Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2023-10-16 10:41:43
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1321.98 | 273.41 | 273.41 |
Net Site Energy | 1321.98 | 273.41 | 273.41 |
Total Source Energy | 3984.64 | 824.10 | 824.10 |
Net Source Energy | 3984.64 | 824.10 | 824.10 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 97.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 173.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 134.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 130.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1224.97 | 97.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 97.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 173.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 134.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 15.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 114.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 24.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 97.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 173.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 134.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 130.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 24.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 67.83 | 20.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 253.35 | 20.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 67.83 | 20.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 253.35 | 20.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1224.970 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1224.970 | 100.00 |
Total On-Site and Utility Electric Sources | 1224.970 | 100.00 |
Total Electricity End Uses | 1224.970 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 3.17 |
Time Setpoint Not Met During Occupied Cooling | 20.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2914.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.61 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7186 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 15.0695 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 9.6875 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 11.2890 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 11.2890 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.7186 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 15.0695 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 9.6875 | 46.45 | 2.5587 | |
Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 11.2890 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 03-AUG-14:00 | 21-DEC-07:10 | - | - | - | - | - | - | - | - | - | - | 31-MAR-11:09 |
Heating | 0.00 | 22443.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 26961.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 11090.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1684.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 96042.03 | 22443.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 22443.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 26961.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 8785.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1684.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 105.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 550.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1974.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 424.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 411.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 76.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3879.48 | 105.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 21.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 113.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 85.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 802.35 | 21.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 21.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 113.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 85.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 802.35 | 21.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.31 |
ZONE2 FINE STORAGE DIRECT AIR | 3.82 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 1.44 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 1.44 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 59007.53 |
PSZ-OFFICE HEATING COIL | 32510.37 |
PSZ-FINE STORAGE HEATING COIL | 117527.39 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 59007.53 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.00 | 1.00 | 1.31 |
PSZ-FINE STORAGE | 3.82 | 3.82 | 3.82 | 3.82 | 3.82 | 3.82 | 1.00 | 1.00 | 3.82 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.31 | 0.120335 |
PSZ-FINE STORAGE_OA_CONTROLLER | 3.82 | 0.353926 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.31 | 1495.87 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.82 | 7289.23 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.31 | 1.31 | 1.31 | 1.31 | 27032.72 | 32510.37 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 3.82 | 3.82 | 3.82 | 3.82 | 94820.55 | 117527.39 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.31 | 0.656019 | 1.31 | 27032.72 | 13849.03 | 27032.72 | 0.764390 | 0.764390 |
PSZ-FINE STORAGE COOLING COIL | 3.82 | 1.91 | 3.82 | 94820.55 | 47410.23 | 94820.55 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.719 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.792 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 15.069 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15.069 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 9.688 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 12.246 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2539.013 | 10.719 | 199.158 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2539.013 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 20997.932 | 15.069 | 699.931 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20997.932 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 31046.942 | 9.688 | 449.956 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 31046.942 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 1.090 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.7823 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 1.301 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 1.301 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9172 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.179 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6691 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6691 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53297977E-11 | 0.35762577E-16 | 0.10093676E-15 | 0.0000000 |
5 | 1 | -5.2159127 | 0.59796011E-04 | -0.14694131E-04 | 0.68696372E-11 |
6 | 0 | 6.3062040 | 1.0902315 | 1.0903060 | |
7 | 4 | 0.72249793E-12 | -0.16720573E-15 | 0.22015083E-14 | 0.12409536E-15 |
8 | 3 | -0.36459118E-03 | 0.53555631E-06 | -0.52695411E-04 | 0.13865996E-12 |
9 | 2 | 1.6915239 | 0.11971291E-01 | 1.1039557 | -0.69896550E-04 |
10 | 1 | -7.1930661 | 0.31446443 | -16.864389 | 0.32415671 |
11 | 0 | 6.0306730 | 0.20232993 | 16.289252 | |
12 | 4 | 0.62407051E-12 | 0.80447548E-15 | -0.19405657E-14 | 0.12807081E-15 |
13 | 3 | -0.32959465E-03 | 0.84747600E-06 | -0.47309261E-04 | 0.11981323E-12 |
14 | 2 | 1.6058071 | 0.19756964E-01 | 1.0389034 | -0.63182077E-04 |
15 | 1 | -7.3135607 | 0.53269638 | -16.443412 | 0.30760774 |
16 | 0 | 6.6091660 | 0.34862863 | 16.305639 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.19405657E-14 | 0.80447548E-15 | 0.62407051E-12 | 0.12807081E-15 |
85 | 3 | -0.47309261E-04 | 0.84747600E-06 | -0.32959465E-03 | 0.11981323E-12 |
86 | 2 | 1.0389034 | 0.19756964E-01 | 1.6058071 | -0.63182077E-04 |
87 | 1 | -16.443412 | 0.53269638 | -7.3135607 | 0.30760774 |
88 | 0 | 16.305639 | 0.34862863 | 6.6091660 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.2213_SHGC_SOUTH_0.25 | 34 | 1 | VerySmooth | 6.927 | 5.835 | 1.184 | 0.251 | ||
2 | NONRESWINDOW_U_1.2213_SHGC_NORTH_0.25 | 35 | 1 | VerySmooth | 6.927 | 5.835 | 1.184 | 0.251 | ||
3 | NONRESWINDOW_U_1.2213_SHGC_EAST_0.25 | 36 | 1 | VerySmooth | 6.927 | 5.835 | 1.184 | 0.251 | ||
4 | NONRESWINDOW_U_1.2213_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 6.927 | 5.835 | 1.184 | 0.251 | ||
5 | SKYLIGHT_U_1.02_SHGC_0.36 | 38 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.361 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41396 | 0.41396 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.40015 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41396 | 0.41396 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.40015 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41396 | 0.41396 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.40015 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41396 | 0.41396 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.40015 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.19502 | 0.25365 | 0.25365 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.849 | 0.366 | 0.255 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 0.153 | 6.473E-004 | 9.992E-004 | 0.546 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.780 | 5.598E-004 | 3.565E-004 | 0.951 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 3.433 | 1.071E-003 | 6.996E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 13276.54239 | 15931.85086 | 1.09337 | 1.31204 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 33.00467 | 1.65347E-002 | 236.87965 | 12.74874 | 0.12033 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 8054.90550 | 9665.88660 | 0.22613 | 0.27136 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 4.60000 | 5.25715E-003 | 236.87965 | 12.74874 | 0.12033 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 49559.73778 | 59471.68534 | 3.18202 | 3.81842 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 33.82100 | 1.65362E-002 | 1393.40969 | 30.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 19752.07848 | 23702.49418 | 0.46743 | 0.56092 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 4.60000 | 5.25715E-003 | 1393.40969 | 30.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 33.90000 | 1.65364E-002 | 3204.84228 | 69.00000 | 0.81403 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 49172.94457 | 59007.53349 | 1.20248 | 1.44297 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4.60000 | 5.25715E-003 | 3204.84228 | 69.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 20205.77 | 1.31204 | 1.31204 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 8617.62 | 0.27136 | 0.27136 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 70903.11 | 3.81842 | 3.81842 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 21264.49 | 0.56092 | 0.56092 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.31204 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.81842 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.44297 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 1.44297 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 59007.53198 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 59007.53349 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.31204 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.31204 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.31204 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.31204 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.31204 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.31204 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.81842 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.81842 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.81842 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.81842 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.81842 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.81842 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.31204 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.81842 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.31204 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12033 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.31204 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1495.86841 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.31204 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.31204 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.31204 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.31204 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.31204 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.65602 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.31204 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 27032.72000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 13849.02713 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 27032.72000 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76439 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76439 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27032.72000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32510.37364 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 32510.37364 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.81842 |
47 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.81842 |
49 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 7289.23469 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.81842 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.81842 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.81842 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.81842 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.81842 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.90921 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.81842 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 94820.55000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 47410.23094 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 94820.55000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 94820.55000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 117527.38666 |
64 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
66 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 117527.38666 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 26013.8 | 11.05 | 10.41 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 91852.5 | 10.53 | 9.92 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 5.7997243455E-002 | 4.7887367314E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.1243093267 | 0.1916719841 | Pass | Pass | 6.4793629906E-002 | 0.3559360891 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 7.8235752042E-002 | 6.8486914471E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 10634.62 | 708.97 | 0.00 | -36.0 | 873.56 | 12181.21 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 66.00 | 12 | |||
Feb | 66.00 | 22 | |||
Mar | 126.00 | 32 | |||
Apr | 206.00 | 19 | |||
May | 144.00 | 46 | |||
Jun | 99.00 | 30 | |||
Jul | 192.00 | 52 | |||
Aug | 240.00 | 34 | |||
Sep | 310.00 | 44 | |||
Oct | 34.00 | 10 | |||
Nov | 63.00 | 12 | |||
Dec | 35.00 | 24 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.089 | 1.301 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.089 | 1.301 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.089 | 1.301 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.948 | 1.090 | 3204.84 | 3170.23 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.992 | 1.301 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.992 | 1.301 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_1.2213_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 6.927 | 0.251 | 0.252 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_1.2213_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 6.927 | 0.251 | 0.252 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_1.2213_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 6.927 | 0.251 | 0.252 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_1.2213_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 6.927 | 0.251 | 0.252 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.27 | 6.180 | 0.449 | 0.450 | |||||||||||||||||
North Total or Average | 6.51 | 6.927 | 0.251 | 0.252 | |||||||||||||||||
Non-North Total or Average | 45.76 | 6.074 | 0.478 | 0.478 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.7186 | 236.88 | 2539.01 | LightsWired | LTG_SCH_OFFICE | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.86 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 15.0695 | 1393.41 | 20997.93 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 239.15 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 9.6875 | 3204.84 | 31046.94 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 353.60 |
Interior Lighting Total | 11.2890 | 4835.13 | 54583.89 | 623.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 8532.22 | AstronomicalClock | - | 83.73 | 83.73 | 134.10 | |
Exterior Lighting Total | 8532.22 | 134.10 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 27032.72 | 20663.54 | 6369.18 | 0.76 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 94820.55 | 66476.79 | 28343.76 | 0.70 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 26013.8 | 11.05 | 10.41 | ||||
PSZ-FINE STORAGE COOLING COIL | 91852.5 | 10.53 | 9.92 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 59007.53 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 32510.37 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 117527.39 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 1.44 | 134.07 | 92.91 | 1.00 | 3.81 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.31 | 1495.87 | 1140.11 | 1.00 | 1.30 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 1110.54 | 3.82 | 7289.23 | 1908.96 | 1.00 | 1.14 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 13276.54 | 15931.85 | 67.26 | 1.093 | 1.312 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 23.90 | 23.90 | 0.00860 | 33.00 | 0.01653 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 49559.74 | 59471.69 | 42.68 | 3.182 | 3.818 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 26.70 | 26.69 | 0.00911 | 33.82 | 0.01654 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 0.00 | 34.99 | 0.01661 | 33.90 | 0.01654 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8054.91 | 9665.89 | 40.81 | 0.226 | 0.271 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00781 | 4.60 | 0.00526 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 19752.08 | 23702.49 | 17.01 | 0.467 | 0.561 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00684 | 4.60 | 0.00526 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 49172.94 | 59007.53 | 18.41 | 1.202 | 1.443 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00645 | 4.60 | 0.00526 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.31 | 1.31 | 0.27 | 0.27 | 1.3120 | 1.3120 | 1.3120 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.82 | 3.82 | 0.56 | 0.56 | 3.8184 | 3.8184 | 3.8184 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 59007.532 | 59007.532 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 59007.53 | 59007.53 | 1.442971 | 10.00 | 8.69 | 0.00645020 | 43.33 | 22.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 10.00 | 0.00645020 | 84.6154 | 59007.53 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 27032.720 | 20663.541 | 1.312040 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 27032.72 | 22138.80 | 1.312040 | 25.67 | 17.65 | 0.00932532 | 12.00 | 11.25 | 0.00800000 | 33.11 | 0.01653489 | 24.92 | 9.1716 | 23.90 | 0.00859702 | 46.5192 | 13271.69 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 32510.374 | 32510.374 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 32510.37 | 32510.37 | 1.312039 | 19.51 | 13.87 | 0.00757137 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 9.1716 | 21.10 | 0.00780506 | 50.1242 | 8054.91 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 94820.550 | 66476.791 | 3.818420 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 94820.55 | 76001.49 | 3.818420 | 28.91 | 19.10 | 0.00980166 | 12.00 | 11.25 | 0.00800000 | 33.90 | 0.01653638 | 25.13 | 9.2689 | 26.69 | 0.00911345 | 41.7202 | 49546.21 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 117527.387 | 117527.387 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 117527.39 | 117527.39 | 3.818424 | 14.54 | 10.97 | 0.00669009 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 9.2689 | 15.56 | 0.00683647 | 62.2602 | 19752.08 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 59007.532 | 59007.532 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 1.442971 | 1.73613439 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 59007.53 | 59007.53 | 1.0000 | 1.73613439 | 1.442971 | 10.00 | 8.69 | 0.00645020 | 26299.0 | 43.33 | 22.14 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 59007.53 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 10.00 | 0.00645020 | 10.00 | 0.00645020 | 84.6154 | 59007.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27032.720 | 20663.541 | 1.312040 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.1753 | 1004.8586 | 1.2032 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.312039 | 1.57860165 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | Sensible | 27032.72 | 22138.80 | 1.0000 | 1.57860310 | 1.312040 | 25.67 | 17.65 | 0.00932532 | 49560.9 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27032.72 | 33.11 | 0.01653489 | 24.92 | 0.12033486 | 9.1716 | 23.90 | 0.00859702 | 23.90 | 0.00859702 | 46.5192 | 13271.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32510.374 | 32510.374 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.312039 | 1.57860165 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 32510.37 | 32510.37 | 1.0000 | 1.57860165 | 1.312039 | 19.51 | 13.87 | 0.00757137 | 38809.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32510.37 | 4.60 | 0.00525715 | 4.60 | 0.12033486 | 9.1716 | 21.01 | 0.00780506 | 21.10 | 0.00780506 | 50.1242 | 8054.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 94820.550 | 66476.791 | 3.818420 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.0608 | 1004.8586 | 1.2032 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.818424 | 4.59420102 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 94820.55 | 76001.49 | 1.0000 | 4.59419654 | 3.818420 | 28.91 | 19.10 | 0.00980166 | 54093.7 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 94820.55 | 33.90 | 0.01653638 | 25.13 | 0.35392606 | 9.2689 | 26.69 | 0.00911345 | 26.69 | 0.00911345 | 41.7202 | 49546.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 117527.387 | 117527.387 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.818424 | 4.59420102 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 117527.39 | 117527.39 | 1.0000 | 4.59420102 | 3.818424 | 14.54 | 10.97 | 0.00669009 | 31524.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 117527.39 | 4.60 | 0.00525715 | 4.60 | 0.35392606 | 9.2689 | 15.56 | 0.00683647 | 15.56 | 0.00683647 | 62.2602 | 19752.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2696.33 | 1046.00 | 381.83 |
ZONE2 FINE STORAGE | 3238.00 | 2899.00 | 2587.50 |
ZONE3 BULK STORAGE | 3144.67 | 3326.83 | 2889.50 |
Facility | 3426.83 | 3400.83 | 2914.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 3.17 | 471.17 | 3.17 | 18.83 |
ZONE2 FINE STORAGE | 0.00 | 195.50 | 0.00 | 1.33 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 3.17 | 586.17 | 3.17 | 20.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.405 | 0.467 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.408 | 0.336 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.149 | 0.000 | 1.350 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1203 | 0.120 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.3539 | 0.354 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 3204.84 | 0.814 | ||
Total Facility | 83.55 | 111.75 | 39241.41 | 4835.13 | 0.4743 | 1.288 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1605058.52 | 0.00 | 1605058.52 | 2631637.25 | 4236695.77 | 3794880.16 | 5393.94 | 3366.06 | 0.00 | 1657.06 |
ZONE2 FINE STORAGE | 4528909.70 | 0.00 | 4528909.70 | 8978522.92 | 13507432.62 | 11161412.23 | 5415.45 | 3344.55 | 0.00 | 1264.44 |
ZONE3 BULK STORAGE | 0.00 | 0.26E+09 | 0.26E+09 | 36596238.64 | 0.29E+09 | 25671248.14 | 6520.29 | 37.72 | 2201.99 | 4958.33 |
Total Facility | 6133968.22 | 0.26E+09 | 0.26E+09 | 48206398.81 | 0.31E+09 | 40627540.53 | 7380.99 | 3396.50 | 2201.99 | 5045.64 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1112 | 0.0000 | 0.1112 | 0.1285 | 0.2397 | 0.1203 | 301.29 | 3334.71 | 0.00 |
ZONE2 FINE STORAGE | 0.3247 | 0.0000 | 0.3247 | 0.2675 | 0.5923 | 0.3539 | 303.00 | 3333.00 | 0.00 |
ZONE3 BULK STORAGE | 0.0000 | 12.4833 | 12.4833 | 1.4046 | 13.8879 | 0.8140 | 2251.54 | 15.67 | 1368.79 |
Total Facility | 0.4359 | 12.4833 | 12.9191 | 1.8007 | 14.7198 | 1.2883 | 2260.04 | 3334.71 | 1368.79 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2323499.70 | 0.00 | 2323499.70 | 3794880.16 | 5354.80 | 1.83 | 3403.36 | 1639.69 |
PSZ-FINE STORAGE | 6556097.60 | 0.00 | 6556097.60 | 11161412.23 | 5401.75 | 0.59 | 3357.65 | 1259.68 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1609 | 0.0000 | 0.1609 | 0.1203 | 299.96 | 0.02 | 3336.03 |
PSZ-FINE STORAGE | 0.4701 | 0.0000 | 0.4701 | 0.3539 | 303.00 | 0.00 | 3333.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 5114.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 4623.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1684 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.5082 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 383 |
Defaulted Fields | 319 |
Fields with Defaults | 1020 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1224.97 | 6718.26 | 01-JAN-07:30 | 96042.03 | 03-AUG-15:00 |
Electricity:Building | 778.82 | 6235.26 | 01-JAN-00:10 | 58611.10 | 28-MAR-12:10 |
Electricity:Zone:ZONE1 OFFICE | 62.81 | 1030.77 | 01-JAN-00:10 | 3867.54 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 762.90 | 6235.26 | 01-JAN-00:10 | 56305.80 | 02-JAN-09:10 |
InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 476.86 | 3104.69 | 01-JAN-00:10 | 36895.31 | 28-MAR-12:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 130.01 | 0.00 | 01-JAN-00:10 | 11090.40 | 10-MAY-11:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 15.92 | 0.00 | 01-JAN-00:10 | 2305.29 | 07-MAY-14:30 |
Ventilation (simple):Fans:Electricity | 15.92 | 0.00 | 01-JAN-00:10 | 2305.29 | 07-MAY-14:30 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 15.92 | 0.00 | 01-JAN-00:10 | 2305.29 | 07-MAY-14:30 |
ElectricityPurchased:Facility | 1224.97 | 6718.26 | 01-JAN-07:30 | 96042.03 | 03-AUG-15:00 |
ElectricityPurchased:Plant | 1224.97 | 6718.26 | 01-JAN-07:30 | 96042.03 | 03-AUG-15:00 |
Cogeneration:ElectricityPurchased | 1224.97 | 6718.26 | 01-JAN-07:30 | 96042.03 | 03-AUG-15:00 |
General:Cogeneration:ElectricityPurchased | 1224.97 | 6718.26 | 01-JAN-07:30 | 96042.03 | 03-AUG-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1224.97 | 6718.26 | 01-JAN-07:30 | 96042.03 | 03-AUG-15:00 |
ElectricityNet:Plant | 1224.97 | 6718.26 | 01-JAN-07:30 | 96042.03 | 03-AUG-15:00 |
Cogeneration:ElectricityNet | 1224.97 | 6718.26 | 01-JAN-07:30 | 96042.03 | 03-AUG-15:00 |
General:Cogeneration:ElectricityNet | 1224.97 | 6718.26 | 01-JAN-07:30 | 96042.03 | 03-AUG-15:00 |
Electricity:HVAC | 287.95 | 0.00 | 01-JAN-00:10 | 37772.97 | 03-AUG-16:00 |
General:Fans:Electricity | 114.09 | 0.00 | 01-JAN-00:10 | 8785.10 | 07-APR-14:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 173.86 | 0.00 | 01-JAN-00:10 | 28987.87 | 03-AUG-16:00 |
General:Cooling:Electricity | 173.86 | 0.00 | 01-JAN-00:10 | 28987.87 | 03-AUG-16:00 |
ExteriorLights:Electricity | 134.10 | 0.00 | 01-JAN-07:30 | 8532.22 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 134.10 | 0.00 | 01-JAN-07:30 | 8532.22 | 01-JAN-00:10 |
Electricity:Plant | 24.10 | 483.00 | 07-FEB-06:10 | 1780.55 | 23-JAN-12:40 |
WaterSystems:Electricity | 24.10 | 483.00 | 07-FEB-06:10 | 1780.55 | 23-JAN-12:40 |
Water Heater:WaterSystems:Electricity | 24.10 | 483.00 | 07-FEB-06:10 | 1780.55 | 23-JAN-12:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 97.01 | 3000.00 | 27-FEB-00:10 | 22443.78 | 21-DEC-07:10 |
NaturalGas:HVAC | 97.01 | 3000.00 | 27-FEB-00:10 | 22443.78 | 21-DEC-07:10 |
Heating:NaturalGas | 97.01 | 3000.00 | 27-FEB-00:10 | 22443.78 | 21-DEC-07:10 |
General:Heating:NaturalGas | 97.01 | 3000.00 | 27-FEB-00:10 | 22443.78 | 21-DEC-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 31-MAR-11:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 31-MAR-11:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 31-MAR-11:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 31-MAR-11:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 31-MAR-11:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 31-MAR-11:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 31-MAR-11:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 31-MAR-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 952.36 | 0.00 | 01-JAN-00:10 | 149456.10 | 03-AUG-15:50 |
EnergyTransfer:Building | 346.41 | 0.00 | 01-JAN-00:10 | 57888.59 | 03-AUG-15:40 |
EnergyTransfer:Zone:ZONE1 OFFICE | 96.18 | 0.00 | 01-JAN-00:10 | 14500.64 | 10-SEP-23:10 |
Heating:EnergyTransfer | 7.22 | 0.00 | 01-JAN-00:10 | 13524.85 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 1.67 | 0.00 | 01-JAN-00:10 | 13524.85 | 06-FEB-06:10 |
General:Heating:EnergyTransfer | 7.22 | 0.00 | 01-JAN-00:10 | 13524.85 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 1.67 | 0.00 | 01-JAN-00:10 | 13524.85 | 06-FEB-06:10 |
Cooling:EnergyTransfer | 339.19 | 0.00 | 01-JAN-00:10 | 57888.59 | 03-AUG-15:40 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 94.52 | 0.00 | 01-JAN-00:10 | 14500.64 | 10-SEP-23:10 |
General:Cooling:EnergyTransfer | 339.19 | 0.00 | 01-JAN-00:10 | 57888.59 | 03-AUG-15:40 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 94.52 | 0.00 | 01-JAN-00:10 | 14500.64 | 10-SEP-23:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 250.23 | 0.00 | 01-JAN-00:10 | 45402.86 | 03-AUG-15:30 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 5.55 | 0.00 | 01-JAN-00:10 | 8959.85 | 05-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 5.55 | 0.00 | 01-JAN-00:10 | 8959.85 | 05-FEB-08:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 244.68 | 0.00 | 01-JAN-00:10 | 45402.86 | 03-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 244.68 | 0.00 | 01-JAN-00:10 | 45402.86 | 03-AUG-15:30 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 605.95 | 0.00 | 01-JAN-00:10 | 91686.60 | 03-AUG-15:50 |
HeatingCoils:EnergyTransfer | 1.63 | 0.00 | 01-JAN-00:10 | 14484.16 | 06-FEB-06:10 |
CoolingCoils:EnergyTransfer | 604.32 | 0.00 | 01-JAN-00:10 | 91686.60 | 03-AUG-15:50 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 1.669 | -94.514 | 0.000 | 0.000 | 9.206 | 30.864 | 31.946 | 12.681 | 0.000 | 5.517 | 22.190 | 0.000 | -8.380 | 0.000 | -11.178 | -0.003 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 5.547 | -244.665 | 0.000 | 0.000 | 17.829 | 239.148 | 0.000 | 0.000 | 0.000 | 6.649 | 24.934 | 0.000 | 0.000 | 0.000 | -49.444 | -0.001 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 34.056 | 353.598 | 107.344 | 163.834 | 0.000 | 1.211 | 94.942 | 0.000 | -65.423 | 0.000 | -689.562 | -0.009 |
Total Facility | 0.000 | 0.000 | 7.216 | -339.179 | 0.000 | 0.000 | 61.091 | 623.610 | 139.290 | 176.515 | 0.000 | 13.378 | 142.066 | 0.000 | -73.803 | 0.000 | -750.184 | -0.013 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 16-APR-23:02 | 0.00 | 0.00 | 0.00 | -24393.83 | 0.00 | 0.00 | 0.00 | 457.02 | 573.75 | 0.00 | 0.00 | 0.00 | 24448.35 | 0.00 | -919.70 | 0.00 | -165.60 | 0.00 |
ZONE2 FINE STORAGE | 01-OCT-15:23 | 0.00 | 0.00 | 0.00 | -80853.70 | 0.00 | 0.00 | 0.00 | 2099.79 | 0.00 | 0.00 | 0.00 | 200.02 | 78553.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-JUN-17:05 | 0.00 | 0.00 | 0.00 | -96402.67 | 0.00 | 0.00 | 0.00 | 5661.51 | 2623.78 | 25857.62 | 0.00 | 1318.73 | 108911.53 | 0.00 | 0.00 | 0.00 | -47970.50 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 07-FEB-06:01 | 0.00 | 0.00 | 31206.18 | 0.00 | 0.00 | 0.00 | 134.98 | 583.97 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -817.90 | 0.00 | -1421.12 | -30259.86 |
ZONE2 FINE STORAGE | 05-FEB-08:65 | 0.00 | 0.00 | 17919.76 | 0.00 | 0.00 | 0.00 | 0.00 | 2099.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -13337.10 | -6682.45 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-FEB-06:01 | 0.00 | 0.00 | 31206.18 | 0.00 | 0.00 | 0.00 | 1276.05 | 5788.46 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7230.36 | 0.00 | -20602.20 | -13061.92 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3120 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1203 | 1.3120 | 0.0917 | 1.0000 | Not calculated | 0.1203 | 0.0917 | ||
PSZ-FINE STORAGE | 3.8184 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.3539 | 3.8184 | 0.0927 | 1.0000 | Not calculated | 0.3539 | 0.0927 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3120 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1203 | 1.3120 | 1.0000 | 1.0000 | Not calculated | 0.1203 | 0.0917 | ||
PSZ-FINE STORAGE | 3.8184 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.3539 | 3.8184 | 1.0000 | 1.0000 | Not calculated | 0.3539 | 0.0927 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3120 | 1.3120 | 1.3120 | No | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.8184 | 3.8184 | 3.8184 | No | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3120 | 1.3120 | 1.3120 | 1.3120 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 3.8184 | 3.8184 | 3.8184 | 3.8184 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3120 | 1.3120 | 1.3120 | No | 0.1203 | 0.4434 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.8184 | 3.8184 | 3.8184 | No | 0.3539 | 0.6310 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3120 | 1.3120 | 1.3120 | 1.3120 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 3.8184 | 3.8184 | 3.8184 | 3.8184 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 3.17 |
Number of hours cooling loads not met | 20.17 |
Number of hours not met | 23.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 97.01 | 22443.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 173.86 | 28987.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 623.61 | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 134.10 | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 15.92 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 114.09 | 8785.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 24.10 | 1780.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 1224.97 |
Natural Gas | 0.00 | 97.01 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 1321.98 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 128.97 |
Space Heating | 0.00 |
Space Cooling | 35.96 |
Fans (All) | 26.89 |
Service Water Heating | 4.98 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 253.35 |
Subtotal | 253.35 |
Natural Gas [MJ/m2] | |
Space Heating | 20.06 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 20.06 |
Subtotal | 20.06 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 47.17 |
Space Heating | 7.34 |
Space Cooling | 13.15 |
Fans (All) | 9.83 |
Service Water Heating | 1.82 |
Receptacle Equipment | 10.54 |
Miscellaneous | 10.14 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 3430. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 7972.17 | 660.83 | 127.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 3721.50 | 5038.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3480.17 | 2233.83 | 2967.50 | 78.50 | 0.00 |
Min | 3480.17 | 660.83 | 0.00 | 0.00 | 0.00 |
Max | 7972.17 | 5038.50 | 2967.50 | 78.50 | 0.00 |
Average | 5057.94 | 2644.39 | 1031.50 | 26.17 | 0.00 |
Sum | 15173.83 | 7933.17 | 3094.50 | 78.50 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 25324.50 | 57394.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 61052.67 | 47733.67 | 78954.67 | 3452.00 | 0.00 |
Min | 25324.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 61052.67 | 57394.50 | 78954.67 | 3452.00 | 0.00 |
Average | 39801.39 | 35042.72 | 26318.22 | 1150.67 | 0.00 |
Sum | 119404.17 | 105128.17 | 78954.67 | 3452.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 7259.17 | 1488.33 | 12.50 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 2911.83 | 5848.17 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 2858.33 | 4294.33 | 1563.00 | 44.33 | 0.00 |
Min | 2858.33 | 1488.33 | 0.00 | 0.00 | 0.00 |
Max | 7259.17 | 5848.17 | 1563.00 | 44.33 | 0.00 |
Average | 4343.11 | 3876.94 | 525.17 | 14.78 | 0.00 |
Sum | 13029.33 | 11630.83 | 1575.50 | 44.33 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 30425.67 | 2601.33 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 22385.50 | 60333.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 53276.67 | 85283.17 | 50945.17 | 1688.00 | 0.00 |
Min | 22385.50 | 2601.33 | 0.00 | 0.00 | 0.00 |
Max | 53276.67 | 85283.17 | 50945.17 | 1688.00 | 0.00 |
Average | 35362.61 | 49406.00 | 16981.72 | 562.67 | 0.00 |
Sum | 106087.83 | 148218.00 | 50945.17 | 1688.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215510E+10 | 20133.51 | 02-JAN-00:02 | 17.17 | 16.96 | 0.606133E+09 | 773.44 | 11-JAN-11:09 | 18.17 | 13.39 |
February | 0.297060E+10 | 20939.37 | 27-FEB-00:01 | 17.77 | 17.47 | 0.568008E+09 | 769.02 | 09-FEB-16:49 | 17.77 | 17.47 |
March | 0.409410E+10 | 20864.45 | 06-MAR-00:02 | 19.87 | 18.29 | 0.669336E+09 | 777.74 | 06-MAR-08:09 | 20.08 | 18.36 |
April | 0.712307E+10 | 24394.64 | 16-APR-23:02 | 14.17 | 11.80 | 0.633297E+09 | 769.07 | 21-APR-15:20 | 30.37 | 20.10 |
May | 0.113864E+11 | 20476.89 | 30-MAY-05:03 | 25.50 | 24.21 | 0.660168E+09 | 769.08 | 04-MAY-15:39 | 25.50 | 24.21 |
June | 0.121388E+11 | 21915.28 | 11-JUN-23:01 | 25.60 | 21.42 | 0.660208E+09 | 769.08 | 09-JUN-15:00 | 25.60 | 21.42 |
July | 0.120331E+11 | 19804.97 | 10-JUL-05:43 | 25.40 | 23.24 | 0.634849E+09 | 769.10 | 07-JUL-15:00 | 25.40 | 23.24 |
August | 0.130112E+11 | 20152.68 | 30-AUG-21:03 | 29.17 | 22.55 | 0.685634E+09 | 769.09 | 21-AUG-15:00 | 29.17 | 22.55 |
September | 0.109613E+11 | 20098.72 | 22-SEP-19:43 | 27.80 | 21.00 | 0.634813E+09 | 768.97 | 11-SEP-07:30 | 27.80 | 21.00 |
October | 0.988226E+10 | 23735.30 | 01-OCT-23:01 | 20.00 | 15.68 | 0.634442E+09 | 769.09 | 11-OCT-15:30 | 30.50 | 21.95 |
November | 0.526041E+10 | 21805.27 | 05-NOV-23:01 | 21.50 | 18.65 | 0.605677E+09 | 769.03 | 21-NOV-15:30 | 21.65 | 15.14 |
December | 0.349924E+10 | 19345.54 | 11-DEC-00:01 | 21.17 | 19.25 | 0.615279E+09 | 769.04 | 01-DEC-16:40 | 21.17 | 19.25 |
Annual Sum or Average | 0.945156E+11 | 0.760784E+10 | ||||||||
Minimum of Months | 0.215510E+10 | 19345.54 | 14.17 | 11.80 | 0.568008E+09 | 768.97 | 17.77 | 13.39 | ||
Maximum of Months | 0.130112E+11 | 24394.64 | 29.17 | 24.21 | 0.685634E+09 | 777.74 | 30.50 | 24.21 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.183985E+10 | 49778.90 | 01-JAN-14:23 | 25.50 | 18.23 | 0.162162E+10 | 2246.81 | 11-JAN-16:10 | 19.83 | 14.57 |
February | 0.450879E+10 | 49449.81 | 26-FEB-14:43 | 26.18 | 20.05 | 0.156662E+10 | 2265.17 | 25-FEB-08:30 | 26.18 | 20.05 |
March | 0.699423E+10 | 60859.17 | 26-MAR-14:13 | 27.93 | 20.14 | 0.186884E+10 | 2246.90 | 23-MAR-14:39 | 27.93 | 20.14 |
April | 0.168523E+11 | 73876.32 | 23-APR-13:53 | 27.70 | 20.99 | 0.183985E+10 | 2246.95 | 18-APR-12:20 | 27.70 | 20.99 |
May | 0.323609E+11 | 75190.28 | 04-MAY-17:06 | 31.42 | 21.65 | 0.192892E+10 | 2247.12 | 04-MAY-15:30 | 31.42 | 21.65 |
June | 0.364317E+11 | 75879.28 | 12-JUN-17:05 | 32.02 | 21.34 | 0.192887E+10 | 2247.12 | 10-JUN-15:50 | 32.02 | 21.34 |
July | 0.373019E+11 | 71239.47 | 23-JUL-11:43 | 31.52 | 25.53 | 0.185471E+10 | 2247.14 | 07-JUL-15:20 | 31.52 | 25.53 |
August | 0.374308E+11 | 71676.04 | 06-AUG-16:33 | 25.33 | 22.97 | 0.200308E+10 | 2247.11 | 03-AUG-15:20 | 25.33 | 22.97 |
September | 0.300235E+11 | 72713.14 | 22-SEP-17:06 | 30.32 | 21.07 | 0.185472E+10 | 2246.81 | 15-SEP-07:10 | 30.32 | 21.07 |
October | 0.258661E+11 | 80856.00 | 01-OCT-15:23 | 27.85 | 18.41 | 0.184609E+10 | 2247.00 | 17-OCT-13:20 | 22.33 | 15.56 |
November | 0.970908E+10 | 58835.18 | 05-NOV-13:53 | 27.20 | 20.73 | 0.174362E+10 | 2246.90 | 14-NOV-15:20 | 18.63 | 12.92 |
December | 0.535891E+10 | 48714.97 | 10-DEC-15:03 | 27.83 | 20.05 | 0.167917E+10 | 2246.88 | 15-DEC-08:09 | 22.00 | 22.00 |
Annual Sum or Average | 0.244678E+12 | 0.217361E+11 | ||||||||
Minimum of Months | 0.183985E+10 | 48714.97 | 25.33 | 18.23 | 0.156662E+10 | 2246.81 | 18.63 | 12.92 | ||
Maximum of Months | 0.374308E+11 | 80856.00 | 32.02 | 25.53 | 0.200308E+10 | 2265.17 | 32.02 | 25.53 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 | 0.288871E+10 | 6039.96 | 02-JAN-14:20 | 26.33 | 18.48 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 | 0.308764E+10 | 6306.21 | 27-FEB-13:09 | 24.58 | 19.62 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 17.62 | 17.16 | 0.405923E+10 | 6371.39 | 30-MAR-13:20 | 28.83 | 22.63 |
April | 0.00 | 0.00 | 01-APR-00:05 | 20.72 | 19.79 | 0.487888E+10 | 8194.95 | 28-APR-15:09 | 33.12 | 23.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.11 | 0.586666E+10 | 8337.81 | 18-MAY-14:39 | 33.30 | 23.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 | 0.606393E+10 | 9022.41 | 14-JUN-14:20 | 34.43 | 24.69 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 | 0.584602E+10 | 9097.65 | 21-JUL-14:39 | 35.00 | 25.22 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 | 23.55 | 0.618558E+10 | 9097.65 | 03-AUG-15:39 | 35.33 | 24.82 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 | 24.22 | 0.537491E+10 | 8821.94 | 09-SEP-15:00 | 35.60 | 26.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 | 0.520678E+10 | 8462.37 | 05-OCT-15:09 | 33.67 | 23.96 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 | 0.406715E+10 | 6788.62 | 02-NOV-13:20 | 29.80 | 24.39 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 | 0.341904E+10 | 6459.93 | 13-DEC-15:20 | 29.67 | 21.50 |
Annual Sum or Average | 0.00 | 0.569445E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 14.12 | 12.36 | 0.288871E+10 | 6039.96 | 24.58 | 18.48 | ||
Maximum of Months | 0.00 | 0.00 | 25.13 | 24.22 | 0.618558E+10 | 9097.65 | 35.60 | 26.43 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.609379E+09 | 31118.28 | 11-JAN-06:01 | 8.00 |
February | 0.335478E+09 | 31206.17 | 07-FEB-06:01 | 8.62 |
March | 0.277584E+09 | 30733.91 | 13-MAR-05:01 | 6.68 |
April | 21083319.76 | 1479.30 | 11-APR-06:30 | 10.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 9879530.89 | 791.39 | 30-OCT-06:15 | 16.33 |
November | 51726982.20 | 3801.54 | 15-NOV-07:20 | 7.90 |
December | 0.363560E+09 | 30361.75 | 23-DEC-06:01 | 6.17 |
Annual Sum or Average | 0.166869E+10 | |||
Minimum of Months | 0.00 | 0.00 | 6.17 | |
Maximum of Months | 0.609379E+09 | 31206.17 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158823E+10 | 5224.57 | 11-JAN-17:10 | 18.50 |
February | 0.113702E+10 | 17919.70 | 05-FEB-08:65 | -2.9 |
March | 0.912446E+09 | 4799.77 | 07-MAR-07:13 | 21.10 |
April | 0.246261E+09 | 4238.13 | 01-APR-06:30 | 20.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 25250.01 | 42.08 | 07-JUN-06:10 | 21.38 |
July | 55252.65 | 184.18 | 11-JUL-06:05 | 26.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 46353.14 | 154.51 | 07-SEP-06:05 | 25.77 |
October | 0.125622E+09 | 4261.57 | 19-OCT-06:20 | 21.67 |
November | 0.424717E+09 | 5015.54 | 29-NOV-07:13 | 21.80 |
December | 0.111265E+10 | 6078.82 | 23-DEC-17:20 | 21.33 |
Annual Sum or Average | 0.554707E+10 | |||
Minimum of Months | 0.00 | 0.00 | -2.9 | |
Maximum of Months | 0.158823E+10 | 17919.70 | 26.28 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:05 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.258145E+10 | 1955.04 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.235440E+10 | 1955.04 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.269003E+10 | 1955.04 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.254196E+10 | 1955.04 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.263574E+10 | 1955.04 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.259625E+10 | 1955.04 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.258145E+10 | 1955.04 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.269003E+10 | 1955.04 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.254196E+10 | 1955.04 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.258145E+10 | 1955.04 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.248766E+10 | 1955.04 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.258145E+10 | 1955.04 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.308638E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.235440E+10 | 1955.04 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.269003E+10 | 1955.04 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.198922E+11 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.182065E+11 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.210336E+11 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.197108E+11 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.204629E+11 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.202815E+11 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.198922E+11 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.210336E+11 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.197108E+11 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.198922E+11 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.191400E+11 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.198922E+11 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.239148E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.182065E+11 | 17848.24 | 0.00 | 0.00 | |
Maximum of Months | 0.210336E+11 | 17848.24 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.294120E+11 | 26389.90 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.269196E+11 | 26389.90 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.310997E+11 | 26389.90 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.291438E+11 | 26389.90 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.302559E+11 | 26389.90 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.299876E+11 | 26389.90 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.294120E+11 | 26389.90 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.310997E+11 | 26389.90 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.291438E+11 | 26389.90 | 01-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.294120E+11 | 26389.90 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.282999E+11 | 26389.90 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.294120E+11 | 26389.90 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.353598E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.269196E+11 | 26389.90 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.310997E+11 | 26389.90 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15997083.90 | 0.253084E+10 |
February | 0.127628E+10 | 0.235440E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28602302.14 | 0.172316E+10 |
March | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80049055.69 | 0.193365E+10 |
April | 0.138726E+10 | 0.254196E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245426E+09 | 0.759839E+09 |
May | 0.144276E+10 | 0.263574E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.848262E+09 | 58916652.55 |
June | 0.144276E+10 | 0.259625E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.975540E+09 | 46430979.05 |
July | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.920885E+09 | 36013287.22 |
August | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105417E+10 | 52689223.74 |
September | 0.138726E+10 | 0.254196E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.580412E+09 | 0.109661E+09 |
October | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.591784E+09 | 0.599649E+09 |
November | 0.133177E+10 | 0.248766E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119221E+09 | 0.120823E+10 |
December | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56890235.28 | 0.211931E+10 |
Annual Sum or Average | 0.168137E+11 | 0.308638E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551724E+10 | 0.111784E+11 |
Minimum of Months | 0.127628E+10 | 0.235440E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15997083.90 | 36013287.22 |
Maximum of Months | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105417E+10 | 0.253084E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1610985.64 | 0.901904E+10 |
February | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4378793.65 | 0.660384E+10 |
March | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24769761.74 | 0.797652E+10 |
April | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179157E+09 | 0.390729E+10 |
May | 0.339505E+10 | 0.204629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.930677E+09 | 0.110523E+10 |
June | 0.339505E+10 | 0.202815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107726E+10 | 0.720094E+09 |
July | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129910E+10 | 0.423406E+09 |
August | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138491E+10 | 0.105473E+10 |
September | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.906568E+09 | 0.165058E+10 |
October | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778904E+09 | 0.382555E+10 |
November | 0.313390E+10 | 0.191400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41794895.90 | 0.518008E+10 |
December | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20109581.57 | 0.797721E+10 |
Annual Sum or Average | 0.395654E+11 | 0.239148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664924E+10 | 0.494436E+11 |
Minimum of Months | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1610985.64 | 0.423406E+09 |
Maximum of Months | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138491E+10 | 0.901904E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64593489.02 | 0.267224E+11 |
February | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31434165.10 | 0.207044E+11 |
March | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5574490.53 | 0.290226E+11 |
April | 0.750829E+10 | 0.291438E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183424E+11 |
May | 0.780862E+10 | 0.302559E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 808010.27 | 0.107503E+11 |
June | 0.780862E+10 | 0.299876E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33536.19 | 0.735087E+10 |
July | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1154862.46 | 0.665554E+10 |
August | 0.810895E+10 | 0.310997E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4719576.62 | 0.103355E+11 |
September | 0.750829E+10 | 0.291438E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28905977.99 | 0.128637E+11 |
October | 0.750829E+10 | 0.294120E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215498E+11 |
November | 0.720796E+10 | 0.282999E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18270112.71 | 0.191547E+11 |
December | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16376564.26 | 0.255257E+11 |
Annual Sum or Average | 0.910005E+11 | 0.353598E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171871E+09 | 0.208978E+12 |
Minimum of Months | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.665554E+10 |
Maximum of Months | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64593489.02 | 0.290226E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1955.04 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 778.52 | 19-JAN-12:10 | 9094.34 | 04-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 1955.04 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1798.20 | 02-FEB-13:00 | 8358.90 | 17-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 1955.04 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1664.42 | 30-MAR-12:00 | 9862.72 | 09-MAR-07:10 |
April | 1680.92 | 01-APR-07:10 | 1955.04 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3470.84 | 28-APR-16:10 | 5034.55 | 11-APR-06:03 |
May | 1680.92 | 01-MAY-07:10 | 1955.04 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3877.54 | 10-MAY-16:10 | 681.16 | 02-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 1955.04 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3895.57 | 28-JUN-16:10 | 1120.82 | 07-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 1955.04 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4413.27 | 21-JUL-16:10 | 567.86 | 30-JUL-10:53 |
August | 1680.92 | 01-AUG-07:10 | 1955.04 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5297.30 | 03-AUG-16:10 | 917.88 | 29-AUG-06:10 |
September | 1680.92 | 01-SEP-07:10 | 1955.04 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3398.63 | 06-SEP-16:10 | 1763.77 | 07-SEP-17:00 |
October | 1680.92 | 02-OCT-07:10 | 1955.04 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3584.63 | 13-OCT-16:10 | 4457.13 | 27-OCT-06:05 |
November | 1680.92 | 01-NOV-07:10 | 1955.04 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1993.29 | 02-NOV-12:00 | 5991.26 | 15-NOV-08:00 |
December | 1680.92 | 01-DEC-08:09 | 1955.04 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1564.92 | 13-DEC-13:00 | 9962.26 | 20-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 778.52 | 567.86 | |||||
Maximum of Months | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 5297.30 | 9962.26 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.07 | 16-JAN-15:00 | 16600.60 | 09-JAN-16:55 |
February | 3955.50 | 01-FEB-08:09 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 647.02 | 02-FEB-13:00 | 21516.40 | 16-FEB-17:55 |
March | 3955.50 | 01-MAR-08:09 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1419.19 | 27-MAR-15:10 | 15760.09 | 09-MAR-09:00 |
April | 3955.50 | 01-APR-07:10 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3935.42 | 28-APR-15:10 | 11769.10 | 01-APR-17:00 |
May | 3955.50 | 01-MAY-07:10 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4232.74 | 18-MAY-16:33 | 3278.35 | 05-MAY-06:10 |
June | 3955.50 | 01-JUN-07:10 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5831.55 | 08-JUN-15:10 | 4314.56 | 06-JUN-20:53 |
July | 3955.50 | 01-JUL-07:10 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5345.12 | 06-JUL-15:10 | 2027.74 | 12-JUL-15:10 |
August | 3955.50 | 01-AUG-07:10 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6735.97 | 03-AUG-16:40 | 4406.25 | 25-AUG-24:00 |
September | 3955.50 | 01-SEP-07:10 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6460.03 | 09-SEP-17:00 | 4187.43 | 19-SEP-19:00 |
October | 3955.50 | 02-OCT-07:10 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5999.59 | 09-OCT-13:56 | 10915.79 | 27-OCT-08:00 |
November | 3955.50 | 01-NOV-07:10 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1402.86 | 02-NOV-15:10 | 10720.32 | 22-NOV-09:00 |
December | 3955.50 | 01-DEC-08:09 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 836.82 | 13-DEC-16:10 | 14610.84 | 30-DEC-16:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.07 | 2027.74 | ||||
Maximum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6735.97 | 21516.40 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 26389.90 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3436.64 | 16-JAN-15:00 | 47988.59 | 03-JAN-09:00 |
February | 9097.65 | 01-FEB-08:09 | 26389.90 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3292.52 | 20-FEB-15:00 | 57090.31 | 04-FEB-11:00 |
March | 9097.65 | 01-MAR-08:09 | 26389.90 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1048.86 | 26-MAR-13:33 | 52447.86 | 09-MAR-09:00 |
April | 9097.65 | 01-APR-07:10 | 26389.90 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 41440.88 | 01-APR-16:00 |
May | 9097.65 | 01-MAY-07:10 | 26389.90 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1092.79 | 27-MAY-13:43 | 26663.27 | 26-MAY-15:00 |
June | 9097.65 | 01-JUN-07:10 | 26389.90 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.31 | 25-JUN-12:53 | 23173.51 | 01-JUN-13:00 |
July | 9097.65 | 01-JUL-07:10 | 26389.90 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1266.86 | 02-JUL-10:52 | 26270.45 | 31-JUL-10:55 |
August | 9097.65 | 01-AUG-07:10 | 26389.90 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 792.57 | 20-AUG-13:45 | 19080.99 | 25-AUG-24:00 |
September | 9097.65 | 01-SEP-07:10 | 26389.90 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.09 | 09-SEP-17:00 | 23211.84 | 12-SEP-20:00 |
October | 9097.65 | 02-OCT-07:10 | 26389.90 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 42279.40 | 27-OCT-11:00 |
November | 9097.65 | 01-NOV-07:10 | 26389.90 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2594.09 | 28-NOV-13:10 | 34204.16 | 09-NOV-08:10 |
December | 9097.65 | 01-DEC-08:09 | 26389.90 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1814.64 | 31-DEC-11:10 | 44176.60 | 19-DEC-12:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19080.99 | |||||
Maximum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 3436.64 | 57090.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20133.51 | 02-JAN-00:02 | 0.00 | 2742.13 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 515.23 |
February | 20939.37 | 27-FEB-00:01 | 0.00 | 3199.16 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20864.45 | 06-MAR-00:02 | 0.00 | 2742.13 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.36 |
April | 24394.64 | 16-APR-23:02 | 0.00 | 2285.11 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.60 |
May | 20476.89 | 30-MAY-05:03 | 554.70 | 1751.92 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 73.79 | 0.00 |
June | 21915.28 | 11-JUN-23:01 | 0.00 | 4570.22 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.50 |
July | 19804.97 | 10-JUL-05:43 | 554.70 | 1751.92 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 70.87 | 0.00 |
August | 20152.68 | 30-AUG-21:03 | 0.00 | 1371.07 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20098.72 | 22-SEP-19:43 | 0.00 | 1371.07 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 235.82 | 0.00 |
October | 23735.30 | 01-OCT-23:01 | 0.00 | 4113.20 | 5163.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 616.22 |
November | 21805.27 | 05-NOV-23:01 | 0.00 | 4570.22 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.53 |
December | 19345.54 | 11-DEC-00:01 | 0.00 | 3199.16 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19345.54 | 0.00 | 1371.07 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24394.64 | 554.70 | 4570.22 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 235.82 | 616.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 49778.90 | 01-JAN-14:23 | 0.00 | 6299.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.91 |
February | 49449.81 | 26-FEB-14:43 | 0.00 | 6299.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.32 |
March | 60859.17 | 26-MAR-14:13 | 0.00 | 6299.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.52 | 0.00 |
April | 73876.32 | 23-APR-13:53 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.54 | 0.00 |
May | 75190.28 | 04-MAY-17:06 | 0.00 | 10498.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.92 | 0.00 |
June | 75879.28 | 12-JUN-17:05 | 0.00 | 12598.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 761.37 | 0.00 |
July | 71239.47 | 23-JUL-11:43 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 957.10 | 0.00 |
August | 71676.04 | 06-AUG-16:33 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 766.29 |
September | 72713.14 | 22-SEP-17:06 | 0.00 | 10498.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1552.02 | 0.00 |
October | 80856.00 | 01-OCT-15:23 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.02 | 0.00 |
November | 58835.18 | 05-NOV-13:53 | 0.00 | 6299.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.16 | 0.00 |
December | 48714.97 | 10-DEC-15:03 | 0.00 | 6299.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 48714.97 | 0.00 | 6299.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 80856.00 | 0.00 | 12598.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1552.02 | 766.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9542.94 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4389.76 |
March | 0.00 | 01-MAR-00:05 | 0.00 | 6209.39 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7280.32 |
April | 0.00 | 01-APR-00:05 | 0.00 | 6209.39 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8308.03 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4403.41 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2915.52 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2990.75 |
August | 0.00 | 01-AUG-00:05 | 0.00 | 6209.39 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4588.57 |
September | 0.00 | 01-SEP-00:03 | 0.00 | 12418.78 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512.39 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8944.06 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4068.15 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8825.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512.39 | |
Maximum of Months | 0.00 | 0.00 | 12418.78 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9542.94 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.892862E+11 | 79927.97 | 19-JAN-15:09 | 0.894719E+10 | 21108.00 | 10-JAN-07:10 |
February | 0.830426E+11 | 81942.02 | 27-FEB-15:20 | 0.775239E+10 | 21882.18 | 06-FEB-06:10 |
March | 0.960261E+11 | 84240.63 | 30-MAR-12:50 | 0.842783E+10 | 18858.86 | 09-MAR-07:10 |
April | 0.963729E+11 | 92064.17 | 28-APR-14:00 | 0.777780E+10 | 5463.81 | 11-APR-06:30 |
May | 0.112490E+12 | 92459.60 | 25-MAY-14:20 | 0.803520E+10 | 3000.00 | 01-MAY-00:10 |
June | 0.114009E+12 | 94538.77 | 28-JUN-14:00 | 0.777600E+10 | 3000.00 | 01-JUN-00:10 |
July | 0.114898E+12 | 95393.64 | 21-JUL-14:39 | 0.803520E+10 | 3000.00 | 01-JUL-00:10 |
August | 0.119743E+12 | 96042.03 | 03-AUG-14:00 | 0.803520E+10 | 3000.00 | 01-AUG-00:10 |
September | 0.109092E+12 | 93499.75 | 09-SEP-14:50 | 0.777600E+10 | 3000.00 | 01-SEP-00:10 |
October | 0.106607E+12 | 94073.63 | 07-OCT-13:09 | 0.803520E+10 | 3000.00 | 01-OCT-00:10 |
November | 0.914507E+11 | 88762.59 | 02-NOV-14:30 | 0.782318E+10 | 9271.73 | 15-NOV-07:19 |
December | 0.919531E+11 | 86492.24 | 15-DEC-13:00 | 0.858611E+10 | 22443.78 | 21-DEC-07:10 |
Annual Sum or Average | 0.122497E+13 | 0.970073E+11 | ||||
Minimum of Months | 0.830426E+11 | 79927.97 | 0.775239E+10 | 3000.00 | ||
Maximum of Months | 0.119743E+12 | 96042.03 | 0.894719E+10 | 22443.78 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.518856E+11 | 0.128802E+11 | 0.115358E+11 | 0.00 | 0.873223E+10 | 0.00 | 0.00 | 0.213134E+10 | 0.00 | 0.00 | 0.00 | 0.212094E+10 | 0.00 |
February | 0.474804E+11 | 0.111243E+11 | 0.105871E+11 | 0.00 | 0.805611E+10 | 0.00 | 0.00 | 0.387413E+10 | 0.00 | 0.00 | 0.00 | 0.192049E+10 | 0.00 |
March | 0.548234E+11 | 0.115492E+11 | 0.123431E+11 | 0.00 | 0.950944E+10 | 0.00 | 0.00 | 0.566596E+10 | 0.00 | 0.00 | 0.00 | 0.213499E+10 | 0.00 |
April | 0.513965E+11 | 0.104332E+11 | 0.114862E+11 | 0.00 | 0.965737E+10 | 0.00 | 0.00 | 0.114043E+11 | 0.00 | 0.00 | 0.00 | 0.199535E+10 | 0.00 |
May | 0.533545E+11 | 0.101107E+11 | 0.119357E+11 | 0.00 | 0.126688E+11 | 0.00 | 0.00 | 0.224008E+11 | 0.00 | 0.00 | 0.00 | 0.201935E+10 | 0.00 |
June | 0.528654E+11 | 0.941957E+10 | 0.118862E+11 | 0.00 | 0.134390E+11 | 0.00 | 0.00 | 0.244648E+11 | 0.00 | 0.00 | 0.00 | 0.193426E+10 | 0.00 |
July | 0.518856E+11 | 0.992638E+10 | 0.115358E+11 | 0.00 | 0.136373E+11 | 0.00 | 0.00 | 0.259693E+11 | 0.00 | 0.00 | 0.00 | 0.194353E+10 | 0.00 |
August | 0.548234E+11 | 0.104690E+11 | 0.123357E+11 | 0.00 | 0.137826E+11 | 0.00 | 0.00 | 0.263424E+11 | 0.00 | 0.00 | 0.00 | 0.198939E+10 | 0.00 |
September | 0.513965E+11 | 0.108632E+11 | 0.114788E+11 | 0.00 | 0.119128E+11 | 0.00 | 0.00 | 0.215112E+11 | 0.00 | 0.00 | 0.00 | 0.192968E+10 | 0.00 |
October | 0.518856E+11 | 0.120048E+11 | 0.115432E+11 | 0.00 | 0.111271E+11 | 0.00 | 0.00 | 0.180283E+11 | 0.00 | 0.00 | 0.00 | 0.201821E+10 | 0.00 |
November | 0.499276E+11 | 0.122659E+11 | 0.110862E+11 | 0.00 | 0.867402E+10 | 0.00 | 0.00 | 0.750404E+10 | 0.00 | 0.00 | 0.00 | 0.199284E+10 | 0.00 |
December | 0.518856E+11 | 0.130492E+11 | 0.115358E+11 | 0.00 | 0.881369E+10 | 0.00 | 0.00 | 0.456676E+10 | 0.00 | 0.00 | 0.00 | 0.210202E+10 | 0.00 |
Annual Sum or Average | 0.623610E+12 | 0.134096E+12 | 0.139290E+12 | 0.00 | 0.130010E+12 | 0.00 | 0.00 | 0.173863E+12 | 0.00 | 0.00 | 0.00 | 0.241011E+11 | 0.00 |
Minimum of Months | 0.474804E+11 | 0.941957E+10 | 0.105871E+11 | 0.00 | 0.805611E+10 | 0.00 | 0.00 | 0.213134E+10 | 0.00 | 0.00 | 0.00 | 0.192049E+10 | 0.00 |
Maximum of Months | 0.548234E+11 | 0.130492E+11 | 0.123431E+11 | 0.00 | 0.137826E+11 | 0.00 | 0.00 | 0.263424E+11 | 0.00 | 0.00 | 0.00 | 0.213499E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.894719E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.775239E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.842783E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.777780E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.803520E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.777600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.803520E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.803520E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.777600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.803520E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.782318E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.858611E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.970073E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.775239E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.894719E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 46193.18 | 02-JAN-09:09 | 8532.22 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 8785.10 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 46193.18 | 01-FEB-09:09 | 8532.22 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 9553.53 | 27-FEB-14:39 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 46193.18 | 01-MAR-09:09 | 8532.22 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 11090.40 | 28-MAR-12:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 46193.18 | 01-APR-08:09 | 8532.22 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 11090.40 | 05-APR-13:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 46193.18 | 01-MAY-08:09 | 8532.22 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 11090.40 | 10-MAY-11:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 46193.18 | 01-JUN-08:09 | 8532.22 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 11090.40 | 03-JUN-14:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 46193.18 | 01-JUL-08:09 | 8532.22 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 11090.40 | 03-JUL-11:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 46193.18 | 01-AUG-08:09 | 8532.22 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 11090.40 | 05-AUG-16:19 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 46193.18 | 01-SEP-08:09 | 8532.22 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 11090.40 | 09-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 46193.18 | 02-OCT-08:09 | 8532.22 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 11090.40 | 12-OCT-12:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 46193.18 | 01-NOV-08:09 | 8532.22 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 11090.40 | 07-NOV-14:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 46193.18 | 01-DEC-09:09 | 8532.22 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 11090.40 | 13-DEC-14:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 46193.18 | 8532.22 | 10112.62 | 0.00 | 8785.10 | 0.00 | 0.00 | |||||
Maximum of Months | 46193.18 | 8532.22 | 10112.62 | 0.00 | 11090.40 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 13113.00 | 19-JAN-14:00 | 0.00 | 0.00 | 0.00 | 1780.55 | 23-JAN-12:39 | 0.00 |
February | 14493.29 | 24-FEB-13:00 | 0.00 | 0.00 | 0.00 | 1780.27 | 06-FEB-12:50 | 0.00 |
March | 15388.26 | 29-MAR-14:00 | 0.00 | 0.00 | 0.00 | 1772.43 | 01-MAR-12:09 | 0.00 |
April | 23736.63 | 28-APR-15:39 | 0.00 | 0.00 | 0.00 | 1756.65 | 01-APR-11:09 | 0.00 |
May | 23877.19 | 25-MAY-15:09 | 0.00 | 0.00 | 0.00 | 1738.55 | 01-MAY-11:39 | 0.00 |
June | 26313.88 | 28-JUN-15:30 | 0.00 | 0.00 | 0.00 | 1721.24 | 01-JUN-11:30 | 0.00 |
July | 27209.42 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | 1710.29 | 01-JUL-11:30 | 0.00 |
August | 28987.87 | 03-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1714.55 | 31-AUG-11:50 | 0.00 |
September | 28100.52 | 09-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1728.69 | 30-SEP-11:39 | 0.00 |
October | 25386.16 | 06-OCT-11:00 | 0.00 | 0.00 | 0.00 | 1747.64 | 31-OCT-11:39 | 0.00 |
November | 19646.81 | 02-NOV-14:30 | 0.00 | 0.00 | 0.00 | 1765.17 | 30-NOV-12:09 | 0.00 |
December | 17357.02 | 15-DEC-13:00 | 0.00 | 0.00 | 0.00 | 1777.69 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 13113.00 | 0.00 | 0.00 | 0.00 | 1710.29 | 0.00 | ||
Maximum of Months | 28987.87 | 0.00 | 0.00 | 0.00 | 1780.55 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 79927.97 | 19-JAN-15:09 | 46193.18 | 10112.62 | 0.00 | 0.00 | 8785.10 | 0.00 | 0.00 | 13091.38 | 0.00 |
February | 81942.02 | 27-FEB-15:20 | 46193.18 | 10112.62 | 0.00 | 0.00 | 9553.53 | 0.00 | 0.00 | 14342.28 | 0.00 |
March | 84240.63 | 30-MAR-12:50 | 46193.18 | 10112.62 | 0.00 | 0.00 | 11090.40 | 0.00 | 0.00 | 15117.38 | 0.00 |
April | 92064.17 | 28-APR-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 11090.40 | 0.00 | 0.00 | 22955.67 | 0.00 |
May | 92459.60 | 25-MAY-14:20 | 46193.18 | 10112.62 | 0.00 | 0.00 | 11090.40 | 0.00 | 0.00 | 23364.29 | 0.00 |
June | 94538.77 | 28-JUN-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 11090.40 | 0.00 | 0.00 | 25455.41 | 0.00 |
July | 95393.64 | 21-JUL-14:39 | 46193.18 | 10112.62 | 0.00 | 0.00 | 11090.40 | 0.00 | 0.00 | 26312.80 | 0.00 |
August | 96042.03 | 03-AUG-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 11090.40 | 0.00 | 0.00 | 26961.33 | 0.00 |
September | 93499.75 | 09-SEP-14:50 | 46193.18 | 10112.62 | 0.00 | 0.00 | 11090.40 | 0.00 | 0.00 | 24410.39 | 0.00 |
October | 94073.63 | 07-OCT-13:09 | 46193.18 | 10112.62 | 0.00 | 0.00 | 11090.40 | 0.00 | 0.00 | 24997.22 | 0.00 |
November | 88762.59 | 02-NOV-14:30 | 46193.18 | 10112.62 | 0.00 | 0.00 | 11090.40 | 0.00 | 0.00 | 19646.81 | 0.00 |
December | 86492.24 | 15-DEC-13:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 11090.40 | 0.00 | 0.00 | 17357.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 79927.97 | 46193.18 | 10112.62 | 0.00 | 0.00 | 8785.10 | 0.00 | 0.00 | 13091.38 | 0.00 | |
Maximum of Months | 96042.03 | 46193.18 | 10112.62 | 0.00 | 0.00 | 11090.40 | 0.00 | 0.00 | 26961.33 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 21108.00 | 10-JAN-07:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 21882.18 | 06-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 18858.86 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 5463.81 | 11-APR-06:30 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 3000.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 3000.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 3000.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 3000.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 3000.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 3000.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 9271.73 | 15-NOV-07:19 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 22443.78 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 3000.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 22443.78 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 20.28 | 1.00 | 20.28 | 1.50 | 22.08 | 0.17 | 22.19 |
February | 0.67 | 20.24 | 0.67 | 20.24 | 3.83 | 23.40 | 0.17 | 23.44 |
March | 0.50 | 20.47 | 0.50 | 20.47 | 6.67 | 23.98 | 0.33 | 24.01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 19.83 | 24.61 | 0.33 | 24.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 65.67 | 24.67 | 2.17 | 24.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 74.17 | 24.69 | 3.17 | 24.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 77.00 | 24.77 | 3.67 | 24.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 84.00 | 24.77 | 4.17 | 24.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 68.50 | 24.74 | 2.83 | 24.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 55.50 | 24.68 | 1.83 | 24.67 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 24.53 | 0.00 | 24.53 |
December | 1.00 | 20.35 | 1.00 | 20.35 | 2.67 | 22.72 | 0.00 | 22.72 |
Annual Sum or Average | 3.17 | 20.32 | 3.17 | 20.32 | 471.17 | 24.65 | 18.83 | 24.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 22.08 | 0.00 | 22.19 |
Maximum of Months | 1.00 | 20.47 | 1.00 | 20.47 | 84.00 | 24.77 | 4.17 | 24.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.37 | 0.00 | 27.37 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.34 | 0.00 | 27.34 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.35 | 0.00 | 27.35 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.49 | 0.00 | 27.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 26.67 | 27.63 | 0.00 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 27.64 | 0.33 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 41.33 | 27.63 | 0.33 | 27.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 34.00 | 27.61 | 0.33 | 27.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 | 27.69 | 0.00 | 27.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 27.63 | 0.33 | 27.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.41 | 0.00 | 27.41 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.32 | 0.00 | 27.32 |
Annual Sum or Average | 0.00 | 0.00 | 195.50 | 27.62 | 1.33 | 27.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.32 | 0.00 | 27.32 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 41.33 | 27.69 | 0.33 | 27.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 221.83 | 22.83 | 103.33 | 22.82 | 49.83 | 22.66 |
February | 144.67 | 22.94 | 120.17 | 23.12 | 27.33 | 22.97 |
March | 144.67 | 22.91 | 142.67 | 23.26 | 18.50 | 23.16 |
April | 33.17 | 23.34 | 229.17 | 23.83 | 3.83 | 23.84 |
May | 32.83 | 23.90 | 312.00 | 23.91 | 32.83 | 23.91 |
June | 25.33 | 23.90 | 311.50 | 23.91 | 25.33 | 23.91 |
July | 47.33 | 23.90 | 300.00 | 23.91 | 47.33 | 23.91 |
August | 51.50 | 23.90 | 324.00 | 23.91 | 51.50 | 23.91 |
September | 44.33 | 23.90 | 300.00 | 23.91 | 44.33 | 23.91 |
October | 48.67 | 23.81 | 262.17 | 23.89 | 35.83 | 23.89 |
November | 74.83 | 23.24 | 166.83 | 23.70 | 12.00 | 23.71 |
December | 176.83 | 22.93 | 124.50 | 23.16 | 33.17 | 23.07 |
Annual Sum or Average | 1046.00 | 23.17 | 2696.33 | 23.63 | 381.83 | 23.59 |
Minimum of Months | 25.33 | 22.83 | 103.33 | 22.82 | 3.83 | 22.66 |
Maximum of Months | 221.83 | 23.90 | 324.00 | 23.91 | 51.50 | 23.91 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 178.83 | 22.90 | 200.00 | 23.72 | 103.17 | 23.49 |
February | 162.83 | 24.14 | 210.83 | 24.88 | 113.00 | 24.81 |
March | 192.00 | 24.60 | 254.17 | 25.31 | 138.00 | 25.29 |
April | 221.33 | 26.46 | 282.83 | 26.53 | 208.83 | 26.56 |
May | 311.17 | 26.72 | 312.00 | 26.72 | 311.17 | 26.72 |
June | 309.17 | 26.72 | 312.00 | 26.72 | 309.17 | 26.72 |
July | 300.00 | 26.72 | 300.00 | 26.72 | 300.00 | 26.72 |
August | 321.00 | 26.72 | 324.00 | 26.72 | 321.00 | 26.72 |
September | 296.67 | 26.72 | 300.00 | 26.72 | 296.67 | 26.72 |
October | 255.67 | 26.64 | 291.00 | 26.65 | 251.00 | 26.67 |
November | 141.00 | 25.68 | 248.00 | 26.25 | 107.83 | 26.32 |
December | 209.33 | 24.24 | 203.17 | 24.85 | 127.67 | 24.84 |
Annual Sum or Average | 2899.00 | 25.94 | 3238.00 | 26.14 | 2587.50 | 26.18 |
Minimum of Months | 141.00 | 22.90 | 200.00 | 23.72 | 103.17 | 23.49 |
Maximum of Months | 321.00 | 26.72 | 324.00 | 26.72 | 321.00 | 26.72 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 290.33 | 21.12 | 176.33 | 20.90 | 170.33 | 20.76 |
February | 256.83 | 22.82 | 187.17 | 22.98 | 173.67 | 23.01 |
March | 242.00 | 24.11 | 232.00 | 24.61 | 163.17 | 24.69 |
April | 264.50 | 28.60 | 280.67 | 28.58 | 250.67 | 28.68 |
May | 312.00 | 30.57 | 312.00 | 30.57 | 312.00 | 30.57 |
June | 312.00 | 31.07 | 312.00 | 31.07 | 312.00 | 31.07 |
July | 300.00 | 31.10 | 300.00 | 31.10 | 300.00 | 31.10 |
August | 324.00 | 30.82 | 324.00 | 30.82 | 324.00 | 30.82 |
September | 300.00 | 29.86 | 300.00 | 29.86 | 300.00 | 29.86 |
October | 273.83 | 29.63 | 292.83 | 29.52 | 268.50 | 29.60 |
November | 188.00 | 26.17 | 223.00 | 26.65 | 136.17 | 26.91 |
December | 263.33 | 22.83 | 204.67 | 23.10 | 179.00 | 23.09 |
Annual Sum or Average | 3326.83 | 27.64 | 3144.67 | 27.92 | 2889.50 | 28.08 |
Minimum of Months | 188.00 | 21.12 | 176.33 | 20.90 | 136.17 | 20.76 |
Maximum of Months | 324.00 | 31.10 | 324.00 | 31.10 | 324.00 | 31.10 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.322289E+10 | 0.855609E+09 | 178.61 | 0.249520E+10 | 0.727690E+09 | 0.00 | 1.00 | 02-JAN-00:02 | 0.00 | 01-JAN-00:10 | 30539.52 | 02-JAN-00:02 | 21653.50 | 02-JAN-00:02 | 8886.03 | 02-JAN-00:02 | 7081.83 | 02-JAN-00:02 | 0.00 | 01-JAN-00:10 |
February | 0.469743E+10 | 0.124407E+10 | 214.32 | 0.356612E+10 | 0.113130E+10 | 0.00 | 1.00 | 27-FEB-00:01 | 0.00 | 01-FEB-00:15 | 30277.58 | 27-FEB-00:01 | 22393.26 | 27-FEB-00:01 | 8236.96 | 27-FEB-00:03 | 7036.31 | 27-FEB-00:01 | 0.00 | 01-FEB-00:10 |
March | 0.643180E+10 | 0.170537E+10 | 278.22 | 0.497476E+10 | 0.145704E+10 | 0.00 | 1.00 | 06-MAR-00:02 | 0.00 | 01-MAR-00:05 | 31432.35 | 26-MAR-23:01 | 22907.54 | 06-MAR-00:02 | 10151.89 | 26-MAR-23:02 | 7230.37 | 26-MAR-23:01 | 0.00 | 01-MAR-00:05 |
April | 0.111882E+11 | 0.299946E+10 | 394.96 | 0.868787E+10 | 0.250037E+10 | 0.00 | 1.00 | 14-APR-17:08 | 0.00 | 01-APR-00:05 | 32834.60 | 23-APR-23:01 | 26263.70 | 16-APR-23:02 | 13055.13 | 23-APR-23:04 | 7492.13 | 28-APR-17:06 | 0.00 | 01-APR-00:05 |
May | 0.197816E+11 | 0.538383E+10 | 528.63 | 0.140529E+11 | 0.572870E+10 | 0.00 | 1.00 | 01-MAY-17:08 | 0.00 | 01-MAY-00:15 | 34410.43 | 21-MAY-23:01 | 23595.31 | 03-MAY-17:42 | 16427.84 | 21-MAY-23:05 | 7792.77 | 21-MAY-23:01 | 0.00 | 01-MAY-00:10 |
June | 0.209801E+11 | 0.576714E+10 | 529.02 | 0.150054E+11 | 0.597466E+10 | 0.00 | 1.00 | 01-JUN-17:06 | 0.00 | 01-JUN-00:15 | 34311.43 | 04-JUN-23:01 | 24149.85 | 12-JUN-17:42 | 15763.41 | 04-JUN-23:06 | 7854.07 | 04-JUN-23:01 | 0.00 | 01-JUN-00:10 |
July | 0.217885E+11 | 0.593613E+10 | 516.64 | 0.148286E+11 | 0.695989E+10 | 0.00 | 1.00 | 01-JUL-17:08 | 0.00 | 01-JUL-00:13 | 34796.06 | 30-JUL-23:02 | 23027.65 | 18-JUL-21:43 | 18221.79 | 30-JUL-23:04 | 7908.40 | 02-JUL-23:01 | 0.00 | 01-JUL-00:10 |
August | 0.233489E+11 | 0.633009E+10 | 553.52 | 0.159487E+11 | 0.740021E+10 | 0.00 | 1.00 | 01-AUG-17:05 | 0.00 | 01-AUG-00:13 | 34646.09 | 06-AUG-23:01 | 23460.90 | 30-AUG-21:03 | 18286.62 | 13-AUG-23:06 | 7871.41 | 13-AUG-23:01 | 0.00 | 01-AUG-00:05 |
September | 0.197392E+11 | 0.524441E+10 | 516.31 | 0.133199E+11 | 0.641929E+10 | 0.00 | 1.00 | 01-SEP-17:08 | 0.00 | 01-SEP-00:13 | 35231.36 | 04-SEP-23:02 | 23354.16 | 22-SEP-17:42 | 19779.79 | 04-SEP-23:06 | 7904.49 | 09-SEP-17:05 | 0.00 | 01-SEP-00:03 |
October | 0.167497E+11 | 0.448840E+10 | 473.59 | 0.119592E+11 | 0.479051E+10 | 0.00 | 1.00 | 01-OCT-23:01 | 0.00 | 01-OCT-00:10 | 34671.08 | 22-OCT-23:01 | 25278.73 | 01-OCT-23:01 | 16944.14 | 22-OCT-23:05 | 7808.53 | 22-OCT-23:01 | 0.00 | 01-OCT-00:10 |
November | 0.832650E+10 | 0.221159E+10 | 320.74 | 0.641368E+10 | 0.191282E+10 | 0.00 | 1.00 | 01-NOV-17:43 | 0.00 | 01-NOV-00:15 | 31167.71 | 05-NOV-23:01 | 23293.42 | 05-NOV-23:01 | 12593.69 | 03-NOV-17:08 | 7388.07 | 03-NOV-17:08 | 0.00 | 01-NOV-00:10 |
December | 0.553338E+10 | 0.146793E+10 | 245.81 | 0.417125E+10 | 0.136213E+10 | 0.00 | 1.00 | 11-DEC-00:01 | 0.00 | 01-DEC-00:10 | 31503.32 | 11-DEC-00:01 | 21154.48 | 11-DEC-00:01 | 10611.75 | 11-DEC-00:03 | 7241.73 | 11-DEC-00:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.161788E+12 | 0.436340E+11 | 4750.38 | 0.115424E+12 | 0.463646E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.322289E+10 | 0.855609E+09 | 178.61 | 0.249520E+10 | 0.727690E+09 | 0.00 | 1.00 | 0.00 | 30277.58 | 21154.48 | 8236.96 | 7036.31 | 0.00 | |||||||
Maximum of Months | 0.233489E+11 | 0.633009E+10 | 553.52 | 0.159487E+11 | 0.740021E+10 | 0.00 | 1.00 | 0.00 | 35231.36 | 26263.70 | 19779.79 | 7908.40 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.443536E+10 | 0.127573E+10 | 91.25 | 0.324666E+10 | 0.118870E+10 | 0.00 | 0.68 | 01-JAN-14:23 | 0.00 | 01-JAN-00:10 | 66370.99 | 01-JAN-14:23 | 56089.82 | 01-JAN-14:23 | 10669.28 | 19-JAN-12:00 | 18151.96 | 01-JAN-14:23 | 0.00 | 01-JAN-00:10 |
February | 0.915910E+10 | 0.263007E+10 | 134.86 | 0.686986E+10 | 0.228924E+10 | 0.00 | 0.70 | 26-FEB-14:43 | 0.00 | 01-FEB-00:10 | 68580.03 | 26-FEB-14:43 | 56095.78 | 26-FEB-14:43 | 12484.24 | 26-FEB-14:43 | 18848.26 | 26-FEB-14:43 | 0.00 | 01-FEB-00:10 |
March | 0.137234E+11 | 0.396059E+10 | 197.72 | 0.105601E+11 | 0.316334E+10 | 0.00 | 0.85 | 26-MAR-14:13 | 0.00 | 01-MAR-00:05 | 84275.78 | 26-MAR-14:13 | 70133.04 | 26-MAR-14:13 | 14356.22 | 26-MAR-14:53 | 23244.04 | 26-MAR-14:13 | 0.00 | 01-MAR-00:05 |
April | 0.288150E+11 | 0.840482E+10 | 294.29 | 0.226339E+11 | 0.618104E+10 | 0.00 | 1.00 | 23-APR-13:53 | 0.00 | 01-APR-00:05 | 109731.48 | 28-APR-17:42 | 83662.54 | 23-APR-13:53 | 31993.12 | 29-APR-17:06 | 28657.65 | 28-APR-17:06 | 0.00 | 01-APR-00:05 |
May | 0.573200E+11 | 0.170169E+11 | 472.79 | 0.417880E+11 | 0.155319E+11 | 0.00 | 1.00 | 02-MAY-17:06 | 0.00 | 01-MAY-00:10 | 113553.86 | 28-MAY-09:23 | 87328.39 | 04-MAY-17:06 | 46565.36 | 28-MAY-09:23 | 29747.07 | 28-MAY-09:23 | 0.00 | 01-MAY-00:10 |
June | 0.624011E+11 | 0.186976E+11 | 504.51 | 0.464431E+11 | 0.159580E+11 | 0.00 | 1.00 | 01-JUN-17:06 | 0.00 | 01-JUN-00:10 | 107651.39 | 20-JUN-17:08 | 89513.91 | 11-JUN-15:32 | 35434.65 | 04-JUN-08:53 | 29432.75 | 20-JUN-17:08 | 0.00 | 01-JUN-00:10 |
July | 0.675188E+11 | 0.200331E+11 | 543.30 | 0.473255E+11 | 0.201933E+11 | 0.00 | 1.00 | 02-JUL-09:43 | 0.00 | 01-JUL-00:13 | 114515.63 | 02-JUL-09:43 | 82188.43 | 23-JUL-11:43 | 50389.07 | 02-JUL-09:03 | 30006.97 | 02-JUL-11:02 | 0.00 | 01-JUL-00:10 |
August | 0.677104E+11 | 0.200124E+11 | 527.84 | 0.476674E+11 | 0.200431E+11 | 0.00 | 1.00 | 01-AUG-17:05 | 0.00 | 01-AUG-00:10 | 113710.87 | 06-AUG-09:13 | 83991.62 | 30-AUG-17:05 | 46773.06 | 06-AUG-09:13 | 30162.28 | 20-AUG-13:32 | 0.00 | 01-AUG-00:05 |
September | 0.560167E+11 | 0.162668E+11 | 450.69 | 0.385612E+11 | 0.174554E+11 | 0.00 | 1.00 | 03-SEP-10:32 | 0.00 | 01-SEP-00:13 | 123578.33 | 04-SEP-23:01 | 84368.50 | 22-SEP-17:06 | 68416.19 | 04-SEP-23:01 | 30872.77 | 10-SEP-13:42 | 0.00 | 01-SEP-00:03 |
October | 0.464298E+11 | 0.135399E+11 | 392.69 | 0.333629E+11 | 0.130669E+11 | 0.00 | 1.00 | 01-OCT-13:23 | 0.00 | 01-OCT-00:10 | 117950.66 | 08-OCT-09:23 | 91188.57 | 01-OCT-15:23 | 54945.49 | 08-OCT-09:23 | 30326.31 | 08-OCT-14:02 | 0.00 | 01-OCT-00:10 |
November | 0.182809E+11 | 0.529245E+10 | 235.93 | 0.141378E+11 | 0.414312E+10 | 0.00 | 0.85 | 05-NOV-13:53 | 0.00 | 01-NOV-00:10 | 90303.95 | 11-NOV-13:23 | 67696.61 | 05-NOV-13:53 | 30190.04 | 11-NOV-13:23 | 23757.32 | 11-NOV-14:43 | 0.00 | 01-NOV-00:10 |
December | 0.107218E+11 | 0.309883E+10 | 142.56 | 0.804288E+10 | 0.267890E+10 | 0.00 | 0.71 | 10-DEC-15:03 | 0.00 | 01-DEC-00:10 | 69993.43 | 10-DEC-15:03 | 55951.11 | 10-DEC-15:03 | 14042.32 | 10-DEC-15:03 | 19649.79 | 10-DEC-15:03 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.442532E+12 | 0.130229E+12 | 3988.43 | 0.320639E+12 | 0.121893E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.443536E+10 | 0.127573E+10 | 91.25 | 0.324666E+10 | 0.118870E+10 | 0.00 | 0.68 | 0.00 | 66370.99 | 55951.11 | 10669.28 | 18151.96 | 0.00 | |||||||
Maximum of Months | 0.677104E+11 | 0.200331E+11 | 543.30 | 0.476674E+11 | 0.201933E+11 | 0.00 | 1.00 | 0.00 | 123578.33 | 91188.57 | 68416.19 | 30872.77 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.99 | 28.67 | 24.32 | 95.83 | 174.63 | 7.33 | 0.00 | 0.00 |
February | 59.89 | 30.29 | 29.60 | 115.23 | 149.10 | 2.17 | 0.00 | 0.00 |
March | 58.96 | 26.02 | 32.95 | 120.90 | 133.60 | 1.67 | 0.00 | 0.00 |
April | 72.95 | 33.32 | 39.63 | 179.19 | 86.43 | 0.00 | 0.00 | 0.00 |
May | 61.05 | 19.86 | 41.18 | 201.39 | 25.91 | 0.00 | 0.00 | 0.00 |
June | 67.84 | 23.82 | 44.03 | 232.21 | 22.39 | 0.00 | 0.00 | 0.00 |
July | 61.94 | 17.23 | 44.72 | 206.50 | 16.04 | 0.00 | 0.00 | 0.00 |
August | 62.49 | 19.02 | 43.47 | 212.23 | 22.42 | 0.00 | 0.00 | 0.00 |
September | 57.55 | 19.69 | 37.86 | 178.48 | 33.30 | 0.00 | 0.00 | 0.00 |
October | 58.80 | 25.31 | 33.49 | 173.40 | 58.03 | 0.00 | 0.00 | 0.00 |
November | 50.71 | 25.56 | 25.15 | 111.65 | 124.18 | 0.00 | 0.00 | 0.00 |
December | 48.84 | 26.07 | 22.77 | 97.26 | 156.75 | 2.33 | 0.00 | 0.00 |
Annual Sum or Average | 59.47 | 24.51 | 34.96 | 160.56 | 83.21 | 13.50 | 0.00 | 0.00 |
Minimum of Months | 48.84 | 17.23 | 22.77 | 95.83 | 16.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 72.95 | 33.32 | 44.72 | 232.21 | 174.63 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.99 | 28.67 | 24.32 | 95.83 | 174.63 | 7.33 | 0.00 | 0.00 |
February | 59.89 | 30.29 | 29.60 | 115.23 | 149.10 | 2.17 | 0.00 | 0.00 |
March | 58.96 | 26.02 | 32.95 | 120.90 | 133.60 | 1.67 | 0.00 | 0.00 |
April | 72.95 | 33.32 | 39.63 | 179.19 | 86.43 | 0.00 | 0.00 | 0.00 |
May | 61.05 | 19.86 | 41.18 | 201.39 | 25.91 | 0.00 | 0.00 | 0.00 |
June | 67.84 | 23.82 | 44.03 | 232.21 | 22.39 | 0.00 | 0.00 | 0.00 |
July | 61.94 | 17.23 | 44.72 | 206.50 | 16.04 | 0.00 | 0.00 | 0.00 |
August | 62.49 | 19.02 | 43.47 | 212.23 | 22.42 | 0.00 | 0.00 | 0.00 |
September | 57.55 | 19.69 | 37.86 | 178.48 | 33.30 | 0.00 | 0.00 | 0.00 |
October | 58.80 | 25.31 | 33.49 | 173.40 | 58.03 | 0.00 | 0.00 | 0.00 |
November | 50.71 | 25.56 | 25.15 | 111.65 | 124.18 | 0.00 | 0.00 | 0.00 |
December | 48.84 | 26.07 | 22.77 | 97.26 | 156.75 | 2.33 | 0.00 | 0.00 |
Annual Sum or Average | 59.47 | 24.51 | 34.96 | 160.56 | 83.21 | 13.50 | 0.00 | 0.00 |
Minimum of Months | 48.84 | 17.23 | 22.77 | 95.83 | 16.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 72.95 | 33.32 | 44.72 | 232.21 | 174.63 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.28 | 0.00 | 11.28 | 9.06 | 113.58 | 7.67 | 0.00 | 0.00 |
February | 13.31 | 0.00 | 13.31 | 13.18 | 95.13 | 2.17 | 0.00 | 0.00 |
March | 15.45 | 0.00 | 15.45 | 20.07 | 83.53 | 1.67 | 0.00 | 0.00 |
April | 18.34 | 0.18 | 18.17 | 35.01 | 52.39 | 0.00 | 0.00 | 0.00 |
May | 20.99 | 1.09 | 19.90 | 71.24 | 14.32 | 0.00 | 0.00 | 0.00 |
June | 23.96 | 2.11 | 21.85 | 87.18 | 12.41 | 0.00 | 0.00 | 0.00 |
July | 23.08 | 1.16 | 21.92 | 81.51 | 9.03 | 0.00 | 0.00 | 0.00 |
August | 20.58 | 0.31 | 20.27 | 74.05 | 12.53 | 0.00 | 0.00 | 0.00 |
September | 17.63 | 0.01 | 17.63 | 54.66 | 19.50 | 0.00 | 0.00 | 0.00 |
October | 15.31 | 0.00 | 15.31 | 42.06 | 35.87 | 0.00 | 0.00 | 0.00 |
November | 11.63 | 0.00 | 11.63 | 14.77 | 78.34 | 0.00 | 0.00 | 0.00 |
December | 10.49 | 0.00 | 10.49 | 10.12 | 101.15 | 2.33 | 0.00 | 0.00 |
Annual Sum or Average | 16.86 | 0.41 | 16.45 | 42.93 | 52.09 | 13.83 | 0.00 | 0.00 |
Minimum of Months | 10.49 | 0.00 | 10.49 | 9.06 | 9.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.96 | 2.11 | 21.92 | 87.18 | 113.58 | 7.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.28 | 0.00 | 11.28 | 9.06 | 113.58 | 7.67 | 0.00 | 0.00 |
February | 13.31 | 0.00 | 13.31 | 13.18 | 95.13 | 2.17 | 0.00 | 0.00 |
March | 15.45 | 0.00 | 15.45 | 20.07 | 83.53 | 1.67 | 0.00 | 0.00 |
April | 18.34 | 0.18 | 18.17 | 35.01 | 52.39 | 0.00 | 0.00 | 0.00 |
May | 20.99 | 1.09 | 19.90 | 71.24 | 14.32 | 0.00 | 0.00 | 0.00 |
June | 23.96 | 2.11 | 21.85 | 87.18 | 12.41 | 0.00 | 0.00 | 0.00 |
July | 23.08 | 1.16 | 21.92 | 81.51 | 9.02 | 0.00 | 0.00 | 0.00 |
August | 20.58 | 0.31 | 20.27 | 74.05 | 12.52 | 0.00 | 0.00 | 0.00 |
September | 17.63 | 0.01 | 17.63 | 54.66 | 19.50 | 0.00 | 0.00 | 0.00 |
October | 15.31 | 0.00 | 15.31 | 42.06 | 35.87 | 0.00 | 0.00 | 0.00 |
November | 11.63 | 0.00 | 11.63 | 14.77 | 78.34 | 0.00 | 0.00 | 0.00 |
December | 10.49 | 0.00 | 10.49 | 10.12 | 101.15 | 2.33 | 0.00 | 0.00 |
Annual Sum or Average | 16.86 | 0.41 | 16.45 | 42.93 | 52.09 | 13.83 | 0.00 | 0.00 |
Minimum of Months | 10.49 | 0.00 | 10.49 | 9.06 | 9.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.96 | 2.11 | 21.92 | 87.18 | 113.58 | 7.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 94.08 | 68.93 | 61.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 118.95 | 64.03 | 119.17 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 131.37 | 61.46 | 20.17 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 170.30 | 57.32 | 2.17 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 171.26 | 35.98 | 1.83 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 192.57 | 35.13 | 2.67 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 176.63 | 31.09 | 9.50 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 166.26 | 34.60 | 16.00 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 138.78 | 40.48 | 3.50 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 132.17 | 47.84 | 24.50 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 99.45 | 66.02 | 42.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 84.36 | 66.92 | 42.67 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 139.73 | 50.72 | 345.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 84.36 | 31.09 | 1.83 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 192.57 | 68.93 | 119.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 94.08 | 68.93 | 61.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 118.95 | 64.03 | 119.17 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 131.37 | 61.46 | 20.17 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 170.30 | 57.32 | 2.17 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 171.26 | 35.98 | 1.83 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 192.57 | 35.13 | 2.67 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 176.63 | 31.09 | 9.50 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 166.26 | 34.60 | 16.00 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 138.78 | 40.48 | 3.50 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 132.17 | 47.84 | 24.50 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 99.45 | 66.02 | 42.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 84.36 | 66.92 | 42.67 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 139.73 | 50.72 | 345.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 84.36 | 31.09 | 1.83 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 192.57 | 68.93 | 119.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 94.08 | 68.93 | 61.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 118.95 | 64.03 | 119.17 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 131.37 | 61.46 | 20.17 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 170.30 | 57.32 | 2.17 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 171.26 | 35.98 | 1.83 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 192.57 | 35.13 | 2.67 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 176.63 | 31.09 | 9.50 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 166.26 | 34.60 | 16.00 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 138.78 | 40.48 | 3.50 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 132.17 | 47.84 | 24.50 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 99.45 | 66.02 | 42.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 84.36 | 66.92 | 42.67 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 139.73 | 50.72 | 345.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 84.36 | 31.09 | 1.83 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 192.57 | 68.93 | 119.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 94.08 | 68.93 | 61.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 118.95 | 64.03 | 119.17 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 131.37 | 61.46 | 20.17 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 170.30 | 57.32 | 2.17 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 171.26 | 35.98 | 1.83 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 192.57 | 35.13 | 2.67 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 176.63 | 31.09 | 9.50 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 166.26 | 34.60 | 16.00 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 138.78 | 40.48 | 3.50 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 132.17 | 47.84 | 24.50 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 99.45 | 66.02 | 42.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 84.36 | 66.92 | 42.67 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 139.73 | 50.72 | 345.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 84.36 | 31.09 | 1.83 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 192.57 | 68.93 | 119.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 94.08 | 68.93 | 61.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 118.95 | 64.03 | 119.17 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 131.37 | 61.46 | 20.17 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 170.30 | 57.32 | 2.17 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 171.26 | 35.98 | 1.83 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 192.57 | 35.13 | 2.67 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 176.63 | 31.09 | 9.50 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 166.26 | 34.60 | 16.00 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 138.78 | 40.48 | 3.50 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 132.17 | 47.84 | 24.50 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 99.45 | 66.02 | 42.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 84.36 | 66.92 | 42.67 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 139.73 | 50.72 | 345.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 84.36 | 31.09 | 1.83 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 192.57 | 68.93 | 119.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 94.08 | 68.93 | 61.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 118.95 | 64.03 | 119.17 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 131.37 | 61.46 | 20.17 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 170.30 | 57.32 | 2.17 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 171.26 | 35.98 | 1.83 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 192.57 | 35.13 | 2.67 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 176.63 | 31.09 | 9.50 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 166.26 | 34.60 | 16.00 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 138.78 | 40.48 | 3.50 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 132.17 | 47.84 | 24.50 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 99.45 | 66.02 | 42.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 84.36 | 66.92 | 42.67 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 139.73 | 50.72 | 345.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 84.36 | 31.09 | 1.83 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 192.57 | 68.93 | 119.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 94.08 | 68.93 | 61.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 118.95 | 64.03 | 119.17 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 131.37 | 61.46 | 20.17 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 170.30 | 57.32 | 2.17 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 171.26 | 35.98 | 1.83 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 192.57 | 35.13 | 2.67 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 176.63 | 31.09 | 9.50 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 166.26 | 34.60 | 16.00 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 138.78 | 40.48 | 3.50 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 132.17 | 47.84 | 24.50 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 99.45 | 66.02 | 42.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 84.36 | 66.92 | 42.67 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 139.73 | 50.72 | 345.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 84.36 | 31.09 | 1.83 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 192.57 | 68.93 | 119.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 94.08 | 68.93 | 61.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 118.95 | 64.03 | 119.17 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 131.37 | 61.46 | 20.17 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 170.30 | 57.32 | 2.17 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 171.26 | 35.98 | 1.83 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 192.57 | 35.13 | 2.67 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 176.63 | 31.09 | 9.50 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 166.26 | 34.60 | 16.00 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 138.78 | 40.48 | 3.50 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 132.17 | 47.84 | 24.50 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 99.45 | 66.02 | 42.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 84.36 | 66.92 | 42.67 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 139.73 | 50.72 | 345.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 84.36 | 31.09 | 1.83 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 192.57 | 68.93 | 119.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 94.08 | 68.93 | 61.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 118.95 | 64.03 | 119.17 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 131.37 | 61.46 | 20.17 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 170.30 | 57.32 | 2.17 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 171.26 | 35.98 | 1.83 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 192.57 | 35.13 | 2.67 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 176.63 | 31.09 | 9.50 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 166.26 | 34.60 | 16.00 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 138.78 | 40.48 | 3.50 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 132.17 | 47.84 | 24.50 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 99.45 | 66.02 | 42.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 84.36 | 66.92 | 42.67 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 139.73 | 50.72 | 345.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 84.36 | 31.09 | 1.83 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 192.57 | 68.93 | 119.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 94.08 | 68.93 | 61.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 118.95 | 64.03 | 119.17 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 131.37 | 61.46 | 20.17 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 170.30 | 57.32 | 2.17 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 171.26 | 35.98 | 1.83 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 192.57 | 35.13 | 2.67 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 176.63 | 31.09 | 9.50 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 166.26 | 34.60 | 16.00 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 138.78 | 40.48 | 3.50 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 132.17 | 47.84 | 24.50 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 99.45 | 66.02 | 42.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 84.36 | 66.92 | 42.67 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 139.73 | 50.72 | 345.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 84.36 | 31.09 | 1.83 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 192.57 | 68.93 | 119.17 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141925E+09 | 76782296.77 | 65142570.06 | 0.256680E+09 | 0.467741E+09 |
February | 0.144875E+09 | 73271995.98 | 71603334.29 | 0.278764E+09 | 0.360705E+09 |
March | 0.157929E+09 | 69686012.31 | 88242659.04 | 0.323821E+09 | 0.357846E+09 |
April | 0.189080E+09 | 86355329.22 | 0.102725E+09 | 0.464471E+09 | 0.224026E+09 |
May | 0.163508E+09 | 53198932.77 | 0.110309E+09 | 0.539408E+09 | 69385575.59 |
June | 0.175849E+09 | 61735316.84 | 0.114113E+09 | 0.601876E+09 | 58044504.17 |
July | 0.165903E+09 | 46138257.83 | 0.119765E+09 | 0.553086E+09 | 42965980.27 |
August | 0.167364E+09 | 50936982.08 | 0.116427E+09 | 0.568425E+09 | 60056842.76 |
September | 0.149158E+09 | 51023788.89 | 98134406.15 | 0.462624E+09 | 86324450.77 |
October | 0.157494E+09 | 67787723.35 | 89706733.70 | 0.464446E+09 | 0.155424E+09 |
November | 0.131444E+09 | 66245015.74 | 65199244.68 | 0.289386E+09 | 0.321886E+09 |
December | 0.130825E+09 | 69827436.84 | 60997976.70 | 0.260497E+09 | 0.419844E+09 |
Annual Sum or Average | 0.187536E+10 | 0.772989E+09 | 0.110237E+10 | 0.506348E+10 | 0.262425E+10 |
Minimum of Months | 0.130825E+09 | 46138257.83 | 60997976.70 | 0.256680E+09 | 42965980.27 |
Maximum of Months | 0.189080E+09 | 86355329.22 | 0.119765E+09 | 0.601876E+09 | 0.467741E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141925E+09 | 76782296.77 | 65142570.06 | 0.256680E+09 | 0.467741E+09 |
February | 0.144875E+09 | 73271995.98 | 71603334.29 | 0.278764E+09 | 0.360705E+09 |
March | 0.157929E+09 | 69686012.31 | 88242659.04 | 0.323821E+09 | 0.357846E+09 |
April | 0.189080E+09 | 86355329.22 | 0.102725E+09 | 0.464471E+09 | 0.224026E+09 |
May | 0.163508E+09 | 53198932.77 | 0.110309E+09 | 0.539408E+09 | 69385575.59 |
June | 0.175849E+09 | 61735316.84 | 0.114113E+09 | 0.601876E+09 | 58044504.17 |
July | 0.165903E+09 | 46138257.83 | 0.119765E+09 | 0.553086E+09 | 42965980.27 |
August | 0.167364E+09 | 50936982.08 | 0.116427E+09 | 0.568425E+09 | 60056842.76 |
September | 0.149158E+09 | 51023788.89 | 98134406.15 | 0.462624E+09 | 86324450.77 |
October | 0.157494E+09 | 67787723.35 | 89706733.70 | 0.464446E+09 | 0.155424E+09 |
November | 0.131444E+09 | 66245015.74 | 65199244.68 | 0.289386E+09 | 0.321886E+09 |
December | 0.130825E+09 | 69827436.84 | 60997976.70 | 0.260497E+09 | 0.419844E+09 |
Annual Sum or Average | 0.187536E+10 | 0.772989E+09 | 0.110237E+10 | 0.506348E+10 | 0.262425E+10 |
Minimum of Months | 0.130825E+09 | 46138257.83 | 60997976.70 | 0.256680E+09 | 42965980.27 |
Maximum of Months | 0.189080E+09 | 86355329.22 | 0.119765E+09 | 0.601876E+09 | 0.467741E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 30222704.80 | 0.00 | 30222704.80 | 24259758.44 | 0.304214E+09 |
February | 32204961.39 | 0.00 | 32204961.39 | 31882836.78 | 0.230143E+09 |
March | 41374055.42 | 3955.36 | 41370100.06 | 53754187.94 | 0.223733E+09 |
April | 47542100.41 | 453814.25 | 47088286.17 | 90739420.03 | 0.135807E+09 |
May | 56216753.53 | 2906737.13 | 53310016.40 | 0.190818E+09 | 38367905.97 |
June | 62111800.69 | 5475446.21 | 56636354.48 | 0.225963E+09 | 32177918.35 |
July | 61827849.62 | 3115505.39 | 58712344.23 | 0.218324E+09 | 24173232.89 |
August | 55110794.51 | 829631.01 | 54281163.51 | 0.198329E+09 | 33547389.93 |
September | 45709839.97 | 16883.74 | 45692956.23 | 0.141688E+09 | 50542932.97 |
October | 41018973.49 | 0.00 | 41018973.49 | 0.112653E+09 | 96066846.86 |
November | 30135455.94 | 0.00 | 30135455.94 | 38279154.56 | 0.203056E+09 |
December | 28095440.27 | 0.00 | 28095440.27 | 27101335.48 | 0.270922E+09 |
Annual Sum or Average | 0.531571E+09 | 12801973.09 | 0.518769E+09 | 0.135379E+10 | 0.164275E+10 |
Minimum of Months | 28095440.27 | 0.00 | 28095440.27 | 24259758.44 | 24173232.89 |
Maximum of Months | 62111800.69 | 5475446.21 | 58712344.23 | 0.225963E+09 | 0.304214E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 30221872.17 | 0.00 | 30221872.17 | 24258866.56 | 0.304213E+09 |
February | 32204104.81 | 0.00 | 32204104.81 | 31881956.31 | 0.230142E+09 |
March | 41372884.33 | 3955.17 | 41368929.15 | 53752606.68 | 0.223733E+09 |
April | 47540809.45 | 453792.97 | 47087016.47 | 90737289.43 | 0.135806E+09 |
May | 56215044.66 | 2906600.89 | 53308443.76 | 0.190814E+09 | 38367016.12 |
June | 62109876.54 | 5475189.57 | 56634686.97 | 0.225958E+09 | 32177046.71 |
July | 61825906.95 | 3115359.36 | 58710547.59 | 0.218319E+09 | 24172422.86 |
August | 55109108.93 | 829592.12 | 54279516.81 | 0.198325E+09 | 33546558.29 |
September | 45708446.13 | 16882.95 | 45691563.18 | 0.141684E+09 | 50541988.36 |
October | 41017790.74 | 0.00 | 41017790.74 | 0.112651E+09 | 96065891.33 |
November | 30134640.18 | 0.00 | 30134640.18 | 38278162.11 | 0.203055E+09 |
December | 28094659.49 | 0.00 | 28094659.49 | 27100594.72 | 0.270921E+09 |
Annual Sum or Average | 0.531555E+09 | 12801373.04 | 0.518754E+09 | 0.135376E+10 | 0.164274E+10 |
Minimum of Months | 28094659.49 | 0.00 | 28094659.49 | 24258866.56 | 24172422.86 |
Maximum of Months | 62109876.54 | 5475189.57 | 58710547.59 | 0.225958E+09 | 0.304213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.251973E+09 | 0.184631E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.287765E+09 | 0.154902E+09 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.351852E+09 | 0.164609E+09 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.441405E+09 | 0.148571E+09 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.458690E+09 | 96375190.93 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.499137E+09 | 91065309.73 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.473095E+09 | 83274459.72 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.445321E+09 | 92662813.54 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.359715E+09 | 0.104918E+09 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.353994E+09 | 0.128141E+09 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.257780E+09 | 0.171112E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.225942E+09 | 0.179246E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.440667E+10 | 0.159951E+10 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.225942E+09 | 83274459.72 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.499137E+09 | 0.184631E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.251973E+09 | 0.184631E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.287765E+09 | 0.154902E+09 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.351852E+09 | 0.164609E+09 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.441405E+09 | 0.148571E+09 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.458690E+09 | 96375190.93 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.499137E+09 | 91065309.73 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.473095E+09 | 83274459.72 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.445321E+09 | 92662813.54 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.359715E+09 | 0.104918E+09 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.353994E+09 | 0.128141E+09 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.257780E+09 | 0.171112E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.225942E+09 | 0.179246E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.440667E+10 | 0.159951E+10 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.225942E+09 | 83274459.72 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.499137E+09 | 0.184631E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.251973E+09 | 0.184631E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.287765E+09 | 0.154902E+09 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.351852E+09 | 0.164609E+09 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.441405E+09 | 0.148571E+09 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.458690E+09 | 96375190.93 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.499137E+09 | 91065309.73 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.473095E+09 | 83274459.72 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.445321E+09 | 92662813.54 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.359715E+09 | 0.104918E+09 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.353994E+09 | 0.128141E+09 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.257780E+09 | 0.171112E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.225942E+09 | 0.179246E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.440667E+10 | 0.159951E+10 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.225942E+09 | 83274459.72 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.499137E+09 | 0.184631E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.251973E+09 | 0.184631E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.287765E+09 | 0.154902E+09 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.351852E+09 | 0.164609E+09 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.441405E+09 | 0.148571E+09 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.458690E+09 | 96375190.93 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.499137E+09 | 91065309.73 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.473095E+09 | 83274459.72 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.445321E+09 | 92662813.54 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.359715E+09 | 0.104918E+09 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.353994E+09 | 0.128141E+09 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.257780E+09 | 0.171112E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.225942E+09 | 0.179246E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.440667E+10 | 0.159951E+10 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.225942E+09 | 83274459.72 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.499137E+09 | 0.184631E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.251973E+09 | 0.184631E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.287765E+09 | 0.154902E+09 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.351852E+09 | 0.164609E+09 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.441405E+09 | 0.148571E+09 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.458690E+09 | 96375190.93 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.499137E+09 | 91065309.73 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.473095E+09 | 83274459.72 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.445321E+09 | 92662813.54 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.359715E+09 | 0.104918E+09 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.353994E+09 | 0.128141E+09 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.257780E+09 | 0.171112E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.225942E+09 | 0.179246E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.440667E+10 | 0.159951E+10 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.225942E+09 | 83274459.72 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.499137E+09 | 0.184631E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.251973E+09 | 0.184631E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.287765E+09 | 0.154902E+09 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.351852E+09 | 0.164609E+09 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.441405E+09 | 0.148571E+09 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.458690E+09 | 96375190.93 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.499137E+09 | 91065309.73 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.473095E+09 | 83274459.72 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.445321E+09 | 92662813.54 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.359715E+09 | 0.104918E+09 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.353994E+09 | 0.128141E+09 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.257780E+09 | 0.171112E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.225942E+09 | 0.179246E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.440667E+10 | 0.159951E+10 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.225942E+09 | 83274459.72 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.499137E+09 | 0.184631E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.251973E+09 | 0.184631E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.287765E+09 | 0.154902E+09 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.351852E+09 | 0.164609E+09 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.441405E+09 | 0.148571E+09 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.458690E+09 | 96375190.93 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.499137E+09 | 91065309.73 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.473095E+09 | 83274459.72 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.445321E+09 | 92662813.54 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.359715E+09 | 0.104918E+09 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.353994E+09 | 0.128141E+09 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.257780E+09 | 0.171112E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.225942E+09 | 0.179246E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.440667E+10 | 0.159951E+10 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.225942E+09 | 83274459.72 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.499137E+09 | 0.184631E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.251973E+09 | 0.184631E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.287765E+09 | 0.154902E+09 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.351852E+09 | 0.164609E+09 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.441405E+09 | 0.148571E+09 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.458690E+09 | 96375190.93 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.499137E+09 | 91065309.73 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.473095E+09 | 83274459.72 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.445321E+09 | 92662813.54 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.359715E+09 | 0.104918E+09 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.353994E+09 | 0.128141E+09 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.257780E+09 | 0.171112E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.225942E+09 | 0.179246E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.440667E+10 | 0.159951E+10 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.225942E+09 | 83274459.72 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.499137E+09 | 0.184631E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.251973E+09 | 0.184631E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.287765E+09 | 0.154902E+09 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.351852E+09 | 0.164609E+09 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.441405E+09 | 0.148571E+09 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.458690E+09 | 96375190.93 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.499137E+09 | 91065309.73 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.473095E+09 | 83274459.72 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.445321E+09 | 92662813.54 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.359715E+09 | 0.104918E+09 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.353994E+09 | 0.128141E+09 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.257780E+09 | 0.171112E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.225942E+09 | 0.179246E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.440667E+10 | 0.159951E+10 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.225942E+09 | 83274459.72 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.499137E+09 | 0.184631E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.251973E+09 | 0.184631E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.287765E+09 | 0.154902E+09 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.351852E+09 | 0.164609E+09 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.441405E+09 | 0.148571E+09 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.458690E+09 | 96375190.93 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.499137E+09 | 91065309.73 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.473095E+09 | 83274459.72 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.445321E+09 | 92662813.54 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.359715E+09 | 0.104918E+09 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.353994E+09 | 0.128141E+09 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.257780E+09 | 0.171112E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.225942E+09 | 0.179246E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.440667E+10 | 0.159951E+10 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.225942E+09 | 83274459.72 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.499137E+09 | 0.184631E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 193.56 | 560.20 | 128.54 | 57.33 | 71.21 | 0.00 | 0.00 |
February | 246.04 | 477.69 | 146.40 | 60.58 | 85.82 | 0.00 | 0.00 |
March | 275.61 | 427.95 | 148.82 | 52.04 | 96.78 | 0.00 | 0.00 |
April | 424.99 | 274.23 | 182.58 | 66.98 | 115.60 | 0.00 | 0.00 |
May | 544.51 | 79.70 | 164.07 | 41.89 | 122.18 | 0.00 | 0.00 |
June | 638.03 | 68.89 | 183.61 | 51.86 | 131.75 | 0.00 | 0.00 |
July | 575.56 | 49.68 | 170.05 | 36.78 | 133.27 | 0.00 | 0.00 |
August | 572.33 | 69.68 | 166.12 | 38.65 | 127.47 | 0.00 | 0.00 |
September | 465.92 | 105.24 | 150.36 | 39.38 | 110.98 | 0.00 | 0.00 |
October | 429.31 | 186.17 | 148.23 | 50.62 | 97.61 | 0.00 | 0.00 |
November | 245.61 | 397.83 | 124.68 | 51.11 | 73.56 | 0.00 | 0.00 |
December | 203.99 | 505.04 | 118.67 | 52.14 | 66.53 | 0.00 | 0.00 |
Annual Sum or Average | 402.10 | 265.73 | 152.65 | 49.83 | 102.81 | 0.00 | 0.00 |
Minimum of Months | 193.56 | 49.68 | 118.67 | 36.78 | 66.53 | 0.00 | 0.00 |
Maximum of Months | 638.03 | 560.20 | 183.61 | 66.98 | 133.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3339.86 | 2476.98 | 749.65 | 502.68 | 246.98 | 0.00 | 0.00 |
February | 4148.26 | 2404.23 | 945.84 | 649.00 | 296.84 | 0.00 | 0.00 |
March | 4606.41 | 2276.96 | 1038.30 | 646.65 | 391.66 | 0.00 | 0.00 |
April | 6944.50 | 2555.47 | 1317.91 | 856.37 | 461.54 | 0.00 | 0.00 |
May | 7363.55 | 2054.87 | 1263.38 | 720.93 | 542.45 | 0.00 | 0.00 |
June | 7807.61 | 2154.91 | 1394.29 | 804.30 | 589.99 | 0.00 | 0.00 |
July | 7917.52 | 1979.47 | 1298.91 | 667.58 | 631.33 | 0.00 | 0.00 |
August | 6976.44 | 2147.49 | 1213.82 | 607.97 | 605.85 | 0.00 | 0.00 |
September | 6648.25 | 2283.64 | 1035.89 | 515.83 | 520.07 | 0.00 | 0.00 |
October | 5741.18 | 2380.17 | 984.51 | 584.53 | 399.97 | 0.00 | 0.00 |
November | 3523.10 | 2489.59 | 799.89 | 546.53 | 253.36 | 0.00 | 0.00 |
December | 2930.68 | 2479.17 | 680.57 | 450.10 | 230.46 | 0.00 | 0.00 |
Annual Sum or Average | 5668.49 | 2305.41 | 1060.35 | 628.65 | 431.70 | 0.00 | 0.00 |
Minimum of Months | 2930.68 | 1979.47 | 680.57 | 450.10 | 230.46 | 0.00 | 0.00 |
Maximum of Months | 7917.52 | 2555.47 | 1394.29 | 856.37 | 631.33 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.518420E+09 | 0.150045E+10 | 0.344294E+09 | 0.153565E+09 | 0.190730E+09 | 0.00 | 0.00 |
February | 0.595230E+09 | 0.115563E+10 | 0.354160E+09 | 0.146544E+09 | 0.207616E+09 | 0.00 | 0.00 |
March | 0.738205E+09 | 0.114622E+10 | 0.398604E+09 | 0.139380E+09 | 0.259224E+09 | 0.00 | 0.00 |
April | 0.110157E+10 | 0.710812E+09 | 0.473243E+09 | 0.173618E+09 | 0.299625E+09 | 0.00 | 0.00 |
May | 0.145841E+10 | 0.213472E+09 | 0.439448E+09 | 0.112211E+09 | 0.327237E+09 | 0.00 | 0.00 |
June | 0.165378E+10 | 0.178554E+09 | 0.475919E+09 | 0.134421E+09 | 0.341497E+09 | 0.00 | 0.00 |
July | 0.154159E+10 | 0.133054E+09 | 0.455461E+09 | 98507380.42 | 0.356953E+09 | 0.00 | 0.00 |
August | 0.153293E+10 | 0.186638E+09 | 0.444948E+09 | 0.103533E+09 | 0.341415E+09 | 0.00 | 0.00 |
September | 0.120767E+10 | 0.272779E+09 | 0.389735E+09 | 0.102081E+09 | 0.287653E+09 | 0.00 | 0.00 |
October | 0.114986E+10 | 0.498646E+09 | 0.397026E+09 | 0.135575E+09 | 0.261450E+09 | 0.00 | 0.00 |
November | 0.636628E+09 | 0.103118E+10 | 0.323159E+09 | 0.132490E+09 | 0.190669E+09 | 0.00 | 0.00 |
December | 0.546367E+09 | 0.135270E+10 | 0.317841E+09 | 0.139655E+09 | 0.178186E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.126807E+11 | 0.838014E+10 | 0.481384E+10 | 0.157158E+10 | 0.324226E+10 | 0.00 | 0.00 |
Minimum of Months | 0.518420E+09 | 0.133054E+09 | 0.317841E+09 | 98507380.42 | 0.178186E+09 | 0.00 | 0.00 |
Maximum of Months | 0.165378E+10 | 0.150045E+10 | 0.475919E+09 | 0.173618E+09 | 0.356953E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.894548E+10 | 0.663434E+10 | 0.200787E+10 | 0.134637E+10 | 0.661499E+09 | 0.00 | 0.00 |
February | 0.100355E+11 | 0.581631E+10 | 0.228817E+10 | 0.157007E+10 | 0.718106E+09 | 0.00 | 0.00 |
March | 0.123378E+11 | 0.609861E+10 | 0.278099E+10 | 0.173198E+10 | 0.104902E+10 | 0.00 | 0.00 |
April | 0.180001E+11 | 0.662379E+10 | 0.341602E+10 | 0.221971E+10 | 0.119631E+10 | 0.00 | 0.00 |
May | 0.197225E+11 | 0.550375E+10 | 0.338383E+10 | 0.193093E+10 | 0.145290E+10 | 0.00 | 0.00 |
June | 0.202373E+11 | 0.558553E+10 | 0.361400E+10 | 0.208475E+10 | 0.152925E+10 | 0.00 | 0.00 |
July | 0.212063E+11 | 0.530181E+10 | 0.347901E+10 | 0.178805E+10 | 0.169096E+10 | 0.00 | 0.00 |
August | 0.186857E+11 | 0.575184E+10 | 0.325110E+10 | 0.162839E+10 | 0.162271E+10 | 0.00 | 0.00 |
September | 0.172323E+11 | 0.591920E+10 | 0.268503E+10 | 0.133702E+10 | 0.134801E+10 | 0.00 | 0.00 |
October | 0.153772E+11 | 0.637506E+10 | 0.263690E+10 | 0.156562E+10 | 0.107128E+10 | 0.00 | 0.00 |
November | 0.913187E+10 | 0.645301E+10 | 0.207331E+10 | 0.141659E+10 | 0.656714E+09 | 0.00 | 0.00 |
December | 0.784953E+10 | 0.664021E+10 | 0.182283E+10 | 0.120556E+10 | 0.617275E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.178762E+12 | 0.727034E+11 | 0.334391E+11 | 0.198250E+11 | 0.136140E+11 | 0.00 | 0.00 |
Minimum of Months | 0.784953E+10 | 0.530181E+10 | 0.182283E+10 | 0.120556E+10 | 0.617275E+09 | 0.00 | 0.00 |
Maximum of Months | 0.212063E+11 | 0.664021E+10 | 0.361400E+10 | 0.221971E+10 | 0.169096E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.02 | 8.64 | 3.24 | 3.13 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.58 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.54 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.82 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.37 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.90 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.02 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.47 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.88 | 10.53 | 3.17 | 6.01 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.02 | 8.64 | 2.44 | 3.13 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.67 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.78 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.88 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.06 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.76 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.95 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.96 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.74 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.65 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.05 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.84 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.67 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.65 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.4 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -2.1 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.95 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.58 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 18.00 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.56 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.12 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.9 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.4 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.11 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.49 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.77 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.55 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.84 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.17 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.79 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.49 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.11 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.55 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.09 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.79 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.827572E+09 | -688239862.1 | 0.00 | 0.00 | 744.00 | 0.00 | -139332481.2 | 59.00 | 0.00 | 0.00 |
February | 0.751894E+09 | -627170698.1 | 0.00 | 0.00 | 672.00 | 0.00 | -124723735.9 | 59.00 | 0.00 | 0.00 |
March | 0.841129E+09 | -704946395.8 | 0.00 | 0.00 | 744.00 | 0.00 | -136182704.5 | 58.99 | 0.00 | 0.00 |
April | 0.743053E+09 | -614746862.6 | 0.00 | 0.00 | 720.00 | 0.00 | -128305965.0 | 58.99 | 0.00 | 0.00 |
May | 0.725457E+09 | -594417402.6 | 0.00 | 0.00 | 744.00 | 0.00 | -131039267.7 | 58.99 | 0.00 | 0.00 |
June | 0.682531E+09 | -555359375.8 | 0.00 | 0.00 | 720.00 | 0.00 | -127171417.7 | 58.99 | 0.00 | 0.00 |
July | 0.649669E+09 | -519496199.2 | 0.00 | 0.00 | 744.00 | 0.00 | -130173071.5 | 58.99 | 0.00 | 0.00 |
August | 0.695428E+09 | -564070062.6 | 0.00 | 0.00 | 744.00 | 0.00 | -131357982.4 | 58.99 | 0.00 | 0.00 |
September | 0.678021E+09 | -551593463.8 | 0.00 | 0.00 | 720.00 | 0.00 | -126427074.9 | 58.99 | 0.00 | 0.00 |
October | 0.724494E+09 | -593431501.1 | 0.00 | 0.00 | 744.00 | 0.00 | -131062216.0 | 58.99 | 0.00 | 0.00 |
November | 0.740430E+09 | -611316242.6 | 0.00 | 0.00 | 720.00 | 0.00 | -129114234.5 | 58.99 | 0.00 | 0.00 |
December | 0.808154E+09 | -671008508.5 | 0.00 | 0.00 | 744.00 | 0.00 | -137145241.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.886783E+10 | -0.729580E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.157204E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.649669E+09 | -704946395.8 | 0.00 | 0.00 | 672.00 | 0.00 | -139332481.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.841129E+09 | -519496199.2 | 0.00 | 0.00 | 744.00 | 0.00 | -124723735.9 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 307.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 295.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 296.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 353.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 390.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 380.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 342.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 330.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 308.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4027.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.623751E+09 | 32510.37 | 05-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.320316E+09 | 32510.37 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.265583E+09 | 32510.37 | 10-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1162353.05 | 1596.20 | 11-APR-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 30799691.56 | 4141.75 | 15-NOV-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.374285E+09 | 32510.37 | 20-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.623751E+09 | 32510.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16938001.02 | 18079.05 | 05-FEB-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 16938001.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16938001.02 | 18079.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.322289E+10 | 0.249520E+10 | 30539.52 | 02-JAN-00:02 | 21653.50 | 0.00 |
February | 0.00 | 0.00 | 0.469743E+10 | 0.356612E+10 | 30277.58 | 27-FEB-00:01 | 22393.26 | 0.00 |
March | 0.00 | 0.00 | 0.643180E+10 | 0.497476E+10 | 31432.35 | 26-MAR-23:01 | 21525.56 | 0.00 |
April | 0.00 | 0.00 | 0.111882E+11 | 0.868787E+10 | 32834.60 | 23-APR-23:01 | 20430.85 | 0.00 |
May | 0.00 | 0.00 | 0.197816E+11 | 0.140529E+11 | 34410.43 | 21-MAY-23:01 | 18256.49 | 0.00 |
June | 0.00 | 0.00 | 0.209801E+11 | 0.150054E+11 | 34311.43 | 04-JUN-23:01 | 19016.70 | 0.00 |
July | 0.00 | 0.00 | 0.217885E+11 | 0.148286E+11 | 34796.06 | 30-JUL-23:02 | 16991.57 | 0.00 |
August | 0.00 | 0.00 | 0.233489E+11 | 0.159487E+11 | 34646.09 | 06-AUG-23:01 | 19344.02 | 0.00 |
September | 0.00 | 0.00 | 0.197392E+11 | 0.133199E+11 | 35231.36 | 04-SEP-23:02 | 16015.01 | 0.00 |
October | 0.00 | 0.00 | 0.167497E+11 | 0.119592E+11 | 34671.08 | 22-OCT-23:01 | 18166.42 | 0.00 |
November | 0.00 | 0.00 | 0.832650E+10 | 0.641368E+10 | 31167.71 | 05-NOV-23:01 | 23293.42 | 0.00 |
December | 0.00 | 0.00 | 0.553338E+10 | 0.417125E+10 | 31503.32 | 11-DEC-00:01 | 21154.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.161788E+12 | 0.115424E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.322289E+10 | 0.249520E+10 | 30277.58 | 16015.01 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.233489E+11 | 0.159487E+11 | 35231.36 | 23293.42 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.443536E+10 | 0.324666E+10 | 66370.99 | 01-JAN-14:23 | 56089.82 | 0.00 |
February | 0.00 | 0.00 | 0.915910E+10 | 0.686986E+10 | 68580.03 | 26-FEB-14:43 | 56095.78 | 0.00 |
March | 0.00 | 0.00 | 0.137234E+11 | 0.105601E+11 | 84275.78 | 26-MAR-14:13 | 70133.04 | 0.00 |
April | 0.00 | 0.00 | 0.288150E+11 | 0.226339E+11 | 109731.48 | 28-APR-17:42 | 78509.45 | 0.00 |
May | 0.00 | 0.00 | 0.573200E+11 | 0.417880E+11 | 113553.86 | 28-MAY-09:23 | 66988.49 | 0.00 |
June | 0.00 | 0.00 | 0.624011E+11 | 0.464431E+11 | 107651.39 | 20-JUN-17:08 | 72857.89 | 0.00 |
July | 0.00 | 0.00 | 0.675188E+11 | 0.473255E+11 | 114515.63 | 02-JUL-09:43 | 66476.39 | 0.00 |
August | 0.00 | 0.00 | 0.677104E+11 | 0.476674E+11 | 113710.87 | 06-AUG-09:13 | 66937.81 | 0.00 |
September | 0.00 | 0.00 | 0.560167E+11 | 0.385612E+11 | 123578.33 | 04-SEP-23:01 | 55162.14 | 0.00 |
October | 0.00 | 0.00 | 0.464298E+11 | 0.333629E+11 | 117950.66 | 08-OCT-09:23 | 63005.18 | 0.00 |
November | 0.00 | 0.00 | 0.182809E+11 | 0.141378E+11 | 90303.95 | 11-NOV-13:23 | 60113.91 | 0.00 |
December | 0.00 | 0.00 | 0.107218E+11 | 0.804288E+10 | 69993.43 | 10-DEC-15:03 | 55951.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.442532E+12 | 0.320639E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.443536E+10 | 0.324666E+10 | 66370.99 | 55162.14 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.677104E+11 | 0.476674E+11 | 123578.33 | 78509.45 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.150170E+10 | 0.38 | 1495.87 | 04-JAN-15:20 | 0.94 |
February | 0.139396E+10 | 0.40 | 1495.87 | 07-FEB-08:30 | 0.93 |
March | 0.164767E+10 | 0.44 | 1495.87 | 01-MAR-13:40 | 0.93 |
April | 0.161241E+10 | 0.55 | 1495.87 | 03-APR-13:23 | 0.93 |
May | 0.183541E+10 | 0.70 | 1495.87 | 01-MAY-06:20 | 0.92 |
June | 0.185716E+10 | 0.72 | 1495.87 | 30-JUN-06:15 | 0.92 |
July | 0.182088E+10 | 0.68 | 1495.87 | 01-JUL-06:23 | 0.92 |
August | 0.196218E+10 | 0.73 | 1495.87 | 18-AUG-06:40 | 0.92 |
September | 0.178230E+10 | 0.70 | 1495.87 | 01-SEP-06:05 | 0.93 |
October | 0.172377E+10 | 0.63 | 1495.87 | 02-OCT-06:40 | 0.93 |
November | 0.149612E+10 | 0.46 | 1495.87 | 08-NOV-08:40 | 0.92 |
December | 0.152608E+10 | 0.41 | 1495.87 | 19-DEC-15:00 | 0.93 |
Annual Sum or Average | 0.201596E+11 | 0.57 | |||
Minimum of Months | 0.139396E+10 | 0.38 | 1495.87 | 0.92 | |
Maximum of Months | 0.196218E+10 | 0.73 | 1495.87 | 0.94 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.723052E+10 | 0.58 | 7289.23 | 02-JAN-10:30 | 1.55 |
February | 0.665892E+10 | 0.60 | 7289.23 | 01-FEB-10:40 | 1.54 |
March | 0.783120E+10 | 0.64 | 7289.23 | 01-MAR-11:10 | 1.55 |
April | 0.740394E+10 | 0.70 | 7289.23 | 17-APR-08:20 | 1.56 |
May | 0.840710E+10 | 1.04 | 7289.23 | 01-MAY-06:40 | 1.54 |
June | 0.855026E+10 | 1.15 | 7289.23 | 01-JUN-06:10 | 1.54 |
July | 0.862059E+10 | 1.21 | 7289.23 | 01-JUL-06:20 | 1.54 |
August | 0.896602E+10 | 1.16 | 7289.23 | 01-AUG-07:50 | 1.54 |
September | 0.814800E+10 | 1.02 | 7289.23 | 01-SEP-06:30 | 1.55 |
October | 0.788646E+10 | 0.88 | 7289.23 | 02-OCT-07:40 | 1.55 |
November | 0.699313E+10 | 0.61 | 7289.23 | 13-NOV-11:20 | 1.56 |
December | 0.723528E+10 | 0.59 | 7289.23 | 01-DEC-09:30 | 1.56 |
Annual Sum or Average | 0.939314E+11 | 0.85 | |||
Minimum of Months | 0.665892E+10 | 0.58 | 7289.23 | 1.54 | |
Maximum of Months | 0.896602E+10 | 1.21 | 7289.23 | 1.56 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.235731E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.263802E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.335304E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.461186E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.721924E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.762430E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.775701E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.829227E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.702671E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.621217E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.370771E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.299401E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.637937E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.235731E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.829227E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.850626E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.928899E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.117918E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.158088E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.254240E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.272479E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.286537E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.289784E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.244148E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.214263E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.122856E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.103341E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.224161E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.850626E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.289784E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.150170E+10 | 0.322289E+10 | 0.623751E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139396E+10 | 0.469743E+10 | 0.320316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164767E+10 | 0.643180E+10 | 0.265583E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161241E+10 | 0.111882E+11 | 1162353.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.183541E+10 | 0.197816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.185716E+10 | 0.209801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.182088E+10 | 0.217885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196218E+10 | 0.233489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.178230E+10 | 0.197392E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.172377E+10 | 0.167497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149612E+10 | 0.832650E+10 | 30799691.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152608E+10 | 0.553338E+10 | 0.374285E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201596E+11 | 0.161788E+12 | 0.161590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139396E+10 | 0.322289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196218E+10 | 0.233489E+11 | 0.623751E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.723052E+10 | 0.443536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.665892E+10 | 0.915910E+10 | 16938001.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.783120E+10 | 0.137234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.740394E+10 | 0.288150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.840710E+10 | 0.573200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.855026E+10 | 0.624011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.862059E+10 | 0.675188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.896602E+10 | 0.677104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.814800E+10 | 0.560167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.788646E+10 | 0.464298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.699313E+10 | 0.182809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.723528E+10 | 0.107218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.939314E+11 | 0.442532E+12 | 16938001.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.665892E+10 | 0.443536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.896602E+10 | 0.677104E+11 | 16938001.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.150170E+10 | 0.00 | 0.00 | 0.00 | 0.855609E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139396E+10 | 0.00 | 0.00 | 0.00 | 0.124407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164767E+10 | 0.00 | 0.00 | 0.00 | 0.170537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161241E+10 | 0.00 | 0.00 | 0.00 | 0.299946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.183541E+10 | 0.00 | 0.00 | 0.00 | 0.538383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.185716E+10 | 0.00 | 0.00 | 0.00 | 0.576714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.182088E+10 | 0.00 | 0.00 | 0.00 | 0.593613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196218E+10 | 0.00 | 0.00 | 0.00 | 0.633009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.178230E+10 | 0.00 | 0.00 | 0.00 | 0.524441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.172377E+10 | 0.00 | 0.00 | 0.00 | 0.448840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149612E+10 | 0.00 | 0.00 | 0.00 | 0.221159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152608E+10 | 0.00 | 0.00 | 0.00 | 0.146793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201596E+11 | 0.00 | 0.00 | 0.00 | 0.436340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139396E+10 | 0.00 | 0.00 | 0.00 | 0.855609E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196218E+10 | 0.00 | 0.00 | 0.00 | 0.633009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.723052E+10 | 0.00 | 0.00 | 0.00 | 0.127573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.665892E+10 | 0.00 | 0.00 | 0.00 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.783120E+10 | 0.00 | 0.00 | 0.00 | 0.396059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.740394E+10 | 0.00 | 0.00 | 0.00 | 0.840482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.840710E+10 | 0.00 | 0.00 | 0.00 | 0.170169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.855026E+10 | 0.00 | 0.00 | 0.00 | 0.186976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.862059E+10 | 0.00 | 0.00 | 0.00 | 0.200331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.896602E+10 | 0.00 | 0.00 | 0.00 | 0.200124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.814800E+10 | 0.00 | 0.00 | 0.00 | 0.162668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.788646E+10 | 0.00 | 0.00 | 0.00 | 0.135399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.699313E+10 | 0.00 | 0.00 | 0.00 | 0.529245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.723528E+10 | 0.00 | 0.00 | 0.00 | 0.309883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.939314E+11 | 0.00 | 0.00 | 0.00 | 0.130229E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.665892E+10 | 0.00 | 0.00 | 0.00 | 0.127573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.896602E+10 | 0.00 | 0.00 | 0.00 | 0.200331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.528640E+09 | 0.168163E+09 | 0.00 | 2014848.49 | 0.00 | 0.222273E+09 | 0.552614E+09 | 0.00 | 0.16 |
February | 0.292917E+09 | 0.285617E+09 | 0.00 | 1933667.51 | 460175.69 | 0.122131E+09 | 0.368255E+09 | 0.00 | 0.17 |
March | 0.326895E+09 | 0.445800E+09 | 0.00 | 2999857.69 | 309430.80 | 0.103375E+09 | 0.434319E+09 | 0.00 | 0.18 |
April | 43651578.42 | 0.961861E+09 | 0.00 | 3042128.47 | 492693.35 | 2109464.39 | 0.143556E+09 | 0.00 | 0.18 |
May | 0.00 | 0.294914E+10 | 0.00 | 110853.45 | 0.00 | 0.00 | 74715.09 | 0.00 | 0.20 |
June | 0.00 | 0.346366E+10 | 0.00 | 45018.69 | 0.00 | 0.00 | 33998.11 | 0.00 | 0.21 |
July | 0.00 | 0.393394E+10 | 0.00 | 56101.17 | 0.00 | 0.00 | 34802.68 | 0.00 | 0.20 |
August | 0.00 | 0.383614E+10 | 0.00 | 46318.49 | 0.00 | 0.00 | 171518.16 | 0.00 | 0.21 |
September | 0.00 | 0.304301E+10 | 0.00 | 204211.72 | 0.00 | 0.00 | 6019.25 | 0.00 | 0.20 |
October | 29750970.69 | 0.226039E+10 | 0.00 | 3021946.55 | 0.00 | 0.00 | 0.143416E+09 | 0.00 | 0.19 |
November | 90341623.91 | 0.710082E+09 | 0.00 | 3416694.17 | 582659.15 | 28521203.10 | 0.317800E+09 | 0.00 | 0.17 |
December | 0.364017E+09 | 0.474546E+09 | 0.00 | 1897427.39 | 441787.84 | 0.148071E+09 | 0.447814E+09 | 0.00 | 0.17 |
Annual Sum or Average | 0.167621E+10 | 0.225324E+11 | 0.00 | 18789073.78 | 2286746.82 | 0.626480E+09 | 0.240810E+10 | 0.00 | 0.19 |
Minimum of Months | 0.00 | 0.168163E+09 | 0.00 | 45018.69 | 0.00 | 0.00 | 6019.25 | 0.00 | 0.16 |
Maximum of Months | 0.528640E+09 | 0.393394E+10 | 0.00 | 3416694.17 | 582659.15 | 0.222273E+09 | 0.552614E+09 | 0.00 | 0.21 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.392354E+10 | 0.165210E+09 | 0.00 | 788503.86 | 0.00 | 0.00 | 0.422646E+09 | 0.00 | 0.16 |
February | 0.236269E+10 | 0.428718E+09 | 0.00 | 1782334.39 | 0.00 | 1116720.70 | 0.591678E+09 | 0.00 | 0.17 |
March | 0.216293E+10 | 0.724275E+09 | 0.00 | 4053160.46 | 0.00 | 0.00 | 0.110049E+10 | 0.00 | 0.18 |
April | 0.380441E+09 | 0.179356E+10 | 0.00 | 9281521.93 | 0.00 | 0.00 | 0.861691E+09 | 0.00 | 0.17 |
May | 0.00 | 0.653692E+10 | 0.00 | 260134.22 | 0.00 | 0.00 | 4824813.93 | 0.00 | 0.19 |
June | 868055.51 | 0.836760E+10 | 0.00 | 154959.30 | 0.00 | 0.00 | 11446000.85 | 0.00 | 0.20 |
July | 0.00 | 0.972696E+10 | 0.00 | 25354.00 | 0.00 | 0.00 | 360372.84 | 0.00 | 0.19 |
August | 0.00 | 0.897362E+10 | 0.00 | 231699.00 | 0.00 | 0.00 | 6845496.97 | 0.00 | 0.20 |
September | 0.00 | 0.688285E+10 | 0.00 | 513066.61 | 0.00 | 0.00 | 23693649.13 | 0.00 | 0.19 |
October | 0.262880E+09 | 0.487715E+10 | 0.00 | 6885339.37 | 0.00 | 0.00 | 0.514125E+09 | 0.00 | 0.18 |
November | 0.820495E+09 | 0.131597E+10 | 0.00 | 6701357.21 | 0.00 | 0.00 | 0.119909E+10 | 0.00 | 0.16 |
December | 0.277162E+10 | 0.783105E+09 | 0.00 | 2212234.88 | 0.00 | 0.00 | 0.579341E+09 | 0.00 | 0.16 |
Annual Sum or Average | 0.126855E+11 | 0.505759E+11 | 0.00 | 32889665.23 | 0.00 | 1116720.70 | 0.531623E+10 | 0.00 | 0.18 |
Minimum of Months | 0.00 | 0.165210E+09 | 0.00 | 25354.00 | 0.00 | 0.00 | 360372.84 | 0.00 | 0.16 |
Maximum of Months | 0.392354E+10 | 0.972696E+10 | 0.00 | 9281521.93 | 0.00 | 1116720.70 | 0.119909E+10 | 0.00 | 0.20 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.708657E+12 | 0.495644E+11 | 0.00 | 0.138184E+11 | 0.181112E+11 |
February | 0.771102E+12 | 0.386549E+11 | 0.00 | 0.910075E+10 | 0.251458E+11 |
March | 0.893721E+12 | 0.522336E+11 | 0.00 | 0.886688E+10 | 0.339834E+11 |
April | 0.105335E+13 | 0.495232E+11 | 0.00 | 0.159893E+10 | 0.591841E+11 |
May | 0.104071E+13 | 0.685173E+11 | 0.00 | -0.130415E+11 | 0.107538E+12 |
June | 0.105168E+13 | 0.826946E+11 | 0.00 | -0.163555E+11 | 0.115622E+12 |
July | 0.107520E+13 | 0.811742E+11 | 0.00 | -0.195545E+11 | 0.123312E+12 |
August | 0.101097E+13 | 0.739242E+11 | 0.00 | -0.169643E+11 | 0.125437E+12 |
September | 0.849932E+12 | 0.612379E+11 | 0.00 | -0.130362E+11 | 0.105043E+12 |
October | 0.862632E+12 | 0.651210E+11 | 0.00 | -0.612741E+10 | 0.892430E+11 |
November | 0.669905E+12 | 0.388878E+11 | 0.00 | 0.539971E+10 | 0.419038E+11 |
December | 0.646766E+12 | 0.474322E+11 | 0.00 | 0.103176E+11 | 0.290338E+11 |
Annual Sum or Average | 0.106346E+14 | 0.708965E+12 | 0.00 | -0.359772E+11 | 0.873556E+12 |
Minimum of Months | 0.646766E+12 | 0.386549E+11 | 0.00 | -0.195545E+11 | 0.181112E+11 |
Maximum of Months | 0.107520E+13 | 0.826946E+11 | 0.00 | 0.138184E+11 | 0.125437E+12 |