Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:42
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2023-10-16 10:42:42
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:42
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 588.14 | 121.64 | 121.64 |
Net Site Energy | 588.14 | 121.64 | 121.64 |
Total Source Energy | 1362.33 | 281.76 | 281.76 |
Net Source Energy | 1362.33 | 281.76 | 281.76 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 240.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 97.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 62.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 23.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 347.95 | 240.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 240.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 1.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 97.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 62.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 23.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 240.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 97.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 62.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 23.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 26.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 33.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 10.66 | 49.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 71.96 | 49.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 33.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 10.66 | 49.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 71.96 | 49.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 347.953 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 347.953 | 100.00 |
Total On-Site and Utility Electric Sources | 347.953 | 100.00 |
Total Electricity End Uses | 347.953 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 64.83 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2587.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:42
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:42 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 68.38 |
Skylight-Roof Ratio [%] | 1.49 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 9.3385 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 7.4271 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.7674 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 5.0950 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 5.0950 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 9.3385 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 7.4271 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.7674 | 46.45 | 2.5587 | |
Total | 4835.13 | 5.0950 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 5.0950 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 5.0950 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:42
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-DEC-08:09 | 10-JAN-06:19 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 109560.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8712.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5520.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2224.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1648.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 28141.60 | 109560.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 109560.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 8712.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5520.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2224.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1648.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:42
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 260.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 309.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 196.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 74.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 82.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1101.97 | 260.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 53.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 64.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 15.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 227.91 | 53.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 53.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 64.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 15.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 227.91 | 53.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:42
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.935251 |
ZONE2 FINE STORAGE DIRECT AIR | 1.64 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 1.64 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 1.64 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 66522.08 |
PSZ-OFFICE HEATING COIL | 24359.89 |
PSZ-FINE STORAGE HEATING COIL | 58029.39 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 66522.08 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.935251 | 0.935251 | 0.935251 | 0.935251 | 0.935251 | 0.935251 | 1.00 | 1.00 | 0.935251 |
PSZ-FINE STORAGE | 1.64 | 1.64 | 1.64 | 1.64 | 1.64 | 1.64 | 1.00 | 1.00 | 1.64 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 0.935251 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 1.64 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.935251 | 1035.47 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.64 | 1752.86 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.935251 | 0.935251 | 0.935251 | 0.935251 | 15481.73 | 24359.89 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 1.64 | 1.64 | 1.64 | 1.08 | 31630.07 | 58029.39 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.935250 | 0.467626 | 0.623500 | 15481.73 | 7740.86 | 0.800660 | 0.800660 |
PSZ-FINE STORAGE COOLING COIL | 1.64 | 0.819058 | 1.09 | 31630.07 | 15815.03 | 0.790190 | 0.790190 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:42
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:42
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:42
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 9.339 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 17.412 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 7.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.427 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.767 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 6.326 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2212.108 | 9.339 | 173.516 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2212.108 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 10348.979 | 7.427 | 344.966 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10348.979 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 12073.795 | 3.767 | 174.983 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 12073.795 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2163 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.4974 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.3694 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.6534 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 2.044 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.6534 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.622 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.010 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.608 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.431 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4892 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.431 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.18741198E-13 | -0.13599760E-18 | 0.18147593E-18 | 0.0000000 |
2 | 1 | -5.2160601 | 0.51384690E-04 | -0.74050972E-04 | 0.35929797E-14 |
3 | 0 | 5.4323994 | 0.21628790 | 0.21641333 | |
4 | 2 | 0.53330648E-11 | 0.17872838E-15 | 0.22136589E-15 | 0.0000000 |
5 | 1 | -5.2159880 | 0.41449123E-04 | -0.32205733E-04 | 0.68736940E-11 |
6 | 0 | 5.7134214 | 0.49739196 | 0.49746561 | |
7 | 4 | 0.80462617E-12 | 0.82840410E-16 | -0.20078756E-14 | 0.11271485E-15 |
8 | 3 | -0.39242815E-03 | 0.26180773E-06 | -0.56999769E-04 | 0.15438257E-12 |
9 | 2 | 1.7577325 | 0.56772723E-02 | 1.1542901 | -0.75235290E-04 |
10 | 1 | -7.1048256 | 0.14632850 | -17.186369 | 0.33689683 |
11 | 0 | 5.5924660 | 0.92974441E-01 | 16.277116 | |
12 | 4 | 0.74747876E-12 | 0.20825084E-15 | -0.25659737E-14 | 0.12362927E-15 |
13 | 3 | -0.37328678E-03 | 0.45238042E-06 | -0.54038165E-04 | 0.14344535E-12 |
14 | 2 | 1.7123825 | 0.10013958E-01 | 1.1198054 | -0.71564441E-04 |
15 | 1 | -7.1648294 | 0.26145347 | -16.966117 | 0.32817431 |
16 | 0 | 5.8918369 | 0.16754891 | 16.285382 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.0441747 | 2.0441747 | 2.0441747 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.25659737E-14 | 0.20825084E-15 | 0.74747876E-12 | 0.12362927E-15 |
85 | 3 | -0.54038165E-04 | 0.45238042E-06 | -0.37328678E-03 | 0.14344535E-12 |
86 | 2 | 1.1198054 | 0.10013958E-01 | 1.7123825 | -0.71564441E-04 |
87 | 1 | -16.966117 | 0.26145347 | -7.1648294 | 0.32817431 |
88 | 0 | 16.285382 | 0.16754891 | 5.8918369 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.379_SHGC_SOUTH_0.38 | 34 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.381 | ||
2 | NONRESWINDOW_U_0.379_SHGC_NORTH_0.38 | 35 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.381 | ||
3 | NONRESWINDOW_U_0.379_SHGC_EAST_0.38 | 36 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.381 | ||
4 | NONRESWINDOW_U_0.379_SHGC_WEST_0.38 | 37 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.381 | ||
5 | SKYLIGHT_U_0.5_SHGC_0.4 | 38 | 1 | VerySmooth | 2.843 | 2.843 | 1.000 | 0.401 | ||
6 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | 39 | 1 | VerySmooth | 5.556 | 5.556 | 1.000 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.46913E-002 | 0.29373 | 0.49866 | 0.49866 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.46913E-002 | 0.29373 | 0.49866 | 0.49866 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.46913E-002 | 0.29373 | 0.49866 | 0.49866 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.46913E-002 | 0.29373 | 0.49866 | 0.49866 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.31435 | 0.46556 | 0.46556 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 0.10078 | 0.10078 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.14909 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | CurtainWall | 2.775 | 0.408 | 0.402 |
2 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.268 | 0.549 | 0.552 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.331 | 7.274E-004 | 4.751E-004 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.8381E-005 |
2 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5172E-004 |
3 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.7156E-005 |
4 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6875E-004 |
5 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.6500E-005 |
6 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.0058E-004 |
7 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5724E-005 |
8 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.5867E-004 |
9 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7141E-004 |
10 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.9799E-004 |
11 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4174E-004 |
12 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.2784E-004 |
13 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5769E-004 |
14 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6612E-004 |
15 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3414E-004 |
16 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4540E-004 |
17 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.7702E-004 |
18 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5117E-004 |
19 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1282E-004 |
20 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6765E-004 |
21 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.7738E-004 |
22 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1594E-004 |
23 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8792E-004 |
24 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6675E-005 |
25 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.3672E-004 |
26 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9545E-005 |
27 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.6689E-004 |
28 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.7042E-005 |
29 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0385E-003 |
30 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2447E-005 |
31 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3392E-003 |
32 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0724E-005 |
33 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0273E-004 |
34 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4802E-005 |
35 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0705E-004 |
36 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.8136E-005 |
37 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.2694E-004 |
38 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8781E-005 |
39 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9718E-004 |
40 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6272E-005 |
41 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.4543E-004 |
42 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4418E-005 |
43 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.7696E-004 |
44 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5905E-005 |
45 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.2882E-004 |
46 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.3905E-005 |
47 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7955E-004 |
48 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4789E-005 |
49 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.9451E-004 |
50 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8837E-005 |
51 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0790E-003 |
52 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1687E-005 |
53 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.5743E-004 |
54 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4558E-005 |
55 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3679E-004 |
56 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4861E-005 |
57 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5785E-003 |
58 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8000E-005 |
59 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7555E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.5429E-005 |
61 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7202E-003 |
62 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0864E-005 |
63 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1133E-003 |
64 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6508E-005 |
65 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4631E-003 |
66 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3664E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3505E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5886E-004 |
69 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3656E-003 |
70 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.0526E-005 |
71 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5808E-003 |
72 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1684E-005 |
73 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1575E-004 |
74 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.4446E-004 |
75 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.0901E-004 |
76 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.2150E-004 |
77 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.0022E-004 |
78 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5427E-004 |
79 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6286E-003 |
80 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1734E-005 |
81 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1899E-004 |
82 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6294E-004 |
83 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7855E-004 |
84 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.2703E-004 |
85 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0496E-004 |
86 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.3155E-004 |
87 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3102E-004 |
88 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8162E-004 |
89 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.7608E-005 |
90 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4526E-003 |
91 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.4139E-005 |
92 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6584E-003 |
93 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.3378E-005 |
94 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4005E-003 |
95 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0760E-004 |
96 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8446E-004 |
97 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.3004E-005 |
98 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6061E-003 |
99 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.7998E-005 |
100 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5452E-003 |
101 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9057E-005 |
102 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4782E-003 |
103 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7398E-005 |
104 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.1825E-003 |
105 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0922E-005 |
106 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6465E-004 |
107 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.6432E-005 |
108 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0613E-004 |
109 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.7771E-005 |
110 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0842E-003 |
111 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5431E-005 |
112 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2422E-003 |
113 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2172E-005 |
114 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.8737E-005 |
115 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4832E-005 |
116 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.4496E-005 |
117 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2555E-005 |
118 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.8147E-005 |
119 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1321E-005 |
120 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.9767E-005 |
121 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4771E-005 |
122 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1587E-005 |
123 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.1482E-005 |
124 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.2141E-005 |
125 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5153E-005 |
126 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0460E-005 |
127 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4814E-005 |
128 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2243E-005 |
129 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0778E-005 |
130 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0393E-005 |
131 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4158E-005 |
132 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8721E-005 |
133 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4304E-005 |
134 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0996E-005 |
135 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1298E-005 |
136 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2681E-005 |
137 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7866E-004 |
138 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2795E-004 |
139 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2363E-004 |
140 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6401E-004 |
141 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7853E-004 |
142 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4325E-004 |
143 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5955E-005 |
144 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2983E-005 |
145 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0259E-004 |
146 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7842E-004 |
147 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0671E-004 |
148 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8633E-004 |
149 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3629E-005 |
150 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1988E-004 |
151 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1757E-005 |
152 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1077E-005 |
153 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3689E-004 |
154 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8526E-005 |
155 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5091E-004 |
156 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8601E-005 |
157 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0320E-004 |
158 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7986E-005 |
159 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1734E-005 |
160 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2731E-005 |
161 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3396E-004 |
162 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3984E-005 |
163 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.3010E-004 |
164 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.8123E-005 |
165 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0216E-004 |
166 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2859E-005 |
167 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5935E-005 |
168 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1887E-005 |
169 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4490E-004 |
170 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9201E-004 |
171 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4600E-004 |
172 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2006E-003 |
173 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5472E-004 |
174 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9888E-004 |
175 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6979E-005 |
176 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3777E-004 |
177 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5397E-004 |
178 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6777E-004 |
179 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3303E-004 |
180 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1472E-004 |
181 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4812E-004 |
182 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9552E-004 |
183 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0720E-004 |
184 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4148E-004 |
185 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0107E-004 |
186 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0248E-004 |
187 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5941E-004 |
188 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0444E-004 |
189 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0677E-004 |
190 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0004E-004 |
191 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0708E-004 |
192 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6592E-005 |
193 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9136E-004 |
194 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1566E-005 |
195 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0446E-004 |
196 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0863E-005 |
197 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7431E-004 |
198 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2732E-005 |
199 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6898E-005 |
200 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5662E-005 |
201 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2686E-003 |
202 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1636E-004 |
203 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4231E-003 |
204 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1325E-004 |
205 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2939E-003 |
206 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3238E-004 |
207 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2032E-004 |
208 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0902E-005 |
209 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.8150E-004 |
210 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1581E-004 |
211 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0529E-003 |
212 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4257E-004 |
213 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1613E-003 |
214 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9728E-004 |
215 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2112E-004 |
216 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4671E-004 |
217 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4002E-004 |
218 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3346E-005 |
219 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4086E-004 |
220 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1679E-005 |
221 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8389E-004 |
222 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6732E-005 |
223 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7473E-004 |
224 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9066E-005 |
225 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9164E-004 |
226 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7307E-003 |
227 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8278E-004 |
228 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9735E-003 |
229 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4956E-004 |
230 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6919E-003 |
231 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7498E-004 |
232 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.5506E-004 |
233 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4379E-004 |
234 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3076E-005 |
235 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2612E-004 |
236 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0636E-005 |
237 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4956E-004 |
238 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7745E-005 |
239 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7446E-004 |
240 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1536E-005 |
241 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3634E-003 |
242 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1654E-004 |
243 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3257E-003 |
244 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0811E-004 |
245 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0802E-003 |
246 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4690E-004 |
247 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2227E-003 |
248 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1450E-004 |
249 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1907E-003 |
250 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3390E-004 |
251 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1214E-003 |
252 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0294E-004 |
253 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8942E-003 |
254 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.2875E-004 |
255 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2269E-003 |
256 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1533E-004 |
257 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1228E-004 |
258 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9934E-003 |
259 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9046E-004 |
260 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9550E-003 |
261 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0790E-004 |
262 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0029E-003 |
263 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7501E-004 |
264 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6479E-003 |
265 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9448E-004 |
266 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0774E-005 |
267 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7056E-004 |
268 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8037E-005 |
269 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7332E-004 |
270 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4817E-005 |
271 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7296E-004 |
272 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1506E-005 |
273 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8613E-004 |
274 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1280E-003 |
275 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5984E-004 |
276 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.5748E-004 |
277 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4380E-004 |
278 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6607E-003 |
279 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7351E-004 |
280 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5793E-003 |
281 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1839E-004 |
282 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0189E-004 |
283 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9999E-004 |
284 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1628E-005 |
285 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2590E-003 |
286 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2571E-004 |
287 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1889E-003 |
288 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1418E-004 |
289 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.9496E-004 |
290 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8008E-004 |
291 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7056E-004 |
292 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2857E-004 |
293 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1670E-003 |
294 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8539E-004 |
295 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1930E-003 |
296 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0887E-004 |
297 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3437E-004 |
298 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4180E-004 |
299 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1319E-004 |
300 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5437E-004 |
301 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3894E-004 |
302 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7801E-004 |
303 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7289E-004 |
304 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2588E-004 |
305 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6627E-004 |
306 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1574E-004 |
307 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9433E-004 |
308 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7977E-004 |
309 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8889E-004 |
310 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5371E-004 |
311 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0178E-004 |
312 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4028E-004 |
313 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3683E-005 |
314 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0754E-005 |
315 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0928E-005 |
316 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6642E-005 |
317 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6423E-005 |
318 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8023E-005 |
319 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4795E-005 |
320 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1676E-005 |
321 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3253E-004 |
322 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7270E-005 |
323 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1366E-004 |
324 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4689E-005 |
325 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5220E-004 |
326 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9604E-005 |
327 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7264E-004 |
328 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8999E-005 |
329 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9298E-005 |
330 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7820E-004 |
331 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6089E-005 |
332 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4316E-004 |
333 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7726E-005 |
334 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4706E-004 |
335 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5891E-005 |
336 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3195E-004 |
337 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6188E-004 |
338 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1758E-004 |
339 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3062E-004 |
340 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8425E-005 |
341 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3200E-004 |
342 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0754E-004 |
343 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0257E-004 |
344 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3913E-004 |
345 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6847E-005 |
346 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3577E-005 |
347 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5087E-005 |
348 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1413E-005 |
349 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2576E-005 |
350 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4592E-005 |
351 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5813E-005 |
352 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5594E-005 |
353 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6061E-004 |
354 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.1297E-005 |
355 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9282E-004 |
356 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2420E-005 |
357 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1121E-004 |
358 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.9004E-005 |
359 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0101E-004 |
360 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0338E-005 |
361 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5890E-004 |
362 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.3210E-005 |
363 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2920E-004 |
364 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6846E-005 |
365 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3693E-004 |
366 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.2041E-005 |
367 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0246E-004 |
368 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6189E-005 |
369 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.9179E-003 |
370 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 7.0608E-004 |
371 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.3095E-003 |
372 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.3563E-004 |
373 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.0526E-003 |
374 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.0263E-004 |
375 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.9885E-003 |
376 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.2476E-004 |
377 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 7.2573E-004 |
378 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 6.6191E-003 |
379 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.7391E-004 |
380 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.5827E-003 |
381 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.1536E-004 |
382 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.4759E-003 |
383 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.1878E-004 |
384 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.0194E-003 |
385 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 5.8025E-003 |
386 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 4.1453E-004 |
387 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 4.3851E-003 |
388 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.2681E-004 |
389 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.9470E-003 |
390 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.4269E-004 |
391 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.7483E-003 |
392 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1965E-004 |
393 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.0568E-003 |
394 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.1542E-004 |
395 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.5130E-003 |
396 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.2729E-004 |
397 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.7110E-003 |
398 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.4217E-004 |
399 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.7482E-003 |
400 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.1965E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9372.92576 | 11247.51091 | 0.77938 | 0.93525 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 25.24733 | 8.40527E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 7674.98283 | 9209.97940 | 0.21758 | 0.26110 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -4.30000 | 2.65759E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 21060.17328 | 25272.20793 | 1.36510 | 1.63812 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.40000 | 8.40708E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 17531.37342 | 21037.64810 | 0.41899 | 0.50279 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -4.30000 | 2.65759E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 25.94500 | 8.40636E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 55435.06812 | 66522.08175 | 1.36902 | 1.64283 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 13495.92 | 0.93525 | 0.93525 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 9034.83 | 0.26110 | 0.26110 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 28674.18 | 1.63812 | 1.63812 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 24808.86 | 0.50279 | 0.50279 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.93525 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.63812 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.64283 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 1.64283 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 66522.07829 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 66522.08175 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.93525 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.93525 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.93525 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.93525 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.93525 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.93525 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.63812 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.63812 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.63812 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.63812 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.63812 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.63812 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.93525 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.63812 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.93525 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.93525 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1035.47149 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.93525 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.93525 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.93525 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.93525 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.93525 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.46763 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.62350 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 15481.73000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 7740.86500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15481.73000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 24359.89196 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 24359.89196 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.63812 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.63812 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1752.86206 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.63812 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.63812 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.63812 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.08116 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.63812 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.81906 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.09208 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 31630.07000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15815.03500 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79019 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79019 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31630.07000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 58029.38971 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 58029.38971 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 14756.0 | 12.15 | 11.88 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 30358.2 | 11.75 | 11.48 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1961865003 | 0.1765303986 | Pass | Pass | 0.4751452646 | 2.8791951033 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.3076490728 | 0.2908176582 | Pass | Pass | 0.6538581647 | 2.3062949628 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 5.7568394466E-005 | 1.4434930221E-004 | Pass | Pass | 5.9900047713E-002 | 6.4563792901E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:42
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7304.47 | 300.35 | 0.00 | 65.95 | 73.25 | 7744.08 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:42
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 42.00 | 35 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 40.00 | 22 | |||
Jun | 4.00 | 8 | |||
Jul | 5.00 | 4 | |||
Aug | 7.00 | 8 | |||
Sep | 17.00 | 10 | |||
Oct | 50.00 | 49 | |||
Nov | 69.00 | 59 | |||
Dec | 95.00 | 53 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:42
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.210 | 0.216 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.466 | 0.497 | 3204.84 | 3157.28 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.565 | 0.653 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.565 | 0.653 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.379_SHGC_WEST_0.38 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.153 | 0.381 | 0.420 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.379_SHGC_WEST_0.38 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.153 | 0.381 | 0.420 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.379_SHGC_NORTH_0.38 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.153 | 0.381 | 0.420 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.379_SHGC_NORTH_0.38 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.153 | 0.381 | 0.420 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 86.04 | 4.201 | 0.480 | 0.488 | |||||||||||||||||
North Total or Average | 6.51 | 2.153 | 0.381 | 0.420 | |||||||||||||||||
Non-North Total or Average | 79.53 | 4.369 | 0.488 | 0.494 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:42
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:42
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 9.3385 | 236.88 | 2212.11 | LightsWired | LTG_SCH_OFFICE | 52.33 | 168.00 | 33.21 | 0.0000 | Y | 13.79 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 7.4271 | 1393.41 | 10348.98 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 21.53 | 0.0000 | Y | 41.82 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.7674 | 3204.84 | 12073.79 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 18.60 | 0.0000 | Y | 42.15 |
Interior Lighting Total | 5.0950 | 4835.13 | 24634.88 | 97.76 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 10348.98 | 2587.24 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 10348.98 | 2587.24 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 12073.79 | 3018.45 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 12073.79 | 3018.45 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.29 | 2212.11 | 641.51 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.10 | 2212.11 | 221.21 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 123.84 | AstronomicalClock | - | 42.50 | 42.50 | 0.99 | |
EXTERIOR_LIGHTS_B | 4305.62 | AstronomicalClock | - | 83.54 | 63.02 | 50.93 | |
EXTERIOR_LIGHTS_C | 1091.36 | AstronomicalClock | - | 83.54 | 49.88 | 10.22 | |
Exterior Lighting Total | 5520.82 | 62.14 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:42
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 15481.73 | 12395.60 | 3086.13 | 0.80 | 4.12 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 31630.07 | 24993.77 | 6636.30 | 0.79 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 14756.0 | 12.15 | 11.88 | ||||
PSZ-FINE STORAGE COOLING COIL | 30358.2 | 11.75 | 11.48 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 66522.08 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 24359.89 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 58029.39 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 1.64 | 152.64 | 92.91 | 1.00 | 3.71 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 0.94 | 1035.47 | 1107.16 | 1.00 | 1.42 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 1.64 | 1752.86 | 1070.05 | 1.00 | 1.35 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:42
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9372.93 | 11247.51 | 47.48 | 0.779 | 0.935 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 23.90 | 23.90 | 0.00833 | 25.25 | 0.00841 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 21060.17 | 25272.21 | 18.14 | 1.365 | 1.638 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.70 | 26.70 | 0.00852 | 26.40 | 0.00841 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 0.00 | 29.44 | 0.00866 | 25.95 | 0.00841 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 7674.98 | 9209.98 | 38.88 | 0.218 | 0.261 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00798 | -4.30 | 0.00266 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 17531.37 | 21037.65 | 15.10 | 0.419 | 0.503 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00701 | -4.30 | 0.00266 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 55435.07 | 66522.08 | 20.76 | 1.369 | 1.643 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00640 | -4.30 | 0.00266 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.94 | 0.94 | 0.26 | 0.26 | 0.9353 | 0.9353 | 0.9353 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.64 | 1.64 | 0.50 | 0.50 | 1.6381 | 1.6381 | 1.6381 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 66522.078 | 66522.078 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 66522.08 | 66522.08 | 1.642829 | 10.00 | 8.55 | 0.00639705 | 43.33 | 22.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 10.00 | 0.00639705 | 83.1034 | 66522.08 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 15481.730 | 12395.602 | 0.935250 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 7740.86 | 7314.34 | 0.623500 | 24.97 | 16.48 | 0.00833693 | 12.00 | 11.16 | 0.00800000 | 25.37 | 0.00840546 | 16.68 | 16.4049 | 23.90 | 0.00832851 | 44.6380 | 9368.00 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 24359.892 | 24359.892 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 24359.89 | 24359.89 | 0.935251 | 18.24 | 13.12 | 0.00739523 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 10.9366 | 21.10 | 0.00797699 | 50.7109 | 7674.98 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 31630.070 | 24993.765 | 1.638120 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 15815.03 | 14746.20 | 1.092080 | 27.50 | 17.48 | 0.00849131 | 12.00 | 11.16 | 0.00800000 | 26.40 | 0.00840708 | 17.04 | 38.8901 | 26.70 | 0.00852080 | 38.6516 | 21060.17 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 58029.390 | 58029.390 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 58029.39 | 58029.39 | 1.638116 | 10.41 | 8.16 | 0.00588085 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 25.9268 | 15.56 | 0.00700904 | 63.1866 | 17531.37 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:42:42
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 66522.078 | 66522.078 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 1.642829 | 1.95722008 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 66522.08 | 66522.08 | 1.0000 | 1.95722008 | 1.642829 | 10.00 | 8.55 | 0.00639705 | 26164.9 | 43.33 | 22.02 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 66522.08 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 10.00 | 0.00639705 | 10.00 | 0.00639705 | 83.1034 | 66522.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 15481.730 | 12395.602 | 0.935250 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3379 | 1004.8586 | 1.1914 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.935251 | 1.11423205 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | Sensible | 7740.86 | 7314.34 | 1.0000 | 0.74282045 | 0.623500 | 24.97 | 16.48 | 0.00833693 | 46328.8 | 12.00 | 11.16 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7740.86 | 25.37 | 0.00840546 | 16.68 | 0.10228463 | 16.4049 | 23.90 | 0.00832851 | 23.90 | 0.00832851 | 44.6380 | 9368.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24359.892 | 24359.892 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.935251 | 1.11423205 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 24359.89 | 24359.89 | 1.0000 | 1.11423205 | 0.935251 | 18.24 | 13.12 | 0.00739523 | 37077.3 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24359.89 | -4.30 | 0.00265759 | -4.30 | 0.10228463 | 10.9366 | 21.01 | 0.00797699 | 21.10 | 0.00797699 | 50.7109 | 7674.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31630.070 | 24993.765 | 1.638120 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6249 | 1004.8586 | 1.1914 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.638116 | 1.95160612 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 15815.03 | 14746.20 | 1.0000 | 1.30107355 | 1.092080 | 27.50 | 17.48 | 0.00849131 | 49305.1 | 12.00 | 11.16 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15815.03 | 26.40 | 0.00840708 | 17.04 | 0.42471127 | 38.8901 | 26.70 | 0.00852080 | 26.70 | 0.00852080 | 38.6516 | 21060.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 58029.390 | 58029.390 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.638116 | 1.95160612 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 58029.39 | 58029.39 | 1.0000 | 1.95160612 | 1.638116 | 10.41 | 8.16 | 0.00588085 | 25281.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 58029.39 | -4.30 | 0.00265759 | -4.30 | 0.42471127 | 25.9268 | 15.56 | 0.00700904 | 15.56 | 0.00700904 | 63.1866 | 17531.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:42
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.64 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2146.50 | 3406.17 | 2096.83 |
ZONE2 FINE STORAGE | 2663.67 | 3331.33 | 2466.17 |
ZONE3 BULK STORAGE | 2736.00 | 3383.83 | 2582.83 |
Facility | 2786.33 | 3452.50 | 2587.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 65.50 | 0.00 | 61.17 | 0.00 |
ZONE2 FINE STORAGE | 159.83 | 0.00 | 10.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 219.00 | 0.00 | 64.83 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:42
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.308 | 0.256 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.432 | 0.134 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.44 | 69.00 | 35277.63 | 0.000 | 0.072 | 0.000 | 0.031 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.44 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:42:42
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.50 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.36 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.44 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.30 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1115720.76 | 0.00 | 1115720.76 | 1354166.93 | 2469887.69 | 3225648.14 | 5730.00 | 3030.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 4635538.18 | 0.00 | 4635538.18 | 3862596.58 | 8498134.76 | 13393694.68 | 5730.00 | 3027.00 | 3.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 9256655.69 | 9256655.69 | 19101695.16 | 28358350.85 | 30805497.77 | 8693.33 | 7.17 | 59.50 | 4172.83 |
Total Facility | 5751258.94 | 9256655.69 | 15007914.63 | 24318458.66 | 39326373.30 | 47424840.58 | 8717.17 | 3032.83 | 62.50 | 4172.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.0852 | 0.0000 | 0.0852 | 0.0710 | 0.1562 | 0.1023 | 606.00 | 3030.00 | 0.00 |
ZONE2 FINE STORAGE | 0.3541 | 0.0000 | 0.3541 | 0.1100 | 0.4641 | 0.4247 | 606.00 | 3027.00 | 3.00 |
ZONE3 BULK STORAGE | 0.0000 | 0.3089 | 0.3089 | 0.7069 | 1.0158 | 0.9768 | 3592.00 | 4.50 | 39.50 |
Total Facility | 0.4394 | 0.3089 | 0.7483 | 0.8878 | 1.6361 | 1.5038 | 3593.17 | 3030.17 | 42.50 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 1583617.53 | 0.00 | 1583617.53 | 3225648.14 | 5730.00 | 0.00 | 3030.00 | 0.00 |
PSZ-FINE STORAGE | 6579423.82 | 0.00 | 6579423.82 | 13393694.68 | 5730.00 | 0.00 | 3030.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1210 | 0.0000 | 0.1210 | 0.1023 | 606.00 | 0.00 | 3030.00 |
PSZ-FINE STORAGE | 0.5026 | 0.0000 | 0.5026 | 0.4247 | 606.00 | 0.00 | 3030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 3030.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 3029.17 | 0.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1452 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6032 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:42
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 446 |
Defaulted Fields | 391 |
Fields with Defaults | 1172 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:42:42
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 347.95 | 1565.96 | 16-JAN-12:00 | 28141.60 | 28-DEC-08:10 |
Electricity:Building | 234.27 | 1084.96 | 16-JAN-12:00 | 19728.80 | 02-JAN-09:10 |
Electricity:Zone:ZONE1 OFFICE | 42.95 | 520.87 | 01-JAN-00:10 | 3190.10 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 234.27 | 1084.96 | 16-JAN-12:00 | 19728.80 | 02-JAN-09:10 |
InteriorLights:Electricity | 97.76 | 615.08 | 16-JAN-12:00 | 9693.63 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 13.79 | 51.00 | 01-JAN-00:10 | 1355.05 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 97.76 | 615.08 | 16-JAN-12:00 | 9693.63 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 97.76 | 615.08 | 16-JAN-12:00 | 9693.63 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 13.79 | 51.00 | 01-JAN-00:10 | 1355.05 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 97.76 | 615.08 | 16-JAN-12:00 | 9693.63 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 41.82 | 299.97 | 01-JAN-00:10 | 3848.58 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 41.82 | 299.97 | 01-JAN-00:10 | 3848.58 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 41.82 | 299.97 | 01-JAN-00:10 | 3848.58 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 149.49 | 264.11 | 16-JAN-12:00 | 12690.12 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 42.15 | 264.11 | 16-JAN-12:00 | 4490.00 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 42.15 | 264.11 | 16-JAN-12:00 | 4490.00 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 23.67 | 0.00 | 06-JAN-18:10 | 2293.62 | 10-JAN-18:00 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 347.95 | 1565.96 | 16-JAN-12:00 | 28141.60 | 28-DEC-08:10 |
ElectricityPurchased:Plant | 347.95 | 1565.96 | 16-JAN-12:00 | 28141.60 | 28-DEC-08:10 |
Cogeneration:ElectricityPurchased | 347.95 | 1565.96 | 16-JAN-12:00 | 28141.60 | 28-DEC-08:10 |
General:Cogeneration:ElectricityPurchased | 347.95 | 1565.96 | 16-JAN-12:00 | 28141.60 | 28-DEC-08:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 347.95 | 1565.96 | 16-JAN-12:00 | 28141.60 | 28-DEC-08:10 |
ElectricityNet:Plant | 347.95 | 1565.96 | 16-JAN-12:00 | 28141.60 | 28-DEC-08:10 |
Cogeneration:ElectricityNet | 347.95 | 1565.96 | 16-JAN-12:00 | 28141.60 | 28-DEC-08:10 |
General:Cogeneration:ElectricityNet | 347.95 | 1565.96 | 16-JAN-12:00 | 28141.60 | 28-DEC-08:10 |
Electricity:HVAC | 25.37 | 0.00 | 06-JAN-18:10 | 5431.69 | 22-JUL-15:10 |
General:Fans:Electricity | 23.67 | 0.00 | 06-JAN-18:10 | 2293.62 | 10-JAN-18:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1.71 | 0.00 | 01-JAN-00:10 | 3695.07 | 22-JUL-15:10 |
General:Cooling:Electricity | 1.71 | 0.00 | 01-JAN-00:10 | 3695.07 | 22-JUL-15:10 |
ExteriorLights:Electricity | 62.14 | 0.00 | 01-JAN-08:20 | 5520.82 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 62.14 | 0.00 | 01-JAN-08:20 | 5520.82 | 01-JAN-06:10 |
Electricity:Plant | 26.17 | 481.00 | 27-APR-05:10 | 2430.67 | 10-FEB-12:20 |
WaterSystems:Electricity | 26.17 | 481.00 | 27-APR-05:10 | 2430.67 | 10-FEB-12:20 |
Water Heater:WaterSystems:Electricity | 26.17 | 481.00 | 27-APR-05:10 | 2430.67 | 10-FEB-12:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 240.18 | 0.00 | 06-JAN-18:10 | 109560.68 | 10-JAN-06:20 |
NaturalGas:HVAC | 240.18 | 0.00 | 06-JAN-18:10 | 109560.68 | 10-JAN-06:20 |
Heating:NaturalGas | 240.18 | 0.00 | 06-JAN-18:10 | 109560.68 | 10-JAN-06:20 |
General:Heating:NaturalGas | 240.18 | 0.00 | 06-JAN-18:10 | 109560.68 | 10-JAN-06:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 381.31 | 0.00 | 06-JAN-18:10 | 170177.88 | 10-JAN-06:20 |
EnergyTransfer:Building | 196.46 | 0.00 | 06-JAN-18:10 | 85488.97 | 10-JAN-06:20 |
EnergyTransfer:Zone:ZONE1 OFFICE | 31.39 | 0.00 | 01-JAN-00:10 | 17222.59 | 28-NOV-06:10 |
Heating:EnergyTransfer | 166.34 | 0.00 | 06-JAN-18:10 | 85488.97 | 10-JAN-06:20 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 24.86 | 0.00 | 01-JAN-00:10 | 17222.59 | 28-NOV-06:10 |
General:Heating:EnergyTransfer | 166.34 | 0.00 | 06-JAN-18:10 | 85488.97 | 10-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 24.86 | 0.00 | 01-JAN-00:10 | 17222.59 | 28-NOV-06:10 |
Cooling:EnergyTransfer | 30.12 | 0.00 | 01-JAN-00:10 | 12008.50 | 22-JUL-15:40 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 6.53 | 0.00 | 01-JAN-00:10 | 5872.37 | 22-JUL-16:00 |
General:Cooling:EnergyTransfer | 30.12 | 0.00 | 01-JAN-00:10 | 12008.50 | 22-JUL-15:40 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 6.53 | 0.00 | 01-JAN-00:10 | 5872.37 | 22-JUL-16:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 77.07 | 0.00 | 01-JAN-00:40 | 25035.97 | 10-JAN-06:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 53.48 | 0.00 | 01-JAN-00:40 | 25035.97 | 10-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 53.48 | 0.00 | 01-JAN-00:40 | 25035.97 | 10-JAN-06:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 23.59 | 0.00 | 01-JAN-00:10 | 6281.05 | 22-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 23.59 | 0.00 | 01-JAN-00:10 | 6281.05 | 22-JUL-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 88.01 | 0.00 | 02-JAN-08:50 | 51805.32 | 10-JAN-06:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 88.01 | 0.00 | 02-JAN-08:50 | 51805.32 | 10-JAN-06:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 88.01 | 0.00 | 02-JAN-08:50 | 51805.32 | 10-JAN-06:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 184.84 | 0.00 | 06-JAN-18:10 | 84688.91 | 10-JAN-06:20 |
HeatingCoils:EnergyTransfer | 176.74 | 0.00 | 06-JAN-18:10 | 84688.91 | 10-JAN-06:20 |
CoolingCoils:EnergyTransfer | 8.10 | 0.00 | 01-JAN-00:10 | 15767.63 | 22-JUL-15:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:42
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 24.857 | -6.529 | 0.000 | 0.000 | 10.188 | 13.790 | 29.165 | 9.870 | 0.000 | 0.018 | 0.000 | 0.000 | -7.194 | 0.000 | -17.945 | -56.219 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 53.477 | -23.592 | 0.000 | 0.000 | 28.029 | 41.819 | 0.000 | 27.122 | 0.000 | 0.013 | 0.001 | 0.000 | -12.373 | 0.000 | -39.702 | -74.792 |
ZONE3 BULK STORAGE | 88.008 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 69.038 | 42.148 | 107.344 | 374.348 | 0.000 | 0.343 | 0.000 | 0.000 | -139.416 | 0.000 | -213.205 | -328.607 |
Total Facility | 88.008 | 0.000 | 78.334 | -30.122 | 0.000 | 0.000 | 107.255 | 97.757 | 136.508 | 411.340 | 0.000 | 0.374 | 0.001 | 0.000 | -158.983 | 0.000 | -270.853 | -459.618 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 22-JUL-16:00 | 0.00 | 0.00 | 0.00 | -5872.20 | 0.00 | 0.00 | 911.96 | 826.58 | 1835.05 | 2983.31 | 0.00 | 187.34 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -872.04 |
ZONE2 FINE STORAGE | 22-JUL-15:10 | 0.00 | 0.00 | 0.00 | -6280.78 | 0.00 | 0.00 | 1708.70 | 2263.80 | 0.00 | 4689.96 | 0.00 | 584.09 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2965.77 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-JUL-15:40 | 0.00 | 0.00 | 0.00 | -12007.80 | 0.00 | 0.00 | 6085.47 | 5354.19 | 10035.17 | 62394.36 | 0.00 | 2256.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -74117.45 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 28-NOV-06:32 | 0.00 | 0.00 | 25524.69 | 0.00 | 0.00 | 0.00 | 135.33 | 404.75 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -556.97 | 0.00 | -1485.99 | -24572.33 |
ZONE2 FINE STORAGE | 10-JAN-06:03 | 0.00 | 0.00 | 59180.66 | 0.00 | 0.00 | 0.00 | 365.72 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1121.13 | 0.00 | -4190.05 | -54535.18 |
ZONE3 BULK STORAGE | 10-JAN-05:53 | 51815.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -16716.10 | 0.00 | -20494.87 | -17183.04 |
Total Facility | 28-DEC-06:42 | 44322.26 | 0.00 | 81731.51 | 0.00 | 0.00 | 0.00 | 1413.78 | 1385.75 | 2600.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -14425.35 | 0.00 | -30782.22 | -86246.27 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:42
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9353 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9353 | 0.1094 | 1.0000 | Not calculated | 0.1023 | 0.1094 | ||
PSZ-FINE STORAGE | 1.6381 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.6381 | 0.2593 | 1.0000 | Not calculated | 0.4247 | 0.2593 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9353 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9353 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.1094 | ||
PSZ-FINE STORAGE | 1.6381 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.6381 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.2593 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9353 | 0.9353 | 0.9353 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6381 | 1.6381 | 1.6381 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9353 | 0.9353 | 0.9353 | 0.9353 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.6381 | 1.6381 | 1.6381 | 1.6381 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9353 | 0.9353 | 0.9353 | No | 0.1023 | 0.3917 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6381 | 1.6381 | 1.6381 | No | 0.4247 | 0.8447 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9353 | 0.9353 | 0.9353 | 0.9353 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.6381 | 1.6381 | 1.6381 | 1.6381 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:42
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 64.83 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 64.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 240.18 | 109560.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1.71 | 3695.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 97.76 | 9693.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 62.14 | 5520.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 23.67 | 2293.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.17 | 2430.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 347.95 |
Natural Gas | 0.00 | 240.18 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 588.14 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 20.22 |
Space Heating | 0.00 |
Space Cooling | 0.35 |
Fans (All) | 4.89 |
Service Water Heating | 5.41 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 71.96 |
Subtotal | 71.96 |
Natural Gas [MJ/m2] | |
Space Heating | 49.67 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 49.67 |
Subtotal | 49.67 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 16.62 |
Space Heating | 40.84 |
Space Cooling | 0.29 |
Fans (All) | 4.02 |
Service Water Heating | 4.45 |
Receptacle Equipment | 23.21 |
Miscellaneous | 10.57 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2729. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:42
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8752.83 | 7.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8748.17 | 11.83 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8746.83 | 13.17 | 0.00 | 0.00 | 0.00 |
Min | 8746.83 | 7.17 | 0.00 | 0.00 | 0.00 |
Max | 8752.83 | 13.17 | 0.00 | 0.00 | 0.00 |
Average | 8749.28 | 10.72 | 0.00 | 0.00 | 0.00 |
Sum | 26247.83 | 32.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 82584.00 | 135.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 190479.17 | 713.83 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 190479.17 | 713.83 | 0.00 | 0.00 | 0.00 |
Average | 102030.06 | 282.94 | 0.00 | 0.00 | 0.00 |
Sum | 306090.17 | 848.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8750.67 | 9.33 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8703.00 | 57.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8725.00 | 35.00 | 0.00 | 0.00 | 0.00 |
Min | 8703.00 | 9.33 | 0.00 | 0.00 | 0.00 |
Max | 8750.67 | 57.00 | 0.00 | 0.00 | 0.00 |
Average | 8726.22 | 33.78 | 0.00 | 0.00 | 0.00 |
Sum | 26178.67 | 101.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 81494.00 | 1225.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 189398.17 | 1794.83 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 189398.17 | 1794.83 | 0.00 | 0.00 | 0.00 |
Average | 101306.39 | 1006.61 | 0.00 | 0.00 | 0.00 |
Sum | 303919.17 | 3019.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:42
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:42
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Environment
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Environment
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.92 | 1.45 | 0.497165E+09 | 603.25 | 07-JAN-08:09 | 3.17 | 2.18 |
February | 366618.82 | 475.00 | 04-FEB-15:30 | 8.00 | 6.08 | 0.457411E+09 | 603.25 | 10-FEB-08:09 | 4.33 | 4.19 |
March | 985281.39 | 193.05 | 25-MAR-15:00 | 11.00 | 9.40 | 0.537073E+09 | 614.63 | 25-MAR-13:39 | 11.00 | 9.40 |
April | 0.136740E+09 | 2483.04 | 29-APR-15:50 | 20.00 | 12.39 | 0.524515E+09 | 768.97 | 29-APR-15:20 | 20.00 | 12.39 |
May | 0.317524E+09 | 2445.43 | 25-MAY-16:00 | 18.00 | 13.90 | 0.565127E+09 | 768.99 | 23-MAY-15:09 | 18.00 | 13.90 |
June | 0.109611E+10 | 4578.73 | 13-JUN-16:00 | 26.50 | 17.70 | 0.634060E+09 | 768.99 | 27-JUN-10:00 | 13.00 | 13.00 |
July | 0.196284E+10 | 5872.37 | 22-JUL-16:00 | 29.00 | 16.57 | 0.627145E+09 | 769.00 | 18-JUL-08:00 | 29.00 | 16.57 |
August | 0.210950E+10 | 4441.47 | 14-AUG-16:00 | 26.00 | 15.86 | 0.680300E+09 | 769.00 | 17-AUG-09:30 | 19.50 | 16.05 |
September | 0.850003E+09 | 3456.26 | 13-SEP-16:00 | 23.00 | 16.22 | 0.611328E+09 | 768.99 | 12-SEP-14:09 | 23.00 | 16.22 |
October | 51617784.51 | 782.37 | 07-OCT-16:00 | 18.00 | 9.66 | 0.516908E+09 | 768.96 | 07-OCT-15:00 | 18.00 | 9.66 |
November | 3651127.95 | 318.46 | 10-NOV-16:20 | 9.67 | 7.83 | 0.477488E+09 | 617.38 | 10-NOV-15:39 | 9.67 | 7.83 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.00 | 3.53 | 0.497166E+09 | 603.25 | 30-DEC-08:09 | 0.00 | -2.2 |
Annual Sum or Average | 0.652934E+10 | 0.662569E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | 1.92 | 1.45 | 0.457411E+09 | 603.25 | 0.00 | -2.2 | ||
Maximum of Months | 0.210950E+10 | 5872.37 | 29.00 | 17.70 | 0.680300E+09 | 769.00 | 29.00 | 16.57 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115457E+10 | 4799.64 | 21-JAN-10:50 | 4.85 | 4.39 | 0.659646E+09 | 912.75 | 19-JAN-15:09 | 4.85 | 4.39 |
February | 0.158567E+10 | 4718.95 | 23-FEB-15:40 | 4.67 | 4.34 | 0.605774E+09 | 902.73 | 27-FEB-16:10 | 8.00 | 6.56 |
March | 0.212372E+10 | 4277.13 | 14-MAR-14:10 | 5.67 | 2.77 | 0.724158E+09 | 993.23 | 25-MAR-13:20 | 13.33 | 10.57 |
April | 0.244967E+10 | 4872.62 | 12-APR-07:10 | 4.50 | 3.00 | 0.874896E+09 | 1723.70 | 29-APR-15:09 | 20.00 | 12.69 |
May | 0.282679E+10 | 5550.71 | 01-MAY-15:00 | 8.00 | 6.98 | 0.100731E+10 | 1727.73 | 22-MAY-15:30 | 23.50 | 15.68 |
June | 0.262288E+10 | 5075.78 | 07-JUN-10:00 | 7.00 | 6.47 | 0.131098E+10 | 2205.56 | 13-JUN-15:00 | 26.50 | 17.70 |
July | 0.246077E+10 | 6281.05 | 22-JUL-15:10 | 29.00 | 16.93 | 0.145102E+10 | 2246.81 | 22-JUL-12:09 | 29.00 | 16.93 |
August | 0.209109E+10 | 4216.27 | 19-AUG-07:10 | 12.67 | 11.93 | 0.157768E+10 | 2169.88 | 14-AUG-15:00 | 12.67 | 11.93 |
September | 0.189664E+10 | 5171.71 | 28-SEP-07:05 | 8.17 | 7.16 | 0.122114E+10 | 1959.15 | 13-SEP-15:09 | 8.17 | 7.16 |
October | 0.199003E+10 | 5745.52 | 06-OCT-07:10 | 3.83 | 3.69 | 0.806740E+09 | 1427.79 | 07-OCT-15:20 | 18.67 | 9.96 |
November | 0.165610E+10 | 4207.37 | 28-NOV-12:00 | 6.00 | 3.78 | 0.646188E+09 | 987.89 | 10-NOV-14:20 | 6.00 | 3.78 |
December | 0.733695E+09 | 4356.11 | 01-DEC-10:10 | 5.00 | 4.09 | 0.650621E+09 | 833.35 | 21-DEC-14:50 | 8.00 | 6.98 |
Annual Sum or Average | 0.235916E+11 | 0.115362E+11 | ||||||||
Minimum of Months | 0.733695E+09 | 4207.37 | 3.83 | 2.77 | 0.605774E+09 | 833.35 | 4.85 | 3.78 | ||
Maximum of Months | 0.282679E+10 | 6281.05 | 29.00 | 16.93 | 0.157768E+10 | 2246.81 | 29.00 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.92 | 1.45 | 0.758589E+09 | 1231.96 | 19-JAN-15:39 | 8.33 | 7.46 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 | 5.79 | 0.732644E+09 | 1228.78 | 27-FEB-16:19 | 8.00 | 6.64 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 3.80 | 3.71 | 0.962732E+09 | 1515.79 | 25-MAR-13:30 | 13.00 | 10.25 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 | 1.84 | 0.170514E+10 | 3577.71 | 29-APR-15:30 | 20.00 | 12.54 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 | 8.15 | 0.216241E+10 | 3581.72 | 26-MAY-15:20 | 15.33 | 12.61 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 | 7.39 | 0.292231E+10 | 4796.15 | 26-JUN-15:20 | 22.67 | 17.34 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 | 9.95 | 0.333622E+10 | 5633.11 | 22-JUL-15:30 | 29.00 | 16.79 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 | 9.82 | 0.362670E+10 | 4871.92 | 21-AUG-14:09 | 21.00 | 15.01 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 | 10.95 | 0.265685E+10 | 4128.13 | 13-SEP-15:20 | 23.00 | 16.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 | 5.83 | 0.154403E+10 | 2905.05 | 02-OCT-15:39 | 14.00 | 10.13 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 | 4.29 | 0.850917E+09 | 1507.46 | 10-NOV-14:39 | 12.00 | 8.58 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.00 | 3.53 | 0.704269E+09 | 1045.22 | 21-DEC-14:00 | 8.00 | 6.98 |
Annual Sum or Average | 0.00 | 0.219628E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 1.92 | 1.45 | 0.704269E+09 | 1045.22 | 8.00 | 6.64 | ||
Maximum of Months | 0.00 | 0.00 | 12.43 | 10.95 | 0.362670E+10 | 5633.11 | 29.00 | 17.34 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.430401E+10 | 24973.10 | 10-JAN-06:22 | -4.0 |
February | 0.369026E+10 | 24964.83 | 13-FEB-06:12 | -1.0 |
March | 0.388087E+10 | 24940.45 | 06-MAR-06:12 | 4.00 |
April | 0.161921E+10 | 24777.72 | 03-APR-05:12 | 3.67 |
May | 0.110560E+10 | 24681.36 | 10-MAY-05:01 | 3.50 |
June | 0.248514E+09 | 24602.19 | 08-JUN-05:01 | 6.17 |
July | 0.124497E+09 | 24384.08 | 05-JUL-05:01 | 7.33 |
August | 93100193.78 | 1200.76 | 30-AUG-06:10 | 9.50 |
September | 0.277922E+09 | 24220.79 | 07-SEP-05:02 | 8.83 |
October | 0.178548E+10 | 24777.08 | 23-OCT-05:12 | 3.33 |
November | 0.325882E+10 | 25524.56 | 28-NOV-06:32 | 1.00 |
December | 0.446901E+10 | 24984.38 | 26-DEC-06:22 | 1.95 |
Annual Sum or Average | 0.248573E+11 | |||
Minimum of Months | 93100193.78 | 1200.76 | -4.0 | |
Maximum of Months | 0.446901E+10 | 25524.56 | 9.50 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113774E+11 | 59180.72 | 10-JAN-06:03 | -4.0 |
February | 0.993943E+10 | 59089.55 | 18-FEB-06:22 | -1.5 |
March | 0.715180E+10 | 58812.73 | 16-MAR-05:01 | 1.08 |
April | 0.942505E+09 | 57170.21 | 03-APR-05:01 | 3.83 |
May | 0.117667E+09 | 15577.95 | 06-MAY-05:13 | 2.33 |
June | 61454045.60 | 1012.66 | 13-JUN-17:00 | 27.00 |
July | 57652043.54 | 736.60 | 29-JUL-07:00 | 13.00 |
August | 59163330.18 | 1160.76 | 14-AUG-17:00 | 27.00 |
September | 54333064.27 | 729.34 | 27-SEP-06:50 | 9.67 |
October | 0.162407E+10 | 58820.52 | 19-OCT-05:08 | 6.67 |
November | 0.774806E+10 | 58845.20 | 28-NOV-06:01 | 1.00 |
December | 0.143436E+11 | 58835.20 | 28-DEC-06:01 | 1.00 |
Annual Sum or Average | 0.534771E+11 | |||
Minimum of Months | 54333064.27 | 729.34 | -4.0 | |
Maximum of Months | 0.143436E+11 | 59180.72 | 27.00 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232297E+11 | 51815.81 | 10-JAN-05:53 | -4.0 |
February | 0.169005E+11 | 39037.29 | 17-FEB-04:00 | -2.0 |
March | 0.406828E+10 | 21183.42 | 04-MAR-06:00 | 3.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.743193E+10 | 34341.10 | 29-NOV-03:57 | -1.0 |
December | 0.363780E+11 | 51340.96 | 30-DEC-01:00 | -2.0 |
Annual Sum or Average | 0.880085E+11 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 0.363780E+11 | 51815.81 | 12.43 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.127139E+10 | 1355.05 | 02-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.110373E+10 | 1355.05 | 01-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.124946E+10 | 1355.05 | 01-MAR-08:09 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.104822E+10 | 1355.05 | 10-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.107499E+10 | 1355.05 | 04-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.105576E+10 | 1224.06 | 05-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.102671E+10 | 1355.05 | 07-JUL-07:30 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.112962E+10 | 1355.05 | 08-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.109137E+10 | 1355.05 | 01-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.118829E+10 | 1355.05 | 02-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.122552E+10 | 1355.05 | 01-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.132509E+10 | 1355.05 | 01-DEC-08:09 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.137901E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.102671E+10 | 1224.06 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.132509E+10 | 1355.05 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.392732E+10 | 3848.58 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.340669E+10 | 3848.58 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.371686E+10 | 3848.58 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.317302E+10 | 3848.58 | 03-APR-08:09 | 0.00 | 0.00 |
May | 0.316736E+10 | 3527.86 | 02-MAY-08:09 | 0.00 | 0.00 |
June | 0.303459E+10 | 3527.86 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.305168E+10 | 3527.86 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.339369E+10 | 3848.58 | 08-AUG-08:09 | 0.00 | 0.00 |
September | 0.345916E+10 | 3848.58 | 02-SEP-08:09 | 0.00 | 0.00 |
October | 0.371705E+10 | 3848.58 | 03-OCT-08:09 | 0.00 | 0.00 |
November | 0.376381E+10 | 3848.58 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.400771E+10 | 3848.58 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.418189E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.303459E+10 | 3527.86 | 0.00 | 0.00 | |
Maximum of Months | 0.400771E+10 | 3848.58 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.426583E+10 | 4490.00 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.352760E+10 | 4490.00 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.358435E+10 | 3961.65 | 03-MAR-16:49 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.306560E+10 | 3961.65 | 10-APR-07:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.304112E+10 | 3169.37 | 01-MAY-06:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.295136E+10 | 3169.37 | 17-JUN-06:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.293411E+10 | 2971.24 | 07-JUL-07:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.322489E+10 | 3741.67 | 08-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.327727E+10 | 3961.65 | 08-SEP-07:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.370132E+10 | 4490.00 | 20-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.405552E+10 | 4490.00 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.451923E+10 | 4490.00 | 01-DEC-14:50 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.421482E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.293411E+10 | 2971.24 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.451923E+10 | 4490.00 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.127139E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163419E+10 |
February | 0.127628E+10 | 0.110373E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159539E+10 |
March | 0.149825E+10 | 0.124946E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156151E+10 |
April | 0.138726E+10 | 0.104822E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6327.68 | 0.118958E+10 |
May | 0.144276E+10 | 0.107499E+10 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2433.65 | 0.181641E+10 |
June | 0.144276E+10 | 0.105576E+10 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4848227.95 | 0.145220E+10 |
July | 0.138726E+10 | 0.102671E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10008896.75 | 0.126007E+10 |
August | 0.149825E+10 | 0.112962E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3394828.68 | 0.112048E+10 |
September | 0.138726E+10 | 0.109137E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113589E+10 |
October | 0.138726E+10 | 0.118829E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134572E+10 |
November | 0.133177E+10 | 0.122552E+10 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171333E+10 |
December | 0.138726E+10 | 0.132509E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212043E+10 |
Annual Sum or Average | 0.168137E+11 | 0.137901E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18260714.71 | 0.179452E+11 |
Minimum of Months | 0.127628E+10 | 0.102671E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112048E+10 |
Maximum of Months | 0.149825E+10 | 0.132509E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10008896.75 | 0.212043E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.392732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205170E+10 |
February | 0.300332E+10 | 0.340669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284392E+10 |
March | 0.352563E+10 | 0.371686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179878E+10 |
April | 0.326447E+10 | 0.317302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 994343.64 | 0.191415E+10 |
May | 0.339505E+10 | 0.316736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263054.69 | 0.492400E+10 |
June | 0.339505E+10 | 0.303459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1485487.17 | 0.440630E+10 |
July | 0.326447E+10 | 0.305168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8676846.95 | 0.435537E+10 |
August | 0.352563E+10 | 0.339369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1666599.53 | 0.351574E+10 |
September | 0.326447E+10 | 0.345916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299923E+10 |
October | 0.326447E+10 | 0.371705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249652E+10 |
November | 0.313390E+10 | 0.376381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337642E+10 |
December | 0.326447E+10 | 0.400771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502029E+10 |
Annual Sum or Average | 0.395654E+11 | 0.418189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13086331.98 | 0.397024E+11 |
Minimum of Months | 0.300332E+10 | 0.303459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179878E+10 |
Maximum of Months | 0.352563E+10 | 0.400771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8676846.95 | 0.502029E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.426583E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41803793.40 | 0.559439E+10 |
February | 0.690763E+10 | 0.352760E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739359E+10 |
March | 0.810895E+10 | 0.358435E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2046971.66 | 0.475273E+10 |
April | 0.750829E+10 | 0.306560E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14886498.10 | 0.762223E+10 |
May | 0.780862E+10 | 0.304112E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27627547.32 | 0.211290E+11 |
June | 0.780862E+10 | 0.295136E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33004855.68 | 0.195022E+11 |
July | 0.750829E+10 | 0.293411E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32158240.16 | 0.195529E+11 |
August | 0.810895E+10 | 0.322489E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11188280.38 | 0.161164E+11 |
September | 0.750829E+10 | 0.327727E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6291905.12 | 0.128229E+11 |
October | 0.750829E+10 | 0.370132E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.865948E+10 |
November | 0.720796E+10 | 0.405552E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44554989.16 | 0.772814E+10 |
December | 0.750829E+10 | 0.451923E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18444939.47 | 0.121278E+11 |
Annual Sum or Average | 0.910005E+11 | 0.421482E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232008E+09 | 0.143002E+12 |
Minimum of Months | 0.690763E+10 | 0.293411E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475273E+10 |
Maximum of Months | 0.810895E+10 | 0.451923E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44554989.16 | 0.211290E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1355.05 | 02-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 7046.75 | 10-JAN-18:00 |
February | 1680.92 | 01-FEB-08:09 | 1355.05 | 01-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 5790.09 | 17-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 1355.05 | 01-MAR-08:09 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 5493.02 | 31-MAR-07:00 |
April | 1680.92 | 01-APR-07:10 | 1355.05 | 10-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.81 | 30-APR-15:00 | 4380.14 | 11-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 1355.05 | 04-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 22-MAY-15:00 | 4825.78 | 05-MAY-07:00 |
June | 1680.92 | 01-JUN-07:10 | 1224.06 | 05-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 777.58 | 13-JUN-17:00 | 3993.44 | 08-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 1355.05 | 07-JUL-07:30 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1203.49 | 21-JUL-17:00 | 3103.38 | 05-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 1355.05 | 08-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 757.14 | 14-AUG-17:00 | 3058.48 | 24-AUG-06:10 |
September | 1680.92 | 01-SEP-07:10 | 1355.05 | 01-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 3936.54 | 20-SEP-06:10 |
October | 1680.92 | 02-OCT-07:10 | 1355.05 | 02-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4774.64 | 04-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 1355.05 | 01-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6200.24 | 29-NOV-08:00 |
December | 1680.92 | 01-DEC-08:09 | 1355.05 | 01-DEC-08:09 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6337.43 | 28-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1224.06 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3058.48 | |||||
Maximum of Months | 1680.92 | 1355.05 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 1203.49 | 7046.75 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3848.58 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 7181.69 | 10-JAN-18:00 |
February | 3955.50 | 01-FEB-08:09 | 3848.58 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4535.64 | 01-FEB-16:10 |
March | 3955.50 | 01-MAR-08:09 | 3848.58 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 7242.05 | 31-MAR-08:00 |
April | 3955.50 | 01-APR-07:10 | 3848.58 | 03-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.56 | 30-APR-19:00 | 3791.65 | 24-APR-15:10 |
May | 3955.50 | 01-MAY-07:10 | 3527.86 | 02-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.64 | 22-MAY-15:10 | 8654.35 | 01-MAY-15:05 |
June | 3955.50 | 01-JUN-07:10 | 3527.86 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.93 | 12-JUN-18:00 | 5827.23 | 07-JUN-15:05 |
July | 3955.50 | 01-JUL-07:10 | 3527.86 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 584.09 | 22-JUL-15:10 | 5284.15 | 30-JUL-19:00 |
August | 3955.50 | 01-AUG-07:10 | 3848.58 | 08-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.11 | 14-AUG-18:00 | 5497.09 | 22-AUG-16:00 |
September | 3955.50 | 01-SEP-07:10 | 3848.58 | 02-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 5197.59 | 29-SEP-15:10 |
October | 3955.50 | 02-OCT-07:10 | 3848.58 | 03-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4389.32 | 01-OCT-24:00 |
November | 3955.50 | 01-NOV-07:10 | 3848.58 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6477.05 | 15-NOV-07:10 |
December | 3955.50 | 01-DEC-08:09 | 3848.58 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 10545.41 | 02-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3527.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3791.65 | ||||
Maximum of Months | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 584.09 | 10545.41 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 4490.00 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3723.79 | 29-JAN-06:00 | 21411.51 | 10-JAN-16:00 |
February | 9097.65 | 01-FEB-08:09 | 4490.00 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 11006.32 | 19-FEB-22:00 |
March | 9097.65 | 01-MAR-08:09 | 3961.65 | 03-MAR-16:49 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 383.95 | 19-MAR-12:00 | 17871.94 | 31-MAR-08:00 |
April | 9097.65 | 01-APR-07:10 | 3961.65 | 10-APR-07:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1134.65 | 30-APR-19:00 | 14652.52 | 24-APR-12:10 |
May | 9097.65 | 01-MAY-07:10 | 3169.37 | 01-MAY-06:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2203.24 | 22-MAY-15:00 | 34437.30 | 01-MAY-13:00 |
June | 9097.65 | 01-JUN-07:10 | 3169.37 | 17-JUN-06:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2007.05 | 13-JUN-16:00 | 24094.67 | 07-JUN-15:00 |
July | 9097.65 | 01-JUL-07:10 | 2971.24 | 07-JUL-07:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1614.75 | 22-JUL-19:00 | 20608.01 | 30-JUL-19:00 |
August | 9097.65 | 01-AUG-07:10 | 3741.67 | 08-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1606.33 | 14-AUG-18:00 | 22669.42 | 22-AUG-16:00 |
September | 9097.65 | 01-SEP-07:10 | 3961.65 | 08-SEP-07:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 639.86 | 24-SEP-16:00 | 17334.91 | 19-SEP-15:00 |
October | 9097.65 | 02-OCT-07:10 | 4490.00 | 20-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 15636.69 | 01-OCT-24:00 |
November | 9097.65 | 01-NOV-07:10 | 4490.00 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5667.39 | 24-NOV-11:50 | 12887.85 | 28-NOV-08:70 |
December | 9097.65 | 01-DEC-08:09 | 4490.00 | 01-DEC-14:50 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5322.05 | 23-DEC-11:00 | 17744.47 | 28-DEC-08:70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 2971.24 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11006.32 | |||||
Maximum of Months | 9097.65 | 4490.00 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 5667.39 | 34437.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 152.99 | 1409.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.10 |
February | 475.00 | 04-FEB-15:30 | 1680.92 | 871.75 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.83 |
March | 193.05 | 25-MAR-15:00 | 1680.92 | 1178.89 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.53 |
April | 2483.04 | 29-APR-15:50 | 1680.92 | 826.58 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.11 |
May | 2445.43 | 25-MAY-16:00 | 1680.92 | 826.58 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.74 |
June | 4578.73 | 13-JUN-16:00 | 1680.92 | 826.58 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 222.62 | 0.00 |
July | 5872.37 | 22-JUL-16:00 | 1680.92 | 826.58 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 187.34 | 0.00 |
August | 4441.47 | 14-AUG-16:00 | 1680.92 | 826.58 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 165.62 | 0.00 |
September | 3456.26 | 13-SEP-16:00 | 1680.92 | 826.58 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.40 |
October | 782.37 | 07-OCT-16:00 | 1680.92 | 871.75 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 318.46 | 10-NOV-16:20 | 1680.92 | 1355.05 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 637.70 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 101.99 | 939.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 101.99 | 939.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5872.37 | 1680.92 | 1355.05 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 222.62 | 637.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4799.64 | 21-JAN-10:50 | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.52 |
February | 4718.95 | 23-FEB-15:40 | 3955.50 | 3207.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 685.03 |
March | 4277.13 | 14-MAR-14:10 | 3955.50 | 2245.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 808.97 |
April | 4872.62 | 12-APR-07:10 | 3955.50 | 3395.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5550.71 | 01-MAY-15:00 | 3955.50 | 2245.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3513.02 |
June | 5075.78 | 07-JUN-10:00 | 3955.50 | 2886.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2157.07 |
July | 6281.05 | 22-JUL-15:10 | 3955.50 | 2263.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 584.09 | 0.00 |
August | 4216.27 | 19-AUG-07:10 | 3955.50 | 3395.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2242.35 |
September | 5171.71 | 28-SEP-07:05 | 7911.00 | 6791.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5745.52 | 06-OCT-07:10 | 3955.50 | 3395.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4207.37 | 28-NOV-12:00 | 3955.50 | 3207.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4356.11 | 01-DEC-10:10 | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 572.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4207.37 | 3955.50 | 2245.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6281.05 | 7911.00 | 6791.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 584.09 | 3513.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 1584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2687.51 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 1056.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2099.28 |
March | 0.00 | 01-MAR-00:05 | 0.00 | 1056.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2765.83 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6323.32 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8156.51 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13899.64 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6551.82 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7462.74 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 528.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10252.42 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3660.87 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 1056.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2142.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 528.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 1584.69 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13899.64 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.327018E+11 | 28081.36 | 10-JAN-16:49 | 0.565519E+11 | 109560.68 | 10-JAN-06:19 |
February | 0.284464E+11 | 23227.35 | 01-FEB-09:09 | 0.439241E+11 | 80436.79 | 18-FEB-06:10 |
March | 0.306186E+11 | 22549.72 | 15-MAR-08:09 | 0.236032E+11 | 56312.73 | 04-MAR-06:19 |
April | 0.267275E+11 | 22416.98 | 10-APR-08:09 | 0.384231E+10 | 28262.15 | 11-APR-05:10 |
May | 0.266533E+11 | 21139.30 | 04-MAY-07:10 | 0.165560E+10 | 18772.25 | 20-MAY-05:10 |
June | 0.260292E+11 | 20904.38 | 13-JUN-08:09 | 0.205356E+09 | 10968.28 | 08-JUN-05:10 |
July | 0.261046E+11 | 22803.33 | 22-JUL-14:00 | 51799834.21 | 8475.61 | 05-JUL-05:10 |
August | 0.284684E+11 | 22934.50 | 08-AUG-08:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.279516E+11 | 22386.87 | 08-SEP-08:09 | 0.240258E+09 | 7535.98 | 07-SEP-05:10 |
October | 0.299364E+11 | 23167.66 | 31-OCT-08:09 | 0.514844E+10 | 27728.16 | 23-OCT-05:10 |
November | 0.308360E+11 | 27781.57 | 28-NOV-16:49 | 0.273394E+11 | 82189.58 | 28-NOV-06:10 |
December | 0.334789E+11 | 28141.60 | 28-DEC-08:09 | 0.776225E+11 | 95451.06 | 28-DEC-07:10 |
Annual Sum or Average | 0.347953E+12 | 0.240185E+12 | ||||
Minimum of Months | 0.260292E+11 | 20904.38 | 0.00 | 0.00 | ||
Maximum of Months | 0.334789E+11 | 28141.60 | 0.776225E+11 | 109560.68 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.946455E+10 | 0.733037E+10 | 0.112984E+11 | 0.00 | 0.236369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224479E+10 | 0.00 |
February | 0.803802E+10 | 0.586071E+10 | 0.103734E+11 | 0.00 | 0.212795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204629E+10 | 0.00 |
March | 0.855067E+10 | 0.544556E+10 | 0.121089E+11 | 0.00 | 0.220574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230774E+10 | 0.00 |
April | 0.728684E+10 | 0.421817E+10 | 0.112578E+11 | 0.00 | 0.176788E+10 | 0.00 | 0.00 | 18324751.25 | 0.00 | 0.00 | 0.00 | 0.217857E+10 | 0.00 |
May | 0.728346E+10 | 0.359021E+10 | 0.117000E+11 | 0.00 | 0.180609E+10 | 0.00 | 0.00 | 41776503.83 | 0.00 | 0.00 | 0.00 | 0.223177E+10 | 0.00 |
June | 0.704170E+10 | 0.311401E+10 | 0.116594E+11 | 0.00 | 0.179156E+10 | 0.00 | 0.00 | 0.265173E+09 | 0.00 | 0.00 | 0.00 | 0.215740E+10 | 0.00 |
July | 0.701251E+10 | 0.334938E+10 | 0.112984E+11 | 0.00 | 0.172063E+10 | 0.00 | 0.00 | 0.569286E+09 | 0.00 | 0.00 | 0.00 | 0.215441E+10 | 0.00 |
August | 0.774819E+10 | 0.397180E+10 | 0.121016E+11 | 0.00 | 0.185679E+10 | 0.00 | 0.00 | 0.584353E+09 | 0.00 | 0.00 | 0.00 | 0.220576E+10 | 0.00 |
September | 0.782781E+10 | 0.481213E+10 | 0.112504E+11 | 0.00 | 0.172311E+10 | 0.00 | 0.00 | 0.226619E+09 | 0.00 | 0.00 | 0.00 | 0.211150E+10 | 0.00 |
October | 0.860667E+10 | 0.605506E+10 | 0.113057E+11 | 0.00 | 0.178814E+10 | 0.00 | 0.00 | 1562462.48 | 0.00 | 0.00 | 0.00 | 0.217925E+10 | 0.00 |
November | 0.904485E+10 | 0.680625E+10 | 0.108562E+11 | 0.00 | 0.200105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212767E+10 | 0.00 |
December | 0.985202E+10 | 0.758543E+10 | 0.112984E+11 | 0.00 | 0.251525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222781E+10 | 0.00 |
Annual Sum or Average | 0.977573E+11 | 0.621391E+11 | 0.136508E+12 | 0.00 | 0.236679E+11 | 0.00 | 0.00 | 0.170710E+10 | 0.00 | 0.00 | 0.00 | 0.261730E+11 | 0.00 |
Minimum of Months | 0.701251E+10 | 0.311401E+10 | 0.103734E+11 | 0.00 | 0.172063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204629E+10 | 0.00 |
Maximum of Months | 0.985202E+10 | 0.758543E+10 | 0.121089E+11 | 0.00 | 0.251525E+10 | 0.00 | 0.00 | 0.584353E+09 | 0.00 | 0.00 | 0.00 | 0.230774E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.565519E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.439241E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.236032E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.384231E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.165560E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.205356E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 51799834.21 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.240258E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.514844E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.273394E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.776225E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.240185E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.776225E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 9693.63 | 02-JAN-09:09 | 5520.82 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 2293.62 | 10-JAN-17:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 9693.63 | 01-FEB-09:09 | 5520.82 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 2149.73 | 18-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 8945.30 | 13-MAR-08:09 | 5520.82 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 2038.03 | 04-MAR-07:19 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 8945.30 | 10-APR-08:09 | 5520.82 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 1820.89 | 12-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 7722.00 | 04-MAY-07:10 | 4975.14 | 01-MAY-19:19 | 10035.17 | 01-MAY-07:10 | 0.00 | 1787.31 | 06-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 7129.88 | 01-JUN-07:10 | 4975.14 | 01-JUN-19:00 | 10035.17 | 01-JUN-07:10 | 0.00 | 1736.62 | 01-JUN-06:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 7722.00 | 07-JUL-07:30 | 4975.14 | 01-JUL-20:19 | 10035.17 | 01-JUL-07:10 | 0.00 | 1736.62 | 21-JUL-13:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 8945.30 | 08-AUG-08:09 | 5520.82 | 14-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 1736.62 | 01-AUG-07:19 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 8945.30 | 08-SEP-08:09 | 5520.82 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 1736.62 | 01-SEP-08:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 9693.63 | 20-OCT-08:09 | 5520.82 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 1866.52 | 28-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 9693.63 | 01-NOV-08:09 | 5520.82 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 2177.31 | 29-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 9693.63 | 01-DEC-14:50 | 5520.82 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 2224.21 | 28-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 7129.88 | 4975.14 | 10035.17 | 0.00 | 1736.62 | 0.00 | 0.00 | |||||
Maximum of Months | 9693.63 | 5520.82 | 10035.17 | 0.00 | 2293.62 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2422.33 | 30-JAN-12:09 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2430.67 | 10-FEB-12:20 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2423.62 | 01-MAR-12:30 | 0.00 |
April | 658.03 | 29-APR-15:50 | 0.00 | 0.00 | 0.00 | 2365.51 | 01-APR-11:30 | 0.00 |
May | 705.53 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 | 2256.84 | 03-MAY-11:20 | 0.00 |
June | 1379.60 | 13-JUN-15:00 | 0.00 | 0.00 | 0.00 | 2133.00 | 01-JUN-11:20 | 0.00 |
July | 3695.07 | 22-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1997.57 | 07-JUL-11:00 | 0.00 |
August | 1265.49 | 14-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1948.86 | 31-AUG-11:39 | 0.00 |
September | 1018.18 | 13-SEP-15:00 | 0.00 | 0.00 | 0.00 | 2016.28 | 30-SEP-11:39 | 0.00 |
October | 244.45 | 07-OCT-15:39 | 0.00 | 0.00 | 0.00 | 2117.16 | 26-OCT-11:00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2241.06 | 25-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2363.80 | 30-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1948.86 | 0.00 | ||
Maximum of Months | 3695.07 | 0.00 | 0.00 | 0.00 | 2430.67 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 28081.36 | 10-JAN-16:49 | 8712.41 | 10035.17 | 5520.82 | 0.00 | 2197.44 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23227.35 | 01-FEB-09:09 | 9693.63 | 10035.17 | 0.00 | 0.00 | 1810.11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22549.72 | 15-MAR-08:09 | 8945.30 | 10035.17 | 0.00 | 0.00 | 1881.41 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22416.98 | 10-APR-08:09 | 8945.30 | 10035.17 | 0.00 | 0.00 | 1751.73 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21139.30 | 04-MAY-07:10 | 7722.00 | 10035.17 | 0.00 | 0.00 | 1736.62 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20904.38 | 13-JUN-08:09 | 6820.77 | 10035.17 | 0.00 | 0.00 | 1736.62 | 0.00 | 0.00 | 637.71 | 0.00 |
July | 22803.33 | 22-JUL-14:00 | 5637.30 | 10035.17 | 0.00 | 0.00 | 1736.62 | 0.00 | 0.00 | 3618.43 | 0.00 |
August | 22934.50 | 08-AUG-08:20 | 8945.30 | 10035.17 | 0.00 | 0.00 | 1736.62 | 0.00 | 0.00 | 548.93 | 0.00 |
September | 22386.87 | 08-SEP-08:09 | 8945.30 | 10035.17 | 0.00 | 0.00 | 1736.62 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 23167.66 | 31-OCT-08:09 | 9693.63 | 10035.17 | 0.00 | 0.00 | 1762.38 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 27781.57 | 28-NOV-16:49 | 8712.41 | 10035.17 | 5520.82 | 0.00 | 1900.81 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28141.60 | 28-DEC-08:09 | 8712.41 | 10035.17 | 5520.82 | 0.00 | 2224.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 20904.38 | 5637.30 | 10035.17 | 0.00 | 0.00 | 1736.62 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28141.60 | 9693.63 | 10035.17 | 5520.82 | 0.00 | 2224.21 | 0.00 | 0.00 | 3618.43 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 109560.68 | 10-JAN-06:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 80436.79 | 18-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 56312.73 | 04-MAR-06:19 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 28262.15 | 11-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 18772.25 | 20-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 10968.28 | 08-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 8475.61 | 05-JUL-05:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 7535.98 | 07-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 27728.16 | 23-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 82189.58 | 28-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 95451.06 | 28-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 109560.68 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.67 | 18.75 | 8.83 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
February | 8.67 | 19.15 | 7.83 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
March | 9.17 | 19.76 | 9.17 | 19.76 | 0.00 | 19.76 | 0.00 | 19.76 |
April | 6.83 | 20.16 | 6.83 | 20.16 | 0.00 | 20.16 | 0.00 | 20.16 |
May | 4.67 | 20.26 | 4.67 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
June | 0.17 | 20.47 | 0.17 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.50 | 20.52 | 0.50 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
October | 6.50 | 20.17 | 6.50 | 20.17 | 0.00 | 20.17 | 0.00 | 20.17 |
November | 8.17 | 19.77 | 8.00 | 19.82 | 0.00 | 19.82 | 0.00 | 19.82 |
December | 10.17 | 18.82 | 8.67 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
Annual Sum or Average | 65.50 | 19.50 | 61.17 | 19.65 | 0.00 | 19.65 | 0.00 | 19.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.67 | 20.52 | 9.17 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 29.83 | 14.85 | 2.50 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
February | 30.67 | 14.90 | 2.17 | 14.90 | 0.00 | 14.90 | 0.00 | 14.90 |
March | 9.33 | 14.95 | 0.50 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
April | 3.50 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6.00 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
November | 24.33 | 14.92 | 1.33 | 14.92 | 0.00 | 14.92 | 0.00 | 14.92 |
December | 56.17 | 14.86 | 3.50 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
Annual Sum or Average | 159.83 | 14.89 | 10.00 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 56.17 | 14.98 | 3.50 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.05 | 300.00 | 21.05 | 300.00 | 21.05 |
February | 276.00 | 21.05 | 276.00 | 21.05 | 276.00 | 21.05 |
March | 324.00 | 21.06 | 324.00 | 21.06 | 324.00 | 21.06 |
April | 300.00 | 21.58 | 214.00 | 21.39 | 214.00 | 21.31 |
May | 312.00 | 21.91 | 145.50 | 21.65 | 145.50 | 21.52 |
June | 289.67 | 23.10 | 19.67 | 23.01 | 15.17 | 22.92 |
July | 186.17 | 23.42 | 39.67 | 23.44 | 4.83 | 23.39 |
August | 239.67 | 23.55 | 10.33 | 23.56 | 0.00 | 23.56 |
September | 290.67 | 23.15 | 15.17 | 23.04 | 15.17 | 22.95 |
October | 300.00 | 21.43 | 214.17 | 21.29 | 214.17 | 21.23 |
November | 288.00 | 21.07 | 288.00 | 21.07 | 288.00 | 21.07 |
December | 300.00 | 21.05 | 300.00 | 21.05 | 300.00 | 21.05 |
Annual Sum or Average | 3406.17 | 21.87 | 2146.50 | 21.59 | 2096.83 | 21.44 |
Minimum of Months | 186.17 | 21.05 | 10.33 | 21.05 | 0.00 | 21.05 |
Maximum of Months | 324.00 | 23.55 | 324.00 | 23.56 | 324.00 | 23.56 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.65 | 300.00 | 15.65 | 300.00 | 15.65 |
February | 276.00 | 15.64 | 276.00 | 15.64 | 276.00 | 15.64 |
March | 324.00 | 15.77 | 324.00 | 15.77 | 324.00 | 15.77 |
April | 300.00 | 17.85 | 272.00 | 17.67 | 272.00 | 17.60 |
May | 312.00 | 18.82 | 244.00 | 18.46 | 244.00 | 18.32 |
June | 274.50 | 21.22 | 88.67 | 21.08 | 66.50 | 20.78 |
July | 169.33 | 22.02 | 117.33 | 23.00 | 19.50 | 22.82 |
August | 199.00 | 22.57 | 74.33 | 23.24 | 0.00 | 23.24 |
September | 288.50 | 21.15 | 83.67 | 20.75 | 80.50 | 20.48 |
October | 300.00 | 17.18 | 295.67 | 17.15 | 295.67 | 17.14 |
November | 288.00 | 15.78 | 288.00 | 15.78 | 288.00 | 15.78 |
December | 300.00 | 15.56 | 300.00 | 15.56 | 300.00 | 15.56 |
Annual Sum or Average | 3331.33 | 17.97 | 2663.67 | 17.61 | 2466.17 | 17.29 |
Minimum of Months | 169.33 | 15.56 | 74.33 | 15.56 | 0.00 | 15.56 |
Maximum of Months | 324.00 | 22.57 | 324.00 | 23.24 | 324.00 | 23.24 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 10.77 | 300.00 | 10.77 | 300.00 | 10.77 |
February | 276.00 | 11.03 | 276.00 | 11.03 | 276.00 | 11.03 |
March | 324.00 | 11.66 | 324.00 | 11.66 | 324.00 | 11.66 |
April | 300.00 | 16.21 | 288.17 | 16.11 | 288.17 | 16.07 |
May | 312.00 | 18.12 | 267.50 | 17.87 | 267.50 | 17.78 |
June | 292.67 | 21.01 | 105.83 | 20.63 | 93.83 | 20.30 |
July | 185.67 | 22.06 | 101.83 | 22.88 | 24.00 | 22.71 |
August | 205.50 | 22.52 | 65.67 | 23.11 | 2.33 | 23.09 |
September | 300.00 | 20.64 | 119.00 | 20.19 | 119.00 | 19.93 |
October | 300.00 | 15.48 | 300.00 | 15.48 | 300.00 | 15.48 |
November | 288.00 | 11.63 | 288.00 | 11.63 | 288.00 | 11.63 |
December | 300.00 | 10.40 | 300.00 | 10.40 | 300.00 | 10.40 |
Annual Sum or Average | 3383.83 | 15.59 | 2736.00 | 14.98 | 2582.83 | 14.57 |
Minimum of Months | 185.67 | 10.40 | 65.67 | 10.40 | 2.33 | 10.40 |
Maximum of Months | 324.00 | 22.52 | 324.00 | 23.11 | 324.00 | 23.09 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 85097728.57 | 18324751.25 | 16.33 | 83263795.71 | 1833932.86 | 0.00 | 0.41 | 29-APR-15:50 | 0.00 | 01-APR-00:10 | 3130.50 | 29-APR-15:50 | 3034.50 | 29-APR-15:50 | 105.59 | 29-APR-15:20 | 658.03 | 29-APR-15:50 | 0.00 | 01-APR-00:10 |
May | 0.194892E+09 | 41776503.83 | 34.83 | 0.171254E+09 | 23637787.46 | 0.00 | 0.42 | 22-MAY-16:00 | 0.00 | 01-MAY-00:10 | 3377.28 | 22-MAY-16:00 | 3003.30 | 22-MAY-16:00 | 526.84 | 23-MAY-15:00 | 705.53 | 22-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.125830E+10 | 0.265173E+09 | 154.75 | 0.107923E+10 | 0.179067E+09 | 0.00 | 0.80 | 13-JUN-16:00 | 0.00 | 01-JUN-00:10 | 6741.89 | 13-JUN-16:00 | 5934.72 | 13-JUN-16:00 | 1096.82 | 26-JUN-16:00 | 1379.60 | 13-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.250076E+10 | 0.520593E+09 | 220.67 | 0.217297E+10 | 0.327785E+09 | 0.00 | 0.94 | 22-JUL-16:00 | 0.00 | 01-JUL-00:10 | 7702.90 | 22-JUL-16:00 | 7537.26 | 22-JUL-16:00 | 1205.53 | 24-JUL-16:00 | 1622.12 | 22-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 0.279980E+10 | 0.584353E+09 | 259.75 | 0.242986E+10 | 0.369939E+09 | 0.00 | 0.75 | 14-AUG-16:00 | 0.00 | 01-AUG-00:10 | 6161.39 | 14-AUG-16:00 | 5734.52 | 14-AUG-16:00 | 1055.79 | 18-AUG-16:00 | 1265.49 | 14-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 0.106754E+10 | 0.226619E+09 | 154.25 | 0.925131E+09 | 0.142406E+09 | 0.00 | 0.61 | 13-SEP-16:00 | 0.00 | 01-SEP-00:10 | 5027.21 | 13-SEP-16:00 | 4377.66 | 13-SEP-16:00 | 807.89 | 12-SEP-14:30 | 1018.18 | 13-SEP-16:00 | 0.00 | 01-SEP-00:10 |
October | 7105364.03 | 1562462.48 | 2.67 | 7105364.03 | 0.00 | 0.00 | 0.15 | 07-OCT-15:40 | 0.00 | 01-OCT-00:10 | 1115.63 | 07-OCT-15:40 | 1115.63 | 07-OCT-15:40 | 0.00 | 07-OCT-14:30 | 244.45 | 07-OCT-15:40 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.791349E+10 | 0.165840E+10 | 843.25 | 0.686882E+10 | 0.104467E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.279980E+10 | 0.584353E+09 | 259.75 | 0.242986E+10 | 0.369939E+09 | 0.00 | 0.94 | 0.00 | 7702.90 | 7537.26 | 1205.53 | 1622.12 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 |
July | 0.188227E+09 | 48693100.75 | 11.17 | 0.186562E+09 | 1665298.56 | 0.00 | 0.55 | 22-JUL-15:10 | 0.00 | 01-JUL-00:10 | 8160.35 | 22-JUL-15:10 | 8160.35 | 22-JUL-15:10 | 229.80 | 22-JUL-12:10 | 2090.72 | 22-JUL-15:10 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.188227E+09 | 48693100.75 | 11.17 | 0.186562E+09 | 1665298.56 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.188227E+09 | 48693100.75 | 11.17 | 0.186562E+09 | 1665298.56 | 0.00 | 0.55 | 0.00 | 8160.35 | 8160.35 | 229.80 | 2090.72 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.23 | 14.45 | 29.78 | 32.30 | 100.67 | 0.00 | 0.00 | 0.00 |
February | 78.24 | 33.23 | 45.01 | 70.76 | 93.95 | 0.00 | 0.00 | 0.00 |
March | 70.51 | 13.55 | 56.96 | 54.81 | 73.53 | 0.00 | 0.00 | 0.00 |
April | 165.92 | 65.74 | 100.19 | 189.60 | 62.82 | 0.00 | 0.00 | 0.00 |
May | 194.61 | 78.90 | 115.71 | 218.37 | 54.55 | 0.00 | 0.00 | 0.00 |
June | 210.56 | 86.88 | 123.68 | 245.29 | 47.68 | 0.00 | 0.00 | 0.00 |
July | 214.45 | 94.61 | 119.85 | 255.70 | 48.32 | 0.00 | 0.00 | 0.00 |
August | 179.98 | 77.84 | 102.14 | 215.86 | 53.93 | 0.00 | 0.00 | 0.00 |
September | 145.69 | 65.85 | 79.84 | 171.17 | 63.32 | 0.00 | 0.00 | 0.00 |
October | 77.36 | 27.91 | 49.45 | 77.41 | 71.87 | 0.00 | 0.00 | 0.00 |
November | 41.87 | 12.33 | 29.55 | 31.14 | 87.06 | 0.00 | 0.00 | 0.00 |
December | 23.52 | 4.90 | 18.62 | 10.72 | 114.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 120.70 | 48.03 | 72.67 | 131.28 | 72.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.52 | 4.90 | 18.62 | 10.72 | 47.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 214.45 | 94.61 | 123.68 | 255.70 | 114.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.23 | 14.45 | 29.78 | 32.30 | 100.67 | 0.00 | 0.00 | 0.00 |
February | 78.24 | 33.23 | 45.01 | 70.76 | 93.95 | 0.00 | 0.00 | 0.00 |
March | 70.51 | 13.55 | 56.96 | 54.81 | 73.53 | 0.00 | 0.00 | 0.00 |
April | 165.92 | 65.74 | 100.19 | 189.60 | 62.82 | 0.00 | 0.00 | 0.00 |
May | 194.61 | 78.90 | 115.71 | 218.37 | 54.55 | 0.00 | 0.00 | 0.00 |
June | 210.56 | 86.88 | 123.68 | 245.29 | 47.68 | 0.00 | 0.00 | 0.00 |
July | 214.45 | 94.61 | 119.85 | 255.70 | 48.32 | 0.00 | 0.00 | 0.00 |
August | 179.98 | 77.84 | 102.14 | 215.86 | 53.93 | 0.00 | 0.00 | 0.00 |
September | 145.69 | 65.85 | 79.84 | 171.17 | 63.32 | 0.00 | 0.00 | 0.00 |
October | 77.36 | 27.91 | 49.45 | 77.41 | 71.87 | 0.00 | 0.00 | 0.00 |
November | 41.87 | 12.33 | 29.55 | 31.14 | 87.06 | 0.00 | 0.00 | 0.00 |
December | 23.52 | 4.90 | 18.62 | 10.72 | 114.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 120.70 | 48.03 | 72.67 | 131.28 | 72.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.52 | 4.90 | 18.62 | 10.72 | 47.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 214.45 | 94.61 | 123.68 | 255.70 | 114.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.91 | 0.00 | 12.91 | 2.39 | 61.46 | 0.00 | 0.00 | 0.00 |
February | 20.15 | 0.00 | 20.15 | 6.00 | 56.54 | 0.00 | 0.00 | 0.00 |
March | 27.89 | 0.00 | 27.89 | 14.63 | 44.31 | 0.00 | 0.00 | 0.00 |
April | 45.48 | 0.25 | 45.23 | 37.63 | 36.30 | 0.00 | 0.00 | 0.00 |
May | 57.02 | 2.95 | 54.07 | 47.09 | 29.94 | 0.00 | 0.00 | 0.00 |
June | 62.59 | 3.83 | 58.76 | 58.48 | 26.52 | 0.00 | 0.00 | 0.00 |
July | 59.51 | 3.36 | 56.14 | 56.44 | 26.72 | 0.00 | 0.00 | 0.00 |
August | 47.01 | 0.91 | 46.10 | 43.20 | 30.35 | 0.00 | 0.00 | 0.00 |
September | 35.64 | 0.02 | 35.62 | 30.04 | 37.49 | 0.00 | 0.00 | 0.00 |
October | 22.82 | 0.00 | 22.82 | 13.78 | 42.59 | 0.00 | 0.00 | 0.00 |
November | 13.71 | 0.00 | 13.71 | 3.46 | 51.78 | 0.00 | 0.00 | 0.00 |
December | 9.34 | 0.00 | 9.34 | 0.53 | 67.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 34.57 | 0.95 | 33.62 | 26.24 | 42.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.34 | 0.00 | 9.34 | 0.53 | 26.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.59 | 3.83 | 58.76 | 58.48 | 67.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.91 | 0.00 | 12.91 | 2.39 | 61.46 | 0.00 | 0.00 | 0.00 |
February | 20.15 | 0.00 | 20.15 | 6.00 | 56.54 | 0.00 | 0.00 | 0.00 |
March | 27.89 | 0.00 | 27.89 | 14.63 | 44.31 | 0.00 | 0.00 | 0.00 |
April | 45.47 | 0.25 | 45.23 | 37.63 | 36.30 | 0.00 | 0.00 | 0.00 |
May | 57.02 | 2.95 | 54.07 | 47.09 | 29.94 | 0.00 | 0.00 | 0.00 |
June | 62.59 | 3.83 | 58.76 | 58.48 | 26.52 | 0.00 | 0.00 | 0.00 |
July | 59.50 | 3.36 | 56.14 | 56.44 | 26.72 | 0.00 | 0.00 | 0.00 |
August | 47.01 | 0.91 | 46.10 | 43.20 | 30.35 | 0.00 | 0.00 | 0.00 |
September | 35.64 | 0.02 | 35.62 | 30.04 | 37.49 | 0.00 | 0.00 | 0.00 |
October | 22.82 | 0.00 | 22.82 | 13.78 | 42.59 | 0.00 | 0.00 | 0.00 |
November | 13.71 | 0.00 | 13.71 | 3.46 | 51.78 | 0.00 | 0.00 | 0.00 |
December | 9.34 | 0.00 | 9.34 | 0.53 | 67.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 34.57 | 0.95 | 33.62 | 26.24 | 42.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.34 | 0.00 | 9.34 | 0.53 | 26.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.59 | 3.83 | 58.76 | 58.48 | 67.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.08 | 36.43 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.12 | 34.61 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.50 | 26.88 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 93.19 | 24.84 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 109.63 | 22.01 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 118.57 | 19.66 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 121.01 | 20.88 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 104.22 | 24.53 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.84 | 27.70 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.83 | 27.87 | 2.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 12.06 | 31.24 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.03 | 40.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.43 | 28.03 | 2.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.03 | 19.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 121.01 | 40.01 | 2.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.08 | 36.43 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.12 | 34.61 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.50 | 26.88 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 93.19 | 24.84 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 109.63 | 22.01 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 118.57 | 19.66 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 121.01 | 20.88 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 104.22 | 24.53 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.84 | 27.70 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.83 | 27.87 | 2.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 12.06 | 31.24 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.03 | 40.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.43 | 28.03 | 2.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.03 | 19.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 121.01 | 40.01 | 2.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.08 | 36.43 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.12 | 34.61 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.50 | 26.88 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 93.19 | 24.84 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 109.63 | 22.01 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 118.57 | 19.66 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 121.01 | 20.88 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 104.22 | 24.53 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.84 | 27.70 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.83 | 27.87 | 2.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 12.06 | 31.24 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.03 | 40.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.43 | 28.03 | 2.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.03 | 19.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 121.01 | 40.01 | 2.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.08 | 36.43 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.12 | 34.61 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.50 | 26.88 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 93.19 | 24.84 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 109.63 | 22.01 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 118.57 | 19.66 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 121.01 | 20.88 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 104.22 | 24.53 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.84 | 27.70 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.83 | 27.87 | 2.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 12.06 | 31.24 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.03 | 40.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.43 | 28.03 | 2.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.03 | 19.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 121.01 | 40.01 | 2.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.08 | 36.43 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.12 | 34.61 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.50 | 26.88 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 93.19 | 24.84 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 109.63 | 22.01 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 118.57 | 19.66 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 121.01 | 20.88 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 104.22 | 24.53 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.84 | 27.70 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.83 | 27.87 | 2.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 12.06 | 31.24 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.03 | 40.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.43 | 28.03 | 2.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.03 | 19.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 121.01 | 40.01 | 2.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.08 | 36.43 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.12 | 34.61 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.50 | 26.88 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 93.19 | 24.84 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 109.63 | 22.01 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 118.57 | 19.66 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 121.01 | 20.88 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 104.22 | 24.53 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.84 | 27.70 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.83 | 27.87 | 2.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 12.06 | 31.24 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.03 | 40.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.43 | 28.03 | 2.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.03 | 19.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 121.01 | 40.01 | 2.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.08 | 36.43 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.12 | 34.61 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.50 | 26.88 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 93.19 | 24.84 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 109.63 | 22.01 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 118.57 | 19.66 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 121.01 | 20.88 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 104.22 | 24.53 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.84 | 27.70 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.83 | 27.87 | 2.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 12.06 | 31.24 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.03 | 40.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.43 | 28.03 | 2.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.03 | 19.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 121.01 | 40.01 | 2.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.08 | 36.43 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.12 | 34.61 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.50 | 26.88 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 93.19 | 24.84 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 109.63 | 22.01 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 118.57 | 19.66 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 121.01 | 20.88 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 104.22 | 24.53 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.84 | 27.70 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.83 | 27.87 | 2.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 12.06 | 31.24 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.03 | 40.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.43 | 28.03 | 2.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.03 | 19.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 121.01 | 40.01 | 2.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.08 | 36.43 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.12 | 34.61 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.50 | 26.88 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 93.19 | 24.84 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 109.63 | 22.01 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 118.57 | 19.66 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 121.01 | 20.88 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 104.22 | 24.53 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.84 | 27.70 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.83 | 27.87 | 2.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 12.06 | 31.24 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.03 | 40.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.43 | 28.03 | 2.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.03 | 19.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 121.01 | 40.01 | 2.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.08 | 36.43 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.12 | 34.61 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.50 | 26.88 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 93.19 | 24.84 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 109.63 | 22.01 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 118.57 | 19.66 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 121.01 | 20.88 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 104.22 | 24.53 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.84 | 27.70 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.83 | 27.87 | 2.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 12.06 | 31.24 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.03 | 40.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.43 | 28.03 | 2.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.03 | 19.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 121.01 | 40.01 | 2.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.08 | 36.43 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.12 | 34.61 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.50 | 26.88 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 93.19 | 24.84 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 109.63 | 22.01 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 118.57 | 19.66 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 121.01 | 20.88 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 104.22 | 24.53 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.84 | 27.70 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.83 | 27.87 | 2.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 12.06 | 31.24 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.03 | 40.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.43 | 28.03 | 2.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.03 | 19.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 121.01 | 40.01 | 2.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.08 | 36.43 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.12 | 34.61 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.50 | 26.88 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 93.19 | 24.84 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 109.63 | 22.01 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 118.57 | 19.66 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 121.01 | 20.88 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 104.22 | 24.53 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.84 | 27.70 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.83 | 27.87 | 2.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 12.06 | 31.24 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.03 | 40.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.43 | 28.03 | 2.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.03 | 19.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 121.01 | 40.01 | 2.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.08 | 36.43 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.12 | 34.61 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.50 | 26.88 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 93.19 | 24.84 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 109.63 | 22.01 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 118.57 | 19.66 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 121.01 | 20.88 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 104.22 | 24.53 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.84 | 27.70 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.83 | 27.87 | 2.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 12.06 | 31.24 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.03 | 40.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.43 | 28.03 | 2.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.03 | 19.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 121.01 | 40.01 | 2.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.08 | 36.43 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.12 | 34.61 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.50 | 26.88 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 93.19 | 24.84 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 109.63 | 22.01 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 118.57 | 19.66 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 121.01 | 20.88 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 104.22 | 24.53 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.84 | 27.70 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.83 | 27.87 | 2.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 12.06 | 31.24 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.03 | 40.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.43 | 28.03 | 2.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.03 | 19.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 121.01 | 40.01 | 2.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.45 | 37.78 | 172.33 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.75 | 37.07 | 142.17 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.96 | 27.97 | 59.00 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.94 | 33.41 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 160.96 | 33.28 | 7.83 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 173.83 | 30.03 | 5.00 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.31 | 32.87 | 4.00 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.18 | 38.54 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.79 | 41.89 | 57.17 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.28 | 37.77 | 125.33 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.90 | 32.42 | 92.83 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.33 | 41.15 | 60.83 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.61 | 35.34 | 728.00 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.33 | 27.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.31 | 41.89 | 172.33 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.118466E+09 | 38704346.47 | 79761221.34 | 86505448.42 | 0.269632E+09 |
February | 0.189279E+09 | 80398761.05 | 0.108881E+09 | 0.171172E+09 | 0.227296E+09 |
March | 0.188864E+09 | 36303582.83 | 0.152560E+09 | 0.146806E+09 | 0.196941E+09 |
April | 0.430071E+09 | 0.170391E+09 | 0.259680E+09 | 0.491433E+09 | 0.162833E+09 |
May | 0.521245E+09 | 0.211320E+09 | 0.309924E+09 | 0.584885E+09 | 0.146100E+09 |
June | 0.545784E+09 | 0.225196E+09 | 0.320587E+09 | 0.635799E+09 | 0.123575E+09 |
July | 0.574394E+09 | 0.253401E+09 | 0.320993E+09 | 0.684864E+09 | 0.129432E+09 |
August | 0.482070E+09 | 0.208490E+09 | 0.273580E+09 | 0.578153E+09 | 0.144457E+09 |
September | 0.377622E+09 | 0.170679E+09 | 0.206943E+09 | 0.443674E+09 | 0.164137E+09 |
October | 0.207202E+09 | 74752083.80 | 0.132450E+09 | 0.207326E+09 | 0.192485E+09 |
November | 0.108539E+09 | 31953652.74 | 76585343.64 | 80709695.21 | 0.225647E+09 |
December | 62991728.83 | 13111787.98 | 49879940.85 | 28708264.26 | 0.305553E+09 |
Annual Sum or Average | 0.380653E+10 | 0.151470E+10 | 0.229183E+10 | 0.414004E+10 | 0.228809E+10 |
Minimum of Months | 62991728.83 | 13111787.98 | 49879940.85 | 28708264.26 | 0.123575E+09 |
Maximum of Months | 0.574394E+09 | 0.253401E+09 | 0.320993E+09 | 0.684864E+09 | 0.305553E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.118466E+09 | 38704346.47 | 79761221.34 | 86505448.42 | 0.269632E+09 |
February | 0.189279E+09 | 80398761.05 | 0.108881E+09 | 0.171172E+09 | 0.227296E+09 |
March | 0.188864E+09 | 36303582.83 | 0.152560E+09 | 0.146806E+09 | 0.196941E+09 |
April | 0.430071E+09 | 0.170391E+09 | 0.259680E+09 | 0.491433E+09 | 0.162833E+09 |
May | 0.521245E+09 | 0.211320E+09 | 0.309924E+09 | 0.584885E+09 | 0.146100E+09 |
June | 0.545784E+09 | 0.225196E+09 | 0.320587E+09 | 0.635799E+09 | 0.123575E+09 |
July | 0.574394E+09 | 0.253401E+09 | 0.320993E+09 | 0.684864E+09 | 0.129432E+09 |
August | 0.482070E+09 | 0.208490E+09 | 0.273580E+09 | 0.578153E+09 | 0.144457E+09 |
September | 0.377622E+09 | 0.170679E+09 | 0.206943E+09 | 0.443674E+09 | 0.164137E+09 |
October | 0.207202E+09 | 74752083.80 | 0.132450E+09 | 0.207326E+09 | 0.192485E+09 |
November | 0.108539E+09 | 31953652.74 | 76585343.64 | 80709695.21 | 0.225647E+09 |
December | 62991728.83 | 13111787.98 | 49879940.85 | 28708264.26 | 0.305553E+09 |
Annual Sum or Average | 0.380653E+10 | 0.151470E+10 | 0.229183E+10 | 0.414004E+10 | 0.228809E+10 |
Minimum of Months | 62991728.83 | 13111787.98 | 49879940.85 | 28708264.26 | 0.123575E+09 |
Maximum of Months | 0.574394E+09 | 0.253401E+09 | 0.320993E+09 | 0.684864E+09 | 0.305553E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 34569656.69 | 0.00 | 34569656.69 | 6395136.29 | 0.164614E+09 |
February | 48757919.88 | 0.00 | 48757919.88 | 14517651.53 | 0.136785E+09 |
March | 74709325.25 | 1058.91 | 74708266.34 | 39195188.15 | 0.118677E+09 |
April | 0.117874E+09 | 637971.16 | 0.117236E+09 | 97546347.73 | 94091001.85 |
May | 0.152729E+09 | 7902725.09 | 0.144826E+09 | 0.126136E+09 | 80196462.25 |
June | 0.162240E+09 | 9923470.49 | 0.152317E+09 | 0.151589E+09 | 68730172.21 |
July | 0.159382E+09 | 9012731.00 | 0.150370E+09 | 0.151176E+09 | 71579538.32 |
August | 0.125916E+09 | 2439432.28 | 0.123477E+09 | 0.115710E+09 | 81293268.76 |
September | 92386794.19 | 55538.11 | 92331256.08 | 77865994.69 | 97179296.29 |
October | 61129597.21 | 0.00 | 61129597.21 | 36897128.79 | 0.114076E+09 |
November | 35544954.04 | 0.00 | 35544954.04 | 8957578.79 | 0.134222E+09 |
December | 25012887.13 | 0.00 | 25012887.13 | 1429567.09 | 0.180026E+09 |
Annual Sum or Average | 0.109025E+10 | 29972927.05 | 0.106028E+10 | 0.827416E+09 | 0.134147E+10 |
Minimum of Months | 25012887.13 | 0.00 | 25012887.13 | 1429567.09 | 68730172.21 |
Maximum of Months | 0.162240E+09 | 9923470.49 | 0.152317E+09 | 0.151589E+09 | 0.180026E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 34568471.84 | 0.00 | 34568471.84 | 6394441.19 | 0.164614E+09 |
February | 48756291.65 | 0.00 | 48756291.65 | 14516298.73 | 0.136785E+09 |
March | 74706663.97 | 1058.86 | 74705605.11 | 39192351.88 | 0.118677E+09 |
April | 0.117870E+09 | 637941.26 | 0.117232E+09 | 97542107.28 | 94090666.40 |
May | 0.152724E+09 | 7902354.68 | 0.144822E+09 | 0.126130E+09 | 80196137.76 |
June | 0.162235E+09 | 9923005.37 | 0.152312E+09 | 0.151582E+09 | 68729887.05 |
July | 0.159378E+09 | 9012308.57 | 0.150365E+09 | 0.151170E+09 | 71579136.94 |
August | 0.125913E+09 | 2439317.94 | 0.123473E+09 | 0.115706E+09 | 81292700.61 |
September | 92384093.86 | 55535.51 | 92328558.35 | 77863033.51 | 97178599.85 |
October | 61127603.02 | 0.00 | 61127603.02 | 36895116.80 | 0.114075E+09 |
November | 35543732.70 | 0.00 | 35543732.70 | 8956731.29 | 0.134221E+09 |
December | 25012016.75 | 0.00 | 25012016.75 | 1429292.42 | 0.180026E+09 |
Annual Sum or Average | 0.109022E+10 | 29971522.18 | 0.106025E+10 | 0.827378E+09 | 0.134146E+10 |
Minimum of Months | 25012016.75 | 0.00 | 25012016.75 | 1429292.42 | 68729887.05 |
Maximum of Months | 0.162235E+09 | 9923005.37 | 0.152312E+09 | 0.151582E+09 | 0.180026E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26990615.33 | 97564099.08 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53515499.65 | 83735865.80 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81702235.46 | 72002326.92 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.241544E+09 | 64387944.81 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.293638E+09 | 58956528.57 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.307327E+09 | 50949993.09 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.324114E+09 | 55926409.61 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.279146E+09 | 65695973.62 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.193975E+09 | 71809563.18 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 90611204.64 | 74650616.64 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 31252067.96 | 80967246.57 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 0.107153E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.193729E+10 | 0.883800E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 50949993.09 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.324114E+09 | 0.107153E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26990615.33 | 97564099.08 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53515499.65 | 83735865.80 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81702235.46 | 72002326.92 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.241544E+09 | 64387944.81 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.293638E+09 | 58956528.57 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.307327E+09 | 50949993.09 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.324114E+09 | 55926409.61 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.279146E+09 | 65695973.62 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.193975E+09 | 71809563.18 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 90611204.64 | 74650616.64 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 31252067.96 | 80967246.57 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 0.107153E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.193729E+10 | 0.883800E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 50949993.09 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.324114E+09 | 0.107153E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26990615.33 | 97564099.08 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53515499.65 | 83735865.80 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81702235.46 | 72002326.92 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.241544E+09 | 64387944.81 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.293638E+09 | 58956528.57 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.307327E+09 | 50949993.09 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.324114E+09 | 55926409.61 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.279146E+09 | 65695973.62 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.193975E+09 | 71809563.18 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 90611204.64 | 74650616.64 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 31252067.96 | 80967246.57 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 0.107153E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.193729E+10 | 0.883800E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 50949993.09 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.324114E+09 | 0.107153E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26990615.33 | 97564099.08 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53515499.65 | 83735865.80 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81702235.46 | 72002326.92 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.241544E+09 | 64387944.81 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.293638E+09 | 58956528.57 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.307327E+09 | 50949993.09 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.324114E+09 | 55926409.61 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.279146E+09 | 65695973.62 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.193975E+09 | 71809563.18 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 90611204.64 | 74650616.64 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 31252067.96 | 80967246.57 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 0.107153E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.193729E+10 | 0.883800E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 50949993.09 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.324114E+09 | 0.107153E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26990615.33 | 97564099.08 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53515499.65 | 83735865.80 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81702235.46 | 72002326.92 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.241544E+09 | 64387944.81 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.293638E+09 | 58956528.57 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.307327E+09 | 50949993.09 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.324114E+09 | 55926409.61 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.279146E+09 | 65695973.62 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.193975E+09 | 71809563.18 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 90611204.64 | 74650616.64 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 31252067.96 | 80967246.57 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 0.107153E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.193729E+10 | 0.883800E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 50949993.09 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.324114E+09 | 0.107153E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26990615.33 | 97564099.08 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53515499.65 | 83735865.80 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81702235.46 | 72002326.92 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.241544E+09 | 64387944.81 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.293638E+09 | 58956528.57 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.307327E+09 | 50949993.09 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.324114E+09 | 55926409.61 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.279146E+09 | 65695973.62 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.193975E+09 | 71809563.18 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 90611204.64 | 74650616.64 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 31252067.96 | 80967246.57 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 0.107153E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.193729E+10 | 0.883800E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 50949993.09 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.324114E+09 | 0.107153E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26990615.33 | 97564099.08 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53515499.65 | 83735865.80 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81702235.46 | 72002326.92 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.241544E+09 | 64387944.81 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.293638E+09 | 58956528.57 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.307327E+09 | 50949993.09 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.324114E+09 | 55926409.61 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.279146E+09 | 65695973.62 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.193975E+09 | 71809563.18 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 90611204.64 | 74650616.64 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 31252067.96 | 80967246.57 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 0.107153E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.193729E+10 | 0.883800E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 50949993.09 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.324114E+09 | 0.107153E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26990615.33 | 97564099.08 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53515499.65 | 83735865.80 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81702235.46 | 72002326.92 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.241544E+09 | 64387944.81 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.293638E+09 | 58956528.57 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.307327E+09 | 50949993.09 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.324114E+09 | 55926409.61 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.279146E+09 | 65695973.62 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.193975E+09 | 71809563.18 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 90611204.64 | 74650616.64 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 31252067.96 | 80967246.57 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 0.107153E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.193729E+10 | 0.883800E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 50949993.09 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.324114E+09 | 0.107153E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26990615.33 | 97564099.08 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53515499.65 | 83735865.80 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81702235.46 | 72002326.92 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.241544E+09 | 64387944.81 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.293638E+09 | 58956528.57 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.307327E+09 | 50949993.09 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.324114E+09 | 55926409.61 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.279146E+09 | 65695973.62 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.193975E+09 | 71809563.18 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 90611204.64 | 74650616.64 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 31252067.96 | 80967246.57 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 0.107153E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.193729E+10 | 0.883800E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 50949993.09 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.324114E+09 | 0.107153E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26990615.33 | 97564099.08 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53515499.65 | 83735865.80 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81702235.46 | 72002326.92 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.241544E+09 | 64387944.81 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.293638E+09 | 58956528.57 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.307327E+09 | 50949993.09 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.324114E+09 | 55926409.61 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.279146E+09 | 65695973.62 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.193975E+09 | 71809563.18 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 90611204.64 | 74650616.64 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 31252067.96 | 80967246.57 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 0.107153E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.193729E+10 | 0.883800E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 50949993.09 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.324114E+09 | 0.107153E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26990615.33 | 97564099.08 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53515499.65 | 83735865.80 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81702235.46 | 72002326.92 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.241544E+09 | 64387944.81 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.293638E+09 | 58956528.57 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.307327E+09 | 50949993.09 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.324114E+09 | 55926409.61 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.279146E+09 | 65695973.62 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.193975E+09 | 71809563.18 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 90611204.64 | 74650616.64 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 31252067.96 | 80967246.57 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 0.107153E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.193729E+10 | 0.883800E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 50949993.09 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.324114E+09 | 0.107153E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26990615.33 | 97564099.08 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53515499.65 | 83735865.80 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81702235.46 | 72002326.92 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.241544E+09 | 64387944.81 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.293638E+09 | 58956528.57 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.307327E+09 | 50949993.09 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.324114E+09 | 55926409.61 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.279146E+09 | 65695973.62 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.193975E+09 | 71809563.18 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 90611204.64 | 74650616.64 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 31252067.96 | 80967246.57 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 0.107153E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.193729E+10 | 0.883800E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 50949993.09 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.324114E+09 | 0.107153E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26990615.33 | 97564099.08 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53515499.65 | 83735865.80 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81702235.46 | 72002326.92 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.241544E+09 | 64387944.81 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.293638E+09 | 58956528.57 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.307327E+09 | 50949993.09 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.324114E+09 | 55926409.61 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.279146E+09 | 65695973.62 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.193975E+09 | 71809563.18 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 90611204.64 | 74650616.64 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 31252067.96 | 80967246.57 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 0.107153E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.193729E+10 | 0.883800E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 50949993.09 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.324114E+09 | 0.107153E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26990615.33 | 97564099.08 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53515499.65 | 83735865.80 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81702235.46 | 72002326.92 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.241544E+09 | 64387944.81 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.293638E+09 | 58956528.57 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.307327E+09 | 50949993.09 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.324114E+09 | 55926409.61 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.279146E+09 | 65695973.62 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.193975E+09 | 71809563.18 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 90611204.64 | 74650616.64 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 31252067.96 | 80967246.57 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 0.107153E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.193729E+10 | 0.883800E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13476942.16 | 50949993.09 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.324114E+09 | 0.107153E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57456547.01 | 0.101197E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98571215.46 | 89670801.34 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141852E+09 | 74920439.46 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.365311E+09 | 86595303.87 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431128E+09 | 89126953.44 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.450577E+09 | 77836256.00 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472222E+09 | 88036619.40 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407588E+09 | 0.103220E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289767E+09 | 0.108591E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142708E+09 | 0.101154E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61954849.90 | 84035459.82 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 0.110219E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295216E+10 | 0.111460E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 33025833.76 | 74920439.46 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472222E+09 | 0.110219E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 65.02 | 319.91 | 114.27 | 28.90 | 85.37 | 0.00 | 0.00 |
February | 150.61 | 298.09 | 196.79 | 66.47 | 130.32 | 0.00 | 0.00 |
March | 136.77 | 233.55 | 196.81 | 27.11 | 169.70 | 0.00 | 0.00 |
April | 453.37 | 197.15 | 422.80 | 131.97 | 290.83 | 0.00 | 0.00 |
May | 528.34 | 166.39 | 503.26 | 163.70 | 339.57 | 0.00 | 0.00 |
June | 605.10 | 145.94 | 546.31 | 181.42 | 364.89 | 0.00 | 0.00 |
July | 621.99 | 147.80 | 547.92 | 195.95 | 351.97 | 0.00 | 0.00 |
August | 516.97 | 167.43 | 453.99 | 157.50 | 296.49 | 0.00 | 0.00 |
September | 401.01 | 200.22 | 362.66 | 131.74 | 230.92 | 0.00 | 0.00 |
October | 180.98 | 227.53 | 200.37 | 55.82 | 144.55 | 0.00 | 0.00 |
November | 67.39 | 275.87 | 111.18 | 24.66 | 86.52 | 0.00 | 0.00 |
December | 21.14 | 361.22 | 65.71 | 9.79 | 55.92 | 0.00 | 0.00 |
Annual Sum or Average | 312.96 | 228.11 | 310.55 | 97.96 | 212.59 | 0.00 | 0.00 |
Minimum of Months | 21.14 | 145.94 | 65.71 | 9.79 | 55.92 | 0.00 | 0.00 |
Maximum of Months | 621.99 | 361.22 | 547.92 | 195.95 | 364.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 141.08 | 509.97 | 199.60 | 47.95 | 151.65 | 0.00 | 0.00 |
February | 309.70 | 484.58 | 352.07 | 117.19 | 234.88 | 0.00 | 0.00 |
March | 427.06 | 376.36 | 454.22 | 84.43 | 369.79 | 0.00 | 0.00 |
April | 1304.63 | 347.77 | 1109.70 | 594.21 | 515.49 | 0.00 | 0.00 |
May | 1534.85 | 308.17 | 1338.59 | 743.66 | 594.93 | 0.00 | 0.00 |
June | 1659.94 | 275.19 | 1427.18 | 774.57 | 652.60 | 0.00 | 0.00 |
July | 1694.14 | 292.33 | 1447.64 | 847.48 | 600.16 | 0.00 | 0.00 |
August | 1459.10 | 343.39 | 1243.51 | 752.92 | 490.58 | 0.00 | 0.00 |
September | 1047.71 | 387.86 | 901.97 | 533.42 | 368.55 | 0.00 | 0.00 |
October | 473.62 | 390.20 | 457.68 | 195.33 | 262.34 | 0.00 | 0.00 |
November | 168.80 | 437.32 | 220.62 | 58.29 | 162.33 | 0.00 | 0.00 |
December | 70.44 | 560.09 | 139.31 | 29.24 | 110.07 | 0.00 | 0.00 |
Annual Sum or Average | 860.04 | 392.35 | 776.27 | 399.53 | 376.74 | 0.00 | 0.00 |
Minimum of Months | 70.44 | 275.19 | 139.31 | 29.24 | 110.07 | 0.00 | 0.00 |
Maximum of Months | 1694.14 | 560.09 | 1447.64 | 847.48 | 652.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2942.04 | 6914.20 | 645.19 | 182.63 | 462.56 | 0.00 | 0.00 |
February | 5493.53 | 6810.71 | 1118.25 | 401.82 | 716.43 | 0.00 | 0.00 |
March | 6973.41 | 4911.75 | 1392.60 | 264.64 | 1127.96 | 0.00 | 0.00 |
April | 18136.92 | 3966.55 | 3372.49 | 1800.12 | 1572.37 | 0.00 | 0.00 |
May | 20778.96 | 3488.58 | 4039.61 | 2224.93 | 1814.68 | 0.00 | 0.00 |
June | 22859.33 | 2933.33 | 4304.04 | 2313.43 | 1990.61 | 0.00 | 0.00 |
July | 21634.45 | 3179.37 | 4362.52 | 2531.86 | 1830.65 | 0.00 | 0.00 |
August | 18897.88 | 3702.44 | 3758.94 | 2262.54 | 1496.40 | 0.00 | 0.00 |
September | 14328.08 | 4204.02 | 2773.27 | 1649.09 | 1124.17 | 0.00 | 0.00 |
October | 7064.71 | 4860.64 | 1424.92 | 624.70 | 800.22 | 0.00 | 0.00 |
November | 3012.58 | 5650.60 | 703.89 | 208.74 | 495.15 | 0.00 | 0.00 |
December | 1774.17 | 7653.53 | 449.26 | 113.51 | 335.75 | 0.00 | 0.00 |
Annual Sum or Average | 12016.33 | 4847.56 | 2367.63 | 1218.47 | 1149.16 | 0.00 | 0.00 |
Minimum of Months | 1774.17 | 2933.33 | 449.26 | 113.51 | 335.75 | 0.00 | 0.00 |
Maximum of Months | 22859.33 | 7653.53 | 4362.52 | 2531.86 | 1990.61 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.174152E+09 | 0.856842E+09 | 0.306069E+09 | 77408692.93 | 0.228661E+09 | 0.00 | 0.00 |
February | 0.364365E+09 | 0.721147E+09 | 0.476073E+09 | 0.160798E+09 | 0.315275E+09 | 0.00 | 0.00 |
March | 0.366314E+09 | 0.625550E+09 | 0.527144E+09 | 72609283.44 | 0.454535E+09 | 0.00 | 0.00 |
April | 0.117513E+10 | 0.511026E+09 | 0.109589E+10 | 0.342057E+09 | 0.753829E+09 | 0.00 | 0.00 |
May | 0.141510E+10 | 0.445655E+09 | 0.134794E+10 | 0.438446E+09 | 0.909496E+09 | 0.00 | 0.00 |
June | 0.156842E+10 | 0.378266E+09 | 0.141604E+10 | 0.470239E+09 | 0.945803E+09 | 0.00 | 0.00 |
July | 0.166593E+10 | 0.395881E+09 | 0.146755E+10 | 0.524828E+09 | 0.942721E+09 | 0.00 | 0.00 |
August | 0.138466E+10 | 0.448439E+09 | 0.121597E+10 | 0.421860E+09 | 0.794110E+09 | 0.00 | 0.00 |
September | 0.103942E+10 | 0.518974E+09 | 0.940016E+09 | 0.341469E+09 | 0.598546E+09 | 0.00 | 0.00 |
October | 0.484741E+09 | 0.609417E+09 | 0.536661E+09 | 0.149504E+09 | 0.387156E+09 | 0.00 | 0.00 |
November | 0.174663E+09 | 0.715066E+09 | 0.288167E+09 | 63907305.49 | 0.224259E+09 | 0.00 | 0.00 |
December | 56613407.83 | 0.967496E+09 | 0.176008E+09 | 26223575.96 | 0.149785E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.986952E+10 | 0.719376E+10 | 0.979353E+10 | 0.308935E+10 | 0.670418E+10 | 0.00 | 0.00 |
Minimum of Months | 56613407.83 | 0.378266E+09 | 0.176008E+09 | 26223575.96 | 0.149785E+09 | 0.00 | 0.00 |
Maximum of Months | 0.166593E+10 | 0.967496E+09 | 0.146755E+10 | 0.524828E+09 | 0.945803E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.377869E+09 | 0.136590E+10 | 0.534600E+09 | 0.128429E+09 | 0.406171E+09 | 0.00 | 0.00 |
February | 0.749217E+09 | 0.117230E+10 | 0.851728E+09 | 0.283515E+09 | 0.568214E+09 | 0.00 | 0.00 |
March | 0.114383E+10 | 0.100803E+10 | 0.121658E+10 | 0.226133E+09 | 0.990448E+09 | 0.00 | 0.00 |
April | 0.338161E+10 | 0.901431E+09 | 0.287635E+10 | 0.154020E+10 | 0.133615E+10 | 0.00 | 0.00 |
May | 0.411094E+10 | 0.825391E+09 | 0.358528E+10 | 0.199183E+10 | 0.159345E+10 | 0.00 | 0.00 |
June | 0.430258E+10 | 0.713300E+09 | 0.369925E+10 | 0.200770E+10 | 0.169155E+10 | 0.00 | 0.00 |
July | 0.453760E+10 | 0.782970E+09 | 0.387737E+10 | 0.226989E+10 | 0.160748E+10 | 0.00 | 0.00 |
August | 0.390805E+10 | 0.919744E+09 | 0.333060E+10 | 0.201663E+10 | 0.131397E+10 | 0.00 | 0.00 |
September | 0.271565E+10 | 0.100533E+10 | 0.233792E+10 | 0.138263E+10 | 0.955282E+09 | 0.00 | 0.00 |
October | 0.126856E+10 | 0.104511E+10 | 0.122584E+10 | 0.523177E+09 | 0.702664E+09 | 0.00 | 0.00 |
November | 0.437529E+09 | 0.113354E+10 | 0.571859E+09 | 0.151099E+09 | 0.420760E+09 | 0.00 | 0.00 |
December | 0.188677E+09 | 0.150015E+10 | 0.373139E+09 | 78319649.82 | 0.294820E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.271221E+11 | 0.123732E+11 | 0.244805E+11 | 0.125995E+11 | 0.118810E+11 | 0.00 | 0.00 |
Minimum of Months | 0.188677E+09 | 0.713300E+09 | 0.373139E+09 | 78319649.82 | 0.294820E+09 | 0.00 | 0.00 |
Maximum of Months | 0.453760E+10 | 0.150015E+10 | 0.387737E+10 | 0.226989E+10 | 0.169155E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.787997E+10 | 0.185190E+11 | 0.172808E+10 | 0.489157E+09 | 0.123892E+10 | 0.00 | 0.00 |
February | 0.132899E+11 | 0.164765E+11 | 0.270527E+10 | 0.972077E+09 | 0.173320E+10 | 0.00 | 0.00 |
March | 0.186776E+11 | 0.131556E+11 | 0.372993E+10 | 0.708807E+09 | 0.302112E+10 | 0.00 | 0.00 |
April | 0.470109E+11 | 0.102813E+11 | 0.874150E+10 | 0.466590E+10 | 0.407559E+10 | 0.00 | 0.00 |
May | 0.556544E+11 | 0.934382E+10 | 0.108197E+11 | 0.595926E+10 | 0.486043E+10 | 0.00 | 0.00 |
June | 0.592514E+11 | 0.760319E+10 | 0.111561E+11 | 0.599642E+10 | 0.515966E+10 | 0.00 | 0.00 |
July | 0.579457E+11 | 0.851562E+10 | 0.116846E+11 | 0.678135E+10 | 0.490323E+10 | 0.00 | 0.00 |
August | 0.506161E+11 | 0.991661E+10 | 0.100679E+11 | 0.605999E+10 | 0.400795E+10 | 0.00 | 0.00 |
September | 0.371384E+11 | 0.108968E+11 | 0.718830E+10 | 0.427445E+10 | 0.291386E+10 | 0.00 | 0.00 |
October | 0.189221E+11 | 0.130187E+11 | 0.381650E+10 | 0.167320E+10 | 0.214331E+10 | 0.00 | 0.00 |
November | 0.780860E+10 | 0.146464E+11 | 0.182448E+10 | 0.541050E+09 | 0.128343E+10 | 0.00 | 0.00 |
December | 0.475195E+10 | 0.204992E+11 | 0.120329E+10 | 0.304019E+09 | 0.899275E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.378947E+12 | 0.152873E+12 | 0.746656E+11 | 0.384257E+11 | 0.362400E+11 | 0.00 | 0.00 |
Minimum of Months | 0.475195E+10 | 0.760319E+10 | 0.120329E+10 | 0.304019E+09 | 0.899275E+09 | 0.00 | 0.00 |
Maximum of Months | 0.592514E+11 | 0.204992E+11 | 0.116846E+11 | 0.678135E+10 | 0.515966E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.23 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -1.9 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.24 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.07 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.27 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.49 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.75 | 10.65 | 2.92 | 3.95 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.43 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.66 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.75 | 10.65 | 3.35 | 4.49 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.37 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.22 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.13 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.08 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.53 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.80 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.18 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.22 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.10 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.01 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.64 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.64 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.53 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -7.0 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.9 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.05 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.5 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -7.0 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.08 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.31 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.06 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.54 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.01 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.95 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.45 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.54 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.956478E+09 | -869203116.5 | 0.00 | 0.00 | 744.00 | 0.00 | -87274783.0 | 59.00 | 0.00 | 0.00 |
February | 0.882649E+09 | -803824950.9 | 0.00 | 0.00 | 672.00 | 0.00 | -78824062.7 | 58.99 | 0.00 | 0.00 |
March | 0.101964E+10 | -933146668.5 | 0.00 | 0.00 | 744.00 | 0.00 | -86489384.9 | 58.99 | 0.00 | 0.00 |
April | 0.931685E+09 | -850510403.4 | 0.00 | 0.00 | 720.00 | 0.00 | -81174774.9 | 58.99 | 0.00 | 0.00 |
May | 0.943507E+09 | -860901651.2 | 0.00 | 0.00 | 744.00 | 0.00 | -82605775.3 | 58.99 | 0.00 | 0.00 |
June | 0.910271E+09 | -834455734.5 | 0.00 | 0.00 | 720.00 | 0.00 | -75815306.8 | 58.99 | 0.00 | 0.00 |
July | 0.866047E+09 | -789600306.4 | 0.00 | 0.00 | 744.00 | 0.00 | -76446364.7 | 58.99 | 0.00 | 0.00 |
August | 0.917567E+09 | -841423495.9 | 0.00 | 0.00 | 744.00 | 0.00 | -76143578.3 | 58.99 | 0.00 | 0.00 |
September | 0.864289E+09 | -788060154.5 | 0.00 | 0.00 | 720.00 | 0.00 | -76228902.1 | 58.99 | 0.00 | 0.00 |
October | 0.891317E+09 | -806687922.9 | 0.00 | 0.00 | 744.00 | 0.00 | -84629093.3 | 58.99 | 0.00 | 0.00 |
November | 0.880623E+09 | -796619221.6 | 0.00 | 0.00 | 720.00 | 0.00 | -84004232.6 | 58.99 | 0.00 | 0.00 |
December | 0.939439E+09 | -851920540.5 | 0.00 | 0.00 | 744.00 | 0.00 | -87518377.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.110035E+11 | -0.100264E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -977154636.4 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.864289E+09 | -933146668.5 | 0.00 | 0.00 | 672.00 | 0.00 | -87518377.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.101964E+10 | -788060154.5 | 0.00 | 0.00 | 744.00 | 0.00 | -75815306.8 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.96 | 0.83 | 01-JAN-12:30 | 86.53 | 0.00 | 0.00 | 0.00 | 68.07 | 0.00 | 0.00 | 0.00 |
February | 217.00 | 0.88 | 0.58 | 10-FEB-13:30 | 119.55 | 0.00 | 0.00 | 0.00 | 648.14 | 0.00 | 0.00 | 38.17 |
March | 215.50 | 0.85 | 0.50 | 16-MAR-12:20 | 168.15 | 0.00 | 0.00 | 10.00 | 144.27 | 0.00 | 0.00 | 4.33 |
April | 359.67 | 0.80 | 0.50 | 02-APR-11:20 | 203.85 | 0.00 | 0.00 | 67.50 | 161.96 | 0.00 | 0.00 | 28.83 |
May | 417.17 | 0.78 | 0.50 | 01-MAY-11:50 | 220.25 | 0.00 | 0.00 | 98.33 | 170.12 | 0.00 | 0.00 | 38.83 |
June | 410.67 | 0.76 | 0.50 | 02-JUN-10:39 | 244.26 | 0.00 | 0.00 | 115.83 | 187.94 | 0.00 | 0.00 | 64.50 |
July | 429.00 | 0.78 | 0.50 | 01-JUL-12:30 | 221.86 | 0.00 | 0.00 | 95.17 | 172.36 | 0.00 | 0.00 | 44.33 |
August | 396.33 | 0.81 | 0.50 | 01-AUG-10:30 | 198.70 | 0.00 | 0.00 | 56.33 | 157.81 | 0.00 | 0.00 | 16.00 |
September | 337.67 | 0.85 | 0.50 | 03-SEP-11:50 | 161.99 | 0.00 | 0.00 | 20.17 | 132.15 | 0.00 | 0.00 | 6.17 |
October | 234.00 | 0.88 | 0.67 | 01-OCT-10:00 | 140.35 | 0.00 | 0.00 | 0.00 | 113.33 | 0.00 | 0.00 | 0.00 |
November | 171.33 | 0.94 | 0.83 | 01-NOV-12:20 | 98.38 | 0.00 | 0.00 | 0.00 | 78.46 | 0.00 | 0.00 | 0.00 |
December | 131.67 | 0.97 | 0.83 | 02-DEC-11:09 | 78.50 | 0.00 | 0.00 | 0.00 | 62.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3515.67 | 0.83 | 180.13 | 0.00 | 0.00 | 463.33 | 176.58 | 0.00 | 0.00 | 241.17 | ||
Minimum of Months | 131.67 | 0.76 | 0.50 | 78.50 | 0.00 | 0.00 | 0.00 | 62.84 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 429.00 | 0.97 | 0.83 | 244.26 | 0.00 | 0.00 | 115.83 | 648.14 | 0.00 | 0.00 | 64.50 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.78 | 0.50 | 09-JAN-11:20 | 144.17 | 11.06 | 0.00 | 38.50 | 117.32 | 14.37 | 0.00 | 10.33 |
February | 217.00 | 0.69 | 0.50 | 01-FEB-12:09 | 198.96 | 12.78 | 0.00 | 104.50 | 161.90 | 16.37 | 11.83 | 63.00 |
March | 215.50 | 0.64 | 0.50 | 01-MAR-11:39 | 482.36 | 14.55 | 8.67 | 206.33 | 402.55 | 17.22 | 33.83 | 161.33 |
April | 359.67 | 0.61 | 0.50 | 01-APR-08:09 | 604.72 | 15.58 | 16.50 | 277.50 | 512.16 | 18.81 | 124.17 | 228.67 |
May | 417.17 | 0.60 | 0.50 | 01-MAY-07:19 | 358.68 | 15.05 | 0.00 | 324.33 | 717.24 | 19.53 | 126.50 | 272.00 |
June | 410.67 | 0.58 | 0.50 | 01-JUN-07:30 | 394.78 | 15.58 | 0.17 | 335.83 | 1250.07 | 21.04 | 130.67 | 283.67 |
July | 429.00 | 0.59 | 0.50 | 01-JUL-07:40 | 362.65 | 15.12 | 0.00 | 338.17 | 867.33 | 20.05 | 134.50 | 279.83 |
August | 396.33 | 0.61 | 0.50 | 01-AUG-07:49 | 326.09 | 14.65 | 0.00 | 294.50 | 267.04 | 18.53 | 111.17 | 244.17 |
September | 337.67 | 0.63 | 0.50 | 01-SEP-08:20 | 270.57 | 14.15 | 0.00 | 227.33 | 222.94 | 18.14 | 91.00 | 174.50 |
October | 234.00 | 0.64 | 0.50 | 01-OCT-09:09 | 792.10 | 13.69 | 0.00 | 150.17 | 409.22 | 18.81 | 47.50 | 111.50 |
November | 171.33 | 0.73 | 0.50 | 01-NOV-12:30 | 164.45 | 11.94 | 0.00 | 50.17 | 134.33 | 15.31 | 0.00 | 18.67 |
December | 131.67 | 0.80 | 0.58 | 02-DEC-10:00 | 132.24 | 11.11 | 0.00 | 6.67 | 109.25 | 14.44 | 0.00 | 0.00 |
Annual Sum or Average | 3515.67 | 0.64 | 373.10 | 14.26 | 25.33 | 2354.00 | 519.95 | 18.38 | 811.17 | 1847.67 | ||
Minimum of Months | 131.67 | 0.58 | 0.50 | 132.24 | 11.06 | 0.00 | 6.67 | 109.25 | 14.37 | 0.00 | 0.00 | |
Maximum of Months | 429.00 | 0.80 | 0.58 | 792.10 | 15.58 | 16.50 | 338.17 | 1250.07 | 21.04 | 134.50 | 283.67 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.89 | 0.64 | 19-JAN-15:20 | 217.39 | 22.62 | 87.50 | 18.50 | 97.68 | 19.88 | 72.33 | 0.00 |
February | 217.00 | 0.83 | 0.61 | 17-FEB-15:39 | 507.36 | 24.42 | 123.33 | 50.17 | 144.34 | 21.30 | 119.83 | 7.83 |
March | 215.50 | 0.82 | 0.61 | 02-MAR-16:49 | 316.54 | 23.43 | 157.50 | 46.33 | 217.16 | 23.84 | 176.33 | 17.50 |
April | 359.67 | 0.76 | 0.61 | 01-APR-14:20 | 401.31 | 22.87 | 241.00 | 138.33 | 359.64 | 24.00 | 284.50 | 85.83 |
May | 417.17 | 0.76 | 0.61 | 01-MAY-13:00 | 366.31 | 22.22 | 265.17 | 148.67 | 398.52 | 23.28 | 328.83 | 104.17 |
June | 410.67 | 0.74 | 0.61 | 01-JUN-14:09 | 396.70 | 22.53 | 268.83 | 174.17 | 505.78 | 23.55 | 319.83 | 104.83 |
July | 429.00 | 0.74 | 0.61 | 01-JUL-15:09 | 385.80 | 22.29 | 270.50 | 175.00 | 518.49 | 23.38 | 332.17 | 116.67 |
August | 396.33 | 0.76 | 0.61 | 01-AUG-14:09 | 390.17 | 22.47 | 248.83 | 144.67 | 390.20 | 23.37 | 301.33 | 107.17 |
September | 337.67 | 0.78 | 0.61 | 01-SEP-14:30 | 474.11 | 24.17 | 202.00 | 119.00 | 364.99 | 24.64 | 241.83 | 77.50 |
October | 234.00 | 0.81 | 0.61 | 01-OCT-14:39 | 343.76 | 24.03 | 139.33 | 57.83 | 185.00 | 23.14 | 153.33 | 20.67 |
November | 171.33 | 0.88 | 0.64 | 02-NOV-14:20 | 216.02 | 22.33 | 80.83 | 17.50 | 107.61 | 20.35 | 73.50 | 0.00 |
December | 131.67 | 0.92 | 0.77 | 03-DEC-12:20 | 154.15 | 19.13 | 36.00 | 0.00 | 82.59 | 19.12 | 31.00 | 0.00 |
Annual Sum or Average | 3515.67 | 0.79 | 369.46 | 22.79 | 2120.83 | 1090.17 | 333.78 | 22.95 | 2434.83 | 642.17 | ||
Minimum of Months | 131.67 | 0.74 | 0.61 | 154.15 | 19.13 | 36.00 | 0.00 | 82.59 | 19.12 | 31.00 | 0.00 | |
Maximum of Months | 429.00 | 0.92 | 0.77 | 507.36 | 24.42 | 270.50 | 175.00 | 518.49 | 24.64 | 332.17 | 116.67 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.500749E+10 | 24359.89 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.424974E+10 | 24359.89 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.438406E+10 | 24359.89 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167948E+10 | 24359.89 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107160E+10 | 24359.89 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140090E+09 | 24359.89 | 01-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 35905886.16 | 24359.89 | 03-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163034E+09 | 24359.89 | 06-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.182521E+10 | 24359.89 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.365515E+10 | 24359.89 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.514720E+10 | 24359.89 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.273590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.514720E+10 | 24359.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.140056E+11 | 58029.39 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114828E+11 | 58029.39 | 09-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.823610E+10 | 58029.39 | 13-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.928135E+09 | 56404.09 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 55795673.74 | 15325.72 | 06-MAY-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.165898E+10 | 58029.39 | 17-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.872753E+10 | 58029.39 | 07-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171842E+11 | 58029.39 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.622791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.171842E+11 | 58029.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.229934E+11 | 51663.22 | 10-JAN-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167028E+11 | 38884.67 | 17-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.397929E+10 | 21030.80 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.735080E+10 | 34188.47 | 29-NOV-03:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.360764E+11 | 51188.14 | 30-DEC-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.871027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.360764E+11 | 51663.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 85097728.57 | 83263795.71 | 3130.50 | 29-APR-15:50 | 3034.50 | 0.00 |
May | 0.00 | 0.00 | 0.194892E+09 | 0.171254E+09 | 3377.28 | 22-MAY-16:00 | 3003.30 | 0.00 |
June | 0.00 | 0.00 | 0.125830E+10 | 0.107923E+10 | 6741.89 | 13-JUN-16:00 | 5934.72 | 0.00 |
July | 0.00 | 0.00 | 0.250076E+10 | 0.217297E+10 | 7702.90 | 22-JUL-16:00 | 7537.26 | 0.00 |
August | 0.00 | 0.00 | 0.279980E+10 | 0.242986E+10 | 6161.39 | 14-AUG-16:00 | 5734.52 | 0.00 |
September | 0.00 | 0.00 | 0.106754E+10 | 0.925131E+09 | 5027.21 | 13-SEP-16:00 | 4377.66 | 0.00 |
October | 0.00 | 0.00 | 7105364.03 | 7105364.03 | 1115.63 | 07-OCT-15:40 | 1115.63 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.791349E+10 | 0.686882E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.279980E+10 | 0.242986E+10 | 7702.90 | 7537.26 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.188227E+09 | 0.186562E+09 | 8160.35 | 22-JUL-15:10 | 8160.35 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.188227E+09 | 0.186562E+09 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.188227E+09 | 0.186562E+09 | 8160.35 | 8160.35 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.235442E+09 | 0.04 | 152.64 | 01-JAN-00:03 | 0.08 |
February | 0.196713E+09 | 0.04 | 152.64 | 01-FEB-00:05 | 0.08 |
March | 88666220.96 | 0.02 | 152.64 | 01-MAR-00:05 | 0.08 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 80710835.46 | 0.02 | 152.64 | 04-NOV-05:40 | 0.08 |
December | 0.300232E+09 | 0.06 | 152.64 | 01-DEC-00:05 | 0.08 |
Annual Sum or Average | 0.901764E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.300232E+09 | 0.06 | 152.64 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.106429E+10 | 0.39 | 1035.47 | 02-JAN-07:05 | 0.92 |
February | 0.977849E+09 | 0.39 | 1035.47 | 01-FEB-08:00 | 0.91 |
March | 0.114132E+10 | 0.40 | 1035.47 | 01-MAR-07:20 | 0.91 |
April | 0.104681E+10 | 0.37 | 1035.47 | 01-APR-06:50 | 0.92 |
May | 0.108254E+10 | 0.37 | 1035.47 | 01-MAY-06:50 | 0.92 |
June | 0.106966E+10 | 0.37 | 1035.47 | 01-JUN-06:10 | 0.91 |
July | 0.102650E+10 | 0.34 | 1035.47 | 01-JUL-09:40 | 0.91 |
August | 0.110713E+10 | 0.36 | 1035.47 | 01-AUG-07:20 | 0.91 |
September | 0.102898E+10 | 0.36 | 1035.47 | 01-SEP-09:00 | 0.91 |
October | 0.104668E+10 | 0.36 | 1035.47 | 02-OCT-06:10 | 0.92 |
November | 0.101423E+10 | 0.37 | 1035.47 | 01-NOV-06:10 | 0.92 |
December | 0.106679E+10 | 0.40 | 1035.47 | 01-DEC-07:20 | 0.92 |
Annual Sum or Average | 0.126728E+11 | 0.37 | |||
Minimum of Months | 0.977849E+09 | 0.34 | 1035.47 | 0.91 | |
Maximum of Months | 0.114132E+10 | 0.40 | 1035.47 | 0.92 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.106396E+10 | 0.53 | 1752.86 | 02-JAN-06:01 | 0.89 |
February | 0.953392E+09 | 0.53 | 1752.86 | 09-FEB-06:01 | 0.89 |
March | 0.975752E+09 | 0.47 | 1752.86 | 13-MAR-05:01 | 0.89 |
April | 0.721074E+09 | 0.25 | 1703.77 | 03-APR-05:01 | 0.89 |
May | 0.723550E+09 | 0.21 | 751.84 | 06-MAY-06:10 | 0.56 |
June | 0.721899E+09 | 0.21 | 701.14 | 01-JUN-06:10 | 0.54 |
July | 0.694133E+09 | 0.20 | 701.14 | 21-JUL-15:00 | 0.53 |
August | 0.749664E+09 | 0.21 | 701.14 | 01-AUG-06:10 | 0.53 |
September | 0.694133E+09 | 0.20 | 701.14 | 01-SEP-06:10 | 0.53 |
October | 0.741458E+09 | 0.27 | 1752.86 | 17-OCT-05:10 | 0.88 |
November | 0.906107E+09 | 0.46 | 1752.86 | 07-NOV-06:01 | 0.88 |
December | 0.114823E+10 | 0.56 | 1752.86 | 04-DEC-06:01 | 0.89 |
Annual Sum or Average | 0.100934E+11 | 0.34 | |||
Minimum of Months | 0.694133E+09 | 0.20 | 701.14 | 0.53 | |
Maximum of Months | 0.114823E+10 | 0.56 | 1752.86 | 0.89 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.106429E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.977849E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.114132E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.106513E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.112432E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.133483E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.154709E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.169148E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.125560E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.104825E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.101423E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.106679E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.143312E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.977849E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.169148E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.106396E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.953392E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.975752E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.721074E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.723550E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.721899E+09 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.742826E+09 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.749664E+09 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.694133E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.741458E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.906107E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.114823E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.101420E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.694133E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.114823E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.106429E+10 | 0.00 | 0.500749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.977849E+09 | 0.00 | 0.424974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114132E+10 | 0.00 | 0.438406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104681E+10 | 85097728.57 | 0.167948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108254E+10 | 0.194892E+09 | 0.107160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.106966E+10 | 0.125830E+10 | 0.140090E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102650E+10 | 0.250076E+10 | 35905886.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.110713E+10 | 0.279980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102898E+10 | 0.106754E+10 | 0.163034E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104668E+10 | 7105364.03 | 0.182521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101423E+10 | 0.00 | 0.365515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106679E+10 | 0.00 | 0.514720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126728E+11 | 0.791349E+10 | 0.273590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.977849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.114132E+10 | 0.279980E+10 | 0.514720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.106396E+10 | 0.00 | 0.140056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.953392E+09 | 0.00 | 0.114828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.975752E+09 | 0.00 | 0.823610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.721074E+09 | 0.00 | 0.928135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.723550E+09 | 0.00 | 55795673.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.721899E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.694133E+09 | 0.188227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.749664E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.694133E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.741458E+09 | 0.00 | 0.165898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.906107E+09 | 0.00 | 0.872753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114823E+10 | 0.00 | 0.171842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100934E+11 | 0.188227E+09 | 0.622791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.694133E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.114823E+10 | 0.188227E+09 | 0.171842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.106429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.977849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104681E+10 | 0.00 | 0.00 | 0.00 | 18324751.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108254E+10 | 0.00 | 0.00 | 0.00 | 41776503.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.106966E+10 | 0.00 | 0.00 | 0.00 | 0.265173E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102650E+10 | 0.00 | 0.00 | 0.00 | 0.520593E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.110713E+10 | 0.00 | 0.00 | 0.00 | 0.584353E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102898E+10 | 0.00 | 0.00 | 0.00 | 0.226619E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104668E+10 | 0.00 | 0.00 | 0.00 | 1562462.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126728E+11 | 0.00 | 0.00 | 0.00 | 0.165840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.977849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.114132E+10 | 0.00 | 0.00 | 0.00 | 0.584353E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.106396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.953392E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.975752E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.721074E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.723550E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.721899E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.694133E+09 | 0.00 | 0.00 | 0.00 | 48693100.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.749664E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.694133E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.741458E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.906107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100934E+11 | 0.00 | 0.00 | 0.00 | 48693100.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.694133E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.114823E+10 | 0.00 | 0.00 | 0.00 | 48693100.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201339E+10 | 0.00 | 0.00 | 0.12 |
February | 2410566.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174742E+10 | 0.00 | 0.00 | 0.13 |
March | 19611009.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189554E+10 | 0.00 | 0.00 | 0.13 |
April | 0.642071E+09 | 0.00 | 0.00 | 100954.99 | 292948.37 | 0.696632E+09 | 67931348.51 | 0.00 | 0.13 |
May | 0.902850E+09 | 0.00 | 0.00 | 241972.08 | 0.00 | 0.364621E+09 | 0.143578E+09 | 0.00 | 0.13 |
June | 0.523684E+09 | 4414197.07 | 0.00 | 1513759.18 | 0.00 | 12114572.97 | 0.623821E+09 | 0.00 | 0.13 |
July | 0.156238E+09 | 6099750.28 | 0.00 | 2906897.67 | 0.00 | 0.00 | 0.705800E+09 | 0.00 | 0.12 |
August | 55858317.41 | 0.00 | 0.00 | 3499918.74 | 0.00 | 0.00 | 0.748627E+09 | 0.00 | 0.14 |
September | 0.450087E+09 | 0.00 | 0.00 | 1310137.05 | 0.00 | 0.00 | 0.558786E+09 | 0.00 | 0.13 |
October | 0.548958E+09 | 0.00 | 0.00 | 7234.10 | 0.00 | 0.805870E+09 | 11608230.24 | 0.00 | 0.12 |
November | 43282488.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158146E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196383E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.334505E+10 | 10513947.34 | 0.00 | 9580873.81 | 292948.37 | 0.110809E+11 | 0.286015E+10 | 0.00 | 0.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.902850E+09 | 6099750.28 | 0.00 | 3499918.74 | 292948.37 | 0.201339E+10 | 0.748627E+09 | 0.00 | 0.14 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.256498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269439E+10 | 0.00 | 0.00 | 0.17 |
February | 0.316250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122680E+10 | 0.00 | 0.00 | 0.18 |
March | 0.396770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680384E+09 | 0.00 | 0.00 | 0.19 |
April | 0.370532E+10 | 0.00 | 0.00 | 0.00 | 5636826.06 | 0.00 | 0.00 | 0.00 | 0.18 |
May | 0.398856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
June | 0.397045E+10 | 0.00 | 0.00 | 0.00 | 943173.21 | 0.00 | 0.00 | 0.00 | 0.19 |
July | 0.364040E+10 | 0.00 | 0.00 | 279995.47 | 1546452.87 | 0.00 | 0.137955E+09 | 0.00 | 0.18 |
August | 0.366909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
September | 0.317540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
October | 0.320283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49025455.46 | 0.00 | 0.00 | 0.17 |
November | 0.290975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.937782E+09 | 0.00 | 0.00 | 0.17 |
December | 0.188047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310795E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.398375E+11 | 0.00 | 0.00 | 279995.47 | 8126452.14 | 0.869634E+10 | 0.137955E+09 | 0.00 | 0.18 |
Minimum of Months | 0.188047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.398856E+10 | 0.00 | 0.00 | 279995.47 | 5636826.06 | 0.310795E+10 | 0.137955E+09 | 0.00 | 0.19 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:42:42
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.151231E+12 | 0.129754E+11 | 0.00 | 0.727276E+10 | 0.145444E+11 |
February | 0.259232E+12 | 0.168231E+11 | 0.00 | 0.613914E+10 | 0.114888E+11 |
March | 0.334053E+12 | 0.120905E+11 | 0.00 | 0.656324E+10 | 0.700379E+10 |
April | 0.948962E+12 | 0.163116E+11 | 0.00 | 0.510613E+10 | 0.133812E+10 |
May | 0.113735E+13 | 0.408383E+11 | 0.00 | 0.539985E+10 | 0.764878E+09 |
June | 0.116005E+13 | 0.383970E+11 | 0.00 | 0.512623E+10 | 0.158874E+10 |
July | 0.119050E+13 | 0.389175E+11 | 0.00 | 0.463594E+10 | 0.327416E+10 |
August | 0.985603E+12 | 0.328588E+11 | 0.00 | 0.447708E+10 | 0.338416E+10 |
September | 0.714766E+12 | 0.269347E+11 | 0.00 | 0.418558E+10 | 0.137138E+10 |
October | 0.315563E+12 | 0.191730E+11 | 0.00 | 0.461831E+10 | 0.167291E+10 |
November | 0.962669E+11 | 0.180956E+11 | 0.00 | 0.547227E+10 | 0.760593E+10 |
December | 0.108990E+11 | 0.269369E+11 | 0.00 | 0.695229E+10 | 0.192148E+11 |
Annual Sum or Average | 0.730447E+13 | 0.300352E+12 | 0.00 | 0.659488E+11 | 0.732520E+11 |
Minimum of Months | 0.108990E+11 | 0.120905E+11 | 0.00 | 0.418558E+10 | 0.764878E+09 |
Maximum of Months | 0.119050E+13 | 0.408383E+11 | 0.00 | 0.727276E+10 | 0.192148E+11 |