Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2023-10-16 10:41:42
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:42
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1383.09 | 286.05 | 286.05 |
Net Site Energy | 1383.09 | 286.05 | 286.05 |
Total Source Energy | 4370.92 | 903.99 | 903.99 |
Net Source Energy | 4370.92 | 903.99 | 903.99 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 4.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 268.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 134.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 190.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 23.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1378.61 | 4.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 4.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 268.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 134.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 34.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 155.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 23.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 4.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 268.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 134.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 190.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 23.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 99.60 | 0.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 285.12 | 0.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 99.60 | 0.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 285.12 | 0.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1378.612 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1378.612 | 100.00 |
Total On-Site and Utility Electric Sources | 1378.612 | 100.00 |
Total Electricity End Uses | 1378.612 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.67 |
Time Setpoint Not Met During Occupied Cooling | 62.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3120.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:42
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.61 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7186 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 15.0695 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 9.6875 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 11.2890 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 11.2890 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.7186 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 15.0695 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 9.6875 | 46.45 | 2.5587 | |
Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 11.2890 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:42
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 06-JUN-14:50 | 02-JAN-06:10 | - | - | - | - | - | - | - | - | - | - | 12-JAN-12:39 |
Heating | 0.00 | 88911.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 44663.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 13961.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1662.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 116594.23 | 88911.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 88911.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 44663.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 11656.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1662.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:42
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 4.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 849.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1974.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 424.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 601.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 74.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4366.07 | 4.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 175.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 124.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 902.99 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 175.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 124.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 902.99 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:42
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.52 |
ZONE2 FINE STORAGE DIRECT AIR | 5.80 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 3.85 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 3.85 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 153780.87 |
PSZ-OFFICE HEATING COIL | 35815.38 |
PSZ-FINE STORAGE HEATING COIL | 171950.08 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 153780.87 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.52 | 1.52 | 1.52 | 1.52 | 1.52 | 1.52 | 1.00 | 1.00 | 1.52 |
PSZ-FINE STORAGE | 5.80 | 5.80 | 5.80 | 5.80 | 5.80 | 5.80 | 1.00 | 1.00 | 5.80 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.52 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 5.80 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.52 | 1663.69 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 5.80 | 9992.87 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.52 | 1.52 | 1.52 | 1.52 | 30462.00 | 35815.38 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 5.80 | 5.80 | 5.80 | 5.80 | 136907.12 | 171950.08 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.52 | 0.760018 | 1.52 | 30462.00 | 15642.59 | 30462.00 | 0.775690 | 0.775690 |
PSZ-FINE STORAGE COOLING COIL | 5.80 | 2.90 | 5.80 | 136907.12 | 69632.40 | 136907.12 | 0.717010 | 0.717010 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:42
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:42
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:42
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.719 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.792 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 15.069 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15.069 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 9.688 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 12.246 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2539.013 | 10.719 | 199.158 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2539.013 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 20997.932 | 15.069 | 699.931 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20997.932 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 31046.942 | 9.688 | 449.956 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 31046.942 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 982.6 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.7823 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 3 | 0.167 | 7.732 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 3 | 0.167 | 7.732 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1000E-02 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.179 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.36859539E-11 | 0.84954153E-14 | 0.47616952E-16 | 0.0000000 |
5 | 1 | -5.1234640 | 0.46000535E-01 | -0.53498711E-03 | 0.47618904E-11 |
6 | 0 | 987.76235 | 982.59289 | 982.63942 | |
7 | 4 | 0.72249793E-12 | -0.16720573E-15 | 0.22015083E-14 | 0.12409536E-15 |
8 | 3 | -0.36459118E-03 | 0.53555631E-06 | -0.52695411E-04 | 0.13865996E-12 |
9 | 2 | 1.6915239 | 0.11971291E-01 | 1.1039557 | -0.69896550E-04 |
10 | 1 | -7.1930661 | 0.31446443 | -16.864389 | 0.32415671 |
11 | 0 | 6.0306730 | 0.20232993 | 16.289252 | |
12 | 3 | -0.11556429E-04 | 0.42115602E-06 | -0.11737956E-05 | 0.71542051E-15 |
13 | 2 | 0.42692330 | 0.53556778E-01 | 0.17992628 | -0.21068281E-05 |
14 | 1 | -10.558915 | 3.4986983 | -9.7344214 | 0.71768033E-01 |
15 | 0 | 17.309178 | 3.6249194 | 16.731671 | |
16 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
17 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
18 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
19 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
20 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
21 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
22 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
23 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
24 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
25 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
26 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
27 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
28 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
29 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
30 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
31 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
32 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
33 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
34 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
35 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
36 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
37 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
38 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
39 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
40 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
41 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
42 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
43 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
44 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
45 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
46 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
47 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
48 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
49 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
50 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
51 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
52 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
53 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
54 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
55 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
56 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
57 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
58 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
59 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
60 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
61 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
62 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
63 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
64 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
65 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
66 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
67 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
68 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
69 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
70 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
71 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
72 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
73 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
74 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
75 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
76 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
77 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
78 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
79 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
80 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
81 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
82 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
83 | 3 | -0.11737956E-05 | 0.42115602E-06 | -0.11556429E-04 | 0.71542051E-15 |
84 | 2 | 0.17992628 | 0.53556778E-01 | 0.42692330 | -0.21068281E-05 |
85 | 1 | -9.7344214 | 3.4986983 | -10.558915 | 0.71768033E-01 |
86 | 0 | 16.731671 | 3.6249194 | 17.309178 | |
87 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
88 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
89 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
90 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.2_SHGC_SOUTH_0.25 | 34 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
2 | NONRESWINDOW_U_1.2_SHGC_NORTH_0.25 | 35 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
3 | NONRESWINDOW_U_1.2_SHGC_EAST_0.25 | 36 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
4 | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
5 | SKYLIGHT_U_1.02_SHGC_0.36 | 38 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.361 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.19502 | 0.25365 | 0.25365 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.849 | 0.366 | 0.255 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 0.153 | 6.473E-004 | 9.992E-004 | 0.546 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.780 | 5.598E-004 | 3.565E-004 | 0.951 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 3.433 | 1.071E-003 | 6.996E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 15007.87675 | 18009.45210 | 1.26670 | 1.52004 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 41.51500 | 9.15709E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 7156.64021 | 8587.96825 | 0.20590 | 0.24708 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 6.30000 | 6.07234E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 73511.90864 | 88214.29037 | 4.83661 | 5.80393 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | 42.00000 | 9.15790E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 18089.06281 | 21706.87538 | 0.43881 | 0.52658 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 6.30000 | 6.07234E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 | 42.00000 | 9.15790E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 128150.72593 | 153780.87112 | 3.21230 | 3.85476 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 23463.26 | 1.52004 | 1.52004 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 7308.37 | 0.24708 | 0.24708 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 108285.91 | 5.80393 | 5.80393 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 19818.26 | 0.52658 | 0.52658 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.52004 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.80393 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 3.85476 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 3.85476 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 153780.87134 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 153780.87112 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.52004 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.52004 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.52004 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.52004 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.52004 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.52004 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.80393 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.80393 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.80393 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 5.80393 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.80393 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 5.80393 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.52004 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 5.80393 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.52004 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.52004 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1663.68685 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.52004 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.52004 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.52004 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.52004 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.52004 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.76002 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.52004 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 30462.00000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 15642.58816 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 30462.00000 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.77569 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.77569 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 30462.00000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35815.37812 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 35815.37812 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.80393 |
47 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 5.80393 |
49 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 9992.87366 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 5.80393 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 5.80393 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 5.80393 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 5.80393 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 5.80393 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.90197 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 5.80393 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 136907.12000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 69632.40054 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 136907.12000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71701 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71701 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 136907.12000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 171950.07700 |
64 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
66 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 171950.07700 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 29281.7 | 11.01 | 10.37 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 132396.9 | 10.47 | 9.87 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 4.6142483437E-002 | 3.4029195761E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.1555079981 | 0.1628475224 | Pass | Pass | 0.2112006989 | 1.1154882466 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 0.1741168439 | 0.2042517401 | Pass | Pass | 3.0989326416E-002 | 0.1541996029 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:42
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8385.32 | 1941.82 | 0.00 | -86.6 | 1118.40 | 11358.99 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:42
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.60 | 4 | |||
Feb | 21.40 | 43 | |||
Mar | 12.00 | 35 | |||
Apr | 29.10 | 12 | |||
May | 29.10 | 57 | |||
Jun | 197.10 | 59 | |||
Jul | 47.90 | 83 | |||
Aug | 0.00 | 0 | |||
Sep | 171.60 | 106 | |||
Oct | 4.80 | 31 | |||
Nov | 1.20 | 7 | |||
Dec | 33.00 | 13 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:42
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 3.584 | 7.732 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 3.584 | 7.732 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 3.584 | 7.732 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 7.226 | 982.639 | 3204.84 | 3170.23 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 2.711 | 7.732 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 2.711 | 7.732 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 6.813 | 0.251 | 0.252 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 6.813 | 0.251 | 0.252 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_1.2_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 6.813 | 0.251 | 0.252 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_1.2_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 6.813 | 0.251 | 0.252 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.27 | 6.141 | 0.449 | 0.450 | |||||||||||||||||
North Total or Average | 6.51 | 6.813 | 0.251 | 0.252 | |||||||||||||||||
Non-North Total or Average | 45.76 | 6.046 | 0.478 | 0.478 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:42
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:42
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.7186 | 236.88 | 2539.01 | LightsWired | LTG_SCH_OFFICE | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.86 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 15.0695 | 1393.41 | 20997.93 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 239.15 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 9.6875 | 3204.84 | 31046.94 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 353.60 |
Interior Lighting Total | 11.2890 | 4835.13 | 54583.89 | 623.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 8532.22 | AstronomicalClock | - | 83.75 | 83.75 | 134.14 | |
Exterior Lighting Total | 8532.22 | 134.14 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:42
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 30462.00 | 23629.07 | 6832.93 | 0.78 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 136907.12 | 98163.77 | 38743.35 | 0.72 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 29281.7 | 11.01 | 10.37 | ||||
PSZ-FINE STORAGE COOLING COIL | 132396.9 | 10.47 | 9.87 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 153780.87 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 35815.38 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 171950.08 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 3.85 | 358.15 | 92.91 | 1.00 | 3.25 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 1.52 | 1663.69 | 1094.51 | 1.00 | 1.33 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.59 | 1018.41 | 5.80 | 9992.87 | 1721.74 | 1.00 | 1.15 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:42
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 15007.88 | 18009.45 | 76.03 | 1.267 | 1.520 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 23.90 | 23.90 | 0.00824 | 41.52 | 0.00916 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 73511.91 | 88214.29 | 63.31 | 4.837 | 5.804 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | 26.70 | 26.70 | 0.00823 | 42.00 | 0.00916 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 | 0.00 | 46.89 | 0.00924 | 42.00 | 0.00916 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 7156.64 | 8587.97 | 36.25 | 0.206 | 0.247 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00836 | 6.30 | 0.00607 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 18089.06 | 21706.88 | 15.58 | 0.439 | 0.527 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00774 | 6.30 | 0.00607 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 128150.73 | 153780.87 | 47.98 | 3.212 | 3.855 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00783 | 6.30 | 0.00607 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.52 | 1.52 | 0.25 | 0.25 | 1.5200 | 1.5200 | 1.5200 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 5.80 | 5.80 | 0.53 | 0.53 | 5.8039 | 5.8039 | 5.8039 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 153780.871 | 153780.871 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 153780.87 | 153780.87 | 3.854763 | 10.00 | 10.00 | 0.00783127 | 43.33 | 21.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 10.00 | 0.00783127 | 99.9999 | 153780.87 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 30462.000 | 23629.069 | 1.520040 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 30462.00 | 29063.17 | 1.520040 | 26.00 | 16.66 | 0.00830208 | 12.00 | 11.03 | 0.00800000 | 41.61 | 0.00915725 | 22.16 | 6.7291 | 23.90 | 0.00824036 | 43.5212 | 15003.24 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 35815.378 | 35815.378 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 35815.38 | 35815.38 | 1.520035 | 20.02 | 14.42 | 0.00820320 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 6.7291 | 21.10 | 0.00835693 | 52.3074 | 7156.64 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 136907.120 | 98163.774 | 5.803930 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | 136907.12 | 131730.98 | 5.803930 | 29.26 | 17.76 | 0.00829701 | 12.00 | 11.03 | 0.00800000 | 42.00 | 0.00915790 | 22.26 | 7.3176 | 26.70 | 0.00822903 | 36.7950 | 73511.91 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 171950.077 | 171950.077 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 171950.08 | 171950.08 | 5.803934 | 14.88 | 11.85 | 0.00761808 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 7.3176 | 15.56 | 0.00774012 | 68.6616 | 18089.06 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:42
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 153780.871 | 153780.871 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 3.854763 | 4.52466511 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 153780.87 | 153780.87 | 1.0000 | 4.52466511 | 3.854763 | 10.00 | 10.00 | 0.00783127 | 29779.3 | 43.33 | 21.85 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 153780.87 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 10.00 | 0.00783127 | 10.00 | 0.00783127 | 99.9999 | 153780.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 30462.000 | 23629.069 | 1.520040 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2732 | 1004.8586 | 1.1738 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.520035 | 1.78419518 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | Sensible | 30462.00 | 29063.17 | 1.0000 | 1.78420085 | 1.520040 | 26.00 | 16.66 | 0.00830208 | 47295.2 | 12.00 | 11.03 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30462.00 | 41.61 | 0.00915725 | 22.16 | 0.10228463 | 6.7291 | 23.90 | 0.00824036 | 23.90 | 0.00824036 | 43.5212 | 15003.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35815.378 | 35815.378 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.520035 | 1.78419518 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 35815.38 | 35815.38 | 1.0000 | 1.78419518 | 1.520035 | 20.02 | 14.42 | 0.00820320 | 40941.3 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35815.38 | 6.30 | 0.00607234 | 6.30 | 0.10228463 | 6.7291 | 21.01 | 0.00835693 | 21.10 | 0.00835693 | 52.3074 | 7156.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 136907.120 | 98163.774 | 5.803930 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2637 | 1004.8586 | 1.1738 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 5.803934 | 6.81257374 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | Sensible | 136907.12 | 131730.98 | 1.0000 | 6.81256865 | 5.803930 | 29.26 | 17.76 | 0.00829701 | 50599.0 | 12.00 | 11.03 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 136907.12 | 42.00 | 0.00915790 | 22.26 | 0.42471127 | 7.3176 | 26.70 | 0.00822903 | 26.70 | 0.00822903 | 36.7950 | 73511.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 171950.077 | 171950.077 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 5.803934 | 6.81257374 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 171950.08 | 171950.08 | 1.0000 | 6.81257374 | 5.803934 | 14.88 | 11.85 | 0.00761808 | 34217.1 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 171950.08 | 6.30 | 0.00607234 | 6.30 | 0.42471127 | 7.3176 | 15.56 | 0.00774012 | 15.56 | 0.00774012 | 68.6616 | 18089.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:42
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2710.67 | 912.33 | 352.83 |
ZONE2 FINE STORAGE | 3345.00 | 2710.67 | 2480.67 |
ZONE3 BULK STORAGE | 3345.83 | 3366.00 | 3120.33 |
Facility | 3560.33 | 3458.67 | 3120.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 0.67 | 99.33 | 0.67 | 59.83 |
ZONE2 FINE STORAGE | 0.50 | 576.67 | 0.00 | 14.17 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1.17 | 652.83 | 0.67 | 62.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:42
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.351 | 0.392 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.42 | 30.00 | 2953.02 | 0.495 | 0.187 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.088 | 0.000 | 2.307 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.42 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:42
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.42 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.53 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1267136.12 | 0.00 | 1267136.12 | 1786839.17 | 3053975.29 | 3225648.14 | 5398.72 | 3361.28 | 0.00 | 415.45 |
ZONE2 FINE STORAGE | 5662901.53 | 0.00 | 5662901.53 | 4051620.53 | 9714522.06 | 13393694.68 | 5408.87 | 3351.13 | 0.00 | 1896.82 |
ZONE3 BULK STORAGE | 0.00 | 0.53E+09 | 0.53E+09 | 17587623.02 | 0.55E+09 | 30805497.77 | 4584.47 | 0.17 | 4175.36 | 3966.59 |
Total Facility | 6930037.65 | 0.53E+09 | 0.54E+09 | 23426082.72 | 0.56E+09 | 47424840.58 | 6680.37 | 3378.90 | 4175.36 | 4126.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.0956 | 0.0000 | 0.0956 | 0.1067 | 0.2023 | 0.1023 | 275.24 | 3360.76 | 0.00 |
ZONE2 FINE STORAGE | 0.3907 | 0.0000 | 0.3907 | 0.1472 | 0.5379 | 0.4247 | 302.67 | 3333.33 | 0.00 |
ZONE3 BULK STORAGE | 0.0000 | 20.8515 | 20.8515 | 0.8039 | 21.6554 | 0.9768 | 1489.62 | 0.00 | 2146.38 |
Total Facility | 0.4863 | 20.8515 | 21.3378 | 1.0578 | 22.3956 | 1.5038 | 1556.70 | 3360.76 | 2146.38 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 1745825.05 | 0.00 | 1745825.05 | 3225648.14 | 5389.12 | 0.55 | 3370.33 | 408.10 |
PSZ-FINE STORAGE | 7802188.90 | 0.00 | 7802188.90 | 13393694.68 | 5381.91 | 1.75 | 3376.35 | 1893.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1317 | 0.0000 | 0.1317 | 0.1023 | 266.98 | 0.32 | 3368.71 |
PSZ-FINE STORAGE | 0.5383 | 0.0000 | 0.5383 | 0.4247 | 301.99 | 0.02 | 3333.99 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 3905.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 5327.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.5699 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:42
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 383 |
Defaulted Fields | 319 |
Fields with Defaults | 1020 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:41:42
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1378.61 | 6718.26 | 01-JAN-08:20 | 116594.23 | 06-JUN-14:50 |
Electricity:Building | 797.52 | 6235.26 | 01-JAN-00:10 | 58611.10 | 06-FEB-14:00 |
Electricity:Zone:ZONE1 OFFICE | 62.81 | 1030.77 | 01-JAN-00:10 | 3867.54 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 762.90 | 6235.26 | 01-JAN-00:10 | 56305.80 | 02-JAN-09:10 |
InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 495.56 | 3104.69 | 01-JAN-00:10 | 36895.31 | 06-FEB-14:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 190.02 | 0.00 | 01-JAN-08:20 | 13961.85 | 24-MAR-15:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 34.62 | 0.00 | 01-JAN-00:10 | 2305.29 | 30-JUN-05:10 |
Ventilation (simple):Fans:Electricity | 34.62 | 0.00 | 01-JAN-00:10 | 2305.29 | 30-JUN-05:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 34.62 | 0.00 | 01-JAN-00:10 | 2305.29 | 30-JUN-05:10 |
ElectricityPurchased:Facility | 1378.61 | 6718.26 | 01-JAN-08:20 | 116594.23 | 06-JUN-14:50 |
ElectricityPurchased:Plant | 1378.61 | 6718.26 | 01-JAN-08:20 | 116594.23 | 06-JUN-14:50 |
Cogeneration:ElectricityPurchased | 1378.61 | 6718.26 | 01-JAN-08:20 | 116594.23 | 06-JUN-14:50 |
General:Cogeneration:ElectricityPurchased | 1378.61 | 6718.26 | 01-JAN-08:20 | 116594.23 | 06-JUN-14:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1378.61 | 6718.26 | 01-JAN-08:20 | 116594.23 | 06-JUN-14:50 |
ElectricityNet:Plant | 1378.61 | 6718.26 | 01-JAN-08:20 | 116594.23 | 06-JUN-14:50 |
Cogeneration:ElectricityNet | 1378.61 | 6718.26 | 01-JAN-08:20 | 116594.23 | 06-JUN-14:50 |
General:Cogeneration:ElectricityNet | 1378.61 | 6718.26 | 01-JAN-08:20 | 116594.23 | 06-JUN-14:50 |
Electricity:HVAC | 423.58 | 0.00 | 01-JAN-08:20 | 59389.15 | 06-JUN-15:10 |
General:Fans:Electricity | 155.40 | 0.00 | 01-JAN-08:20 | 12014.71 | 02-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 268.18 | 0.00 | 01-JAN-00:10 | 47732.59 | 06-JUN-15:10 |
General:Cooling:Electricity | 268.18 | 0.00 | 01-JAN-00:10 | 47732.59 | 06-JUN-15:10 |
ExteriorLights:Electricity | 134.14 | 0.00 | 01-JAN-07:20 | 8532.22 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 134.14 | 0.00 | 01-JAN-07:20 | 8532.22 | 01-JAN-00:10 |
Electricity:Plant | 23.37 | 483.00 | 13-MAR-05:10 | 1776.64 | 17-JAN-12:10 |
WaterSystems:Electricity | 23.37 | 483.00 | 13-MAR-05:10 | 1776.64 | 17-JAN-12:10 |
Water Heater:WaterSystems:Electricity | 23.37 | 483.00 | 13-MAR-05:10 | 1776.64 | 17-JAN-12:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4.48 | 0.00 | 01-JAN-08:20 | 88911.53 | 02-JAN-06:10 |
NaturalGas:HVAC | 4.48 | 0.00 | 01-JAN-08:20 | 88911.53 | 02-JAN-06:10 |
Heating:NaturalGas | 4.48 | 0.00 | 01-JAN-08:20 | 88911.53 | 02-JAN-06:10 |
General:Heating:NaturalGas | 4.48 | 0.00 | 01-JAN-08:20 | 88911.53 | 02-JAN-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-JAN-12:40 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-JAN-12:40 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-JAN-12:40 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-JAN-12:40 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-JAN-12:40 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-JAN-12:40 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-JAN-12:40 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-JAN-12:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1404.33 | 0.00 | 01-JAN-08:20 | 220519.19 | 06-JUN-15:10 |
EnergyTransfer:Building | 551.84 | 0.00 | 01-JAN-08:20 | 98738.29 | 06-JUN-15:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 103.54 | 0.00 | 01-JAN-00:10 | 20646.06 | 06-JUN-16:10 |
Heating:EnergyTransfer | 10.78 | 0.00 | 01-JAN-08:20 | 68188.86 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.85 | 0.00 | 01-JAN-00:10 | 14357.22 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 10.78 | 0.00 | 01-JAN-08:20 | 68188.86 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.85 | 0.00 | 01-JAN-00:10 | 14357.22 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 541.06 | 0.00 | 01-JAN-00:10 | 98738.29 | 06-JUN-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 102.69 | 0.00 | 01-JAN-00:10 | 20646.06 | 06-JUN-16:10 |
General:Cooling:EnergyTransfer | 541.06 | 0.00 | 01-JAN-00:10 | 98738.29 | 06-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 102.69 | 0.00 | 01-JAN-00:10 | 20646.06 | 06-JUN-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 445.77 | 0.00 | 01-JAN-00:10 | 81359.26 | 06-JUN-15:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 7.40 | 0.00 | 01-JAN-00:10 | 13095.55 | 01-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 7.40 | 0.00 | 01-JAN-00:10 | 13095.55 | 01-JAN-07:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 438.37 | 0.00 | 01-JAN-00:10 | 81359.26 | 06-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 438.37 | 0.00 | 01-JAN-00:10 | 81359.26 | 06-JUN-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 2.53 | 0.00 | 01-JAN-08:00 | 47706.97 | 03-JAN-07:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 2.53 | 0.00 | 01-JAN-08:00 | 47706.97 | 03-JAN-07:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 2.53 | 0.00 | 01-JAN-08:00 | 47706.97 | 03-JAN-07:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 852.49 | 0.00 | 01-JAN-08:20 | 121780.90 | 06-JUN-15:10 |
HeatingCoils:EnergyTransfer | 3.37 | 0.00 | 01-JAN-08:20 | 68130.27 | 02-JAN-06:10 |
CoolingCoils:EnergyTransfer | 849.12 | 0.00 | 01-JAN-00:10 | 121780.90 | 06-JUN-15:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:42
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 0.853 | -102.690 | 0.000 | 0.000 | 9.153 | 30.864 | 31.946 | 15.274 | 0.000 | 9.048 | 17.968 | 0.000 | -7.774 | 0.000 | -4.641 | -0.001 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 7.398 | -438.361 | 0.000 | 0.000 | 17.533 | 239.148 | 0.000 | 0.000 | 0.000 | 15.221 | 169.951 | 0.000 | 0.000 | 0.000 | -10.891 | -0.005 |
ZONE3 BULK STORAGE | 2.526 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21.627 | 353.598 | 107.344 | 203.905 | 0.000 | 5.371 | 1318.991 | 0.000 | -63.460 | 0.000 | -1949.902 | -0.014 |
Total Facility | 2.526 | 0.000 | 8.252 | -541.051 | 0.000 | 0.000 | 48.313 | 623.610 | 139.290 | 219.179 | 0.000 | 29.640 | 1506.910 | 0.000 | -71.234 | 0.000 | -1965.434 | -0.019 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 22-APR-05:01 | 0.00 | 0.00 | 0.00 | -29702.31 | 0.00 | 0.00 | 71.56 | 583.97 | 573.75 | 0.00 | 0.00 | 0.00 | 29094.38 | 0.00 | -507.70 | 0.00 | -113.65 | 0.00 |
ZONE2 FINE STORAGE | 08-MAY-21:02 | 0.00 | 0.00 | 0.00 | -113608.67 | 0.00 | 0.00 | 0.00 | 2099.79 | 0.00 | 0.00 | 0.00 | 1264.46 | 110244.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 04-MAY-05:01 | 0.00 | 0.00 | 0.00 | -138324.27 | 0.00 | 0.00 | 310.58 | 5788.46 | 2623.78 | 67.50 | 0.00 | 862.70 | 208729.77 | 0.00 | -3116.63 | 0.00 | -76941.89 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 02-JAN-06:01 | 0.00 | 0.00 | 34654.10 | 0.00 | 0.00 | 0.00 | 144.45 | 583.97 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -735.39 | 0.00 | -560.62 | -34660.26 |
ZONE2 FINE STORAGE | 01-JAN-07:05 | 0.00 | 0.00 | 26191.06 | 0.00 | 0.00 | 0.00 | 0.00 | 2099.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -28290.85 |
ZONE3 BULK STORAGE | 03-JAN-07:00 | 47706.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 914.90 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3203.16 | 0.00 | -1375.60 | -49197.50 |
Total Facility | 02-JAN-06:01 | 46198.10 | 0.00 | 42062.10 | 0.00 | 0.00 | 0.00 | 1407.83 | 5788.46 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5708.89 | 0.00 | -560.62 | -91810.76 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:42
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.5200 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.5200 | 0.0673 | 1.0000 | Not calculated | 0.1023 | 0.0673 | ||
PSZ-FINE STORAGE | 5.8039 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 5.8039 | 0.0732 | 1.0000 | Not calculated | 0.4247 | 0.0732 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.5200 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.5200 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0673 | ||
PSZ-FINE STORAGE | 5.8039 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 5.8039 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.0732 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5200 | 1.5200 | 1.5200 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.8039 | 5.8039 | 5.8039 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.5200 | 1.5200 | 1.5200 | 1.5200 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 5.8039 | 5.8039 | 5.8039 | 5.8039 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5200 | 1.5200 | 1.5200 | No | 0.1023 | 0.4140 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.8039 | 5.8039 | 5.8039 | No | 0.4247 | 0.8066 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.5200 | 1.5200 | 1.5200 | 1.5200 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 5.8039 | 5.8039 | 5.8039 | 5.8039 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:42
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 0.67 |
Number of hours cooling loads not met | 62.00 |
Number of hours not met | 62.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 4.48 | 88911.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 268.18 | 47732.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 623.61 | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 134.14 | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 34.62 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 155.40 | 12014.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 23.37 | 1776.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 1378.61 |
Natural Gas | 0.00 | 4.48 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 1383.09 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 128.97 |
Space Heating | 0.00 |
Space Cooling | 55.46 |
Fans (All) | 39.30 |
Service Water Heating | 4.83 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 285.12 |
Subtotal | 285.12 |
Natural Gas [MJ/m2] | |
Space Heating | 0.93 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.93 |
Subtotal | 0.93 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 45.09 |
Space Heating | 0.32 |
Space Cooling | 19.39 |
Fans (All) | 13.74 |
Service Water Heating | 1.69 |
Receptacle Equipment | 10.07 |
Miscellaneous | 9.70 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 3430. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:42
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 5611.00 | 2896.50 | 252.50 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 5337.67 | 3422.33 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 2942.00 | 2000.17 | 2183.83 | 1583.33 | 50.67 |
Min | 2942.00 | 2000.17 | 0.00 | 0.00 | 0.00 |
Max | 5611.00 | 3422.33 | 2183.83 | 1583.33 | 50.67 |
Average | 4630.22 | 2773.00 | 812.11 | 527.78 | 16.89 |
Sum | 13890.67 | 8319.00 | 2436.33 | 1583.33 | 50.67 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33024.83 | 2.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 46338.50 | 36380.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 34548.00 | 55875.67 | 42341.67 | 55602.00 | 2825.67 |
Min | 33024.83 | 2.17 | 0.00 | 0.00 | 0.00 |
Max | 46338.50 | 55875.67 | 42341.67 | 55602.00 | 2825.67 |
Average | 37970.44 | 30752.78 | 14113.89 | 18534.00 | 941.89 |
Sum | 113911.33 | 92258.33 | 42341.67 | 55602.00 | 2825.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 5477.00 | 3250.17 | 32.83 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 5077.17 | 3682.83 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3014.67 | 2567.17 | 1779.67 | 1048.33 | 350.17 |
Min | 3014.67 | 2567.17 | 0.00 | 0.00 | 0.00 |
Max | 5477.00 | 3682.83 | 1779.67 | 1048.33 | 350.17 |
Average | 4522.94 | 3166.72 | 604.17 | 349.44 | 116.72 |
Sum | 13568.83 | 9500.17 | 1812.50 | 1048.33 | 350.17 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 31975.83 | 1051.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 42901.00 | 39818.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 41425.00 | 65049.33 | 33516.83 | 33985.00 | 17216.83 |
Min | 31975.83 | 1051.17 | 0.00 | 0.00 | 0.00 |
Max | 42901.00 | 65049.33 | 33516.83 | 33985.00 | 17216.83 |
Average | 38767.28 | 35306.17 | 11172.28 | 11328.33 | 5738.94 |
Sum | 116301.83 | 105918.50 | 33516.83 | 33985.00 | 17216.83 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:42
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:42
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
For: Environment
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Environment
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Environment
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185336E+10 | 5024.80 | 14-JAN-16:00 | 21.30 | 15.07 | 0.614768E+09 | 769.02 | 07-JAN-15:39 | 21.30 | 15.07 |
February | 0.320513E+10 | 16356.90 | 25-FEB-06:03 | 17.60 | 15.67 | 0.577492E+09 | 769.06 | 24-FEB-15:09 | 17.60 | 15.67 |
March | 0.703655E+10 | 29562.94 | 29-MAR-05:01 | 21.18 | 17.34 | 0.685207E+09 | 769.08 | 10-MAR-16:30 | 21.18 | 17.34 |
April | 0.104268E+11 | 29701.87 | 22-APR-05:01 | 21.90 | 16.71 | 0.635283E+09 | 769.10 | 18-APR-12:09 | 21.90 | 16.71 |
May | 0.135141E+11 | 29670.76 | 09-MAY-05:01 | 26.97 | 19.07 | 0.660948E+09 | 769.10 | 16-MAY-12:09 | 35.80 | 23.77 |
June | 0.137696E+11 | 28261.48 | 03-JUN-05:01 | 30.03 | 22.07 | 0.661036E+09 | 769.12 | 14-JUN-12:09 | 34.37 | 24.12 |
July | 0.125390E+11 | 25157.48 | 07-JUL-05:01 | 31.52 | 25.91 | 0.635589E+09 | 769.12 | 01-JUL-15:39 | 31.52 | 25.91 |
August | 0.123766E+11 | 23785.16 | 07-AUG-05:01 | 29.53 | 24.79 | 0.686366E+09 | 769.11 | 08-AUG-14:30 | 36.75 | 26.49 |
September | 0.105946E+11 | 27246.76 | 27-SEP-05:01 | 23.08 | 20.68 | 0.635424E+09 | 769.12 | 22-SEP-15:50 | 23.08 | 20.68 |
October | 0.909373E+10 | 29514.94 | 25-OCT-05:01 | 19.02 | 16.53 | 0.635208E+09 | 769.09 | 10-OCT-15:00 | 19.02 | 16.53 |
November | 0.554415E+10 | 27847.85 | 03-NOV-05:02 | 15.83 | 12.47 | 0.608455E+09 | 776.60 | 03-NOV-07:10 | 17.13 | 12.62 |
December | 0.273783E+10 | 6611.41 | 01-DEC-15:20 | 23.03 | 13.49 | 0.625227E+09 | 769.03 | 05-DEC-15:39 | 20.37 | 14.37 |
Annual Sum or Average | 0.102691E+12 | 0.766100E+10 | ||||||||
Minimum of Months | 0.185336E+10 | 5024.80 | 15.83 | 12.47 | 0.577492E+09 | 769.02 | 17.13 | 12.62 | ||
Maximum of Months | 0.137696E+11 | 29701.87 | 31.52 | 25.91 | 0.686366E+09 | 776.60 | 36.75 | 26.49 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.904565E+09 | 7940.15 | 26-JAN-13:52 | 22.50 | 13.87 | 0.163752E+10 | 2246.84 | 04-JAN-14:00 | 22.50 | 13.87 |
February | 0.585916E+10 | 28925.83 | 20-FEB-15:45 | 25.72 | 14.13 | 0.162818E+10 | 2247.01 | 22-FEB-16:10 | 26.37 | 15.92 |
March | 0.238311E+11 | 103329.20 | 29-MAR-17:05 | 32.00 | 18.46 | 0.199178E+10 | 2265.17 | 01-MAR-09:39 | 32.00 | 18.46 |
April | 0.518112E+11 | 113275.09 | 29-APR-19:02 | 33.82 | 19.17 | 0.185460E+10 | 2247.23 | 17-APR-13:20 | 33.82 | 19.17 |
May | 0.717512E+11 | 113613.71 | 08-MAY-21:02 | 33.85 | 19.67 | 0.192919E+10 | 2247.31 | 25-MAY-15:00 | 38.60 | 24.76 |
June | 0.713936E+11 | 110585.12 | 12-JUN-05:01 | 34.12 | 19.12 | 0.192933E+10 | 2247.35 | 14-JUN-15:50 | 35.73 | 24.59 |
July | 0.618702E+11 | 106486.34 | 07-JUL-05:01 | 31.52 | 25.91 | 0.185499E+10 | 2247.33 | 05-JUL-15:39 | 31.52 | 25.91 |
August | 0.547124E+11 | 99847.25 | 09-AUG-05:01 | 29.90 | 25.20 | 0.200322E+10 | 2246.85 | 08-AUG-15:00 | 29.90 | 25.20 |
September | 0.440807E+11 | 104617.24 | 26-SEP-17:05 | 34.60 | 22.33 | 0.185472E+10 | 2247.26 | 27-SEP-15:00 | 35.60 | 22.58 |
October | 0.349282E+11 | 109368.84 | 01-OCT-12:22 | 34.50 | 19.89 | 0.185350E+10 | 2247.22 | 03-OCT-15:20 | 35.03 | 22.43 |
November | 0.144143E+11 | 97868.80 | 05-NOV-14:02 | 29.33 | 17.25 | 0.175910E+10 | 2247.08 | 09-NOV-13:50 | 29.38 | 17.92 |
December | 0.281106E+10 | 23031.59 | 03-DEC-14:30 | 24.05 | 14.20 | 0.173636E+10 | 2273.35 | 06-DEC-10:39 | 20.70 | 12.58 |
Annual Sum or Average | 0.438368E+12 | 0.220325E+11 | ||||||||
Minimum of Months | 0.904565E+09 | 7940.15 | 22.50 | 13.87 | 0.162818E+10 | 2246.84 | 20.70 | 12.58 | ||
Maximum of Months | 0.717512E+11 | 113613.71 | 34.60 | 25.91 | 0.200322E+10 | 2273.35 | 38.60 | 25.91 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 7.83 | 7.49 | 0.348303E+10 | 6471.34 | 31-JAN-13:00 | 21.00 | 11.17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.85 | 0.386706E+10 | 7072.33 | 22-FEB-13:00 | 27.00 | 16.33 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.96 | 0.580865E+10 | 9097.65 | 10-MAR-13:20 | 31.80 | 19.67 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.77 | 0.675252E+10 | 9097.65 | 01-APR-12:09 | 33.13 | 20.92 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.24 | 0.742704E+10 | 9097.65 | 01-MAY-07:00 | 34.10 | 20.48 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.58 | 0.739279E+10 | 9097.65 | 01-JUN-12:09 | 32.47 | 21.64 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.65 | 0.679746E+10 | 9097.65 | 01-JUL-08:39 | 32.83 | 26.02 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 | 0.714450E+10 | 9097.65 | 01-AUG-10:39 | 31.77 | 25.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 | 0.634449E+10 | 9097.65 | 01-SEP-12:20 | 31.67 | 25.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.85 | 0.601289E+10 | 9097.65 | 02-OCT-10:09 | 32.65 | 20.76 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 | 0.459244E+10 | 8343.15 | 04-NOV-13:30 | 30.20 | 17.21 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.11 | 0.375049E+10 | 6432.88 | 02-DEC-11:30 | 21.85 | 12.75 |
Annual Sum or Average | 0.00 | 0.693734E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 7.83 | 7.49 | 0.348303E+10 | 6432.88 | 21.00 | 11.17 | ||
Maximum of Months | 0.00 | 0.00 | 32.95 | 26.26 | 0.742704E+10 | 9097.65 | 34.10 | 26.02 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.522525E+09 | 34654.68 | 02-JAN-06:01 | 6.45 |
February | 0.118837E+09 | 5530.14 | 03-FEB-07:05 | 8.50 |
March | 23900753.79 | 1188.01 | 22-MAR-06:10 | 17.87 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 32497747.41 | 1055.46 | 14-NOV-07:10 | 15.67 |
December | 0.155570E+09 | 5416.09 | 21-DEC-07:10 | 5.68 |
Annual Sum or Average | 0.853330E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.68 | |
Maximum of Months | 0.522525E+09 | 34654.68 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.325748E+10 | 26191.11 | 01-JAN-07:05 | 7.25 |
February | 0.124781E+10 | 6828.02 | 03-FEB-17:55 | 20.30 |
March | 0.383028E+09 | 5984.79 | 27-MAR-06:30 | 20.30 |
April | 4449068.69 | 4155.12 | 10-APR-06:05 | 18.85 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 48840524.71 | 4761.56 | 16-OCT-06:05 | 21.32 |
November | 0.517248E+09 | 5486.69 | 09-NOV-07:13 | 18.63 |
December | 0.193948E+10 | 7667.26 | 29-DEC-17:15 | 18.17 |
Annual Sum or Average | 0.739834E+10 | |||
Minimum of Months | 0.00 | 0.00 | 7.25 | |
Maximum of Months | 0.325748E+10 | 26191.11 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.252589E+10 | 47706.97 | 03-JAN-07:00 | 5.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.252589E+10 | |||
Minimum of Months | 0.00 | 0.00 | 5.40 | |
Maximum of Months | 0.252589E+10 | 47706.97 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.258145E+10 | 1955.04 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.235440E+10 | 1955.04 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.269003E+10 | 1955.04 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.254196E+10 | 1955.04 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.263574E+10 | 1955.04 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.259625E+10 | 1955.04 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.258145E+10 | 1955.04 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.269003E+10 | 1955.04 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.254196E+10 | 1955.04 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.258145E+10 | 1955.04 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.248766E+10 | 1955.04 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.258145E+10 | 1955.04 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.308638E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.235440E+10 | 1955.04 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.269003E+10 | 1955.04 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.198922E+11 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.182065E+11 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.210336E+11 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.197108E+11 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.204629E+11 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.202815E+11 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.198922E+11 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.210336E+11 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.197108E+11 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.198922E+11 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.191400E+11 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.198922E+11 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.239148E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.182065E+11 | 17848.24 | 0.00 | 0.00 | |
Maximum of Months | 0.210336E+11 | 17848.24 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.294120E+11 | 26389.90 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.269196E+11 | 26389.90 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.310997E+11 | 26389.90 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.291438E+11 | 26389.90 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.302559E+11 | 26389.90 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.299876E+11 | 26389.90 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.294120E+11 | 26389.90 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.310997E+11 | 26389.90 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.291438E+11 | 26389.90 | 01-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.294120E+11 | 26389.90 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.282999E+11 | 26389.90 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.294120E+11 | 26389.90 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.353598E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.269196E+11 | 26389.90 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.310997E+11 | 26389.90 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127978E+10 |
February | 0.127628E+10 | 0.235440E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26513625.52 | 0.932799E+09 |
March | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359597E+09 | 0.554103E+09 |
April | 0.138726E+10 | 0.254196E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112410E+10 | 86276768.32 |
May | 0.144276E+10 | 0.263574E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185284E+10 | 33334741.51 |
June | 0.144276E+10 | 0.259625E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171462E+10 | 13821392.09 |
July | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131153E+10 | 21632187.25 |
August | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111957E+10 | 28181486.87 |
September | 0.138726E+10 | 0.254196E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.824515E+09 | 41305392.51 |
October | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552540E+09 | 0.145094E+09 |
November | 0.133177E+10 | 0.248766E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161899E+09 | 0.441983E+09 |
December | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 375854.01 | 0.106301E+10 |
Annual Sum or Average | 0.168137E+11 | 0.308638E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904809E+10 | 0.464131E+10 |
Minimum of Months | 0.127628E+10 | 0.235440E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13821392.09 |
Maximum of Months | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185284E+10 | 0.127978E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245035E+10 |
February | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163502.92 | 0.291041E+10 |
March | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327318E+09 | 0.192229E+10 |
April | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201730E+10 | 0.246817E+09 |
May | 0.339505E+10 | 0.204629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385124E+10 | 90068621.80 |
June | 0.339505E+10 | 0.202815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284149E+10 | 43777573.29 |
July | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295792E+10 | 24537728.35 |
August | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165747E+10 | 41095703.42 |
September | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101963E+10 | 0.103334E+09 |
October | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504598E+09 | 0.267739E+09 |
November | 0.313390E+10 | 0.191400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44004076.38 | 0.696057E+09 |
December | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209441E+10 |
Annual Sum or Average | 0.395654E+11 | 0.239148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152212E+11 | 0.108909E+11 |
Minimum of Months | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24537728.35 |
Maximum of Months | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385124E+10 | 0.291041E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.880875E+10 |
February | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8363841.75 | 0.109198E+11 |
March | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2833962.49 | 0.100362E+11 |
April | 0.750829E+10 | 0.291438E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4765420.07 | 0.745592E+10 |
May | 0.780862E+10 | 0.302559E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28195922.34 | 0.834304E+10 |
June | 0.780862E+10 | 0.299876E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30478110.27 | 0.573155E+10 |
July | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2070644.91 | 0.671000E+10 |
August | 0.810895E+10 | 0.310997E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564756E+10 |
September | 0.750829E+10 | 0.291438E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24346657.16 | 0.457975E+10 |
October | 0.750829E+10 | 0.294120E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3090364.20 | 0.360501E+10 |
November | 0.720796E+10 | 0.282999E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360237E+10 |
December | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16641450.61 | 0.612773E+10 |
Annual Sum or Average | 0.910005E+11 | 0.353598E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120786E+09 | 0.815678E+11 |
Minimum of Months | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360237E+10 |
Maximum of Months | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30478110.27 | 0.109198E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1955.04 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6017.20 | 31-JAN-07:20 |
February | 1680.92 | 01-FEB-08:09 | 1955.04 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 933.60 | 22-FEB-13:00 | 5020.38 | 02-FEB-07:05 |
March | 1680.92 | 01-MAR-08:09 | 1955.04 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3924.23 | 27-MAR-16:10 | 3684.86 | 16-MAR-06:05 |
April | 1680.92 | 01-APR-07:10 | 1955.04 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7088.60 | 27-APR-16:10 | 1956.93 | 10-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 1955.04 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8520.01 | 05-MAY-16:10 | 432.40 | 15-MAY-05:01 |
June | 1680.92 | 01-JUN-07:10 | 1955.04 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8343.91 | 06-JUN-16:10 | 311.62 | 18-JUN-01:33 |
July | 1680.92 | 01-JUL-07:10 | 1955.04 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5668.62 | 06-JUL-16:10 | 300.51 | 26-JUL-05:01 |
August | 1680.92 | 01-AUG-07:10 | 1955.04 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5095.61 | 07-AUG-16:10 | 312.48 | 16-AUG-05:01 |
September | 1680.92 | 01-SEP-07:10 | 1955.04 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4315.37 | 27-SEP-16:10 | 347.75 | 19-SEP-05:01 |
October | 1680.92 | 02-OCT-07:10 | 1955.04 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4208.43 | 03-OCT-16:05 | 2794.47 | 31-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 1955.04 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1825.47 | 09-NOV-13:00 | 4403.91 | 27-NOV-07:05 |
December | 1680.92 | 01-DEC-08:09 | 1955.04 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 53.53 | 28-DEC-13:55 | 5753.61 | 21-DEC-07:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.51 | |||||
Maximum of Months | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 8520.01 | 6017.20 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6075.27 | 31-JAN-09:00 |
February | 3955.50 | 01-FEB-08:09 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.40 | 22-FEB-15:00 | 9101.69 | 09-FEB-16:10 |
March | 3955.50 | 01-MAR-08:09 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4336.90 | 27-MAR-15:10 | 10061.88 | 24-MAR-23:00 |
April | 3955.50 | 01-APR-07:10 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12686.84 | 15-APR-15:10 | 3094.35 | 22-APR-18:00 |
May | 3955.50 | 01-MAY-07:10 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13994.47 | 05-MAY-15:10 | 1334.15 | 15-MAY-04:25 |
June | 3955.50 | 01-JUN-07:10 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14246.40 | 06-JUN-15:10 | 1397.89 | 18-JUN-02:20 |
July | 3955.50 | 01-JUL-07:10 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7170.30 | 20-JUL-15:10 | 1075.59 | 19-JUL-02:30 |
August | 3955.50 | 01-AUG-07:10 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4567.28 | 07-AUG-15:10 | 1255.50 | 15-AUG-23:40 |
September | 3955.50 | 01-SEP-07:10 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4943.36 | 22-SEP-15:10 | 985.67 | 08-SEP-21:20 |
October | 3955.50 | 02-OCT-07:10 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5685.82 | 03-OCT-15:10 | 2009.03 | 12-OCT-03:00 |
November | 3955.50 | 01-NOV-07:10 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 694.89 | 03-NOV-15:10 | 2937.85 | 30-NOV-09:00 |
December | 3955.50 | 01-DEC-08:09 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 8637.49 | 29-DEC-17:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 985.67 | ||||
Maximum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14246.40 | 10061.88 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 26389.90 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 28585.85 | 24-JAN-13:10 |
February | 9097.65 | 01-FEB-08:09 | 26389.90 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1100.14 | 13-FEB-20:00 | 34172.47 | 18-FEB-11:00 |
March | 9097.65 | 01-MAR-08:09 | 26389.90 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 707.72 | 30-MAR-14:30 | 24174.46 | 01-MAR-11:00 |
April | 9097.65 | 01-APR-07:10 | 26389.90 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 863.96 | 22-APR-15:20 | 19010.48 | 17-APR-14:00 |
May | 9097.65 | 01-MAY-07:10 | 26389.90 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2830.18 | 31-MAY-14:40 | 16229.48 | 10-MAY-12:10 |
June | 9097.65 | 01-JUN-07:10 | 26389.90 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3194.82 | 03-JUN-17:50 | 16602.99 | 06-JUN-14:00 |
July | 9097.65 | 01-JUL-07:10 | 26389.90 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 574.42 | 24-JUL-17:10 | 15365.95 | 19-JUL-12:10 |
August | 9097.65 | 01-AUG-07:10 | 26389.90 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 14060.99 | 31-AUG-11:00 |
September | 9097.65 | 01-SEP-07:10 | 26389.90 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1662.81 | 12-SEP-12:10 | 15725.25 | 19-SEP-12:10 |
October | 9097.65 | 02-OCT-07:10 | 26389.90 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.46 | 22-OCT-20:20 | 10887.29 | 17-OCT-14:00 |
November | 9097.65 | 01-NOV-07:10 | 26389.90 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 15335.28 | 30-NOV-11:17 |
December | 9097.65 | 01-DEC-08:09 | 26389.90 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2839.91 | 22-DEC-07:25 | 20647.02 | 31-DEC-14:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10887.29 | |||||
Maximum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 3194.82 | 34172.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5024.80 | 14-JAN-16:00 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.29 |
February | 16356.90 | 25-FEB-06:03 | 739.61 | 2335.89 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.60 |
March | 29562.94 | 29-MAR-05:01 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.50 |
April | 29701.87 | 22-APR-05:01 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.65 |
May | 29670.76 | 09-MAY-05:01 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.50 |
June | 28261.48 | 03-JUN-05:01 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 | 0.00 |
July | 25157.48 | 07-JUL-05:01 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 117.57 | 0.00 |
August | 23785.16 | 07-AUG-05:01 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 30.48 | 0.00 |
September | 27246.76 | 27-SEP-05:01 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.76 |
October | 29514.94 | 25-OCT-05:01 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 380.30 |
November | 27847.85 | 03-NOV-05:02 | 1109.41 | 3503.84 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 658.28 |
December | 6611.41 | 01-DEC-15:20 | 3361.84 | 3910.08 | 3825.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5024.80 | 739.61 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29701.87 | 3361.84 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 117.57 | 658.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7940.15 | 26-JAN-13:52 | 19777.50 | 89241.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 830.15 |
February | 28925.83 | 20-FEB-15:45 | 0.00 | 4199.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.57 |
March | 103329.20 | 29-MAR-17:05 | 0.00 | 12598.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2752.18 | 0.00 |
April | 113275.09 | 29-APR-19:02 | 0.00 | 10498.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 574.95 | 0.00 |
May | 113613.71 | 08-MAY-21:02 | 0.00 | 10498.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1264.46 | 0.00 |
June | 110585.12 | 12-JUN-05:01 | 4351.05 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1579.46 | 0.00 |
July | 106486.34 | 07-JUL-05:01 | 4351.05 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.43 | 0.00 |
August | 99847.25 | 09-AUG-05:01 | 4351.05 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 495.28 | 0.00 |
September | 104617.24 | 26-SEP-17:05 | 0.00 | 12598.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1321.39 | 0.00 |
October | 109368.84 | 01-OCT-12:22 | 0.00 | 12598.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1260.60 | 0.00 |
November | 97868.80 | 05-NOV-14:02 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.31 | 0.00 |
December | 23031.59 | 03-DEC-14:30 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 7940.15 | 0.00 | 4199.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 113613.71 | 19777.50 | 89241.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2752.18 | 830.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 6209.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.71 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1124.77 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.84 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1133.33 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 947.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 6209.39 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1133.33 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.917907E+11 | 77473.20 | 12-JAN-14:50 | 0.423496E+10 | 88911.53 | 02-JAN-06:10 |
February | 0.868154E+11 | 85392.46 | 22-FEB-14:39 | 0.102164E+09 | 6481.13 | 01-FEB-07:10 |
March | 0.109105E+12 | 97430.92 | 28-MAR-14:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.119543E+12 | 107785.93 | 27-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.138746E+12 | 115042.10 | 03-MAY-14:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.139239E+12 | 116594.23 | 06-JUN-14:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.135401E+12 | 112132.68 | 06-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.135533E+12 | 108794.36 | 07-AUG-14:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.120413E+12 | 103678.06 | 22-SEP-14:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.111970E+12 | 102545.13 | 03-OCT-14:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.967450E+11 | 89952.48 | 09-NOV-13:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.933107E+11 | 80712.86 | 01-DEC-13:00 | 0.142637E+09 | 7732.24 | 21-DEC-07:19 |
Annual Sum or Average | 0.137861E+13 | 0.447976E+10 | ||||
Minimum of Months | 0.868154E+11 | 77473.20 | 0.00 | 0.00 | ||
Maximum of Months | 0.139239E+12 | 116594.23 | 0.423496E+10 | 88911.53 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.518856E+11 | 0.128905E+11 | 0.115358E+11 | 0.00 | 0.116161E+11 | 0.00 | 0.00 | 0.174936E+10 | 0.00 | 0.00 | 0.00 | 0.211333E+10 | 0.00 |
February | 0.474804E+11 | 0.111550E+11 | 0.105871E+11 | 0.00 | 0.110902E+11 | 0.00 | 0.00 | 0.460139E+10 | 0.00 | 0.00 | 0.00 | 0.190131E+10 | 0.00 |
March | 0.548234E+11 | 0.115595E+11 | 0.123431E+11 | 0.00 | 0.146107E+11 | 0.00 | 0.00 | 0.136795E+11 | 0.00 | 0.00 | 0.00 | 0.208866E+10 | 0.00 |
April | 0.513965E+11 | 0.104127E+11 | 0.114862E+11 | 0.00 | 0.170426E+11 | 0.00 | 0.00 | 0.272776E+11 | 0.00 | 0.00 | 0.00 | 0.192735E+10 | 0.00 |
May | 0.533545E+11 | 0.100800E+11 | 0.119357E+11 | 0.00 | 0.204635E+11 | 0.00 | 0.00 | 0.409862E+11 | 0.00 | 0.00 | 0.00 | 0.192637E+10 | 0.00 |
June | 0.528654E+11 | 0.938885E+10 | 0.118862E+11 | 0.00 | 0.203582E+11 | 0.00 | 0.00 | 0.429137E+11 | 0.00 | 0.00 | 0.00 | 0.182699E+10 | 0.00 |
July | 0.518856E+11 | 0.990079E+10 | 0.115358E+11 | 0.00 | 0.200791E+11 | 0.00 | 0.00 | 0.401639E+11 | 0.00 | 0.00 | 0.00 | 0.183611E+10 | 0.00 |
August | 0.548234E+11 | 0.104486E+11 | 0.123357E+11 | 0.00 | 0.196464E+11 | 0.00 | 0.00 | 0.363955E+11 | 0.00 | 0.00 | 0.00 | 0.188351E+10 | 0.00 |
September | 0.513965E+11 | 0.108530E+11 | 0.114788E+11 | 0.00 | 0.164024E+11 | 0.00 | 0.00 | 0.284297E+11 | 0.00 | 0.00 | 0.00 | 0.185217E+10 | 0.00 |
October | 0.518856E+11 | 0.120202E+11 | 0.115432E+11 | 0.00 | 0.147510E+11 | 0.00 | 0.00 | 0.198055E+11 | 0.00 | 0.00 | 0.00 | 0.196497E+10 | 0.00 |
November | 0.499276E+11 | 0.123018E+11 | 0.110862E+11 | 0.00 | 0.123422E+11 | 0.00 | 0.00 | 0.912303E+10 | 0.00 | 0.00 | 0.00 | 0.196418E+10 | 0.00 |
December | 0.518856E+11 | 0.131311E+11 | 0.115358E+11 | 0.00 | 0.116143E+11 | 0.00 | 0.00 | 0.305406E+10 | 0.00 | 0.00 | 0.00 | 0.208984E+10 | 0.00 |
Annual Sum or Average | 0.623610E+12 | 0.134142E+12 | 0.139290E+12 | 0.00 | 0.190017E+12 | 0.00 | 0.00 | 0.268179E+12 | 0.00 | 0.00 | 0.00 | 0.233748E+11 | 0.00 |
Minimum of Months | 0.474804E+11 | 0.938885E+10 | 0.105871E+11 | 0.00 | 0.110902E+11 | 0.00 | 0.00 | 0.174936E+10 | 0.00 | 0.00 | 0.00 | 0.182699E+10 | 0.00 |
Maximum of Months | 0.548234E+11 | 0.131311E+11 | 0.123431E+11 | 0.00 | 0.204635E+11 | 0.00 | 0.00 | 0.429137E+11 | 0.00 | 0.00 | 0.00 | 0.211333E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.423496E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.102164E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.142637E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.447976E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.423496E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 46193.18 | 02-JAN-09:09 | 8532.22 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 12809.21 | 31-JAN-12:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 46193.18 | 01-FEB-09:09 | 8532.22 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 13961.85 | 21-FEB-13:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 46193.18 | 01-MAR-09:09 | 8532.22 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 13961.85 | 24-MAR-15:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 46193.18 | 01-APR-08:09 | 8532.22 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 13961.85 | 01-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 46193.18 | 01-MAY-08:09 | 8532.22 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 13961.85 | 02-MAY-13:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 46193.18 | 01-JUN-08:09 | 8532.22 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 13961.85 | 22-JUN-07:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 46193.18 | 01-JUL-08:09 | 8532.22 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 13961.85 | 01-JUL-06:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 46193.18 | 01-AUG-08:09 | 8532.22 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 13961.85 | 04-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 46193.18 | 01-SEP-08:09 | 8532.22 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 13961.85 | 01-SEP-08:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 46193.18 | 02-OCT-08:09 | 8532.22 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 13961.85 | 13-OCT-15:39 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 46193.18 | 01-NOV-08:09 | 8532.22 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 13961.85 | 21-NOV-14:39 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 46193.18 | 01-DEC-09:09 | 8532.22 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 13193.42 | 01-DEC-13:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 46193.18 | 8532.22 | 10112.62 | 0.00 | 12809.21 | 0.00 | 0.00 | |||||
Maximum of Months | 46193.18 | 8532.22 | 10112.62 | 0.00 | 13961.85 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 6665.80 | 12-JAN-14:00 | 0.00 | 0.00 | 0.00 | 1776.64 | 17-JAN-12:09 | 0.00 |
February | 13421.01 | 22-FEB-14:39 | 0.00 | 0.00 | 0.00 | 1774.61 | 01-FEB-12:20 | 0.00 |
March | 25577.21 | 28-MAR-14:00 | 0.00 | 0.00 | 0.00 | 1761.79 | 01-MAR-12:39 | 0.00 |
April | 38210.39 | 27-APR-15:09 | 0.00 | 0.00 | 0.00 | 1736.83 | 01-APR-11:39 | 0.00 |
May | 45718.10 | 05-MAY-15:09 | 0.00 | 0.00 | 0.00 | 1709.52 | 01-MAY-11:50 | 0.00 |
June | 47732.59 | 06-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1685.41 | 01-JUN-11:50 | 0.00 |
July | 40483.65 | 06-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1671.72 | 01-JUL-11:09 | 0.00 |
August | 37736.66 | 07-AUG-15:30 | 0.00 | 0.00 | 0.00 | 1682.53 | 31-AUG-11:50 | 0.00 |
September | 32456.91 | 22-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1704.46 | 30-SEP-11:30 | 0.00 |
October | 30796.66 | 03-OCT-15:09 | 0.00 | 0.00 | 0.00 | 1732.61 | 31-OCT-11:00 | 0.00 |
November | 17979.41 | 09-NOV-13:50 | 0.00 | 0.00 | 0.00 | 1757.87 | 30-NOV-12:50 | 0.00 |
December | 9545.59 | 02-DEC-14:30 | 0.00 | 0.00 | 0.00 | 1773.80 | 30-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6665.80 | 0.00 | 0.00 | 0.00 | 1671.72 | 0.00 | ||
Maximum of Months | 47732.59 | 0.00 | 0.00 | 0.00 | 1776.64 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 77473.20 | 12-JAN-14:50 | 46193.18 | 10112.62 | 0.00 | 0.00 | 12809.21 | 0.00 | 0.00 | 6647.16 | 0.00 |
February | 85392.46 | 22-FEB-14:39 | 46193.18 | 10112.62 | 0.00 | 0.00 | 13961.85 | 0.00 | 0.00 | 13421.01 | 0.00 |
March | 97430.92 | 28-MAR-14:50 | 46193.18 | 10112.62 | 0.00 | 0.00 | 13961.85 | 0.00 | 0.00 | 25451.29 | 0.00 |
April | 107785.93 | 27-APR-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 13961.85 | 0.00 | 0.00 | 35829.43 | 0.00 |
May | 115042.10 | 03-MAY-14:50 | 46193.18 | 10112.62 | 0.00 | 0.00 | 13961.85 | 0.00 | 0.00 | 43090.05 | 0.00 |
June | 116594.23 | 06-JUN-14:50 | 46193.18 | 10112.62 | 0.00 | 0.00 | 13961.85 | 0.00 | 0.00 | 44663.74 | 0.00 |
July | 112132.68 | 06-JUL-13:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 13961.85 | 0.00 | 0.00 | 40229.30 | 0.00 |
August | 108794.36 | 07-AUG-14:30 | 46193.18 | 10112.62 | 0.00 | 0.00 | 13961.85 | 0.00 | 0.00 | 36872.60 | 0.00 |
September | 103678.06 | 22-SEP-14:39 | 46193.18 | 10112.62 | 0.00 | 0.00 | 13961.85 | 0.00 | 0.00 | 31734.01 | 0.00 |
October | 102545.13 | 03-OCT-14:09 | 46193.18 | 10112.62 | 0.00 | 0.00 | 13961.85 | 0.00 | 0.00 | 30593.66 | 0.00 |
November | 89952.48 | 09-NOV-13:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 13961.85 | 0.00 | 0.00 | 17972.13 | 0.00 |
December | 80712.86 | 01-DEC-13:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 13193.42 | 0.00 | 0.00 | 9485.76 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 77473.20 | 46193.18 | 10112.62 | 0.00 | 0.00 | 12809.21 | 0.00 | 0.00 | 6647.16 | 0.00 | |
Maximum of Months | 116594.23 | 46193.18 | 10112.62 | 0.00 | 0.00 | 13961.85 | 0.00 | 0.00 | 44663.74 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 88911.53 | 02-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 6481.13 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 7732.24 | 21-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 88911.53 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 20.15 | 0.67 | 20.15 | 0.00 | 20.15 | 0.00 | 20.15 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.52 | 0.17 | 24.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.97 | 2.00 | 24.77 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 26.00 | 6.83 | 25.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 27.80 | 8.83 | 26.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 27.77 | 9.00 | 27.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 28.04 | 9.33 | 27.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 27.00 | 9.50 | 26.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 26.17 | 8.33 | 25.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 25.42 | 5.50 | 25.10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.49 | 0.33 | 24.49 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 20.15 | 0.67 | 20.15 | 99.33 | 27.08 | 59.83 | 26.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.15 | 0.67 | 20.15 | 20.67 | 28.04 | 9.50 | 27.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.33 | 0.00 | 27.33 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.69 | 0.00 | 27.69 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 64.33 | 27.85 | 0.50 | 27.84 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 101.17 | 28.07 | 3.17 | 28.05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 98.00 | 28.11 | 3.83 | 28.09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 105.67 | 27.98 | 3.00 | 27.97 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 92.50 | 27.74 | 3.00 | 27.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 64.67 | 27.63 | 0.50 | 27.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 31.83 | 27.75 | 0.17 | 27.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.58 | 0.00 | 27.58 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 14.97 | 0.00 | 14.97 | 576.67 | 27.89 | 14.17 | 27.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 14.97 | 0.00 | 14.97 | 105.67 | 28.11 | 3.83 | 28.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 245.00 | 23.08 | 25.67 | 22.91 | 23.83 | 22.76 |
February | 117.00 | 23.12 | 71.50 | 23.41 | 0.50 | 23.40 |
March | 21.67 | 23.56 | 251.67 | 23.88 | 0.00 | 23.88 |
April | 0.00 | 0.00 | 298.00 | 23.92 | 0.00 | 23.92 |
May | 11.50 | 24.36 | 312.00 | 23.96 | 11.50 | 23.97 |
June | 44.00 | 24.17 | 312.00 | 23.98 | 44.00 | 24.00 |
July | 95.67 | 24.08 | 300.00 | 23.99 | 95.67 | 24.01 |
August | 110.33 | 24.05 | 324.00 | 23.98 | 110.33 | 23.99 |
September | 60.67 | 24.04 | 300.00 | 23.96 | 60.67 | 23.97 |
October | 3.17 | 24.00 | 299.67 | 23.92 | 3.17 | 23.92 |
November | 29.00 | 23.44 | 195.50 | 23.84 | 0.00 | 23.84 |
December | 174.33 | 23.15 | 20.67 | 23.18 | 3.17 | 23.14 |
Annual Sum or Average | 912.33 | 23.48 | 2710.67 | 23.80 | 352.83 | 23.80 |
Minimum of Months | 0.00 | 0.00 | 20.67 | 22.91 | 0.00 | 22.76 |
Maximum of Months | 245.00 | 24.36 | 324.00 | 23.99 | 110.33 | 24.01 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 127.00 | 21.33 | 209.33 | 23.35 | 55.33 | 22.73 |
February | 97.83 | 23.75 | 215.33 | 25.44 | 46.17 | 25.36 |
March | 213.33 | 26.52 | 303.50 | 26.57 | 201.67 | 26.61 |
April | 256.00 | 26.70 | 300.00 | 26.70 | 256.00 | 26.70 |
May | 311.67 | 26.71 | 312.00 | 26.71 | 311.67 | 26.71 |
June | 310.83 | 26.71 | 312.00 | 26.71 | 310.83 | 26.71 |
July | 300.00 | 26.71 | 300.00 | 26.71 | 300.00 | 26.71 |
August | 321.83 | 26.71 | 324.00 | 26.71 | 321.83 | 26.71 |
September | 290.67 | 26.71 | 300.00 | 26.71 | 290.67 | 26.71 |
October | 236.17 | 26.70 | 300.00 | 26.68 | 236.17 | 26.69 |
November | 153.50 | 26.05 | 249.33 | 26.40 | 124.83 | 26.47 |
December | 91.83 | 22.00 | 219.50 | 24.71 | 25.50 | 24.34 |
Annual Sum or Average | 2710.67 | 26.14 | 3345.00 | 26.32 | 2480.67 | 26.35 |
Minimum of Months | 91.83 | 21.33 | 209.33 | 23.35 | 25.50 | 22.73 |
Maximum of Months | 321.83 | 26.71 | 324.00 | 26.71 | 321.83 | 26.71 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 234.00 | 20.98 | 232.33 | 21.42 | 176.67 | 21.16 |
February | 241.83 | 24.81 | 231.17 | 25.12 | 202.83 | 25.19 |
March | 292.83 | 29.45 | 278.50 | 29.80 | 253.50 | 30.05 |
April | 281.83 | 35.77 | 296.50 | 35.53 | 279.00 | 35.65 |
May | 312.00 | 38.43 | 312.00 | 38.43 | 312.00 | 38.43 |
June | 312.00 | 38.44 | 312.00 | 38.44 | 312.00 | 38.44 |
July | 300.00 | 35.19 | 300.00 | 35.19 | 300.00 | 35.19 |
August | 324.00 | 33.75 | 324.00 | 33.75 | 324.00 | 33.75 |
September | 300.00 | 32.77 | 300.00 | 32.77 | 300.00 | 32.77 |
October | 278.50 | 31.56 | 274.17 | 31.72 | 257.17 | 31.91 |
November | 253.83 | 27.01 | 250.17 | 27.29 | 222.17 | 27.44 |
December | 235.17 | 22.33 | 235.00 | 22.77 | 181.00 | 22.63 |
Annual Sum or Average | 3366.00 | 31.44 | 3345.83 | 31.59 | 3120.33 | 31.77 |
Minimum of Months | 234.00 | 20.98 | 231.17 | 21.42 | 176.67 | 21.16 |
Maximum of Months | 324.00 | 38.44 | 324.00 | 38.44 | 324.00 | 38.44 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.269763E+10 | 0.731198E+09 | 195.05 | 0.252802E+10 | 0.169601E+09 | 0.00 | 0.26 | 14-JAN-15:50 | 0.00 | 01-JAN-00:05 | 7201.56 | 14-JAN-15:50 | 6619.89 | 12-JAN-15:40 | 1157.41 | 17-JAN-14:50 | 1922.64 | 14-JAN-15:50 | 0.00 | 01-JAN-00:05 |
February | 0.458130E+10 | 0.123608E+10 | 217.06 | 0.419663E+10 | 0.384677E+09 | 0.00 | 0.71 | 25-FEB-06:03 | 0.00 | 01-FEB-00:10 | 21786.48 | 25-FEB-06:03 | 18211.99 | 25-FEB-06:03 | 3574.49 | 25-FEB-06:03 | 5383.16 | 25-FEB-06:03 | 0.00 | 01-FEB-00:10 |
March | 0.972558E+10 | 0.270732E+10 | 302.52 | 0.890720E+10 | 0.818379E+09 | 0.00 | 1.00 | 07-MAR-06:02 | 0.00 | 01-MAR-00:10 | 34290.36 | 11-MAR-06:01 | 31951.24 | 29-MAR-05:01 | 7650.51 | 11-MAR-06:03 | 7958.90 | 11-MAR-06:01 | 0.00 | 01-MAR-00:10 |
April | 0.140253E+11 | 0.424337E+10 | 322.20 | 0.130639E+11 | 0.961434E+09 | 0.00 | 1.00 | 01-APR-05:01 | 0.00 | 01-APR-00:10 | 34744.73 | 03-APR-05:01 | 32199.96 | 15-APR-05:01 | 8196.62 | 03-APR-05:04 | 8315.02 | 27-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.196968E+11 | 0.619502E+10 | 399.01 | 0.168538E+11 | 0.284300E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 38677.96 | 24-MAY-05:01 | 32529.11 | 09-MAY-05:01 | 17612.15 | 24-MAY-05:06 | 9699.14 | 07-MAY-15:01 | 0.00 | 01-MAY-00:10 |
June | 0.216448E+11 | 0.665931E+10 | 405.63 | 0.171153E+11 | 0.452949E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 38585.30 | 26-JUN-05:01 | 31433.16 | 13-JUN-05:01 | 21056.60 | 26-JUN-05:06 | 9928.04 | 11-JUN-15:41 | 0.00 | 01-JUN-00:10 |
July | 0.224365E+11 | 0.642462E+10 | 394.88 | 0.154518E+11 | 0.698473E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 39041.16 | 19-JUL-05:02 | 28263.28 | 07-JUL-05:01 | 22749.98 | 20-JUL-05:08 | 9800.68 | 02-JUL-15:41 | 0.00 | 01-JUL-00:10 |
August | 0.228443E+11 | 0.635879E+10 | 366.78 | 0.152544E+11 | 0.758983E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 39576.57 | 16-AUG-05:01 | 26512.40 | 07-AUG-05:01 | 21846.10 | 19-AUG-05:07 | 8927.81 | 31-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.183869E+11 | 0.512681E+10 | 319.00 | 0.131029E+11 | 0.528397E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 39413.04 | 09-SEP-05:01 | 29562.30 | 27-SEP-05:01 | 22357.37 | 11-SEP-05:06 | 8829.14 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 0.131009E+11 | 0.369355E+10 | 313.99 | 0.112496E+11 | 0.185129E+10 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 37028.07 | 12-OCT-05:01 | 31637.59 | 25-OCT-05:01 | 14723.73 | 12-OCT-05:04 | 8391.32 | 12-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.760769E+10 | 0.208385E+10 | 257.93 | 0.702030E+10 | 0.587385E+09 | 0.00 | 1.00 | 01-NOV-05:01 | 0.00 | 01-NOV-00:10 | 32689.65 | 09-NOV-06:01 | 30604.49 | 03-NOV-05:02 | 4747.43 | 09-NOV-06:01 | 7666.33 | 09-NOV-06:01 | 0.00 | 01-NOV-00:10 |
December | 0.379577E+10 | 0.102505E+10 | 227.00 | 0.357159E+10 | 0.224179E+09 | 0.00 | 0.31 | 02-DEC-15:10 | 0.00 | 01-DEC-00:10 | 8364.97 | 02-DEC-15:10 | 8238.41 | 02-DEC-14:55 | 854.88 | 16-DEC-16:00 | 2221.62 | 02-DEC-15:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.160544E+12 | 0.464850E+11 | 3721.04 | 0.128316E+12 | 0.322280E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.269763E+10 | 0.731198E+09 | 195.05 | 0.252802E+10 | 0.169601E+09 | 0.00 | 0.26 | 0.00 | 7201.56 | 6619.89 | 854.88 | 1922.64 | 0.00 | |||||||
Maximum of Months | 0.228443E+11 | 0.665931E+10 | 405.63 | 0.171153E+11 | 0.758983E+10 | 0.00 | 1.00 | 0.00 | 39576.57 | 32529.11 | 22749.98 | 9928.04 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.343411E+10 | 0.101816E+10 | 114.04 | 0.322395E+10 | 0.210168E+09 | 0.00 | 0.14 | 26-JAN-13:52 | 0.00 | 01-JAN-00:05 | 16869.07 | 26-JAN-13:52 | 15895.48 | 12-JAN-14:50 | 2159.16 | 13-JAN-14:40 | 4960.46 | 26-JAN-13:52 | 0.00 | 01-JAN-00:05 |
February | 0.114090E+11 | 0.336531E+10 | 180.25 | 0.105357E+11 | 0.873284E+09 | 0.00 | 0.29 | 22-FEB-14:30 | 0.00 | 01-FEB-00:10 | 35225.43 | 22-FEB-14:30 | 33719.33 | 22-FEB-14:30 | 5638.02 | 25-FEB-15:50 | 10690.84 | 22-FEB-14:30 | 0.00 | 01-FEB-00:10 |
March | 0.358914E+11 | 0.109722E+11 | 338.61 | 0.333070E+11 | 0.258435E+10 | 0.00 | 0.93 | 28-MAR-17:05 | 0.00 | 01-MAR-00:10 | 120744.41 | 29-MAR-17:05 | 120209.93 | 29-MAR-17:05 | 9215.47 | 10-MAR-18:08 | 37917.75 | 28-MAR-17:05 | 0.00 | 01-MAR-00:10 |
April | 0.695423E+11 | 0.230342E+11 | 514.75 | 0.662035E+11 | 0.333878E+10 | 0.00 | 1.00 | 01-APR-17:05 | 0.00 | 01-APR-00:10 | 138037.68 | 02-APR-13:52 | 132150.88 | 29-APR-19:02 | 16503.18 | 02-APR-10:32 | 44615.02 | 16-APR-15:02 | 0.00 | 01-APR-00:10 |
May | 0.101181E+12 | 0.347911E+11 | 591.13 | 0.905697E+11 | 0.106109E+11 | 0.00 | 1.00 | 01-MAY-17:03 | 0.00 | 01-MAY-00:13 | 150670.35 | 20-MAY-21:03 | 133490.06 | 14-MAY-13:02 | 42588.17 | 20-MAY-21:42 | 46472.69 | 07-MAY-15:01 | 0.00 | 01-MAY-00:10 |
June | 0.106672E+12 | 0.362544E+11 | 581.52 | 0.902997E+11 | 0.163721E+11 | 0.00 | 1.00 | 01-JUN-17:04 | 0.00 | 01-JUN-00:13 | 160263.98 | 17-JUN-23:03 | 131832.45 | 18-JUN-15:42 | 58071.35 | 17-JUN-23:03 | 47317.92 | 11-JUN-15:41 | 0.00 | 01-JUN-00:10 |
July | 0.106092E+12 | 0.337393E+11 | 595.21 | 0.787464E+11 | 0.273459E+11 | 0.00 | 1.00 | 01-JUL-17:04 | 0.00 | 01-JUL-00:12 | 157854.09 | 03-JUL-05:01 | 129438.63 | 04-JUL-15:41 | 55036.64 | 12-JUL-05:01 | 46042.96 | 02-JUL-15:41 | 0.00 | 01-JUL-00:10 |
August | 0.970706E+11 | 0.300368E+11 | 594.43 | 0.705682E+11 | 0.265025E+11 | 0.00 | 1.00 | 01-AUG-17:05 | 0.00 | 01-AUG-00:13 | 157768.02 | 10-AUG-05:01 | 121768.40 | 06-AUG-15:42 | 54957.79 | 10-AUG-05:01 | 44156.98 | 06-AUG-15:02 | 0.00 | 01-AUG-00:10 |
September | 0.752932E+11 | 0.233029E+11 | 545.71 | 0.576175E+11 | 0.176758E+11 | 0.00 | 1.00 | 01-SEP-17:05 | 0.00 | 01-SEP-00:13 | 147448.30 | 14-SEP-17:05 | 125583.77 | 24-SEP-13:42 | 47598.21 | 09-SEP-05:07 | 43135.72 | 17-SEP-14:22 | 0.00 | 01-SEP-00:10 |
October | 0.517292E+11 | 0.161119E+11 | 434.62 | 0.462457E+11 | 0.548351E+10 | 0.00 | 1.00 | 01-OCT-11:42 | 0.00 | 01-OCT-00:15 | 133873.49 | 01-OCT-11:42 | 133873.49 | 01-OCT-11:42 | 17083.88 | 03-OCT-17:05 | 42138.92 | 01-OCT-14:22 | 0.00 | 01-OCT-00:10 |
November | 0.233841E+11 | 0.703918E+10 | 252.95 | 0.217448E+11 | 0.163921E+10 | 0.00 | 0.85 | 05-NOV-14:02 | 0.00 | 01-NOV-00:10 | 113145.20 | 05-NOV-14:02 | 113145.20 | 05-NOV-14:02 | 5879.90 | 19-NOV-12:32 | 32602.45 | 05-NOV-14:02 | 0.00 | 01-NOV-00:10 |
December | 0.687808E+10 | 0.202901E+10 | 164.46 | 0.642440E+10 | 0.453681E+09 | 0.00 | 0.21 | 01-DEC-14:07 | 0.00 | 01-DEC-00:10 | 25695.96 | 03-DEC-14:30 | 25442.89 | 01-DEC-14:07 | 2277.30 | 16-DEC-14:30 | 7498.54 | 03-DEC-14:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.688577E+12 | 0.221694E+12 | 4907.69 | 0.575487E+12 | 0.113090E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.343411E+10 | 0.101816E+10 | 114.04 | 0.322395E+10 | 0.210168E+09 | 0.00 | 0.14 | 0.00 | 16869.07 | 15895.48 | 2159.16 | 4960.46 | 0.00 | |||||||
Maximum of Months | 0.106672E+12 | 0.362544E+11 | 595.21 | 0.905697E+11 | 0.273459E+11 | 0.00 | 1.00 | 0.00 | 160263.98 | 133873.49 | 58071.35 | 47317.92 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.55 | 17.46 | 27.09 | 76.04 | 166.42 | 16.33 | 0.00 | 0.00 |
February | 50.78 | 18.78 | 32.00 | 104.25 | 142.60 | 0.00 | 0.00 | 0.00 |
March | 65.91 | 26.43 | 39.47 | 174.38 | 96.73 | 0.00 | 0.00 | 0.00 |
April | 79.60 | 37.17 | 42.43 | 278.18 | 45.35 | 0.00 | 0.00 | 0.00 |
May | 75.63 | 32.07 | 43.56 | 311.87 | 16.61 | 0.00 | 0.00 | 0.00 |
June | 71.46 | 28.01 | 43.45 | 309.69 | 13.59 | 0.00 | 0.00 | 0.00 |
July | 52.75 | 10.27 | 42.47 | 220.82 | 7.73 | 0.00 | 0.00 | 0.00 |
August | 48.30 | 8.47 | 39.84 | 190.12 | 15.45 | 0.00 | 0.00 | 0.00 |
September | 53.29 | 15.72 | 37.58 | 180.14 | 34.35 | 0.00 | 0.00 | 0.00 |
October | 55.67 | 22.31 | 33.36 | 173.15 | 86.72 | 0.00 | 0.00 | 0.00 |
November | 50.56 | 21.80 | 28.76 | 124.46 | 139.31 | 0.00 | 0.00 | 0.00 |
December | 43.23 | 16.70 | 26.54 | 75.51 | 172.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.63 | 21.24 | 36.40 | 185.13 | 77.82 | 16.33 | 0.00 | 0.00 |
Minimum of Months | 43.23 | 8.47 | 26.54 | 75.51 | 7.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 79.60 | 37.17 | 43.56 | 311.87 | 172.78 | 16.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.55 | 17.46 | 27.09 | 76.04 | 166.42 | 16.33 | 0.00 | 0.00 |
February | 50.78 | 18.78 | 32.00 | 104.25 | 142.60 | 0.00 | 0.00 | 0.00 |
March | 65.91 | 26.43 | 39.47 | 174.38 | 96.73 | 0.00 | 0.00 | 0.00 |
April | 79.60 | 37.17 | 42.43 | 278.18 | 45.35 | 0.00 | 0.00 | 0.00 |
May | 75.63 | 32.07 | 43.56 | 311.87 | 16.61 | 0.00 | 0.00 | 0.00 |
June | 71.46 | 28.01 | 43.45 | 309.69 | 13.59 | 0.00 | 0.00 | 0.00 |
July | 52.75 | 10.27 | 42.47 | 220.82 | 7.73 | 0.00 | 0.00 | 0.00 |
August | 48.30 | 8.47 | 39.84 | 190.12 | 15.45 | 0.00 | 0.00 | 0.00 |
September | 53.29 | 15.72 | 37.58 | 180.14 | 34.35 | 0.00 | 0.00 | 0.00 |
October | 55.67 | 22.31 | 33.36 | 173.15 | 86.72 | 0.00 | 0.00 | 0.00 |
November | 50.56 | 21.80 | 28.76 | 124.46 | 139.31 | 0.00 | 0.00 | 0.00 |
December | 43.23 | 16.70 | 26.54 | 75.51 | 172.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.63 | 21.24 | 36.40 | 185.13 | 77.82 | 16.33 | 0.00 | 0.00 |
Minimum of Months | 43.23 | 8.47 | 26.54 | 75.51 | 7.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 79.60 | 37.17 | 43.56 | 311.87 | 172.78 | 16.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.34 | 0.00 | 12.34 | 7.12 | 100.68 | 16.67 | 0.00 | 0.00 |
February | 14.63 | 0.00 | 14.63 | 17.15 | 84.99 | 0.00 | 0.00 | 0.00 |
March | 17.64 | 0.00 | 17.63 | 39.41 | 57.38 | 0.00 | 0.00 | 0.00 |
April | 19.23 | 0.15 | 19.08 | 77.08 | 26.23 | 0.00 | 0.00 | 0.00 |
May | 21.55 | 0.94 | 20.60 | 110.57 | 9.60 | 0.00 | 0.00 | 0.00 |
June | 22.20 | 1.08 | 21.12 | 118.40 | 7.99 | 0.00 | 0.00 | 0.00 |
July | 21.82 | 0.51 | 21.30 | 100.30 | 4.42 | 0.00 | 0.00 | 0.00 |
August | 19.98 | 0.16 | 19.82 | 84.34 | 8.93 | 0.00 | 0.00 | 0.00 |
September | 17.70 | 0.00 | 17.70 | 62.46 | 19.97 | 0.00 | 0.00 | 0.00 |
October | 15.33 | 0.00 | 15.33 | 46.04 | 50.43 | 0.00 | 0.00 | 0.00 |
November | 12.99 | 0.00 | 12.99 | 21.39 | 82.09 | 0.00 | 0.00 | 0.00 |
December | 12.04 | 0.00 | 12.04 | 8.22 | 105.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 17.30 | 0.24 | 17.06 | 57.91 | 46.30 | 16.67 | 0.00 | 0.00 |
Minimum of Months | 12.04 | 0.00 | 12.04 | 7.12 | 4.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.20 | 1.08 | 21.30 | 118.40 | 105.05 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.34 | 0.00 | 12.34 | 7.12 | 100.68 | 16.67 | 0.00 | 0.00 |
February | 14.63 | 0.00 | 14.63 | 17.15 | 84.99 | 0.00 | 0.00 | 0.00 |
March | 17.64 | 0.00 | 17.63 | 39.41 | 57.38 | 0.00 | 0.00 | 0.00 |
April | 19.23 | 0.15 | 19.08 | 77.08 | 26.23 | 0.00 | 0.00 | 0.00 |
May | 21.55 | 0.94 | 20.60 | 110.57 | 9.60 | 0.00 | 0.00 | 0.00 |
June | 22.20 | 1.08 | 21.12 | 118.40 | 7.99 | 0.00 | 0.00 | 0.00 |
July | 21.82 | 0.51 | 21.30 | 100.30 | 4.42 | 0.00 | 0.00 | 0.00 |
August | 19.98 | 0.16 | 19.82 | 84.34 | 8.93 | 0.00 | 0.00 | 0.00 |
September | 17.70 | 0.00 | 17.70 | 62.46 | 19.97 | 0.00 | 0.00 | 0.00 |
October | 15.33 | 0.00 | 15.33 | 46.04 | 50.43 | 0.00 | 0.00 | 0.00 |
November | 12.99 | 0.00 | 12.99 | 21.39 | 82.09 | 0.00 | 0.00 | 0.00 |
December | 12.04 | 0.00 | 12.04 | 8.22 | 105.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 17.30 | 0.24 | 17.06 | 57.91 | 46.30 | 16.67 | 0.00 | 0.00 |
Minimum of Months | 12.04 | 0.00 | 12.04 | 7.12 | 4.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.20 | 1.08 | 21.30 | 118.40 | 105.05 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 78.34 | 56.51 | 228.50 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 102.16 | 54.63 | 60.00 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 142.59 | 52.14 | 2.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 186.91 | 48.83 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 196.86 | 40.12 | 3.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 185.38 | 37.37 | 16.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 130.60 | 24.96 | 12.17 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 114.60 | 24.59 | 47.83 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 113.43 | 33.42 | 62.67 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 128.90 | 54.89 | 7.17 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 104.53 | 60.98 | 11.50 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 75.84 | 60.39 | 168.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 130.05 | 45.67 | 619.67 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 75.84 | 24.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 196.86 | 60.98 | 228.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 78.34 | 56.51 | 228.50 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 102.16 | 54.63 | 60.00 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 142.59 | 52.14 | 2.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 186.91 | 48.83 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 196.86 | 40.12 | 3.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 185.38 | 37.37 | 16.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 130.60 | 24.96 | 12.17 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 114.60 | 24.59 | 47.83 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 113.43 | 33.42 | 62.67 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 128.90 | 54.89 | 7.17 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 104.53 | 60.98 | 11.50 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 75.84 | 60.39 | 168.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 130.05 | 45.67 | 619.67 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 75.84 | 24.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 196.86 | 60.98 | 228.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 78.34 | 56.51 | 228.50 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 102.16 | 54.63 | 60.00 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 142.59 | 52.14 | 2.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 186.91 | 48.83 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 196.86 | 40.12 | 3.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 185.38 | 37.37 | 16.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 130.60 | 24.96 | 12.17 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 114.60 | 24.59 | 47.83 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 113.43 | 33.42 | 62.67 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 128.90 | 54.89 | 7.17 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 104.53 | 60.98 | 11.50 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 75.84 | 60.39 | 168.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 130.05 | 45.67 | 619.67 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 75.84 | 24.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 196.86 | 60.98 | 228.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 78.34 | 56.51 | 228.50 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 102.16 | 54.63 | 60.00 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 142.59 | 52.14 | 2.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 186.91 | 48.83 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 196.86 | 40.12 | 3.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 185.38 | 37.37 | 16.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 130.60 | 24.96 | 12.17 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 114.60 | 24.59 | 47.83 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 113.43 | 33.42 | 62.67 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 128.90 | 54.89 | 7.17 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 104.53 | 60.98 | 11.50 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 75.84 | 60.39 | 168.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 130.05 | 45.67 | 619.67 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 75.84 | 24.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 196.86 | 60.98 | 228.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 78.34 | 56.51 | 228.50 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 102.16 | 54.63 | 60.00 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 142.59 | 52.14 | 2.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 186.91 | 48.83 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 196.86 | 40.12 | 3.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 185.38 | 37.37 | 16.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 130.60 | 24.96 | 12.17 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 114.60 | 24.59 | 47.83 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 113.43 | 33.42 | 62.67 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 128.90 | 54.89 | 7.17 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 104.53 | 60.98 | 11.50 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 75.84 | 60.39 | 168.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 130.05 | 45.67 | 619.67 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 75.84 | 24.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 196.86 | 60.98 | 228.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 78.34 | 56.51 | 228.50 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 102.16 | 54.63 | 60.00 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 142.59 | 52.14 | 2.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 186.91 | 48.83 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 196.86 | 40.12 | 3.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 185.38 | 37.37 | 16.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 130.60 | 24.96 | 12.17 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 114.60 | 24.59 | 47.83 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 113.43 | 33.42 | 62.67 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 128.90 | 54.89 | 7.17 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 104.53 | 60.98 | 11.50 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 75.84 | 60.39 | 168.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 130.05 | 45.67 | 619.67 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 75.84 | 24.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 196.86 | 60.98 | 228.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 78.34 | 56.51 | 228.50 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 102.16 | 54.63 | 60.00 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 142.59 | 52.14 | 2.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 186.91 | 48.83 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 196.86 | 40.12 | 3.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 185.38 | 37.37 | 16.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 130.60 | 24.96 | 12.17 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 114.60 | 24.59 | 47.83 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 113.43 | 33.42 | 62.67 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 128.90 | 54.89 | 7.17 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 104.53 | 60.98 | 11.50 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 75.84 | 60.39 | 168.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 130.05 | 45.67 | 619.67 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 75.84 | 24.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 196.86 | 60.98 | 228.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 78.34 | 56.51 | 228.50 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 102.16 | 54.63 | 60.00 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 142.59 | 52.14 | 2.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 186.91 | 48.83 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 196.86 | 40.12 | 3.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 185.38 | 37.37 | 16.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 130.60 | 24.96 | 12.17 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 114.60 | 24.59 | 47.83 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 113.43 | 33.42 | 62.67 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 128.90 | 54.89 | 7.17 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 104.53 | 60.98 | 11.50 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 75.84 | 60.39 | 168.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 130.05 | 45.67 | 619.67 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 75.84 | 24.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 196.86 | 60.98 | 228.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 78.34 | 56.51 | 228.50 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 102.16 | 54.63 | 60.00 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 142.59 | 52.14 | 2.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 186.91 | 48.83 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 196.86 | 40.12 | 3.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 185.38 | 37.37 | 16.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 130.60 | 24.96 | 12.17 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 114.60 | 24.59 | 47.83 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 113.43 | 33.42 | 62.67 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 128.90 | 54.89 | 7.17 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 104.53 | 60.98 | 11.50 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 75.84 | 60.39 | 168.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 130.05 | 45.67 | 619.67 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 75.84 | 24.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 196.86 | 60.98 | 228.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 78.34 | 56.51 | 228.50 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 102.16 | 54.63 | 60.00 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 142.59 | 52.14 | 2.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 186.91 | 48.83 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 196.86 | 40.12 | 3.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 185.38 | 37.37 | 16.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 130.60 | 24.96 | 12.17 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 114.60 | 24.59 | 47.83 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 113.43 | 33.42 | 62.67 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 128.90 | 54.89 | 7.17 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 104.53 | 60.98 | 11.50 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 75.84 | 60.39 | 168.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 130.05 | 45.67 | 619.67 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 75.84 | 24.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 196.86 | 60.98 | 228.50 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119317E+09 | 46759457.72 | 72557141.67 | 0.203658E+09 | 0.445730E+09 |
February | 0.122855E+09 | 45442081.83 | 77412949.57 | 0.252197E+09 | 0.344977E+09 |
March | 0.176528E+09 | 70797959.45 | 0.105730E+09 | 0.467049E+09 | 0.259075E+09 |
April | 0.206321E+09 | 96346432.54 | 0.109975E+09 | 0.721048E+09 | 0.117536E+09 |
May | 0.202569E+09 | 85904051.13 | 0.116665E+09 | 0.835300E+09 | 44481424.78 |
June | 0.185226E+09 | 72601842.11 | 0.112624E+09 | 0.802721E+09 | 35220058.07 |
July | 0.141281E+09 | 27519299.37 | 0.113762E+09 | 0.591438E+09 | 20706218.76 |
August | 0.129377E+09 | 22677496.91 | 0.106699E+09 | 0.509209E+09 | 41385112.63 |
September | 0.138138E+09 | 40736732.51 | 97401692.02 | 0.466924E+09 | 89037179.21 |
October | 0.149107E+09 | 59764424.93 | 89342775.44 | 0.463773E+09 | 0.232279E+09 |
November | 0.131059E+09 | 56505357.95 | 74553833.02 | 0.322600E+09 | 0.361081E+09 |
December | 0.115794E+09 | 44717288.20 | 71077153.99 | 0.202246E+09 | 0.462765E+09 |
Annual Sum or Average | 0.181757E+10 | 0.669772E+09 | 0.114780E+10 | 0.583816E+10 | 0.245427E+10 |
Minimum of Months | 0.115794E+09 | 22677496.91 | 71077153.99 | 0.202246E+09 | 20706218.76 |
Maximum of Months | 0.206321E+09 | 96346432.54 | 0.116665E+09 | 0.835300E+09 | 0.462765E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119317E+09 | 46759457.72 | 72557141.67 | 0.203658E+09 | 0.445730E+09 |
February | 0.122855E+09 | 45442081.83 | 77412949.57 | 0.252197E+09 | 0.344977E+09 |
March | 0.176528E+09 | 70797959.45 | 0.105730E+09 | 0.467049E+09 | 0.259075E+09 |
April | 0.206321E+09 | 96346432.54 | 0.109975E+09 | 0.721048E+09 | 0.117536E+09 |
May | 0.202569E+09 | 85904051.13 | 0.116665E+09 | 0.835300E+09 | 44481424.78 |
June | 0.185226E+09 | 72601842.11 | 0.112624E+09 | 0.802721E+09 | 35220058.07 |
July | 0.141281E+09 | 27519299.37 | 0.113762E+09 | 0.591438E+09 | 20706218.76 |
August | 0.129377E+09 | 22677496.91 | 0.106699E+09 | 0.509209E+09 | 41385112.63 |
September | 0.138138E+09 | 40736732.51 | 97401692.02 | 0.466924E+09 | 89037179.21 |
October | 0.149107E+09 | 59764424.93 | 89342775.44 | 0.463773E+09 | 0.232279E+09 |
November | 0.131059E+09 | 56505357.95 | 74553833.02 | 0.322600E+09 | 0.361081E+09 |
December | 0.115794E+09 | 44717288.20 | 71077153.99 | 0.202246E+09 | 0.462765E+09 |
Annual Sum or Average | 0.181757E+10 | 0.669772E+09 | 0.114780E+10 | 0.583816E+10 | 0.245427E+10 |
Minimum of Months | 0.115794E+09 | 22677496.91 | 71077153.99 | 0.202246E+09 | 20706218.76 |
Maximum of Months | 0.206321E+09 | 96346432.54 | 0.116665E+09 | 0.835300E+09 | 0.462765E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33046738.31 | 0.00 | 33046738.31 | 19082046.68 | 0.269670E+09 |
February | 35395458.44 | 0.00 | 35395458.44 | 41485220.75 | 0.205601E+09 |
March | 47238227.42 | 9028.93 | 47229198.49 | 0.105566E+09 | 0.153687E+09 |
April | 49856391.18 | 398203.59 | 49458187.59 | 0.199784E+09 | 67978372.78 |
May | 57712664.30 | 2524546.39 | 55188117.91 | 0.296153E+09 | 25719282.89 |
June | 57553981.12 | 2798877.76 | 54755103.37 | 0.306893E+09 | 20714562.42 |
July | 58431371.17 | 1377771.14 | 57053600.03 | 0.268638E+09 | 11836090.48 |
August | 53515662.64 | 427659.85 | 53088002.79 | 0.225909E+09 | 23928341.73 |
September | 45888126.03 | 10822.86 | 45877303.17 | 0.161888E+09 | 51766515.27 |
October | 41070187.91 | 0.00 | 41070187.91 | 0.123311E+09 | 0.135071E+09 |
November | 33664697.58 | 0.00 | 33664697.58 | 55439065.60 | 0.212775E+09 |
December | 32237683.47 | 0.00 | 32237683.47 | 22010258.99 | 0.281377E+09 |
Annual Sum or Average | 0.545611E+09 | 7546910.52 | 0.538064E+09 | 0.182616E+10 | 0.146012E+10 |
Minimum of Months | 32237683.47 | 0.00 | 32237683.47 | 19082046.68 | 11836090.48 |
Maximum of Months | 58431371.17 | 2798877.76 | 57053600.03 | 0.306893E+09 | 0.281377E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33045727.07 | 0.00 | 33045727.07 | 19080957.79 | 0.269668E+09 |
February | 35394403.61 | 0.00 | 35394403.61 | 41483770.10 | 0.205600E+09 |
March | 47236881.95 | 9028.51 | 47227853.45 | 0.105564E+09 | 0.153685E+09 |
April | 49855121.52 | 398184.93 | 49456936.59 | 0.199782E+09 | 67976657.62 |
May | 57711111.73 | 2524428.06 | 55186683.67 | 0.296151E+09 | 25718215.06 |
June | 57552329.92 | 2798746.57 | 54753583.35 | 0.306890E+09 | 20714056.32 |
July | 58429416.44 | 1377706.56 | 57051709.88 | 0.268634E+09 | 11835581.32 |
August | 53513838.26 | 427639.80 | 53086198.46 | 0.225904E+09 | 23927525.29 |
September | 45886653.77 | 10822.35 | 45875831.42 | 0.161885E+09 | 51765222.31 |
October | 41069040.85 | 0.00 | 41069040.85 | 0.123309E+09 | 0.135069E+09 |
November | 33663765.90 | 0.00 | 33663765.90 | 55438022.80 | 0.212772E+09 |
December | 32236700.80 | 0.00 | 32236700.80 | 22009191.28 | 0.281376E+09 |
Annual Sum or Average | 0.545595E+09 | 7546556.78 | 0.538048E+09 | 0.182613E+10 | 0.146011E+10 |
Minimum of Months | 32236700.80 | 0.00 | 32236700.80 | 19080957.79 | 11835581.32 |
Maximum of Months | 58429416.44 | 2798746.57 | 57051709.88 | 0.306890E+09 | 0.281376E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.209825E+09 | 0.151367E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.247140E+09 | 0.132155E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.381922E+09 | 0.139642E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.484459E+09 | 0.126577E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.527266E+09 | 0.107449E+09 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.480504E+09 | 96866554.06 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.349798E+09 | 66863198.41 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.306955E+09 | 65867949.83 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.294012E+09 | 86627350.05 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.345242E+09 | 0.147026E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.270931E+09 | 0.158066E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.203140E+09 | 0.161756E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.410119E+10 | 0.144026E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.203140E+09 | 65867949.83 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.527266E+09 | 0.161756E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.209825E+09 | 0.151367E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.247140E+09 | 0.132155E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.381922E+09 | 0.139642E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.484459E+09 | 0.126577E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.527266E+09 | 0.107449E+09 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.480504E+09 | 96866554.06 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.349798E+09 | 66863198.41 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.306955E+09 | 65867949.83 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.294012E+09 | 86627350.05 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.345242E+09 | 0.147026E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.270931E+09 | 0.158066E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.203140E+09 | 0.161756E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.410119E+10 | 0.144026E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.203140E+09 | 65867949.83 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.527266E+09 | 0.161756E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.209825E+09 | 0.151367E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.247140E+09 | 0.132155E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.381922E+09 | 0.139642E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.484459E+09 | 0.126577E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.527266E+09 | 0.107449E+09 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.480504E+09 | 96866554.06 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.349798E+09 | 66863198.41 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.306955E+09 | 65867949.83 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.294012E+09 | 86627350.05 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.345242E+09 | 0.147026E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.270931E+09 | 0.158066E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.203140E+09 | 0.161756E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.410119E+10 | 0.144026E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.203140E+09 | 65867949.83 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.527266E+09 | 0.161756E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.209825E+09 | 0.151367E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.247140E+09 | 0.132155E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.381922E+09 | 0.139642E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.484459E+09 | 0.126577E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.527266E+09 | 0.107449E+09 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.480504E+09 | 96866554.06 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.349798E+09 | 66863198.41 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.306955E+09 | 65867949.83 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.294012E+09 | 86627350.05 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.345242E+09 | 0.147026E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.270931E+09 | 0.158066E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.203140E+09 | 0.161756E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.410119E+10 | 0.144026E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.203140E+09 | 65867949.83 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.527266E+09 | 0.161756E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.209825E+09 | 0.151367E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.247140E+09 | 0.132155E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.381922E+09 | 0.139642E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.484459E+09 | 0.126577E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.527266E+09 | 0.107449E+09 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.480504E+09 | 96866554.06 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.349798E+09 | 66863198.41 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.306955E+09 | 65867949.83 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.294012E+09 | 86627350.05 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.345242E+09 | 0.147026E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.270931E+09 | 0.158066E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.203140E+09 | 0.161756E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.410119E+10 | 0.144026E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.203140E+09 | 65867949.83 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.527266E+09 | 0.161756E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.209825E+09 | 0.151367E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.247140E+09 | 0.132155E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.381922E+09 | 0.139642E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.484459E+09 | 0.126577E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.527266E+09 | 0.107449E+09 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.480504E+09 | 96866554.06 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.349798E+09 | 66863198.41 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.306955E+09 | 65867949.83 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.294012E+09 | 86627350.05 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.345242E+09 | 0.147026E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.270931E+09 | 0.158066E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.203140E+09 | 0.161756E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.410119E+10 | 0.144026E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.203140E+09 | 65867949.83 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.527266E+09 | 0.161756E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.209825E+09 | 0.151367E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.247140E+09 | 0.132155E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.381922E+09 | 0.139642E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.484459E+09 | 0.126577E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.527266E+09 | 0.107449E+09 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.480504E+09 | 96866554.06 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.349798E+09 | 66863198.41 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.306955E+09 | 65867949.83 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.294012E+09 | 86627350.05 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.345242E+09 | 0.147026E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.270931E+09 | 0.158066E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.203140E+09 | 0.161756E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.410119E+10 | 0.144026E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.203140E+09 | 65867949.83 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.527266E+09 | 0.161756E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.209825E+09 | 0.151367E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.247140E+09 | 0.132155E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.381922E+09 | 0.139642E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.484459E+09 | 0.126577E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.527266E+09 | 0.107449E+09 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.480504E+09 | 96866554.06 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.349798E+09 | 66863198.41 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.306955E+09 | 65867949.83 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.294012E+09 | 86627350.05 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.345242E+09 | 0.147026E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.270931E+09 | 0.158066E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.203140E+09 | 0.161756E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.410119E+10 | 0.144026E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.203140E+09 | 65867949.83 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.527266E+09 | 0.161756E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.209825E+09 | 0.151367E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.247140E+09 | 0.132155E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.381922E+09 | 0.139642E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.484459E+09 | 0.126577E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.527266E+09 | 0.107449E+09 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.480504E+09 | 96866554.06 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.349798E+09 | 66863198.41 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.306955E+09 | 65867949.83 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.294012E+09 | 86627350.05 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.345242E+09 | 0.147026E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.270931E+09 | 0.158066E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.203140E+09 | 0.161756E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.410119E+10 | 0.144026E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.203140E+09 | 65867949.83 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.527266E+09 | 0.161756E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.209825E+09 | 0.151367E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.247140E+09 | 0.132155E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.381922E+09 | 0.139642E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.484459E+09 | 0.126577E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.527266E+09 | 0.107449E+09 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.480504E+09 | 96866554.06 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.349798E+09 | 66863198.41 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.306955E+09 | 65867949.83 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.294012E+09 | 86627350.05 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.345242E+09 | 0.147026E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.270931E+09 | 0.158066E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.203140E+09 | 0.161756E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.410119E+10 | 0.144026E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.203140E+09 | 65867949.83 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.527266E+09 | 0.161756E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 160.11 | 527.99 | 113.77 | 34.92 | 78.86 | 0.00 | 0.00 |
February | 239.92 | 452.30 | 130.83 | 37.57 | 93.26 | 0.00 | 0.00 |
March | 426.24 | 306.88 | 167.09 | 52.87 | 114.22 | 0.00 | 0.00 |
April | 710.38 | 143.01 | 197.67 | 74.65 | 123.02 | 0.00 | 0.00 |
May | 844.51 | 52.06 | 194.36 | 66.03 | 128.32 | 0.00 | 0.00 |
June | 856.06 | 43.04 | 187.33 | 58.18 | 129.15 | 0.00 | 0.00 |
July | 642.20 | 24.27 | 149.13 | 21.58 | 127.55 | 0.00 | 0.00 |
August | 548.88 | 48.73 | 136.57 | 17.25 | 119.31 | 0.00 | 0.00 |
September | 485.14 | 108.59 | 142.00 | 31.44 | 110.55 | 0.00 | 0.00 |
October | 438.24 | 274.17 | 142.01 | 44.63 | 97.38 | 0.00 | 0.00 |
November | 289.81 | 440.91 | 127.10 | 43.60 | 83.50 | 0.00 | 0.00 |
December | 159.85 | 548.06 | 110.54 | 33.39 | 77.15 | 0.00 | 0.00 |
Annual Sum or Average | 484.33 | 246.51 | 149.87 | 42.96 | 106.92 | 0.00 | 0.00 |
Minimum of Months | 159.85 | 24.27 | 110.54 | 17.25 | 77.15 | 0.00 | 0.00 |
Maximum of Months | 856.06 | 548.06 | 197.67 | 74.65 | 129.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5227.84 | 2309.49 | 695.22 | 371.45 | 323.78 | 0.00 | 0.00 |
February | 8276.01 | 2035.05 | 874.02 | 485.84 | 388.18 | 0.00 | 0.00 |
March | 8681.51 | 2013.47 | 1176.41 | 702.48 | 473.93 | 0.00 | 0.00 |
April | 10780.89 | 2917.17 | 1509.65 | 1053.64 | 456.01 | 0.00 | 0.00 |
May | 12161.93 | 3020.32 | 1600.74 | 1103.24 | 497.50 | 0.00 | 0.00 |
June | 10489.50 | 2931.73 | 1498.16 | 949.98 | 548.18 | 0.00 | 0.00 |
July | 7284.55 | 1819.16 | 1052.58 | 375.95 | 676.63 | 0.00 | 0.00 |
August | 5268.87 | 1634.82 | 910.40 | 258.86 | 651.54 | 0.00 | 0.00 |
September | 5515.11 | 2048.73 | 932.87 | 392.92 | 539.95 | 0.00 | 0.00 |
October | 7369.47 | 2588.78 | 1046.67 | 662.77 | 383.91 | 0.00 | 0.00 |
November | 6878.66 | 2285.64 | 871.39 | 572.12 | 299.27 | 0.00 | 0.00 |
December | 5343.95 | 2363.47 | 675.03 | 363.67 | 311.36 | 0.00 | 0.00 |
Annual Sum or Average | 7762.01 | 2330.72 | 1070.42 | 607.27 | 463.15 | 0.00 | 0.00 |
Minimum of Months | 5227.84 | 1634.82 | 675.03 | 258.86 | 299.27 | 0.00 | 0.00 |
Maximum of Months | 12161.93 | 3020.32 | 1600.74 | 1103.24 | 676.63 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.428844E+09 | 0.141416E+10 | 0.304726E+09 | 93518915.45 | 0.211207E+09 | 0.00 | 0.00 |
February | 0.580419E+09 | 0.109421E+10 | 0.316500E+09 | 90884163.66 | 0.225616E+09 | 0.00 | 0.00 |
March | 0.114164E+10 | 0.821937E+09 | 0.447530E+09 | 0.141614E+09 | 0.305916E+09 | 0.00 | 0.00 |
April | 0.184131E+10 | 0.370676E+09 | 0.512354E+09 | 0.193489E+09 | 0.318864E+09 | 0.00 | 0.00 |
May | 0.226194E+10 | 0.139439E+09 | 0.520561E+09 | 0.176857E+09 | 0.343704E+09 | 0.00 | 0.00 |
June | 0.221890E+10 | 0.111547E+09 | 0.485558E+09 | 0.150801E+09 | 0.334757E+09 | 0.00 | 0.00 |
July | 0.172006E+10 | 64998128.03 | 0.399424E+09 | 57794076.44 | 0.341630E+09 | 0.00 | 0.00 |
August | 0.147011E+10 | 0.130506E+09 | 0.365783E+09 | 46210293.47 | 0.319572E+09 | 0.00 | 0.00 |
September | 0.125748E+10 | 0.281464E+09 | 0.368052E+09 | 81495110.23 | 0.286557E+09 | 0.00 | 0.00 |
October | 0.117379E+10 | 0.734327E+09 | 0.380354E+09 | 0.119529E+09 | 0.260825E+09 | 0.00 | 0.00 |
November | 0.751197E+09 | 0.114283E+10 | 0.329447E+09 | 0.113011E+09 | 0.216436E+09 | 0.00 | 0.00 |
December | 0.428151E+09 | 0.146792E+10 | 0.296063E+09 | 89434576.39 | 0.206629E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.152739E+11 | 0.777402E+10 | 0.472635E+10 | 0.135464E+10 | 0.337171E+10 | 0.00 | 0.00 |
Minimum of Months | 0.428151E+09 | 64998128.03 | 0.296063E+09 | 46210293.47 | 0.206629E+09 | 0.00 | 0.00 |
Maximum of Months | 0.226194E+10 | 0.146792E+10 | 0.520561E+09 | 0.193489E+09 | 0.343704E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.140022E+11 | 0.618573E+10 | 0.186209E+10 | 0.994885E+09 | 0.867201E+09 | 0.00 | 0.00 |
February | 0.200213E+11 | 0.492319E+10 | 0.211443E+10 | 0.117534E+10 | 0.939089E+09 | 0.00 | 0.00 |
March | 0.232526E+11 | 0.539288E+10 | 0.315090E+10 | 0.188152E+10 | 0.126938E+10 | 0.00 | 0.00 |
April | 0.279441E+11 | 0.756132E+10 | 0.391302E+10 | 0.273104E+10 | 0.118198E+10 | 0.00 | 0.00 |
May | 0.325745E+11 | 0.808961E+10 | 0.428742E+10 | 0.295493E+10 | 0.133250E+10 | 0.00 | 0.00 |
June | 0.271888E+11 | 0.759905E+10 | 0.388323E+10 | 0.246236E+10 | 0.142087E+10 | 0.00 | 0.00 |
July | 0.195109E+11 | 0.487243E+10 | 0.281924E+10 | 0.100694E+10 | 0.181230E+10 | 0.00 | 0.00 |
August | 0.141121E+11 | 0.437869E+10 | 0.243840E+10 | 0.693323E+09 | 0.174508E+10 | 0.00 | 0.00 |
September | 0.142952E+11 | 0.531031E+10 | 0.241799E+10 | 0.101844E+10 | 0.139955E+10 | 0.00 | 0.00 |
October | 0.197384E+11 | 0.693378E+10 | 0.280341E+10 | 0.177515E+10 | 0.102826E+10 | 0.00 | 0.00 |
November | 0.178295E+11 | 0.592438E+10 | 0.225865E+10 | 0.148294E+10 | 0.775706E+09 | 0.00 | 0.00 |
December | 0.143132E+11 | 0.633031E+10 | 0.180799E+10 | 0.974049E+09 | 0.833939E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.244783E+12 | 0.735017E+11 | 0.337568E+11 | 0.191509E+11 | 0.146058E+11 | 0.00 | 0.00 |
Minimum of Months | 0.140022E+11 | 0.437869E+10 | 0.180799E+10 | 0.693323E+09 | 0.775706E+09 | 0.00 | 0.00 |
Maximum of Months | 0.325745E+11 | 0.808961E+10 | 0.428742E+10 | 0.295493E+10 | 0.181230E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.38 | 7.87 | 1.20 | 0.38 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.78 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.60 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.33 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.97 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.39 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.29 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.70 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.74 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.46 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.88 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.77 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.38 | 7.87 | 0.66 | 0.38 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.20 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.20 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.50 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.67 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.64 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.53 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.36 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.58 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.68 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.05 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.17 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.30 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.20 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.68 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.56 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.58 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.74 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.62 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.38 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.42 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.18 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.17 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.06 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.93 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.62 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.18 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.48 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.26 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.04 | 0.00 | 15.61 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.70 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.41 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.59 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.48 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.819585E+09 | -679987811.4 | 0.00 | 0.00 | 744.00 | 0.00 | -139597426.7 | 58.99 | 0.00 | 0.00 |
February | 0.732650E+09 | -611530294.6 | 0.00 | 0.00 | 672.00 | 0.00 | -121119414.4 | 58.99 | 0.00 | 0.00 |
March | 0.794988E+09 | -666818438.3 | 0.00 | 0.00 | 744.00 | 0.00 | -128169716.3 | 58.99 | 0.00 | 0.00 |
April | 0.675282E+09 | -556028754.5 | 0.00 | 0.00 | 720.00 | 0.00 | -119253520.8 | 58.99 | 0.00 | 0.00 |
May | 0.632820E+09 | -510928082.7 | 0.00 | 0.00 | 744.00 | 0.00 | -121892170.8 | 58.99 | 0.00 | 0.00 |
June | 0.574644E+09 | -456447238.9 | 0.00 | 0.00 | 720.00 | 0.00 | -118196448.4 | 58.99 | 0.00 | 0.00 |
July | 0.542189E+09 | -420677665.3 | 0.00 | 0.00 | 744.00 | 0.00 | -121511265.8 | 58.99 | 0.00 | 0.00 |
August | 0.590183E+09 | -467790045.0 | 0.00 | 0.00 | 744.00 | 0.00 | -122393257.7 | 58.99 | 0.00 | 0.00 |
September | 0.600093E+09 | -481506087.5 | 0.00 | 0.00 | 720.00 | 0.00 | -118586598.9 | 58.99 | 0.00 | 0.00 |
October | 0.670806E+09 | -546561125.4 | 0.00 | 0.00 | 744.00 | 0.00 | -124245004.4 | 58.99 | 0.00 | 0.00 |
November | 0.711933E+09 | -586877244.1 | 0.00 | 0.00 | 720.00 | 0.00 | -125056135.0 | 58.99 | 0.00 | 0.00 |
December | 0.796159E+09 | -659807202.7 | 0.00 | 0.00 | 744.00 | 0.00 | -136351436.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.814133E+10 | -0.664496E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.149637E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.542189E+09 | -679987811.4 | 0.00 | 0.00 | 672.00 | 0.00 | -139597426.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.819585E+09 | -420677665.3 | 0.00 | 0.00 | 744.00 | 0.00 | -118196448.4 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 319.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 364.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 386.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 372.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 317.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 315.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4237.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.436375E+09 | 35815.38 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 66818592.51 | 5877.91 | 03-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 93181099.21 | 5590.48 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.596375E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.436375E+09 | 35815.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.285345E+09 | 25469.59 | 01-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.285345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.285345E+09 | 25469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.249293E+10 | 47348.11 | 03-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.249293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.249293E+10 | 47348.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.269763E+10 | 0.252802E+10 | 7201.56 | 14-JAN-15:50 | 6374.73 | 0.00 |
February | 0.00 | 0.00 | 0.458130E+10 | 0.419663E+10 | 21786.48 | 25-FEB-06:03 | 18211.99 | 0.00 |
March | 0.00 | 0.00 | 0.972558E+10 | 0.890720E+10 | 34290.36 | 11-MAR-06:01 | 27692.62 | 0.00 |
April | 0.00 | 0.00 | 0.140253E+11 | 0.130639E+11 | 34744.73 | 03-APR-05:01 | 28465.22 | 0.00 |
May | 0.00 | 0.00 | 0.196968E+11 | 0.168538E+11 | 38677.96 | 24-MAY-05:01 | 21864.04 | 0.00 |
June | 0.00 | 0.00 | 0.216448E+11 | 0.171153E+11 | 38585.30 | 26-JUN-05:01 | 19105.66 | 0.00 |
July | 0.00 | 0.00 | 0.224365E+11 | 0.154518E+11 | 39041.16 | 19-JUL-05:02 | 18165.39 | 0.00 |
August | 0.00 | 0.00 | 0.228443E+11 | 0.152544E+11 | 39576.57 | 16-AUG-05:01 | 20556.12 | 0.00 |
September | 0.00 | 0.00 | 0.183869E+11 | 0.131029E+11 | 39413.04 | 09-SEP-05:01 | 19653.96 | 0.00 |
October | 0.00 | 0.00 | 0.131009E+11 | 0.112496E+11 | 37028.07 | 12-OCT-05:01 | 23236.49 | 0.00 |
November | 0.00 | 0.00 | 0.760769E+10 | 0.702030E+10 | 32689.65 | 09-NOV-06:01 | 27942.22 | 0.00 |
December | 0.00 | 0.00 | 0.379577E+10 | 0.357159E+10 | 8364.97 | 02-DEC-15:10 | 8230.60 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.160544E+12 | 0.128316E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.269763E+10 | 0.252802E+10 | 7201.56 | 6374.73 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.228443E+11 | 0.171153E+11 | 39576.57 | 28465.22 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.343411E+10 | 0.322395E+10 | 16869.07 | 26-JAN-13:52 | 15800.74 | 0.00 |
February | 0.00 | 0.00 | 0.114090E+11 | 0.105357E+11 | 35225.43 | 22-FEB-14:30 | 33719.33 | 0.00 |
March | 0.00 | 0.00 | 0.358914E+11 | 0.333070E+11 | 120744.41 | 29-MAR-17:05 | 120209.93 | 0.00 |
April | 0.00 | 0.00 | 0.695423E+11 | 0.662035E+11 | 138037.68 | 02-APR-13:52 | 130884.95 | 0.00 |
May | 0.00 | 0.00 | 0.101181E+12 | 0.905697E+11 | 150670.35 | 20-MAY-21:03 | 109420.27 | 0.00 |
June | 0.00 | 0.00 | 0.106672E+12 | 0.902997E+11 | 160263.98 | 17-JUN-23:03 | 102192.63 | 0.00 |
July | 0.00 | 0.00 | 0.106092E+12 | 0.787464E+11 | 157854.09 | 03-JUL-05:01 | 104825.08 | 0.00 |
August | 0.00 | 0.00 | 0.970706E+11 | 0.705682E+11 | 157768.02 | 10-AUG-05:01 | 102810.23 | 0.00 |
September | 0.00 | 0.00 | 0.752932E+11 | 0.576175E+11 | 147448.30 | 14-SEP-17:05 | 108769.11 | 0.00 |
October | 0.00 | 0.00 | 0.517292E+11 | 0.462457E+11 | 133873.49 | 01-OCT-11:42 | 133873.49 | 0.00 |
November | 0.00 | 0.00 | 0.233841E+11 | 0.217448E+11 | 113145.20 | 05-NOV-14:02 | 113145.20 | 0.00 |
December | 0.00 | 0.00 | 0.687808E+10 | 0.642440E+10 | 25695.96 | 03-DEC-14:30 | 25431.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.688577E+12 | 0.575487E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.343411E+10 | 0.322395E+10 | 16869.07 | 15800.74 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.106672E+12 | 0.905697E+11 | 160263.98 | 133873.49 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 32663077.90 | 0.00 | 358.15 | 01-JAN-00:05 | 0.08 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 32663077.90 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32663077.90 | 0.00 | 358.15 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.165299E+10 | 0.35 | 1663.69 | 07-JAN-11:15 | 0.91 |
February | 0.151610E+10 | 0.35 | 1663.69 | 06-FEB-11:25 | 0.92 |
March | 0.179383E+10 | 0.38 | 1663.69 | 04-MAR-11:43 | 0.92 |
April | 0.170064E+10 | 0.42 | 1663.69 | 01-APR-09:15 | 0.91 |
May | 0.183295E+10 | 0.51 | 1663.69 | 01-MAY-10:55 | 0.91 |
June | 0.184340E+10 | 0.53 | 1663.69 | 06-JUN-16:50 | 0.91 |
July | 0.179576E+10 | 0.50 | 1663.69 | 01-JUL-09:10 | 0.91 |
August | 0.188637E+10 | 0.46 | 1663.69 | 01-AUG-11:10 | 0.91 |
September | 0.171986E+10 | 0.41 | 1663.69 | 07-SEP-08:55 | 0.91 |
October | 0.168823E+10 | 0.39 | 1663.69 | 03-OCT-07:00 | 0.91 |
November | 0.158865E+10 | 0.35 | 1663.69 | 01-NOV-09:10 | 0.91 |
December | 0.164738E+10 | 0.34 | 1663.69 | 02-DEC-10:57 | 0.92 |
Annual Sum or Average | 0.206662E+11 | 0.42 | |||
Minimum of Months | 0.151610E+10 | 0.34 | 1663.69 | 0.91 | |
Maximum of Months | 0.188637E+10 | 0.53 | 1663.69 | 0.92 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.991299E+10 | 0.56 | 9992.87 | 04-JAN-14:20 | 1.44 |
February | 0.911662E+10 | 0.55 | 9992.87 | 01-FEB-13:00 | 1.44 |
March | 0.109900E+11 | 0.72 | 9992.87 | 01-MAR-11:13 | 1.44 |
April | 0.114287E+11 | 1.10 | 9992.87 | 01-APR-08:63 | 1.43 |
May | 0.129958E+11 | 1.22 | 9992.87 | 01-MAY-10:50 | 1.44 |
June | 0.130512E+11 | 1.23 | 9992.87 | 01-JUN-07:10 | 1.43 |
July | 0.127853E+11 | 1.22 | 9992.87 | 01-JUL-07:00 | 1.43 |
August | 0.128179E+11 | 1.22 | 9992.87 | 01-AUG-10:30 | 1.43 |
September | 0.114085E+11 | 1.16 | 9992.87 | 01-SEP-09:00 | 1.43 |
October | 0.106944E+11 | 0.89 | 9992.87 | 02-OCT-07:20 | 1.44 |
November | 0.960387E+10 | 0.59 | 9992.87 | 01-NOV-07:25 | 1.44 |
December | 0.989428E+10 | 0.53 | 9992.87 | 01-DEC-11:00 | 1.44 |
Annual Sum or Average | 0.134699E+12 | 0.92 | |||
Minimum of Months | 0.911662E+10 | 0.53 | 9992.87 | 1.43 | |
Maximum of Months | 0.130512E+11 | 1.23 | 9992.87 | 1.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.238419E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.275217E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.450115E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.594401E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.802797E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.850271E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.822038E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.824516E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.684667E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.538179E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.367250E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.267243E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.671511E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.238419E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.850271E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.109312E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.124819E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.219622E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.344629E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.477870E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.493055E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.465246E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.428546E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.347114E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.268064E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.166430E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.119233E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.356394E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.109312E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.493055E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.165299E+10 | 0.269763E+10 | 0.436375E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151610E+10 | 0.458130E+10 | 66818592.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179383E+10 | 0.972558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.170064E+10 | 0.140253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.183295E+10 | 0.196968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.184340E+10 | 0.216448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.179576E+10 | 0.224365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.188637E+10 | 0.228443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.171986E+10 | 0.183869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168823E+10 | 0.131009E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158865E+10 | 0.760769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164738E+10 | 0.379577E+10 | 93181099.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206662E+11 | 0.160544E+12 | 0.596375E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151610E+10 | 0.269763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.188637E+10 | 0.228443E+11 | 0.436375E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.991299E+10 | 0.343411E+10 | 0.285345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.911662E+10 | 0.114090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109900E+11 | 0.358914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.114287E+11 | 0.695423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129958E+11 | 0.101181E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130512E+11 | 0.106672E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.127853E+11 | 0.106092E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.128179E+11 | 0.970706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.114085E+11 | 0.752932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.106944E+11 | 0.517292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.960387E+10 | 0.233841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.989428E+10 | 0.687808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134699E+12 | 0.688577E+12 | 0.285345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.911662E+10 | 0.343411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130512E+11 | 0.106672E+12 | 0.285345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.165299E+10 | 0.00 | 0.00 | 0.00 | 0.731198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151610E+10 | 0.00 | 0.00 | 0.00 | 0.123608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179383E+10 | 0.00 | 0.00 | 0.00 | 0.270732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.170064E+10 | 0.00 | 0.00 | 0.00 | 0.424337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.183295E+10 | 0.00 | 0.00 | 0.00 | 0.619502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.184340E+10 | 0.00 | 0.00 | 0.00 | 0.665931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.179576E+10 | 0.00 | 0.00 | 0.00 | 0.642462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.188637E+10 | 0.00 | 0.00 | 0.00 | 0.635879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.171986E+10 | 0.00 | 0.00 | 0.00 | 0.512681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168823E+10 | 0.00 | 0.00 | 0.00 | 0.369355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158865E+10 | 0.00 | 0.00 | 0.00 | 0.208385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164738E+10 | 0.00 | 0.00 | 0.00 | 0.102505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206662E+11 | 0.00 | 0.00 | 0.00 | 0.464850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151610E+10 | 0.00 | 0.00 | 0.00 | 0.731198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.188637E+10 | 0.00 | 0.00 | 0.00 | 0.665931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.991299E+10 | 0.00 | 0.00 | 0.00 | 0.101816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.911662E+10 | 0.00 | 0.00 | 0.00 | 0.336531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109900E+11 | 0.00 | 0.00 | 0.00 | 0.109722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.114287E+11 | 0.00 | 0.00 | 0.00 | 0.230342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129958E+11 | 0.00 | 0.00 | 0.00 | 0.347911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130512E+11 | 0.00 | 0.00 | 0.00 | 0.362544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.127853E+11 | 0.00 | 0.00 | 0.00 | 0.337393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.128179E+11 | 0.00 | 0.00 | 0.00 | 0.300368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.114085E+11 | 0.00 | 0.00 | 0.00 | 0.233029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.106944E+11 | 0.00 | 0.00 | 0.00 | 0.161119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.960387E+10 | 0.00 | 0.00 | 0.00 | 0.703918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.989428E+10 | 0.00 | 0.00 | 0.00 | 0.202901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134699E+12 | 0.00 | 0.00 | 0.00 | 0.221694E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.911662E+10 | 0.00 | 0.00 | 0.00 | 0.101816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130512E+11 | 0.00 | 0.00 | 0.00 | 0.362544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.318252E+09 | 0.00 | 0.00 | 5757764.26 | 0.00 | 0.153495E+09 | 0.599509E+09 | 0.00 | 0.14 |
February | 0.135480E+09 | 24009115.33 | 0.00 | 10402285.87 | 0.00 | 37624228.32 | 0.399413E+09 | 0.00 | 0.14 |
March | 31725444.58 | 0.345993E+09 | 0.00 | 10765494.01 | 0.00 | 0.00 | 0.177141E+09 | 0.00 | 0.15 |
April | 0.00 | 0.105135E+10 | 0.00 | 1667769.47 | 0.00 | 0.00 | 6389555.87 | 0.00 | 0.15 |
May | 0.00 | 0.239633E+10 | 0.00 | 238046.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
June | 0.00 | 0.326396E+10 | 0.00 | 62332.56 | 0.00 | 0.00 | 47994.88 | 0.00 | 0.16 |
July | 0.00 | 0.385273E+10 | 0.00 | 10304.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
August | 0.00 | 0.407851E+10 | 0.00 | 6537.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
September | 0.00 | 0.298142E+10 | 0.00 | 9754.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
October | 0.00 | 0.105897E+10 | 0.00 | 3209315.98 | 0.00 | 0.00 | 25334000.24 | 0.00 | 0.14 |
November | 62859671.12 | 0.177241E+09 | 0.00 | 10040677.04 | 0.00 | 0.00 | 0.222495E+09 | 0.00 | 0.14 |
December | 0.185517E+09 | 0.00 | 0.00 | 9689210.02 | 0.00 | 75451329.27 | 0.654639E+09 | 0.00 | 0.14 |
Annual Sum or Average | 0.733834E+09 | 0.192305E+11 | 0.00 | 51859491.91 | 0.00 | 0.266571E+09 | 0.208497E+10 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 6537.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.318252E+09 | 0.407851E+10 | 0.00 | 10765494.01 | 0.00 | 0.153495E+09 | 0.654639E+09 | 0.00 | 0.16 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.404993E+10 | 0.00 | 0.00 | 2556985.57 | 0.00 | 19013458.95 | 0.123143E+10 | 0.00 | 0.20 |
February | 0.184574E+10 | 8398009.77 | 0.00 | 22443454.58 | 0.00 | 0.00 | 0.156190E+10 | 0.00 | 0.20 |
March | 0.442364E+09 | 0.893930E+09 | 0.00 | 32385594.13 | 370634.69 | 0.00 | 0.125886E+10 | 0.00 | 0.22 |
April | 5697630.68 | 0.380016E+10 | 0.00 | 8459774.82 | 0.00 | 0.00 | 0.113635E+09 | 0.00 | 0.23 |
May | 0.00 | 0.102407E+11 | 0.00 | 28600.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
June | 0.00 | 0.147637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.174337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
August | 0.00 | 0.178030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
September | 0.00 | 0.123294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
October | 48256892.41 | 0.363928E+10 | 0.00 | 5899810.31 | 622954.45 | 0.00 | 0.194935E+09 | 0.00 | 0.21 |
November | 0.698697E+09 | 0.279910E+09 | 0.00 | 27250560.70 | 0.00 | 0.00 | 0.125209E+10 | 0.00 | 0.20 |
December | 0.295177E+10 | 0.00 | 0.00 | 9903743.84 | 0.00 | 0.00 | 0.194821E+10 | 0.00 | 0.20 |
Annual Sum or Average | 0.100425E+11 | 0.811922E+11 | 0.00 | 0.108929E+09 | 993589.14 | 19013458.95 | 0.756107E+10 | 0.00 | 0.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.404993E+10 | 0.178030E+11 | 0.00 | 32385594.13 | 622954.45 | 19013458.95 | 0.194821E+10 | 0.00 | 0.27 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:42
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.503981E+12 | 0.216121E+11 | 0.00 | 0.171359E+11 | 0.890086E+10 |
February | 0.569903E+12 | 0.682545E+11 | 0.00 | 0.110594E+11 | 0.206270E+11 |
March | 0.795060E+12 | 0.167407E+12 | 0.00 | 0.397677E+10 | 0.592964E+11 |
April | 0.897058E+12 | 0.251261E+12 | 0.00 | -0.657889E+10 | 0.110845E+12 |
May | 0.998347E+12 | 0.293848E+12 | 0.00 | -0.174781E+11 | 0.161864E+12 |
June | 0.928012E+12 | 0.267292E+12 | 0.00 | -0.254497E+11 | 0.171230E+12 |
July | 0.726610E+12 | 0.224332E+12 | 0.00 | -0.305644E+11 | 0.168693E+12 |
August | 0.603412E+12 | 0.209045E+12 | 0.00 | -0.318340E+11 | 0.156310E+12 |
September | 0.676534E+12 | 0.156918E+12 | 0.00 | -0.242026E+11 | 0.122110E+12 |
October | 0.655624E+12 | 0.162907E+12 | 0.00 | -0.662594E+10 | 0.846356E+11 |
November | 0.557606E+12 | 0.945834E+11 | 0.00 | 0.731047E+10 | 0.401148E+11 |
December | 0.473174E+12 | 0.243562E+11 | 0.00 | 0.166813E+11 | 0.137774E+11 |
Annual Sum or Average | 0.838532E+13 | 0.194182E+13 | 0.00 | -0.865698E+11 | 0.111840E+13 |
Minimum of Months | 0.473174E+12 | 0.216121E+11 | 0.00 | -0.318340E+11 | 0.890086E+10 |
Maximum of Months | 0.998347E+12 | 0.293848E+12 | 0.00 | 0.171359E+11 | 0.171230E+12 |