Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2023-10-16 10:41:44
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1801.52 | 372.59 | 372.59 |
Net Site Energy | 1801.52 | 372.59 | 372.59 |
Total Source Energy | 4256.48 | 880.32 | 880.32 |
Net Source Energy | 4256.48 | 880.32 | 880.32 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 695.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 46.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 134.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 135.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1105.92 | 695.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 695.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 46.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 134.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 4.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 131.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 695.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 46.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 134.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 135.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 26.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 43.23 | 143.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 228.73 | 143.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 43.23 | 143.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 228.73 | 143.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1105.916 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1105.916 | 100.00 |
Total On-Site and Utility Electric Sources | 1105.916 | 100.00 |
Total Electricity End Uses | 1105.916 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 70.17 |
Time Setpoint Not Met During Occupied Cooling | 2.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3080.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.61 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7186 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 15.0695 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 9.6875 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 11.2890 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 11.2890 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.7186 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 15.0695 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 9.6875 | 46.45 | 2.5587 | |
Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 11.2890 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUN-14:00 | 21-DEC-17:00 | - | - | - | - | - | - | - | - | - | - | 08-JUN-11:09 |
Heating | 0.00 | 337132.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 24377.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 12165.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1770.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 94618.84 | 337132.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 337132.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 24377.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 9860.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1770.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 754.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 146.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1974.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 424.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 430.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 84.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3502.44 | 754.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 155.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 30.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 89.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 724.37 | 155.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 155.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 30.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 89.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 724.37 | 155.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.53 |
ZONE2 FINE STORAGE DIRECT AIR | 4.36 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 4.93 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 4.93 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 163672.83 |
PSZ-OFFICE HEATING COIL | 33100.19 |
PSZ-FINE STORAGE HEATING COIL | 116304.87 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 163672.84 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.53 | 1.53 | 1.53 | 1.53 | 1.53 | 1.53 | 1.00 | 1.000000 | 1.53 |
PSZ-FINE STORAGE | 4.36 | 4.36 | 4.36 | 4.36 | 4.36 | 4.36 | 1.00 | 1.00 | 4.36 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.53 | 0.120335 |
PSZ-FINE STORAGE_OA_CONTROLLER | 4.36 | 0.353926 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.53 | 1675.68 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 4.36 | 8184.59 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.53 | 1.53 | 1.53 | 1.53 | 25343.41 | 33100.19 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 4.36 | 4.36 | 4.36 | 4.36 | 79853.31 | 116304.87 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.53 | 0.765498 | 1.53 | 25343.41 | 12671.74 | 25343.41 | 0.800660 | 0.800660 |
PSZ-FINE STORAGE COOLING COIL | 4.36 | 2.18 | 4.36 | 79853.31 | 41165.29 | 79853.31 | 0.800240 | 0.800240 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.719 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.792 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 15.069 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15.069 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 9.688 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 12.246 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2539.013 | 10.719 | 199.158 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2539.013 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 20997.932 | 15.069 | 699.931 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20997.932 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 31046.942 | 9.688 | 449.956 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 31046.942 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5959 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.7823 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.8517 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.8517 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.678 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.179 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.075 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.075 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53319041E-11 | 0.92099297E-16 | 0.18475806E-15 | 0.0000000 |
5 | 1 | -5.2159728 | 0.43155192E-04 | -0.26885250E-04 | 0.68722794E-11 |
6 | 0 | 5.8118483 | 0.59583229 | 0.59590233 | |
7 | 4 | 0.72249793E-12 | -0.16720573E-15 | 0.22015083E-14 | 0.12409536E-15 |
8 | 3 | -0.36459118E-03 | 0.53555631E-06 | -0.52695411E-04 | 0.13865996E-12 |
9 | 2 | 1.6915239 | 0.11971291E-01 | 1.1039557 | -0.69896550E-04 |
10 | 1 | -7.1930661 | 0.31446443 | -16.864389 | 0.32415671 |
11 | 0 | 6.0306730 | 0.20232993 | 16.289252 | |
12 | 4 | 0.70899133E-12 | 0.18867256E-15 | 0.20714601E-14 | 0.12737467E-15 |
13 | 3 | -0.35990531E-03 | 0.57946993E-06 | -0.51972542E-04 | 0.13607632E-12 |
14 | 2 | 1.6802142 | 0.13022526E-01 | 1.0953649 | -0.68997686E-04 |
15 | 1 | -7.2085490 | 0.34322300 | -16.809118 | 0.32197680 |
16 | 0 | 6.1062597 | 0.22131885 | 16.291370 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.20714601E-14 | 0.18867256E-15 | 0.70899133E-12 | 0.12737467E-15 |
85 | 3 | -0.51972542E-04 | 0.57946993E-06 | -0.35990531E-03 | 0.13607632E-12 |
86 | 2 | 1.0953649 | 0.13022526E-01 | 1.6802142 | -0.68997686E-04 |
87 | 1 | -16.809118 | 0.34322300 | -7.2085490 | 0.32197680 |
88 | 0 | 16.291370 | 0.22131885 | 6.1062597 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5726_SHGC_SOUTH_0.49 | 34 | 1 | VerySmooth | 3.256 | 3.256 | 1.000 | 0.491 | ||
2 | NONRESWINDOW_U_0.5726_SHGC_NORTH_0.49 | 35 | 1 | VerySmooth | 3.256 | 3.256 | 1.000 | 0.491 | ||
3 | NONRESWINDOW_U_0.5726_SHGC_EAST_0.49 | 36 | 1 | VerySmooth | 3.256 | 3.256 | 1.000 | 0.491 | ||
4 | NONRESWINDOW_U_0.5726_SHGC_WEST_0.49 | 37 | 1 | VerySmooth | 3.256 | 3.256 | 1.000 | 0.491 | ||
5 | SKYLIGHT_U_1.02_SHGC_0.49 | 38 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.491 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.40797 | 0.37218 | 0.37218 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 1.45195E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.40797 | 0.37218 | 0.37218 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 1.45195E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.40797 | 0.37218 | 0.37218 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 1.45195E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.40797 | 0.37218 | 0.37218 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 1.45195E-002 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.32532 | 0.12431 | 0.12431 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.849 | 0.366 | 0.255 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 0.153 | 6.473E-004 | 9.992E-004 | 0.546 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.780 | 5.598E-004 | 3.565E-004 | 0.951 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 3.433 | 1.071E-003 | 6.996E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 12588.34015 | 15106.00819 | 1.27583 | 1.53100 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 32.22267 | 5.47268E-003 | 236.87965 | 12.74874 | 0.12033 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 12701.83848 | 15242.20618 | 0.43952 | 0.52743 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -17.90000 | 9.55238E-004 | 236.87965 | 12.74874 | 0.12033 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 45985.01600 | 55182.01920 | 3.63276 | 4.35931 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.90000 | 5.47527E-003 | 1393.40969 | 30.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 49545.84729 | 59455.01675 | 1.44305 | 1.73166 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | -17.90000 | 9.55238E-004 | 1393.40969 | 30.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.90000 | 5.47527E-003 | 3204.84228 | 69.00000 | 0.81403 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 136394.02982 | 163672.83578 | 4.10531 | 4.92637 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 3204.84228 | 69.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 18892.00 | 1.53100 | 1.53100 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 14420.55 | 0.52743 | 0.52743 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 65444.33 | 4.35931 | 4.35931 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 53209.62 | 1.73166 | 1.73166 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.53100 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.35931 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 4.92637 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 4.92637 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 163672.82945 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 163672.83578 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.53100 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.53100 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.53100 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.53100 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.53100 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.53100 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.35931 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.35931 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.35931 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 4.35931 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.35931 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 4.35931 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.53100 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 4.35931 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.53100 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12033 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.53100 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1675.68300 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.53100 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.53100 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.53100 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.53100 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.53100 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.76550 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.53100 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25343.41000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 12671.74309 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 25343.41000 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25343.41000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33100.19166 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 33100.19166 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.35931 |
47 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.35931 |
49 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 8184.59410 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.35931 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.35931 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.35931 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.35931 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.35931 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.17965 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.35931 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 79853.31000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 41165.28655 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 79853.31000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80024 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80024 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 79853.31000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 116304.86610 |
64 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
66 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 116304.86610 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 24155.4 | 10.70 | 10.08 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 76469.4 | 10.15 | 9.56 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.2302760858 | 0.2363990710 | Pass | Pass | 0.7413815091 | 1.2634785097 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.5756296969 | 0.6279101807 | Pass | Pass | 1.6608415055 | 8.9020279305 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 1.3265326299E-002 | 3.0890165943E-002 | Pass | Pass | 5.3111981785E-002 | 0.1488634425 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 10004.27 | 741.53 | 0.00 | 65.55 | 479.36 | 11290.74 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 11.00 | 10 | |||
Feb | 15.00 | 16 | |||
Mar | 88.00 | 32 | |||
Apr | 159.00 | 54 | |||
May | 30.00 | 24 | |||
Jun | 11.00 | 4 | |||
Jul | 167.00 | 26 | |||
Aug | 33.00 | 24 | |||
Sep | 8.00 | 8 | |||
Oct | 13.00 | 10 | |||
Nov | 12.00 | 22 | |||
Dec | 11.00 | 18 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.755 | 0.852 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.755 | 0.852 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.755 | 0.852 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.551 | 0.596 | 3204.84 | 3170.23 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.707 | 0.852 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.707 | 0.852 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.5726_SHGC_WEST_0.49 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.256 | 0.491 | 0.492 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.5726_SHGC_WEST_0.49 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.256 | 0.491 | 0.492 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.5726_SHGC_NORTH_0.49 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.256 | 0.491 | 0.492 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.5726_SHGC_NORTH_0.49 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.256 | 0.491 | 0.492 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.27 | 4.939 | 0.531 | 0.531 | |||||||||||||||||
North Total or Average | 6.51 | 3.256 | 0.491 | 0.492 | |||||||||||||||||
Non-North Total or Average | 45.76 | 5.179 | 0.536 | 0.537 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.7186 | 236.88 | 2539.01 | LightsWired | LTG_SCH_OFFICE | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.86 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 15.0695 | 1393.41 | 20997.93 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 239.15 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 9.6875 | 3204.84 | 31046.94 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 353.60 |
Interior Lighting Total | 11.2890 | 4835.13 | 54583.89 | 623.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 8532.22 | AstronomicalClock | - | 83.67 | 83.67 | 134.01 | |
Exterior Lighting Total | 8532.22 | 134.01 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25343.41 | 20291.45 | 5051.96 | 0.80 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 79853.31 | 63901.81 | 15951.50 | 0.80 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 24155.4 | 10.70 | 10.08 | ||||
PSZ-FINE STORAGE COOLING COIL | 76469.4 | 10.15 | 9.56 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 163672.83 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 33100.19 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 116304.87 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 4.93 | 457.71 | 92.91 | 1.00 | 3.16 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 1.53 | 1675.68 | 1094.51 | 1.00 | 1.33 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.59 | 1110.54 | 4.36 | 8184.59 | 1877.50 | 1.00 | 1.15 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 12588.34 | 15106.01 | 63.77 | 1.276 | 1.531 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 23.90 | 23.90 | 0.00812 | 32.22 | 0.00547 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 45985.02 | 55182.02 | 39.60 | 3.633 | 4.359 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 26.70 | 26.70 | 0.00794 | 33.90 | 0.00548 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 0.00 | 34.31 | 0.00557 | 33.90 | 0.00548 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 12701.84 | 15242.21 | 64.35 | 0.440 | 0.527 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00763 | -17.90 | 0.00096 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 49545.85 | 59455.02 | 42.67 | 1.443 | 1.732 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 15.56 | 15.55 | 0.00654 | -17.90 | 0.00096 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 136394.03 | 163672.84 | 51.07 | 4.105 | 4.926 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00596 | -17.90 | 0.00096 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.53 | 1.53 | 0.53 | 0.53 | 1.5310 | 1.5310 | 1.5310 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 4.36 | 4.36 | 1.73 | 1.73 | 4.3593 | 4.3593 | 4.3593 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 163672.829 | 163672.829 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 163672.83 | 163672.83 | 4.926367 | 10.00 | 6.48 | 0.00595899 | 43.33 | 19.68 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 10.00 | 0.00595899 | 63.5673 | 163672.84 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 25343.410 | 20291.455 | 1.531000 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 25343.41 | 25343.41 | 1.531000 | 25.67 | 14.33 | 0.00791002 | 12.00 | 9.33 | 0.00791002 | 32.42 | 0.00547299 | 14.59 | 7.8599 | 23.90 | 0.00811802 | 35.7085 | 12582.37 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 33100.192 | 33100.192 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 33100.19 | 33100.19 | 1.530996 | 17.99 | 10.90 | 0.00710167 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 7.8599 | 21.10 | 0.00762599 | 39.8005 | 12701.84 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 79853.310 | 63901.813 | 4.359310 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 79853.31 | 79853.31 | 4.359310 | 29.17 | 15.34 | 0.00774341 | 12.00 | 9.17 | 0.00774341 | 33.90 | 0.00547527 | 15.07 | 8.1189 | 26.70 | 0.00794383 | 29.5883 | 45985.02 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 116304.866 | 116304.866 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 116304.87 | 116304.87 | 4.359309 | 12.84 | 7.84 | 0.00608776 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 8.1189 | 15.55 | 0.00654128 | 48.4345 | 49545.85 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 163672.829 | 163672.829 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 4.926367 | 4.81521676 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 163672.83 | 163672.83 | 1.0000 | 4.81521676 | 4.926367 | 10.00 | 6.48 | 0.00595899 | 25058.5 | 43.33 | 19.68 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 163672.83 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 10.00 | 0.00595899 | 10.00 | 0.00595899 | 63.5673 | 163672.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25343.410 | 20291.455 | 1.531000 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5443 | 1004.8586 | 0.9774 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.530996 | 1.49645260 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | Sensible | 25343.41 | 25343.41 | 1.0000 | 1.49645698 | 1.531000 | 25.67 | 14.33 | 0.00791002 | 45951.9 | 12.00 | 9.33 | 0.00791002 | 32017.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25343.41 | 32.42 | 0.00547299 | 14.59 | 0.12033486 | 7.8599 | 23.90 | 0.00811802 | 23.90 | 0.00811802 | 35.7085 | 12582.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33100.192 | 33100.192 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.530996 | 1.49645260 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 33100.19 | 33100.19 | 1.0000 | 1.49645260 | 1.530996 | 17.99 | 10.90 | 0.00710167 | 36073.2 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33100.19 | -17.90 | 0.00095524 | -17.90 | 0.12033486 | 7.8599 | 21.05 | 0.00762599 | 21.10 | 0.00762599 | 39.8005 | 12701.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 79853.310 | 63901.813 | 4.359310 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2346 | 1004.8586 | 0.9774 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 4.359309 | 4.26095293 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 79853.31 | 79853.31 | 1.0000 | 4.26095356 | 4.359310 | 29.17 | 15.34 | 0.00774341 | 49096.3 | 12.00 | 9.17 | 0.00774341 | 31596.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 79853.31 | 33.90 | 0.00547527 | 15.07 | 0.35392606 | 8.1189 | 26.70 | 0.00794383 | 26.70 | 0.00794383 | 29.5883 | 45985.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 116304.866 | 116304.866 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 4.359309 | 4.26095293 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | Sensible | 116304.87 | 116304.87 | 1.0000 | 4.26095293 | 4.359309 | 12.84 | 7.84 | 0.00608776 | 28269.0 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 116304.87 | -17.90 | 0.00095524 | -17.90 | 0.35392606 | 8.1189 | 15.55 | 0.00654128 | 15.55 | 0.00654128 | 48.4345 | 49545.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.12 | 1.53 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.35 | 4.36 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2286.17 | 2479.33 | 1499.67 |
ZONE2 FINE STORAGE | 2990.17 | 2818.17 | 2288.00 |
ZONE3 BULK STORAGE | 3290.33 | 3351.33 | 3062.67 |
Facility | 3541.67 | 3453.83 | 3080.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 166.67 | 103.50 | 56.67 | 2.17 |
ZONE2 FINE STORAGE | 418.17 | 48.00 | 27.67 | 0.00 |
ZONE3 BULK STORAGE | 3.67 | 0.00 | 0.00 | 0.00 |
Facility | 543.83 | 135.00 | 70.17 | 2.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.475 | 0.527 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.421 | 0.429 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.179 | 0.000 | 0.464 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1203 | 0.120 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.3539 | 0.354 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 3204.84 | 0.814 | ||
Total Facility | 83.53 | 111.75 | 39241.41 | 4835.13 | 0.4743 | 1.288 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1729020.53 | 0.00 | 1729020.53 | 3234112.16 | 4963132.69 | 3794880.16 | 5698.76 | 2745.59 | 315.64 | 0.00 |
ZONE2 FINE STORAGE | 4471877.02 | 0.00 | 4471877.02 | 12220565.15 | 16692442.17 | 11161412.23 | 5709.79 | 2901.81 | 148.39 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 83236817.65 | 83236817.65 | 48534297.12 | 0.13E+09 | 25671248.14 | 7329.65 | 64.24 | 1366.11 | 5116.83 |
Total Facility | 6200897.55 | 83236817.65 | 89437715.20 | 63988974.43 | 0.15E+09 | 40627540.53 | 7985.06 | 3004.28 | 1718.16 | 5116.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1321 | 0.0000 | 0.1321 | 0.1467 | 0.2788 | 0.1203 | 574.76 | 2745.59 | 315.64 |
ZONE2 FINE STORAGE | 0.3416 | 0.0000 | 0.3416 | 0.3490 | 0.6906 | 0.3539 | 585.79 | 2901.81 | 148.39 |
ZONE3 BULK STORAGE | 0.0000 | 4.4318 | 4.4318 | 1.7638 | 6.1956 | 0.8140 | 2819.95 | 28.55 | 787.50 |
Total Facility | 0.4737 | 4.4318 | 4.9055 | 2.2594 | 7.1650 | 1.2883 | 2861.06 | 2968.58 | 1139.56 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 1651879.04 | 0.00 | 1651879.04 | 3794880.16 | 8445.26 | 1.06 | 313.69 | 0.00 |
PSZ-FINE STORAGE | 4272361.04 | 0.00 | 4272361.04 | 11161412.23 | 8612.19 | 0.50 | 147.31 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1262 | 0.0000 | 0.1262 | 0.1203 | 3321.26 | 1.06 | 313.69 |
PSZ-FINE STORAGE | 0.3264 | 0.0000 | 0.3264 | 0.3539 | 3488.19 | 0.50 | 147.31 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2745.04 | 325.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2901.65 | 151.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1150 | 0.4408 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.3382 | 1.3617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 383 |
Defaulted Fields | 319 |
Fields with Defaults | 1020 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1105.92 | 6718.26 | 01-JAN-12:20 | 94618.84 | 26-JUN-15:00 |
Electricity:Building | 767.18 | 6235.26 | 01-JAN-00:10 | 58611.10 | 06-JUN-10:50 |
Electricity:Zone:ZONE1 OFFICE | 62.81 | 1030.77 | 01-JAN-00:10 | 3867.54 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 762.90 | 6235.26 | 01-JAN-00:10 | 56305.80 | 02-JAN-09:10 |
InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 465.23 | 3104.69 | 01-JAN-00:10 | 36895.31 | 06-JUN-10:50 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 135.89 | 0.00 | 01-JAN-10:10 | 12165.57 | 07-JUL-09:40 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 4.28 | 0.00 | 01-JAN-00:10 | 2305.29 | 26-JUN-09:50 |
Ventilation (simple):Fans:Electricity | 4.28 | 0.00 | 01-JAN-00:10 | 2305.29 | 26-JUN-09:50 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 4.28 | 0.00 | 01-JAN-00:10 | 2305.29 | 26-JUN-09:50 |
ElectricityPurchased:Facility | 1105.92 | 6718.26 | 01-JAN-12:20 | 94618.84 | 26-JUN-15:00 |
ElectricityPurchased:Plant | 1105.92 | 6718.26 | 01-JAN-12:20 | 94618.84 | 26-JUN-15:00 |
Cogeneration:ElectricityPurchased | 1105.92 | 6718.26 | 01-JAN-12:20 | 94618.84 | 26-JUN-15:00 |
General:Cogeneration:ElectricityPurchased | 1105.92 | 6718.26 | 01-JAN-12:20 | 94618.84 | 26-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1105.92 | 6718.26 | 01-JAN-12:20 | 94618.84 | 26-JUN-15:00 |
ElectricityNet:Plant | 1105.92 | 6718.26 | 01-JAN-12:20 | 94618.84 | 26-JUN-15:00 |
Cogeneration:ElectricityNet | 1105.92 | 6718.26 | 01-JAN-12:20 | 94618.84 | 26-JUN-15:00 |
General:Cogeneration:ElectricityNet | 1105.92 | 6718.26 | 01-JAN-12:20 | 94618.84 | 26-JUN-15:00 |
Electricity:HVAC | 177.92 | 0.00 | 01-JAN-10:10 | 35154.56 | 26-JUN-15:10 |
General:Fans:Electricity | 131.61 | 0.00 | 01-JAN-10:10 | 10317.99 | 06-FEB-13:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 46.31 | 0.00 | 01-JAN-00:10 | 25294.28 | 26-JUN-15:10 |
General:Cooling:Electricity | 46.31 | 0.00 | 01-JAN-00:10 | 25294.28 | 26-JUN-15:10 |
ExteriorLights:Electricity | 134.01 | 0.00 | 01-JAN-07:30 | 8532.22 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 134.01 | 0.00 | 01-JAN-07:30 | 8532.22 | 01-JAN-00:10 |
Electricity:Plant | 26.80 | 483.00 | 02-JAN-06:50 | 2664.10 | 15-FEB-12:50 |
WaterSystems:Electricity | 26.80 | 483.00 | 02-JAN-06:50 | 2664.10 | 15-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 26.80 | 483.00 | 02-JAN-06:50 | 2664.10 | 15-FEB-12:50 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 695.61 | 4750.00 | 16-JUN-10:30 | 337132.75 | 21-DEC-18:00 |
NaturalGas:HVAC | 695.61 | 4750.00 | 16-JUN-10:30 | 337132.75 | 21-DEC-18:00 |
Heating:NaturalGas | 695.61 | 4750.00 | 16-JUN-10:30 | 337132.75 | 21-DEC-18:00 |
General:Heating:NaturalGas | 695.61 | 4750.00 | 16-JUN-10:30 | 337132.75 | 21-DEC-18:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 08-JUN-11:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 08-JUN-11:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 08-JUN-11:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 08-JUN-11:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 08-JUN-11:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 08-JUN-11:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 08-JUN-11:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 08-JUN-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1138.10 | 0.00 | 01-JAN-10:10 | 523748.11 | 23-DEC-06:10 |
EnergyTransfer:Building | 567.75 | 0.00 | 01-JAN-10:10 | 264218.40 | 23-DEC-06:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 70.82 | 0.00 | 01-JAN-00:10 | 30096.00 | 20-DEC-07:20 |
Heating:EnergyTransfer | 454.22 | 0.00 | 01-JAN-10:10 | 264218.40 | 23-DEC-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 35.12 | 0.00 | 01-JAN-00:10 | 30096.00 | 20-DEC-07:20 |
General:Heating:EnergyTransfer | 454.22 | 0.00 | 01-JAN-10:10 | 264218.40 | 23-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 35.12 | 0.00 | 01-JAN-00:10 | 30096.00 | 20-DEC-07:20 |
Cooling:EnergyTransfer | 113.53 | 0.00 | 01-JAN-00:10 | 52669.84 | 26-JUN-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 35.70 | 0.00 | 01-JAN-00:10 | 14129.41 | 26-JUN-17:00 |
General:Cooling:EnergyTransfer | 113.53 | 0.00 | 01-JAN-00:10 | 52669.84 | 26-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 35.70 | 0.00 | 01-JAN-00:10 | 14129.41 | 26-JUN-17:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 220.54 | 0.00 | 01-JAN-00:40 | 85685.32 | 21-DEC-18:50 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 142.72 | 0.00 | 01-JAN-00:40 | 85685.32 | 21-DEC-18:50 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 142.72 | 0.00 | 01-JAN-00:40 | 85685.32 | 21-DEC-18:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 77.82 | 0.00 | 01-JAN-00:10 | 40688.66 | 26-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 77.82 | 0.00 | 01-JAN-00:10 | 40688.66 | 26-JUN-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 276.39 | 0.00 | 01-JAN-09:30 | 164828.73 | 21-DEC-18:30 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 276.39 | 0.00 | 01-JAN-09:30 | 164828.73 | 21-DEC-18:30 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 276.39 | 0.00 | 01-JAN-09:30 | 164828.73 | 21-DEC-18:30 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 570.35 | 0.00 | 01-JAN-10:10 | 260934.72 | 21-DEC-18:00 |
HeatingCoils:EnergyTransfer | 416.45 | 0.00 | 01-JAN-10:10 | 260934.72 | 21-DEC-18:00 |
CoolingCoils:EnergyTransfer | 153.90 | 0.00 | 01-JAN-00:10 | 68752.95 | 26-JUN-15:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 35.117 | -35.701 | 0.000 | 0.000 | 9.825 | 30.864 | 31.946 | 16.867 | 0.000 | 1.903 | 0.000 | 0.000 | -12.142 | 0.000 | -36.796 | -41.883 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 142.715 | -77.821 | 0.000 | 0.000 | 22.653 | 239.148 | 0.000 | 0.000 | 0.000 | 2.924 | 0.000 | 0.000 | 0.000 | 0.000 | -131.929 | -197.691 |
ZONE3 BULK STORAGE | 276.386 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 58.470 | 353.598 | 107.344 | 154.680 | 0.000 | 13.499 | 0.000 | 0.000 | -133.298 | 0.000 | -550.543 | -280.136 |
Total Facility | 276.386 | 0.000 | 177.832 | -113.522 | 0.000 | 0.000 | 90.948 | 623.610 | 139.290 | 171.547 | 0.000 | 18.327 | 0.000 | 0.000 | -145.440 | 0.000 | -719.268 | -519.710 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 06-AUG-23:01 | 0.00 | 0.00 | 0.00 | -22438.24 | 0.00 | 0.00 | 0.00 | 457.02 | 573.75 | 0.00 | 0.00 | 0.00 | 22311.13 | 0.00 | -469.36 | 0.00 | -434.30 | 0.00 |
ZONE2 FINE STORAGE | 06-AUG-13:23 | 0.00 | 0.00 | 0.00 | -67605.11 | 0.00 | 0.00 | 0.00 | 2099.79 | 0.00 | 0.00 | 0.00 | 578.96 | 64926.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JUL-17:05 | 0.00 | 0.00 | 0.00 | -84689.10 | 0.00 | 0.00 | 0.00 | 5661.51 | 2623.78 | 20365.41 | 0.00 | 3330.73 | 57608.79 | 0.00 | 0.00 | 0.00 | -4901.12 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 20-DEC-07:13 | 0.00 | 0.00 | 34420.28 | 0.00 | 0.00 | 0.00 | 226.41 | 1066.39 | 956.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1637.58 | 0.00 | -17691.74 | -17340.00 |
ZONE2 FINE STORAGE | 21-DEC-19:21 | 0.00 | 0.00 | 129396.34 | 0.00 | 0.00 | 0.00 | 0.00 | 2099.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -27693.76 | -103802.37 |
ZONE3 BULK STORAGE | 21-DEC-18:11 | 164932.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -17826.95 | 0.00 | -121349.31 | -30910.76 |
Total Facility | 23-DEC-06:01 | 164357.01 | 0.00 | 162271.76 | 0.00 | 0.00 | 0.00 | 1465.72 | 5788.46 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19731.75 | 0.00 | -112405.59 | -204369.38 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.5310 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1203 | 1.5310 | 0.0786 | 1.0000 | Not calculated | 0.1203 | 0.0786 | ||
PSZ-FINE STORAGE | 4.3593 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.3539 | 4.3593 | 0.0812 | 1.0000 | Not calculated | 0.3539 | 0.0812 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.5310 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1203 | 1.5310 | 1.0000 | 1.0000 | Not calculated | 0.1203 | 0.0786 | ||
PSZ-FINE STORAGE | 4.3593 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.3539 | 4.3593 | 1.0000 | 1.0000 | Not calculated | 0.3539 | 0.0812 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5310 | 1.5310 | 1.5310 | No | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.3593 | 4.3593 | 4.3593 | No | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.5310 | 1.5310 | 1.5310 | 1.5310 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 4.3593 | 4.3593 | 4.3593 | 4.3593 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5310 | 1.5310 | 1.5310 | No | 0.1203 | 0.2282 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.3593 | 4.3593 | 4.3593 | No | 0.3539 | 0.2044 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.5310 | 1.5310 | 1.5310 | 1.5310 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 4.3593 | 4.3593 | 4.3593 | 4.3593 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 70.17 |
Number of hours cooling loads not met | 2.17 |
Number of hours not met | 72.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 695.61 | 337132.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 46.31 | 25294.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 623.61 | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 134.01 | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 4.28 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 131.61 | 10317.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.80 | 2664.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 1105.92 |
Natural Gas | 0.00 | 695.61 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 1801.52 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 128.97 |
Space Heating | 0.00 |
Space Cooling | 9.58 |
Fans (All) | 28.11 |
Service Water Heating | 5.54 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 228.73 |
Subtotal | 228.73 |
Natural Gas [MJ/m2] | |
Space Heating | 143.87 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 143.87 |
Subtotal | 143.87 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 34.62 |
Space Heating | 38.61 |
Space Cooling | 2.57 |
Fans (All) | 7.54 |
Service Water Heating | 1.49 |
Receptacle Equipment | 7.73 |
Miscellaneous | 7.44 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 3430. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8605.00 | 155.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8625.50 | 134.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7169.50 | 1579.67 | 10.83 | 0.00 | 0.00 |
Min | 7169.50 | 134.50 | 0.00 | 0.00 | 0.00 |
Max | 8625.50 | 1579.67 | 10.83 | 0.00 | 0.00 |
Average | 8133.33 | 623.06 | 3.61 | 0.00 | 0.00 |
Sum | 24400.00 | 1869.17 | 10.83 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 80626.00 | 2093.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 140170.83 | 50495.17 | 527.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 140170.83 | 50495.17 | 527.00 | 0.00 | 0.00 |
Average | 84607.94 | 17529.39 | 175.67 | 0.00 | 0.00 |
Sum | 253823.83 | 52588.17 | 527.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8700.50 | 59.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8547.67 | 212.33 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7864.33 | 895.67 | 0.00 | 0.00 | 0.00 |
Min | 7864.33 | 59.50 | 0.00 | 0.00 | 0.00 |
Max | 8700.50 | 895.67 | 0.00 | 0.00 | 0.00 |
Average | 8370.83 | 389.17 | 0.00 | 0.00 | 0.00 |
Sum | 25112.50 | 1167.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 80143.00 | 2576.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 160475.33 | 30717.67 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 160475.33 | 30717.67 | 0.00 | 0.00 | 0.00 |
Average | 91215.11 | 11097.89 | 0.00 | 0.00 | 0.00 |
Sum | 273645.33 | 33293.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 90875034.62 | 2113.57 | 20-JAN-15:50 | 18.33 | 7.40 | 0.522525E+09 | 768.96 | 23-JAN-16:19 | 17.33 | 6.05 |
February | 45906760.52 | 1929.16 | 18-FEB-14:50 | 19.17 | 7.95 | 0.470960E+09 | 768.96 | 18-FEB-16:00 | 17.00 | 6.80 |
March | 0.410412E+09 | 8445.76 | 13-MAR-17:12 | 20.67 | 6.10 | 0.582658E+09 | 768.97 | 16-MAR-12:09 | 16.00 | 5.12 |
April | 0.319938E+09 | 5656.22 | 20-APR-17:20 | 18.33 | 8.40 | 0.549559E+09 | 768.97 | 19-APR-12:09 | 18.33 | 8.40 |
May | 0.230402E+10 | 15434.43 | 31-MAY-17:08 | 26.83 | 14.58 | 0.637061E+09 | 769.03 | 30-MAY-15:09 | 26.83 | 14.58 |
June | 0.827282E+10 | 21780.14 | 25-JUN-23:01 | 19.40 | 11.14 | 0.659932E+09 | 769.06 | 03-JUN-14:00 | 19.40 | 11.14 |
July | 0.815881E+10 | 21865.79 | 16-JUL-23:01 | 21.67 | 10.80 | 0.634723E+09 | 769.06 | 27-JUL-13:50 | 26.50 | 16.93 |
August | 0.860690E+10 | 22438.31 | 06-AUG-23:01 | 18.00 | 12.51 | 0.685364E+09 | 769.06 | 05-AUG-13:30 | 18.00 | 12.51 |
September | 0.591642E+10 | 21634.77 | 04-SEP-23:01 | 16.73 | 11.35 | 0.630626E+09 | 769.06 | 01-SEP-13:00 | 16.73 | 11.35 |
October | 0.123366E+10 | 7887.64 | 10-OCT-17:13 | 23.00 | 7.55 | 0.579228E+09 | 768.97 | 28-OCT-15:30 | 12.50 | 4.64 |
November | 0.297844E+09 | 3859.65 | 07-NOV-15:30 | 21.50 | 7.27 | 0.519743E+09 | 768.97 | 25-NOV-16:19 | 10.33 | 3.93 |
December | 44335415.47 | 2177.70 | 02-DEC-15:30 | 20.00 | 7.03 | 0.516116E+09 | 768.97 | 02-DEC-13:09 | 20.00 | 7.03 |
Annual Sum or Average | 0.357019E+11 | 0.698849E+10 | ||||||||
Minimum of Months | 44335415.47 | 1929.16 | 16.73 | 6.10 | 0.470960E+09 | 768.96 | 10.33 | 3.93 | ||
Maximum of Months | 0.860690E+10 | 22438.31 | 26.83 | 14.58 | 0.685364E+09 | 769.06 | 26.83 | 16.93 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10930786.03 | 2656.42 | 05-JAN-15:00 | -15.0 | -15.0 | 0.991555E+09 | 2010.20 | 20-JAN-14:39 | 20.33 | 6.84 |
February | 6087693.96 | 707.06 | 11-FEB-13:20 | -7.0 | -7.1 | 0.865218E+09 | 2040.28 | 18-FEB-14:50 | 19.17 | 7.95 |
March | 0.102533E+09 | 6578.65 | 15-MAR-14:20 | 20.67 | 6.10 | 0.121107E+10 | 2246.80 | 16-MAR-14:39 | 16.00 | 5.22 |
April | 7175987.26 | 1823.44 | 21-APR-13:30 | 15.50 | 6.04 | 0.120421E+10 | 2246.80 | 20-APR-13:09 | 15.50 | 6.04 |
May | 0.210189E+10 | 15840.50 | 18-MAY-14:30 | 23.50 | 11.45 | 0.173404E+10 | 2246.82 | 23-MAY-15:09 | 18.00 | 11.42 |
June | 0.209908E+11 | 62617.28 | 15-JUN-17:05 | 31.63 | 14.49 | 0.192124E+10 | 2247.03 | 17-JUN-13:39 | 26.63 | 17.27 |
July | 0.212791E+11 | 66042.43 | 23-JUL-11:13 | 30.67 | 16.00 | 0.184957E+10 | 2247.00 | 20-JUL-14:20 | 30.67 | 16.00 |
August | 0.209672E+11 | 67607.59 | 06-AUG-13:23 | 28.50 | 16.13 | 0.199564E+10 | 2247.03 | 04-AUG-10:00 | 28.50 | 16.13 |
September | 0.117218E+11 | 61968.07 | 10-SEP-12:43 | 32.25 | 13.24 | 0.180661E+10 | 2246.97 | 01-SEP-14:39 | 32.25 | 13.24 |
October | 0.622643E+09 | 13877.99 | 11-OCT-14:20 | 26.67 | 9.64 | 0.137436E+10 | 2246.80 | 21-OCT-13:30 | 14.50 | 5.62 |
November | 13656437.61 | 1505.69 | 29-NOV-11:00 | -9.0 | -9.0 | 0.105415E+10 | 2246.80 | 08-NOV-15:30 | -9.0 | -9.0 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 2.77 | -0.5 | 0.904893E+09 | 1939.84 | 02-DEC-15:09 | 21.33 | 7.63 |
Annual Sum or Average | 0.778239E+11 | 0.169126E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -15.0 | -15.0 | 0.865218E+09 | 1939.84 | -9.0 | -9.0 | ||
Maximum of Months | 0.212791E+11 | 67607.59 | 32.25 | 16.13 | 0.199564E+10 | 2247.03 | 32.25 | 17.27 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.50 | -1.8 | 0.101826E+10 | 2100.72 | 24-JAN-14:50 | 17.17 | 6.51 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -5.3 | -5.3 | 0.873044E+09 | 2216.12 | 18-FEB-14:39 | 19.33 | 7.91 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.1 | -1.1 | 0.138458E+10 | 3603.39 | 15-MAR-14:20 | 20.67 | 6.10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 | 2.10 | 0.140921E+10 | 3021.51 | 21-APR-13:39 | 15.33 | 5.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 | 4.75 | 0.293603E+10 | 5079.40 | 31-MAY-15:09 | 28.00 | 14.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 | 11.26 | 0.539239E+10 | 9097.65 | 26-JUN-13:20 | 36.97 | 15.36 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 | 10.91 | 0.536004E+10 | 9008.79 | 17-JUL-13:09 | 35.83 | 14.79 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 | 15.43 | 0.564169E+10 | 9097.65 | 16-AUG-14:09 | 36.83 | 16.33 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 | 10.64 | 0.438583E+10 | 7525.02 | 09-SEP-13:09 | 32.43 | 12.96 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 | 8.03 | 0.212341E+10 | 4749.94 | 11-OCT-14:39 | 26.33 | 9.55 |
November | 0.00 | 0.00 | 01-NOV-00:03 | -5.7 | -5.7 | 0.112346E+10 | 2735.09 | 09-NOV-11:00 | 20.00 | 9.32 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 2.77 | -0.5 | 0.882923E+09 | 2090.52 | 04-DEC-14:30 | 19.50 | 6.42 |
Annual Sum or Average | 0.00 | 0.325309E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -5.7 | -5.7 | 0.873044E+09 | 2090.52 | 15.33 | 5.87 | ||
Maximum of Months | 0.00 | 0.00 | 22.27 | 15.43 | 0.564169E+10 | 9097.65 | 36.97 | 16.33 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.540113E+10 | 33650.74 | 05-JAN-06:12 | -17.0 |
February | 0.633809E+10 | 33844.77 | 13-FEB-06:12 | -10.7 |
March | 0.494090E+10 | 33703.78 | 19-MAR-02:42 | -9.0 |
April | 0.331146E+10 | 34005.67 | 17-APR-05:31 | -8.0 |
May | 0.706558E+09 | 33277.24 | 02-MAY-05:01 | 1.67 |
June | 30493260.90 | 1961.33 | 15-JUN-06:07 | 16.10 |
July | 19053271.25 | 1923.34 | 20-JUL-06:07 | 14.83 |
August | 54777328.08 | 1990.42 | 09-AUG-06:07 | 13.17 |
September | 0.158656E+09 | 23331.85 | 22-SEP-05:02 | -1.7 |
October | 0.236871E+10 | 33730.80 | 30-OCT-05:22 | -10.0 |
November | 0.390304E+10 | 34062.41 | 30-NOV-06:31 | -12.0 |
December | 0.788444E+10 | 34420.22 | 20-DEC-07:13 | -19.0 |
Annual Sum or Average | 0.351173E+11 | |||
Minimum of Months | 19053271.25 | 1923.34 | -19.0 | |
Maximum of Months | 0.788444E+10 | 34420.22 | 16.10 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.208606E+11 | 121524.42 | 16-JAN-02:12 | -10.7 |
February | 0.242964E+11 | 121738.44 | 12-FEB-09:22 | -12.5 |
March | 0.183685E+11 | 129014.42 | 19-MAR-07:01 | -15.2 |
April | 0.138824E+11 | 121460.65 | 16-APR-01:42 | -3.8 |
May | 0.345473E+10 | 109339.41 | 02-MAY-05:01 | 1.67 |
June | 0.413775E+09 | 8022.14 | 10-JUN-06:25 | 13.30 |
July | 0.277931E+09 | 8139.36 | 29-JUL-06:25 | 17.50 |
August | 0.474755E+09 | 8156.81 | 24-AUG-06:25 | 14.00 |
September | 0.103739E+10 | 8186.01 | 20-SEP-06:25 | 11.65 |
October | 0.870815E+10 | 121611.22 | 29-OCT-17:22 | -6.0 |
November | 0.150253E+11 | 126776.53 | 30-NOV-06:01 | -12.0 |
December | 0.359158E+11 | 129395.97 | 21-DEC-19:21 | -20.5 |
Annual Sum or Average | 0.142716E+12 | |||
Minimum of Months | 0.277931E+09 | 8022.14 | -20.5 | |
Maximum of Months | 0.359158E+11 | 129395.97 | 17.50 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.418813E+11 | 93643.38 | 05-JAN-19:51 | -17.0 |
February | 0.604963E+11 | 129283.94 | 12-FEB-05:51 | -19.0 |
March | 0.276187E+11 | 151888.61 | 19-MAR-07:00 | -15.6 |
April | 0.145471E+11 | 70124.83 | 17-APR-05:00 | -8.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.100017E+11 | 79231.00 | 31-OCT-23:57 | -5.8 |
November | 0.243118E+11 | 122587.81 | 30-NOV-06:00 | -12.0 |
December | 0.975301E+11 | 164931.80 | 21-DEC-18:11 | -21.3 |
Annual Sum or Average | 0.276387E+12 | |||
Minimum of Months | 0.00 | 0.00 | -21.3 | |
Maximum of Months | 0.975301E+11 | 164931.80 | 22.27 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.258145E+10 | 1955.04 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.235440E+10 | 1955.04 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.269003E+10 | 1955.04 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.254196E+10 | 1955.04 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.263574E+10 | 1955.04 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.259625E+10 | 1955.04 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.258145E+10 | 1955.04 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.269003E+10 | 1955.04 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.254196E+10 | 1955.04 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.258145E+10 | 1955.04 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.248766E+10 | 1955.04 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.258145E+10 | 1955.04 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.308638E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.235440E+10 | 1955.04 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.269003E+10 | 1955.04 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.198922E+11 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.182065E+11 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.210336E+11 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.197108E+11 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.204629E+11 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.202815E+11 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.198922E+11 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.210336E+11 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.197108E+11 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.198922E+11 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.191400E+11 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.198922E+11 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.239148E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.182065E+11 | 17848.24 | 0.00 | 0.00 | |
Maximum of Months | 0.210336E+11 | 17848.24 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.294120E+11 | 26389.90 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.269196E+11 | 26389.90 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.310997E+11 | 26389.90 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.291438E+11 | 26389.90 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.302559E+11 | 26389.90 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.299876E+11 | 26389.90 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.294120E+11 | 26389.90 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.310997E+11 | 26389.90 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.291438E+11 | 26389.90 | 01-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.294120E+11 | 26389.90 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.282999E+11 | 26389.90 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.294120E+11 | 26389.90 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.353598E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.269196E+11 | 26389.90 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.310997E+11 | 26389.90 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360253E+10 |
February | 0.127628E+10 | 0.235440E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457979E+10 |
March | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3855.83 | 0.455753E+10 |
April | 0.138726E+10 | 0.254196E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411449E+10 |
May | 0.144276E+10 | 0.263574E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40355662.38 | 0.237422E+10 |
June | 0.144276E+10 | 0.259625E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609413E+09 | 0.849963E+09 |
July | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531413E+09 | 0.824006E+09 |
August | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505265E+09 | 0.949331E+09 |
September | 0.138726E+10 | 0.254196E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211458E+09 | 0.149481E+10 |
October | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5417688.78 | 0.369595E+10 |
November | 0.133177E+10 | 0.248766E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1746.14 | 0.378050E+10 |
December | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597256E+10 |
Annual Sum or Average | 0.168137E+11 | 0.308638E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190333E+10 | 0.367957E+11 |
Minimum of Months | 0.127628E+10 | 0.235440E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.824006E+09 |
Maximum of Months | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609413E+09 | 0.597256E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935773E+10 |
February | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150042E+11 |
March | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161766E+11 |
April | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159163E+11 |
May | 0.339505E+10 | 0.204629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12648689.49 | 0.942076E+10 |
June | 0.339505E+10 | 0.202815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.992949E+09 | 0.479502E+10 |
July | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104619E+10 | 0.480311E+10 |
August | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.652931E+09 | 0.496537E+10 |
September | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219298E+09 | 0.702485E+10 |
October | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71570.77 | 0.125606E+11 |
November | 0.313390E+10 | 0.191400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108216E+11 |
December | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210833E+11 |
Annual Sum or Average | 0.395654E+11 | 0.239148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292409E+10 | 0.131929E+12 |
Minimum of Months | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479502E+10 |
Maximum of Months | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104619E+10 | 0.210833E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227913E+09 | 0.229756E+11 |
February | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172082E+09 | 0.385366E+11 |
March | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150102E+09 | 0.395010E+11 |
April | 0.750829E+10 | 0.291438E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731468E+09 | 0.363841E+11 |
May | 0.780862E+10 | 0.302559E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627150E+09 | 0.246374E+11 |
June | 0.780862E+10 | 0.299876E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303106E+09 | 0.207032E+11 |
July | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117466E+09 | 0.233877E+11 |
August | 0.810895E+10 | 0.310997E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61097889.65 | 0.228688E+11 |
September | 0.750829E+10 | 0.291438E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195678E+09 | 0.273823E+11 |
October | 0.750829E+10 | 0.294120E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29091720.96 | 0.361977E+11 |
November | 0.720796E+10 | 0.282999E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258408E+09 | 0.274773E+11 |
December | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761174E+09 | 0.554981E+11 |
Annual Sum or Average | 0.910005E+11 | 0.353598E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363474E+10 | 0.375550E+12 |
Minimum of Months | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29091720.96 | 0.207032E+11 |
Maximum of Months | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761174E+09 | 0.554981E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1955.04 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 14037.18 | 05-JAN-18:00 |
February | 1680.92 | 01-FEB-08:09 | 1955.04 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 12961.40 | 13-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 1955.04 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.43 | 14-MAR-13:00 | 13199.93 | 27-MAR-16:10 |
April | 1680.92 | 01-APR-07:10 | 1955.04 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 12353.79 | 14-APR-07:00 |
May | 1680.92 | 01-MAY-07:10 | 1955.04 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1497.96 | 31-MAY-16:10 | 9789.60 | 02-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 1955.04 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5053.79 | 26-JUN-17:00 | 4708.25 | 09-JUN-06:03 |
July | 1680.92 | 01-JUL-07:10 | 1955.04 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3709.91 | 17-JUL-16:10 | 4884.99 | 03-JUL-06:03 |
August | 1680.92 | 01-AUG-07:10 | 1955.04 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4202.20 | 16-AUG-17:00 | 4160.47 | 15-AUG-06:03 |
September | 1680.92 | 01-SEP-07:10 | 1955.04 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2648.06 | 12-SEP-16:10 | 9346.29 | 21-SEP-16:02 |
October | 1680.92 | 02-OCT-07:10 | 1955.04 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 405.08 | 10-OCT-17:00 | 12548.59 | 30-OCT-16:10 |
November | 1680.92 | 01-NOV-07:10 | 1955.04 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 | 05-NOV-13:00 | 13019.33 | 29-NOV-18:00 |
December | 1680.92 | 01-DEC-08:09 | 1955.04 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 21598.23 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4160.47 | |||||
Maximum of Months | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 5053.79 | 21598.23 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 14840.87 | 14-JAN-16:03 |
February | 3955.50 | 01-FEB-08:09 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 21343.83 | 11-FEB-16:03 |
March | 3955.50 | 01-MAR-08:09 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 38888.90 | 19-MAR-07:06 |
April | 3955.50 | 01-APR-07:10 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 27961.67 | 14-APR-07:00 |
May | 3955.50 | 01-MAY-07:10 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 753.68 | 31-MAY-16:00 | 17159.65 | 18-MAY-16:55 |
June | 3955.50 | 01-JUN-07:10 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6987.80 | 06-JUN-16:40 | 11602.85 | 20-JUN-17:00 |
July | 3955.50 | 01-JUL-07:10 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6835.42 | 15-JUL-15:10 | 8225.43 | 03-JUL-03:00 |
August | 3955.50 | 01-AUG-07:10 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7256.86 | 02-AUG-16:00 | 10958.02 | 29-AUG-16:00 |
September | 3955.50 | 01-SEP-07:10 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3627.37 | 09-SEP-15:10 | 23181.54 | 21-SEP-15:02 |
October | 3955.50 | 02-OCT-07:10 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.53 | 11-OCT-14:00 | 24710.41 | 03-OCT-15:02 |
November | 3955.50 | 01-NOV-07:10 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 24084.08 | 01-NOV-07:00 |
December | 3955.50 | 01-DEC-08:09 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 38063.15 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8225.43 | ||||
Maximum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7256.86 | 38888.90 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 26389.90 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5416.65 | 19-JAN-14:00 | 42225.22 | 07-JAN-12:00 |
February | 9097.65 | 01-FEB-08:09 | 26389.90 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6641.57 | 26-FEB-16:00 | 73689.31 | 11-FEB-15:00 |
March | 9097.65 | 01-MAR-08:09 | 26389.90 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5418.61 | 31-MAR-14:00 | 107989.46 | 19-MAR-06:51 |
April | 9097.65 | 01-APR-07:10 | 26389.90 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10614.48 | 07-APR-16:00 | 67250.47 | 14-APR-07:10 |
May | 9097.65 | 01-MAY-07:10 | 26389.90 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9002.60 | 04-MAY-15:00 | 64658.03 | 26-MAY-10:55 |
June | 9097.65 | 01-JUN-07:10 | 26389.90 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5145.25 | 04-JUN-14:53 | 37026.23 | 20-JUN-17:00 |
July | 9097.65 | 01-JUL-07:10 | 26389.90 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2965.98 | 16-JUL-12:02 | 33615.70 | 05-JUL-16:00 |
August | 9097.65 | 01-AUG-07:10 | 26389.90 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2087.90 | 02-AUG-12:55 | 39682.24 | 29-AUG-16:00 |
September | 9097.65 | 01-SEP-07:10 | 26389.90 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6901.06 | 26-SEP-12:10 | 72052.59 | 21-SEP-14:50 |
October | 9097.65 | 02-OCT-07:10 | 26389.90 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2968.11 | 11-OCT-14:00 | 64280.13 | 03-OCT-14:55 |
November | 9097.65 | 01-NOV-07:10 | 26389.90 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6779.64 | 07-NOV-14:00 | 60514.07 | 01-NOV-10:00 |
December | 9097.65 | 01-DEC-08:09 | 26389.90 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19300.62 | 02-DEC-12:00 | 94628.18 | 21-DEC-18:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 2087.90 | 33615.70 | |||||
Maximum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 19300.62 | 107989.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2113.57 | 20-JAN-15:50 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.85 |
February | 1929.16 | 18-FEB-14:50 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.43 |
March | 8445.76 | 13-MAR-17:12 | 0.00 | 1828.09 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.76 |
April | 5656.22 | 20-APR-17:20 | 0.00 | 1371.07 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 644.28 |
May | 15434.43 | 31-MAY-17:08 | 0.00 | 1828.09 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.77 | 0.00 |
June | 21780.14 | 25-JUN-23:01 | 0.00 | 4570.22 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432.35 |
July | 21865.79 | 16-JUL-23:01 | 0.00 | 4570.22 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.66 |
August | 22438.31 | 06-AUG-23:01 | 0.00 | 4113.20 | 5163.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.30 |
September | 21634.77 | 04-SEP-23:01 | 0.00 | 3199.16 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 542.67 |
October | 7887.64 | 10-OCT-17:13 | 0.00 | 1371.07 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.91 |
November | 3859.65 | 07-NOV-15:30 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.45 |
December | 2177.70 | 02-DEC-15:30 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1929.16 | 0.00 | 1371.07 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22438.31 | 1680.92 | 4570.22 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 362.77 | 644.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2656.42 | 05-JAN-15:00 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 707.06 | 11-FEB-13:20 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8405.09 |
March | 6578.65 | 15-MAR-14:20 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1071.75 |
April | 1823.44 | 21-APR-13:30 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2838.83 |
May | 15840.50 | 18-MAY-14:30 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 803.72 |
June | 62617.28 | 15-JUN-17:05 | 0.00 | 12598.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4228.54 | 0.00 |
July | 66042.43 | 23-JUL-11:13 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 594.99 | 0.00 |
August | 67607.59 | 06-AUG-13:23 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 578.96 | 0.00 |
September | 61968.07 | 10-SEP-12:43 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1581.93 | 0.00 |
October | 13877.99 | 11-OCT-14:20 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.37 |
November | 1505.69 | 29-NOV-11:00 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1463.43 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6418.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 67607.59 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4228.54 | 8405.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 9314.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3545.60 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 12418.78 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11952.03 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 9314.08 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10921.86 |
April | 0.00 | 01-APR-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5466.49 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7904.83 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6044.54 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12254.03 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14383.94 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8049.73 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13380.41 |
November | 0.00 | 01-NOV-00:03 | 0.00 | 9314.08 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36523.87 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 12418.78 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12136.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3545.60 | |
Maximum of Months | 0.00 | 0.00 | 12418.78 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36523.87 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.911732E+11 | 71577.04 | 07-JAN-16:49 | 0.961180E+11 | 184251.30 | 05-JAN-06:10 |
February | 0.830154E+11 | 68801.87 | 18-FEB-15:09 | 0.124270E+12 | 241221.70 | 12-FEB-06:10 |
March | 0.935815E+11 | 73180.00 | 15-MAR-14:30 | 0.732786E+11 | 305738.43 | 19-MAR-07:10 |
April | 0.861079E+11 | 70802.44 | 20-APR-12:00 | 0.480002E+11 | 168256.40 | 17-APR-05:10 |
May | 0.891757E+11 | 77870.69 | 31-MAY-14:00 | 0.144392E+11 | 52763.79 | 02-MAY-05:49 |
June | 0.993895E+11 | 94618.84 | 26-JUN-14:00 | 0.123120E+11 | 4750.00 | 01-JUN-00:10 |
July | 0.985923E+11 | 90694.55 | 15-JUL-14:39 | 0.127224E+11 | 4750.00 | 01-JUL-00:10 |
August | 0.103346E+12 | 92185.21 | 16-AUG-13:00 | 0.127224E+11 | 4750.00 | 01-AUG-00:10 |
September | 0.930465E+11 | 86497.78 | 09-SEP-12:00 | 0.124020E+11 | 15795.17 | 22-SEP-06:10 |
October | 0.890479E+11 | 76949.05 | 11-OCT-13:00 | 0.364754E+11 | 156362.70 | 31-OCT-23:49 |
November | 0.868402E+11 | 71812.37 | 06-NOV-16:00 | 0.638685E+11 | 251251.25 | 30-NOV-06:10 |
December | 0.926006E+11 | 71575.08 | 23-DEC-16:49 | 0.188998E+12 | 337132.75 | 21-DEC-17:00 |
Annual Sum or Average | 0.110592E+13 | 0.695607E+12 | ||||
Minimum of Months | 0.830154E+11 | 68801.87 | 0.123120E+11 | 4750.00 | ||
Maximum of Months | 0.103346E+12 | 94618.84 | 0.188998E+12 | 337132.75 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.518856E+11 | 0.137659E+11 | 0.115358E+11 | 0.00 | 0.116227E+11 | 0.00 | 0.00 | 13375180.97 | 0.00 | 0.00 | 0.00 | 0.234980E+10 | 0.00 |
February | 0.474804E+11 | 0.115902E+11 | 0.105871E+11 | 0.00 | 0.111982E+11 | 0.00 | 0.00 | 11954461.97 | 0.00 | 0.00 | 0.00 | 0.214757E+10 | 0.00 |
March | 0.548234E+11 | 0.116414E+11 | 0.123431E+11 | 0.00 | 0.120978E+11 | 0.00 | 0.00 | 0.265364E+09 | 0.00 | 0.00 | 0.00 | 0.241053E+10 | 0.00 |
April | 0.513965E+11 | 0.100595E+11 | 0.114862E+11 | 0.00 | 0.107623E+11 | 0.00 | 0.00 | 0.143419E+09 | 0.00 | 0.00 | 0.00 | 0.225998E+10 | 0.00 |
May | 0.533545E+11 | 0.934790E+10 | 0.119357E+11 | 0.00 | 0.102256E+11 | 0.00 | 0.00 | 0.203205E+10 | 0.00 | 0.00 | 0.00 | 0.227997E+10 | 0.00 |
June | 0.528654E+11 | 0.849297E+10 | 0.118862E+11 | 0.00 | 0.118796E+11 | 0.00 | 0.00 | 0.120917E+11 | 0.00 | 0.00 | 0.00 | 0.217368E+10 | 0.00 |
July | 0.518856E+11 | 0.902538E+10 | 0.115358E+11 | 0.00 | 0.119086E+11 | 0.00 | 0.00 | 0.120793E+11 | 0.00 | 0.00 | 0.00 | 0.215755E+10 | 0.00 |
August | 0.548234E+11 | 0.993150E+10 | 0.123357E+11 | 0.00 | 0.122114E+11 | 0.00 | 0.00 | 0.118439E+11 | 0.00 | 0.00 | 0.00 | 0.219988E+10 | 0.00 |
September | 0.513965E+11 | 0.107404E+11 | 0.114788E+11 | 0.00 | 0.103605E+11 | 0.00 | 0.00 | 0.695558E+10 | 0.00 | 0.00 | 0.00 | 0.211470E+10 | 0.00 |
October | 0.518856E+11 | 0.123427E+11 | 0.115432E+11 | 0.00 | 0.102941E+11 | 0.00 | 0.00 | 0.773315E+09 | 0.00 | 0.00 | 0.00 | 0.220901E+10 | 0.00 |
November | 0.499276E+11 | 0.130082E+11 | 0.110862E+11 | 0.00 | 0.105527E+11 | 0.00 | 0.00 | 79762192.05 | 0.00 | 0.00 | 0.00 | 0.218569E+10 | 0.00 |
December | 0.518856E+11 | 0.140628E+11 | 0.115358E+11 | 0.00 | 0.127809E+11 | 0.00 | 0.00 | 19621777.93 | 0.00 | 0.00 | 0.00 | 0.231587E+10 | 0.00 |
Annual Sum or Average | 0.623610E+12 | 0.134009E+12 | 0.139290E+12 | 0.00 | 0.135894E+12 | 0.00 | 0.00 | 0.463094E+11 | 0.00 | 0.00 | 0.00 | 0.268042E+11 | 0.00 |
Minimum of Months | 0.474804E+11 | 0.849297E+10 | 0.105871E+11 | 0.00 | 0.102256E+11 | 0.00 | 0.00 | 11954461.97 | 0.00 | 0.00 | 0.00 | 0.211470E+10 | 0.00 |
Maximum of Months | 0.548234E+11 | 0.140628E+11 | 0.123431E+11 | 0.00 | 0.127809E+11 | 0.00 | 0.00 | 0.120917E+11 | 0.00 | 0.00 | 0.00 | 0.241053E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.961180E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.124270E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.732786E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.480002E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.144392E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.123120E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.127224E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.127224E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.124020E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.364754E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.638685E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.188998E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.695607E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.123120E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.188998E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 46193.18 | 02-JAN-09:09 | 8532.22 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 10317.99 | 02-JAN-07:49 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 46193.18 | 01-FEB-09:09 | 8532.22 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 10317.99 | 01-FEB-08:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 46193.18 | 01-MAR-09:09 | 8532.22 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 10317.99 | 01-MAR-07:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 46193.18 | 01-APR-08:09 | 8532.22 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 10317.99 | 03-APR-06:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 46193.18 | 01-MAY-08:09 | 8532.22 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 9860.28 | 01-MAY-06:19 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 46193.18 | 01-JUN-08:09 | 8532.22 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 12165.57 | 06-JUN-10:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 46193.18 | 01-JUL-08:09 | 8532.22 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 12165.57 | 07-JUL-09:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 46193.18 | 01-AUG-08:09 | 8532.22 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 12165.57 | 04-AUG-10:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 46193.18 | 01-SEP-08:09 | 8532.22 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 12165.57 | 12-SEP-15:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 46193.18 | 02-OCT-08:09 | 8532.22 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 10317.99 | 25-OCT-06:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 46193.18 | 01-NOV-08:09 | 8532.22 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 10317.99 | 01-NOV-07:19 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 46193.18 | 01-DEC-09:09 | 8532.22 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 10317.99 | 05-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 46193.18 | 8532.22 | 10112.62 | 0.00 | 9860.28 | 0.00 | 0.00 | |||||
Maximum of Months | 46193.18 | 8532.22 | 10112.62 | 0.00 | 12165.57 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 863.24 | 20-JAN-15:30 | 0.00 | 0.00 | 0.00 | 2653.41 | 31-JAN-12:50 | 0.00 |
February | 828.18 | 18-FEB-14:50 | 0.00 | 0.00 | 0.00 | 2664.10 | 15-FEB-12:50 | 0.00 |
March | 5183.52 | 15-MAR-14:30 | 0.00 | 0.00 | 0.00 | 2646.10 | 02-MAR-12:09 | 0.00 |
April | 2845.27 | 20-APR-13:30 | 0.00 | 0.00 | 0.00 | 2523.53 | 03-APR-11:20 | 0.00 |
May | 9919.64 | 31-MAY-14:00 | 0.00 | 0.00 | 0.00 | 2330.06 | 01-MAY-11:50 | 0.00 |
June | 25294.28 | 26-JUN-15:09 | 0.00 | 0.00 | 0.00 | 2010.86 | 05-JUN-11:00 | 0.00 |
July | 21463.42 | 15-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1805.13 | 03-JUL-11:39 | 0.00 |
August | 22000.19 | 16-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1794.95 | 30-AUG-11:20 | 0.00 |
September | 16265.70 | 09-SEP-12:00 | 0.00 | 0.00 | 0.00 | 1811.45 | 30-SEP-11:00 | 0.00 |
October | 9046.58 | 11-OCT-13:00 | 0.00 | 0.00 | 0.00 | 2078.37 | 30-OCT-11:39 | 0.00 |
November | 2305.28 | 09-NOV-13:09 | 0.00 | 0.00 | 0.00 | 2320.39 | 27-NOV-12:09 | 0.00 |
December | 943.87 | 02-DEC-14:00 | 0.00 | 0.00 | 0.00 | 2537.06 | 30-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 828.18 | 0.00 | 0.00 | 0.00 | 1794.95 | 0.00 | ||
Maximum of Months | 25294.28 | 0.00 | 0.00 | 0.00 | 2664.10 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 71577.04 | 07-JAN-16:49 | 40988.70 | 10112.62 | 8532.22 | 0.00 | 10317.99 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 68801.87 | 18-FEB-15:09 | 46193.18 | 10112.62 | 0.00 | 0.00 | 9860.28 | 0.00 | 0.00 | 800.40 | 0.00 |
March | 73180.00 | 15-MAR-14:30 | 46193.18 | 10112.62 | 0.00 | 0.00 | 9860.28 | 0.00 | 0.00 | 5183.52 | 0.00 |
April | 70802.44 | 20-APR-12:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 9860.28 | 0.00 | 0.00 | 2823.69 | 0.00 |
May | 77870.69 | 31-MAY-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 9860.28 | 0.00 | 0.00 | 9919.64 | 0.00 |
June | 94618.84 | 26-JUN-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 12165.57 | 0.00 | 0.00 | 24377.35 | 0.00 |
July | 90694.55 | 15-JUL-14:39 | 46193.18 | 10112.62 | 0.00 | 0.00 | 12165.57 | 0.00 | 0.00 | 20461.28 | 0.00 |
August | 92185.21 | 16-AUG-13:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 12165.57 | 0.00 | 0.00 | 21990.78 | 0.00 |
September | 86497.78 | 09-SEP-12:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 12165.57 | 0.00 | 0.00 | 16265.70 | 0.00 |
October | 76949.05 | 11-OCT-13:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 9860.28 | 0.00 | 0.00 | 9046.58 | 0.00 |
November | 71812.37 | 06-NOV-16:00 | 40988.70 | 10112.62 | 8532.22 | 0.00 | 9860.28 | 0.00 | 0.00 | 704.39 | 0.00 |
December | 71575.08 | 23-DEC-16:49 | 40988.70 | 10112.62 | 8532.22 | 0.00 | 10317.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 68801.87 | 40988.70 | 10112.62 | 0.00 | 0.00 | 9860.28 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 94618.84 | 46193.18 | 10112.62 | 8532.22 | 0.00 | 12165.57 | 0.00 | 0.00 | 24377.35 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 184251.30 | 05-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 241221.70 | 12-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 305738.43 | 19-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 168256.40 | 17-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 52763.79 | 02-MAY-05:49 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 4750.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 4750.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 4750.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 15795.17 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 156362.70 | 31-OCT-23:49 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 251251.25 | 30-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 337132.75 | 21-DEC-17:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 4750.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 337132.75 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 23.00 | 16.53 | 8.50 | 17.27 | 0.00 | 17.27 | 0.00 | 17.27 |
February | 33.83 | 15.83 | 8.33 | 16.49 | 0.00 | 16.49 | 0.00 | 16.49 |
March | 20.83 | 16.50 | 8.17 | 17.29 | 0.00 | 17.29 | 0.00 | 17.29 |
April | 19.00 | 16.54 | 7.17 | 17.28 | 0.00 | 17.28 | 0.00 | 17.28 |
May | 2.67 | 18.77 | 2.17 | 19.16 | 0.83 | 19.95 | 0.00 | 19.95 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 28.50 | 24.82 | 0.50 | 24.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 24.76 | 0.50 | 24.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 33.17 | 24.71 | 0.67 | 24.71 |
September | 0.33 | 20.43 | 0.33 | 20.43 | 14.67 | 24.44 | 0.50 | 24.44 |
October | 10.17 | 16.83 | 4.33 | 17.59 | 0.17 | 17.66 | 0.00 | 17.66 |
November | 14.50 | 17.14 | 7.67 | 17.85 | 0.00 | 17.85 | 0.00 | 17.85 |
December | 42.33 | 15.55 | 10.00 | 16.19 | 0.00 | 16.19 | 0.00 | 16.19 |
Annual Sum or Average | 166.67 | 16.25 | 56.67 | 17.00 | 103.50 | 19.45 | 2.17 | 19.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.19 | 0.00 | 16.19 |
Maximum of Months | 42.33 | 20.43 | 10.00 | 20.43 | 33.17 | 24.82 | 0.67 | 24.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 71.67 | 14.26 | 4.50 | 14.26 | 0.00 | 14.26 | 0.00 | 14.26 |
February | 77.33 | 14.04 | 4.83 | 14.04 | 0.00 | 14.04 | 0.00 | 14.04 |
March | 59.00 | 14.23 | 3.67 | 14.23 | 0.00 | 14.23 | 0.00 | 14.23 |
April | 44.00 | 14.35 | 2.83 | 14.34 | 0.00 | 14.34 | 0.00 | 14.34 |
May | 4.83 | 14.76 | 0.67 | 14.75 | 0.00 | 14.75 | 0.00 | 14.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.66 | 0.00 | 27.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 27.66 | 0.00 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.58 | 0.00 | 27.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.54 | 0.00 | 27.54 |
October | 21.33 | 14.22 | 1.83 | 14.23 | 0.00 | 14.23 | 0.00 | 14.23 |
November | 47.83 | 14.32 | 3.50 | 14.32 | 0.00 | 14.32 | 0.00 | 14.32 |
December | 92.17 | 13.88 | 5.83 | 13.89 | 0.00 | 13.89 | 0.00 | 13.89 |
Annual Sum or Average | 418.17 | 14.15 | 27.67 | 14.15 | 48.00 | 15.46 | 0.00 | 15.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.89 | 0.00 | 13.89 |
Maximum of Months | 92.17 | 14.76 | 5.83 | 14.75 | 18.00 | 27.66 | 0.00 | 27.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.67 | 9.02 | 0.00 | 9.02 | 0.00 | 9.02 | 0.00 | 9.02 |
Annual Sum or Average | 3.67 | 9.02 | 0.00 | 9.02 | 0.00 | 9.02 | 0.00 | 9.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.67 | 9.02 | 0.00 | 9.02 | 0.00 | 9.02 | 0.00 | 9.02 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.49 | 242.33 | 21.31 | 242.33 | 21.24 |
February | 276.00 | 21.31 | 244.83 | 21.20 | 244.83 | 21.16 |
March | 324.00 | 21.82 | 224.67 | 21.52 | 224.67 | 21.40 |
April | 300.00 | 22.01 | 177.33 | 21.67 | 177.33 | 21.51 |
May | 248.50 | 22.98 | 47.83 | 22.74 | 42.33 | 22.54 |
June | 26.00 | 23.73 | 213.67 | 23.89 | 0.00 | 23.89 |
July | 19.33 | 23.88 | 235.50 | 23.90 | 6.83 | 23.90 |
August | 21.50 | 23.80 | 238.17 | 23.90 | 1.00 | 23.90 |
September | 93.17 | 23.35 | 106.17 | 23.58 | 4.67 | 23.52 |
October | 282.83 | 22.47 | 107.83 | 22.09 | 107.83 | 21.87 |
November | 288.00 | 21.82 | 187.33 | 21.53 | 187.33 | 21.40 |
December | 300.00 | 21.36 | 260.50 | 21.22 | 260.50 | 21.17 |
Annual Sum or Average | 2479.33 | 21.99 | 2286.17 | 22.03 | 1499.67 | 21.80 |
Minimum of Months | 19.33 | 21.31 | 47.83 | 21.20 | 0.00 | 21.16 |
Maximum of Months | 324.00 | 23.88 | 260.50 | 23.90 | 260.50 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 18.70 | 250.33 | 18.29 | 250.33 | 18.14 |
February | 276.00 | 18.24 | 243.00 | 17.93 | 243.00 | 17.82 |
March | 287.50 | 18.99 | 249.33 | 18.79 | 224.83 | 18.47 |
April | 265.83 | 19.87 | 191.50 | 19.40 | 177.17 | 19.04 |
May | 119.50 | 21.45 | 225.83 | 23.72 | 50.50 | 23.14 |
June | 210.83 | 26.53 | 294.33 | 26.57 | 201.17 | 26.60 |
July | 228.17 | 26.62 | 289.33 | 26.60 | 224.50 | 26.62 |
August | 227.83 | 26.57 | 309.83 | 26.57 | 219.83 | 26.60 |
September | 128.33 | 25.24 | 248.33 | 26.00 | 92.33 | 26.00 |
October | 201.67 | 19.86 | 203.00 | 20.50 | 125.83 | 19.86 |
November | 272.50 | 19.22 | 210.67 | 18.73 | 203.83 | 18.46 |
December | 300.00 | 17.89 | 274.67 | 17.65 | 274.67 | 17.57 |
Annual Sum or Average | 2818.17 | 21.12 | 2990.17 | 21.57 | 2288.00 | 21.30 |
Minimum of Months | 119.50 | 17.89 | 191.50 | 17.65 | 50.50 | 17.57 |
Maximum of Months | 300.00 | 26.62 | 309.83 | 26.60 | 274.67 | 26.62 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 12.27 | 300.00 | 12.27 | 300.00 | 12.27 |
February | 276.00 | 11.86 | 276.00 | 11.86 | 276.00 | 11.86 |
March | 324.00 | 13.66 | 320.33 | 13.61 | 320.33 | 13.60 |
April | 300.00 | 14.47 | 300.00 | 14.47 | 300.00 | 14.47 |
May | 274.17 | 20.30 | 143.83 | 19.71 | 126.50 | 19.21 |
June | 249.67 | 29.78 | 293.17 | 29.57 | 238.00 | 29.74 |
July | 278.83 | 29.88 | 300.00 | 29.74 | 278.83 | 29.79 |
August | 273.17 | 29.78 | 324.00 | 29.46 | 273.17 | 29.56 |
September | 190.00 | 26.87 | 223.83 | 27.23 | 140.67 | 27.47 |
October | 297.50 | 17.74 | 221.17 | 17.04 | 221.17 | 16.75 |
November | 288.00 | 13.12 | 288.00 | 13.12 | 288.00 | 13.12 |
December | 300.00 | 11.46 | 300.00 | 11.46 | 300.00 | 11.46 |
Annual Sum or Average | 3351.33 | 18.74 | 3290.33 | 18.82 | 3062.67 | 18.68 |
Minimum of Months | 190.00 | 11.46 | 143.83 | 11.46 | 126.50 | 11.46 |
Maximum of Months | 324.00 | 29.88 | 324.00 | 29.74 | 320.33 | 29.79 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 48812383.13 | 13375180.97 | 6.92 | 48812383.13 | 0.00 | 0.00 | 0.16 | 20-JAN-15:30 | 0.00 | 01-JAN-00:03 | 3173.33 | 20-JAN-15:30 | 3173.33 | 20-JAN-15:30 | 0.00 | 19-JAN-16:00 | 863.24 | 20-JAN-15:30 | 0.00 | 01-JAN-00:03 |
February | 43658053.76 | 11954461.97 | 6.50 | 43658053.76 | -0.0 | 0.00 | 0.15 | 18-FEB-14:50 | 0.00 | 01-FEB-00:03 | 3041.47 | 18-FEB-14:50 | 3041.47 | 18-FEB-14:50 | 0.00 | 18-FEB-13:40 | 828.18 | 18-FEB-14:50 | 0.00 | 01-FEB-00:03 |
March | 0.462136E+09 | 0.125090E+09 | 42.01 | 0.462136E+09 | -0.0 | 0.00 | 0.44 | 13-MAR-17:12 | 0.00 | 01-MAR-00:03 | 9383.40 | 13-MAR-17:12 | 9383.40 | 13-MAR-17:12 | 0.00 | 31-MAR-15:30 | 2440.54 | 13-MAR-17:12 | 0.00 | 01-MAR-00:03 |
April | 0.435611E+09 | 0.118609E+09 | 45.56 | 0.435611E+09 | -0.0 | 0.00 | 0.31 | 20-APR-17:20 | 0.00 | 01-APR-00:10 | 6382.48 | 20-APR-17:20 | 6382.48 | 20-APR-17:20 | 0.00 | 27-APR-15:40 | 1696.18 | 20-APR-17:20 | 0.00 | 01-APR-00:10 |
May | 0.247312E+10 | 0.672626E+09 | 138.81 | 0.245435E+10 | 18771616.96 | 0.00 | 0.77 | 31-MAY-17:08 | 0.00 | 01-MAY-00:10 | 17516.85 | 31-MAY-17:08 | 17516.85 | 31-MAY-17:08 | 515.30 | 31-MAY-09:00 | 4575.14 | 31-MAY-17:08 | 0.00 | 01-MAY-00:10 |
June | 0.105940E+11 | 0.302068E+10 | 407.48 | 0.101840E+11 | 0.410017E+09 | 0.00 | 1.00 | 04-JUN-23:02 | 0.00 | 01-JUN-00:10 | 25631.80 | 18-JUN-23:02 | 24618.75 | 11-JUN-23:02 | 3150.69 | 21-JUN-17:10 | 6670.92 | 26-JUN-17:42 | 0.00 | 01-JUN-00:10 |
July | 0.106452E+11 | 0.300801E+10 | 414.53 | 0.100615E+11 | 0.583653E+09 | 0.00 | 1.00 | 01-JUL-17:05 | 0.00 | 01-JUL-00:15 | 28546.49 | 30-JUL-23:02 | 24624.58 | 16-JUL-23:01 | 10033.70 | 30-JUL-23:02 | 6624.67 | 30-JUL-23:02 | 0.00 | 01-JUL-00:10 |
August | 0.108276E+11 | 0.305200E+10 | 432.07 | 0.103862E+11 | 0.441410E+09 | 0.00 | 1.00 | 02-AUG-17:06 | 0.00 | 01-AUG-00:10 | 26336.03 | 27-AUG-23:02 | 25347.14 | 06-AUG-23:01 | 4066.73 | 21-AUG-18:23 | 6490.58 | 16-AUG-17:04 | 0.00 | 01-AUG-00:10 |
September | 0.692184E+10 | 0.190513E+10 | 300.75 | 0.685901E+10 | 62823667.11 | 0.00 | 1.00 | 02-SEP-17:06 | 0.00 | 01-SEP-00:15 | 24810.24 | 04-SEP-23:01 | 24810.24 | 04-SEP-23:01 | 1184.34 | 01-SEP-09:00 | 5993.54 | 12-SEP-17:05 | 0.00 | 01-SEP-00:10 |
October | 0.114202E+10 | 0.308047E+09 | 74.12 | 0.114202E+10 | 0.00 | 0.00 | 0.42 | 11-OCT-15:10 | 0.00 | 01-OCT-00:10 | 8805.10 | 10-OCT-17:13 | 8805.10 | 10-OCT-17:13 | 0.00 | 11-OCT-14:00 | 2366.71 | 11-OCT-15:10 | 0.00 | 01-OCT-00:10 |
November | 0.252103E+09 | 68342793.84 | 21.92 | 0.252103E+09 | -0.0 | 0.00 | 0.25 | 07-NOV-15:30 | 0.00 | 01-NOV-00:03 | 5249.91 | 07-NOV-15:30 | 5249.91 | 07-NOV-15:30 | 0.00 | 07-NOV-15:20 | 1406.54 | 07-NOV-15:30 | 0.00 | 01-NOV-00:03 |
December | 71699890.40 | 19621777.93 | 9.17 | 71699890.40 | 0.00 | 0.00 | 0.17 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 | 3477.54 | 02-DEC-15:00 | 3477.54 | 02-DEC-15:00 | 0.00 | 02-DEC-15:30 | 943.87 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.439178E+11 | 0.123235E+11 | 1899.83 | 0.424011E+11 | 0.151668E+10 | 0.00 | ||||||||||||||
Minimum of Months | 43658053.76 | 11954461.97 | 6.50 | 43658053.76 | -0.0 | 0.00 | 0.15 | 0.00 | 3041.47 | 3041.47 | 0.00 | 828.18 | 0.00 | |||||||
Maximum of Months | 0.108276E+11 | 0.305200E+10 | 432.07 | 0.103862E+11 | 0.583653E+09 | 0.00 | 1.00 | 0.00 | 28546.49 | 25347.14 | 10033.70 | 6670.92 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.473763E+09 | 0.140273E+09 | 22.83 | 0.473763E+09 | -0.0 | 0.00 | 0.19 | 15-MAR-14:10 | 0.00 | 01-MAR-00:03 | 12702.68 | 15-MAR-14:10 | 12702.68 | 15-MAR-14:10 | 0.00 | 15-MAR-12:20 | 3718.80 | 15-MAR-14:10 | 0.00 | 01-MAR-00:03 |
April | 83150635.37 | 24809527.42 | 6.17 | 83150635.37 | -0.0 | 0.00 | 0.09 | 21-APR-13:30 | 0.00 | 01-APR-00:10 | 6089.93 | 21-APR-13:30 | 6089.93 | 21-APR-13:30 | 0.00 | 21-APR-13:00 | 1810.71 | 21-APR-13:30 | 0.00 | 01-APR-00:10 |
May | 0.454613E+10 | 0.135942E+10 | 116.83 | 0.454050E+10 | 5633960.45 | 0.00 | 0.35 | 17-MAY-13:40 | 0.00 | 01-MAY-00:10 | 24132.64 | 31-MAY-14:50 | 24132.64 | 31-MAY-14:50 | 334.60 | 30-MAY-15:00 | 7439.04 | 31-MAY-14:50 | 0.00 | 01-MAY-00:10 |
June | 0.289827E+11 | 0.907101E+10 | 308.51 | 0.284080E+11 | 0.574680E+09 | 0.00 | 1.00 | 14-JUN-17:05 | 0.00 | 01-JUN-00:10 | 73115.79 | 15-JUN-17:05 | 73115.79 | 15-JUN-17:05 | 9176.06 | 18-JUN-10:43 | 23969.57 | 26-JUN-17:42 | 0.00 | 01-JUN-00:10 |
July | 0.291579E+11 | 0.907133E+10 | 309.92 | 0.283888E+11 | 0.769096E+09 | 0.00 | 1.00 | 01-JUL-17:05 | 0.00 | 01-JUL-00:10 | 77091.85 | 23-JUL-11:13 | 77091.85 | 23-JUL-11:13 | 9428.37 | 30-JUL-13:33 | 23604.41 | 23-JUL-13:52 | 0.00 | 01-JUL-00:10 |
August | 0.284768E+11 | 0.879189E+10 | 301.25 | 0.279445E+11 | 0.532322E+09 | 0.00 | 1.00 | 06-AUG-11:23 | 0.00 | 01-AUG-00:10 | 78830.40 | 06-AUG-13:23 | 78830.40 | 06-AUG-13:23 | 6065.95 | 05-AUG-15:50 | 23267.73 | 16-AUG-17:04 | 0.00 | 01-AUG-00:10 |
September | 0.166547E+11 | 0.505045E+10 | 217.37 | 0.166118E+11 | 42934957.33 | 0.00 | 1.00 | 10-SEP-12:43 | 0.00 | 01-SEP-00:10 | 72476.08 | 10-SEP-12:43 | 72476.08 | 10-SEP-12:43 | 1877.38 | 01-SEP-14:20 | 22233.89 | 10-SEP-12:43 | 0.00 | 01-SEP-00:10 |
October | 0.156861E+10 | 0.465269E+09 | 55.33 | 0.156861E+10 | -0.0 | 0.00 | 0.34 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 | 22096.96 | 11-OCT-14:10 | 22096.96 | 11-OCT-14:10 | 0.00 | 11-OCT-13:40 | 6751.01 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 38083925.77 | 11419398.22 | 4.83 | 38083925.77 | 0.00 | 0.00 | 0.06 | 09-NOV-13:10 | 0.00 | 01-NOV-00:03 | 3752.88 | 09-NOV-13:10 | 3752.88 | 09-NOV-13:10 | 0.00 | 08-NOV-14:50 | 1122.89 | 09-NOV-13:10 | 0.00 | 01-NOV-00:03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.109982E+12 | 0.339859E+11 | 1343.05 | 0.108057E+12 | 0.192467E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.291579E+11 | 0.907133E+10 | 309.92 | 0.284080E+11 | 0.769096E+09 | 0.00 | 1.00 | 0.00 | 78830.40 | 78830.40 | 9428.37 | 23969.57 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.91 | 96.85 | 56.06 | 143.29 | 179.23 | 0.00 | 0.00 | 0.00 |
February | 185.66 | 115.38 | 70.28 | 172.11 | 182.33 | 0.00 | 0.00 | 0.00 |
March | 216.41 | 119.49 | 96.92 | 212.11 | 138.01 | 0.00 | 0.00 | 0.00 |
April | 202.83 | 85.55 | 117.28 | 190.98 | 119.20 | 0.00 | 0.00 | 0.00 |
May | 248.67 | 87.62 | 161.04 | 269.79 | 79.89 | 0.00 | 0.00 | 0.00 |
June | 304.51 | 146.66 | 157.85 | 386.00 | 53.99 | 0.00 | 0.00 | 0.00 |
July | 247.68 | 90.59 | 157.09 | 313.58 | 50.17 | 0.00 | 0.00 | 0.00 |
August | 259.20 | 128.25 | 130.96 | 322.95 | 57.18 | 0.00 | 0.00 | 0.00 |
September | 230.13 | 110.61 | 119.52 | 273.69 | 84.86 | 0.00 | 0.00 | 0.00 |
October | 192.43 | 109.79 | 82.64 | 196.62 | 152.21 | 0.00 | 0.00 | 0.00 |
November | 158.14 | 95.92 | 62.22 | 150.80 | 167.21 | 0.00 | 0.00 | 0.00 |
December | 127.87 | 75.52 | 52.35 | 108.88 | 207.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 210.60 | 105.05 | 105.54 | 228.62 | 122.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.87 | 75.52 | 52.35 | 108.88 | 50.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 304.51 | 146.66 | 161.04 | 386.00 | 207.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.91 | 96.85 | 56.06 | 143.29 | 179.23 | 0.00 | 0.00 | 0.00 |
February | 185.66 | 115.38 | 70.28 | 172.11 | 182.33 | 0.00 | 0.00 | 0.00 |
March | 216.41 | 119.49 | 96.92 | 212.11 | 138.01 | 0.00 | 0.00 | 0.00 |
April | 202.83 | 85.55 | 117.28 | 190.98 | 119.20 | 0.00 | 0.00 | 0.00 |
May | 248.67 | 87.62 | 161.04 | 269.79 | 79.89 | 0.00 | 0.00 | 0.00 |
June | 304.51 | 146.66 | 157.85 | 386.00 | 53.99 | 0.00 | 0.00 | 0.00 |
July | 247.68 | 90.59 | 157.09 | 313.58 | 50.17 | 0.00 | 0.00 | 0.00 |
August | 259.20 | 128.25 | 130.96 | 322.95 | 57.18 | 0.00 | 0.00 | 0.00 |
September | 230.13 | 110.61 | 119.52 | 273.69 | 84.86 | 0.00 | 0.00 | 0.00 |
October | 192.43 | 109.79 | 82.64 | 196.62 | 152.21 | 0.00 | 0.00 | 0.00 |
November | 158.14 | 95.92 | 62.22 | 150.80 | 167.21 | 0.00 | 0.00 | 0.00 |
December | 127.87 | 75.52 | 52.35 | 108.88 | 207.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 210.60 | 105.05 | 105.54 | 228.62 | 122.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.87 | 75.52 | 52.35 | 108.88 | 50.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 304.51 | 146.66 | 161.04 | 386.00 | 207.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.81 | 0.00 | 26.81 | 6.04 | 111.34 | 0.00 | 0.00 | 0.00 |
February | 33.69 | 0.00 | 33.69 | 7.70 | 112.51 | 0.00 | 0.00 | 0.00 |
March | 45.87 | 0.01 | 45.86 | 21.87 | 84.07 | 0.00 | 0.00 | 0.00 |
April | 57.61 | 0.36 | 57.25 | 32.76 | 70.49 | 0.00 | 0.00 | 0.00 |
May | 78.73 | 2.64 | 76.09 | 68.35 | 44.19 | 0.00 | 0.00 | 0.00 |
June | 86.12 | 9.44 | 76.69 | 103.61 | 28.66 | 0.00 | 0.00 | 0.00 |
July | 81.74 | 5.42 | 76.32 | 99.61 | 27.33 | 0.00 | 0.00 | 0.00 |
August | 65.20 | 1.78 | 63.42 | 74.47 | 32.45 | 0.00 | 0.00 | 0.00 |
September | 54.58 | 0.04 | 54.55 | 54.32 | 49.45 | 0.00 | 0.00 | 0.00 |
October | 39.06 | 0.00 | 39.06 | 19.30 | 91.51 | 0.00 | 0.00 | 0.00 |
November | 29.65 | 0.00 | 29.65 | 9.02 | 102.23 | 0.00 | 0.00 | 0.00 |
December | 25.08 | 0.00 | 25.08 | 4.99 | 129.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.11 | 1.64 | 50.46 | 42.03 | 73.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.08 | 0.00 | 25.08 | 4.99 | 27.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 86.12 | 9.44 | 76.69 | 103.61 | 129.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.81 | 0.00 | 26.81 | 6.04 | 111.34 | 0.00 | 0.00 | 0.00 |
February | 33.69 | 0.00 | 33.69 | 7.70 | 112.51 | 0.00 | 0.00 | 0.00 |
March | 45.86 | 0.01 | 45.86 | 21.87 | 84.07 | 0.00 | 0.00 | 0.00 |
April | 57.60 | 0.36 | 57.25 | 32.76 | 70.49 | 0.00 | 0.00 | 0.00 |
May | 78.73 | 2.64 | 76.09 | 68.35 | 44.19 | 0.00 | 0.00 | 0.00 |
June | 86.12 | 9.44 | 76.69 | 103.61 | 28.66 | 0.00 | 0.00 | 0.00 |
July | 81.73 | 5.42 | 76.31 | 99.61 | 27.33 | 0.00 | 0.00 | 0.00 |
August | 65.20 | 1.78 | 63.41 | 74.47 | 32.45 | 0.00 | 0.00 | 0.00 |
September | 54.58 | 0.04 | 54.55 | 54.32 | 49.45 | 0.00 | 0.00 | 0.00 |
October | 39.06 | 0.00 | 39.06 | 19.29 | 91.51 | 0.00 | 0.00 | 0.00 |
November | 29.65 | 0.00 | 29.65 | 9.02 | 102.23 | 0.00 | 0.00 | 0.00 |
December | 25.08 | 0.00 | 25.08 | 4.99 | 129.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.11 | 1.64 | 50.46 | 42.03 | 73.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.08 | 0.00 | 25.08 | 4.99 | 27.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 86.12 | 9.44 | 76.69 | 103.61 | 129.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 54.57 | 100.77 | 6.67 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.01 | 103.77 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 114.33 | 76.96 | 12.00 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 123.40 | 63.36 | 13.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 165.15 | 52.27 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 213.18 | 57.11 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 181.77 | 58.36 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 181.71 | 62.79 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 138.71 | 75.38 | 1.67 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 91.38 | 94.11 | 11.67 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 67.19 | 88.70 | 9.67 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 41.68 | 122.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 121.42 | 79.59 | 60.83 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 41.68 | 52.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 213.18 | 122.72 | 13.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 54.57 | 100.77 | 6.67 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.01 | 103.77 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 114.33 | 76.96 | 12.00 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 123.40 | 63.36 | 13.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 165.15 | 52.27 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 213.18 | 57.11 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 181.77 | 58.36 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 181.71 | 62.79 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 138.71 | 75.38 | 1.67 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 91.38 | 94.11 | 11.67 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 67.19 | 88.70 | 9.67 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 41.68 | 122.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 121.42 | 79.59 | 60.83 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 41.68 | 52.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 213.18 | 122.72 | 13.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 54.57 | 100.77 | 6.67 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.01 | 103.77 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 114.33 | 76.96 | 12.00 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 123.40 | 63.36 | 13.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 165.15 | 52.27 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 213.18 | 57.11 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 181.77 | 58.36 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 181.71 | 62.79 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 138.71 | 75.38 | 1.67 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 91.38 | 94.11 | 11.67 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 67.19 | 88.70 | 9.67 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 41.68 | 122.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 121.42 | 79.59 | 60.83 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 41.68 | 52.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 213.18 | 122.72 | 13.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 54.57 | 100.77 | 6.67 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.01 | 103.77 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 114.33 | 76.96 | 12.00 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 123.40 | 63.36 | 13.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 165.15 | 52.27 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 213.18 | 57.11 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 181.77 | 58.36 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 181.71 | 62.79 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 138.71 | 75.38 | 1.67 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 91.38 | 94.11 | 11.67 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 67.19 | 88.70 | 9.67 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 41.68 | 122.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 121.42 | 79.59 | 60.83 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 41.68 | 52.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 213.18 | 122.72 | 13.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 54.57 | 100.77 | 6.67 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.01 | 103.77 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 114.33 | 76.96 | 12.00 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 123.40 | 63.36 | 13.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 165.15 | 52.27 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 213.18 | 57.11 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 181.77 | 58.36 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 181.71 | 62.79 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 138.71 | 75.38 | 1.67 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 91.38 | 94.11 | 11.67 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 67.19 | 88.70 | 9.67 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 41.68 | 122.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 121.42 | 79.59 | 60.83 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 41.68 | 52.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 213.18 | 122.72 | 13.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 54.57 | 100.77 | 6.67 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.01 | 103.77 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 114.33 | 76.96 | 12.00 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 123.40 | 63.36 | 13.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 165.15 | 52.27 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 213.18 | 57.11 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 181.77 | 58.36 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 181.71 | 62.79 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 138.71 | 75.38 | 1.67 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 91.38 | 94.11 | 11.67 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 67.19 | 88.70 | 9.67 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 41.68 | 122.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 121.42 | 79.59 | 60.83 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 41.68 | 52.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 213.18 | 122.72 | 13.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 54.57 | 100.77 | 6.67 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.01 | 103.77 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 114.33 | 76.96 | 12.00 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 123.40 | 63.36 | 13.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 165.15 | 52.27 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 213.18 | 57.11 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 181.77 | 58.36 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 181.71 | 62.79 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 138.71 | 75.38 | 1.67 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 91.38 | 94.11 | 11.67 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 67.19 | 88.70 | 9.67 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 41.68 | 122.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 121.42 | 79.59 | 60.83 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 41.68 | 52.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 213.18 | 122.72 | 13.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 54.57 | 100.77 | 6.67 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.01 | 103.77 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 114.33 | 76.96 | 12.00 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 123.40 | 63.36 | 13.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 165.15 | 52.27 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 213.18 | 57.11 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 181.77 | 58.36 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 181.71 | 62.79 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 138.71 | 75.38 | 1.67 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 91.38 | 94.11 | 11.67 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 67.19 | 88.70 | 9.67 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 41.68 | 122.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 121.42 | 79.59 | 60.83 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 41.68 | 52.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 213.18 | 122.72 | 13.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 54.57 | 100.77 | 6.67 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.01 | 103.77 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 114.33 | 76.96 | 12.00 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 123.40 | 63.36 | 13.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 165.15 | 52.27 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 213.18 | 57.11 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 181.77 | 58.36 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 181.71 | 62.79 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 138.71 | 75.38 | 1.67 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 91.38 | 94.11 | 11.67 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 67.19 | 88.70 | 9.67 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 41.68 | 122.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 121.42 | 79.59 | 60.83 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 41.68 | 52.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 213.18 | 122.72 | 13.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.33 | 35.21 | 14.12 | 54.57 | 100.77 | 6.67 | 0.00 | 0.00 |
February | 71.97 | 55.33 | 16.64 | 82.01 | 103.77 | 3.67 | 0.00 | 0.00 |
March | 93.20 | 65.26 | 27.94 | 114.33 | 76.96 | 12.00 | 0.00 | 0.00 |
April | 100.75 | 58.90 | 41.85 | 123.40 | 63.36 | 13.67 | 0.00 | 0.00 |
May | 128.63 | 68.49 | 60.14 | 165.15 | 52.27 | 0.00 | 0.00 | 0.00 |
June | 160.96 | 112.26 | 48.70 | 213.18 | 57.11 | 0.00 | 0.00 | 0.00 |
July | 139.54 | 83.02 | 56.52 | 181.77 | 58.36 | 0.00 | 0.00 | 0.00 |
August | 138.81 | 99.08 | 39.73 | 181.71 | 62.79 | 1.83 | 0.00 | 0.00 |
September | 109.04 | 72.99 | 36.04 | 138.71 | 75.38 | 1.67 | 0.00 | 0.00 |
October | 77.95 | 55.16 | 22.80 | 91.38 | 94.11 | 11.67 | 0.00 | 0.00 |
November | 56.59 | 40.89 | 15.70 | 67.19 | 88.70 | 9.67 | 0.00 | 0.00 |
December | 41.66 | 27.62 | 14.03 | 41.68 | 122.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97.47 | 64.52 | 32.95 | 121.42 | 79.59 | 60.83 | 0.00 | 0.00 |
Minimum of Months | 41.66 | 27.62 | 14.03 | 41.68 | 52.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.96 | 112.26 | 60.14 | 213.18 | 122.72 | 13.67 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.409563E+09 | 0.259400E+09 | 0.150163E+09 | 0.383778E+09 | 0.480048E+09 |
February | 0.449155E+09 | 0.279136E+09 | 0.170019E+09 | 0.416375E+09 | 0.441097E+09 |
March | 0.579644E+09 | 0.320047E+09 | 0.259597E+09 | 0.568128E+09 | 0.369633E+09 |
April | 0.525748E+09 | 0.221752E+09 | 0.303996E+09 | 0.495030E+09 | 0.308976E+09 |
May | 0.666033E+09 | 0.234692E+09 | 0.431341E+09 | 0.722598E+09 | 0.213971E+09 |
June | 0.789286E+09 | 0.380136E+09 | 0.409150E+09 | 0.100052E+10 | 0.139942E+09 |
July | 0.663385E+09 | 0.242637E+09 | 0.420748E+09 | 0.839880E+09 | 0.134374E+09 |
August | 0.694254E+09 | 0.343492E+09 | 0.350762E+09 | 0.864998E+09 | 0.153164E+09 |
September | 0.596489E+09 | 0.286695E+09 | 0.309794E+09 | 0.709412E+09 | 0.219960E+09 |
October | 0.515402E+09 | 0.294056E+09 | 0.221346E+09 | 0.526634E+09 | 0.407673E+09 |
November | 0.409894E+09 | 0.248630E+09 | 0.161264E+09 | 0.390884E+09 | 0.433416E+09 |
December | 0.342476E+09 | 0.202261E+09 | 0.140215E+09 | 0.291624E+09 | 0.554524E+09 |
Annual Sum or Average | 0.664133E+10 | 0.331294E+10 | 0.332839E+10 | 0.720986E+10 | 0.385678E+10 |
Minimum of Months | 0.342476E+09 | 0.202261E+09 | 0.140215E+09 | 0.291624E+09 | 0.134374E+09 |
Maximum of Months | 0.789286E+09 | 0.380136E+09 | 0.431341E+09 | 0.100052E+10 | 0.554524E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.409563E+09 | 0.259400E+09 | 0.150163E+09 | 0.383778E+09 | 0.480048E+09 |
February | 0.449155E+09 | 0.279136E+09 | 0.170019E+09 | 0.416375E+09 | 0.441097E+09 |
March | 0.579644E+09 | 0.320047E+09 | 0.259597E+09 | 0.568128E+09 | 0.369633E+09 |
April | 0.525748E+09 | 0.221752E+09 | 0.303996E+09 | 0.495030E+09 | 0.308976E+09 |
May | 0.666033E+09 | 0.234692E+09 | 0.431341E+09 | 0.722598E+09 | 0.213971E+09 |
June | 0.789286E+09 | 0.380136E+09 | 0.409150E+09 | 0.100052E+10 | 0.139942E+09 |
July | 0.663385E+09 | 0.242637E+09 | 0.420748E+09 | 0.839880E+09 | 0.134374E+09 |
August | 0.694254E+09 | 0.343492E+09 | 0.350762E+09 | 0.864998E+09 | 0.153164E+09 |
September | 0.596489E+09 | 0.286695E+09 | 0.309794E+09 | 0.709412E+09 | 0.219960E+09 |
October | 0.515402E+09 | 0.294056E+09 | 0.221346E+09 | 0.526634E+09 | 0.407673E+09 |
November | 0.409894E+09 | 0.248630E+09 | 0.161264E+09 | 0.390884E+09 | 0.433416E+09 |
December | 0.342476E+09 | 0.202261E+09 | 0.140215E+09 | 0.291624E+09 | 0.554524E+09 |
Annual Sum or Average | 0.664133E+10 | 0.331294E+10 | 0.332839E+10 | 0.720986E+10 | 0.385678E+10 |
Minimum of Months | 0.342476E+09 | 0.202261E+09 | 0.140215E+09 | 0.291624E+09 | 0.134374E+09 |
Maximum of Months | 0.789286E+09 | 0.380136E+09 | 0.431341E+09 | 0.100052E+10 | 0.554524E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 71803384.49 | 0.00 | 71803384.49 | 16177450.03 | 0.298223E+09 |
February | 81514584.58 | 0.00 | 81514584.58 | 18624588.06 | 0.272172E+09 |
March | 0.122845E+09 | 13414.35 | 0.122832E+09 | 58570475.90 | 0.225170E+09 |
April | 0.149315E+09 | 921844.23 | 0.148393E+09 | 84913882.54 | 0.182701E+09 |
May | 0.210883E+09 | 7075901.60 | 0.203807E+09 | 0.183072E+09 | 0.118365E+09 |
June | 0.223236E+09 | 24458860.85 | 0.198777E+09 | 0.268557E+09 | 74294351.02 |
July | 0.218921E+09 | 14512686.28 | 0.204408E+09 | 0.266797E+09 | 73196933.82 |
August | 0.174627E+09 | 4773230.35 | 0.169854E+09 | 0.199460E+09 | 86905770.26 |
September | 0.141479E+09 | 93103.05 | 0.141386E+09 | 0.140800E+09 | 0.128167E+09 |
October | 0.104620E+09 | 0.00 | 0.104620E+09 | 51681496.46 | 0.245092E+09 |
November | 76857816.77 | 0.00 | 76857816.77 | 23371238.29 | 0.264969E+09 |
December | 67180993.68 | 0.00 | 67180993.68 | 13370061.11 | 0.346777E+09 |
Annual Sum or Average | 0.164328E+10 | 51849040.70 | 0.159143E+10 | 0.132540E+10 | 0.231603E+10 |
Minimum of Months | 67180993.68 | 0.00 | 67180993.68 | 13370061.11 | 73196933.82 |
Maximum of Months | 0.223236E+09 | 24458860.85 | 0.204408E+09 | 0.268557E+09 | 0.346777E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 71801489.53 | 0.00 | 71801489.53 | 16176493.68 | 0.298223E+09 |
February | 81512575.24 | 0.00 | 81512575.24 | 18623659.87 | 0.272172E+09 |
March | 0.122842E+09 | 13413.72 | 0.122828E+09 | 58568014.77 | 0.225170E+09 |
April | 0.149311E+09 | 921801.03 | 0.148389E+09 | 84910046.78 | 0.182701E+09 |
May | 0.210876E+09 | 7075569.94 | 0.203801E+09 | 0.183065E+09 | 0.118365E+09 |
June | 0.223229E+09 | 24457714.43 | 0.198771E+09 | 0.268550E+09 | 74293573.77 |
July | 0.218914E+09 | 14512006.05 | 0.204402E+09 | 0.266790E+09 | 73196254.69 |
August | 0.174623E+09 | 4773006.62 | 0.169850E+09 | 0.199455E+09 | 86905025.02 |
September | 0.141475E+09 | 93098.68 | 0.141382E+09 | 0.140796E+09 | 0.128166E+09 |
October | 0.104617E+09 | 0.00 | 0.104617E+09 | 51679577.99 | 0.245092E+09 |
November | 76855794.09 | 0.00 | 76855794.09 | 23370112.47 | 0.264968E+09 |
December | 67179114.98 | 0.00 | 67179114.98 | 13369440.14 | 0.346776E+09 |
Annual Sum or Average | 0.164324E+10 | 51846610.47 | 0.159139E+10 | 0.132535E+10 | 0.231603E+10 |
Minimum of Months | 67179114.98 | 0.00 | 67179114.98 | 13369440.14 | 73196254.69 |
Maximum of Months | 0.223229E+09 | 24457714.43 | 0.204402E+09 | 0.268550E+09 | 0.346776E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.146160E+09 | 0.269905E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.198398E+09 | 0.251042E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.306211E+09 | 0.206135E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.319849E+09 | 0.164231E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.442351E+09 | 0.139997E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.552567E+09 | 0.148025E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.486847E+09 | 0.156307E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.486688E+09 | 0.168188E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.359548E+09 | 0.195373E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.244747E+09 | 0.252074E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.174147E+09 | 0.229915E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.111636E+09 | 0.328691E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.382915E+10 | 0.250988E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.111636E+09 | 0.139997E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.552567E+09 | 0.328691E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.146160E+09 | 0.269905E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.198398E+09 | 0.251042E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.306211E+09 | 0.206135E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.319849E+09 | 0.164231E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.442351E+09 | 0.139997E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.552567E+09 | 0.148025E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.486847E+09 | 0.156307E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.486688E+09 | 0.168188E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.359548E+09 | 0.195373E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.244747E+09 | 0.252074E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.174147E+09 | 0.229915E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.111636E+09 | 0.328691E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.382915E+10 | 0.250988E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.111636E+09 | 0.139997E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.552567E+09 | 0.328691E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.146160E+09 | 0.269905E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.198398E+09 | 0.251042E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.306211E+09 | 0.206135E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.319849E+09 | 0.164231E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.442351E+09 | 0.139997E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.552567E+09 | 0.148025E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.486847E+09 | 0.156307E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.486688E+09 | 0.168188E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.359548E+09 | 0.195373E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.244747E+09 | 0.252074E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.174147E+09 | 0.229915E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.111636E+09 | 0.328691E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.382915E+10 | 0.250988E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.111636E+09 | 0.139997E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.552567E+09 | 0.328691E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.146160E+09 | 0.269905E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.198398E+09 | 0.251042E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.306211E+09 | 0.206135E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.319849E+09 | 0.164231E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.442351E+09 | 0.139997E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.552567E+09 | 0.148025E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.486847E+09 | 0.156307E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.486688E+09 | 0.168188E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.359548E+09 | 0.195373E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.244747E+09 | 0.252074E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.174147E+09 | 0.229915E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.111636E+09 | 0.328691E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.382915E+10 | 0.250988E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.111636E+09 | 0.139997E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.552567E+09 | 0.328691E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.146160E+09 | 0.269905E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.198398E+09 | 0.251042E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.306211E+09 | 0.206135E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.319849E+09 | 0.164231E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.442351E+09 | 0.139997E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.552567E+09 | 0.148025E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.486847E+09 | 0.156307E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.486688E+09 | 0.168188E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.359548E+09 | 0.195373E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.244747E+09 | 0.252074E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.174147E+09 | 0.229915E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.111636E+09 | 0.328691E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.382915E+10 | 0.250988E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.111636E+09 | 0.139997E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.552567E+09 | 0.328691E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.146160E+09 | 0.269905E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.198398E+09 | 0.251042E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.306211E+09 | 0.206135E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.319849E+09 | 0.164231E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.442351E+09 | 0.139997E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.552567E+09 | 0.148025E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.486847E+09 | 0.156307E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.486688E+09 | 0.168188E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.359548E+09 | 0.195373E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.244747E+09 | 0.252074E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.174147E+09 | 0.229915E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.111636E+09 | 0.328691E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.382915E+10 | 0.250988E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.111636E+09 | 0.139997E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.552567E+09 | 0.328691E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.146160E+09 | 0.269905E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.198398E+09 | 0.251042E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.306211E+09 | 0.206135E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.319849E+09 | 0.164231E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.442351E+09 | 0.139997E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.552567E+09 | 0.148025E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.486847E+09 | 0.156307E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.486688E+09 | 0.168188E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.359548E+09 | 0.195373E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.244747E+09 | 0.252074E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.174147E+09 | 0.229915E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.111636E+09 | 0.328691E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.382915E+10 | 0.250988E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.111636E+09 | 0.139997E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.552567E+09 | 0.328691E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.146160E+09 | 0.269905E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.198398E+09 | 0.251042E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.306211E+09 | 0.206135E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.319849E+09 | 0.164231E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.442351E+09 | 0.139997E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.552567E+09 | 0.148025E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.486847E+09 | 0.156307E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.486688E+09 | 0.168188E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.359548E+09 | 0.195373E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.244747E+09 | 0.252074E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.174147E+09 | 0.229915E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.111636E+09 | 0.328691E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.382915E+10 | 0.250988E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.111636E+09 | 0.139997E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.552567E+09 | 0.328691E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.146160E+09 | 0.269905E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.198398E+09 | 0.251042E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.306211E+09 | 0.206135E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.319849E+09 | 0.164231E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.442351E+09 | 0.139997E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.552567E+09 | 0.148025E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.486847E+09 | 0.156307E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.486688E+09 | 0.168188E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.359548E+09 | 0.195373E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.244747E+09 | 0.252074E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.174147E+09 | 0.229915E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.111636E+09 | 0.328691E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.382915E+10 | 0.250988E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.111636E+09 | 0.139997E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.552567E+09 | 0.328691E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132123E+09 | 94299134.29 | 37823689.62 | 0.146160E+09 | 0.269905E+09 |
February | 0.174104E+09 | 0.133854E+09 | 40250177.83 | 0.198398E+09 | 0.251042E+09 |
March | 0.249634E+09 | 0.174802E+09 | 74831107.11 | 0.306211E+09 | 0.206135E+09 |
April | 0.261143E+09 | 0.152676E+09 | 0.108468E+09 | 0.319849E+09 | 0.164231E+09 |
May | 0.344512E+09 | 0.183434E+09 | 0.161079E+09 | 0.442351E+09 | 0.139997E+09 |
June | 0.417197E+09 | 0.290967E+09 | 0.126230E+09 | 0.552567E+09 | 0.148025E+09 |
July | 0.373738E+09 | 0.222367E+09 | 0.151371E+09 | 0.486847E+09 | 0.156307E+09 |
August | 0.371784E+09 | 0.265373E+09 | 0.106411E+09 | 0.486688E+09 | 0.168188E+09 |
September | 0.282626E+09 | 0.189198E+09 | 93428386.50 | 0.359548E+09 | 0.195373E+09 |
October | 0.208794E+09 | 0.147730E+09 | 61064360.30 | 0.244747E+09 | 0.252074E+09 |
November | 0.146690E+09 | 0.105996E+09 | 40693851.51 | 0.174147E+09 | 0.229915E+09 |
December | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.111636E+09 | 0.328691E+09 |
Annual Sum or Average | 0.307392E+10 | 0.203468E+10 | 0.103924E+10 | 0.382915E+10 | 0.250988E+10 |
Minimum of Months | 0.111577E+09 | 73986877.37 | 37589938.21 | 0.111636E+09 | 0.139997E+09 |
Maximum of Months | 0.417197E+09 | 0.290967E+09 | 0.161079E+09 | 0.552567E+09 | 0.328691E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 285.01 | 567.50 | 359.44 | 193.70 | 165.74 | 0.00 | 0.00 |
February | 345.73 | 575.78 | 438.71 | 230.77 | 207.95 | 0.00 | 0.00 |
March | 461.91 | 438.09 | 524.56 | 238.99 | 285.56 | 0.00 | 0.00 |
April | 444.82 | 376.72 | 520.88 | 171.82 | 349.06 | 0.00 | 0.00 |
May | 673.37 | 245.26 | 654.80 | 180.53 | 474.27 | 0.00 | 0.00 |
June | 974.09 | 160.18 | 781.26 | 312.19 | 469.08 | 0.00 | 0.00 |
July | 823.01 | 151.64 | 658.83 | 192.02 | 466.81 | 0.00 | 0.00 |
August | 793.70 | 178.12 | 648.80 | 260.05 | 388.75 | 0.00 | 0.00 |
September | 654.75 | 267.34 | 569.42 | 221.29 | 348.13 | 0.00 | 0.00 |
October | 427.54 | 483.13 | 462.98 | 219.58 | 243.40 | 0.00 | 0.00 |
November | 309.88 | 529.12 | 375.58 | 191.84 | 183.74 | 0.00 | 0.00 |
December | 213.87 | 659.14 | 305.90 | 151.03 | 154.87 | 0.00 | 0.00 |
Annual Sum or Average | 534.84 | 385.02 | 525.41 | 213.39 | 312.01 | 0.00 | 0.00 |
Minimum of Months | 213.87 | 151.64 | 305.90 | 151.03 | 154.87 | 0.00 | 0.00 |
Maximum of Months | 974.09 | 659.14 | 781.26 | 312.19 | 474.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1904.12 | 7084.31 | 493.29 | 352.07 | 141.22 | 0.00 | 0.00 |
February | 2859.68 | 8661.87 | 719.68 | 553.30 | 166.38 | 0.00 | 0.00 |
March | 4236.50 | 5540.34 | 932.02 | 652.64 | 279.39 | 0.00 | 0.00 |
April | 4624.48 | 3777.15 | 1007.50 | 589.03 | 418.47 | 0.00 | 0.00 |
May | 6498.57 | 1790.12 | 1286.26 | 684.86 | 601.40 | 0.00 | 0.00 |
June | 10799.26 | 3329.71 | 1609.56 | 1122.56 | 487.00 | 0.00 | 0.00 |
July | 9662.07 | 3460.59 | 1395.38 | 830.22 | 565.15 | 0.00 | 0.00 |
August | 9311.30 | 3842.41 | 1388.08 | 990.79 | 397.29 | 0.00 | 0.00 |
September | 6045.86 | 3667.31 | 1090.38 | 729.93 | 360.45 | 0.00 | 0.00 |
October | 3453.73 | 4392.72 | 779.55 | 551.56 | 227.99 | 0.00 | 0.00 |
November | 2353.38 | 5668.98 | 565.93 | 408.94 | 157.00 | 0.00 | 0.00 |
December | 1516.80 | 11576.95 | 416.58 | 276.24 | 140.34 | 0.00 | 0.00 |
Annual Sum or Average | 5284.48 | 5216.82 | 974.73 | 645.19 | 329.54 | 0.00 | 0.00 |
Minimum of Months | 1516.80 | 1790.12 | 416.58 | 276.24 | 140.34 | 0.00 | 0.00 |
Maximum of Months | 10799.26 | 11576.95 | 1609.56 | 1122.56 | 601.40 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.763371E+09 | 0.152000E+10 | 0.962731E+09 | 0.518800E+09 | 0.443931E+09 | 0.00 | 0.00 |
February | 0.836379E+09 | 0.139292E+10 | 0.106134E+10 | 0.558272E+09 | 0.503065E+09 | 0.00 | 0.00 |
March | 0.123718E+10 | 0.117339E+10 | 0.140497E+10 | 0.640121E+09 | 0.764853E+09 | 0.00 | 0.00 |
April | 0.115298E+10 | 0.976452E+09 | 0.135012E+10 | 0.445348E+09 | 0.904773E+09 | 0.00 | 0.00 |
May | 0.180356E+10 | 0.656903E+09 | 0.175383E+10 | 0.483535E+09 | 0.127029E+10 | 0.00 | 0.00 |
June | 0.252485E+10 | 0.415189E+09 | 0.202504E+10 | 0.809189E+09 | 0.121585E+10 | 0.00 | 0.00 |
July | 0.220436E+10 | 0.406156E+09 | 0.176460E+10 | 0.514299E+09 | 0.125031E+10 | 0.00 | 0.00 |
August | 0.212585E+10 | 0.477080E+09 | 0.173776E+10 | 0.696531E+09 | 0.104123E+10 | 0.00 | 0.00 |
September | 0.169710E+10 | 0.692938E+09 | 0.147593E+10 | 0.573576E+09 | 0.902356E+09 | 0.00 | 0.00 |
October | 0.114512E+10 | 0.129403E+10 | 0.124004E+10 | 0.588112E+09 | 0.651928E+09 | 0.00 | 0.00 |
November | 0.803219E+09 | 0.137148E+10 | 0.973502E+09 | 0.497260E+09 | 0.476242E+09 | 0.00 | 0.00 |
December | 0.572837E+09 | 0.176545E+10 | 0.819313E+09 | 0.404522E+09 | 0.414791E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.168668E+11 | 0.121420E+11 | 0.165692E+11 | 0.672957E+10 | 0.983961E+10 | 0.00 | 0.00 |
Minimum of Months | 0.572837E+09 | 0.406156E+09 | 0.819313E+09 | 0.404522E+09 | 0.414791E+09 | 0.00 | 0.00 |
Maximum of Months | 0.252485E+10 | 0.176545E+10 | 0.202504E+10 | 0.809189E+09 | 0.127029E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.509999E+10 | 0.189746E+11 | 0.132123E+10 | 0.942991E+09 | 0.378237E+09 | 0.00 | 0.00 |
February | 0.691814E+10 | 0.209548E+11 | 0.174104E+10 | 0.133854E+10 | 0.402502E+09 | 0.00 | 0.00 |
March | 0.113470E+11 | 0.148392E+11 | 0.249634E+10 | 0.174802E+10 | 0.748311E+09 | 0.00 | 0.00 |
April | 0.119867E+11 | 0.979037E+10 | 0.261143E+10 | 0.152676E+10 | 0.108468E+10 | 0.00 | 0.00 |
May | 0.174058E+11 | 0.479467E+10 | 0.344512E+10 | 0.183434E+10 | 0.161079E+10 | 0.00 | 0.00 |
June | 0.279917E+11 | 0.863061E+10 | 0.417197E+10 | 0.290967E+10 | 0.126230E+10 | 0.00 | 0.00 |
July | 0.258789E+11 | 0.926885E+10 | 0.373738E+10 | 0.222367E+10 | 0.151371E+10 | 0.00 | 0.00 |
August | 0.249394E+11 | 0.102915E+11 | 0.371784E+10 | 0.265373E+10 | 0.106411E+10 | 0.00 | 0.00 |
September | 0.156709E+11 | 0.950568E+10 | 0.282626E+10 | 0.189198E+10 | 0.934284E+09 | 0.00 | 0.00 |
October | 0.925048E+10 | 0.117655E+11 | 0.208794E+10 | 0.147730E+10 | 0.610644E+09 | 0.00 | 0.00 |
November | 0.609997E+10 | 0.146940E+11 | 0.146690E+10 | 0.105996E+10 | 0.406939E+09 | 0.00 | 0.00 |
December | 0.406259E+10 | 0.310077E+11 | 0.111577E+10 | 0.739869E+09 | 0.375899E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.166651E+12 | 0.164517E+12 | 0.307392E+11 | 0.203468E+11 | 0.103924E+11 | 0.00 | 0.00 |
Minimum of Months | 0.406259E+10 | 0.479467E+10 | 0.111577E+10 | 0.739869E+09 | 0.375899E+09 | 0.00 | 0.00 |
Maximum of Months | 0.279917E+11 | 0.310077E+11 | 0.417197E+10 | 0.290967E+10 | 0.161079E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.36 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.29 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.52 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.46 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.25 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.79 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.35 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.31 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.37 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.25 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.97 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.74 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.90 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.49 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.92 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.63 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.90 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.36 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.05 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.73 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.10 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.94 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.97 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.36 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.4 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.45 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.30 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.22 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.9 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.22 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.55 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.98 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 8.00 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.50 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.87 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.65 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.75 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.80 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.54 | 196.33 | 4.00 |
September | 14.95 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.73 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.33 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.94 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.55 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.75 | 29.40 | 16.00 | 9.80 | 20.54 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.50 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.73 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.65 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.92 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.90 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.40 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.06 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.06 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.65 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.105637E+10 | -901546111.3 | 0.00 | 0.00 | 744.00 | 0.00 | -154824736.2 | 58.99 | 0.00 | 0.00 |
February | 0.978845E+09 | -838411876.3 | 0.00 | 0.00 | 672.00 | 0.00 | -140433318.9 | 58.99 | 0.00 | 0.00 |
March | 0.111685E+10 | -965408603.9 | 0.00 | 0.00 | 744.00 | 0.00 | -151441595.6 | 58.99 | 0.00 | 0.00 |
April | 0.100795E+10 | -861660811.3 | 0.00 | 0.00 | 720.00 | 0.00 | -146290572.6 | 58.99 | 0.00 | 0.00 |
May | 0.986445E+09 | -846629417.4 | 0.00 | 0.00 | 744.00 | 0.00 | -139815659.3 | 58.99 | 0.00 | 0.00 |
June | 0.921668E+09 | -793585000.6 | 0.00 | 0.00 | 720.00 | 0.00 | -128082682.6 | 58.99 | 0.00 | 0.00 |
July | 0.863756E+09 | -732136235.8 | 0.00 | 0.00 | 744.00 | 0.00 | -131619833.7 | 58.99 | 0.00 | 0.00 |
August | 0.906071E+09 | -773612662.4 | 0.00 | 0.00 | 744.00 | 0.00 | -132458650.1 | 59.00 | 0.00 | 0.00 |
September | 0.862313E+09 | -733233273.1 | 0.00 | 0.00 | 720.00 | 0.00 | -129079577.0 | 58.99 | 0.00 | 0.00 |
October | 0.915608E+09 | -771070609.6 | 0.00 | 0.00 | 744.00 | 0.00 | -144537519.8 | 58.99 | 0.00 | 0.00 |
November | 0.933679E+09 | -786507376.8 | 0.00 | 0.00 | 720.00 | 0.00 | -147171153.6 | 58.99 | 0.00 | 0.00 |
December | 0.102171E+10 | -866017573.1 | 0.00 | 0.00 | 744.00 | 0.00 | -155694811.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.115713E+11 | -0.986982E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.170145E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.862313E+09 | -965408603.9 | 0.00 | 0.00 | 672.00 | 0.00 | -155694811.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.111685E+10 | -732136235.8 | 0.00 | 0.00 | 744.00 | 0.00 | -128082682.6 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 276.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 245.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 296.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 415.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 421.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 430.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 394.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 354.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 262.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 257.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 251.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3902.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 245.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 430.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.554793E+10 | 33100.19 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.650674E+10 | 33100.19 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.490340E+10 | 33100.19 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.313053E+10 | 33100.19 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.487689E+09 | 33100.19 | 01-MAY-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 60420374.12 | 23532.00 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.234722E+10 | 33100.19 | 04-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.399462E+10 | 33100.19 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.822505E+10 | 33100.19 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.352036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.822505E+10 | 33100.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.165530E+11 | 116304.87 | 01-JAN-02:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.201705E+11 | 116304.87 | 01-FEB-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135739E+11 | 116304.87 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.915237E+10 | 116304.87 | 02-APR-03:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.666058E+09 | 106153.70 | 02-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.552239E+10 | 116304.87 | 24-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109741E+11 | 116304.87 | 01-NOV-00:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.312492E+11 | 116304.87 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107861E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.312492E+11 | 116304.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.413491E+11 | 93185.67 | 05-JAN-19:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.598925E+11 | 128826.37 | 12-FEB-05:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271912E+11 | 151430.90 | 19-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143263E+11 | 69667.12 | 17-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.988780E+10 | 78773.29 | 31-OCT-23:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.239955E+11 | 122130.10 | 30-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.967450E+11 | 163672.83 | 21-DEC-17:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.273387E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.967450E+11 | 163672.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 48812383.13 | 48812383.13 | 3173.33 | 20-JAN-15:30 | 3173.33 | 0.00 |
February | 0.00 | 0.00 | 43658053.76 | 43658053.76 | 3041.47 | 18-FEB-14:50 | 3041.47 | 0.00 |
March | 0.00 | 0.00 | 0.462136E+09 | 0.462136E+09 | 9383.40 | 13-MAR-17:12 | 9383.40 | 0.00 |
April | 0.00 | 0.00 | 0.435611E+09 | 0.435611E+09 | 6382.48 | 20-APR-17:20 | 6382.48 | 0.00 |
May | 0.00 | 0.00 | 0.247312E+10 | 0.245435E+10 | 17516.85 | 31-MAY-17:08 | 17516.85 | 0.00 |
June | 0.00 | 0.00 | 0.105940E+11 | 0.101840E+11 | 25631.80 | 18-JUN-23:02 | 23622.61 | 0.00 |
July | 0.00 | 0.00 | 0.106452E+11 | 0.100615E+11 | 28546.49 | 30-JUL-23:02 | 18512.79 | 0.00 |
August | 0.00 | 0.00 | 0.108276E+11 | 0.103862E+11 | 26336.03 | 27-AUG-23:02 | 22431.68 | 0.00 |
September | 0.00 | 0.00 | 0.692184E+10 | 0.685901E+10 | 24810.24 | 04-SEP-23:01 | 24810.24 | 0.00 |
October | 0.00 | 0.00 | 0.114202E+10 | 0.114202E+10 | 8805.10 | 10-OCT-17:13 | 8805.10 | 0.00 |
November | 0.00 | 0.00 | 0.252103E+09 | 0.252103E+09 | 5249.91 | 07-NOV-15:30 | 5249.91 | 0.00 |
December | 0.00 | 0.00 | 71699890.40 | 71699890.40 | 3477.54 | 02-DEC-15:00 | 3477.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.439178E+11 | 0.424011E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 43658053.76 | 43658053.76 | 3041.47 | 3041.47 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.108276E+11 | 0.103862E+11 | 28546.49 | 24810.24 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.473763E+09 | 0.473763E+09 | 12702.68 | 15-MAR-14:10 | 12702.68 | 0.00 |
April | 0.00 | 0.00 | 83150635.37 | 83150635.37 | 6089.93 | 21-APR-13:30 | 6089.93 | 0.00 |
May | 0.00 | 0.00 | 0.454613E+10 | 0.454050E+10 | 24132.64 | 31-MAY-14:50 | 24132.64 | 0.00 |
June | 0.00 | 0.00 | 0.289827E+11 | 0.284080E+11 | 73115.79 | 15-JUN-17:05 | 73115.79 | 0.00 |
July | 0.00 | 0.00 | 0.291579E+11 | 0.283888E+11 | 77091.85 | 23-JUL-11:13 | 77091.85 | 0.00 |
August | 0.00 | 0.00 | 0.284768E+11 | 0.279445E+11 | 78830.40 | 06-AUG-13:23 | 78830.40 | 0.00 |
September | 0.00 | 0.00 | 0.166547E+11 | 0.166118E+11 | 72476.08 | 10-SEP-12:43 | 72476.08 | 0.00 |
October | 0.00 | 0.00 | 0.156861E+10 | 0.156861E+10 | 22096.96 | 11-OCT-14:10 | 22096.96 | 0.00 |
November | 0.00 | 0.00 | 38083925.77 | 38083925.77 | 3752.88 | 09-NOV-13:10 | 3752.88 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.109982E+12 | 0.108057E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.291579E+11 | 0.284080E+11 | 78830.40 | 78830.40 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.529627E+09 | 0.04 | 457.71 | 01-JAN-00:03 | 0.09 |
February | 0.602320E+09 | 0.05 | 457.71 | 01-FEB-00:03 | 0.09 |
March | 0.425479E+09 | 0.03 | 457.71 | 01-MAR-02:00 | 0.09 |
April | 0.220215E+09 | 0.02 | 457.71 | 01-APR-19:50 | 0.09 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.113695E+09 | 0.01 | 457.71 | 25-OCT-03:40 | 0.09 |
November | 0.314850E+09 | 0.02 | 457.71 | 01-NOV-00:03 | 0.09 |
December | 0.783295E+09 | 0.06 | 457.71 | 01-DEC-00:03 | 0.09 |
Annual Sum or Average | 0.298948E+10 | 0.02 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.783295E+09 | 0.06 | 457.71 | 0.09 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.175960E+10 | 0.63 | 1675.68 | 02-JAN-18:00 | 1.11 |
February | 0.166096E+10 | 0.69 | 1675.68 | 02-FEB-13:00 | 1.11 |
March | 0.188905E+10 | 0.63 | 1675.68 | 01-MAR-17:50 | 1.11 |
April | 0.172840E+10 | 0.56 | 1675.68 | 03-APR-16:15 | 1.11 |
May | 0.174342E+10 | 0.45 | 1675.68 | 02-MAY-16:13 | 1.11 |
June | 0.188641E+10 | 0.70 | 1675.68 | 02-JUN-10:20 | 1.10 |
July | 0.182923E+10 | 0.68 | 1675.68 | 01-JUL-10:20 | 1.11 |
August | 0.196902E+10 | 0.73 | 1675.68 | 01-AUG-15:30 | 1.10 |
September | 0.174887E+10 | 0.60 | 1675.68 | 01-SEP-09:10 | 1.09 |
October | 0.169668E+10 | 0.48 | 1675.68 | 04-OCT-06:17 | 1.10 |
November | 0.165244E+10 | 0.51 | 1675.68 | 01-NOV-06:20 | 1.11 |
December | 0.182535E+10 | 0.69 | 1675.68 | 05-DEC-08:20 | 1.11 |
Annual Sum or Average | 0.213894E+11 | 0.61 | |||
Minimum of Months | 0.165244E+10 | 0.45 | 1675.68 | 1.09 | |
Maximum of Months | 0.196902E+10 | 0.73 | 1675.68 | 1.11 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.933352E+10 | 1.41 | 8184.59 | 02-JAN-17:30 | 1.90 |
February | 0.893489E+10 | 1.49 | 8184.59 | 06-FEB-13:20 | 1.90 |
March | 0.978325E+10 | 1.30 | 8184.59 | 01-MAR-17:50 | 1.90 |
April | 0.881370E+10 | 1.15 | 8184.59 | 03-APR-07:20 | 1.90 |
May | 0.848215E+10 | 0.78 | 8184.59 | 05-MAY-11:40 | 1.89 |
June | 0.880298E+10 | 0.93 | 8184.59 | 01-JUN-12:20 | 1.88 |
July | 0.856705E+10 | 0.92 | 8184.59 | 01-JUL-07:05 | 1.90 |
August | 0.903399E+10 | 0.91 | 8184.59 | 01-AUG-11:23 | 1.89 |
September | 0.823813E+10 | 0.80 | 8184.59 | 02-SEP-10:00 | 1.88 |
October | 0.848371E+10 | 0.91 | 8184.59 | 04-OCT-14:00 | 1.89 |
November | 0.858537E+10 | 1.21 | 8184.59 | 08-NOV-14:20 | 1.90 |
December | 0.101723E+11 | 1.55 | 8184.59 | 05-DEC-17:50 | 1.90 |
Annual Sum or Average | 0.107231E+12 | 1.11 | |||
Minimum of Months | 0.823813E+10 | 0.78 | 8184.59 | 1.88 | |
Maximum of Months | 0.101723E+11 | 1.55 | 8184.59 | 1.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.177298E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.167292E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.201414E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.184701E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.241604E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.490710E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.483724E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.502102E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.365400E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.200472E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.172078E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.184497E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.337129E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.167292E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.502102E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.933352E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.893489E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.992352E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.883851E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.984157E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.178740E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.176384E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.178259E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.132886E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.894898E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.859679E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.101723E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.141217E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.859679E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.178740E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.175960E+10 | 48812383.13 | 0.554793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166096E+10 | 43658053.76 | 0.650674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.188905E+10 | 0.462136E+09 | 0.490340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172840E+10 | 0.435611E+09 | 0.313053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.174342E+10 | 0.247312E+10 | 0.487689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.188641E+10 | 0.105940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.182923E+10 | 0.106452E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196902E+10 | 0.108276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174887E+10 | 0.692184E+10 | 60420374.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169668E+10 | 0.114202E+10 | 0.234722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165244E+10 | 0.252103E+09 | 0.399462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182535E+10 | 71699890.40 | 0.822505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.213894E+11 | 0.439178E+11 | 0.352036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.165244E+10 | 43658053.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196902E+10 | 0.108276E+11 | 0.822505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.933352E+10 | 0.00 | 0.165530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.893489E+10 | 0.00 | 0.201705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.978325E+10 | 0.473763E+09 | 0.135739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.881370E+10 | 83150635.37 | 0.915237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.848215E+10 | 0.454613E+10 | 0.666058E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.880298E+10 | 0.289827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.856705E+10 | 0.291579E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.903399E+10 | 0.284768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.823813E+10 | 0.166547E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.848371E+10 | 0.156861E+10 | 0.552239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.858537E+10 | 38083925.77 | 0.109741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101723E+11 | 0.00 | 0.312492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107231E+12 | 0.109982E+12 | 0.107861E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.823813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101723E+11 | 0.291579E+11 | 0.312492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.175960E+10 | 0.00 | 0.00 | 0.00 | 13375180.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166096E+10 | 0.00 | 0.00 | 0.00 | 11954461.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.188905E+10 | 0.00 | 0.00 | 0.00 | 0.125090E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172840E+10 | 0.00 | 0.00 | 0.00 | 0.118609E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.174342E+10 | 0.00 | 0.00 | 0.00 | 0.672626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.188641E+10 | 0.00 | 0.00 | 0.00 | 0.302068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.182923E+10 | 0.00 | 0.00 | 0.00 | 0.300801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196902E+10 | 0.00 | 0.00 | 0.00 | 0.305200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174887E+10 | 0.00 | 0.00 | 0.00 | 0.190513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169668E+10 | 0.00 | 0.00 | 0.00 | 0.308047E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165244E+10 | 0.00 | 0.00 | 0.00 | 68342793.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182535E+10 | 0.00 | 0.00 | 0.00 | 19621777.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.213894E+11 | 0.00 | 0.00 | 0.00 | 0.123235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.165244E+10 | 0.00 | 0.00 | 0.00 | 11954461.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196902E+10 | 0.00 | 0.00 | 0.00 | 0.305200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.933352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.893489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.978325E+10 | 0.00 | 0.00 | 0.00 | 0.140273E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.881370E+10 | 0.00 | 0.00 | 0.00 | 24809527.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.848215E+10 | 0.00 | 0.00 | 0.00 | 0.135942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.880298E+10 | 0.00 | 0.00 | 0.00 | 0.907101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.856705E+10 | 0.00 | 0.00 | 0.00 | 0.907133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.903399E+10 | 0.00 | 0.00 | 0.00 | 0.879189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.823813E+10 | 0.00 | 0.00 | 0.00 | 0.505045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.848371E+10 | 0.00 | 0.00 | 0.00 | 0.465269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.858537E+10 | 0.00 | 0.00 | 0.00 | 11419398.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107231E+12 | 0.00 | 0.00 | 0.00 | 0.339859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.823813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101723E+11 | 0.00 | 0.00 | 0.00 | 0.907133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.451188E+09 | 0.00 | 0.00 | 106423.92 | 0.00 | 0.152823E+10 | 0.152529E+09 | 0.00 | 0.16 |
February | 0.337913E+09 | 0.00 | 0.00 | 45574.45 | 0.00 | 0.159174E+10 | 45128727.33 | 0.00 | 0.15 |
March | 0.397267E+09 | 0.00 | 0.00 | 657114.49 | 0.00 | 0.126328E+10 | 0.355796E+09 | 0.00 | 0.18 |
April | 0.583833E+09 | 0.00 | 0.00 | 503577.12 | 0.00 | 0.779356E+09 | 0.247517E+09 | 0.00 | 0.16 |
May | 0.234596E+09 | 5492705.55 | 0.00 | 3401250.79 | 0.00 | 89329659.02 | 0.137547E+10 | 0.00 | 0.27 |
June | 17974085.49 | 0.259146E+09 | 0.00 | 4334046.73 | 0.00 | 0.00 | 0.393363E+09 | 0.00 | 0.22 |
July | 14964712.67 | 0.288832E+09 | 0.00 | 3664362.65 | 0.00 | 0.00 | 0.302576E+09 | 0.00 | 0.20 |
August | 29252598.10 | 0.209888E+09 | 0.00 | 6157793.24 | 0.00 | 0.00 | 0.614387E+09 | 0.00 | 0.23 |
September | 74737158.42 | 46852290.65 | 0.00 | 5925041.06 | 0.00 | 11850425.43 | 0.987444E+09 | 0.00 | 0.27 |
October | 0.491283E+09 | 0.00 | 0.00 | 1998640.43 | 0.00 | 0.597215E+09 | 0.956146E+09 | 0.00 | 0.20 |
November | 0.523593E+09 | 0.00 | 0.00 | 464007.11 | 0.00 | 0.111513E+10 | 0.348371E+09 | 0.00 | 0.17 |
December | 0.324119E+09 | 0.00 | 0.00 | 62062.91 | 0.00 | 0.191701E+10 | 40390165.96 | 0.00 | 0.15 |
Annual Sum or Average | 0.348072E+10 | 0.810211E+09 | 0.00 | 27319894.91 | 0.00 | 0.889313E+10 | 0.581911E+10 | 0.00 | 0.20 |
Minimum of Months | 14964712.67 | 0.00 | 0.00 | 45574.45 | 0.00 | 0.00 | 40390165.96 | 0.00 | 0.15 |
Maximum of Months | 0.583833E+09 | 0.288832E+09 | 0.00 | 6157793.24 | 0.00 | 0.191701E+10 | 0.137547E+10 | 0.00 | 0.27 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.406669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106636E+10 | 0.00 | 0.00 | 0.15 |
February | 0.382583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.993573E+09 | 0.00 | 0.00 | 0.15 |
March | 0.404545E+10 | 0.00 | 0.00 | 163737.88 | 0.00 | 0.615919E+09 | 0.124857E+09 | 0.00 | 0.16 |
April | 0.379327E+10 | 0.00 | 0.00 | 11951.34 | 0.00 | 0.238376E+09 | 44263463.27 | 0.00 | 0.15 |
May | 0.254517E+10 | 0.00 | 0.00 | 3502612.21 | 0.00 | 0.00 | 0.134932E+10 | 0.00 | 0.18 |
June | 0.178972E+09 | 0.218082E+09 | 0.00 | 24041389.95 | 0.00 | 0.00 | 0.179852E+10 | 0.00 | 0.21 |
July | 0.131317E+09 | 0.186984E+09 | 0.00 | 24104166.27 | 0.00 | 0.00 | 0.183508E+10 | 0.00 | 0.22 |
August | 0.241795E+09 | 0.162581E+09 | 0.00 | 31054631.30 | 0.00 | 0.00 | 0.272786E+10 | 0.00 | 0.23 |
September | 0.789653E+09 | 4214819.55 | 0.00 | 19305657.52 | 0.00 | 0.00 | 0.234823E+10 | 0.00 | 0.21 |
October | 0.349577E+10 | 0.00 | 0.00 | 1037393.67 | 0.00 | 0.707015E+09 | 0.565138E+09 | 0.00 | 0.15 |
November | 0.405016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672061E+09 | 0.00 | 0.00 | 0.14 |
December | 0.297259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247801E+10 | 0.00 | 0.00 | 0.14 |
Annual Sum or Average | 0.301367E+11 | 0.571862E+09 | 0.00 | 0.103222E+09 | 0.00 | 0.677132E+10 | 0.107933E+11 | 0.00 | 0.17 |
Minimum of Months | 0.131317E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.406669E+10 | 0.218082E+09 | 0.00 | 31054631.30 | 0.00 | 0.247801E+10 | 0.272786E+10 | 0.00 | 0.23 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.529701E+12 | 0.452573E+11 | 0.00 | 0.726510E+10 | 0.327281E+11 |
February | 0.677532E+12 | 0.725002E+11 | 0.00 | 0.679423E+10 | 0.377557E+11 |
March | 0.855161E+12 | 0.759470E+11 | 0.00 | 0.680338E+10 | 0.288113E+11 |
April | 0.884913E+12 | 0.699010E+11 | 0.00 | 0.568726E+10 | 0.220532E+11 |
May | 0.110242E+13 | 0.476525E+11 | 0.00 | 0.561400E+10 | 0.223368E+11 |
June | 0.121213E+13 | 0.446445E+11 | 0.00 | 0.216128E+10 | 0.639804E+11 |
July | 0.112109E+13 | 0.549997E+11 | 0.00 | 0.203868E+10 | 0.646049E+11 |
August | 0.111876E+13 | 0.548627E+11 | 0.00 | 0.354337E+10 | 0.638707E+11 |
September | 0.832226E+12 | 0.525040E+11 | 0.00 | 0.438318E+10 | 0.428738E+11 |
October | 0.684334E+12 | 0.684055E+11 | 0.00 | 0.682052E+10 | 0.222019E+11 |
November | 0.567329E+12 | 0.529588E+11 | 0.00 | 0.670978E+10 | 0.252742E+11 |
December | 0.418676E+12 | 0.101897E+12 | 0.00 | 0.773218E+10 | 0.528705E+11 |
Annual Sum or Average | 0.100043E+14 | 0.741531E+12 | 0.00 | 0.655530E+11 | 0.479361E+12 |
Minimum of Months | 0.418676E+12 | 0.446445E+11 | 0.00 | 0.203868E+10 | 0.220532E+11 |
Maximum of Months | 0.121213E+13 | 0.101897E+12 | 0.00 | 0.773218E+10 | 0.646049E+11 |