Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2023-10-16 10:41:47
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 624.19 | 129.10 | 129.10 |
Net Site Energy | 624.19 | 129.10 | 129.10 |
Total Source Energy | 1973.96 | 408.25 | 408.25 |
Net Source Energy | 1973.96 | 408.25 | 408.25 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 19.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 317.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 92.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 137.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 31.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 622.82 | 1.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 19.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 317.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 92.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 137.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 30.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 24.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 19.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 317.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 92.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 137.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 31.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 24.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 84.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 15.61 | 0.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 128.81 | 0.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 84.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 15.61 | 0.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 128.81 | 0.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 622.821 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 622.821 | 100.00 |
Total On-Site and Utility Electric Sources | 622.821 | 100.00 |
Total Electricity End Uses | 622.821 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 4.83 |
Time Setpoint Not Met During Occupied Cooling | 5.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1934.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 135.81 |
Skylight-Roof Ratio [%] | 2.95 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 9.9957 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 10.2257 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 6.2431 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.5746 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.5746 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 9.9957 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 10.2257 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 6.2431 | 46.45 | 2.5587 | |
Total | 4835.13 | 7.5746 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 7.5746 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 7.5746 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-OCT-14:39 | 03-JAN-06:10 | - | - | - | - | - | - | - | - | - | - | 26-JUN-11:09 |
Heating | 0.00 | 22215.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 7768.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 27862.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4755.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1741.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 52181.60 | 22215.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 22215.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 7768.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 27862.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2449.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1741.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 61.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1005.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 293.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 434.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 99.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 78.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1972.47 | 1.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 12.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 207.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 407.95 | 0.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 12.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 207.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 407.95 | 0.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.10 |
ZONE2 FINE STORAGE DIRECT AIR | 2.87 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 1.21 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 1.21 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 48506.73 |
PSZ-OFFICE HEATING COIL | 26985.13 |
PSZ-FINE STORAGE HEATING COIL | 89177.75 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 48506.73 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.10 | 1.10 | 1.10 | 1.10 | 1.10 | 1.10 | 1.00 | 1.00 | 1.10 |
PSZ-FINE STORAGE | 2.87 | 2.87 | 2.87 | 2.87 | 2.87 | 2.87 | 1.00 | 1.000000 | 2.87 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.10 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.87 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.10 | 1222.32 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.87 | 3069.01 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.10 | 1.10 | 1.10 | 1.10 | 18777.70 | 26985.13 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.87 | 2.87 | 2.87 | 1.89 | 58722.99 | 89177.75 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.10 | 0.552007 | 0.736007 | 18777.70 | 9388.85 | 0.800820 | 0.800820 |
PSZ-FINE STORAGE COOLING COIL | 2.87 | 1.43 | 1.91 | 58722.99 | 29361.49 | 0.767250 | 0.767250 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 9.996 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.069 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 10.226 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.226 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 6.243 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 8.802 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2367.778 | 9.996 | 185.726 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2367.778 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 14248.589 | 10.226 | 474.953 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 14248.589 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 20008.023 | 6.243 | 289.971 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20008.023 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3263 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5959 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.5871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.7823 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.7823 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.065 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.678 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.604 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.179 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.179 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.38866262E-07 | 0.77198350E-12 | 0.86409618E-13 | 0.0000000 |
2 | 1 | -5.2160226 | 0.42725752E-04 | -0.49098391E-04 | 0.74579932E-08 |
3 | 0 | 5.5423254 | 0.32626013 | 0.32635195 | |
4 | 2 | 0.53319041E-11 | 0.92099297E-16 | 0.18475806E-15 | 0.0000000 |
5 | 1 | -5.2159728 | 0.43155192E-04 | -0.26885250E-04 | 0.68722794E-11 |
6 | 0 | 5.8118483 | 0.59583229 | 0.59590233 | |
7 | 4 | 0.76068674E-12 | 0.17122987E-15 | -0.23910318E-14 | 0.12033535E-15 |
8 | 3 | -0.37775691E-03 | 0.40878477E-06 | -0.54729085E-04 | 0.14597214E-12 |
9 | 2 | 1.7230416 | 0.90045648E-02 | 1.1279077 | -0.72421780E-04 |
10 | 1 | -7.1505571 | 0.23437850 | -17.017997 | 0.33022598 |
11 | 0 | 5.8211705 | 0.14989371 | 16.283421 | |
12 | 4 | 0.72249793E-12 | -0.16720573E-15 | 0.22015083E-14 | 0.12409536E-15 |
13 | 3 | -0.36459118E-03 | 0.53555631E-06 | -0.52695411E-04 | 0.13865996E-12 |
14 | 2 | 1.6915239 | 0.11971291E-01 | 1.1039557 | -0.69896550E-04 |
15 | 1 | -7.1930661 | 0.31446443 | -16.864389 | 0.32415671 |
16 | 0 | 6.0306730 | 0.20232993 | 16.289252 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.22015083E-14 | -0.16720573E-15 | 0.72249793E-12 | 0.12409536E-15 |
85 | 3 | -0.52695411E-04 | 0.53555631E-06 | -0.36459118E-03 | 0.13865996E-12 |
86 | 2 | 1.1039557 | 0.11971291E-01 | 1.6915239 | -0.69896550E-04 |
87 | 1 | -16.864389 | 0.31446443 | -7.1930661 | 0.32415671 |
88 | 0 | 16.289252 | 0.20232993 | 6.0306730 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.6283_SHGC_SOUTH_0.25 | 34 | 1 | VerySmooth | 3.572 | 3.572 | 1.000 | 0.252 | ||
2 | NONRESWINDOW_U_0.6283_SHGC_NORTH_0.25 | 35 | 1 | VerySmooth | 3.572 | 3.572 | 1.000 | 0.252 | ||
3 | NONRESWINDOW_U_0.6283_SHGC_EAST_0.25 | 36 | 1 | VerySmooth | 3.572 | 3.572 | 1.000 | 0.252 | ||
4 | NONRESWINDOW_U_0.6283_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 3.572 | 3.572 | 1.000 | 0.252 | ||
5 | SKYLIGHT_U_1.02_SHGC_0.39 | 38 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.391 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.15349 | 0.58024 | 0.58024 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.80019E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.15349 | 0.58024 | 0.58024 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.80019E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.15349 | 0.58024 | 0.58024 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.80019E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.15349 | 0.58024 | 0.58024 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.80019E-002 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.22227 | 0.21773 | 0.21773 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE2 FINE STORAGE | 14 | 0 |
2 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE2 FINE STORAGE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_1.02_SHGC_0.39 | SKYLIGHT_FRAME_NONRES | CurtainWall | 5.547 | 0.364 | 0.355 |
2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.849 | 0.366 | 0.185 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.710 | 8.455E-004 | 5.523E-004 | 0.277 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.4549E-005 |
2 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1541E-004 |
3 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.4209E-005 |
4 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.8788E-004 |
5 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.2937E-005 |
6 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.7325E-004 |
7 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0636E-004 |
8 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.8167E-004 |
9 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6915E-004 |
10 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.3532E-004 |
11 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4322E-004 |
12 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.9332E-004 |
13 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6310E-004 |
14 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.4188E-004 |
15 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5287E-004 |
16 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6012E-004 |
17 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.7605E-004 |
18 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9672E-004 |
19 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1817E-004 |
20 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1953E-004 |
21 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.8184E-004 |
22 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4388E-004 |
23 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.1394E-004 |
24 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.4870E-005 |
25 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.7357E-004 |
26 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0716E-004 |
27 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.1568E-004 |
28 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1555E-004 |
29 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1446E-003 |
30 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.5304E-005 |
31 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3712E-003 |
32 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.5889E-005 |
33 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.7324E-004 |
34 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.5129E-005 |
35 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3176E-004 |
36 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8589E-005 |
37 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0148E-003 |
38 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6617E-005 |
39 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2155E-004 |
40 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0156E-005 |
41 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.1291E-004 |
42 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.2571E-005 |
43 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.7989E-004 |
44 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4225E-005 |
45 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.2241E-004 |
46 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9791E-005 |
47 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9613E-004 |
48 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8111E-005 |
49 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.2888E-004 |
50 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3094E-005 |
51 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0967E-003 |
52 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4802E-005 |
53 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.4186E-004 |
54 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0108E-005 |
55 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5560E-004 |
56 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8212E-005 |
57 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9735E-003 |
58 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.7019E-005 |
59 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.2324E-003 |
60 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.0762E-005 |
61 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9799E-003 |
62 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.7669E-005 |
63 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1425E-003 |
64 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0473E-005 |
65 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6530E-003 |
66 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1537E-004 |
67 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5612E-003 |
68 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2531E-004 |
69 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3351E-003 |
70 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9553E-005 |
71 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.6082E-003 |
72 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.7083E-005 |
73 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9743E-004 |
74 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4205E-004 |
75 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.9707E-004 |
76 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.7493E-004 |
77 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.1998E-004 |
78 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6606E-004 |
79 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6643E-003 |
80 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.0659E-005 |
81 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1261E-004 |
82 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2706E-004 |
83 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7587E-004 |
84 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.5586E-004 |
85 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9544E-004 |
86 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.8892E-004 |
87 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5215E-004 |
88 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9830E-004 |
89 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0402E-004 |
90 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8003E-003 |
91 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.1063E-005 |
92 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0761E-003 |
93 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.7576E-005 |
94 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6307E-003 |
95 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1944E-004 |
96 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1045E-004 |
97 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.1196E-005 |
98 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8835E-003 |
99 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.6222E-005 |
100 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8631E-003 |
101 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.4087E-005 |
102 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5626E-003 |
103 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4014E-005 |
104 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.2205E-003 |
105 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.8731E-005 |
106 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.4603E-004 |
107 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.4475E-005 |
108 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.0843E-004 |
109 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.3236E-005 |
110 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2272E-003 |
111 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.1656E-005 |
112 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2729E-003 |
113 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2543E-005 |
114 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9197E-005 |
115 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8412E-005 |
116 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0620E-005 |
117 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7740E-005 |
118 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6731E-005 |
119 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4598E-005 |
120 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5286E-005 |
121 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6327E-005 |
122 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9529E-005 |
123 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8565E-005 |
124 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3456E-005 |
125 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5517E-005 |
126 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0901E-005 |
127 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1685E-005 |
128 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2542E-005 |
129 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2887E-005 |
130 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9763E-005 |
131 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8538E-005 |
132 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8714E-005 |
133 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7036E-005 |
134 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9189E-005 |
135 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4582E-005 |
136 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1042E-005 |
137 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2116E-004 |
138 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1017E-004 |
139 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5601E-004 |
140 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1811E-004 |
141 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4147E-004 |
142 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.3849E-005 |
143 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2514E-005 |
144 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3080E-005 |
145 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4464E-005 |
146 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5521E-004 |
147 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9476E-005 |
148 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9822E-004 |
149 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2591E-005 |
150 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5669E-004 |
151 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4916E-005 |
152 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6240E-005 |
153 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2916E-005 |
154 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2864E-005 |
155 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5043E-005 |
156 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2427E-005 |
157 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8022E-005 |
158 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3530E-005 |
159 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4899E-005 |
160 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1079E-005 |
161 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8482E-004 |
162 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9625E-005 |
163 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0909E-004 |
164 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9559E-005 |
165 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3241E-004 |
166 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8865E-005 |
167 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2500E-005 |
168 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7738E-005 |
169 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2542E-004 |
170 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.4522E-004 |
171 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3028E-004 |
172 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0193E-003 |
173 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2279E-004 |
174 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0076E-004 |
175 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0532E-005 |
176 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7293E-004 |
177 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6830E-004 |
178 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9543E-004 |
179 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6794E-004 |
180 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0674E-004 |
181 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.9234E-004 |
182 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9364E-004 |
183 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5069E-004 |
184 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0290E-004 |
185 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3856E-004 |
186 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1628E-005 |
187 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0037E-004 |
188 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0095E-005 |
189 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5306E-004 |
190 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5367E-005 |
191 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5061E-004 |
192 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8433E-005 |
193 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0668E-004 |
194 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5040E-005 |
195 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0727E-004 |
196 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4150E-005 |
197 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1264E-004 |
198 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6309E-005 |
199 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0473E-005 |
200 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3210E-005 |
201 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8363E-004 |
202 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2891E-005 |
203 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.7337E-004 |
204 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.8612E-005 |
205 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.4530E-004 |
206 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.4455E-005 |
207 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2387E-004 |
208 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6113E-005 |
209 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0959E-003 |
210 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1144E-004 |
211 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2445E-003 |
212 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1326E-004 |
213 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0492E-003 |
214 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9041E-004 |
215 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2445E-004 |
216 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5215E-004 |
217 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4442E-004 |
218 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6707E-005 |
219 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3843E-004 |
220 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5289E-005 |
221 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7996E-004 |
222 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8571E-005 |
223 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2708E-004 |
224 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5686E-005 |
225 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6677E-004 |
226 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8059E-003 |
227 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6486E-004 |
228 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1221E-003 |
229 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9832E-004 |
230 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5028E-003 |
231 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2726E-004 |
232 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9459E-004 |
233 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5779E-004 |
234 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7197E-005 |
235 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4223E-004 |
236 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5366E-005 |
237 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1600E-004 |
238 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9019E-005 |
239 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9961E-004 |
240 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7482E-005 |
241 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0272E-003 |
242 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.6625E-005 |
243 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0018E-003 |
244 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9588E-005 |
245 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4476E-003 |
246 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2008E-005 |
247 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6165E-003 |
248 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3274E-005 |
249 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1487E-003 |
250 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5424E-004 |
251 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1472E-003 |
252 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2553E-004 |
253 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5707E-003 |
254 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2460E-004 |
255 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6195E-003 |
256 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2024E-004 |
257 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7400E-004 |
258 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8326E-003 |
259 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6025E-004 |
260 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8781E-003 |
261 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3768E-004 |
262 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3865E-003 |
263 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0001E-004 |
264 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6530E-003 |
265 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3150E-004 |
266 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6248E-005 |
267 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1339E-004 |
268 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4286E-005 |
269 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6578E-004 |
270 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7190E-005 |
271 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9852E-004 |
272 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7461E-005 |
273 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3728E-004 |
274 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3941E-004 |
275 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1982E-004 |
276 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2118E-004 |
277 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8012E-004 |
278 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1128E-003 |
279 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9891E-004 |
280 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6031E-003 |
281 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8144E-004 |
282 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9669E-005 |
283 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9598E-004 |
284 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1896E-005 |
285 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.9373E-004 |
286 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8467E-005 |
287 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5919E-003 |
288 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3045E-005 |
289 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0231E-004 |
290 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5941E-004 |
291 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1868E-004 |
292 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2095E-004 |
293 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4146E-004 |
294 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5550E-004 |
295 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5949E-003 |
296 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1554E-004 |
297 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1470E-005 |
298 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8911E-004 |
299 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8523E-005 |
300 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3402E-004 |
301 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.9602E-005 |
302 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0752E-004 |
303 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2574E-004 |
304 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7337E-004 |
305 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3949E-004 |
306 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4584E-004 |
307 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9563E-004 |
308 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2073E-004 |
309 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6414E-004 |
310 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5420E-004 |
311 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1039E-004 |
312 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4748E-004 |
313 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6603E-005 |
314 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6529E-005 |
315 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8681E-005 |
316 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3803E-005 |
317 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5028E-005 |
318 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3271E-005 |
319 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1671E-005 |
320 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7584E-005 |
321 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0956E-005 |
322 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4238E-005 |
323 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7402E-005 |
324 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2444E-005 |
325 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3628E-005 |
326 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4122E-005 |
327 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2556E-004 |
328 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5637E-005 |
329 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9778E-005 |
330 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1513E-004 |
331 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2128E-005 |
332 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.3769E-005 |
333 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5385E-005 |
334 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.6563E-005 |
335 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9741E-005 |
336 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6869E-004 |
337 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0401E-004 |
338 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.9655E-005 |
339 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5584E-005 |
340 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6894E-005 |
341 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9796E-005 |
342 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.8488E-005 |
343 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4732E-004 |
344 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0119E-004 |
345 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0227E-005 |
346 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1880E-005 |
347 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2159E-005 |
348 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0437E-005 |
349 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.3333E-005 |
350 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1237E-005 |
351 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9684E-005 |
352 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3161E-005 |
353 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3928E-004 |
354 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6885E-005 |
355 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9440E-004 |
356 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0432E-005 |
357 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5422E-004 |
358 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6796E-005 |
359 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0983E-004 |
360 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5702E-005 |
361 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0462E-004 |
362 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4879E-005 |
363 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5756E-005 |
364 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0446E-005 |
365 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7787E-005 |
366 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1279E-005 |
367 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4724E-004 |
368 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8139E-005 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10974.76670 | 13169.72004 | 0.92001 | 1.10401 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 30.64733 | 8.23245E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 7494.31933 | 8993.18320 | 0.21418 | 0.25701 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 3.80000 | 5.05843E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 36575.95953 | 43891.15143 | 2.39009 | 2.86811 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 31.30000 | 8.23349E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 17816.40784 | 21379.68941 | 0.42926 | 0.51511 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 3.80000 | 5.05843E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 31.30000 | 8.23349E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 40422.27663 | 48506.73196 | 1.00638 | 1.20765 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 16431.45 | 1.10401 | 1.10401 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 7885.99 | 0.25701 | 0.25701 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 52384.25 | 2.86811 | 2.86811 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 20881.46 | 0.51511 | 0.51511 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.10401 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.86811 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.20765 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 1.20765 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 48506.73038 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 48506.73196 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.10401 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.10401 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.10401 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.10401 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.10401 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.10401 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.86811 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.86811 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.86811 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.86811 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.86811 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.86811 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.10401 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.86811 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.10401 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.10401 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1222.31938 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.10401 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.10401 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.10401 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.10401 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.10401 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55201 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.73601 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18777.70000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9388.85000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80082 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80082 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18777.70000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26985.12659 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 26985.12659 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.86811 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.86811 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3069.00829 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.86811 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.86811 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.86811 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.89295 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.86811 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.43405 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.91207 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 58722.99000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 29361.49500 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76725 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76725 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 58722.99000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 89177.75411 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 89177.75411 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 17921.0 | 11.74 | 11.47 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 56495.6 | 11.70 | 11.44 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 2.6331542604E-002 | 2.0338561234E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 4.3563323018E-002 | 4.4465561888E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 3.3593863684E-002 | 3.2635233975E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 11666.11 | 391.48 | 0.00 | 88.04 | 106.11 | 12251.79 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.00 | 2 | |||
Feb | 59.00 | 53 | |||
Mar | 58.58 | 43 | |||
Apr | 46.42 | 14 | |||
May | 18.00 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 3.00 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 18.00 | 12 | |||
Dec | 4.00 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.540 | 0.587 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.540 | 0.587 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.540 | 0.587 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.540 | 0.587 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.540 | 0.587 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.540 | 0.587 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.540 | 0.587 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.312 | 0.326 | 1393.41 | 1368.35 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.551 | 0.596 | 3204.84 | 3094.09 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.659 | 0.782 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.659 | 0.782 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.6283_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.572 | 0.252 | 0.251 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.6283_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.572 | 0.252 | 0.251 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.6283_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.572 | 0.252 | 0.251 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.6283_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.572 | 0.252 | 0.251 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_1.02_SHGC_0.39 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.391 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.364 | 0.355 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_1.02_SHGC_0.39 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.391 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.364 | 0.355 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_1.02_SHGC_0.39 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.391 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.364 | 0.355 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_1.02_SHGC_0.39 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.391 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.364 | 0.355 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_1.02_SHGC_0.39 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.391 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.364 | 0.355 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_1.02_SHGC_0.39 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.391 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.364 | 0.355 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_1.02_SHGC_0.39 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.391 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.364 | 0.355 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_1.02_SHGC_0.39 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.391 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.364 | 0.355 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_1.02_SHGC_0.39 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.391 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.364 | 0.355 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_1.02_SHGC_0.39 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.391 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.364 | 0.355 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_1.02_SHGC_0.39 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.391 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.364 | 0.355 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_1.02_SHGC_0.39 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.391 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.364 | 0.355 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_1.02_SHGC_0.39 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.391 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.364 | 0.355 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_1.02_SHGC_0.39 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.391 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.364 | 0.355 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 153.47 | 5.542 | 0.490 | 0.384 | |||||||||||||||||
North Total or Average | 6.51 | 3.572 | 0.252 | 0.251 | |||||||||||||||||
Non-North Total or Average | 146.96 | 5.630 | 0.501 | 0.390 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 9.9957 | 236.88 | 2367.78 | LightsWired | LTG_SCH_OFFICE | 56.95 | 168.00 | 56.07 | 0.0000 | Y | 24.92 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 10.2257 | 1393.41 | 14248.59 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 49.69 | 0.0000 | Y | 132.92 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 6.2431 | 3204.84 | 20008.02 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 42.51 | 0.0000 | Y | 159.64 |
Interior Lighting Total | 7.5746 | 4835.13 | 36624.39 | 317.48 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 14248.59 | 3562.15 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 14248.59 | 3562.15 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 20008.02 | 5002.01 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 20008.02 | 5002.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 125.92 | AstronomicalClock | - | 42.14 | 42.14 | 1.00 | |
EXTERIOR_LIGHTS_B | 6860.50 | AstronomicalClock | - | 83.75 | 71.27 | 91.78 | |
Exterior Lighting Total | 6986.42 | 92.78 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18777.70 | 15037.56 | 3740.14 | 0.80 | 3.91 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 58722.99 | 45055.21 | 13667.78 | 0.77 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 17921.0 | 11.74 | 11.47 | ||||
PSZ-FINE STORAGE COOLING COIL | 56495.6 | 11.70 | 11.44 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 48506.73 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 26985.13 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 89177.75 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 1.21 | 112.20 | 92.91 | 1.00 | 3.96 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.10 | 1222.32 | 1107.16 | 1.00 | 1.38 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.87 | 3069.01 | 1070.05 | 1.00 | 1.27 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10974.77 | 13169.72 | 55.60 | 0.920 | 1.104 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 23.90 | 23.90 | 0.00828 | 30.65 | 0.00823 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 36575.96 | 43891.15 | 31.50 | 2.390 | 2.868 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.70 | 26.70 | 0.00830 | 31.30 | 0.00823 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 0.00 | 32.08 | 0.00830 | 31.30 | 0.00823 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 7494.32 | 8993.18 | 37.97 | 0.214 | 0.257 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00789 | 3.80 | 0.00506 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 17816.41 | 21379.69 | 15.34 | 0.429 | 0.515 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 15.56 | 15.56 | 0.00697 | 3.80 | 0.00506 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 40422.28 | 48506.73 | 15.14 | 1.006 | 1.208 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00620 | 3.80 | 0.00506 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.10 | 1.10 | 0.26 | 0.26 | 1.1040 | 1.1040 | 1.1040 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.87 | 2.87 | 0.52 | 0.52 | 2.8681 | 2.8681 | 2.8681 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 48506.730 | 48506.730 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 48506.73 | 48506.73 | 1.207652 | 10.00 | 8.27 | 0.00619822 | 43.33 | 21.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 10.00 | 0.00619822 | 79.8964 | 48506.73 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 18777.700 | 15037.558 | 1.104010 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 9388.85 | 8982.65 | 0.736007 | 25.45 | 16.51 | 0.00827211 | 12.00 | 11.09 | 0.00800000 | 30.77 | 0.00823264 | 18.27 | 13.8972 | 23.90 | 0.00827614 | 44.0049 | 10972.92 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 26985.127 | 26985.127 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 26985.13 | 26985.13 | 1.104015 | 19.42 | 13.73 | 0.00763209 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 9.2648 | 21.10 | 0.00789488 | 49.7919 | 7494.32 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 58722.990 | 45055.214 | 2.868110 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29361.49 | 28208.37 | 1.912073 | 28.27 | 17.49 | 0.00829142 | 12.00 | 11.09 | 0.00800000 | 31.30 | 0.00823349 | 18.45 | 22.2121 | 26.70 | 0.00830149 | 37.3665 | 36575.96 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 89177.754 | 89177.754 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 89177.75 | 89177.75 | 2.868105 | 13.82 | 10.51 | 0.00668892 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 14.8081 | 15.56 | 0.00697233 | 62.3536 | 17816.41 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 48506.730 | 48506.730 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 1.207652 | 1.42717790 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 48506.73 | 48506.73 | 1.0000 | 1.42717790 | 1.207652 | 10.00 | 8.27 | 0.00619822 | 25664.1 | 43.33 | 21.93 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 48506.73 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 10.00 | 0.00619822 | 10.00 | 0.00619822 | 79.8964 | 48506.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18777.700 | 15037.558 | 1.104010 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2174 | 1004.8586 | 1.1818 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.104015 | 1.30470087 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | Sensible | 9388.85 | 8982.65 | 1.0000 | 0.86979698 | 0.736007 | 25.45 | 16.51 | 0.00827211 | 46656.2 | 12.00 | 11.09 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9388.85 | 30.77 | 0.00823264 | 18.27 | 0.10228463 | 13.8972 | 23.90 | 0.00827614 | 23.90 | 0.00827614 | 44.0049 | 10972.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26985.127 | 26985.127 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.104015 | 1.30470087 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 26985.13 | 26985.13 | 1.0000 | 1.30470087 | 1.104015 | 19.42 | 13.73 | 0.00763209 | 38873.9 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26985.13 | 3.80 | 0.00505843 | 3.80 | 0.10228463 | 9.2648 | 21.01 | 0.00789488 | 21.10 | 0.00789488 | 49.7919 | 7494.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 58722.990 | 45055.214 | 2.868110 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2533 | 1004.8586 | 1.1818 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.868105 | 3.38946569 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | Sensible | 29361.49 | 28208.37 | 1.0000 | 2.25964747 | 1.912073 | 28.27 | 17.49 | 0.00829142 | 49576.6 | 12.00 | 11.09 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29361.49 | 31.30 | 0.00823349 | 18.45 | 0.42471127 | 22.2121 | 26.70 | 0.00830149 | 26.70 | 0.00830149 | 37.3665 | 36575.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 89177.754 | 89177.754 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.868105 | 3.38946569 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | Sensible | 89177.75 | 89177.75 | 1.0000 | 3.38946569 | 2.868105 | 13.82 | 10.51 | 0.00668892 | 30784.2 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 89177.75 | 3.80 | 0.00505843 | 3.80 | 0.42471127 | 14.8081 | 15.56 | 0.00697233 | 15.56 | 0.00697233 | 62.3536 | 17816.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.10 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 2.87 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 1522.83 | 1722.67 | 162.17 |
ZONE2 FINE STORAGE | 2433.50 | 2349.00 | 1367.67 |
ZONE3 BULK STORAGE | 2513.50 | 2886.00 | 1867.17 |
Facility | 2864.67 | 3050.83 | 1934.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 4.83 | 62.50 | 4.83 | 5.67 |
ZONE2 FINE STORAGE | 0.83 | 13.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 5.67 | 75.50 | 4.83 | 5.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 1.586 | 0.272 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.775 | 0.179 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.44 | 69.00 | 35277.63 | 0.000 | 0.116 | 0.000 | 0.099 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.44 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.50 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.36 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.44 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.30 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 6065837.15 | 0.00 | 6065837.15 | 1377013.49 | 7442850.64 | 3225648.14 | 5385.72 | 624.17 | 2750.12 | 278.93 |
ZONE2 FINE STORAGE | 8245861.48 | 0.00 | 8245861.48 | 4130661.33 | 12376522.81 | 13393694.68 | 5684.40 | 1768.52 | 1307.09 | 49.44 |
ZONE3 BULK STORAGE | 0.00 | 17419228.34 | 17419228.34 | 25131564.63 | 42550792.97 | 30805497.77 | 8644.67 | 6.63 | 108.69 | 4403.10 |
Total Facility | 14311698.63 | 17419228.34 | 31730926.97 | 30639239.45 | 62370166.42 | 47424840.58 | 8661.08 | 1943.77 | 3022.59 | 4447.81 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.4345 | 0.0000 | 0.4345 | 0.0748 | 0.5093 | 0.1023 | 493.56 | 624.17 | 2518.27 |
ZONE2 FINE STORAGE | 0.6157 | 0.0000 | 0.6157 | 0.1429 | 0.7586 | 0.4247 | 603.00 | 1768.33 | 1264.67 |
ZONE3 BULK STORAGE | 0.0000 | 0.9320 | 0.9320 | 1.1039 | 2.0359 | 0.9768 | 3534.75 | 5.30 | 95.95 |
Total Facility | 1.0503 | 0.9320 | 1.9823 | 1.3216 | 3.3038 | 1.5038 | 3537.08 | 1942.25 | 2740.02 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 8471553.06 | 0.00 | 8471553.06 | 3225648.14 | 5371.83 | 0.50 | 3387.67 | 278.93 |
PSZ-FINE STORAGE | 11516177.21 | 0.00 | 11516177.21 | 13393694.68 | 5673.31 | 0.64 | 3086.06 | 49.44 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.6068 | 0.0000 | 0.6068 | 0.1023 | 486.09 | 0.17 | 3149.74 |
PSZ-FINE STORAGE | 0.8599 | 0.0000 | 0.8599 | 0.4247 | 595.00 | 0.33 | 3040.67 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2039.27 | 1407.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2663.55 | 441.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.7747 | 0.5767 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 1.0050 | 1.1369 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 426 |
Defaulted Fields | 391 |
Fields with Defaults | 1157 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 622.82 | 3051.37 | 26-FEB-10:40 | 52181.60 | 17-OCT-14:40 |
Electricity:Building | 455.00 | 2570.37 | 26-FEB-10:40 | 40750.63 | 02-JAN-16:00 |
Electricity:Zone:ZONE1 OFFICE | 54.64 | 857.54 | 01-JAN-00:10 | 3432.39 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 454.54 | 2570.37 | 26-FEB-10:40 | 40750.63 | 02-JAN-16:00 |
InteriorLights:Electricity | 317.48 | 2081.83 | 26-FEB-10:40 | 30696.62 | 02-JAN-16:00 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 24.92 | 368.99 | 01-JAN-00:10 | 1578.50 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 317.48 | 2081.83 | 26-FEB-10:40 | 30696.62 | 02-JAN-16:00 |
LightsWired:InteriorLights:Electricity | 317.48 | 2081.83 | 26-FEB-10:40 | 30696.62 | 02-JAN-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 24.92 | 368.99 | 01-JAN-00:10 | 1578.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 317.48 | 2081.83 | 26-FEB-10:40 | 30696.62 | 02-JAN-16:00 |
Electricity:Zone:ZONE2 FINE STORAGE | 132.92 | 712.43 | 26-FEB-10:40 | 12111.30 | 02-JAN-15:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 132.92 | 712.43 | 26-FEB-10:40 | 12111.30 | 02-JAN-15:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 132.92 | 712.43 | 26-FEB-10:40 | 12111.30 | 02-JAN-15:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 267.45 | 1000.40 | 01-JAN-11:50 | 25511.43 | 17-OCT-15:50 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 159.64 | 1000.40 | 01-JAN-11:50 | 17006.82 | 02-JAN-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 159.64 | 1000.40 | 01-JAN-11:50 | 17006.82 | 02-JAN-16:00 |
InteriorEquipment:Electricity | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.72 | 488.55 | 01-JAN-00:10 | 1853.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.72 | 488.55 | 01-JAN-00:10 | 1853.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 31.34 | 0.00 | 01-JAN-00:10 | 4878.62 | 16-OCT-12:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.46 | 0.00 | 01-JAN-00:10 | 2305.29 | 16-OCT-14:50 |
Ventilation (simple):Fans:Electricity | 0.46 | 0.00 | 01-JAN-00:10 | 2305.29 | 16-OCT-14:50 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.46 | 0.00 | 01-JAN-00:10 | 2305.29 | 16-OCT-14:50 |
ElectricityPurchased:Facility | 622.82 | 3051.37 | 26-FEB-10:40 | 52181.60 | 17-OCT-14:40 |
ElectricityPurchased:Plant | 622.82 | 3051.37 | 26-FEB-10:40 | 52181.60 | 17-OCT-14:40 |
Cogeneration:ElectricityPurchased | 622.82 | 3051.37 | 26-FEB-10:40 | 52181.60 | 17-OCT-14:40 |
General:Cogeneration:ElectricityPurchased | 622.82 | 3051.37 | 26-FEB-10:40 | 52181.60 | 17-OCT-14:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 622.82 | 3051.37 | 26-FEB-10:40 | 52181.60 | 17-OCT-14:40 |
ElectricityNet:Plant | 622.82 | 3051.37 | 26-FEB-10:40 | 52181.60 | 17-OCT-14:40 |
Cogeneration:ElectricityNet | 622.82 | 3051.37 | 26-FEB-10:40 | 52181.60 | 17-OCT-14:40 |
General:Cogeneration:ElectricityNet | 622.82 | 3051.37 | 26-FEB-10:40 | 52181.60 | 17-OCT-14:40 |
Electricity:HVAC | 50.41 | 0.00 | 01-JAN-00:10 | 13696.24 | 16-OCT-12:00 |
General:Fans:Electricity | 30.88 | 0.00 | 01-JAN-00:10 | 2573.32 | 16-OCT-12:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 19.53 | 0.00 | 01-JAN-00:10 | 11165.02 | 16-OCT-12:00 |
General:Cooling:Electricity | 19.53 | 0.00 | 01-JAN-00:10 | 11165.02 | 16-OCT-12:00 |
ExteriorLights:Electricity | 92.78 | 0.00 | 01-JAN-07:00 | 6986.42 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 92.78 | 0.00 | 01-JAN-07:00 | 6986.42 | 01-JAN-06:10 |
Electricity:Plant | 24.63 | 481.00 | 10-JAN-06:10 | 1797.12 | 25-JAN-12:40 |
WaterSystems:Electricity | 24.63 | 481.00 | 10-JAN-06:10 | 1797.12 | 25-JAN-12:40 |
Water Heater:WaterSystems:Electricity | 24.63 | 481.00 | 10-JAN-06:10 | 1797.12 | 25-JAN-12:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1.37 | 0.00 | 01-JAN-00:10 | 22215.06 | 03-JAN-06:10 |
NaturalGas:HVAC | 1.37 | 0.00 | 01-JAN-00:10 | 22215.06 | 03-JAN-06:10 |
Heating:NaturalGas | 1.37 | 0.00 | 01-JAN-00:10 | 22215.06 | 03-JAN-06:10 |
General:Heating:NaturalGas | 1.37 | 0.00 | 01-JAN-00:10 | 22215.06 | 03-JAN-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 26-JUN-11:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 26-JUN-11:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 26-JUN-11:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 26-JUN-11:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 26-JUN-11:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 26-JUN-11:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 26-JUN-11:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 26-JUN-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 209.23 | 0.00 | 01-JAN-00:10 | 74127.67 | 17-AUG-15:00 |
EnergyTransfer:Building | 122.15 | 0.00 | 01-JAN-00:10 | 32906.36 | 30-SEP-14:00 |
EnergyTransfer:Zone:ZONE1 OFFICE | 46.83 | 0.00 | 01-JAN-00:10 | 12655.90 | 03-JAN-06:10 |
Heating:EnergyTransfer | 2.80 | 0.00 | 01-JAN-00:10 | 16672.68 | 03-JAN-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 1.86 | 0.00 | 01-JAN-00:10 | 12655.90 | 03-JAN-06:10 |
General:Heating:EnergyTransfer | 2.80 | 0.00 | 01-JAN-00:10 | 16672.68 | 03-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 1.86 | 0.00 | 01-JAN-00:10 | 12655.90 | 03-JAN-06:10 |
Cooling:EnergyTransfer | 119.35 | 0.00 | 01-JAN-00:10 | 32906.36 | 30-SEP-14:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 44.97 | 0.00 | 01-JAN-00:10 | 10373.61 | 26-MAY-17:20 |
General:Cooling:EnergyTransfer | 119.35 | 0.00 | 01-JAN-00:10 | 32906.36 | 30-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 44.97 | 0.00 | 01-JAN-00:10 | 10373.61 | 26-MAY-17:20 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 75.32 | 0.00 | 01-JAN-00:10 | 25252.00 | 30-SEP-14:00 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.94 | 0.00 | 01-JAN-00:10 | 7652.48 | 03-JAN-03:20 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.94 | 0.00 | 01-JAN-00:10 | 7652.48 | 03-JAN-03:20 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 74.38 | 0.00 | 01-JAN-00:10 | 25252.00 | 30-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 74.38 | 0.00 | 01-JAN-00:10 | 25252.00 | 30-SEP-14:00 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 87.08 | 0.00 | 01-JAN-00:10 | 44799.71 | 17-AUG-15:00 |
HeatingCoils:EnergyTransfer | 0.94 | 0.00 | 01-JAN-00:10 | 16502.05 | 03-JAN-06:10 |
CoolingCoils:EnergyTransfer | 86.14 | 0.00 | 01-JAN-00:10 | 44799.71 | 17-AUG-15:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 1.861 | -44.972 | 0.000 | 0.000 | 9.215 | 24.919 | 29.720 | 9.355 | 0.000 | 0.165 | 0.000 | 0.000 | -8.976 | 0.000 | -10.918 | -10.368 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 0.938 | -74.379 | 0.000 | 0.000 | 19.597 | 132.918 | 0.000 | 45.543 | 0.000 | 0.179 | 0.000 | 0.000 | -21.427 | 0.000 | -36.996 | -66.373 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 45.962 | 159.641 | 107.344 | 577.553 | 0.000 | 5.230 | 0.032 | 0.000 | -247.728 | 0.000 | -300.926 | -347.077 |
Total Facility | 0.000 | 0.000 | 2.799 | -119.351 | 0.000 | 0.000 | 74.774 | 317.478 | 137.063 | 632.451 | 0.000 | 5.575 | 0.032 | 0.000 | -278.131 | 0.000 | -348.840 | -423.818 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 26-MAY-17:15 | 0.00 | 0.00 | 0.00 | -20744.78 | 0.00 | 0.00 | 0.00 | 368.99 | 488.55 | 1135.89 | 0.00 | 0.00 | 19370.45 | 0.00 | -0.00 | 0.00 | -619.10 | 0.00 |
ZONE2 FINE STORAGE | 20-AUG-13:33 | 0.00 | 0.00 | 0.00 | -51209.53 | 0.00 | 0.00 | 0.00 | 1068.64 | 0.00 | 6441.72 | 0.00 | 0.00 | 44832.79 | 0.00 | -0.00 | 0.00 | -1133.62 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 15-JUL-17:06 | 0.00 | 0.00 | 0.00 | -62554.41 | 0.00 | 0.00 | 0.00 | 3175.72 | 2538.58 | 54763.34 | 0.00 | 0.00 | 2076.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 03-JAN-06:01 | 0.00 | 0.00 | 27275.67 | 0.00 | 0.00 | 0.00 | 142.35 | 471.50 | 556.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -653.09 | 0.00 | -653.27 | -27139.32 |
ZONE2 FINE STORAGE | 03-JAN-06:40 | 0.00 | 0.00 | 31053.33 | 0.00 | 0.00 | 0.00 | 353.29 | 1424.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1604.12 | 0.00 | -619.88 | -30607.47 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-JAN-06:42 | 0.00 | 0.00 | 38692.49 | 0.00 | 0.00 | 0.00 | 1316.43 | 3897.16 | 2606.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -27841.90 | 0.00 | -2828.22 | -15842.15 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1040 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.1040 | 0.0926 | 1.0000 | Not calculated | 0.1023 | 0.0926 | ||
PSZ-FINE STORAGE | 2.8681 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.8681 | 0.1481 | 1.0000 | Not calculated | 0.4247 | 0.1481 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1040 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.1040 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0926 | ||
PSZ-FINE STORAGE | 2.8681 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.8681 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1481 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1040 | 1.1040 | 1.1040 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.8681 | 2.8681 | 2.8681 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1040 | 1.1040 | 1.1040 | 1.1040 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.8681 | 2.8681 | 2.8681 | 2.8681 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1040 | 1.1040 | 1.1040 | No | 0.1023 | 0.3980 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.8681 | 2.8681 | 2.8681 | No | 0.4247 | 0.8245 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1040 | 1.1040 | 1.1040 | 1.1040 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.8681 | 2.8681 | 2.8681 | 2.8681 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 4.83 |
Number of hours cooling loads not met | 5.67 |
Number of hours not met | 10.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1.37 | 22215.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 19.53 | 11165.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 317.48 | 30696.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 92.78 | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 137.06 | 10054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.46 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 30.88 | 2573.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 24.63 | 1797.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 137.06 | 622.82 |
Natural Gas | 0.00 | 1.37 |
Additional | 0.00 | 0.00 |
Total | 137.06 | 624.19 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 65.66 |
Space Heating | 0.00 |
Space Cooling | 4.04 |
Fans (All) | 6.48 |
Service Water Heating | 5.09 |
Receptacle Equipment | 28.35 |
Miscellaneous (All) | 128.81 |
Subtotal | 128.81 |
Natural Gas [MJ/m2] | |
Space Heating | 0.28 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.28 |
Subtotal | 0.28 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 50.86 |
Space Heating | 0.22 |
Space Cooling | 3.13 |
Fans (All) | 5.02 |
Service Water Heating | 3.95 |
Receptacle Equipment | 21.96 |
Miscellaneous | 14.86 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2970. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4378. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8554.83 | 205.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7443.50 | 1316.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 6461.33 | 2298.33 | 0.33 | 0.00 | 0.00 |
Min | 6461.33 | 205.17 | 0.00 | 0.00 | 0.00 |
Max | 8554.83 | 2298.33 | 0.33 | 0.00 | 0.00 |
Average | 7486.56 | 1273.33 | 0.11 | 0.00 | 0.00 |
Sum | 22459.67 | 3820.00 | 0.33 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 54162.50 | 28556.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 121020.67 | 70149.33 | 23.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 121020.67 | 70149.33 | 23.00 | 0.00 | 0.00 |
Average | 69403.39 | 32901.94 | 7.67 | 0.00 | 0.00 |
Sum | 208210.17 | 98705.83 | 23.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8430.00 | 330.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 6290.67 | 2469.33 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 5923.50 | 2836.50 | 0.00 | 0.00 | 0.00 |
Min | 5923.50 | 330.00 | 0.00 | 0.00 | 0.00 |
Max | 8430.00 | 2836.50 | 0.00 | 0.00 | 0.00 |
Average | 6881.39 | 1878.61 | 0.00 | 0.00 | 0.00 |
Sum | 20644.17 | 5635.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 32730.17 | 296.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 48159.00 | 34560.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 115633.67 | 75559.33 | 0.00 | 0.00 | 0.00 |
Min | 32730.17 | 296.83 | 0.00 | 0.00 | 0.00 |
Max | 115633.67 | 75559.33 | 0.00 | 0.00 | 0.00 |
Average | 65507.61 | 36805.39 | 0.00 | 0.00 | 0.00 |
Sum | 196522.83 | 110416.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 2920.00 | 0.00 |
Sum | 0.00 | 8760.00 | 8760.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 27573.00 | 0.00 |
Sum | 0.00 | 191193.00 | 82719.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128236E+10 | 4159.92 | 21-JAN-15:20 | 14.00 | 11.03 | 0.610004E+09 | 769.00 | 17-JAN-14:09 | 14.00 | 11.03 |
February | 0.115249E+10 | 4328.09 | 03-FEB-15:20 | 22.33 | 9.30 | 0.566325E+09 | 768.98 | 01-FEB-13:50 | 22.33 | 9.30 |
March | 0.149120E+10 | 6488.18 | 22-MAR-17:20 | 17.33 | 15.24 | 0.662593E+09 | 769.01 | 23-MAR-15:00 | 21.00 | 17.19 |
April | 0.338278E+10 | 19215.09 | 28-APR-17:15 | 14.33 | 11.68 | 0.631106E+09 | 769.00 | 27-APR-10:20 | 14.33 | 11.68 |
May | 0.400732E+10 | 20747.22 | 26-MAY-17:15 | 15.33 | 10.34 | 0.658806E+09 | 769.00 | 02-MAY-15:50 | 15.33 | 10.34 |
June | 0.555824E+10 | 20336.07 | 04-JUN-23:02 | 14.00 | 12.74 | 0.660065E+09 | 769.02 | 28-JUN-09:39 | 21.67 | 18.63 |
July | 0.701468E+10 | 20528.33 | 04-JUL-23:01 | 16.00 | 14.12 | 0.634658E+09 | 769.02 | 29-JUL-08:39 | 21.33 | 18.45 |
August | 0.717499E+10 | 19151.91 | 27-AUG-23:01 | 15.02 | 14.97 | 0.685461E+09 | 769.03 | 18-AUG-08:30 | 15.02 | 14.97 |
September | 0.547916E+10 | 19062.78 | 04-SEP-23:02 | 15.83 | 14.07 | 0.634704E+09 | 769.02 | 23-SEP-10:30 | 21.50 | 17.91 |
October | 0.487313E+10 | 20466.26 | 15-OCT-23:02 | 20.33 | 10.84 | 0.633638E+09 | 769.03 | 05-OCT-09:09 | 20.33 | 10.84 |
November | 0.200934E+10 | 4497.67 | 18-NOV-15:10 | 23.83 | 14.21 | 0.601520E+09 | 769.00 | 10-NOV-13:30 | 23.83 | 14.21 |
December | 0.154636E+10 | 4454.73 | 05-DEC-15:20 | 24.33 | 12.97 | 0.619737E+09 | 768.99 | 07-DEC-14:09 | 20.67 | 15.41 |
Annual Sum or Average | 0.449721E+11 | 0.759862E+10 | ||||||||
Minimum of Months | 0.115249E+10 | 4159.92 | 14.00 | 9.30 | 0.566325E+09 | 768.98 | 14.00 | 9.30 | ||
Maximum of Months | 0.717499E+10 | 20747.22 | 24.33 | 15.24 | 0.685461E+09 | 769.03 | 23.83 | 18.63 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.180024E+10 | 5115.49 | 12-JAN-09:00 | 8.00 | 8.00 | 0.138539E+10 | 2246.79 | 18-JAN-14:39 | 23.53 | 14.82 |
February | 0.204674E+10 | 4203.04 | 25-FEB-12:45 | 10.50 | 9.59 | 0.126898E+10 | 2246.79 | 03-FEB-15:30 | 10.50 | 9.59 |
March | 0.281584E+10 | 8530.11 | 23-MAR-14:20 | 22.67 | 17.32 | 0.149802E+10 | 2246.88 | 23-MAR-14:09 | 22.67 | 17.32 |
April | 0.479305E+10 | 36735.96 | 30-APR-17:05 | 21.67 | 15.82 | 0.170626E+10 | 2246.92 | 27-APR-13:20 | 21.67 | 15.82 |
May | 0.521940E+10 | 37205.30 | 28-MAY-12:25 | 21.50 | 15.64 | 0.180901E+10 | 2246.91 | 04-MAY-13:20 | 21.50 | 15.64 |
June | 0.910968E+10 | 39739.94 | 04-JUN-11:23 | 20.50 | 14.79 | 0.189012E+10 | 2246.97 | 29-JUN-14:50 | 22.17 | 18.15 |
July | 0.145471E+11 | 49541.77 | 30-JUL-14:43 | 23.17 | 19.04 | 0.184969E+10 | 2246.96 | 21-JUL-13:39 | 23.17 | 19.04 |
August | 0.145323E+11 | 51206.15 | 20-AUG-13:33 | 23.33 | 18.14 | 0.199589E+10 | 2246.97 | 25-AUG-14:50 | 22.33 | 18.29 |
September | 0.883433E+10 | 38470.53 | 03-SEP-13:41 | 21.17 | 16.05 | 0.182211E+10 | 2246.95 | 11-SEP-13:50 | 23.00 | 17.26 |
October | 0.670764E+10 | 50286.46 | 15-OCT-14:13 | 31.00 | 15.33 | 0.179107E+10 | 2246.95 | 03-OCT-13:00 | 31.00 | 15.33 |
November | 0.211304E+10 | 4889.80 | 01-NOV-08:70 | 12.33 | 11.60 | 0.150095E+10 | 2246.80 | 18-NOV-13:39 | 26.00 | 15.08 |
December | 0.185941E+10 | 5135.20 | 01-DEC-08:13 | 9.67 | 9.31 | 0.145104E+10 | 2246.79 | 05-DEC-15:09 | 24.67 | 13.10 |
Annual Sum or Average | 0.743788E+11 | 0.199685E+11 | ||||||||
Minimum of Months | 0.180024E+10 | 4203.04 | 8.00 | 8.00 | 0.126898E+10 | 2246.79 | 10.50 | 9.59 | ||
Maximum of Months | 0.145471E+11 | 51206.15 | 31.00 | 19.04 | 0.199589E+10 | 2246.97 | 31.00 | 19.04 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 | 0.248865E+10 | 3979.54 | 24-JAN-15:50 | 24.17 | 15.12 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 | 0.238014E+10 | 4111.79 | 03-FEB-15:09 | 22.67 | 9.08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.62 | 0.286467E+10 | 4709.59 | 23-MAR-14:39 | 22.33 | 17.37 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 | 0.361495E+10 | 5774.36 | 26-APR-14:09 | 25.50 | 16.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 | 14.50 | 0.410246E+10 | 6232.60 | 04-MAY-12:39 | 23.33 | 16.64 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 | 0.466248E+10 | 6365.55 | 29-JUN-10:39 | 24.67 | 19.30 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 16.43 | 15.81 | 0.498462E+10 | 6390.64 | 19-JUL-14:50 | 27.00 | 20.29 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 | 0.535278E+10 | 6373.59 | 19-AUG-14:20 | 26.67 | 19.73 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 | 14.83 | 0.465344E+10 | 8524.82 | 29-SEP-13:09 | 35.67 | 18.16 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 | 0.435198E+10 | 8420.32 | 16-OCT-12:09 | 35.68 | 17.48 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.07 | 0.291067E+10 | 4572.91 | 01-NOV-14:30 | 17.00 | 13.18 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.44 | 0.267135E+10 | 4184.43 | 05-DEC-15:20 | 24.33 | 12.97 |
Annual Sum or Average | 0.00 | 0.450382E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 7.63 | 5.44 | 0.238014E+10 | 3979.54 | 17.00 | 9.08 | ||
Maximum of Months | 0.00 | 0.00 | 18.42 | 17.39 | 0.535278E+10 | 8524.82 | 35.68 | 20.29 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.517309E+09 | 27275.70 | 03-JAN-06:01 | 4.67 |
February | 0.251741E+09 | 26678.16 | 28-FEB-06:02 | 10.17 |
March | 0.370008E+09 | 27170.54 | 30-MAR-05:01 | 4.97 |
April | 0.101552E+09 | 26871.13 | 01-APR-05:01 | 7.83 |
May | 75098315.52 | 1371.72 | 05-MAY-06:10 | 16.17 |
June | 26363050.17 | 1631.33 | 28-JUN-06:05 | 16.03 |
July | 5902800.63 | 1388.99 | 06-JUL-06:10 | 16.00 |
August | 8061147.84 | 1695.42 | 10-AUG-06:05 | 18.17 |
September | 16989095.40 | 1463.92 | 15-SEP-06:10 | 14.00 |
October | 52330677.59 | 1636.10 | 03-OCT-06:05 | 19.17 |
November | 0.134115E+09 | 15114.19 | 27-NOV-06:03 | 10.67 |
December | 0.301373E+09 | 26898.78 | 15-DEC-06:01 | 6.00 |
Annual Sum or Average | 0.186084E+10 | |||
Minimum of Months | 5902800.63 | 1371.72 | 4.67 | |
Maximum of Months | 0.517309E+09 | 27275.70 | 19.17 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169661E+09 | 31053.33 | 03-JAN-06:40 | 3.67 |
February | 70558587.28 | 1394.65 | 27-FEB-08:00 | 9.00 |
March | 76665936.84 | 1253.77 | 28-MAR-07:00 | 11.00 |
April | 74630297.92 | 1119.27 | 21-APR-07:00 | 13.00 |
May | 73737115.00 | 1257.53 | 25-MAY-07:00 | 14.00 |
June | 62621212.37 | 1128.09 | 07-JUN-07:00 | 14.00 |
July | 38968170.39 | 1132.81 | 05-JUL-06:12 | 17.33 |
August | 54306880.00 | 1101.34 | 18-AUG-06:13 | 17.67 |
September | 70420678.95 | 1172.65 | 27-SEP-07:00 | 16.00 |
October | 68466217.52 | 1072.59 | 20-OCT-07:00 | 17.00 |
November | 68416304.69 | 1143.33 | 01-NOV-07:00 | 11.00 |
December | 0.110029E+09 | 1365.11 | 16-DEC-13:00 | 26.00 |
Annual Sum or Average | 0.938482E+09 | |||
Minimum of Months | 38968170.39 | 1072.59 | 3.67 | |
Maximum of Months | 0.169661E+09 | 31053.33 | 26.00 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.208425E+10 | 1578.50 | 02-JAN-08:09 | 0.248944E+10 | 1853.89 | 02-JAN-08:09 |
February | 0.190093E+10 | 1578.50 | 01-FEB-08:09 | 0.226834E+10 | 1853.89 | 01-FEB-08:09 |
March | 0.217193E+10 | 1578.50 | 01-MAR-08:09 | 0.258391E+10 | 1853.89 | 01-MAR-08:09 |
April | 0.205237E+10 | 1578.50 | 01-APR-07:10 | 0.244723E+10 | 1853.89 | 01-APR-07:10 |
May | 0.212809E+10 | 1578.50 | 01-MAY-07:10 | 0.253668E+10 | 1853.89 | 01-MAY-07:10 |
June | 0.209621E+10 | 1578.50 | 01-JUN-07:10 | 0.249447E+10 | 1853.89 | 01-JUN-07:10 |
July | 0.208425E+10 | 1578.50 | 01-JUL-07:10 | 0.248944E+10 | 1853.89 | 01-JUL-07:10 |
August | 0.217193E+10 | 1578.50 | 01-AUG-07:10 | 0.258391E+10 | 1853.89 | 01-AUG-07:10 |
September | 0.205237E+10 | 1578.50 | 01-SEP-07:10 | 0.244723E+10 | 1853.89 | 01-SEP-07:10 |
October | 0.208425E+10 | 1578.50 | 02-OCT-07:10 | 0.248944E+10 | 1853.89 | 02-OCT-07:10 |
November | 0.200853E+10 | 1578.50 | 01-NOV-07:10 | 0.239999E+10 | 1853.89 | 01-NOV-07:10 |
December | 0.208425E+10 | 1578.50 | 01-DEC-08:09 | 0.248944E+10 | 1853.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.249194E+11 | 0.297195E+11 | ||||
Minimum of Months | 0.190093E+10 | 1578.50 | 0.226834E+10 | 1853.89 | ||
Maximum of Months | 0.217193E+10 | 1578.50 | 0.258391E+10 | 1853.89 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.122140E+11 | 12111.30 | 02-JAN-15:09 | 0.00 | 0.00 |
February | 0.103071E+11 | 12111.30 | 02-FEB-09:09 | 0.00 | 0.00 |
March | 0.112992E+11 | 12111.30 | 23-MAR-08:09 | 0.00 | 0.00 |
April | 0.105269E+11 | 11102.03 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.102552E+11 | 11102.03 | 09-MAY-08:09 | 0.00 | 0.00 |
June | 0.103266E+11 | 11102.03 | 16-JUN-08:09 | 0.00 | 0.00 |
July | 0.102637E+11 | 11102.03 | 05-JUL-08:09 | 0.00 | 0.00 |
August | 0.112661E+11 | 11102.03 | 07-AUG-08:09 | 0.00 | 0.00 |
September | 0.109093E+11 | 12111.30 | 21-SEP-08:09 | 0.00 | 0.00 |
October | 0.116562E+11 | 12111.30 | 12-OCT-08:09 | 0.00 | 0.00 |
November | 0.114963E+11 | 12111.30 | 02-NOV-14:30 | 0.00 | 0.00 |
December | 0.123970E+11 | 12111.30 | 01-DEC-15:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.132918E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.102552E+11 | 11102.03 | 0.00 | 0.00 | |
Maximum of Months | 0.123970E+11 | 12111.30 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.152741E+11 | 17006.82 | 02-JAN-15:00 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.126359E+11 | 15589.58 | 14-FEB-15:00 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.136227E+11 | 15006.02 | 01-MAR-16:00 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.122112E+11 | 14172.35 | 21-APR-14:00 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.121391E+11 | 12755.11 | 09-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.119813E+11 | 12505.01 | 08-JUN-07:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.119239E+11 | 12505.01 | 12-JUL-07:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.129587E+11 | 12755.11 | 31-AUG-14:50 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.127433E+11 | 15006.02 | 18-SEP-07:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.142038E+11 | 15589.58 | 17-OCT-14:00 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.142518E+11 | 17006.82 | 06-NOV-15:50 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.156954E+11 | 17006.82 | 01-DEC-15:00 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.159641E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.119239E+11 | 12505.01 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.156954E+11 | 17006.82 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.208425E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2798181.94 | 0.108679E+10 |
February | 0.127628E+10 | 0.190093E+10 | 0.226834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 945983.50 | 0.120279E+10 |
March | 0.149825E+10 | 0.217193E+10 | 0.258391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24084.01 | 0.148226E+10 |
April | 0.138726E+10 | 0.205237E+10 | 0.244723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3118066.08 | 0.973091E+09 |
May | 0.144276E+10 | 0.212809E+10 | 0.253668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44083.49 | 0.108283E+10 |
June | 0.144276E+10 | 0.209621E+10 | 0.249447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 812327.74 | 0.697070E+09 |
July | 0.138726E+10 | 0.208425E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22658533.64 | 0.442906E+09 |
August | 0.149825E+10 | 0.217193E+10 | 0.258391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22901949.63 | 0.507666E+09 |
September | 0.138726E+10 | 0.205237E+10 | 0.244723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36703337.85 | 0.593590E+09 |
October | 0.138726E+10 | 0.208425E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70409932.48 | 0.697427E+09 |
November | 0.133177E+10 | 0.200853E+10 | 0.239999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1399517.80 | 0.107596E+10 |
December | 0.138726E+10 | 0.208425E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3320700.52 | 0.107594E+10 |
Annual Sum or Average | 0.168137E+11 | 0.249194E+11 | 0.297195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165137E+09 | 0.109183E+11 |
Minimum of Months | 0.127628E+10 | 0.190093E+10 | 0.226834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24084.01 | 0.442906E+09 |
Maximum of Months | 0.149825E+10 | 0.217193E+10 | 0.258391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70409932.48 | 0.148226E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.122140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5187359.77 | 0.276971E+10 |
February | 0.300332E+10 | 0.103071E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357273E+10 |
March | 0.352563E+10 | 0.112992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428505E+10 |
April | 0.326447E+10 | 0.105269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41969.06 | 0.343797E+10 |
May | 0.339505E+10 | 0.102552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416539E+10 |
June | 0.339505E+10 | 0.103266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283196E+10 |
July | 0.326447E+10 | 0.102637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3411398.96 | 0.213479E+10 |
August | 0.352563E+10 | 0.112661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2088478.18 | 0.247245E+10 |
September | 0.326447E+10 | 0.109093E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47005364.64 | 0.226706E+10 |
October | 0.326447E+10 | 0.116562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118172E+09 | 0.287486E+10 |
November | 0.313390E+10 | 0.114963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2874194.47 | 0.315633E+10 |
December | 0.326447E+10 | 0.123970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 609060.10 | 0.302772E+10 |
Annual Sum or Average | 0.395654E+11 | 0.132918E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179390E+09 | 0.369960E+11 |
Minimum of Months | 0.300332E+10 | 0.102552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213479E+10 |
Maximum of Months | 0.352563E+10 | 0.123970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118172E+09 | 0.428505E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.152741E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381446E+09 | 0.108926E+11 |
February | 0.690763E+10 | 0.126359E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31043737.34 | 0.151590E+11 |
March | 0.810895E+10 | 0.136227E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19055464.80 | 0.193869E+11 |
April | 0.750829E+10 | 0.122112E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43170605.35 | 0.176729E+11 |
May | 0.780862E+10 | 0.121391E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230755E+11 |
June | 0.780862E+10 | 0.119813E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186789E+11 |
July | 0.750829E+10 | 0.119239E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170748E+11 |
August | 0.810895E+10 | 0.129587E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184532E+11 |
September | 0.750829E+10 | 0.127433E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52741636.98 | 0.156620E+11 |
October | 0.750829E+10 | 0.142038E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435170E+09 | 0.166508E+11 |
November | 0.720796E+10 | 0.142518E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109991E+09 | 0.141236E+11 |
December | 0.750829E+10 | 0.156954E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425096E+09 | 0.120262E+11 |
Annual Sum or Average | 0.910005E+11 | 0.159641E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149771E+10 | 0.198856E+12 |
Minimum of Months | 0.690763E+10 | 0.119239E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108926E+11 |
Maximum of Months | 0.810895E+10 | 0.156954E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435170E+09 | 0.230755E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1578.50 | 02-JAN-08:09 | 1853.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 470.66 | 18-JAN-13:00 | 4622.54 | 09-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 1578.50 | 01-FEB-08:09 | 1853.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 407.30 | 01-FEB-12:10 | 3699.92 | 10-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 1578.50 | 01-MAR-08:09 | 1853.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.80 | 11-MAR-14:00 | 4410.16 | 30-MAR-06:10 |
April | 1680.92 | 01-APR-07:10 | 1578.50 | 01-APR-07:10 | 1853.89 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 480.01 | 26-APR-11:10 | 3619.14 | 17-APR-17:00 |
May | 1680.92 | 01-MAY-07:10 | 1578.50 | 01-MAY-07:10 | 1853.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 03-MAY-12:00 | 3195.78 | 12-MAY-16:10 |
June | 1680.92 | 01-JUN-07:10 | 1578.50 | 01-JUN-07:10 | 1853.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.06 | 29-JUN-11:10 | 2481.07 | 05-JUN-06:05 |
July | 1680.92 | 01-JUL-07:10 | 1578.50 | 01-JUL-07:10 | 1853.89 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 945.38 | 19-JUL-12:00 | 2078.21 | 17-JUL-06:20 |
August | 1680.92 | 01-AUG-07:10 | 1578.50 | 01-AUG-07:10 | 1853.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 924.09 | 18-AUG-12:00 | 2261.21 | 28-AUG-07:00 |
September | 1680.92 | 01-SEP-07:10 | 1578.50 | 01-SEP-07:10 | 1853.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2665.85 | 29-SEP-12:00 | 2619.97 | 20-SEP-07:00 |
October | 1680.92 | 02-OCT-07:10 | 1578.50 | 02-OCT-07:10 | 1853.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2977.09 | 16-OCT-11:10 | 3386.35 | 12-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 1578.50 | 01-NOV-07:10 | 1853.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.19 | 19-NOV-13:00 | 3646.45 | 30-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1578.50 | 01-DEC-08:09 | 1853.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 475.80 | 19-DEC-13:00 | 3985.92 | 13-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1578.50 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 2.80 | 2078.21 | |||||
Maximum of Months | 1680.92 | 1578.50 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 2977.09 | 4622.54 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 12111.30 | 02-JAN-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 729.51 | 15-JAN-10:00 | 4558.33 | 27-JAN-05:00 |
February | 3955.50 | 01-FEB-08:09 | 12111.30 | 02-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5340.59 | 25-FEB-16:10 |
March | 3955.50 | 01-MAR-08:09 | 12111.30 | 23-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7942.98 | 28-MAR-15:10 |
April | 3955.50 | 01-APR-07:10 | 11102.03 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.00 | 26-APR-13:00 | 8366.20 | 17-APR-15:55 |
May | 3955.50 | 01-MAY-07:10 | 11102.03 | 09-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 7754.32 | 12-MAY-16:00 |
June | 3955.50 | 01-JUN-07:10 | 11102.03 | 16-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 4500.76 | 12-JUN-16:00 |
July | 3955.50 | 01-JUL-07:10 | 11102.03 | 05-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.83 | 31-JUL-13:00 | 4235.90 | 20-JUL-18:00 |
August | 3955.50 | 01-AUG-07:10 | 11102.03 | 07-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.90 | 17-AUG-14:00 | 3134.10 | 22-AUG-17:00 |
September | 3955.50 | 01-SEP-07:10 | 12111.30 | 21-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2249.71 | 29-SEP-15:10 | 3732.38 | 02-SEP-15:10 |
October | 3955.50 | 02-OCT-07:10 | 12111.30 | 12-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2171.04 | 14-OCT-15:10 | 4638.81 | 23-OCT-15:10 |
November | 3955.50 | 01-NOV-07:10 | 12111.30 | 02-NOV-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.13 | 19-NOV-10:00 | 4748.19 | 30-NOV-07:10 |
December | 3955.50 | 01-DEC-08:09 | 12111.30 | 01-DEC-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.32 | 25-DEC-12:00 | 4882.22 | 13-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 11102.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3134.10 | ||||
Maximum of Months | 3955.50 | 12111.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2249.71 | 8366.20 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 17006.82 | 02-JAN-15:00 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6809.41 | 15-JAN-10:00 | 19095.20 | 27-JAN-05:00 |
February | 9097.65 | 01-FEB-08:09 | 15589.58 | 14-FEB-15:00 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4249.57 | 01-FEB-12:00 | 25583.61 | 25-FEB-13:05 |
March | 9097.65 | 01-MAR-08:09 | 15006.02 | 01-MAR-16:00 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1381.68 | 11-MAR-11:00 | 31403.06 | 28-MAR-14:20 |
April | 9097.65 | 01-APR-07:10 | 14172.35 | 21-APR-14:00 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3104.76 | 01-APR-12:10 | 37127.77 | 17-APR-15:55 |
May | 9097.65 | 01-MAY-07:10 | 12755.11 | 09-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 34587.69 | 12-MAY-16:00 |
June | 9097.65 | 01-JUN-07:10 | 12505.01 | 08-JUN-07:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 20735.64 | 06-JUN-13:00 |
July | 9097.65 | 01-JUL-07:10 | 12505.01 | 12-JUL-07:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 24970.87 | 20-JUL-09:00 |
August | 9097.65 | 01-AUG-07:10 | 12755.11 | 31-AUG-14:50 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 17994.25 | 22-AUG-16:00 |
September | 9097.65 | 01-SEP-07:10 | 15006.02 | 18-SEP-07:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5343.79 | 29-SEP-10:12 | 23521.56 | 02-SEP-15:00 |
October | 9097.65 | 02-OCT-07:10 | 15589.58 | 17-OCT-14:00 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15067.90 | 14-OCT-12:10 | 23747.12 | 07-OCT-08:00 |
November | 9097.65 | 01-NOV-07:10 | 17006.82 | 06-NOV-15:50 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4150.73 | 19-NOV-13:00 | 19011.81 | 01-NOV-08:00 |
December | 9097.65 | 01-DEC-08:09 | 17006.82 | 01-DEC-15:00 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10184.33 | 18-DEC-11:00 | 22530.85 | 12-DEC-13:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 12505.01 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17994.25 | |||||
Maximum of Months | 9097.65 | 17006.82 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 15067.90 | 37127.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4159.92 | 21-JAN-15:20 | 1680.92 | 1578.50 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.17 |
February | 4328.09 | 03-FEB-15:20 | 1680.92 | 1578.50 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.57 |
March | 6488.18 | 22-MAR-17:20 | 0.00 | 737.99 | 977.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.38 |
April | 19215.09 | 28-APR-17:15 | 0.00 | 737.99 | 977.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 622.73 |
May | 20747.22 | 26-MAY-17:15 | 0.00 | 737.99 | 977.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 619.10 |
June | 20336.07 | 04-JUN-23:02 | 0.00 | 1844.97 | 2442.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.81 |
July | 20528.33 | 04-JUL-23:01 | 0.00 | 2582.96 | 3419.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19151.91 | 27-AUG-23:01 | 0.00 | 2582.96 | 3419.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.31 |
September | 19062.78 | 04-SEP-23:02 | 0.00 | 1844.97 | 2442.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20466.26 | 15-OCT-23:02 | 0.00 | 2213.97 | 2931.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.80 |
November | 4497.67 | 18-NOV-15:10 | 1680.92 | 1578.50 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.14 |
December | 4454.73 | 05-DEC-15:20 | 1680.92 | 1578.50 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 20.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4159.92 | 0.00 | 737.99 | 977.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20747.22 | 1680.92 | 2582.96 | 3419.84 | 0.00 | 0.00 | 0.00 | 0.00 | 20.13 | 622.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5115.49 | 12-JAN-09:00 | 3955.50 | 10686.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4203.04 | 25-FEB-12:45 | 4192.83 | 18166.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2469.25 |
March | 8530.11 | 23-MAR-14:20 | 3955.50 | 10092.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 573.39 |
April | 36735.96 | 30-APR-17:05 | 0.00 | 2612.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 671.21 |
May | 37205.30 | 28-MAY-12:25 | 0.00 | 1899.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1610.08 |
June | 39739.94 | 04-JUN-11:23 | 0.00 | 2137.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1659.59 |
July | 49541.77 | 30-JUL-14:43 | 0.00 | 2849.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1097.53 |
August | 51206.15 | 20-AUG-13:33 | 0.00 | 3205.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1133.62 |
September | 38470.53 | 03-SEP-13:41 | 0.00 | 7480.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2086.55 |
October | 50286.46 | 15-OCT-14:13 | 0.00 | 3918.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1174.19 | 0.00 |
November | 4889.80 | 01-NOV-08:70 | 3955.50 | 11102.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1649.56 |
December | 5135.20 | 01-DEC-08:13 | 11866.50 | 29387.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4203.04 | 0.00 | 1899.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 51206.15 | 11866.50 | 29387.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1174.19 | 2469.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 2000.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6864.51 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6218.11 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9706.84 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 4001.60 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6956.01 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5244.29 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 4001.60 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4138.26 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5482.11 |
September | 0.00 | 01-SEP-00:05 | 0.00 | 4001.60 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6061.00 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2000.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8990.29 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6988.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 2000.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 4001.60 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9706.84 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.549316E+11 | 48362.38 | 10-JAN-16:00 | 0.577886E+09 | 22215.06 | 03-JAN-06:10 |
February | 0.473762E+11 | 43542.54 | 14-FEB-15:00 | 0.179387E+09 | 7472.98 | 28-FEB-06:10 |
March | 0.521399E+11 | 41375.59 | 11-MAR-16:00 | 0.329676E+09 | 12118.49 | 30-MAR-05:10 |
April | 0.482298E+11 | 41105.35 | 21-APR-14:00 | 18823853.47 | 8161.98 | 01-APR-05:10 |
May | 0.481982E+11 | 39592.31 | 09-MAY-08:20 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.493680E+11 | 42168.85 | 29-JUN-13:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.522813E+11 | 45415.21 | 31-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.561661E+11 | 46789.57 | 17-AUG-14:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.516492E+11 | 50645.70 | 30-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.547846E+11 | 52181.60 | 17-OCT-14:39 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.519659E+11 | 48360.36 | 28-NOV-16:00 | 24354408.87 | 5167.25 | 27-NOV-06:10 |
December | 0.557301E+11 | 48978.86 | 05-DEC-16:40 | 0.242562E+09 | 8173.79 | 15-DEC-06:10 |
Annual Sum or Average | 0.622821E+12 | 0.137269E+10 | ||||
Minimum of Months | 0.473762E+11 | 39592.31 | 0.00 | 0.00 | ||
Maximum of Months | 0.561661E+11 | 52181.60 | 0.577886E+09 | 22215.06 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.295724E+11 | 0.936091E+10 | 0.113456E+11 | 0.00 | 0.243535E+10 | 0.00 | 0.00 | 0.107295E+09 | 0.00 | 0.00 | 0.00 | 0.211010E+10 | 0.00 |
February | 0.248440E+11 | 0.793049E+10 | 0.104160E+11 | 0.00 | 0.223457E+10 | 0.00 | 0.00 | 33548591.35 | 0.00 | 0.00 | 0.00 | 0.191767E+10 | 0.00 |
March | 0.270938E+11 | 0.801952E+10 | 0.121559E+11 | 0.00 | 0.262685E+10 | 0.00 | 0.00 | 88129604.05 | 0.00 | 0.00 | 0.00 | 0.215562E+10 | 0.00 |
April | 0.247905E+11 | 0.701454E+10 | 0.113034E+11 | 0.00 | 0.247044E+10 | 0.00 | 0.00 | 0.613023E+09 | 0.00 | 0.00 | 0.00 | 0.203796E+10 | 0.00 |
May | 0.245224E+11 | 0.663046E+10 | 0.117471E+11 | 0.00 | 0.259089E+10 | 0.00 | 0.00 | 0.616566E+09 | 0.00 | 0.00 | 0.00 | 0.209085E+10 | 0.00 |
June | 0.244041E+11 | 0.612485E+10 | 0.117048E+11 | 0.00 | 0.273665E+10 | 0.00 | 0.00 | 0.237028E+10 | 0.00 | 0.00 | 0.00 | 0.202728E+10 | 0.00 |
July | 0.242718E+11 | 0.642977E+10 | 0.113456E+11 | 0.00 | 0.295278E+10 | 0.00 | 0.00 | 0.524428E+10 | 0.00 | 0.00 | 0.00 | 0.203706E+10 | 0.00 |
August | 0.263968E+11 | 0.695059E+10 | 0.121485E+11 | 0.00 | 0.307419E+10 | 0.00 | 0.00 | 0.551025E+10 | 0.00 | 0.00 | 0.00 | 0.208571E+10 | 0.00 |
September | 0.257050E+11 | 0.744211E+10 | 0.112960E+11 | 0.00 | 0.275414E+10 | 0.00 | 0.00 | 0.245252E+10 | 0.00 | 0.00 | 0.00 | 0.199947E+10 | 0.00 |
October | 0.279443E+11 | 0.846385E+10 | 0.113530E+11 | 0.00 | 0.270570E+10 | 0.00 | 0.00 | 0.225740E+10 | 0.00 | 0.00 | 0.00 | 0.206044E+10 | 0.00 |
November | 0.277567E+11 | 0.886734E+10 | 0.109019E+11 | 0.00 | 0.232932E+10 | 0.00 | 0.00 | 0.101714E+09 | 0.00 | 0.00 | 0.00 | 0.200900E+10 | 0.00 |
December | 0.301766E+11 | 0.954535E+10 | 0.113456E+11 | 0.00 | 0.242945E+10 | 0.00 | 0.00 | 0.134040E+09 | 0.00 | 0.00 | 0.00 | 0.209901E+10 | 0.00 |
Annual Sum or Average | 0.317478E+12 | 0.927798E+11 | 0.137063E+12 | 0.00 | 0.313404E+11 | 0.00 | 0.00 | 0.195290E+11 | 0.00 | 0.00 | 0.00 | 0.246302E+11 | 0.00 |
Minimum of Months | 0.242718E+11 | 0.612485E+10 | 0.104160E+11 | 0.00 | 0.223457E+10 | 0.00 | 0.00 | 33548591.35 | 0.00 | 0.00 | 0.00 | 0.191767E+10 | 0.00 |
Maximum of Months | 0.301766E+11 | 0.954535E+10 | 0.121559E+11 | 0.00 | 0.307419E+10 | 0.00 | 0.00 | 0.551025E+10 | 0.00 | 0.00 | 0.00 | 0.215562E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.577886E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.179387E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.329676E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 18823853.47 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 24354408.87 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.242562E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.137269E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.577886E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 30696.62 | 02-JAN-15:00 | 6986.42 | 01-JAN-06:10 | 10054.01 | 02-JAN-08:09 | 0.00 | 2449.92 | 02-JAN-08:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 29279.39 | 14-FEB-15:00 | 6986.42 | 01-FEB-06:10 | 10054.01 | 01-FEB-08:09 | 0.00 | 2449.92 | 01-FEB-14:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 27270.96 | 01-MAR-16:00 | 6986.42 | 01-MAR-06:10 | 10054.01 | 01-MAR-08:09 | 0.00 | 2449.92 | 07-MAR-07:19 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 26852.88 | 21-APR-14:00 | 6986.42 | 01-APR-05:10 | 10054.01 | 01-APR-07:10 | 0.00 | 2449.92 | 01-APR-09:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 25435.64 | 09-MAY-08:09 | 6986.42 | 01-MAY-18:30 | 10054.01 | 01-MAY-07:10 | 0.00 | 2449.92 | 03-MAY-11:20 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 24018.41 | 16-JUN-08:09 | 6986.42 | 01-JUN-18:49 | 10054.01 | 01-JUN-07:10 | 0.00 | 3026.25 | 26-JUN-10:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 24769.96 | 18-JUL-07:10 | 6986.42 | 01-JUL-18:00 | 10054.01 | 01-JUL-07:10 | 0.00 | 4755.22 | 19-JUL-10:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 24769.96 | 05-AUG-07:10 | 6986.42 | 01-AUG-18:49 | 10054.01 | 01-AUG-07:10 | 0.00 | 4755.22 | 17-AUG-14:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 27862.15 | 21-SEP-08:09 | 6986.42 | 01-SEP-05:10 | 10054.01 | 01-SEP-07:10 | 0.00 | 4874.68 | 29-SEP-12:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 29279.39 | 17-OCT-14:00 | 6986.42 | 01-OCT-05:10 | 10054.01 | 02-OCT-07:10 | 0.00 | 4878.62 | 16-OCT-12:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 30696.62 | 06-NOV-15:50 | 6986.42 | 01-NOV-05:10 | 10054.01 | 01-NOV-07:10 | 0.00 | 2449.92 | 06-NOV-14:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 30696.62 | 01-DEC-15:00 | 6986.42 | 01-DEC-06:10 | 10054.01 | 01-DEC-08:09 | 0.00 | 2449.92 | 01-DEC-12:39 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 24018.41 | 6986.42 | 10054.01 | 0.00 | 2449.92 | 0.00 | 0.00 | |||||
Maximum of Months | 30696.62 | 6986.42 | 10054.01 | 0.00 | 4878.62 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 1184.18 | 14-JAN-14:00 | 0.00 | 0.00 | 0.00 | 1797.12 | 25-JAN-12:39 | 0.00 |
February | 1059.25 | 01-FEB-11:00 | 0.00 | 0.00 | 0.00 | 1797.11 | 09-FEB-12:30 | 0.00 |
March | 2682.04 | 23-MAR-13:00 | 0.00 | 0.00 | 0.00 | 1795.29 | 03-MAR-12:30 | 0.00 |
April | 6868.24 | 30-APR-11:50 | 0.00 | 0.00 | 0.00 | 1789.26 | 01-APR-11:09 | 0.00 |
May | 6710.20 | 28-MAY-13:00 | 0.00 | 0.00 | 0.00 | 1781.84 | 01-MAY-11:09 | 0.00 |
June | 9283.95 | 29-JUN-17:49 | 0.00 | 0.00 | 0.00 | 1773.27 | 01-JUN-11:09 | 0.00 |
July | 9723.66 | 31-JUL-14:20 | 0.00 | 0.00 | 0.00 | 1767.38 | 01-JUL-11:09 | 0.00 |
August | 9902.23 | 17-AUG-14:00 | 0.00 | 0.00 | 0.00 | 1766.58 | 31-AUG-11:30 | 0.00 |
September | 10891.37 | 29-SEP-12:00 | 0.00 | 0.00 | 0.00 | 1771.34 | 30-SEP-11:09 | 0.00 |
October | 11165.02 | 16-OCT-11:00 | 0.00 | 0.00 | 0.00 | 1780.02 | 31-OCT-11:00 | 0.00 |
November | 1953.73 | 18-NOV-13:00 | 0.00 | 0.00 | 0.00 | 1788.16 | 30-NOV-12:39 | 0.00 |
December | 1370.34 | 05-DEC-14:00 | 0.00 | 0.00 | 0.00 | 1794.15 | 28-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1059.25 | 0.00 | 0.00 | 0.00 | 1766.58 | 0.00 | ||
Maximum of Months | 11165.02 | 0.00 | 0.00 | 0.00 | 1797.12 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 48362.38 | 10-JAN-16:00 | 27270.96 | 10054.01 | 6986.42 | 0.00 | 2449.92 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 43542.54 | 14-FEB-15:00 | 29279.39 | 10054.01 | 0.00 | 0.00 | 2449.92 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 41375.59 | 11-MAR-16:00 | 27270.96 | 10054.01 | 0.00 | 0.00 | 2449.92 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 41105.35 | 21-APR-14:00 | 26852.88 | 10054.01 | 0.00 | 0.00 | 2449.92 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 39592.31 | 09-MAY-08:20 | 25435.64 | 10054.01 | 0.00 | 0.00 | 2449.92 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 42168.85 | 29-JUN-13:00 | 20582.62 | 10054.01 | 0.00 | 0.00 | 2910.98 | 0.00 | 0.00 | 6918.15 | 0.00 |
July | 45415.21 | 31-JUL-14:00 | 20582.62 | 10054.01 | 0.00 | 0.00 | 3602.57 | 0.00 | 0.00 | 9443.91 | 0.00 |
August | 46789.57 | 17-AUG-14:30 | 20582.62 | 10054.01 | 0.00 | 0.00 | 4755.22 | 0.00 | 0.00 | 9665.25 | 0.00 |
September | 50645.70 | 30-SEP-14:00 | 24426.37 | 10054.01 | 0.00 | 0.00 | 4755.22 | 0.00 | 0.00 | 9671.88 | 0.00 |
October | 52181.60 | 17-OCT-14:39 | 27862.15 | 10054.01 | 0.00 | 0.00 | 4755.22 | 0.00 | 0.00 | 7768.69 | 0.00 |
November | 48360.36 | 28-NOV-16:00 | 27270.96 | 10054.01 | 6986.42 | 0.00 | 2449.92 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 48978.86 | 05-DEC-16:40 | 27270.96 | 10054.01 | 6986.42 | 0.00 | 2449.92 | 0.00 | 0.00 | 617.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 39592.31 | 20582.62 | 10054.01 | 0.00 | 0.00 | 2449.92 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 52181.60 | 29279.39 | 10054.01 | 6986.42 | 0.00 | 4755.22 | 0.00 | 0.00 | 9671.88 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 22215.06 | 03-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 7472.98 | 28-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 12118.49 | 30-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 8161.98 | 01-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 5167.25 | 27-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 8173.79 | 15-DEC-06:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 22215.06 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 20.31 | 2.00 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
February | 1.00 | 20.47 | 1.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
March | 0.83 | 20.46 | 0.83 | 20.46 | 0.17 | 20.83 | 0.00 | 20.83 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.49 | 0.00 | 24.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 24.50 | 0.00 | 24.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 24.52 | 1.17 | 24.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 24.58 | 1.00 | 24.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 24.54 | 0.83 | 24.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 24.50 | 2.00 | 24.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 24.51 | 0.67 | 24.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.00 | 24.47 |
December | 1.00 | 20.44 | 1.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Annual Sum or Average | 4.83 | 20.40 | 4.83 | 20.40 | 62.50 | 23.97 | 5.67 | 24.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 0.00 | 20.31 |
Maximum of Months | 2.00 | 20.47 | 2.00 | 20.47 | 16.00 | 24.58 | 2.00 | 24.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.33 | 0.00 | 27.33 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.00 | 27.27 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.34 | 0.00 | 27.34 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.36 | 0.00 | 27.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.40 | 0.00 | 27.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.33 | 0.00 | 27.33 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.47 | 0.00 | 27.47 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 14.99 | 0.00 | 14.99 | 13.00 | 26.64 | 0.00 | 26.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 14.99 | 0.00 | 14.99 | 4.67 | 27.47 | 0.00 | 27.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 280.67 | 23.07 | 40.33 | 22.83 | 40.33 | 22.65 |
February | 263.67 | 23.18 | 18.17 | 23.05 | 18.17 | 22.94 |
March | 293.00 | 23.12 | 36.17 | 23.02 | 22.00 | 22.90 |
April | 119.00 | 23.46 | 101.33 | 23.63 | 2.33 | 23.61 |
May | 86.33 | 23.61 | 122.33 | 23.78 | 0.00 | 23.78 |
June | 21.33 | 23.82 | 222.67 | 23.90 | 1.00 | 23.90 |
July | 9.50 | 23.56 | 273.17 | 23.90 | 7.17 | 23.90 |
August | 17.67 | 23.76 | 296.67 | 23.90 | 15.33 | 23.90 |
September | 19.67 | 23.82 | 232.33 | 23.90 | 9.00 | 23.90 |
October | 88.83 | 23.69 | 137.50 | 23.82 | 11.50 | 23.82 |
November | 232.50 | 23.38 | 13.33 | 23.32 | 7.83 | 23.25 |
December | 290.50 | 23.29 | 28.83 | 23.10 | 27.50 | 22.95 |
Annual Sum or Average | 1722.67 | 23.29 | 1522.83 | 23.48 | 162.17 | 23.40 |
Minimum of Months | 9.50 | 23.07 | 13.33 | 22.83 | 0.00 | 22.65 |
Maximum of Months | 293.00 | 23.82 | 296.67 | 23.90 | 40.33 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 232.17 | 21.44 | 123.17 | 21.39 | 78.83 | 20.92 |
February | 219.50 | 21.69 | 90.00 | 21.66 | 58.17 | 21.31 |
March | 257.83 | 21.75 | 111.33 | 21.89 | 64.00 | 21.54 |
April | 131.50 | 24.40 | 212.00 | 25.41 | 62.17 | 25.51 |
May | 118.00 | 25.11 | 241.00 | 25.81 | 68.00 | 25.95 |
June | 174.00 | 26.47 | 294.00 | 26.42 | 161.67 | 26.49 |
July | 240.83 | 26.70 | 300.00 | 26.62 | 240.83 | 26.65 |
August | 270.00 | 26.66 | 324.00 | 26.59 | 270.00 | 26.61 |
September | 199.33 | 26.57 | 285.50 | 26.46 | 195.17 | 26.51 |
October | 128.50 | 25.52 | 249.17 | 26.14 | 90.83 | 26.23 |
November | 146.83 | 22.43 | 123.50 | 23.42 | 23.17 | 23.14 |
December | 230.50 | 22.17 | 79.83 | 21.96 | 54.83 | 21.56 |
Annual Sum or Average | 2349.00 | 24.15 | 2433.50 | 24.84 | 1367.67 | 24.90 |
Minimum of Months | 118.00 | 21.44 | 79.83 | 21.39 | 23.17 | 20.92 |
Maximum of Months | 270.00 | 26.70 | 324.00 | 26.62 | 270.00 | 26.65 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 19.72 | 181.17 | 19.19 | 181.17 | 18.95 |
February | 276.00 | 20.25 | 141.67 | 19.76 | 141.67 | 19.51 |
March | 305.00 | 20.23 | 153.67 | 19.89 | 138.50 | 19.59 |
April | 154.67 | 22.97 | 144.00 | 24.19 | 35.17 | 24.26 |
May | 126.33 | 24.94 | 214.67 | 25.77 | 55.17 | 26.06 |
June | 184.50 | 28.07 | 291.50 | 27.62 | 173.17 | 27.82 |
July | 288.50 | 28.79 | 300.00 | 28.74 | 288.50 | 28.76 |
August | 307.00 | 28.71 | 324.00 | 28.64 | 307.00 | 28.66 |
September | 214.83 | 28.31 | 296.00 | 27.91 | 213.50 | 28.04 |
October | 156.00 | 27.06 | 246.67 | 27.21 | 116.00 | 27.53 |
November | 273.17 | 21.84 | 63.33 | 21.42 | 60.50 | 21.11 |
December | 300.00 | 20.51 | 156.83 | 20.04 | 156.83 | 19.81 |
Annual Sum or Average | 2886.00 | 23.94 | 2513.50 | 24.51 | 1867.17 | 24.62 |
Minimum of Months | 126.33 | 19.72 | 63.33 | 19.19 | 35.17 | 18.95 |
Maximum of Months | 307.00 | 28.79 | 324.00 | 28.74 | 307.00 | 28.76 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.480244E+09 | 0.107295E+09 | 49.75 | 0.460755E+09 | 19488623.98 | 0.00 | 0.58 | 14-JAN-15:00 | 0.00 | 01-JAN-00:10 | 5432.04 | 24-JAN-15:30 | 5275.27 | 24-JAN-15:30 | 801.45 | 17-JAN-14:00 | 1184.18 | 14-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.149761E+09 | 33548591.35 | 26.17 | 0.147985E+09 | 1775822.12 | 0.00 | 0.54 | 03-FEB-15:00 | 0.00 | 01-FEB-00:10 | 4703.14 | 03-FEB-15:00 | 4703.14 | 03-FEB-15:00 | 301.21 | 01-FEB-13:40 | 1059.25 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 |
March | 0.370291E+09 | 81647500.94 | 37.56 | 0.318533E+09 | 51757854.65 | 0.00 | 0.93 | 22-MAR-17:20 | 0.00 | 01-MAR-00:10 | 10265.06 | 23-MAR-17:20 | 8381.35 | 22-MAR-17:20 | 2027.05 | 23-MAR-17:20 | 2057.19 | 23-MAR-17:20 | 0.00 | 01-MAR-00:10 |
April | 0.151628E+10 | 0.330875E+09 | 136.36 | 0.125707E+10 | 0.259213E+09 | 0.00 | 1.00 | 08-APR-17:15 | 0.00 | 01-APR-00:10 | 19595.00 | 26-APR-17:11 | 14627.57 | 26-APR-17:10 | 7582.39 | 30-APR-23:03 | 4129.33 | 26-APR-17:11 | 0.00 | 01-APR-00:10 |
May | 0.173487E+10 | 0.378745E+09 | 152.06 | 0.148008E+10 | 0.254791E+09 | 0.00 | 1.00 | 01-MAY-17:10 | 0.00 | 01-MAY-00:05 | 19379.13 | 02-MAY-17:15 | 16238.42 | 26-MAY-17:15 | 7074.10 | 05-MAY-17:55 | 4089.75 | 02-MAY-17:15 | 0.00 | 01-MAY-00:05 |
June | 0.478645E+10 | 0.101260E+10 | 250.82 | 0.370031E+10 | 0.108614E+10 | 0.00 | 1.00 | 01-JUN-17:10 | 0.00 | 01-JUN-00:10 | 20862.12 | 27-JUN-17:10 | 16504.08 | 24-JUN-17:10 | 8797.99 | 27-JUN-21:05 | 4345.46 | 27-JUN-17:10 | 0.00 | 01-JUN-00:10 |
July | 0.854825E+10 | 0.177515E+10 | 316.84 | 0.622787E+10 | 0.232038E+10 | 0.00 | 1.00 | 01-JUL-05:35 | 0.00 | 01-JUL-00:05 | 21575.06 | 28-JUL-17:10 | 17228.79 | 08-JUL-17:10 | 10429.42 | 29-JUL-19:05 | 4455.17 | 28-JUL-17:10 | 0.00 | 01-JUL-00:05 |
August | 0.929258E+10 | 0.191946E+10 | 341.48 | 0.667460E+10 | 0.261799E+10 | 0.00 | 1.00 | 01-AUG-00:25 | 0.00 | 01-AUG-00:10 | 21282.02 | 18-AUG-17:10 | 17180.13 | 19-AUG-17:08 | 10628.38 | 07-AUG-01:05 | 4411.10 | 18-AUG-17:10 | 0.00 | 01-AUG-00:10 |
September | 0.502373E+10 | 0.108360E+10 | 260.00 | 0.384229E+10 | 0.118144E+10 | 0.00 | 1.00 | 01-SEP-17:10 | 0.00 | 01-SEP-00:05 | 21322.62 | 21-SEP-22:55 | 18436.31 | 30-SEP-01:45 | 9782.87 | 22-SEP-18:45 | 4417.29 | 21-SEP-22:55 | 0.00 | 01-SEP-00:05 |
October | 0.472514E+10 | 0.103100E+10 | 245.64 | 0.395459E+10 | 0.770545E+09 | 0.00 | 1.00 | 01-OCT-23:01 | 0.00 | 01-OCT-00:10 | 21248.51 | 04-OCT-17:15 | 18492.77 | 16-OCT-17:45 | 10391.72 | 05-OCT-17:15 | 4405.97 | 04-OCT-17:15 | 0.00 | 01-OCT-00:10 |
November | 0.442620E+09 | 98781011.25 | 57.83 | 0.430906E+09 | 11713868.00 | 0.00 | 0.61 | 18-NOV-14:10 | 0.00 | 01-NOV-00:10 | 5817.46 | 18-NOV-14:30 | 5817.46 | 18-NOV-14:30 | 819.20 | 10-NOV-13:10 | 1285.43 | 18-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.598324E+09 | 0.133979E+09 | 82.00 | 0.594450E+09 | 3874449.56 | 0.00 | 0.63 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 | 5802.11 | 05-DEC-15:00 | 5802.11 | 05-DEC-15:00 | 524.99 | 07-DEC-14:00 | 1268.60 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.376685E+11 | 0.798668E+10 | 1956.50 | 0.290894E+11 | 0.857911E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.149761E+09 | 33548591.35 | 26.17 | 0.147985E+09 | 1775822.12 | 0.00 | 0.54 | 0.00 | 4703.14 | 4703.14 | 301.21 | 1059.25 | 0.00 | |||||||
Maximum of Months | 0.929258E+10 | 0.191946E+10 | 341.48 | 0.667460E+10 | 0.261799E+10 | 0.00 | 1.00 | 0.00 | 21575.06 | 18492.77 | 10628.38 | 4455.17 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 25590330.21 | 6482103.11 | 2.17 | 18383500.52 | 7206829.69 | 0.00 | 0.18 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 | 5077.47 | 23-MAR-14:00 | 3728.99 | 23-MAR-14:00 | 1348.48 | 23-MAR-14:00 | 1278.24 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.115073E+10 | 0.282148E+09 | 48.36 | 0.941282E+09 | 0.209451E+09 | 0.00 | 1.00 | 09-APR-13:35 | 0.00 | 01-APR-00:10 | 61765.06 | 30-APR-13:05 | 56023.27 | 30-APR-10:15 | 10941.86 | 30-APR-17:05 | 13834.18 | 30-APR-11:11 | 0.00 | 01-APR-00:10 |
May | 0.959499E+09 | 0.237821E+09 | 53.25 | 0.792106E+09 | 0.167393E+09 | 0.00 | 1.00 | 21-MAY-12:55 | 0.00 | 01-MAY-00:05 | 60686.81 | 28-MAY-13:55 | 49313.62 | 28-MAY-12:25 | 13470.32 | 28-MAY-13:55 | 13420.40 | 28-MAY-13:55 | 0.00 | 01-MAY-00:05 |
June | 0.569260E+10 | 0.135768E+10 | 149.77 | 0.413792E+10 | 0.155468E+10 | 0.00 | 1.00 | 04-JUN-10:15 | 0.00 | 01-JUN-00:10 | 65220.86 | 29-JUN-17:45 | 49958.94 | 25-JUN-12:52 | 25621.42 | 27-JUN-17:12 | 14238.93 | 29-JUN-17:45 | 0.00 | 01-JUN-00:10 |
July | 0.149133E+11 | 0.346913E+10 | 243.95 | 0.103179E+11 | 0.459542E+10 | 0.00 | 1.00 | 01-JUL-17:10 | 0.00 | 01-JUL-00:05 | 67430.78 | 31-JUL-17:12 | 52580.80 | 15-JUL-17:06 | 31571.48 | 28-JUL-17:12 | 14836.10 | 23-JUL-10:45 | 0.00 | 01-JUL-00:05 |
August | 0.154450E+11 | 0.359078E+10 | 244.58 | 0.103634E+11 | 0.508154E+10 | 0.00 | 1.00 | 01-AUG-17:11 | 0.00 | 01-AUG-00:10 | 67254.45 | 13-AUG-10:05 | 49797.12 | 27-AUG-11:02 | 28868.61 | 18-AUG-17:12 | 14898.59 | 06-AUG-12:53 | 0.00 | 01-AUG-00:10 |
September | 0.549952E+10 | 0.136892E+10 | 146.40 | 0.430823E+10 | 0.119129E+10 | 0.00 | 1.00 | 03-SEP-10:25 | 0.00 | 01-SEP-00:05 | 64969.74 | 10-SEP-11:05 | 52575.50 | 30-SEP-17:15 | 23904.61 | 24-SEP-11:25 | 14196.66 | 10-SEP-11:05 | 0.00 | 01-SEP-00:05 |
October | 0.477521E+10 | 0.122640E+10 | 124.57 | 0.420156E+10 | 0.573647E+09 | 0.00 | 1.00 | 01-OCT-10:35 | 0.00 | 01-OCT-00:10 | 67949.67 | 01-OCT-11:53 | 57030.74 | 15-OCT-17:05 | 27175.10 | 01-OCT-16:02 | 15031.94 | 01-OCT-11:53 | 0.00 | 01-OCT-00:10 |
November | 10955758.94 | 2933331.41 | 2.00 | 10955758.94 | 0.00 | 0.00 | 0.10 | 18-NOV-14:00 | 0.00 | 01-NOV-00:10 | 2497.47 | 18-NOV-14:00 | 2497.47 | 18-NOV-14:00 | 0.00 | 18-NOV-14:00 | 668.30 | 18-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 228744.28 | 61045.25 | 0.17 | 228744.28 | 0.00 | 0.00 | 0.02 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 | 381.24 | 05-DEC-15:00 | 381.24 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 | 101.74 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.484726E+11 | 0.115424E+11 | 1015.22 | 0.350920E+11 | 0.133806E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.154450E+11 | 0.359078E+10 | 244.58 | 0.103634E+11 | 0.508154E+10 | 0.00 | 1.00 | 0.00 | 67949.67 | 57030.74 | 31571.48 | 15031.94 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.89 | 31.24 | 30.65 | 82.06 | 109.60 | 0.00 | 0.00 | 0.00 |
February | 73.66 | 33.97 | 39.69 | 90.70 | 101.66 | 0.00 | 0.00 | 0.00 |
March | 84.39 | 37.29 | 47.10 | 106.02 | 105.83 | 0.00 | 0.00 | 0.00 |
April | 116.16 | 60.32 | 55.84 | 162.71 | 95.16 | 0.00 | 0.00 | 0.00 |
May | 114.15 | 52.55 | 61.60 | 151.56 | 89.05 | 0.00 | 0.00 | 0.00 |
June | 121.18 | 60.56 | 60.62 | 172.68 | 69.94 | 0.00 | 0.00 | 0.00 |
July | 128.29 | 68.62 | 59.67 | 195.16 | 62.90 | 0.00 | 0.00 | 0.00 |
August | 120.17 | 65.02 | 55.16 | 186.42 | 65.74 | 0.00 | 0.00 | 0.00 |
September | 102.90 | 54.96 | 47.94 | 153.09 | 75.91 | 0.00 | 0.00 | 0.00 |
October | 78.80 | 43.04 | 35.76 | 121.31 | 84.46 | 0.00 | 0.00 | 0.00 |
November | 71.10 | 37.14 | 33.95 | 93.78 | 108.75 | 0.00 | 0.00 | 0.00 |
December | 62.73 | 33.58 | 29.15 | 83.94 | 115.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.70 | 48.25 | 46.45 | 133.50 | 90.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 61.89 | 31.24 | 29.15 | 82.06 | 62.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.29 | 68.62 | 61.60 | 195.16 | 115.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.89 | 31.24 | 30.65 | 82.06 | 109.60 | 0.00 | 0.00 | 0.00 |
February | 73.66 | 33.97 | 39.69 | 90.70 | 101.66 | 0.00 | 0.00 | 0.00 |
March | 84.39 | 37.29 | 47.10 | 106.02 | 105.83 | 0.00 | 0.00 | 0.00 |
April | 116.16 | 60.32 | 55.84 | 162.71 | 95.16 | 0.00 | 0.00 | 0.00 |
May | 114.15 | 52.55 | 61.60 | 151.56 | 89.05 | 0.00 | 0.00 | 0.00 |
June | 121.18 | 60.56 | 60.62 | 172.68 | 69.94 | 0.00 | 0.00 | 0.00 |
July | 128.29 | 68.62 | 59.67 | 195.16 | 62.90 | 0.00 | 0.00 | 0.00 |
August | 120.17 | 65.02 | 55.16 | 186.42 | 65.74 | 0.00 | 0.00 | 0.00 |
September | 102.90 | 54.96 | 47.94 | 153.09 | 75.91 | 0.00 | 0.00 | 0.00 |
October | 78.80 | 43.04 | 35.76 | 121.31 | 84.46 | 0.00 | 0.00 | 0.00 |
November | 71.10 | 37.14 | 33.95 | 93.78 | 108.75 | 0.00 | 0.00 | 0.00 |
December | 62.73 | 33.58 | 29.15 | 83.94 | 115.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.70 | 48.25 | 46.45 | 133.50 | 90.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 61.89 | 31.24 | 29.15 | 82.06 | 62.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.29 | 68.62 | 61.60 | 195.16 | 115.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 0.00 | 14.04 | 7.90 | 66.61 | 0.00 | 0.00 | 0.00 |
February | 17.63 | 0.00 | 17.63 | 8.73 | 62.17 | 0.00 | 0.00 | 0.00 |
March | 21.60 | 0.00 | 21.60 | 13.36 | 64.37 | 0.00 | 0.00 | 0.00 |
April | 24.96 | 0.16 | 24.80 | 16.76 | 57.25 | 0.00 | 0.00 | 0.00 |
May | 30.17 | 1.64 | 28.52 | 20.95 | 50.35 | 0.00 | 0.00 | 0.00 |
June | 31.94 | 3.19 | 28.75 | 28.46 | 39.33 | 0.00 | 0.00 | 0.00 |
July | 30.25 | 2.60 | 27.65 | 30.11 | 35.68 | 0.00 | 0.00 | 0.00 |
August | 25.19 | 0.63 | 24.56 | 24.28 | 38.19 | 0.00 | 0.00 | 0.00 |
September | 21.21 | 0.01 | 21.20 | 18.41 | 46.46 | 0.00 | 0.00 | 0.00 |
October | 16.82 | 0.00 | 16.82 | 17.15 | 51.07 | 0.00 | 0.00 | 0.00 |
November | 15.23 | 0.00 | 15.23 | 7.83 | 66.60 | 0.00 | 0.00 | 0.00 |
December | 13.07 | 0.00 | 13.07 | 6.57 | 70.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21.86 | 0.69 | 21.17 | 16.76 | 53.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.07 | 0.00 | 13.07 | 6.57 | 35.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 31.94 | 3.19 | 28.75 | 30.11 | 70.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 0.00 | 14.04 | 7.90 | 66.61 | 0.00 | 0.00 | 0.00 |
February | 17.62 | 0.00 | 17.62 | 8.73 | 62.17 | 0.00 | 0.00 | 0.00 |
March | 21.60 | 0.00 | 21.60 | 13.35 | 64.37 | 0.00 | 0.00 | 0.00 |
April | 24.96 | 0.16 | 24.80 | 16.76 | 57.25 | 0.00 | 0.00 | 0.00 |
May | 30.17 | 1.64 | 28.52 | 20.95 | 50.35 | 0.00 | 0.00 | 0.00 |
June | 31.94 | 3.19 | 28.75 | 28.46 | 39.33 | 0.00 | 0.00 | 0.00 |
July | 30.25 | 2.60 | 27.65 | 30.11 | 35.68 | 0.00 | 0.00 | 0.00 |
August | 25.19 | 0.63 | 24.56 | 24.28 | 38.19 | 0.00 | 0.00 | 0.00 |
September | 21.21 | 0.01 | 21.20 | 18.41 | 46.46 | 0.00 | 0.00 | 0.00 |
October | 16.82 | 0.00 | 16.82 | 17.15 | 51.07 | 0.00 | 0.00 | 0.00 |
November | 15.23 | 0.00 | 15.23 | 7.83 | 66.60 | 0.00 | 0.00 | 0.00 |
December | 13.07 | 0.00 | 13.07 | 6.57 | 70.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21.86 | 0.69 | 21.17 | 16.76 | 53.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.07 | 0.00 | 13.07 | 6.57 | 35.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 31.94 | 3.19 | 28.75 | 30.11 | 70.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.38 | 25.34 | 13.04 | 58.42 | 56.62 | 15.67 | 0.00 | 0.00 |
February | 43.62 | 24.56 | 19.07 | 63.30 | 50.78 | 5.00 | 0.00 | 0.00 |
March | 56.38 | 31.88 | 24.50 | 86.70 | 50.89 | 23.50 | 0.00 | 0.00 |
April | 84.22 | 60.78 | 23.43 | 134.48 | 49.12 | 0.00 | 0.00 | 0.00 |
May | 84.00 | 53.46 | 30.53 | 130.91 | 46.03 | 0.00 | 0.00 | 0.00 |
June | 89.05 | 60.75 | 28.29 | 143.19 | 38.60 | 0.00 | 0.00 | 0.00 |
July | 97.59 | 72.62 | 24.97 | 161.42 | 38.37 | 0.00 | 0.00 | 0.00 |
August | 90.50 | 68.98 | 21.52 | 150.27 | 40.18 | 0.00 | 0.00 | 0.00 |
September | 69.80 | 49.39 | 20.42 | 112.80 | 43.96 | 0.50 | 0.00 | 0.00 |
October | 50.12 | 34.58 | 15.55 | 80.65 | 49.49 | 0.00 | 0.00 | 0.00 |
November | 40.88 | 26.24 | 14.64 | 60.34 | 57.26 | 9.67 | 0.00 | 0.00 |
December | 35.82 | 24.42 | 11.39 | 52.73 | 61.13 | 10.67 | 0.00 | 0.00 |
Annual Sum or Average | 65.14 | 44.53 | 20.61 | 103.15 | 48.53 | 65.00 | 0.00 | 0.00 |
Minimum of Months | 35.82 | 24.42 | 11.39 | 52.73 | 38.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 97.59 | 72.62 | 30.53 | 161.42 | 61.13 | 23.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.38 | 25.34 | 13.04 | 58.42 | 56.62 | 15.67 | 0.00 | 0.00 |
February | 43.62 | 24.56 | 19.07 | 63.30 | 50.78 | 5.00 | 0.00 | 0.00 |
March | 56.38 | 31.88 | 24.50 | 86.70 | 50.89 | 23.50 | 0.00 | 0.00 |
April | 84.22 | 60.78 | 23.43 | 134.48 | 49.12 | 0.00 | 0.00 | 0.00 |
May | 84.00 | 53.46 | 30.53 | 130.91 | 46.03 | 0.00 | 0.00 | 0.00 |
June | 89.05 | 60.75 | 28.29 | 143.19 | 38.60 | 0.00 | 0.00 | 0.00 |
July | 97.59 | 72.62 | 24.97 | 161.42 | 38.37 | 0.00 | 0.00 | 0.00 |
August | 90.50 | 68.98 | 21.52 | 150.27 | 40.18 | 0.00 | 0.00 | 0.00 |
September | 69.80 | 49.39 | 20.42 | 112.80 | 43.96 | 0.50 | 0.00 | 0.00 |
October | 50.12 | 34.58 | 15.55 | 80.65 | 49.49 | 0.00 | 0.00 | 0.00 |
November | 40.88 | 26.24 | 14.64 | 60.34 | 57.26 | 9.67 | 0.00 | 0.00 |
December | 35.82 | 24.42 | 11.39 | 52.73 | 61.13 | 10.67 | 0.00 | 0.00 |
Annual Sum or Average | 65.14 | 44.53 | 20.61 | 103.15 | 48.53 | 65.00 | 0.00 | 0.00 |
Minimum of Months | 35.82 | 24.42 | 11.39 | 52.73 | 38.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 97.59 | 72.62 | 30.53 | 161.42 | 61.13 | 23.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.38 | 25.34 | 13.04 | 58.42 | 56.62 | 15.67 | 0.00 | 0.00 |
February | 43.62 | 24.56 | 19.07 | 63.30 | 50.78 | 5.00 | 0.00 | 0.00 |
March | 56.38 | 31.88 | 24.50 | 86.70 | 50.89 | 23.50 | 0.00 | 0.00 |
April | 84.22 | 60.78 | 23.43 | 134.48 | 49.12 | 0.00 | 0.00 | 0.00 |
May | 84.00 | 53.46 | 30.53 | 130.91 | 46.03 | 0.00 | 0.00 | 0.00 |
June | 89.05 | 60.75 | 28.29 | 143.19 | 38.60 | 0.00 | 0.00 | 0.00 |
July | 97.59 | 72.62 | 24.97 | 161.42 | 38.37 | 0.00 | 0.00 | 0.00 |
August | 90.50 | 68.98 | 21.52 | 150.27 | 40.18 | 0.00 | 0.00 | 0.00 |
September | 69.80 | 49.39 | 20.42 | 112.80 | 43.96 | 0.50 | 0.00 | 0.00 |
October | 50.12 | 34.58 | 15.55 | 80.65 | 49.49 | 0.00 | 0.00 | 0.00 |
November | 40.88 | 26.24 | 14.64 | 60.34 | 57.26 | 9.67 | 0.00 | 0.00 |
December | 35.82 | 24.42 | 11.39 | 52.73 | 61.13 | 10.67 | 0.00 | 0.00 |
Annual Sum or Average | 65.14 | 44.53 | 20.61 | 103.15 | 48.53 | 65.00 | 0.00 | 0.00 |
Minimum of Months | 35.82 | 24.42 | 11.39 | 52.73 | 38.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 97.59 | 72.62 | 30.53 | 161.42 | 61.13 | 23.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.38 | 25.34 | 13.04 | 58.42 | 56.62 | 15.67 | 0.00 | 0.00 |
February | 43.62 | 24.56 | 19.07 | 63.30 | 50.78 | 5.00 | 0.00 | 0.00 |
March | 56.38 | 31.88 | 24.50 | 86.70 | 50.89 | 23.50 | 0.00 | 0.00 |
April | 84.22 | 60.78 | 23.43 | 134.48 | 49.12 | 0.00 | 0.00 | 0.00 |
May | 84.00 | 53.46 | 30.53 | 130.91 | 46.03 | 0.00 | 0.00 | 0.00 |
June | 89.05 | 60.75 | 28.29 | 143.19 | 38.60 | 0.00 | 0.00 | 0.00 |
July | 97.59 | 72.62 | 24.97 | 161.42 | 38.37 | 0.00 | 0.00 | 0.00 |
August | 90.50 | 68.98 | 21.52 | 150.27 | 40.18 | 0.00 | 0.00 | 0.00 |
September | 69.80 | 49.39 | 20.42 | 112.80 | 43.96 | 0.50 | 0.00 | 0.00 |
October | 50.12 | 34.58 | 15.55 | 80.65 | 49.49 | 0.00 | 0.00 | 0.00 |
November | 40.88 | 26.24 | 14.64 | 60.34 | 57.26 | 9.67 | 0.00 | 0.00 |
December | 35.82 | 24.42 | 11.39 | 52.73 | 61.13 | 10.67 | 0.00 | 0.00 |
Annual Sum or Average | 65.14 | 44.53 | 20.61 | 103.15 | 48.53 | 65.00 | 0.00 | 0.00 |
Minimum of Months | 35.82 | 24.42 | 11.39 | 52.73 | 38.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 97.59 | 72.62 | 30.53 | 161.42 | 61.13 | 23.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.38 | 25.34 | 13.04 | 58.42 | 56.62 | 15.67 | 0.00 | 0.00 |
February | 43.62 | 24.56 | 19.07 | 63.30 | 50.78 | 5.00 | 0.00 | 0.00 |
March | 56.38 | 31.88 | 24.50 | 86.70 | 50.89 | 23.50 | 0.00 | 0.00 |
April | 84.22 | 60.78 | 23.43 | 134.48 | 49.12 | 0.00 | 0.00 | 0.00 |
May | 84.00 | 53.46 | 30.53 | 130.91 | 46.03 | 0.00 | 0.00 | 0.00 |
June | 89.05 | 60.75 | 28.29 | 143.19 | 38.60 | 0.00 | 0.00 | 0.00 |
July | 97.59 | 72.62 | 24.97 | 161.42 | 38.37 | 0.00 | 0.00 | 0.00 |
August | 90.50 | 68.98 | 21.52 | 150.27 | 40.18 | 0.00 | 0.00 | 0.00 |
September | 69.80 | 49.39 | 20.42 | 112.80 | 43.96 | 0.50 | 0.00 | 0.00 |
October | 50.12 | 34.58 | 15.55 | 80.65 | 49.49 | 0.00 | 0.00 | 0.00 |
November | 40.88 | 26.24 | 14.64 | 60.34 | 57.26 | 9.67 | 0.00 | 0.00 |
December | 35.82 | 24.42 | 11.39 | 52.73 | 61.13 | 10.67 | 0.00 | 0.00 |
Annual Sum or Average | 65.14 | 44.53 | 20.61 | 103.15 | 48.53 | 65.00 | 0.00 | 0.00 |
Minimum of Months | 35.82 | 24.42 | 11.39 | 52.73 | 38.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 97.59 | 72.62 | 30.53 | 161.42 | 61.13 | 23.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.38 | 25.34 | 13.04 | 58.42 | 56.62 | 15.67 | 0.00 | 0.00 |
February | 43.62 | 24.56 | 19.07 | 63.30 | 50.78 | 5.00 | 0.00 | 0.00 |
March | 56.38 | 31.88 | 24.50 | 86.70 | 50.89 | 23.50 | 0.00 | 0.00 |
April | 84.22 | 60.78 | 23.43 | 134.48 | 49.12 | 0.00 | 0.00 | 0.00 |
May | 84.00 | 53.46 | 30.53 | 130.91 | 46.03 | 0.00 | 0.00 | 0.00 |
June | 89.05 | 60.75 | 28.29 | 143.19 | 38.60 | 0.00 | 0.00 | 0.00 |
July | 97.59 | 72.62 | 24.97 | 161.42 | 38.37 | 0.00 | 0.00 | 0.00 |
August | 90.50 | 68.98 | 21.52 | 150.27 | 40.18 | 0.00 | 0.00 | 0.00 |
September | 69.80 | 49.39 | 20.42 | 112.80 | 43.96 | 0.50 | 0.00 | 0.00 |
October | 50.12 | 34.58 | 15.55 | 80.65 | 49.49 | 0.00 | 0.00 | 0.00 |
November | 40.88 | 26.24 | 14.64 | 60.34 | 57.26 | 9.67 | 0.00 | 0.00 |
December | 35.82 | 24.42 | 11.39 | 52.73 | 61.13 | 10.67 | 0.00 | 0.00 |
Annual Sum or Average | 65.14 | 44.53 | 20.61 | 103.15 | 48.53 | 65.00 | 0.00 | 0.00 |
Minimum of Months | 35.82 | 24.42 | 11.39 | 52.73 | 38.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 97.59 | 72.62 | 30.53 | 161.42 | 61.13 | 23.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.38 | 25.34 | 13.04 | 58.42 | 56.62 | 15.67 | 0.00 | 0.00 |
February | 43.62 | 24.56 | 19.07 | 63.30 | 50.78 | 5.00 | 0.00 | 0.00 |
March | 56.38 | 31.88 | 24.50 | 86.70 | 50.89 | 23.50 | 0.00 | 0.00 |
April | 84.22 | 60.78 | 23.43 | 134.48 | 49.12 | 0.00 | 0.00 | 0.00 |
May | 84.00 | 53.46 | 30.53 | 130.91 | 46.03 | 0.00 | 0.00 | 0.00 |
June | 89.05 | 60.75 | 28.29 | 143.19 | 38.60 | 0.00 | 0.00 | 0.00 |
July | 97.59 | 72.62 | 24.97 | 161.42 | 38.37 | 0.00 | 0.00 | 0.00 |
August | 90.50 | 68.98 | 21.52 | 150.27 | 40.18 | 0.00 | 0.00 | 0.00 |
September | 69.80 | 49.39 | 20.42 | 112.80 | 43.96 | 0.50 | 0.00 | 0.00 |
October | 50.12 | 34.58 | 15.55 | 80.65 | 49.49 | 0.00 | 0.00 | 0.00 |
November | 40.88 | 26.24 | 14.64 | 60.34 | 57.26 | 9.67 | 0.00 | 0.00 |
December | 35.82 | 24.42 | 11.39 | 52.73 | 61.13 | 10.67 | 0.00 | 0.00 |
Annual Sum or Average | 65.14 | 44.53 | 20.61 | 103.15 | 48.53 | 65.00 | 0.00 | 0.00 |
Minimum of Months | 35.82 | 24.42 | 11.39 | 52.73 | 38.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 97.59 | 72.62 | 30.53 | 161.42 | 61.13 | 23.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.38 | 25.34 | 13.04 | 58.42 | 56.62 | 15.67 | 0.00 | 0.00 |
February | 43.62 | 24.56 | 19.07 | 63.30 | 50.78 | 5.00 | 0.00 | 0.00 |
March | 56.38 | 31.88 | 24.50 | 86.70 | 50.89 | 23.50 | 0.00 | 0.00 |
April | 84.22 | 60.78 | 23.43 | 134.48 | 49.12 | 0.00 | 0.00 | 0.00 |
May | 84.00 | 53.46 | 30.53 | 130.91 | 46.03 | 0.00 | 0.00 | 0.00 |
June | 89.05 | 60.75 | 28.29 | 143.19 | 38.60 | 0.00 | 0.00 | 0.00 |
July | 97.59 | 72.62 | 24.97 | 161.42 | 38.37 | 0.00 | 0.00 | 0.00 |
August | 90.50 | 68.98 | 21.52 | 150.27 | 40.18 | 0.00 | 0.00 | 0.00 |
September | 69.80 | 49.39 | 20.42 | 112.80 | 43.96 | 0.50 | 0.00 | 0.00 |
October | 50.12 | 34.58 | 15.55 | 80.65 | 49.49 | 0.00 | 0.00 | 0.00 |
November | 40.88 | 26.24 | 14.64 | 60.34 | 57.26 | 9.67 | 0.00 | 0.00 |
December | 35.82 | 24.42 | 11.39 | 52.73 | 61.13 | 10.67 | 0.00 | 0.00 |
Annual Sum or Average | 65.14 | 44.53 | 20.61 | 103.15 | 48.53 | 65.00 | 0.00 | 0.00 |
Minimum of Months | 35.82 | 24.42 | 11.39 | 52.73 | 38.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 97.59 | 72.62 | 30.53 | 161.42 | 61.13 | 23.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.38 | 25.34 | 13.04 | 58.42 | 56.62 | 15.67 | 0.00 | 0.00 |
February | 43.62 | 24.56 | 19.07 | 63.30 | 50.78 | 5.00 | 0.00 | 0.00 |
March | 56.38 | 31.88 | 24.50 | 86.70 | 50.89 | 23.50 | 0.00 | 0.00 |
April | 84.22 | 60.78 | 23.43 | 134.48 | 49.12 | 0.00 | 0.00 | 0.00 |
May | 84.00 | 53.46 | 30.53 | 130.91 | 46.03 | 0.00 | 0.00 | 0.00 |
June | 89.05 | 60.75 | 28.29 | 143.19 | 38.60 | 0.00 | 0.00 | 0.00 |
July | 97.59 | 72.62 | 24.97 | 161.42 | 38.37 | 0.00 | 0.00 | 0.00 |
August | 90.50 | 68.98 | 21.52 | 150.27 | 40.18 | 0.00 | 0.00 | 0.00 |
September | 69.80 | 49.39 | 20.42 | 112.80 | 43.96 | 0.50 | 0.00 | 0.00 |
October | 50.12 | 34.58 | 15.55 | 80.65 | 49.49 | 0.00 | 0.00 | 0.00 |
November | 40.88 | 26.24 | 14.64 | 60.34 | 57.26 | 9.67 | 0.00 | 0.00 |
December | 35.82 | 24.42 | 11.39 | 52.73 | 61.13 | 10.67 | 0.00 | 0.00 |
Annual Sum or Average | 65.14 | 44.53 | 20.61 | 103.15 | 48.53 | 65.00 | 0.00 | 0.00 |
Minimum of Months | 35.82 | 24.42 | 11.39 | 52.73 | 38.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 97.59 | 72.62 | 30.53 | 161.42 | 61.13 | 23.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.38 | 25.34 | 13.04 | 58.42 | 56.62 | 15.67 | 0.00 | 0.00 |
February | 43.62 | 24.56 | 19.07 | 63.30 | 50.78 | 5.00 | 0.00 | 0.00 |
March | 56.38 | 31.88 | 24.50 | 86.70 | 50.89 | 23.50 | 0.00 | 0.00 |
April | 84.22 | 60.78 | 23.43 | 134.48 | 49.12 | 0.00 | 0.00 | 0.00 |
May | 84.00 | 53.46 | 30.53 | 130.91 | 46.03 | 0.00 | 0.00 | 0.00 |
June | 89.05 | 60.75 | 28.29 | 143.19 | 38.60 | 0.00 | 0.00 | 0.00 |
July | 97.59 | 72.62 | 24.97 | 161.42 | 38.37 | 0.00 | 0.00 | 0.00 |
August | 90.50 | 68.98 | 21.52 | 150.27 | 40.18 | 0.00 | 0.00 | 0.00 |
September | 69.80 | 49.39 | 20.42 | 112.80 | 43.96 | 0.50 | 0.00 | 0.00 |
October | 50.12 | 34.58 | 15.55 | 80.65 | 49.49 | 0.00 | 0.00 | 0.00 |
November | 40.88 | 26.24 | 14.64 | 60.34 | 57.26 | 9.67 | 0.00 | 0.00 |
December | 35.82 | 24.42 | 11.39 | 52.73 | 61.13 | 10.67 | 0.00 | 0.00 |
Annual Sum or Average | 65.14 | 44.53 | 20.61 | 103.15 | 48.53 | 65.00 | 0.00 | 0.00 |
Minimum of Months | 35.82 | 24.42 | 11.39 | 52.73 | 38.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 97.59 | 72.62 | 30.53 | 161.42 | 61.13 | 23.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.38 | 25.34 | 13.04 | 58.42 | 56.62 | 15.67 | 0.00 | 0.00 |
February | 43.62 | 24.56 | 19.07 | 63.30 | 50.78 | 5.00 | 0.00 | 0.00 |
March | 56.38 | 31.88 | 24.50 | 86.70 | 50.89 | 23.50 | 0.00 | 0.00 |
April | 84.22 | 60.78 | 23.43 | 134.48 | 49.12 | 0.00 | 0.00 | 0.00 |
May | 84.00 | 53.46 | 30.53 | 130.91 | 46.03 | 0.00 | 0.00 | 0.00 |
June | 89.05 | 60.75 | 28.29 | 143.19 | 38.60 | 0.00 | 0.00 | 0.00 |
July | 97.59 | 72.62 | 24.97 | 161.42 | 38.37 | 0.00 | 0.00 | 0.00 |
August | 90.50 | 68.98 | 21.52 | 150.27 | 40.18 | 0.00 | 0.00 | 0.00 |
September | 69.80 | 49.39 | 20.42 | 112.80 | 43.96 | 0.50 | 0.00 | 0.00 |
October | 50.12 | 34.58 | 15.55 | 80.65 | 49.49 | 0.00 | 0.00 | 0.00 |
November | 40.88 | 26.24 | 14.64 | 60.34 | 57.26 | 9.67 | 0.00 | 0.00 |
December | 35.82 | 24.42 | 11.39 | 52.73 | 61.13 | 10.67 | 0.00 | 0.00 |
Annual Sum or Average | 65.14 | 44.53 | 20.61 | 103.15 | 48.53 | 65.00 | 0.00 | 0.00 |
Minimum of Months | 35.82 | 24.42 | 11.39 | 52.73 | 38.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 97.59 | 72.62 | 30.53 | 161.42 | 61.13 | 23.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.38 | 25.34 | 13.04 | 58.42 | 56.62 | 15.67 | 0.00 | 0.00 |
February | 43.62 | 24.56 | 19.07 | 63.30 | 50.78 | 5.00 | 0.00 | 0.00 |
March | 56.38 | 31.88 | 24.50 | 86.70 | 50.89 | 23.50 | 0.00 | 0.00 |
April | 84.22 | 60.78 | 23.43 | 134.48 | 49.12 | 0.00 | 0.00 | 0.00 |
May | 84.00 | 53.46 | 30.53 | 130.91 | 46.03 | 0.00 | 0.00 | 0.00 |
June | 89.05 | 60.75 | 28.29 | 143.19 | 38.60 | 0.00 | 0.00 | 0.00 |
July | 97.59 | 72.62 | 24.97 | 161.42 | 38.37 | 0.00 | 0.00 | 0.00 |
August | 90.50 | 68.98 | 21.52 | 150.27 | 40.18 | 0.00 | 0.00 | 0.00 |
September | 69.80 | 49.39 | 20.42 | 112.80 | 43.96 | 0.50 | 0.00 | 0.00 |
October | 50.12 | 34.58 | 15.55 | 80.65 | 49.49 | 0.00 | 0.00 | 0.00 |
November | 40.88 | 26.24 | 14.64 | 60.34 | 57.26 | 9.67 | 0.00 | 0.00 |
December | 35.82 | 24.42 | 11.39 | 52.73 | 61.13 | 10.67 | 0.00 | 0.00 |
Annual Sum or Average | 65.14 | 44.53 | 20.61 | 103.15 | 48.53 | 65.00 | 0.00 | 0.00 |
Minimum of Months | 35.82 | 24.42 | 11.39 | 52.73 | 38.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 97.59 | 72.62 | 30.53 | 161.42 | 61.13 | 23.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.38 | 25.34 | 13.04 | 58.42 | 56.62 | 15.67 | 0.00 | 0.00 |
February | 43.62 | 24.56 | 19.07 | 63.30 | 50.78 | 5.00 | 0.00 | 0.00 |
March | 56.38 | 31.88 | 24.50 | 86.70 | 50.89 | 23.50 | 0.00 | 0.00 |
April | 84.22 | 60.78 | 23.43 | 134.48 | 49.12 | 0.00 | 0.00 | 0.00 |
May | 84.00 | 53.46 | 30.53 | 130.91 | 46.03 | 0.00 | 0.00 | 0.00 |
June | 89.05 | 60.75 | 28.29 | 143.19 | 38.60 | 0.00 | 0.00 | 0.00 |
July | 97.59 | 72.62 | 24.97 | 161.42 | 38.37 | 0.00 | 0.00 | 0.00 |
August | 90.50 | 68.98 | 21.52 | 150.27 | 40.18 | 0.00 | 0.00 | 0.00 |
September | 69.80 | 49.39 | 20.42 | 112.80 | 43.96 | 0.50 | 0.00 | 0.00 |
October | 50.12 | 34.58 | 15.55 | 80.65 | 49.49 | 0.00 | 0.00 | 0.00 |
November | 40.88 | 26.24 | 14.64 | 60.34 | 57.26 | 9.67 | 0.00 | 0.00 |
December | 35.82 | 24.42 | 11.39 | 52.73 | 61.13 | 10.67 | 0.00 | 0.00 |
Annual Sum or Average | 65.14 | 44.53 | 20.61 | 103.15 | 48.53 | 65.00 | 0.00 | 0.00 |
Minimum of Months | 35.82 | 24.42 | 11.39 | 52.73 | 38.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 97.59 | 72.62 | 30.53 | 161.42 | 61.13 | 23.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.38 | 25.34 | 13.04 | 58.42 | 56.62 | 15.67 | 0.00 | 0.00 |
February | 43.62 | 24.56 | 19.07 | 63.30 | 50.78 | 5.00 | 0.00 | 0.00 |
March | 56.38 | 31.88 | 24.50 | 86.70 | 50.89 | 23.50 | 0.00 | 0.00 |
April | 84.22 | 60.78 | 23.43 | 134.48 | 49.12 | 0.00 | 0.00 | 0.00 |
May | 84.00 | 53.46 | 30.53 | 130.91 | 46.03 | 0.00 | 0.00 | 0.00 |
June | 89.05 | 60.75 | 28.29 | 143.19 | 38.60 | 0.00 | 0.00 | 0.00 |
July | 97.59 | 72.62 | 24.97 | 161.42 | 38.37 | 0.00 | 0.00 | 0.00 |
August | 90.50 | 68.98 | 21.52 | 150.27 | 40.18 | 0.00 | 0.00 | 0.00 |
September | 69.80 | 49.39 | 20.42 | 112.80 | 43.96 | 0.50 | 0.00 | 0.00 |
October | 50.12 | 34.58 | 15.55 | 80.65 | 49.49 | 0.00 | 0.00 | 0.00 |
November | 40.88 | 26.24 | 14.64 | 60.34 | 57.26 | 9.67 | 0.00 | 0.00 |
December | 35.82 | 24.42 | 11.39 | 52.73 | 61.13 | 10.67 | 0.00 | 0.00 |
Annual Sum or Average | 65.14 | 44.53 | 20.61 | 103.15 | 48.53 | 65.00 | 0.00 | 0.00 |
Minimum of Months | 35.82 | 24.42 | 11.39 | 52.73 | 38.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 97.59 | 72.62 | 30.53 | 161.42 | 61.13 | 23.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 87.47 | 69.43 | 27.67 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 95.04 | 61.86 | 14.33 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 127.81 | 62.75 | 47.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 192.71 | 63.81 | 5.17 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 186.31 | 63.10 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.96 | 55.75 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 220.64 | 60.83 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.33 | 62.83 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 156.02 | 65.08 | 1.50 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 112.01 | 71.61 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 89.56 | 72.96 | 19.17 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 79.27 | 76.40 | 15.17 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 146.28 | 65.58 | 130.00 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 79.27 | 55.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 220.64 | 76.40 | 47.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.165761E+09 | 83680416.58 | 82080089.53 | 0.219803E+09 | 0.293553E+09 |
February | 0.178200E+09 | 82187440.48 | 96012772.88 | 0.219430E+09 | 0.245946E+09 |
March | 0.226023E+09 | 99871076.63 | 0.126152E+09 | 0.283966E+09 | 0.283453E+09 |
April | 0.301091E+09 | 0.156353E+09 | 0.144738E+09 | 0.421756E+09 | 0.246667E+09 |
May | 0.305741E+09 | 0.140755E+09 | 0.164986E+09 | 0.405945E+09 | 0.238511E+09 |
June | 0.314096E+09 | 0.156963E+09 | 0.157133E+09 | 0.447576E+09 | 0.181278E+09 |
July | 0.343622E+09 | 0.183789E+09 | 0.159833E+09 | 0.522706E+09 | 0.168480E+09 |
August | 0.321876E+09 | 0.174137E+09 | 0.147739E+09 | 0.499320E+09 | 0.176078E+09 |
September | 0.266712E+09 | 0.142464E+09 | 0.124248E+09 | 0.396798E+09 | 0.196758E+09 |
October | 0.211053E+09 | 0.115266E+09 | 95786958.15 | 0.324909E+09 | 0.226227E+09 |
November | 0.184282E+09 | 96271190.46 | 88011008.02 | 0.243082E+09 | 0.281884E+09 |
December | 0.168009E+09 | 89929742.44 | 78079734.58 | 0.224814E+09 | 0.308077E+09 |
Annual Sum or Average | 0.298647E+10 | 0.152167E+10 | 0.146480E+10 | 0.421010E+10 | 0.284691E+10 |
Minimum of Months | 0.165761E+09 | 82187440.48 | 78079734.58 | 0.219430E+09 | 0.168480E+09 |
Maximum of Months | 0.343622E+09 | 0.183789E+09 | 0.164986E+09 | 0.522706E+09 | 0.308077E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.165761E+09 | 83680416.58 | 82080089.53 | 0.219803E+09 | 0.293553E+09 |
February | 0.178200E+09 | 82187440.48 | 96012772.88 | 0.219430E+09 | 0.245946E+09 |
March | 0.226023E+09 | 99871076.63 | 0.126152E+09 | 0.283966E+09 | 0.283453E+09 |
April | 0.301091E+09 | 0.156353E+09 | 0.144738E+09 | 0.421756E+09 | 0.246667E+09 |
May | 0.305741E+09 | 0.140755E+09 | 0.164986E+09 | 0.405945E+09 | 0.238511E+09 |
June | 0.314096E+09 | 0.156963E+09 | 0.157133E+09 | 0.447576E+09 | 0.181278E+09 |
July | 0.343622E+09 | 0.183789E+09 | 0.159833E+09 | 0.522706E+09 | 0.168480E+09 |
August | 0.321876E+09 | 0.174137E+09 | 0.147739E+09 | 0.499320E+09 | 0.176078E+09 |
September | 0.266712E+09 | 0.142464E+09 | 0.124248E+09 | 0.396798E+09 | 0.196758E+09 |
October | 0.211053E+09 | 0.115266E+09 | 95786958.15 | 0.324909E+09 | 0.226227E+09 |
November | 0.184282E+09 | 96271190.46 | 88011008.02 | 0.243082E+09 | 0.281884E+09 |
December | 0.168009E+09 | 89929742.44 | 78079734.58 | 0.224814E+09 | 0.308077E+09 |
Annual Sum or Average | 0.298647E+10 | 0.152167E+10 | 0.146480E+10 | 0.421010E+10 | 0.284691E+10 |
Minimum of Months | 0.165761E+09 | 82187440.48 | 78079734.58 | 0.219430E+09 | 0.168480E+09 |
Maximum of Months | 0.343622E+09 | 0.183789E+09 | 0.164986E+09 | 0.522706E+09 | 0.308077E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37608032.36 | 0.00 | 37608032.36 | 21172345.40 | 0.178409E+09 |
February | 42639569.70 | 0.00 | 42639569.70 | 21118864.97 | 0.150395E+09 |
March | 57856777.19 | 2101.94 | 57854675.25 | 35770769.30 | 0.172403E+09 |
April | 64706737.07 | 418984.49 | 64287752.58 | 43446214.15 | 0.148382E+09 |
May | 80799630.00 | 4399131.38 | 76400498.62 | 56123153.42 | 0.134871E+09 |
June | 82791055.08 | 8278631.33 | 74512423.75 | 73763725.91 | 0.101934E+09 |
July | 81014815.76 | 6963590.51 | 74051225.25 | 80636273.02 | 95573376.88 |
August | 67463903.85 | 1675986.65 | 65787917.20 | 65022251.78 | 0.102291E+09 |
September | 54982697.04 | 21958.86 | 54960738.17 | 47712794.54 | 0.120417E+09 |
October | 45054435.88 | 0.00 | 45054435.88 | 45938487.74 | 0.136785E+09 |
November | 39477619.92 | 0.00 | 39477619.92 | 20303890.05 | 0.172628E+09 |
December | 35009879.03 | 0.00 | 35009879.03 | 17607591.61 | 0.188332E+09 |
Annual Sum or Average | 0.689405E+09 | 21760385.16 | 0.667645E+09 | 0.528616E+09 | 0.170242E+10 |
Minimum of Months | 35009879.03 | 0.00 | 35009879.03 | 17607591.61 | 95573376.88 |
Maximum of Months | 82791055.08 | 8278631.33 | 76400498.62 | 80636273.02 | 0.188332E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37606988.46 | 0.00 | 37606988.46 | 21171514.27 | 0.178408E+09 |
February | 42638301.05 | 0.00 | 42638301.05 | 21117640.89 | 0.150394E+09 |
March | 57855062.38 | 2101.84 | 57852960.54 | 35768823.03 | 0.172402E+09 |
April | 64705116.38 | 418964.85 | 64286151.52 | 43444711.74 | 0.148381E+09 |
May | 80797285.91 | 4398925.19 | 76398360.72 | 56120196.79 | 0.134871E+09 |
June | 82788649.05 | 8278243.30 | 74510405.75 | 73760342.43 | 0.101934E+09 |
July | 81012680.52 | 6963264.11 | 74049416.40 | 80633441.92 | 95572878.49 |
August | 67462286.67 | 1675908.09 | 65786378.58 | 65020602.77 | 0.102291E+09 |
September | 54981291.79 | 21957.84 | 54959333.96 | 47711309.48 | 0.120416E+09 |
October | 45053230.82 | 0.00 | 45053230.82 | 45937333.39 | 0.136784E+09 |
November | 39476510.63 | 0.00 | 39476510.63 | 20302961.47 | 0.172627E+09 |
December | 35008925.79 | 0.00 | 35008925.79 | 17607075.73 | 0.188330E+09 |
Annual Sum or Average | 0.689386E+09 | 21759365.22 | 0.667627E+09 | 0.528596E+09 | 0.170241E+10 |
Minimum of Months | 35008925.79 | 0.00 | 35008925.79 | 17607075.73 | 95572878.49 |
Maximum of Months | 82788649.05 | 8278243.30 | 76398360.72 | 80633441.92 | 0.188330E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102798E+09 | 67865751.07 | 34932482.17 | 0.156467E+09 | 0.151663E+09 |
February | 0.105532E+09 | 59409335.90 | 46122598.77 | 0.153131E+09 | 0.122854E+09 |
March | 0.150998E+09 | 85379052.46 | 65618643.42 | 0.232224E+09 | 0.136309E+09 |
April | 0.218289E+09 | 0.157553E+09 | 60736272.79 | 0.348565E+09 | 0.127317E+09 |
May | 0.224976E+09 | 0.143197E+09 | 81779250.83 | 0.350634E+09 | 0.123291E+09 |
June | 0.230814E+09 | 0.157474E+09 | 73340053.71 | 0.371150E+09 | 0.100059E+09 |
July | 0.261397E+09 | 0.194511E+09 | 66886550.64 | 0.432350E+09 | 0.102759E+09 |
August | 0.242400E+09 | 0.184754E+09 | 57646466.67 | 0.402489E+09 | 0.107630E+09 |
September | 0.180928E+09 | 0.128008E+09 | 52920623.74 | 0.292374E+09 | 0.113957E+09 |
October | 0.134255E+09 | 92618348.93 | 41636441.60 | 0.216014E+09 | 0.132541E+09 |
November | 0.105970E+09 | 68010788.38 | 37959293.64 | 0.156410E+09 | 0.148405E+09 |
December | 95938622.88 | 65419550.89 | 30519071.98 | 0.141245E+09 | 0.163736E+09 |
Annual Sum or Average | 0.205430E+10 | 0.140420E+10 | 0.650098E+09 | 0.325305E+10 | 0.153052E+10 |
Minimum of Months | 95938622.88 | 59409335.90 | 30519071.98 | 0.141245E+09 | 0.100059E+09 |
Maximum of Months | 0.261397E+09 | 0.194511E+09 | 81779250.83 | 0.432350E+09 | 0.163736E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102798E+09 | 67865751.07 | 34932482.17 | 0.156467E+09 | 0.151663E+09 |
February | 0.105532E+09 | 59409335.90 | 46122598.77 | 0.153131E+09 | 0.122854E+09 |
March | 0.150998E+09 | 85379052.46 | 65618643.42 | 0.232224E+09 | 0.136309E+09 |
April | 0.218289E+09 | 0.157553E+09 | 60736272.79 | 0.348565E+09 | 0.127317E+09 |
May | 0.224976E+09 | 0.143197E+09 | 81779250.83 | 0.350634E+09 | 0.123291E+09 |
June | 0.230814E+09 | 0.157474E+09 | 73340053.71 | 0.371150E+09 | 0.100059E+09 |
July | 0.261397E+09 | 0.194511E+09 | 66886550.64 | 0.432350E+09 | 0.102759E+09 |
August | 0.242400E+09 | 0.184754E+09 | 57646466.67 | 0.402489E+09 | 0.107630E+09 |
September | 0.180928E+09 | 0.128008E+09 | 52920623.74 | 0.292374E+09 | 0.113957E+09 |
October | 0.134255E+09 | 92618348.93 | 41636441.60 | 0.216014E+09 | 0.132541E+09 |
November | 0.105970E+09 | 68010788.38 | 37959293.64 | 0.156410E+09 | 0.148405E+09 |
December | 95938622.88 | 65419550.89 | 30519071.98 | 0.141245E+09 | 0.163736E+09 |
Annual Sum or Average | 0.205430E+10 | 0.140420E+10 | 0.650098E+09 | 0.325305E+10 | 0.153052E+10 |
Minimum of Months | 95938622.88 | 59409335.90 | 30519071.98 | 0.141245E+09 | 0.100059E+09 |
Maximum of Months | 0.261397E+09 | 0.194511E+09 | 81779250.83 | 0.432350E+09 | 0.163736E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102798E+09 | 67865751.07 | 34932482.17 | 0.156467E+09 | 0.151663E+09 |
February | 0.105532E+09 | 59409335.90 | 46122598.77 | 0.153131E+09 | 0.122854E+09 |
March | 0.150998E+09 | 85379052.46 | 65618643.42 | 0.232224E+09 | 0.136309E+09 |
April | 0.218289E+09 | 0.157553E+09 | 60736272.79 | 0.348565E+09 | 0.127317E+09 |
May | 0.224976E+09 | 0.143197E+09 | 81779250.83 | 0.350634E+09 | 0.123291E+09 |
June | 0.230814E+09 | 0.157474E+09 | 73340053.71 | 0.371150E+09 | 0.100059E+09 |
July | 0.261397E+09 | 0.194511E+09 | 66886550.64 | 0.432350E+09 | 0.102759E+09 |
August | 0.242400E+09 | 0.184754E+09 | 57646466.67 | 0.402489E+09 | 0.107630E+09 |
September | 0.180928E+09 | 0.128008E+09 | 52920623.74 | 0.292374E+09 | 0.113957E+09 |
October | 0.134255E+09 | 92618348.93 | 41636441.60 | 0.216014E+09 | 0.132541E+09 |
November | 0.105970E+09 | 68010788.38 | 37959293.64 | 0.156410E+09 | 0.148405E+09 |
December | 95938622.88 | 65419550.89 | 30519071.98 | 0.141245E+09 | 0.163736E+09 |
Annual Sum or Average | 0.205430E+10 | 0.140420E+10 | 0.650098E+09 | 0.325305E+10 | 0.153052E+10 |
Minimum of Months | 95938622.88 | 59409335.90 | 30519071.98 | 0.141245E+09 | 0.100059E+09 |
Maximum of Months | 0.261397E+09 | 0.194511E+09 | 81779250.83 | 0.432350E+09 | 0.163736E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102798E+09 | 67865751.07 | 34932482.17 | 0.156467E+09 | 0.151663E+09 |
February | 0.105532E+09 | 59409335.90 | 46122598.77 | 0.153131E+09 | 0.122854E+09 |
March | 0.150998E+09 | 85379052.46 | 65618643.42 | 0.232224E+09 | 0.136309E+09 |
April | 0.218289E+09 | 0.157553E+09 | 60736272.79 | 0.348565E+09 | 0.127317E+09 |
May | 0.224976E+09 | 0.143197E+09 | 81779250.83 | 0.350634E+09 | 0.123291E+09 |
June | 0.230814E+09 | 0.157474E+09 | 73340053.71 | 0.371150E+09 | 0.100059E+09 |
July | 0.261397E+09 | 0.194511E+09 | 66886550.64 | 0.432350E+09 | 0.102759E+09 |
August | 0.242400E+09 | 0.184754E+09 | 57646466.67 | 0.402489E+09 | 0.107630E+09 |
September | 0.180928E+09 | 0.128008E+09 | 52920623.74 | 0.292374E+09 | 0.113957E+09 |
October | 0.134255E+09 | 92618348.93 | 41636441.60 | 0.216014E+09 | 0.132541E+09 |
November | 0.105970E+09 | 68010788.38 | 37959293.64 | 0.156410E+09 | 0.148405E+09 |
December | 95938622.88 | 65419550.89 | 30519071.98 | 0.141245E+09 | 0.163736E+09 |
Annual Sum or Average | 0.205430E+10 | 0.140420E+10 | 0.650098E+09 | 0.325305E+10 | 0.153052E+10 |
Minimum of Months | 95938622.88 | 59409335.90 | 30519071.98 | 0.141245E+09 | 0.100059E+09 |
Maximum of Months | 0.261397E+09 | 0.194511E+09 | 81779250.83 | 0.432350E+09 | 0.163736E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102798E+09 | 67865751.07 | 34932482.17 | 0.156467E+09 | 0.151663E+09 |
February | 0.105532E+09 | 59409335.90 | 46122598.77 | 0.153131E+09 | 0.122854E+09 |
March | 0.150998E+09 | 85379052.46 | 65618643.42 | 0.232224E+09 | 0.136309E+09 |
April | 0.218289E+09 | 0.157553E+09 | 60736272.79 | 0.348565E+09 | 0.127317E+09 |
May | 0.224976E+09 | 0.143197E+09 | 81779250.83 | 0.350634E+09 | 0.123291E+09 |
June | 0.230814E+09 | 0.157474E+09 | 73340053.71 | 0.371150E+09 | 0.100059E+09 |
July | 0.261397E+09 | 0.194511E+09 | 66886550.64 | 0.432350E+09 | 0.102759E+09 |
August | 0.242400E+09 | 0.184754E+09 | 57646466.67 | 0.402489E+09 | 0.107630E+09 |
September | 0.180928E+09 | 0.128008E+09 | 52920623.74 | 0.292374E+09 | 0.113957E+09 |
October | 0.134255E+09 | 92618348.93 | 41636441.60 | 0.216014E+09 | 0.132541E+09 |
November | 0.105970E+09 | 68010788.38 | 37959293.64 | 0.156410E+09 | 0.148405E+09 |
December | 95938622.88 | 65419550.89 | 30519071.98 | 0.141245E+09 | 0.163736E+09 |
Annual Sum or Average | 0.205430E+10 | 0.140420E+10 | 0.650098E+09 | 0.325305E+10 | 0.153052E+10 |
Minimum of Months | 95938622.88 | 59409335.90 | 30519071.98 | 0.141245E+09 | 0.100059E+09 |
Maximum of Months | 0.261397E+09 | 0.194511E+09 | 81779250.83 | 0.432350E+09 | 0.163736E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102798E+09 | 67865751.07 | 34932482.17 | 0.156467E+09 | 0.151663E+09 |
February | 0.105532E+09 | 59409335.90 | 46122598.77 | 0.153131E+09 | 0.122854E+09 |
March | 0.150998E+09 | 85379052.46 | 65618643.42 | 0.232224E+09 | 0.136309E+09 |
April | 0.218289E+09 | 0.157553E+09 | 60736272.79 | 0.348565E+09 | 0.127317E+09 |
May | 0.224976E+09 | 0.143197E+09 | 81779250.83 | 0.350634E+09 | 0.123291E+09 |
June | 0.230814E+09 | 0.157474E+09 | 73340053.71 | 0.371150E+09 | 0.100059E+09 |
July | 0.261397E+09 | 0.194511E+09 | 66886550.64 | 0.432350E+09 | 0.102759E+09 |
August | 0.242400E+09 | 0.184754E+09 | 57646466.67 | 0.402489E+09 | 0.107630E+09 |
September | 0.180928E+09 | 0.128008E+09 | 52920623.74 | 0.292374E+09 | 0.113957E+09 |
October | 0.134255E+09 | 92618348.93 | 41636441.60 | 0.216014E+09 | 0.132541E+09 |
November | 0.105970E+09 | 68010788.38 | 37959293.64 | 0.156410E+09 | 0.148405E+09 |
December | 95938622.88 | 65419550.89 | 30519071.98 | 0.141245E+09 | 0.163736E+09 |
Annual Sum or Average | 0.205430E+10 | 0.140420E+10 | 0.650098E+09 | 0.325305E+10 | 0.153052E+10 |
Minimum of Months | 95938622.88 | 59409335.90 | 30519071.98 | 0.141245E+09 | 0.100059E+09 |
Maximum of Months | 0.261397E+09 | 0.194511E+09 | 81779250.83 | 0.432350E+09 | 0.163736E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102798E+09 | 67865751.07 | 34932482.17 | 0.156467E+09 | 0.151663E+09 |
February | 0.105532E+09 | 59409335.90 | 46122598.77 | 0.153131E+09 | 0.122854E+09 |
March | 0.150998E+09 | 85379052.46 | 65618643.42 | 0.232224E+09 | 0.136309E+09 |
April | 0.218289E+09 | 0.157553E+09 | 60736272.79 | 0.348565E+09 | 0.127317E+09 |
May | 0.224976E+09 | 0.143197E+09 | 81779250.83 | 0.350634E+09 | 0.123291E+09 |
June | 0.230814E+09 | 0.157474E+09 | 73340053.71 | 0.371150E+09 | 0.100059E+09 |
July | 0.261397E+09 | 0.194511E+09 | 66886550.64 | 0.432350E+09 | 0.102759E+09 |
August | 0.242400E+09 | 0.184754E+09 | 57646466.67 | 0.402489E+09 | 0.107630E+09 |
September | 0.180928E+09 | 0.128008E+09 | 52920623.74 | 0.292374E+09 | 0.113957E+09 |
October | 0.134255E+09 | 92618348.93 | 41636441.60 | 0.216014E+09 | 0.132541E+09 |
November | 0.105970E+09 | 68010788.38 | 37959293.64 | 0.156410E+09 | 0.148405E+09 |
December | 95938622.88 | 65419550.89 | 30519071.98 | 0.141245E+09 | 0.163736E+09 |
Annual Sum or Average | 0.205430E+10 | 0.140420E+10 | 0.650098E+09 | 0.325305E+10 | 0.153052E+10 |
Minimum of Months | 95938622.88 | 59409335.90 | 30519071.98 | 0.141245E+09 | 0.100059E+09 |
Maximum of Months | 0.261397E+09 | 0.194511E+09 | 81779250.83 | 0.432350E+09 | 0.163736E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102798E+09 | 67865751.07 | 34932482.17 | 0.156467E+09 | 0.151663E+09 |
February | 0.105532E+09 | 59409335.90 | 46122598.77 | 0.153131E+09 | 0.122854E+09 |
March | 0.150998E+09 | 85379052.46 | 65618643.42 | 0.232224E+09 | 0.136309E+09 |
April | 0.218289E+09 | 0.157553E+09 | 60736272.79 | 0.348565E+09 | 0.127317E+09 |
May | 0.224976E+09 | 0.143197E+09 | 81779250.83 | 0.350634E+09 | 0.123291E+09 |
June | 0.230814E+09 | 0.157474E+09 | 73340053.71 | 0.371150E+09 | 0.100059E+09 |
July | 0.261397E+09 | 0.194511E+09 | 66886550.64 | 0.432350E+09 | 0.102759E+09 |
August | 0.242400E+09 | 0.184754E+09 | 57646466.67 | 0.402489E+09 | 0.107630E+09 |
September | 0.180928E+09 | 0.128008E+09 | 52920623.74 | 0.292374E+09 | 0.113957E+09 |
October | 0.134255E+09 | 92618348.93 | 41636441.60 | 0.216014E+09 | 0.132541E+09 |
November | 0.105970E+09 | 68010788.38 | 37959293.64 | 0.156410E+09 | 0.148405E+09 |
December | 95938622.88 | 65419550.89 | 30519071.98 | 0.141245E+09 | 0.163736E+09 |
Annual Sum or Average | 0.205430E+10 | 0.140420E+10 | 0.650098E+09 | 0.325305E+10 | 0.153052E+10 |
Minimum of Months | 95938622.88 | 59409335.90 | 30519071.98 | 0.141245E+09 | 0.100059E+09 |
Maximum of Months | 0.261397E+09 | 0.194511E+09 | 81779250.83 | 0.432350E+09 | 0.163736E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102798E+09 | 67865751.07 | 34932482.17 | 0.156467E+09 | 0.151663E+09 |
February | 0.105532E+09 | 59409335.90 | 46122598.77 | 0.153131E+09 | 0.122854E+09 |
March | 0.150998E+09 | 85379052.46 | 65618643.42 | 0.232224E+09 | 0.136309E+09 |
April | 0.218289E+09 | 0.157553E+09 | 60736272.79 | 0.348565E+09 | 0.127317E+09 |
May | 0.224976E+09 | 0.143197E+09 | 81779250.83 | 0.350634E+09 | 0.123291E+09 |
June | 0.230814E+09 | 0.157474E+09 | 73340053.71 | 0.371150E+09 | 0.100059E+09 |
July | 0.261397E+09 | 0.194511E+09 | 66886550.64 | 0.432350E+09 | 0.102759E+09 |
August | 0.242400E+09 | 0.184754E+09 | 57646466.67 | 0.402489E+09 | 0.107630E+09 |
September | 0.180928E+09 | 0.128008E+09 | 52920623.74 | 0.292374E+09 | 0.113957E+09 |
October | 0.134255E+09 | 92618348.93 | 41636441.60 | 0.216014E+09 | 0.132541E+09 |
November | 0.105970E+09 | 68010788.38 | 37959293.64 | 0.156410E+09 | 0.148405E+09 |
December | 95938622.88 | 65419550.89 | 30519071.98 | 0.141245E+09 | 0.163736E+09 |
Annual Sum or Average | 0.205430E+10 | 0.140420E+10 | 0.650098E+09 | 0.325305E+10 | 0.153052E+10 |
Minimum of Months | 95938622.88 | 59409335.90 | 30519071.98 | 0.141245E+09 | 0.100059E+09 |
Maximum of Months | 0.261397E+09 | 0.194511E+09 | 81779250.83 | 0.432350E+09 | 0.163736E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102798E+09 | 67865751.07 | 34932482.17 | 0.156467E+09 | 0.151663E+09 |
February | 0.105532E+09 | 59409335.90 | 46122598.77 | 0.153131E+09 | 0.122854E+09 |
March | 0.150998E+09 | 85379052.46 | 65618643.42 | 0.232224E+09 | 0.136309E+09 |
April | 0.218289E+09 | 0.157553E+09 | 60736272.79 | 0.348565E+09 | 0.127317E+09 |
May | 0.224976E+09 | 0.143197E+09 | 81779250.83 | 0.350634E+09 | 0.123291E+09 |
June | 0.230814E+09 | 0.157474E+09 | 73340053.71 | 0.371150E+09 | 0.100059E+09 |
July | 0.261397E+09 | 0.194511E+09 | 66886550.64 | 0.432350E+09 | 0.102759E+09 |
August | 0.242400E+09 | 0.184754E+09 | 57646466.67 | 0.402489E+09 | 0.107630E+09 |
September | 0.180928E+09 | 0.128008E+09 | 52920623.74 | 0.292374E+09 | 0.113957E+09 |
October | 0.134255E+09 | 92618348.93 | 41636441.60 | 0.216014E+09 | 0.132541E+09 |
November | 0.105970E+09 | 68010788.38 | 37959293.64 | 0.156410E+09 | 0.148405E+09 |
December | 95938622.88 | 65419550.89 | 30519071.98 | 0.141245E+09 | 0.163736E+09 |
Annual Sum or Average | 0.205430E+10 | 0.140420E+10 | 0.650098E+09 | 0.325305E+10 | 0.153052E+10 |
Minimum of Months | 95938622.88 | 59409335.90 | 30519071.98 | 0.141245E+09 | 0.100059E+09 |
Maximum of Months | 0.261397E+09 | 0.194511E+09 | 81779250.83 | 0.432350E+09 | 0.163736E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102798E+09 | 67865751.07 | 34932482.17 | 0.156467E+09 | 0.151663E+09 |
February | 0.105532E+09 | 59409335.90 | 46122598.77 | 0.153131E+09 | 0.122854E+09 |
March | 0.150998E+09 | 85379052.46 | 65618643.42 | 0.232224E+09 | 0.136309E+09 |
April | 0.218289E+09 | 0.157553E+09 | 60736272.79 | 0.348565E+09 | 0.127317E+09 |
May | 0.224976E+09 | 0.143197E+09 | 81779250.83 | 0.350634E+09 | 0.123291E+09 |
June | 0.230814E+09 | 0.157474E+09 | 73340053.71 | 0.371150E+09 | 0.100059E+09 |
July | 0.261397E+09 | 0.194511E+09 | 66886550.64 | 0.432350E+09 | 0.102759E+09 |
August | 0.242400E+09 | 0.184754E+09 | 57646466.67 | 0.402489E+09 | 0.107630E+09 |
September | 0.180928E+09 | 0.128008E+09 | 52920623.74 | 0.292374E+09 | 0.113957E+09 |
October | 0.134255E+09 | 92618348.93 | 41636441.60 | 0.216014E+09 | 0.132541E+09 |
November | 0.105970E+09 | 68010788.38 | 37959293.64 | 0.156410E+09 | 0.148405E+09 |
December | 95938622.88 | 65419550.89 | 30519071.98 | 0.141245E+09 | 0.163736E+09 |
Annual Sum or Average | 0.205430E+10 | 0.140420E+10 | 0.650098E+09 | 0.325305E+10 | 0.153052E+10 |
Minimum of Months | 95938622.88 | 59409335.90 | 30519071.98 | 0.141245E+09 | 0.100059E+09 |
Maximum of Months | 0.261397E+09 | 0.194511E+09 | 81779250.83 | 0.432350E+09 | 0.163736E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102798E+09 | 67865751.07 | 34932482.17 | 0.156467E+09 | 0.151663E+09 |
February | 0.105532E+09 | 59409335.90 | 46122598.77 | 0.153131E+09 | 0.122854E+09 |
March | 0.150998E+09 | 85379052.46 | 65618643.42 | 0.232224E+09 | 0.136309E+09 |
April | 0.218289E+09 | 0.157553E+09 | 60736272.79 | 0.348565E+09 | 0.127317E+09 |
May | 0.224976E+09 | 0.143197E+09 | 81779250.83 | 0.350634E+09 | 0.123291E+09 |
June | 0.230814E+09 | 0.157474E+09 | 73340053.71 | 0.371150E+09 | 0.100059E+09 |
July | 0.261397E+09 | 0.194511E+09 | 66886550.64 | 0.432350E+09 | 0.102759E+09 |
August | 0.242400E+09 | 0.184754E+09 | 57646466.67 | 0.402489E+09 | 0.107630E+09 |
September | 0.180928E+09 | 0.128008E+09 | 52920623.74 | 0.292374E+09 | 0.113957E+09 |
October | 0.134255E+09 | 92618348.93 | 41636441.60 | 0.216014E+09 | 0.132541E+09 |
November | 0.105970E+09 | 68010788.38 | 37959293.64 | 0.156410E+09 | 0.148405E+09 |
December | 95938622.88 | 65419550.89 | 30519071.98 | 0.141245E+09 | 0.163736E+09 |
Annual Sum or Average | 0.205430E+10 | 0.140420E+10 | 0.650098E+09 | 0.325305E+10 | 0.153052E+10 |
Minimum of Months | 95938622.88 | 59409335.90 | 30519071.98 | 0.141245E+09 | 0.100059E+09 |
Maximum of Months | 0.261397E+09 | 0.194511E+09 | 81779250.83 | 0.432350E+09 | 0.163736E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102798E+09 | 67865751.07 | 34932482.17 | 0.156467E+09 | 0.151663E+09 |
February | 0.105532E+09 | 59409335.90 | 46122598.77 | 0.153131E+09 | 0.122854E+09 |
March | 0.150998E+09 | 85379052.46 | 65618643.42 | 0.232224E+09 | 0.136309E+09 |
April | 0.218289E+09 | 0.157553E+09 | 60736272.79 | 0.348565E+09 | 0.127317E+09 |
May | 0.224976E+09 | 0.143197E+09 | 81779250.83 | 0.350634E+09 | 0.123291E+09 |
June | 0.230814E+09 | 0.157474E+09 | 73340053.71 | 0.371150E+09 | 0.100059E+09 |
July | 0.261397E+09 | 0.194511E+09 | 66886550.64 | 0.432350E+09 | 0.102759E+09 |
August | 0.242400E+09 | 0.184754E+09 | 57646466.67 | 0.402489E+09 | 0.107630E+09 |
September | 0.180928E+09 | 0.128008E+09 | 52920623.74 | 0.292374E+09 | 0.113957E+09 |
October | 0.134255E+09 | 92618348.93 | 41636441.60 | 0.216014E+09 | 0.132541E+09 |
November | 0.105970E+09 | 68010788.38 | 37959293.64 | 0.156410E+09 | 0.148405E+09 |
December | 95938622.88 | 65419550.89 | 30519071.98 | 0.141245E+09 | 0.163736E+09 |
Annual Sum or Average | 0.205430E+10 | 0.140420E+10 | 0.650098E+09 | 0.325305E+10 | 0.153052E+10 |
Minimum of Months | 95938622.88 | 59409335.90 | 30519071.98 | 0.141245E+09 | 0.100059E+09 |
Maximum of Months | 0.261397E+09 | 0.194511E+09 | 81779250.83 | 0.432350E+09 | 0.163736E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102798E+09 | 67865751.07 | 34932482.17 | 0.156467E+09 | 0.151663E+09 |
February | 0.105532E+09 | 59409335.90 | 46122598.77 | 0.153131E+09 | 0.122854E+09 |
March | 0.150998E+09 | 85379052.46 | 65618643.42 | 0.232224E+09 | 0.136309E+09 |
April | 0.218289E+09 | 0.157553E+09 | 60736272.79 | 0.348565E+09 | 0.127317E+09 |
May | 0.224976E+09 | 0.143197E+09 | 81779250.83 | 0.350634E+09 | 0.123291E+09 |
June | 0.230814E+09 | 0.157474E+09 | 73340053.71 | 0.371150E+09 | 0.100059E+09 |
July | 0.261397E+09 | 0.194511E+09 | 66886550.64 | 0.432350E+09 | 0.102759E+09 |
August | 0.242400E+09 | 0.184754E+09 | 57646466.67 | 0.402489E+09 | 0.107630E+09 |
September | 0.180928E+09 | 0.128008E+09 | 52920623.74 | 0.292374E+09 | 0.113957E+09 |
October | 0.134255E+09 | 92618348.93 | 41636441.60 | 0.216014E+09 | 0.132541E+09 |
November | 0.105970E+09 | 68010788.38 | 37959293.64 | 0.156410E+09 | 0.148405E+09 |
December | 95938622.88 | 65419550.89 | 30519071.98 | 0.141245E+09 | 0.163736E+09 |
Annual Sum or Average | 0.205430E+10 | 0.140420E+10 | 0.650098E+09 | 0.325305E+10 | 0.153052E+10 |
Minimum of Months | 95938622.88 | 59409335.90 | 30519071.98 | 0.141245E+09 | 0.100059E+09 |
Maximum of Months | 0.261397E+09 | 0.194511E+09 | 81779250.83 | 0.432350E+09 | 0.163736E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.234289E+09 | 0.185973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.229926E+09 | 0.149641E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.342322E+09 | 0.168067E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.499515E+09 | 0.165391E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.499023E+09 | 0.168998E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.518294E+09 | 0.144513E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.590954E+09 | 0.162926E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.549948E+09 | 0.168287E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.404408E+09 | 0.168684E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.300010E+09 | 0.191810E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.232144E+09 | 0.189120E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.212314E+09 | 0.204628E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.461315E+10 | 0.206804E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.212314E+09 | 0.144513E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.590954E+09 | 0.204628E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 175.05 | 347.53 | 151.86 | 62.49 | 89.37 | 0.00 | 0.00 |
February | 193.61 | 322.41 | 182.57 | 67.95 | 114.63 | 0.00 | 0.00 |
March | 233.69 | 335.34 | 211.98 | 74.58 | 137.40 | 0.00 | 0.00 |
April | 354.96 | 300.83 | 282.25 | 120.97 | 161.29 | 0.00 | 0.00 |
May | 343.32 | 277.10 | 288.63 | 108.39 | 180.25 | 0.00 | 0.00 |
June | 400.00 | 216.26 | 306.24 | 127.50 | 178.74 | 0.00 | 0.00 |
July | 448.14 | 194.79 | 317.08 | 142.44 | 174.64 | 0.00 | 0.00 |
August | 419.67 | 206.13 | 290.73 | 131.28 | 159.44 | 0.00 | 0.00 |
September | 338.69 | 240.44 | 248.22 | 109.94 | 138.28 | 0.00 | 0.00 |
October | 273.33 | 267.48 | 191.24 | 86.07 | 105.17 | 0.00 | 0.00 |
November | 197.17 | 344.64 | 172.65 | 74.28 | 98.37 | 0.00 | 0.00 |
December | 175.51 | 365.16 | 151.60 | 67.15 | 84.45 | 0.00 | 0.00 |
Annual Sum or Average | 296.65 | 284.64 | 233.12 | 97.88 | 135.24 | 0.00 | 0.00 |
Minimum of Months | 175.05 | 194.79 | 151.60 | 62.49 | 84.45 | 0.00 | 0.00 |
Maximum of Months | 448.14 | 365.16 | 317.08 | 142.44 | 180.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 817.85 | 792.74 | 537.33 | 354.73 | 182.59 | 0.00 | 0.00 |
February | 886.18 | 710.96 | 610.72 | 343.80 | 266.91 | 0.00 | 0.00 |
March | 1213.83 | 712.49 | 789.27 | 446.28 | 342.99 | 0.00 | 0.00 |
April | 1882.68 | 687.67 | 1179.03 | 850.98 | 328.05 | 0.00 | 0.00 |
May | 1832.77 | 644.44 | 1175.95 | 748.49 | 427.46 | 0.00 | 0.00 |
June | 2004.67 | 540.44 | 1246.68 | 850.55 | 396.13 | 0.00 | 0.00 |
July | 2259.90 | 537.12 | 1366.32 | 1016.71 | 349.62 | 0.00 | 0.00 |
August | 2103.81 | 562.58 | 1267.03 | 965.71 | 301.32 | 0.00 | 0.00 |
September | 1579.18 | 615.51 | 977.24 | 691.40 | 285.84 | 0.00 | 0.00 |
October | 1129.10 | 692.79 | 701.75 | 484.12 | 217.63 | 0.00 | 0.00 |
November | 844.81 | 801.57 | 572.37 | 367.34 | 205.03 | 0.00 | 0.00 |
December | 738.29 | 855.85 | 501.47 | 341.95 | 159.52 | 0.00 | 0.00 |
Annual Sum or Average | 1444.15 | 679.46 | 911.98 | 623.38 | 288.60 | 0.00 | 0.00 |
Minimum of Months | 738.29 | 537.12 | 501.47 | 341.95 | 159.52 | 0.00 | 0.00 |
Maximum of Months | 2259.90 | 855.85 | 1366.32 | 1016.71 | 427.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 11543.42 | 7813.13 | 2174.60 | 1435.23 | 739.37 | 0.00 | 0.00 |
February | 12393.99 | 6641.03 | 2472.48 | 1391.66 | 1080.82 | 0.00 | 0.00 |
March | 16653.81 | 6594.17 | 3195.91 | 1807.04 | 1388.87 | 0.00 | 0.00 |
April | 22442.48 | 6903.78 | 4774.56 | 3446.18 | 1328.38 | 0.00 | 0.00 |
May | 20387.11 | 7169.10 | 4763.94 | 3033.01 | 1730.93 | 0.00 | 0.00 |
June | 25322.59 | 8413.05 | 5051.59 | 3447.54 | 1604.05 | 0.00 | 0.00 |
July | 37991.48 | 10753.61 | 5536.02 | 4120.31 | 1415.71 | 0.00 | 0.00 |
August | 33470.30 | 11245.36 | 5131.82 | 3911.69 | 1220.14 | 0.00 | 0.00 |
September | 18410.10 | 9976.25 | 3957.19 | 2799.74 | 1157.45 | 0.00 | 0.00 |
October | 14294.06 | 9754.30 | 2841.39 | 1960.12 | 881.27 | 0.00 | 0.00 |
November | 11713.10 | 7541.19 | 2316.69 | 1486.46 | 830.22 | 0.00 | 0.00 |
December | 10549.94 | 8443.95 | 2029.13 | 1383.17 | 645.96 | 0.00 | 0.00 |
Annual Sum or Average | 19658.28 | 8454.68 | 3693.39 | 2524.74 | 1168.65 | 0.00 | 0.00 |
Minimum of Months | 10549.94 | 6594.17 | 2029.13 | 1383.17 | 645.96 | 0.00 | 0.00 |
Maximum of Months | 37991.48 | 11245.36 | 5536.02 | 4120.31 | 1730.93 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.468847E+09 | 0.930821E+09 | 0.406736E+09 | 0.167361E+09 | 0.239375E+09 | 0.00 | 0.00 |
February | 0.468389E+09 | 0.779972E+09 | 0.441678E+09 | 0.164375E+09 | 0.277303E+09 | 0.00 | 0.00 |
March | 0.625923E+09 | 0.898164E+09 | 0.567758E+09 | 0.199746E+09 | 0.368011E+09 | 0.00 | 0.00 |
April | 0.920062E+09 | 0.779757E+09 | 0.731594E+09 | 0.313543E+09 | 0.418051E+09 | 0.00 | 0.00 |
May | 0.919555E+09 | 0.742184E+09 | 0.773078E+09 | 0.290308E+09 | 0.482770E+09 | 0.00 | 0.00 |
June | 0.103680E+10 | 0.560552E+09 | 0.793772E+09 | 0.330483E+09 | 0.463289E+09 | 0.00 | 0.00 |
July | 0.120031E+10 | 0.521729E+09 | 0.849271E+09 | 0.381505E+09 | 0.467766E+09 | 0.00 | 0.00 |
August | 0.112404E+10 | 0.552093E+09 | 0.778678E+09 | 0.351626E+09 | 0.427052E+09 | 0.00 | 0.00 |
September | 0.877894E+09 | 0.623223E+09 | 0.643388E+09 | 0.284973E+09 | 0.358416E+09 | 0.00 | 0.00 |
October | 0.732092E+09 | 0.716421E+09 | 0.512214E+09 | 0.230532E+09 | 0.281682E+09 | 0.00 | 0.00 |
November | 0.511061E+09 | 0.893315E+09 | 0.447519E+09 | 0.192542E+09 | 0.254976E+09 | 0.00 | 0.00 |
December | 0.470079E+09 | 0.978052E+09 | 0.406038E+09 | 0.179859E+09 | 0.226178E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.935505E+10 | 0.897628E+10 | 0.735172E+10 | 0.308685E+10 | 0.426487E+10 | 0.00 | 0.00 |
Minimum of Months | 0.468389E+09 | 0.521729E+09 | 0.406038E+09 | 0.164375E+09 | 0.226178E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120031E+10 | 0.978052E+09 | 0.849271E+09 | 0.381505E+09 | 0.482770E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.219054E+10 | 0.212328E+10 | 0.143918E+10 | 0.950121E+09 | 0.489055E+09 | 0.00 | 0.00 |
February | 0.214384E+10 | 0.171996E+10 | 0.147745E+10 | 0.831731E+09 | 0.645716E+09 | 0.00 | 0.00 |
March | 0.325113E+10 | 0.190833E+10 | 0.211397E+10 | 0.119531E+10 | 0.918661E+09 | 0.00 | 0.00 |
April | 0.487991E+10 | 0.178243E+10 | 0.305605E+10 | 0.220574E+10 | 0.850308E+09 | 0.00 | 0.00 |
May | 0.490888E+10 | 0.172607E+10 | 0.314966E+10 | 0.200475E+10 | 0.114491E+10 | 0.00 | 0.00 |
June | 0.519610E+10 | 0.140083E+10 | 0.323140E+10 | 0.220463E+10 | 0.102676E+10 | 0.00 | 0.00 |
July | 0.605290E+10 | 0.143862E+10 | 0.365956E+10 | 0.272315E+10 | 0.936412E+09 | 0.00 | 0.00 |
August | 0.563484E+10 | 0.150682E+10 | 0.339360E+10 | 0.258655E+10 | 0.807051E+09 | 0.00 | 0.00 |
September | 0.409323E+10 | 0.159540E+10 | 0.253299E+10 | 0.179211E+10 | 0.740889E+09 | 0.00 | 0.00 |
October | 0.302419E+10 | 0.185558E+10 | 0.187957E+10 | 0.129666E+10 | 0.582910E+09 | 0.00 | 0.00 |
November | 0.218974E+10 | 0.207767E+10 | 0.148358E+10 | 0.952151E+09 | 0.531430E+09 | 0.00 | 0.00 |
December | 0.197743E+10 | 0.229231E+10 | 0.134314E+10 | 0.915874E+09 | 0.427267E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.455427E+11 | 0.214273E+11 | 0.287601E+11 | 0.196588E+11 | 0.910137E+10 | 0.00 | 0.00 |
Minimum of Months | 0.197743E+10 | 0.140083E+10 | 0.134314E+10 | 0.831731E+09 | 0.427267E+09 | 0.00 | 0.00 |
Maximum of Months | 0.605290E+10 | 0.229231E+10 | 0.365956E+10 | 0.272315E+10 | 0.114491E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.309179E+11 | 0.209267E+11 | 0.582445E+10 | 0.384411E+10 | 0.198034E+10 | 0.00 | 0.00 |
February | 0.299835E+11 | 0.160660E+11 | 0.598142E+10 | 0.336671E+10 | 0.261472E+10 | 0.00 | 0.00 |
March | 0.446056E+11 | 0.176618E+11 | 0.855993E+10 | 0.483997E+10 | 0.371996E+10 | 0.00 | 0.00 |
April | 0.581709E+11 | 0.178946E+11 | 0.123757E+11 | 0.893250E+10 | 0.344317E+10 | 0.00 | 0.00 |
May | 0.546048E+11 | 0.192017E+11 | 0.127597E+11 | 0.812362E+10 | 0.463611E+10 | 0.00 | 0.00 |
June | 0.656362E+11 | 0.218066E+11 | 0.130937E+11 | 0.893602E+10 | 0.415769E+10 | 0.00 | 0.00 |
July | 0.101756E+12 | 0.288025E+11 | 0.148277E+11 | 0.110358E+11 | 0.379184E+10 | 0.00 | 0.00 |
August | 0.896469E+11 | 0.301196E+11 | 0.137451E+11 | 0.104771E+11 | 0.326801E+10 | 0.00 | 0.00 |
September | 0.477190E+11 | 0.258584E+11 | 0.102570E+11 | 0.725693E+10 | 0.300010E+10 | 0.00 | 0.00 |
October | 0.382852E+11 | 0.261259E+11 | 0.761039E+10 | 0.525000E+10 | 0.236039E+10 | 0.00 | 0.00 |
November | 0.303604E+11 | 0.195468E+11 | 0.600485E+10 | 0.385292E+10 | 0.215193E+10 | 0.00 | 0.00 |
December | 0.282569E+11 | 0.226163E+11 | 0.543483E+10 | 0.370468E+10 | 0.173014E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.619944E+12 | 0.266627E+12 | 0.116475E+12 | 0.796204E+11 | 0.368544E+11 | 0.00 | 0.00 |
Minimum of Months | 0.282569E+11 | 0.160660E+11 | 0.543483E+10 | 0.336671E+10 | 0.173014E+10 | 0.00 | 0.00 |
Maximum of Months | 0.101756E+12 | 0.301196E+11 | 0.148277E+11 | 0.110358E+11 | 0.463611E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.821762E+09 | -742376514.9 | 0.00 | 0.00 | 744.00 | 0.00 | -79385039.2 | 58.99 | 0.00 | 0.00 |
February | 0.753947E+09 | -682806536.0 | 0.00 | 0.00 | 672.00 | 0.00 | -71140771.2 | 58.99 | 0.00 | 0.00 |
March | 0.867721E+09 | -789289893.7 | 0.00 | 0.00 | 744.00 | 0.00 | -78430668.2 | 58.99 | 0.00 | 0.00 |
April | 0.791010E+09 | -718028101.6 | 0.00 | 0.00 | 720.00 | 0.00 | -72982090.9 | 58.99 | 0.00 | 0.00 |
May | 0.802524E+09 | -727626304.0 | 0.00 | 0.00 | 744.00 | 0.00 | -74897421.7 | 58.99 | 0.00 | 0.00 |
June | 0.780410E+09 | -708293295.5 | 0.00 | 0.00 | 720.00 | 0.00 | -72116381.8 | 58.99 | 0.00 | 0.00 |
July | 0.748350E+09 | -674427717.9 | 0.00 | 0.00 | 744.00 | 0.00 | -73922429.0 | 58.99 | 0.00 | 0.00 |
August | 0.797590E+09 | -723280863.5 | 0.00 | 0.00 | 744.00 | 0.00 | -74308895.6 | 58.99 | 0.00 | 0.00 |
September | 0.752531E+09 | -680578967.4 | 0.00 | 0.00 | 720.00 | 0.00 | -71952402.0 | 58.99 | 0.00 | 0.00 |
October | 0.772093E+09 | -697608866.2 | 0.00 | 0.00 | 744.00 | 0.00 | -74484073.3 | 58.99 | 0.00 | 0.00 |
November | 0.762201E+09 | -687594718.0 | 0.00 | 0.00 | 720.00 | 0.00 | -74605956.8 | 58.99 | 0.00 | 0.00 |
December | 0.810597E+09 | -732060640.6 | 0.00 | 0.00 | 744.00 | 0.00 | -78536628.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.946074E+10 | -0.856397E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -896762758.6 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.748350E+09 | -789289893.7 | 0.00 | 0.00 | 672.00 | 0.00 | -79385039.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.867721E+09 | -674427717.9 | 0.00 | 0.00 | 744.00 | 0.00 | -71140771.2 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.88 | 0.58 | 16-JAN-11:09 | 138.20 | 0.00 | 0.00 | 6.83 | 117.36 | 0.00 | 0.00 | 0.00 |
February | 279.67 | 0.81 | 0.50 | 10-FEB-11:09 | 182.28 | 0.00 | 0.00 | 33.00 | 692.66 | 0.00 | 0.00 | 39.33 |
March | 338.17 | 0.77 | 0.50 | 03-MAR-10:30 | 886.59 | 0.00 | 0.00 | 98.83 | 234.52 | 0.00 | 0.00 | 42.83 |
April | 358.33 | 0.78 | 0.50 | 05-APR-10:39 | 213.17 | 0.00 | 0.00 | 42.67 | 173.81 | 0.00 | 0.00 | 27.00 |
May | 393.83 | 0.75 | 0.50 | 01-MAY-10:00 | 258.99 | 0.00 | 0.00 | 112.33 | 1940.23 | 0.00 | 0.00 | 82.50 |
June | 381.00 | 0.76 | 0.50 | 01-JUN-10:39 | 1659.93 | 0.00 | 0.00 | 107.17 | 705.00 | 0.00 | 0.00 | 41.17 |
July | 408.67 | 0.77 | 0.50 | 01-JUL-10:20 | 225.76 | 0.00 | 0.00 | 87.83 | 2357.81 | 0.00 | 0.00 | 68.17 |
August | 390.67 | 0.80 | 0.50 | 01-AUG-10:09 | 201.37 | 0.00 | 0.00 | 43.83 | 733.71 | 0.00 | 0.00 | 26.50 |
September | 328.83 | 0.80 | 0.50 | 05-SEP-10:09 | 201.44 | 0.00 | 0.00 | 42.83 | 165.34 | 0.00 | 0.00 | 14.00 |
October | 296.17 | 0.84 | 0.50 | 04-OCT-10:50 | 1427.39 | 0.00 | 0.00 | 49.67 | 130.87 | 0.00 | 0.00 | 10.00 |
November | 300.00 | 0.86 | 0.50 | 02-NOV-11:20 | 146.76 | 0.00 | 0.00 | 13.00 | 124.35 | 0.00 | 0.00 | 0.83 |
December | 297.00 | 0.90 | 0.67 | 01-DEC-10:39 | 120.15 | 0.00 | 0.00 | 0.00 | 102.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4065.67 | 0.81 | 477.60 | 0.00 | 0.00 | 638.00 | 692.05 | 0.00 | 0.00 | 352.33 | ||
Minimum of Months | 279.67 | 0.75 | 0.50 | 120.15 | 0.00 | 0.00 | 0.00 | 102.93 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 408.67 | 0.90 | 0.67 | 1659.93 | 0.00 | 0.00 | 112.33 | 2357.81 | 0.00 | 0.00 | 82.50 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.75 | 0.50 | 01-JAN-11:50 | 161.78 | 11.36 | 0.00 | 64.50 | 133.05 | 15.07 | 0.83 | 41.33 |
February | 279.67 | 0.69 | 0.50 | 01-FEB-10:00 | 208.93 | 12.45 | 0.00 | 128.67 | 849.68 | 16.10 | 20.33 | 89.33 |
March | 338.17 | 0.65 | 0.50 | 01-MAR-11:09 | 249.62 | 12.97 | 0.00 | 207.00 | 281.99 | 16.61 | 45.83 | 155.33 |
April | 358.33 | 0.63 | 0.50 | 01-APR-09:20 | 1462.67 | 14.31 | 34.83 | 230.33 | 206.92 | 16.67 | 60.67 | 171.17 |
May | 393.83 | 0.62 | 0.50 | 01-MAY-07:19 | 281.77 | 13.21 | 0.00 | 271.83 | 238.87 | 16.92 | 72.83 | 206.83 |
June | 381.00 | 0.62 | 0.50 | 01-JUN-07:19 | 265.66 | 12.78 | 0.00 | 262.17 | 222.66 | 16.47 | 58.50 | 198.83 |
July | 408.67 | 0.63 | 0.50 | 01-JUL-07:00 | 248.84 | 12.55 | 0.00 | 266.50 | 208.88 | 16.36 | 72.17 | 192.17 |
August | 390.67 | 0.65 | 0.50 | 01-AUG-07:40 | 1576.58 | 13.96 | 36.67 | 238.17 | 194.13 | 16.26 | 60.17 | 169.67 |
September | 328.83 | 0.65 | 0.50 | 01-SEP-07:30 | 231.54 | 12.23 | 0.00 | 200.50 | 191.08 | 15.98 | 31.00 | 137.50 |
October | 296.17 | 0.72 | 0.50 | 01-OCT-09:39 | 2383.48 | 13.25 | 36.17 | 138.00 | 899.19 | 16.87 | 42.83 | 97.17 |
November | 300.00 | 0.74 | 0.50 | 01-NOV-08:00 | 170.34 | 11.18 | 0.00 | 84.67 | 139.80 | 14.78 | 6.00 | 57.67 |
December | 297.00 | 0.78 | 0.50 | 01-DEC-10:09 | 140.81 | 10.55 | 0.00 | 46.67 | 115.28 | 14.22 | 0.17 | 23.67 |
Annual Sum or Average | 4065.67 | 0.67 | 619.63 | 12.65 | 107.67 | 2139.00 | 293.09 | 16.09 | 471.33 | 1540.67 | ||
Minimum of Months | 279.67 | 0.62 | 0.50 | 140.81 | 10.55 | 0.00 | 46.67 | 115.28 | 14.22 | 0.17 | 23.67 | |
Maximum of Months | 408.67 | 0.78 | 0.50 | 2383.48 | 14.31 | 36.67 | 271.83 | 899.19 | 16.92 | 72.83 | 206.83 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.350673E+09 | 26985.13 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121867E+09 | 26985.13 | 27-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.224582E+09 | 26985.13 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12985355.12 | 26985.13 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16281785.76 | 15075.71 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164288E+09 | 26985.13 | 13-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.890678E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.350673E+09 | 26985.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 44550846.97 | 30587.33 | 03-JAN-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44550846.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44550846.97 | 30587.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.480244E+09 | 0.460755E+09 | 5432.04 | 24-JAN-15:30 | 5275.27 | 0.00 |
February | 0.00 | 0.00 | 0.149761E+09 | 0.147985E+09 | 4703.14 | 03-FEB-15:00 | 4703.14 | 0.00 |
March | 0.00 | 0.00 | 0.370291E+09 | 0.318533E+09 | 10265.06 | 23-MAR-17:20 | 8238.02 | 0.00 |
April | 0.00 | 0.00 | 0.151628E+10 | 0.125707E+10 | 19595.00 | 26-APR-17:11 | 14564.54 | 0.00 |
May | 0.00 | 0.00 | 0.173487E+10 | 0.148008E+10 | 19379.13 | 02-MAY-17:15 | 12838.35 | 0.00 |
June | 0.00 | 0.00 | 0.478645E+10 | 0.370031E+10 | 20862.12 | 27-JUN-17:10 | 15366.31 | 0.00 |
July | 0.00 | 0.00 | 0.854825E+10 | 0.622787E+10 | 21575.06 | 28-JUL-17:10 | 13980.70 | 0.00 |
August | 0.00 | 0.00 | 0.929258E+10 | 0.667460E+10 | 21282.02 | 18-AUG-17:10 | 14694.80 | 0.00 |
September | 0.00 | 0.00 | 0.502373E+10 | 0.384229E+10 | 21322.62 | 21-SEP-22:55 | 12154.24 | 0.00 |
October | 0.00 | 0.00 | 0.472514E+10 | 0.395459E+10 | 21248.51 | 04-OCT-17:15 | 11426.65 | 0.00 |
November | 0.00 | 0.00 | 0.442620E+09 | 0.430906E+09 | 5817.46 | 18-NOV-14:30 | 5817.46 | 0.00 |
December | 0.00 | 0.00 | 0.598324E+09 | 0.594450E+09 | 5802.11 | 05-DEC-15:00 | 5802.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.376685E+11 | 0.290894E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.149761E+09 | 0.147985E+09 | 4703.14 | 4703.14 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.929258E+10 | 0.667460E+10 | 21575.06 | 15366.31 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 25590330.21 | 18383500.52 | 5077.47 | 23-MAR-14:00 | 3728.99 | 0.00 |
April | 0.00 | 0.00 | 0.115073E+10 | 0.941282E+09 | 61765.06 | 30-APR-13:05 | 52184.47 | 0.00 |
May | 0.00 | 0.00 | 0.959499E+09 | 0.792106E+09 | 60686.81 | 28-MAY-13:55 | 47216.49 | 0.00 |
June | 0.00 | 0.00 | 0.569260E+10 | 0.413792E+10 | 65220.86 | 29-JUN-17:45 | 41574.93 | 0.00 |
July | 0.00 | 0.00 | 0.149133E+11 | 0.103179E+11 | 67430.78 | 31-JUL-17:12 | 41397.99 | 0.00 |
August | 0.00 | 0.00 | 0.154450E+11 | 0.103634E+11 | 67254.45 | 13-AUG-10:05 | 42496.01 | 0.00 |
September | 0.00 | 0.00 | 0.549952E+10 | 0.430823E+10 | 64969.74 | 10-SEP-11:05 | 43666.28 | 0.00 |
October | 0.00 | 0.00 | 0.477521E+10 | 0.420156E+10 | 67949.67 | 01-OCT-11:53 | 45317.48 | 0.00 |
November | 0.00 | 0.00 | 10955758.94 | 10955758.94 | 2497.47 | 18-NOV-14:00 | 2497.47 | 0.00 |
December | 0.00 | 0.00 | 228744.28 | 228744.28 | 381.24 | 05-DEC-15:00 | 381.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.484726E+11 | 0.350920E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.154450E+11 | 0.103634E+11 | 67949.67 | 52184.47 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.121849E+10 | 0.35 | 1222.32 | 02-JAN-08:30 | 0.92 |
February | 0.111647E+10 | 0.35 | 1222.32 | 01-FEB-14:30 | 0.92 |
March | 0.131430E+10 | 0.38 | 1222.32 | 03-MAR-07:25 | 0.92 |
April | 0.125017E+10 | 0.38 | 1222.32 | 01-APR-09:30 | 0.92 |
May | 0.132471E+10 | 0.39 | 1222.32 | 06-MAY-06:30 | 0.92 |
June | 0.142578E+10 | 0.47 | 1222.32 | 03-JUN-16:30 | 0.92 |
July | 0.151591E+10 | 0.50 | 1222.32 | 01-JUL-06:40 | 0.92 |
August | 0.160011E+10 | 0.53 | 1222.32 | 01-AUG-15:00 | 0.92 |
September | 0.139566E+10 | 0.47 | 1222.32 | 02-SEP-15:50 | 0.92 |
October | 0.134248E+10 | 0.41 | 1222.32 | 02-OCT-22:40 | 0.91 |
November | 0.116260E+10 | 0.34 | 1222.32 | 06-NOV-14:10 | 0.92 |
December | 0.121412E+10 | 0.35 | 1222.32 | 01-DEC-12:40 | 0.92 |
Annual Sum or Average | 0.158808E+11 | 0.41 | |||
Minimum of Months | 0.111647E+10 | 0.34 | 1222.32 | 0.91 | |
Maximum of Months | 0.160011E+10 | 0.53 | 1222.32 | 0.92 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.121686E+10 | 0.20 | 1227.60 | 02-JAN-07:10 | 0.54 |
February | 0.111810E+10 | 0.20 | 1227.60 | 01-FEB-07:10 | 0.54 |
March | 0.131255E+10 | 0.21 | 1227.60 | 01-MAR-07:05 | 0.54 |
April | 0.122027E+10 | 0.21 | 1227.60 | 25-APR-12:30 | 0.54 |
May | 0.126618E+10 | 0.21 | 1227.60 | 03-MAY-11:20 | 0.54 |
June | 0.129677E+10 | 0.22 | 1832.40 | 25-JUN-11:37 | 0.69 |
July | 0.132571E+10 | 0.22 | 3069.01 | 15-JUL-17:06 | 0.88 |
August | 0.137986E+10 | 0.23 | 3069.01 | 06-AUG-12:13 | 0.88 |
September | 0.124114E+10 | 0.21 | 1883.73 | 29-SEP-17:10 | 0.70 |
October | 0.123834E+10 | 0.21 | 3069.01 | 01-OCT-11:53 | 0.88 |
November | 0.116671E+10 | 0.20 | 1227.60 | 18-NOV-13:10 | 0.54 |
December | 0.121533E+10 | 0.20 | 1227.60 | 01-DEC-07:05 | 0.54 |
Annual Sum or Average | 0.149978E+11 | 0.21 | |||
Minimum of Months | 0.111810E+10 | 0.20 | 1227.60 | 0.54 | |
Maximum of Months | 0.137986E+10 | 0.23 | 3069.01 | 0.88 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.132578E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.115002E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.139595E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.158105E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.170346E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.243839E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.329105E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.351957E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.247926E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.237348E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.126139E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.134810E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.238675E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.115002E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.351957E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.121686E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.111810E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.131904E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.150242E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.150400E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.265445E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.479484E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.497064E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.261006E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.246475E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.116965E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.121539E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.265402E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.111810E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.497064E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.121849E+10 | 0.480244E+09 | 0.350673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111647E+10 | 0.149761E+09 | 0.121867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131430E+10 | 0.370291E+09 | 0.224582E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125017E+10 | 0.151628E+10 | 12985355.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132471E+10 | 0.173487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142578E+10 | 0.478645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.151591E+10 | 0.854825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160011E+10 | 0.929258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139566E+10 | 0.502373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134248E+10 | 0.472514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116260E+10 | 0.442620E+09 | 16281785.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121412E+10 | 0.598324E+09 | 0.164288E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158808E+11 | 0.376685E+11 | 0.890678E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111647E+10 | 0.149761E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160011E+10 | 0.929258E+10 | 0.350673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.121686E+10 | 0.00 | 44550846.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131255E+10 | 25590330.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122027E+10 | 0.109113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.126618E+10 | 0.947167E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129677E+10 | 0.548888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.132571E+10 | 0.140356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137986E+10 | 0.148285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.124114E+10 | 0.534477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123834E+10 | 0.468755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116671E+10 | 10955758.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121533E+10 | 228744.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149978E+11 | 0.464604E+11 | 44550846.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137986E+10 | 0.148285E+11 | 44550846.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.121849E+10 | 0.00 | 0.00 | 0.00 | 0.107295E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 33548591.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131430E+10 | 0.00 | 0.00 | 0.00 | 81647500.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125017E+10 | 0.00 | 0.00 | 0.00 | 0.330875E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132471E+10 | 0.00 | 0.00 | 0.00 | 0.378745E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142578E+10 | 0.00 | 0.00 | 0.00 | 0.101260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.151591E+10 | 0.00 | 0.00 | 0.00 | 0.177515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160011E+10 | 0.00 | 0.00 | 0.00 | 0.191946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139566E+10 | 0.00 | 0.00 | 0.00 | 0.108360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134248E+10 | 0.00 | 0.00 | 0.00 | 0.103100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116260E+10 | 0.00 | 0.00 | 0.00 | 98781011.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121412E+10 | 0.00 | 0.00 | 0.00 | 0.133979E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158808E+11 | 0.00 | 0.00 | 0.00 | 0.798668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 33548591.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160011E+10 | 0.00 | 0.00 | 0.00 | 0.191946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.121686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131255E+10 | 0.00 | 0.00 | 0.00 | 6482103.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.282148E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.126618E+10 | 0.00 | 0.00 | 0.00 | 0.237821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129677E+10 | 0.00 | 0.00 | 0.00 | 0.135768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.132571E+10 | 0.00 | 0.00 | 0.00 | 0.346913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137986E+10 | 0.00 | 0.00 | 0.00 | 0.359078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.124114E+10 | 0.00 | 0.00 | 0.00 | 0.136892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123834E+10 | 0.00 | 0.00 | 0.00 | 0.122640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116671E+10 | 0.00 | 0.00 | 0.00 | 2933331.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 61045.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149978E+11 | 0.00 | 0.00 | 0.00 | 0.115424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137986E+10 | 0.00 | 0.00 | 0.00 | 0.359078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.375285E+09 | 5410461.45 | 0.00 | 2018140.07 | 0.00 | 31535106.66 | 0.180229E+10 | 0.00 | 0.38 |
February | 0.362502E+09 | 3263701.89 | 0.00 | 1837213.72 | 0.00 | 1880737.21 | 0.191131E+10 | 0.00 | 0.38 |
March | 0.439055E+09 | 0.00 | 0.00 | 2424247.38 | 0.00 | 9617328.50 | 0.223889E+10 | 0.00 | 0.41 |
April | 46018310.32 | 5665049.89 | 0.00 | 5667562.22 | 0.00 | 0.00 | 0.355650E+10 | 0.00 | 0.77 |
May | 30231924.59 | 5888657.13 | 0.00 | 6799500.49 | 0.00 | 0.00 | 0.411435E+10 | 0.00 | 0.85 |
June | 18313488.97 | 0.125954E+09 | 0.00 | 8327707.45 | 0.00 | 0.00 | 0.308707E+10 | 0.00 | 1.04 |
July | 762754.39 | 0.546078E+09 | 0.00 | 8507818.75 | 0.00 | 0.00 | 0.149521E+10 | 0.00 | 0.91 |
August | 2424248.91 | 0.687753E+09 | 0.00 | 5779639.06 | 0.00 | 0.00 | 0.126838E+10 | 0.00 | 0.93 |
September | 22369926.55 | 0.158957E+09 | 0.00 | 7031034.65 | 0.00 | 0.00 | 0.273131E+10 | 0.00 | 0.96 |
October | 19678684.92 | 0.287466E+09 | 0.00 | 5547934.03 | 31801.37 | 0.00 | 0.230486E+10 | 0.00 | 0.77 |
November | 0.149317E+09 | 1544461.50 | 0.00 | 3394026.51 | 0.00 | 0.00 | 0.284871E+10 | 0.00 | 0.55 |
December | 0.278716E+09 | 1884675.46 | 0.00 | 2559406.92 | 0.00 | 0.00 | 0.205176E+10 | 0.00 | 0.46 |
Annual Sum or Average | 0.174467E+10 | 0.182986E+10 | 0.00 | 59894231.24 | 31801.37 | 43033172.38 | 0.294106E+11 | 0.00 | 0.70 |
Minimum of Months | 762754.39 | 0.00 | 0.00 | 1837213.72 | 0.00 | 0.00 | 0.126838E+10 | 0.00 | 0.38 |
Maximum of Months | 0.439055E+09 | 0.687753E+09 | 0.00 | 8507818.75 | 31801.37 | 31535106.66 | 0.411435E+10 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.354549E+10 | 0.00 | 0.00 | 1055.50 | 886396.62 | 0.00 | 8280488.10 | 0.00 | 0.18 |
February | 0.359980E+10 | 0.00 | 0.00 | 10436.23 | 0.00 | 0.00 | 21739515.70 | 0.00 | 0.18 |
March | 0.430366E+10 | 0.00 | 0.00 | 477483.15 | 0.00 | 0.00 | 0.451178E+09 | 0.00 | 0.20 |
April | 0.244620E+10 | 304851.58 | 0.00 | 5390089.39 | 0.00 | 0.00 | 0.354572E+10 | 0.00 | 0.30 |
May | 0.227691E+10 | 0.00 | 0.00 | 6333745.60 | 0.00 | 0.00 | 0.441458E+10 | 0.00 | 0.32 |
June | 0.102798E+10 | 9849536.91 | 0.00 | 17326196.21 | 0.00 | 0.00 | 0.555999E+10 | 0.00 | 0.47 |
July | 62061505.09 | 0.533257E+09 | 0.00 | 28923151.32 | 0.00 | 0.00 | 0.470669E+10 | 0.00 | 0.56 |
August | 89517791.84 | 0.595437E+09 | 0.00 | 26192716.18 | 0.00 | 0.00 | 0.413750E+10 | 0.00 | 0.58 |
September | 0.745317E+09 | 97352339.31 | 0.00 | 11844479.18 | 0.00 | 0.00 | 0.566817E+10 | 0.00 | 0.44 |
October | 0.113980E+10 | 0.263742E+09 | 0.00 | 6391340.96 | 0.00 | 0.00 | 0.347149E+10 | 0.00 | 0.35 |
November | 0.383812E+10 | 0.00 | 0.00 | 71449.47 | 0.00 | 0.00 | 0.141407E+09 | 0.00 | 0.18 |
December | 0.345598E+10 | 0.00 | 0.00 | 25961.74 | 0.00 | 0.00 | 56356824.43 | 0.00 | 0.18 |
Annual Sum or Average | 0.265308E+11 | 0.149994E+10 | 0.00 | 0.102988E+09 | 886396.62 | 0.00 | 0.321831E+11 | 0.00 | 0.33 |
Minimum of Months | 62061505.09 | 0.00 | 0.00 | 1055.50 | 0.00 | 0.00 | 8280488.10 | 0.00 | 0.18 |
Maximum of Months | 0.430366E+10 | 0.595437E+09 | 0.00 | 28923151.32 | 886396.62 | 0.00 | 0.566817E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.579224E+12 | 0.219864E+11 | 0.00 | 0.576102E+10 | 0.770201E+09 |
February | 0.654891E+12 | 0.295591E+11 | 0.00 | 0.589728E+10 | 0.240828E+09 |
March | 0.920251E+12 | 0.368766E+11 | 0.00 | 0.745478E+10 | 0.589104E+09 |
April | 0.124398E+13 | 0.330828E+11 | 0.00 | 0.977911E+10 | 0.328588E+10 |
May | 0.130594E+13 | 0.425484E+11 | 0.00 | 0.109742E+11 | 0.331094E+10 |
June | 0.130120E+13 | 0.357869E+11 | 0.00 | 0.975652E+10 | 0.128493E+11 |
July | 0.142493E+13 | 0.390962E+11 | 0.00 | 0.530849E+10 | 0.287058E+11 |
August | 0.132243E+13 | 0.403596E+11 | 0.00 | 0.433294E+10 | 0.302478E+11 |
September | 0.102967E+13 | 0.294470E+11 | 0.00 | 0.934561E+10 | 0.129758E+11 |
October | 0.734948E+12 | 0.303340E+11 | 0.00 | 0.659871E+10 | 0.117578E+11 |
November | 0.618751E+12 | 0.282710E+11 | 0.00 | 0.698696E+10 | 0.563363E+09 |
December | 0.529898E+12 | 0.241300E+11 | 0.00 | 0.584698E+10 | 0.810866E+09 |
Annual Sum or Average | 0.116661E+14 | 0.391478E+12 | 0.00 | 0.880426E+11 | 0.106108E+12 |
Minimum of Months | 0.529898E+12 | 0.219864E+11 | 0.00 | 0.433294E+10 | 0.240828E+09 |
Maximum of Months | 0.142493E+13 | 0.425484E+11 | 0.00 | 0.109742E+11 | 0.302478E+11 |