Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:42
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2023-10-16 10:42:35
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:35
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 571.04 | 118.10 | 118.10 |
Net Site Energy | 571.04 | 118.10 | 118.10 |
Total Source Energy | 1808.45 | 374.02 | 374.02 |
Net Source Energy | 1808.45 | 374.02 | 374.02 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 175.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 88.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 86.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 571.02 | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 175.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 88.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 61.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 37.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 49.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 22.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 175.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 88.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 61.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 86.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 22.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 30.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 58.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 118.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 30.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 58.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 118.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 571.020 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 571.020 | 100.00 |
Total On-Site and Utility Electric Sources | 571.020 | 100.00 |
Total Electricity End Uses | 571.020 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 66.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2980.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:35
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:42 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 119.93 |
Skylight-Roof Ratio [%] | 2.61 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 9.3385 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 7.4271 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.7674 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 5.0950 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 5.0950 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 9.3385 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 7.4271 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.7674 | 46.45 | 2.5587 | |
Total | 4835.13 | 5.0950 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 5.0950 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 5.0950 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:35
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:00 | 02-JAN-07:19 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 3560.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 32343.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4788.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8411.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1564.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 57142.72 | 3560.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 3560.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 32343.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 4788.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 6105.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1564.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:35
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 556.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 278.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 195.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 274.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 69.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1808.42 | 0.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 115.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 57.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 56.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 374.02 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 115.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 57.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 56.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 374.02 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:35
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.32 |
ZONE2 FINE STORAGE DIRECT AIR | 3.84 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 0.976836 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 0.976836 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 39959.00 |
PSZ-OFFICE HEATING COIL | 31407.51 |
PSZ-FINE STORAGE HEATING COIL | 114955.97 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 0.000000 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.32 | 1.32 | 1.32 | 1.32 | 1.32 | 1.32 | 1.00 | 1.00 | 1.32 |
PSZ-FINE STORAGE | 3.84 | 3.84 | 3.84 | 3.84 | 3.84 | 3.84 | 1.00 | 1.00 | 3.84 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.32 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 3.84 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.32 | 1465.29 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.84 | 6560.05 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.32 | 1.32 | 1.32 | 0.873488 | 28293.11 | 31407.51 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 3.84 | 3.84 | 3.84 | 2.53 | 95342.32 | 114955.97 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.32 | 0.661733 | 0.882313 | 28293.11 | 14146.56 | 0.750680 | 0.750680 |
PSZ-FINE STORAGE COOLING COIL | 3.84 | 1.92 | 2.56 | 95342.32 | 47671.16 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:35
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:35
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:35
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 9.339 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 17.412 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 7.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.427 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.767 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 6.326 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2212.108 | 9.339 | 173.516 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2212.108 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 10348.979 | 7.427 | 344.966 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10348.979 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 12073.795 | 3.767 | 174.983 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 12073.795 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2405 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.7173 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.6534 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 2.825 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 2.825 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.158 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.394 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.431 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2546 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2546 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.77015739E-08 | 0.38457199E-13 | 0.23136523E-13 | 0.0000000 |
2 | 1 | -5.2160498 | 0.48395528E-04 | -0.66612159E-04 | 0.14765390E-08 |
3 | 0 | 5.4565497 | 0.24045158 | 0.24056658 | |
4 | 2 | 0.53311453E-11 | 0.59398160E-16 | 0.15345153E-15 | 0.0000000 |
5 | 1 | -5.2159564 | 0.46378490E-04 | -0.22332804E-04 | 0.68713370E-11 |
6 | 0 | 5.9333026 | 0.71729982 | 0.71736853 | |
7 | 4 | 0.74747876E-12 | 0.20825084E-15 | -0.25659737E-14 | 0.12362927E-15 |
8 | 3 | -0.37328678E-03 | 0.45238042E-06 | -0.54038165E-04 | 0.14344535E-12 |
9 | 2 | 1.7123825 | 0.10013958E-01 | 1.1198054 | -0.71564441E-04 |
10 | 1 | -7.1648294 | 0.26145347 | -16.966117 | 0.32817431 |
11 | 0 | 5.8918369 | 0.16754891 | 16.285382 | |
12 | 4 | 0.33466332E-12 | 0.89461943E-14 | -0.12859024E-13 | 0.20877214E-15 |
13 | 3 | -0.22871403E-03 | 0.15053116E-05 | -0.31975464E-04 | 0.68322840E-13 |
14 | 2 | 1.3386772 | 0.41030944E-01 | 0.83718830 | -0.43809927E-04 |
15 | 1 | -7.7424045 | 1.2165027 | -15.097018 | 0.25560053 |
16 | 0 | 8.5066984 | 0.84520726 | 16.362604 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.12859024E-13 | 0.89461943E-14 | 0.33466332E-12 | 0.20877214E-15 |
85 | 3 | -0.31975464E-04 | 0.15053116E-05 | -0.22871403E-03 | 0.68322840E-13 |
86 | 2 | 0.83718830 | 0.41030944E-01 | 1.3386772 | -0.43809927E-04 |
87 | 1 | -15.097018 | 1.2165027 | -7.7424045 | 0.25560053 |
88 | 0 | 16.362604 | 0.84520726 | 8.5066984 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.498_SHGC_SOUTH_0.22 | 34 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 | ||
2 | NONRESWINDOW_U_0.498_SHGC_NORTH_0.22 | 35 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 | ||
3 | NONRESWINDOW_U_0.498_SHGC_EAST_0.22 | 36 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 | ||
4 | NONRESWINDOW_U_0.498_SHGC_WEST_0.22 | 37 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 | ||
5 | SKYLIGHT_U_0.75_SHGC_0.35 | 38 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.356 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.20312 | 0.36283 | 0.36283 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | CurtainWall | 4.099 | 0.350 | 0.402 |
2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.799 | 0.390 | 0.214 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.331 | 7.274E-004 | 4.751E-004 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.0781E-005 |
2 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0023E-004 |
3 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.2170E-005 |
4 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1837E-004 |
5 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8164E-005 |
6 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.0943E-004 |
7 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0405E-004 |
8 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.7737E-004 |
9 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6152E-004 |
10 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6949E-004 |
11 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3813E-004 |
12 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.8284E-004 |
13 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4503E-004 |
14 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6630E-004 |
15 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4902E-004 |
16 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5698E-004 |
17 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.6633E-004 |
18 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2855E-004 |
19 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1016E-004 |
20 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3336E-004 |
21 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.1472E-004 |
22 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1843E-004 |
23 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.0972E-004 |
24 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.3095E-005 |
25 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.2971E-004 |
26 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1606E-005 |
27 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.6690E-004 |
28 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.3572E-005 |
29 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.8827E-004 |
30 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6469E-005 |
31 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3671E-003 |
32 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4800E-005 |
33 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7887E-004 |
34 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4982E-005 |
35 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.9043E-004 |
36 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6080E-005 |
37 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.3787E-004 |
38 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3193E-005 |
39 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1725E-004 |
40 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9365E-005 |
41 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.2324E-004 |
42 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8383E-005 |
43 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3929E-004 |
44 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9193E-005 |
45 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.2930E-004 |
46 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8349E-005 |
47 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9265E-004 |
48 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7452E-005 |
49 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.1409E-004 |
50 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9494E-005 |
51 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.4335E-004 |
52 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0495E-005 |
53 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1428E-004 |
54 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8855E-005 |
55 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5174E-004 |
56 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7546E-005 |
57 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3823E-003 |
58 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.8154E-005 |
59 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.0238E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.9817E-005 |
61 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.6665E-003 |
62 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4723E-005 |
63 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1384E-003 |
64 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9663E-005 |
65 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.2020E-003 |
66 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.2566E-005 |
67 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.2118E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.6596E-005 |
69 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8346E-003 |
70 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.2119E-005 |
71 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.6075E-003 |
72 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.5940E-005 |
73 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2377E-004 |
74 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7772E-004 |
75 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.3115E-004 |
76 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9253E-004 |
77 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.3782E-004 |
78 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4562E-004 |
79 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6603E-003 |
80 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.8724E-005 |
81 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0092E-004 |
82 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8294E-004 |
83 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6981E-004 |
84 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6685E-004 |
85 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8741E-004 |
86 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.4816E-004 |
87 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.4798E-004 |
88 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9480E-004 |
89 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.8248E-005 |
90 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.1774E-003 |
91 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.8036E-005 |
92 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.8320E-003 |
93 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.4619E-005 |
94 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.2002E-003 |
95 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1688E-004 |
96 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.0623E-004 |
97 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.9122E-005 |
98 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6606E-003 |
99 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5575E-005 |
100 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.8099E-003 |
101 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.3135E-005 |
102 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.2292E-003 |
103 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.2593E-005 |
104 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.2186E-003 |
105 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7363E-005 |
106 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.7677E-004 |
107 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.4202E-005 |
108 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2869E-004 |
109 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1832E-005 |
110 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0563E-003 |
111 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.0323E-005 |
112 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2689E-003 |
113 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2319E-005 |
114 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6623E-005 |
115 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8587E-005 |
116 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9474E-005 |
117 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6057E-005 |
118 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5533E-005 |
119 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4598E-005 |
120 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5286E-005 |
121 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4434E-005 |
122 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7783E-005 |
123 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7745E-005 |
124 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2962E-005 |
125 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3609E-005 |
126 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1094E-005 |
127 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1685E-005 |
128 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2542E-005 |
129 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1936E-005 |
130 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0279E-005 |
131 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8550E-005 |
132 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9597E-005 |
133 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7482E-005 |
134 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9692E-005 |
135 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4582E-005 |
136 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1042E-005 |
137 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3056E-004 |
138 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1442E-004 |
139 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3931E-004 |
140 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2304E-004 |
141 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1328E-004 |
142 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.4494E-005 |
143 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2514E-005 |
144 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3080E-005 |
145 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2522E-005 |
146 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6815E-004 |
147 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2291E-005 |
148 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8510E-004 |
149 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1087E-005 |
150 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3329E-004 |
151 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4916E-005 |
152 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6240E-005 |
153 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.9357E-005 |
154 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4958E-005 |
155 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2853E-005 |
156 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4901E-005 |
157 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9651E-005 |
158 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4251E-005 |
159 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4899E-005 |
160 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1079E-005 |
161 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6039E-004 |
162 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4172E-005 |
163 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7689E-004 |
164 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5024E-005 |
165 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2500E-004 |
166 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0171E-005 |
167 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2500E-005 |
168 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7738E-005 |
169 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3137E-005 |
170 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5398E-004 |
171 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0982E-005 |
172 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.3737E-004 |
173 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.8937E-005 |
174 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2943E-004 |
175 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0532E-005 |
176 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7293E-004 |
177 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2639E-004 |
178 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3507E-004 |
179 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5540E-004 |
180 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5569E-004 |
181 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0537E-004 |
182 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0844E-004 |
183 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5069E-004 |
184 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0290E-004 |
185 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7691E-004 |
186 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0170E-005 |
187 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4637E-004 |
188 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0228E-005 |
189 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6910E-004 |
190 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.8481E-005 |
191 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5061E-004 |
192 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8433E-005 |
193 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2636E-004 |
194 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7626E-005 |
195 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3116E-004 |
196 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7153E-005 |
197 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1996E-004 |
198 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7278E-005 |
199 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0473E-005 |
200 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3210E-005 |
201 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3886E-003 |
202 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.4660E-005 |
203 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6110E-003 |
204 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.2182E-005 |
205 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1948E-003 |
206 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.9944E-005 |
207 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2387E-004 |
208 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6113E-005 |
209 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1601E-004 |
210 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2276E-004 |
211 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8410E-004 |
212 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4955E-004 |
213 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9391E-004 |
214 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5080E-004 |
215 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2445E-004 |
216 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5215E-004 |
217 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8033E-004 |
218 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9473E-005 |
219 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8103E-004 |
220 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8449E-005 |
221 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9843E-004 |
222 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9749E-005 |
223 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2708E-004 |
224 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5686E-005 |
225 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3272E-004 |
226 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3594E-003 |
227 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2493E-004 |
228 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8179E-003 |
229 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5729E-004 |
230 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7739E-003 |
231 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2726E-004 |
232 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9459E-004 |
233 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9170E-004 |
234 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9610E-005 |
235 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8052E-004 |
236 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8121E-005 |
237 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3899E-004 |
238 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0224E-005 |
239 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9961E-004 |
240 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7482E-005 |
241 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5114E-003 |
242 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.7085E-005 |
243 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5891E-003 |
244 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.1255E-005 |
245 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8450E-003 |
246 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8133E-005 |
247 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6165E-003 |
248 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3274E-005 |
249 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1149E-003 |
250 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6646E-004 |
251 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1052E-003 |
252 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5581E-004 |
253 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4653E-003 |
254 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1115E-004 |
255 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6195E-003 |
256 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2024E-004 |
257 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5258E-004 |
258 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4758E-003 |
259 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3665E-004 |
260 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6699E-003 |
261 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8926E-004 |
262 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9094E-003 |
263 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0001E-004 |
264 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6530E-003 |
265 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4553E-004 |
266 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7925E-005 |
267 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2917E-004 |
268 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6301E-005 |
269 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7821E-004 |
270 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8219E-005 |
271 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9852E-004 |
272 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7461E-005 |
273 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2950E-004 |
274 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.4185E-004 |
275 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1172E-004 |
276 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3421E-004 |
277 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4615E-004 |
278 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1775E-003 |
279 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9891E-004 |
280 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6031E-003 |
281 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7771E-004 |
282 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.4939E-005 |
283 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0208E-004 |
284 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7972E-005 |
285 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9053E-004 |
286 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.2559E-005 |
287 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5919E-003 |
288 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3045E-005 |
289 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1037E-004 |
290 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9576E-004 |
291 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2842E-004 |
292 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6124E-004 |
293 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6735E-004 |
294 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9116E-004 |
295 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5949E-003 |
296 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1554E-004 |
297 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8980E-005 |
298 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8288E-004 |
299 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6217E-005 |
300 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3315E-004 |
301 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4395E-005 |
302 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9607E-004 |
303 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2574E-004 |
304 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7337E-004 |
305 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3234E-004 |
306 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4623E-004 |
307 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9125E-004 |
308 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2421E-004 |
309 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3522E-004 |
310 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5972E-004 |
311 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1039E-004 |
312 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4748E-004 |
313 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4104E-005 |
314 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6327E-005 |
315 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7664E-005 |
316 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4270E-005 |
317 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4585E-005 |
318 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3803E-005 |
319 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1671E-005 |
320 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7584E-005 |
321 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2011E-005 |
322 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5224E-005 |
323 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0177E-005 |
324 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3802E-005 |
325 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.7219E-005 |
326 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4909E-005 |
327 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2556E-004 |
328 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5637E-005 |
329 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8807E-005 |
330 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0862E-004 |
331 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1553E-005 |
332 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0282E-005 |
333 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0024E-005 |
334 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1881E-005 |
335 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9741E-005 |
336 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6869E-004 |
337 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.9195E-005 |
338 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.6287E-005 |
339 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2743E-005 |
340 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5747E-005 |
341 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2154E-005 |
342 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9029E-005 |
343 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4732E-004 |
344 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0119E-004 |
345 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8697E-005 |
346 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2490E-005 |
347 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2083E-005 |
348 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1436E-005 |
349 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4279E-005 |
350 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1842E-005 |
351 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9684E-005 |
352 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3161E-005 |
353 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3677E-004 |
354 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7999E-005 |
355 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9707E-004 |
356 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2436E-005 |
357 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5727E-004 |
358 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8700E-005 |
359 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0983E-004 |
360 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5702E-005 |
361 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.8814E-005 |
362 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4630E-005 |
363 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3007E-005 |
364 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1051E-005 |
365 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6308E-005 |
366 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2148E-005 |
367 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4724E-004 |
368 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8139E-005 |
369 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.8820E-003 |
370 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.5796E-004 |
371 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.4702E-003 |
372 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1535E-004 |
373 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.2905E-003 |
374 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.0093E-004 |
375 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.7364E-003 |
376 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.0749E-004 |
377 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.5685E-004 |
378 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.3441E-003 |
379 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.1883E-004 |
380 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.7396E-003 |
381 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.0614E-004 |
382 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.4413E-003 |
383 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.0394E-004 |
384 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.3300E-003 |
385 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.6596E-003 |
386 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.0069E-004 |
387 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.0280E-003 |
388 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.6091E-004 |
389 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.3916E-003 |
390 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.2296E-004 |
391 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.1798E-003 |
392 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.8715E-004 |
393 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.7377E-003 |
394 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.0107E-004 |
395 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.0532E-003 |
396 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.6109E-004 |
397 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.2463E-003 |
398 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.2273E-004 |
399 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.1798E-003 |
400 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.8715E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 13398.59246 | 16078.31095 | 1.10289 | 1.32347 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 42.21800 | 1.07808E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 4794.58451 | 5753.50141 | 0.13427 | 0.16113 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 12.70000 | 9.15345E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 49862.16647 | 59834.59976 | 3.19953 | 3.83944 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 42.80000 | 1.07818E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 5454.32701 | 6545.19241 | 0.12904 | 0.42471 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 12.70000 | 9.15345E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 42.80000 | 1.07818E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 0.00000 | 0.00000 | 0.00000 | 0.97684 | 00:10:00 | 12.70000 | 9.15345E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 21323.07 | 1.32347 | 1.32347 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 4727.81 | 0.16113 | 0.16113 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 76521.35 | 3.83944 | 3.83944 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 14023.03 | 0.42471 | 0.42471 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.32347 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.83944 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.97684 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 0.97684 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 39959.00499 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 0.00000 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.32347 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.32347 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.32347 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.32347 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.32347 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.32347 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.83944 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.83944 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.83944 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.83944 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.83944 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.83944 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.32347 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.83944 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.32347 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.32347 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1465.28774 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.32347 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.32347 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.32347 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.87349 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.32347 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.66173 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.88231 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28293.11000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14146.55500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75068 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75068 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28293.11000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31407.50782 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 31407.50782 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.83944 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.83944 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 6560.05230 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.83944 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.83944 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.83944 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.53403 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.83944 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.91972 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.55963 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 95342.32000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 47671.16000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 95342.32000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 114955.97111 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 114955.97111 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 27265.1 | 11.96 | 11.69 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 92358.0 | 11.12 | 10.87 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 3.5957538906E-002 | 2.1740727014E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 4.7824477826E-002 | 3.5786098022E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 6.4533071267E-002 | 4.5616249156E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:35
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8505.58 | 448.94 | 0.00 | -130.3 | 788.29 | 9612.60 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:35
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:35
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.233 | 0.240 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.985 | 2.825 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.985 | 2.825 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.985 | 2.825 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.653 | 0.717 | 3204.84 | 3105.72 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.685 | 2.825 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.685 | 2.825 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.498_SHGC_WEST_0.22 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.831 | 0.221 | 0.243 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.498_SHGC_WEST_0.22 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.831 | 0.221 | 0.243 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.498_SHGC_NORTH_0.22 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.831 | 0.221 | 0.243 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.498_SHGC_NORTH_0.22 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.831 | 0.221 | 0.243 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.402 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 137.59 | 5.185 | 0.479 | 0.381 | |||||||||||||||||
North Total or Average | 6.51 | 2.831 | 0.221 | 0.243 | |||||||||||||||||
Non-North Total or Average | 131.09 | 5.302 | 0.492 | 0.388 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:35
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:35
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 9.3385 | 236.88 | 2212.11 | LightsWired | LTG_SCH_OFFICE | 52.33 | 168.00 | 33.34 | 0.0000 | Y | 13.84 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 7.4271 | 1393.41 | 10348.98 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 18.18 | 0.0000 | Y | 35.32 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.7674 | 3204.84 | 12073.79 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 17.15 | 0.0000 | Y | 38.87 |
Interior Lighting Total | 5.0950 | 4835.13 | 24634.88 | 88.03 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 10348.98 | 2587.24 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 10348.98 | 2587.24 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 12073.79 | 3018.45 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 12073.79 | 3018.45 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.29 | 2212.11 | 641.51 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.10 | 2212.11 | 221.21 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 123.84 | AstronomicalClock | - | 41.85 | 41.85 | 0.97 | |
EXTERIOR_LIGHTS_B | 4305.62 | AstronomicalClock | - | 83.85 | 62.85 | 50.80 | |
EXTERIOR_LIGHTS_C | 1091.36 | AstronomicalClock | - | 83.85 | 48.85 | 10.01 | |
Exterior Lighting Total | 5520.82 | 61.78 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:35
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28293.11 | 21239.07 | 7054.04 | 0.75 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 95342.32 | 66842.59 | 28499.73 | 0.70 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 27265.1 | 11.96 | 11.69 | ||||
PSZ-FINE STORAGE COOLING COIL | 92358.0 | 11.12 | 10.87 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 39959.00 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 31407.51 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 114955.97 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.98 | 90.76 | 92.91 | 1.00 | 4.17 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.32 | 1465.29 | 1107.16 | 1.00 | 1.34 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.60 | 1018.41 | 3.84 | 6560.05 | 1708.60 | 1.00 | 1.18 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:35
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 13398.59 | 16078.31 | 67.88 | 1.103 | 1.323 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 23.90 | 23.90 | 0.00833 | 42.22 | 0.01078 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 49862.17 | 59834.60 | 42.94 | 3.200 | 3.839 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 26.70 | 26.70 | 0.00847 | 42.80 | 0.01078 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 0.00 | 42.77 | 0.01086 | 42.80 | 0.01078 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 4794.58 | 5753.50 | 24.29 | 0.134 | 0.161 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00903 | 12.70 | 0.00915 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 5454.33 | 6545.19 | 4.70 | 0.129 | 0.425 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00865 | 12.70 | 0.00915 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | 00:10:00 | 10.00 | 11.69 | 0.00856 | 12.70 | 0.00915 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.32 | 1.32 | 0.16 | 0.16 | 1.3235 | 1.3235 | 1.3235 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.84 | 3.84 | 0.42 | 0.42 | 3.8394 | 3.8394 | 3.8394 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 39959.005 | 39959.005 | -999.0 | -999.0 | -999.000 | 1/21 00:10:00 | 1/21 00:10:00 | 39959.00 | 39959.00 | 0.976836 | 10.00 | 10.00 | 0.00800000 | 43.33 | 22.14 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 10.00 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | ||
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 28293.110 | 21239.072 | 1.323470 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 14146.56 | 13061.46 | 0.882313 | 26.22 | 17.17 | 0.00851609 | 12.00 | 11.25 | 0.00800000 | 42.31 | 0.01078097 | 23.73 | 11.5928 | 23.90 | 0.00832638 | 45.0868 | 13398.16 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 31407.508 | 31407.508 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 31407.51 | 31407.51 | 1.323467 | 20.38 | 15.55 | 0.00903989 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 7.7285 | 21.10 | 0.00903038 | 57.8929 | 4794.58 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 95342.320 | 66842.594 | 3.839440 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 47671.16 | 43545.36 | 2.559627 | 29.87 | 18.57 | 0.00872482 | 12.00 | 11.25 | 0.00800000 | 42.80 | 0.01078182 | 23.86 | 16.5927 | 26.70 | 0.00846898 | 38.8164 | 49861.22 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 114955.971 | 114955.971 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 114955.97 | 114955.97 | 3.839435 | 15.24 | 13.44 | 0.00886419 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 11.0618 | 15.56 | 0.00882821 | 80.1592 | 5287.83 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:42:35
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 39959.005 | 39959.005 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.976836 | 1.17571482 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 39959.00 | 39959.00 | 1.0000 | 1.17571482 | 0.976836 | 10.00 | 10.00 | 0.00800000 | 30204.6 | 43.33 | 22.14 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39959.00 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 10.00 | 0.00800000 | 10.00 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28293.110 | 21239.072 | 1.323470 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6710 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.323467 | 1.59291790 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | Sensible | 14146.56 | 13061.46 | 1.0000 | 1.06194790 | 0.882313 | 26.22 | 17.17 | 0.00851609 | 48063.4 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14146.56 | 42.31 | 0.01078097 | 23.73 | 0.10228463 | 11.5928 | 23.90 | 0.00832638 | 23.90 | 0.00832638 | 45.0868 | 13398.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31407.508 | 31407.508 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.323467 | 1.59291790 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 31407.51 | 31407.51 | 1.0000 | 1.59291790 | 1.323467 | 20.38 | 15.55 | 0.00903989 | 43427.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31407.51 | 12.70 | 0.00915345 | 12.70 | 0.10228463 | 7.7285 | 21.02 | 0.00903038 | 21.10 | 0.00903038 | 57.8929 | 4794.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 95342.320 | 66842.594 | 3.839440 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0590 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.839435 | 4.62112490 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | Sensible | 47671.16 | 43545.36 | 1.0000 | 3.08075381 | 2.559627 | 29.87 | 18.57 | 0.00872482 | 52318.5 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 47671.16 | 42.80 | 0.01078182 | 23.86 | 0.42471127 | 16.5927 | 26.70 | 0.00846898 | 26.70 | 0.00846898 | 38.8164 | 49861.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 114955.971 | 114955.971 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.839435 | 4.62112490 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 114955.97 | 114955.97 | 1.0000 | 4.62112490 | 3.839435 | 15.24 | 13.44 | 0.00886419 | 37737.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 114955.97 | 12.70 | 0.00915345 | 12.70 | 0.42471127 | 11.0618 | 15.56 | 0.00882821 | 15.56 | 0.00882821 | 80.1592 | 5287.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:35
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 3179.67 | 496.17 | 329.50 |
ZONE2 FINE STORAGE | 3426.67 | 2792.83 | 2640.83 |
ZONE3 BULK STORAGE | 3384.17 | 3155.83 | 2957.00 |
Facility | 3436.67 | 3196.33 | 2980.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 0.00 | 74.50 | 0.00 | 66.00 |
ZONE2 FINE STORAGE | 0.00 | 482.33 | 0.00 | 9.33 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 546.17 | 0.00 | 66.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:35
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.354 | 0.407 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.498 | 0.222 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.122 | 0.000 | 2.188 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:42:35
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.56 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1269904.19 | 0.00 | 1269904.19 | 1981619.38 | 3251523.57 | 3225648.14 | 5388.96 | 3371.04 | 0.00 | 172.45 |
ZONE2 FINE STORAGE | 5946899.19 | 0.00 | 5946899.19 | 5278757.67 | 11225656.86 | 13393694.68 | 5402.90 | 3357.10 | 0.00 | 1850.56 |
ZONE3 BULK STORAGE | 0.00 | 0.57E+09 | 0.57E+09 | 26777788.21 | 0.59E+09 | 30805497.77 | 4237.29 | 8.00 | 4514.71 | 5105.75 |
Total Facility | 7216803.38 | 0.57E+09 | 0.57E+09 | 34038165.26 | 0.61E+09 | 47424840.58 | 6769.90 | 3398.27 | 4514.71 | 5106.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.0963 | 0.0000 | 0.0963 | 0.1106 | 0.2069 | 0.1023 | 264.96 | 3371.04 | 0.00 |
ZONE2 FINE STORAGE | 0.3914 | 0.0000 | 0.3914 | 0.1747 | 0.5661 | 0.4247 | 302.13 | 3333.87 | 0.00 |
ZONE3 BULK STORAGE | 0.0000 | 19.8061 | 19.8061 | 1.1165 | 20.9226 | 0.9768 | 1548.65 | 4.00 | 2083.35 |
Total Facility | 0.4877 | 19.8061 | 20.2938 | 1.4018 | 21.6956 | 1.5038 | 1645.90 | 3371.04 | 2083.35 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 1839653.55 | 0.00 | 1839653.55 | 3225648.14 | 5367.95 | 1.89 | 3390.16 | 170.65 |
PSZ-FINE STORAGE | 8614895.32 | 0.00 | 8614895.32 | 13393694.68 | 5286.87 | 8.31 | 3464.82 | 1849.98 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1395 | 0.0000 | 0.1395 | 0.1023 | 246.21 | 1.42 | 3388.37 |
PSZ-FINE STORAGE | 0.5670 | 0.0000 | 0.5670 | 0.4247 | 299.82 | 0.21 | 3335.97 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 3689.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 5271.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1442 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6026 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:35
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 446 |
Defaulted Fields | 391 |
Fields with Defaults | 1172 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:42:35
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 571.02 | 1565.96 | 01-JAN-09:40 | 57142.72 | 10-AUG-16:00 |
Electricity:Building | 261.55 | 1084.96 | 01-JAN-09:40 | 20921.89 | 18-NOV-17:00 |
Electricity:Zone:ZONE1 OFFICE | 43.01 | 520.87 | 01-JAN-00:10 | 3190.10 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 224.54 | 1084.96 | 01-JAN-09:40 | 19354.64 | 14-MAR-08:10 |
InteriorLights:Electricity | 88.03 | 615.08 | 01-JAN-09:40 | 9319.46 | 14-MAR-08:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 13.84 | 51.00 | 01-JAN-00:10 | 1355.05 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 88.03 | 615.08 | 01-JAN-09:40 | 9319.46 | 14-MAR-08:10 |
LightsWired:InteriorLights:Electricity | 88.03 | 615.08 | 01-JAN-09:40 | 9319.46 | 14-MAR-08:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 13.84 | 51.00 | 01-JAN-00:10 | 1355.05 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 88.03 | 615.08 | 01-JAN-09:40 | 9319.46 | 14-MAR-08:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 35.32 | 299.97 | 01-JAN-00:10 | 3848.58 | 14-MAR-08:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 35.32 | 299.97 | 01-JAN-00:10 | 3848.58 | 14-MAR-08:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 35.32 | 299.97 | 01-JAN-00:10 | 3848.58 | 14-MAR-08:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 183.22 | 264.11 | 01-JAN-09:40 | 14467.07 | 06-NOV-17:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 38.87 | 264.11 | 01-JAN-09:40 | 4115.84 | 14-MAR-08:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 38.87 | 264.11 | 01-JAN-09:40 | 4115.84 | 14-MAR-08:10 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 86.81 | 0.00 | 01-JAN-00:10 | 8427.94 | 10-AUG-16:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 37.00 | 0.00 | 01-JAN-00:10 | 2305.29 | 08-FEB-14:50 |
Ventilation (simple):Fans:Electricity | 37.00 | 0.00 | 01-JAN-00:10 | 2305.29 | 08-FEB-14:50 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 37.00 | 0.00 | 01-JAN-00:10 | 2305.29 | 08-FEB-14:50 |
ElectricityPurchased:Facility | 571.02 | 1565.96 | 01-JAN-09:40 | 57142.72 | 10-AUG-16:00 |
ElectricityPurchased:Plant | 571.02 | 1565.96 | 01-JAN-09:40 | 57142.72 | 10-AUG-16:00 |
Cogeneration:ElectricityPurchased | 571.02 | 1565.96 | 01-JAN-09:40 | 57142.72 | 10-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 571.02 | 1565.96 | 01-JAN-09:40 | 57142.72 | 10-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 571.02 | 1565.96 | 01-JAN-09:40 | 57142.72 | 10-AUG-16:00 |
ElectricityNet:Plant | 571.02 | 1565.96 | 01-JAN-09:40 | 57142.72 | 10-AUG-16:00 |
Cogeneration:ElectricityNet | 571.02 | 1565.96 | 01-JAN-09:40 | 57142.72 | 10-AUG-16:00 |
General:Cogeneration:ElectricityNet | 571.02 | 1565.96 | 01-JAN-09:40 | 57142.72 | 10-AUG-16:00 |
Electricity:HVAC | 225.68 | 0.00 | 01-JAN-00:10 | 38606.15 | 10-AUG-16:10 |
General:Fans:Electricity | 49.81 | 0.00 | 01-JAN-00:10 | 6122.64 | 10-AUG-16:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 175.87 | 0.00 | 01-JAN-00:10 | 32483.51 | 10-AUG-16:10 |
General:Cooling:Electricity | 175.87 | 0.00 | 01-JAN-00:10 | 32483.51 | 10-AUG-16:10 |
ExteriorLights:Electricity | 61.78 | 0.00 | 01-JAN-07:10 | 5520.82 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 61.78 | 0.00 | 01-JAN-07:10 | 5520.82 | 01-JAN-06:10 |
Electricity:Plant | 22.02 | 481.00 | 27-MAR-05:10 | 1738.29 | 13-JAN-12:30 |
WaterSystems:Electricity | 22.02 | 481.00 | 27-MAR-05:10 | 1738.29 | 13-JAN-12:30 |
Water Heater:WaterSystems:Electricity | 22.02 | 481.00 | 27-MAR-05:10 | 1738.29 | 13-JAN-12:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 0.02 | 0.00 | 01-JAN-00:10 | 3560.79 | 02-JAN-07:20 |
NaturalGas:HVAC | 0.02 | 0.00 | 01-JAN-00:10 | 3560.79 | 02-JAN-07:20 |
Heating:NaturalGas | 0.02 | 0.00 | 01-JAN-00:10 | 3560.79 | 02-JAN-07:20 |
General:Heating:NaturalGas | 0.02 | 0.00 | 01-JAN-00:10 | 3560.79 | 02-JAN-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 975.76 | 0.00 | 01-JAN-00:10 | 156432.70 | 10-AUG-16:10 |
EnergyTransfer:Building | 363.33 | 0.00 | 01-JAN-00:10 | 54591.59 | 21-JUL-16:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 96.12 | 0.00 | 01-JAN-00:10 | 17176.36 | 16-AUG-12:00 |
Heating:EnergyTransfer | 0.60 | 0.00 | 01-JAN-00:10 | 1969.00 | 02-JAN-07:20 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.01 | 0.00 | 01-JAN-00:10 | 1969.00 | 02-JAN-07:20 |
General:Heating:EnergyTransfer | 0.60 | 0.00 | 01-JAN-00:10 | 1969.00 | 02-JAN-07:20 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.01 | 0.00 | 01-JAN-00:10 | 1969.00 | 02-JAN-07:20 |
Cooling:EnergyTransfer | 362.73 | 0.00 | 01-JAN-00:10 | 54591.59 | 21-JUL-16:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 96.11 | 0.00 | 01-JAN-00:10 | 17176.36 | 16-AUG-12:00 |
General:Cooling:EnergyTransfer | 362.73 | 0.00 | 01-JAN-00:10 | 54591.59 | 21-JUL-16:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 96.11 | 0.00 | 01-JAN-00:10 | 17176.36 | 16-AUG-12:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 267.21 | 0.00 | 01-JAN-00:10 | 45294.34 | 21-MAY-12:50 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.58 | 0.00 | 01-JAN-00:10 | 1823.88 | 01-MAR-08:30 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.58 | 0.00 | 01-JAN-00:10 | 1823.88 | 01-MAR-08:30 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 266.62 | 0.00 | 01-JAN-00:10 | 45294.34 | 21-MAY-12:50 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 266.62 | 0.00 | 01-JAN-00:10 | 45294.34 | 21-MAY-12:50 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 612.43 | 0.00 | 01-JAN-00:10 | 105618.73 | 22-AUG-17:00 |
HeatingCoils:EnergyTransfer | 0.02 | 0.00 | 01-JAN-00:10 | 2321.01 | 02-JAN-07:20 |
CoolingCoils:EnergyTransfer | 612.41 | 0.00 | 01-JAN-00:10 | 105618.73 | 22-AUG-17:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:35
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 0.013 | -96.109 | 0.000 | 0.000 | 9.123 | 13.843 | 29.165 | 12.320 | 0.000 | 12.469 | 24.834 | 0.000 | -2.780 | 0.000 | -2.877 | -0.000 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 0.584 | -266.619 | 0.000 | 0.000 | 17.457 | 35.319 | 0.000 | 43.705 | 0.000 | 25.498 | 162.571 | 0.000 | -8.799 | 0.000 | -9.716 | -0.000 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20.604 | 38.871 | 107.344 | 793.540 | 0.000 | 57.764 | 0.012 | 0.000 | -208.164 | 0.000 | -540.350 | -269.609 |
Total Facility | 0.000 | 0.000 | 0.596 | -362.728 | 0.000 | 0.000 | 47.184 | 88.033 | 136.508 | 849.565 | 0.000 | 95.732 | 187.417 | 0.000 | -219.744 | 0.000 | -552.943 | -269.609 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 26-APR-05:01 | 0.00 | 0.00 | 0.00 | -26852.54 | 0.00 | 0.00 | 76.45 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 26626.56 | 0.00 | -276.48 | 0.00 | -175.50 | 0.00 |
ZONE2 FINE STORAGE | 29-OCT-14:53 | 0.00 | 0.00 | 0.00 | -80234.65 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 2469.08 | 0.00 | 2026.47 | 75439.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-JUL-05:01 | 0.00 | 0.00 | 0.00 | -97157.35 | 0.00 | 0.00 | 367.22 | 879.19 | 2600.55 | 12.75 | 0.00 | 1354.40 | 193044.51 | 0.00 | -13171.92 | 0.00 | -87929.35 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 02-JAN-07:20 | 0.00 | 0.00 | 1968.76 | 0.00 | 0.00 | 0.00 | 226.13 | 739.11 | 917.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -339.77 | 0.00 | -3069.37 | -442.39 |
ZONE2 FINE STORAGE | 29-APR-06:07 | 0.00 | 0.00 | 2139.14 | 0.00 | 0.00 | 0.00 | 340.99 | 2716.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -424.50 | 0.00 | -71.42 | -4700.81 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 29-APR-06:07 | -4659.92 | 4659.92 | 2139.14 | -4659.92 | 0.00 | 0.00 | 1121.56 | 6625.09 | 2967.56 | 0.00 | 0.00 | 11.32 | 16491.44 | 0.00 | -23706.67 | 0.00 | -989.52 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:35
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3235 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.3235 | 0.0773 | 1.0000 | Not calculated | 0.1023 | 0.0773 | ||
PSZ-FINE STORAGE | 3.8394 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.8394 | 0.1106 | 1.0000 | Not calculated | 0.4247 | 0.1106 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3235 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.3235 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0773 | ||
PSZ-FINE STORAGE | 3.8394 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.8394 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1106 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3235 | 1.3235 | 1.3235 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.8394 | 3.8394 | 3.8394 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3235 | 1.3235 | 1.3235 | 1.3235 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.8394 | 3.8394 | 3.8394 | 3.8394 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3235 | 1.3235 | 1.3235 | No | 0.1023 | 0.6348 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.8394 | 3.8394 | 3.8394 | No | 0.4247 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3235 | 1.3235 | 1.3235 | 1.3235 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.8394 | 3.8394 | 3.8394 | 3.8394 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:35
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 66.00 |
Number of hours not met | 66.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.02 | 3560.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 175.87 | 32483.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 88.03 | 9319.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 61.78 | 5520.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 37.00 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 49.81 | 6122.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 22.02 | 1738.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 571.02 |
Natural Gas | 0.00 | 0.02 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 571.04 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 18.21 |
Space Heating | 0.00 |
Space Cooling | 36.37 |
Fans (All) | 17.96 |
Service Water Heating | 4.55 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 118.10 |
Subtotal | 118.10 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 15.42 |
Space Heating | 0.00 |
Space Cooling | 30.80 |
Fans (All) | 15.20 |
Service Water Heating | 3.86 |
Receptacle Equipment | 23.91 |
Miscellaneous | 10.82 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2729. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:35
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 5278.33 | 3047.50 | 434.17 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 3414.17 | 5345.83 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 2164.83 | 2684.33 | 1960.00 | 1903.00 | 47.83 |
Min | 2164.83 | 2684.33 | 0.00 | 0.00 | 0.00 |
Max | 5278.33 | 5345.83 | 1960.00 | 1903.00 | 47.83 |
Average | 3619.11 | 3692.56 | 798.06 | 634.33 | 15.94 |
Sum | 10857.33 | 11077.67 | 2394.17 | 1903.00 | 47.83 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33021.83 | 5.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 24827.00 | 57892.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 30736.83 | 66419.17 | 46628.83 | 44997.17 | 2411.00 |
Min | 24827.00 | 5.17 | 0.00 | 0.00 | 0.00 |
Max | 33021.83 | 66419.17 | 46628.83 | 44997.17 | 2411.00 |
Average | 29528.56 | 41438.78 | 15542.94 | 14999.06 | 803.67 |
Sum | 88585.67 | 124316.33 | 46628.83 | 44997.17 | 2411.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 4470.83 | 4199.83 | 89.33 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 2300.00 | 6460.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 1579.17 | 4016.00 | 1417.17 | 1406.33 | 341.33 |
Min | 1579.17 | 4016.00 | 0.00 | 0.00 | 0.00 |
Max | 4470.83 | 6460.00 | 1417.17 | 1406.33 | 341.33 |
Average | 2783.33 | 4891.94 | 502.17 | 468.78 | 113.78 |
Sum | 8350.00 | 14675.83 | 1506.50 | 1406.33 | 341.33 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 31789.50 | 1237.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 18326.50 | 64392.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 20578.83 | 97134.00 | 31459.83 | 30227.50 | 11792.83 |
Min | 18326.50 | 1237.50 | 0.00 | 0.00 | 0.00 |
Max | 31789.50 | 97134.00 | 31459.83 | 30227.50 | 11792.83 |
Average | 23564.94 | 54254.67 | 10486.61 | 10075.83 | 3930.94 |
Sum | 70694.83 | 162764.00 | 31459.83 | 30227.50 | 11792.83 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:35
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:35
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.306472E+10 | 19033.50 | 30-JAN-06:02 | 20.03 | 17.43 | 0.630120E+09 | 769.03 | 31-JAN-16:00 | 23.00 | 17.31 |
February | 0.389971E+10 | 20034.77 | 08-FEB-06:01 | 21.85 | 18.67 | 0.582456E+09 | 769.04 | 08-FEB-16:19 | 25.00 | 20.42 |
March | 0.589643E+10 | 26371.32 | 28-MAR-05:01 | 25.67 | 14.74 | 0.685176E+09 | 769.04 | 29-MAR-10:30 | 27.55 | 21.92 |
April | 0.706939E+10 | 26853.18 | 26-APR-05:01 | 23.17 | 12.12 | 0.635022E+09 | 769.09 | 27-APR-12:09 | 36.00 | 19.62 |
May | 0.983354E+10 | 26376.52 | 11-MAY-05:01 | 28.00 | 16.07 | 0.660694E+09 | 769.09 | 22-MAY-13:20 | 37.90 | 22.72 |
June | 0.107509E+11 | 24275.56 | 16-JUN-05:01 | 28.17 | 20.46 | 0.660797E+09 | 769.11 | 12-JUN-12:09 | 28.17 | 20.46 |
July | 0.114025E+11 | 24326.07 | 22-JUL-05:01 | 31.00 | 23.08 | 0.635520E+09 | 769.11 | 31-JUL-12:09 | 40.98 | 25.84 |
August | 0.126153E+11 | 21945.02 | 07-AUG-05:01 | 32.82 | 23.16 | 0.686429E+09 | 769.28 | 22-AUG-12:09 | 41.07 | 28.76 |
September | 0.105075E+11 | 21069.02 | 05-SEP-05:01 | 30.17 | 24.66 | 0.635417E+09 | 769.10 | 05-SEP-12:09 | 40.98 | 24.12 |
October | 0.922062E+10 | 26007.15 | 20-OCT-05:01 | 23.17 | 16.23 | 0.635313E+09 | 769.08 | 16-OCT-14:50 | 23.17 | 16.23 |
November | 0.710329E+10 | 24370.78 | 13-NOV-06:01 | 20.92 | 17.72 | 0.609716E+09 | 769.07 | 01-NOV-15:30 | 20.92 | 17.72 |
December | 0.474615E+10 | 23982.04 | 13-DEC-06:02 | 15.02 | 12.69 | 0.634037E+09 | 769.05 | 05-DEC-15:09 | 15.02 | 12.69 |
Annual Sum or Average | 0.961100E+11 | 0.769070E+10 | ||||||||
Minimum of Months | 0.306472E+10 | 19033.50 | 15.02 | 12.12 | 0.582456E+09 | 769.03 | 15.02 | 12.69 | ||
Maximum of Months | 0.126153E+11 | 26853.18 | 32.82 | 24.66 | 0.686429E+09 | 769.28 | 41.07 | 28.76 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.531434E+09 | 4272.39 | 31-JAN-13:40 | 23.30 | 16.04 | 0.166577E+10 | 2246.83 | 28-JAN-14:00 | 23.30 | 16.04 |
February | 0.225850E+10 | 28708.29 | 05-FEB-14:55 | 32.00 | 19.39 | 0.163302E+10 | 2246.90 | 06-FEB-14:30 | 32.25 | 17.25 |
March | 0.719785E+10 | 61612.52 | 26-MAR-12:43 | 34.83 | 18.09 | 0.196519E+10 | 2246.91 | 21-MAR-12:50 | 34.83 | 18.09 |
April | 0.153113E+11 | 70267.56 | 28-APR-17:06 | 34.05 | 20.50 | 0.184851E+10 | 2246.96 | 07-APR-14:20 | 34.05 | 20.50 |
May | 0.321528E+11 | 75586.82 | 14-MAY-17:23 | 33.50 | 21.38 | 0.192889E+10 | 2247.03 | 30-MAY-15:00 | 38.50 | 25.32 |
June | 0.375413E+11 | 75395.21 | 20-JUN-18:23 | 35.95 | 20.66 | 0.192887E+10 | 2247.08 | 21-JUN-15:50 | 38.92 | 22.69 |
July | 0.458012E+11 | 72834.42 | 22-JUL-05:01 | 31.00 | 23.08 | 0.185489E+10 | 2247.08 | 12-JUL-14:50 | 31.00 | 23.08 |
August | 0.481272E+11 | 70252.01 | 07-AUG-05:01 | 32.82 | 23.16 | 0.200334E+10 | 2247.08 | 15-AUG-14:00 | 39.00 | 25.15 |
September | 0.360477E+11 | 69463.53 | 04-SEP-12:22 | 40.80 | 24.42 | 0.185473E+10 | 2247.07 | 05-SEP-12:39 | 40.93 | 23.77 |
October | 0.261165E+11 | 80241.62 | 29-OCT-14:53 | 32.00 | 19.85 | 0.185485E+10 | 2247.00 | 16-OCT-13:09 | 32.00 | 19.85 |
November | 0.124489E+11 | 60804.64 | 11-NOV-14:13 | 30.67 | 19.80 | 0.177663E+10 | 2246.97 | 04-NOV-14:20 | 30.67 | 19.80 |
December | 0.308791E+10 | 28776.67 | 03-DEC-13:35 | 27.93 | 20.01 | 0.179417E+10 | 2251.50 | 23-DEC-11:09 | 23.33 | 19.23 |
Annual Sum or Average | 0.266623E+12 | 0.221089E+11 | ||||||||
Minimum of Months | 0.531434E+09 | 4272.39 | 23.30 | 16.04 | 0.163302E+10 | 2246.83 | 23.30 | 16.04 | ||
Maximum of Months | 0.481272E+11 | 80241.62 | 40.80 | 24.42 | 0.200334E+10 | 2251.50 | 40.93 | 25.32 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.84 | 0.365168E+10 | 5639.99 | 28-JAN-14:30 | 27.00 | 16.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 14.59 | 0.393355E+10 | 7282.84 | 06-FEB-15:09 | 32.32 | 17.34 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 | 18.46 | 0.525125E+10 | 9097.65 | 27-MAR-10:00 | 38.00 | 18.84 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 | 20.11 | 0.559323E+10 | 9097.65 | 24-APR-12:09 | 37.07 | 17.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 | 23.56 | 0.701521E+10 | 9097.65 | 04-MAY-09:00 | 37.40 | 18.18 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 23.24 | 0.728043E+10 | 9097.65 | 01-JUN-08:00 | 37.00 | 22.08 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 | 27.02 | 0.725853E+10 | 9097.65 | 01-JUL-09:39 | 36.80 | 26.55 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 | 28.28 | 0.787767E+10 | 9097.65 | 01-AUG-08:50 | 36.33 | 24.56 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 | 25.04 | 0.690476E+10 | 9097.65 | 01-SEP-10:09 | 36.08 | 24.95 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 | 26.77 | 0.621270E+10 | 9097.65 | 02-OCT-12:09 | 36.12 | 19.21 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 | 21.17 | 0.507687E+10 | 7929.14 | 01-NOV-14:09 | 32.83 | 26.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 | 15.63 | 0.434027E+10 | 6336.82 | 06-DEC-13:00 | 27.00 | 20.88 |
Annual Sum or Average | 0.00 | 0.703962E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 15.70 | 12.84 | 0.365168E+10 | 5639.99 | 27.00 | 16.03 | ||
Maximum of Months | 0.00 | 0.00 | 33.23 | 28.28 | 0.787767E+10 | 9097.65 | 38.00 | 26.55 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11242363.03 | 1969.00 | 02-JAN-07:20 | 13.00 |
February | 539849.28 | 260.06 | 24-FEB-07:10 | 19.17 |
March | 465983.45 | 347.21 | 09-MAR-07:10 | 20.17 |
April | 13210.54 | 22.02 | 05-APR-06:10 | 17.02 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 242068.55 | 138.26 | 27-DEC-07:10 | 20.92 |
Annual Sum or Average | 12503474.86 | |||
Minimum of Months | 0.00 | 0.00 | 13.00 | |
Maximum of Months | 11242363.03 | 1969.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.371712E+09 | 1756.80 | 17-JAN-12:20 | 25.07 |
February | 80692396.94 | 1713.65 | 15-FEB-08:00 | 23.20 |
March | 46073895.65 | 1823.88 | 01-MAR-08:30 | 26.00 |
April | 4394915.25 | 2139.10 | 29-APR-06:07 | 25.25 |
May | 758124.06 | 1167.47 | 15-MAY-06:04 | 23.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 882185.21 | 1877.98 | 23-SEP-06:10 | 25.97 |
October | 2751415.98 | 1760.02 | 25-OCT-06:10 | 24.93 |
November | 717149.56 | 1195.25 | 25-NOV-07:10 | 24.70 |
December | 76007561.77 | 1496.74 | 23-DEC-17:50 | 24.20 |
Annual Sum or Average | 0.583989E+09 | |||
Minimum of Months | 0.00 | 0.00 | 23.17 | |
Maximum of Months | 0.371712E+09 | 2139.10 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.120443E+10 | 1355.05 | 02-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.107372E+10 | 1355.05 | 01-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.123743E+10 | 1355.05 | 01-MAR-08:09 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.115349E+10 | 1355.05 | 01-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.116815E+10 | 1224.06 | 01-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.112513E+10 | 1355.05 | 08-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.109692E+10 | 1355.05 | 14-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.117872E+10 | 1355.05 | 12-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.111749E+10 | 1355.05 | 01-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.114589E+10 | 1355.05 | 02-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.112870E+10 | 1355.05 | 01-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.121340E+10 | 1355.05 | 01-DEC-08:09 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.138435E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.107372E+10 | 1224.06 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.123743E+10 | 1355.05 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.323435E+10 | 3527.86 | 02-JAN-15:00 | 0.00 | 0.00 |
February | 0.279317E+10 | 3527.86 | 09-FEB-09:09 | 0.00 | 0.00 |
March | 0.308124E+10 | 3848.58 | 14-MAR-08:09 | 0.00 | 0.00 |
April | 0.276737E+10 | 3527.86 | 18-APR-08:09 | 0.00 | 0.00 |
May | 0.286372E+10 | 3395.71 | 10-MAY-07:10 | 0.00 | 0.00 |
June | 0.283369E+10 | 3207.15 | 02-JUN-08:09 | 0.00 | 0.00 |
July | 0.277095E+10 | 3395.71 | 14-JUL-07:10 | 0.00 | 0.00 |
August | 0.291438E+10 | 3395.71 | 14-AUG-07:10 | 0.00 | 0.00 |
September | 0.278948E+10 | 3395.71 | 01-SEP-07:10 | 0.00 | 0.00 |
October | 0.295774E+10 | 3527.86 | 20-OCT-08:09 | 0.00 | 0.00 |
November | 0.299980E+10 | 3527.86 | 04-NOV-08:09 | 0.00 | 0.00 |
December | 0.331280E+10 | 3848.58 | 09-DEC-15:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.353187E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.276737E+10 | 3207.15 | 0.00 | 0.00 | |
Maximum of Months | 0.331280E+10 | 3848.58 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.346301E+10 | 3961.65 | 02-JAN-16:00 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.308535E+10 | 3961.65 | 09-FEB-16:00 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.342819E+10 | 4115.84 | 14-MAR-08:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.310429E+10 | 3961.65 | 18-APR-07:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.313785E+10 | 3301.38 | 10-MAY-07:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.307429E+10 | 3169.37 | 01-JUN-06:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.303892E+10 | 3301.38 | 14-JUL-07:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.324900E+10 | 3301.38 | 05-AUG-07:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.312776E+10 | 3301.38 | 01-SEP-07:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.328491E+10 | 3631.52 | 30-OCT-07:10 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.331097E+10 | 3961.65 | 06-NOV-16:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.356668E+10 | 3961.65 | 01-DEC-16:49 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.388712E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.303892E+10 | 3169.37 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.356668E+10 | 4115.84 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.120443E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9621575.44 | 0.784831E+09 |
February | 0.127628E+10 | 0.107372E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104499E+09 | 0.629242E+09 |
March | 0.149825E+10 | 0.123743E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369530E+09 | 0.416742E+09 |
April | 0.138726E+10 | 0.115349E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.709462E+09 | 0.189079E+09 |
May | 0.144276E+10 | 0.116815E+10 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154319E+10 | 30540247.82 |
June | 0.144276E+10 | 0.112513E+10 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188954E+10 | 7204635.78 |
July | 0.138726E+10 | 0.109692E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211742E+10 | 44012.25 |
August | 0.149825E+10 | 0.117872E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237402E+10 | 1954.29 |
September | 0.138726E+10 | 0.111749E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163660E+10 | 7871921.63 |
October | 0.138726E+10 | 0.114589E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111004E+10 | 41813901.89 |
November | 0.133177E+10 | 0.112870E+10 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524656E+09 | 0.217947E+09 |
December | 0.138726E+10 | 0.121340E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80812074.85 | 0.552119E+09 |
Annual Sum or Average | 0.168137E+11 | 0.138435E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124694E+11 | 0.287744E+10 |
Minimum of Months | 0.127628E+10 | 0.107372E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9621575.44 | 1954.29 |
Maximum of Months | 0.149825E+10 | 0.123743E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237402E+10 | 0.784831E+09 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.323435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1783740.30 | 0.212842E+10 |
February | 0.300332E+10 | 0.279317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101886E+09 | 0.235291E+10 |
March | 0.352563E+10 | 0.308124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382607E+09 | 0.155744E+10 |
April | 0.326447E+10 | 0.276737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104719E+10 | 0.732394E+09 |
May | 0.339505E+10 | 0.286372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307108E+10 | 0.103711E+09 |
June | 0.339505E+10 | 0.283369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404196E+10 | 25069672.90 |
July | 0.326447E+10 | 0.277095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530425E+10 | 0.00 |
August | 0.352563E+10 | 0.291438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537259E+10 | 0.00 |
September | 0.326447E+10 | 0.278948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359436E+10 | 20823573.42 |
October | 0.326447E+10 | 0.295774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200077E+10 | 0.186552E+09 |
November | 0.313390E+10 | 0.299980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554399E+09 | 0.752114E+09 |
December | 0.326447E+10 | 0.331280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25518499.20 | 0.185627E+10 |
Annual Sum or Average | 0.395654E+11 | 0.353187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254984E+11 | 0.971571E+10 |
Minimum of Months | 0.300332E+10 | 0.276737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1783740.30 | 0.00 |
Maximum of Months | 0.352563E+10 | 0.331280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537259E+10 | 0.235291E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.346301E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8104807.93 | 0.865822E+10 |
February | 0.690763E+10 | 0.308535E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114928E+09 | 0.114376E+11 |
March | 0.810895E+10 | 0.342819E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357334E+09 | 0.993294E+10 |
April | 0.750829E+10 | 0.310429E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103053E+09 | 0.617659E+10 |
May | 0.780862E+10 | 0.313785E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316705E+09 | 0.218927E+10 |
June | 0.780862E+10 | 0.307429E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327431E+09 | 0.197885E+10 |
July | 0.750829E+10 | 0.303892E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309057E+09 | 0.155765E+10 |
August | 0.810895E+10 | 0.324900E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254201E+09 | 0.176988E+10 |
September | 0.750829E+10 | 0.312776E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160850E+09 | 0.181918E+10 |
October | 0.750829E+10 | 0.328491E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57874024.23 | 0.299176E+10 |
November | 0.720796E+10 | 0.331097E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4247046.10 | 0.568070E+10 |
December | 0.750829E+10 | 0.356668E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11533209.83 | 0.944337E+10 |
Annual Sum or Average | 0.910005E+11 | 0.388712E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202532E+10 | 0.636360E+11 |
Minimum of Months | 0.690763E+10 | 0.303892E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4247046.10 | 0.155765E+10 |
Maximum of Months | 0.810895E+10 | 0.356668E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357334E+09 | 0.114376E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1355.05 | 02-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1318.13 | 23-JAN-13:00 | 4460.09 | 19-JAN-07:03 |
February | 1680.92 | 01-FEB-08:09 | 1355.05 | 01-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2631.60 | 07-FEB-13:00 | 3971.46 | 13-FEB-07:05 |
March | 1680.92 | 01-MAR-08:09 | 1355.05 | 01-MAR-08:09 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5181.78 | 27-MAR-11:10 | 3366.82 | 07-MAR-07:05 |
April | 1680.92 | 01-APR-07:10 | 1355.05 | 01-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6121.95 | 28-APR-12:00 | 2654.32 | 05-APR-06:40 |
May | 1680.92 | 01-MAY-07:10 | 1224.06 | 01-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5925.96 | 09-MAY-12:00 | 1293.77 | 01-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 1355.05 | 08-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7538.03 | 09-JUN-16:10 | 308.77 | 07-JUN-05:01 |
July | 1680.92 | 01-JUL-07:10 | 1355.05 | 14-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7526.40 | 21-JUL-17:00 | 10.05 | 03-JUL-04:00 |
August | 1680.92 | 01-AUG-07:10 | 1355.05 | 12-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7857.93 | 16-AUG-12:00 | 1.28 | 31-AUG-04:00 |
September | 1680.92 | 01-SEP-07:10 | 1355.05 | 01-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6143.48 | 05-SEP-16:10 | 377.33 | 25-SEP-05:01 |
October | 1680.92 | 02-OCT-07:10 | 1355.05 | 02-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5317.36 | 19-OCT-16:10 | 714.57 | 30-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 1355.05 | 01-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3370.35 | 01-NOV-16:10 | 2735.48 | 22-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1355.05 | 01-DEC-08:09 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1558.19 | 01-DEC-13:00 | 3676.85 | 18-DEC-07:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1224.06 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 1318.13 | 1.28 | |||||
Maximum of Months | 1680.92 | 1355.05 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 7857.93 | 4460.09 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3527.86 | 02-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.93 | 23-JAN-14:00 | 3842.79 | 19-JAN-09:00 |
February | 3955.50 | 01-FEB-08:09 | 3527.86 | 09-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2638.12 | 05-FEB-15:00 | 4693.99 | 10-FEB-16:30 |
March | 3955.50 | 01-MAR-08:09 | 3848.58 | 14-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5261.28 | 01-MAR-16:10 | 3529.41 | 25-MAR-09:00 |
April | 3955.50 | 01-APR-07:10 | 3527.86 | 18-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7226.22 | 28-APR-15:10 | 2358.40 | 04-APR-07:00 |
May | 3955.50 | 01-MAY-07:10 | 3395.71 | 10-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19494.32 | 21-MAY-12:51 | 1308.37 | 01-MAY-07:10 |
June | 3955.50 | 01-JUN-07:10 | 3207.15 | 02-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10184.02 | 09-JUN-15:40 | 883.76 | 07-JUN-06:10 |
July | 3955.50 | 01-JUL-07:10 | 3395.71 | 14-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10207.58 | 14-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 3955.50 | 01-AUG-07:10 | 3395.71 | 14-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8722.87 | 10-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 3955.50 | 01-SEP-07:10 | 3395.71 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7470.13 | 02-SEP-16:00 | 610.14 | 25-SEP-05:09 |
October | 3955.50 | 02-OCT-07:10 | 3527.86 | 20-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7954.05 | 19-OCT-15:10 | 1704.44 | 21-OCT-07:00 |
November | 3955.50 | 01-NOV-07:10 | 3527.86 | 04-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2937.75 | 01-NOV-15:10 | 2205.92 | 22-NOV-07:10 |
December | 3955.50 | 01-DEC-08:09 | 3848.58 | 09-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 958.83 | 10-DEC-12:50 | 3274.49 | 16-DEC-16:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3207.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.93 | 0.00 | ||||
Maximum of Months | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19494.32 | 4693.99 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 3961.65 | 02-JAN-16:00 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2066.79 | 23-JAN-13:10 | 15366.10 | 19-JAN-09:40 |
February | 9097.65 | 01-FEB-08:09 | 3961.65 | 09-FEB-16:00 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4632.79 | 05-FEB-12:05 | 22737.78 | 10-FEB-15:00 |
March | 9097.65 | 01-MAR-08:09 | 4115.84 | 14-MAR-08:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13466.23 | 01-MAR-11:00 | 35406.29 | 25-MAR-09:00 |
April | 9097.65 | 01-APR-07:10 | 3961.65 | 18-APR-07:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3246.18 | 25-APR-07:53 | 10803.76 | 04-APR-07:10 |
May | 9097.65 | 01-MAY-07:10 | 3301.38 | 10-MAY-07:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5623.59 | 22-MAY-07:53 | 8674.43 | 01-MAY-08:00 |
June | 9097.65 | 01-JUN-07:10 | 3169.37 | 01-JUN-06:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3297.00 | 09-JUN-15:00 | 6188.30 | 07-JUN-05:50 |
July | 9097.65 | 01-JUL-07:10 | 3301.38 | 14-JUL-07:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3921.45 | 15-JUL-09:55 | 3769.51 | 16-JUL-16:52 |
August | 9097.65 | 01-AUG-07:10 | 3301.38 | 05-AUG-07:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5129.76 | 16-AUG-10:53 | 4864.63 | 10-AUG-20:52 |
September | 9097.65 | 01-SEP-07:10 | 3301.38 | 01-SEP-07:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2204.10 | 26-SEP-11:00 | 5065.20 | 27-SEP-05:55 |
October | 9097.65 | 02-OCT-07:10 | 3631.52 | 30-OCT-07:10 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.39 | 19-OCT-09:53 | 9997.20 | 21-OCT-07:10 |
November | 9097.65 | 01-NOV-07:10 | 3961.65 | 06-NOV-16:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 893.92 | 19-NOV-19:00 | 8317.85 | 20-NOV-16:20 |
December | 9097.65 | 01-DEC-08:09 | 3961.65 | 01-DEC-16:49 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1517.01 | 10-DEC-11:55 | 25900.62 | 15-DEC-12:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 3169.37 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 893.92 | 3769.51 | |||||
Maximum of Months | 9097.65 | 4115.84 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 13466.23 | 35406.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19033.50 | 30-JAN-06:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.37 |
February | 20034.77 | 08-FEB-06:01 | 1294.31 | 356.97 | 3853.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.13 |
March | 26371.32 | 28-MAR-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.96 |
April | 26853.18 | 26-APR-05:01 | 1664.11 | 458.96 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.50 |
May | 26376.52 | 11-MAY-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 23.29 | 0.00 |
June | 24275.56 | 16-JUN-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 20.62 | 0.00 |
July | 24326.07 | 22-JUL-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 112.55 | 0.00 |
August | 21945.02 | 07-AUG-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 270.71 | 0.00 |
September | 21069.02 | 05-SEP-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 82.74 | 0.00 |
October | 26007.15 | 20-OCT-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 389.83 |
November | 24370.78 | 13-NOV-06:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.90 |
December | 23982.04 | 13-DEC-06:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 721.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19033.50 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26853.18 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 270.71 | 721.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4272.39 | 31-JAN-13:40 | 3955.50 | 2245.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.91 |
February | 28708.29 | 05-FEB-14:55 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2560.78 | 0.00 |
March | 61612.52 | 26-MAR-12:43 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1077.73 | 0.00 |
April | 70267.56 | 28-APR-17:06 | 0.00 | 2075.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3489.29 | 0.00 |
May | 75586.82 | 14-MAY-17:23 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2231.01 | 0.00 |
June | 75395.21 | 20-JUN-18:23 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2947.14 | 0.00 |
July | 72834.42 | 22-JUL-05:01 | 4351.05 | 2999.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1241.85 | 0.00 |
August | 70252.01 | 07-AUG-05:01 | 4351.05 | 2999.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 788.39 | 0.00 |
September | 69463.53 | 04-SEP-12:22 | 0.00 | 1499.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3361.80 | 0.00 |
October | 80241.62 | 29-OCT-14:53 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2026.47 | 0.00 |
November | 60804.64 | 11-NOV-14:13 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 901.92 | 0.00 |
December | 28776.67 | 03-DEC-13:35 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4272.39 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 80241.62 | 4351.05 | 2999.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3489.29 | 308.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 528.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1045.94 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3333.70 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2292.77 |
April | 0.00 | 01-APR-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2335.00 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 1056.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1305.89 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.54 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.40 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.09 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1139.73 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 528.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 535.34 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1762.29 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4203.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 528.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.54 | |
Maximum of Months | 0.00 | 0.00 | 1056.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4203.99 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.315611E+11 | 25692.01 | 30-JAN-15:50 | 23434814.85 | 3560.79 | 02-JAN-07:19 |
February | 0.297323E+11 | 32361.59 | 06-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.364371E+11 | 35802.94 | 27-MAR-15:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.398806E+11 | 38960.73 | 28-APR-12:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.535361E+11 | 44996.21 | 31-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.592954E+11 | 50488.81 | 09-JUN-15:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.666299E+11 | 51394.00 | 14-JUL-15:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.710169E+11 | 57142.72 | 10-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.592573E+11 | 47969.00 | 06-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.505828E+11 | 42737.26 | 07-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.392354E+11 | 39140.20 | 01-NOV-15:50 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.338553E+11 | 30923.09 | 01-DEC-15:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.571020E+12 | 23434814.85 | ||||
Minimum of Months | 0.297323E+11 | 25692.01 | 0.00 | 0.00 | ||
Maximum of Months | 0.710169E+11 | 57142.72 | 23434814.85 | 3560.79 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.790179E+10 | 0.609812E+10 | 0.112984E+11 | 0.00 | 0.317943E+10 | 0.00 | 0.00 | 0.111172E+10 | 0.00 | 0.00 | 0.00 | 0.197165E+10 | 0.00 |
February | 0.695224E+10 | 0.521477E+10 | 0.103734E+11 | 0.00 | 0.305359E+10 | 0.00 | 0.00 | 0.236463E+10 | 0.00 | 0.00 | 0.00 | 0.177370E+10 | 0.00 |
March | 0.774686E+10 | 0.534618E+10 | 0.121089E+11 | 0.00 | 0.411252E+10 | 0.00 | 0.00 | 0.517115E+10 | 0.00 | 0.00 | 0.00 | 0.195148E+10 | 0.00 |
April | 0.702515E+10 | 0.471938E+10 | 0.112578E+11 | 0.00 | 0.557664E+10 | 0.00 | 0.00 | 0.949312E+10 | 0.00 | 0.00 | 0.00 | 0.180857E+10 | 0.00 |
May | 0.716971E+10 | 0.451144E+10 | 0.117000E+11 | 0.00 | 0.944004E+10 | 0.00 | 0.00 | 0.189006E+11 | 0.00 | 0.00 | 0.00 | 0.181442E+10 | 0.00 |
June | 0.703311E+10 | 0.419601E+10 | 0.116594E+11 | 0.00 | 0.106154E+11 | 0.00 | 0.00 | 0.240639E+11 | 0.00 | 0.00 | 0.00 | 0.172763E+10 | 0.00 |
July | 0.690680E+10 | 0.439881E+10 | 0.112984E+11 | 0.00 | 0.119581E+11 | 0.00 | 0.00 | 0.303240E+11 | 0.00 | 0.00 | 0.00 | 0.174390E+10 | 0.00 |
August | 0.734211E+10 | 0.471350E+10 | 0.121016E+11 | 0.00 | 0.123753E+11 | 0.00 | 0.00 | 0.326919E+11 | 0.00 | 0.00 | 0.00 | 0.179252E+10 | 0.00 |
September | 0.703473E+10 | 0.497444E+10 | 0.112504E+11 | 0.00 | 0.103769E+11 | 0.00 | 0.00 | 0.238592E+11 | 0.00 | 0.00 | 0.00 | 0.176158E+10 | 0.00 |
October | 0.738854E+10 | 0.559131E+10 | 0.113057E+11 | 0.00 | 0.814265E+10 | 0.00 | 0.00 | 0.162916E+11 | 0.00 | 0.00 | 0.00 | 0.186291E+10 | 0.00 |
November | 0.743947E+10 | 0.579925E+10 | 0.108562E+11 | 0.00 | 0.474435E+10 | 0.00 | 0.00 | 0.854443E+10 | 0.00 | 0.00 | 0.00 | 0.185174E+10 | 0.00 |
December | 0.809287E+10 | 0.621406E+10 | 0.112984E+11 | 0.00 | 0.323984E+10 | 0.00 | 0.00 | 0.305233E+10 | 0.00 | 0.00 | 0.00 | 0.195779E+10 | 0.00 |
Annual Sum or Average | 0.880334E+11 | 0.617773E+11 | 0.136508E+12 | 0.00 | 0.868148E+11 | 0.00 | 0.00 | 0.175869E+12 | 0.00 | 0.00 | 0.00 | 0.220179E+11 | 0.00 |
Minimum of Months | 0.690680E+10 | 0.419601E+10 | 0.103734E+11 | 0.00 | 0.305359E+10 | 0.00 | 0.00 | 0.111172E+10 | 0.00 | 0.00 | 0.00 | 0.172763E+10 | 0.00 |
Maximum of Months | 0.809287E+10 | 0.621406E+10 | 0.121089E+11 | 0.00 | 0.123753E+11 | 0.00 | 0.00 | 0.326919E+11 | 0.00 | 0.00 | 0.00 | 0.197165E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 23434814.85 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 23434814.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 23434814.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 8712.41 | 20-JAN-16:00 | 5520.82 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 3275.11 | 02-JAN-07:19 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 8712.41 | 09-FEB-16:00 | 5520.82 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 5515.43 | 08-FEB-14:50 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 9319.46 | 14-MAR-08:09 | 5520.82 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 5697.35 | 27-MAR-11:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 8712.41 | 18-APR-07:10 | 5520.82 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 5934.85 | 28-APR-11:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 7921.15 | 10-MAY-07:10 | 5520.82 | 01-MAY-05:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 6332.57 | 31-MAY-16:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 7439.02 | 08-JUN-07:10 | 5520.82 | 01-JUN-05:10 | 10035.17 | 01-JUN-07:10 | 0.00 | 7335.00 | 09-JUN-16:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 8052.13 | 14-JUL-07:10 | 5520.82 | 01-JUL-05:10 | 10035.17 | 01-JUL-07:10 | 0.00 | 7526.76 | 14-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 8052.13 | 14-AUG-07:10 | 5520.82 | 01-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 8427.94 | 10-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 8052.13 | 01-SEP-07:10 | 5520.82 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 6791.84 | 08-SEP-15:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 8382.27 | 30-OCT-07:10 | 5520.82 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 5943.67 | 05-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 8712.41 | 29-NOV-16:49 | 5520.82 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 5795.53 | 01-NOV-11:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 8945.30 | 09-DEC-15:00 | 5520.82 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 5515.43 | 01-DEC-12:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 7439.02 | 5520.82 | 10035.17 | 0.00 | 3275.11 | 0.00 | 0.00 | |||||
Maximum of Months | 9319.46 | 5520.82 | 10035.17 | 0.00 | 8427.94 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 3935.33 | 23-JAN-13:00 | 0.00 | 0.00 | 0.00 | 1738.29 | 13-JAN-12:30 | 0.00 |
February | 9061.08 | 07-FEB-13:39 | 0.00 | 0.00 | 0.00 | 1735.49 | 01-FEB-12:00 | 0.00 |
March | 13602.03 | 27-MAR-11:50 | 0.00 | 0.00 | 0.00 | 1723.16 | 01-MAR-12:30 | 0.00 |
April | 18500.42 | 28-APR-11:00 | 0.00 | 0.00 | 0.00 | 1702.13 | 01-APR-11:50 | 0.00 |
May | 22126.47 | 31-MAY-16:10 | 0.00 | 0.00 | 0.00 | 1679.63 | 01-MAY-11:39 | 0.00 |
June | 26833.84 | 09-JUN-16:10 | 0.00 | 0.00 | 0.00 | 1661.14 | 01-JUN-11:30 | 0.00 |
July | 27738.00 | 14-JUL-16:10 | 0.00 | 0.00 | 0.00 | 1652.30 | 31-JUL-11:50 | 0.00 |
August | 32483.51 | 10-AUG-16:10 | 0.00 | 0.00 | 0.00 | 1664.06 | 31-AUG-11:09 | 0.00 |
September | 23966.19 | 06-SEP-16:10 | 0.00 | 0.00 | 0.00 | 1683.21 | 30-SEP-11:00 | 0.00 |
October | 18974.90 | 07-OCT-15:39 | 0.00 | 0.00 | 0.00 | 1706.30 | 31-OCT-11:39 | 0.00 |
November | 15472.67 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 1726.00 | 30-NOV-12:30 | 0.00 |
December | 8062.59 | 04-DEC-13:09 | 0.00 | 0.00 | 0.00 | 1736.93 | 29-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3935.33 | 0.00 | 0.00 | 0.00 | 1652.30 | 0.00 | ||
Maximum of Months | 32483.51 | 0.00 | 0.00 | 0.00 | 1738.29 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 25692.01 | 30-JAN-15:50 | 8250.41 | 10035.17 | 0.00 | 0.00 | 3210.14 | 0.00 | 0.00 | 2488.88 | 0.00 |
February | 32361.59 | 06-FEB-15:00 | 7622.56 | 10035.17 | 0.00 | 0.00 | 5515.43 | 0.00 | 0.00 | 7482.22 | 0.00 |
March | 35802.94 | 27-MAR-15:50 | 5729.49 | 10035.17 | 0.00 | 0.00 | 5515.43 | 0.00 | 0.00 | 12944.37 | 0.00 |
April | 38960.73 | 28-APR-12:20 | 5348.18 | 10035.17 | 0.00 | 0.00 | 5532.36 | 0.00 | 0.00 | 16383.13 | 0.00 |
May | 44996.21 | 31-MAY-15:00 | 5116.38 | 10035.17 | 0.00 | 0.00 | 6326.66 | 0.00 | 0.00 | 21951.55 | 0.00 |
June | 50488.81 | 09-JUN-15:50 | 5446.52 | 10035.17 | 0.00 | 0.00 | 7215.88 | 0.00 | 0.00 | 26226.05 | 0.00 |
July | 51394.00 | 14-JUL-15:20 | 5009.56 | 10035.17 | 0.00 | 0.00 | 7474.31 | 0.00 | 0.00 | 27311.70 | 0.00 |
August | 57142.72 | 10-AUG-15:00 | 4788.24 | 10035.17 | 0.00 | 0.00 | 8411.10 | 0.00 | 0.00 | 32343.65 | 0.00 |
September | 47969.00 | 06-SEP-15:00 | 5684.32 | 10035.17 | 0.00 | 0.00 | 6771.46 | 0.00 | 0.00 | 23910.09 | 0.00 |
October | 42737.26 | 07-OCT-15:00 | 6473.59 | 10035.17 | 0.00 | 0.00 | 5687.94 | 0.00 | 0.00 | 18966.81 | 0.00 |
November | 39140.20 | 01-NOV-15:50 | 6848.90 | 10035.17 | 0.00 | 0.00 | 5609.77 | 0.00 | 0.00 | 15221.27 | 0.00 |
December | 30923.09 | 01-DEC-15:09 | 6743.23 | 10035.17 | 0.00 | 0.00 | 5515.43 | 0.00 | 0.00 | 6929.86 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 25692.01 | 4788.24 | 10035.17 | 0.00 | 0.00 | 3210.14 | 0.00 | 0.00 | 2488.88 | 0.00 | |
Maximum of Months | 57142.72 | 8250.41 | 10035.17 | 0.00 | 0.00 | 8411.10 | 0.00 | 0.00 | 32343.65 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 3560.79 | 02-JAN-07:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 3560.79 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.49 | 0.50 | 24.49 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.57 | 1.33 | 24.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.58 | 3.00 | 24.58 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 25.16 | 8.33 | 25.02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 25.34 | 9.17 | 25.25 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 26.31 | 10.33 | 25.94 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 26.36 | 11.17 | 25.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 26.15 | 8.33 | 25.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 25.50 | 8.17 | 25.24 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.64 | 5.00 | 24.64 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.51 | 0.67 | 24.51 |
Annual Sum or Average | 0.00 | 0.00 | 74.50 | 25.70 | 66.00 | 25.44 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 26.36 | 11.17 | 25.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.26 | 0.00 | 27.26 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.44 | 0.00 | 27.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.51 | 0.00 | 27.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 49.67 | 27.63 | 0.00 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 70.67 | 27.61 | 0.50 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 109.33 | 27.73 | 3.33 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 108.17 | 27.73 | 4.33 | 27.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 73.17 | 27.61 | 1.17 | 27.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 36.50 | 27.55 | 0.00 | 27.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.42 | 0.00 | 27.42 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.28 | 0.00 | 27.28 |
Annual Sum or Average | 0.00 | 0.00 | 482.33 | 27.65 | 9.33 | 27.65 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 109.33 | 27.73 | 4.33 | 27.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 109.83 | 23.40 | 88.67 | 23.62 | 0.00 | 23.62 |
February | 28.00 | 23.25 | 176.83 | 23.81 | 0.83 | 23.82 |
March | 12.00 | 23.53 | 254.33 | 23.89 | 1.00 | 23.89 |
April | 3.00 | 24.08 | 295.83 | 23.91 | 3.00 | 23.91 |
May | 16.83 | 24.18 | 312.00 | 23.94 | 16.83 | 23.95 |
June | 45.67 | 24.13 | 312.00 | 23.97 | 45.67 | 23.98 |
July | 76.33 | 24.12 | 300.00 | 23.99 | 76.33 | 24.01 |
August | 86.33 | 24.15 | 324.00 | 24.00 | 86.33 | 24.03 |
September | 57.83 | 24.14 | 300.00 | 23.98 | 57.83 | 24.00 |
October | 28.17 | 24.12 | 300.00 | 23.95 | 28.17 | 23.96 |
November | 11.50 | 24.01 | 288.00 | 23.92 | 11.50 | 23.92 |
December | 20.67 | 23.48 | 228.00 | 23.87 | 2.00 | 23.87 |
Annual Sum or Average | 496.17 | 23.88 | 3179.67 | 23.92 | 329.50 | 23.94 |
Minimum of Months | 3.00 | 23.25 | 88.67 | 23.62 | 0.00 | 23.62 |
Maximum of Months | 109.83 | 24.18 | 324.00 | 24.00 | 86.33 | 24.03 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 111.67 | 23.35 | 187.83 | 24.99 | 25.00 | 25.02 |
February | 92.67 | 25.26 | 227.33 | 26.03 | 58.67 | 26.10 |
March | 154.33 | 26.47 | 309.17 | 26.43 | 146.67 | 26.47 |
April | 244.17 | 26.66 | 300.00 | 26.63 | 244.17 | 26.64 |
May | 290.33 | 26.71 | 312.00 | 26.71 | 290.33 | 26.71 |
June | 310.50 | 26.71 | 312.00 | 26.71 | 310.50 | 26.71 |
July | 299.67 | 26.71 | 300.00 | 26.71 | 299.67 | 26.71 |
August | 324.00 | 26.71 | 324.00 | 26.71 | 324.00 | 26.71 |
September | 298.50 | 26.71 | 300.00 | 26.71 | 298.50 | 26.71 |
October | 286.50 | 26.72 | 300.00 | 26.72 | 286.50 | 26.72 |
November | 246.33 | 26.68 | 288.00 | 26.65 | 246.33 | 26.66 |
December | 134.17 | 25.90 | 266.33 | 26.19 | 110.50 | 26.24 |
Annual Sum or Average | 2792.83 | 26.47 | 3426.67 | 26.53 | 2640.83 | 26.57 |
Minimum of Months | 92.67 | 23.35 | 187.83 | 24.99 | 25.00 | 25.02 |
Maximum of Months | 324.00 | 26.72 | 324.00 | 26.72 | 324.00 | 26.72 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 138.50 | 22.68 | 156.67 | 24.20 | 25.00 | 24.22 |
February | 174.50 | 26.55 | 222.17 | 26.85 | 130.33 | 27.10 |
March | 242.00 | 29.03 | 309.83 | 28.64 | 234.17 | 28.81 |
April | 287.67 | 30.47 | 300.00 | 30.39 | 287.67 | 30.41 |
May | 312.00 | 33.73 | 312.00 | 33.73 | 312.00 | 33.73 |
June | 312.00 | 34.97 | 312.00 | 34.97 | 312.00 | 34.97 |
July | 300.00 | 36.57 | 300.00 | 36.57 | 300.00 | 36.57 |
August | 324.00 | 36.87 | 324.00 | 36.87 | 324.00 | 36.87 |
September | 300.00 | 34.34 | 300.00 | 34.34 | 300.00 | 34.34 |
October | 300.00 | 32.01 | 300.00 | 32.01 | 300.00 | 32.01 |
November | 278.50 | 29.58 | 288.00 | 29.52 | 278.50 | 29.54 |
December | 186.67 | 26.90 | 259.50 | 27.01 | 153.33 | 27.21 |
Annual Sum or Average | 3155.83 | 32.03 | 3384.17 | 31.92 | 2957.00 | 32.15 |
Minimum of Months | 138.50 | 22.68 | 156.67 | 24.20 | 25.00 | 24.22 |
Maximum of Months | 324.00 | 36.87 | 324.00 | 36.87 | 324.00 | 36.87 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.403394E+10 | 0.972942E+09 | 243.25 | 0.327027E+10 | 0.763672E+09 | 0.00 | 1.00 | 30-JAN-06:02 | 0.00 | 01-JAN-00:10 | 32336.50 | 30-JAN-06:02 | 21335.84 | 30-JAN-06:02 | 11000.66 | 30-JAN-06:02 | 6885.71 | 30-JAN-06:02 | 0.00 | 01-JAN-00:10 |
February | 0.536528E+10 | 0.129361E+10 | 240.71 | 0.430269E+10 | 0.106258E+10 | 0.00 | 1.00 | 06-FEB-06:02 | 0.00 | 01-FEB-00:10 | 33626.96 | 09-FEB-06:01 | 22091.35 | 08-FEB-06:01 | 12853.64 | 09-FEB-06:03 | 7075.44 | 09-FEB-06:01 | 0.00 | 01-FEB-00:10 |
March | 0.797431E+10 | 0.195435E+10 | 296.84 | 0.666886E+10 | 0.130545E+10 | 0.00 | 1.00 | 01-MAR-06:02 | 0.00 | 01-MAR-00:10 | 33853.75 | 29-MAR-05:01 | 28760.24 | 28-MAR-05:01 | 13481.69 | 29-MAR-05:04 | 7106.86 | 29-MAR-05:01 | 0.00 | 01-MAR-00:10 |
April | 0.100018E+11 | 0.251928E+10 | 291.40 | 0.825900E+10 | 0.174280E+10 | 0.00 | 1.00 | 01-APR-05:02 | 0.00 | 01-APR-00:10 | 34144.08 | 10-APR-05:01 | 29115.79 | 26-APR-05:01 | 13944.43 | 20-APR-05:04 | 7146.23 | 10-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.145168E+11 | 0.384003E+10 | 325.11 | 0.118187E+11 | 0.269808E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:05 | 36261.44 | 24-MAY-05:01 | 28956.11 | 11-MAY-05:01 | 18253.94 | 24-MAY-05:04 | 7567.16 | 30-MAY-05:01 | 0.00 | 01-MAY-00:05 |
June | 0.177056E+11 | 0.470792E+10 | 326.09 | 0.130691E+11 | 0.463651E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 36329.45 | 08-JUN-05:02 | 26738.37 | 16-JUN-05:01 | 20275.91 | 19-JUN-05:07 | 7842.27 | 09-JUN-05:01 | 0.00 | 01-JUN-00:10 |
July | 0.202360E+11 | 0.547548E+10 | 345.82 | 0.140418E+11 | 0.619414E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 35321.28 | 06-JUL-05:01 | 27044.11 | 22-JUL-05:01 | 20607.75 | 06-JUL-05:08 | 7914.34 | 15-JUL-05:01 | 0.00 | 01-JUL-00:10 |
August | 0.226772E+11 | 0.614335E+10 | 358.64 | 0.155324E+11 | 0.714474E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 35321.28 | 31-AUG-05:04 | 24719.14 | 07-AUG-05:01 | 20823.19 | 08-AUG-05:10 | 8284.47 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 0.180973E+11 | 0.470026E+10 | 325.74 | 0.126736E+11 | 0.542380E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 36924.66 | 25-SEP-05:02 | 23443.69 | 05-SEP-05:01 | 20353.64 | 23-SEP-05:04 | 7714.53 | 07-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 0.144773E+11 | 0.361216E+10 | 308.74 | 0.108131E+11 | 0.366421E+10 | 0.00 | 1.00 | 01-OCT-11:58 | 0.00 | 01-OCT-00:10 | 36334.68 | 07-OCT-05:01 | 28028.26 | 20-OCT-05:01 | 20332.43 | 02-OCT-05:06 | 7560.62 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.106552E+11 | 0.257282E+10 | 281.90 | 0.812025E+10 | 0.253496E+10 | 0.00 | 1.00 | 01-NOV-05:01 | 0.00 | 01-NOV-00:10 | 35561.99 | 03-NOV-05:01 | 26109.82 | 18-NOV-06:01 | 15845.75 | 03-NOV-05:05 | 7325.04 | 03-NOV-05:01 | 0.00 | 01-NOV-00:10 |
December | 0.663800E+10 | 0.157968E+10 | 270.62 | 0.520850E+10 | 0.142950E+10 | 0.00 | 1.00 | 01-DEC-06:02 | 0.00 | 01-DEC-00:10 | 33503.96 | 06-DEC-06:02 | 26154.71 | 13-DEC-06:02 | 13486.75 | 06-DEC-06:03 | 7058.16 | 06-DEC-06:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.152379E+12 | 0.393719E+11 | 3614.88 | 0.113778E+12 | 0.386004E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.403394E+10 | 0.972942E+09 | 240.71 | 0.327027E+10 | 0.763672E+09 | 0.00 | 1.00 | 0.00 | 32336.50 | 21335.84 | 11000.66 | 6885.71 | 0.00 | |||||||
Maximum of Months | 0.226772E+11 | 0.614335E+10 | 358.64 | 0.155324E+11 | 0.714474E+10 | 0.00 | 1.00 | 0.00 | 36924.66 | 29115.79 | 20823.19 | 8284.47 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.490219E+09 | 0.138782E+09 | 49.17 | 0.372447E+09 | 0.117773E+09 | 0.00 | 0.19 | 28-JAN-14:00 | 0.00 | 01-JAN-00:10 | 7456.76 | 28-JAN-14:00 | 7456.76 | 28-JAN-14:00 | 2226.75 | 30-JAN-13:10 | 2249.81 | 28-JAN-14:00 | 0.00 | 01-JAN-00:10 |
February | 0.373901E+10 | 0.107102E+10 | 143.42 | 0.289598E+10 | 0.843027E+09 | 0.00 | 0.81 | 05-FEB-14:55 | 0.00 | 01-FEB-00:10 | 36983.00 | 05-FEB-14:55 | 33287.51 | 05-FEB-14:55 | 6941.72 | 07-FEB-16:10 | 10714.19 | 05-FEB-14:55 | 0.00 | 01-FEB-00:10 |
March | 0.110981E+11 | 0.321679E+10 | 250.21 | 0.912021E+10 | 0.197785E+10 | 0.00 | 1.00 | 23-MAR-17:10 | 0.00 | 01-MAR-00:10 | 73350.70 | 26-MAR-12:43 | 73350.70 | 26-MAR-12:43 | 12034.06 | 28-MAR-17:12 | 21951.72 | 26-MAR-12:43 | 0.00 | 01-MAR-00:10 |
April | 0.237268E+11 | 0.697384E+10 | 345.92 | 0.193749E+11 | 0.435186E+10 | 0.00 | 1.00 | 01-APR-17:10 | 0.00 | 01-APR-00:10 | 102701.62 | 30-APR-17:33 | 84348.27 | 30-APR-12:53 | 32925.02 | 30-APR-17:33 | 27329.09 | 30-APR-12:53 | 0.00 | 01-APR-00:10 |
May | 0.498689E+11 | 0.150605E+11 | 551.34 | 0.404001E+11 | 0.946880E+10 | 0.00 | 1.00 | 01-MAY-17:08 | 0.00 | 01-MAY-00:05 | 111245.76 | 24-MAY-05:08 | 90099.87 | 21-MAY-11:43 | 47175.65 | 24-MAY-05:08 | 30540.87 | 31-MAY-18:23 | 0.00 | 01-MAY-00:05 |
June | 0.648506E+11 | 0.193560E+11 | 579.08 | 0.473349E+11 | 0.175157E+11 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:13 | 113745.83 | 14-JUN-05:05 | 89189.73 | 20-JUN-18:23 | 46617.31 | 09-JUN-05:01 | 30670.03 | 09-JUN-17:05 | 0.00 | 01-JUN-00:10 |
July | 0.823708E+11 | 0.248485E+11 | 601.84 | 0.580985E+11 | 0.242723E+11 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:15 | 112090.91 | 04-JUL-23:03 | 88724.06 | 04-JUL-11:43 | 46720.79 | 04-JUL-23:03 | 31495.91 | 30-JUL-13:02 | 0.00 | 01-JUL-00:10 |
August | 0.882320E+11 | 0.265485E+11 | 608.78 | 0.611899E+11 | 0.270421E+11 | 0.00 | 1.00 | 01-AUG-00:23 | 0.00 | 01-AUG-00:13 | 115590.08 | 08-AUG-05:01 | 86529.45 | 06-AUG-10:23 | 52971.74 | 08-AUG-05:01 | 31845.08 | 10-AUG-17:42 | 0.00 | 01-AUG-00:10 |
September | 0.654859E+11 | 0.191589E+11 | 571.25 | 0.452428E+11 | 0.202431E+11 | 0.00 | 1.00 | 01-SEP-00:23 | 0.00 | 01-SEP-00:13 | 111786.27 | 08-SEP-17:06 | 87783.60 | 04-SEP-12:22 | 49889.20 | 23-SEP-05:09 | 30558.30 | 04-SEP-14:22 | 0.00 | 01-SEP-00:10 |
October | 0.438286E+11 | 0.126794E+11 | 516.40 | 0.323985E+11 | 0.114301E+11 | 0.00 | 1.00 | 01-OCT-08:35 | 0.00 | 01-OCT-00:15 | 112442.77 | 07-OCT-05:06 | 92339.97 | 29-OCT-14:53 | 44644.79 | 07-OCT-17:08 | 29276.23 | 07-OCT-17:08 | 0.00 | 01-OCT-00:10 |
November | 0.210672E+11 | 0.597161E+10 | 321.40 | 0.156540E+11 | 0.541320E+10 | 0.00 | 1.00 | 01-NOV-17:08 | 0.00 | 01-NOV-00:10 | 80219.27 | 01-NOV-17:08 | 70523.97 | 11-NOV-14:13 | 27877.67 | 01-NOV-17:08 | 21618.44 | 05-NOV-16:23 | 0.00 | 01-NOV-00:10 |
December | 0.527451E+10 | 0.147265E+10 | 176.33 | 0.383809E+10 | 0.143642E+10 | 0.00 | 0.82 | 03-DEC-13:35 | 0.00 | 01-DEC-00:10 | 40202.47 | 03-DEC-13:35 | 32354.46 | 03-DEC-13:35 | 8470.67 | 03-DEC-12:15 | 10791.38 | 03-DEC-12:55 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.460033E+12 | 0.136497E+12 | 4715.14 | 0.335920E+12 | 0.124112E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.490219E+09 | 0.138782E+09 | 49.17 | 0.372447E+09 | 0.117773E+09 | 0.00 | 0.19 | 0.00 | 7456.76 | 7456.76 | 2226.75 | 2249.81 | 0.00 | |||||||
Maximum of Months | 0.882320E+11 | 0.265485E+11 | 608.78 | 0.611899E+11 | 0.270421E+11 | 0.00 | 1.00 | 0.00 | 115590.08 | 92339.97 | 52971.74 | 31845.08 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 48.38 | 13.92 | 34.45 | 70.20 | 61.80 | 0.00 | 0.00 | 0.00 |
February | 55.17 | 15.79 | 39.38 | 86.38 | 55.69 | 0.00 | 0.00 | 0.00 |
March | 65.29 | 19.38 | 45.91 | 115.15 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 71.18 | 19.94 | 51.24 | 143.71 | 32.36 | 0.00 | 0.00 | 0.00 |
May | 77.44 | 23.12 | 54.32 | 186.26 | 11.44 | 0.00 | 0.00 | 0.00 |
June | 80.16 | 25.32 | 54.85 | 202.27 | 4.83 | 0.00 | 0.00 | 0.00 |
July | 73.56 | 21.06 | 52.50 | 209.74 | 0.69 | 0.00 | 0.00 | 0.00 |
August | 75.31 | 22.84 | 52.47 | 214.73 | 0.43 | 0.00 | 0.00 | 0.00 |
September | 71.75 | 22.56 | 49.19 | 179.10 | 6.73 | 0.00 | 0.00 | 0.00 |
October | 63.77 | 20.60 | 43.17 | 140.81 | 19.43 | 0.00 | 0.00 | 0.00 |
November | 54.89 | 17.97 | 36.92 | 103.47 | 40.14 | 0.00 | 0.00 | 0.00 |
December | 45.92 | 13.91 | 32.01 | 71.07 | 58.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.27 | 19.71 | 45.56 | 143.90 | 27.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 45.92 | 13.91 | 32.01 | 70.20 | 0.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.16 | 25.32 | 54.85 | 214.73 | 61.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 48.38 | 13.92 | 34.45 | 70.20 | 61.80 | 0.00 | 0.00 | 0.00 |
February | 55.17 | 15.79 | 39.38 | 86.38 | 55.69 | 0.00 | 0.00 | 0.00 |
March | 65.29 | 19.38 | 45.91 | 115.15 | 45.32 | 0.00 | 0.00 | 0.00 |
April | 71.18 | 19.94 | 51.24 | 143.71 | 32.36 | 0.00 | 0.00 | 0.00 |
May | 77.44 | 23.12 | 54.32 | 186.26 | 11.44 | 0.00 | 0.00 | 0.00 |
June | 80.16 | 25.32 | 54.85 | 202.27 | 4.83 | 0.00 | 0.00 | 0.00 |
July | 73.56 | 21.06 | 52.50 | 209.74 | 0.69 | 0.00 | 0.00 | 0.00 |
August | 75.31 | 22.84 | 52.47 | 214.73 | 0.43 | 0.00 | 0.00 | 0.00 |
September | 71.75 | 22.56 | 49.19 | 179.10 | 6.73 | 0.00 | 0.00 | 0.00 |
October | 63.77 | 20.60 | 43.17 | 140.81 | 19.43 | 0.00 | 0.00 | 0.00 |
November | 54.89 | 17.97 | 36.92 | 103.47 | 40.14 | 0.00 | 0.00 | 0.00 |
December | 45.92 | 13.91 | 32.01 | 71.07 | 58.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.27 | 19.71 | 45.56 | 143.90 | 27.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 45.92 | 13.91 | 32.01 | 70.20 | 0.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.16 | 25.32 | 54.85 | 214.73 | 61.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.85 | 0.00 | 15.85 | 17.58 | 36.60 | 0.00 | 0.00 | 0.00 |
February | 18.17 | 0.00 | 18.17 | 23.57 | 32.99 | 0.00 | 0.00 | 0.00 |
March | 20.88 | 0.00 | 20.87 | 33.94 | 26.60 | 0.00 | 0.00 | 0.00 |
April | 23.55 | 0.07 | 23.49 | 48.79 | 18.57 | 0.00 | 0.00 | 0.00 |
May | 26.54 | 0.84 | 25.70 | 72.33 | 6.29 | 0.00 | 0.00 | 0.00 |
June | 28.29 | 1.53 | 26.76 | 82.63 | 2.87 | 0.00 | 0.00 | 0.00 |
July | 26.00 | 0.74 | 25.26 | 89.87 | 0.40 | 0.00 | 0.00 | 0.00 |
August | 24.28 | 0.26 | 24.01 | 87.36 | 0.22 | 0.00 | 0.00 | 0.00 |
September | 22.06 | 0.01 | 22.05 | 65.75 | 3.75 | 0.00 | 0.00 | 0.00 |
October | 19.55 | 0.00 | 19.55 | 47.46 | 11.09 | 0.00 | 0.00 | 0.00 |
November | 16.78 | 0.00 | 16.78 | 30.33 | 23.29 | 0.00 | 0.00 | 0.00 |
December | 14.80 | 0.00 | 14.80 | 18.19 | 34.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21.41 | 0.29 | 21.12 | 51.65 | 16.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.80 | 0.00 | 14.80 | 17.58 | 0.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 28.29 | 1.53 | 26.76 | 89.87 | 36.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.85 | 0.00 | 15.85 | 17.58 | 36.59 | 0.00 | 0.00 | 0.00 |
February | 18.17 | 0.00 | 18.17 | 23.57 | 32.99 | 0.00 | 0.00 | 0.00 |
March | 20.87 | 0.00 | 20.87 | 33.94 | 26.60 | 0.00 | 0.00 | 0.00 |
April | 23.55 | 0.07 | 23.49 | 48.79 | 18.57 | 0.00 | 0.00 | 0.00 |
May | 26.53 | 0.84 | 25.70 | 72.33 | 6.29 | 0.00 | 0.00 | 0.00 |
June | 28.29 | 1.53 | 26.75 | 82.63 | 2.87 | 0.00 | 0.00 | 0.00 |
July | 26.00 | 0.74 | 25.26 | 89.87 | 0.40 | 0.00 | 0.00 | 0.00 |
August | 24.28 | 0.26 | 24.01 | 87.36 | 0.22 | 0.00 | 0.00 | 0.00 |
September | 22.05 | 0.01 | 22.05 | 65.75 | 3.75 | 0.00 | 0.00 | 0.00 |
October | 19.55 | 0.00 | 19.55 | 47.46 | 11.09 | 0.00 | 0.00 | 0.00 |
November | 16.78 | 0.00 | 16.78 | 30.33 | 23.29 | 0.00 | 0.00 | 0.00 |
December | 14.79 | 0.00 | 14.79 | 18.19 | 34.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21.41 | 0.29 | 21.12 | 51.65 | 16.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.79 | 0.00 | 14.79 | 17.58 | 0.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 28.29 | 1.53 | 26.75 | 89.87 | 36.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.03 | 13.41 | 21.62 | 53.84 | 32.77 | 0.50 | 0.00 | 0.00 |
February | 42.56 | 17.42 | 25.13 | 67.60 | 30.58 | 0.00 | 0.00 | 0.00 |
March | 51.54 | 21.72 | 29.83 | 86.15 | 28.16 | 0.00 | 0.00 | 0.00 |
April | 60.79 | 27.06 | 33.74 | 108.33 | 23.66 | 0.00 | 0.00 | 0.00 |
May | 69.00 | 33.67 | 35.32 | 131.36 | 13.36 | 0.00 | 0.00 | 0.00 |
June | 71.94 | 36.71 | 35.22 | 138.92 | 10.34 | 0.00 | 0.00 | 0.00 |
July | 69.80 | 35.55 | 34.25 | 140.50 | 5.08 | 0.00 | 0.00 | 0.00 |
August | 66.47 | 32.79 | 33.68 | 134.37 | 4.69 | 0.00 | 0.00 | 0.00 |
September | 59.63 | 28.72 | 30.92 | 115.57 | 11.37 | 0.00 | 0.00 | 0.00 |
October | 50.11 | 23.59 | 26.52 | 91.97 | 18.95 | 0.00 | 0.00 | 0.00 |
November | 39.73 | 17.37 | 22.36 | 67.07 | 28.29 | 0.00 | 0.00 | 0.00 |
December | 32.53 | 12.62 | 19.91 | 50.27 | 32.75 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 25.09 | 29.06 | 98.99 | 19.93 | 4.00 | 0.00 | 0.00 |
Minimum of Months | 32.53 | 12.62 | 19.91 | 50.27 | 4.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.94 | 36.71 | 35.32 | 140.50 | 32.77 | 3.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.03 | 13.41 | 21.62 | 53.84 | 32.77 | 0.50 | 0.00 | 0.00 |
February | 42.56 | 17.42 | 25.13 | 67.60 | 30.58 | 0.00 | 0.00 | 0.00 |
March | 51.54 | 21.72 | 29.83 | 86.15 | 28.16 | 0.00 | 0.00 | 0.00 |
April | 60.79 | 27.06 | 33.74 | 108.33 | 23.66 | 0.00 | 0.00 | 0.00 |
May | 69.00 | 33.67 | 35.32 | 131.36 | 13.36 | 0.00 | 0.00 | 0.00 |
June | 71.94 | 36.71 | 35.22 | 138.92 | 10.34 | 0.00 | 0.00 | 0.00 |
July | 69.80 | 35.55 | 34.25 | 140.50 | 5.08 | 0.00 | 0.00 | 0.00 |
August | 66.47 | 32.79 | 33.68 | 134.37 | 4.69 | 0.00 | 0.00 | 0.00 |
September | 59.63 | 28.72 | 30.92 | 115.57 | 11.37 | 0.00 | 0.00 | 0.00 |
October | 50.11 | 23.59 | 26.52 | 91.97 | 18.95 | 0.00 | 0.00 | 0.00 |
November | 39.73 | 17.37 | 22.36 | 67.07 | 28.29 | 0.00 | 0.00 | 0.00 |
December | 32.53 | 12.62 | 19.91 | 50.27 | 32.75 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 25.09 | 29.06 | 98.99 | 19.93 | 4.00 | 0.00 | 0.00 |
Minimum of Months | 32.53 | 12.62 | 19.91 | 50.27 | 4.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.94 | 36.71 | 35.32 | 140.50 | 32.77 | 3.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.03 | 13.41 | 21.62 | 53.84 | 32.77 | 0.50 | 0.00 | 0.00 |
February | 42.56 | 17.42 | 25.13 | 67.60 | 30.58 | 0.00 | 0.00 | 0.00 |
March | 51.54 | 21.72 | 29.83 | 86.15 | 28.16 | 0.00 | 0.00 | 0.00 |
April | 60.79 | 27.06 | 33.74 | 108.33 | 23.66 | 0.00 | 0.00 | 0.00 |
May | 69.00 | 33.67 | 35.32 | 131.36 | 13.36 | 0.00 | 0.00 | 0.00 |
June | 71.94 | 36.71 | 35.22 | 138.92 | 10.34 | 0.00 | 0.00 | 0.00 |
July | 69.80 | 35.55 | 34.25 | 140.50 | 5.08 | 0.00 | 0.00 | 0.00 |
August | 66.47 | 32.79 | 33.68 | 134.37 | 4.69 | 0.00 | 0.00 | 0.00 |
September | 59.63 | 28.72 | 30.92 | 115.57 | 11.37 | 0.00 | 0.00 | 0.00 |
October | 50.11 | 23.59 | 26.52 | 91.97 | 18.95 | 0.00 | 0.00 | 0.00 |
November | 39.73 | 17.37 | 22.36 | 67.07 | 28.29 | 0.00 | 0.00 | 0.00 |
December | 32.53 | 12.62 | 19.91 | 50.27 | 32.75 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 25.09 | 29.06 | 98.99 | 19.93 | 4.00 | 0.00 | 0.00 |
Minimum of Months | 32.53 | 12.62 | 19.91 | 50.27 | 4.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.94 | 36.71 | 35.32 | 140.50 | 32.77 | 3.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.03 | 13.41 | 21.62 | 53.84 | 32.77 | 0.50 | 0.00 | 0.00 |
February | 42.56 | 17.42 | 25.13 | 67.60 | 30.58 | 0.00 | 0.00 | 0.00 |
March | 51.54 | 21.72 | 29.83 | 86.15 | 28.16 | 0.00 | 0.00 | 0.00 |
April | 60.79 | 27.06 | 33.74 | 108.33 | 23.66 | 0.00 | 0.00 | 0.00 |
May | 69.00 | 33.67 | 35.32 | 131.36 | 13.36 | 0.00 | 0.00 | 0.00 |
June | 71.94 | 36.71 | 35.22 | 138.92 | 10.34 | 0.00 | 0.00 | 0.00 |
July | 69.80 | 35.55 | 34.25 | 140.50 | 5.08 | 0.00 | 0.00 | 0.00 |
August | 66.47 | 32.79 | 33.68 | 134.37 | 4.69 | 0.00 | 0.00 | 0.00 |
September | 59.63 | 28.72 | 30.92 | 115.57 | 11.37 | 0.00 | 0.00 | 0.00 |
October | 50.11 | 23.59 | 26.52 | 91.97 | 18.95 | 0.00 | 0.00 | 0.00 |
November | 39.73 | 17.37 | 22.36 | 67.07 | 28.29 | 0.00 | 0.00 | 0.00 |
December | 32.53 | 12.62 | 19.91 | 50.27 | 32.75 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 25.09 | 29.06 | 98.99 | 19.93 | 4.00 | 0.00 | 0.00 |
Minimum of Months | 32.53 | 12.62 | 19.91 | 50.27 | 4.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.94 | 36.71 | 35.32 | 140.50 | 32.77 | 3.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.03 | 13.41 | 21.62 | 53.84 | 32.77 | 0.50 | 0.00 | 0.00 |
February | 42.56 | 17.42 | 25.13 | 67.60 | 30.58 | 0.00 | 0.00 | 0.00 |
March | 51.54 | 21.72 | 29.83 | 86.15 | 28.16 | 0.00 | 0.00 | 0.00 |
April | 60.79 | 27.06 | 33.74 | 108.33 | 23.66 | 0.00 | 0.00 | 0.00 |
May | 69.00 | 33.67 | 35.32 | 131.36 | 13.36 | 0.00 | 0.00 | 0.00 |
June | 71.94 | 36.71 | 35.22 | 138.92 | 10.34 | 0.00 | 0.00 | 0.00 |
July | 69.80 | 35.55 | 34.25 | 140.50 | 5.08 | 0.00 | 0.00 | 0.00 |
August | 66.47 | 32.79 | 33.68 | 134.37 | 4.69 | 0.00 | 0.00 | 0.00 |
September | 59.63 | 28.72 | 30.92 | 115.57 | 11.37 | 0.00 | 0.00 | 0.00 |
October | 50.11 | 23.59 | 26.52 | 91.97 | 18.95 | 0.00 | 0.00 | 0.00 |
November | 39.73 | 17.37 | 22.36 | 67.07 | 28.29 | 0.00 | 0.00 | 0.00 |
December | 32.53 | 12.62 | 19.91 | 50.27 | 32.75 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 25.09 | 29.06 | 98.99 | 19.93 | 4.00 | 0.00 | 0.00 |
Minimum of Months | 32.53 | 12.62 | 19.91 | 50.27 | 4.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.94 | 36.71 | 35.32 | 140.50 | 32.77 | 3.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.03 | 13.41 | 21.62 | 53.84 | 32.77 | 0.50 | 0.00 | 0.00 |
February | 42.56 | 17.42 | 25.13 | 67.60 | 30.58 | 0.00 | 0.00 | 0.00 |
March | 51.54 | 21.72 | 29.83 | 86.15 | 28.16 | 0.00 | 0.00 | 0.00 |
April | 60.79 | 27.06 | 33.74 | 108.33 | 23.66 | 0.00 | 0.00 | 0.00 |
May | 69.00 | 33.67 | 35.32 | 131.36 | 13.36 | 0.00 | 0.00 | 0.00 |
June | 71.94 | 36.71 | 35.22 | 138.92 | 10.34 | 0.00 | 0.00 | 0.00 |
July | 69.80 | 35.55 | 34.25 | 140.50 | 5.08 | 0.00 | 0.00 | 0.00 |
August | 66.47 | 32.79 | 33.68 | 134.37 | 4.69 | 0.00 | 0.00 | 0.00 |
September | 59.63 | 28.72 | 30.92 | 115.57 | 11.37 | 0.00 | 0.00 | 0.00 |
October | 50.11 | 23.59 | 26.52 | 91.97 | 18.95 | 0.00 | 0.00 | 0.00 |
November | 39.73 | 17.37 | 22.36 | 67.07 | 28.29 | 0.00 | 0.00 | 0.00 |
December | 32.53 | 12.62 | 19.91 | 50.27 | 32.75 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 25.09 | 29.06 | 98.99 | 19.93 | 4.00 | 0.00 | 0.00 |
Minimum of Months | 32.53 | 12.62 | 19.91 | 50.27 | 4.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.94 | 36.71 | 35.32 | 140.50 | 32.77 | 3.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.03 | 13.41 | 21.62 | 53.84 | 32.77 | 0.50 | 0.00 | 0.00 |
February | 42.56 | 17.42 | 25.13 | 67.60 | 30.58 | 0.00 | 0.00 | 0.00 |
March | 51.54 | 21.72 | 29.83 | 86.15 | 28.16 | 0.00 | 0.00 | 0.00 |
April | 60.79 | 27.06 | 33.74 | 108.33 | 23.66 | 0.00 | 0.00 | 0.00 |
May | 69.00 | 33.67 | 35.32 | 131.36 | 13.36 | 0.00 | 0.00 | 0.00 |
June | 71.94 | 36.71 | 35.22 | 138.92 | 10.34 | 0.00 | 0.00 | 0.00 |
July | 69.80 | 35.55 | 34.25 | 140.50 | 5.08 | 0.00 | 0.00 | 0.00 |
August | 66.47 | 32.79 | 33.68 | 134.37 | 4.69 | 0.00 | 0.00 | 0.00 |
September | 59.63 | 28.72 | 30.92 | 115.57 | 11.37 | 0.00 | 0.00 | 0.00 |
October | 50.11 | 23.59 | 26.52 | 91.97 | 18.95 | 0.00 | 0.00 | 0.00 |
November | 39.73 | 17.37 | 22.36 | 67.07 | 28.29 | 0.00 | 0.00 | 0.00 |
December | 32.53 | 12.62 | 19.91 | 50.27 | 32.75 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 25.09 | 29.06 | 98.99 | 19.93 | 4.00 | 0.00 | 0.00 |
Minimum of Months | 32.53 | 12.62 | 19.91 | 50.27 | 4.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.94 | 36.71 | 35.32 | 140.50 | 32.77 | 3.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.03 | 13.41 | 21.62 | 53.84 | 32.77 | 0.50 | 0.00 | 0.00 |
February | 42.56 | 17.42 | 25.13 | 67.60 | 30.58 | 0.00 | 0.00 | 0.00 |
March | 51.54 | 21.72 | 29.83 | 86.15 | 28.16 | 0.00 | 0.00 | 0.00 |
April | 60.79 | 27.06 | 33.74 | 108.33 | 23.66 | 0.00 | 0.00 | 0.00 |
May | 69.00 | 33.67 | 35.32 | 131.36 | 13.36 | 0.00 | 0.00 | 0.00 |
June | 71.94 | 36.71 | 35.22 | 138.92 | 10.34 | 0.00 | 0.00 | 0.00 |
July | 69.80 | 35.55 | 34.25 | 140.50 | 5.08 | 0.00 | 0.00 | 0.00 |
August | 66.47 | 32.79 | 33.68 | 134.37 | 4.69 | 0.00 | 0.00 | 0.00 |
September | 59.63 | 28.72 | 30.92 | 115.57 | 11.37 | 0.00 | 0.00 | 0.00 |
October | 50.11 | 23.59 | 26.52 | 91.97 | 18.95 | 0.00 | 0.00 | 0.00 |
November | 39.73 | 17.37 | 22.36 | 67.07 | 28.29 | 0.00 | 0.00 | 0.00 |
December | 32.53 | 12.62 | 19.91 | 50.27 | 32.75 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 25.09 | 29.06 | 98.99 | 19.93 | 4.00 | 0.00 | 0.00 |
Minimum of Months | 32.53 | 12.62 | 19.91 | 50.27 | 4.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.94 | 36.71 | 35.32 | 140.50 | 32.77 | 3.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.03 | 13.41 | 21.62 | 53.84 | 32.77 | 0.50 | 0.00 | 0.00 |
February | 42.56 | 17.42 | 25.13 | 67.60 | 30.58 | 0.00 | 0.00 | 0.00 |
March | 51.54 | 21.72 | 29.83 | 86.15 | 28.16 | 0.00 | 0.00 | 0.00 |
April | 60.79 | 27.06 | 33.74 | 108.33 | 23.66 | 0.00 | 0.00 | 0.00 |
May | 69.00 | 33.67 | 35.32 | 131.36 | 13.36 | 0.00 | 0.00 | 0.00 |
June | 71.94 | 36.71 | 35.22 | 138.92 | 10.34 | 0.00 | 0.00 | 0.00 |
July | 69.80 | 35.55 | 34.25 | 140.50 | 5.08 | 0.00 | 0.00 | 0.00 |
August | 66.47 | 32.79 | 33.68 | 134.37 | 4.69 | 0.00 | 0.00 | 0.00 |
September | 59.63 | 28.72 | 30.92 | 115.57 | 11.37 | 0.00 | 0.00 | 0.00 |
October | 50.11 | 23.59 | 26.52 | 91.97 | 18.95 | 0.00 | 0.00 | 0.00 |
November | 39.73 | 17.37 | 22.36 | 67.07 | 28.29 | 0.00 | 0.00 | 0.00 |
December | 32.53 | 12.62 | 19.91 | 50.27 | 32.75 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 25.09 | 29.06 | 98.99 | 19.93 | 4.00 | 0.00 | 0.00 |
Minimum of Months | 32.53 | 12.62 | 19.91 | 50.27 | 4.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.94 | 36.71 | 35.32 | 140.50 | 32.77 | 3.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.03 | 13.41 | 21.62 | 53.84 | 32.77 | 0.50 | 0.00 | 0.00 |
February | 42.56 | 17.42 | 25.13 | 67.60 | 30.58 | 0.00 | 0.00 | 0.00 |
March | 51.54 | 21.72 | 29.83 | 86.15 | 28.16 | 0.00 | 0.00 | 0.00 |
April | 60.79 | 27.06 | 33.74 | 108.33 | 23.66 | 0.00 | 0.00 | 0.00 |
May | 69.00 | 33.67 | 35.32 | 131.36 | 13.36 | 0.00 | 0.00 | 0.00 |
June | 71.94 | 36.71 | 35.22 | 138.92 | 10.34 | 0.00 | 0.00 | 0.00 |
July | 69.80 | 35.55 | 34.25 | 140.50 | 5.08 | 0.00 | 0.00 | 0.00 |
August | 66.47 | 32.79 | 33.68 | 134.37 | 4.69 | 0.00 | 0.00 | 0.00 |
September | 59.63 | 28.72 | 30.92 | 115.57 | 11.37 | 0.00 | 0.00 | 0.00 |
October | 50.11 | 23.59 | 26.52 | 91.97 | 18.95 | 0.00 | 0.00 | 0.00 |
November | 39.73 | 17.37 | 22.36 | 67.07 | 28.29 | 0.00 | 0.00 | 0.00 |
December | 32.53 | 12.62 | 19.91 | 50.27 | 32.75 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 25.09 | 29.06 | 98.99 | 19.93 | 4.00 | 0.00 | 0.00 |
Minimum of Months | 32.53 | 12.62 | 19.91 | 50.27 | 4.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.94 | 36.71 | 35.32 | 140.50 | 32.77 | 3.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.03 | 13.41 | 21.62 | 53.84 | 32.77 | 0.50 | 0.00 | 0.00 |
February | 42.56 | 17.42 | 25.13 | 67.60 | 30.58 | 0.00 | 0.00 | 0.00 |
March | 51.54 | 21.72 | 29.83 | 86.15 | 28.16 | 0.00 | 0.00 | 0.00 |
April | 60.79 | 27.06 | 33.74 | 108.33 | 23.66 | 0.00 | 0.00 | 0.00 |
May | 69.00 | 33.67 | 35.32 | 131.36 | 13.36 | 0.00 | 0.00 | 0.00 |
June | 71.94 | 36.71 | 35.22 | 138.92 | 10.34 | 0.00 | 0.00 | 0.00 |
July | 69.80 | 35.55 | 34.25 | 140.50 | 5.08 | 0.00 | 0.00 | 0.00 |
August | 66.47 | 32.79 | 33.68 | 134.37 | 4.69 | 0.00 | 0.00 | 0.00 |
September | 59.63 | 28.72 | 30.92 | 115.57 | 11.37 | 0.00 | 0.00 | 0.00 |
October | 50.11 | 23.59 | 26.52 | 91.97 | 18.95 | 0.00 | 0.00 | 0.00 |
November | 39.73 | 17.37 | 22.36 | 67.07 | 28.29 | 0.00 | 0.00 | 0.00 |
December | 32.53 | 12.62 | 19.91 | 50.27 | 32.75 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 25.09 | 29.06 | 98.99 | 19.93 | 4.00 | 0.00 | 0.00 |
Minimum of Months | 32.53 | 12.62 | 19.91 | 50.27 | 4.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.94 | 36.71 | 35.32 | 140.50 | 32.77 | 3.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.03 | 13.41 | 21.62 | 53.84 | 32.77 | 0.50 | 0.00 | 0.00 |
February | 42.56 | 17.42 | 25.13 | 67.60 | 30.58 | 0.00 | 0.00 | 0.00 |
March | 51.54 | 21.72 | 29.83 | 86.15 | 28.16 | 0.00 | 0.00 | 0.00 |
April | 60.79 | 27.06 | 33.74 | 108.33 | 23.66 | 0.00 | 0.00 | 0.00 |
May | 69.00 | 33.67 | 35.32 | 131.36 | 13.36 | 0.00 | 0.00 | 0.00 |
June | 71.94 | 36.71 | 35.22 | 138.92 | 10.34 | 0.00 | 0.00 | 0.00 |
July | 69.80 | 35.55 | 34.25 | 140.50 | 5.08 | 0.00 | 0.00 | 0.00 |
August | 66.47 | 32.79 | 33.68 | 134.37 | 4.69 | 0.00 | 0.00 | 0.00 |
September | 59.63 | 28.72 | 30.92 | 115.57 | 11.37 | 0.00 | 0.00 | 0.00 |
October | 50.11 | 23.59 | 26.52 | 91.97 | 18.95 | 0.00 | 0.00 | 0.00 |
November | 39.73 | 17.37 | 22.36 | 67.07 | 28.29 | 0.00 | 0.00 | 0.00 |
December | 32.53 | 12.62 | 19.91 | 50.27 | 32.75 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 25.09 | 29.06 | 98.99 | 19.93 | 4.00 | 0.00 | 0.00 |
Minimum of Months | 32.53 | 12.62 | 19.91 | 50.27 | 4.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.94 | 36.71 | 35.32 | 140.50 | 32.77 | 3.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.03 | 13.41 | 21.62 | 53.84 | 32.77 | 0.50 | 0.00 | 0.00 |
February | 42.56 | 17.42 | 25.13 | 67.60 | 30.58 | 0.00 | 0.00 | 0.00 |
March | 51.54 | 21.72 | 29.83 | 86.15 | 28.16 | 0.00 | 0.00 | 0.00 |
April | 60.79 | 27.06 | 33.74 | 108.33 | 23.66 | 0.00 | 0.00 | 0.00 |
May | 69.00 | 33.67 | 35.32 | 131.36 | 13.36 | 0.00 | 0.00 | 0.00 |
June | 71.94 | 36.71 | 35.22 | 138.92 | 10.34 | 0.00 | 0.00 | 0.00 |
July | 69.80 | 35.55 | 34.25 | 140.50 | 5.08 | 0.00 | 0.00 | 0.00 |
August | 66.47 | 32.79 | 33.68 | 134.37 | 4.69 | 0.00 | 0.00 | 0.00 |
September | 59.63 | 28.72 | 30.92 | 115.57 | 11.37 | 0.00 | 0.00 | 0.00 |
October | 50.11 | 23.59 | 26.52 | 91.97 | 18.95 | 0.00 | 0.00 | 0.00 |
November | 39.73 | 17.37 | 22.36 | 67.07 | 28.29 | 0.00 | 0.00 | 0.00 |
December | 32.53 | 12.62 | 19.91 | 50.27 | 32.75 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 25.09 | 29.06 | 98.99 | 19.93 | 4.00 | 0.00 | 0.00 |
Minimum of Months | 32.53 | 12.62 | 19.91 | 50.27 | 4.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.94 | 36.71 | 35.32 | 140.50 | 32.77 | 3.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.03 | 13.41 | 21.62 | 53.84 | 32.77 | 0.50 | 0.00 | 0.00 |
February | 42.56 | 17.42 | 25.13 | 67.60 | 30.58 | 0.00 | 0.00 | 0.00 |
March | 51.54 | 21.72 | 29.83 | 86.15 | 28.16 | 0.00 | 0.00 | 0.00 |
April | 60.79 | 27.06 | 33.74 | 108.33 | 23.66 | 0.00 | 0.00 | 0.00 |
May | 69.00 | 33.67 | 35.32 | 131.36 | 13.36 | 0.00 | 0.00 | 0.00 |
June | 71.94 | 36.71 | 35.22 | 138.92 | 10.34 | 0.00 | 0.00 | 0.00 |
July | 69.80 | 35.55 | 34.25 | 140.50 | 5.08 | 0.00 | 0.00 | 0.00 |
August | 66.47 | 32.79 | 33.68 | 134.37 | 4.69 | 0.00 | 0.00 | 0.00 |
September | 59.63 | 28.72 | 30.92 | 115.57 | 11.37 | 0.00 | 0.00 | 0.00 |
October | 50.11 | 23.59 | 26.52 | 91.97 | 18.95 | 0.00 | 0.00 | 0.00 |
November | 39.73 | 17.37 | 22.36 | 67.07 | 28.29 | 0.00 | 0.00 | 0.00 |
December | 32.53 | 12.62 | 19.91 | 50.27 | 32.75 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 25.09 | 29.06 | 98.99 | 19.93 | 4.00 | 0.00 | 0.00 |
Minimum of Months | 32.53 | 12.62 | 19.91 | 50.27 | 4.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.94 | 36.71 | 35.32 | 140.50 | 32.77 | 3.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.71 | 51.82 | 28.17 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 106.08 | 51.33 | 10.67 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.56 | 51.28 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.78 | 48.04 | 7.00 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.57 | 36.13 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.29 | 34.48 | 9.00 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.83 | 30.83 | 2.67 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.62 | 31.64 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.90 | 36.81 | 24.50 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.14 | 45.11 | 36.00 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.39 | 55.18 | 9.50 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 79.13 | 55.11 | 27.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.67 | 43.92 | 161.83 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 79.13 | 30.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.29 | 55.18 | 36.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129580E+09 | 37296421.77 | 92283737.01 | 0.188028E+09 | 0.165526E+09 |
February | 0.133465E+09 | 38187796.51 | 95277149.95 | 0.208972E+09 | 0.134726E+09 |
March | 0.174872E+09 | 51901583.78 | 0.122970E+09 | 0.308417E+09 | 0.121377E+09 |
April | 0.184492E+09 | 51682616.32 | 0.132810E+09 | 0.372504E+09 | 83871039.03 |
May | 0.207429E+09 | 61931043.89 | 0.145497E+09 | 0.498873E+09 | 30630817.92 |
June | 0.207786E+09 | 65618834.09 | 0.142167E+09 | 0.524278E+09 | 12526580.28 |
July | 0.197015E+09 | 56402515.75 | 0.140612E+09 | 0.561763E+09 | 1840615.03 |
August | 0.201714E+09 | 61165381.08 | 0.140548E+09 | 0.575122E+09 | 1157185.15 |
September | 0.185974E+09 | 58466131.95 | 0.127508E+09 | 0.464215E+09 | 17449797.11 |
October | 0.170810E+09 | 55178373.88 | 0.115632E+09 | 0.377151E+09 | 52042577.80 |
November | 0.142273E+09 | 46586452.21 | 95686220.86 | 0.268202E+09 | 0.104047E+09 |
December | 0.123002E+09 | 37258343.02 | 85743945.89 | 0.190355E+09 | 0.156723E+09 |
Annual Sum or Average | 0.205841E+10 | 0.621675E+09 | 0.143674E+10 | 0.453788E+10 | 0.881918E+09 |
Minimum of Months | 0.123002E+09 | 37258343.02 | 85743945.89 | 0.188028E+09 | 1157185.15 |
Maximum of Months | 0.207786E+09 | 65618834.09 | 0.145497E+09 | 0.575122E+09 | 0.165526E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129580E+09 | 37296421.77 | 92283737.01 | 0.188028E+09 | 0.165526E+09 |
February | 0.133465E+09 | 38187796.51 | 95277149.95 | 0.208972E+09 | 0.134726E+09 |
March | 0.174872E+09 | 51901583.78 | 0.122970E+09 | 0.308417E+09 | 0.121377E+09 |
April | 0.184492E+09 | 51682616.32 | 0.132810E+09 | 0.372504E+09 | 83871039.03 |
May | 0.207429E+09 | 61931043.89 | 0.145497E+09 | 0.498873E+09 | 30630817.92 |
June | 0.207786E+09 | 65618834.09 | 0.142167E+09 | 0.524278E+09 | 12526580.28 |
July | 0.197015E+09 | 56402515.75 | 0.140612E+09 | 0.561763E+09 | 1840615.03 |
August | 0.201714E+09 | 61165381.08 | 0.140548E+09 | 0.575122E+09 | 1157185.15 |
September | 0.185974E+09 | 58466131.95 | 0.127508E+09 | 0.464215E+09 | 17449797.11 |
October | 0.170810E+09 | 55178373.88 | 0.115632E+09 | 0.377151E+09 | 52042577.80 |
November | 0.142273E+09 | 46586452.21 | 95686220.86 | 0.268202E+09 | 0.104047E+09 |
December | 0.123002E+09 | 37258343.02 | 85743945.89 | 0.190355E+09 | 0.156723E+09 |
Annual Sum or Average | 0.205841E+10 | 0.621675E+09 | 0.143674E+10 | 0.453788E+10 | 0.881918E+09 |
Minimum of Months | 0.123002E+09 | 37258343.02 | 85743945.89 | 0.188028E+09 | 1157185.15 |
Maximum of Months | 0.207786E+09 | 65618834.09 | 0.145497E+09 | 0.575122E+09 | 0.165526E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42456455.33 | 0.00 | 42456455.33 | 47092029.02 | 98016432.62 |
February | 43957531.69 | 0.00 | 43957531.69 | 57014718.97 | 79802063.85 |
March | 55911838.82 | 2426.05 | 55909412.77 | 90914056.89 | 71246561.31 |
April | 61052037.88 | 176125.64 | 60875912.24 | 0.126472E+09 | 48126891.75 |
May | 71073430.18 | 2244487.82 | 68828942.36 | 0.193718E+09 | 16854854.67 |
June | 73320657.73 | 3970901.36 | 69349756.36 | 0.214182E+09 | 7450202.69 |
July | 69646505.94 | 1983698.41 | 67662807.54 | 0.240721E+09 | 1078417.81 |
August | 65023602.41 | 701847.09 | 64321755.31 | 0.233981E+09 | 591718.36 |
September | 57167731.12 | 14230.38 | 57153500.74 | 0.170431E+09 | 9712360.90 |
October | 52355881.29 | 0.00 | 52355881.29 | 0.127116E+09 | 29696336.96 |
November | 43496514.54 | 0.00 | 43496514.54 | 78620148.20 | 60369741.73 |
December | 39627607.77 | 0.00 | 39627607.77 | 48729219.49 | 92238581.87 |
Annual Sum or Average | 0.675090E+09 | 9093716.75 | 0.665996E+09 | 0.162899E+10 | 0.515184E+09 |
Minimum of Months | 39627607.77 | 0.00 | 39627607.77 | 47092029.02 | 591718.36 |
Maximum of Months | 73320657.73 | 3970901.36 | 69349756.36 | 0.240721E+09 | 98016432.62 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42455061.96 | 0.00 | 42455061.96 | 47090224.90 | 98015327.16 |
February | 43956115.94 | 0.00 | 43956115.94 | 57012820.66 | 79801181.28 |
March | 55910065.88 | 2425.94 | 55907639.94 | 90911599.01 | 71245508.69 |
April | 61050140.22 | 176117.39 | 60874022.83 | 0.126470E+09 | 48125893.56 |
May | 71071216.99 | 2244382.62 | 68826834.37 | 0.193716E+09 | 16854167.53 |
June | 73318345.70 | 3970715.24 | 69347630.47 | 0.214179E+09 | 7449713.77 |
July | 69644365.68 | 1983605.43 | 67660760.25 | 0.240719E+09 | 1078284.33 |
August | 65021631.72 | 701814.19 | 64319817.53 | 0.233979E+09 | 591636.16 |
September | 57165995.84 | 14229.71 | 57151766.13 | 0.170429E+09 | 9711821.06 |
October | 52354257.58 | 0.00 | 52354257.58 | 0.127114E+09 | 29695318.03 |
November | 43495127.02 | 0.00 | 43495127.02 | 78618435.47 | 60368513.52 |
December | 39626306.83 | 0.00 | 39626306.83 | 48727538.37 | 92237448.82 |
Annual Sum or Average | 0.675069E+09 | 9093290.52 | 0.665975E+09 | 0.162896E+10 | 0.515175E+09 |
Minimum of Months | 39626306.83 | 0.00 | 39626306.83 | 47090224.90 | 591636.16 |
Maximum of Months | 73318345.70 | 3970715.24 | 69347630.47 | 0.240719E+09 | 98015327.16 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93822120.02 | 35915247.20 | 57906872.82 | 0.144217E+09 | 87761819.64 |
February | 0.102950E+09 | 42143273.86 | 60806537.48 | 0.163541E+09 | 73981715.39 |
March | 0.138054E+09 | 58163361.83 | 79890625.60 | 0.230746E+09 | 75414877.44 |
April | 0.157574E+09 | 70130857.18 | 87443447.75 | 0.280783E+09 | 61332571.92 |
May | 0.184807E+09 | 90192900.70 | 94613777.42 | 0.351845E+09 | 35795113.68 |
June | 0.186461E+09 | 95161930.03 | 91299561.83 | 0.360078E+09 | 26799757.02 |
July | 0.186960E+09 | 95219554.15 | 91740099.84 | 0.376317E+09 | 13593687.90 |
August | 0.178035E+09 | 87815876.26 | 90218870.61 | 0.359905E+09 | 12554564.01 |
September | 0.154569E+09 | 74429477.57 | 80139517.72 | 0.299552E+09 | 29481227.98 |
October | 0.134204E+09 | 63173426.62 | 71031018.34 | 0.246326E+09 | 50748143.65 |
November | 0.102980E+09 | 45035021.65 | 57945049.50 | 0.173837E+09 | 73324016.15 |
December | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 87727536.23 |
Annual Sum or Average | 0.170755E+10 | 0.791172E+09 | 0.916374E+09 | 0.312178E+10 | 0.628515E+09 |
Minimum of Months | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 12554564.01 |
Maximum of Months | 0.186960E+09 | 95219554.15 | 94613777.42 | 0.376317E+09 | 87761819.64 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93822120.02 | 35915247.20 | 57906872.82 | 0.144217E+09 | 87761819.64 |
February | 0.102950E+09 | 42143273.86 | 60806537.48 | 0.163541E+09 | 73981715.39 |
March | 0.138054E+09 | 58163361.83 | 79890625.60 | 0.230746E+09 | 75414877.44 |
April | 0.157574E+09 | 70130857.18 | 87443447.75 | 0.280783E+09 | 61332571.92 |
May | 0.184807E+09 | 90192900.70 | 94613777.42 | 0.351845E+09 | 35795113.68 |
June | 0.186461E+09 | 95161930.03 | 91299561.83 | 0.360078E+09 | 26799757.02 |
July | 0.186960E+09 | 95219554.15 | 91740099.84 | 0.376317E+09 | 13593687.90 |
August | 0.178035E+09 | 87815876.26 | 90218870.61 | 0.359905E+09 | 12554564.01 |
September | 0.154569E+09 | 74429477.57 | 80139517.72 | 0.299552E+09 | 29481227.98 |
October | 0.134204E+09 | 63173426.62 | 71031018.34 | 0.246326E+09 | 50748143.65 |
November | 0.102980E+09 | 45035021.65 | 57945049.50 | 0.173837E+09 | 73324016.15 |
December | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 87727536.23 |
Annual Sum or Average | 0.170755E+10 | 0.791172E+09 | 0.916374E+09 | 0.312178E+10 | 0.628515E+09 |
Minimum of Months | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 12554564.01 |
Maximum of Months | 0.186960E+09 | 95219554.15 | 94613777.42 | 0.376317E+09 | 87761819.64 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93822120.02 | 35915247.20 | 57906872.82 | 0.144217E+09 | 87761819.64 |
February | 0.102950E+09 | 42143273.86 | 60806537.48 | 0.163541E+09 | 73981715.39 |
March | 0.138054E+09 | 58163361.83 | 79890625.60 | 0.230746E+09 | 75414877.44 |
April | 0.157574E+09 | 70130857.18 | 87443447.75 | 0.280783E+09 | 61332571.92 |
May | 0.184807E+09 | 90192900.70 | 94613777.42 | 0.351845E+09 | 35795113.68 |
June | 0.186461E+09 | 95161930.03 | 91299561.83 | 0.360078E+09 | 26799757.02 |
July | 0.186960E+09 | 95219554.15 | 91740099.84 | 0.376317E+09 | 13593687.90 |
August | 0.178035E+09 | 87815876.26 | 90218870.61 | 0.359905E+09 | 12554564.01 |
September | 0.154569E+09 | 74429477.57 | 80139517.72 | 0.299552E+09 | 29481227.98 |
October | 0.134204E+09 | 63173426.62 | 71031018.34 | 0.246326E+09 | 50748143.65 |
November | 0.102980E+09 | 45035021.65 | 57945049.50 | 0.173837E+09 | 73324016.15 |
December | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 87727536.23 |
Annual Sum or Average | 0.170755E+10 | 0.791172E+09 | 0.916374E+09 | 0.312178E+10 | 0.628515E+09 |
Minimum of Months | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 12554564.01 |
Maximum of Months | 0.186960E+09 | 95219554.15 | 94613777.42 | 0.376317E+09 | 87761819.64 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93822120.02 | 35915247.20 | 57906872.82 | 0.144217E+09 | 87761819.64 |
February | 0.102950E+09 | 42143273.86 | 60806537.48 | 0.163541E+09 | 73981715.39 |
March | 0.138054E+09 | 58163361.83 | 79890625.60 | 0.230746E+09 | 75414877.44 |
April | 0.157574E+09 | 70130857.18 | 87443447.75 | 0.280783E+09 | 61332571.92 |
May | 0.184807E+09 | 90192900.70 | 94613777.42 | 0.351845E+09 | 35795113.68 |
June | 0.186461E+09 | 95161930.03 | 91299561.83 | 0.360078E+09 | 26799757.02 |
July | 0.186960E+09 | 95219554.15 | 91740099.84 | 0.376317E+09 | 13593687.90 |
August | 0.178035E+09 | 87815876.26 | 90218870.61 | 0.359905E+09 | 12554564.01 |
September | 0.154569E+09 | 74429477.57 | 80139517.72 | 0.299552E+09 | 29481227.98 |
October | 0.134204E+09 | 63173426.62 | 71031018.34 | 0.246326E+09 | 50748143.65 |
November | 0.102980E+09 | 45035021.65 | 57945049.50 | 0.173837E+09 | 73324016.15 |
December | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 87727536.23 |
Annual Sum or Average | 0.170755E+10 | 0.791172E+09 | 0.916374E+09 | 0.312178E+10 | 0.628515E+09 |
Minimum of Months | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 12554564.01 |
Maximum of Months | 0.186960E+09 | 95219554.15 | 94613777.42 | 0.376317E+09 | 87761819.64 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93822120.02 | 35915247.20 | 57906872.82 | 0.144217E+09 | 87761819.64 |
February | 0.102950E+09 | 42143273.86 | 60806537.48 | 0.163541E+09 | 73981715.39 |
March | 0.138054E+09 | 58163361.83 | 79890625.60 | 0.230746E+09 | 75414877.44 |
April | 0.157574E+09 | 70130857.18 | 87443447.75 | 0.280783E+09 | 61332571.92 |
May | 0.184807E+09 | 90192900.70 | 94613777.42 | 0.351845E+09 | 35795113.68 |
June | 0.186461E+09 | 95161930.03 | 91299561.83 | 0.360078E+09 | 26799757.02 |
July | 0.186960E+09 | 95219554.15 | 91740099.84 | 0.376317E+09 | 13593687.90 |
August | 0.178035E+09 | 87815876.26 | 90218870.61 | 0.359905E+09 | 12554564.01 |
September | 0.154569E+09 | 74429477.57 | 80139517.72 | 0.299552E+09 | 29481227.98 |
October | 0.134204E+09 | 63173426.62 | 71031018.34 | 0.246326E+09 | 50748143.65 |
November | 0.102980E+09 | 45035021.65 | 57945049.50 | 0.173837E+09 | 73324016.15 |
December | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 87727536.23 |
Annual Sum or Average | 0.170755E+10 | 0.791172E+09 | 0.916374E+09 | 0.312178E+10 | 0.628515E+09 |
Minimum of Months | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 12554564.01 |
Maximum of Months | 0.186960E+09 | 95219554.15 | 94613777.42 | 0.376317E+09 | 87761819.64 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93822120.02 | 35915247.20 | 57906872.82 | 0.144217E+09 | 87761819.64 |
February | 0.102950E+09 | 42143273.86 | 60806537.48 | 0.163541E+09 | 73981715.39 |
March | 0.138054E+09 | 58163361.83 | 79890625.60 | 0.230746E+09 | 75414877.44 |
April | 0.157574E+09 | 70130857.18 | 87443447.75 | 0.280783E+09 | 61332571.92 |
May | 0.184807E+09 | 90192900.70 | 94613777.42 | 0.351845E+09 | 35795113.68 |
June | 0.186461E+09 | 95161930.03 | 91299561.83 | 0.360078E+09 | 26799757.02 |
July | 0.186960E+09 | 95219554.15 | 91740099.84 | 0.376317E+09 | 13593687.90 |
August | 0.178035E+09 | 87815876.26 | 90218870.61 | 0.359905E+09 | 12554564.01 |
September | 0.154569E+09 | 74429477.57 | 80139517.72 | 0.299552E+09 | 29481227.98 |
October | 0.134204E+09 | 63173426.62 | 71031018.34 | 0.246326E+09 | 50748143.65 |
November | 0.102980E+09 | 45035021.65 | 57945049.50 | 0.173837E+09 | 73324016.15 |
December | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 87727536.23 |
Annual Sum or Average | 0.170755E+10 | 0.791172E+09 | 0.916374E+09 | 0.312178E+10 | 0.628515E+09 |
Minimum of Months | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 12554564.01 |
Maximum of Months | 0.186960E+09 | 95219554.15 | 94613777.42 | 0.376317E+09 | 87761819.64 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93822120.02 | 35915247.20 | 57906872.82 | 0.144217E+09 | 87761819.64 |
February | 0.102950E+09 | 42143273.86 | 60806537.48 | 0.163541E+09 | 73981715.39 |
March | 0.138054E+09 | 58163361.83 | 79890625.60 | 0.230746E+09 | 75414877.44 |
April | 0.157574E+09 | 70130857.18 | 87443447.75 | 0.280783E+09 | 61332571.92 |
May | 0.184807E+09 | 90192900.70 | 94613777.42 | 0.351845E+09 | 35795113.68 |
June | 0.186461E+09 | 95161930.03 | 91299561.83 | 0.360078E+09 | 26799757.02 |
July | 0.186960E+09 | 95219554.15 | 91740099.84 | 0.376317E+09 | 13593687.90 |
August | 0.178035E+09 | 87815876.26 | 90218870.61 | 0.359905E+09 | 12554564.01 |
September | 0.154569E+09 | 74429477.57 | 80139517.72 | 0.299552E+09 | 29481227.98 |
October | 0.134204E+09 | 63173426.62 | 71031018.34 | 0.246326E+09 | 50748143.65 |
November | 0.102980E+09 | 45035021.65 | 57945049.50 | 0.173837E+09 | 73324016.15 |
December | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 87727536.23 |
Annual Sum or Average | 0.170755E+10 | 0.791172E+09 | 0.916374E+09 | 0.312178E+10 | 0.628515E+09 |
Minimum of Months | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 12554564.01 |
Maximum of Months | 0.186960E+09 | 95219554.15 | 94613777.42 | 0.376317E+09 | 87761819.64 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93822120.02 | 35915247.20 | 57906872.82 | 0.144217E+09 | 87761819.64 |
February | 0.102950E+09 | 42143273.86 | 60806537.48 | 0.163541E+09 | 73981715.39 |
March | 0.138054E+09 | 58163361.83 | 79890625.60 | 0.230746E+09 | 75414877.44 |
April | 0.157574E+09 | 70130857.18 | 87443447.75 | 0.280783E+09 | 61332571.92 |
May | 0.184807E+09 | 90192900.70 | 94613777.42 | 0.351845E+09 | 35795113.68 |
June | 0.186461E+09 | 95161930.03 | 91299561.83 | 0.360078E+09 | 26799757.02 |
July | 0.186960E+09 | 95219554.15 | 91740099.84 | 0.376317E+09 | 13593687.90 |
August | 0.178035E+09 | 87815876.26 | 90218870.61 | 0.359905E+09 | 12554564.01 |
September | 0.154569E+09 | 74429477.57 | 80139517.72 | 0.299552E+09 | 29481227.98 |
October | 0.134204E+09 | 63173426.62 | 71031018.34 | 0.246326E+09 | 50748143.65 |
November | 0.102980E+09 | 45035021.65 | 57945049.50 | 0.173837E+09 | 73324016.15 |
December | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 87727536.23 |
Annual Sum or Average | 0.170755E+10 | 0.791172E+09 | 0.916374E+09 | 0.312178E+10 | 0.628515E+09 |
Minimum of Months | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 12554564.01 |
Maximum of Months | 0.186960E+09 | 95219554.15 | 94613777.42 | 0.376317E+09 | 87761819.64 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93822120.02 | 35915247.20 | 57906872.82 | 0.144217E+09 | 87761819.64 |
February | 0.102950E+09 | 42143273.86 | 60806537.48 | 0.163541E+09 | 73981715.39 |
March | 0.138054E+09 | 58163361.83 | 79890625.60 | 0.230746E+09 | 75414877.44 |
April | 0.157574E+09 | 70130857.18 | 87443447.75 | 0.280783E+09 | 61332571.92 |
May | 0.184807E+09 | 90192900.70 | 94613777.42 | 0.351845E+09 | 35795113.68 |
June | 0.186461E+09 | 95161930.03 | 91299561.83 | 0.360078E+09 | 26799757.02 |
July | 0.186960E+09 | 95219554.15 | 91740099.84 | 0.376317E+09 | 13593687.90 |
August | 0.178035E+09 | 87815876.26 | 90218870.61 | 0.359905E+09 | 12554564.01 |
September | 0.154569E+09 | 74429477.57 | 80139517.72 | 0.299552E+09 | 29481227.98 |
October | 0.134204E+09 | 63173426.62 | 71031018.34 | 0.246326E+09 | 50748143.65 |
November | 0.102980E+09 | 45035021.65 | 57945049.50 | 0.173837E+09 | 73324016.15 |
December | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 87727536.23 |
Annual Sum or Average | 0.170755E+10 | 0.791172E+09 | 0.916374E+09 | 0.312178E+10 | 0.628515E+09 |
Minimum of Months | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 12554564.01 |
Maximum of Months | 0.186960E+09 | 95219554.15 | 94613777.42 | 0.376317E+09 | 87761819.64 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93822120.02 | 35915247.20 | 57906872.82 | 0.144217E+09 | 87761819.64 |
February | 0.102950E+09 | 42143273.86 | 60806537.48 | 0.163541E+09 | 73981715.39 |
March | 0.138054E+09 | 58163361.83 | 79890625.60 | 0.230746E+09 | 75414877.44 |
April | 0.157574E+09 | 70130857.18 | 87443447.75 | 0.280783E+09 | 61332571.92 |
May | 0.184807E+09 | 90192900.70 | 94613777.42 | 0.351845E+09 | 35795113.68 |
June | 0.186461E+09 | 95161930.03 | 91299561.83 | 0.360078E+09 | 26799757.02 |
July | 0.186960E+09 | 95219554.15 | 91740099.84 | 0.376317E+09 | 13593687.90 |
August | 0.178035E+09 | 87815876.26 | 90218870.61 | 0.359905E+09 | 12554564.01 |
September | 0.154569E+09 | 74429477.57 | 80139517.72 | 0.299552E+09 | 29481227.98 |
October | 0.134204E+09 | 63173426.62 | 71031018.34 | 0.246326E+09 | 50748143.65 |
November | 0.102980E+09 | 45035021.65 | 57945049.50 | 0.173837E+09 | 73324016.15 |
December | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 87727536.23 |
Annual Sum or Average | 0.170755E+10 | 0.791172E+09 | 0.916374E+09 | 0.312178E+10 | 0.628515E+09 |
Minimum of Months | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 12554564.01 |
Maximum of Months | 0.186960E+09 | 95219554.15 | 94613777.42 | 0.376317E+09 | 87761819.64 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93822120.02 | 35915247.20 | 57906872.82 | 0.144217E+09 | 87761819.64 |
February | 0.102950E+09 | 42143273.86 | 60806537.48 | 0.163541E+09 | 73981715.39 |
March | 0.138054E+09 | 58163361.83 | 79890625.60 | 0.230746E+09 | 75414877.44 |
April | 0.157574E+09 | 70130857.18 | 87443447.75 | 0.280783E+09 | 61332571.92 |
May | 0.184807E+09 | 90192900.70 | 94613777.42 | 0.351845E+09 | 35795113.68 |
June | 0.186461E+09 | 95161930.03 | 91299561.83 | 0.360078E+09 | 26799757.02 |
July | 0.186960E+09 | 95219554.15 | 91740099.84 | 0.376317E+09 | 13593687.90 |
August | 0.178035E+09 | 87815876.26 | 90218870.61 | 0.359905E+09 | 12554564.01 |
September | 0.154569E+09 | 74429477.57 | 80139517.72 | 0.299552E+09 | 29481227.98 |
October | 0.134204E+09 | 63173426.62 | 71031018.34 | 0.246326E+09 | 50748143.65 |
November | 0.102980E+09 | 45035021.65 | 57945049.50 | 0.173837E+09 | 73324016.15 |
December | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 87727536.23 |
Annual Sum or Average | 0.170755E+10 | 0.791172E+09 | 0.916374E+09 | 0.312178E+10 | 0.628515E+09 |
Minimum of Months | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 12554564.01 |
Maximum of Months | 0.186960E+09 | 95219554.15 | 94613777.42 | 0.376317E+09 | 87761819.64 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93822120.02 | 35915247.20 | 57906872.82 | 0.144217E+09 | 87761819.64 |
February | 0.102950E+09 | 42143273.86 | 60806537.48 | 0.163541E+09 | 73981715.39 |
March | 0.138054E+09 | 58163361.83 | 79890625.60 | 0.230746E+09 | 75414877.44 |
April | 0.157574E+09 | 70130857.18 | 87443447.75 | 0.280783E+09 | 61332571.92 |
May | 0.184807E+09 | 90192900.70 | 94613777.42 | 0.351845E+09 | 35795113.68 |
June | 0.186461E+09 | 95161930.03 | 91299561.83 | 0.360078E+09 | 26799757.02 |
July | 0.186960E+09 | 95219554.15 | 91740099.84 | 0.376317E+09 | 13593687.90 |
August | 0.178035E+09 | 87815876.26 | 90218870.61 | 0.359905E+09 | 12554564.01 |
September | 0.154569E+09 | 74429477.57 | 80139517.72 | 0.299552E+09 | 29481227.98 |
October | 0.134204E+09 | 63173426.62 | 71031018.34 | 0.246326E+09 | 50748143.65 |
November | 0.102980E+09 | 45035021.65 | 57945049.50 | 0.173837E+09 | 73324016.15 |
December | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 87727536.23 |
Annual Sum or Average | 0.170755E+10 | 0.791172E+09 | 0.916374E+09 | 0.312178E+10 | 0.628515E+09 |
Minimum of Months | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 12554564.01 |
Maximum of Months | 0.186960E+09 | 95219554.15 | 94613777.42 | 0.376317E+09 | 87761819.64 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93822120.02 | 35915247.20 | 57906872.82 | 0.144217E+09 | 87761819.64 |
February | 0.102950E+09 | 42143273.86 | 60806537.48 | 0.163541E+09 | 73981715.39 |
March | 0.138054E+09 | 58163361.83 | 79890625.60 | 0.230746E+09 | 75414877.44 |
April | 0.157574E+09 | 70130857.18 | 87443447.75 | 0.280783E+09 | 61332571.92 |
May | 0.184807E+09 | 90192900.70 | 94613777.42 | 0.351845E+09 | 35795113.68 |
June | 0.186461E+09 | 95161930.03 | 91299561.83 | 0.360078E+09 | 26799757.02 |
July | 0.186960E+09 | 95219554.15 | 91740099.84 | 0.376317E+09 | 13593687.90 |
August | 0.178035E+09 | 87815876.26 | 90218870.61 | 0.359905E+09 | 12554564.01 |
September | 0.154569E+09 | 74429477.57 | 80139517.72 | 0.299552E+09 | 29481227.98 |
October | 0.134204E+09 | 63173426.62 | 71031018.34 | 0.246326E+09 | 50748143.65 |
November | 0.102980E+09 | 45035021.65 | 57945049.50 | 0.173837E+09 | 73324016.15 |
December | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 87727536.23 |
Annual Sum or Average | 0.170755E+10 | 0.791172E+09 | 0.916374E+09 | 0.312178E+10 | 0.628515E+09 |
Minimum of Months | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 12554564.01 |
Maximum of Months | 0.186960E+09 | 95219554.15 | 94613777.42 | 0.376317E+09 | 87761819.64 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93822120.02 | 35915247.20 | 57906872.82 | 0.144217E+09 | 87761819.64 |
February | 0.102950E+09 | 42143273.86 | 60806537.48 | 0.163541E+09 | 73981715.39 |
March | 0.138054E+09 | 58163361.83 | 79890625.60 | 0.230746E+09 | 75414877.44 |
April | 0.157574E+09 | 70130857.18 | 87443447.75 | 0.280783E+09 | 61332571.92 |
May | 0.184807E+09 | 90192900.70 | 94613777.42 | 0.351845E+09 | 35795113.68 |
June | 0.186461E+09 | 95161930.03 | 91299561.83 | 0.360078E+09 | 26799757.02 |
July | 0.186960E+09 | 95219554.15 | 91740099.84 | 0.376317E+09 | 13593687.90 |
August | 0.178035E+09 | 87815876.26 | 90218870.61 | 0.359905E+09 | 12554564.01 |
September | 0.154569E+09 | 74429477.57 | 80139517.72 | 0.299552E+09 | 29481227.98 |
October | 0.134204E+09 | 63173426.62 | 71031018.34 | 0.246326E+09 | 50748143.65 |
November | 0.102980E+09 | 45035021.65 | 57945049.50 | 0.173837E+09 | 73324016.15 |
December | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 87727536.23 |
Annual Sum or Average | 0.170755E+10 | 0.791172E+09 | 0.916374E+09 | 0.312178E+10 | 0.628515E+09 |
Minimum of Months | 87130103.63 | 33791396.97 | 53338706.66 | 0.134633E+09 | 12554564.01 |
Maximum of Months | 0.186960E+09 | 95219554.15 | 94613777.42 | 0.376317E+09 | 87761819.64 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.232234E+09 | 0.138800E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.256622E+09 | 0.124166E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.352371E+09 | 0.137338E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416746E+09 | 0.124527E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499721E+09 | 96782723.89 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503589E+09 | 89379571.15 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.511129E+09 | 82580836.52 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483775E+09 | 84746001.23 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.417052E+09 | 95403968.38 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353927E+09 | 0.120812E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.260199E+09 | 0.143025E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 0.147599E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449930E+10 | 0.138516E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211929E+09 | 82580836.52 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.511129E+09 | 0.147599E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 174.01 | 195.24 | 128.46 | 27.85 | 100.61 | 0.00 | 0.00 |
February | 218.60 | 176.06 | 146.68 | 31.57 | 115.11 | 0.00 | 0.00 |
March | 297.47 | 143.12 | 172.33 | 38.76 | 133.57 | 0.00 | 0.00 |
April | 384.86 | 101.70 | 189.46 | 40.01 | 149.45 | 0.00 | 0.00 |
May | 516.88 | 35.17 | 207.96 | 47.92 | 160.04 | 0.00 | 0.00 |
June | 569.64 | 15.25 | 216.90 | 53.70 | 163.21 | 0.00 | 0.00 |
July | 599.21 | 2.16 | 199.12 | 43.60 | 155.52 | 0.00 | 0.00 |
August | 604.15 | 1.29 | 199.18 | 46.20 | 152.98 | 0.00 | 0.00 |
September | 489.68 | 20.95 | 187.61 | 45.12 | 142.49 | 0.00 | 0.00 |
October | 376.53 | 61.02 | 166.64 | 41.20 | 125.44 | 0.00 | 0.00 |
November | 267.46 | 126.72 | 143.34 | 35.95 | 107.39 | 0.00 | 0.00 |
December | 177.65 | 185.03 | 121.44 | 27.82 | 93.62 | 0.00 | 0.00 |
Annual Sum or Average | 390.67 | 88.17 | 173.36 | 40.00 | 133.35 | 0.00 | 0.00 |
Minimum of Months | 174.01 | 1.29 | 121.44 | 27.82 | 93.62 | 0.00 | 0.00 |
Maximum of Months | 604.15 | 195.24 | 216.90 | 53.70 | 163.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 753.82 | 458.73 | 490.41 | 187.73 | 302.68 | 0.00 | 0.00 |
February | 946.42 | 428.13 | 595.77 | 243.88 | 351.89 | 0.00 | 0.00 |
March | 1206.11 | 394.19 | 721.61 | 304.02 | 417.59 | 0.00 | 0.00 |
April | 1516.57 | 331.27 | 851.10 | 378.79 | 472.30 | 0.00 | 0.00 |
May | 1839.09 | 187.10 | 965.98 | 471.44 | 494.55 | 0.00 | 0.00 |
June | 1944.87 | 144.75 | 1007.12 | 513.99 | 493.13 | 0.00 | 0.00 |
July | 1967.01 | 71.05 | 977.24 | 497.71 | 479.53 | 0.00 | 0.00 |
August | 1881.22 | 65.62 | 930.59 | 459.01 | 471.57 | 0.00 | 0.00 |
September | 1617.95 | 159.24 | 834.86 | 402.01 | 432.85 | 0.00 | 0.00 |
October | 1287.55 | 265.26 | 701.49 | 330.21 | 371.28 | 0.00 | 0.00 |
November | 938.94 | 396.04 | 556.22 | 243.24 | 312.97 | 0.00 | 0.00 |
December | 703.73 | 458.55 | 455.43 | 176.63 | 278.80 | 0.00 | 0.00 |
Annual Sum or Average | 1385.87 | 279.02 | 758.04 | 351.23 | 406.81 | 0.00 | 0.00 |
Minimum of Months | 703.73 | 65.62 | 455.43 | 176.63 | 278.80 | 0.00 | 0.00 |
Maximum of Months | 1967.01 | 458.73 | 1007.12 | 513.99 | 494.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 10539.79 | 5370.35 | 2201.82 | 843.95 | 1357.87 | 0.00 | 0.00 |
February | 13338.31 | 5455.55 | 2669.67 | 1091.04 | 1578.63 | 0.00 | 0.00 |
March | 20558.41 | 5742.22 | 3228.62 | 1355.25 | 1873.36 | 0.00 | 0.00 |
April | 29132.33 | 6486.61 | 3806.09 | 1687.27 | 2118.82 | 0.00 | 0.00 |
May | 39903.89 | 8336.59 | 4318.67 | 2100.06 | 2218.61 | 0.00 | 0.00 |
June | 42981.60 | 8704.79 | 4501.65 | 2289.39 | 2212.26 | 0.00 | 0.00 |
July | 46252.83 | 8115.73 | 4366.87 | 2215.65 | 2151.22 | 0.00 | 0.00 |
August | 42715.05 | 8547.11 | 4159.62 | 2044.07 | 2115.55 | 0.00 | 0.00 |
September | 35497.07 | 9211.77 | 3733.16 | 1791.32 | 1941.84 | 0.00 | 0.00 |
October | 25006.43 | 9843.14 | 3140.69 | 1475.07 | 1665.61 | 0.00 | 0.00 |
November | 15621.64 | 7338.60 | 2495.50 | 1091.45 | 1404.05 | 0.00 | 0.00 |
December | 9502.87 | 6024.26 | 2045.64 | 794.89 | 1250.75 | 0.00 | 0.00 |
Annual Sum or Average | 27669.34 | 7442.11 | 3392.22 | 1567.20 | 1825.02 | 0.00 | 0.00 |
Minimum of Months | 9502.87 | 5370.35 | 2045.64 | 794.89 | 1250.75 | 0.00 | 0.00 |
Maximum of Months | 46252.83 | 9843.14 | 4501.65 | 2289.39 | 2218.61 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.466076E+09 | 0.522920E+09 | 0.344072E+09 | 74592843.54 | 0.269479E+09 | 0.00 | 0.00 |
February | 0.528830E+09 | 0.425913E+09 | 0.354844E+09 | 76375593.01 | 0.278468E+09 | 0.00 | 0.00 |
March | 0.796756E+09 | 0.383343E+09 | 0.461565E+09 | 0.103808E+09 | 0.357757E+09 | 0.00 | 0.00 |
April | 0.997554E+09 | 0.263599E+09 | 0.491087E+09 | 0.103717E+09 | 0.387369E+09 | 0.00 | 0.00 |
May | 0.138441E+10 | 94205479.13 | 0.557002E+09 | 0.128351E+09 | 0.428651E+09 | 0.00 | 0.00 |
June | 0.147650E+10 | 39532743.81 | 0.562211E+09 | 0.139179E+09 | 0.423032E+09 | 0.00 | 0.00 |
July | 0.160491E+10 | 5785374.17 | 0.533320E+09 | 0.116772E+09 | 0.416548E+09 | 0.00 | 0.00 |
August | 0.161816E+10 | 3455025.67 | 0.533473E+09 | 0.123734E+09 | 0.409739E+09 | 0.00 | 0.00 |
September | 0.126926E+10 | 54290964.29 | 0.486282E+09 | 0.116961E+09 | 0.369321E+09 | 0.00 | 0.00 |
October | 0.100848E+10 | 0.163429E+09 | 0.446331E+09 | 0.110357E+09 | 0.335974E+09 | 0.00 | 0.00 |
November | 0.693257E+09 | 0.328446E+09 | 0.371537E+09 | 93172904.41 | 0.278364E+09 | 0.00 | 0.00 |
December | 0.475815E+09 | 0.495571E+09 | 0.325258E+09 | 74516686.05 | 0.250742E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.123200E+11 | 0.278049E+10 | 0.546698E+10 | 0.126154E+10 | 0.420544E+10 | 0.00 | 0.00 |
Minimum of Months | 0.466076E+09 | 3455025.67 | 0.325258E+09 | 74516686.05 | 0.250742E+09 | 0.00 | 0.00 |
Maximum of Months | 0.161816E+10 | 0.522920E+09 | 0.562211E+09 | 0.139179E+09 | 0.428651E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.201904E+10 | 0.122867E+10 | 0.131351E+10 | 0.502813E+09 | 0.810696E+09 | 0.00 | 0.00 |
February | 0.228958E+10 | 0.103574E+10 | 0.144130E+10 | 0.590006E+09 | 0.851292E+09 | 0.00 | 0.00 |
March | 0.323045E+10 | 0.105581E+10 | 0.193276E+10 | 0.814287E+09 | 0.111847E+10 | 0.00 | 0.00 |
April | 0.393096E+10 | 0.858656E+09 | 0.220604E+10 | 0.981832E+09 | 0.122421E+10 | 0.00 | 0.00 |
May | 0.492583E+10 | 0.501132E+09 | 0.258729E+10 | 0.126270E+10 | 0.132459E+10 | 0.00 | 0.00 |
June | 0.504110E+10 | 0.375197E+09 | 0.261046E+10 | 0.133227E+10 | 0.127819E+10 | 0.00 | 0.00 |
July | 0.526843E+10 | 0.190312E+09 | 0.261744E+10 | 0.133307E+10 | 0.128436E+10 | 0.00 | 0.00 |
August | 0.503867E+10 | 0.175764E+09 | 0.249249E+10 | 0.122942E+10 | 0.126306E+10 | 0.00 | 0.00 |
September | 0.419373E+10 | 0.412737E+09 | 0.216397E+10 | 0.104201E+10 | 0.112195E+10 | 0.00 | 0.00 |
October | 0.344857E+10 | 0.710474E+09 | 0.187886E+10 | 0.884428E+09 | 0.994434E+09 | 0.00 | 0.00 |
November | 0.243372E+10 | 0.102654E+10 | 0.144172E+10 | 0.630490E+09 | 0.811231E+09 | 0.00 | 0.00 |
December | 0.188486E+10 | 0.122819E+10 | 0.121982E+10 | 0.473080E+09 | 0.746742E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.437049E+11 | 0.879921E+10 | 0.239056E+11 | 0.110764E+11 | 0.128292E+11 | 0.00 | 0.00 |
Minimum of Months | 0.188486E+10 | 0.175764E+09 | 0.121982E+10 | 0.473080E+09 | 0.746742E+09 | 0.00 | 0.00 |
Maximum of Months | 0.526843E+10 | 0.122867E+10 | 0.261744E+10 | 0.133307E+10 | 0.132459E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.282298E+11 | 0.143839E+11 | 0.589735E+10 | 0.226044E+10 | 0.363691E+10 | 0.00 | 0.00 |
February | 0.322680E+11 | 0.131981E+11 | 0.645846E+10 | 0.263944E+10 | 0.381902E+10 | 0.00 | 0.00 |
March | 0.550637E+11 | 0.153800E+11 | 0.864752E+10 | 0.362990E+10 | 0.501762E+10 | 0.00 | 0.00 |
April | 0.755110E+11 | 0.168133E+11 | 0.986539E+10 | 0.437341E+10 | 0.549198E+10 | 0.00 | 0.00 |
May | 0.106879E+12 | 0.223287E+11 | 0.115671E+11 | 0.562479E+10 | 0.594232E+10 | 0.00 | 0.00 |
June | 0.111408E+12 | 0.225628E+11 | 0.116683E+11 | 0.593410E+10 | 0.573417E+10 | 0.00 | 0.00 |
July | 0.123884E+12 | 0.217372E+11 | 0.116962E+11 | 0.593439E+10 | 0.576184E+10 | 0.00 | 0.00 |
August | 0.114408E+12 | 0.228926E+11 | 0.111411E+11 | 0.547482E+10 | 0.566630E+10 | 0.00 | 0.00 |
September | 0.920084E+11 | 0.238769E+11 | 0.967635E+10 | 0.464310E+10 | 0.503325E+10 | 0.00 | 0.00 |
October | 0.669772E+11 | 0.263639E+11 | 0.841202E+10 | 0.395084E+10 | 0.446118E+10 | 0.00 | 0.00 |
November | 0.404913E+11 | 0.190216E+11 | 0.646833E+10 | 0.282903E+10 | 0.363930E+10 | 0.00 | 0.00 |
December | 0.254525E+11 | 0.161354E+11 | 0.547904E+10 | 0.212904E+10 | 0.335000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.872580E+12 | 0.234694E+12 | 0.106977E+12 | 0.494233E+11 | 0.575539E+11 | 0.00 | 0.00 |
Minimum of Months | 0.254525E+11 | 0.131981E+11 | 0.547904E+10 | 0.212904E+10 | 0.335000E+10 | 0.00 | 0.00 |
Maximum of Months | 0.123884E+12 | 0.263639E+11 | 0.116962E+11 | 0.593439E+10 | 0.594232E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.683493E+09 | -608901467.8 | 0.00 | 0.00 | 744.00 | 0.00 | -74591597.2 | 58.99 | 0.00 | 0.00 |
February | 0.610018E+09 | -543785636.6 | 0.00 | 0.00 | 672.00 | 0.00 | -66232055.6 | 58.99 | 0.00 | 0.00 |
March | 0.663043E+09 | -590755001.9 | 0.00 | 0.00 | 744.00 | 0.00 | -72288142.0 | 58.99 | 0.00 | 0.00 |
April | 0.561661E+09 | -493212079.5 | 0.00 | 0.00 | 720.00 | 0.00 | -68449403.9 | 58.99 | 0.00 | 0.00 |
May | 0.526050E+09 | -456686037.6 | 0.00 | 0.00 | 744.00 | 0.00 | -69364152.3 | 58.99 | 0.00 | 0.00 |
June | 0.480731E+09 | -413924948.1 | 0.00 | 0.00 | 720.00 | 0.00 | -66806133.2 | 58.99 | 0.00 | 0.00 |
July | 0.455768E+09 | -387620314.1 | 0.00 | 0.00 | 744.00 | 0.00 | -68147252.7 | 58.99 | 0.00 | 0.00 |
August | 0.503745E+09 | -435318650.4 | 0.00 | 0.00 | 744.00 | 0.00 | -68426035.2 | 58.99 | 0.00 | 0.00 |
September | 0.514765E+09 | -448233549.2 | 0.00 | 0.00 | 720.00 | 0.00 | -66531078.2 | 58.98 | 0.00 | 0.00 |
October | 0.574353E+09 | -505122964.5 | 0.00 | 0.00 | 744.00 | 0.00 | -69229752.3 | 58.99 | 0.00 | 0.00 |
November | 0.604910E+09 | -536758220.7 | 0.00 | 0.00 | 720.00 | 0.00 | -68152124.5 | 58.99 | 0.00 | 0.00 |
December | 0.669545E+09 | -596901953.0 | 0.00 | 0.00 | 744.00 | 0.00 | -72642915.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.684808E+10 | -0.601722E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -830860642.7 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.455768E+09 | -608901467.8 | 0.00 | 0.00 | 672.00 | 0.00 | -74591597.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.683493E+09 | -387620314.1 | 0.00 | 0.00 | 744.00 | 0.00 | -66232055.6 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.78 | 0.50 | 08-JAN-11:00 | 214.19 | 0.00 | 0.00 | 80.33 | 396.64 | 0.00 | 0.00 | 26.17 |
February | 308.33 | 0.74 | 0.50 | 01-FEB-11:09 | 246.38 | 0.00 | 0.00 | 114.33 | 449.93 | 0.00 | 0.00 | 67.83 |
March | 357.50 | 0.71 | 0.50 | 01-MAR-10:00 | 286.40 | 0.00 | 0.00 | 163.83 | 228.57 | 0.00 | 0.00 | 117.33 |
April | 375.00 | 0.70 | 0.50 | 01-APR-10:50 | 315.74 | 0.00 | 0.00 | 183.00 | 603.88 | 0.00 | 0.00 | 157.33 |
May | 405.33 | 0.71 | 0.50 | 01-MAY-10:09 | 812.87 | 0.00 | 0.00 | 208.17 | 227.64 | 0.00 | 0.00 | 122.33 |
June | 403.50 | 0.71 | 0.50 | 01-JUN-10:30 | 342.99 | 0.00 | 0.00 | 206.67 | 216.51 | 0.00 | 0.00 | 113.50 |
July | 405.00 | 0.70 | 0.50 | 01-JUL-10:39 | 621.53 | 0.00 | 0.00 | 216.17 | 227.42 | 0.00 | 0.00 | 123.83 |
August | 395.83 | 0.69 | 0.50 | 01-AUG-10:39 | 918.40 | 0.00 | 0.00 | 210.00 | 253.56 | 0.00 | 0.00 | 150.83 |
September | 358.83 | 0.69 | 0.50 | 01-SEP-10:09 | 315.28 | 0.00 | 0.00 | 182.67 | 252.77 | 0.00 | 0.00 | 139.33 |
October | 351.17 | 0.72 | 0.50 | 01-OCT-10:09 | 268.00 | 0.00 | 0.00 | 149.50 | 314.64 | 0.00 | 0.00 | 108.50 |
November | 318.83 | 0.75 | 0.50 | 01-NOV-10:39 | 230.31 | 0.00 | 0.00 | 99.67 | 559.69 | 0.00 | 0.00 | 70.17 |
December | 319.00 | 0.79 | 0.50 | 04-DEC-12:20 | 203.53 | 0.00 | 0.00 | 55.17 | 167.47 | 0.00 | 0.00 | 1.50 |
Annual Sum or Average | 4323.33 | 0.72 | 415.21 | 0.00 | 0.00 | 1869.50 | 319.42 | 0.00 | 0.00 | 1198.67 | ||
Minimum of Months | 308.33 | 0.69 | 0.50 | 203.53 | 0.00 | 0.00 | 55.17 | 167.47 | 0.00 | 0.00 | 1.50 | |
Maximum of Months | 405.33 | 0.79 | 0.50 | 918.40 | 0.00 | 0.00 | 216.17 | 603.88 | 0.00 | 0.00 | 157.33 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.64 | 0.50 | 01-JAN-09:39 | 610.24 | 14.14 | 20.17 | 197.67 | 323.63 | 18.82 | 58.50 | 184.17 |
February | 308.33 | 0.64 | 0.50 | 01-FEB-09:09 | 736.88 | 14.42 | 16.50 | 200.00 | 230.20 | 16.97 | 56.00 | 164.33 |
March | 357.50 | 0.62 | 0.50 | 01-MAR-08:00 | 767.40 | 13.92 | 0.00 | 251.67 | 651.97 | 17.27 | 75.83 | 210.17 |
April | 375.00 | 0.62 | 0.50 | 01-APR-08:20 | 743.72 | 13.96 | 0.00 | 268.00 | 646.15 | 17.30 | 90.33 | 229.17 |
May | 405.33 | 0.61 | 0.50 | 01-MAY-07:49 | 345.21 | 14.03 | 0.00 | 292.83 | 298.53 | 17.46 | 103.33 | 252.00 |
June | 403.50 | 0.61 | 0.50 | 01-JUN-07:40 | 350.95 | 13.99 | 0.00 | 292.33 | 302.99 | 17.52 | 105.83 | 250.33 |
July | 405.00 | 0.60 | 0.50 | 01-JUL-07:30 | 357.21 | 14.04 | 0.00 | 297.00 | 330.22 | 19.20 | 127.83 | 277.67 |
August | 395.83 | 0.61 | 0.50 | 01-AUG-07:49 | 462.04 | 14.23 | 0.00 | 289.00 | 408.16 | 17.64 | 106.33 | 251.50 |
September | 358.83 | 0.61 | 0.50 | 01-SEP-07:00 | 1053.35 | 14.38 | 0.00 | 263.83 | 928.92 | 17.88 | 100.67 | 224.83 |
October | 351.17 | 0.62 | 0.50 | 01-OCT-08:09 | 304.10 | 14.04 | 0.00 | 241.67 | 254.48 | 17.59 | 91.00 | 203.00 |
November | 318.83 | 0.64 | 0.50 | 01-NOV-08:30 | 263.21 | 13.84 | 0.00 | 205.17 | 568.06 | 17.35 | 56.83 | 164.33 |
December | 319.00 | 0.66 | 0.50 | 01-DEC-09:20 | 232.93 | 13.00 | 0.00 | 188.50 | 359.69 | 16.33 | 9.50 | 145.50 |
Annual Sum or Average | 4323.33 | 0.62 | 516.01 | 14.01 | 36.67 | 2987.67 | 441.48 | 17.64 | 982.00 | 2557.00 | ||
Minimum of Months | 308.33 | 0.60 | 0.50 | 232.93 | 13.00 | 0.00 | 188.50 | 230.20 | 16.33 | 9.50 | 145.50 | |
Maximum of Months | 405.33 | 0.66 | 0.50 | 1053.35 | 14.42 | 20.17 | 297.00 | 928.92 | 19.20 | 127.83 | 277.67 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.87 | 0.68 | 01-JAN-16:10 | 219.04 | 22.50 | 166.67 | 25.67 | 109.14 | 20.26 | 147.17 | 0.00 |
February | 308.33 | 0.85 | 0.61 | 10-FEB-16:10 | 259.65 | 22.76 | 156.50 | 34.83 | 167.00 | 22.17 | 156.50 | 21.33 |
March | 357.50 | 0.84 | 0.61 | 01-MAR-16:10 | 285.03 | 22.49 | 171.67 | 59.83 | 205.46 | 23.02 | 189.67 | 28.50 |
April | 375.00 | 0.85 | 0.61 | 06-APR-16:30 | 233.89 | 20.00 | 142.00 | 49.00 | 164.50 | 21.04 | 178.50 | 17.17 |
May | 405.33 | 0.83 | 0.61 | 29-MAY-15:30 | 249.55 | 19.88 | 142.00 | 65.67 | 175.02 | 21.14 | 181.00 | 22.17 |
June | 403.50 | 0.81 | 0.61 | 04-JUN-15:50 | 265.49 | 19.88 | 145.33 | 80.67 | 189.57 | 21.17 | 192.67 | 31.67 |
July | 405.00 | 0.81 | 0.61 | 06-JUL-16:10 | 262.18 | 19.79 | 150.33 | 77.83 | 176.74 | 20.96 | 198.00 | 28.33 |
August | 395.83 | 0.81 | 0.61 | 03-AUG-15:50 | 260.47 | 20.19 | 158.83 | 79.83 | 190.71 | 21.50 | 205.83 | 34.83 |
September | 358.83 | 0.82 | 0.61 | 01-SEP-16:10 | 277.23 | 21.70 | 172.50 | 81.50 | 234.58 | 23.55 | 202.67 | 41.50 |
October | 351.17 | 0.83 | 0.61 | 01-OCT-16:10 | 266.12 | 23.16 | 189.50 | 62.33 | 177.04 | 23.52 | 200.17 | 28.83 |
November | 318.83 | 0.85 | 0.61 | 01-NOV-16:19 | 277.37 | 23.76 | 175.83 | 35.17 | 134.68 | 22.32 | 170.50 | 6.83 |
December | 319.00 | 0.88 | 0.68 | 01-DEC-15:09 | 219.04 | 22.58 | 161.83 | 21.17 | 106.56 | 20.25 | 140.00 | 0.00 |
Annual Sum or Average | 4323.33 | 0.84 | 256.67 | 21.43 | 1933.00 | 673.50 | 171.14 | 21.73 | 2162.67 | 261.17 | ||
Minimum of Months | 308.33 | 0.81 | 0.61 | 219.04 | 19.79 | 142.00 | 21.17 | 106.56 | 20.25 | 140.00 | 0.00 | |
Maximum of Months | 405.33 | 0.88 | 0.68 | 285.03 | 23.76 | 189.50 | 81.50 | 234.58 | 23.55 | 205.83 | 41.50 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 15178558.43 | 2321.01 | 02-JAN-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15178558.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15178558.43 | 2321.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.403394E+10 | 0.327027E+10 | 32336.50 | 30-JAN-06:02 | 21335.84 | 0.00 |
February | 0.00 | 0.00 | 0.536528E+10 | 0.430269E+10 | 33626.96 | 09-FEB-06:01 | 20949.36 | 0.00 |
March | 0.00 | 0.00 | 0.797431E+10 | 0.666886E+10 | 33853.75 | 29-MAR-05:01 | 20766.95 | 0.00 |
April | 0.00 | 0.00 | 0.100018E+11 | 0.825900E+10 | 34144.08 | 10-APR-05:01 | 20781.32 | 0.00 |
May | 0.00 | 0.00 | 0.145168E+11 | 0.118187E+11 | 36261.44 | 24-MAY-05:01 | 18209.89 | 0.00 |
June | 0.00 | 0.00 | 0.177056E+11 | 0.130691E+11 | 36329.45 | 08-JUN-05:02 | 17226.63 | 0.00 |
July | 0.00 | 0.00 | 0.202360E+11 | 0.140418E+11 | 35321.28 | 06-JUL-05:01 | 15888.43 | 0.00 |
August | 0.00 | 0.00 | 0.226772E+11 | 0.155324E+11 | 35321.28 | 31-AUG-05:04 | 15730.49 | 0.00 |
September | 0.00 | 0.00 | 0.180973E+11 | 0.126736E+11 | 36924.66 | 25-SEP-05:02 | 17774.89 | 0.00 |
October | 0.00 | 0.00 | 0.144773E+11 | 0.108131E+11 | 36334.68 | 07-OCT-05:01 | 17635.59 | 0.00 |
November | 0.00 | 0.00 | 0.106552E+11 | 0.812025E+10 | 35561.99 | 03-NOV-05:01 | 20188.32 | 0.00 |
December | 0.00 | 0.00 | 0.663800E+10 | 0.520850E+10 | 33503.96 | 06-DEC-06:02 | 20194.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.152379E+12 | 0.113778E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.403394E+10 | 0.327027E+10 | 32336.50 | 15730.49 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.226772E+11 | 0.155324E+11 | 36924.66 | 21335.84 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.490219E+09 | 0.372447E+09 | 7456.76 | 28-JAN-14:00 | 7456.76 | 0.00 |
February | 0.00 | 0.00 | 0.373901E+10 | 0.289598E+10 | 36983.00 | 05-FEB-14:55 | 33287.51 | 0.00 |
March | 0.00 | 0.00 | 0.110981E+11 | 0.912021E+10 | 73350.70 | 26-MAR-12:43 | 73350.70 | 0.00 |
April | 0.00 | 0.00 | 0.237268E+11 | 0.193749E+11 | 102701.62 | 30-APR-17:33 | 69776.59 | 0.00 |
May | 0.00 | 0.00 | 0.498689E+11 | 0.404001E+11 | 111245.76 | 24-MAY-05:08 | 64070.11 | 0.00 |
June | 0.00 | 0.00 | 0.648506E+11 | 0.473349E+11 | 113745.83 | 14-JUN-05:05 | 67874.91 | 0.00 |
July | 0.00 | 0.00 | 0.823708E+11 | 0.580985E+11 | 112090.91 | 04-JUL-23:03 | 65370.12 | 0.00 |
August | 0.00 | 0.00 | 0.882320E+11 | 0.611899E+11 | 115590.08 | 08-AUG-05:01 | 62618.33 | 0.00 |
September | 0.00 | 0.00 | 0.654859E+11 | 0.452428E+11 | 111786.27 | 08-SEP-17:06 | 63659.32 | 0.00 |
October | 0.00 | 0.00 | 0.438286E+11 | 0.323985E+11 | 112442.77 | 07-OCT-05:06 | 67816.17 | 0.00 |
November | 0.00 | 0.00 | 0.210672E+11 | 0.156540E+11 | 80219.27 | 01-NOV-17:08 | 52341.60 | 0.00 |
December | 0.00 | 0.00 | 0.527451E+10 | 0.383809E+10 | 40202.47 | 03-DEC-13:35 | 32354.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.460033E+12 | 0.335920E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.490219E+09 | 0.372447E+09 | 7456.76 | 7456.76 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.882320E+11 | 0.611899E+11 | 115590.08 | 73350.70 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.581652E+09 | 0.20 | 1465.29 | 30-JAN-06:02 | 0.90 |
February | 0.538344E+09 | 0.21 | 1465.29 | 06-FEB-06:02 | 0.89 |
March | 0.639845E+09 | 0.23 | 1465.29 | 01-MAR-06:02 | 0.90 |
April | 0.605321E+09 | 0.22 | 1465.29 | 01-APR-05:02 | 0.89 |
May | 0.707094E+09 | 0.25 | 1465.29 | 01-MAY-05:01 | 0.89 |
June | 0.814909E+09 | 0.28 | 1465.29 | 01-JUN-05:01 | 0.90 |
July | 0.940522E+09 | 0.31 | 1465.29 | 01-JUL-05:01 | 0.89 |
August | 0.106175E+10 | 0.33 | 1465.29 | 01-AUG-05:01 | 0.89 |
September | 0.815929E+09 | 0.29 | 1465.29 | 01-SEP-05:01 | 0.89 |
October | 0.665380E+09 | 0.24 | 1465.29 | 02-OCT-05:01 | 0.88 |
November | 0.584639E+09 | 0.22 | 1465.29 | 01-NOV-05:01 | 0.89 |
December | 0.589344E+09 | 0.21 | 1465.29 | 01-DEC-06:02 | 0.90 |
Annual Sum or Average | 0.854473E+10 | 0.25 | |||
Minimum of Months | 0.538344E+09 | 0.20 | 1465.29 | 0.88 | |
Maximum of Months | 0.106175E+10 | 0.33 | 1465.29 | 0.90 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.259778E+10 | 0.31 | 2624.02 | 07-JAN-15:30 | 0.84 |
February | 0.240022E+10 | 0.32 | 2624.02 | 04-FEB-10:20 | 0.84 |
March | 0.286207E+10 | 0.36 | 5100.91 | 26-MAR-12:43 | 1.24 |
April | 0.289660E+10 | 0.44 | 6342.44 | 28-APR-17:06 | 1.37 |
May | 0.370414E+10 | 0.65 | 6560.05 | 04-MAY-17:06 | 1.39 |
June | 0.406904E+10 | 0.70 | 6560.05 | 01-JUN-17:05 | 1.39 |
July | 0.484304E+10 | 0.73 | 6560.05 | 01-JUL-17:06 | 1.38 |
August | 0.513908E+10 | 0.75 | 6560.05 | 01-AUG-05:01 | 1.38 |
September | 0.403752E+10 | 0.70 | 6560.05 | 01-SEP-17:05 | 1.38 |
October | 0.341176E+10 | 0.60 | 6560.05 | 01-OCT-09:53 | 1.38 |
November | 0.269147E+10 | 0.40 | 5043.21 | 05-NOV-16:23 | 1.23 |
December | 0.261408E+10 | 0.32 | 2624.02 | 06-DEC-11:00 | 0.83 |
Annual Sum or Average | 0.412668E+11 | 0.52 | |||
Minimum of Months | 0.240022E+10 | 0.31 | 2624.02 | 0.83 | |
Maximum of Months | 0.513908E+10 | 0.75 | 6560.05 | 1.39 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.155459E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.183196E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.259420E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.312460E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.454712E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.552283E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.641600E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.720510E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.551619E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.427754E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.315746E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.216903E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.479166E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.155459E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.720510E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.273656E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.347123E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.607886E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.987044E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.187647E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.234250E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.296916E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.316876E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.231965E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.160912E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.866308E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.408673E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.177763E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.273656E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.316876E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.581652E+09 | 0.403394E+10 | 15178558.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.538344E+09 | 0.536528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.639845E+09 | 0.797431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.605321E+09 | 0.100018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.707094E+09 | 0.145168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.814909E+09 | 0.177056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.940522E+09 | 0.202360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.106175E+10 | 0.226772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.815929E+09 | 0.180973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.665380E+09 | 0.144773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.584639E+09 | 0.106552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.589344E+09 | 0.663800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.854473E+10 | 0.152379E+12 | 15178558.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.538344E+09 | 0.403394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.106175E+10 | 0.226772E+11 | 15178558.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.259778E+10 | 0.490219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.240022E+10 | 0.373901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.286207E+10 | 0.110981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.289660E+10 | 0.237268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.370414E+10 | 0.498689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.406904E+10 | 0.648506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.484304E+10 | 0.823708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.513908E+10 | 0.882320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.403752E+10 | 0.654859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.341176E+10 | 0.438286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.269147E+10 | 0.210672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261408E+10 | 0.527451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.412668E+11 | 0.460033E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.240022E+10 | 0.490219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.513908E+10 | 0.882320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.581652E+09 | 0.00 | 0.00 | 0.00 | 0.972942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.538344E+09 | 0.00 | 0.00 | 0.00 | 0.129361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.639845E+09 | 0.00 | 0.00 | 0.00 | 0.195435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.605321E+09 | 0.00 | 0.00 | 0.00 | 0.251928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.707094E+09 | 0.00 | 0.00 | 0.00 | 0.384003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.814909E+09 | 0.00 | 0.00 | 0.00 | 0.470792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.940522E+09 | 0.00 | 0.00 | 0.00 | 0.547548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.106175E+10 | 0.00 | 0.00 | 0.00 | 0.614335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.815929E+09 | 0.00 | 0.00 | 0.00 | 0.470026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.665380E+09 | 0.00 | 0.00 | 0.00 | 0.361216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.584639E+09 | 0.00 | 0.00 | 0.00 | 0.257282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.589344E+09 | 0.00 | 0.00 | 0.00 | 0.157968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.854473E+10 | 0.00 | 0.00 | 0.00 | 0.393719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.538344E+09 | 0.00 | 0.00 | 0.00 | 0.972942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.106175E+10 | 0.00 | 0.00 | 0.00 | 0.614335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.259778E+10 | 0.00 | 0.00 | 0.00 | 0.138782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.240022E+10 | 0.00 | 0.00 | 0.00 | 0.107102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.286207E+10 | 0.00 | 0.00 | 0.00 | 0.321679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.289660E+10 | 0.00 | 0.00 | 0.00 | 0.697384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.370414E+10 | 0.00 | 0.00 | 0.00 | 0.150605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.406904E+10 | 0.00 | 0.00 | 0.00 | 0.193560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.484304E+10 | 0.00 | 0.00 | 0.00 | 0.248485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.513908E+10 | 0.00 | 0.00 | 0.00 | 0.265485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.403752E+10 | 0.00 | 0.00 | 0.00 | 0.191589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.341176E+10 | 0.00 | 0.00 | 0.00 | 0.126794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.269147E+10 | 0.00 | 0.00 | 0.00 | 0.597161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261408E+10 | 0.00 | 0.00 | 0.00 | 0.147265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.412668E+11 | 0.00 | 0.00 | 0.00 | 0.136497E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.240022E+10 | 0.00 | 0.00 | 0.00 | 0.138782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.513908E+10 | 0.00 | 0.00 | 0.00 | 0.265485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112585E+09 | 0.108648E+09 | 0.00 | 2926835.70 | 0.00 | 13020278.93 | 0.287048E+09 | 0.00 | 0.14 |
February | 61662715.79 | 0.257233E+09 | 0.00 | 2996619.40 | 0.00 | 0.00 | 0.141958E+09 | 0.00 | 0.14 |
March | 39466208.36 | 0.545472E+09 | 0.00 | 3486680.15 | 0.00 | 0.00 | 0.104188E+09 | 0.00 | 0.15 |
April | 2675513.72 | 0.106034E+10 | 0.00 | 4043522.04 | 0.00 | 0.00 | 49804842.84 | 0.00 | 0.15 |
May | 0.00 | 0.203693E+10 | 0.00 | 2736169.02 | 0.00 | 0.00 | 5205803.91 | 0.00 | 0.15 |
June | 0.00 | 0.307326E+10 | 0.00 | 1177001.24 | 0.00 | 0.00 | 909005.03 | 0.00 | 0.16 |
July | 0.00 | 0.406028E+10 | 0.00 | 1129912.07 | 0.00 | 0.00 | 819837.65 | 0.00 | 0.15 |
August | 0.00 | 0.456118E+10 | 0.00 | 65140.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
September | 0.00 | 0.335121E+10 | 0.00 | 1094946.28 | 0.00 | 0.00 | 1129457.51 | 0.00 | 0.15 |
October | 0.00 | 0.217247E+10 | 0.00 | 1388483.82 | 0.00 | 0.00 | 7230116.87 | 0.00 | 0.14 |
November | 0.00 | 0.127104E+10 | 0.00 | 2735834.68 | 0.00 | 0.00 | 13783310.33 | 0.00 | 0.14 |
December | 45378590.98 | 0.414739E+09 | 0.00 | 3246187.99 | 0.00 | 0.00 | 0.128255E+09 | 0.00 | 0.14 |
Annual Sum or Average | 0.261768E+09 | 0.229128E+11 | 0.00 | 27027332.85 | 0.00 | 13020278.93 | 0.740331E+09 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.108648E+09 | 0.00 | 65140.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.112585E+09 | 0.456118E+10 | 0.00 | 4043522.04 | 0.00 | 13020278.93 | 0.287048E+09 | 0.00 | 0.16 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.281335E+10 | 19370570.46 | 0.00 | 294743.98 | 1167860.73 | 0.00 | 0.400205E+09 | 0.00 | 0.20 |
February | 0.145162E+10 | 0.204827E+09 | 0.00 | 1966018.03 | 0.00 | 0.00 | 0.966818E+09 | 0.00 | 0.20 |
March | 0.934075E+09 | 0.877910E+09 | 0.00 | 4318369.76 | 544658.52 | 0.00 | 0.891536E+09 | 0.00 | 0.22 |
April | 0.380780E+09 | 0.271273E+10 | 0.00 | 3516452.67 | 175765.22 | 0.00 | 0.465070E+09 | 0.00 | 0.22 |
May | 1290174.92 | 0.811574E+10 | 0.00 | 1531107.66 | 875155.28 | 0.00 | 64302639.67 | 0.00 | 0.25 |
June | 0.00 | 0.136159E+11 | 0.00 | 248529.37 | 0.00 | 0.00 | 4771311.40 | 0.00 | 0.28 |
July | 0.00 | 0.198981E+11 | 0.00 | 272329.99 | 0.00 | 0.00 | 982177.35 | 0.00 | 0.29 |
August | 0.00 | 0.219652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
September | 0.00 | 0.149528E+11 | 0.00 | 28704.32 | 2737497.96 | 0.00 | 231723.92 | 0.00 | 0.27 |
October | 0.00 | 0.781634E+10 | 0.00 | 1508035.54 | 8746992.41 | 0.00 | 83781086.82 | 0.00 | 0.24 |
November | 0.183316E+09 | 0.280671E+10 | 0.00 | 2431489.01 | 0.00 | 0.00 | 0.181272E+09 | 0.00 | 0.21 |
December | 0.140936E+10 | 0.340496E+09 | 0.00 | 2546024.15 | 1102249.82 | 0.00 | 0.902328E+09 | 0.00 | 0.20 |
Annual Sum or Average | 0.717378E+10 | 0.933262E+11 | 0.00 | 18661804.48 | 15350179.95 | 0.00 | 0.396130E+10 | 0.00 | 0.24 |
Minimum of Months | 0.00 | 19370570.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.281335E+10 | 0.219652E+11 | 0.00 | 4318369.76 | 8746992.41 | 0.00 | 0.966818E+09 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:42:35
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.501093E+12 | 0.196241E+11 | 0.00 | 0.100973E+11 | 0.564414E+10 |
February | 0.568387E+12 | 0.225622E+11 | 0.00 | 0.740166E+10 | 0.114689E+11 |
March | 0.738190E+12 | 0.221482E+11 | 0.00 | 0.448625E+10 | 0.242435E+11 |
April | 0.811953E+12 | 0.313101E+11 | 0.00 | -0.267998E+10 | 0.432217E+11 |
May | 0.899888E+12 | 0.515038E+11 | 0.00 | -0.152784E+11 | 0.832863E+11 |
June | 0.889556E+12 | 0.559743E+11 | 0.00 | -0.244824E+11 | 0.106620E+12 |
July | 0.895632E+12 | 0.415893E+11 | 0.00 | -0.341215E+11 | 0.132931E+12 |
August | 0.865666E+12 | 0.549696E+11 | 0.00 | -0.367512E+11 | 0.143601E+12 |
September | 0.746797E+12 | 0.538169E+11 | 0.00 | -0.267631E+11 | 0.107443E+12 |
October | 0.636352E+12 | 0.452736E+11 | 0.00 | -0.161273E+11 | 0.745975E+11 |
November | 0.497348E+12 | 0.284216E+11 | 0.00 | -0.342526E+10 | 0.402668E+11 |
December | 0.454716E+12 | 0.217452E+11 | 0.00 | 0.737147E+10 | 0.149648E+11 |
Annual Sum or Average | 0.850558E+13 | 0.448939E+12 | 0.00 | -0.130272E+12 | 0.788288E+12 |
Minimum of Months | 0.454716E+12 | 0.196241E+11 | 0.00 | -0.367512E+11 | 0.564414E+10 |
Maximum of Months | 0.899888E+12 | 0.559743E+11 | 0.00 | 0.100973E+11 | 0.143601E+12 |