49 | 22.39 | 36.29 | 56.31 | 34.33 | 0.00 | 0.00 |
March | 59.12 | 25.62 | 33.51 | 67.91 | 49.53 | 8.83 | 0.00 | 0.00 |
April | 93.00 | 47.13 | 45.87 | 116.65 | 44.88 | 4.83 | 0.00 | 0.00 |
May | 120.05 | 61.27 | 58.78 | 149.34 | 50.69 | 0.00 | 0.00 | 0.00 |
June | 131.08 | 76.11 | 54.97 | 162.43 | 47.47 | 0.00 | 0.00 | 0.00 |
July | 136.77 | 89.61 | 47.16 | 172.01 | 52.77 | 0.00 | 0.00 | 0.00 |
August | 110.34 | 69.86 | 40.49 | 136.46 | 57.63 | 0.00 | 0.00 | 0.00 |
September | 78.58 | 43.78 | 34.80 | 90.19 | 66.49 | 5.83 | 0.00 | 0.00 |
October | 47.22 | 22.59 | 24.63 | 51.98 | 56.01 | 13.83 | 0.00 | 0.00 |
November | 23.33 | 6.33 | 17.00 | 21.39 | 47.92 | 48.33 | 0.00 | 0.00 |
December | 17.12 | 4.83 | 12.29 | 13.13 | 60.99 | 62.33 | 0.00 | 0.00 |
Annual Sum or Average | 72.80 | 38.84 | 33.96 | 86.33 | 54.35 | 212.17 | 0.00 | 0.00 |
Minimum of Months | 17.12 | 4.49 | 12.29 | 13.13 | 44.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.77 | 89.61 | 58.78 | 172.01 | 66.49 | 62.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.57 | 4.49 | 15.08 | 14.80 | 61.34 | 33.83 | 0.00 | 0.00 |
February | 34.87 | 12.49 | 22.39 | 36.29 | 56.31 | 34.33 | 0.00 | 0.00 |
March | 59.12 | 25.62 | 33.51 | 67.91 | 49.53 | 8.83 | 0.00 | 0.00 |
April | 93.00 | 47.13 | 45.87 | 116.65 | 44.88 | 4.83 | 0.00 | 0.00 |
May | 120.05 | 61.27 | 58.78 | 149.34 | 50.69 | 0.00 | 0.00 | 0.00 |
June | 131.08 | 76.11 | 54.97 | 162.43 | 47.47 | 0.00 | 0.00 | 0.00 |
July | 136.77 | 89.61 | 47.16 | 172.01 | 52.77 | 0.00 | 0.00 | 0.00 |
August | 110.34 | 69.86 | 40.49 | 136.46 | 57.63 | 0.00 | 0.00 | 0.00 |
September | 78.58 | 43.78 | 34.80 | 90.19 | 66.49 | 5.83 | 0.00 | 0.00 |
October | 47.22 | 22.59 | 24.63 | 51.98 | 56.01 | 13.83 | 0.00 | 0.00 |
November | 23.33 | 6.33 | 17.00 | 21.39 | 47.92 | 48.33 | 0.00 | 0.00 |
December | 17.12 | 4.83 | 12.29 | 13.13 | 60.99 | 62.33 | 0.00 | 0.00 |
Annual Sum or Average | 72.80 | 38.84 | 33.96 | 86.33 | 54.35 | 212.17 | 0.00 | 0.00 |
Minimum of Months | 17.12 | 4.49 | 12.29 | 13.13 | 44.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.77 | 89.61 | 58.78 | 172.01 | 66.49 | 62.33 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108122E+09 | 32103306.91 | 76018307.89 | 46608829.04 | 0.345427E+09 |
February | 0.173500E+09 | 64623203.54 | 0.108876E+09 | 0.125849E+09 | 0.266812E+09 |
March | 0.270578E+09 | 91417062.02 | 0.179161E+09 | 0.234319E+09 | 0.237876E+09 |
April | 0.397495E+09 | 0.151668E+09 | 0.245827E+09 | 0.407298E+09 | 0.193013E+09 |
May | 0.529808E+09 | 0.215475E+09 | 0.314334E+09 | 0.572362E+09 | 0.192055E+09 |
June | 0.492944E+09 | 0.191424E+09 | 0.301520E+09 | 0.533250E+09 | 0.159002E+09 |
July | 0.630362E+09 | 0.331837E+09 | 0.298526E+09 | 0.750381E+09 | 0.157686E+09 |
August | 0.520365E+09 | 0.265426E+09 | 0.254938E+09 | 0.627219E+09 | 0.156407E+09 |
September | 0.411615E+09 | 0.198025E+09 | 0.213591E+09 | 0.452786E+09 | 0.206404E+09 |
October | 0.242222E+09 | 99092833.58 | 0.143129E+09 | 0.220744E+09 | 0.234522E+09 |
November | 0.116637E+09 | 33225367.21 | 83411214.22 | 67395110.42 | 0.261676E+09 |
December | 0.102253E+09 | 35867605.16 | 66385120.44 | 57917601.27 | 0.347704E+09 |
Annual Sum or Average | 0.399590E+10 | 0.171018E+10 | 0.228572E+10 | 0.409613E+10 | 0.275858E+10 |
Minimum of Months | 0.102253E+09 | 32103306.91 | 66385120.44 | 46608829.04 | 0.156407E+09 |
Maximum of Months | 0.630362E+09 | 0.331837E+09 | 0.314334E+09 | 0.750381E+09 | 0.347704E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108122E+09 | 32103306.91 | 76018307.89 | 46608829.04 | 0.345427E+09 |
February | 0.173500E+09 | 64623203.54 | 0.108876E+09 | 0.125849E+09 | 0.266812E+09 |
March | 0.270578E+09 | 91417062.02 | 0.179161E+09 | 0.234319E+09 | 0.237876E+09 |
April | 0.397495E+09 | 0.151668E+09 | 0.245827E+09 | 0.407298E+09 | 0.193013E+09 |
May | 0.529808E+09 | 0.215475E+09 | 0.314334E+09 | 0.572362E+09 | 0.192055E+09 |
June | 0.492944E+09 | 0.191424E+09 | 0.301520E+09 | 0.533250E+09 | 0.159002E+09 |
July | 0.630362E+09 | 0.331837E+09 | 0.298526E+09 | 0.750381E+09 | 0.157686E+09 |
August | 0.520365E+09 | 0.265426E+09 | 0.254938E+09 | 0.627219E+09 | 0.156407E+09 |
September | 0.411615E+09 | 0.198025E+09 | 0.213591E+09 | 0.452786E+09 | 0.206404E+09 |
October | 0.242222E+09 | 99092833.58 | 0.143129E+09 | 0.220744E+09 | 0.234522E+09 |
November | 0.116637E+09 | 33225367.21 | 83411214.22 | 67395110.42 | 0.261676E+09 |
December | 0.102253E+09 | 35867605.16 | 66385120.44 | 57917601.27 | 0.347704E+09 |
Annual Sum or Average | 0.399590E+10 | 0.171018E+10 | 0.228572E+10 | 0.409613E+10 | 0.275858E+10 |
Minimum of Months | 0.102253E+09 | 32103306.91 | 66385120.44 | 46608829.04 | 0.156407E+09 |
Maximum of Months | 0.630362E+09 | 0.331837E+09 | 0.314334E+09 | 0.750381E+09 | 0.347704E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37047291.95 | 0.00 | 37047291.95 | 1775957.17 | 0.212764E+09 |
February | 52067903.54 | 0.00 | 52067903.54 | 11732076.54 | 0.165360E+09 |
March | 84945400.62 | 1694.17 | 84943706.44 | 38814713.00 | 0.143944E+09 |
April | 0.116505E+09 | 564349.27 | 0.115940E+09 | 78858667.99 | 0.112171E+09 |
May | 0.154582E+09 | 4519910.97 | 0.150062E+09 | 0.119180E+09 | 0.108332E+09 |
June | 0.157369E+09 | 10354948.37 | 0.147015E+09 | 0.128900E+09 | 87385988.90 |
July | 0.154687E+09 | 12174915.22 | 0.142512E+09 | 0.139942E+09 | 86420595.33 |
August | 0.125656E+09 | 3832074.87 | 0.121824E+09 | 0.115631E+09 | 86338617.13 |
September | 94098771.83 | 60912.38 | 94037859.45 | 60801676.00 | 0.123004E+09 |
October | 66587274.63 | 0.00 | 66587274.63 | 28762410.96 | 0.140642E+09 |
November | 40590374.91 | 0.00 | 40590374.91 | 6544011.74 | 0.158951E+09 |
December | 31480644.54 | 0.00 | 31480644.54 | 1110588.59 | 0.210795E+09 |
Annual Sum or Average | 0.111562E+10 | 31508805.24 | 0.108411E+10 | 0.732053E+09 | 0.163611E+10 |
Minimum of Months | 31480644.54 | 0.00 | 31480644.54 | 1110588.59 | 86338617.13 |
Maximum of Months | 0.157369E+09 | 12174915.22 | 0.150062E+09 | 0.139942E+09 | 0.212764E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37045994.81 | 0.00 | 37045994.81 | 1775665.00 | 0.212764E+09 |
February | 52066167.00 | 0.00 | 52066167.00 | 11730994.78 | 0.165360E+09 |
March | 84942643.14 | 1694.10 | 84940949.04 | 38812174.89 | 0.143944E+09 |
April | 0.116501E+09 | 564322.82 | 0.115937E+09 | 78854853.95 | 0.112170E+09 |
May | 0.154578E+09 | 4519699.11 | 0.150058E+09 | 0.119174E+09 | 0.108332E+09 |
June | 0.157365E+09 | 10354463.02 | 0.147010E+09 | 0.128894E+09 | 87385764.53 |
July | 0.154683E+09 | 12174344.56 | 0.142508E+09 | 0.139936E+09 | 86420305.51 |
August | 0.125652E+09 | 3831895.25 | 0.121820E+09 | 0.115627E+09 | 86338208.88 |
September | 94095927.95 | 60909.52 | 94035018.43 | 60798774.67 | 0.123003E+09 |
October | 66585148.86 | 0.00 | 66585148.86 | 28760511.99 | 0.140642E+09 |
November | 40588964.18 | 0.00 | 40588964.18 | 6543266.28 | 0.158951E+09 |
December | 31479558.13 | 0.00 | 31479558.13 | 1110422.49 | 0.210795E+09 |
Annual Sum or Average | 0.111558E+10 | 31507328.38 | 0.108408E+10 | 0.732018E+09 | 0.163611E+10 |
Minimum of Months | 31479558.13 | 0.00 | 31479558.13 | 1110422.49 | 86338208.88 |
Maximum of Months | 0.157365E+09 | 12174344.56 | 0.150058E+09 | 0.139936E+09 | 0.212764E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52410320.57 | 12019636.69 | 40390683.88 | 39634284.94 | 0.164288E+09 |
February | 84365383.18 | 30204567.19 | 54160816.00 | 87787773.54 | 0.136229E+09 |
March | 0.158359E+09 | 68611028.04 | 89747722.37 | 0.181895E+09 | 0.132669E+09 |
April | 0.241055E+09 | 0.122160E+09 | 0.118895E+09 | 0.302359E+09 | 0.116322E+09 |
May | 0.321548E+09 | 0.164106E+09 | 0.157442E+09 | 0.399996E+09 | 0.135759E+09 |
June | 0.339770E+09 | 0.197284E+09 | 0.142487E+09 | 0.421015E+09 | 0.123036E+09 |
July | 0.366324E+09 | 0.240011E+09 | 0.126313E+09 | 0.460716E+09 | 0.141335E+09 |
August | 0.295547E+09 | 0.187103E+09 | 0.108443E+09 | 0.365497E+09 | 0.154365E+09 |
September | 0.203675E+09 | 0.113485E+09 | 90190440.29 | 0.233785E+09 | 0.172340E+09 |
October | 0.126475E+09 | 60509219.73 | 65965345.66 | 0.139221E+09 | 0.150020E+09 |
November | 60469444.28 | 16401230.55 | 44068213.74 | 55437377.39 | 0.124206E+09 |
December | 45848729.04 | 12938468.12 | 32910260.92 | 35175787.51 | 0.163343E+09 |
Annual Sum or Average | 0.229585E+10 | 0.122483E+10 | 0.107101E+10 | 0.272252E+10 | 0.171391E+10 |
Minimum of Months | 45848729.04 | 12019636.69 | 32910260.92 | 35175787.51 | 0.116322E+09 |
Maximum of Months | 0.366324E+09 | 0.240011E+09 | 0.157442E+09 | 0.460716E+09 | 0.172340E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52410320.57 | 12019636.69 | 40390683.88 | 39634284.94 | 0.164288E+09 |
February | 84365383.18 | 30204567.19 | 54160816.00 | 87787773.54 | 0.136229E+09 |
March | 0.158359E+09 | 68611028.04 | 89747722.37 | 0.181895E+09 | 0.132669E+09 |
April | 0.241055E+09 | 0.122160E+09 | 0.118895E+09 | 0.302359E+09 | 0.116322E+09 |
May | 0.321548E+09 | 0.164106E+09 | 0.157442E+09 | 0.399996E+09 | 0.135759E+09 |
June | 0.339770E+09 | 0.197284E+09 | 0.142487E+09 | 0.421015E+09 | 0.123036E+09 |
July | 0.366324E+09 | 0.240011E+09 | 0.126313E+09 | 0.460716E+09 | 0.141335E+09 |
August | 0.295547E+09 | 0.187103E+09 | 0.108443E+09 | 0.365497E+09 | 0.154365E+09 |
September | 0.203675E+09 | 0.113485E+09 | 90190440.29 | 0.233785E+09 | 0.172340E+09 |
October | 0.126475E+09 | 60509219.73 | 65965345.66 | 0.139221E+09 | 0.150020E+09 |
November | 60469444.28 | 16401230.55 | 44068213.74 | 55437377.39 | 0.124206E+09 |
December | 45848729.04 | 12938468.12 | 32910260.92 | 35175787.51 | 0.163343E+09 |
Annual Sum or Average | 0.229585E+10 | 0.122483E+10 | 0.107101E+10 | 0.272252E+10 | 0.171391E+10 |
Minimum of Months | 45848729.04 | 12019636.69 | 32910260.92 | 35175787.51 | 0.116322E+09 |
Maximum of Months | 0.366324E+09 | 0.240011E+09 | 0.157442E+09 | 0.460716E+09 | 0.172340E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52410320.57 | 12019636.69 | 40390683.88 | 39634284.94 | 0.164288E+09 |
February | 84365383.18 | 30204567.19 | 54160816.00 | 87787773.54 | 0.136229E+09 |
March | 0.158359E+09 | 68611028.04 | 89747722.37 | 0.181895E+09 | 0.132669E+09 |
April | 0.241055E+09 | 0.122160E+09 | 0.118895E+09 | 0.302359E+09 | 0.116322E+09 |
May | 0.321548E+09 | 0.164106E+09 | 0.157442E+09 | 0.399996E+09 | 0.135759E+09 |
June | 0.339770E+09 | 0.197284E+09 | 0.142487E+09 | 0.421015E+09 | 0.123036E+09 |
July | 0.366324E+09 | 0.240011E+09 | 0.126313E+09 | 0.460716E+09 | 0.141335E+09 |
August | 0.295547E+09 | 0.187103E+09 | 0.108443E+09 | 0.365497E+09 | 0.154365E+09 |
September | 0.203675E+09 | 0.113485E+09 | 90190440.29 | 0.233785E+09 | 0.172340E+09 |
October | 0.126475E+09 | 60509219.73 | 65965345.66 | 0.139221E+09 | 0.150020E+09 |
November | 60469444.28 | 16401230.55 | 44068213.74 | 55437377.39 | 0.124206E+09 |
December | 45848729.04 | 12938468.12 | 32910260.92 | 35175787.51 | 0.163343E+09 |
Annual Sum or Average | 0.229585E+10 | 0.122483E+10 | 0.107101E+10 | 0.272252E+10 | 0.171391E+10 |
Minimum of Months | 45848729.04 | 12019636.69 | 32910260.92 | 35175787.51 | 0.116322E+09 |
Maximum of Months | 0.366324E+09 | 0.240011E+09 | 0.157442E+09 | 0.460716E+09 | 0.172340E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52410320.57 | 12019636.69 | 40390683.88 | 39634284.94 | 0.164288E+09 |
February | 84365383.18 | 30204567.19 | 54160816.00 | 87787773.54 | 0.136229E+09 |
March | 0.158359E+09 | 68611028.04 | 89747722.37 | 0.181895E+09 | 0.132669E+09 |
April | 0.241055E+09 | 0.122160E+09 | 0.118895E+09 | 0.302359E+09 | 0.116322E+09 |
May | 0.321548E+09 | 0.164106E+09 | 0.157442E+09 | 0.399996E+09 | 0.135759E+09 |
June | 0.339770E+09 | 0.197284E+09 | 0.142487E+09 | 0.421015E+09 | 0.123036E+09 |
July | 0.366324E+09 | 0.240011E+09 | 0.126313E+09 | 0.460716E+09 | 0.141335E+09 |
August | 0.295547E+09 | 0.187103E+09 | 0.108443E+09 | 0.365497E+09 | 0.154365E+09 |
September | 0.203675E+09 | 0.113485E+09 | 90190440.29 | 0.233785E+09 | 0.172340E+09 |
October | 0.126475E+09 | 60509219.73 | 65965345.66 | 0.139221E+09 | 0.150020E+09 |
November | 60469444.28 | 16401230.55 | 44068213.74 | 55437377.39 | 0.124206E+09 |
December | 45848729.04 | 12938468.12 | 32910260.92 | 35175787.51 | 0.163343E+09 |
Annual Sum or Average | 0.229585E+10 | 0.122483E+10 | 0.107101E+10 | 0.272252E+10 | 0.171391E+10 |
Minimum of Months | 45848729.04 | 12019636.69 | 32910260.92 | 35175787.51 | 0.116322E+09 |
Maximum of Months | 0.366324E+09 | 0.240011E+09 | 0.157442E+09 | 0.460716E+09 | 0.172340E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52410320.57 | 12019636.69 | 40390683.88 | 39634284.94 | 0.164288E+09 |
February | 84365383.18 | 30204567.19 | 54160816.00 | 87787773.54 | 0.136229E+09 |
March | 0.158359E+09 | 68611028.04 | 89747722.37 | 0.181895E+09 | 0.132669E+09 |
April | 0.241055E+09 | 0.122160E+09 | 0.118895E+09 | 0.302359E+09 | 0.116322E+09 |
May | 0.321548E+09 | 0.164106E+09 | 0.157442E+09 | 0.399996E+09 | 0.135759E+09 |
June | 0.339770E+09 | 0.197284E+09 | 0.142487E+09 | 0.421015E+09 | 0.123036E+09 |
July | 0.366324E+09 | 0.240011E+09 | 0.126313E+09 | 0.460716E+09 | 0.141335E+09 |
August | 0.295547E+09 | 0.187103E+09 | 0.108443E+09 | 0.365497E+09 | 0.154365E+09 |
September | 0.203675E+09 | 0.113485E+09 | 90190440.29 | 0.233785E+09 | 0.172340E+09 |
October | 0.126475E+09 | 60509219.73 | 65965345.66 | 0.139221E+09 | 0.150020E+09 |
November | 60469444.28 | 16401230.55 | 44068213.74 | 55437377.39 | 0.124206E+09 |
December | 45848729.04 | 12938468.12 | 32910260.92 | 35175787.51 | 0.163343E+09 |
Annual Sum or Average | 0.229585E+10 | 0.122483E+10 | 0.107101E+10 | 0.272252E+10 | 0.171391E+10 |
Minimum of Months | 45848729.04 | 12019636.69 | 32910260.92 | 35175787.51 | 0.116322E+09 |
Maximum of Months | 0.366324E+09 | 0.240011E+09 | 0.157442E+09 | 0.460716E+09 | 0.172340E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52410320.57 | 12019636.69 | 40390683.88 | 39634284.94 | 0.164288E+09 |
February | 84365383.18 | 30204567.19 | 54160816.00 | 87787773.54 | 0.136229E+09 |
March | 0.158359E+09 | 68611028.04 | 89747722.37 | 0.181895E+09 | 0.132669E+09 |
April | 0.241055E+09 | 0.122160E+09 | 0.118895E+09 | 0.302359E+09 | 0.116322E+09 |
May | 0.321548E+09 | 0.164106E+09 | 0.157442E+09 | 0.399996E+09 | 0.135759E+09 |
June | 0.339770E+09 | 0.197284E+09 | 0.142487E+09 | 0.421015E+09 | 0.123036E+09 |
July | 0.366324E+09 | 0.240011E+09 | 0.126313E+09 | 0.460716E+09 | 0.141335E+09 |
August | 0.295547E+09 | 0.187103E+09 | 0.108443E+09 | 0.365497E+09 | 0.154365E+09 |
September | 0.203675E+09 | 0.113485E+09 | 90190440.29 | 0.233785E+09 | 0.172340E+09 |
October | 0.126475E+09 | 60509219.73 | 65965345.66 | 0.139221E+09 | 0.150020E+09 |
November | 60469444.28 | 16401230.55 | 44068213.74 | 55437377.39 | 0.124206E+09 |
December | 45848729.04 | 12938468.12 | 32910260.92 | 35175787.51 | 0.163343E+09 |
Annual Sum or Average | 0.229585E+10 | 0.122483E+10 | 0.107101E+10 | 0.272252E+10 | 0.171391E+10 |
Minimum of Months | 45848729.04 | 12019636.69 | 32910260.92 | 35175787.51 | 0.116322E+09 |
Maximum of Months | 0.366324E+09 | 0.240011E+09 | 0.157442E+09 | 0.460716E+09 | 0.172340E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52410320.57 | 12019636.69 | 40390683.88 | 39634284.94 | 0.164288E+09 |
February | 84365383.18 | 30204567.19 | 54160816.00 | 87787773.54 | 0.136229E+09 |
March | 0.158359E+09 | 68611028.04 | 89747722.37 | 0.181895E+09 | 0.132669E+09 |
April | 0.241055E+09 | 0.122160E+09 | 0.118895E+09 | 0.302359E+09 | 0.116322E+09 |
May | 0.321548E+09 | 0.164106E+09 | 0.157442E+09 | 0.399996E+09 | 0.135759E+09 |
June | 0.339770E+09 | 0.197284E+09 | 0.142487E+09 | 0.421015E+09 | 0.123036E+09 |
July | 0.366324E+09 | 0.240011E+09 | 0.126313E+09 | 0.460716E+09 | 0.141335E+09 |
August | 0.295547E+09 | 0.187103E+09 | 0.108443E+09 | 0.365497E+09 | 0.154365E+09 |
September | 0.203675E+09 | 0.113485E+09 | 90190440.29 | 0.233785E+09 | 0.172340E+09 |
October | 0.126475E+09 | 60509219.73 | 65965345.66 | 0.139221E+09 | 0.150020E+09 |
November | 60469444.28 | 16401230.55 | 44068213.74 | 55437377.39 | 0.124206E+09 |
December | 45848729.04 | 12938468.12 | 32910260.92 | 35175787.51 | 0.163343E+09 |
Annual Sum or Average | 0.229585E+10 | 0.122483E+10 | 0.107101E+10 | 0.272252E+10 | 0.171391E+10 |
Minimum of Months | 45848729.04 | 12019636.69 | 32910260.92 | 35175787.51 | 0.116322E+09 |
Maximum of Months | 0.366324E+09 | 0.240011E+09 | 0.157442E+09 | 0.460716E+09 | 0.172340E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52410320.57 | 12019636.69 | 40390683.88 | 39634284.94 | 0.164288E+09 |
February | 84365383.18 | 30204567.19 | 54160816.00 | 87787773.54 | 0.136229E+09 |
March | 0.158359E+09 | 68611028.04 | 89747722.37 | 0.181895E+09 | 0.132669E+09 |
April | 0.241055E+09 | 0.122160E+09 | 0.118895E+09 | 0.302359E+09 | 0.116322E+09 |
May | 0.321548E+09 | 0.164106E+09 | 0.157442E+09 | 0.399996E+09 | 0.135759E+09 |
June | 0.339770E+09 | 0.197284E+09 | 0.142487E+09 | 0.421015E+09 | 0.123036E+09 |
July | 0.366324E+09 | 0.240011E+09 | 0.126313E+09 | 0.460716E+09 | 0.141335E+09 |
August | 0.295547E+09 | 0.187103E+09 | 0.108443E+09 | 0.365497E+09 | 0.154365E+09 |
September | 0.203675E+09 | 0.113485E+09 | 90190440.29 | 0.233785E+09 | 0.172340E+09 |
October | 0.126475E+09 | 60509219.73 | 65965345.66 | 0.139221E+09 | 0.150020E+09 |
November | 60469444.28 | 16401230.55 | 44068213.74 | 55437377.39 | 0.124206E+09 |
December | 45848729.04 | 12938468.12 | 32910260.92 | 35175787.51 | 0.163343E+09 |
Annual Sum or Average | 0.229585E+10 | 0.122483E+10 | 0.107101E+10 | 0.272252E+10 | 0.171391E+10 |
Minimum of Months | 45848729.04 | 12019636.69 | 32910260.92 | 35175787.51 | 0.116322E+09 |
Maximum of Months | 0.366324E+09 | 0.240011E+09 | 0.157442E+09 | 0.460716E+09 | 0.172340E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52410320.57 | 12019636.69 | 40390683.88 | 39634284.94 | 0.164288E+09 |
February | 84365383.18 | 30204567.19 | 54160816.00 | 87787773.54 | 0.136229E+09 |
March | 0.158359E+09 | 68611028.04 | 89747722.37 | 0.181895E+09 | 0.132669E+09 |
April | 0.241055E+09 | 0.122160E+09 | 0.118895E+09 | 0.302359E+09 | 0.116322E+09 |
May | 0.321548E+09 | 0.164106E+09 | 0.157442E+09 | 0.399996E+09 | 0.135759E+09 |
June | 0.339770E+09 | 0.197284E+09 | 0.142487E+09 | 0.421015E+09 | 0.123036E+09 |
July | 0.366324E+09 | 0.240011E+09 | 0.126313E+09 | 0.460716E+09 | 0.141335E+09 |
August | 0.295547E+09 | 0.187103E+09 | 0.108443E+09 | 0.365497E+09 | 0.154365E+09 |
September | 0.203675E+09 | 0.113485E+09 | 90190440.29 | 0.233785E+09 | 0.172340E+09 |
October | 0.126475E+09 | 60509219.73 | 65965345.66 | 0.139221E+09 | 0.150020E+09 |
November | 60469444.28 | 16401230.55 | 44068213.74 | 55437377.39 | 0.124206E+09 |
December | 45848729.04 | 12938468.12 | 32910260.92 | 35175787.51 | 0.163343E+09 |
Annual Sum or Average | 0.229585E+10 | 0.122483E+10 | 0.107101E+10 | 0.272252E+10 | 0.171391E+10 |
Minimum of Months | 45848729.04 | 12019636.69 | 32910260.92 | 35175787.51 | 0.116322E+09 |
Maximum of Months | 0.366324E+09 | 0.240011E+09 | 0.157442E+09 | 0.460716E+09 | 0.172340E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52410320.57 | 12019636.69 | 40390683.88 | 39634284.94 | 0.164288E+09 |
February | 84365383.18 | 30204567.19 | 54160816.00 | 87787773.54 | 0.136229E+09 |
March | 0.158359E+09 | 68611028.04 | 89747722.37 | 0.181895E+09 | 0.132669E+09 |
April | 0.241055E+09 | 0.122160E+09 | 0.118895E+09 | 0.302359E+09 | 0.116322E+09 |
May | 0.321548E+09 | 0.164106E+09 | 0.157442E+09 | 0.399996E+09 | 0.135759E+09 |
June | 0.339770E+09 | 0.197284E+09 | 0.142487E+09 | 0.421015E+09 | 0.123036E+09 |
July | 0.366324E+09 | 0.240011E+09 | 0.126313E+09 | 0.460716E+09 | 0.141335E+09 |
August | 0.295547E+09 | 0.187103E+09 | 0.108443E+09 | 0.365497E+09 | 0.154365E+09 |
September | 0.203675E+09 | 0.113485E+09 | 90190440.29 | 0.233785E+09 | 0.172340E+09 |
October | 0.126475E+09 | 60509219.73 | 65965345.66 | 0.139221E+09 | 0.150020E+09 |
November | 60469444.28 | 16401230.55 | 44068213.74 | 55437377.39 | 0.124206E+09 |
December | 45848729.04 | 12938468.12 | 32910260.92 | 35175787.51 | 0.163343E+09 |
Annual Sum or Average | 0.229585E+10 | 0.122483E+10 | 0.107101E+10 | 0.272252E+10 | 0.171391E+10 |
Minimum of Months | 45848729.04 | 12019636.69 | 32910260.92 | 35175787.51 | 0.116322E+09 |
Maximum of Months | 0.366324E+09 | 0.240011E+09 | 0.157442E+09 | 0.460716E+09 | 0.172340E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 30.36 | 411.04 | 108.40 | 23.97 | 84.43 | 0.00 | 0.00 |
February | 108.68 | 352.23 | 186.48 | 53.43 | 133.06 | 0.00 | 0.00 |
March | 200.89 | 282.05 | 265.47 | 68.26 | 197.21 | 0.00 | 0.00 |
April | 373.77 | 234.13 | 396.60 | 117.46 | 279.14 | 0.00 | 0.00 |
May | 514.76 | 222.68 | 511.04 | 164.27 | 346.77 | 0.00 | 0.00 |
June | 507.66 | 186.86 | 501.78 | 155.69 | 346.09 | 0.00 | 0.00 |
July | 661.85 | 179.31 | 586.21 | 256.88 | 329.33 | 0.00 | 0.00 |
August | 553.59 | 180.16 | 482.39 | 201.06 | 281.33 | 0.00 | 0.00 |
September | 394.33 | 252.22 | 390.21 | 152.84 | 237.37 | 0.00 | 0.00 |
October | 183.40 | 277.23 | 230.59 | 73.99 | 156.60 | 0.00 | 0.00 |
November | 53.61 | 321.12 | 121.32 | 25.64 | 95.68 | 0.00 | 0.00 |
December | 38.90 | 411.87 | 99.86 | 26.78 | 73.08 | 0.00 | 0.00 |
Annual Sum or Average | 303.07 | 275.58 | 324.17 | 110.46 | 213.71 | 0.00 | 0.00 |
Minimum of Months | 30.36 | 179.31 | 99.86 | 23.97 | 73.08 | 0.00 | 0.00 |
Maximum of Months | 661.85 | 411.87 | 586.21 | 256.88 | 346.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 508.00 | 3998.45 | 195.68 | 44.88 | 150.80 | 0.00 | 0.00 |
February | 1268.76 | 3618.15 | 348.73 | 124.85 | 223.88 | 0.00 | 0.00 |
March | 2176.85 | 2320.31 | 591.24 | 256.16 | 335.08 | 0.00 | 0.00 |
April | 3931.79 | 1715.76 | 930.00 | 471.30 | 458.70 | 0.00 | 0.00 |
May | 4958.18 | 1632.58 | 1200.52 | 612.70 | 587.82 | 0.00 | 0.00 |
June | 5424.33 | 1582.50 | 1310.84 | 761.12 | 549.72 | 0.00 | 0.00 |
July | 6187.04 | 2098.54 | 1367.70 | 896.10 | 471.60 | 0.00 | 0.00 |
August | 4729.47 | 2543.56 | 1103.44 | 698.56 | 404.88 | 0.00 | 0.00 |
September | 2809.86 | 2438.76 | 785.78 | 437.83 | 347.96 | 0.00 | 0.00 |
October | 1704.89 | 1993.07 | 472.20 | 225.92 | 246.29 | 0.00 | 0.00 |
November | 699.59 | 2427.00 | 233.29 | 63.28 | 170.02 | 0.00 | 0.00 |
December | 426.25 | 3611.57 | 171.18 | 48.31 | 122.87 | 0.00 | 0.00 |
Annual Sum or Average | 2912.06 | 2494.16 | 728.01 | 388.39 | 339.62 | 0.00 | 0.00 |
Minimum of Months | 426.25 | 1582.50 | 171.18 | 44.88 | 122.87 | 0.00 | 0.00 |
Maximum of Months | 6187.04 | 3998.45 | 1367.70 | 896.10 | 587.82 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 81305373.49 | 0.110092E+10 | 0.290337E+09 | 64206613.83 | 0.226130E+09 | 0.00 | 0.00 |
February | 0.262919E+09 | 0.852104E+09 | 0.451133E+09 | 0.129246E+09 | 0.321887E+09 | 0.00 | 0.00 |
March | 0.538076E+09 | 0.755452E+09 | 0.711045E+09 | 0.182838E+09 | 0.528207E+09 | 0.00 | 0.00 |
April | 0.968809E+09 | 0.606866E+09 | 0.102799E+10 | 0.304464E+09 | 0.723531E+09 | 0.00 | 0.00 |
May | 0.137873E+10 | 0.596423E+09 | 0.136878E+10 | 0.439989E+09 | 0.928788E+09 | 0.00 | 0.00 |
June | 0.131585E+10 | 0.484333E+09 | 0.130062E+10 | 0.403557E+09 | 0.897065E+09 | 0.00 | 0.00 |
July | 0.177270E+10 | 0.480275E+09 | 0.157009E+10 | 0.688022E+09 | 0.882072E+09 | 0.00 | 0.00 |
August | 0.148275E+10 | 0.482540E+09 | 0.129204E+10 | 0.538517E+09 | 0.753520E+09 | 0.00 | 0.00 |
September | 0.102211E+10 | 0.653754E+09 | 0.101143E+10 | 0.396171E+09 | 0.615254E+09 | 0.00 | 0.00 |
October | 0.491208E+09 | 0.742526E+09 | 0.617616E+09 | 0.198186E+09 | 0.419431E+09 | 0.00 | 0.00 |
November | 0.138956E+09 | 0.832333E+09 | 0.314453E+09 | 66450734.41 | 0.248002E+09 | 0.00 | 0.00 |
December | 0.104203E+09 | 0.110314E+10 | 0.267466E+09 | 71735210.31 | 0.195730E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.955761E+10 | 0.869067E+10 | 0.102230E+11 | 0.348338E+10 | 0.673962E+10 | 0.00 | 0.00 |
Minimum of Months | 81305373.49 | 0.480275E+09 | 0.267466E+09 | 64206613.83 | 0.195730E+09 | 0.00 | 0.00 |
Maximum of Months | 0.177270E+10 | 0.110314E+10 | 0.157009E+10 | 0.688022E+09 | 0.928788E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.136063E+10 | 0.107095E+11 | 0.524103E+09 | 0.120196E+09 | 0.403907E+09 | 0.00 | 0.00 |
February | 0.306940E+10 | 0.875303E+10 | 0.843654E+09 | 0.302046E+09 | 0.541608E+09 | 0.00 | 0.00 |
March | 0.583047E+10 | 0.621471E+10 | 0.158359E+10 | 0.686110E+09 | 0.897477E+09 | 0.00 | 0.00 |
April | 0.101912E+11 | 0.444724E+10 | 0.241055E+10 | 0.122160E+10 | 0.118895E+10 | 0.00 | 0.00 |
May | 0.132800E+11 | 0.437270E+10 | 0.321548E+10 | 0.164106E+10 | 0.157442E+10 | 0.00 | 0.00 |
June | 0.140599E+11 | 0.410184E+10 | 0.339770E+10 | 0.197284E+10 | 0.142487E+10 | 0.00 | 0.00 |
July | 0.165714E+11 | 0.562074E+10 | 0.366324E+10 | 0.240011E+10 | 0.126313E+10 | 0.00 | 0.00 |
August | 0.126674E+11 | 0.681268E+10 | 0.295547E+10 | 0.187103E+10 | 0.108443E+10 | 0.00 | 0.00 |
September | 0.728317E+10 | 0.632126E+10 | 0.203675E+10 | 0.113485E+10 | 0.901904E+09 | 0.00 | 0.00 |
October | 0.456638E+10 | 0.533824E+10 | 0.126475E+10 | 0.605092E+09 | 0.659653E+09 | 0.00 | 0.00 |
November | 0.181333E+10 | 0.629078E+10 | 0.604694E+09 | 0.164012E+09 | 0.440682E+09 | 0.00 | 0.00 |
December | 0.114166E+10 | 0.967323E+10 | 0.458487E+09 | 0.129385E+09 | 0.329103E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.918349E+11 | 0.786559E+11 | 0.229585E+11 | 0.122483E+11 | 0.107101E+11 | 0.00 | 0.00 |
Minimum of Months | 0.114166E+10 | 0.410184E+10 | 0.458487E+09 | 0.120196E+09 | 0.329103E+09 | 0.00 | 0.00 |
Maximum of Months | 0.165714E+11 | 0.107095E+11 | 0.366324E+10 | 0.240011E+10 | 0.157442E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.100551E+10 | -848744283.7 | 0.00 | 0.00 | 744.00 | 0.00 | -156766169.9 | 58.99 | 0.00 | 0.00 |
February | 0.925326E+09 | -785120065.7 | 0.00 | 0.00 | 672.00 | 0.00 | -140206391.8 | 58.99 | 0.00 | 0.00 |
March | 0.105928E+10 | -907215006.7 | 0.00 | 0.00 | 744.00 | 0.00 | -152063977.4 | 58.99 | 0.00 | 0.00 |
April | 0.962062E+09 | -819652554.6 | 0.00 | 0.00 | 720.00 | 0.00 | -142409147.9 | 58.99 | 0.00 | 0.00 |
May | 0.960650E+09 | -820651173.0 | 0.00 | 0.00 | 744.00 | 0.00 | -139999096.2 | 58.99 | 0.00 | 0.00 |
June | 0.918404E+09 | -786773043.7 | 0.00 | 0.00 | 720.00 | 0.00 | -131631281.8 | 58.99 | 0.00 | 0.00 |
July | 0.872893E+09 | -739280868.9 | 0.00 | 0.00 | 744.00 | 0.00 | -133611968.4 | 58.99 | 0.00 | 0.00 |
August | 0.921007E+09 | -787243937.9 | 0.00 | 0.00 | 744.00 | 0.00 | -133763254.5 | 58.99 | 0.00 | 0.00 |
September | 0.872531E+09 | -741753587.7 | 0.00 | 0.00 | 720.00 | 0.00 | -130777692.6 | 58.99 | 0.00 | 0.00 |
October | 0.912809E+09 | -767164246.7 | 0.00 | 0.00 | 744.00 | 0.00 | -145644401.9 | 58.99 | 0.00 | 0.00 |
November | 0.914503E+09 | -766218650.2 | 0.00 | 0.00 | 720.00 | 0.00 | -148284451.0 | 58.99 | 0.00 | 0.00 |
December | 0.983481E+09 | -827210002.3 | 0.00 | 0.00 | 744.00 | 0.00 | -156271326.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.113085E+11 | -0.959703E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.171143E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.872531E+09 | -907215006.7 | 0.00 | 0.00 | 672.00 | 0.00 | -156766169.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.105928E+10 | -739280868.9 | 0.00 | 0.00 | 744.00 | 0.00 | -130777692.6 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 237.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 259.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 247.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 427.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 366.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 301.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 245.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 242.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.588499E+10 | 29383.84 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.429438E+10 | 29383.84 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.247078E+10 | 29383.84 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119955E+10 | 29383.84 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.238450E+09 | 29383.84 | 11-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26201782.14 | 14939.06 | 14-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12030429.70 | 4529.30 | 28-SEP-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.791217E+09 | 29383.84 | 11-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.274368E+10 | 29383.84 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.464361E+10 | 29383.84 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.223049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.588499E+10 | 29383.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.197604E+11 | 101827.36 | 01-JAN-22:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135749E+11 | 101827.36 | 08-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.432992E+10 | 92449.63 | 30-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.100924E+10 | 55375.09 | 11-APR-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.356385E+09 | 60407.50 | 31-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.729230E+10 | 101827.36 | 29-NOV-20:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157222E+11 | 101827.36 | 05-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.620453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.197604E+11 | 101827.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.342068E+11 | 56751.13 | 15-JAN-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.226636E+11 | 82669.43 | 19-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.181255E+10 | 25745.05 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.202301E+11 | 42946.65 | 25-DEC-01:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.789130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.342068E+11 | 82669.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 99.34 | 99.34 | 0.09 | 27-FEB-14:40 | 0.09 | 0.00 |
March | 0.00 | 0.00 | 1014.40 | 993.88 | 0.38 | 18-MAR-13:50 | 0.38 | 0.00 |
April | 0.00 | 0.00 | 0.331159E+09 | 0.317049E+09 | 19556.56 | 27-APR-18:35 | 18615.85 | 0.00 |
May | 0.00 | 0.00 | 0.745924E+09 | 0.670167E+09 | 20488.18 | 05-MAY-17:15 | 15951.39 | 0.00 |
June | 0.00 | 0.00 | 0.160786E+10 | 0.153444E+10 | 19816.02 | 22-JUN-17:43 | 18327.62 | 0.00 |
July | 0.00 | 0.00 | 0.418594E+10 | 0.362346E+10 | 20892.43 | 27-JUL-18:23 | 16155.69 | 0.00 |
August | 0.00 | 0.00 | 0.549119E+10 | 0.475879E+10 | 20663.93 | 26-AUG-17:11 | 14085.27 | 0.00 |
September | 0.00 | 0.00 | 0.164109E+10 | 0.136457E+10 | 20349.19 | 22-SEP-17:11 | 15702.11 | 0.00 |
October | 0.00 | 0.00 | 44031375.11 | 44031297.60 | 17719.68 | 04-OCT-17:25 | 17719.68 | 0.00 |
November | 0.00 | 0.00 | 15810403.04 | 12018245.31 | 2117.43 | 04-NOV-15:00 | 1636.21 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.140630E+11 | 0.123245E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.549119E+10 | 0.475879E+10 | 20892.43 | 18615.85 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.167093E+09 | 0.162457E+09 | 13192.73 | 27-APR-14:50 | 12720.79 | 0.00 |
May | 0.00 | 0.00 | 0.394551E+09 | 0.360880E+09 | 11351.55 | 06-MAY-13:30 | 9227.79 | 0.00 |
June | 0.00 | 0.00 | 0.131026E+10 | 0.127192E+10 | 65862.66 | 22-JUN-18:02 | 59702.62 | 0.00 |
July | 0.00 | 0.00 | 0.578793E+10 | 0.517196E+10 | 69519.77 | 27-JUL-18:45 | 51378.05 | 0.00 |
August | 0.00 | 0.00 | 0.859384E+10 | 0.772476E+10 | 68110.02 | 13-AUG-13:53 | 59974.36 | 0.00 |
September | 0.00 | 0.00 | 0.130300E+10 | 0.106983E+10 | 66929.64 | 14-SEP-17:11 | 57855.29 | 0.00 |
October | 0.00 | 0.00 | 175.80 | 175.80 | 0.29 | 04-OCT-12:40 | 0.29 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.175567E+11 | 0.157618E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.859384E+10 | 0.772476E+10 | 69519.77 | 59974.36 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.425886E+09 | 0.05 | 270.59 | 01-JAN-00:03 | 0.08 |
February | 0.268887E+09 | 0.03 | 270.59 | 01-FEB-00:05 | 0.08 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 47868150.25 | 0.01 | 270.59 | 16-NOV-06:30 | 0.08 |
December | 0.380564E+09 | 0.04 | 270.59 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.112320E+10 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.425886E+09 | 0.05 | 270.59 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.139678E+10 | 0.52 | 1326.69 | 09-JAN-13:00 | 0.95 |
February | 0.127554E+10 | 0.50 | 1326.69 | 10-FEB-11:20 | 0.95 |
March | 0.145470E+10 | 0.41 | 1326.69 | 04-MAR-07:30 | 0.95 |
April | 0.133829E+10 | 0.39 | 1326.69 | 20-APR-06:15 | 0.95 |
May | 0.138174E+10 | 0.38 | 1326.69 | 01-MAY-06:30 | 0.94 |
June | 0.140293E+10 | 0.40 | 1326.69 | 01-JUN-06:10 | 0.94 |
July | 0.143721E+10 | 0.41 | 1326.69 | 03-JUL-14:10 | 0.94 |
August | 0.155045E+10 | 0.46 | 1326.69 | 01-AUG-13:50 | 0.94 |
September | 0.136424E+10 | 0.39 | 1326.69 | 01-SEP-15:30 | 0.94 |
October | 0.132915E+10 | 0.37 | 1326.69 | 30-OCT-07:00 | 0.95 |
November | 0.129265E+10 | 0.38 | 1326.69 | 07-NOV-07:30 | 0.94 |
December | 0.136744E+10 | 0.44 | 1326.69 | 11-DEC-15:10 | 0.95 |
Annual Sum or Average | 0.165911E+11 | 0.42 | |||
Minimum of Months | 0.127554E+10 | 0.37 | 1326.69 | 0.94 | |
Maximum of Months | 0.155045E+10 | 0.52 | 1326.69 | 0.95 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.410762E+10 | 0.76 | 3446.42 | 05-JAN-08:00 | 0.91 |
February | 0.362026E+10 | 0.68 | 3446.42 | 01-FEB-08:20 | 0.91 |
March | 0.385123E+10 | 0.53 | 3446.42 | 24-MAR-06:30 | 0.91 |
April | 0.345261E+10 | 0.39 | 3446.42 | 27-APR-12:50 | 0.90 |
May | 0.354843E+10 | 0.35 | 3446.42 | 05-MAY-14:40 | 0.90 |
June | 0.355334E+10 | 0.36 | 3446.42 | 09-JUN-16:00 | 0.91 |
July | 0.346870E+10 | 0.35 | 3446.42 | 06-JUL-14:00 | 0.90 |
August | 0.373760E+10 | 0.38 | 3446.42 | 07-AUG-15:30 | 0.90 |
September | 0.341351E+10 | 0.35 | 3446.42 | 08-SEP-16:00 | 0.91 |
October | 0.342638E+10 | 0.35 | 3446.42 | 30-OCT-06:20 | 0.91 |
November | 0.355097E+10 | 0.58 | 3446.42 | 13-NOV-17:40 | 0.91 |
December | 0.398167E+10 | 0.75 | 3446.42 | 01-DEC-08:50 | 0.91 |
Annual Sum or Average | 0.437123E+11 | 0.48 | |||
Minimum of Months | 0.341351E+10 | 0.35 | 3446.42 | 0.90 | |
Maximum of Months | 0.410762E+10 | 0.76 | 3446.42 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.139678E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.127554E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.145470E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.142800E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.157650E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.182258E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.252813E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.300348E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.178785E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.134091E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.129698E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.136744E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.202789E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.127554E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.300348E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.410762E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.362026E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.385123E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.350258E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.366249E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.392808E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.511233E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.621451E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.378400E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.342638E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.355097E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.398167E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.487421E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.342638E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.621451E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.139678E+10 | 0.00 | 0.588499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127554E+10 | 99.34 | 0.429438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145470E+10 | 1014.40 | 0.247078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133829E+10 | 0.331159E+09 | 0.119955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138174E+10 | 0.745924E+09 | 0.238450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140293E+10 | 0.160786E+10 | 26201782.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143721E+10 | 0.418594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.155045E+10 | 0.549119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136424E+10 | 0.164109E+10 | 12030429.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132915E+10 | 44031375.11 | 0.791217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129265E+10 | 15810403.04 | 0.274368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136744E+10 | 0.00 | 0.464361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165911E+11 | 0.140630E+11 | 0.223049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.155045E+10 | 0.549119E+10 | 0.588499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.410762E+10 | 0.00 | 0.197604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.362026E+10 | 0.00 | 0.135749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.385123E+10 | 0.00 | 0.432992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.345261E+10 | 0.167093E+09 | 0.100924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.354843E+10 | 0.394551E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.355334E+10 | 0.131026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.346870E+10 | 0.578793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.373760E+10 | 0.859384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.341351E+10 | 0.130300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.342638E+10 | 175.80 | 0.356385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.355097E+10 | 0.00 | 0.729230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.398167E+10 | 0.00 | 0.157222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.437123E+11 | 0.175567E+11 | 0.620453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.341351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.410762E+10 | 0.859384E+10 | 0.197604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.139678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127554E+10 | 0.00 | 0.00 | 0.00 | 27.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145470E+10 | 0.00 | 0.00 | 0.00 | 282.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133829E+10 | 0.00 | 0.00 | 0.00 | 89714066.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138174E+10 | 0.00 | 0.00 | 0.00 | 0.194767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140293E+10 | 0.00 | 0.00 | 0.00 | 0.419647E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143721E+10 | 0.00 | 0.00 | 0.00 | 0.109092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.155045E+10 | 0.00 | 0.00 | 0.00 | 0.145303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136424E+10 | 0.00 | 0.00 | 0.00 | 0.423610E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132915E+10 | 0.00 | 0.00 | 0.00 | 11760523.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129265E+10 | 0.00 | 0.00 | 0.00 | 4323733.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165911E+11 | 0.00 | 0.00 | 0.00 | 0.368777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.155045E+10 | 0.00 | 0.00 | 0.00 | 0.145303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.410762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.362026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.385123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.345261E+10 | 0.00 | 0.00 | 0.00 | 49976481.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.354843E+10 | 0.00 | 0.00 | 0.00 | 0.114061E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.355334E+10 | 0.00 | 0.00 | 0.00 | 0.374732E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.346870E+10 | 0.00 | 0.00 | 0.00 | 0.164363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.373760E+10 | 0.00 | 0.00 | 0.00 | 0.247692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.341351E+10 | 0.00 | 0.00 | 0.00 | 0.370484E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.342638E+10 | 0.00 | 0.00 | 0.00 | 51.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.355097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.398167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.437123E+11 | 0.00 | 0.00 | 0.00 | 0.502980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.341351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.410762E+10 | 0.00 | 0.00 | 0.00 | 0.247692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 24159017.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189329E+10 | 0.00 | 0.00 | 0.12 |
February | 0.273910E+09 | 0.00 | 0.00 | 6455.72 | 0.00 | 0.132501E+10 | 20519183.52 | 0.00 | 0.13 |
March | 0.743111E+09 | 0.00 | 0.00 | 29750.47 | 0.00 | 0.849404E+09 | 90857192.65 | 0.00 | 0.14 |
April | 0.799090E+09 | 5457170.25 | 0.00 | 592983.09 | 0.00 | 0.307881E+09 | 0.535705E+09 | 0.00 | 0.20 |
May | 0.428653E+09 | 11521433.76 | 0.00 | 2853285.30 | 0.00 | 13866166.16 | 0.230664E+10 | 0.00 | 0.42 |
June | 0.118459E+09 | 7425369.12 | 0.00 | 5354069.19 | 0.00 | 0.00 | 0.345535E+10 | 0.00 | 0.68 |
July | 15390784.10 | 84060079.09 | 0.00 | 6986724.50 | 0.00 | 0.00 | 0.322680E+10 | 0.00 | 0.81 |
August | 25179464.18 | 0.168172E+09 | 0.00 | 6093365.19 | 0.00 | 0.00 | 0.290816E+10 | 0.00 | 0.76 |
September | 96400233.04 | 21112902.49 | 0.00 | 5102565.11 | 0.00 | 0.00 | 0.341843E+10 | 0.00 | 0.66 |
October | 0.840601E+09 | 0.00 | 0.00 | 758951.83 | 0.00 | 0.183718E+09 | 0.882427E+09 | 0.00 | 0.21 |
November | 0.470277E+09 | 0.00 | 0.00 | 70548.52 | 0.00 | 0.102842E+10 | 74010461.29 | 0.00 | 0.14 |
December | 0.118504E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170195E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.395373E+10 | 0.297749E+09 | 0.00 | 27848698.90 | 0.00 | 0.730353E+10 | 0.169189E+11 | 0.00 | 0.37 |
Minimum of Months | 15390784.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.840601E+09 | 0.168172E+09 | 0.00 | 6986724.50 | 0.00 | 0.189329E+10 | 0.345535E+10 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.426331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104941E+10 | 0.00 | 0.00 | 0.17 |
February | 0.400431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627476E+09 | 0.00 | 0.00 | 0.18 |
March | 0.499804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93297403.91 | 0.00 | 0.00 | 0.19 |
April | 0.440156E+10 | 0.00 | 0.00 | 361287.86 | 0.00 | 2847132.18 | 0.265723E+09 | 0.00 | 0.20 |
May | 0.447730E+10 | 0.00 | 0.00 | 1901110.80 | 0.00 | 0.00 | 0.168629E+10 | 0.00 | 0.27 |
June | 0.277979E+10 | 75437.43 | 0.00 | 6309943.75 | 0.00 | 0.00 | 0.500748E+10 | 0.00 | 0.40 |
July | 0.111517E+10 | 54137378.50 | 0.00 | 13641267.83 | 0.00 | 0.00 | 0.775669E+10 | 0.00 | 0.58 |
August | 0.106439E+10 | 0.187541E+09 | 0.00 | 12030269.12 | 0.00 | 0.00 | 0.655101E+10 | 0.00 | 0.56 |
September | 0.312082E+10 | 0.00 | 0.00 | 6188718.17 | 0.00 | 0.00 | 0.457337E+10 | 0.00 | 0.39 |
October | 0.451199E+10 | 0.00 | 0.00 | 47397.21 | 0.00 | 0.00 | 95307033.43 | 0.00 | 0.18 |
November | 0.421300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227234E+09 | 0.00 | 0.00 | 0.17 |
December | 0.411834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935441E+09 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.430680E+11 | 0.241754E+09 | 0.00 | 40479994.75 | 0.00 | 0.293571E+10 | 0.259359E+11 | 0.00 | 0.29 |
Minimum of Months | 0.106439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.499804E+10 | 0.187541E+09 | 0.00 | 13641267.83 | 0.00 | 0.104941E+10 | 0.775669E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.101827E+12 | 0.537970E+11 | 0.00 | 0.723017E+10 | 0.208506E+11 |
February | 0.248815E+12 | 0.470262E+11 | 0.00 | 0.625123E+10 | 0.142476E+11 |
March | 0.500028E+12 | 0.494776E+11 | 0.00 | 0.677474E+10 | 0.333124E+10 |
April | 0.805803E+12 | 0.504644E+11 | 0.00 | 0.630830E+10 | 0.170649E+10 |
May | 0.109127E+13 | 0.614040E+11 | 0.00 | 0.891776E+10 | 0.156196E+10 |
June | 0.111096E+13 | 0.591139E+11 | 0.00 | 0.113953E+11 | 0.372578E+10 |
July | 0.119365E+13 | 0.572492E+11 | 0.00 | 0.120741E+11 | 0.127084E+11 |
August | 0.941143E+12 | 0.555403E+11 | 0.00 | 0.104008E+11 | 0.180150E+11 |
September | 0.662249E+12 | 0.383450E+11 | 0.00 | 0.112670E+11 | 0.374464E+10 |
October | 0.388860E+12 | 0.491342E+11 | 0.00 | 0.651485E+10 | 0.613930E+09 |
November | 0.134002E+12 | 0.410817E+11 | 0.00 | 0.601301E+10 | 0.538782E+10 |
December | 0.687268E+11 | 0.421021E+11 | 0.00 | 0.687424E+10 | 0.149937E+11 |
Annual Sum or Average | 0.724734E+13 | 0.604736E+12 | 0.00 | 0.100021E+12 | 0.100887E+12 |
Minimum of Months | 0.687268E+11 | 0.383450E+11 | 0.00 | 0.601301E+10 | 0.613930E+09 |
Maximum of Months | 0.119365E+13 | 0.614040E+11 | 0.00 | 0.120741E+11 | 0.208506E+11 |