Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2023-10-16 10:41:43
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2369.12 | 489.98 | 489.98 |
Net Site Energy | 2369.12 | 489.98 | 489.98 |
Total Source Energy | 4051.84 | 838.00 | 838.00 |
Net Source Energy | 4051.84 | 838.00 | 838.00 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1656.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 14.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 396.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 92.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 137.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 44.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 712.30 | 1656.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1656.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 14.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 396.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 92.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 137.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 43.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1656.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 14.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 396.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 92.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 137.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 44.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 26.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 101.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 17.74 | 342.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 147.32 | 342.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 101.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 17.74 | 342.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 147.32 | 342.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 712.297 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 712.297 | 100.00 |
Total On-Site and Utility Electric Sources | 712.297 | 100.00 |
Total Electricity End Uses | 712.297 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 82.00 |
Time Setpoint Not Met During Occupied Cooling | 2.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3162.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.61 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 9.9957 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 10.2257 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 6.2431 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.5746 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.5746 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 9.9957 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 10.2257 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 6.2431 | 46.45 | 2.5587 | |
Total | 4835.13 | 7.5746 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 7.5746 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 7.5746 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-14:50 | 09-DEC-08:00 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 493488.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 14644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 28376.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5101.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1767.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 59944.56 | 493488.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 493488.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 14644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 28376.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2796.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1767.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1796.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 47.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1256.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 293.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 434.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 139.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 84.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2255.85 | 1796.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 371.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 9.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 259.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 28.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 466.55 | 371.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 371.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 9.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 259.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 28.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 466.55 | 371.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.10 |
ZONE2 FINE STORAGE DIRECT AIR | 2.47 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 7.23 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 7.23 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 282246.16 |
PSZ-OFFICE HEATING COIL | 29677.45 |
PSZ-FINE STORAGE HEATING COIL | 90133.70 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 282246.16 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.10 | 1.10 | 1.10 | 1.10 | 1.10 | 1.10 | 1.00 | 1.00 | 1.10 |
PSZ-FINE STORAGE | 2.47 | 2.47 | 2.47 | 2.47 | 2.47 | 2.47 | 1.00 | 1.000000 | 2.47 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.10 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.47 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.10 | 1219.86 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.47 | 2641.76 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.10 | 1.10 | 1.10 | 1.10 | 21124.84 | 29677.45 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.47 | 2.47 | 2.47 | 1.63 | 61306.84 | 90133.70 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.10 | 0.550895 | 0.734527 | 21124.84 | 10562.42 | 0.793420 | 0.793420 |
PSZ-FINE STORAGE COOLING COIL | 2.47 | 1.23 | 1.65 | 61306.84 | 30653.42 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 9.996 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.069 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 10.226 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.226 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 6.243 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 8.802 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2367.778 | 9.996 | 185.726 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2367.778 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 14248.589 | 10.226 | 474.953 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 14248.589 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 20008.023 | 6.243 | 289.971 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20008.023 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2893 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.4332 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.4896 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.7823 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.7823 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.457 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.309 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.943 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.179 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.179 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.87112823E-12 | 0.85080972E-17 | 0.21755189E-17 | 0.0000000 |
2 | 1 | -5.2160329 | 0.44465164E-04 | -0.55377147E-04 | 0.16700973E-12 |
3 | 0 | 5.5053245 | 0.28924715 | 0.28934699 | |
4 | 2 | 0.53503428E-11 | 0.43487872E-15 | 0.25437469E-15 | 0.0000000 |
5 | 1 | -5.2159992 | 0.41060176E-04 | -0.36984335E-04 | 0.68788638E-11 |
6 | 0 | 5.6491605 | 0.43312021 | 0.43319826 | |
7 | 4 | 0.78026225E-12 | 0.12659145E-15 | -0.22020359E-14 | 0.11649932E-15 |
8 | 3 | -0.38432829E-03 | 0.34368276E-06 | -0.55745575E-04 | 0.14971848E-12 |
9 | 2 | 1.7386347 | 0.75169100E-02 | 1.1397638 | -0.73682039E-04 |
10 | 1 | -7.1298666 | 0.19478837 | -17.093767 | 0.33322565 |
11 | 0 | 5.7181297 | 0.12420785 | 16.280573 | |
12 | 4 | 0.72249793E-12 | -0.16720573E-15 | 0.22015083E-14 | 0.12409536E-15 |
13 | 3 | -0.36459118E-03 | 0.53555631E-06 | -0.52695411E-04 | 0.13865996E-12 |
14 | 2 | 1.6915239 | 0.11971291E-01 | 1.1039557 | -0.69896550E-04 |
15 | 1 | -7.1930661 | 0.31446443 | -16.864389 | 0.32415671 |
16 | 0 | 6.0306730 | 0.20232993 | 16.289252 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.22015083E-14 | -0.16720573E-15 | 0.72249793E-12 | 0.12409536E-15 |
85 | 3 | -0.52695411E-04 | 0.53555631E-06 | -0.36459118E-03 | 0.13865996E-12 |
86 | 2 | 1.1039557 | 0.11971291E-01 | 1.6915239 | -0.69896550E-04 |
87 | 1 | -16.864389 | 0.31446443 | -7.1930661 | 0.32415671 |
88 | 0 | 16.289252 | 0.20232993 | 6.0306730 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5016_SHGC_SOUTH_0.4 | 34 | 1 | VerySmooth | 2.852 | 2.852 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.5016_SHGC_NORTH_0.4 | 35 | 1 | VerySmooth | 2.852 | 2.852 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.5016_SHGC_EAST_0.4 | 36 | 1 | VerySmooth | 2.852 | 2.852 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.5016_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.852 | 2.852 | 1.000 | 0.401 | ||
5 | SKYLIGHT_U_1.02_SHGC_0.49 | 38 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.491 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.95586E-002 | 0.31435 | 0.46537 | 0.46537 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10843 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.95586E-002 | 0.31435 | 0.46537 | 0.46537 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10843 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.95586E-002 | 0.31435 | 0.46537 | 0.46537 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10843 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.95586E-002 | 0.31435 | 0.46537 | 0.46537 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10843 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.32532 | 0.12431 | 0.12431 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE3 BULK STORAGE | 10 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.849 | 0.366 | 0.255 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.710 | 8.455E-004 | 5.523E-004 | 0.277 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0441E-004 |
2 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7472E-004 |
3 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6964E-004 |
4 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2079E-004 |
5 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8116E-004 |
6 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8959E-004 |
7 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3627E-004 |
8 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4320E-003 |
9 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0883E-003 |
10 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2199E-004 |
11 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5268E-003 |
12 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4692E-003 |
13 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0407E-004 |
14 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1662E-004 |
15 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1317E-004 |
16 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4320E-003 |
17 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1369E-004 |
18 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8592E-004 |
19 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9978E-004 |
20 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2079E-004 |
21 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4468E-004 |
22 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2051E-004 |
23 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5771E-004 |
24 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2079E-004 |
25 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6841E-004 |
26 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1484E-004 |
27 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3578E-003 |
28 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4320E-003 |
29 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1686E-003 |
30 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1774E-003 |
31 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0429E-003 |
32 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4692E-003 |
33 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0136E-003 |
34 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.8563E-004 |
35 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5164E-003 |
36 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4320E-003 |
37 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8057E-004 |
38 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6099E-004 |
39 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.0378E-004 |
40 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2079E-004 |
41 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.1475E-002 |
42 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.2928E-004 |
43 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.1220E-002 |
44 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.7120E-004 |
45 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.0147E-002 |
46 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.6289E-004 |
47 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.1238E-003 |
48 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 4.9215E-004 |
49 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.3819E-004 |
50 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.7860E-002 |
51 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.8319E-004 |
52 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.2958E-002 |
53 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.6689E-004 |
54 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.2169E-002 |
55 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.9195E-004 |
56 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.7684E-002 |
57 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.6918E-003 |
58 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.7186E-004 |
59 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.3367E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.9366E-004 |
61 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.1454E-003 |
62 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.2366E-004 |
63 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.2005E-003 |
64 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.0398E-004 |
65 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.3693E-002 |
66 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.8060E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.0199E-002 |
68 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.9967E-004 |
69 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 7.3649E-003 |
70 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.2458E-004 |
71 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.1869E-002 |
72 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.0618E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10642.89264 | 12771.47116 | 0.91816 | 1.10179 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 29.85733 | 1.53626E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 14526.45830 | 17431.74996 | 0.42773 | 0.51328 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20000 | 3.61342E-004 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 30588.86570 | 36706.63884 | 2.05736 | 2.46883 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 31.20000 | 1.53651E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 57410.66662 | 68892.79995 | 1.42286 | 1.70744 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -26.20000 | 3.61342E-004 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 31.20000 | 1.53651E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 235205.13178 | 282246.15813 | 6.02403 | 7.22884 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 15850.92 | 1.10179 | 1.10179 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 16804.74 | 0.51328 | 0.51328 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 44079.05 | 2.46883 | 2.46883 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 68647.55 | 1.70744 | 1.70744 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.10179 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.46883 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.22884 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 7.22884 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 282246.15653 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 282246.15813 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.10179 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.10179 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.10179 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.10179 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.10179 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.10179 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.46883 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.46883 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.46883 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.46883 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.46883 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.46883 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.10179 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.46883 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.10179 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.10179 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1219.85669 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.10179 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.10179 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.10179 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.10179 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.10179 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55090 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.73453 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21124.84000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10562.42000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79342 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79342 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21124.84000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29677.45481 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 29677.45481 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.46883 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.46883 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2641.76100 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.46883 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.46883 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.46883 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.62943 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.46883 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.23441 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.64589 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 61306.84000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 30653.42000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 61306.84000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 90133.69852 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 90133.69852 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 20269.4 | 11.74 | 11.47 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 59387.8 | 12.06 | 11.79 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.3001588304 | 0.2645049089 | Pass | Pass | 1.2021042081 | 9.4986398779 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.6083237348 | 0.5742725122 | Pass | Pass | 0.7508656444 | 0.8315726483 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 7.5596194308E-005 | 1.9270623910E-004 | Pass | Pass | 1.9630882807E-002 | 2.0796584294E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8393.07 | 1157.89 | 0.00 | 90.33 | 453.34 | 10094.66 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.456 | 0.490 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.456 | 0.490 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.456 | 0.490 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.456 | 0.490 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.456 | 0.490 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.456 | 0.490 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.456 | 0.490 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.278 | 0.289 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.409 | 0.433 | 3204.84 | 3170.23 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.659 | 0.782 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.659 | 0.782 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.5016_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.852 | 0.401 | 0.402 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.5016_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.852 | 0.401 | 0.402 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.5016_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.852 | 0.401 | 0.402 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.5016_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.852 | 0.401 | 0.402 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.27 | 4.803 | 0.500 | 0.501 | |||||||||||||||||
North Total or Average | 6.51 | 2.852 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 45.76 | 5.080 | 0.514 | 0.515 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 9.9957 | 236.88 | 2367.78 | LightsWired | LTG_SCH_OFFICE | 56.95 | 168.00 | 48.40 | 0.0000 | Y | 21.51 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 10.2257 | 1393.41 | 14248.59 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 162.28 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 6.2431 | 3204.84 | 20008.02 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 56.70 | 0.0000 | Y | 212.94 |
Interior Lighting Total | 7.5746 | 4835.13 | 36624.39 | 396.73 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.12 | 20008.02 | 2320.93 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.11 | 2367.78 | 260.46 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.11 | 2367.78 | 260.46 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 125.92 | AstronomicalClock | - | 42.24 | 42.24 | 1.00 | |
EXTERIOR_LIGHTS_B | 6860.50 | AstronomicalClock | - | 83.63 | 71.21 | 91.71 | |
Exterior Lighting Total | 6986.42 | 92.71 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21124.84 | 16760.87 | 4363.97 | 0.79 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 61306.84 | 42981.00 | 18325.84 | 0.70 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 20269.4 | 11.74 | 11.47 | ||||
PSZ-FINE STORAGE COOLING COIL | 59387.8 | 12.06 | 11.79 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 282246.16 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 29677.45 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 90133.70 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 7.23 | 671.63 | 92.91 | 1.00 | 3.05 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.10 | 1219.86 | 1107.16 | 1.00 | 1.38 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.47 | 2641.76 | 1070.05 | 1.00 | 1.29 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10642.89 | 12771.47 | 53.92 | 0.918 | 1.102 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 23.90 | 23.90 | 0.00873 | 29.86 | 0.01536 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 30588.87 | 36706.64 | 26.34 | 2.057 | 2.469 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 26.70 | 26.69 | 0.00965 | 31.20 | 0.01537 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 0.00 | 31.71 | 0.01543 | 31.20 | 0.01537 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 14526.46 | 17431.75 | 73.59 | 0.428 | 0.513 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00727 | -26.20 | 0.00036 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 57410.67 | 68892.80 | 49.44 | 1.423 | 1.707 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.55 | 0.00603 | -26.20 | 0.00036 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 235205.13 | 282246.16 | 88.07 | 6.024 | 7.229 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 9.99 | 0.00530 | -26.20 | 0.00036 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.10 | 1.10 | 0.51 | 0.51 | 1.1018 | 1.1018 | 1.1018 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.47 | 2.47 | 1.71 | 1.71 | 2.4688 | 2.4688 | 2.4688 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 282246.157 | 282246.157 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 282246.16 | 282246.16 | 7.228840 | 9.99 | 7.01 | 0.00530122 | 43.33 | 21.59 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 9.99 | 0.00530122 | 66.5363 | 282246.16 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 21124.840 | 16760.871 | 1.101790 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 10562.42 | 8670.36 | 0.734527 | 25.42 | 17.10 | 0.00934750 | 12.00 | 10.84 | 0.00800000 | 30.14 | 0.01536312 | 22.84 | 13.9252 | 23.90 | 0.00873123 | 45.0916 | 10632.54 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 29677.455 | 29677.455 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 29677.45 | 29677.45 | 1.101790 | 16.66 | 11.39 | 0.00662731 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 9.2835 | 21.10 | 0.00726854 | 44.6063 | 14526.46 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 61306.840 | 42980.999 | 2.468830 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30653.42 | 22561.82 | 1.645887 | 28.38 | 19.06 | 0.01063353 | 12.00 | 10.84 | 0.00800000 | 31.20 | 0.01536508 | 23.13 | 25.8044 | 26.69 | 0.00965044 | 42.1372 | 30588.87 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 90133.699 | 90133.699 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 90133.70 | 90133.70 | 2.468826 | 8.37 | 5.93 | 0.00505643 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 17.2030 | 15.55 | 0.00603194 | 52.5358 | 57410.67 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 282246.157 | 282246.157 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 7.228840 | 8.30272608 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 282246.16 | 282246.16 | 1.0000 | 8.30272608 | 7.228840 | 9.99 | 7.01 | 0.00530122 | 23397.6 | 43.33 | 21.59 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 282246.16 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 9.99 | 0.00530122 | 9.99 | 0.00530122 | 66.5363 | 282246.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21124.840 | 16760.871 | 1.101790 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.2165 | 1004.8586 | 1.1486 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.101790 | 1.26546760 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | Sensible | 10562.42 | 8670.36 | 1.0000 | 0.84364488 | 0.734527 | 25.42 | 17.10 | 0.00934750 | 49362.6 | 12.00 | 10.84 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10562.42 | 30.14 | 0.01536312 | 22.84 | 0.10228463 | 13.9252 | 23.90 | 0.00873123 | 23.90 | 0.00873123 | 45.0916 | 10632.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29677.455 | 29677.455 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.101790 | 1.26546760 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 29677.45 | 29677.45 | 1.0000 | 1.26546760 | 1.101790 | 16.66 | 11.39 | 0.00662731 | 33522.0 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29677.45 | -26.20 | 0.00036134 | -26.20 | 0.10228463 | 9.2835 | 21.05 | 0.00726854 | 21.10 | 0.00726854 | 44.6063 | 14526.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 61306.840 | 42980.999 | 2.468830 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.6072 | 1004.8586 | 1.1486 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.468826 | 2.83558500 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 30653.42 | 22561.82 | 1.0000 | 1.89039272 | 1.645887 | 28.38 | 19.06 | 0.01063353 | 55671.2 | 12.00 | 10.84 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30653.42 | 31.20 | 0.01536508 | 23.13 | 0.42471127 | 25.8044 | 26.69 | 0.00965044 | 26.69 | 0.00965044 | 42.1372 | 30588.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 90133.699 | 90133.699 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.468826 | 2.83558500 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 90133.70 | 90133.70 | 1.0000 | 2.83558500 | 2.468826 | 8.37 | 5.93 | 0.00505643 | 21132.0 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 90133.70 | -26.20 | 0.00036134 | -26.20 | 0.42471127 | 17.2030 | 15.55 | 0.00603194 | 15.55 | 0.00603194 | 52.5358 | 57410.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.10 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 2.47 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2845.33 | 2883.33 | 2245.00 |
ZONE2 FINE STORAGE | 3218.50 | 3228.67 | 2864.50 |
ZONE3 BULK STORAGE | 3374.83 | 3335.83 | 3109.83 |
Facility | 3455.83 | 3395.83 | 3162.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 270.00 | 52.17 | 65.17 | 2.17 |
ZONE2 FINE STORAGE | 571.17 | 11.33 | 27.00 | 0.00 |
ZONE3 BULK STORAGE | 12.33 | 0.00 | 7.83 | 0.00 |
Facility | 744.33 | 62.17 | 82.00 | 2.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.683 | 0.366 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.546 | 0.353 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.216 | 0.000 | 0.141 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.50 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.36 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.28 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2643916.16 | 0.00 | 2643916.16 | 2349425.27 | 4993341.43 | 3225648.14 | 5585.32 | 2358.50 | 816.18 | 98.18 |
ZONE2 FINE STORAGE | 5820584.27 | 0.00 | 5820584.27 | 9790874.37 | 15611458.64 | 13393694.68 | 5715.66 | 2530.67 | 513.67 | 9.82 |
ZONE3 BULK STORAGE | 0.00 | 31952308.82 | 31952308.82 | 56304356.95 | 88256665.76 | 30805497.77 | 6679.68 | 131.33 | 1948.98 | 5100.68 |
Total Facility | 8464500.43 | 31952308.82 | 40416809.25 | 68444656.59 | 0.11E+09 | 47424840.58 | 7832.36 | 2816.08 | 2877.05 | 5101.68 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1876 | 0.0000 | 0.1876 | 0.1012 | 0.2888 | 0.1023 | 551.83 | 2358.50 | 725.67 |
ZONE2 FINE STORAGE | 0.4417 | 0.0000 | 0.4417 | 0.2881 | 0.7298 | 0.4247 | 601.44 | 2530.67 | 503.89 |
ZONE3 BULK STORAGE | 0.0000 | 1.3537 | 1.3537 | 2.1287 | 3.4824 | 0.9768 | 2591.28 | 53.00 | 991.72 |
Total Facility | 0.6293 | 1.3537 | 1.9830 | 2.5180 | 4.5011 | 1.5038 | 2708.45 | 2737.75 | 1822.59 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 3487802.61 | 0.00 | 3487802.61 | 3225648.14 | 5581.90 | 0.17 | 3177.93 | 98.18 |
PSZ-FINE STORAGE | 7678510.65 | 0.00 | 7678510.65 | 13393694.68 | 5714.00 | 0.17 | 3045.84 | 9.82 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2475 | 0.0000 | 0.2475 | 0.1023 | 549.00 | 0.17 | 3086.84 |
PSZ-FINE STORAGE | 0.5827 | 0.0000 | 0.5827 | 0.4247 | 599.78 | 0.17 | 3036.06 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2842.33 | 350.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2919.76 | 128.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2660 | 0.5038 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6836 | 1.0181 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 389 |
Defaulted Fields | 319 |
Fields with Defaults | 1046 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 712.30 | 4450.93 | 19-MAR-09:20 | 59944.56 | 04-AUG-14:50 |
Electricity:Building | 534.36 | 3969.93 | 01-JAN-10:30 | 40750.63 | 08-DEC-15:50 |
Electricity:Zone:ZONE1 OFFICE | 51.23 | 776.36 | 01-JAN-10:30 | 3432.39 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 533.80 | 3969.93 | 01-JAN-10:30 | 40750.63 | 08-DEC-15:50 |
InteriorLights:Electricity | 396.74 | 3481.38 | 01-JAN-10:30 | 30696.62 | 08-DEC-15:50 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 21.51 | 287.82 | 01-JAN-10:30 | 1578.50 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 396.74 | 3481.38 | 01-JAN-10:30 | 30696.62 | 08-DEC-15:50 |
LightsWired:InteriorLights:Electricity | 396.74 | 3481.38 | 01-JAN-10:30 | 30696.62 | 08-DEC-15:50 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 21.51 | 287.82 | 01-JAN-10:30 | 1578.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 396.74 | 3481.38 | 01-JAN-10:30 | 30696.62 | 08-DEC-15:50 |
Electricity:Zone:ZONE2 FINE STORAGE | 162.28 | 1424.86 | 01-JAN-00:10 | 12111.30 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 162.28 | 1424.86 | 01-JAN-00:10 | 12111.30 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 162.28 | 1424.86 | 01-JAN-00:10 | 12111.30 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 320.85 | 1768.71 | 01-JAN-10:30 | 25539.44 | 26-JUN-12:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 212.95 | 1768.71 | 01-JAN-10:30 | 17006.82 | 02-JAN-10:30 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 212.95 | 1768.71 | 01-JAN-10:30 | 17006.82 | 02-JAN-10:30 |
InteriorEquipment:Electricity | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.72 | 488.55 | 01-JAN-00:10 | 1853.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.72 | 488.55 | 01-JAN-00:10 | 1853.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 44.04 | 0.00 | 24-FEB-18:10 | 5180.42 | 04-AUG-15:30 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.56 | 0.00 | 01-JAN-00:10 | 2305.29 | 26-JUN-18:00 |
Ventilation (simple):Fans:Electricity | 0.56 | 0.00 | 01-JAN-00:10 | 2305.29 | 26-JUN-18:00 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.56 | 0.00 | 01-JAN-00:10 | 2305.29 | 26-JUN-18:00 |
ElectricityPurchased:Facility | 712.30 | 4450.93 | 11-JUN-14:40 | 59944.56 | 04-AUG-14:50 |
ElectricityPurchased:Plant | 712.30 | 4450.93 | 11-JUN-14:40 | 59944.56 | 04-AUG-14:50 |
Cogeneration:ElectricityPurchased | 712.30 | 4450.93 | 11-JUN-14:40 | 59944.56 | 04-AUG-14:50 |
General:Cogeneration:ElectricityPurchased | 712.30 | 4450.93 | 11-JUN-14:40 | 59944.56 | 04-AUG-14:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 712.30 | 4450.93 | 11-JUN-14:40 | 59944.56 | 04-AUG-14:50 |
ElectricityNet:Plant | 712.30 | 4450.93 | 11-JUN-14:40 | 59944.56 | 04-AUG-14:50 |
Cogeneration:ElectricityNet | 712.30 | 4450.93 | 11-JUN-14:40 | 59944.56 | 04-AUG-14:50 |
General:Cogeneration:ElectricityNet | 712.30 | 4450.93 | 11-JUN-14:40 | 59944.56 | 04-AUG-14:50 |
Electricity:HVAC | 58.45 | 0.00 | 24-FEB-18:10 | 18249.12 | 04-AUG-15:40 |
General:Fans:Electricity | 43.49 | 0.00 | 24-FEB-18:10 | 4533.25 | 09-DEC-08:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 14.96 | 0.00 | 01-JAN-00:10 | 15377.93 | 04-AUG-15:40 |
General:Cooling:Electricity | 14.96 | 0.00 | 01-JAN-00:10 | 15377.93 | 04-AUG-15:40 |
ExteriorLights:Electricity | 92.71 | 0.00 | 01-JAN-08:00 | 6986.42 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 92.71 | 0.00 | 01-JAN-08:00 | 6986.42 | 01-JAN-06:10 |
Electricity:Plant | 26.78 | 481.00 | 02-JAN-06:40 | 2938.63 | 17-FEB-12:50 |
WaterSystems:Electricity | 26.78 | 481.00 | 02-JAN-06:40 | 2938.63 | 17-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 26.78 | 481.00 | 02-JAN-06:40 | 2938.63 | 17-FEB-12:50 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1656.82 | 0.00 | 24-FEB-18:10 | 493488.92 | 09-DEC-09:00 |
NaturalGas:HVAC | 1656.82 | 0.00 | 24-FEB-18:10 | 493488.92 | 09-DEC-09:00 |
Heating:NaturalGas | 1656.82 | 0.00 | 24-FEB-18:10 | 493488.92 | 09-DEC-09:00 |
General:Heating:NaturalGas | 1656.82 | 0.00 | 24-FEB-18:10 | 493488.92 | 09-DEC-09:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2662.59 | 0.00 | 24-FEB-18:10 | 776206.76 | 09-DEC-06:20 |
EnergyTransfer:Building | 1315.83 | 0.00 | 24-FEB-18:10 | 389535.66 | 09-DEC-06:20 |
EnergyTransfer:Zone:ZONE1 OFFICE | 81.83 | 0.00 | 01-JAN-00:40 | 30485.00 | 02-FEB-07:10 |
Heating:EnergyTransfer | 1252.30 | 0.00 | 24-FEB-18:10 | 389535.66 | 09-DEC-06:20 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 60.89 | 0.00 | 01-JAN-00:40 | 30485.00 | 02-FEB-07:10 |
General:Heating:EnergyTransfer | 1252.30 | 0.00 | 24-FEB-18:10 | 389535.66 | 09-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 60.89 | 0.00 | 01-JAN-00:40 | 30485.00 | 02-FEB-07:10 |
Cooling:EnergyTransfer | 63.52 | 0.00 | 01-JAN-00:10 | 34007.99 | 04-AUG-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 20.95 | 0.00 | 01-JAN-00:10 | 10739.82 | 14-SEP-17:30 |
General:Cooling:EnergyTransfer | 63.52 | 0.00 | 01-JAN-00:10 | 34007.99 | 04-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 20.95 | 0.00 | 01-JAN-00:10 | 10739.82 | 14-SEP-17:30 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 255.55 | 0.00 | 01-JAN-00:40 | 89949.62 | 09-DEC-02:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 212.97 | 0.00 | 01-JAN-00:40 | 89949.62 | 09-DEC-02:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 212.97 | 0.00 | 01-JAN-00:40 | 89949.62 | 09-DEC-02:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 42.58 | 0.00 | 01-JAN-00:10 | 25534.36 | 04-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 42.58 | 0.00 | 01-JAN-00:10 | 25534.36 | 04-AUG-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 978.45 | 0.00 | 12-JAN-12:40 | 285255.42 | 09-DEC-08:30 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 978.45 | 0.00 | 12-JAN-12:40 | 285255.42 | 09-DEC-08:30 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 978.45 | 0.00 | 12-JAN-12:40 | 285255.42 | 09-DEC-08:30 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1346.77 | 0.00 | 24-FEB-18:10 | 393498.47 | 09-DEC-09:00 |
HeatingCoils:EnergyTransfer | 1282.61 | 0.00 | 24-FEB-18:10 | 393498.47 | 09-DEC-09:00 |
CoolingCoils:EnergyTransfer | 64.16 | 0.00 | 01-JAN-00:10 | 60916.06 | 04-AUG-15:40 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 60.885 | -20.946 | 0.000 | 0.000 | 10.102 | 21.512 | 29.720 | 10.754 | 0.000 | 0.594 | 0.000 | 0.000 | -13.358 | 0.000 | -41.858 | -57.404 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 212.970 | -42.574 | 0.000 | 0.000 | 26.064 | 162.279 | 0.000 | 0.000 | 0.000 | 0.880 | 0.001 | 0.000 | 0.000 | 0.000 | -156.738 | -202.880 |
ZONE3 BULK STORAGE | 978.448 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 66.273 | 212.945 | 107.344 | 114.640 | 0.000 | 13.025 | 0.000 | 0.000 | -169.044 | 0.000 | -944.436 | -379.195 |
Total Facility | 978.448 | 0.000 | 273.855 | -63.520 | 0.000 | 0.000 | 102.439 | 396.736 | 137.063 | 125.395 | 0.000 | 14.498 | 0.002 | 0.000 | -182.402 | 0.000 | -1143.032 | -639.480 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 23-JUL-23:02 | 0.00 | 0.00 | 0.00 | -22090.41 | 0.00 | 0.00 | 0.00 | 368.99 | 488.55 | 0.00 | 0.00 | 0.00 | 21718.26 | 0.00 | -451.27 | 0.00 | -34.12 | 0.00 |
ZONE2 FINE STORAGE | 16-AUG-17:22 | 0.00 | 0.00 | 0.00 | -47666.30 | 0.00 | 0.00 | 0.00 | 1424.86 | 0.00 | 0.00 | 0.00 | 0.00 | 47132.20 | 0.00 | -0.00 | 0.00 | -890.77 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-JUL-17:08 | 0.00 | 0.00 | 0.00 | -58227.52 | 0.00 | 0.00 | 0.00 | 3558.75 | 2538.58 | 25331.90 | 0.00 | 146.03 | 30091.40 | 0.00 | 0.00 | 0.00 | -3439.15 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 02-FEB-06:31 | 0.00 | 0.00 | 33027.34 | 0.00 | 0.00 | 0.00 | 149.52 | 471.50 | 556.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2085.46 | 0.00 | -4076.76 | -28042.29 |
ZONE2 FINE STORAGE | 09-DEC-06:41 | 0.00 | 0.00 | 97639.45 | 0.00 | 0.00 | 0.00 | 401.21 | 1424.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -34237.75 | -65227.77 |
ZONE3 BULK STORAGE | 09-DEC-08:25 | 285857.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8477.35 | 15006.02 | 8200.12 | 0.00 | 0.00 | 0.00 | 1575.94 | 0.00 | -24261.44 | 0.00 | -294855.19 | 0.00 |
Total Facility | 09-DEC-06:11 | 282929.86 | 0.00 | 122435.13 | 0.00 | 0.00 | 0.00 | 1441.81 | 3897.16 | 2606.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19915.34 | 0.00 | -289035.98 | -104358.83 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1018 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.1018 | 0.0928 | 1.0000 | Not calculated | 0.1023 | 0.0928 | ||
PSZ-FINE STORAGE | 2.4688 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.4688 | 0.1720 | 1.0000 | Not calculated | 0.4247 | 0.1720 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1018 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.1018 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0928 | ||
PSZ-FINE STORAGE | 2.4688 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.4688 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1720 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1018 | 1.1018 | 1.1018 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4688 | 2.4688 | 2.4688 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1018 | 1.1018 | 1.1018 | 1.1018 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.4688 | 2.4688 | 2.4688 | 2.4688 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1018 | 1.1018 | 1.1018 | No | 0.1023 | 0.1993 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4688 | 2.4688 | 2.4688 | No | 0.4247 | 0.2487 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1018 | 1.1018 | 1.1018 | 1.1018 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.4688 | 2.4688 | 2.4688 | 2.4688 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 82.00 |
Number of hours cooling loads not met | 2.17 |
Number of hours not met | 84.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1656.82 | 493488.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 14.96 | 15377.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 396.74 | 30696.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 92.71 | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 137.06 | 10054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.56 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 43.49 | 4533.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.78 | 2938.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 137.06 | 712.30 |
Natural Gas | 0.00 | 1656.82 |
Additional | 0.00 | 0.00 |
Total | 137.06 | 2369.12 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 82.05 |
Space Heating | 0.00 |
Space Cooling | 3.09 |
Fans (All) | 9.11 |
Service Water Heating | 5.54 |
Receptacle Equipment | 28.35 |
Miscellaneous (All) | 147.32 |
Subtotal | 147.32 |
Natural Gas [MJ/m2] | |
Space Heating | 342.66 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 342.66 |
Subtotal | 342.66 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 16.75 |
Space Heating | 69.93 |
Space Cooling | 0.63 |
Fans (All) | 1.86 |
Service Water Heating | 1.13 |
Receptacle Equipment | 5.79 |
Miscellaneous | 3.91 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2970. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4378. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8635.17 | 124.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7935.50 | 824.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7813.83 | 910.00 | 36.17 | 0.00 | 0.00 |
Min | 7813.83 | 124.83 | 0.00 | 0.00 | 0.00 |
Max | 8635.17 | 910.00 | 36.17 | 0.00 | 0.00 |
Average | 8128.17 | 619.78 | 12.06 | 0.00 | 0.00 |
Sum | 24384.50 | 1859.33 | 36.17 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 67832.00 | 14887.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 160006.00 | 29681.50 | 1505.50 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 160006.00 | 29681.50 | 1505.50 | 0.00 | 0.00 |
Average | 86955.00 | 14856.17 | 501.83 | 0.00 | 0.00 |
Sum | 260865.00 | 44568.50 | 1505.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8330.83 | 429.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7212.33 | 1547.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7179.00 | 1564.33 | 16.67 | 0.00 | 0.00 |
Min | 7179.00 | 429.17 | 0.00 | 0.00 | 0.00 |
Max | 8330.83 | 1564.33 | 16.67 | 0.00 | 0.00 |
Average | 7574.06 | 1180.39 | 5.56 | 0.00 | 0.00 |
Sum | 22722.17 | 3541.17 | 16.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 31619.50 | 1407.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 64122.50 | 18596.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 149223.50 | 41177.00 | 792.50 | 0.00 | 0.00 |
Min | 31619.50 | 1407.50 | 0.00 | 0.00 | 0.00 |
Max | 149223.50 | 41177.00 | 792.50 | 0.00 | 0.00 |
Average | 81655.17 | 20393.67 | 264.17 | 0.00 | 0.00 |
Sum | 244965.50 | 61181.00 | 792.50 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 2920.00 | 0.00 |
Sum | 0.00 | 8760.00 | 8760.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 33027.00 | 0.00 |
Average | 0.00 | 63731.00 | 11009.00 | 0.00 |
Sum | 0.00 | 191193.00 | 33027.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -2.8 | -3.2 | 0.496891E+09 | 603.25 | 18-JAN-08:09 | -12.3 | -12.7 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -24.1 | -24.4 | 0.457200E+09 | 603.25 | 04-FEB-08:09 | -30.3 | -30.5 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -11.0 | -12.0 | 0.538169E+09 | 691.59 | 25-MAR-15:20 | 18.53 | 10.46 |
April | 0.235524E+09 | 14727.32 | 18-APR-18:15 | 22.80 | 16.71 | 0.520218E+09 | 769.02 | 18-APR-15:00 | 22.80 | 16.71 |
May | 0.777079E+09 | 16425.19 | 31-MAY-21:45 | 20.20 | 15.15 | 0.617700E+09 | 769.02 | 30-MAY-14:30 | 20.20 | 15.15 |
June | 0.434594E+10 | 20551.28 | 22-JUN-20:43 | 15.97 | 12.22 | 0.650540E+09 | 769.03 | 14-JUN-14:39 | 15.97 | 12.22 |
July | 0.606944E+10 | 22093.64 | 23-JUL-23:02 | 16.37 | 12.81 | 0.634578E+09 | 769.03 | 14-JUL-10:50 | 16.37 | 12.81 |
August | 0.616633E+10 | 20273.08 | 07-AUG-17:11 | 22.43 | 14.04 | 0.685218E+09 | 769.03 | 12-AUG-15:39 | 20.97 | 17.87 |
September | 0.328114E+10 | 21951.67 | 15-SEP-18:11 | 19.47 | 12.19 | 0.608303E+09 | 769.02 | 11-SEP-08:00 | 19.47 | 12.19 |
October | 69806133.90 | 1076.60 | 20-OCT-15:30 | 22.30 | 13.06 | 0.519804E+09 | 768.97 | 02-OCT-15:00 | 22.30 | 13.06 |
November | 2073660.47 | 264.19 | 04-NOV-17:00 | 7.80 | 3.63 | 0.485770E+09 | 762.16 | 03-NOV-15:09 | 7.80 | 3.63 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 | -1.3 | 0.496943E+09 | 603.25 | 09-DEC-08:50 | -22.8 | -23.0 |
Annual Sum or Average | 0.209473E+11 | 0.671133E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -24.1 | -24.4 | 0.457200E+09 | 603.25 | -30.3 | -30.5 | ||
Maximum of Months | 0.616633E+10 | 22093.64 | 22.80 | 16.71 | 0.685218E+09 | 769.03 | 22.80 | 17.87 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.175337E+09 | 5562.98 | 12-JAN-13:10 | 2.20 | 0.51 | 0.649044E+09 | 812.78 | 13-JAN-14:00 | 3.90 | 1.72 |
February | 0.570982E+09 | 5802.08 | 21-FEB-14:30 | -0.6 | -2.8 | 0.601884E+09 | 999.19 | 24-FEB-15:39 | 8.30 | 5.79 |
March | 0.150265E+10 | 7043.32 | 21-MAR-14:00 | -0.6 | -4.2 | 0.746518E+09 | 1309.23 | 25-MAR-15:09 | 18.72 | 10.45 |
April | 0.240067E+10 | 7377.29 | 21-APR-13:00 | -1.1 | -1.6 | 0.875348E+09 | 2246.80 | 18-APR-15:30 | -1.1 | -1.6 |
May | 0.208769E+10 | 9919.44 | 31-MAY-15:10 | 29.72 | 19.55 | 0.133960E+10 | 2246.80 | 31-MAY-10:09 | 29.72 | 19.55 |
June | 0.749002E+10 | 44035.64 | 25-JUN-16:33 | 31.87 | 21.81 | 0.175254E+10 | 2246.95 | 29-JUN-12:09 | 27.88 | 20.57 |
July | 0.101195E+11 | 45926.46 | 02-JUL-16:03 | 29.32 | 21.36 | 0.182503E+10 | 2246.97 | 28-JUL-14:30 | 26.10 | 19.37 |
August | 0.887983E+10 | 47668.28 | 16-AUG-17:22 | 23.05 | 15.39 | 0.196185E+10 | 2246.96 | 01-AUG-13:09 | 23.05 | 15.39 |
September | 0.525947E+10 | 33870.31 | 08-SEP-17:10 | 28.43 | 18.19 | 0.151982E+10 | 2246.94 | 08-SEP-12:09 | 28.43 | 18.19 |
October | 0.260922E+10 | 6169.04 | 23-OCT-08:20 | 1.00 | -0.9 | 0.871265E+09 | 1624.19 | 20-OCT-15:09 | 1.00 | -0.9 |
November | 0.120891E+10 | 5821.98 | 09-NOV-16:00 | 2.20 | 0.43 | 0.709303E+09 | 1421.66 | 03-NOV-14:50 | 2.20 | 0.43 |
December | 0.271053E+09 | 6934.92 | 04-DEC-11:55 | -1.7 | -3.2 | 0.649690E+09 | 863.04 | 02-DEC-15:39 | -1.7 | -3.2 |
Annual Sum or Average | 0.425753E+11 | 0.135019E+11 | ||||||||
Minimum of Months | 0.175337E+09 | 5562.98 | -1.7 | -4.2 | 0.601884E+09 | 812.78 | -1.7 | -3.2 | ||
Maximum of Months | 0.101195E+11 | 47668.28 | 31.87 | 21.81 | 0.196185E+10 | 2246.97 | 29.72 | 20.57 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -2.8 | -3.2 | 0.644085E+09 | 806.32 | 12-JAN-13:30 | 2.20 | 0.51 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -24.1 | -24.4 | 0.601200E+09 | 1118.44 | 24-FEB-15:20 | 8.30 | 5.71 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -11.0 | -12.0 | 0.798320E+09 | 1809.93 | 25-MAR-15:30 | 18.35 | 10.46 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.2 | 0.121733E+10 | 4375.84 | 18-APR-15:09 | 27.75 | 20.46 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 | 5.15 | 0.232187E+10 | 5101.32 | 31-MAY-15:20 | 29.43 | 19.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.69 | 0.389888E+10 | 7040.90 | 26-JUN-14:20 | 31.50 | 22.02 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.94 | 0.456784E+10 | 6651.95 | 03-JUL-15:09 | 29.82 | 24.29 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 | 17.82 | 0.474485E+10 | 8000.79 | 04-AUG-15:39 | 33.90 | 26.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 | 0.328620E+10 | 6564.07 | 08-SEP-14:30 | 30.30 | 19.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.39 | 0.118839E+10 | 2375.85 | 02-OCT-15:30 | 17.45 | 14.25 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.5 | 0.818672E+09 | 1965.05 | 03-NOV-14:50 | 16.10 | 9.74 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 | -1.3 | 0.639522E+09 | 902.29 | 02-DEC-15:50 | 5.68 | 3.15 |
Annual Sum or Average | 0.00 | 0.247272E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -24.1 | -24.4 | 0.601200E+09 | 806.32 | 2.20 | 0.51 | ||
Maximum of Months | 0.00 | 0.00 | 18.93 | 17.82 | 0.474485E+10 | 8000.79 | 33.90 | 26.00 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149786E+11 | 32989.46 | 27-JAN-06:31 | -17.9 |
February | 0.113505E+11 | 33027.24 | 02-FEB-06:31 | -36.7 |
March | 0.867373E+10 | 30556.08 | 06-MAR-06:41 | -13.1 |
April | 0.422995E+10 | 30330.36 | 03-APR-05:32 | -7.2 |
May | 0.860479E+09 | 29934.41 | 02-MAY-05:01 | 2.20 |
June | 0.127181E+09 | 29442.26 | 05-JUN-05:01 | 9.32 |
July | 18852052.48 | 1595.53 | 20-JUL-06:05 | 19.50 |
August | 45758175.83 | 1439.30 | 07-AUG-06:10 | 8.87 |
September | 0.354044E+09 | 29883.43 | 29-SEP-05:01 | 0.92 |
October | 0.221898E+10 | 30019.84 | 17-OCT-05:12 | 0.83 |
November | 0.661321E+10 | 30468.33 | 24-NOV-06:11 | -13.5 |
December | 0.114138E+11 | 30543.75 | 11-DEC-06:21 | -21.9 |
Annual Sum or Average | 0.608852E+11 | |||
Minimum of Months | 18852052.48 | 1439.30 | -36.7 | |
Maximum of Months | 0.149786E+11 | 33027.24 | 19.50 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.589353E+11 | 96588.12 | 19-JAN-06:41 | -27.8 |
February | 0.411532E+11 | 96218.31 | 02-FEB-06:01 | -36.7 |
March | 0.252046E+11 | 93058.67 | 05-MAR-10:02 | -8.8 |
April | 0.980218E+10 | 92952.59 | 03-APR-02:22 | -6.1 |
May | 0.743346E+09 | 69133.27 | 02-MAY-05:21 | 2.20 |
June | 60374570.45 | 1141.89 | 14-JUN-07:00 | 17.80 |
July | 54728684.08 | 982.45 | 20-JUL-07:00 | 20.00 |
August | 63584893.49 | 1010.72 | 25-AUG-07:00 | 13.90 |
September | 0.269608E+09 | 33721.61 | 29-SEP-05:36 | 0.37 |
October | 0.459763E+10 | 80956.32 | 26-OCT-05:01 | -0.8 |
November | 0.251115E+11 | 92977.83 | 28-NOV-22:02 | -7.4 |
December | 0.469740E+11 | 97639.43 | 09-DEC-06:41 | -22.8 |
Annual Sum or Average | 0.212970E+12 | |||
Minimum of Months | 54728684.08 | 982.45 | -36.7 | |
Maximum of Months | 0.589353E+11 | 97639.43 | 20.00 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.301294E+12 | 283518.63 | 18-JAN-19:50 | -17.8 |
February | 0.201121E+12 | 267672.07 | 01-FEB-21:00 | -28.9 |
March | 0.105556E+12 | 191249.53 | 06-MAR-08:70 | -11.8 |
April | 0.231121E+11 | 112023.40 | 02-APR-23:55 | -5.6 |
May | 0.304079E+09 | 16597.11 | 02-MAY-02:55 | 2.80 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.295226E+10 | 25853.40 | 24-OCT-05:53 | 2.20 |
November | 0.113906E+12 | 185405.90 | 26-NOV-04:00 | -25.0 |
December | 0.230203E+12 | 285857.18 | 09-DEC-08:25 | -22.8 |
Annual Sum or Average | 0.978449E+12 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.301294E+12 | 285857.18 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187483E+10 | 1578.50 | 02-JAN-08:09 | 0.248944E+10 | 1853.89 | 02-JAN-08:09 |
February | 0.167701E+10 | 1578.50 | 11-FEB-16:00 | 0.226834E+10 | 1853.89 | 01-FEB-08:09 |
March | 0.186293E+10 | 1520.62 | 01-MAR-16:00 | 0.258391E+10 | 1853.89 | 01-MAR-08:09 |
April | 0.174878E+10 | 1520.62 | 10-APR-07:10 | 0.244723E+10 | 1853.89 | 01-APR-07:10 |
May | 0.177549E+10 | 1346.99 | 02-MAY-07:10 | 0.253668E+10 | 1853.89 | 01-MAY-07:10 |
June | 0.173681E+10 | 1404.87 | 05-JUN-07:10 | 0.249447E+10 | 1853.89 | 01-JUN-07:10 |
July | 0.173430E+10 | 1404.87 | 08-JUL-07:10 | 0.248944E+10 | 1853.89 | 01-JUL-07:10 |
August | 0.181977E+10 | 1404.87 | 16-AUG-07:10 | 0.258391E+10 | 1853.89 | 01-AUG-07:10 |
September | 0.174982E+10 | 1520.62 | 21-SEP-07:10 | 0.244723E+10 | 1853.89 | 01-SEP-07:10 |
October | 0.181194E+10 | 1578.50 | 21-OCT-07:10 | 0.248944E+10 | 1853.89 | 02-OCT-07:10 |
November | 0.179689E+10 | 1578.50 | 01-NOV-07:10 | 0.239999E+10 | 1853.89 | 01-NOV-07:10 |
December | 0.192298E+10 | 1578.50 | 01-DEC-16:30 | 0.248944E+10 | 1853.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.215115E+11 | 0.297195E+11 | ||||
Minimum of Months | 0.167701E+10 | 1346.99 | 0.226834E+10 | 1853.89 | ||
Maximum of Months | 0.192298E+10 | 1578.50 | 0.258391E+10 | 1853.89 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.134983E+11 | 12111.30 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.123544E+11 | 12111.30 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.142728E+11 | 12111.30 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.133752E+11 | 12111.30 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.138855E+11 | 12111.30 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.137624E+11 | 12111.30 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.134983E+11 | 12111.30 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.142728E+11 | 12111.30 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.133752E+11 | 12111.30 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.134983E+11 | 12111.30 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.129879E+11 | 12111.30 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.134983E+11 | 12111.30 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.162279E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.123544E+11 | 12111.30 | 0.00 | 0.00 | |
Maximum of Months | 0.142728E+11 | 12111.30 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.183400E+11 | 17006.82 | 02-JAN-10:30 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.166134E+11 | 17006.82 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.186243E+11 | 17006.82 | 13-MAR-08:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.172592E+11 | 16349.22 | 01-APR-08:20 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.177151E+11 | 15691.63 | 04-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.174908E+11 | 15691.63 | 05-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.172067E+11 | 15691.63 | 06-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.182561E+11 | 16349.22 | 29-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.173770E+11 | 16349.22 | 21-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.179446E+11 | 17006.82 | 20-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.174849E+11 | 17006.82 | 04-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.186333E+11 | 17006.82 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.212945E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.166134E+11 | 15691.63 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.186333E+11 | 17006.82 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.187483E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.819396E+10 |
February | 0.127628E+10 | 0.167701E+10 | 0.226834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611450E+10 |
March | 0.149825E+10 | 0.186293E+10 | 0.258391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 432905.01 | 0.504518E+10 |
April | 0.138726E+10 | 0.174878E+10 | 0.244723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39611663.60 | 0.290592E+10 |
May | 0.144276E+10 | 0.177549E+10 | 0.253668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33715733.74 | 0.157910E+10 |
June | 0.144276E+10 | 0.173681E+10 | 0.249447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154425E+09 | 0.928657E+09 |
July | 0.138726E+10 | 0.173430E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112739E+09 | 0.588060E+09 |
August | 0.149825E+10 | 0.181977E+10 | 0.258391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159741E+09 | 0.846485E+09 |
September | 0.138726E+10 | 0.174982E+10 | 0.244723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92850470.38 | 0.153774E+10 |
October | 0.138726E+10 | 0.181194E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263279E+10 |
November | 0.133177E+10 | 0.179689E+10 | 0.239999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475429E+10 |
December | 0.138726E+10 | 0.192298E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673128E+10 |
Annual Sum or Average | 0.168137E+11 | 0.215115E+11 | 0.297195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593516E+09 | 0.418580E+11 |
Minimum of Months | 0.127628E+10 | 0.167701E+10 | 0.226834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588060E+09 |
Maximum of Months | 0.149825E+10 | 0.192298E+10 | 0.258391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159741E+09 | 0.819396E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.134983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309785E+11 |
February | 0.300332E+10 | 0.123544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226894E+11 |
March | 0.352563E+10 | 0.142728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7903414.34 | 0.177865E+11 |
April | 0.326447E+10 | 0.133752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174032E+09 | 0.969734E+10 |
May | 0.339505E+10 | 0.138855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43277386.52 | 0.530611E+10 |
June | 0.339505E+10 | 0.137624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338528E+09 | 0.412633E+10 |
July | 0.326447E+10 | 0.134983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85499162.11 | 0.344537E+10 |
August | 0.352563E+10 | 0.142728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130580E+09 | 0.469865E+10 |
September | 0.326447E+10 | 0.133752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99162588.49 | 0.597918E+10 |
October | 0.326447E+10 | 0.134983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 637680.23 | 0.835934E+10 |
November | 0.313390E+10 | 0.129879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179122E+11 |
December | 0.326447E+10 | 0.134983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257586E+11 |
Annual Sum or Average | 0.395654E+11 | 0.162279E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.879621E+09 | 0.156738E+12 |
Minimum of Months | 0.300332E+10 | 0.123544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344537E+10 |
Maximum of Months | 0.352563E+10 | 0.142728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338528E+09 | 0.309785E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.183400E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142135E+12 |
February | 0.690763E+10 | 0.166134E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.988078E+11 |
March | 0.810895E+10 | 0.186243E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.921547E+09 | 0.673329E+11 |
April | 0.750829E+10 | 0.172592E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383392E+10 | 0.334004E+11 |
May | 0.780862E+10 | 0.177151E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175909E+10 | 0.176333E+11 |
June | 0.780862E+10 | 0.174908E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107470E+10 | 0.198101E+11 |
July | 0.750829E+10 | 0.172067E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8451699.32 | 0.212944E+11 |
August | 0.810895E+10 | 0.182561E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42332031.84 | 0.258766E+11 |
September | 0.750829E+10 | 0.173770E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260674E+09 | 0.279404E+11 |
October | 0.750829E+10 | 0.179446E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.823210E+09 | 0.253229E+11 |
November | 0.720796E+10 | 0.174849E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98084651.78 | 0.696172E+11 |
December | 0.750829E+10 | 0.186333E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111540E+12 |
Annual Sum or Average | 0.910005E+11 | 0.212945E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.882202E+10 | 0.660712E+12 |
Minimum of Months | 0.690763E+10 | 0.166134E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176333E+11 |
Maximum of Months | 0.810895E+10 | 0.186333E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383392E+10 | 0.142135E+12 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1578.50 | 02-JAN-08:09 | 1853.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 19449.20 | 18-JAN-18:00 |
February | 1680.92 | 01-FEB-08:09 | 1578.50 | 11-FEB-16:00 | 1853.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 19069.32 | 02-FEB-08:00 |
March | 1680.92 | 01-MAR-08:09 | 1520.62 | 01-MAR-16:00 | 1853.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 69.83 | 19-MAR-14:00 | 14166.26 | 06-MAR-08:00 |
April | 1680.92 | 01-APR-07:10 | 1520.62 | 10-APR-07:10 | 1853.89 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1101.31 | 15-APR-17:00 | 9781.10 | 03-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 1346.99 | 02-MAY-07:10 | 1853.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1372.00 | 31-MAY-17:00 | 6080.15 | 02-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 1404.87 | 05-JUN-07:10 | 1853.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2064.90 | 26-JUN-16:10 | 4367.20 | 02-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 1404.87 | 08-JUL-07:10 | 1853.89 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1820.90 | 25-JUL-16:10 | 2964.77 | 24-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 1404.87 | 16-AUG-07:10 | 1853.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2478.83 | 04-AUG-16:10 | 3904.30 | 07-AUG-06:10 |
September | 1680.92 | 01-SEP-07:10 | 1520.62 | 21-SEP-07:10 | 1853.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2050.48 | 06-SEP-16:10 | 6040.26 | 29-SEP-06:10 |
October | 1680.92 | 02-OCT-07:10 | 1578.50 | 21-OCT-07:10 | 1853.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 7354.91 | 24-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 1578.50 | 01-NOV-07:10 | 1853.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 11990.33 | 24-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1578.50 | 01-DEC-16:30 | 1853.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 18326.19 | 08-DEC-17:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1346.99 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2964.77 | |||||
Maximum of Months | 1680.92 | 1578.50 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 2478.83 | 19449.20 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 12111.30 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 53391.50 | 18-JAN-18:00 |
February | 3955.50 | 01-FEB-08:09 | 12111.30 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 33244.30 | 04-FEB-18:00 |
March | 3955.50 | 01-MAR-08:09 | 12111.30 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 762.46 | 19-MAR-16:00 | 32673.63 | 06-MAR-08:00 |
April | 3955.50 | 01-APR-07:10 | 12111.30 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4551.27 | 15-APR-17:00 | 20410.75 | 25-APR-06:08 |
May | 3955.50 | 01-MAY-07:10 | 12111.30 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1411.02 | 31-MAY-15:10 | 8666.90 | 02-MAY-02:47 |
June | 3955.50 | 01-JUN-07:10 | 12111.30 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4355.47 | 11-JUN-15:00 | 8919.65 | 02-JUN-08:00 |
July | 3955.50 | 01-JUL-07:10 | 12111.30 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2374.13 | 25-JUL-16:00 | 6251.13 | 10-JUL-15:10 |
August | 3955.50 | 01-AUG-07:10 | 12111.30 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2967.70 | 04-AUG-16:20 | 6783.88 | 30-AUG-15:10 |
September | 3955.50 | 01-SEP-07:10 | 12111.30 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2596.44 | 06-SEP-15:40 | 8361.52 | 18-SEP-23:00 |
October | 3955.50 | 02-OCT-07:10 | 12111.30 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.27 | 20-OCT-15:10 | 13974.88 | 24-OCT-06:10 |
November | 3955.50 | 01-NOV-07:10 | 12111.30 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 29671.83 | 25-NOV-16:10 |
December | 3955.50 | 01-DEC-08:09 | 12111.30 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 58916.11 | 09-DEC-08:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 12111.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6251.13 | ||||
Maximum of Months | 3955.50 | 12111.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4551.27 | 58916.11 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 17006.82 | 02-JAN-10:30 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 193550.18 | 18-JAN-16:00 |
February | 9097.65 | 01-FEB-08:09 | 17006.82 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 137023.14 | 28-FEB-10:00 |
March | 9097.65 | 01-MAR-08:09 | 17006.82 | 13-MAR-08:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18238.10 | 25-MAR-15:00 | 124911.23 | 06-MAR-08:70 |
April | 9097.65 | 01-APR-07:10 | 16349.22 | 01-APR-08:20 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42422.26 | 15-APR-15:00 | 59362.65 | 02-APR-23:55 |
May | 9097.65 | 01-MAY-07:10 | 15691.63 | 04-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26320.40 | 04-MAY-14:00 | 41389.93 | 13-MAY-12:55 |
June | 9097.65 | 01-JUN-07:10 | 15691.63 | 05-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19572.10 | 11-JUN-15:00 | 37744.72 | 02-JUN-08:00 |
July | 9097.65 | 01-JUL-07:10 | 15691.63 | 06-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1673.62 | 25-JUL-16:00 | 35603.17 | 10-JUL-14:00 |
August | 9097.65 | 01-AUG-07:10 | 16349.22 | 29-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2410.92 | 21-AUG-13:00 | 33871.80 | 30-AUG-14:55 |
September | 9097.65 | 01-SEP-07:10 | 16349.22 | 21-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9196.09 | 06-SEP-14:00 | 37843.09 | 18-SEP-16:00 |
October | 9097.65 | 02-OCT-07:10 | 17006.82 | 20-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17094.38 | 20-OCT-15:00 | 34510.70 | 24-OCT-07:10 |
November | 9097.65 | 01-NOV-07:10 | 17006.82 | 04-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9416.23 | 20-NOV-10:00 | 134634.92 | 25-NOV-11:00 |
December | 9097.65 | 01-DEC-08:09 | 17006.82 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 229982.21 | 09-DEC-08:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 15691.63 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33871.80 | |||||
Maximum of Months | 9097.65 | 17006.82 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 42422.26 | 229982.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 1844.97 | 2442.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1232.35 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 2582.96 | 3419.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2471.47 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 2582.96 | 3419.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2778.24 |
April | 14727.32 | 18-APR-18:15 | 0.00 | 656.81 | 977.10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.83 | 0.00 |
May | 16425.19 | 31-MAY-21:45 | 0.00 | 737.99 | 977.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.05 |
June | 20551.28 | 22-JUN-20:43 | 0.00 | 1106.98 | 1465.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.68 |
July | 22093.64 | 23-JUL-23:02 | 0.00 | 2213.97 | 2931.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.12 |
August | 20273.08 | 07-AUG-17:11 | 0.00 | 2878.16 | 4885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.37 |
September | 21951.67 | 15-SEP-18:11 | 0.00 | 3689.95 | 4885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.01 |
October | 1076.60 | 20-OCT-15:30 | 1680.92 | 1231.23 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.36 |
November | 264.19 | 04-NOV-17:00 | 1075.79 | 2500.99 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 747.85 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1475.98 | 1954.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1313.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 656.81 | 977.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22093.64 | 1680.92 | 3689.95 | 4885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 33.83 | 2778.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5562.98 | 12-JAN-13:10 | 3955.50 | 12111.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2011.15 |
February | 5802.08 | 21-FEB-14:30 | 3955.50 | 12111.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2715.61 |
March | 7043.32 | 21-MAR-14:00 | 3955.50 | 12111.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4295.96 |
April | 7377.29 | 21-APR-13:00 | 3955.50 | 12111.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4144.75 |
May | 9919.44 | 31-MAY-15:10 | 3955.50 | 10686.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1411.02 | 0.00 |
June | 44035.64 | 25-JUN-16:33 | 0.00 | 4274.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3410.68 | 0.00 |
July | 45926.46 | 02-JUL-16:03 | 0.00 | 4274.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1015.05 | 0.00 |
August | 47668.28 | 16-AUG-17:22 | 0.00 | 12823.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 890.77 |
September | 33870.31 | 08-SEP-17:10 | 0.00 | 5699.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 687.03 | 0.00 |
October | 6169.04 | 23-OCT-08:20 | 3955.50 | 12111.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2125.74 |
November | 5821.98 | 09-NOV-16:00 | 3955.50 | 12111.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7392.64 |
December | 6934.92 | 04-DEC-11:55 | 7911.00 | 24222.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4158.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5562.98 | 0.00 | 4274.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 47668.28 | 7911.00 | 24222.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3410.68 | 7392.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 10004.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24532.35 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 14005.62 | 14350.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60205.97 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 14005.62 | 14350.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62313.18 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11316.13 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 4001.60 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6774.47 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9400.46 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8609.91 |
August | 0.00 | 01-AUG-00:05 | 0.00 | 4001.60 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9702.78 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12021.51 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2000.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10727.42 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7655.20 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 8003.21 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25208.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 2000.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6774.47 | |
Maximum of Months | 0.00 | 0.00 | 14005.62 | 14350.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62313.18 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.635393E+11 | 50073.98 | 18-JAN-16:00 | 0.495028E+12 | 492121.10 | 18-JAN-17:00 |
February | 0.565940E+11 | 46459.96 | 02-FEB-15:00 | 0.335372E+12 | 427588.37 | 01-FEB-20:00 |
March | 0.620711E+11 | 45496.32 | 13-MAR-08:30 | 0.185706E+12 | 335500.53 | 06-MAR-08:09 |
April | 0.558321E+11 | 46316.37 | 18-APR-14:00 | 0.503526E+11 | 193781.89 | 03-APR-05:49 |
May | 0.560749E+11 | 48745.44 | 31-MAY-14:00 | 0.229145E+10 | 57325.59 | 02-MAY-05:10 |
June | 0.582089E+11 | 55391.64 | 27-JUN-14:39 | 84017482.33 | 8479.86 | 05-JUN-05:10 |
July | 0.593460E+11 | 56625.09 | 03-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.624572E+11 | 59944.56 | 04-AUG-14:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.573760E+11 | 53368.93 | 08-SEP-14:20 | 0.742932E+09 | 27540.18 | 30-SEP-05:19 |
October | 0.581377E+11 | 44543.44 | 27-OCT-08:09 | 0.136588E+11 | 68685.94 | 24-OCT-05:00 |
November | 0.589721E+11 | 49763.51 | 25-NOV-16:49 | 0.192280E+12 | 315709.38 | 25-NOV-17:00 |
December | 0.636883E+11 | 50126.62 | 09-DEC-16:00 | 0.381308E+12 | 493488.92 | 09-DEC-08:00 |
Annual Sum or Average | 0.712297E+12 | 0.165682E+13 | ||||
Minimum of Months | 0.558321E+11 | 44543.44 | 0.00 | 0.00 | ||
Maximum of Months | 0.636883E+11 | 59944.56 | 0.495028E+12 | 493488.92 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.337131E+11 | 0.101238E+11 | 0.113456E+11 | 0.00 | 0.600370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235313E+10 | 0.00 |
February | 0.306448E+11 | 0.833291E+10 | 0.104160E+11 | 0.00 | 0.504083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215946E+10 | 0.00 |
March | 0.347600E+11 | 0.810335E+10 | 0.121559E+11 | 0.00 | 0.461671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243508E+10 | 0.00 |
April | 0.323831E+11 | 0.669176E+10 | 0.113034E+11 | 0.00 | 0.308860E+10 | 0.00 | 0.00 | 89394984.80 | 0.00 | 0.00 | 0.00 | 0.227581E+10 | 0.00 |
May | 0.333761E+11 | 0.597129E+10 | 0.117471E+11 | 0.00 | 0.240028E+10 | 0.00 | 0.00 | 0.285972E+09 | 0.00 | 0.00 | 0.00 | 0.229416E+10 | 0.00 |
June | 0.329900E+11 | 0.533417E+10 | 0.117048E+11 | 0.00 | 0.274016E+10 | 0.00 | 0.00 | 0.325902E+10 | 0.00 | 0.00 | 0.00 | 0.218068E+10 | 0.00 |
July | 0.324393E+11 | 0.567708E+10 | 0.113456E+11 | 0.00 | 0.269510E+10 | 0.00 | 0.00 | 0.504191E+10 | 0.00 | 0.00 | 0.00 | 0.214701E+10 | 0.00 |
August | 0.343487E+11 | 0.647272E+10 | 0.121485E+11 | 0.00 | 0.281072E+10 | 0.00 | 0.00 | 0.449270E+10 | 0.00 | 0.00 | 0.00 | 0.218381E+10 | 0.00 |
September | 0.325019E+11 | 0.732893E+10 | 0.112960E+11 | 0.00 | 0.236273E+10 | 0.00 | 0.00 | 0.179226E+10 | 0.00 | 0.00 | 0.00 | 0.209417E+10 | 0.00 |
October | 0.332548E+11 | 0.876147E+10 | 0.113530E+11 | 0.00 | 0.257902E+10 | 0.00 | 0.00 | 1750394.36 | 0.00 | 0.00 | 0.00 | 0.218770E+10 | 0.00 |
November | 0.322697E+11 | 0.950450E+10 | 0.109019E+11 | 0.00 | 0.412876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216732E+10 | 0.00 |
December | 0.340545E+11 | 0.104047E+11 | 0.113456E+11 | 0.00 | 0.557795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230554E+10 | 0.00 |
Annual Sum or Average | 0.396736E+12 | 0.927067E+11 | 0.137063E+12 | 0.00 | 0.440446E+11 | 0.00 | 0.00 | 0.149630E+11 | 0.00 | 0.00 | 0.00 | 0.267839E+11 | 0.00 |
Minimum of Months | 0.306448E+11 | 0.533417E+10 | 0.104160E+11 | 0.00 | 0.236273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209417E+10 | 0.00 |
Maximum of Months | 0.347600E+11 | 0.104047E+11 | 0.121559E+11 | 0.00 | 0.600370E+10 | 0.00 | 0.00 | 0.504191E+10 | 0.00 | 0.00 | 0.00 | 0.243508E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.495028E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.335372E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.185706E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.503526E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.229145E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 84017482.33 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.742932E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.136588E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.192280E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.381308E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.165682E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.495028E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 30638.74 | 10-JAN-15:30 | 6986.42 | 01-JAN-06:10 | 10054.01 | 02-JAN-08:09 | 0.00 | 4364.12 | 18-JAN-17:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 30580.87 | 08-FEB-09:09 | 6986.42 | 01-FEB-06:10 | 10054.01 | 01-FEB-08:09 | 0.00 | 4251.71 | 02-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 30522.99 | 13-MAR-08:09 | 6986.42 | 01-MAR-06:10 | 10054.01 | 01-MAR-08:09 | 0.00 | 3911.38 | 06-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 29865.39 | 01-APR-08:20 | 6986.42 | 01-APR-05:10 | 10054.01 | 01-APR-07:10 | 0.00 | 3498.29 | 03-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 29092.04 | 04-MAY-08:09 | 6986.42 | 01-MAY-19:10 | 10054.01 | 01-MAY-07:10 | 0.00 | 3126.73 | 02-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 29149.92 | 05-JUN-08:09 | 6986.42 | 01-JUN-19:40 | 10054.01 | 01-JUN-07:10 | 0.00 | 4602.20 | 30-JUN-14:39 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 29149.92 | 08-JUL-08:20 | 6986.42 | 01-JUL-19:00 | 10054.01 | 01-JUL-07:10 | 0.00 | 4714.82 | 03-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 29749.63 | 29-AUG-08:09 | 6986.42 | 01-AUG-19:40 | 10054.01 | 01-AUG-07:10 | 0.00 | 5180.42 | 04-AUG-15:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 29865.39 | 21-SEP-08:09 | 6986.42 | 01-SEP-05:10 | 10054.01 | 01-SEP-07:10 | 0.00 | 4581.86 | 08-SEP-14:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 30522.99 | 20-OCT-08:09 | 6986.42 | 01-OCT-05:10 | 10054.01 | 02-OCT-07:10 | 0.00 | 3193.75 | 24-OCT-06:19 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 30638.74 | 08-NOV-15:30 | 6986.42 | 01-NOV-05:10 | 10054.01 | 01-NOV-07:10 | 0.00 | 3954.24 | 25-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 30696.62 | 08-DEC-15:50 | 6986.42 | 01-DEC-06:10 | 10054.01 | 01-DEC-08:09 | 0.00 | 4533.25 | 09-DEC-08:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 29092.04 | 6986.42 | 10054.01 | 0.00 | 3126.73 | 0.00 | 0.00 | |||||
Maximum of Months | 30696.62 | 6986.42 | 10054.01 | 0.00 | 5180.42 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2912.41 | 30-JAN-12:20 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2938.63 | 17-FEB-12:50 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2932.45 | 01-MAR-12:20 | 0.00 |
April | 3767.67 | 18-APR-14:00 | 0.00 | 0.00 | 0.00 | 2836.42 | 01-APR-11:50 | 0.00 |
May | 6271.90 | 31-MAY-15:09 | 0.00 | 0.00 | 0.00 | 2636.71 | 01-MAY-11:00 | 0.00 |
June | 10886.74 | 26-JUN-15:00 | 0.00 | 0.00 | 0.00 | 2342.13 | 02-JUN-11:50 | 0.00 |
July | 11698.04 | 03-JUL-14:00 | 0.00 | 0.00 | 0.00 | 2044.21 | 03-JUL-11:00 | 0.00 |
August | 15377.93 | 04-AUG-15:39 | 0.00 | 0.00 | 0.00 | 1824.78 | 31-AUG-11:00 | 0.00 |
September | 9265.79 | 11-SEP-17:19 | 0.00 | 0.00 | 0.00 | 1967.61 | 28-SEP-11:50 | 0.00 |
October | 414.85 | 20-OCT-14:00 | 0.00 | 0.00 | 0.00 | 2226.96 | 28-OCT-11:39 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2541.56 | 30-NOV-12:30 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2766.76 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1824.78 | 0.00 | ||
Maximum of Months | 15377.93 | 0.00 | 0.00 | 0.00 | 2938.63 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 50073.98 | 18-JAN-16:00 | 27270.96 | 10054.01 | 6986.42 | 0.00 | 4134.36 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 46459.96 | 02-FEB-15:00 | 30349.35 | 10054.01 | 0.00 | 0.00 | 3602.37 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 45496.32 | 13-MAR-08:30 | 30522.99 | 10054.01 | 0.00 | 0.00 | 3204.99 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 46316.37 | 18-APR-14:00 | 28376.56 | 10054.01 | 0.00 | 0.00 | 2276.56 | 0.00 | 0.00 | 3767.67 | 0.00 |
May | 48745.44 | 31-MAY-14:00 | 28376.56 | 10054.01 | 0.00 | 0.00 | 2276.56 | 0.00 | 0.00 | 6231.93 | 0.00 |
June | 55391.64 | 27-JUN-14:39 | 28376.56 | 10054.01 | 0.00 | 0.00 | 4588.07 | 0.00 | 0.00 | 10587.24 | 0.00 |
July | 56625.09 | 03-JUL-14:00 | 28376.56 | 10054.01 | 0.00 | 0.00 | 4714.82 | 0.00 | 0.00 | 11698.04 | 0.00 |
August | 59944.56 | 04-AUG-14:50 | 28376.56 | 10054.01 | 0.00 | 0.00 | 5101.72 | 0.00 | 0.00 | 14644.45 | 0.00 |
September | 53368.93 | 08-SEP-14:20 | 28376.56 | 10054.01 | 0.00 | 0.00 | 4581.86 | 0.00 | 0.00 | 8587.93 | 0.00 |
October | 44543.44 | 27-OCT-08:09 | 30522.99 | 10054.01 | 0.00 | 0.00 | 2286.98 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 49763.51 | 25-NOV-16:49 | 27270.96 | 10054.01 | 6986.42 | 0.00 | 3834.03 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 50126.62 | 09-DEC-16:00 | 27270.96 | 10054.01 | 6986.42 | 0.00 | 4193.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 44543.44 | 27270.96 | 10054.01 | 0.00 | 0.00 | 2276.56 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 59944.56 | 30522.99 | 10054.01 | 6986.42 | 0.00 | 5101.72 | 0.00 | 0.00 | 14644.45 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 492121.10 | 18-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 427588.37 | 01-FEB-20:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 335500.53 | 06-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 193781.89 | 03-APR-05:49 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 57325.59 | 02-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 8479.86 | 05-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 27540.18 | 30-SEP-05:19 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 68685.94 | 24-OCT-05:00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 315709.38 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 493488.92 | 09-DEC-08:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 493488.92 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 86.50 | 15.12 | 9.83 | 15.49 | 0.00 | 15.49 | 0.00 | 15.49 |
February | 53.17 | 15.46 | 9.33 | 16.00 | 0.00 | 16.00 | 0.00 | 16.00 |
March | 31.50 | 16.26 | 10.17 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 |
April | 12.67 | 17.77 | 8.00 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
May | 2.83 | 19.92 | 2.83 | 19.92 | 0.33 | 20.18 | 0.00 | 20.18 |
June | 0.17 | 20.43 | 0.17 | 20.43 | 10.67 | 24.46 | 0.17 | 24.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 24.59 | 0.83 | 24.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 24.55 | 0.83 | 24.55 |
September | 1.00 | 20.18 | 1.00 | 20.18 | 8.33 | 23.69 | 0.33 | 23.72 |
October | 7.17 | 19.98 | 7.17 | 19.98 | 0.00 | 19.98 | 0.00 | 19.98 |
November | 28.67 | 15.94 | 7.33 | 16.64 | 0.00 | 16.64 | 0.00 | 16.64 |
December | 46.33 | 15.52 | 9.33 | 16.08 | 0.00 | 16.08 | 0.00 | 16.08 |
Annual Sum or Average | 270.00 | 15.80 | 65.17 | 16.48 | 52.17 | 17.57 | 2.17 | 17.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.49 | 0.00 | 15.49 |
Maximum of Months | 86.50 | 20.43 | 10.17 | 20.43 | 16.67 | 24.59 | 0.83 | 24.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 121.33 | 13.67 | 4.83 | 13.67 | 0.00 | 13.67 | 0.00 | 13.67 |
February | 103.00 | 13.96 | 4.50 | 13.96 | 0.00 | 13.96 | 0.00 | 13.96 |
March | 86.50 | 14.31 | 4.83 | 14.31 | 0.00 | 14.31 | 0.00 | 14.31 |
April | 42.83 | 14.62 | 2.83 | 14.62 | 0.00 | 14.62 | 0.00 | 14.62 |
May | 2.83 | 14.86 | 0.50 | 14.87 | 0.00 | 14.87 | 0.00 | 14.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.36 | 0.00 | 27.36 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.36 | 0.00 | 27.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.27 | 0.00 | 27.27 |
September | 0.50 | 14.99 | 0.17 | 14.99 | 0.33 | 19.09 | 0.00 | 19.09 |
October | 20.17 | 14.89 | 2.17 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
November | 76.67 | 14.18 | 2.67 | 14.17 | 0.00 | 14.17 | 0.00 | 14.17 |
December | 117.33 | 13.98 | 4.50 | 13.98 | 0.00 | 13.98 | 0.00 | 13.98 |
Annual Sum or Average | 571.17 | 14.07 | 27.00 | 14.07 | 11.33 | 14.32 | 0.00 | 14.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 0.00 | 13.67 |
Maximum of Months | 121.33 | 14.99 | 4.83 | 14.99 | 6.33 | 27.36 | 0.00 | 27.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12.33 | 8.53 | 7.83 | 8.42 | 0.00 | 8.42 | 0.00 | 8.42 |
Annual Sum or Average | 12.33 | 8.53 | 7.83 | 8.42 | 0.00 | 8.42 | 0.00 | 8.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.33 | 8.53 | 7.83 | 8.42 | 0.00 | 8.42 | 0.00 | 8.42 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.02 | 300.00 | 21.02 | 300.00 | 21.02 |
February | 276.00 | 21.03 | 276.00 | 21.03 | 276.00 | 21.03 |
March | 324.00 | 21.06 | 320.50 | 21.06 | 320.50 | 21.05 |
April | 295.50 | 21.44 | 239.33 | 21.31 | 236.50 | 21.26 |
May | 297.00 | 22.80 | 82.67 | 22.60 | 72.67 | 22.44 |
June | 151.50 | 23.36 | 168.83 | 23.62 | 53.50 | 23.63 |
July | 85.67 | 23.86 | 270.17 | 23.90 | 77.17 | 23.90 |
August | 113.67 | 23.84 | 275.17 | 23.89 | 95.00 | 23.89 |
September | 152.00 | 22.62 | 138.00 | 22.88 | 39.00 | 22.69 |
October | 300.00 | 21.48 | 226.67 | 21.32 | 226.67 | 21.26 |
November | 288.00 | 21.21 | 248.00 | 21.14 | 248.00 | 21.11 |
December | 300.00 | 21.03 | 300.00 | 21.03 | 300.00 | 21.03 |
Annual Sum or Average | 2883.33 | 21.72 | 2845.33 | 21.81 | 2245.00 | 21.68 |
Minimum of Months | 85.67 | 21.02 | 82.67 | 21.02 | 39.00 | 21.02 |
Maximum of Months | 324.00 | 23.86 | 320.50 | 23.90 | 320.50 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.53 | 300.00 | 15.53 | 300.00 | 15.53 |
February | 276.00 | 15.58 | 276.00 | 15.58 | 276.00 | 15.58 |
March | 324.00 | 15.97 | 324.00 | 15.97 | 324.00 | 15.97 |
April | 293.83 | 17.57 | 274.67 | 17.44 | 270.83 | 17.36 |
May | 285.33 | 21.32 | 128.50 | 21.07 | 111.50 | 20.78 |
June | 207.00 | 24.71 | 238.50 | 25.32 | 146.33 | 25.41 |
July | 233.67 | 26.46 | 289.33 | 26.43 | 228.33 | 26.46 |
August | 235.00 | 26.35 | 302.00 | 26.37 | 222.00 | 26.41 |
September | 185.83 | 22.19 | 218.17 | 23.14 | 118.17 | 22.90 |
October | 300.00 | 17.77 | 281.67 | 17.65 | 281.67 | 17.61 |
November | 288.00 | 16.45 | 285.67 | 16.43 | 285.67 | 16.43 |
December | 300.00 | 15.54 | 300.00 | 15.54 | 300.00 | 15.54 |
Annual Sum or Average | 3228.67 | 19.12 | 3218.50 | 19.31 | 2864.50 | 19.13 |
Minimum of Months | 185.83 | 15.53 | 128.50 | 15.53 | 111.50 | 15.53 |
Maximum of Months | 324.00 | 26.46 | 324.00 | 26.43 | 324.00 | 26.46 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 10.00 | 300.00 | 10.00 | 300.00 | 10.00 |
February | 276.00 | 10.06 | 276.00 | 10.06 | 276.00 | 10.06 |
March | 324.00 | 10.63 | 324.00 | 10.63 | 324.00 | 10.63 |
April | 300.00 | 13.37 | 292.00 | 13.27 | 292.00 | 13.23 |
May | 307.17 | 18.53 | 255.83 | 18.34 | 251.33 | 18.23 |
June | 234.50 | 24.12 | 226.83 | 24.73 | 159.83 | 24.83 |
July | 245.33 | 27.81 | 291.17 | 27.63 | 240.83 | 27.72 |
August | 241.67 | 27.31 | 299.17 | 27.17 | 228.50 | 27.28 |
September | 219.17 | 21.65 | 221.83 | 22.22 | 149.33 | 22.01 |
October | 300.00 | 13.46 | 300.00 | 13.46 | 300.00 | 13.46 |
November | 288.00 | 11.36 | 288.00 | 11.36 | 288.00 | 11.36 |
December | 300.00 | 9.96 | 300.00 | 9.96 | 300.00 | 9.96 |
Annual Sum or Average | 3335.83 | 15.90 | 3374.83 | 16.09 | 3109.83 | 15.89 |
Minimum of Months | 219.17 | 9.96 | 221.83 | 9.96 | 149.33 | 9.96 |
Maximum of Months | 324.00 | 27.81 | 324.00 | 27.63 | 324.00 | 27.72 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.313387E+09 | 73238758.75 | 19.08 | 0.232656E+09 | 80731310.32 | 0.00 | 1.00 | 18-APR-18:15 | 0.00 | 01-APR-00:10 | 22436.34 | 18-APR-18:15 | 16908.20 | 18-APR-18:15 | 5528.14 | 18-APR-18:15 | 4855.37 | 18-APR-18:15 | 0.00 | 01-APR-00:10 |
May | 0.712915E+09 | 0.164715E+09 | 50.11 | 0.560980E+09 | 0.151935E+09 | 0.00 | 1.00 | 30-MAY-19:21 | 0.00 | 01-MAY-00:05 | 23210.99 | 30-MAY-19:21 | 16741.45 | 31-MAY-20:31 | 7680.82 | 30-MAY-20:25 | 4990.60 | 30-MAY-19:21 | 0.00 | 01-MAY-00:05 |
June | 0.560080E+10 | 0.124564E+10 | 224.32 | 0.421464E+10 | 0.138616E+10 | 0.00 | 1.00 | 08-JUN-17:15 | 0.00 | 01-JUN-00:10 | 25272.91 | 25-JUN-23:01 | 20475.36 | 20-JUN-17:15 | 12925.72 | 14-JUN-17:15 | 5328.35 | 25-JUN-23:01 | 0.00 | 01-JUN-00:10 |
July | 0.853452E+10 | 0.186249E+10 | 302.32 | 0.605082E+10 | 0.248370E+10 | 0.00 | 1.00 | 01-JUL-00:23 | 0.00 | 01-JUL-00:10 | 25558.19 | 03-JUL-21:30 | 19661.67 | 18-JUL-17:15 | 13758.60 | 03-JUL-21:58 | 5393.40 | 26-JUL-17:10 | 0.00 | 01-JUL-00:10 |
August | 0.843176E+10 | 0.185450E+10 | 315.89 | 0.600583E+10 | 0.242593E+10 | 0.00 | 1.00 | 01-AUG-17:08 | 0.00 | 01-AUG-00:05 | 26222.75 | 04-AUG-00:25 | 20484.36 | 07-AUG-17:11 | 15520.70 | 04-AUG-05:55 | 5441.67 | 04-AUG-00:25 | 0.00 | 01-AUG-00:05 |
September | 0.326813E+10 | 0.743311E+09 | 147.59 | 0.285438E+10 | 0.413753E+09 | 0.00 | 1.00 | 01-SEP-17:10 | 0.00 | 01-SEP-00:10 | 23213.93 | 11-SEP-19:05 | 20689.23 | 01-SEP-17:11 | 10811.97 | 12-SEP-03:23 | 5103.55 | 06-SEP-17:08 | 0.00 | 01-SEP-00:10 |
October | 7335014.76 | 1750394.36 | 3.33 | 7334999.71 | 15.05 | 0.00 | 0.18 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1753.25 | 20-OCT-15:00 | 1753.25 | 20-OCT-15:00 | 0.01 | 11-OCT-15:20 | 414.85 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.268689E+11 | 0.594564E+10 | 1062.65 | 0.199266E+11 | 0.694221E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.853452E+10 | 0.186249E+10 | 315.89 | 0.605082E+10 | 0.248370E+10 | 0.00 | 1.00 | 0.00 | 26222.75 | 20689.23 | 15520.70 | 5441.67 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 61880921.01 | 16156226.05 | 3.50 | 37566943.36 | 24313977.65 | 0.00 | 0.24 | 18-APR-15:00 | 0.00 | 01-APR-00:10 | 7416.39 | 18-APR-15:00 | 4626.95 | 18-APR-15:00 | 2789.44 | 18-APR-15:00 | 1937.32 | 18-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.464848E+09 | 0.121256E+09 | 13.00 | 0.336150E+09 | 0.128698E+09 | 0.00 | 0.55 | 31-MAY-15:00 | 0.00 | 01-MAY-00:05 | 16106.66 | 31-MAY-15:10 | 12474.83 | 31-MAY-15:00 | 3725.70 | 31-MAY-13:30 | 4226.21 | 31-MAY-15:00 | 0.00 | 01-MAY-00:05 |
June | 0.822031E+10 | 0.201338E+10 | 149.93 | 0.559652E+10 | 0.262380E+10 | 0.00 | 1.00 | 11-JUN-11:30 | 0.00 | 01-JUN-00:10 | 70707.12 | 26-JUN-19:55 | 48021.35 | 25-JUN-16:33 | 28312.19 | 26-JUN-19:55 | 16200.33 | 25-JUN-13:53 | 0.00 | 01-JUN-00:10 |
July | 0.134507E+11 | 0.317942E+10 | 209.71 | 0.852620E+10 | 0.492450E+10 | 0.00 | 1.00 | 01-JUL-17:10 | 0.00 | 01-JUL-00:10 | 74322.18 | 03-JUL-19:45 | 51467.53 | 18-JUL-17:15 | 36635.34 | 03-JUL-19:45 | 16300.81 | 03-JUL-19:45 | 0.00 | 01-JUL-00:10 |
August | 0.109600E+11 | 0.263820E+10 | 192.65 | 0.708166E+10 | 0.387834E+10 | 0.00 | 1.00 | 01-AUG-17:10 | 0.00 | 01-AUG-00:05 | 76036.26 | 03-AUG-19:05 | 53675.20 | 09-AUG-17:15 | 40692.64 | 03-AUG-19:05 | 16471.67 | 03-AUG-19:05 | 0.00 | 01-AUG-00:05 |
September | 0.413277E+10 | 0.104895E+10 | 82.44 | 0.333845E+10 | 0.794326E+09 | 0.00 | 1.00 | 07-SEP-17:10 | 0.00 | 01-SEP-00:10 | 67341.57 | 11-SEP-17:15 | 54811.93 | 09-SEP-17:15 | 20899.17 | 11-SEP-17:15 | 15255.89 | 11-SEP-17:15 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.372905E+11 | 0.901736E+10 | 651.23 | 0.249165E+11 | 0.123740E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.134507E+11 | 0.317942E+10 | 209.71 | 0.852620E+10 | 0.492450E+10 | 0.00 | 1.00 | 0.00 | 76036.26 | 54811.93 | 40692.64 | 16471.67 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 71.04 | 28.82 | 42.22 | 27.08 | 302.85 | 0.00 | 0.00 | 0.00 |
February | 103.33 | 50.69 | 52.65 | 61.93 | 235.09 | 0.00 | 0.00 | 0.00 |
March | 124.08 | 46.22 | 77.85 | 92.97 | 140.81 | 0.00 | 0.00 | 0.00 |
April | 180.88 | 89.38 | 91.49 | 190.19 | 92.99 | 0.00 | 0.00 | 0.00 |
May | 181.37 | 72.46 | 108.90 | 209.78 | 55.86 | 0.00 | 0.00 | 0.00 |
June | 212.49 | 91.91 | 120.57 | 264.95 | 47.55 | 0.00 | 0.00 | 0.00 |
July | 228.63 | 108.65 | 119.98 | 290.30 | 44.79 | 0.00 | 0.00 | 0.00 |
August | 199.26 | 91.13 | 108.13 | 254.03 | 53.37 | 0.00 | 0.00 | 0.00 |
September | 161.69 | 76.66 | 85.04 | 187.04 | 83.91 | 0.00 | 0.00 | 0.00 |
October | 113.17 | 50.45 | 62.73 | 107.20 | 104.60 | 0.00 | 0.00 | 0.00 |
November | 67.70 | 25.15 | 42.55 | 40.36 | 175.44 | 0.00 | 0.00 | 0.00 |
December | 52.29 | 24.87 | 27.42 | 25.91 | 267.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 141.48 | 63.05 | 78.43 | 146.40 | 133.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.29 | 24.87 | 27.42 | 25.91 | 44.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 228.63 | 108.65 | 120.57 | 290.30 | 302.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 71.04 | 28.82 | 42.22 | 27.08 | 302.85 | 0.00 | 0.00 | 0.00 |
February | 103.33 | 50.69 | 52.65 | 61.93 | 235.09 | 0.00 | 0.00 | 0.00 |
March | 124.08 | 46.22 | 77.85 | 92.97 | 140.81 | 0.00 | 0.00 | 0.00 |
April | 180.88 | 89.38 | 91.49 | 190.19 | 92.99 | 0.00 | 0.00 | 0.00 |
May | 181.37 | 72.46 | 108.90 | 209.78 | 55.86 | 0.00 | 0.00 | 0.00 |
June | 212.49 | 91.91 | 120.57 | 264.95 | 47.55 | 0.00 | 0.00 | 0.00 |
July | 228.63 | 108.65 | 119.98 | 290.30 | 44.79 | 0.00 | 0.00 | 0.00 |
August | 199.26 | 91.13 | 108.13 | 254.03 | 53.37 | 0.00 | 0.00 | 0.00 |
September | 161.69 | 76.66 | 85.04 | 187.04 | 83.91 | 0.00 | 0.00 | 0.00 |
October | 113.17 | 50.45 | 62.73 | 107.20 | 104.60 | 0.00 | 0.00 | 0.00 |
November | 67.70 | 25.15 | 42.55 | 40.36 | 175.44 | 0.00 | 0.00 | 0.00 |
December | 52.29 | 24.87 | 27.42 | 25.91 | 267.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 141.48 | 63.05 | 78.43 | 146.40 | 133.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.29 | 24.87 | 27.42 | 25.91 | 44.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 228.63 | 108.65 | 120.57 | 290.30 | 302.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.44 | 0.00 | 19.44 | 0.01 | 193.90 | 0.00 | 0.00 | 0.00 |
February | 24.65 | 0.00 | 24.65 | 0.85 | 152.04 | 0.00 | 0.00 | 0.00 |
March | 36.95 | 0.00 | 36.95 | 11.05 | 88.77 | 0.00 | 0.00 | 0.00 |
April | 42.75 | 0.29 | 42.45 | 25.14 | 56.20 | 0.00 | 0.00 | 0.00 |
May | 55.70 | 2.16 | 53.54 | 50.95 | 31.13 | 0.00 | 0.00 | 0.00 |
June | 64.95 | 5.87 | 59.09 | 71.57 | 26.00 | 0.00 | 0.00 | 0.00 |
July | 60.94 | 4.09 | 56.85 | 67.83 | 24.64 | 0.00 | 0.00 | 0.00 |
August | 51.22 | 1.07 | 50.15 | 56.52 | 29.91 | 0.00 | 0.00 | 0.00 |
September | 39.17 | 0.03 | 39.14 | 32.92 | 49.93 | 0.00 | 0.00 | 0.00 |
October | 29.10 | 0.00 | 29.10 | 13.58 | 63.70 | 0.00 | 0.00 | 0.00 |
November | 20.35 | 0.00 | 20.35 | 3.08 | 109.20 | 0.00 | 0.00 | 0.00 |
December | 13.20 | 0.00 | 13.20 | 0.00 | 167.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.27 | 1.13 | 37.14 | 27.95 | 82.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.20 | 0.00 | 13.20 | 0.00 | 24.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 64.95 | 5.87 | 59.09 | 71.57 | 193.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.44 | 0.00 | 19.44 | 0.01 | 193.90 | 0.00 | 0.00 | 0.00 |
February | 24.65 | 0.00 | 24.65 | 0.85 | 152.04 | 0.00 | 0.00 | 0.00 |
March | 36.95 | 0.00 | 36.95 | 11.05 | 88.77 | 0.00 | 0.00 | 0.00 |
April | 42.74 | 0.29 | 42.45 | 25.14 | 56.20 | 0.00 | 0.00 | 0.00 |
May | 55.70 | 2.16 | 53.54 | 50.95 | 31.13 | 0.00 | 0.00 | 0.00 |
June | 64.95 | 5.87 | 59.09 | 71.57 | 26.00 | 0.00 | 0.00 | 0.00 |
July | 60.93 | 4.09 | 56.85 | 67.83 | 24.64 | 0.00 | 0.00 | 0.00 |
August | 51.22 | 1.07 | 50.15 | 56.52 | 29.91 | 0.00 | 0.00 | 0.00 |
September | 39.17 | 0.03 | 39.14 | 32.92 | 49.93 | 0.00 | 0.00 | 0.00 |
October | 29.09 | 0.00 | 29.09 | 13.58 | 63.70 | 0.00 | 0.00 | 0.00 |
November | 20.35 | 0.00 | 20.35 | 3.08 | 109.20 | 0.00 | 0.00 | 0.00 |
December | 13.20 | 0.00 | 13.20 | 0.00 | 167.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.27 | 1.13 | 37.14 | 27.95 | 82.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.20 | 0.00 | 13.20 | 0.00 | 24.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 64.95 | 5.87 | 59.09 | 71.57 | 193.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 7.91 | 211.91 | 2.67 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 28.07 | 157.80 | 0.17 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 78.12 | 83.81 | 16.67 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 123.30 | 54.20 | 47.00 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 159.84 | 38.58 | 30.50 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 177.86 | 45.93 | 39.17 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 174.57 | 53.99 | 28.67 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 148.24 | 53.79 | 35.33 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 108.08 | 73.05 | 12.67 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 67.52 | 60.76 | 14.17 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 26.21 | 105.26 | 0.00 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 8.34 | 171.99 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 92.68 | 92.30 | 227.50 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 7.91 | 38.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 177.86 | 211.91 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 7.91 | 211.91 | 2.67 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 28.07 | 157.80 | 0.17 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 78.12 | 83.81 | 16.67 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 123.30 | 54.20 | 47.00 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 159.84 | 38.58 | 30.50 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 177.86 | 45.93 | 39.17 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 174.57 | 53.99 | 28.67 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 148.24 | 53.79 | 35.33 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 108.08 | 73.05 | 12.67 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 67.52 | 60.76 | 14.17 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 26.21 | 105.26 | 0.00 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 8.34 | 171.99 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 92.68 | 92.30 | 227.50 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 7.91 | 38.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 177.86 | 211.91 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 7.91 | 211.91 | 2.67 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 28.07 | 157.80 | 0.17 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 78.12 | 83.81 | 16.67 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 123.30 | 54.20 | 47.00 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 159.84 | 38.58 | 30.50 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 177.86 | 45.93 | 39.17 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 174.57 | 53.99 | 28.67 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 148.24 | 53.79 | 35.33 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 108.08 | 73.05 | 12.67 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 67.52 | 60.76 | 14.17 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 26.21 | 105.26 | 0.00 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 8.34 | 171.99 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 92.68 | 92.30 | 227.50 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 7.91 | 38.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 177.86 | 211.91 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 7.91 | 211.91 | 2.67 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 28.07 | 157.80 | 0.17 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 78.12 | 83.81 | 16.67 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 123.30 | 54.20 | 47.00 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 159.84 | 38.58 | 30.50 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 177.86 | 45.93 | 39.17 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 174.57 | 53.99 | 28.67 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 148.24 | 53.79 | 35.33 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 108.08 | 73.05 | 12.67 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 67.52 | 60.76 | 14.17 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 26.21 | 105.26 | 0.00 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 8.34 | 171.99 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 92.68 | 92.30 | 227.50 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 7.91 | 38.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 177.86 | 211.91 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 7.91 | 211.91 | 2.67 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 28.07 | 157.80 | 0.17 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 78.12 | 83.81 | 16.67 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 123.30 | 54.20 | 47.00 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 159.84 | 38.58 | 30.50 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 177.86 | 45.93 | 39.17 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 174.57 | 53.99 | 28.67 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 148.24 | 53.79 | 35.33 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 108.08 | 73.05 | 12.67 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 67.52 | 60.76 | 14.17 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 26.21 | 105.26 | 0.00 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 8.34 | 171.99 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 92.68 | 92.30 | 227.50 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 7.91 | 38.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 177.86 | 211.91 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 7.91 | 211.91 | 2.67 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 28.07 | 157.80 | 0.17 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 78.12 | 83.81 | 16.67 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 123.30 | 54.20 | 47.00 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 159.84 | 38.58 | 30.50 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 177.86 | 45.93 | 39.17 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 174.57 | 53.99 | 28.67 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 148.24 | 53.79 | 35.33 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 108.08 | 73.05 | 12.67 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 67.52 | 60.76 | 14.17 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 26.21 | 105.26 | 0.00 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 8.34 | 171.99 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 92.68 | 92.30 | 227.50 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 7.91 | 38.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 177.86 | 211.91 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 7.91 | 211.91 | 2.67 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 28.07 | 157.80 | 0.17 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 78.12 | 83.81 | 16.67 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 123.30 | 54.20 | 47.00 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 159.84 | 38.58 | 30.50 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 177.86 | 45.93 | 39.17 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 174.57 | 53.99 | 28.67 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 148.24 | 53.79 | 35.33 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 108.08 | 73.05 | 12.67 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 67.52 | 60.76 | 14.17 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 26.21 | 105.26 | 0.00 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 8.34 | 171.99 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 92.68 | 92.30 | 227.50 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 7.91 | 38.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 177.86 | 211.91 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 7.91 | 211.91 | 2.67 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 28.07 | 157.80 | 0.17 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 78.12 | 83.81 | 16.67 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 123.30 | 54.20 | 47.00 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 159.84 | 38.58 | 30.50 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 177.86 | 45.93 | 39.17 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 174.57 | 53.99 | 28.67 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 148.24 | 53.79 | 35.33 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 108.08 | 73.05 | 12.67 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 67.52 | 60.76 | 14.17 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 26.21 | 105.26 | 0.00 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 8.34 | 171.99 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 92.68 | 92.30 | 227.50 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 7.91 | 38.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 177.86 | 211.91 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 7.91 | 211.91 | 2.67 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 28.07 | 157.80 | 0.17 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 78.12 | 83.81 | 16.67 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 123.30 | 54.20 | 47.00 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 159.84 | 38.58 | 30.50 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 177.86 | 45.93 | 39.17 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 174.57 | 53.99 | 28.67 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 148.24 | 53.79 | 35.33 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 108.08 | 73.05 | 12.67 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 67.52 | 60.76 | 14.17 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 26.21 | 105.26 | 0.00 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 8.34 | 171.99 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 92.68 | 92.30 | 227.50 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 7.91 | 38.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 177.86 | 211.91 | 47.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 7.91 | 211.91 | 2.67 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 28.07 | 157.80 | 0.17 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 78.12 | 83.81 | 16.67 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 123.30 | 54.20 | 47.00 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 159.84 | 38.58 | 30.50 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 177.86 | 45.93 | 39.17 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 174.57 | 53.99 | 28.67 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 148.24 | 53.79 | 35.33 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 108.08 | 73.05 | 12.67 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 67.52 | 60.76 | 14.17 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 26.21 | 105.26 | 0.00 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 8.34 | 171.99 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 92.68 | 92.30 | 227.50 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 7.91 | 38.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 177.86 | 211.91 | 47.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.190265E+09 | 77183664.42 | 0.113082E+09 | 72518489.40 | 0.811152E+09 |
February | 0.249987E+09 | 0.122621E+09 | 0.127366E+09 | 0.149826E+09 | 0.568718E+09 |
March | 0.332324E+09 | 0.123798E+09 | 0.208526E+09 | 0.249023E+09 | 0.377139E+09 |
April | 0.468829E+09 | 0.231677E+09 | 0.237152E+09 | 0.492983E+09 | 0.241027E+09 |
May | 0.485771E+09 | 0.194080E+09 | 0.291691E+09 | 0.561879E+09 | 0.149625E+09 |
June | 0.550765E+09 | 0.238241E+09 | 0.312524E+09 | 0.686738E+09 | 0.123261E+09 |
July | 0.612361E+09 | 0.291017E+09 | 0.321344E+09 | 0.777535E+09 | 0.119957E+09 |
August | 0.533701E+09 | 0.244088E+09 | 0.289613E+09 | 0.680407E+09 | 0.142938E+09 |
September | 0.419113E+09 | 0.198693E+09 | 0.220420E+09 | 0.484813E+09 | 0.217487E+09 |
October | 0.303128E+09 | 0.135122E+09 | 0.168006E+09 | 0.287138E+09 | 0.280166E+09 |
November | 0.175478E+09 | 65177503.11 | 0.110301E+09 | 0.104619E+09 | 0.454730E+09 |
December | 0.140049E+09 | 66606830.53 | 73442141.58 | 69400320.81 | 0.715945E+09 |
Annual Sum or Average | 0.446177E+10 | 0.198830E+10 | 0.247347E+10 | 0.461688E+10 | 0.420215E+10 |
Minimum of Months | 0.140049E+09 | 65177503.11 | 73442141.58 | 69400320.81 | 0.119957E+09 |
Maximum of Months | 0.612361E+09 | 0.291017E+09 | 0.321344E+09 | 0.777535E+09 | 0.811152E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.190265E+09 | 77183664.42 | 0.113082E+09 | 72518489.40 | 0.811152E+09 |
February | 0.249987E+09 | 0.122621E+09 | 0.127366E+09 | 0.149826E+09 | 0.568718E+09 |
March | 0.332324E+09 | 0.123798E+09 | 0.208526E+09 | 0.249023E+09 | 0.377139E+09 |
April | 0.468829E+09 | 0.231677E+09 | 0.237152E+09 | 0.492983E+09 | 0.241027E+09 |
May | 0.485771E+09 | 0.194080E+09 | 0.291691E+09 | 0.561879E+09 | 0.149625E+09 |
June | 0.550765E+09 | 0.238241E+09 | 0.312524E+09 | 0.686738E+09 | 0.123261E+09 |
July | 0.612361E+09 | 0.291017E+09 | 0.321344E+09 | 0.777535E+09 | 0.119957E+09 |
August | 0.533701E+09 | 0.244088E+09 | 0.289613E+09 | 0.680407E+09 | 0.142938E+09 |
September | 0.419113E+09 | 0.198693E+09 | 0.220420E+09 | 0.484813E+09 | 0.217487E+09 |
October | 0.303128E+09 | 0.135122E+09 | 0.168006E+09 | 0.287138E+09 | 0.280166E+09 |
November | 0.175478E+09 | 65177503.11 | 0.110301E+09 | 0.104619E+09 | 0.454730E+09 |
December | 0.140049E+09 | 66606830.53 | 73442141.58 | 69400320.81 | 0.715945E+09 |
Annual Sum or Average | 0.446177E+10 | 0.198830E+10 | 0.247347E+10 | 0.461688E+10 | 0.420215E+10 |
Minimum of Months | 0.140049E+09 | 65177503.11 | 73442141.58 | 69400320.81 | 0.119957E+09 |
Maximum of Months | 0.612361E+09 | 0.291017E+09 | 0.321344E+09 | 0.777535E+09 | 0.811152E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52073982.96 | 0.00 | 52073982.96 | 20737.38 | 0.519335E+09 |
February | 59630661.61 | 0.00 | 59630661.61 | 2045814.63 | 0.367806E+09 |
March | 98960829.24 | 2684.40 | 98958144.85 | 29596710.22 | 0.237764E+09 |
April | 0.110796E+09 | 754006.91 | 0.110042E+09 | 65174130.03 | 0.145665E+09 |
May | 0.149190E+09 | 5777377.20 | 0.143413E+09 | 0.136473E+09 | 83366456.22 |
June | 0.168363E+09 | 15209045.09 | 0.153154E+09 | 0.185506E+09 | 67393534.45 |
July | 0.163211E+09 | 10950639.71 | 0.152260E+09 | 0.181680E+09 | 66001873.32 |
August | 0.137186E+09 | 2858059.88 | 0.134328E+09 | 0.151388E+09 | 80118489.80 |
September | 0.101528E+09 | 67832.33 | 0.101460E+09 | 85326358.22 | 0.129407E+09 |
October | 77929157.78 | 0.00 | 77929157.78 | 36384057.05 | 0.170613E+09 |
November | 52753737.13 | 0.00 | 52753737.13 | 7977296.22 | 0.283045E+09 |
December | 35359907.87 | 0.00 | 35359907.87 | 0.00 | 0.447547E+09 |
Annual Sum or Average | 0.120698E+10 | 35619645.52 | 0.117136E+10 | 0.881571E+09 | 0.259806E+10 |
Minimum of Months | 35359907.87 | 0.00 | 35359907.87 | 0.00 | 66001873.32 |
Maximum of Months | 0.168363E+09 | 15209045.09 | 0.153154E+09 | 0.185506E+09 | 0.519335E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52072306.59 | 0.00 | 52072306.59 | 20720.63 | 0.519336E+09 |
February | 59628805.47 | 0.00 | 59628805.47 | 2045525.90 | 0.367807E+09 |
March | 98957687.10 | 2684.27 | 98955002.83 | 29594479.57 | 0.237765E+09 |
April | 0.110793E+09 | 753971.57 | 0.110039E+09 | 65171531.18 | 0.145666E+09 |
May | 0.149186E+09 | 5777106.41 | 0.143409E+09 | 0.136467E+09 | 83366171.03 |
June | 0.168358E+09 | 15208332.23 | 0.153149E+09 | 0.185500E+09 | 67393131.89 |
July | 0.163206E+09 | 10950126.44 | 0.152256E+09 | 0.181674E+09 | 66001212.02 |
August | 0.137182E+09 | 2857925.91 | 0.134324E+09 | 0.151383E+09 | 80118029.37 |
September | 0.101525E+09 | 67829.15 | 0.101457E+09 | 85323433.45 | 0.129406E+09 |
October | 77926706.53 | 0.00 | 77926706.53 | 36381849.86 | 0.170612E+09 |
November | 52751976.39 | 0.00 | 52751976.39 | 7976606.02 | 0.283045E+09 |
December | 35358789.52 | 0.00 | 35358789.52 | 0.00 | 0.447547E+09 |
Annual Sum or Average | 0.120695E+10 | 35617975.98 | 0.117133E+10 | 0.881537E+09 | 0.259806E+10 |
Minimum of Months | 35358789.52 | 0.00 | 35358789.52 | 0.00 | 66001212.02 |
Maximum of Months | 0.168358E+09 | 15208332.23 | 0.153149E+09 | 0.185500E+09 | 0.519336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 21199201.50 | 0.567593E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 67895622.62 | 0.381744E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.209232E+09 | 0.224466E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.319598E+09 | 0.140477E+09 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.428104E+09 | 0.103325E+09 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.461014E+09 | 0.119044E+09 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.467567E+09 | 0.144616E+09 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.397042E+09 | 0.144069E+09 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.280142E+09 | 0.189354E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.180855E+09 | 0.162732E+09 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 67931233.20 | 0.272844E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 22333503.11 | 0.460662E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.292291E+10 | 0.291092E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 21199201.50 | 0.103325E+09 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.467567E+09 | 0.567593E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 21199201.50 | 0.567593E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 67895622.62 | 0.381744E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.209232E+09 | 0.224466E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.319598E+09 | 0.140477E+09 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.428104E+09 | 0.103325E+09 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.461014E+09 | 0.119044E+09 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.467567E+09 | 0.144616E+09 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.397042E+09 | 0.144069E+09 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.280142E+09 | 0.189354E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.180855E+09 | 0.162732E+09 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 67931233.20 | 0.272844E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 22333503.11 | 0.460662E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.292291E+10 | 0.291092E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 21199201.50 | 0.103325E+09 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.467567E+09 | 0.567593E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 21199201.50 | 0.567593E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 67895622.62 | 0.381744E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.209232E+09 | 0.224466E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.319598E+09 | 0.140477E+09 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.428104E+09 | 0.103325E+09 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.461014E+09 | 0.119044E+09 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.467567E+09 | 0.144616E+09 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.397042E+09 | 0.144069E+09 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.280142E+09 | 0.189354E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.180855E+09 | 0.162732E+09 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 67931233.20 | 0.272844E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 22333503.11 | 0.460662E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.292291E+10 | 0.291092E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 21199201.50 | 0.103325E+09 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.467567E+09 | 0.567593E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 21199201.50 | 0.567593E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 67895622.62 | 0.381744E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.209232E+09 | 0.224466E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.319598E+09 | 0.140477E+09 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.428104E+09 | 0.103325E+09 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.461014E+09 | 0.119044E+09 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.467567E+09 | 0.144616E+09 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.397042E+09 | 0.144069E+09 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.280142E+09 | 0.189354E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.180855E+09 | 0.162732E+09 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 67931233.20 | 0.272844E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 22333503.11 | 0.460662E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.292291E+10 | 0.291092E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 21199201.50 | 0.103325E+09 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.467567E+09 | 0.567593E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 21199201.50 | 0.567593E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 67895622.62 | 0.381744E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.209232E+09 | 0.224466E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.319598E+09 | 0.140477E+09 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.428104E+09 | 0.103325E+09 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.461014E+09 | 0.119044E+09 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.467567E+09 | 0.144616E+09 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.397042E+09 | 0.144069E+09 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.280142E+09 | 0.189354E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.180855E+09 | 0.162732E+09 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 67931233.20 | 0.272844E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 22333503.11 | 0.460662E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.292291E+10 | 0.291092E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 21199201.50 | 0.103325E+09 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.467567E+09 | 0.567593E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 21199201.50 | 0.567593E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 67895622.62 | 0.381744E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.209232E+09 | 0.224466E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.319598E+09 | 0.140477E+09 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.428104E+09 | 0.103325E+09 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.461014E+09 | 0.119044E+09 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.467567E+09 | 0.144616E+09 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.397042E+09 | 0.144069E+09 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.280142E+09 | 0.189354E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.180855E+09 | 0.162732E+09 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 67931233.20 | 0.272844E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 22333503.11 | 0.460662E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.292291E+10 | 0.291092E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 21199201.50 | 0.103325E+09 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.467567E+09 | 0.567593E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 21199201.50 | 0.567593E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 67895622.62 | 0.381744E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.209232E+09 | 0.224466E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.319598E+09 | 0.140477E+09 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.428104E+09 | 0.103325E+09 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.461014E+09 | 0.119044E+09 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.467567E+09 | 0.144616E+09 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.397042E+09 | 0.144069E+09 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.280142E+09 | 0.189354E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.180855E+09 | 0.162732E+09 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 67931233.20 | 0.272844E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 22333503.11 | 0.460662E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.292291E+10 | 0.291092E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 21199201.50 | 0.103325E+09 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.467567E+09 | 0.567593E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 21199201.50 | 0.567593E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 67895622.62 | 0.381744E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.209232E+09 | 0.224466E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.319598E+09 | 0.140477E+09 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.428104E+09 | 0.103325E+09 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.461014E+09 | 0.119044E+09 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.467567E+09 | 0.144616E+09 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.397042E+09 | 0.144069E+09 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.280142E+09 | 0.189354E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.180855E+09 | 0.162732E+09 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 67931233.20 | 0.272844E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 22333503.11 | 0.460662E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.292291E+10 | 0.291092E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 21199201.50 | 0.103325E+09 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.467567E+09 | 0.567593E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 21199201.50 | 0.567593E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 67895622.62 | 0.381744E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.209232E+09 | 0.224466E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.319598E+09 | 0.140477E+09 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.428104E+09 | 0.103325E+09 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.461014E+09 | 0.119044E+09 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.467567E+09 | 0.144616E+09 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.397042E+09 | 0.144069E+09 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.280142E+09 | 0.189354E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.180855E+09 | 0.162732E+09 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 67931233.20 | 0.272844E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 22333503.11 | 0.460662E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.292291E+10 | 0.291092E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 21199201.50 | 0.103325E+09 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.467567E+09 | 0.567593E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 21199201.50 | 0.567593E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 67895622.62 | 0.381744E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.209232E+09 | 0.224466E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.319598E+09 | 0.140477E+09 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.428104E+09 | 0.103325E+09 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.461014E+09 | 0.119044E+09 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.467567E+09 | 0.144616E+09 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.397042E+09 | 0.144069E+09 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.280142E+09 | 0.189354E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.180855E+09 | 0.162732E+09 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 67931233.20 | 0.272844E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 22333503.11 | 0.460662E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.292291E+10 | 0.291092E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 21199201.50 | 0.103325E+09 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.467567E+09 | 0.567593E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 34.96 | 974.29 | 180.96 | 57.63 | 123.32 | 0.00 | 0.00 |
February | 102.92 | 751.61 | 255.97 | 101.37 | 154.59 | 0.00 | 0.00 |
March | 198.08 | 449.19 | 322.05 | 92.44 | 229.60 | 0.00 | 0.00 |
April | 427.27 | 294.97 | 447.24 | 179.34 | 267.90 | 0.00 | 0.00 |
May | 519.78 | 172.29 | 474.13 | 149.24 | 324.90 | 0.00 | 0.00 |
June | 670.07 | 144.15 | 554.88 | 195.56 | 359.32 | 0.00 | 0.00 |
July | 714.14 | 136.74 | 579.13 | 225.48 | 353.65 | 0.00 | 0.00 |
August | 620.48 | 165.93 | 500.96 | 184.40 | 316.56 | 0.00 | 0.00 |
September | 437.86 | 265.60 | 401.73 | 153.36 | 248.36 | 0.00 | 0.00 |
October | 236.89 | 331.91 | 284.54 | 100.90 | 183.64 | 0.00 | 0.00 |
November | 77.89 | 560.28 | 176.10 | 50.29 | 125.81 | 0.00 | 0.00 |
December | 36.92 | 853.89 | 130.98 | 49.74 | 81.24 | 0.00 | 0.00 |
Annual Sum or Average | 341.02 | 423.58 | 359.51 | 128.36 | 231.15 | 0.00 | 0.00 |
Minimum of Months | 34.96 | 136.74 | 130.98 | 49.74 | 81.24 | 0.00 | 0.00 |
Maximum of Months | 714.14 | 974.29 | 579.13 | 225.48 | 359.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 456.71 | 19967.16 | 340.28 | 148.34 | 191.94 | 0.00 | 0.00 |
February | 1452.10 | 15674.81 | 466.12 | 233.18 | 232.94 | 0.00 | 0.00 |
March | 3606.11 | 6916.70 | 731.71 | 349.89 | 381.82 | 0.00 | 0.00 |
April | 5079.50 | 3275.03 | 993.55 | 596.93 | 396.61 | 0.00 | 0.00 |
May | 6449.74 | 1341.19 | 1194.06 | 670.94 | 523.12 | 0.00 | 0.00 |
June | 6987.24 | 2035.06 | 1357.84 | 794.17 | 563.68 | 0.00 | 0.00 |
July | 7074.96 | 2804.76 | 1368.24 | 841.75 | 526.49 | 0.00 | 0.00 |
August | 5507.23 | 2484.45 | 1139.24 | 648.65 | 490.58 | 0.00 | 0.00 |
September | 4046.25 | 2944.79 | 884.97 | 513.52 | 371.45 | 0.00 | 0.00 |
October | 2682.15 | 2912.94 | 562.48 | 278.80 | 283.68 | 0.00 | 0.00 |
November | 1167.74 | 8248.10 | 335.72 | 124.34 | 211.38 | 0.00 | 0.00 |
December | 437.88 | 14744.52 | 230.97 | 113.57 | 117.40 | 0.00 | 0.00 |
Annual Sum or Average | 3758.19 | 6904.95 | 802.16 | 443.86 | 358.31 | 0.00 | 0.00 |
Minimum of Months | 437.88 | 1341.19 | 230.97 | 113.57 | 117.40 | 0.00 | 0.00 |
Maximum of Months | 7074.96 | 19967.16 | 1368.24 | 841.75 | 563.68 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 93629860.57 | 0.260953E+10 | 0.484677E+09 | 0.154367E+09 | 0.330310E+09 | 0.00 | 0.00 |
February | 0.248989E+09 | 0.181830E+10 | 0.619234E+09 | 0.245241E+09 | 0.373992E+09 | 0.00 | 0.00 |
March | 0.530544E+09 | 0.120311E+10 | 0.862567E+09 | 0.247600E+09 | 0.614966E+09 | 0.00 | 0.00 |
April | 0.110748E+10 | 0.764557E+09 | 0.115925E+10 | 0.464862E+09 | 0.694385E+09 | 0.00 | 0.00 |
May | 0.139217E+10 | 0.461455E+09 | 0.126992E+10 | 0.399715E+09 | 0.870204E+09 | 0.00 | 0.00 |
June | 0.173681E+10 | 0.373641E+09 | 0.143825E+10 | 0.506899E+09 | 0.931352E+09 | 0.00 | 0.00 |
July | 0.191274E+10 | 0.366234E+09 | 0.155114E+10 | 0.603934E+09 | 0.947204E+09 | 0.00 | 0.00 |
August | 0.166189E+10 | 0.444414E+09 | 0.134177E+10 | 0.493892E+09 | 0.847878E+09 | 0.00 | 0.00 |
September | 0.113493E+10 | 0.688436E+09 | 0.104128E+10 | 0.397522E+09 | 0.643756E+09 | 0.00 | 0.00 |
October | 0.634474E+09 | 0.888990E+09 | 0.762111E+09 | 0.270243E+09 | 0.491868E+09 | 0.00 | 0.00 |
November | 0.201889E+09 | 0.145225E+10 | 0.456463E+09 | 0.130355E+09 | 0.326108E+09 | 0.00 | 0.00 |
December | 98880134.64 | 0.228706E+10 | 0.350817E+09 | 0.133214E+09 | 0.217603E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107544E+11 | 0.133580E+11 | 0.113375E+11 | 0.404784E+10 | 0.728963E+10 | 0.00 | 0.00 |
Minimum of Months | 93629860.57 | 0.366234E+09 | 0.350817E+09 | 0.130355E+09 | 0.217603E+09 | 0.00 | 0.00 |
Maximum of Months | 0.191274E+10 | 0.260953E+10 | 0.155114E+10 | 0.603934E+09 | 0.947204E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.122325E+10 | 0.534801E+11 | 0.911401E+09 | 0.397312E+09 | 0.514089E+09 | 0.00 | 0.00 |
February | 0.351292E+10 | 0.379205E+11 | 0.112763E+10 | 0.564098E+09 | 0.563533E+09 | 0.00 | 0.00 |
March | 0.965860E+10 | 0.185257E+11 | 0.195982E+10 | 0.937155E+09 | 0.102266E+10 | 0.00 | 0.00 |
April | 0.131661E+11 | 0.848887E+10 | 0.257527E+10 | 0.154725E+10 | 0.102802E+10 | 0.00 | 0.00 |
May | 0.172750E+11 | 0.359225E+10 | 0.319817E+10 | 0.179706E+10 | 0.140112E+10 | 0.00 | 0.00 |
June | 0.181109E+11 | 0.527488E+10 | 0.351953E+10 | 0.205848E+10 | 0.146105E+10 | 0.00 | 0.00 |
July | 0.189496E+11 | 0.751226E+10 | 0.366470E+10 | 0.225455E+10 | 0.141015E+10 | 0.00 | 0.00 |
August | 0.147506E+11 | 0.665435E+10 | 0.305134E+10 | 0.173736E+10 | 0.131398E+10 | 0.00 | 0.00 |
September | 0.104879E+11 | 0.763291E+10 | 0.229385E+10 | 0.133104E+10 | 0.962804E+09 | 0.00 | 0.00 |
October | 0.718386E+10 | 0.780202E+10 | 0.150654E+10 | 0.746738E+09 | 0.759802E+09 | 0.00 | 0.00 |
November | 0.302679E+10 | 0.213791E+11 | 0.870186E+09 | 0.322288E+09 | 0.547898E+09 | 0.00 | 0.00 |
December | 0.117281E+10 | 0.394917E+11 | 0.618634E+09 | 0.304181E+09 | 0.314453E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.118518E+12 | 0.217755E+12 | 0.252971E+11 | 0.139975E+11 | 0.112996E+11 | 0.00 | 0.00 |
Minimum of Months | 0.117281E+10 | 0.359225E+10 | 0.618634E+09 | 0.304181E+09 | 0.314453E+09 | 0.00 | 0.00 |
Maximum of Months | 0.189496E+11 | 0.534801E+11 | 0.366470E+10 | 0.225455E+10 | 0.146105E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.106537E+10 | -977156636.6 | 0.00 | 0.00 | 744.00 | 0.00 | -88210641.9 | 58.99 | 0.00 | 0.00 |
February | 0.995158E+09 | -915648199.6 | 0.00 | 0.00 | 672.00 | 0.00 | -79509808.9 | 58.99 | 0.00 | 0.00 |
March | 0.114679E+10 | -0.105947E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -87318180.0 | 58.99 | 0.00 | 0.00 |
April | 0.102891E+10 | -946413957.6 | 0.00 | 0.00 | 720.00 | 0.00 | -82496201.2 | 58.99 | 0.00 | 0.00 |
May | 0.100598E+10 | -926235146.6 | 0.00 | 0.00 | 744.00 | 0.00 | -79742473.9 | 58.99 | 0.00 | 0.00 |
June | 0.933790E+09 | -860528036.0 | 0.00 | 0.00 | 720.00 | 0.00 | -73262417.5 | 58.99 | 0.00 | 0.00 |
July | 0.858821E+09 | -784697922.9 | 0.00 | 0.00 | 744.00 | 0.00 | -74123522.8 | 58.99 | 0.00 | 0.00 |
August | 0.895103E+09 | -820487981.6 | 0.00 | 0.00 | 744.00 | 0.00 | -74615358.7 | 58.99 | 0.00 | 0.00 |
September | 0.847557E+09 | -773209824.7 | 0.00 | 0.00 | 720.00 | 0.00 | -74346795.6 | 58.99 | 0.00 | 0.00 |
October | 0.899350E+09 | -814134646.3 | 0.00 | 0.00 | 744.00 | 0.00 | -85215137.3 | 58.99 | 0.00 | 0.00 |
November | 0.920194E+09 | -835948459.0 | 0.00 | 0.00 | 720.00 | 0.00 | -84245282.5 | 58.99 | 0.00 | 0.00 |
December | 0.101729E+10 | -929157845.4 | 0.00 | 0.00 | 744.00 | 0.00 | -88136306.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.116143E+11 | -0.106431E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -971222127.0 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.847557E+09 | -0.105947E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -88210641.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.114679E+10 | -773209824.7 | 0.00 | 0.00 | 744.00 | 0.00 | -73262417.5 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 214.17 | 0.95 | 0.88 | 01-JAN-10:30 | 121.98 | 9.11 | 0.00 | 30.67 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 226.83 | 0.95 | 0.88 | 03-FEB-11:30 | 131.01 | 9.23 | 0.00 | 59.67 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 334.33 | 0.92 | 0.88 | 01-MAR-08:00 | 214.81 | 11.77 | 0.00 | 164.67 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 285.17 | 0.92 | 0.88 | 02-APR-14:39 | 239.53 | 11.76 | 0.00 | 189.83 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 428.67 | 0.91 | 0.88 | 01-MAY-07:30 | 797.94 | 12.54 | 0.00 | 264.50 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 400.67 | 0.91 | 0.88 | 01-JUN-07:40 | 1988.92 | 12.87 | 0.00 | 282.33 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 414.00 | 0.91 | 0.88 | 01-JUL-07:00 | 1830.37 | 13.59 | 20.00 | 277.67 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 410.83 | 0.91 | 0.88 | 01-AUG-08:30 | 1101.34 | 12.98 | 14.67 | 260.33 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 326.50 | 0.92 | 0.88 | 01-SEP-07:40 | 212.33 | 11.66 | 0.00 | 161.33 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 325.17 | 0.94 | 0.88 | 02-OCT-09:20 | 162.51 | 10.28 | 0.00 | 93.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 254.83 | 0.94 | 0.88 | 01-NOV-10:09 | 139.26 | 9.75 | 0.00 | 51.50 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 186.17 | 0.98 | 0.88 | 18-DEC-12:30 | 79.33 | 6.95 | 0.00 | 0.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3807.33 | 0.93 | 713.77 | 11.49 | 34.67 | 1835.67 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 186.17 | 0.91 | 0.88 | 79.33 | 6.95 | 0.00 | 0.17 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 428.67 | 0.98 | 0.88 | 1988.92 | 13.59 | 20.00 | 282.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.83 | 0.78 | 01-JAN-10:30 | 816.15 | 23.08 | 73.17 | 112.33 | 789.28 | 22.82 | 91.67 | 191.67 |
February | 226.83 | 0.83 | 0.78 | 01-FEB-11:00 | 1294.65 | 22.84 | 71.17 | 136.83 | 1424.07 | 24.53 | 105.83 | 204.83 |
March | 334.33 | 0.81 | 0.78 | 01-MAR-08:00 | 633.25 | 19.36 | 59.50 | 204.83 | 1831.11 | 24.74 | 182.17 | 290.17 |
April | 285.17 | 0.81 | 0.78 | 02-APR-14:39 | 504.05 | 17.85 | 23.17 | 194.83 | 3501.14 | 26.01 | 149.33 | 320.83 |
May | 428.67 | 0.81 | 0.78 | 01-MAY-07:10 | 466.22 | 17.07 | 0.00 | 298.50 | 1939.07 | 22.61 | 205.17 | 373.17 |
June | 400.67 | 0.80 | 0.78 | 01-JUN-06:10 | 535.06 | 17.32 | 0.50 | 346.83 | 2552.87 | 23.15 | 207.67 | 379.83 |
July | 414.00 | 0.80 | 0.78 | 01-JUL-06:10 | 524.10 | 17.62 | 6.50 | 339.67 | 2903.50 | 23.49 | 217.17 | 389.67 |
August | 410.83 | 0.81 | 0.78 | 01-AUG-08:30 | 494.28 | 17.55 | 20.17 | 283.83 | 2363.44 | 23.97 | 213.00 | 356.00 |
September | 326.50 | 0.81 | 0.78 | 01-SEP-07:40 | 471.58 | 17.88 | 31.00 | 204.67 | 2513.83 | 25.86 | 169.67 | 308.33 |
October | 325.17 | 0.82 | 0.78 | 01-OCT-11:20 | 900.19 | 21.30 | 81.33 | 180.67 | 1416.42 | 24.31 | 155.67 | 255.17 |
November | 254.83 | 0.83 | 0.78 | 01-NOV-09:00 | 582.92 | 21.16 | 70.33 | 112.50 | 901.32 | 23.07 | 109.33 | 199.17 |
December | 186.17 | 0.85 | 0.78 | 01-DEC-14:09 | 562.79 | 21.48 | 48.67 | 58.50 | 565.51 | 20.26 | 27.67 | 133.50 |
Annual Sum or Average | 3807.33 | 0.81 | 619.38 | 19.07 | 485.50 | 2474.00 | 2034.51 | 23.82 | 1834.33 | 3402.33 | ||
Minimum of Months | 186.17 | 0.80 | 0.78 | 466.22 | 17.07 | 0.00 | 58.50 | 565.51 | 20.26 | 27.67 | 133.50 | |
Maximum of Months | 428.67 | 0.85 | 0.78 | 1294.65 | 23.08 | 81.33 | 346.83 | 3501.14 | 26.01 | 217.17 | 389.67 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.171595E+11 | 29677.45 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128587E+11 | 29677.45 | 01-FEB-00:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.950875E+10 | 29677.45 | 01-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.451071E+10 | 29677.45 | 01-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.678623E+09 | 29677.45 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 56617932.54 | 29677.45 | 05-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.288012E+09 | 29677.45 | 25-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.224243E+10 | 29677.45 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.733910E+10 | 29677.45 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130407E+11 | 29677.45 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.676832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.171595E+11 | 29677.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.688321E+11 | 90133.70 | 01-JAN-01:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.479709E+11 | 90133.70 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.288557E+11 | 90133.70 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106417E+11 | 90133.70 | 01-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.637606E+09 | 68731.93 | 02-MAY-05:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.210925E+09 | 33307.55 | 29-SEP-05:36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.462224E+10 | 80419.33 | 26-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.285022E+11 | 90133.70 | 10-NOV-03:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.544740E+11 | 90133.70 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.244747E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.688321E+11 | 90133.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.299508E+12 | 282246.16 | 18-JAN-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.199544E+12 | 267000.49 | 01-FEB-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104237E+12 | 190577.03 | 06-MAR-08:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.226173E+11 | 111351.77 | 02-APR-23:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.283472E+09 | 15925.47 | 02-MAY-02:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.278187E+10 | 25181.78 | 24-OCT-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112780E+12 | 184734.27 | 26-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.228424E+12 | 282246.16 | 08-DEC-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.970176E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.299508E+12 | 282246.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.313387E+09 | 0.232656E+09 | 22436.34 | 18-APR-18:15 | 16908.20 | 0.00 |
May | 0.00 | 0.00 | 0.712915E+09 | 0.560980E+09 | 23210.99 | 30-MAY-19:21 | 15877.06 | 0.00 |
June | 0.00 | 0.00 | 0.560080E+10 | 0.421464E+10 | 25272.91 | 25-JUN-23:01 | 14169.10 | 0.00 |
July | 0.00 | 0.00 | 0.853452E+10 | 0.605082E+10 | 25558.19 | 03-JUL-21:30 | 12147.72 | 0.00 |
August | 0.00 | 0.00 | 0.843176E+10 | 0.600583E+10 | 26222.75 | 04-AUG-00:25 | 11352.35 | 0.00 |
September | 0.00 | 0.00 | 0.326813E+10 | 0.285438E+10 | 23213.93 | 11-SEP-19:05 | 16604.94 | 0.00 |
October | 0.00 | 0.00 | 7335014.76 | 7334999.71 | 1753.25 | 20-OCT-15:00 | 1753.25 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.268689E+11 | 0.199266E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.853452E+10 | 0.605082E+10 | 26222.75 | 16908.20 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 61880921.01 | 37566943.36 | 7416.39 | 18-APR-15:00 | 4626.95 | 0.00 |
May | 0.00 | 0.00 | 0.464848E+09 | 0.336150E+09 | 16106.66 | 31-MAY-15:10 | 12469.89 | 0.00 |
June | 0.00 | 0.00 | 0.822031E+10 | 0.559652E+10 | 70707.12 | 26-JUN-19:55 | 42394.93 | 0.00 |
July | 0.00 | 0.00 | 0.134507E+11 | 0.852620E+10 | 74322.18 | 03-JUL-19:45 | 37686.84 | 0.00 |
August | 0.00 | 0.00 | 0.109600E+11 | 0.708166E+10 | 76036.26 | 03-AUG-19:05 | 35343.62 | 0.00 |
September | 0.00 | 0.00 | 0.413277E+10 | 0.333845E+10 | 67341.57 | 11-SEP-17:15 | 46442.40 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.372905E+11 | 0.249165E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.134507E+11 | 0.852620E+10 | 76036.26 | 46442.40 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.178561E+10 | 0.08 | 671.63 | 01-JAN-00:02 | 0.08 |
February | 0.157633E+10 | 0.08 | 671.63 | 01-FEB-00:01 | 0.08 |
March | 0.131725E+10 | 0.06 | 671.63 | 01-MAR-00:01 | 0.08 |
April | 0.493316E+09 | 0.02 | 671.63 | 01-APR-00:10 | 0.08 |
May | 20552023.13 | 0.00 | 671.63 | 01-MAY-22:20 | 0.08 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.169789E+09 | 0.01 | 671.63 | 15-OCT-21:37 | 0.08 |
November | 0.112518E+10 | 0.05 | 671.63 | 10-NOV-00:40 | 0.08 |
December | 0.178077E+10 | 0.08 | 671.63 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.826880E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.178561E+10 | 0.08 | 671.63 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.147413E+10 | 0.80 | 1219.86 | 02-JAN-07:20 | 0.95 |
February | 0.130604E+10 | 0.75 | 1219.86 | 08-FEB-16:00 | 0.95 |
March | 0.142951E+10 | 0.63 | 1219.86 | 14-MAR-10:00 | 0.95 |
April | 0.126343E+10 | 0.47 | 1219.86 | 01-APR-10:50 | 0.95 |
May | 0.127383E+10 | 0.39 | 1219.86 | 02-MAY-08:70 | 0.95 |
June | 0.137534E+10 | 0.45 | 1219.86 | 14-JUN-08:15 | 0.94 |
July | 0.143835E+10 | 0.47 | 1219.86 | 06-JUL-06:40 | 0.94 |
August | 0.150561E+10 | 0.49 | 1219.86 | 02-AUG-15:00 | 0.94 |
September | 0.128609E+10 | 0.41 | 1219.86 | 05-SEP-08:65 | 0.95 |
October | 0.123376E+10 | 0.38 | 1219.86 | 07-OCT-07:50 | 0.95 |
November | 0.126636E+10 | 0.58 | 1219.86 | 04-NOV-08:30 | 0.95 |
December | 0.139310E+10 | 0.75 | 1219.86 | 30-DEC-11:10 | 0.95 |
Annual Sum or Average | 0.162455E+11 | 0.55 | |||
Minimum of Months | 0.123376E+10 | 0.38 | 1219.86 | 0.94 | |
Maximum of Months | 0.150561E+10 | 0.80 | 1219.86 | 0.95 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.274397E+10 | 0.68 | 2641.76 | 01-JAN-01:23 | 0.92 |
February | 0.215846E+10 | 0.64 | 2641.76 | 01-FEB-00:01 | 0.93 |
March | 0.186995E+10 | 0.56 | 2641.76 | 01-MAR-00:01 | 0.93 |
April | 0.133186E+10 | 0.41 | 2641.76 | 01-APR-05:11 | 0.92 |
May | 0.110589E+10 | 0.23 | 2014.49 | 02-MAY-05:21 | 0.92 |
June | 0.112876E+10 | 0.24 | 2641.76 | 25-JUN-13:53 | 0.91 |
July | 0.110243E+10 | 0.22 | 2641.76 | 02-JUL-13:23 | 0.91 |
August | 0.115700E+10 | 0.23 | 2574.73 | 03-AUG-17:08 | 0.89 |
September | 0.105727E+10 | 0.22 | 1641.33 | 08-SEP-17:10 | 0.72 |
October | 0.117547E+10 | 0.35 | 2357.04 | 26-OCT-05:01 | 0.92 |
November | 0.173722E+10 | 0.52 | 2641.76 | 10-NOV-03:23 | 0.92 |
December | 0.240408E+10 | 0.65 | 2641.76 | 01-DEC-00:03 | 0.92 |
Annual Sum or Average | 0.189724E+11 | 0.41 | |||
Minimum of Months | 0.105727E+10 | 0.22 | 1641.33 | 0.72 | |
Maximum of Months | 0.274397E+10 | 0.68 | 2641.76 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.147413E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.130604E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.142951E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.133667E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.143854E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.262098E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.330084E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.336010E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.202941E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.123551E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.126636E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.139310E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.221912E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.123551E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.336010E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.274397E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.215846E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.186995E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.134801E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.122715E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.314214E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.428186E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.379520E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.210622E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.117547E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.173722E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.240408E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.279897E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.117547E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.428186E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.147413E+10 | 0.00 | 0.171595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130604E+10 | 0.00 | 0.128587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142951E+10 | 0.00 | 0.950875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126343E+10 | 0.313387E+09 | 0.451071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.127383E+10 | 0.712915E+09 | 0.678623E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137534E+10 | 0.560080E+10 | 56617932.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143835E+10 | 0.853452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150561E+10 | 0.843176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128609E+10 | 0.326813E+10 | 0.288012E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123376E+10 | 7335014.76 | 0.224243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126636E+10 | 0.00 | 0.733910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139310E+10 | 0.00 | 0.130407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162455E+11 | 0.268689E+11 | 0.676832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150561E+10 | 0.853452E+10 | 0.171595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.274397E+10 | 0.00 | 0.688321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.215846E+10 | 0.00 | 0.479709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.186995E+10 | 0.00 | 0.288557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133186E+10 | 61880921.01 | 0.106417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.110589E+10 | 0.464848E+09 | 0.637606E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112876E+10 | 0.816898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110243E+10 | 0.130094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.115700E+10 | 0.107814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105727E+10 | 0.407353E+10 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.117547E+10 | 0.00 | 0.462224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.173722E+10 | 0.00 | 0.285022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.240408E+10 | 0.00 | 0.544740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189724E+11 | 0.365600E+11 | 0.244747E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.105727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.274397E+10 | 0.130094E+11 | 0.688321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.147413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126343E+10 | 0.00 | 0.00 | 0.00 | 73238758.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.127383E+10 | 0.00 | 0.00 | 0.00 | 0.164715E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137534E+10 | 0.00 | 0.00 | 0.00 | 0.124564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143835E+10 | 0.00 | 0.00 | 0.00 | 0.186249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150561E+10 | 0.00 | 0.00 | 0.00 | 0.185450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128609E+10 | 0.00 | 0.00 | 0.00 | 0.743311E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123376E+10 | 0.00 | 0.00 | 0.00 | 1750394.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162455E+11 | 0.00 | 0.00 | 0.00 | 0.594564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150561E+10 | 0.00 | 0.00 | 0.00 | 0.186249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.274397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.215846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.186995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133186E+10 | 0.00 | 0.00 | 0.00 | 16156226.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.110589E+10 | 0.00 | 0.00 | 0.00 | 0.121256E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112876E+10 | 0.00 | 0.00 | 0.00 | 0.201338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110243E+10 | 0.00 | 0.00 | 0.00 | 0.317942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.115700E+10 | 0.00 | 0.00 | 0.00 | 0.263820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105727E+10 | 0.00 | 0.00 | 0.00 | 0.104895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.117547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.173722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.240408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189724E+11 | 0.00 | 0.00 | 0.00 | 0.901736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.105727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.274397E+10 | 0.00 | 0.00 | 0.00 | 0.317942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379767E+10 | 0.00 | 0.00 | 0.12 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295741E+10 | 0.00 | 0.00 | 0.13 |
March | 40292467.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237768E+10 | 0.00 | 0.00 | 0.13 |
April | 0.238457E+09 | 35822264.79 | 0.00 | 104702.35 | 3670272.75 | 0.137028E+10 | 0.134074E+09 | 0.00 | 0.15 |
May | 0.502034E+09 | 39616081.18 | 0.00 | 768599.70 | 0.00 | 0.132338E+09 | 0.901288E+09 | 0.00 | 0.29 |
June | 0.161186E+09 | 0.579464E+09 | 0.00 | 2994144.98 | 0.00 | 5551748.73 | 0.146574E+10 | 0.00 | 0.57 |
July | 11943989.66 | 0.904118E+09 | 0.00 | 3885659.14 | 322435.32 | 0.00 | 0.120407E+10 | 0.00 | 0.68 |
August | 9229636.26 | 0.920669E+09 | 0.00 | 4293106.00 | 3912374.60 | 0.00 | 0.144773E+10 | 0.00 | 0.74 |
September | 0.337978E+09 | 0.152734E+09 | 0.00 | 3141073.98 | 0.00 | 86593398.71 | 0.157384E+10 | 0.00 | 0.45 |
October | 0.596513E+09 | 0.00 | 0.00 | 23696.01 | 0.00 | 0.867333E+09 | 55958210.82 | 0.00 | 0.14 |
November | 0.244641E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193061E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317622E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.214227E+10 | 0.263242E+10 | 0.00 | 15210982.18 | 7905082.67 | 0.167017E+11 | 0.678271E+10 | 0.00 | 0.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.596513E+09 | 0.920669E+09 | 0.00 | 4293106.00 | 3912374.60 | 0.379767E+10 | 0.157384E+10 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.382591E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123850E+11 | 0.00 | 0.00 | 0.17 |
February | 0.121447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.832801E+10 | 0.00 | 0.00 | 0.18 |
March | 0.313939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394468E+10 | 0.00 | 0.00 | 0.19 |
April | 0.385159E+10 | 1103605.13 | 0.00 | 16134.42 | 35087725.02 | 0.954771E+09 | 4318971.95 | 0.00 | 0.18 |
May | 0.314963E+10 | 40579503.36 | 0.00 | 107923.76 | 1694939.71 | 22039404.70 | 28221909.54 | 0.00 | 0.19 |
June | 0.164807E+10 | 0.927224E+09 | 0.00 | 3568759.28 | 0.00 | 0.00 | 0.183030E+10 | 0.00 | 0.31 |
July | 0.533146E+09 | 0.177369E+10 | 0.00 | 6901735.52 | 0.00 | 0.00 | 0.221804E+10 | 0.00 | 0.38 |
August | 0.530185E+09 | 0.139345E+10 | 0.00 | 6446185.22 | 0.00 | 0.00 | 0.263241E+10 | 0.00 | 0.38 |
September | 0.260463E+10 | 0.303935E+09 | 0.00 | 2308200.28 | 0.00 | 4296338.73 | 0.117125E+10 | 0.00 | 0.24 |
October | 0.398746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149328E+09 | 0.00 | 0.00 | 0.17 |
November | 0.225734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426969E+10 | 0.00 | 0.00 | 0.17 |
December | 0.901960E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.929339E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.242005E+11 | 0.443998E+10 | 0.00 | 19348938.48 | 36782664.73 | 0.393512E+11 | 0.788455E+10 | 0.00 | 0.23 |
Minimum of Months | 0.382591E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.398746E+10 | 0.177369E+10 | 0.00 | 6901735.52 | 35087725.02 | 0.123850E+11 | 0.263241E+10 | 0.00 | 0.38 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.383326E+12 | 0.242842E+12 | 0.00 | 0.165653E+11 | 0.109527E+12 |
February | 0.446488E+12 | 0.170088E+12 | 0.00 | 0.124999E+11 | 0.749989E+11 |
March | 0.725471E+12 | 0.118891E+12 | 0.00 | 0.950204E+10 | 0.431037E+11 |
April | 0.886788E+12 | 0.562664E+11 | 0.00 | 0.647936E+10 | 0.130475E+11 |
May | 0.105573E+13 | 0.320115E+11 | 0.00 | 0.465847E+10 | 0.215548E+10 |
June | 0.111987E+13 | 0.358717E+11 | 0.00 | 0.363171E+10 | 0.171075E+11 |
July | 0.114758E+13 | 0.400378E+11 | 0.00 | 0.136610E+10 | 0.270271E+11 |
August | 0.993946E+12 | 0.473400E+11 | 0.00 | 0.250717E+10 | 0.238845E+11 |
September | 0.690525E+12 | 0.514702E+11 | 0.00 | 0.539123E+10 | 0.943717E+10 |
October | 0.481674E+12 | 0.478081E+11 | 0.00 | 0.565662E+10 | 0.402136E+10 |
November | 0.268912E+12 | 0.123012E+12 | 0.00 | 0.870229E+10 | 0.436595E+11 |
December | 0.192763E+12 | 0.192252E+12 | 0.00 | 0.133716E+11 | 0.853686E+11 |
Annual Sum or Average | 0.839307E+13 | 0.115789E+13 | 0.00 | 0.903317E+11 | 0.453338E+12 |
Minimum of Months | 0.192763E+12 | 0.320115E+11 | 0.00 | 0.136610E+10 | 0.215548E+10 |
Maximum of Months | 0.114758E+13 | 0.242842E+12 | 0.00 | 0.165653E+11 | 0.109527E+12 |