Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2023-10-16 10:41:43
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1172.70 | 242.54 | 242.54 |
Net Site Energy | 1172.70 | 242.54 | 242.54 |
Total Source Energy | 3680.82 | 761.27 | 761.27 |
Net Source Energy | 3680.82 | 761.27 | 761.27 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 15.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 96.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 138.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1156.80 | 15.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 15.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 96.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 13.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 124.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 24.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 15.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 96.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 138.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 24.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 53.72 | 3.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 239.25 | 3.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 53.72 | 3.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 239.25 | 3.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1156.799 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1156.799 | 100.00 |
Total On-Site and Utility Electric Sources | 1156.799 | 100.00 |
Total Electricity End Uses | 1156.799 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 24.17 |
Time Setpoint Not Met During Occupied Cooling | 20.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2879.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.61 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7186 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 15.0695 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 9.6875 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 11.2890 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 11.2890 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.7186 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 15.0695 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 9.6875 | 46.45 | 2.5587 | |
Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 11.2890 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 15-JUN-14:00 | 27-DEC-06:10 | - | - | - | - | - | - | - | - | - | - | 17-AUG-11:30 |
Heating | 0.00 | 75412.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 27206.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 12183.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1710.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 97407.09 | 75412.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 75412.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 27206.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 9878.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1710.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 17.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 305.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1974.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 424.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 438.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 79.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3663.58 | 17.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 3.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 63.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 90.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 757.70 | 3.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 3.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 63.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 90.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 757.70 | 3.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.51 |
ZONE2 FINE STORAGE DIRECT AIR | 4.78 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 2.74 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 2.74 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 97096.60 |
PSZ-OFFICE HEATING COIL | 32757.36 |
PSZ-FINE STORAGE HEATING COIL | 131878.87 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 97096.61 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.51 | 1.51 | 1.51 | 1.51 | 1.51 | 1.51 | 1.00 | 1.00 | 1.51 |
PSZ-FINE STORAGE | 4.78 | 4.78 | 4.78 | 4.78 | 4.78 | 4.78 | 1.00 | 1.00 | 4.78 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.51 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 4.78 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.51 | 1647.85 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 4.78 | 8230.60 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.51 | 1.51 | 1.51 | 1.51 | 25368.34 | 32757.36 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 4.78 | 4.78 | 4.78 | 4.78 | 97069.69 | 131878.87 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.51 | 0.752785 | 1.51 | 25368.34 | 13103.56 | 25368.34 | 0.800190 | 0.800190 |
PSZ-FINE STORAGE COOLING COIL | 4.78 | 2.39 | 4.78 | 97069.69 | 49543.38 | 97069.69 | 0.770720 | 0.770720 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.719 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.792 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 15.069 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15.069 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 9.688 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 12.246 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2539.013 | 10.719 | 199.158 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2539.013 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 20997.932 | 15.069 | 699.931 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20997.932 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 31046.942 | 9.688 | 449.956 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 31046.942 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5959 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.7823 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 1.301 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 1.301 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.678 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.179 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6691 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6691 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53319041E-11 | 0.92099297E-16 | 0.18475806E-15 | 0.0000000 |
5 | 1 | -5.2159728 | 0.43155192E-04 | -0.26885250E-04 | 0.68722794E-11 |
6 | 0 | 5.8118483 | 0.59583229 | 0.59590233 | |
7 | 4 | 0.72249793E-12 | -0.16720573E-15 | 0.22015083E-14 | 0.12409536E-15 |
8 | 3 | -0.36459118E-03 | 0.53555631E-06 | -0.52695411E-04 | 0.13865996E-12 |
9 | 2 | 1.6915239 | 0.11971291E-01 | 1.1039557 | -0.69896550E-04 |
10 | 1 | -7.1930661 | 0.31446443 | -16.864389 | 0.32415671 |
11 | 0 | 6.0306730 | 0.20232993 | 16.289252 | |
12 | 4 | 0.62407051E-12 | 0.80447548E-15 | -0.19405657E-14 | 0.12807081E-15 |
13 | 3 | -0.32959465E-03 | 0.84747600E-06 | -0.47309261E-04 | 0.11981323E-12 |
14 | 2 | 1.6058071 | 0.19756964E-01 | 1.0389034 | -0.63182077E-04 |
15 | 1 | -7.3135607 | 0.53269638 | -16.443412 | 0.30760774 |
16 | 0 | 6.6091660 | 0.34862863 | 16.305639 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.19405657E-14 | 0.80447548E-15 | 0.62407051E-12 | 0.12807081E-15 |
85 | 3 | -0.47309261E-04 | 0.84747600E-06 | -0.32959465E-03 | 0.11981323E-12 |
86 | 2 | 1.0389034 | 0.19756964E-01 | 1.6058071 | -0.63182077E-04 |
87 | 1 | -16.443412 | 0.53269638 | -7.3135607 | 0.30760774 |
88 | 0 | 16.305639 | 0.34862863 | 6.6091660 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.6283_SHGC_SOUTH_0.25 | 34 | 1 | VerySmooth | 3.572 | 3.572 | 1.000 | 0.252 | ||
2 | NONRESWINDOW_U_0.6283_SHGC_NORTH_0.25 | 35 | 1 | VerySmooth | 3.572 | 3.572 | 1.000 | 0.252 | ||
3 | NONRESWINDOW_U_0.6283_SHGC_EAST_0.25 | 36 | 1 | VerySmooth | 3.572 | 3.572 | 1.000 | 0.252 | ||
4 | NONRESWINDOW_U_0.6283_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 3.572 | 3.572 | 1.000 | 0.252 | ||
5 | SKYLIGHT_U_1.02_SHGC_0.39 | 38 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.391 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.15349 | 0.58024 | 0.58024 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.80019E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.15349 | 0.58024 | 0.58024 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.80019E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.15349 | 0.58024 | 0.58024 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.80019E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.15349 | 0.58024 | 0.58024 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.80019E-002 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.22227 | 0.21773 | 0.21773 | 0.39000 | 0.13867 | 0.18233 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.849 | 0.366 | 0.255 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 0.153 | 6.473E-004 | 9.992E-004 | 0.546 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.780 | 5.598E-004 | 3.565E-004 | 0.951 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 3.433 | 1.071E-003 | 6.996E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 13226.19116 | 15871.42939 | 1.25464 | 1.50557 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 37.14667 | 6.86994E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 9735.44849 | 11682.53819 | 0.31511 | 0.37814 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20000 | 2.80840E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 53875.20677 | 64650.24813 | 3.98366 | 4.78039 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 38.10000 | 6.87148E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 31694.76475 | 38033.71769 | 0.86407 | 1.03689 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | -5.20000 | 2.80840E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 37.97000 | 6.87126E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 80913.83832 | 97096.60599 | 2.27953 | 2.73543 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 20237.41 | 1.50557 | 1.50557 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 10337.27 | 0.37814 | 0.37814 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 78822.78 | 4.78039 | 4.78039 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 35849.12 | 1.03689 | 1.03689 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.50557 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.78039 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.73543 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 2.73543 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 97096.60008 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 97096.60599 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.50557 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.50557 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.50557 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.50557 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.50557 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.50557 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.78039 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.78039 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.78039 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 4.78039 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.78039 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 4.78039 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.50557 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 4.78039 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.50557 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.50557 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1647.85487 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.50557 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.50557 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.50557 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.50557 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.50557 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.75279 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.50557 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25368.34000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 13103.55962 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 25368.34000 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80019 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80019 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25368.34000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32757.35825 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 32757.35825 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.78039 |
47 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.78039 |
49 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 8230.59764 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.78039 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.78039 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.78039 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.78039 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.78039 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.39020 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.78039 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 97069.69000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 49543.38400 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 97069.69000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.77072 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.77072 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 97069.69000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 131878.87244 |
64 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
66 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 131878.87244 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 24200.0 | 10.73 | 10.11 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 93357.4 | 10.29 | 9.69 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 6.0027136526E-002 | 3.6641803916E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.1256879435 | 0.1284082139 | Pass | Pass | 8.7930926150E-002 | 0.6768367485 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 6.6571669247E-002 | 5.5281976363E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 11471.84 | 652.75 | 0.00 | 74.75 | 418.61 | 12618.03 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.089 | 1.301 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.089 | 1.301 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.089 | 1.301 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.551 | 0.596 | 3204.84 | 3170.23 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.992 | 1.301 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.992 | 1.301 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.6283_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.572 | 0.252 | 0.251 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.6283_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.572 | 0.252 | 0.251 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.6283_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.572 | 0.252 | 0.251 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.6283_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.572 | 0.252 | 0.251 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.27 | 5.046 | 0.450 | 0.450 | |||||||||||||||||
North Total or Average | 6.51 | 3.572 | 0.252 | 0.251 | |||||||||||||||||
Non-North Total or Average | 45.76 | 5.256 | 0.478 | 0.478 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.7186 | 236.88 | 2539.01 | LightsWired | LTG_SCH_OFFICE | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.86 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 15.0695 | 1393.41 | 20997.93 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 239.15 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 9.6875 | 3204.84 | 31046.94 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 353.60 |
Interior Lighting Total | 11.2890 | 4835.13 | 54583.89 | 623.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 8532.22 | AstronomicalClock | - | 83.77 | 83.77 | 134.16 | |
Exterior Lighting Total | 8532.22 | 134.16 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25368.34 | 20299.49 | 5068.85 | 0.80 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 97069.69 | 74813.55 | 22256.14 | 0.77 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 24200.0 | 10.73 | 10.11 | ||||
PSZ-FINE STORAGE COOLING COIL | 93357.4 | 10.29 | 9.69 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 97096.60 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 32757.36 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 131878.87 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.74 | 254.15 | 92.91 | 1.00 | 3.40 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 1.51 | 1647.85 | 1094.51 | 1.00 | 1.33 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.59 | 1018.41 | 4.78 | 8230.60 | 1721.74 | 1.00 | 1.16 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 13226.19 | 15871.43 | 67.00 | 1.255 | 1.506 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 23.90 | 23.90 | 0.00816 | 37.15 | 0.00687 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 53875.21 | 64650.25 | 46.40 | 3.984 | 4.780 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 26.70 | 26.70 | 0.00807 | 38.10 | 0.00687 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 37.96 | 0.00696 | 37.97 | 0.00687 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9735.45 | 11682.54 | 49.32 | 0.315 | 0.378 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00772 | -5.20 | 0.00281 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 31694.76 | 38033.72 | 27.30 | 0.864 | 1.037 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 15.56 | 15.56 | 0.00661 | -5.20 | 0.00281 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 80913.84 | 97096.61 | 30.30 | 2.280 | 2.735 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00601 | -5.20 | 0.00281 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.51 | 1.51 | 0.38 | 0.38 | 1.5056 | 1.5056 | 1.5056 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 4.78 | 4.78 | 1.04 | 1.04 | 4.7804 | 4.7804 | 4.7804 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 97096.600 | 97096.600 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 97096.60 | 97096.60 | 2.735433 | 10.00 | 7.07 | 0.00601425 | 43.33 | 20.46 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 10.00 | 0.00601425 | 68.5340 | 97096.61 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 25368.340 | 20299.492 | 1.505570 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 25368.34 | 25089.40 | 1.505570 | 25.84 | 15.21 | 0.00807677 | 12.00 | 10.01 | 0.00800000 | 37.32 | 0.00687023 | 17.93 | 6.7937 | 23.90 | 0.00816473 | 38.3696 | 13223.86 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 32757.358 | 32757.358 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 32757.36 | 32757.36 | 1.505570 | 19.27 | 12.27 | 0.00738901 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 6.7937 | 21.10 | 0.00772289 | 43.0560 | 9735.45 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 97069.690 | 74813.551 | 4.780390 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 97069.69 | 97069.69 | 4.780390 | 29.33 | 16.27 | 0.00796193 | 12.00 | 9.97 | 0.00796193 | 38.10 | 0.00687148 | 18.17 | 8.8844 | 26.70 | 0.00806826 | 32.1034 | 53875.21 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 131878.872 | 131878.872 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 131878.87 | 131878.87 | 4.780391 | 13.71 | 8.97 | 0.00627478 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 8.8844 | 15.56 | 0.00661278 | 52.2991 | 31694.76 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 97096.600 | 97096.600 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 2.735433 | 2.85669919 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 97096.60 | 97096.60 | 1.0000 | 2.85669919 | 2.735433 | 10.00 | 7.07 | 0.00601425 | 25199.4 | 43.33 | 20.46 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 97096.60 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 10.00 | 0.00601425 | 10.00 | 0.00601425 | 68.5340 | 97096.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25368.340 | 20299.492 | 1.505570 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.8543 | 1004.8586 | 1.0443 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.505570 | 1.57231474 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | Sensible | 25368.34 | 25089.40 | 1.0000 | 1.57231453 | 1.505570 | 25.84 | 15.21 | 0.00807677 | 46551.3 | 12.00 | 10.01 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25368.34 | 37.32 | 0.00687023 | 17.93 | 0.10228463 | 6.7937 | 23.90 | 0.00816473 | 23.90 | 0.00816473 | 38.3696 | 13223.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32757.358 | 32757.358 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.505570 | 1.57231474 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 32757.36 | 32757.36 | 1.0000 | 1.57231474 | 1.505570 | 19.27 | 12.27 | 0.00738901 | 38104.3 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32757.36 | -5.20 | 0.00280840 | -5.20 | 0.10228463 | 6.7937 | 21.05 | 0.00772289 | 21.10 | 0.00772289 | 43.0560 | 9735.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 97069.690 | 74813.551 | 4.780390 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6408 | 1004.8586 | 1.0443 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 4.780391 | 4.99231453 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 97069.69 | 97069.69 | 1.0000 | 4.99231297 | 4.780390 | 29.33 | 16.27 | 0.00796193 | 49817.7 | 12.00 | 9.97 | 0.00796193 | 32148.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 97069.69 | 38.10 | 0.00687148 | 18.17 | 0.42471127 | 8.8844 | 26.70 | 0.00806826 | 26.70 | 0.00806826 | 32.1034 | 53875.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 131878.872 | 131878.872 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 4.780391 | 4.99231453 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | Sensible | 131878.87 | 131878.87 | 1.0000 | 4.99231453 | 4.780391 | 13.71 | 8.97 | 0.00627478 | 29630.5 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 131878.87 | -5.20 | 0.00280840 | -5.20 | 0.42471127 | 8.8844 | 15.56 | 0.00661278 | 15.56 | 0.00661278 | 52.2991 | 31694.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.51 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 4.78 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2091.00 | 1783.67 | 599.17 |
ZONE2 FINE STORAGE | 2811.50 | 2678.67 | 1989.83 |
ZONE3 BULK STORAGE | 3132.00 | 3306.33 | 2871.00 |
Facility | 3444.17 | 3407.50 | 2879.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 20.67 | 25.50 | 20.50 | 20.67 |
ZONE2 FINE STORAGE | 31.17 | 175.83 | 5.33 | 0.17 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 50.17 | 198.83 | 24.17 | 20.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 1.147 | 0.377 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1.276 | 0.397 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.171 | 0.000 | 1.016 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.54 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 4144320.97 | 0.00 | 4144320.97 | 2540397.15 | 6684718.12 | 3225648.14 | 5582.98 | 1864.90 | 1312.12 | 0.62 |
ZONE2 FINE STORAGE | 14017040.93 | 0.00 | 14017040.93 | 11108117.21 | 25125158.13 | 13393694.68 | 5560.96 | 2046.61 | 1152.43 | 59.15 |
ZONE3 BULK STORAGE | 0.00 | 0.22E+09 | 0.22E+09 | 44570327.94 | 0.27E+09 | 30805497.77 | 6571.20 | 30.05 | 2158.75 | 4864.96 |
Total Facility | 18161361.89 | 0.22E+09 | 0.24E+09 | 58218842.30 | 0.30E+09 | 47424840.58 | 7573.23 | 2371.59 | 3580.09 | 4866.77 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.3164 | 0.0000 | 0.3164 | 0.1042 | 0.4207 | 0.1023 | 459.60 | 1864.90 | 1311.50 |
ZONE2 FINE STORAGE | 1.0187 | 0.0000 | 1.0187 | 0.3191 | 1.3378 | 0.4247 | 496.11 | 2046.61 | 1093.28 |
ZONE3 BULK STORAGE | 0.0000 | 9.5070 | 9.5070 | 1.6443 | 11.1512 | 0.9768 | 2425.89 | 14.58 | 1195.53 |
Total Facility | 1.3351 | 9.5070 | 10.8421 | 2.0676 | 12.9097 | 1.5038 | 2449.23 | 2356.13 | 2568.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 4519915.66 | 0.00 | 4519915.66 | 3225648.14 | 5582.16 | 0.08 | 3177.76 | 0.62 |
PSZ-FINE STORAGE | 15287388.05 | 0.00 | 15287388.05 | 13393694.68 | 5560.07 | 0.39 | 3199.54 | 59.15 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.3451 | 0.0000 | 0.3451 | 0.1023 | 458.78 | 0.08 | 3177.14 |
PSZ-FINE STORAGE | 1.1110 | 0.0000 | 1.1110 | 0.4247 | 495.22 | 0.39 | 3140.39 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2469.33 | 715.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2707.79 | 494.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.3647 | 0.4961 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 1.1914 | 1.7947 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 383 |
Defaulted Fields | 319 |
Fields with Defaults | 1020 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1156.80 | 6718.26 | 01-JAN-07:30 | 97407.09 | 15-JUN-15:00 |
Electricity:Building | 776.29 | 6235.26 | 01-JAN-00:10 | 58611.10 | 19-APR-12:30 |
Electricity:Zone:ZONE1 OFFICE | 62.81 | 1030.77 | 01-JAN-00:10 | 3867.54 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 762.90 | 6235.26 | 01-JAN-00:10 | 56305.80 | 02-JAN-09:10 |
InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 474.33 | 3104.69 | 01-JAN-00:10 | 36895.31 | 19-APR-12:30 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 138.30 | 0.00 | 01-JAN-00:10 | 12183.75 | 19-APR-15:30 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 13.39 | 0.00 | 01-JAN-00:10 | 2305.29 | 19-APR-15:30 |
Ventilation (simple):Fans:Electricity | 13.39 | 0.00 | 01-JAN-00:10 | 2305.29 | 19-APR-15:30 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 13.39 | 0.00 | 01-JAN-00:10 | 2305.29 | 19-APR-15:30 |
ElectricityPurchased:Facility | 1156.80 | 6718.26 | 01-JAN-07:30 | 97407.09 | 15-JUN-15:00 |
ElectricityPurchased:Plant | 1156.80 | 6718.26 | 01-JAN-07:30 | 97407.09 | 15-JUN-15:00 |
Cogeneration:ElectricityPurchased | 1156.80 | 6718.26 | 01-JAN-07:30 | 97407.09 | 15-JUN-15:00 |
General:Cogeneration:ElectricityPurchased | 1156.80 | 6718.26 | 01-JAN-07:30 | 97407.09 | 15-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1156.80 | 6718.26 | 01-JAN-07:30 | 97407.09 | 15-JUN-15:00 |
ElectricityNet:Plant | 1156.80 | 6718.26 | 01-JAN-07:30 | 97407.09 | 15-JUN-15:00 |
Cogeneration:ElectricityNet | 1156.80 | 6718.26 | 01-JAN-07:30 | 97407.09 | 15-JUN-15:00 |
General:Cogeneration:ElectricityNet | 1156.80 | 6718.26 | 01-JAN-07:30 | 97407.09 | 15-JUN-15:00 |
Electricity:HVAC | 221.39 | 0.00 | 01-JAN-00:10 | 39026.05 | 15-JUN-15:10 |
General:Fans:Electricity | 124.91 | 0.00 | 01-JAN-00:10 | 10132.60 | 28-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 96.48 | 0.00 | 01-JAN-00:10 | 29147.60 | 15-JUN-15:10 |
General:Cooling:Electricity | 96.48 | 0.00 | 01-JAN-00:10 | 29147.60 | 15-JUN-15:10 |
ExteriorLights:Electricity | 134.16 | 0.00 | 01-JAN-07:20 | 8532.22 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 134.16 | 0.00 | 01-JAN-07:20 | 8532.22 | 01-JAN-00:10 |
Electricity:Plant | 24.95 | 483.00 | 04-JAN-06:10 | 2049.61 | 25-JAN-13:00 |
WaterSystems:Electricity | 24.95 | 483.00 | 04-JAN-06:10 | 2049.61 | 25-JAN-13:00 |
Water Heater:WaterSystems:Electricity | 24.95 | 483.00 | 04-JAN-06:10 | 2049.61 | 25-JAN-13:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 15.90 | 0.00 | 01-JAN-00:10 | 75412.51 | 27-DEC-06:10 |
NaturalGas:HVAC | 15.90 | 0.00 | 01-JAN-00:10 | 75412.51 | 27-DEC-06:10 |
Heating:NaturalGas | 15.90 | 0.00 | 01-JAN-00:10 | 75412.51 | 27-DEC-06:10 |
General:Heating:NaturalGas | 15.90 | 0.00 | 01-JAN-00:10 | 75412.51 | 27-DEC-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 17-AUG-11:30 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 17-AUG-11:30 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 17-AUG-11:30 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 17-AUG-11:30 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 17-AUG-11:30 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 17-AUG-11:30 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 17-AUG-11:30 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 17-AUG-11:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 615.24 | 0.00 | 01-JAN-00:10 | 144641.49 | 15-JUN-15:10 |
EnergyTransfer:Building | 287.56 | 0.00 | 01-JAN-00:10 | 64027.40 | 15-JUN-15:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 64.66 | 0.00 | 01-JAN-00:10 | 17181.43 | 27-DEC-06:10 |
Heating:EnergyTransfer | 29.71 | 0.00 | 01-JAN-00:10 | 58268.45 | 27-DEC-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 6.06 | 0.00 | 01-JAN-00:10 | 17181.43 | 27-DEC-06:10 |
General:Heating:EnergyTransfer | 29.71 | 0.00 | 01-JAN-00:10 | 58268.45 | 27-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 6.06 | 0.00 | 01-JAN-00:10 | 17181.43 | 27-DEC-06:10 |
Cooling:EnergyTransfer | 257.86 | 0.00 | 01-JAN-00:10 | 64027.40 | 15-JUN-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 58.60 | 0.00 | 01-JAN-00:10 | 14373.73 | 05-JUN-17:00 |
General:Cooling:EnergyTransfer | 257.86 | 0.00 | 01-JAN-00:10 | 64027.40 | 15-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 58.60 | 0.00 | 01-JAN-00:10 | 14373.73 | 05-JUN-17:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 222.36 | 0.00 | 01-JAN-00:10 | 50816.22 | 15-JUN-15:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 23.11 | 0.00 | 01-JAN-00:10 | 24245.16 | 26-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 23.11 | 0.00 | 01-JAN-00:10 | 24245.16 | 26-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 199.25 | 0.00 | 01-JAN-00:10 | 50816.22 | 15-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 199.25 | 0.00 | 01-JAN-00:10 | 50816.22 | 15-JUN-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.55 | 0.00 | 01-JAN-00:10 | 26911.95 | 31-DEC-07:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.55 | 0.00 | 01-JAN-00:10 | 26911.95 | 31-DEC-07:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.55 | 0.00 | 01-JAN-00:10 | 26911.95 | 31-DEC-07:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 327.67 | 0.00 | 01-JAN-00:10 | 80614.09 | 15-JUN-15:10 |
HeatingCoils:EnergyTransfer | 10.72 | 0.00 | 01-JAN-00:10 | 56960.25 | 27-DEC-06:10 |
CoolingCoils:EnergyTransfer | 316.95 | 0.00 | 01-JAN-00:10 | 80614.09 | 15-JUN-15:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 6.055 | -58.603 | 0.000 | 0.000 | 9.356 | 30.864 | 31.946 | 11.535 | 0.000 | 3.165 | 0.000 | 0.000 | -9.044 | 0.000 | -16.845 | -8.429 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 23.106 | -199.246 | 0.000 | 0.000 | 19.427 | 239.148 | 0.000 | 0.000 | 0.000 | 9.587 | 0.001 | 0.000 | 0.000 | 0.000 | -68.717 | -23.305 |
ZONE3 BULK STORAGE | 0.545 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 43.009 | 353.598 | 107.344 | 194.391 | 0.000 | 10.519 | 0.019 | 0.000 | -83.038 | 0.000 | -545.771 | -80.597 |
Total Facility | 0.545 | 0.000 | 29.161 | -257.848 | 0.000 | 0.000 | 71.793 | 623.610 | 139.290 | 205.926 | 0.000 | 23.270 | 0.020 | 0.000 | -92.082 | 0.000 | -631.333 | -112.331 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 17-MAY-05:01 | 0.00 | 0.00 | 0.00 | -33483.73 | 0.00 | 0.00 | 81.19 | 583.97 | 573.75 | 0.00 | 0.00 | 0.00 | 33269.69 | 0.00 | -674.02 | 0.00 | -350.85 | 0.00 |
ZONE2 FINE STORAGE | 24-SEP-12:57 | 0.00 | 0.00 | 0.00 | -95693.76 | 0.00 | 0.00 | 0.00 | 2099.79 | 0.00 | 0.00 | 0.00 | 0.00 | 94672.02 | 0.00 | -0.00 | 0.00 | -1078.05 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-JUN-05:43 | 0.00 | 0.00 | 0.00 | -105248.24 | 0.00 | 0.00 | 602.97 | 5788.46 | 2623.78 | 0.00 | 0.00 | 11.78 | 113450.93 | 0.00 | -3726.91 | 0.00 | -13502.77 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 27-DEC-06:01 | 0.00 | 0.00 | 32977.90 | 0.00 | 0.00 | 0.00 | 146.81 | 583.97 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -941.20 | 0.00 | -1536.71 | -31804.52 |
ZONE2 FINE STORAGE | 27-DEC-06:01 | 0.00 | 0.00 | 127982.02 | 0.00 | 0.00 | 0.00 | 368.88 | 2099.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -5782.60 | -124668.09 |
ZONE3 BULK STORAGE | 31-DEC-06:53 | 26923.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 10584.87 | 0.00 | -8727.00 | 0.00 | -31885.63 | 0.00 |
Total Facility | 27-DEC-06:01 | 17139.36 | 0.00 | 160959.92 | 0.00 | 0.00 | 0.00 | 1430.59 | 5788.46 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9847.64 | 0.00 | -25887.16 | -152207.31 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.5056 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.5056 | 0.0679 | 1.0000 | Not calculated | 0.1023 | 0.0679 | ||
PSZ-FINE STORAGE | 4.7804 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 4.7804 | 0.0888 | 1.0000 | Not calculated | 0.4247 | 0.0888 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.5056 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.5056 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0679 | ||
PSZ-FINE STORAGE | 4.7804 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 4.7804 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.0888 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5056 | 1.5056 | 1.5056 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.7804 | 4.7804 | 4.7804 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.5056 | 1.5056 | 1.5056 | 1.5056 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 4.7804 | 4.7804 | 4.7804 | 4.7804 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5056 | 1.5056 | 1.5056 | No | 0.1023 | 0.2705 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.7804 | 4.7804 | 4.7804 | No | 0.4247 | 0.4096 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.5056 | 1.5056 | 1.5056 | 1.5056 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 4.7804 | 4.7804 | 4.7804 | 4.7804 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 24.17 |
Number of hours cooling loads not met | 20.83 |
Number of hours not met | 45.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 15.90 | 75412.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 96.48 | 29147.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 623.61 | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 134.16 | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 13.39 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 124.91 | 10132.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 24.95 | 2049.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 1156.80 |
Natural Gas | 0.00 | 15.90 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 1172.70 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 128.97 |
Space Heating | 0.00 |
Space Cooling | 19.95 |
Fans (All) | 28.60 |
Service Water Heating | 5.16 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 239.25 |
Subtotal | 239.25 |
Natural Gas [MJ/m2] | |
Space Heating | 3.29 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 3.29 |
Subtotal | 3.29 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 53.18 |
Space Heating | 1.36 |
Space Cooling | 8.23 |
Fans (All) | 11.79 |
Service Water Heating | 2.13 |
Receptacle Equipment | 11.88 |
Miscellaneous | 11.44 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 3430. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 7007.50 | 1752.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7715.67 | 1044.33 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 5113.33 | 3398.83 | 247.83 | 0.00 | 0.00 |
Min | 5113.33 | 1044.33 | 0.00 | 0.00 | 0.00 |
Max | 7715.67 | 3398.83 | 247.83 | 0.00 | 0.00 |
Average | 6612.17 | 2065.22 | 82.61 | 0.00 | 0.00 |
Sum | 19836.50 | 6195.67 | 247.83 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 70519.50 | 12199.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 101838.17 | 78735.33 | 10619.50 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 101838.17 | 78735.33 | 10619.50 | 0.00 | 0.00 |
Average | 68461.56 | 30311.61 | 3539.83 | 0.00 | 0.00 |
Sum | 205384.67 | 90934.83 | 10619.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 7381.83 | 1378.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7440.17 | 1319.83 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 5770.33 | 2989.67 | 0.00 | 0.00 | 0.00 |
Min | 5770.33 | 1319.83 | 0.00 | 0.00 | 0.00 |
Max | 7440.17 | 2989.67 | 0.00 | 0.00 | 0.00 |
Average | 6864.11 | 1895.89 | 0.00 | 0.00 | 0.00 |
Sum | 20592.33 | 5687.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 32857.17 | 169.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 68158.50 | 14560.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 118078.50 | 73114.50 | 0.00 | 0.00 | 0.00 |
Min | 32857.17 | 169.83 | 0.00 | 0.00 | 0.00 |
Max | 118078.50 | 73114.50 | 0.00 | 0.00 | 0.00 |
Average | 73031.39 | 29281.61 | 0.00 | 0.00 | 0.00 |
Sum | 219094.17 | 87844.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.245671E+09 | 3305.81 | 12-JAN-15:30 | 18.90 | 10.10 | 0.565051E+09 | 768.97 | 18-JAN-16:00 | 11.70 | 5.72 |
February | 0.541517E+09 | 3926.48 | 21-FEB-17:00 | 22.20 | 7.81 | 0.538629E+09 | 768.97 | 06-FEB-13:09 | 22.20 | 7.81 |
March | 0.162593E+10 | 5353.58 | 14-MAR-16:00 | 24.40 | 10.33 | 0.658186E+09 | 768.96 | 30-MAR-12:09 | 17.30 | 5.95 |
April | 0.436760E+10 | 29573.64 | 28-APR-05:03 | 14.22 | 8.86 | 0.631240E+09 | 769.03 | 29-APR-09:09 | 22.48 | 14.18 |
May | 0.742482E+10 | 33484.07 | 17-MAY-05:01 | 14.08 | 5.19 | 0.659923E+09 | 769.07 | 24-MAY-13:00 | 30.00 | 18.55 |
June | 0.970877E+10 | 32879.50 | 13-JUN-05:01 | 15.18 | 4.59 | 0.660210E+09 | 769.06 | 29-JUN-14:50 | 27.93 | 18.22 |
July | 0.957108E+10 | 25735.16 | 11-JUL-05:01 | 21.70 | 15.06 | 0.635052E+09 | 769.09 | 17-JUL-15:00 | 30.60 | 21.38 |
August | 0.968698E+10 | 28691.14 | 23-AUG-05:01 | 20.00 | 11.78 | 0.685713E+09 | 769.08 | 03-AUG-12:09 | 20.00 | 11.78 |
September | 0.816265E+10 | 33091.84 | 30-SEP-05:02 | 9.72 | 6.50 | 0.634895E+09 | 769.07 | 13-SEP-13:39 | 9.72 | 6.50 |
October | 0.519995E+10 | 26403.10 | 02-OCT-05:01 | 23.72 | 15.10 | 0.633903E+09 | 769.07 | 04-OCT-13:50 | 29.82 | 19.34 |
November | 0.180177E+10 | 6599.07 | 03-NOV-16:00 | 23.90 | 13.45 | 0.587545E+09 | 769.01 | 03-NOV-12:00 | 23.90 | 13.45 |
December | 0.267128E+09 | 3126.94 | 16-DEC-16:00 | 15.00 | 4.18 | 0.567472E+09 | 768.97 | 11-DEC-16:30 | 15.00 | 4.18 |
Annual Sum or Average | 0.586039E+11 | 0.745782E+10 | ||||||||
Minimum of Months | 0.245671E+09 | 3126.94 | 9.72 | 4.18 | 0.538629E+09 | 768.96 | 9.72 | 4.18 | ||
Maximum of Months | 0.970877E+10 | 33484.07 | 24.40 | 15.10 | 0.685713E+09 | 769.09 | 30.60 | 21.38 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7078849.71 | 1504.68 | 27-JAN-09:10 | -1.2 | -5.7 | 0.122815E+10 | 2246.64 | 12-JAN-15:30 | -1.2 | -5.7 |
February | 43835588.25 | 3977.13 | 22-FEB-14:00 | 21.70 | 7.92 | 0.127181E+10 | 2246.80 | 21-FEB-15:00 | 21.70 | 7.92 |
March | 0.734202E+09 | 10550.31 | 16-MAR-15:00 | 22.80 | 8.72 | 0.171400E+10 | 2246.81 | 10-MAR-13:20 | 22.80 | 8.72 |
April | 0.110603E+11 | 92544.12 | 30-APR-10:21 | 23.60 | 13.16 | 0.180154E+10 | 2246.90 | 29-APR-09:39 | 23.60 | 13.16 |
May | 0.260815E+11 | 87512.75 | 07-MAY-11:31 | 24.43 | 11.16 | 0.191974E+10 | 2247.02 | 23-MAY-14:09 | 27.07 | 16.89 |
June | 0.411097E+11 | 90852.42 | 17-JUN-04:41 | 24.50 | 13.67 | 0.192806E+10 | 2247.10 | 29-JUN-15:50 | 28.30 | 18.33 |
July | 0.404029E+11 | 83549.63 | 11-JUL-02:11 | 25.03 | 16.36 | 0.185469E+10 | 2247.10 | 27-JUL-12:09 | 32.88 | 20.83 |
August | 0.375371E+11 | 92077.31 | 11-AUG-01:21 | 23.90 | 14.11 | 0.200222E+10 | 2247.12 | 02-AUG-13:00 | 23.90 | 14.11 |
September | 0.286967E+11 | 95712.30 | 24-SEP-12:57 | 22.80 | 12.63 | 0.185191E+10 | 2247.11 | 09-SEP-13:30 | 22.80 | 12.63 |
October | 0.124794E+11 | 94757.27 | 01-OCT-09:11 | 22.93 | 13.06 | 0.181774E+10 | 2247.11 | 04-OCT-14:30 | 30.00 | 19.20 |
November | 0.108368E+10 | 15328.52 | 03-NOV-15:00 | 23.30 | 13.57 | 0.153215E+10 | 2246.83 | 03-NOV-13:39 | 23.30 | 13.57 |
December | 17597224.51 | 1405.55 | 30-DEC-09:15 | 1.50 | -1.0 | 0.121604E+10 | 2050.94 | 16-DEC-15:30 | 1.50 | -1.0 |
Annual Sum or Average | 0.199254E+12 | 0.201381E+11 | ||||||||
Minimum of Months | 7078849.71 | 1405.55 | -1.2 | -5.7 | 0.121604E+10 | 2050.94 | -1.2 | -5.7 | ||
Maximum of Months | 0.411097E+11 | 95712.30 | 25.03 | 16.36 | 0.200222E+10 | 2247.12 | 32.88 | 20.83 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 | 3.92 | 0.166922E+10 | 3018.79 | 03-JAN-15:09 | 20.50 | 8.33 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 | 1.84 | 0.181752E+10 | 3825.99 | 22-FEB-14:30 | 21.95 | 7.96 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 | 2.40 | 0.281991E+10 | 4580.12 | 22-MAR-13:50 | 24.50 | 9.16 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 | 2.41 | 0.408814E+10 | 7311.63 | 21-APR-14:00 | 32.20 | 15.49 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 | 8.41 | 0.536656E+10 | 8636.05 | 19-MAY-14:20 | 34.80 | 17.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 | 11.56 | 0.632485E+10 | 9097.65 | 01-JUN-14:39 | 36.33 | 14.55 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 | 17.07 | 0.587367E+10 | 9097.65 | 01-JUL-13:09 | 36.28 | 19.79 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 | 18.12 | 0.610027E+10 | 9097.65 | 04-AUG-15:30 | 35.85 | 19.45 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 | 17.18 | 0.536674E+10 | 8317.65 | 19-SEP-14:20 | 33.70 | 16.73 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 | 8.67 | 0.434771E+10 | 7716.79 | 03-OCT-14:20 | 32.43 | 19.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 | 5.64 | 0.262502E+10 | 5253.38 | 03-NOV-15:09 | 23.40 | 13.55 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 | 5.46 | 0.159150E+10 | 2756.36 | 16-DEC-15:20 | 15.00 | 4.18 |
Annual Sum or Average | 0.00 | 0.479911E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 6.42 | 1.84 | 0.159150E+10 | 2756.36 | 15.00 | 4.18 | ||
Maximum of Months | 0.00 | 0.00 | 27.63 | 18.12 | 0.632485E+10 | 9097.65 | 36.33 | 19.79 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.172139E+10 | 32897.91 | 06-JAN-06:01 | 0.10 |
February | 0.115868E+10 | 32906.28 | 02-FEB-06:01 | -3.5 |
March | 0.697845E+09 | 32910.09 | 02-MAR-06:01 | -3.5 |
April | 0.117728E+09 | 24457.38 | 11-APR-05:02 | 4.90 |
May | 25795662.83 | 5628.97 | 10-MAY-05:50 | 17.48 |
June | 5816677.85 | 2737.85 | 01-JUN-05:50 | 18.98 |
July | 1874368.49 | 1985.79 | 10-JUL-06:05 | 22.67 |
August | 5092581.21 | 2350.71 | 28-AUG-06:05 | 20.37 |
September | 3487772.52 | 1874.53 | 25-SEP-06:10 | 10.55 |
October | 78097206.81 | 3721.70 | 19-OCT-06:00 | 17.80 |
November | 0.526039E+09 | 32895.89 | 28-NOV-06:01 | 1.02 |
December | 0.171351E+10 | 32977.93 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.605535E+10 | |||
Minimum of Months | 1874368.49 | 1874.53 | -3.5 | |
Maximum of Months | 0.172139E+10 | 32977.93 | 22.67 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.519283E+10 | 119586.60 | 28-JAN-06:01 | -3.3 |
February | 0.406674E+10 | 79132.93 | 01-FEB-06:01 | -0.8 |
March | 0.300437E+10 | 41648.49 | 02-MAR-06:32 | -2.4 |
April | 0.959306E+09 | 8297.28 | 04-APR-06:25 | 11.95 |
May | 0.325549E+09 | 8181.45 | 04-MAY-06:25 | 15.30 |
June | 17484725.12 | 7147.09 | 01-JUN-06:02 | 19.37 |
July | 2334472.48 | 6845.04 | 05-JUL-06:03 | 18.07 |
August | 30036675.95 | 7586.24 | 17-AUG-06:13 | 17.40 |
September | 0.154667E+09 | 7902.36 | 30-SEP-06:25 | 10.25 |
October | 0.787456E+09 | 8259.62 | 11-OCT-06:25 | 7.50 |
November | 0.250622E+10 | 50555.93 | 28-NOV-05:03 | -0.3 |
December | 0.605857E+10 | 127982.06 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.231056E+11 | |||
Minimum of Months | 2334472.48 | 6845.04 | -3.5 | |
Maximum of Months | 0.605857E+10 | 127982.06 | 19.37 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 53846414.28 | 12139.91 | 28-JAN-05:55 | -3.3 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.491390E+09 | 26923.06 | 31-DEC-06:53 | -2.8 |
Annual Sum or Average | 0.545236E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.3 | |
Maximum of Months | 0.491390E+09 | 26923.06 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.258145E+10 | 1955.04 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.235440E+10 | 1955.04 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.269003E+10 | 1955.04 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.254196E+10 | 1955.04 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.263574E+10 | 1955.04 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.259625E+10 | 1955.04 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.258145E+10 | 1955.04 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.269003E+10 | 1955.04 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.254196E+10 | 1955.04 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.258145E+10 | 1955.04 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.248766E+10 | 1955.04 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.258145E+10 | 1955.04 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.308638E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.235440E+10 | 1955.04 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.269003E+10 | 1955.04 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.198922E+11 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.182065E+11 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.210336E+11 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.197108E+11 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.204629E+11 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.202815E+11 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.198922E+11 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.210336E+11 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.197108E+11 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.198922E+11 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.191400E+11 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.198922E+11 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.239148E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.182065E+11 | 17848.24 | 0.00 | 0.00 | |
Maximum of Months | 0.210336E+11 | 17848.24 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.294120E+11 | 26389.90 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.269196E+11 | 26389.90 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.310997E+11 | 26389.90 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.291438E+11 | 26389.90 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.302559E+11 | 26389.90 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.299876E+11 | 26389.90 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.294120E+11 | 26389.90 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.310997E+11 | 26389.90 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.291438E+11 | 26389.90 | 01-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.294120E+11 | 26389.90 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.282999E+11 | 26389.90 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.294120E+11 | 26389.90 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.353598E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.269196E+11 | 26389.90 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.310997E+11 | 26389.90 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262471E+10 |
February | 0.127628E+10 | 0.235440E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227789E+10 |
March | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2731419.28 | 0.235634E+10 |
April | 0.138726E+10 | 0.254196E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202926E+09 | 0.137057E+10 |
May | 0.144276E+10 | 0.263574E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486500E+09 | 0.783962E+09 |
June | 0.144276E+10 | 0.259625E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.890581E+09 | 0.325424E+09 |
July | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655750E+09 | 0.281130E+09 |
August | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557545E+09 | 0.381885E+09 |
September | 0.138726E+10 | 0.254196E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296735E+09 | 0.472133E+09 |
October | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72076598.69 | 0.131448E+10 |
November | 0.133177E+10 | 0.248766E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218327E+10 |
December | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247296E+10 |
Annual Sum or Average | 0.168137E+11 | 0.308638E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316485E+10 | 0.168448E+11 |
Minimum of Months | 0.127628E+10 | 0.235440E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281130E+09 |
Maximum of Months | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.890581E+09 | 0.262471E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.938249E+10 |
February | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.872320E+10 |
March | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101785E+11 |
April | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428497E+09 | 0.667315E+10 |
May | 0.339505E+10 | 0.204629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149286E+10 | 0.403248E+10 |
June | 0.339505E+10 | 0.202815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306958E+10 | 0.143585E+10 |
July | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222519E+10 | 0.116651E+10 |
August | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174963E+10 | 0.166857E+10 |
September | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483265E+09 | 0.200983E+10 |
October | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137596E+09 | 0.619125E+10 |
November | 0.313390E+10 | 0.191400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.895161E+10 |
December | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.830388E+10 |
Annual Sum or Average | 0.395654E+11 | 0.239148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.958662E+10 | 0.687173E+11 |
Minimum of Months | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116651E+10 |
Maximum of Months | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306958E+10 | 0.101785E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38032323.55 | 0.232278E+11 |
February | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420500E+09 | 0.215235E+11 |
March | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166111E+09 | 0.275546E+11 |
April | 0.750829E+10 | 0.291438E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.591872E+09 | 0.245434E+11 |
May | 0.780862E+10 | 0.302559E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59302884.66 | 0.217153E+11 |
June | 0.780862E+10 | 0.299876E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155017E+09 | 0.110978E+11 |
July | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77712693.22 | 0.983742E+10 |
August | 0.810895E+10 | 0.310997E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32673307.67 | 0.114545E+11 |
September | 0.750829E+10 | 0.291438E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 438110.28 | 0.113548E+11 |
October | 0.750829E+10 | 0.294120E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8770384.46 | 0.249966E+11 |
November | 0.720796E+10 | 0.282999E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3174448.67 | 0.263940E+11 |
December | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9881843.47 | 0.202577E+11 |
Annual Sum or Average | 0.910005E+11 | 0.353598E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156349E+10 | 0.233957E+12 |
Minimum of Months | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 438110.28 | 0.983742E+10 |
Maximum of Months | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.591872E+09 | 0.275546E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1955.04 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 7460.59 | 27-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 1955.04 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 8481.63 | 08-FEB-18:00 |
March | 1680.92 | 01-MAR-08:09 | 1955.04 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 316.45 | 21-MAR-16:10 | 7439.85 | 27-MAR-07:00 |
April | 1680.92 | 01-APR-07:10 | 1955.04 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3395.45 | 21-APR-16:10 | 5056.54 | 10-APR-17:00 |
May | 1680.92 | 01-MAY-07:10 | 1955.04 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3866.77 | 19-MAY-17:00 | 3874.38 | 02-MAY-06:05 |
June | 1680.92 | 01-JUN-07:10 | 1955.04 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5062.65 | 05-JUN-17:00 | 1702.62 | 29-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 1955.04 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4591.60 | 03-JUL-17:00 | 1628.57 | 05-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 1955.04 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3821.37 | 07-AUG-16:10 | 1910.28 | 31-AUG-06:03 |
September | 1680.92 | 01-SEP-07:10 | 1955.04 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2285.71 | 18-SEP-17:00 | 3261.31 | 25-SEP-06:05 |
October | 1680.92 | 02-OCT-07:10 | 1955.04 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2064.57 | 05-OCT-16:10 | 4149.85 | 25-OCT-06:05 |
November | 1680.92 | 01-NOV-07:10 | 1955.04 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6165.10 | 28-NOV-07:05 |
December | 1680.92 | 01-DEC-08:09 | 1955.04 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7860.90 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1628.57 | |||||
Maximum of Months | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 5062.65 | 8481.63 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 17006.99 | 25-JAN-16:03 |
February | 3955.50 | 01-FEB-08:09 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 28177.50 | 08-FEB-17:55 |
March | 3955.50 | 01-MAR-08:09 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 21052.55 | 27-MAR-07:00 |
April | 3955.50 | 01-APR-07:10 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10262.48 | 21-APR-15:10 | 23558.81 | 22-APR-07:00 |
May | 3955.50 | 01-MAY-07:10 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8861.35 | 19-MAY-17:00 | 12974.27 | 01-MAY-08:00 |
June | 3955.50 | 01-JUN-07:10 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12642.52 | 05-JUN-17:00 | 8840.77 | 28-JUN-02:00 |
July | 3955.50 | 01-JUL-07:10 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10060.25 | 03-JUL-17:00 | 6191.28 | 18-JUL-21:00 |
August | 3955.50 | 01-AUG-07:10 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8755.39 | 26-AUG-15:10 | 7144.35 | 14-AUG-01:00 |
September | 3955.50 | 01-SEP-07:10 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2894.43 | 18-SEP-17:00 | 6454.93 | 23-SEP-17:00 |
October | 3955.50 | 02-OCT-07:10 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3446.01 | 01-OCT-15:05 | 12443.23 | 06-OCT-08:00 |
November | 3955.50 | 01-NOV-07:10 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 16623.96 | 15-NOV-09:00 |
December | 3955.50 | 01-DEC-08:09 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 17641.47 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6191.28 | ||||
Maximum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12642.52 | 28177.50 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 26389.90 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6547.06 | 03-JAN-17:00 | 33492.20 | 26-JAN-10:00 |
February | 9097.65 | 01-FEB-08:09 | 26389.90 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8752.79 | 06-FEB-22:00 | 52303.08 | 09-FEB-01:00 |
March | 9097.65 | 01-MAR-08:09 | 26389.90 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11978.81 | 03-MAR-16:00 | 53988.46 | 27-MAR-07:10 |
April | 9097.65 | 01-APR-07:10 | 26389.90 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14881.91 | 01-APR-15:00 | 73753.17 | 06-APR-12:10 |
May | 9097.65 | 01-MAY-07:10 | 26389.90 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2088.48 | 14-MAY-14:55 | 45516.73 | 01-MAY-10:00 |
June | 9097.65 | 01-JUN-07:10 | 26389.90 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2577.41 | 02-JUN-16:00 | 37092.32 | 28-JUN-02:00 |
July | 9097.65 | 01-JUL-07:10 | 26389.90 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3327.01 | 02-JUL-21:55 | 28690.07 | 08-JUL-15:00 |
August | 9097.65 | 01-AUG-07:10 | 26389.90 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1548.13 | 07-AUG-16:00 | 29869.89 | 14-AUG-01:00 |
September | 9097.65 | 01-SEP-07:10 | 26389.90 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 382.37 | 10-SEP-14:43 | 21963.80 | 23-SEP-17:00 |
October | 9097.65 | 02-OCT-07:10 | 26389.90 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1406.58 | 01-OCT-14:52 | 48433.88 | 06-OCT-09:00 |
November | 9097.65 | 01-NOV-07:10 | 26389.90 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 870.48 | 23-NOV-16:00 | 42364.17 | 15-NOV-09:00 |
December | 9097.65 | 01-DEC-08:09 | 26389.90 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2116.20 | 10-DEC-15:00 | 41503.71 | 18-DEC-08:70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 382.37 | 21963.80 | |||||
Maximum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 14881.91 | 73753.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3305.81 | 12-JAN-15:30 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.57 |
February | 3926.48 | 21-FEB-17:00 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.45 |
March | 5353.58 | 14-MAR-16:00 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 46.73 | 0.00 |
April | 29573.64 | 28-APR-05:03 | 739.61 | 2335.89 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.70 |
May | 33484.07 | 17-MAY-05:01 | 1479.21 | 4671.78 | 4590.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.85 |
June | 32879.50 | 13-JUN-05:01 | 1664.11 | 5255.76 | 5163.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 689.15 |
July | 25735.16 | 11-JUL-05:01 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.70 |
August | 28691.14 | 23-AUG-05:01 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.77 |
September | 33091.84 | 30-SEP-05:02 | 924.51 | 2919.87 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395.87 |
October | 26403.10 | 02-OCT-05:01 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.73 |
November | 6599.07 | 03-NOV-16:00 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
December | 3126.94 | 16-DEC-16:00 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3126.94 | 739.61 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33484.07 | 1849.01 | 5839.73 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 46.73 | 689.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1504.68 | 27-JAN-09:10 | 7911.00 | 35696.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3900.43 |
February | 3977.13 | 22-FEB-14:00 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10550.31 | 16-MAR-15:00 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2304.91 |
April | 92544.12 | 30-APR-10:21 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.26 |
May | 87512.75 | 07-MAY-11:31 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.66 |
June | 90852.42 | 17-JUN-04:41 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 753.15 |
July | 83549.63 | 11-JUL-02:11 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.02 |
August | 92077.31 | 11-AUG-01:21 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.39 |
September | 95712.30 | 24-SEP-12:57 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1078.05 |
October | 94757.27 | 01-OCT-09:11 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15328.52 | 03-NOV-15:00 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1405.55 | 30-DEC-09:15 | 7911.00 | 35696.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2336.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1405.55 | 0.00 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 95712.30 | 7911.00 | 35696.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3900.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8088.95 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17474.99 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12263.38 |
April | 0.00 | 01-APR-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5691.30 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5533.78 |
June | 0.00 | 01-JUN-00:05 | 0.00 | 6209.39 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9466.51 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.81 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2523.93 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9509.41 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3809.24 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13674.56 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4964.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.81 | |
Maximum of Months | 0.00 | 0.00 | 6209.39 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17474.99 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.887614E+11 | 67969.16 | 26-JAN-13:09 | 0.471308E+10 | 61091.91 | 28-JAN-06:10 |
February | 0.804762E+11 | 69079.57 | 21-FEB-15:00 | 0.247316E+10 | 42833.18 | 02-FEB-06:10 |
March | 0.918588E+11 | 72760.52 | 22-MAR-12:00 | 0.971897E+09 | 34561.00 | 02-MAR-06:10 |
April | 0.901610E+11 | 87695.20 | 21-APR-14:39 | 27758368.32 | 6523.04 | 11-APR-05:10 |
May | 0.101828E+12 | 91907.08 | 19-MAY-13:00 | 3140380.82 | 3916.32 | 10-MAY-05:49 |
June | 0.111288E+12 | 97407.09 | 15-JUN-14:00 | 1160325.52 | 1933.88 | 01-JUN-05:49 |
July | 0.111336E+12 | 95797.02 | 26-JUL-14:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.112636E+12 | 93823.94 | 08-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.101968E+12 | 90945.13 | 01-SEP-14:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.922926E+11 | 89815.23 | 03-OCT-13:50 | 1552917.47 | 2588.20 | 19-OCT-05:00 |
November | 0.851801E+11 | 73274.02 | 03-NOV-14:00 | 0.762670E+09 | 34903.15 | 28-NOV-06:10 |
December | 0.890145E+11 | 71121.08 | 18-DEC-16:00 | 0.694950E+10 | 75412.51 | 27-DEC-06:10 |
Annual Sum or Average | 0.115680E+13 | 0.159039E+11 | ||||
Minimum of Months | 0.804762E+11 | 67969.16 | 0.00 | 0.00 | ||
Maximum of Months | 0.112636E+12 | 97407.09 | 0.694950E+10 | 75412.51 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.518856E+11 | 0.131772E+11 | 0.115358E+11 | 0.00 | 0.993775E+10 | 0.00 | 0.00 | 294.00 | 0.00 | 0.00 | 0.00 | 0.222511E+10 | 0.00 |
February | 0.474804E+11 | 0.112728E+11 | 0.105871E+11 | 0.00 | 0.907638E+10 | 0.00 | 0.00 | 40414090.57 | 0.00 | 0.00 | 0.00 | 0.201908E+10 | 0.00 |
March | 0.548234E+11 | 0.115850E+11 | 0.123431E+11 | 0.00 | 0.105878E+11 | 0.00 | 0.00 | 0.275902E+09 | 0.00 | 0.00 | 0.00 | 0.224354E+10 | 0.00 |
April | 0.513965E+11 | 0.103103E+11 | 0.114862E+11 | 0.00 | 0.101791E+11 | 0.00 | 0.00 | 0.470762E+10 | 0.00 | 0.00 | 0.00 | 0.208123E+10 | 0.00 |
May | 0.533545E+11 | 0.988031E+10 | 0.119357E+11 | 0.00 | 0.124910E+11 | 0.00 | 0.00 | 0.120755E+11 | 0.00 | 0.00 | 0.00 | 0.209060E+10 | 0.00 |
June | 0.528654E+11 | 0.917384E+10 | 0.118862E+11 | 0.00 | 0.149601E+11 | 0.00 | 0.00 | 0.204152E+11 | 0.00 | 0.00 | 0.00 | 0.198705E+10 | 0.00 |
July | 0.518856E+11 | 0.964994E+10 | 0.115358E+11 | 0.00 | 0.146979E+11 | 0.00 | 0.00 | 0.215843E+11 | 0.00 | 0.00 | 0.00 | 0.198205E+10 | 0.00 |
August | 0.548234E+11 | 0.103103E+11 | 0.123357E+11 | 0.00 | 0.145266E+11 | 0.00 | 0.00 | 0.186140E+11 | 0.00 | 0.00 | 0.00 | 0.202556E+10 | 0.00 |
September | 0.513965E+11 | 0.108120E+11 | 0.114788E+11 | 0.00 | 0.121949E+11 | 0.00 | 0.00 | 0.141177E+11 | 0.00 | 0.00 | 0.00 | 0.196796E+10 | 0.00 |
October | 0.518856E+11 | 0.121123E+11 | 0.115432E+11 | 0.00 | 0.102182E+11 | 0.00 | 0.00 | 0.446312E+10 | 0.00 | 0.00 | 0.00 | 0.207016E+10 | 0.00 |
November | 0.499276E+11 | 0.125065E+11 | 0.110862E+11 | 0.00 | 0.940978E+10 | 0.00 | 0.00 | 0.185889E+09 | 0.00 | 0.00 | 0.00 | 0.206410E+10 | 0.00 |
December | 0.518856E+11 | 0.133717E+11 | 0.115358E+11 | 0.00 | 0.100251E+11 | 0.00 | 0.00 | 332.29 | 0.00 | 0.00 | 0.00 | 0.219627E+10 | 0.00 |
Annual Sum or Average | 0.623610E+12 | 0.134162E+12 | 0.139290E+12 | 0.00 | 0.138305E+12 | 0.00 | 0.00 | 0.964796E+11 | 0.00 | 0.00 | 0.00 | 0.249527E+11 | 0.00 |
Minimum of Months | 0.474804E+11 | 0.917384E+10 | 0.105871E+11 | 0.00 | 0.907638E+10 | 0.00 | 0.00 | 294.00 | 0.00 | 0.00 | 0.00 | 0.196796E+10 | 0.00 |
Maximum of Months | 0.548234E+11 | 0.133717E+11 | 0.123431E+11 | 0.00 | 0.149601E+11 | 0.00 | 0.00 | 0.215843E+11 | 0.00 | 0.00 | 0.00 | 0.224354E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.471308E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.247316E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.971897E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 27758368.32 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 3140380.82 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 1160325.52 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 1552917.47 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.762670E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.694950E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.159039E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.694950E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 46193.18 | 02-JAN-09:09 | 8532.22 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 10132.60 | 28-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 46193.18 | 01-FEB-09:09 | 8532.22 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 9878.45 | 01-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 46193.18 | 01-MAR-09:09 | 8532.22 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 9878.45 | 07-MAR-12:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 46193.18 | 01-APR-08:09 | 8532.22 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 12183.75 | 19-APR-12:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 46193.18 | 01-MAY-08:09 | 8532.22 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 12183.75 | 08-MAY-11:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 46193.18 | 01-JUN-08:09 | 8532.22 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 12183.75 | 01-JUN-08:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 46193.18 | 01-JUL-08:09 | 8532.22 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 12183.75 | 01-JUL-07:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 46193.18 | 01-AUG-08:09 | 8532.22 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 12183.75 | 01-AUG-08:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 46193.18 | 01-SEP-08:09 | 8532.22 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 12183.75 | 01-SEP-10:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 46193.18 | 02-OCT-08:09 | 8532.22 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 12183.75 | 03-OCT-10:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 46193.18 | 01-NOV-08:09 | 8532.22 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 9878.45 | 01-NOV-06:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 46193.18 | 01-DEC-09:09 | 8532.22 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 10132.60 | 27-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 46193.18 | 8532.22 | 10112.62 | 0.00 | 9878.45 | 0.00 | 0.00 | |||||
Maximum of Months | 46193.18 | 8532.22 | 10112.62 | 0.00 | 12183.75 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.08 | 03-JAN-13:20 | 0.00 | 0.00 | 0.00 | 2049.61 | 25-JAN-12:00 | 0.00 |
February | 1115.24 | 21-FEB-15:00 | 0.00 | 0.00 | 0.00 | 2047.23 | 03-FEB-12:00 | 0.00 |
March | 4808.62 | 22-MAR-12:00 | 0.00 | 0.00 | 0.00 | 1936.30 | 04-MAR-12:09 | 0.00 |
April | 19142.73 | 21-APR-15:09 | 0.00 | 0.00 | 0.00 | 1797.79 | 01-APR-11:09 | 0.00 |
May | 22424.66 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 | 1773.15 | 01-MAY-11:09 | 0.00 |
June | 29147.60 | 15-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1747.97 | 01-JUN-11:09 | 0.00 |
July | 25615.36 | 26-JUL-14:30 | 0.00 | 0.00 | 0.00 | 1730.83 | 01-JUL-11:20 | 0.00 |
August | 26257.10 | 07-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1731.05 | 31-AUG-11:09 | 0.00 |
September | 20921.53 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1748.13 | 30-SEP-11:09 | 0.00 |
October | 19742.29 | 03-OCT-13:00 | 0.00 | 0.00 | 0.00 | 1772.83 | 31-OCT-11:09 | 0.00 |
November | 5347.53 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 | 1798.30 | 29-NOV-12:20 | 0.00 |
December | 0.07 | 01-DEC-13:09 | 0.00 | 0.00 | 0.00 | 1818.45 | 29-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.07 | 0.00 | 0.00 | 0.00 | 1730.83 | 0.00 | ||
Maximum of Months | 29147.60 | 0.00 | 0.00 | 0.00 | 2049.61 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 67969.16 | 26-JAN-13:09 | 46193.18 | 10112.62 | 0.00 | 0.00 | 9878.45 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 69079.57 | 21-FEB-15:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 9878.45 | 0.00 | 0.00 | 1115.24 | 0.00 |
March | 72760.52 | 22-MAR-12:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 9878.45 | 0.00 | 0.00 | 4808.62 | 0.00 |
April | 87695.20 | 21-APR-14:39 | 46193.18 | 10112.62 | 0.00 | 0.00 | 12183.75 | 0.00 | 0.00 | 17458.47 | 0.00 |
May | 91907.08 | 19-MAY-13:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 12183.75 | 0.00 | 0.00 | 21719.29 | 0.00 |
June | 97407.09 | 15-JUN-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 12183.75 | 0.00 | 0.00 | 27206.90 | 0.00 |
July | 95797.02 | 26-JUL-14:20 | 46193.18 | 10112.62 | 0.00 | 0.00 | 12183.75 | 0.00 | 0.00 | 25608.74 | 0.00 |
August | 93823.94 | 08-AUG-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 12183.75 | 0.00 | 0.00 | 23634.86 | 0.00 |
September | 90945.13 | 01-SEP-14:50 | 46193.18 | 10112.62 | 0.00 | 0.00 | 12183.75 | 0.00 | 0.00 | 20751.00 | 0.00 |
October | 89815.23 | 03-OCT-13:50 | 46193.18 | 10112.62 | 0.00 | 0.00 | 12183.75 | 0.00 | 0.00 | 19633.15 | 0.00 |
November | 73274.02 | 03-NOV-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 9878.45 | 0.00 | 0.00 | 5347.53 | 0.00 |
December | 71121.08 | 18-DEC-16:00 | 40988.70 | 10112.62 | 8532.22 | 0.00 | 9878.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 67969.16 | 40988.70 | 10112.62 | 0.00 | 0.00 | 9878.45 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 97407.09 | 46193.18 | 10112.62 | 8532.22 | 0.00 | 12183.75 | 0.00 | 0.00 | 27206.90 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 61091.91 | 28-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 42833.18 | 02-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 34561.00 | 02-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 6523.04 | 11-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 3916.32 | 10-MAY-05:49 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 1933.88 | 01-JUN-05:49 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 2588.20 | 19-OCT-05:00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 34903.15 | 28-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 75412.51 | 27-DEC-06:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 75412.51 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.17 | 19.97 | 6.17 | 19.97 | 0.00 | 19.97 | 0.00 | 19.97 |
February | 4.33 | 20.05 | 4.33 | 20.05 | 0.00 | 20.05 | 0.00 | 20.05 |
March | 2.00 | 20.22 | 2.00 | 20.22 | 0.00 | 20.22 | 0.00 | 20.22 |
April | 0.17 | 20.53 | 0.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.56 | 1.33 | 24.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 25.24 | 4.33 | 24.98 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 26.18 | 5.50 | 25.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 26.27 | 5.33 | 25.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.89 | 3.33 | 24.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.55 | 0.83 | 24.55 |
November | 2.00 | 20.26 | 2.00 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
December | 6.00 | 19.67 | 5.83 | 19.74 | 0.00 | 19.74 | 0.00 | 19.74 |
Annual Sum or Average | 20.67 | 19.96 | 20.50 | 19.98 | 25.50 | 22.17 | 20.67 | 22.77 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.74 | 0.00 | 19.74 |
Maximum of Months | 6.17 | 20.53 | 6.17 | 20.53 | 7.50 | 26.27 | 5.50 | 25.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.17 | 14.85 | 1.33 | 14.83 | 0.00 | 14.83 | 0.00 | 14.83 |
February | 4.50 | 14.86 | 0.83 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
March | 1.00 | 14.96 | 0.17 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.55 | 0.00 | 27.55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 27.76 | 0.00 | 27.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 43.33 | 27.80 | 0.00 | 27.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 50.17 | 27.79 | 0.17 | 27.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 36.67 | 27.75 | 0.00 | 27.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 27.71 | 0.00 | 27.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.59 | 0.00 | 27.59 |
November | 1.17 | 14.86 | 0.50 | 14.88 | 0.00 | 14.88 | 0.00 | 14.88 |
December | 15.33 | 14.79 | 2.50 | 14.78 | 0.00 | 14.78 | 0.00 | 14.78 |
Annual Sum or Average | 31.17 | 14.83 | 5.33 | 14.82 | 175.83 | 25.54 | 0.17 | 25.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.78 | 0.00 | 14.78 |
Maximum of Months | 15.33 | 14.96 | 2.50 | 14.96 | 50.17 | 27.80 | 0.17 | 27.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 22.30 | 142.83 | 21.94 | 142.83 | 21.76 |
February | 276.00 | 22.67 | 94.50 | 22.29 | 94.50 | 22.07 |
March | 323.33 | 23.14 | 70.83 | 22.79 | 70.83 | 22.55 |
April | 148.17 | 23.56 | 52.67 | 23.55 | 7.00 | 23.47 |
May | 34.17 | 23.61 | 188.00 | 23.86 | 0.00 | 23.86 |
June | 2.17 | 22.14 | 286.33 | 23.89 | 0.00 | 23.89 |
July | 47.00 | 23.92 | 300.00 | 23.90 | 47.00 | 23.91 |
August | 19.67 | 23.85 | 321.33 | 23.90 | 19.00 | 23.90 |
September | 22.67 | 23.86 | 277.50 | 23.90 | 20.50 | 23.90 |
October | 62.83 | 23.67 | 153.00 | 23.83 | 4.50 | 23.83 |
November | 247.67 | 23.09 | 60.67 | 22.81 | 49.67 | 22.58 |
December | 300.00 | 22.33 | 143.33 | 21.96 | 143.33 | 21.77 |
Annual Sum or Average | 1783.67 | 22.88 | 2091.00 | 23.08 | 599.17 | 22.88 |
Minimum of Months | 2.17 | 22.14 | 52.67 | 21.94 | 0.00 | 21.76 |
Maximum of Months | 323.33 | 23.92 | 321.33 | 23.90 | 143.33 | 23.91 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 293.83 | 20.72 | 160.17 | 20.01 | 158.00 | 19.64 |
February | 241.00 | 21.53 | 113.33 | 20.92 | 99.17 | 20.42 |
March | 171.50 | 21.71 | 189.67 | 22.72 | 76.33 | 22.11 |
April | 97.17 | 24.50 | 235.33 | 25.89 | 48.50 | 25.87 |
May | 189.67 | 26.53 | 291.83 | 26.60 | 179.83 | 26.63 |
June | 262.83 | 26.70 | 311.17 | 26.69 | 262.83 | 26.69 |
July | 292.00 | 26.71 | 300.00 | 26.71 | 292.00 | 26.71 |
August | 298.83 | 26.70 | 324.00 | 26.69 | 298.83 | 26.69 |
September | 250.83 | 26.67 | 294.50 | 26.66 | 248.67 | 26.67 |
October | 133.33 | 25.70 | 252.00 | 26.29 | 96.00 | 26.37 |
November | 147.67 | 21.62 | 173.17 | 22.86 | 63.33 | 22.26 |
December | 300.00 | 20.71 | 166.33 | 19.99 | 166.33 | 19.65 |
Annual Sum or Average | 2678.67 | 24.16 | 2811.50 | 24.63 | 1989.83 | 24.58 |
Minimum of Months | 97.17 | 20.71 | 113.33 | 19.99 | 48.50 | 19.64 |
Maximum of Months | 300.00 | 26.71 | 324.00 | 26.71 | 298.83 | 26.71 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.91 | 300.00 | 15.91 | 300.00 | 15.91 |
February | 276.00 | 17.35 | 262.83 | 17.23 | 262.83 | 17.19 |
March | 324.00 | 20.19 | 183.50 | 19.50 | 183.50 | 19.18 |
April | 166.00 | 25.06 | 177.67 | 26.11 | 79.50 | 26.37 |
May | 264.50 | 29.59 | 294.83 | 29.48 | 254.67 | 29.58 |
June | 312.00 | 31.78 | 312.00 | 31.78 | 312.00 | 31.78 |
July | 300.00 | 31.26 | 300.00 | 31.26 | 300.00 | 31.26 |
August | 324.00 | 30.60 | 324.00 | 30.60 | 324.00 | 30.60 |
September | 282.67 | 29.96 | 300.00 | 29.85 | 282.67 | 29.89 |
October | 191.00 | 26.87 | 227.17 | 27.29 | 132.33 | 27.63 |
November | 266.17 | 20.24 | 150.00 | 19.67 | 139.50 | 19.28 |
December | 300.00 | 15.48 | 300.00 | 15.48 | 300.00 | 15.48 |
Annual Sum or Average | 3306.33 | 24.48 | 3132.00 | 24.68 | 2871.00 | 24.70 |
Minimum of Months | 166.00 | 15.48 | 150.00 | 15.48 | 79.50 | 15.48 |
Maximum of Months | 324.00 | 31.78 | 324.00 | 31.78 | 324.00 | 31.78 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 1055.38 | 294.00 | 3.58 | 1055.38 | 0.00 | 0.00 | 0.00 | 03-JAN-13:20 | 0.00 | 01-JAN-00:10 | 0.29 | 03-JAN-13:20 | 0.29 | 03-JAN-13:20 | 0.00 | 03-JAN-16:50 | 0.08 | 03-JAN-13:20 | 0.00 | 01-JAN-00:10 |
February | 0.148162E+09 | 40401238.73 | 28.42 | 0.148162E+09 | -0.0 | 0.00 | 0.20 | 21-FEB-16:00 | 0.00 | 01-FEB-00:10 | 4128.52 | 21-FEB-16:00 | 4128.52 | 21-FEB-16:00 | 0.00 | 21-FEB-15:20 | 1115.24 | 21-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 0.739652E+09 | 0.200316E+09 | 75.92 | 0.739652E+09 | 0.00 | 0.00 | 0.34 | 14-MAR-16:00 | 0.00 | 01-MAR-00:10 | 7055.18 | 14-MAR-16:00 | 7055.18 | 14-MAR-16:00 | 0.00 | 14-MAR-15:40 | 1892.66 | 21-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.403030E+10 | 0.112467E+10 | 175.12 | 0.401485E+10 | 15451342.54 | 0.00 | 1.00 | 20-APR-05:02 | 0.00 | 01-APR-00:10 | 23632.26 | 29-APR-05:02 | 23336.46 | 20-APR-05:55 | 3181.39 | 29-APR-05:45 | 5599.34 | 29-APR-05:02 | 0.00 | 01-APR-00:10 |
May | 0.861202E+10 | 0.243340E+10 | 274.94 | 0.835406E+10 | 0.257961E+09 | 0.00 | 1.00 | 01-MAY-05:02 | 0.00 | 01-MAY-00:10 | 25434.49 | 23-MAY-05:01 | 24034.85 | 31-MAY-05:01 | 9216.17 | 25-MAY-05:03 | 6017.71 | 23-MAY-05:01 | 0.00 | 01-MAY-00:10 |
June | 0.123600E+11 | 0.366470E+10 | 317.60 | 0.117753E+11 | 0.584714E+09 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:05 | 26445.76 | 28-JUN-05:01 | 24784.22 | 17-JUN-05:01 | 10374.49 | 28-JUN-05:03 | 6230.70 | 28-JUN-05:01 | 0.00 | 01-JUN-00:05 |
July | 0.142191E+11 | 0.400565E+10 | 319.11 | 0.115997E+11 | 0.261945E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 30258.57 | 21-JUL-05:01 | 25471.06 | 03-JUL-05:01 | 17929.68 | 21-JUL-05:07 | 7201.84 | 23-JUL-13:12 | 0.00 | 01-JUL-00:10 |
August | 0.130557E+11 | 0.366543E+10 | 327.80 | 0.112231E+11 | 0.183260E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 29267.63 | 03-AUG-05:01 | 26034.99 | 06-AUG-21:35 | 14298.29 | 02-AUG-05:10 | 6754.77 | 06-AUG-21:35 | 0.00 | 01-AUG-00:10 |
September | 0.105898E+11 | 0.292995E+10 | 280.75 | 0.918008E+10 | 0.140970E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 28591.15 | 22-SEP-05:01 | 25850.67 | 04-SEP-17:03 | 14394.18 | 22-SEP-05:21 | 6947.66 | 03-SEP-13:15 | 0.00 | 01-SEP-00:10 |
October | 0.452512E+10 | 0.122012E+10 | 177.50 | 0.408165E+10 | 0.443472E+09 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 26758.01 | 04-OCT-05:02 | 24504.64 | 02-OCT-05:01 | 11861.98 | 04-OCT-05:03 | 6293.45 | 04-OCT-05:02 | 0.00 | 01-OCT-00:10 |
November | 0.443694E+09 | 0.119571E+09 | 52.25 | 0.440114E+09 | 3580524.20 | 0.00 | 0.38 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 | 8243.31 | 03-NOV-16:00 | 8243.31 | 03-NOV-16:00 | 337.73 | 03-NOV-12:50 | 2169.49 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 |
December | 1192.87 | 332.29 | 4.42 | 1192.87 | 0.00 | 0.00 | 0.00 | 01-DEC-13:10 | 0.00 | 01-DEC-00:10 | 0.27 | 01-DEC-13:10 | 0.27 | 01-DEC-13:10 | 0.00 | 16-DEC-12:20 | 0.07 | 01-DEC-13:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.687235E+11 | 0.194042E+11 | 2037.40 | 0.615566E+11 | 0.716692E+10 | 0.00 | ||||||||||||||
Minimum of Months | 1055.38 | 294.00 | 3.58 | 1055.38 | -0.0 | 0.00 | 0.00 | 0.00 | 0.27 | 0.27 | 0.00 | 0.07 | 0.00 | |||||||
Maximum of Months | 0.142191E+11 | 0.400565E+10 | 327.80 | 0.117753E+11 | 0.261945E+10 | 0.00 | 1.00 | 0.00 | 30258.57 | 26034.99 | 17929.68 | 7201.84 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 42623.89 | 12851.84 | 5.83 | 42623.89 | -0.0 | 0.00 | 0.00 | 23-FEB-13:00 | 0.00 | 01-FEB-00:10 | 5.90 | 23-FEB-13:00 | 5.90 | 23-FEB-13:00 | 0.00 | 23-FEB-13:20 | 1.78 | 23-FEB-13:00 | 0.00 | 01-FEB-00:10 |
March | 0.251452E+09 | 75586661.75 | 35.50 | 0.251452E+09 | -0.0 | 0.00 | 0.14 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 10544.73 | 22-MAR-13:00 | 10544.73 | 22-MAR-13:00 | 0.00 | 22-MAR-14:00 | 3185.08 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.116470E+11 | 0.358295E+10 | 163.45 | 0.116368E+11 | 10179916.56 | 0.00 | 1.00 | 02-APR-13:35 | 0.00 | 01-APR-00:10 | 93983.85 | 30-APR-10:21 | 93983.85 | 30-APR-10:21 | 4510.65 | 30-APR-09:13 | 26533.12 | 30-APR-16:03 | 0.00 | 01-APR-00:10 |
May | 0.309869E+11 | 0.964207E+10 | 303.80 | 0.304009E+11 | 0.586059E+09 | 0.00 | 1.00 | 04-MAY-17:25 | 0.00 | 01-MAY-00:10 | 103959.27 | 27-MAY-20:45 | 96817.22 | 28-MAY-17:53 | 26924.67 | 28-MAY-08:23 | 28313.34 | 21-MAY-15:32 | 0.00 | 01-MAY-00:10 |
June | 0.515486E+11 | 0.167505E+11 | 418.47 | 0.501932E+11 | 0.135540E+10 | 0.00 | 1.00 | 01-JUN-00:45 | 0.00 | 01-JUN-00:05 | 108982.17 | 19-JUN-17:57 | 97353.92 | 28-JUN-17:42 | 36994.45 | 19-JUN-17:57 | 29487.58 | 18-JUN-15:52 | 0.00 | 01-JUN-00:05 |
July | 0.570193E+11 | 0.175787E+11 | 427.42 | 0.491223E+11 | 0.789704E+10 | 0.00 | 1.00 | 01-JUL-01:55 | 0.00 | 01-JUL-00:15 | 116377.55 | 21-JUL-21:00 | 96306.78 | 04-JUL-16:22 | 55629.79 | 21-JUL-21:00 | 30322.46 | 02-JUL-15:32 | 0.00 | 01-JUL-00:10 |
August | 0.484734E+11 | 0.149485E+11 | 393.65 | 0.439943E+11 | 0.447909E+10 | 0.00 | 1.00 | 01-AUG-00:25 | 0.00 | 01-AUG-00:15 | 111980.55 | 01-AUG-22:15 | 96488.72 | 28-AUG-17:42 | 48487.00 | 01-AUG-22:15 | 29513.45 | 06-AUG-15:12 | 0.00 | 01-AUG-00:10 |
September | 0.371545E+11 | 0.111877E+11 | 296.01 | 0.335014E+11 | 0.365311E+10 | 0.00 | 1.00 | 01-SEP-17:42 | 0.00 | 01-SEP-00:10 | 109275.35 | 09-SEP-19:51 | 96774.64 | 06-SEP-18:23 | 44311.35 | 03-SEP-07:25 | 28020.14 | 17-SEP-15:12 | 0.00 | 01-SEP-00:10 |
October | 0.109239E+11 | 0.324301E+10 | 149.96 | 0.101086E+11 | 0.815247E+09 | 0.00 | 1.00 | 01-OCT-09:11 | 0.00 | 01-OCT-00:10 | 108143.13 | 03-OCT-17:12 | 95038.25 | 22-OCT-14:13 | 35676.97 | 03-OCT-17:12 | 27469.52 | 03-OCT-18:05 | 0.00 | 01-OCT-00:10 |
November | 0.222927E+09 | 66317521.46 | 14.83 | 0.221675E+09 | 1252085.79 | 0.00 | 0.14 | 03-NOV-15:00 | 0.00 | 01-NOV-00:10 | 11455.27 | 03-NOV-15:00 | 11455.27 | 03-NOV-15:00 | 281.40 | 03-NOV-13:30 | 3384.56 | 03-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.248228E+12 | 0.770754E+11 | 2208.92 | 0.229430E+12 | 0.187974E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.570193E+11 | 0.175787E+11 | 427.42 | 0.501932E+11 | 0.789704E+10 | 0.00 | 1.00 | 0.00 | 116377.55 | 97353.92 | 55629.79 | 30322.46 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.00 | 37.79 | 29.22 | 77.69 | 138.61 | 0.00 | 0.00 | 0.00 |
February | 75.39 | 40.01 | 35.38 | 93.19 | 127.17 | 0.00 | 0.00 | 0.00 |
March | 102.73 | 55.01 | 47.72 | 138.36 | 114.74 | 0.00 | 0.00 | 0.00 |
April | 117.93 | 63.55 | 54.38 | 184.79 | 80.57 | 0.00 | 0.00 | 0.00 |
May | 127.03 | 67.83 | 59.20 | 222.61 | 57.80 | 0.00 | 0.00 | 0.00 |
June | 124.00 | 66.61 | 57.39 | 247.93 | 35.61 | 0.00 | 0.00 | 0.00 |
July | 110.12 | 54.75 | 55.37 | 218.97 | 31.92 | 0.00 | 0.00 | 0.00 |
August | 106.39 | 54.11 | 52.27 | 202.84 | 41.40 | 0.00 | 0.00 | 0.00 |
September | 109.07 | 60.80 | 48.27 | 196.97 | 69.49 | 0.00 | 0.00 | 0.00 |
October | 93.70 | 54.65 | 39.06 | 143.14 | 97.56 | 0.00 | 0.00 | 0.00 |
November | 78.20 | 47.42 | 30.78 | 98.43 | 137.85 | 0.00 | 0.00 | 0.00 |
December | 63.49 | 34.51 | 28.98 | 68.46 | 157.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98.00 | 53.12 | 44.88 | 158.05 | 90.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.49 | 34.51 | 28.98 | 68.46 | 31.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 127.03 | 67.83 | 59.20 | 247.93 | 157.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.00 | 37.79 | 29.22 | 77.69 | 138.61 | 0.00 | 0.00 | 0.00 |
February | 75.39 | 40.01 | 35.38 | 93.19 | 127.17 | 0.00 | 0.00 | 0.00 |
March | 102.73 | 55.01 | 47.72 | 138.36 | 114.74 | 0.00 | 0.00 | 0.00 |
April | 117.93 | 63.55 | 54.38 | 184.79 | 80.57 | 0.00 | 0.00 | 0.00 |
May | 127.03 | 67.83 | 59.20 | 222.61 | 57.80 | 0.00 | 0.00 | 0.00 |
June | 124.00 | 66.61 | 57.39 | 247.93 | 35.61 | 0.00 | 0.00 | 0.00 |
July | 110.12 | 54.75 | 55.37 | 218.97 | 31.92 | 0.00 | 0.00 | 0.00 |
August | 106.39 | 54.11 | 52.27 | 202.84 | 41.40 | 0.00 | 0.00 | 0.00 |
September | 109.07 | 60.80 | 48.27 | 196.97 | 69.49 | 0.00 | 0.00 | 0.00 |
October | 93.70 | 54.65 | 39.06 | 143.14 | 97.56 | 0.00 | 0.00 | 0.00 |
November | 78.20 | 47.42 | 30.78 | 98.43 | 137.85 | 0.00 | 0.00 | 0.00 |
December | 63.49 | 34.51 | 28.98 | 68.46 | 157.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98.00 | 53.12 | 44.88 | 158.05 | 90.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.49 | 34.51 | 28.98 | 68.46 | 31.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 127.03 | 67.83 | 59.20 | 247.93 | 157.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.85 | 0.00 | 13.85 | 2.42 | 86.96 | 0.00 | 0.00 | 0.00 |
February | 16.91 | 0.00 | 16.91 | 6.73 | 78.49 | 0.00 | 0.00 | 0.00 |
March | 22.14 | 0.00 | 22.14 | 13.32 | 70.37 | 0.00 | 0.00 | 0.00 |
April | 25.67 | 0.30 | 25.37 | 26.68 | 47.40 | 0.00 | 0.00 | 0.00 |
May | 30.48 | 2.36 | 28.12 | 46.51 | 31.64 | 0.00 | 0.00 | 0.00 |
June | 32.34 | 4.08 | 28.26 | 68.23 | 19.78 | 0.00 | 0.00 | 0.00 |
July | 29.80 | 2.90 | 26.90 | 61.44 | 17.86 | 0.00 | 0.00 | 0.00 |
August | 25.32 | 0.69 | 24.62 | 46.67 | 23.35 | 0.00 | 0.00 | 0.00 |
September | 21.94 | 0.02 | 21.92 | 34.25 | 40.77 | 0.00 | 0.00 | 0.00 |
October | 18.20 | 0.00 | 18.20 | 14.65 | 59.16 | 0.00 | 0.00 | 0.00 |
November | 14.69 | 0.00 | 14.69 | 2.74 | 86.65 | 0.00 | 0.00 | 0.00 |
December | 13.74 | 0.00 | 13.74 | 1.29 | 99.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.12 | 0.87 | 21.25 | 27.18 | 55.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.74 | 0.00 | 13.74 | 1.29 | 17.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.34 | 4.08 | 28.26 | 68.23 | 99.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.85 | 0.00 | 13.85 | 2.42 | 86.96 | 0.00 | 0.00 | 0.00 |
February | 16.91 | 0.00 | 16.91 | 6.73 | 78.49 | 0.00 | 0.00 | 0.00 |
March | 22.14 | 0.00 | 22.14 | 13.32 | 70.37 | 0.00 | 0.00 | 0.00 |
April | 25.67 | 0.30 | 25.37 | 26.68 | 47.40 | 0.00 | 0.00 | 0.00 |
May | 30.48 | 2.36 | 28.12 | 46.51 | 31.64 | 0.00 | 0.00 | 0.00 |
June | 32.34 | 4.08 | 28.26 | 68.23 | 19.78 | 0.00 | 0.00 | 0.00 |
July | 29.79 | 2.90 | 26.90 | 61.44 | 17.86 | 0.00 | 0.00 | 0.00 |
August | 25.32 | 0.69 | 24.62 | 46.67 | 23.35 | 0.00 | 0.00 | 0.00 |
September | 21.94 | 0.02 | 21.92 | 34.25 | 40.77 | 0.00 | 0.00 | 0.00 |
October | 18.20 | 0.00 | 18.20 | 14.65 | 59.16 | 0.00 | 0.00 | 0.00 |
November | 14.69 | 0.00 | 14.69 | 2.74 | 86.65 | 0.00 | 0.00 | 0.00 |
December | 13.74 | 0.00 | 13.74 | 1.29 | 99.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.12 | 0.87 | 21.25 | 27.18 | 55.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.74 | 0.00 | 13.74 | 1.29 | 17.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.34 | 4.08 | 28.26 | 68.23 | 99.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 85.72 | 73.74 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 112.33 | 73.02 | 3.00 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 160.26 | 74.12 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 203.63 | 66.60 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 228.30 | 62.93 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 247.75 | 50.86 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 216.71 | 40.96 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 199.43 | 49.36 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 180.07 | 66.66 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 127.70 | 74.76 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 94.25 | 85.87 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 75.85 | 85.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 161.18 | 66.99 | 4.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 75.85 | 40.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 247.75 | 85.87 | 3.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 85.72 | 73.74 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 112.33 | 73.02 | 3.00 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 160.26 | 74.12 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 203.63 | 66.60 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 228.30 | 62.93 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 247.75 | 50.86 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 216.71 | 40.96 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 199.43 | 49.36 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 180.07 | 66.66 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 127.70 | 74.76 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 94.25 | 85.87 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 75.85 | 85.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 161.18 | 66.99 | 4.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 75.85 | 40.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 247.75 | 85.87 | 3.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 85.72 | 73.74 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 112.33 | 73.02 | 3.00 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 160.26 | 74.12 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 203.63 | 66.60 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 228.30 | 62.93 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 247.75 | 50.86 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 216.71 | 40.96 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 199.43 | 49.36 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 180.07 | 66.66 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 127.70 | 74.76 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 94.25 | 85.87 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 75.85 | 85.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 161.18 | 66.99 | 4.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 75.85 | 40.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 247.75 | 85.87 | 3.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 85.72 | 73.74 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 112.33 | 73.02 | 3.00 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 160.26 | 74.12 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 203.63 | 66.60 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 228.30 | 62.93 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 247.75 | 50.86 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 216.71 | 40.96 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 199.43 | 49.36 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 180.07 | 66.66 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 127.70 | 74.76 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 94.25 | 85.87 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 75.85 | 85.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 161.18 | 66.99 | 4.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 75.85 | 40.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 247.75 | 85.87 | 3.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 85.72 | 73.74 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 112.33 | 73.02 | 3.00 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 160.26 | 74.12 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 203.63 | 66.60 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 228.30 | 62.93 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 247.75 | 50.86 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 216.71 | 40.96 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 199.43 | 49.36 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 180.07 | 66.66 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 127.70 | 74.76 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 94.25 | 85.87 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 75.85 | 85.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 161.18 | 66.99 | 4.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 75.85 | 40.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 247.75 | 85.87 | 3.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 85.72 | 73.74 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 112.33 | 73.02 | 3.00 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 160.26 | 74.12 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 203.63 | 66.60 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 228.30 | 62.93 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 247.75 | 50.86 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 216.71 | 40.96 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 199.43 | 49.36 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 180.07 | 66.66 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 127.70 | 74.76 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 94.25 | 85.87 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 75.85 | 85.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 161.18 | 66.99 | 4.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 75.85 | 40.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 247.75 | 85.87 | 3.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 85.72 | 73.74 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 112.33 | 73.02 | 3.00 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 160.26 | 74.12 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 203.63 | 66.60 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 228.30 | 62.93 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 247.75 | 50.86 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 216.71 | 40.96 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 199.43 | 49.36 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 180.07 | 66.66 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 127.70 | 74.76 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 94.25 | 85.87 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 75.85 | 85.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 161.18 | 66.99 | 4.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 75.85 | 40.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 247.75 | 85.87 | 3.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 85.72 | 73.74 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 112.33 | 73.02 | 3.00 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 160.26 | 74.12 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 203.63 | 66.60 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 228.30 | 62.93 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 247.75 | 50.86 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 216.71 | 40.96 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 199.43 | 49.36 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 180.07 | 66.66 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 127.70 | 74.76 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 94.25 | 85.87 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 75.85 | 85.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 161.18 | 66.99 | 4.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 75.85 | 40.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 247.75 | 85.87 | 3.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 85.72 | 73.74 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 112.33 | 73.02 | 3.00 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 160.26 | 74.12 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 203.63 | 66.60 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 228.30 | 62.93 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 247.75 | 50.86 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 216.71 | 40.96 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 199.43 | 49.36 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 180.07 | 66.66 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 127.70 | 74.76 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 94.25 | 85.87 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 75.85 | 85.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 161.18 | 66.99 | 4.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 75.85 | 40.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 247.75 | 85.87 | 3.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 85.72 | 73.74 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 112.33 | 73.02 | 3.00 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 160.26 | 74.12 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 203.63 | 66.60 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 228.30 | 62.93 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 247.75 | 50.86 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 216.71 | 40.96 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 199.43 | 49.36 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 180.07 | 66.66 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 127.70 | 74.76 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 94.25 | 85.87 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 75.85 | 85.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 161.18 | 66.99 | 4.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 75.85 | 40.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 247.75 | 85.87 | 3.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.179463E+09 | 0.101204E+09 | 78259173.43 | 0.208091E+09 | 0.371251E+09 |
February | 0.182386E+09 | 96789877.26 | 85595682.28 | 0.225437E+09 | 0.307660E+09 |
March | 0.275156E+09 | 0.147345E+09 | 0.127811E+09 | 0.370586E+09 | 0.307331E+09 |
April | 0.305676E+09 | 0.164734E+09 | 0.140942E+09 | 0.478981E+09 | 0.208842E+09 |
May | 0.340226E+09 | 0.181670E+09 | 0.158556E+09 | 0.596236E+09 | 0.154804E+09 |
June | 0.321406E+09 | 0.172662E+09 | 0.148744E+09 | 0.642631E+09 | 92313808.21 |
July | 0.294955E+09 | 0.146648E+09 | 0.148307E+09 | 0.586490E+09 | 85481652.76 |
August | 0.284942E+09 | 0.144939E+09 | 0.140004E+09 | 0.543283E+09 | 0.110878E+09 |
September | 0.282710E+09 | 0.157595E+09 | 0.125115E+09 | 0.510536E+09 | 0.180108E+09 |
October | 0.250972E+09 | 0.146361E+09 | 0.104610E+09 | 0.383393E+09 | 0.261304E+09 |
November | 0.202684E+09 | 0.122913E+09 | 79770336.35 | 0.255122E+09 | 0.357304E+09 |
December | 0.170052E+09 | 92436426.13 | 77615197.29 | 0.183373E+09 | 0.422169E+09 |
Annual Sum or Average | 0.309063E+10 | 0.167530E+10 | 0.141533E+10 | 0.498416E+10 | 0.285945E+10 |
Minimum of Months | 0.170052E+09 | 92436426.13 | 77615197.29 | 0.183373E+09 | 85481652.76 |
Maximum of Months | 0.340226E+09 | 0.181670E+09 | 0.158556E+09 | 0.642631E+09 | 0.422169E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.179463E+09 | 0.101204E+09 | 78259173.43 | 0.208091E+09 | 0.371251E+09 |
February | 0.182386E+09 | 96789877.26 | 85595682.28 | 0.225437E+09 | 0.307660E+09 |
March | 0.275156E+09 | 0.147345E+09 | 0.127811E+09 | 0.370586E+09 | 0.307331E+09 |
April | 0.305676E+09 | 0.164734E+09 | 0.140942E+09 | 0.478981E+09 | 0.208842E+09 |
May | 0.340226E+09 | 0.181670E+09 | 0.158556E+09 | 0.596236E+09 | 0.154804E+09 |
June | 0.321406E+09 | 0.172662E+09 | 0.148744E+09 | 0.642631E+09 | 92313808.21 |
July | 0.294955E+09 | 0.146648E+09 | 0.148307E+09 | 0.586490E+09 | 85481652.76 |
August | 0.284942E+09 | 0.144939E+09 | 0.140004E+09 | 0.543283E+09 | 0.110878E+09 |
September | 0.282710E+09 | 0.157595E+09 | 0.125115E+09 | 0.510536E+09 | 0.180108E+09 |
October | 0.250972E+09 | 0.146361E+09 | 0.104610E+09 | 0.383393E+09 | 0.261304E+09 |
November | 0.202684E+09 | 0.122913E+09 | 79770336.35 | 0.255122E+09 | 0.357304E+09 |
December | 0.170052E+09 | 92436426.13 | 77615197.29 | 0.183373E+09 | 0.422169E+09 |
Annual Sum or Average | 0.309063E+10 | 0.167530E+10 | 0.141533E+10 | 0.498416E+10 | 0.285945E+10 |
Minimum of Months | 0.170052E+09 | 92436426.13 | 77615197.29 | 0.183373E+09 | 85481652.76 |
Maximum of Months | 0.340226E+09 | 0.181670E+09 | 0.158556E+09 | 0.642631E+09 | 0.422169E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37099673.28 | 0.00 | 37099673.28 | 6475076.73 | 0.232914E+09 |
February | 40918508.79 | 0.00 | 40918508.79 | 16292249.64 | 0.189889E+09 |
March | 59306438.91 | 7670.77 | 59298768.14 | 35689164.34 | 0.188482E+09 |
April | 66535406.92 | 781060.78 | 65754346.14 | 69153127.84 | 0.122855E+09 |
May | 81639584.07 | 6316636.56 | 75322947.50 | 0.124584E+09 | 84747504.89 |
June | 83832858.99 | 10571494.93 | 73261364.06 | 0.176860E+09 | 51268509.57 |
July | 79803954.64 | 7754630.16 | 72049324.48 | 0.164561E+09 | 47835012.70 |
August | 67814502.26 | 1858921.28 | 65955580.98 | 0.124997E+09 | 62553031.46 |
September | 56878671.07 | 60335.66 | 56818335.41 | 88782441.81 | 0.105677E+09 |
October | 48740899.13 | 0.00 | 48740899.13 | 39239570.94 | 0.158459E+09 |
November | 38078983.12 | 0.00 | 38078983.12 | 7090218.94 | 0.224602E+09 |
December | 36812348.67 | 0.00 | 36812348.67 | 3456165.22 | 0.267301E+09 |
Annual Sum or Average | 0.697462E+09 | 27350750.15 | 0.670111E+09 | 0.857180E+09 | 0.173658E+10 |
Minimum of Months | 36812348.67 | 0.00 | 36812348.67 | 3456165.22 | 47835012.70 |
Maximum of Months | 83832858.99 | 10571494.93 | 75322947.50 | 0.176860E+09 | 0.267301E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37098677.13 | 0.00 | 37098677.13 | 6474557.84 | 0.232913E+09 |
February | 40917432.20 | 0.00 | 40917432.20 | 16291629.10 | 0.189888E+09 |
March | 59304907.93 | 7670.41 | 59297237.52 | 35687860.11 | 0.188480E+09 |
April | 66533769.09 | 781024.17 | 65752744.91 | 69151802.01 | 0.122854E+09 |
May | 81637421.85 | 6316340.50 | 75321081.36 | 0.124582E+09 | 84746224.63 |
June | 83830620.15 | 10570999.43 | 73259620.71 | 0.176857E+09 | 51267433.02 |
July | 79801737.42 | 7754266.69 | 72047470.73 | 0.164558E+09 | 47834165.79 |
August | 67812748.68 | 1858834.15 | 65953914.53 | 0.124995E+09 | 62552122.49 |
September | 56877294.21 | 60332.84 | 56816961.37 | 88781109.00 | 0.105675E+09 |
October | 48739645.26 | 0.00 | 48739645.26 | 39238459.93 | 0.158458E+09 |
November | 38078011.80 | 0.00 | 38078011.80 | 7089906.84 | 0.224601E+09 |
December | 36811327.25 | 0.00 | 36811327.25 | 3455840.89 | 0.267300E+09 |
Annual Sum or Average | 0.697444E+09 | 27349468.18 | 0.670094E+09 | 0.857163E+09 | 0.173657E+10 |
Minimum of Months | 36811327.25 | 0.00 | 36811327.25 | 3455840.89 | 47834165.79 |
Maximum of Months | 83830620.15 | 10570999.43 | 75321081.36 | 0.176857E+09 | 0.267300E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.229582E+09 | 0.197508E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.271742E+09 | 0.176647E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.429244E+09 | 0.198513E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.527805E+09 | 0.172617E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.611472E+09 | 0.168562E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.642179E+09 | 0.131837E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.580439E+09 | 0.109708E+09 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.534146E+09 | 0.132206E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.466739E+09 | 0.172792E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.342036E+09 | 0.200248E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.244291E+09 | 0.222573E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.203162E+09 | 0.229298E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.508284E+10 | 0.211251E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.203162E+09 | 0.109708E+09 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.642179E+09 | 0.229298E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.229582E+09 | 0.197508E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.271742E+09 | 0.176647E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.429244E+09 | 0.198513E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.527805E+09 | 0.172617E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.611472E+09 | 0.168562E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.642179E+09 | 0.131837E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.580439E+09 | 0.109708E+09 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.534146E+09 | 0.132206E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.466739E+09 | 0.172792E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.342036E+09 | 0.200248E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.244291E+09 | 0.222573E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.203162E+09 | 0.229298E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.508284E+10 | 0.211251E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.203162E+09 | 0.109708E+09 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.642179E+09 | 0.229298E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.229582E+09 | 0.197508E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.271742E+09 | 0.176647E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.429244E+09 | 0.198513E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.527805E+09 | 0.172617E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.611472E+09 | 0.168562E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.642179E+09 | 0.131837E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.580439E+09 | 0.109708E+09 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.534146E+09 | 0.132206E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.466739E+09 | 0.172792E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.342036E+09 | 0.200248E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.244291E+09 | 0.222573E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.203162E+09 | 0.229298E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.508284E+10 | 0.211251E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.203162E+09 | 0.109708E+09 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.642179E+09 | 0.229298E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.229582E+09 | 0.197508E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.271742E+09 | 0.176647E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.429244E+09 | 0.198513E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.527805E+09 | 0.172617E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.611472E+09 | 0.168562E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.642179E+09 | 0.131837E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.580439E+09 | 0.109708E+09 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.534146E+09 | 0.132206E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.466739E+09 | 0.172792E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.342036E+09 | 0.200248E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.244291E+09 | 0.222573E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.203162E+09 | 0.229298E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.508284E+10 | 0.211251E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.203162E+09 | 0.109708E+09 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.642179E+09 | 0.229298E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.229582E+09 | 0.197508E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.271742E+09 | 0.176647E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.429244E+09 | 0.198513E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.527805E+09 | 0.172617E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.611472E+09 | 0.168562E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.642179E+09 | 0.131837E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.580439E+09 | 0.109708E+09 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.534146E+09 | 0.132206E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.466739E+09 | 0.172792E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.342036E+09 | 0.200248E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.244291E+09 | 0.222573E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.203162E+09 | 0.229298E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.508284E+10 | 0.211251E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.203162E+09 | 0.109708E+09 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.642179E+09 | 0.229298E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.229582E+09 | 0.197508E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.271742E+09 | 0.176647E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.429244E+09 | 0.198513E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.527805E+09 | 0.172617E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.611472E+09 | 0.168562E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.642179E+09 | 0.131837E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.580439E+09 | 0.109708E+09 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.534146E+09 | 0.132206E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.466739E+09 | 0.172792E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.342036E+09 | 0.200248E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.244291E+09 | 0.222573E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.203162E+09 | 0.229298E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.508284E+10 | 0.211251E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.203162E+09 | 0.109708E+09 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.642179E+09 | 0.229298E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.229582E+09 | 0.197508E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.271742E+09 | 0.176647E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.429244E+09 | 0.198513E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.527805E+09 | 0.172617E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.611472E+09 | 0.168562E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.642179E+09 | 0.131837E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.580439E+09 | 0.109708E+09 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.534146E+09 | 0.132206E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.466739E+09 | 0.172792E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.342036E+09 | 0.200248E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.244291E+09 | 0.222573E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.203162E+09 | 0.229298E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.508284E+10 | 0.211251E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.203162E+09 | 0.109708E+09 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.642179E+09 | 0.229298E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.229582E+09 | 0.197508E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.271742E+09 | 0.176647E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.429244E+09 | 0.198513E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.527805E+09 | 0.172617E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.611472E+09 | 0.168562E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.642179E+09 | 0.131837E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.580439E+09 | 0.109708E+09 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.534146E+09 | 0.132206E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.466739E+09 | 0.172792E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.342036E+09 | 0.200248E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.244291E+09 | 0.222573E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.203162E+09 | 0.229298E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.508284E+10 | 0.211251E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.203162E+09 | 0.109708E+09 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.642179E+09 | 0.229298E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.229582E+09 | 0.197508E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.271742E+09 | 0.176647E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.429244E+09 | 0.198513E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.527805E+09 | 0.172617E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.611472E+09 | 0.168562E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.642179E+09 | 0.131837E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.580439E+09 | 0.109708E+09 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.534146E+09 | 0.132206E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.466739E+09 | 0.172792E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.342036E+09 | 0.200248E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.244291E+09 | 0.222573E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.203162E+09 | 0.229298E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.508284E+10 | 0.211251E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.203162E+09 | 0.109708E+09 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.642179E+09 | 0.229298E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.229582E+09 | 0.197508E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.271742E+09 | 0.176647E+09 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.429244E+09 | 0.198513E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.527805E+09 | 0.172617E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.611472E+09 | 0.168562E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.642179E+09 | 0.131837E+09 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.580439E+09 | 0.109708E+09 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.534146E+09 | 0.132206E+09 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.466739E+09 | 0.172792E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.342036E+09 | 0.200248E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.244291E+09 | 0.222573E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.203162E+09 | 0.229298E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.508284E+10 | 0.211251E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.203162E+09 | 0.109708E+09 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.642179E+09 | 0.229298E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 150.31 | 441.23 | 161.71 | 75.57 | 86.14 | 0.00 | 0.00 |
February | 192.15 | 403.64 | 184.61 | 80.02 | 104.59 | 0.00 | 0.00 |
March | 297.33 | 364.19 | 249.75 | 110.03 | 139.72 | 0.00 | 0.00 |
April | 420.74 | 253.74 | 287.20 | 127.71 | 159.49 | 0.00 | 0.00 |
May | 536.77 | 177.40 | 315.01 | 140.37 | 174.64 | 0.00 | 0.00 |
June | 630.83 | 109.30 | 312.68 | 141.38 | 171.30 | 0.00 | 0.00 |
July | 559.34 | 98.07 | 279.84 | 115.29 | 164.54 | 0.00 | 0.00 |
August | 498.47 | 128.96 | 263.41 | 109.62 | 153.79 | 0.00 | 0.00 |
September | 461.78 | 219.86 | 262.03 | 121.65 | 140.38 | 0.00 | 0.00 |
October | 312.35 | 310.21 | 223.80 | 109.29 | 114.51 | 0.00 | 0.00 |
November | 192.84 | 439.52 | 185.77 | 94.84 | 90.93 | 0.00 | 0.00 |
December | 127.20 | 502.53 | 154.47 | 69.02 | 85.44 | 0.00 | 0.00 |
Annual Sum or Average | 365.76 | 286.78 | 240.24 | 107.98 | 132.26 | 0.00 | 0.00 |
Minimum of Months | 127.20 | 98.07 | 154.47 | 69.02 | 85.44 | 0.00 | 0.00 |
Maximum of Months | 630.83 | 502.53 | 315.01 | 141.38 | 174.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3001.98 | 3114.41 | 704.34 | 494.14 | 210.20 | 0.00 | 0.00 |
February | 3950.77 | 2966.31 | 901.11 | 637.25 | 263.86 | 0.00 | 0.00 |
March | 5288.56 | 2700.95 | 1258.05 | 887.91 | 370.14 | 0.00 | 0.00 |
April | 7695.23 | 2184.29 | 1564.87 | 1159.99 | 404.88 | 0.00 | 0.00 |
May | 10520.69 | 2615.59 | 1725.33 | 1281.40 | 443.93 | 0.00 | 0.00 |
June | 11658.18 | 3291.29 | 1821.82 | 1411.87 | 409.96 | 0.00 | 0.00 |
July | 10467.35 | 2812.38 | 1576.75 | 1135.85 | 440.90 | 0.00 | 0.00 |
August | 9386.89 | 3078.79 | 1474.36 | 1062.55 | 411.81 | 0.00 | 0.00 |
September | 9003.00 | 3245.56 | 1349.82 | 1008.86 | 340.96 | 0.00 | 0.00 |
October | 5098.89 | 2659.81 | 1018.32 | 739.23 | 279.09 | 0.00 | 0.00 |
November | 3145.92 | 3036.74 | 798.30 | 592.63 | 205.67 | 0.00 | 0.00 |
December | 2714.44 | 3781.49 | 653.25 | 435.21 | 218.05 | 0.00 | 0.00 |
Annual Sum or Average | 6839.82 | 2957.42 | 1238.35 | 904.57 | 333.78 | 0.00 | 0.00 |
Minimum of Months | 2714.44 | 2184.29 | 653.25 | 435.21 | 205.67 | 0.00 | 0.00 |
Maximum of Months | 11658.18 | 3781.49 | 1821.82 | 1411.87 | 443.93 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.402597E+09 | 0.118179E+10 | 0.433125E+09 | 0.202408E+09 | 0.230717E+09 | 0.00 | 0.00 |
February | 0.464852E+09 | 0.976491E+09 | 0.446607E+09 | 0.193580E+09 | 0.253027E+09 | 0.00 | 0.00 |
March | 0.796359E+09 | 0.975435E+09 | 0.668923E+09 | 0.294705E+09 | 0.374218E+09 | 0.00 | 0.00 |
April | 0.109056E+10 | 0.657685E+09 | 0.744422E+09 | 0.331031E+09 | 0.413391E+09 | 0.00 | 0.00 |
May | 0.143770E+10 | 0.475161E+09 | 0.843730E+09 | 0.375973E+09 | 0.467757E+09 | 0.00 | 0.00 |
June | 0.163512E+10 | 0.283308E+09 | 0.810475E+09 | 0.366466E+09 | 0.444009E+09 | 0.00 | 0.00 |
July | 0.149814E+10 | 0.262669E+09 | 0.749516E+09 | 0.308805E+09 | 0.440711E+09 | 0.00 | 0.00 |
August | 0.133511E+10 | 0.345413E+09 | 0.705512E+09 | 0.293595E+09 | 0.411917E+09 | 0.00 | 0.00 |
September | 0.119694E+10 | 0.569874E+09 | 0.679176E+09 | 0.315310E+09 | 0.363865E+09 | 0.00 | 0.00 |
October | 0.836597E+09 | 0.830859E+09 | 0.599424E+09 | 0.292723E+09 | 0.306701E+09 | 0.00 | 0.00 |
November | 0.499852E+09 | 0.113924E+10 | 0.481524E+09 | 0.245827E+09 | 0.235698E+09 | 0.00 | 0.00 |
December | 0.340698E+09 | 0.134598E+10 | 0.413727E+09 | 0.184873E+09 | 0.228854E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115345E+11 | 0.904391E+10 | 0.757616E+10 | 0.340530E+10 | 0.417087E+10 | 0.00 | 0.00 |
Minimum of Months | 0.340698E+09 | 0.262669E+09 | 0.413727E+09 | 0.184873E+09 | 0.228854E+09 | 0.00 | 0.00 |
Maximum of Months | 0.163512E+10 | 0.134598E+10 | 0.843730E+09 | 0.375973E+09 | 0.467757E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.804051E+10 | 0.834163E+10 | 0.188650E+10 | 0.132350E+10 | 0.563002E+09 | 0.00 | 0.00 |
February | 0.955770E+10 | 0.717610E+10 | 0.217996E+10 | 0.154163E+10 | 0.638331E+09 | 0.00 | 0.00 |
March | 0.141649E+11 | 0.723421E+10 | 0.336955E+10 | 0.237818E+10 | 0.991375E+09 | 0.00 | 0.00 |
April | 0.199460E+11 | 0.566168E+10 | 0.405613E+10 | 0.300669E+10 | 0.104944E+10 | 0.00 | 0.00 |
May | 0.281786E+11 | 0.700560E+10 | 0.462114E+10 | 0.343211E+10 | 0.118902E+10 | 0.00 | 0.00 |
June | 0.302180E+11 | 0.853103E+10 | 0.472216E+10 | 0.365955E+10 | 0.106261E+10 | 0.00 | 0.00 |
July | 0.280358E+11 | 0.753269E+10 | 0.422318E+10 | 0.304227E+10 | 0.118091E+10 | 0.00 | 0.00 |
August | 0.251418E+11 | 0.824623E+10 | 0.394892E+10 | 0.284593E+10 | 0.110299E+10 | 0.00 | 0.00 |
September | 0.233358E+11 | 0.841249E+10 | 0.349872E+10 | 0.261496E+10 | 0.883762E+09 | 0.00 | 0.00 |
October | 0.136569E+11 | 0.712405E+10 | 0.272746E+10 | 0.197996E+10 | 0.747507E+09 | 0.00 | 0.00 |
November | 0.815424E+10 | 0.787124E+10 | 0.206920E+10 | 0.153611E+10 | 0.533097E+09 | 0.00 | 0.00 |
December | 0.727035E+10 | 0.101283E+11 | 0.174967E+10 | 0.116566E+10 | 0.584019E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.215701E+12 | 0.932653E+11 | 0.390526E+11 | 0.285265E+11 | 0.105261E+11 | 0.00 | 0.00 |
Minimum of Months | 0.727035E+10 | 0.566168E+10 | 0.174967E+10 | 0.116566E+10 | 0.533097E+09 | 0.00 | 0.00 |
Maximum of Months | 0.302180E+11 | 0.101283E+11 | 0.472216E+10 | 0.365955E+10 | 0.118902E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.931897E+09 | -782879048.8 | 0.00 | 0.00 | 744.00 | 0.00 | -149017884.2 | 58.99 | 0.00 | 0.00 |
February | 0.850198E+09 | -718615782.7 | 0.00 | 0.00 | 672.00 | 0.00 | -131581871.3 | 58.99 | 0.00 | 0.00 |
March | 0.949804E+09 | -808969557.5 | 0.00 | 0.00 | 744.00 | 0.00 | -140834373.6 | 58.99 | 0.00 | 0.00 |
April | 0.829062E+09 | -701670473.3 | 0.00 | 0.00 | 720.00 | 0.00 | -127391756.2 | 58.99 | 0.00 | 0.00 |
May | 0.796877E+09 | -670062588.2 | 0.00 | 0.00 | 744.00 | 0.00 | -126814778.8 | 58.99 | 0.00 | 0.00 |
June | 0.734990E+09 | -614641929.8 | 0.00 | 0.00 | 720.00 | 0.00 | -120348018.8 | 58.99 | 0.00 | 0.00 |
July | 0.688180E+09 | -564850588.4 | 0.00 | 0.00 | 744.00 | 0.00 | -123329022.1 | 58.99 | 0.00 | 0.00 |
August | 0.731779E+09 | -607210790.8 | 0.00 | 0.00 | 744.00 | 0.00 | -124567933.4 | 58.99 | 0.00 | 0.00 |
September | 0.715950E+09 | -594571683.0 | 0.00 | 0.00 | 720.00 | 0.00 | -121377966.5 | 58.99 | 0.00 | 0.00 |
October | 0.776500E+09 | -646574106.6 | 0.00 | 0.00 | 744.00 | 0.00 | -129925811.8 | 58.99 | 0.00 | 0.00 |
November | 0.812044E+09 | -676117906.1 | 0.00 | 0.00 | 720.00 | 0.00 | -135926242.2 | 58.99 | 0.00 | 0.00 |
December | 0.902300E+09 | -753474972.4 | 0.00 | 0.00 | 744.00 | 0.00 | -148824838.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.971958E+10 | -0.813964E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.157994E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.688180E+09 | -808969557.5 | 0.00 | 0.00 | 672.00 | 0.00 | -149017884.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.949804E+09 | -564850588.4 | 0.00 | 0.00 | 744.00 | 0.00 | -120348018.8 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 276.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 373.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 398.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 400.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 377.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 365.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 295.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 289.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4125.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.138784E+10 | 32757.36 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.886064E+09 | 32757.36 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.478027E+09 | 32757.36 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18510097.90 | 24829.16 | 11-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2072870.69 | 5212.30 | 10-MAY-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 756907.56 | 2523.03 | 01-JUN-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1019647.50 | 3398.82 | 19-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.335398E+09 | 32757.36 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146032E+10 | 32757.36 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.457002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.146032E+10 | 32757.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.171807E+10 | 117285.25 | 28-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.775173E+09 | 76175.07 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174373E+09 | 39709.13 | 02-MAR-06:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176127E+09 | 48534.05 | 28-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.277551E+10 | 125887.32 | 27-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.561926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.277551E+10 | 125887.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 52133786.73 | 11885.74 | 28-JAN-05:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.479143E+09 | 26669.00 | 31-DEC-06:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.531277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.479143E+09 | 26669.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1055.38 | 1055.38 | 0.29 | 03-JAN-13:20 | 0.29 | 0.00 |
February | 0.00 | 0.00 | 0.148162E+09 | 0.148162E+09 | 4128.52 | 21-FEB-16:00 | 4128.52 | 0.00 |
March | 0.00 | 0.00 | 0.739652E+09 | 0.739652E+09 | 7055.18 | 14-MAR-16:00 | 7055.18 | 0.00 |
April | 0.00 | 0.00 | 0.403030E+10 | 0.401485E+10 | 23632.26 | 29-APR-05:02 | 20953.02 | 0.00 |
May | 0.00 | 0.00 | 0.861202E+10 | 0.835406E+10 | 25434.49 | 23-MAY-05:01 | 20149.99 | 0.00 |
June | 0.00 | 0.00 | 0.123600E+11 | 0.117753E+11 | 26445.76 | 28-JUN-05:01 | 16169.51 | 0.00 |
July | 0.00 | 0.00 | 0.142191E+11 | 0.115997E+11 | 30258.57 | 21-JUL-05:01 | 12652.07 | 0.00 |
August | 0.00 | 0.00 | 0.130557E+11 | 0.112231E+11 | 29267.63 | 03-AUG-05:01 | 16476.63 | 0.00 |
September | 0.00 | 0.00 | 0.105898E+11 | 0.918008E+10 | 28591.15 | 22-SEP-05:01 | 14811.63 | 0.00 |
October | 0.00 | 0.00 | 0.452512E+10 | 0.408165E+10 | 26758.01 | 04-OCT-05:02 | 14974.50 | 0.00 |
November | 0.00 | 0.00 | 0.443694E+09 | 0.440114E+09 | 8243.31 | 03-NOV-16:00 | 8243.31 | 0.00 |
December | 0.00 | 0.00 | 1192.87 | 1192.87 | 0.27 | 01-DEC-13:10 | 0.27 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.687235E+11 | 0.615566E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1055.38 | 1055.38 | 0.27 | 0.27 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.142191E+11 | 0.117753E+11 | 30258.57 | 20953.02 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 42623.89 | 42623.89 | 5.90 | 23-FEB-13:00 | 5.90 | 0.00 |
March | 0.00 | 0.00 | 0.251452E+09 | 0.251452E+09 | 10544.73 | 22-MAR-13:00 | 10544.73 | 0.00 |
April | 0.00 | 0.00 | 0.116470E+11 | 0.116368E+11 | 93983.85 | 30-APR-10:21 | 93983.85 | 0.00 |
May | 0.00 | 0.00 | 0.309869E+11 | 0.304009E+11 | 103959.27 | 27-MAY-20:45 | 79751.98 | 0.00 |
June | 0.00 | 0.00 | 0.515486E+11 | 0.501932E+11 | 108982.17 | 19-JUN-17:57 | 71987.72 | 0.00 |
July | 0.00 | 0.00 | 0.570193E+11 | 0.491223E+11 | 116377.55 | 21-JUL-21:00 | 60747.76 | 0.00 |
August | 0.00 | 0.00 | 0.484734E+11 | 0.439943E+11 | 111980.55 | 01-AUG-22:15 | 63493.55 | 0.00 |
September | 0.00 | 0.00 | 0.371545E+11 | 0.335014E+11 | 109275.35 | 09-SEP-19:51 | 69648.53 | 0.00 |
October | 0.00 | 0.00 | 0.109239E+11 | 0.101086E+11 | 108143.13 | 03-OCT-17:12 | 72466.15 | 0.00 |
November | 0.00 | 0.00 | 0.222927E+09 | 0.221675E+09 | 11455.27 | 03-NOV-15:00 | 11455.27 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.248228E+12 | 0.229430E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.570193E+11 | 0.501932E+11 | 116377.55 | 93983.85 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 1677391.84 | 0.00 | 254.15 | 28-JAN-05:50 | 0.09 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 11970478.13 | 0.00 | 254.15 | 27-DEC-01:40 | 0.09 |
Annual Sum or Average | 13647869.97 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11970478.13 | 0.00 | 254.15 | 0.09 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.166146E+10 | 0.41 | 1647.85 | 06-JAN-12:40 | 1.04 |
February | 0.152260E+10 | 0.42 | 1647.85 | 01-FEB-08:70 | 1.04 |
March | 0.177437E+10 | 0.43 | 1647.85 | 01-MAR-07:50 | 1.04 |
April | 0.163591E+10 | 0.40 | 1647.85 | 28-APR-10:40 | 1.03 |
May | 0.173046E+10 | 0.43 | 1647.85 | 01-MAY-15:30 | 1.04 |
June | 0.175172E+10 | 0.47 | 1647.85 | 06-JUN-14:50 | 1.03 |
July | 0.170381E+10 | 0.45 | 1647.85 | 08-JUL-16:15 | 1.02 |
August | 0.182546E+10 | 0.46 | 1647.85 | 03-AUG-16:30 | 1.02 |
September | 0.167820E+10 | 0.42 | 1647.85 | 05-SEP-06:20 | 1.02 |
October | 0.164213E+10 | 0.39 | 1647.85 | 16-OCT-13:00 | 1.02 |
November | 0.157427E+10 | 0.39 | 1647.85 | 03-NOV-12:20 | 1.03 |
December | 0.166249E+10 | 0.41 | 1647.85 | 01-DEC-07:13 | 1.03 |
Annual Sum or Average | 0.201629E+11 | 0.42 | |||
Minimum of Months | 0.152260E+10 | 0.39 | 1647.85 | 1.02 | |
Maximum of Months | 0.182546E+10 | 0.47 | 1647.85 | 1.04 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.827461E+10 | 0.73 | 8230.60 | 27-JAN-07:20 | 1.64 |
February | 0.755379E+10 | 0.68 | 8230.60 | 01-FEB-08:30 | 1.63 |
March | 0.881345E+10 | 0.67 | 8230.60 | 07-MAR-12:50 | 1.63 |
April | 0.830135E+10 | 0.67 | 8230.60 | 01-APR-11:20 | 1.63 |
May | 0.910616E+10 | 0.81 | 8230.60 | 01-MAY-14:40 | 1.63 |
June | 0.975025E+10 | 1.00 | 8230.60 | 01-JUN-07:04 | 1.63 |
July | 0.967245E+10 | 0.98 | 8230.60 | 01-JUL-06:10 | 1.61 |
August | 0.990701E+10 | 0.94 | 8230.60 | 01-AUG-06:10 | 1.61 |
September | 0.883456E+10 | 0.77 | 8230.60 | 01-SEP-06:10 | 1.61 |
October | 0.833822E+10 | 0.64 | 8230.60 | 16-OCT-14:30 | 1.61 |
November | 0.783552E+10 | 0.61 | 8230.60 | 01-NOV-13:50 | 1.61 |
December | 0.835068E+10 | 0.79 | 8230.60 | 04-DEC-07:05 | 1.63 |
Annual Sum or Average | 0.104738E+12 | 0.78 | |||
Minimum of Months | 0.755379E+10 | 0.61 | 8230.60 | 1.61 | |
Maximum of Months | 0.990701E+10 | 1.00 | 8230.60 | 1.64 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.166146E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.156300E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.197469E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.276058E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.416386E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.541643E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.570946E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.549089E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.460815E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.286224E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.169384E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.166249E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.395671E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.156300E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.570946E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.827461E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.755380E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.888904E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.118843E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.187482E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.265008E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.272511E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.248556E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.200223E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.115812E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.790183E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.835068E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.181813E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.755380E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.272511E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.166146E+10 | 1055.38 | 0.138784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152260E+10 | 0.148162E+09 | 0.886064E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177437E+10 | 0.739652E+09 | 0.478027E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163591E+10 | 0.403030E+10 | 18510097.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.173046E+10 | 0.861202E+10 | 2072870.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.175172E+10 | 0.123600E+11 | 756907.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.170381E+10 | 0.142191E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.182546E+10 | 0.130557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167820E+10 | 0.105898E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164213E+10 | 0.452512E+10 | 1019647.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157427E+10 | 0.443694E+09 | 0.335398E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166249E+10 | 1192.87 | 0.146032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201629E+11 | 0.687235E+11 | 0.457002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152260E+10 | 1055.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182546E+10 | 0.142191E+11 | 0.146032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.827461E+10 | 0.00 | 0.171807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.755379E+10 | 42623.89 | 0.775173E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.881345E+10 | 0.251452E+09 | 0.174373E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.830135E+10 | 0.116470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.910616E+10 | 0.309869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.975025E+10 | 0.515486E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.967245E+10 | 0.570193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.990701E+10 | 0.484734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.883456E+10 | 0.371545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.833822E+10 | 0.109239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.783552E+10 | 0.222927E+09 | 0.176127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.835068E+10 | 0.00 | 0.277551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104738E+12 | 0.248228E+12 | 0.561926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.755379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.990701E+10 | 0.570193E+11 | 0.277551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.166146E+10 | 0.00 | 0.00 | 0.00 | 294.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152260E+10 | 0.00 | 0.00 | 0.00 | 40401238.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177437E+10 | 0.00 | 0.00 | 0.00 | 0.200316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163591E+10 | 0.00 | 0.00 | 0.00 | 0.112467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.173046E+10 | 0.00 | 0.00 | 0.00 | 0.243340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.175172E+10 | 0.00 | 0.00 | 0.00 | 0.366470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.170381E+10 | 0.00 | 0.00 | 0.00 | 0.400565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.182546E+10 | 0.00 | 0.00 | 0.00 | 0.366543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167820E+10 | 0.00 | 0.00 | 0.00 | 0.292995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164213E+10 | 0.00 | 0.00 | 0.00 | 0.122012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157427E+10 | 0.00 | 0.00 | 0.00 | 0.119571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166249E+10 | 0.00 | 0.00 | 0.00 | 332.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201629E+11 | 0.00 | 0.00 | 0.00 | 0.194042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152260E+10 | 0.00 | 0.00 | 0.00 | 294.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182546E+10 | 0.00 | 0.00 | 0.00 | 0.400565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.827461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.755379E+10 | 0.00 | 0.00 | 0.00 | 12851.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.881345E+10 | 0.00 | 0.00 | 0.00 | 75586661.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.830135E+10 | 0.00 | 0.00 | 0.00 | 0.358295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.910616E+10 | 0.00 | 0.00 | 0.00 | 0.964207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.975025E+10 | 0.00 | 0.00 | 0.00 | 0.167505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.967245E+10 | 0.00 | 0.00 | 0.00 | 0.175787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.990701E+10 | 0.00 | 0.00 | 0.00 | 0.149485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.883456E+10 | 0.00 | 0.00 | 0.00 | 0.111877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.833822E+10 | 0.00 | 0.00 | 0.00 | 0.324301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.783552E+10 | 0.00 | 0.00 | 0.00 | 66317521.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.835068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104738E+12 | 0.00 | 0.00 | 0.00 | 0.770754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.755379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.990701E+10 | 0.00 | 0.00 | 0.00 | 0.175787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.775723E+09 | 0.00 | 0.00 | 392623.04 | 0.00 | 0.344664E+09 | 0.712558E+09 | 0.00 | 0.19 |
February | 0.597911E+09 | 0.00 | 0.00 | 907897.09 | 0.00 | 0.157736E+09 | 0.122646E+10 | 0.00 | 0.35 |
March | 0.411356E+09 | 19990.15 | 0.00 | 2717964.60 | 0.00 | 52210128.84 | 0.242949E+10 | 0.00 | 0.62 |
April | 71183904.77 | 55003762.46 | 0.00 | 4906364.17 | 0.00 | 0.00 | 0.221722E+10 | 0.00 | 0.64 |
May | 8298641.17 | 0.261384E+09 | 0.00 | 6759691.31 | 0.00 | 0.00 | 0.114742E+10 | 0.00 | 0.54 |
June | 467476.66 | 0.611194E+09 | 0.00 | 7612003.76 | 115049.62 | 0.00 | 0.269649E+09 | 0.00 | 0.36 |
July | 0.00 | 0.160891E+10 | 0.00 | 4560538.46 | 0.00 | 0.00 | 37427210.30 | 0.00 | 0.36 |
August | 273198.00 | 0.884558E+09 | 0.00 | 8645115.75 | 653742.87 | 0.00 | 0.442510E+09 | 0.00 | 0.51 |
September | 2186623.71 | 0.666860E+09 | 0.00 | 7738888.57 | 0.00 | 0.00 | 0.747015E+09 | 0.00 | 0.52 |
October | 24258139.58 | 0.151815E+09 | 0.00 | 7070516.70 | 0.00 | 0.00 | 0.303964E+10 | 0.00 | 0.85 |
November | 0.325760E+09 | 0.00 | 0.00 | 3070628.74 | 0.00 | 46916811.48 | 0.273551E+10 | 0.00 | 0.59 |
December | 0.778353E+09 | 0.00 | 0.00 | 416559.95 | 0.00 | 0.387587E+09 | 0.791398E+09 | 0.00 | 0.18 |
Annual Sum or Average | 0.299577E+10 | 0.423974E+10 | 0.00 | 54798792.14 | 768792.49 | 0.989114E+09 | 0.157963E+11 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 392623.04 | 0.00 | 0.00 | 37427210.30 | 0.00 | 0.18 |
Maximum of Months | 0.778353E+09 | 0.160891E+10 | 0.00 | 8645115.75 | 653742.87 | 0.387587E+09 | 0.303964E+10 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.501440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34054850.18 | 0.00 | 0.00 | 0.18 |
February | 0.450528E+10 | 0.00 | 0.00 | 58547.76 | 0.00 | 25293133.55 | 0.210765E+09 | 0.00 | 0.20 |
March | 0.458357E+10 | 0.00 | 0.00 | 1213219.82 | 0.00 | 0.00 | 0.251855E+10 | 0.00 | 0.39 |
April | 0.101664E+10 | 78104461.55 | 0.00 | 14128130.41 | 0.00 | 0.00 | 0.684185E+10 | 0.00 | 0.73 |
May | 0.164558E+09 | 0.489552E+09 | 0.00 | 20335788.05 | 0.00 | 0.00 | 0.556311E+10 | 0.00 | 0.78 |
June | 8782873.29 | 0.138437E+10 | 0.00 | 21596331.29 | 12829.39 | 0.00 | 0.291397E+10 | 0.00 | 0.66 |
July | 2004508.68 | 0.344357E+10 | 0.00 | 10332106.60 | 0.00 | 0.00 | 0.166170E+10 | 0.00 | 0.69 |
August | 32460032.97 | 0.169913E+10 | 0.00 | 21551857.48 | 342399.13 | 0.00 | 0.428499E+10 | 0.00 | 0.82 |
September | 79089115.19 | 0.125864E+10 | 0.00 | 23241570.14 | 0.00 | 0.00 | 0.459003E+10 | 0.00 | 0.79 |
October | 0.802128E+09 | 0.217550E+09 | 0.00 | 15461332.20 | 0.00 | 0.00 | 0.103892E+11 | 0.00 | 0.92 |
November | 0.400395E+10 | 0.00 | 0.00 | 1805321.34 | 0.00 | 0.00 | 0.292207E+10 | 0.00 | 0.33 |
December | 0.534911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47313091.52 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.255620E+11 | 0.857091E+10 | 0.00 | 0.129724E+09 | 355228.51 | 0.106661E+09 | 0.418963E+11 | 0.00 | 0.56 |
Minimum of Months | 2004508.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.534911E+10 | 0.344357E+10 | 0.00 | 23241570.14 | 342399.13 | 47313091.52 | 0.103892E+11 | 0.00 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.640256E+12 | 0.458204E+11 | 0.00 | 0.688179E+10 | 0.155503E+10 |
February | 0.677820E+12 | 0.415034E+11 | 0.00 | 0.672441E+10 | 0.100055E+10 |
March | 0.104500E+13 | 0.528844E+11 | 0.00 | 0.999908E+10 | 0.158650E+10 |
April | 0.116038E+13 | 0.452061E+11 | 0.00 | 0.100498E+11 | 0.203941E+11 |
May | 0.126947E+13 | 0.582231E+11 | 0.00 | 0.617196E+10 | 0.516755E+11 |
June | 0.125597E+13 | 0.746597E+11 | 0.00 | 0.123245E+10 | 0.843242E+11 |
July | 0.119234E+13 | 0.694362E+11 | 0.00 | -0.334835E+10 | 0.928227E+11 |
August | 0.111044E+13 | 0.696408E+11 | 0.00 | 0.219888E+10 | 0.801430E+11 |
September | 0.101643E+13 | 0.570562E+11 | 0.00 | 0.352691E+10 | 0.618620E+11 |
October | 0.877301E+12 | 0.483397E+11 | 0.00 | 0.139232E+11 | 0.199126E+11 |
November | 0.675647E+12 | 0.494308E+11 | 0.00 | 0.100391E+11 | 0.110366E+10 |
December | 0.550786E+12 | 0.405443E+11 | 0.00 | 0.735417E+10 | 0.223452E+10 |
Annual Sum or Average | 0.114718E+14 | 0.652745E+12 | 0.00 | 0.747534E+11 | 0.418614E+12 |
Minimum of Months | 0.550786E+12 | 0.405443E+11 | 0.00 | -0.334835E+10 | 0.100055E+10 |
Maximum of Months | 0.126947E+13 | 0.746597E+11 | 0.00 | 0.139232E+11 | 0.928227E+11 |