Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2023-10-16 10:43:19
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 559.17 | 115.65 | 115.65 |
Net Site Energy | 463.61 | 95.88 | 95.88 |
Total Source Energy | 1250.22 | 258.57 | 258.57 |
Net Source Energy | 947.59 | 195.98 | 195.98 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 249.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 77.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 42.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 24.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 309.21 | 249.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 249.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 2.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 77.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 42.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 24.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 25.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 249.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 2.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 77.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 42.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 24.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 25.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 24.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 10.89 | 51.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 63.95 | 51.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 24.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 10.89 | 51.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 63.95 | 51.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 100.240 | 32.42 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -4.68 | -1.5 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 95.559 | 30.90 |
Electricity Coming From Utility | 227.091 | 73.44 |
Surplus Electricity Going To Utility | 13.440 | 4.35 |
Net Electricity From Utility | 213.651 | 69.10 |
Total On-Site and Utility Electric Sources | 309.210 | 100.00 |
Total Electricity End Uses | 309.210 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 61.67 |
Time Setpoint Not Met During Occupied Cooling | 0.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2480.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 68.38 |
Skylight-Roof Ratio [%] | 1.49 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 6.1633 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 6.6844 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.1969 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.3473 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.3473 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 6.1633 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 6.6844 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.1969 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.3473 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.3473 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.3473 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-14:00 | 19-FEB-07:10 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 121710.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5698.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5414.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4086.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1754.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 26988.39 | 121710.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 121710.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 5698.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 5414.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 1780.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1754.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 270.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 245.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 134.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 78.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 81.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 979.27 | 270.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 56.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 50.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 16.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 202.53 | 56.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 56.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 50.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 16.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 202.53 | 56.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.916961 |
ZONE2 FINE STORAGE DIRECT AIR | 1.79 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 2.45 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 2.45 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 99047.42 |
PSZ-OFFICE HEATING COIL | 23847.66 |
PSZ-FINE STORAGE HEATING COIL | 62154.48 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 99047.42 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.916961 | 0.916961 | 0.916961 | 0.916961 | 0.916961 | 0.916961 | 1.00 | 1.00 | 0.916961 |
PSZ-FINE STORAGE | 1.79 | 1.79 | 1.79 | 1.79 | 1.79 | 1.79 | 1.00 | 1.00 | 1.79 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 0.916961 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 1.79 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.916961 | 1015.22 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.79 | 1913.78 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.916961 | 0.916961 | 0.916961 | 0.916961 | 15412.05 | 23847.66 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 1.79 | 1.79 | 1.79 | 1.18 | 37228.36 | 62154.48 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.916960 | 0.458480 | 0.611307 | 15412.05 | 7706.02 | 0.800090 | 0.800090 |
PSZ-FINE STORAGE COOLING COIL | 1.79 | 0.894252 | 1.19 | 37228.36 | 18614.18 | 0.760380 | 0.760380 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 6.163 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 14.237 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 6.684 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.684 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.197 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 5.756 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1459.960 | 6.163 | 114.518 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1459.960 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 9314.081 | 6.684 | 310.469 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 9314.081 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 10245.499 | 3.197 | 148.485 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10245.499 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2163 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.4974 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.3953 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 1.090 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 2.044 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 1.090 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.622 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.010 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.431 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8179 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4892 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8179 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.18741198E-13 | -0.13599760E-18 | 0.18147593E-18 | 0.0000000 |
2 | 1 | -5.2160601 | 0.51384690E-04 | -0.74050972E-04 | 0.35929797E-14 |
3 | 0 | 5.4323994 | 0.21628790 | 0.21641333 | |
4 | 2 | 0.53330648E-11 | 0.17872838E-15 | 0.22136589E-15 | 0.0000000 |
5 | 1 | -5.2159880 | 0.41449123E-04 | -0.32205733E-04 | 0.68736940E-11 |
6 | 0 | 5.7134214 | 0.49739196 | 0.49746561 | |
7 | 4 | 0.79936253E-12 | 0.91184990E-16 | -0.20402017E-14 | 0.11337666E-15 |
8 | 3 | -0.39068608E-03 | 0.27956711E-06 | -0.56729907E-04 | 0.15337474E-12 |
9 | 2 | 1.7536362 | 0.60734726E-02 | 1.1511739 | -0.74901239E-04 |
10 | 1 | -7.1101691 | 0.15671991 | -17.166525 | 0.33610966 |
11 | 0 | 5.6193701 | 0.99652939E-01 | 16.277855 | |
12 | 4 | 0.66371400E-12 | 0.53179206E-15 | -0.16135038E-14 | 0.12763715E-15 |
13 | 3 | -0.34381841E-03 | 0.72524581E-06 | -0.49494796E-04 | 0.12740378E-12 |
14 | 2 | 1.6410015 | 0.16611487E-01 | 1.0655968 | -0.65911423E-04 |
15 | 1 | -7.2631964 | 0.44301797 | -16.616845 | 0.31441025 |
16 | 0 | 6.3700550 | 0.28788606 | 16.298814 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.0441747 | 2.0441747 | 2.0441747 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.16135038E-14 | 0.53179206E-15 | 0.66371400E-12 | 0.12763715E-15 |
85 | 3 | -0.49494796E-04 | 0.72524581E-06 | -0.34381841E-03 | 0.12740378E-12 |
86 | 2 | 1.0655968 | 0.16611487E-01 | 1.6410015 | -0.65911423E-04 |
87 | 1 | -16.616845 | 0.44301797 | -7.2631964 | 0.31441025 |
88 | 0 | 16.298814 | 0.28788606 | 6.3700550 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.362_SHGC_SOUTH_0.359 | 34 | 1 | VerySmooth | 2.057 | 2.057 | 1.000 | 0.360 | ||
2 | NONRESWINDOW_U_0.362_SHGC_NORTH_0.359 | 35 | 1 | VerySmooth | 2.057 | 2.057 | 1.000 | 0.360 | ||
3 | NONRESWINDOW_U_0.362_SHGC_EAST_0.359 | 36 | 1 | VerySmooth | 2.057 | 2.057 | 1.000 | 0.360 | ||
4 | NONRESWINDOW_U_0.362_SHGC_WEST_0.359 | 37 | 1 | VerySmooth | 2.057 | 2.057 | 1.000 | 0.360 | ||
5 | SKYLIGHT_U_0.5_SHGC_0.4 | 38 | 1 | VerySmooth | 2.843 | 2.843 | 1.000 | 0.401 | ||
6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 39 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.555 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.63679E-002 | 0.27216 | 0.52074 | 0.52074 | 0.35900 | 0.14248 | 0.19174 | 0.00000 | 0.84000 | 0.84000 | 0.11599 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.63679E-002 | 0.27216 | 0.52074 | 0.52074 | 0.35900 | 0.14248 | 0.19174 | 0.00000 | 0.84000 | 0.84000 | 0.11599 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.63679E-002 | 0.27216 | 0.52074 | 0.52074 | 0.35900 | 0.14248 | 0.19174 | 0.00000 | 0.84000 | 0.84000 | 0.11599 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.63679E-002 | 0.27216 | 0.52074 | 0.52074 | 0.35900 | 0.14248 | 0.19174 | 0.00000 | 0.84000 | 0.84000 | 0.11599 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.31435 | 0.46556 | 0.46556 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.41263 | 0.18041 | 0.18041 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | CurtainWall | 2.775 | 0.408 | 0.402 |
2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.099 | 0.553 | 0.552 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.331 | 7.274E-004 | 4.751E-004 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.8383E-005 |
2 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9059E-004 |
3 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.6724E-005 |
4 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1833E-004 |
5 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.7716E-005 |
6 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2223E-004 |
7 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5724E-005 |
8 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.5867E-004 |
9 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7280E-004 |
10 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.3162E-004 |
11 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4265E-004 |
12 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.7242E-004 |
13 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6356E-004 |
14 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.7307E-004 |
15 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3414E-004 |
16 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4540E-004 |
17 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.8126E-004 |
18 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7061E-004 |
19 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1714E-004 |
20 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9369E-004 |
21 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.0355E-004 |
22 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1840E-004 |
23 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8792E-004 |
24 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6675E-005 |
25 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5223E-004 |
26 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.8894E-005 |
27 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8442E-004 |
28 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0962E-004 |
29 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0916E-003 |
30 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.3360E-005 |
31 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3392E-003 |
32 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0724E-005 |
33 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.3939E-004 |
34 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.8837E-005 |
35 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5304E-004 |
36 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.3587E-005 |
37 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.5445E-004 |
38 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9124E-005 |
39 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9718E-004 |
40 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6272E-005 |
41 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.8173E-004 |
42 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5921E-005 |
43 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.2485E-004 |
44 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7956E-005 |
45 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3760E-004 |
46 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4026E-005 |
47 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7955E-004 |
48 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4789E-005 |
49 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8644E-004 |
50 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0204E-005 |
51 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3822E-004 |
52 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3600E-005 |
53 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.2493E-004 |
54 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4581E-005 |
55 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3679E-004 |
56 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4861E-005 |
57 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4239E-003 |
58 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.2287E-005 |
59 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5589E-003 |
60 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.1342E-005 |
61 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6407E-003 |
62 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0957E-005 |
63 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1133E-003 |
64 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6508E-005 |
65 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3970E-003 |
66 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4655E-004 |
67 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2759E-003 |
68 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7259E-004 |
69 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3502E-003 |
70 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.0531E-005 |
71 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5808E-003 |
72 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1684E-005 |
73 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2486E-004 |
74 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.0875E-004 |
75 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.1378E-004 |
76 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.7498E-004 |
77 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.1308E-004 |
78 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4765E-004 |
79 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6286E-003 |
80 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1734E-005 |
81 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.2443E-004 |
82 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6901E-004 |
83 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8173E-004 |
84 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.0446E-004 |
85 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0750E-004 |
86 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.0643E-004 |
87 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3102E-004 |
88 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8162E-004 |
89 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.8706E-005 |
90 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3001E-003 |
91 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.4334E-005 |
92 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4627E-003 |
93 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.3836E-005 |
94 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3293E-003 |
95 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0760E-004 |
96 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8446E-004 |
97 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2755E-005 |
98 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5114E-003 |
99 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.7255E-005 |
100 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4348E-003 |
101 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9135E-005 |
102 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4372E-003 |
103 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7398E-005 |
104 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.1825E-003 |
105 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0364E-005 |
106 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.8487E-004 |
107 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.5512E-005 |
108 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.2943E-004 |
109 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8046E-005 |
110 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1354E-003 |
111 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5431E-005 |
112 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2422E-003 |
113 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0886E-005 |
114 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.8931E-005 |
115 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.3569E-005 |
116 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.4148E-005 |
117 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.3007E-005 |
118 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.8130E-005 |
119 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0686E-005 |
120 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.8896E-005 |
121 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4358E-005 |
122 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1664E-005 |
123 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0794E-005 |
124 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1607E-005 |
125 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5611E-005 |
126 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9659E-005 |
127 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3969E-005 |
128 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1488E-005 |
129 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0478E-005 |
130 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9470E-005 |
131 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.3362E-005 |
132 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7547E-005 |
133 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.3452E-005 |
134 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0493E-005 |
135 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0664E-005 |
136 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2423E-005 |
137 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1711E-004 |
138 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9330E-004 |
139 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7628E-004 |
140 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1942E-004 |
141 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8026E-004 |
142 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3323E-004 |
143 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5103E-005 |
144 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2222E-005 |
145 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1080E-004 |
146 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9086E-004 |
147 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1774E-004 |
148 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0571E-004 |
149 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.4732E-005 |
150 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1406E-004 |
151 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1117E-005 |
152 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0201E-005 |
153 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1944E-004 |
154 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5535E-005 |
155 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2893E-004 |
156 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5088E-005 |
157 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6996E-005 |
158 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6682E-005 |
159 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1095E-005 |
160 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2472E-005 |
161 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5391E-004 |
162 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5556E-005 |
163 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2541E-004 |
164 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7809E-005 |
165 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8558E-004 |
166 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9368E-005 |
167 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5083E-005 |
168 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1405E-005 |
169 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5631E-004 |
170 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.3914E-004 |
171 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6071E-004 |
172 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1341E-003 |
173 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5863E-004 |
174 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7513E-004 |
175 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6080E-005 |
176 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3729E-004 |
177 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0962E-004 |
178 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1361E-004 |
179 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0835E-004 |
180 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4546E-004 |
181 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5467E-004 |
182 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7454E-004 |
183 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0654E-004 |
184 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4057E-004 |
185 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6663E-004 |
186 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2538E-005 |
187 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8389E-004 |
188 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2566E-005 |
189 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6772E-004 |
190 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.4727E-005 |
191 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0642E-004 |
192 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5894E-005 |
193 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6786E-004 |
194 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8459E-005 |
195 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7528E-004 |
196 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7305E-005 |
197 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6326E-004 |
198 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1099E-005 |
199 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6000E-005 |
200 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5319E-005 |
201 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1030E-003 |
202 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0683E-004 |
203 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2103E-003 |
204 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0232E-004 |
205 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2166E-003 |
206 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2559E-004 |
207 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2332E-004 |
208 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0027E-005 |
209 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0365E-003 |
210 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5420E-004 |
211 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1244E-003 |
212 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6592E-004 |
213 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1866E-003 |
214 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6164E-004 |
215 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2412E-004 |
216 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4700E-004 |
217 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1585E-004 |
218 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0445E-005 |
219 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1194E-004 |
220 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8445E-005 |
221 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6782E-004 |
222 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4904E-005 |
223 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7391E-004 |
224 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8641E-005 |
225 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0393E-004 |
226 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6215E-003 |
227 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9761E-004 |
228 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8341E-003 |
229 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5969E-004 |
230 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6389E-003 |
231 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7417E-004 |
232 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.5926E-004 |
233 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2822E-004 |
234 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0694E-005 |
235 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0853E-004 |
236 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8014E-005 |
237 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3433E-004 |
238 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5984E-005 |
239 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7422E-004 |
240 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1060E-005 |
241 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2545E-003 |
242 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0991E-004 |
243 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1971E-003 |
244 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0080E-004 |
245 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0072E-003 |
246 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4042E-004 |
247 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2266E-003 |
248 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1357E-004 |
249 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2146E-003 |
250 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9510E-004 |
251 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1499E-003 |
252 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5797E-004 |
253 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9641E-003 |
254 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.9470E-004 |
255 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2308E-003 |
256 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1830E-004 |
257 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2063E-004 |
258 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8994E-003 |
259 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9987E-004 |
260 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8443E-003 |
261 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2435E-004 |
262 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9795E-003 |
263 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7477E-004 |
264 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6474E-003 |
265 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9041E-004 |
266 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9024E-005 |
267 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6537E-004 |
268 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6064E-005 |
269 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6494E-004 |
270 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3367E-005 |
271 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7271E-004 |
272 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1031E-005 |
273 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8871E-004 |
274 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1264E-003 |
275 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6297E-004 |
276 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.5265E-004 |
277 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5773E-004 |
278 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7027E-003 |
279 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7326E-004 |
280 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5789E-003 |
281 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0983E-004 |
282 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8919E-005 |
283 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8729E-004 |
284 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.8172E-005 |
285 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2535E-003 |
286 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2124E-004 |
287 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1930E-003 |
288 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1325E-004 |
289 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0562E-004 |
290 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7460E-004 |
291 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8124E-004 |
292 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2072E-004 |
293 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2311E-003 |
294 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7274E-004 |
295 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1970E-003 |
296 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1180E-004 |
297 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3399E-004 |
298 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5471E-004 |
299 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1321E-004 |
300 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6316E-004 |
301 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4537E-004 |
302 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9165E-004 |
303 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7207E-004 |
304 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2995E-004 |
305 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7364E-004 |
306 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2008E-004 |
307 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0027E-004 |
308 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8164E-004 |
309 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.0842E-004 |
310 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5055E-004 |
311 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0466E-004 |
312 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4053E-004 |
313 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4038E-005 |
314 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0102E-005 |
315 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0625E-005 |
316 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5619E-005 |
317 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5943E-005 |
318 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7266E-005 |
319 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3950E-005 |
320 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1198E-005 |
321 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3323E-004 |
322 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6008E-005 |
323 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1313E-004 |
324 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3180E-005 |
325 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4867E-004 |
326 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8546E-005 |
327 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7182E-004 |
328 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8575E-005 |
329 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8112E-005 |
330 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8206E-004 |
331 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5080E-005 |
332 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4543E-004 |
333 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.9734E-005 |
334 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4918E-004 |
335 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.4996E-005 |
336 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3143E-004 |
337 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6365E-004 |
338 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1960E-004 |
339 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3170E-004 |
340 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9105E-005 |
341 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3569E-004 |
342 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0613E-004 |
343 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0188E-004 |
344 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3821E-004 |
345 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7352E-005 |
346 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2567E-005 |
347 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.4734E-005 |
348 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0144E-005 |
349 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0958E-005 |
350 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3863E-005 |
351 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.4918E-005 |
352 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5252E-005 |
353 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7159E-004 |
354 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.0390E-005 |
355 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9947E-004 |
356 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0951E-005 |
357 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1409E-004 |
358 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.6505E-005 |
359 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0389E-004 |
360 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.9465E-005 |
361 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6273E-004 |
362 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.2706E-005 |
363 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3123E-004 |
364 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5845E-005 |
365 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3697E-004 |
366 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0702E-005 |
367 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0177E-004 |
368 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5496E-005 |
369 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.5090E-003 |
370 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.4018E-004 |
371 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.0575E-003 |
372 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.8807E-004 |
373 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 4.6089E-003 |
374 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.4270E-004 |
375 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.5669E-003 |
376 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 4.5086E-004 |
377 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.6804E-004 |
378 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.9150E-003 |
379 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.3567E-004 |
380 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.0760E-003 |
381 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.5412E-004 |
382 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.0218E-003 |
383 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.4572E-004 |
384 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.4523E-003 |
385 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 5.2106E-003 |
386 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.6471E-004 |
387 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.9172E-003 |
388 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.8718E-004 |
389 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.5105E-003 |
390 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.1176E-004 |
391 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.2194E-003 |
392 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.7466E-004 |
393 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.2723E-003 |
394 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.6492E-004 |
395 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.9488E-003 |
396 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.8730E-004 |
397 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.4559E-003 |
398 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.1163E-004 |
399 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.2193E-003 |
400 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.7466E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9155.41564 | 10986.49877 | 0.76413 | 0.91696 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 28.22133 | 8.81961E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 8476.27194 | 10171.52633 | 0.24123 | 0.28948 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -4.20000 | 2.69032E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 22908.29094 | 27489.94913 | 1.49042 | 1.78850 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40000 | 8.82150E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 23343.30556 | 28011.96667 | 0.55990 | 0.67189 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | -4.20000 | 2.69032E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 29.40000 | 8.82150E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 82539.51927 | 99047.42312 | 2.04583 | 2.45499 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 13550.62 | 0.91696 | 0.91696 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 9632.96 | 0.28948 | 0.28948 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 32724.45 | 1.78850 | 1.78850 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 29597.52 | 0.67189 | 0.67189 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.91696 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.78850 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.45499 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 2.45499 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 99047.41738 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 99047.42312 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.91696 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.91696 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.91696 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.91696 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.91696 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.91696 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.78850 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.78850 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.78850 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.78850 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.78850 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.78850 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.91696 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.78850 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.91696 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.91696 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1015.22098 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.91696 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.91696 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.91696 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.91696 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.91696 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.45848 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.61131 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 15412.05000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 7706.02500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80009 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80009 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15412.05000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 23847.66433 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 23847.66433 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.78850 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.78850 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1913.78318 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.78850 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.78850 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.78850 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.18041 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.78850 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.89425 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.19233 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 37228.36000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18614.18000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76038 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76038 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 37228.36000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 62154.47719 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 62154.47719 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 14700.5 | 12.19 | 11.92 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 35839.3 | 11.91 | 11.64 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1910387724 | 0.1660385798 | Pass | Pass | 1.1965375276 | 8.7897708603 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.3923685229 | 0.3535895278 | Pass | Pass | 0.1602468772 | 0.4695248325 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 2.1767480194E-005 | 3.1636495475E-005 | Pass | Pass | 4.4038409830E-002 | 4.7324263213E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7135.36 | 384.07 | 0.00 | 65.10 | 61.51 | 7646.06 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.373 | 0.395 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.373 | 0.395 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.373 | 0.395 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.373 | 0.395 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.373 | 0.395 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.373 | 0.395 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.373 | 0.395 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.210 | 0.216 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.937 | 1.090 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.937 | 1.090 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.937 | 1.090 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.466 | 0.497 | 3204.84 | 3157.28 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.864 | 1.090 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.864 | 1.090 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.362_SHGC_WEST_0.359 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.057 | 0.360 | 0.360 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.362_SHGC_WEST_0.359 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.057 | 0.360 | 0.360 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.362_SHGC_NORTH_0.359 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.057 | 0.360 | 0.360 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.362_SHGC_NORTH_0.359 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.057 | 0.360 | 0.360 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 86.04 | 3.466 | 0.478 | 0.476 | |||||||||||||||||
North Total or Average | 6.51 | 2.057 | 0.360 | 0.360 | |||||||||||||||||
Non-North Total or Average | 79.53 | 3.581 | 0.487 | 0.486 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 6.1633 | 236.88 | 1459.96 | LightsWired | LTG_SCH_OFFICE | 44.65 | 168.00 | 29.05 | 0.0000 | Y | 7.96 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 6.6844 | 1393.41 | 9314.08 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 20.35 | 0.0000 | Y | 35.58 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.1969 | 3204.84 | 10245.50 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 17.72 | 0.0000 | Y | 34.08 |
Interior Lighting Total | 4.3473 | 4835.13 | 21019.54 | 77.62 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 9314.08 | 2328.52 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 9314.08 | 2328.52 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10245.50 | 2561.37 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10245.50 | 2561.37 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.29 | 1459.96 | 423.39 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.10 | 1459.96 | 146.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 119.03 | AstronomicalClock | - | 42.59 | 42.59 | 0.95 | |
EXTERIOR_LIGHTS_B | 2955.82 | AstronomicalClock | - | 83.55 | 63.07 | 34.99 | |
EXTERIOR_LIGHTS_C | 694.12 | AstronomicalClock | - | 83.55 | 49.79 | 6.49 | |
Exterior Lighting Total | 3768.97 | 42.43 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 15412.05 | 12331.03 | 3081.02 | 0.80 | 4.12 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 37228.36 | 28307.70 | 8920.66 | 0.76 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 14700.5 | 12.19 | 11.92 | ||||
PSZ-FINE STORAGE COOLING COIL | 35839.3 | 11.91 | 11.64 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 99047.42 | 0.87 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 23847.66 | 0.86 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 62154.48 | 0.86 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.45 | 228.09 | 92.91 | 1.00 | 3.46 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 0.92 | 1015.22 | 1107.16 | 1.00 | 1.42 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 1.79 | 1913.78 | 1070.05 | 1.00 | 1.33 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9155.42 | 10986.50 | 46.38 | 0.764 | 0.917 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 23.90 | 23.90 | 0.00836 | 28.22 | 0.00882 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 22908.29 | 27489.95 | 19.73 | 1.490 | 1.789 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 26.70 | 26.70 | 0.00855 | 29.40 | 0.00882 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 0.00 | 30.06 | 0.00888 | 29.40 | 0.00882 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8476.27 | 10171.53 | 42.94 | 0.241 | 0.289 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00735 | -4.20 | 0.00269 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 23343.31 | 28011.97 | 20.10 | 0.560 | 0.672 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 15.56 | 15.56 | 0.00599 | -4.20 | 0.00269 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 82539.52 | 99047.42 | 30.91 | 2.046 | 2.455 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00534 | -4.20 | 0.00269 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.92 | 0.92 | 0.29 | 0.29 | 0.9170 | 0.9170 | 0.9170 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.79 | 1.79 | 0.67 | 0.67 | 1.7885 | 1.7885 | 1.7885 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 99047.417 | 99047.417 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 99047.42 | 99047.42 | 2.454992 | 10.00 | 7.31 | 0.00533889 | 43.33 | 21.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 10.00 | 0.00533889 | 69.2254 | 99047.42 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 15412.050 | 12331.027 | 0.916960 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 7706.02 | 7209.23 | 0.611307 | 25.31 | 16.62 | 0.00840896 | 12.00 | 11.13 | 0.00800000 | 28.36 | 0.00881983 | 18.00 | 16.7321 | 23.90 | 0.00835734 | 44.6271 | 9150.11 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 23847.664 | 23847.664 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 23847.66 | 23847.66 | 0.916961 | 18.20 | 12.51 | 0.00682729 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 11.1547 | 21.10 | 0.00734670 | 46.5842 | 8476.27 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 37228.360 | 28307.700 | 1.788500 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 18614.18 | 17130.90 | 1.192333 | 28.22 | 17.79 | 0.00861346 | 12.00 | 11.13 | 0.00800000 | 29.40 | 0.00882150 | 18.34 | 35.6202 | 26.70 | 0.00854868 | 38.6342 | 22906.45 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 62154.477 | 62154.477 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 62154.48 | 62154.48 | 1.788503 | 10.86 | 7.57 | 0.00520627 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 23.7467 | 15.56 | 0.00598979 | 53.8972 | 23343.31 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 99047.417 | 99047.417 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 2.454992 | 2.91405327 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 99047.42 | 99047.42 | 1.0000 | 2.91405327 | 2.454992 | 10.00 | 7.31 | 0.00533889 | 23497.3 | 43.33 | 21.98 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 99047.42 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 10.00 | 0.00533889 | 10.00 | 0.00533889 | 69.2254 | 99047.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 15412.050 | 12331.027 | 0.916960 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4718 | 1004.8586 | 1.1870 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.916961 | 1.08842382 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | Sensible | 7706.02 | 7209.23 | 1.0000 | 0.72561538 | 0.611307 | 25.31 | 16.62 | 0.00840896 | 46859.2 | 12.00 | 11.13 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7706.02 | 28.36 | 0.00881983 | 18.00 | 0.10228463 | 16.7321 | 23.90 | 0.00835734 | 23.90 | 0.00835734 | 44.6271 | 9150.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23847.664 | 23847.664 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.916961 | 1.08842382 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 23847.66 | 23847.66 | 1.0000 | 1.08842382 | 0.916961 | 18.20 | 12.51 | 0.00682729 | 35589.3 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23847.66 | -4.20 | 0.00269032 | -4.20 | 0.10228463 | 11.1547 | 21.01 | 0.00734670 | 21.10 | 0.00734670 | 46.5842 | 8476.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 37228.360 | 28307.700 | 1.788500 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8520 | 1004.8586 | 1.1870 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.788503 | 2.12293704 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | Sensible | 18614.18 | 17130.90 | 1.0000 | 1.41528868 | 1.192333 | 28.22 | 17.79 | 0.00861346 | 50353.5 | 12.00 | 11.13 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18614.18 | 29.40 | 0.00882150 | 18.34 | 0.42471127 | 35.6202 | 26.70 | 0.00854868 | 26.70 | 0.00854868 | 38.6342 | 22906.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 62154.477 | 62154.477 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.788503 | 2.12293704 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | Sensible | 62154.48 | 62154.48 | 1.0000 | 2.12293704 | 1.788503 | 10.86 | 7.57 | 0.00520627 | 24042.3 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 62154.48 | -4.20 | 0.00269032 | -4.20 | 0.42471127 | 23.7467 | 15.56 | 0.00598979 | 15.56 | 0.00598979 | 53.8972 | 23343.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 0.92 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.79 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2196.33 | 3117.50 | 1958.17 |
ZONE2 FINE STORAGE | 2766.00 | 3073.67 | 2311.50 |
ZONE3 BULK STORAGE | 2874.33 | 3143.83 | 2477.17 |
Facility | 2897.50 | 3255.17 | 2480.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 62.00 | 0.83 | 57.00 | 0.83 |
ZONE2 FINE STORAGE | 246.83 | 0.50 | 12.83 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 300.67 | 1.33 | 61.67 | 0.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.626 | 0.299 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.446 | 0.224 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.43 | 69.00 | 35277.63 | 0.000 | 0.117 | 0.000 | 0.055 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.43 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.50 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.36 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.43 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.29 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2256663.61 | 0.00 | 2256663.61 | 1769020.99 | 4025684.60 | 3225648.14 | 5717.91 | 2202.08 | 840.01 | 0.00 |
ZONE2 FINE STORAGE | 4754870.87 | 0.00 | 4754870.87 | 6389014.32 | 11143885.19 | 13393694.68 | 5728.82 | 2949.33 | 81.85 | 1.18 |
ZONE3 BULK STORAGE | 0.00 | 15911360.43 | 15911360.43 | 31317628.16 | 47228988.59 | 30805497.77 | 8448.69 | 47.00 | 264.31 | 4996.00 |
Total Facility | 7011534.48 | 15911360.43 | 22922894.91 | 39475663.47 | 62398558.38 | 47424840.58 | 8601.86 | 3019.50 | 1139.61 | 4996.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1724 | 0.0000 | 0.1724 | 0.0826 | 0.2550 | 0.1023 | 593.91 | 2202.08 | 840.01 |
ZONE2 FINE STORAGE | 0.3630 | 0.0000 | 0.3630 | 0.1829 | 0.5459 | 0.4247 | 606.00 | 2949.33 | 80.67 |
ZONE3 BULK STORAGE | 0.0000 | 0.5379 | 0.5379 | 1.1520 | 1.6899 | 0.9768 | 3467.53 | 26.83 | 141.64 |
Total Facility | 0.5354 | 0.5379 | 1.0732 | 1.4175 | 2.4908 | 1.5038 | 3477.86 | 2999.33 | 1015.76 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 3179519.69 | 0.00 | 3179519.69 | 3225648.14 | 5714.74 | 0.17 | 3045.09 | 0.00 |
PSZ-FINE STORAGE | 6699194.99 | 0.00 | 6699194.99 | 13393694.68 | 5728.82 | 0.00 | 3031.18 | 1.18 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2429 | 0.0000 | 0.2429 | 0.1023 | 590.74 | 0.17 | 3045.09 |
PSZ-FINE STORAGE | 0.5114 | 0.0000 | 0.5114 | 0.4247 | 606.00 | 0.00 | 3030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2523.64 | 529.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 3008.68 | 22.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2494 | 0.4798 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6111 | 0.9946 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 451 |
Defaulted Fields | 395 |
Fields with Defaults | 1183 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 309.21 | 1525.96 | 22-JAN-12:40 | 26988.39 | 10-AUG-15:00 |
Electricity:Building | 214.18 | 1044.96 | 15-JAN-11:10 | 17874.00 | 16-DEC-16:00 |
Electricity:Zone:ZONE1 OFFICE | 37.13 | 520.87 | 01-JAN-00:10 | 2598.04 | 02-JAN-16:30 |
Electricity:SpaceType:GENERAL | 214.13 | 1044.96 | 15-JAN-11:10 | 17874.00 | 16-DEC-16:00 |
InteriorLights:Electricity | 77.62 | 575.09 | 15-JAN-11:10 | 7838.83 | 16-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 7.96 | 51.00 | 01-JAN-00:10 | 762.98 | 02-JAN-16:30 |
InteriorLights:Electricity:SpaceType:GENERAL | 77.62 | 575.09 | 15-JAN-11:10 | 7838.83 | 16-DEC-16:00 |
LightsWired:InteriorLights:Electricity | 77.62 | 575.09 | 15-JAN-11:10 | 7838.83 | 16-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 7.96 | 51.00 | 01-JAN-00:10 | 762.98 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 77.62 | 575.09 | 15-JAN-11:10 | 7838.83 | 16-DEC-16:00 |
Electricity:Zone:ZONE2 FINE STORAGE | 35.58 | 290.41 | 30-JUN-17:10 | 3413.39 | 16-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 35.58 | 290.41 | 30-JUN-17:10 | 3413.39 | 16-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 35.58 | 290.41 | 30-JUN-17:10 | 3413.39 | 16-DEC-16:00 |
Electricity:Zone:ZONE3 BULK STORAGE | 141.47 | 224.12 | 15-JAN-11:10 | 12662.03 | 10-AUG-15:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 34.08 | 224.12 | 15-JAN-11:10 | 3671.05 | 16-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 34.08 | 224.12 | 15-JAN-11:10 | 3671.05 | 16-DEC-16:00 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 24.88 | 0.00 | 08-JAN-13:20 | 4086.03 | 10-AUG-15:00 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.05 | 0.00 | 01-JAN-00:10 | 2305.29 | 31-JUL-14:40 |
Ventilation (simple):Fans:Electricity | 0.05 | 0.00 | 01-JAN-00:10 | 2305.29 | 31-JUL-14:40 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.05 | 0.00 | 01-JAN-00:10 | 2305.29 | 31-JUL-14:40 |
ElectricityProduced:Facility | 95.56 | -0.00 | 17-APR-18:50 | 21687.50 | 18-MAY-11:30 |
ElectricityProduced:Plant | 95.56 | -0.00 | 17-APR-18:50 | 21687.50 | 18-MAY-11:30 |
Photovoltaic:ElectricityProduced | 100.24 | 0.00 | 01-JAN-00:10 | 23339.58 | 18-MAY-11:30 |
PowerConversion:ElectricityProduced | -4.68 | -1652.08 | 18-MAY-11:30 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 25.73 | 481.00 | 18-MAY-05:10 | 2334.43 | 13-FEB-13:00 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 227.09 | 0.00 | 01-JAN-10:20 | 24861.55 | 26-DEC-16:30 |
ElectricityPurchased:Plant | 227.09 | 0.00 | 01-JAN-10:20 | 24861.55 | 26-DEC-16:30 |
Cogeneration:ElectricityPurchased | 227.09 | 0.00 | 01-JAN-10:20 | 24861.55 | 26-DEC-16:30 |
General:Cogeneration:ElectricityPurchased | 227.09 | 0.00 | 01-JAN-10:20 | 24861.55 | 26-DEC-16:30 |
ElectricitySurplusSold:Facility | 13.44 | 0.00 | 01-JAN-00:10 | 19289.67 | 14-MAY-12:30 |
ElectricitySurplusSold:Plant | 13.44 | 0.00 | 01-JAN-00:10 | 19289.67 | 14-MAY-12:30 |
Cogeneration:ElectricitySurplusSold | 13.44 | 0.00 | 01-JAN-00:10 | 19289.67 | 14-MAY-12:30 |
General:Cogeneration:ElectricitySurplusSold | 13.44 | 0.00 | 01-JAN-00:10 | 19289.67 | 14-MAY-12:30 |
ElectricityNet:Facility | 213.65 | -19289.67 | 14-MAY-12:30 | 24861.55 | 26-DEC-16:30 |
ElectricityNet:Plant | 213.65 | -19289.67 | 14-MAY-12:30 | 24861.55 | 26-DEC-16:30 |
Cogeneration:ElectricityNet | 213.65 | -19289.67 | 14-MAY-12:30 | 24861.55 | 26-DEC-16:30 |
General:Cogeneration:ElectricityNet | 213.65 | -19289.67 | 14-MAY-12:30 | 24861.55 | 26-DEC-16:30 |
Electricity:HVAC | 26.86 | 0.00 | 08-JAN-13:20 | 7645.04 | 10-AUG-15:30 |
General:Fans:Electricity | 24.83 | 0.00 | 08-JAN-13:20 | 2389.37 | 18-FEB-18:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 2.03 | 0.00 | 01-JAN-00:10 | 5864.31 | 10-AUG-15:30 |
General:Cooling:Electricity | 2.03 | 0.00 | 01-JAN-00:10 | 5864.31 | 10-AUG-15:30 |
ExteriorLights:Electricity | 42.43 | 0.00 | 01-JAN-08:10 | 3768.97 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 42.43 | 0.00 | 01-JAN-08:10 | 3768.97 | 01-JAN-06:10 |
WaterSystems:Electricity | 25.73 | 481.00 | 18-MAY-05:10 | 2334.43 | 13-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 25.73 | 481.00 | 18-MAY-05:10 | 2334.43 | 13-FEB-13:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 249.96 | 0.00 | 08-JAN-13:20 | 121710.97 | 19-FEB-07:10 |
NaturalGas:HVAC | 249.96 | 0.00 | 08-JAN-13:20 | 121710.97 | 19-FEB-07:10 |
Heating:NaturalGas | 249.96 | 0.00 | 08-JAN-13:20 | 121710.97 | 19-FEB-07:10 |
General:Heating:NaturalGas | 249.96 | 0.00 | 08-JAN-13:20 | 121710.97 | 19-FEB-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 428.69 | 0.00 | 08-JAN-13:20 | 206486.74 | 19-FEB-06:50 |
EnergyTransfer:Building | 219.71 | 0.00 | 08-JAN-13:20 | 103485.53 | 19-FEB-06:50 |
EnergyTransfer:Zone:ZONE1 OFFICE | 36.08 | 0.00 | 01-JAN-00:10 | 17220.66 | 17-JAN-06:10 |
Heating:EnergyTransfer | 190.55 | 0.00 | 08-JAN-13:20 | 103485.53 | 19-FEB-06:50 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 26.55 | 0.00 | 01-JAN-00:10 | 17220.66 | 17-JAN-06:10 |
General:Heating:EnergyTransfer | 190.55 | 0.00 | 08-JAN-13:20 | 103485.53 | 19-FEB-06:50 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 26.55 | 0.00 | 01-JAN-00:10 | 17220.66 | 17-JAN-06:10 |
Cooling:EnergyTransfer | 29.16 | 0.00 | 01-JAN-00:10 | 17948.42 | 10-AUG-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 9.54 | 0.00 | 01-JAN-00:10 | 7112.00 | 10-AUG-17:00 |
General:Cooling:EnergyTransfer | 29.16 | 0.00 | 01-JAN-00:10 | 17948.42 | 10-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 9.54 | 0.00 | 01-JAN-00:10 | 7112.00 | 10-AUG-17:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 80.43 | 0.00 | 01-JAN-00:40 | 28863.30 | 19-FEB-04:50 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 60.80 | 0.00 | 01-JAN-00:40 | 28863.30 | 19-FEB-04:50 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 60.80 | 0.00 | 01-JAN-00:40 | 28863.30 | 19-FEB-04:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 19.62 | 0.00 | 01-JAN-00:10 | 12031.79 | 14-AUG-17:40 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 19.62 | 0.00 | 01-JAN-00:10 | 12031.79 | 14-AUG-17:40 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 103.20 | 0.00 | 02-JAN-09:10 | 75208.32 | 19-FEB-07:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 103.20 | 0.00 | 02-JAN-09:10 | 75208.32 | 19-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 103.20 | 0.00 | 02-JAN-09:10 | 75208.32 | 19-FEB-07:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 208.98 | 0.00 | 08-JAN-13:20 | 103001.21 | 19-FEB-06:50 |
HeatingCoils:EnergyTransfer | 199.73 | 0.00 | 08-JAN-13:20 | 103001.21 | 19-FEB-06:50 |
CoolingCoils:EnergyTransfer | 9.25 | 0.00 | 01-JAN-00:10 | 24840.60 | 10-AUG-15:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 26.548 | -9.536 | 0.000 | 0.000 | 10.124 | 7.961 | 29.165 | 9.386 | 0.000 | 0.162 | 0.001 | 0.000 | -6.034 | 0.000 | -20.342 | -47.433 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 60.804 | -19.625 | 0.000 | 0.000 | 27.185 | 35.580 | 0.000 | 27.114 | 0.000 | 0.216 | 0.002 | 0.000 | -10.903 | 0.000 | -56.915 | -63.456 |
ZONE3 BULK STORAGE | 103.195 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 66.357 | 34.082 | 107.344 | 369.421 | 0.000 | 3.196 | 0.000 | 0.000 | -103.440 | 0.000 | -278.054 | -302.100 |
Total Facility | 103.195 | 0.000 | 87.352 | -29.161 | 0.000 | 0.000 | 103.666 | 77.622 | 136.508 | 405.921 | 0.000 | 3.574 | 0.003 | 0.000 | -120.377 | 0.000 | -355.312 | -412.988 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 15-AUG-05:03 | 0.00 | 0.00 | 0.00 | -17935.55 | 0.00 | 0.00 | 90.90 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 18155.05 | 0.00 | -376.38 | 0.00 | -535.52 | 0.00 |
ZONE2 FINE STORAGE | 10-AUG-17:10 | 0.00 | 0.00 | 0.00 | -32152.62 | 0.00 | 0.00 | 0.00 | 374.19 | 0.00 | 1673.90 | 0.00 | 835.54 | 29268.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-AUG-17:10 | 0.00 | 0.00 | 0.00 | -32152.62 | 0.00 | 0.00 | 0.00 | 834.98 | 2519.91 | 68376.89 | 0.00 | 32862.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -72441.70 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 09-JAN-06:12 | 0.00 | 0.00 | 24492.75 | 0.00 | 0.00 | 0.00 | 118.54 | 227.91 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -613.23 | 0.00 | -1420.58 | -23355.91 |
ZONE2 FINE STORAGE | 19-FEB-04:03 | 0.00 | 0.00 | 63477.85 | 0.00 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1212.53 | 0.00 | -6008.63 | -56556.66 |
ZONE3 BULK STORAGE | 19-FEB-07:00 | 75207.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 448.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8813.45 | 0.00 | -36781.55 | -30060.88 |
Total Facility | 19-FEB-06:42 | 75021.50 | 0.00 | 69057.07 | 0.00 | 0.00 | 0.00 | 0.00 | 799.21 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -16714.70 | 0.00 | -45592.94 | -83040.02 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9170 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9170 | 0.1115 | 1.0000 | Not calculated | 0.1023 | 0.1115 | ||
PSZ-FINE STORAGE | 1.7885 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.7885 | 0.2375 | 1.0000 | Not calculated | 0.4247 | 0.2375 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9170 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9170 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.1115 | ||
PSZ-FINE STORAGE | 1.7885 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.7885 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.2375 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9170 | 0.9170 | 0.9170 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7885 | 1.7885 | 1.7885 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9170 | 0.9170 | 0.9170 | 0.9170 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.7885 | 1.7885 | 1.7885 | 1.7885 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9170 | 0.9170 | 0.9170 | No | 0.1023 | 0.3533 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7885 | 1.7885 | 1.7885 | No | 0.4247 | 0.6321 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9170 | 0.9170 | 0.9170 | 0.9170 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.7885 | 1.7885 | 1.7885 | 1.7885 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 61.67 |
Number of hours cooling loads not met | 0.83 |
Number of hours not met | 62.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 249.96 | 121710.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 2.03 | 5864.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 77.62 | 7838.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 42.43 | 3768.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.05 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 24.83 | 2389.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 25.73 | 2334.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 309.21 |
Natural Gas | 0.00 | 249.96 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 559.17 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 100.24 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 16.05 |
Space Heating | 0.00 |
Space Cooling | 0.42 |
Fans (All) | 5.15 |
Service Water Heating | 5.32 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 63.95 |
Subtotal | 63.95 |
Natural Gas [MJ/m2] | |
Space Heating | 51.70 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 51.70 |
Subtotal | 51.70 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 13.88 |
Space Heating | 44.70 |
Space Cooling | 0.36 |
Fans (All) | 4.45 |
Service Water Heating | 4.60 |
Receptacle Equipment | 24.41 |
Miscellaneous | 7.59 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
LTG_SCH_OFFICE | 2328. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8712.50 | 47.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8628.50 | 131.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8549.50 | 210.50 | 0.00 | 0.00 | 0.00 |
Min | 8549.50 | 47.50 | 0.00 | 0.00 | 0.00 |
Max | 8712.50 | 210.50 | 0.00 | 0.00 | 0.00 |
Average | 8630.17 | 129.83 | 0.00 | 0.00 | 0.00 |
Sum | 25890.50 | 389.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 80130.00 | 2589.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 182716.17 | 8476.83 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 182716.17 | 8476.83 | 0.00 | 0.00 | 0.00 |
Average | 98624.39 | 3688.61 | 0.00 | 0.00 | 0.00 |
Sum | 295873.17 | 11065.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8695.17 | 64.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8486.00 | 274.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8457.50 | 302.50 | 0.00 | 0.00 | 0.00 |
Min | 8457.50 | 64.83 | 0.00 | 0.00 | 0.00 |
Max | 8695.17 | 302.50 | 0.00 | 0.00 | 0.00 |
Average | 8546.22 | 213.78 | 0.00 | 0.00 | 0.00 |
Sum | 25638.67 | 641.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 77181.50 | 5537.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 179202.17 | 11990.83 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 179202.17 | 11990.83 | 0.00 | 0.00 | 0.00 |
Average | 96470.22 | 5842.78 | 0.00 | 0.00 | 0.00 |
Sum | 289410.67 | 17528.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 | 4.99 | 0.497140E+09 | 603.25 | 11-JAN-08:09 | 9.50 | 7.29 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 | 6.66 | 0.458142E+09 | 676.24 | 27-FEB-16:10 | 19.32 | 12.38 |
March | 2866787.62 | 227.30 | 25-MAR-14:40 | 11.50 | 3.82 | 0.539103E+09 | 707.73 | 18-MAR-15:00 | 11.50 | 3.82 |
April | 68408416.06 | 2233.79 | 27-APR-16:00 | 27.20 | 16.90 | 0.517982E+09 | 768.98 | 27-APR-15:00 | 27.20 | 16.90 |
May | 0.451386E+09 | 3374.47 | 15-MAY-16:00 | 23.90 | 12.85 | 0.599857E+09 | 769.00 | 06-MAY-13:09 | 23.90 | 12.85 |
June | 0.130035E+10 | 5021.19 | 28-JUN-16:00 | 26.10 | 16.29 | 0.640614E+09 | 768.98 | 21-JUN-12:50 | 26.10 | 16.29 |
July | 0.281329E+10 | 16955.48 | 24-JUL-05:02 | 15.87 | 13.15 | 0.632564E+09 | 769.00 | 15-JUL-13:00 | 15.87 | 13.15 |
August | 0.338147E+10 | 17938.59 | 15-AUG-05:03 | 13.05 | 11.44 | 0.684048E+09 | 769.00 | 29-AUG-09:09 | 23.27 | 17.82 |
September | 0.142231E+10 | 4889.17 | 14-SEP-16:00 | 24.40 | 17.04 | 0.617212E+09 | 769.00 | 23-SEP-14:09 | 23.30 | 17.84 |
October | 96389110.09 | 1883.83 | 04-OCT-15:50 | 21.20 | 11.42 | 0.526115E+09 | 768.96 | 04-OCT-15:00 | 21.10 | 11.40 |
November | 90622.57 | 119.88 | 06-NOV-13:50 | 11.70 | 10.15 | 0.479672E+09 | 765.01 | 04-NOV-15:00 | 11.70 | 10.15 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.40 | 3.48 | 0.497165E+09 | 603.25 | 30-DEC-08:09 | 4.32 | 4.10 |
Annual Sum or Average | 0.953657E+10 | 0.668961E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.40 | 3.48 | 0.458142E+09 | 603.25 | 4.32 | 3.82 | ||
Maximum of Months | 0.338147E+10 | 17938.59 | 27.20 | 17.04 | 0.684048E+09 | 769.00 | 27.20 | 17.84 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.283854E+09 | 3893.15 | 20-JAN-13:30 | 6.70 | 4.72 | 0.650971E+09 | 890.41 | 11-JAN-14:30 | 6.70 | 4.72 |
February | 0.722448E+09 | 4084.65 | 08-FEB-13:20 | 6.30 | 3.74 | 0.620520E+09 | 1179.67 | 27-FEB-15:39 | 19.60 | 12.34 |
March | 0.172591E+10 | 4237.10 | 24-MAR-10:20 | 5.73 | 0.93 | 0.774847E+09 | 1237.94 | 18-MAR-15:00 | 5.73 | 0.93 |
April | 0.167766E+10 | 4086.33 | 18-APR-10:00 | 6.10 | 4.31 | 0.844090E+09 | 1800.50 | 27-APR-15:39 | 27.20 | 17.03 |
May | 0.209135E+10 | 4904.55 | 18-MAY-08:20 | 6.47 | 5.77 | 0.116927E+10 | 1999.95 | 15-MAY-15:00 | 6.47 | 5.77 |
June | 0.192219E+10 | 4702.83 | 29-JUN-07:05 | 12.20 | 11.29 | 0.140574E+10 | 2246.80 | 28-JUN-14:09 | 12.20 | 11.29 |
July | 0.259233E+10 | 27939.73 | 24-JUL-17:20 | 28.50 | 17.94 | 0.161123E+10 | 2246.88 | 31-JUL-12:50 | 27.02 | 18.25 |
August | 0.304553E+10 | 32154.02 | 10-AUG-17:10 | 31.62 | 18.84 | 0.177736E+10 | 2246.88 | 10-AUG-12:39 | 31.62 | 18.84 |
September | 0.209195E+10 | 5213.80 | 16-SEP-07:10 | 10.68 | 10.68 | 0.134416E+10 | 2246.77 | 14-SEP-15:00 | 10.68 | 10.68 |
October | 0.171847E+10 | 4395.85 | 12-OCT-07:10 | 6.38 | 5.17 | 0.863561E+09 | 1685.97 | 04-OCT-15:09 | 6.38 | 5.17 |
November | 0.113035E+10 | 4192.49 | 14-NOV-11:10 | 5.10 | 3.47 | 0.665129E+09 | 1318.97 | 04-NOV-14:50 | 5.10 | 3.47 |
December | 0.622479E+09 | 4042.96 | 06-DEC-13:10 | 5.10 | 4.25 | 0.653296E+09 | 894.14 | 02-DEC-13:00 | 5.10 | 4.25 |
Annual Sum or Average | 0.196245E+11 | 0.123802E+11 | ||||||||
Minimum of Months | 0.283854E+09 | 3893.15 | 5.10 | 0.93 | 0.620520E+09 | 890.41 | 5.10 | 0.93 | ||
Maximum of Months | 0.304553E+10 | 32154.02 | 31.62 | 18.84 | 0.177736E+10 | 2246.88 | 31.62 | 18.84 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 | 4.99 | 0.694600E+09 | 1208.45 | 11-JAN-15:09 | 14.40 | 10.49 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 | 6.66 | 0.757889E+09 | 1852.23 | 27-FEB-15:50 | 19.50 | 12.39 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 | 0.121132E+10 | 2146.28 | 18-MAR-15:39 | 20.40 | 10.40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 | 0.159212E+10 | 3544.76 | 29-APR-15:20 | 21.47 | 14.98 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 | 0.257870E+10 | 4437.01 | 15-MAY-15:20 | 23.50 | 12.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.29 | 0.316917E+10 | 5348.00 | 28-JUN-15:30 | 26.10 | 15.92 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.22 | 0.379981E+10 | 6268.29 | 31-JUL-14:39 | 28.30 | 18.91 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.75 | 0.430724E+10 | 6720.87 | 10-AUG-15:00 | 31.20 | 18.74 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 | 0.310988E+10 | 5202.65 | 14-SEP-15:09 | 23.98 | 16.97 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.42 | 0.172574E+10 | 3514.49 | 04-OCT-15:09 | 21.60 | 11.48 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 | 8.04 | 0.960965E+09 | 2298.08 | 04-NOV-15:09 | 20.92 | 15.94 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.40 | 3.48 | 0.735983E+09 | 1217.11 | 05-DEC-14:30 | 10.30 | 6.71 |
Annual Sum or Average | 0.00 | 0.246434E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.40 | 3.48 | 0.694600E+09 | 1208.45 | 10.30 | 6.71 | ||
Maximum of Months | 0.00 | 0.00 | 17.17 | 13.75 | 0.430724E+10 | 6720.87 | 31.20 | 18.91 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.548862E+10 | 24492.74 | 09-JAN-06:12 | -1.3 |
February | 0.443273E+10 | 24474.24 | 13-FEB-06:12 | 2.40 |
March | 0.369783E+10 | 24429.64 | 24-MAR-05:12 | 2.43 |
April | 0.219156E+10 | 24410.19 | 11-APR-05:12 | 5.60 |
May | 0.559284E+09 | 24098.46 | 19-MAY-05:01 | 7.88 |
June | 0.198101E+09 | 23529.00 | 15-JUN-05:02 | 8.98 |
July | 65522890.67 | 1204.26 | 25-JUL-06:10 | 13.98 |
August | 66834857.15 | 1270.15 | 01-AUG-06:10 | 11.32 |
September | 0.147773E+09 | 23534.97 | 28-SEP-05:02 | 8.30 |
October | 0.161372E+10 | 24278.74 | 30-OCT-05:12 | 7.20 |
November | 0.340103E+10 | 24446.26 | 24-NOV-06:12 | 1.83 |
December | 0.468525E+10 | 24477.18 | 26-DEC-06:22 | -1.1 |
Annual Sum or Average | 0.265483E+11 | |||
Minimum of Months | 65522890.67 | 1204.26 | -1.3 | |
Maximum of Months | 0.548862E+10 | 24492.74 | 13.98 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169907E+11 | 63300.67 | 15-JAN-05:23 | -2.5 |
February | 0.123653E+11 | 63477.82 | 19-FEB-04:03 | -5.1 |
March | 0.626304E+10 | 62934.34 | 06-MAR-06:01 | 6.70 |
April | 0.191621E+10 | 62947.55 | 19-APR-05:01 | 1.78 |
May | 89672320.30 | 1129.34 | 05-MAY-16:00 | 25.00 |
June | 65128172.37 | 795.05 | 13-JUN-07:00 | 11.70 |
July | 61820540.34 | 934.18 | 07-JUL-16:10 | 27.02 |
August | 73905675.99 | 886.29 | 22-AUG-16:10 | 26.90 |
September | 64476557.54 | 847.11 | 22-SEP-16:00 | 25.00 |
October | 0.885734E+09 | 62962.82 | 28-OCT-05:06 | 8.22 |
November | 0.759973E+10 | 62921.42 | 30-NOV-06:01 | 5.60 |
December | 0.144289E+11 | 62950.84 | 22-DEC-06:01 | 0.60 |
Annual Sum or Average | 0.608045E+11 | |||
Minimum of Months | 61820540.34 | 795.05 | -5.1 | |
Maximum of Months | 0.169907E+11 | 63477.82 | 27.02 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.410448E+11 | 54300.02 | 15-JAN-05:00 | -2.8 |
February | 0.268723E+11 | 75208.32 | 19-FEB-07:00 | -5.0 |
March | 0.152333E+09 | 7778.70 | 05-MAR-06:33 | 2.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.568880E+10 | 27959.32 | 29-NOV-21:00 | 5.00 |
December | 0.294369E+11 | 41048.12 | 25-DEC-01:53 | 1.10 |
Annual Sum or Average | 0.103195E+12 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.410448E+11 | 75208.32 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.734104E+09 | 762.98 | 02-JAN-16:30 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.639660E+09 | 750.89 | 04-FEB-16:00 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.700794E+09 | 741.95 | 22-MAR-07:10 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.615924E+09 | 726.31 | 03-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.617999E+09 | 697.61 | 17-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.618180E+09 | 687.88 | 29-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.612572E+09 | 724.12 | 12-JUL-08:30 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.663748E+09 | 717.75 | 02-AUG-07:30 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.629478E+09 | 742.79 | 25-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.678293E+09 | 761.64 | 31-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.703721E+09 | 762.98 | 06-NOV-16:49 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.746567E+09 | 762.98 | 01-DEC-16:19 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.796104E+10 | 0.291647E+11 | ||||
Minimum of Months | 0.612572E+09 | 687.88 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.746567E+09 | 762.98 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.337711E+10 | 3394.33 | 13-JAN-15:00 | 0.00 | 0.00 |
February | 0.292511E+10 | 3313.49 | 06-FEB-15:00 | 0.00 | 0.00 |
March | 0.314039E+10 | 3253.39 | 14-MAR-08:09 | 0.00 | 0.00 |
April | 0.268546E+10 | 3095.62 | 19-APR-08:09 | 0.00 | 0.00 |
May | 0.259840E+10 | 3086.48 | 04-MAY-08:09 | 0.00 | 0.00 |
June | 0.258714E+10 | 2939.16 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.267061E+10 | 3225.76 | 12-JUL-08:09 | 0.00 | 0.00 |
August | 0.292963E+10 | 3124.43 | 23-AUG-08:09 | 0.00 | 0.00 |
September | 0.285870E+10 | 3191.50 | 21-SEP-08:09 | 0.00 | 0.00 |
October | 0.315673E+10 | 3284.28 | 31-OCT-08:09 | 0.00 | 0.00 |
November | 0.321244E+10 | 3403.58 | 30-NOV-15:00 | 0.00 | 0.00 |
December | 0.343788E+10 | 3413.39 | 16-DEC-15:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.355796E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.258714E+10 | 2939.16 | 0.00 | 0.00 | |
Maximum of Months | 0.343788E+10 | 3413.39 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.335544E+10 | 3620.02 | 13-JAN-15:00 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.280771E+10 | 3381.45 | 06-FEB-15:00 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.290906E+10 | 3102.81 | 02-MAR-15:00 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.253648E+10 | 2767.37 | 03-APR-07:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.254115E+10 | 2522.88 | 06-MAY-06:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.247204E+10 | 2186.81 | 22-JUN-06:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.251021E+10 | 2849.26 | 12-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.269019E+10 | 2683.50 | 28-AUG-07:30 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.265892E+10 | 3025.07 | 21-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.295194E+10 | 3339.40 | 31-OCT-07:10 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.313641E+10 | 3644.18 | 30-NOV-15:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.351204E+10 | 3671.05 | 16-DEC-15:00 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.340816E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.247204E+10 | 2186.81 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.351204E+10 | 3671.05 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.734104E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259913E+10 |
February | 0.127628E+10 | 0.639660E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218854E+10 |
March | 0.149825E+10 | 0.700794E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209685E+10 |
April | 0.138726E+10 | 0.615924E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11666582.62 | 0.169770E+10 |
May | 0.144276E+10 | 0.617999E+09 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 850121.44 | 0.155082E+10 |
June | 0.144276E+10 | 0.618180E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6663018.73 | 0.131333E+10 |
July | 0.138726E+10 | 0.612572E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38222081.16 | 0.103223E+10 |
August | 0.149825E+10 | 0.663748E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103169E+09 | 0.968533E+09 |
September | 0.138726E+10 | 0.629478E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1386270.13 | 0.952928E+09 |
October | 0.138726E+10 | 0.678293E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162305E+10 |
November | 0.133177E+10 | 0.703721E+09 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202448E+10 |
December | 0.138726E+10 | 0.746567E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229471E+10 |
Annual Sum or Average | 0.168137E+11 | 0.796104E+10 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161957E+09 | 0.203423E+11 |
Minimum of Months | 0.127628E+10 | 0.612572E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952928E+09 |
Maximum of Months | 0.149825E+10 | 0.746567E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103169E+09 | 0.259913E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.337711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.730550E+10 |
February | 0.300332E+10 | 0.292511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 507370.23 | 0.611053E+10 |
March | 0.352563E+10 | 0.314039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3504691.99 | 0.519003E+10 |
April | 0.326447E+10 | 0.268546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93977087.07 | 0.448881E+10 |
May | 0.339505E+10 | 0.259840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 736507.48 | 0.458537E+10 |
June | 0.339505E+10 | 0.258714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430061E+10 |
July | 0.326447E+10 | 0.267061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29371991.16 | 0.407930E+10 |
August | 0.352563E+10 | 0.292963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87635730.46 | 0.374024E+10 |
September | 0.326447E+10 | 0.285870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246306E+10 |
October | 0.326447E+10 | 0.315673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391714E+10 |
November | 0.313390E+10 | 0.321244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242370.67 | 0.481448E+10 |
December | 0.326447E+10 | 0.343788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592005E+10 |
Annual Sum or Average | 0.395654E+11 | 0.355796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215976E+09 | 0.569151E+11 |
Minimum of Months | 0.300332E+10 | 0.258714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246306E+10 |
Maximum of Months | 0.352563E+10 | 0.343788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93977087.07 | 0.730550E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.335544E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90810726.71 | 0.168806E+11 |
February | 0.690763E+10 | 0.280771E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339154E+09 | 0.144561E+11 |
March | 0.810895E+10 | 0.290906E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260691E+09 | 0.137627E+11 |
April | 0.750829E+10 | 0.253648E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.899964E+09 | 0.152696E+11 |
May | 0.780862E+10 | 0.254115E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34707549.20 | 0.201442E+11 |
June | 0.780862E+10 | 0.247204E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37158.07 | 0.192423E+11 |
July | 0.750829E+10 | 0.251021E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11729634.44 | 0.191169E+11 |
August | 0.810895E+10 | 0.269019E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142173E+09 | 0.188034E+11 |
September | 0.750829E+10 | 0.265892E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 105622.99 | 0.117560E+11 |
October | 0.750829E+10 | 0.295194E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 629115.25 | 0.140030E+11 |
November | 0.720796E+10 | 0.313641E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117538E+09 | 0.109701E+11 |
December | 0.750829E+10 | 0.351204E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48995878.63 | 0.122914E+11 |
Annual Sum or Average | 0.910005E+11 | 0.340816E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194654E+10 | 0.186696E+12 |
Minimum of Months | 0.690763E+10 | 0.247204E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37158.07 | 0.109701E+11 |
Maximum of Months | 0.810895E+10 | 0.351204E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.899964E+09 | 0.201442E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 762.98 | 02-JAN-16:30 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 6019.79 | 06-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 750.89 | 04-FEB-16:00 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6268.74 | 13-FEB-18:00 |
March | 1680.92 | 01-MAR-08:09 | 741.95 | 22-MAR-07:10 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6222.22 | 24-MAR-06:10 |
April | 1680.92 | 01-APR-07:10 | 726.31 | 03-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 809.89 | 27-APR-16:10 | 5133.95 | 19-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 697.61 | 17-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.86 | 05-MAY-16:10 | 4536.91 | 24-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 687.88 | 29-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 702.12 | 28-JUN-17:00 | 3592.08 | 14-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 724.12 | 12-JUL-08:30 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1314.35 | 24-JUL-16:10 | 2911.81 | 12-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 717.75 | 02-AUG-07:30 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1877.52 | 10-AUG-17:00 | 3410.76 | 01-AUG-07:00 |
September | 1680.92 | 01-SEP-07:10 | 742.79 | 25-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.77 | 14-SEP-17:00 | 3260.69 | 27-SEP-07:00 |
October | 1680.92 | 02-OCT-07:10 | 761.64 | 31-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4336.07 | 31-OCT-17:00 |
November | 1680.92 | 01-NOV-07:10 | 762.98 | 06-NOV-16:49 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6037.99 | 29-NOV-18:00 |
December | 1680.92 | 01-DEC-08:09 | 762.98 | 01-DEC-16:19 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6200.60 | 26-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 687.88 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2911.81 | |||||
Maximum of Months | 1680.92 | 762.98 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 1877.52 | 6268.74 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3394.33 | 13-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 10097.99 | 28-JAN-08:00 |
February | 3955.50 | 01-FEB-08:09 | 3313.49 | 06-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.41 | 27-FEB-15:00 | 8753.23 | 13-FEB-08:00 |
March | 3955.50 | 01-MAR-08:09 | 3253.39 | 14-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.38 | 18-MAR-16:00 | 8205.16 | 24-MAR-06:07 |
April | 3955.50 | 01-APR-07:10 | 3095.62 | 19-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3476.26 | 01-APR-16:00 | 6717.18 | 08-APR-07:00 |
May | 3955.50 | 01-MAY-07:10 | 3086.48 | 04-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.05 | 05-MAY-16:00 | 6967.80 | 17-MAY-19:00 |
June | 3955.50 | 01-JUN-07:10 | 2939.16 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 7313.11 | 13-JUN-03:00 |
July | 3955.50 | 01-JUL-07:10 | 3225.76 | 12-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1015.17 | 24-JUL-15:10 | 4629.14 | 28-JUL-07:00 |
August | 3955.50 | 01-AUG-07:10 | 3124.43 | 23-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1750.10 | 08-AUG-17:00 | 7082.38 | 11-AUG-04:00 |
September | 3955.50 | 01-SEP-07:10 | 3191.50 | 21-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 4597.42 | 26-SEP-16:00 |
October | 3955.50 | 02-OCT-07:10 | 3284.28 | 31-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 6021.13 | 31-OCT-20:00 |
November | 3955.50 | 01-NOV-07:10 | 3403.58 | 30-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.89 | 04-NOV-15:10 | 9471.90 | 29-NOV-18:00 |
December | 3955.50 | 01-DEC-08:09 | 3413.39 | 16-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 7013.80 | 22-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 2939.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4597.42 | ||||
Maximum of Months | 3955.50 | 3413.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3476.26 | 10097.99 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 3620.02 | 13-JAN-15:00 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6451.21 | 11-JAN-14:00 | 19763.72 | 14-JAN-19:53 |
February | 9097.65 | 01-FEB-08:09 | 3381.45 | 06-FEB-15:00 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4462.88 | 24-FEB-04:00 | 24892.66 | 13-FEB-11:00 |
March | 9097.65 | 01-MAR-08:09 | 3102.81 | 02-MAR-15:00 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8251.04 | 18-MAR-16:00 | 23194.61 | 22-MAR-09:00 |
April | 9097.65 | 01-APR-07:10 | 2767.37 | 03-APR-07:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23318.54 | 01-APR-16:00 | 20216.98 | 18-APR-16:00 |
May | 9097.65 | 01-MAY-07:10 | 2522.88 | 06-MAY-06:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1728.50 | 05-MAY-16:00 | 28055.92 | 10-MAY-15:00 |
June | 9097.65 | 01-JUN-07:10 | 2186.81 | 22-JUN-06:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.93 | 20-JUN-17:00 | 29089.15 | 13-JUN-10:00 |
July | 9097.65 | 01-JUL-07:10 | 2849.26 | 12-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1334.68 | 24-JUL-15:00 | 20422.25 | 03-JUL-16:00 |
August | 9097.65 | 01-AUG-07:10 | 2683.50 | 28-AUG-07:30 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3776.21 | 29-AUG-18:00 | 28758.32 | 11-AUG-04:00 |
September | 9097.65 | 01-SEP-07:10 | 3025.07 | 21-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.38 | 22-SEP-15:50 | 18309.63 | 26-SEP-15:40 |
October | 9097.65 | 02-OCT-07:10 | 3339.40 | 31-OCT-07:10 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 271.14 | 08-OCT-16:00 | 15422.39 | 14-OCT-11:00 |
November | 9097.65 | 01-NOV-07:10 | 3644.18 | 30-NOV-15:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5490.19 | 27-NOV-03:15 | 18012.46 | 29-NOV-17:00 |
December | 9097.65 | 01-DEC-08:09 | 3671.05 | 16-DEC-15:00 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7115.33 | 14-DEC-12:00 | 25370.46 | 26-DEC-14:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 2186.81 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 61.93 | 15422.39 | |||||
Maximum of Months | 9097.65 | 3671.05 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 23318.54 | 29089.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 152.99 | 1409.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 859.69 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 101.99 | 939.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.40 |
March | 227.30 | 25-MAR-14:40 | 1680.92 | 465.42 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.06 |
April | 2233.79 | 27-APR-16:00 | 1680.92 | 465.42 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 280.23 | 0.00 |
May | 3374.47 | 15-MAY-16:00 | 1680.92 | 465.42 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
June | 5021.19 | 28-JUN-16:00 | 1680.92 | 465.42 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 204.01 | 0.00 |
July | 16955.48 | 24-JUL-05:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.84 |
August | 17938.59 | 15-AUG-05:03 | 739.61 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 535.52 |
September | 4889.17 | 14-SEP-16:00 | 1680.92 | 465.42 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 32.01 | 0.00 |
October | 1883.83 | 04-OCT-15:50 | 1680.92 | 484.17 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.61 |
November | 119.88 | 06-NOV-13:50 | 1680.92 | 679.49 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 503.38 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 101.99 | 939.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 101.99 | 939.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17938.59 | 1680.92 | 679.49 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 280.23 | 859.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3893.15 | 20-JAN-13:30 | 3955.50 | 3174.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.36 |
February | 4084.65 | 08-FEB-13:20 | 3955.50 | 3027.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 773.03 |
March | 4237.10 | 24-MAR-10:20 | 3955.50 | 2524.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2009.29 |
April | 4086.33 | 18-APR-10:00 | 3955.50 | 2002.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 903.84 |
May | 4904.55 | 18-MAY-08:20 | 3955.50 | 2627.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2172.00 |
June | 4702.83 | 29-JUN-07:05 | 7911.00 | 5328.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2647.34 |
July | 27939.73 | 24-JUL-17:20 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.31 | 0.00 |
August | 32154.02 | 10-AUG-17:10 | 0.00 | 1496.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 835.54 | 0.00 |
September | 5213.80 | 16-SEP-07:10 | 3955.50 | 2826.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2188.28 |
October | 4395.85 | 12-OCT-07:10 | 3955.50 | 2868.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2325.30 |
November | 4192.49 | 14-NOV-11:10 | 3955.50 | 2947.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 983.37 |
December | 4042.96 | 06-DEC-13:10 | 3955.50 | 3011.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 641.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3893.15 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32154.02 | 7911.00 | 5328.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 835.54 | 2647.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 1344.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8984.93 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 896.48 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3479.16 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6306.68 |
April | 0.00 | 01-APR-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4526.99 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12117.82 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3907.74 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5487.22 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7610.40 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8457.85 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 448.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3869.74 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 896.48 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5470.07 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 896.48 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3728.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 448.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3479.16 | |
Maximum of Months | 0.00 | 0.00 | 1344.72 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12117.82 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.287653E+11 | 24860.99 | 13-JAN-16:00 | 0.821589E+11 | 98131.27 | 09-JAN-06:10 |
February | 0.250976E+11 | 20891.07 | 15-FEB-15:00 | 0.563590E+11 | 121710.97 | 19-FEB-07:10 |
March | 0.269945E+11 | 20472.44 | 14-MAR-08:09 | 0.148423E+11 | 40900.70 | 24-MAR-06:10 |
April | 0.239989E+11 | 19794.78 | 03-APR-08:09 | 0.554455E+10 | 33534.56 | 19-APR-05:10 |
May | 0.240224E+11 | 19762.72 | 05-MAY-14:30 | 0.595715E+09 | 10455.36 | 18-MAY-05:10 |
June | 0.235628E+11 | 19803.23 | 28-JUN-14:00 | 0.115749E+09 | 5667.65 | 14-JUN-05:10 |
July | 0.239207E+11 | 26051.41 | 31-JUL-14:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.263056E+11 | 26988.39 | 10-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.246467E+11 | 20416.01 | 21-SEP-08:09 | 64480253.91 | 5547.52 | 30-SEP-05:10 |
October | 0.261615E+11 | 20800.02 | 31-OCT-08:09 | 0.340283E+10 | 26878.48 | 30-OCT-05:10 |
November | 0.267299E+11 | 24830.70 | 29-NOV-16:19 | 0.234047E+11 | 61588.00 | 29-NOV-17:00 |
December | 0.290040E+11 | 24861.55 | 26-DEC-16:30 | 0.634687E+11 | 78950.41 | 26-DEC-07:19 |
Annual Sum or Average | 0.309210E+12 | 0.249957E+12 | ||||
Minimum of Months | 0.235628E+11 | 19762.72 | 0.00 | 0.00 | ||
Maximum of Months | 0.290040E+11 | 26988.39 | 0.821589E+11 | 121710.97 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.243329E+10 | 7984.45 | 30-JAN-11:30 | 0.00 | 0.00 |
February | 0.395708E+10 | 11347.28 | 27-FEB-12:30 | 0.00 | 0.00 |
March | 0.692566E+10 | 15981.12 | 24-MAR-12:30 | 0.00 | 0.00 |
April | 0.102378E+11 | 18753.37 | 25-APR-12:09 | 0.00 | 0.00 |
May | 0.132303E+11 | 21687.50 | 18-MAY-11:30 | 0.00 | 0.00 |
June | 0.137212E+11 | 20163.18 | 19-JUN-12:09 | 0.00 | 0.00 |
July | 0.145937E+11 | 20329.57 | 05-JUL-10:30 | 0.00 | 0.00 |
August | 0.118361E+11 | 18364.81 | 06-AUG-12:30 | 0.00 | 0.00 |
September | 0.842235E+10 | 16053.22 | 07-SEP-12:30 | 0.00 | 0.00 |
October | 0.543146E+10 | 13674.95 | 03-OCT-11:00 | 0.00 | 0.00 |
November | 0.268707E+10 | 8324.41 | 11-NOV-12:20 | 0.00 | 0.00 |
December | 0.208249E+10 | 6644.04 | 01-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.955586E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.208249E+10 | 6644.04 | 0.00 | 0.00 | |
Maximum of Months | 0.145937E+11 | 21687.50 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.746666E+10 | 0.497022E+10 | 0.112984E+11 | 0.00 | 0.280523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222480E+10 | 0.00 |
February | 0.637248E+10 | 0.398275E+10 | 0.103734E+11 | 0.00 | 0.234167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202732E+10 | 0.00 |
March | 0.675024E+10 | 0.371515E+10 | 0.121089E+11 | 0.00 | 0.213786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228229E+10 | 0.00 |
April | 0.583787E+10 | 0.289871E+10 | 0.112578E+11 | 0.00 | 0.184001E+10 | 0.00 | 0.00 | 16413027.15 | 0.00 | 0.00 | 0.00 | 0.214819E+10 | 0.00 |
May | 0.575755E+10 | 0.248318E+10 | 0.117000E+11 | 0.00 | 0.184265E+10 | 0.00 | 0.00 | 49308174.40 | 0.00 | 0.00 | 0.00 | 0.218971E+10 | 0.00 |
June | 0.567736E+10 | 0.215933E+10 | 0.116594E+11 | 0.00 | 0.183534E+10 | 0.00 | 0.00 | 0.123283E+09 | 0.00 | 0.00 | 0.00 | 0.210811E+10 | 0.00 |
July | 0.579340E+10 | 0.232112E+10 | 0.112984E+11 | 0.00 | 0.177222E+10 | 0.00 | 0.00 | 0.633009E+09 | 0.00 | 0.00 | 0.00 | 0.210254E+10 | 0.00 |
August | 0.628357E+10 | 0.273211E+10 | 0.121016E+11 | 0.00 | 0.196188E+10 | 0.00 | 0.00 | 0.107668E+10 | 0.00 | 0.00 | 0.00 | 0.214981E+10 | 0.00 |
September | 0.614709E+10 | 0.329177E+10 | 0.112504E+11 | 0.00 | 0.176395E+10 | 0.00 | 0.00 | 0.130855E+09 | 0.00 | 0.00 | 0.00 | 0.206266E+10 | 0.00 |
October | 0.678697E+10 | 0.412220E+10 | 0.113057E+11 | 0.00 | 0.180633E+10 | 0.00 | 0.00 | 1224063.41 | 0.00 | 0.00 | 0.00 | 0.213903E+10 | 0.00 |
November | 0.705257E+10 | 0.462146E+10 | 0.108562E+11 | 0.00 | 0.210277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209687E+10 | 0.00 |
December | 0.769649E+10 | 0.513530E+10 | 0.112984E+11 | 0.00 | 0.267100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220289E+10 | 0.00 |
Annual Sum or Average | 0.776222E+11 | 0.424333E+11 | 0.136508E+12 | 0.00 | 0.248809E+11 | 0.00 | 0.00 | 0.203077E+10 | 0.00 | 0.00 | 0.00 | 0.257342E+11 | 0.00 |
Minimum of Months | 0.567736E+10 | 0.215933E+10 | 0.103734E+11 | 0.00 | 0.176395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202732E+10 | 0.00 |
Maximum of Months | 0.769649E+10 | 0.513530E+10 | 0.121089E+11 | 0.00 | 0.280523E+10 | 0.00 | 0.00 | 0.107668E+10 | 0.00 | 0.00 | 0.00 | 0.228229E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.821589E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.563590E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.148423E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.554455E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.595715E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.115749E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 64480253.91 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.340283E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.234047E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.634687E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.249957E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.821589E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 7759.87 | 13-JAN-15:00 | 3768.97 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 2374.71 | 07-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 7245.56 | 15-FEB-15:00 | 3768.97 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 2389.37 | 18-FEB-17:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 6926.00 | 14-MAR-08:09 | 3768.97 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 2363.94 | 24-MAR-06:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 6347.96 | 03-APR-07:10 | 3768.97 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 1925.77 | 11-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 5956.36 | 04-MAY-08:09 | 3421.91 | 01-MAY-19:19 | 10035.17 | 01-MAY-07:10 | 0.00 | 1780.73 | 03-MAY-06:49 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 5516.97 | 29-JUN-07:10 | 3421.91 | 01-JUN-19:00 | 10035.17 | 01-JUN-07:10 | 0.00 | 1780.73 | 03-JUN-13:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 6798.32 | 12-JUL-08:09 | 3421.91 | 01-JUL-20:10 | 10035.17 | 01-JUL-07:10 | 0.00 | 4086.03 | 31-JUL-14:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 6373.50 | 23-AUG-08:09 | 3768.97 | 16-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 4086.03 | 10-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 6938.98 | 21-SEP-08:09 | 3768.97 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 1780.73 | 02-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 7315.04 | 31-OCT-08:09 | 3768.97 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 1902.33 | 31-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 7800.20 | 30-NOV-15:00 | 3768.97 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 2308.68 | 29-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 7838.83 | 16-DEC-15:00 | 3768.97 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 2361.74 | 26-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5516.97 | 3421.91 | 10035.17 | 0.00 | 1780.73 | 0.00 | 0.00 | |||||
Maximum of Months | 7838.83 | 3768.97 | 10035.17 | 0.00 | 4086.03 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2328.42 | 31-JAN-12:30 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2334.43 | 13-FEB-12:00 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2320.00 | 01-MAR-12:20 | 0.00 | 01-MAR-00:10 |
April | 862.19 | 27-APR-15:00 | 0.00 | 0.00 | 0.00 | 2229.73 | 01-APR-11:39 | 0.00 | 01-APR-00:10 |
May | 898.90 | 15-MAY-15:00 | 0.00 | 0.00 | 0.00 | 2073.40 | 02-MAY-11:00 | 0.00 | 01-MAY-00:10 |
June | 2006.97 | 28-JUN-15:00 | 0.00 | 0.00 | 0.00 | 1816.16 | 14-JUN-11:30 | 0.00 | 01-JUN-00:10 |
July | 5223.83 | 31-JUL-15:00 | 0.00 | 0.00 | 0.00 | 1798.51 | 01-JUL-11:09 | 0.00 | 01-JUL-00:10 |
August | 5864.31 | 10-AUG-15:30 | 0.00 | 0.00 | 0.00 | 1792.76 | 31-AUG-11:09 | 0.00 | 01-AUG-00:10 |
September | 1354.84 | 14-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1800.45 | 30-SEP-11:30 | 0.00 | 01-SEP-00:10 |
October | 235.16 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 1912.16 | 27-OCT-11:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2097.29 | 27-NOV-12:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2254.36 | 30-DEC-12:39 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1792.76 | 0.00 | |||
Maximum of Months | 5864.31 | 0.00 | 0.00 | 0.00 | 2334.43 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 24860.99 | 13-JAN-16:00 | 7180.87 | 10035.17 | 3768.97 | 0.00 | 2262.60 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20891.07 | 15-FEB-15:00 | 7245.56 | 10035.17 | 0.00 | 0.00 | 1806.30 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20472.44 | 14-MAR-08:09 | 6926.00 | 10035.17 | 0.00 | 0.00 | 1828.43 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19794.78 | 03-APR-08:09 | 6299.41 | 10035.17 | 0.00 | 0.00 | 1780.73 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19762.72 | 05-MAY-14:30 | 5352.44 | 10035.17 | 0.00 | 0.00 | 1780.73 | 0.00 | 0.00 | 812.90 | 0.00 |
June | 19803.23 | 28-JUN-14:00 | 4280.81 | 10035.17 | 0.00 | 0.00 | 1780.73 | 0.00 | 0.00 | 1945.24 | 0.00 |
July | 26051.41 | 31-JUL-14:39 | 5161.47 | 10035.17 | 0.00 | 0.00 | 4086.03 | 0.00 | 0.00 | 5013.83 | 0.00 |
August | 26988.39 | 10-AUG-14:00 | 5414.09 | 10035.17 | 0.00 | 0.00 | 4086.03 | 0.00 | 0.00 | 5698.31 | 0.00 |
September | 20416.01 | 21-SEP-08:09 | 6938.98 | 10035.17 | 0.00 | 0.00 | 1780.73 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20800.02 | 31-OCT-08:09 | 7315.04 | 10035.17 | 0.00 | 0.00 | 1780.73 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 24830.70 | 29-NOV-16:19 | 7180.87 | 10035.17 | 3768.97 | 0.00 | 2236.51 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 24861.55 | 26-DEC-16:30 | 7180.87 | 10035.17 | 3768.97 | 0.00 | 2264.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 19762.72 | 4280.81 | 10035.17 | 0.00 | 0.00 | 1780.73 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26988.39 | 7315.04 | 10035.17 | 3768.97 | 0.00 | 4086.03 | 0.00 | 0.00 | 5698.31 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 98131.27 | 09-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 121710.97 | 19-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 40900.70 | 24-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 33534.56 | 19-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 10455.36 | 18-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 5667.65 | 14-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 5547.52 | 30-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 26878.48 | 30-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 61588.00 | 29-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 78950.41 | 26-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 121710.97 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.17 | 18.41 | 8.67 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
February | 9.33 | 18.95 | 8.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
March | 9.50 | 19.53 | 9.00 | 19.66 | 0.00 | 19.66 | 0.00 | 19.66 |
April | 7.33 | 19.98 | 7.33 | 19.98 | 0.00 | 19.98 | 0.00 | 19.98 |
May | 1.00 | 20.43 | 1.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
June | 0.50 | 20.50 | 0.50 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.54 | 0.83 | 24.54 |
September | 0.50 | 20.38 | 0.50 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
October | 5.33 | 20.19 | 5.33 | 20.19 | 0.00 | 20.19 | 0.00 | 20.19 |
November | 8.00 | 19.87 | 8.00 | 19.87 | 0.00 | 19.87 | 0.00 | 19.87 |
December | 9.33 | 19.15 | 8.67 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
Annual Sum or Average | 62.00 | 19.37 | 57.00 | 19.55 | 0.83 | 19.59 | 0.83 | 19.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 11.17 | 20.50 | 9.00 | 20.50 | 0.83 | 24.54 | 0.83 | 24.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 82.17 | 14.82 | 3.50 | 14.82 | 0.00 | 14.82 | 0.00 | 14.82 |
February | 57.50 | 14.79 | 2.67 | 14.79 | 0.00 | 14.79 | 0.00 | 14.79 |
March | 19.67 | 14.94 | 2.00 | 14.94 | 0.00 | 14.94 | 0.00 | 14.94 |
April | 4.50 | 14.96 | 0.17 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.00 | 27.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.00 | 27.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3.17 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
November | 19.17 | 14.94 | 1.50 | 14.94 | 0.00 | 14.94 | 0.00 | 14.94 |
December | 60.67 | 14.89 | 3.00 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
Annual Sum or Average | 246.83 | 14.86 | 12.83 | 14.86 | 0.50 | 14.88 | 0.00 | 14.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 82.17 | 14.97 | 3.50 | 14.97 | 0.33 | 27.29 | 0.00 | 27.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.05 | 300.00 | 21.05 | 300.00 | 21.05 |
February | 276.00 | 21.07 | 273.33 | 21.06 | 273.33 | 21.06 |
March | 324.00 | 21.10 | 315.50 | 21.08 | 315.50 | 21.08 |
April | 300.00 | 21.46 | 231.33 | 21.30 | 231.33 | 21.24 |
May | 310.83 | 22.52 | 56.50 | 22.30 | 56.50 | 22.14 |
June | 281.83 | 23.25 | 6.33 | 23.22 | 3.50 | 23.19 |
July | 119.83 | 23.62 | 81.33 | 23.73 | 0.00 | 23.73 |
August | 82.83 | 23.61 | 134.50 | 23.79 | 0.67 | 23.79 |
September | 234.17 | 23.23 | 25.17 | 23.24 | 5.00 | 23.20 |
October | 300.00 | 21.60 | 194.50 | 21.40 | 194.50 | 21.31 |
November | 288.00 | 21.11 | 277.83 | 21.09 | 277.83 | 21.08 |
December | 300.00 | 21.05 | 300.00 | 21.05 | 300.00 | 21.05 |
Annual Sum or Average | 3117.50 | 21.83 | 2196.33 | 21.64 | 1958.17 | 21.49 |
Minimum of Months | 82.83 | 21.05 | 6.33 | 21.05 | 0.00 | 21.05 |
Maximum of Months | 324.00 | 23.62 | 315.50 | 23.79 | 315.50 | 23.79 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.56 | 300.00 | 15.56 | 300.00 | 15.56 |
February | 276.00 | 15.80 | 276.00 | 15.80 | 276.00 | 15.80 |
March | 324.00 | 16.25 | 324.00 | 16.25 | 324.00 | 16.25 |
April | 300.00 | 17.54 | 274.67 | 17.34 | 274.67 | 17.27 |
May | 299.67 | 20.20 | 160.00 | 19.79 | 157.33 | 19.57 |
June | 241.67 | 21.67 | 83.17 | 21.91 | 40.00 | 21.64 |
July | 115.67 | 23.37 | 171.83 | 24.84 | 18.83 | 24.95 |
August | 103.83 | 24.01 | 227.00 | 25.16 | 33.33 | 25.29 |
September | 224.83 | 21.50 | 98.83 | 21.99 | 36.83 | 21.71 |
October | 300.00 | 17.77 | 262.50 | 17.53 | 262.50 | 17.44 |
November | 288.00 | 15.99 | 288.00 | 15.99 | 288.00 | 15.99 |
December | 300.00 | 15.59 | 300.00 | 15.59 | 300.00 | 15.59 |
Annual Sum or Average | 3073.67 | 18.05 | 2766.00 | 18.11 | 2311.50 | 17.72 |
Minimum of Months | 103.83 | 15.56 | 83.17 | 15.56 | 18.83 | 15.56 |
Maximum of Months | 324.00 | 24.01 | 324.00 | 25.16 | 324.00 | 25.29 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 10.34 | 300.00 | 10.34 | 300.00 | 10.34 |
February | 276.00 | 11.19 | 276.00 | 11.19 | 276.00 | 11.19 |
March | 324.00 | 13.10 | 324.00 | 13.10 | 324.00 | 13.10 |
April | 300.00 | 15.68 | 286.83 | 15.56 | 286.83 | 15.51 |
May | 309.67 | 19.86 | 194.33 | 19.42 | 194.33 | 19.23 |
June | 250.83 | 21.40 | 91.83 | 21.50 | 54.17 | 21.17 |
July | 139.67 | 24.25 | 174.17 | 25.37 | 43.00 | 25.69 |
August | 129.17 | 25.80 | 242.50 | 26.13 | 71.33 | 26.47 |
September | 226.50 | 21.49 | 107.50 | 21.83 | 50.33 | 21.48 |
October | 300.00 | 16.43 | 289.17 | 16.34 | 289.17 | 16.31 |
November | 288.00 | 12.34 | 288.00 | 12.34 | 288.00 | 12.34 |
December | 300.00 | 10.61 | 300.00 | 10.61 | 300.00 | 10.61 |
Annual Sum or Average | 3143.83 | 15.88 | 2874.33 | 15.82 | 2477.17 | 15.35 |
Minimum of Months | 129.17 | 10.34 | 91.83 | 10.34 | 43.00 | 10.34 |
Maximum of Months | 324.00 | 25.80 | 324.00 | 26.13 | 324.00 | 26.47 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 74446185.45 | 16413027.15 | 12.67 | 70991246.21 | 3454939.24 | 0.00 | 0.51 | 27-APR-16:00 | 0.00 | 01-APR-00:10 | 3948.47 | 27-APR-16:00 | 3656.38 | 27-APR-16:00 | 292.09 | 27-APR-16:00 | 862.19 | 27-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.234975E+09 | 49308174.40 | 29.33 | 0.213610E+09 | 21364383.31 | 0.00 | 0.58 | 15-MAY-16:00 | 0.00 | 01-MAY-00:10 | 4390.01 | 06-MAY-15:00 | 4387.83 | 15-MAY-16:00 | 835.94 | 06-MAY-13:00 | 898.90 | 15-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.560873E+09 | 0.117258E+09 | 67.33 | 0.544357E+09 | 16515315.95 | 0.00 | 0.80 | 28-JUN-16:00 | 0.00 | 01-JUN-00:10 | 6541.84 | 28-JUN-16:00 | 6306.95 | 28-JUN-16:00 | 310.36 | 21-JUN-17:00 | 1336.57 | 28-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.197891E+10 | 0.406685E+09 | 143.80 | 0.173166E+10 | 0.247250E+09 | 0.00 | 1.00 | 24-JUL-05:02 | 0.00 | 01-JUL-00:10 | 15466.25 | 31-JUL-05:55 | 10980.37 | 24-JUL-05:02 | 5889.94 | 25-JUL-05:03 | 3109.80 | 31-JUL-05:55 | 0.00 | 01-JUL-00:10 |
August | 0.293633E+10 | 0.606452E+09 | 184.04 | 0.254822E+10 | 0.388105E+09 | 0.00 | 1.00 | 01-AUG-05:03 | 0.00 | 01-AUG-00:10 | 15653.89 | 25-AUG-05:03 | 10925.54 | 09-AUG-05:03 | 6395.76 | 26-AUG-05:03 | 3144.16 | 25-AUG-05:03 | 0.00 | 01-AUG-00:10 |
September | 0.637304E+09 | 0.130855E+09 | 58.08 | 0.534945E+09 | 0.102359E+09 | 0.00 | 0.81 | 14-SEP-16:00 | 0.00 | 01-SEP-00:10 | 6863.46 | 14-SEP-16:00 | 5962.91 | 14-SEP-16:00 | 1394.98 | 14-SEP-13:00 | 1354.84 | 14-SEP-16:00 | 0.00 | 01-SEP-00:10 |
October | 5556338.93 | 1224063.41 | 4.17 | 5556336.59 | 2.34 | 0.00 | 0.16 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1074.54 | 04-OCT-15:00 | 1074.54 | 04-OCT-15:00 | 0.00 | 06-OCT-13:20 | 235.16 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.642839E+10 | 0.132820E+10 | 499.42 | 0.564934E+10 | 0.779049E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.293633E+10 | 0.606452E+09 | 184.04 | 0.254822E+10 | 0.388105E+09 | 0.00 | 1.00 | 0.00 | 15653.89 | 10980.37 | 6395.76 | 3144.16 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 23097984.63 | 6025409.20 | 3.50 | 22613766.13 | 484218.50 | 0.00 | 0.16 | 28-JUN-15:00 | 0.00 | 01-JUN-00:10 | 2635.71 | 28-JUN-15:00 | 2635.71 | 28-JUN-15:00 | 81.50 | 28-JUN-16:00 | 685.85 | 28-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.918095E+09 | 0.226323E+09 | 42.01 | 0.795544E+09 | 0.122551E+09 | 0.00 | 1.00 | 23-JUL-13:25 | 0.00 | 01-JUL-00:10 | 39756.15 | 31-JUL-18:02 | 37070.22 | 23-JUL-13:25 | 6578.50 | 31-JUL-18:02 | 8909.80 | 31-JUL-18:02 | 0.00 | 01-JUL-00:10 |
August | 0.188232E+10 | 0.470229E+09 | 74.36 | 0.163310E+10 | 0.249222E+09 | 0.00 | 1.00 | 10-AUG-17:10 | 0.00 | 01-AUG-00:10 | 39758.31 | 13-AUG-13:35 | 36440.31 | 15-AUG-17:45 | 6482.95 | 13-AUG-11:35 | 9249.99 | 10-AUG-17:10 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.282351E+10 | 0.702577E+09 | 119.87 | 0.245126E+10 | 0.372258E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.188232E+10 | 0.470229E+09 | 74.36 | 0.163310E+10 | 0.249222E+09 | 0.00 | 1.00 | 0.00 | 39758.31 | 37070.22 | 6578.50 | 9249.99 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.95 | 10.38 | 24.57 | 18.74 | 93.70 | 0.00 | 0.00 | 0.00 |
February | 62.09 | 23.13 | 38.96 | 52.69 | 79.28 | 0.00 | 0.00 | 0.00 |
March | 87.46 | 29.55 | 57.91 | 87.57 | 60.78 | 0.00 | 0.00 | 0.00 |
April | 132.77 | 50.66 | 82.11 | 153.81 | 48.34 | 0.00 | 0.00 | 0.00 |
May | 171.26 | 69.65 | 101.61 | 206.04 | 46.46 | 0.00 | 0.00 | 0.00 |
June | 164.65 | 63.94 | 100.71 | 197.37 | 39.94 | 0.00 | 0.00 | 0.00 |
July | 203.76 | 107.26 | 96.50 | 258.36 | 42.27 | 0.00 | 0.00 | 0.00 |
August | 168.21 | 85.80 | 82.41 | 215.13 | 43.17 | 0.00 | 0.00 | 0.00 |
September | 137.49 | 66.14 | 71.34 | 165.41 | 54.12 | 0.00 | 0.00 | 0.00 |
October | 78.30 | 32.03 | 46.27 | 83.41 | 56.87 | 0.00 | 0.00 | 0.00 |
November | 38.96 | 11.10 | 27.86 | 28.20 | 70.79 | 0.00 | 0.00 | 0.00 |
December | 33.05 | 11.59 | 21.46 | 21.78 | 94.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.70 | 46.95 | 62.75 | 124.50 | 60.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.05 | 10.38 | 21.46 | 18.74 | 39.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 203.76 | 107.26 | 101.61 | 258.36 | 94.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.95 | 10.38 | 24.57 | 18.74 | 93.70 | 0.00 | 0.00 | 0.00 |
February | 62.09 | 23.13 | 38.96 | 52.69 | 79.28 | 0.00 | 0.00 | 0.00 |
March | 87.46 | 29.55 | 57.91 | 87.57 | 60.78 | 0.00 | 0.00 | 0.00 |
April | 132.77 | 50.66 | 82.11 | 153.81 | 48.34 | 0.00 | 0.00 | 0.00 |
May | 171.26 | 69.65 | 101.61 | 206.04 | 46.46 | 0.00 | 0.00 | 0.00 |
June | 164.65 | 63.94 | 100.71 | 197.37 | 39.94 | 0.00 | 0.00 | 0.00 |
July | 203.76 | 107.26 | 96.50 | 258.36 | 42.27 | 0.00 | 0.00 | 0.00 |
August | 168.21 | 85.80 | 82.41 | 215.13 | 43.17 | 0.00 | 0.00 | 0.00 |
September | 137.49 | 66.14 | 71.34 | 165.41 | 54.12 | 0.00 | 0.00 | 0.00 |
October | 78.30 | 32.03 | 46.27 | 83.41 | 56.87 | 0.00 | 0.00 | 0.00 |
November | 38.96 | 11.10 | 27.86 | 28.20 | 70.79 | 0.00 | 0.00 | 0.00 |
December | 33.05 | 11.59 | 21.46 | 21.78 | 94.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.70 | 46.95 | 62.75 | 124.50 | 60.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.05 | 10.38 | 21.46 | 18.74 | 39.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 203.76 | 107.26 | 101.61 | 258.36 | 94.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.98 | 0.00 | 11.98 | 1.22 | 57.46 | 0.00 | 0.00 | 0.00 |
February | 18.63 | 0.00 | 18.63 | 6.73 | 48.48 | 0.00 | 0.00 | 0.00 |
March | 27.46 | 0.00 | 27.46 | 17.59 | 36.34 | 0.00 | 0.00 | 0.00 |
April | 38.91 | 0.19 | 38.73 | 34.40 | 27.88 | 0.00 | 0.00 | 0.00 |
May | 49.97 | 1.46 | 48.51 | 48.66 | 26.16 | 0.00 | 0.00 | 0.00 |
June | 52.56 | 3.46 | 49.11 | 52.77 | 22.08 | 0.00 | 0.00 | 0.00 |
July | 50.00 | 3.94 | 46.07 | 52.13 | 23.23 | 0.00 | 0.00 | 0.00 |
August | 40.62 | 1.24 | 39.38 | 42.61 | 23.84 | 0.00 | 0.00 | 0.00 |
September | 31.43 | 0.02 | 31.41 | 26.32 | 31.94 | 0.00 | 0.00 | 0.00 |
October | 21.52 | 0.00 | 21.52 | 14.40 | 33.82 | 0.00 | 0.00 | 0.00 |
November | 13.56 | 0.00 | 13.56 | 4.23 | 42.68 | 0.00 | 0.00 | 0.00 |
December | 10.18 | 0.00 | 10.18 | 0.89 | 56.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 30.63 | 0.87 | 29.76 | 25.27 | 35.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.18 | 0.00 | 10.18 | 0.89 | 22.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.56 | 3.94 | 49.11 | 52.77 | 57.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.97 | 0.00 | 11.97 | 1.22 | 57.46 | 0.00 | 0.00 | 0.00 |
February | 18.63 | 0.00 | 18.63 | 6.73 | 48.48 | 0.00 | 0.00 | 0.00 |
March | 27.46 | 0.00 | 27.46 | 17.59 | 36.34 | 0.00 | 0.00 | 0.00 |
April | 38.91 | 0.19 | 38.73 | 34.40 | 27.88 | 0.00 | 0.00 | 0.00 |
May | 49.97 | 1.46 | 48.51 | 48.65 | 26.16 | 0.00 | 0.00 | 0.00 |
June | 52.56 | 3.46 | 49.10 | 52.76 | 22.08 | 0.00 | 0.00 | 0.00 |
July | 50.00 | 3.94 | 46.07 | 52.13 | 23.23 | 0.00 | 0.00 | 0.00 |
August | 40.62 | 1.24 | 39.38 | 42.61 | 23.84 | 0.00 | 0.00 | 0.00 |
September | 31.43 | 0.02 | 31.41 | 26.32 | 31.94 | 0.00 | 0.00 | 0.00 |
October | 21.52 | 0.00 | 21.52 | 14.40 | 33.82 | 0.00 | 0.00 | 0.00 |
November | 13.56 | 0.00 | 13.56 | 4.23 | 42.68 | 0.00 | 0.00 | 0.00 |
December | 10.18 | 0.00 | 10.18 | 0.89 | 56.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 30.63 | 0.86 | 29.76 | 25.27 | 35.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.18 | 0.00 | 10.18 | 0.89 | 22.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.56 | 3.94 | 49.10 | 52.76 | 57.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.28 | 35.05 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.50 | 31.03 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.79 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.78 | 19.81 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.60 | 19.67 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.52 | 17.87 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.55 | 19.64 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.64 | 20.54 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 67.07 | 24.25 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.45 | 22.95 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.76 | 26.27 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.41 | 24.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.55 | 35.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.28 | 35.05 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.50 | 31.03 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.79 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.78 | 19.81 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.60 | 19.67 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.52 | 17.87 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.55 | 19.64 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.64 | 20.54 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 67.07 | 24.25 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.45 | 22.95 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.76 | 26.27 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.41 | 24.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.55 | 35.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.28 | 35.05 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.50 | 31.03 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.79 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.78 | 19.81 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.60 | 19.67 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.52 | 17.87 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.55 | 19.64 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.64 | 20.54 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 67.07 | 24.25 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.45 | 22.95 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.76 | 26.27 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.41 | 24.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.55 | 35.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.28 | 35.05 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.50 | 31.03 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.79 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.78 | 19.81 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.60 | 19.67 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.52 | 17.87 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.55 | 19.64 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.64 | 20.54 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 67.07 | 24.25 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.45 | 22.95 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.76 | 26.27 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.41 | 24.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.55 | 35.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.28 | 35.05 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.50 | 31.03 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.79 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.78 | 19.81 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.60 | 19.67 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.52 | 17.87 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.55 | 19.64 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.64 | 20.54 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 67.07 | 24.25 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.45 | 22.95 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.76 | 26.27 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.41 | 24.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.55 | 35.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.28 | 35.05 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.50 | 31.03 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.79 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.78 | 19.81 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.60 | 19.67 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.52 | 17.87 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.55 | 19.64 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.64 | 20.54 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 67.07 | 24.25 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.45 | 22.95 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.76 | 26.27 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.41 | 24.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.55 | 35.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.28 | 35.05 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.50 | 31.03 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.79 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.78 | 19.81 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.60 | 19.67 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.52 | 17.87 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.55 | 19.64 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.64 | 20.54 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 67.07 | 24.25 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.45 | 22.95 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.76 | 26.27 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.41 | 24.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.55 | 35.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.28 | 35.05 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.50 | 31.03 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.79 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.78 | 19.81 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.60 | 19.67 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.52 | 17.87 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.55 | 19.64 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.64 | 20.54 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 67.07 | 24.25 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.45 | 22.95 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.76 | 26.27 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.41 | 24.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.55 | 35.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.28 | 35.05 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.50 | 31.03 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.79 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.78 | 19.81 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.60 | 19.67 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.52 | 17.87 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.55 | 19.64 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.64 | 20.54 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 67.07 | 24.25 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.45 | 22.95 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.76 | 26.27 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.41 | 24.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.55 | 35.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.28 | 35.05 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.50 | 31.03 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.79 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.78 | 19.81 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.60 | 19.67 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.52 | 17.87 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.55 | 19.64 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.64 | 20.54 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 67.07 | 24.25 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.45 | 22.95 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.76 | 26.27 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.41 | 24.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.55 | 35.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.28 | 35.05 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.50 | 31.03 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.79 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.78 | 19.81 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.60 | 19.67 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.52 | 17.87 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.55 | 19.64 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.64 | 20.54 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 67.07 | 24.25 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.45 | 22.95 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.76 | 26.27 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.41 | 24.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.55 | 35.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.28 | 35.05 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.50 | 31.03 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.79 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.78 | 19.81 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.60 | 19.67 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.52 | 17.87 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.55 | 19.64 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.64 | 20.54 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 67.07 | 24.25 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.45 | 22.95 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.76 | 26.27 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.41 | 24.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.55 | 35.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.28 | 35.05 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.50 | 31.03 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.79 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.78 | 19.81 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.60 | 19.67 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.52 | 17.87 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.55 | 19.64 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.64 | 20.54 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 67.07 | 24.25 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.45 | 22.95 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.76 | 26.27 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.41 | 24.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.55 | 35.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.28 | 35.05 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.50 | 31.03 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.79 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.78 | 19.81 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.60 | 19.67 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.52 | 17.87 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.55 | 19.64 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.64 | 20.54 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 67.07 | 24.25 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.45 | 22.95 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.76 | 26.27 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.41 | 24.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.55 | 35.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.14 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.91 | 27.32 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.74 | 23.31 | 10.50 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.33 | 21.71 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.59 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.37 | 22.78 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.41 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 144.03 | 28.26 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.13 | 31.60 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 58.02 | 26.64 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.94 | 22.98 | 45.83 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.91 | 29.75 | 43.33 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.92 | 26.23 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.91 | 21.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.41 | 31.60 | 45.83 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93609665.34 | 27794440.75 | 65815224.59 | 50197784.33 | 0.250965E+09 |
February | 0.150213E+09 | 55949557.06 | 94263196.03 | 0.127462E+09 | 0.191800E+09 |
March | 0.234262E+09 | 79147176.98 | 0.155114E+09 | 0.234559E+09 | 0.162791E+09 |
April | 0.344143E+09 | 0.131311E+09 | 0.212832E+09 | 0.398684E+09 | 0.125308E+09 |
May | 0.458698E+09 | 0.186554E+09 | 0.272144E+09 | 0.551851E+09 | 0.124451E+09 |
June | 0.426781E+09 | 0.165731E+09 | 0.261050E+09 | 0.511594E+09 | 0.103531E+09 |
July | 0.545756E+09 | 0.287298E+09 | 0.258458E+09 | 0.692002E+09 | 0.113203E+09 |
August | 0.450522E+09 | 0.229801E+09 | 0.220721E+09 | 0.576205E+09 | 0.115631E+09 |
September | 0.356369E+09 | 0.171446E+09 | 0.184923E+09 | 0.428737E+09 | 0.140268E+09 |
October | 0.209711E+09 | 85792715.97 | 0.123919E+09 | 0.223407E+09 | 0.152311E+09 |
November | 0.100982E+09 | 28765899.50 | 72215864.18 | 73085219.47 | 0.183479E+09 |
December | 88528491.19 | 31053499.54 | 57474991.65 | 58338593.36 | 0.252828E+09 |
Annual Sum or Average | 0.345957E+10 | 0.148064E+10 | 0.197893E+10 | 0.392612E+10 | 0.191657E+10 |
Minimum of Months | 88528491.19 | 27794440.75 | 57474991.65 | 50197784.33 | 0.103531E+09 |
Maximum of Months | 0.545756E+09 | 0.287298E+09 | 0.272144E+09 | 0.692002E+09 | 0.252828E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93609665.34 | 27794440.75 | 65815224.59 | 50197784.33 | 0.250965E+09 |
February | 0.150213E+09 | 55949557.06 | 94263196.03 | 0.127462E+09 | 0.191800E+09 |
March | 0.234262E+09 | 79147176.98 | 0.155114E+09 | 0.234559E+09 | 0.162791E+09 |
April | 0.344143E+09 | 0.131311E+09 | 0.212832E+09 | 0.398684E+09 | 0.125308E+09 |
May | 0.458698E+09 | 0.186554E+09 | 0.272144E+09 | 0.551851E+09 | 0.124451E+09 |
June | 0.426781E+09 | 0.165731E+09 | 0.261050E+09 | 0.511594E+09 | 0.103531E+09 |
July | 0.545756E+09 | 0.287298E+09 | 0.258458E+09 | 0.692002E+09 | 0.113203E+09 |
August | 0.450522E+09 | 0.229801E+09 | 0.220721E+09 | 0.576205E+09 | 0.115631E+09 |
September | 0.356369E+09 | 0.171446E+09 | 0.184923E+09 | 0.428737E+09 | 0.140268E+09 |
October | 0.209711E+09 | 85792715.97 | 0.123919E+09 | 0.223407E+09 | 0.152311E+09 |
November | 0.100982E+09 | 28765899.50 | 72215864.18 | 73085219.47 | 0.183479E+09 |
December | 88528491.19 | 31053499.54 | 57474991.65 | 58338593.36 | 0.252828E+09 |
Annual Sum or Average | 0.345957E+10 | 0.148064E+10 | 0.197893E+10 | 0.392612E+10 | 0.191657E+10 |
Minimum of Months | 88528491.19 | 27794440.75 | 57474991.65 | 50197784.33 | 0.103531E+09 |
Maximum of Months | 0.545756E+09 | 0.287298E+09 | 0.272144E+09 | 0.692002E+09 | 0.252828E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 32074850.23 | 0.00 | 32074850.23 | 3266880.69 | 0.153898E+09 |
February | 45079413.90 | 0.00 | 45079413.90 | 16274190.74 | 0.117281E+09 |
March | 73544133.97 | 1466.78 | 73542667.18 | 47124318.56 | 97343735.78 |
April | 0.100868E+09 | 488603.01 | 0.100379E+09 | 89156643.61 | 72254837.58 |
May | 0.133835E+09 | 3913254.10 | 0.129921E+09 | 0.130321E+09 | 70063668.11 |
June | 0.136248E+09 | 8965120.00 | 0.127282E+09 | 0.136768E+09 | 57221486.46 |
July | 0.133925E+09 | 10540813.15 | 0.123384E+09 | 0.139626E+09 | 62219932.96 |
August | 0.108790E+09 | 3317738.52 | 0.105473E+09 | 0.114127E+09 | 63865473.46 |
September | 81468951.01 | 52736.79 | 81416214.22 | 68223773.35 | 82797803.84 |
October | 57650012.96 | 0.00 | 57650012.96 | 38574249.21 | 90596507.32 |
November | 35142384.98 | 0.00 | 35142384.98 | 10962563.61 | 0.110628E+09 |
December | 27255351.36 | 0.00 | 27255351.36 | 2370718.96 | 0.152443E+09 |
Annual Sum or Average | 0.965880E+09 | 27279732.36 | 0.938601E+09 | 0.796796E+09 | 0.113061E+10 |
Minimum of Months | 27255351.36 | 0.00 | 27255351.36 | 2370718.96 | 57221486.46 |
Maximum of Months | 0.136248E+09 | 10540813.15 | 0.129921E+09 | 0.139626E+09 | 0.153898E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 32073727.19 | 0.00 | 32073727.19 | 3266419.42 | 0.153898E+09 |
February | 45077910.44 | 0.00 | 45077910.44 | 16272890.20 | 0.117281E+09 |
March | 73541746.59 | 1466.72 | 73540279.88 | 47121780.14 | 97343508.12 |
April | 0.100864E+09 | 488580.11 | 0.100376E+09 | 89152953.83 | 72254596.72 |
May | 0.133830E+09 | 3913070.68 | 0.129917E+09 | 0.130315E+09 | 70063395.87 |
June | 0.136243E+09 | 8964699.80 | 0.127279E+09 | 0.136763E+09 | 57221238.44 |
July | 0.133921E+09 | 10540319.09 | 0.123381E+09 | 0.139621E+09 | 62219616.75 |
August | 0.108787E+09 | 3317583.01 | 0.105470E+09 | 0.114124E+09 | 63865098.51 |
September | 81466488.84 | 52734.32 | 81413754.52 | 68220936.26 | 82797317.48 |
October | 57648172.51 | 0.00 | 57648172.51 | 38572281.82 | 90596054.17 |
November | 35141163.59 | 0.00 | 35141163.59 | 10961609.41 | 0.110628E+09 |
December | 27254410.75 | 0.00 | 27254410.75 | 2370392.81 | 0.152443E+09 |
Annual Sum or Average | 0.965850E+09 | 27278453.72 | 0.938572E+09 | 0.796763E+09 | 0.113061E+10 |
Minimum of Months | 27254410.75 | 0.00 | 27254410.75 | 2370392.81 | 57221238.44 |
Maximum of Months | 0.136243E+09 | 10540319.09 | 0.129917E+09 | 0.139621E+09 | 0.153898E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22169498.07 | 93879218.72 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54430333.61 | 75073379.69 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125311E+09 | 64734387.76 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211962E+09 | 51335454.11 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.288207E+09 | 52674962.26 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304606E+09 | 46312441.74 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333607E+09 | 52595845.01 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266877E+09 | 55025362.22 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173845E+09 | 62850036.15 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100311E+09 | 61475715.25 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35662318.57 | 68099514.03 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19707338.32 | 94753381.84 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193670E+10 | 0.778810E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19707338.32 | 46312441.74 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333607E+09 | 94753381.84 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22169498.07 | 93879218.72 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54430333.61 | 75073379.69 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125311E+09 | 64734387.76 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211962E+09 | 51335454.11 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.288207E+09 | 52674962.26 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304606E+09 | 46312441.74 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333607E+09 | 52595845.01 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266877E+09 | 55025362.22 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173845E+09 | 62850036.15 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100311E+09 | 61475715.25 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35662318.57 | 68099514.03 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19707338.32 | 94753381.84 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193670E+10 | 0.778810E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19707338.32 | 46312441.74 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333607E+09 | 94753381.84 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22169498.07 | 93879218.72 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54430333.61 | 75073379.69 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125311E+09 | 64734387.76 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211962E+09 | 51335454.11 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.288207E+09 | 52674962.26 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304606E+09 | 46312441.74 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333607E+09 | 52595845.01 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266877E+09 | 55025362.22 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173845E+09 | 62850036.15 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100311E+09 | 61475715.25 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35662318.57 | 68099514.03 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19707338.32 | 94753381.84 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193670E+10 | 0.778810E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19707338.32 | 46312441.74 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333607E+09 | 94753381.84 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22169498.07 | 93879218.72 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54430333.61 | 75073379.69 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125311E+09 | 64734387.76 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211962E+09 | 51335454.11 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.288207E+09 | 52674962.26 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304606E+09 | 46312441.74 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333607E+09 | 52595845.01 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266877E+09 | 55025362.22 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173845E+09 | 62850036.15 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100311E+09 | 61475715.25 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35662318.57 | 68099514.03 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19707338.32 | 94753381.84 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193670E+10 | 0.778810E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19707338.32 | 46312441.74 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333607E+09 | 94753381.84 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22169498.07 | 93879218.72 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54430333.61 | 75073379.69 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125311E+09 | 64734387.76 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211962E+09 | 51335454.11 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.288207E+09 | 52674962.26 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304606E+09 | 46312441.74 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333607E+09 | 52595845.01 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266877E+09 | 55025362.22 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173845E+09 | 62850036.15 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100311E+09 | 61475715.25 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35662318.57 | 68099514.03 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19707338.32 | 94753381.84 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193670E+10 | 0.778810E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19707338.32 | 46312441.74 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333607E+09 | 94753381.84 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22169498.07 | 93879218.72 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54430333.61 | 75073379.69 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125311E+09 | 64734387.76 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211962E+09 | 51335454.11 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.288207E+09 | 52674962.26 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304606E+09 | 46312441.74 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333607E+09 | 52595845.01 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266877E+09 | 55025362.22 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173845E+09 | 62850036.15 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100311E+09 | 61475715.25 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35662318.57 | 68099514.03 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19707338.32 | 94753381.84 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193670E+10 | 0.778810E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19707338.32 | 46312441.74 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333607E+09 | 94753381.84 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22169498.07 | 93879218.72 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54430333.61 | 75073379.69 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125311E+09 | 64734387.76 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211962E+09 | 51335454.11 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.288207E+09 | 52674962.26 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304606E+09 | 46312441.74 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333607E+09 | 52595845.01 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266877E+09 | 55025362.22 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173845E+09 | 62850036.15 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100311E+09 | 61475715.25 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35662318.57 | 68099514.03 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19707338.32 | 94753381.84 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193670E+10 | 0.778810E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19707338.32 | 46312441.74 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333607E+09 | 94753381.84 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22169498.07 | 93879218.72 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54430333.61 | 75073379.69 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125311E+09 | 64734387.76 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211962E+09 | 51335454.11 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.288207E+09 | 52674962.26 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304606E+09 | 46312441.74 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333607E+09 | 52595845.01 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266877E+09 | 55025362.22 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173845E+09 | 62850036.15 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100311E+09 | 61475715.25 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35662318.57 | 68099514.03 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19707338.32 | 94753381.84 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193670E+10 | 0.778810E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19707338.32 | 46312441.74 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333607E+09 | 94753381.84 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22169498.07 | 93879218.72 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54430333.61 | 75073379.69 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125311E+09 | 64734387.76 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211962E+09 | 51335454.11 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.288207E+09 | 52674962.26 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304606E+09 | 46312441.74 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333607E+09 | 52595845.01 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266877E+09 | 55025362.22 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173845E+09 | 62850036.15 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100311E+09 | 61475715.25 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35662318.57 | 68099514.03 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19707338.32 | 94753381.84 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193670E+10 | 0.778810E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19707338.32 | 46312441.74 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333607E+09 | 94753381.84 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22169498.07 | 93879218.72 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54430333.61 | 75073379.69 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125311E+09 | 64734387.76 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211962E+09 | 51335454.11 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.288207E+09 | 52674962.26 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304606E+09 | 46312441.74 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333607E+09 | 52595845.01 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266877E+09 | 55025362.22 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173845E+09 | 62850036.15 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100311E+09 | 61475715.25 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35662318.57 | 68099514.03 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19707338.32 | 94753381.84 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193670E+10 | 0.778810E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19707338.32 | 46312441.74 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333607E+09 | 94753381.84 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22169498.07 | 93879218.72 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54430333.61 | 75073379.69 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125311E+09 | 64734387.76 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211962E+09 | 51335454.11 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.288207E+09 | 52674962.26 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304606E+09 | 46312441.74 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333607E+09 | 52595845.01 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266877E+09 | 55025362.22 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173845E+09 | 62850036.15 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100311E+09 | 61475715.25 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35662318.57 | 68099514.03 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19707338.32 | 94753381.84 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193670E+10 | 0.778810E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19707338.32 | 46312441.74 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333607E+09 | 94753381.84 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22169498.07 | 93879218.72 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54430333.61 | 75073379.69 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125311E+09 | 64734387.76 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211962E+09 | 51335454.11 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.288207E+09 | 52674962.26 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304606E+09 | 46312441.74 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333607E+09 | 52595845.01 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266877E+09 | 55025362.22 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173845E+09 | 62850036.15 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100311E+09 | 61475715.25 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35662318.57 | 68099514.03 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19707338.32 | 94753381.84 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193670E+10 | 0.778810E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19707338.32 | 46312441.74 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333607E+09 | 94753381.84 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22169498.07 | 93879218.72 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54430333.61 | 75073379.69 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125311E+09 | 64734387.76 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211962E+09 | 51335454.11 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.288207E+09 | 52674962.26 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304606E+09 | 46312441.74 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333607E+09 | 52595845.01 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266877E+09 | 55025362.22 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173845E+09 | 62850036.15 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100311E+09 | 61475715.25 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35662318.57 | 68099514.03 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19707338.32 | 94753381.84 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193670E+10 | 0.778810E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19707338.32 | 46312441.74 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333607E+09 | 94753381.84 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22169498.07 | 93879218.72 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54430333.61 | 75073379.69 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125311E+09 | 64734387.76 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211962E+09 | 51335454.11 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.288207E+09 | 52674962.26 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304606E+09 | 46312441.74 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333607E+09 | 52595845.01 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266877E+09 | 55025362.22 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173845E+09 | 62850036.15 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100311E+09 | 61475715.25 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35662318.57 | 68099514.03 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19707338.32 | 94753381.84 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193670E+10 | 0.778810E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19707338.32 | 46312441.74 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333607E+09 | 94753381.84 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51252448.27 | 79966200.81 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98972534.28 | 66098350.82 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200191E+09 | 62442718.77 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319677E+09 | 56273220.99 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.422097E+09 | 66152964.73 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444202E+09 | 59043972.13 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483223E+09 | 69136053.97 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385763E+09 | 75700643.33 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256956E+09 | 81903388.15 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155405E+09 | 71362727.95 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67240352.10 | 59553189.55 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45304296.28 | 79688001.15 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.293028E+10 | 0.827321E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45304296.28 | 56273220.99 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483223E+09 | 81903388.15 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 35.81 | 298.20 | 93.85 | 20.75 | 73.10 | 0.00 | 0.00 |
February | 115.97 | 252.66 | 161.45 | 46.25 | 115.20 | 0.00 | 0.00 |
March | 208.84 | 192.75 | 229.84 | 59.10 | 170.74 | 0.00 | 0.00 |
April | 375.89 | 151.91 | 343.37 | 101.70 | 241.67 | 0.00 | 0.00 |
May | 508.11 | 143.97 | 442.45 | 142.22 | 300.23 | 0.00 | 0.00 |
June | 498.30 | 122.06 | 434.43 | 134.80 | 299.64 | 0.00 | 0.00 |
July | 618.79 | 128.79 | 507.53 | 222.40 | 285.13 | 0.00 | 0.00 |
August | 514.38 | 132.93 | 417.65 | 174.07 | 243.57 | 0.00 | 0.00 |
September | 382.52 | 171.19 | 337.84 | 132.33 | 205.51 | 0.00 | 0.00 |
October | 194.29 | 180.05 | 199.64 | 64.06 | 135.58 | 0.00 | 0.00 |
November | 62.96 | 225.04 | 105.03 | 22.20 | 82.84 | 0.00 | 0.00 |
December | 42.24 | 299.53 | 86.46 | 23.19 | 63.27 | 0.00 | 0.00 |
Annual Sum or Average | 297.63 | 191.35 | 280.66 | 95.63 | 185.03 | 0.00 | 0.00 |
Minimum of Months | 35.81 | 122.06 | 86.46 | 20.75 | 63.27 | 0.00 | 0.00 |
Maximum of Months | 618.79 | 299.53 | 507.53 | 222.40 | 300.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 115.88 | 490.71 | 196.60 | 38.39 | 158.20 | 0.00 | 0.00 |
February | 314.99 | 434.45 | 351.74 | 116.87 | 234.87 | 0.00 | 0.00 |
March | 655.00 | 338.37 | 615.68 | 264.15 | 351.53 | 0.00 | 0.00 |
April | 1144.86 | 277.27 | 980.32 | 499.10 | 481.22 | 0.00 | 0.00 |
May | 1506.46 | 275.33 | 1273.99 | 657.32 | 616.68 | 0.00 | 0.00 |
June | 1645.25 | 250.14 | 1396.10 | 819.39 | 576.70 | 0.00 | 0.00 |
July | 1743.76 | 274.92 | 1456.29 | 961.54 | 494.75 | 0.00 | 0.00 |
August | 1394.97 | 287.62 | 1167.46 | 742.71 | 424.76 | 0.00 | 0.00 |
September | 938.98 | 339.47 | 820.78 | 455.74 | 365.04 | 0.00 | 0.00 |
October | 524.33 | 321.33 | 484.68 | 226.31 | 258.38 | 0.00 | 0.00 |
November | 192.62 | 367.82 | 236.17 | 57.81 | 178.36 | 0.00 | 0.00 |
December | 103.01 | 495.28 | 169.84 | 40.94 | 128.90 | 0.00 | 0.00 |
Annual Sum or Average | 859.77 | 345.74 | 764.80 | 408.51 | 356.29 | 0.00 | 0.00 |
Minimum of Months | 103.01 | 250.14 | 169.84 | 38.39 | 128.90 | 0.00 | 0.00 |
Maximum of Months | 1743.76 | 495.28 | 1456.29 | 961.54 | 616.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2897.10 | 5866.94 | 646.27 | 145.05 | 501.21 | 0.00 | 0.00 |
February | 5830.09 | 5447.12 | 1153.41 | 409.31 | 744.10 | 0.00 | 0.00 |
March | 9584.95 | 3919.09 | 1965.88 | 852.18 | 1113.69 | 0.00 | 0.00 |
April | 15557.68 | 2811.85 | 3096.42 | 1571.85 | 1524.57 | 0.00 | 0.00 |
May | 20668.71 | 2466.99 | 3997.61 | 2043.89 | 1953.72 | 0.00 | 0.00 |
June | 21759.17 | 2203.34 | 4365.33 | 2538.25 | 1827.08 | 0.00 | 0.00 |
July | 22206.11 | 2499.62 | 4555.48 | 2988.04 | 1567.44 | 0.00 | 0.00 |
August | 17675.30 | 2781.28 | 3674.85 | 2329.16 | 1345.69 | 0.00 | 0.00 |
September | 12590.62 | 3087.38 | 2614.31 | 1457.82 | 1156.49 | 0.00 | 0.00 |
October | 7409.79 | 3113.67 | 1567.00 | 748.43 | 818.57 | 0.00 | 0.00 |
November | 3390.95 | 3824.17 | 771.73 | 206.65 | 565.08 | 0.00 | 0.00 |
December | 2377.55 | 5515.33 | 564.30 | 155.91 | 408.39 | 0.00 | 0.00 |
Annual Sum or Average | 11861.92 | 3620.20 | 2421.49 | 1292.71 | 1128.77 | 0.00 | 0.00 |
Minimum of Months | 2377.55 | 2203.34 | 564.30 | 145.05 | 408.39 | 0.00 | 0.00 |
Maximum of Months | 22206.11 | 5866.94 | 4555.48 | 2988.04 | 1953.72 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 95910360.68 | 0.798707E+09 | 0.251368E+09 | 55588881.50 | 0.195779E+09 | 0.00 | 0.00 |
February | 0.280545E+09 | 0.611235E+09 | 0.390583E+09 | 0.111899E+09 | 0.278684E+09 | 0.00 | 0.00 |
March | 0.559347E+09 | 0.516253E+09 | 0.615609E+09 | 0.158297E+09 | 0.457312E+09 | 0.00 | 0.00 |
April | 0.974298E+09 | 0.393747E+09 | 0.890019E+09 | 0.263599E+09 | 0.626419E+09 | 0.00 | 0.00 |
May | 0.136092E+10 | 0.385605E+09 | 0.118506E+10 | 0.380934E+09 | 0.804127E+09 | 0.00 | 0.00 |
June | 0.129160E+10 | 0.316385E+09 | 0.112605E+10 | 0.349392E+09 | 0.776662E+09 | 0.00 | 0.00 |
July | 0.165736E+10 | 0.344952E+09 | 0.135936E+10 | 0.595677E+09 | 0.763682E+09 | 0.00 | 0.00 |
August | 0.137771E+10 | 0.356039E+09 | 0.111862E+10 | 0.466238E+09 | 0.652384E+09 | 0.00 | 0.00 |
September | 0.991502E+09 | 0.443715E+09 | 0.875673E+09 | 0.342997E+09 | 0.532676E+09 | 0.00 | 0.00 |
October | 0.520395E+09 | 0.482247E+09 | 0.534721E+09 | 0.171585E+09 | 0.363135E+09 | 0.00 | 0.00 |
November | 0.163190E+09 | 0.583309E+09 | 0.272247E+09 | 57531799.00 | 0.214715E+09 | 0.00 | 0.00 |
December | 0.113138E+09 | 0.802263E+09 | 0.231567E+09 | 62106999.08 | 0.169460E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.938591E+10 | 0.603446E+10 | 0.885088E+10 | 0.301585E+10 | 0.583503E+10 | 0.00 | 0.00 |
Minimum of Months | 95910360.68 | 0.316385E+09 | 0.231567E+09 | 55588881.50 | 0.169460E+09 | 0.00 | 0.00 |
Maximum of Months | 0.165736E+10 | 0.802263E+09 | 0.135936E+10 | 0.595677E+09 | 0.804127E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.310373E+09 | 0.131431E+10 | 0.526570E+09 | 0.102834E+09 | 0.423736E+09 | 0.00 | 0.00 |
February | 0.762025E+09 | 0.105103E+10 | 0.850921E+09 | 0.282724E+09 | 0.568197E+09 | 0.00 | 0.00 |
March | 0.175436E+10 | 0.906281E+09 | 0.164904E+10 | 0.707505E+09 | 0.941537E+09 | 0.00 | 0.00 |
April | 0.296747E+10 | 0.718696E+09 | 0.254100E+10 | 0.129367E+10 | 0.124732E+10 | 0.00 | 0.00 |
May | 0.403490E+10 | 0.737449E+09 | 0.341227E+10 | 0.176055E+10 | 0.165171E+10 | 0.00 | 0.00 |
June | 0.426449E+10 | 0.648374E+09 | 0.361868E+10 | 0.212386E+10 | 0.149482E+10 | 0.00 | 0.00 |
July | 0.467049E+10 | 0.736342E+09 | 0.390053E+10 | 0.257539E+10 | 0.132514E+10 | 0.00 | 0.00 |
August | 0.373628E+10 | 0.770355E+09 | 0.312694E+10 | 0.198926E+10 | 0.113767E+10 | 0.00 | 0.00 |
September | 0.243383E+10 | 0.879901E+09 | 0.212746E+10 | 0.118128E+10 | 0.946181E+09 | 0.00 | 0.00 |
October | 0.140435E+10 | 0.860660E+09 | 0.129818E+10 | 0.606139E+09 | 0.692037E+09 | 0.00 | 0.00 |
November | 0.499272E+09 | 0.953393E+09 | 0.612152E+09 | 0.149835E+09 | 0.462316E+09 | 0.00 | 0.00 |
December | 0.275903E+09 | 0.132655E+10 | 0.454910E+09 | 0.109651E+09 | 0.345259E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.271137E+11 | 0.109033E+11 | 0.241186E+11 | 0.128827E+11 | 0.112359E+11 | 0.00 | 0.00 |
Minimum of Months | 0.275903E+09 | 0.648374E+09 | 0.454910E+09 | 0.102834E+09 | 0.345259E+09 | 0.00 | 0.00 |
Maximum of Months | 0.467049E+10 | 0.132655E+10 | 0.390053E+10 | 0.257539E+10 | 0.165171E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.775958E+10 | 0.157140E+11 | 0.173096E+10 | 0.388510E+09 | 0.134245E+10 | 0.00 | 0.00 |
February | 0.141042E+11 | 0.131777E+11 | 0.279033E+10 | 0.990206E+09 | 0.180013E+10 | 0.00 | 0.00 |
March | 0.256723E+11 | 0.104969E+11 | 0.526541E+10 | 0.228249E+10 | 0.298292E+10 | 0.00 | 0.00 |
April | 0.403255E+11 | 0.728833E+10 | 0.802592E+10 | 0.407423E+10 | 0.395169E+10 | 0.00 | 0.00 |
May | 0.553591E+11 | 0.660758E+10 | 0.107072E+11 | 0.547435E+10 | 0.523285E+10 | 0.00 | 0.00 |
June | 0.563998E+11 | 0.571106E+10 | 0.113149E+11 | 0.657915E+10 | 0.473579E+10 | 0.00 | 0.00 |
July | 0.594769E+11 | 0.669498E+10 | 0.122014E+11 | 0.800316E+10 | 0.419823E+10 | 0.00 | 0.00 |
August | 0.473415E+11 | 0.744939E+10 | 0.984273E+10 | 0.623842E+10 | 0.360430E+10 | 0.00 | 0.00 |
September | 0.326349E+11 | 0.800249E+10 | 0.677630E+10 | 0.377867E+10 | 0.299763E+10 | 0.00 | 0.00 |
October | 0.198464E+11 | 0.833964E+10 | 0.419706E+10 | 0.200459E+10 | 0.219247E+10 | 0.00 | 0.00 |
November | 0.878935E+10 | 0.991224E+10 | 0.200033E+10 | 0.535644E+09 | 0.146468E+10 | 0.00 | 0.00 |
December | 0.636803E+10 | 0.147723E+11 | 0.151142E+10 | 0.417595E+09 | 0.109383E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.374077E+12 | 0.114167E+12 | 0.763640E+11 | 0.407670E+11 | 0.355970E+11 | 0.00 | 0.00 |
Minimum of Months | 0.636803E+10 | 0.571106E+10 | 0.151142E+10 | 0.388510E+09 | 0.109383E+10 | 0.00 | 0.00 |
Maximum of Months | 0.594769E+11 | 0.157140E+11 | 0.122014E+11 | 0.800316E+10 | 0.523285E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.936528E+09 | -848750825.0 | 0.00 | 0.00 | 744.00 | 0.00 | -87777174.7 | 58.99 | 0.00 | 0.00 |
February | 0.864016E+09 | -785126754.5 | 0.00 | 0.00 | 672.00 | 0.00 | -78888801.9 | 58.99 | 0.00 | 0.00 |
March | 0.993545E+09 | -907218067.1 | 0.00 | 0.00 | 744.00 | 0.00 | -86327224.5 | 58.99 | 0.00 | 0.00 |
April | 0.901488E+09 | -819656574.2 | 0.00 | 0.00 | 720.00 | 0.00 | -81830945.0 | 58.99 | 0.00 | 0.00 |
May | 0.901136E+09 | -820653554.7 | 0.00 | 0.00 | 744.00 | 0.00 | -80482877.4 | 58.99 | 0.00 | 0.00 |
June | 0.861593E+09 | -786766496.9 | 0.00 | 0.00 | 720.00 | 0.00 | -74826068.9 | 58.99 | 0.00 | 0.00 |
July | 0.813747E+09 | -739276567.9 | 0.00 | 0.00 | 744.00 | 0.00 | -74470871.3 | 58.99 | 0.00 | 0.00 |
August | 0.861344E+09 | -787240301.9 | 0.00 | 0.00 | 744.00 | 0.00 | -74103250.1 | 58.99 | 0.00 | 0.00 |
September | 0.816008E+09 | -741745060.1 | 0.00 | 0.00 | 720.00 | 0.00 | -74262972.1 | 58.99 | 0.00 | 0.00 |
October | 0.850809E+09 | -767149691.2 | 0.00 | 0.00 | 744.00 | 0.00 | -83658972.8 | 58.99 | 0.00 | 0.00 |
November | 0.849969E+09 | -766216818.6 | 0.00 | 0.00 | 720.00 | 0.00 | -83751773.0 | 58.99 | 0.00 | 0.00 |
December | 0.914692E+09 | -827207072.8 | 0.00 | 0.00 | 744.00 | 0.00 | -87484484.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.105649E+11 | -0.959701E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -967865416.3 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.813747E+09 | -907218067.1 | 0.00 | 0.00 | 672.00 | 0.00 | -87777174.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.993545E+09 | -739276567.9 | 0.00 | 0.00 | 744.00 | 0.00 | -74103250.1 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.88 | 0.70 | 31-JAN-12:30 | 91.08 | 0.00 | 0.00 | 0.00 | 68.92 | 0.00 | 0.00 | 0.00 |
February | 259.50 | 0.83 | 0.50 | 26-FEB-11:20 | 116.76 | 0.00 | 0.00 | 0.00 | 279.16 | 0.00 | 0.00 | 20.33 |
March | 247.00 | 0.77 | 0.50 | 06-MAR-11:30 | 164.45 | 0.00 | 0.00 | 18.33 | 187.92 | 0.00 | 0.00 | 5.17 |
April | 379.50 | 0.73 | 0.50 | 02-APR-10:00 | 192.86 | 0.00 | 0.00 | 66.00 | 150.66 | 0.00 | 0.00 | 17.17 |
May | 427.83 | 0.71 | 0.50 | 01-MAY-10:20 | 234.12 | 0.00 | 0.00 | 120.17 | 180.85 | 0.00 | 0.00 | 66.00 |
June | 375.17 | 0.71 | 0.50 | 01-JUN-10:30 | 212.49 | 0.00 | 0.00 | 102.17 | 736.24 | 0.00 | 0.00 | 74.83 |
July | 471.00 | 0.76 | 0.50 | 01-JUL-11:39 | 182.49 | 0.00 | 0.00 | 87.33 | 143.10 | 0.00 | 0.00 | 45.33 |
August | 366.67 | 0.77 | 0.50 | 02-AUG-10:09 | 258.12 | 0.00 | 0.00 | 51.67 | 132.32 | 0.00 | 0.00 | 17.33 |
September | 301.17 | 0.75 | 0.50 | 01-SEP-12:09 | 791.88 | 0.00 | 0.00 | 40.17 | 135.74 | 0.00 | 0.00 | 4.00 |
October | 245.33 | 0.82 | 0.50 | 01-OCT-12:30 | 124.55 | 0.00 | 0.00 | 1.00 | 101.17 | 0.00 | 0.00 | 0.00 |
November | 242.67 | 0.86 | 0.70 | 19-NOV-11:30 | 100.10 | 0.00 | 0.00 | 0.00 | 75.51 | 0.00 | 0.00 | 0.00 |
December | 160.33 | 0.89 | 0.71 | 10-DEC-12:30 | 77.57 | 0.00 | 0.00 | 0.00 | 61.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | 0.78 | 224.02 | 0.00 | 0.00 | 486.83 | 203.51 | 0.00 | 0.00 | 250.17 | ||
Minimum of Months | 160.33 | 0.71 | 0.50 | 77.57 | 0.00 | 0.00 | 0.00 | 61.54 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 471.00 | 0.89 | 0.71 | 791.88 | 0.00 | 0.00 | 120.17 | 736.24 | 0.00 | 0.00 | 74.83 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.69 | 0.50 | 02-JAN-10:00 | 147.31 | 10.88 | 0.00 | 42.00 | 121.97 | 13.89 | 0.00 | 15.00 |
February | 259.50 | 0.64 | 0.50 | 01-FEB-11:09 | 190.84 | 12.23 | 0.00 | 104.17 | 157.57 | 15.51 | 5.33 | 71.33 |
March | 247.00 | 0.60 | 0.50 | 01-MAR-09:50 | 757.52 | 14.69 | 14.50 | 194.67 | 733.25 | 17.23 | 45.00 | 151.50 |
April | 379.50 | 0.59 | 0.50 | 01-APR-08:09 | 567.28 | 14.84 | 17.33 | 256.33 | 542.92 | 17.70 | 92.67 | 211.83 |
May | 427.83 | 0.58 | 0.50 | 01-MAY-07:19 | 1219.09 | 16.14 | 39.67 | 313.50 | 311.49 | 17.98 | 99.17 | 258.00 |
June | 375.17 | 0.58 | 0.50 | 01-JUN-07:19 | 346.87 | 14.22 | 2.33 | 307.50 | 545.61 | 19.27 | 111.33 | 277.17 |
July | 471.00 | 0.62 | 0.50 | 01-JUL-06:10 | 294.22 | 12.56 | 2.33 | 264.00 | 1072.67 | 17.97 | 98.17 | 231.33 |
August | 366.67 | 0.61 | 0.50 | 01-AUG-06:19 | 272.07 | 13.07 | 0.33 | 259.83 | 542.18 | 17.52 | 75.83 | 211.50 |
September | 301.17 | 0.59 | 0.50 | 01-SEP-07:49 | 278.42 | 13.72 | 0.00 | 216.83 | 224.01 | 17.41 | 50.00 | 164.17 |
October | 245.33 | 0.63 | 0.50 | 01-OCT-08:30 | 207.76 | 12.37 | 0.00 | 146.17 | 545.00 | 17.58 | 38.83 | 102.17 |
November | 242.67 | 0.66 | 0.50 | 01-NOV-10:09 | 161.65 | 11.52 | 0.00 | 65.50 | 134.07 | 14.58 | 0.00 | 26.67 |
December | 160.33 | 0.72 | 0.50 | 01-DEC-10:20 | 129.85 | 10.56 | 0.00 | 15.83 | 106.81 | 13.92 | 0.00 | 4.33 |
Annual Sum or Average | 3714.00 | 0.62 | 423.22 | 13.36 | 76.50 | 2186.33 | 471.16 | 17.08 | 616.33 | 1725.00 | ||
Minimum of Months | 160.33 | 0.58 | 0.50 | 129.85 | 10.56 | 0.00 | 15.83 | 106.81 | 13.89 | 0.00 | 4.33 | |
Maximum of Months | 471.00 | 0.72 | 0.50 | 1219.09 | 16.14 | 39.67 | 313.50 | 1072.67 | 19.27 | 111.33 | 277.17 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.87 | 0.66 | 20-JAN-15:30 | 148.78 | 20.67 | 61.17 | 7.17 | 71.34 | 18.60 | 27.50 | 0.00 |
February | 259.50 | 0.83 | 0.61 | 19-FEB-15:30 | 289.57 | 22.88 | 115.50 | 25.17 | 100.07 | 20.03 | 84.50 | 0.00 |
March | 247.00 | 0.77 | 0.61 | 01-MAR-15:20 | 343.01 | 23.46 | 134.33 | 59.50 | 225.63 | 23.55 | 148.50 | 23.33 |
April | 379.50 | 0.76 | 0.61 | 01-APR-14:30 | 293.29 | 21.58 | 188.67 | 86.17 | 369.35 | 23.47 | 229.17 | 56.83 |
May | 427.83 | 0.74 | 0.61 | 02-MAY-14:09 | 301.82 | 21.10 | 216.83 | 123.33 | 305.60 | 22.15 | 261.83 | 79.17 |
June | 375.17 | 0.74 | 0.61 | 01-JUN-14:09 | 297.89 | 21.05 | 200.00 | 96.17 | 342.01 | 22.20 | 266.33 | 71.00 |
July | 471.00 | 0.76 | 0.61 | 01-JUL-13:39 | 261.96 | 19.87 | 186.00 | 103.00 | 409.69 | 21.12 | 239.00 | 95.17 |
August | 366.67 | 0.76 | 0.61 | 02-AUG-14:09 | 285.83 | 21.04 | 175.50 | 78.50 | 357.64 | 22.10 | 212.00 | 68.50 |
September | 301.17 | 0.74 | 0.61 | 01-SEP-14:50 | 471.10 | 24.26 | 172.00 | 97.83 | 390.44 | 24.71 | 190.67 | 64.17 |
October | 245.33 | 0.79 | 0.61 | 01-OCT-15:09 | 296.41 | 23.38 | 132.33 | 41.17 | 149.03 | 21.62 | 125.50 | 7.33 |
November | 242.67 | 0.87 | 0.65 | 04-NOV-15:30 | 152.16 | 19.73 | 53.33 | 5.00 | 77.02 | 18.98 | 40.33 | 0.00 |
December | 160.33 | 0.87 | 0.66 | 06-DEC-14:30 | 137.46 | 19.17 | 42.00 | 0.00 | 74.17 | 19.02 | 20.67 | 0.00 |
Annual Sum or Average | 3714.00 | 0.78 | 282.50 | 21.47 | 1677.67 | 723.00 | 271.06 | 21.70 | 1846.00 | 465.50 | ||
Minimum of Months | 160.33 | 0.74 | 0.61 | 137.46 | 19.17 | 42.00 | 0.00 | 71.34 | 18.60 | 20.67 | 0.00 | |
Maximum of Months | 471.00 | 0.87 | 0.66 | 471.10 | 24.26 | 216.83 | 123.33 | 409.69 | 24.71 | 266.33 | 95.17 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.617340E+10 | 23847.66 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.487802E+10 | 23847.66 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.392956E+10 | 23847.66 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.220328E+10 | 23847.66 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.437007E+09 | 23847.66 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 84109978.63 | 23847.66 | 07-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 47183763.02 | 23847.66 | 28-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158629E+10 | 23847.66 | 02-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.372003E+10 | 23847.66 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.527655E+10 | 23847.66 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.283354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.617340E+10 | 23847.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.201600E+11 | 62154.48 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142358E+11 | 62154.48 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.678498E+10 | 62154.48 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.184098E+10 | 62154.48 | 07-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.883253E+09 | 62154.48 | 24-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.870547E+10 | 62154.48 | 30-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168850E+11 | 62154.48 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.694956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.201600E+11 | 62154.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.405972E+11 | 54071.77 | 15-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.265873E+11 | 74979.97 | 19-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145015E+09 | 7550.64 | 05-MAR-06:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.554670E+10 | 27731.16 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.290221E+11 | 40820.13 | 25-DEC-01:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101898E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.405972E+11 | 74979.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 74446185.45 | 70991246.21 | 3948.47 | 27-APR-16:00 | 3656.38 | 0.00 |
May | 0.00 | 0.00 | 0.234975E+09 | 0.213610E+09 | 4390.01 | 06-MAY-15:00 | 3651.31 | 0.00 |
June | 0.00 | 0.00 | 0.560873E+09 | 0.544357E+09 | 6541.84 | 28-JUN-16:00 | 6306.95 | 0.00 |
July | 0.00 | 0.00 | 0.197891E+10 | 0.173166E+10 | 15466.25 | 31-JUL-05:55 | 10704.83 | 0.00 |
August | 0.00 | 0.00 | 0.293633E+10 | 0.254822E+10 | 15653.89 | 25-AUG-05:03 | 10262.10 | 0.00 |
September | 0.00 | 0.00 | 0.637304E+09 | 0.534945E+09 | 6863.46 | 14-SEP-16:00 | 5962.91 | 0.00 |
October | 0.00 | 0.00 | 5556338.93 | 5556336.59 | 1074.54 | 04-OCT-15:00 | 1074.54 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.642839E+10 | 0.564934E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.293633E+10 | 0.254822E+10 | 15653.89 | 10704.83 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 23097984.63 | 22613766.13 | 2635.71 | 28-JUN-15:00 | 2635.71 | 0.00 |
July | 0.00 | 0.00 | 0.918095E+09 | 0.795544E+09 | 39756.15 | 31-JUL-18:02 | 33177.66 | 0.00 |
August | 0.00 | 0.00 | 0.188232E+10 | 0.163310E+10 | 39758.31 | 13-AUG-13:35 | 33654.23 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.282351E+10 | 0.245126E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.188232E+10 | 0.163310E+10 | 39758.31 | 33654.23 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.445482E+09 | 0.06 | 228.09 | 01-JAN-00:03 | 0.08 |
February | 0.283927E+09 | 0.04 | 228.09 | 01-FEB-00:05 | 0.08 |
March | 7216907.99 | 0.00 | 228.09 | 05-MAR-02:43 | 0.08 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.141784E+09 | 0.02 | 228.09 | 13-NOV-00:30 | 0.08 |
December | 0.412976E+09 | 0.05 | 228.09 | 01-DEC-00:05 | 0.08 |
Annual Sum or Average | 0.129139E+10 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.445482E+09 | 0.06 | 228.09 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.106088E+10 | 0.45 | 1015.22 | 02-JAN-08:00 | 0.92 |
February | 0.971953E+09 | 0.44 | 1015.22 | 01-FEB-07:30 | 0.92 |
March | 0.112041E+10 | 0.40 | 1015.22 | 04-MAR-12:00 | 0.92 |
April | 0.102947E+10 | 0.38 | 1015.22 | 01-APR-06:30 | 0.92 |
May | 0.105448E+10 | 0.37 | 1015.22 | 03-MAY-06:50 | 0.92 |
June | 0.104717E+10 | 0.37 | 1015.22 | 03-JUN-13:10 | 0.92 |
July | 0.100747E+10 | 0.34 | 1015.22 | 01-JUL-06:30 | 0.92 |
August | 0.109019E+10 | 0.37 | 1015.22 | 01-AUG-15:30 | 0.91 |
September | 0.100610E+10 | 0.35 | 1015.22 | 02-SEP-14:00 | 0.91 |
October | 0.102336E+10 | 0.36 | 1015.22 | 02-OCT-15:20 | 0.92 |
November | 0.993027E+09 | 0.36 | 1015.22 | 01-NOV-15:10 | 0.91 |
December | 0.104383E+10 | 0.39 | 1015.22 | 01-DEC-07:10 | 0.92 |
Annual Sum or Average | 0.124483E+11 | 0.38 | |||
Minimum of Months | 0.971953E+09 | 0.34 | 1015.22 | 0.91 | |
Maximum of Months | 0.112041E+10 | 0.45 | 1015.22 | 0.92 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.129886E+10 | 0.56 | 1913.78 | 02-JAN-06:01 | 0.89 |
February | 0.108579E+10 | 0.51 | 1913.78 | 06-FEB-06:01 | 0.89 |
March | 0.101023E+10 | 0.43 | 1913.78 | 06-MAR-06:01 | 0.89 |
April | 0.810537E+09 | 0.27 | 1913.78 | 07-APR-05:01 | 0.89 |
May | 0.788172E+09 | 0.21 | 765.51 | 01-MAY-06:10 | 0.54 |
June | 0.788172E+09 | 0.21 | 765.51 | 01-JUN-06:05 | 0.54 |
July | 0.763374E+09 | 0.20 | 1601.09 | 24-JUL-17:20 | 0.81 |
August | 0.826271E+09 | 0.22 | 1913.78 | 10-AUG-17:10 | 0.88 |
September | 0.757858E+09 | 0.20 | 765.51 | 01-SEP-06:10 | 0.53 |
October | 0.782970E+09 | 0.23 | 1913.78 | 24-OCT-05:01 | 0.89 |
November | 0.967957E+09 | 0.44 | 1913.78 | 30-NOV-06:01 | 0.89 |
December | 0.121420E+10 | 0.56 | 1913.78 | 01-DEC-06:01 | 0.89 |
Annual Sum or Average | 0.110944E+11 | 0.34 | |||
Minimum of Months | 0.757858E+09 | 0.20 | 765.51 | 0.53 | |
Maximum of Months | 0.129886E+10 | 0.56 | 1913.78 | 0.89 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.106088E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.971953E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.112041E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.104588E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.110378E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.116442E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.141415E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.169664E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.113695E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.102459E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.993027E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.104383E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.137765E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.971953E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.169664E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.129886E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.108579E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.101023E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.810537E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.788172E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.794198E+09 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.989697E+09 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.129650E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.757858E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.782970E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.967957E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.121420E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.117970E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.757858E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.129886E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.106088E+10 | 0.00 | 0.617340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.971953E+09 | 0.00 | 0.487802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112041E+10 | 0.00 | 0.392956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102947E+10 | 74446185.45 | 0.220328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.105448E+10 | 0.234975E+09 | 0.437007E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104717E+10 | 0.560873E+09 | 84109978.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.100747E+10 | 0.197891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109019E+10 | 0.293633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100610E+10 | 0.637304E+09 | 47183763.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.102336E+10 | 5556338.93 | 0.158629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.993027E+09 | 0.00 | 0.372003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104383E+10 | 0.00 | 0.527655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.124483E+11 | 0.642839E+10 | 0.283354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.971953E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.112041E+10 | 0.293633E+10 | 0.617340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.129886E+10 | 0.00 | 0.201600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108579E+10 | 0.00 | 0.142358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101023E+10 | 0.00 | 0.678498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.810537E+09 | 0.00 | 0.184098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.788172E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.788172E+09 | 23097984.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.763374E+09 | 0.892946E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.826271E+09 | 0.185105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.757858E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.782970E+09 | 0.00 | 0.883253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.967957E+09 | 0.00 | 0.870547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121420E+10 | 0.00 | 0.168850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110944E+11 | 0.276710E+10 | 0.694956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.757858E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129886E+10 | 0.185105E+10 | 0.201600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.106088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.971953E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102947E+10 | 0.00 | 0.00 | 0.00 | 16413027.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.105448E+10 | 0.00 | 0.00 | 0.00 | 49308174.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104717E+10 | 0.00 | 0.00 | 0.00 | 0.117258E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.100747E+10 | 0.00 | 0.00 | 0.00 | 0.406685E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109019E+10 | 0.00 | 0.00 | 0.00 | 0.606452E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100610E+10 | 0.00 | 0.00 | 0.00 | 0.130855E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.102336E+10 | 0.00 | 0.00 | 0.00 | 1224063.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.993027E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.124483E+11 | 0.00 | 0.00 | 0.00 | 0.132820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.971953E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.112041E+10 | 0.00 | 0.00 | 0.00 | 0.606452E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.129886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.810537E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.788172E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.788172E+09 | 0.00 | 0.00 | 0.00 | 6025409.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.763374E+09 | 0.00 | 0.00 | 0.00 | 0.226323E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.826271E+09 | 0.00 | 0.00 | 0.00 | 0.470229E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.757858E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.782970E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.967957E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110944E+11 | 0.00 | 0.00 | 0.00 | 0.702577E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.757858E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129886E+10 | 0.00 | 0.00 | 0.00 | 0.470229E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194786E+10 | 0.00 | 0.00 | 0.12 |
February | 24652087.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158605E+10 | 0.00 | 0.00 | 0.13 |
March | 0.102361E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149807E+10 | 0.00 | 0.00 | 0.13 |
April | 0.315678E+09 | 3112764.54 | 0.00 | 51156.20 | 0.00 | 0.883277E+09 | 79707126.84 | 0.00 | 0.14 |
May | 0.881250E+09 | 3094092.69 | 0.00 | 506583.24 | 0.00 | 63550890.53 | 0.531895E+09 | 0.00 | 0.23 |
June | 0.389975E+09 | 3739908.85 | 0.00 | 1986355.09 | 0.00 | 0.00 | 0.175988E+10 | 0.00 | 0.41 |
July | 31476874.98 | 47128067.37 | 0.00 | 3709262.99 | 0.00 | 0.00 | 0.233549E+10 | 0.00 | 0.58 |
August | 19374659.18 | 0.118684E+09 | 0.00 | 3512115.83 | 0.00 | 0.00 | 0.223635E+10 | 0.00 | 0.56 |
September | 0.371362E+09 | 3709390.35 | 0.00 | 2095039.32 | 0.00 | 830480.24 | 0.179825E+10 | 0.00 | 0.41 |
October | 0.515122E+09 | 0.00 | 0.00 | 80829.99 | 0.00 | 0.667428E+09 | 0.164817E+09 | 0.00 | 0.14 |
November | 40853327.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146846E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185084E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.269211E+10 | 0.179468E+09 | 0.00 | 11941342.67 | 0.00 | 0.996636E+10 | 0.890639E+10 | 0.00 | 0.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.881250E+09 | 0.118684E+09 | 0.00 | 3709262.99 | 0.00 | 0.194786E+10 | 0.233549E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.124099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371897E+10 | 0.00 | 0.00 | 0.17 |
February | 0.174139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219180E+10 | 0.00 | 0.00 | 0.18 |
March | 0.311342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552109E+09 | 0.00 | 0.00 | 0.19 |
April | 0.283716E+10 | 0.00 | 0.00 | 0.00 | 46840621.41 | 78595550.10 | 0.00 | 0.00 | 0.18 |
May | 0.342763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
June | 0.349826E+10 | 0.00 | 0.00 | 42812.07 | 0.00 | 0.00 | 44236475.58 | 0.00 | 0.19 |
July | 0.278867E+10 | 18222572.22 | 0.00 | 984475.35 | 0.00 | 0.00 | 0.615605E+09 | 0.00 | 0.20 |
August | 0.267831E+10 | 55507098.72 | 0.00 | 1440886.35 | 0.00 | 0.00 | 0.568590E+09 | 0.00 | 0.22 |
September | 0.360858E+10 | 0.00 | 0.00 | 21667.92 | 0.00 | 0.00 | 52059476.90 | 0.00 | 0.18 |
October | 0.295616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51933375.75 | 0.00 | 0.00 | 0.17 |
November | 0.234736E+10 | 0.00 | 0.00 | 0.00 | 253442.77 | 0.113936E+10 | 0.00 | 0.00 | 0.17 |
December | 0.164588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289999E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.318838E+11 | 73729670.93 | 0.00 | 2489841.69 | 47094064.18 | 0.106328E+11 | 0.128049E+10 | 0.00 | 0.19 |
Minimum of Months | 0.124099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.360858E+10 | 55507098.72 | 0.00 | 1440886.35 | 46840621.41 | 0.371897E+10 | 0.615605E+09 | 0.00 | 0.22 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.913541E+11 | 0.364159E+11 | 0.00 | 0.690782E+10 | 0.152276E+11 |
February | 0.239663E+12 | 0.307266E+11 | 0.00 | 0.554390E+10 | 0.106578E+11 |
March | 0.488617E+12 | 0.292614E+11 | 0.00 | 0.526596E+10 | 0.398275E+10 |
April | 0.796780E+12 | 0.296365E+11 | 0.00 | 0.414451E+10 | 0.159114E+10 |
May | 0.108267E+13 | 0.391551E+11 | 0.00 | 0.490174E+10 | 0.442991E+09 |
June | 0.110297E+13 | 0.379424E+11 | 0.00 | 0.569064E+10 | 0.738893E+09 |
July | 0.118781E+13 | 0.378460E+11 | 0.00 | 0.571806E+10 | 0.353001E+10 |
August | 0.934811E+12 | 0.369496E+11 | 0.00 | 0.534727E+10 | 0.589533E+10 |
September | 0.652281E+12 | 0.245187E+11 | 0.00 | 0.582949E+10 | 0.785456E+09 |
October | 0.377054E+12 | 0.289635E+11 | 0.00 | 0.435554E+10 | 0.940074E+09 |
November | 0.123457E+12 | 0.247739E+11 | 0.00 | 0.499578E+10 | 0.543253E+10 |
December | 0.578910E+11 | 0.278827E+11 | 0.00 | 0.639670E+10 | 0.122851E+11 |
Annual Sum or Average | 0.713536E+13 | 0.384072E+12 | 0.00 | 0.650974E+11 | 0.615096E+11 |
Minimum of Months | 0.578910E+11 | 0.245187E+11 | 0.00 | 0.414451E+10 | 0.442991E+09 |