Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2023-10-16 10:41:44
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1241.95 | 256.86 | 256.86 |
Net Site Energy | 1241.95 | 256.86 | 256.86 |
Total Source Energy | 3925.72 | 811.92 | 811.92 |
Net Source Energy | 3925.72 | 811.92 | 811.92 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 3.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 158.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 134.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 158.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1238.33 | 3.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 3.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 158.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 134.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 22.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 135.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 24.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 3.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 158.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 134.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 158.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 24.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 70.58 | 0.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 256.11 | 0.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 70.58 | 0.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 256.11 | 0.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1238.334 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1238.334 | 100.00 |
Total On-Site and Utility Electric Sources | 1238.334 | 100.00 |
Total Electricity End Uses | 1238.334 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 5.17 |
Time Setpoint Not Met During Occupied Cooling | 37.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2600.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.61 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7186 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 15.0695 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 9.6875 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 11.2890 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 11.2890 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.7186 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 15.0695 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 9.6875 | 46.45 | 2.5587 | |
Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 11.2890 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUN-14:00 | 01-JAN-07:30 | - | - | - | - | - | - | - | - | - | - | 27-APR-11:20 |
Heating | 0.00 | 47260.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 33566.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 12853.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1679.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 104406.17 | 47260.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 47260.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 33566.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 10548.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1679.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 3.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 503.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1974.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 424.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 500.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 76.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3921.80 | 3.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 104.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 103.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 811.11 | 0.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 104.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 103.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 811.11 | 0.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.57 |
ZONE2 FINE STORAGE DIRECT AIR | 5.13 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 2.24 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 2.24 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 83163.95 |
PSZ-OFFICE HEATING COIL | 34987.64 |
PSZ-FINE STORAGE HEATING COIL | 144735.25 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 83163.96 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.57 | 1.57 | 1.57 | 1.57 | 1.57 | 1.57 | 1.00 | 1.00 | 1.57 |
PSZ-FINE STORAGE | 5.13 | 5.13 | 5.13 | 5.13 | 5.13 | 5.13 | 1.00 | 1.00 | 5.13 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.57 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 5.13 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.57 | 1718.26 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 5.13 | 8830.35 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.57 | 1.57 | 1.57 | 1.57 | 28044.54 | 34987.64 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 5.13 | 5.13 | 5.13 | 5.13 | 112167.59 | 144735.25 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.57 | 0.784947 | 1.57 | 28044.54 | 14464.21 | 28044.54 | 0.800690 | 0.800690 |
PSZ-FINE STORAGE COOLING COIL | 5.13 | 2.56 | 5.13 | 112167.59 | 57174.24 | 112167.59 | 0.742280 | 0.742280 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.719 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.792 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 15.069 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15.069 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 9.688 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 12.246 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2539.013 | 10.719 | 199.158 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2539.013 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 20997.932 | 15.069 | 699.931 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20997.932 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 31046.942 | 9.688 | 449.956 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 31046.942 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 1.090 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.7823 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 1.301 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 1.301 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9172 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.179 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6691 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6691 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53297977E-11 | 0.35762577E-16 | 0.10093676E-15 | 0.0000000 |
5 | 1 | -5.2159127 | 0.59796011E-04 | -0.14694131E-04 | 0.68696372E-11 |
6 | 0 | 6.3062040 | 1.0902315 | 1.0903060 | |
7 | 4 | 0.72249793E-12 | -0.16720573E-15 | 0.22015083E-14 | 0.12409536E-15 |
8 | 3 | -0.36459118E-03 | 0.53555631E-06 | -0.52695411E-04 | 0.13865996E-12 |
9 | 2 | 1.6915239 | 0.11971291E-01 | 1.1039557 | -0.69896550E-04 |
10 | 1 | -7.1930661 | 0.31446443 | -16.864389 | 0.32415671 |
11 | 0 | 6.0306730 | 0.20232993 | 16.289252 | |
12 | 4 | 0.62407051E-12 | 0.80447548E-15 | -0.19405657E-14 | 0.12807081E-15 |
13 | 3 | -0.32959465E-03 | 0.84747600E-06 | -0.47309261E-04 | 0.11981323E-12 |
14 | 2 | 1.6058071 | 0.19756964E-01 | 1.0389034 | -0.63182077E-04 |
15 | 1 | -7.3135607 | 0.53269638 | -16.443412 | 0.30760774 |
16 | 0 | 6.6091660 | 0.34862863 | 16.305639 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.19405657E-14 | 0.80447548E-15 | 0.62407051E-12 | 0.12807081E-15 |
85 | 3 | -0.47309261E-04 | 0.84747600E-06 | -0.32959465E-03 | 0.11981323E-12 |
86 | 2 | 1.0389034 | 0.19756964E-01 | 1.6058071 | -0.63182077E-04 |
87 | 1 | -16.443412 | 0.53269638 | -7.3135607 | 0.30760774 |
88 | 0 | 16.305639 | 0.34862863 | 6.6091660 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.7283_SHGC_SOUTH_0.25 | 34 | 1 | VerySmooth | 4.139 | 4.139 | 1.000 | 0.254 | ||
2 | NONRESWINDOW_U_0.7283_SHGC_NORTH_0.25 | 35 | 1 | VerySmooth | 4.139 | 4.139 | 1.000 | 0.254 | ||
3 | NONRESWINDOW_U_0.7283_SHGC_EAST_0.25 | 36 | 1 | VerySmooth | 4.139 | 4.139 | 1.000 | 0.254 | ||
4 | NONRESWINDOW_U_0.7283_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 4.139 | 4.139 | 1.000 | 0.254 | ||
5 | SKYLIGHT_U_1.02_SHGC_0.36 | 38 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.361 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.12675 | 0.51233 | 0.51233 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 2.71778E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.12675 | 0.51233 | 0.51233 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 2.71778E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.12675 | 0.51233 | 0.51233 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 2.71778E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.12675 | 0.51233 | 0.51233 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 2.71778E-002 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.19502 | 0.25365 | 0.25365 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.849 | 0.366 | 0.255 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 0.153 | 6.473E-004 | 9.992E-004 | 0.546 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.780 | 5.598E-004 | 3.565E-004 | 0.951 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 3.433 | 1.071E-003 | 6.996E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 14437.22909 | 17324.67491 | 1.30825 | 1.56989 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 39.47000 | 5.62903E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 8375.66734 | 10050.80081 | 0.25887 | 0.31064 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 0.50000 | 4.31558E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 60510.62668 | 72612.75202 | 4.27395 | 5.12873 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 23815.69192 | 28578.83031 | 0.62028 | 0.74434 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 0.50000 | 4.31558E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 69303.29662 | 83163.95595 | 1.86521 | 2.23825 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 22289.48 | 1.56989 | 1.56989 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 8775.30 | 0.31064 | 0.31064 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 89382.77 | 5.12873 | 5.12873 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 27010.80 | 0.74434 | 0.74434 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.56989 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.12873 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.23825 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 2.23825 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 83163.95319 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 83163.95595 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.56989 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.56989 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.56989 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.56989 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.56989 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.56989 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.12873 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.12873 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.12873 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 5.12873 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.12873 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 5.12873 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.56989 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 5.12873 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.56989 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.56989 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1718.25766 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.56989 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.56989 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.56989 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.56989 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.56989 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.78495 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.56989 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28044.54000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 14464.21302 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 28044.54000 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80069 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80069 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28044.54000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34987.64314 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 34987.64314 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.12873 |
47 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 5.12873 |
49 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 8830.35426 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 5.12873 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 5.12873 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 5.12873 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 5.12873 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 5.12873 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.56437 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 5.12873 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 112167.59000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 57174.24211 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 112167.59000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74228 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74228 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 112167.59000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 144735.25322 |
64 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
66 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 144735.25322 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 26826.0 | 10.83 | 10.20 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 108183.5 | 10.38 | 9.78 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1260390254 | 0.1209296800 | Pass | Pass | 2.8044772965E-002 | 0.1754206521 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.2656341201 | 0.3254330674 | Pass | Pass | 4.2019635551 | 34.6147415159 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 8.2953746580E-002 | 7.6190223906E-002 | Pass | Pass | 1.6838558344E-002 | 7.2201957412E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 10355.77 | 724.19 | 0.00 | 31.93 | 651.27 | 11763.19 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 2 | |||
Feb | 34.00 | 28 | |||
Mar | 40.00 | 18 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 81.00 | 18 | |||
Aug | 71.00 | 20 | |||
Sep | 27.00 | 12 | |||
Oct | 9.00 | 6 | |||
Nov | 35.00 | 14 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.089 | 1.301 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.089 | 1.301 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.089 | 1.301 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.948 | 1.090 | 3204.84 | 3170.23 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.992 | 1.301 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.992 | 1.301 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.7283_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 4.139 | 0.254 | 0.251 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.7283_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 4.139 | 0.254 | 0.251 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.7283_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 4.139 | 0.254 | 0.251 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.7283_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 4.139 | 0.254 | 0.251 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.27 | 5.238 | 0.450 | 0.450 | |||||||||||||||||
North Total or Average | 6.51 | 4.139 | 0.254 | 0.251 | |||||||||||||||||
Non-North Total or Average | 45.76 | 5.394 | 0.478 | 0.478 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.7186 | 236.88 | 2539.01 | LightsWired | LTG_SCH_OFFICE | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.86 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 15.0695 | 1393.41 | 20997.93 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 239.15 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 9.6875 | 3204.84 | 31046.94 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 353.60 |
Interior Lighting Total | 11.2890 | 4835.13 | 54583.89 | 623.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 8532.22 | AstronomicalClock | - | 83.79 | 83.79 | 134.19 | |
Exterior Lighting Total | 8532.22 | 134.19 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28044.54 | 22454.98 | 5589.56 | 0.80 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 112167.59 | 83259.76 | 28907.83 | 0.74 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 26826.0 | 10.83 | 10.20 | ||||
PSZ-FINE STORAGE COOLING COIL | 108183.5 | 10.38 | 9.78 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 83163.95 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 34987.64 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 144735.25 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.24 | 207.96 | 92.91 | 1.00 | 3.51 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 1.57 | 1718.26 | 1094.51 | 1.00 | 1.32 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.59 | 1018.41 | 5.13 | 8830.35 | 1721.74 | 1.00 | 1.15 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 14437.23 | 17324.67 | 73.14 | 1.308 | 1.570 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 23.90 | 23.90 | 0.00807 | 39.47 | 0.00563 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 60510.63 | 72612.75 | 52.11 | 4.274 | 5.129 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 26.70 | 26.70 | 0.00788 | 40.67 | 0.00563 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 40.84 | 0.00572 | 40.67 | 0.00563 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8375.67 | 10050.80 | 42.43 | 0.259 | 0.311 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00782 | 0.50 | 0.00432 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 23815.69 | 28578.83 | 20.51 | 0.620 | 0.744 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 15.56 | 15.56 | 0.00682 | 0.50 | 0.00432 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 69303.30 | 83163.96 | 25.95 | 1.865 | 2.238 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00647 | 0.50 | 0.00432 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.57 | 1.57 | 0.31 | 0.31 | 1.5699 | 1.5699 | 1.5699 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 5.13 | 5.13 | 0.74 | 0.74 | 5.1287 | 5.1287 | 5.1287 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 83163.953 | 83163.953 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 83163.95 | 83163.95 | 2.238247 | 10.00 | 7.95 | 0.00647379 | 43.33 | 21.00 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 10.00 | 0.00647379 | 77.1619 | 83163.96 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 28044.540 | 22454.983 | 1.569890 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 28044.54 | 28044.54 | 1.569890 | 25.92 | 15.57 | 0.00790709 | 12.00 | 10.32 | 0.00790709 | 39.82 | 0.00562958 | 18.28 | 6.5154 | 23.90 | 0.00806600 | 39.6842 | 14422.27 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 34987.643 | 34987.643 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 34987.64 | 34987.64 | 1.569894 | 19.71 | 13.06 | 0.00758742 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 6.5154 | 21.10 | 0.00781545 | 45.6028 | 8375.67 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 112167.590 | 83259.759 | 5.128730 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 112167.59 | 112167.59 | 5.128730 | 29.41 | 16.57 | 0.00769493 | 12.00 | 10.10 | 0.00769493 | 40.80 | 0.00563111 | 18.58 | 8.2810 | 26.70 | 0.00788131 | 32.8344 | 60497.34 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 144735.253 | 144735.253 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 144735.25 | 144735.25 | 5.128735 | 14.31 | 9.96 | 0.00660843 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 8.2810 | 15.56 | 0.00681545 | 56.3998 | 23815.69 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 83163.953 | 83163.953 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 2.238247 | 2.44683908 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 83163.95 | 83163.95 | 1.0000 | 2.44683908 | 2.238247 | 10.00 | 7.95 | 0.00647379 | 26358.0 | 43.33 | 21.00 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 83163.95 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 10.00 | 0.00647379 | 10.00 | 0.00647379 | 77.1619 | 83163.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28044.540 | 22454.983 | 1.569890 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5389 | 1004.8586 | 1.0932 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.569894 | 1.71619909 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | Sensible | 28044.54 | 28044.54 | 1.0000 | 1.71619467 | 1.569890 | 25.92 | 15.57 | 0.00790709 | 46201.9 | 12.00 | 10.32 | 0.00790709 | 32009.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28044.54 | 39.82 | 0.00562958 | 18.28 | 0.10228463 | 6.5154 | 23.90 | 0.00806600 | 23.90 | 0.00806600 | 39.6842 | 14422.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34987.643 | 34987.643 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.569894 | 1.71619909 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 34987.64 | 34987.64 | 1.0000 | 1.71619909 | 1.569894 | 19.71 | 13.06 | 0.00758742 | 39061.0 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34987.64 | 0.50 | 0.00431558 | 0.50 | 0.10228463 | 6.5154 | 21.05 | 0.00781545 | 21.10 | 0.00781545 | 45.6028 | 8375.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 112167.590 | 83259.759 | 5.128730 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.1445 | 1004.8586 | 1.0932 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 5.128735 | 5.60670294 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 112167.59 | 112167.59 | 1.0000 | 5.60669798 | 5.128730 | 29.41 | 16.57 | 0.00769493 | 49221.6 | 12.00 | 10.10 | 0.00769493 | 31474.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 112167.59 | 40.80 | 0.00563111 | 18.58 | 0.42471127 | 8.2810 | 26.70 | 0.00788131 | 26.70 | 0.00788131 | 32.8344 | 60497.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 144735.253 | 144735.253 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 5.128735 | 5.60670294 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | Sensible | 144735.25 | 144735.25 | 1.0000 | 5.60670294 | 5.128735 | 14.31 | 9.96 | 0.00660843 | 31082.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 144735.25 | 0.50 | 0.00431558 | 0.50 | 0.42471127 | 8.2810 | 15.56 | 0.00681545 | 15.56 | 0.00681545 | 56.3998 | 23815.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 5.13 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 1836.50 | 1305.17 | 149.50 |
ZONE2 FINE STORAGE | 3049.83 | 2241.50 | 1817.00 |
ZONE3 BULK STORAGE | 2852.83 | 3233.33 | 2598.67 |
Facility | 3459.83 | 3380.83 | 2600.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 5.17 | 59.67 | 5.00 | 37.00 |
ZONE2 FINE STORAGE | 3.83 | 318.50 | 0.33 | 1.33 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 8.83 | 370.83 | 5.17 | 37.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.344 | 0.481 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.538 | 0.361 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.151 | 0.000 | 1.559 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.54 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1251108.43 | 0.00 | 1251108.43 | 2774240.53 | 4025348.96 | 3225648.14 | 5415.74 | 3344.26 | 0.00 | 255.49 |
ZONE2 FINE STORAGE | 5617987.60 | 0.00 | 5617987.60 | 9791994.30 | 15409981.90 | 13393694.68 | 5696.40 | 2842.56 | 221.05 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.37E+09 | 0.37E+09 | 38699785.83 | 0.40E+09 | 30805497.77 | 5913.39 | 8.26 | 2838.34 | 5116.00 |
Total Facility | 6869096.03 | 0.37E+09 | 0.37E+09 | 51266020.66 | 0.42E+09 | 47424840.58 | 7300.01 | 3347.17 | 3051.55 | 5116.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.0948 | 0.0000 | 0.0948 | 0.1325 | 0.2273 | 0.1023 | 292.10 | 3343.90 | 0.00 |
ZONE2 FINE STORAGE | 0.4292 | 0.0000 | 0.4292 | 0.2883 | 0.7175 | 0.4247 | 572.40 | 2842.56 | 221.05 |
ZONE3 BULK STORAGE | 0.0000 | 14.4922 | 14.4922 | 1.4276 | 15.9198 | 0.9768 | 2129.05 | 5.35 | 1501.60 |
Total Facility | 0.5240 | 14.4922 | 15.0162 | 1.8483 | 16.8645 | 1.5038 | 2176.01 | 3343.90 | 1714.81 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 1495166.65 | 0.00 | 1495166.65 | 3225648.14 | 5412.84 | 0.29 | 3346.87 | 249.76 |
PSZ-FINE STORAGE | 6713908.64 | 0.00 | 6713908.64 | 13393694.68 | 5695.65 | 0.00 | 3064.35 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1133 | 0.0000 | 0.1133 | 0.1023 | 289.82 | 0.24 | 3345.94 |
PSZ-FINE STORAGE | 0.5129 | 0.0000 | 0.5129 | 0.4247 | 571.65 | 0.00 | 3064.35 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 3719.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2841.92 | 225.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1188 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.5077 | 1.8779 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 383 |
Defaulted Fields | 319 |
Fields with Defaults | 1020 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1238.33 | 6718.26 | 01-JAN-09:00 | 104406.17 | 28-JUN-15:00 |
Electricity:Building | 785.82 | 6235.26 | 01-JAN-00:10 | 58611.10 | 01-APR-15:00 |
Electricity:Zone:ZONE1 OFFICE | 62.81 | 1030.77 | 01-JAN-00:10 | 3867.54 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 762.90 | 6235.26 | 01-JAN-00:10 | 56305.80 | 02-JAN-09:10 |
InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 483.86 | 3104.69 | 01-JAN-00:10 | 36895.31 | 01-APR-15:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 158.18 | 0.00 | 01-JAN-00:40 | 12853.91 | 03-APR-12:20 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 22.92 | 0.00 | 01-JAN-00:10 | 2305.29 | 28-AUG-05:10 |
Ventilation (simple):Fans:Electricity | 22.92 | 0.00 | 01-JAN-00:10 | 2305.29 | 28-AUG-05:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 22.92 | 0.00 | 01-JAN-00:10 | 2305.29 | 28-AUG-05:10 |
ElectricityPurchased:Facility | 1238.33 | 6718.26 | 01-JAN-09:00 | 104406.17 | 28-JUN-15:00 |
ElectricityPurchased:Plant | 1238.33 | 6718.26 | 01-JAN-09:00 | 104406.17 | 28-JUN-15:00 |
Cogeneration:ElectricityPurchased | 1238.33 | 6718.26 | 01-JAN-09:00 | 104406.17 | 28-JUN-15:00 |
General:Cogeneration:ElectricityPurchased | 1238.33 | 6718.26 | 01-JAN-09:00 | 104406.17 | 28-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1238.33 | 6718.26 | 01-JAN-09:00 | 104406.17 | 28-JUN-15:00 |
ElectricityNet:Plant | 1238.33 | 6718.26 | 01-JAN-09:00 | 104406.17 | 28-JUN-15:00 |
Cogeneration:ElectricityNet | 1238.33 | 6718.26 | 01-JAN-09:00 | 104406.17 | 28-JUN-15:00 |
General:Cogeneration:ElectricityNet | 1238.33 | 6718.26 | 01-JAN-09:00 | 104406.17 | 28-JUN-15:00 |
Electricity:HVAC | 294.22 | 0.00 | 01-JAN-00:40 | 47415.49 | 30-JUN-16:00 |
General:Fans:Electricity | 135.25 | 0.00 | 01-JAN-00:40 | 10548.61 | 28-AUG-16:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 158.96 | 0.00 | 01-JAN-00:10 | 36866.88 | 30-JUN-16:00 |
General:Cooling:Electricity | 158.96 | 0.00 | 01-JAN-00:10 | 36866.88 | 30-JUN-16:00 |
ExteriorLights:Electricity | 134.19 | 0.00 | 01-JAN-07:30 | 8532.22 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 134.19 | 0.00 | 01-JAN-07:30 | 8532.22 | 01-JAN-00:10 |
Electricity:Plant | 24.10 | 483.00 | 20-APR-10:00 | 1795.28 | 23-JAN-12:10 |
WaterSystems:Electricity | 24.10 | 483.00 | 20-APR-10:00 | 1795.28 | 23-JAN-12:10 |
Water Heater:WaterSystems:Electricity | 24.10 | 483.00 | 20-APR-10:00 | 1795.28 | 23-JAN-12:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 3.61 | 0.00 | 01-JAN-00:40 | 47260.48 | 01-JAN-07:30 |
NaturalGas:HVAC | 3.61 | 0.00 | 01-JAN-00:40 | 47260.48 | 01-JAN-07:30 |
Heating:NaturalGas | 3.61 | 0.00 | 01-JAN-00:40 | 47260.48 | 01-JAN-07:30 |
General:Heating:NaturalGas | 3.61 | 0.00 | 01-JAN-00:40 | 47260.48 | 01-JAN-07:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-APR-11:20 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-APR-11:20 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-APR-11:20 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-APR-11:20 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-APR-11:20 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-APR-11:20 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-APR-11:20 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-APR-11:20 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 871.36 | 0.00 | 01-JAN-00:40 | 177046.67 | 30-JUN-16:00 |
EnergyTransfer:Building | 377.79 | 0.00 | 01-JAN-00:40 | 78927.78 | 30-JUN-16:00 |
EnergyTransfer:Zone:ZONE1 OFFICE | 82.58 | 0.00 | 01-JAN-00:10 | 18810.22 | 30-JUN-16:10 |
Heating:EnergyTransfer | 16.31 | 0.00 | 01-JAN-00:40 | 34818.08 | 01-JAN-07:30 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 2.24 | 0.00 | 01-JAN-00:10 | 15952.98 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 16.31 | 0.00 | 01-JAN-00:40 | 34818.08 | 01-JAN-07:30 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 2.24 | 0.00 | 01-JAN-00:10 | 15952.98 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 361.48 | 0.00 | 01-JAN-00:10 | 78927.78 | 30-JUN-16:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 80.34 | 0.00 | 01-JAN-00:10 | 18810.22 | 30-JUN-16:10 |
General:Cooling:EnergyTransfer | 361.48 | 0.00 | 01-JAN-00:10 | 78927.78 | 30-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 80.34 | 0.00 | 01-JAN-00:10 | 18810.22 | 30-JUN-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 295.07 | 0.00 | 01-JAN-00:40 | 62753.71 | 30-JUN-16:00 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 13.93 | 0.00 | 01-JAN-00:40 | 20682.95 | 01-JAN-06:50 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 13.93 | 0.00 | 01-JAN-00:40 | 20682.95 | 01-JAN-06:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 281.14 | 0.00 | 01-JAN-00:10 | 62753.71 | 30-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 281.14 | 0.00 | 01-JAN-00:10 | 62753.71 | 30-JUN-16:00 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.14 | 0.00 | 01-JAN-00:10 | 14774.33 | 01-JAN-07:30 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.14 | 0.00 | 01-JAN-00:10 | 14774.33 | 01-JAN-07:30 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.14 | 0.00 | 01-JAN-00:10 | 14774.33 | 01-JAN-07:30 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 493.57 | 0.00 | 01-JAN-00:40 | 98118.89 | 30-JUN-16:00 |
HeatingCoils:EnergyTransfer | 2.44 | 0.00 | 01-JAN-00:40 | 33779.69 | 01-JAN-07:30 |
CoolingCoils:EnergyTransfer | 491.13 | 0.00 | 01-JAN-00:10 | 98118.89 | 30-JUN-16:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 2.242 | -80.340 | 0.000 | 0.000 | 9.196 | 30.864 | 31.946 | 14.074 | 0.000 | 8.269 | 5.568 | 0.000 | -8.691 | 0.000 | -13.128 | -0.002 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 13.928 | -281.132 | 0.000 | 0.000 | 17.954 | 239.148 | 0.000 | 0.000 | 0.000 | 21.369 | 37.717 | 0.000 | 0.000 | 0.000 | -48.983 | -0.007 |
ZONE3 BULK STORAGE | 0.143 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32.742 | 353.598 | 107.344 | 205.431 | 0.000 | 14.202 | 25.407 | 0.000 | -87.223 | 0.000 | -651.643 | -0.013 |
Total Facility | 0.143 | 0.000 | 16.170 | -361.473 | 0.000 | 0.000 | 59.892 | 623.610 | 139.290 | 219.505 | 0.000 | 43.840 | 68.691 | 0.000 | -95.914 | 0.000 | -713.754 | -0.022 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 14-AUG-05:01 | 0.00 | 0.00 | 0.00 | -27071.85 | 0.00 | 0.00 | 56.91 | 583.97 | 573.75 | 0.00 | 0.00 | 0.00 | 26416.39 | 0.00 | -314.28 | 0.00 | -244.89 | 0.00 |
ZONE2 FINE STORAGE | 08-SEP-18:22 | 0.00 | 0.00 | 0.00 | -93223.79 | 0.00 | 0.00 | 0.00 | 2099.79 | 0.00 | 0.00 | 0.00 | 2729.13 | 88394.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 13-AUG-16:22 | 0.00 | 0.00 | 0.00 | -110807.66 | 0.00 | 0.00 | 0.00 | 5661.51 | 573.75 | 20969.22 | 0.00 | 14865.15 | 68738.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 03-JAN-06:01 | 0.00 | 0.00 | 34015.95 | 0.00 | 0.00 | 0.00 | 138.21 | 583.97 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -594.56 | 0.00 | -1024.53 | -33692.79 |
ZONE2 FINE STORAGE | 01-JAN-06:43 | 0.00 | 0.00 | 61275.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2099.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4782.59 | -58592.45 |
ZONE3 BULK STORAGE | 01-JAN-07:27 | 14795.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 6913.58 | 0.00 | -9408.52 | 0.00 | -15404.81 | 0.00 |
Total Facility | 01-JAN-06:43 | 11335.54 | 0.00 | 61275.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5661.51 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7076.56 | 0.00 | -18785.74 | -52983.75 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.5699 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.5699 | 0.0652 | 1.0000 | Not calculated | 0.1023 | 0.0652 | ||
PSZ-FINE STORAGE | 5.1287 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 5.1287 | 0.0828 | 1.0000 | Not calculated | 0.4247 | 0.0828 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.5699 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.5699 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0652 | ||
PSZ-FINE STORAGE | 5.1287 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 5.1287 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.0828 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5699 | 1.5699 | 1.5699 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.1287 | 5.1287 | 5.1287 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.5699 | 1.5699 | 1.5699 | 1.5699 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 5.1287 | 5.1287 | 5.1287 | 5.1287 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5699 | 1.5699 | 1.5699 | No | 0.1023 | 0.3293 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.1287 | 5.1287 | 5.1287 | No | 0.4247 | 0.5706 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.5699 | 1.5699 | 1.5699 | 1.5699 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 5.1287 | 5.1287 | 5.1287 | 5.1287 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 5.17 |
Number of hours cooling loads not met | 37.33 |
Number of hours not met | 42.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 3.61 | 47260.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 158.96 | 36866.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 623.61 | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 134.19 | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 22.92 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 135.25 | 10548.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 24.10 | 1795.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 1238.33 |
Natural Gas | 0.00 | 3.61 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 1241.95 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 128.97 |
Space Heating | 0.00 |
Space Cooling | 32.88 |
Fans (All) | 32.71 |
Service Water Heating | 4.98 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 256.11 |
Subtotal | 256.11 |
Natural Gas [MJ/m2] | |
Space Heating | 0.75 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.75 |
Subtotal | 0.75 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 50.21 |
Space Heating | 0.29 |
Space Cooling | 12.80 |
Fans (All) | 12.74 |
Service Water Heating | 1.94 |
Receptacle Equipment | 11.22 |
Miscellaneous | 10.81 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 3430. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 6795.17 | 1964.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7813.33 | 946.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 4468.33 | 3373.83 | 914.67 | 3.17 | 0.00 |
Min | 4468.33 | 946.67 | 0.00 | 0.00 | 0.00 |
Max | 7813.33 | 3373.83 | 914.67 | 3.17 | 0.00 |
Average | 6358.94 | 2095.11 | 304.89 | 1.06 | 0.00 |
Sum | 19076.83 | 6285.33 | 914.67 | 3.17 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 75166.00 | 7553.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 86103.67 | 68920.50 | 35981.67 | 187.17 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 86103.67 | 68920.50 | 35981.67 | 187.17 | 0.00 |
Average | 64765.56 | 25491.17 | 11993.89 | 62.39 | 0.00 |
Sum | 194296.67 | 76473.50 | 35981.67 | 187.17 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 7646.67 | 1113.33 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7708.17 | 1051.83 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 5865.50 | 2816.83 | 77.67 | 0.00 | 0.00 |
Min | 5865.50 | 1051.83 | 0.00 | 0.00 | 0.00 |
Max | 7708.17 | 2816.83 | 77.67 | 0.00 | 0.00 |
Average | 7073.44 | 1660.67 | 25.89 | 0.00 | 0.00 |
Sum | 21220.33 | 4982.00 | 77.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 33023.17 | 3.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 72951.00 | 9768.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 115094.33 | 71807.50 | 4291.17 | 0.00 | 0.00 |
Min | 33023.17 | 3.83 | 0.00 | 0.00 | 0.00 |
Max | 115094.33 | 71807.50 | 4291.17 | 0.00 | 0.00 |
Average | 73689.50 | 27193.11 | 1430.39 | 0.00 | 0.00 |
Sum | 221068.50 | 81579.33 | 4291.17 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.251719E+10 | 6937.30 | 31-JAN-16:30 | 29.00 | 10.73 | 0.618438E+09 | 769.01 | 21-JAN-11:00 | 29.00 | 10.73 |
February | 0.144458E+10 | 5211.83 | 25-FEB-17:00 | 17.00 | 8.59 | 0.568701E+09 | 769.02 | 15-FEB-15:20 | 17.00 | 8.59 |
March | 0.295749E+10 | 7875.44 | 18-MAR-16:00 | 27.20 | 11.10 | 0.672012E+09 | 780.00 | 28-MAR-12:09 | 18.48 | 7.20 |
April | 0.709233E+10 | 25516.11 | 15-APR-05:01 | 20.83 | 11.87 | 0.634366E+09 | 769.34 | 18-APR-07:10 | 17.50 | 10.29 |
May | 0.919572E+10 | 25394.32 | 30-MAY-05:01 | 18.00 | 8.75 | 0.660394E+09 | 768.97 | 01-MAY-12:09 | 18.00 | 8.75 |
June | 0.122376E+11 | 25895.22 | 19-JUN-05:01 | 22.17 | 10.17 | 0.660702E+09 | 769.04 | 30-JUN-08:20 | 31.67 | 19.56 |
July | 0.115926E+11 | 26494.48 | 11-JUL-05:01 | 26.00 | 16.96 | 0.635406E+09 | 769.09 | 14-JUL-15:50 | 29.83 | 20.34 |
August | 0.118143E+11 | 27071.81 | 14-AUG-05:01 | 26.00 | 16.58 | 0.686202E+09 | 769.08 | 07-AUG-12:20 | 26.00 | 16.58 |
September | 0.100816E+11 | 26634.42 | 27-SEP-05:01 | 20.00 | 13.62 | 0.635277E+09 | 769.10 | 11-SEP-12:09 | 20.00 | 13.62 |
October | 0.635401E+10 | 26700.29 | 05-OCT-05:01 | 19.00 | 13.00 | 0.632015E+09 | 769.08 | 03-OCT-12:20 | 19.00 | 13.00 |
November | 0.335926E+10 | 21618.96 | 01-NOV-05:02 | 19.67 | 14.77 | 0.601677E+09 | 769.04 | 02-NOV-09:00 | 23.00 | 15.53 |
December | 0.169548E+10 | 6003.95 | 22-DEC-16:30 | 24.50 | 9.81 | 0.612011E+09 | 768.96 | 04-DEC-16:40 | 24.50 | 9.81 |
Annual Sum or Average | 0.803421E+11 | 0.761720E+10 | ||||||||
Minimum of Months | 0.144458E+10 | 5211.83 | 17.00 | 8.59 | 0.568701E+09 | 768.96 | 17.00 | 7.20 | ||
Maximum of Months | 0.122376E+11 | 27071.81 | 29.00 | 16.96 | 0.686202E+09 | 780.00 | 31.67 | 20.34 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.262595E+10 | 13687.35 | 31-JAN-15:50 | 28.83 | 10.78 | 0.169084E+10 | 2246.87 | 09-JAN-15:20 | 28.83 | 10.78 |
February | 0.723880E+09 | 9565.40 | 23-FEB-14:00 | 18.00 | 10.78 | 0.152032E+10 | 2246.85 | 22-FEB-15:09 | 18.00 | 10.78 |
March | 0.403286E+10 | 39024.24 | 18-MAR-17:10 | 26.92 | 12.85 | 0.186768E+10 | 2246.90 | 18-MAR-12:09 | 26.92 | 12.85 |
April | 0.244766E+11 | 88537.21 | 25-APR-17:05 | 32.83 | 15.34 | 0.184436E+10 | 2246.80 | 26-APR-15:00 | 26.00 | 9.66 |
May | 0.352487E+11 | 88634.72 | 29-MAY-11:32 | 29.67 | 13.02 | 0.192617E+10 | 2246.80 | 27-MAY-12:09 | 29.67 | 13.02 |
June | 0.533217E+11 | 89861.00 | 18-JUN-08:23 | 31.00 | 17.21 | 0.192886E+10 | 2247.00 | 30-JUN-08:39 | 32.33 | 19.42 |
July | 0.509153E+11 | 92253.78 | 18-JUL-18:22 | 36.50 | 20.23 | 0.185476E+10 | 2247.14 | 15-JUL-13:39 | 36.50 | 20.23 |
August | 0.476754E+11 | 93218.37 | 11-AUG-18:22 | 36.00 | 19.44 | 0.200314E+10 | 2247.11 | 03-AUG-13:20 | 36.00 | 19.44 |
September | 0.381121E+11 | 93226.35 | 08-SEP-18:22 | 35.80 | 20.05 | 0.185428E+10 | 2247.14 | 05-SEP-14:30 | 35.80 | 20.05 |
October | 0.182311E+11 | 91175.21 | 04-OCT-17:05 | 33.83 | 17.44 | 0.182188E+10 | 2247.11 | 03-OCT-12:39 | 33.83 | 17.44 |
November | 0.501188E+10 | 30073.73 | 01-NOV-17:12 | 25.33 | 14.39 | 0.169742E+10 | 2246.99 | 01-NOV-13:20 | 25.33 | 14.39 |
December | 0.763510E+09 | 9088.02 | 22-DEC-15:40 | 25.33 | 10.21 | 0.160194E+10 | 2246.81 | 13-DEC-14:00 | 25.33 | 10.21 |
Annual Sum or Average | 0.281139E+12 | 0.216116E+11 | ||||||||
Minimum of Months | 0.723880E+09 | 9088.02 | 18.00 | 10.21 | 0.152032E+10 | 2246.80 | 18.00 | 9.66 | ||
Maximum of Months | 0.533217E+11 | 93226.35 | 36.50 | 20.23 | 0.200314E+10 | 2247.14 | 36.50 | 20.23 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4.27 | 1.81 | 0.293527E+10 | 5188.02 | 31-JAN-15:30 | 28.50 | 10.89 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 | 4.43 | 0.254801E+10 | 4718.11 | 23-FEB-14:30 | 18.00 | 10.57 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 | 8.83 | 0.369320E+10 | 6271.43 | 18-MAR-15:20 | 27.20 | 12.06 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 | 7.34 | 0.524813E+10 | 8928.58 | 14-APR-15:30 | 35.00 | 14.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 | 7.18 | 0.617529E+10 | 9097.65 | 15-MAY-14:09 | 36.00 | 14.79 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 | 11.09 | 0.708127E+10 | 9097.65 | 01-JUN-12:30 | 36.00 | 16.80 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 | 14.60 | 0.661748E+10 | 9097.65 | 01-JUL-12:09 | 35.33 | 13.39 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.35 | 0.708886E+10 | 9097.65 | 01-AUG-13:30 | 35.50 | 21.37 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 | 16.66 | 0.617097E+10 | 9097.65 | 01-SEP-13:09 | 35.27 | 21.95 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 | 15.51 | 0.482809E+10 | 8984.61 | 06-OCT-14:09 | 35.00 | 15.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 | 10.27 | 0.340469E+10 | 6233.72 | 01-NOV-15:09 | 28.83 | 16.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 | 2.98 | 0.246761E+10 | 4440.49 | 01-DEC-14:30 | 23.50 | 10.17 |
Annual Sum or Average | 0.00 | 0.582589E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.27 | 1.81 | 0.246761E+10 | 4440.49 | 18.00 | 10.17 | ||
Maximum of Months | 0.00 | 0.00 | 29.40 | 18.35 | 0.708886E+10 | 9097.65 | 36.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.470357E+09 | 34015.95 | 03-JAN-06:01 | 8.33 |
February | 0.441952E+09 | 32856.52 | 06-FEB-06:02 | 9.00 |
March | 0.391052E+09 | 32655.49 | 27-MAR-05:01 | 2.52 |
April | 23695089.53 | 1143.32 | 04-APR-06:10 | 15.33 |
May | 725105.60 | 612.15 | 01-MAY-06:07 | 13.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 42293870.21 | 5155.30 | 25-OCT-06:10 | 5.00 |
November | 0.167695E+09 | 25109.66 | 24-NOV-06:02 | 3.17 |
December | 0.704124E+09 | 33520.55 | 18-DEC-06:01 | 3.83 |
Annual Sum or Average | 0.224189E+10 | |||
Minimum of Months | 0.00 | 0.00 | 2.52 | |
Maximum of Months | 0.704124E+09 | 34015.95 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.297848E+10 | 61275.21 | 01-JAN-06:43 | 1.38 |
February | 0.271819E+10 | 8791.50 | 11-FEB-07:25 | 14.50 |
March | 0.209911E+10 | 8841.14 | 20-MAR-06:25 | 11.35 |
April | 0.529201E+09 | 8813.16 | 05-APR-06:25 | 16.50 |
May | 0.103521E+09 | 8351.31 | 01-MAY-06:25 | 14.50 |
June | 213219.78 | 1262.00 | 22-JUN-06:04 | 22.67 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 457539.65 | 2213.76 | 19-AUG-06:04 | 23.00 |
September | 13782675.02 | 6428.48 | 15-SEP-06:05 | 17.88 |
October | 0.719092E+09 | 8944.84 | 20-OCT-06:25 | 15.00 |
November | 0.152974E+10 | 8707.51 | 13-NOV-07:25 | 16.00 |
December | 0.323602E+10 | 8836.48 | 04-DEC-07:25 | 3.00 |
Annual Sum or Average | 0.139278E+11 | |||
Minimum of Months | 0.00 | 0.00 | 1.38 | |
Maximum of Months | 0.323602E+10 | 61275.21 | 27.73 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.142890E+09 | 14795.11 | 01-JAN-07:27 | 1.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.142890E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.00 | |
Maximum of Months | 0.142890E+09 | 14795.11 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.258145E+10 | 1955.04 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.235440E+10 | 1955.04 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.269003E+10 | 1955.04 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.254196E+10 | 1955.04 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.263574E+10 | 1955.04 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.259625E+10 | 1955.04 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.258145E+10 | 1955.04 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.269003E+10 | 1955.04 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.254196E+10 | 1955.04 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.258145E+10 | 1955.04 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.248766E+10 | 1955.04 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.258145E+10 | 1955.04 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.308638E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.235440E+10 | 1955.04 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.269003E+10 | 1955.04 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.198922E+11 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.182065E+11 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.210336E+11 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.197108E+11 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.204629E+11 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.202815E+11 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.198922E+11 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.210336E+11 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.197108E+11 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.198922E+11 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.191400E+11 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.198922E+11 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.239148E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.182065E+11 | 17848.24 | 0.00 | 0.00 | |
Maximum of Months | 0.210336E+11 | 17848.24 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.294120E+11 | 26389.90 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.269196E+11 | 26389.90 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.310997E+11 | 26389.90 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.291438E+11 | 26389.90 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.302559E+11 | 26389.90 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.299876E+11 | 26389.90 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.294120E+11 | 26389.90 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.310997E+11 | 26389.90 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.291438E+11 | 26389.90 | 01-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.294120E+11 | 26389.90 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.282999E+11 | 26389.90 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.294120E+11 | 26389.90 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.353598E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.269196E+11 | 26389.90 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.310997E+11 | 26389.90 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21848014.07 | 0.178251E+10 |
February | 0.127628E+10 | 0.235440E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196088E+10 |
March | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64638733.07 | 0.206104E+10 |
April | 0.138726E+10 | 0.254196E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595442E+09 | 0.804751E+09 |
May | 0.144276E+10 | 0.263574E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107633E+10 | 0.472980E+09 |
June | 0.144276E+10 | 0.259625E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196221E+10 | 0.151076E+09 |
July | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159181E+10 | 0.164111E+09 |
August | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144653E+10 | 0.226607E+09 |
September | 0.138726E+10 | 0.254196E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103249E+10 | 0.377981E+09 |
October | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430895E+09 | 0.121153E+10 |
November | 0.133177E+10 | 0.248766E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44750219.54 | 0.178416E+10 |
December | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2388398.05 | 0.213037E+10 |
Annual Sum or Average | 0.168137E+11 | 0.308638E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826934E+10 | 0.131280E+11 |
Minimum of Months | 0.127628E+10 | 0.235440E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151076E+09 |
Maximum of Months | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196221E+10 | 0.213037E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5768096.75 | 0.671099E+10 |
February | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637366E+10 |
March | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24949094.67 | 0.810836E+10 |
April | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122064E+10 | 0.338158E+10 |
May | 0.339505E+10 | 0.204629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274794E+10 | 0.205396E+10 |
June | 0.339505E+10 | 0.202815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584808E+10 | 0.648135E+09 |
July | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492031E+10 | 0.607940E+09 |
August | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335732E+10 | 0.979888E+09 |
September | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245144E+10 | 0.162849E+10 |
October | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.781185E+09 | 0.502246E+10 |
November | 0.313390E+10 | 0.191400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9572888.56 | 0.695067E+10 |
December | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1312599.67 | 0.651692E+10 |
Annual Sum or Average | 0.395654E+11 | 0.239148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213685E+11 | 0.489831E+11 |
Minimum of Months | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.607940E+09 |
Maximum of Months | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584808E+10 | 0.810836E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553728E+09 | 0.146344E+11 |
February | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174201E+11 |
March | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85889457.05 | 0.245730E+11 |
April | 0.750829E+10 | 0.291438E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177907E+09 | 0.159018E+11 |
May | 0.780862E+10 | 0.302559E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17741771.29 | 0.121542E+11 |
June | 0.780862E+10 | 0.299876E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171691E+09 | 0.605783E+10 |
July | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126447E+09 | 0.681395E+10 |
August | 0.810895E+10 | 0.310997E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118576E+09 | 0.824927E+10 |
September | 0.750829E+10 | 0.291438E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36097464.13 | 0.111702E+11 |
October | 0.750829E+10 | 0.294120E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31433805.42 | 0.209293E+11 |
November | 0.720796E+10 | 0.282999E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74204845.33 | 0.203725E+11 |
December | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188179E+09 | 0.151017E+11 |
Annual Sum or Average | 0.910005E+11 | 0.353598E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158189E+10 | 0.173378E+12 |
Minimum of Months | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605783E+10 |
Maximum of Months | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553728E+09 | 0.245730E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1955.04 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1602.40 | 31-JAN-17:10 | 6467.89 | 12-JAN-07:05 |
February | 1680.92 | 01-FEB-08:09 | 1955.04 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6850.38 | 01-FEB-08:00 |
March | 1680.92 | 01-MAR-08:09 | 1955.04 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1905.26 | 16-MAR-16:10 | 8268.73 | 27-MAR-06:05 |
April | 1680.92 | 01-APR-07:10 | 1955.04 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4271.00 | 10-APR-16:10 | 5559.56 | 21-APR-06:05 |
May | 1680.92 | 01-MAY-07:10 | 1955.04 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5523.34 | 18-MAY-16:10 | 4077.91 | 01-MAY-06:03 |
June | 1680.92 | 01-JUN-07:10 | 1955.04 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8581.61 | 30-JUN-16:10 | 1845.16 | 21-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 1955.04 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7499.93 | 20-JUL-17:00 | 1128.51 | 17-JUL-19:52 |
August | 1680.92 | 01-AUG-07:10 | 1955.04 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7290.78 | 25-AUG-17:00 | 1753.72 | 24-AUG-06:10 |
September | 1680.92 | 01-SEP-07:10 | 1955.04 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6063.03 | 08-SEP-16:10 | 2771.53 | 22-SEP-06:05 |
October | 1680.92 | 02-OCT-07:10 | 1955.04 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4624.74 | 04-OCT-17:00 | 6827.75 | 25-OCT-06:03 |
November | 1680.92 | 01-NOV-07:10 | 1955.04 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.16 | 01-NOV-16:10 | 6776.49 | 24-NOV-07:40 |
December | 1680.92 | 01-DEC-08:09 | 1955.04 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 146.16 | 21-DEC-15:00 | 8344.13 | 14-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1128.51 | |||||
Maximum of Months | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 8581.61 | 8344.13 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 674.81 | 31-JAN-16:50 | 9242.35 | 11-JAN-08:00 |
February | 3955.50 | 01-FEB-08:09 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 14294.28 | 02-FEB-16:55 |
March | 3955.50 | 01-MAR-08:09 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1195.94 | 16-MAR-16:00 | 11666.38 | 11-MAR-16:10 |
April | 3955.50 | 01-APR-07:10 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6721.44 | 10-APR-16:00 | 7781.20 | 28-APR-07:00 |
May | 3955.50 | 01-MAY-07:10 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9306.01 | 10-MAY-16:00 | 5617.53 | 23-MAY-06:10 |
June | 3955.50 | 01-JUN-07:10 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17955.74 | 30-JUN-16:00 | 3392.02 | 13-JUN-06:10 |
July | 3955.50 | 01-JUL-07:10 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18139.32 | 22-JUL-16:00 | 4720.55 | 26-JUL-24:00 |
August | 3955.50 | 01-AUG-07:10 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12615.26 | 12-AUG-16:00 | 9324.72 | 28-AUG-16:52 |
September | 3955.50 | 01-SEP-07:10 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10604.32 | 01-SEP-16:00 | 5300.28 | 15-SEP-07:00 |
October | 3955.50 | 02-OCT-07:10 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6816.63 | 10-OCT-15:10 | 11659.16 | 25-OCT-17:00 |
November | 3955.50 | 01-NOV-07:10 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 967.46 | 01-NOV-15:40 | 11114.78 | 29-NOV-08:00 |
December | 3955.50 | 01-DEC-08:09 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.01 | 25-DEC-14:00 | 10108.60 | 07-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3392.02 | ||||
Maximum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18139.32 | 14294.28 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 26389.90 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10115.86 | 06-JAN-13:10 | 19324.55 | 11-JAN-08:70 |
February | 9097.65 | 01-FEB-08:09 | 26389.90 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 37815.22 | 02-FEB-12:00 |
March | 9097.65 | 01-MAR-08:09 | 26389.90 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3766.22 | 15-MAR-15:00 | 34908.67 | 24-MAR-14:00 |
April | 9097.65 | 01-APR-07:10 | 26389.90 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7129.66 | 01-APR-14:50 | 27232.06 | 26-APR-18:00 |
May | 9097.65 | 01-MAY-07:10 | 26389.90 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1227.52 | 15-MAY-17:00 | 19560.52 | 23-MAY-05:00 |
June | 9097.65 | 01-JUN-07:10 | 26389.90 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2788.95 | 16-JUN-16:00 | 14231.14 | 13-JUN-06:00 |
July | 9097.65 | 01-JUL-07:10 | 26389.90 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1982.57 | 30-JUL-18:00 | 24123.18 | 17-JUL-20:00 |
August | 9097.65 | 01-AUG-07:10 | 26389.90 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2041.86 | 25-AUG-17:00 | 36215.02 | 28-AUG-17:00 |
September | 9097.65 | 01-SEP-07:10 | 26389.90 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2953.54 | 17-SEP-11:53 | 22686.06 | 03-SEP-05:00 |
October | 9097.65 | 02-OCT-07:10 | 26389.90 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2014.97 | 01-OCT-13:00 | 46685.30 | 07-OCT-14:51 |
November | 9097.65 | 01-NOV-07:10 | 26389.90 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3935.06 | 19-NOV-15:00 | 54687.97 | 22-NOV-11:55 |
December | 9097.65 | 01-DEC-08:09 | 26389.90 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4443.48 | 21-DEC-14:00 | 21958.87 | 07-DEC-08:70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14231.14 | |||||
Maximum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 10115.86 | 54687.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6937.30 | 31-JAN-16:30 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 478.61 | 0.00 |
February | 5211.83 | 25-FEB-17:00 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.17 |
March | 7875.44 | 18-MAR-16:00 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 116.85 | 0.00 |
April | 25516.11 | 15-APR-05:01 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.37 |
May | 25394.32 | 30-MAY-05:01 | 1664.11 | 5255.76 | 5163.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 729.86 |
June | 25895.22 | 19-JUN-05:01 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 538.93 |
July | 26494.48 | 11-JUL-05:01 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.42 |
August | 27071.81 | 14-AUG-05:01 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.89 |
September | 26634.42 | 27-SEP-05:01 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 685.03 |
October | 26700.29 | 05-OCT-05:01 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 709.91 |
November | 21618.96 | 01-NOV-05:02 | 924.51 | 2919.87 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.57 |
December | 6003.95 | 22-DEC-16:30 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 45.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5211.83 | 924.51 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27071.81 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 478.61 | 729.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13687.35 | 31-JAN-15:50 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.21 | 0.00 |
February | 9565.40 | 23-FEB-14:00 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.10 |
March | 39024.24 | 18-MAR-17:10 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.82 | 0.00 |
April | 88537.21 | 25-APR-17:05 | 0.00 | 12598.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3288.79 | 0.00 |
May | 88634.72 | 29-MAY-11:32 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1597.70 | 0.00 |
June | 89861.00 | 18-JUN-08:23 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2838.10 | 0.00 |
July | 92253.78 | 18-JUL-18:22 | 0.00 | 10498.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5216.87 | 0.00 |
August | 93218.37 | 11-AUG-18:22 | 0.00 | 10498.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2829.99 | 0.00 |
September | 93226.35 | 08-SEP-18:22 | 0.00 | 10498.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2729.13 | 0.00 |
October | 91175.21 | 04-OCT-17:05 | 0.00 | 12598.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5081.56 | 0.00 |
November | 30073.73 | 01-NOV-17:12 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1039.17 |
December | 9088.02 | 22-DEC-15:40 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 9088.02 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 93226.35 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5216.87 | 1039.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 9314.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9875.50 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8841.20 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7073.71 |
April | 0.00 | 01-APR-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6039.62 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7805.23 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2854.47 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3669.65 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1323.10 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2821.23 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.68 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3911.76 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7386.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1323.10 | |
Maximum of Months | 0.00 | 0.00 | 9314.08 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9875.50 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.919409E+11 | 78828.53 | 31-JAN-15:00 | 0.155988E+10 | 47260.48 | 01-JAN-07:30 |
February | 0.820075E+11 | 74347.20 | 16-FEB-13:30 | 0.490550E+09 | 9661.36 | 28-FEB-07:10 |
March | 0.955388E+11 | 80960.32 | 18-MAR-14:20 | 0.490517E+09 | 14638.23 | 27-MAR-06:10 |
April | 0.100660E+12 | 93524.79 | 14-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.110706E+12 | 95642.55 | 18-MAY-14:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.122454E+12 | 104406.17 | 28-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.120323E+12 | 100927.02 | 19-JUL-13:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.123687E+12 | 101476.77 | 25-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.111788E+12 | 97994.17 | 08-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.996128E+11 | 94307.20 | 02-OCT-13:00 | 26654665.28 | 4794.29 | 25-OCT-06:49 |
November | 0.890315E+11 | 82372.33 | 01-NOV-14:39 | 0.160480E+09 | 10951.62 | 24-NOV-07:10 |
December | 0.905850E+11 | 75913.77 | 22-DEC-15:30 | 0.884335E+09 | 16755.11 | 07-DEC-07:10 |
Annual Sum or Average | 0.123833E+13 | 0.361242E+10 | ||||
Minimum of Months | 0.820075E+11 | 74347.20 | 0.00 | 0.00 | ||
Maximum of Months | 0.123687E+12 | 104406.17 | 0.155988E+10 | 47260.48 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.518856E+11 | 0.131413E+11 | 0.115358E+11 | 0.00 | 0.104910E+11 | 0.00 | 0.00 | 0.273435E+10 | 0.00 | 0.00 | 0.00 | 0.215290E+10 | 0.00 |
February | 0.474804E+11 | 0.112728E+11 | 0.105871E+11 | 0.00 | 0.961200E+10 | 0.00 | 0.00 | 0.110476E+10 | 0.00 | 0.00 | 0.00 | 0.195040E+10 | 0.00 |
March | 0.548234E+11 | 0.115902E+11 | 0.123431E+11 | 0.00 | 0.112904E+11 | 0.00 | 0.00 | 0.333316E+10 | 0.00 | 0.00 | 0.00 | 0.215861E+10 | 0.00 |
April | 0.513965E+11 | 0.103052E+11 | 0.114862E+11 | 0.00 | 0.126537E+11 | 0.00 | 0.00 | 0.128203E+11 | 0.00 | 0.00 | 0.00 | 0.199794E+10 | 0.00 |
May | 0.533545E+11 | 0.986495E+10 | 0.119357E+11 | 0.00 | 0.148824E+11 | 0.00 | 0.00 | 0.186621E+11 | 0.00 | 0.00 | 0.00 | 0.200673E+10 | 0.00 |
June | 0.528654E+11 | 0.921992E+10 | 0.118862E+11 | 0.00 | 0.175437E+11 | 0.00 | 0.00 | 0.290326E+11 | 0.00 | 0.00 | 0.00 | 0.190639E+10 | 0.00 |
July | 0.518856E+11 | 0.964994E+10 | 0.115358E+11 | 0.00 | 0.173102E+11 | 0.00 | 0.00 | 0.280314E+11 | 0.00 | 0.00 | 0.00 | 0.190994E+10 | 0.00 |
August | 0.548234E+11 | 0.102950E+11 | 0.123357E+11 | 0.00 | 0.171891E+11 | 0.00 | 0.00 | 0.270876E+11 | 0.00 | 0.00 | 0.00 | 0.195599E+10 | 0.00 |
September | 0.513965E+11 | 0.108120E+11 | 0.114788E+11 | 0.00 | 0.147993E+11 | 0.00 | 0.00 | 0.213932E+11 | 0.00 | 0.00 | 0.00 | 0.190805E+10 | 0.00 |
October | 0.518856E+11 | 0.121226E+11 | 0.115432E+11 | 0.00 | 0.119252E+11 | 0.00 | 0.00 | 0.101214E+11 | 0.00 | 0.00 | 0.00 | 0.201488E+10 | 0.00 |
November | 0.499276E+11 | 0.125270E+11 | 0.110862E+11 | 0.00 | 0.100281E+11 | 0.00 | 0.00 | 0.345476E+10 | 0.00 | 0.00 | 0.00 | 0.200775E+10 | 0.00 |
December | 0.518856E+11 | 0.133922E+11 | 0.115358E+11 | 0.00 | 0.104519E+11 | 0.00 | 0.00 | 0.118798E+10 | 0.00 | 0.00 | 0.00 | 0.213147E+10 | 0.00 |
Annual Sum or Average | 0.623610E+12 | 0.134193E+12 | 0.139290E+12 | 0.00 | 0.158177E+12 | 0.00 | 0.00 | 0.158963E+12 | 0.00 | 0.00 | 0.00 | 0.241010E+11 | 0.00 |
Minimum of Months | 0.474804E+11 | 0.921992E+10 | 0.105871E+11 | 0.00 | 0.961200E+10 | 0.00 | 0.00 | 0.110476E+10 | 0.00 | 0.00 | 0.00 | 0.190639E+10 | 0.00 |
Maximum of Months | 0.548234E+11 | 0.133922E+11 | 0.123431E+11 | 0.00 | 0.175437E+11 | 0.00 | 0.00 | 0.290326E+11 | 0.00 | 0.00 | 0.00 | 0.215861E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.155988E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.490550E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.490517E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 26654665.28 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.160480E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.884335E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.361242E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.155988E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 46193.18 | 02-JAN-09:09 | 8532.22 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 10548.61 | 13-JAN-15:20 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 46193.18 | 01-FEB-09:09 | 8532.22 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 10548.61 | 01-FEB-11:50 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 46193.18 | 01-MAR-09:09 | 8532.22 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 11701.26 | 18-MAR-15:20 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 46193.18 | 01-APR-08:09 | 8532.22 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 12853.91 | 03-APR-12:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 46193.18 | 01-MAY-08:09 | 8532.22 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 12853.91 | 19-MAY-16:49 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 46193.18 | 01-JUN-08:09 | 8532.22 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 12853.91 | 01-JUN-14:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 46193.18 | 01-JUL-08:09 | 8532.22 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 12853.91 | 08-JUL-10:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 46193.18 | 01-AUG-08:09 | 8532.22 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 12853.91 | 03-AUG-12:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 46193.18 | 01-SEP-08:09 | 8532.22 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 12853.91 | 06-SEP-11:20 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 46193.18 | 02-OCT-08:09 | 8532.22 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 12853.91 | 04-OCT-11:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 46193.18 | 01-NOV-08:09 | 8532.22 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 10548.61 | 01-NOV-09:39 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 46193.18 | 01-DEC-09:09 | 8532.22 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 10548.61 | 01-DEC-11:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 46193.18 | 8532.22 | 10112.62 | 0.00 | 10548.61 | 0.00 | 0.00 | |||||
Maximum of Months | 46193.18 | 8532.22 | 10112.62 | 0.00 | 12853.91 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 10215.79 | 31-JAN-15:00 | 0.00 | 0.00 | 0.00 | 1795.28 | 23-JAN-12:09 | 0.00 |
February | 5768.21 | 22-FEB-15:00 | 0.00 | 0.00 | 0.00 | 1794.68 | 02-FEB-12:39 | 0.00 |
March | 12191.14 | 18-MAR-14:00 | 0.00 | 0.00 | 0.00 | 1784.94 | 01-MAR-12:09 | 0.00 |
April | 23406.24 | 14-APR-15:00 | 0.00 | 0.00 | 0.00 | 1763.77 | 01-APR-11:20 | 0.00 |
May | 26601.33 | 18-MAY-15:09 | 0.00 | 0.00 | 0.00 | 1738.74 | 01-MAY-11:39 | 0.00 |
June | 36866.88 | 30-JUN-15:00 | 0.00 | 0.00 | 0.00 | 1715.50 | 01-JUN-11:20 | 0.00 |
July | 32868.30 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | 1701.03 | 01-JUL-11:30 | 0.00 |
August | 33174.69 | 25-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1706.40 | 31-AUG-11:30 | 0.00 |
September | 29206.83 | 08-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1725.16 | 30-SEP-11:00 | 0.00 |
October | 24348.51 | 06-OCT-15:09 | 0.00 | 0.00 | 0.00 | 1750.37 | 31-OCT-11:39 | 0.00 |
November | 13966.08 | 01-NOV-14:00 | 0.00 | 0.00 | 0.00 | 1773.63 | 30-NOV-12:09 | 0.00 |
December | 7307.30 | 22-DEC-15:30 | 0.00 | 0.00 | 0.00 | 1790.18 | 30-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5768.21 | 0.00 | 0.00 | 0.00 | 1701.03 | 0.00 | ||
Maximum of Months | 36866.88 | 0.00 | 0.00 | 0.00 | 1795.28 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 78828.53 | 31-JAN-15:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 10548.61 | 0.00 | 0.00 | 10215.79 | 0.00 |
February | 74347.20 | 16-FEB-13:30 | 46193.18 | 10112.62 | 0.00 | 0.00 | 10548.61 | 0.00 | 0.00 | 5738.49 | 0.00 |
March | 80960.32 | 18-MAR-14:20 | 46193.18 | 10112.62 | 0.00 | 0.00 | 11317.04 | 0.00 | 0.00 | 11596.60 | 0.00 |
April | 93524.79 | 14-APR-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 12853.91 | 0.00 | 0.00 | 22642.26 | 0.00 |
May | 95642.55 | 18-MAY-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 12853.91 | 0.00 | 0.00 | 24783.47 | 0.00 |
June | 104406.17 | 28-JUN-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 12853.91 | 0.00 | 0.00 | 33566.61 | 0.00 |
July | 100927.02 | 19-JUL-13:39 | 46193.18 | 10112.62 | 0.00 | 0.00 | 12853.91 | 0.00 | 0.00 | 30112.44 | 0.00 |
August | 101476.77 | 25-AUG-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 12853.91 | 0.00 | 0.00 | 30635.84 | 0.00 |
September | 97994.17 | 08-SEP-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 12853.91 | 0.00 | 0.00 | 27147.30 | 0.00 |
October | 94307.20 | 02-OCT-13:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 12853.91 | 0.00 | 0.00 | 23471.38 | 0.00 |
November | 82372.33 | 01-NOV-14:39 | 46193.18 | 10112.62 | 0.00 | 0.00 | 10548.61 | 0.00 | 0.00 | 13796.73 | 0.00 |
December | 75913.77 | 22-DEC-15:30 | 46193.18 | 10112.62 | 0.00 | 0.00 | 10548.61 | 0.00 | 0.00 | 7307.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 74347.20 | 46193.18 | 10112.62 | 0.00 | 0.00 | 10548.61 | 0.00 | 0.00 | 5738.49 | 0.00 | |
Maximum of Months | 104406.17 | 46193.18 | 10112.62 | 0.00 | 0.00 | 12853.91 | 0.00 | 0.00 | 33566.61 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 47260.48 | 01-JAN-07:30 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 9661.36 | 28-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 14638.23 | 27-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 4794.29 | 25-OCT-06:49 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 10951.62 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 16755.11 | 07-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 47260.48 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 19.67 | 1.33 | 19.95 | 0.00 | 19.95 | 0.00 | 19.95 |
February | 0.50 | 20.51 | 0.50 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
March | 1.17 | 20.45 | 1.17 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.61 | 0.83 | 24.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 25.60 | 2.83 | 25.14 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 27.61 | 7.67 | 26.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 27.63 | 8.17 | 26.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 26.69 | 8.50 | 25.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 25.11 | 6.67 | 24.99 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.14 | 2.00 | 24.94 |
November | 0.17 | 20.53 | 0.17 | 20.53 | 0.33 | 22.54 | 0.33 | 23.21 |
December | 1.83 | 20.33 | 1.83 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
Annual Sum or Average | 5.17 | 20.19 | 5.00 | 20.28 | 59.67 | 25.90 | 37.00 | 25.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.95 | 0.00 | 19.95 |
Maximum of Months | 1.83 | 20.53 | 1.83 | 20.53 | 16.83 | 27.63 | 8.50 | 26.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.83 | 14.79 | 0.33 | 14.79 | 0.00 | 14.79 | 0.00 | 14.79 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.00 | 27.31 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 27.67 | 0.00 | 27.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 34.83 | 27.82 | 0.00 | 27.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 67.00 | 27.98 | 0.33 | 27.98 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 75.33 | 27.89 | 0.50 | 27.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 60.33 | 27.79 | 0.33 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 27.68 | 0.17 | 27.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.64 | 0.00 | 27.64 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.83 | 14.79 | 0.33 | 14.79 | 318.50 | 27.66 | 1.33 | 27.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.83 | 14.79 | 0.33 | 14.79 | 75.33 | 27.98 | 0.50 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 244.00 | 23.15 | 28.17 | 22.94 | 28.17 | 22.77 |
February | 240.50 | 23.18 | 19.50 | 23.03 | 19.50 | 22.89 |
March | 231.50 | 23.20 | 36.00 | 23.11 | 18.17 | 22.98 |
April | 54.83 | 23.77 | 124.67 | 23.86 | 0.00 | 23.86 |
May | 10.67 | 23.90 | 164.50 | 23.90 | 0.00 | 23.90 |
June | 0.00 | 0.00 | 283.67 | 23.93 | 0.00 | 23.93 |
July | 5.33 | 24.22 | 294.33 | 23.94 | 5.33 | 23.94 |
August | 1.83 | 24.15 | 316.83 | 23.93 | 1.83 | 23.93 |
September | 1.67 | 24.36 | 299.17 | 23.93 | 1.67 | 23.93 |
October | 76.17 | 23.39 | 135.83 | 23.73 | 0.00 | 23.73 |
November | 153.67 | 23.24 | 75.17 | 23.31 | 16.17 | 23.20 |
December | 285.00 | 23.11 | 58.67 | 22.78 | 58.67 | 22.55 |
Annual Sum or Average | 1305.17 | 23.22 | 1836.50 | 23.51 | 149.50 | 23.41 |
Minimum of Months | 0.00 | 0.00 | 19.50 | 22.78 | 0.00 | 22.55 |
Maximum of Months | 285.00 | 24.36 | 316.83 | 23.94 | 58.67 | 23.94 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 113.00 | 21.76 | 215.67 | 23.94 | 48.50 | 23.39 |
February | 123.50 | 22.25 | 163.17 | 23.82 | 35.50 | 23.36 |
March | 108.33 | 22.42 | 237.00 | 24.69 | 40.17 | 24.33 |
April | 171.00 | 26.39 | 265.67 | 26.57 | 152.83 | 26.60 |
May | 204.50 | 26.69 | 299.50 | 26.68 | 203.50 | 26.68 |
June | 251.17 | 26.70 | 312.00 | 26.71 | 251.17 | 26.71 |
July | 283.00 | 26.71 | 300.00 | 26.71 | 283.00 | 26.71 |
August | 304.17 | 26.71 | 324.00 | 26.71 | 304.17 | 26.71 |
September | 265.00 | 26.71 | 300.00 | 26.70 | 265.00 | 26.70 |
October | 145.17 | 25.83 | 254.50 | 26.34 | 111.50 | 26.40 |
November | 100.33 | 23.55 | 219.83 | 25.26 | 49.67 | 25.08 |
December | 172.33 | 22.11 | 158.50 | 22.70 | 72.00 | 22.10 |
Annual Sum or Average | 2241.50 | 25.43 | 3049.83 | 25.87 | 1817.00 | 25.87 |
Minimum of Months | 100.33 | 21.76 | 158.50 | 22.70 | 35.50 | 22.10 |
Maximum of Months | 304.17 | 26.71 | 324.00 | 26.71 | 304.17 | 26.71 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 262.83 | 20.62 | 137.33 | 19.83 | 129.83 | 19.34 |
February | 261.50 | 20.57 | 129.00 | 19.90 | 127.17 | 19.54 |
March | 231.33 | 22.18 | 139.83 | 22.48 | 94.83 | 22.24 |
April | 243.00 | 29.91 | 271.33 | 29.80 | 229.17 | 29.95 |
May | 293.50 | 31.52 | 312.00 | 31.38 | 293.50 | 31.43 |
June | 312.00 | 34.51 | 312.00 | 34.51 | 312.00 | 34.51 |
July | 300.00 | 33.58 | 300.00 | 33.58 | 300.00 | 33.58 |
August | 324.00 | 33.37 | 324.00 | 33.37 | 324.00 | 33.37 |
September | 300.00 | 31.96 | 300.00 | 31.96 | 300.00 | 31.96 |
October | 219.33 | 28.48 | 242.67 | 28.66 | 182.67 | 28.91 |
November | 185.83 | 22.21 | 169.67 | 22.93 | 90.50 | 22.60 |
December | 300.00 | 19.41 | 215.00 | 18.85 | 215.00 | 18.61 |
Annual Sum or Average | 3233.33 | 27.80 | 2852.83 | 28.25 | 2598.67 | 28.47 |
Minimum of Months | 185.83 | 19.41 | 129.00 | 18.85 | 90.50 | 18.61 |
Maximum of Months | 324.00 | 34.51 | 324.00 | 34.51 | 324.00 | 34.51 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.358113E+10 | 0.972559E+09 | 214.86 | 0.356629E+10 | 14840696.19 | 0.00 | 0.41 | 31-JAN-16:30 | 0.00 | 01-JAN-00:03 | 9228.36 | 31-JAN-16:30 | 9228.36 | 31-JAN-16:30 | 687.66 | 09-JAN-11:10 | 2690.00 | 31-JAN-16:30 | 0.00 | 01-JAN-00:03 |
February | 0.207920E+10 | 0.564558E+09 | 178.17 | 0.197323E+10 | 0.105977E+09 | 0.00 | 0.27 | 22-FEB-16:00 | 0.00 | 01-FEB-00:10 | 6549.15 | 22-FEB-16:00 | 6518.62 | 22-FEB-16:00 | 1010.50 | 18-FEB-11:20 | 1751.78 | 22-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 0.410599E+10 | 0.112162E+10 | 241.53 | 0.406871E+10 | 37279800.69 | 0.00 | 0.43 | 16-MAR-16:00 | 0.00 | 01-MAR-00:10 | 9962.03 | 18-MAR-16:00 | 9962.03 | 18-MAR-16:00 | 851.62 | 06-MAR-13:20 | 2855.97 | 16-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.902803E+10 | 0.259965E+10 | 283.29 | 0.902803E+10 | -0.0 | 0.00 | 1.00 | 05-APR-05:02 | 0.00 | 01-APR-00:10 | 27795.23 | 15-APR-05:01 | 27795.23 | 15-APR-05:01 | 0.00 | 14-APR-05:03 | 6588.82 | 15-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.116149E+11 | 0.346340E+10 | 324.23 | 0.116149E+11 | -0.0 | 0.00 | 1.00 | 01-MAY-05:02 | 0.00 | 01-MAY-00:10 | 27932.37 | 11-MAY-05:01 | 27932.37 | 11-MAY-05:01 | 0.00 | 17-MAY-05:01 | 6621.12 | 11-MAY-05:01 | 0.00 | 01-MAY-00:10 |
June | 0.153515E+11 | 0.494619E+10 | 379.84 | 0.153288E+11 | 22685946.79 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 28247.80 | 19-JUN-05:01 | 28247.80 | 19-JUN-05:01 | 1610.37 | 17-JUN-16:55 | 8621.91 | 28-JUN-17:39 | 0.00 | 01-JUN-00:10 |
July | 0.157284E+11 | 0.480198E+10 | 366.00 | 0.144443E+11 | 0.128408E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 34663.86 | 14-JUL-05:01 | 29254.49 | 11-JUL-05:01 | 14288.24 | 14-JUL-05:05 | 8281.55 | 16-JUL-16:51 | 0.00 | 01-JUL-00:10 |
August | 0.162064E+11 | 0.492996E+10 | 363.05 | 0.148020E+11 | 0.140445E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 33407.70 | 10-AUG-05:01 | 29792.42 | 14-AUG-05:01 | 11777.55 | 10-AUG-05:04 | 8154.17 | 27-AUG-16:12 | 0.00 | 01-AUG-00:10 |
September | 0.137953E+11 | 0.405834E+10 | 317.50 | 0.125788E+11 | 0.121649E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 33105.48 | 02-SEP-05:01 | 28905.94 | 27-SEP-05:01 | 11248.95 | 02-SEP-05:05 | 7725.31 | 02-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 0.825691E+10 | 0.233557E+10 | 274.42 | 0.800890E+10 | 0.248011E+09 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 31967.34 | 03-OCT-05:01 | 29428.21 | 02-OCT-05:01 | 8305.67 | 03-OCT-05:04 | 7395.40 | 03-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.458653E+10 | 0.123983E+10 | 226.67 | 0.439106E+10 | 0.195470E+09 | 0.00 | 0.91 | 01-NOV-05:02 | 0.00 | 01-NOV-00:10 | 24566.77 | 01-NOV-05:02 | 24566.77 | 01-NOV-05:02 | 2555.10 | 03-NOV-05:03 | 5913.45 | 01-NOV-05:02 | 0.00 | 01-NOV-00:10 |
December | 0.237178E+10 | 0.642814E+09 | 180.00 | 0.236980E+10 | 1983878.04 | 0.00 | 0.34 | 22-DEC-16:20 | 0.00 | 01-DEC-00:10 | 7788.75 | 22-DEC-16:30 | 7788.75 | 22-DEC-16:30 | 302.23 | 13-DEC-11:50 | 2092.75 | 22-DEC-16:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.106706E+12 | 0.316765E+11 | 3349.55 | 0.102175E+12 | 0.453127E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.207920E+10 | 0.564558E+09 | 178.17 | 0.197323E+10 | -0.0 | 0.00 | 0.27 | 0.00 | 6549.15 | 6518.62 | 0.00 | 1751.78 | 0.00 | |||||||
Maximum of Months | 0.162064E+11 | 0.494619E+10 | 379.84 | 0.153288E+11 | 0.140445E+10 | 0.00 | 1.00 | 0.00 | 34663.86 | 29792.42 | 14288.24 | 8621.91 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.588222E+10 | 0.176179E+10 | 141.33 | 0.586437E+10 | 17850148.56 | 0.00 | 0.26 | 31-JAN-16:00 | 0.00 | 01-JAN-00:03 | 23567.32 | 31-JAN-16:00 | 23567.32 | 31-JAN-16:00 | 1068.13 | 09-JAN-12:00 | 7618.01 | 31-JAN-16:00 | 0.00 | 01-JAN-00:03 |
February | 0.182047E+10 | 0.540205E+09 | 69.42 | 0.174887E+10 | 71603088.34 | 0.00 | 0.15 | 23-FEB-14:00 | 0.00 | 01-FEB-00:10 | 14555.01 | 16-FEB-13:30 | 14289.45 | 23-FEB-14:00 | 2099.27 | 18-FEB-11:50 | 4269.08 | 16-FEB-13:30 | 0.00 | 01-FEB-00:10 |
March | 0.734874E+10 | 0.221154E+10 | 154.72 | 0.732234E+10 | 26394403.18 | 0.00 | 0.45 | 18-MAR-17:10 | 0.00 | 01-MAR-00:10 | 44602.23 | 18-MAR-17:10 | 44602.23 | 18-MAR-17:10 | 1188.33 | 18-MAR-10:50 | 13318.11 | 18-MAR-17:10 | 0.00 | 01-MAR-00:10 |
April | 0.319955E+11 | 0.102206E+11 | 308.73 | 0.319955E+11 | -0.0 | 0.00 | 1.00 | 09-APR-13:43 | 0.00 | 01-APR-00:10 | 102223.63 | 25-APR-18:23 | 102223.63 | 25-APR-18:23 | 0.00 | 18-APR-17:05 | 32077.54 | 14-APR-17:04 | 0.00 | 01-APR-00:10 |
May | 0.459258E+11 | 0.151987E+11 | 410.54 | 0.459258E+11 | -0.0 | 0.00 | 1.00 | 03-MAY-17:05 | 0.00 | 01-MAY-00:10 | 103421.25 | 29-MAY-11:32 | 103421.25 | 29-MAY-11:32 | 0.00 | 14-MAY-15:13 | 32858.66 | 15-MAY-17:04 | 0.00 | 01-MAY-00:10 |
June | 0.681935E+11 | 0.240864E+11 | 534.92 | 0.681121E+11 | 81371705.76 | 0.00 | 1.00 | 01-JUN-17:04 | 0.00 | 01-JUN-00:15 | 106713.86 | 17-JUN-19:02 | 105465.59 | 17-JUN-19:02 | 9435.22 | 17-JUN-17:04 | 36200.13 | 28-JUN-17:42 | 0.00 | 01-JUN-00:10 |
July | 0.694497E+11 | 0.232294E+11 | 562.56 | 0.647801E+11 | 0.466959E+10 | 0.00 | 1.00 | 01-JUL-17:04 | 0.00 | 01-JUL-00:13 | 119758.54 | 17-JUL-19:42 | 107135.86 | 09-JUL-12:42 | 29095.15 | 14-JUL-05:05 | 35495.55 | 20-JUL-17:42 | 0.00 | 01-JUL-00:10 |
August | 0.663035E+11 | 0.221576E+11 | 541.91 | 0.616743E+11 | 0.462929E+10 | 0.00 | 1.00 | 01-AUG-17:04 | 0.00 | 01-AUG-00:13 | 115308.90 | 20-AUG-09:43 | 108173.83 | 20-AUG-13:42 | 17458.31 | 09-AUG-19:03 | 35411.35 | 27-AUG-15:32 | 0.00 | 01-AUG-00:10 |
September | 0.535908E+11 | 0.173348E+11 | 473.43 | 0.494145E+11 | 0.417631E+10 | 0.00 | 1.00 | 04-SEP-11:13 | 0.00 | 01-SEP-00:15 | 122030.98 | 04-SEP-11:13 | 108168.66 | 24-SEP-14:02 | 27240.34 | 03-SEP-09:19 | 34244.15 | 07-SEP-17:04 | 0.00 | 01-SEP-00:10 |
October | 0.246748E+11 | 0.778582E+10 | 262.14 | 0.239202E+11 | 0.754659E+09 | 0.00 | 1.00 | 04-OCT-17:05 | 0.00 | 01-OCT-00:15 | 105825.86 | 09-OCT-13:43 | 105825.86 | 09-OCT-13:43 | 9626.29 | 03-OCT-09:00 | 32817.08 | 01-OCT-13:52 | 0.00 | 01-OCT-00:10 |
November | 0.741042E+10 | 0.221493E+10 | 138.96 | 0.726428E+10 | 0.146141E+09 | 0.00 | 0.35 | 01-NOV-15:00 | 0.00 | 01-NOV-00:10 | 34439.95 | 01-NOV-15:00 | 33670.49 | 01-NOV-17:12 | 4950.59 | 13-NOV-16:20 | 10751.88 | 01-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 0.182998E+10 | 0.545169E+09 | 56.92 | 0.182911E+10 | 878630.52 | 0.00 | 0.19 | 22-DEC-15:30 | 0.00 | 01-DEC-00:10 | 17299.37 | 22-DEC-15:30 | 17299.37 | 22-DEC-15:30 | 153.07 | 13-DEC-14:10 | 5240.52 | 22-DEC-15:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.384425E+12 | 0.127287E+12 | 3655.57 | 0.369851E+12 | 0.145741E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.182047E+10 | 0.540205E+09 | 56.92 | 0.174887E+10 | -0.0 | 0.00 | 0.15 | 0.00 | 14555.01 | 14289.45 | 0.00 | 4269.08 | 0.00 | |||||||
Maximum of Months | 0.694497E+11 | 0.240864E+11 | 562.56 | 0.681121E+11 | 0.466959E+10 | 0.00 | 1.00 | 0.00 | 122030.98 | 108173.83 | 29095.15 | 36200.13 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 42.23 | 25.45 | 130.56 | 130.68 | 0.00 | 0.00 | 0.00 |
February | 54.34 | 26.23 | 28.11 | 80.10 | 129.30 | 0.00 | 0.00 | 0.00 |
March | 72.21 | 34.46 | 37.75 | 125.28 | 116.05 | 0.00 | 0.00 | 0.00 |
April | 110.00 | 62.46 | 47.55 | 247.54 | 80.72 | 0.00 | 0.00 | 0.00 |
May | 110.64 | 61.74 | 48.89 | 267.25 | 62.81 | 0.00 | 0.00 | 0.00 |
June | 117.51 | 68.96 | 48.55 | 327.44 | 32.20 | 0.00 | 0.00 | 0.00 |
July | 85.68 | 39.91 | 45.77 | 242.43 | 27.77 | 0.00 | 0.00 | 0.00 |
August | 81.78 | 40.97 | 40.81 | 232.60 | 34.17 | 0.00 | 0.00 | 0.00 |
September | 71.31 | 29.92 | 41.39 | 190.27 | 44.54 | 0.00 | 0.00 | 0.00 |
October | 72.86 | 41.58 | 31.28 | 153.60 | 102.56 | 0.00 | 0.00 | 0.00 |
November | 66.98 | 40.33 | 26.65 | 120.96 | 133.46 | 0.00 | 0.00 | 0.00 |
December | 54.46 | 31.12 | 23.34 | 90.94 | 160.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.55 | 43.39 | 37.16 | 184.53 | 87.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.34 | 26.23 | 23.34 | 80.10 | 27.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 117.51 | 68.96 | 48.89 | 327.44 | 160.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 42.23 | 25.45 | 130.56 | 130.68 | 0.00 | 0.00 | 0.00 |
February | 54.34 | 26.23 | 28.11 | 80.10 | 129.30 | 0.00 | 0.00 | 0.00 |
March | 72.21 | 34.46 | 37.75 | 125.28 | 116.05 | 0.00 | 0.00 | 0.00 |
April | 110.00 | 62.46 | 47.55 | 247.54 | 80.72 | 0.00 | 0.00 | 0.00 |
May | 110.64 | 61.74 | 48.89 | 267.25 | 62.81 | 0.00 | 0.00 | 0.00 |
June | 117.51 | 68.96 | 48.55 | 327.44 | 32.20 | 0.00 | 0.00 | 0.00 |
July | 85.68 | 39.91 | 45.77 | 242.43 | 27.77 | 0.00 | 0.00 | 0.00 |
August | 81.78 | 40.97 | 40.81 | 232.60 | 34.17 | 0.00 | 0.00 | 0.00 |
September | 71.31 | 29.92 | 41.39 | 190.27 | 44.54 | 0.00 | 0.00 | 0.00 |
October | 72.86 | 41.58 | 31.28 | 153.60 | 102.56 | 0.00 | 0.00 | 0.00 |
November | 66.98 | 40.33 | 26.65 | 120.96 | 133.46 | 0.00 | 0.00 | 0.00 |
December | 54.46 | 31.12 | 23.34 | 90.94 | 160.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.55 | 43.39 | 37.16 | 184.53 | 87.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.34 | 26.23 | 23.34 | 80.10 | 27.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 117.51 | 68.96 | 48.89 | 327.44 | 160.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.60 | 0.00 | 11.60 | 9.81 | 77.62 | 0.00 | 0.00 | 0.00 |
February | 13.22 | 0.00 | 13.22 | 5.91 | 78.36 | 0.00 | 0.00 | 0.00 |
March | 17.57 | 0.00 | 17.57 | 18.56 | 70.41 | 0.00 | 0.00 | 0.00 |
April | 21.58 | 0.39 | 21.19 | 42.58 | 46.25 | 0.00 | 0.00 | 0.00 |
May | 25.79 | 2.69 | 23.10 | 60.72 | 33.32 | 0.00 | 0.00 | 0.00 |
June | 29.90 | 6.09 | 23.81 | 99.21 | 17.03 | 0.00 | 0.00 | 0.00 |
July | 25.24 | 3.00 | 22.24 | 82.20 | 15.22 | 0.00 | 0.00 | 0.00 |
August | 20.26 | 0.70 | 19.57 | 68.25 | 19.21 | 0.00 | 0.00 | 0.00 |
September | 18.92 | 0.02 | 18.91 | 55.30 | 25.77 | 0.00 | 0.00 | 0.00 |
October | 14.63 | 0.00 | 14.63 | 23.64 | 61.06 | 0.00 | 0.00 | 0.00 |
November | 12.19 | 0.00 | 12.19 | 8.58 | 80.05 | 0.00 | 0.00 | 0.00 |
December | 10.84 | 0.00 | 10.84 | 5.12 | 96.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 18.50 | 1.08 | 17.42 | 40.15 | 51.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.84 | 0.00 | 10.84 | 5.12 | 15.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 29.90 | 6.09 | 23.81 | 99.21 | 96.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.60 | 0.00 | 11.60 | 9.81 | 77.62 | 0.00 | 0.00 | 0.00 |
February | 13.22 | 0.00 | 13.22 | 5.91 | 78.36 | 0.00 | 0.00 | 0.00 |
March | 17.57 | 0.00 | 17.57 | 18.56 | 70.41 | 0.00 | 0.00 | 0.00 |
April | 21.58 | 0.39 | 21.19 | 42.58 | 46.25 | 0.00 | 0.00 | 0.00 |
May | 25.79 | 2.69 | 23.10 | 60.72 | 33.32 | 0.00 | 0.00 | 0.00 |
June | 29.90 | 6.09 | 23.81 | 99.21 | 17.03 | 0.00 | 0.00 | 0.00 |
July | 25.24 | 3.00 | 22.24 | 82.20 | 15.22 | 0.00 | 0.00 | 0.00 |
August | 20.26 | 0.70 | 19.56 | 68.25 | 19.21 | 0.00 | 0.00 | 0.00 |
September | 18.92 | 0.02 | 18.91 | 55.30 | 25.77 | 0.00 | 0.00 | 0.00 |
October | 14.63 | 0.00 | 14.63 | 23.64 | 61.06 | 0.00 | 0.00 | 0.00 |
November | 12.19 | 0.00 | 12.19 | 8.58 | 80.05 | 0.00 | 0.00 | 0.00 |
December | 10.84 | 0.00 | 10.84 | 5.12 | 96.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 18.50 | 1.08 | 17.42 | 40.14 | 51.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.84 | 0.00 | 10.84 | 5.12 | 15.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 29.90 | 6.09 | 23.81 | 99.21 | 96.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 100.03 | 75.59 | 6.67 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 90.51 | 63.01 | 11.67 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 133.29 | 69.36 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 216.04 | 72.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 238.05 | 69.50 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 258.61 | 51.52 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 209.53 | 39.35 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 194.53 | 47.66 | 0.33 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 153.96 | 49.08 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 128.42 | 79.86 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 92.56 | 77.79 | 16.17 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 82.33 | 85.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 158.47 | 65.06 | 34.83 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 82.33 | 39.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 258.61 | 85.18 | 16.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 100.03 | 75.59 | 6.67 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 90.51 | 63.01 | 11.67 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 133.29 | 69.36 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 216.04 | 72.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 238.05 | 69.50 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 258.61 | 51.52 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 209.53 | 39.35 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 194.53 | 47.66 | 0.33 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 153.96 | 49.08 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 128.42 | 79.86 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 92.56 | 77.79 | 16.17 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 82.33 | 85.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 158.47 | 65.06 | 34.83 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 82.33 | 39.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 258.61 | 85.18 | 16.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 100.03 | 75.59 | 6.67 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 90.51 | 63.01 | 11.67 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 133.29 | 69.36 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 216.04 | 72.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 238.05 | 69.50 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 258.61 | 51.52 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 209.53 | 39.35 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 194.53 | 47.66 | 0.33 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 153.96 | 49.08 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 128.42 | 79.86 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 92.56 | 77.79 | 16.17 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 82.33 | 85.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 158.47 | 65.06 | 34.83 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 82.33 | 39.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 258.61 | 85.18 | 16.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 100.03 | 75.59 | 6.67 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 90.51 | 63.01 | 11.67 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 133.29 | 69.36 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 216.04 | 72.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 238.05 | 69.50 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 258.61 | 51.52 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 209.53 | 39.35 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 194.53 | 47.66 | 0.33 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 153.96 | 49.08 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 128.42 | 79.86 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 92.56 | 77.79 | 16.17 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 82.33 | 85.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 158.47 | 65.06 | 34.83 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 82.33 | 39.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 258.61 | 85.18 | 16.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 100.03 | 75.59 | 6.67 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 90.51 | 63.01 | 11.67 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 133.29 | 69.36 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 216.04 | 72.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 238.05 | 69.50 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 258.61 | 51.52 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 209.53 | 39.35 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 194.53 | 47.66 | 0.33 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 153.96 | 49.08 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 128.42 | 79.86 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 92.56 | 77.79 | 16.17 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 82.33 | 85.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 158.47 | 65.06 | 34.83 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 82.33 | 39.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 258.61 | 85.18 | 16.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 100.03 | 75.59 | 6.67 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 90.51 | 63.01 | 11.67 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 133.29 | 69.36 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 216.04 | 72.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 238.05 | 69.50 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 258.61 | 51.52 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 209.53 | 39.35 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 194.53 | 47.66 | 0.33 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 153.96 | 49.08 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 128.42 | 79.86 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 92.56 | 77.79 | 16.17 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 82.33 | 85.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 158.47 | 65.06 | 34.83 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 82.33 | 39.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 258.61 | 85.18 | 16.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 100.03 | 75.59 | 6.67 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 90.51 | 63.01 | 11.67 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 133.29 | 69.36 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 216.04 | 72.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 238.05 | 69.50 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 258.61 | 51.52 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 209.53 | 39.35 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 194.53 | 47.66 | 0.33 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 153.96 | 49.08 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 128.42 | 79.86 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 92.56 | 77.79 | 16.17 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 82.33 | 85.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 158.47 | 65.06 | 34.83 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 82.33 | 39.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 258.61 | 85.18 | 16.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 100.03 | 75.59 | 6.67 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 90.51 | 63.01 | 11.67 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 133.29 | 69.36 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 216.04 | 72.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 238.05 | 69.50 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 258.61 | 51.52 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 209.53 | 39.35 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 194.53 | 47.66 | 0.33 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 153.96 | 49.08 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 128.42 | 79.86 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 92.56 | 77.79 | 16.17 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 82.33 | 85.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 158.47 | 65.06 | 34.83 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 82.33 | 39.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 258.61 | 85.18 | 16.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 100.03 | 75.59 | 6.67 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 90.51 | 63.01 | 11.67 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 133.29 | 69.36 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 216.04 | 72.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 238.05 | 69.50 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 258.61 | 51.52 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 209.53 | 39.35 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 194.53 | 47.66 | 0.33 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 153.96 | 49.08 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 128.42 | 79.86 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 92.56 | 77.79 | 16.17 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 82.33 | 85.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 158.47 | 65.06 | 34.83 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 82.33 | 39.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 258.61 | 85.18 | 16.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.49 | 59.07 | 17.42 | 100.03 | 75.59 | 6.67 | 0.00 | 0.00 |
February | 74.42 | 47.83 | 26.59 | 90.51 | 63.01 | 11.67 | 0.00 | 0.00 |
March | 105.23 | 67.30 | 37.93 | 133.29 | 69.36 | 0.00 | 0.00 | 0.00 |
April | 162.63 | 125.59 | 37.04 | 216.04 | 72.27 | 0.00 | 0.00 | 0.00 |
May | 179.00 | 140.54 | 38.46 | 238.05 | 69.50 | 0.00 | 0.00 | 0.00 |
June | 188.49 | 154.08 | 34.41 | 258.61 | 51.52 | 0.00 | 0.00 | 0.00 |
July | 152.74 | 110.58 | 42.16 | 209.53 | 39.35 | 0.00 | 0.00 | 0.00 |
August | 140.78 | 104.06 | 36.72 | 194.53 | 47.66 | 0.33 | 0.00 | 0.00 |
September | 113.23 | 71.04 | 42.20 | 153.96 | 49.08 | 0.00 | 0.00 | 0.00 |
October | 100.88 | 75.82 | 25.05 | 128.42 | 79.86 | 0.00 | 0.00 | 0.00 |
November | 74.96 | 54.26 | 20.70 | 92.56 | 77.79 | 16.17 | 0.00 | 0.00 |
December | 66.18 | 48.41 | 17.76 | 82.33 | 85.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.79 | 88.40 | 31.38 | 158.47 | 65.06 | 34.83 | 0.00 | 0.00 |
Minimum of Months | 66.18 | 47.83 | 17.42 | 82.33 | 39.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.49 | 154.08 | 42.20 | 258.61 | 85.18 | 16.17 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181288E+09 | 0.113118E+09 | 68170376.46 | 0.349689E+09 | 0.350018E+09 |
February | 0.131450E+09 | 63444780.91 | 68004929.09 | 0.193783E+09 | 0.312801E+09 |
March | 0.193410E+09 | 92305875.75 | 0.101104E+09 | 0.335557E+09 | 0.310829E+09 |
April | 0.285130E+09 | 0.161887E+09 | 0.123244E+09 | 0.641626E+09 | 0.209236E+09 |
May | 0.296334E+09 | 0.165376E+09 | 0.130958E+09 | 0.715795E+09 | 0.168237E+09 |
June | 0.304582E+09 | 0.178747E+09 | 0.125836E+09 | 0.848734E+09 | 83455654.87 |
July | 0.229489E+09 | 0.106899E+09 | 0.122591E+09 | 0.649337E+09 | 74381081.83 |
August | 0.219032E+09 | 0.109722E+09 | 0.109309E+09 | 0.623008E+09 | 91527407.09 |
September | 0.184837E+09 | 77559438.27 | 0.107277E+09 | 0.493186E+09 | 0.115457E+09 |
October | 0.195142E+09 | 0.111366E+09 | 83775617.40 | 0.411411E+09 | 0.274694E+09 |
November | 0.173620E+09 | 0.104548E+09 | 69072347.18 | 0.313523E+09 | 0.345917E+09 |
December | 0.145862E+09 | 83341599.49 | 62520315.44 | 0.243567E+09 | 0.429360E+09 |
Annual Sum or Average | 0.254018E+10 | 0.136831E+10 | 0.117186E+10 | 0.581922E+10 | 0.276591E+10 |
Minimum of Months | 0.131450E+09 | 63444780.91 | 62520315.44 | 0.193783E+09 | 74381081.83 |
Maximum of Months | 0.304582E+09 | 0.178747E+09 | 0.130958E+09 | 0.848734E+09 | 0.429360E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181288E+09 | 0.113118E+09 | 68170376.46 | 0.349689E+09 | 0.350018E+09 |
February | 0.131450E+09 | 63444780.91 | 68004929.09 | 0.193783E+09 | 0.312801E+09 |
March | 0.193410E+09 | 92305875.75 | 0.101104E+09 | 0.335557E+09 | 0.310829E+09 |
April | 0.285130E+09 | 0.161887E+09 | 0.123244E+09 | 0.641626E+09 | 0.209236E+09 |
May | 0.296334E+09 | 0.165376E+09 | 0.130958E+09 | 0.715795E+09 | 0.168237E+09 |
June | 0.304582E+09 | 0.178747E+09 | 0.125836E+09 | 0.848734E+09 | 83455654.87 |
July | 0.229489E+09 | 0.106899E+09 | 0.122591E+09 | 0.649337E+09 | 74381081.83 |
August | 0.219032E+09 | 0.109722E+09 | 0.109309E+09 | 0.623008E+09 | 91527407.09 |
September | 0.184837E+09 | 77559438.27 | 0.107277E+09 | 0.493186E+09 | 0.115457E+09 |
October | 0.195142E+09 | 0.111366E+09 | 83775617.40 | 0.411411E+09 | 0.274694E+09 |
November | 0.173620E+09 | 0.104548E+09 | 69072347.18 | 0.313523E+09 | 0.345917E+09 |
December | 0.145862E+09 | 83341599.49 | 62520315.44 | 0.243567E+09 | 0.429360E+09 |
Annual Sum or Average | 0.254018E+10 | 0.136831E+10 | 0.117186E+10 | 0.581922E+10 | 0.276591E+10 |
Minimum of Months | 0.131450E+09 | 63444780.91 | 62520315.44 | 0.193783E+09 | 74381081.83 |
Maximum of Months | 0.304582E+09 | 0.178747E+09 | 0.130958E+09 | 0.848734E+09 | 0.429360E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 31069929.10 | 0.00 | 31069929.10 | 26266899.06 | 0.207907E+09 |
February | 31977233.33 | 0.00 | 31977233.33 | 14303166.33 | 0.189574E+09 |
March | 47067343.67 | 8893.91 | 47058449.76 | 49708503.70 | 0.188594E+09 |
April | 55936042.68 | 1015900.50 | 54920142.18 | 0.110358E+09 | 0.119885E+09 |
May | 69067257.25 | 7202951.39 | 61864305.86 | 0.162645E+09 | 89234705.00 |
June | 77509988.04 | 15784066.75 | 61725921.29 | 0.257155E+09 | 44143851.88 |
July | 67603695.08 | 8027795.28 | 59575899.80 | 0.220161E+09 | 40756631.02 |
August | 54277189.57 | 1873753.87 | 52403435.70 | 0.182807E+09 | 51464231.18 |
September | 49053075.55 | 45373.51 | 49007702.04 | 0.143343E+09 | 66799055.11 |
October | 39183319.34 | 0.00 | 39183319.34 | 63313330.97 | 0.163540E+09 |
November | 31593765.24 | 0.00 | 31593765.24 | 22246058.97 | 0.207488E+09 |
December | 29022163.57 | 0.00 | 29022163.57 | 13718688.04 | 0.258392E+09 |
Annual Sum or Average | 0.583361E+09 | 33958735.22 | 0.549402E+09 | 0.126603E+10 | 0.162778E+10 |
Minimum of Months | 29022163.57 | 0.00 | 29022163.57 | 13718688.04 | 40756631.02 |
Maximum of Months | 77509988.04 | 15784066.75 | 61864305.86 | 0.257155E+09 | 0.258392E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 31069169.72 | 0.00 | 31069169.72 | 26266375.23 | 0.207905E+09 |
February | 31976337.70 | 0.00 | 31976337.70 | 14302308.40 | 0.189573E+09 |
March | 47066024.86 | 8893.50 | 47057131.37 | 49706836.69 | 0.188593E+09 |
April | 55934735.75 | 1015852.89 | 54918882.86 | 0.110357E+09 | 0.119883E+09 |
May | 69065487.18 | 7202613.78 | 61862873.40 | 0.162643E+09 | 89232993.79 |
June | 77507850.35 | 15783326.93 | 61724523.42 | 0.257151E+09 | 44142584.09 |
July | 67601785.51 | 8027419.01 | 59574366.50 | 0.220158E+09 | 40755760.12 |
August | 54275807.02 | 1873666.04 | 52402140.97 | 0.182806E+09 | 51463112.78 |
September | 49051698.69 | 45371.38 | 49006327.31 | 0.143341E+09 | 66797889.24 |
October | 39182357.41 | 0.00 | 39182357.41 | 63312528.12 | 0.163538E+09 |
November | 31592945.98 | 0.00 | 31592945.98 | 22245447.33 | 0.207486E+09 |
December | 29021414.92 | 0.00 | 29021414.92 | 13718287.61 | 0.258390E+09 |
Annual Sum or Average | 0.583346E+09 | 33957143.53 | 0.549388E+09 | 0.126601E+10 | 0.162776E+10 |
Minimum of Months | 29021414.92 | 0.00 | 29021414.92 | 13718287.61 | 40755760.12 |
Maximum of Months | 77507850.35 | 15783326.93 | 61862873.40 | 0.257151E+09 | 0.258390E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.267911E+09 | 0.202460E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.218952E+09 | 0.152436E+09 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.357011E+09 | 0.185781E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.559974E+09 | 0.187327E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.637590E+09 | 0.186161E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.670329E+09 | 0.133535E+09 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.561213E+09 | 0.105397E+09 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.521019E+09 | 0.127659E+09 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.399052E+09 | 0.127211E+09 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.343953E+09 | 0.213891E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.239904E+09 | 0.201625E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.220509E+09 | 0.228149E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.499742E+10 | 0.205163E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.218952E+09 | 0.105397E+09 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.670329E+09 | 0.228149E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.267911E+09 | 0.202460E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.218952E+09 | 0.152436E+09 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.357011E+09 | 0.185781E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.559974E+09 | 0.187327E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.637590E+09 | 0.186161E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.670329E+09 | 0.133535E+09 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.561213E+09 | 0.105397E+09 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.521019E+09 | 0.127659E+09 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.399052E+09 | 0.127211E+09 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.343953E+09 | 0.213891E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.239904E+09 | 0.201625E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.220509E+09 | 0.228149E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.499742E+10 | 0.205163E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.218952E+09 | 0.105397E+09 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.670329E+09 | 0.228149E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.267911E+09 | 0.202460E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.218952E+09 | 0.152436E+09 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.357011E+09 | 0.185781E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.559974E+09 | 0.187327E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.637590E+09 | 0.186161E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.670329E+09 | 0.133535E+09 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.561213E+09 | 0.105397E+09 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.521019E+09 | 0.127659E+09 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.399052E+09 | 0.127211E+09 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.343953E+09 | 0.213891E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.239904E+09 | 0.201625E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.220509E+09 | 0.228149E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.499742E+10 | 0.205163E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.218952E+09 | 0.105397E+09 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.670329E+09 | 0.228149E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.267911E+09 | 0.202460E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.218952E+09 | 0.152436E+09 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.357011E+09 | 0.185781E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.559974E+09 | 0.187327E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.637590E+09 | 0.186161E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.670329E+09 | 0.133535E+09 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.561213E+09 | 0.105397E+09 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.521019E+09 | 0.127659E+09 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.399052E+09 | 0.127211E+09 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.343953E+09 | 0.213891E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.239904E+09 | 0.201625E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.220509E+09 | 0.228149E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.499742E+10 | 0.205163E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.218952E+09 | 0.105397E+09 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.670329E+09 | 0.228149E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.267911E+09 | 0.202460E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.218952E+09 | 0.152436E+09 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.357011E+09 | 0.185781E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.559974E+09 | 0.187327E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.637590E+09 | 0.186161E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.670329E+09 | 0.133535E+09 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.561213E+09 | 0.105397E+09 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.521019E+09 | 0.127659E+09 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.399052E+09 | 0.127211E+09 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.343953E+09 | 0.213891E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.239904E+09 | 0.201625E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.220509E+09 | 0.228149E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.499742E+10 | 0.205163E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.218952E+09 | 0.105397E+09 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.670329E+09 | 0.228149E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.267911E+09 | 0.202460E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.218952E+09 | 0.152436E+09 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.357011E+09 | 0.185781E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.559974E+09 | 0.187327E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.637590E+09 | 0.186161E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.670329E+09 | 0.133535E+09 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.561213E+09 | 0.105397E+09 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.521019E+09 | 0.127659E+09 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.399052E+09 | 0.127211E+09 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.343953E+09 | 0.213891E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.239904E+09 | 0.201625E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.220509E+09 | 0.228149E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.499742E+10 | 0.205163E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.218952E+09 | 0.105397E+09 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.670329E+09 | 0.228149E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.267911E+09 | 0.202460E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.218952E+09 | 0.152436E+09 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.357011E+09 | 0.185781E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.559974E+09 | 0.187327E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.637590E+09 | 0.186161E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.670329E+09 | 0.133535E+09 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.561213E+09 | 0.105397E+09 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.521019E+09 | 0.127659E+09 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.399052E+09 | 0.127211E+09 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.343953E+09 | 0.213891E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.239904E+09 | 0.201625E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.220509E+09 | 0.228149E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.499742E+10 | 0.205163E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.218952E+09 | 0.105397E+09 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.670329E+09 | 0.228149E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.267911E+09 | 0.202460E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.218952E+09 | 0.152436E+09 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.357011E+09 | 0.185781E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.559974E+09 | 0.187327E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.637590E+09 | 0.186161E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.670329E+09 | 0.133535E+09 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.561213E+09 | 0.105397E+09 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.521019E+09 | 0.127659E+09 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.399052E+09 | 0.127211E+09 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.343953E+09 | 0.213891E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.239904E+09 | 0.201625E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.220509E+09 | 0.228149E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.499742E+10 | 0.205163E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.218952E+09 | 0.105397E+09 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.670329E+09 | 0.228149E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.267911E+09 | 0.202460E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.218952E+09 | 0.152436E+09 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.357011E+09 | 0.185781E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.559974E+09 | 0.187327E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.637590E+09 | 0.186161E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.670329E+09 | 0.133535E+09 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.561213E+09 | 0.105397E+09 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.521019E+09 | 0.127659E+09 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.399052E+09 | 0.127211E+09 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.343953E+09 | 0.213891E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.239904E+09 | 0.201625E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.220509E+09 | 0.228149E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.499742E+10 | 0.205163E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.218952E+09 | 0.105397E+09 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.670329E+09 | 0.228149E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204864E+09 | 0.158202E+09 | 46662624.08 | 0.267911E+09 | 0.202460E+09 |
February | 0.180037E+09 | 0.115705E+09 | 64332094.26 | 0.218952E+09 | 0.152436E+09 |
March | 0.281844E+09 | 0.180261E+09 | 0.101583E+09 | 0.357011E+09 | 0.185781E+09 |
April | 0.421548E+09 | 0.325530E+09 | 96018908.41 | 0.559974E+09 | 0.187327E+09 |
May | 0.479432E+09 | 0.376424E+09 | 0.103008E+09 | 0.637590E+09 | 0.186161E+09 |
June | 0.488561E+09 | 0.399377E+09 | 89184342.93 | 0.670329E+09 | 0.133535E+09 |
July | 0.409094E+09 | 0.296184E+09 | 0.112911E+09 | 0.561213E+09 | 0.105397E+09 |
August | 0.377064E+09 | 0.278724E+09 | 98340501.86 | 0.521019E+09 | 0.127659E+09 |
September | 0.293498E+09 | 0.184123E+09 | 0.109375E+09 | 0.399052E+09 | 0.127211E+09 |
October | 0.270189E+09 | 0.203084E+09 | 67105044.65 | 0.343953E+09 | 0.213891E+09 |
November | 0.194299E+09 | 0.140648E+09 | 53650865.11 | 0.239904E+09 | 0.201625E+09 |
December | 0.177245E+09 | 0.129672E+09 | 47573167.20 | 0.220509E+09 | 0.228149E+09 |
Annual Sum or Average | 0.377768E+10 | 0.278793E+10 | 0.989744E+09 | 0.499742E+10 | 0.205163E+10 |
Minimum of Months | 0.177245E+09 | 0.115705E+09 | 46662624.08 | 0.218952E+09 | 0.105397E+09 |
Maximum of Months | 0.488561E+09 | 0.399377E+09 | 0.112911E+09 | 0.670329E+09 | 0.228149E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 277.66 | 413.54 | 158.57 | 84.47 | 74.10 | 0.00 | 0.00 |
February | 166.94 | 410.23 | 135.11 | 52.45 | 82.66 | 0.00 | 0.00 |
March | 282.43 | 367.67 | 179.57 | 68.93 | 110.63 | 0.00 | 0.00 |
April | 579.64 | 253.36 | 263.17 | 125.70 | 137.47 | 0.00 | 0.00 |
May | 652.95 | 189.26 | 272.85 | 128.87 | 143.98 | 0.00 | 0.00 |
June | 849.73 | 94.87 | 294.82 | 150.10 | 144.72 | 0.00 | 0.00 |
July | 647.34 | 84.05 | 221.84 | 85.82 | 136.03 | 0.00 | 0.00 |
August | 600.87 | 105.93 | 204.08 | 83.33 | 120.75 | 0.00 | 0.00 |
September | 491.09 | 140.57 | 180.47 | 59.88 | 120.59 | 0.00 | 0.00 |
October | 351.80 | 324.55 | 174.97 | 83.16 | 91.81 | 0.00 | 0.00 |
November | 254.08 | 422.01 | 158.34 | 80.67 | 77.67 | 0.00 | 0.00 |
December | 186.35 | 507.78 | 130.59 | 62.23 | 68.36 | 0.00 | 0.00 |
Annual Sum or Average | 446.28 | 275.58 | 198.09 | 88.93 | 109.16 | 0.00 | 0.00 |
Minimum of Months | 166.94 | 84.05 | 130.59 | 52.45 | 68.36 | 0.00 | 0.00 |
Maximum of Months | 849.73 | 507.78 | 294.82 | 150.10 | 144.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3883.76 | 2743.76 | 764.88 | 590.66 | 174.22 | 0.00 | 0.00 |
February | 3364.73 | 2224.79 | 744.20 | 478.28 | 265.92 | 0.00 | 0.00 |
March | 5342.67 | 2341.92 | 1052.29 | 673.02 | 379.27 | 0.00 | 0.00 |
April | 11551.62 | 2784.34 | 1626.34 | 1255.90 | 370.44 | 0.00 | 0.00 |
May | 11445.74 | 3351.72 | 1789.99 | 1405.41 | 384.59 | 0.00 | 0.00 |
June | 11538.80 | 4261.84 | 1884.88 | 1540.81 | 344.08 | 0.00 | 0.00 |
July | 10516.03 | 3403.84 | 1527.38 | 1105.82 | 421.56 | 0.00 | 0.00 |
August | 9052.86 | 3787.38 | 1407.80 | 1040.64 | 367.16 | 0.00 | 0.00 |
September | 7252.98 | 3220.42 | 1132.32 | 710.35 | 421.97 | 0.00 | 0.00 |
October | 5965.14 | 3191.16 | 1008.77 | 758.23 | 250.54 | 0.00 | 0.00 |
November | 3699.70 | 2644.40 | 749.61 | 542.63 | 206.99 | 0.00 | 0.00 |
December | 3000.31 | 3091.13 | 661.76 | 484.14 | 177.62 | 0.00 | 0.00 |
Annual Sum or Average | 7235.36 | 3092.77 | 1197.89 | 884.05 | 313.85 | 0.00 | 0.00 |
Minimum of Months | 3000.31 | 2224.79 | 661.76 | 478.28 | 174.22 | 0.00 | 0.00 |
Maximum of Months | 11551.62 | 4261.84 | 1884.88 | 1540.81 | 421.97 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.743689E+09 | 0.110763E+10 | 0.424716E+09 | 0.226236E+09 | 0.198480E+09 | 0.00 | 0.00 |
February | 0.403854E+09 | 0.992431E+09 | 0.326853E+09 | 0.126890E+09 | 0.199963E+09 | 0.00 | 0.00 |
March | 0.756450E+09 | 0.984764E+09 | 0.480954E+09 | 0.184630E+09 | 0.296324E+09 | 0.00 | 0.00 |
April | 0.150244E+10 | 0.656711E+09 | 0.682132E+09 | 0.325805E+09 | 0.356327E+09 | 0.00 | 0.00 |
May | 0.174885E+10 | 0.506919E+09 | 0.730801E+09 | 0.345158E+09 | 0.385643E+09 | 0.00 | 0.00 |
June | 0.220249E+10 | 0.245912E+09 | 0.764183E+09 | 0.389061E+09 | 0.375122E+09 | 0.00 | 0.00 |
July | 0.173384E+10 | 0.225118E+09 | 0.594184E+09 | 0.229853E+09 | 0.364331E+09 | 0.00 | 0.00 |
August | 0.160938E+10 | 0.283735E+09 | 0.546616E+09 | 0.223192E+09 | 0.323424E+09 | 0.00 | 0.00 |
September | 0.127291E+10 | 0.364364E+09 | 0.467779E+09 | 0.155210E+09 | 0.312569E+09 | 0.00 | 0.00 |
October | 0.942257E+09 | 0.869273E+09 | 0.468649E+09 | 0.222732E+09 | 0.245917E+09 | 0.00 | 0.00 |
November | 0.658583E+09 | 0.109385E+10 | 0.410427E+09 | 0.209095E+09 | 0.201331E+09 | 0.00 | 0.00 |
December | 0.499115E+09 | 0.136005E+10 | 0.349767E+09 | 0.166683E+09 | 0.183084E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.140739E+11 | 0.869075E+10 | 0.624706E+10 | 0.280454E+10 | 0.344252E+10 | 0.00 | 0.00 |
Minimum of Months | 0.403854E+09 | 0.225118E+09 | 0.326853E+09 | 0.126890E+09 | 0.183084E+09 | 0.00 | 0.00 |
Maximum of Months | 0.220249E+10 | 0.136005E+10 | 0.764183E+09 | 0.389061E+09 | 0.385643E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104023E+11 | 0.734889E+10 | 0.204864E+10 | 0.158202E+10 | 0.466626E+09 | 0.00 | 0.00 |
February | 0.813996E+10 | 0.538222E+10 | 0.180037E+10 | 0.115705E+10 | 0.643321E+09 | 0.00 | 0.00 |
March | 0.143098E+11 | 0.627259E+10 | 0.281844E+10 | 0.180261E+10 | 0.101583E+10 | 0.00 | 0.00 |
April | 0.299418E+11 | 0.721701E+10 | 0.421548E+10 | 0.325530E+10 | 0.960189E+09 | 0.00 | 0.00 |
May | 0.306563E+11 | 0.897724E+10 | 0.479432E+10 | 0.376424E+10 | 0.103008E+10 | 0.00 | 0.00 |
June | 0.299086E+11 | 0.110467E+11 | 0.488561E+10 | 0.399377E+10 | 0.891843E+09 | 0.00 | 0.00 |
July | 0.281661E+11 | 0.911684E+10 | 0.409094E+10 | 0.296184E+10 | 0.112911E+10 | 0.00 | 0.00 |
August | 0.242472E+11 | 0.101441E+11 | 0.377064E+10 | 0.278724E+10 | 0.983405E+09 | 0.00 | 0.00 |
September | 0.187997E+11 | 0.834732E+10 | 0.293498E+10 | 0.184123E+10 | 0.109375E+10 | 0.00 | 0.00 |
October | 0.159770E+11 | 0.854721E+10 | 0.270189E+10 | 0.203084E+10 | 0.671050E+09 | 0.00 | 0.00 |
November | 0.958962E+10 | 0.685429E+10 | 0.194299E+10 | 0.140648E+10 | 0.536509E+09 | 0.00 | 0.00 |
December | 0.803602E+10 | 0.827929E+10 | 0.177245E+10 | 0.129672E+10 | 0.475732E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.228174E+12 | 0.975337E+11 | 0.377768E+11 | 0.278793E+11 | 0.989744E+10 | 0.00 | 0.00 |
Minimum of Months | 0.803602E+10 | 0.538222E+10 | 0.177245E+10 | 0.115705E+10 | 0.466626E+09 | 0.00 | 0.00 |
Maximum of Months | 0.306563E+11 | 0.110467E+11 | 0.488561E+10 | 0.399377E+10 | 0.112911E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.47 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.35 | 6.24 | 2.64 | 2.53 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.67 | 1.96 | 3.53 | 3.02 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.14 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.07 | -4.9 | 3.62 | 8.60 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.28 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.99 | 9.86 | 3.72 | 19.28 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.15 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.59 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.99 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.80 | 1.49 | 3.02 | 1.83 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.57 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.15 | 11.45 | 3.72 | 19.28 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.73 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.42 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.79 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.57 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.57 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.74 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.40 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.27 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.81 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 19.01 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.20 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.90 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.73 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.81 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.2 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.59 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.4 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.42 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.97 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.24 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.53 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.48 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.5 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.6 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.6 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.73 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.18 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.71 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.57 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.18 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.11 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.19 | 16-AUG-10:00 | 35.00 | 17.00 | 2.10 | 24.33 | 140.50 | 837.00 |
September | 22.23 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.53 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.06 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.06 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.18 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.73 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.70 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 14.00 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.75 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.18 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.11 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.17 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.18 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.859491E+09 | -720550937.1 | 0.00 | 0.00 | 744.00 | 0.00 | -138940103.4 | 58.99 | 0.00 | 0.00 |
February | 0.781611E+09 | -655392536.5 | 0.00 | 0.00 | 672.00 | 0.00 | -126218516.3 | 58.99 | 0.00 | 0.00 |
March | 0.865085E+09 | -728584657.0 | 0.00 | 0.00 | 744.00 | 0.00 | -136500113.7 | 58.99 | 0.00 | 0.00 |
April | 0.745911E+09 | -623092925.2 | 0.00 | 0.00 | 720.00 | 0.00 | -122817598.2 | 58.99 | 0.00 | 0.00 |
May | 0.712610E+09 | -587757343.8 | 0.00 | 0.00 | 744.00 | 0.00 | -124852512.6 | 58.99 | 0.00 | 0.00 |
June | 0.654416E+09 | -535589745.4 | 0.00 | 0.00 | 720.00 | 0.00 | -118826526.3 | 58.99 | 0.00 | 0.00 |
July | 0.616233E+09 | -494115929.2 | 0.00 | 0.00 | 744.00 | 0.00 | -122117107.5 | 58.99 | 0.00 | 0.00 |
August | 0.661895E+09 | -538558361.7 | 0.00 | 0.00 | 744.00 | 0.00 | -123336195.0 | 58.99 | 0.00 | 0.00 |
September | 0.656531E+09 | -537058864.2 | 0.00 | 0.00 | 720.00 | 0.00 | -119471887.0 | 58.99 | 0.00 | 0.00 |
October | 0.721088E+09 | -592656660.2 | 0.00 | 0.00 | 744.00 | 0.00 | -128431066.3 | 58.99 | 0.00 | 0.00 |
November | 0.755433E+09 | -624740926.9 | 0.00 | 0.00 | 720.00 | 0.00 | -130692307.2 | 58.99 | 0.00 | 0.00 |
December | 0.837622E+09 | -697053252.0 | 0.00 | 0.00 | 744.00 | 0.00 | -140568539.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.886792E+10 | -0.733515E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.153277E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.616233E+09 | -728584657.0 | 0.00 | 0.00 | 672.00 | 0.00 | -140568539.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.865085E+09 | -494115929.2 | 0.00 | 0.00 | 744.00 | 0.00 | -118826526.3 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 309.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 344.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 380.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 403.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 418.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 399.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 361.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 350.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 348.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 288.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 290.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4135.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 418.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.385563E+09 | 34987.64 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.327099E+09 | 34987.64 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.328024E+09 | 34987.64 | 27-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17355267.93 | 5150.77 | 25-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.106011E+09 | 26944.13 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.600151E+09 | 34987.64 | 06-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.600151E+09 | 34987.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.535373E+09 | 59210.64 | 01-JAN-06:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.535373E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.535373E+09 | 59210.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.139866E+09 | 14587.21 | 01-JAN-07:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139866E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.139866E+09 | 14587.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.358113E+10 | 0.356629E+10 | 9228.36 | 31-JAN-16:30 | 9228.36 | 0.00 |
February | 0.00 | 0.00 | 0.207920E+10 | 0.197323E+10 | 6549.15 | 22-FEB-16:00 | 6518.62 | 0.00 |
March | 0.00 | 0.00 | 0.410599E+10 | 0.406871E+10 | 9962.03 | 18-MAR-16:00 | 9962.03 | 0.00 |
April | 0.00 | 0.00 | 0.902803E+10 | 0.902803E+10 | 27795.23 | 15-APR-05:01 | 27795.23 | 0.00 |
May | 0.00 | 0.00 | 0.116149E+11 | 0.116149E+11 | 27932.37 | 11-MAY-05:01 | 27932.37 | 0.00 |
June | 0.00 | 0.00 | 0.153515E+11 | 0.153288E+11 | 28247.80 | 19-JUN-05:01 | 28247.80 | 0.00 |
July | 0.00 | 0.00 | 0.157284E+11 | 0.144443E+11 | 34663.86 | 14-JUL-05:01 | 21468.76 | 0.00 |
August | 0.00 | 0.00 | 0.162064E+11 | 0.148020E+11 | 33407.70 | 10-AUG-05:01 | 22697.01 | 0.00 |
September | 0.00 | 0.00 | 0.137953E+11 | 0.125788E+11 | 33105.48 | 02-SEP-05:01 | 23488.03 | 0.00 |
October | 0.00 | 0.00 | 0.825691E+10 | 0.800890E+10 | 31967.34 | 03-OCT-05:01 | 25362.67 | 0.00 |
November | 0.00 | 0.00 | 0.458653E+10 | 0.439106E+10 | 24566.77 | 01-NOV-05:02 | 24566.77 | 0.00 |
December | 0.00 | 0.00 | 0.237178E+10 | 0.236980E+10 | 7788.75 | 22-DEC-16:30 | 7788.75 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.106706E+12 | 0.102175E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.207920E+10 | 0.197323E+10 | 6549.15 | 6518.62 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.162064E+11 | 0.153288E+11 | 34663.86 | 28247.80 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.588222E+10 | 0.586437E+10 | 23567.32 | 31-JAN-16:00 | 23567.32 | 0.00 |
February | 0.00 | 0.00 | 0.182047E+10 | 0.174887E+10 | 14555.01 | 16-FEB-13:30 | 12797.89 | 0.00 |
March | 0.00 | 0.00 | 0.734874E+10 | 0.732234E+10 | 44602.23 | 18-MAR-17:10 | 44602.23 | 0.00 |
April | 0.00 | 0.00 | 0.319955E+11 | 0.319955E+11 | 102223.63 | 25-APR-18:23 | 102223.63 | 0.00 |
May | 0.00 | 0.00 | 0.459258E+11 | 0.459258E+11 | 103421.25 | 29-MAY-11:32 | 103421.25 | 0.00 |
June | 0.00 | 0.00 | 0.681935E+11 | 0.681121E+11 | 106713.86 | 17-JUN-19:02 | 105465.59 | 0.00 |
July | 0.00 | 0.00 | 0.694497E+11 | 0.647801E+11 | 119758.54 | 17-JUL-19:42 | 102900.36 | 0.00 |
August | 0.00 | 0.00 | 0.663035E+11 | 0.616743E+11 | 115308.90 | 20-AUG-09:43 | 98757.99 | 0.00 |
September | 0.00 | 0.00 | 0.535908E+11 | 0.494145E+11 | 122030.98 | 04-SEP-11:13 | 97599.17 | 0.00 |
October | 0.00 | 0.00 | 0.246748E+11 | 0.239202E+11 | 105825.86 | 09-OCT-13:43 | 105825.86 | 0.00 |
November | 0.00 | 0.00 | 0.741042E+10 | 0.726428E+10 | 34439.95 | 01-NOV-15:00 | 33294.33 | 0.00 |
December | 0.00 | 0.00 | 0.182998E+10 | 0.182911E+10 | 17299.37 | 22-DEC-15:30 | 17299.37 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.384425E+12 | 0.369851E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.182047E+10 | 0.174887E+10 | 14555.01 | 12797.89 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.694497E+11 | 0.681121E+11 | 122030.98 | 105825.86 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 2994574.54 | 0.00 | 207.96 | 01-JAN-04:20 | 0.08 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 2994574.54 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2994574.54 | 0.00 | 207.96 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.170673E+10 | 0.38 | 1718.26 | 02-JAN-13:50 | 0.99 |
February | 0.156931E+10 | 0.38 | 1718.26 | 21-FEB-12:20 | 0.98 |
March | 0.184125E+10 | 0.40 | 1718.26 | 04-MAR-14:30 | 0.98 |
April | 0.171865E+10 | 0.40 | 1718.26 | 06-APR-09:50 | 0.99 |
May | 0.180708E+10 | 0.44 | 1718.26 | 05-MAY-09:30 | 0.99 |
June | 0.187153E+10 | 0.54 | 1718.26 | 07-JUN-06:57 | 0.99 |
July | 0.180505E+10 | 0.50 | 1718.26 | 06-JUL-07:10 | 0.99 |
August | 0.191784E+10 | 0.49 | 1718.26 | 05-AUG-08:30 | 0.98 |
September | 0.175667E+10 | 0.44 | 1718.26 | 01-SEP-13:40 | 0.98 |
October | 0.171903E+10 | 0.39 | 1718.26 | 03-OCT-07:20 | 0.98 |
November | 0.163495E+10 | 0.37 | 1718.26 | 06-NOV-16:10 | 0.99 |
December | 0.170987E+10 | 0.38 | 1718.26 | 30-DEC-12:10 | 0.99 |
Annual Sum or Average | 0.210580E+11 | 0.43 | |||
Minimum of Months | 0.156931E+10 | 0.37 | 1718.26 | 0.98 | |
Maximum of Months | 0.191784E+10 | 0.54 | 1718.26 | 0.99 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.878124E+10 | 0.61 | 8830.35 | 23-JAN-13:40 | 1.55 |
February | 0.804269E+10 | 0.58 | 8830.35 | 01-FEB-11:50 | 1.55 |
March | 0.944804E+10 | 0.63 | 8830.35 | 01-MAR-13:00 | 1.55 |
April | 0.922754E+10 | 0.81 | 8830.35 | 01-APR-08:40 | 1.56 |
May | 0.100228E+11 | 0.95 | 8830.35 | 01-MAY-08:50 | 1.56 |
June | 0.109381E+11 | 1.23 | 8830.35 | 01-JUN-06:20 | 1.55 |
July | 0.107182E+11 | 1.25 | 8830.35 | 01-JUL-06:10 | 1.56 |
August | 0.109533E+11 | 1.20 | 8830.35 | 01-AUG-06:10 | 1.53 |
September | 0.984985E+10 | 1.11 | 8830.35 | 01-SEP-06:10 | 1.53 |
October | 0.907620E+10 | 0.73 | 8830.35 | 02-OCT-06:10 | 1.54 |
November | 0.839315E+10 | 0.57 | 8830.35 | 01-NOV-09:40 | 1.54 |
December | 0.874205E+10 | 0.58 | 8830.35 | 01-DEC-11:10 | 1.55 |
Annual Sum or Average | 0.114193E+12 | 0.85 | |||
Minimum of Months | 0.804269E+10 | 0.57 | 8830.35 | 1.53 | |
Maximum of Months | 0.109533E+11 | 1.25 | 8830.35 | 1.56 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.267929E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.213387E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.296286E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.431829E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.527048E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.681773E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.660703E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.684780E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.581501E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.405459E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.287478E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.235269E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.527344E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.213387E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.684780E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.105430E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.858289E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.116596E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.194482E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.252215E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.350245E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.339476E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.331109E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.271847E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.168620E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.106081E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.928722E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.241480E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.858289E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.350245E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.170673E+10 | 0.358113E+10 | 0.385563E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156931E+10 | 0.207920E+10 | 0.327099E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.184125E+10 | 0.410599E+10 | 0.328024E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171865E+10 | 0.902803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.180708E+10 | 0.116149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.187153E+10 | 0.153515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.180505E+10 | 0.157284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.191784E+10 | 0.162064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.175667E+10 | 0.137953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.171903E+10 | 0.825691E+10 | 17355267.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163495E+10 | 0.458653E+10 | 0.106011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170987E+10 | 0.237178E+10 | 0.600151E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210580E+11 | 0.106706E+12 | 0.176420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.156931E+10 | 0.207920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.191784E+10 | 0.162064E+11 | 0.600151E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.878124E+10 | 0.588222E+10 | 0.535373E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.804269E+10 | 0.182047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.944804E+10 | 0.734874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.922754E+10 | 0.319955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.100228E+11 | 0.459258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.109381E+11 | 0.681935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.107182E+11 | 0.694497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109533E+11 | 0.663035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.984985E+10 | 0.535908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.907620E+10 | 0.246748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.839315E+10 | 0.741042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.874205E+10 | 0.182998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114193E+12 | 0.384425E+12 | 0.535373E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.804269E+10 | 0.182047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109533E+11 | 0.694497E+11 | 0.535373E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.170673E+10 | 0.00 | 0.00 | 0.00 | 0.972559E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156931E+10 | 0.00 | 0.00 | 0.00 | 0.564558E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.184125E+10 | 0.00 | 0.00 | 0.00 | 0.112162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171865E+10 | 0.00 | 0.00 | 0.00 | 0.259965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.180708E+10 | 0.00 | 0.00 | 0.00 | 0.346340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.187153E+10 | 0.00 | 0.00 | 0.00 | 0.494619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.180505E+10 | 0.00 | 0.00 | 0.00 | 0.480198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.191784E+10 | 0.00 | 0.00 | 0.00 | 0.492996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.175667E+10 | 0.00 | 0.00 | 0.00 | 0.405834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.171903E+10 | 0.00 | 0.00 | 0.00 | 0.233557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163495E+10 | 0.00 | 0.00 | 0.00 | 0.123983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170987E+10 | 0.00 | 0.00 | 0.00 | 0.642814E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210580E+11 | 0.00 | 0.00 | 0.00 | 0.316765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.156931E+10 | 0.00 | 0.00 | 0.00 | 0.564558E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.191784E+10 | 0.00 | 0.00 | 0.00 | 0.494619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.878124E+10 | 0.00 | 0.00 | 0.00 | 0.176179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.804269E+10 | 0.00 | 0.00 | 0.00 | 0.540205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.944804E+10 | 0.00 | 0.00 | 0.00 | 0.221154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.922754E+10 | 0.00 | 0.00 | 0.00 | 0.102206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.100228E+11 | 0.00 | 0.00 | 0.00 | 0.151987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.109381E+11 | 0.00 | 0.00 | 0.00 | 0.240864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.107182E+11 | 0.00 | 0.00 | 0.00 | 0.232294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109533E+11 | 0.00 | 0.00 | 0.00 | 0.221576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.984985E+10 | 0.00 | 0.00 | 0.00 | 0.173348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.907620E+10 | 0.00 | 0.00 | 0.00 | 0.778582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.839315E+10 | 0.00 | 0.00 | 0.00 | 0.221493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.874205E+10 | 0.00 | 0.00 | 0.00 | 0.545169E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114193E+12 | 0.00 | 0.00 | 0.00 | 0.127287E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.804269E+10 | 0.00 | 0.00 | 0.00 | 0.540205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109533E+11 | 0.00 | 0.00 | 0.00 | 0.240864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.171972E+09 | 524482.82 | 0.00 | 4346088.08 | 0.00 | 0.119458E+09 | 0.526496E+09 | 0.00 | 0.14 |
February | 0.316382E+09 | 0.00 | 0.00 | 2456936.67 | 0.00 | 99228020.24 | 0.693596E+09 | 0.00 | 0.14 |
March | 0.191740E+09 | 7583213.35 | 0.00 | 4632312.67 | 0.00 | 0.102792E+09 | 0.622051E+09 | 0.00 | 0.15 |
April | 42977124.86 | 0.189095E+09 | 0.00 | 7730752.44 | 0.00 | 0.00 | 0.200777E+09 | 0.00 | 0.14 |
May | 1555733.25 | 0.382960E+09 | 0.00 | 7516805.60 | 0.00 | 0.00 | 85133251.71 | 0.00 | 0.15 |
June | 0.00 | 0.940480E+09 | 0.00 | 3914454.16 | 0.00 | 0.00 | 7929333.16 | 0.00 | 0.16 |
July | 0.00 | 0.122540E+10 | 0.00 | 1850727.44 | 0.00 | 0.00 | 5553432.47 | 0.00 | 0.15 |
August | 0.00 | 0.129648E+10 | 0.00 | 2949819.65 | 0.00 | 0.00 | 4448584.92 | 0.00 | 0.15 |
September | 0.00 | 0.893843E+09 | 0.00 | 3129821.63 | 0.00 | 0.00 | 17149934.92 | 0.00 | 0.15 |
October | 75964890.54 | 0.230998E+09 | 0.00 | 6430735.65 | 0.00 | 15950315.30 | 0.343721E+09 | 0.00 | 0.14 |
November | 0.145380E+09 | 10462093.80 | 0.00 | 5114969.01 | 2621.45 | 47471888.48 | 0.540590E+09 | 0.00 | 0.14 |
December | 0.388354E+09 | 8425.16 | 0.00 | 2966665.81 | 0.00 | 0.166798E+09 | 0.594283E+09 | 0.00 | 0.14 |
Annual Sum or Average | 0.133433E+10 | 0.517784E+10 | 0.00 | 53040088.80 | 2621.45 | 0.551697E+09 | 0.364173E+10 | 0.00 | 0.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1850727.44 | 0.00 | 0.00 | 4448584.92 | 0.00 | 0.14 |
Maximum of Months | 0.388354E+09 | 0.129648E+10 | 0.00 | 7730752.44 | 2621.45 | 0.166798E+09 | 0.693596E+09 | 0.00 | 0.16 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.208485E+10 | 0.00 | 0.00 | 4380565.00 | 0.00 | 0.00 | 0.173248E+10 | 0.00 | 0.19 |
February | 0.379653E+10 | 0.00 | 0.00 | 1206981.89 | 0.00 | 0.00 | 0.116494E+10 | 0.00 | 0.19 |
March | 0.240512E+10 | 21785.69 | 0.00 | 6766845.88 | 0.00 | 0.00 | 0.239180E+10 | 0.00 | 0.23 |
April | 0.272001E+09 | 0.301255E+09 | 0.00 | 25699369.57 | 0.00 | 0.00 | 0.230296E+10 | 0.00 | 0.26 |
May | 64463670.36 | 0.780850E+09 | 0.00 | 20280967.67 | 0.00 | 0.00 | 0.127795E+10 | 0.00 | 0.24 |
June | 970935.73 | 0.257828E+10 | 0.00 | 3498034.24 | 0.00 | 0.00 | 60028290.80 | 0.00 | 0.20 |
July | 0.00 | 0.348551E+10 | 0.00 | 1105011.28 | 0.00 | 0.00 | 43418664.78 | 0.00 | 0.18 |
August | 654419.69 | 0.367857E+10 | 0.00 | 1322435.95 | 0.00 | 0.00 | 0.118924E+09 | 0.00 | 0.21 |
September | 24412928.22 | 0.231815E+10 | 0.00 | 5328645.44 | 0.00 | 0.00 | 0.612154E+09 | 0.00 | 0.23 |
October | 0.640965E+09 | 0.470836E+09 | 0.00 | 14773514.91 | 0.00 | 0.00 | 0.317984E+10 | 0.00 | 0.28 |
November | 0.155634E+10 | 605425.66 | 0.00 | 8230355.43 | 0.00 | 0.00 | 0.391017E+10 | 0.00 | 0.27 |
December | 0.386358E+10 | 0.00 | 0.00 | 1272143.13 | 55175.66 | 0.00 | 0.112328E+10 | 0.00 | 0.20 |
Annual Sum or Average | 0.147099E+11 | 0.136141E+11 | 0.00 | 93864870.40 | 55175.66 | 0.00 | 0.179179E+11 | 0.00 | 0.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1105011.28 | 0.00 | 0.00 | 43418664.78 | 0.00 | 0.18 |
Maximum of Months | 0.386358E+10 | 0.367857E+10 | 0.00 | 25699369.57 | 55175.66 | 0.00 | 0.391017E+10 | 0.00 | 0.28 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.614890E+12 | 0.313778E+11 | 0.00 | 0.645906E+10 | 0.126968E+11 |
February | 0.617421E+12 | 0.344569E+11 | 0.00 | 0.775800E+10 | 0.516789E+10 |
March | 0.859527E+12 | 0.478078E+11 | 0.00 | 0.748801E+10 | 0.149504E+11 |
April | 0.112876E+13 | 0.567349E+11 | 0.00 | 0.347667E+10 | 0.538438E+11 |
May | 0.118349E+13 | 0.752414E+11 | 0.00 | 0.111516E+10 | 0.762027E+11 |
June | 0.120702E+13 | 0.933052E+11 | 0.00 | -0.326045E+10 | 0.112578E+12 |
July | 0.107304E+13 | 0.987350E+11 | 0.00 | -0.498272E+10 | 0.113210E+12 |
August | 0.973897E+12 | 0.907337E+11 | 0.00 | -0.503592E+10 | 0.109598E+12 |
September | 0.810957E+12 | 0.701780E+11 | 0.00 | -0.252131E+10 | 0.887792E+11 |
October | 0.759507E+12 | 0.535020E+11 | 0.00 | 0.490010E+10 | 0.430624E+11 |
November | 0.617887E+12 | 0.400818E+11 | 0.00 | 0.807155E+10 | 0.155062E+11 |
December | 0.509371E+12 | 0.320326E+11 | 0.00 | 0.845864E+10 | 0.567394E+10 |
Annual Sum or Average | 0.103558E+14 | 0.724187E+12 | 0.00 | 0.319268E+11 | 0.651268E+12 |
Minimum of Months | 0.509371E+12 | 0.313778E+11 | 0.00 | -0.503592E+10 | 0.516789E+10 |
Maximum of Months | 0.120702E+13 | 0.987350E+11 | 0.00 | 0.845864E+10 | 0.113210E+12 |