Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Simulation Timestamp: 2023-10-16 10:41:47
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 640.27 | 132.42 | 132.42 |
Net Site Energy | 640.27 | 132.42 | 132.42 |
Total Source Energy | 2027.74 | 419.38 | 419.38 |
Net Source Energy | 2027.74 | 419.38 | 419.38 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 191.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 134.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 92.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 62.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 640.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 191.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 134.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 92.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 32.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 30.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 22.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 191.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 134.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 92.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 62.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 22.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 47.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 57.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 132.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 47.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 57.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 132.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 640.272 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 640.272 | 100.00 |
Total On-Site and Utility Electric Sources | 640.272 | 100.00 |
Total Electricity End Uses | 640.272 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 102.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3636.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Latitude [deg] | 10.82 |
Longitude [deg] | 106.67 |
Elevation [m] | 5.00 |
Time Zone | 7.00 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 119.93 |
Skylight-Roof Ratio [%] | 2.61 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.8432 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 10.2257 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 6.2431 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.6162 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.6162 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.8432 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 10.2257 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 6.2431 | 46.45 | 2.5587 | |
Total | 4835.13 | 7.6162 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 7.6162 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 7.6162 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 06-MAY-15:09 | - | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 22812.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8295.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5508.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1288.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 47940.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 22812.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 8295.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 3203.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1288.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 606.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 426.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 199.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 69.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2027.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 125.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 88.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 41.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 419.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 125.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 88.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 41.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 419.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.24 |
ZONE2 FINE STORAGE DIRECT AIR | 3.17 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 0.976836 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 0.976836 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 39959.00 |
PSZ-OFFICE HEATING COIL | 28354.35 |
PSZ-FINE STORAGE HEATING COIL | 143219.78 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 0.000000 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.00 | 1.00 | 1.24 |
PSZ-FINE STORAGE | 3.17 | 3.17 | 3.17 | 3.17 | 3.17 | 3.17 | 1.00 | 1.00 | 3.17 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.24 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 3.17 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.24 | 1367.55 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.17 | 3396.19 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.24 | 1.24 | 1.24 | 0.815223 | 25825.00 | 28354.35 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 3.17 | 3.17 | 3.17 | 2.09 | 78814.68 | 143219.78 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.24 | 0.617593 | 0.823460 | 25825.00 | 12912.50 | 0.759090 | 0.759090 |
PSZ-FINE STORAGE COOLING COIL | 3.17 | 1.59 | 2.12 | 78814.68 | 39407.34 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.90 | 26.70 | 26.00 | 26.40 | 27.50 | 28.30 | 29.20 | 29.00 | 28.90 | 27.20 | 27.50 | 27.60 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 | 10.82 | 106.67 | 7.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.60 | 3.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.843 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.917 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 10.226 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.226 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 6.243 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 8.802 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2568.536 | 10.843 | 201.474 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2568.536 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 14248.589 | 10.226 | 474.953 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 14248.589 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 20008.023 | 6.243 | 289.971 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20008.023 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2405 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.7173 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.6534 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 2.825 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 2.825 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.158 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.394 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.431 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2546 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2546 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.77015739E-08 | 0.38457199E-13 | 0.23136523E-13 | 0.0000000 |
2 | 1 | -5.2160498 | 0.48395528E-04 | -0.66612159E-04 | 0.14765390E-08 |
3 | 0 | 5.4565497 | 0.24045158 | 0.24056658 | |
4 | 2 | 0.53311453E-11 | 0.59398160E-16 | 0.15345153E-15 | 0.0000000 |
5 | 1 | -5.2159564 | 0.46378490E-04 | -0.22332804E-04 | 0.68713370E-11 |
6 | 0 | 5.9333026 | 0.71729982 | 0.71736853 | |
7 | 4 | 0.74747876E-12 | 0.20825084E-15 | -0.25659737E-14 | 0.12362927E-15 |
8 | 3 | -0.37328678E-03 | 0.45238042E-06 | -0.54038165E-04 | 0.14344535E-12 |
9 | 2 | 1.7123825 | 0.10013958E-01 | 1.1198054 | -0.71564441E-04 |
10 | 1 | -7.1648294 | 0.26145347 | -16.966117 | 0.32817431 |
11 | 0 | 5.8918369 | 0.16754891 | 16.285382 | |
12 | 4 | 0.33466332E-12 | 0.89461943E-14 | -0.12859024E-13 | 0.20877214E-15 |
13 | 3 | -0.22871403E-03 | 0.15053116E-05 | -0.31975464E-04 | 0.68322840E-13 |
14 | 2 | 1.3386772 | 0.41030944E-01 | 0.83718830 | -0.43809927E-04 |
15 | 1 | -7.7424045 | 1.2165027 | -15.097018 | 0.25560053 |
16 | 0 | 8.5066984 | 0.84520726 | 16.362604 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.12859024E-13 | 0.89461943E-14 | 0.33466332E-12 | 0.20877214E-15 |
85 | 3 | -0.31975464E-04 | 0.15053116E-05 | -0.22871403E-03 | 0.68322840E-13 |
86 | 2 | 0.83718830 | 0.41030944E-01 | 1.3386772 | -0.43809927E-04 |
87 | 1 | -15.097018 | 1.2165027 | -7.7424045 | 0.25560053 |
88 | 0 | 16.362604 | 0.84520726 | 8.5066984 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.569_SHGC_SOUTH_0.25 | 34 | 1 | VerySmooth | 3.235 | 3.235 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.569_SHGC_NORTH_0.25 | 35 | 1 | VerySmooth | 3.235 | 3.235 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.569_SHGC_EAST_0.25 | 36 | 1 | VerySmooth | 3.235 | 3.235 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.569_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 3.235 | 3.235 | 1.000 | 0.251 | ||
5 | SKYLIGHT_U_0.75_SHGC_0.35 | 38 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.356 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60218 | 0.60218 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43216E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60218 | 0.60218 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43216E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60218 | 0.60218 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43216E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60218 | 0.60218 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43216E-002 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.20312 | 0.36283 | 0.36283 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | CurtainWall | 4.099 | 0.350 | 0.402 |
2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.799 | 0.390 | 0.214 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.710 | 8.455E-004 | 5.523E-004 | 0.277 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.9537E-005 |
2 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2785E-004 |
3 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.2400E-005 |
4 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.7469E-004 |
5 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8228E-005 |
6 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.5763E-004 |
7 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0405E-004 |
8 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.7737E-004 |
9 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6179E-004 |
10 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6260E-004 |
11 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4126E-004 |
12 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.7387E-004 |
13 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4541E-004 |
14 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4613E-004 |
15 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4902E-004 |
16 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5698E-004 |
17 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.0799E-004 |
18 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1781E-004 |
19 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5653E-004 |
20 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1999E-004 |
21 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.5032E-004 |
22 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0851E-004 |
23 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.0972E-004 |
24 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.3095E-005 |
25 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.6550E-004 |
26 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6736E-005 |
27 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3959E-004 |
28 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.7513E-005 |
29 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2064E-003 |
30 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.3161E-005 |
31 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3671E-003 |
32 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4800E-005 |
33 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.6526E-004 |
34 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3229E-005 |
35 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.1837E-004 |
36 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3852E-005 |
37 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3315E-004 |
38 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.2455E-005 |
39 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1725E-004 |
40 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9365E-005 |
41 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.2600E-004 |
42 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8065E-005 |
43 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.4213E-004 |
44 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8715E-005 |
45 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1006E-004 |
46 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8630E-005 |
47 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9265E-004 |
48 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7452E-005 |
49 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.9115E-004 |
50 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8322E-005 |
51 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.3144E-004 |
52 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8968E-005 |
53 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.5280E-004 |
54 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8817E-005 |
55 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5174E-004 |
56 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7546E-005 |
57 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4928E-003 |
58 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4026E-005 |
59 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8703E-003 |
60 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4654E-005 |
61 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3411E-003 |
62 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3057E-005 |
63 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1384E-003 |
64 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9663E-005 |
65 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.6914E-003 |
66 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.9719E-005 |
67 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8060E-003 |
68 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.0609E-005 |
69 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3934E-003 |
70 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.5531E-005 |
71 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.6075E-003 |
72 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.5940E-005 |
73 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7579E-004 |
74 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3240E-004 |
75 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8869E-004 |
76 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3572E-004 |
77 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.5598E-004 |
78 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2072E-004 |
79 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6603E-003 |
80 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.8724E-005 |
81 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0001E-004 |
82 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.6558E-004 |
83 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7163E-004 |
84 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.9053E-004 |
85 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7702E-004 |
86 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.3509E-004 |
87 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.4798E-004 |
88 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9480E-004 |
89 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.6809E-005 |
90 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7697E-003 |
91 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.7963E-005 |
92 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0172E-003 |
93 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.2465E-005 |
94 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6471E-003 |
95 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1688E-004 |
96 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.0623E-004 |
97 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.9017E-005 |
98 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.2490E-003 |
99 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.6142E-005 |
100 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.5356E-003 |
101 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.3333E-005 |
102 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.9079E-003 |
103 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.2593E-005 |
104 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.2186E-003 |
105 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7250E-005 |
106 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0502E-003 |
107 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.4820E-005 |
108 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0510E-003 |
109 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2558E-005 |
110 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2929E-003 |
111 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.0323E-005 |
112 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2689E-003 |
113 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1729E-005 |
114 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5140E-005 |
115 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8675E-005 |
116 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8978E-005 |
117 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6344E-005 |
118 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4187E-005 |
119 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4598E-005 |
120 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5286E-005 |
121 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2964E-005 |
122 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7173E-005 |
123 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7330E-005 |
124 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2807E-005 |
125 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3040E-005 |
126 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9195E-005 |
127 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1685E-005 |
128 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2542E-005 |
129 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1702E-005 |
130 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0598E-005 |
131 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8582E-005 |
132 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9983E-005 |
133 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5916E-005 |
134 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9484E-005 |
135 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4582E-005 |
136 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1042E-005 |
137 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0976E-004 |
138 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8747E-005 |
139 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1334E-004 |
140 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8914E-005 |
141 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.7139E-005 |
142 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2640E-005 |
143 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2514E-005 |
144 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3080E-005 |
145 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2697E-005 |
146 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1954E-004 |
147 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2470E-005 |
148 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2404E-004 |
149 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7968E-005 |
150 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0539E-004 |
151 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4916E-005 |
152 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6240E-005 |
153 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9545E-005 |
154 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2841E-005 |
155 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8750E-005 |
156 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2475E-005 |
157 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5931E-005 |
158 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2332E-005 |
159 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4899E-005 |
160 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1079E-005 |
161 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0570E-004 |
162 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4978E-005 |
163 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0838E-004 |
164 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4083E-005 |
165 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.4856E-005 |
166 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2969E-005 |
167 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2500E-005 |
168 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7738E-005 |
169 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.9382E-005 |
170 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6450E-004 |
171 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.8360E-005 |
172 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9586E-004 |
173 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5562E-005 |
174 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2863E-004 |
175 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0532E-005 |
176 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7293E-004 |
177 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9722E-004 |
178 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5274E-004 |
179 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1815E-004 |
180 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5368E-004 |
181 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7238E-004 |
182 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4948E-004 |
183 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5069E-004 |
184 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0290E-004 |
185 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7587E-004 |
186 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7334E-005 |
187 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9173E-004 |
188 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5195E-005 |
189 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5966E-004 |
190 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5490E-005 |
191 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5061E-004 |
192 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8433E-005 |
193 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2068E-005 |
194 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5218E-005 |
195 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9756E-005 |
196 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4460E-005 |
197 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0087E-005 |
198 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4435E-005 |
199 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0473E-005 |
200 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3210E-005 |
201 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6592E-004 |
202 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1305E-005 |
203 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.4441E-004 |
204 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6991E-005 |
205 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9245E-004 |
206 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0856E-005 |
207 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2387E-004 |
208 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6113E-005 |
209 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.9862E-004 |
210 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0008E-004 |
211 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1106E-003 |
212 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9911E-004 |
213 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.7987E-004 |
214 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2884E-004 |
215 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2445E-004 |
216 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5215E-004 |
217 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3927E-004 |
218 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7278E-005 |
219 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3257E-004 |
220 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6065E-005 |
221 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4681E-004 |
222 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6225E-005 |
223 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2708E-004 |
224 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5686E-005 |
225 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5237E-004 |
226 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8106E-003 |
227 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4773E-004 |
228 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1033E-003 |
229 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5890E-004 |
230 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5847E-003 |
231 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2726E-004 |
232 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9459E-004 |
233 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6573E-004 |
234 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8103E-005 |
235 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5139E-004 |
236 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6542E-005 |
237 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8216E-004 |
238 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6697E-005 |
239 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9961E-004 |
240 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7482E-005 |
241 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4623E-003 |
242 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7982E-005 |
243 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5267E-003 |
244 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1343E-005 |
245 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7894E-003 |
246 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7853E-005 |
247 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6165E-003 |
248 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3274E-005 |
249 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6573E-003 |
250 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0196E-004 |
251 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7667E-003 |
252 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8054E-004 |
253 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9796E-003 |
254 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8396E-004 |
255 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6195E-003 |
256 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2024E-004 |
257 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7909E-004 |
258 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5815E-003 |
259 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6627E-004 |
260 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0506E-003 |
261 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9821E-004 |
262 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0355E-003 |
263 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0001E-004 |
264 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6530E-003 |
265 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3750E-004 |
266 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7224E-005 |
267 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2079E-004 |
268 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5599E-005 |
269 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4190E-004 |
270 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5439E-005 |
271 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9852E-004 |
272 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7461E-005 |
273 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4411E-004 |
274 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1301E-003 |
275 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2784E-004 |
276 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0463E-003 |
277 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5244E-004 |
278 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3848E-003 |
279 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9891E-004 |
280 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6031E-003 |
281 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2212E-004 |
282 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1064E-005 |
283 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5222E-004 |
284 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.3946E-005 |
285 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7674E-004 |
286 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7929E-005 |
287 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5919E-003 |
288 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3045E-005 |
289 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5679E-004 |
290 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8682E-004 |
291 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9079E-004 |
292 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5201E-004 |
293 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3066E-004 |
294 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2473E-004 |
295 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5949E-003 |
296 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1554E-004 |
297 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1946E-005 |
298 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9360E-004 |
299 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0455E-005 |
300 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4715E-004 |
301 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5933E-005 |
302 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9225E-004 |
303 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2574E-004 |
304 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7337E-004 |
305 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4363E-004 |
306 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4474E-004 |
307 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0600E-004 |
308 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2329E-004 |
309 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4276E-004 |
310 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3591E-004 |
311 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1039E-004 |
312 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4748E-004 |
313 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2958E-005 |
314 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6385E-005 |
315 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7278E-005 |
316 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4471E-005 |
317 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2745E-005 |
318 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2789E-005 |
319 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1671E-005 |
320 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7584E-005 |
321 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0134E-005 |
322 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5104E-005 |
323 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8472E-005 |
324 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3714E-005 |
325 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1842E-005 |
326 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3194E-005 |
327 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2556E-004 |
328 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5637E-005 |
329 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8355E-005 |
330 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0633E-004 |
331 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2146E-005 |
332 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.9981E-005 |
333 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0337E-005 |
334 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.6987E-005 |
335 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9741E-005 |
336 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6869E-004 |
337 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.7208E-005 |
338 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5107E-005 |
339 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2864E-005 |
340 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5201E-005 |
341 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0450E-005 |
342 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1999E-005 |
343 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4732E-004 |
344 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0119E-004 |
345 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8025E-005 |
346 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2673E-005 |
347 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1701E-005 |
348 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1672E-005 |
349 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9027E-005 |
350 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1038E-005 |
351 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9684E-005 |
352 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3161E-005 |
353 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4030E-004 |
354 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6859E-005 |
355 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0244E-004 |
356 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1341E-005 |
357 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3496E-004 |
358 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1154E-005 |
359 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0983E-004 |
360 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5702E-005 |
361 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6922E-005 |
362 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4383E-005 |
363 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2471E-005 |
364 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0924E-005 |
365 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.9131E-005 |
366 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9062E-005 |
367 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4724E-004 |
368 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8139E-005 |
369 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 3.4688E-003 |
370 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 4.2555E-004 |
371 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 3.0298E-003 |
372 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.8509E-004 |
373 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.5070E-003 |
374 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.4882E-004 |
375 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.9731E-003 |
376 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.4928E-004 |
377 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.2294E-004 |
378 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.9598E-003 |
379 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.8609E-004 |
380 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.3251E-003 |
381 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.5273E-004 |
382 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.7357E-003 |
383 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.4525E-004 |
384 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.6476E-003 |
385 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.8524E-003 |
386 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.1743E-004 |
387 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.1878E-003 |
388 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.7739E-004 |
389 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.3214E-003 |
390 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.3249E-004 |
391 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.4770E-003 |
392 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.1257E-004 |
393 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.8426E-003 |
394 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.1734E-004 |
395 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.1909E-003 |
396 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.7735E-004 |
397 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.3691E-003 |
398 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.3257E-004 |
399 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.4769E-003 |
400 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.1257E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 12503.73570 | 15004.48284 | 1.02932 | 1.23519 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 | 34.69000 | 1.71572E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 1589.07967 | 1906.89561 | 4.40670E-002 | 0.10228 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 20.10000 | 1.47983E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 41211.13091 | 49453.35709 | 2.64489 | 3.17387 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 35.20000 | 1.71581E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 0.00000 | 0.00000 | 0.00000 | 0.42471 | 00:10:00 | 20.10000 | 1.47983E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 | |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 35.20000 | 1.71581E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 0.00000 | 0.00000 | 0.00000 | 0.97684 | 00:10:00 | 20.10000 | 1.47983E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 19117.15 | 1.23519 | 1.23519 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 2461.78 | 0.10228 | 0.10228 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 60778.71 | 3.17387 | 3.17387 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 10221.91 | 0.42471 | 0.42471 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.23519 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.17387 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.97684 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 0.97684 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 39959.00499 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 0.00000 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.23519 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.23519 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.23519 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.23519 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.23519 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.23519 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.17387 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.17387 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.17387 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.17387 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.17387 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.17387 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.23519 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.17387 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.23519 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.23519 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1367.54745 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.23519 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.23519 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.23519 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.81522 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.23519 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61759 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.82346 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25825.00000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12912.50000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75909 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75909 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25825.00000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28354.34650 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 28354.34650 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.17387 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.17387 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3396.18790 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.17387 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.17387 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.17387 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.09475 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.17387 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.58693 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.11591 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 78814.68000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 39407.34000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 78814.68000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 143219.78017 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 143219.78017 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 24865.7 | 11.92 | 11.65 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 76347.7 | 11.12 | 10.87 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 1.7605883648E-002 | 1.5146854199E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.2057616443 | 0.2275529810 | Pass | Pass | 0.4196232422 | 1.8703628333 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 4.4926241874E-002 | 4.4338546080E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 11321.16 | 634.86 | 0.00 | -259.7 | 927.71 | 12624.07 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10 | 0.00 | 20.10 | Wetbulb [C] | 1.80 | 0.00 |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20 | 8.50 | 25.80 | Wetbulb [C] | 4.10 | 160.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 57.00 | 12 | |||
Feb | 0.00 | 0 | |||
Mar | 153.60 | 31 | |||
Apr | 87.00 | 59 | |||
May | 227.22 | 128 | |||
Jun | 144.58 | 109 | |||
Jul | 42.40 | 24 | |||
Aug | 164.90 | 163 | |||
Sep | 119.60 | 50 | |||
Oct | 365.70 | 188 | |||
Nov | 70.90 | 67 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.233 | 0.240 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.985 | 2.825 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.985 | 2.825 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.985 | 2.825 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.653 | 0.717 | 3204.84 | 3105.72 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.685 | 2.825 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.685 | 2.825 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.569_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.235 | 0.251 | 0.276 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.569_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.235 | 0.251 | 0.276 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.569_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.235 | 0.251 | 0.276 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.569_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.235 | 0.251 | 0.276 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 137.59 | 5.237 | 0.483 | 0.385 | |||||||||||||||||
North Total or Average | 6.51 | 3.235 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 131.09 | 5.337 | 0.494 | 0.391 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.8432 | 236.88 | 2568.54 | LightsWired | LTG_SCH_OFFICE | 52.33 | 168.00 | 42.61 | 0.0000 | Y | 20.54 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 10.2257 | 1393.41 | 14248.59 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 19.06 | 0.0000 | Y | 50.97 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 6.2431 | 3204.84 | 20008.02 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 16.80 | 0.0000 | Y | 63.10 |
Interior Lighting Total | 7.6162 | 4835.13 | 36825.15 | 134.62 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 14248.59 | 3562.15 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 14248.59 | 3562.15 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 20008.02 | 5002.01 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 20008.02 | 5002.01 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.29 | 2568.54 | 744.88 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.10 | 2568.54 | 256.85 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 125.92 | AstronomicalClock | - | 41.93 | 41.93 | 0.99 | |
EXTERIOR_LIGHTS_B | 6860.50 | AstronomicalClock | - | 83.83 | 71.26 | 91.77 | |
Exterior Lighting Total | 6986.42 | 92.76 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25825.00 | 19603.50 | 6221.50 | 0.76 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 78814.68 | 55255.40 | 23559.28 | 0.70 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 24865.7 | 11.92 | 11.65 | ||||
PSZ-FINE STORAGE COOLING COIL | 76347.7 | 11.12 | 10.87 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 39959.00 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 28354.35 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 143219.78 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.98 | 90.76 | 92.91 | 1.00 | 4.17 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.24 | 1367.55 | 1107.16 | 1.00 | 1.35 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 3.17 | 3396.19 | 1070.05 | 1.00 | 1.26 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 12503.74 | 15004.48 | 63.34 | 1.029 | 1.235 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 | 23.90 | 23.90 | 0.00855 | 34.69 | 0.01716 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 41211.13 | 49453.36 | 35.49 | 2.645 | 3.174 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 26.70 | 26.70 | 0.00912 | 35.20 | 0.01716 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 0.00 | 35.70 | 0.01724 | 35.20 | 0.01716 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 1589.08 | 1906.90 | 8.05 | 0.044 | 0.102 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.01389 | 20.10 | 0.01480 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.425 | 00:10:00 | 15.56 | 18.45 | 0.01332 | 20.10 | 0.01480 | 0.425 | 0.00 | |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | 00:10:00 | 10.00 | 17.92 | 0.01288 | 20.10 | 0.01480 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.24 | 1.24 | 0.10 | 0.10 | 1.2352 | 1.2352 | 1.2352 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.17 | 3.17 | 0.42 | 0.42 | 3.1739 | 3.1739 | 3.1739 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 39959.005 | 39959.005 | -999.0 | -999.0 | -999.000 | 12/21 00:10:00 | 12/21 00:10:00 | 39959.00 | 39959.00 | 0.976836 | 10.00 | 10.00 | 0.00800000 | 43.33 | 22.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 10.00 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | ||
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 25825.000 | 19603.499 | 1.235190 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 | 12912.50 | 10665.09 | 0.823460 | 25.70 | 17.62 | 0.00926534 | 12.00 | 11.25 | 0.00800000 | 34.78 | 0.01715734 | 25.72 | 12.4213 | 23.90 | 0.00855272 | 46.2982 | 12502.21 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 28354.346 | 28354.346 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 28354.35 | 28354.35 | 1.235186 | 21.02 | 20.01 | 0.01428291 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 8.2809 | 19.49 | 0.01423637 | 99.9999 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 78814.680 | 55255.396 | 3.173870 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 39407.34 | 30194.66 | 2.115913 | 28.70 | 19.34 | 0.01019391 | 12.00 | 11.25 | 0.00800000 | 35.20 | 0.01715815 | 25.83 | 20.0722 | 26.70 | 0.00911802 | 41.7538 | 41211.13 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 143219.780 | 143219.780 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 143219.78 | 143219.78 | 3.173867 | 2.69 | 2.69 | 0.01351662 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 13.3815 | 18.45 | 0.01331862 | 99.9999 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 39959.005 | 39959.005 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.976836 | 1.17571482 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 39959.00 | 39959.00 | 1.0000 | 1.17571482 | 0.976836 | 10.00 | 10.00 | 0.00800000 | 30204.6 | 43.33 | 22.14 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39959.00 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 10.00 | 0.00800000 | 10.00 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25825.000 | 19603.499 | 1.235190 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.0638 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.235186 | 1.48666419 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 | Sensible | 12912.50 | 10665.09 | 1.0000 | 0.99111232 | 0.823460 | 25.70 | 17.62 | 0.00926534 | 49437.6 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12912.50 | 34.78 | 0.01715734 | 25.72 | 0.10228463 | 12.4213 | 23.90 | 0.00855272 | 23.90 | 0.00855272 | 46.2982 | 12502.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28354.346 | 28354.346 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.235186 | 1.48666419 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 28354.35 | 28354.35 | 1.0000 | 1.48666419 | 1.235186 | 21.02 | 20.01 | 0.01428291 | 57400.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28354.35 | 20.10 | 0.01479830 | 20.10 | 0.10228463 | 8.2809 | 21.10 | 0.01423637 | 19.49 | 0.01423637 | 99.9999 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 78814.680 | 55255.396 | 3.173870 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7900 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.173867 | 3.82005059 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | Sensible | 39407.34 | 30194.66 | 1.0000 | 2.54670267 | 2.115913 | 28.70 | 19.34 | 0.01019391 | 54879.1 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39407.34 | 35.20 | 0.01715815 | 25.83 | 0.42471127 | 20.0722 | 26.70 | 0.00911802 | 26.70 | 0.00911802 | 41.7538 | 41211.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 143219.780 | 143219.780 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.173867 | 3.82005059 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 143219.78 | 143219.78 | 1.0000 | 3.82005059 | 3.173867 | 2.69 | 2.69 | 0.01351662 | 36574.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 143219.78 | 20.10 | 0.01479830 | 20.10 | 0.42471127 | 13.3815 | 0.00 | 0.01331862 | 18.45 | 0.01331862 | 99.9999 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 3636.00 | 960.17 | 960.17 |
ZONE2 FINE STORAGE | 3636.00 | 3623.00 | 3623.00 |
ZONE3 BULK STORAGE | 3636.00 | 3636.00 | 3636.00 |
Facility | 3636.00 | 3636.00 | 3636.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 0.00 | 106.00 | 0.00 | 102.00 |
ZONE2 FINE STORAGE | 0.00 | 334.33 | 0.00 | 0.83 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 440.33 | 0.00 | 102.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.359 | 0.374 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.499 | 0.158 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.60 | 69.00 | 35277.63 | 0.000 | 0.100 | 0.000 | 2.730 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.60 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.60 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.57 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1284038.26 | 0.00 | 1284038.26 | 1771116.47 | 3055154.73 | 3225648.14 | 5366.18 | 3393.82 | 0.00 | 119.72 |
ZONE2 FINE STORAGE | 6040382.05 | 0.00 | 6040382.05 | 4070082.89 | 10110464.94 | 13393694.68 | 5400.87 | 3359.13 | 0.00 | 2391.38 |
ZONE3 BULK STORAGE | 0.00 | 0.51E+09 | 0.51E+09 | 23593493.67 | 0.53E+09 | 30805497.77 | 4788.63 | 0.00 | 3971.37 | 4938.28 |
Total Facility | 7324420.31 | 0.51E+09 | 0.52E+09 | 29434693.03 | 0.54E+09 | 47424840.58 | 6205.46 | 3418.83 | 3971.37 | 4991.35 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.0975 | 0.0000 | 0.0975 | 0.1013 | 0.1989 | 0.1023 | 242.18 | 3393.82 | 0.00 |
ZONE2 FINE STORAGE | 0.3911 | 0.0000 | 0.3911 | 0.1235 | 0.5145 | 0.4247 | 301.62 | 3334.38 | 0.00 |
ZONE3 BULK STORAGE | 0.0000 | 24.9103 | 24.9103 | 0.9167 | 25.8270 | 0.9768 | 1072.42 | 0.00 | 2563.58 |
Total Facility | 0.4886 | 24.9103 | 25.3989 | 1.1415 | 26.5404 | 1.5038 | 1081.46 | 3394.08 | 2563.58 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 1860161.37 | 0.00 | 1860161.37 | 3225648.14 | 5339.99 | 1.72 | 3418.30 | 117.23 |
PSZ-FINE STORAGE | 8750367.70 | 0.00 | 8750367.70 | 13393694.68 | 5322.26 | 13.28 | 3424.46 | 2389.43 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1413 | 0.0000 | 0.1413 | 0.1023 | 218.00 | 1.49 | 3416.51 |
PSZ-FINE STORAGE | 0.5665 | 0.0000 | 0.5665 | 0.4247 | 300.45 | 0.20 | 3335.35 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 3695.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 5811.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1436 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6020 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 429 |
Defaulted Fields | 391 |
Fields with Defaults | 1171 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 640.27 | 1984.66 | 20-AUG-11:20 | 47940.55 | 06-MAY-15:10 |
Electricity:Building | 304.05 | 1455.85 | 17-SEP-13:30 | 25154.13 | 02-JAN-17:00 |
Electricity:Zone:ZONE1 OFFICE | 49.71 | 694.23 | 16-JAN-15:30 | 3408.44 | 02-JAN-17:00 |
Electricity:SpaceType:GENERAL | 271.13 | 1443.59 | 05-MAR-14:30 | 23107.81 | 18-DEC-16:00 |
InteriorLights:Electricity | 134.62 | 973.71 | 05-MAR-14:30 | 13072.63 | 18-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 20.55 | 224.35 | 16-JAN-15:30 | 1573.38 | 02-JAN-17:00 |
InteriorLights:Electricity:SpaceType:GENERAL | 134.62 | 973.71 | 05-MAR-14:30 | 13072.63 | 18-DEC-16:00 |
LightsWired:InteriorLights:Electricity | 134.62 | 973.71 | 05-MAR-14:30 | 13072.63 | 18-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 20.55 | 224.35 | 16-JAN-15:30 | 1573.38 | 02-JAN-17:00 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 134.62 | 973.71 | 05-MAR-14:30 | 13072.63 | 18-DEC-16:00 |
Electricity:Zone:ZONE2 FINE STORAGE | 50.97 | 311.69 | 08-JAN-10:00 | 5298.77 | 18-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 50.97 | 311.69 | 08-JAN-10:00 | 5298.77 | 18-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 50.97 | 311.69 | 08-JAN-10:00 | 5298.77 | 18-DEC-16:00 |
Electricity:Zone:ZONE3 BULK STORAGE | 203.38 | 437.68 | 01-JAN-08:30 | 17070.45 | 02-JAN-17:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 63.10 | 437.68 | 01-JAN-08:30 | 6565.03 | 02-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 63.10 | 437.68 | 01-JAN-08:30 | 6565.03 | 02-JAN-17:00 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 62.97 | 0.00 | 01-JAN-00:10 | 5508.61 | 06-MAY-15:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 32.93 | 0.00 | 01-JAN-00:10 | 2305.29 | 02-JAN-15:20 |
Ventilation (simple):Fans:Electricity | 32.93 | 0.00 | 01-JAN-00:10 | 2305.29 | 02-JAN-15:20 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 32.93 | 0.00 | 01-JAN-00:10 | 2305.29 | 02-JAN-15:20 |
ElectricityPurchased:Facility | 640.27 | 1984.66 | 20-AUG-11:20 | 47940.55 | 06-MAY-15:10 |
ElectricityPurchased:Plant | 640.27 | 1984.66 | 20-AUG-11:20 | 47940.55 | 06-MAY-15:10 |
Cogeneration:ElectricityPurchased | 640.27 | 1984.66 | 20-AUG-11:20 | 47940.55 | 06-MAY-15:10 |
General:Cogeneration:ElectricityPurchased | 640.27 | 1984.66 | 20-AUG-11:20 | 47940.55 | 06-MAY-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 640.27 | 1984.66 | 20-AUG-11:20 | 47940.55 | 06-MAY-15:10 |
ElectricityNet:Plant | 640.27 | 1984.66 | 20-AUG-11:20 | 47940.55 | 06-MAY-15:10 |
Cogeneration:ElectricityNet | 640.27 | 1984.66 | 20-AUG-11:20 | 47940.55 | 06-MAY-15:10 |
General:Cogeneration:ElectricityNet | 640.27 | 1984.66 | 20-AUG-11:20 | 47940.55 | 06-MAY-15:10 |
Electricity:HVAC | 221.41 | 0.00 | 01-JAN-00:10 | 26015.87 | 06-MAY-15:10 |
General:Fans:Electricity | 30.04 | 0.00 | 01-JAN-00:10 | 3203.31 | 06-MAY-15:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 191.37 | 0.00 | 01-JAN-00:10 | 22812.56 | 06-MAY-15:10 |
General:Cooling:Electricity | 191.37 | 0.00 | 01-JAN-00:10 | 22812.56 | 06-MAY-15:10 |
ExteriorLights:Electricity | 92.76 | 0.00 | 01-JAN-06:20 | 6986.42 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 92.76 | 0.00 | 01-JAN-06:20 | 6986.42 | 01-JAN-06:10 |
Electricity:Plant | 22.05 | 481.00 | 02-JAN-06:10 | 1702.68 | 17-JAN-12:20 |
WaterSystems:Electricity | 22.05 | 481.00 | 02-JAN-06:10 | 1702.68 | 17-JAN-12:20 |
Water Heater:WaterSystems:Electricity | 22.05 | 481.00 | 02-JAN-06:10 | 1702.68 | 17-JAN-12:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1132.28 | 0.00 | 01-JAN-00:10 | 124696.80 | 06-MAY-15:10 |
EnergyTransfer:Building | 395.94 | 0.00 | 01-JAN-00:10 | 46024.03 | 06-MAY-15:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 106.74 | 0.00 | 01-JAN-00:10 | 13771.01 | 05-SEP-05:10 |
Heating:EnergyTransfer | 0.01 | 0.00 | 01-JAN-00:10 | 681.03 | 08-APR-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 0.01 | 0.00 | 01-JAN-00:10 | 681.03 | 08-APR-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 395.93 | 0.00 | 01-JAN-00:10 | 46024.03 | 06-MAY-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 106.74 | 0.00 | 01-JAN-00:10 | 13771.01 | 05-SEP-05:10 |
General:Cooling:EnergyTransfer | 395.93 | 0.00 | 01-JAN-00:10 | 46024.03 | 06-MAY-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 106.74 | 0.00 | 01-JAN-00:10 | 13771.01 | 05-SEP-05:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 289.20 | 0.00 | 01-JAN-00:10 | 34836.90 | 06-MAY-15:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.01 | 0.00 | 01-JAN-00:10 | 681.03 | 08-APR-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.01 | 0.00 | 01-JAN-00:10 | 681.03 | 08-APR-06:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 289.19 | 0.00 | 01-JAN-00:10 | 34836.90 | 06-MAY-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 289.19 | 0.00 | 01-JAN-00:10 | 34836.90 | 06-MAY-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 736.34 | 0.00 | 01-JAN-00:10 | 79817.00 | 13-JUN-15:40 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 736.34 | 0.00 | 01-JAN-00:10 | 79817.00 | 13-JUN-15:40 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 0.000 | -106.739 | 0.000 | 0.000 | 9.114 | 20.545 | 29.165 | 14.362 | 0.000 | 8.787 | 28.026 | 0.000 | -2.282 | 0.000 | -0.977 | -0.002 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 0.009 | -289.180 | 0.000 | 0.000 | 17.086 | 50.967 | 0.000 | 46.690 | 0.000 | 9.469 | 174.416 | 0.000 | -6.087 | 0.000 | -3.370 | -0.000 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20.998 | 63.105 | 107.344 | 857.444 | 0.000 | 3.429 | 0.008 | 0.000 | -157.550 | 0.000 | -695.201 | -199.568 |
Total Facility | 0.000 | 0.000 | 0.009 | -395.919 | 0.000 | 0.000 | 47.198 | 134.617 | 136.508 | 918.497 | 0.000 | 21.685 | 202.450 | 0.000 | -165.919 | 0.000 | -699.549 | -199.570 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 23-FEB-06:01 | 0.00 | 0.00 | 0.00 | -22407.95 | 0.00 | 0.00 | 69.21 | 469.96 | 550.52 | 0.00 | 0.00 | 0.00 | 21900.84 | 0.00 | -288.61 | 0.00 | -293.98 | 0.00 |
ZONE2 FINE STORAGE | 16-JAN-12:32 | 0.00 | 0.00 | 0.00 | -63604.15 | 0.00 | 0.00 | 0.00 | 311.69 | 0.00 | 5817.54 | 0.00 | 363.63 | 57111.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 25-FEB-06:01 | 0.00 | 0.00 | 0.00 | -80167.05 | 0.00 | 0.00 | 561.32 | 1968.69 | 2600.55 | 0.00 | 0.00 | 0.00 | 94792.38 | 0.00 | -17219.29 | 0.00 | -2536.60 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 08-APR-06:10 | 0.00 | 0.00 | 1362.51 | 0.00 | 0.00 | 0.00 | 340.14 | 3740.25 | 0.00 | 3.98 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -31.52 | -5415.36 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 08-APR-06:10 | -5693.19 | 5693.19 | 1362.51 | -5693.19 | 0.00 | 0.00 | 1126.41 | 9850.56 | 2967.56 | 62.91 | 0.00 | 75.93 | 0.00 | 0.00 | -4543.74 | 0.00 | -2370.88 | -2838.05 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2352 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.2352 | 0.0828 | 1.0000 | Not calculated | 0.1023 | 0.0828 | ||
PSZ-FINE STORAGE | 3.1739 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.1739 | 0.1338 | 1.0000 | Not calculated | 0.4247 | 0.1338 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2352 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.2352 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0828 | ||
PSZ-FINE STORAGE | 3.1739 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.1739 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1338 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2352 | 1.2352 | 1.2352 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.1739 | 3.1739 | 3.1739 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2352 | 1.2352 | 1.2352 | 1.2352 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.1739 | 3.1739 | 3.1739 | 3.1739 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2352 | 1.2352 | 1.2352 | No | 0.1023 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.1739 | 3.1739 | 3.1739 | No | 0.4247 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2352 | 1.2352 | 1.2352 | 1.2352 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.1739 | 3.1739 | 3.1739 | 3.1739 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Total gross floor area [m2] | 4835.13 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 102.83 |
Number of hours not met | 102.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 191.37 | 22812.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 134.62 | 13072.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 92.76 | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 32.93 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 30.04 | 3203.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 22.05 | 1702.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 640.27 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 640.27 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 27.84 |
Space Heating | 0.00 |
Space Cooling | 39.58 |
Fans (All) | 13.02 |
Service Water Heating | 4.56 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 132.42 |
Subtotal | 132.42 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 21.02 |
Space Heating | 0.00 |
Space Cooling | 29.89 |
Fans (All) | 9.83 |
Service Water Heating | 3.44 |
Receptacle Equipment | 21.32 |
Miscellaneous | 14.49 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2729. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 3781.17 | 4432.83 | 546.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 189.50 | 8570.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 1382.83 | 6515.17 | 862.00 | 0.00 |
Min | 0.00 | 1382.83 | 0.00 | 0.00 | 0.00 |
Max | 3781.17 | 8570.50 | 6515.17 | 862.00 | 0.00 |
Average | 1323.56 | 4795.39 | 2353.72 | 287.33 | 0.00 |
Sum | 3970.67 | 14386.17 | 7061.17 | 862.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33022.50 | 4.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 205.50 | 82513.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 14090.00 | 136338.00 | 40765.00 | 0.00 |
Min | 0.00 | 4.50 | 0.00 | 0.00 | 0.00 |
Max | 33022.50 | 82513.50 | 136338.00 | 40765.00 | 0.00 |
Average | 11076.00 | 32202.67 | 45446.00 | 13588.33 | 0.00 |
Sum | 33228.00 | 96608.00 | 136338.00 | 40765.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 2659.67 | 5961.17 | 139.17 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7.83 | 8752.17 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 2893.67 | 5134.67 | 730.67 | 1.00 |
Min | 0.00 | 2893.67 | 0.00 | 0.00 | 0.00 |
Max | 2659.67 | 8752.17 | 5134.67 | 730.67 | 1.00 |
Average | 889.17 | 5869.00 | 1757.94 | 243.56 | 0.33 |
Sum | 2667.50 | 17607.00 | 5273.83 | 730.67 | 1.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 28396.50 | 4630.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 82719.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 42290.83 | 114126.67 | 34717.50 | 58.00 |
Min | 0.00 | 4630.50 | 0.00 | 0.00 | 0.00 |
Max | 28396.50 | 82719.00 | 114126.67 | 34717.50 | 58.00 |
Average | 9465.50 | 43213.44 | 38042.22 | 11572.50 | 19.33 |
Sum | 28396.50 | 129640.33 | 114126.67 | 34717.50 | 58.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:47
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.838101E+10 | 20397.28 | 24-JAN-06:01 | 19.57 | 17.63 | 0.635229E+09 | 769.08 | 05-JAN-14:20 | 19.57 | 17.63 |
February | 0.810347E+10 | 22409.68 | 23-FEB-06:01 | 22.85 | 19.63 | 0.584449E+09 | 769.08 | 03-FEB-15:50 | 22.85 | 19.63 |
March | 0.989487E+10 | 19188.30 | 04-MAR-06:01 | 24.10 | 20.01 | 0.686118E+09 | 769.07 | 25-MAR-13:00 | 33.00 | 25.07 |
April | 0.940482E+10 | 17050.28 | 27-APR-05:01 | 26.00 | 23.88 | 0.635347E+09 | 769.07 | 28-APR-10:39 | 32.53 | 25.19 |
May | 0.980338E+10 | 17015.18 | 31-MAY-05:01 | 24.17 | 24.17 | 0.660787E+09 | 769.10 | 01-MAY-12:09 | 24.17 | 24.17 |
June | 0.996551E+10 | 16544.75 | 27-JUN-05:01 | 23.00 | 23.00 | 0.660789E+09 | 769.09 | 12-JUN-12:09 | 23.00 | 23.00 |
July | 0.875040E+10 | 18786.94 | 19-JUL-05:01 | 23.98 | 23.53 | 0.635317E+09 | 769.07 | 15-JUL-14:00 | 23.98 | 23.53 |
August | 0.939140E+10 | 16549.58 | 24-AUG-05:01 | 24.00 | 24.00 | 0.686128E+09 | 769.06 | 30-AUG-14:20 | 29.67 | 25.94 |
September | 0.870932E+10 | 17234.48 | 06-SEP-05:01 | 25.08 | 24.21 | 0.635317E+09 | 769.07 | 09-SEP-13:30 | 32.60 | 26.71 |
October | 0.823150E+10 | 16962.37 | 11-OCT-05:01 | 24.00 | 23.32 | 0.635278E+09 | 769.07 | 07-OCT-14:09 | 24.00 | 23.32 |
November | 0.804721E+10 | 19145.35 | 25-NOV-06:01 | 20.58 | 18.85 | 0.609858E+09 | 769.07 | 02-NOV-15:30 | 20.58 | 18.85 |
December | 0.805910E+10 | 19677.99 | 21-DEC-06:01 | 18.07 | 17.39 | 0.635196E+09 | 769.08 | 27-DEC-13:09 | 31.17 | 21.17 |
Annual Sum or Average | 0.106742E+12 | 0.769981E+10 | ||||||||
Minimum of Months | 0.804721E+10 | 16544.75 | 18.07 | 17.39 | 0.584449E+09 | 769.06 | 19.57 | 17.63 | ||
Maximum of Months | 0.996551E+10 | 22409.68 | 26.00 | 24.21 | 0.686128E+09 | 769.10 | 33.00 | 26.71 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.210929E+11 | 63604.01 | 16-JAN-12:32 | 30.63 | 21.94 | 0.185466E+10 | 2246.98 | 17-JAN-16:40 | 28.97 | 22.10 |
February | 0.226132E+11 | 59376.38 | 25-FEB-06:01 | 23.67 | 20.77 | 0.170649E+10 | 2246.98 | 28-FEB-14:00 | 35.00 | 24.83 |
March | 0.283909E+11 | 57889.65 | 19-MAR-10:23 | 33.10 | 23.31 | 0.200316E+10 | 2247.04 | 21-MAR-14:20 | 35.33 | 24.01 |
April | 0.289817E+11 | 58272.26 | 23-APR-16:42 | 32.20 | 24.78 | 0.185469E+10 | 2247.04 | 11-APR-14:20 | 32.20 | 24.78 |
May | 0.288019E+11 | 56328.45 | 29-MAY-17:23 | 33.50 | 26.76 | 0.192893E+10 | 2247.04 | 10-MAY-15:20 | 33.50 | 26.76 |
June | 0.301921E+11 | 55215.28 | 20-JUN-05:07 | 24.00 | 24.00 | 0.192890E+10 | 2247.03 | 17-JUN-15:09 | 24.00 | 24.00 |
July | 0.239983E+11 | 59871.47 | 16-JUL-15:13 | 25.27 | 23.80 | 0.185479E+10 | 2246.97 | 01-JUL-14:30 | 25.27 | 23.80 |
August | 0.231029E+11 | 54560.22 | 30-AUG-05:01 | 24.00 | 23.38 | 0.200315E+10 | 2247.03 | 28-AUG-13:00 | 24.00 | 23.38 |
September | 0.231640E+11 | 56316.69 | 10-SEP-11:32 | 32.33 | 25.96 | 0.185476E+10 | 2247.02 | 06-SEP-14:20 | 32.33 | 25.96 |
October | 0.198944E+11 | 56009.94 | 09-OCT-12:02 | 31.57 | 26.98 | 0.185489E+10 | 2246.98 | 03-OCT-12:50 | 31.57 | 26.98 |
November | 0.196967E+11 | 58862.91 | 19-NOV-15:23 | 30.80 | 25.37 | 0.178055E+10 | 2246.98 | 06-NOV-13:09 | 30.80 | 25.37 |
December | 0.192631E+11 | 63049.12 | 03-DEC-14:43 | 31.00 | 21.94 | 0.185440E+10 | 2246.98 | 02-DEC-15:20 | 31.00 | 21.94 |
Annual Sum or Average | 0.289192E+12 | 0.224794E+11 | ||||||||
Minimum of Months | 0.192631E+11 | 54560.22 | 23.67 | 20.77 | 0.170649E+10 | 2246.97 | 24.00 | 21.94 | ||
Maximum of Months | 0.301921E+11 | 63604.01 | 33.50 | 26.98 | 0.200316E+10 | 2247.04 | 35.33 | 26.98 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 | 23.60 | 0.562222E+10 | 8392.79 | 04-JAN-13:39 | 34.03 | 23.47 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 | 22.46 | 0.539303E+10 | 8844.97 | 28-FEB-14:39 | 35.00 | 24.83 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 | 22.97 | 0.653962E+10 | 9097.65 | 21-MAR-12:50 | 36.17 | 23.06 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 | 25.10 | 0.612617E+10 | 9060.79 | 01-APR-14:20 | 35.33 | 26.89 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 | 26.40 | 0.634966E+10 | 9097.65 | 01-MAY-12:09 | 34.40 | 26.31 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 | 23.91 | 0.640724E+10 | 9097.65 | 12-JUN-15:09 | 35.90 | 27.62 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 | 24.33 | 0.558073E+10 | 8067.93 | 15-JUL-15:00 | 33.20 | 25.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 | 24.75 | 0.610234E+10 | 8377.02 | 14-AUG-13:20 | 33.53 | 27.57 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 | 25.66 | 0.567134E+10 | 8445.18 | 06-SEP-14:20 | 33.67 | 26.68 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 | 25.35 | 0.545210E+10 | 8019.91 | 04-OCT-14:20 | 32.83 | 26.21 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 | 24.37 | 0.527028E+10 | 8313.88 | 18-NOV-13:20 | 33.20 | 25.24 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 | 23.43 | 0.548807E+10 | 8070.18 | 08-DEC-14:39 | 33.00 | 23.51 |
Annual Sum or Average | 0.00 | 0.700028E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 23.80 | 22.46 | 0.527028E+10 | 8019.91 | 32.83 | 23.06 | ||
Maximum of Months | 0.00 | 0.00 | 28.62 | 26.40 | 0.653962E+10 | 9097.65 | 36.17 | 27.62 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 25380.50 | 84.60 | 02-JAN-07:10 | 23.85 |
February | 162512.83 | 842.72 | 28-FEB-07:05 | 25.17 |
March | 835952.17 | 1196.04 | 27-MAR-06:10 | 26.20 |
April | 1416274.06 | 1362.07 | 08-APR-06:10 | 26.53 |
May | 1445676.30 | 1267.38 | 20-MAY-06:10 | 26.38 |
June | 960830.51 | 1306.60 | 24-JUN-06:10 | 26.38 |
July | 789519.63 | 827.48 | 01-JUL-06:10 | 25.30 |
August | 633511.92 | 1182.64 | 26-AUG-06:10 | 26.17 |
September | 842628.25 | 1155.12 | 26-SEP-06:10 | 26.18 |
October | 1018405.96 | 650.81 | 19-OCT-06:10 | 25.18 |
November | 484131.65 | 608.20 | 03-NOV-06:10 | 25.08 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 8614823.77 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 1445676.30 | 1362.07 | 26.53 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.175214E+10 | 1573.38 | 02-JAN-16:00 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.156296E+10 | 1421.29 | 01-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.176917E+10 | 1573.38 | 28-MAR-07:10 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.165788E+10 | 1573.38 | 21-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.173345E+10 | 1573.38 | 17-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.163474E+10 | 1573.38 | 20-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.170967E+10 | 1573.38 | 11-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.177408E+10 | 1573.38 | 02-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.171778E+10 | 1573.38 | 16-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.175514E+10 | 1573.38 | 10-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.170226E+10 | 1573.38 | 01-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.177577E+10 | 1573.38 | 04-DEC-16:49 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.205450E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.156296E+10 | 1421.29 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.177577E+10 | 1573.38 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.433001E+10 | 4857.20 | 07-JAN-15:00 | 0.00 | 0.00 |
February | 0.388788E+10 | 4675.25 | 01-FEB-16:00 | 0.00 | 0.00 |
March | 0.441202E+10 | 4675.25 | 01-MAR-16:00 | 0.00 | 0.00 |
April | 0.415792E+10 | 4415.64 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.438124E+10 | 4415.64 | 05-MAY-08:09 | 0.00 | 0.00 |
June | 0.438818E+10 | 4285.64 | 01-JUN-07:10 | 0.00 | 0.00 |
July | 0.426620E+10 | 4415.64 | 14-JUL-08:09 | 0.00 | 0.00 |
August | 0.439884E+10 | 4415.64 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.409291E+10 | 4285.64 | 01-SEP-07:10 | 0.00 | 0.00 |
October | 0.417654E+10 | 4675.25 | 23-OCT-07:10 | 0.00 | 0.00 |
November | 0.411652E+10 | 4857.20 | 07-NOV-15:00 | 0.00 | 0.00 |
December | 0.435885E+10 | 5298.77 | 18-DEC-15:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.509671E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.388788E+10 | 4285.64 | 0.00 | 0.00 | |
Maximum of Months | 0.441202E+10 | 5298.77 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.544424E+10 | 6565.03 | 02-JAN-16:00 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.488748E+10 | 6017.95 | 02-FEB-16:00 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.551502E+10 | 5470.86 | 01-MAR-16:40 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.510472E+10 | 5252.11 | 01-APR-06:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.526572E+10 | 5470.86 | 17-MAY-07:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.518193E+10 | 5470.86 | 20-JUN-07:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.515172E+10 | 5470.86 | 11-JUL-07:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.541164E+10 | 5470.86 | 08-AUG-07:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.512391E+10 | 5252.11 | 01-SEP-06:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.527346E+10 | 5470.86 | 11-OCT-15:00 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.523676E+10 | 6565.03 | 06-NOV-16:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.550819E+10 | 6565.03 | 01-DEC-16:00 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.631048E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.488748E+10 | 5252.11 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.551502E+10 | 6565.03 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.175214E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611809E+09 | 0.144674E+09 |
February | 0.127628E+10 | 0.156296E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674455E+09 | 74002305.02 |
March | 0.149825E+10 | 0.176917E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.974166E+09 | 0.102166E+09 |
April | 0.138726E+10 | 0.165788E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.907759E+09 | 41965374.06 |
May | 0.144276E+10 | 0.173345E+10 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.989676E+09 | 54327582.32 |
June | 0.144276E+10 | 0.163474E+10 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.996070E+09 | 60509821.86 |
July | 0.138726E+10 | 0.170967E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.596393E+09 | 59147868.24 |
August | 0.149825E+10 | 0.177408E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.785403E+09 | 91883021.14 |
September | 0.138726E+10 | 0.171778E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.640548E+09 | 56198305.78 |
October | 0.138726E+10 | 0.175514E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551346E+09 | 76308387.35 |
November | 0.133177E+10 | 0.170226E+10 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560489E+09 | 78823205.13 |
December | 0.138726E+10 | 0.177577E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498936E+09 | 0.137487E+09 |
Annual Sum or Average | 0.168137E+11 | 0.205450E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.878705E+10 | 0.977493E+09 |
Minimum of Months | 0.127628E+10 | 0.156296E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498936E+09 | 41965374.06 |
Maximum of Months | 0.149825E+10 | 0.177577E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.996070E+09 | 0.144674E+09 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.433001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435438E+09 | 0.531334E+09 |
February | 0.300332E+10 | 0.388788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.711023E+09 | 0.203147E+09 |
March | 0.352563E+10 | 0.441202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120904E+10 | 0.303070E+09 |
April | 0.326447E+10 | 0.415792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123040E+10 | 61700913.29 |
May | 0.339505E+10 | 0.438124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141968E+10 | 0.155902E+09 |
June | 0.339505E+10 | 0.438818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129419E+10 | 0.140610E+09 |
July | 0.326447E+10 | 0.426620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700545E+09 | 0.186245E+09 |
August | 0.352563E+10 | 0.439884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.797187E+09 | 0.340842E+09 |
September | 0.326447E+10 | 0.409291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614214E+09 | 0.198399E+09 |
October | 0.326447E+10 | 0.417654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433865E+09 | 0.306429E+09 |
November | 0.313390E+10 | 0.411652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323934E+09 | 0.340949E+09 |
December | 0.326447E+10 | 0.435885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299559E+09 | 0.601575E+09 |
Annual Sum or Average | 0.395654E+11 | 0.509671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.946908E+10 | 0.337020E+10 |
Minimum of Months | 0.300332E+10 | 0.388788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299559E+09 | 61700913.29 |
Maximum of Months | 0.352563E+10 | 0.441202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141968E+10 | 0.601575E+09 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.544424E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1001062.94 | 0.578146E+10 |
February | 0.690763E+10 | 0.488748E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2247602.39 | 0.387773E+10 |
March | 0.810895E+10 | 0.551502E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17239700.11 | 0.653195E+10 |
April | 0.750829E+10 | 0.510472E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10253926.58 | 0.360009E+10 |
May | 0.780862E+10 | 0.526572E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29261831.73 | 0.427946E+10 |
June | 0.780862E+10 | 0.518193E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5105224.97 | 0.431276E+10 |
July | 0.750829E+10 | 0.515172E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 659310.68 | 0.402379E+10 |
August | 0.810895E+10 | 0.541164E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15899096.28 | 0.620780E+10 |
September | 0.750829E+10 | 0.512391E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1673055.61 | 0.396217E+10 |
October | 0.750829E+10 | 0.527346E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 715227.17 | 0.470197E+10 |
November | 0.720796E+10 | 0.523676E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1387024.27 | 0.451665E+10 |
December | 0.750829E+10 | 0.550819E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 807629.44 | 0.577260E+10 |
Annual Sum or Average | 0.910005E+11 | 0.631048E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 86250692.15 | 0.575684E+11 |
Minimum of Months | 0.690763E+10 | 0.488748E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 659310.68 | 0.360009E+10 |
Maximum of Months | 0.810895E+10 | 0.551502E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29261831.73 | 0.653195E+10 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1573.38 | 02-JAN-16:00 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3687.33 | 04-JAN-13:00 | 1622.04 | 24-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 1421.29 | 01-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3752.94 | 28-FEB-13:00 | 976.86 | 01-FEB-07:05 |
March | 1680.92 | 01-MAR-08:09 | 1573.38 | 28-MAR-07:10 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4050.73 | 20-MAR-16:10 | 399.95 | 03-MAR-06:01 |
April | 1680.92 | 01-APR-07:10 | 1573.38 | 21-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4167.80 | 11-APR-16:10 | 251.92 | 13-APR-05:01 |
May | 1680.92 | 01-MAY-07:10 | 1573.38 | 17-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4692.74 | 05-MAY-16:10 | 470.88 | 08-MAY-22:00 |
June | 1680.92 | 01-JUN-07:10 | 1573.38 | 20-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4359.97 | 13-JUN-16:10 | 497.81 | 20-JUN-23:00 |
July | 1680.92 | 01-JUL-07:10 | 1573.38 | 11-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3560.50 | 26-JUL-17:00 | 303.10 | 19-JUL-18:55 |
August | 1680.92 | 01-AUG-07:10 | 1573.38 | 02-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3595.15 | 09-AUG-16:10 | 417.88 | 23-AUG-20:00 |
September | 1680.92 | 01-SEP-07:10 | 1573.38 | 16-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3202.13 | 12-SEP-12:00 | 430.49 | 15-SEP-17:00 |
October | 1680.92 | 02-OCT-07:10 | 1573.38 | 10-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3080.66 | 04-OCT-12:00 | 397.91 | 23-OCT-05:01 |
November | 1680.92 | 01-NOV-07:10 | 1573.38 | 01-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2899.83 | 10-NOV-12:10 | 666.29 | 27-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1573.38 | 04-DEC-16:49 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2878.14 | 26-DEC-13:00 | 2012.50 | 21-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1421.29 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 2878.14 | 251.92 | |||||
Maximum of Months | 1680.92 | 1573.38 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 4692.74 | 2012.50 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 4857.20 | 07-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2057.19 | 31-JAN-16:10 | 5127.33 | 07-JAN-05:00 |
February | 3955.50 | 01-FEB-08:09 | 4675.25 | 01-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3182.22 | 28-FEB-16:05 | 1418.11 | 01-FEB-07:05 |
March | 3955.50 | 01-MAR-08:09 | 4675.25 | 01-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4818.09 | 19-MAR-16:00 | 1208.60 | 14-MAR-21:50 |
April | 3955.50 | 01-APR-07:10 | 4415.64 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3303.95 | 11-APR-16:00 | 1001.52 | 14-APR-16:00 |
May | 3955.50 | 01-MAY-07:10 | 4415.64 | 05-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5657.62 | 06-MAY-15:10 | 1855.67 | 08-MAY-22:00 |
June | 3955.50 | 01-JUN-07:10 | 4285.64 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4531.02 | 16-JUN-15:30 | 2086.44 | 20-JUN-23:00 |
July | 3955.50 | 01-JUL-07:10 | 4415.64 | 14-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2779.55 | 13-JUL-16:00 | 1479.33 | 19-JUL-19:00 |
August | 3955.50 | 01-AUG-07:10 | 4415.64 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3174.55 | 09-AUG-16:00 | 1822.94 | 23-AUG-20:00 |
September | 3955.50 | 01-SEP-07:10 | 4285.64 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3225.97 | 10-SEP-14:58 | 2921.37 | 15-SEP-17:00 |
October | 3955.50 | 02-OCT-07:10 | 4675.25 | 23-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2807.88 | 29-OCT-12:58 | 1322.12 | 30-OCT-16:20 |
November | 3955.50 | 01-NOV-07:10 | 4857.20 | 07-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1462.32 | 04-NOV-15:10 | 1242.39 | 25-NOV-08:00 |
December | 3955.50 | 01-DEC-08:09 | 5298.77 | 18-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1321.90 | 13-DEC-16:10 | 1922.98 | 21-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 4285.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1321.90 | 1001.52 | ||||
Maximum of Months | 3955.50 | 5298.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5657.62 | 5127.33 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 6565.03 | 02-JAN-16:00 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1520.14 | 11-JAN-10:53 | 32735.18 | 07-JAN-05:00 |
February | 9097.65 | 01-FEB-08:09 | 6017.95 | 02-FEB-16:00 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 447.41 | 12-FEB-12:45 | 8119.73 | 21-FEB-09:55 |
March | 9097.65 | 01-MAR-08:09 | 5470.86 | 01-MAR-16:40 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1634.98 | 19-MAR-11:55 | 9410.22 | 14-MAR-22:00 |
April | 9097.65 | 01-APR-07:10 | 5252.11 | 01-APR-06:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1232.72 | 17-APR-09:43 | 7769.56 | 14-APR-16:00 |
May | 9097.65 | 01-MAY-07:10 | 5470.86 | 17-MAY-07:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3911.18 | 01-MAY-13:53 | 14428.56 | 08-MAY-22:00 |
June | 9097.65 | 01-JUN-07:10 | 5470.86 | 20-JUN-07:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 828.66 | 18-JUN-13:55 | 16326.27 | 20-JUN-23:00 |
July | 9097.65 | 01-JUL-07:10 | 5470.86 | 11-JUL-07:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 650.90 | 27-JUL-16:55 | 19375.25 | 03-JUL-13:00 |
August | 9097.65 | 01-AUG-07:10 | 5470.86 | 08-AUG-07:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1663.36 | 06-AUG-11:55 | 20184.36 | 25-AUG-11:00 |
September | 9097.65 | 01-SEP-07:10 | 5252.11 | 01-SEP-06:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1381.01 | 22-SEP-15:55 | 17665.98 | 15-SEP-17:00 |
October | 9097.65 | 02-OCT-07:10 | 5470.86 | 11-OCT-15:00 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 439.41 | 06-OCT-10:55 | 12826.34 | 11-OCT-13:10 |
November | 9097.65 | 01-NOV-07:10 | 6565.03 | 06-NOV-16:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 498.14 | 18-NOV-12:55 | 8929.04 | 25-NOV-08:70 |
December | 9097.65 | 01-DEC-08:09 | 6565.03 | 01-DEC-16:00 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 605.65 | 29-DEC-18:55 | 14202.73 | 20-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 5252.11 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 439.41 | 7769.56 | |||||
Maximum of Months | 9097.65 | 6565.03 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 3911.18 | 32735.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20397.28 | 24-JAN-06:01 | 1664.11 | 4229.68 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 480.16 |
February | 22409.68 | 23-FEB-06:01 | 1849.01 | 4699.65 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.98 |
March | 19188.30 | 04-MAR-06:01 | 1664.11 | 4229.68 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.00 |
April | 17050.28 | 27-APR-05:01 | 1849.01 | 4699.65 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.32 |
May | 17015.18 | 31-MAY-05:01 | 1849.01 | 4699.65 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.31 |
June | 16544.75 | 27-JUN-05:01 | 1849.01 | 4699.65 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.87 |
July | 18786.94 | 19-JUL-05:01 | 1849.01 | 4699.65 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.10 |
August | 16549.58 | 24-AUG-05:01 | 1849.01 | 4699.65 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.86 |
September | 17234.48 | 06-SEP-05:01 | 1849.01 | 4699.65 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.63 |
October | 16962.37 | 11-OCT-05:01 | 1849.01 | 4699.65 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.14 |
November | 19145.35 | 25-NOV-06:01 | 1849.01 | 4699.65 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.37 |
December | 19677.99 | 21-DEC-06:01 | 1479.21 | 3759.72 | 4404.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 599.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16544.75 | 1479.21 | 3759.72 | 4404.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.00 | |
Maximum of Months | 22409.68 | 1849.01 | 4699.65 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 599.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 63604.01 | 16-JAN-12:32 | 0.00 | 1246.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.63 | 0.00 |
February | 59376.38 | 25-FEB-06:01 | 4351.05 | 6233.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.96 |
March | 57889.65 | 19-MAR-10:23 | 0.00 | 1246.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1970.52 | 0.00 |
April | 58272.26 | 23-APR-16:42 | 0.00 | 2285.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 963.23 | 0.00 |
May | 56328.45 | 29-MAY-17:23 | 0.00 | 2493.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1163.84 | 0.00 |
June | 55215.28 | 20-JUN-05:07 | 4351.05 | 6233.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.16 |
July | 59871.47 | 16-JUL-15:13 | 0.00 | 1246.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.16 |
August | 54560.22 | 30-AUG-05:01 | 4351.05 | 6233.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.77 |
September | 56316.69 | 10-SEP-11:32 | 0.00 | 1246.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 823.90 | 0.00 |
October | 56009.94 | 09-OCT-12:02 | 0.00 | 1246.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 682.93 | 0.00 |
November | 58862.91 | 19-NOV-15:23 | 0.00 | 2077.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 683.55 | 0.00 |
December | 63049.12 | 03-DEC-14:43 | 0.00 | 1870.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 648.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 54560.22 | 0.00 | 1246.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 63604.01 | 4351.05 | 6233.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1970.52 | 417.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 875.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1395.73 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 2626.05 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2229.26 |
March | 0.00 | 01-MAR-00:05 | 0.00 | 1750.70 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3341.66 |
April | 0.00 | 01-APR-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2630.54 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1392.27 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3088.21 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2628.40 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3621.15 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2317.00 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 875.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1015.02 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1311.30 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1930.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 875.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1015.02 | |
Maximum of Months | 0.00 | 0.00 | 2626.05 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3621.15 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.503313E+11 | 40842.19 | 31-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.478747E+11 | 41795.10 | 28-FEB-15:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.569331E+11 | 42780.26 | 20-MAR-15:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.565774E+11 | 43641.77 | 11-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.594031E+11 | 47940.55 | 06-MAY-15:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.593952E+11 | 47259.19 | 13-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.519852E+11 | 40892.21 | 19-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.554481E+11 | 42727.19 | 01-AUG-15:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.526127E+11 | 42082.13 | 13-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.510252E+11 | 41763.45 | 04-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.490782E+11 | 40747.54 | 20-NOV-15:39 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.496077E+11 | 40576.13 | 13-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.640272E+12 | 0.00 | ||||
Minimum of Months | 0.478747E+11 | 40576.13 | 0.00 | 0.00 | ||
Maximum of Months | 0.594031E+11 | 47940.55 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.115264E+11 | 0.832971E+10 | 0.112984E+11 | 0.00 | 0.444814E+10 | 0.00 | 0.00 | 0.128476E+11 | 0.00 | 0.00 | 0.00 | 0.188105E+10 | 0.00 |
February | 0.103383E+11 | 0.738555E+10 | 0.103734E+11 | 0.00 | 0.464476E+10 | 0.00 | 0.00 | 0.134287E+11 | 0.00 | 0.00 | 0.00 | 0.170398E+10 | 0.00 |
March | 0.116962E+11 | 0.788118E+10 | 0.121089E+11 | 0.00 | 0.580036E+10 | 0.00 | 0.00 | 0.175390E+11 | 0.00 | 0.00 | 0.00 | 0.190737E+10 | 0.00 |
April | 0.109205E+11 | 0.741276E+10 | 0.112578E+11 | 0.00 | 0.644885E+10 | 0.00 | 0.00 | 0.187246E+11 | 0.00 | 0.00 | 0.00 | 0.181291E+10 | 0.00 |
May | 0.113804E+11 | 0.750392E+10 | 0.117000E+11 | 0.00 | 0.669645E+10 | 0.00 | 0.00 | 0.202569E+11 | 0.00 | 0.00 | 0.00 | 0.186547E+10 | 0.00 |
June | 0.112048E+11 | 0.716125E+10 | 0.116594E+11 | 0.00 | 0.666332E+10 | 0.00 | 0.00 | 0.208941E+11 | 0.00 | 0.00 | 0.00 | 0.181230E+10 | 0.00 |
July | 0.111276E+11 | 0.747038E+10 | 0.112984E+11 | 0.00 | 0.503592E+10 | 0.00 | 0.00 | 0.152166E+11 | 0.00 | 0.00 | 0.00 | 0.183638E+10 | 0.00 |
August | 0.115846E+11 | 0.758356E+10 | 0.121016E+11 | 0.00 | 0.517168E+10 | 0.00 | 0.00 | 0.171300E+11 | 0.00 | 0.00 | 0.00 | 0.187673E+10 | 0.00 |
September | 0.109346E+11 | 0.756367E+10 | 0.112504E+11 | 0.00 | 0.507142E+10 | 0.00 | 0.00 | 0.159885E+11 | 0.00 | 0.00 | 0.00 | 0.180415E+10 | 0.00 |
October | 0.112051E+11 | 0.805724E+10 | 0.113057E+11 | 0.00 | 0.452741E+10 | 0.00 | 0.00 | 0.140693E+11 | 0.00 | 0.00 | 0.00 | 0.186038E+10 | 0.00 |
November | 0.110556E+11 | 0.801955E+10 | 0.108562E+11 | 0.00 | 0.425963E+10 | 0.00 | 0.00 | 0.130803E+11 | 0.00 | 0.00 | 0.00 | 0.180700E+10 | 0.00 |
December | 0.116428E+11 | 0.839390E+10 | 0.112984E+11 | 0.00 | 0.420028E+10 | 0.00 | 0.00 | 0.121932E+11 | 0.00 | 0.00 | 0.00 | 0.187911E+10 | 0.00 |
Annual Sum or Average | 0.134617E+12 | 0.927627E+11 | 0.136508E+12 | 0.00 | 0.629682E+11 | 0.00 | 0.00 | 0.191369E+12 | 0.00 | 0.00 | 0.00 | 0.220468E+11 | 0.00 |
Minimum of Months | 0.103383E+11 | 0.716125E+10 | 0.103734E+11 | 0.00 | 0.420028E+10 | 0.00 | 0.00 | 0.121932E+11 | 0.00 | 0.00 | 0.00 | 0.170398E+10 | 0.00 |
Maximum of Months | 0.116962E+11 | 0.839390E+10 | 0.121089E+11 | 0.00 | 0.669645E+10 | 0.00 | 0.00 | 0.208941E+11 | 0.00 | 0.00 | 0.00 | 0.190737E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 12813.66 | 02-JAN-16:00 | 6986.42 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 4549.79 | 04-JAN-12:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 11652.96 | 02-FEB-16:00 | 6986.42 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 4649.06 | 15-FEB-12:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 11567.40 | 17-MAR-07:10 | 6986.42 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 4888.16 | 20-MAR-15:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 10782.80 | 21-APR-07:10 | 6986.42 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 4941.61 | 18-APR-15:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 11329.89 | 17-MAY-07:10 | 6986.42 | 01-MAY-05:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 5508.61 | 06-MAY-15:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 11329.89 | 20-JUN-07:10 | 6986.42 | 01-JUN-05:10 | 10035.17 | 01-JUN-07:10 | 0.00 | 5444.17 | 13-JUN-15:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 11329.89 | 11-JUL-07:10 | 6986.42 | 01-JUL-05:10 | 10035.17 | 01-JUL-07:10 | 0.00 | 4590.33 | 26-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 11329.89 | 08-AUG-07:10 | 6986.42 | 01-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 4890.99 | 15-AUG-11:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 10782.80 | 16-SEP-07:10 | 6986.42 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 4760.31 | 05-SEP-11:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 11719.49 | 23-OCT-07:10 | 6986.42 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 4661.34 | 04-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 12813.66 | 07-NOV-16:49 | 6986.42 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 4609.58 | 13-NOV-12:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 13072.63 | 18-DEC-15:00 | 6986.42 | 01-DEC-17:30 | 10035.17 | 01-DEC-08:09 | 0.00 | 4589.61 | 11-DEC-12:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 10782.80 | 6986.42 | 10035.17 | 0.00 | 4549.79 | 0.00 | 0.00 | |||||
Maximum of Months | 13072.63 | 6986.42 | 10035.17 | 0.00 | 5508.61 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 15775.33 | 04-JAN-12:00 | 0.00 | 0.00 | 0.00 | 1702.68 | 17-JAN-12:20 | 0.00 |
February | 17084.96 | 28-FEB-14:00 | 0.00 | 0.00 | 0.00 | 1702.11 | 01-FEB-12:39 | 0.00 |
March | 18468.27 | 20-MAR-15:09 | 0.00 | 0.00 | 0.00 | 1699.76 | 02-MAR-12:20 | 0.00 |
April | 18969.11 | 11-APR-15:00 | 0.00 | 0.00 | 0.00 | 1695.75 | 01-APR-11:00 | 0.00 |
May | 22812.56 | 06-MAY-15:09 | 0.00 | 0.00 | 0.00 | 1691.25 | 01-MAY-11:20 | 0.00 |
June | 22349.86 | 13-JUN-15:30 | 0.00 | 0.00 | 0.00 | 1687.45 | 01-JUN-11:09 | 0.00 |
July | 15734.31 | 26-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1685.54 | 28-JUL-11:09 | 0.00 |
August | 18500.75 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 1688.09 | 31-AUG-11:50 | 0.00 |
September | 17624.24 | 06-SEP-11:00 | 0.00 | 0.00 | 0.00 | 1691.88 | 30-SEP-11:09 | 0.00 |
October | 16759.39 | 04-OCT-11:00 | 0.00 | 0.00 | 0.00 | 1696.43 | 31-OCT-11:30 | 0.00 |
November | 15237.27 | 15-NOV-12:00 | 0.00 | 0.00 | 0.00 | 1700.36 | 30-NOV-12:20 | 0.00 |
December | 14748.86 | 12-DEC-12:00 | 0.00 | 0.00 | 0.00 | 1702.35 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 14748.86 | 0.00 | 0.00 | 0.00 | 1685.54 | 0.00 | ||
Maximum of Months | 22812.56 | 0.00 | 0.00 | 0.00 | 1702.68 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 40842.19 | 31-JAN-15:00 | 10955.84 | 10035.17 | 0.00 | 0.00 | 4302.73 | 0.00 | 0.00 | 13869.82 | 0.00 |
February | 41795.10 | 28-FEB-15:30 | 9274.18 | 10035.17 | 0.00 | 0.00 | 4500.30 | 0.00 | 0.00 | 16308.66 | 0.00 |
March | 42780.26 | 20-MAR-15:30 | 7906.20 | 10035.17 | 0.00 | 0.00 | 4869.02 | 0.00 | 0.00 | 18393.68 | 0.00 |
April | 43641.77 | 11-APR-15:00 | 9232.49 | 10035.17 | 0.00 | 0.00 | 4923.99 | 0.00 | 0.00 | 18969.11 | 0.00 |
May | 47940.55 | 06-MAY-15:09 | 8295.80 | 10035.17 | 0.00 | 0.00 | 5508.61 | 0.00 | 0.00 | 22812.56 | 0.00 |
June | 47259.19 | 13-JUN-15:00 | 8295.80 | 10035.17 | 0.00 | 0.00 | 5377.26 | 0.00 | 0.00 | 21977.80 | 0.00 |
July | 40892.21 | 19-JUL-14:00 | 9326.62 | 10035.17 | 0.00 | 0.00 | 4380.25 | 0.00 | 0.00 | 15485.61 | 0.00 |
August | 42727.19 | 01-AUG-15:20 | 7906.20 | 10035.17 | 0.00 | 0.00 | 4837.45 | 0.00 | 0.00 | 18375.45 | 0.00 |
September | 42082.13 | 13-SEP-15:00 | 9779.58 | 10035.17 | 0.00 | 0.00 | 4482.87 | 0.00 | 0.00 | 16210.41 | 0.00 |
October | 41763.45 | 04-OCT-15:00 | 9779.58 | 10035.17 | 0.00 | 0.00 | 4443.99 | 0.00 | 0.00 | 15929.78 | 0.00 |
November | 40747.54 | 20-NOV-15:39 | 11008.28 | 10035.17 | 0.00 | 0.00 | 4342.26 | 0.00 | 0.00 | 13820.66 | 0.00 |
December | 40576.13 | 13-DEC-15:00 | 11449.85 | 10035.17 | 0.00 | 0.00 | 4266.33 | 0.00 | 0.00 | 13146.73 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 40576.13 | 7906.20 | 10035.17 | 0.00 | 0.00 | 4266.33 | 0.00 | 0.00 | 13146.73 | 0.00 | |
Maximum of Months | 47940.55 | 11449.85 | 10035.17 | 0.00 | 0.00 | 5508.61 | 0.00 | 0.00 | 22812.56 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 25.02 | 8.00 | 24.92 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 25.30 | 7.67 | 25.10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 25.11 | 8.83 | 25.06 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 25.29 | 8.33 | 25.25 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 25.61 | 9.83 | 25.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 25.42 | 9.17 | 25.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 25.26 | 8.33 | 25.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 25.24 | 9.17 | 25.20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 25.29 | 8.67 | 25.20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 25.30 | 8.17 | 25.16 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 25.05 | 8.00 | 25.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 24.98 | 7.83 | 24.88 |
Annual Sum or Average | 0.00 | 0.00 | 106.00 | 25.25 | 102.00 | 25.16 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 24.98 | 7.67 | 24.88 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 25.61 | 9.83 | 25.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 27.49 | 0.00 | 27.49 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 27.53 | 0.00 | 27.53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 27.59 | 0.00 | 27.59 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 33.17 | 27.56 | 0.33 | 27.55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 | 27.54 | 0.00 | 27.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 33.50 | 27.57 | 0.17 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 34.33 | 27.47 | 0.00 | 27.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 27.48 | 0.00 | 27.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 | 27.49 | 0.17 | 27.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 25.50 | 27.48 | 0.00 | 27.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 27.46 | 0.17 | 27.46 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 27.50 | 0.00 | 27.50 |
Annual Sum or Average | 0.00 | 0.00 | 334.33 | 27.52 | 0.83 | 27.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 27.46 | 0.00 | 27.46 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 | 27.59 | 0.33 | 27.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 37.17 | 24.08 | 300.00 | 23.94 | 37.17 | 23.96 |
February | 24.33 | 24.16 | 276.00 | 23.95 | 24.33 | 23.97 |
March | 56.33 | 24.10 | 324.00 | 23.96 | 56.33 | 23.98 |
April | 73.33 | 24.08 | 300.00 | 23.97 | 73.33 | 23.99 |
May | 122.50 | 24.03 | 312.00 | 23.97 | 122.50 | 23.99 |
June | 117.50 | 24.03 | 312.00 | 23.97 | 117.50 | 23.98 |
July | 65.83 | 24.06 | 300.00 | 23.96 | 65.83 | 23.98 |
August | 133.50 | 24.00 | 324.00 | 23.96 | 133.50 | 23.97 |
September | 102.17 | 24.02 | 300.00 | 23.96 | 102.17 | 23.97 |
October | 107.33 | 24.00 | 300.00 | 23.95 | 107.33 | 23.96 |
November | 76.17 | 24.02 | 288.00 | 23.95 | 76.17 | 23.96 |
December | 44.00 | 24.06 | 300.00 | 23.94 | 44.00 | 23.96 |
Annual Sum or Average | 960.17 | 24.04 | 3636.00 | 23.96 | 960.17 | 23.97 |
Minimum of Months | 24.33 | 24.00 | 276.00 | 23.94 | 24.33 | 23.96 |
Maximum of Months | 133.50 | 24.16 | 324.00 | 23.97 | 133.50 | 23.99 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 295.00 | 26.72 | 300.00 | 26.72 | 295.00 | 26.72 |
February | 271.50 | 26.72 | 276.00 | 26.72 | 271.50 | 26.72 |
March | 324.00 | 26.72 | 324.00 | 26.72 | 324.00 | 26.72 |
April | 300.00 | 26.71 | 300.00 | 26.71 | 300.00 | 26.71 |
May | 312.00 | 26.71 | 312.00 | 26.71 | 312.00 | 26.71 |
June | 312.00 | 26.71 | 312.00 | 26.71 | 312.00 | 26.71 |
July | 297.50 | 26.72 | 300.00 | 26.72 | 297.50 | 26.72 |
August | 324.00 | 26.72 | 324.00 | 26.72 | 324.00 | 26.72 |
September | 300.00 | 26.72 | 300.00 | 26.72 | 300.00 | 26.72 |
October | 300.00 | 26.72 | 300.00 | 26.72 | 300.00 | 26.72 |
November | 288.00 | 26.72 | 288.00 | 26.72 | 288.00 | 26.72 |
December | 299.00 | 26.71 | 300.00 | 26.71 | 299.00 | 26.71 |
Annual Sum or Average | 3623.00 | 26.72 | 3636.00 | 26.72 | 3623.00 | 26.72 |
Minimum of Months | 271.50 | 26.71 | 276.00 | 26.71 | 271.50 | 26.71 |
Maximum of Months | 324.00 | 26.72 | 324.00 | 26.72 | 324.00 | 26.72 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 30.42 | 300.00 | 30.42 | 300.00 | 30.42 |
February | 276.00 | 31.08 | 276.00 | 31.08 | 276.00 | 31.08 |
March | 324.00 | 31.54 | 324.00 | 31.54 | 324.00 | 31.54 |
April | 300.00 | 31.75 | 300.00 | 31.75 | 300.00 | 31.75 |
May | 312.00 | 31.72 | 312.00 | 31.72 | 312.00 | 31.72 |
June | 312.00 | 31.85 | 312.00 | 31.85 | 312.00 | 31.85 |
July | 300.00 | 30.45 | 300.00 | 30.45 | 300.00 | 30.45 |
August | 324.00 | 30.58 | 324.00 | 30.58 | 324.00 | 30.58 |
September | 300.00 | 30.64 | 300.00 | 30.64 | 300.00 | 30.64 |
October | 300.00 | 30.07 | 300.00 | 30.07 | 300.00 | 30.07 |
November | 288.00 | 30.16 | 288.00 | 30.16 | 288.00 | 30.16 |
December | 300.00 | 30.06 | 300.00 | 30.06 | 300.00 | 30.06 |
Annual Sum or Average | 3636.00 | 30.87 | 3636.00 | 30.87 | 3636.00 | 30.87 |
Minimum of Months | 276.00 | 30.06 | 276.00 | 30.06 | 276.00 | 30.06 |
Maximum of Months | 324.00 | 31.85 | 324.00 | 31.85 | 324.00 | 31.85 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.136796E+11 | 0.324649E+10 | 301.72 | 0.961227E+10 | 0.406730E+10 | 0.00 | 1.00 | 02-JAN-06:01 | 0.00 | 01-JAN-00:10 | 33703.58 | 02-JAN-06:01 | 21661.65 | 24-JAN-06:01 | 17423.69 | 02-JAN-06:03 | 6823.70 | 02-JAN-06:01 | 0.00 | 01-JAN-00:10 |
February | 0.131977E+11 | 0.317246E+10 | 280.52 | 0.936359E+10 | 0.383414E+10 | 0.00 | 1.00 | 01-FEB-06:01 | 0.00 | 01-FEB-00:03 | 33194.89 | 15-FEB-06:01 | 23980.87 | 23-FEB-06:01 | 15783.05 | 15-FEB-06:04 | 6797.64 | 16-FEB-06:01 | 0.00 | 01-FEB-00:03 |
March | 0.167698E+11 | 0.405655E+10 | 330.79 | 0.115556E+11 | 0.521419E+10 | 0.00 | 1.00 | 01-MAR-06:01 | 0.00 | 01-MAR-00:05 | 33384.82 | 25-MAR-05:01 | 20907.62 | 04-MAR-06:01 | 16897.72 | 25-MAR-05:04 | 6907.05 | 28-MAR-05:01 | 0.00 | 01-MAR-00:05 |
April | 0.171325E+11 | 0.412351E+10 | 308.95 | 0.110608E+11 | 0.607167E+10 | 0.00 | 1.00 | 01-APR-05:01 | 0.00 | 01-APR-00:10 | 33394.38 | 24-APR-05:01 | 18700.56 | 27-APR-05:01 | 17773.92 | 11-APR-05:05 | 6907.05 | 03-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.192887E+11 | 0.460558E+10 | 325.34 | 0.115790E+11 | 0.770970E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 33671.69 | 17-MAY-05:01 | 18401.27 | 31-MAY-05:01 | 21116.33 | 22-MAY-05:07 | 6946.25 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 |
June | 0.195465E+11 | 0.467775E+10 | 322.55 | 0.117726E+11 | 0.777394E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 33703.58 | 21-JUN-05:01 | 18007.04 | 03-JUN-05:01 | 20162.08 | 10-JUN-05:09 | 6907.05 | 10-JUN-05:11 | 0.00 | 01-JUN-00:10 |
July | 0.154826E+11 | 0.361031E+10 | 304.30 | 0.100275E+11 | 0.545514E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 33408.72 | 24-JUL-05:01 | 20332.11 | 19-JUL-05:01 | 16319.09 | 24-JUL-05:05 | 6864.12 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 |
August | 0.186874E+11 | 0.433910E+10 | 327.03 | 0.109198E+11 | 0.776762E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 33671.69 | 21-AUG-05:01 | 17957.75 | 24-AUG-05:01 | 19590.90 | 07-AUG-05:06 | 6907.05 | 12-AUG-05:11 | 0.00 | 01-AUG-00:10 |
September | 0.166366E+11 | 0.387732E+10 | 306.08 | 0.100948E+11 | 0.654174E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 33458.56 | 22-SEP-05:01 | 18746.07 | 06-SEP-05:01 | 18779.68 | 25-SEP-05:06 | 6907.05 | 08-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 0.156853E+11 | 0.361428E+10 | 301.85 | 0.947187E+10 | 0.621339E+10 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 33703.58 | 23-OCT-05:02 | 18387.38 | 11-OCT-05:01 | 18501.83 | 30-OCT-05:04 | 6876.29 | 05-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.144169E+11 | 0.334951E+10 | 289.12 | 0.922693E+10 | 0.518996E+10 | 0.00 | 1.00 | 01-NOV-05:01 | 0.00 | 01-NOV-00:10 | 33465.51 | 24-NOV-06:01 | 20309.65 | 25-NOV-06:01 | 18295.06 | 13-NOV-06:06 | 6871.44 | 08-NOV-06:01 | 0.00 | 01-NOV-00:10 |
December | 0.134234E+11 | 0.315790E+10 | 300.37 | 0.922676E+10 | 0.419668E+10 | 0.00 | 1.00 | 01-DEC-06:01 | 0.00 | 01-DEC-00:10 | 33703.58 | 11-DEC-06:01 | 20899.79 | 21-DEC-06:01 | 17021.46 | 11-DEC-06:04 | 6823.70 | 11-DEC-06:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.193947E+12 | 0.458308E+11 | 3698.62 | 0.123911E+12 | 0.700355E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.131977E+11 | 0.315790E+10 | 280.52 | 0.922676E+10 | 0.383414E+10 | 0.00 | 1.00 | 0.00 | 33194.89 | 17957.75 | 15783.05 | 6797.64 | 0.00 | |||||||
Maximum of Months | 0.195465E+11 | 0.467775E+10 | 330.79 | 0.117726E+11 | 0.777394E+10 | 0.00 | 1.00 | 0.00 | 33703.58 | 23980.87 | 21116.33 | 6946.25 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.352101E+11 | 0.960111E+10 | 425.81 | 0.239771E+11 | 0.112330E+11 | 0.00 | 1.00 | 01-JAN-11:55 | 0.00 | 01-JAN-00:10 | 95689.81 | 11-JAN-06:06 | 71381.30 | 16-JAN-14:32 | 41570.80 | 11-JAN-06:06 | 22770.08 | 08-JAN-13:32 | 0.00 | 01-JAN-00:10 |
February | 0.374417E+11 | 0.102563E+11 | 430.68 | 0.258238E+11 | 0.116179E+11 | 0.00 | 1.00 | 01-FEB-18:08 | 0.00 | 01-FEB-00:03 | 94239.80 | 16-FEB-06:05 | 68281.91 | 26-FEB-14:23 | 38654.13 | 16-FEB-06:05 | 23429.45 | 26-FEB-15:02 | 0.00 | 01-FEB-00:03 |
March | 0.492878E+11 | 0.134825E+11 | 518.73 | 0.328484E+11 | 0.164394E+11 | 0.00 | 1.00 | 01-MAR-06:01 | 0.00 | 01-MAR-00:05 | 96721.16 | 25-MAR-05:06 | 68024.47 | 19-MAR-13:42 | 44451.27 | 25-MAR-05:06 | 23798.29 | 26-MAR-13:53 | 0.00 | 01-MAR-00:05 |
April | 0.539241E+11 | 0.146011E+11 | 537.36 | 0.336425E+11 | 0.202816E+11 | 0.00 | 1.00 | 01-APR-05:08 | 0.00 | 01-APR-00:15 | 96813.43 | 01-APR-05:08 | 65546.77 | 23-APR-14:43 | 46058.89 | 01-APR-05:08 | 23889.62 | 02-APR-15:02 | 0.00 | 01-APR-00:10 |
May | 0.584165E+11 | 0.156513E+11 | 547.40 | 0.336719E+11 | 0.247446E+11 | 0.00 | 1.00 | 01-MAY-00:35 | 0.00 | 01-MAY-00:25 | 99158.85 | 04-MAY-05:07 | 65061.41 | 07-MAY-13:02 | 51979.44 | 04-MAY-05:07 | 24078.28 | 28-MAY-14:03 | 0.00 | 01-MAY-00:10 |
June | 0.607660E+11 | 0.162163E+11 | 547.20 | 0.351220E+11 | 0.256441E+11 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:15 | 97228.84 | 06-JUN-05:06 | 61441.13 | 18-JUN-14:23 | 46486.10 | 06-JUN-05:06 | 24464.19 | 18-JUN-13:43 | 0.00 | 01-JUN-00:10 |
July | 0.434001E+11 | 0.116063E+11 | 510.08 | 0.270990E+11 | 0.163011E+11 | 0.00 | 1.00 | 01-JUL-17:08 | 0.00 | 01-JUL-00:10 | 95012.15 | 14-JUL-05:01 | 65076.00 | 16-JUL-15:13 | 39262.76 | 14-JUL-05:01 | 23578.31 | 26-JUL-17:06 | 0.00 | 01-JUL-00:10 |
August | 0.487723E+11 | 0.127909E+11 | 492.73 | 0.266692E+11 | 0.221031E+11 | 0.00 | 1.00 | 01-AUG-05:05 | 0.00 | 01-AUG-00:10 | 102761.85 | 04-AUG-05:02 | 61027.18 | 27-AUG-16:12 | 58315.44 | 04-AUG-05:02 | 24215.27 | 13-AUG-12:43 | 0.00 | 01-AUG-00:10 |
September | 0.457555E+11 | 0.121112E+11 | 493.31 | 0.265216E+11 | 0.192339E+11 | 0.00 | 1.00 | 01-SEP-05:08 | 0.00 | 01-SEP-00:23 | 96836.96 | 01-SEP-05:08 | 64060.87 | 10-SEP-13:32 | 45460.01 | 01-SEP-05:08 | 23697.47 | 04-SEP-16:03 | 0.00 | 01-SEP-00:10 |
October | 0.396122E+11 | 0.104550E+11 | 463.24 | 0.227048E+11 | 0.169074E+11 | 0.00 | 1.00 | 01-OCT-08:35 | 0.00 | 01-OCT-00:15 | 99210.72 | 24-OCT-05:04 | 63371.30 | 08-OCT-14:13 | 49766.15 | 24-OCT-05:04 | 23627.09 | 29-OCT-12:53 | 0.00 | 01-OCT-00:10 |
November | 0.364545E+11 | 0.973080E+10 | 431.84 | 0.223751E+11 | 0.140794E+11 | 0.00 | 1.00 | 01-NOV-17:10 | 0.00 | 01-NOV-00:10 | 96222.47 | 30-NOV-06:06 | 66155.55 | 19-NOV-13:23 | 42308.22 | 30-NOV-06:06 | 23145.76 | 11-NOV-14:02 | 0.00 | 01-NOV-00:10 |
December | 0.333544E+11 | 0.903533E+10 | 406.53 | 0.219062E+11 | 0.114482E+11 | 0.00 | 1.00 | 03-DEC-10:03 | 0.00 | 01-DEC-00:10 | 95922.54 | 30-DEC-06:01 | 69213.57 | 03-DEC-14:43 | 41275.81 | 30-DEC-06:01 | 23112.34 | 31-DEC-09:53 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.542395E+12 | 0.145538E+12 | 5804.90 | 0.332362E+12 | 0.210034E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.333544E+11 | 0.903533E+10 | 406.53 | 0.219062E+11 | 0.112330E+11 | 0.00 | 1.00 | 0.00 | 94239.80 | 61027.18 | 38654.13 | 22770.08 | 0.00 | |||||||
Maximum of Months | 0.607660E+11 | 0.162163E+11 | 547.40 | 0.351220E+11 | 0.256441E+11 | 0.00 | 1.00 | 0.00 | 102761.85 | 71381.30 | 58315.44 | 24464.19 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 82.77 | 29.23 | 53.54 | 155.06 | 32.72 | 0.00 | 0.00 | 0.00 |
February | 90.67 | 32.09 | 58.58 | 174.59 | 27.83 | 0.00 | 0.00 | 0.00 |
March | 101.69 | 40.20 | 61.49 | 200.18 | 22.82 | 0.00 | 0.00 | 0.00 |
April | 102.00 | 38.99 | 63.01 | 200.86 | 14.64 | 0.00 | 0.00 | 0.00 |
May | 86.89 | 25.74 | 61.16 | 175.75 | 15.17 | 0.00 | 0.00 | 0.00 |
June | 94.11 | 32.41 | 61.71 | 188.44 | 15.97 | 0.00 | 0.00 | 0.00 |
July | 80.32 | 18.96 | 61.36 | 152.16 | 22.18 | 0.00 | 0.00 | 0.00 |
August | 87.37 | 25.91 | 61.47 | 163.53 | 19.96 | 0.00 | 0.00 | 0.00 |
September | 81.68 | 22.60 | 59.08 | 156.62 | 19.80 | 0.00 | 0.00 | 0.00 |
October | 76.79 | 19.78 | 57.00 | 140.94 | 23.24 | 0.00 | 0.00 | 0.00 |
November | 74.77 | 20.32 | 54.46 | 138.65 | 25.81 | 0.00 | 0.00 | 0.00 |
December | 76.67 | 25.11 | 51.56 | 143.14 | 34.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 86.26 | 27.56 | 58.69 | 165.70 | 22.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.77 | 18.96 | 51.56 | 138.65 | 14.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.00 | 40.20 | 63.01 | 200.86 | 34.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 82.77 | 29.23 | 53.54 | 155.06 | 32.72 | 0.00 | 0.00 | 0.00 |
February | 90.67 | 32.09 | 58.58 | 174.59 | 27.83 | 0.00 | 0.00 | 0.00 |
March | 101.69 | 40.20 | 61.49 | 200.18 | 22.82 | 0.00 | 0.00 | 0.00 |
April | 102.00 | 38.99 | 63.01 | 200.86 | 14.64 | 0.00 | 0.00 | 0.00 |
May | 86.89 | 25.74 | 61.16 | 175.75 | 15.17 | 0.00 | 0.00 | 0.00 |
June | 94.11 | 32.41 | 61.71 | 188.44 | 15.97 | 0.00 | 0.00 | 0.00 |
July | 80.32 | 18.96 | 61.36 | 152.16 | 22.18 | 0.00 | 0.00 | 0.00 |
August | 87.37 | 25.91 | 61.47 | 163.53 | 19.96 | 0.00 | 0.00 | 0.00 |
September | 81.68 | 22.60 | 59.08 | 156.62 | 19.80 | 0.00 | 0.00 | 0.00 |
October | 76.79 | 19.78 | 57.00 | 140.94 | 23.24 | 0.00 | 0.00 | 0.00 |
November | 74.77 | 20.32 | 54.46 | 138.65 | 25.81 | 0.00 | 0.00 | 0.00 |
December | 76.67 | 25.11 | 51.56 | 143.14 | 34.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 86.26 | 27.56 | 58.69 | 165.70 | 22.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.77 | 18.96 | 51.56 | 138.65 | 14.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.00 | 40.20 | 63.01 | 200.86 | 34.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.65 | 0.00 | 24.65 | 46.51 | 19.05 | 0.00 | 0.00 | 0.00 |
February | 26.29 | 0.00 | 26.29 | 52.55 | 16.21 | 0.00 | 0.00 | 0.00 |
March | 27.01 | 0.00 | 27.00 | 57.34 | 13.22 | 0.00 | 0.00 | 0.00 |
April | 29.74 | 0.56 | 29.18 | 64.10 | 8.48 | 0.00 | 0.00 | 0.00 |
May | 37.75 | 4.12 | 33.63 | 83.06 | 8.85 | 0.00 | 0.00 | 0.00 |
June | 45.84 | 9.16 | 36.69 | 100.19 | 9.37 | 0.00 | 0.00 | 0.00 |
July | 39.41 | 4.01 | 35.40 | 78.22 | 12.78 | 0.00 | 0.00 | 0.00 |
August | 32.80 | 1.61 | 31.19 | 65.14 | 11.62 | 0.00 | 0.00 | 0.00 |
September | 27.76 | 0.04 | 27.73 | 55.82 | 11.60 | 0.00 | 0.00 | 0.00 |
October | 26.71 | 0.00 | 26.71 | 49.79 | 13.61 | 0.00 | 0.00 | 0.00 |
November | 25.27 | 0.00 | 25.27 | 47.35 | 15.07 | 0.00 | 0.00 | 0.00 |
December | 23.94 | 0.00 | 23.94 | 44.81 | 20.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 30.62 | 1.63 | 28.99 | 62.10 | 13.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.94 | 0.00 | 23.94 | 44.81 | 8.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 45.84 | 9.16 | 36.69 | 100.19 | 20.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.65 | 0.00 | 24.65 | 46.51 | 19.05 | 0.00 | 0.00 | 0.00 |
February | 26.29 | 0.00 | 26.29 | 52.54 | 16.21 | 0.00 | 0.00 | 0.00 |
March | 27.00 | 0.00 | 27.00 | 57.34 | 13.22 | 0.00 | 0.00 | 0.00 |
April | 29.74 | 0.56 | 29.18 | 64.09 | 8.47 | 0.00 | 0.00 | 0.00 |
May | 37.75 | 4.12 | 33.63 | 83.05 | 8.85 | 0.00 | 0.00 | 0.00 |
June | 45.84 | 9.15 | 36.69 | 100.18 | 9.37 | 0.00 | 0.00 | 0.00 |
July | 39.41 | 4.01 | 35.40 | 78.22 | 12.78 | 0.00 | 0.00 | 0.00 |
August | 32.80 | 1.61 | 31.19 | 65.13 | 11.62 | 0.00 | 0.00 | 0.00 |
September | 27.76 | 0.04 | 27.72 | 55.81 | 11.60 | 0.00 | 0.00 | 0.00 |
October | 26.70 | 0.00 | 26.70 | 49.79 | 13.61 | 0.00 | 0.00 | 0.00 |
November | 25.27 | 0.00 | 25.27 | 47.35 | 15.07 | 0.00 | 0.00 | 0.00 |
December | 23.94 | 0.00 | 23.94 | 44.81 | 20.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 30.62 | 1.63 | 28.99 | 62.10 | 13.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.94 | 0.00 | 23.94 | 44.81 | 8.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 45.84 | 9.15 | 36.69 | 100.18 | 20.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.96 | 24.91 | 27.05 | 95.15 | 18.36 | 0.00 | 0.00 | 0.00 |
February | 59.85 | 31.05 | 28.81 | 110.98 | 18.56 | 0.00 | 0.00 | 0.00 |
March | 69.53 | 40.79 | 28.74 | 129.33 | 15.46 | 0.00 | 0.00 | 0.00 |
April | 70.25 | 39.33 | 30.92 | 131.37 | 11.34 | 0.00 | 0.00 | 0.00 |
May | 58.84 | 25.58 | 33.27 | 111.18 | 10.00 | 0.00 | 0.00 | 0.00 |
June | 63.63 | 31.49 | 32.14 | 120.02 | 9.77 | 0.00 | 0.00 | 0.00 |
July | 53.54 | 17.75 | 35.79 | 99.71 | 12.30 | 0.00 | 0.00 | 0.00 |
August | 59.12 | 25.37 | 33.74 | 106.04 | 11.88 | 0.00 | 0.00 | 0.00 |
September | 54.67 | 21.25 | 33.42 | 101.85 | 11.49 | 0.00 | 0.00 | 0.00 |
October | 49.99 | 17.74 | 32.24 | 89.54 | 12.55 | 0.00 | 0.00 | 0.00 |
November | 47.59 | 17.98 | 29.62 | 86.88 | 14.88 | 0.00 | 0.00 | 0.00 |
December | 48.15 | 21.63 | 26.52 | 88.03 | 19.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.22 | 26.18 | 31.03 | 105.75 | 13.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.59 | 17.74 | 26.52 | 86.88 | 9.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.25 | 40.79 | 35.79 | 131.37 | 19.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.96 | 24.91 | 27.05 | 95.15 | 18.36 | 0.00 | 0.00 | 0.00 |
February | 59.85 | 31.05 | 28.81 | 110.98 | 18.56 | 0.00 | 0.00 | 0.00 |
March | 69.53 | 40.79 | 28.74 | 129.33 | 15.46 | 0.00 | 0.00 | 0.00 |
April | 70.25 | 39.33 | 30.92 | 131.37 | 11.34 | 0.00 | 0.00 | 0.00 |
May | 58.84 | 25.58 | 33.27 | 111.18 | 10.00 | 0.00 | 0.00 | 0.00 |
June | 63.63 | 31.49 | 32.14 | 120.02 | 9.77 | 0.00 | 0.00 | 0.00 |
July | 53.54 | 17.75 | 35.79 | 99.71 | 12.30 | 0.00 | 0.00 | 0.00 |
August | 59.12 | 25.37 | 33.74 | 106.04 | 11.88 | 0.00 | 0.00 | 0.00 |
September | 54.67 | 21.25 | 33.42 | 101.85 | 11.49 | 0.00 | 0.00 | 0.00 |
October | 49.99 | 17.74 | 32.24 | 89.54 | 12.55 | 0.00 | 0.00 | 0.00 |
November | 47.59 | 17.98 | 29.62 | 86.88 | 14.88 | 0.00 | 0.00 | 0.00 |
December | 48.15 | 21.63 | 26.52 | 88.03 | 19.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.22 | 26.18 | 31.03 | 105.75 | 13.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.59 | 17.74 | 26.52 | 86.88 | 9.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.25 | 40.79 | 35.79 | 131.37 | 19.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.96 | 24.91 | 27.05 | 95.15 | 18.36 | 0.00 | 0.00 | 0.00 |
February | 59.85 | 31.05 | 28.81 | 110.98 | 18.56 | 0.00 | 0.00 | 0.00 |
March | 69.53 | 40.79 | 28.74 | 129.33 | 15.46 | 0.00 | 0.00 | 0.00 |
April | 70.25 | 39.33 | 30.92 | 131.37 | 11.34 | 0.00 | 0.00 | 0.00 |
May | 58.84 | 25.58 | 33.27 | 111.18 | 10.00 | 0.00 | 0.00 | 0.00 |
June | 63.63 | 31.49 | 32.14 | 120.02 | 9.77 | 0.00 | 0.00 | 0.00 |
July | 53.54 | 17.75 | 35.79 | 99.71 | 12.30 | 0.00 | 0.00 | 0.00 |
August | 59.12 | 25.37 | 33.74 | 106.04 | 11.88 | 0.00 | 0.00 | 0.00 |
September | 54.67 | 21.25 | 33.42 | 101.85 | 11.49 | 0.00 | 0.00 | 0.00 |
October | 49.99 | 17.74 | 32.24 | 89.54 | 12.55 | 0.00 | 0.00 | 0.00 |
November | 47.59 | 17.98 | 29.62 | 86.88 | 14.88 | 0.00 | 0.00 | 0.00 |
December | 48.15 | 21.63 | 26.52 | 88.03 | 19.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.22 | 26.18 | 31.03 | 105.75 | 13.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.59 | 17.74 | 26.52 | 86.88 | 9.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.25 | 40.79 | 35.79 | 131.37 | 19.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.96 | 24.91 | 27.05 | 95.15 | 18.36 | 0.00 | 0.00 | 0.00 |
February | 59.85 | 31.05 | 28.81 | 110.98 | 18.56 | 0.00 | 0.00 | 0.00 |
March | 69.53 | 40.79 | 28.74 | 129.33 | 15.46 | 0.00 | 0.00 | 0.00 |
April | 70.25 | 39.33 | 30.92 | 131.37 | 11.34 | 0.00 | 0.00 | 0.00 |
May | 58.84 | 25.58 | 33.27 | 111.18 | 10.00 | 0.00 | 0.00 | 0.00 |
June | 63.63 | 31.49 | 32.14 | 120.02 | 9.77 | 0.00 | 0.00 | 0.00 |
July | 53.54 | 17.75 | 35.79 | 99.71 | 12.30 | 0.00 | 0.00 | 0.00 |
August | 59.12 | 25.37 | 33.74 | 106.04 | 11.88 | 0.00 | 0.00 | 0.00 |
September | 54.67 | 21.25 | 33.42 | 101.85 | 11.49 | 0.00 | 0.00 | 0.00 |
October | 49.99 | 17.74 | 32.24 | 89.54 | 12.55 | 0.00 | 0.00 | 0.00 |
November | 47.59 | 17.98 | 29.62 | 86.88 | 14.88 | 0.00 | 0.00 | 0.00 |
December | 48.15 | 21.63 | 26.52 | 88.03 | 19.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.22 | 26.18 | 31.03 | 105.75 | 13.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.59 | 17.74 | 26.52 | 86.88 | 9.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.25 | 40.79 | 35.79 | 131.37 | 19.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.96 | 24.91 | 27.05 | 95.15 | 18.36 | 0.00 | 0.00 | 0.00 |
February | 59.85 | 31.05 | 28.81 | 110.98 | 18.56 | 0.00 | 0.00 | 0.00 |
March | 69.53 | 40.79 | 28.74 | 129.33 | 15.46 | 0.00 | 0.00 | 0.00 |
April | 70.25 | 39.33 | 30.92 | 131.37 | 11.34 | 0.00 | 0.00 | 0.00 |
May | 58.84 | 25.58 | 33.27 | 111.18 | 10.00 | 0.00 | 0.00 | 0.00 |
June | 63.63 | 31.49 | 32.14 | 120.02 | 9.77 | 0.00 | 0.00 | 0.00 |
July | 53.54 | 17.75 | 35.79 | 99.71 | 12.30 | 0.00 | 0.00 | 0.00 |
August | 59.12 | 25.37 | 33.74 | 106.04 | 11.88 | 0.00 | 0.00 | 0.00 |
September | 54.67 | 21.25 | 33.42 | 101.85 | 11.49 | 0.00 | 0.00 | 0.00 |
October | 49.99 | 17.74 | 32.24 | 89.54 | 12.55 | 0.00 | 0.00 | 0.00 |
November | 47.59 | 17.98 | 29.62 | 86.88 | 14.88 | 0.00 | 0.00 | 0.00 |
December | 48.15 | 21.63 | 26.52 | 88.03 | 19.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.22 | 26.18 | 31.03 | 105.75 | 13.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.59 | 17.74 | 26.52 | 86.88 | 9.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.25 | 40.79 | 35.79 | 131.37 | 19.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.96 | 24.91 | 27.05 | 95.15 | 18.36 | 0.00 | 0.00 | 0.00 |
February | 59.85 | 31.05 | 28.81 | 110.98 | 18.56 | 0.00 | 0.00 | 0.00 |
March | 69.53 | 40.79 | 28.74 | 129.33 | 15.46 | 0.00 | 0.00 | 0.00 |
April | 70.25 | 39.33 | 30.92 | 131.37 | 11.34 | 0.00 | 0.00 | 0.00 |
May | 58.84 | 25.58 | 33.27 | 111.18 | 10.00 | 0.00 | 0.00 | 0.00 |
June | 63.63 | 31.49 | 32.14 | 120.02 | 9.77 | 0.00 | 0.00 | 0.00 |
July | 53.54 | 17.75 | 35.79 | 99.71 | 12.30 | 0.00 | 0.00 | 0.00 |
August | 59.12 | 25.37 | 33.74 | 106.04 | 11.88 | 0.00 | 0.00 | 0.00 |
September | 54.67 | 21.25 | 33.42 | 101.85 | 11.49 | 0.00 | 0.00 | 0.00 |
October | 49.99 | 17.74 | 32.24 | 89.54 | 12.55 | 0.00 | 0.00 | 0.00 |
November | 47.59 | 17.98 | 29.62 | 86.88 | 14.88 | 0.00 | 0.00 | 0.00 |
December | 48.15 | 21.63 | 26.52 | 88.03 | 19.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.22 | 26.18 | 31.03 | 105.75 | 13.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.59 | 17.74 | 26.52 | 86.88 | 9.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.25 | 40.79 | 35.79 | 131.37 | 19.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.96 | 24.91 | 27.05 | 95.15 | 18.36 | 0.00 | 0.00 | 0.00 |
February | 59.85 | 31.05 | 28.81 | 110.98 | 18.56 | 0.00 | 0.00 | 0.00 |
March | 69.53 | 40.79 | 28.74 | 129.33 | 15.46 | 0.00 | 0.00 | 0.00 |
April | 70.25 | 39.33 | 30.92 | 131.37 | 11.34 | 0.00 | 0.00 | 0.00 |
May | 58.84 | 25.58 | 33.27 | 111.18 | 10.00 | 0.00 | 0.00 | 0.00 |
June | 63.63 | 31.49 | 32.14 | 120.02 | 9.77 | 0.00 | 0.00 | 0.00 |
July | 53.54 | 17.75 | 35.79 | 99.71 | 12.30 | 0.00 | 0.00 | 0.00 |
August | 59.12 | 25.37 | 33.74 | 106.04 | 11.88 | 0.00 | 0.00 | 0.00 |
September | 54.67 | 21.25 | 33.42 | 101.85 | 11.49 | 0.00 | 0.00 | 0.00 |
October | 49.99 | 17.74 | 32.24 | 89.54 | 12.55 | 0.00 | 0.00 | 0.00 |
November | 47.59 | 17.98 | 29.62 | 86.88 | 14.88 | 0.00 | 0.00 | 0.00 |
December | 48.15 | 21.63 | 26.52 | 88.03 | 19.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.22 | 26.18 | 31.03 | 105.75 | 13.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.59 | 17.74 | 26.52 | 86.88 | 9.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.25 | 40.79 | 35.79 | 131.37 | 19.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.96 | 24.91 | 27.05 | 95.15 | 18.36 | 0.00 | 0.00 | 0.00 |
February | 59.85 | 31.05 | 28.81 | 110.98 | 18.56 | 0.00 | 0.00 | 0.00 |
March | 69.53 | 40.79 | 28.74 | 129.33 | 15.46 | 0.00 | 0.00 | 0.00 |
April | 70.25 | 39.33 | 30.92 | 131.37 | 11.34 | 0.00 | 0.00 | 0.00 |
May | 58.84 | 25.58 | 33.27 | 111.18 | 10.00 | 0.00 | 0.00 | 0.00 |
June | 63.63 | 31.49 | 32.14 | 120.02 | 9.77 | 0.00 | 0.00 | 0.00 |
July | 53.54 | 17.75 | 35.79 | 99.71 | 12.30 | 0.00 | 0.00 | 0.00 |
August | 59.12 | 25.37 | 33.74 | 106.04 | 11.88 | 0.00 | 0.00 | 0.00 |
September | 54.67 | 21.25 | 33.42 | 101.85 | 11.49 | 0.00 | 0.00 | 0.00 |
October | 49.99 | 17.74 | 32.24 | 89.54 | 12.55 | 0.00 | 0.00 | 0.00 |
November | 47.59 | 17.98 | 29.62 | 86.88 | 14.88 | 0.00 | 0.00 | 0.00 |
December | 48.15 | 21.63 | 26.52 | 88.03 | 19.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.22 | 26.18 | 31.03 | 105.75 | 13.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.59 | 17.74 | 26.52 | 86.88 | 9.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.25 | 40.79 | 35.79 | 131.37 | 19.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.96 | 24.91 | 27.05 | 95.15 | 18.36 | 0.00 | 0.00 | 0.00 |
February | 59.85 | 31.05 | 28.81 | 110.98 | 18.56 | 0.00 | 0.00 | 0.00 |
March | 69.53 | 40.79 | 28.74 | 129.33 | 15.46 | 0.00 | 0.00 | 0.00 |
April | 70.25 | 39.33 | 30.92 | 131.37 | 11.34 | 0.00 | 0.00 | 0.00 |
May | 58.84 | 25.58 | 33.27 | 111.18 | 10.00 | 0.00 | 0.00 | 0.00 |
June | 63.63 | 31.49 | 32.14 | 120.02 | 9.77 | 0.00 | 0.00 | 0.00 |
July | 53.54 | 17.75 | 35.79 | 99.71 | 12.30 | 0.00 | 0.00 | 0.00 |
August | 59.12 | 25.37 | 33.74 | 106.04 | 11.88 | 0.00 | 0.00 | 0.00 |
September | 54.67 | 21.25 | 33.42 | 101.85 | 11.49 | 0.00 | 0.00 | 0.00 |
October | 49.99 | 17.74 | 32.24 | 89.54 | 12.55 | 0.00 | 0.00 | 0.00 |
November | 47.59 | 17.98 | 29.62 | 86.88 | 14.88 | 0.00 | 0.00 | 0.00 |
December | 48.15 | 21.63 | 26.52 | 88.03 | 19.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.22 | 26.18 | 31.03 | 105.75 | 13.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.59 | 17.74 | 26.52 | 86.88 | 9.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.25 | 40.79 | 35.79 | 131.37 | 19.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.96 | 24.91 | 27.05 | 95.15 | 18.36 | 0.00 | 0.00 | 0.00 |
February | 59.85 | 31.05 | 28.81 | 110.98 | 18.56 | 0.00 | 0.00 | 0.00 |
March | 69.53 | 40.79 | 28.74 | 129.33 | 15.46 | 0.00 | 0.00 | 0.00 |
April | 70.25 | 39.33 | 30.92 | 131.37 | 11.34 | 0.00 | 0.00 | 0.00 |
May | 58.84 | 25.58 | 33.27 | 111.18 | 10.00 | 0.00 | 0.00 | 0.00 |
June | 63.63 | 31.49 | 32.14 | 120.02 | 9.77 | 0.00 | 0.00 | 0.00 |
July | 53.54 | 17.75 | 35.79 | 99.71 | 12.30 | 0.00 | 0.00 | 0.00 |
August | 59.12 | 25.37 | 33.74 | 106.04 | 11.88 | 0.00 | 0.00 | 0.00 |
September | 54.67 | 21.25 | 33.42 | 101.85 | 11.49 | 0.00 | 0.00 | 0.00 |
October | 49.99 | 17.74 | 32.24 | 89.54 | 12.55 | 0.00 | 0.00 | 0.00 |
November | 47.59 | 17.98 | 29.62 | 86.88 | 14.88 | 0.00 | 0.00 | 0.00 |
December | 48.15 | 21.63 | 26.52 | 88.03 | 19.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.22 | 26.18 | 31.03 | 105.75 | 13.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.59 | 17.74 | 26.52 | 86.88 | 9.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.25 | 40.79 | 35.79 | 131.37 | 19.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.96 | 24.91 | 27.05 | 95.15 | 18.36 | 0.00 | 0.00 | 0.00 |
February | 59.85 | 31.05 | 28.81 | 110.98 | 18.56 | 0.00 | 0.00 | 0.00 |
March | 69.53 | 40.79 | 28.74 | 129.33 | 15.46 | 0.00 | 0.00 | 0.00 |
April | 70.25 | 39.33 | 30.92 | 131.37 | 11.34 | 0.00 | 0.00 | 0.00 |
May | 58.84 | 25.58 | 33.27 | 111.18 | 10.00 | 0.00 | 0.00 | 0.00 |
June | 63.63 | 31.49 | 32.14 | 120.02 | 9.77 | 0.00 | 0.00 | 0.00 |
July | 53.54 | 17.75 | 35.79 | 99.71 | 12.30 | 0.00 | 0.00 | 0.00 |
August | 59.12 | 25.37 | 33.74 | 106.04 | 11.88 | 0.00 | 0.00 | 0.00 |
September | 54.67 | 21.25 | 33.42 | 101.85 | 11.49 | 0.00 | 0.00 | 0.00 |
October | 49.99 | 17.74 | 32.24 | 89.54 | 12.55 | 0.00 | 0.00 | 0.00 |
November | 47.59 | 17.98 | 29.62 | 86.88 | 14.88 | 0.00 | 0.00 | 0.00 |
December | 48.15 | 21.63 | 26.52 | 88.03 | 19.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.22 | 26.18 | 31.03 | 105.75 | 13.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.59 | 17.74 | 26.52 | 86.88 | 9.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.25 | 40.79 | 35.79 | 131.37 | 19.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.96 | 24.91 | 27.05 | 95.15 | 18.36 | 0.00 | 0.00 | 0.00 |
February | 59.85 | 31.05 | 28.81 | 110.98 | 18.56 | 0.00 | 0.00 | 0.00 |
March | 69.53 | 40.79 | 28.74 | 129.33 | 15.46 | 0.00 | 0.00 | 0.00 |
April | 70.25 | 39.33 | 30.92 | 131.37 | 11.34 | 0.00 | 0.00 | 0.00 |
May | 58.84 | 25.58 | 33.27 | 111.18 | 10.00 | 0.00 | 0.00 | 0.00 |
June | 63.63 | 31.49 | 32.14 | 120.02 | 9.77 | 0.00 | 0.00 | 0.00 |
July | 53.54 | 17.75 | 35.79 | 99.71 | 12.30 | 0.00 | 0.00 | 0.00 |
August | 59.12 | 25.37 | 33.74 | 106.04 | 11.88 | 0.00 | 0.00 | 0.00 |
September | 54.67 | 21.25 | 33.42 | 101.85 | 11.49 | 0.00 | 0.00 | 0.00 |
October | 49.99 | 17.74 | 32.24 | 89.54 | 12.55 | 0.00 | 0.00 | 0.00 |
November | 47.59 | 17.98 | 29.62 | 86.88 | 14.88 | 0.00 | 0.00 | 0.00 |
December | 48.15 | 21.63 | 26.52 | 88.03 | 19.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.22 | 26.18 | 31.03 | 105.75 | 13.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.59 | 17.74 | 26.52 | 86.88 | 9.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.25 | 40.79 | 35.79 | 131.37 | 19.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.96 | 24.91 | 27.05 | 95.15 | 18.36 | 0.00 | 0.00 | 0.00 |
February | 59.85 | 31.05 | 28.81 | 110.98 | 18.56 | 0.00 | 0.00 | 0.00 |
March | 69.53 | 40.79 | 28.74 | 129.33 | 15.46 | 0.00 | 0.00 | 0.00 |
April | 70.25 | 39.33 | 30.92 | 131.37 | 11.34 | 0.00 | 0.00 | 0.00 |
May | 58.84 | 25.58 | 33.27 | 111.18 | 10.00 | 0.00 | 0.00 | 0.00 |
June | 63.63 | 31.49 | 32.14 | 120.02 | 9.77 | 0.00 | 0.00 | 0.00 |
July | 53.54 | 17.75 | 35.79 | 99.71 | 12.30 | 0.00 | 0.00 | 0.00 |
August | 59.12 | 25.37 | 33.74 | 106.04 | 11.88 | 0.00 | 0.00 | 0.00 |
September | 54.67 | 21.25 | 33.42 | 101.85 | 11.49 | 0.00 | 0.00 | 0.00 |
October | 49.99 | 17.74 | 32.24 | 89.54 | 12.55 | 0.00 | 0.00 | 0.00 |
November | 47.59 | 17.98 | 29.62 | 86.88 | 14.88 | 0.00 | 0.00 | 0.00 |
December | 48.15 | 21.63 | 26.52 | 88.03 | 19.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.22 | 26.18 | 31.03 | 105.75 | 13.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.59 | 17.74 | 26.52 | 86.88 | 9.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.25 | 40.79 | 35.79 | 131.37 | 19.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.96 | 24.91 | 27.05 | 95.15 | 18.36 | 0.00 | 0.00 | 0.00 |
February | 59.85 | 31.05 | 28.81 | 110.98 | 18.56 | 0.00 | 0.00 | 0.00 |
March | 69.53 | 40.79 | 28.74 | 129.33 | 15.46 | 0.00 | 0.00 | 0.00 |
April | 70.25 | 39.33 | 30.92 | 131.37 | 11.34 | 0.00 | 0.00 | 0.00 |
May | 58.84 | 25.58 | 33.27 | 111.18 | 10.00 | 0.00 | 0.00 | 0.00 |
June | 63.63 | 31.49 | 32.14 | 120.02 | 9.77 | 0.00 | 0.00 | 0.00 |
July | 53.54 | 17.75 | 35.79 | 99.71 | 12.30 | 0.00 | 0.00 | 0.00 |
August | 59.12 | 25.37 | 33.74 | 106.04 | 11.88 | 0.00 | 0.00 | 0.00 |
September | 54.67 | 21.25 | 33.42 | 101.85 | 11.49 | 0.00 | 0.00 | 0.00 |
October | 49.99 | 17.74 | 32.24 | 89.54 | 12.55 | 0.00 | 0.00 | 0.00 |
November | 47.59 | 17.98 | 29.62 | 86.88 | 14.88 | 0.00 | 0.00 | 0.00 |
December | 48.15 | 21.63 | 26.52 | 88.03 | 19.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.22 | 26.18 | 31.03 | 105.75 | 13.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.59 | 17.74 | 26.52 | 86.88 | 9.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.25 | 40.79 | 35.79 | 131.37 | 19.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.28 | 39.04 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.84 | 40.59 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.11 | 35.06 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 191.94 | 28.03 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.81 | 26.34 | 153.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.68 | 25.33 | 67.00 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.05 | 28.65 | 3.50 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.88 | 27.56 | 81.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.50 | 27.62 | 28.50 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.02 | 29.85 | 65.00 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.22 | 32.85 | 22.83 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.77 | 39.44 | 29.83 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.04 | 31.66 | 452.33 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.22 | 25.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 191.94 | 40.59 | 153.67 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.221681E+09 | 78284555.57 | 0.143396E+09 | 0.415304E+09 | 87624331.93 |
February | 0.219348E+09 | 77633443.43 | 0.141714E+09 | 0.422368E+09 | 67328270.08 |
March | 0.272367E+09 | 0.107680E+09 | 0.164687E+09 | 0.536164E+09 | 61125035.22 |
April | 0.264381E+09 | 0.101056E+09 | 0.163326E+09 | 0.520633E+09 | 37954938.30 |
May | 0.232730E+09 | 68932137.35 | 0.163798E+09 | 0.470730E+09 | 40628836.62 |
June | 0.243945E+09 | 84003696.89 | 0.159941E+09 | 0.488427E+09 | 41386872.15 |
July | 0.215136E+09 | 50784937.62 | 0.164351E+09 | 0.407557E+09 | 59414953.89 |
August | 0.234022E+09 | 69388628.09 | 0.164634E+09 | 0.437994E+09 | 53473875.39 |
September | 0.211721E+09 | 58582592.98 | 0.153138E+09 | 0.405964E+09 | 51319421.50 |
October | 0.205662E+09 | 52990425.58 | 0.152671E+09 | 0.377486E+09 | 62240058.63 |
November | 0.193813E+09 | 52665452.63 | 0.141148E+09 | 0.359381E+09 | 66896193.99 |
December | 0.205363E+09 | 67253785.62 | 0.138109E+09 | 0.383388E+09 | 93320823.26 |
Annual Sum or Average | 0.272017E+10 | 0.869256E+09 | 0.185091E+10 | 0.522540E+10 | 0.722714E+09 |
Minimum of Months | 0.193813E+09 | 50784937.62 | 0.138109E+09 | 0.359381E+09 | 37954938.30 |
Maximum of Months | 0.272367E+09 | 0.107680E+09 | 0.164687E+09 | 0.536164E+09 | 93320823.26 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.221681E+09 | 78284555.57 | 0.143396E+09 | 0.415304E+09 | 87624331.93 |
February | 0.219348E+09 | 77633443.43 | 0.141714E+09 | 0.422368E+09 | 67328270.08 |
March | 0.272367E+09 | 0.107680E+09 | 0.164687E+09 | 0.536164E+09 | 61125035.22 |
April | 0.264381E+09 | 0.101056E+09 | 0.163326E+09 | 0.520633E+09 | 37954938.30 |
May | 0.232730E+09 | 68932137.35 | 0.163798E+09 | 0.470730E+09 | 40628836.62 |
June | 0.243945E+09 | 84003696.89 | 0.159941E+09 | 0.488427E+09 | 41386872.15 |
July | 0.215136E+09 | 50784937.62 | 0.164351E+09 | 0.407557E+09 | 59414953.89 |
August | 0.234022E+09 | 69388628.09 | 0.164634E+09 | 0.437994E+09 | 53473875.39 |
September | 0.211721E+09 | 58582592.98 | 0.153138E+09 | 0.405964E+09 | 51319421.50 |
October | 0.205662E+09 | 52990425.58 | 0.152671E+09 | 0.377486E+09 | 62240058.63 |
November | 0.193813E+09 | 52665452.63 | 0.141148E+09 | 0.359381E+09 | 66896193.99 |
December | 0.205363E+09 | 67253785.62 | 0.138109E+09 | 0.383388E+09 | 93320823.26 |
Annual Sum or Average | 0.272017E+10 | 0.869256E+09 | 0.185091E+10 | 0.522540E+10 | 0.722714E+09 |
Minimum of Months | 0.193813E+09 | 50784937.62 | 0.138109E+09 | 0.359381E+09 | 37954938.30 |
Maximum of Months | 0.272367E+09 | 0.107680E+09 | 0.164687E+09 | 0.536164E+09 | 93320823.26 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66014107.71 | 0.00 | 66014107.71 | 0.124571E+09 | 51014837.15 |
February | 63604241.65 | 0.00 | 63604241.65 | 0.127119E+09 | 39221869.24 |
March | 72330530.75 | 12772.18 | 72317758.57 | 0.153575E+09 | 35421690.09 |
April | 77095458.20 | 1452960.40 | 75642497.80 | 0.166137E+09 | 21967925.05 |
May | 0.101115E+09 | 11035434.82 | 90079927.44 | 0.222458E+09 | 23697156.59 |
June | 0.118824E+09 | 23729916.09 | 95094421.52 | 0.259683E+09 | 24279949.74 |
July | 0.105552E+09 | 10743834.65 | 94808014.59 | 0.209516E+09 | 34226345.41 |
August | 87854349.87 | 4315389.29 | 83538960.58 | 0.174461E+09 | 31119189.41 |
September | 71964609.48 | 99284.84 | 71865324.64 | 0.144675E+09 | 30079264.45 |
October | 71527824.82 | 0.00 | 71527824.82 | 0.133348E+09 | 36451182.28 |
November | 65497815.40 | 0.00 | 65497815.40 | 0.122739E+09 | 39067762.85 |
December | 64131789.98 | 0.00 | 64131789.98 | 0.120019E+09 | 54353937.21 |
Annual Sum or Average | 0.965512E+09 | 51389592.26 | 0.914123E+09 | 0.195830E+10 | 0.420901E+09 |
Minimum of Months | 63604241.65 | 0.00 | 63604241.65 | 0.120019E+09 | 21967925.05 |
Maximum of Months | 0.118824E+09 | 23729916.09 | 95094421.52 | 0.259683E+09 | 54353937.21 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66012072.14 | 0.00 | 66012072.14 | 0.124568E+09 | 51014004.54 |
February | 63602352.55 | 0.00 | 63602352.55 | 0.127117E+09 | 39220921.82 |
March | 72328517.32 | 12771.58 | 72315745.74 | 0.153572E+09 | 35420769.46 |
April | 77093195.21 | 1452892.29 | 75640302.92 | 0.166133E+09 | 21967188.96 |
May | 0.101112E+09 | 11034917.57 | 90076890.72 | 0.222452E+09 | 23696571.05 |
June | 0.118820E+09 | 23728803.84 | 95091198.75 | 0.259675E+09 | 24279430.45 |
July | 0.105548E+09 | 10743331.07 | 94804660.23 | 0.209509E+09 | 34225731.55 |
August | 87851422.41 | 4315187.02 | 83536235.39 | 0.174457E+09 | 31118568.71 |
September | 71962306.01 | 99280.19 | 71863025.82 | 0.144671E+09 | 30078712.34 |
October | 71525490.68 | 0.00 | 71525490.68 | 0.133345E+09 | 36450641.67 |
November | 65495689.49 | 0.00 | 65495689.49 | 0.122735E+09 | 39067097.98 |
December | 64129771.06 | 0.00 | 64129771.06 | 0.120017E+09 | 54353101.82 |
Annual Sum or Average | 0.965481E+09 | 51387183.56 | 0.914093E+09 | 0.195825E+10 | 0.420893E+09 |
Minimum of Months | 63602352.55 | 0.00 | 63602352.55 | 0.120017E+09 | 21967188.96 |
Maximum of Months | 0.118820E+09 | 23728803.84 | 95091198.75 | 0.259675E+09 | 54353101.82 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139167E+09 | 66711853.24 | 72454853.33 | 0.254840E+09 | 49181882.51 |
February | 0.144797E+09 | 75106376.30 | 69690163.67 | 0.268481E+09 | 44906585.33 |
March | 0.186227E+09 | 0.109254E+09 | 76972999.00 | 0.346402E+09 | 41402357.74 |
April | 0.182089E+09 | 0.101951E+09 | 80138586.32 | 0.340506E+09 | 29399851.22 |
May | 0.157606E+09 | 68504884.84 | 89100783.41 | 0.297797E+09 | 26785788.33 |
June | 0.164917E+09 | 81611812.55 | 83305408.05 | 0.311094E+09 | 25329975.21 |
July | 0.143399E+09 | 47548118.69 | 95851218.54 | 0.267076E+09 | 32952608.58 |
August | 0.158337E+09 | 67955551.24 | 90381266.57 | 0.284026E+09 | 31809546.24 |
September | 0.141696E+09 | 55068414.89 | 86627624.19 | 0.263988E+09 | 29790820.96 |
October | 0.133890E+09 | 47526586.69 | 86362925.35 | 0.239832E+09 | 33625872.69 |
November | 0.123363E+09 | 46596465.64 | 76766434.06 | 0.225202E+09 | 38572035.57 |
December | 0.128964E+09 | 57924158.47 | 71039831.93 | 0.235786E+09 | 51030732.15 |
Annual Sum or Average | 0.180445E+10 | 0.825759E+09 | 0.978692E+09 | 0.333503E+10 | 0.434788E+09 |
Minimum of Months | 0.123363E+09 | 46596465.64 | 69690163.67 | 0.225202E+09 | 25329975.21 |
Maximum of Months | 0.186227E+09 | 0.109254E+09 | 95851218.54 | 0.346402E+09 | 51030732.15 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139167E+09 | 66711853.24 | 72454853.33 | 0.254840E+09 | 49181882.51 |
February | 0.144797E+09 | 75106376.30 | 69690163.67 | 0.268481E+09 | 44906585.33 |
March | 0.186227E+09 | 0.109254E+09 | 76972999.00 | 0.346402E+09 | 41402357.74 |
April | 0.182089E+09 | 0.101951E+09 | 80138586.32 | 0.340506E+09 | 29399851.22 |
May | 0.157606E+09 | 68504884.84 | 89100783.41 | 0.297797E+09 | 26785788.33 |
June | 0.164917E+09 | 81611812.55 | 83305408.05 | 0.311094E+09 | 25329975.21 |
July | 0.143399E+09 | 47548118.69 | 95851218.54 | 0.267076E+09 | 32952608.58 |
August | 0.158337E+09 | 67955551.24 | 90381266.57 | 0.284026E+09 | 31809546.24 |
September | 0.141696E+09 | 55068414.89 | 86627624.19 | 0.263988E+09 | 29790820.96 |
October | 0.133890E+09 | 47526586.69 | 86362925.35 | 0.239832E+09 | 33625872.69 |
November | 0.123363E+09 | 46596465.64 | 76766434.06 | 0.225202E+09 | 38572035.57 |
December | 0.128964E+09 | 57924158.47 | 71039831.93 | 0.235786E+09 | 51030732.15 |
Annual Sum or Average | 0.180445E+10 | 0.825759E+09 | 0.978692E+09 | 0.333503E+10 | 0.434788E+09 |
Minimum of Months | 0.123363E+09 | 46596465.64 | 69690163.67 | 0.225202E+09 | 25329975.21 |
Maximum of Months | 0.186227E+09 | 0.109254E+09 | 95851218.54 | 0.346402E+09 | 51030732.15 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139167E+09 | 66711853.24 | 72454853.33 | 0.254840E+09 | 49181882.51 |
February | 0.144797E+09 | 75106376.30 | 69690163.67 | 0.268481E+09 | 44906585.33 |
March | 0.186227E+09 | 0.109254E+09 | 76972999.00 | 0.346402E+09 | 41402357.74 |
April | 0.182089E+09 | 0.101951E+09 | 80138586.32 | 0.340506E+09 | 29399851.22 |
May | 0.157606E+09 | 68504884.84 | 89100783.41 | 0.297797E+09 | 26785788.33 |
June | 0.164917E+09 | 81611812.55 | 83305408.05 | 0.311094E+09 | 25329975.21 |
July | 0.143399E+09 | 47548118.69 | 95851218.54 | 0.267076E+09 | 32952608.58 |
August | 0.158337E+09 | 67955551.24 | 90381266.57 | 0.284026E+09 | 31809546.24 |
September | 0.141696E+09 | 55068414.89 | 86627624.19 | 0.263988E+09 | 29790820.96 |
October | 0.133890E+09 | 47526586.69 | 86362925.35 | 0.239832E+09 | 33625872.69 |
November | 0.123363E+09 | 46596465.64 | 76766434.06 | 0.225202E+09 | 38572035.57 |
December | 0.128964E+09 | 57924158.47 | 71039831.93 | 0.235786E+09 | 51030732.15 |
Annual Sum or Average | 0.180445E+10 | 0.825759E+09 | 0.978692E+09 | 0.333503E+10 | 0.434788E+09 |
Minimum of Months | 0.123363E+09 | 46596465.64 | 69690163.67 | 0.225202E+09 | 25329975.21 |
Maximum of Months | 0.186227E+09 | 0.109254E+09 | 95851218.54 | 0.346402E+09 | 51030732.15 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139167E+09 | 66711853.24 | 72454853.33 | 0.254840E+09 | 49181882.51 |
February | 0.144797E+09 | 75106376.30 | 69690163.67 | 0.268481E+09 | 44906585.33 |
March | 0.186227E+09 | 0.109254E+09 | 76972999.00 | 0.346402E+09 | 41402357.74 |
April | 0.182089E+09 | 0.101951E+09 | 80138586.32 | 0.340506E+09 | 29399851.22 |
May | 0.157606E+09 | 68504884.84 | 89100783.41 | 0.297797E+09 | 26785788.33 |
June | 0.164917E+09 | 81611812.55 | 83305408.05 | 0.311094E+09 | 25329975.21 |
July | 0.143399E+09 | 47548118.69 | 95851218.54 | 0.267076E+09 | 32952608.58 |
August | 0.158337E+09 | 67955551.24 | 90381266.57 | 0.284026E+09 | 31809546.24 |
September | 0.141696E+09 | 55068414.89 | 86627624.19 | 0.263988E+09 | 29790820.96 |
October | 0.133890E+09 | 47526586.69 | 86362925.35 | 0.239832E+09 | 33625872.69 |
November | 0.123363E+09 | 46596465.64 | 76766434.06 | 0.225202E+09 | 38572035.57 |
December | 0.128964E+09 | 57924158.47 | 71039831.93 | 0.235786E+09 | 51030732.15 |
Annual Sum or Average | 0.180445E+10 | 0.825759E+09 | 0.978692E+09 | 0.333503E+10 | 0.434788E+09 |
Minimum of Months | 0.123363E+09 | 46596465.64 | 69690163.67 | 0.225202E+09 | 25329975.21 |
Maximum of Months | 0.186227E+09 | 0.109254E+09 | 95851218.54 | 0.346402E+09 | 51030732.15 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139167E+09 | 66711853.24 | 72454853.33 | 0.254840E+09 | 49181882.51 |
February | 0.144797E+09 | 75106376.30 | 69690163.67 | 0.268481E+09 | 44906585.33 |
March | 0.186227E+09 | 0.109254E+09 | 76972999.00 | 0.346402E+09 | 41402357.74 |
April | 0.182089E+09 | 0.101951E+09 | 80138586.32 | 0.340506E+09 | 29399851.22 |
May | 0.157606E+09 | 68504884.84 | 89100783.41 | 0.297797E+09 | 26785788.33 |
June | 0.164917E+09 | 81611812.55 | 83305408.05 | 0.311094E+09 | 25329975.21 |
July | 0.143399E+09 | 47548118.69 | 95851218.54 | 0.267076E+09 | 32952608.58 |
August | 0.158337E+09 | 67955551.24 | 90381266.57 | 0.284026E+09 | 31809546.24 |
September | 0.141696E+09 | 55068414.89 | 86627624.19 | 0.263988E+09 | 29790820.96 |
October | 0.133890E+09 | 47526586.69 | 86362925.35 | 0.239832E+09 | 33625872.69 |
November | 0.123363E+09 | 46596465.64 | 76766434.06 | 0.225202E+09 | 38572035.57 |
December | 0.128964E+09 | 57924158.47 | 71039831.93 | 0.235786E+09 | 51030732.15 |
Annual Sum or Average | 0.180445E+10 | 0.825759E+09 | 0.978692E+09 | 0.333503E+10 | 0.434788E+09 |
Minimum of Months | 0.123363E+09 | 46596465.64 | 69690163.67 | 0.225202E+09 | 25329975.21 |
Maximum of Months | 0.186227E+09 | 0.109254E+09 | 95851218.54 | 0.346402E+09 | 51030732.15 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139167E+09 | 66711853.24 | 72454853.33 | 0.254840E+09 | 49181882.51 |
February | 0.144797E+09 | 75106376.30 | 69690163.67 | 0.268481E+09 | 44906585.33 |
March | 0.186227E+09 | 0.109254E+09 | 76972999.00 | 0.346402E+09 | 41402357.74 |
April | 0.182089E+09 | 0.101951E+09 | 80138586.32 | 0.340506E+09 | 29399851.22 |
May | 0.157606E+09 | 68504884.84 | 89100783.41 | 0.297797E+09 | 26785788.33 |
June | 0.164917E+09 | 81611812.55 | 83305408.05 | 0.311094E+09 | 25329975.21 |
July | 0.143399E+09 | 47548118.69 | 95851218.54 | 0.267076E+09 | 32952608.58 |
August | 0.158337E+09 | 67955551.24 | 90381266.57 | 0.284026E+09 | 31809546.24 |
September | 0.141696E+09 | 55068414.89 | 86627624.19 | 0.263988E+09 | 29790820.96 |
October | 0.133890E+09 | 47526586.69 | 86362925.35 | 0.239832E+09 | 33625872.69 |
November | 0.123363E+09 | 46596465.64 | 76766434.06 | 0.225202E+09 | 38572035.57 |
December | 0.128964E+09 | 57924158.47 | 71039831.93 | 0.235786E+09 | 51030732.15 |
Annual Sum or Average | 0.180445E+10 | 0.825759E+09 | 0.978692E+09 | 0.333503E+10 | 0.434788E+09 |
Minimum of Months | 0.123363E+09 | 46596465.64 | 69690163.67 | 0.225202E+09 | 25329975.21 |
Maximum of Months | 0.186227E+09 | 0.109254E+09 | 95851218.54 | 0.346402E+09 | 51030732.15 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139167E+09 | 66711853.24 | 72454853.33 | 0.254840E+09 | 49181882.51 |
February | 0.144797E+09 | 75106376.30 | 69690163.67 | 0.268481E+09 | 44906585.33 |
March | 0.186227E+09 | 0.109254E+09 | 76972999.00 | 0.346402E+09 | 41402357.74 |
April | 0.182089E+09 | 0.101951E+09 | 80138586.32 | 0.340506E+09 | 29399851.22 |
May | 0.157606E+09 | 68504884.84 | 89100783.41 | 0.297797E+09 | 26785788.33 |
June | 0.164917E+09 | 81611812.55 | 83305408.05 | 0.311094E+09 | 25329975.21 |
July | 0.143399E+09 | 47548118.69 | 95851218.54 | 0.267076E+09 | 32952608.58 |
August | 0.158337E+09 | 67955551.24 | 90381266.57 | 0.284026E+09 | 31809546.24 |
September | 0.141696E+09 | 55068414.89 | 86627624.19 | 0.263988E+09 | 29790820.96 |
October | 0.133890E+09 | 47526586.69 | 86362925.35 | 0.239832E+09 | 33625872.69 |
November | 0.123363E+09 | 46596465.64 | 76766434.06 | 0.225202E+09 | 38572035.57 |
December | 0.128964E+09 | 57924158.47 | 71039831.93 | 0.235786E+09 | 51030732.15 |
Annual Sum or Average | 0.180445E+10 | 0.825759E+09 | 0.978692E+09 | 0.333503E+10 | 0.434788E+09 |
Minimum of Months | 0.123363E+09 | 46596465.64 | 69690163.67 | 0.225202E+09 | 25329975.21 |
Maximum of Months | 0.186227E+09 | 0.109254E+09 | 95851218.54 | 0.346402E+09 | 51030732.15 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139167E+09 | 66711853.24 | 72454853.33 | 0.254840E+09 | 49181882.51 |
February | 0.144797E+09 | 75106376.30 | 69690163.67 | 0.268481E+09 | 44906585.33 |
March | 0.186227E+09 | 0.109254E+09 | 76972999.00 | 0.346402E+09 | 41402357.74 |
April | 0.182089E+09 | 0.101951E+09 | 80138586.32 | 0.340506E+09 | 29399851.22 |
May | 0.157606E+09 | 68504884.84 | 89100783.41 | 0.297797E+09 | 26785788.33 |
June | 0.164917E+09 | 81611812.55 | 83305408.05 | 0.311094E+09 | 25329975.21 |
July | 0.143399E+09 | 47548118.69 | 95851218.54 | 0.267076E+09 | 32952608.58 |
August | 0.158337E+09 | 67955551.24 | 90381266.57 | 0.284026E+09 | 31809546.24 |
September | 0.141696E+09 | 55068414.89 | 86627624.19 | 0.263988E+09 | 29790820.96 |
October | 0.133890E+09 | 47526586.69 | 86362925.35 | 0.239832E+09 | 33625872.69 |
November | 0.123363E+09 | 46596465.64 | 76766434.06 | 0.225202E+09 | 38572035.57 |
December | 0.128964E+09 | 57924158.47 | 71039831.93 | 0.235786E+09 | 51030732.15 |
Annual Sum or Average | 0.180445E+10 | 0.825759E+09 | 0.978692E+09 | 0.333503E+10 | 0.434788E+09 |
Minimum of Months | 0.123363E+09 | 46596465.64 | 69690163.67 | 0.225202E+09 | 25329975.21 |
Maximum of Months | 0.186227E+09 | 0.109254E+09 | 95851218.54 | 0.346402E+09 | 51030732.15 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139167E+09 | 66711853.24 | 72454853.33 | 0.254840E+09 | 49181882.51 |
February | 0.144797E+09 | 75106376.30 | 69690163.67 | 0.268481E+09 | 44906585.33 |
March | 0.186227E+09 | 0.109254E+09 | 76972999.00 | 0.346402E+09 | 41402357.74 |
April | 0.182089E+09 | 0.101951E+09 | 80138586.32 | 0.340506E+09 | 29399851.22 |
May | 0.157606E+09 | 68504884.84 | 89100783.41 | 0.297797E+09 | 26785788.33 |
June | 0.164917E+09 | 81611812.55 | 83305408.05 | 0.311094E+09 | 25329975.21 |
July | 0.143399E+09 | 47548118.69 | 95851218.54 | 0.267076E+09 | 32952608.58 |
August | 0.158337E+09 | 67955551.24 | 90381266.57 | 0.284026E+09 | 31809546.24 |
September | 0.141696E+09 | 55068414.89 | 86627624.19 | 0.263988E+09 | 29790820.96 |
October | 0.133890E+09 | 47526586.69 | 86362925.35 | 0.239832E+09 | 33625872.69 |
November | 0.123363E+09 | 46596465.64 | 76766434.06 | 0.225202E+09 | 38572035.57 |
December | 0.128964E+09 | 57924158.47 | 71039831.93 | 0.235786E+09 | 51030732.15 |
Annual Sum or Average | 0.180445E+10 | 0.825759E+09 | 0.978692E+09 | 0.333503E+10 | 0.434788E+09 |
Minimum of Months | 0.123363E+09 | 46596465.64 | 69690163.67 | 0.225202E+09 | 25329975.21 |
Maximum of Months | 0.186227E+09 | 0.109254E+09 | 95851218.54 | 0.346402E+09 | 51030732.15 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139167E+09 | 66711853.24 | 72454853.33 | 0.254840E+09 | 49181882.51 |
February | 0.144797E+09 | 75106376.30 | 69690163.67 | 0.268481E+09 | 44906585.33 |
March | 0.186227E+09 | 0.109254E+09 | 76972999.00 | 0.346402E+09 | 41402357.74 |
April | 0.182089E+09 | 0.101951E+09 | 80138586.32 | 0.340506E+09 | 29399851.22 |
May | 0.157606E+09 | 68504884.84 | 89100783.41 | 0.297797E+09 | 26785788.33 |
June | 0.164917E+09 | 81611812.55 | 83305408.05 | 0.311094E+09 | 25329975.21 |
July | 0.143399E+09 | 47548118.69 | 95851218.54 | 0.267076E+09 | 32952608.58 |
August | 0.158337E+09 | 67955551.24 | 90381266.57 | 0.284026E+09 | 31809546.24 |
September | 0.141696E+09 | 55068414.89 | 86627624.19 | 0.263988E+09 | 29790820.96 |
October | 0.133890E+09 | 47526586.69 | 86362925.35 | 0.239832E+09 | 33625872.69 |
November | 0.123363E+09 | 46596465.64 | 76766434.06 | 0.225202E+09 | 38572035.57 |
December | 0.128964E+09 | 57924158.47 | 71039831.93 | 0.235786E+09 | 51030732.15 |
Annual Sum or Average | 0.180445E+10 | 0.825759E+09 | 0.978692E+09 | 0.333503E+10 | 0.434788E+09 |
Minimum of Months | 0.123363E+09 | 46596465.64 | 69690163.67 | 0.225202E+09 | 25329975.21 |
Maximum of Months | 0.186227E+09 | 0.109254E+09 | 95851218.54 | 0.346402E+09 | 51030732.15 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139167E+09 | 66711853.24 | 72454853.33 | 0.254840E+09 | 49181882.51 |
February | 0.144797E+09 | 75106376.30 | 69690163.67 | 0.268481E+09 | 44906585.33 |
March | 0.186227E+09 | 0.109254E+09 | 76972999.00 | 0.346402E+09 | 41402357.74 |
April | 0.182089E+09 | 0.101951E+09 | 80138586.32 | 0.340506E+09 | 29399851.22 |
May | 0.157606E+09 | 68504884.84 | 89100783.41 | 0.297797E+09 | 26785788.33 |
June | 0.164917E+09 | 81611812.55 | 83305408.05 | 0.311094E+09 | 25329975.21 |
July | 0.143399E+09 | 47548118.69 | 95851218.54 | 0.267076E+09 | 32952608.58 |
August | 0.158337E+09 | 67955551.24 | 90381266.57 | 0.284026E+09 | 31809546.24 |
September | 0.141696E+09 | 55068414.89 | 86627624.19 | 0.263988E+09 | 29790820.96 |
October | 0.133890E+09 | 47526586.69 | 86362925.35 | 0.239832E+09 | 33625872.69 |
November | 0.123363E+09 | 46596465.64 | 76766434.06 | 0.225202E+09 | 38572035.57 |
December | 0.128964E+09 | 57924158.47 | 71039831.93 | 0.235786E+09 | 51030732.15 |
Annual Sum or Average | 0.180445E+10 | 0.825759E+09 | 0.978692E+09 | 0.333503E+10 | 0.434788E+09 |
Minimum of Months | 0.123363E+09 | 46596465.64 | 69690163.67 | 0.225202E+09 | 25329975.21 |
Maximum of Months | 0.186227E+09 | 0.109254E+09 | 95851218.54 | 0.346402E+09 | 51030732.15 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139167E+09 | 66711853.24 | 72454853.33 | 0.254840E+09 | 49181882.51 |
February | 0.144797E+09 | 75106376.30 | 69690163.67 | 0.268481E+09 | 44906585.33 |
March | 0.186227E+09 | 0.109254E+09 | 76972999.00 | 0.346402E+09 | 41402357.74 |
April | 0.182089E+09 | 0.101951E+09 | 80138586.32 | 0.340506E+09 | 29399851.22 |
May | 0.157606E+09 | 68504884.84 | 89100783.41 | 0.297797E+09 | 26785788.33 |
June | 0.164917E+09 | 81611812.55 | 83305408.05 | 0.311094E+09 | 25329975.21 |
July | 0.143399E+09 | 47548118.69 | 95851218.54 | 0.267076E+09 | 32952608.58 |
August | 0.158337E+09 | 67955551.24 | 90381266.57 | 0.284026E+09 | 31809546.24 |
September | 0.141696E+09 | 55068414.89 | 86627624.19 | 0.263988E+09 | 29790820.96 |
October | 0.133890E+09 | 47526586.69 | 86362925.35 | 0.239832E+09 | 33625872.69 |
November | 0.123363E+09 | 46596465.64 | 76766434.06 | 0.225202E+09 | 38572035.57 |
December | 0.128964E+09 | 57924158.47 | 71039831.93 | 0.235786E+09 | 51030732.15 |
Annual Sum or Average | 0.180445E+10 | 0.825759E+09 | 0.978692E+09 | 0.333503E+10 | 0.434788E+09 |
Minimum of Months | 0.123363E+09 | 46596465.64 | 69690163.67 | 0.225202E+09 | 25329975.21 |
Maximum of Months | 0.186227E+09 | 0.109254E+09 | 95851218.54 | 0.346402E+09 | 51030732.15 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139167E+09 | 66711853.24 | 72454853.33 | 0.254840E+09 | 49181882.51 |
February | 0.144797E+09 | 75106376.30 | 69690163.67 | 0.268481E+09 | 44906585.33 |
March | 0.186227E+09 | 0.109254E+09 | 76972999.00 | 0.346402E+09 | 41402357.74 |
April | 0.182089E+09 | 0.101951E+09 | 80138586.32 | 0.340506E+09 | 29399851.22 |
May | 0.157606E+09 | 68504884.84 | 89100783.41 | 0.297797E+09 | 26785788.33 |
June | 0.164917E+09 | 81611812.55 | 83305408.05 | 0.311094E+09 | 25329975.21 |
July | 0.143399E+09 | 47548118.69 | 95851218.54 | 0.267076E+09 | 32952608.58 |
August | 0.158337E+09 | 67955551.24 | 90381266.57 | 0.284026E+09 | 31809546.24 |
September | 0.141696E+09 | 55068414.89 | 86627624.19 | 0.263988E+09 | 29790820.96 |
October | 0.133890E+09 | 47526586.69 | 86362925.35 | 0.239832E+09 | 33625872.69 |
November | 0.123363E+09 | 46596465.64 | 76766434.06 | 0.225202E+09 | 38572035.57 |
December | 0.128964E+09 | 57924158.47 | 71039831.93 | 0.235786E+09 | 51030732.15 |
Annual Sum or Average | 0.180445E+10 | 0.825759E+09 | 0.978692E+09 | 0.333503E+10 | 0.434788E+09 |
Minimum of Months | 0.123363E+09 | 46596465.64 | 69690163.67 | 0.225202E+09 | 25329975.21 |
Maximum of Months | 0.186227E+09 | 0.109254E+09 | 95851218.54 | 0.346402E+09 | 51030732.15 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139167E+09 | 66711853.24 | 72454853.33 | 0.254840E+09 | 49181882.51 |
February | 0.144797E+09 | 75106376.30 | 69690163.67 | 0.268481E+09 | 44906585.33 |
March | 0.186227E+09 | 0.109254E+09 | 76972999.00 | 0.346402E+09 | 41402357.74 |
April | 0.182089E+09 | 0.101951E+09 | 80138586.32 | 0.340506E+09 | 29399851.22 |
May | 0.157606E+09 | 68504884.84 | 89100783.41 | 0.297797E+09 | 26785788.33 |
June | 0.164917E+09 | 81611812.55 | 83305408.05 | 0.311094E+09 | 25329975.21 |
July | 0.143399E+09 | 47548118.69 | 95851218.54 | 0.267076E+09 | 32952608.58 |
August | 0.158337E+09 | 67955551.24 | 90381266.57 | 0.284026E+09 | 31809546.24 |
September | 0.141696E+09 | 55068414.89 | 86627624.19 | 0.263988E+09 | 29790820.96 |
October | 0.133890E+09 | 47526586.69 | 86362925.35 | 0.239832E+09 | 33625872.69 |
November | 0.123363E+09 | 46596465.64 | 76766434.06 | 0.225202E+09 | 38572035.57 |
December | 0.128964E+09 | 57924158.47 | 71039831.93 | 0.235786E+09 | 51030732.15 |
Annual Sum or Average | 0.180445E+10 | 0.825759E+09 | 0.978692E+09 | 0.333503E+10 | 0.434788E+09 |
Minimum of Months | 0.123363E+09 | 46596465.64 | 69690163.67 | 0.225202E+09 | 25329975.21 |
Maximum of Months | 0.186227E+09 | 0.109254E+09 | 95851218.54 | 0.346402E+09 | 51030732.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378405E+09 | 0.104564E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396369E+09 | 98185461.29 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509203E+09 | 93893933.21 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497507E+09 | 72651628.20 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428036E+09 | 70548316.60 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450186E+09 | 65648735.78 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.393871E+09 | 76747086.83 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.414840E+09 | 73817526.99 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387514E+09 | 71583319.98 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.350911E+09 | 79958164.13 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332349E+09 | 85156375.03 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350256E+09 | 0.105638E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.488945E+10 | 0.998393E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332349E+09 | 65648735.78 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509203E+09 | 0.105638E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 403.09 | 103.48 | 214.83 | 58.46 | 156.37 | 0.00 | 0.00 |
February | 454.27 | 88.08 | 233.92 | 64.18 | 169.74 | 0.00 | 0.00 |
March | 514.99 | 72.05 | 257.39 | 80.42 | 176.97 | 0.00 | 0.00 |
April | 529.79 | 46.11 | 263.48 | 79.10 | 184.39 | 0.00 | 0.00 |
May | 517.41 | 47.83 | 249.29 | 59.71 | 189.57 | 0.00 | 0.00 |
June | 576.94 | 50.36 | 279.91 | 83.13 | 196.79 | 0.00 | 0.00 |
July | 460.36 | 69.50 | 239.46 | 45.94 | 193.52 | 0.00 | 0.00 |
August | 457.09 | 62.93 | 240.35 | 55.04 | 185.31 | 0.00 | 0.00 |
September | 424.74 | 62.67 | 218.89 | 45.28 | 173.61 | 0.00 | 0.00 |
October | 381.30 | 73.55 | 206.98 | 39.57 | 167.41 | 0.00 | 0.00 |
November | 371.83 | 81.59 | 200.08 | 40.64 | 159.45 | 0.00 | 0.00 |
December | 375.86 | 110.23 | 201.23 | 50.22 | 151.02 | 0.00 | 0.00 |
Annual Sum or Average | 455.43 | 72.37 | 233.74 | 58.39 | 175.36 | 0.00 | 0.00 |
Minimum of Months | 371.83 | 46.11 | 200.08 | 39.57 | 151.02 | 0.00 | 0.00 |
Maximum of Months | 576.94 | 110.23 | 279.91 | 83.13 | 196.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1332.05 | 257.07 | 727.42 | 348.70 | 378.72 | 0.00 | 0.00 |
February | 1553.71 | 259.88 | 837.94 | 434.64 | 403.30 | 0.00 | 0.00 |
March | 1810.64 | 216.41 | 973.41 | 571.07 | 402.34 | 0.00 | 0.00 |
April | 1839.15 | 158.80 | 983.51 | 550.66 | 432.85 | 0.00 | 0.00 |
May | 1556.59 | 140.01 | 823.81 | 358.08 | 465.73 | 0.00 | 0.00 |
June | 1680.29 | 136.81 | 890.76 | 440.80 | 449.95 | 0.00 | 0.00 |
July | 1396.00 | 172.24 | 749.55 | 248.53 | 501.01 | 0.00 | 0.00 |
August | 1484.61 | 166.27 | 827.63 | 355.20 | 472.42 | 0.00 | 0.00 |
September | 1425.86 | 160.91 | 765.33 | 297.44 | 467.90 | 0.00 | 0.00 |
October | 1253.60 | 175.76 | 699.84 | 248.42 | 451.42 | 0.00 | 0.00 |
November | 1216.37 | 208.34 | 666.31 | 251.68 | 414.63 | 0.00 | 0.00 |
December | 1232.45 | 266.74 | 674.09 | 302.77 | 371.33 | 0.00 | 0.00 |
Annual Sum or Average | 1480.54 | 193.02 | 801.06 | 366.58 | 434.48 | 0.00 | 0.00 |
Minimum of Months | 1216.37 | 136.81 | 666.31 | 248.42 | 371.33 | 0.00 | 0.00 |
Maximum of Months | 1839.15 | 266.74 | 983.51 | 571.07 | 501.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 24723.05 | 6053.48 | 3256.85 | 1557.85 | 1699.00 | 0.00 | 0.00 |
February | 30758.03 | 7319.22 | 3747.86 | 1938.60 | 1809.26 | 0.00 | 0.00 |
March | 34229.96 | 6793.73 | 4349.68 | 2544.73 | 1804.95 | 0.00 | 0.00 |
April | 35581.02 | 5860.74 | 4396.21 | 2454.40 | 1941.82 | 0.00 | 0.00 |
May | 34088.71 | 5402.40 | 3685.73 | 1596.40 | 2089.33 | 0.00 | 0.00 |
June | 36291.70 | 5534.64 | 3983.63 | 1965.08 | 2018.55 | 0.00 | 0.00 |
July | 27743.40 | 5522.19 | 3355.77 | 1108.14 | 2247.63 | 0.00 | 0.00 |
August | 30658.13 | 5037.46 | 3702.89 | 1583.53 | 2119.36 | 0.00 | 0.00 |
September | 28528.04 | 5263.33 | 3425.04 | 1325.98 | 2099.05 | 0.00 | 0.00 |
October | 23126.41 | 5100.00 | 3133.04 | 1107.91 | 2025.13 | 0.00 | 0.00 |
November | 23902.66 | 5222.27 | 2984.12 | 1124.01 | 1860.11 | 0.00 | 0.00 |
December | 22642.60 | 5593.13 | 3019.59 | 1353.77 | 1665.82 | 0.00 | 0.00 |
Annual Sum or Average | 29325.77 | 5714.91 | 3584.17 | 1635.03 | 1949.13 | 0.00 | 0.00 |
Minimum of Months | 22642.60 | 5037.46 | 2984.12 | 1107.91 | 1665.82 | 0.00 | 0.00 |
Maximum of Months | 36291.70 | 7319.22 | 4396.21 | 2544.73 | 2247.63 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.107962E+10 | 0.277156E+09 | 0.575387E+09 | 0.156569E+09 | 0.418818E+09 | 0.00 | 0.00 |
February | 0.109897E+10 | 0.213094E+09 | 0.565902E+09 | 0.155267E+09 | 0.410635E+09 | 0.00 | 0.00 |
March | 0.137936E+10 | 0.192979E+09 | 0.689394E+09 | 0.215387E+09 | 0.474007E+09 | 0.00 | 0.00 |
April | 0.137321E+10 | 0.119515E+09 | 0.682952E+09 | 0.205017E+09 | 0.477934E+09 | 0.00 | 0.00 |
May | 0.138584E+10 | 0.128116E+09 | 0.667687E+09 | 0.159935E+09 | 0.507753E+09 | 0.00 | 0.00 |
June | 0.149542E+10 | 0.130543E+09 | 0.725535E+09 | 0.215466E+09 | 0.510068E+09 | 0.00 | 0.00 |
July | 0.123302E+10 | 0.186162E+09 | 0.641371E+09 | 0.123057E+09 | 0.518314E+09 | 0.00 | 0.00 |
August | 0.122427E+10 | 0.168548E+09 | 0.643751E+09 | 0.147408E+09 | 0.496343E+09 | 0.00 | 0.00 |
September | 0.110092E+10 | 0.162447E+09 | 0.567369E+09 | 0.117364E+09 | 0.450005E+09 | 0.00 | 0.00 |
October | 0.102128E+10 | 0.196994E+09 | 0.554376E+09 | 0.105981E+09 | 0.448396E+09 | 0.00 | 0.00 |
November | 0.963794E+09 | 0.211485E+09 | 0.518620E+09 | 0.105331E+09 | 0.413289E+09 | 0.00 | 0.00 |
December | 0.100670E+10 | 0.295235E+09 | 0.538988E+09 | 0.134508E+09 | 0.404480E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.143624E+11 | 0.228227E+10 | 0.737133E+10 | 0.184129E+10 | 0.553004E+10 | 0.00 | 0.00 |
Minimum of Months | 0.963794E+09 | 0.119515E+09 | 0.518620E+09 | 0.105331E+09 | 0.404480E+09 | 0.00 | 0.00 |
Maximum of Months | 0.149542E+10 | 0.295235E+09 | 0.725535E+09 | 0.215466E+09 | 0.518314E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.356776E+10 | 0.688546E+09 | 0.194833E+10 | 0.933966E+09 | 0.101437E+10 | 0.00 | 0.00 |
February | 0.375873E+10 | 0.628692E+09 | 0.202715E+10 | 0.105149E+10 | 0.975662E+09 | 0.00 | 0.00 |
March | 0.484962E+10 | 0.579633E+09 | 0.260717E+10 | 0.152955E+10 | 0.107762E+10 | 0.00 | 0.00 |
April | 0.476709E+10 | 0.411598E+09 | 0.254925E+10 | 0.142731E+10 | 0.112194E+10 | 0.00 | 0.00 |
May | 0.416916E+10 | 0.375001E+09 | 0.220648E+10 | 0.959068E+09 | 0.124741E+10 | 0.00 | 0.00 |
June | 0.435531E+10 | 0.354620E+09 | 0.230884E+10 | 0.114257E+10 | 0.116628E+10 | 0.00 | 0.00 |
July | 0.373906E+10 | 0.461337E+09 | 0.200759E+10 | 0.665674E+09 | 0.134192E+10 | 0.00 | 0.00 |
August | 0.397637E+10 | 0.445334E+09 | 0.221672E+10 | 0.951378E+09 | 0.126534E+10 | 0.00 | 0.00 |
September | 0.369583E+10 | 0.417071E+09 | 0.198374E+10 | 0.770958E+09 | 0.121279E+10 | 0.00 | 0.00 |
October | 0.335764E+10 | 0.470762E+09 | 0.187445E+10 | 0.665372E+09 | 0.120908E+10 | 0.00 | 0.00 |
November | 0.315283E+10 | 0.540008E+09 | 0.172708E+10 | 0.652351E+09 | 0.107473E+10 | 0.00 | 0.00 |
December | 0.330100E+10 | 0.714430E+09 | 0.180550E+10 | 0.810938E+09 | 0.994558E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.466904E+11 | 0.608703E+10 | 0.252623E+11 | 0.115606E+11 | 0.137017E+11 | 0.00 | 0.00 |
Minimum of Months | 0.315283E+10 | 0.354620E+09 | 0.172708E+10 | 0.652351E+09 | 0.975662E+09 | 0.00 | 0.00 |
Maximum of Months | 0.484962E+10 | 0.714430E+09 | 0.260717E+10 | 0.152955E+10 | 0.134192E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.662182E+11 | 0.162136E+11 | 0.872315E+10 | 0.417254E+10 | 0.455061E+10 | 0.00 | 0.00 |
February | 0.744098E+11 | 0.177067E+11 | 0.906683E+10 | 0.468986E+10 | 0.437697E+10 | 0.00 | 0.00 |
March | 0.916815E+11 | 0.181963E+11 | 0.116502E+11 | 0.681580E+10 | 0.483438E+10 | 0.00 | 0.00 |
April | 0.922260E+11 | 0.151910E+11 | 0.113950E+11 | 0.636179E+10 | 0.503319E+10 | 0.00 | 0.00 |
May | 0.913032E+11 | 0.144698E+11 | 0.987187E+10 | 0.427579E+10 | 0.559607E+10 | 0.00 | 0.00 |
June | 0.940681E+11 | 0.143458E+11 | 0.103256E+11 | 0.509349E+10 | 0.523209E+10 | 0.00 | 0.00 |
July | 0.743079E+11 | 0.147906E+11 | 0.898809E+10 | 0.296805E+10 | 0.602004E+10 | 0.00 | 0.00 |
August | 0.821147E+11 | 0.134923E+11 | 0.991783E+10 | 0.424133E+10 | 0.567650E+10 | 0.00 | 0.00 |
September | 0.739447E+11 | 0.136426E+11 | 0.887769E+10 | 0.343695E+10 | 0.544074E+10 | 0.00 | 0.00 |
October | 0.619418E+11 | 0.136598E+11 | 0.839154E+10 | 0.296742E+10 | 0.542412E+10 | 0.00 | 0.00 |
November | 0.619557E+11 | 0.135361E+11 | 0.773484E+10 | 0.291344E+10 | 0.482140E+10 | 0.00 | 0.00 |
December | 0.606459E+11 | 0.149806E+11 | 0.808767E+10 | 0.362593E+10 | 0.446174E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.924818E+12 | 0.180225E+12 | 0.113030E+12 | 0.515624E+11 | 0.614679E+11 | 0.00 | 0.00 |
Minimum of Months | 0.606459E+11 | 0.134923E+11 | 0.773484E+10 | 0.291344E+10 | 0.437697E+10 | 0.00 | 0.00 |
Maximum of Months | 0.940681E+11 | 0.181963E+11 | 0.116502E+11 | 0.681580E+10 | 0.602004E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 26.42 | 22.38 | 20.70 | 2.25 | 18.66 | 103.85 | 146.57 | 0.01 |
February | 27.50 | 22.91 | 21.01 | 2.37 | 18.54 | 110.59 | 164.59 | 0.00 |
March | 28.33 | 23.63 | 21.77 | 3.67 | 19.85 | 110.33 | 194.39 | 0.01 |
April | 29.15 | 25.37 | 24.04 | 2.98 | 21.51 | 118.69 | 185.56 | 0.03 |
May | 29.01 | 26.53 | 25.72 | 3.19 | 23.00 | 127.71 | 124.87 | 0.08 |
June | 28.86 | 26.50 | 25.74 | 3.10 | 22.78 | 123.38 | 156.09 | 0.05 |
July | 27.25 | 24.29 | 23.20 | 2.32 | 21.53 | 137.39 | 88.28 | 0.02 |
August | 27.54 | 25.86 | 25.31 | 3.22 | 21.55 | 129.55 | 122.00 | 0.07 |
September | 27.58 | 25.59 | 24.93 | 2.22 | 22.01 | 128.30 | 103.37 | 0.04 |
October | 26.89 | 25.07 | 24.46 | 2.18 | 21.39 | 123.79 | 92.41 | 0.11 |
November | 26.68 | 24.14 | 23.20 | 1.94 | 20.29 | 113.70 | 103.30 | 0.02 |
December | 25.97 | 22.85 | 21.57 | 2.00 | 18.63 | 101.83 | 131.96 | 0.00 |
Annual Sum or Average | 27.59 | 24.60 | 23.48 | 2.62 | 20.82 | 119.14 | 134.17 | 0.04 |
Minimum of Months | 25.97 | 22.38 | 20.70 | 1.94 | 18.54 | 101.83 | 88.28 | 0.00 |
Maximum of Months | 29.15 | 26.53 | 25.74 | 3.67 | 23.00 | 137.39 | 194.39 | 0.11 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 34.10 | 04-JAN-12:00 | 23.67 | 19.40 | 5.00 | 24.66 | 266.50 | 576.50 |
February | 35.00 | 21-FEB-13:00 | 22.02 | 16.00 | 2.10 | 24.16 | 230.00 | 672.50 |
March | 36.40 | 21-MAR-12:00 | 23.01 | 17.00 | 5.00 | 26.97 | 269.50 | 658.50 |
April | 35.50 | 01-APR-13:00 | 26.96 | 24.00 | 2.50 | 27.14 | 295.50 | 519.50 |
May | 37.60 | 06-MAY-12:00 | 26.43 | 22.60 | 4.00 | 29.39 | 317.00 | 525.50 |
June | 36.00 | 12-JUN-14:00 | 27.60 | 25.00 | 4.00 | 28.43 | 235.00 | 472.00 |
July | 33.20 | 15-JUL-15:00 | 25.63 | 23.00 | 2.00 | 27.95 | 219.00 | 181.00 |
August | 34.00 | 10-AUG-13:00 | 27.86 | 26.00 | 5.00 | 26.65 | 344.50 | 278.50 |
September | 34.00 | 06-SEP-13:00 | 26.51 | 24.00 | 4.00 | 25.00 | 258.00 | 581.50 |
October | 33.00 | 04-OCT-13:00 | 26.23 | 24.00 | 4.00 | 25.16 | 303.00 | 428.50 |
November | 34.30 | 18-NOV-12:00 | 25.34 | 22.20 | 3.00 | 25.49 | 289.50 | 511.50 |
December | 33.00 | 07-DEC-13:00 | 23.23 | 19.00 | 3.00 | 22.98 | 215.00 | 596.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 33.00 | 22.02 | 16.00 | 2.00 | 22.98 | 215.00 | 181.00 | |
Maximum of Months | 37.60 | 27.86 | 26.00 | 5.00 | 29.39 | 344.50 | 672.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 18.70 | 23-JAN-05:00 | 16.92 | 16.00 | 2.00 | 7.75 | 0.00 | 0.00 |
February | 20.30 | 21-FEB-09:00 | 19.04 | 18.40 | 2.00 | 10.50 | 258.50 | 564.00 |
March | 22.00 | 03-MAR-05:00 | 19.94 | 19.00 | 3.00 | 13.35 | 0.00 | 0.00 |
April | 22.90 | 14-APR-15:00 | 22.90 | 22.90 | 3.00 | 14.65 | 199.50 | 264.50 |
May | 22.00 | 10-MAY-19:00 | 22.00 | 22.00 | 2.00 | 18.28 | 0.00 | 0.00 |
June | 23.00 | 20-JUN-23:00 | 23.00 | 23.00 | 2.00 | 19.35 | 0.00 | 0.00 |
July | 23.00 | 13-JUL-04:00 | 22.27 | 22.00 | 0.00 | 13.91 | 0.00 | 0.00 |
August | 22.00 | 20-AUG-10:00 | 22.00 | 22.00 | 5.00 | 18.28 | 430.50 | 41.50 |
September | 22.90 | 19-SEP-03:00 | 22.78 | 22.78 | 0.00 | 21.27 | 0.00 | 0.00 |
October | 22.50 | 23-OCT-04:00 | 22.50 | 22.50 | 2.80 | 18.82 | 0.00 | 0.00 |
November | 20.00 | 25-NOV-04:00 | 18.63 | 18.00 | 2.00 | 10.69 | 0.00 | 0.00 |
December | 18.00 | 21-DEC-04:00 | 17.36 | 17.00 | 3.00 | 9.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.00 | 16.92 | 16.00 | 0.00 | 7.75 | 0.00 | 0.00 | |
Maximum of Months | 23.00 | 23.00 | 23.00 | 5.00 | 21.27 | 430.50 | 564.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 25.53 | 12-JAN-12:00 | 32.40 | 23.10 | 2.00 | 25.00 | 353.00 | 347.00 |
February | 26.17 | 14-FEB-15:00 | 32.30 | 24.20 | 2.00 | 25.16 | 200.00 | 199.00 |
March | 26.28 | 27-MAR-12:00 | 34.20 | 23.60 | 4.00 | 26.32 | 326.00 | 535.00 |
April | 27.93 | 10-APR-16:49 | 31.52 | 26.85 | 4.08 | 27.70 | 110.67 | 57.00 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 30.11 | 15-JUN-09:00 | 33.20 | 29.20 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.43 | 20-JUL-14:00 | 32.80 | 24.20 | 1.00 | 26.65 | 305.00 | 253.00 |
August | 28.81 | 14-AUG-16:00 | 32.00 | 28.00 | 1.00 | 25.16 | 107.50 | 223.00 |
September | 30.06 | 30-SEP-10:00 | 32.80 | 29.40 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 27.36 | 16-OCT-14:00 | 31.50 | 26.00 | 3.00 | 24.16 | 239.00 | 346.50 |
November | 27.56 | 10-NOV-12:00 | 31.00 | 26.40 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.86 | 03-DEC-12:00 | 31.50 | 25.30 | 1.00 | 23.49 | 301.00 | 468.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 25.53 | 29.00 | 23.10 | 1.00 | 22.47 | 0.00 | 0.00 | |
Maximum of Months | 30.11 | 34.20 | 29.40 | 6.00 | 28.11 | 398.00 | 535.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.20 | 09-JAN-21:00 | 26.50 | 24.77 | 4.00 | 25.16 | 0.00 | 0.00 |
February | 24.40 | 15-FEB-18:00 | 28.30 | 25.33 | 4.00 | 20.75 | 0.00 | 0.00 |
March | 25.30 | 28-MAR-06:00 | 27.20 | 25.72 | 3.00 | 19.87 | 103.00 | 28.00 |
April | 27.00 | 10-APR-17:00 | 30.50 | 27.87 | 4.50 | 25.00 | 20.00 | 20.50 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 29.20 | 15-JUN-09:00 | 33.20 | 30.11 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.00 | 10-JUL-14:00 | 26.50 | 26.11 | 2.30 | 23.49 | 286.00 | 36.50 |
August | 28.00 | 02-AUG-10:00 | 31.00 | 28.65 | 4.00 | 24.16 | 419.00 | 195.50 |
September | 29.40 | 30-SEP-10:00 | 32.80 | 30.06 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 26.50 | 16-OCT-08:00 | 29.00 | 27.04 | 2.50 | 21.78 | 300.00 | 326.00 |
November | 26.40 | 10-NOV-12:00 | 31.00 | 27.56 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.00 | 10-DEC-17:00 | 29.00 | 26.74 | 3.00 | 21.78 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.20 | 26.50 | 24.77 | 2.30 | 19.87 | 0.00 | 0.00 | |
Maximum of Months | 29.40 | 33.20 | 30.11 | 6.00 | 28.11 | 419.00 | 421.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 29.71 | 38.82 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 29.90 | 44.34 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 30.35 | 50.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 30.97 | 51.18 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.58 | 43.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 32.02 | 46.77 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 32.16 | 39.95 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 31.97 | 43.65 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 31.50 | 40.53 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.87 | 37.35 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 30.27 | 35.77 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 29.84 | 36.19 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 30.93 | 42.35 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 29.71 | 35.77 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 32.16 | 51.18 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.592704E+09 | -522980309.7 | 0.00 | 0.00 | 744.00 | 0.00 | -69723545.5 | 58.98 | 0.00 | 0.00 |
February | 0.540291E+09 | -477407410.7 | 0.00 | 0.00 | 672.00 | 0.00 | -62883918.3 | 58.99 | 0.00 | 0.00 |
March | 0.618929E+09 | -549158924.0 | 0.00 | 0.00 | 744.00 | 0.00 | -69769716.8 | 58.99 | 0.00 | 0.00 |
April | 0.566141E+09 | -499168364.3 | 0.00 | 0.00 | 720.00 | 0.00 | -66972572.6 | 58.98 | 0.00 | 0.00 |
May | 0.577008E+09 | -507779328.2 | 0.00 | 0.00 | 744.00 | 0.00 | -69228744.3 | 58.99 | 0.00 | 0.00 |
June | 0.565387E+09 | -498284054.2 | 0.00 | 0.00 | 720.00 | 0.00 | -67103029.3 | 58.98 | 0.00 | 0.00 |
July | 0.548364E+09 | -479121641.6 | 0.00 | 0.00 | 744.00 | 0.00 | -69242331.3 | 58.99 | 0.00 | 0.00 |
August | 0.588094E+09 | -518278044.3 | 0.00 | 0.00 | 744.00 | 0.00 | -69815913.4 | 58.98 | 0.00 | 0.00 |
September | 0.557347E+09 | -490098197.1 | 0.00 | 0.00 | 720.00 | 0.00 | -67248472.1 | 58.99 | 0.00 | 0.00 |
October | 0.571829E+09 | -502267440.6 | 0.00 | 0.00 | 744.00 | 0.00 | -69561743.8 | 58.99 | 0.00 | 0.00 |
November | 0.560130E+09 | -492725258.3 | 0.00 | 0.00 | 720.00 | 0.00 | -67404856.1 | 58.99 | 0.00 | 0.00 |
December | 0.590467E+09 | -520530751.7 | 0.00 | 0.00 | 744.00 | 0.00 | -69936647.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.687669E+10 | -0.605780E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -818891490.8 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.540291E+09 | -549158924.0 | 0.00 | 0.00 | 672.00 | 0.00 | -69936647.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.618929E+09 | -477407410.7 | 0.00 | 0.00 | 744.00 | 0.00 | -62883918.3 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.71 | 0.50 | 02-JAN-10:30 | 279.25 | 0.00 | 0.00 | 155.17 | 227.85 | 0.00 | 0.00 | 112.00 |
February | 321.17 | 0.70 | 0.50 | 01-FEB-10:30 | 300.31 | 0.00 | 0.00 | 153.33 | 246.87 | 0.00 | 0.00 | 115.00 |
March | 361.17 | 0.69 | 0.50 | 01-MAR-09:00 | 769.15 | 0.00 | 0.00 | 183.50 | 1354.28 | 0.00 | 0.00 | 129.67 |
April | 358.33 | 0.70 | 0.50 | 01-APR-10:20 | 781.59 | 0.00 | 0.00 | 187.50 | 228.16 | 0.00 | 0.00 | 103.00 |
May | 376.33 | 0.72 | 0.50 | 01-MAY-11:00 | 344.96 | 0.00 | 0.00 | 200.00 | 196.48 | 0.00 | 0.00 | 57.83 |
June | 370.50 | 0.73 | 0.50 | 01-JUN-10:00 | 336.38 | 0.00 | 0.00 | 195.17 | 181.50 | 0.00 | 0.00 | 27.00 |
July | 383.17 | 0.72 | 0.50 | 01-JUL-10:50 | 347.73 | 0.00 | 0.00 | 201.50 | 192.40 | 0.00 | 0.00 | 66.00 |
August | 369.33 | 0.70 | 0.50 | 01-AUG-10:00 | 417.35 | 0.00 | 0.00 | 204.00 | 223.55 | 0.00 | 0.00 | 105.50 |
September | 357.83 | 0.69 | 0.50 | 01-SEP-09:39 | 844.88 | 0.00 | 0.00 | 190.17 | 627.33 | 0.00 | 0.00 | 142.50 |
October | 356.83 | 0.69 | 0.50 | 01-OCT-09:50 | 342.30 | 0.00 | 0.00 | 185.00 | 593.30 | 0.00 | 0.00 | 146.50 |
November | 337.67 | 0.70 | 0.50 | 01-NOV-09:39 | 306.76 | 0.00 | 0.00 | 163.67 | 246.36 | 0.00 | 0.00 | 123.17 |
December | 349.33 | 0.71 | 0.50 | 01-DEC-09:39 | 652.25 | 0.00 | 0.00 | 164.00 | 221.81 | 0.00 | 0.00 | 106.17 |
Annual Sum or Average | 4292.33 | 0.71 | 477.59 | 0.00 | 0.00 | 2183.00 | 378.44 | 0.00 | 0.00 | 1234.33 | ||
Minimum of Months | 321.17 | 0.69 | 0.50 | 279.25 | 0.00 | 0.00 | 153.33 | 181.50 | 0.00 | 0.00 | 27.00 | |
Maximum of Months | 383.17 | 0.73 | 0.50 | 844.88 | 0.00 | 0.00 | 204.00 | 1354.28 | 0.00 | 0.00 | 146.50 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.62 | 0.50 | 01-JAN-08:30 | 314.32 | 14.19 | 0.00 | 242.83 | 266.15 | 17.73 | 88.33 | 205.83 |
February | 321.17 | 0.61 | 0.50 | 01-FEB-08:20 | 340.85 | 14.34 | 0.00 | 231.17 | 290.82 | 17.98 | 90.67 | 198.00 |
March | 361.17 | 0.60 | 0.50 | 01-MAR-08:09 | 1165.77 | 14.49 | 0.00 | 269.33 | 1986.33 | 19.79 | 104.00 | 228.33 |
April | 358.33 | 0.60 | 0.50 | 01-APR-07:40 | 363.05 | 14.73 | 0.00 | 268.50 | 310.69 | 18.53 | 105.67 | 228.50 |
May | 376.33 | 0.60 | 0.50 | 01-MAY-07:30 | 370.46 | 14.56 | 0.00 | 277.17 | 322.64 | 18.02 | 93.00 | 243.67 |
June | 370.50 | 0.60 | 0.50 | 01-JUN-07:49 | 1512.88 | 15.80 | 36.67 | 271.67 | 325.37 | 18.32 | 105.67 | 237.83 |
July | 383.17 | 0.61 | 0.50 | 01-JUL-07:30 | 371.96 | 14.32 | 0.00 | 275.83 | 329.20 | 17.62 | 92.17 | 242.17 |
August | 369.33 | 0.60 | 0.50 | 01-AUG-07:30 | 384.67 | 14.82 | 0.00 | 276.83 | 335.30 | 18.31 | 100.00 | 243.83 |
September | 357.83 | 0.60 | 0.50 | 01-SEP-07:30 | 370.78 | 14.32 | 0.00 | 259.67 | 340.15 | 19.06 | 111.33 | 239.17 |
October | 356.83 | 0.60 | 0.50 | 01-OCT-07:40 | 691.01 | 15.61 | 35.50 | 257.83 | 342.78 | 18.76 | 96.33 | 232.67 |
November | 337.67 | 0.61 | 0.50 | 01-NOV-07:49 | 341.31 | 14.64 | 0.00 | 239.33 | 290.58 | 18.08 | 87.50 | 207.83 |
December | 349.33 | 0.62 | 0.50 | 01-DEC-07:49 | 306.89 | 14.11 | 0.00 | 238.67 | 258.66 | 17.60 | 75.67 | 203.33 |
Annual Sum or Average | 4292.33 | 0.61 | 549.13 | 14.67 | 72.17 | 3108.83 | 451.95 | 18.32 | 1150.33 | 2711.17 | ||
Minimum of Months | 321.17 | 0.60 | 0.50 | 306.89 | 14.11 | 0.00 | 231.17 | 258.66 | 17.60 | 75.67 | 198.00 | |
Maximum of Months | 383.17 | 0.62 | 0.50 | 1512.88 | 15.80 | 36.67 | 277.17 | 1986.33 | 19.79 | 111.33 | 243.83 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.80 | 0.61 | 16-JAN-15:30 | 328.80 | 23.86 | 216.17 | 93.33 | 193.60 | 22.83 | 225.83 | 16.67 |
February | 321.17 | 0.78 | 0.61 | 01-FEB-16:10 | 364.69 | 23.95 | 191.83 | 102.67 | 258.33 | 24.45 | 220.83 | 50.17 |
March | 361.17 | 0.77 | 0.61 | 02-MAR-14:30 | 373.74 | 23.26 | 200.17 | 114.17 | 301.61 | 24.10 | 253.33 | 84.00 |
April | 358.33 | 0.77 | 0.61 | 01-APR-14:20 | 324.35 | 21.72 | 184.67 | 107.17 | 293.29 | 22.95 | 252.33 | 77.33 |
May | 376.33 | 0.78 | 0.61 | 01-MAY-14:20 | 317.78 | 20.73 | 155.67 | 121.00 | 235.67 | 22.06 | 214.17 | 56.50 |
June | 370.50 | 0.74 | 0.61 | 01-JUN-14:30 | 354.85 | 21.17 | 175.00 | 212.00 | 277.90 | 22.58 | 245.33 | 63.33 |
July | 383.17 | 0.79 | 0.61 | 02-JUL-16:10 | 304.15 | 20.23 | 129.33 | 100.67 | 220.18 | 21.56 | 186.67 | 37.67 |
August | 369.33 | 0.78 | 0.61 | 01-AUG-14:30 | 316.56 | 21.06 | 160.33 | 97.67 | 249.27 | 22.33 | 225.50 | 65.00 |
September | 357.83 | 0.81 | 0.61 | 02-SEP-14:20 | 277.53 | 20.65 | 149.17 | 63.50 | 209.50 | 22.64 | 212.50 | 39.17 |
October | 356.83 | 0.81 | 0.61 | 02-OCT-14:09 | 283.65 | 22.78 | 193.67 | 70.67 | 185.05 | 23.83 | 225.33 | 30.67 |
November | 337.67 | 0.81 | 0.61 | 02-NOV-14:30 | 280.27 | 23.38 | 202.67 | 73.00 | 168.33 | 22.97 | 212.50 | 10.83 |
December | 349.33 | 0.81 | 0.64 | 01-DEC-13:20 | 288.19 | 23.35 | 211.83 | 82.00 | 155.56 | 21.78 | 214.83 | 0.00 |
Annual Sum or Average | 4292.33 | 0.79 | 317.77 | 22.13 | 2170.50 | 1237.83 | 229.51 | 22.82 | 2689.17 | 531.33 | ||
Minimum of Months | 321.17 | 0.74 | 0.61 | 277.53 | 20.23 | 129.33 | 63.50 | 155.56 | 21.56 | 186.67 | 0.00 | |
Maximum of Months | 383.17 | 0.81 | 0.64 | 373.74 | 23.95 | 216.17 | 212.00 | 301.61 | 24.45 | 253.33 | 84.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.136796E+11 | 0.961227E+10 | 33703.58 | 02-JAN-06:01 | 16749.72 | 0.00 |
February | 0.00 | 0.00 | 0.131977E+11 | 0.936359E+10 | 33194.89 | 15-FEB-06:01 | 17557.48 | 0.00 |
March | 0.00 | 0.00 | 0.167698E+11 | 0.115556E+11 | 33384.82 | 25-MAR-05:01 | 16709.61 | 0.00 |
April | 0.00 | 0.00 | 0.171325E+11 | 0.110608E+11 | 33394.38 | 24-APR-05:01 | 17802.07 | 0.00 |
May | 0.00 | 0.00 | 0.192887E+11 | 0.115790E+11 | 33671.69 | 17-MAY-05:01 | 15097.81 | 0.00 |
June | 0.00 | 0.00 | 0.195465E+11 | 0.117726E+11 | 33703.58 | 21-JUN-05:01 | 16315.53 | 0.00 |
July | 0.00 | 0.00 | 0.154826E+11 | 0.100275E+11 | 33408.72 | 24-JUL-05:01 | 17570.77 | 0.00 |
August | 0.00 | 0.00 | 0.186874E+11 | 0.109198E+11 | 33671.69 | 21-AUG-05:01 | 15214.79 | 0.00 |
September | 0.00 | 0.00 | 0.166366E+11 | 0.100948E+11 | 33458.56 | 22-SEP-05:01 | 17159.62 | 0.00 |
October | 0.00 | 0.00 | 0.156853E+11 | 0.947187E+10 | 33703.58 | 23-OCT-05:02 | 15653.83 | 0.00 |
November | 0.00 | 0.00 | 0.144169E+11 | 0.922693E+10 | 33465.51 | 24-NOV-06:01 | 18054.55 | 0.00 |
December | 0.00 | 0.00 | 0.134234E+11 | 0.922676E+10 | 33703.58 | 11-DEC-06:01 | 16960.61 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.193947E+12 | 0.123911E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.131977E+11 | 0.922676E+10 | 33194.89 | 15097.81 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.195465E+11 | 0.117726E+11 | 33703.58 | 18054.55 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.352101E+11 | 0.239771E+11 | 95689.81 | 11-JAN-06:06 | 54119.00 | 0.00 |
February | 0.00 | 0.00 | 0.374417E+11 | 0.258238E+11 | 94239.80 | 16-FEB-06:05 | 55585.67 | 0.00 |
March | 0.00 | 0.00 | 0.492878E+11 | 0.328484E+11 | 96721.16 | 25-MAR-05:06 | 52269.89 | 0.00 |
April | 0.00 | 0.00 | 0.539241E+11 | 0.336425E+11 | 96813.43 | 01-APR-05:08 | 50754.54 | 0.00 |
May | 0.00 | 0.00 | 0.584165E+11 | 0.336719E+11 | 99158.85 | 04-MAY-05:07 | 47179.41 | 0.00 |
June | 0.00 | 0.00 | 0.607660E+11 | 0.351220E+11 | 97228.84 | 06-JUN-05:06 | 50742.74 | 0.00 |
July | 0.00 | 0.00 | 0.434001E+11 | 0.270990E+11 | 95012.15 | 14-JUL-05:01 | 55749.39 | 0.00 |
August | 0.00 | 0.00 | 0.487723E+11 | 0.266692E+11 | 102761.85 | 04-AUG-05:02 | 44446.41 | 0.00 |
September | 0.00 | 0.00 | 0.457555E+11 | 0.265216E+11 | 96836.96 | 01-SEP-05:08 | 51376.96 | 0.00 |
October | 0.00 | 0.00 | 0.396122E+11 | 0.227048E+11 | 99210.72 | 24-OCT-05:04 | 49444.57 | 0.00 |
November | 0.00 | 0.00 | 0.364545E+11 | 0.223751E+11 | 96222.47 | 30-NOV-06:06 | 53914.25 | 0.00 |
December | 0.00 | 0.00 | 0.333544E+11 | 0.219062E+11 | 95922.54 | 30-DEC-06:01 | 54646.73 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.542395E+12 | 0.332362E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.333544E+11 | 0.219062E+11 | 94239.80 | 44446.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.607660E+11 | 0.351220E+11 | 102761.85 | 55749.39 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.610907E+09 | 0.23 | 1367.55 | 02-JAN-06:01 | 0.89 |
February | 0.592543E+09 | 0.24 | 1367.55 | 01-FEB-06:01 | 0.89 |
March | 0.735369E+09 | 0.27 | 1367.55 | 01-MAR-06:01 | 0.89 |
April | 0.741813E+09 | 0.27 | 1367.55 | 01-APR-05:01 | 0.89 |
May | 0.832189E+09 | 0.28 | 1367.55 | 01-MAY-05:01 | 0.88 |
June | 0.847643E+09 | 0.29 | 1367.55 | 01-JUN-05:01 | 0.89 |
July | 0.658006E+09 | 0.24 | 1367.55 | 01-JUL-05:01 | 0.89 |
August | 0.782473E+09 | 0.27 | 1367.55 | 01-AUG-05:01 | 0.89 |
September | 0.700817E+09 | 0.26 | 1367.55 | 01-SEP-05:01 | 0.89 |
October | 0.655404E+09 | 0.24 | 1367.55 | 02-OCT-05:01 | 0.89 |
November | 0.611609E+09 | 0.23 | 1367.55 | 01-NOV-05:01 | 0.89 |
December | 0.598170E+09 | 0.23 | 1367.55 | 01-DEC-06:01 | 0.89 |
Annual Sum or Average | 0.836694E+10 | 0.26 | |||
Minimum of Months | 0.592543E+09 | 0.23 | 1367.55 | 0.88 | |
Maximum of Months | 0.847643E+09 | 0.29 | 1367.55 | 0.89 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.162081E+10 | 0.31 | 3396.19 | 08-JAN-13:32 | 0.87 |
February | 0.157306E+10 | 0.35 | 3396.19 | 05-FEB-10:33 | 0.87 |
March | 0.193895E+10 | 0.39 | 3396.19 | 01-MAR-06:01 | 0.86 |
April | 0.196701E+10 | 0.41 | 3396.19 | 01-APR-05:08 | 0.86 |
May | 0.208495E+10 | 0.41 | 3396.19 | 01-MAY-17:06 | 0.86 |
June | 0.213470E+10 | 0.43 | 3396.19 | 01-JUN-05:01 | 0.86 |
July | 0.179931E+10 | 0.38 | 3396.19 | 02-JUL-09:33 | 0.86 |
August | 0.187989E+10 | 0.36 | 3396.19 | 01-AUG-05:05 | 0.86 |
September | 0.179073E+10 | 0.38 | 3396.19 | 01-SEP-05:08 | 0.86 |
October | 0.169924E+10 | 0.34 | 3396.19 | 01-OCT-09:53 | 0.86 |
November | 0.159336E+10 | 0.33 | 3396.19 | 04-NOV-05:01 | 0.86 |
December | 0.159101E+10 | 0.30 | 3396.19 | 03-DEC-10:03 | 0.87 |
Annual Sum or Average | 0.216730E+11 | 0.37 | |||
Minimum of Months | 0.157306E+10 | 0.30 | 3396.19 | 0.86 | |
Maximum of Months | 0.213470E+10 | 0.43 | 3396.19 | 0.87 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.385739E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.376500E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.479192E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.486532E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.543777E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.552539E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.426832E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.512157E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.457814E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.426968E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.396112E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.375607E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.541977E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.375607E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.552539E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.112219E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.118293E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.154214E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.165681E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.177363E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.183511E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.134056E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.146708E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.139019E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.121542E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.113242E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.106263E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.167211E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.106263E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.183511E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.610907E+09 | 0.136796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.592543E+09 | 0.131977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.735369E+09 | 0.167698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.741813E+09 | 0.171325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.832189E+09 | 0.192887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.847643E+09 | 0.195465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.658006E+09 | 0.154826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.782473E+09 | 0.186874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.700817E+09 | 0.166366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.655404E+09 | 0.156853E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.611609E+09 | 0.144169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.598170E+09 | 0.134234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.836694E+10 | 0.193947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.592543E+09 | 0.131977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.847643E+09 | 0.195465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.162081E+10 | 0.352101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157306E+10 | 0.374417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193895E+10 | 0.492878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196701E+10 | 0.539241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.208495E+10 | 0.584165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.213470E+10 | 0.607660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.179931E+10 | 0.434001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.187989E+10 | 0.487723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.179073E+10 | 0.457555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169924E+10 | 0.396122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159336E+10 | 0.364545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159101E+10 | 0.333544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216730E+11 | 0.542395E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.157306E+10 | 0.333544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.213470E+10 | 0.607660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.610907E+09 | 0.00 | 0.00 | 0.00 | 0.324649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.592543E+09 | 0.00 | 0.00 | 0.00 | 0.317246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.735369E+09 | 0.00 | 0.00 | 0.00 | 0.405655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.741813E+09 | 0.00 | 0.00 | 0.00 | 0.412351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.832189E+09 | 0.00 | 0.00 | 0.00 | 0.460558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.847643E+09 | 0.00 | 0.00 | 0.00 | 0.467775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.658006E+09 | 0.00 | 0.00 | 0.00 | 0.361031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.782473E+09 | 0.00 | 0.00 | 0.00 | 0.433910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.700817E+09 | 0.00 | 0.00 | 0.00 | 0.387732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.655404E+09 | 0.00 | 0.00 | 0.00 | 0.361428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.611609E+09 | 0.00 | 0.00 | 0.00 | 0.334951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.598170E+09 | 0.00 | 0.00 | 0.00 | 0.315790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.836694E+10 | 0.00 | 0.00 | 0.00 | 0.458308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.592543E+09 | 0.00 | 0.00 | 0.00 | 0.315790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.847643E+09 | 0.00 | 0.00 | 0.00 | 0.467775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.162081E+10 | 0.00 | 0.00 | 0.00 | 0.960111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157306E+10 | 0.00 | 0.00 | 0.00 | 0.102563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193895E+10 | 0.00 | 0.00 | 0.00 | 0.134825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196701E+10 | 0.00 | 0.00 | 0.00 | 0.146011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.208495E+10 | 0.00 | 0.00 | 0.00 | 0.156513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.213470E+10 | 0.00 | 0.00 | 0.00 | 0.162163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.179931E+10 | 0.00 | 0.00 | 0.00 | 0.116063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.187989E+10 | 0.00 | 0.00 | 0.00 | 0.127909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.179073E+10 | 0.00 | 0.00 | 0.00 | 0.121112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169924E+10 | 0.00 | 0.00 | 0.00 | 0.104550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159336E+10 | 0.00 | 0.00 | 0.00 | 0.973080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159101E+10 | 0.00 | 0.00 | 0.00 | 0.903533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216730E+11 | 0.00 | 0.00 | 0.00 | 0.145538E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.157306E+10 | 0.00 | 0.00 | 0.00 | 0.903533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.213470E+10 | 0.00 | 0.00 | 0.00 | 0.162163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.217650E+10 | 0.00 | 1767796.60 | 0.00 | 0.00 | 1895740.51 | 0.00 | 0.14 |
February | 0.00 | 0.217709E+10 | 0.00 | 590794.12 | 0.00 | 0.00 | 58446.13 | 0.00 | 0.15 |
March | 0.00 | 0.284715E+10 | 0.00 | 431049.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
April | 0.00 | 0.335677E+10 | 0.00 | 29838.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
May | 0.00 | 0.404806E+10 | 0.00 | 156223.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
June | 0.00 | 0.419587E+10 | 0.00 | 79014.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
July | 0.00 | 0.288816E+10 | 0.00 | 77623.99 | 0.00 | 0.00 | 60959.46 | 0.00 | 0.15 |
August | 0.00 | 0.395326E+10 | 0.00 | 117989.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
September | 0.00 | 0.352394E+10 | 0.00 | 3690.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
October | 0.00 | 0.321348E+10 | 0.00 | 298432.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
November | 0.00 | 0.270409E+10 | 0.00 | 928342.60 | 0.00 | 0.00 | 68212.88 | 0.00 | 0.14 |
December | 0.00 | 0.229539E+10 | 0.00 | 1713173.19 | 0.00 | 0.00 | 445965.52 | 0.00 | 0.14 |
Annual Sum or Average | 0.00 | 0.373798E+11 | 0.00 | 6193968.93 | 0.00 | 0.00 | 2529324.51 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.217650E+10 | 0.00 | 3690.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.00 | 0.419587E+10 | 0.00 | 1767796.60 | 0.00 | 0.00 | 1895740.51 | 0.00 | 0.16 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 8936400.48 | 0.710746E+10 | 0.00 | 975102.50 | 7063498.31 | 0.00 | 86728959.78 | 0.00 | 0.22 |
February | 981160.36 | 0.793158E+10 | 0.00 | 397231.57 | 2948562.41 | 0.00 | 11949151.95 | 0.00 | 0.24 |
March | 119947.24 | 0.102670E+11 | 0.00 | 79754.34 | 7649530.96 | 0.00 | 2415630.05 | 0.00 | 0.26 |
April | 0.00 | 0.135759E+11 | 0.00 | 0.00 | 13850380.22 | 0.00 | 0.00 | 0.00 | 0.26 |
May | 0.00 | 0.162630E+11 | 0.00 | 0.00 | 13814212.10 | 0.00 | 0.00 | 0.00 | 0.26 |
June | 0.00 | 0.172448E+11 | 0.00 | 0.00 | 13121084.43 | 0.00 | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.106495E+11 | 0.00 | 0.00 | 16449621.59 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.139369E+11 | 0.00 | 12284.32 | 3773095.59 | 0.00 | 13444.98 | 0.00 | 0.25 |
September | 0.00 | 0.131706E+11 | 0.00 | 0.00 | 14368522.31 | 0.00 | 0.00 | 0.00 | 0.25 |
October | 0.00 | 0.109934E+11 | 0.00 | 16298.96 | 21219034.20 | 0.00 | 1120180.78 | 0.00 | 0.23 |
November | 0.00 | 0.942246E+10 | 0.00 | 146566.78 | 4852315.21 | 0.00 | 13471912.33 | 0.00 | 0.23 |
December | 9469877.01 | 0.739535E+10 | 0.00 | 626294.90 | 1706327.26 | 0.00 | 61558069.30 | 0.00 | 0.22 |
Annual Sum or Average | 19507385.10 | 0.137958E+12 | 0.00 | 2253533.36 | 0.120816E+09 | 0.00 | 0.177257E+09 | 0.00 | 0.24 |
Minimum of Months | 0.00 | 0.710746E+10 | 0.00 | 0.00 | 1706327.26 | 0.00 | 0.00 | 0.00 | 0.22 |
Maximum of Months | 9469877.01 | 0.172448E+11 | 0.00 | 975102.50 | 21219034.20 | 0.00 | 86728959.78 | 0.00 | 0.27 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:47
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.828919E+12 | 0.477503E+11 | 0.00 | -0.134884E+11 | 0.617372E+11 |
February | 0.827942E+12 | 0.509487E+11 | 0.00 | -0.151716E+11 | 0.640682E+11 |
March | 0.108622E+13 | 0.616762E+11 | 0.00 | -0.182795E+11 | 0.835966E+11 |
April | 0.107954E+13 | 0.616132E+11 | 0.00 | -0.244242E+11 | 0.897812E+11 |
May | 0.103929E+13 | 0.555072E+11 | 0.00 | -0.292655E+11 | 0.979622E+11 |
June | 0.106538E+13 | 0.671226E+11 | 0.00 | -0.296732E+11 | 0.101207E+12 |
July | 0.884651E+12 | 0.557601E+11 | 0.00 | -0.217354E+11 | 0.740993E+11 |
August | 0.112173E+13 | 0.477181E+11 | 0.00 | -0.252661E+11 | 0.845897E+11 |
September | 0.882915E+12 | 0.501239E+11 | 0.00 | -0.255456E+11 | 0.783806E+11 |
October | 0.946735E+12 | 0.448696E+11 | 0.00 | -0.228629E+11 | 0.693667E+11 |
November | 0.780812E+12 | 0.451558E+11 | 0.00 | -0.194499E+11 | 0.639517E+11 |
December | 0.777024E+12 | 0.466118E+11 | 0.00 | -0.144934E+11 | 0.589711E+11 |
Annual Sum or Average | 0.113212E+14 | 0.634857E+12 | 0.00 | -0.259656E+12 | 0.927711E+12 |
Minimum of Months | 0.777024E+12 | 0.448696E+11 | 0.00 | -0.296732E+11 | 0.589711E+11 |
Maximum of Months | 0.112173E+13 | 0.671226E+11 | 0.00 | -0.134884E+11 | 0.101207E+12 |