Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2023-10-16 10:43:07
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:07
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 436.68 | 90.31 | 90.31 |
Net Site Energy | 436.68 | 90.31 | 90.31 |
Total Source Energy | 1371.95 | 283.75 | 283.75 |
Net Source Energy | 1371.95 | 283.75 | 283.75 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 5.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 73.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 86.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 49.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 23.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 431.39 | 5.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 5.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 73.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 86.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 61.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 21.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 27.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 23.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 5.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 73.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 86.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 61.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 49.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 23.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 30.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 30.26 | 1.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 89.22 | 1.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 30.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 30.26 | 1.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 89.22 | 1.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 431.391 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 431.391 | 100.00 |
Total On-Site and Utility Electric Sources | 431.391 | 100.00 |
Total Electricity End Uses | 431.391 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 7.67 |
Time Setpoint Not Met During Occupied Cooling | 27.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2735.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:07
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 68.38 |
Skylight-Roof Ratio [%] | 1.49 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 6.9682 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 7.4271 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.5521 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8362 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8362 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 6.9682 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 7.4271 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.5521 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.8362 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.8362 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.8362 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:07
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUN-15:00 | 02-JAN-06:10 | - | - | - | - | - | - | - | - | - | - | 11-OCT-11:30 |
Heating | 0.00 | 32125.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 20512.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5145.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5533.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1575.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 42802.01 | 32125.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 32125.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 20512.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 5145.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 3228.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1575.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:07
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 5.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 232.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 274.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 195.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 156.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 74.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1366.21 | 5.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 48.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 56.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 32.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 282.56 | 1.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 48.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 56.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 32.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 282.56 | 1.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:07
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.29 |
ZONE2 FINE STORAGE DIRECT AIR | 3.44 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 1.58 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 1.58 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 58672.31 |
PSZ-OFFICE HEATING COIL | 29126.58 |
PSZ-FINE STORAGE HEATING COIL | 99272.97 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 58672.32 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.29 | 1.29 | 1.29 | 1.29 | 1.29 | 1.29 | 1.00 | 1.000000 | 1.29 |
PSZ-FINE STORAGE | 3.44 | 3.44 | 3.44 | 3.44 | 3.44 | 3.44 | 1.00 | 1.00 | 3.44 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.29 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 3.44 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.29 | 1423.61 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.44 | 3676.39 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.29 | 1.29 | 1.29 | 0.848641 | 23242.63 | 29126.58 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 3.44 | 3.44 | 3.44 | 2.27 | 76930.36 | 99272.97 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.29 | 0.642910 | 0.857213 | 23242.63 | 11621.32 | 0.800690 | 0.800690 |
PSZ-FINE STORAGE COOLING COIL | 3.44 | 1.72 | 2.29 | 76930.36 | 38465.18 | 0.734800 | 0.734800 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:07
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:07
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:07
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 6.968 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 15.042 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 7.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.427 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.552 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 6.111 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1650.627 | 6.968 | 129.474 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1650.627 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 10348.979 | 7.427 | 344.966 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10348.979 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 11383.888 | 3.552 | 164.984 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11383.888 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2405 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5892 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.6534 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 1.134 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 1.134 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.158 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.697 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.431 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7826 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7826 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.77015739E-08 | 0.38457199E-13 | 0.23136523E-13 | 0.0000000 |
2 | 1 | -5.2160498 | 0.48395528E-04 | -0.66612159E-04 | 0.14765390E-08 |
3 | 0 | 5.4565497 | 0.24045158 | 0.24056658 | |
4 | 2 | 0.53319589E-11 | 0.95168195E-16 | 0.18684196E-15 | 0.0000000 |
5 | 1 | -5.2159738 | 0.43009049E-04 | -0.27188221E-04 | 0.68723469E-11 |
6 | 0 | 5.8052090 | 0.58919217 | 0.58926237 | |
7 | 4 | 0.74747876E-12 | 0.20825084E-15 | -0.25659737E-14 | 0.12362927E-15 |
8 | 3 | -0.37328678E-03 | 0.45238042E-06 | -0.54038165E-04 | 0.14344535E-12 |
9 | 2 | 1.7123825 | 0.10013958E-01 | 1.1198054 | -0.71564441E-04 |
10 | 1 | -7.1648294 | 0.26145347 | -16.966117 | 0.32817431 |
11 | 0 | 5.8918369 | 0.16754891 | 16.285382 | |
12 | 4 | 0.65556131E-12 | 0.57298371E-15 | -0.14028959E-14 | 0.12439065E-15 |
13 | 3 | -0.34087882E-03 | 0.75102955E-06 | -0.49042705E-04 | 0.12583838E-12 |
14 | 2 | 1.6337693 | 0.17263784E-01 | 1.0601096 | -0.65347397E-04 |
15 | 1 | -7.2734424 | 0.46143774 | -16.581274 | 0.31301327 |
16 | 0 | 6.4190060 | 0.30028979 | 16.300205 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.14028959E-14 | 0.57298371E-15 | 0.65556131E-12 | 0.12439065E-15 |
85 | 3 | -0.49042705E-04 | 0.75102955E-06 | -0.34087882E-03 | 0.12583838E-12 |
86 | 2 | 1.0601096 | 0.17263784E-01 | 1.6337693 | -0.65347397E-04 |
87 | 1 | -16.581274 | 0.46143774 | -7.2734424 | 0.31301327 |
88 | 0 | 16.300205 | 0.30028979 | 6.4190060 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.454_SHGC_SOUTH_0.249 | 34 | 1 | VerySmooth | 2.580 | 2.580 | 1.000 | 0.250 | ||
2 | NONRESWINDOW_U_0.454_SHGC_NORTH_0.249 | 35 | 1 | VerySmooth | 2.580 | 2.580 | 1.000 | 0.250 | ||
3 | NONRESWINDOW_U_0.454_SHGC_EAST_0.249 | 36 | 1 | VerySmooth | 2.580 | 2.580 | 1.000 | 0.250 | ||
4 | NONRESWINDOW_U_0.454_SHGC_WEST_0.249 | 37 | 1 | VerySmooth | 2.580 | 2.580 | 1.000 | 0.250 | ||
5 | SKYLIGHT_U_0.65_SHGC_0.3 | 38 | 1 | VerySmooth | 3.695 | 3.695 | 1.000 | 0.302 | ||
6 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | 39 | 1 | VerySmooth | 5.108 | 5.108 | 1.000 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.61639E-002 | 0.16038 | 0.61778 | 0.61778 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12084 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.61639E-002 | 0.16038 | 0.61778 | 0.61778 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12084 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.61639E-002 | 0.16038 | 0.61778 | 0.61778 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12084 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.61639E-002 | 0.16038 | 0.61778 | 0.61778 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12084 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.19440 | 0.51093 | 0.51093 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.96142E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 0.12500 | 0.12500 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | CurtainWall | 3.575 | 0.301 | 0.402 |
2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.867 | 0.549 | 0.401 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.331 | 7.274E-004 | 4.751E-004 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.7190E-005 |
2 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1891E-004 |
3 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.7841E-005 |
4 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4613E-004 |
5 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.5933E-005 |
6 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.4217E-004 |
7 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.8648E-005 |
8 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.6551E-004 |
9 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6039E-004 |
10 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.0626E-004 |
11 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3512E-004 |
12 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.3320E-004 |
13 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4812E-004 |
14 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.8152E-004 |
15 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3945E-004 |
16 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4949E-004 |
17 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5979E-004 |
18 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4386E-004 |
19 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0141E-004 |
20 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5523E-004 |
21 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.3720E-004 |
22 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2060E-004 |
23 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.9614E-004 |
24 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8929E-005 |
25 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.8592E-004 |
26 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.5069E-005 |
27 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1955E-004 |
28 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9566E-005 |
29 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0144E-003 |
30 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.4845E-005 |
31 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3502E-003 |
32 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.2167E-005 |
33 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.8133E-004 |
34 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3973E-005 |
35 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.9779E-004 |
36 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.5980E-005 |
37 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.7023E-004 |
38 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0673E-005 |
39 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0462E-004 |
40 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7378E-005 |
41 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.6296E-004 |
42 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5706E-005 |
43 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.9361E-004 |
44 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6771E-005 |
45 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.4898E-004 |
46 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5639E-005 |
47 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8419E-004 |
48 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5748E-005 |
49 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2077E-003 |
50 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7330E-005 |
51 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4658E-003 |
52 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8772E-005 |
53 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.8442E-004 |
54 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6144E-005 |
55 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4212E-004 |
56 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5828E-005 |
57 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.2762E-003 |
58 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.8855E-005 |
59 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.6273E-003 |
60 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2022E-005 |
61 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1020E-003 |
62 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.2270E-005 |
63 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1230E-003 |
64 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7635E-005 |
65 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7406E-003 |
66 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0298E-004 |
67 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6654E-003 |
68 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1186E-004 |
69 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4389E-003 |
70 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1066E-005 |
71 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5923E-003 |
72 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3189E-005 |
73 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9237E-004 |
74 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.2929E-004 |
75 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.9477E-004 |
76 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6245E-004 |
77 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.2784E-004 |
78 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5224E-004 |
79 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6412E-003 |
80 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.4188E-005 |
81 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0178E-004 |
82 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6420E-004 |
83 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6741E-004 |
84 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0403E-003 |
85 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8926E-004 |
86 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.9938E-004 |
87 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3714E-004 |
88 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8629E-004 |
89 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5236E-005 |
90 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1439E-003 |
91 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.3951E-005 |
92 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5261E-003 |
93 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.2004E-005 |
94 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7424E-003 |
95 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1086E-004 |
96 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.9267E-004 |
97 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.4970E-005 |
98 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0106E-003 |
99 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0985E-005 |
100 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0200E-003 |
101 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0099E-005 |
102 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6822E-003 |
103 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.9227E-005 |
104 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.1977E-003 |
105 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.3102E-005 |
106 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.3174E-004 |
107 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9582E-005 |
108 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.7927E-004 |
109 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8940E-005 |
110 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0809E-003 |
111 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7155E-005 |
112 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2526E-003 |
113 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3050E-005 |
114 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9165E-005 |
115 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8696E-005 |
116 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0687E-005 |
117 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6903E-005 |
118 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6802E-005 |
119 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4598E-005 |
120 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5286E-005 |
121 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6688E-005 |
122 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9086E-005 |
123 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8803E-005 |
124 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3361E-005 |
125 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4942E-005 |
126 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1803E-005 |
127 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1685E-005 |
128 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2542E-005 |
129 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2526E-005 |
130 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9757E-005 |
131 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8494E-005 |
132 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8832E-005 |
133 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7904E-005 |
134 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9533E-005 |
135 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4582E-005 |
136 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1042E-005 |
137 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7605E-004 |
138 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3693E-004 |
139 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9781E-004 |
140 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5223E-004 |
141 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3003E-004 |
142 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0238E-004 |
143 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2514E-005 |
144 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3080E-005 |
145 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0771E-005 |
146 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5339E-004 |
147 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2392E-005 |
148 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9585E-004 |
149 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7027E-005 |
150 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5640E-004 |
151 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4916E-005 |
152 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6240E-005 |
153 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7263E-005 |
154 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4725E-005 |
155 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3022E-005 |
156 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4620E-005 |
157 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.3522E-005 |
158 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4510E-005 |
159 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4899E-005 |
160 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1079E-005 |
161 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2596E-004 |
162 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6337E-005 |
163 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6223E-004 |
164 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7775E-005 |
165 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4262E-004 |
166 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1880E-005 |
167 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2500E-005 |
168 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7738E-005 |
169 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0338E-004 |
170 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.6841E-004 |
171 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0327E-004 |
172 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0495E-003 |
173 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1052E-004 |
174 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0654E-004 |
175 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0532E-005 |
176 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7293E-004 |
177 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1476E-004 |
178 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5244E-004 |
179 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6975E-004 |
180 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7886E-004 |
181 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4498E-004 |
182 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1797E-004 |
183 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5069E-004 |
184 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0290E-004 |
185 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0014E-004 |
186 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0705E-005 |
187 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0924E-004 |
188 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0943E-005 |
189 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.0097E-004 |
190 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0814E-005 |
191 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5061E-004 |
192 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8433E-005 |
193 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3026E-004 |
194 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7097E-005 |
195 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3633E-004 |
196 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6512E-005 |
197 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2494E-004 |
198 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7682E-005 |
199 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0473E-005 |
200 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3210E-005 |
201 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1556E-003 |
202 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.2489E-005 |
203 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3213E-003 |
204 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.9648E-005 |
205 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0750E-003 |
206 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2640E-005 |
207 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2387E-004 |
208 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6113E-005 |
209 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4835E-004 |
210 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9179E-004 |
211 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2850E-004 |
212 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1228E-004 |
213 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2611E-004 |
214 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4450E-004 |
215 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2445E-004 |
216 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5215E-004 |
217 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7275E-004 |
218 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8632E-005 |
219 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7210E-004 |
220 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7443E-005 |
221 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0222E-004 |
222 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0254E-005 |
223 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2708E-004 |
224 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5686E-005 |
225 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4070E-004 |
226 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8797E-003 |
227 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3409E-004 |
228 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2177E-003 |
229 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7625E-004 |
230 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5309E-003 |
231 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2726E-004 |
232 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9459E-004 |
233 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7841E-004 |
234 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8635E-005 |
235 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6531E-004 |
236 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6962E-005 |
237 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4218E-004 |
238 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0738E-005 |
239 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9961E-004 |
240 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7482E-005 |
241 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1838E-003 |
242 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3654E-005 |
243 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1902E-003 |
244 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7346E-005 |
245 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6005E-003 |
246 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0099E-004 |
247 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6165E-003 |
248 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3274E-005 |
249 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0103E-003 |
250 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1103E-004 |
251 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.8145E-004 |
252 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9083E-004 |
253 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4262E-003 |
254 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9213E-004 |
255 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6195E-003 |
256 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2024E-004 |
257 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5537E-004 |
258 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8735E-003 |
259 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3953E-004 |
260 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9284E-003 |
261 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1164E-004 |
262 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4192E-003 |
263 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0001E-004 |
264 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6530E-003 |
265 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3894E-004 |
266 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7054E-005 |
267 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2172E-004 |
268 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5232E-005 |
269 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8300E-004 |
270 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8620E-005 |
271 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9852E-004 |
272 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7461E-005 |
273 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3090E-004 |
274 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.4608E-004 |
275 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1266E-004 |
276 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2855E-004 |
277 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6283E-004 |
278 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1214E-003 |
279 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9891E-004 |
280 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6031E-003 |
281 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0868E-004 |
282 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2759E-005 |
283 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2589E-004 |
284 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5411E-005 |
285 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5192E-004 |
286 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.5140E-005 |
287 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5919E-003 |
288 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3045E-005 |
289 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7982E-004 |
290 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7523E-004 |
291 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9406E-004 |
292 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3847E-004 |
293 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8465E-004 |
294 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9257E-004 |
295 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5949E-003 |
296 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1554E-004 |
297 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1119E-005 |
298 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8907E-004 |
299 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7457E-005 |
300 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3438E-004 |
301 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2368E-005 |
302 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0872E-004 |
303 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2574E-004 |
304 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7337E-004 |
305 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3947E-004 |
306 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4651E-004 |
307 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9453E-004 |
308 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2269E-004 |
309 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5213E-004 |
310 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6565E-004 |
311 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1039E-004 |
312 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4748E-004 |
313 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6269E-005 |
314 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6322E-005 |
315 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8620E-005 |
316 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3836E-005 |
317 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5636E-005 |
318 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3950E-005 |
319 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1671E-005 |
320 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7584E-005 |
321 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1693E-005 |
322 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4549E-005 |
323 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8951E-005 |
324 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2905E-005 |
325 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0079E-004 |
326 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5110E-005 |
327 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2556E-004 |
328 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5637E-005 |
329 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0445E-005 |
330 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1494E-004 |
331 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2329E-005 |
332 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.3784E-005 |
333 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2905E-005 |
334 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.6784E-005 |
335 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9741E-005 |
336 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6869E-004 |
337 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0473E-004 |
338 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8824E-005 |
339 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5890E-005 |
340 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6808E-005 |
341 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7361E-005 |
342 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1553E-005 |
343 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4732E-004 |
344 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0119E-004 |
345 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9727E-005 |
346 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1944E-005 |
347 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2231E-005 |
348 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0648E-005 |
349 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5809E-005 |
350 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1838E-005 |
351 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9684E-005 |
352 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3161E-005 |
353 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3945E-004 |
354 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7465E-005 |
355 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9604E-004 |
356 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1445E-005 |
357 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6610E-004 |
358 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0354E-005 |
359 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0983E-004 |
360 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5702E-005 |
361 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0377E-004 |
362 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4703E-005 |
363 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5582E-005 |
364 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0629E-005 |
365 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0201E-005 |
366 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2864E-005 |
367 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4724E-004 |
368 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8139E-005 |
369 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 3.2667E-003 |
370 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.9627E-004 |
371 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.8691E-003 |
372 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.5378E-004 |
373 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.7745E-003 |
374 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.4291E-004 |
375 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.7866E-003 |
376 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1636E-004 |
377 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.0023E-004 |
378 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.6552E-003 |
379 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.6474E-004 |
380 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.0378E-003 |
381 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.5000E-004 |
382 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.9473E-003 |
383 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.1270E-004 |
384 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.3974E-003 |
385 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.0075E-003 |
386 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.2119E-004 |
387 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.2642E-003 |
388 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.7509E-004 |
389 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.5362E-003 |
390 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.3325E-004 |
391 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.2429E-003 |
392 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.9254E-004 |
393 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.0942E-003 |
394 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.2153E-004 |
395 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.3025E-003 |
396 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.7527E-004 |
397 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.4287E-003 |
398 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.3306E-004 |
399 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.2428E-003 |
400 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.9254E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11824.39121 | 14189.26945 | 1.07152 | 1.28582 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 39.47000 | 5.62903E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 7261.71711 | 8714.06054 | 0.22437 | 0.26925 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 0.50000 | 4.31558E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 40533.51611 | 48640.21934 | 2.86311 | 3.43573 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 17204.69872 | 20645.63846 | 0.44811 | 0.53773 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 0.50000 | 4.31558E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 48893.59634 | 58672.31561 | 1.31592 | 1.57910 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 18571.10 | 1.28582 | 1.28582 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 7921.06 | 0.26925 | 0.26925 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 62019.87 | 3.43573 | 3.43573 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 21463.22 | 0.53773 | 0.53773 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.28582 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.43573 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.57910 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 1.57910 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 58672.31304 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 58672.31561 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.28582 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.28582 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.28582 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.28582 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.28582 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.28582 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.43573 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.43573 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.43573 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.43573 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.43573 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.43573 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.28582 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.43573 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.28582 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.28582 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1423.60635 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.28582 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.28582 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.28582 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.84864 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.28582 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.64291 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.85721 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23242.63000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11621.31500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80069 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80069 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23242.63000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29126.57646 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 29126.57646 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.43573 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.43573 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3676.39012 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.43573 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.43573 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.43573 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.26758 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.43573 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.71786 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.29049 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 76930.36000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 38465.18000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73480 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73480 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 76930.36000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 99272.97139 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 99272.97139 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 22244.6 | 11.61 | 11.34 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 74261.1 | 10.96 | 10.71 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 8.9514710001E-002 | 9.8082238592E-002 | Pass | Pass | 1.0933826298E-002 | 0.1126309758 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.2087181785 | 0.2406019081 | Pass | Pass | 0.1053324966 | 0.5895302679 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 6.9930962591E-002 | 5.5346671713E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:07
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 10356.97 | 450.56 | 0.00 | 10.98 | 324.53 | 11143.09 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:07
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 2 | |||
Feb | 34.00 | 28 | |||
Mar | 40.00 | 18 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 81.00 | 18 | |||
Aug | 71.00 | 20 | |||
Sep | 27.00 | 12 | |||
Oct | 9.00 | 6 | |||
Nov | 35.00 | 14 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:07
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.233 | 0.240 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.545 | 0.589 | 3204.84 | 3157.28 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.892 | 1.134 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.892 | 1.134 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.454_SHGC_WEST_0.249 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.580 | 0.250 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.454_SHGC_WEST_0.249 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.580 | 0.250 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.454_SHGC_NORTH_0.249 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.580 | 0.250 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.454_SHGC_NORTH_0.249 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.580 | 0.250 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 86.04 | 4.247 | 0.429 | 0.370 | |||||||||||||||||
North Total or Average | 6.51 | 2.580 | 0.250 | 0.250 | |||||||||||||||||
Non-North Total or Average | 79.53 | 4.384 | 0.444 | 0.380 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:07
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:07
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 6.9682 | 236.88 | 1650.63 | LightsWired | LTG_SCH_OFFICE | 52.33 | 168.00 | 33.75 | 0.0000 | Y | 10.46 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 7.4271 | 1393.41 | 10348.98 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 19.45 | 0.0000 | Y | 37.78 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.5521 | 3204.84 | 11383.89 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 18.05 | 0.0000 | Y | 38.57 |
Interior Lighting Total | 4.8362 | 4835.13 | 23383.49 | 86.80 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10348.98 | 2587.24 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10348.98 | 2587.24 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 11383.89 | 2845.97 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 11383.89 | 2845.97 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.29 | 1650.63 | 478.68 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.10 | 1650.63 | 165.06 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 123.84 | AstronomicalClock | - | 41.79 | 41.79 | 0.97 | |
EXTERIOR_LIGHTS_B | 4305.62 | AstronomicalClock | - | 83.79 | 62.79 | 50.75 | |
EXTERIOR_LIGHTS_C | 1091.36 | AstronomicalClock | - | 83.79 | 49.01 | 10.04 | |
Exterior Lighting Total | 5520.82 | 61.76 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:07
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23242.63 | 18610.14 | 4632.49 | 0.80 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 76930.36 | 56528.43 | 20401.93 | 0.73 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 22244.6 | 11.61 | 11.34 | ||||
PSZ-FINE STORAGE COOLING COIL | 74261.1 | 10.96 | 10.71 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 58672.31 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 29126.58 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 99272.97 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 1.58 | 146.72 | 92.91 | 1.00 | 3.74 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.29 | 1423.61 | 1107.16 | 1.00 | 1.35 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 3.44 | 3676.39 | 1070.05 | 1.00 | 1.25 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:07
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11824.39 | 14189.27 | 59.90 | 1.072 | 1.286 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 23.90 | 23.90 | 0.00816 | 39.47 | 0.00563 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 40533.52 | 48640.22 | 34.91 | 2.863 | 3.436 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 26.70 | 26.70 | 0.00801 | 40.67 | 0.00563 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 40.11 | 0.00572 | 40.67 | 0.00563 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 7261.72 | 8714.06 | 36.79 | 0.224 | 0.269 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00797 | 0.50 | 0.00432 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 17204.70 | 20645.64 | 14.82 | 0.448 | 0.538 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 15.56 | 15.56 | 0.00701 | 0.50 | 0.00432 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 48893.60 | 58672.32 | 18.31 | 1.316 | 1.579 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00641 | 0.50 | 0.00432 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.29 | 1.29 | 0.27 | 0.27 | 1.2858 | 1.2858 | 1.2858 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.44 | 3.44 | 0.54 | 0.54 | 3.4357 | 3.4357 | 3.4357 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 58672.313 | 58672.313 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 58672.31 | 58672.31 | 1.579103 | 10.00 | 7.87 | 0.00640516 | 43.33 | 21.00 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 10.00 | 0.00640516 | 76.3506 | 58672.32 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 23242.630 | 18610.141 | 1.285820 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 11621.32 | 11621.31 | 0.857213 | 26.16 | 15.69 | 0.00795467 | 12.00 | 10.37 | 0.00795467 | 39.82 | 0.00562958 | 18.28 | 11.9322 | 23.90 | 0.00815594 | 40.1218 | 11806.22 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 29126.576 | 29126.576 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 29126.58 | 29126.58 | 1.285820 | 19.38 | 13.01 | 0.00767536 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 7.9548 | 21.10 | 0.00796573 | 46.4673 | 7261.72 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 76930.360 | 56528.429 | 3.435730 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 38465.18 | 38465.18 | 2.290487 | 29.40 | 16.58 | 0.00771713 | 12.00 | 10.13 | 0.00771713 | 40.80 | 0.00563111 | 18.58 | 18.5424 | 26.70 | 0.00801161 | 33.3718 | 40505.37 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 99272.971 | 99272.971 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 99272.97 | 99272.97 | 3.435727 | 13.70 | 9.78 | 0.00668124 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 12.3616 | 15.56 | 0.00701493 | 58.0279 | 17204.70 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:07
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 58672.313 | 58672.313 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 1.579103 | 1.72626619 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 58672.31 | 58672.31 | 1.0000 | 1.72626619 | 1.579103 | 10.00 | 7.87 | 0.00640516 | 26185.4 | 43.33 | 21.00 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 58672.31 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 10.00 | 0.00640516 | 10.00 | 0.00640516 | 76.3506 | 58672.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23242.630 | 18610.141 | 1.285820 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6273 | 1004.8586 | 1.0932 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.285820 | 1.40565050 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | Sensible | 11621.32 | 11621.31 | 1.0000 | 0.93710066 | 0.857213 | 26.16 | 15.69 | 0.00795467 | 46569.0 | 12.00 | 10.37 | 0.00795467 | 32129.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11621.32 | 39.82 | 0.00562958 | 18.28 | 0.10228463 | 11.9322 | 23.90 | 0.00815594 | 23.90 | 0.00815594 | 40.1218 | 11806.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29126.576 | 29126.576 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.285820 | 1.40565050 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 29126.58 | 29126.58 | 1.0000 | 1.40565050 | 1.285820 | 19.38 | 13.01 | 0.00767536 | 38945.0 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29126.58 | 0.50 | 0.00431558 | 0.50 | 0.10228463 | 7.9548 | 21.01 | 0.00796573 | 21.10 | 0.00796573 | 46.4673 | 7261.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 76930.360 | 56528.429 | 3.435730 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.1858 | 1004.8586 | 1.0932 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.435727 | 3.75591670 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 38465.18 | 38465.18 | 1.0000 | 2.50394678 | 2.290487 | 29.40 | 16.58 | 0.00771713 | 49268.8 | 12.00 | 10.13 | 0.00771713 | 31530.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38465.18 | 40.80 | 0.00563111 | 18.58 | 0.42471127 | 18.5424 | 26.70 | 0.00801161 | 26.70 | 0.00801161 | 33.3718 | 40505.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 99272.971 | 99272.971 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.435727 | 3.75591670 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | Sensible | 99272.97 | 99272.97 | 1.0000 | 3.75591670 | 3.435727 | 13.70 | 9.78 | 0.00668124 | 30642.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 99272.97 | 0.50 | 0.00431558 | 0.50 | 0.42471127 | 12.3616 | 15.56 | 0.00701493 | 15.56 | 0.00701493 | 58.0279 | 17204.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:07
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.29 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 3.44 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 1753.50 | 1689.17 | 377.33 |
ZONE2 FINE STORAGE | 2720.33 | 2673.17 | 1894.50 |
ZONE3 BULK STORAGE | 2918.50 | 3353.83 | 2732.33 |
Facility | 2968.17 | 3543.67 | 2735.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 7.67 | 30.33 | 7.67 | 27.67 |
ZONE2 FINE STORAGE | 2.33 | 195.33 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 10.00 | 225.50 | 7.67 | 27.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:07
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.622 | 0.403 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.572 | 0.200 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.102 | 0.000 | 1.463 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:07
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.55 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2244228.28 | 0.00 | 2244228.28 | 2048805.51 | 4293033.79 | 3225648.14 | 5633.76 | 2383.00 | 743.24 | 0.04 |
ZONE2 FINE STORAGE | 6232781.75 | 0.00 | 6232781.75 | 5439996.83 | 11672778.58 | 13393694.68 | 5623.98 | 2771.44 | 364.58 | 40.05 |
ZONE3 BULK STORAGE | 0.00 | 0.35E+09 | 0.35E+09 | 26280419.40 | 0.37E+09 | 30805497.77 | 6037.59 | 8.59 | 2713.82 | 5116.00 |
Total Facility | 8477010.02 | 0.35E+09 | 0.36E+09 | 33769221.75 | 0.39E+09 | 47424840.58 | 7374.65 | 2956.42 | 3635.01 | 5116.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1714 | 0.0000 | 0.1714 | 0.1111 | 0.2826 | 0.1023 | 509.80 | 2383.00 | 743.20 |
ZONE2 FINE STORAGE | 0.4577 | 0.0000 | 0.4577 | 0.1601 | 0.6178 | 0.4247 | 539.78 | 2771.44 | 324.78 |
ZONE3 BULK STORAGE | 0.0000 | 13.6132 | 13.6132 | 0.9694 | 14.5826 | 0.9768 | 2209.99 | 5.44 | 1420.56 |
Total Facility | 0.6291 | 13.6132 | 14.2423 | 1.2407 | 15.4830 | 1.5038 | 2250.65 | 2953.27 | 2314.57 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2682000.86 | 0.00 | 2682000.86 | 3225648.14 | 5632.87 | 0.17 | 3126.96 | 0.04 |
PSZ-FINE STORAGE | 7448639.48 | 0.00 | 7448639.48 | 13393694.68 | 5620.52 | 0.33 | 3139.15 | 40.05 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2049 | 0.0000 | 0.2049 | 0.1023 | 508.91 | 0.17 | 3126.92 |
PSZ-FINE STORAGE | 0.5470 | 0.0000 | 0.5470 | 0.4247 | 536.32 | 0.33 | 3099.35 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2789.42 | 340.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 3033.72 | 115.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2161 | 0.4181 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6214 | 1.1265 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:07
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 446 |
Defaulted Fields | 391 |
Fields with Defaults | 1172 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:07
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 431.39 | 1550.86 | 01-JAN-11:00 | 42802.01 | 28-JUN-16:00 |
Electricity:Building | 245.14 | 1069.86 | 01-JAN-11:00 | 19979.94 | 10-AUG-08:10 |
Electricity:Zone:ZONE1 OFFICE | 39.62 | 520.87 | 01-JAN-00:10 | 2846.16 | 28-NOV-16:30 |
Electricity:SpaceType:GENERAL | 223.31 | 1069.86 | 01-JAN-11:00 | 18412.05 | 31-OCT-08:10 |
InteriorLights:Electricity | 86.80 | 599.99 | 01-JAN-11:00 | 8376.88 | 31-OCT-08:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.46 | 51.00 | 01-JAN-00:10 | 1011.11 | 28-NOV-16:30 |
InteriorLights:Electricity:SpaceType:GENERAL | 86.80 | 599.99 | 01-JAN-11:00 | 8376.88 | 31-OCT-08:10 |
LightsWired:InteriorLights:Electricity | 86.80 | 599.99 | 01-JAN-11:00 | 8376.88 | 31-OCT-08:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.46 | 51.00 | 01-JAN-00:10 | 1011.11 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 86.80 | 599.99 | 01-JAN-11:00 | 8376.88 | 31-OCT-08:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 37.78 | 299.97 | 01-JAN-00:10 | 3679.95 | 06-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 37.78 | 299.97 | 01-JAN-00:10 | 3679.95 | 06-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 37.78 | 299.97 | 01-JAN-00:10 | 3679.95 | 06-DEC-16:00 |
Electricity:Zone:ZONE3 BULK STORAGE | 167.74 | 249.02 | 01-JAN-11:00 | 13806.78 | 17-OCT-15:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 38.57 | 249.02 | 01-JAN-11:00 | 3896.80 | 06-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 38.57 | 249.02 | 01-JAN-11:00 | 3896.80 | 06-DEC-16:00 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 49.37 | 0.00 | 01-JAN-00:40 | 5913.03 | 30-JUN-16:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 21.83 | 0.00 | 01-JAN-00:10 | 2305.29 | 28-AUG-05:10 |
Ventilation (simple):Fans:Electricity | 21.83 | 0.00 | 01-JAN-00:10 | 2305.29 | 28-AUG-05:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 21.83 | 0.00 | 01-JAN-00:10 | 2305.29 | 28-AUG-05:10 |
ElectricityPurchased:Facility | 431.39 | 1550.86 | 01-JAN-11:00 | 42802.01 | 28-JUN-16:00 |
ElectricityPurchased:Plant | 431.39 | 1550.86 | 01-JAN-11:00 | 42802.01 | 28-JUN-16:00 |
Cogeneration:ElectricityPurchased | 431.39 | 1550.86 | 01-JAN-11:00 | 42802.01 | 28-JUN-16:00 |
General:Cogeneration:ElectricityPurchased | 431.39 | 1550.86 | 01-JAN-11:00 | 42802.01 | 28-JUN-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 431.39 | 1550.86 | 01-JAN-11:00 | 42802.01 | 28-JUN-16:00 |
ElectricityNet:Plant | 431.39 | 1550.86 | 01-JAN-11:00 | 42802.01 | 28-JUN-16:00 |
Cogeneration:ElectricityNet | 431.39 | 1550.86 | 01-JAN-11:00 | 42802.01 | 28-JUN-16:00 |
General:Cogeneration:ElectricityNet | 431.39 | 1550.86 | 01-JAN-11:00 | 42802.01 | 28-JUN-16:00 |
Electricity:HVAC | 101.12 | 0.00 | 01-JAN-00:40 | 25124.16 | 30-JUN-16:10 |
General:Fans:Electricity | 27.55 | 0.00 | 01-JAN-00:40 | 3607.74 | 30-JUN-16:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 73.57 | 0.00 | 01-JAN-00:10 | 21516.42 | 30-JUN-16:10 |
General:Cooling:Electricity | 73.57 | 0.00 | 01-JAN-00:10 | 21516.42 | 30-JUN-16:10 |
ExteriorLights:Electricity | 61.76 | 0.00 | 01-JAN-07:30 | 5520.82 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 61.76 | 0.00 | 01-JAN-07:30 | 5520.82 | 01-JAN-06:10 |
Electricity:Plant | 23.38 | 481.00 | 05-JAN-06:10 | 1787.25 | 21-JAN-12:10 |
WaterSystems:Electricity | 23.38 | 481.00 | 05-JAN-06:10 | 1787.25 | 21-JAN-12:10 |
Water Heater:WaterSystems:Electricity | 23.38 | 481.00 | 05-JAN-06:10 | 1787.25 | 21-JAN-12:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 5.29 | 0.00 | 01-JAN-00:40 | 32125.49 | 02-JAN-06:10 |
NaturalGas:HVAC | 5.29 | 0.00 | 01-JAN-00:40 | 32125.49 | 02-JAN-06:10 |
Heating:NaturalGas | 5.29 | 0.00 | 01-JAN-00:40 | 32125.49 | 02-JAN-06:10 |
General:Heating:NaturalGas | 5.29 | 0.00 | 01-JAN-00:40 | 32125.49 | 02-JAN-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-OCT-11:30 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-OCT-11:30 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-OCT-11:30 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-OCT-11:30 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-OCT-11:30 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-OCT-11:30 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-OCT-11:30 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-OCT-11:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 464.76 | 0.00 | 01-JAN-00:40 | 113792.73 | 30-JUN-16:10 |
EnergyTransfer:Building | 211.94 | 0.00 | 01-JAN-00:40 | 50820.30 | 30-JUN-16:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 61.63 | 0.00 | 01-JAN-00:10 | 15629.91 | 02-JAN-06:10 |
Heating:EnergyTransfer | 6.50 | 0.00 | 01-JAN-00:40 | 23664.25 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 3.23 | 0.00 | 01-JAN-00:10 | 15629.91 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 6.50 | 0.00 | 01-JAN-00:40 | 23664.25 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 3.23 | 0.00 | 01-JAN-00:10 | 15629.91 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 205.44 | 0.00 | 01-JAN-00:10 | 50820.30 | 30-JUN-16:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 58.40 | 0.00 | 01-JAN-00:10 | 14971.96 | 30-JUN-16:10 |
General:Cooling:EnergyTransfer | 205.44 | 0.00 | 01-JAN-00:10 | 50820.30 | 30-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 58.40 | 0.00 | 01-JAN-00:10 | 14971.96 | 30-JUN-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 150.31 | 0.00 | 01-JAN-00:40 | 37339.66 | 30-JUN-16:00 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 3.27 | 0.00 | 01-JAN-00:40 | 15853.93 | 01-JAN-07:30 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 3.27 | 0.00 | 01-JAN-00:40 | 15853.93 | 01-JAN-07:30 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 147.04 | 0.00 | 01-JAN-00:10 | 37339.66 | 30-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 147.04 | 0.00 | 01-JAN-00:10 | 37339.66 | 30-JUN-16:00 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 252.82 | 0.00 | 01-JAN-00:40 | 62972.42 | 30-JUN-16:10 |
HeatingCoils:EnergyTransfer | 3.58 | 0.00 | 01-JAN-00:40 | 23367.58 | 02-JAN-06:10 |
CoolingCoils:EnergyTransfer | 249.25 | 0.00 | 01-JAN-00:10 | 62972.42 | 30-JUN-16:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:07
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 3.228 | -58.400 | 0.000 | 0.000 | 9.348 | 10.456 | 29.165 | 13.007 | 0.000 | 6.674 | 0.419 | 0.000 | -5.399 | 0.000 | -8.497 | -0.000 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 3.268 | -147.038 | 0.000 | 0.000 | 20.192 | 37.779 | 0.000 | 38.569 | 0.000 | 12.117 | 69.919 | 0.000 | -12.930 | 0.000 | -21.876 | -0.001 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 35.469 | 38.566 | 107.344 | 762.112 | 0.000 | 56.410 | 0.039 | 0.000 | -154.986 | 0.000 | -441.558 | -403.356 |
Total Facility | 0.000 | 0.000 | 6.496 | -205.438 | 0.000 | 0.000 | 65.009 | 86.801 | 136.508 | 813.688 | 0.000 | 75.201 | 70.377 | 0.000 | -173.315 | 0.000 | -471.931 | -403.357 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 22-MAY-05:01 | 0.00 | 0.00 | 0.00 | -29999.49 | 0.00 | 0.00 | 83.11 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 30577.59 | 0.00 | -519.22 | 0.00 | -743.50 | 0.00 |
ZONE2 FINE STORAGE | 17-SEP-15:02 | 0.00 | 0.00 | 0.00 | -66678.24 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 2956.40 | 0.00 | 2005.12 | 61416.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-JUL-05:05 | 0.00 | 0.00 | 0.00 | -71940.99 | 0.00 | 0.00 | 546.29 | 849.01 | 2600.55 | 0.00 | 0.00 | 152.47 | 91956.55 | 0.00 | -22041.15 | 0.00 | -2122.72 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 19-DEC-06:01 | 0.00 | 0.00 | 29399.71 | 0.00 | 0.00 | 0.00 | 139.78 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -579.78 | 0.00 | -843.55 | -28717.67 |
ZONE2 FINE STORAGE | 01-JAN-07:23 | 0.00 | 0.00 | 47561.88 | 0.00 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1145.57 | 0.00 | -3053.75 | -43662.53 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 01-JAN-07:23 | 0.00 | 0.00 | 47561.88 | 0.00 | 0.00 | 0.00 | 0.00 | 848.19 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -15798.29 | 0.00 | -17249.59 | -15832.06 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:07
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2858 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.2858 | 0.0795 | 1.0000 | Not calculated | 0.1023 | 0.0795 | ||
PSZ-FINE STORAGE | 3.4357 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.4357 | 0.1236 | 1.0000 | Not calculated | 0.4247 | 0.1236 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2858 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.2858 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0795 | ||
PSZ-FINE STORAGE | 3.4357 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.4357 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1236 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2858 | 1.2858 | 1.2858 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.4357 | 3.4357 | 3.4357 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2858 | 1.2858 | 1.2858 | 1.2858 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.4357 | 3.4357 | 3.4357 | 3.4357 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2858 | 1.2858 | 1.2858 | No | 0.1023 | 0.3799 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.4357 | 3.4357 | 3.4357 | No | 0.4247 | 0.7898 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2858 | 1.2858 | 1.2858 | 1.2858 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.4357 | 3.4357 | 3.4357 | 3.4357 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:07
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 7.67 |
Number of hours cooling loads not met | 27.67 |
Number of hours not met | 35.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 5.29 | 32125.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 73.57 | 21516.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 86.80 | 8376.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 61.76 | 5520.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 21.83 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 27.55 | 3607.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 23.38 | 1787.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 431.39 |
Natural Gas | 0.00 | 5.29 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 436.68 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 17.95 |
Space Heating | 0.00 |
Space Cooling | 15.22 |
Fans (All) | 10.21 |
Service Water Heating | 4.84 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 89.22 |
Subtotal | 89.22 |
Natural Gas [MJ/m2] | |
Space Heating | 1.09 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 1.09 |
Subtotal | 1.09 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 19.88 |
Space Heating | 1.21 |
Space Cooling | 16.85 |
Fans (All) | 11.31 |
Service Water Heating | 5.35 |
Receptacle Equipment | 31.26 |
Miscellaneous | 14.14 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2729. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:07
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 7145.83 | 1614.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7903.50 | 856.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 4524.17 | 3440.83 | 794.00 | 1.00 | 0.00 |
Min | 4524.17 | 856.50 | 0.00 | 0.00 | 0.00 |
Max | 7903.50 | 3440.83 | 794.00 | 1.00 | 0.00 |
Average | 6524.50 | 1970.50 | 264.67 | 0.33 | 0.00 |
Sum | 19573.50 | 5911.50 | 794.00 | 1.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 72802.50 | 9916.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 90323.83 | 70287.17 | 30536.50 | 45.50 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 90323.83 | 70287.17 | 30536.50 | 45.50 | 0.00 |
Average | 65384.44 | 26734.56 | 10178.83 | 15.17 | 0.00 |
Sum | 196153.33 | 80203.67 | 30536.50 | 45.50 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 7732.17 | 1027.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7762.83 | 997.17 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 5955.33 | 2761.00 | 43.67 | 0.00 | 0.00 |
Min | 5955.33 | 997.17 | 0.00 | 0.00 | 0.00 |
Max | 7762.83 | 2761.00 | 43.67 | 0.00 | 0.00 |
Average | 7150.11 | 1595.33 | 14.56 | 0.00 | 0.00 |
Sum | 21450.33 | 4786.00 | 43.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 32920.00 | 107.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 70836.50 | 11882.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 119067.00 | 69800.17 | 2325.83 | 0.00 | 0.00 |
Min | 32920.00 | 107.00 | 0.00 | 0.00 | 0.00 |
Max | 119067.00 | 69800.17 | 2325.83 | 0.00 | 0.00 |
Average | 74274.50 | 27263.22 | 775.28 | 0.00 | 0.00 |
Sum | 222823.50 | 81789.67 | 2325.83 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:07
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:07
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Environment
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Environment
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103230E+10 | 4342.39 | 31-JAN-16:40 | 29.00 | 10.73 | 0.596039E+09 | 768.96 | 20-JAN-16:40 | 29.00 | 10.73 |
February | 0.352683E+09 | 2529.65 | 01-FEB-16:00 | 16.00 | 7.03 | 0.519411E+09 | 768.97 | 18-FEB-15:00 | 22.00 | 14.07 |
March | 0.130957E+10 | 5042.20 | 18-MAR-16:00 | 27.20 | 11.10 | 0.649037E+09 | 768.99 | 18-MAR-10:09 | 27.20 | 11.10 |
April | 0.526117E+10 | 29447.38 | 24-APR-05:02 | 15.17 | 4.62 | 0.633436E+09 | 769.01 | 14-APR-15:00 | 15.17 | 4.62 |
May | 0.714450E+10 | 29999.99 | 22-MAY-05:01 | 15.17 | 5.60 | 0.659872E+09 | 769.04 | 31-MAY-15:00 | 37.00 | 13.71 |
June | 0.945811E+10 | 28273.37 | 21-JUN-05:01 | 18.00 | 8.30 | 0.660422E+09 | 769.08 | 01-JUN-15:20 | 18.00 | 8.30 |
July | 0.903332E+10 | 28040.01 | 01-JUL-05:01 | 18.83 | 6.90 | 0.635229E+09 | 769.09 | 22-JUL-15:00 | 38.00 | 18.60 |
August | 0.942645E+10 | 26545.45 | 24-AUG-05:01 | 19.83 | 9.70 | 0.685974E+09 | 769.08 | 30-AUG-15:20 | 38.00 | 18.03 |
September | 0.807266E+10 | 26027.57 | 16-SEP-05:01 | 19.90 | 12.48 | 0.635014E+09 | 769.08 | 07-SEP-13:39 | 19.90 | 12.48 |
October | 0.485225E+10 | 26750.90 | 06-OCT-05:01 | 19.00 | 10.35 | 0.630338E+09 | 769.08 | 02-OCT-14:09 | 19.00 | 10.35 |
November | 0.197625E+10 | 6436.21 | 01-NOV-16:00 | 28.00 | 15.72 | 0.593898E+09 | 769.02 | 14-NOV-15:30 | 20.00 | 15.52 |
December | 0.481718E+09 | 3085.88 | 01-DEC-15:30 | 23.30 | 10.04 | 0.567284E+09 | 768.96 | 01-DEC-14:00 | 23.30 | 10.04 |
Annual Sum or Average | 0.584010E+11 | 0.746595E+10 | ||||||||
Minimum of Months | 0.352683E+09 | 2529.65 | 15.17 | 4.62 | 0.519411E+09 | 768.96 | 15.17 | 4.62 | ||
Maximum of Months | 0.945811E+10 | 29999.99 | 29.00 | 15.72 | 0.685974E+09 | 769.09 | 38.00 | 18.60 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.469263E+09 | 3585.52 | 12-JAN-08:70 | 6.67 | 5.50 | 0.128745E+10 | 2176.36 | 31-JAN-16:40 | 29.00 | 10.73 |
February | 0.966783E+09 | 4458.91 | 01-FEB-08:70 | 5.67 | 3.96 | 0.102744E+10 | 1818.29 | 01-FEB-16:10 | 15.83 | 6.96 |
March | 0.769473E+09 | 4644.46 | 25-MAR-07:10 | 5.55 | 0.92 | 0.144881E+10 | 2246.80 | 17-MAR-15:39 | 5.55 | 0.92 |
April | 0.978486E+10 | 60095.35 | 14-APR-17:06 | 34.83 | 14.48 | 0.179829E+10 | 2246.81 | 15-APR-08:39 | 25.33 | 14.51 |
May | 0.174292E+11 | 62364.10 | 21-MAY-17:03 | 31.83 | 13.32 | 0.192194E+10 | 2246.80 | 22-MAY-10:39 | 26.33 | 10.27 |
June | 0.312571E+11 | 64521.61 | 18-JUN-10:32 | 35.33 | 17.77 | 0.192855E+10 | 2247.06 | 30-JUN-15:09 | 41.00 | 19.02 |
July | 0.295600E+11 | 65761.69 | 30-JUL-11:02 | 34.33 | 19.08 | 0.185436E+10 | 2247.09 | 22-JUL-15:00 | 34.33 | 19.08 |
August | 0.269201E+11 | 66074.71 | 21-AUG-17:42 | 33.18 | 17.49 | 0.200270E+10 | 2246.98 | 14-AUG-15:20 | 33.18 | 17.49 |
September | 0.202557E+11 | 66678.52 | 17-SEP-15:02 | 32.07 | 17.14 | 0.185320E+10 | 2246.97 | 01-SEP-10:00 | 32.07 | 17.14 |
October | 0.778311E+10 | 57837.68 | 05-OCT-17:06 | 33.67 | 15.15 | 0.172574E+10 | 2246.95 | 04-OCT-10:00 | 33.67 | 15.15 |
November | 0.102841E+10 | 6389.39 | 01-NOV-15:20 | 28.67 | 16.04 | 0.142717E+10 | 2246.86 | 01-NOV-15:39 | 28.33 | 15.88 |
December | 0.818827E+09 | 5093.55 | 05-DEC-08:70 | 2.83 | -2.3 | 0.109779E+10 | 1915.25 | 01-DEC-15:39 | 2.83 | -2.3 |
Annual Sum or Average | 0.147043E+12 | 0.193734E+11 | ||||||||
Minimum of Months | 0.469263E+09 | 3585.52 | 2.83 | -2.3 | 0.102744E+10 | 1818.29 | 2.83 | -2.3 | ||
Maximum of Months | 0.312571E+11 | 66678.52 | 35.33 | 19.08 | 0.200270E+10 | 2247.09 | 41.00 | 19.08 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 | 1.81 | 0.257373E+10 | 4417.04 | 31-JAN-15:39 | 28.67 | 10.84 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 | 4.43 | 0.221194E+10 | 3955.93 | 01-FEB-14:00 | 15.00 | 6.87 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 | 8.83 | 0.320570E+10 | 5194.92 | 18-MAR-15:30 | 27.20 | 11.82 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 | 7.34 | 0.502737E+10 | 8592.92 | 14-APR-15:39 | 35.00 | 14.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 | 7.18 | 0.603730E+10 | 9097.65 | 18-MAY-14:39 | 36.00 | 14.04 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 | 11.09 | 0.698316E+10 | 9097.65 | 01-JUN-12:00 | 37.00 | 17.36 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 | 14.60 | 0.650450E+10 | 9097.65 | 01-JUL-12:30 | 36.00 | 13.69 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.35 | 0.697961E+10 | 9097.65 | 01-AUG-13:00 | 36.00 | 21.59 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 | 16.66 | 0.605342E+10 | 9097.65 | 01-SEP-13:50 | 36.33 | 22.01 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 | 15.51 | 0.470801E+10 | 8694.72 | 06-OCT-14:39 | 35.00 | 15.01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 | 10.27 | 0.307751E+10 | 5454.67 | 01-NOV-15:20 | 28.67 | 16.04 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 | 2.98 | 0.216931E+10 | 3831.71 | 01-DEC-14:00 | 23.60 | 10.12 |
Annual Sum or Average | 0.00 | 0.555316E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.27 | 1.81 | 0.216931E+10 | 3831.71 | 15.00 | 6.87 | ||
Maximum of Months | 0.00 | 0.00 | 29.40 | 18.35 | 0.698316E+10 | 9097.65 | 37.00 | 22.01 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.650300E+09 | 29393.78 | 02-JAN-06:01 | 4.33 |
February | 0.714509E+09 | 29378.54 | 09-FEB-06:01 | 5.17 |
March | 0.533329E+09 | 29123.79 | 27-MAR-05:01 | 2.52 |
April | 30729236.97 | 1062.72 | 21-APR-06:15 | 9.67 |
May | 7173619.82 | 1013.73 | 03-MAY-06:05 | 18.33 |
June | 575209.12 | 900.28 | 12-JUN-06:05 | 21.53 |
July | 21255.08 | 106.28 | 01-JUL-06:03 | 18.83 |
August | 348625.09 | 960.22 | 25-AUG-06:05 | 21.67 |
September | 608991.14 | 443.11 | 22-SEP-06:15 | 17.17 |
October | 54790042.56 | 4209.53 | 25-OCT-06:20 | 5.00 |
November | 0.192514E+09 | 25249.95 | 24-NOV-06:02 | 3.17 |
December | 0.104333E+10 | 29399.74 | 19-DEC-06:01 | 3.17 |
Annual Sum or Average | 0.322823E+10 | |||
Minimum of Months | 21255.08 | 106.28 | 2.52 | |
Maximum of Months | 0.104333E+10 | 29399.74 | 21.67 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116436E+10 | 47561.80 | 01-JAN-07:23 | 1.00 |
February | 0.176223E+09 | 1409.49 | 01-FEB-07:40 | 5.00 |
March | 0.485302E+09 | 2943.51 | 15-MAR-16:10 | 28.20 |
April | 0.170001E+09 | 3393.74 | 01-APR-13:10 | 31.17 |
May | 93135251.92 | 1394.67 | 15-MAY-06:13 | 17.67 |
June | 4716478.74 | 1373.99 | 14-JUN-06:01 | 20.50 |
July | 4330179.46 | 1226.83 | 29-JUL-06:05 | 21.17 |
August | 7734061.71 | 3237.65 | 15-AUG-06:05 | 26.33 |
September | 41883340.10 | 1754.46 | 08-SEP-06:05 | 24.00 |
October | 0.121657E+09 | 1801.90 | 31-OCT-17:00 | 27.00 |
November | 0.320252E+09 | 1922.15 | 10-NOV-14:00 | 27.00 |
December | 0.678006E+09 | 24289.44 | 08-DEC-06:50 | 2.00 |
Annual Sum or Average | 0.326760E+10 | |||
Minimum of Months | 4330179.46 | 1226.83 | 1.00 | |
Maximum of Months | 0.116436E+10 | 47561.80 | 31.17 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.892002E+09 | 995.23 | 20-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.814386E+09 | 992.93 | 11-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.913780E+09 | 983.09 | 21-MAR-07:10 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.836096E+09 | 959.87 | 29-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.867438E+09 | 923.74 | 26-MAY-08:30 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.877724E+09 | 905.62 | 12-JUN-09:30 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.854530E+09 | 929.95 | 27-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.925315E+09 | 983.56 | 04-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.843150E+09 | 969.77 | 29-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.879653E+09 | 986.99 | 27-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.849059E+09 | 1011.11 | 28-NOV-16:30 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.902927E+09 | 1011.11 | 01-DEC-16:30 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.104561E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.814386E+09 | 905.62 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.925315E+09 | 1011.11 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.350945E+10 | 3641.25 | 13-JAN-09:09 | 0.00 | 0.00 |
February | 0.300786E+10 | 3646.09 | 03-FEB-09:09 | 0.00 | 0.00 |
March | 0.322676E+10 | 3628.93 | 14-MAR-08:09 | 0.00 | 0.00 |
April | 0.293422E+10 | 3491.02 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.297619E+10 | 3337.58 | 06-MAY-08:09 | 0.00 | 0.00 |
June | 0.306829E+10 | 3339.52 | 22-JUN-08:09 | 0.00 | 0.00 |
July | 0.291166E+10 | 3423.33 | 25-JUL-08:09 | 0.00 | 0.00 |
August | 0.316897E+10 | 3473.83 | 10-AUG-08:09 | 0.00 | 0.00 |
September | 0.294177E+10 | 3464.39 | 28-SEP-08:09 | 0.00 | 0.00 |
October | 0.327371E+10 | 3665.52 | 31-OCT-08:09 | 0.00 | 0.00 |
November | 0.329666E+10 | 3656.39 | 04-NOV-08:09 | 0.00 | 0.00 |
December | 0.346345E+10 | 3679.95 | 06-DEC-15:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.377790E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.291166E+10 | 3337.58 | 0.00 | 0.00 | |
Maximum of Months | 0.350945E+10 | 3679.95 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.367089E+10 | 3709.39 | 13-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.312247E+10 | 3727.28 | 03-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.326871E+10 | 3572.09 | 14-MAR-08:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.296362E+10 | 3300.34 | 04-APR-07:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.300117E+10 | 3011.10 | 06-MAY-07:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.297996E+10 | 2998.04 | 10-JUN-07:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.293584E+10 | 3191.84 | 27-JUL-07:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.316432E+10 | 3335.82 | 04-AUG-07:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.298829E+10 | 3306.86 | 18-SEP-07:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.337805E+10 | 3749.99 | 31-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.340289E+10 | 3799.37 | 30-NOV-15:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.368964E+10 | 3896.80 | 06-DEC-15:00 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.385659E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.293584E+10 | 2998.04 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.368964E+10 | 3896.80 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.892002E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19745693.95 | 0.115462E+10 |
February | 0.127628E+10 | 0.814386E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128753E+10 |
March | 0.149825E+10 | 0.913780E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55636895.00 | 0.133169E+10 |
April | 0.138726E+10 | 0.836096E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491433E+09 | 0.519178E+09 |
May | 0.144276E+10 | 0.867438E+09 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.874677E+09 | 0.288305E+09 |
June | 0.144276E+10 | 0.877724E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153991E+10 | 76968427.42 |
July | 0.138726E+10 | 0.854530E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124697E+10 | 74758553.14 |
August | 0.149825E+10 | 0.925315E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119572E+10 | 0.113531E+09 |
September | 0.138726E+10 | 0.843150E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.845081E+09 | 0.209571E+09 |
October | 0.138726E+10 | 0.879653E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360591E+09 | 0.814378E+09 |
November | 0.133177E+10 | 0.849059E+09 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40554380.54 | 0.118580E+10 |
December | 0.138726E+10 | 0.902927E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3321897.00 | 0.144096E+10 |
Annual Sum or Average | 0.168137E+11 | 0.104561E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667365E+10 | 0.849729E+10 |
Minimum of Months | 0.127628E+10 | 0.814386E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74758553.14 |
Maximum of Months | 0.149825E+10 | 0.925315E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153991E+10 | 0.144096E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.350945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31676707.49 | 0.276500E+10 |
February | 0.300332E+10 | 0.300786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240867E+10 |
March | 0.352563E+10 | 0.322676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35467782.79 | 0.333705E+10 |
April | 0.326447E+10 | 0.293422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.701044E+09 | 0.170716E+10 |
May | 0.339505E+10 | 0.297619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154509E+10 | 0.109907E+10 |
June | 0.339505E+10 | 0.306829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328079E+10 | 0.349947E+09 |
July | 0.326447E+10 | 0.291166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276818E+10 | 0.321991E+09 |
August | 0.352563E+10 | 0.316897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189017E+10 | 0.524745E+09 |
September | 0.326447E+10 | 0.294177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138275E+10 | 0.875828E+09 |
October | 0.326447E+10 | 0.327371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441010E+09 | 0.255623E+10 |
November | 0.313390E+10 | 0.329666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23455704.24 | 0.322703E+10 |
December | 0.326447E+10 | 0.346345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17293470.82 | 0.270359E+10 |
Annual Sum or Average | 0.395654E+11 | 0.377790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121169E+11 | 0.218763E+11 |
Minimum of Months | 0.300332E+10 | 0.291166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321991E+09 |
Maximum of Months | 0.352563E+10 | 0.350945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328079E+10 | 0.333705E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.367089E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.936171E+09 | 0.884900E+10 |
February | 0.690763E+10 | 0.312247E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10284048.38 | 0.100577E+11 |
March | 0.810895E+10 | 0.326871E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381168E+09 | 0.139388E+11 |
April | 0.750829E+10 | 0.296362E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.591229E+09 | 0.102107E+11 |
May | 0.780862E+10 | 0.300117E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107724E+09 | 0.778681E+10 |
June | 0.780862E+10 | 0.297996E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498608E+09 | 0.354838E+10 |
July | 0.750829E+10 | 0.293584E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376077E+09 | 0.409024E+10 |
August | 0.810895E+10 | 0.316432E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298952E+09 | 0.519934E+10 |
September | 0.750829E+10 | 0.298829E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150811E+09 | 0.724209E+10 |
October | 0.750829E+10 | 0.337805E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95696539.34 | 0.142058E+11 |
November | 0.720796E+10 | 0.340289E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234687E+09 | 0.127685E+11 |
December | 0.750829E+10 | 0.368964E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372746E+09 | 0.945360E+10 |
Annual Sum or Average | 0.910005E+11 | 0.385659E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405415E+10 | 0.107351E+12 |
Minimum of Months | 0.690763E+10 | 0.293584E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10284048.38 | 0.354838E+10 |
Maximum of Months | 0.810895E+10 | 0.368964E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.936171E+09 | 0.142058E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 995.23 | 20-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1501.22 | 31-JAN-17:10 | 5976.56 | 12-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 992.93 | 11-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6197.36 | 01-FEB-08:00 |
March | 1680.92 | 01-MAR-08:09 | 983.09 | 21-MAR-07:10 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1717.75 | 16-MAR-16:10 | 7466.33 | 27-MAR-06:10 |
April | 1680.92 | 01-APR-07:10 | 959.87 | 29-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3839.88 | 14-APR-16:10 | 5092.62 | 21-APR-06:05 |
May | 1680.92 | 01-MAY-07:10 | 923.74 | 26-MAY-08:30 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4746.12 | 31-MAY-16:10 | 3656.18 | 01-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 905.62 | 12-JUN-09:30 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7003.82 | 30-JUN-16:10 | 1692.46 | 21-JUN-06:05 |
July | 1680.92 | 01-JUL-07:10 | 929.95 | 27-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6174.37 | 20-JUL-17:00 | 631.82 | 27-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 983.56 | 04-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6312.57 | 25-AUG-17:00 | 1621.54 | 24-AUG-06:10 |
September | 1680.92 | 01-SEP-07:10 | 969.77 | 29-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5251.19 | 08-SEP-16:10 | 2519.88 | 22-SEP-06:10 |
October | 1680.92 | 02-OCT-07:10 | 986.99 | 27-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3931.84 | 04-OCT-17:00 | 6328.91 | 25-OCT-06:03 |
November | 1680.92 | 01-NOV-07:10 | 1011.11 | 28-NOV-16:30 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1427.63 | 01-NOV-16:10 | 6219.54 | 24-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1011.11 | 01-DEC-16:30 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 123.17 | 21-DEC-15:00 | 7670.78 | 06-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 905.62 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 631.82 | |||||
Maximum of Months | 1680.92 | 1011.11 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 7003.82 | 7670.78 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3641.25 | 13-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 710.66 | 16-JAN-12:00 | 4236.63 | 01-JAN-01:30 |
February | 3955.50 | 01-FEB-08:09 | 3646.09 | 03-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5424.08 | 02-FEB-17:03 |
March | 3955.50 | 01-MAR-08:09 | 3628.93 | 14-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1087.28 | 15-MAR-15:10 | 5083.97 | 28-MAR-06:10 |
April | 3955.50 | 01-APR-07:10 | 3491.02 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3734.13 | 10-APR-16:00 | 4012.86 | 21-APR-06:10 |
May | 3955.50 | 01-MAY-07:10 | 3337.58 | 06-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5170.01 | 10-MAY-16:00 | 2854.89 | 23-MAY-06:10 |
June | 3955.50 | 01-JUN-07:10 | 3339.52 | 22-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9974.58 | 30-JUN-16:00 | 1881.27 | 13-JUN-06:10 |
July | 3955.50 | 01-JUL-07:10 | 3423.33 | 25-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10076.35 | 22-JUL-16:00 | 2544.34 | 26-JUL-24:00 |
August | 3955.50 | 01-AUG-07:10 | 3473.83 | 10-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7009.00 | 12-AUG-16:00 | 5180.42 | 28-AUG-17:00 |
September | 3955.50 | 01-SEP-07:10 | 3464.39 | 28-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5892.34 | 01-SEP-16:00 | 2833.72 | 15-SEP-07:00 |
October | 3955.50 | 02-OCT-07:10 | 3665.52 | 31-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3787.01 | 10-OCT-15:10 | 5999.47 | 22-OCT-14:00 |
November | 3955.50 | 01-NOV-07:10 | 3656.39 | 04-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 865.08 | 19-NOV-13:00 | 5336.89 | 24-NOV-08:00 |
December | 3955.50 | 01-DEC-08:09 | 3679.95 | 06-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 572.91 | 25-DEC-16:00 | 4918.64 | 07-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3337.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1881.27 | ||||
Maximum of Months | 3955.50 | 3679.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10076.35 | 5999.47 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 3709.39 | 13-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13053.61 | 06-JAN-13:10 | 12539.91 | 11-JAN-08:70 |
February | 9097.65 | 01-FEB-08:09 | 3727.28 | 03-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1250.18 | 18-FEB-14:00 | 22597.47 | 02-FEB-12:00 |
March | 9097.65 | 01-MAR-08:09 | 3572.09 | 14-MAR-08:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8278.16 | 15-MAR-13:00 | 20368.58 | 24-MAR-14:00 |
April | 9097.65 | 01-APR-07:10 | 3300.34 | 04-APR-07:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10644.66 | 01-APR-15:00 | 18209.09 | 26-APR-18:00 |
May | 9097.65 | 01-MAY-07:10 | 3011.10 | 06-MAY-07:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1637.63 | 31-MAY-16:00 | 13884.46 | 23-MAY-05:00 |
June | 9097.65 | 01-JUN-07:10 | 2998.04 | 10-JUN-07:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3128.93 | 16-JUN-16:00 | 9956.46 | 13-JUN-06:00 |
July | 9097.65 | 01-JUL-07:10 | 3191.84 | 27-JUL-07:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2470.97 | 17-JUL-15:00 | 19520.35 | 17-JUL-19:52 |
August | 9097.65 | 01-AUG-07:10 | 3335.82 | 04-AUG-07:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2279.69 | 25-AUG-16:00 | 24292.05 | 28-AUG-17:00 |
September | 9097.65 | 01-SEP-07:10 | 3306.86 | 18-SEP-07:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2159.31 | 17-SEP-11:43 | 15601.14 | 03-SEP-05:00 |
October | 9097.65 | 02-OCT-07:10 | 3749.99 | 31-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2644.21 | 31-OCT-16:00 | 32030.61 | 07-OCT-14:51 |
November | 9097.65 | 01-NOV-07:10 | 3799.37 | 30-NOV-15:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4619.56 | 19-NOV-15:00 | 31650.74 | 22-NOV-12:00 |
December | 9097.65 | 01-DEC-08:09 | 3896.80 | 06-DEC-15:00 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5559.11 | 21-DEC-14:00 | 15774.63 | 07-DEC-08:70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 2998.04 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 1250.18 | 9956.46 | |||||
Maximum of Months | 9097.65 | 3896.80 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 13053.61 | 32030.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4342.39 | 31-JAN-16:40 | 1680.92 | 616.78 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 366.90 | 0.00 |
February | 2529.65 | 01-FEB-16:00 | 1680.92 | 653.56 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.07 |
March | 5042.20 | 18-MAR-16:00 | 1680.92 | 653.04 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 0.00 |
April | 29447.38 | 24-APR-05:02 | 1109.41 | 305.97 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.25 |
May | 29999.99 | 22-MAY-05:01 | 1294.31 | 356.97 | 3853.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 743.50 |
June | 28273.37 | 21-JUN-05:01 | 1664.11 | 458.96 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 514.94 |
July | 28040.01 | 01-JUL-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.91 |
August | 26545.45 | 24-AUG-05:01 | 1664.11 | 458.96 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.67 |
September | 26027.57 | 16-SEP-05:01 | 1479.21 | 407.96 | 4404.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.98 |
October | 26750.90 | 06-OCT-05:01 | 1479.21 | 407.96 | 4404.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 550.65 |
November | 6436.21 | 01-NOV-16:00 | 1680.92 | 651.22 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 454.41 | 0.00 |
December | 3085.88 | 01-DEC-15:30 | 1680.92 | 648.76 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2529.65 | 1109.41 | 305.97 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29999.99 | 1849.01 | 653.56 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 454.41 | 743.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3585.52 | 12-JAN-08:70 | 3955.50 | 3297.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2867.25 |
February | 4458.91 | 01-FEB-08:70 | 3955.50 | 3298.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4070.94 |
March | 4644.46 | 25-MAR-07:10 | 3955.50 | 3237.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2720.10 |
April | 60095.35 | 14-APR-17:06 | 0.00 | 1962.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1776.58 | 0.00 |
May | 62364.10 | 21-MAY-17:03 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2420.09 | 0.00 |
June | 64521.61 | 18-JUN-10:32 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.68 | 0.00 |
July | 65761.69 | 30-JUL-11:02 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2218.92 | 0.00 |
August | 66074.71 | 21-AUG-17:42 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1703.44 | 0.00 |
September | 66678.52 | 17-SEP-15:02 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2005.12 | 0.00 |
October | 57837.68 | 05-OCT-17:06 | 0.00 | 2180.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1768.58 | 0.00 |
November | 6389.39 | 01-NOV-15:20 | 3955.50 | 2912.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 521.53 | 0.00 |
December | 5093.55 | 05-DEC-08:70 | 3955.50 | 3236.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3585.52 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 66678.52 | 3955.50 | 3298.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2420.09 | 4070.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 996.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8499.93 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5746.86 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4427.81 |
April | 0.00 | 01-APR-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3695.01 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5474.34 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1865.25 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2247.37 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 799.71 |
September | 0.00 | 01-SEP-00:05 | 0.00 | 996.09 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1803.62 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3320.27 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2658.55 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5026.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 799.71 | |
Maximum of Months | 0.00 | 0.00 | 996.09 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8499.93 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.300864E+11 | 22406.54 | 24-JAN-15:00 | 0.149505E+10 | 32125.49 | 02-JAN-06:10 |
February | 0.264620E+11 | 22012.76 | 02-FEB-09:09 | 0.987117E+09 | 13635.97 | 13-FEB-06:10 |
March | 0.294532E+11 | 23059.03 | 18-MAR-15:00 | 0.687343E+09 | 13503.37 | 27-MAR-06:10 |
April | 0.327568E+11 | 33512.89 | 14-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.384493E+11 | 34838.96 | 18-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.472310E+11 | 42802.01 | 28-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.465137E+11 | 39882.71 | 22-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.471169E+11 | 40285.73 | 26-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.410335E+11 | 37563.19 | 08-SEP-15:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.335008E+11 | 35096.13 | 06-OCT-15:30 | 34072407.74 | 3722.13 | 25-OCT-06:00 |
November | 0.287155E+11 | 25455.93 | 01-NOV-14:50 | 0.205532E+09 | 9266.87 | 24-NOV-07:10 |
December | 0.300715E+11 | 22426.61 | 01-DEC-15:00 | 0.188388E+10 | 29261.57 | 18-DEC-07:10 |
Annual Sum or Average | 0.431391E+12 | 0.529299E+10 | ||||
Minimum of Months | 0.264620E+11 | 22012.76 | 0.00 | 0.00 | ||
Maximum of Months | 0.472310E+11 | 42802.01 | 0.188388E+10 | 32125.49 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.807234E+10 | 0.636974E+10 | 0.112984E+11 | 0.00 | 0.205582E+10 | 0.00 | 0.00 | 0.201540E+09 | 0.00 | 0.00 | 0.00 | 0.208856E+10 | 0.00 |
February | 0.694471E+10 | 0.536714E+10 | 0.103734E+11 | 0.00 | 0.188234E+10 | 0.00 | 0.00 | 1611295.64 | 0.00 | 0.00 | 0.00 | 0.189284E+10 | 0.00 |
March | 0.740925E+10 | 0.536606E+10 | 0.121089E+11 | 0.00 | 0.219756E+10 | 0.00 | 0.00 | 0.275902E+09 | 0.00 | 0.00 | 0.00 | 0.209554E+10 | 0.00 |
April | 0.673394E+10 | 0.460344E+10 | 0.112578E+11 | 0.00 | 0.344156E+10 | 0.00 | 0.00 | 0.478032E+10 | 0.00 | 0.00 | 0.00 | 0.193980E+10 | 0.00 |
May | 0.684480E+10 | 0.425466E+10 | 0.117000E+11 | 0.00 | 0.526345E+10 | 0.00 | 0.00 | 0.843981E+10 | 0.00 | 0.00 | 0.00 | 0.194663E+10 | 0.00 |
June | 0.692597E+10 | 0.392051E+10 | 0.116594E+11 | 0.00 | 0.754005E+10 | 0.00 | 0.00 | 0.153350E+11 | 0.00 | 0.00 | 0.00 | 0.185012E+10 | 0.00 |
July | 0.670203E+10 | 0.412994E+10 | 0.112984E+11 | 0.00 | 0.744317E+10 | 0.00 | 0.00 | 0.150887E+11 | 0.00 | 0.00 | 0.00 | 0.185153E+10 | 0.00 |
August | 0.725860E+10 | 0.453094E+10 | 0.121016E+11 | 0.00 | 0.697463E+10 | 0.00 | 0.00 | 0.143544E+11 | 0.00 | 0.00 | 0.00 | 0.189677E+10 | 0.00 |
September | 0.677321E+10 | 0.493138E+10 | 0.112504E+11 | 0.00 | 0.543014E+10 | 0.00 | 0.00 | 0.107969E+11 | 0.00 | 0.00 | 0.00 | 0.185153E+10 | 0.00 |
October | 0.753141E+10 | 0.571056E+10 | 0.113057E+11 | 0.00 | 0.313755E+10 | 0.00 | 0.00 | 0.386178E+10 | 0.00 | 0.00 | 0.00 | 0.195376E+10 | 0.00 |
November | 0.754861E+10 | 0.604106E+10 | 0.108562E+11 | 0.00 | 0.194351E+10 | 0.00 | 0.00 | 0.379820E+09 | 0.00 | 0.00 | 0.00 | 0.194629E+10 | 0.00 |
December | 0.805602E+10 | 0.653206E+10 | 0.112984E+11 | 0.00 | 0.206452E+10 | 0.00 | 0.00 | 53627739.76 | 0.00 | 0.00 | 0.00 | 0.206696E+10 | 0.00 |
Annual Sum or Average | 0.868009E+11 | 0.617575E+11 | 0.136508E+12 | 0.00 | 0.493743E+11 | 0.00 | 0.00 | 0.735694E+11 | 0.00 | 0.00 | 0.00 | 0.233803E+11 | 0.00 |
Minimum of Months | 0.670203E+10 | 0.392051E+10 | 0.103734E+11 | 0.00 | 0.188234E+10 | 0.00 | 0.00 | 1611295.64 | 0.00 | 0.00 | 0.00 | 0.185012E+10 | 0.00 |
Maximum of Months | 0.807234E+10 | 0.653206E+10 | 0.121089E+11 | 0.00 | 0.754005E+10 | 0.00 | 0.00 | 0.153350E+11 | 0.00 | 0.00 | 0.00 | 0.209554E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.149505E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.987117E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.687343E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 34072407.74 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.205532E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.188388E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.529299E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.188388E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 8311.46 | 13-JAN-09:09 | 5520.82 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 2480.92 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 8341.22 | 03-FEB-09:09 | 5520.82 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 2272.49 | 09-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 8147.51 | 14-MAR-08:09 | 5520.82 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 2313.74 | 27-MAR-06:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 7659.39 | 01-APR-08:09 | 5520.82 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 4605.64 | 14-APR-16:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 7081.90 | 06-MAY-08:09 | 5520.82 | 01-MAY-05:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 4787.37 | 31-MAY-16:49 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 7098.62 | 22-JUN-08:09 | 5520.82 | 01-JUN-05:10 | 10035.17 | 01-JUN-07:10 | 0.00 | 5913.03 | 30-JUN-16:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 7427.06 | 25-JUL-08:09 | 5520.82 | 01-JUL-05:10 | 10035.17 | 01-JUL-07:10 | 0.00 | 5280.25 | 05-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 7639.47 | 10-AUG-08:09 | 5520.82 | 01-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 5494.57 | 25-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 7517.10 | 28-SEP-08:09 | 5520.82 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 4844.49 | 08-SEP-16:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 8376.88 | 31-OCT-08:09 | 5520.82 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 4612.04 | 06-OCT-16:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 8336.04 | 04-NOV-08:09 | 5520.82 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 2223.25 | 24-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 8318.65 | 29-DEC-09:09 | 5520.82 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 2560.76 | 18-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 7081.90 | 5520.82 | 10035.17 | 0.00 | 2223.25 | 0.00 | 0.00 | |||||
Maximum of Months | 8376.88 | 5520.82 | 10035.17 | 0.00 | 5913.03 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 1435.04 | 31-JAN-16:40 | 0.00 | 0.00 | 0.00 | 1787.25 | 21-JAN-12:09 | 0.00 |
February | 190.29 | 22-FEB-15:00 | 0.00 | 0.00 | 0.00 | 1787.11 | 01-FEB-12:50 | 0.00 |
March | 3070.85 | 18-MAR-15:39 | 0.00 | 0.00 | 0.00 | 1776.90 | 01-MAR-12:09 | 0.00 |
April | 11857.77 | 14-APR-16:10 | 0.00 | 0.00 | 0.00 | 1755.71 | 01-APR-11:09 | 0.00 |
May | 13809.98 | 31-MAY-16:10 | 0.00 | 0.00 | 0.00 | 1731.39 | 01-MAY-11:50 | 0.00 |
June | 21516.42 | 30-JUN-16:10 | 0.00 | 0.00 | 0.00 | 1708.26 | 01-JUN-11:39 | 0.00 |
July | 18198.70 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | 1693.87 | 01-JUL-11:20 | 0.00 |
August | 19234.99 | 25-AUG-16:10 | 0.00 | 0.00 | 0.00 | 1699.30 | 31-AUG-11:20 | 0.00 |
September | 15959.22 | 08-SEP-16:10 | 0.00 | 0.00 | 0.00 | 1717.87 | 30-SEP-11:09 | 0.00 |
October | 12572.27 | 06-OCT-15:09 | 0.00 | 0.00 | 0.00 | 1742.87 | 31-OCT-11:30 | 0.00 |
November | 4840.10 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 1765.98 | 30-NOV-12:09 | 0.00 |
December | 890.99 | 22-DEC-16:30 | 0.00 | 0.00 | 0.00 | 1782.58 | 30-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 190.29 | 0.00 | 0.00 | 0.00 | 1693.87 | 0.00 | ||
Maximum of Months | 21516.42 | 0.00 | 0.00 | 0.00 | 1787.25 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 22406.54 | 24-JAN-15:00 | 7577.44 | 10035.17 | 0.00 | 0.00 | 2040.00 | 0.00 | 0.00 | 1003.28 | 0.00 |
February | 22012.76 | 02-FEB-09:09 | 8281.49 | 10035.17 | 0.00 | 0.00 | 2040.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 23059.03 | 18-MAR-15:00 | 6350.47 | 10035.17 | 0.00 | 0.00 | 2040.00 | 0.00 | 0.00 | 3039.49 | 0.00 |
April | 33512.89 | 14-APR-15:00 | 5619.33 | 10035.17 | 0.00 | 0.00 | 4456.87 | 0.00 | 0.00 | 11813.00 | 0.00 |
May | 34838.96 | 18-MAY-15:00 | 5136.22 | 10035.17 | 0.00 | 0.00 | 4561.67 | 0.00 | 0.00 | 13524.35 | 0.00 |
June | 42802.01 | 28-JUN-15:00 | 5145.44 | 10035.17 | 0.00 | 0.00 | 5533.59 | 0.00 | 0.00 | 20512.36 | 0.00 |
July | 39882.71 | 22-JUL-15:00 | 5911.64 | 10035.17 | 0.00 | 0.00 | 5256.20 | 0.00 | 0.00 | 18198.70 | 0.00 |
August | 40285.73 | 26-AUG-15:00 | 5882.38 | 10035.17 | 0.00 | 0.00 | 5087.28 | 0.00 | 0.00 | 17704.91 | 0.00 |
September | 37563.19 | 08-SEP-15:39 | 5409.13 | 10035.17 | 0.00 | 0.00 | 4731.40 | 0.00 | 0.00 | 15809.83 | 0.00 |
October | 35096.13 | 06-OCT-15:30 | 6525.46 | 10035.17 | 0.00 | 0.00 | 4498.35 | 0.00 | 0.00 | 12454.31 | 0.00 |
November | 25455.93 | 01-NOV-14:50 | 7044.09 | 10035.17 | 0.00 | 0.00 | 2040.00 | 0.00 | 0.00 | 4720.27 | 0.00 |
December | 22426.61 | 01-DEC-15:00 | 7905.15 | 10035.17 | 0.00 | 0.00 | 2040.00 | 0.00 | 0.00 | 712.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 22012.76 | 5136.22 | 10035.17 | 0.00 | 0.00 | 2040.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42802.01 | 8281.49 | 10035.17 | 0.00 | 0.00 | 5533.59 | 0.00 | 0.00 | 20512.36 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 32125.49 | 02-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 13635.97 | 13-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 13503.37 | 27-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 3722.13 | 25-OCT-06:00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 9266.87 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 29261.57 | 18-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 32125.49 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 20.18 | 1.50 | 20.18 | 0.00 | 20.18 | 0.00 | 20.18 |
February | 1.67 | 20.29 | 1.67 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
March | 1.33 | 20.43 | 1.33 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.53 | 0.83 | 24.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.59 | 0.67 | 25.11 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 25.17 | 5.33 | 24.95 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 25.31 | 7.00 | 25.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 25.47 | 7.00 | 25.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 25.04 | 5.33 | 24.89 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.68 | 1.50 | 24.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.17 | 20.21 | 3.17 | 20.21 | 0.00 | 20.21 | 0.00 | 20.21 |
Annual Sum or Average | 7.67 | 20.26 | 7.67 | 20.26 | 30.33 | 23.56 | 27.67 | 24.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 20.43 | 3.17 | 20.43 | 8.00 | 25.59 | 7.00 | 25.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 14.93 | 0.00 | 14.93 | 0.00 | 14.93 | 0.00 | 14.93 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.47 | 0.00 | 27.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 27.57 | 0.00 | 27.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 47.17 | 27.75 | 0.00 | 27.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 50.17 | 27.69 | 0.00 | 27.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 34.33 | 27.66 | 0.00 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 27.56 | 0.00 | 27.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.45 | 0.00 | 27.45 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
Annual Sum or Average | 2.33 | 14.94 | 0.00 | 14.94 | 195.33 | 27.50 | 0.00 | 27.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 14.99 | 0.00 | 14.99 | 50.17 | 27.75 | 0.00 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 22.91 | 73.83 | 22.56 | 73.83 | 22.33 |
February | 276.00 | 22.29 | 69.17 | 22.05 | 69.17 | 21.89 |
March | 307.17 | 22.96 | 47.67 | 22.71 | 47.67 | 22.53 |
April | 99.17 | 23.70 | 54.83 | 23.74 | 1.67 | 23.71 |
May | 33.50 | 23.50 | 85.17 | 23.79 | 0.00 | 23.79 |
June | 1.00 | 22.77 | 247.00 | 23.91 | 0.00 | 23.91 |
July | 5.00 | 23.99 | 288.00 | 23.93 | 4.67 | 23.93 |
August | 4.83 | 23.86 | 313.17 | 23.92 | 4.50 | 23.92 |
September | 5.00 | 23.99 | 290.33 | 23.91 | 4.83 | 23.92 |
October | 118.50 | 23.48 | 100.50 | 23.68 | 0.83 | 23.68 |
November | 239.00 | 23.27 | 50.33 | 23.19 | 36.67 | 23.10 |
December | 300.00 | 22.35 | 133.50 | 21.99 | 133.50 | 21.81 |
Annual Sum or Average | 1689.17 | 22.88 | 1753.50 | 23.13 | 377.33 | 22.96 |
Minimum of Months | 1.00 | 22.29 | 47.67 | 21.99 | 0.00 | 21.81 |
Maximum of Months | 307.17 | 23.99 | 313.17 | 23.93 | 133.50 | 23.93 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 281.67 | 21.40 | 118.33 | 20.69 | 117.67 | 20.30 |
February | 276.00 | 20.20 | 152.67 | 19.71 | 152.67 | 19.48 |
March | 269.33 | 21.44 | 125.83 | 21.41 | 84.50 | 20.97 |
April | 81.83 | 25.25 | 235.67 | 26.20 | 47.67 | 26.21 |
May | 113.17 | 26.68 | 294.67 | 26.64 | 112.00 | 26.65 |
June | 220.17 | 26.70 | 312.00 | 26.70 | 220.17 | 26.70 |
July | 267.00 | 26.71 | 300.00 | 26.70 | 267.00 | 26.71 |
August | 288.67 | 26.71 | 324.00 | 26.71 | 288.67 | 26.71 |
September | 249.67 | 26.71 | 300.00 | 26.69 | 249.67 | 26.70 |
October | 135.33 | 24.69 | 213.67 | 25.64 | 75.17 | 25.67 |
November | 190.33 | 22.26 | 131.17 | 22.72 | 67.00 | 22.41 |
December | 300.00 | 19.90 | 212.33 | 19.42 | 212.33 | 19.22 |
Annual Sum or Average | 2673.17 | 23.72 | 2720.33 | 24.28 | 1894.50 | 24.23 |
Minimum of Months | 81.83 | 19.90 | 118.33 | 19.42 | 47.67 | 19.22 |
Maximum of Months | 300.00 | 26.71 | 324.00 | 26.71 | 288.67 | 26.71 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.05 | 164.83 | 19.36 | 164.83 | 19.03 |
February | 276.00 | 19.49 | 190.17 | 19.09 | 190.17 | 18.92 |
March | 279.33 | 21.08 | 132.33 | 20.87 | 101.50 | 20.46 |
April | 230.00 | 29.31 | 266.17 | 29.26 | 209.83 | 29.44 |
May | 299.67 | 31.10 | 312.00 | 31.02 | 299.67 | 31.05 |
June | 312.00 | 34.01 | 312.00 | 34.01 | 312.00 | 34.01 |
July | 300.00 | 33.14 | 300.00 | 33.14 | 300.00 | 33.14 |
August | 324.00 | 32.96 | 324.00 | 32.96 | 324.00 | 32.96 |
September | 300.00 | 31.65 | 300.00 | 31.65 | 300.00 | 31.65 |
October | 209.33 | 28.41 | 225.50 | 28.61 | 172.00 | 28.88 |
November | 223.50 | 21.76 | 124.17 | 21.73 | 91.00 | 21.41 |
December | 300.00 | 18.35 | 267.33 | 18.15 | 267.33 | 18.08 |
Annual Sum or Average | 3353.83 | 26.95 | 2918.50 | 27.38 | 2732.33 | 27.56 |
Minimum of Months | 209.33 | 18.35 | 124.17 | 18.15 | 91.00 | 18.08 |
Maximum of Months | 324.00 | 34.01 | 324.00 | 34.01 | 324.00 | 34.01 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.806452E+09 | 0.201540E+09 | 98.50 | 0.806452E+09 | 0.00 | 0.00 | 0.58 | 31-JAN-16:50 | 0.00 | 01-JAN-00:05 | 5484.44 | 31-JAN-16:40 | 5484.44 | 31-JAN-16:40 | 0.00 | 14-JAN-16:20 | 1435.04 | 31-JAN-16:40 | 0.00 | 01-JAN-00:05 |
February | 6317947.97 | 1611295.64 | 6.50 | 6016540.56 | 301407.41 | 0.00 | 0.08 | 22-FEB-16:00 | 0.00 | 01-FEB-00:10 | 749.82 | 22-FEB-16:00 | 749.82 | 22-FEB-16:00 | 44.82 | 18-FEB-16:00 | 190.29 | 22-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 0.983932E+09 | 0.247443E+09 | 96.75 | 0.979560E+09 | 4371955.68 | 0.00 | 0.60 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 5979.24 | 18-MAR-16:00 | 5979.24 | 18-MAR-16:00 | 277.17 | 18-MAR-10:50 | 1496.68 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.568697E+10 | 0.145151E+10 | 244.53 | 0.568617E+10 | 798782.60 | 0.00 | 1.00 | 05-APR-05:03 | 0.00 | 01-APR-00:10 | 21738.34 | 25-APR-05:01 | 21738.34 | 25-APR-05:01 | 1985.66 | 17-APR-05:02 | 4741.18 | 25-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.819045E+10 | 0.213845E+10 | 288.52 | 0.819045E+10 | -0.0 | 0.00 | 1.00 | 01-MAY-05:02 | 0.00 | 01-MAY-00:10 | 21817.60 | 11-MAY-05:01 | 21817.60 | 11-MAY-05:01 | 0.00 | 09-MAY-05:03 | 4758.47 | 11-MAY-05:01 | 0.00 | 01-MAY-00:10 |
June | 0.114228E+11 | 0.321547E+10 | 320.91 | 0.114020E+11 | 20789786.54 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 23216.57 | 30-JUN-05:01 | 23216.57 | 30-JUN-05:01 | 1277.13 | 17-JUN-16:55 | 5950.81 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.118558E+11 | 0.314293E+10 | 314.57 | 0.107186E+11 | 0.113714E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 28298.00 | 14-JUL-05:01 | 23814.71 | 22-JUL-05:01 | 14601.49 | 14-JUL-05:17 | 5909.59 | 14-JUL-05:01 | 0.00 | 01-JUL-00:10 |
August | 0.124737E+11 | 0.329454E+10 | 325.48 | 0.111767E+11 | 0.129702E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 26899.99 | 01-AUG-05:01 | 23621.91 | 16-AUG-05:01 | 12043.31 | 04-AUG-05:54 | 5751.45 | 28-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.105096E+11 | 0.268022E+10 | 294.27 | 0.932568E+10 | 0.118389E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:05 | 27100.95 | 02-SEP-05:01 | 22939.74 | 20-SEP-05:01 | 13047.79 | 05-SEP-05:53 | 5852.35 | 02-SEP-05:01 | 0.00 | 01-SEP-00:05 |
October | 0.499065E+10 | 0.125166E+10 | 211.75 | 0.475046E+10 | 0.240197E+09 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 25802.70 | 03-OCT-05:01 | 22278.91 | 02-OCT-05:01 | 10398.23 | 03-OCT-05:10 | 5535.05 | 03-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.127494E+10 | 0.314542E+09 | 112.67 | 0.123423E+10 | 40709473.52 | 0.00 | 0.74 | 01-NOV-15:50 | 0.00 | 01-NOV-00:10 | 7849.43 | 01-NOV-16:00 | 7468.57 | 01-NOV-16:00 | 912.86 | 14-NOV-16:00 | 1945.15 | 01-NOV-15:30 | 0.00 | 01-NOV-00:10 |
December | 0.215208E+09 | 53627739.76 | 32.17 | 0.215208E+09 | 0.00 | 0.00 | 0.38 | 22-DEC-16:30 | 0.00 | 01-DEC-00:10 | 3631.32 | 22-DEC-16:30 | 3631.32 | 22-DEC-16:30 | 0.00 | 26-DEC-15:30 | 890.99 | 22-DEC-16:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.684167E+11 | 0.179935E+11 | 2346.61 | 0.644915E+11 | 0.392521E+10 | 0.00 | ||||||||||||||
Minimum of Months | 6317947.97 | 1611295.64 | 6.50 | 6016540.56 | -0.0 | 0.00 | 0.08 | 0.00 | 749.82 | 749.82 | 0.00 | 190.29 | 0.00 | |||||||
Maximum of Months | 0.124737E+11 | 0.329454E+10 | 325.48 | 0.114020E+11 | 0.129702E+10 | 0.00 | 1.00 | 0.00 | 28298.00 | 23814.71 | 14601.49 | 5950.81 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 94094848.38 | 28459077.14 | 11.83 | 94094848.38 | -0.0 | 0.00 | 0.17 | 18-MAR-15:30 | 0.00 | 01-MAR-00:10 | 5321.33 | 18-MAR-15:30 | 5321.33 | 18-MAR-15:30 | 0.00 | 18-MAR-16:30 | 1594.96 | 18-MAR-15:30 | 0.00 | 01-MAR-00:10 |
April | 0.109973E+11 | 0.332881E+10 | 230.10 | 0.109951E+11 | 2142608.98 | 0.00 | 1.00 | 04-APR-17:10 | 0.00 | 01-APR-00:10 | 73119.54 | 16-APR-18:11 | 73119.54 | 16-APR-18:11 | 4160.62 | 16-APR-10:25 | 20679.06 | 14-APR-17:06 | 0.00 | 01-APR-00:10 |
May | 0.203554E+11 | 0.630136E+10 | 342.35 | 0.203554E+11 | 0.00 | 0.00 | 1.00 | 01-MAY-17:08 | 0.00 | 01-MAY-00:10 | 72468.63 | 29-MAY-20:45 | 72468.63 | 29-MAY-20:45 | 0.00 | 24-MAY-20:35 | 21193.02 | 15-MAY-17:06 | 0.00 | 01-MAY-00:10 |
June | 0.374883E+11 | 0.121196E+11 | 475.64 | 0.373955E+11 | 92735534.87 | 0.00 | 1.00 | 01-JUN-15:20 | 0.00 | 01-JUN-00:10 | 75633.85 | 18-JUN-05:45 | 74105.64 | 18-JUN-04:35 | 9114.79 | 17-JUN-17:06 | 23207.24 | 28-JUN-17:42 | 0.00 | 01-JUN-00:10 |
July | 0.392900E+11 | 0.119457E+11 | 487.16 | 0.351966E+11 | 0.409332E+10 | 0.00 | 1.00 | 01-JUL-00:25 | 0.00 | 01-JUL-00:15 | 93959.23 | 13-JUL-20:52 | 73437.31 | 08-JUL-03:45 | 53390.61 | 14-JUL-01:22 | 22712.25 | 20-JUL-17:42 | 0.00 | 01-JUL-00:10 |
August | 0.362827E+11 | 0.110598E+11 | 458.05 | 0.323630E+11 | 0.391969E+10 | 0.00 | 1.00 | 01-AUG-02:25 | 0.00 | 01-AUG-00:15 | 90667.79 | 09-AUG-19:52 | 74426.57 | 31-AUG-03:15 | 41636.31 | 09-AUG-18:02 | 22615.07 | 13-AUG-14:12 | 0.00 | 01-AUG-00:10 |
September | 0.273729E+11 | 0.811667E+10 | 374.33 | 0.240682E+11 | 0.330467E+10 | 0.00 | 1.00 | 01-SEP-00:35 | 0.00 | 01-SEP-00:05 | 92446.94 | 04-SEP-08:52 | 74671.80 | 26-SEP-21:15 | 50689.67 | 04-SEP-07:55 | 22166.07 | 07-SEP-17:05 | 0.00 | 01-SEP-00:05 |
October | 0.872928E+10 | 0.261012E+10 | 166.21 | 0.819071E+10 | 0.538569E+09 | 0.00 | 1.00 | 01-OCT-08:15 | 0.00 | 01-OCT-00:10 | 85582.56 | 02-OCT-22:41 | 73914.22 | 06-OCT-23:13 | 28937.89 | 02-OCT-22:41 | 21202.25 | 02-OCT-22:41 | 0.00 | 01-OCT-00:10 |
November | 0.219383E+09 | 65277275.63 | 15.17 | 0.203751E+09 | 15631764.34 | 0.00 | 0.29 | 01-NOV-15:10 | 0.00 | 01-NOV-00:10 | 9710.35 | 01-NOV-15:10 | 8840.14 | 01-NOV-15:10 | 975.16 | 01-NOV-14:20 | 2905.53 | 01-NOV-15:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.180829E+12 | 0.555758E+11 | 2560.85 | 0.168863E+12 | 0.119668E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.392900E+11 | 0.121196E+11 | 487.16 | 0.373955E+11 | 0.409332E+10 | 0.00 | 1.00 | 0.00 | 93959.23 | 74671.80 | 53390.61 | 23207.24 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 82.11 | 51.20 | 30.91 | 126.57 | 81.48 | 0.00 | 0.00 | 0.00 |
February | 65.99 | 31.85 | 34.14 | 85.97 | 72.77 | 0.00 | 0.00 | 0.00 |
March | 88.03 | 42.18 | 45.84 | 127.65 | 70.59 | 0.00 | 0.00 | 0.00 |
April | 134.29 | 76.55 | 57.75 | 227.46 | 52.27 | 0.00 | 0.00 | 0.00 |
May | 134.88 | 75.50 | 59.38 | 240.44 | 40.98 | 0.00 | 0.00 | 0.00 |
June | 143.35 | 84.39 | 58.96 | 285.60 | 20.10 | 0.00 | 0.00 | 0.00 |
July | 104.26 | 48.67 | 55.59 | 211.54 | 16.72 | 0.00 | 0.00 | 0.00 |
August | 99.61 | 50.05 | 49.56 | 201.90 | 20.72 | 0.00 | 0.00 | 0.00 |
September | 86.76 | 36.50 | 50.27 | 167.43 | 28.14 | 0.00 | 0.00 | 0.00 |
October | 88.64 | 50.66 | 37.99 | 142.62 | 67.80 | 0.00 | 0.00 | 0.00 |
November | 81.35 | 48.99 | 32.36 | 118.12 | 85.23 | 0.00 | 0.00 | 0.00 |
December | 65.78 | 37.43 | 28.35 | 92.65 | 98.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98.04 | 52.91 | 45.13 | 169.34 | 54.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 65.78 | 31.85 | 28.35 | 85.97 | 16.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.35 | 84.39 | 59.38 | 285.60 | 98.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 82.11 | 51.20 | 30.91 | 126.57 | 81.48 | 0.00 | 0.00 | 0.00 |
February | 65.99 | 31.85 | 34.14 | 85.97 | 72.77 | 0.00 | 0.00 | 0.00 |
March | 88.03 | 42.18 | 45.84 | 127.65 | 70.59 | 0.00 | 0.00 | 0.00 |
April | 134.29 | 76.55 | 57.75 | 227.46 | 52.27 | 0.00 | 0.00 | 0.00 |
May | 134.88 | 75.50 | 59.38 | 240.44 | 40.98 | 0.00 | 0.00 | 0.00 |
June | 143.35 | 84.39 | 58.96 | 285.60 | 20.10 | 0.00 | 0.00 | 0.00 |
July | 104.26 | 48.67 | 55.59 | 211.54 | 16.72 | 0.00 | 0.00 | 0.00 |
August | 99.61 | 50.05 | 49.56 | 201.90 | 20.72 | 0.00 | 0.00 | 0.00 |
September | 86.76 | 36.50 | 50.27 | 167.43 | 28.14 | 0.00 | 0.00 | 0.00 |
October | 88.64 | 50.66 | 37.99 | 142.62 | 67.80 | 0.00 | 0.00 | 0.00 |
November | 81.35 | 48.99 | 32.36 | 118.12 | 85.23 | 0.00 | 0.00 | 0.00 |
December | 65.78 | 37.43 | 28.35 | 92.65 | 98.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98.04 | 52.91 | 45.13 | 169.34 | 54.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 65.78 | 31.85 | 28.35 | 85.97 | 16.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.35 | 84.39 | 59.38 | 285.60 | 98.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.09 | 0.00 | 14.09 | 13.77 | 47.91 | 0.00 | 0.00 | 0.00 |
February | 16.05 | 0.00 | 16.05 | 11.41 | 43.28 | 0.00 | 0.00 | 0.00 |
March | 21.34 | 0.00 | 21.34 | 23.25 | 42.15 | 0.00 | 0.00 | 0.00 |
April | 26.08 | 0.35 | 25.73 | 40.67 | 29.79 | 0.00 | 0.00 | 0.00 |
May | 30.71 | 2.66 | 28.05 | 55.35 | 21.81 | 0.00 | 0.00 | 0.00 |
June | 35.23 | 6.30 | 28.92 | 83.97 | 10.73 | 0.00 | 0.00 | 0.00 |
July | 30.06 | 3.05 | 27.01 | 70.30 | 9.15 | 0.00 | 0.00 | 0.00 |
August | 24.42 | 0.65 | 23.76 | 58.04 | 11.66 | 0.00 | 0.00 | 0.00 |
September | 22.98 | 0.01 | 22.96 | 48.39 | 16.24 | 0.00 | 0.00 | 0.00 |
October | 17.77 | 0.00 | 17.77 | 23.56 | 40.05 | 0.00 | 0.00 | 0.00 |
November | 14.80 | 0.00 | 14.80 | 11.73 | 50.46 | 0.00 | 0.00 | 0.00 |
December | 13.16 | 0.00 | 13.16 | 9.22 | 58.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.25 | 1.09 | 21.16 | 37.59 | 31.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.16 | 0.00 | 13.16 | 9.22 | 9.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 35.23 | 6.30 | 28.92 | 83.97 | 58.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.09 | 0.00 | 14.09 | 13.77 | 47.91 | 0.00 | 0.00 | 0.00 |
February | 16.05 | 0.00 | 16.05 | 11.41 | 43.28 | 0.00 | 0.00 | 0.00 |
March | 21.34 | 0.00 | 21.34 | 23.25 | 42.15 | 0.00 | 0.00 | 0.00 |
April | 26.08 | 0.35 | 25.73 | 40.67 | 29.79 | 0.00 | 0.00 | 0.00 |
May | 30.71 | 2.66 | 28.05 | 55.35 | 21.81 | 0.00 | 0.00 | 0.00 |
June | 35.22 | 6.30 | 28.92 | 83.97 | 10.73 | 0.00 | 0.00 | 0.00 |
July | 30.06 | 3.05 | 27.01 | 70.30 | 9.15 | 0.00 | 0.00 | 0.00 |
August | 24.42 | 0.65 | 23.76 | 58.04 | 11.66 | 0.00 | 0.00 | 0.00 |
September | 22.98 | 0.01 | 22.96 | 48.39 | 16.24 | 0.00 | 0.00 | 0.00 |
October | 17.77 | 0.00 | 17.77 | 23.56 | 40.05 | 0.00 | 0.00 | 0.00 |
November | 14.80 | 0.00 | 14.80 | 11.73 | 50.46 | 0.00 | 0.00 | 0.00 |
December | 13.16 | 0.00 | 13.16 | 9.22 | 58.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.25 | 1.09 | 21.16 | 37.59 | 31.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.16 | 0.00 | 13.16 | 9.22 | 9.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 35.22 | 6.30 | 28.92 | 83.97 | 58.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.23 | 27.00 | 8.23 | 50.25 | 40.13 | 0.00 | 0.00 | 0.00 |
February | 34.88 | 22.33 | 12.55 | 46.95 | 31.47 | 0.00 | 0.00 | 0.00 |
March | 50.00 | 32.09 | 17.91 | 70.86 | 33.25 | 0.00 | 0.00 | 0.00 |
April | 77.76 | 60.27 | 17.49 | 117.81 | 31.66 | 0.00 | 0.00 | 0.00 |
May | 85.87 | 67.72 | 18.16 | 132.22 | 28.27 | 0.00 | 0.00 | 0.00 |
June | 90.51 | 74.27 | 16.24 | 149.33 | 17.82 | 0.00 | 0.00 | 0.00 |
July | 73.26 | 53.36 | 19.90 | 121.68 | 12.70 | 0.00 | 0.00 | 0.00 |
August | 67.45 | 50.11 | 17.33 | 112.30 | 16.06 | 0.00 | 0.00 | 0.00 |
September | 53.98 | 34.06 | 19.92 | 88.01 | 18.55 | 0.00 | 0.00 | 0.00 |
October | 47.61 | 35.79 | 11.83 | 69.22 | 36.66 | 0.00 | 0.00 | 0.00 |
November | 34.72 | 24.95 | 9.77 | 46.87 | 39.88 | 0.00 | 0.00 | 0.00 |
December | 30.34 | 21.95 | 8.39 | 40.57 | 44.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.90 | 42.08 | 14.82 | 87.36 | 29.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.34 | 21.95 | 8.23 | 40.57 | 12.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.51 | 74.27 | 19.92 | 149.33 | 44.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.23 | 27.00 | 8.23 | 50.25 | 40.13 | 0.00 | 0.00 | 0.00 |
February | 34.88 | 22.33 | 12.55 | 46.95 | 31.47 | 0.00 | 0.00 | 0.00 |
March | 50.00 | 32.09 | 17.91 | 70.86 | 33.25 | 0.00 | 0.00 | 0.00 |
April | 77.76 | 60.27 | 17.49 | 117.81 | 31.66 | 0.00 | 0.00 | 0.00 |
May | 85.87 | 67.72 | 18.16 | 132.22 | 28.27 | 0.00 | 0.00 | 0.00 |
June | 90.51 | 74.27 | 16.24 | 149.33 | 17.82 | 0.00 | 0.00 | 0.00 |
July | 73.26 | 53.36 | 19.90 | 121.68 | 12.70 | 0.00 | 0.00 | 0.00 |
August | 67.45 | 50.11 | 17.33 | 112.30 | 16.06 | 0.00 | 0.00 | 0.00 |
September | 53.98 | 34.06 | 19.92 | 88.01 | 18.55 | 0.00 | 0.00 | 0.00 |
October | 47.61 | 35.79 | 11.83 | 69.22 | 36.66 | 0.00 | 0.00 | 0.00 |
November | 34.72 | 24.95 | 9.77 | 46.87 | 39.88 | 0.00 | 0.00 | 0.00 |
December | 30.34 | 21.95 | 8.39 | 40.57 | 44.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.90 | 42.08 | 14.82 | 87.36 | 29.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.34 | 21.95 | 8.23 | 40.57 | 12.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.51 | 74.27 | 19.92 | 149.33 | 44.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.23 | 27.00 | 8.23 | 50.25 | 40.13 | 0.00 | 0.00 | 0.00 |
February | 34.88 | 22.33 | 12.55 | 46.95 | 31.47 | 0.00 | 0.00 | 0.00 |
March | 50.00 | 32.09 | 17.91 | 70.86 | 33.25 | 0.00 | 0.00 | 0.00 |
April | 77.76 | 60.27 | 17.49 | 117.81 | 31.66 | 0.00 | 0.00 | 0.00 |
May | 85.87 | 67.72 | 18.16 | 132.22 | 28.27 | 0.00 | 0.00 | 0.00 |
June | 90.51 | 74.27 | 16.24 | 149.33 | 17.82 | 0.00 | 0.00 | 0.00 |
July | 73.26 | 53.36 | 19.90 | 121.68 | 12.70 | 0.00 | 0.00 | 0.00 |
August | 67.45 | 50.11 | 17.33 | 112.30 | 16.06 | 0.00 | 0.00 | 0.00 |
September | 53.98 | 34.06 | 19.92 | 88.01 | 18.55 | 0.00 | 0.00 | 0.00 |
October | 47.61 | 35.79 | 11.83 | 69.22 | 36.66 | 0.00 | 0.00 | 0.00 |
November | 34.72 | 24.95 | 9.77 | 46.87 | 39.88 | 0.00 | 0.00 | 0.00 |
December | 30.34 | 21.95 | 8.39 | 40.57 | 44.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.90 | 42.08 | 14.82 | 87.36 | 29.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.34 | 21.95 | 8.23 | 40.57 | 12.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.51 | 74.27 | 19.92 | 149.33 | 44.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.23 | 27.00 | 8.23 | 50.25 | 40.13 | 0.00 | 0.00 | 0.00 |
February | 34.88 | 22.33 | 12.55 | 46.95 | 31.47 | 0.00 | 0.00 | 0.00 |
March | 50.00 | 32.09 | 17.91 | 70.86 | 33.25 | 0.00 | 0.00 | 0.00 |
April | 77.76 | 60.27 | 17.49 | 117.81 | 31.66 | 0.00 | 0.00 | 0.00 |
May | 85.87 | 67.72 | 18.16 | 132.22 | 28.27 | 0.00 | 0.00 | 0.00 |
June | 90.51 | 74.27 | 16.24 | 149.33 | 17.82 | 0.00 | 0.00 | 0.00 |
July | 73.26 | 53.36 | 19.90 | 121.68 | 12.70 | 0.00 | 0.00 | 0.00 |
August | 67.45 | 50.11 | 17.33 | 112.30 | 16.06 | 0.00 | 0.00 | 0.00 |
September | 53.98 | 34.06 | 19.92 | 88.01 | 18.55 | 0.00 | 0.00 | 0.00 |
October | 47.61 | 35.79 | 11.83 | 69.22 | 36.66 | 0.00 | 0.00 | 0.00 |
November | 34.72 | 24.95 | 9.77 | 46.87 | 39.88 | 0.00 | 0.00 | 0.00 |
December | 30.34 | 21.95 | 8.39 | 40.57 | 44.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.90 | 42.08 | 14.82 | 87.36 | 29.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.34 | 21.95 | 8.23 | 40.57 | 12.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.51 | 74.27 | 19.92 | 149.33 | 44.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.23 | 27.00 | 8.23 | 50.25 | 40.13 | 0.00 | 0.00 | 0.00 |
February | 34.88 | 22.33 | 12.55 | 46.95 | 31.47 | 0.00 | 0.00 | 0.00 |
March | 50.00 | 32.09 | 17.91 | 70.86 | 33.25 | 0.00 | 0.00 | 0.00 |
April | 77.76 | 60.27 | 17.49 | 117.81 | 31.66 | 0.00 | 0.00 | 0.00 |
May | 85.87 | 67.72 | 18.16 | 132.22 | 28.27 | 0.00 | 0.00 | 0.00 |
June | 90.51 | 74.27 | 16.24 | 149.33 | 17.82 | 0.00 | 0.00 | 0.00 |
July | 73.26 | 53.36 | 19.90 | 121.68 | 12.70 | 0.00 | 0.00 | 0.00 |
August | 67.45 | 50.11 | 17.33 | 112.30 | 16.06 | 0.00 | 0.00 | 0.00 |
September | 53.98 | 34.06 | 19.92 | 88.01 | 18.55 | 0.00 | 0.00 | 0.00 |
October | 47.61 | 35.79 | 11.83 | 69.22 | 36.66 | 0.00 | 0.00 | 0.00 |
November | 34.72 | 24.95 | 9.77 | 46.87 | 39.88 | 0.00 | 0.00 | 0.00 |
December | 30.34 | 21.95 | 8.39 | 40.57 | 44.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.90 | 42.08 | 14.82 | 87.36 | 29.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.34 | 21.95 | 8.23 | 40.57 | 12.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.51 | 74.27 | 19.92 | 149.33 | 44.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.23 | 27.00 | 8.23 | 50.25 | 40.13 | 0.00 | 0.00 | 0.00 |
February | 34.88 | 22.33 | 12.55 | 46.95 | 31.47 | 0.00 | 0.00 | 0.00 |
March | 50.00 | 32.09 | 17.91 | 70.86 | 33.25 | 0.00 | 0.00 | 0.00 |
April | 77.76 | 60.27 | 17.49 | 117.81 | 31.66 | 0.00 | 0.00 | 0.00 |
May | 85.87 | 67.72 | 18.16 | 132.22 | 28.27 | 0.00 | 0.00 | 0.00 |
June | 90.51 | 74.27 | 16.24 | 149.33 | 17.82 | 0.00 | 0.00 | 0.00 |
July | 73.26 | 53.36 | 19.90 | 121.68 | 12.70 | 0.00 | 0.00 | 0.00 |
August | 67.45 | 50.11 | 17.33 | 112.30 | 16.06 | 0.00 | 0.00 | 0.00 |
September | 53.98 | 34.06 | 19.92 | 88.01 | 18.55 | 0.00 | 0.00 | 0.00 |
October | 47.61 | 35.79 | 11.83 | 69.22 | 36.66 | 0.00 | 0.00 | 0.00 |
November | 34.72 | 24.95 | 9.77 | 46.87 | 39.88 | 0.00 | 0.00 | 0.00 |
December | 30.34 | 21.95 | 8.39 | 40.57 | 44.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.90 | 42.08 | 14.82 | 87.36 | 29.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.34 | 21.95 | 8.23 | 40.57 | 12.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.51 | 74.27 | 19.92 | 149.33 | 44.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.23 | 27.00 | 8.23 | 50.25 | 40.13 | 0.00 | 0.00 | 0.00 |
February | 34.88 | 22.33 | 12.55 | 46.95 | 31.47 | 0.00 | 0.00 | 0.00 |
March | 50.00 | 32.09 | 17.91 | 70.86 | 33.25 | 0.00 | 0.00 | 0.00 |
April | 77.76 | 60.27 | 17.49 | 117.81 | 31.66 | 0.00 | 0.00 | 0.00 |
May | 85.87 | 67.72 | 18.16 | 132.22 | 28.27 | 0.00 | 0.00 | 0.00 |
June | 90.51 | 74.27 | 16.24 | 149.33 | 17.82 | 0.00 | 0.00 | 0.00 |
July | 73.26 | 53.36 | 19.90 | 121.68 | 12.70 | 0.00 | 0.00 | 0.00 |
August | 67.45 | 50.11 | 17.33 | 112.30 | 16.06 | 0.00 | 0.00 | 0.00 |
September | 53.98 | 34.06 | 19.92 | 88.01 | 18.55 | 0.00 | 0.00 | 0.00 |
October | 47.61 | 35.79 | 11.83 | 69.22 | 36.66 | 0.00 | 0.00 | 0.00 |
November | 34.72 | 24.95 | 9.77 | 46.87 | 39.88 | 0.00 | 0.00 | 0.00 |
December | 30.34 | 21.95 | 8.39 | 40.57 | 44.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.90 | 42.08 | 14.82 | 87.36 | 29.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.34 | 21.95 | 8.23 | 40.57 | 12.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.51 | 74.27 | 19.92 | 149.33 | 44.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.23 | 27.00 | 8.23 | 50.25 | 40.13 | 0.00 | 0.00 | 0.00 |
February | 34.88 | 22.33 | 12.55 | 46.95 | 31.47 | 0.00 | 0.00 | 0.00 |
March | 50.00 | 32.09 | 17.91 | 70.86 | 33.25 | 0.00 | 0.00 | 0.00 |
April | 77.76 | 60.27 | 17.49 | 117.81 | 31.66 | 0.00 | 0.00 | 0.00 |
May | 85.87 | 67.72 | 18.16 | 132.22 | 28.27 | 0.00 | 0.00 | 0.00 |
June | 90.51 | 74.27 | 16.24 | 149.33 | 17.82 | 0.00 | 0.00 | 0.00 |
July | 73.26 | 53.36 | 19.90 | 121.68 | 12.70 | 0.00 | 0.00 | 0.00 |
August | 67.45 | 50.11 | 17.33 | 112.30 | 16.06 | 0.00 | 0.00 | 0.00 |
September | 53.98 | 34.06 | 19.92 | 88.01 | 18.55 | 0.00 | 0.00 | 0.00 |
October | 47.61 | 35.79 | 11.83 | 69.22 | 36.66 | 0.00 | 0.00 | 0.00 |
November | 34.72 | 24.95 | 9.77 | 46.87 | 39.88 | 0.00 | 0.00 | 0.00 |
December | 30.34 | 21.95 | 8.39 | 40.57 | 44.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.90 | 42.08 | 14.82 | 87.36 | 29.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.34 | 21.95 | 8.23 | 40.57 | 12.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.51 | 74.27 | 19.92 | 149.33 | 44.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.23 | 27.00 | 8.23 | 50.25 | 40.13 | 0.00 | 0.00 | 0.00 |
February | 34.88 | 22.33 | 12.55 | 46.95 | 31.47 | 0.00 | 0.00 | 0.00 |
March | 50.00 | 32.09 | 17.91 | 70.86 | 33.25 | 0.00 | 0.00 | 0.00 |
April | 77.76 | 60.27 | 17.49 | 117.81 | 31.66 | 0.00 | 0.00 | 0.00 |
May | 85.87 | 67.72 | 18.16 | 132.22 | 28.27 | 0.00 | 0.00 | 0.00 |
June | 90.51 | 74.27 | 16.24 | 149.33 | 17.82 | 0.00 | 0.00 | 0.00 |
July | 73.26 | 53.36 | 19.90 | 121.68 | 12.70 | 0.00 | 0.00 | 0.00 |
August | 67.45 | 50.11 | 17.33 | 112.30 | 16.06 | 0.00 | 0.00 | 0.00 |
September | 53.98 | 34.06 | 19.92 | 88.01 | 18.55 | 0.00 | 0.00 | 0.00 |
October | 47.61 | 35.79 | 11.83 | 69.22 | 36.66 | 0.00 | 0.00 | 0.00 |
November | 34.72 | 24.95 | 9.77 | 46.87 | 39.88 | 0.00 | 0.00 | 0.00 |
December | 30.34 | 21.95 | 8.39 | 40.57 | 44.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.90 | 42.08 | 14.82 | 87.36 | 29.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.34 | 21.95 | 8.23 | 40.57 | 12.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.51 | 74.27 | 19.92 | 149.33 | 44.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.23 | 27.00 | 8.23 | 50.25 | 40.13 | 0.00 | 0.00 | 0.00 |
February | 34.88 | 22.33 | 12.55 | 46.95 | 31.47 | 0.00 | 0.00 | 0.00 |
March | 50.00 | 32.09 | 17.91 | 70.86 | 33.25 | 0.00 | 0.00 | 0.00 |
April | 77.76 | 60.27 | 17.49 | 117.81 | 31.66 | 0.00 | 0.00 | 0.00 |
May | 85.87 | 67.72 | 18.16 | 132.22 | 28.27 | 0.00 | 0.00 | 0.00 |
June | 90.51 | 74.27 | 16.24 | 149.33 | 17.82 | 0.00 | 0.00 | 0.00 |
July | 73.26 | 53.36 | 19.90 | 121.68 | 12.70 | 0.00 | 0.00 | 0.00 |
August | 67.45 | 50.11 | 17.33 | 112.30 | 16.06 | 0.00 | 0.00 | 0.00 |
September | 53.98 | 34.06 | 19.92 | 88.01 | 18.55 | 0.00 | 0.00 | 0.00 |
October | 47.61 | 35.79 | 11.83 | 69.22 | 36.66 | 0.00 | 0.00 | 0.00 |
November | 34.72 | 24.95 | 9.77 | 46.87 | 39.88 | 0.00 | 0.00 | 0.00 |
December | 30.34 | 21.95 | 8.39 | 40.57 | 44.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.90 | 42.08 | 14.82 | 87.36 | 29.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.34 | 21.95 | 8.23 | 40.57 | 12.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.51 | 74.27 | 19.92 | 149.33 | 44.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.23 | 27.00 | 8.23 | 50.25 | 40.13 | 0.00 | 0.00 | 0.00 |
February | 34.88 | 22.33 | 12.55 | 46.95 | 31.47 | 0.00 | 0.00 | 0.00 |
March | 50.00 | 32.09 | 17.91 | 70.86 | 33.25 | 0.00 | 0.00 | 0.00 |
April | 77.76 | 60.27 | 17.49 | 117.81 | 31.66 | 0.00 | 0.00 | 0.00 |
May | 85.87 | 67.72 | 18.16 | 132.22 | 28.27 | 0.00 | 0.00 | 0.00 |
June | 90.51 | 74.27 | 16.24 | 149.33 | 17.82 | 0.00 | 0.00 | 0.00 |
July | 73.26 | 53.36 | 19.90 | 121.68 | 12.70 | 0.00 | 0.00 | 0.00 |
August | 67.45 | 50.11 | 17.33 | 112.30 | 16.06 | 0.00 | 0.00 | 0.00 |
September | 53.98 | 34.06 | 19.92 | 88.01 | 18.55 | 0.00 | 0.00 | 0.00 |
October | 47.61 | 35.79 | 11.83 | 69.22 | 36.66 | 0.00 | 0.00 | 0.00 |
November | 34.72 | 24.95 | 9.77 | 46.87 | 39.88 | 0.00 | 0.00 | 0.00 |
December | 30.34 | 21.95 | 8.39 | 40.57 | 44.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.90 | 42.08 | 14.82 | 87.36 | 29.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.34 | 21.95 | 8.23 | 40.57 | 12.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.51 | 74.27 | 19.92 | 149.33 | 44.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.23 | 27.00 | 8.23 | 50.25 | 40.13 | 0.00 | 0.00 | 0.00 |
February | 34.88 | 22.33 | 12.55 | 46.95 | 31.47 | 0.00 | 0.00 | 0.00 |
March | 50.00 | 32.09 | 17.91 | 70.86 | 33.25 | 0.00 | 0.00 | 0.00 |
April | 77.76 | 60.27 | 17.49 | 117.81 | 31.66 | 0.00 | 0.00 | 0.00 |
May | 85.87 | 67.72 | 18.16 | 132.22 | 28.27 | 0.00 | 0.00 | 0.00 |
June | 90.51 | 74.27 | 16.24 | 149.33 | 17.82 | 0.00 | 0.00 | 0.00 |
July | 73.26 | 53.36 | 19.90 | 121.68 | 12.70 | 0.00 | 0.00 | 0.00 |
August | 67.45 | 50.11 | 17.33 | 112.30 | 16.06 | 0.00 | 0.00 | 0.00 |
September | 53.98 | 34.06 | 19.92 | 88.01 | 18.55 | 0.00 | 0.00 | 0.00 |
October | 47.61 | 35.79 | 11.83 | 69.22 | 36.66 | 0.00 | 0.00 | 0.00 |
November | 34.72 | 24.95 | 9.77 | 46.87 | 39.88 | 0.00 | 0.00 | 0.00 |
December | 30.34 | 21.95 | 8.39 | 40.57 | 44.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.90 | 42.08 | 14.82 | 87.36 | 29.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.34 | 21.95 | 8.23 | 40.57 | 12.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.51 | 74.27 | 19.92 | 149.33 | 44.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.23 | 27.00 | 8.23 | 50.25 | 40.13 | 0.00 | 0.00 | 0.00 |
February | 34.88 | 22.33 | 12.55 | 46.95 | 31.47 | 0.00 | 0.00 | 0.00 |
March | 50.00 | 32.09 | 17.91 | 70.86 | 33.25 | 0.00 | 0.00 | 0.00 |
April | 77.76 | 60.27 | 17.49 | 117.81 | 31.66 | 0.00 | 0.00 | 0.00 |
May | 85.87 | 67.72 | 18.16 | 132.22 | 28.27 | 0.00 | 0.00 | 0.00 |
June | 90.51 | 74.27 | 16.24 | 149.33 | 17.82 | 0.00 | 0.00 | 0.00 |
July | 73.26 | 53.36 | 19.90 | 121.68 | 12.70 | 0.00 | 0.00 | 0.00 |
August | 67.45 | 50.11 | 17.33 | 112.30 | 16.06 | 0.00 | 0.00 | 0.00 |
September | 53.98 | 34.06 | 19.92 | 88.01 | 18.55 | 0.00 | 0.00 | 0.00 |
October | 47.61 | 35.79 | 11.83 | 69.22 | 36.66 | 0.00 | 0.00 | 0.00 |
November | 34.72 | 24.95 | 9.77 | 46.87 | 39.88 | 0.00 | 0.00 | 0.00 |
December | 30.34 | 21.95 | 8.39 | 40.57 | 44.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.90 | 42.08 | 14.82 | 87.36 | 29.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.34 | 21.95 | 8.23 | 40.57 | 12.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.51 | 74.27 | 19.92 | 149.33 | 44.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.23 | 27.00 | 8.23 | 50.25 | 40.13 | 0.00 | 0.00 | 0.00 |
February | 34.88 | 22.33 | 12.55 | 46.95 | 31.47 | 0.00 | 0.00 | 0.00 |
March | 50.00 | 32.09 | 17.91 | 70.86 | 33.25 | 0.00 | 0.00 | 0.00 |
April | 77.76 | 60.27 | 17.49 | 117.81 | 31.66 | 0.00 | 0.00 | 0.00 |
May | 85.87 | 67.72 | 18.16 | 132.22 | 28.27 | 0.00 | 0.00 | 0.00 |
June | 90.51 | 74.27 | 16.24 | 149.33 | 17.82 | 0.00 | 0.00 | 0.00 |
July | 73.26 | 53.36 | 19.90 | 121.68 | 12.70 | 0.00 | 0.00 | 0.00 |
August | 67.45 | 50.11 | 17.33 | 112.30 | 16.06 | 0.00 | 0.00 | 0.00 |
September | 53.98 | 34.06 | 19.92 | 88.01 | 18.55 | 0.00 | 0.00 | 0.00 |
October | 47.61 | 35.79 | 11.83 | 69.22 | 36.66 | 0.00 | 0.00 | 0.00 |
November | 34.72 | 24.95 | 9.77 | 46.87 | 39.88 | 0.00 | 0.00 | 0.00 |
December | 30.34 | 21.95 | 8.39 | 40.57 | 44.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.90 | 42.08 | 14.82 | 87.36 | 29.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.34 | 21.95 | 8.23 | 40.57 | 12.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.51 | 74.27 | 19.92 | 149.33 | 44.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 105.52 | 44.25 | 6.17 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 97.44 | 36.13 | 5.50 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 141.24 | 39.41 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 222.76 | 43.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 244.26 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 264.14 | 33.19 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 213.90 | 25.84 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 198.32 | 30.77 | 0.00 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 157.63 | 31.46 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 133.51 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 98.59 | 46.08 | 16.67 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 88.11 | 49.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 164.09 | 39.40 | 28.33 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 88.11 | 25.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 264.14 | 49.69 | 16.67 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219920E+09 | 0.137128E+09 | 82791987.57 | 0.338995E+09 | 0.218248E+09 |
February | 0.159647E+09 | 77056095.77 | 82591054.02 | 0.207983E+09 | 0.176034E+09 |
March | 0.235773E+09 | 0.112983E+09 | 0.122790E+09 | 0.341910E+09 | 0.189058E+09 |
April | 0.348085E+09 | 0.198407E+09 | 0.149678E+09 | 0.589579E+09 | 0.135471E+09 |
May | 0.361261E+09 | 0.202215E+09 | 0.159047E+09 | 0.643995E+09 | 0.109758E+09 |
June | 0.371568E+09 | 0.218743E+09 | 0.152826E+09 | 0.740276E+09 | 52104938.52 |
July | 0.279254E+09 | 0.130370E+09 | 0.148884E+09 | 0.566582E+09 | 44788099.92 |
August | 0.266804E+09 | 0.134050E+09 | 0.132754E+09 | 0.540762E+09 | 55498377.89 |
September | 0.224894E+09 | 94606726.51 | 0.130287E+09 | 0.433988E+09 | 72937059.68 |
October | 0.237424E+09 | 0.135680E+09 | 0.101744E+09 | 0.381981E+09 | 0.181605E+09 |
November | 0.210857E+09 | 0.126970E+09 | 83887418.65 | 0.306175E+09 | 0.220910E+09 |
December | 0.176185E+09 | 0.100255E+09 | 75930065.93 | 0.248142E+09 | 0.264148E+09 |
Annual Sum or Average | 0.309167E+10 | 0.166846E+10 | 0.142321E+10 | 0.534037E+10 | 0.172056E+10 |
Minimum of Months | 0.159647E+09 | 77056095.77 | 75930065.93 | 0.207983E+09 | 44788099.92 |
Maximum of Months | 0.371568E+09 | 0.218743E+09 | 0.159047E+09 | 0.740276E+09 | 0.264148E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219920E+09 | 0.137128E+09 | 82791987.57 | 0.338995E+09 | 0.218248E+09 |
February | 0.159647E+09 | 77056095.77 | 82591054.02 | 0.207983E+09 | 0.176034E+09 |
March | 0.235773E+09 | 0.112983E+09 | 0.122790E+09 | 0.341910E+09 | 0.189058E+09 |
April | 0.348085E+09 | 0.198407E+09 | 0.149678E+09 | 0.589579E+09 | 0.135471E+09 |
May | 0.361261E+09 | 0.202215E+09 | 0.159047E+09 | 0.643995E+09 | 0.109758E+09 |
June | 0.371568E+09 | 0.218743E+09 | 0.152826E+09 | 0.740276E+09 | 52104938.52 |
July | 0.279254E+09 | 0.130370E+09 | 0.148884E+09 | 0.566582E+09 | 44788099.92 |
August | 0.266804E+09 | 0.134050E+09 | 0.132754E+09 | 0.540762E+09 | 55498377.89 |
September | 0.224894E+09 | 94606726.51 | 0.130287E+09 | 0.433988E+09 | 72937059.68 |
October | 0.237424E+09 | 0.135680E+09 | 0.101744E+09 | 0.381981E+09 | 0.181605E+09 |
November | 0.210857E+09 | 0.126970E+09 | 83887418.65 | 0.306175E+09 | 0.220910E+09 |
December | 0.176185E+09 | 0.100255E+09 | 75930065.93 | 0.248142E+09 | 0.264148E+09 |
Annual Sum or Average | 0.309167E+10 | 0.166846E+10 | 0.142321E+10 | 0.534037E+10 | 0.172056E+10 |
Minimum of Months | 0.159647E+09 | 77056095.77 | 75930065.93 | 0.207983E+09 | 44788099.92 |
Maximum of Months | 0.371568E+09 | 0.218743E+09 | 0.159047E+09 | 0.740276E+09 | 0.264148E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37734002.91 | 0.00 | 37734002.91 | 36869661.75 | 0.128324E+09 |
February | 38835911.47 | 0.00 | 38835911.47 | 27593720.19 | 0.104701E+09 |
March | 57158307.13 | 6465.08 | 57151842.05 | 62279036.21 | 0.112888E+09 |
April | 67594919.39 | 895159.68 | 66699759.70 | 0.105413E+09 | 77217648.33 |
May | 82257493.35 | 7124142.05 | 75133351.29 | 0.148253E+09 | 58423366.64 |
June | 91304562.79 | 16339277.66 | 74965285.13 | 0.217650E+09 | 27805474.68 |
July | 80517146.00 | 8163032.49 | 72354113.51 | 0.188285E+09 | 24505695.92 |
August | 65396491.52 | 1753237.33 | 63643254.19 | 0.155453E+09 | 31236047.29 |
September | 59554611.04 | 35428.82 | 59519182.22 | 0.125420E+09 | 42104490.24 |
October | 47587604.12 | 0.00 | 47587604.12 | 63105930.74 | 0.107271E+09 |
November | 38370194.72 | 0.00 | 38370194.72 | 30401519.78 | 0.130802E+09 |
December | 35247019.76 | 0.00 | 35247019.76 | 24697340.40 | 0.156120E+09 |
Annual Sum or Average | 0.701558E+09 | 34316743.13 | 0.667242E+09 | 0.118542E+10 | 0.100140E+10 |
Minimum of Months | 35247019.76 | 0.00 | 35247019.76 | 24697340.40 | 24505695.92 |
Maximum of Months | 91304562.79 | 16339277.66 | 75133351.29 | 0.217650E+09 | 0.156120E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37733080.66 | 0.00 | 37733080.66 | 36869073.64 | 0.128322E+09 |
February | 38834823.73 | 0.00 | 38834823.73 | 27592580.08 | 0.104700E+09 |
March | 57156705.66 | 6464.78 | 57150240.88 | 62277211.25 | 0.112887E+09 |
April | 67593348.00 | 895117.73 | 66698230.28 | 0.105411E+09 | 77216507.68 |
May | 82255419.72 | 7123808.13 | 75131611.59 | 0.148251E+09 | 58422115.18 |
June | 91302099.25 | 16338511.82 | 74963587.44 | 0.217647E+09 | 27804640.14 |
July | 80514901.21 | 8162649.88 | 72352251.33 | 0.188282E+09 | 24505237.95 |
August | 65394836.92 | 1753155.16 | 63641681.76 | 0.155451E+09 | 31235311.81 |
September | 59552939.79 | 35427.16 | 59517512.62 | 0.125418E+09 | 42103702.40 |
October | 47586435.87 | 0.00 | 47586435.87 | 63104937.28 | 0.107269E+09 |
November | 38369199.74 | 0.00 | 38369199.74 | 30400695.44 | 0.130800E+09 |
December | 35246110.53 | 0.00 | 35246110.53 | 24696751.99 | 0.156119E+09 |
Annual Sum or Average | 0.701540E+09 | 34315134.66 | 0.667225E+09 | 0.118540E+10 | 0.100139E+10 |
Minimum of Months | 35246110.53 | 0.00 | 35246110.53 | 24696751.99 | 24505237.95 |
Maximum of Months | 91302099.25 | 16338511.82 | 75131611.59 | 0.217647E+09 | 0.156119E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 94355623.09 | 72325097.57 | 22030525.53 | 0.134597E+09 | 0.107483E+09 |
February | 84390078.34 | 54017379.14 | 30372699.19 | 0.113588E+09 | 76123804.72 |
March | 0.133920E+09 | 85960204.55 | 47959866.32 | 0.189785E+09 | 89066398.66 |
April | 0.201565E+09 | 0.156232E+09 | 45332791.60 | 0.305369E+09 | 82067509.69 |
May | 0.230002E+09 | 0.181370E+09 | 48632413.10 | 0.354130E+09 | 75728914.52 |
June | 0.234612E+09 | 0.192506E+09 | 42106032.02 | 0.387075E+09 | 46182193.97 |
July | 0.196231E+09 | 0.142923E+09 | 53307905.49 | 0.325918E+09 | 34017636.57 |
August | 0.180650E+09 | 0.134221E+09 | 46428870.63 | 0.300790E+09 | 43009120.24 |
September | 0.139910E+09 | 88271679.32 | 51638450.33 | 0.228118E+09 | 48071440.34 |
October | 0.127529E+09 | 95846675.28 | 31681874.48 | 0.185408E+09 | 98200536.78 |
November | 89988678.90 | 64658839.94 | 25329838.96 | 0.121487E+09 | 0.103379E+09 |
December | 81252819.85 | 58792405.44 | 22460414.41 | 0.108675E+09 | 0.120207E+09 |
Annual Sum or Average | 0.179441E+10 | 0.132713E+10 | 0.467282E+09 | 0.275494E+10 | 0.923536E+09 |
Minimum of Months | 81252819.85 | 54017379.14 | 22030525.53 | 0.108675E+09 | 34017636.57 |
Maximum of Months | 0.234612E+09 | 0.192506E+09 | 53307905.49 | 0.387075E+09 | 0.120207E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 94355623.09 | 72325097.57 | 22030525.53 | 0.134597E+09 | 0.107483E+09 |
February | 84390078.34 | 54017379.14 | 30372699.19 | 0.113588E+09 | 76123804.72 |
March | 0.133920E+09 | 85960204.55 | 47959866.32 | 0.189785E+09 | 89066398.66 |
April | 0.201565E+09 | 0.156232E+09 | 45332791.60 | 0.305369E+09 | 82067509.69 |
May | 0.230002E+09 | 0.181370E+09 | 48632413.10 | 0.354130E+09 | 75728914.52 |
June | 0.234612E+09 | 0.192506E+09 | 42106032.02 | 0.387075E+09 | 46182193.97 |
July | 0.196231E+09 | 0.142923E+09 | 53307905.49 | 0.325918E+09 | 34017636.57 |
August | 0.180650E+09 | 0.134221E+09 | 46428870.63 | 0.300790E+09 | 43009120.24 |
September | 0.139910E+09 | 88271679.32 | 51638450.33 | 0.228118E+09 | 48071440.34 |
October | 0.127529E+09 | 95846675.28 | 31681874.48 | 0.185408E+09 | 98200536.78 |
November | 89988678.90 | 64658839.94 | 25329838.96 | 0.121487E+09 | 0.103379E+09 |
December | 81252819.85 | 58792405.44 | 22460414.41 | 0.108675E+09 | 0.120207E+09 |
Annual Sum or Average | 0.179441E+10 | 0.132713E+10 | 0.467282E+09 | 0.275494E+10 | 0.923536E+09 |
Minimum of Months | 81252819.85 | 54017379.14 | 22030525.53 | 0.108675E+09 | 34017636.57 |
Maximum of Months | 0.234612E+09 | 0.192506E+09 | 53307905.49 | 0.387075E+09 | 0.120207E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 94355623.09 | 72325097.57 | 22030525.53 | 0.134597E+09 | 0.107483E+09 |
February | 84390078.34 | 54017379.14 | 30372699.19 | 0.113588E+09 | 76123804.72 |
March | 0.133920E+09 | 85960204.55 | 47959866.32 | 0.189785E+09 | 89066398.66 |
April | 0.201565E+09 | 0.156232E+09 | 45332791.60 | 0.305369E+09 | 82067509.69 |
May | 0.230002E+09 | 0.181370E+09 | 48632413.10 | 0.354130E+09 | 75728914.52 |
June | 0.234612E+09 | 0.192506E+09 | 42106032.02 | 0.387075E+09 | 46182193.97 |
July | 0.196231E+09 | 0.142923E+09 | 53307905.49 | 0.325918E+09 | 34017636.57 |
August | 0.180650E+09 | 0.134221E+09 | 46428870.63 | 0.300790E+09 | 43009120.24 |
September | 0.139910E+09 | 88271679.32 | 51638450.33 | 0.228118E+09 | 48071440.34 |
October | 0.127529E+09 | 95846675.28 | 31681874.48 | 0.185408E+09 | 98200536.78 |
November | 89988678.90 | 64658839.94 | 25329838.96 | 0.121487E+09 | 0.103379E+09 |
December | 81252819.85 | 58792405.44 | 22460414.41 | 0.108675E+09 | 0.120207E+09 |
Annual Sum or Average | 0.179441E+10 | 0.132713E+10 | 0.467282E+09 | 0.275494E+10 | 0.923536E+09 |
Minimum of Months | 81252819.85 | 54017379.14 | 22030525.53 | 0.108675E+09 | 34017636.57 |
Maximum of Months | 0.234612E+09 | 0.192506E+09 | 53307905.49 | 0.387075E+09 | 0.120207E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 94355623.09 | 72325097.57 | 22030525.53 | 0.134597E+09 | 0.107483E+09 |
February | 84390078.34 | 54017379.14 | 30372699.19 | 0.113588E+09 | 76123804.72 |
March | 0.133920E+09 | 85960204.55 | 47959866.32 | 0.189785E+09 | 89066398.66 |
April | 0.201565E+09 | 0.156232E+09 | 45332791.60 | 0.305369E+09 | 82067509.69 |
May | 0.230002E+09 | 0.181370E+09 | 48632413.10 | 0.354130E+09 | 75728914.52 |
June | 0.234612E+09 | 0.192506E+09 | 42106032.02 | 0.387075E+09 | 46182193.97 |
July | 0.196231E+09 | 0.142923E+09 | 53307905.49 | 0.325918E+09 | 34017636.57 |
August | 0.180650E+09 | 0.134221E+09 | 46428870.63 | 0.300790E+09 | 43009120.24 |
September | 0.139910E+09 | 88271679.32 | 51638450.33 | 0.228118E+09 | 48071440.34 |
October | 0.127529E+09 | 95846675.28 | 31681874.48 | 0.185408E+09 | 98200536.78 |
November | 89988678.90 | 64658839.94 | 25329838.96 | 0.121487E+09 | 0.103379E+09 |
December | 81252819.85 | 58792405.44 | 22460414.41 | 0.108675E+09 | 0.120207E+09 |
Annual Sum or Average | 0.179441E+10 | 0.132713E+10 | 0.467282E+09 | 0.275494E+10 | 0.923536E+09 |
Minimum of Months | 81252819.85 | 54017379.14 | 22030525.53 | 0.108675E+09 | 34017636.57 |
Maximum of Months | 0.234612E+09 | 0.192506E+09 | 53307905.49 | 0.387075E+09 | 0.120207E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 94355623.09 | 72325097.57 | 22030525.53 | 0.134597E+09 | 0.107483E+09 |
February | 84390078.34 | 54017379.14 | 30372699.19 | 0.113588E+09 | 76123804.72 |
March | 0.133920E+09 | 85960204.55 | 47959866.32 | 0.189785E+09 | 89066398.66 |
April | 0.201565E+09 | 0.156232E+09 | 45332791.60 | 0.305369E+09 | 82067509.69 |
May | 0.230002E+09 | 0.181370E+09 | 48632413.10 | 0.354130E+09 | 75728914.52 |
June | 0.234612E+09 | 0.192506E+09 | 42106032.02 | 0.387075E+09 | 46182193.97 |
July | 0.196231E+09 | 0.142923E+09 | 53307905.49 | 0.325918E+09 | 34017636.57 |
August | 0.180650E+09 | 0.134221E+09 | 46428870.63 | 0.300790E+09 | 43009120.24 |
September | 0.139910E+09 | 88271679.32 | 51638450.33 | 0.228118E+09 | 48071440.34 |
October | 0.127529E+09 | 95846675.28 | 31681874.48 | 0.185408E+09 | 98200536.78 |
November | 89988678.90 | 64658839.94 | 25329838.96 | 0.121487E+09 | 0.103379E+09 |
December | 81252819.85 | 58792405.44 | 22460414.41 | 0.108675E+09 | 0.120207E+09 |
Annual Sum or Average | 0.179441E+10 | 0.132713E+10 | 0.467282E+09 | 0.275494E+10 | 0.923536E+09 |
Minimum of Months | 81252819.85 | 54017379.14 | 22030525.53 | 0.108675E+09 | 34017636.57 |
Maximum of Months | 0.234612E+09 | 0.192506E+09 | 53307905.49 | 0.387075E+09 | 0.120207E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 94355623.09 | 72325097.57 | 22030525.53 | 0.134597E+09 | 0.107483E+09 |
February | 84390078.34 | 54017379.14 | 30372699.19 | 0.113588E+09 | 76123804.72 |
March | 0.133920E+09 | 85960204.55 | 47959866.32 | 0.189785E+09 | 89066398.66 |
April | 0.201565E+09 | 0.156232E+09 | 45332791.60 | 0.305369E+09 | 82067509.69 |
May | 0.230002E+09 | 0.181370E+09 | 48632413.10 | 0.354130E+09 | 75728914.52 |
June | 0.234612E+09 | 0.192506E+09 | 42106032.02 | 0.387075E+09 | 46182193.97 |
July | 0.196231E+09 | 0.142923E+09 | 53307905.49 | 0.325918E+09 | 34017636.57 |
August | 0.180650E+09 | 0.134221E+09 | 46428870.63 | 0.300790E+09 | 43009120.24 |
September | 0.139910E+09 | 88271679.32 | 51638450.33 | 0.228118E+09 | 48071440.34 |
October | 0.127529E+09 | 95846675.28 | 31681874.48 | 0.185408E+09 | 98200536.78 |
November | 89988678.90 | 64658839.94 | 25329838.96 | 0.121487E+09 | 0.103379E+09 |
December | 81252819.85 | 58792405.44 | 22460414.41 | 0.108675E+09 | 0.120207E+09 |
Annual Sum or Average | 0.179441E+10 | 0.132713E+10 | 0.467282E+09 | 0.275494E+10 | 0.923536E+09 |
Minimum of Months | 81252819.85 | 54017379.14 | 22030525.53 | 0.108675E+09 | 34017636.57 |
Maximum of Months | 0.234612E+09 | 0.192506E+09 | 53307905.49 | 0.387075E+09 | 0.120207E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 94355623.09 | 72325097.57 | 22030525.53 | 0.134597E+09 | 0.107483E+09 |
February | 84390078.34 | 54017379.14 | 30372699.19 | 0.113588E+09 | 76123804.72 |
March | 0.133920E+09 | 85960204.55 | 47959866.32 | 0.189785E+09 | 89066398.66 |
April | 0.201565E+09 | 0.156232E+09 | 45332791.60 | 0.305369E+09 | 82067509.69 |
May | 0.230002E+09 | 0.181370E+09 | 48632413.10 | 0.354130E+09 | 75728914.52 |
June | 0.234612E+09 | 0.192506E+09 | 42106032.02 | 0.387075E+09 | 46182193.97 |
July | 0.196231E+09 | 0.142923E+09 | 53307905.49 | 0.325918E+09 | 34017636.57 |
August | 0.180650E+09 | 0.134221E+09 | 46428870.63 | 0.300790E+09 | 43009120.24 |
September | 0.139910E+09 | 88271679.32 | 51638450.33 | 0.228118E+09 | 48071440.34 |
October | 0.127529E+09 | 95846675.28 | 31681874.48 | 0.185408E+09 | 98200536.78 |
November | 89988678.90 | 64658839.94 | 25329838.96 | 0.121487E+09 | 0.103379E+09 |
December | 81252819.85 | 58792405.44 | 22460414.41 | 0.108675E+09 | 0.120207E+09 |
Annual Sum or Average | 0.179441E+10 | 0.132713E+10 | 0.467282E+09 | 0.275494E+10 | 0.923536E+09 |
Minimum of Months | 81252819.85 | 54017379.14 | 22030525.53 | 0.108675E+09 | 34017636.57 |
Maximum of Months | 0.234612E+09 | 0.192506E+09 | 53307905.49 | 0.387075E+09 | 0.120207E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 94355623.09 | 72325097.57 | 22030525.53 | 0.134597E+09 | 0.107483E+09 |
February | 84390078.34 | 54017379.14 | 30372699.19 | 0.113588E+09 | 76123804.72 |
March | 0.133920E+09 | 85960204.55 | 47959866.32 | 0.189785E+09 | 89066398.66 |
April | 0.201565E+09 | 0.156232E+09 | 45332791.60 | 0.305369E+09 | 82067509.69 |
May | 0.230002E+09 | 0.181370E+09 | 48632413.10 | 0.354130E+09 | 75728914.52 |
June | 0.234612E+09 | 0.192506E+09 | 42106032.02 | 0.387075E+09 | 46182193.97 |
July | 0.196231E+09 | 0.142923E+09 | 53307905.49 | 0.325918E+09 | 34017636.57 |
August | 0.180650E+09 | 0.134221E+09 | 46428870.63 | 0.300790E+09 | 43009120.24 |
September | 0.139910E+09 | 88271679.32 | 51638450.33 | 0.228118E+09 | 48071440.34 |
October | 0.127529E+09 | 95846675.28 | 31681874.48 | 0.185408E+09 | 98200536.78 |
November | 89988678.90 | 64658839.94 | 25329838.96 | 0.121487E+09 | 0.103379E+09 |
December | 81252819.85 | 58792405.44 | 22460414.41 | 0.108675E+09 | 0.120207E+09 |
Annual Sum or Average | 0.179441E+10 | 0.132713E+10 | 0.467282E+09 | 0.275494E+10 | 0.923536E+09 |
Minimum of Months | 81252819.85 | 54017379.14 | 22030525.53 | 0.108675E+09 | 34017636.57 |
Maximum of Months | 0.234612E+09 | 0.192506E+09 | 53307905.49 | 0.387075E+09 | 0.120207E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 94355623.09 | 72325097.57 | 22030525.53 | 0.134597E+09 | 0.107483E+09 |
February | 84390078.34 | 54017379.14 | 30372699.19 | 0.113588E+09 | 76123804.72 |
March | 0.133920E+09 | 85960204.55 | 47959866.32 | 0.189785E+09 | 89066398.66 |
April | 0.201565E+09 | 0.156232E+09 | 45332791.60 | 0.305369E+09 | 82067509.69 |
May | 0.230002E+09 | 0.181370E+09 | 48632413.10 | 0.354130E+09 | 75728914.52 |
June | 0.234612E+09 | 0.192506E+09 | 42106032.02 | 0.387075E+09 | 46182193.97 |
July | 0.196231E+09 | 0.142923E+09 | 53307905.49 | 0.325918E+09 | 34017636.57 |
August | 0.180650E+09 | 0.134221E+09 | 46428870.63 | 0.300790E+09 | 43009120.24 |
September | 0.139910E+09 | 88271679.32 | 51638450.33 | 0.228118E+09 | 48071440.34 |
October | 0.127529E+09 | 95846675.28 | 31681874.48 | 0.185408E+09 | 98200536.78 |
November | 89988678.90 | 64658839.94 | 25329838.96 | 0.121487E+09 | 0.103379E+09 |
December | 81252819.85 | 58792405.44 | 22460414.41 | 0.108675E+09 | 0.120207E+09 |
Annual Sum or Average | 0.179441E+10 | 0.132713E+10 | 0.467282E+09 | 0.275494E+10 | 0.923536E+09 |
Minimum of Months | 81252819.85 | 54017379.14 | 22030525.53 | 0.108675E+09 | 34017636.57 |
Maximum of Months | 0.234612E+09 | 0.192506E+09 | 53307905.49 | 0.387075E+09 | 0.120207E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 94355623.09 | 72325097.57 | 22030525.53 | 0.134597E+09 | 0.107483E+09 |
February | 84390078.34 | 54017379.14 | 30372699.19 | 0.113588E+09 | 76123804.72 |
March | 0.133920E+09 | 85960204.55 | 47959866.32 | 0.189785E+09 | 89066398.66 |
April | 0.201565E+09 | 0.156232E+09 | 45332791.60 | 0.305369E+09 | 82067509.69 |
May | 0.230002E+09 | 0.181370E+09 | 48632413.10 | 0.354130E+09 | 75728914.52 |
June | 0.234612E+09 | 0.192506E+09 | 42106032.02 | 0.387075E+09 | 46182193.97 |
July | 0.196231E+09 | 0.142923E+09 | 53307905.49 | 0.325918E+09 | 34017636.57 |
August | 0.180650E+09 | 0.134221E+09 | 46428870.63 | 0.300790E+09 | 43009120.24 |
September | 0.139910E+09 | 88271679.32 | 51638450.33 | 0.228118E+09 | 48071440.34 |
October | 0.127529E+09 | 95846675.28 | 31681874.48 | 0.185408E+09 | 98200536.78 |
November | 89988678.90 | 64658839.94 | 25329838.96 | 0.121487E+09 | 0.103379E+09 |
December | 81252819.85 | 58792405.44 | 22460414.41 | 0.108675E+09 | 0.120207E+09 |
Annual Sum or Average | 0.179441E+10 | 0.132713E+10 | 0.467282E+09 | 0.275494E+10 | 0.923536E+09 |
Minimum of Months | 81252819.85 | 54017379.14 | 22030525.53 | 0.108675E+09 | 34017636.57 |
Maximum of Months | 0.234612E+09 | 0.192506E+09 | 53307905.49 | 0.387075E+09 | 0.120207E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 94355623.09 | 72325097.57 | 22030525.53 | 0.134597E+09 | 0.107483E+09 |
February | 84390078.34 | 54017379.14 | 30372699.19 | 0.113588E+09 | 76123804.72 |
March | 0.133920E+09 | 85960204.55 | 47959866.32 | 0.189785E+09 | 89066398.66 |
April | 0.201565E+09 | 0.156232E+09 | 45332791.60 | 0.305369E+09 | 82067509.69 |
May | 0.230002E+09 | 0.181370E+09 | 48632413.10 | 0.354130E+09 | 75728914.52 |
June | 0.234612E+09 | 0.192506E+09 | 42106032.02 | 0.387075E+09 | 46182193.97 |
July | 0.196231E+09 | 0.142923E+09 | 53307905.49 | 0.325918E+09 | 34017636.57 |
August | 0.180650E+09 | 0.134221E+09 | 46428870.63 | 0.300790E+09 | 43009120.24 |
September | 0.139910E+09 | 88271679.32 | 51638450.33 | 0.228118E+09 | 48071440.34 |
October | 0.127529E+09 | 95846675.28 | 31681874.48 | 0.185408E+09 | 98200536.78 |
November | 89988678.90 | 64658839.94 | 25329838.96 | 0.121487E+09 | 0.103379E+09 |
December | 81252819.85 | 58792405.44 | 22460414.41 | 0.108675E+09 | 0.120207E+09 |
Annual Sum or Average | 0.179441E+10 | 0.132713E+10 | 0.467282E+09 | 0.275494E+10 | 0.923536E+09 |
Minimum of Months | 81252819.85 | 54017379.14 | 22030525.53 | 0.108675E+09 | 34017636.57 |
Maximum of Months | 0.234612E+09 | 0.192506E+09 | 53307905.49 | 0.387075E+09 | 0.120207E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 94355623.09 | 72325097.57 | 22030525.53 | 0.134597E+09 | 0.107483E+09 |
February | 84390078.34 | 54017379.14 | 30372699.19 | 0.113588E+09 | 76123804.72 |
March | 0.133920E+09 | 85960204.55 | 47959866.32 | 0.189785E+09 | 89066398.66 |
April | 0.201565E+09 | 0.156232E+09 | 45332791.60 | 0.305369E+09 | 82067509.69 |
May | 0.230002E+09 | 0.181370E+09 | 48632413.10 | 0.354130E+09 | 75728914.52 |
June | 0.234612E+09 | 0.192506E+09 | 42106032.02 | 0.387075E+09 | 46182193.97 |
July | 0.196231E+09 | 0.142923E+09 | 53307905.49 | 0.325918E+09 | 34017636.57 |
August | 0.180650E+09 | 0.134221E+09 | 46428870.63 | 0.300790E+09 | 43009120.24 |
September | 0.139910E+09 | 88271679.32 | 51638450.33 | 0.228118E+09 | 48071440.34 |
October | 0.127529E+09 | 95846675.28 | 31681874.48 | 0.185408E+09 | 98200536.78 |
November | 89988678.90 | 64658839.94 | 25329838.96 | 0.121487E+09 | 0.103379E+09 |
December | 81252819.85 | 58792405.44 | 22460414.41 | 0.108675E+09 | 0.120207E+09 |
Annual Sum or Average | 0.179441E+10 | 0.132713E+10 | 0.467282E+09 | 0.275494E+10 | 0.923536E+09 |
Minimum of Months | 81252819.85 | 54017379.14 | 22030525.53 | 0.108675E+09 | 34017636.57 |
Maximum of Months | 0.234612E+09 | 0.192506E+09 | 53307905.49 | 0.387075E+09 | 0.120207E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 94355623.09 | 72325097.57 | 22030525.53 | 0.134597E+09 | 0.107483E+09 |
February | 84390078.34 | 54017379.14 | 30372699.19 | 0.113588E+09 | 76123804.72 |
March | 0.133920E+09 | 85960204.55 | 47959866.32 | 0.189785E+09 | 89066398.66 |
April | 0.201565E+09 | 0.156232E+09 | 45332791.60 | 0.305369E+09 | 82067509.69 |
May | 0.230002E+09 | 0.181370E+09 | 48632413.10 | 0.354130E+09 | 75728914.52 |
June | 0.234612E+09 | 0.192506E+09 | 42106032.02 | 0.387075E+09 | 46182193.97 |
July | 0.196231E+09 | 0.142923E+09 | 53307905.49 | 0.325918E+09 | 34017636.57 |
August | 0.180650E+09 | 0.134221E+09 | 46428870.63 | 0.300790E+09 | 43009120.24 |
September | 0.139910E+09 | 88271679.32 | 51638450.33 | 0.228118E+09 | 48071440.34 |
October | 0.127529E+09 | 95846675.28 | 31681874.48 | 0.185408E+09 | 98200536.78 |
November | 89988678.90 | 64658839.94 | 25329838.96 | 0.121487E+09 | 0.103379E+09 |
December | 81252819.85 | 58792405.44 | 22460414.41 | 0.108675E+09 | 0.120207E+09 |
Annual Sum or Average | 0.179441E+10 | 0.132713E+10 | 0.467282E+09 | 0.275494E+10 | 0.923536E+09 |
Minimum of Months | 81252819.85 | 54017379.14 | 22030525.53 | 0.108675E+09 | 34017636.57 |
Maximum of Months | 0.234612E+09 | 0.192506E+09 | 53307905.49 | 0.387075E+09 | 0.120207E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 94355623.09 | 72325097.57 | 22030525.53 | 0.134597E+09 | 0.107483E+09 |
February | 84390078.34 | 54017379.14 | 30372699.19 | 0.113588E+09 | 76123804.72 |
March | 0.133920E+09 | 85960204.55 | 47959866.32 | 0.189785E+09 | 89066398.66 |
April | 0.201565E+09 | 0.156232E+09 | 45332791.60 | 0.305369E+09 | 82067509.69 |
May | 0.230002E+09 | 0.181370E+09 | 48632413.10 | 0.354130E+09 | 75728914.52 |
June | 0.234612E+09 | 0.192506E+09 | 42106032.02 | 0.387075E+09 | 46182193.97 |
July | 0.196231E+09 | 0.142923E+09 | 53307905.49 | 0.325918E+09 | 34017636.57 |
August | 0.180650E+09 | 0.134221E+09 | 46428870.63 | 0.300790E+09 | 43009120.24 |
September | 0.139910E+09 | 88271679.32 | 51638450.33 | 0.228118E+09 | 48071440.34 |
October | 0.127529E+09 | 95846675.28 | 31681874.48 | 0.185408E+09 | 98200536.78 |
November | 89988678.90 | 64658839.94 | 25329838.96 | 0.121487E+09 | 0.103379E+09 |
December | 81252819.85 | 58792405.44 | 22460414.41 | 0.108675E+09 | 0.120207E+09 |
Annual Sum or Average | 0.179441E+10 | 0.132713E+10 | 0.467282E+09 | 0.275494E+10 | 0.923536E+09 |
Minimum of Months | 81252819.85 | 54017379.14 | 22030525.53 | 0.108675E+09 | 34017636.57 |
Maximum of Months | 0.234612E+09 | 0.192506E+09 | 53307905.49 | 0.387075E+09 | 0.120207E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.282623E+09 | 0.118523E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.235728E+09 | 87417273.76 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.378293E+09 | 0.105569E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.577395E+09 | 0.112157E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.654220E+09 | 0.114770E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.684662E+09 | 86037702.68 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.572913E+09 | 69197652.93 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.531180E+09 | 82401756.43 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.408564E+09 | 81553298.58 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.357597E+09 | 0.132389E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.255549E+09 | 0.119450E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.236002E+09 | 0.133082E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.517473E+10 | 0.124255E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.235728E+09 | 69197652.93 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.684662E+09 | 0.133082E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 279.54 | 257.66 | 192.39 | 102.40 | 90.00 | 0.00 | 0.00 |
February | 193.07 | 230.40 | 164.09 | 63.70 | 100.39 | 0.00 | 0.00 |
March | 299.72 | 223.37 | 218.74 | 84.37 | 134.36 | 0.00 | 0.00 |
April | 536.03 | 163.88 | 320.74 | 153.78 | 166.96 | 0.00 | 0.00 |
May | 588.99 | 122.99 | 331.18 | 156.32 | 174.87 | 0.00 | 0.00 |
June | 736.70 | 59.22 | 357.15 | 181.39 | 175.76 | 0.00 | 0.00 |
July | 562.45 | 50.53 | 268.65 | 103.44 | 165.20 | 0.00 | 0.00 |
August | 519.21 | 64.11 | 248.06 | 101.41 | 146.65 | 0.00 | 0.00 |
September | 431.61 | 88.74 | 219.48 | 73.03 | 146.45 | 0.00 | 0.00 |
October | 331.18 | 214.53 | 212.82 | 101.31 | 111.51 | 0.00 | 0.00 |
November | 257.83 | 269.51 | 192.30 | 97.97 | 94.33 | 0.00 | 0.00 |
December | 201.93 | 312.02 | 157.88 | 74.86 | 83.02 | 0.00 | 0.00 |
Annual Sum or Average | 412.45 | 171.21 | 240.56 | 107.99 | 132.58 | 0.00 | 0.00 |
Minimum of Months | 193.07 | 50.53 | 157.88 | 63.70 | 83.02 | 0.00 | 0.00 |
Maximum of Months | 736.70 | 312.02 | 357.15 | 181.39 | 175.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 703.54 | 561.81 | 493.20 | 378.04 | 115.15 | 0.00 | 0.00 |
February | 657.34 | 440.53 | 488.37 | 312.60 | 175.77 | 0.00 | 0.00 |
March | 992.01 | 465.55 | 700.00 | 449.31 | 250.69 | 0.00 | 0.00 |
April | 1649.37 | 443.27 | 1088.70 | 843.85 | 244.85 | 0.00 | 0.00 |
May | 1851.04 | 395.84 | 1202.22 | 948.02 | 254.20 | 0.00 | 0.00 |
June | 2090.68 | 249.44 | 1267.20 | 1039.77 | 227.42 | 0.00 | 0.00 |
July | 1703.57 | 177.81 | 1025.70 | 747.06 | 278.64 | 0.00 | 0.00 |
August | 1572.23 | 224.81 | 944.26 | 701.58 | 242.68 | 0.00 | 0.00 |
September | 1232.12 | 259.65 | 755.69 | 476.78 | 278.91 | 0.00 | 0.00 |
October | 969.13 | 513.29 | 666.59 | 500.99 | 165.60 | 0.00 | 0.00 |
November | 656.18 | 558.37 | 486.05 | 349.24 | 136.81 | 0.00 | 0.00 |
December | 568.05 | 628.32 | 424.71 | 307.31 | 117.40 | 0.00 | 0.00 |
Annual Sum or Average | 1223.02 | 409.99 | 796.60 | 589.16 | 207.44 | 0.00 | 0.00 |
Minimum of Months | 568.05 | 177.81 | 424.71 | 307.31 | 115.15 | 0.00 | 0.00 |
Maximum of Months | 2090.68 | 628.32 | 1267.20 | 1039.77 | 278.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 13306.71 | 4862.39 | 2447.60 | 1890.10 | 557.50 | 0.00 | 0.00 |
February | 13922.05 | 3973.34 | 2381.44 | 1530.48 | 850.95 | 0.00 | 0.00 |
March | 18834.86 | 4086.92 | 3367.32 | 2153.66 | 1213.66 | 0.00 | 0.00 |
April | 32203.42 | 4754.00 | 5204.30 | 4018.88 | 1185.42 | 0.00 | 0.00 |
May | 39625.93 | 5965.48 | 5727.98 | 4497.30 | 1230.68 | 0.00 | 0.00 |
June | 48551.63 | 7536.78 | 6031.62 | 4930.58 | 1101.04 | 0.00 | 0.00 |
July | 39375.82 | 5899.69 | 4887.63 | 3538.63 | 1349.00 | 0.00 | 0.00 |
August | 35266.62 | 6481.01 | 4504.95 | 3330.03 | 1174.92 | 0.00 | 0.00 |
September | 25848.32 | 5466.92 | 3623.43 | 2273.13 | 1350.31 | 0.00 | 0.00 |
October | 18759.77 | 5819.43 | 3228.06 | 2426.33 | 801.73 | 0.00 | 0.00 |
November | 12862.90 | 4652.41 | 2398.76 | 1736.40 | 662.36 | 0.00 | 0.00 |
December | 11728.24 | 5736.85 | 2117.62 | 1549.25 | 568.38 | 0.00 | 0.00 |
Annual Sum or Average | 25911.35 | 5446.47 | 3833.26 | 2828.95 | 1004.31 | 0.00 | 0.00 |
Minimum of Months | 11728.24 | 3973.34 | 2117.62 | 1530.48 | 557.50 | 0.00 | 0.00 |
Maximum of Months | 48551.63 | 7536.78 | 6031.62 | 4930.58 | 1350.31 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.748707E+09 | 0.690119E+09 | 0.515306E+09 | 0.274255E+09 | 0.241051E+09 | 0.00 | 0.00 |
February | 0.467074E+09 | 0.557392E+09 | 0.396965E+09 | 0.154112E+09 | 0.242853E+09 | 0.00 | 0.00 |
March | 0.802763E+09 | 0.598277E+09 | 0.585860E+09 | 0.225979E+09 | 0.359881E+09 | 0.00 | 0.00 |
April | 0.138939E+10 | 0.424787E+09 | 0.831359E+09 | 0.398605E+09 | 0.432754E+09 | 0.00 | 0.00 |
May | 0.157754E+10 | 0.329404E+09 | 0.887036E+09 | 0.418677E+09 | 0.468359E+09 | 0.00 | 0.00 |
June | 0.190952E+10 | 0.153493E+09 | 0.925743E+09 | 0.470163E+09 | 0.455580E+09 | 0.00 | 0.00 |
July | 0.150647E+10 | 0.135327E+09 | 0.719541E+09 | 0.277066E+09 | 0.442475E+09 | 0.00 | 0.00 |
August | 0.139066E+10 | 0.171703E+09 | 0.664400E+09 | 0.271606E+09 | 0.392794E+09 | 0.00 | 0.00 |
September | 0.111875E+10 | 0.230015E+09 | 0.568895E+09 | 0.189284E+09 | 0.379611E+09 | 0.00 | 0.00 |
October | 0.887026E+09 | 0.574603E+09 | 0.570023E+09 | 0.271360E+09 | 0.298663E+09 | 0.00 | 0.00 |
November | 0.668303E+09 | 0.698574E+09 | 0.498454E+09 | 0.253940E+09 | 0.244514E+09 | 0.00 | 0.00 |
December | 0.540860E+09 | 0.835715E+09 | 0.422862E+09 | 0.200509E+09 | 0.222353E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.130071E+11 | 0.539941E+10 | 0.758645E+10 | 0.340556E+10 | 0.418089E+10 | 0.00 | 0.00 |
Minimum of Months | 0.467074E+09 | 0.135327E+09 | 0.396965E+09 | 0.154112E+09 | 0.222353E+09 | 0.00 | 0.00 |
Maximum of Months | 0.190952E+10 | 0.835715E+09 | 0.925743E+09 | 0.470163E+09 | 0.468359E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.188436E+10 | 0.150476E+10 | 0.132098E+10 | 0.101255E+10 | 0.308427E+09 | 0.00 | 0.00 |
February | 0.159023E+10 | 0.106573E+10 | 0.118146E+10 | 0.756243E+09 | 0.425218E+09 | 0.00 | 0.00 |
March | 0.265699E+10 | 0.124693E+10 | 0.187488E+10 | 0.120344E+10 | 0.671438E+09 | 0.00 | 0.00 |
April | 0.427516E+10 | 0.114895E+10 | 0.282191E+10 | 0.218725E+10 | 0.634659E+09 | 0.00 | 0.00 |
May | 0.495782E+10 | 0.106020E+10 | 0.322003E+10 | 0.253918E+10 | 0.680854E+09 | 0.00 | 0.00 |
June | 0.541905E+10 | 0.646551E+09 | 0.328457E+10 | 0.269509E+10 | 0.589484E+09 | 0.00 | 0.00 |
July | 0.456285E+10 | 0.476247E+09 | 0.274724E+10 | 0.200093E+10 | 0.746311E+09 | 0.00 | 0.00 |
August | 0.421106E+10 | 0.602128E+09 | 0.252910E+10 | 0.187910E+10 | 0.650004E+09 | 0.00 | 0.00 |
September | 0.319366E+10 | 0.673000E+09 | 0.195874E+10 | 0.123580E+10 | 0.722938E+09 | 0.00 | 0.00 |
October | 0.259571E+10 | 0.137481E+10 | 0.178540E+10 | 0.134185E+10 | 0.443546E+09 | 0.00 | 0.00 |
November | 0.170082E+10 | 0.144731E+10 | 0.125984E+10 | 0.905224E+09 | 0.354618E+09 | 0.00 | 0.00 |
December | 0.152145E+10 | 0.168290E+10 | 0.113754E+10 | 0.823094E+09 | 0.314446E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.385692E+11 | 0.129295E+11 | 0.251217E+11 | 0.185798E+11 | 0.654194E+10 | 0.00 | 0.00 |
Minimum of Months | 0.152145E+10 | 0.476247E+09 | 0.113754E+10 | 0.756243E+09 | 0.308427E+09 | 0.00 | 0.00 |
Maximum of Months | 0.541905E+10 | 0.168290E+10 | 0.328457E+10 | 0.269509E+10 | 0.746311E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.356407E+11 | 0.130234E+11 | 0.655566E+10 | 0.506246E+10 | 0.149320E+10 | 0.00 | 0.00 |
February | 0.336802E+11 | 0.961231E+10 | 0.576118E+10 | 0.370255E+10 | 0.205863E+10 | 0.00 | 0.00 |
March | 0.504473E+11 | 0.109464E+11 | 0.901902E+10 | 0.576836E+10 | 0.325067E+10 | 0.00 | 0.00 |
April | 0.834713E+11 | 0.123224E+11 | 0.134896E+11 | 0.104169E+11 | 0.307261E+10 | 0.00 | 0.00 |
May | 0.106134E+12 | 0.159779E+11 | 0.153418E+11 | 0.120456E+11 | 0.329625E+10 | 0.00 | 0.00 |
June | 0.125846E+12 | 0.195353E+11 | 0.156340E+11 | 0.127801E+11 | 0.285390E+10 | 0.00 | 0.00 |
July | 0.105464E+12 | 0.158017E+11 | 0.130910E+11 | 0.947787E+10 | 0.361315E+10 | 0.00 | 0.00 |
August | 0.944581E+11 | 0.173587E+11 | 0.120661E+11 | 0.891916E+10 | 0.314690E+10 | 0.00 | 0.00 |
September | 0.669988E+11 | 0.141703E+11 | 0.939194E+10 | 0.589194E+10 | 0.350000E+10 | 0.00 | 0.00 |
October | 0.502462E+11 | 0.155868E+11 | 0.864604E+10 | 0.649868E+10 | 0.214736E+10 | 0.00 | 0.00 |
November | 0.333406E+11 | 0.120590E+11 | 0.621758E+10 | 0.450075E+10 | 0.171683E+10 | 0.00 | 0.00 |
December | 0.314129E+11 | 0.153656E+11 | 0.567184E+10 | 0.414950E+10 | 0.152234E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.817140E+12 | 0.171760E+12 | 0.120886E+12 | 0.892138E+11 | 0.316718E+11 | 0.00 | 0.00 |
Minimum of Months | 0.314129E+11 | 0.961231E+10 | 0.567184E+10 | 0.370255E+10 | 0.149320E+10 | 0.00 | 0.00 |
Maximum of Months | 0.125846E+12 | 0.195353E+11 | 0.156340E+11 | 0.127801E+11 | 0.361315E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.47 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.35 | 6.24 | 2.64 | 2.53 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.67 | 1.96 | 3.53 | 3.02 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.14 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.07 | -4.9 | 3.62 | 8.60 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.28 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.99 | 9.86 | 3.72 | 19.28 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.15 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.59 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.99 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.80 | 1.49 | 3.02 | 1.83 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.57 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.15 | 11.45 | 3.72 | 19.28 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.73 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.42 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.79 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.57 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.57 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.74 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.40 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.27 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.81 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 19.01 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.20 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.90 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.73 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.81 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.2 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.59 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.4 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.42 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.97 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.24 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.53 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.48 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.5 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.6 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.6 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.73 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.18 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.71 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.57 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.18 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.11 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.19 | 16-AUG-10:00 | 35.00 | 17.00 | 2.10 | 24.33 | 140.50 | 837.00 |
September | 22.23 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.53 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.06 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.06 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.18 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.73 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.70 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 14.00 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.75 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.18 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.11 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.17 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.18 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.800442E+09 | -720553119.6 | 0.00 | 0.00 | 744.00 | 0.00 | -79888492.1 | 58.99 | 0.00 | 0.00 |
February | 0.729109E+09 | -655398481.9 | 0.00 | 0.00 | 672.00 | 0.00 | -73710688.1 | 58.99 | 0.00 | 0.00 |
March | 0.807107E+09 | -728583758.5 | 0.00 | 0.00 | 744.00 | 0.00 | -78522771.4 | 58.99 | 0.00 | 0.00 |
April | 0.692897E+09 | -623094810.1 | 0.00 | 0.00 | 720.00 | 0.00 | -69801749.5 | 58.99 | 0.00 | 0.00 |
May | 0.658543E+09 | -587757315.1 | 0.00 | 0.00 | 744.00 | 0.00 | -70786151.6 | 58.99 | 0.00 | 0.00 |
June | 0.602804E+09 | -535592006.0 | 0.00 | 0.00 | 720.00 | 0.00 | -67211829.8 | 58.99 | 0.00 | 0.00 |
July | 0.563233E+09 | -494113816.9 | 0.00 | 0.00 | 744.00 | 0.00 | -69118816.6 | 58.99 | 0.00 | 0.00 |
August | 0.608379E+09 | -538548607.3 | 0.00 | 0.00 | 744.00 | 0.00 | -69830088.6 | 58.99 | 0.00 | 0.00 |
September | 0.604740E+09 | -537063888.7 | 0.00 | 0.00 | 720.00 | 0.00 | -67676453.6 | 58.99 | 0.00 | 0.00 |
October | 0.665363E+09 | -592654188.3 | 0.00 | 0.00 | 744.00 | 0.00 | -72709156.0 | 58.99 | 0.00 | 0.00 |
November | 0.699221E+09 | -624736211.8 | 0.00 | 0.00 | 720.00 | 0.00 | -74484502.0 | 58.99 | 0.00 | 0.00 |
December | 0.778632E+09 | -697060907.7 | 0.00 | 0.00 | 744.00 | 0.00 | -81571169.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.821047E+10 | -0.733516E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -875311868.9 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.563233E+09 | -728583758.5 | 0.00 | 0.00 | 672.00 | 0.00 | -81571169.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.807107E+09 | -494113816.9 | 0.00 | 0.00 | 744.00 | 0.00 | -67211829.8 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.85 | 0.50 | 06-JAN-12:30 | 105.59 | 0.00 | 0.00 | 0.00 | 90.92 | 0.00 | 0.00 | 0.00 |
February | 241.00 | 0.78 | 0.50 | 05-FEB-12:20 | 152.12 | 0.00 | 0.00 | 20.50 | 1118.10 | 0.00 | 0.00 | 26.50 |
March | 344.33 | 0.75 | 0.50 | 02-MAR-11:50 | 181.81 | 0.00 | 0.00 | 56.67 | 147.81 | 0.00 | 0.00 | 20.50 |
April | 380.33 | 0.73 | 0.50 | 04-APR-11:30 | 183.35 | 0.00 | 0.00 | 38.17 | 1267.12 | 0.00 | 0.00 | 56.00 |
May | 403.17 | 0.72 | 0.50 | 01-MAY-10:00 | 804.41 | 0.00 | 0.00 | 62.17 | 1296.77 | 0.00 | 0.00 | 52.33 |
June | 418.17 | 0.76 | 0.50 | 04-JUN-11:39 | 1907.95 | 0.00 | 0.00 | 73.83 | 128.78 | 0.00 | 0.00 | 6.50 |
July | 399.50 | 0.72 | 0.50 | 01-JUL-11:39 | 1368.30 | 0.00 | 0.00 | 116.50 | 154.81 | 0.00 | 0.00 | 32.00 |
August | 361.83 | 0.73 | 0.50 | 01-AUG-10:20 | 485.10 | 0.00 | 0.00 | 61.67 | 1157.85 | 0.00 | 0.00 | 59.83 |
September | 350.17 | 0.72 | 0.50 | 01-SEP-10:00 | 202.67 | 0.00 | 0.00 | 62.33 | 163.63 | 0.00 | 0.00 | 23.33 |
October | 348.00 | 0.79 | 0.50 | 01-OCT-10:30 | 139.49 | 0.00 | 0.00 | 21.17 | 1060.75 | 0.00 | 0.00 | 41.67 |
November | 288.50 | 0.83 | 0.50 | 02-NOV-11:09 | 120.85 | 0.00 | 0.00 | 6.33 | 101.50 | 0.00 | 0.00 | 0.00 |
December | 290.67 | 0.82 | 0.50 | 31-DEC-12:30 | 1015.85 | 0.00 | 0.00 | 44.33 | 92.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4135.50 | 0.76 | 603.48 | 0.00 | 0.00 | 563.67 | 573.21 | 0.00 | 0.00 | 318.67 | ||
Minimum of Months | 241.00 | 0.72 | 0.50 | 105.59 | 0.00 | 0.00 | 0.00 | 90.92 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 418.17 | 0.85 | 0.50 | 1907.95 | 0.00 | 0.00 | 116.50 | 1296.77 | 0.00 | 0.00 | 59.83 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.73 | 0.50 | 01-JAN-10:00 | 128.36 | 9.53 | 0.00 | 32.17 | 105.88 | 13.22 | 0.00 | 19.33 |
February | 241.00 | 0.67 | 0.50 | 03-FEB-11:09 | 1041.54 | 11.09 | 0.00 | 93.00 | 148.59 | 14.73 | 12.33 | 57.50 |
March | 344.33 | 0.63 | 0.50 | 01-MAR-08:20 | 213.20 | 12.00 | 0.00 | 174.17 | 178.48 | 15.76 | 45.17 | 131.17 |
April | 380.33 | 0.62 | 0.50 | 01-APR-09:09 | 1636.62 | 11.94 | 0.00 | 211.67 | 1762.51 | 16.00 | 44.17 | 144.33 |
May | 403.17 | 0.61 | 0.50 | 01-MAY-08:09 | 222.69 | 12.13 | 0.00 | 231.17 | 1796.61 | 16.26 | 43.17 | 164.17 |
June | 418.17 | 0.63 | 0.50 | 01-JUN-07:00 | 195.85 | 11.32 | 0.00 | 204.00 | 165.49 | 15.34 | 21.83 | 132.50 |
July | 399.50 | 0.61 | 0.50 | 01-JUL-08:50 | 230.62 | 12.27 | 0.00 | 223.50 | 197.40 | 16.13 | 37.50 | 162.00 |
August | 361.83 | 0.62 | 0.50 | 01-AUG-08:39 | 1462.05 | 12.24 | 0.00 | 194.83 | 194.04 | 16.26 | 45.17 | 141.67 |
September | 350.17 | 0.61 | 0.50 | 01-SEP-08:09 | 238.56 | 12.60 | 0.00 | 209.17 | 199.28 | 16.33 | 58.83 | 160.17 |
October | 348.00 | 0.68 | 0.50 | 01-OCT-07:00 | 775.71 | 13.30 | 36.67 | 134.67 | 139.71 | 14.29 | 19.00 | 74.83 |
November | 288.50 | 0.70 | 0.50 | 01-NOV-08:39 | 569.49 | 10.05 | 0.00 | 77.17 | 120.15 | 13.79 | 5.00 | 33.67 |
December | 290.67 | 0.72 | 0.50 | 02-DEC-10:20 | 284.11 | 9.82 | 0.00 | 46.67 | 108.96 | 13.48 | 0.00 | 20.67 |
Annual Sum or Average | 4135.50 | 0.65 | 575.47 | 11.62 | 36.67 | 1832.17 | 466.15 | 15.25 | 332.17 | 1242.00 | ||
Minimum of Months | 241.00 | 0.61 | 0.50 | 128.36 | 9.53 | 0.00 | 32.17 | 105.88 | 13.22 | 0.00 | 19.33 | |
Maximum of Months | 418.17 | 0.73 | 0.50 | 1636.62 | 13.30 | 36.67 | 231.17 | 1796.61 | 16.33 | 58.83 | 164.17 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.84 | 0.61 | 26-JAN-16:30 | 279.66 | 21.65 | 106.67 | 42.17 | 97.97 | 18.89 | 74.17 | 0.00 |
February | 241.00 | 0.82 | 0.61 | 02-FEB-16:19 | 340.40 | 21.79 | 94.00 | 33.50 | 112.77 | 19.53 | 81.67 | 3.00 |
March | 344.33 | 0.81 | 0.61 | 02-MAR-16:10 | 304.14 | 21.94 | 137.33 | 42.83 | 267.20 | 23.36 | 157.00 | 38.50 |
April | 380.33 | 0.79 | 0.61 | 01-APR-15:20 | 223.29 | 20.18 | 135.33 | 63.67 | 280.29 | 22.14 | 160.67 | 65.67 |
May | 403.17 | 0.79 | 0.61 | 01-MAY-15:00 | 219.46 | 19.97 | 116.67 | 45.33 | 311.26 | 21.35 | 157.17 | 63.50 |
June | 418.17 | 0.80 | 0.61 | 01-JUN-15:00 | 206.77 | 19.44 | 99.00 | 22.17 | 381.18 | 21.01 | 160.00 | 56.33 |
July | 399.50 | 0.80 | 0.61 | 01-JUL-16:00 | 206.86 | 19.56 | 100.33 | 26.00 | 287.68 | 20.95 | 157.33 | 49.00 |
August | 361.83 | 0.81 | 0.61 | 01-AUG-15:39 | 197.25 | 19.62 | 92.33 | 24.50 | 231.53 | 20.84 | 126.17 | 41.50 |
September | 350.17 | 0.80 | 0.61 | 01-SEP-15:50 | 250.68 | 21.07 | 133.00 | 39.67 | 200.75 | 21.85 | 149.33 | 31.50 |
October | 348.00 | 0.82 | 0.61 | 01-OCT-16:10 | 323.08 | 22.23 | 126.00 | 42.50 | 203.41 | 22.08 | 118.33 | 28.33 |
November | 288.50 | 0.83 | 0.61 | 02-NOV-15:30 | 550.40 | 23.29 | 101.17 | 53.83 | 106.78 | 19.47 | 78.83 | 0.00 |
December | 290.67 | 0.84 | 0.63 | 13-DEC-16:19 | 424.26 | 22.51 | 95.83 | 46.50 | 91.91 | 18.99 | 66.50 | 0.00 |
Annual Sum or Average | 4135.50 | 0.81 | 282.82 | 20.95 | 1337.67 | 482.67 | 226.90 | 20.99 | 1487.17 | 377.33 | ||
Minimum of Months | 241.00 | 0.79 | 0.61 | 197.25 | 19.44 | 92.33 | 22.17 | 91.91 | 18.89 | 66.50 | 0.00 | |
Maximum of Months | 418.17 | 0.84 | 0.63 | 550.40 | 23.29 | 137.33 | 63.67 | 381.18 | 23.36 | 160.67 | 65.67 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.566009E+09 | 29126.58 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.670366E+09 | 29126.58 | 03-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.466000E+09 | 29126.58 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22147479.56 | 3423.01 | 25-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136692E+09 | 25692.40 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102574E+10 | 29126.58 | 05-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.288695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.102574E+10 | 29126.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.441659E+09 | 47046.87 | 01-JAN-07:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.250108E+09 | 23851.98 | 08-DEC-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.691767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.441659E+09 | 47046.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.806452E+09 | 0.806452E+09 | 5484.44 | 31-JAN-16:40 | 5484.44 | 0.00 |
February | 0.00 | 0.00 | 6317947.97 | 6016540.56 | 749.82 | 22-FEB-16:00 | 749.82 | 0.00 |
March | 0.00 | 0.00 | 0.983932E+09 | 0.979560E+09 | 5979.24 | 18-MAR-16:00 | 5979.24 | 0.00 |
April | 0.00 | 0.00 | 0.568697E+10 | 0.568617E+10 | 21738.34 | 25-APR-05:01 | 21738.34 | 0.00 |
May | 0.00 | 0.00 | 0.819045E+10 | 0.819045E+10 | 21817.60 | 11-MAY-05:01 | 21817.60 | 0.00 |
June | 0.00 | 0.00 | 0.114228E+11 | 0.114020E+11 | 23216.57 | 30-JUN-05:01 | 23216.57 | 0.00 |
July | 0.00 | 0.00 | 0.118558E+11 | 0.107186E+11 | 28298.00 | 14-JUL-05:01 | 14095.31 | 0.00 |
August | 0.00 | 0.00 | 0.124737E+11 | 0.111767E+11 | 26899.99 | 01-AUG-05:01 | 16559.09 | 0.00 |
September | 0.00 | 0.00 | 0.105096E+11 | 0.932568E+10 | 27100.95 | 02-SEP-05:01 | 17007.43 | 0.00 |
October | 0.00 | 0.00 | 0.499065E+10 | 0.475046E+10 | 25802.70 | 03-OCT-05:01 | 16187.42 | 0.00 |
November | 0.00 | 0.00 | 0.127494E+10 | 0.123423E+10 | 7849.43 | 01-NOV-16:00 | 7468.57 | 0.00 |
December | 0.00 | 0.00 | 0.215208E+09 | 0.215208E+09 | 3631.32 | 22-DEC-16:30 | 3631.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.684167E+11 | 0.644915E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6317947.97 | 6016540.56 | 749.82 | 749.82 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.124737E+11 | 0.114020E+11 | 28298.00 | 23216.57 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 94094848.38 | 94094848.38 | 5321.33 | 18-MAR-15:30 | 5321.33 | 0.00 |
April | 0.00 | 0.00 | 0.109973E+11 | 0.109951E+11 | 73119.54 | 16-APR-18:11 | 73119.54 | 0.00 |
May | 0.00 | 0.00 | 0.203554E+11 | 0.203554E+11 | 72468.63 | 29-MAY-20:45 | 72468.63 | 0.00 |
June | 0.00 | 0.00 | 0.374883E+11 | 0.373955E+11 | 75633.85 | 18-JUN-05:45 | 72271.14 | 0.00 |
July | 0.00 | 0.00 | 0.392900E+11 | 0.351966E+11 | 93959.23 | 13-JUL-20:52 | 43320.71 | 0.00 |
August | 0.00 | 0.00 | 0.362827E+11 | 0.323630E+11 | 90667.79 | 09-AUG-19:52 | 49289.66 | 0.00 |
September | 0.00 | 0.00 | 0.273729E+11 | 0.240682E+11 | 92446.94 | 04-SEP-08:52 | 45438.28 | 0.00 |
October | 0.00 | 0.00 | 0.872928E+10 | 0.819071E+10 | 85582.56 | 02-OCT-22:41 | 56644.67 | 0.00 |
November | 0.00 | 0.00 | 0.219383E+09 | 0.203751E+09 | 9710.35 | 01-NOV-15:10 | 8840.14 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.180829E+12 | 0.168863E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.392900E+11 | 0.373955E+11 | 93959.23 | 73119.54 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.583939E+09 | 0.24 | 1423.61 | 02-JAN-06:01 | 1.00 |
February | 0.542959E+09 | 0.25 | 1423.61 | 03-FEB-06:01 | 1.00 |
March | 0.625246E+09 | 0.26 | 1423.61 | 02-MAR-06:02 | 0.99 |
April | 0.575186E+09 | 0.24 | 1423.61 | 12-APR-05:02 | 1.00 |
May | 0.629943E+09 | 0.25 | 1423.61 | 02-MAY-05:02 | 1.00 |
June | 0.756629E+09 | 0.30 | 1423.61 | 01-JUN-05:01 | 1.00 |
July | 0.699763E+09 | 0.28 | 1423.61 | 01-JUL-05:01 | 1.00 |
August | 0.741200E+09 | 0.29 | 1423.61 | 01-AUG-05:01 | 0.98 |
September | 0.638950E+09 | 0.26 | 1423.61 | 01-SEP-05:01 | 0.98 |
October | 0.583018E+09 | 0.23 | 1423.61 | 02-OCT-05:01 | 0.99 |
November | 0.545893E+09 | 0.23 | 1255.76 | 24-NOV-06:02 | 1.00 |
December | 0.599990E+09 | 0.25 | 1423.61 | 05-DEC-06:01 | 1.00 |
Annual Sum or Average | 0.752272E+10 | 0.26 | |||
Minimum of Months | 0.542959E+09 | 0.23 | 1255.76 | 0.98 | |
Maximum of Months | 0.756629E+09 | 0.30 | 1423.61 | 1.00 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.147188E+10 | 0.23 | 1742.29 | 01-JAN-07:23 | 0.97 |
February | 0.133938E+10 | 0.22 | 1470.56 | 01-FEB-07:10 | 0.59 |
March | 0.157232E+10 | 0.23 | 1470.56 | 18-MAR-14:40 | 0.59 |
April | 0.155123E+10 | 0.26 | 3676.39 | 14-APR-17:06 | 0.97 |
May | 0.174734E+10 | 0.31 | 3676.39 | 06-MAY-17:06 | 0.97 |
June | 0.212119E+10 | 0.40 | 3676.39 | 01-JUN-17:05 | 0.96 |
July | 0.205468E+10 | 0.39 | 3676.39 | 01-JUL-17:05 | 0.97 |
August | 0.202033E+10 | 0.37 | 3676.39 | 01-AUG-17:05 | 0.96 |
September | 0.174781E+10 | 0.33 | 3676.39 | 04-SEP-14:43 | 0.96 |
October | 0.153522E+10 | 0.25 | 3364.44 | 05-OCT-17:06 | 0.93 |
November | 0.139762E+10 | 0.21 | 1470.56 | 02-NOV-14:30 | 0.58 |
December | 0.146453E+10 | 0.23 | 1665.56 | 18-DEC-07:10 | 0.64 |
Annual Sum or Average | 0.200235E+11 | 0.29 | |||
Minimum of Months | 0.133938E+10 | 0.21 | 1470.56 | 0.58 | |
Maximum of Months | 0.212119E+10 | 0.40 | 3676.39 | 0.97 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.785479E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.544571E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.872690E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.202670E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.276839E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.397210E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.384270E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.403574E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.331917E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.183468E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.860435E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.653618E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.255163E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.544571E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.403574E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.147188E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.133938E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.160078E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.488004E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.804870E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.142407E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.140004E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.130802E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.986448E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.414534E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.146289E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.146453E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.755994E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.133938E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.142407E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.583939E+09 | 0.806452E+09 | 0.566009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.542959E+09 | 6317947.97 | 0.670366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.625246E+09 | 0.983932E+09 | 0.466000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.575186E+09 | 0.567139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.629943E+09 | 0.814070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.756629E+09 | 0.113491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.699763E+09 | 0.118194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.741200E+09 | 0.124106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.638950E+09 | 0.104245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.583018E+09 | 0.496552E+10 | 22147479.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.545893E+09 | 0.127494E+10 | 0.136692E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.599990E+09 | 0.215208E+09 | 0.102574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.752272E+10 | 0.680681E+11 | 0.288695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.542959E+09 | 6317947.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.756629E+09 | 0.124106E+11 | 0.102574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.147188E+10 | 0.00 | 0.441659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157232E+10 | 94094848.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155123E+10 | 0.108206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.174734E+10 | 0.201990E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.212119E+10 | 0.370165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.205468E+10 | 0.382601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.202033E+10 | 0.353263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174781E+10 | 0.265369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153522E+10 | 0.852972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139762E+10 | 0.219383E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146453E+10 | 0.00 | 0.250108E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200235E+11 | 0.177003E+12 | 0.691767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.212119E+10 | 0.382601E+11 | 0.441659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.583939E+09 | 0.00 | 0.00 | 0.00 | 0.201540E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.542959E+09 | 0.00 | 0.00 | 0.00 | 1611295.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.625246E+09 | 0.00 | 0.00 | 0.00 | 0.247443E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.575186E+09 | 0.00 | 0.00 | 0.00 | 0.145151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.629943E+09 | 0.00 | 0.00 | 0.00 | 0.213845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.756629E+09 | 0.00 | 0.00 | 0.00 | 0.321547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.699763E+09 | 0.00 | 0.00 | 0.00 | 0.314293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.741200E+09 | 0.00 | 0.00 | 0.00 | 0.329454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.638950E+09 | 0.00 | 0.00 | 0.00 | 0.268022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.583018E+09 | 0.00 | 0.00 | 0.00 | 0.125166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.545893E+09 | 0.00 | 0.00 | 0.00 | 0.314542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.599990E+09 | 0.00 | 0.00 | 0.00 | 53627739.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.752272E+10 | 0.00 | 0.00 | 0.00 | 0.179935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.542959E+09 | 0.00 | 0.00 | 0.00 | 1611295.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.756629E+09 | 0.00 | 0.00 | 0.00 | 0.329454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.147188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157232E+10 | 0.00 | 0.00 | 0.00 | 28459077.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155123E+10 | 0.00 | 0.00 | 0.00 | 0.332881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.174734E+10 | 0.00 | 0.00 | 0.00 | 0.630136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.212119E+10 | 0.00 | 0.00 | 0.00 | 0.121196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.205468E+10 | 0.00 | 0.00 | 0.00 | 0.119457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.202033E+10 | 0.00 | 0.00 | 0.00 | 0.110598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174781E+10 | 0.00 | 0.00 | 0.00 | 0.811667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153522E+10 | 0.00 | 0.00 | 0.00 | 0.261012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139762E+10 | 0.00 | 0.00 | 0.00 | 65277275.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200235E+11 | 0.00 | 0.00 | 0.00 | 0.555758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.212119E+10 | 0.00 | 0.00 | 0.00 | 0.121196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.322834E+09 | 1706299.15 | 0.00 | 1434503.69 | 0.00 | 36962090.99 | 0.778184E+09 | 0.00 | 0.31 |
February | 0.659417E+09 | 0.00 | 0.00 | 297418.85 | 0.00 | 71142238.72 | 0.415198E+09 | 0.00 | 0.18 |
March | 0.388383E+09 | 10339740.96 | 0.00 | 1548695.84 | 0.00 | 17101078.78 | 0.901437E+09 | 0.00 | 0.32 |
April | 7355402.49 | 0.173528E+09 | 0.00 | 4368976.73 | 0.00 | 0.00 | 0.692898E+09 | 0.00 | 0.30 |
May | 577383.02 | 0.355668E+09 | 0.00 | 5046237.91 | 0.00 | 0.00 | 0.342507E+09 | 0.00 | 0.25 |
June | 42613.82 | 0.870075E+09 | 0.00 | 4699847.95 | 0.00 | 0.00 | 67872056.58 | 0.00 | 0.17 |
July | 0.00 | 0.115724E+10 | 0.00 | 3423666.64 | 0.00 | 0.00 | 30190936.37 | 0.00 | 0.15 |
August | 0.00 | 0.126615E+10 | 0.00 | 4557808.18 | 0.00 | 0.00 | 40673784.12 | 0.00 | 0.19 |
September | 31254.85 | 0.913255E+09 | 0.00 | 4583317.65 | 0.00 | 0.00 | 0.116546E+09 | 0.00 | 0.24 |
October | 59052762.12 | 0.229123E+09 | 0.00 | 4497598.88 | 0.00 | 0.00 | 0.112155E+10 | 0.00 | 0.38 |
November | 0.186231E+09 | 9334888.65 | 0.00 | 2659116.80 | 0.00 | 1986257.56 | 0.148156E+10 | 0.00 | 0.39 |
December | 0.555147E+09 | 0.00 | 0.00 | 574385.93 | 208595.12 | 0.167257E+09 | 0.431109E+09 | 0.00 | 0.22 |
Annual Sum or Average | 0.217907E+10 | 0.498642E+10 | 0.00 | 37691575.03 | 208595.12 | 0.294449E+09 | 0.641973E+10 | 0.00 | 0.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 297418.85 | 0.00 | 0.00 | 30190936.37 | 0.00 | 0.15 |
Maximum of Months | 0.659417E+09 | 0.126615E+10 | 0.00 | 5046237.91 | 208595.12 | 0.167257E+09 | 0.148156E+10 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.206491E+10 | 0.00 | 0.00 | 0.00 | 497176.73 | 4995562.69 | 0.00 | 0.00 | 0.18 |
February | 0.283290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
March | 0.253960E+10 | 214499.96 | 0.00 | 76492.78 | 4500583.74 | 0.00 | 0.119635E+09 | 0.00 | 0.20 |
April | 0.476841E+09 | 0.234506E+09 | 0.00 | 7937026.18 | 7321975.81 | 0.00 | 0.153603E+10 | 0.00 | 0.31 |
May | 71761741.55 | 0.705495E+09 | 0.00 | 7630506.88 | 0.00 | 0.00 | 0.109324E+10 | 0.00 | 0.29 |
June | 1517841.04 | 0.245483E+10 | 0.00 | 3660453.74 | 424344.40 | 0.00 | 0.330684E+09 | 0.00 | 0.27 |
July | 709479.10 | 0.353325E+10 | 0.00 | 1727852.43 | 2285602.64 | 0.00 | 0.183415E+09 | 0.00 | 0.27 |
August | 1646687.30 | 0.363756E+10 | 0.00 | 2243884.13 | 4427358.36 | 0.00 | 0.352697E+09 | 0.00 | 0.31 |
September | 29949765.64 | 0.221367E+10 | 0.00 | 4062810.10 | 99129.18 | 0.00 | 0.655844E+09 | 0.00 | 0.32 |
October | 0.137312E+10 | 0.394579E+09 | 0.00 | 4411477.04 | 0.00 | 0.00 | 0.114442E+10 | 0.00 | 0.28 |
November | 0.277573E+10 | 0.00 | 0.00 | 230126.86 | 509187.57 | 0.00 | 0.143779E+09 | 0.00 | 0.19 |
December | 0.248489E+10 | 0.00 | 0.00 | 0.00 | 13190726.67 | 5897190.95 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.146536E+11 | 0.131741E+11 | 0.00 | 31980630.13 | 33256085.10 | 10892753.63 | 0.555974E+10 | 0.00 | 0.25 |
Minimum of Months | 709479.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.283290E+10 | 0.363756E+10 | 0.00 | 7937026.18 | 13190726.67 | 5897190.95 | 0.153603E+10 | 0.00 | 0.32 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:07
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.607151E+12 | 0.190226E+11 | 0.00 | 0.320712E+10 | 0.149218E+10 |
February | 0.608073E+12 | 0.210129E+11 | 0.00 | 0.397895E+10 | 0.324681E+09 |
March | 0.851685E+12 | 0.290382E+11 | 0.00 | 0.395273E+10 | 0.157527E+10 |
April | 0.113321E+13 | 0.290861E+11 | 0.00 | 0.234061E+10 | 0.214645E+11 |
May | 0.119140E+13 | 0.426781E+11 | 0.00 | 0.466328E+09 | 0.369857E+11 |
June | 0.121949E+13 | 0.587066E+11 | 0.00 | -0.290211E+10 | 0.642461E+11 |
July | 0.108366E+13 | 0.678804E+11 | 0.00 | -0.448482E+10 | 0.662344E+11 |
August | 0.982204E+12 | 0.585308E+11 | 0.00 | -0.452968E+10 | 0.631108E+11 |
September | 0.816271E+12 | 0.423903E+11 | 0.00 | -0.233854E+10 | 0.486793E+11 |
October | 0.757337E+12 | 0.348559E+11 | 0.00 | 0.307902E+10 | 0.175936E+11 |
November | 0.609532E+12 | 0.267909E+11 | 0.00 | 0.458234E+10 | 0.194299E+10 |
December | 0.496953E+12 | 0.205715E+11 | 0.00 | 0.363147E+10 | 0.876866E+09 |
Annual Sum or Average | 0.103570E+14 | 0.450564E+12 | 0.00 | 0.109834E+11 | 0.324526E+12 |
Minimum of Months | 0.496953E+12 | 0.190226E+11 | 0.00 | -0.452968E+10 | 0.324681E+09 |
Maximum of Months | 0.121949E+13 | 0.678804E+11 | 0.00 | 0.458234E+10 | 0.662344E+11 |