Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:42
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2023-10-16 10:42:58
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:58
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 427.56 | 88.43 | 88.43 |
Net Site Energy | 427.56 | 88.43 | 88.43 |
Total Source Energy | 1273.14 | 263.31 | 263.31 |
Net Source Energy | 1273.14 | 263.31 | 263.31 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 38.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 42.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 85.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 38.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 388.70 | 38.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 38.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 42.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 85.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 61.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 12.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 25.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 24.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 38.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 42.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 85.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 61.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 38.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 24.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 30.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 21.74 | 8.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 80.39 | 8.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 30.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 21.74 | 8.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 80.39 | 8.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 388.701 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 388.701 | 100.00 |
Total On-Site and Utility Electric Sources | 388.701 | 100.00 |
Total Electricity End Uses | 388.701 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 35.17 |
Time Setpoint Not Met During Occupied Cooling | 20.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2944.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:58
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:42 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 68.38 |
Skylight-Roof Ratio [%] | 1.49 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 6.9682 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 7.4271 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.5521 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8362 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8362 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 6.9682 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 7.4271 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.5521 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.8362 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.8362 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.8362 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:58
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 15-JUN-15:00 | 27-DEC-06:30 | - | - | - | - | - | - | - | - | - | - | 29-JUN-11:20 |
Heating | 0.00 | 72920.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 14875.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5628.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5214.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1585.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 37338.71 | 72920.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 72920.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 14875.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 5628.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2909.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1585.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:58
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 42.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 135.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 270.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 195.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 121.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 76.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1231.02 | 42.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 8.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 27.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 55.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 25.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 254.60 | 8.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 8.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 27.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 55.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 25.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 254.60 | 8.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:58
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.26 |
ZONE2 FINE STORAGE DIRECT AIR | 3.20 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 2.42 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 2.42 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 85933.58 |
PSZ-OFFICE HEATING COIL | 27881.80 |
PSZ-FINE STORAGE HEATING COIL | 91353.46 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 85933.59 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.26 | 1.26 | 1.26 | 1.26 | 1.26 | 1.26 | 1.00 | 1.00 | 1.26 |
PSZ-FINE STORAGE | 3.20 | 3.20 | 3.20 | 3.20 | 3.20 | 3.20 | 1.00 | 1.00 | 3.20 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.26 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 3.20 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.26 | 1395.50 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.20 | 3425.01 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.26 | 1.26 | 1.26 | 0.831888 | 21595.65 | 27881.80 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 3.20 | 3.20 | 3.20 | 2.11 | 66422.44 | 91353.46 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.26 | 0.630218 | 0.840293 | 21595.65 | 10797.83 | 0.800210 | 0.800210 |
PSZ-FINE STORAGE COOLING COIL | 3.20 | 1.60 | 2.13 | 66422.44 | 33211.22 | 0.762280 | 0.762280 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:58
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:58
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:58
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 6.968 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 15.042 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 7.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.427 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.552 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 6.111 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1650.627 | 6.968 | 129.474 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1650.627 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 10348.979 | 7.427 | 344.966 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10348.979 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 11383.888 | 3.552 | 164.984 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11383.888 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2405 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5892 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.6534 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 1.134 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 2.044 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 1.134 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.158 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.697 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.431 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7826 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4892 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7826 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.77015739E-08 | 0.38457199E-13 | 0.23136523E-13 | 0.0000000 |
2 | 1 | -5.2160498 | 0.48395528E-04 | -0.66612159E-04 | 0.14765390E-08 |
3 | 0 | 5.4565497 | 0.24045158 | 0.24056658 | |
4 | 2 | 0.53319589E-11 | 0.95168195E-16 | 0.18684196E-15 | 0.0000000 |
5 | 1 | -5.2159738 | 0.43009049E-04 | -0.27188221E-04 | 0.68723469E-11 |
6 | 0 | 5.8052090 | 0.58919217 | 0.58926237 | |
7 | 4 | 0.74747876E-12 | 0.20825084E-15 | -0.25659737E-14 | 0.12362927E-15 |
8 | 3 | -0.37328678E-03 | 0.45238042E-06 | -0.54038165E-04 | 0.14344535E-12 |
9 | 2 | 1.7123825 | 0.10013958E-01 | 1.1198054 | -0.71564441E-04 |
10 | 1 | -7.1648294 | 0.26145347 | -16.966117 | 0.32817431 |
11 | 0 | 5.8918369 | 0.16754891 | 16.285382 | |
12 | 4 | 0.65556131E-12 | 0.57298371E-15 | -0.14028959E-14 | 0.12439065E-15 |
13 | 3 | -0.34087882E-03 | 0.75102955E-06 | -0.49042705E-04 | 0.12583838E-12 |
14 | 2 | 1.6337693 | 0.17263784E-01 | 1.0601096 | -0.65347397E-04 |
15 | 1 | -7.2734424 | 0.46143774 | -16.581274 | 0.31301327 |
16 | 0 | 6.4190060 | 0.30028979 | 16.300205 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.0441747 | 2.0441747 | 2.0441747 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.14028959E-14 | 0.57298371E-15 | 0.65556131E-12 | 0.12439065E-15 |
85 | 3 | -0.49042705E-04 | 0.75102955E-06 | -0.34087882E-03 | 0.12583838E-12 |
86 | 2 | 1.0601096 | 0.17263784E-01 | 1.6337693 | -0.65347397E-04 |
87 | 1 | -16.581274 | 0.46143774 | -7.2734424 | 0.31301327 |
88 | 0 | 16.300205 | 0.30028979 | 6.4190060 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.423_SHGC_SOUTH_0.249 | 34 | 1 | VerySmooth | 2.404 | 2.404 | 1.000 | 0.250 | ||
2 | NONRESWINDOW_U_0.423_SHGC_NORTH_0.249 | 35 | 1 | VerySmooth | 2.404 | 2.404 | 1.000 | 0.250 | ||
3 | NONRESWINDOW_U_0.423_SHGC_EAST_0.249 | 36 | 1 | VerySmooth | 2.404 | 2.404 | 1.000 | 0.250 | ||
4 | NONRESWINDOW_U_0.423_SHGC_WEST_0.249 | 37 | 1 | VerySmooth | 2.404 | 2.404 | 1.000 | 0.250 | ||
5 | SKYLIGHT_U_0.55_SHGC_0.3 | 38 | 1 | VerySmooth | 3.127 | 3.127 | 1.000 | 0.301 | ||
6 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | 39 | 1 | VerySmooth | 5.108 | 5.108 | 1.000 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.99333E-002 | 0.16038 | 0.62145 | 0.62145 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12244 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.99333E-002 | 0.16038 | 0.62145 | 0.62145 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12244 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.99333E-002 | 0.16038 | 0.62145 | 0.62145 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12244 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.99333E-002 | 0.16038 | 0.62145 | 0.62145 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12244 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 1.15759E-002 | 0.21195 | 0.55558 | 0.55558 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 7.71143E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 0.12500 | 0.12500 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | CurtainWall | 3.043 | 0.303 | 0.402 |
2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.867 | 0.549 | 0.401 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.331 | 7.274E-004 | 4.751E-004 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.3341E-005 |
2 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.8427E-004 |
3 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4611E-005 |
4 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2925E-004 |
5 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4040E-005 |
6 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.7892E-004 |
7 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5724E-005 |
8 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.5867E-004 |
9 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5484E-004 |
10 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.3285E-004 |
11 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3077E-004 |
12 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.6864E-004 |
13 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4666E-004 |
14 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.8721E-004 |
15 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3414E-004 |
16 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4540E-004 |
17 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5692E-004 |
18 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4753E-004 |
19 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0013E-004 |
20 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6104E-004 |
21 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.4522E-004 |
22 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1879E-004 |
23 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8792E-004 |
24 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6675E-005 |
25 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.1589E-004 |
26 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.3584E-005 |
27 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5423E-004 |
28 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.8442E-005 |
29 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0576E-003 |
30 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2691E-005 |
31 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3392E-003 |
32 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0724E-005 |
33 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4913E-004 |
34 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1872E-005 |
35 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8300E-004 |
36 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3868E-005 |
37 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.1517E-004 |
38 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8938E-005 |
39 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9718E-004 |
40 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6272E-005 |
41 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.9812E-004 |
42 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.3744E-005 |
43 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.3992E-004 |
44 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4728E-005 |
45 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5889E-004 |
46 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4205E-005 |
47 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7955E-004 |
48 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4789E-005 |
49 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.9538E-004 |
50 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4672E-005 |
51 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1905E-003 |
52 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5847E-005 |
53 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2950E-004 |
54 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4546E-005 |
55 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3679E-004 |
56 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4861E-005 |
57 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1435E-003 |
58 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4861E-005 |
59 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4565E-003 |
60 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.7502E-005 |
61 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0387E-003 |
62 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0072E-005 |
63 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1133E-003 |
64 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6508E-005 |
65 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7041E-003 |
66 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.5456E-005 |
67 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6235E-003 |
68 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0302E-004 |
69 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3861E-003 |
70 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.7361E-005 |
71 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5808E-003 |
72 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1684E-005 |
73 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8263E-004 |
74 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0917E-004 |
75 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.8537E-004 |
76 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.3765E-004 |
77 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.0827E-004 |
78 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4397E-004 |
79 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6286E-003 |
80 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1734E-005 |
81 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9657E-004 |
82 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.4211E-004 |
83 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6275E-004 |
84 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.8279E-004 |
85 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8305E-004 |
86 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.6538E-004 |
87 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3102E-004 |
88 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8162E-004 |
89 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.1530E-005 |
90 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9823E-003 |
91 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.0686E-005 |
92 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.3170E-003 |
93 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.9140E-005 |
94 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6786E-003 |
95 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0760E-004 |
96 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8446E-004 |
97 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2334E-005 |
98 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9575E-003 |
99 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8585E-005 |
100 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9569E-003 |
101 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8357E-005 |
102 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6227E-003 |
103 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7398E-005 |
104 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.1825E-003 |
105 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0430E-005 |
106 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.7351E-004 |
107 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.7195E-005 |
108 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2847E-004 |
109 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.7443E-005 |
110 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1312E-003 |
111 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5431E-005 |
112 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2422E-003 |
113 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2552E-005 |
114 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8759E-005 |
115 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8315E-005 |
116 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0282E-005 |
117 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7180E-005 |
118 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6531E-005 |
119 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4598E-005 |
120 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5286E-005 |
121 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6118E-005 |
122 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8985E-005 |
123 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8335E-005 |
124 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3113E-005 |
125 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5005E-005 |
126 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1182E-005 |
127 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1685E-005 |
128 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2542E-005 |
129 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2453E-005 |
130 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9640E-005 |
131 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8273E-005 |
132 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8634E-005 |
133 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7342E-005 |
134 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9321E-005 |
135 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4582E-005 |
136 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1042E-005 |
137 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9352E-004 |
138 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2106E-004 |
139 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2008E-004 |
140 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3185E-004 |
141 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3504E-004 |
142 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.7657E-005 |
143 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2514E-005 |
144 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3080E-005 |
145 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6131E-005 |
146 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5360E-004 |
147 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8990E-005 |
148 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9579E-004 |
149 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9400E-005 |
150 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5683E-004 |
151 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4916E-005 |
152 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6240E-005 |
153 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8788E-005 |
154 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3577E-005 |
155 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2311E-005 |
156 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3243E-005 |
157 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0454E-005 |
158 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3948E-005 |
159 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4899E-005 |
160 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1079E-005 |
161 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0169E-004 |
162 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2358E-005 |
163 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3062E-004 |
164 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2854E-005 |
165 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3712E-004 |
166 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0182E-005 |
167 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2500E-005 |
168 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7738E-005 |
169 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1240E-004 |
170 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1269E-004 |
171 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1417E-004 |
172 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1056E-003 |
173 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1585E-004 |
174 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1808E-004 |
175 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0532E-005 |
176 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7293E-004 |
177 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7724E-004 |
178 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1979E-004 |
179 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4960E-004 |
180 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3722E-004 |
181 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6671E-004 |
182 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0486E-004 |
183 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5069E-004 |
184 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0290E-004 |
185 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0709E-004 |
186 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5443E-005 |
187 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8810E-004 |
188 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.4585E-005 |
189 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7586E-004 |
190 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7767E-005 |
191 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5061E-004 |
192 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8433E-005 |
193 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1673E-004 |
194 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5843E-005 |
195 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1950E-004 |
196 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5045E-005 |
197 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1818E-004 |
198 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6897E-005 |
199 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0473E-005 |
200 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3210E-005 |
201 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0181E-003 |
202 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7009E-005 |
203 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1438E-003 |
204 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.3275E-005 |
205 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0144E-003 |
206 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.8057E-005 |
207 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2387E-004 |
208 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6113E-005 |
209 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6709E-004 |
210 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4805E-004 |
211 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0786E-003 |
212 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5788E-004 |
213 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.8980E-004 |
214 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1606E-004 |
215 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2445E-004 |
216 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5215E-004 |
217 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5697E-004 |
218 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7453E-005 |
219 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5316E-004 |
220 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6098E-005 |
221 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9006E-004 |
222 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9288E-005 |
223 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2708E-004 |
224 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5686E-005 |
225 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5183E-004 |
226 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9357E-003 |
227 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4703E-004 |
228 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2875E-003 |
229 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8592E-004 |
230 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5559E-003 |
231 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2726E-004 |
232 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9459E-004 |
233 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6705E-004 |
234 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7716E-005 |
235 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5248E-004 |
236 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5927E-005 |
237 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2768E-004 |
238 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9744E-005 |
239 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9961E-004 |
240 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7482E-005 |
241 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1132E-003 |
242 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.9594E-005 |
243 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1044E-003 |
244 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2827E-005 |
245 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5304E-003 |
246 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.5900E-005 |
247 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6165E-003 |
248 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3274E-005 |
249 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0851E-003 |
250 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8131E-004 |
251 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0703E-003 |
252 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5633E-004 |
253 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5024E-003 |
254 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5625E-004 |
255 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6195E-003 |
256 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2024E-004 |
257 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6340E-004 |
258 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8889E-003 |
259 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4836E-004 |
260 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9464E-003 |
261 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2286E-004 |
262 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4314E-003 |
263 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0001E-004 |
264 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6530E-003 |
265 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3444E-004 |
266 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6471E-005 |
267 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1675E-004 |
268 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4553E-005 |
269 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7312E-004 |
270 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7783E-005 |
271 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9852E-004 |
272 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7461E-005 |
273 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3323E-004 |
274 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.4458E-004 |
275 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1535E-004 |
276 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2688E-004 |
277 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6995E-004 |
278 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1149E-003 |
279 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9891E-004 |
280 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6031E-003 |
281 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9494E-004 |
282 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0775E-005 |
283 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1084E-004 |
284 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.3190E-005 |
285 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1991E-004 |
286 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.1275E-005 |
287 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5919E-003 |
288 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3045E-005 |
289 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9062E-004 |
290 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6623E-004 |
291 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0594E-004 |
292 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2858E-004 |
293 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0926E-004 |
294 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7161E-004 |
295 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5949E-003 |
296 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1554E-004 |
297 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0677E-005 |
298 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8720E-004 |
299 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7409E-005 |
300 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3264E-004 |
301 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5165E-005 |
302 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0566E-004 |
303 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2574E-004 |
304 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7337E-004 |
305 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3789E-004 |
306 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4517E-004 |
307 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9372E-004 |
308 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2082E-004 |
309 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5588E-004 |
310 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5865E-004 |
311 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1039E-004 |
312 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4748E-004 |
313 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6040E-005 |
314 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6237E-005 |
315 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8299E-005 |
316 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3627E-005 |
317 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5116E-005 |
318 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3524E-005 |
319 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1671E-005 |
320 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7584E-005 |
321 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0705E-005 |
322 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4234E-005 |
323 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7605E-005 |
324 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2495E-005 |
325 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6498E-005 |
326 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4523E-005 |
327 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2556E-004 |
328 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5637E-005 |
329 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9716E-005 |
330 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1410E-004 |
331 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1860E-005 |
332 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.3000E-005 |
333 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.3800E-005 |
334 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.5914E-005 |
335 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9741E-005 |
336 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6869E-004 |
337 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0355E-004 |
338 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8644E-005 |
339 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5043E-005 |
340 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6335E-005 |
341 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7874E-005 |
342 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9552E-005 |
343 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4732E-004 |
344 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0119E-004 |
345 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9568E-005 |
346 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1773E-005 |
347 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1823E-005 |
348 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0385E-005 |
349 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4264E-005 |
350 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1475E-005 |
351 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9684E-005 |
352 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3161E-005 |
353 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3776E-004 |
354 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6822E-005 |
355 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9388E-004 |
356 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0591E-005 |
357 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5809E-004 |
358 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8239E-005 |
359 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0983E-004 |
360 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5702E-005 |
361 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0336E-004 |
362 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4529E-005 |
363 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4969E-005 |
364 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0280E-005 |
365 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8327E-005 |
366 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1896E-005 |
367 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4724E-004 |
368 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8139E-005 |
369 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 3.4538E-003 |
370 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 4.1063E-004 |
371 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 3.0799E-003 |
372 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.7200E-004 |
373 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.9236E-003 |
374 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.5744E-004 |
375 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.7866E-003 |
376 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1636E-004 |
377 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.1623E-004 |
378 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.7457E-003 |
379 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.8473E-004 |
380 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.1502E-003 |
381 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.6473E-004 |
382 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.1025E-003 |
383 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.1270E-004 |
384 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.3974E-003 |
385 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.0169E-003 |
386 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.1979E-004 |
387 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.2578E-003 |
388 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.7386E-004 |
389 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.4756E-003 |
390 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.3220E-004 |
391 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.2429E-003 |
392 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.9254E-004 |
393 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.0313E-003 |
394 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.1985E-004 |
395 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.2641E-003 |
396 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.7389E-004 |
397 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.4575E-003 |
398 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.3217E-004 |
399 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.2428E-003 |
400 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.9254E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11072.55764 | 13287.06917 | 1.05036 | 1.26044 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 37.14667 | 6.86994E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 8345.35573 | 10014.42687 | 0.27003 | 0.32403 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20000 | 2.80840E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 36072.21168 | 43286.65402 | 2.66734 | 3.20080 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 38.10000 | 6.87148E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 22921.59502 | 27505.91402 | 0.62493 | 0.74991 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | -5.20000 | 2.80840E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 37.97000 | 6.87126E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 71611.32269 | 85933.58722 | 2.01748 | 2.42097 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 17174.02 | 1.26044 | 1.26044 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 9261.20 | 0.32403 | 0.32403 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 54455.26 | 3.20080 | 3.20080 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 28486.97 | 0.74991 | 0.74991 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.26044 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.20080 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.42097 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 2.42097 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 85933.58216 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 85933.58722 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.26044 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.26044 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.26044 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.26044 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.26044 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.26044 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.20080 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.20080 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.20080 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.20080 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.20080 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.20080 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.26044 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.20080 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.26044 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.26044 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1395.50343 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.26044 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.26044 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.26044 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.83189 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.26044 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.63022 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.84029 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21595.65000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10797.82500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80021 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80021 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21595.65000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27881.80130 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 27881.80130 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.20080 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.20080 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3425.00979 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.20080 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.20080 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.20080 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.11253 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.20080 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.60040 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.13387 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 66422.44000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 33211.22000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76228 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76228 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 66422.44000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 91353.45859 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 91353.45859 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 20617.5 | 11.48 | 11.22 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 63936.6 | 11.73 | 11.46 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 4.8800986824E-002 | 3.2023954878E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 6.5767153814E-002 | 6.7083596356E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 6.2091706383E-002 | 5.1402212875E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:58
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 11393.79 | 452.66 | 0.00 | 30.64 | 219.75 | 12096.90 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:58
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:58
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.233 | 0.240 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.545 | 0.589 | 3204.84 | 3157.28 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.892 | 1.134 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.892 | 1.134 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.423_SHGC_WEST_0.249 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.404 | 0.250 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.423_SHGC_WEST_0.249 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.404 | 0.250 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.423_SHGC_NORTH_0.249 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.404 | 0.250 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.423_SHGC_NORTH_0.249 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.404 | 0.250 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 86.04 | 4.074 | 0.429 | 0.370 | |||||||||||||||||
North Total or Average | 6.51 | 2.404 | 0.250 | 0.250 | |||||||||||||||||
Non-North Total or Average | 79.53 | 4.210 | 0.443 | 0.380 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:58
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:58
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 6.9682 | 236.88 | 1650.63 | LightsWired | LTG_SCH_OFFICE | 52.33 | 168.00 | 33.20 | 0.0000 | Y | 10.29 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 7.4271 | 1393.41 | 10348.98 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 19.22 | 0.0000 | Y | 37.33 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.5521 | 3204.84 | 11383.89 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 17.66 | 0.0000 | Y | 37.74 |
Interior Lighting Total | 4.8362 | 4835.13 | 23383.49 | 85.36 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10348.98 | 2587.24 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10348.98 | 2587.24 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 11383.89 | 2845.97 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 11383.89 | 2845.97 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.29 | 1650.63 | 478.68 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.10 | 1650.63 | 165.06 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 123.84 | AstronomicalClock | - | 41.77 | 41.77 | 0.97 | |
EXTERIOR_LIGHTS_B | 4305.62 | AstronomicalClock | - | 83.77 | 62.77 | 50.73 | |
EXTERIOR_LIGHTS_C | 1091.36 | AstronomicalClock | - | 83.77 | 48.79 | 10.00 | |
Exterior Lighting Total | 5520.82 | 61.70 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:58
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21595.65 | 17281.06 | 4314.59 | 0.80 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 66422.44 | 50632.50 | 15789.94 | 0.76 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 20617.5 | 11.48 | 11.22 | ||||
PSZ-FINE STORAGE COOLING COIL | 63936.6 | 11.73 | 11.46 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 85933.58 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 27881.80 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 91353.46 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.42 | 224.93 | 92.91 | 1.00 | 3.47 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.26 | 1395.50 | 1107.16 | 1.00 | 1.35 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 3.20 | 3425.01 | 1070.05 | 1.00 | 1.26 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:58
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11072.56 | 13287.07 | 56.09 | 1.050 | 1.260 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 23.90 | 23.90 | 0.00823 | 37.15 | 0.00687 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 36072.21 | 43286.65 | 31.07 | 2.667 | 3.201 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 26.70 | 26.70 | 0.00819 | 38.10 | 0.00687 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 37.68 | 0.00696 | 37.97 | 0.00687 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8345.36 | 10014.43 | 42.28 | 0.270 | 0.324 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00791 | -5.20 | 0.00281 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 22921.60 | 27505.91 | 19.74 | 0.625 | 0.750 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 15.56 | 15.56 | 0.00686 | -5.20 | 0.00281 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 71611.32 | 85933.59 | 26.81 | 2.017 | 2.421 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00621 | -5.20 | 0.00281 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.26 | 1.26 | 0.32 | 0.32 | 1.2604 | 1.2604 | 1.2604 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.20 | 3.20 | 0.75 | 0.75 | 3.2008 | 3.2008 | 3.2008 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 85933.582 | 85933.582 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 85933.58 | 85933.58 | 2.420975 | 10.00 | 7.29 | 0.00621002 | 43.33 | 20.46 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 10.00 | 0.00621002 | 70.7409 | 85933.59 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 21595.650 | 17281.055 | 1.260440 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 10797.83 | 10616.43 | 0.840293 | 26.03 | 15.31 | 0.00811926 | 12.00 | 10.01 | 0.00800000 | 37.32 | 0.00687023 | 17.93 | 12.1725 | 23.90 | 0.00822961 | 38.6709 | 11068.68 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 27881.801 | 27881.801 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 27881.80 | 27881.80 | 1.260437 | 18.92 | 12.24 | 0.00749192 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 8.1150 | 21.10 | 0.00790556 | 44.0598 | 8345.36 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 66422.440 | 50632.498 | 3.200800 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33211.22 | 33167.30 | 2.133867 | 29.22 | 16.27 | 0.00801091 | 12.00 | 10.01 | 0.00800000 | 38.10 | 0.00687148 | 18.17 | 19.9034 | 26.70 | 0.00818523 | 32.5634 | 36072.21 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 91353.459 | 91353.459 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 91353.46 | 91353.46 | 3.200802 | 12.80 | 8.64 | 0.00632529 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 13.2689 | 15.56 | 0.00686333 | 54.2528 | 22921.60 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:42:58
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 85933.582 | 85933.582 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 2.420975 | 2.52830069 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 85933.58 | 85933.58 | 1.0000 | 2.52830069 | 2.420975 | 10.00 | 7.29 | 0.00621002 | 25693.1 | 43.33 | 20.46 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 85933.58 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 10.00 | 0.00621002 | 10.00 | 0.00621002 | 70.7409 | 85933.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21595.650 | 17281.055 | 1.260440 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9333 | 1004.8586 | 1.0443 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.260437 | 1.31631397 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | Sensible | 10797.83 | 10616.43 | 1.0000 | 0.87754499 | 0.840293 | 26.03 | 15.31 | 0.00811926 | 46852.6 | 12.00 | 10.01 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10797.83 | 37.32 | 0.00687023 | 17.93 | 0.10228463 | 12.1725 | 23.90 | 0.00822961 | 23.90 | 0.00822961 | 38.6709 | 11068.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27881.801 | 27881.801 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.260437 | 1.31631397 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 27881.80 | 27881.80 | 1.0000 | 1.31631397 | 1.260437 | 18.92 | 12.24 | 0.00749192 | 38012.6 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27881.80 | -5.20 | 0.00280840 | -5.20 | 0.10228463 | 8.1150 | 21.05 | 0.00790556 | 21.10 | 0.00790556 | 44.0598 | 8345.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 66422.440 | 50632.498 | 3.200800 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7319 | 1004.8586 | 1.0443 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.200802 | 3.34269943 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 33211.22 | 33167.30 | 1.0000 | 2.22846467 | 2.133867 | 29.22 | 16.27 | 0.00801091 | 49828.1 | 12.00 | 10.01 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33211.22 | 38.10 | 0.00687148 | 18.17 | 0.42471127 | 19.9034 | 26.70 | 0.00818523 | 26.70 | 0.00818523 | 32.5634 | 36072.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 91353.459 | 91353.459 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.200802 | 3.34269943 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | Sensible | 91353.46 | 91353.46 | 1.0000 | 3.34269943 | 3.200802 | 12.80 | 8.64 | 0.00632529 | 28834.6 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 91353.46 | -5.20 | 0.00280840 | -5.20 | 0.42471127 | 13.2689 | 15.56 | 0.00686333 | 15.56 | 0.00686333 | 54.2528 | 22921.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:58
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.26 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 3.20 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2451.67 | 1946.83 | 1065.50 |
ZONE2 FINE STORAGE | 3075.83 | 2919.67 | 2442.17 |
ZONE3 BULK STORAGE | 3217.00 | 3292.17 | 2937.33 |
Facility | 3238.50 | 3475.50 | 2944.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 30.17 | 22.33 | 29.83 | 20.67 |
ZONE2 FINE STORAGE | 65.00 | 113.67 | 9.50 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 91.00 | 136.00 | 35.17 | 20.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:58
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.673 | 0.291 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.626 | 0.220 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.116 | 0.000 | 0.944 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:42:58
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.54 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2429488.34 | 0.00 | 2429488.34 | 1717458.42 | 4146946.76 | 3225648.14 | 5606.94 | 2335.48 | 817.59 | 0.22 |
ZONE2 FINE STORAGE | 6783921.64 | 0.00 | 6783921.64 | 6171176.23 | 12955097.86 | 13393694.68 | 5643.84 | 2546.42 | 569.74 | 34.37 |
ZONE3 BULK STORAGE | 0.00 | 0.21E+09 | 0.21E+09 | 30267012.76 | 0.24E+09 | 30805497.77 | 6659.75 | 30.20 | 2070.05 | 4863.91 |
Total Facility | 9213409.98 | 0.21E+09 | 0.22E+09 | 38155647.40 | 0.26E+09 | 47424840.58 | 7637.65 | 2833.90 | 3041.13 | 4864.86 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1856 | 0.0000 | 0.1856 | 0.0806 | 0.2662 | 0.1023 | 483.15 | 2335.48 | 817.37 |
ZONE2 FINE STORAGE | 0.5034 | 0.0000 | 0.5034 | 0.1773 | 0.6807 | 0.4247 | 554.12 | 2546.42 | 535.46 |
ZONE3 BULK STORAGE | 0.0000 | 8.8321 | 8.8321 | 1.1166 | 9.9487 | 0.9768 | 2491.62 | 14.86 | 1129.52 |
Total Facility | 0.6889 | 8.8321 | 9.5210 | 1.3745 | 10.8955 | 1.5038 | 2513.65 | 2818.56 | 2074.46 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2649615.12 | 0.00 | 2649615.12 | 3225648.14 | 5605.69 | 0.17 | 3154.15 | 0.22 |
PSZ-FINE STORAGE | 7398734.84 | 0.00 | 7398734.84 | 13393694.68 | 5642.34 | 0.67 | 3116.99 | 34.37 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2024 | 0.0000 | 0.2024 | 0.1023 | 481.90 | 0.17 | 3153.93 |
PSZ-FINE STORAGE | 0.5490 | 0.0000 | 0.5490 | 0.4247 | 552.62 | 0.67 | 3082.71 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2867.82 | 294.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2945.45 | 187.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2177 | 0.3800 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6219 | 0.9937 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:58
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 446 |
Defaulted Fields | 391 |
Fields with Defaults | 1172 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:42:58
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 388.70 | 1550.86 | 01-JAN-09:10 | 37338.71 | 15-JUN-16:00 |
Electricity:Building | 234.49 | 1069.86 | 01-JAN-09:10 | 19149.10 | 18-SEP-15:00 |
Electricity:Zone:ZONE1 OFFICE | 39.45 | 520.87 | 01-JAN-00:10 | 2846.16 | 17-NOV-17:00 |
Electricity:SpaceType:GENERAL | 221.87 | 1069.86 | 01-JAN-09:10 | 18546.12 | 02-DEC-16:00 |
InteriorLights:Electricity | 85.36 | 599.99 | 01-JAN-09:10 | 8510.94 | 02-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.29 | 51.00 | 01-JAN-00:10 | 1011.11 | 17-NOV-17:00 |
InteriorLights:Electricity:SpaceType:GENERAL | 85.36 | 599.99 | 01-JAN-09:10 | 8510.94 | 02-DEC-16:00 |
LightsWired:InteriorLights:Electricity | 85.36 | 599.99 | 01-JAN-09:10 | 8510.94 | 02-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.29 | 51.00 | 01-JAN-00:10 | 1011.11 | 17-NOV-17:00 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 85.36 | 599.99 | 01-JAN-09:10 | 8510.94 | 02-DEC-16:00 |
Electricity:Zone:ZONE2 FINE STORAGE | 37.33 | 299.97 | 01-JAN-00:10 | 3686.68 | 07-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 37.33 | 299.97 | 01-JAN-00:10 | 3686.68 | 07-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 37.33 | 299.97 | 01-JAN-00:10 | 3686.68 | 07-DEC-16:00 |
Electricity:Zone:ZONE3 BULK STORAGE | 157.71 | 249.02 | 01-JAN-09:10 | 13529.08 | 29-SEP-15:50 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 37.74 | 249.02 | 01-JAN-09:10 | 3894.15 | 07-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 37.74 | 249.02 | 01-JAN-09:10 | 3894.15 | 07-DEC-16:00 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 38.29 | 0.00 | 01-JAN-00:10 | 5237.32 | 15-JUN-15:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 12.63 | 0.00 | 01-JAN-00:10 | 2305.29 | 30-APR-15:30 |
Ventilation (simple):Fans:Electricity | 12.63 | 0.00 | 01-JAN-00:10 | 2305.29 | 30-APR-15:30 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 12.63 | 0.00 | 01-JAN-00:10 | 2305.29 | 30-APR-15:30 |
ElectricityPurchased:Facility | 388.70 | 1550.86 | 01-JAN-09:10 | 37338.71 | 15-JUN-16:00 |
ElectricityPurchased:Plant | 388.70 | 1550.86 | 01-JAN-09:10 | 37338.71 | 15-JUN-16:00 |
Cogeneration:ElectricityPurchased | 388.70 | 1550.86 | 01-JAN-09:10 | 37338.71 | 15-JUN-16:00 |
General:Cogeneration:ElectricityPurchased | 388.70 | 1550.86 | 01-JAN-09:10 | 37338.71 | 15-JUN-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 388.70 | 1550.86 | 01-JAN-09:10 | 37338.71 | 15-JUN-16:00 |
ElectricityNet:Plant | 388.70 | 1550.86 | 01-JAN-09:10 | 37338.71 | 15-JUN-16:00 |
Cogeneration:ElectricityNet | 388.70 | 1550.86 | 01-JAN-09:10 | 37338.71 | 15-JUN-16:00 |
General:Cogeneration:ElectricityNet | 388.70 | 1550.86 | 01-JAN-09:10 | 37338.71 | 15-JUN-16:00 |
Electricity:HVAC | 68.30 | 0.00 | 01-JAN-00:10 | 18021.25 | 15-JUN-15:10 |
General:Fans:Electricity | 25.66 | 0.00 | 01-JAN-00:10 | 2932.03 | 15-JUN-15:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 42.64 | 0.00 | 01-JAN-00:10 | 15089.22 | 15-JUN-15:10 |
General:Cooling:Electricity | 42.64 | 0.00 | 01-JAN-00:10 | 15089.22 | 15-JUN-15:10 |
ExteriorLights:Electricity | 61.70 | 0.00 | 01-JAN-07:20 | 5520.82 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 61.70 | 0.00 | 01-JAN-07:20 | 5520.82 | 01-JAN-06:10 |
Electricity:Plant | 24.21 | 481.00 | 07-MAR-06:10 | 1971.28 | 02-FEB-12:30 |
WaterSystems:Electricity | 24.21 | 481.00 | 07-MAR-06:10 | 1971.28 | 02-FEB-12:30 |
Water Heater:WaterSystems:Electricity | 24.21 | 481.00 | 07-MAR-06:10 | 1971.28 | 02-FEB-12:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 38.86 | 0.00 | 01-JAN-00:10 | 72920.43 | 27-DEC-06:30 |
NaturalGas:HVAC | 38.86 | 0.00 | 01-JAN-00:10 | 72920.43 | 27-DEC-06:30 |
Heating:NaturalGas | 38.86 | 0.00 | 01-JAN-00:10 | 72920.43 | 27-DEC-06:30 |
General:Heating:NaturalGas | 38.86 | 0.00 | 01-JAN-00:10 | 72920.43 | 27-DEC-06:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 29-JUN-11:20 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 29-JUN-11:20 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 29-JUN-11:20 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 29-JUN-11:20 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 29-JUN-11:20 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 29-JUN-11:20 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 29-JUN-11:20 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 29-JUN-11:20 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 362.84 | 0.00 | 01-JAN-00:10 | 113456.16 | 31-DEC-07:10 |
EnergyTransfer:Building | 171.51 | 0.00 | 01-JAN-00:10 | 56913.83 | 31-DEC-07:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 51.99 | 0.00 | 01-JAN-00:10 | 16162.76 | 02-MAR-06:10 |
Heating:EnergyTransfer | 27.01 | 0.00 | 01-JAN-00:10 | 56913.83 | 31-DEC-07:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 8.68 | 0.00 | 01-JAN-00:10 | 16162.76 | 02-MAR-06:10 |
General:Heating:EnergyTransfer | 27.01 | 0.00 | 01-JAN-00:10 | 56913.83 | 31-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 8.68 | 0.00 | 01-JAN-00:10 | 16162.76 | 02-MAR-06:10 |
Cooling:EnergyTransfer | 144.50 | 0.00 | 01-JAN-00:10 | 39615.34 | 15-JUN-16:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 43.30 | 0.00 | 01-JAN-00:10 | 11786.80 | 03-JUL-05:10 |
General:Cooling:EnergyTransfer | 144.50 | 0.00 | 01-JAN-00:10 | 39615.34 | 15-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 43.30 | 0.00 | 01-JAN-00:10 | 11786.80 | 03-JUL-05:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 117.13 | 0.00 | 01-JAN-00:10 | 29481.18 | 15-JUN-15:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 15.93 | 0.00 | 01-JAN-00:10 | 24247.31 | 28-JAN-05:40 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 15.93 | 0.00 | 01-JAN-00:10 | 24247.31 | 28-JAN-05:40 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 101.19 | 0.00 | 01-JAN-00:10 | 29481.18 | 15-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 101.19 | 0.00 | 01-JAN-00:10 | 29481.18 | 15-JUN-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 2.39 | 0.00 | 01-JAN-00:10 | 34478.56 | 31-DEC-07:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 2.39 | 0.00 | 01-JAN-00:10 | 34478.56 | 31-DEC-07:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 2.39 | 0.00 | 01-JAN-00:10 | 34478.56 | 31-DEC-07:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 191.34 | 0.00 | 01-JAN-00:10 | 56542.33 | 31-DEC-07:10 |
HeatingCoils:EnergyTransfer | 26.54 | 0.00 | 01-JAN-00:10 | 56542.33 | 31-DEC-07:10 |
CoolingCoils:EnergyTransfer | 164.79 | 0.00 | 01-JAN-00:10 | 49214.47 | 15-JUN-15:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:58
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 8.685 | -43.300 | 0.000 | 0.000 | 9.617 | 10.287 | 29.165 | 11.796 | 0.000 | 2.425 | 0.000 | 0.000 | -5.933 | 0.000 | -10.396 | -12.346 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 15.934 | -101.191 | 0.000 | 0.000 | 21.981 | 37.332 | 0.000 | 37.359 | 0.000 | 5.391 | 27.147 | 0.000 | -12.352 | 0.000 | -31.602 | -0.000 |
ZONE3 BULK STORAGE | 2.393 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 45.103 | 37.740 | 107.344 | 736.733 | 0.000 | 16.632 | 0.010 | 0.000 | -150.887 | 0.000 | -389.364 | -405.694 |
Total Facility | 2.393 | 0.000 | 24.619 | -144.491 | 0.000 | 0.000 | 76.701 | 85.359 | 136.508 | 785.888 | 0.000 | 24.448 | 27.157 | 0.000 | -169.172 | 0.000 | -431.362 | -418.040 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 17-MAY-05:02 | 0.00 | 0.00 | 0.00 | -28485.44 | 0.00 | 0.00 | 84.86 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 28589.75 | 0.00 | -490.93 | 0.00 | -299.75 | 0.00 |
ZONE2 FINE STORAGE | 25-JUN-15:53 | 0.00 | 0.00 | 0.00 | -58434.71 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 3395.41 | 0.00 | 666.32 | 54073.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-SEP-15:43 | 0.00 | 0.00 | 0.00 | -65223.27 | 0.00 | 0.00 | 0.00 | 720.21 | 469.88 | 57728.38 | 0.00 | 3113.73 | 3191.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 02-MAR-06:12 | 0.00 | 0.00 | 28354.29 | 0.00 | 0.00 | 0.00 | 118.54 | 302.02 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -754.55 | 0.00 | -1238.47 | -27332.35 |
ZONE2 FINE STORAGE | 02-FEB-06:01 | 0.00 | 0.00 | 91850.92 | 0.00 | 0.00 | 0.00 | 364.29 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1269.66 | 0.00 | -3853.81 | -87391.71 |
ZONE3 BULK STORAGE | 31-DEC-06:53 | 34490.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 5438.66 | 0.00 | -16069.05 | 0.00 | -24358.55 | 0.00 |
Total Facility | 28-JAN-06:11 | 20341.33 | 0.00 | 120010.42 | 0.00 | 0.00 | 0.00 | 1430.45 | 1252.83 | 2600.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19245.22 | 0.00 | -30928.65 | -95461.69 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:58
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2604 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.2604 | 0.0812 | 1.0000 | Not calculated | 0.1023 | 0.0812 | ||
PSZ-FINE STORAGE | 3.2008 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.2008 | 0.1327 | 1.0000 | Not calculated | 0.4247 | 0.1327 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2604 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.2604 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0812 | ||
PSZ-FINE STORAGE | 3.2008 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.2008 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1327 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2604 | 1.2604 | 1.2604 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.2008 | 3.2008 | 3.2008 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2604 | 1.2604 | 1.2604 | 1.2604 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.2008 | 3.2008 | 3.2008 | 3.2008 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2604 | 1.2604 | 1.2604 | No | 0.1023 | 0.3157 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.2008 | 3.2008 | 3.2008 | No | 0.4247 | 0.5663 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2604 | 1.2604 | 1.2604 | 1.2604 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.2008 | 3.2008 | 3.2008 | 3.2008 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:58
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 35.17 |
Number of hours cooling loads not met | 20.67 |
Number of hours not met | 55.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 38.86 | 72920.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 42.64 | 15089.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 85.36 | 8510.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 61.70 | 5520.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 12.63 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 25.66 | 2932.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 24.21 | 1971.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 388.70 |
Natural Gas | 0.00 | 38.86 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 427.56 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 17.65 |
Space Heating | 0.00 |
Space Cooling | 8.82 |
Fans (All) | 7.92 |
Service Water Heating | 5.01 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 80.39 |
Subtotal | 80.39 |
Natural Gas [MJ/m2] | |
Space Heating | 8.04 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 8.04 |
Subtotal | 8.04 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 19.96 |
Space Heating | 9.09 |
Space Cooling | 9.97 |
Fans (All) | 8.96 |
Service Water Heating | 5.66 |
Receptacle Equipment | 31.93 |
Miscellaneous | 14.43 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2729. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:58
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 7345.00 | 1415.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7717.50 | 1042.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 5209.00 | 3334.50 | 216.50 | 0.00 | 0.00 |
Min | 5209.00 | 1042.50 | 0.00 | 0.00 | 0.00 |
Max | 7717.50 | 3334.50 | 216.50 | 0.00 | 0.00 |
Average | 6757.17 | 1930.67 | 72.17 | 0.00 | 0.00 |
Sum | 20271.50 | 5792.00 | 216.50 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 69430.00 | 13289.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 106567.00 | 75477.00 | 9149.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 106567.00 | 75477.00 | 9149.00 | 0.00 | 0.00 |
Average | 69674.67 | 29588.67 | 3049.67 | 0.00 | 0.00 |
Sum | 209024.00 | 88766.00 | 9149.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 7614.50 | 1145.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7421.33 | 1338.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 5820.83 | 2939.17 | 0.00 | 0.00 | 0.00 |
Min | 5820.83 | 1145.50 | 0.00 | 0.00 | 0.00 |
Max | 7614.50 | 2939.17 | 0.00 | 0.00 | 0.00 |
Average | 6952.22 | 1807.78 | 0.00 | 0.00 | 0.00 |
Sum | 20856.67 | 5423.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 32895.83 | 131.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 66554.50 | 16164.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 120028.50 | 71164.50 | 0.00 | 0.00 | 0.00 |
Min | 32895.83 | 131.17 | 0.00 | 0.00 | 0.00 |
Max | 120028.50 | 71164.50 | 0.00 | 0.00 | 0.00 |
Average | 73159.61 | 29153.39 | 0.00 | 0.00 | 0.00 |
Sum | 219478.83 | 87460.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:58
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:58
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 91431827.07 | 863.47 | 26-JAN-14:20 | 6.30 | -1.5 | 0.510187E+09 | 755.70 | 12-JAN-16:10 | 6.30 | -1.5 |
February | 0.100856E+09 | 888.61 | 23-FEB-14:50 | 21.28 | 7.21 | 0.482640E+09 | 768.96 | 21-FEB-16:00 | 21.28 | 7.21 |
March | 0.408775E+09 | 2766.37 | 16-MAR-15:50 | 22.30 | 8.43 | 0.606620E+09 | 768.96 | 22-MAR-15:09 | 23.90 | 8.87 |
April | 0.274707E+10 | 14652.97 | 29-APR-05:03 | 17.70 | 12.15 | 0.624818E+09 | 769.00 | 29-APR-08:50 | 22.02 | 14.06 |
May | 0.566636E+10 | 28486.51 | 17-MAY-05:02 | 14.08 | 5.19 | 0.659745E+09 | 769.05 | 30-MAY-15:50 | 33.98 | 17.51 |
June | 0.766441E+10 | 28159.45 | 13-JUN-05:01 | 15.18 | 4.59 | 0.660321E+09 | 769.08 | 26-JUN-15:30 | 33.30 | 17.36 |
July | 0.760347E+10 | 21631.01 | 11-JUL-05:01 | 21.70 | 15.06 | 0.635101E+09 | 769.08 | 14-JUL-15:09 | 33.90 | 18.63 |
August | 0.778785E+10 | 24317.85 | 23-AUG-05:01 | 20.00 | 11.78 | 0.685776E+09 | 769.08 | 21-AUG-15:00 | 20.00 | 11.78 |
September | 0.655616E+10 | 25806.81 | 12-SEP-05:01 | 15.13 | 10.46 | 0.634843E+09 | 769.08 | 05-SEP-14:50 | 15.13 | 10.46 |
October | 0.374694E+10 | 22083.20 | 06-OCT-05:02 | 13.22 | 11.60 | 0.632300E+09 | 769.04 | 05-OCT-15:00 | 13.22 | 11.60 |
November | 0.817198E+09 | 4160.08 | 03-NOV-16:00 | 23.90 | 13.45 | 0.555739E+09 | 768.99 | 03-NOV-13:09 | 23.90 | 13.45 |
December | 0.110156E+09 | 731.50 | 19-DEC-15:20 | 9.40 | 0.61 | 0.508433E+09 | 722.08 | 16-DEC-16:10 | 9.40 | 0.61 |
Annual Sum or Average | 0.433007E+11 | 0.719652E+10 | ||||||||
Minimum of Months | 91431827.07 | 731.50 | 6.30 | -1.5 | 0.482640E+09 | 722.08 | 6.30 | -1.5 | ||
Maximum of Months | 0.778785E+10 | 28486.51 | 23.90 | 15.06 | 0.685776E+09 | 769.08 | 33.98 | 18.63 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141349E+10 | 4794.29 | 06-JAN-08:35 | 0.77 | -3.4 | 0.828205E+09 | 1425.76 | 12-JAN-15:39 | 18.90 | 10.12 |
February | 0.109485E+10 | 4921.38 | 09-FEB-09:20 | 2.57 | -1.4 | 0.839216E+09 | 1635.27 | 23-FEB-14:50 | 21.28 | 7.21 |
March | 0.116447E+10 | 4929.20 | 24-MAR-07:10 | 2.77 | -0.9 | 0.118488E+10 | 1924.86 | 16-MAR-15:09 | 2.77 | -0.9 |
April | 0.240409E+10 | 47720.21 | 30-APR-14:33 | 29.80 | 12.58 | 0.161326E+10 | 2246.82 | 29-APR-10:39 | 29.80 | 12.58 |
May | 0.112264E+11 | 54583.27 | 21-MAY-15:53 | 34.40 | 18.34 | 0.189105E+10 | 2246.94 | 24-MAY-13:00 | 30.00 | 18.55 |
June | 0.219713E+11 | 58434.90 | 25-JUN-15:53 | 31.10 | 16.73 | 0.192758E+10 | 2246.96 | 15-JUN-15:30 | 31.10 | 16.73 |
July | 0.219084E+11 | 57827.02 | 30-JUL-16:53 | 30.60 | 20.10 | 0.185450E+10 | 2247.00 | 26-JUL-14:09 | 30.60 | 20.10 |
August | 0.196808E+11 | 58101.16 | 06-AUG-11:02 | 32.57 | 18.36 | 0.200002E+10 | 2246.95 | 03-AUG-10:39 | 32.57 | 18.36 |
September | 0.137020E+11 | 57935.45 | 17-SEP-13:43 | 32.12 | 16.04 | 0.184148E+10 | 2246.95 | 01-SEP-12:09 | 32.12 | 16.04 |
October | 0.379095E+10 | 53992.77 | 01-OCT-15:13 | 32.43 | 15.77 | 0.168144E+10 | 2246.95 | 04-OCT-13:09 | 29.08 | 19.06 |
November | 0.136797E+10 | 4752.84 | 17-NOV-08:50 | 4.72 | 0.97 | 0.111388E+10 | 2135.60 | 03-NOV-15:20 | 4.72 | 0.97 |
December | 0.147014E+10 | 4759.06 | 19-DEC-09:40 | 1.87 | -3.7 | 0.809230E+09 | 1293.20 | 16-DEC-15:30 | 1.87 | -3.7 |
Annual Sum or Average | 0.101195E+12 | 0.175847E+11 | ||||||||
Minimum of Months | 0.109485E+10 | 4752.84 | 0.77 | -3.7 | 0.809230E+09 | 1293.20 | 1.87 | -3.7 | ||
Maximum of Months | 0.219713E+11 | 58434.90 | 34.40 | 20.10 | 0.200002E+10 | 2247.00 | 32.57 | 20.10 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 | 3.92 | 0.146608E+10 | 2891.15 | 03-JAN-15:09 | 20.50 | 8.33 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 | 1.84 | 0.155366E+10 | 3290.59 | 23-FEB-14:50 | 21.28 | 7.21 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 | 2.40 | 0.252594E+10 | 4147.67 | 22-MAR-13:50 | 24.50 | 9.16 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 | 2.41 | 0.384318E+10 | 7109.99 | 21-APR-15:09 | 32.02 | 15.38 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 | 8.41 | 0.529749E+10 | 8511.58 | 19-MAY-14:20 | 34.80 | 17.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 | 11.56 | 0.627321E+10 | 9097.65 | 01-JUN-14:00 | 36.70 | 14.74 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 | 17.07 | 0.582018E+10 | 9097.65 | 01-JUL-13:30 | 36.65 | 19.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 | 18.12 | 0.604000E+10 | 9097.65 | 07-AUG-15:39 | 36.47 | 18.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 | 17.18 | 0.530324E+10 | 8185.53 | 19-SEP-14:20 | 33.70 | 16.73 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 | 8.67 | 0.410312E+10 | 7568.47 | 03-OCT-14:20 | 32.43 | 19.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 | 5.64 | 0.235744E+10 | 4683.31 | 03-NOV-15:09 | 23.40 | 13.55 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 | 5.46 | 0.131382E+10 | 2270.39 | 01-DEC-14:09 | 14.22 | 6.46 |
Annual Sum or Average | 0.00 | 0.458974E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 6.42 | 1.84 | 0.131382E+10 | 2270.39 | 14.22 | 6.46 | ||
Maximum of Months | 0.00 | 0.00 | 27.63 | 18.12 | 0.627321E+10 | 9097.65 | 36.70 | 19.82 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241695E+10 | 28319.94 | 09-JAN-06:12 | 3.17 |
February | 0.177417E+10 | 28225.08 | 02-FEB-06:01 | -3.5 |
March | 0.110270E+10 | 28354.25 | 02-MAR-06:12 | -3.2 |
April | 98775207.25 | 27479.50 | 01-APR-05:02 | 11.10 |
May | 14248139.64 | 815.64 | 02-MAY-06:20 | 10.33 |
June | 778481.46 | 402.33 | 20-JUN-06:01 | 20.97 |
July | 10463.78 | 52.32 | 10-JUL-06:03 | 22.67 |
August | 648182.80 | 423.98 | 17-AUG-06:15 | 17.40 |
September | 3381917.43 | 765.10 | 27-SEP-06:10 | 11.65 |
October | 37149495.75 | 863.45 | 11-OCT-06:15 | 7.23 |
November | 0.719885E+09 | 28191.97 | 28-NOV-06:01 | 1.02 |
December | 0.251627E+10 | 28237.52 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.868497E+10 | |||
Minimum of Months | 10463.78 | 52.32 | -3.5 | |
Maximum of Months | 0.251627E+10 | 28354.25 | 22.67 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.463921E+10 | 91829.02 | 28-JAN-06:11 | -3.3 |
February | 0.259348E+10 | 91850.90 | 02-FEB-06:01 | -3.5 |
March | 0.924962E+09 | 52612.28 | 02-MAR-05:43 | -3.9 |
April | 0.247372E+09 | 3236.01 | 01-APR-17:00 | 28.90 |
May | 91551611.60 | 1320.58 | 10-MAY-06:12 | 17.77 |
June | 20804034.44 | 1625.93 | 17-JUN-06:05 | 23.07 |
July | 4831960.02 | 1566.57 | 17-JUL-06:02 | 20.18 |
August | 37459017.39 | 1634.69 | 01-AUG-06:03 | 22.48 |
September | 74254615.68 | 1285.16 | 08-SEP-07:00 | 17.80 |
October | 0.113592E+09 | 1489.80 | 13-OCT-07:00 | 14.40 |
November | 0.672686E+09 | 77204.47 | 28-NOV-06:01 | 1.02 |
December | 0.651385E+10 | 83713.30 | 31-DEC-07:03 | -2.7 |
Annual Sum or Average | 0.159341E+11 | |||
Minimum of Months | 4831960.02 | 1285.16 | -3.9 | |
Maximum of Months | 0.651385E+10 | 91850.90 | 28.90 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.254085E+09 | 21051.03 | 28-JAN-06:00 | -3.3 |
February | 0.108390E+09 | 11117.84 | 03-FEB-05:07 | -3.8 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.203062E+10 | 34490.89 | 31-DEC-06:53 | -2.8 |
Annual Sum or Average | 0.239309E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.8 | |
Maximum of Months | 0.203062E+10 | 34490.89 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.893409E+09 | 1001.41 | 17-JAN-16:00 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.803622E+09 | 979.56 | 23-FEB-16:00 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.902093E+09 | 978.88 | 10-MAR-16:00 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.826473E+09 | 956.79 | 20-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.846105E+09 | 916.80 | 03-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.847015E+09 | 883.13 | 26-JUN-10:30 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.830244E+09 | 953.46 | 07-JUL-07:30 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.889750E+09 | 952.63 | 17-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.838266E+09 | 944.97 | 29-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.856291E+09 | 991.63 | 13-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.855363E+09 | 1011.11 | 17-NOV-16:00 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.898622E+09 | 1011.11 | 01-DEC-16:00 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.102873E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.803622E+09 | 883.13 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.902093E+09 | 1011.11 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.341322E+10 | 3651.75 | 02-JAN-15:00 | 0.00 | 0.00 |
February | 0.301757E+10 | 3573.21 | 04-FEB-15:00 | 0.00 | 0.00 |
March | 0.323457E+10 | 3504.73 | 17-MAR-08:09 | 0.00 | 0.00 |
April | 0.291293E+10 | 3321.95 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.291545E+10 | 3173.05 | 04-MAY-08:09 | 0.00 | 0.00 |
June | 0.292130E+10 | 3207.87 | 30-JUN-08:09 | 0.00 | 0.00 |
July | 0.285187E+10 | 3314.18 | 07-JUL-08:09 | 0.00 | 0.00 |
August | 0.305708E+10 | 3355.44 | 24-AUG-08:09 | 0.00 | 0.00 |
September | 0.303799E+10 | 3473.85 | 29-SEP-08:09 | 0.00 | 0.00 |
October | 0.317582E+10 | 3488.00 | 31-OCT-08:09 | 0.00 | 0.00 |
November | 0.331588E+10 | 3673.34 | 20-NOV-15:00 | 0.00 | 0.00 |
December | 0.347853E+10 | 3686.68 | 07-DEC-15:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.373322E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.285187E+10 | 3173.05 | 0.00 | 0.00 | |
Maximum of Months | 0.347853E+10 | 3686.68 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.352936E+10 | 3825.52 | 02-JAN-15:00 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.304557E+10 | 3667.03 | 04-FEB-15:00 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.327892E+10 | 3335.33 | 10-MAR-16:00 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.290161E+10 | 2972.31 | 20-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.292258E+10 | 2784.20 | 03-MAY-06:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.288051E+10 | 2514.92 | 26-JUN-07:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.287424E+10 | 3093.30 | 07-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.306448E+10 | 3180.13 | 24-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.307423E+10 | 3253.89 | 29-SEP-07:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.322755E+10 | 3445.05 | 13-OCT-07:10 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.339329E+10 | 3863.89 | 20-NOV-15:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.354765E+10 | 3894.15 | 07-DEC-15:00 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.377400E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.287424E+10 | 2514.92 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.354765E+10 | 3894.15 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.893409E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166962E+10 |
February | 0.127628E+10 | 0.803622E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3132187.64 | 0.139152E+10 |
March | 0.149825E+10 | 0.902093E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2916903.53 | 0.139942E+10 |
April | 0.138726E+10 | 0.826473E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152768E+09 | 0.818505E+09 |
May | 0.144276E+10 | 0.846105E+09 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358709E+09 | 0.456078E+09 |
June | 0.144276E+10 | 0.847015E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669280E+09 | 0.179131E+09 |
July | 0.138726E+10 | 0.830244E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502921E+09 | 0.145008E+09 |
August | 0.149825E+10 | 0.889750E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430475E+09 | 0.222446E+09 |
September | 0.138726E+10 | 0.838266E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246132E+09 | 0.295699E+09 |
October | 0.138726E+10 | 0.856291E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58719903.32 | 0.826214E+09 |
November | 0.133177E+10 | 0.855363E+09 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136619E+10 |
December | 0.138726E+10 | 0.898622E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162650E+10 |
Annual Sum or Average | 0.168137E+11 | 0.102873E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242505E+10 | 0.103963E+11 |
Minimum of Months | 0.127628E+10 | 0.803622E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145008E+09 |
Maximum of Months | 0.149825E+10 | 0.902093E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669280E+09 | 0.166962E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.341322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1897252.59 | 0.426762E+10 |
February | 0.300332E+10 | 0.301757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36023720.96 | 0.362681E+10 |
March | 0.352563E+10 | 0.323457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28131124.82 | 0.387861E+10 |
April | 0.326447E+10 | 0.291293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300266E+09 | 0.310944E+10 |
May | 0.339505E+10 | 0.291545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.818195E+09 | 0.213138E+10 |
June | 0.339505E+10 | 0.292130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169224E+10 | 0.835964E+09 |
July | 0.326447E+10 | 0.285187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122443E+10 | 0.685691E+09 |
August | 0.352563E+10 | 0.305708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961185E+09 | 0.953209E+09 |
September | 0.326447E+10 | 0.303799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259660E+09 | 0.112014E+10 |
October | 0.326447E+10 | 0.317582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68995491.51 | 0.315787E+10 |
November | 0.313390E+10 | 0.331588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209064.43 | 0.399643E+10 |
December | 0.326447E+10 | 0.347853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11675.12 | 0.383864E+10 |
Annual Sum or Average | 0.395654E+11 | 0.373322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539124E+10 | 0.316018E+11 |
Minimum of Months | 0.300332E+10 | 0.285187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11675.12 | 0.685691E+09 |
Maximum of Months | 0.352563E+10 | 0.347853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169224E+10 | 0.426762E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.352936E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56361566.73 | 0.138639E+11 |
February | 0.690763E+10 | 0.304557E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.723846E+09 | 0.123366E+11 |
March | 0.810895E+10 | 0.327892E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469723E+09 | 0.161205E+11 |
April | 0.750829E+10 | 0.290161E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.970123E+09 | 0.152667E+11 |
May | 0.780862E+10 | 0.292258E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67942420.56 | 0.143924E+11 |
June | 0.780862E+10 | 0.288051E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172392E+09 | 0.735596E+10 |
July | 0.750829E+10 | 0.287424E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78407801.06 | 0.649416E+10 |
August | 0.810895E+10 | 0.306448E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35820021.40 | 0.758720E+10 |
September | 0.750829E+10 | 0.307423E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1697901.43 | 0.756396E+10 |
October | 0.750829E+10 | 0.322755E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19168375.48 | 0.157726E+11 |
November | 0.720796E+10 | 0.339329E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15433616.50 | 0.160023E+11 |
December | 0.750829E+10 | 0.354765E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100103E+09 | 0.113627E+11 |
Annual Sum or Average | 0.910005E+11 | 0.377400E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271102E+10 | 0.144119E+12 |
Minimum of Months | 0.690763E+10 | 0.287424E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1697901.43 | 0.649416E+10 |
Maximum of Months | 0.810895E+10 | 0.354765E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.970123E+09 | 0.161205E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1001.41 | 17-JAN-16:00 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 6436.60 | 27-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 979.56 | 23-FEB-16:00 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 129.95 | 19-FEB-14:00 | 6215.01 | 01-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 978.88 | 10-MAR-16:00 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 256.23 | 21-MAR-16:10 | 5584.56 | 27-MAR-07:00 |
April | 1680.92 | 01-APR-07:10 | 956.79 | 20-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2448.66 | 21-APR-16:10 | 3883.65 | 11-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 916.80 | 03-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2969.39 | 19-MAY-17:00 | 3263.31 | 02-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 883.13 | 26-JUN-10:30 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3887.70 | 05-JUN-17:00 | 1510.46 | 29-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 953.46 | 07-JUL-07:30 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3664.75 | 03-JUL-17:00 | 1391.78 | 05-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 952.63 | 17-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3156.51 | 07-AUG-16:10 | 1643.56 | 31-AUG-06:10 |
September | 1680.92 | 01-SEP-07:10 | 944.97 | 29-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1971.75 | 18-SEP-17:00 | 2876.07 | 25-SEP-06:10 |
October | 1680.92 | 02-OCT-07:10 | 991.63 | 13-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1684.38 | 05-OCT-16:10 | 3614.50 | 25-OCT-06:05 |
November | 1680.92 | 01-NOV-07:10 | 1011.11 | 17-NOV-16:00 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5228.64 | 28-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1011.11 | 01-DEC-16:00 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6000.27 | 27-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 883.13 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1391.78 | |||||
Maximum of Months | 1680.92 | 1011.11 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 3887.70 | 6436.60 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3651.75 | 02-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.06 | 03-JAN-17:10 | 8528.10 | 25-JAN-23:17 |
February | 3955.50 | 01-FEB-08:09 | 3573.21 | 04-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 855.48 | 20-FEB-16:00 | 12327.31 | 08-FEB-18:00 |
March | 3955.50 | 01-MAR-08:09 | 3504.73 | 17-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.70 | 03-MAR-16:10 | 10127.20 | 27-MAR-07:00 |
April | 3955.50 | 01-APR-07:10 | 3321.95 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5701.38 | 21-APR-15:10 | 12536.82 | 22-APR-07:00 |
May | 3955.50 | 01-MAY-07:10 | 3173.05 | 04-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4922.97 | 19-MAY-17:00 | 5947.35 | 01-MAY-08:00 |
June | 3955.50 | 01-JUN-07:10 | 3207.87 | 30-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7023.20 | 05-JUN-17:00 | 5065.92 | 28-JUN-02:00 |
July | 3955.50 | 01-JUL-07:10 | 3314.18 | 07-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5589.03 | 03-JUL-17:00 | 3431.66 | 18-JUL-21:00 |
August | 3955.50 | 01-AUG-07:10 | 3355.44 | 24-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4864.10 | 26-AUG-15:10 | 4151.20 | 14-AUG-01:00 |
September | 3955.50 | 01-SEP-07:10 | 3473.85 | 29-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1608.02 | 18-SEP-17:00 | 3541.45 | 23-SEP-17:00 |
October | 3955.50 | 02-OCT-07:10 | 3488.00 | 31-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.57 | 01-OCT-15:00 | 6249.10 | 23-OCT-18:00 |
November | 3955.50 | 01-NOV-07:10 | 3673.34 | 20-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.62 | 23-NOV-16:00 | 6782.80 | 15-NOV-09:00 |
December | 3955.50 | 01-DEC-08:09 | 3686.68 | 07-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.46 | 10-DEC-15:00 | 9800.82 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3173.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.46 | 3431.66 | ||||
Maximum of Months | 3955.50 | 3686.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7023.20 | 12536.82 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 3825.52 | 02-JAN-15:00 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6387.35 | 03-JAN-17:00 | 21691.88 | 05-JAN-09:00 |
February | 9097.65 | 01-FEB-08:09 | 3667.03 | 04-FEB-15:00 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9060.59 | 06-FEB-22:00 | 34441.54 | 09-FEB-01:00 |
March | 9097.65 | 01-MAR-08:09 | 3335.33 | 10-MAR-16:00 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14344.34 | 03-MAR-16:00 | 35999.68 | 27-MAR-07:10 |
April | 9097.65 | 01-APR-07:10 | 2972.31 | 20-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14856.92 | 01-APR-15:00 | 49783.19 | 22-APR-07:10 |
May | 9097.65 | 01-MAY-07:10 | 2784.20 | 03-MAY-06:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1946.74 | 19-MAY-14:00 | 30504.31 | 01-MAY-10:00 |
June | 9097.65 | 01-JUN-07:10 | 2514.92 | 26-JUN-07:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2126.75 | 02-JUN-16:00 | 26135.78 | 28-JUN-02:00 |
July | 9097.65 | 01-JUL-07:10 | 3093.30 | 07-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2212.27 | 02-JUL-21:53 | 18518.75 | 18-JUL-21:00 |
August | 9097.65 | 01-AUG-07:10 | 3180.13 | 24-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1454.12 | 07-AUG-16:00 | 20930.36 | 14-AUG-01:00 |
September | 9097.65 | 01-SEP-07:10 | 3253.89 | 29-SEP-07:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 315.92 | 10-SEP-14:43 | 14870.06 | 23-SEP-17:00 |
October | 9097.65 | 02-OCT-07:10 | 3445.05 | 13-OCT-07:10 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1640.34 | 18-OCT-16:00 | 32779.72 | 06-OCT-09:00 |
November | 9097.65 | 01-NOV-07:10 | 3863.89 | 20-NOV-15:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1613.60 | 23-NOV-16:00 | 26542.49 | 15-NOV-09:00 |
December | 9097.65 | 01-DEC-08:09 | 3894.15 | 07-DEC-15:00 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3611.81 | 10-DEC-15:00 | 25863.28 | 18-DEC-08:70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 2514.92 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 315.92 | 14870.06 | |||||
Maximum of Months | 9097.65 | 3894.15 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 14856.92 | 49783.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 863.47 | 26-JAN-14:20 | 1680.92 | 821.00 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 546.36 |
February | 888.61 | 23-FEB-14:50 | 1680.92 | 650.60 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.59 |
March | 2766.37 | 16-MAR-15:50 | 1680.92 | 616.78 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.35 |
April | 14652.97 | 29-APR-05:03 | 739.61 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.76 |
May | 28486.51 | 17-MAY-05:02 | 1109.41 | 305.97 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.75 |
June | 28159.45 | 13-JUN-05:01 | 1294.31 | 356.97 | 3853.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.76 |
July | 21631.01 | 11-JUL-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.78 |
August | 24317.85 | 23-AUG-05:01 | 1664.11 | 458.96 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.12 |
September | 25806.81 | 12-SEP-05:01 | 1294.31 | 356.97 | 3853.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.41 |
October | 22083.20 | 06-OCT-05:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 920.47 |
November | 4160.08 | 03-NOV-16:00 | 1680.92 | 659.26 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
December | 731.50 | 19-DEC-15:20 | 1680.92 | 660.41 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 731.50 | 739.61 | 203.98 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 | |
Maximum of Months | 28486.51 | 1849.01 | 821.00 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 920.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4794.29 | 06-JAN-08:35 | 7911.00 | 6238.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2743.64 |
February | 4921.38 | 09-FEB-09:20 | 3955.50 | 3222.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 921.79 |
March | 4929.20 | 24-MAR-07:10 | 3955.50 | 2981.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 47720.21 | 30-APR-14:33 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.46 | 0.00 |
May | 54583.27 | 21-MAY-15:53 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2646.74 | 0.00 |
June | 58434.90 | 25-JUN-15:53 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 666.32 | 0.00 |
July | 57827.02 | 30-JUL-16:53 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1367.57 | 0.00 |
August | 58101.16 | 06-AUG-11:02 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 935.39 | 0.00 |
September | 57935.45 | 17-SEP-13:43 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 907.79 | 0.00 |
October | 53992.77 | 01-OCT-15:13 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1719.52 | 0.00 |
November | 4752.84 | 17-NOV-08:50 | 3955.50 | 2890.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.63 |
December | 4759.06 | 19-DEC-09:40 | 3955.50 | 3097.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4752.84 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 58434.90 | 7911.00 | 6238.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2646.74 | 2743.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6227.79 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10755.03 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7510.10 |
April | 0.00 | 01-APR-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3559.01 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3660.14 |
June | 0.00 | 01-JUN-00:03 | 0.00 | 1494.14 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6414.91 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.72 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1607.39 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6454.37 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2541.26 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8908.70 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2797.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.72 | |
Maximum of Months | 0.00 | 0.00 | 1494.14 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10755.03 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.298538E+11 | 21894.72 | 02-JAN-15:00 | 0.112728E+11 | 71708.98 | 28-JAN-06:19 |
February | 0.264788E+11 | 21699.08 | 02-FEB-15:00 | 0.647198E+10 | 54455.67 | 02-FEB-06:10 |
March | 0.292271E+11 | 21346.53 | 17-MAR-08:09 | 0.247394E+10 | 38876.16 | 02-MAR-06:10 |
April | 0.277362E+11 | 27722.89 | 21-APR-15:09 | 75232856.32 | 6698.76 | 01-APR-05:10 |
May | 0.332377E+11 | 31939.42 | 19-MAY-15:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.394062E+11 | 37338.71 | 15-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.398319E+11 | 34978.27 | 26-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.395018E+11 | 34417.91 | 07-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.349852E+11 | 32493.44 | 05-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.299228E+11 | 31162.41 | 05-OCT-15:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.283712E+11 | 27235.78 | 27-NOV-16:00 | 0.189782E+10 | 37865.24 | 28-NOV-06:10 |
December | 0.301485E+11 | 27227.86 | 08-DEC-16:00 | 0.166675E+11 | 72920.43 | 27-DEC-06:30 |
Annual Sum or Average | 0.388701E+12 | 0.388593E+11 | ||||
Minimum of Months | 0.264788E+11 | 21346.53 | 0.00 | 0.00 | ||
Maximum of Months | 0.398319E+11 | 37338.71 | 0.166675E+11 | 72920.43 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.783599E+10 | 0.639293E+10 | 0.112984E+11 | 0.00 | 0.216960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215695E+10 | 0.00 |
February | 0.686676E+10 | 0.536714E+10 | 0.103734E+11 | 0.00 | 0.191182E+10 | 0.00 | 0.00 | 950533.11 | 0.00 | 0.00 | 0.00 | 0.195876E+10 | 0.00 |
March | 0.741558E+10 | 0.536275E+10 | 0.121089E+11 | 0.00 | 0.212244E+10 | 0.00 | 0.00 | 38397043.49 | 0.00 | 0.00 | 0.00 | 0.217905E+10 | 0.00 |
April | 0.664102E+10 | 0.460676E+10 | 0.112578E+11 | 0.00 | 0.207195E+10 | 0.00 | 0.00 | 0.113795E+10 | 0.00 | 0.00 | 0.00 | 0.202078E+10 | 0.00 |
May | 0.668413E+10 | 0.425969E+10 | 0.117000E+11 | 0.00 | 0.369709E+10 | 0.00 | 0.00 | 0.486611E+10 | 0.00 | 0.00 | 0.00 | 0.203072E+10 | 0.00 |
June | 0.664883E+10 | 0.387400E+10 | 0.116594E+11 | 0.00 | 0.574573E+10 | 0.00 | 0.00 | 0.954868E+10 | 0.00 | 0.00 | 0.00 | 0.192962E+10 | 0.00 |
July | 0.655635E+10 | 0.411357E+10 | 0.112984E+11 | 0.00 | 0.558131E+10 | 0.00 | 0.00 | 0.103593E+11 | 0.00 | 0.00 | 0.00 | 0.192302E+10 | 0.00 |
August | 0.701131E+10 | 0.453794E+10 | 0.121016E+11 | 0.00 | 0.507883E+10 | 0.00 | 0.00 | 0.880614E+10 | 0.00 | 0.00 | 0.00 | 0.196604E+10 | 0.00 |
September | 0.695048E+10 | 0.493138E+10 | 0.112504E+11 | 0.00 | 0.360787E+10 | 0.00 | 0.00 | 0.633495E+10 | 0.00 | 0.00 | 0.00 | 0.191013E+10 | 0.00 |
October | 0.725965E+10 | 0.570393E+10 | 0.113057E+11 | 0.00 | 0.214483E+10 | 0.00 | 0.00 | 0.150018E+10 | 0.00 | 0.00 | 0.00 | 0.200844E+10 | 0.00 |
November | 0.756454E+10 | 0.602781E+10 | 0.108562E+11 | 0.00 | 0.187813E+10 | 0.00 | 0.00 | 43365382.60 | 0.00 | 0.00 | 0.00 | 0.200116E+10 | 0.00 |
December | 0.792480E+10 | 0.651881E+10 | 0.112984E+11 | 0.00 | 0.227873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212781E+10 | 0.00 |
Annual Sum or Average | 0.853594E+11 | 0.616967E+11 | 0.136508E+12 | 0.00 | 0.382883E+11 | 0.00 | 0.00 | 0.426361E+11 | 0.00 | 0.00 | 0.00 | 0.242125E+11 | 0.00 |
Minimum of Months | 0.655635E+10 | 0.387400E+10 | 0.103734E+11 | 0.00 | 0.187813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191013E+10 | 0.00 |
Maximum of Months | 0.792480E+10 | 0.651881E+10 | 0.121089E+11 | 0.00 | 0.574573E+10 | 0.00 | 0.00 | 0.103593E+11 | 0.00 | 0.00 | 0.00 | 0.217905E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.112728E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.647198E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.247394E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 75232856.32 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.189782E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.166675E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.388593E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.166675E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 8160.14 | 02-JAN-15:00 | 5520.82 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 2848.55 | 27-JAN-07:19 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 8009.78 | 04-FEB-15:00 | 5520.82 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 2815.91 | 02-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 7708.39 | 17-MAR-08:09 | 5520.82 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 2528.12 | 02-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 7173.30 | 20-APR-08:09 | 5520.82 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 4233.50 | 21-APR-12:50 | 0.00 | 0.00 | 01-APR-00:10 |
May | 6355.98 | 04-MAY-07:10 | 5520.82 | 01-MAY-05:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 4390.51 | 19-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 6380.99 | 26-JUN-07:10 | 4975.14 | 01-JUN-19:10 | 10035.17 | 01-JUN-07:10 | 0.00 | 5237.32 | 15-JUN-15:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 7350.68 | 07-JUL-08:09 | 5520.82 | 06-JUL-05:10 | 10035.17 | 01-JUL-07:10 | 0.00 | 4652.23 | 26-JUL-14:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 7484.37 | 24-AUG-08:09 | 5520.82 | 01-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 4841.91 | 07-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 7638.48 | 29-SEP-08:09 | 5520.82 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 4386.23 | 05-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 7691.95 | 13-OCT-07:10 | 5520.82 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 4301.04 | 05-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 8216.65 | 24-NOV-15:00 | 5520.82 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 2442.63 | 28-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 8510.94 | 02-DEC-15:00 | 5520.82 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 2887.56 | 27-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 6355.98 | 4975.14 | 10035.17 | 0.00 | 2442.63 | 0.00 | 0.00 | |||||
Maximum of Months | 8510.94 | 5520.82 | 10035.17 | 0.00 | 5237.32 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 1968.54 | 26-JAN-12:00 | 0.00 |
February | 108.44 | 21-FEB-16:30 | 0.00 | 0.00 | 0.00 | 1971.28 | 02-FEB-12:30 | 0.00 |
March | 805.68 | 21-MAR-15:00 | 0.00 | 0.00 | 0.00 | 1875.26 | 02-MAR-12:00 | 0.00 |
April | 7464.32 | 21-APR-15:09 | 0.00 | 0.00 | 0.00 | 1790.48 | 01-APR-11:09 | 0.00 |
May | 10511.70 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 | 1764.82 | 01-MAY-11:09 | 0.00 |
June | 15089.22 | 15-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1740.54 | 01-JUN-11:50 | 0.00 |
July | 13168.84 | 26-JUL-14:20 | 0.00 | 0.00 | 0.00 | 1723.54 | 01-JUL-11:50 | 0.00 |
August | 13655.77 | 07-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1723.67 | 31-AUG-11:30 | 0.00 |
September | 10336.84 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1740.80 | 30-SEP-11:09 | 0.00 |
October | 9261.17 | 03-OCT-13:00 | 0.00 | 0.00 | 0.00 | 1765.45 | 31-OCT-11:09 | 0.00 |
November | 1121.90 | 03-NOV-15:00 | 0.00 | 0.00 | 0.00 | 1790.76 | 29-NOV-12:20 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 1850.88 | 26-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1723.54 | 0.00 | ||
Maximum of Months | 15089.22 | 0.00 | 0.00 | 0.00 | 1971.28 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 21894.72 | 02-JAN-15:00 | 8160.14 | 10035.17 | 0.00 | 0.00 | 1928.21 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21699.08 | 02-FEB-15:00 | 7959.33 | 10035.17 | 0.00 | 0.00 | 1928.21 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21346.53 | 17-MAR-08:09 | 7708.39 | 10035.17 | 0.00 | 0.00 | 1940.01 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27722.89 | 21-APR-15:09 | 4394.28 | 10035.17 | 0.00 | 0.00 | 4233.50 | 0.00 | 0.00 | 7464.32 | 0.00 |
May | 31939.42 | 19-MAY-15:50 | 5542.30 | 10035.17 | 0.00 | 0.00 | 4340.04 | 0.00 | 0.00 | 10432.03 | 0.00 |
June | 37338.71 | 15-JUN-15:00 | 5628.05 | 10035.17 | 0.00 | 0.00 | 5214.82 | 0.00 | 0.00 | 14875.62 | 0.00 |
July | 34978.27 | 26-JUL-13:00 | 5472.02 | 10035.17 | 0.00 | 0.00 | 4645.39 | 0.00 | 0.00 | 13158.11 | 0.00 |
August | 34417.91 | 07-AUG-15:00 | 5404.06 | 10035.17 | 0.00 | 0.00 | 4841.91 | 0.00 | 0.00 | 13655.77 | 0.00 |
September | 32493.44 | 05-SEP-14:00 | 6719.61 | 10035.17 | 0.00 | 0.00 | 4354.38 | 0.00 | 0.00 | 9848.43 | 0.00 |
October | 31162.41 | 05-OCT-15:50 | 6427.38 | 10035.17 | 0.00 | 0.00 | 4296.07 | 0.00 | 0.00 | 8815.47 | 0.00 |
November | 27235.78 | 27-NOV-16:00 | 8142.10 | 10035.17 | 5520.82 | 0.00 | 1937.89 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 27227.86 | 08-DEC-16:00 | 8142.10 | 10035.17 | 5520.82 | 0.00 | 1928.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 21346.53 | 4394.28 | 10035.17 | 0.00 | 0.00 | 1928.21 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37338.71 | 8160.14 | 10035.17 | 5520.82 | 0.00 | 5214.82 | 0.00 | 0.00 | 14875.62 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 71708.98 | 28-JAN-06:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 54455.67 | 02-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 38876.16 | 02-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 6698.76 | 01-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 37865.24 | 28-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 72920.43 | 27-DEC-06:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 72920.43 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.00 | 19.80 | 8.00 | 19.80 | 0.00 | 19.80 | 0.00 | 19.80 |
February | 6.67 | 19.93 | 6.67 | 19.93 | 0.00 | 19.93 | 0.00 | 19.93 |
March | 4.33 | 20.17 | 4.33 | 20.17 | 0.00 | 20.17 | 0.00 | 20.17 |
April | 0.17 | 20.42 | 0.17 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.54 | 1.50 | 24.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 25.19 | 4.33 | 24.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 25.00 | 5.67 | 24.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 24.99 | 5.33 | 24.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 25.33 | 3.17 | 24.99 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.57 | 0.67 | 24.57 |
November | 2.50 | 20.18 | 2.50 | 20.18 | 0.00 | 20.18 | 0.00 | 20.18 |
December | 8.50 | 19.68 | 8.17 | 19.77 | 0.00 | 19.77 | 0.00 | 19.77 |
Annual Sum or Average | 30.17 | 19.88 | 29.83 | 19.91 | 22.33 | 21.30 | 20.67 | 21.97 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.77 | 0.00 | 19.77 |
Maximum of Months | 8.50 | 20.42 | 8.17 | 20.42 | 6.00 | 25.33 | 5.67 | 24.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.50 | 14.87 | 2.67 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
February | 10.50 | 14.86 | 1.33 | 14.85 | 0.00 | 14.85 | 0.00 | 14.85 |
March | 3.50 | 14.87 | 0.67 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.38 | 0.00 | 27.38 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.55 | 0.00 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 | 27.61 | 0.00 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 32.83 | 27.63 | 0.00 | 27.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 27.61 | 0.00 | 27.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.52 | 0.00 | 27.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.44 | 0.00 | 27.44 |
November | 2.50 | 14.90 | 0.17 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
December | 31.00 | 14.84 | 4.67 | 14.83 | 0.00 | 14.83 | 0.00 | 14.83 |
Annual Sum or Average | 65.00 | 14.85 | 9.50 | 14.84 | 113.67 | 22.55 | 0.00 | 22.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 0.00 | 14.83 |
Maximum of Months | 31.00 | 14.90 | 4.67 | 14.89 | 32.83 | 27.63 | 0.00 | 27.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.29 | 262.17 | 21.22 | 262.17 | 21.19 |
February | 276.00 | 21.56 | 206.17 | 21.39 | 206.17 | 21.31 |
March | 324.00 | 22.28 | 149.33 | 21.93 | 149.33 | 21.75 |
April | 221.67 | 23.44 | 33.33 | 23.38 | 11.50 | 23.29 |
May | 58.50 | 23.74 | 160.33 | 23.86 | 0.00 | 23.86 |
June | 1.67 | 22.80 | 273.83 | 23.90 | 0.00 | 23.90 |
July | 40.17 | 23.93 | 300.00 | 23.92 | 40.17 | 23.92 |
August | 14.83 | 23.91 | 321.00 | 23.91 | 14.83 | 23.91 |
September | 19.67 | 23.83 | 271.17 | 23.90 | 16.17 | 23.90 |
October | 110.83 | 23.62 | 114.83 | 23.76 | 5.67 | 23.77 |
November | 279.50 | 22.53 | 95.33 | 22.18 | 95.33 | 21.97 |
December | 300.00 | 21.26 | 264.17 | 21.19 | 264.17 | 21.17 |
Annual Sum or Average | 1946.83 | 22.22 | 2451.67 | 22.54 | 1065.50 | 22.30 |
Minimum of Months | 1.67 | 21.26 | 33.33 | 21.19 | 0.00 | 21.17 |
Maximum of Months | 324.00 | 23.93 | 321.00 | 23.92 | 264.17 | 23.92 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 17.34 | 299.33 | 17.34 | 299.33 | 17.33 |
February | 276.00 | 18.15 | 259.83 | 18.04 | 259.83 | 17.99 |
March | 324.00 | 19.97 | 202.67 | 19.42 | 202.67 | 19.17 |
April | 140.33 | 22.73 | 154.00 | 24.18 | 28.33 | 23.95 |
May | 143.33 | 26.27 | 277.50 | 26.45 | 124.17 | 26.51 |
June | 239.33 | 26.70 | 312.00 | 26.68 | 239.33 | 26.69 |
July | 288.33 | 26.70 | 300.00 | 26.71 | 288.33 | 26.71 |
August | 287.33 | 26.68 | 324.00 | 26.67 | 287.33 | 26.67 |
September | 221.00 | 26.66 | 290.67 | 26.62 | 218.33 | 26.64 |
October | 130.83 | 24.13 | 200.50 | 25.40 | 47.83 | 25.54 |
November | 269.17 | 20.19 | 155.33 | 19.67 | 146.67 | 19.35 |
December | 300.00 | 17.13 | 300.00 | 17.13 | 300.00 | 17.13 |
Annual Sum or Average | 2919.67 | 22.27 | 3075.83 | 22.67 | 2442.17 | 22.53 |
Minimum of Months | 130.83 | 17.13 | 154.00 | 17.13 | 28.33 | 17.13 |
Maximum of Months | 324.00 | 26.70 | 324.00 | 26.71 | 300.00 | 26.71 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 14.92 | 300.00 | 14.92 | 300.00 | 14.92 |
February | 276.00 | 16.04 | 276.00 | 16.04 | 276.00 | 16.04 |
March | 324.00 | 19.12 | 247.50 | 18.72 | 247.50 | 18.55 |
April | 175.83 | 24.01 | 159.00 | 25.00 | 69.83 | 25.12 |
May | 258.50 | 29.46 | 294.00 | 29.33 | 248.17 | 29.44 |
June | 312.00 | 31.64 | 312.00 | 31.64 | 312.00 | 31.64 |
July | 300.00 | 31.11 | 300.00 | 31.11 | 300.00 | 31.11 |
August | 324.00 | 30.46 | 324.00 | 30.46 | 324.00 | 30.46 |
September | 281.00 | 29.81 | 300.00 | 29.69 | 281.00 | 29.73 |
October | 160.33 | 25.68 | 205.17 | 26.50 | 83.00 | 26.88 |
November | 280.50 | 19.41 | 199.33 | 18.91 | 195.83 | 18.68 |
December | 300.00 | 14.06 | 300.00 | 14.06 | 300.00 | 14.06 |
Annual Sum or Average | 3292.17 | 23.74 | 3217.00 | 23.92 | 2937.33 | 23.90 |
Minimum of Months | 160.33 | 14.06 | 159.00 | 14.06 | 69.83 | 14.06 |
Maximum of Months | 324.00 | 31.64 | 324.00 | 31.64 | 324.00 | 31.64 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 3720080.53 | 950533.11 | 4.67 | 3720080.53 | -0.0 | 0.00 | 0.05 | 21-FEB-16:30 | 0.00 | 01-FEB-00:10 | 425.25 | 21-FEB-16:30 | 425.25 | 21-FEB-16:30 | 0.00 | 21-FEB-16:20 | 108.44 | 21-FEB-16:30 | 0.00 | 01-FEB-00:10 |
March | 0.154224E+09 | 38397043.49 | 31.67 | 0.154224E+09 | -0.0 | 0.00 | 0.37 | 21-MAR-16:00 | 0.00 | 01-MAR-00:10 | 3245.39 | 21-MAR-16:00 | 3245.39 | 21-MAR-16:00 | 0.00 | 16-MAR-14:40 | 805.68 | 21-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.238977E+10 | 0.599688E+09 | 165.71 | 0.237493E+10 | 14839772.43 | 0.00 | 1.00 | 20-APR-05:05 | 0.00 | 01-APR-00:10 | 19865.93 | 20-APR-05:05 | 19865.93 | 20-APR-05:05 | 1784.79 | 29-APR-05:03 | 4332.81 | 20-APR-05:05 | 0.00 | 01-APR-00:10 |
May | 0.618882E+10 | 0.153559E+10 | 268.52 | 0.596572E+10 | 0.223102E+09 | 0.00 | 1.00 | 01-MAY-05:03 | 0.00 | 01-MAY-00:10 | 21524.26 | 23-MAY-05:01 | 20402.10 | 31-MAY-05:01 | 6497.30 | 24-MAY-05:02 | 4692.90 | 23-MAY-05:01 | 0.00 | 01-MAY-00:10 |
June | 0.933454E+10 | 0.241550E+10 | 303.07 | 0.882123E+10 | 0.513315E+09 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:03 | 22330.33 | 28-JUN-05:02 | 20971.58 | 17-JUN-05:01 | 9062.93 | 29-JUN-05:45 | 4851.27 | 28-JUN-05:02 | 0.00 | 01-JUN-00:03 |
July | 0.109370E+11 | 0.267619E+10 | 298.48 | 0.871802E+10 | 0.221900E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 25642.46 | 22-JUL-05:01 | 21402.98 | 03-JUL-05:01 | 15653.73 | 21-JUL-05:05 | 5490.61 | 30-JUL-17:23 | 0.00 | 01-JUL-00:10 |
August | 0.101296E+11 | 0.247360E+10 | 318.67 | 0.851347E+10 | 0.161612E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 24769.91 | 03-AUG-05:01 | 20977.53 | 24-AUG-05:01 | 12569.75 | 02-AUG-05:10 | 5269.27 | 03-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.813488E+10 | 0.195888E+10 | 276.33 | 0.689891E+10 | 0.123596E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 24189.06 | 22-SEP-05:01 | 21832.39 | 04-SEP-16:43 | 12747.42 | 22-SEP-05:09 | 5425.65 | 03-SEP-15:02 | 0.00 | 01-SEP-00:10 |
October | 0.313287E+10 | 0.749542E+09 | 178.82 | 0.277155E+10 | 0.361324E+09 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 22658.79 | 04-OCT-05:02 | 20585.90 | 02-OCT-05:01 | 10494.13 | 04-OCT-05:03 | 4912.85 | 04-OCT-05:02 | 0.00 | 01-OCT-00:10 |
November | 0.177017E+09 | 43365382.60 | 27.67 | 0.174809E+09 | 2207535.87 | 0.00 | 0.50 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 | 4714.65 | 03-NOV-16:00 | 4714.65 | 03-NOV-16:00 | 222.91 | 03-NOV-13:10 | 1121.90 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.505824E+11 | 0.124917E+11 | 1873.60 | 0.443966E+11 | 0.618587E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.109370E+11 | 0.267619E+10 | 318.67 | 0.882123E+10 | 0.221900E+10 | 0.00 | 1.00 | 0.00 | 25642.46 | 21832.39 | 15653.73 | 5490.61 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.197149E+10 | 0.538265E+09 | 79.64 | 0.196991E+10 | 1586437.13 | 0.00 | 1.00 | 21-APR-17:10 | 0.00 | 01-APR-00:10 | 63160.00 | 30-APR-10:25 | 63160.00 | 30-APR-10:25 | 250.68 | 29-APR-10:40 | 14427.67 | 30-APR-11:25 | 0.00 | 01-APR-00:10 |
May | 0.124614E+11 | 0.333052E+10 | 258.37 | 0.121161E+11 | 0.345281E+09 | 0.00 | 1.00 | 07-MAY-12:05 | 0.00 | 01-MAY-00:10 | 70505.63 | 28-MAY-08:55 | 64099.91 | 22-MAY-19:31 | 20316.46 | 28-MAY-08:55 | 16456.22 | 19-MAY-17:06 | 0.00 | 01-MAY-00:10 |
June | 0.259986E+11 | 0.713318E+10 | 397.78 | 0.251100E+11 | 0.888573E+09 | 0.00 | 1.00 | 01-JUN-15:10 | 0.00 | 01-JUN-00:03 | 73587.89 | 19-JUN-18:03 | 64247.38 | 26-JUN-22:31 | 26566.06 | 19-JUN-18:03 | 17234.38 | 18-JUN-15:43 | 0.00 | 01-JUN-00:03 |
July | 0.295014E+11 | 0.768314E+10 | 413.55 | 0.247827E+11 | 0.471870E+10 | 0.00 | 1.00 | 01-JUL-17:06 | 0.00 | 01-JUL-00:10 | 79298.09 | 21-JUL-20:55 | 63445.41 | 30-JUL-15:32 | 40990.81 | 21-JUL-20:55 | 17660.14 | 02-JUL-16:03 | 0.00 | 01-JUL-00:10 |
August | 0.242656E+11 | 0.633253E+10 | 367.80 | 0.215192E+11 | 0.274647E+10 | 0.00 | 1.00 | 01-AUG-00:41 | 0.00 | 01-AUG-00:15 | 75432.76 | 03-AUG-00:05 | 64248.36 | 24-AUG-01:25 | 34689.97 | 01-AUG-22:35 | 17189.47 | 06-AUG-15:02 | 0.00 | 01-AUG-00:10 |
September | 0.170982E+11 | 0.437606E+10 | 271.27 | 0.148797E+11 | 0.221853E+10 | 0.00 | 1.00 | 01-SEP-17:06 | 0.00 | 01-SEP-00:10 | 74193.40 | 03-SEP-08:42 | 63966.06 | 10-SEP-20:15 | 31161.82 | 03-SEP-07:55 | 16507.09 | 10-SEP-10:45 | 0.00 | 01-SEP-00:10 |
October | 0.291386E+10 | 0.750637E+09 | 70.75 | 0.254963E+10 | 0.364224E+09 | 0.00 | 1.00 | 01-OCT-09:53 | 0.00 | 01-OCT-00:10 | 70082.13 | 04-OCT-19:35 | 63776.65 | 22-OCT-13:45 | 15834.34 | 08-OCT-13:35 | 16095.46 | 04-OCT-19:35 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.114211E+12 | 0.301443E+11 | 1859.16 | 0.102927E+12 | 0.112834E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.295014E+11 | 0.768314E+10 | 413.55 | 0.251100E+11 | 0.471870E+10 | 0.00 | 1.00 | 0.00 | 79298.09 | 64248.36 | 40990.81 | 17660.14 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.33 | 39.08 | 30.25 | 86.46 | 90.72 | 0.00 | 0.00 | 0.00 |
February | 78.03 | 41.40 | 36.63 | 103.43 | 80.17 | 0.00 | 0.00 | 0.00 |
March | 106.45 | 57.04 | 49.40 | 150.17 | 72.00 | 0.00 | 0.00 | 0.00 |
April | 122.21 | 65.91 | 56.30 | 187.63 | 52.46 | 0.00 | 0.00 | 0.00 |
May | 131.62 | 70.33 | 61.29 | 217.76 | 39.40 | 0.00 | 0.00 | 0.00 |
June | 128.44 | 69.03 | 59.41 | 234.96 | 23.88 | 0.00 | 0.00 | 0.00 |
July | 114.07 | 56.74 | 57.33 | 207.74 | 21.20 | 0.00 | 0.00 | 0.00 |
August | 110.21 | 56.10 | 54.12 | 193.93 | 27.81 | 0.00 | 0.00 | 0.00 |
September | 113.03 | 63.05 | 49.97 | 190.14 | 48.85 | 0.00 | 0.00 | 0.00 |
October | 97.07 | 56.63 | 40.44 | 144.76 | 66.92 | 0.00 | 0.00 | 0.00 |
November | 80.95 | 49.08 | 31.86 | 106.07 | 89.85 | 0.00 | 0.00 | 0.00 |
December | 65.68 | 35.68 | 30.00 | 77.43 | 103.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 101.51 | 55.04 | 46.46 | 158.59 | 59.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 65.68 | 35.68 | 30.00 | 77.43 | 21.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 131.62 | 70.33 | 61.29 | 234.96 | 103.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.33 | 39.08 | 30.25 | 86.46 | 90.72 | 0.00 | 0.00 | 0.00 |
February | 78.03 | 41.40 | 36.63 | 103.43 | 80.17 | 0.00 | 0.00 | 0.00 |
March | 106.45 | 57.04 | 49.40 | 150.17 | 72.00 | 0.00 | 0.00 | 0.00 |
April | 122.21 | 65.91 | 56.30 | 187.63 | 52.46 | 0.00 | 0.00 | 0.00 |
May | 131.62 | 70.33 | 61.29 | 217.76 | 39.40 | 0.00 | 0.00 | 0.00 |
June | 128.44 | 69.03 | 59.41 | 234.96 | 23.88 | 0.00 | 0.00 | 0.00 |
July | 114.07 | 56.74 | 57.33 | 207.74 | 21.20 | 0.00 | 0.00 | 0.00 |
August | 110.21 | 56.10 | 54.12 | 193.93 | 27.81 | 0.00 | 0.00 | 0.00 |
September | 113.03 | 63.05 | 49.97 | 190.14 | 48.85 | 0.00 | 0.00 | 0.00 |
October | 97.07 | 56.63 | 40.44 | 144.76 | 66.92 | 0.00 | 0.00 | 0.00 |
November | 80.95 | 49.08 | 31.86 | 106.07 | 89.85 | 0.00 | 0.00 | 0.00 |
December | 65.68 | 35.68 | 30.00 | 77.43 | 103.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 101.51 | 55.04 | 46.46 | 158.59 | 59.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 65.68 | 35.68 | 30.00 | 77.43 | 21.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 131.62 | 70.33 | 61.29 | 234.96 | 103.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.34 | 0.00 | 14.34 | 6.14 | 55.22 | 0.00 | 0.00 | 0.00 |
February | 17.51 | 0.00 | 17.51 | 12.19 | 48.27 | 0.00 | 0.00 | 0.00 |
March | 22.92 | 0.00 | 22.92 | 20.75 | 43.06 | 0.00 | 0.00 | 0.00 |
April | 26.55 | 0.29 | 26.26 | 31.25 | 30.24 | 0.00 | 0.00 | 0.00 |
May | 31.43 | 2.32 | 29.12 | 48.09 | 21.64 | 0.00 | 0.00 | 0.00 |
June | 33.30 | 4.04 | 29.26 | 65.17 | 13.27 | 0.00 | 0.00 | 0.00 |
July | 30.72 | 2.87 | 27.85 | 58.89 | 11.84 | 0.00 | 0.00 | 0.00 |
August | 26.17 | 0.67 | 25.49 | 45.69 | 15.60 | 0.00 | 0.00 | 0.00 |
September | 22.72 | 0.02 | 22.69 | 34.47 | 28.47 | 0.00 | 0.00 | 0.00 |
October | 18.84 | 0.00 | 18.84 | 18.23 | 39.92 | 0.00 | 0.00 | 0.00 |
November | 15.21 | 0.00 | 15.21 | 6.90 | 54.82 | 0.00 | 0.00 | 0.00 |
December | 14.23 | 0.00 | 14.23 | 4.35 | 63.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.85 | 0.85 | 22.00 | 29.43 | 35.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.23 | 0.00 | 14.23 | 4.35 | 11.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.30 | 4.04 | 29.26 | 65.17 | 63.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.34 | 0.00 | 14.34 | 6.14 | 55.21 | 0.00 | 0.00 | 0.00 |
February | 17.51 | 0.00 | 17.51 | 12.19 | 48.27 | 0.00 | 0.00 | 0.00 |
March | 22.92 | 0.00 | 22.92 | 20.75 | 43.06 | 0.00 | 0.00 | 0.00 |
April | 26.55 | 0.29 | 26.26 | 31.25 | 30.24 | 0.00 | 0.00 | 0.00 |
May | 31.43 | 2.32 | 29.11 | 48.09 | 21.64 | 0.00 | 0.00 | 0.00 |
June | 33.30 | 4.04 | 29.26 | 65.17 | 13.27 | 0.00 | 0.00 | 0.00 |
July | 30.71 | 2.87 | 27.85 | 58.89 | 11.84 | 0.00 | 0.00 | 0.00 |
August | 26.17 | 0.67 | 25.49 | 45.69 | 15.60 | 0.00 | 0.00 | 0.00 |
September | 22.72 | 0.02 | 22.69 | 34.47 | 28.47 | 0.00 | 0.00 | 0.00 |
October | 18.84 | 0.00 | 18.84 | 18.23 | 39.92 | 0.00 | 0.00 | 0.00 |
November | 15.21 | 0.00 | 15.21 | 6.90 | 54.82 | 0.00 | 0.00 | 0.00 |
December | 14.23 | 0.00 | 14.23 | 4.35 | 63.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.85 | 0.85 | 22.00 | 29.43 | 35.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.23 | 0.00 | 14.23 | 4.35 | 11.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.30 | 4.04 | 29.26 | 65.17 | 63.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.60 | 23.98 | 10.62 | 41.19 | 36.15 | 0.00 | 0.00 | 0.00 |
February | 45.20 | 31.87 | 13.33 | 55.95 | 34.09 | 0.00 | 0.00 | 0.00 |
March | 64.19 | 45.49 | 18.70 | 82.65 | 32.21 | 0.00 | 0.00 | 0.00 |
April | 80.49 | 60.04 | 20.46 | 106.52 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 89.06 | 66.63 | 22.43 | 121.82 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 94.35 | 73.63 | 20.71 | 135.04 | 16.70 | 0.00 | 0.00 | 0.00 |
July | 81.48 | 59.20 | 22.28 | 117.91 | 13.43 | 0.00 | 0.00 | 0.00 |
August | 76.05 | 55.24 | 20.81 | 107.92 | 16.62 | 0.00 | 0.00 | 0.00 |
September | 69.15 | 51.92 | 17.23 | 96.03 | 25.02 | 0.00 | 0.00 | 0.00 |
October | 51.45 | 37.34 | 14.10 | 66.48 | 30.73 | 0.00 | 0.00 | 0.00 |
November | 39.47 | 29.08 | 10.39 | 47.09 | 37.64 | 0.00 | 0.00 | 0.00 |
December | 31.83 | 20.81 | 11.02 | 35.54 | 41.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.17 | 46.31 | 16.86 | 84.62 | 27.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.83 | 20.81 | 10.39 | 35.54 | 13.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.35 | 73.63 | 22.43 | 135.04 | 41.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.60 | 23.98 | 10.62 | 41.19 | 36.15 | 0.00 | 0.00 | 0.00 |
February | 45.20 | 31.87 | 13.33 | 55.95 | 34.09 | 0.00 | 0.00 | 0.00 |
March | 64.19 | 45.49 | 18.70 | 82.65 | 32.21 | 0.00 | 0.00 | 0.00 |
April | 80.49 | 60.04 | 20.46 | 106.52 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 89.06 | 66.63 | 22.43 | 121.82 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 94.35 | 73.63 | 20.71 | 135.04 | 16.70 | 0.00 | 0.00 | 0.00 |
July | 81.48 | 59.20 | 22.28 | 117.91 | 13.43 | 0.00 | 0.00 | 0.00 |
August | 76.05 | 55.24 | 20.81 | 107.92 | 16.62 | 0.00 | 0.00 | 0.00 |
September | 69.15 | 51.92 | 17.23 | 96.03 | 25.02 | 0.00 | 0.00 | 0.00 |
October | 51.45 | 37.34 | 14.10 | 66.48 | 30.73 | 0.00 | 0.00 | 0.00 |
November | 39.47 | 29.08 | 10.39 | 47.09 | 37.64 | 0.00 | 0.00 | 0.00 |
December | 31.83 | 20.81 | 11.02 | 35.54 | 41.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.17 | 46.31 | 16.86 | 84.62 | 27.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.83 | 20.81 | 10.39 | 35.54 | 13.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.35 | 73.63 | 22.43 | 135.04 | 41.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.60 | 23.98 | 10.62 | 41.19 | 36.15 | 0.00 | 0.00 | 0.00 |
February | 45.20 | 31.87 | 13.33 | 55.95 | 34.09 | 0.00 | 0.00 | 0.00 |
March | 64.19 | 45.49 | 18.70 | 82.65 | 32.21 | 0.00 | 0.00 | 0.00 |
April | 80.49 | 60.04 | 20.46 | 106.52 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 89.06 | 66.63 | 22.43 | 121.82 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 94.35 | 73.63 | 20.71 | 135.04 | 16.70 | 0.00 | 0.00 | 0.00 |
July | 81.48 | 59.20 | 22.28 | 117.91 | 13.43 | 0.00 | 0.00 | 0.00 |
August | 76.05 | 55.24 | 20.81 | 107.92 | 16.62 | 0.00 | 0.00 | 0.00 |
September | 69.15 | 51.92 | 17.23 | 96.03 | 25.02 | 0.00 | 0.00 | 0.00 |
October | 51.45 | 37.34 | 14.10 | 66.48 | 30.73 | 0.00 | 0.00 | 0.00 |
November | 39.47 | 29.08 | 10.39 | 47.09 | 37.64 | 0.00 | 0.00 | 0.00 |
December | 31.83 | 20.81 | 11.02 | 35.54 | 41.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.17 | 46.31 | 16.86 | 84.62 | 27.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.83 | 20.81 | 10.39 | 35.54 | 13.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.35 | 73.63 | 22.43 | 135.04 | 41.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.60 | 23.98 | 10.62 | 41.19 | 36.15 | 0.00 | 0.00 | 0.00 |
February | 45.20 | 31.87 | 13.33 | 55.95 | 34.09 | 0.00 | 0.00 | 0.00 |
March | 64.19 | 45.49 | 18.70 | 82.65 | 32.21 | 0.00 | 0.00 | 0.00 |
April | 80.49 | 60.04 | 20.46 | 106.52 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 89.06 | 66.63 | 22.43 | 121.82 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 94.35 | 73.63 | 20.71 | 135.04 | 16.70 | 0.00 | 0.00 | 0.00 |
July | 81.48 | 59.20 | 22.28 | 117.91 | 13.43 | 0.00 | 0.00 | 0.00 |
August | 76.05 | 55.24 | 20.81 | 107.92 | 16.62 | 0.00 | 0.00 | 0.00 |
September | 69.15 | 51.92 | 17.23 | 96.03 | 25.02 | 0.00 | 0.00 | 0.00 |
October | 51.45 | 37.34 | 14.10 | 66.48 | 30.73 | 0.00 | 0.00 | 0.00 |
November | 39.47 | 29.08 | 10.39 | 47.09 | 37.64 | 0.00 | 0.00 | 0.00 |
December | 31.83 | 20.81 | 11.02 | 35.54 | 41.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.17 | 46.31 | 16.86 | 84.62 | 27.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.83 | 20.81 | 10.39 | 35.54 | 13.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.35 | 73.63 | 22.43 | 135.04 | 41.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.60 | 23.98 | 10.62 | 41.19 | 36.15 | 0.00 | 0.00 | 0.00 |
February | 45.20 | 31.87 | 13.33 | 55.95 | 34.09 | 0.00 | 0.00 | 0.00 |
March | 64.19 | 45.49 | 18.70 | 82.65 | 32.21 | 0.00 | 0.00 | 0.00 |
April | 80.49 | 60.04 | 20.46 | 106.52 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 89.06 | 66.63 | 22.43 | 121.82 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 94.35 | 73.63 | 20.71 | 135.04 | 16.70 | 0.00 | 0.00 | 0.00 |
July | 81.48 | 59.20 | 22.28 | 117.91 | 13.43 | 0.00 | 0.00 | 0.00 |
August | 76.05 | 55.24 | 20.81 | 107.92 | 16.62 | 0.00 | 0.00 | 0.00 |
September | 69.15 | 51.92 | 17.23 | 96.03 | 25.02 | 0.00 | 0.00 | 0.00 |
October | 51.45 | 37.34 | 14.10 | 66.48 | 30.73 | 0.00 | 0.00 | 0.00 |
November | 39.47 | 29.08 | 10.39 | 47.09 | 37.64 | 0.00 | 0.00 | 0.00 |
December | 31.83 | 20.81 | 11.02 | 35.54 | 41.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.17 | 46.31 | 16.86 | 84.62 | 27.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.83 | 20.81 | 10.39 | 35.54 | 13.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.35 | 73.63 | 22.43 | 135.04 | 41.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.60 | 23.98 | 10.62 | 41.19 | 36.15 | 0.00 | 0.00 | 0.00 |
February | 45.20 | 31.87 | 13.33 | 55.95 | 34.09 | 0.00 | 0.00 | 0.00 |
March | 64.19 | 45.49 | 18.70 | 82.65 | 32.21 | 0.00 | 0.00 | 0.00 |
April | 80.49 | 60.04 | 20.46 | 106.52 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 89.06 | 66.63 | 22.43 | 121.82 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 94.35 | 73.63 | 20.71 | 135.04 | 16.70 | 0.00 | 0.00 | 0.00 |
July | 81.48 | 59.20 | 22.28 | 117.91 | 13.43 | 0.00 | 0.00 | 0.00 |
August | 76.05 | 55.24 | 20.81 | 107.92 | 16.62 | 0.00 | 0.00 | 0.00 |
September | 69.15 | 51.92 | 17.23 | 96.03 | 25.02 | 0.00 | 0.00 | 0.00 |
October | 51.45 | 37.34 | 14.10 | 66.48 | 30.73 | 0.00 | 0.00 | 0.00 |
November | 39.47 | 29.08 | 10.39 | 47.09 | 37.64 | 0.00 | 0.00 | 0.00 |
December | 31.83 | 20.81 | 11.02 | 35.54 | 41.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.17 | 46.31 | 16.86 | 84.62 | 27.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.83 | 20.81 | 10.39 | 35.54 | 13.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.35 | 73.63 | 22.43 | 135.04 | 41.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.60 | 23.98 | 10.62 | 41.19 | 36.15 | 0.00 | 0.00 | 0.00 |
February | 45.20 | 31.87 | 13.33 | 55.95 | 34.09 | 0.00 | 0.00 | 0.00 |
March | 64.19 | 45.49 | 18.70 | 82.65 | 32.21 | 0.00 | 0.00 | 0.00 |
April | 80.49 | 60.04 | 20.46 | 106.52 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 89.06 | 66.63 | 22.43 | 121.82 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 94.35 | 73.63 | 20.71 | 135.04 | 16.70 | 0.00 | 0.00 | 0.00 |
July | 81.48 | 59.20 | 22.28 | 117.91 | 13.43 | 0.00 | 0.00 | 0.00 |
August | 76.05 | 55.24 | 20.81 | 107.92 | 16.62 | 0.00 | 0.00 | 0.00 |
September | 69.15 | 51.92 | 17.23 | 96.03 | 25.02 | 0.00 | 0.00 | 0.00 |
October | 51.45 | 37.34 | 14.10 | 66.48 | 30.73 | 0.00 | 0.00 | 0.00 |
November | 39.47 | 29.08 | 10.39 | 47.09 | 37.64 | 0.00 | 0.00 | 0.00 |
December | 31.83 | 20.81 | 11.02 | 35.54 | 41.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.17 | 46.31 | 16.86 | 84.62 | 27.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.83 | 20.81 | 10.39 | 35.54 | 13.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.35 | 73.63 | 22.43 | 135.04 | 41.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.60 | 23.98 | 10.62 | 41.19 | 36.15 | 0.00 | 0.00 | 0.00 |
February | 45.20 | 31.87 | 13.33 | 55.95 | 34.09 | 0.00 | 0.00 | 0.00 |
March | 64.19 | 45.49 | 18.70 | 82.65 | 32.21 | 0.00 | 0.00 | 0.00 |
April | 80.49 | 60.04 | 20.46 | 106.52 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 89.06 | 66.63 | 22.43 | 121.82 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 94.35 | 73.63 | 20.71 | 135.04 | 16.70 | 0.00 | 0.00 | 0.00 |
July | 81.48 | 59.20 | 22.28 | 117.91 | 13.43 | 0.00 | 0.00 | 0.00 |
August | 76.05 | 55.24 | 20.81 | 107.92 | 16.62 | 0.00 | 0.00 | 0.00 |
September | 69.15 | 51.92 | 17.23 | 96.03 | 25.02 | 0.00 | 0.00 | 0.00 |
October | 51.45 | 37.34 | 14.10 | 66.48 | 30.73 | 0.00 | 0.00 | 0.00 |
November | 39.47 | 29.08 | 10.39 | 47.09 | 37.64 | 0.00 | 0.00 | 0.00 |
December | 31.83 | 20.81 | 11.02 | 35.54 | 41.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.17 | 46.31 | 16.86 | 84.62 | 27.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.83 | 20.81 | 10.39 | 35.54 | 13.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.35 | 73.63 | 22.43 | 135.04 | 41.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.60 | 23.98 | 10.62 | 41.19 | 36.15 | 0.00 | 0.00 | 0.00 |
February | 45.20 | 31.87 | 13.33 | 55.95 | 34.09 | 0.00 | 0.00 | 0.00 |
March | 64.19 | 45.49 | 18.70 | 82.65 | 32.21 | 0.00 | 0.00 | 0.00 |
April | 80.49 | 60.04 | 20.46 | 106.52 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 89.06 | 66.63 | 22.43 | 121.82 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 94.35 | 73.63 | 20.71 | 135.04 | 16.70 | 0.00 | 0.00 | 0.00 |
July | 81.48 | 59.20 | 22.28 | 117.91 | 13.43 | 0.00 | 0.00 | 0.00 |
August | 76.05 | 55.24 | 20.81 | 107.92 | 16.62 | 0.00 | 0.00 | 0.00 |
September | 69.15 | 51.92 | 17.23 | 96.03 | 25.02 | 0.00 | 0.00 | 0.00 |
October | 51.45 | 37.34 | 14.10 | 66.48 | 30.73 | 0.00 | 0.00 | 0.00 |
November | 39.47 | 29.08 | 10.39 | 47.09 | 37.64 | 0.00 | 0.00 | 0.00 |
December | 31.83 | 20.81 | 11.02 | 35.54 | 41.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.17 | 46.31 | 16.86 | 84.62 | 27.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.83 | 20.81 | 10.39 | 35.54 | 13.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.35 | 73.63 | 22.43 | 135.04 | 41.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.60 | 23.98 | 10.62 | 41.19 | 36.15 | 0.00 | 0.00 | 0.00 |
February | 45.20 | 31.87 | 13.33 | 55.95 | 34.09 | 0.00 | 0.00 | 0.00 |
March | 64.19 | 45.49 | 18.70 | 82.65 | 32.21 | 0.00 | 0.00 | 0.00 |
April | 80.49 | 60.04 | 20.46 | 106.52 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 89.06 | 66.63 | 22.43 | 121.82 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 94.35 | 73.63 | 20.71 | 135.04 | 16.70 | 0.00 | 0.00 | 0.00 |
July | 81.48 | 59.20 | 22.28 | 117.91 | 13.43 | 0.00 | 0.00 | 0.00 |
August | 76.05 | 55.24 | 20.81 | 107.92 | 16.62 | 0.00 | 0.00 | 0.00 |
September | 69.15 | 51.92 | 17.23 | 96.03 | 25.02 | 0.00 | 0.00 | 0.00 |
October | 51.45 | 37.34 | 14.10 | 66.48 | 30.73 | 0.00 | 0.00 | 0.00 |
November | 39.47 | 29.08 | 10.39 | 47.09 | 37.64 | 0.00 | 0.00 | 0.00 |
December | 31.83 | 20.81 | 11.02 | 35.54 | 41.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.17 | 46.31 | 16.86 | 84.62 | 27.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.83 | 20.81 | 10.39 | 35.54 | 13.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.35 | 73.63 | 22.43 | 135.04 | 41.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.60 | 23.98 | 10.62 | 41.19 | 36.15 | 0.00 | 0.00 | 0.00 |
February | 45.20 | 31.87 | 13.33 | 55.95 | 34.09 | 0.00 | 0.00 | 0.00 |
March | 64.19 | 45.49 | 18.70 | 82.65 | 32.21 | 0.00 | 0.00 | 0.00 |
April | 80.49 | 60.04 | 20.46 | 106.52 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 89.06 | 66.63 | 22.43 | 121.82 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 94.35 | 73.63 | 20.71 | 135.04 | 16.70 | 0.00 | 0.00 | 0.00 |
July | 81.48 | 59.20 | 22.28 | 117.91 | 13.43 | 0.00 | 0.00 | 0.00 |
August | 76.05 | 55.24 | 20.81 | 107.92 | 16.62 | 0.00 | 0.00 | 0.00 |
September | 69.15 | 51.92 | 17.23 | 96.03 | 25.02 | 0.00 | 0.00 | 0.00 |
October | 51.45 | 37.34 | 14.10 | 66.48 | 30.73 | 0.00 | 0.00 | 0.00 |
November | 39.47 | 29.08 | 10.39 | 47.09 | 37.64 | 0.00 | 0.00 | 0.00 |
December | 31.83 | 20.81 | 11.02 | 35.54 | 41.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.17 | 46.31 | 16.86 | 84.62 | 27.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.83 | 20.81 | 10.39 | 35.54 | 13.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.35 | 73.63 | 22.43 | 135.04 | 41.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.60 | 23.98 | 10.62 | 41.19 | 36.15 | 0.00 | 0.00 | 0.00 |
February | 45.20 | 31.87 | 13.33 | 55.95 | 34.09 | 0.00 | 0.00 | 0.00 |
March | 64.19 | 45.49 | 18.70 | 82.65 | 32.21 | 0.00 | 0.00 | 0.00 |
April | 80.49 | 60.04 | 20.46 | 106.52 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 89.06 | 66.63 | 22.43 | 121.82 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 94.35 | 73.63 | 20.71 | 135.04 | 16.70 | 0.00 | 0.00 | 0.00 |
July | 81.48 | 59.20 | 22.28 | 117.91 | 13.43 | 0.00 | 0.00 | 0.00 |
August | 76.05 | 55.24 | 20.81 | 107.92 | 16.62 | 0.00 | 0.00 | 0.00 |
September | 69.15 | 51.92 | 17.23 | 96.03 | 25.02 | 0.00 | 0.00 | 0.00 |
October | 51.45 | 37.34 | 14.10 | 66.48 | 30.73 | 0.00 | 0.00 | 0.00 |
November | 39.47 | 29.08 | 10.39 | 47.09 | 37.64 | 0.00 | 0.00 | 0.00 |
December | 31.83 | 20.81 | 11.02 | 35.54 | 41.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.17 | 46.31 | 16.86 | 84.62 | 27.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.83 | 20.81 | 10.39 | 35.54 | 13.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.35 | 73.63 | 22.43 | 135.04 | 41.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.60 | 23.98 | 10.62 | 41.19 | 36.15 | 0.00 | 0.00 | 0.00 |
February | 45.20 | 31.87 | 13.33 | 55.95 | 34.09 | 0.00 | 0.00 | 0.00 |
March | 64.19 | 45.49 | 18.70 | 82.65 | 32.21 | 0.00 | 0.00 | 0.00 |
April | 80.49 | 60.04 | 20.46 | 106.52 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 89.06 | 66.63 | 22.43 | 121.82 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 94.35 | 73.63 | 20.71 | 135.04 | 16.70 | 0.00 | 0.00 | 0.00 |
July | 81.48 | 59.20 | 22.28 | 117.91 | 13.43 | 0.00 | 0.00 | 0.00 |
August | 76.05 | 55.24 | 20.81 | 107.92 | 16.62 | 0.00 | 0.00 | 0.00 |
September | 69.15 | 51.92 | 17.23 | 96.03 | 25.02 | 0.00 | 0.00 | 0.00 |
October | 51.45 | 37.34 | 14.10 | 66.48 | 30.73 | 0.00 | 0.00 | 0.00 |
November | 39.47 | 29.08 | 10.39 | 47.09 | 37.64 | 0.00 | 0.00 | 0.00 |
December | 31.83 | 20.81 | 11.02 | 35.54 | 41.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.17 | 46.31 | 16.86 | 84.62 | 27.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.83 | 20.81 | 10.39 | 35.54 | 13.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.35 | 73.63 | 22.43 | 135.04 | 41.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.60 | 23.98 | 10.62 | 41.19 | 36.15 | 0.00 | 0.00 | 0.00 |
February | 45.20 | 31.87 | 13.33 | 55.95 | 34.09 | 0.00 | 0.00 | 0.00 |
March | 64.19 | 45.49 | 18.70 | 82.65 | 32.21 | 0.00 | 0.00 | 0.00 |
April | 80.49 | 60.04 | 20.46 | 106.52 | 27.73 | 0.00 | 0.00 | 0.00 |
May | 89.06 | 66.63 | 22.43 | 121.82 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 94.35 | 73.63 | 20.71 | 135.04 | 16.70 | 0.00 | 0.00 | 0.00 |
July | 81.48 | 59.20 | 22.28 | 117.91 | 13.43 | 0.00 | 0.00 | 0.00 |
August | 76.05 | 55.24 | 20.81 | 107.92 | 16.62 | 0.00 | 0.00 | 0.00 |
September | 69.15 | 51.92 | 17.23 | 96.03 | 25.02 | 0.00 | 0.00 | 0.00 |
October | 51.45 | 37.34 | 14.10 | 66.48 | 30.73 | 0.00 | 0.00 | 0.00 |
November | 39.47 | 29.08 | 10.39 | 47.09 | 37.64 | 0.00 | 0.00 | 0.00 |
December | 31.83 | 20.81 | 11.02 | 35.54 | 41.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.17 | 46.31 | 16.86 | 84.62 | 27.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.83 | 20.81 | 10.39 | 35.54 | 13.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.35 | 73.63 | 22.43 | 135.04 | 41.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.43 | 49.41 | 21.02 | 91.42 | 42.10 | 1.00 | 0.00 | 0.00 |
February | 90.11 | 63.72 | 26.39 | 119.18 | 40.24 | 5.67 | 0.00 | 0.00 |
March | 125.80 | 88.79 | 37.01 | 167.48 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 156.49 | 116.00 | 40.49 | 210.42 | 38.73 | 0.00 | 0.00 | 0.00 |
May | 172.53 | 128.14 | 44.39 | 232.98 | 38.57 | 0.00 | 0.00 | 0.00 |
June | 182.18 | 141.19 | 41.00 | 251.08 | 32.33 | 0.00 | 0.00 | 0.00 |
July | 157.68 | 113.59 | 44.09 | 219.02 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 147.44 | 106.25 | 41.18 | 202.41 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 134.98 | 100.89 | 34.10 | 183.58 | 40.75 | 0.00 | 0.00 | 0.00 |
October | 101.83 | 73.92 | 27.91 | 133.62 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 79.83 | 59.26 | 20.57 | 101.19 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 65.33 | 43.52 | 21.80 | 82.86 | 46.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.84 | 90.46 | 33.38 | 166.44 | 39.27 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 43.52 | 20.57 | 82.86 | 26.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 182.18 | 141.19 | 44.39 | 251.08 | 48.54 | 5.67 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185696E+09 | 0.104673E+09 | 81022633.40 | 0.231561E+09 | 0.242992E+09 |
February | 0.188766E+09 | 0.100147E+09 | 88618206.43 | 0.250228E+09 | 0.193948E+09 |
March | 0.285113E+09 | 0.152789E+09 | 0.132324E+09 | 0.402227E+09 | 0.192838E+09 |
April | 0.316767E+09 | 0.170848E+09 | 0.145919E+09 | 0.486345E+09 | 0.135969E+09 |
May | 0.352530E+09 | 0.188375E+09 | 0.164155E+09 | 0.583241E+09 | 0.105528E+09 |
June | 0.332924E+09 | 0.178928E+09 | 0.153997E+09 | 0.609017E+09 | 61889671.51 |
July | 0.305525E+09 | 0.151981E+09 | 0.153544E+09 | 0.556419E+09 | 56781145.54 |
August | 0.295197E+09 | 0.150249E+09 | 0.144948E+09 | 0.519424E+09 | 74480330.10 |
September | 0.292971E+09 | 0.163437E+09 | 0.129533E+09 | 0.492855E+09 | 0.126625E+09 |
October | 0.259991E+09 | 0.151687E+09 | 0.108304E+09 | 0.387718E+09 | 0.179233E+09 |
November | 0.209811E+09 | 0.127224E+09 | 82587157.97 | 0.274942E+09 | 0.232890E+09 |
December | 0.175912E+09 | 95555942.52 | 80355917.40 | 0.207378E+09 | 0.277769E+09 |
Annual Sum or Average | 0.320120E+10 | 0.173590E+10 | 0.146531E+10 | 0.500136E+10 | 0.188094E+10 |
Minimum of Months | 0.175912E+09 | 95555942.52 | 80355917.40 | 0.207378E+09 | 56781145.54 |
Maximum of Months | 0.352530E+09 | 0.188375E+09 | 0.164155E+09 | 0.609017E+09 | 0.277769E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185696E+09 | 0.104673E+09 | 81022633.40 | 0.231561E+09 | 0.242992E+09 |
February | 0.188766E+09 | 0.100147E+09 | 88618206.43 | 0.250228E+09 | 0.193948E+09 |
March | 0.285113E+09 | 0.152789E+09 | 0.132324E+09 | 0.402227E+09 | 0.192838E+09 |
April | 0.316767E+09 | 0.170848E+09 | 0.145919E+09 | 0.486345E+09 | 0.135969E+09 |
May | 0.352530E+09 | 0.188375E+09 | 0.164155E+09 | 0.583241E+09 | 0.105528E+09 |
June | 0.332924E+09 | 0.178928E+09 | 0.153997E+09 | 0.609017E+09 | 61889671.51 |
July | 0.305525E+09 | 0.151981E+09 | 0.153544E+09 | 0.556419E+09 | 56781145.54 |
August | 0.295197E+09 | 0.150249E+09 | 0.144948E+09 | 0.519424E+09 | 74480330.10 |
September | 0.292971E+09 | 0.163437E+09 | 0.129533E+09 | 0.492855E+09 | 0.126625E+09 |
October | 0.259991E+09 | 0.151687E+09 | 0.108304E+09 | 0.387718E+09 | 0.179233E+09 |
November | 0.209811E+09 | 0.127224E+09 | 82587157.97 | 0.274942E+09 | 0.232890E+09 |
December | 0.175912E+09 | 95555942.52 | 80355917.40 | 0.207378E+09 | 0.277769E+09 |
Annual Sum or Average | 0.320120E+10 | 0.173590E+10 | 0.146531E+10 | 0.500136E+10 | 0.188094E+10 |
Minimum of Months | 0.175912E+09 | 95555942.52 | 80355917.40 | 0.207378E+09 | 56781145.54 |
Maximum of Months | 0.352530E+09 | 0.188375E+09 | 0.164155E+09 | 0.609017E+09 | 0.277769E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38409723.68 | 0.00 | 38409723.68 | 16441072.11 | 0.147888E+09 |
February | 42363408.56 | 0.00 | 42363408.56 | 29481620.11 | 0.116778E+09 |
March | 61399587.01 | 6881.96 | 61392705.06 | 55575398.09 | 0.115328E+09 |
April | 68819967.14 | 743727.02 | 68076240.12 | 81011231.83 | 78375823.96 |
May | 84186207.99 | 6203483.47 | 77982724.51 | 0.128802E+09 | 57972380.13 |
June | 86316350.37 | 10468007.19 | 75848343.17 | 0.168917E+09 | 34401662.65 |
July | 82268093.92 | 7674589.43 | 74593504.49 | 0.157724E+09 | 31711782.88 |
August | 70091161.86 | 1806580.97 | 68284580.89 | 0.122368E+09 | 41794738.86 |
September | 58880102.01 | 55417.85 | 58824684.17 | 89357566.48 | 73804505.20 |
October | 50462020.35 | 0.00 | 50462020.35 | 48839563.25 | 0.106930E+09 |
November | 39423614.56 | 0.00 | 39423614.56 | 17891690.31 | 0.142096E+09 |
December | 38112253.17 | 0.00 | 38112253.17 | 11653487.90 | 0.169815E+09 |
Annual Sum or Average | 0.720732E+09 | 26958687.89 | 0.693774E+09 | 0.928063E+09 | 0.111690E+10 |
Minimum of Months | 38112253.17 | 0.00 | 38112253.17 | 11653487.90 | 31711782.88 |
Maximum of Months | 86316350.37 | 10468007.19 | 77982724.51 | 0.168917E+09 | 0.169815E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38408692.36 | 0.00 | 38408692.36 | 16440245.38 | 0.147887E+09 |
February | 42362293.94 | 0.00 | 42362293.94 | 29480692.93 | 0.116777E+09 |
March | 61398002.02 | 6881.63 | 61391120.39 | 55573772.37 | 0.115327E+09 |
April | 68818274.51 | 743692.17 | 68074582.35 | 81009601.29 | 78374969.76 |
May | 84183985.18 | 6203192.71 | 77980792.47 | 0.128800E+09 | 57971391.12 |
June | 86314054.81 | 10467516.55 | 75846538.27 | 0.168914E+09 | 34400912.53 |
July | 82265814.99 | 7674229.71 | 74591585.28 | 0.157720E+09 | 31711178.58 |
August | 70089351.88 | 1806496.29 | 68282855.59 | 0.122366E+09 | 41794084.38 |
September | 58878676.86 | 55415.25 | 58823261.61 | 89356058.51 | 73803610.10 |
October | 50460722.20 | 0.00 | 50460722.20 | 48838246.00 | 0.106930E+09 |
November | 39422608.95 | 0.00 | 39422608.95 | 17891023.66 | 0.142095E+09 |
December | 38111195.69 | 0.00 | 38111195.69 | 11652845.23 | 0.169814E+09 |
Annual Sum or Average | 0.720714E+09 | 26957424.30 | 0.693756E+09 | 0.928042E+09 | 0.111689E+10 |
Minimum of Months | 38111195.69 | 0.00 | 38111195.69 | 11652845.23 | 31711178.58 |
Maximum of Months | 86314054.81 | 10467516.55 | 77980792.47 | 0.168914E+09 | 0.169814E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92684169.41 | 64238604.35 | 28445565.07 | 0.110325E+09 | 96815161.97 |
February | 0.109342E+09 | 77090334.85 | 32251546.97 | 0.135348E+09 | 82473852.86 |
March | 0.171920E+09 | 0.121831E+09 | 50089049.27 | 0.221378E+09 | 86266885.54 |
April | 0.208640E+09 | 0.155618E+09 | 53022776.81 | 0.276108E+09 | 71876463.78 |
May | 0.238541E+09 | 0.178465E+09 | 60075240.38 | 0.326290E+09 | 63979473.96 |
June | 0.244543E+09 | 0.190855E+09 | 53688139.83 | 0.350027E+09 | 43299174.66 |
July | 0.218223E+09 | 0.158557E+09 | 59665486.08 | 0.315809E+09 | 35972962.09 |
August | 0.203691E+09 | 0.147963E+09 | 55728522.84 | 0.289043E+09 | 44511505.97 |
September | 0.179231E+09 | 0.134579E+09 | 44651910.81 | 0.248903E+09 | 64857992.83 |
October | 0.137791E+09 | 0.100024E+09 | 37767659.23 | 0.178060E+09 | 82302525.68 |
November | 0.102300E+09 | 75365277.46 | 26934609.64 | 0.122060E+09 | 97554748.00 |
December | 85250293.31 | 55742840.25 | 29507453.06 | 95177787.14 | 0.112341E+09 |
Annual Sum or Average | 0.199216E+10 | 0.146033E+10 | 0.531828E+09 | 0.266853E+10 | 0.882251E+09 |
Minimum of Months | 85250293.31 | 55742840.25 | 26934609.64 | 95177787.14 | 35972962.09 |
Maximum of Months | 0.244543E+09 | 0.190855E+09 | 60075240.38 | 0.350027E+09 | 0.112341E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92684169.41 | 64238604.35 | 28445565.07 | 0.110325E+09 | 96815161.97 |
February | 0.109342E+09 | 77090334.85 | 32251546.97 | 0.135348E+09 | 82473852.86 |
March | 0.171920E+09 | 0.121831E+09 | 50089049.27 | 0.221378E+09 | 86266885.54 |
April | 0.208640E+09 | 0.155618E+09 | 53022776.81 | 0.276108E+09 | 71876463.78 |
May | 0.238541E+09 | 0.178465E+09 | 60075240.38 | 0.326290E+09 | 63979473.96 |
June | 0.244543E+09 | 0.190855E+09 | 53688139.83 | 0.350027E+09 | 43299174.66 |
July | 0.218223E+09 | 0.158557E+09 | 59665486.08 | 0.315809E+09 | 35972962.09 |
August | 0.203691E+09 | 0.147963E+09 | 55728522.84 | 0.289043E+09 | 44511505.97 |
September | 0.179231E+09 | 0.134579E+09 | 44651910.81 | 0.248903E+09 | 64857992.83 |
October | 0.137791E+09 | 0.100024E+09 | 37767659.23 | 0.178060E+09 | 82302525.68 |
November | 0.102300E+09 | 75365277.46 | 26934609.64 | 0.122060E+09 | 97554748.00 |
December | 85250293.31 | 55742840.25 | 29507453.06 | 95177787.14 | 0.112341E+09 |
Annual Sum or Average | 0.199216E+10 | 0.146033E+10 | 0.531828E+09 | 0.266853E+10 | 0.882251E+09 |
Minimum of Months | 85250293.31 | 55742840.25 | 26934609.64 | 95177787.14 | 35972962.09 |
Maximum of Months | 0.244543E+09 | 0.190855E+09 | 60075240.38 | 0.350027E+09 | 0.112341E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92684169.41 | 64238604.35 | 28445565.07 | 0.110325E+09 | 96815161.97 |
February | 0.109342E+09 | 77090334.85 | 32251546.97 | 0.135348E+09 | 82473852.86 |
March | 0.171920E+09 | 0.121831E+09 | 50089049.27 | 0.221378E+09 | 86266885.54 |
April | 0.208640E+09 | 0.155618E+09 | 53022776.81 | 0.276108E+09 | 71876463.78 |
May | 0.238541E+09 | 0.178465E+09 | 60075240.38 | 0.326290E+09 | 63979473.96 |
June | 0.244543E+09 | 0.190855E+09 | 53688139.83 | 0.350027E+09 | 43299174.66 |
July | 0.218223E+09 | 0.158557E+09 | 59665486.08 | 0.315809E+09 | 35972962.09 |
August | 0.203691E+09 | 0.147963E+09 | 55728522.84 | 0.289043E+09 | 44511505.97 |
September | 0.179231E+09 | 0.134579E+09 | 44651910.81 | 0.248903E+09 | 64857992.83 |
October | 0.137791E+09 | 0.100024E+09 | 37767659.23 | 0.178060E+09 | 82302525.68 |
November | 0.102300E+09 | 75365277.46 | 26934609.64 | 0.122060E+09 | 97554748.00 |
December | 85250293.31 | 55742840.25 | 29507453.06 | 95177787.14 | 0.112341E+09 |
Annual Sum or Average | 0.199216E+10 | 0.146033E+10 | 0.531828E+09 | 0.266853E+10 | 0.882251E+09 |
Minimum of Months | 85250293.31 | 55742840.25 | 26934609.64 | 95177787.14 | 35972962.09 |
Maximum of Months | 0.244543E+09 | 0.190855E+09 | 60075240.38 | 0.350027E+09 | 0.112341E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92684169.41 | 64238604.35 | 28445565.07 | 0.110325E+09 | 96815161.97 |
February | 0.109342E+09 | 77090334.85 | 32251546.97 | 0.135348E+09 | 82473852.86 |
March | 0.171920E+09 | 0.121831E+09 | 50089049.27 | 0.221378E+09 | 86266885.54 |
April | 0.208640E+09 | 0.155618E+09 | 53022776.81 | 0.276108E+09 | 71876463.78 |
May | 0.238541E+09 | 0.178465E+09 | 60075240.38 | 0.326290E+09 | 63979473.96 |
June | 0.244543E+09 | 0.190855E+09 | 53688139.83 | 0.350027E+09 | 43299174.66 |
July | 0.218223E+09 | 0.158557E+09 | 59665486.08 | 0.315809E+09 | 35972962.09 |
August | 0.203691E+09 | 0.147963E+09 | 55728522.84 | 0.289043E+09 | 44511505.97 |
September | 0.179231E+09 | 0.134579E+09 | 44651910.81 | 0.248903E+09 | 64857992.83 |
October | 0.137791E+09 | 0.100024E+09 | 37767659.23 | 0.178060E+09 | 82302525.68 |
November | 0.102300E+09 | 75365277.46 | 26934609.64 | 0.122060E+09 | 97554748.00 |
December | 85250293.31 | 55742840.25 | 29507453.06 | 95177787.14 | 0.112341E+09 |
Annual Sum or Average | 0.199216E+10 | 0.146033E+10 | 0.531828E+09 | 0.266853E+10 | 0.882251E+09 |
Minimum of Months | 85250293.31 | 55742840.25 | 26934609.64 | 95177787.14 | 35972962.09 |
Maximum of Months | 0.244543E+09 | 0.190855E+09 | 60075240.38 | 0.350027E+09 | 0.112341E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92684169.41 | 64238604.35 | 28445565.07 | 0.110325E+09 | 96815161.97 |
February | 0.109342E+09 | 77090334.85 | 32251546.97 | 0.135348E+09 | 82473852.86 |
March | 0.171920E+09 | 0.121831E+09 | 50089049.27 | 0.221378E+09 | 86266885.54 |
April | 0.208640E+09 | 0.155618E+09 | 53022776.81 | 0.276108E+09 | 71876463.78 |
May | 0.238541E+09 | 0.178465E+09 | 60075240.38 | 0.326290E+09 | 63979473.96 |
June | 0.244543E+09 | 0.190855E+09 | 53688139.83 | 0.350027E+09 | 43299174.66 |
July | 0.218223E+09 | 0.158557E+09 | 59665486.08 | 0.315809E+09 | 35972962.09 |
August | 0.203691E+09 | 0.147963E+09 | 55728522.84 | 0.289043E+09 | 44511505.97 |
September | 0.179231E+09 | 0.134579E+09 | 44651910.81 | 0.248903E+09 | 64857992.83 |
October | 0.137791E+09 | 0.100024E+09 | 37767659.23 | 0.178060E+09 | 82302525.68 |
November | 0.102300E+09 | 75365277.46 | 26934609.64 | 0.122060E+09 | 97554748.00 |
December | 85250293.31 | 55742840.25 | 29507453.06 | 95177787.14 | 0.112341E+09 |
Annual Sum or Average | 0.199216E+10 | 0.146033E+10 | 0.531828E+09 | 0.266853E+10 | 0.882251E+09 |
Minimum of Months | 85250293.31 | 55742840.25 | 26934609.64 | 95177787.14 | 35972962.09 |
Maximum of Months | 0.244543E+09 | 0.190855E+09 | 60075240.38 | 0.350027E+09 | 0.112341E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92684169.41 | 64238604.35 | 28445565.07 | 0.110325E+09 | 96815161.97 |
February | 0.109342E+09 | 77090334.85 | 32251546.97 | 0.135348E+09 | 82473852.86 |
March | 0.171920E+09 | 0.121831E+09 | 50089049.27 | 0.221378E+09 | 86266885.54 |
April | 0.208640E+09 | 0.155618E+09 | 53022776.81 | 0.276108E+09 | 71876463.78 |
May | 0.238541E+09 | 0.178465E+09 | 60075240.38 | 0.326290E+09 | 63979473.96 |
June | 0.244543E+09 | 0.190855E+09 | 53688139.83 | 0.350027E+09 | 43299174.66 |
July | 0.218223E+09 | 0.158557E+09 | 59665486.08 | 0.315809E+09 | 35972962.09 |
August | 0.203691E+09 | 0.147963E+09 | 55728522.84 | 0.289043E+09 | 44511505.97 |
September | 0.179231E+09 | 0.134579E+09 | 44651910.81 | 0.248903E+09 | 64857992.83 |
October | 0.137791E+09 | 0.100024E+09 | 37767659.23 | 0.178060E+09 | 82302525.68 |
November | 0.102300E+09 | 75365277.46 | 26934609.64 | 0.122060E+09 | 97554748.00 |
December | 85250293.31 | 55742840.25 | 29507453.06 | 95177787.14 | 0.112341E+09 |
Annual Sum or Average | 0.199216E+10 | 0.146033E+10 | 0.531828E+09 | 0.266853E+10 | 0.882251E+09 |
Minimum of Months | 85250293.31 | 55742840.25 | 26934609.64 | 95177787.14 | 35972962.09 |
Maximum of Months | 0.244543E+09 | 0.190855E+09 | 60075240.38 | 0.350027E+09 | 0.112341E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92684169.41 | 64238604.35 | 28445565.07 | 0.110325E+09 | 96815161.97 |
February | 0.109342E+09 | 77090334.85 | 32251546.97 | 0.135348E+09 | 82473852.86 |
March | 0.171920E+09 | 0.121831E+09 | 50089049.27 | 0.221378E+09 | 86266885.54 |
April | 0.208640E+09 | 0.155618E+09 | 53022776.81 | 0.276108E+09 | 71876463.78 |
May | 0.238541E+09 | 0.178465E+09 | 60075240.38 | 0.326290E+09 | 63979473.96 |
June | 0.244543E+09 | 0.190855E+09 | 53688139.83 | 0.350027E+09 | 43299174.66 |
July | 0.218223E+09 | 0.158557E+09 | 59665486.08 | 0.315809E+09 | 35972962.09 |
August | 0.203691E+09 | 0.147963E+09 | 55728522.84 | 0.289043E+09 | 44511505.97 |
September | 0.179231E+09 | 0.134579E+09 | 44651910.81 | 0.248903E+09 | 64857992.83 |
October | 0.137791E+09 | 0.100024E+09 | 37767659.23 | 0.178060E+09 | 82302525.68 |
November | 0.102300E+09 | 75365277.46 | 26934609.64 | 0.122060E+09 | 97554748.00 |
December | 85250293.31 | 55742840.25 | 29507453.06 | 95177787.14 | 0.112341E+09 |
Annual Sum or Average | 0.199216E+10 | 0.146033E+10 | 0.531828E+09 | 0.266853E+10 | 0.882251E+09 |
Minimum of Months | 85250293.31 | 55742840.25 | 26934609.64 | 95177787.14 | 35972962.09 |
Maximum of Months | 0.244543E+09 | 0.190855E+09 | 60075240.38 | 0.350027E+09 | 0.112341E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92684169.41 | 64238604.35 | 28445565.07 | 0.110325E+09 | 96815161.97 |
February | 0.109342E+09 | 77090334.85 | 32251546.97 | 0.135348E+09 | 82473852.86 |
March | 0.171920E+09 | 0.121831E+09 | 50089049.27 | 0.221378E+09 | 86266885.54 |
April | 0.208640E+09 | 0.155618E+09 | 53022776.81 | 0.276108E+09 | 71876463.78 |
May | 0.238541E+09 | 0.178465E+09 | 60075240.38 | 0.326290E+09 | 63979473.96 |
June | 0.244543E+09 | 0.190855E+09 | 53688139.83 | 0.350027E+09 | 43299174.66 |
July | 0.218223E+09 | 0.158557E+09 | 59665486.08 | 0.315809E+09 | 35972962.09 |
August | 0.203691E+09 | 0.147963E+09 | 55728522.84 | 0.289043E+09 | 44511505.97 |
September | 0.179231E+09 | 0.134579E+09 | 44651910.81 | 0.248903E+09 | 64857992.83 |
October | 0.137791E+09 | 0.100024E+09 | 37767659.23 | 0.178060E+09 | 82302525.68 |
November | 0.102300E+09 | 75365277.46 | 26934609.64 | 0.122060E+09 | 97554748.00 |
December | 85250293.31 | 55742840.25 | 29507453.06 | 95177787.14 | 0.112341E+09 |
Annual Sum or Average | 0.199216E+10 | 0.146033E+10 | 0.531828E+09 | 0.266853E+10 | 0.882251E+09 |
Minimum of Months | 85250293.31 | 55742840.25 | 26934609.64 | 95177787.14 | 35972962.09 |
Maximum of Months | 0.244543E+09 | 0.190855E+09 | 60075240.38 | 0.350027E+09 | 0.112341E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92684169.41 | 64238604.35 | 28445565.07 | 0.110325E+09 | 96815161.97 |
February | 0.109342E+09 | 77090334.85 | 32251546.97 | 0.135348E+09 | 82473852.86 |
March | 0.171920E+09 | 0.121831E+09 | 50089049.27 | 0.221378E+09 | 86266885.54 |
April | 0.208640E+09 | 0.155618E+09 | 53022776.81 | 0.276108E+09 | 71876463.78 |
May | 0.238541E+09 | 0.178465E+09 | 60075240.38 | 0.326290E+09 | 63979473.96 |
June | 0.244543E+09 | 0.190855E+09 | 53688139.83 | 0.350027E+09 | 43299174.66 |
July | 0.218223E+09 | 0.158557E+09 | 59665486.08 | 0.315809E+09 | 35972962.09 |
August | 0.203691E+09 | 0.147963E+09 | 55728522.84 | 0.289043E+09 | 44511505.97 |
September | 0.179231E+09 | 0.134579E+09 | 44651910.81 | 0.248903E+09 | 64857992.83 |
October | 0.137791E+09 | 0.100024E+09 | 37767659.23 | 0.178060E+09 | 82302525.68 |
November | 0.102300E+09 | 75365277.46 | 26934609.64 | 0.122060E+09 | 97554748.00 |
December | 85250293.31 | 55742840.25 | 29507453.06 | 95177787.14 | 0.112341E+09 |
Annual Sum or Average | 0.199216E+10 | 0.146033E+10 | 0.531828E+09 | 0.266853E+10 | 0.882251E+09 |
Minimum of Months | 85250293.31 | 55742840.25 | 26934609.64 | 95177787.14 | 35972962.09 |
Maximum of Months | 0.244543E+09 | 0.190855E+09 | 60075240.38 | 0.350027E+09 | 0.112341E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92684169.41 | 64238604.35 | 28445565.07 | 0.110325E+09 | 96815161.97 |
February | 0.109342E+09 | 77090334.85 | 32251546.97 | 0.135348E+09 | 82473852.86 |
March | 0.171920E+09 | 0.121831E+09 | 50089049.27 | 0.221378E+09 | 86266885.54 |
April | 0.208640E+09 | 0.155618E+09 | 53022776.81 | 0.276108E+09 | 71876463.78 |
May | 0.238541E+09 | 0.178465E+09 | 60075240.38 | 0.326290E+09 | 63979473.96 |
June | 0.244543E+09 | 0.190855E+09 | 53688139.83 | 0.350027E+09 | 43299174.66 |
July | 0.218223E+09 | 0.158557E+09 | 59665486.08 | 0.315809E+09 | 35972962.09 |
August | 0.203691E+09 | 0.147963E+09 | 55728522.84 | 0.289043E+09 | 44511505.97 |
September | 0.179231E+09 | 0.134579E+09 | 44651910.81 | 0.248903E+09 | 64857992.83 |
October | 0.137791E+09 | 0.100024E+09 | 37767659.23 | 0.178060E+09 | 82302525.68 |
November | 0.102300E+09 | 75365277.46 | 26934609.64 | 0.122060E+09 | 97554748.00 |
December | 85250293.31 | 55742840.25 | 29507453.06 | 95177787.14 | 0.112341E+09 |
Annual Sum or Average | 0.199216E+10 | 0.146033E+10 | 0.531828E+09 | 0.266853E+10 | 0.882251E+09 |
Minimum of Months | 85250293.31 | 55742840.25 | 26934609.64 | 95177787.14 | 35972962.09 |
Maximum of Months | 0.244543E+09 | 0.190855E+09 | 60075240.38 | 0.350027E+09 | 0.112341E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92684169.41 | 64238604.35 | 28445565.07 | 0.110325E+09 | 96815161.97 |
February | 0.109342E+09 | 77090334.85 | 32251546.97 | 0.135348E+09 | 82473852.86 |
March | 0.171920E+09 | 0.121831E+09 | 50089049.27 | 0.221378E+09 | 86266885.54 |
April | 0.208640E+09 | 0.155618E+09 | 53022776.81 | 0.276108E+09 | 71876463.78 |
May | 0.238541E+09 | 0.178465E+09 | 60075240.38 | 0.326290E+09 | 63979473.96 |
June | 0.244543E+09 | 0.190855E+09 | 53688139.83 | 0.350027E+09 | 43299174.66 |
July | 0.218223E+09 | 0.158557E+09 | 59665486.08 | 0.315809E+09 | 35972962.09 |
August | 0.203691E+09 | 0.147963E+09 | 55728522.84 | 0.289043E+09 | 44511505.97 |
September | 0.179231E+09 | 0.134579E+09 | 44651910.81 | 0.248903E+09 | 64857992.83 |
October | 0.137791E+09 | 0.100024E+09 | 37767659.23 | 0.178060E+09 | 82302525.68 |
November | 0.102300E+09 | 75365277.46 | 26934609.64 | 0.122060E+09 | 97554748.00 |
December | 85250293.31 | 55742840.25 | 29507453.06 | 95177787.14 | 0.112341E+09 |
Annual Sum or Average | 0.199216E+10 | 0.146033E+10 | 0.531828E+09 | 0.266853E+10 | 0.882251E+09 |
Minimum of Months | 85250293.31 | 55742840.25 | 26934609.64 | 95177787.14 | 35972962.09 |
Maximum of Months | 0.244543E+09 | 0.190855E+09 | 60075240.38 | 0.350027E+09 | 0.112341E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92684169.41 | 64238604.35 | 28445565.07 | 0.110325E+09 | 96815161.97 |
February | 0.109342E+09 | 77090334.85 | 32251546.97 | 0.135348E+09 | 82473852.86 |
March | 0.171920E+09 | 0.121831E+09 | 50089049.27 | 0.221378E+09 | 86266885.54 |
April | 0.208640E+09 | 0.155618E+09 | 53022776.81 | 0.276108E+09 | 71876463.78 |
May | 0.238541E+09 | 0.178465E+09 | 60075240.38 | 0.326290E+09 | 63979473.96 |
June | 0.244543E+09 | 0.190855E+09 | 53688139.83 | 0.350027E+09 | 43299174.66 |
July | 0.218223E+09 | 0.158557E+09 | 59665486.08 | 0.315809E+09 | 35972962.09 |
August | 0.203691E+09 | 0.147963E+09 | 55728522.84 | 0.289043E+09 | 44511505.97 |
September | 0.179231E+09 | 0.134579E+09 | 44651910.81 | 0.248903E+09 | 64857992.83 |
October | 0.137791E+09 | 0.100024E+09 | 37767659.23 | 0.178060E+09 | 82302525.68 |
November | 0.102300E+09 | 75365277.46 | 26934609.64 | 0.122060E+09 | 97554748.00 |
December | 85250293.31 | 55742840.25 | 29507453.06 | 95177787.14 | 0.112341E+09 |
Annual Sum or Average | 0.199216E+10 | 0.146033E+10 | 0.531828E+09 | 0.266853E+10 | 0.882251E+09 |
Minimum of Months | 85250293.31 | 55742840.25 | 26934609.64 | 95177787.14 | 35972962.09 |
Maximum of Months | 0.244543E+09 | 0.190855E+09 | 60075240.38 | 0.350027E+09 | 0.112341E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92684169.41 | 64238604.35 | 28445565.07 | 0.110325E+09 | 96815161.97 |
February | 0.109342E+09 | 77090334.85 | 32251546.97 | 0.135348E+09 | 82473852.86 |
March | 0.171920E+09 | 0.121831E+09 | 50089049.27 | 0.221378E+09 | 86266885.54 |
April | 0.208640E+09 | 0.155618E+09 | 53022776.81 | 0.276108E+09 | 71876463.78 |
May | 0.238541E+09 | 0.178465E+09 | 60075240.38 | 0.326290E+09 | 63979473.96 |
June | 0.244543E+09 | 0.190855E+09 | 53688139.83 | 0.350027E+09 | 43299174.66 |
July | 0.218223E+09 | 0.158557E+09 | 59665486.08 | 0.315809E+09 | 35972962.09 |
August | 0.203691E+09 | 0.147963E+09 | 55728522.84 | 0.289043E+09 | 44511505.97 |
September | 0.179231E+09 | 0.134579E+09 | 44651910.81 | 0.248903E+09 | 64857992.83 |
October | 0.137791E+09 | 0.100024E+09 | 37767659.23 | 0.178060E+09 | 82302525.68 |
November | 0.102300E+09 | 75365277.46 | 26934609.64 | 0.122060E+09 | 97554748.00 |
December | 85250293.31 | 55742840.25 | 29507453.06 | 95177787.14 | 0.112341E+09 |
Annual Sum or Average | 0.199216E+10 | 0.146033E+10 | 0.531828E+09 | 0.266853E+10 | 0.882251E+09 |
Minimum of Months | 85250293.31 | 55742840.25 | 26934609.64 | 95177787.14 | 35972962.09 |
Maximum of Months | 0.244543E+09 | 0.190855E+09 | 60075240.38 | 0.350027E+09 | 0.112341E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92684169.41 | 64238604.35 | 28445565.07 | 0.110325E+09 | 96815161.97 |
February | 0.109342E+09 | 77090334.85 | 32251546.97 | 0.135348E+09 | 82473852.86 |
March | 0.171920E+09 | 0.121831E+09 | 50089049.27 | 0.221378E+09 | 86266885.54 |
April | 0.208640E+09 | 0.155618E+09 | 53022776.81 | 0.276108E+09 | 71876463.78 |
May | 0.238541E+09 | 0.178465E+09 | 60075240.38 | 0.326290E+09 | 63979473.96 |
June | 0.244543E+09 | 0.190855E+09 | 53688139.83 | 0.350027E+09 | 43299174.66 |
July | 0.218223E+09 | 0.158557E+09 | 59665486.08 | 0.315809E+09 | 35972962.09 |
August | 0.203691E+09 | 0.147963E+09 | 55728522.84 | 0.289043E+09 | 44511505.97 |
September | 0.179231E+09 | 0.134579E+09 | 44651910.81 | 0.248903E+09 | 64857992.83 |
October | 0.137791E+09 | 0.100024E+09 | 37767659.23 | 0.178060E+09 | 82302525.68 |
November | 0.102300E+09 | 75365277.46 | 26934609.64 | 0.122060E+09 | 97554748.00 |
December | 85250293.31 | 55742840.25 | 29507453.06 | 95177787.14 | 0.112341E+09 |
Annual Sum or Average | 0.199216E+10 | 0.146033E+10 | 0.531828E+09 | 0.266853E+10 | 0.882251E+09 |
Minimum of Months | 85250293.31 | 55742840.25 | 26934609.64 | 95177787.14 | 35972962.09 |
Maximum of Months | 0.244543E+09 | 0.190855E+09 | 60075240.38 | 0.350027E+09 | 0.112341E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188650E+09 | 0.132350E+09 | 56300176.49 | 0.244871E+09 | 0.112755E+09 |
February | 0.217996E+09 | 0.154163E+09 | 63833071.41 | 0.288322E+09 | 97357999.02 |
March | 0.336955E+09 | 0.237818E+09 | 99137503.77 | 0.448583E+09 | 0.112213E+09 |
April | 0.405613E+09 | 0.300669E+09 | 0.104944E+09 | 0.545401E+09 | 0.100399E+09 |
May | 0.462114E+09 | 0.343211E+09 | 0.118902E+09 | 0.624018E+09 | 0.103297E+09 |
June | 0.472216E+09 | 0.365955E+09 | 0.106261E+09 | 0.650808E+09 | 83808863.13 |
July | 0.422318E+09 | 0.304227E+09 | 0.118091E+09 | 0.586619E+09 | 70674237.85 |
August | 0.394892E+09 | 0.284593E+09 | 0.110299E+09 | 0.542122E+09 | 83157860.15 |
September | 0.349872E+09 | 0.261496E+09 | 88376182.82 | 0.475848E+09 | 0.105624E+09 |
October | 0.272746E+09 | 0.197996E+09 | 74750699.27 | 0.357885E+09 | 0.117714E+09 |
November | 0.206920E+09 | 0.153611E+09 | 53309655.57 | 0.262294E+09 | 0.125814E+09 |
December | 0.174967E+09 | 0.116566E+09 | 58401891.86 | 0.221930E+09 | 0.125515E+09 |
Annual Sum or Average | 0.390526E+10 | 0.285265E+10 | 0.105261E+10 | 0.524870E+10 | 0.123833E+10 |
Minimum of Months | 0.174967E+09 | 0.116566E+09 | 53309655.57 | 0.221930E+09 | 70674237.85 |
Maximum of Months | 0.472216E+09 | 0.365955E+09 | 0.118902E+09 | 0.650808E+09 | 0.125814E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 181.22 | 287.90 | 167.34 | 78.16 | 89.18 | 0.00 | 0.00 |
February | 228.46 | 254.10 | 191.08 | 82.79 | 108.28 | 0.00 | 0.00 |
March | 339.85 | 228.11 | 258.75 | 114.09 | 144.65 | 0.00 | 0.00 |
April | 436.89 | 164.50 | 297.52 | 132.40 | 165.12 | 0.00 | 0.00 |
May | 530.37 | 120.77 | 326.10 | 145.29 | 180.81 | 0.00 | 0.00 |
June | 599.28 | 73.32 | 323.49 | 146.14 | 177.35 | 0.00 | 0.00 |
July | 532.27 | 65.09 | 289.57 | 119.22 | 170.35 | 0.00 | 0.00 |
August | 478.69 | 86.28 | 272.77 | 113.54 | 159.22 | 0.00 | 0.00 |
September | 448.96 | 154.38 | 271.49 | 126.15 | 145.34 | 0.00 | 0.00 |
October | 324.46 | 212.15 | 231.82 | 113.27 | 118.55 | 0.00 | 0.00 |
November | 222.02 | 285.40 | 192.31 | 98.17 | 94.14 | 0.00 | 0.00 |
December | 158.80 | 329.46 | 159.81 | 71.35 | 88.46 | 0.00 | 0.00 |
Annual Sum or Average | 374.04 | 188.13 | 248.73 | 111.80 | 136.93 | 0.00 | 0.00 |
Minimum of Months | 158.80 | 65.09 | 159.81 | 71.35 | 88.46 | 0.00 | 0.00 |
Maximum of Months | 599.28 | 329.46 | 326.10 | 146.14 | 180.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 576.67 | 506.05 | 484.46 | 335.78 | 148.69 | 0.00 | 0.00 |
February | 783.27 | 477.28 | 632.77 | 446.12 | 186.64 | 0.00 | 0.00 |
March | 1157.14 | 450.92 | 898.63 | 636.81 | 261.82 | 0.00 | 0.00 |
April | 1491.32 | 388.22 | 1126.92 | 840.53 | 286.39 | 0.00 | 0.00 |
May | 1705.52 | 334.42 | 1246.85 | 932.84 | 314.01 | 0.00 | 0.00 |
June | 1890.58 | 233.87 | 1320.83 | 1030.85 | 289.98 | 0.00 | 0.00 |
July | 1650.73 | 188.03 | 1140.65 | 828.78 | 311.87 | 0.00 | 0.00 |
August | 1510.83 | 232.66 | 1064.69 | 773.40 | 291.29 | 0.00 | 0.00 |
September | 1344.39 | 350.31 | 968.07 | 726.89 | 241.18 | 0.00 | 0.00 |
October | 930.72 | 430.20 | 720.24 | 522.82 | 197.41 | 0.00 | 0.00 |
November | 659.28 | 526.92 | 552.55 | 407.07 | 145.48 | 0.00 | 0.00 |
December | 497.49 | 587.20 | 445.60 | 291.37 | 154.24 | 0.00 | 0.00 |
Annual Sum or Average | 1184.66 | 391.66 | 884.39 | 648.29 | 236.10 | 0.00 | 0.00 |
Minimum of Months | 497.49 | 188.03 | 445.60 | 291.37 | 145.48 | 0.00 | 0.00 |
Maximum of Months | 1890.58 | 587.20 | 1320.83 | 1030.85 | 314.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 11546.25 | 6472.77 | 2253.88 | 1581.24 | 672.64 | 0.00 | 0.00 |
February | 14912.73 | 5656.83 | 2883.55 | 2039.20 | 844.35 | 0.00 | 0.00 |
March | 21882.97 | 4864.71 | 4025.75 | 2841.31 | 1184.44 | 0.00 | 0.00 |
April | 26823.05 | 3811.36 | 5007.57 | 3711.96 | 1295.61 | 0.00 | 0.00 |
May | 35264.95 | 4326.09 | 5521.07 | 4100.49 | 1420.58 | 0.00 | 0.00 |
June | 45080.06 | 5569.08 | 5829.83 | 4517.97 | 1311.86 | 0.00 | 0.00 |
July | 38465.93 | 4601.17 | 5045.61 | 3634.73 | 1410.89 | 0.00 | 0.00 |
August | 34885.54 | 5005.79 | 4717.94 | 3400.15 | 1317.79 | 0.00 | 0.00 |
September | 30132.67 | 5121.85 | 4319.41 | 3228.35 | 1091.06 | 0.00 | 0.00 |
October | 16516.83 | 4507.85 | 3258.62 | 2365.54 | 893.08 | 0.00 | 0.00 |
November | 13260.09 | 5471.87 | 2554.57 | 1896.43 | 658.14 | 0.00 | 0.00 |
December | 10427.17 | 7767.32 | 2090.41 | 1392.66 | 697.75 | 0.00 | 0.00 |
Annual Sum or Average | 24972.91 | 5264.47 | 3962.72 | 2894.63 | 1068.09 | 0.00 | 0.00 |
Minimum of Months | 10427.17 | 3811.36 | 2090.41 | 1392.66 | 658.14 | 0.00 | 0.00 |
Maximum of Months | 45080.06 | 7767.32 | 5829.83 | 4517.97 | 1420.58 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.485368E+09 | 0.771124E+09 | 0.448210E+09 | 0.209347E+09 | 0.238864E+09 | 0.00 | 0.00 |
February | 0.552691E+09 | 0.614722E+09 | 0.462257E+09 | 0.200295E+09 | 0.261962E+09 | 0.00 | 0.00 |
March | 0.910241E+09 | 0.610969E+09 | 0.693023E+09 | 0.305591E+09 | 0.387432E+09 | 0.00 | 0.00 |
April | 0.113242E+10 | 0.426396E+09 | 0.771173E+09 | 0.343184E+09 | 0.427989E+09 | 0.00 | 0.00 |
May | 0.142055E+10 | 0.323463E+09 | 0.873431E+09 | 0.389157E+09 | 0.484274E+09 | 0.00 | 0.00 |
June | 0.155334E+10 | 0.190052E+09 | 0.838479E+09 | 0.378791E+09 | 0.459688E+09 | 0.00 | 0.00 |
July | 0.142563E+10 | 0.174334E+09 | 0.775583E+09 | 0.319310E+09 | 0.456273E+09 | 0.00 | 0.00 |
August | 0.128211E+10 | 0.231080E+09 | 0.730575E+09 | 0.304112E+09 | 0.426463E+09 | 0.00 | 0.00 |
September | 0.116371E+10 | 0.400146E+09 | 0.703700E+09 | 0.326986E+09 | 0.376714E+09 | 0.00 | 0.00 |
October | 0.869022E+09 | 0.568235E+09 | 0.620905E+09 | 0.303374E+09 | 0.317531E+09 | 0.00 | 0.00 |
November | 0.575464E+09 | 0.739767E+09 | 0.498469E+09 | 0.254449E+09 | 0.244021E+09 | 0.00 | 0.00 |
December | 0.425323E+09 | 0.882429E+09 | 0.428047E+09 | 0.191112E+09 | 0.236935E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.117959E+11 | 0.593272E+10 | 0.784385E+10 | 0.352571E+10 | 0.431815E+10 | 0.00 | 0.00 |
Minimum of Months | 0.425323E+09 | 0.174334E+09 | 0.428047E+09 | 0.191112E+09 | 0.236935E+09 | 0.00 | 0.00 |
Maximum of Months | 0.155334E+10 | 0.882429E+09 | 0.873431E+09 | 0.389157E+09 | 0.484274E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.154455E+10 | 0.135541E+10 | 0.129758E+10 | 0.899340E+09 | 0.398238E+09 | 0.00 | 0.00 |
February | 0.189488E+10 | 0.115463E+10 | 0.153079E+10 | 0.107926E+10 | 0.451522E+09 | 0.00 | 0.00 |
March | 0.309929E+10 | 0.120774E+10 | 0.240689E+10 | 0.170564E+10 | 0.701247E+09 | 0.00 | 0.00 |
April | 0.386551E+10 | 0.100627E+10 | 0.292097E+10 | 0.217865E+10 | 0.742319E+09 | 0.00 | 0.00 |
May | 0.456806E+10 | 0.895713E+09 | 0.333957E+10 | 0.249852E+10 | 0.841053E+09 | 0.00 | 0.00 |
June | 0.490037E+10 | 0.606188E+09 | 0.342360E+10 | 0.267196E+10 | 0.751634E+09 | 0.00 | 0.00 |
July | 0.442132E+10 | 0.503621E+09 | 0.305512E+10 | 0.221980E+10 | 0.835317E+09 | 0.00 | 0.00 |
August | 0.404660E+10 | 0.623161E+09 | 0.285168E+10 | 0.207148E+10 | 0.780199E+09 | 0.00 | 0.00 |
September | 0.348465E+10 | 0.908012E+09 | 0.250923E+10 | 0.188410E+10 | 0.625127E+09 | 0.00 | 0.00 |
October | 0.249284E+10 | 0.115224E+10 | 0.192908E+10 | 0.140033E+10 | 0.528747E+09 | 0.00 | 0.00 |
November | 0.170884E+10 | 0.136577E+10 | 0.143220E+10 | 0.105511E+10 | 0.377085E+09 | 0.00 | 0.00 |
December | 0.133249E+10 | 0.157277E+10 | 0.119350E+10 | 0.780400E+09 | 0.413104E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.373594E+11 | 0.123515E+11 | 0.278902E+11 | 0.204446E+11 | 0.744559E+10 | 0.00 | 0.00 |
Minimum of Months | 0.133249E+10 | 0.503621E+09 | 0.119350E+10 | 0.780400E+09 | 0.377085E+09 | 0.00 | 0.00 |
Maximum of Months | 0.490037E+10 | 0.157277E+10 | 0.342360E+10 | 0.267196E+10 | 0.841053E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.309255E+11 | 0.173367E+11 | 0.603680E+10 | 0.423519E+10 | 0.180161E+10 | 0.00 | 0.00 |
February | 0.360769E+11 | 0.136850E+11 | 0.697589E+10 | 0.493323E+10 | 0.204266E+10 | 0.00 | 0.00 |
March | 0.586113E+11 | 0.130296E+11 | 0.107826E+11 | 0.761016E+10 | 0.317240E+10 | 0.00 | 0.00 |
April | 0.695253E+11 | 0.987905E+10 | 0.129796E+11 | 0.962141E+10 | 0.335821E+10 | 0.00 | 0.00 |
May | 0.944536E+11 | 0.115870E+11 | 0.147876E+11 | 0.109828E+11 | 0.380488E+10 | 0.00 | 0.00 |
June | 0.116848E+12 | 0.144351E+11 | 0.151109E+11 | 0.117106E+11 | 0.340035E+10 | 0.00 | 0.00 |
July | 0.103027E+12 | 0.123238E+11 | 0.135142E+11 | 0.973525E+10 | 0.377893E+10 | 0.00 | 0.00 |
August | 0.934374E+11 | 0.134075E+11 | 0.126365E+11 | 0.910696E+10 | 0.352958E+10 | 0.00 | 0.00 |
September | 0.781039E+11 | 0.132758E+11 | 0.111959E+11 | 0.836788E+10 | 0.282804E+10 | 0.00 | 0.00 |
October | 0.442387E+11 | 0.120738E+11 | 0.872788E+10 | 0.633586E+10 | 0.239202E+10 | 0.00 | 0.00 |
November | 0.343701E+11 | 0.141831E+11 | 0.662145E+10 | 0.491554E+10 | 0.170591E+10 | 0.00 | 0.00 |
December | 0.279281E+11 | 0.208040E+11 | 0.559896E+10 | 0.373010E+10 | 0.186886E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.787546E+12 | 0.166020E+12 | 0.124968E+12 | 0.912849E+11 | 0.336834E+11 | 0.00 | 0.00 |
Minimum of Months | 0.279281E+11 | 0.987905E+10 | 0.559896E+10 | 0.373010E+10 | 0.170591E+10 | 0.00 | 0.00 |
Maximum of Months | 0.116848E+12 | 0.208040E+11 | 0.151109E+11 | 0.117106E+11 | 0.380488E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.868694E+09 | -782882422.6 | 0.00 | 0.00 | 744.00 | 0.00 | -85811254.2 | 59.00 | 0.00 | 0.00 |
February | 0.795034E+09 | -718603889.7 | 0.00 | 0.00 | 672.00 | 0.00 | -76430332.1 | 59.00 | 0.00 | 0.00 |
March | 0.890665E+09 | -808956435.6 | 0.00 | 0.00 | 744.00 | 0.00 | -81708124.1 | 59.00 | 0.00 | 0.00 |
April | 0.774416E+09 | -701668287.5 | 0.00 | 0.00 | 720.00 | 0.00 | -72747595.6 | 58.99 | 0.00 | 0.00 |
May | 0.741810E+09 | -670066885.5 | 0.00 | 0.00 | 744.00 | 0.00 | -71743092.0 | 58.99 | 0.00 | 0.00 |
June | 0.682744E+09 | -614639564.9 | 0.00 | 0.00 | 720.00 | 0.00 | -68104486.7 | 58.99 | 0.00 | 0.00 |
July | 0.634618E+09 | -564857833.1 | 0.00 | 0.00 | 744.00 | 0.00 | -69760327.7 | 58.99 | 0.00 | 0.00 |
August | 0.677639E+09 | -607215340.9 | 0.00 | 0.00 | 744.00 | 0.00 | -70423198.6 | 58.99 | 0.00 | 0.00 |
September | 0.663167E+09 | -594569137.2 | 0.00 | 0.00 | 720.00 | 0.00 | -68597521.6 | 58.99 | 0.00 | 0.00 |
October | 0.720212E+09 | -646568545.3 | 0.00 | 0.00 | 744.00 | 0.00 | -73643703.2 | 58.99 | 0.00 | 0.00 |
November | 0.754279E+09 | -676111460.1 | 0.00 | 0.00 | 720.00 | 0.00 | -78167994.8 | 58.99 | 0.00 | 0.00 |
December | 0.839401E+09 | -753469131.6 | 0.00 | 0.00 | 744.00 | 0.00 | -85932146.6 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.904268E+10 | -0.813961E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -903069777.3 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.634618E+09 | -808956435.6 | 0.00 | 0.00 | 672.00 | 0.00 | -85932146.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.890665E+09 | -564857833.1 | 0.00 | 0.00 | 744.00 | 0.00 | -68104486.7 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.80 | 0.50 | 08-JAN-11:00 | 806.52 | 0.00 | 0.00 | 34.33 | 106.04 | 0.00 | 0.00 | 0.00 |
February | 268.33 | 0.78 | 0.50 | 14-FEB-13:30 | 149.66 | 0.00 | 0.00 | 14.00 | 125.76 | 0.00 | 0.00 | 4.33 |
March | 351.83 | 0.75 | 0.50 | 02-MAR-10:00 | 186.39 | 0.00 | 0.00 | 62.50 | 152.12 | 0.00 | 0.00 | 36.67 |
April | 373.83 | 0.73 | 0.50 | 01-APR-10:39 | 195.03 | 0.00 | 0.00 | 51.33 | 159.40 | 0.00 | 0.00 | 30.50 |
May | 408.83 | 0.72 | 0.50 | 01-MAY-10:09 | 942.51 | 0.00 | 0.00 | 82.17 | 1533.98 | 0.00 | 0.00 | 53.17 |
June | 398.00 | 0.72 | 0.50 | 01-JUN-10:50 | 3568.84 | 0.00 | 0.00 | 114.67 | 150.67 | 0.00 | 0.00 | 15.17 |
July | 400.17 | 0.72 | 0.50 | 01-JUL-11:30 | 1527.87 | 0.00 | 0.00 | 123.33 | 163.34 | 0.00 | 0.00 | 37.67 |
August | 377.83 | 0.71 | 0.50 | 01-AUG-10:39 | 604.03 | 0.00 | 0.00 | 74.00 | 165.91 | 0.00 | 0.00 | 34.67 |
September | 365.83 | 0.76 | 0.50 | 02-SEP-10:20 | 176.18 | 0.00 | 0.00 | 57.50 | 146.11 | 0.00 | 0.00 | 24.17 |
October | 318.83 | 0.76 | 0.50 | 02-OCT-09:39 | 158.06 | 0.00 | 0.00 | 27.00 | 1134.57 | 0.00 | 0.00 | 46.83 |
November | 295.83 | 0.83 | 0.50 | 02-NOV-10:20 | 116.93 | 0.00 | 0.00 | 1.17 | 98.29 | 0.00 | 0.00 | 0.00 |
December | 289.50 | 0.82 | 0.50 | 01-DEC-11:30 | 124.86 | 0.00 | 0.00 | 0.00 | 104.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4125.67 | 0.75 | 783.60 | 0.00 | 0.00 | 642.00 | 355.34 | 0.00 | 0.00 | 283.17 | ||
Minimum of Months | 268.33 | 0.71 | 0.50 | 116.93 | 0.00 | 0.00 | 0.00 | 98.29 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 408.83 | 0.83 | 0.50 | 3568.84 | 0.00 | 0.00 | 123.33 | 1533.98 | 0.00 | 0.00 | 53.17 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.67 | 0.50 | 01-JAN-09:09 | 153.63 | 10.60 | 0.00 | 60.67 | 1037.21 | 18.39 | 51.83 | 85.17 |
February | 268.33 | 0.65 | 0.50 | 01-FEB-11:09 | 1255.94 | 13.71 | 31.33 | 98.83 | 382.14 | 16.64 | 33.67 | 81.17 |
March | 351.83 | 0.63 | 0.50 | 01-MAR-08:00 | 292.01 | 11.96 | 1.83 | 154.33 | 185.31 | 15.71 | 36.00 | 118.00 |
April | 373.83 | 0.61 | 0.50 | 01-APR-08:39 | 1557.58 | 12.32 | 0.00 | 220.83 | 2868.38 | 18.04 | 90.17 | 169.67 |
May | 408.83 | 0.60 | 0.50 | 01-MAY-07:19 | 245.19 | 12.54 | 0.00 | 252.67 | 1657.41 | 16.50 | 83.00 | 197.83 |
June | 398.00 | 0.60 | 0.50 | 01-JUN-07:40 | 233.02 | 12.39 | 0.00 | 241.83 | 198.75 | 16.38 | 67.50 | 182.17 |
July | 400.17 | 0.61 | 0.50 | 01-JUL-07:40 | 246.29 | 12.45 | 0.00 | 233.83 | 211.08 | 16.40 | 76.00 | 180.00 |
August | 377.83 | 0.60 | 0.50 | 01-AUG-07:49 | 1377.70 | 12.65 | 0.00 | 234.83 | 1418.19 | 16.59 | 75.17 | 180.33 |
September | 365.83 | 0.64 | 0.50 | 01-SEP-09:30 | 210.80 | 11.49 | 0.00 | 155.50 | 177.29 | 15.40 | 39.83 | 115.50 |
October | 318.83 | 0.64 | 0.50 | 01-OCT-09:30 | 855.42 | 11.40 | 0.00 | 139.50 | 159.67 | 15.23 | 32.83 | 76.00 |
November | 295.83 | 0.70 | 0.50 | 01-NOV-12:39 | 143.24 | 10.26 | 0.00 | 50.17 | 121.03 | 14.03 | 2.33 | 26.83 |
December | 289.50 | 0.68 | 0.50 | 01-DEC-10:09 | 153.78 | 10.98 | 0.00 | 64.67 | 968.23 | 17.76 | 46.17 | 81.00 |
Annual Sum or Average | 4125.67 | 0.63 | 560.73 | 11.95 | 33.17 | 1907.67 | 808.61 | 16.41 | 634.50 | 1493.67 | ||
Minimum of Months | 268.33 | 0.60 | 0.50 | 143.24 | 10.26 | 0.00 | 50.17 | 121.03 | 14.03 | 2.33 | 26.83 | |
Maximum of Months | 408.83 | 0.70 | 0.50 | 1557.58 | 13.71 | 31.33 | 252.67 | 2868.38 | 18.39 | 90.17 | 197.83 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.83 | 0.64 | 20-JAN-15:30 | 381.50 | 23.55 | 106.83 | 39.83 | 99.48 | 19.82 | 60.17 | 0.00 |
February | 268.33 | 0.81 | 0.61 | 08-FEB-16:19 | 281.34 | 22.66 | 101.83 | 30.00 | 171.62 | 21.88 | 87.00 | 11.83 |
March | 351.83 | 0.79 | 0.61 | 01-MAR-16:10 | 402.49 | 22.63 | 133.83 | 63.00 | 349.31 | 23.20 | 142.33 | 41.33 |
April | 373.83 | 0.79 | 0.61 | 01-APR-15:09 | 284.24 | 20.92 | 123.17 | 45.17 | 460.98 | 22.04 | 151.33 | 59.50 |
May | 408.83 | 0.78 | 0.61 | 01-MAY-14:00 | 227.50 | 20.20 | 120.00 | 31.50 | 249.80 | 21.71 | 169.00 | 58.67 |
June | 398.00 | 0.78 | 0.61 | 01-JUN-15:00 | 223.48 | 20.11 | 102.50 | 20.83 | 261.08 | 21.61 | 158.17 | 46.17 |
July | 400.17 | 0.78 | 0.61 | 01-JUL-14:00 | 221.10 | 20.07 | 108.00 | 24.00 | 241.76 | 21.55 | 174.67 | 44.67 |
August | 377.83 | 0.79 | 0.61 | 01-AUG-15:09 | 219.29 | 20.18 | 114.67 | 28.00 | 228.14 | 21.63 | 154.33 | 41.67 |
September | 365.83 | 0.80 | 0.61 | 01-SEP-16:10 | 272.68 | 21.04 | 139.17 | 43.67 | 327.99 | 23.11 | 160.83 | 49.00 |
October | 318.83 | 0.80 | 0.61 | 01-OCT-15:09 | 550.28 | 24.06 | 125.33 | 56.17 | 193.05 | 22.84 | 122.33 | 23.00 |
November | 295.83 | 0.83 | 0.61 | 02-NOV-15:20 | 380.87 | 22.85 | 99.17 | 41.00 | 95.05 | 19.54 | 57.67 | 0.00 |
December | 289.50 | 0.83 | 0.65 | 05-DEC-15:39 | 327.35 | 22.97 | 108.00 | 34.67 | 91.63 | 19.48 | 57.83 | 0.00 |
Annual Sum or Average | 4125.67 | 0.80 | 306.59 | 21.59 | 1382.50 | 457.83 | 240.93 | 21.62 | 1495.67 | 375.83 | ||
Minimum of Months | 268.33 | 0.78 | 0.61 | 219.29 | 20.07 | 99.17 | 20.83 | 91.63 | 19.48 | 57.67 | 0.00 | |
Maximum of Months | 408.83 | 0.83 | 0.65 | 550.28 | 24.06 | 139.17 | 63.00 | 460.98 | 23.20 | 174.67 | 59.50 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.273639E+10 | 27881.80 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.192525E+10 | 27881.80 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.111953E+10 | 27881.80 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 50148653.45 | 27881.80 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.743995E+09 | 27881.80 | 06-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.289599E+10 | 27881.80 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.947130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.289599E+10 | 27881.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.462642E+10 | 91353.46 | 28-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.235565E+10 | 91353.46 | 02-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.559307E+09 | 52158.27 | 02-MAR-05:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.531726E+09 | 76421.03 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.665066E+10 | 83765.96 | 31-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147238E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.665066E+10 | 91353.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.249567E+09 | 20826.08 | 28-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103662E+09 | 10891.09 | 03-FEB-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199412E+10 | 34266.04 | 31-DEC-06:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.199412E+10 | 34266.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 3720080.53 | 3720080.53 | 425.25 | 21-FEB-16:30 | 425.25 | 0.00 |
March | 0.00 | 0.00 | 0.154224E+09 | 0.154224E+09 | 3245.39 | 21-MAR-16:00 | 3245.39 | 0.00 |
April | 0.00 | 0.00 | 0.238977E+10 | 0.237493E+10 | 19865.93 | 20-APR-05:05 | 19865.93 | 0.00 |
May | 0.00 | 0.00 | 0.618882E+10 | 0.596572E+10 | 21524.26 | 23-MAY-05:01 | 16822.07 | 0.00 |
June | 0.00 | 0.00 | 0.933454E+10 | 0.882123E+10 | 22330.33 | 28-JUN-05:02 | 13598.84 | 0.00 |
July | 0.00 | 0.00 | 0.109370E+11 | 0.871802E+10 | 25642.46 | 22-JUL-05:01 | 10975.82 | 0.00 |
August | 0.00 | 0.00 | 0.101296E+11 | 0.851347E+10 | 24769.91 | 03-AUG-05:01 | 13801.07 | 0.00 |
September | 0.00 | 0.00 | 0.813488E+10 | 0.689891E+10 | 24189.06 | 22-SEP-05:01 | 12231.96 | 0.00 |
October | 0.00 | 0.00 | 0.313287E+10 | 0.277155E+10 | 22658.79 | 04-OCT-05:02 | 12451.46 | 0.00 |
November | 0.00 | 0.00 | 0.177017E+09 | 0.174809E+09 | 4714.65 | 03-NOV-16:00 | 4714.65 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.505824E+11 | 0.443966E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109370E+11 | 0.882123E+10 | 25642.46 | 19865.93 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.197149E+10 | 0.196991E+10 | 63160.00 | 30-APR-10:25 | 63160.00 | 0.00 |
May | 0.00 | 0.00 | 0.124614E+11 | 0.121161E+11 | 70505.63 | 28-MAY-08:55 | 50189.17 | 0.00 |
June | 0.00 | 0.00 | 0.259986E+11 | 0.251100E+11 | 73587.89 | 19-JUN-18:03 | 47021.83 | 0.00 |
July | 0.00 | 0.00 | 0.295014E+11 | 0.247827E+11 | 79298.09 | 21-JUL-20:55 | 38307.28 | 0.00 |
August | 0.00 | 0.00 | 0.242656E+11 | 0.215192E+11 | 75432.76 | 03-AUG-00:05 | 43935.53 | 0.00 |
September | 0.00 | 0.00 | 0.170982E+11 | 0.148797E+11 | 74193.40 | 03-SEP-08:42 | 45833.48 | 0.00 |
October | 0.00 | 0.00 | 0.291386E+10 | 0.254963E+10 | 70082.13 | 04-OCT-19:35 | 55430.66 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.114211E+12 | 0.102927E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.295014E+11 | 0.251100E+11 | 79298.09 | 63160.00 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 4465258.11 | 0.00 | 224.93 | 27-JAN-06:39 | 0.09 |
February | 4569370.34 | 0.00 | 224.93 | 02-FEB-04:20 | 0.09 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 36394295.71 | 0.01 | 224.93 | 22-DEC-05:50 | 0.09 |
Annual Sum or Average | 45428924.16 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36394295.71 | 0.01 | 224.93 | 0.09 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.647543E+09 | 0.28 | 1395.50 | 02-JAN-06:01 | 1.04 |
February | 0.576435E+09 | 0.28 | 1395.50 | 01-FEB-06:01 | 1.05 |
March | 0.638060E+09 | 0.28 | 1395.50 | 01-MAR-06:01 | 1.05 |
April | 0.555222E+09 | 0.25 | 1395.50 | 01-APR-05:02 | 1.05 |
May | 0.589017E+09 | 0.25 | 1395.50 | 09-MAY-05:02 | 1.05 |
June | 0.645147E+09 | 0.28 | 1395.50 | 01-JUN-05:01 | 1.05 |
July | 0.633038E+09 | 0.27 | 1395.50 | 01-JUL-05:01 | 1.04 |
August | 0.657594E+09 | 0.28 | 1395.50 | 01-AUG-05:01 | 1.03 |
September | 0.581088E+09 | 0.26 | 1395.50 | 01-SEP-05:01 | 1.03 |
October | 0.557174E+09 | 0.24 | 1395.50 | 02-OCT-05:01 | 1.04 |
November | 0.557234E+09 | 0.25 | 1395.50 | 06-NOV-06:02 | 1.05 |
December | 0.652801E+09 | 0.28 | 1395.50 | 01-DEC-06:01 | 1.05 |
Annual Sum or Average | 0.729035E+10 | 0.27 | |||
Minimum of Months | 0.555222E+09 | 0.24 | 1395.50 | 1.03 | |
Maximum of Months | 0.657594E+09 | 0.28 | 1395.50 | 1.05 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.151759E+10 | 0.40 | 3425.01 | 28-JAN-06:11 | 1.02 |
February | 0.133081E+10 | 0.32 | 3425.01 | 02-FEB-06:01 | 1.02 |
March | 0.148438E+10 | 0.26 | 1955.51 | 02-MAR-05:43 | 1.02 |
April | 0.137088E+10 | 0.24 | 2827.65 | 30-APR-14:33 | 0.92 |
May | 0.155445E+10 | 0.29 | 3425.01 | 19-MAY-17:06 | 1.01 |
June | 0.175901E+10 | 0.37 | 3425.01 | 01-JUN-17:06 | 1.01 |
July | 0.176180E+10 | 0.36 | 3425.01 | 01-JUL-17:06 | 1.00 |
August | 0.176047E+10 | 0.35 | 3425.01 | 01-AUG-17:06 | 1.00 |
September | 0.150112E+10 | 0.28 | 3425.01 | 03-SEP-11:13 | 1.00 |
October | 0.137605E+10 | 0.23 | 3425.01 | 01-OCT-14:33 | 1.01 |
November | 0.132090E+10 | 0.25 | 2865.17 | 28-NOV-06:01 | 1.01 |
December | 0.158954E+10 | 0.45 | 3140.54 | 31-DEC-07:03 | 1.01 |
Annual Sum or Average | 0.183270E+11 | 0.32 | |||
Minimum of Months | 0.132090E+10 | 0.23 | 1955.51 | 0.92 | |
Maximum of Months | 0.176180E+10 | 0.45 | 3425.01 | 1.02 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.647543E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.577385E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.676457E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.115491E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.212461E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.306065E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.330923E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.313120E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.253997E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.130672E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.600599E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.652801E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.197821E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.577385E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.330923E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.151759E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.133081E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.148438E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.190914E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.488498E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.889219E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.944494E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.809300E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.587718E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.212669E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.132090E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.158954E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.484713E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.132090E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.944494E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.647543E+09 | 0.00 | 0.273639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.576435E+09 | 3720080.53 | 0.192525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.638060E+09 | 0.154224E+09 | 0.111953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.555222E+09 | 0.238774E+10 | 50148653.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.589017E+09 | 0.616491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.645147E+09 | 0.927863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.633038E+09 | 0.108360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.657594E+09 | 0.100552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.581088E+09 | 0.809389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.557174E+09 | 0.311996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.557234E+09 | 0.177017E+09 | 0.743995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.652801E+09 | 0.00 | 0.289599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.729035E+10 | 0.502713E+11 | 0.947130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.555222E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.657594E+09 | 0.108360E+11 | 0.289599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.151759E+10 | 0.00 | 0.462642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133081E+10 | 0.00 | 0.235565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148438E+10 | 0.00 | 0.559307E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137088E+10 | 0.195584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155445E+10 | 0.122747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.175901E+10 | 0.255364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176180E+10 | 0.286908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.176047E+10 | 0.236378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150112E+10 | 0.165381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137605E+10 | 0.282562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132090E+10 | 0.00 | 0.531726E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158954E+10 | 0.00 | 0.665066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183270E+11 | 0.111459E+12 | 0.147238E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176180E+10 | 0.286908E+11 | 0.665066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.647543E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.576435E+09 | 0.00 | 0.00 | 0.00 | 950533.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.638060E+09 | 0.00 | 0.00 | 0.00 | 38397043.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.555222E+09 | 0.00 | 0.00 | 0.00 | 0.599688E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.589017E+09 | 0.00 | 0.00 | 0.00 | 0.153559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.645147E+09 | 0.00 | 0.00 | 0.00 | 0.241550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.633038E+09 | 0.00 | 0.00 | 0.00 | 0.267619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.657594E+09 | 0.00 | 0.00 | 0.00 | 0.247360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.581088E+09 | 0.00 | 0.00 | 0.00 | 0.195888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.557174E+09 | 0.00 | 0.00 | 0.00 | 0.749542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.557234E+09 | 0.00 | 0.00 | 0.00 | 43365382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.652801E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.729035E+10 | 0.00 | 0.00 | 0.00 | 0.124917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.555222E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.657594E+09 | 0.00 | 0.00 | 0.00 | 0.267619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.151759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137088E+10 | 0.00 | 0.00 | 0.00 | 0.538265E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155445E+10 | 0.00 | 0.00 | 0.00 | 0.333052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.175901E+10 | 0.00 | 0.00 | 0.00 | 0.713318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176180E+10 | 0.00 | 0.00 | 0.00 | 0.768314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.176047E+10 | 0.00 | 0.00 | 0.00 | 0.633253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150112E+10 | 0.00 | 0.00 | 0.00 | 0.437606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137605E+10 | 0.00 | 0.00 | 0.00 | 0.750637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183270E+11 | 0.00 | 0.00 | 0.00 | 0.301443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176180E+10 | 0.00 | 0.00 | 0.00 | 0.768314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.414004E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.875047E+09 | 0.00 | 0.00 | 0.12 |
February | 0.459697E+09 | 0.00 | 0.00 | 26724.81 | 0.00 | 0.546583E+09 | 61179587.79 | 0.00 | 0.15 |
March | 0.636472E+09 | 0.00 | 0.00 | 400276.07 | 0.00 | 0.222033E+09 | 0.386409E+09 | 0.00 | 0.23 |
April | 0.119269E+09 | 40360139.22 | 0.00 | 3106387.84 | 0.00 | 0.00 | 0.115594E+10 | 0.00 | 0.36 |
May | 3250995.07 | 0.223105E+09 | 0.00 | 4680050.66 | 0.00 | 0.00 | 0.712445E+09 | 0.00 | 0.35 |
June | 89370.72 | 0.573081E+09 | 0.00 | 5381731.85 | 0.00 | 0.00 | 0.159680E+09 | 0.00 | 0.26 |
July | 0.00 | 0.144354E+10 | 0.00 | 2834825.90 | 0.00 | 0.00 | 17533811.99 | 0.00 | 0.26 |
August | 53888.98 | 0.835034E+09 | 0.00 | 4778642.18 | 0.00 | 0.00 | 0.219274E+09 | 0.00 | 0.35 |
September | 989921.33 | 0.627571E+09 | 0.00 | 4684078.18 | 0.00 | 0.00 | 0.437913E+09 | 0.00 | 0.35 |
October | 25058098.06 | 0.126569E+09 | 0.00 | 4590205.67 | 0.00 | 0.00 | 0.188441E+10 | 0.00 | 0.51 |
November | 0.497566E+09 | 0.00 | 0.00 | 1060993.75 | 0.00 | 0.167395E+09 | 0.878088E+09 | 0.00 | 0.27 |
December | 0.474789E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913479E+09 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.263124E+10 | 0.386926E+10 | 0.00 | 31543916.91 | 0.00 | 0.272454E+10 | 0.591287E+10 | 0.00 | 0.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.636472E+09 | 0.144354E+10 | 0.00 | 5381731.85 | 0.00 | 0.913479E+09 | 0.188441E+10 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.308312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251025E+09 | 0.00 | 0.00 | 0.17 |
February | 0.257636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86916121.11 | 0.00 | 0.00 | 0.18 |
March | 0.277742E+10 | 0.00 | 0.00 | 0.00 | 1821998.63 | 36366149.72 | 0.00 | 0.00 | 0.19 |
April | 0.194596E+10 | 42433742.92 | 0.00 | 1571846.25 | 12682672.06 | 0.00 | 0.492083E+09 | 0.00 | 0.22 |
May | 0.461498E+09 | 0.308219E+09 | 0.00 | 7749718.35 | 130236.99 | 0.00 | 0.150297E+10 | 0.00 | 0.33 |
June | 18609390.59 | 0.120067E+10 | 0.00 | 9986254.70 | 3869.71 | 0.00 | 0.118642E+10 | 0.00 | 0.35 |
July | 1725560.30 | 0.232831E+10 | 0.00 | 4820443.48 | 900584.84 | 0.00 | 0.852588E+09 | 0.00 | 0.36 |
August | 79232736.65 | 0.125347E+10 | 0.00 | 9271686.59 | 10638.80 | 0.00 | 0.168320E+10 | 0.00 | 0.40 |
September | 0.189689E+09 | 0.764188E+09 | 0.00 | 9773291.51 | 58209.61 | 0.00 | 0.156671E+10 | 0.00 | 0.37 |
October | 0.203850E+10 | 0.124616E+09 | 0.00 | 2593103.44 | 3851.31 | 0.00 | 0.168866E+10 | 0.00 | 0.29 |
November | 0.304458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22461853.89 | 0.00 | 0.00 | 0.17 |
December | 0.326493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362971E+09 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.194816E+11 | 0.602191E+10 | 0.00 | 45766344.33 | 15612061.95 | 0.759740E+09 | 0.897263E+10 | 0.00 | 0.27 |
Minimum of Months | 1725560.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.326493E+10 | 0.232831E+10 | 0.00 | 9986254.70 | 12682672.06 | 0.362971E+09 | 0.168866E+10 | 0.00 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:42:58
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.630863E+12 | 0.289350E+11 | 0.00 | 0.462319E+10 | 0.366045E+10 |
February | 0.667442E+12 | 0.241258E+11 | 0.00 | 0.373076E+10 | 0.209208E+10 |
March | 0.103375E+13 | 0.320675E+11 | 0.00 | 0.405727E+10 | 0.987729E+09 |
April | 0.115327E+13 | 0.291335E+11 | 0.00 | 0.362342E+10 | 0.552430E+10 |
May | 0.126581E+13 | 0.424742E+11 | 0.00 | 0.217610E+10 | 0.235163E+11 |
June | 0.125422E+13 | 0.565536E+11 | 0.00 | -396638605.8 | 0.448818E+11 |
July | 0.119113E+13 | 0.544662E+11 | 0.00 | -0.291715E+10 | 0.507977E+11 |
August | 0.110841E+13 | 0.535529E+11 | 0.00 | -109329829.9 | 0.432014E+11 |
September | 0.101401E+13 | 0.415100E+11 | 0.00 | 0.829128E+09 | 0.315681E+11 |
October | 0.870760E+12 | 0.332903E+11 | 0.00 | 0.539265E+10 | 0.754691E+10 |
November | 0.665497E+12 | 0.320484E+11 | 0.00 | 0.461115E+10 | 0.842482E+09 |
December | 0.538624E+12 | 0.244981E+11 | 0.00 | 0.501617E+10 | 0.512678E+10 |
Annual Sum or Average | 0.113938E+14 | 0.452656E+12 | 0.00 | 0.306367E+11 | 0.219746E+12 |
Minimum of Months | 0.538624E+12 | 0.241258E+11 | 0.00 | -0.291715E+10 | 0.842482E+09 |
Maximum of Months | 0.126581E+13 | 0.565536E+11 | 0.00 | 0.539265E+10 | 0.507977E+11 |