Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2023-10-16 10:41:44
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3248.93 | 671.94 | 671.94 |
Net Site Energy | 3248.93 | 671.94 | 671.94 |
Total Source Energy | 5586.95 | 1155.49 | 1155.49 |
Net Source Energy | 5586.95 | 1155.49 | 1155.49 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2257.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 133.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 60.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 29.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 991.41 | 2257.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 2257.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 5.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 133.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 60.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 29.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 2257.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 5.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 133.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 60.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 29.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 19.75 | 466.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 205.04 | 466.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 19.75 | 466.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 205.04 | 466.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 991.412 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 991.412 | 100.00 |
Total On-Site and Utility Electric Sources | 991.412 | 100.00 |
Total Electricity End Uses | 991.412 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 156.83 |
Time Setpoint Not Met During Occupied Cooling | 0.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2865.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 20.56 |
Skylight-Roof Ratio [%] | 0.45 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7186 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 15.0695 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 9.6875 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 11.2890 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 11.2890 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.7186 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 15.0695 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 9.6875 | 46.45 | 2.5587 | |
Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 11.2890 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 30-DEC-15:39 | 28-JAN-17:10 | - | - | - | - | - | - | - | - | - | - | 12-JAN-12:20 |
Heating | 0.00 | 370082.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4186.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2749.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 71773.77 | 370082.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 370082.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 4186.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 2749.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2447.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 18.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1974.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 421.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 191.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 92.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3139.80 | 2447.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 506.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 39.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 19.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 649.37 | 506.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 506.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 39.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 19.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 649.37 | 506.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.00 |
ZONE2 FINE STORAGE DIRECT AIR | 2.40 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 4.44 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 4.44 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 178959.00 |
PSZ-OFFICE HEATING COIL | 31626.74 |
PSZ-FINE STORAGE HEATING COIL | 94234.80 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 178959.00 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PSZ-FINE STORAGE | 2.40 | 2.40 | 2.40 | 2.40 | 2.40 | 2.40 | 1.00 | 1.00 | 2.40 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.00 | 0.120335 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.40 | 0.353926 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.00 | 1141.72 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.40 | 2631.90 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.00 | 1.00 | 1.00 | 1.00 | 16576.93 | 31626.74 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.40 | 2.40 | 2.40 | 2.40 | 44258.90 | 94234.80 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.00 | 0.500706 | 1.00 | 16576.93 | 8288.47 | 16576.93 | 0.800660 | 0.800660 |
PSZ-FINE STORAGE COOLING COIL | 2.40 | 1.20 | 2.40 | 44258.90 | 21953.21 | 44258.90 | 0.800660 | 0.800660 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.719 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.792 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 15.069 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15.069 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 9.688 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 12.246 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2539.013 | 10.719 | 199.158 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2539.013 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 20997.932 | 15.069 | 699.931 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20997.932 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 31046.942 | 9.688 | 449.956 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 31046.942 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2893 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.4332 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.4133 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.7823 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.7823 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.457 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.309 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.320 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.179 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.179 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.87112823E-12 | 0.85080972E-17 | 0.21755189E-17 | 0.0000000 |
2 | 1 | -5.2160329 | 0.44465164E-04 | -0.55377147E-04 | 0.16700973E-12 |
3 | 0 | 5.5053245 | 0.28924715 | 0.28934699 | |
4 | 2 | 0.53503428E-11 | 0.43487872E-15 | 0.25437469E-15 | 0.0000000 |
5 | 1 | -5.2159992 | 0.41060176E-04 | -0.36984335E-04 | 0.68788638E-11 |
6 | 0 | 5.6491605 | 0.43312021 | 0.43319826 | |
7 | 4 | 0.79569988E-12 | 0.97024197E-16 | -0.20560970E-14 | 0.11376788E-15 |
8 | 3 | -0.38947258E-03 | 0.29188957E-06 | -0.56541964E-04 | 0.15267338E-12 |
9 | 2 | 1.7507793 | 0.63492849E-02 | 1.1490006 | -0.74668540E-04 |
10 | 1 | -7.1139048 | 0.16396836 | -17.152679 | 0.33556055 |
11 | 0 | 5.6381505 | 0.10431759 | 16.278371 | |
12 | 4 | 0.72249793E-12 | -0.16720573E-15 | 0.22015083E-14 | 0.12409536E-15 |
13 | 3 | -0.36459118E-03 | 0.53555631E-06 | -0.52695411E-04 | 0.13865996E-12 |
14 | 2 | 1.6915239 | 0.11971291E-01 | 1.1039557 | -0.69896550E-04 |
15 | 1 | -7.1930661 | 0.31446443 | -16.864389 | 0.32415671 |
16 | 0 | 6.0306730 | 0.20232993 | 16.289252 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.22015083E-14 | -0.16720573E-15 | 0.72249793E-12 | 0.12409536E-15 |
85 | 3 | -0.52695411E-04 | 0.53555631E-06 | -0.36459118E-03 | 0.13865996E-12 |
86 | 2 | 1.1039557 | 0.11971291E-01 | 1.6915239 | -0.69896550E-04 |
87 | 1 | -16.864389 | 0.31446443 | -7.1930661 | 0.32415671 |
88 | 0 | 16.289252 | 0.20232993 | 6.0306730 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.4603_SHGC_SOUTH_0.45 | 34 | 1 | VerySmooth | 2.617 | 2.617 | 1.000 | 0.451 | ||
2 | NONRESWINDOW_U_0.4603_SHGC_NORTH_0.45 | 35 | 1 | VerySmooth | 2.617 | 2.617 | 1.000 | 0.451 | ||
3 | NONRESWINDOW_U_0.4603_SHGC_EAST_0.45 | 36 | 1 | VerySmooth | 2.617 | 2.617 | 1.000 | 0.451 | ||
4 | NONRESWINDOW_U_0.4603_SHGC_WEST_0.45 | 37 | 1 | VerySmooth | 2.617 | 2.617 | 1.000 | 0.451 | ||
5 | SKYLIGHT_U_0.98_SHGC_0.49 | 38 | 1 | VerySmooth | 5.556 | 5.556 | 1.000 | 0.490 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.53501E-002 | 0.36619 | 0.42298 | 0.42298 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.11997 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.53501E-002 | 0.36619 | 0.42298 | 0.42298 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.11997 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.53501E-002 | 0.36619 | 0.42298 | 0.42298 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.11997 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.53501E-002 | 0.36619 | 0.42298 | 0.42298 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.11997 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.32532 | 0.13808 | 0.13808 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 0.14909 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.610 | 0.480 | 0.440 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 0.153 | 6.473E-004 | 9.992E-004 | 0.546 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.780 | 5.598E-004 | 3.565E-004 | 0.951 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 3.433 | 1.071E-003 | 6.996E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9986.14239 | 11983.37087 | 0.83451 | 1.00141 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 25.97200 | 7.00497E-003 | 236.87965 | 12.74874 | 0.12033 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 12819.71778 | 15383.66134 | 0.36568 | 0.43882 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90000 | 6.45023E-005 | 236.87965 | 12.74874 | 0.12033 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 30762.35489 | 36914.82587 | 2.00387 | 2.40465 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 27.09400 | 7.00668E-003 | 1393.40969 | 30.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 46559.18855 | 55871.02626 | 1.11832 | 1.34199 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -41.90000 | 6.45023E-005 | 1393.40969 | 30.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 27.23000 | 7.00688E-003 | 3204.84228 | 69.00000 | 0.81403 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 149132.49692 | 178958.99630 | 3.70144 | 4.44173 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 3204.84228 | 69.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 14491.68 | 1.00141 | 1.00141 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 18928.30 | 0.43882 | 0.43882 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 42291.72 | 2.40465 | 2.40465 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 63295.79 | 1.34199 | 1.34199 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.00141 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.40465 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 4.44173 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 4.44173 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 178959.00173 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 178958.99630 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.00141 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.00141 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.00141 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.00141 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.00141 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.00141 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.40465 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.40465 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.40465 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.40465 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.40465 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.40465 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.00141 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.40465 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.00141 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12033 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.00141 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1141.72038 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.00141 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.00141 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.00141 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.00141 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.00141 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50071 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.00141 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16576.93000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 8288.46692 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16576.93000 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16576.93000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31626.73930 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 31626.73930 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.40465 |
47 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.40465 |
49 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2631.89893 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.40465 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.40465 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.40465 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.40465 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.40465 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.20232 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.40465 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 44258.90000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 21953.21291 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 44258.90000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 44258.90000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 94234.80361 |
64 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
66 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 94234.80361 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 15799.9 | 9.78 | 9.21 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 42392.3 | 10.34 | 9.74 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.5380917189 | 0.5388973902 | Pass | Pass | 1.2055311269 | 2.9400861943 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 1.0514646381 | 1.0213900080 | Pass | Pass | 0.6689818905 | 0.6644363711 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 3.9880821349E-005 | 6.4335727707E-005 | Pass | Pass | 2.3777128235E-002 | 2.2717627315E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5266.96 | 862.50 | 0.00 | 178.28 | 658.65 | 6966.42 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.389 | 0.413 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.389 | 0.413 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.389 | 0.413 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.389 | 0.413 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.389 | 0.413 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.389 | 0.413 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.389 | 0.413 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.278 | 0.289 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.409 | 0.433 | 3204.84 | 3184.28 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.659 | 0.782 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.659 | 0.782 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.4603_SHGC_WEST_0.45 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.617 | 0.451 | 0.452 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.4603_SHGC_WEST_0.45 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.617 | 0.451 | 0.452 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.4603_SHGC_NORTH_0.45 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.617 | 0.451 | 0.452 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.4603_SHGC_NORTH_0.45 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.617 | 0.451 | 0.452 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.57 | 0.00 | 2.06 | 2.06 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.610 | 0.480 | 0.440 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.57 | 0.00 | 2.06 | 2.06 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.610 | 0.480 | 0.440 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.57 | 0.00 | 2.06 | 2.06 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.610 | 0.480 | 0.440 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.57 | 0.00 | 2.06 | 2.06 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.610 | 0.480 | 0.440 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.57 | 0.00 | 2.06 | 2.06 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.610 | 0.480 | 0.440 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.57 | 0.00 | 2.06 | 2.06 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.610 | 0.480 | 0.440 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.57 | 0.00 | 2.06 | 2.06 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.610 | 0.480 | 0.440 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.57 | 0.00 | 2.06 | 2.06 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.610 | 0.480 | 0.440 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.57 | 0.00 | 2.06 | 2.06 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.610 | 0.480 | 0.440 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.57 | 0.00 | 2.06 | 2.06 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.610 | 0.480 | 0.440 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 38.22 | 4.328 | 0.505 | 0.505 | |||||||||||||||||
North Total or Average | 6.51 | 2.617 | 0.451 | 0.452 | |||||||||||||||||
Non-North Total or Average | 31.72 | 4.679 | 0.516 | 0.516 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.7186 | 236.88 | 2539.01 | LightsWired | LTG_SCH_OFFICE | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.86 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 15.0695 | 1393.41 | 20997.93 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 239.15 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 9.6875 | 3204.84 | 31046.94 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 353.60 |
Interior Lighting Total | 11.2890 | 4835.13 | 54583.89 | 623.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 8532.22 | AstronomicalClock | - | 83.06 | 83.06 | 133.03 | |
Exterior Lighting Total | 8532.22 | 133.03 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16576.93 | 13272.48 | 3304.45 | 0.80 | 3.15 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 44258.90 | 35436.33 | 8822.57 | 0.80 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 15799.9 | 9.78 | 9.21 | ||||
PSZ-FINE STORAGE COOLING COIL | 42392.3 | 10.34 | 9.74 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 178959.00 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 31626.74 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 94234.80 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 4.44 | 412.68 | 92.91 | 1.00 | 3.20 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.00 | 1141.72 | 1140.11 | 1.00 | 1.36 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 2.40 | 2631.90 | 1094.51 | 1.00 | 1.26 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9986.14 | 11983.37 | 50.59 | 0.835 | 1.001 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00823 | 25.97 | 0.00700 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 30762.35 | 36914.83 | 26.49 | 2.004 | 2.405 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 26.70 | 26.70 | 0.00815 | 27.09 | 0.00701 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 0.00 | 29.72 | 0.00715 | 27.23 | 0.00701 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 12819.72 | 15383.66 | 64.94 | 0.366 | 0.439 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00821 | -41.90 | 0.00006 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 46559.19 | 55871.03 | 40.10 | 1.118 | 1.342 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00766 | -41.90 | 0.00006 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 149132.50 | 178959.00 | 55.84 | 3.701 | 4.442 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00755 | -41.90 | 0.00006 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.00 | 1.00 | 0.44 | 0.44 | 1.0014 | 1.0014 | 1.0014 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.40 | 2.40 | 1.34 | 1.34 | 2.4046 | 2.4046 | 2.4046 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 178959.002 | 178959.002 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 178959.00 | 178959.00 | 4.441727 | 10.00 | 9.79 | 0.00755418 | 43.33 | 21.96 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 10.00 | 0.00755418 | 97.4656 | 178959.00 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 16576.930 | 13272.485 | 1.001410 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 16576.93 | 16349.12 | 1.001410 | 25.09 | 16.26 | 0.00808159 | 12.00 | 11.12 | 0.00800000 | 25.97 | 0.00700497 | 15.63 | 12.0165 | 23.90 | 0.00822863 | 43.8899 | 9986.14 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 31626.739 | 31626.739 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 31626.74 | 31626.74 | 1.001413 | 13.49 | 10.96 | 0.00722926 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 12.0165 | 21.10 | 0.00820780 | 51.8964 | 12819.72 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 44258.900 | 35436.331 | 2.404650 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 44258.90 | 44258.90 | 2.404650 | 27.68 | 17.07 | 0.00797908 | 12.00 | 11.10 | 0.00797908 | 27.20 | 0.00700683 | 16.07 | 14.7184 | 26.70 | 0.00814699 | 36.7921 | 30745.20 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 94234.804 | 94234.804 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 94234.80 | 94234.80 | 2.404647 | 7.10 | 7.10 | 0.00654241 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 14.7184 | 15.56 | 0.00766041 | 68.6423 | 46559.19 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 178959.002 | 178959.002 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 4.441727 | 5.26539731 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 178959.00 | 178959.00 | 1.0000 | 5.26539731 | 4.441727 | 10.00 | 9.79 | 0.00755418 | 29080.6 | 43.33 | 21.96 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 178959.00 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 10.00 | 0.00755418 | 10.00 | 0.00755418 | 97.4656 | 178959.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16576.930 | 13272.485 | 1.001410 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.8633 | 1004.8586 | 1.1854 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.001413 | 1.18711381 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | Sensible | 16576.93 | 16349.12 | 1.0000 | 1.18711076 | 1.001410 | 25.09 | 16.26 | 0.00808159 | 45801.5 | 12.00 | 11.12 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16576.93 | 25.97 | 0.00700497 | 15.63 | 0.12033486 | 12.0165 | 23.90 | 0.00822863 | 23.90 | 0.00822863 | 43.8899 | 9986.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31626.739 | 31626.739 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.001413 | 1.18711381 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 31626.74 | 31626.74 | 1.0000 | 1.18711381 | 1.001413 | 13.49 | 10.96 | 0.00722926 | 31813.6 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31626.74 | -41.90 | 0.00006450 | -41.90 | 0.12033486 | 12.0165 | 21.05 | 0.00820780 | 21.10 | 0.00820780 | 51.8964 | 12819.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 44258.900 | 35436.331 | 2.404650 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6727 | 1004.8586 | 1.1854 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.404647 | 2.85056259 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 44258.90 | 44258.90 | 1.0000 | 2.85056660 | 2.404650 | 27.68 | 17.07 | 0.00797908 | 48178.0 | 12.00 | 11.10 | 0.00797908 | 32191.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 44258.90 | 27.20 | 0.00700683 | 16.07 | 0.35392606 | 14.7184 | 26.70 | 0.00814699 | 26.70 | 0.00814699 | 36.7921 | 30745.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 94234.804 | 94234.804 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.404647 | 2.85056259 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 94234.80 | 94234.80 | 1.0000 | 2.85056259 | 2.404647 | 7.10 | 7.10 | 0.00654241 | 23584.4 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 94234.80 | -41.90 | 0.00006450 | -41.90 | 0.35392606 | 14.7184 | 15.56 | 0.00766041 | 15.56 | 0.00766041 | 68.6423 | 46559.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.35 | 2.40 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2576.83 | 3174.50 | 2420.33 |
ZONE2 FINE STORAGE | 3119.17 | 2958.33 | 2520.17 |
ZONE3 BULK STORAGE | 3149.17 | 3239.00 | 2855.83 |
Facility | 3428.67 | 3304.00 | 2865.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 429.17 | 22.50 | 132.50 | 0.67 |
ZONE2 FINE STORAGE | 723.00 | 0.83 | 31.83 | 0.00 |
ZONE3 BULK STORAGE | 44.50 | 0.00 | 13.67 | 0.00 |
Facility | 1031.50 | 23.33 | 156.83 | 0.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.410 | 0.462 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.411 | 0.264 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.111 | 0.000 | 0.033 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.50 | 12.75 | 1010.76 | 236.88 | 0.1203 | 0.120 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.36 | 30.00 | 2953.02 | 1393.41 | 0.3539 | 0.354 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 3204.84 | 0.814 | ||
Total Facility | 83.28 | 111.75 | 39241.41 | 4835.13 | 0.4743 | 1.288 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1580954.26 | 0.00 | 1580954.26 | 2552845.52 | 4133799.77 | 3794880.16 | 5378.52 | 3381.48 | 0.00 | 1555.42 |
ZONE2 FINE STORAGE | 4363021.14 | 0.00 | 4363021.14 | 7850569.53 | 12213590.67 | 11161412.23 | 5729.67 | 2784.67 | 245.67 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 10266576.17 | 10266576.17 | 30999447.47 | 41266023.63 | 25671248.14 | 8394.00 | 40.17 | 325.83 | 4375.33 |
Total Facility | 5943975.40 | 10266576.17 | 16210551.57 | 41402862.51 | 57613414.08 | 40627540.53 | 8613.50 | 3406.20 | 563.67 | 4698.21 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1132 | 0.0000 | 0.1132 | 0.1278 | 0.2410 | 0.1203 | 264.56 | 3371.44 | 0.00 |
ZONE2 FINE STORAGE | 0.3333 | 0.0000 | 0.3333 | 0.2146 | 0.5479 | 0.3539 | 605.67 | 2784.67 | 245.67 |
ZONE3 BULK STORAGE | 0.0000 | 0.3240 | 0.3240 | 1.0875 | 1.4114 | 0.8140 | 3482.17 | 15.83 | 138.00 |
Total Facility | 0.4466 | 0.3240 | 0.7705 | 1.4298 | 2.2003 | 1.2883 | 3489.50 | 3371.88 | 375.83 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2221661.77 | 0.00 | 2221661.77 | 3794880.16 | 5348.17 | 2.81 | 3409.02 | 1529.42 |
PSZ-FINE STORAGE | 6131206.67 | 0.00 | 6131206.67 | 11161412.23 | 5729.00 | 0.00 | 3031.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1591 | 0.0000 | 0.1591 | 0.1203 | 253.08 | 1.04 | 3381.88 |
PSZ-FINE STORAGE | 0.4684 | 0.0000 | 0.4684 | 0.3539 | 605.00 | 0.00 | 3031.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 5033.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2784.00 | 248.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1652 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.4975 | 1.2841 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 383 |
Defaulted Fields | 319 |
Fields with Defaults | 1020 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 991.41 | 6718.26 | 19-MAR-12:00 | 71773.77 | 30-DEC-15:40 |
Electricity:Building | 762.90 | 6235.26 | 01-JAN-00:10 | 56305.80 | 02-JAN-09:10 |
Electricity:Zone:ZONE1 OFFICE | 62.81 | 1030.77 | 01-JAN-00:10 | 3867.54 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 762.90 | 6235.26 | 01-JAN-00:10 | 56305.80 | 02-JAN-09:10 |
InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 460.94 | 3104.69 | 01-JAN-00:10 | 34590.02 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 60.42 | 0.00 | 18-MAR-17:10 | 4186.30 | 02-JAN-13:40 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 991.41 | 6718.26 | 19-MAR-12:00 | 71773.77 | 30-DEC-15:40 |
ElectricityPurchased:Plant | 991.41 | 6718.26 | 19-MAR-12:00 | 71773.77 | 30-DEC-15:40 |
Cogeneration:ElectricityPurchased | 991.41 | 6718.26 | 19-MAR-12:00 | 71773.77 | 30-DEC-15:40 |
General:Cogeneration:ElectricityPurchased | 991.41 | 6718.26 | 19-MAR-12:00 | 71773.77 | 30-DEC-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 991.41 | 6718.26 | 19-MAR-12:00 | 71773.77 | 30-DEC-15:40 |
ElectricityNet:Plant | 991.41 | 6718.26 | 19-MAR-12:00 | 71773.77 | 30-DEC-15:40 |
Cogeneration:ElectricityNet | 991.41 | 6718.26 | 19-MAR-12:00 | 71773.77 | 30-DEC-15:40 |
General:Cogeneration:ElectricityNet | 991.41 | 6718.26 | 19-MAR-12:00 | 71773.77 | 30-DEC-15:40 |
Electricity:HVAC | 66.28 | 0.00 | 18-MAR-17:10 | 13763.32 | 21-JUL-16:00 |
General:Fans:Electricity | 60.42 | 0.00 | 18-MAR-17:10 | 4186.30 | 02-JAN-13:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 5.86 | 0.00 | 01-JAN-00:10 | 9989.70 | 21-JUL-16:00 |
General:Cooling:Electricity | 5.86 | 0.00 | 01-JAN-00:10 | 9989.70 | 21-JUL-16:00 |
ExteriorLights:Electricity | 133.03 | 0.00 | 01-JAN-11:20 | 8532.22 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 133.03 | 0.00 | 01-JAN-11:20 | 8532.22 | 01-JAN-00:10 |
Electricity:Plant | 29.21 | 483.00 | 01-JAN-18:40 | 3179.36 | 13-JAN-12:40 |
WaterSystems:Electricity | 29.21 | 483.00 | 01-JAN-18:40 | 3179.36 | 13-JAN-12:40 |
Water Heater:WaterSystems:Electricity | 29.21 | 483.00 | 01-JAN-18:40 | 3179.36 | 13-JAN-12:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 2257.52 | 5250.00 | 18-MAR-17:10 | 370082.88 | 28-JAN-17:10 |
NaturalGas:HVAC | 2257.52 | 5250.00 | 18-MAR-17:10 | 370082.88 | 28-JAN-17:10 |
Heating:NaturalGas | 2257.52 | 5250.00 | 18-MAR-17:10 | 370082.88 | 28-JAN-17:10 |
General:Heating:NaturalGas | 2257.52 | 5250.00 | 18-MAR-17:10 | 370082.88 | 28-JAN-17:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-JAN-12:20 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-JAN-12:20 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-JAN-12:20 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-JAN-12:20 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-JAN-12:20 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-JAN-12:20 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-JAN-12:20 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-JAN-12:20 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3239.18 | 0.00 | 18-MAR-17:10 | 584101.96 | 29-JAN-00:20 |
EnergyTransfer:Building | 1594.14 | 0.00 | 18-MAR-17:10 | 291724.90 | 29-JAN-00:20 |
EnergyTransfer:Zone:ZONE1 OFFICE | 104.59 | 0.00 | 01-JAN-00:40 | 27749.90 | 14-MAR-06:10 |
Heating:EnergyTransfer | 1560.81 | 0.00 | 18-MAR-17:10 | 291724.90 | 29-JAN-00:20 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 93.22 | 0.00 | 01-JAN-00:40 | 27749.90 | 14-MAR-06:10 |
General:Heating:EnergyTransfer | 1560.81 | 0.00 | 18-MAR-17:10 | 291724.90 | 29-JAN-00:20 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 93.22 | 0.00 | 01-JAN-00:40 | 27749.90 | 14-MAR-06:10 |
Cooling:EnergyTransfer | 33.33 | 0.00 | 01-JAN-00:10 | 27226.40 | 21-JUL-16:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 11.37 | 0.00 | 01-JAN-00:10 | 8168.49 | 21-JUL-16:00 |
General:Cooling:EnergyTransfer | 33.33 | 0.00 | 01-JAN-00:10 | 27226.40 | 21-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 11.37 | 0.00 | 01-JAN-00:10 | 8168.49 | 21-JUL-16:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 321.76 | 0.00 | 01-JAN-00:40 | 96102.44 | 29-JAN-00:20 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 299.80 | 0.00 | 01-JAN-00:40 | 96102.44 | 29-JAN-00:20 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 299.80 | 0.00 | 01-JAN-00:40 | 96102.44 | 29-JAN-00:20 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 21.96 | 0.00 | 01-JAN-00:10 | 19057.92 | 21-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 21.96 | 0.00 | 01-JAN-00:10 | 19057.92 | 21-JUL-16:00 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 1167.79 | 0.00 | 09-FEB-11:50 | 180945.80 | 28-JAN-14:50 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 1167.79 | 0.00 | 09-FEB-11:50 | 180945.80 | 28-JAN-14:50 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 1167.79 | 0.00 | 09-FEB-11:50 | 180945.80 | 28-JAN-14:50 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1645.04 | 0.00 | 18-MAR-17:10 | 292377.06 | 29-JAN-00:20 |
HeatingCoils:EnergyTransfer | 1624.88 | 0.00 | 18-MAR-17:10 | 292377.06 | 29-JAN-00:20 |
CoolingCoils:EnergyTransfer | 20.16 | 0.00 | 01-JAN-00:10 | 32936.11 | 21-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 93.214 | -11.374 | 0.000 | 0.000 | 10.297 | 30.864 | 31.946 | 7.956 | 0.000 | 0.078 | 0.000 | 0.000 | -19.190 | 0.000 | -61.752 | -82.038 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 299.802 | -21.958 | 0.000 | 0.000 | 27.120 | 239.148 | 0.000 | 0.000 | 0.000 | 0.037 | 0.001 | 0.000 | 0.000 | 0.000 | -152.332 | -391.818 |
ZONE3 BULK STORAGE | 1167.791 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 71.396 | 353.598 | 107.344 | 60.666 | 0.000 | 0.342 | 0.000 | 0.000 | -187.458 | 0.000 | -619.619 | -954.059 |
Total Facility | 1167.791 | 0.000 | 393.016 | -33.332 | 0.000 | 0.000 | 108.813 | 623.610 | 139.290 | 68.623 | 0.000 | 0.456 | 0.002 | 0.000 | -206.648 | 0.000 | -833.703 | -1427.915 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 09-JUL-23:02 | 0.00 | 0.00 | 0.00 | -16028.91 | 0.00 | 0.00 | 0.00 | 457.02 | 573.75 | 0.00 | 0.00 | 0.00 | 15813.48 | 0.00 | -509.06 | 0.00 | -306.29 | 0.00 |
ZONE2 FINE STORAGE | 23-JUL-10:53 | 0.00 | 0.00 | 0.00 | -22074.60 | 0.00 | 0.00 | 0.00 | 2099.79 | 0.00 | 0.00 | 0.00 | 0.00 | 19974.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 21-JUL-16:00 | 0.00 | 0.00 | 0.00 | -27217.68 | 0.00 | 0.00 | 5648.22 | 40988.70 | 10112.62 | 8508.19 | 0.00 | 9980.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -48020.48 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 01-MAY-05:01 | 0.00 | 0.00 | 30635.98 | 0.00 | 0.00 | 0.00 | 149.15 | 583.97 | 573.75 | 420.04 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1037.70 | -31325.18 |
ZONE2 FINE STORAGE | 25-FEB-06:41 | 0.00 | 0.00 | 100971.34 | 0.00 | 0.00 | 0.00 | 397.03 | 2099.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -26267.92 | -77200.24 |
ZONE3 BULK STORAGE | 28-JAN-14:50 | 180943.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8668.38 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6890.99 | 0.00 | -214335.03 | -2975.38 |
Total Facility | 28-JAN-06:11 | 179380.52 | 0.00 | 123537.82 | 0.00 | 0.00 | 0.00 | 1423.59 | 5788.46 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -13423.44 | 0.00 | -145124.30 | -154206.43 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0014 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1203 | 1.0014 | 0.1202 | 1.0000 | Not calculated | 0.1203 | 0.1202 | ||
PSZ-FINE STORAGE | 2.4046 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.3539 | 2.4046 | 0.1472 | 1.0000 | Not calculated | 0.3539 | 0.1472 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0014 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1203 | 1.0014 | 1.0000 | 1.0000 | Not calculated | 0.1203 | 0.1202 | ||
PSZ-FINE STORAGE | 2.4046 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.3539 | 2.4046 | 1.0000 | 1.0000 | Not calculated | 0.3539 | 0.1472 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0014 | 1.0014 | 1.0014 | No | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4046 | 2.4046 | 2.4046 | No | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0014 | 1.0014 | 1.0014 | 1.0014 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 2.4046 | 2.4046 | 2.4046 | 2.4046 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0014 | 1.0014 | 1.0014 | No | 0.1203 | 0.2742 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4046 | 2.4046 | 2.4046 | No | 0.3539 | 0.2637 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0014 | 1.0014 | 1.0014 | 1.0014 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 2.4046 | 2.4046 | 2.4046 | 2.4046 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 156.83 |
Number of hours cooling loads not met | 0.67 |
Number of hours not met | 157.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 2257.52 | 370082.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 5.86 | 9989.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 623.61 | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 133.03 | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 60.42 | 4186.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 29.21 | 3179.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 991.41 |
Natural Gas | 0.00 | 2257.52 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 3248.93 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 128.97 |
Space Heating | 0.00 |
Space Cooling | 1.21 |
Fans (All) | 12.50 |
Service Water Heating | 6.04 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 205.04 |
Subtotal | 205.04 |
Natural Gas [MJ/m2] | |
Space Heating | 466.90 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 466.90 |
Subtotal | 466.90 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 19.19 |
Space Heating | 69.48 |
Space Cooling | 0.18 |
Fans (All) | 1.86 |
Service Water Heating | 0.90 |
Receptacle Equipment | 4.29 |
Miscellaneous | 4.09 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 3430. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8754.17 | 5.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8660.17 | 99.83 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8621.67 | 138.33 | 0.00 | 0.00 | 0.00 |
Min | 8621.67 | 5.83 | 0.00 | 0.00 | 0.00 |
Max | 8754.17 | 138.33 | 0.00 | 0.00 | 0.00 |
Average | 8678.67 | 81.33 | 0.00 | 0.00 | 0.00 |
Sum | 26036.00 | 244.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 80273.50 | 2445.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 184524.83 | 6668.17 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 184524.83 | 6668.17 | 0.00 | 0.00 | 0.00 |
Average | 99275.11 | 3037.89 | 0.00 | 0.00 | 0.00 |
Sum | 297825.33 | 9113.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8756.83 | 3.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8608.67 | 151.33 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8623.67 | 136.33 | 0.00 | 0.00 | 0.00 |
Min | 8608.67 | 3.17 | 0.00 | 0.00 | 0.00 |
Max | 8756.83 | 151.33 | 0.00 | 0.00 | 0.00 |
Average | 8663.06 | 96.94 | 0.00 | 0.00 | 0.00 |
Sum | 25989.17 | 290.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 79080.00 | 3639.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 184643.67 | 6549.33 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 184643.67 | 6549.33 | 0.00 | 0.00 | 0.00 |
Average | 98916.89 | 3396.11 | 0.00 | 0.00 | 0.00 |
Sum | 296750.67 | 10188.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -14.9 | -15.4 | 0.494617E+09 | 603.25 | 07-JAN-08:09 | -7.2 | -7.4 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -20.2 | -20.7 | 0.455885E+09 | 603.25 | 03-FEB-08:09 | -14.4 | -14.6 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -28.9 | -29.2 | 0.535503E+09 | 603.25 | 11-MAR-08:09 | -9.8 | -10.7 |
April | 35632463.86 | 757.72 | 29-APR-11:00 | 8.30 | 4.18 | 0.501917E+09 | 737.41 | 22-APR-15:09 | 8.30 | 4.18 |
May | 0.318296E+09 | 2924.37 | 13-MAY-15:00 | 20.00 | 9.32 | 0.576341E+09 | 768.96 | 31-MAY-15:39 | 21.83 | 10.78 |
June | 0.298860E+10 | 13338.87 | 21-JUN-17:10 | 26.02 | 14.32 | 0.649927E+09 | 769.03 | 30-JUN-13:09 | 26.78 | 17.02 |
July | 0.436177E+10 | 16028.77 | 09-JUL-23:02 | 13.03 | 11.01 | 0.629990E+09 | 769.03 | 24-JUL-15:20 | 21.30 | 15.91 |
August | 0.317901E+10 | 14438.73 | 11-AUG-17:43 | 25.60 | 14.89 | 0.668007E+09 | 769.02 | 01-AUG-13:20 | 25.60 | 14.89 |
September | 0.466850E+09 | 3060.74 | 02-SEP-15:00 | 16.70 | 10.81 | 0.535279E+09 | 768.98 | 02-SEP-14:00 | 16.70 | 10.81 |
October | 24080827.62 | 938.95 | 07-OCT-13:20 | 6.67 | 5.44 | 0.497365E+09 | 633.51 | 03-OCT-15:09 | 6.67 | 5.44 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 0.476583E+09 | 603.25 | 03-NOV-07:10 | -16.9 | -17.2 |
December | 163276.82 | 1632.77 | 28-DEC-08:05 | -27.9 | -28.1 | 0.495401E+09 | 603.25 | 02-DEC-08:09 | -27.9 | -28.1 |
Annual Sum or Average | 0.113744E+11 | 0.651682E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -28.9 | -29.2 | 0.455885E+09 | 603.25 | -27.9 | -28.1 | ||
Maximum of Months | 0.436177E+10 | 16028.77 | 26.02 | 14.89 | 0.668007E+09 | 769.03 | 26.78 | 17.02 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 204778.66 | 224.36 | 21-JAN-13:10 | -5.6 | -6.2 | 0.648968E+09 | 787.42 | 11-JAN-11:39 | -5.6 | -6.2 |
February | 0.119629E+09 | 4214.76 | 09-FEB-12:00 | -1.7 | -2.1 | 0.597049E+09 | 787.84 | 09-FEB-16:10 | 0.13 | -0.8 |
March | 0.885075E+09 | 7166.29 | 28-MAR-12:10 | -7.6 | -10.2 | 0.711472E+09 | 1104.45 | 22-MAR-15:09 | -7.6 | -10.2 |
April | 0.162292E+10 | 5516.48 | 08-APR-12:40 | -3.7 | -6.4 | 0.811875E+09 | 1559.44 | 22-APR-14:30 | 15.00 | 6.61 |
May | 0.104753E+10 | 4358.25 | 16-MAY-08:15 | 5.20 | 3.93 | 0.125693E+10 | 2140.42 | 13-MAY-15:09 | 5.20 | 3.93 |
June | 0.358555E+10 | 18452.32 | 21-JUN-18:13 | 25.20 | 14.12 | 0.179222E+10 | 2246.94 | 30-JUN-12:39 | 26.33 | 17.53 |
July | 0.663433E+10 | 22074.65 | 23-JUL-10:53 | 22.80 | 15.42 | 0.180303E+10 | 2246.92 | 22-JUL-10:39 | 22.80 | 15.42 |
August | 0.429256E+10 | 17598.87 | 02-AUG-17:33 | 22.97 | 14.50 | 0.180128E+10 | 2246.92 | 04-AUG-12:09 | 21.28 | 14.52 |
September | 0.233705E+10 | 5883.97 | 29-SEP-08:70 | -4.4 | -4.8 | 0.105013E+10 | 1998.03 | 02-SEP-15:09 | -4.4 | -4.8 |
October | 0.140792E+10 | 8035.24 | 27-OCT-13:05 | -11.7 | -12.7 | 0.700244E+09 | 1244.88 | 03-OCT-15:09 | -11.7 | -12.7 |
November | 25205870.60 | 2086.65 | 04-NOV-14:00 | -9.4 | -11.0 | 0.623116E+09 | 787.42 | 30-NOV-11:09 | -28.6 | -28.9 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -25.8 | -26.0 | 0.648987E+09 | 787.42 | 06-DEC-16:40 | -23.0 | -23.3 |
Annual Sum or Average | 0.219580E+11 | 0.124453E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.597049E+09 | 787.42 | -28.6 | -28.9 | ||
Maximum of Months | 0.663433E+10 | 22074.65 | 25.20 | 15.42 | 0.180303E+10 | 2246.94 | 26.33 | 17.53 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -14.9 | -15.4 | 0.634568E+09 | 780.44 | 11-JAN-14:20 | -33.7 | -33.8 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -20.2 | -20.7 | 0.591689E+09 | 795.65 | 15-FEB-14:09 | -8.1 | -9.1 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -28.9 | -29.2 | 0.717753E+09 | 1265.75 | 22-MAR-15:09 | 5.60 | 2.29 |
April | 0.00 | 0.00 | 01-APR-00:03 | -11.7 | -13.3 | 0.917243E+09 | 2000.66 | 22-APR-14:30 | 15.00 | 6.61 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 | 2.18 | 0.199071E+10 | 3440.71 | 13-MAY-15:20 | 20.00 | 9.32 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.14 | 0.347676E+10 | 5578.01 | 30-JUN-15:09 | 27.38 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 | 0.402985E+10 | 6242.13 | 22-JUL-13:20 | 26.87 | 16.62 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.83 | 0.362298E+10 | 6045.65 | 04-AUG-15:09 | 22.70 | 14.61 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 | 0.163705E+10 | 3440.50 | 02-SEP-15:20 | 16.70 | 10.68 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 | 0.12 | 0.723659E+09 | 1427.70 | 03-OCT-15:20 | 12.43 | 6.74 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 0.618258E+09 | 780.54 | 25-NOV-15:20 | -20.0 | -20.3 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -25.8 | -26.0 | 0.644023E+09 | 780.42 | 04-DEC-14:20 | -21.3 | -21.6 |
Annual Sum or Average | 0.00 | 0.196045E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -28.9 | -29.2 | 0.591689E+09 | 780.42 | -33.7 | -33.8 | ||
Maximum of Months | 0.00 | 0.00 | 16.35 | 13.77 | 0.402985E+10 | 6242.13 | 27.38 | 17.05 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.163958E+11 | 29346.01 | 19-JAN-06:01 | -2.5 |
February | 0.142333E+11 | 29673.60 | 09-FEB-06:01 | 0.00 |
March | 0.145609E+11 | 29418.14 | 22-MAR-05:01 | -1.9 |
April | 0.730895E+10 | 29696.91 | 20-APR-05:01 | 0.60 |
May | 0.157782E+10 | 30635.82 | 01-MAY-05:01 | 7.30 |
June | 0.125397E+09 | 26309.11 | 01-JUN-05:02 | 7.20 |
July | 28822732.11 | 3442.89 | 05-JUL-06:05 | 8.30 |
August | 0.195617E+09 | 28673.77 | 31-AUG-05:01 | -1.2 |
September | 0.190098E+10 | 30272.44 | 19-SEP-05:01 | 9.60 |
October | 0.823370E+10 | 30549.16 | 04-OCT-05:01 | 7.70 |
November | 0.128369E+11 | 28599.40 | 04-NOV-05:01 | -7.9 |
December | 0.158169E+11 | 29164.00 | 23-DEC-06:01 | -3.8 |
Annual Sum or Average | 0.932151E+11 | |||
Minimum of Months | 28822732.11 | 3442.89 | -7.9 | |
Maximum of Months | 0.163958E+11 | 30635.82 | 9.60 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.599635E+11 | 100685.83 | 28-JAN-06:41 | -18.8 |
February | 0.477030E+11 | 100971.73 | 25-FEB-06:41 | -24.4 |
March | 0.435629E+11 | 99404.85 | 04-MAR-06:41 | -27.0 |
April | 0.213251E+11 | 97121.33 | 02-APR-09:42 | -9.6 |
May | 0.143297E+10 | 68305.17 | 27-MAY-05:01 | 0.10 |
June | 0.203689E+09 | 2575.37 | 02-JUN-07:00 | 9.40 |
July | 0.165554E+09 | 2864.01 | 20-JUL-07:00 | 14.40 |
August | 0.207333E+09 | 2933.10 | 29-AUG-07:00 | 7.80 |
September | 0.216312E+10 | 81086.28 | 25-SEP-05:01 | -1.2 |
October | 0.251119E+11 | 97135.06 | 30-OCT-01:02 | -12.8 |
November | 0.420376E+11 | 97042.66 | 10-NOV-04:02 | -18.9 |
December | 0.559263E+11 | 97943.74 | 09-DEC-02:61 | -24.9 |
Annual Sum or Average | 0.299803E+12 | |||
Minimum of Months | 0.165554E+09 | 2575.37 | -27.0 | |
Maximum of Months | 0.599635E+11 | 100971.73 | 14.40 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238600E+12 | 180945.80 | 28-JAN-14:50 | -20.0 |
February | 0.191390E+12 | 180174.03 | 25-FEB-12:00 | -23.9 |
March | 0.168606E+12 | 171134.50 | 02-MAR-05:00 | -26.7 |
April | 0.671302E+11 | 156328.05 | 02-APR-19:54 | -12.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.188318E+10 | 38267.55 | 30-SEP-05:00 | -4.4 |
October | 0.940096E+11 | 134408.57 | 27-OCT-04:00 | -17.8 |
November | 0.171723E+12 | 144824.79 | 10-NOV-01:51 | -20.0 |
December | 0.234449E+12 | 165888.02 | 22-DEC-14:00 | -23.9 |
Annual Sum or Average | 0.116779E+13 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.238600E+12 | 180945.80 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.258145E+10 | 1955.04 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.235440E+10 | 1955.04 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.269003E+10 | 1955.04 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.254196E+10 | 1955.04 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.263574E+10 | 1955.04 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.259625E+10 | 1955.04 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.258145E+10 | 1955.04 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.269003E+10 | 1955.04 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.254196E+10 | 1955.04 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.258145E+10 | 1955.04 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.248766E+10 | 1955.04 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.258145E+10 | 1955.04 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.308638E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.235440E+10 | 1955.04 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.269003E+10 | 1955.04 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.198922E+11 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.182065E+11 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.210336E+11 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.197108E+11 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.204629E+11 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.202815E+11 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.198922E+11 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.210336E+11 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.197108E+11 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.198922E+11 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.191400E+11 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.198922E+11 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.239148E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.182065E+11 | 17848.24 | 0.00 | 0.00 | |
Maximum of Months | 0.210336E+11 | 17848.24 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.294120E+11 | 26389.90 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.269196E+11 | 26389.90 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.310997E+11 | 26389.90 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.291438E+11 | 26389.90 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.302559E+11 | 26389.90 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.299876E+11 | 26389.90 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.294120E+11 | 26389.90 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.310997E+11 | 26389.90 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.291438E+11 | 26389.90 | 01-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.294120E+11 | 26389.90 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.282999E+11 | 26389.90 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.294120E+11 | 26389.90 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.353598E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.269196E+11 | 26389.90 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.310997E+11 | 26389.90 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.846452E+10 |
February | 0.127628E+10 | 0.235440E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671905E+10 |
March | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.818942E+10 |
April | 0.138726E+10 | 0.254196E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576558E+10 |
May | 0.144276E+10 | 0.263574E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319008E+10 |
June | 0.144276E+10 | 0.259625E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21834762.13 | 0.198821E+10 |
July | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46117732.17 | 0.153502E+10 |
August | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9816635.46 | 0.243071E+10 |
September | 0.138726E+10 | 0.254196E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307029E+10 |
October | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.615304E+10 |
November | 0.133177E+10 | 0.248766E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637986E+10 |
December | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.786624E+10 |
Annual Sum or Average | 0.168137E+11 | 0.308638E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77769129.77 | 0.617520E+11 |
Minimum of Months | 0.127628E+10 | 0.235440E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153502E+10 |
Maximum of Months | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46117732.17 | 0.846452E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180932E+11 |
February | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149818E+11 |
March | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216041E+11 |
April | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194270E+11 |
May | 0.339505E+10 | 0.204629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105182E+11 |
June | 0.339505E+10 | 0.202815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2143639.90 | 0.791506E+10 |
July | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34955576.58 | 0.651964E+10 |
August | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839466E+10 |
September | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.733847E+10 |
October | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169434E+11 |
November | 0.313390E+10 | 0.191400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678003E+10 |
December | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138168E+11 |
Annual Sum or Average | 0.395654E+11 | 0.239148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37099216.48 | 0.152332E+12 |
Minimum of Months | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.651964E+10 |
Maximum of Months | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34955576.58 | 0.216041E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587345E+11 |
February | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479154E+11 |
March | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659836E+11 |
April | 0.750829E+10 | 0.291438E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6758954.72 | 0.496990E+11 |
May | 0.780862E+10 | 0.302559E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151583E+09 | 0.273759E+11 |
June | 0.780862E+10 | 0.299876E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18077832.72 | 0.242128E+11 |
July | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12886532.14 | 0.243513E+11 |
August | 0.810895E+10 | 0.310997E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35296491.45 | 0.289865E+11 |
September | 0.750829E+10 | 0.291438E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212539E+11 |
October | 0.750829E+10 | 0.294120E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28432146.10 | 0.473504E+11 |
November | 0.720796E+10 | 0.282999E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217110E+11 |
December | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474022E+11 |
Annual Sum or Average | 0.910005E+11 | 0.353598E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253035E+09 | 0.464977E+12 |
Minimum of Months | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212539E+11 |
Maximum of Months | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151583E+09 | 0.659836E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1955.04 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 24871.29 | 12-JAN-07:05 |
February | 1680.92 | 01-FEB-08:09 | 1955.04 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 25884.64 | 27-FEB-07:01 |
March | 1680.92 | 01-MAR-08:09 | 1955.04 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 22554.56 | 01-MAR-07:10 |
April | 1680.92 | 01-APR-07:10 | 1955.04 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 19573.92 | 03-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 1955.04 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 9713.65 | 16-MAY-07:00 |
June | 1680.92 | 01-JUN-07:10 | 1955.04 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 923.87 | 29-JUN-16:10 | 5641.00 | 06-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 1955.04 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3058.93 | 21-JUL-16:10 | 5903.55 | 17-JUL-06:03 |
August | 1680.92 | 01-AUG-07:10 | 1955.04 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 839.20 | 11-AUG-16:10 | 10189.28 | 31-AUG-06:05 |
September | 1680.92 | 01-SEP-07:10 | 1955.04 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 11836.24 | 29-SEP-07:00 |
October | 1680.92 | 02-OCT-07:10 | 1955.04 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 19893.42 | 31-OCT-07:00 |
November | 1680.92 | 01-NOV-07:10 | 1955.04 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 22582.36 | 29-NOV-07:55 |
December | 1680.92 | 01-DEC-08:09 | 1955.04 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 24097.26 | 15-DEC-12:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5641.00 | |||||
Maximum of Months | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 3058.93 | 25884.64 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 62877.88 | 28-JAN-17:00 |
February | 3955.50 | 01-FEB-08:09 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 37996.20 | 23-FEB-17:00 |
March | 3955.50 | 01-MAR-08:09 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 28886.69 | 25-MAR-15:10 |
April | 3955.50 | 01-APR-07:10 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 32403.49 | 01-APR-18:51 |
May | 3955.50 | 01-MAY-07:10 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 16697.69 | 27-MAY-08:00 |
June | 3955.50 | 01-JUN-07:10 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 609.25 | 30-JUN-15:10 | 14361.74 | 24-JUN-21:00 |
July | 3955.50 | 01-JUL-07:10 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4975.26 | 21-JUL-16:00 | 9047.69 | 17-JUL-16:00 |
August | 3955.50 | 01-AUG-07:10 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 14433.54 | 29-AUG-20:00 |
September | 3955.50 | 01-SEP-07:10 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 9720.32 | 21-SEP-15:05 |
October | 3955.50 | 02-OCT-07:10 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 21565.34 | 27-OCT-06:10 |
November | 3955.50 | 01-NOV-07:10 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 21115.08 | 03-NOV-20:00 |
December | 3955.50 | 01-DEC-08:09 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 24517.19 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9047.69 | ||||
Maximum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4975.26 | 62877.88 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 26389.90 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 173781.01 | 28-JAN-14:55 |
February | 9097.65 | 01-FEB-08:09 | 26389.90 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 119540.67 | 25-FEB-12:00 |
March | 9097.65 | 01-MAR-08:09 | 26389.90 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 86531.42 | 25-MAR-09:00 |
April | 9097.65 | 01-APR-07:10 | 26389.90 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1313.22 | 17-APR-18:00 | 82545.96 | 01-APR-18:51 |
May | 9097.65 | 01-MAY-07:10 | 26389.90 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8128.79 | 30-MAY-18:00 | 56617.96 | 27-MAY-11:00 |
June | 9097.65 | 01-JUN-07:10 | 26389.90 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1909.87 | 03-JUN-16:00 | 44813.39 | 24-JUN-21:00 |
July | 9097.65 | 01-JUL-07:10 | 26389.90 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2387.80 | 21-JUL-16:00 | 28975.48 | 17-JUL-16:00 |
August | 9097.65 | 01-AUG-07:10 | 26389.90 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4032.34 | 23-AUG-18:00 | 50540.50 | 31-AUG-09:00 |
September | 9097.65 | 01-SEP-07:10 | 26389.90 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 27162.72 | 21-SEP-14:00 |
October | 9097.65 | 02-OCT-07:10 | 26389.90 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3213.70 | 01-OCT-17:00 | 61509.55 | 31-OCT-09:00 |
November | 9097.65 | 01-NOV-07:10 | 26389.90 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 62460.07 | 01-NOV-09:00 |
December | 9097.65 | 01-DEC-08:09 | 26389.90 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 89102.39 | 22-DEC-14:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27162.72 | |||||
Maximum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 8128.79 | 173781.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 3656.18 | 4590.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1985.56 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 2742.13 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1511.84 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 2742.13 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 728.04 |
April | 757.72 | 29-APR-11:00 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2924.37 | 13-MAY-15:00 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.37 |
June | 13338.87 | 21-JUN-17:10 | 0.00 | 1371.07 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 187.38 | 0.00 |
July | 16028.77 | 09-JUL-23:02 | 0.00 | 2285.11 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.29 |
August | 14438.73 | 11-AUG-17:43 | 0.00 | 1371.07 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 218.12 | 0.00 |
September | 3060.74 | 02-SEP-15:00 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.46 |
October | 938.95 | 07-OCT-13:20 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349.93 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 457.02 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1666.85 |
December | 1632.77 | 28-DEC-08:05 | 10085.53 | 11730.24 | 11475.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2955.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 457.02 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16028.77 | 10085.53 | 11730.24 | 11475.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.12 | 2955.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 224.36 | 21-JAN-13:10 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4214.76 | 09-FEB-12:00 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7166.29 | 28-MAR-12:10 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5516.48 | 08-APR-12:40 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4768.88 |
May | 4358.25 | 16-MAY-08:15 | 7911.00 | 35696.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5728.12 |
June | 18452.32 | 21-JUN-18:13 | 0.00 | 6299.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.72 |
July | 22074.65 | 23-JUL-10:53 | 0.00 | 6299.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17598.87 | 02-AUG-17:33 | 0.00 | 6299.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.52 |
September | 5883.97 | 29-SEP-08:70 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.21 |
October | 8035.24 | 27-OCT-13:05 | 7911.00 | 35696.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3034.14 |
November | 2086.65 | 04-NOV-14:00 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 10498.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 6299.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22074.65 | 7911.00 | 35696.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5728.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 24837.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32539.04 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 18628.16 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25576.60 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 18628.16 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12752.09 |
April | 0.00 | 01-APR-00:03 | 0.00 | 9314.08 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44259.07 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 6209.39 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6749.76 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5168.54 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7245.13 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13222.70 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7438.67 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13854.67 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26006.15 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 15523.47 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 24837.55 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44259.07 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.906749E+11 | 71773.65 | 12-JAN-15:30 | 0.434709E+12 | 370082.88 | 28-JAN-17:10 |
February | 0.798447E+11 | 70760.97 | 02-FEB-09:09 | 0.350481E+12 | 353100.69 | 24-FEB-06:19 |
March | 0.880739E+11 | 65508.40 | 13-MAR-07:10 | 0.316802E+12 | 300422.92 | 04-MAR-06:00 |
April | 0.787268E+11 | 63241.30 | 15-APR-14:00 | 0.140396E+12 | 285731.68 | 02-APR-19:49 |
May | 0.773368E+11 | 63765.88 | 13-MAY-14:39 | 0.183622E+11 | 44855.40 | 27-MAY-05:10 |
June | 0.756497E+11 | 70096.31 | 30-JUN-12:00 | 0.137946E+11 | 15073.93 | 02-JUN-06:10 |
July | 0.767815E+11 | 71144.17 | 29-JUL-14:00 | 0.141061E+11 | 11445.42 | 05-JUL-06:10 |
August | 0.824464E+11 | 69051.95 | 04-AUG-14:20 | 0.144303E+11 | 23553.95 | 31-AUG-06:10 |
September | 0.793472E+11 | 63159.05 | 02-SEP-14:09 | 0.225722E+11 | 85479.82 | 30-SEP-05:30 |
October | 0.849558E+11 | 70742.97 | 31-OCT-08:30 | 0.184463E+12 | 256946.66 | 31-OCT-05:10 |
November | 0.857491E+11 | 71624.30 | 29-NOV-15:00 | 0.321780E+12 | 273239.38 | 29-NOV-07:00 |
December | 0.918248E+11 | 71773.77 | 30-DEC-15:39 | 0.425620E+12 | 290283.93 | 01-DEC-17:00 |
Annual Sum or Average | 0.991412E+12 | 0.225752E+13 | ||||
Minimum of Months | 0.756497E+11 | 63159.05 | 0.137946E+11 | 11445.42 | ||
Maximum of Months | 0.918248E+11 | 71773.77 | 0.434709E+12 | 370082.88 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.518856E+11 | 0.183579E+11 | 0.115358E+11 | 0.00 | 0.639049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250505E+10 | 0.00 |
February | 0.474804E+11 | 0.137352E+11 | 0.105871E+11 | 0.00 | 0.576315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227883E+10 | 0.00 |
March | 0.548234E+11 | 0.119844E+11 | 0.123431E+11 | 0.00 | 0.634168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258144E+10 | 0.00 |
April | 0.513965E+11 | 0.843666E+10 | 0.114862E+11 | 0.00 | 0.495365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245377E+10 | 0.00 |
May | 0.533545E+11 | 0.551352E+10 | 0.119357E+11 | 0.00 | 0.394210E+10 | 0.00 | 0.00 | 64248235.60 | 0.00 | 0.00 | 0.00 | 0.252666E+10 | 0.00 |
June | 0.528654E+11 | 0.307160E+10 | 0.118862E+11 | 0.00 | 0.392005E+10 | 0.00 | 0.00 | 0.148163E+10 | 0.00 | 0.00 | 0.00 | 0.242488E+10 | 0.00 |
July | 0.518856E+11 | 0.426952E+10 | 0.115358E+11 | 0.00 | 0.381697E+10 | 0.00 | 0.00 | 0.287729E+10 | 0.00 | 0.00 | 0.00 | 0.239629E+10 | 0.00 |
August | 0.548234E+11 | 0.736672E+10 | 0.123357E+11 | 0.00 | 0.407368E+10 | 0.00 | 0.00 | 0.140285E+10 | 0.00 | 0.00 | 0.00 | 0.244409E+10 | 0.00 |
September | 0.513965E+11 | 0.102438E+11 | 0.114788E+11 | 0.00 | 0.385893E+10 | 0.00 | 0.00 | 33637864.15 | 0.00 | 0.00 | 0.00 | 0.233553E+10 | 0.00 |
October | 0.518856E+11 | 0.138171E+11 | 0.115432E+11 | 0.00 | 0.529930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241067E+10 | 0.00 |
November | 0.499276E+11 | 0.165713E+11 | 0.110862E+11 | 0.00 | 0.580339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236062E+10 | 0.00 |
December | 0.518856E+11 | 0.196582E+11 | 0.115358E+11 | 0.00 | 0.625779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248732E+10 | 0.00 |
Annual Sum or Average | 0.623610E+12 | 0.133026E+12 | 0.139290E+12 | 0.00 | 0.604212E+11 | 0.00 | 0.00 | 0.585966E+10 | 0.00 | 0.00 | 0.00 | 0.292051E+11 | 0.00 |
Minimum of Months | 0.474804E+11 | 0.307160E+10 | 0.105871E+11 | 0.00 | 0.381697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227883E+10 | 0.00 |
Maximum of Months | 0.548234E+11 | 0.196582E+11 | 0.123431E+11 | 0.00 | 0.639049E+10 | 0.00 | 0.00 | 0.287729E+10 | 0.00 | 0.00 | 0.00 | 0.258144E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.434709E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.350481E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.316802E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.140396E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.183622E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.137946E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.141061E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.144303E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.225722E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.184463E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.321780E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.425620E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.225752E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.137946E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.434709E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 46193.18 | 02-JAN-09:09 | 8532.22 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 4186.30 | 02-JAN-13:39 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 46193.18 | 01-FEB-09:09 | 8532.22 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 4186.30 | 01-FEB-08:20 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 46193.18 | 01-MAR-09:09 | 8532.22 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 4186.30 | 01-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 46193.18 | 01-APR-08:09 | 8532.22 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 4186.30 | 01-APR-06:40 | 0.00 | 0.00 | 01-APR-00:10 |
May | 46193.18 | 01-MAY-08:09 | 8532.22 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 3773.62 | 27-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 46193.18 | 01-JUN-08:09 | 8532.22 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 3773.62 | 03-JUN-14:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 46193.18 | 01-JUL-08:09 | 8532.22 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 3773.62 | 03-JUL-15:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 46193.18 | 01-AUG-08:09 | 8532.22 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 3773.62 | 02-AUG-15:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 46193.18 | 01-SEP-08:09 | 8532.22 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 4186.30 | 29-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 46193.18 | 02-OCT-08:09 | 8532.22 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 4186.30 | 10-OCT-07:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 46193.18 | 01-NOV-08:09 | 8532.22 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 4186.30 | 01-NOV-11:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 46193.18 | 01-DEC-09:09 | 8532.22 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 4186.30 | 01-DEC-10:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 46193.18 | 8532.22 | 10112.62 | 0.00 | 3773.62 | 0.00 | 0.00 | |||||
Maximum of Months | 46193.18 | 8532.22 | 10112.62 | 0.00 | 4186.30 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 3179.36 | 13-JAN-12:39 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 3176.60 | 04-FEB-12:20 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 3176.54 | 01-MAR-12:39 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 3176.58 | 21-APR-11:39 | 0.00 |
May | 1043.88 | 13-MAY-14:00 | 0.00 | 0.00 | 0.00 | 3176.51 | 05-MAY-11:39 | 0.00 |
June | 7979.76 | 30-JUN-14:50 | 0.00 | 0.00 | 0.00 | 3072.06 | 03-JUN-11:50 | 0.00 |
July | 9989.70 | 21-JUL-15:00 | 0.00 | 0.00 | 0.00 | 2927.82 | 05-JUL-11:50 | 0.00 |
August | 6676.04 | 04-AUG-14:30 | 0.00 | 0.00 | 0.00 | 2812.29 | 02-AUG-11:30 | 0.00 |
September | 978.03 | 02-SEP-14:00 | 0.00 | 0.00 | 0.00 | 2796.55 | 28-SEP-11:39 | 0.00 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 2904.46 | 30-OCT-11:39 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 3048.14 | 30-NOV-12:20 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 3175.52 | 28-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2796.55 | 0.00 | ||
Maximum of Months | 9989.70 | 0.00 | 0.00 | 0.00 | 3179.36 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 71773.65 | 12-JAN-15:30 | 46193.18 | 10112.62 | 8532.22 | 0.00 | 4186.30 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 70760.97 | 02-FEB-09:09 | 46193.18 | 10112.62 | 8532.22 | 0.00 | 4186.30 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 65508.40 | 13-MAR-07:10 | 40988.70 | 10112.62 | 8532.22 | 0.00 | 4186.30 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 63241.30 | 15-APR-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 4186.30 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 63765.88 | 13-MAY-14:39 | 46193.18 | 10112.62 | 0.00 | 0.00 | 3773.62 | 0.00 | 0.00 | 1005.64 | 0.00 |
June | 70096.31 | 30-JUN-12:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 3773.62 | 0.00 | 0.00 | 7531.23 | 0.00 |
July | 71144.17 | 29-JUL-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 3773.62 | 0.00 | 0.00 | 9210.16 | 0.00 |
August | 69051.95 | 04-AUG-14:20 | 46193.18 | 10112.62 | 0.00 | 0.00 | 3773.62 | 0.00 | 0.00 | 6637.20 | 0.00 |
September | 63159.05 | 02-SEP-14:09 | 46193.18 | 10112.62 | 0.00 | 0.00 | 3773.62 | 0.00 | 0.00 | 855.73 | 0.00 |
October | 70742.97 | 31-OCT-08:30 | 46193.18 | 10112.62 | 8532.22 | 0.00 | 4186.30 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 71624.30 | 29-NOV-15:00 | 46193.18 | 10112.62 | 8532.22 | 0.00 | 4186.30 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71773.77 | 30-DEC-15:39 | 46193.18 | 10112.62 | 8532.22 | 0.00 | 4186.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 63159.05 | 40988.70 | 10112.62 | 0.00 | 0.00 | 3773.62 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 71773.77 | 46193.18 | 10112.62 | 8532.22 | 0.00 | 4186.30 | 0.00 | 0.00 | 9210.16 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 370082.88 | 28-JAN-17:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 353100.69 | 24-FEB-06:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 300422.92 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 285731.68 | 02-APR-19:49 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 44855.40 | 27-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 15073.93 | 02-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 11445.42 | 05-JUL-06:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 23553.95 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 85479.82 | 30-SEP-05:30 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 256946.66 | 31-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 273239.38 | 29-NOV-07:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 290283.93 | 01-DEC-17:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 11445.42 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 370082.88 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 90.00 | 15.87 | 25.83 | 16.53 | 0.00 | 16.53 | 0.00 | 16.53 |
February | 81.00 | 15.68 | 19.17 | 16.29 | 0.00 | 16.29 | 0.00 | 16.29 |
March | 79.00 | 16.00 | 22.50 | 16.69 | 0.00 | 16.69 | 0.00 | 16.69 |
April | 33.17 | 16.09 | 10.67 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 |
May | 4.67 | 20.08 | 4.67 | 20.08 | 0.00 | 20.08 | 0.00 | 20.08 |
June | 0.17 | 20.43 | 0.17 | 20.43 | 5.17 | 24.26 | 0.00 | 24.26 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 24.54 | 0.50 | 24.54 |
August | 0.33 | 20.37 | 0.33 | 20.37 | 4.17 | 23.95 | 0.17 | 23.97 |
September | 4.17 | 19.98 | 4.17 | 19.98 | 0.00 | 19.98 | 0.00 | 19.98 |
October | 24.83 | 16.43 | 8.50 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
November | 34.50 | 16.57 | 13.17 | 17.32 | 0.00 | 17.32 | 0.00 | 17.32 |
December | 77.33 | 16.18 | 23.33 | 16.89 | 0.00 | 16.89 | 0.00 | 16.89 |
Annual Sum or Average | 429.17 | 16.11 | 132.50 | 16.82 | 22.50 | 17.12 | 0.67 | 17.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.29 | 0.00 | 16.29 |
Maximum of Months | 90.00 | 20.43 | 25.83 | 20.43 | 13.17 | 24.54 | 0.50 | 24.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 118.17 | 13.69 | 4.50 | 13.69 | 0.00 | 13.69 | 0.00 | 13.69 |
February | 104.83 | 13.76 | 4.50 | 13.76 | 0.00 | 13.76 | 0.00 | 13.76 |
March | 106.67 | 13.89 | 5.00 | 13.88 | 0.00 | 13.88 | 0.00 | 13.88 |
April | 67.00 | 14.20 | 4.83 | 14.20 | 0.00 | 14.20 | 0.00 | 14.20 |
May | 3.17 | 14.90 | 0.17 | 14.91 | 0.00 | 14.91 | 0.00 | 14.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.00 | 27.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.31 | 0.00 | 27.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8.83 | 14.82 | 1.00 | 14.82 | 0.00 | 14.82 | 0.00 | 14.82 |
October | 87.00 | 14.34 | 3.50 | 14.34 | 0.00 | 14.34 | 0.00 | 14.34 |
November | 112.17 | 14.06 | 4.17 | 14.05 | 0.00 | 14.05 | 0.00 | 14.05 |
December | 115.17 | 13.80 | 4.17 | 13.80 | 0.00 | 13.80 | 0.00 | 13.80 |
Annual Sum or Average | 723.00 | 13.95 | 31.83 | 13.95 | 0.83 | 13.96 | 0.00 | 13.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.17 | 14.90 | 5.00 | 14.91 | 0.67 | 27.31 | 0.00 | 27.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.67 | 7.33 | 9.00 | 7.33 | 0.00 | 7.33 | 0.00 | 7.33 |
February | 17.83 | 9.14 | 4.67 | 9.13 | 0.00 | 9.13 | 0.00 | 9.13 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44.50 | 8.06 | 13.67 | 8.02 | 0.00 | 8.02 | 0.00 | 8.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 26.67 | 9.14 | 9.00 | 9.13 | 0.00 | 9.13 | 0.00 | 9.13 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.89 | 300.00 | 20.89 | 300.00 | 20.89 |
February | 276.00 | 20.93 | 276.00 | 20.93 | 276.00 | 20.93 |
March | 324.00 | 20.95 | 324.00 | 20.95 | 324.00 | 20.95 |
April | 300.00 | 21.11 | 288.33 | 21.08 | 288.33 | 21.07 |
May | 312.00 | 22.10 | 160.33 | 21.78 | 160.33 | 21.63 |
June | 212.17 | 23.34 | 17.83 | 23.33 | 4.33 | 23.29 |
July | 77.67 | 23.18 | 96.50 | 23.58 | 0.00 | 23.58 |
August | 184.67 | 23.02 | 57.17 | 23.11 | 10.67 | 23.02 |
September | 300.00 | 21.76 | 168.67 | 21.52 | 168.67 | 21.41 |
October | 300.00 | 21.05 | 300.00 | 21.05 | 300.00 | 21.05 |
November | 288.00 | 21.00 | 288.00 | 21.00 | 288.00 | 21.00 |
December | 300.00 | 20.94 | 300.00 | 20.94 | 300.00 | 20.94 |
Annual Sum or Average | 3174.50 | 21.50 | 2576.83 | 21.35 | 2420.33 | 21.25 |
Minimum of Months | 77.67 | 20.89 | 17.83 | 20.89 | 0.00 | 20.89 |
Maximum of Months | 324.00 | 23.34 | 324.00 | 23.58 | 324.00 | 23.58 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.53 | 300.00 | 15.53 | 300.00 | 15.53 |
February | 276.00 | 15.53 | 276.00 | 15.53 | 276.00 | 15.53 |
March | 324.00 | 15.63 | 324.00 | 15.63 | 324.00 | 15.63 |
April | 300.00 | 17.14 | 296.50 | 17.12 | 296.50 | 17.11 |
May | 305.50 | 20.76 | 165.17 | 20.12 | 165.17 | 19.81 |
June | 86.83 | 23.04 | 205.17 | 25.28 | 10.33 | 25.18 |
July | 61.83 | 24.93 | 254.33 | 26.18 | 31.17 | 26.22 |
August | 117.50 | 22.81 | 203.67 | 24.74 | 22.67 | 24.57 |
September | 298.67 | 19.48 | 206.33 | 18.96 | 206.33 | 18.74 |
October | 300.00 | 16.06 | 300.00 | 16.06 | 300.00 | 16.06 |
November | 288.00 | 15.54 | 288.00 | 15.54 | 288.00 | 15.54 |
December | 300.00 | 15.53 | 300.00 | 15.53 | 300.00 | 15.53 |
Annual Sum or Average | 2958.33 | 17.40 | 3119.17 | 17.90 | 2520.17 | 17.47 |
Minimum of Months | 61.83 | 15.53 | 165.17 | 15.53 | 10.33 | 15.53 |
Maximum of Months | 324.00 | 24.93 | 324.00 | 26.18 | 324.00 | 26.22 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 9.92 | 300.00 | 9.92 | 300.00 | 9.92 |
February | 276.00 | 9.98 | 276.00 | 9.98 | 276.00 | 9.98 |
March | 324.00 | 10.14 | 324.00 | 10.14 | 324.00 | 10.14 |
April | 300.00 | 11.74 | 300.00 | 11.74 | 300.00 | 11.74 |
May | 312.00 | 17.23 | 310.00 | 17.21 | 310.00 | 17.21 |
June | 208.67 | 22.02 | 108.00 | 22.43 | 47.33 | 22.04 |
July | 109.00 | 25.33 | 213.33 | 26.14 | 53.50 | 26.40 |
August | 221.33 | 22.16 | 136.00 | 22.84 | 63.17 | 22.65 |
September | 300.00 | 15.88 | 293.83 | 15.82 | 293.83 | 15.80 |
October | 300.00 | 10.53 | 300.00 | 10.53 | 300.00 | 10.53 |
November | 288.00 | 10.00 | 288.00 | 10.00 | 288.00 | 10.00 |
December | 300.00 | 10.00 | 300.00 | 10.00 | 300.00 | 10.00 |
Annual Sum or Average | 3239.00 | 13.58 | 3149.17 | 13.61 | 2855.83 | 13.23 |
Minimum of Months | 109.00 | 9.92 | 108.00 | 9.92 | 47.33 | 9.92 |
Maximum of Months | 324.00 | 25.33 | 324.00 | 26.14 | 324.00 | 26.40 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 |
May | 0.212305E+09 | 64248235.60 | 38.92 | 0.212305E+09 | 0.00 | 0.00 | 0.25 | 13-MAY-15:00 | 0.00 | 01-MAY-00:05 | 3502.99 | 13-MAY-15:00 | 3502.99 | 13-MAY-15:00 | 0.00 | 12-MAY-14:10 | 1043.88 | 13-MAY-15:00 | 0.00 | 01-MAY-00:05 |
June | 0.337873E+10 | 0.100183E+10 | 259.00 | 0.325454E+10 | 0.124189E+09 | 0.00 | 0.96 | 21-JUN-17:10 | 0.00 | 01-JUN-00:10 | 15400.29 | 21-JUN-17:10 | 15400.29 | 21-JUN-17:10 | 1604.45 | 30-JUN-18:35 | 4252.73 | 21-JUN-17:10 | 0.00 | 01-JUN-00:10 |
July | 0.524748E+10 | 0.154238E+10 | 314.63 | 0.485801E+10 | 0.389475E+09 | 0.00 | 1.00 | 09-JUL-23:02 | 0.00 | 01-JUL-00:10 | 17502.10 | 23-JUL-23:02 | 16523.38 | 11-JUL-19:43 | 2388.48 | 23-JUL-23:03 | 4745.22 | 29-JUL-17:10 | 0.00 | 01-JUL-00:10 |
August | 0.342054E+10 | 0.100746E+10 | 256.19 | 0.319810E+10 | 0.222444E+09 | 0.00 | 1.00 | 11-AUG-17:43 | 0.00 | 01-AUG-00:10 | 16246.15 | 11-AUG-17:43 | 16246.15 | 11-AUG-17:43 | 1185.36 | 03-AUG-13:00 | 4417.46 | 11-AUG-17:43 | 0.00 | 01-AUG-00:10 |
September | 0.110627E+09 | 33637864.15 | 24.75 | 0.108707E+09 | 1919773.88 | 0.00 | 0.23 | 02-SEP-15:00 | 0.00 | 01-SEP-00:10 | 3268.54 | 02-SEP-15:00 | 3158.13 | 02-SEP-15:00 | 112.42 | 02-SEP-14:40 | 978.03 | 02-SEP-15:00 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.123697E+11 | 0.364955E+10 | 893.49 | 0.116317E+11 | 0.738028E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.524748E+10 | 0.154238E+10 | 314.63 | 0.485801E+10 | 0.389475E+09 | 0.00 | 1.00 | 0.00 | 17502.10 | 16523.38 | 2388.48 | 4745.22 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 |
June | 0.168444E+10 | 0.479802E+09 | 43.22 | 0.164471E+10 | 39722559.70 | 0.00 | 0.49 | 21-JUN-18:13 | 0.00 | 01-JUN-00:10 | 20471.79 | 21-JUN-18:13 | 20471.79 | 21-JUN-18:13 | 2174.14 | 30-JUN-11:30 | 5722.57 | 21-JUN-18:13 | 0.00 | 01-JUN-00:10 |
July | 0.470448E+10 | 0.133491E+10 | 103.22 | 0.459797E+10 | 0.106500E+09 | 0.00 | 0.57 | 21-JUL-16:00 | 0.00 | 01-JUL-00:10 | 24702.99 | 23-JUL-10:53 | 24480.43 | 23-JUL-10:53 | 1749.72 | 24-JUL-15:00 | 6855.94 | 21-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 0.139904E+10 | 0.395395E+09 | 40.39 | 0.136161E+10 | 37439873.84 | 0.00 | 0.45 | 02-AUG-17:33 | 0.00 | 01-AUG-00:10 | 19390.39 | 02-AUG-17:33 | 19390.39 | 02-AUG-17:33 | 1969.26 | 04-AUG-11:20 | 5301.64 | 02-AUG-17:33 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.778796E+10 | 0.221010E+10 | 186.83 | 0.760429E+10 | 0.183663E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.470448E+10 | 0.133491E+10 | 103.22 | 0.459797E+10 | 0.106500E+09 | 0.00 | 0.57 | 0.00 | 24702.99 | 24480.43 | 2174.14 | 6855.94 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5.56 | 0.97 | 4.59 | 0.00 | 379.61 | 0.00 | 0.00 | 0.00 |
February | 33.06 | 11.58 | 21.48 | 4.18 | 322.72 | 0.00 | 0.00 | 0.00 |
March | 99.38 | 43.04 | 56.34 | 50.10 | 230.76 | 0.00 | 0.00 | 0.00 |
April | 234.44 | 121.54 | 112.90 | 222.67 | 117.94 | 0.00 | 0.00 | 0.00 |
May | 227.68 | 103.72 | 123.95 | 234.70 | 53.60 | 0.00 | 0.00 | 0.00 |
June | 249.64 | 106.55 | 143.09 | 267.43 | 35.79 | 0.00 | 0.00 | 0.00 |
July | 208.63 | 78.86 | 129.76 | 221.36 | 43.27 | 0.00 | 0.00 | 0.00 |
August | 171.99 | 73.08 | 98.90 | 169.32 | 64.22 | 0.00 | 0.00 | 0.00 |
September | 103.64 | 43.26 | 60.38 | 79.68 | 103.51 | 0.00 | 0.00 | 0.00 |
October | 40.59 | 12.15 | 28.43 | 13.12 | 199.72 | 0.00 | 0.00 | 0.00 |
November | 16.27 | 5.89 | 10.38 | 0.83 | 364.78 | 0.00 | 0.00 | 0.00 |
December | 1.46 | 0.16 | 1.31 | 0.00 | 405.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.33 | 50.17 | 66.15 | 105.70 | 192.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1.46 | 0.16 | 1.31 | 0.00 | 35.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 249.64 | 121.54 | 143.09 | 267.43 | 405.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5.56 | 0.97 | 4.59 | 0.00 | 379.61 | 0.00 | 0.00 | 0.00 |
February | 33.06 | 11.58 | 21.48 | 4.18 | 322.72 | 0.00 | 0.00 | 0.00 |
March | 99.38 | 43.04 | 56.34 | 50.10 | 230.76 | 0.00 | 0.00 | 0.00 |
April | 234.44 | 121.54 | 112.90 | 222.67 | 117.94 | 0.00 | 0.00 | 0.00 |
May | 227.68 | 103.72 | 123.95 | 234.70 | 53.60 | 0.00 | 0.00 | 0.00 |
June | 249.64 | 106.55 | 143.09 | 267.43 | 35.79 | 0.00 | 0.00 | 0.00 |
July | 208.63 | 78.86 | 129.76 | 221.36 | 43.27 | 0.00 | 0.00 | 0.00 |
August | 171.99 | 73.08 | 98.90 | 169.32 | 64.22 | 0.00 | 0.00 | 0.00 |
September | 103.64 | 43.26 | 60.38 | 79.68 | 103.51 | 0.00 | 0.00 | 0.00 |
October | 40.59 | 12.15 | 28.43 | 13.12 | 199.72 | 0.00 | 0.00 | 0.00 |
November | 16.27 | 5.89 | 10.38 | 0.83 | 364.78 | 0.00 | 0.00 | 0.00 |
December | 1.46 | 0.16 | 1.31 | 0.00 | 405.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.33 | 50.17 | 66.15 | 105.70 | 192.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1.46 | 0.16 | 1.31 | 0.00 | 35.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 249.64 | 121.54 | 143.09 | 267.43 | 405.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.34 | 0.00 | 2.34 | 0.00 | 224.26 | 0.00 | 0.00 | 0.00 |
February | 10.36 | 0.00 | 10.36 | 0.00 | 200.85 | 0.00 | 0.00 | 0.00 |
March | 27.79 | 0.01 | 27.78 | 1.20 | 149.47 | 0.00 | 0.00 | 0.00 |
April | 50.56 | 1.41 | 49.15 | 18.18 | 72.36 | 0.00 | 0.00 | 0.00 |
May | 77.50 | 12.52 | 64.99 | 60.40 | 27.09 | 0.00 | 0.00 | 0.00 |
June | 99.92 | 21.93 | 77.99 | 91.28 | 15.38 | 0.00 | 0.00 | 0.00 |
July | 84.33 | 13.88 | 70.45 | 76.13 | 21.04 | 0.00 | 0.00 | 0.00 |
August | 54.18 | 2.93 | 51.25 | 35.62 | 35.35 | 0.00 | 0.00 | 0.00 |
September | 30.14 | 0.09 | 30.05 | 8.54 | 64.02 | 0.00 | 0.00 | 0.00 |
October | 14.58 | 0.00 | 14.58 | 0.76 | 123.69 | 0.00 | 0.00 | 0.00 |
November | 4.53 | 0.00 | 4.53 | 0.00 | 220.81 | 0.00 | 0.00 | 0.00 |
December | 0.71 | 0.00 | 0.71 | 0.00 | 237.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.22 | 4.42 | 33.80 | 24.49 | 115.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.71 | 0.00 | 0.71 | 0.00 | 15.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 99.92 | 21.93 | 77.99 | 91.28 | 237.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.34 | 0.00 | 2.34 | 0.00 | 224.26 | 0.00 | 0.00 | 0.00 |
February | 10.36 | 0.00 | 10.36 | 0.00 | 200.85 | 0.00 | 0.00 | 0.00 |
March | 27.79 | 0.01 | 27.78 | 1.20 | 149.47 | 0.00 | 0.00 | 0.00 |
April | 50.56 | 1.41 | 49.15 | 18.18 | 72.36 | 0.00 | 0.00 | 0.00 |
May | 77.50 | 12.52 | 64.98 | 60.39 | 27.09 | 0.00 | 0.00 | 0.00 |
June | 99.92 | 21.93 | 77.99 | 91.27 | 15.38 | 0.00 | 0.00 | 0.00 |
July | 84.33 | 13.88 | 70.45 | 76.12 | 21.04 | 0.00 | 0.00 | 0.00 |
August | 54.18 | 2.93 | 51.25 | 35.62 | 35.35 | 0.00 | 0.00 | 0.00 |
September | 30.14 | 0.09 | 30.05 | 8.54 | 64.02 | 0.00 | 0.00 | 0.00 |
October | 14.58 | 0.00 | 14.58 | 0.76 | 123.69 | 0.00 | 0.00 | 0.00 |
November | 4.53 | 0.00 | 4.53 | 0.00 | 220.81 | 0.00 | 0.00 | 0.00 |
December | 0.71 | 0.00 | 0.71 | 0.00 | 237.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.22 | 4.42 | 33.80 | 24.48 | 115.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.71 | 0.00 | 0.71 | 0.00 | 15.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 99.92 | 21.93 | 77.99 | 91.27 | 237.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.37 | 0.23 | 2.14 | 0.00 | 210.69 | 0.00 | 0.00 | 0.00 |
February | 12.07 | 3.07 | 9.00 | 0.01 | 182.19 | 3.17 | 0.00 | 0.00 |
March | 42.17 | 18.13 | 24.04 | 25.25 | 119.73 | 0.00 | 0.00 | 0.00 |
April | 84.36 | 45.62 | 38.74 | 95.05 | 60.84 | 0.00 | 0.00 | 0.00 |
May | 109.71 | 62.40 | 47.30 | 136.58 | 32.19 | 0.00 | 0.00 | 0.00 |
June | 118.93 | 59.23 | 59.70 | 144.74 | 24.60 | 0.00 | 0.00 | 0.00 |
July | 106.72 | 51.56 | 55.16 | 125.76 | 32.17 | 0.00 | 0.00 | 0.00 |
August | 80.47 | 39.07 | 41.40 | 89.57 | 41.99 | 0.00 | 0.00 | 0.00 |
September | 43.65 | 17.41 | 26.24 | 40.97 | 52.44 | 1.00 | 0.00 | 0.00 |
October | 17.99 | 4.48 | 13.51 | 8.06 | 92.19 | 10.83 | 0.00 | 0.00 |
November | 4.50 | 0.40 | 4.10 | 0.00 | 206.57 | 0.00 | 0.00 | 0.00 |
December | 0.66 | 0.01 | 0.65 | 0.00 | 225.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.17 | 25.26 | 26.92 | 55.79 | 106.34 | 15.00 | 0.00 | 0.00 |
Minimum of Months | 0.66 | 0.01 | 0.65 | 0.00 | 24.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.93 | 62.40 | 59.70 | 144.74 | 225.24 | 10.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.37 | 0.23 | 2.14 | 0.00 | 210.69 | 0.00 | 0.00 | 0.00 |
February | 12.07 | 3.07 | 9.00 | 0.01 | 182.19 | 3.17 | 0.00 | 0.00 |
March | 42.17 | 18.13 | 24.04 | 25.25 | 119.73 | 0.00 | 0.00 | 0.00 |
April | 84.36 | 45.62 | 38.74 | 95.05 | 60.84 | 0.00 | 0.00 | 0.00 |
May | 109.71 | 62.40 | 47.30 | 136.58 | 32.19 | 0.00 | 0.00 | 0.00 |
June | 118.93 | 59.23 | 59.70 | 144.74 | 24.60 | 0.00 | 0.00 | 0.00 |
July | 106.72 | 51.56 | 55.16 | 125.76 | 32.17 | 0.00 | 0.00 | 0.00 |
August | 80.47 | 39.07 | 41.40 | 89.57 | 41.99 | 0.00 | 0.00 | 0.00 |
September | 43.65 | 17.41 | 26.24 | 40.97 | 52.44 | 1.00 | 0.00 | 0.00 |
October | 17.99 | 4.48 | 13.51 | 8.06 | 92.19 | 10.83 | 0.00 | 0.00 |
November | 4.50 | 0.40 | 4.10 | 0.00 | 206.57 | 0.00 | 0.00 | 0.00 |
December | 0.66 | 0.01 | 0.65 | 0.00 | 225.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.17 | 25.26 | 26.92 | 55.79 | 106.34 | 15.00 | 0.00 | 0.00 |
Minimum of Months | 0.66 | 0.01 | 0.65 | 0.00 | 24.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.93 | 62.40 | 59.70 | 144.74 | 225.24 | 10.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.37 | 0.23 | 2.14 | 0.00 | 210.69 | 0.00 | 0.00 | 0.00 |
February | 12.07 | 3.07 | 9.00 | 0.01 | 182.19 | 3.17 | 0.00 | 0.00 |
March | 42.17 | 18.13 | 24.04 | 25.25 | 119.73 | 0.00 | 0.00 | 0.00 |
April | 84.36 | 45.62 | 38.74 | 95.05 | 60.84 | 0.00 | 0.00 | 0.00 |
May | 109.71 | 62.40 | 47.30 | 136.58 | 32.19 | 0.00 | 0.00 | 0.00 |
June | 118.93 | 59.23 | 59.70 | 144.74 | 24.60 | 0.00 | 0.00 | 0.00 |
July | 106.72 | 51.56 | 55.16 | 125.76 | 32.17 | 0.00 | 0.00 | 0.00 |
August | 80.47 | 39.07 | 41.40 | 89.57 | 41.99 | 0.00 | 0.00 | 0.00 |
September | 43.65 | 17.41 | 26.24 | 40.97 | 52.44 | 1.00 | 0.00 | 0.00 |
October | 17.99 | 4.48 | 13.51 | 8.06 | 92.19 | 10.83 | 0.00 | 0.00 |
November | 4.50 | 0.40 | 4.10 | 0.00 | 206.57 | 0.00 | 0.00 | 0.00 |
December | 0.66 | 0.01 | 0.65 | 0.00 | 225.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.17 | 25.26 | 26.92 | 55.79 | 106.34 | 15.00 | 0.00 | 0.00 |
Minimum of Months | 0.66 | 0.01 | 0.65 | 0.00 | 24.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.93 | 62.40 | 59.70 | 144.74 | 225.24 | 10.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.37 | 0.23 | 2.14 | 0.00 | 210.69 | 0.00 | 0.00 | 0.00 |
February | 12.07 | 3.07 | 9.00 | 0.01 | 182.19 | 3.17 | 0.00 | 0.00 |
March | 42.17 | 18.13 | 24.04 | 25.25 | 119.73 | 0.00 | 0.00 | 0.00 |
April | 84.36 | 45.62 | 38.74 | 95.05 | 60.84 | 0.00 | 0.00 | 0.00 |
May | 109.71 | 62.40 | 47.30 | 136.58 | 32.19 | 0.00 | 0.00 | 0.00 |
June | 118.93 | 59.23 | 59.70 | 144.74 | 24.60 | 0.00 | 0.00 | 0.00 |
July | 106.72 | 51.56 | 55.16 | 125.76 | 32.17 | 0.00 | 0.00 | 0.00 |
August | 80.47 | 39.07 | 41.40 | 89.57 | 41.99 | 0.00 | 0.00 | 0.00 |
September | 43.65 | 17.41 | 26.24 | 40.97 | 52.44 | 1.00 | 0.00 | 0.00 |
October | 17.99 | 4.48 | 13.51 | 8.06 | 92.19 | 10.83 | 0.00 | 0.00 |
November | 4.50 | 0.40 | 4.10 | 0.00 | 206.57 | 0.00 | 0.00 | 0.00 |
December | 0.66 | 0.01 | 0.65 | 0.00 | 225.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.17 | 25.26 | 26.92 | 55.79 | 106.34 | 15.00 | 0.00 | 0.00 |
Minimum of Months | 0.66 | 0.01 | 0.65 | 0.00 | 24.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.93 | 62.40 | 59.70 | 144.74 | 225.24 | 10.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.37 | 0.23 | 2.14 | 0.00 | 210.69 | 0.00 | 0.00 | 0.00 |
February | 12.07 | 3.07 | 9.00 | 0.01 | 182.19 | 3.17 | 0.00 | 0.00 |
March | 42.17 | 18.13 | 24.04 | 25.25 | 119.73 | 0.00 | 0.00 | 0.00 |
April | 84.36 | 45.62 | 38.74 | 95.05 | 60.84 | 0.00 | 0.00 | 0.00 |
May | 109.71 | 62.40 | 47.30 | 136.58 | 32.19 | 0.00 | 0.00 | 0.00 |
June | 118.93 | 59.23 | 59.70 | 144.74 | 24.60 | 0.00 | 0.00 | 0.00 |
July | 106.72 | 51.56 | 55.16 | 125.76 | 32.17 | 0.00 | 0.00 | 0.00 |
August | 80.47 | 39.07 | 41.40 | 89.57 | 41.99 | 0.00 | 0.00 | 0.00 |
September | 43.65 | 17.41 | 26.24 | 40.97 | 52.44 | 1.00 | 0.00 | 0.00 |
October | 17.99 | 4.48 | 13.51 | 8.06 | 92.19 | 10.83 | 0.00 | 0.00 |
November | 4.50 | 0.40 | 4.10 | 0.00 | 206.57 | 0.00 | 0.00 | 0.00 |
December | 0.66 | 0.01 | 0.65 | 0.00 | 225.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.17 | 25.26 | 26.92 | 55.79 | 106.34 | 15.00 | 0.00 | 0.00 |
Minimum of Months | 0.66 | 0.01 | 0.65 | 0.00 | 24.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.93 | 62.40 | 59.70 | 144.74 | 225.24 | 10.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.37 | 0.23 | 2.14 | 0.00 | 210.69 | 0.00 | 0.00 | 0.00 |
February | 12.07 | 3.07 | 9.00 | 0.01 | 182.19 | 3.17 | 0.00 | 0.00 |
March | 42.17 | 18.13 | 24.04 | 25.25 | 119.73 | 0.00 | 0.00 | 0.00 |
April | 84.36 | 45.62 | 38.74 | 95.05 | 60.84 | 0.00 | 0.00 | 0.00 |
May | 109.71 | 62.40 | 47.30 | 136.58 | 32.19 | 0.00 | 0.00 | 0.00 |
June | 118.93 | 59.23 | 59.70 | 144.74 | 24.60 | 0.00 | 0.00 | 0.00 |
July | 106.72 | 51.56 | 55.16 | 125.76 | 32.17 | 0.00 | 0.00 | 0.00 |
August | 80.47 | 39.07 | 41.40 | 89.57 | 41.99 | 0.00 | 0.00 | 0.00 |
September | 43.65 | 17.41 | 26.24 | 40.97 | 52.44 | 1.00 | 0.00 | 0.00 |
October | 17.99 | 4.48 | 13.51 | 8.06 | 92.19 | 10.83 | 0.00 | 0.00 |
November | 4.50 | 0.40 | 4.10 | 0.00 | 206.57 | 0.00 | 0.00 | 0.00 |
December | 0.66 | 0.01 | 0.65 | 0.00 | 225.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.17 | 25.26 | 26.92 | 55.79 | 106.34 | 15.00 | 0.00 | 0.00 |
Minimum of Months | 0.66 | 0.01 | 0.65 | 0.00 | 24.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.93 | 62.40 | 59.70 | 144.74 | 225.24 | 10.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.37 | 0.23 | 2.14 | 0.00 | 210.69 | 0.00 | 0.00 | 0.00 |
February | 12.07 | 3.07 | 9.00 | 0.01 | 182.19 | 3.17 | 0.00 | 0.00 |
March | 42.17 | 18.13 | 24.04 | 25.25 | 119.73 | 0.00 | 0.00 | 0.00 |
April | 84.36 | 45.62 | 38.74 | 95.05 | 60.84 | 0.00 | 0.00 | 0.00 |
May | 109.71 | 62.40 | 47.30 | 136.58 | 32.19 | 0.00 | 0.00 | 0.00 |
June | 118.93 | 59.23 | 59.70 | 144.74 | 24.60 | 0.00 | 0.00 | 0.00 |
July | 106.72 | 51.56 | 55.16 | 125.76 | 32.17 | 0.00 | 0.00 | 0.00 |
August | 80.47 | 39.07 | 41.40 | 89.57 | 41.99 | 0.00 | 0.00 | 0.00 |
September | 43.65 | 17.41 | 26.24 | 40.97 | 52.44 | 1.00 | 0.00 | 0.00 |
October | 17.99 | 4.48 | 13.51 | 8.06 | 92.19 | 10.83 | 0.00 | 0.00 |
November | 4.50 | 0.40 | 4.10 | 0.00 | 206.57 | 0.00 | 0.00 | 0.00 |
December | 0.66 | 0.01 | 0.65 | 0.00 | 225.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.17 | 25.26 | 26.92 | 55.79 | 106.34 | 15.00 | 0.00 | 0.00 |
Minimum of Months | 0.66 | 0.01 | 0.65 | 0.00 | 24.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.93 | 62.40 | 59.70 | 144.74 | 225.24 | 10.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.37 | 0.23 | 2.14 | 0.00 | 210.69 | 0.00 | 0.00 | 0.00 |
February | 12.07 | 3.07 | 9.00 | 0.01 | 182.19 | 3.17 | 0.00 | 0.00 |
March | 42.17 | 18.13 | 24.04 | 25.25 | 119.73 | 0.00 | 0.00 | 0.00 |
April | 84.36 | 45.62 | 38.74 | 95.05 | 60.84 | 0.00 | 0.00 | 0.00 |
May | 109.71 | 62.40 | 47.30 | 136.58 | 32.19 | 0.00 | 0.00 | 0.00 |
June | 118.93 | 59.23 | 59.70 | 144.74 | 24.60 | 0.00 | 0.00 | 0.00 |
July | 106.72 | 51.56 | 55.16 | 125.76 | 32.17 | 0.00 | 0.00 | 0.00 |
August | 80.47 | 39.07 | 41.40 | 89.57 | 41.99 | 0.00 | 0.00 | 0.00 |
September | 43.65 | 17.41 | 26.24 | 40.97 | 52.44 | 1.00 | 0.00 | 0.00 |
October | 17.99 | 4.48 | 13.51 | 8.06 | 92.19 | 10.83 | 0.00 | 0.00 |
November | 4.50 | 0.40 | 4.10 | 0.00 | 206.57 | 0.00 | 0.00 | 0.00 |
December | 0.66 | 0.01 | 0.65 | 0.00 | 225.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.17 | 25.26 | 26.92 | 55.79 | 106.34 | 15.00 | 0.00 | 0.00 |
Minimum of Months | 0.66 | 0.01 | 0.65 | 0.00 | 24.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.93 | 62.40 | 59.70 | 144.74 | 225.24 | 10.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.37 | 0.23 | 2.14 | 0.00 | 210.69 | 0.00 | 0.00 | 0.00 |
February | 12.07 | 3.07 | 9.00 | 0.01 | 182.19 | 3.17 | 0.00 | 0.00 |
March | 42.17 | 18.13 | 24.04 | 25.25 | 119.73 | 0.00 | 0.00 | 0.00 |
April | 84.36 | 45.62 | 38.74 | 95.05 | 60.84 | 0.00 | 0.00 | 0.00 |
May | 109.71 | 62.40 | 47.30 | 136.58 | 32.19 | 0.00 | 0.00 | 0.00 |
June | 118.93 | 59.23 | 59.70 | 144.74 | 24.60 | 0.00 | 0.00 | 0.00 |
July | 106.72 | 51.56 | 55.16 | 125.76 | 32.17 | 0.00 | 0.00 | 0.00 |
August | 80.47 | 39.07 | 41.40 | 89.57 | 41.99 | 0.00 | 0.00 | 0.00 |
September | 43.65 | 17.41 | 26.24 | 40.97 | 52.44 | 1.00 | 0.00 | 0.00 |
October | 17.99 | 4.48 | 13.51 | 8.06 | 92.19 | 10.83 | 0.00 | 0.00 |
November | 4.50 | 0.40 | 4.10 | 0.00 | 206.57 | 0.00 | 0.00 | 0.00 |
December | 0.66 | 0.01 | 0.65 | 0.00 | 225.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.17 | 25.26 | 26.92 | 55.79 | 106.34 | 15.00 | 0.00 | 0.00 |
Minimum of Months | 0.66 | 0.01 | 0.65 | 0.00 | 24.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.93 | 62.40 | 59.70 | 144.74 | 225.24 | 10.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.37 | 0.23 | 2.14 | 0.00 | 210.69 | 0.00 | 0.00 | 0.00 |
February | 12.07 | 3.07 | 9.00 | 0.01 | 182.19 | 3.17 | 0.00 | 0.00 |
March | 42.17 | 18.13 | 24.04 | 25.25 | 119.73 | 0.00 | 0.00 | 0.00 |
April | 84.36 | 45.62 | 38.74 | 95.05 | 60.84 | 0.00 | 0.00 | 0.00 |
May | 109.71 | 62.40 | 47.30 | 136.58 | 32.19 | 0.00 | 0.00 | 0.00 |
June | 118.93 | 59.23 | 59.70 | 144.74 | 24.60 | 0.00 | 0.00 | 0.00 |
July | 106.72 | 51.56 | 55.16 | 125.76 | 32.17 | 0.00 | 0.00 | 0.00 |
August | 80.47 | 39.07 | 41.40 | 89.57 | 41.99 | 0.00 | 0.00 | 0.00 |
September | 43.65 | 17.41 | 26.24 | 40.97 | 52.44 | 1.00 | 0.00 | 0.00 |
October | 17.99 | 4.48 | 13.51 | 8.06 | 92.19 | 10.83 | 0.00 | 0.00 |
November | 4.50 | 0.40 | 4.10 | 0.00 | 206.57 | 0.00 | 0.00 | 0.00 |
December | 0.66 | 0.01 | 0.65 | 0.00 | 225.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.17 | 25.26 | 26.92 | 55.79 | 106.34 | 15.00 | 0.00 | 0.00 |
Minimum of Months | 0.66 | 0.01 | 0.65 | 0.00 | 24.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.93 | 62.40 | 59.70 | 144.74 | 225.24 | 10.83 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 14882589.50 | 2591856.91 | 12290732.59 | 0.00 | 0.101674E+10 |
February | 79983635.98 | 28020551.88 | 51963084.10 | 10119243.86 | 0.780732E+09 |
March | 0.266173E+09 | 0.115266E+09 | 0.150907E+09 | 0.134190E+09 | 0.618075E+09 |
April | 0.607665E+09 | 0.315024E+09 | 0.292641E+09 | 0.577158E+09 | 0.305689E+09 |
May | 0.609808E+09 | 0.277809E+09 | 0.331999E+09 | 0.628629E+09 | 0.143550E+09 |
June | 0.647068E+09 | 0.276184E+09 | 0.370884E+09 | 0.693187E+09 | 92768652.59 |
July | 0.558782E+09 | 0.211224E+09 | 0.347558E+09 | 0.592879E+09 | 0.115884E+09 |
August | 0.460652E+09 | 0.195748E+09 | 0.264904E+09 | 0.453514E+09 | 0.172016E+09 |
September | 0.268629E+09 | 0.112131E+09 | 0.156497E+09 | 0.206527E+09 | 0.268301E+09 |
October | 0.108706E+09 | 32552850.77 | 76153601.19 | 35149881.58 | 0.534918E+09 |
November | 42170257.46 | 15276304.67 | 26893952.79 | 2146455.36 | 0.945520E+09 |
December | 3920692.16 | 420368.89 | 3500323.27 | 0.00 | 0.108504E+10 |
Annual Sum or Average | 0.366844E+10 | 0.158225E+10 | 0.208619E+10 | 0.333350E+10 | 0.607923E+10 |
Minimum of Months | 3920692.16 | 420368.89 | 3500323.27 | 0.00 | 92768652.59 |
Maximum of Months | 0.647068E+09 | 0.315024E+09 | 0.370884E+09 | 0.693187E+09 | 0.108504E+10 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 14882589.50 | 2591856.91 | 12290732.59 | 0.00 | 0.101674E+10 |
February | 79983635.98 | 28020551.88 | 51963084.10 | 10119243.86 | 0.780732E+09 |
March | 0.266173E+09 | 0.115266E+09 | 0.150907E+09 | 0.134190E+09 | 0.618075E+09 |
April | 0.607665E+09 | 0.315024E+09 | 0.292641E+09 | 0.577158E+09 | 0.305689E+09 |
May | 0.609808E+09 | 0.277809E+09 | 0.331999E+09 | 0.628629E+09 | 0.143550E+09 |
June | 0.647068E+09 | 0.276184E+09 | 0.370884E+09 | 0.693187E+09 | 92768652.59 |
July | 0.558782E+09 | 0.211224E+09 | 0.347558E+09 | 0.592879E+09 | 0.115884E+09 |
August | 0.460652E+09 | 0.195748E+09 | 0.264904E+09 | 0.453514E+09 | 0.172016E+09 |
September | 0.268629E+09 | 0.112131E+09 | 0.156497E+09 | 0.206527E+09 | 0.268301E+09 |
October | 0.108706E+09 | 32552850.77 | 76153601.19 | 35149881.58 | 0.534918E+09 |
November | 42170257.46 | 15276304.67 | 26893952.79 | 2146455.36 | 0.945520E+09 |
December | 3920692.16 | 420368.89 | 3500323.27 | 0.00 | 0.108504E+10 |
Annual Sum or Average | 0.366844E+10 | 0.158225E+10 | 0.208619E+10 | 0.333350E+10 | 0.607923E+10 |
Minimum of Months | 3920692.16 | 420368.89 | 3500323.27 | 0.00 | 92768652.59 |
Maximum of Months | 0.647068E+09 | 0.315024E+09 | 0.370884E+09 | 0.693187E+09 | 0.108504E+10 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6277321.93 | 0.00 | 6277321.93 | 0.00 | 0.600657E+09 |
February | 25063431.53 | 0.00 | 25063431.53 | 0.00 | 0.485904E+09 |
March | 74437434.47 | 24878.43 | 74412556.05 | 3226217.07 | 0.400331E+09 |
April | 0.131052E+09 | 3661331.01 | 0.127390E+09 | 47129811.78 | 0.187548E+09 |
May | 0.207586E+09 | 33527608.14 | 0.174058E+09 | 0.161764E+09 | 72549781.54 |
June | 0.258996E+09 | 56839889.16 | 0.202156E+09 | 0.236590E+09 | 39857404.92 |
July | 0.225868E+09 | 37165114.35 | 0.188702E+09 | 0.203902E+09 | 56351332.48 |
August | 0.145109E+09 | 7846847.01 | 0.137262E+09 | 95413354.16 | 94682664.99 |
September | 78116556.98 | 225385.50 | 77891171.48 | 22130784.07 | 0.165946E+09 |
October | 39063963.15 | 0.00 | 39063963.15 | 2027075.43 | 0.331296E+09 |
November | 11731867.32 | 0.00 | 11731867.32 | 0.00 | 0.572332E+09 |
December | 1904210.15 | 0.00 | 1904210.15 | 0.00 | 0.635983E+09 |
Annual Sum or Average | 0.120520E+10 | 0.139291E+09 | 0.106591E+10 | 0.772183E+09 | 0.364344E+10 |
Minimum of Months | 1904210.15 | 0.00 | 1904210.15 | 0.00 | 39857404.92 |
Maximum of Months | 0.258996E+09 | 56839889.16 | 0.202156E+09 | 0.236590E+09 | 0.635983E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6277095.04 | 0.00 | 6277095.04 | 0.00 | 0.600656E+09 |
February | 25062582.98 | 0.00 | 25062582.98 | 0.00 | 0.485903E+09 |
March | 74435064.37 | 24877.26 | 74410187.11 | 3225802.25 | 0.400332E+09 |
April | 0.131048E+09 | 3661159.39 | 0.127386E+09 | 47126929.25 | 0.187549E+09 |
May | 0.207579E+09 | 33526036.65 | 0.174053E+09 | 0.161756E+09 | 72549650.00 |
June | 0.258987E+09 | 56837225.00 | 0.202149E+09 | 0.236578E+09 | 39857359.60 |
July | 0.225860E+09 | 37163372.37 | 0.188696E+09 | 0.203892E+09 | 56351362.03 |
August | 0.145104E+09 | 7846479.22 | 0.137258E+09 | 95408144.90 | 94682547.81 |
September | 78113975.86 | 225374.93 | 77888600.92 | 22129022.41 | 0.165946E+09 |
October | 39062624.94 | 0.00 | 39062624.94 | 2026804.00 | 0.331296E+09 |
November | 11731443.27 | 0.00 | 11731443.27 | 0.00 | 0.572331E+09 |
December | 1904138.31 | 0.00 | 1904138.31 | 0.00 | 0.635982E+09 |
Annual Sum or Average | 0.120516E+10 | 0.139285E+09 | 0.106588E+10 | 0.772143E+09 | 0.364344E+10 |
Minimum of Months | 1904138.31 | 0.00 | 1904138.31 | 0.00 | 39857359.60 |
Maximum of Months | 0.258987E+09 | 56837225.00 | 0.202149E+09 | 0.236578E+09 | 0.635982E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6348617.64 | 621089.23 | 5727528.41 | 0.00 | 0.564310E+09 |
February | 29196265.26 | 7428725.85 | 21767539.41 | 21286.47 | 0.440766E+09 |
March | 0.112951E+09 | 48564302.36 | 64386624.33 | 67639439.78 | 0.320687E+09 |
April | 0.218659E+09 | 0.118236E+09 | 0.100422E+09 | 0.246383E+09 | 0.157698E+09 |
May | 0.293835E+09 | 0.167145E+09 | 0.126690E+09 | 0.365827E+09 | 86209777.34 |
June | 0.308263E+09 | 0.153533E+09 | 0.154731E+09 | 0.375160E+09 | 63759846.16 |
July | 0.285843E+09 | 0.138096E+09 | 0.147747E+09 | 0.336828E+09 | 86162345.59 |
August | 0.215518E+09 | 0.104640E+09 | 0.110877E+09 | 0.239912E+09 | 0.112459E+09 |
September | 0.113141E+09 | 45118305.63 | 68023086.89 | 0.106192E+09 | 0.135916E+09 |
October | 48180346.56 | 12004834.37 | 36175512.19 | 21578508.57 | 0.246934E+09 |
November | 11662255.45 | 1036583.65 | 10625671.80 | 0.00 | 0.535422E+09 |
December | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 0.603286E+09 |
Annual Sum or Average | 0.164537E+10 | 0.796462E+09 | 0.848906E+09 | 0.175954E+10 | 0.335361E+10 |
Minimum of Months | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 63759846.16 |
Maximum of Months | 0.308263E+09 | 0.167145E+09 | 0.154731E+09 | 0.375160E+09 | 0.603286E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6348617.64 | 621089.23 | 5727528.41 | 0.00 | 0.564310E+09 |
February | 29196265.26 | 7428725.85 | 21767539.41 | 21286.47 | 0.440766E+09 |
March | 0.112951E+09 | 48564302.36 | 64386624.33 | 67639439.78 | 0.320687E+09 |
April | 0.218659E+09 | 0.118236E+09 | 0.100422E+09 | 0.246383E+09 | 0.157698E+09 |
May | 0.293835E+09 | 0.167145E+09 | 0.126690E+09 | 0.365827E+09 | 86209777.34 |
June | 0.308263E+09 | 0.153533E+09 | 0.154731E+09 | 0.375160E+09 | 63759846.16 |
July | 0.285843E+09 | 0.138096E+09 | 0.147747E+09 | 0.336828E+09 | 86162345.59 |
August | 0.215518E+09 | 0.104640E+09 | 0.110877E+09 | 0.239912E+09 | 0.112459E+09 |
September | 0.113141E+09 | 45118305.63 | 68023086.89 | 0.106192E+09 | 0.135916E+09 |
October | 48180346.56 | 12004834.37 | 36175512.19 | 21578508.57 | 0.246934E+09 |
November | 11662255.45 | 1036583.65 | 10625671.80 | 0.00 | 0.535422E+09 |
December | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 0.603286E+09 |
Annual Sum or Average | 0.164537E+10 | 0.796462E+09 | 0.848906E+09 | 0.175954E+10 | 0.335361E+10 |
Minimum of Months | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 63759846.16 |
Maximum of Months | 0.308263E+09 | 0.167145E+09 | 0.154731E+09 | 0.375160E+09 | 0.603286E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6348617.64 | 621089.23 | 5727528.41 | 0.00 | 0.564310E+09 |
February | 29196265.26 | 7428725.85 | 21767539.41 | 21286.47 | 0.440766E+09 |
March | 0.112951E+09 | 48564302.36 | 64386624.33 | 67639439.78 | 0.320687E+09 |
April | 0.218659E+09 | 0.118236E+09 | 0.100422E+09 | 0.246383E+09 | 0.157698E+09 |
May | 0.293835E+09 | 0.167145E+09 | 0.126690E+09 | 0.365827E+09 | 86209777.34 |
June | 0.308263E+09 | 0.153533E+09 | 0.154731E+09 | 0.375160E+09 | 63759846.16 |
July | 0.285843E+09 | 0.138096E+09 | 0.147747E+09 | 0.336828E+09 | 86162345.59 |
August | 0.215518E+09 | 0.104640E+09 | 0.110877E+09 | 0.239912E+09 | 0.112459E+09 |
September | 0.113141E+09 | 45118305.63 | 68023086.89 | 0.106192E+09 | 0.135916E+09 |
October | 48180346.56 | 12004834.37 | 36175512.19 | 21578508.57 | 0.246934E+09 |
November | 11662255.45 | 1036583.65 | 10625671.80 | 0.00 | 0.535422E+09 |
December | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 0.603286E+09 |
Annual Sum or Average | 0.164537E+10 | 0.796462E+09 | 0.848906E+09 | 0.175954E+10 | 0.335361E+10 |
Minimum of Months | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 63759846.16 |
Maximum of Months | 0.308263E+09 | 0.167145E+09 | 0.154731E+09 | 0.375160E+09 | 0.603286E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6348617.64 | 621089.23 | 5727528.41 | 0.00 | 0.564310E+09 |
February | 29196265.26 | 7428725.85 | 21767539.41 | 21286.47 | 0.440766E+09 |
March | 0.112951E+09 | 48564302.36 | 64386624.33 | 67639439.78 | 0.320687E+09 |
April | 0.218659E+09 | 0.118236E+09 | 0.100422E+09 | 0.246383E+09 | 0.157698E+09 |
May | 0.293835E+09 | 0.167145E+09 | 0.126690E+09 | 0.365827E+09 | 86209777.34 |
June | 0.308263E+09 | 0.153533E+09 | 0.154731E+09 | 0.375160E+09 | 63759846.16 |
July | 0.285843E+09 | 0.138096E+09 | 0.147747E+09 | 0.336828E+09 | 86162345.59 |
August | 0.215518E+09 | 0.104640E+09 | 0.110877E+09 | 0.239912E+09 | 0.112459E+09 |
September | 0.113141E+09 | 45118305.63 | 68023086.89 | 0.106192E+09 | 0.135916E+09 |
October | 48180346.56 | 12004834.37 | 36175512.19 | 21578508.57 | 0.246934E+09 |
November | 11662255.45 | 1036583.65 | 10625671.80 | 0.00 | 0.535422E+09 |
December | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 0.603286E+09 |
Annual Sum or Average | 0.164537E+10 | 0.796462E+09 | 0.848906E+09 | 0.175954E+10 | 0.335361E+10 |
Minimum of Months | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 63759846.16 |
Maximum of Months | 0.308263E+09 | 0.167145E+09 | 0.154731E+09 | 0.375160E+09 | 0.603286E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6348617.64 | 621089.23 | 5727528.41 | 0.00 | 0.564310E+09 |
February | 29196265.26 | 7428725.85 | 21767539.41 | 21286.47 | 0.440766E+09 |
March | 0.112951E+09 | 48564302.36 | 64386624.33 | 67639439.78 | 0.320687E+09 |
April | 0.218659E+09 | 0.118236E+09 | 0.100422E+09 | 0.246383E+09 | 0.157698E+09 |
May | 0.293835E+09 | 0.167145E+09 | 0.126690E+09 | 0.365827E+09 | 86209777.34 |
June | 0.308263E+09 | 0.153533E+09 | 0.154731E+09 | 0.375160E+09 | 63759846.16 |
July | 0.285843E+09 | 0.138096E+09 | 0.147747E+09 | 0.336828E+09 | 86162345.59 |
August | 0.215518E+09 | 0.104640E+09 | 0.110877E+09 | 0.239912E+09 | 0.112459E+09 |
September | 0.113141E+09 | 45118305.63 | 68023086.89 | 0.106192E+09 | 0.135916E+09 |
October | 48180346.56 | 12004834.37 | 36175512.19 | 21578508.57 | 0.246934E+09 |
November | 11662255.45 | 1036583.65 | 10625671.80 | 0.00 | 0.535422E+09 |
December | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 0.603286E+09 |
Annual Sum or Average | 0.164537E+10 | 0.796462E+09 | 0.848906E+09 | 0.175954E+10 | 0.335361E+10 |
Minimum of Months | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 63759846.16 |
Maximum of Months | 0.308263E+09 | 0.167145E+09 | 0.154731E+09 | 0.375160E+09 | 0.603286E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6348617.64 | 621089.23 | 5727528.41 | 0.00 | 0.564310E+09 |
February | 29196265.26 | 7428725.85 | 21767539.41 | 21286.47 | 0.440766E+09 |
March | 0.112951E+09 | 48564302.36 | 64386624.33 | 67639439.78 | 0.320687E+09 |
April | 0.218659E+09 | 0.118236E+09 | 0.100422E+09 | 0.246383E+09 | 0.157698E+09 |
May | 0.293835E+09 | 0.167145E+09 | 0.126690E+09 | 0.365827E+09 | 86209777.34 |
June | 0.308263E+09 | 0.153533E+09 | 0.154731E+09 | 0.375160E+09 | 63759846.16 |
July | 0.285843E+09 | 0.138096E+09 | 0.147747E+09 | 0.336828E+09 | 86162345.59 |
August | 0.215518E+09 | 0.104640E+09 | 0.110877E+09 | 0.239912E+09 | 0.112459E+09 |
September | 0.113141E+09 | 45118305.63 | 68023086.89 | 0.106192E+09 | 0.135916E+09 |
October | 48180346.56 | 12004834.37 | 36175512.19 | 21578508.57 | 0.246934E+09 |
November | 11662255.45 | 1036583.65 | 10625671.80 | 0.00 | 0.535422E+09 |
December | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 0.603286E+09 |
Annual Sum or Average | 0.164537E+10 | 0.796462E+09 | 0.848906E+09 | 0.175954E+10 | 0.335361E+10 |
Minimum of Months | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 63759846.16 |
Maximum of Months | 0.308263E+09 | 0.167145E+09 | 0.154731E+09 | 0.375160E+09 | 0.603286E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6348617.64 | 621089.23 | 5727528.41 | 0.00 | 0.564310E+09 |
February | 29196265.26 | 7428725.85 | 21767539.41 | 21286.47 | 0.440766E+09 |
March | 0.112951E+09 | 48564302.36 | 64386624.33 | 67639439.78 | 0.320687E+09 |
April | 0.218659E+09 | 0.118236E+09 | 0.100422E+09 | 0.246383E+09 | 0.157698E+09 |
May | 0.293835E+09 | 0.167145E+09 | 0.126690E+09 | 0.365827E+09 | 86209777.34 |
June | 0.308263E+09 | 0.153533E+09 | 0.154731E+09 | 0.375160E+09 | 63759846.16 |
July | 0.285843E+09 | 0.138096E+09 | 0.147747E+09 | 0.336828E+09 | 86162345.59 |
August | 0.215518E+09 | 0.104640E+09 | 0.110877E+09 | 0.239912E+09 | 0.112459E+09 |
September | 0.113141E+09 | 45118305.63 | 68023086.89 | 0.106192E+09 | 0.135916E+09 |
October | 48180346.56 | 12004834.37 | 36175512.19 | 21578508.57 | 0.246934E+09 |
November | 11662255.45 | 1036583.65 | 10625671.80 | 0.00 | 0.535422E+09 |
December | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 0.603286E+09 |
Annual Sum or Average | 0.164537E+10 | 0.796462E+09 | 0.848906E+09 | 0.175954E+10 | 0.335361E+10 |
Minimum of Months | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 63759846.16 |
Maximum of Months | 0.308263E+09 | 0.167145E+09 | 0.154731E+09 | 0.375160E+09 | 0.603286E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6348617.64 | 621089.23 | 5727528.41 | 0.00 | 0.564310E+09 |
February | 29196265.26 | 7428725.85 | 21767539.41 | 21286.47 | 0.440766E+09 |
March | 0.112951E+09 | 48564302.36 | 64386624.33 | 67639439.78 | 0.320687E+09 |
April | 0.218659E+09 | 0.118236E+09 | 0.100422E+09 | 0.246383E+09 | 0.157698E+09 |
May | 0.293835E+09 | 0.167145E+09 | 0.126690E+09 | 0.365827E+09 | 86209777.34 |
June | 0.308263E+09 | 0.153533E+09 | 0.154731E+09 | 0.375160E+09 | 63759846.16 |
July | 0.285843E+09 | 0.138096E+09 | 0.147747E+09 | 0.336828E+09 | 86162345.59 |
August | 0.215518E+09 | 0.104640E+09 | 0.110877E+09 | 0.239912E+09 | 0.112459E+09 |
September | 0.113141E+09 | 45118305.63 | 68023086.89 | 0.106192E+09 | 0.135916E+09 |
October | 48180346.56 | 12004834.37 | 36175512.19 | 21578508.57 | 0.246934E+09 |
November | 11662255.45 | 1036583.65 | 10625671.80 | 0.00 | 0.535422E+09 |
December | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 0.603286E+09 |
Annual Sum or Average | 0.164537E+10 | 0.796462E+09 | 0.848906E+09 | 0.175954E+10 | 0.335361E+10 |
Minimum of Months | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 63759846.16 |
Maximum of Months | 0.308263E+09 | 0.167145E+09 | 0.154731E+09 | 0.375160E+09 | 0.603286E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6348617.64 | 621089.23 | 5727528.41 | 0.00 | 0.564310E+09 |
February | 29196265.26 | 7428725.85 | 21767539.41 | 21286.47 | 0.440766E+09 |
March | 0.112951E+09 | 48564302.36 | 64386624.33 | 67639439.78 | 0.320687E+09 |
April | 0.218659E+09 | 0.118236E+09 | 0.100422E+09 | 0.246383E+09 | 0.157698E+09 |
May | 0.293835E+09 | 0.167145E+09 | 0.126690E+09 | 0.365827E+09 | 86209777.34 |
June | 0.308263E+09 | 0.153533E+09 | 0.154731E+09 | 0.375160E+09 | 63759846.16 |
July | 0.285843E+09 | 0.138096E+09 | 0.147747E+09 | 0.336828E+09 | 86162345.59 |
August | 0.215518E+09 | 0.104640E+09 | 0.110877E+09 | 0.239912E+09 | 0.112459E+09 |
September | 0.113141E+09 | 45118305.63 | 68023086.89 | 0.106192E+09 | 0.135916E+09 |
October | 48180346.56 | 12004834.37 | 36175512.19 | 21578508.57 | 0.246934E+09 |
November | 11662255.45 | 1036583.65 | 10625671.80 | 0.00 | 0.535422E+09 |
December | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 0.603286E+09 |
Annual Sum or Average | 0.164537E+10 | 0.796462E+09 | 0.848906E+09 | 0.175954E+10 | 0.335361E+10 |
Minimum of Months | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 63759846.16 |
Maximum of Months | 0.308263E+09 | 0.167145E+09 | 0.154731E+09 | 0.375160E+09 | 0.603286E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6348617.64 | 621089.23 | 5727528.41 | 0.00 | 0.564310E+09 |
February | 29196265.26 | 7428725.85 | 21767539.41 | 21286.47 | 0.440766E+09 |
March | 0.112951E+09 | 48564302.36 | 64386624.33 | 67639439.78 | 0.320687E+09 |
April | 0.218659E+09 | 0.118236E+09 | 0.100422E+09 | 0.246383E+09 | 0.157698E+09 |
May | 0.293835E+09 | 0.167145E+09 | 0.126690E+09 | 0.365827E+09 | 86209777.34 |
June | 0.308263E+09 | 0.153533E+09 | 0.154731E+09 | 0.375160E+09 | 63759846.16 |
July | 0.285843E+09 | 0.138096E+09 | 0.147747E+09 | 0.336828E+09 | 86162345.59 |
August | 0.215518E+09 | 0.104640E+09 | 0.110877E+09 | 0.239912E+09 | 0.112459E+09 |
September | 0.113141E+09 | 45118305.63 | 68023086.89 | 0.106192E+09 | 0.135916E+09 |
October | 48180346.56 | 12004834.37 | 36175512.19 | 21578508.57 | 0.246934E+09 |
November | 11662255.45 | 1036583.65 | 10625671.80 | 0.00 | 0.535422E+09 |
December | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 0.603286E+09 |
Annual Sum or Average | 0.164537E+10 | 0.796462E+09 | 0.848906E+09 | 0.175954E+10 | 0.335361E+10 |
Minimum of Months | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 63759846.16 |
Maximum of Months | 0.308263E+09 | 0.167145E+09 | 0.154731E+09 | 0.375160E+09 | 0.603286E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1207.73 | 15.80 | 1.94 | 13.86 | 0.00 | 0.00 |
February | 1.67 | 1040.45 | 86.84 | 23.17 | 63.68 | 0.00 | 0.00 |
March | 83.73 | 741.58 | 254.34 | 86.09 | 168.25 | 0.00 | 0.00 |
April | 472.93 | 371.81 | 570.00 | 245.90 | 324.10 | 0.00 | 0.00 |
May | 575.31 | 146.48 | 610.36 | 232.48 | 377.88 | 0.00 | 0.00 |
June | 701.85 | 86.77 | 699.12 | 256.96 | 442.16 | 0.00 | 0.00 |
July | 583.30 | 116.95 | 585.91 | 185.48 | 400.43 | 0.00 | 0.00 |
August | 402.21 | 191.46 | 452.33 | 152.03 | 300.30 | 0.00 | 0.00 |
September | 170.88 | 329.51 | 267.55 | 86.70 | 180.85 | 0.00 | 0.00 |
October | 21.97 | 641.02 | 110.34 | 24.31 | 86.03 | 0.00 | 0.00 |
November | 0.28 | 1169.80 | 41.59 | 11.79 | 29.80 | 0.00 | 0.00 |
December | 0.00 | 1285.11 | 4.35 | 0.31 | 4.04 | 0.00 | 0.00 |
Annual Sum or Average | 252.29 | 608.52 | 309.08 | 109.18 | 199.90 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 86.77 | 4.35 | 0.31 | 4.04 | 0.00 | 0.00 |
Maximum of Months | 701.85 | 1285.11 | 699.12 | 256.96 | 442.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 17031.30 | 23.70 | 2.32 | 21.38 | 0.00 | 0.00 |
February | 0.27 | 15524.71 | 120.69 | 30.71 | 89.98 | 0.00 | 0.00 |
March | 885.37 | 11440.42 | 421.71 | 181.32 | 240.39 | 0.00 | 0.00 |
April | 3348.06 | 5016.14 | 843.59 | 456.16 | 387.43 | 0.00 | 0.00 |
May | 4779.95 | 1130.40 | 1097.05 | 624.05 | 473.01 | 0.00 | 0.00 |
June | 5185.28 | 797.26 | 1189.29 | 592.33 | 596.95 | 0.00 | 0.00 |
July | 4757.72 | 1179.11 | 1067.22 | 515.59 | 551.62 | 0.00 | 0.00 |
August | 3144.96 | 1443.83 | 804.65 | 390.68 | 413.97 | 0.00 | 0.00 |
September | 1405.95 | 2115.22 | 436.50 | 174.07 | 262.43 | 0.00 | 0.00 |
October | 264.29 | 6419.76 | 179.88 | 44.82 | 135.06 | 0.00 | 0.00 |
November | 0.00 | 14503.73 | 44.99 | 4.00 | 40.99 | 0.00 | 0.00 |
December | 0.00 | 17273.91 | 6.61 | 0.14 | 6.47 | 0.00 | 0.00 |
Annual Sum or Average | 1991.75 | 7783.95 | 521.74 | 252.56 | 269.19 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 797.26 | 6.61 | 0.14 | 6.47 | 0.00 | 0.00 |
Maximum of Months | 5185.28 | 17273.91 | 1189.29 | 624.05 | 596.95 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.323480E+10 | 42319595.98 | 5183713.82 | 37135882.16 | 0.00 | 0.00 |
February | 4030188.61 | 0.251706E+10 | 0.210093E+09 | 56041103.75 | 0.154052E+09 | 0.00 | 0.00 |
March | 0.224274E+09 | 0.198626E+10 | 0.681218E+09 | 0.230582E+09 | 0.450636E+09 | 0.00 | 0.00 |
April | 0.122583E+10 | 0.963736E+09 | 0.147743E+10 | 0.637371E+09 | 0.840058E+09 | 0.00 | 0.00 |
May | 0.154092E+10 | 0.392339E+09 | 0.163478E+10 | 0.622671E+09 | 0.101211E+10 | 0.00 | 0.00 |
June | 0.181919E+10 | 0.224897E+09 | 0.181212E+10 | 0.666045E+09 | 0.114607E+10 | 0.00 | 0.00 |
July | 0.156232E+10 | 0.313235E+09 | 0.156929E+10 | 0.496776E+09 | 0.107251E+10 | 0.00 | 0.00 |
August | 0.107727E+10 | 0.512817E+09 | 0.121152E+10 | 0.407189E+09 | 0.804328E+09 | 0.00 | 0.00 |
September | 0.442917E+09 | 0.854097E+09 | 0.693488E+09 | 0.224713E+09 | 0.468775E+09 | 0.00 | 0.00 |
October | 58831444.52 | 0.171691E+10 | 0.295539E+09 | 65105701.54 | 0.230434E+09 | 0.00 | 0.00 |
November | 718125.57 | 0.303213E+10 | 0.107804E+09 | 30552609.34 | 77251216.16 | 0.00 | 0.00 |
December | 0.00 | 0.344204E+10 | 11649732.77 | 840737.77 | 10808995.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.795629E+10 | 0.191903E+11 | 0.974725E+10 | 0.344307E+10 | 0.630418E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.224897E+09 | 11649732.77 | 840737.77 | 10808995.00 | 0.00 | 0.00 |
Maximum of Months | 0.181919E+10 | 0.344204E+10 | 0.181212E+10 | 0.666045E+09 | 0.114607E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.456166E+11 | 63486176.40 | 6210892.33 | 57275284.06 | 0.00 | 0.00 |
February | 641850.67 | 0.375574E+11 | 0.291963E+09 | 74287258.49 | 0.217675E+09 | 0.00 | 0.00 |
March | 0.237138E+10 | 0.306420E+11 | 0.112951E+10 | 0.485643E+09 | 0.643866E+09 | 0.00 | 0.00 |
April | 0.867816E+10 | 0.130018E+11 | 0.218659E+10 | 0.118236E+10 | 0.100422E+10 | 0.00 | 0.00 |
May | 0.128026E+11 | 0.302766E+10 | 0.293835E+10 | 0.167145E+10 | 0.126690E+10 | 0.00 | 0.00 |
June | 0.134402E+11 | 0.206651E+10 | 0.308263E+10 | 0.153533E+10 | 0.154731E+10 | 0.00 | 0.00 |
July | 0.127431E+11 | 0.315812E+10 | 0.285843E+10 | 0.138096E+10 | 0.147747E+10 | 0.00 | 0.00 |
August | 0.842346E+10 | 0.386716E+10 | 0.215518E+10 | 0.104640E+10 | 0.110877E+10 | 0.00 | 0.00 |
September | 0.364422E+10 | 0.548266E+10 | 0.113141E+10 | 0.451183E+09 | 0.680231E+09 | 0.00 | 0.00 |
October | 0.707884E+09 | 0.171947E+11 | 0.481803E+09 | 0.120048E+09 | 0.361755E+09 | 0.00 | 0.00 |
November | 0.00 | 0.375937E+11 | 0.116623E+09 | 10365836.48 | 0.106257E+09 | 0.00 | 0.00 |
December | 0.00 | 0.462664E+11 | 17696238.01 | 369852.99 | 17326385.03 | 0.00 | 0.00 |
Annual Sum or Average | 0.628117E+11 | 0.245475E+12 | 0.164537E+11 | 0.796462E+10 | 0.848906E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.206651E+10 | 17696238.01 | 369852.99 | 17326385.03 | 0.00 | 0.00 |
Maximum of Months | 0.134402E+11 | 0.462664E+11 | 0.308263E+10 | 0.167145E+10 | 0.154731E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.6 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.7 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.25 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.88 | 6.41 | 3.45 | 5.66 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.85 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.70 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.45 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.85 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.7 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.7 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.60 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.03 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.79 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.30 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.34 | 11.70 | 4.67 | 18.88 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.77 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.91 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 8.01 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.6 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.1 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.6 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.34 | 11.70 | 6.20 | 18.88 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.2 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.3 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.1 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.9 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.7 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.24 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.65 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.03 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.97 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.33 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.36 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.29 | 141.00 | 225.33 |
August | 16.14 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.82 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 8.01 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.6 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.1 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.36 | 29.07 | 14.40 | 8.80 | 19.29 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.7 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.78 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.75 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.41 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.30 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.1 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.5 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.1 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.121136E+10 | -0.105363E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -157729142.2 | 58.99 | 0.00 | 0.00 |
February | 0.111020E+10 | -967999826.8 | 0.00 | 0.00 | 672.00 | 0.00 | -142197581.4 | 58.99 | 0.00 | 0.00 |
March | 0.128816E+10 | -0.113141E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156746819.5 | 58.99 | 0.00 | 0.00 |
April | 0.120141E+10 | -0.105105E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -150357366.3 | 58.99 | 0.00 | 0.00 |
May | 0.123273E+10 | -0.108504E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -147695070.4 | 58.99 | 0.00 | 0.00 |
June | 0.117334E+10 | -0.104139E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -131951424.7 | 59.00 | 0.00 | 0.00 |
July | 0.110230E+10 | -968519886.6 | 0.00 | 0.00 | 744.00 | 0.00 | -133781352.8 | 58.99 | 0.00 | 0.00 |
August | 0.115061E+10 | -0.101498E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -135632596.3 | 58.99 | 0.00 | 0.00 |
September | 0.108298E+10 | -940048902.6 | 0.00 | 0.00 | 720.00 | 0.00 | -142935768.7 | 58.99 | 0.00 | 0.00 |
October | 0.111720E+10 | -960826428.8 | 0.00 | 0.00 | 744.00 | 0.00 | -156378067.0 | 59.00 | 0.00 | 0.00 |
November | 0.110824E+10 | -955939308.2 | 0.00 | 0.00 | 720.00 | 0.00 | -152297022.2 | 58.99 | 0.00 | 0.00 |
December | 0.119373E+10 | -0.103624E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -157487353.6 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139723E+11 | -0.122071E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.176519E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.108298E+10 | -0.113141E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -157729142.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.128816E+10 | -940048902.6 | 0.00 | 0.00 | 744.00 | 0.00 | -131951424.7 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 108.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 205.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 329.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 421.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 545.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 583.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 562.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 467.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 356.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 265.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 135.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 583.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.215744E+11 | 31626.74 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.184353E+11 | 31626.74 | 01-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.185308E+11 | 31626.74 | 01-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.899457E+10 | 31626.74 | 01-APR-02:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.176881E+10 | 31626.74 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.123693E+09 | 28337.64 | 01-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29097814.29 | 4188.48 | 05-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.248413E+09 | 31626.74 | 30-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.254840E+10 | 31626.74 | 05-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.106854E+11 | 31626.74 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.175316E+11 | 31626.74 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.212798E+11 | 31626.74 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121750E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 29097814.29 | 4188.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.215744E+11 | 31626.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.691080E+11 | 94234.80 | 01-JAN-00:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.543384E+11 | 94234.80 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.488601E+11 | 94234.80 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.220668E+11 | 94234.80 | 01-APR-00:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114507E+10 | 67508.45 | 27-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.200228E+10 | 80461.69 | 25-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.277285E+11 | 94234.80 | 11-OCT-01:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.507924E+11 | 94234.80 | 01-NOV-00:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.659873E+11 | 94234.80 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342029E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.691080E+11 | 94234.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.237489E+12 | 178959.00 | 12-JAN-03:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.190402E+12 | 178959.00 | 23-FEB-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167588E+12 | 170721.83 | 02-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.665966E+11 | 155915.37 | 02-APR-19:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.183693E+10 | 37854.93 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.931954E+11 | 133995.86 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170653E+12 | 144412.11 | 10-NOV-01:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.233343E+12 | 165475.32 | 22-DEC-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116110E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.237489E+12 | 178959.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.212305E+09 | 0.212305E+09 | 3502.99 | 13-MAY-15:00 | 3502.99 | 0.00 |
June | 0.00 | 0.00 | 0.337873E+10 | 0.325454E+10 | 15400.29 | 21-JUN-17:10 | 15400.29 | 0.00 |
July | 0.00 | 0.00 | 0.524748E+10 | 0.485801E+10 | 17502.10 | 23-JUL-23:02 | 15364.39 | 0.00 |
August | 0.00 | 0.00 | 0.342054E+10 | 0.319810E+10 | 16246.15 | 11-AUG-17:43 | 16246.15 | 0.00 |
September | 0.00 | 0.00 | 0.110627E+09 | 0.108707E+09 | 3268.54 | 02-SEP-15:00 | 3158.13 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.123697E+11 | 0.116317E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.524748E+10 | 0.485801E+10 | 17502.10 | 16246.15 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.168444E+10 | 0.164471E+10 | 20471.79 | 21-JUN-18:13 | 20471.79 | 0.00 |
July | 0.00 | 0.00 | 0.470448E+10 | 0.459797E+10 | 24702.99 | 23-JUL-10:53 | 24480.43 | 0.00 |
August | 0.00 | 0.00 | 0.139904E+10 | 0.136161E+10 | 19390.39 | 02-AUG-17:33 | 19390.39 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.778796E+10 | 0.760429E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.470448E+10 | 0.459797E+10 | 24702.99 | 24480.43 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.110533E+10 | 0.08 | 412.68 | 01-JAN-00:01 | 0.08 |
February | 0.991924E+09 | 0.08 | 412.68 | 01-FEB-00:02 | 0.08 |
March | 0.101446E+10 | 0.07 | 412.68 | 01-MAR-00:02 | 0.08 |
April | 0.531205E+09 | 0.04 | 412.68 | 01-APR-00:03 | 0.08 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 46096670.16 | 0.00 | 412.68 | 28-SEP-01:27 | 0.08 |
October | 0.812325E+09 | 0.06 | 412.68 | 01-OCT-00:10 | 0.08 |
November | 0.106967E+10 | 0.08 | 412.68 | 01-NOV-00:10 | 0.08 |
December | 0.110533E+10 | 0.08 | 412.68 | 01-DEC-00:02 | 0.08 |
Annual Sum or Average | 0.667634E+10 | 0.04 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.110533E+10 | 0.08 | 412.68 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.137286E+10 | 0.79 | 1141.72 | 02-JAN-08:00 | 0.96 |
February | 0.127085E+10 | 0.78 | 1141.72 | 01-FEB-09:00 | 0.96 |
March | 0.144283E+10 | 0.76 | 1141.72 | 01-MAR-09:40 | 0.96 |
April | 0.124592E+10 | 0.57 | 1141.72 | 01-APR-07:40 | 0.96 |
May | 0.119556E+10 | 0.39 | 1141.72 | 01-MAY-10:10 | 0.95 |
June | 0.120936E+10 | 0.43 | 1141.72 | 01-JUN-14:10 | 0.95 |
July | 0.119811E+10 | 0.45 | 1141.72 | 01-JUL-06:30 | 0.94 |
August | 0.125913E+10 | 0.44 | 1141.72 | 02-AUG-11:50 | 0.94 |
September | 0.114721E+10 | 0.39 | 1141.72 | 02-SEP-06:30 | 0.95 |
October | 0.123126E+10 | 0.56 | 1141.72 | 02-OCT-12:10 | 0.95 |
November | 0.124601E+10 | 0.71 | 1141.72 | 01-NOV-07:50 | 0.95 |
December | 0.135340E+10 | 0.77 | 1141.72 | 01-DEC-11:50 | 0.96 |
Annual Sum or Average | 0.151725E+11 | 0.59 | |||
Minimum of Months | 0.114721E+10 | 0.39 | 1141.72 | 0.94 | |
Maximum of Months | 0.144283E+10 | 0.79 | 1141.72 | 0.96 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.391231E+10 | 0.81 | 2631.90 | 02-JAN-13:40 | 0.92 |
February | 0.350038E+10 | 0.81 | 2631.90 | 01-FEB-08:20 | 0.92 |
March | 0.388439E+10 | 0.81 | 2631.90 | 01-MAR-10:20 | 0.92 |
April | 0.317653E+10 | 0.69 | 2631.90 | 01-APR-06:40 | 0.92 |
May | 0.274654E+10 | 0.40 | 2631.90 | 27-MAY-07:10 | 0.91 |
June | 0.271070E+10 | 0.36 | 2631.90 | 03-JUN-14:30 | 0.91 |
July | 0.261886E+10 | 0.35 | 2631.90 | 03-JUL-15:30 | 0.90 |
August | 0.281455E+10 | 0.36 | 2631.90 | 02-AUG-15:40 | 0.90 |
September | 0.266562E+10 | 0.42 | 2631.90 | 25-SEP-07:20 | 0.91 |
October | 0.325571E+10 | 0.74 | 2631.90 | 02-OCT-06:30 | 0.91 |
November | 0.348770E+10 | 0.81 | 2631.90 | 01-NOV-11:10 | 0.92 |
December | 0.379907E+10 | 0.82 | 2631.90 | 01-DEC-10:30 | 0.92 |
Annual Sum or Average | 0.385724E+11 | 0.61 | |||
Minimum of Months | 0.261886E+10 | 0.35 | 2631.90 | 0.90 | |
Maximum of Months | 0.391231E+10 | 0.82 | 2631.90 | 0.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.137286E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.127085E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.144283E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.124592E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.125981E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.221118E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.274049E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.226659E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.118085E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.123126E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.124601E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.135340E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.188220E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.118085E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.274049E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.391231E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.350038E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.388439E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.317653E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.274654E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.319050E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.395377E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.320995E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.266562E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.325571E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.348770E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.379907E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.407825E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.266562E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.395377E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.137286E+10 | 0.00 | 0.215744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127085E+10 | 0.00 | 0.184353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144283E+10 | 0.00 | 0.185308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124592E+10 | 0.00 | 0.899457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.119556E+10 | 0.212305E+09 | 0.176881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.120936E+10 | 0.337873E+10 | 0.123693E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119811E+10 | 0.524748E+10 | 29097814.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.125913E+10 | 0.342054E+10 | 0.248413E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.114721E+10 | 0.110627E+09 | 0.254840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123126E+10 | 0.00 | 0.106854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124601E+10 | 0.00 | 0.175316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135340E+10 | 0.00 | 0.212798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151725E+11 | 0.123697E+11 | 0.121750E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.114721E+10 | 0.00 | 29097814.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144283E+10 | 0.524748E+10 | 0.215744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.391231E+10 | 0.00 | 0.691080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.350038E+10 | 0.00 | 0.543384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.388439E+10 | 0.00 | 0.488601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.317653E+10 | 0.00 | 0.220668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.274654E+10 | 0.00 | 0.114507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.271070E+10 | 0.168444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.261886E+10 | 0.470448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.281455E+10 | 0.139904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.266562E+10 | 0.00 | 0.200228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.325571E+10 | 0.00 | 0.277285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.348770E+10 | 0.00 | 0.507924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379907E+10 | 0.00 | 0.659873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.385724E+11 | 0.778796E+10 | 0.342029E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.261886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.391231E+10 | 0.470448E+10 | 0.691080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.137286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.119556E+10 | 0.00 | 0.00 | 0.00 | 64248235.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.120936E+10 | 0.00 | 0.00 | 0.00 | 0.100183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119811E+10 | 0.00 | 0.00 | 0.00 | 0.154238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.125913E+10 | 0.00 | 0.00 | 0.00 | 0.100746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.114721E+10 | 0.00 | 0.00 | 0.00 | 33637864.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151725E+11 | 0.00 | 0.00 | 0.00 | 0.364955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.114721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144283E+10 | 0.00 | 0.00 | 0.00 | 0.154238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.391231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.350038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.388439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.317653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.274654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.271070E+10 | 0.00 | 0.00 | 0.00 | 0.479802E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.261886E+10 | 0.00 | 0.00 | 0.00 | 0.133491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.281455E+10 | 0.00 | 0.00 | 0.00 | 0.395395E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.266562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.325571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.348770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.385724E+11 | 0.00 | 0.00 | 0.00 | 0.221010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.261886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.391231E+10 | 0.00 | 0.00 | 0.00 | 0.133491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674807E+10 | 0.00 | 0.00 | 0.19 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565054E+10 | 0.00 | 0.00 | 0.19 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559121E+10 | 0.00 | 0.00 | 0.20 |
April | 0.255716E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288956E+10 | 0.00 | 0.00 | 0.18 |
May | 0.917930E+09 | 0.00 | 0.00 | 286954.57 | 0.00 | 0.603786E+09 | 0.175761E+09 | 0.00 | 0.17 |
June | 0.253573E+09 | 6333481.59 | 0.00 | 5021896.94 | 0.00 | 60699969.77 | 0.913844E+09 | 0.00 | 0.18 |
July | 0.145580E+09 | 21932628.55 | 0.00 | 7220144.60 | 0.00 | 24761759.50 | 0.683990E+09 | 0.00 | 0.17 |
August | 0.409923E+09 | 452142.67 | 0.00 | 5639963.27 | 0.00 | 0.126911E+09 | 0.952343E+09 | 0.00 | 0.18 |
September | 0.105752E+10 | 0.00 | 0.00 | 206229.24 | 0.00 | 0.114809E+10 | 0.169432E+09 | 0.00 | 0.17 |
October | 0.129318E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377237E+10 | 0.00 | 0.00 | 0.17 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.616264E+10 | 0.00 | 0.00 | 0.18 |
December | 707683.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702206E+10 | 0.00 | 0.00 | 0.19 |
Annual Sum or Average | 0.317027E+10 | 28718252.81 | 0.00 | 18375188.62 | 0.00 | 0.398007E+11 | 0.289537E+10 | 0.00 | 0.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24761759.50 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.105752E+10 | 21932628.55 | 0.00 | 7220144.60 | 0.00 | 0.702206E+10 | 0.952343E+09 | 0.00 | 0.20 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 11085996.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131500E+11 | 0.00 | 0.00 | 0.14 |
February | 0.620184E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.966970E+10 | 0.00 | 0.00 | 0.15 |
March | 0.267623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.741773E+10 | 0.00 | 0.00 | 0.16 |
April | 0.389592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175654E+10 | 0.00 | 0.00 | 0.15 |
May | 0.384305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23280331.77 | 0.00 | 0.00 | 0.15 |
June | 0.234736E+10 | 0.00 | 0.00 | 4646032.22 | 0.00 | 0.00 | 0.317117E+10 | 0.00 | 0.23 |
July | 0.104038E+10 | 8851369.16 | 0.00 | 9750972.40 | 0.00 | 0.00 | 0.440050E+10 | 0.00 | 0.25 |
August | 0.307438E+10 | 0.00 | 0.00 | 4871130.74 | 0.00 | 0.00 | 0.337489E+10 | 0.00 | 0.24 |
September | 0.514509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77286612.64 | 0.00 | 0.00 | 0.15 |
October | 0.363605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376523E+10 | 0.00 | 0.00 | 0.14 |
November | 0.316540E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121995E+11 | 0.00 | 0.00 | 0.14 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139700E+11 | 0.00 | 0.00 | 0.14 |
Annual Sum or Average | 0.266063E+11 | 8851369.16 | 0.00 | 19268135.36 | 0.00 | 0.620293E+11 | 0.109466E+11 | 0.00 | 0.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.514509E+10 | 8851369.16 | 0.00 | 9750972.40 | 0.00 | 0.139700E+11 | 0.440050E+10 | 0.00 | 0.25 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | -0.857433E+11 | 0.106101E+12 | 0.00 | 0.229858E+11 | 0.106535E+12 |
February | 0.507964E+11 | 0.869679E+11 | 0.00 | 0.187114E+11 | 0.873052E+11 |
March | 0.437315E+12 | 0.119556E+12 | 0.00 | 0.183899E+11 | 0.818237E+11 |
April | 0.790539E+12 | 0.932414E+11 | 0.00 | 0.113024E+11 | 0.427379E+11 |
May | 0.101313E+13 | 0.527480E+11 | 0.00 | 0.782580E+10 | 0.157249E+11 |
June | 0.106784E+13 | 0.459686E+11 | 0.00 | 0.845029E+10 | 0.202157E+11 |
July | 0.981378E+12 | 0.454920E+11 | 0.00 | 0.820420E+10 | 0.269063E+11 |
August | 0.732278E+12 | 0.542807E+11 | 0.00 | 0.101485E+11 | 0.204043E+11 |
September | 0.335429E+12 | 0.411165E+11 | 0.00 | 0.105986E+11 | 0.163289E+11 |
October | 0.986505E+11 | 0.880181E+11 | 0.00 | 0.144333E+11 | 0.528537E+11 |
November | -0.463498E+11 | 0.431482E+11 | 0.00 | 0.227446E+11 | 0.828030E+11 |
December | -0.108295E+12 | 0.858622E+11 | 0.00 | 0.244892E+11 | 0.105010E+12 |
Annual Sum or Average | 0.526696E+13 | 0.862501E+12 | 0.00 | 0.178284E+12 | 0.658649E+12 |
Minimum of Months | -0.108295E+12 | 0.411165E+11 | 0.00 | 0.782580E+10 | 0.157249E+11 |
Maximum of Months | 0.106784E+13 | 0.119556E+12 | 0.00 | 0.244892E+11 | 0.106535E+12 |