Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2023-10-16 10:41:49
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1172.62 | 242.52 | 242.52 |
Net Site Energy | 1172.62 | 242.52 | 242.52 |
Total Source Energy | 2629.31 | 543.79 | 543.79 |
Net Source Energy | 2629.31 | 543.79 | 543.79 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 520.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 22.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 92.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 137.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 61.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 652.04 | 520.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 520.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 22.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 311.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 92.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 137.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 3.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 58.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 25.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 520.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 22.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 311.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 92.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 137.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 61.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 25.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 83.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 22.88 | 107.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 134.85 | 107.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 83.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 22.88 | 107.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 134.85 | 107.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 652.039 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 652.039 | 100.00 |
Total On-Site and Utility Electric Sources | 652.039 | 100.00 |
Total Electricity End Uses | 652.039 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 63.17 |
Time Setpoint Not Met During Occupied Cooling | 3.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3114.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 135.81 |
Skylight-Roof Ratio [%] | 2.95 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 9.9957 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 10.2257 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 6.2431 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.5746 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.5746 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 9.9957 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 10.2257 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 6.2431 | 46.45 | 2.5587 | |
Total | 4835.13 | 7.5746 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 7.5746 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 7.5746 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-AUG-14:09 | 21-DEC-17:00 | - | - | - | - | - | - | - | - | - | - | 20-JUL-11:00 |
Heating | 0.00 | 288983.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 13952.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 21244.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7325.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1749.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 54326.33 | 288983.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 288983.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 13952.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 21244.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 5020.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1749.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 564.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 71.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 986.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 293.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 434.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 196.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 82.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2065.01 | 564.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 116.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 14.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 204.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 40.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 427.08 | 116.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 116.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 14.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 204.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 40.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 427.08 | 116.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.36 |
ZONE2 FINE STORAGE DIRECT AIR | 3.57 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 4.51 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 4.51 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 149985.33 |
PSZ-OFFICE HEATING COIL | 29148.91 |
PSZ-FINE STORAGE HEATING COIL | 99766.43 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 149985.34 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.36 | 1.36 | 1.36 | 1.36 | 1.36 | 1.36 | 1.00 | 1.00 | 1.36 |
PSZ-FINE STORAGE | 3.57 | 3.57 | 3.57 | 3.57 | 3.57 | 3.57 | 1.00 | 1.00 | 3.57 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.36 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 3.57 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.36 | 1501.19 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.57 | 6106.66 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.36 | 1.36 | 1.36 | 1.36 | 22444.83 | 29148.91 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 3.57 | 3.57 | 3.57 | 2.36 | 66227.52 | 99766.43 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.36 | 0.677946 | 0.903927 | 22444.83 | 11222.42 | 0.800660 | 0.800660 |
PSZ-FINE STORAGE COOLING COIL | 3.57 | 1.79 | 2.38 | 66227.52 | 33113.76 | 0.800440 | 0.800440 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 9.996 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.069 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 10.226 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.226 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 6.243 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 8.802 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2367.778 | 9.996 | 185.726 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2367.778 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 14248.589 | 10.226 | 474.953 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 14248.589 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 20008.023 | 6.243 | 289.971 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20008.023 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3263 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5039 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.4896 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.7823 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.7823 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.065 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.984 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.943 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.179 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.179 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.38866262E-07 | 0.77198350E-12 | 0.86409618E-13 | 0.0000000 |
2 | 1 | -5.2160226 | 0.42725752E-04 | -0.49098391E-04 | 0.74579932E-08 |
3 | 0 | 5.5423254 | 0.32626013 | 0.32635195 | |
4 | 2 | 0.53329527E-11 | 0.16835480E-15 | 0.21851247E-15 | 0.0000000 |
5 | 1 | -5.2159869 | 0.41525994E-04 | -0.31791204E-04 | 0.68735589E-11 |
6 | 0 | 5.7199065 | 0.50387806 | 0.50395137 | |
7 | 4 | 0.78026225E-12 | 0.12659145E-15 | -0.22020359E-14 | 0.11649932E-15 |
8 | 3 | -0.38432829E-03 | 0.34368276E-06 | -0.55745575E-04 | 0.14971848E-12 |
9 | 2 | 1.7386347 | 0.75169100E-02 | 1.1397638 | -0.73682039E-04 |
10 | 1 | -7.1298666 | 0.19478837 | -17.093767 | 0.33322565 |
11 | 0 | 5.7181297 | 0.12420785 | 16.280573 | |
12 | 4 | 0.72249793E-12 | -0.16720573E-15 | 0.22015083E-14 | 0.12409536E-15 |
13 | 3 | -0.36459118E-03 | 0.53555631E-06 | -0.52695411E-04 | 0.13865996E-12 |
14 | 2 | 1.6915239 | 0.11971291E-01 | 1.1039557 | -0.69896550E-04 |
15 | 1 | -7.1930661 | 0.31446443 | -16.864389 | 0.32415671 |
16 | 0 | 6.0306730 | 0.20232993 | 16.289252 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.22015083E-14 | -0.16720573E-15 | 0.72249793E-12 | 0.12409536E-15 |
85 | 3 | -0.52695411E-04 | 0.53555631E-06 | -0.36459118E-03 | 0.13865996E-12 |
86 | 2 | 1.1039557 | 0.11971291E-01 | 1.6915239 | -0.69896550E-04 |
87 | 1 | -16.864389 | 0.31446443 | -7.1930661 | 0.32415671 |
88 | 0 | 16.289252 | 0.20232993 | 6.0306730 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5016_SHGC_SOUTH_0.4 | 34 | 1 | VerySmooth | 2.852 | 2.852 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.5016_SHGC_NORTH_0.4 | 35 | 1 | VerySmooth | 2.852 | 2.852 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.5016_SHGC_EAST_0.4 | 36 | 1 | VerySmooth | 2.852 | 2.852 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.5016_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.852 | 2.852 | 1.000 | 0.401 | ||
5 | SKYLIGHT_U_1.02_SHGC_0.49 | 38 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.491 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.95586E-002 | 0.31435 | 0.46537 | 0.46537 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10843 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.95586E-002 | 0.31435 | 0.46537 | 0.46537 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10843 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.95586E-002 | 0.31435 | 0.46537 | 0.46537 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10843 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.95586E-002 | 0.31435 | 0.46537 | 0.46537 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10843 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.32532 | 0.12431 | 0.12431 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | CurtainWall | 5.547 | 0.455 | 0.435 |
2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.849 | 0.366 | 0.255 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.710 | 8.455E-004 | 5.523E-004 | 0.277 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1771E-004 |
2 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6181E-004 |
3 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0318E-004 |
4 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.1888E-004 |
5 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0256E-004 |
6 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.9354E-004 |
7 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2942E-004 |
8 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8650E-004 |
9 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1384E-004 |
10 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.0170E-004 |
11 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7851E-004 |
12 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6710E-004 |
13 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0521E-004 |
14 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.0001E-004 |
15 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0772E-004 |
16 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9482E-004 |
17 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.5987E-004 |
18 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5390E-004 |
19 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.8491E-004 |
20 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.8734E-004 |
21 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0247E-004 |
22 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7515E-004 |
23 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.9148E-004 |
24 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0330E-004 |
25 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.5943E-004 |
26 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4236E-004 |
27 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.7847E-004 |
28 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5671E-004 |
29 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3590E-003 |
30 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0487E-004 |
31 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6700E-003 |
32 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.0218E-005 |
33 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.2021E-004 |
34 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.7159E-005 |
35 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5854E-004 |
36 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0336E-004 |
37 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1560E-003 |
38 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1515E-005 |
39 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.5701E-004 |
40 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.3249E-005 |
41 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.7576E-004 |
42 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8275E-005 |
43 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.4663E-004 |
44 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1089E-005 |
45 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.8962E-004 |
46 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2793E-005 |
47 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3864E-004 |
48 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.0764E-005 |
49 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2001E-003 |
50 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.0612E-005 |
51 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4348E-003 |
52 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.4011E-005 |
53 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.7078E-004 |
54 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.3415E-005 |
55 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1104E-004 |
56 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.0887E-005 |
57 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0921E-003 |
58 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0466E-004 |
59 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3311E-003 |
60 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1280E-004 |
61 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.2364E-003 |
62 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.3518E-005 |
63 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3917E-003 |
64 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.3634E-005 |
65 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8386E-003 |
66 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7128E-004 |
67 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7006E-003 |
68 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9345E-004 |
69 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8167E-003 |
70 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1272E-004 |
71 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.4048E-003 |
72 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1670E-005 |
73 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.3813E-004 |
74 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.8675E-004 |
75 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0892E-004 |
76 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.5719E-004 |
77 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.2673E-004 |
78 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1359E-004 |
79 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0267E-003 |
80 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1033E-004 |
81 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.7106E-004 |
82 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0111E-003 |
83 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.2147E-004 |
84 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2140E-003 |
85 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5111E-004 |
86 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0183E-004 |
87 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.2865E-004 |
88 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4129E-004 |
89 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3010E-004 |
90 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9367E-003 |
91 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1219E-004 |
92 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.2106E-003 |
93 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0932E-004 |
94 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8455E-003 |
95 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4533E-004 |
96 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.8723E-004 |
97 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.6849E-005 |
98 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0497E-003 |
99 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.9667E-005 |
100 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9800E-003 |
101 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8458E-005 |
102 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.0176E-003 |
103 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.0097E-005 |
104 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.9266E-003 |
105 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.3665E-005 |
106 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.2265E-004 |
107 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.7391E-005 |
108 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6031E-004 |
109 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.7178E-005 |
110 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4384E-003 |
111 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.7229E-005 |
112 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5505E-003 |
113 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9451E-005 |
114 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.4524E-005 |
115 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2876E-005 |
116 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1174E-005 |
117 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2479E-005 |
118 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6103E-005 |
119 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1321E-005 |
120 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.9767E-005 |
121 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0309E-005 |
122 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9587E-005 |
123 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8132E-005 |
124 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0280E-005 |
125 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.4034E-005 |
126 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7947E-005 |
127 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4814E-005 |
128 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2243E-005 |
129 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9585E-005 |
130 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0209E-005 |
131 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2930E-005 |
132 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8455E-005 |
133 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2234E-005 |
134 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0359E-005 |
135 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1298E-005 |
136 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2681E-005 |
137 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3733E-004 |
138 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7545E-004 |
139 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.9760E-004 |
140 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9369E-004 |
141 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9564E-004 |
142 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3529E-004 |
143 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5955E-005 |
144 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2983E-005 |
145 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1534E-004 |
146 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9165E-004 |
147 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2237E-004 |
148 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9744E-004 |
149 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.9134E-005 |
150 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3166E-004 |
151 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1757E-005 |
152 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1077E-005 |
153 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1093E-004 |
154 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5483E-005 |
155 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1679E-004 |
156 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4854E-005 |
157 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.7649E-005 |
158 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6790E-005 |
159 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1734E-005 |
160 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2731E-005 |
161 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1790E-004 |
162 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2320E-005 |
163 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7217E-004 |
164 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.3169E-005 |
165 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9201E-004 |
166 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9535E-005 |
167 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5935E-005 |
168 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1887E-005 |
169 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6516E-004 |
170 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2042E-003 |
171 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7046E-004 |
172 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4671E-003 |
173 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6611E-004 |
174 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6703E-004 |
175 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6979E-005 |
176 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3777E-004 |
177 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.1684E-004 |
178 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9704E-004 |
179 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3991E-004 |
180 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2100E-004 |
181 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0693E-004 |
182 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7826E-004 |
183 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0720E-004 |
184 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4148E-004 |
185 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7478E-004 |
186 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.9091E-005 |
187 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8508E-004 |
188 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.7793E-005 |
189 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9580E-004 |
190 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.4096E-005 |
191 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0708E-004 |
192 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6592E-005 |
193 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5874E-004 |
194 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8445E-005 |
195 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6252E-004 |
196 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7141E-005 |
197 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6294E-004 |
198 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1004E-005 |
199 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6898E-005 |
200 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5662E-005 |
201 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1844E-003 |
202 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0372E-004 |
203 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3049E-003 |
204 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8240E-005 |
205 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2787E-003 |
206 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2286E-004 |
207 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2032E-004 |
208 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0902E-005 |
209 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2364E-003 |
210 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4509E-004 |
211 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3714E-003 |
212 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5217E-004 |
213 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3042E-003 |
214 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5905E-004 |
215 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2112E-004 |
216 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4671E-004 |
217 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0783E-004 |
218 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0555E-005 |
219 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0134E-004 |
220 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8462E-005 |
221 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6219E-004 |
222 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4491E-005 |
223 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7473E-004 |
224 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9066E-005 |
225 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1494E-004 |
226 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0091E-003 |
227 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0972E-004 |
228 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3188E-003 |
229 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6785E-004 |
230 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8401E-003 |
231 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7498E-004 |
232 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.5506E-004 |
233 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2149E-004 |
234 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0971E-005 |
235 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0049E-004 |
236 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8258E-005 |
237 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1832E-004 |
238 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5274E-005 |
239 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7446E-004 |
240 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1536E-005 |
241 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3256E-003 |
242 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0740E-004 |
243 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2762E-003 |
244 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.7745E-005 |
245 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9892E-003 |
246 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3498E-004 |
247 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2227E-003 |
248 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1450E-004 |
249 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3566E-003 |
250 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8850E-004 |
251 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3126E-003 |
252 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4941E-004 |
253 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0227E-003 |
254 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.6112E-004 |
255 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2269E-003 |
256 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1533E-004 |
257 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2644E-004 |
258 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1578E-003 |
259 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0595E-004 |
260 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1455E-003 |
261 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2515E-004 |
262 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0683E-003 |
263 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7501E-004 |
264 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6479E-003 |
265 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8374E-004 |
266 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9451E-005 |
267 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5851E-004 |
268 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6517E-005 |
269 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4671E-004 |
270 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2577E-005 |
271 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7296E-004 |
272 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1506E-005 |
273 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8541E-004 |
274 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1145E-003 |
275 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6039E-004 |
276 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.4568E-004 |
277 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5139E-004 |
278 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5741E-003 |
279 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7351E-004 |
280 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5793E-003 |
281 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.9035E-004 |
282 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.6913E-005 |
283 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6988E-004 |
284 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.5996E-005 |
285 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1524E-003 |
286 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1531E-004 |
287 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1889E-003 |
288 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1418E-004 |
289 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.9588E-004 |
290 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6036E-004 |
291 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7589E-004 |
292 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0670E-004 |
293 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1673E-003 |
294 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2754E-004 |
295 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1930E-003 |
296 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0887E-004 |
297 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2791E-004 |
298 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1558E-004 |
299 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0865E-004 |
300 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3304E-004 |
301 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4056E-004 |
302 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4882E-004 |
303 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7289E-004 |
304 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2588E-004 |
305 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4259E-004 |
306 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0699E-004 |
307 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7667E-004 |
308 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7056E-004 |
309 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7942E-004 |
310 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2955E-004 |
311 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0178E-004 |
312 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4028E-004 |
313 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0414E-005 |
314 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0131E-005 |
315 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8179E-005 |
316 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5916E-005 |
317 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3861E-005 |
318 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6575E-005 |
319 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4795E-005 |
320 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1676E-005 |
321 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2786E-004 |
322 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6551E-005 |
323 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0837E-004 |
324 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3810E-005 |
325 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3855E-004 |
326 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7928E-005 |
327 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7264E-004 |
328 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8999E-005 |
329 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4360E-005 |
330 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6730E-004 |
331 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2549E-005 |
332 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3452E-004 |
333 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7852E-005 |
334 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3980E-004 |
335 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5891E-005 |
336 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3195E-004 |
337 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5078E-004 |
338 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1339E-004 |
339 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2233E-004 |
340 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.4315E-005 |
341 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2864E-004 |
342 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9823E-005 |
343 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0257E-004 |
344 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3913E-004 |
345 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4557E-005 |
346 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3211E-005 |
347 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2590E-005 |
348 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0926E-005 |
349 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7149E-005 |
350 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3510E-005 |
351 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5813E-005 |
352 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5594E-005 |
353 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4274E-004 |
354 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8960E-005 |
355 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7643E-004 |
356 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9661E-005 |
357 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7608E-004 |
358 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.2603E-005 |
359 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0101E-004 |
360 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0338E-005 |
361 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5103E-004 |
362 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.2056E-005 |
363 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2242E-004 |
364 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5461E-005 |
365 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2793E-004 |
366 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8871E-005 |
367 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0246E-004 |
368 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6189E-005 |
369 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.3081E-002 |
370 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.6300E-004 |
371 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.3157E-002 |
372 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.1478E-004 |
373 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.0920E-002 |
374 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.9380E-004 |
375 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.1238E-003 |
376 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 4.9215E-004 |
377 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.7264E-004 |
378 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.0086E-002 |
379 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.2762E-004 |
380 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.5725E-002 |
381 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.9792E-004 |
382 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.5136E-002 |
383 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.9195E-004 |
384 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.7684E-002 |
385 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.6903E-003 |
386 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.6733E-004 |
387 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.3170E-003 |
388 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.8933E-004 |
389 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.0707E-003 |
390 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.2088E-004 |
391 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.2005E-003 |
392 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.0398E-004 |
393 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.3492E-002 |
394 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.7531E-004 |
395 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.0008E-002 |
396 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.9490E-004 |
397 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 7.2006E-003 |
398 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.2213E-004 |
399 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.1869E-002 |
400 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.0618E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11148.27021 | 13377.92425 | 1.12991 | 1.35589 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 32.42000 | 5.47299E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 10553.23994 | 12663.88792 | 0.36507 | 0.43809 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -17.90000 | 9.55238E-004 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 37700.06097 | 45240.07317 | 2.97840 | 3.57408 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.90000 | 5.47527E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 38349.87890 | 46019.85468 | 1.11706 | 1.34047 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | -17.90000 | 9.55238E-004 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.90000 | 5.47527E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 124987.78065 | 149985.33678 | 3.76205 | 4.51446 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 16718.67 | 1.35589 | 1.35589 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 12066.74 | 0.43809 | 0.43809 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 54605.52 | 3.57408 | 3.57408 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 46139.38 | 1.34047 | 1.34047 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.35589 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.57408 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 4.51446 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 4.51446 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 149985.32964 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 149985.33678 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.35589 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.35589 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.35589 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.35589 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.35589 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.35589 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.57408 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.57408 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.57408 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.57408 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.57408 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.57408 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.35589 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.57408 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.35589 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.35589 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1501.18800 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.35589 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.35589 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.35589 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.35589 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.35589 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.67795 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.90393 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22444.83000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11222.41500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22444.83000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29148.91239 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 29148.91239 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.57408 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.57408 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 6106.66387 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.57408 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.57408 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.57408 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.35889 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.57408 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.78704 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.38272 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 66227.52000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 33113.76000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80044 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80044 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 66227.52000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 99766.42646 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 99766.42646 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 21392.7 | 11.40 | 11.14 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 63453.0 | 11.49 | 11.23 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1891867874 | 0.1883073157 | Pass | Pass | 0.8038281321 | 4.3254368546 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.4819716833 | 0.5411133494 | Pass | Pass | 0.7096097066 | 1.0848126358 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 1.2098589282E-002 | 2.6624166650E-002 | Pass | Pass | 9.9720453067E-002 | 0.5397571380 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 9855.03 | 544.90 | 0.00 | 75.67 | 237.31 | 10712.93 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 11.00 | 10 | |||
Feb | 15.00 | 16 | |||
Mar | 88.00 | 32 | |||
Apr | 159.00 | 54 | |||
May | 30.00 | 24 | |||
Jun | 11.00 | 4 | |||
Jul | 167.00 | 26 | |||
Aug | 33.00 | 24 | |||
Sep | 8.00 | 8 | |||
Oct | 13.00 | 10 | |||
Nov | 12.00 | 22 | |||
Dec | 11.00 | 18 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.456 | 0.490 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.456 | 0.490 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.456 | 0.490 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.456 | 0.490 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.456 | 0.490 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.456 | 0.490 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.456 | 0.490 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.312 | 0.326 | 1393.41 | 1368.35 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.471 | 0.504 | 3204.84 | 3094.09 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.659 | 0.782 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.659 | 0.782 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.5016_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.852 | 0.401 | 0.402 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.5016_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.852 | 0.401 | 0.402 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.5016_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.852 | 0.401 | 0.402 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.5016_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.852 | 0.401 | 0.402 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 153.47 | 5.459 | 0.524 | 0.525 | |||||||||||||||||
North Total or Average | 6.51 | 2.852 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 146.96 | 5.575 | 0.529 | 0.530 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 9.9957 | 236.88 | 2367.78 | LightsWired | LTG_SCH_OFFICE | 56.95 | 168.00 | 48.37 | 0.0000 | Y | 21.50 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 10.2257 | 1393.41 | 14248.59 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 49.60 | 0.0000 | Y | 132.67 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 6.2431 | 3204.84 | 20008.02 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 41.91 | 0.0000 | Y | 157.41 |
Interior Lighting Total | 7.5746 | 4835.13 | 36624.39 | 311.58 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 14248.59 | 3562.15 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 14248.59 | 3562.15 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 20008.02 | 5002.01 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 20008.02 | 5002.01 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.11 | 2367.78 | 260.46 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.11 | 2367.78 | 260.46 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 125.92 | AstronomicalClock | - | 42.26 | 42.26 | 1.00 | |
EXTERIOR_LIGHTS_B | 6860.50 | AstronomicalClock | - | 83.67 | 71.25 | 91.75 | |
Exterior Lighting Total | 6986.42 | 92.75 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22444.83 | 17970.68 | 4474.15 | 0.80 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 66227.52 | 53011.16 | 13216.36 | 0.80 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 21392.7 | 11.40 | 11.14 | ||||
PSZ-FINE STORAGE COOLING COIL | 63453.0 | 11.49 | 11.23 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 149985.33 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 29148.91 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 99766.43 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 4.51 | 419.44 | 92.91 | 1.00 | 3.19 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.36 | 1501.19 | 1107.16 | 1.00 | 1.34 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.60 | 1018.41 | 3.57 | 6106.66 | 1708.60 | 1.00 | 1.19 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11148.27 | 13377.92 | 56.48 | 1.130 | 1.356 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 23.90 | 23.90 | 0.00819 | 32.42 | 0.00547 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 37700.06 | 45240.07 | 32.47 | 2.978 | 3.574 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 26.70 | 26.70 | 0.00808 | 33.90 | 0.00548 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 0.00 | 34.15 | 0.00557 | 33.90 | 0.00548 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10553.24 | 12663.89 | 53.46 | 0.365 | 0.438 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00787 | -17.90 | 0.00096 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 38349.88 | 46019.85 | 33.03 | 1.117 | 1.340 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 15.56 | 15.56 | 0.00689 | -17.90 | 0.00096 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 124987.78 | 149985.34 | 46.80 | 3.762 | 4.514 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00609 | -17.90 | 0.00096 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.36 | 1.36 | 0.44 | 0.44 | 1.3559 | 1.3559 | 1.3559 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.57 | 3.57 | 1.34 | 1.34 | 3.5741 | 3.5741 | 3.5741 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 149985.330 | 149985.330 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 149985.33 | 149985.33 | 4.514458 | 10.00 | 6.62 | 0.00608979 | 43.33 | 19.68 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 10.00 | 0.00608979 | 64.9469 | 149985.34 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 22444.830 | 17970.678 | 1.355890 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 11222.42 | 11222.42 | 0.903927 | 25.68 | 14.40 | 0.00798819 | 12.00 | 9.41 | 0.00798819 | 32.81 | 0.00547359 | 14.72 | 11.3156 | 23.90 | 0.00819369 | 36.0377 | 11131.70 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 29148.912 | 29148.912 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 29148.91 | 29148.91 | 1.355892 | 18.11 | 11.17 | 0.00735088 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 7.5437 | 21.10 | 0.00787272 | 41.0690 | 10553.24 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 66227.520 | 53011.156 | 3.574080 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33113.76 | 33113.76 | 2.382720 | 29.27 | 15.39 | 0.00777393 | 12.00 | 9.20 | 0.00777393 | 33.90 | 0.00547527 | 15.07 | 17.8246 | 26.70 | 0.00808391 | 30.1045 | 37699.93 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 99766.426 | 99766.426 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 99766.43 | 99766.43 | 3.574078 | 11.58 | 7.41 | 0.00618291 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 11.8831 | 15.56 | 0.00688790 | 50.9632 | 38349.88 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 149985.330 | 149985.330 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 4.514458 | 4.41260082 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 149985.33 | 149985.33 | 1.0000 | 4.41260082 | 4.514458 | 10.00 | 6.62 | 0.00608979 | 25388.6 | 43.33 | 19.68 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 149985.33 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 10.00 | 0.00608979 | 10.00 | 0.00608979 | 64.9469 | 149985.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22444.830 | 17970.678 | 1.355890 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6896 | 1004.8586 | 0.9774 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.355892 | 1.32530012 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | Sensible | 11222.42 | 11222.42 | 1.0000 | 0.88353192 | 0.903927 | 25.68 | 14.40 | 0.00798819 | 46167.2 | 12.00 | 9.41 | 0.00798819 | 32214.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11222.42 | 32.81 | 0.00547359 | 14.72 | 0.10228463 | 11.3156 | 23.90 | 0.00819369 | 23.90 | 0.00819369 | 36.0377 | 11131.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29148.912 | 29148.912 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.355892 | 1.32530012 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 29148.91 | 29148.91 | 1.0000 | 1.32530012 | 1.355892 | 18.11 | 11.17 | 0.00735088 | 36831.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29148.91 | -17.90 | 0.00095524 | -17.90 | 0.10228463 | 7.5437 | 21.05 | 0.00787272 | 21.10 | 0.00787272 | 41.0690 | 10553.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 66227.520 | 53011.156 | 3.574080 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2913 | 1004.8586 | 0.9774 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.574078 | 3.49343848 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 33113.76 | 33113.76 | 1.0000 | 2.32896015 | 2.382720 | 29.27 | 15.39 | 0.00777393 | 49277.0 | 12.00 | 9.20 | 0.00777393 | 31673.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33113.76 | 33.90 | 0.00547527 | 15.07 | 0.42471127 | 17.8246 | 26.70 | 0.00808391 | 26.70 | 0.00808391 | 30.1045 | 37699.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 99766.426 | 99766.426 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.574078 | 3.49343848 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | Sensible | 99766.43 | 99766.43 | 1.0000 | 3.49343848 | 3.574078 | 11.58 | 7.41 | 0.00618291 | 27232.1 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 99766.43 | -17.90 | 0.00095524 | -17.90 | 0.42471127 | 11.8831 | 15.56 | 0.00688790 | 15.56 | 0.00688790 | 50.9632 | 38349.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.36 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 3.57 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2274.00 | 2587.67 | 1609.50 |
ZONE2 FINE STORAGE | 3084.50 | 2949.00 | 2490.17 |
ZONE3 BULK STORAGE | 3318.33 | 3376.83 | 3102.33 |
Facility | 3477.50 | 3461.83 | 3114.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 98.50 | 70.83 | 52.50 | 3.67 |
ZONE2 FINE STORAGE | 401.83 | 34.67 | 24.83 | 0.00 |
ZONE3 BULK STORAGE | 2.67 | 0.00 | 0.00 | 0.00 |
Facility | 467.00 | 95.33 | 63.17 | 3.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.814 | 0.305 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.616 | 0.237 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.141 | 0.000 | 0.422 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.50 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.36 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.28 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 3253273.24 | 0.00 | 3253273.24 | 1841849.66 | 5095122.90 | 3225648.14 | 5514.92 | 2244.36 | 1000.71 | 151.64 |
ZONE2 FINE STORAGE | 6651728.31 | 0.00 | 6651728.31 | 6789202.86 | 13440931.17 | 13393694.68 | 5694.80 | 2541.75 | 523.45 | 17.93 |
ZONE3 BULK STORAGE | 0.00 | 77281387.68 | 77281387.68 | 38312560.14 | 0.12E+09 | 30805497.77 | 7802.50 | 35.72 | 921.78 | 5116.83 |
Total Facility | 9905001.55 | 77281387.68 | 87186389.23 | 46943612.66 | 0.13E+09 | 47424840.58 | 8175.27 | 2755.31 | 2062.30 | 5116.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.2262 | 0.0000 | 0.2262 | 0.0849 | 0.3111 | 0.1023 | 517.15 | 2244.19 | 874.66 |
ZONE2 FINE STORAGE | 0.5004 | 0.0000 | 0.5004 | 0.1939 | 0.6943 | 0.4247 | 588.42 | 2541.75 | 505.83 |
ZONE3 BULK STORAGE | 0.0000 | 4.0358 | 4.0358 | 1.3923 | 5.4281 | 0.9768 | 3031.56 | 17.33 | 587.10 |
Total Facility | 0.7266 | 4.0358 | 4.7624 | 1.6711 | 6.4335 | 1.5038 | 3051.40 | 2736.75 | 1589.34 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 3108126.13 | 0.00 | 3108126.13 | 3225648.14 | 7760.62 | 1.08 | 998.30 | 151.64 |
PSZ-FINE STORAGE | 6354953.18 | 0.00 | 6354953.18 | 13393694.68 | 8237.97 | 0.33 | 521.70 | 17.93 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2161 | 0.0000 | 0.2161 | 0.1023 | 2762.51 | 0.92 | 872.57 |
PSZ-FINE STORAGE | 0.4781 | 0.0000 | 0.4781 | 0.4247 | 3131.58 | 0.33 | 504.08 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2756.28 | 525.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2909.60 | 167.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2195 | 0.4250 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.5483 | 0.9190 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 429 |
Defaulted Fields | 391 |
Fields with Defaults | 1171 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 652.04 | 2970.19 | 19-FEB-13:40 | 54326.33 | 16-AUG-14:10 |
Electricity:Building | 452.55 | 2489.19 | 19-FEB-13:30 | 40750.63 | 04-JAN-15:50 |
Electricity:Zone:ZONE1 OFFICE | 51.22 | 776.36 | 01-JAN-14:10 | 3432.39 | 02-JAN-16:30 |
Electricity:SpaceType:GENERAL | 448.65 | 2489.19 | 19-FEB-13:30 | 40750.63 | 04-JAN-15:50 |
InteriorLights:Electricity | 311.58 | 2000.65 | 19-FEB-13:30 | 30696.62 | 04-JAN-15:50 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 21.50 | 287.82 | 01-JAN-14:10 | 1578.50 | 02-JAN-16:30 |
InteriorLights:Electricity:SpaceType:GENERAL | 311.58 | 2000.65 | 19-FEB-13:30 | 30696.62 | 04-JAN-15:50 |
LightsWired:InteriorLights:Electricity | 311.58 | 2000.65 | 19-FEB-13:30 | 30696.62 | 04-JAN-15:50 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 21.50 | 287.82 | 01-JAN-14:10 | 1578.50 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 311.58 | 2000.65 | 19-FEB-13:30 | 30696.62 | 04-JAN-15:50 |
Electricity:Zone:ZONE2 FINE STORAGE | 132.68 | 712.43 | 19-FEB-13:30 | 12111.30 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 132.68 | 712.43 | 19-FEB-13:30 | 12111.30 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 132.68 | 712.43 | 19-FEB-13:30 | 12111.30 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 268.66 | 1000.40 | 08-JAN-11:00 | 25206.94 | 02-JAN-15:50 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 157.41 | 1000.40 | 08-JAN-11:00 | 17006.82 | 02-JAN-15:50 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 157.41 | 1000.40 | 08-JAN-11:00 | 17006.82 | 02-JAN-15:50 |
InteriorEquipment:Electricity | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.72 | 488.55 | 01-JAN-00:10 | 1853.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.72 | 488.55 | 01-JAN-00:10 | 1853.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 61.95 | 0.00 | 01-JAN-10:00 | 7791.28 | 26-JUN-15:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 3.91 | 0.00 | 01-JAN-00:10 | 2305.29 | 26-JUN-09:50 |
Ventilation (simple):Fans:Electricity | 3.91 | 0.00 | 01-JAN-00:10 | 2305.29 | 26-JUN-09:50 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 3.91 | 0.00 | 01-JAN-00:10 | 2305.29 | 26-JUN-09:50 |
ElectricityPurchased:Facility | 652.04 | 2970.19 | 04-JUN-12:20 | 54326.33 | 16-AUG-14:10 |
ElectricityPurchased:Plant | 652.04 | 2970.19 | 04-JUN-12:20 | 54326.33 | 16-AUG-14:10 |
Cogeneration:ElectricityPurchased | 652.04 | 2970.19 | 04-JUN-12:20 | 54326.33 | 16-AUG-14:10 |
General:Cogeneration:ElectricityPurchased | 652.04 | 2970.19 | 04-JUN-12:20 | 54326.33 | 16-AUG-14:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 652.04 | 2970.19 | 04-JUN-12:20 | 54326.33 | 16-AUG-14:10 |
ElectricityNet:Plant | 652.04 | 2970.19 | 04-JUN-12:20 | 54326.33 | 16-AUG-14:10 |
Cogeneration:ElectricityNet | 652.04 | 2970.19 | 04-JUN-12:20 | 54326.33 | 16-AUG-14:10 |
General:Cogeneration:ElectricityNet | 652.04 | 2970.19 | 04-JUN-12:20 | 54326.33 | 16-AUG-14:10 |
Electricity:HVAC | 80.74 | 0.00 | 01-JAN-10:00 | 21764.43 | 26-JUN-15:10 |
General:Fans:Electricity | 58.05 | 0.00 | 01-JAN-10:00 | 6312.51 | 21-DEC-18:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 22.69 | 0.00 | 01-JAN-00:10 | 16278.44 | 26-JUN-15:10 |
General:Cooling:Electricity | 22.69 | 0.00 | 01-JAN-00:10 | 16278.44 | 26-JUN-15:10 |
ExteriorLights:Electricity | 92.75 | 0.00 | 01-JAN-07:30 | 6986.42 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 92.75 | 0.00 | 01-JAN-07:30 | 6986.42 | 01-JAN-06:10 |
Electricity:Plant | 25.99 | 481.00 | 05-JAN-06:30 | 2602.82 | 13-FEB-13:00 |
WaterSystems:Electricity | 25.99 | 481.00 | 05-JAN-06:30 | 2602.82 | 13-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 25.99 | 481.00 | 05-JAN-06:30 | 2602.82 | 13-FEB-13:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 520.58 | 0.00 | 01-JAN-10:00 | 288983.99 | 21-DEC-18:00 |
NaturalGas:HVAC | 520.58 | 0.00 | 01-JAN-10:00 | 288983.99 | 21-DEC-18:00 |
Heating:NaturalGas | 520.58 | 0.00 | 01-JAN-10:00 | 288983.99 | 21-DEC-18:00 |
General:Heating:NaturalGas | 520.58 | 0.00 | 01-JAN-10:00 | 288983.99 | 21-DEC-18:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-JUL-12:00 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-JUL-12:00 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-JUL-12:00 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-JUL-12:00 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-JUL-12:00 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-JUL-12:00 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-JUL-12:00 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-JUL-12:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 978.00 | 0.00 | 01-JAN-10:00 | 439365.04 | 23-DEC-06:20 |
EnergyTransfer:Building | 492.29 | 0.00 | 01-JAN-10:00 | 221459.93 | 23-DEC-06:20 |
EnergyTransfer:Zone:ZONE1 OFFICE | 57.26 | 0.00 | 01-JAN-00:10 | 20802.16 | 20-DEC-07:10 |
Heating:EnergyTransfer | 399.15 | 0.00 | 01-JAN-10:00 | 221459.93 | 23-DEC-06:20 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 27.15 | 0.00 | 01-JAN-00:10 | 20802.16 | 20-DEC-07:10 |
General:Heating:EnergyTransfer | 399.15 | 0.00 | 01-JAN-10:00 | 221459.93 | 23-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 27.15 | 0.00 | 01-JAN-00:10 | 20802.16 | 20-DEC-07:10 |
Cooling:EnergyTransfer | 93.15 | 0.00 | 01-JAN-00:10 | 40087.02 | 26-JUN-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 30.10 | 0.00 | 01-JAN-00:10 | 11262.04 | 11-SEP-03:20 |
General:Cooling:EnergyTransfer | 93.15 | 0.00 | 01-JAN-00:10 | 40087.02 | 26-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 30.10 | 0.00 | 01-JAN-00:10 | 11262.04 | 11-SEP-03:20 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 160.55 | 0.00 | 01-JAN-00:40 | 54977.88 | 23-DEC-06:50 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 97.51 | 0.00 | 01-JAN-00:40 | 54977.88 | 23-DEC-06:50 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 97.51 | 0.00 | 01-JAN-00:40 | 54977.88 | 23-DEC-06:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 63.05 | 0.00 | 01-JAN-00:10 | 30578.43 | 26-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 63.05 | 0.00 | 01-JAN-00:10 | 30578.43 | 26-JUN-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 274.48 | 0.00 | 01-JAN-09:30 | 150913.11 | 21-DEC-23:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 274.48 | 0.00 | 01-JAN-09:30 | 150913.11 | 21-DEC-23:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 274.48 | 0.00 | 01-JAN-09:30 | 150913.11 | 21-DEC-23:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 485.71 | 0.00 | 01-JAN-10:00 | 224509.96 | 21-DEC-18:00 |
HeatingCoils:EnergyTransfer | 395.83 | 0.00 | 01-JAN-10:00 | 224509.96 | 21-DEC-18:00 |
CoolingCoils:EnergyTransfer | 89.88 | 0.00 | 01-JAN-00:10 | 52399.42 | 26-JUN-15:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 27.154 | -30.102 | 0.000 | 0.000 | 9.859 | 21.498 | 29.720 | 13.701 | 0.000 | 1.110 | 0.000 | 0.000 | -11.068 | 0.000 | -20.946 | -40.927 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 97.507 | -63.044 | 0.000 | 0.000 | 24.178 | 132.675 | 0.000 | 47.467 | 0.000 | 1.645 | 0.000 | 0.000 | -28.985 | 0.000 | -71.172 | -140.271 |
ZONE3 BULK STORAGE | 274.483 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 59.772 | 157.408 | 107.344 | 518.507 | 0.000 | 19.078 | 0.001 | 0.000 | -398.443 | 0.000 | -441.196 | -296.952 |
Total Facility | 274.483 | 0.000 | 124.661 | -93.146 | 0.000 | 0.000 | 93.809 | 311.582 | 137.063 | 579.675 | 0.000 | 21.833 | 0.001 | 0.000 | -438.496 | 0.000 | -533.314 | -478.150 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 13-AUG-23:02 | 0.00 | 0.00 | 0.00 | -26233.81 | 0.00 | 0.00 | 0.00 | 368.99 | 488.55 | 0.00 | 0.00 | 0.00 | 26241.47 | 0.00 | -490.69 | 0.00 | -374.51 | 0.00 |
ZONE2 FINE STORAGE | 23-JUL-12:02 | 0.00 | 0.00 | 0.00 | -55160.69 | 0.00 | 0.00 | 0.00 | 712.43 | 0.00 | 9561.91 | 0.00 | 339.40 | 44546.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JUL-17:06 | 0.00 | 0.00 | 0.00 | -71686.13 | 0.00 | 0.00 | 0.00 | 3094.54 | 2538.58 | 58261.73 | 0.00 | 2602.88 | 5188.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 23-DEC-06:22 | 0.00 | 0.00 | 29982.83 | 0.00 | 0.00 | 0.00 | 118.54 | 471.50 | 556.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1551.72 | 0.00 | -2397.66 | -27179.66 |
ZONE2 FINE STORAGE | 23-DEC-06:41 | 0.00 | 0.00 | 108326.51 | 0.00 | 0.00 | 0.00 | 390.22 | 1424.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3600.80 | 0.00 | -11666.45 | -94874.35 |
ZONE3 BULK STORAGE | 21-DEC-23:00 | 150913.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -31029.70 | 0.00 | -102986.10 | -20948.52 |
Total Facility | 23-DEC-06:51 | 150404.77 | 0.00 | 127789.90 | 0.00 | 0.00 | 0.00 | 1412.69 | 3897.16 | 2606.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -63488.78 | 0.00 | -90370.07 | -132251.87 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3559 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.3559 | 0.0754 | 1.0000 | Not calculated | 0.1023 | 0.0754 | ||
PSZ-FINE STORAGE | 3.5741 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.5741 | 0.1188 | 1.0000 | Not calculated | 0.4247 | 0.1188 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3559 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.3559 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0754 | ||
PSZ-FINE STORAGE | 3.5741 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.5741 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1188 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3559 | 1.3559 | 1.3559 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.5741 | 3.5741 | 3.5741 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3559 | 1.3559 | 1.3559 | 1.3559 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.5741 | 3.5741 | 3.5741 | 3.5741 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3559 | 1.3559 | 1.3559 | No | 0.1023 | 0.2335 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.5741 | 3.5741 | 3.5741 | No | 0.4247 | 0.3168 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3559 | 1.3559 | 1.3559 | 1.3559 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.5741 | 3.5741 | 3.5741 | 3.5741 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 63.17 |
Number of hours cooling loads not met | 3.67 |
Number of hours not met | 66.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 520.58 | 288983.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 22.69 | 16278.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 311.58 | 30696.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 92.75 | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 137.06 | 10054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 3.91 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 58.05 | 6312.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 25.99 | 2602.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 137.06 | 652.04 |
Natural Gas | 0.00 | 520.58 |
Additional | 0.00 | 0.00 |
Total | 137.06 | 1172.62 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 64.44 |
Space Heating | 0.00 |
Space Cooling | 4.69 |
Fans (All) | 12.81 |
Service Water Heating | 5.38 |
Receptacle Equipment | 28.35 |
Miscellaneous (All) | 134.85 |
Subtotal | 134.85 |
Natural Gas [MJ/m2] | |
Space Heating | 107.67 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 107.67 |
Subtotal | 107.67 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 26.57 |
Space Heating | 44.39 |
Space Cooling | 1.94 |
Fans (All) | 5.28 |
Service Water Heating | 2.22 |
Receptacle Equipment | 11.69 |
Miscellaneous | 7.91 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2970. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4378. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8627.17 | 132.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8629.50 | 130.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7209.00 | 1541.67 | 9.33 | 0.00 | 0.00 |
Min | 7209.00 | 130.50 | 0.00 | 0.00 | 0.00 |
Max | 8629.50 | 1541.67 | 9.33 | 0.00 | 0.00 |
Average | 8155.22 | 601.67 | 3.11 | 0.00 | 0.00 |
Sum | 24465.67 | 1805.00 | 9.33 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 80290.50 | 2428.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 142029.50 | 48728.50 | 435.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 142029.50 | 48728.50 | 435.00 | 0.00 | 0.00 |
Average | 85115.67 | 17052.33 | 145.00 | 0.00 | 0.00 |
Sum | 255347.00 | 51157.00 | 435.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8713.00 | 47.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8530.50 | 229.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7921.00 | 839.00 | 0.00 | 0.00 | 0.00 |
Min | 7921.00 | 47.00 | 0.00 | 0.00 | 0.00 |
Max | 8713.00 | 839.00 | 0.00 | 0.00 | 0.00 |
Average | 8388.17 | 371.83 | 0.00 | 0.00 | 0.00 |
Sum | 25164.50 | 1115.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 33024.33 | 2.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 79621.50 | 3097.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 162657.17 | 28535.83 | 0.00 | 0.00 | 0.00 |
Min | 33024.33 | 2.67 | 0.00 | 0.00 | 0.00 |
Max | 162657.17 | 28535.83 | 0.00 | 0.00 | 0.00 |
Average | 91767.67 | 10545.33 | 0.00 | 0.00 | 0.00 |
Sum | 275303.00 | 31636.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4461744.60 | 375.90 | 11-JAN-15:10 | 2.83 | 2.83 | 0.514992E+09 | 768.97 | 20-JAN-14:39 | 20.33 | 6.84 |
February | 4949125.28 | 247.06 | 18-FEB-14:50 | 19.17 | 7.95 | 0.466861E+09 | 768.97 | 18-FEB-16:00 | 17.00 | 6.80 |
March | 0.197957E+09 | 3289.50 | 15-MAR-16:00 | 19.00 | 5.38 | 0.577068E+09 | 768.97 | 08-MAR-16:00 | 19.00 | 5.38 |
April | 0.105288E+09 | 1971.45 | 21-APR-13:50 | 15.17 | 5.71 | 0.541624E+09 | 768.97 | 06-APR-15:30 | 15.17 | 5.71 |
May | 0.164887E+10 | 21801.79 | 09-MAY-17:21 | 20.50 | 8.47 | 0.636181E+09 | 768.98 | 30-MAY-15:00 | 21.10 | 13.26 |
June | 0.708226E+10 | 25405.16 | 25-JUN-23:01 | 19.40 | 11.14 | 0.659930E+09 | 769.04 | 22-JUN-13:50 | 19.40 | 11.14 |
July | 0.699514E+10 | 25741.22 | 02-JUL-23:01 | 17.83 | 10.79 | 0.634661E+09 | 769.04 | 31-JUL-15:00 | 18.00 | 17.32 |
August | 0.759999E+10 | 26233.30 | 13-AUG-23:02 | 16.17 | 9.05 | 0.685388E+09 | 769.04 | 05-AUG-15:50 | 16.17 | 9.05 |
September | 0.536377E+10 | 26127.80 | 17-SEP-23:02 | 14.80 | 8.48 | 0.632306E+09 | 769.01 | 01-SEP-14:09 | 14.80 | 8.48 |
October | 0.980760E+09 | 20067.41 | 07-OCT-17:15 | 19.67 | 8.38 | 0.580851E+09 | 768.96 | 13-OCT-12:09 | 16.17 | 6.99 |
November | 0.115028E+09 | 2274.38 | 07-NOV-15:30 | 21.50 | 7.27 | 0.513165E+09 | 768.97 | 07-NOV-13:09 | 21.50 | 7.27 |
December | 3952859.31 | 534.98 | 02-DEC-15:30 | 20.00 | 7.03 | 0.511377E+09 | 768.97 | 02-DEC-14:20 | 20.00 | 7.03 |
Annual Sum or Average | 0.301024E+11 | 0.695440E+10 | ||||||||
Minimum of Months | 3952859.31 | 247.06 | 2.83 | 2.83 | 0.466861E+09 | 768.96 | 14.80 | 5.38 | ||
Maximum of Months | 0.759999E+10 | 26233.30 | 21.50 | 11.14 | 0.685388E+09 | 769.04 | 21.50 | 17.32 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148337E+10 | 6036.00 | 14-JAN-16:15 | -5.3 | -5.3 | 0.810794E+09 | 1586.48 | 20-JAN-14:30 | 20.50 | 6.87 |
February | 0.154570E+10 | 5644.30 | 11-FEB-14:00 | -7.0 | -7.4 | 0.724578E+09 | 1601.58 | 18-FEB-14:30 | 19.50 | 7.87 |
March | 0.121449E+10 | 5163.53 | 27-MAR-12:50 | -2.8 | -2.8 | 0.100387E+10 | 2113.20 | 15-MAR-15:09 | -2.8 | -2.8 |
April | 0.124545E+10 | 5145.11 | 22-APR-08:20 | 0.00 | -0.2 | 0.967385E+09 | 1864.64 | 21-APR-13:39 | 0.00 | -0.2 |
May | 0.999955E+09 | 6617.48 | 18-MAY-14:30 | 23.50 | 11.45 | 0.152684E+10 | 2246.80 | 10-MAY-15:20 | 23.50 | 11.45 |
June | 0.147571E+11 | 52334.32 | 15-JUN-17:06 | 31.63 | 14.49 | 0.191565E+10 | 2247.08 | 26-JUN-14:30 | 38.55 | 15.43 |
July | 0.148526E+11 | 55160.33 | 23-JUL-12:02 | 32.33 | 15.99 | 0.184790E+10 | 2247.00 | 15-JUL-15:20 | 32.33 | 15.99 |
August | 0.151559E+11 | 51553.74 | 10-AUG-17:06 | 31.83 | 14.52 | 0.199027E+10 | 2247.08 | 16-AUG-14:20 | 36.67 | 16.29 |
September | 0.783677E+10 | 51715.78 | 04-SEP-13:33 | 29.40 | 13.36 | 0.177274E+10 | 2246.89 | 01-SEP-13:50 | 29.40 | 13.36 |
October | 0.151782E+10 | 6568.20 | 11-OCT-14:10 | 26.83 | 9.68 | 0.119320E+10 | 2246.80 | 11-OCT-12:20 | 26.83 | 9.68 |
November | 0.142281E+10 | 5279.90 | 21-NOV-12:00 | -2.0 | -2.0 | 0.860880E+09 | 1798.05 | 07-NOV-14:00 | -2.0 | -2.0 |
December | 0.101348E+10 | 4972.17 | 06-DEC-10:50 | -2.0 | -3.7 | 0.773414E+09 | 1556.45 | 02-DEC-15:09 | -2.0 | -3.7 |
Annual Sum or Average | 0.630454E+11 | 0.153875E+11 | ||||||||
Minimum of Months | 0.999955E+09 | 4972.17 | -7.0 | -7.4 | 0.724578E+09 | 1556.45 | -2.8 | -3.7 | ||
Maximum of Months | 0.151559E+11 | 55160.33 | 32.33 | 15.99 | 0.199027E+10 | 2247.08 | 38.55 | 16.29 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.50 | -1.8 | 0.934502E+09 | 1891.48 | 24-JAN-14:00 | 17.00 | 6.48 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -5.3 | -5.3 | 0.819337E+09 | 1991.69 | 18-FEB-14:39 | 19.33 | 7.91 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 | -1.1 | 0.126424E+10 | 3213.63 | 15-MAR-14:39 | 20.33 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 | 2.10 | 0.127785E+10 | 2702.52 | 21-APR-13:50 | 15.17 | 5.71 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 | 4.75 | 0.267077E+10 | 4657.73 | 31-MAY-14:00 | 28.00 | 14.63 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 | 11.26 | 0.527264E+10 | 9097.65 | 26-JUN-13:39 | 37.33 | 15.29 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 | 10.91 | 0.530901E+10 | 8894.76 | 17-JUL-13:09 | 35.83 | 14.79 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 | 15.43 | 0.557548E+10 | 9060.41 | 16-AUG-14:20 | 36.67 | 16.29 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 | 10.64 | 0.426308E+10 | 7402.84 | 09-SEP-13:09 | 32.43 | 12.96 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 | 8.03 | 0.198094E+10 | 4411.19 | 11-OCT-14:50 | 26.17 | 9.50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 | -5.7 | 0.102712E+10 | 2406.00 | 09-NOV-11:00 | 20.00 | 9.32 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 2.77 | -0.5 | 0.833202E+09 | 1898.41 | 04-DEC-14:39 | 19.33 | 6.32 |
Annual Sum or Average | 0.00 | 0.312282E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -5.7 | -5.7 | 0.819337E+09 | 1891.48 | 15.17 | 5.71 | ||
Maximum of Months | 0.00 | 0.00 | 22.27 | 15.43 | 0.557548E+10 | 9097.65 | 37.33 | 16.29 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.455321E+10 | 29589.79 | 05-JAN-06:01 | -17.0 |
February | 0.489032E+10 | 29875.31 | 06-FEB-06:12 | -10.0 |
March | 0.387875E+10 | 29495.22 | 23-MAR-05:01 | 4.00 |
April | 0.273153E+10 | 29690.40 | 04-APR-05:12 | -2.3 |
May | 0.590412E+09 | 29419.85 | 03-MAY-05:01 | 1.17 |
June | 18074887.60 | 4804.22 | 29-JUN-05:40 | 18.50 |
July | 7262514.25 | 2821.41 | 18-JUL-06:05 | 22.33 |
August | 18955839.96 | 7000.34 | 18-AUG-06:00 | 18.00 |
September | 70217444.45 | 5088.36 | 22-SEP-06:10 | -1.4 |
October | 0.162811E+10 | 29451.78 | 31-OCT-05:01 | -8.2 |
November | 0.298818E+10 | 29772.66 | 30-NOV-06:12 | -12.0 |
December | 0.577924E+10 | 29982.81 | 23-DEC-06:22 | -22.1 |
Annual Sum or Average | 0.271543E+11 | |||
Minimum of Months | 7262514.25 | 2821.41 | -22.1 | |
Maximum of Months | 0.577924E+10 | 29982.81 | 22.33 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167192E+11 | 104356.54 | 05-JAN-03:22 | -16.0 |
February | 0.188952E+11 | 104364.48 | 07-FEB-00:02 | -8.0 |
March | 0.118806E+11 | 104351.48 | 18-MAR-20:22 | -7.8 |
April | 0.800690E+10 | 102954.76 | 15-APR-04:52 | -5.0 |
May | 0.119524E+10 | 72259.58 | 03-MAY-05:01 | 1.17 |
June | 0.116854E+09 | 2203.66 | 16-JUN-06:50 | 15.42 |
July | 98873882.93 | 2259.52 | 29-JUL-07:00 | 18.00 |
August | 0.143943E+09 | 2326.05 | 24-AUG-07:00 | 15.00 |
September | 0.196575E+09 | 2346.76 | 22-SEP-07:00 | 0.00 |
October | 0.482807E+10 | 102809.51 | 31-OCT-22:22 | -6.8 |
November | 0.101163E+11 | 104327.82 | 29-NOV-21:22 | -14.5 |
December | 0.253101E+11 | 108326.08 | 23-DEC-06:41 | -22.2 |
Annual Sum or Average | 0.975079E+11 | |||
Minimum of Months | 98873882.93 | 2203.66 | -22.2 | |
Maximum of Months | 0.253101E+11 | 108326.08 | 18.00 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.431690E+11 | 89776.58 | 05-JAN-19:51 | -17.0 |
February | 0.598174E+11 | 122759.45 | 12-FEB-05:33 | -19.3 |
March | 0.282737E+11 | 134965.62 | 19-MAR-06:51 | -15.6 |
April | 0.145419E+11 | 64540.50 | 17-APR-04:53 | -8.0 |
May | 5894895.00 | 2883.69 | 03-MAY-03:20 | 2.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.100175E+11 | 73191.99 | 31-OCT-24:00 | -5.8 |
November | 0.249919E+11 | 112795.38 | 30-NOV-05:51 | -12.0 |
December | 0.936664E+11 | 150913.11 | 21-DEC-23:00 | -18.0 |
Annual Sum or Average | 0.274484E+12 | |||
Minimum of Months | 0.00 | 0.00 | -19.3 | |
Maximum of Months | 0.936664E+11 | 150913.11 | 22.27 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187084E+10 | 1578.50 | 02-JAN-16:30 | 0.248944E+10 | 1853.89 | 02-JAN-08:09 |
February | 0.168930E+10 | 1578.50 | 04-FEB-16:00 | 0.226834E+10 | 1853.89 | 01-FEB-08:09 |
March | 0.188105E+10 | 1578.50 | 18-MAR-07:10 | 0.258391E+10 | 1853.89 | 01-MAR-08:09 |
April | 0.173944E+10 | 1520.62 | 01-APR-07:10 | 0.244723E+10 | 1853.89 | 01-APR-07:10 |
May | 0.177419E+10 | 1404.87 | 09-MAY-08:39 | 0.253668E+10 | 1853.89 | 01-MAY-07:10 |
June | 0.174155E+10 | 1404.87 | 23-JUN-08:30 | 0.249447E+10 | 1853.89 | 01-JUN-07:10 |
July | 0.173975E+10 | 1404.87 | 01-JUL-07:10 | 0.248944E+10 | 1853.89 | 01-JUL-07:10 |
August | 0.182645E+10 | 1404.87 | 21-AUG-07:19 | 0.258391E+10 | 1853.89 | 01-AUG-07:10 |
September | 0.175401E+10 | 1462.75 | 23-SEP-07:10 | 0.244723E+10 | 1853.89 | 01-SEP-07:10 |
October | 0.181695E+10 | 1578.50 | 23-OCT-07:10 | 0.248944E+10 | 1853.89 | 02-OCT-07:10 |
November | 0.179340E+10 | 1578.50 | 01-NOV-07:10 | 0.239999E+10 | 1853.89 | 01-NOV-07:10 |
December | 0.187130E+10 | 1578.50 | 01-DEC-16:19 | 0.248944E+10 | 1853.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.214982E+11 | 0.297195E+11 | ||||
Minimum of Months | 0.168930E+10 | 1404.87 | 0.226834E+10 | 1853.89 | ||
Maximum of Months | 0.188105E+10 | 1578.50 | 0.258391E+10 | 1853.89 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.126887E+11 | 12111.30 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.113009E+11 | 12111.30 | 01-FEB-15:50 | 0.00 | 0.00 |
March | 0.118324E+11 | 12111.30 | 02-MAR-15:50 | 0.00 | 0.00 |
April | 0.101273E+11 | 11102.03 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.957441E+10 | 11102.03 | 09-MAY-08:09 | 0.00 | 0.00 |
June | 0.982437E+10 | 10686.44 | 08-JUN-07:10 | 0.00 | 0.00 |
July | 0.940336E+10 | 11102.03 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.108736E+11 | 11102.03 | 05-AUG-08:09 | 0.00 | 0.00 |
September | 0.105855E+11 | 12111.30 | 16-SEP-08:09 | 0.00 | 0.00 |
October | 0.117334E+11 | 12111.30 | 04-OCT-08:09 | 0.00 | 0.00 |
November | 0.120155E+11 | 12111.30 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.127159E+11 | 12111.30 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.132675E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.940336E+10 | 10686.44 | 0.00 | 0.00 | |
Maximum of Months | 0.127159E+11 | 12111.30 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.158183E+11 | 17006.82 | 02-JAN-15:50 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.137110E+11 | 17006.82 | 02-FEB-15:50 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.136447E+11 | 15006.02 | 02-MAR-16:49 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.117071E+11 | 14172.35 | 03-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.115375E+11 | 12505.01 | 16-MAY-07:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.113399E+11 | 11337.88 | 23-JUN-08:30 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.112493E+11 | 12505.01 | 01-JUL-07:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.122642E+11 | 12505.01 | 28-AUG-15:00 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.121323E+11 | 13755.52 | 23-SEP-15:00 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.135730E+11 | 15006.02 | 12-OCT-07:10 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.146786E+11 | 17006.82 | 06-NOV-15:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.157524E+11 | 17006.82 | 01-DEC-14:00 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.157408E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.112493E+11 | 11337.88 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.158183E+11 | 17006.82 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.187084E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206650E+10 |
February | 0.127628E+10 | 0.168930E+10 | 0.226834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261555E+10 |
March | 0.149825E+10 | 0.188105E+10 | 0.258391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2143.03 | 0.258678E+10 |
April | 0.138726E+10 | 0.173944E+10 | 0.244723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232562E+10 |
May | 0.144276E+10 | 0.177419E+10 | 0.253668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23633001.99 | 0.134952E+10 |
June | 0.144276E+10 | 0.174155E+10 | 0.249447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354346E+09 | 0.467367E+09 |
July | 0.138726E+10 | 0.173975E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310044E+09 | 0.450338E+09 |
August | 0.149825E+10 | 0.182645E+10 | 0.258391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294239E+09 | 0.525596E+09 |
September | 0.138726E+10 | 0.175401E+10 | 0.244723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124682E+09 | 0.852057E+09 |
October | 0.138726E+10 | 0.181695E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3141479.64 | 0.213112E+10 |
November | 0.133177E+10 | 0.179340E+10 | 0.239999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32321.49 | 0.216679E+10 |
December | 0.138726E+10 | 0.187130E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340857E+10 |
Annual Sum or Average | 0.168137E+11 | 0.214982E+11 | 0.297195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111012E+10 | 0.209458E+11 |
Minimum of Months | 0.127628E+10 | 0.168930E+10 | 0.226834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450338E+09 |
Maximum of Months | 0.149825E+10 | 0.188105E+10 | 0.258391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354346E+09 | 0.340857E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.126887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501671E+10 |
February | 0.300332E+10 | 0.113009E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812240E+10 |
March | 0.352563E+10 | 0.118324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.859051E+10 |
April | 0.326447E+10 | 0.101273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.828033E+10 |
May | 0.339505E+10 | 0.957441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7470953.11 | 0.485846E+10 |
June | 0.339505E+10 | 0.982437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555924E+09 | 0.270535E+10 |
July | 0.326447E+10 | 0.940336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588833E+09 | 0.272032E+10 |
August | 0.352563E+10 | 0.108736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366837E+09 | 0.281548E+10 |
September | 0.326447E+10 | 0.105855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124561E+09 | 0.395652E+10 |
October | 0.326447E+10 | 0.117334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39761.95 | 0.681752E+10 |
November | 0.313390E+10 | 0.120155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 645960.22 | 0.577440E+10 |
December | 0.326447E+10 | 0.127159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199007.90 | 0.115144E+11 |
Annual Sum or Average | 0.395654E+11 | 0.132675E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164451E+10 | 0.711724E+11 |
Minimum of Months | 0.300332E+10 | 0.940336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270535E+10 |
Maximum of Months | 0.352563E+10 | 0.127159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588833E+09 | 0.115144E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.158183E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271108E+09 | 0.176738E+11 |
February | 0.690763E+10 | 0.137110E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186565E+09 | 0.299361E+11 |
March | 0.810895E+10 | 0.136447E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262338E+09 | 0.299779E+11 |
April | 0.750829E+10 | 0.117071E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.978760E+09 | 0.272131E+11 |
May | 0.780862E+10 | 0.115375E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.983386E+09 | 0.174420E+11 |
June | 0.780862E+10 | 0.113399E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459773E+09 | 0.157780E+11 |
July | 0.750829E+10 | 0.112493E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136047E+09 | 0.183885E+11 |
August | 0.810895E+10 | 0.122642E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78368551.81 | 0.179340E+11 |
September | 0.750829E+10 | 0.121323E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275392E+09 | 0.211285E+11 |
October | 0.750829E+10 | 0.135730E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67767653.08 | 0.274961E+11 |
November | 0.720796E+10 | 0.146786E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297206E+09 | 0.210109E+11 |
December | 0.750829E+10 | 0.157524E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.751376E+09 | 0.433927E+11 |
Annual Sum or Average | 0.910005E+11 | 0.157408E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474809E+10 | 0.287372E+12 |
Minimum of Months | 0.690763E+10 | 0.112493E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67767653.08 | 0.157780E+11 |
Maximum of Months | 0.810895E+10 | 0.158183E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.983386E+09 | 0.433927E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1578.50 | 02-JAN-16:30 | 1853.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 8498.62 | 05-JAN-18:00 |
February | 1680.92 | 01-FEB-08:09 | 1578.50 | 04-FEB-16:00 | 1853.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 7734.71 | 13-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 1578.50 | 18-MAR-07:10 | 1853.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 | 14-MAR-13:00 | 7745.29 | 27-MAR-16:10 |
April | 1680.92 | 01-APR-07:10 | 1520.62 | 01-APR-07:10 | 1853.89 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 7316.53 | 17-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 1404.87 | 09-MAY-08:39 | 1853.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 893.65 | 31-MAY-16:10 | 5790.73 | 02-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 1404.87 | 23-JUN-08:30 | 1853.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3015.81 | 26-JUN-17:00 | 3000.85 | 09-JUN-06:05 |
July | 1680.92 | 01-JUL-07:10 | 1404.87 | 01-JUL-07:10 | 1853.89 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.63 | 17-JUL-12:00 | 2978.13 | 03-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 1404.87 | 21-AUG-07:19 | 1853.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2517.94 | 16-AUG-17:00 | 2546.26 | 23-AUG-06:10 |
September | 1680.92 | 01-SEP-07:10 | 1462.75 | 23-SEP-07:10 | 1853.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1577.71 | 12-SEP-16:10 | 5854.74 | 21-SEP-16:03 |
October | 1680.92 | 02-OCT-07:10 | 1578.50 | 23-OCT-07:10 | 1853.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.21 | 10-OCT-17:00 | 7481.10 | 30-OCT-16:10 |
November | 1680.92 | 01-NOV-07:10 | 1578.50 | 01-NOV-07:10 | 1853.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.80 | 05-NOV-12:30 | 7837.12 | 29-NOV-18:00 |
December | 1680.92 | 01-DEC-08:09 | 1578.50 | 01-DEC-16:19 | 1853.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 12794.62 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1404.87 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2546.26 | |||||
Maximum of Months | 1680.92 | 1578.50 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 3015.81 | 12794.62 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 12111.30 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 7912.74 | 07-JAN-08:00 |
February | 3955.50 | 01-FEB-08:09 | 12111.30 | 01-FEB-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 11585.03 | 11-FEB-16:10 |
March | 3955.50 | 01-MAR-08:09 | 12111.30 | 02-MAR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 21632.36 | 19-MAR-06:51 |
April | 3955.50 | 01-APR-07:10 | 11102.03 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 15543.06 | 14-APR-07:00 |
May | 3955.50 | 01-MAY-07:10 | 11102.03 | 09-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.71 | 31-MAY-16:00 | 8625.39 | 18-MAY-16:55 |
June | 3955.50 | 01-JUN-07:10 | 10686.44 | 08-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3882.11 | 06-JUN-16:40 | 6446.16 | 20-JUN-16:55 |
July | 3955.50 | 01-JUL-07:10 | 11102.03 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3796.88 | 15-JUL-15:10 | 4929.62 | 03-JUL-02:55 |
August | 3955.50 | 01-AUG-07:10 | 11102.03 | 05-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4031.58 | 02-AUG-16:00 | 6122.31 | 27-AUG-18:00 |
September | 3955.50 | 01-SEP-07:10 | 12111.30 | 16-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2015.20 | 09-SEP-15:10 | 12017.36 | 21-SEP-15:05 |
October | 3955.50 | 02-OCT-07:10 | 12111.30 | 04-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.40 | 11-OCT-14:00 | 11846.25 | 03-OCT-15:05 |
November | 3955.50 | 01-NOV-07:10 | 12111.30 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.39 | 05-NOV-15:00 | 13380.04 | 01-NOV-07:00 |
December | 3955.50 | 01-DEC-08:09 | 12111.30 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.06 | 01-DEC-14:00 | 21146.20 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 10686.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4929.62 | ||||
Maximum of Months | 3955.50 | 12111.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4031.58 | 21632.36 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 17006.82 | 02-JAN-15:50 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5497.36 | 19-JAN-14:00 | 33332.30 | 07-JAN-12:00 |
February | 9097.65 | 01-FEB-08:09 | 17006.82 | 02-FEB-15:50 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6083.40 | 18-FEB-14:00 | 58169.25 | 11-FEB-15:00 |
March | 9097.65 | 01-MAR-08:09 | 15006.02 | 02-MAR-16:49 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5999.01 | 31-MAR-14:00 | 85245.96 | 19-MAR-06:52 |
April | 9097.65 | 01-APR-07:10 | 14172.35 | 03-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12095.00 | 07-APR-16:00 | 52159.29 | 14-APR-07:10 |
May | 9097.65 | 01-MAY-07:10 | 12505.01 | 16-MAY-07:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9154.54 | 04-MAY-15:00 | 47980.64 | 26-MAY-11:00 |
June | 9097.65 | 01-JUN-07:10 | 11337.88 | 23-JUN-08:30 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5363.01 | 06-JUN-12:10 | 29473.78 | 20-JUN-16:55 |
July | 9097.65 | 01-JUL-07:10 | 12505.01 | 01-JUL-07:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2435.85 | 16-JUL-12:02 | 26252.24 | 03-JUL-02:55 |
August | 9097.65 | 01-AUG-07:10 | 12505.01 | 28-AUG-15:00 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2389.76 | 02-AUG-12:55 | 31147.57 | 27-AUG-18:00 |
September | 9097.65 | 01-SEP-07:10 | 13755.52 | 23-SEP-15:00 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7891.46 | 26-SEP-12:10 | 56631.12 | 21-SEP-14:50 |
October | 9097.65 | 02-OCT-07:10 | 15006.02 | 12-OCT-07:10 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3916.31 | 11-OCT-14:00 | 47038.39 | 03-OCT-15:00 |
November | 9097.65 | 01-NOV-07:10 | 17006.82 | 06-NOV-15:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6840.21 | 07-NOV-14:00 | 47769.66 | 01-NOV-10:00 |
December | 9097.65 | 01-DEC-08:09 | 17006.82 | 01-DEC-14:00 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18258.78 | 02-DEC-12:00 | 75236.43 | 21-DEC-19:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 11337.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 2389.76 | 26252.24 | |||||
Maximum of Months | 9097.65 | 17006.82 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 18258.78 | 85245.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 375.90 | 11-JAN-15:10 | 1680.92 | 1231.23 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 526.16 |
February | 247.06 | 18-FEB-14:50 | 1680.92 | 1231.23 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.35 |
March | 3289.50 | 15-MAR-16:00 | 1680.92 | 1231.23 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 352.89 |
April | 1971.45 | 21-APR-13:50 | 1680.92 | 1231.23 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.47 |
May | 21801.79 | 09-MAY-17:21 | 0.00 | 3013.46 | 4885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.78 |
June | 25405.16 | 25-JUN-23:01 | 0.00 | 3320.95 | 4396.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.23 |
July | 25741.22 | 02-JUL-23:01 | 0.00 | 2951.96 | 3908.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393.81 |
August | 26233.30 | 13-AUG-23:02 | 0.00 | 2213.97 | 2931.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.51 |
September | 26127.80 | 17-SEP-23:02 | 0.00 | 1844.97 | 2442.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358.49 |
October | 20067.41 | 07-OCT-17:15 | 0.00 | 710.93 | 977.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.05 |
November | 2274.38 | 07-NOV-15:30 | 1680.92 | 1231.23 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.29 |
December | 534.98 | 02-DEC-15:30 | 1680.92 | 1231.23 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 247.06 | 0.00 | 710.93 | 977.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.05 | |
Maximum of Months | 26233.30 | 1680.92 | 3320.95 | 4885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 526.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6036.00 | 14-JAN-16:15 | 7911.00 | 21372.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7354.39 |
February | 5644.30 | 11-FEB-14:00 | 3955.50 | 10092.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4445.18 |
March | 5163.53 | 27-MAR-12:50 | 3955.50 | 6055.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7237.46 |
April | 5145.11 | 22-APR-08:20 | 3955.50 | 11102.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2754.19 |
May | 6617.48 | 18-MAY-14:30 | 3955.50 | 6055.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.51 |
June | 52334.32 | 15-JUN-17:06 | 0.00 | 6530.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2429.65 | 0.00 |
July | 55160.33 | 23-JUL-12:02 | 0.00 | 2849.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.40 | 0.00 |
August | 51553.74 | 10-AUG-17:06 | 0.00 | 7124.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1822.15 | 0.00 |
September | 51715.78 | 04-SEP-13:33 | 0.00 | 3205.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 624.58 | 0.00 |
October | 6568.20 | 11-OCT-14:10 | 3955.50 | 10092.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.36 | 0.00 |
November | 5279.90 | 21-NOV-12:00 | 3955.50 | 8074.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.40 |
December | 4972.17 | 06-DEC-10:50 | 3955.50 | 9083.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 815.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4972.17 | 0.00 | 2849.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 55160.33 | 7911.00 | 21372.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2429.65 | 7354.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 8003.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2798.87 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 8003.21 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9434.83 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8437.06 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4079.00 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 4001.60 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5875.23 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4324.00 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9729.51 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11382.46 |
September | 0.00 | 01-SEP-00:05 | 0.00 | 4001.60 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6374.81 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2000.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10158.33 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28831.41 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 8003.21 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9580.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 2000.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2798.87 | |
Maximum of Months | 0.00 | 0.00 | 8003.21 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28831.41 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.593013E+11 | 51073.28 | 05-JAN-16:49 | 0.847272E+11 | 165507.93 | 05-JAN-06:10 |
February | 0.527119E+11 | 47540.39 | 06-FEB-15:50 | 0.108984E+12 | 209848.56 | 12-FEB-05:30 |
March | 0.553267E+11 | 43622.83 | 20-MAR-08:09 | 0.576890E+11 | 238128.32 | 19-MAR-07:10 |
April | 0.485013E+11 | 43226.85 | 03-APR-08:09 | 0.325882E+11 | 143412.54 | 17-APR-05:10 |
May | 0.476025E+11 | 39826.97 | 16-MAY-07:10 | 0.146414E+10 | 37266.84 | 02-MAY-05:10 |
June | 0.543396E+11 | 54146.90 | 26-JUN-14:00 | 5055670.82 | 3328.19 | 29-JUN-05:40 |
July | 0.541598E+11 | 50218.74 | 01-JUL-14:00 | 315185.30 | 525.31 | 17-JUL-05:19 |
August | 0.579744E+11 | 54326.33 | 16-AUG-14:09 | 3459022.08 | 4817.20 | 18-AUG-05:00 |
September | 0.527926E+11 | 48710.69 | 08-SEP-15:00 | 23962433.85 | 5975.08 | 22-SEP-06:10 |
October | 0.536891E+11 | 44515.27 | 11-OCT-14:00 | 0.220701E+11 | 128834.17 | 31-OCT-23:30 |
November | 0.554454E+11 | 50960.60 | 28-NOV-16:49 | 0.502639E+11 | 204816.27 | 30-NOV-06:10 |
December | 0.601939E+11 | 51629.32 | 21-DEC-16:49 | 0.162757E+12 | 288983.99 | 21-DEC-17:00 |
Annual Sum or Average | 0.652039E+12 | 0.520577E+12 | ||||
Minimum of Months | 0.476025E+11 | 39826.97 | 315185.30 | 525.31 | ||
Maximum of Months | 0.601939E+11 | 54326.33 | 0.162757E+12 | 288983.99 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.303778E+11 | 0.980944E+10 | 0.113456E+11 | 0.00 | 0.549208E+10 | 0.00 | 0.00 | 12.36 | 0.00 | 0.00 | 0.00 | 0.227641E+10 | 0.00 |
February | 0.267012E+11 | 0.816943E+10 | 0.104160E+11 | 0.00 | 0.534423E+10 | 0.00 | 0.00 | 17.20 | 0.00 | 0.00 | 0.00 | 0.208113E+10 | 0.00 |
March | 0.273582E+11 | 0.806982E+10 | 0.121559E+11 | 0.00 | 0.538272E+10 | 0.00 | 0.00 | 21353418.01 | 0.00 | 0.00 | 0.00 | 0.233875E+10 | 0.00 |
April | 0.235739E+11 | 0.682171E+10 | 0.113034E+11 | 0.00 | 0.460938E+10 | 0.00 | 0.00 | 2226352.00 | 0.00 | 0.00 | 0.00 | 0.219068E+10 | 0.00 |
May | 0.228861E+11 | 0.625215E+10 | 0.117471E+11 | 0.00 | 0.411485E+10 | 0.00 | 0.00 | 0.389303E+09 | 0.00 | 0.00 | 0.00 | 0.221305E+10 | 0.00 |
June | 0.229059E+11 | 0.565694E+10 | 0.117048E+11 | 0.00 | 0.565153E+10 | 0.00 | 0.00 | 0.630771E+10 | 0.00 | 0.00 | 0.00 | 0.211273E+10 | 0.00 |
July | 0.223924E+11 | 0.599199E+10 | 0.113456E+11 | 0.00 | 0.588443E+10 | 0.00 | 0.00 | 0.645076E+10 | 0.00 | 0.00 | 0.00 | 0.209468E+10 | 0.00 |
August | 0.249642E+11 | 0.666974E+10 | 0.121485E+11 | 0.00 | 0.580654E+10 | 0.00 | 0.00 | 0.624911E+10 | 0.00 | 0.00 | 0.00 | 0.213635E+10 | 0.00 |
September | 0.244718E+11 | 0.737923E+10 | 0.112960E+11 | 0.00 | 0.444548E+10 | 0.00 | 0.00 | 0.314769E+10 | 0.00 | 0.00 | 0.00 | 0.205241E+10 | 0.00 |
October | 0.271234E+11 | 0.864410E+10 | 0.113530E+11 | 0.00 | 0.430778E+10 | 0.00 | 0.00 | 0.121004E+09 | 0.00 | 0.00 | 0.00 | 0.213986E+10 | 0.00 |
November | 0.284875E+11 | 0.923622E+10 | 0.109019E+11 | 0.00 | 0.470049E+10 | 0.00 | 0.00 | 3263581.46 | 0.00 | 0.00 | 0.00 | 0.211604E+10 | 0.00 |
December | 0.303396E+11 | 0.100526E+11 | 0.113456E+11 | 0.00 | 0.621427E+10 | 0.00 | 0.00 | 21671.83 | 0.00 | 0.00 | 0.00 | 0.224191E+10 | 0.00 |
Annual Sum or Average | 0.311582E+12 | 0.927533E+11 | 0.137063E+12 | 0.00 | 0.619538E+11 | 0.00 | 0.00 | 0.226924E+11 | 0.00 | 0.00 | 0.00 | 0.259940E+11 | 0.00 |
Minimum of Months | 0.223924E+11 | 0.565694E+10 | 0.104160E+11 | 0.00 | 0.411485E+10 | 0.00 | 0.00 | 12.36 | 0.00 | 0.00 | 0.00 | 0.205241E+10 | 0.00 |
Maximum of Months | 0.303778E+11 | 0.100526E+11 | 0.121559E+11 | 0.00 | 0.621427E+10 | 0.00 | 0.00 | 0.645076E+10 | 0.00 | 0.00 | 0.00 | 0.233875E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.847272E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.108984E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.576890E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.325882E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.146414E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 5055670.82 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 315185.30 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 3459022.08 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 23962433.85 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.220701E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.502639E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.162757E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.520577E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 315185.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.162757E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 30696.62 | 04-JAN-15:50 | 6986.42 | 01-JAN-06:10 | 10054.01 | 02-JAN-08:09 | 0.00 | 5507.83 | 05-JAN-17:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 30638.74 | 06-FEB-15:50 | 6986.42 | 01-FEB-06:10 | 10054.01 | 01-FEB-08:09 | 0.00 | 5421.18 | 06-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 27688.52 | 18-MAR-08:09 | 6986.42 | 01-MAR-06:10 | 10054.01 | 01-MAR-08:09 | 0.00 | 5107.52 | 04-MAR-17:40 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 26679.24 | 03-APR-08:09 | 6986.42 | 01-APR-05:10 | 10054.01 | 01-APR-07:10 | 0.00 | 5111.15 | 17-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 24596.32 | 16-MAY-07:10 | 6986.42 | 01-MAY-18:49 | 10054.01 | 01-MAY-07:10 | 0.00 | 4181.89 | 02-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 22835.50 | 23-JUN-08:30 | 6986.42 | 01-JUN-19:19 | 10054.01 | 01-JUN-07:10 | 0.00 | 7791.28 | 26-JUN-15:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 24596.32 | 01-JUL-07:10 | 6986.42 | 01-JUL-19:30 | 10054.01 | 01-JUL-07:10 | 0.00 | 6896.99 | 15-JUL-15:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 23786.89 | 05-AUG-08:09 | 6986.42 | 01-AUG-19:10 | 10054.01 | 01-AUG-07:10 | 0.00 | 7325.58 | 16-AUG-14:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 26271.28 | 16-SEP-08:09 | 6986.42 | 01-SEP-05:10 | 10054.01 | 01-SEP-07:10 | 0.00 | 6249.15 | 02-SEP-13:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 27804.27 | 30-OCT-08:09 | 6986.42 | 01-OCT-05:10 | 10054.01 | 02-OCT-07:10 | 0.00 | 5209.43 | 31-OCT-16:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 30638.74 | 09-NOV-15:30 | 6986.42 | 01-NOV-05:10 | 10054.01 | 01-NOV-07:10 | 0.00 | 5335.48 | 30-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 30696.62 | 26-DEC-15:00 | 6986.42 | 01-DEC-06:10 | 10054.01 | 01-DEC-08:09 | 0.00 | 6312.51 | 21-DEC-17:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 22835.50 | 6986.42 | 10054.01 | 0.00 | 4181.89 | 0.00 | 0.00 | |||||
Maximum of Months | 30696.62 | 6986.42 | 10054.01 | 0.00 | 7791.28 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.02 | 20-JAN-14:50 | 0.00 | 0.00 | 0.00 | 2592.75 | 31-JAN-12:09 | 0.00 |
February | 0.03 | 18-FEB-14:20 | 0.00 | 0.00 | 0.00 | 2602.82 | 13-FEB-12:00 | 0.00 |
March | 840.25 | 14-MAR-12:00 | 0.00 | 0.00 | 0.00 | 2587.34 | 01-MAR-12:00 | 0.00 |
April | 283.79 | 20-APR-12:00 | 0.00 | 0.00 | 0.00 | 2468.59 | 01-APR-11:39 | 0.00 |
May | 4164.10 | 31-MAY-15:00 | 0.00 | 0.00 | 0.00 | 2258.04 | 01-MAY-11:39 | 0.00 |
June | 16278.44 | 26-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1915.67 | 03-JUN-11:00 | 0.00 |
July | 12529.61 | 15-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1796.22 | 05-JUL-11:39 | 0.00 |
August | 13952.56 | 16-AUG-14:09 | 0.00 | 0.00 | 0.00 | 1787.34 | 30-AUG-11:39 | 0.00 |
September | 9112.50 | 12-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1799.02 | 30-SEP-11:09 | 0.00 |
October | 4007.28 | 11-OCT-13:00 | 0.00 | 0.00 | 0.00 | 2005.20 | 31-OCT-11:00 | 0.00 |
November | 441.44 | 07-NOV-14:00 | 0.00 | 0.00 | 0.00 | 2271.50 | 30-NOV-12:00 | 0.00 |
December | 35.70 | 02-DEC-14:00 | 0.00 | 0.00 | 0.00 | 2475.96 | 30-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.02 | 0.00 | 0.00 | 0.00 | 1787.34 | 0.00 | ||
Maximum of Months | 16278.44 | 0.00 | 0.00 | 0.00 | 2602.82 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 51073.28 | 05-JAN-16:49 | 27270.96 | 10054.01 | 6986.42 | 0.00 | 5143.45 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 47540.39 | 06-FEB-15:50 | 30638.74 | 10054.01 | 0.00 | 0.00 | 4841.18 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 43622.83 | 20-MAR-08:09 | 27688.52 | 10054.01 | 0.00 | 0.00 | 4186.83 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 43226.85 | 03-APR-08:09 | 26679.24 | 10054.01 | 0.00 | 0.00 | 4861.91 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 39826.97 | 16-MAY-07:10 | 24596.32 | 10054.01 | 0.00 | 0.00 | 3943.85 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 54146.90 | 26-JUN-14:00 | 19226.08 | 10054.01 | 0.00 | 0.00 | 7540.25 | 0.00 | 0.00 | 15564.04 | 0.00 |
July | 50218.74 | 01-JUL-14:00 | 21244.63 | 10054.01 | 0.00 | 0.00 | 6563.93 | 0.00 | 0.00 | 10595.90 | 0.00 |
August | 54326.33 | 16-AUG-14:09 | 21244.63 | 10054.01 | 0.00 | 0.00 | 7325.58 | 0.00 | 0.00 | 13952.56 | 0.00 |
September | 48710.69 | 08-SEP-15:00 | 24480.57 | 10054.01 | 0.00 | 0.00 | 6249.15 | 0.00 | 0.00 | 6327.52 | 0.00 |
October | 44515.27 | 11-OCT-14:00 | 25088.37 | 10054.01 | 0.00 | 0.00 | 3943.85 | 0.00 | 0.00 | 3663.01 | 0.00 |
November | 50960.60 | 28-NOV-16:49 | 27270.96 | 10054.01 | 6986.42 | 0.00 | 5036.81 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 51629.32 | 21-DEC-16:49 | 27270.96 | 10054.01 | 6986.42 | 0.00 | 5701.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 39826.97 | 19226.08 | 10054.01 | 0.00 | 0.00 | 3943.85 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 54326.33 | 30638.74 | 10054.01 | 6986.42 | 0.00 | 7540.25 | 0.00 | 0.00 | 15564.04 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 165507.93 | 05-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 209848.56 | 12-FEB-05:30 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 238128.32 | 19-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 143412.54 | 17-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 37266.84 | 02-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 3328.19 | 29-JUN-05:40 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 525.31 | 17-JUL-05:19 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 4817.20 | 18-AUG-05:00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 5975.08 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 128834.17 | 31-OCT-23:30 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 204816.27 | 30-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 288983.99 | 21-DEC-17:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 525.31 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 288983.99 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.67 | 18.32 | 8.50 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 |
February | 22.17 | 16.52 | 8.33 | 17.25 | 0.00 | 17.25 | 0.00 | 17.25 |
March | 12.17 | 17.92 | 8.50 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 |
April | 9.00 | 18.52 | 6.67 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
May | 1.50 | 19.91 | 1.50 | 19.91 | 0.17 | 20.15 | 0.00 | 20.15 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 24.70 | 1.00 | 24.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 24.65 | 1.17 | 24.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 24.66 | 1.33 | 24.65 |
September | 0.17 | 20.49 | 0.17 | 20.49 | 9.00 | 24.43 | 0.17 | 24.43 |
October | 3.33 | 19.40 | 3.17 | 19.52 | 0.00 | 19.52 | 0.00 | 19.52 |
November | 8.50 | 18.81 | 7.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
December | 30.00 | 16.14 | 8.67 | 16.87 | 0.00 | 16.87 | 0.00 | 16.87 |
Annual Sum or Average | 98.50 | 17.33 | 52.50 | 18.07 | 70.83 | 20.18 | 3.67 | 20.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.87 | 0.00 | 16.87 |
Maximum of Months | 30.00 | 20.49 | 8.67 | 20.49 | 20.83 | 24.70 | 1.33 | 24.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 74.83 | 14.45 | 4.33 | 14.46 | 0.00 | 14.46 | 0.00 | 14.46 |
February | 73.67 | 14.28 | 4.17 | 14.28 | 0.00 | 14.28 | 0.00 | 14.28 |
March | 57.83 | 14.47 | 4.33 | 14.47 | 0.00 | 14.47 | 0.00 | 14.47 |
April | 39.17 | 14.55 | 2.50 | 14.55 | 0.00 | 14.55 | 0.00 | 14.55 |
May | 4.33 | 14.86 | 0.50 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.57 | 0.00 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.58 | 0.00 | 27.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.51 | 0.00 | 27.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.52 | 0.00 | 27.52 |
October | 19.67 | 14.49 | 1.33 | 14.49 | 0.00 | 14.49 | 0.00 | 14.49 |
November | 45.00 | 14.52 | 3.17 | 14.52 | 0.00 | 14.52 | 0.00 | 14.52 |
December | 87.33 | 14.18 | 4.50 | 14.19 | 0.00 | 14.19 | 0.00 | 14.19 |
Annual Sum or Average | 401.83 | 14.39 | 24.83 | 14.39 | 34.67 | 15.38 | 0.00 | 15.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.19 | 0.00 | 14.19 |
Maximum of Months | 87.33 | 14.86 | 4.50 | 14.86 | 13.50 | 27.58 | 0.00 | 27.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.67 | 9.13 | 0.00 | 9.13 | 0.00 | 9.13 | 0.00 | 9.13 |
Annual Sum or Average | 2.67 | 9.13 | 0.00 | 9.13 | 0.00 | 9.13 | 0.00 | 9.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 9.13 | 0.00 | 9.13 | 0.00 | 9.13 | 0.00 | 9.13 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.37 | 262.00 | 21.25 | 262.00 | 21.21 |
February | 276.00 | 21.23 | 254.67 | 21.15 | 254.67 | 21.13 |
March | 324.00 | 21.73 | 235.50 | 21.47 | 235.50 | 21.36 |
April | 300.00 | 21.88 | 190.83 | 21.59 | 190.83 | 21.46 |
May | 292.83 | 23.14 | 49.33 | 22.87 | 47.33 | 22.66 |
June | 39.50 | 23.74 | 185.17 | 23.88 | 4.83 | 23.88 |
July | 41.50 | 23.82 | 220.17 | 23.89 | 26.33 | 23.89 |
August | 29.17 | 23.77 | 218.83 | 23.89 | 9.00 | 23.89 |
September | 100.17 | 23.59 | 81.50 | 23.68 | 3.00 | 23.64 |
October | 296.50 | 22.59 | 106.17 | 22.20 | 106.17 | 21.97 |
November | 288.00 | 21.72 | 199.50 | 21.47 | 199.50 | 21.36 |
December | 300.00 | 21.30 | 270.33 | 21.20 | 270.33 | 21.17 |
Annual Sum or Average | 2587.67 | 22.02 | 2274.00 | 22.00 | 1609.50 | 21.79 |
Minimum of Months | 29.17 | 21.23 | 49.33 | 21.15 | 3.00 | 21.13 |
Maximum of Months | 324.00 | 23.82 | 270.33 | 23.89 | 270.33 | 23.89 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 17.09 | 295.50 | 17.05 | 295.50 | 17.04 |
February | 276.00 | 16.87 | 272.17 | 16.84 | 272.17 | 16.83 |
March | 318.83 | 18.09 | 264.83 | 17.63 | 264.83 | 17.46 |
April | 300.00 | 18.62 | 231.17 | 18.12 | 231.17 | 17.92 |
May | 192.33 | 21.47 | 152.67 | 22.13 | 64.17 | 21.58 |
June | 184.50 | 26.54 | 295.83 | 26.55 | 176.17 | 26.59 |
July | 216.00 | 26.64 | 293.50 | 26.60 | 215.33 | 26.61 |
August | 199.00 | 26.64 | 312.50 | 26.57 | 196.33 | 26.60 |
September | 110.67 | 24.80 | 236.00 | 25.83 | 67.33 | 25.83 |
October | 263.67 | 19.91 | 175.50 | 19.46 | 152.33 | 18.99 |
November | 288.00 | 17.90 | 256.67 | 17.62 | 256.67 | 17.52 |
December | 300.00 | 16.72 | 298.17 | 16.71 | 298.17 | 16.70 |
Annual Sum or Average | 2949.00 | 20.14 | 3084.50 | 20.54 | 2490.17 | 20.27 |
Minimum of Months | 110.67 | 16.72 | 152.67 | 16.71 | 64.17 | 16.70 |
Maximum of Months | 318.83 | 26.64 | 312.50 | 26.60 | 298.17 | 26.61 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 11.80 | 300.00 | 11.80 | 300.00 | 11.80 |
February | 276.00 | 11.53 | 276.00 | 11.53 | 276.00 | 11.53 |
March | 324.00 | 13.11 | 324.00 | 13.11 | 324.00 | 13.11 |
April | 300.00 | 13.82 | 300.00 | 13.82 | 300.00 | 13.82 |
May | 302.33 | 19.81 | 166.83 | 19.07 | 164.50 | 18.70 |
June | 244.00 | 29.50 | 286.83 | 29.33 | 227.00 | 29.54 |
July | 279.33 | 29.74 | 300.00 | 29.61 | 279.33 | 29.65 |
August | 266.33 | 29.68 | 324.00 | 29.34 | 266.33 | 29.45 |
September | 196.83 | 26.42 | 210.00 | 26.86 | 134.50 | 27.12 |
October | 300.00 | 17.23 | 242.67 | 16.70 | 242.67 | 16.49 |
November | 288.00 | 12.60 | 288.00 | 12.60 | 288.00 | 12.60 |
December | 300.00 | 11.17 | 300.00 | 11.17 | 300.00 | 11.17 |
Annual Sum or Average | 3376.83 | 18.32 | 3318.33 | 18.40 | 3102.33 | 18.25 |
Minimum of Months | 196.83 | 11.17 | 166.83 | 11.17 | 134.50 | 11.17 |
Maximum of Months | 324.00 | 29.74 | 324.00 | 29.61 | 324.00 | 29.65 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 50.88 | 12.36 | 0.33 | 50.88 | -0.0 | 0.00 | 0.00 | 20-JAN-14:50 | 0.00 | 01-JAN-00:03 | 0.08 | 20-JAN-14:50 | 0.08 | 20-JAN-14:50 | 0.00 | 01-JAN-00:03 | 0.02 | 20-JAN-14:50 | 0.00 | 01-JAN-00:03 |
February | 70.82 | 17.20 | 0.17 | 70.82 | 0.00 | 0.00 | 0.00 | 18-FEB-14:20 | 0.00 | 01-FEB-00:03 | 0.12 | 18-FEB-14:20 | 0.12 | 18-FEB-14:20 | 0.00 | 01-FEB-00:03 | 0.03 | 18-FEB-14:20 | 0.00 | 01-FEB-00:03 |
March | 91425417.15 | 21353418.01 | 18.08 | 91425417.15 | 0.00 | 0.00 | 0.36 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 3649.33 | 14-MAR-13:00 | 3649.33 | 14-MAR-13:00 | 0.00 | 14-MAR-13:00 | 840.25 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 9262356.58 | 2226352.00 | 10.17 | 9262356.58 | -0.0 | 0.00 | 0.12 | 20-APR-13:00 | 0.00 | 01-APR-00:10 | 1190.16 | 20-APR-13:00 | 1190.16 | 20-APR-13:00 | 0.00 | 20-APR-13:10 | 283.79 | 20-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 0.126664E+10 | 0.294898E+09 | 109.57 | 0.126402E+10 | 2616551.12 | 0.00 | 1.00 | 06-MAY-17:21 | 0.00 | 01-MAY-00:05 | 21582.89 | 31-MAY-18:41 | 20768.75 | 16-MAY-17:15 | 2119.16 | 31-MAY-19:21 | 4712.54 | 31-MAY-18:41 | 0.00 | 01-MAY-00:05 |
June | 0.831621E+10 | 0.198240E+10 | 339.69 | 0.797393E+10 | 0.342276E+09 | 0.00 | 1.00 | 01-JUN-17:10 | 0.00 | 01-JUN-00:10 | 23899.53 | 21-JUN-17:15 | 21276.20 | 01-JUN-19:05 | 10157.74 | 20-JUN-18:35 | 5453.05 | 26-JUN-17:42 | 0.00 | 01-JUN-00:10 |
July | 0.860142E+10 | 0.202341E+10 | 336.72 | 0.804141E+10 | 0.560008E+09 | 0.00 | 1.00 | 01-JUL-01:11 | 0.00 | 01-JUL-00:10 | 24524.88 | 31-JUL-17:15 | 21157.78 | 18-JUL-21:03 | 12667.34 | 31-JUL-17:15 | 5279.30 | 31-JUL-17:15 | 0.00 | 01-JUL-00:10 |
August | 0.863778E+10 | 0.203221E+10 | 349.13 | 0.820726E+10 | 0.430518E+09 | 0.00 | 1.00 | 01-AUG-02:35 | 0.00 | 01-AUG-00:10 | 23981.27 | 04-AUG-01:25 | 21390.74 | 08-AUG-18:23 | 12236.03 | 04-AUG-02:33 | 5303.59 | 16-AUG-17:06 | 0.00 | 01-AUG-00:10 |
September | 0.533667E+10 | 0.123017E+10 | 248.86 | 0.529191E+10 | 44755492.75 | 0.00 | 1.00 | 01-SEP-00:05 | 0.00 | 01-SEP-00:10 | 21826.29 | 02-SEP-19:58 | 21432.59 | 02-SEP-19:05 | 3978.04 | 01-SEP-20:45 | 4909.84 | 12-SEP-17:06 | 0.00 | 01-SEP-00:05 |
October | 0.398750E+09 | 91164518.71 | 43.75 | 0.398750E+09 | 0.00 | 0.00 | 1.00 | 07-OCT-17:15 | 0.00 | 01-OCT-00:10 | 20647.12 | 07-OCT-17:15 | 20647.12 | 11-OCT-17:15 | 0.00 | 07-OCT-17:15 | 4503.18 | 07-OCT-17:15 | 0.00 | 01-OCT-00:10 |
November | 13735099.81 | 3263581.46 | 5.33 | 13735099.81 | -0.0 | 0.00 | 0.19 | 07-NOV-15:00 | 0.00 | 01-NOV-00:10 | 1870.72 | 07-NOV-15:00 | 1870.72 | 07-NOV-15:00 | 0.00 | 07-NOV-15:20 | 441.44 | 07-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 89428.49 | 21671.83 | 0.83 | 89428.49 | -0.0 | 0.00 | 0.02 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 | 147.32 | 02-DEC-15:00 | 147.32 | 02-DEC-15:00 | 0.00 | 02-DEC-14:20 | 35.70 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.326720E+11 | 0.768111E+10 | 1462.63 | 0.312918E+11 | 0.138017E+10 | 0.00 | ||||||||||||||
Minimum of Months | 50.88 | 12.36 | 0.17 | 50.88 | -0.0 | 0.00 | 0.00 | 0.00 | 0.08 | 0.08 | 0.00 | 0.02 | 0.00 | |||||||
Maximum of Months | 0.863778E+10 | 0.203221E+10 | 349.13 | 0.820726E+10 | 0.560008E+09 | 0.00 | 1.00 | 0.00 | 24524.88 | 21432.59 | 12667.34 | 5453.05 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.348595E+09 | 94404056.02 | 22.50 | 0.348595E+09 | -0.0 | 0.00 | 0.33 | 31-MAY-14:50 | 0.00 | 01-MAY-00:05 | 9221.42 | 31-MAY-14:50 | 9221.42 | 31-MAY-14:50 | 0.00 | 31-MAY-14:20 | 2481.76 | 31-MAY-14:50 | 0.00 | 01-MAY-00:05 |
June | 0.163248E+11 | 0.432531E+10 | 266.34 | 0.159302E+11 | 0.394592E+09 | 0.00 | 1.00 | 04-JUN-11:45 | 0.00 | 01-JUN-00:10 | 71734.51 | 18-JUN-09:45 | 64202.76 | 15-JUN-19:03 | 23580.48 | 18-JUN-09:05 | 17108.13 | 26-JUN-17:42 | 0.00 | 01-JUN-00:10 |
July | 0.168524E+11 | 0.442735E+10 | 281.24 | 0.163615E+11 | 0.490890E+09 | 0.00 | 1.00 | 01-JUL-13:40 | 0.00 | 01-JUL-00:10 | 73842.44 | 30-JUL-11:05 | 64904.12 | 23-JUL-09:25 | 29275.05 | 30-JUL-15:59 | 16831.08 | 23-JUL-14:02 | 0.00 | 01-JUL-00:10 |
August | 0.161921E+11 | 0.421690E+10 | 261.12 | 0.158830E+11 | 0.309122E+09 | 0.00 | 1.00 | 02-AUG-17:08 | 0.00 | 01-AUG-00:10 | 68352.54 | 03-AUG-17:11 | 64739.96 | 27-AUG-13:15 | 21572.40 | 05-AUG-18:03 | 16699.20 | 16-AUG-17:06 | 0.00 | 01-AUG-00:10 |
September | 0.737181E+10 | 0.191752E+10 | 172.04 | 0.734640E+10 | 25406441.04 | 0.00 | 1.00 | 02-SEP-17:08 | 0.00 | 01-SEP-00:05 | 65123.68 | 03-SEP-12:55 | 64082.61 | 03-SEP-13:51 | 4296.00 | 03-SEP-12:55 | 15063.41 | 04-SEP-13:33 | 0.00 | 01-SEP-00:05 |
October | 0.113506E+09 | 29839345.37 | 8.67 | 0.113506E+09 | -0.0 | 0.00 | 0.34 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 | 9107.88 | 11-OCT-14:00 | 9107.88 | 11-OCT-14:00 | 0.00 | 11-OCT-15:10 | 2411.10 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.572032E+11 | 0.150113E+11 | 1011.91 | 0.559832E+11 | 0.122001E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.168524E+11 | 0.442735E+10 | 281.24 | 0.163615E+11 | 0.490890E+09 | 0.00 | 1.00 | 0.00 | 73842.44 | 64904.12 | 29275.05 | 17108.13 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.82 | 74.62 | 43.20 | 115.47 | 163.31 | 0.00 | 0.00 | 0.00 |
February | 143.05 | 88.90 | 54.15 | 138.26 | 167.24 | 0.00 | 0.00 | 0.00 |
March | 166.75 | 92.07 | 74.68 | 171.81 | 125.45 | 0.00 | 0.00 | 0.00 |
April | 156.29 | 65.92 | 90.37 | 154.60 | 108.23 | 0.00 | 0.00 | 0.00 |
May | 191.60 | 67.52 | 124.09 | 220.04 | 71.79 | 0.00 | 0.00 | 0.00 |
June | 234.63 | 113.00 | 121.63 | 317.47 | 48.18 | 0.00 | 0.00 | 0.00 |
July | 190.84 | 69.80 | 121.04 | 258.27 | 44.53 | 0.00 | 0.00 | 0.00 |
August | 199.72 | 98.81 | 100.91 | 265.06 | 50.87 | 0.00 | 0.00 | 0.00 |
September | 177.31 | 85.22 | 92.09 | 223.52 | 77.17 | 0.00 | 0.00 | 0.00 |
October | 148.27 | 84.59 | 63.68 | 159.00 | 140.38 | 0.00 | 0.00 | 0.00 |
November | 121.85 | 73.91 | 47.94 | 121.73 | 152.17 | 0.00 | 0.00 | 0.00 |
December | 98.52 | 58.19 | 40.34 | 87.26 | 190.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 162.27 | 80.94 | 81.32 | 186.23 | 111.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.52 | 58.19 | 40.34 | 87.26 | 44.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 234.63 | 113.00 | 124.09 | 317.47 | 190.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.82 | 74.62 | 43.20 | 115.47 | 163.31 | 0.00 | 0.00 | 0.00 |
February | 143.05 | 88.90 | 54.15 | 138.26 | 167.24 | 0.00 | 0.00 | 0.00 |
March | 166.75 | 92.07 | 74.68 | 171.81 | 125.45 | 0.00 | 0.00 | 0.00 |
April | 156.29 | 65.92 | 90.37 | 154.60 | 108.23 | 0.00 | 0.00 | 0.00 |
May | 191.60 | 67.52 | 124.09 | 220.04 | 71.79 | 0.00 | 0.00 | 0.00 |
June | 234.63 | 113.00 | 121.63 | 317.47 | 48.18 | 0.00 | 0.00 | 0.00 |
July | 190.84 | 69.80 | 121.04 | 258.27 | 44.53 | 0.00 | 0.00 | 0.00 |
August | 199.72 | 98.81 | 100.91 | 265.06 | 50.87 | 0.00 | 0.00 | 0.00 |
September | 177.31 | 85.22 | 92.09 | 223.52 | 77.17 | 0.00 | 0.00 | 0.00 |
October | 148.27 | 84.59 | 63.68 | 159.00 | 140.38 | 0.00 | 0.00 | 0.00 |
November | 121.85 | 73.91 | 47.94 | 121.73 | 152.17 | 0.00 | 0.00 | 0.00 |
December | 98.52 | 58.19 | 40.34 | 87.26 | 190.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 162.27 | 80.94 | 81.32 | 186.23 | 111.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.52 | 58.19 | 40.34 | 87.26 | 44.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 234.63 | 113.00 | 124.09 | 317.47 | 190.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.66 | 0.00 | 20.66 | 4.44 | 101.81 | 0.00 | 0.00 | 0.00 |
February | 25.96 | 0.00 | 25.96 | 5.47 | 103.71 | 0.00 | 0.00 | 0.00 |
March | 35.34 | 0.00 | 35.34 | 16.92 | 76.53 | 0.00 | 0.00 | 0.00 |
April | 44.39 | 0.27 | 44.11 | 25.81 | 64.15 | 0.00 | 0.00 | 0.00 |
May | 60.67 | 2.04 | 58.63 | 55.10 | 39.72 | 0.00 | 0.00 | 0.00 |
June | 66.36 | 7.27 | 59.09 | 85.24 | 25.47 | 0.00 | 0.00 | 0.00 |
July | 62.98 | 4.17 | 58.80 | 82.15 | 24.20 | 0.00 | 0.00 | 0.00 |
August | 50.24 | 1.37 | 48.86 | 61.11 | 28.89 | 0.00 | 0.00 | 0.00 |
September | 42.06 | 0.03 | 42.03 | 43.97 | 45.10 | 0.00 | 0.00 | 0.00 |
October | 30.10 | 0.00 | 30.10 | 14.66 | 84.48 | 0.00 | 0.00 | 0.00 |
November | 22.85 | 0.00 | 22.85 | 6.72 | 93.34 | 0.00 | 0.00 | 0.00 |
December | 19.33 | 0.00 | 19.33 | 3.71 | 119.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.15 | 1.27 | 38.88 | 33.93 | 67.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.33 | 0.00 | 19.33 | 3.71 | 24.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.36 | 7.27 | 59.09 | 85.24 | 119.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.66 | 0.00 | 20.66 | 4.44 | 101.81 | 0.00 | 0.00 | 0.00 |
February | 25.96 | 0.00 | 25.96 | 5.47 | 103.71 | 0.00 | 0.00 | 0.00 |
March | 35.34 | 0.00 | 35.33 | 16.92 | 76.53 | 0.00 | 0.00 | 0.00 |
April | 44.38 | 0.27 | 44.11 | 25.81 | 64.15 | 0.00 | 0.00 | 0.00 |
May | 60.66 | 2.04 | 58.63 | 55.10 | 39.72 | 0.00 | 0.00 | 0.00 |
June | 66.36 | 7.27 | 59.09 | 85.24 | 25.47 | 0.00 | 0.00 | 0.00 |
July | 62.98 | 4.17 | 58.80 | 82.15 | 24.20 | 0.00 | 0.00 | 0.00 |
August | 50.23 | 1.37 | 48.86 | 61.11 | 28.89 | 0.00 | 0.00 | 0.00 |
September | 42.06 | 0.03 | 42.03 | 43.97 | 45.10 | 0.00 | 0.00 | 0.00 |
October | 30.10 | 0.00 | 30.10 | 14.66 | 84.48 | 0.00 | 0.00 | 0.00 |
November | 22.85 | 0.00 | 22.85 | 6.72 | 93.34 | 0.00 | 0.00 | 0.00 |
December | 19.33 | 0.00 | 19.33 | 3.71 | 119.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.15 | 1.27 | 38.88 | 33.93 | 67.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.33 | 0.00 | 19.33 | 3.71 | 24.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.36 | 7.27 | 59.09 | 85.24 | 119.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.51 | 28.91 | 11.60 | 43.72 | 90.02 | 3.17 | 0.00 | 0.00 |
February | 59.10 | 45.43 | 13.66 | 67.43 | 92.33 | 4.00 | 0.00 | 0.00 |
March | 76.53 | 53.59 | 22.94 | 95.63 | 71.35 | 8.83 | 0.00 | 0.00 |
April | 82.73 | 48.37 | 34.36 | 103.40 | 60.17 | 10.50 | 0.00 | 0.00 |
May | 105.62 | 56.24 | 49.38 | 144.17 | 43.26 | 0.17 | 0.00 | 0.00 |
June | 132.17 | 92.18 | 39.99 | 197.91 | 37.67 | 0.00 | 0.00 | 0.00 |
July | 114.58 | 68.17 | 46.41 | 171.60 | 35.53 | 0.17 | 0.00 | 0.00 |
August | 113.98 | 81.36 | 32.62 | 170.03 | 39.98 | 2.67 | 0.00 | 0.00 |
September | 89.54 | 59.94 | 29.60 | 127.13 | 53.12 | 1.17 | 0.00 | 0.00 |
October | 64.01 | 45.29 | 18.72 | 79.56 | 77.49 | 1.00 | 0.00 | 0.00 |
November | 46.47 | 33.58 | 12.89 | 54.90 | 81.92 | 3.67 | 0.00 | 0.00 |
December | 34.21 | 22.68 | 11.52 | 32.51 | 106.59 | 0.67 | 0.00 | 0.00 |
Annual Sum or Average | 80.04 | 52.98 | 27.06 | 107.51 | 65.65 | 36.00 | 0.00 | 0.00 |
Minimum of Months | 34.21 | 22.68 | 11.52 | 32.51 | 35.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.17 | 92.18 | 49.38 | 197.91 | 106.59 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.51 | 28.91 | 11.60 | 43.72 | 90.02 | 3.17 | 0.00 | 0.00 |
February | 59.10 | 45.43 | 13.66 | 67.43 | 92.33 | 4.00 | 0.00 | 0.00 |
March | 76.53 | 53.59 | 22.94 | 95.63 | 71.35 | 8.83 | 0.00 | 0.00 |
April | 82.73 | 48.37 | 34.36 | 103.40 | 60.17 | 10.50 | 0.00 | 0.00 |
May | 105.62 | 56.24 | 49.38 | 144.17 | 43.26 | 0.17 | 0.00 | 0.00 |
June | 132.17 | 92.18 | 39.99 | 197.91 | 37.67 | 0.00 | 0.00 | 0.00 |
July | 114.58 | 68.17 | 46.41 | 171.60 | 35.53 | 0.17 | 0.00 | 0.00 |
August | 113.98 | 81.36 | 32.62 | 170.03 | 39.98 | 2.67 | 0.00 | 0.00 |
September | 89.54 | 59.94 | 29.60 | 127.13 | 53.12 | 1.17 | 0.00 | 0.00 |
October | 64.01 | 45.29 | 18.72 | 79.56 | 77.49 | 1.00 | 0.00 | 0.00 |
November | 46.47 | 33.58 | 12.89 | 54.90 | 81.92 | 3.67 | 0.00 | 0.00 |
December | 34.21 | 22.68 | 11.52 | 32.51 | 106.59 | 0.67 | 0.00 | 0.00 |
Annual Sum or Average | 80.04 | 52.98 | 27.06 | 107.51 | 65.65 | 36.00 | 0.00 | 0.00 |
Minimum of Months | 34.21 | 22.68 | 11.52 | 32.51 | 35.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.17 | 92.18 | 49.38 | 197.91 | 106.59 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.51 | 28.91 | 11.60 | 43.72 | 90.02 | 3.17 | 0.00 | 0.00 |
February | 59.10 | 45.43 | 13.66 | 67.43 | 92.33 | 4.00 | 0.00 | 0.00 |
March | 76.53 | 53.59 | 22.94 | 95.63 | 71.35 | 8.83 | 0.00 | 0.00 |
April | 82.73 | 48.37 | 34.36 | 103.40 | 60.17 | 10.50 | 0.00 | 0.00 |
May | 105.62 | 56.24 | 49.38 | 144.17 | 43.26 | 0.17 | 0.00 | 0.00 |
June | 132.17 | 92.18 | 39.99 | 197.91 | 37.67 | 0.00 | 0.00 | 0.00 |
July | 114.58 | 68.17 | 46.41 | 171.60 | 35.53 | 0.17 | 0.00 | 0.00 |
August | 113.98 | 81.36 | 32.62 | 170.03 | 39.98 | 2.67 | 0.00 | 0.00 |
September | 89.54 | 59.94 | 29.60 | 127.13 | 53.12 | 1.17 | 0.00 | 0.00 |
October | 64.01 | 45.29 | 18.72 | 79.56 | 77.49 | 1.00 | 0.00 | 0.00 |
November | 46.47 | 33.58 | 12.89 | 54.90 | 81.92 | 3.67 | 0.00 | 0.00 |
December | 34.21 | 22.68 | 11.52 | 32.51 | 106.59 | 0.67 | 0.00 | 0.00 |
Annual Sum or Average | 80.04 | 52.98 | 27.06 | 107.51 | 65.65 | 36.00 | 0.00 | 0.00 |
Minimum of Months | 34.21 | 22.68 | 11.52 | 32.51 | 35.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.17 | 92.18 | 49.38 | 197.91 | 106.59 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.51 | 28.91 | 11.60 | 43.72 | 90.02 | 3.17 | 0.00 | 0.00 |
February | 59.10 | 45.43 | 13.66 | 67.43 | 92.33 | 4.00 | 0.00 | 0.00 |
March | 76.53 | 53.59 | 22.94 | 95.63 | 71.35 | 8.83 | 0.00 | 0.00 |
April | 82.73 | 48.37 | 34.36 | 103.40 | 60.17 | 10.50 | 0.00 | 0.00 |
May | 105.62 | 56.24 | 49.38 | 144.17 | 43.26 | 0.17 | 0.00 | 0.00 |
June | 132.17 | 92.18 | 39.99 | 197.91 | 37.67 | 0.00 | 0.00 | 0.00 |
July | 114.58 | 68.17 | 46.41 | 171.60 | 35.53 | 0.17 | 0.00 | 0.00 |
August | 113.98 | 81.36 | 32.62 | 170.03 | 39.98 | 2.67 | 0.00 | 0.00 |
September | 89.54 | 59.94 | 29.60 | 127.13 | 53.12 | 1.17 | 0.00 | 0.00 |
October | 64.01 | 45.29 | 18.72 | 79.56 | 77.49 | 1.00 | 0.00 | 0.00 |
November | 46.47 | 33.58 | 12.89 | 54.90 | 81.92 | 3.67 | 0.00 | 0.00 |
December | 34.21 | 22.68 | 11.52 | 32.51 | 106.59 | 0.67 | 0.00 | 0.00 |
Annual Sum or Average | 80.04 | 52.98 | 27.06 | 107.51 | 65.65 | 36.00 | 0.00 | 0.00 |
Minimum of Months | 34.21 | 22.68 | 11.52 | 32.51 | 35.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.17 | 92.18 | 49.38 | 197.91 | 106.59 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.51 | 28.91 | 11.60 | 43.72 | 90.02 | 3.17 | 0.00 | 0.00 |
February | 59.10 | 45.43 | 13.66 | 67.43 | 92.33 | 4.00 | 0.00 | 0.00 |
March | 76.53 | 53.59 | 22.94 | 95.63 | 71.35 | 8.83 | 0.00 | 0.00 |
April | 82.73 | 48.37 | 34.36 | 103.40 | 60.17 | 10.50 | 0.00 | 0.00 |
May | 105.62 | 56.24 | 49.38 | 144.17 | 43.26 | 0.17 | 0.00 | 0.00 |
June | 132.17 | 92.18 | 39.99 | 197.91 | 37.67 | 0.00 | 0.00 | 0.00 |
July | 114.58 | 68.17 | 46.41 | 171.60 | 35.53 | 0.17 | 0.00 | 0.00 |
August | 113.98 | 81.36 | 32.62 | 170.03 | 39.98 | 2.67 | 0.00 | 0.00 |
September | 89.54 | 59.94 | 29.60 | 127.13 | 53.12 | 1.17 | 0.00 | 0.00 |
October | 64.01 | 45.29 | 18.72 | 79.56 | 77.49 | 1.00 | 0.00 | 0.00 |
November | 46.47 | 33.58 | 12.89 | 54.90 | 81.92 | 3.67 | 0.00 | 0.00 |
December | 34.21 | 22.68 | 11.52 | 32.51 | 106.59 | 0.67 | 0.00 | 0.00 |
Annual Sum or Average | 80.04 | 52.98 | 27.06 | 107.51 | 65.65 | 36.00 | 0.00 | 0.00 |
Minimum of Months | 34.21 | 22.68 | 11.52 | 32.51 | 35.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.17 | 92.18 | 49.38 | 197.91 | 106.59 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.51 | 28.91 | 11.60 | 43.72 | 90.02 | 3.17 | 0.00 | 0.00 |
February | 59.10 | 45.43 | 13.66 | 67.43 | 92.33 | 4.00 | 0.00 | 0.00 |
March | 76.53 | 53.59 | 22.94 | 95.63 | 71.35 | 8.83 | 0.00 | 0.00 |
April | 82.73 | 48.37 | 34.36 | 103.40 | 60.17 | 10.50 | 0.00 | 0.00 |
May | 105.62 | 56.24 | 49.38 | 144.17 | 43.26 | 0.17 | 0.00 | 0.00 |
June | 132.17 | 92.18 | 39.99 | 197.91 | 37.67 | 0.00 | 0.00 | 0.00 |
July | 114.58 | 68.17 | 46.41 | 171.60 | 35.53 | 0.17 | 0.00 | 0.00 |
August | 113.98 | 81.36 | 32.62 | 170.03 | 39.98 | 2.67 | 0.00 | 0.00 |
September | 89.54 | 59.94 | 29.60 | 127.13 | 53.12 | 1.17 | 0.00 | 0.00 |
October | 64.01 | 45.29 | 18.72 | 79.56 | 77.49 | 1.00 | 0.00 | 0.00 |
November | 46.47 | 33.58 | 12.89 | 54.90 | 81.92 | 3.67 | 0.00 | 0.00 |
December | 34.21 | 22.68 | 11.52 | 32.51 | 106.59 | 0.67 | 0.00 | 0.00 |
Annual Sum or Average | 80.04 | 52.98 | 27.06 | 107.51 | 65.65 | 36.00 | 0.00 | 0.00 |
Minimum of Months | 34.21 | 22.68 | 11.52 | 32.51 | 35.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.17 | 92.18 | 49.38 | 197.91 | 106.59 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.51 | 28.91 | 11.60 | 43.72 | 90.02 | 3.17 | 0.00 | 0.00 |
February | 59.10 | 45.43 | 13.66 | 67.43 | 92.33 | 4.00 | 0.00 | 0.00 |
March | 76.53 | 53.59 | 22.94 | 95.63 | 71.35 | 8.83 | 0.00 | 0.00 |
April | 82.73 | 48.37 | 34.36 | 103.40 | 60.17 | 10.50 | 0.00 | 0.00 |
May | 105.62 | 56.24 | 49.38 | 144.17 | 43.26 | 0.17 | 0.00 | 0.00 |
June | 132.17 | 92.18 | 39.99 | 197.91 | 37.67 | 0.00 | 0.00 | 0.00 |
July | 114.58 | 68.17 | 46.41 | 171.60 | 35.53 | 0.17 | 0.00 | 0.00 |
August | 113.98 | 81.36 | 32.62 | 170.03 | 39.98 | 2.67 | 0.00 | 0.00 |
September | 89.54 | 59.94 | 29.60 | 127.13 | 53.12 | 1.17 | 0.00 | 0.00 |
October | 64.01 | 45.29 | 18.72 | 79.56 | 77.49 | 1.00 | 0.00 | 0.00 |
November | 46.47 | 33.58 | 12.89 | 54.90 | 81.92 | 3.67 | 0.00 | 0.00 |
December | 34.21 | 22.68 | 11.52 | 32.51 | 106.59 | 0.67 | 0.00 | 0.00 |
Annual Sum or Average | 80.04 | 52.98 | 27.06 | 107.51 | 65.65 | 36.00 | 0.00 | 0.00 |
Minimum of Months | 34.21 | 22.68 | 11.52 | 32.51 | 35.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.17 | 92.18 | 49.38 | 197.91 | 106.59 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.51 | 28.91 | 11.60 | 43.72 | 90.02 | 3.17 | 0.00 | 0.00 |
February | 59.10 | 45.43 | 13.66 | 67.43 | 92.33 | 4.00 | 0.00 | 0.00 |
March | 76.53 | 53.59 | 22.94 | 95.63 | 71.35 | 8.83 | 0.00 | 0.00 |
April | 82.73 | 48.37 | 34.36 | 103.40 | 60.17 | 10.50 | 0.00 | 0.00 |
May | 105.62 | 56.24 | 49.38 | 144.17 | 43.26 | 0.17 | 0.00 | 0.00 |
June | 132.17 | 92.18 | 39.99 | 197.91 | 37.67 | 0.00 | 0.00 | 0.00 |
July | 114.58 | 68.17 | 46.41 | 171.60 | 35.53 | 0.17 | 0.00 | 0.00 |
August | 113.98 | 81.36 | 32.62 | 170.03 | 39.98 | 2.67 | 0.00 | 0.00 |
September | 89.54 | 59.94 | 29.60 | 127.13 | 53.12 | 1.17 | 0.00 | 0.00 |
October | 64.01 | 45.29 | 18.72 | 79.56 | 77.49 | 1.00 | 0.00 | 0.00 |
November | 46.47 | 33.58 | 12.89 | 54.90 | 81.92 | 3.67 | 0.00 | 0.00 |
December | 34.21 | 22.68 | 11.52 | 32.51 | 106.59 | 0.67 | 0.00 | 0.00 |
Annual Sum or Average | 80.04 | 52.98 | 27.06 | 107.51 | 65.65 | 36.00 | 0.00 | 0.00 |
Minimum of Months | 34.21 | 22.68 | 11.52 | 32.51 | 35.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.17 | 92.18 | 49.38 | 197.91 | 106.59 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.51 | 28.91 | 11.60 | 43.72 | 90.02 | 3.17 | 0.00 | 0.00 |
February | 59.10 | 45.43 | 13.66 | 67.43 | 92.33 | 4.00 | 0.00 | 0.00 |
March | 76.53 | 53.59 | 22.94 | 95.63 | 71.35 | 8.83 | 0.00 | 0.00 |
April | 82.73 | 48.37 | 34.36 | 103.40 | 60.17 | 10.50 | 0.00 | 0.00 |
May | 105.62 | 56.24 | 49.38 | 144.17 | 43.26 | 0.17 | 0.00 | 0.00 |
June | 132.17 | 92.18 | 39.99 | 197.91 | 37.67 | 0.00 | 0.00 | 0.00 |
July | 114.58 | 68.17 | 46.41 | 171.60 | 35.53 | 0.17 | 0.00 | 0.00 |
August | 113.98 | 81.36 | 32.62 | 170.03 | 39.98 | 2.67 | 0.00 | 0.00 |
September | 89.54 | 59.94 | 29.60 | 127.13 | 53.12 | 1.17 | 0.00 | 0.00 |
October | 64.01 | 45.29 | 18.72 | 79.56 | 77.49 | 1.00 | 0.00 | 0.00 |
November | 46.47 | 33.58 | 12.89 | 54.90 | 81.92 | 3.67 | 0.00 | 0.00 |
December | 34.21 | 22.68 | 11.52 | 32.51 | 106.59 | 0.67 | 0.00 | 0.00 |
Annual Sum or Average | 80.04 | 52.98 | 27.06 | 107.51 | 65.65 | 36.00 | 0.00 | 0.00 |
Minimum of Months | 34.21 | 22.68 | 11.52 | 32.51 | 35.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.17 | 92.18 | 49.38 | 197.91 | 106.59 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.51 | 28.91 | 11.60 | 43.72 | 90.02 | 3.17 | 0.00 | 0.00 |
February | 59.10 | 45.43 | 13.66 | 67.43 | 92.33 | 4.00 | 0.00 | 0.00 |
March | 76.53 | 53.59 | 22.94 | 95.63 | 71.35 | 8.83 | 0.00 | 0.00 |
April | 82.73 | 48.37 | 34.36 | 103.40 | 60.17 | 10.50 | 0.00 | 0.00 |
May | 105.62 | 56.24 | 49.38 | 144.17 | 43.26 | 0.17 | 0.00 | 0.00 |
June | 132.17 | 92.18 | 39.99 | 197.91 | 37.67 | 0.00 | 0.00 | 0.00 |
July | 114.58 | 68.17 | 46.41 | 171.60 | 35.53 | 0.17 | 0.00 | 0.00 |
August | 113.98 | 81.36 | 32.62 | 170.03 | 39.98 | 2.67 | 0.00 | 0.00 |
September | 89.54 | 59.94 | 29.60 | 127.13 | 53.12 | 1.17 | 0.00 | 0.00 |
October | 64.01 | 45.29 | 18.72 | 79.56 | 77.49 | 1.00 | 0.00 | 0.00 |
November | 46.47 | 33.58 | 12.89 | 54.90 | 81.92 | 3.67 | 0.00 | 0.00 |
December | 34.21 | 22.68 | 11.52 | 32.51 | 106.59 | 0.67 | 0.00 | 0.00 |
Annual Sum or Average | 80.04 | 52.98 | 27.06 | 107.51 | 65.65 | 36.00 | 0.00 | 0.00 |
Minimum of Months | 34.21 | 22.68 | 11.52 | 32.51 | 35.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.17 | 92.18 | 49.38 | 197.91 | 106.59 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.51 | 28.91 | 11.60 | 43.72 | 90.02 | 3.17 | 0.00 | 0.00 |
February | 59.10 | 45.43 | 13.66 | 67.43 | 92.33 | 4.00 | 0.00 | 0.00 |
March | 76.53 | 53.59 | 22.94 | 95.63 | 71.35 | 8.83 | 0.00 | 0.00 |
April | 82.73 | 48.37 | 34.36 | 103.40 | 60.17 | 10.50 | 0.00 | 0.00 |
May | 105.62 | 56.24 | 49.38 | 144.17 | 43.26 | 0.17 | 0.00 | 0.00 |
June | 132.17 | 92.18 | 39.99 | 197.91 | 37.67 | 0.00 | 0.00 | 0.00 |
July | 114.58 | 68.17 | 46.41 | 171.60 | 35.53 | 0.17 | 0.00 | 0.00 |
August | 113.98 | 81.36 | 32.62 | 170.03 | 39.98 | 2.67 | 0.00 | 0.00 |
September | 89.54 | 59.94 | 29.60 | 127.13 | 53.12 | 1.17 | 0.00 | 0.00 |
October | 64.01 | 45.29 | 18.72 | 79.56 | 77.49 | 1.00 | 0.00 | 0.00 |
November | 46.47 | 33.58 | 12.89 | 54.90 | 81.92 | 3.67 | 0.00 | 0.00 |
December | 34.21 | 22.68 | 11.52 | 32.51 | 106.59 | 0.67 | 0.00 | 0.00 |
Annual Sum or Average | 80.04 | 52.98 | 27.06 | 107.51 | 65.65 | 36.00 | 0.00 | 0.00 |
Minimum of Months | 34.21 | 22.68 | 11.52 | 32.51 | 35.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.17 | 92.18 | 49.38 | 197.91 | 106.59 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.51 | 28.91 | 11.60 | 43.72 | 90.02 | 3.17 | 0.00 | 0.00 |
February | 59.10 | 45.43 | 13.66 | 67.43 | 92.33 | 4.00 | 0.00 | 0.00 |
March | 76.53 | 53.59 | 22.94 | 95.63 | 71.35 | 8.83 | 0.00 | 0.00 |
April | 82.73 | 48.37 | 34.36 | 103.40 | 60.17 | 10.50 | 0.00 | 0.00 |
May | 105.62 | 56.24 | 49.38 | 144.17 | 43.26 | 0.17 | 0.00 | 0.00 |
June | 132.17 | 92.18 | 39.99 | 197.91 | 37.67 | 0.00 | 0.00 | 0.00 |
July | 114.58 | 68.17 | 46.41 | 171.60 | 35.53 | 0.17 | 0.00 | 0.00 |
August | 113.98 | 81.36 | 32.62 | 170.03 | 39.98 | 2.67 | 0.00 | 0.00 |
September | 89.54 | 59.94 | 29.60 | 127.13 | 53.12 | 1.17 | 0.00 | 0.00 |
October | 64.01 | 45.29 | 18.72 | 79.56 | 77.49 | 1.00 | 0.00 | 0.00 |
November | 46.47 | 33.58 | 12.89 | 54.90 | 81.92 | 3.67 | 0.00 | 0.00 |
December | 34.21 | 22.68 | 11.52 | 32.51 | 106.59 | 0.67 | 0.00 | 0.00 |
Annual Sum or Average | 80.04 | 52.98 | 27.06 | 107.51 | 65.65 | 36.00 | 0.00 | 0.00 |
Minimum of Months | 34.21 | 22.68 | 11.52 | 32.51 | 35.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.17 | 92.18 | 49.38 | 197.91 | 106.59 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.51 | 28.91 | 11.60 | 43.72 | 90.02 | 3.17 | 0.00 | 0.00 |
February | 59.10 | 45.43 | 13.66 | 67.43 | 92.33 | 4.00 | 0.00 | 0.00 |
March | 76.53 | 53.59 | 22.94 | 95.63 | 71.35 | 8.83 | 0.00 | 0.00 |
April | 82.73 | 48.37 | 34.36 | 103.40 | 60.17 | 10.50 | 0.00 | 0.00 |
May | 105.62 | 56.24 | 49.38 | 144.17 | 43.26 | 0.17 | 0.00 | 0.00 |
June | 132.17 | 92.18 | 39.99 | 197.91 | 37.67 | 0.00 | 0.00 | 0.00 |
July | 114.58 | 68.17 | 46.41 | 171.60 | 35.53 | 0.17 | 0.00 | 0.00 |
August | 113.98 | 81.36 | 32.62 | 170.03 | 39.98 | 2.67 | 0.00 | 0.00 |
September | 89.54 | 59.94 | 29.60 | 127.13 | 53.12 | 1.17 | 0.00 | 0.00 |
October | 64.01 | 45.29 | 18.72 | 79.56 | 77.49 | 1.00 | 0.00 | 0.00 |
November | 46.47 | 33.58 | 12.89 | 54.90 | 81.92 | 3.67 | 0.00 | 0.00 |
December | 34.21 | 22.68 | 11.52 | 32.51 | 106.59 | 0.67 | 0.00 | 0.00 |
Annual Sum or Average | 80.04 | 52.98 | 27.06 | 107.51 | 65.65 | 36.00 | 0.00 | 0.00 |
Minimum of Months | 34.21 | 22.68 | 11.52 | 32.51 | 35.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.17 | 92.18 | 49.38 | 197.91 | 106.59 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.51 | 28.91 | 11.60 | 43.72 | 90.02 | 3.17 | 0.00 | 0.00 |
February | 59.10 | 45.43 | 13.66 | 67.43 | 92.33 | 4.00 | 0.00 | 0.00 |
March | 76.53 | 53.59 | 22.94 | 95.63 | 71.35 | 8.83 | 0.00 | 0.00 |
April | 82.73 | 48.37 | 34.36 | 103.40 | 60.17 | 10.50 | 0.00 | 0.00 |
May | 105.62 | 56.24 | 49.38 | 144.17 | 43.26 | 0.17 | 0.00 | 0.00 |
June | 132.17 | 92.18 | 39.99 | 197.91 | 37.67 | 0.00 | 0.00 | 0.00 |
July | 114.58 | 68.17 | 46.41 | 171.60 | 35.53 | 0.17 | 0.00 | 0.00 |
August | 113.98 | 81.36 | 32.62 | 170.03 | 39.98 | 2.67 | 0.00 | 0.00 |
September | 89.54 | 59.94 | 29.60 | 127.13 | 53.12 | 1.17 | 0.00 | 0.00 |
October | 64.01 | 45.29 | 18.72 | 79.56 | 77.49 | 1.00 | 0.00 | 0.00 |
November | 46.47 | 33.58 | 12.89 | 54.90 | 81.92 | 3.67 | 0.00 | 0.00 |
December | 34.21 | 22.68 | 11.52 | 32.51 | 106.59 | 0.67 | 0.00 | 0.00 |
Annual Sum or Average | 80.04 | 52.98 | 27.06 | 107.51 | 65.65 | 36.00 | 0.00 | 0.00 |
Minimum of Months | 34.21 | 22.68 | 11.52 | 32.51 | 35.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.17 | 92.18 | 49.38 | 197.91 | 106.59 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 55.41 | 99.65 | 5.17 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.71 | 103.31 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 115.66 | 75.67 | 13.67 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 125.04 | 61.59 | 16.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 167.97 | 49.75 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 214.36 | 56.51 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 182.22 | 58.49 | 0.33 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 182.25 | 62.86 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 139.58 | 74.97 | 2.00 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 92.57 | 92.44 | 12.83 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 68.12 | 87.04 | 10.17 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 42.17 | 122.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 122.51 | 78.61 | 66.33 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 42.17 | 49.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 214.36 | 122.32 | 16.67 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315572E+09 | 0.199870E+09 | 0.115702E+09 | 0.309277E+09 | 0.437418E+09 |
February | 0.346078E+09 | 0.215077E+09 | 0.131001E+09 | 0.334486E+09 | 0.404596E+09 |
March | 0.446621E+09 | 0.246599E+09 | 0.200022E+09 | 0.460182E+09 | 0.336018E+09 |
April | 0.405093E+09 | 0.170862E+09 | 0.234231E+09 | 0.400714E+09 | 0.280537E+09 |
May | 0.513184E+09 | 0.180832E+09 | 0.332352E+09 | 0.589344E+09 | 0.192279E+09 |
June | 0.608152E+09 | 0.292898E+09 | 0.315253E+09 | 0.822892E+09 | 0.124884E+09 |
July | 0.511144E+09 | 0.186954E+09 | 0.324190E+09 | 0.691737E+09 | 0.119278E+09 |
August | 0.534929E+09 | 0.264664E+09 | 0.270265E+09 | 0.709935E+09 | 0.136246E+09 |
September | 0.459600E+09 | 0.220901E+09 | 0.238699E+09 | 0.579364E+09 | 0.200023E+09 |
October | 0.397121E+09 | 0.226573E+09 | 0.170549E+09 | 0.425862E+09 | 0.375982E+09 |
November | 0.315827E+09 | 0.191572E+09 | 0.124255E+09 | 0.315516E+09 | 0.394427E+09 |
December | 0.263881E+09 | 0.155844E+09 | 0.108037E+09 | 0.233718E+09 | 0.510508E+09 |
Annual Sum or Average | 0.511720E+10 | 0.255265E+10 | 0.256456E+10 | 0.587303E+10 | 0.351220E+10 |
Minimum of Months | 0.263881E+09 | 0.155844E+09 | 0.108037E+09 | 0.233718E+09 | 0.119278E+09 |
Maximum of Months | 0.608152E+09 | 0.292898E+09 | 0.332352E+09 | 0.822892E+09 | 0.510508E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315572E+09 | 0.199870E+09 | 0.115702E+09 | 0.309277E+09 | 0.437418E+09 |
February | 0.346078E+09 | 0.215077E+09 | 0.131001E+09 | 0.334486E+09 | 0.404596E+09 |
March | 0.446621E+09 | 0.246599E+09 | 0.200022E+09 | 0.460182E+09 | 0.336018E+09 |
April | 0.405093E+09 | 0.170862E+09 | 0.234231E+09 | 0.400714E+09 | 0.280537E+09 |
May | 0.513184E+09 | 0.180832E+09 | 0.332352E+09 | 0.589344E+09 | 0.192279E+09 |
June | 0.608152E+09 | 0.292898E+09 | 0.315253E+09 | 0.822892E+09 | 0.124884E+09 |
July | 0.511144E+09 | 0.186954E+09 | 0.324190E+09 | 0.691737E+09 | 0.119278E+09 |
August | 0.534929E+09 | 0.264664E+09 | 0.270265E+09 | 0.709935E+09 | 0.136246E+09 |
September | 0.459600E+09 | 0.220901E+09 | 0.238699E+09 | 0.579364E+09 | 0.200023E+09 |
October | 0.397121E+09 | 0.226573E+09 | 0.170549E+09 | 0.425862E+09 | 0.375982E+09 |
November | 0.315827E+09 | 0.191572E+09 | 0.124255E+09 | 0.315516E+09 | 0.394427E+09 |
December | 0.263881E+09 | 0.155844E+09 | 0.108037E+09 | 0.233718E+09 | 0.510508E+09 |
Annual Sum or Average | 0.511720E+10 | 0.255265E+10 | 0.256456E+10 | 0.587303E+10 | 0.351220E+10 |
Minimum of Months | 0.263881E+09 | 0.155844E+09 | 0.108037E+09 | 0.233718E+09 | 0.119278E+09 |
Maximum of Months | 0.608152E+09 | 0.292898E+09 | 0.332352E+09 | 0.822892E+09 | 0.510508E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 55325142.07 | 0.00 | 55325142.07 | 11887814.34 | 0.272690E+09 |
February | 62807707.53 | 0.00 | 62807707.53 | 13235400.00 | 0.250906E+09 |
March | 94653093.88 | 10335.88 | 94642758.00 | 45326850.51 | 0.204967E+09 |
April | 0.115049E+09 | 710289.13 | 0.114338E+09 | 66893373.54 | 0.166266E+09 |
May | 0.162487E+09 | 5452044.69 | 0.157035E+09 | 0.147575E+09 | 0.106383E+09 |
June | 0.172005E+09 | 18845768.36 | 0.153159E+09 | 0.220936E+09 | 66014118.07 |
July | 0.168680E+09 | 11182152.98 | 0.157498E+09 | 0.220037E+09 | 64809114.60 |
August | 0.134552E+09 | 3677816.15 | 0.130874E+09 | 0.163686E+09 | 77377639.61 |
September | 0.109011E+09 | 71736.72 | 0.108939E+09 | 0.113965E+09 | 0.116900E+09 |
October | 80610534.05 | 0.00 | 80610534.05 | 39268061.10 | 0.226276E+09 |
November | 59219626.80 | 0.00 | 59219626.80 | 17428115.53 | 0.241940E+09 |
December | 51763549.12 | 0.00 | 51763549.12 | 9935180.46 | 0.319804E+09 |
Annual Sum or Average | 0.126616E+10 | 39950143.90 | 0.122621E+10 | 0.107017E+10 | 0.211433E+10 |
Minimum of Months | 51763549.12 | 0.00 | 51763549.12 | 9935180.46 | 64809114.60 |
Maximum of Months | 0.172005E+09 | 18845768.36 | 0.157498E+09 | 0.220936E+09 | 0.319804E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 55323681.99 | 0.00 | 55323681.99 | 11887145.34 | 0.272689E+09 |
February | 62806159.31 | 0.00 | 62806159.31 | 13234759.47 | 0.250906E+09 |
March | 94650538.89 | 10335.39 | 94640203.50 | 45324965.65 | 0.204967E+09 |
April | 0.115045E+09 | 710255.83 | 0.114335E+09 | 66890369.93 | 0.166266E+09 |
May | 0.162482E+09 | 5451789.15 | 0.157030E+09 | 0.147570E+09 | 0.106383E+09 |
June | 0.172000E+09 | 18844885.03 | 0.153155E+09 | 0.220930E+09 | 66013421.08 |
July | 0.168675E+09 | 11181628.86 | 0.157494E+09 | 0.220030E+09 | 64808509.24 |
August | 0.134548E+09 | 3677643.77 | 0.130871E+09 | 0.163682E+09 | 77376984.68 |
September | 0.109008E+09 | 71733.36 | 0.108936E+09 | 0.113962E+09 | 0.116899E+09 |
October | 80608377.68 | 0.00 | 80608377.68 | 39266595.55 | 0.226276E+09 |
November | 59218068.30 | 0.00 | 59218068.30 | 17427320.09 | 0.241940E+09 |
December | 51762101.56 | 0.00 | 51762101.56 | 9934750.93 | 0.319803E+09 |
Annual Sum or Average | 0.126613E+10 | 39948271.39 | 0.122618E+10 | 0.107014E+10 | 0.211433E+10 |
Minimum of Months | 51762101.56 | 0.00 | 51762101.56 | 9934750.93 | 64808509.24 |
Maximum of Months | 0.172000E+09 | 18844885.03 | 0.157494E+09 | 0.220930E+09 | 0.319803E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108493E+09 | 77433946.96 | 31059008.11 | 0.117091E+09 | 0.241118E+09 |
February | 0.142966E+09 | 0.109915E+09 | 33051524.37 | 0.163123E+09 | 0.223367E+09 |
March | 0.204987E+09 | 0.143539E+09 | 61447732.50 | 0.256145E+09 | 0.191097E+09 |
April | 0.214438E+09 | 0.125370E+09 | 89068574.33 | 0.268024E+09 | 0.155972E+09 |
May | 0.282897E+09 | 0.150627E+09 | 0.132270E+09 | 0.386153E+09 | 0.115875E+09 |
June | 0.342582E+09 | 0.238928E+09 | 0.103654E+09 | 0.512977E+09 | 97644249.66 |
July | 0.306896E+09 | 0.182598E+09 | 0.124298E+09 | 0.459618E+09 | 95171137.26 |
August | 0.305291E+09 | 0.217911E+09 | 87379763.21 | 0.455406E+09 | 0.107079E+09 |
September | 0.232079E+09 | 0.155360E+09 | 76718930.45 | 0.329528E+09 | 0.137690E+09 |
October | 0.171452E+09 | 0.121309E+09 | 50143137.29 | 0.213080E+09 | 0.207543E+09 |
November | 0.120455E+09 | 87039033.98 | 33415848.01 | 0.142303E+09 | 0.212344E+09 |
December | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 0.285479E+09 |
Annual Sum or Average | 0.252416E+10 | 0.167078E+10 | 0.853374E+09 | 0.339051E+10 | 0.207038E+10 |
Minimum of Months | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 95171137.26 |
Maximum of Months | 0.342582E+09 | 0.238928E+09 | 0.132270E+09 | 0.512977E+09 | 0.285479E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108493E+09 | 77433946.96 | 31059008.11 | 0.117091E+09 | 0.241118E+09 |
February | 0.142966E+09 | 0.109915E+09 | 33051524.37 | 0.163123E+09 | 0.223367E+09 |
March | 0.204987E+09 | 0.143539E+09 | 61447732.50 | 0.256145E+09 | 0.191097E+09 |
April | 0.214438E+09 | 0.125370E+09 | 89068574.33 | 0.268024E+09 | 0.155972E+09 |
May | 0.282897E+09 | 0.150627E+09 | 0.132270E+09 | 0.386153E+09 | 0.115875E+09 |
June | 0.342582E+09 | 0.238928E+09 | 0.103654E+09 | 0.512977E+09 | 97644249.66 |
July | 0.306896E+09 | 0.182598E+09 | 0.124298E+09 | 0.459618E+09 | 95171137.26 |
August | 0.305291E+09 | 0.217911E+09 | 87379763.21 | 0.455406E+09 | 0.107079E+09 |
September | 0.232079E+09 | 0.155360E+09 | 76718930.45 | 0.329528E+09 | 0.137690E+09 |
October | 0.171452E+09 | 0.121309E+09 | 50143137.29 | 0.213080E+09 | 0.207543E+09 |
November | 0.120455E+09 | 87039033.98 | 33415848.01 | 0.142303E+09 | 0.212344E+09 |
December | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 0.285479E+09 |
Annual Sum or Average | 0.252416E+10 | 0.167078E+10 | 0.853374E+09 | 0.339051E+10 | 0.207038E+10 |
Minimum of Months | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 95171137.26 |
Maximum of Months | 0.342582E+09 | 0.238928E+09 | 0.132270E+09 | 0.512977E+09 | 0.285479E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108493E+09 | 77433946.96 | 31059008.11 | 0.117091E+09 | 0.241118E+09 |
February | 0.142966E+09 | 0.109915E+09 | 33051524.37 | 0.163123E+09 | 0.223367E+09 |
March | 0.204987E+09 | 0.143539E+09 | 61447732.50 | 0.256145E+09 | 0.191097E+09 |
April | 0.214438E+09 | 0.125370E+09 | 89068574.33 | 0.268024E+09 | 0.155972E+09 |
May | 0.282897E+09 | 0.150627E+09 | 0.132270E+09 | 0.386153E+09 | 0.115875E+09 |
June | 0.342582E+09 | 0.238928E+09 | 0.103654E+09 | 0.512977E+09 | 97644249.66 |
July | 0.306896E+09 | 0.182598E+09 | 0.124298E+09 | 0.459618E+09 | 95171137.26 |
August | 0.305291E+09 | 0.217911E+09 | 87379763.21 | 0.455406E+09 | 0.107079E+09 |
September | 0.232079E+09 | 0.155360E+09 | 76718930.45 | 0.329528E+09 | 0.137690E+09 |
October | 0.171452E+09 | 0.121309E+09 | 50143137.29 | 0.213080E+09 | 0.207543E+09 |
November | 0.120455E+09 | 87039033.98 | 33415848.01 | 0.142303E+09 | 0.212344E+09 |
December | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 0.285479E+09 |
Annual Sum or Average | 0.252416E+10 | 0.167078E+10 | 0.853374E+09 | 0.339051E+10 | 0.207038E+10 |
Minimum of Months | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 95171137.26 |
Maximum of Months | 0.342582E+09 | 0.238928E+09 | 0.132270E+09 | 0.512977E+09 | 0.285479E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108493E+09 | 77433946.96 | 31059008.11 | 0.117091E+09 | 0.241118E+09 |
February | 0.142966E+09 | 0.109915E+09 | 33051524.37 | 0.163123E+09 | 0.223367E+09 |
March | 0.204987E+09 | 0.143539E+09 | 61447732.50 | 0.256145E+09 | 0.191097E+09 |
April | 0.214438E+09 | 0.125370E+09 | 89068574.33 | 0.268024E+09 | 0.155972E+09 |
May | 0.282897E+09 | 0.150627E+09 | 0.132270E+09 | 0.386153E+09 | 0.115875E+09 |
June | 0.342582E+09 | 0.238928E+09 | 0.103654E+09 | 0.512977E+09 | 97644249.66 |
July | 0.306896E+09 | 0.182598E+09 | 0.124298E+09 | 0.459618E+09 | 95171137.26 |
August | 0.305291E+09 | 0.217911E+09 | 87379763.21 | 0.455406E+09 | 0.107079E+09 |
September | 0.232079E+09 | 0.155360E+09 | 76718930.45 | 0.329528E+09 | 0.137690E+09 |
October | 0.171452E+09 | 0.121309E+09 | 50143137.29 | 0.213080E+09 | 0.207543E+09 |
November | 0.120455E+09 | 87039033.98 | 33415848.01 | 0.142303E+09 | 0.212344E+09 |
December | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 0.285479E+09 |
Annual Sum or Average | 0.252416E+10 | 0.167078E+10 | 0.853374E+09 | 0.339051E+10 | 0.207038E+10 |
Minimum of Months | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 95171137.26 |
Maximum of Months | 0.342582E+09 | 0.238928E+09 | 0.132270E+09 | 0.512977E+09 | 0.285479E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108493E+09 | 77433946.96 | 31059008.11 | 0.117091E+09 | 0.241118E+09 |
February | 0.142966E+09 | 0.109915E+09 | 33051524.37 | 0.163123E+09 | 0.223367E+09 |
March | 0.204987E+09 | 0.143539E+09 | 61447732.50 | 0.256145E+09 | 0.191097E+09 |
April | 0.214438E+09 | 0.125370E+09 | 89068574.33 | 0.268024E+09 | 0.155972E+09 |
May | 0.282897E+09 | 0.150627E+09 | 0.132270E+09 | 0.386153E+09 | 0.115875E+09 |
June | 0.342582E+09 | 0.238928E+09 | 0.103654E+09 | 0.512977E+09 | 97644249.66 |
July | 0.306896E+09 | 0.182598E+09 | 0.124298E+09 | 0.459618E+09 | 95171137.26 |
August | 0.305291E+09 | 0.217911E+09 | 87379763.21 | 0.455406E+09 | 0.107079E+09 |
September | 0.232079E+09 | 0.155360E+09 | 76718930.45 | 0.329528E+09 | 0.137690E+09 |
October | 0.171452E+09 | 0.121309E+09 | 50143137.29 | 0.213080E+09 | 0.207543E+09 |
November | 0.120455E+09 | 87039033.98 | 33415848.01 | 0.142303E+09 | 0.212344E+09 |
December | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 0.285479E+09 |
Annual Sum or Average | 0.252416E+10 | 0.167078E+10 | 0.853374E+09 | 0.339051E+10 | 0.207038E+10 |
Minimum of Months | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 95171137.26 |
Maximum of Months | 0.342582E+09 | 0.238928E+09 | 0.132270E+09 | 0.512977E+09 | 0.285479E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108493E+09 | 77433946.96 | 31059008.11 | 0.117091E+09 | 0.241118E+09 |
February | 0.142966E+09 | 0.109915E+09 | 33051524.37 | 0.163123E+09 | 0.223367E+09 |
March | 0.204987E+09 | 0.143539E+09 | 61447732.50 | 0.256145E+09 | 0.191097E+09 |
April | 0.214438E+09 | 0.125370E+09 | 89068574.33 | 0.268024E+09 | 0.155972E+09 |
May | 0.282897E+09 | 0.150627E+09 | 0.132270E+09 | 0.386153E+09 | 0.115875E+09 |
June | 0.342582E+09 | 0.238928E+09 | 0.103654E+09 | 0.512977E+09 | 97644249.66 |
July | 0.306896E+09 | 0.182598E+09 | 0.124298E+09 | 0.459618E+09 | 95171137.26 |
August | 0.305291E+09 | 0.217911E+09 | 87379763.21 | 0.455406E+09 | 0.107079E+09 |
September | 0.232079E+09 | 0.155360E+09 | 76718930.45 | 0.329528E+09 | 0.137690E+09 |
October | 0.171452E+09 | 0.121309E+09 | 50143137.29 | 0.213080E+09 | 0.207543E+09 |
November | 0.120455E+09 | 87039033.98 | 33415848.01 | 0.142303E+09 | 0.212344E+09 |
December | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 0.285479E+09 |
Annual Sum or Average | 0.252416E+10 | 0.167078E+10 | 0.853374E+09 | 0.339051E+10 | 0.207038E+10 |
Minimum of Months | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 95171137.26 |
Maximum of Months | 0.342582E+09 | 0.238928E+09 | 0.132270E+09 | 0.512977E+09 | 0.285479E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108493E+09 | 77433946.96 | 31059008.11 | 0.117091E+09 | 0.241118E+09 |
February | 0.142966E+09 | 0.109915E+09 | 33051524.37 | 0.163123E+09 | 0.223367E+09 |
March | 0.204987E+09 | 0.143539E+09 | 61447732.50 | 0.256145E+09 | 0.191097E+09 |
April | 0.214438E+09 | 0.125370E+09 | 89068574.33 | 0.268024E+09 | 0.155972E+09 |
May | 0.282897E+09 | 0.150627E+09 | 0.132270E+09 | 0.386153E+09 | 0.115875E+09 |
June | 0.342582E+09 | 0.238928E+09 | 0.103654E+09 | 0.512977E+09 | 97644249.66 |
July | 0.306896E+09 | 0.182598E+09 | 0.124298E+09 | 0.459618E+09 | 95171137.26 |
August | 0.305291E+09 | 0.217911E+09 | 87379763.21 | 0.455406E+09 | 0.107079E+09 |
September | 0.232079E+09 | 0.155360E+09 | 76718930.45 | 0.329528E+09 | 0.137690E+09 |
October | 0.171452E+09 | 0.121309E+09 | 50143137.29 | 0.213080E+09 | 0.207543E+09 |
November | 0.120455E+09 | 87039033.98 | 33415848.01 | 0.142303E+09 | 0.212344E+09 |
December | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 0.285479E+09 |
Annual Sum or Average | 0.252416E+10 | 0.167078E+10 | 0.853374E+09 | 0.339051E+10 | 0.207038E+10 |
Minimum of Months | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 95171137.26 |
Maximum of Months | 0.342582E+09 | 0.238928E+09 | 0.132270E+09 | 0.512977E+09 | 0.285479E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108493E+09 | 77433946.96 | 31059008.11 | 0.117091E+09 | 0.241118E+09 |
February | 0.142966E+09 | 0.109915E+09 | 33051524.37 | 0.163123E+09 | 0.223367E+09 |
March | 0.204987E+09 | 0.143539E+09 | 61447732.50 | 0.256145E+09 | 0.191097E+09 |
April | 0.214438E+09 | 0.125370E+09 | 89068574.33 | 0.268024E+09 | 0.155972E+09 |
May | 0.282897E+09 | 0.150627E+09 | 0.132270E+09 | 0.386153E+09 | 0.115875E+09 |
June | 0.342582E+09 | 0.238928E+09 | 0.103654E+09 | 0.512977E+09 | 97644249.66 |
July | 0.306896E+09 | 0.182598E+09 | 0.124298E+09 | 0.459618E+09 | 95171137.26 |
August | 0.305291E+09 | 0.217911E+09 | 87379763.21 | 0.455406E+09 | 0.107079E+09 |
September | 0.232079E+09 | 0.155360E+09 | 76718930.45 | 0.329528E+09 | 0.137690E+09 |
October | 0.171452E+09 | 0.121309E+09 | 50143137.29 | 0.213080E+09 | 0.207543E+09 |
November | 0.120455E+09 | 87039033.98 | 33415848.01 | 0.142303E+09 | 0.212344E+09 |
December | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 0.285479E+09 |
Annual Sum or Average | 0.252416E+10 | 0.167078E+10 | 0.853374E+09 | 0.339051E+10 | 0.207038E+10 |
Minimum of Months | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 95171137.26 |
Maximum of Months | 0.342582E+09 | 0.238928E+09 | 0.132270E+09 | 0.512977E+09 | 0.285479E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108493E+09 | 77433946.96 | 31059008.11 | 0.117091E+09 | 0.241118E+09 |
February | 0.142966E+09 | 0.109915E+09 | 33051524.37 | 0.163123E+09 | 0.223367E+09 |
March | 0.204987E+09 | 0.143539E+09 | 61447732.50 | 0.256145E+09 | 0.191097E+09 |
April | 0.214438E+09 | 0.125370E+09 | 89068574.33 | 0.268024E+09 | 0.155972E+09 |
May | 0.282897E+09 | 0.150627E+09 | 0.132270E+09 | 0.386153E+09 | 0.115875E+09 |
June | 0.342582E+09 | 0.238928E+09 | 0.103654E+09 | 0.512977E+09 | 97644249.66 |
July | 0.306896E+09 | 0.182598E+09 | 0.124298E+09 | 0.459618E+09 | 95171137.26 |
August | 0.305291E+09 | 0.217911E+09 | 87379763.21 | 0.455406E+09 | 0.107079E+09 |
September | 0.232079E+09 | 0.155360E+09 | 76718930.45 | 0.329528E+09 | 0.137690E+09 |
October | 0.171452E+09 | 0.121309E+09 | 50143137.29 | 0.213080E+09 | 0.207543E+09 |
November | 0.120455E+09 | 87039033.98 | 33415848.01 | 0.142303E+09 | 0.212344E+09 |
December | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 0.285479E+09 |
Annual Sum or Average | 0.252416E+10 | 0.167078E+10 | 0.853374E+09 | 0.339051E+10 | 0.207038E+10 |
Minimum of Months | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 95171137.26 |
Maximum of Months | 0.342582E+09 | 0.238928E+09 | 0.132270E+09 | 0.512977E+09 | 0.285479E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108493E+09 | 77433946.96 | 31059008.11 | 0.117091E+09 | 0.241118E+09 |
February | 0.142966E+09 | 0.109915E+09 | 33051524.37 | 0.163123E+09 | 0.223367E+09 |
March | 0.204987E+09 | 0.143539E+09 | 61447732.50 | 0.256145E+09 | 0.191097E+09 |
April | 0.214438E+09 | 0.125370E+09 | 89068574.33 | 0.268024E+09 | 0.155972E+09 |
May | 0.282897E+09 | 0.150627E+09 | 0.132270E+09 | 0.386153E+09 | 0.115875E+09 |
June | 0.342582E+09 | 0.238928E+09 | 0.103654E+09 | 0.512977E+09 | 97644249.66 |
July | 0.306896E+09 | 0.182598E+09 | 0.124298E+09 | 0.459618E+09 | 95171137.26 |
August | 0.305291E+09 | 0.217911E+09 | 87379763.21 | 0.455406E+09 | 0.107079E+09 |
September | 0.232079E+09 | 0.155360E+09 | 76718930.45 | 0.329528E+09 | 0.137690E+09 |
October | 0.171452E+09 | 0.121309E+09 | 50143137.29 | 0.213080E+09 | 0.207543E+09 |
November | 0.120455E+09 | 87039033.98 | 33415848.01 | 0.142303E+09 | 0.212344E+09 |
December | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 0.285479E+09 |
Annual Sum or Average | 0.252416E+10 | 0.167078E+10 | 0.853374E+09 | 0.339051E+10 | 0.207038E+10 |
Minimum of Months | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 95171137.26 |
Maximum of Months | 0.342582E+09 | 0.238928E+09 | 0.132270E+09 | 0.512977E+09 | 0.285479E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108493E+09 | 77433946.96 | 31059008.11 | 0.117091E+09 | 0.241118E+09 |
February | 0.142966E+09 | 0.109915E+09 | 33051524.37 | 0.163123E+09 | 0.223367E+09 |
March | 0.204987E+09 | 0.143539E+09 | 61447732.50 | 0.256145E+09 | 0.191097E+09 |
April | 0.214438E+09 | 0.125370E+09 | 89068574.33 | 0.268024E+09 | 0.155972E+09 |
May | 0.282897E+09 | 0.150627E+09 | 0.132270E+09 | 0.386153E+09 | 0.115875E+09 |
June | 0.342582E+09 | 0.238928E+09 | 0.103654E+09 | 0.512977E+09 | 97644249.66 |
July | 0.306896E+09 | 0.182598E+09 | 0.124298E+09 | 0.459618E+09 | 95171137.26 |
August | 0.305291E+09 | 0.217911E+09 | 87379763.21 | 0.455406E+09 | 0.107079E+09 |
September | 0.232079E+09 | 0.155360E+09 | 76718930.45 | 0.329528E+09 | 0.137690E+09 |
October | 0.171452E+09 | 0.121309E+09 | 50143137.29 | 0.213080E+09 | 0.207543E+09 |
November | 0.120455E+09 | 87039033.98 | 33415848.01 | 0.142303E+09 | 0.212344E+09 |
December | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 0.285479E+09 |
Annual Sum or Average | 0.252416E+10 | 0.167078E+10 | 0.853374E+09 | 0.339051E+10 | 0.207038E+10 |
Minimum of Months | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 95171137.26 |
Maximum of Months | 0.342582E+09 | 0.238928E+09 | 0.132270E+09 | 0.512977E+09 | 0.285479E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108493E+09 | 77433946.96 | 31059008.11 | 0.117091E+09 | 0.241118E+09 |
February | 0.142966E+09 | 0.109915E+09 | 33051524.37 | 0.163123E+09 | 0.223367E+09 |
March | 0.204987E+09 | 0.143539E+09 | 61447732.50 | 0.256145E+09 | 0.191097E+09 |
April | 0.214438E+09 | 0.125370E+09 | 89068574.33 | 0.268024E+09 | 0.155972E+09 |
May | 0.282897E+09 | 0.150627E+09 | 0.132270E+09 | 0.386153E+09 | 0.115875E+09 |
June | 0.342582E+09 | 0.238928E+09 | 0.103654E+09 | 0.512977E+09 | 97644249.66 |
July | 0.306896E+09 | 0.182598E+09 | 0.124298E+09 | 0.459618E+09 | 95171137.26 |
August | 0.305291E+09 | 0.217911E+09 | 87379763.21 | 0.455406E+09 | 0.107079E+09 |
September | 0.232079E+09 | 0.155360E+09 | 76718930.45 | 0.329528E+09 | 0.137690E+09 |
October | 0.171452E+09 | 0.121309E+09 | 50143137.29 | 0.213080E+09 | 0.207543E+09 |
November | 0.120455E+09 | 87039033.98 | 33415848.01 | 0.142303E+09 | 0.212344E+09 |
December | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 0.285479E+09 |
Annual Sum or Average | 0.252416E+10 | 0.167078E+10 | 0.853374E+09 | 0.339051E+10 | 0.207038E+10 |
Minimum of Months | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 95171137.26 |
Maximum of Months | 0.342582E+09 | 0.238928E+09 | 0.132270E+09 | 0.512977E+09 | 0.285479E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108493E+09 | 77433946.96 | 31059008.11 | 0.117091E+09 | 0.241118E+09 |
February | 0.142966E+09 | 0.109915E+09 | 33051524.37 | 0.163123E+09 | 0.223367E+09 |
March | 0.204987E+09 | 0.143539E+09 | 61447732.50 | 0.256145E+09 | 0.191097E+09 |
April | 0.214438E+09 | 0.125370E+09 | 89068574.33 | 0.268024E+09 | 0.155972E+09 |
May | 0.282897E+09 | 0.150627E+09 | 0.132270E+09 | 0.386153E+09 | 0.115875E+09 |
June | 0.342582E+09 | 0.238928E+09 | 0.103654E+09 | 0.512977E+09 | 97644249.66 |
July | 0.306896E+09 | 0.182598E+09 | 0.124298E+09 | 0.459618E+09 | 95171137.26 |
August | 0.305291E+09 | 0.217911E+09 | 87379763.21 | 0.455406E+09 | 0.107079E+09 |
September | 0.232079E+09 | 0.155360E+09 | 76718930.45 | 0.329528E+09 | 0.137690E+09 |
October | 0.171452E+09 | 0.121309E+09 | 50143137.29 | 0.213080E+09 | 0.207543E+09 |
November | 0.120455E+09 | 87039033.98 | 33415848.01 | 0.142303E+09 | 0.212344E+09 |
December | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 0.285479E+09 |
Annual Sum or Average | 0.252416E+10 | 0.167078E+10 | 0.853374E+09 | 0.339051E+10 | 0.207038E+10 |
Minimum of Months | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 95171137.26 |
Maximum of Months | 0.342582E+09 | 0.238928E+09 | 0.132270E+09 | 0.512977E+09 | 0.285479E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108493E+09 | 77433946.96 | 31059008.11 | 0.117091E+09 | 0.241118E+09 |
February | 0.142966E+09 | 0.109915E+09 | 33051524.37 | 0.163123E+09 | 0.223367E+09 |
March | 0.204987E+09 | 0.143539E+09 | 61447732.50 | 0.256145E+09 | 0.191097E+09 |
April | 0.214438E+09 | 0.125370E+09 | 89068574.33 | 0.268024E+09 | 0.155972E+09 |
May | 0.282897E+09 | 0.150627E+09 | 0.132270E+09 | 0.386153E+09 | 0.115875E+09 |
June | 0.342582E+09 | 0.238928E+09 | 0.103654E+09 | 0.512977E+09 | 97644249.66 |
July | 0.306896E+09 | 0.182598E+09 | 0.124298E+09 | 0.459618E+09 | 95171137.26 |
August | 0.305291E+09 | 0.217911E+09 | 87379763.21 | 0.455406E+09 | 0.107079E+09 |
September | 0.232079E+09 | 0.155360E+09 | 76718930.45 | 0.329528E+09 | 0.137690E+09 |
October | 0.171452E+09 | 0.121309E+09 | 50143137.29 | 0.213080E+09 | 0.207543E+09 |
November | 0.120455E+09 | 87039033.98 | 33415848.01 | 0.142303E+09 | 0.212344E+09 |
December | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 0.285479E+09 |
Annual Sum or Average | 0.252416E+10 | 0.167078E+10 | 0.853374E+09 | 0.339051E+10 | 0.207038E+10 |
Minimum of Months | 91621553.95 | 60754491.35 | 30867062.60 | 87066478.94 | 95171137.26 |
Maximum of Months | 0.342582E+09 | 0.238928E+09 | 0.132270E+09 | 0.512977E+09 | 0.285479E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.148414E+09 | 0.266906E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.200081E+09 | 0.249919E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.309773E+09 | 0.202665E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.324103E+09 | 0.159646E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.449881E+09 | 0.133254E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.555629E+09 | 0.146476E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.488064E+09 | 0.156651E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.488145E+09 | 0.168353E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.361789E+09 | 0.194333E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.247937E+09 | 0.247584E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.176577E+09 | 0.225615E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.327635E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.386333E+10 | 0.247903E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.112936E+09 | 0.133254E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.555629E+09 | 0.327635E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 227.14 | 517.57 | 276.95 | 149.25 | 127.71 | 0.00 | 0.00 |
February | 274.38 | 528.83 | 338.03 | 177.81 | 160.23 | 0.00 | 0.00 |
March | 372.13 | 398.62 | 404.18 | 184.15 | 220.03 | 0.00 | 0.00 |
April | 358.45 | 342.40 | 401.34 | 132.39 | 268.96 | 0.00 | 0.00 |
May | 547.96 | 220.71 | 504.53 | 139.10 | 365.43 | 0.00 | 0.00 |
June | 800.81 | 142.69 | 601.97 | 240.54 | 361.43 | 0.00 | 0.00 |
July | 677.85 | 134.48 | 507.63 | 147.95 | 359.68 | 0.00 | 0.00 |
August | 651.35 | 158.52 | 499.91 | 200.37 | 299.53 | 0.00 | 0.00 |
September | 533.84 | 243.40 | 438.74 | 170.50 | 268.24 | 0.00 | 0.00 |
October | 343.49 | 445.88 | 356.73 | 169.19 | 187.54 | 0.00 | 0.00 |
November | 247.88 | 482.00 | 289.39 | 147.82 | 141.57 | 0.00 | 0.00 |
December | 169.28 | 607.35 | 235.70 | 116.37 | 119.32 | 0.00 | 0.00 |
Annual Sum or Average | 434.46 | 350.96 | 404.83 | 164.42 | 240.41 | 0.00 | 0.00 |
Minimum of Months | 169.28 | 134.48 | 235.70 | 116.37 | 119.32 | 0.00 | 0.00 |
Maximum of Months | 800.81 | 607.35 | 601.97 | 240.54 | 365.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 612.03 | 1260.33 | 567.09 | 404.75 | 162.35 | 0.00 | 0.00 |
February | 944.00 | 1292.64 | 827.35 | 636.08 | 191.27 | 0.00 | 0.00 |
March | 1338.87 | 998.87 | 1071.47 | 750.28 | 321.19 | 0.00 | 0.00 |
April | 1447.66 | 842.44 | 1158.23 | 677.15 | 481.08 | 0.00 | 0.00 |
May | 2018.42 | 605.68 | 1478.70 | 787.33 | 691.38 | 0.00 | 0.00 |
June | 2770.71 | 527.40 | 1850.37 | 1290.51 | 559.86 | 0.00 | 0.00 |
July | 2402.42 | 497.46 | 1604.14 | 954.44 | 649.71 | 0.00 | 0.00 |
August | 2380.41 | 559.70 | 1595.76 | 1139.02 | 456.73 | 0.00 | 0.00 |
September | 1779.86 | 743.69 | 1253.51 | 839.14 | 414.38 | 0.00 | 0.00 |
October | 1113.77 | 1084.83 | 896.18 | 634.08 | 262.10 | 0.00 | 0.00 |
November | 768.61 | 1146.92 | 650.61 | 470.12 | 180.49 | 0.00 | 0.00 |
December | 455.10 | 1492.20 | 478.91 | 317.56 | 161.34 | 0.00 | 0.00 |
Annual Sum or Average | 1505.18 | 919.12 | 1120.57 | 741.72 | 378.84 | 0.00 | 0.00 |
Minimum of Months | 455.10 | 497.46 | 478.91 | 317.56 | 161.34 | 0.00 | 0.00 |
Maximum of Months | 2770.71 | 1492.20 | 1850.37 | 1290.51 | 691.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7332.21 | 22162.75 | 1578.53 | 1126.63 | 451.90 | 0.00 | 0.00 |
February | 11124.77 | 25701.53 | 2302.97 | 1770.56 | 532.41 | 0.00 | 0.00 |
March | 15390.58 | 14956.58 | 2982.48 | 2088.44 | 894.04 | 0.00 | 0.00 |
April | 17278.51 | 10903.28 | 3223.99 | 1884.88 | 1339.11 | 0.00 | 0.00 |
May | 22240.01 | 5373.48 | 4116.04 | 2191.56 | 1924.47 | 0.00 | 0.00 |
June | 31918.29 | 10511.34 | 5150.58 | 3592.18 | 1558.40 | 0.00 | 0.00 |
July | 29539.07 | 11249.80 | 4465.21 | 2656.72 | 1808.49 | 0.00 | 0.00 |
August | 28163.14 | 12317.41 | 4441.86 | 3170.52 | 1271.34 | 0.00 | 0.00 |
September | 18175.88 | 11548.44 | 3489.21 | 2335.78 | 1153.44 | 0.00 | 0.00 |
October | 11855.53 | 12658.31 | 2494.55 | 1764.99 | 729.56 | 0.00 | 0.00 |
November | 8976.40 | 16390.62 | 1810.99 | 1308.60 | 502.39 | 0.00 | 0.00 |
December | 5680.75 | 31894.16 | 1333.06 | 883.95 | 449.10 | 0.00 | 0.00 |
Annual Sum or Average | 17337.55 | 15422.58 | 3119.15 | 2064.62 | 1054.53 | 0.00 | 0.00 |
Minimum of Months | 5680.75 | 5373.48 | 1333.06 | 883.95 | 449.10 | 0.00 | 0.00 |
Maximum of Months | 31918.29 | 31894.16 | 5150.58 | 3592.18 | 1924.47 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.608370E+09 | 0.138626E+10 | 0.741793E+09 | 0.399740E+09 | 0.342053E+09 | 0.00 | 0.00 |
February | 0.663773E+09 | 0.127934E+10 | 0.817770E+09 | 0.430154E+09 | 0.387616E+09 | 0.00 | 0.00 |
March | 0.996713E+09 | 0.106767E+10 | 0.108255E+10 | 0.493219E+09 | 0.589326E+09 | 0.00 | 0.00 |
April | 0.929097E+09 | 0.887491E+09 | 0.104028E+10 | 0.343145E+09 | 0.697136E+09 | 0.00 | 0.00 |
May | 0.146765E+10 | 0.591140E+09 | 0.135134E+10 | 0.372568E+09 | 0.978769E+09 | 0.00 | 0.00 |
June | 0.207570E+10 | 0.369842E+09 | 0.156031E+10 | 0.623487E+09 | 0.936821E+09 | 0.00 | 0.00 |
July | 0.181556E+10 | 0.360189E+09 | 0.135964E+10 | 0.396272E+09 | 0.963372E+09 | 0.00 | 0.00 |
August | 0.174457E+10 | 0.424577E+09 | 0.133896E+10 | 0.536683E+09 | 0.802275E+09 | 0.00 | 0.00 |
September | 0.138371E+10 | 0.630901E+09 | 0.113722E+10 | 0.441945E+09 | 0.695273E+09 | 0.00 | 0.00 |
October | 0.919999E+09 | 0.119426E+10 | 0.955462E+09 | 0.453146E+09 | 0.502316E+09 | 0.00 | 0.00 |
November | 0.642501E+09 | 0.124935E+10 | 0.750092E+09 | 0.383143E+09 | 0.366948E+09 | 0.00 | 0.00 |
December | 0.453406E+09 | 0.162672E+10 | 0.631288E+09 | 0.311688E+09 | 0.319600E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.137010E+11 | 0.110677E+11 | 0.127667E+11 | 0.518519E+10 | 0.758151E+10 | 0.00 | 0.00 |
Minimum of Months | 0.453406E+09 | 0.360189E+09 | 0.631288E+09 | 0.311688E+09 | 0.319600E+09 | 0.00 | 0.00 |
Maximum of Months | 0.207570E+10 | 0.162672E+10 | 0.156031E+10 | 0.623487E+09 | 0.978769E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.163927E+10 | 0.337566E+10 | 0.151890E+10 | 0.108408E+10 | 0.434826E+09 | 0.00 | 0.00 |
February | 0.228373E+10 | 0.312714E+10 | 0.200153E+10 | 0.153881E+10 | 0.462721E+09 | 0.00 | 0.00 |
March | 0.358603E+10 | 0.267536E+10 | 0.286982E+10 | 0.200955E+10 | 0.860268E+09 | 0.00 | 0.00 |
April | 0.375234E+10 | 0.218361E+10 | 0.300214E+10 | 0.175518E+10 | 0.124696E+10 | 0.00 | 0.00 |
May | 0.540614E+10 | 0.162225E+10 | 0.396056E+10 | 0.210878E+10 | 0.185178E+10 | 0.00 | 0.00 |
June | 0.718168E+10 | 0.136702E+10 | 0.479615E+10 | 0.334499E+10 | 0.145116E+10 | 0.00 | 0.00 |
July | 0.643465E+10 | 0.133240E+10 | 0.429654E+10 | 0.255637E+10 | 0.174018E+10 | 0.00 | 0.00 |
August | 0.637568E+10 | 0.149911E+10 | 0.427407E+10 | 0.305076E+10 | 0.122332E+10 | 0.00 | 0.00 |
September | 0.461339E+10 | 0.192765E+10 | 0.324911E+10 | 0.217504E+10 | 0.107407E+10 | 0.00 | 0.00 |
October | 0.298312E+10 | 0.290561E+10 | 0.240032E+10 | 0.169832E+10 | 0.702004E+09 | 0.00 | 0.00 |
November | 0.199224E+10 | 0.297281E+10 | 0.168637E+10 | 0.121855E+10 | 0.467822E+09 | 0.00 | 0.00 |
December | 0.121893E+10 | 0.399670E+10 | 0.128270E+10 | 0.850563E+09 | 0.432139E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.474672E+11 | 0.289853E+11 | 0.353382E+11 | 0.233910E+11 | 0.119472E+11 | 0.00 | 0.00 |
Minimum of Months | 0.121893E+10 | 0.133240E+10 | 0.128270E+10 | 0.850563E+09 | 0.432139E+09 | 0.00 | 0.00 |
Maximum of Months | 0.718168E+10 | 0.399670E+10 | 0.479615E+10 | 0.334499E+10 | 0.185178E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.196386E+11 | 0.593607E+11 | 0.422793E+10 | 0.301757E+10 | 0.121036E+10 | 0.00 | 0.00 |
February | 0.269130E+11 | 0.621771E+11 | 0.557134E+10 | 0.428333E+10 | 0.128801E+10 | 0.00 | 0.00 |
March | 0.412221E+11 | 0.400597E+11 | 0.798827E+10 | 0.559368E+10 | 0.239460E+10 | 0.00 | 0.00 |
April | 0.447859E+11 | 0.282613E+11 | 0.835659E+10 | 0.488562E+10 | 0.347097E+10 | 0.00 | 0.00 |
May | 0.595676E+11 | 0.143923E+11 | 0.110244E+11 | 0.586988E+10 | 0.515451E+10 | 0.00 | 0.00 |
June | 0.827322E+11 | 0.272454E+11 | 0.133503E+11 | 0.931094E+10 | 0.403936E+10 | 0.00 | 0.00 |
July | 0.791174E+11 | 0.301315E+11 | 0.119596E+11 | 0.711576E+10 | 0.484386E+10 | 0.00 | 0.00 |
August | 0.754322E+11 | 0.329910E+11 | 0.118971E+11 | 0.849192E+10 | 0.340516E+10 | 0.00 | 0.00 |
September | 0.471119E+11 | 0.299336E+11 | 0.904404E+10 | 0.605433E+10 | 0.298971E+10 | 0.00 | 0.00 |
October | 0.317538E+11 | 0.339040E+11 | 0.668141E+10 | 0.472735E+10 | 0.195406E+10 | 0.00 | 0.00 |
November | 0.232668E+11 | 0.424845E+11 | 0.469408E+10 | 0.339188E+10 | 0.130220E+10 | 0.00 | 0.00 |
December | 0.152153E+11 | 0.854253E+11 | 0.357046E+10 | 0.236758E+10 | 0.120288E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.546757E+12 | 0.486366E+12 | 0.983655E+11 | 0.651098E+11 | 0.332557E+11 | 0.00 | 0.00 |
Minimum of Months | 0.152153E+11 | 0.143923E+11 | 0.357046E+10 | 0.236758E+10 | 0.120288E+10 | 0.00 | 0.00 |
Maximum of Months | 0.827322E+11 | 0.854253E+11 | 0.133503E+11 | 0.931094E+10 | 0.515451E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.36 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.29 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.52 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.46 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.25 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.79 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.35 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.31 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.37 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.25 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.97 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.74 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.90 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.49 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.92 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.63 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.90 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.36 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.05 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.73 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.10 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.94 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.97 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.36 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.4 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.45 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.30 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.22 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.9 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.22 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.55 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.98 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 8.00 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.50 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.87 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.65 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.75 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.80 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.54 | 196.33 | 4.00 |
September | 14.95 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.73 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.33 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.94 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.55 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.75 | 29.40 | 16.00 | 9.80 | 20.54 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.50 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.73 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.65 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.92 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.90 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.40 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.06 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.06 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.65 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.988466E+09 | -901547005.0 | 0.00 | 0.00 | 744.00 | 0.00 | -86918937.5 | 58.99 | 0.00 | 0.00 |
February | 0.917068E+09 | -838405195.8 | 0.00 | 0.00 | 672.00 | 0.00 | -78662440.5 | 58.98 | 0.00 | 0.00 |
March | 0.105040E+10 | -965400630.2 | 0.00 | 0.00 | 744.00 | 0.00 | -85003109.5 | 58.99 | 0.00 | 0.00 |
April | 0.943737E+09 | -861666719.0 | 0.00 | 0.00 | 720.00 | 0.00 | -82069908.5 | 58.99 | 0.00 | 0.00 |
May | 0.925063E+09 | -846616428.6 | 0.00 | 0.00 | 744.00 | 0.00 | -78446843.1 | 58.99 | 0.00 | 0.00 |
June | 0.865632E+09 | -793587785.8 | 0.00 | 0.00 | 720.00 | 0.00 | -72044294.2 | 58.99 | 0.00 | 0.00 |
July | 0.806223E+09 | -732136034.4 | 0.00 | 0.00 | 744.00 | 0.00 | -74086923.3 | 58.99 | 0.00 | 0.00 |
August | 0.848148E+09 | -773650614.1 | 0.00 | 0.00 | 744.00 | 0.00 | -74497741.3 | 58.99 | 0.00 | 0.00 |
September | 0.805589E+09 | -733235858.4 | 0.00 | 0.00 | 720.00 | 0.00 | -72352937.8 | 58.99 | 0.00 | 0.00 |
October | 0.851689E+09 | -771067522.3 | 0.00 | 0.00 | 744.00 | 0.00 | -80621859.4 | 58.99 | 0.00 | 0.00 |
November | 0.869040E+09 | -786507526.7 | 0.00 | 0.00 | 720.00 | 0.00 | -82532192.9 | 58.99 | 0.00 | 0.00 |
December | 0.953110E+09 | -866022503.1 | 0.00 | 0.00 | 744.00 | 0.00 | -87087722.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.108242E+11 | -0.986984E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -954324910.3 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.805589E+09 | -965400630.2 | 0.00 | 0.00 | 672.00 | 0.00 | -87087722.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.105040E+10 | -732136034.4 | 0.00 | 0.00 | 744.00 | 0.00 | -72044294.2 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.92 | 0.58 | 29-JAN-11:20 | 109.75 | 0.00 | 0.00 | 2.50 | 93.09 | 0.00 | 0.00 | 0.00 |
February | 245.50 | 0.89 | 0.50 | 19-FEB-13:30 | 129.97 | 0.00 | 0.00 | 5.67 | 110.94 | 0.00 | 0.00 | 1.67 |
March | 296.17 | 0.81 | 0.50 | 01-MAR-11:50 | 188.10 | 0.00 | 0.00 | 49.83 | 1218.12 | 0.00 | 0.00 | 54.67 |
April | 296.67 | 0.75 | 0.50 | 03-APR-11:30 | 254.72 | 0.00 | 0.00 | 103.33 | 201.24 | 0.00 | 0.00 | 61.50 |
May | 415.33 | 0.72 | 0.50 | 01-MAY-10:09 | 306.61 | 0.00 | 0.00 | 200.83 | 692.87 | 0.00 | 0.00 | 137.83 |
June | 421.50 | 0.75 | 0.50 | 01-JUN-10:20 | 263.68 | 0.00 | 0.00 | 145.33 | 2354.29 | 0.00 | 0.00 | 107.33 |
July | 430.33 | 0.73 | 0.50 | 02-JUL-10:09 | 293.24 | 0.00 | 0.00 | 182.00 | 1352.31 | 0.00 | 0.00 | 132.17 |
August | 394.50 | 0.77 | 0.50 | 01-AUG-10:39 | 233.85 | 0.00 | 0.00 | 93.33 | 189.21 | 0.00 | 0.00 | 62.00 |
September | 354.00 | 0.79 | 0.50 | 01-SEP-11:00 | 214.71 | 0.00 | 0.00 | 80.33 | 174.53 | 0.00 | 0.00 | 48.33 |
October | 262.67 | 0.84 | 0.50 | 01-OCT-11:00 | 168.36 | 0.00 | 0.00 | 18.33 | 142.25 | 0.00 | 0.00 | 5.17 |
November | 257.67 | 0.90 | 0.50 | 01-NOV-11:30 | 122.29 | 0.00 | 0.00 | 1.33 | 105.44 | 0.00 | 0.00 | 0.17 |
December | 251.17 | 0.92 | 0.67 | 04-DEC-11:09 | 109.10 | 0.00 | 0.00 | 0.00 | 92.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3902.00 | 0.80 | 212.61 | 0.00 | 0.00 | 882.83 | 656.02 | 0.00 | 0.00 | 610.83 | ||
Minimum of Months | 245.50 | 0.72 | 0.50 | 109.10 | 0.00 | 0.00 | 0.00 | 92.91 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 430.33 | 0.92 | 0.67 | 306.61 | 0.00 | 0.00 | 200.83 | 2354.29 | 0.00 | 0.00 | 137.83 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.79 | 0.50 | 02-JAN-10:30 | 145.25 | 10.00 | 0.00 | 62.33 | 688.53 | 13.65 | 4.50 | 52.17 |
February | 245.50 | 0.74 | 0.50 | 01-FEB-10:39 | 172.93 | 11.28 | 0.00 | 53.83 | 530.74 | 15.22 | 15.00 | 43.17 |
March | 296.17 | 0.65 | 0.50 | 01-MAR-10:39 | 991.38 | 15.24 | 28.67 | 209.33 | 1798.35 | 16.68 | 46.17 | 142.00 |
April | 296.67 | 0.61 | 0.50 | 03-APR-09:39 | 327.97 | 14.38 | 0.00 | 251.33 | 276.91 | 18.21 | 83.33 | 213.67 |
May | 415.33 | 0.60 | 0.50 | 01-MAY-07:40 | 2204.91 | 16.44 | 55.17 | 314.17 | 925.26 | 19.39 | 129.33 | 284.83 |
June | 421.50 | 0.61 | 0.50 | 01-JUN-06:30 | 1649.94 | 14.75 | 19.17 | 301.67 | 3310.31 | 20.56 | 120.00 | 283.50 |
July | 430.33 | 0.61 | 0.50 | 01-JUL-08:50 | 2868.06 | 15.73 | 36.67 | 315.33 | 2198.37 | 18.38 | 122.83 | 276.17 |
August | 394.50 | 0.61 | 0.50 | 01-AUG-07:19 | 991.20 | 13.93 | 0.00 | 284.33 | 1931.18 | 19.41 | 113.50 | 229.33 |
September | 354.00 | 0.64 | 0.50 | 01-SEP-09:09 | 278.25 | 13.42 | 0.00 | 230.67 | 519.33 | 18.68 | 85.33 | 203.83 |
October | 262.67 | 0.66 | 0.50 | 01-OCT-09:09 | 223.58 | 12.81 | 0.00 | 163.83 | 399.32 | 17.69 | 55.00 | 124.00 |
November | 257.67 | 0.74 | 0.50 | 01-NOV-08:00 | 163.53 | 11.05 | 0.00 | 68.67 | 370.24 | 16.60 | 30.33 | 62.33 |
December | 251.17 | 0.77 | 0.50 | 01-DEC-10:09 | 145.98 | 10.65 | 0.00 | 57.83 | 232.40 | 15.25 | 11.83 | 45.33 |
Annual Sum or Average | 3902.00 | 0.66 | 1011.28 | 13.65 | 139.67 | 2313.33 | 1246.90 | 17.81 | 817.17 | 1960.33 | ||
Minimum of Months | 245.50 | 0.60 | 0.50 | 145.25 | 10.00 | 0.00 | 53.83 | 232.40 | 13.65 | 4.50 | 43.17 | |
Maximum of Months | 430.33 | 0.79 | 0.50 | 2868.06 | 16.44 | 55.17 | 315.33 | 3310.31 | 20.56 | 129.33 | 284.83 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.84 | 0.78 | 01-JAN-14:09 | 1264.16 | 23.05 | 88.67 | 121.17 | 1470.92 | 24.43 | 108.50 | 167.83 |
February | 245.50 | 0.84 | 0.78 | 01-FEB-10:00 | 1874.20 | 23.02 | 76.17 | 106.17 | 2257.93 | 25.89 | 96.50 | 173.50 |
March | 296.17 | 0.82 | 0.78 | 01-MAR-10:00 | 430.38 | 17.52 | 24.00 | 144.50 | 2661.50 | 26.11 | 145.00 | 274.83 |
April | 296.67 | 0.81 | 0.78 | 03-APR-09:50 | 478.17 | 17.50 | 11.17 | 204.83 | 2486.17 | 25.20 | 149.50 | 321.17 |
May | 415.33 | 0.81 | 0.78 | 01-MAY-07:49 | 515.87 | 17.26 | 3.00 | 317.17 | 2482.13 | 23.61 | 214.00 | 363.83 |
June | 421.50 | 0.80 | 0.78 | 01-JUN-06:10 | 485.89 | 16.91 | 0.17 | 316.33 | 2478.69 | 21.75 | 184.67 | 367.83 |
July | 430.33 | 0.81 | 0.78 | 01-JUL-13:00 | 495.53 | 17.04 | 2.50 | 319.00 | 2056.05 | 22.79 | 200.83 | 369.67 |
August | 394.50 | 0.81 | 0.78 | 01-AUG-06:30 | 437.63 | 17.01 | 1.67 | 241.50 | 2836.22 | 23.54 | 156.00 | 359.00 |
September | 354.00 | 0.82 | 0.78 | 01-SEP-11:39 | 747.18 | 18.52 | 45.83 | 198.33 | 2404.57 | 25.75 | 172.17 | 289.67 |
October | 262.67 | 0.82 | 0.78 | 01-OCT-11:39 | 1322.59 | 21.28 | 56.00 | 143.17 | 2146.54 | 25.36 | 109.50 | 266.17 |
November | 257.67 | 0.83 | 0.78 | 01-NOV-09:20 | 1120.78 | 23.70 | 86.17 | 116.67 | 1356.45 | 25.01 | 98.67 | 187.50 |
December | 251.17 | 0.83 | 0.78 | 01-DEC-10:30 | 916.98 | 23.26 | 78.00 | 111.83 | 1120.37 | 24.53 | 90.67 | 181.00 |
Annual Sum or Average | 3902.00 | 0.82 | 772.66 | 19.18 | 473.33 | 2340.67 | 2207.11 | 24.29 | 1726.00 | 3322.00 | ||
Minimum of Months | 245.50 | 0.80 | 0.78 | 430.38 | 16.91 | 0.17 | 106.17 | 1120.37 | 21.75 | 90.67 | 167.83 | |
Maximum of Months | 430.33 | 0.84 | 0.78 | 1874.20 | 23.70 | 88.67 | 319.00 | 2836.22 | 26.11 | 214.00 | 369.67 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.458063E+10 | 29148.91 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.497431E+10 | 29148.91 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.375194E+10 | 29148.91 | 01-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.246144E+10 | 29148.91 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.375744E+09 | 29148.91 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3342844.18 | 4421.64 | 29-JUN-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 202888.63 | 676.30 | 17-JUL-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2319648.64 | 6510.30 | 18-AUG-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15682048.67 | 4094.64 | 22-SEP-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158061E+10 | 29148.91 | 16-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.297832E+10 | 29148.91 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.598333E+10 | 29148.91 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.267079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 202888.63 | 676.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.598333E+10 | 29148.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.169532E+11 | 99766.43 | 01-JAN-07:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.190447E+11 | 99766.43 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.118778E+11 | 99766.43 | 02-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.755973E+10 | 99766.43 | 03-APR-02:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.609421E+09 | 69818.45 | 03-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.501895E+10 | 99766.43 | 25-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102707E+11 | 99766.43 | 01-NOV-03:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.262658E+11 | 99766.43 | 06-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.976002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.262658E+11 | 99766.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.426219E+11 | 89357.12 | 05-JAN-19:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.592393E+11 | 122340.01 | 12-FEB-05:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.278513E+11 | 134546.65 | 19-MAR-06:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143298E+11 | 64121.06 | 17-APR-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4112491.84 | 2464.19 | 03-MAY-03:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.990944E+10 | 72772.51 | 31-OCT-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.246594E+11 | 112376.45 | 30-NOV-05:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.929103E+11 | 149985.33 | 21-DEC-17:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271525E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.929103E+11 | 149985.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 50.88 | 50.88 | 0.08 | 20-JAN-14:50 | 0.08 | 0.00 |
February | 0.00 | 0.00 | 70.82 | 70.82 | 0.12 | 18-FEB-14:20 | 0.12 | 0.00 |
March | 0.00 | 0.00 | 91425417.15 | 91425417.15 | 3649.33 | 14-MAR-13:00 | 3649.33 | 0.00 |
April | 0.00 | 0.00 | 9262356.58 | 9262356.58 | 1190.16 | 20-APR-13:00 | 1190.16 | 0.00 |
May | 0.00 | 0.00 | 0.126664E+10 | 0.126402E+10 | 21582.89 | 31-MAY-18:41 | 20503.12 | 0.00 |
June | 0.00 | 0.00 | 0.831621E+10 | 0.797393E+10 | 23899.53 | 21-JUN-17:15 | 16551.35 | 0.00 |
July | 0.00 | 0.00 | 0.860142E+10 | 0.804141E+10 | 24524.88 | 31-JUL-17:15 | 11857.54 | 0.00 |
August | 0.00 | 0.00 | 0.863778E+10 | 0.820726E+10 | 23981.27 | 04-AUG-01:25 | 11799.44 | 0.00 |
September | 0.00 | 0.00 | 0.533667E+10 | 0.529191E+10 | 21826.29 | 02-SEP-19:58 | 19393.49 | 0.00 |
October | 0.00 | 0.00 | 0.398750E+09 | 0.398750E+09 | 20647.12 | 07-OCT-17:15 | 20647.12 | 0.00 |
November | 0.00 | 0.00 | 13735099.81 | 13735099.81 | 1870.72 | 07-NOV-15:00 | 1870.72 | 0.00 |
December | 0.00 | 0.00 | 89428.49 | 89428.49 | 147.32 | 02-DEC-15:00 | 147.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.326720E+11 | 0.312918E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 50.88 | 50.88 | 0.08 | 0.08 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.863778E+10 | 0.820726E+10 | 24524.88 | 20647.12 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.348595E+09 | 0.348595E+09 | 9221.42 | 31-MAY-14:50 | 9221.42 | 0.00 |
June | 0.00 | 0.00 | 0.163248E+11 | 0.159302E+11 | 71734.51 | 18-JUN-09:45 | 50844.35 | 0.00 |
July | 0.00 | 0.00 | 0.168524E+11 | 0.163615E+11 | 73842.44 | 30-JUL-11:05 | 47772.43 | 0.00 |
August | 0.00 | 0.00 | 0.161921E+11 | 0.158830E+11 | 68352.54 | 03-AUG-17:11 | 56225.06 | 0.00 |
September | 0.00 | 0.00 | 0.737181E+10 | 0.734640E+10 | 65123.68 | 03-SEP-12:55 | 60827.68 | 0.00 |
October | 0.00 | 0.00 | 0.113506E+09 | 0.113506E+09 | 9107.88 | 11-OCT-14:00 | 9107.88 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.572032E+11 | 0.559832E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.168524E+11 | 0.163615E+11 | 73842.44 | 60827.68 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.544291E+09 | 0.05 | 419.44 | 01-JAN-00:03 | 0.09 |
February | 0.576454E+09 | 0.05 | 419.44 | 01-FEB-00:03 | 0.09 |
March | 0.419923E+09 | 0.04 | 419.44 | 01-MAR-00:50 | 0.09 |
April | 0.211314E+09 | 0.02 | 419.44 | 01-APR-19:20 | 0.09 |
May | 1761649.23 | 0.00 | 419.44 | 03-MAY-03:03 | 0.09 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.107964E+09 | 0.01 | 419.44 | 25-OCT-03:30 | 0.09 |
November | 0.331442E+09 | 0.03 | 419.44 | 01-NOV-00:10 | 0.09 |
December | 0.753432E+09 | 0.06 | 419.44 | 01-DEC-00:03 | 0.09 |
Annual Sum or Average | 0.294658E+10 | 0.02 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.753432E+09 | 0.06 | 419.44 | 0.09 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156601E+10 | 0.59 | 1501.19 | 14-JAN-08:20 | 1.12 |
February | 0.145989E+10 | 0.64 | 1501.19 | 07-FEB-11:30 | 1.12 |
March | 0.167005E+10 | 0.59 | 1501.19 | 01-MAR-07:30 | 1.12 |
April | 0.153763E+10 | 0.54 | 1501.19 | 01-APR-06:20 | 1.12 |
May | 0.156145E+10 | 0.45 | 1501.19 | 24-MAY-15:40 | 1.11 |
June | 0.180957E+10 | 0.63 | 1501.19 | 16-JUN-10:20 | 1.11 |
July | 0.176385E+10 | 0.59 | 1501.19 | 01-JUL-06:40 | 1.12 |
August | 0.191343E+10 | 0.65 | 1501.19 | 01-AUG-09:40 | 1.12 |
September | 0.165345E+10 | 0.54 | 1501.19 | 27-SEP-09:10 | 1.12 |
October | 0.150916E+10 | 0.46 | 1501.19 | 02-OCT-07:00 | 1.11 |
November | 0.146821E+10 | 0.48 | 1501.19 | 18-NOV-08:00 | 1.12 |
December | 0.159716E+10 | 0.64 | 1501.19 | 06-DEC-10:00 | 1.12 |
Annual Sum or Average | 0.195099E+11 | 0.57 | |||
Minimum of Months | 0.145989E+10 | 0.45 | 1501.19 | 1.11 | |
Maximum of Months | 0.191343E+10 | 0.65 | 1501.19 | 1.12 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.338177E+10 | 0.96 | 6106.66 | 01-JAN-07:22 | 1.73 |
February | 0.330788E+10 | 1.00 | 6106.66 | 01-FEB-06:01 | 1.73 |
March | 0.329275E+10 | 0.84 | 6106.66 | 02-MAR-04:02 | 1.73 |
April | 0.286043E+10 | 0.72 | 6106.66 | 03-APR-02:52 | 1.73 |
May | 0.255164E+10 | 0.44 | 4273.56 | 03-MAY-05:01 | 1.73 |
June | 0.275799E+10 | 0.49 | 6106.66 | 14-JUN-17:08 | 1.73 |
July | 0.268943E+10 | 0.47 | 6106.66 | 01-JUL-17:06 | 1.73 |
August | 0.279642E+10 | 0.47 | 6106.66 | 10-AUG-17:06 | 1.72 |
September | 0.249552E+10 | 0.43 | 5924.91 | 04-SEP-13:33 | 1.70 |
October | 0.269066E+10 | 0.55 | 6106.66 | 25-OCT-05:01 | 1.73 |
November | 0.290084E+10 | 0.79 | 6106.66 | 01-NOV-03:42 | 1.73 |
December | 0.386368E+10 | 1.05 | 6106.66 | 06-DEC-06:01 | 1.73 |
Annual Sum or Average | 0.355890E+11 | 0.68 | |||
Minimum of Months | 0.249552E+10 | 0.43 | 4273.56 | 1.70 | |
Maximum of Months | 0.386368E+10 | 1.05 | 6106.66 | 1.73 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.156601E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.145989E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.169140E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.153985E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.185634E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.379197E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.378726E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.394564E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.288362E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.160032E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.147147E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.159718E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.271910E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.145989E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.394564E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.338177E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.330788E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.329275E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.286043E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.264605E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.708330E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.711678E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.701332E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.441305E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.272050E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.290084E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.386368E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.506003E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.264605E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.711678E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.156601E+10 | 50.88 | 0.458063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145989E+10 | 70.82 | 0.497431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167005E+10 | 91425417.15 | 0.375194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153763E+10 | 9262356.58 | 0.246144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156145E+10 | 0.126664E+10 | 0.375744E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.180957E+10 | 0.831621E+10 | 3342844.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176385E+10 | 0.860142E+10 | 202888.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.191343E+10 | 0.863778E+10 | 2319648.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165345E+10 | 0.533667E+10 | 15682048.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150916E+10 | 0.398750E+09 | 0.158061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146821E+10 | 13735099.81 | 0.297832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159716E+10 | 89428.49 | 0.598333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195099E+11 | 0.326720E+11 | 0.267079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145989E+10 | 50.88 | 202888.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.191343E+10 | 0.863778E+10 | 0.598333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.338177E+10 | 0.00 | 0.169532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.330788E+10 | 0.00 | 0.190447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.329275E+10 | 0.00 | 0.118778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.286043E+10 | 0.00 | 0.755973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.255164E+10 | 0.348595E+09 | 0.609421E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.275799E+10 | 0.160109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.268943E+10 | 0.164920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.279642E+10 | 0.158533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.249552E+10 | 0.721392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.269066E+10 | 0.113506E+09 | 0.501895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.290084E+10 | 0.00 | 0.102707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.386368E+10 | 0.00 | 0.262658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.355890E+11 | 0.560322E+11 | 0.976002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.249552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.386368E+10 | 0.164920E+11 | 0.262658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.156601E+10 | 0.00 | 0.00 | 0.00 | 12.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145989E+10 | 0.00 | 0.00 | 0.00 | 17.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167005E+10 | 0.00 | 0.00 | 0.00 | 21353418.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153763E+10 | 0.00 | 0.00 | 0.00 | 2226352.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156145E+10 | 0.00 | 0.00 | 0.00 | 0.294898E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.180957E+10 | 0.00 | 0.00 | 0.00 | 0.198240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176385E+10 | 0.00 | 0.00 | 0.00 | 0.202341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.191343E+10 | 0.00 | 0.00 | 0.00 | 0.203221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165345E+10 | 0.00 | 0.00 | 0.00 | 0.123017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150916E+10 | 0.00 | 0.00 | 0.00 | 91164518.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146821E+10 | 0.00 | 0.00 | 0.00 | 3263581.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159716E+10 | 0.00 | 0.00 | 0.00 | 21671.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195099E+11 | 0.00 | 0.00 | 0.00 | 0.768111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145989E+10 | 0.00 | 0.00 | 0.00 | 12.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.191343E+10 | 0.00 | 0.00 | 0.00 | 0.203221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.338177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.330788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.329275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.286043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.255164E+10 | 0.00 | 0.00 | 0.00 | 94404056.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.275799E+10 | 0.00 | 0.00 | 0.00 | 0.432531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.268943E+10 | 0.00 | 0.00 | 0.00 | 0.442735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.279642E+10 | 0.00 | 0.00 | 0.00 | 0.421690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.249552E+10 | 0.00 | 0.00 | 0.00 | 0.191752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.269066E+10 | 0.00 | 0.00 | 0.00 | 29839345.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.290084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.386368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.355890E+11 | 0.00 | 0.00 | 0.00 | 0.150113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.249552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.386368E+10 | 0.00 | 0.00 | 0.00 | 0.442735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.335180E+09 | 0.00 | 0.00 | 1912.62 | 0.00 | 0.147078E+10 | 11917200.59 | 0.00 | 0.13 |
February | 0.255788E+09 | 0.00 | 0.00 | 1188.39 | 0.00 | 0.146571E+10 | 10462831.18 | 0.00 | 0.13 |
March | 0.364905E+09 | 0.00 | 0.00 | 320605.44 | 0.00 | 0.116032E+10 | 0.422118E+09 | 0.00 | 0.23 |
April | 0.493069E+09 | 0.00 | 0.00 | 162994.99 | 0.00 | 0.774247E+09 | 0.350971E+09 | 0.00 | 0.21 |
May | 0.235242E+09 | 1973949.52 | 0.00 | 2539351.02 | 0.00 | 90230471.01 | 0.187082E+10 | 0.00 | 0.52 |
June | 8218454.73 | 0.209867E+09 | 0.00 | 5482175.30 | 0.00 | 0.00 | 0.142363E+10 | 0.00 | 0.62 |
July | 9215944.71 | 0.243308E+09 | 0.00 | 5912881.92 | 108935.30 | 0.00 | 0.105321E+10 | 0.00 | 0.57 |
August | 21422963.21 | 0.242146E+09 | 0.00 | 7402312.66 | 0.00 | 0.00 | 0.186231E+10 | 0.00 | 0.66 |
September | 62512695.89 | 31270451.26 | 0.00 | 6602948.85 | 0.00 | 5680709.64 | 0.215935E+10 | 0.00 | 0.71 |
October | 0.425145E+09 | 0.00 | 0.00 | 1590806.64 | 0.00 | 0.512096E+09 | 0.151839E+10 | 0.00 | 0.35 |
November | 0.488788E+09 | 0.00 | 0.00 | 168771.37 | 0.00 | 0.103332E+10 | 0.280132E+09 | 0.00 | 0.18 |
December | 0.244232E+09 | 0.00 | 0.00 | 4084.32 | 0.00 | 0.173604E+10 | 21004613.35 | 0.00 | 0.13 |
Annual Sum or Average | 0.294372E+10 | 0.728565E+09 | 0.00 | 30190033.51 | 108935.30 | 0.824843E+10 | 0.109843E+11 | 0.00 | 0.37 |
Minimum of Months | 8218454.73 | 0.00 | 0.00 | 1188.39 | 0.00 | 0.00 | 10462831.18 | 0.00 | 0.13 |
Maximum of Months | 0.493069E+09 | 0.243308E+09 | 0.00 | 7402312.66 | 108935.30 | 0.173604E+10 | 0.215935E+10 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.371465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169688E+10 | 0.00 | 0.00 | 0.17 |
February | 0.359918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161107E+10 | 0.00 | 0.00 | 0.18 |
March | 0.378251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115332E+10 | 0.00 | 0.00 | 0.19 |
April | 0.357027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432532E+09 | 0.00 | 0.00 | 0.18 |
May | 0.331685E+10 | 736420.18 | 0.00 | 383485.05 | 0.00 | 6135717.86 | 0.231237E+09 | 0.00 | 0.20 |
June | 0.199537E+09 | 0.280737E+09 | 0.00 | 15762864.53 | 13234.34 | 0.00 | 0.317908E+10 | 0.00 | 0.44 |
July | 82981095.56 | 0.238121E+09 | 0.00 | 16086185.33 | 0.00 | 0.00 | 0.272174E+10 | 0.00 | 0.41 |
August | 0.219514E+09 | 0.230445E+09 | 0.00 | 20434689.03 | 0.00 | 0.00 | 0.409377E+10 | 0.00 | 0.42 |
September | 0.103093E+10 | 7859662.41 | 0.00 | 11267690.76 | 0.00 | 0.00 | 0.332330E+10 | 0.00 | 0.39 |
October | 0.389885E+10 | 0.00 | 0.00 | 207963.43 | 0.00 | 0.870203E+09 | 0.244911E+09 | 0.00 | 0.19 |
November | 0.385306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102824E+10 | 0.00 | 0.00 | 0.17 |
December | 0.279580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321814E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.300641E+11 | 0.757900E+09 | 0.00 | 64142878.12 | 13234.34 | 0.100165E+11 | 0.137940E+11 | 0.00 | 0.26 |
Minimum of Months | 82981095.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.389885E+10 | 0.280737E+09 | 0.00 | 20434689.03 | 13234.34 | 0.321814E+10 | 0.409377E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.519294E+12 | 0.334514E+11 | 0.00 | 0.722941E+10 | 0.205671E+11 |
February | 0.665898E+12 | 0.545304E+11 | 0.00 | 0.694222E+10 | 0.257261E+11 |
March | 0.841132E+12 | 0.556219E+11 | 0.00 | 0.688350E+10 | 0.143208E+11 |
April | 0.869891E+12 | 0.498272E+11 | 0.00 | 0.562125E+10 | 0.824868E+10 |
May | 0.108608E+13 | 0.328151E+11 | 0.00 | 0.575674E+10 | 0.247940E+10 |
June | 0.119844E+13 | 0.316455E+11 | 0.00 | 0.461296E+10 | 0.309504E+11 |
July | 0.110885E+13 | 0.410231E+11 | 0.00 | 0.364115E+10 | 0.319047E+11 |
August | 0.110650E+13 | 0.393646E+11 | 0.00 | 0.603573E+10 | 0.310801E+11 |
September | 0.821928E+12 | 0.392070E+11 | 0.00 | 0.677895E+10 | 0.158644E+11 |
October | 0.672098E+12 | 0.511606E+11 | 0.00 | 0.747139E+10 | 0.619440E+10 |
November | 0.556799E+12 | 0.391003E+11 | 0.00 | 0.668370E+10 | 0.123725E+11 |
December | 0.408126E+12 | 0.771544E+11 | 0.00 | 0.801523E+10 | 0.375978E+11 |
Annual Sum or Average | 0.985503E+13 | 0.544902E+12 | 0.00 | 0.756722E+11 | 0.237307E+12 |
Minimum of Months | 0.408126E+12 | 0.316455E+11 | 0.00 | 0.364115E+10 | 0.247940E+10 |
Maximum of Months | 0.119844E+13 | 0.771544E+11 | 0.00 | 0.801523E+10 | 0.375978E+11 |