Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2023-10-16 10:41:44
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1485.28 | 307.18 | 307.18 |
Net Site Energy | 1485.28 | 307.18 | 307.18 |
Total Source Energy | 4703.86 | 972.85 | 972.85 |
Net Source Energy | 4703.86 | 972.85 | 972.85 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 352.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 134.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 213.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1485.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 352.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 134.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 40.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 172.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 22.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 352.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 134.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 213.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 22.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 121.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 307.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 121.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 307.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1485.273 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1485.273 | 100.00 |
Total On-Site and Utility Electric Sources | 1485.273 | 100.00 |
Total Electricity End Uses | 1485.273 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 72.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3308.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.61 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7186 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 15.0695 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 9.6875 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 11.2890 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 11.2890 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.7186 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 15.0695 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 9.6875 | 46.45 | 2.5587 | |
Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 11.2890 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:39 | 02-JAN-07:19 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:00 |
Heating | 0.00 | 1154.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 55271.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 40988.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 15036.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1570.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 122979.65 | 1154.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 1154.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 55271.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 40988.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 12731.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1570.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1115.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1974.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 425.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 674.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 71.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4703.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 230.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 139.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 972.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 230.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 139.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 972.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.65 |
ZONE2 FINE STORAGE DIRECT AIR | 6.35 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 1.05 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 1.05 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 42795.74 |
PSZ-OFFICE HEATING COIL | 38807.15 |
PSZ-FINE STORAGE HEATING COIL | 189109.54 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 42795.74 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.65 | 1.65 | 1.65 | 1.65 | 1.65 | 1.65 | 1.00 | 1.00 | 1.65 |
PSZ-FINE STORAGE | 6.35 | 6.35 | 6.35 | 6.35 | 6.35 | 6.35 | 1.00 | 1.00 | 6.35 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.65 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 6.35 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.65 | 1801.17 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 6.35 | 10929.98 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.65 | 1.65 | 1.65 | 1.65 | 34513.97 | 38807.15 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 6.35 | 6.35 | 6.35 | 6.35 | 157487.99 | 189109.54 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.65 | 0.822822 | 1.65 | 34513.97 | 17696.07 | 34513.97 | 0.758180 | 0.758180 |
PSZ-FINE STORAGE COOLING COIL | 6.35 | 3.17 | 6.35 | 157487.99 | 78820.59 | 157487.99 | 0.701320 | 0.701320 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.719 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.792 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 15.069 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15.069 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 9.688 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 12.246 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2539.013 | 10.719 | 199.158 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2539.013 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 20997.932 | 15.069 | 699.931 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20997.932 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 31046.942 | 9.688 | 449.956 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 31046.942 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 982.6 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.7823 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 3 | 0.167 | 7.732 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 3 | 0.167 | 7.732 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1000E-02 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.179 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.36859539E-11 | 0.84954153E-14 | 0.47616952E-16 | 0.0000000 |
5 | 1 | -5.1234640 | 0.46000535E-01 | -0.53498711E-03 | 0.47618904E-11 |
6 | 0 | 987.76235 | 982.59289 | 982.63942 | |
7 | 4 | 0.72249793E-12 | -0.16720573E-15 | 0.22015083E-14 | 0.12409536E-15 |
8 | 3 | -0.36459118E-03 | 0.53555631E-06 | -0.52695411E-04 | 0.13865996E-12 |
9 | 2 | 1.6915239 | 0.11971291E-01 | 1.1039557 | -0.69896550E-04 |
10 | 1 | -7.1930661 | 0.31446443 | -16.864389 | 0.32415671 |
11 | 0 | 6.0306730 | 0.20232993 | 16.289252 | |
12 | 3 | -0.11556429E-04 | 0.42115602E-06 | -0.11737956E-05 | 0.71542051E-15 |
13 | 2 | 0.42692330 | 0.53556778E-01 | 0.17992628 | -0.21068281E-05 |
14 | 1 | -10.558915 | 3.4986983 | -9.7344214 | 0.71768033E-01 |
15 | 0 | 17.309178 | 3.6249194 | 16.731671 | |
16 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
17 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
18 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
19 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
20 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
21 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
22 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
23 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
24 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
25 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
26 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
27 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
28 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
29 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
30 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
31 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
32 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
33 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
34 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
35 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
36 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
37 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
38 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
39 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
40 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
41 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
42 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
43 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
44 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
45 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
46 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
47 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
48 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
49 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
50 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
51 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
52 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
53 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
54 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
55 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
56 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
57 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
58 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
59 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
60 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
61 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
62 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
63 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
64 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
65 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
66 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
67 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
68 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
69 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
70 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
71 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
72 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
73 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
74 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
75 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
76 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
77 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
78 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
79 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
80 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
81 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
82 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
83 | 3 | -0.11737956E-05 | 0.42115602E-06 | -0.11556429E-04 | 0.71542051E-15 |
84 | 2 | 0.17992628 | 0.53556778E-01 | 0.42692330 | -0.21068281E-05 |
85 | 1 | -9.7344214 | 3.4986983 | -10.558915 | 0.71768033E-01 |
86 | 0 | 16.731671 | 3.6249194 | 17.309178 | |
87 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
88 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
89 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
90 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.2_SHGC_SOUTH_0.25 | 34 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
2 | NONRESWINDOW_U_1.2_SHGC_NORTH_0.25 | 35 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
3 | NONRESWINDOW_U_1.2_SHGC_EAST_0.25 | 36 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
4 | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
5 | SKYLIGHT_U_1.02_SHGC_0.36 | 38 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.361 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.19502 | 0.25365 | 0.25365 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.849 | 0.366 | 0.255 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 0.153 | 6.473E-004 | 9.992E-004 | 0.546 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.780 | 5.598E-004 | 3.565E-004 | 0.951 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 3.433 | 1.071E-003 | 6.996E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 16659.72736 | 19991.67283 | 1.37137 | 1.64564 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 42.31500 | 1.07810E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 5676.63118 | 6811.95741 | 0.15912 | 0.19095 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 12.70000 | 9.15345E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 82438.26394 | 98925.91673 | 5.29018 | 6.34821 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 42.80000 | 1.07818E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 10387.15535 | 12464.58642 | 0.24574 | 0.42471 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 12.70000 | 9.15345E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 42.80000 | 1.07818E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 35663.12005 | 42795.74406 | 0.87181 | 1.04618 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12.70000 | 9.15345E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 25959.40 | 1.64564 | 1.64564 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 5412.58 | 0.19095 | 0.19095 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 121112.10 | 6.34821 | 6.34821 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 14023.03 | 0.42471 | 0.42471 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.64564 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.34821 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.04618 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 1.04618 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 42795.74413 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 42795.74406 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.64564 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.64564 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.64564 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.64564 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.64564 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.64564 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.34821 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.34821 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.34821 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 6.34821 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.34821 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 6.34821 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.64564 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 6.34821 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.64564 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.64564 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1801.16603 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.64564 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.64564 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.64564 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.64564 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.64564 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.82282 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.64564 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 34513.97000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 17696.07187 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 34513.97000 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75818 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75818 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 34513.97000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 38807.14921 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 38807.14921 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.34821 |
47 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 6.34821 |
49 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 10929.97850 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 6.34821 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 6.34821 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 6.34821 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 6.34821 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 6.34821 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.17411 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 6.34821 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 157487.99000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 78820.58604 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 157487.99000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70132 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70132 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 157487.99000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 189109.54399 |
64 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
66 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 189109.54399 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 33235.9 | 11.08 | 10.44 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 152553.6 | 10.53 | 9.92 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 4.7190802790E-002 | 2.9288219471E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 6.6615689151E-002 | 4.9911342464E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 0.1901907254 | 0.1519497970 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7597.36 | 1930.95 | 0.00 | -131.5 | 1450.26 | 10847.08 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 3.584 | 7.732 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 3.584 | 7.732 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 3.584 | 7.732 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 7.226 | 982.639 | 3204.84 | 3170.23 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 2.711 | 7.732 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 2.711 | 7.732 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 6.813 | 0.251 | 0.252 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 6.813 | 0.251 | 0.252 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_1.2_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 6.813 | 0.251 | 0.252 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_1.2_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 6.813 | 0.251 | 0.252 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.27 | 6.141 | 0.449 | 0.450 | |||||||||||||||||
North Total or Average | 6.51 | 6.813 | 0.251 | 0.252 | |||||||||||||||||
Non-North Total or Average | 45.76 | 6.046 | 0.478 | 0.478 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.7186 | 236.88 | 2539.01 | LightsWired | LTG_SCH_OFFICE | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.86 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 15.0695 | 1393.41 | 20997.93 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 239.15 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 9.6875 | 3204.84 | 31046.94 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 353.60 |
Interior Lighting Total | 11.2890 | 4835.13 | 54583.89 | 623.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 8532.22 | AstronomicalClock | - | 83.85 | 83.85 | 134.30 | |
Exterior Lighting Total | 8532.22 | 134.30 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 34513.97 | 26167.80 | 8346.17 | 0.76 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 157487.99 | 110449.48 | 47038.51 | 0.70 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 33235.9 | 11.08 | 10.44 | ||||
PSZ-FINE STORAGE COOLING COIL | 152553.6 | 10.53 | 9.92 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 42795.74 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 38807.15 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 189109.54 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 1.05 | 97.20 | 92.91 | 1.00 | 4.10 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 1.65 | 1801.17 | 1094.51 | 1.00 | 1.32 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.59 | 1018.41 | 6.35 | 10929.98 | 1721.74 | 1.00 | 1.14 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 16659.73 | 19991.67 | 84.40 | 1.371 | 1.646 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 23.90 | 23.90 | 0.00833 | 42.31 | 0.01078 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 82438.26 | 98925.92 | 71.00 | 5.290 | 6.348 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 26.70 | 26.70 | 0.00841 | 42.80 | 0.01078 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 0.00 | 47.79 | 0.01086 | 42.80 | 0.01078 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 5676.63 | 6811.96 | 28.76 | 0.159 | 0.191 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00893 | 12.70 | 0.00915 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 10387.16 | 12464.59 | 8.95 | 0.246 | 0.425 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00860 | 12.70 | 0.00915 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 35663.12 | 42795.74 | 13.35 | 0.872 | 1.046 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00763 | 12.70 | 0.00915 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.65 | 1.65 | 0.19 | 0.19 | 1.6456 | 1.6456 | 1.6456 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 6.35 | 6.35 | 0.42 | 0.42 | 6.3482 | 6.3482 | 6.3482 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 42795.744 | 42795.744 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 42795.74 | 42795.74 | 1.046178 | 10.00 | 10.00 | 0.00763498 | 43.33 | 22.14 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 10.00 | 0.00763498 | 99.9999 | 42795.74 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 34513.970 | 26167.802 | 1.645640 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 34513.97 | 32002.29 | 1.645640 | 25.93 | 17.04 | 0.00847858 | 12.00 | 11.25 | 0.00800000 | 42.31 | 0.01078097 | 23.73 | 6.2155 | 23.90 | 0.00832600 | 45.0856 | 16659.73 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 38807.149 | 38807.149 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 38807.15 | 38807.15 | 1.645644 | 20.50 | 15.51 | 0.00894074 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 6.2155 | 21.10 | 0.00892665 | 57.2370 | 5676.63 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 157487.990 | 110449.477 | 6.348210 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 157487.99 | 146265.95 | 6.348210 | 29.18 | 18.21 | 0.00856600 | 12.00 | 11.25 | 0.00800000 | 42.80 | 0.01078182 | 23.86 | 6.6903 | 26.70 | 0.00840713 | 38.5384 | 82438.26 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 189109.544 | 189109.544 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 189109.54 | 189109.54 | 6.348212 | 15.37 | 13.29 | 0.00866198 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 6.6903 | 15.56 | 0.00862674 | 78.3540 | 10148.86 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 42795.744 | 42795.744 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 1.046178 | 1.25917458 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 42795.74 | 42795.74 | 1.0000 | 1.25917458 | 1.046178 | 10.00 | 10.00 | 0.00763498 | 29284.8 | 43.33 | 22.14 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 42795.74 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 10.00 | 0.00763498 | 10.00 | 0.00763498 | 99.9999 | 42795.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 34513.970 | 26167.802 | 1.645640 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6013 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.645644 | 1.98068846 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | Sensible | 34513.97 | 32002.29 | 1.0000 | 1.98068405 | 1.645640 | 25.93 | 17.04 | 0.00847858 | 47672.6 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34513.97 | 42.31 | 0.01078097 | 23.73 | 0.10228463 | 6.2155 | 23.90 | 0.00832600 | 23.90 | 0.00832600 | 45.0856 | 16659.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 38807.149 | 38807.149 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.645644 | 1.98068846 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 38807.15 | 38807.15 | 1.0000 | 1.98068846 | 1.645644 | 20.50 | 15.51 | 0.00894074 | 43302.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38807.15 | 12.70 | 0.00915345 | 12.70 | 0.10228463 | 6.2155 | 21.02 | 0.00892665 | 21.10 | 0.00892665 | 57.2370 | 5676.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 157487.990 | 110449.477 | 6.348210 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7638 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 6.348212 | 7.64067575 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | Sensible | 157487.99 | 146265.95 | 1.0000 | 7.64067370 | 6.348210 | 29.18 | 18.21 | 0.00856600 | 51204.6 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 157487.99 | 42.80 | 0.01078182 | 23.86 | 0.42471127 | 6.6903 | 26.70 | 0.00840713 | 26.70 | 0.00840713 | 38.5384 | 82438.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 189109.544 | 189109.544 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 6.348212 | 7.64067575 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 189109.54 | 189109.54 | 1.0000 | 7.64067575 | 6.348212 | 15.37 | 13.29 | 0.00866198 | 37354.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 189109.54 | 12.70 | 0.00915345 | 12.70 | 0.42471127 | 6.6903 | 15.56 | 0.00862674 | 15.56 | 0.00862674 | 78.3540 | 10148.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 3340.33 | 407.83 | 306.67 |
ZONE2 FINE STORAGE | 3523.17 | 2996.67 | 2912.83 |
ZONE3 BULK STORAGE | 3457.33 | 3453.50 | 3302.00 |
Facility | 3619.83 | 3459.17 | 3308.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 0.00 | 133.83 | 0.00 | 67.67 |
ZONE2 FINE STORAGE | 0.00 | 668.17 | 0.00 | 16.50 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 777.00 | 0.00 | 72.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.352 | 0.492 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.496 | 0.399 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.180 | 0.000 | 2.585 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.54 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1281566.70 | 0.00 | 1281566.70 | 2685553.59 | 3967120.29 | 3225648.14 | 5394.94 | 3365.06 | 0.00 | 700.29 |
ZONE2 FINE STORAGE | 5764684.85 | 0.00 | 5764684.85 | 9501763.81 | 15266448.65 | 13393694.68 | 5405.39 | 3354.61 | 0.00 | 2097.64 |
ZONE3 BULK STORAGE | 0.00 | 0.61E+09 | 0.61E+09 | 39432196.75 | 0.65E+09 | 30805497.77 | 3866.84 | 5.96 | 4887.20 | 5105.50 |
Total Facility | 7046251.54 | 0.61E+09 | 0.62E+09 | 51619514.15 | 0.67E+09 | 47424840.58 | 6414.72 | 3389.78 | 4887.20 | 5106.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.0959 | 0.0000 | 0.0959 | 0.1339 | 0.2297 | 0.1023 | 271.38 | 3364.62 | 0.00 |
ZONE2 FINE STORAGE | 0.3909 | 0.0000 | 0.3909 | 0.3144 | 0.7053 | 0.4247 | 302.28 | 3333.72 | 0.00 |
ZONE3 BULK STORAGE | 0.0000 | 23.3552 | 23.3552 | 1.6442 | 24.9993 | 0.9768 | 1203.54 | 2.04 | 2430.42 |
Total Facility | 0.4868 | 23.3552 | 23.8420 | 2.0924 | 25.9344 | 1.5038 | 1290.81 | 3364.62 | 2430.42 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 1856529.91 | 0.00 | 1856529.91 | 3225648.14 | 5381.84 | 0.66 | 3377.50 | 681.97 |
PSZ-FINE STORAGE | 8350958.13 | 0.00 | 8350958.13 | 13393694.68 | 5365.01 | 2.66 | 3392.33 | 2092.97 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1389 | 0.0000 | 0.1389 | 0.1023 | 261.30 | 0.49 | 3374.20 |
PSZ-FINE STORAGE | 0.5663 | 0.0000 | 0.5663 | 0.4247 | 301.52 | 0.07 | 3334.41 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 4205.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 5533.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1433 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.5986 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 383 |
Defaulted Fields | 319 |
Fields with Defaults | 1020 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1485.27 | 6718.26 | 01-JAN-07:10 | 122979.65 | 10-AUG-15:40 |
Electricity:Building | 803.10 | 6235.26 | 01-JAN-00:10 | 58611.10 | 23-JAN-13:10 |
Electricity:Zone:ZONE1 OFFICE | 62.81 | 1030.77 | 01-JAN-00:10 | 3867.54 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 762.90 | 6235.26 | 01-JAN-00:10 | 56305.80 | 02-JAN-09:10 |
InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 501.14 | 3104.69 | 01-JAN-00:10 | 36895.31 | 23-JAN-13:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 213.06 | 0.00 | 01-JAN-00:10 | 15036.44 | 19-OCT-08:00 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 40.20 | 0.00 | 01-JAN-00:10 | 2305.29 | 04-FEB-14:30 |
Ventilation (simple):Fans:Electricity | 40.20 | 0.00 | 01-JAN-00:10 | 2305.29 | 04-FEB-14:30 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 40.20 | 0.00 | 01-JAN-00:10 | 2305.29 | 04-FEB-14:30 |
ElectricityPurchased:Facility | 1485.27 | 6718.26 | 01-JAN-07:10 | 122979.65 | 10-AUG-15:40 |
ElectricityPurchased:Plant | 1485.27 | 6718.26 | 01-JAN-07:10 | 122979.65 | 10-AUG-15:40 |
Cogeneration:ElectricityPurchased | 1485.27 | 6718.26 | 01-JAN-07:10 | 122979.65 | 10-AUG-15:40 |
General:Cogeneration:ElectricityPurchased | 1485.27 | 6718.26 | 01-JAN-07:10 | 122979.65 | 10-AUG-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1485.27 | 6718.26 | 01-JAN-07:10 | 122979.65 | 10-AUG-15:40 |
ElectricityNet:Plant | 1485.27 | 6718.26 | 01-JAN-07:10 | 122979.65 | 10-AUG-15:40 |
Cogeneration:ElectricityNet | 1485.27 | 6718.26 | 01-JAN-07:10 | 122979.65 | 10-AUG-15:40 |
General:Cogeneration:ElectricityNet | 1485.27 | 6718.26 | 01-JAN-07:10 | 122979.65 | 10-AUG-15:40 |
Electricity:HVAC | 525.16 | 0.00 | 01-JAN-00:10 | 68875.08 | 10-AUG-16:00 |
General:Fans:Electricity | 172.87 | 0.00 | 01-JAN-00:10 | 12731.14 | 03-JAN-15:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 352.29 | 0.00 | 01-JAN-00:10 | 56143.93 | 10-AUG-16:00 |
General:Cooling:Electricity | 352.29 | 0.00 | 01-JAN-00:10 | 56143.93 | 10-AUG-16:00 |
ExteriorLights:Electricity | 134.30 | 0.00 | 01-JAN-07:10 | 8532.22 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 134.30 | 0.00 | 01-JAN-07:10 | 8532.22 | 01-JAN-00:10 |
Electricity:Plant | 22.72 | 483.00 | 09-FEB-06:10 | 1745.80 | 12-JAN-13:00 |
WaterSystems:Electricity | 22.72 | 483.00 | 09-FEB-06:10 | 1745.80 | 12-JAN-13:00 |
Water Heater:WaterSystems:Electricity | 22.72 | 483.00 | 09-FEB-06:10 | 1745.80 | 12-JAN-13:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 1154.45 | 02-JAN-07:20 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 1154.45 | 02-JAN-07:20 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 1154.45 | 02-JAN-07:20 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 1154.45 | 02-JAN-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-13:00 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-13:00 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-13:00 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-13:00 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-13:00 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-13:00 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-13:00 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-13:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1763.06 | 0.00 | 01-JAN-00:10 | 250121.52 | 10-AUG-16:00 |
EnergyTransfer:Building | 665.09 | 0.00 | 01-JAN-00:10 | 93146.56 | 21-JUL-15:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 125.20 | 0.00 | 01-JAN-00:10 | 20184.76 | 16-AUG-12:00 |
Heating:EnergyTransfer | 2.84 | 0.00 | 01-JAN-00:10 | 8020.58 | 02-JAN-17:50 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.14 | 0.00 | 01-JAN-00:10 | 1614.86 | 02-JAN-07:20 |
General:Heating:EnergyTransfer | 2.84 | 0.00 | 01-JAN-00:10 | 8020.58 | 02-JAN-17:50 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.14 | 0.00 | 01-JAN-00:10 | 1614.86 | 02-JAN-07:20 |
Cooling:EnergyTransfer | 662.25 | 0.00 | 01-JAN-00:10 | 93146.56 | 21-JUL-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 125.05 | 0.00 | 01-JAN-00:10 | 20184.76 | 16-AUG-12:00 |
General:Cooling:EnergyTransfer | 662.25 | 0.00 | 01-JAN-00:10 | 93146.56 | 21-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 125.05 | 0.00 | 01-JAN-00:10 | 20184.76 | 16-AUG-12:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 539.90 | 0.00 | 01-JAN-00:10 | 76308.85 | 21-JUL-15:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 2.70 | 0.00 | 01-JAN-00:10 | 8020.58 | 02-JAN-17:50 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 2.70 | 0.00 | 01-JAN-00:10 | 8020.58 | 02-JAN-17:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 537.20 | 0.00 | 01-JAN-00:10 | 76308.85 | 21-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 537.20 | 0.00 | 01-JAN-00:10 | 76308.85 | 21-JUL-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1097.97 | 0.00 | 01-JAN-00:10 | 163914.92 | 22-AUG-17:00 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 742.80 | 02-JAN-07:20 |
CoolingCoils:EnergyTransfer | 1097.97 | 0.00 | 01-JAN-00:10 | 163914.92 | 22-AUG-17:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 0.144 | -125.052 | 0.000 | 0.000 | 9.118 | 30.864 | 31.946 | 17.397 | 0.000 | 15.856 | 29.415 | 0.000 | -5.225 | 0.000 | -4.462 | -0.000 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 2.700 | -537.191 | 0.000 | 0.000 | 17.164 | 239.148 | 0.000 | 0.000 | 0.000 | 45.377 | 251.852 | 0.000 | 0.000 | 0.000 | -19.051 | -0.010 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.592 | 353.598 | 107.344 | 202.696 | 0.000 | 1.750 | 1407.525 | 0.000 | -61.878 | 0.000 | -2027.628 | -0.037 |
Total Facility | 0.000 | 0.000 | 2.844 | -662.242 | 0.000 | 0.000 | 42.873 | 623.610 | 139.290 | 220.093 | 0.000 | 62.983 | 1688.792 | 0.000 | -67.103 | 0.000 | -2051.141 | -0.047 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 27-MAR-05:01 | 0.00 | 0.00 | 0.00 | -33377.49 | 0.00 | 0.00 | 71.69 | 583.97 | 573.75 | 0.00 | 0.00 | 0.00 | 33043.47 | 0.00 | -554.68 | 0.00 | -340.71 | 0.00 |
ZONE2 FINE STORAGE | 26-MAR-16:02 | 0.00 | 0.00 | 0.00 | -132994.50 | 0.00 | 0.00 | 0.00 | 2099.79 | 0.00 | 0.00 | 0.00 | 2646.78 | 128247.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-JUL-05:01 | 0.00 | 0.00 | 0.00 | -149423.69 | 0.00 | 0.00 | 346.40 | 5788.46 | 2623.78 | 0.00 | 0.00 | 2429.79 | 236579.71 | 0.00 | -3535.49 | 0.00 | -94808.96 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 02-JAN-07:15 | 0.00 | 0.00 | 1928.18 | 0.00 | 0.00 | 0.00 | 225.96 | 1066.39 | 956.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -589.80 | 0.00 | -3190.32 | -396.66 |
ZONE2 FINE STORAGE | 15-FEB-07:43 | 0.00 | 0.00 | 8422.52 | 0.00 | 0.00 | 0.00 | 420.56 | 12598.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1475.94 | -19965.90 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 15-FEB-07:43 | 0.00 | 0.00 | 8555.20 | 0.00 | 0.00 | 0.00 | 1927.04 | 32293.31 | 3006.28 | 2715.64 | 0.00 | 3346.44 | 0.00 | 0.00 | -32.74 | 0.00 | -2466.32 | -49344.86 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.6456 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.6456 | 0.0622 | 1.0000 | Not calculated | 0.1023 | 0.0622 | ||
PSZ-FINE STORAGE | 6.3482 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 6.3482 | 0.0669 | 1.0000 | Not calculated | 0.4247 | 0.0669 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.6456 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.6456 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0622 | ||
PSZ-FINE STORAGE | 6.3482 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 6.3482 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.0669 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6456 | 1.6456 | 1.6456 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.3482 | 6.3482 | 6.3482 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.6456 | 1.6456 | 1.6456 | 1.6456 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 6.3482 | 6.3482 | 6.3482 | 6.3482 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6456 | 1.6456 | 1.6456 | No | 0.1023 | 0.5357 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.3482 | 6.3482 | 6.3482 | No | 0.4247 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.6456 | 1.6456 | 1.6456 | 1.6456 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 6.3482 | 6.3482 | 6.3482 | 6.3482 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 72.33 |
Number of hours not met | 72.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 1154.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 352.29 | 56143.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 623.61 | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 134.30 | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 40.20 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 172.87 | 12731.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 22.72 | 1745.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 1485.27 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 1485.28 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 128.97 |
Space Heating | 0.00 |
Space Cooling | 72.86 |
Fans (All) | 44.07 |
Service Water Heating | 4.70 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 307.18 |
Subtotal | 307.18 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 41.99 |
Space Heating | 0.00 |
Space Cooling | 23.72 |
Fans (All) | 14.35 |
Service Water Heating | 1.53 |
Receptacle Equipment | 9.38 |
Miscellaneous | 9.04 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 3430. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 4988.67 | 3150.00 | 621.33 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 3562.17 | 5197.83 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 2357.67 | 2224.83 | 1770.50 | 2138.67 | 268.33 |
Min | 2357.67 | 2224.83 | 0.00 | 0.00 | 0.00 |
Max | 4988.67 | 5197.83 | 1770.50 | 2138.67 | 268.33 |
Average | 3636.17 | 3524.22 | 797.28 | 712.89 | 89.44 |
Sum | 10908.50 | 10572.67 | 2391.83 | 2138.67 | 268.33 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33024.33 | 2.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 31851.00 | 50868.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 18356.17 | 63824.00 | 40727.00 | 55021.33 | 13264.50 |
Min | 18356.17 | 2.67 | 0.00 | 0.00 | 0.00 |
Max | 33024.33 | 63824.00 | 40727.00 | 55021.33 | 13264.50 |
Average | 27743.83 | 38231.56 | 13575.67 | 18340.44 | 4421.50 |
Sum | 83231.50 | 114694.67 | 40727.00 | 55021.33 | 13264.50 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 4263.33 | 4372.17 | 124.50 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 2662.17 | 6097.83 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 1820.67 | 3452.50 | 1321.17 | 1363.17 | 802.50 |
Min | 1820.67 | 3452.50 | 0.00 | 0.00 | 0.00 |
Max | 4263.33 | 6097.83 | 1321.17 | 1363.17 | 802.50 |
Average | 2915.39 | 4640.83 | 481.89 | 454.39 | 267.50 |
Sum | 8746.17 | 13922.50 | 1445.67 | 1363.17 | 802.50 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 31901.33 | 1125.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 27737.50 | 54981.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 14998.83 | 87962.83 | 28177.50 | 29267.17 | 30786.67 |
Min | 14998.83 | 1125.67 | 0.00 | 0.00 | 0.00 |
Max | 31901.33 | 87962.83 | 28177.50 | 29267.17 | 30786.67 |
Average | 24879.22 | 48023.33 | 9392.50 | 9755.72 | 10262.22 |
Sum | 74637.67 | 144070.00 | 28177.50 | 29267.17 | 30786.67 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.430432E+10 | 24117.71 | 30-JAN-06:01 | 20.03 | 17.43 | 0.632454E+09 | 778.39 | 23-JAN-08:09 | 20.03 | 17.43 |
February | 0.508690E+10 | 25747.68 | 28-FEB-06:02 | 16.87 | 15.12 | 0.583280E+09 | 769.04 | 11-FEB-15:50 | 16.87 | 15.12 |
March | 0.759493E+10 | 33377.98 | 27-MAR-05:01 | 21.92 | 13.45 | 0.685677E+09 | 769.08 | 21-MAR-15:30 | 21.92 | 13.45 |
April | 0.902702E+10 | 33254.71 | 25-APR-05:01 | 23.83 | 13.00 | 0.635127E+09 | 769.11 | 28-APR-15:50 | 34.42 | 21.78 |
May | 0.128326E+11 | 32994.03 | 05-MAY-05:01 | 26.00 | 15.80 | 0.660842E+09 | 769.12 | 31-MAY-15:30 | 37.25 | 26.96 |
June | 0.142043E+11 | 29891.58 | 16-JUN-05:01 | 28.17 | 20.46 | 0.660952E+09 | 769.13 | 19-JUN-15:00 | 36.60 | 25.61 |
July | 0.155205E+11 | 31650.02 | 03-JUL-05:01 | 28.83 | 16.82 | 0.635721E+09 | 769.14 | 20-JUL-15:00 | 38.10 | 27.03 |
August | 0.169411E+11 | 27684.20 | 06-AUG-15:31 | 40.40 | 25.42 | 0.686562E+09 | 769.14 | 29-AUG-15:00 | 37.00 | 29.07 |
September | 0.135978E+11 | 26039.80 | 13-SEP-05:01 | 29.83 | 23.56 | 0.635598E+09 | 769.13 | 12-SEP-15:00 | 29.83 | 23.56 |
October | 0.114934E+11 | 31330.74 | 20-OCT-05:01 | 23.17 | 16.23 | 0.635413E+09 | 769.10 | 03-OCT-13:20 | 23.17 | 16.23 |
November | 0.858683E+10 | 29854.36 | 18-NOV-06:01 | 20.08 | 16.00 | 0.609752E+09 | 769.09 | 06-NOV-15:09 | 20.08 | 16.00 |
December | 0.586281E+10 | 28929.01 | 01-DEC-06:02 | 17.17 | 12.52 | 0.634588E+09 | 769.07 | 01-DEC-15:30 | 27.45 | 18.29 |
Annual Sum or Average | 0.125052E+12 | 0.769597E+10 | ||||||||
Minimum of Months | 0.430432E+10 | 24117.71 | 16.87 | 12.52 | 0.583280E+09 | 769.04 | 16.87 | 13.45 | ||
Maximum of Months | 0.169411E+11 | 33377.98 | 40.40 | 25.42 | 0.686562E+09 | 778.39 | 38.10 | 29.07 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.700568E+10 | 24992.64 | 29-JAN-15:15 | 25.33 | 19.76 | 0.181462E+10 | 2267.72 | 13-JAN-09:20 | 25.33 | 19.76 |
February | 0.114945E+11 | 104934.86 | 05-FEB-14:23 | 31.80 | 19.36 | 0.168978E+10 | 2251.16 | 23-FEB-08:00 | 19.70 | 16.42 |
March | 0.224434E+11 | 132998.34 | 26-MAR-16:02 | 31.70 | 18.58 | 0.199684E+10 | 2247.12 | 21-MAR-13:50 | 31.70 | 18.58 |
April | 0.363311E+11 | 132175.03 | 23-APR-17:02 | 30.83 | 19.27 | 0.185356E+10 | 2247.24 | 27-APR-15:50 | 35.82 | 22.63 |
May | 0.632416E+11 | 124998.06 | 11-MAY-19:02 | 35.50 | 20.63 | 0.192901E+10 | 2247.32 | 22-MAY-15:09 | 36.77 | 23.84 |
June | 0.713513E+11 | 123934.26 | 15-JUN-17:04 | 37.67 | 20.98 | 0.192914E+10 | 2247.32 | 12-JUN-13:09 | 37.67 | 20.98 |
July | 0.833698E+11 | 121670.96 | 02-JUL-15:01 | 38.07 | 22.80 | 0.185526E+10 | 2247.40 | 31-JUL-15:00 | 39.70 | 25.38 |
August | 0.860232E+11 | 117365.49 | 06-AUG-09:42 | 37.58 | 24.12 | 0.200375E+10 | 2247.42 | 10-AUG-15:00 | 41.60 | 30.36 |
September | 0.664462E+11 | 118417.77 | 04-SEP-16:21 | 40.35 | 23.48 | 0.185491E+10 | 2247.36 | 05-SEP-15:39 | 39.07 | 25.40 |
October | 0.501646E+11 | 125346.07 | 15-OCT-14:22 | 34.50 | 20.54 | 0.185480E+10 | 2247.24 | 04-OCT-15:00 | 34.50 | 20.54 |
November | 0.273676E+11 | 102683.80 | 05-NOV-13:22 | 33.20 | 21.19 | 0.177897E+10 | 2247.15 | 06-NOV-14:09 | 32.83 | 20.61 |
December | 0.119578E+11 | 61086.96 | 03-DEC-14:13 | 27.00 | 20.88 | 0.184127E+10 | 2247.05 | 01-DEC-13:30 | 27.00 | 20.88 |
Annual Sum or Average | 0.537197E+12 | 0.224019E+11 | ||||||||
Minimum of Months | 0.700568E+10 | 24992.64 | 25.33 | 18.58 | 0.168978E+10 | 2247.05 | 19.70 | 16.42 | ||
Maximum of Months | 0.860232E+11 | 132998.34 | 40.35 | 24.12 | 0.200375E+10 | 2267.72 | 41.60 | 30.36 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.84 | 0.431117E+10 | 6811.94 | 28-JAN-14:09 | 27.67 | 14.14 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 14.59 | 0.436576E+10 | 8579.59 | 06-FEB-14:50 | 32.42 | 17.27 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 | 18.46 | 0.566309E+10 | 9097.65 | 01-MAR-13:09 | 35.33 | 18.49 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 | 20.11 | 0.614774E+10 | 9097.65 | 01-APR-12:09 | 32.17 | 15.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 | 23.56 | 0.735803E+10 | 9097.65 | 01-MAY-12:09 | 31.83 | 21.95 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 23.24 | 0.748426E+10 | 9097.65 | 01-JUN-08:30 | 35.00 | 21.85 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 | 27.02 | 0.735746E+10 | 9097.65 | 01-JUL-08:50 | 34.50 | 27.94 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 | 28.28 | 0.795949E+10 | 9097.65 | 01-AUG-08:20 | 34.33 | 24.05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 | 25.04 | 0.709006E+10 | 9097.65 | 01-SEP-09:09 | 33.82 | 25.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 | 26.77 | 0.666733E+10 | 9097.65 | 02-OCT-10:09 | 33.70 | 21.34 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 | 21.17 | 0.542328E+10 | 9097.65 | 01-NOV-12:09 | 32.48 | 26.16 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 | 15.63 | 0.458066E+10 | 7056.13 | 01-DEC-13:30 | 28.10 | 18.32 |
Annual Sum or Average | 0.00 | 0.744083E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 15.70 | 12.84 | 0.431117E+10 | 6811.94 | 27.67 | 14.14 | ||
Maximum of Months | 0.00 | 0.00 | 33.23 | 28.28 | 0.795949E+10 | 9097.65 | 35.33 | 27.94 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 61921906.29 | 1928.15 | 02-JAN-07:15 | 13.00 |
February | 36996274.77 | 1280.67 | 27-FEB-07:10 | 16.83 |
March | 17300480.20 | 1294.84 | 17-MAR-06:10 | 16.83 |
April | 117731.71 | 392.44 | 05-APR-06:10 | 17.02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 27642503.47 | 1216.03 | 13-DEC-07:10 | 15.25 |
Annual Sum or Average | 0.143979E+09 | |||
Minimum of Months | 0.00 | 0.00 | 13.00 | |
Maximum of Months | 61921906.29 | 1928.15 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111945E+10 | 8180.26 | 02-JAN-17:43 | 20.17 |
February | 0.583860E+09 | 8422.72 | 15-FEB-07:43 | 21.57 |
March | 0.324375E+09 | 7977.86 | 01-MAR-07:15 | 24.33 |
April | 45311404.79 | 5602.35 | 06-APR-06:05 | 21.22 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 60512116.62 | 6671.31 | 24-NOV-07:13 | 19.67 |
December | 0.566549E+09 | 7902.13 | 27-DEC-07:13 | 20.93 |
Annual Sum or Average | 0.270005E+10 | |||
Minimum of Months | 0.00 | 0.00 | 19.67 | |
Maximum of Months | 0.111945E+10 | 8422.72 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.258145E+10 | 1955.04 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.235440E+10 | 1955.04 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.269003E+10 | 1955.04 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.254196E+10 | 1955.04 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.263574E+10 | 1955.04 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.259625E+10 | 1955.04 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.258145E+10 | 1955.04 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.269003E+10 | 1955.04 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.254196E+10 | 1955.04 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.258145E+10 | 1955.04 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.248766E+10 | 1955.04 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.258145E+10 | 1955.04 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.308638E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.235440E+10 | 1955.04 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.269003E+10 | 1955.04 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.198922E+11 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.182065E+11 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.210336E+11 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.197108E+11 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.204629E+11 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.202815E+11 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.198922E+11 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.210336E+11 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.197108E+11 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.198922E+11 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.191400E+11 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.198922E+11 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.239148E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.182065E+11 | 17848.24 | 0.00 | 0.00 | |
Maximum of Months | 0.210336E+11 | 17848.24 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.294120E+11 | 26389.90 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.269196E+11 | 26389.90 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.310997E+11 | 26389.90 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.291438E+11 | 26389.90 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.302559E+11 | 26389.90 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.299876E+11 | 26389.90 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.294120E+11 | 26389.90 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.310997E+11 | 26389.90 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.291438E+11 | 26389.90 | 01-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.294120E+11 | 26389.90 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.282999E+11 | 26389.90 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.294120E+11 | 26389.90 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.353598E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.269196E+11 | 26389.90 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.310997E+11 | 26389.90 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11679339.10 | 0.114118E+10 |
February | 0.127628E+10 | 0.235440E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124475E+09 | 0.965182E+09 |
March | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452972E+09 | 0.647199E+09 |
April | 0.138726E+10 | 0.254196E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.884674E+09 | 0.322170E+09 |
May | 0.144276E+10 | 0.263574E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192975E+10 | 64716650.95 |
June | 0.144276E+10 | 0.259625E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240287E+10 | 26522283.31 |
July | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278086E+10 | 630424.31 |
August | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307910E+10 | 360313.87 |
September | 0.138726E+10 | 0.254196E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208952E+10 | 25795662.83 |
October | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137429E+10 | 97318247.98 |
November | 0.133177E+10 | 0.248766E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628243E+09 | 0.351154E+09 |
December | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97321114.38 | 0.819919E+09 |
Annual Sum or Average | 0.168137E+11 | 0.308638E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158558E+11 | 0.446214E+10 |
Minimum of Months | 0.127628E+10 | 0.235440E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11679339.10 | 360313.87 |
Maximum of Months | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307910E+10 | 0.114118E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2733654.30 | 0.451949E+10 |
February | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178926E+09 | 0.459481E+10 |
March | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682903E+09 | 0.305765E+10 |
April | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186387E+10 | 0.136534E+10 |
May | 0.339505E+10 | 0.204629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545817E+10 | 0.183704E+09 |
June | 0.339505E+10 | 0.202815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.719411E+10 | 45979684.31 |
July | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.943317E+10 | 0.00 |
August | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.957070E+10 | 0.00 |
September | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639537E+10 | 37293123.08 |
October | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356165E+10 | 0.328143E+09 |
November | 0.313390E+10 | 0.191400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.989990E+09 | 0.136084E+10 |
December | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45906193.01 | 0.355754E+10 |
Annual Sum or Average | 0.395654E+11 | 0.239148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453775E+11 | 0.190508E+11 |
Minimum of Months | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2733654.30 | 0.00 |
Maximum of Months | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.957070E+10 | 0.459481E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31374980.70 | 0.153398E+11 |
February | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6831175.48 | 0.171389E+11 |
March | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94978634.36 | 0.159399E+11 |
April | 0.750829E+10 | 0.291438E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2081688.82 | 0.141215E+11 |
May | 0.780862E+10 | 0.302559E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19113698.32 | 0.121666E+11 |
June | 0.780862E+10 | 0.299876E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3187047.66 | 0.130247E+11 |
July | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2099228.20 | 0.121047E+11 |
August | 0.810895E+10 | 0.310997E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1323432.32 | 0.123598E+11 |
September | 0.750829E+10 | 0.291438E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4137847.24 | 0.102581E+11 |
October | 0.750829E+10 | 0.294120E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3713056.86 | 0.879103E+10 |
November | 0.720796E+10 | 0.282999E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132108E+09 | 0.773303E+10 |
December | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1183302.90 | 0.122340E+11 |
Annual Sum or Average | 0.910005E+11 | 0.353598E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302132E+09 | 0.151212E+12 |
Minimum of Months | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1183302.90 | 0.773303E+10 |
Maximum of Months | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132108E+09 | 0.171389E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1955.04 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1417.77 | 23-JAN-13:00 | 4876.31 | 19-JAN-07:05 |
February | 1680.92 | 01-FEB-08:09 | 1955.04 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2816.31 | 07-FEB-13:00 | 4200.31 | 13-FEB-07:05 |
March | 1680.92 | 01-MAR-08:09 | 1955.04 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5653.76 | 27-MAR-11:10 | 3651.06 | 06-MAR-07:05 |
April | 1680.92 | 01-APR-07:10 | 1955.04 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6328.06 | 28-APR-12:00 | 3009.60 | 05-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 1955.04 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6573.11 | 10-MAY-16:10 | 1380.97 | 01-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 1955.04 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9144.82 | 09-JUN-16:10 | 492.15 | 07-JUN-05:01 |
July | 1680.92 | 01-JUL-07:10 | 1955.04 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8928.86 | 21-JUL-17:00 | 43.22 | 02-JUL-04:53 |
August | 1680.92 | 01-AUG-07:10 | 1955.04 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8538.20 | 16-AUG-12:00 | 48.06 | 27-AUG-06:00 |
September | 1680.92 | 01-SEP-07:10 | 1955.04 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7147.77 | 05-SEP-16:10 | 519.95 | 25-SEP-05:01 |
October | 1680.92 | 02-OCT-07:10 | 1955.04 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6641.20 | 19-OCT-16:10 | 735.83 | 30-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 1955.04 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3885.12 | 01-NOV-16:10 | 2982.37 | 22-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1955.04 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1629.30 | 01-DEC-13:00 | 3871.64 | 13-DEC-07:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1417.77 | 43.22 | |||||
Maximum of Months | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 9144.82 | 4876.31 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.18 | 23-JAN-14:00 | 8582.48 | 19-JAN-09:00 |
February | 3955.50 | 01-FEB-08:09 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5132.02 | 05-FEB-15:05 | 9347.06 | 10-FEB-18:00 |
March | 3955.50 | 01-MAR-08:09 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9470.35 | 01-MAR-16:10 | 7065.11 | 25-MAR-09:00 |
April | 3955.50 | 01-APR-07:10 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13007.64 | 28-APR-15:10 | 4782.11 | 04-APR-07:00 |
May | 3955.50 | 01-MAY-07:10 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34468.92 | 21-MAY-12:51 | 2355.12 | 01-MAY-07:05 |
June | 3955.50 | 01-JUN-07:10 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18327.84 | 09-JUN-15:40 | 1621.73 | 07-JUN-05:40 |
July | 3955.50 | 01-JUL-07:10 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18373.42 | 14-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 3955.50 | 01-AUG-07:10 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15699.85 | 10-AUG-16:00 | 0.00 | 01-AUG-00:05 |
September | 3955.50 | 01-SEP-07:10 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13445.94 | 02-SEP-16:00 | 1103.71 | 25-SEP-05:05 |
October | 3955.50 | 02-OCT-07:10 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14316.89 | 19-OCT-15:10 | 3068.33 | 21-OCT-07:00 |
November | 3955.50 | 01-NOV-07:10 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5287.74 | 01-NOV-15:10 | 4141.46 | 22-NOV-07:20 |
December | 3955.50 | 01-DEC-08:09 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1869.20 | 10-DEC-12:47 | 8028.17 | 16-DEC-08:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.18 | 0.00 | ||||
Maximum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34468.92 | 9347.06 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 26389.90 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2613.42 | 29-JAN-07:00 | 34030.80 | 18-JAN-15:00 |
February | 9097.65 | 01-FEB-08:09 | 26389.90 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4242.95 | 15-FEB-07:55 | 45123.49 | 10-FEB-15:05 |
March | 9097.65 | 01-MAR-08:09 | 26389.90 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7843.22 | 01-MAR-04:00 | 63565.65 | 25-MAR-09:00 |
April | 9097.65 | 01-APR-07:10 | 26389.90 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4016.58 | 25-APR-07:53 | 28400.28 | 28-APR-13:05 |
May | 9097.65 | 01-MAY-07:10 | 26389.90 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4928.06 | 28-MAY-03:53 | 47298.50 | 21-MAY-12:51 |
June | 9097.65 | 01-JUN-07:10 | 26389.90 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1034.58 | 22-JUN-08:51 | 28641.50 | 29-JUN-13:30 |
July | 9097.65 | 01-JUL-07:10 | 26389.90 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 551.94 | 20-JUL-20:51 | 25094.74 | 14-JUL-12:10 |
August | 9097.65 | 01-AUG-07:10 | 26389.90 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1516.45 | 01-AUG-23:55 | 20050.18 | 11-AUG-15:00 |
September | 9097.65 | 01-SEP-07:10 | 26389.90 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1607.81 | 30-SEP-07:52 | 20182.61 | 02-SEP-13:55 |
October | 9097.65 | 02-OCT-07:10 | 26389.90 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 878.76 | 29-OCT-04:55 | 16814.49 | 19-OCT-12:40 |
November | 9097.65 | 01-NOV-07:10 | 26389.90 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4397.18 | 19-NOV-19:00 | 12375.94 | 20-NOV-16:10 |
December | 9097.65 | 01-DEC-08:09 | 26389.90 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 430.77 | 26-DEC-22:00 | 40412.78 | 15-DEC-12:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 430.77 | 12375.94 | |||||
Maximum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 7843.22 | 63565.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24117.71 | 30-JAN-06:01 | 1294.31 | 4087.81 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.22 |
February | 25747.68 | 28-FEB-06:02 | 924.51 | 2919.87 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 619.81 |
March | 33377.98 | 27-MAR-05:01 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340.71 |
April | 33254.71 | 25-APR-05:01 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.63 |
May | 32994.03 | 05-MAY-05:01 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.28 |
June | 29891.58 | 16-JUN-05:01 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.77 |
July | 31650.02 | 03-JUL-05:01 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 0.00 |
August | 27684.20 | 06-AUG-15:31 | 0.00 | 4570.22 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 991.93 | 0.00 |
September | 26039.80 | 13-SEP-05:01 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 71.17 | 0.00 |
October | 31330.74 | 20-OCT-05:01 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 593.96 |
November | 29854.36 | 18-NOV-06:01 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.21 |
December | 28929.01 | 01-DEC-06:02 | 1109.41 | 3503.84 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 796.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 24117.71 | 0.00 | 2919.87 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33377.98 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 991.93 | 796.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24992.64 | 29-JAN-15:15 | 0.00 | 4199.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.77 |
February | 104934.86 | 05-FEB-14:23 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4286.99 | 0.00 |
March | 132998.34 | 26-MAR-16:02 | 0.00 | 10498.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2646.78 | 0.00 |
April | 132175.03 | 23-APR-17:02 | 0.00 | 10498.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2473.93 | 0.00 |
May | 124998.06 | 11-MAY-19:02 | 0.00 | 10498.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2481.06 | 0.00 |
June | 123934.26 | 15-JUN-17:04 | 0.00 | 16798.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6293.97 | 0.00 |
July | 121670.96 | 02-JUL-15:01 | 0.00 | 14698.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7132.58 | 0.00 |
August | 117365.49 | 06-AUG-09:42 | 0.00 | 12598.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3542.57 | 0.00 |
September | 118417.77 | 04-SEP-16:21 | 0.00 | 14698.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8060.53 | 0.00 |
October | 125346.07 | 15-OCT-14:22 | 0.00 | 12598.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4776.42 | 0.00 |
November | 102683.80 | 05-NOV-13:22 | 0.00 | 10498.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3733.88 | 0.00 |
December | 61086.96 | 03-DEC-14:13 | 0.00 | 6299.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.53 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 24992.64 | 0.00 | 4199.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 132998.34 | 0.00 | 16798.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8060.53 | 430.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 612.21 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2590.45 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 618.60 |
April | 0.00 | 01-APR-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2015.71 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1953.09 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.17 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.78 |
August | 0.00 | 01-AUG-00:05 | 0.00 | 6209.39 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 900.24 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1743.73 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 746.51 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1186.06 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2432.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.17 | |
Maximum of Months | 0.00 | 0.00 | 6209.39 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2590.45 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.974884E+11 | 86577.13 | 23-JAN-13:39 | 3344768.25 | 1154.45 | 02-JAN-07:19 |
February | 0.921001E+11 | 94011.96 | 07-FEB-13:50 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.110736E+12 | 100319.11 | 27-MAR-12:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.113372E+12 | 107305.11 | 28-APR-12:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.135416E+12 | 111795.84 | 31-MAY-14:39 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.143765E+12 | 118233.40 | 09-JUN-14:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.153447E+12 | 121457.51 | 14-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.161758E+12 | 122979.65 | 10-AUG-15:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.140579E+12 | 114117.37 | 06-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.127161E+12 | 108300.42 | 07-OCT-13:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.108129E+12 | 102633.74 | 01-NOV-14:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.101322E+12 | 91135.94 | 06-DEC-13:39 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.148527E+13 | 3344768.25 | ||||
Minimum of Months | 0.921001E+11 | 86577.13 | 0.00 | 0.00 | ||
Maximum of Months | 0.161758E+12 | 122979.65 | 3344768.25 | 1154.45 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.518856E+11 | 0.127215E+11 | 0.115358E+11 | 0.00 | 0.128841E+11 | 0.00 | 0.00 | 0.642749E+10 | 0.00 | 0.00 | 0.00 | 0.203382E+10 | 0.00 |
February | 0.474804E+11 | 0.110373E+11 | 0.105871E+11 | 0.00 | 0.124090E+11 | 0.00 | 0.00 | 0.875608E+10 | 0.00 | 0.00 | 0.00 | 0.183017E+10 | 0.00 |
March | 0.548234E+11 | 0.115595E+11 | 0.123431E+11 | 0.00 | 0.154444E+11 | 0.00 | 0.00 | 0.145539E+11 | 0.00 | 0.00 | 0.00 | 0.201177E+10 | 0.00 |
April | 0.513965E+11 | 0.104844E+11 | 0.114862E+11 | 0.00 | 0.162097E+11 | 0.00 | 0.00 | 0.219284E+11 | 0.00 | 0.00 | 0.00 | 0.186637E+10 | 0.00 |
May | 0.533545E+11 | 0.102694E+11 | 0.119357E+11 | 0.00 | 0.204846E+11 | 0.00 | 0.00 | 0.374990E+11 | 0.00 | 0.00 | 0.00 | 0.187247E+10 | 0.00 |
June | 0.528654E+11 | 0.967554E+10 | 0.118862E+11 | 0.00 | 0.217529E+11 | 0.00 | 0.00 | 0.458014E+11 | 0.00 | 0.00 | 0.00 | 0.178348E+10 | 0.00 |
July | 0.518856E+11 | 0.100953E+11 | 0.115358E+11 | 0.00 | 0.229266E+11 | 0.00 | 0.00 | 0.552009E+11 | 0.00 | 0.00 | 0.00 | 0.180280E+10 | 0.00 |
August | 0.548234E+11 | 0.105817E+11 | 0.123357E+11 | 0.00 | 0.237395E+11 | 0.00 | 0.00 | 0.584268E+11 | 0.00 | 0.00 | 0.00 | 0.185096E+10 | 0.00 |
September | 0.513965E+11 | 0.108786E+11 | 0.114788E+11 | 0.00 | 0.209716E+11 | 0.00 | 0.00 | 0.440353E+11 | 0.00 | 0.00 | 0.00 | 0.181799E+10 | 0.00 |
October | 0.518856E+11 | 0.119383E+11 | 0.115432E+11 | 0.00 | 0.183129E+11 | 0.00 | 0.00 | 0.315601E+11 | 0.00 | 0.00 | 0.00 | 0.192120E+10 | 0.00 |
November | 0.499276E+11 | 0.121533E+11 | 0.110862E+11 | 0.00 | 0.146208E+11 | 0.00 | 0.00 | 0.184316E+11 | 0.00 | 0.00 | 0.00 | 0.190942E+10 | 0.00 |
December | 0.518856E+11 | 0.129007E+11 | 0.115358E+11 | 0.00 | 0.133080E+11 | 0.00 | 0.00 | 0.967314E+10 | 0.00 | 0.00 | 0.00 | 0.201922E+10 | 0.00 |
Annual Sum or Average | 0.623610E+12 | 0.134295E+12 | 0.139290E+12 | 0.00 | 0.213064E+12 | 0.00 | 0.00 | 0.352294E+12 | 0.00 | 0.00 | 0.00 | 0.227197E+11 | 0.00 |
Minimum of Months | 0.474804E+11 | 0.967554E+10 | 0.105871E+11 | 0.00 | 0.124090E+11 | 0.00 | 0.00 | 0.642749E+10 | 0.00 | 0.00 | 0.00 | 0.178348E+10 | 0.00 |
Maximum of Months | 0.548234E+11 | 0.129007E+11 | 0.123431E+11 | 0.00 | 0.237395E+11 | 0.00 | 0.00 | 0.584268E+11 | 0.00 | 0.00 | 0.00 | 0.203382E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 3344768.25 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3344768.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 3344768.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 46193.18 | 02-JAN-09:09 | 8532.22 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 15036.44 | 23-JAN-12:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 46193.18 | 01-FEB-09:09 | 8532.22 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 15036.44 | 01-FEB-12:50 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 46193.18 | 01-MAR-09:09 | 8532.22 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 15036.44 | 01-MAR-09:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 46193.18 | 01-APR-08:09 | 8532.22 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 15036.44 | 01-APR-09:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 46193.18 | 01-MAY-08:09 | 8532.22 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 15036.44 | 01-MAY-08:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 46193.18 | 01-JUN-08:09 | 8532.22 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 15036.44 | 01-JUN-06:40 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 46193.18 | 01-JUL-08:09 | 8532.22 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 15036.44 | 01-JUL-06:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 46193.18 | 01-AUG-08:09 | 8532.22 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 15036.44 | 01-AUG-06:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 46193.18 | 01-SEP-08:09 | 8532.22 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 15036.44 | 01-SEP-06:19 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 46193.18 | 02-OCT-08:09 | 8532.22 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 15036.44 | 19-OCT-07:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 46193.18 | 01-NOV-08:09 | 8532.22 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 15036.44 | 28-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 46193.18 | 01-DEC-09:09 | 8532.22 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 15036.44 | 01-DEC-11:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 46193.18 | 8532.22 | 10112.62 | 0.00 | 15036.44 | 0.00 | 0.00 | |||||
Maximum of Months | 46193.18 | 8532.22 | 10112.62 | 0.00 | 15036.44 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 13531.43 | 23-JAN-13:50 | 0.00 | 0.00 | 0.00 | 1745.80 | 12-JAN-12:00 | 0.00 |
February | 20960.86 | 07-FEB-13:39 | 0.00 | 0.00 | 0.00 | 1743.02 | 01-FEB-12:09 | 0.00 |
March | 28095.98 | 27-MAR-11:00 | 0.00 | 0.00 | 0.00 | 1730.62 | 01-MAR-12:20 | 0.00 |
April | 36023.47 | 28-APR-11:00 | 0.00 | 0.00 | 0.00 | 1709.34 | 01-APR-11:50 | 0.00 |
May | 41565.62 | 31-MAY-15:00 | 0.00 | 0.00 | 0.00 | 1686.88 | 01-MAY-11:09 | 0.00 |
June | 48966.49 | 09-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1667.98 | 01-JUN-11:30 | 0.00 |
July | 50017.52 | 21-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1659.05 | 31-JUL-11:30 | 0.00 |
August | 56143.93 | 10-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1670.91 | 31-AUG-11:00 | 0.00 |
September | 43597.17 | 06-SEP-15:50 | 0.00 | 0.00 | 0.00 | 1690.32 | 30-SEP-11:09 | 0.00 |
October | 36014.84 | 07-OCT-15:50 | 0.00 | 0.00 | 0.00 | 1713.62 | 31-OCT-11:09 | 0.00 |
November | 29723.65 | 01-NOV-13:00 | 0.00 | 0.00 | 0.00 | 1733.41 | 30-NOV-12:00 | 0.00 |
December | 18085.00 | 06-DEC-13:39 | 0.00 | 0.00 | 0.00 | 1744.50 | 30-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 13531.43 | 0.00 | 0.00 | 0.00 | 1659.05 | 0.00 | ||
Maximum of Months | 56143.93 | 0.00 | 0.00 | 0.00 | 1745.80 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 86577.13 | 23-JAN-13:39 | 46193.18 | 10112.62 | 0.00 | 0.00 | 15036.44 | 0.00 | 0.00 | 13519.18 | 0.00 |
February | 94011.96 | 07-FEB-13:50 | 46193.18 | 10112.62 | 0.00 | 0.00 | 15036.44 | 0.00 | 0.00 | 20956.77 | 0.00 |
March | 100319.11 | 27-MAR-12:09 | 46193.18 | 10112.62 | 0.00 | 0.00 | 15036.44 | 0.00 | 0.00 | 27287.98 | 0.00 |
April | 107305.11 | 28-APR-12:09 | 46193.18 | 10112.62 | 0.00 | 0.00 | 15036.44 | 0.00 | 0.00 | 34294.39 | 0.00 |
May | 111795.84 | 31-MAY-14:39 | 46193.18 | 10112.62 | 0.00 | 0.00 | 15036.44 | 0.00 | 0.00 | 38802.58 | 0.00 |
June | 118233.40 | 09-JUN-14:20 | 46193.18 | 10112.62 | 0.00 | 0.00 | 15036.44 | 0.00 | 0.00 | 45243.86 | 0.00 |
July | 121457.51 | 14-JUL-13:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 15036.44 | 0.00 | 0.00 | 48489.47 | 0.00 |
August | 122979.65 | 10-AUG-15:39 | 40988.70 | 10112.62 | 0.00 | 0.00 | 15036.44 | 0.00 | 0.00 | 55271.26 | 0.00 |
September | 114117.37 | 06-SEP-13:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 15036.44 | 0.00 | 0.00 | 41136.73 | 0.00 |
October | 108300.42 | 07-OCT-13:30 | 46193.18 | 10112.62 | 0.00 | 0.00 | 15036.44 | 0.00 | 0.00 | 35304.56 | 0.00 |
November | 102633.74 | 01-NOV-14:09 | 46193.18 | 10112.62 | 0.00 | 0.00 | 15036.44 | 0.00 | 0.00 | 29601.38 | 0.00 |
December | 91135.94 | 06-DEC-13:39 | 46193.18 | 10112.62 | 0.00 | 0.00 | 15036.44 | 0.00 | 0.00 | 18085.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 86577.13 | 40988.70 | 10112.62 | 0.00 | 0.00 | 15036.44 | 0.00 | 0.00 | 13519.18 | 0.00 | |
Maximum of Months | 122979.65 | 46193.18 | 10112.62 | 0.00 | 0.00 | 15036.44 | 0.00 | 0.00 | 55271.26 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 1154.45 | 02-JAN-07:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 1154.45 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.57 | 0.33 | 24.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.57 | 1.33 | 24.57 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.61 | 1.83 | 24.61 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 25.06 | 4.17 | 24.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 27.44 | 8.67 | 26.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 27.76 | 8.50 | 26.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 28.33 | 28.59 | 9.83 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 28.30 | 10.00 | 27.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 28.14 | 8.67 | 27.36 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 26.86 | 8.33 | 26.16 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 25.01 | 5.17 | 24.85 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.56 | 0.83 | 24.56 |
Annual Sum or Average | 0.00 | 0.00 | 133.83 | 27.66 | 67.67 | 26.85 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.56 | 0.33 | 24.56 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 28.33 | 28.59 | 10.00 | 27.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.58 | 0.00 | 27.58 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.60 | 0.17 | 27.59 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 | 27.74 | 0.00 | 27.74 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 90.50 | 27.90 | 1.17 | 27.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 104.67 | 27.98 | 3.67 | 27.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 115.17 | 28.31 | 4.17 | 28.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 109.50 | 28.31 | 4.50 | 28.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 103.33 | 27.95 | 2.83 | 27.94 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 73.83 | 27.73 | 0.00 | 27.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 27.61 | 0.00 | 27.61 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.46 | 0.00 | 27.46 |
Annual Sum or Average | 0.00 | 0.00 | 668.17 | 28.01 | 16.50 | 28.01 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 115.17 | 28.31 | 4.50 | 28.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 63.17 | 23.39 | 151.50 | 23.75 | 0.00 | 23.75 |
February | 19.67 | 23.37 | 214.33 | 23.86 | 0.67 | 23.86 |
March | 6.83 | 23.81 | 283.50 | 23.91 | 0.83 | 23.91 |
April | 3.00 | 24.12 | 299.33 | 23.92 | 3.00 | 23.92 |
May | 15.50 | 24.26 | 312.00 | 23.95 | 15.50 | 23.96 |
June | 43.00 | 24.20 | 312.00 | 23.98 | 43.00 | 24.00 |
July | 72.67 | 24.16 | 300.00 | 24.00 | 72.67 | 24.03 |
August | 82.17 | 24.15 | 324.00 | 24.00 | 82.17 | 24.03 |
September | 53.50 | 24.20 | 300.00 | 23.99 | 53.50 | 24.02 |
October | 25.33 | 24.18 | 300.00 | 23.95 | 25.33 | 23.97 |
November | 9.33 | 24.08 | 288.00 | 23.92 | 9.33 | 23.93 |
December | 13.67 | 23.71 | 255.67 | 23.90 | 0.67 | 23.90 |
Annual Sum or Average | 407.83 | 23.99 | 3340.33 | 23.94 | 306.67 | 23.96 |
Minimum of Months | 3.00 | 23.37 | 151.50 | 23.75 | 0.00 | 23.75 |
Maximum of Months | 82.17 | 24.26 | 324.00 | 24.00 | 82.17 | 24.03 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 102.50 | 25.03 | 245.50 | 26.12 | 58.83 | 26.17 |
February | 168.00 | 26.25 | 248.00 | 26.45 | 148.00 | 26.50 |
March | 224.17 | 26.61 | 315.67 | 26.60 | 219.33 | 26.62 |
April | 253.83 | 26.69 | 300.00 | 26.68 | 253.83 | 26.68 |
May | 304.50 | 26.71 | 312.00 | 26.71 | 304.50 | 26.71 |
June | 312.00 | 26.71 | 312.00 | 26.71 | 312.00 | 26.71 |
July | 300.00 | 26.71 | 300.00 | 26.71 | 300.00 | 26.71 |
August | 324.00 | 26.72 | 324.00 | 26.72 | 324.00 | 26.72 |
September | 300.00 | 26.71 | 300.00 | 26.71 | 300.00 | 26.71 |
October | 291.00 | 26.71 | 300.00 | 26.71 | 291.00 | 26.71 |
November | 254.17 | 26.69 | 288.00 | 26.67 | 254.17 | 26.68 |
December | 162.50 | 26.32 | 278.00 | 26.47 | 147.17 | 26.51 |
Annual Sum or Average | 2996.67 | 26.60 | 3523.17 | 26.63 | 2912.83 | 26.65 |
Minimum of Months | 102.50 | 25.03 | 245.50 | 26.12 | 58.83 | 26.17 |
Maximum of Months | 324.00 | 26.72 | 324.00 | 26.72 | 324.00 | 26.72 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 250.00 | 25.50 | 254.67 | 25.83 | 212.00 | 25.94 |
February | 249.83 | 27.25 | 243.17 | 27.53 | 219.83 | 27.70 |
March | 294.00 | 29.14 | 283.50 | 29.42 | 258.67 | 29.64 |
April | 279.33 | 32.25 | 290.00 | 32.16 | 272.83 | 32.26 |
May | 312.00 | 36.40 | 312.00 | 36.40 | 312.00 | 36.40 |
June | 312.00 | 37.86 | 312.00 | 37.86 | 312.00 | 37.86 |
July | 300.00 | 39.46 | 300.00 | 39.46 | 300.00 | 39.46 |
August | 324.00 | 39.60 | 324.00 | 39.60 | 324.00 | 39.60 |
September | 300.00 | 36.71 | 300.00 | 36.71 | 300.00 | 36.71 |
October | 296.17 | 33.70 | 300.00 | 33.65 | 296.17 | 33.66 |
November | 272.50 | 30.10 | 274.17 | 30.15 | 261.67 | 30.25 |
December | 263.67 | 26.74 | 263.83 | 26.99 | 232.83 | 27.13 |
Annual Sum or Average | 3453.50 | 33.25 | 3457.33 | 33.34 | 3302.00 | 33.48 |
Minimum of Months | 249.83 | 25.50 | 243.17 | 25.83 | 212.00 | 25.94 |
Maximum of Months | 324.00 | 39.60 | 324.00 | 39.60 | 324.00 | 39.60 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.658385E+10 | 0.176190E+10 | 255.97 | 0.564111E+10 | 0.942745E+09 | 0.00 | 1.00 | 30-JAN-06:01 | 0.00 | 01-JAN-00:10 | 39887.23 | 30-JAN-06:01 | 26882.29 | 30-JAN-06:01 | 13004.94 | 30-JAN-06:01 | 9191.86 | 30-JAN-06:01 | 0.00 | 01-JAN-00:10 |
February | 0.782209E+10 | 0.211220E+10 | 247.77 | 0.656074E+10 | 0.126136E+10 | 0.00 | 1.00 | 06-FEB-06:01 | 0.00 | 01-FEB-00:10 | 41170.02 | 09-FEB-06:01 | 29120.28 | 28-FEB-06:02 | 15052.87 | 09-FEB-06:03 | 9392.83 | 09-FEB-06:01 | 0.00 | 01-FEB-00:10 |
March | 0.111259E+11 | 0.308023E+10 | 310.20 | 0.965724E+10 | 0.146865E+10 | 0.00 | 1.00 | 01-MAR-06:01 | 0.00 | 01-MAR-00:10 | 41825.21 | 29-MAR-05:01 | 36263.11 | 27-MAR-05:01 | 16645.27 | 29-MAR-05:03 | 9489.15 | 29-MAR-05:01 | 0.00 | 01-MAR-00:10 |
April | 0.134276E+11 | 0.386949E+10 | 306.38 | 0.114392E+11 | 0.198846E+10 | 0.00 | 1.00 | 01-APR-05:01 | 0.00 | 01-APR-00:10 | 42152.68 | 20-APR-05:01 | 36344.36 | 25-APR-05:01 | 17170.49 | 12-APR-05:03 | 9535.70 | 20-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.191704E+11 | 0.585693E+10 | 367.98 | 0.160805E+11 | 0.308988E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 44649.32 | 25-MAY-05:01 | 36264.84 | 05-MAY-05:01 | 23804.91 | 24-MAY-05:04 | 10766.09 | 31-MAY-18:11 | 0.00 | 01-MAY-00:10 |
June | 0.232513E+11 | 0.711537E+10 | 395.69 | 0.177310E+11 | 0.552032E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 44317.32 | 08-JUN-05:01 | 33122.34 | 16-JUN-05:01 | 25192.14 | 20-JUN-05:06 | 10695.97 | 18-JUN-15:31 | 0.00 | 01-JUN-00:10 |
July | 0.267230E+11 | 0.826816E+10 | 486.39 | 0.192834E+11 | 0.743953E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 43087.47 | 29-JUL-05:02 | 35057.81 | 03-JUL-05:01 | 24594.66 | 06-JUL-05:07 | 10481.26 | 15-JUL-05:01 | 0.00 | 01-JUL-00:10 |
August | 0.295562E+11 | 0.913148E+10 | 505.69 | 0.210101E+11 | 0.854607E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:05 | 43087.47 | 31-AUG-05:01 | 32178.76 | 06-AUG-15:31 | 24711.33 | 08-AUG-05:07 | 11083.21 | 06-AUG-14:51 | 0.00 | 01-AUG-00:05 |
September | 0.232616E+11 | 0.695326E+10 | 395.64 | 0.169010E+11 | 0.636062E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 45043.40 | 25-SEP-05:01 | 29153.72 | 13-SEP-05:01 | 25412.74 | 23-SEP-05:05 | 10707.52 | 10-SEP-13:31 | 0.00 | 01-SEP-00:10 |
October | 0.183933E+11 | 0.532421E+10 | 339.24 | 0.142939E+11 | 0.409944E+10 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 44617.38 | 17-OCT-05:02 | 34181.97 | 20-OCT-05:01 | 24971.14 | 07-OCT-05:05 | 10012.82 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.135762E+11 | 0.376971E+10 | 290.95 | 0.107728E+11 | 0.280346E+10 | 0.00 | 1.00 | 01-NOV-05:01 | 0.00 | 01-NOV-00:10 | 44066.06 | 03-NOV-05:01 | 32312.68 | 18-NOV-06:01 | 19832.26 | 03-NOV-05:05 | 9786.42 | 03-NOV-05:01 | 0.00 | 01-NOV-00:10 |
December | 0.912386E+10 | 0.244478E+10 | 277.65 | 0.750423E+10 | 0.161963E+10 | 0.00 | 1.00 | 01-DEC-06:02 | 0.00 | 01-DEC-00:10 | 41097.43 | 06-DEC-06:01 | 32144.00 | 01-DEC-06:02 | 16205.97 | 06-DEC-06:03 | 9381.90 | 06-DEC-06:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.202015E+12 | 0.596878E+11 | 4179.57 | 0.156875E+12 | 0.451401E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.658385E+10 | 0.176190E+10 | 247.77 | 0.564111E+10 | 0.942745E+09 | 0.00 | 1.00 | 0.00 | 39887.23 | 26882.29 | 13004.94 | 9191.86 | 0.00 | |||||||
Maximum of Months | 0.295562E+11 | 0.913148E+10 | 505.69 | 0.210101E+11 | 0.854607E+10 | 0.00 | 1.00 | 0.00 | 45043.40 | 36344.36 | 25412.74 | 11083.21 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.159497E+11 | 0.466559E+10 | 226.53 | 0.135544E+11 | 0.239529E+10 | 0.00 | 0.24 | 23-JAN-13:40 | 0.00 | 01-JAN-00:10 | 37374.91 | 29-JAN-15:15 | 32584.98 | 28-JAN-14:00 | 9558.57 | 29-JAN-13:20 | 10843.19 | 29-JAN-15:15 | 0.00 | 01-JAN-00:10 |
February | 0.223975E+11 | 0.664388E+10 | 238.62 | 0.189165E+11 | 0.348101E+10 | 0.00 | 0.86 | 05-FEB-14:23 | 0.00 | 01-FEB-00:10 | 132382.26 | 05-FEB-13:43 | 123112.80 | 05-FEB-14:23 | 13441.71 | 07-FEB-18:10 | 39512.90 | 05-FEB-14:23 | 0.00 | 01-FEB-00:10 |
March | 0.376736E+11 | 0.114736E+11 | 339.29 | 0.329864E+11 | 0.468722E+10 | 0.00 | 1.00 | 26-MAR-16:02 | 0.00 | 01-MAR-00:10 | 154164.54 | 26-MAR-16:02 | 154164.54 | 26-MAR-16:02 | 21915.74 | 28-MAR-17:08 | 45325.49 | 26-MAR-16:02 | 0.00 | 01-MAR-00:10 |
April | 0.571513E+11 | 0.180589E+11 | 439.87 | 0.491753E+11 | 0.797595E+10 | 0.00 | 1.00 | 23-APR-17:02 | 0.00 | 01-APR-00:10 | 177457.57 | 30-APR-15:42 | 153409.71 | 23-APR-17:02 | 51417.57 | 30-APR-15:42 | 49411.04 | 30-APR-12:22 | 0.00 | 01-APR-00:10 |
May | 0.949391E+11 | 0.316421E+11 | 584.59 | 0.812875E+11 | 0.136515E+11 | 0.00 | 1.00 | 04-MAY-17:04 | 0.00 | 01-MAY-00:15 | 178480.77 | 29-MAY-13:42 | 152075.39 | 07-MAY-15:42 | 56171.72 | 24-MAY-19:42 | 52783.58 | 31-MAY-18:22 | 0.00 | 01-MAY-00:10 |
June | 0.116039E+12 | 0.386860E+11 | 581.23 | 0.910861E+11 | 0.249531E+11 | 0.00 | 1.00 | 01-JUN-17:04 | 0.00 | 01-JUN-00:12 | 185758.84 | 09-JUN-05:01 | 150519.95 | 20-JUN-17:42 | 77934.20 | 09-JUN-05:01 | 52941.86 | 09-JUN-17:42 | 0.00 | 01-JUN-00:10 |
July | 0.138396E+12 | 0.469328E+11 | 602.77 | 0.105376E+12 | 0.330203E+11 | 0.00 | 1.00 | 01-JUL-17:04 | 0.00 | 01-JUL-00:12 | 184484.97 | 18-JUL-05:01 | 150128.04 | 04-JUL-10:22 | 71259.06 | 18-JUL-05:01 | 55073.07 | 30-JUL-13:01 | 0.00 | 01-JUL-00:10 |
August | 0.145559E+12 | 0.492953E+11 | 610.69 | 0.109089E+12 | 0.364700E+11 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:12 | 191296.36 | 08-AUG-05:01 | 145792.38 | 06-AUG-09:42 | 86392.63 | 08-AUG-05:01 | 54945.04 | 10-AUG-17:42 | 0.00 | 01-AUG-00:05 |
September | 0.113199E+12 | 0.370820E+11 | 578.76 | 0.851185E+11 | 0.280809E+11 | 0.00 | 1.00 | 01-SEP-17:04 | 0.00 | 01-SEP-00:12 | 183813.28 | 10-SEP-17:42 | 147602.92 | 04-SEP-12:22 | 72169.46 | 10-SEP-17:42 | 53210.34 | 04-SEP-14:21 | 0.00 | 01-SEP-00:10 |
October | 0.822701E+11 | 0.262359E+11 | 560.80 | 0.656093E+11 | 0.166608E+11 | 0.00 | 1.00 | 01-OCT-11:42 | 0.00 | 01-OCT-00:13 | 180240.68 | 08-OCT-09:02 | 152812.54 | 15-OCT-14:22 | 63943.19 | 01-OCT-19:03 | 50252.18 | 07-OCT-17:05 | 0.00 | 01-OCT-00:10 |
November | 0.478067E+11 | 0.146619E+11 | 378.80 | 0.387018E+11 | 0.910490E+10 | 0.00 | 0.86 | 05-NOV-14:02 | 0.00 | 01-NOV-00:15 | 132649.37 | 05-NOV-14:02 | 124675.32 | 05-NOV-13:22 | 43341.87 | 03-NOV-05:01 | 40357.67 | 05-NOV-14:02 | 0.00 | 01-NOV-00:10 |
December | 0.245689E+11 | 0.722836E+10 | 261.60 | 0.201801E+11 | 0.438885E+10 | 0.00 | 0.54 | 03-DEC-14:13 | 0.00 | 01-DEC-00:10 | 84216.17 | 03-DEC-14:13 | 69991.50 | 10-DEC-12:43 | 18859.60 | 24-DEC-13:30 | 24322.04 | 10-DEC-12:43 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.895951E+12 | 0.292606E+12 | 5403.55 | 0.711081E+12 | 0.184870E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.159497E+11 | 0.466559E+10 | 226.53 | 0.135544E+11 | 0.239529E+10 | 0.00 | 0.24 | 0.00 | 37374.91 | 32584.98 | 9558.57 | 10843.19 | 0.00 | |||||||
Maximum of Months | 0.145559E+12 | 0.492953E+11 | 610.69 | 0.109089E+12 | 0.364700E+11 | 0.00 | 1.00 | 0.00 | 191296.36 | 154164.54 | 86392.63 | 55073.07 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.12 | 12.48 | 30.64 | 80.86 | 115.37 | 0.00 | 0.00 | 0.00 |
February | 49.17 | 14.14 | 35.02 | 105.09 | 102.57 | 0.00 | 0.00 | 0.00 |
March | 58.02 | 17.19 | 40.83 | 147.94 | 84.15 | 0.00 | 0.00 | 0.00 |
April | 63.18 | 17.61 | 45.57 | 195.65 | 61.12 | 0.00 | 0.00 | 0.00 |
May | 68.87 | 20.56 | 48.31 | 268.18 | 24.48 | 0.00 | 0.00 | 0.00 |
June | 71.29 | 22.52 | 48.78 | 294.90 | 11.95 | 0.00 | 0.00 | 0.00 |
July | 65.54 | 18.85 | 46.69 | 314.73 | 1.97 | 0.00 | 0.00 | 0.00 |
August | 66.90 | 20.23 | 46.67 | 322.98 | 1.27 | 0.00 | 0.00 | 0.00 |
September | 63.74 | 20.00 | 43.75 | 260.83 | 14.85 | 0.00 | 0.00 | 0.00 |
October | 56.72 | 18.32 | 38.39 | 199.68 | 38.08 | 0.00 | 0.00 | 0.00 |
November | 48.88 | 16.05 | 32.83 | 139.56 | 72.27 | 0.00 | 0.00 | 0.00 |
December | 40.99 | 12.52 | 28.47 | 87.30 | 105.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.07 | 17.55 | 40.52 | 202.03 | 52.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 40.99 | 12.48 | 28.47 | 80.86 | 1.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.29 | 22.52 | 48.78 | 322.98 | 115.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.12 | 12.48 | 30.64 | 80.86 | 115.37 | 0.00 | 0.00 | 0.00 |
February | 49.17 | 14.14 | 35.02 | 105.09 | 102.57 | 0.00 | 0.00 | 0.00 |
March | 58.02 | 17.19 | 40.83 | 147.94 | 84.15 | 0.00 | 0.00 | 0.00 |
April | 63.18 | 17.61 | 45.57 | 195.65 | 61.12 | 0.00 | 0.00 | 0.00 |
May | 68.87 | 20.56 | 48.31 | 268.18 | 24.48 | 0.00 | 0.00 | 0.00 |
June | 71.29 | 22.52 | 48.78 | 294.90 | 11.95 | 0.00 | 0.00 | 0.00 |
July | 65.54 | 18.85 | 46.69 | 314.73 | 1.97 | 0.00 | 0.00 | 0.00 |
August | 66.90 | 20.23 | 46.67 | 322.98 | 1.27 | 0.00 | 0.00 | 0.00 |
September | 63.74 | 20.00 | 43.75 | 260.83 | 14.85 | 0.00 | 0.00 | 0.00 |
October | 56.72 | 18.32 | 38.39 | 199.68 | 38.08 | 0.00 | 0.00 | 0.00 |
November | 48.88 | 16.05 | 32.83 | 139.56 | 72.27 | 0.00 | 0.00 | 0.00 |
December | 40.99 | 12.52 | 28.47 | 87.30 | 105.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.07 | 17.55 | 40.52 | 202.03 | 52.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 40.99 | 12.48 | 28.47 | 80.86 | 1.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.29 | 22.52 | 48.78 | 322.98 | 115.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.10 | 0.00 | 14.10 | 17.75 | 69.01 | 0.00 | 0.00 | 0.00 |
February | 16.16 | 0.00 | 16.16 | 26.63 | 61.46 | 0.00 | 0.00 | 0.00 |
March | 18.57 | 0.00 | 18.56 | 42.46 | 49.81 | 0.00 | 0.00 | 0.00 |
April | 20.98 | 0.10 | 20.89 | 67.24 | 35.29 | 0.00 | 0.00 | 0.00 |
May | 23.89 | 1.04 | 22.85 | 106.79 | 13.48 | 0.00 | 0.00 | 0.00 |
June | 25.65 | 1.85 | 23.79 | 124.16 | 6.97 | 0.00 | 0.00 | 0.00 |
July | 23.41 | 0.94 | 22.47 | 138.89 | 1.12 | 0.00 | 0.00 | 0.00 |
August | 21.70 | 0.35 | 21.36 | 136.09 | 0.64 | 0.00 | 0.00 | 0.00 |
September | 19.62 | 0.01 | 19.61 | 98.65 | 8.36 | 0.00 | 0.00 | 0.00 |
October | 17.38 | 0.00 | 17.38 | 68.70 | 21.92 | 0.00 | 0.00 | 0.00 |
November | 14.92 | 0.00 | 14.92 | 40.94 | 42.18 | 0.00 | 0.00 | 0.00 |
December | 13.16 | 0.00 | 13.16 | 20.45 | 62.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 19.14 | 0.36 | 18.78 | 74.36 | 30.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.16 | 0.00 | 13.16 | 17.75 | 0.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 25.65 | 1.85 | 23.79 | 138.89 | 69.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.10 | 0.00 | 14.10 | 17.75 | 69.01 | 0.00 | 0.00 | 0.00 |
February | 16.16 | 0.00 | 16.16 | 26.63 | 61.46 | 0.00 | 0.00 | 0.00 |
March | 18.56 | 0.00 | 18.56 | 42.46 | 49.81 | 0.00 | 0.00 | 0.00 |
April | 20.98 | 0.10 | 20.89 | 67.24 | 35.29 | 0.00 | 0.00 | 0.00 |
May | 23.89 | 1.04 | 22.85 | 106.78 | 13.48 | 0.00 | 0.00 | 0.00 |
June | 25.64 | 1.85 | 23.79 | 124.16 | 6.97 | 0.00 | 0.00 | 0.00 |
July | 23.40 | 0.94 | 22.47 | 138.89 | 1.12 | 0.00 | 0.00 | 0.00 |
August | 21.70 | 0.35 | 21.36 | 136.09 | 0.64 | 0.00 | 0.00 | 0.00 |
September | 19.62 | 0.01 | 19.61 | 98.65 | 8.36 | 0.00 | 0.00 | 0.00 |
October | 17.38 | 0.00 | 17.38 | 68.70 | 21.92 | 0.00 | 0.00 | 0.00 |
November | 14.92 | 0.00 | 14.92 | 40.94 | 42.18 | 0.00 | 0.00 | 0.00 |
December | 13.16 | 0.00 | 13.16 | 20.45 | 62.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 19.14 | 0.36 | 18.78 | 74.36 | 30.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.16 | 0.00 | 13.16 | 17.75 | 0.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 25.64 | 1.85 | 23.79 | 138.89 | 69.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 78.48 | 45.55 | 69.50 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 97.59 | 45.03 | 53.50 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 121.18 | 46.19 | 15.17 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 145.87 | 45.89 | 19.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 166.25 | 39.17 | 5.83 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 172.75 | 37.90 | 8.83 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 169.32 | 34.34 | 3.17 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 160.42 | 34.81 | 9.17 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 143.65 | 39.36 | 31.83 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 119.25 | 44.86 | 45.33 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 93.25 | 46.69 | 43.83 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 73.97 | 44.94 | 83.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 128.64 | 42.03 | 388.33 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 73.97 | 34.34 | 3.17 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 172.75 | 46.69 | 83.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 78.48 | 45.55 | 69.50 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 97.59 | 45.03 | 53.50 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 121.18 | 46.19 | 15.17 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 145.87 | 45.89 | 19.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 166.25 | 39.17 | 5.83 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 172.75 | 37.90 | 8.83 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 169.32 | 34.34 | 3.17 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 160.42 | 34.81 | 9.17 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 143.65 | 39.36 | 31.83 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 119.25 | 44.86 | 45.33 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 93.25 | 46.69 | 43.83 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 73.97 | 44.94 | 83.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 128.64 | 42.03 | 388.33 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 73.97 | 34.34 | 3.17 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 172.75 | 46.69 | 83.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 78.48 | 45.55 | 69.50 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 97.59 | 45.03 | 53.50 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 121.18 | 46.19 | 15.17 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 145.87 | 45.89 | 19.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 166.25 | 39.17 | 5.83 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 172.75 | 37.90 | 8.83 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 169.32 | 34.34 | 3.17 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 160.42 | 34.81 | 9.17 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 143.65 | 39.36 | 31.83 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 119.25 | 44.86 | 45.33 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 93.25 | 46.69 | 43.83 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 73.97 | 44.94 | 83.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 128.64 | 42.03 | 388.33 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 73.97 | 34.34 | 3.17 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 172.75 | 46.69 | 83.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 78.48 | 45.55 | 69.50 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 97.59 | 45.03 | 53.50 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 121.18 | 46.19 | 15.17 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 145.87 | 45.89 | 19.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 166.25 | 39.17 | 5.83 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 172.75 | 37.90 | 8.83 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 169.32 | 34.34 | 3.17 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 160.42 | 34.81 | 9.17 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 143.65 | 39.36 | 31.83 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 119.25 | 44.86 | 45.33 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 93.25 | 46.69 | 43.83 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 73.97 | 44.94 | 83.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 128.64 | 42.03 | 388.33 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 73.97 | 34.34 | 3.17 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 172.75 | 46.69 | 83.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 78.48 | 45.55 | 69.50 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 97.59 | 45.03 | 53.50 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 121.18 | 46.19 | 15.17 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 145.87 | 45.89 | 19.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 166.25 | 39.17 | 5.83 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 172.75 | 37.90 | 8.83 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 169.32 | 34.34 | 3.17 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 160.42 | 34.81 | 9.17 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 143.65 | 39.36 | 31.83 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 119.25 | 44.86 | 45.33 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 93.25 | 46.69 | 43.83 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 73.97 | 44.94 | 83.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 128.64 | 42.03 | 388.33 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 73.97 | 34.34 | 3.17 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 172.75 | 46.69 | 83.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 78.48 | 45.55 | 69.50 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 97.59 | 45.03 | 53.50 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 121.18 | 46.19 | 15.17 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 145.87 | 45.89 | 19.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 166.25 | 39.17 | 5.83 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 172.75 | 37.90 | 8.83 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 169.32 | 34.34 | 3.17 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 160.42 | 34.81 | 9.17 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 143.65 | 39.36 | 31.83 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 119.25 | 44.86 | 45.33 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 93.25 | 46.69 | 43.83 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 73.97 | 44.94 | 83.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 128.64 | 42.03 | 388.33 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 73.97 | 34.34 | 3.17 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 172.75 | 46.69 | 83.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 78.48 | 45.55 | 69.50 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 97.59 | 45.03 | 53.50 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 121.18 | 46.19 | 15.17 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 145.87 | 45.89 | 19.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 166.25 | 39.17 | 5.83 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 172.75 | 37.90 | 8.83 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 169.32 | 34.34 | 3.17 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 160.42 | 34.81 | 9.17 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 143.65 | 39.36 | 31.83 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 119.25 | 44.86 | 45.33 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 93.25 | 46.69 | 43.83 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 73.97 | 44.94 | 83.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 128.64 | 42.03 | 388.33 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 73.97 | 34.34 | 3.17 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 172.75 | 46.69 | 83.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 78.48 | 45.55 | 69.50 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 97.59 | 45.03 | 53.50 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 121.18 | 46.19 | 15.17 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 145.87 | 45.89 | 19.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 166.25 | 39.17 | 5.83 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 172.75 | 37.90 | 8.83 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 169.32 | 34.34 | 3.17 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 160.42 | 34.81 | 9.17 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 143.65 | 39.36 | 31.83 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 119.25 | 44.86 | 45.33 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 93.25 | 46.69 | 43.83 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 73.97 | 44.94 | 83.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 128.64 | 42.03 | 388.33 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 73.97 | 34.34 | 3.17 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 172.75 | 46.69 | 83.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 78.48 | 45.55 | 69.50 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 97.59 | 45.03 | 53.50 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 121.18 | 46.19 | 15.17 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 145.87 | 45.89 | 19.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 166.25 | 39.17 | 5.83 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 172.75 | 37.90 | 8.83 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 169.32 | 34.34 | 3.17 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 160.42 | 34.81 | 9.17 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 143.65 | 39.36 | 31.83 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 119.25 | 44.86 | 45.33 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 93.25 | 46.69 | 43.83 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 73.97 | 44.94 | 83.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 128.64 | 42.03 | 388.33 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 73.97 | 34.34 | 3.17 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 172.75 | 46.69 | 83.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 78.48 | 45.55 | 69.50 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 97.59 | 45.03 | 53.50 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 121.18 | 46.19 | 15.17 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 145.87 | 45.89 | 19.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 166.25 | 39.17 | 5.83 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 172.75 | 37.90 | 8.83 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 169.32 | 34.34 | 3.17 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 160.42 | 34.81 | 9.17 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 143.65 | 39.36 | 31.83 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 119.25 | 44.86 | 45.33 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 93.25 | 46.69 | 43.83 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 73.97 | 44.94 | 83.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 128.64 | 42.03 | 388.33 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 73.97 | 34.34 | 3.17 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 172.75 | 46.69 | 83.17 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115499E+09 | 33430114.87 | 82069350.32 | 0.216564E+09 | 0.309014E+09 |
February | 0.118943E+09 | 34211376.74 | 84731438.60 | 0.254229E+09 | 0.248137E+09 |
March | 0.155399E+09 | 46040397.02 | 0.109359E+09 | 0.396240E+09 | 0.225392E+09 |
April | 0.163755E+09 | 45644833.27 | 0.118110E+09 | 0.507132E+09 | 0.158436E+09 |
May | 0.184463E+09 | 55070047.26 | 0.129393E+09 | 0.718305E+09 | 65580075.11 |
June | 0.184790E+09 | 58358977.90 | 0.126431E+09 | 0.764381E+09 | 30962674.99 |
July | 0.175542E+09 | 50493352.68 | 0.125049E+09 | 0.842964E+09 | 5265380.52 |
August | 0.179188E+09 | 54196184.91 | 0.124992E+09 | 0.865072E+09 | 3390785.73 |
September | 0.165224E+09 | 51829243.54 | 0.113395E+09 | 0.676069E+09 | 38500846.73 |
October | 0.151910E+09 | 49076778.40 | 0.102833E+09 | 0.534816E+09 | 0.101986E+09 |
November | 0.126705E+09 | 41610043.46 | 85095231.67 | 0.361732E+09 | 0.187330E+09 |
December | 0.109780E+09 | 33526329.08 | 76253413.23 | 0.233828E+09 | 0.281545E+09 |
Annual Sum or Average | 0.183120E+10 | 0.553488E+09 | 0.127771E+10 | 0.637133E+10 | 0.165554E+10 |
Minimum of Months | 0.109780E+09 | 33430114.87 | 76253413.23 | 0.216564E+09 | 3390785.73 |
Maximum of Months | 0.184790E+09 | 58358977.90 | 0.129393E+09 | 0.865072E+09 | 0.309014E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115499E+09 | 33430114.87 | 82069350.32 | 0.216564E+09 | 0.309014E+09 |
February | 0.118943E+09 | 34211376.74 | 84731438.60 | 0.254229E+09 | 0.248137E+09 |
March | 0.155399E+09 | 46040397.02 | 0.109359E+09 | 0.396240E+09 | 0.225392E+09 |
April | 0.163755E+09 | 45644833.27 | 0.118110E+09 | 0.507132E+09 | 0.158436E+09 |
May | 0.184463E+09 | 55070047.26 | 0.129393E+09 | 0.718305E+09 | 65580075.11 |
June | 0.184790E+09 | 58358977.90 | 0.126431E+09 | 0.764381E+09 | 30962674.99 |
July | 0.175542E+09 | 50493352.68 | 0.125049E+09 | 0.842964E+09 | 5265380.52 |
August | 0.179188E+09 | 54196184.91 | 0.124992E+09 | 0.865072E+09 | 3390785.73 |
September | 0.165224E+09 | 51829243.54 | 0.113395E+09 | 0.676069E+09 | 38500846.73 |
October | 0.151910E+09 | 49076778.40 | 0.102833E+09 | 0.534816E+09 | 0.101986E+09 |
November | 0.126705E+09 | 41610043.46 | 85095231.67 | 0.361732E+09 | 0.187330E+09 |
December | 0.109780E+09 | 33526329.08 | 76253413.23 | 0.233828E+09 | 0.281545E+09 |
Annual Sum or Average | 0.183120E+10 | 0.553488E+09 | 0.127771E+10 | 0.637133E+10 | 0.165554E+10 |
Minimum of Months | 0.109780E+09 | 33430114.87 | 76253413.23 | 0.216564E+09 | 3390785.73 |
Maximum of Months | 0.184790E+09 | 58358977.90 | 0.129393E+09 | 0.865072E+09 | 0.309014E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37757180.39 | 0.00 | 37757180.39 | 47536541.61 | 0.184836E+09 |
February | 39092110.75 | 0.00 | 39092110.75 | 64421781.55 | 0.148694E+09 |
March | 49725459.30 | 4356.41 | 49721102.89 | 0.113732E+09 | 0.133420E+09 |
April | 54391648.46 | 253761.02 | 54137887.44 | 0.174287E+09 | 91479185.66 |
May | 63986555.05 | 2775915.28 | 61210639.76 | 0.286016E+09 | 36099010.05 |
June | 66473330.18 | 4799522.49 | 61673807.69 | 0.321826E+09 | 18056022.64 |
July | 62688753.09 | 2515175.01 | 60173578.08 | 0.372006E+09 | 3011781.55 |
August | 58130145.26 | 927816.44 | 57202328.83 | 0.364498E+09 | 1713390.16 |
September | 50851213.01 | 23723.51 | 50827489.50 | 0.255701E+09 | 21667384.76 |
October | 46560892.55 | 0.00 | 46560892.55 | 0.184018E+09 | 58711875.84 |
November | 38682121.08 | 0.00 | 38682121.08 | 0.106127E+09 | 0.109327E+09 |
December | 35241442.63 | 0.00 | 35241442.63 | 54782069.67 | 0.167868E+09 |
Annual Sum or Average | 0.603581E+09 | 11300270.16 | 0.592281E+09 | 0.234495E+10 | 0.974884E+09 |
Minimum of Months | 35241442.63 | 0.00 | 35241442.63 | 47536541.61 | 1713390.16 |
Maximum of Months | 66473330.18 | 4799522.49 | 61673807.69 | 0.372006E+09 | 0.184836E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37755941.24 | 0.00 | 37755941.24 | 47534433.77 | 0.184834E+09 |
February | 39090851.70 | 0.00 | 39090851.70 | 64419525.99 | 0.148693E+09 |
March | 49723882.49 | 4356.21 | 49719526.28 | 0.113729E+09 | 0.133418E+09 |
April | 54389956.29 | 253749.12 | 54136207.16 | 0.174284E+09 | 91477493.74 |
May | 63984550.27 | 2775785.17 | 61208765.09 | 0.286013E+09 | 36097728.57 |
June | 66471214.63 | 4799297.53 | 61671917.10 | 0.321822E+09 | 18055025.11 |
July | 62686814.52 | 2515057.12 | 60171757.40 | 0.372003E+09 | 3011454.08 |
August | 58128378.47 | 927772.95 | 57200605.52 | 0.364496E+09 | 1713176.62 |
September | 50849669.28 | 23722.39 | 50825946.88 | 0.255699E+09 | 21666348.84 |
October | 46559448.55 | 0.00 | 46559448.55 | 0.184015E+09 | 58710017.63 |
November | 38680887.14 | 0.00 | 38680887.14 | 0.106124E+09 | 0.109325E+09 |
December | 35240285.69 | 0.00 | 35240285.69 | 54780100.46 | 0.167867E+09 |
Annual Sum or Average | 0.603562E+09 | 11299740.50 | 0.592262E+09 | 0.234492E+10 | 0.974868E+09 |
Minimum of Months | 35240285.69 | 0.00 | 35240285.69 | 47534433.77 | 1713176.62 |
Maximum of Months | 66471214.63 | 4799297.53 | 61671917.10 | 0.372003E+09 | 0.184834E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.210191E+09 | 0.122014E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.236080E+09 | 0.108936E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.324557E+09 | 0.123706E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.378093E+09 | 0.118951E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.445293E+09 | 0.104921E+09 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.447766E+09 | 98240783.13 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.453519E+09 | 91976307.17 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.429679E+09 | 93234564.81 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.372341E+09 | 0.102016E+09 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.319392E+09 | 0.120149E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.241701E+09 | 0.121011E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.198116E+09 | 0.120356E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.405673E+10 | 0.132551E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.198116E+09 | 91976307.17 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.453519E+09 | 0.123706E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.210191E+09 | 0.122014E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.236080E+09 | 0.108936E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.324557E+09 | 0.123706E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.378093E+09 | 0.118951E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.445293E+09 | 0.104921E+09 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.447766E+09 | 98240783.13 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.453519E+09 | 91976307.17 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.429679E+09 | 93234564.81 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.372341E+09 | 0.102016E+09 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.319392E+09 | 0.120149E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.241701E+09 | 0.121011E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.198116E+09 | 0.120356E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.405673E+10 | 0.132551E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.198116E+09 | 91976307.17 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.453519E+09 | 0.123706E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.210191E+09 | 0.122014E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.236080E+09 | 0.108936E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.324557E+09 | 0.123706E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.378093E+09 | 0.118951E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.445293E+09 | 0.104921E+09 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.447766E+09 | 98240783.13 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.453519E+09 | 91976307.17 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.429679E+09 | 93234564.81 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.372341E+09 | 0.102016E+09 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.319392E+09 | 0.120149E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.241701E+09 | 0.121011E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.198116E+09 | 0.120356E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.405673E+10 | 0.132551E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.198116E+09 | 91976307.17 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.453519E+09 | 0.123706E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.210191E+09 | 0.122014E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.236080E+09 | 0.108936E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.324557E+09 | 0.123706E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.378093E+09 | 0.118951E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.445293E+09 | 0.104921E+09 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.447766E+09 | 98240783.13 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.453519E+09 | 91976307.17 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.429679E+09 | 93234564.81 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.372341E+09 | 0.102016E+09 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.319392E+09 | 0.120149E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.241701E+09 | 0.121011E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.198116E+09 | 0.120356E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.405673E+10 | 0.132551E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.198116E+09 | 91976307.17 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.453519E+09 | 0.123706E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.210191E+09 | 0.122014E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.236080E+09 | 0.108936E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.324557E+09 | 0.123706E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.378093E+09 | 0.118951E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.445293E+09 | 0.104921E+09 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.447766E+09 | 98240783.13 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.453519E+09 | 91976307.17 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.429679E+09 | 93234564.81 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.372341E+09 | 0.102016E+09 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.319392E+09 | 0.120149E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.241701E+09 | 0.121011E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.198116E+09 | 0.120356E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.405673E+10 | 0.132551E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.198116E+09 | 91976307.17 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.453519E+09 | 0.123706E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.210191E+09 | 0.122014E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.236080E+09 | 0.108936E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.324557E+09 | 0.123706E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.378093E+09 | 0.118951E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.445293E+09 | 0.104921E+09 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.447766E+09 | 98240783.13 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.453519E+09 | 91976307.17 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.429679E+09 | 93234564.81 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.372341E+09 | 0.102016E+09 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.319392E+09 | 0.120149E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.241701E+09 | 0.121011E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.198116E+09 | 0.120356E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.405673E+10 | 0.132551E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.198116E+09 | 91976307.17 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.453519E+09 | 0.123706E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.210191E+09 | 0.122014E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.236080E+09 | 0.108936E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.324557E+09 | 0.123706E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.378093E+09 | 0.118951E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.445293E+09 | 0.104921E+09 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.447766E+09 | 98240783.13 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.453519E+09 | 91976307.17 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.429679E+09 | 93234564.81 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.372341E+09 | 0.102016E+09 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.319392E+09 | 0.120149E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.241701E+09 | 0.121011E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.198116E+09 | 0.120356E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.405673E+10 | 0.132551E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.198116E+09 | 91976307.17 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.453519E+09 | 0.123706E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.210191E+09 | 0.122014E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.236080E+09 | 0.108936E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.324557E+09 | 0.123706E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.378093E+09 | 0.118951E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.445293E+09 | 0.104921E+09 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.447766E+09 | 98240783.13 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.453519E+09 | 91976307.17 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.429679E+09 | 93234564.81 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.372341E+09 | 0.102016E+09 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.319392E+09 | 0.120149E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.241701E+09 | 0.121011E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.198116E+09 | 0.120356E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.405673E+10 | 0.132551E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.198116E+09 | 91976307.17 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.453519E+09 | 0.123706E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.210191E+09 | 0.122014E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.236080E+09 | 0.108936E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.324557E+09 | 0.123706E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.378093E+09 | 0.118951E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.445293E+09 | 0.104921E+09 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.447766E+09 | 98240783.13 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.453519E+09 | 91976307.17 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.429679E+09 | 93234564.81 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.372341E+09 | 0.102016E+09 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.319392E+09 | 0.120149E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.241701E+09 | 0.121011E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.198116E+09 | 0.120356E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.405673E+10 | 0.132551E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.198116E+09 | 91976307.17 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.453519E+09 | 0.123706E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.210191E+09 | 0.122014E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.236080E+09 | 0.108936E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.324557E+09 | 0.123706E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.378093E+09 | 0.118951E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.445293E+09 | 0.104921E+09 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.447766E+09 | 98240783.13 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.453519E+09 | 91976307.17 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.429679E+09 | 93234564.81 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.372341E+09 | 0.102016E+09 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.319392E+09 | 0.120149E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.241701E+09 | 0.121011E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.198116E+09 | 0.120356E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.405673E+10 | 0.132551E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.198116E+09 | 91976307.17 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.453519E+09 | 0.123706E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 192.86 | 364.41 | 114.44 | 24.96 | 89.48 | 0.00 | 0.00 |
February | 260.33 | 324.96 | 130.65 | 28.28 | 102.37 | 0.00 | 0.00 |
March | 378.94 | 266.06 | 153.17 | 34.38 | 118.79 | 0.00 | 0.00 |
April | 525.37 | 192.42 | 168.32 | 35.42 | 132.91 | 0.00 | 0.00 |
May | 749.45 | 75.43 | 185.52 | 43.19 | 142.33 | 0.00 | 0.00 |
June | 837.78 | 37.48 | 193.88 | 48.73 | 145.14 | 0.00 | 0.00 |
July | 907.18 | 6.12 | 177.89 | 39.58 | 138.31 | 0.00 | 0.00 |
August | 918.11 | 3.79 | 177.21 | 41.16 | 136.05 | 0.00 | 0.00 |
September | 718.91 | 46.38 | 166.72 | 40.01 | 126.71 | 0.00 | 0.00 |
October | 536.74 | 119.97 | 148.20 | 36.65 | 111.55 | 0.00 | 0.00 |
November | 360.53 | 228.43 | 127.61 | 32.11 | 95.51 | 0.00 | 0.00 |
December | 213.08 | 333.15 | 108.29 | 25.03 | 83.25 | 0.00 | 0.00 |
Annual Sum or Average | 551.65 | 165.69 | 154.41 | 35.82 | 118.59 | 0.00 | 0.00 |
Minimum of Months | 192.86 | 3.79 | 108.29 | 24.96 | 83.25 | 0.00 | 0.00 |
Maximum of Months | 918.11 | 364.41 | 193.88 | 48.73 | 145.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5769.87 | 1656.69 | 688.07 | 263.74 | 424.33 | 0.00 | 0.00 |
February | 7391.06 | 1640.58 | 834.27 | 340.95 | 493.32 | 0.00 | 0.00 |
March | 7440.76 | 1805.02 | 1008.94 | 423.52 | 585.43 | 0.00 | 0.00 |
April | 8063.56 | 2151.36 | 1189.40 | 527.27 | 662.13 | 0.00 | 0.00 |
May | 9840.25 | 2619.77 | 1349.58 | 656.27 | 693.32 | 0.00 | 0.00 |
June | 9678.42 | 2844.94 | 1406.77 | 715.43 | 691.33 | 0.00 | 0.00 |
July | 10634.35 | 2929.07 | 1364.65 | 692.39 | 672.26 | 0.00 | 0.00 |
August | 9402.65 | 2997.96 | 1299.88 | 638.77 | 661.11 | 0.00 | 0.00 |
September | 8371.59 | 2836.27 | 1166.61 | 559.79 | 606.83 | 0.00 | 0.00 |
October | 6339.61 | 2708.68 | 981.46 | 460.96 | 520.50 | 0.00 | 0.00 |
November | 4707.13 | 2036.04 | 779.84 | 341.08 | 438.77 | 0.00 | 0.00 |
December | 4909.38 | 1673.56 | 639.26 | 248.40 | 390.86 | 0.00 | 0.00 |
Annual Sum or Average | 7715.11 | 2329.06 | 1060.07 | 489.75 | 570.32 | 0.00 | 0.00 |
Minimum of Months | 4707.13 | 1640.58 | 639.26 | 248.40 | 390.86 | 0.00 | 0.00 |
Maximum of Months | 10634.35 | 2997.96 | 1406.77 | 715.43 | 693.32 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.516548E+09 | 0.976045E+09 | 0.306512E+09 | 66860229.73 | 0.239652E+09 | 0.00 | 0.00 |
February | 0.629786E+09 | 0.786148E+09 | 0.316069E+09 | 68422753.48 | 0.247646E+09 | 0.00 | 0.00 |
March | 0.101494E+10 | 0.712624E+09 | 0.410248E+09 | 92089506.66 | 0.318159E+09 | 0.00 | 0.00 |
April | 0.136175E+10 | 0.498747E+09 | 0.436291E+09 | 91797176.69 | 0.344494E+09 | 0.00 | 0.00 |
May | 0.200732E+10 | 0.202036E+09 | 0.496898E+09 | 0.115692E+09 | 0.381206E+09 | 0.00 | 0.00 |
June | 0.217154E+10 | 97161107.41 | 0.502525E+09 | 0.126317E+09 | 0.376209E+09 | 0.00 | 0.00 |
July | 0.242978E+10 | 16398065.59 | 0.476459E+09 | 0.106017E+09 | 0.370442E+09 | 0.00 | 0.00 |
August | 0.245908E+10 | 10149306.15 | 0.474635E+09 | 0.110248E+09 | 0.364387E+09 | 0.00 | 0.00 |
September | 0.186341E+10 | 0.120212E+09 | 0.432149E+09 | 0.103706E+09 | 0.328443E+09 | 0.00 | 0.00 |
October | 0.143760E+10 | 0.321327E+09 | 0.396941E+09 | 98153556.79 | 0.298787E+09 | 0.00 | 0.00 |
November | 0.934503E+09 | 0.592101E+09 | 0.330774E+09 | 83220086.91 | 0.247553E+09 | 0.00 | 0.00 |
December | 0.570707E+09 | 0.892313E+09 | 0.290041E+09 | 67052658.16 | 0.222989E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.173970E+11 | 0.522526E+10 | 0.486954E+10 | 0.112958E+10 | 0.373997E+10 | 0.00 | 0.00 |
Minimum of Months | 0.516548E+09 | 10149306.15 | 0.290041E+09 | 66860229.73 | 0.222989E+09 | 0.00 | 0.00 |
Maximum of Months | 0.245908E+10 | 0.976045E+09 | 0.502525E+09 | 0.126317E+09 | 0.381206E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.154540E+11 | 0.443729E+10 | 0.184292E+10 | 0.706388E+09 | 0.113653E+10 | 0.00 | 0.00 |
February | 0.178805E+11 | 0.396888E+10 | 0.201827E+10 | 0.824824E+09 | 0.119344E+10 | 0.00 | 0.00 |
March | 0.199293E+11 | 0.483457E+10 | 0.270235E+10 | 0.113435E+10 | 0.156801E+10 | 0.00 | 0.00 |
April | 0.209008E+11 | 0.557634E+10 | 0.308293E+10 | 0.136669E+10 | 0.171624E+10 | 0.00 | 0.00 |
May | 0.263561E+11 | 0.701679E+10 | 0.361472E+10 | 0.175775E+10 | 0.185698E+10 | 0.00 | 0.00 |
June | 0.250865E+11 | 0.737407E+10 | 0.364634E+10 | 0.185441E+10 | 0.179193E+10 | 0.00 | 0.00 |
July | 0.284830E+11 | 0.784522E+10 | 0.365507E+10 | 0.185450E+10 | 0.180057E+10 | 0.00 | 0.00 |
August | 0.251841E+11 | 0.802973E+10 | 0.348160E+10 | 0.171088E+10 | 0.177072E+10 | 0.00 | 0.00 |
September | 0.216991E+11 | 0.735161E+10 | 0.302386E+10 | 0.145097E+10 | 0.157289E+10 | 0.00 | 0.00 |
October | 0.169800E+11 | 0.725492E+10 | 0.262876E+10 | 0.123464E+10 | 0.139412E+10 | 0.00 | 0.00 |
November | 0.122009E+11 | 0.527741E+10 | 0.202135E+10 | 0.884071E+09 | 0.113728E+10 | 0.00 | 0.00 |
December | 0.131493E+11 | 0.448245E+10 | 0.171220E+10 | 0.665325E+09 | 0.104687E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.243304E+12 | 0.734493E+11 | 0.334304E+11 | 0.154448E+11 | 0.179856E+11 | 0.00 | 0.00 |
Minimum of Months | 0.122009E+11 | 0.396888E+10 | 0.171220E+10 | 0.665325E+09 | 0.104687E+10 | 0.00 | 0.00 |
Maximum of Months | 0.284830E+11 | 0.802973E+10 | 0.365507E+10 | 0.185450E+10 | 0.185698E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.740519E+09 | -608904138.2 | 0.00 | 0.00 | 744.00 | 0.00 | -131614733.3 | 58.99 | 0.00 | 0.00 |
February | 0.661043E+09 | -543789879.9 | 0.00 | 0.00 | 672.00 | 0.00 | -117252845.5 | 58.99 | 0.00 | 0.00 |
March | 0.718448E+09 | -590745644.6 | 0.00 | 0.00 | 744.00 | 0.00 | -127702663.2 | 58.99 | 0.00 | 0.00 |
April | 0.613875E+09 | -493207070.0 | 0.00 | 0.00 | 720.00 | 0.00 | -120667511.0 | 58.99 | 0.00 | 0.00 |
May | 0.578749E+09 | -456694554.8 | 0.00 | 0.00 | 744.00 | 0.00 | -122054088.9 | 58.99 | 0.00 | 0.00 |
June | 0.531792E+09 | -413931065.9 | 0.00 | 0.00 | 720.00 | 0.00 | -117860878.3 | 58.99 | 0.00 | 0.00 |
July | 0.508738E+09 | -387622820.3 | 0.00 | 0.00 | 744.00 | 0.00 | -121115189.0 | 58.99 | 0.00 | 0.00 |
August | 0.557169E+09 | -435323827.9 | 0.00 | 0.00 | 744.00 | 0.00 | -121845647.8 | 58.99 | 0.00 | 0.00 |
September | 0.565808E+09 | -448221634.6 | 0.00 | 0.00 | 720.00 | 0.00 | -117586072.2 | 58.99 | 0.00 | 0.00 |
October | 0.627218E+09 | -505129011.8 | 0.00 | 0.00 | 744.00 | 0.00 | -122089414.5 | 58.99 | 0.00 | 0.00 |
November | 0.657386E+09 | -536753044.9 | 0.00 | 0.00 | 720.00 | 0.00 | -120632547.9 | 58.99 | 0.00 | 0.00 |
December | 0.725614E+09 | -596890114.5 | 0.00 | 0.00 | 744.00 | 0.00 | -128724267.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.748636E+10 | -0.601721E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.146915E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.508738E+09 | -608904138.2 | 0.00 | 0.00 | 672.00 | 0.00 | -131614733.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.740519E+09 | -387622820.3 | 0.00 | 0.00 | 744.00 | 0.00 | -117252845.5 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 325.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 375.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 403.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 405.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 395.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 358.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 351.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 319.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4323.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 2150400.66 | 996.75 | 02-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2150400.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2150400.66 | 996.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.658385E+10 | 0.564111E+10 | 39887.23 | 30-JAN-06:01 | 26882.29 | 0.00 |
February | 0.00 | 0.00 | 0.782209E+10 | 0.656074E+10 | 41170.02 | 09-FEB-06:01 | 26748.94 | 0.00 |
March | 0.00 | 0.00 | 0.111259E+11 | 0.965724E+10 | 41825.21 | 29-MAR-05:01 | 25773.88 | 0.00 |
April | 0.00 | 0.00 | 0.134276E+11 | 0.114392E+11 | 42152.68 | 20-APR-05:01 | 25557.22 | 0.00 |
May | 0.00 | 0.00 | 0.191704E+11 | 0.160805E+11 | 44649.32 | 25-MAY-05:01 | 23036.19 | 0.00 |
June | 0.00 | 0.00 | 0.232513E+11 | 0.177310E+11 | 44317.32 | 08-JUN-05:01 | 21221.08 | 0.00 |
July | 0.00 | 0.00 | 0.267230E+11 | 0.192834E+11 | 43087.47 | 29-JUL-05:02 | 24779.57 | 0.00 |
August | 0.00 | 0.00 | 0.295562E+11 | 0.210101E+11 | 43087.47 | 31-AUG-05:01 | 22710.26 | 0.00 |
September | 0.00 | 0.00 | 0.232616E+11 | 0.169010E+11 | 45043.40 | 25-SEP-05:01 | 23995.27 | 0.00 |
October | 0.00 | 0.00 | 0.183933E+11 | 0.142939E+11 | 44617.38 | 17-OCT-05:02 | 22733.15 | 0.00 |
November | 0.00 | 0.00 | 0.135762E+11 | 0.107728E+11 | 44066.06 | 03-NOV-05:01 | 24925.80 | 0.00 |
December | 0.00 | 0.00 | 0.912386E+10 | 0.750423E+10 | 41097.43 | 06-DEC-06:01 | 25165.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.202015E+12 | 0.156875E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.658385E+10 | 0.564111E+10 | 39887.23 | 21221.08 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.295562E+11 | 0.210101E+11 | 45043.40 | 26882.29 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.159497E+11 | 0.135544E+11 | 37374.91 | 29-JAN-15:15 | 28053.37 | 0.00 |
February | 0.00 | 0.00 | 0.223975E+11 | 0.189165E+11 | 132382.26 | 05-FEB-13:43 | 122282.08 | 0.00 |
March | 0.00 | 0.00 | 0.376736E+11 | 0.329864E+11 | 154164.54 | 26-MAR-16:02 | 154164.54 | 0.00 |
April | 0.00 | 0.00 | 0.571513E+11 | 0.491753E+11 | 177457.57 | 30-APR-15:42 | 126040.00 | 0.00 |
May | 0.00 | 0.00 | 0.949391E+11 | 0.812875E+11 | 178480.77 | 29-MAY-13:42 | 122323.66 | 0.00 |
June | 0.00 | 0.00 | 0.116039E+12 | 0.910861E+11 | 185758.84 | 09-JUN-05:01 | 107824.64 | 0.00 |
July | 0.00 | 0.00 | 0.138396E+12 | 0.105376E+12 | 184484.97 | 18-JUL-05:01 | 113225.92 | 0.00 |
August | 0.00 | 0.00 | 0.145559E+12 | 0.109089E+12 | 191296.36 | 08-AUG-05:01 | 104903.73 | 0.00 |
September | 0.00 | 0.00 | 0.113199E+12 | 0.851185E+11 | 183813.28 | 10-SEP-17:42 | 111643.82 | 0.00 |
October | 0.00 | 0.00 | 0.822701E+11 | 0.656093E+11 | 180240.68 | 08-OCT-09:02 | 116920.40 | 0.00 |
November | 0.00 | 0.00 | 0.478067E+11 | 0.387018E+11 | 132649.37 | 05-NOV-14:02 | 124012.40 | 0.00 |
December | 0.00 | 0.00 | 0.245689E+11 | 0.201801E+11 | 84216.17 | 03-DEC-14:13 | 69783.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.895951E+12 | 0.711081E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.159497E+11 | 0.135544E+11 | 37374.91 | 28053.37 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.145559E+12 | 0.109089E+12 | 191296.36 | 154164.54 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.178576E+10 | 0.33 | 1801.17 | 02-JAN-08:50 | 0.89 |
February | 0.164838E+10 | 0.35 | 1801.17 | 01-FEB-09:20 | 0.89 |
March | 0.194625E+10 | 0.38 | 1801.17 | 01-MAR-09:37 | 0.89 |
April | 0.182054E+10 | 0.38 | 1801.17 | 01-APR-11:35 | 0.89 |
May | 0.195106E+10 | 0.45 | 1801.17 | 01-MAY-07:55 | 0.89 |
June | 0.199471E+10 | 0.51 | 1801.17 | 01-JUN-06:13 | 0.89 |
July | 0.201063E+10 | 0.61 | 1801.17 | 01-JUL-08:37 | 0.89 |
August | 0.216093E+10 | 0.64 | 1801.17 | 01-AUG-09:10 | 0.89 |
September | 0.193137E+10 | 0.51 | 1801.17 | 01-SEP-08:30 | 0.89 |
October | 0.186412E+10 | 0.42 | 1801.17 | 03-OCT-08:55 | 0.89 |
November | 0.174735E+10 | 0.36 | 1801.17 | 01-NOV-06:20 | 0.89 |
December | 0.179579E+10 | 0.34 | 1801.17 | 01-DEC-08:43 | 0.89 |
Annual Sum or Average | 0.226569E+11 | 0.44 | |||
Minimum of Months | 0.164838E+10 | 0.33 | 1801.17 | 0.89 | |
Maximum of Months | 0.216093E+10 | 0.64 | 1801.17 | 0.89 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.108406E+11 | 0.53 | 10929.98 | 02-JAN-12:23 | 1.40 |
February | 0.100197E+11 | 0.57 | 10929.98 | 01-FEB-11:04 | 1.40 |
March | 0.119336E+11 | 0.69 | 10929.98 | 01-MAR-10:30 | 1.40 |
April | 0.117160E+11 | 0.91 | 10929.98 | 01-APR-08:50 | 1.40 |
May | 0.134992E+11 | 1.18 | 10929.98 | 01-MAY-09:33 | 1.40 |
June | 0.140464E+11 | 1.20 | 10929.98 | 02-JUN-13:40 | 1.40 |
July | 0.147414E+11 | 1.20 | 10929.98 | 01-JUL-07:55 | 1.39 |
August | 0.154040E+11 | 1.22 | 10929.98 | 01-AUG-08:65 | 1.39 |
September | 0.136154E+11 | 1.20 | 10929.98 | 01-SEP-06:30 | 1.39 |
October | 0.125982E+11 | 1.13 | 10929.98 | 02-OCT-06:50 | 1.39 |
November | 0.109112E+11 | 0.78 | 10929.98 | 01-NOV-10:45 | 1.39 |
December | 0.108834E+11 | 0.55 | 10929.98 | 01-DEC-10:50 | 1.40 |
Annual Sum or Average | 0.150209E+12 | 0.93 | |||
Minimum of Months | 0.100197E+11 | 0.53 | 10929.98 | 1.39 | |
Maximum of Months | 0.154040E+11 | 1.22 | 10929.98 | 1.40 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.354766E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.376058E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.502648E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.569003E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.780799E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.911008E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.102788E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.112924E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.888463E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.718833E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.551707E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.424058E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.823446E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.354766E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.112924E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.155062E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.166635E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.234073E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.297749E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.451413E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.527324E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.616742E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.646993E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.506974E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.388341E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.255731E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.181118E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.442815E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.155062E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.646993E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.178576E+10 | 0.658385E+10 | 2150400.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164838E+10 | 0.782209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.194625E+10 | 0.111259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182054E+10 | 0.134276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.195106E+10 | 0.191704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.199471E+10 | 0.232513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.201063E+10 | 0.267230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.216093E+10 | 0.295562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.193137E+10 | 0.232616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.186412E+10 | 0.183933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174735E+10 | 0.135762E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179579E+10 | 0.912386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226569E+11 | 0.202015E+12 | 2150400.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.164838E+10 | 0.658385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.216093E+10 | 0.295562E+11 | 2150400.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.108406E+11 | 0.159497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100197E+11 | 0.223975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119336E+11 | 0.376736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117160E+11 | 0.571513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134992E+11 | 0.949391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140464E+11 | 0.116039E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147414E+11 | 0.138396E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.154040E+11 | 0.145559E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136154E+11 | 0.113199E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125982E+11 | 0.822701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109112E+11 | 0.478067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108834E+11 | 0.245689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.150209E+12 | 0.895951E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.100197E+11 | 0.159497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154040E+11 | 0.145559E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.178576E+10 | 0.00 | 0.00 | 0.00 | 0.176190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164838E+10 | 0.00 | 0.00 | 0.00 | 0.211220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.194625E+10 | 0.00 | 0.00 | 0.00 | 0.308023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182054E+10 | 0.00 | 0.00 | 0.00 | 0.386949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.195106E+10 | 0.00 | 0.00 | 0.00 | 0.585693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.199471E+10 | 0.00 | 0.00 | 0.00 | 0.711537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.201063E+10 | 0.00 | 0.00 | 0.00 | 0.826816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.216093E+10 | 0.00 | 0.00 | 0.00 | 0.913148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.193137E+10 | 0.00 | 0.00 | 0.00 | 0.695326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.186412E+10 | 0.00 | 0.00 | 0.00 | 0.532421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174735E+10 | 0.00 | 0.00 | 0.00 | 0.376971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179579E+10 | 0.00 | 0.00 | 0.00 | 0.244478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226569E+11 | 0.00 | 0.00 | 0.00 | 0.596878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.164838E+10 | 0.00 | 0.00 | 0.00 | 0.176190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.216093E+10 | 0.00 | 0.00 | 0.00 | 0.913148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.108406E+11 | 0.00 | 0.00 | 0.00 | 0.466559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100197E+11 | 0.00 | 0.00 | 0.00 | 0.664388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119336E+11 | 0.00 | 0.00 | 0.00 | 0.114736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117160E+11 | 0.00 | 0.00 | 0.00 | 0.180589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134992E+11 | 0.00 | 0.00 | 0.00 | 0.316421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140464E+11 | 0.00 | 0.00 | 0.00 | 0.386860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147414E+11 | 0.00 | 0.00 | 0.00 | 0.469328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.154040E+11 | 0.00 | 0.00 | 0.00 | 0.492953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136154E+11 | 0.00 | 0.00 | 0.00 | 0.370820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125982E+11 | 0.00 | 0.00 | 0.00 | 0.262359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109112E+11 | 0.00 | 0.00 | 0.00 | 0.146619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108834E+11 | 0.00 | 0.00 | 0.00 | 0.722836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.150209E+12 | 0.00 | 0.00 | 0.00 | 0.292606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.100197E+11 | 0.00 | 0.00 | 0.00 | 0.466559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154040E+11 | 0.00 | 0.00 | 0.00 | 0.492953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 96307806.99 | 0.136409E+09 | 0.00 | 8249249.63 | 0.00 | 3866258.98 | 0.283074E+09 | 0.00 | 0.14 |
February | 53458118.29 | 0.277647E+09 | 0.00 | 8012942.01 | 0.00 | 0.00 | 0.131717E+09 | 0.00 | 0.14 |
March | 26994146.85 | 0.570007E+09 | 0.00 | 7523017.58 | 0.00 | 0.00 | 0.105342E+09 | 0.00 | 0.15 |
April | 225994.89 | 0.107933E+10 | 0.00 | 5929740.51 | 0.00 | 0.00 | 50179735.77 | 0.00 | 0.15 |
May | 0.00 | 0.206687E+10 | 0.00 | 3418371.12 | 0.00 | 0.00 | 4258712.87 | 0.00 | 0.15 |
June | 0.00 | 0.313451E+10 | 0.00 | 1562099.31 | 0.00 | 0.00 | 983225.79 | 0.00 | 0.16 |
July | 0.00 | 0.417245E+10 | 0.00 | 916927.43 | 0.00 | 0.00 | 516598.43 | 0.00 | 0.16 |
August | 0.00 | 0.468775E+10 | 0.00 | 20403.80 | 0.00 | 0.00 | 3857.43 | 0.00 | 0.17 |
September | 0.00 | 0.340157E+10 | 0.00 | 1595977.53 | 0.00 | 0.00 | 956949.25 | 0.00 | 0.16 |
October | 0.00 | 0.218761E+10 | 0.00 | 1966907.28 | 0.00 | 0.00 | 6120047.03 | 0.00 | 0.14 |
November | 0.00 | 0.127406E+10 | 0.00 | 3572098.34 | 0.00 | 0.00 | 13014549.26 | 0.00 | 0.14 |
December | 38773971.47 | 0.433197E+09 | 0.00 | 6453607.93 | 0.00 | 0.00 | 0.120307E+09 | 0.00 | 0.14 |
Annual Sum or Average | 0.215760E+09 | 0.234214E+11 | 0.00 | 49221342.48 | 0.00 | 3866258.98 | 0.716473E+09 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.136409E+09 | 0.00 | 20403.80 | 0.00 | 0.00 | 3857.43 | 0.00 | 0.14 |
Maximum of Months | 96307806.99 | 0.468775E+10 | 0.00 | 8249249.63 | 0.00 | 3866258.98 | 0.283074E+09 | 0.00 | 0.17 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.128087E+10 | 0.134485E+09 | 0.00 | 19650690.93 | 0.00 | 0.00 | 0.141318E+10 | 0.00 | 0.20 |
February | 0.665571E+09 | 0.493158E+09 | 0.00 | 23975818.12 | 0.00 | 0.00 | 0.966636E+09 | 0.00 | 0.20 |
March | 0.430796E+09 | 0.144382E+10 | 0.00 | 26085039.24 | 6039.90 | 0.00 | 0.821286E+09 | 0.00 | 0.22 |
April | 94654815.27 | 0.351088E+10 | 0.00 | 10551066.72 | 0.00 | 0.00 | 0.469799E+09 | 0.00 | 0.22 |
May | 0.00 | 0.857877E+10 | 0.00 | 1910968.48 | 0.00 | 0.00 | 37403842.55 | 0.00 | 0.24 |
June | 0.00 | 0.138685E+11 | 0.00 | 253563.07 | 0.00 | 0.00 | 1490255.97 | 0.00 | 0.27 |
July | 0.00 | 0.195458E+11 | 0.00 | 380107.22 | 0.00 | 0.00 | 347890.79 | 0.00 | 0.27 |
August | 0.00 | 0.214411E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
September | 0.00 | 0.150647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
October | 0.00 | 0.856849E+10 | 0.00 | 2689868.82 | 0.00 | 0.00 | 57790968.29 | 0.00 | 0.23 |
November | 69631070.54 | 0.392419E+10 | 0.00 | 4220924.84 | 0.00 | 0.00 | 0.165833E+09 | 0.00 | 0.21 |
December | 0.630100E+09 | 0.917187E+09 | 0.00 | 18788102.92 | 0.00 | 0.00 | 0.914777E+09 | 0.00 | 0.20 |
Annual Sum or Average | 0.317163E+10 | 0.974911E+11 | 0.00 | 0.108506E+09 | 6039.90 | 0.00 | 0.484855E+10 | 0.00 | 0.23 |
Minimum of Months | 0.00 | 0.134485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.128087E+10 | 0.214411E+11 | 0.00 | 26085039.24 | 6039.90 | 0.00 | 0.141318E+10 | 0.00 | 0.28 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.473863E+12 | 0.544718E+11 | 0.00 | 0.945272E+10 | 0.289622E+11 |
February | 0.526324E+12 | 0.908757E+11 | 0.00 | 0.627487E+10 | 0.389757E+11 |
March | 0.666875E+12 | 0.142478E+12 | 0.00 | 0.338598E+10 | 0.633533E+11 |
April | 0.721295E+12 | 0.181732E+12 | 0.00 | -0.358766E+10 | 0.925073E+11 |
May | 0.787760E+12 | 0.241408E+12 | 0.00 | -0.149331E+11 | 0.151608E+12 |
June | 0.779082E+12 | 0.241055E+12 | 0.00 | -0.239046E+11 | 0.185092E+12 |
July | 0.779265E+12 | 0.232489E+12 | 0.00 | -0.326220E+11 | 0.220320E+12 |
August | 0.757505E+12 | 0.229943E+12 | 0.00 | -0.351196E+11 | 0.233542E+12 |
September | 0.659180E+12 | 0.194069E+12 | 0.00 | -0.260387E+11 | 0.180496E+12 |
October | 0.570447E+12 | 0.151482E+12 | 0.00 | -0.156482E+11 | 0.132224E+12 |
November | 0.450978E+12 | 0.103635E+12 | 0.00 | -0.435084E+10 | 0.798145E+11 |
December | 0.424787E+12 | 0.673108E+11 | 0.00 | 0.555958E+10 | 0.433659E+11 |
Annual Sum or Average | 0.759736E+13 | 0.193095E+13 | 0.00 | -0.131531E+12 | 0.145026E+13 |
Minimum of Months | 0.424787E+12 | 0.544718E+11 | 0.00 | -0.351196E+11 | 0.289622E+11 |
Maximum of Months | 0.787760E+12 | 0.241408E+12 | 0.00 | 0.945272E+10 | 0.233542E+12 |