Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:42
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2023-10-16 10:43:02
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:02
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 491.01 | 101.55 | 101.55 |
Net Site Energy | 491.01 | 101.55 | 101.55 |
Total Source Energy | 1550.13 | 320.60 | 320.60 |
Net Source Energy | 1550.13 | 320.60 | 320.60 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 126.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 80.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 60.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 488.66 | 2.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 2.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 126.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 80.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 61.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 31.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 29.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 22.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 2.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 126.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 80.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 61.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 60.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 22.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 29.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 43.34 | 0.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 101.06 | 0.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 29.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 43.34 | 0.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 101.06 | 0.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 488.659 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 488.659 | 100.00 |
Total On-Site and Utility Electric Sources | 488.659 | 100.00 |
Total Electricity End Uses | 488.659 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 2.50 |
Time Setpoint Not Met During Occupied Cooling | 55.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2807.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:02
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:42 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 119.93 |
Skylight-Roof Ratio [%] | 2.61 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 6.9682 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 7.4271 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.5521 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8362 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8362 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 6.9682 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 7.4271 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.5521 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.8362 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.8362 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.8362 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:02
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 06-JUN-15:39 | 03-JAN-06:10 | - | - | - | - | - | - | - | - | - | - | 15-MAR-11:20 |
Heating | 0.00 | 28261.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 24910.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4838.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5731.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1570.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 47085.63 | 28261.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 28261.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 24910.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 4838.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 3426.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1570.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:02
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 400.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 256.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 195.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 191.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 71.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1547.58 | 2.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 82.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 52.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 39.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 320.07 | 0.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 82.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 52.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 39.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 320.07 | 0.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:02
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.19 |
ZONE2 FINE STORAGE DIRECT AIR | 3.43 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 0.976836 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 0.976836 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 38969.50 |
PSZ-OFFICE HEATING COIL | 28386.52 |
PSZ-FINE STORAGE HEATING COIL | 103401.81 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 37723.57 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.19 | 1.19 | 1.19 | 1.19 | 1.19 | 1.19 | 1.00 | 1.000000 | 1.19 |
PSZ-FINE STORAGE | 3.43 | 3.43 | 3.43 | 3.43 | 3.43 | 3.43 | 1.00 | 1.000000 | 3.43 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.19 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 3.43 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.19 | 1315.83 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.43 | 3666.07 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.19 | 1.19 | 1.19 | 0.784394 | 24430.85 | 28386.52 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 3.43 | 3.43 | 3.43 | 2.26 | 84462.65 | 103401.81 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.19 | 0.594238 | 0.792320 | 24430.85 | 12215.42 | 0.765060 | 0.765060 |
PSZ-FINE STORAGE COOLING COIL | 3.43 | 1.71 | 2.28 | 84462.65 | 42231.32 | 0.703870 | 0.703870 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:02
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:02
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:02
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 6.968 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 15.042 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 7.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.427 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.552 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 6.111 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1650.627 | 6.968 | 129.474 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1650.627 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 10348.979 | 7.427 | 344.966 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10348.979 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 11383.888 | 3.552 | 164.984 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11383.888 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2405 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.7173 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.6534 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 2.825 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 2.825 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.158 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.394 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.431 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2546 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2546 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.77015739E-08 | 0.38457199E-13 | 0.23136523E-13 | 0.0000000 |
2 | 1 | -5.2160498 | 0.48395528E-04 | -0.66612159E-04 | 0.14765390E-08 |
3 | 0 | 5.4565497 | 0.24045158 | 0.24056658 | |
4 | 2 | 0.53311453E-11 | 0.59398160E-16 | 0.15345153E-15 | 0.0000000 |
5 | 1 | -5.2159564 | 0.46378490E-04 | -0.22332804E-04 | 0.68713370E-11 |
6 | 0 | 5.9333026 | 0.71729982 | 0.71736853 | |
7 | 4 | 0.74747876E-12 | 0.20825084E-15 | -0.25659737E-14 | 0.12362927E-15 |
8 | 3 | -0.37328678E-03 | 0.45238042E-06 | -0.54038165E-04 | 0.14344535E-12 |
9 | 2 | 1.7123825 | 0.10013958E-01 | 1.1198054 | -0.71564441E-04 |
10 | 1 | -7.1648294 | 0.26145347 | -16.966117 | 0.32817431 |
11 | 0 | 5.8918369 | 0.16754891 | 16.285382 | |
12 | 4 | 0.33466332E-12 | 0.89461943E-14 | -0.12859024E-13 | 0.20877214E-15 |
13 | 3 | -0.22871403E-03 | 0.15053116E-05 | -0.31975464E-04 | 0.68322840E-13 |
14 | 2 | 1.3386772 | 0.41030944E-01 | 0.83718830 | -0.43809927E-04 |
15 | 1 | -7.7424045 | 1.2165027 | -15.097018 | 0.25560053 |
16 | 0 | 8.5066984 | 0.84520726 | 16.362604 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.12859024E-13 | 0.89461943E-14 | 0.33466332E-12 | 0.20877214E-15 |
85 | 3 | -0.31975464E-04 | 0.15053116E-05 | -0.22871403E-03 | 0.68322840E-13 |
86 | 2 | 0.83718830 | 0.41030944E-01 | 1.3386772 | -0.43809927E-04 |
87 | 1 | -15.097018 | 1.2165027 | -7.7424045 | 0.25560053 |
88 | 0 | 16.362604 | 0.84520726 | 8.5066984 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.503_SHGC_SOUTH_0.229 | 34 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.230 | ||
2 | NONRESWINDOW_U_0.503_SHGC_NORTH_0.229 | 35 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.230 | ||
3 | NONRESWINDOW_U_0.503_SHGC_EAST_0.229 | 36 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.230 | ||
4 | NONRESWINDOW_U_0.503_SHGC_WEST_0.229 | 37 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.230 | ||
5 | SKYLIGHT_U_0.7_SHGC_0.3 | 38 | 1 | VerySmooth | 3.979 | 3.979 | 1.000 | 0.303 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.93472E-002 | 0.14029 | 0.63161 | 0.63161 | 0.22900 | 0.16611 | 0.25065 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.93472E-002 | 0.14029 | 0.63161 | 0.63161 | 0.22900 | 0.16611 | 0.25065 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.93472E-002 | 0.14029 | 0.63161 | 0.63161 | 0.22900 | 0.16611 | 0.25065 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.93472E-002 | 0.14029 | 0.63161 | 0.63161 | 0.22900 | 0.16611 | 0.25065 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.17728 | 0.47032 | 0.47032 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 2.40661E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | CurtainWall | 3.838 | 0.300 | 0.402 |
2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.799 | 0.390 | 0.214 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.331 | 7.274E-004 | 4.751E-004 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.9193E-005 |
2 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8745E-004 |
3 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.0518E-005 |
4 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0437E-004 |
5 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.6885E-005 |
6 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.0781E-004 |
7 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0157E-004 |
8 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.7234E-004 |
9 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6035E-004 |
10 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.7134E-004 |
11 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3648E-004 |
12 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.8673E-004 |
13 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4458E-004 |
14 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6713E-004 |
15 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4476E-004 |
16 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5357E-004 |
17 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.6131E-004 |
18 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2934E-004 |
19 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0440E-004 |
20 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3538E-004 |
21 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.1579E-004 |
22 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1760E-004 |
23 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.0436E-004 |
24 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1182E-005 |
25 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.0166E-004 |
26 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1073E-005 |
27 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.3608E-004 |
28 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.3591E-005 |
29 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.7670E-004 |
30 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.5250E-005 |
31 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3611E-003 |
32 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3609E-005 |
33 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5951E-004 |
34 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3970E-005 |
35 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.6842E-004 |
36 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.5318E-005 |
37 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.3327E-004 |
38 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1987E-005 |
39 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1206E-004 |
40 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8484E-005 |
41 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.2426E-004 |
42 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7222E-005 |
43 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.4225E-004 |
44 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8154E-005 |
45 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3052E-004 |
46 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7202E-005 |
47 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8883E-004 |
48 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6707E-005 |
49 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.2562E-004 |
50 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8523E-005 |
51 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0906E-003 |
52 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9708E-005 |
53 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.4101E-004 |
54 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7726E-005 |
55 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4746E-004 |
56 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6794E-005 |
57 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0011E-003 |
58 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.7724E-005 |
59 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5434E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.9825E-005 |
61 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4678E-003 |
62 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3590E-005 |
63 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1327E-003 |
64 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8762E-005 |
65 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0394E-003 |
66 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.4217E-005 |
67 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0173E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.9484E-005 |
69 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.6857E-003 |
70 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1261E-005 |
71 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.6038E-003 |
72 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4693E-005 |
73 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1043E-004 |
74 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8911E-004 |
75 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.1654E-004 |
76 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0841E-004 |
77 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.3362E-004 |
78 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4697E-004 |
79 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6538E-003 |
80 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6639E-005 |
81 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9989E-004 |
82 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.5533E-004 |
83 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6814E-004 |
84 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6278E-004 |
85 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8784E-004 |
86 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.6535E-004 |
87 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.4325E-004 |
88 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9096E-004 |
89 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.6649E-005 |
90 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.8708E-003 |
91 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.6354E-005 |
92 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.4473E-003 |
93 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.3440E-005 |
94 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0561E-003 |
95 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1412E-004 |
96 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.0087E-004 |
97 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7494E-005 |
98 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4313E-003 |
99 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.3990E-005 |
100 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5293E-003 |
101 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1887E-005 |
102 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.0247E-003 |
103 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.1055E-005 |
104 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.2128E-003 |
105 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5771E-005 |
106 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.4531E-004 |
107 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2650E-005 |
108 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.9340E-004 |
109 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0583E-005 |
110 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0427E-003 |
111 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.8879E-005 |
112 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2630E-003 |
113 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2693E-005 |
114 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7426E-005 |
115 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8770E-005 |
116 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9922E-005 |
117 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6233E-005 |
118 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6001E-005 |
119 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4598E-005 |
120 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5286E-005 |
121 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5213E-005 |
122 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8184E-005 |
123 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8176E-005 |
124 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3169E-005 |
125 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3996E-005 |
126 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1504E-005 |
127 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1685E-005 |
128 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2542E-005 |
129 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2149E-005 |
130 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0224E-005 |
131 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8641E-005 |
132 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9516E-005 |
133 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7788E-005 |
134 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9712E-005 |
135 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4582E-005 |
136 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1042E-005 |
137 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3993E-004 |
138 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2585E-004 |
139 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5123E-004 |
140 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3761E-004 |
141 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1796E-004 |
142 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9102E-005 |
143 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2514E-005 |
144 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3080E-005 |
145 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3881E-005 |
146 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8824E-004 |
147 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3943E-005 |
148 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1091E-004 |
149 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2550E-005 |
150 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4063E-004 |
151 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4916E-005 |
152 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6240E-005 |
153 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4723E-005 |
154 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5370E-005 |
155 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9616E-005 |
156 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5401E-005 |
157 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2281E-005 |
158 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4572E-005 |
159 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4899E-005 |
160 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1079E-005 |
161 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8185E-004 |
162 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6328E-005 |
163 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0447E-004 |
164 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7697E-005 |
165 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3241E-004 |
166 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1471E-005 |
167 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2500E-005 |
168 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7738E-005 |
169 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.4285E-005 |
170 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.2556E-004 |
171 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2351E-005 |
172 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.3039E-004 |
173 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0157E-004 |
174 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5307E-004 |
175 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0532E-005 |
176 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7293E-004 |
177 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4218E-004 |
178 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5417E-004 |
179 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7573E-004 |
180 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8013E-004 |
181 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1530E-004 |
182 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1814E-004 |
183 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5069E-004 |
184 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0290E-004 |
185 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4627E-004 |
186 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2439E-005 |
187 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3630E-004 |
188 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2992E-005 |
189 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.9211E-004 |
190 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0573E-005 |
191 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5061E-004 |
192 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8433E-005 |
193 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3309E-004 |
194 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7995E-005 |
195 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3959E-004 |
196 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7589E-005 |
197 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2472E-004 |
198 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7733E-005 |
199 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0473E-005 |
200 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3210E-005 |
201 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4021E-003 |
202 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.6178E-005 |
203 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6313E-003 |
204 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3970E-005 |
205 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1935E-003 |
206 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2736E-005 |
207 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2387E-004 |
208 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6113E-005 |
209 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0173E-004 |
210 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3330E-004 |
211 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6710E-004 |
212 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6310E-004 |
213 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9135E-004 |
214 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6244E-004 |
215 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2445E-004 |
216 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5215E-004 |
217 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8457E-004 |
218 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9716E-005 |
219 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8622E-004 |
220 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8724E-005 |
221 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0504E-004 |
222 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0297E-005 |
223 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2708E-004 |
224 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5686E-005 |
225 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3247E-004 |
226 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1935E-003 |
227 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2463E-004 |
228 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6104E-003 |
229 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6110E-004 |
230 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6882E-003 |
231 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2726E-004 |
232 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9459E-004 |
233 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9180E-004 |
234 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9706E-005 |
235 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8061E-004 |
236 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8223E-005 |
237 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4567E-004 |
238 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0769E-005 |
239 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9961E-004 |
240 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7482E-005 |
241 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4234E-003 |
242 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.7556E-005 |
243 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4815E-003 |
244 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.1772E-005 |
245 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7792E-003 |
246 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0103E-004 |
247 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6165E-003 |
248 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3274E-005 |
249 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0538E-003 |
250 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5997E-004 |
251 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0325E-003 |
252 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4818E-004 |
253 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4212E-003 |
254 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1849E-004 |
255 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6195E-003 |
256 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2024E-004 |
257 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5112E-004 |
258 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2370E-003 |
259 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3502E-004 |
260 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3743E-003 |
261 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9333E-004 |
262 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7021E-003 |
263 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0001E-004 |
264 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6530E-003 |
265 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4485E-004 |
266 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7924E-005 |
267 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2837E-004 |
268 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6291E-005 |
269 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8315E-004 |
270 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8652E-005 |
271 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9852E-004 |
272 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7461E-005 |
273 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2899E-004 |
274 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0337E-004 |
275 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1098E-004 |
276 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.9172E-004 |
277 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4926E-004 |
278 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1484E-003 |
279 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9891E-004 |
280 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6031E-003 |
281 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5597E-004 |
282 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.4958E-005 |
283 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7800E-004 |
284 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7965E-005 |
285 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8236E-004 |
286 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.4768E-005 |
287 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5919E-003 |
288 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3045E-005 |
289 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9304E-004 |
290 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9150E-004 |
291 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0933E-004 |
292 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5649E-004 |
293 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5944E-004 |
294 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9806E-004 |
295 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5949E-003 |
296 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1554E-004 |
297 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9568E-005 |
298 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8339E-004 |
299 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6451E-005 |
300 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3233E-004 |
301 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6004E-005 |
302 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9971E-004 |
303 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2574E-004 |
304 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7337E-004 |
305 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3356E-004 |
306 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4624E-004 |
307 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9124E-004 |
308 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2387E-004 |
309 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3856E-004 |
310 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6366E-004 |
311 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1039E-004 |
312 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4748E-004 |
313 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4760E-005 |
314 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6393E-005 |
315 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8025E-005 |
316 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4269E-005 |
317 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5064E-005 |
318 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3985E-005 |
319 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1671E-005 |
320 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7584E-005 |
321 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2086E-005 |
322 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5186E-005 |
323 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0102E-005 |
324 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3747E-005 |
325 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.9730E-005 |
326 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5179E-005 |
327 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2556E-004 |
328 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5637E-005 |
329 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9449E-005 |
330 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1034E-004 |
331 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1894E-005 |
332 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1231E-005 |
333 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0636E-005 |
334 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.3569E-005 |
335 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9741E-005 |
336 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6869E-004 |
337 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0086E-004 |
338 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.6946E-005 |
339 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3665E-005 |
340 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6091E-005 |
341 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3535E-005 |
342 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0416E-005 |
343 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4732E-004 |
344 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0119E-004 |
345 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9009E-005 |
346 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2443E-005 |
347 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2232E-005 |
348 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1365E-005 |
349 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5244E-005 |
350 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1964E-005 |
351 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9684E-005 |
352 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3161E-005 |
353 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3676E-004 |
354 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8050E-005 |
355 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9619E-004 |
356 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2428E-005 |
357 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6176E-004 |
358 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9937E-005 |
359 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0983E-004 |
360 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5702E-005 |
361 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0009E-004 |
362 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4729E-005 |
363 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3699E-005 |
364 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1075E-005 |
365 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8023E-005 |
366 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2688E-005 |
367 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4724E-004 |
368 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8139E-005 |
369 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.7655E-003 |
370 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.4275E-004 |
371 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.3769E-003 |
372 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.0178E-004 |
373 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.2549E-003 |
374 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 2.9087E-004 |
375 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.6432E-003 |
376 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 2.9102E-004 |
377 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.4253E-004 |
378 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.1994E-003 |
379 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.0642E-004 |
380 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.6218E-003 |
381 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.9628E-004 |
382 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.3975E-003 |
383 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.8766E-004 |
384 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.2049E-003 |
385 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.5805E-003 |
386 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.9382E-004 |
387 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.9616E-003 |
388 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.5471E-004 |
389 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.3636E-003 |
390 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.1849E-004 |
391 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.0628E-003 |
392 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.7713E-004 |
393 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.6752E-003 |
394 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.9424E-004 |
395 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.9971E-003 |
396 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.5492E-004 |
397 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.2127E-003 |
398 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.1824E-004 |
399 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.0627E-003 |
400 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.7713E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11734.34147 | 14081.20977 | 0.99040 | 1.18848 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 41.51500 | 9.15709E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 6220.44797 | 7464.53756 | 0.17888 | 0.21466 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 6.30000 | 6.07234E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 43394.87998 | 52073.85598 | 2.85507 | 3.42608 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 42.00000 | 9.15790E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 12170.02767 | 14604.03320 | 0.29523 | 0.42471 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 6.30000 | 6.07234E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 42.00000 | 9.15790E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 31436.31023 | 37723.57228 | 0.78800 | 0.97684 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 18809.23 | 1.18848 | 1.18848 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 6581.85 | 0.21466 | 0.21466 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 67062.51 | 3.42608 | 3.42608 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 16881.75 | 0.42471 | 0.42471 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.18848 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.42608 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.97684 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 0.97684 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 38969.50361 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 37723.57228 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.18848 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.18848 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.18848 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.18848 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.18848 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.18848 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.42608 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.42608 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.42608 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.42608 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.42608 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.42608 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.18848 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.42608 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.18848 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.18848 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1315.83149 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.18848 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.18848 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.18848 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.78439 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.18848 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.59424 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.79232 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24430.85000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12215.42500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76506 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76506 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24430.85000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28386.52000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 28386.52000 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.42608 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.42608 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3666.06722 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.42608 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.42608 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.42608 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.26121 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.42608 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.71304 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.28405 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 84462.65000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 42231.32500 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70387 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70387 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 84462.65000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 103401.81231 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 103401.81231 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 23507.9 | 11.88 | 11.61 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 81799.7 | 11.11 | 10.86 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 3.4721045888E-002 | 2.3886424048E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.1317718684 | 0.1495134346 | Pass | Pass | 0.3014840443 | 1.7471360378 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 6.6300168078E-002 | 5.3076350993E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:02
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 9282.59 | 440.55 | 0.00 | -94.5 | 573.19 | 10201.88 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:02
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.60 | 4 | |||
Feb | 21.40 | 43 | |||
Mar | 12.00 | 35 | |||
Apr | 29.10 | 12 | |||
May | 29.10 | 57 | |||
Jun | 197.10 | 59 | |||
Jul | 47.90 | 83 | |||
Aug | 0.00 | 0 | |||
Sep | 171.60 | 106 | |||
Oct | 4.80 | 31 | |||
Nov | 1.20 | 7 | |||
Dec | 33.00 | 13 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:02
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.233 | 0.240 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.985 | 2.825 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.985 | 2.825 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.985 | 2.825 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.653 | 0.717 | 3204.84 | 3105.72 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.685 | 2.825 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.685 | 2.825 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.503_SHGC_WEST_0.229 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.860 | 0.230 | 0.230 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.503_SHGC_WEST_0.229 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.860 | 0.230 | 0.230 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.503_SHGC_NORTH_0.229 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.860 | 0.230 | 0.230 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.503_SHGC_NORTH_0.229 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.860 | 0.230 | 0.230 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 137.59 | 5.146 | 0.472 | 0.379 | |||||||||||||||||
North Total or Average | 6.51 | 2.860 | 0.230 | 0.230 | |||||||||||||||||
Non-North Total or Average | 131.09 | 5.260 | 0.484 | 0.387 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:02
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:02
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 6.9682 | 236.88 | 1650.63 | LightsWired | LTG_SCH_OFFICE | 52.33 | 168.00 | 33.02 | 0.0000 | Y | 10.23 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 7.4271 | 1393.41 | 10348.98 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 17.79 | 0.0000 | Y | 34.56 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.5521 | 3204.84 | 11383.89 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 16.89 | 0.0000 | Y | 36.09 |
Interior Lighting Total | 4.8362 | 4835.13 | 23383.49 | 80.88 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10348.98 | 2587.24 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10348.98 | 2587.24 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 11383.89 | 2845.97 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 11383.89 | 2845.97 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.29 | 1650.63 | 478.68 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.10 | 1650.63 | 165.06 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 123.84 | AstronomicalClock | - | 41.75 | 41.75 | 0.97 | |
EXTERIOR_LIGHTS_B | 4305.62 | AstronomicalClock | - | 83.75 | 62.75 | 50.72 | |
EXTERIOR_LIGHTS_C | 1091.36 | AstronomicalClock | - | 83.75 | 48.85 | 10.01 | |
Exterior Lighting Total | 5520.82 | 61.70 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:02
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24430.85 | 18691.07 | 5739.78 | 0.77 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 84462.65 | 59450.73 | 25011.92 | 0.70 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 23507.9 | 11.88 | 11.61 | ||||
PSZ-FINE STORAGE COOLING COIL | 81799.7 | 11.11 | 10.86 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 38969.50 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 28386.52 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 103401.81 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.98 | 90.76 | 92.91 | 1.00 | 4.17 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.19 | 1315.83 | 1107.16 | 1.00 | 1.36 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 3.43 | 3666.07 | 1070.05 | 1.00 | 1.25 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:02
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11734.34 | 14081.21 | 59.44 | 0.990 | 1.188 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 23.90 | 23.90 | 0.00829 | 41.52 | 0.00916 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 43394.88 | 52073.86 | 37.37 | 2.855 | 3.426 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 26.70 | 26.70 | 0.00833 | 42.00 | 0.00916 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 0.00 | 41.89 | 0.00924 | 42.00 | 0.00916 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 6220.45 | 7464.54 | 31.51 | 0.179 | 0.215 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00852 | 6.30 | 0.00607 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 12170.03 | 14604.03 | 10.48 | 0.295 | 0.425 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00779 | 6.30 | 0.00607 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 31436.31 | 37723.57 | 11.77 | 0.788 | 0.977 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00762 | 6.30 | 0.00607 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.19 | 1.19 | 0.21 | 0.21 | 1.1885 | 1.1885 | 1.1885 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.43 | 3.43 | 0.42 | 0.42 | 3.4261 | 3.4261 | 3.4261 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 38969.504 | 38969.504 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 38969.50 | 38969.50 | 0.976836 | 10.00 | 9.78 | 0.00762186 | 43.33 | 21.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 10.00 | 0.00762186 | 97.3576 | 37723.57 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 24430.850 | 18691.066 | 1.188480 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 12215.42 | 11565.65 | 0.792320 | 26.35 | 16.83 | 0.00836024 | 12.00 | 11.03 | 0.00800000 | 41.61 | 0.00915725 | 22.16 | 12.9095 | 23.90 | 0.00828515 | 43.7544 | 11729.11 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 28386.520 | 28386.520 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 28386.52 | 28386.52 | 1.188476 | 19.75 | 14.41 | 0.00830861 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 8.6064 | 21.10 | 0.00851920 | 53.3084 | 6220.45 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 84462.650 | 59450.725 | 3.426080 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 42231.32 | 39992.41 | 2.284053 | 29.49 | 17.94 | 0.00842829 | 12.00 | 11.03 | 0.00800000 | 42.00 | 0.00915790 | 22.26 | 18.5946 | 26.70 | 0.00832505 | 37.2183 | 43394.88 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 103401.812 | 103401.812 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 103401.81 | 103401.81 | 3.426080 | 14.41 | 11.68 | 0.00763934 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 12.3964 | 15.56 | 0.00786108 | 69.7198 | 11914.73 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:02
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 38969.504 | 38969.504 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.976836 | 1.14659581 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 38969.50 | 38969.50 | 1.0000 | 1.14659581 | 0.976836 | 10.00 | 9.78 | 0.00762186 | 29251.8 | 43.33 | 21.85 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38969.50 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 10.00 | 0.00762186 | 10.00 | 0.00762186 | 97.3576 | 37723.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24430.850 | 18691.066 | 1.188480 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3813 | 1004.8586 | 1.1738 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.188476 | 1.39501574 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | Sensible | 12215.42 | 11565.65 | 1.0000 | 0.93001370 | 0.792320 | 26.35 | 16.83 | 0.00836024 | 47793.8 | 12.00 | 11.03 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12215.42 | 41.61 | 0.00915725 | 22.16 | 0.10228463 | 12.9095 | 23.90 | 0.00828515 | 23.90 | 0.00828515 | 43.7544 | 11729.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28386.520 | 28386.520 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.188476 | 1.39501574 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 28386.52 | 28386.52 | 1.0000 | 1.39501574 | 1.188476 | 19.75 | 14.41 | 0.00830861 | 40929.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28386.52 | 6.30 | 0.00607234 | 6.30 | 0.10228463 | 8.6064 | 21.02 | 0.00851920 | 21.10 | 0.00851920 | 53.3084 | 6220.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 84462.650 | 59450.725 | 3.426080 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5078 | 1004.8586 | 1.1738 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.426080 | 4.02148253 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | Sensible | 42231.32 | 39992.41 | 1.0000 | 2.68098859 | 2.284053 | 29.49 | 17.94 | 0.00842829 | 51172.1 | 12.00 | 11.03 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 42231.32 | 42.00 | 0.00915790 | 22.26 | 0.42471127 | 18.5946 | 26.70 | 0.00832505 | 26.70 | 0.00832505 | 37.2183 | 43394.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 103401.812 | 103401.812 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.426080 | 4.02148253 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 103401.81 | 103401.81 | 1.0000 | 4.02148253 | 3.426080 | 14.41 | 11.68 | 0.00763934 | 33791.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 103401.81 | 6.30 | 0.00607234 | 6.30 | 0.42471127 | 12.3964 | 15.56 | 0.00786108 | 15.56 | 0.00786108 | 69.7198 | 11914.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:02
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2563.83 | 1258.17 | 462.17 |
ZONE2 FINE STORAGE | 2988.17 | 2949.83 | 2390.50 |
ZONE3 BULK STORAGE | 3082.50 | 3293.83 | 2802.67 |
Facility | 3087.33 | 3407.00 | 2807.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 2.50 | 58.67 | 2.50 | 54.83 |
ZONE2 FINE STORAGE | 0.67 | 334.17 | 0.00 | 4.33 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 3.17 | 387.67 | 2.50 | 55.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:02
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.353 | 0.352 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.496 | 0.104 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.059 | 0.000 | 1.940 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:02
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.56 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1262329.82 | 0.00 | 1262329.82 | 1486676.65 | 2749006.47 | 3225648.14 | 5394.67 | 3365.33 | 0.00 | 97.68 |
ZONE2 FINE STORAGE | 5760031.56 | 0.00 | 5760031.56 | 2250900.29 | 8010931.85 | 13393694.68 | 5409.40 | 3350.60 | 0.00 | 1580.48 |
ZONE3 BULK STORAGE | 0.00 | 0.47E+09 | 0.47E+09 | 11943479.77 | 0.49E+09 | 30805497.77 | 5003.61 | 0.17 | 3756.23 | 3964.52 |
Total Facility | 7022361.38 | 0.47E+09 | 0.48E+09 | 15681056.71 | 0.50E+09 | 47424840.58 | 7014.37 | 3382.63 | 3756.23 | 4043.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.0960 | 0.0000 | 0.0960 | 0.0958 | 0.1918 | 0.1023 | 270.67 | 3365.33 | 0.00 |
ZONE2 FINE STORAGE | 0.3909 | 0.0000 | 0.3909 | 0.0818 | 0.4727 | 0.4247 | 302.53 | 3333.47 | 0.00 |
ZONE3 BULK STORAGE | 0.0000 | 17.5827 | 17.5827 | 0.5459 | 18.1286 | 0.9768 | 1818.18 | 0.00 | 1817.82 |
Total Facility | 0.4869 | 17.5827 | 18.0695 | 0.7235 | 18.7930 | 1.5038 | 1890.37 | 3365.33 | 1817.82 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 1739215.77 | 0.00 | 1739215.77 | 3225648.14 | 5379.91 | 1.09 | 3379.01 | 95.97 |
PSZ-FINE STORAGE | 7936026.34 | 0.00 | 7936026.34 | 13393694.68 | 5350.14 | 5.04 | 3404.82 | 1579.95 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1323 | 0.0000 | 0.1323 | 0.1023 | 257.78 | 0.77 | 3377.45 |
PSZ-FINE STORAGE | 0.5385 | 0.0000 | 0.5385 | 0.4247 | 300.92 | 0.14 | 3334.93 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 3599.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 4989.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1372 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.5744 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:02
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 446 |
Defaulted Fields | 391 |
Fields with Defaults | 1172 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:02
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 488.66 | 1550.86 | 01-JAN-09:20 | 47085.63 | 06-JUN-15:40 |
Electricity:Building | 248.53 | 1069.86 | 01-JAN-09:20 | 19822.04 | 18-JUL-08:10 |
Electricity:Zone:ZONE1 OFFICE | 39.40 | 520.87 | 01-JAN-00:10 | 2830.89 | 11-OCT-07:10 |
Electricity:SpaceType:GENERAL | 217.39 | 1069.86 | 01-JAN-09:20 | 17983.55 | 07-SEP-08:10 |
InteriorLights:Electricity | 80.88 | 599.99 | 01-JAN-09:20 | 7948.38 | 07-SEP-08:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.23 | 51.00 | 01-JAN-00:10 | 995.84 | 11-OCT-07:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 80.88 | 599.99 | 01-JAN-09:20 | 7948.38 | 07-SEP-08:10 |
LightsWired:InteriorLights:Electricity | 80.88 | 599.99 | 01-JAN-09:20 | 7948.38 | 07-SEP-08:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.23 | 51.00 | 01-JAN-00:10 | 995.84 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 80.88 | 599.99 | 01-JAN-09:20 | 7948.38 | 07-SEP-08:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 34.56 | 299.97 | 01-JAN-00:10 | 3491.43 | 07-SEP-08:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 34.56 | 299.97 | 01-JAN-00:10 | 3491.43 | 07-SEP-08:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 34.56 | 299.97 | 01-JAN-00:10 | 3491.43 | 07-SEP-08:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 174.58 | 249.02 | 01-JAN-09:20 | 13792.29 | 18-JUL-07:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 36.09 | 249.02 | 01-JAN-09:20 | 3489.80 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 36.09 | 249.02 | 01-JAN-09:20 | 3489.80 | 11-OCT-07:10 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 60.50 | 0.00 | 01-JAN-00:10 | 5868.26 | 06-JUN-16:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 31.14 | 0.00 | 01-JAN-00:10 | 2305.29 | 30-JUN-05:10 |
Ventilation (simple):Fans:Electricity | 31.14 | 0.00 | 01-JAN-00:10 | 2305.29 | 30-JUN-05:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 31.14 | 0.00 | 01-JAN-00:10 | 2305.29 | 30-JUN-05:10 |
ElectricityPurchased:Facility | 488.66 | 1550.86 | 01-JAN-09:20 | 47085.63 | 06-JUN-15:40 |
ElectricityPurchased:Plant | 488.66 | 1550.86 | 01-JAN-09:20 | 47085.63 | 06-JUN-15:40 |
Cogeneration:ElectricityPurchased | 488.66 | 1550.86 | 01-JAN-09:20 | 47085.63 | 06-JUN-15:40 |
General:Cogeneration:ElectricityPurchased | 488.66 | 1550.86 | 01-JAN-09:20 | 47085.63 | 06-JUN-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 488.66 | 1550.86 | 01-JAN-09:20 | 47085.63 | 06-JUN-15:40 |
ElectricityNet:Plant | 488.66 | 1550.86 | 01-JAN-09:20 | 47085.63 | 06-JUN-15:40 |
Cogeneration:ElectricityNet | 488.66 | 1550.86 | 01-JAN-09:20 | 47085.63 | 06-JUN-15:40 |
General:Cogeneration:ElectricityNet | 488.66 | 1550.86 | 01-JAN-09:20 | 47085.63 | 06-JUN-15:40 |
Electricity:HVAC | 155.77 | 0.00 | 01-JAN-00:10 | 29061.64 | 06-JUN-15:10 |
General:Fans:Electricity | 29.36 | 0.00 | 01-JAN-00:10 | 3562.97 | 06-JUN-16:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 126.40 | 0.00 | 01-JAN-00:10 | 25540.27 | 06-JUN-15:10 |
General:Cooling:Electricity | 126.40 | 0.00 | 01-JAN-00:10 | 25540.27 | 06-JUN-15:10 |
ExteriorLights:Electricity | 61.70 | 0.00 | 01-JAN-07:20 | 5520.82 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 61.70 | 0.00 | 01-JAN-07:20 | 5520.82 | 01-JAN-06:10 |
Electricity:Plant | 22.67 | 481.00 | 05-JAN-06:10 | 1769.27 | 17-JAN-12:20 |
WaterSystems:Electricity | 22.67 | 481.00 | 05-JAN-06:10 | 1769.27 | 17-JAN-12:20 |
Water Heater:WaterSystems:Electricity | 22.67 | 481.00 | 05-JAN-06:10 | 1769.27 | 17-JAN-12:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 2.35 | 0.00 | 01-JAN-00:10 | 28261.52 | 03-JAN-06:10 |
NaturalGas:HVAC | 2.35 | 0.00 | 01-JAN-00:10 | 28261.52 | 03-JAN-06:10 |
Heating:NaturalGas | 2.35 | 0.00 | 01-JAN-00:10 | 28261.52 | 03-JAN-06:10 |
General:Heating:NaturalGas | 2.35 | 0.00 | 01-JAN-00:10 | 28261.52 | 03-JAN-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 15-MAR-11:20 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 15-MAR-11:20 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 15-MAR-11:20 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 15-MAR-11:20 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 15-MAR-11:20 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 15-MAR-11:20 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 15-MAR-11:20 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 15-MAR-11:20 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 732.24 | 0.00 | 01-JAN-00:10 | 126945.03 | 06-JUN-15:10 |
EnergyTransfer:Building | 284.62 | 0.00 | 01-JAN-00:10 | 55902.49 | 06-JUN-15:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 76.71 | 0.00 | 01-JAN-00:10 | 16427.37 | 06-JUN-16:10 |
Heating:EnergyTransfer | 1.88 | 0.00 | 01-JAN-00:10 | 20377.71 | 03-JAN-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 1.13 | 0.00 | 01-JAN-00:10 | 14525.68 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 1.88 | 0.00 | 01-JAN-00:10 | 20377.71 | 03-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 1.13 | 0.00 | 01-JAN-00:10 | 14525.68 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 282.74 | 0.00 | 01-JAN-00:10 | 55902.49 | 06-JUN-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 75.58 | 0.00 | 01-JAN-00:10 | 16427.37 | 06-JUN-16:10 |
General:Cooling:EnergyTransfer | 282.74 | 0.00 | 01-JAN-00:10 | 55902.49 | 06-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 75.58 | 0.00 | 01-JAN-00:10 | 16427.37 | 06-JUN-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 207.91 | 0.00 | 01-JAN-00:10 | 43113.15 | 06-JUN-15:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.76 | 0.00 | 01-JAN-00:10 | 11155.22 | 01-JAN-06:30 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.76 | 0.00 | 01-JAN-00:10 | 11155.22 | 01-JAN-06:30 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 207.16 | 0.00 | 01-JAN-00:10 | 43113.15 | 06-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 207.16 | 0.00 | 01-JAN-00:10 | 43113.15 | 06-JUN-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 447.61 | 0.00 | 01-JAN-00:10 | 75727.76 | 22-JUN-16:30 |
HeatingCoils:EnergyTransfer | 1.59 | 0.00 | 01-JAN-00:10 | 21306.39 | 03-JAN-06:10 |
CoolingCoils:EnergyTransfer | 446.03 | 0.00 | 01-JAN-00:10 | 75727.76 | 22-JUN-16:30 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:02
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 1.128 | -75.584 | 0.000 | 0.000 | 9.217 | 10.231 | 29.165 | 11.461 | 0.000 | 7.881 | 14.052 | 0.000 | -4.044 | 0.000 | -3.506 | -0.000 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 0.757 | -207.150 | 0.000 | 0.000 | 18.825 | 34.558 | 0.000 | 36.407 | 0.000 | 8.564 | 122.933 | 0.000 | -10.300 | 0.000 | -4.593 | -0.000 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 27.915 | 36.094 | 107.344 | 736.862 | 0.000 | 32.327 | 0.011 | 0.000 | -199.751 | 0.000 | -456.651 | -284.140 |
Total Facility | 0.000 | 0.000 | 1.884 | -282.733 | 0.000 | 0.000 | 55.957 | 80.882 | 136.508 | 784.730 | 0.000 | 48.772 | 136.996 | 0.000 | -214.095 | 0.000 | -464.750 | -284.140 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 25-OCT-05:01 | 0.00 | 0.00 | 0.00 | -23687.38 | 0.00 | 0.00 | 78.05 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 23720.20 | 0.00 | -356.50 | 0.00 | -355.88 | 0.00 |
ZONE2 FINE STORAGE | 08-OCT-14:13 | 0.00 | 0.00 | 0.00 | -72509.13 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 3522.45 | 0.00 | 197.69 | 68489.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 04-MAY-05:01 | 0.00 | 0.00 | 0.00 | -89958.71 | 0.00 | 0.00 | 363.36 | 849.01 | 2600.55 | 67.81 | 0.00 | 587.06 | 145979.13 | 0.00 | -8898.97 | 0.00 | -51589.24 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 02-JAN-06:01 | 0.00 | 0.00 | 27527.78 | 0.00 | 0.00 | 0.00 | 145.76 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -444.07 | 0.00 | -536.82 | -27294.17 |
ZONE2 FINE STORAGE | 03-JAN-06:01 | 0.00 | 0.00 | 60744.72 | 0.00 | 0.00 | 0.00 | 354.25 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1033.31 | 0.00 | -182.97 | -60182.66 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-JAN-06:01 | 0.00 | 0.00 | 88084.83 | 0.00 | 0.00 | 0.00 | 1358.08 | 849.01 | 2600.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -20739.06 | 0.00 | -1679.28 | -70474.14 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:02
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1885 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.1885 | 0.0861 | 1.0000 | Not calculated | 0.1023 | 0.0861 | ||
PSZ-FINE STORAGE | 3.4261 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.4261 | 0.1240 | 1.0000 | Not calculated | 0.4247 | 0.1240 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1885 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.1885 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0861 | ||
PSZ-FINE STORAGE | 3.4261 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.4261 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1240 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1885 | 1.1885 | 1.1885 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.4261 | 3.4261 | 3.4261 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1885 | 1.1885 | 1.1885 | 1.1885 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.4261 | 3.4261 | 3.4261 | 3.4261 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1885 | 1.1885 | 1.1885 | No | 0.1023 | 0.4765 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.4261 | 3.4261 | 3.4261 | No | 0.4247 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1885 | 1.1885 | 1.1885 | 1.1885 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.4261 | 3.4261 | 3.4261 | 3.4261 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:02
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 2.50 |
Number of hours cooling loads not met | 55.00 |
Number of hours not met | 57.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 2.35 | 28261.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 126.40 | 25540.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 80.88 | 7948.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 61.70 | 5520.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 31.14 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 29.36 | 3562.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 22.67 | 1769.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 488.66 |
Natural Gas | 0.00 | 2.35 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 491.01 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 16.73 |
Space Heating | 0.00 |
Space Cooling | 26.14 |
Fans (All) | 12.51 |
Service Water Heating | 4.69 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 101.06 |
Subtotal | 101.06 |
Natural Gas [MJ/m2] | |
Space Heating | 0.49 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.49 |
Subtotal | 0.49 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 16.47 |
Space Heating | 0.48 |
Space Cooling | 25.74 |
Fans (All) | 12.32 |
Service Water Heating | 4.62 |
Receptacle Equipment | 27.80 |
Miscellaneous | 12.57 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2729. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:02
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 5924.50 | 2777.83 | 57.67 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 5132.33 | 3627.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3004.00 | 2176.17 | 2583.33 | 996.50 | 0.00 |
Min | 3004.00 | 2176.17 | 0.00 | 0.00 | 0.00 |
Max | 5924.50 | 3627.67 | 2583.33 | 996.50 | 0.00 |
Average | 4686.94 | 2860.56 | 880.33 | 332.17 | 0.00 |
Sum | 14060.83 | 8581.67 | 2641.00 | 996.50 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33026.50 | 0.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 41271.50 | 41447.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 52929.00 | 51833.17 | 55597.83 | 30833.00 | 0.00 |
Min | 33026.50 | 0.50 | 0.00 | 0.00 | 0.00 |
Max | 52929.00 | 51833.17 | 55597.83 | 30833.00 | 0.00 |
Average | 42409.00 | 31093.72 | 18532.61 | 10277.67 | 0.00 |
Sum | 127227.00 | 93281.17 | 55597.83 | 30833.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 5658.50 | 3085.17 | 16.33 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 4826.67 | 3933.33 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3049.83 | 2757.50 | 2189.17 | 741.67 | 21.83 |
Min | 3049.83 | 2757.50 | 0.00 | 0.00 | 0.00 |
Max | 5658.50 | 3933.33 | 2189.17 | 741.67 | 21.83 |
Average | 4511.67 | 3258.67 | 735.17 | 247.22 | 7.28 |
Sum | 13535.00 | 9776.00 | 2205.50 | 741.67 | 21.83 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 31639.17 | 1387.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 37941.00 | 44778.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 54188.00 | 64748.00 | 48713.50 | 22587.33 | 956.17 |
Min | 31639.17 | 1387.83 | 0.00 | 0.00 | 0.00 |
Max | 54188.00 | 64748.00 | 48713.50 | 22587.33 | 956.17 |
Average | 41256.06 | 36971.28 | 16237.83 | 7529.11 | 318.72 |
Sum | 123768.17 | 110913.83 | 48713.50 | 22587.33 | 956.17 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:02
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:02
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Environment
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Environment
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.554322E+09 | 2523.61 | 14-JAN-16:00 | 21.30 | 15.07 | 0.579363E+09 | 770.88 | 04-JAN-15:39 | 21.30 | 15.07 |
February | 0.168639E+10 | 4934.66 | 22-FEB-16:10 | 26.37 | 15.92 | 0.565140E+09 | 769.02 | 24-FEB-16:00 | 25.60 | 17.28 |
March | 0.500349E+10 | 22527.51 | 29-MAR-05:01 | 21.18 | 17.34 | 0.684049E+09 | 769.03 | 18-MAR-14:00 | 21.18 | 17.34 |
April | 0.778993E+10 | 23553.42 | 04-APR-05:01 | 22.68 | 15.57 | 0.635137E+09 | 769.08 | 27-APR-13:39 | 39.40 | 19.89 |
May | 0.100420E+11 | 23215.18 | 08-MAY-05:01 | 28.90 | 19.72 | 0.660752E+09 | 769.08 | 08-MAY-10:39 | 35.80 | 20.97 |
June | 0.103225E+11 | 22443.05 | 13-JUN-05:01 | 32.37 | 22.66 | 0.660818E+09 | 769.11 | 05-JUN-12:09 | 32.37 | 22.66 |
July | 0.945235E+10 | 18740.27 | 07-JUL-05:01 | 31.52 | 25.91 | 0.635410E+09 | 769.09 | 07-JUL-12:09 | 39.13 | 24.79 |
August | 0.960683E+10 | 17674.89 | 09-AUG-05:01 | 29.90 | 25.20 | 0.686196E+09 | 769.08 | 07-AUG-12:09 | 29.90 | 25.20 |
September | 0.833945E+10 | 20973.59 | 27-SEP-05:01 | 23.08 | 20.68 | 0.635300E+09 | 769.07 | 23-SEP-14:39 | 23.08 | 20.68 |
October | 0.714748E+10 | 23686.47 | 25-OCT-05:01 | 19.02 | 16.53 | 0.635098E+09 | 769.08 | 02-OCT-13:09 | 19.02 | 16.53 |
November | 0.419174E+10 | 22280.92 | 02-NOV-05:02 | 16.55 | 13.37 | 0.607303E+09 | 769.03 | 09-NOV-10:39 | 26.17 | 18.15 |
December | 0.144848E+10 | 4549.91 | 01-DEC-15:20 | 23.03 | 13.49 | 0.612064E+09 | 769.01 | 05-DEC-16:30 | 19.20 | 14.16 |
Annual Sum or Average | 0.755849E+11 | 0.759663E+10 | ||||||||
Minimum of Months | 0.554322E+09 | 2523.61 | 16.55 | 13.37 | 0.565140E+09 | 769.01 | 19.02 | 14.16 | ||
Maximum of Months | 0.103225E+11 | 23686.47 | 32.37 | 25.91 | 0.686196E+09 | 770.88 | 39.40 | 25.20 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.962324E+09 | 4440.03 | 21-JAN-08:70 | 6.77 | 5.86 | 0.114161E+10 | 1795.79 | 26-JAN-14:30 | 22.05 | 13.77 |
February | 0.954529E+09 | 3910.03 | 02-FEB-08:70 | 8.07 | 7.90 | 0.134076E+10 | 2246.83 | 23-FEB-13:30 | 26.35 | 13.97 |
March | 0.705465E+10 | 60634.07 | 12-MAR-14:53 | 31.50 | 19.60 | 0.192862E+10 | 2246.95 | 29-MAR-13:09 | 32.13 | 19.67 |
April | 0.233985E+11 | 68049.18 | 29-APR-17:06 | 34.20 | 19.21 | 0.185296E+10 | 2246.95 | 25-APR-10:00 | 34.20 | 19.21 |
May | 0.364872E+11 | 68698.74 | 28-MAY-09:43 | 36.18 | 19.95 | 0.192898E+10 | 2247.09 | 04-MAY-12:00 | 36.18 | 19.95 |
June | 0.370524E+11 | 68009.13 | 07-JUN-05:01 | 33.20 | 19.50 | 0.192897E+10 | 2247.10 | 05-JUN-12:39 | 33.20 | 19.50 |
July | 0.316283E+11 | 62783.92 | 07-JUL-05:01 | 31.52 | 25.91 | 0.185474E+10 | 2247.05 | 08-JUL-12:30 | 35.60 | 27.93 |
August | 0.270510E+11 | 60567.40 | 09-AUG-05:01 | 29.90 | 25.20 | 0.200305E+10 | 2247.06 | 07-AUG-13:39 | 29.90 | 25.20 |
September | 0.212701E+11 | 62365.16 | 24-SEP-11:43 | 33.60 | 25.12 | 0.185479E+10 | 2246.98 | 18-SEP-13:09 | 33.60 | 25.12 |
October | 0.155390E+11 | 72510.14 | 08-OCT-14:13 | 32.33 | 18.80 | 0.184598E+10 | 2246.97 | 14-OCT-14:50 | 31.37 | 20.80 |
November | 0.449711E+10 | 28881.37 | 11-NOV-14:45 | 28.45 | 17.08 | 0.169200E+10 | 2246.92 | 08-NOV-15:09 | 28.45 | 17.08 |
December | 0.126005E+10 | 4916.40 | 21-DEC-08:20 | 6.40 | 5.45 | 0.136834E+10 | 2246.80 | 01-DEC-14:50 | 6.40 | 5.45 |
Annual Sum or Average | 0.207155E+12 | 0.207408E+11 | ||||||||
Minimum of Months | 0.954529E+09 | 3910.03 | 6.40 | 5.45 | 0.114161E+10 | 1795.79 | 6.40 | 5.45 | ||
Maximum of Months | 0.370524E+11 | 72510.14 | 36.18 | 25.91 | 0.200305E+10 | 2247.10 | 36.18 | 27.93 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 | 0.246062E+10 | 4008.99 | 26-JAN-14:30 | 22.05 | 13.77 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.85 | 0.309568E+10 | 5850.03 | 23-FEB-14:20 | 26.20 | 13.97 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.96 | 0.524593E+10 | 8728.95 | 28-MAR-15:30 | 35.55 | 18.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.77 | 0.623961E+10 | 9097.65 | 13-APR-14:39 | 36.23 | 19.38 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.24 | 0.713542E+10 | 9097.65 | 01-MAY-09:20 | 36.47 | 21.42 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.58 | 0.716042E+10 | 9097.65 | 01-JUN-15:09 | 35.52 | 20.96 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.65 | 0.637626E+10 | 9097.65 | 01-JUL-10:09 | 35.88 | 27.06 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 | 0.654477E+10 | 9097.65 | 05-AUG-12:00 | 35.70 | 26.86 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 | 0.586539E+10 | 9097.65 | 26-SEP-14:09 | 35.77 | 22.87 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.85 | 0.550889E+10 | 9097.65 | 02-OCT-12:30 | 35.90 | 21.26 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 | 0.435982E+10 | 6769.36 | 04-NOV-14:20 | 30.27 | 17.30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.11 | 0.309278E+10 | 5448.29 | 01-DEC-14:39 | 23.43 | 13.26 |
Annual Sum or Average | 0.00 | 0.630856E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 7.83 | 7.49 | 0.246062E+10 | 4008.99 | 22.05 | 13.26 | ||
Maximum of Months | 0.00 | 0.00 | 32.95 | 26.26 | 0.716042E+10 | 9097.65 | 36.47 | 27.06 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.752829E+09 | 27528.23 | 02-JAN-06:01 | 6.45 |
February | 0.167386E+09 | 19351.52 | 02-FEB-06:03 | 6.92 |
March | 273471.55 | 143.67 | 27-MAR-06:10 | 20.30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 1904607.06 | 1830.06 | 27-NOV-07:30 | 10.45 |
December | 0.205690E+09 | 25961.09 | 23-DEC-06:02 | 5.43 |
Annual Sum or Average | 0.112808E+10 | |||
Minimum of Months | 0.00 | 0.00 | 5.43 | |
Maximum of Months | 0.752829E+09 | 27528.23 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.441581E+09 | 60745.73 | 03-JAN-06:01 | 5.57 |
February | 0.210672E+09 | 1616.99 | 06-FEB-15:00 | 25.50 |
March | 15001315.89 | 1094.10 | 03-MAR-18:00 | 25.50 |
April | 897447.73 | 887.95 | 18-APR-06:05 | 24.75 |
May | 975878.57 | 1735.47 | 25-MAY-06:10 | 30.80 |
June | 1281.02 | 4.27 | 28-JUN-06:10 | 27.12 |
July | 175746.78 | 585.82 | 27-JUL-06:10 | 27.12 |
August | 1177888.61 | 1492.46 | 11-AUG-06:10 | 26.55 |
September | 2156986.60 | 1736.81 | 12-SEP-06:10 | 27.02 |
October | 96552.67 | 114.35 | 03-OCT-06:10 | 23.67 |
November | 3875784.24 | 380.00 | 27-NOV-12:30 | 24.85 |
December | 79903256.88 | 1264.17 | 28-DEC-14:00 | 24.60 |
Annual Sum or Average | 0.756515E+09 | |||
Minimum of Months | 1281.02 | 4.27 | 5.57 | |
Maximum of Months | 0.441581E+09 | 60745.73 | 30.80 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.874855E+09 | 987.59 | 18-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.788057E+09 | 985.47 | 10-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.889486E+09 | 992.32 | 18-MAR-07:10 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.829543E+09 | 939.26 | 03-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.853785E+09 | 962.50 | 24-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.846789E+09 | 979.04 | 24-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.842648E+09 | 983.04 | 26-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.909936E+09 | 986.33 | 16-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.836076E+09 | 990.04 | 09-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.850432E+09 | 995.84 | 11-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.830329E+09 | 974.80 | 03-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.878676E+09 | 981.36 | 29-DEC-16:00 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.102306E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.788057E+09 | 939.26 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.909936E+09 | 995.84 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.313317E+10 | 3336.74 | 18-JAN-09:09 | 0.00 | 0.00 |
February | 0.273105E+10 | 3361.14 | 10-FEB-09:09 | 0.00 | 0.00 |
March | 0.297090E+10 | 3298.84 | 13-MAR-08:09 | 0.00 | 0.00 |
April | 0.275066E+10 | 3240.45 | 08-APR-08:09 | 0.00 | 0.00 |
May | 0.281676E+10 | 3267.33 | 03-MAY-08:09 | 0.00 | 0.00 |
June | 0.276716E+10 | 3420.47 | 24-JUN-08:09 | 0.00 | 0.00 |
July | 0.266970E+10 | 3389.94 | 27-JUL-08:09 | 0.00 | 0.00 |
August | 0.284604E+10 | 3467.84 | 16-AUG-08:09 | 0.00 | 0.00 |
September | 0.272763E+10 | 3491.43 | 07-SEP-08:09 | 0.00 | 0.00 |
October | 0.292246E+10 | 3309.18 | 11-OCT-08:09 | 0.00 | 0.00 |
November | 0.302200E+10 | 3360.04 | 27-NOV-15:00 | 0.00 | 0.00 |
December | 0.320028E+10 | 3371.69 | 29-DEC-15:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.345578E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.266970E+10 | 3240.45 | 0.00 | 0.00 | |
Maximum of Months | 0.320028E+10 | 3491.43 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.324493E+10 | 3374.81 | 03-JAN-16:00 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.284583E+10 | 3325.84 | 10-FEB-08:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.313095E+10 | 3442.79 | 18-MAR-07:10 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.286422E+10 | 2988.27 | 01-APR-06:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.290061E+10 | 3020.31 | 24-MAY-07:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.287089E+10 | 3339.55 | 24-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.286143E+10 | 3299.76 | 26-JUL-07:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.305531E+10 | 3441.17 | 16-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.291713E+10 | 3486.18 | 07-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.305620E+10 | 3489.80 | 11-OCT-07:10 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.306375E+10 | 3481.63 | 27-NOV-16:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.328262E+10 | 3471.28 | 29-DEC-16:00 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.360939E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.284583E+10 | 2988.27 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.328262E+10 | 3489.80 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.874855E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85814.44 | 0.982630E+09 |
February | 0.127628E+10 | 0.788057E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23572455.21 | 0.673215E+09 |
March | 0.149825E+10 | 0.889486E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322985E+09 | 0.390398E+09 |
April | 0.138726E+10 | 0.829543E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961744E+09 | 55635915.38 |
May | 0.144276E+10 | 0.853785E+09 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158044E+10 | 10377698.39 |
June | 0.144276E+10 | 0.846789E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150849E+10 | 4805765.01 |
July | 0.138726E+10 | 0.842648E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110579E+10 | 5225578.25 |
August | 0.149825E+10 | 0.909936E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.988263E+09 | 7896701.25 |
September | 0.138726E+10 | 0.836076E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731489E+09 | 15990070.07 |
October | 0.138726E+10 | 0.850432E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506056E+09 | 0.123485E+09 |
November | 0.133177E+10 | 0.830329E+09 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151543E+09 | 0.379312E+09 |
December | 0.138726E+10 | 0.878676E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 934000.86 | 0.857124E+09 |
Annual Sum or Average | 0.168137E+11 | 0.102306E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.788139E+10 | 0.350610E+10 |
Minimum of Months | 0.127628E+10 | 0.788057E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85814.44 | 4805765.01 |
Maximum of Months | 0.149825E+10 | 0.909936E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158044E+10 | 0.982630E+09 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.313317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 961231.31 | 0.818468E+09 |
February | 0.300332E+10 | 0.273105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2143224.60 | 0.115326E+10 |
March | 0.352563E+10 | 0.297090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183666E+09 | 0.954414E+09 |
April | 0.326447E+10 | 0.275066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113120E+10 | 0.134424E+09 |
May | 0.339505E+10 | 0.281676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216646E+10 | 50306114.80 |
June | 0.339505E+10 | 0.276716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159504E+10 | 23714599.68 |
July | 0.326447E+10 | 0.266970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166705E+10 | 13869270.28 |
August | 0.352563E+10 | 0.284604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.932902E+09 | 22092767.29 |
September | 0.326447E+10 | 0.272763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571724E+09 | 60517321.26 |
October | 0.326447E+10 | 0.292246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283148E+09 | 0.146130E+09 |
November | 0.313390E+10 | 0.302200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24813863.93 | 0.354551E+09 |
December | 0.326447E+10 | 0.320028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4757931.59 | 0.861629E+09 |
Annual Sum or Average | 0.395654E+11 | 0.345578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.856386E+10 | 0.459338E+10 |
Minimum of Months | 0.300332E+10 | 0.266970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 961231.31 | 13869270.28 |
Maximum of Months | 0.352563E+10 | 0.320028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216646E+10 | 0.115326E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.324493E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21831841.29 | 0.341278E+10 |
February | 0.690763E+10 | 0.284583E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10423144.37 | 0.545610E+10 |
March | 0.810895E+10 | 0.313095E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10071612.61 | 0.609118E+10 |
April | 0.750829E+10 | 0.286422E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150448E+09 | 0.171078E+10 |
May | 0.780862E+10 | 0.290061E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311348E+09 | 0.152734E+10 |
June | 0.780862E+10 | 0.287089E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126059E+09 | 0.103248E+10 |
July | 0.750829E+10 | 0.286143E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14895845.14 | 0.146931E+10 |
August | 0.810895E+10 | 0.305531E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2243182.65 | 0.137218E+10 |
September | 0.750829E+10 | 0.291713E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8944575.75 | 0.140320E+10 |
October | 0.750829E+10 | 0.305620E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2230995.87 | 0.140590E+10 |
November | 0.720796E+10 | 0.306375E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235655E+10 |
December | 0.750829E+10 | 0.328262E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18166626.61 | 0.369231E+10 |
Annual Sum or Average | 0.910005E+11 | 0.360939E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676664E+09 | 0.309301E+11 |
Minimum of Months | 0.690763E+10 | 0.284583E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103248E+10 |
Maximum of Months | 0.810895E+10 | 0.328262E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311348E+09 | 0.609118E+10 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 987.59 | 18-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 | 08-JAN-14:00 | 5858.77 | 05-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 985.47 | 10-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 917.88 | 22-FEB-13:00 | 5010.01 | 02-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 992.32 | 18-MAR-07:10 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3705.83 | 28-MAR-16:10 | 3418.60 | 16-MAR-06:05 |
April | 1680.92 | 01-APR-07:10 | 939.26 | 03-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6152.82 | 27-APR-16:10 | 1855.03 | 10-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 962.50 | 24-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7386.27 | 05-MAY-16:10 | 278.64 | 15-MAY-05:01 |
June | 1680.92 | 01-JUN-07:10 | 979.04 | 24-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7405.72 | 06-JUN-16:10 | 141.76 | 18-JUN-02:13 |
July | 1680.92 | 01-JUL-07:10 | 983.04 | 26-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5298.34 | 07-JUL-16:10 | 141.68 | 26-JUL-05:01 |
August | 1680.92 | 01-AUG-07:10 | 986.33 | 16-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4691.01 | 07-AUG-16:10 | 209.51 | 16-AUG-05:01 |
September | 1680.92 | 01-SEP-07:10 | 990.04 | 09-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4046.78 | 27-SEP-16:10 | 240.80 | 19-SEP-05:01 |
October | 1680.92 | 02-OCT-07:10 | 995.84 | 11-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3973.82 | 02-OCT-16:10 | 2787.29 | 31-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 974.80 | 03-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1806.59 | 09-NOV-13:00 | 4439.46 | 27-NOV-07:03 |
December | 1680.92 | 01-DEC-08:09 | 981.36 | 29-DEC-16:00 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 63.39 | 24-DEC-14:00 | 5661.89 | 21-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 939.26 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 | 141.68 | |||||
Maximum of Months | 1680.92 | 995.84 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 7405.72 | 5858.77 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3336.74 | 18-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.55 | 08-JAN-15:00 | 2635.82 | 31-JAN-08:00 |
February | 3955.50 | 01-FEB-08:09 | 3361.14 | 10-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.90 | 05-FEB-15:00 | 3611.63 | 18-FEB-08:10 |
March | 3955.50 | 01-MAR-08:09 | 3298.84 | 13-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2409.51 | 27-MAR-15:10 | 5566.13 | 24-MAR-24:00 |
April | 3955.50 | 01-APR-07:10 | 3240.45 | 08-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7048.41 | 15-APR-15:10 | 1583.54 | 22-APR-18:00 |
May | 3955.50 | 01-MAY-07:10 | 3267.33 | 03-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7774.82 | 05-MAY-15:10 | 733.19 | 15-MAY-03:10 |
June | 3955.50 | 01-JUN-07:10 | 3420.47 | 24-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7914.81 | 06-JUN-15:10 | 739.82 | 18-JUN-04:25 |
July | 3955.50 | 01-JUL-07:10 | 3389.94 | 27-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3983.49 | 20-JUL-15:10 | 606.37 | 19-JUL-03:00 |
August | 3955.50 | 01-AUG-07:10 | 3467.84 | 16-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2537.43 | 07-AUG-15:10 | 619.61 | 15-AUG-23:46 |
September | 3955.50 | 01-SEP-07:10 | 3491.43 | 07-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2746.36 | 22-SEP-15:10 | 534.57 | 08-SEP-21:00 |
October | 3955.50 | 02-OCT-07:10 | 3309.18 | 11-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3159.66 | 03-OCT-15:10 | 1081.00 | 12-OCT-03:00 |
November | 3955.50 | 01-NOV-07:10 | 3360.04 | 27-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386.12 | 03-NOV-15:10 | 1266.30 | 28-NOV-05:00 |
December | 3955.50 | 01-DEC-08:09 | 3371.69 | 29-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.48 | 24-DEC-14:00 | 2478.86 | 29-DEC-17:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3240.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.55 | 534.57 | ||||
Maximum of Months | 3955.50 | 3491.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7914.81 | 5566.13 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 3374.81 | 03-JAN-16:00 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 840.61 | 12-JAN-15:00 | 10043.71 | 31-JAN-08:70 |
February | 9097.65 | 01-FEB-08:09 | 3325.84 | 10-FEB-08:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 671.79 | 13-FEB-20:00 | 14193.64 | 18-FEB-08:10 |
March | 9097.65 | 01-MAR-08:09 | 3442.79 | 18-MAR-07:10 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 692.97 | 27-MAR-15:00 | 23653.25 | 24-MAR-23:00 |
April | 9097.65 | 01-APR-07:10 | 2988.27 | 01-APR-06:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2367.08 | 15-APR-14:00 | 10259.69 | 22-APR-18:00 |
May | 9097.65 | 01-MAY-07:10 | 3020.31 | 24-MAY-07:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.22 | 27-MAY-15:00 | 7080.68 | 24-MAY-07:20 |
June | 9097.65 | 01-JUN-07:10 | 3339.55 | 24-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1682.76 | 06-JUN-15:00 | 10309.75 | 24-JUN-10:00 |
July | 9097.65 | 01-JUL-07:10 | 3299.76 | 26-JUL-07:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 362.03 | 02-JUL-13:42 | 6041.30 | 18-JUL-12:20 |
August | 9097.65 | 01-AUG-07:10 | 3441.17 | 16-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.98 | 27-AUG-13:55 | 5211.18 | 10-AUG-15:45 |
September | 9097.65 | 01-SEP-07:10 | 3486.18 | 07-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 433.95 | 29-SEP-11:55 | 3220.23 | 08-SEP-21:00 |
October | 9097.65 | 02-OCT-07:10 | 3489.80 | 11-OCT-07:10 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.20 | 15-OCT-11:23 | 6210.12 | 11-OCT-15:20 |
November | 9097.65 | 01-NOV-07:10 | 3481.63 | 27-NOV-16:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 9077.63 | 02-NOV-11:00 |
December | 9097.65 | 01-DEC-08:09 | 3471.28 | 29-DEC-16:00 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1558.25 | 24-DEC-14:00 | 8215.53 | 31-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 2988.27 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3220.23 | |||||
Maximum of Months | 9097.65 | 3489.80 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 2367.08 | 23653.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2523.61 | 14-JAN-16:00 | 1680.92 | 776.59 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.05 |
February | 4934.66 | 22-FEB-16:10 | 1680.92 | 648.70 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 210.86 | 0.00 |
March | 22527.51 | 29-MAR-05:01 | 1479.21 | 407.96 | 4404.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.36 |
April | 23553.42 | 04-APR-05:01 | 1664.11 | 458.96 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.01 |
May | 23215.18 | 08-MAY-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 9.74 | 0.00 |
June | 22443.05 | 13-JUN-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 164.54 | 0.00 |
July | 18740.27 | 07-JUL-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 137.67 | 0.00 |
August | 17674.89 | 09-AUG-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 84.13 | 0.00 |
September | 20973.59 | 27-SEP-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.77 |
October | 23686.47 | 25-OCT-05:01 | 1664.11 | 458.96 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.88 |
November | 22280.92 | 02-NOV-05:02 | 1109.41 | 305.97 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 480.49 |
December | 4549.91 | 01-DEC-15:20 | 1680.92 | 662.38 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2523.61 | 1109.41 | 305.97 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23686.47 | 1849.01 | 776.59 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 210.86 | 480.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4440.03 | 21-JAN-08:70 | 3955.50 | 3143.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.01 |
February | 3910.03 | 02-FEB-08:70 | 3955.50 | 3104.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.70 |
March | 60634.07 | 12-MAR-14:53 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.61 | 0.00 |
April | 68049.18 | 29-APR-17:06 | 0.00 | 1866.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.65 | 0.00 |
May | 68698.74 | 28-MAY-09:43 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1891.46 | 0.00 |
June | 68009.13 | 07-JUN-05:01 | 4351.05 | 2999.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 876.20 | 0.00 |
July | 62783.92 | 07-JUL-05:01 | 4351.05 | 2999.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.00 | 0.00 |
August | 60567.40 | 09-AUG-05:01 | 4351.05 | 2999.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.21 | 0.00 |
September | 62365.16 | 24-SEP-11:43 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 687.38 | 0.00 |
October | 72510.14 | 08-OCT-14:13 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.69 | 0.00 |
November | 28881.37 | 11-NOV-14:45 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.78 | 0.00 |
December | 4916.40 | 21-DEC-08:20 | 3955.50 | 3049.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 760.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3910.03 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 72510.14 | 4351.05 | 3143.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1891.46 | 760.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.58 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.76 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.13 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 780.32 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1163.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1163.16 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.289323E+11 | 21359.23 | 13-JAN-15:00 | 0.168392E+10 | 28261.52 | 03-JAN-06:10 |
February | 0.262537E+11 | 22716.87 | 22-FEB-15:00 | 0.294246E+09 | 9953.92 | 02-FEB-07:10 |
March | 0.337320E+11 | 32085.37 | 28-MAR-15:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.423873E+11 | 39694.43 | 27-APR-15:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.538160E+11 | 45786.76 | 05-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.551821E+11 | 47085.63 | 06-JUN-15:39 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.534275E+11 | 43248.99 | 03-JUL-15:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.520306E+11 | 41078.29 | 07-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.443368E+11 | 37181.40 | 22-SEP-15:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.386064E+11 | 36579.35 | 02-OCT-14:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.305644E+11 | 29545.12 | 08-NOV-15:00 | 5824168.05 | 3873.45 | 27-NOV-07:30 |
December | 0.293901E+11 | 22323.04 | 02-DEC-16:00 | 0.368711E+09 | 10613.19 | 21-DEC-07:19 |
Annual Sum or Average | 0.488659E+12 | 0.235270E+10 | ||||
Minimum of Months | 0.262537E+11 | 21359.23 | 0.00 | 0.00 | ||
Maximum of Months | 0.551821E+11 | 47085.63 | 0.168392E+10 | 28261.52 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.725296E+10 | 0.620743E+10 | 0.112984E+11 | 0.00 | 0.201034E+10 | 0.00 | 0.00 | 0.114313E+09 | 0.00 | 0.00 | 0.00 | 0.204886E+10 | 0.00 |
February | 0.636494E+10 | 0.529096E+10 | 0.103734E+11 | 0.00 | 0.182117E+10 | 0.00 | 0.00 | 0.558519E+09 | 0.00 | 0.00 | 0.00 | 0.184469E+10 | 0.00 |
March | 0.699133E+10 | 0.534618E+10 | 0.121089E+11 | 0.00 | 0.301871E+10 | 0.00 | 0.00 | 0.423846E+10 | 0.00 | 0.00 | 0.00 | 0.202837E+10 | 0.00 |
April | 0.644441E+10 | 0.467301E+10 | 0.112578E+11 | 0.00 | 0.601402E+10 | 0.00 | 0.00 | 0.121275E+11 | 0.00 | 0.00 | 0.00 | 0.187059E+10 | 0.00 |
May | 0.657116E+10 | 0.438887E+10 | 0.117000E+11 | 0.00 | 0.868483E+10 | 0.00 | 0.00 | 0.206025E+11 | 0.00 | 0.00 | 0.00 | 0.186873E+10 | 0.00 |
June | 0.648484E+10 | 0.401967E+10 | 0.116594E+11 | 0.00 | 0.876717E+10 | 0.00 | 0.00 | 0.224814E+11 | 0.00 | 0.00 | 0.00 | 0.176970E+10 | 0.00 |
July | 0.637378E+10 | 0.428276E+10 | 0.112984E+11 | 0.00 | 0.854594E+10 | 0.00 | 0.00 | 0.211487E+11 | 0.00 | 0.00 | 0.00 | 0.177790E+10 | 0.00 |
August | 0.681129E+10 | 0.462737E+10 | 0.121016E+11 | 0.00 | 0.767096E+10 | 0.00 | 0.00 | 0.189937E+11 | 0.00 | 0.00 | 0.00 | 0.182569E+10 | 0.00 |
September | 0.648083E+10 | 0.495788E+10 | 0.112504E+11 | 0.00 | 0.559252E+10 | 0.00 | 0.00 | 0.142591E+11 | 0.00 | 0.00 | 0.00 | 0.179614E+10 | 0.00 |
October | 0.682909E+10 | 0.564431E+10 | 0.113057E+11 | 0.00 | 0.418710E+10 | 0.00 | 0.00 | 0.873497E+10 | 0.00 | 0.00 | 0.00 | 0.190521E+10 | 0.00 |
November | 0.691609E+10 | 0.589531E+10 | 0.108562E+11 | 0.00 | 0.220907E+10 | 0.00 | 0.00 | 0.278312E+10 | 0.00 | 0.00 | 0.00 | 0.190459E+10 | 0.00 |
December | 0.736158E+10 | 0.636312E+10 | 0.112984E+11 | 0.00 | 0.198021E+10 | 0.00 | 0.00 | 0.361125E+09 | 0.00 | 0.00 | 0.00 | 0.202574E+10 | 0.00 |
Annual Sum or Average | 0.808823E+11 | 0.616969E+11 | 0.136508E+12 | 0.00 | 0.605021E+11 | 0.00 | 0.00 | 0.126403E+12 | 0.00 | 0.00 | 0.00 | 0.226662E+11 | 0.00 |
Minimum of Months | 0.636494E+10 | 0.401967E+10 | 0.103734E+11 | 0.00 | 0.182117E+10 | 0.00 | 0.00 | 0.114313E+09 | 0.00 | 0.00 | 0.00 | 0.176970E+10 | 0.00 |
Maximum of Months | 0.736158E+10 | 0.636312E+10 | 0.121089E+11 | 0.00 | 0.876717E+10 | 0.00 | 0.00 | 0.224814E+11 | 0.00 | 0.00 | 0.00 | 0.204886E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.168392E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.294246E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 5824168.05 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.368711E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.235270E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.168392E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 7563.62 | 18-JAN-08:09 | 5520.82 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 2478.45 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 7509.32 | 10-FEB-08:09 | 5520.82 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 2180.47 | 02-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 7689.53 | 18-MAR-07:10 | 5520.82 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 4386.04 | 28-MAR-16:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 6954.25 | 03-APR-07:10 | 5520.82 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 4905.10 | 27-APR-16:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 7045.77 | 24-MAY-07:10 | 5520.82 | 01-MAY-05:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 5754.86 | 05-MAY-16:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 7721.62 | 24-JUN-08:09 | 5520.82 | 01-JUN-05:10 | 10035.17 | 01-JUN-07:10 | 0.00 | 5868.26 | 06-JUN-16:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 7609.57 | 27-JUL-08:09 | 5520.82 | 01-JUL-05:10 | 10035.17 | 01-JUL-07:10 | 0.00 | 5464.75 | 03-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 7876.61 | 16-AUG-08:09 | 5520.82 | 01-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 5154.95 | 07-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 7948.38 | 07-SEP-08:09 | 5520.82 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 4794.22 | 14-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 7760.84 | 11-OCT-07:10 | 5520.82 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 4595.11 | 02-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 7707.04 | 27-NOV-16:00 | 5520.82 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 4298.05 | 01-NOV-12:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 7713.41 | 29-DEC-16:00 | 5520.82 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 2193.69 | 21-DEC-07:19 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 6954.25 | 5520.82 | 10035.17 | 0.00 | 2180.47 | 0.00 | 0.00 | |||||
Maximum of Months | 7948.38 | 5520.82 | 10035.17 | 0.00 | 5868.26 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 824.01 | 14-JAN-15:00 | 0.00 | 0.00 | 0.00 | 1769.27 | 17-JAN-12:20 | 0.00 |
February | 3218.24 | 22-FEB-14:00 | 0.00 | 0.00 | 0.00 | 1767.19 | 01-FEB-12:00 | 0.00 |
March | 11204.02 | 29-MAR-15:09 | 0.00 | 0.00 | 0.00 | 1754.06 | 01-MAR-12:09 | 0.00 |
April | 18659.31 | 27-APR-15:09 | 0.00 | 0.00 | 0.00 | 1729.52 | 01-APR-11:09 | 0.00 |
May | 24002.52 | 05-MAY-16:10 | 0.00 | 0.00 | 0.00 | 1702.29 | 01-MAY-11:50 | 0.00 |
June | 25540.27 | 06-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1678.52 | 01-JUN-11:50 | 0.00 |
July | 22428.93 | 03-JUL-16:10 | 0.00 | 0.00 | 0.00 | 1664.93 | 01-JUL-11:20 | 0.00 |
August | 20406.60 | 07-AUG-16:10 | 0.00 | 0.00 | 0.00 | 1675.48 | 31-AUG-11:00 | 0.00 |
September | 16685.05 | 22-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1697.45 | 30-SEP-11:50 | 0.00 |
October | 15514.34 | 03-OCT-15:09 | 0.00 | 0.00 | 0.00 | 1725.16 | 31-OCT-11:39 | 0.00 |
November | 7305.48 | 09-NOV-13:50 | 0.00 | 0.00 | 0.00 | 1750.24 | 30-NOV-12:00 | 0.00 |
December | 1603.51 | 01-DEC-14:50 | 0.00 | 0.00 | 0.00 | 1765.76 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 824.01 | 0.00 | 0.00 | 0.00 | 1664.93 | 0.00 | ||
Maximum of Months | 25540.27 | 0.00 | 0.00 | 0.00 | 1769.27 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 21359.23 | 13-JAN-15:00 | 6882.00 | 10035.17 | 0.00 | 0.00 | 1992.76 | 0.00 | 0.00 | 714.00 | 0.00 |
February | 22716.87 | 22-FEB-15:00 | 6029.29 | 10035.17 | 0.00 | 0.00 | 1992.76 | 0.00 | 0.00 | 2933.15 | 0.00 |
March | 32085.37 | 28-MAR-15:50 | 5210.69 | 10035.17 | 0.00 | 0.00 | 4298.05 | 0.00 | 0.00 | 10955.99 | 0.00 |
April | 39694.43 | 27-APR-15:20 | 4642.06 | 10035.17 | 0.00 | 0.00 | 4846.33 | 0.00 | 0.00 | 18592.43 | 0.00 |
May | 45786.76 | 05-MAY-15:00 | 5261.28 | 10035.17 | 0.00 | 0.00 | 5549.99 | 0.00 | 0.00 | 23363.75 | 0.00 |
June | 47085.63 | 06-JUN-15:39 | 4838.19 | 10035.17 | 0.00 | 0.00 | 5731.52 | 0.00 | 0.00 | 24910.45 | 0.00 |
July | 43248.99 | 03-JUL-15:50 | 4515.71 | 10035.17 | 0.00 | 0.00 | 5313.13 | 0.00 | 0.00 | 21946.41 | 0.00 |
August | 41078.29 | 07-AUG-14:00 | 4682.10 | 10035.17 | 0.00 | 0.00 | 4977.31 | 0.00 | 0.00 | 19736.38 | 0.00 |
September | 37181.40 | 22-SEP-15:30 | 4468.48 | 10035.17 | 0.00 | 0.00 | 4542.84 | 0.00 | 0.00 | 16560.53 | 0.00 |
October | 36579.35 | 02-OCT-14:50 | 5467.49 | 10035.17 | 0.00 | 0.00 | 4449.97 | 0.00 | 0.00 | 14950.67 | 0.00 |
November | 29545.12 | 08-NOV-15:00 | 7173.49 | 10035.17 | 0.00 | 0.00 | 4298.05 | 0.00 | 0.00 | 6333.55 | 0.00 |
December | 22323.04 | 02-DEC-16:00 | 7599.35 | 10035.17 | 0.00 | 0.00 | 1992.76 | 0.00 | 0.00 | 1105.49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 21359.23 | 4468.48 | 10035.17 | 0.00 | 0.00 | 1992.76 | 0.00 | 0.00 | 714.00 | 0.00 | |
Maximum of Months | 47085.63 | 7599.35 | 10035.17 | 0.00 | 0.00 | 5731.52 | 0.00 | 0.00 | 24910.45 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 28261.52 | 03-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 9953.92 | 02-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 3873.45 | 27-NOV-07:30 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 10613.19 | 21-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 28261.52 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 20.29 | 2.17 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
February | 0.17 | 20.45 | 0.17 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.47 | 0.33 | 24.47 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 25.00 | 5.00 | 24.84 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 25.74 | 8.67 | 25.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 25.66 | 8.33 | 25.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 25.69 | 9.67 | 25.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 25.38 | 9.33 | 25.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 25.01 | 8.17 | 25.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.65 | 4.83 | 24.65 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.54 | 0.50 | 24.54 |
December | 0.17 | 20.46 | 0.17 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
Annual Sum or Average | 2.50 | 20.31 | 2.50 | 20.31 | 58.67 | 24.99 | 54.83 | 25.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.29 | 0.00 | 20.29 |
Maximum of Months | 2.17 | 20.46 | 2.17 | 20.46 | 10.50 | 25.74 | 9.67 | 25.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.39 | 0.00 | 27.39 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 31.17 | 27.59 | 0.00 | 27.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 65.17 | 27.69 | 0.83 | 27.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 73.00 | 27.68 | 1.83 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 70.50 | 27.63 | 1.17 | 27.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 42.67 | 27.52 | 0.50 | 27.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 | 27.47 | 0.00 | 27.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 27.54 | 0.00 | 27.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.31 | 0.00 | 27.31 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 14.99 | 0.00 | 14.99 | 334.17 | 27.58 | 4.33 | 27.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 14.99 | 0.00 | 14.99 | 73.00 | 27.69 | 1.83 | 27.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 22.58 | 63.67 | 22.31 | 63.67 | 22.13 |
February | 211.83 | 23.10 | 22.33 | 23.05 | 10.00 | 22.97 |
March | 46.50 | 23.49 | 187.33 | 23.82 | 0.00 | 23.82 |
April | 0.00 | 0.00 | 287.50 | 23.92 | 0.00 | 23.92 |
May | 14.00 | 24.11 | 312.00 | 23.94 | 14.00 | 23.95 |
June | 52.50 | 24.06 | 312.00 | 23.96 | 52.50 | 23.97 |
July | 105.00 | 24.04 | 300.00 | 23.97 | 105.00 | 23.99 |
August | 130.33 | 24.02 | 324.00 | 23.97 | 130.33 | 23.98 |
September | 72.17 | 24.01 | 300.00 | 23.95 | 72.17 | 23.96 |
October | 3.83 | 23.98 | 296.83 | 23.92 | 3.83 | 23.92 |
November | 41.83 | 23.34 | 147.50 | 23.78 | 0.00 | 23.78 |
December | 280.17 | 23.14 | 10.67 | 23.07 | 10.67 | 22.99 |
Annual Sum or Average | 1258.17 | 23.29 | 2563.83 | 23.66 | 462.17 | 23.64 |
Minimum of Months | 0.00 | 0.00 | 10.67 | 22.31 | 0.00 | 22.13 |
Maximum of Months | 300.00 | 24.11 | 324.00 | 23.97 | 130.33 | 23.99 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.39 | 137.33 | 19.76 | 137.33 | 19.43 |
February | 177.17 | 21.81 | 117.33 | 22.62 | 38.83 | 22.28 |
March | 141.83 | 26.02 | 275.83 | 26.27 | 114.50 | 26.37 |
April | 228.67 | 26.70 | 300.00 | 26.69 | 228.67 | 26.69 |
May | 306.00 | 26.71 | 312.00 | 26.71 | 306.00 | 26.71 |
June | 308.33 | 26.71 | 312.00 | 26.71 | 308.33 | 26.71 |
July | 299.83 | 26.71 | 300.00 | 26.71 | 299.83 | 26.71 |
August | 323.33 | 26.71 | 324.00 | 26.71 | 323.33 | 26.71 |
September | 289.17 | 26.71 | 300.00 | 26.72 | 289.17 | 26.72 |
October | 226.00 | 26.70 | 300.00 | 26.64 | 226.00 | 26.66 |
November | 99.33 | 25.33 | 228.67 | 26.03 | 62.67 | 26.14 |
December | 250.17 | 21.86 | 81.00 | 21.74 | 55.83 | 21.40 |
Annual Sum or Average | 2949.83 | 25.28 | 2988.17 | 25.64 | 2390.50 | 25.73 |
Minimum of Months | 99.33 | 20.39 | 81.00 | 19.76 | 38.83 | 19.43 |
Maximum of Months | 323.33 | 26.71 | 324.00 | 26.72 | 323.33 | 26.72 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 19.56 | 162.67 | 18.90 | 162.67 | 18.58 |
February | 188.67 | 21.83 | 133.00 | 22.53 | 63.50 | 22.25 |
March | 237.50 | 28.93 | 291.33 | 28.76 | 217.83 | 28.97 |
April | 298.33 | 32.40 | 300.00 | 32.38 | 298.33 | 32.39 |
May | 312.00 | 35.09 | 312.00 | 35.09 | 312.00 | 35.09 |
June | 312.00 | 35.22 | 312.00 | 35.22 | 312.00 | 35.22 |
July | 300.00 | 32.88 | 300.00 | 32.88 | 300.00 | 32.88 |
August | 324.00 | 31.71 | 324.00 | 31.71 | 324.00 | 31.71 |
September | 300.00 | 31.16 | 300.00 | 31.16 | 300.00 | 31.16 |
October | 282.50 | 30.32 | 300.00 | 30.20 | 282.50 | 30.24 |
November | 189.50 | 27.73 | 237.17 | 27.81 | 154.00 | 28.10 |
December | 249.33 | 21.38 | 110.33 | 21.25 | 75.83 | 20.81 |
Annual Sum or Average | 3293.83 | 29.48 | 3082.50 | 29.88 | 2802.67 | 30.14 |
Minimum of Months | 188.67 | 19.56 | 110.33 | 18.90 | 63.50 | 18.58 |
Maximum of Months | 324.00 | 35.22 | 324.00 | 35.22 | 324.00 | 35.22 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.457707E+09 | 0.114313E+09 | 87.42 | 0.411411E+09 | 46295898.04 | 0.00 | 0.30 | 14-JAN-16:00 | 0.00 | 01-JAN-00:10 | 3370.61 | 14-JAN-16:00 | 2729.68 | 14-JAN-16:00 | 642.12 | 14-JAN-15:40 | 824.01 | 14-JAN-16:00 | 0.00 | 01-JAN-00:10 |
February | 0.199961E+10 | 0.490146E+09 | 174.22 | 0.175448E+10 | 0.245133E+09 | 0.00 | 0.58 | 24-FEB-15:50 | 0.00 | 01-FEB-00:10 | 6647.63 | 24-FEB-15:50 | 5795.03 | 22-FEB-15:30 | 1605.26 | 25-FEB-17:00 | 1621.03 | 24-FEB-15:50 | 0.00 | 01-FEB-00:10 |
March | 0.643047E+10 | 0.158945E+10 | 288.29 | 0.567563E+10 | 0.754842E+09 | 0.00 | 1.00 | 07-MAR-06:03 | 0.00 | 01-MAR-00:10 | 27343.88 | 11-MAR-06:01 | 24417.75 | 27-MAR-05:02 | 6832.54 | 11-MAR-06:03 | 5854.30 | 11-MAR-06:01 | 0.00 | 01-MAR-00:10 |
April | 0.102172E+11 | 0.268909E+10 | 298.79 | 0.929081E+10 | 0.926377E+09 | 0.00 | 1.00 | 01-APR-05:01 | 0.00 | 01-APR-00:10 | 27511.39 | 03-APR-05:01 | 25348.72 | 04-APR-05:01 | 6577.01 | 03-APR-05:04 | 6088.52 | 27-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.148543E+11 | 0.405897E+10 | 329.40 | 0.122641E+11 | 0.259023E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 30215.49 | 24-MAY-05:01 | 25400.43 | 08-MAY-05:01 | 13384.41 | 24-MAY-05:06 | 6443.11 | 03-MAY-16:10 | 0.00 | 01-MAY-00:10 |
June | 0.167448E+11 | 0.448155E+10 | 326.92 | 0.126112E+11 | 0.413363E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 30945.82 | 26-JUN-05:01 | 25024.88 | 13-JUN-05:01 | 16773.72 | 26-JUN-05:05 | 6915.41 | 22-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.175205E+11 | 0.435504E+10 | 324.67 | 0.113425E+11 | 0.617796E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 31311.43 | 19-JUL-05:01 | 21042.32 | 07-JUL-05:01 | 17868.35 | 20-JUL-05:07 | 6663.32 | 06-JUL-05:01 | 0.00 | 01-JUL-00:10 |
August | 0.182784E+11 | 0.440120E+10 | 329.70 | 0.113911E+11 | 0.688733E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 31524.79 | 16-AUG-05:01 | 19726.61 | 09-AUG-05:01 | 16953.42 | 19-AUG-05:05 | 6618.27 | 28-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.146385E+11 | 0.351362E+10 | 300.47 | 0.976983E+10 | 0.486865E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 31609.68 | 09-SEP-05:01 | 22481.20 | 27-SEP-05:01 | 17844.39 | 05-SEP-05:06 | 6508.52 | 05-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 0.992299E+10 | 0.242681E+10 | 297.08 | 0.816181E+10 | 0.176118E+10 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 29306.40 | 12-OCT-05:01 | 25078.33 | 25-OCT-05:01 | 11656.79 | 12-OCT-05:04 | 6146.83 | 12-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.518801E+10 | 0.126262E+10 | 244.70 | 0.462315E+10 | 0.564859E+09 | 0.00 | 1.00 | 01-NOV-05:02 | 0.00 | 01-NOV-00:10 | 26204.41 | 09-NOV-06:02 | 24035.02 | 03-NOV-05:02 | 4975.67 | 09-NOV-06:02 | 5661.17 | 09-NOV-06:02 | 0.00 | 01-NOV-00:10 |
December | 0.145065E+10 | 0.356987E+09 | 164.25 | 0.130274E+10 | 0.147904E+09 | 0.00 | 0.47 | 02-DEC-15:10 | 0.00 | 01-DEC-00:10 | 5198.80 | 02-DEC-15:10 | 5012.86 | 02-DEC-15:00 | 713.27 | 16-DEC-16:00 | 1241.30 | 02-DEC-15:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.117703E+12 | 0.297398E+11 | 3165.91 | 0.885987E+11 | 0.291044E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.457707E+09 | 0.114313E+09 | 87.42 | 0.411411E+09 | 46295898.04 | 0.00 | 0.30 | 0.00 | 3370.61 | 2729.68 | 642.12 | 824.01 | 0.00 | |||||||
Maximum of Months | 0.182784E+11 | 0.448155E+10 | 329.70 | 0.126112E+11 | 0.688733E+10 | 0.00 | 1.00 | 0.00 | 31609.68 | 25400.43 | 17868.35 | 6915.41 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.234194E+09 | 68372790.55 | 20.17 | 0.202746E+09 | 31448206.81 | 0.00 | 0.15 | 22-FEB-15:00 | 0.00 | 01-FEB-00:10 | 5676.78 | 22-FEB-15:00 | 4948.30 | 22-FEB-15:00 | 1106.50 | 24-FEB-15:00 | 1674.91 | 22-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.902371E+10 | 0.264901E+10 | 216.91 | 0.778762E+10 | 0.123608E+10 | 0.00 | 1.00 | 12-MAR-12:13 | 0.00 | 01-MAR-00:10 | 72683.27 | 12-MAR-14:53 | 68721.28 | 12-MAR-14:53 | 7511.04 | 10-MAR-18:20 | 20244.59 | 12-MAR-14:53 | 0.00 | 01-MAR-00:10 |
April | 0.307554E+11 | 0.943844E+10 | 436.83 | 0.280660E+11 | 0.268940E+10 | 0.00 | 1.00 | 01-APR-17:08 | 0.00 | 01-APR-00:10 | 83020.92 | 18-APR-17:06 | 78336.12 | 16-APR-11:32 | 11321.15 | 18-APR-17:06 | 25707.28 | 16-APR-14:52 | 0.00 | 01-APR-00:10 |
May | 0.529430E+11 | 0.165435E+11 | 569.06 | 0.445910E+11 | 0.835196E+10 | 0.00 | 1.00 | 01-MAY-11:30 | 0.00 | 01-MAY-00:25 | 93703.03 | 24-MAY-05:01 | 78692.58 | 07-MAY-10:23 | 39439.83 | 24-MAY-05:01 | 26790.40 | 07-MAY-15:02 | 0.00 | 01-MAY-00:10 |
June | 0.587199E+11 | 0.179998E+11 | 563.98 | 0.453628E+11 | 0.133572E+11 | 0.00 | 1.00 | 01-JUN-05:07 | 0.00 | 01-JUN-00:15 | 97290.17 | 29-JUN-05:07 | 78157.82 | 04-JUN-11:43 | 36871.89 | 29-JUN-05:07 | 27490.12 | 10-JUN-17:05 | 0.00 | 01-JUN-00:10 |
July | 0.587135E+11 | 0.167937E+11 | 574.56 | 0.380550E+11 | 0.206585E+11 | 0.00 | 1.00 | 01-JUL-00:23 | 0.00 | 01-JUL-00:13 | 100697.10 | 25-JUL-05:06 | 74707.78 | 04-JUL-17:02 | 53116.46 | 19-JUL-05:01 | 27007.55 | 02-JUL-15:42 | 0.00 | 01-JUL-00:10 |
August | 0.525284E+11 | 0.145926E+11 | 565.13 | 0.322460E+11 | 0.202824E+11 | 0.00 | 1.00 | 01-AUG-05:06 | 0.00 | 01-AUG-00:15 | 98076.74 | 18-AUG-17:08 | 69168.16 | 06-AUG-15:43 | 43602.96 | 16-AUG-17:10 | 26080.77 | 07-AUG-17:05 | 0.00 | 01-AUG-00:10 |
September | 0.383490E+11 | 0.107455E+11 | 487.06 | 0.252359E+11 | 0.131131E+11 | 0.00 | 1.00 | 01-SEP-05:06 | 0.00 | 01-SEP-00:15 | 101832.24 | 06-SEP-05:01 | 72208.07 | 26-SEP-17:06 | 43770.40 | 06-SEP-05:01 | 25671.03 | 14-SEP-17:06 | 0.00 | 01-SEP-00:10 |
October | 0.217834E+11 | 0.630816E+10 | 341.30 | 0.178560E+11 | 0.392742E+10 | 0.00 | 1.00 | 01-OCT-10:03 | 0.00 | 01-OCT-00:15 | 81610.54 | 09-OCT-13:02 | 80839.59 | 08-OCT-14:53 | 15250.57 | 13-OCT-17:10 | 24294.80 | 01-OCT-14:43 | 0.00 | 01-OCT-00:10 |
November | 0.525757E+10 | 0.152050E+10 | 162.31 | 0.451899E+10 | 0.738585E+09 | 0.00 | 0.84 | 11-NOV-14:45 | 0.00 | 01-NOV-00:10 | 34087.37 | 11-NOV-14:45 | 31599.44 | 11-NOV-14:45 | 4929.30 | 11-NOV-10:43 | 9246.37 | 11-NOV-14:45 | 0.00 | 01-NOV-00:10 |
December | 14474898.31 | 4137329.48 | 4.00 | 13723307.58 | 751590.73 | 0.00 | 0.04 | 01-DEC-14:40 | 0.00 | 01-DEC-00:10 | 1461.27 | 01-DEC-14:40 | 1385.94 | 01-DEC-14:40 | 77.41 | 01-DEC-15:00 | 416.86 | 01-DEC-14:40 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.328323E+12 | 0.966636E+11 | 3941.29 | 0.243936E+12 | 0.843868E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.587199E+11 | 0.179998E+11 | 574.56 | 0.453628E+11 | 0.206585E+11 | 0.00 | 1.00 | 0.00 | 101832.24 | 80839.59 | 53116.46 | 27490.12 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 53.26 | 20.71 | 32.56 | 72.36 | 83.77 | 0.33 | 0.00 | 0.00 |
February | 60.84 | 22.39 | 38.46 | 91.56 | 72.11 | 0.00 | 0.00 | 0.00 |
March | 79.31 | 31.87 | 47.44 | 138.41 | 51.87 | 0.00 | 0.00 | 0.00 |
April | 95.86 | 44.87 | 50.99 | 202.82 | 23.08 | 0.00 | 0.00 | 0.00 |
May | 90.80 | 38.45 | 52.35 | 219.82 | 7.02 | 0.00 | 0.00 | 0.00 |
June | 85.65 | 33.44 | 52.22 | 216.52 | 5.03 | 0.00 | 0.00 | 0.00 |
July | 63.32 | 12.28 | 51.04 | 157.17 | 2.82 | 0.00 | 0.00 | 0.00 |
August | 58.07 | 10.19 | 47.87 | 135.93 | 6.30 | 0.00 | 0.00 | 0.00 |
September | 64.14 | 18.98 | 45.16 | 134.15 | 16.26 | 0.00 | 0.00 | 0.00 |
October | 66.57 | 26.49 | 40.09 | 128.04 | 49.04 | 0.00 | 0.00 | 0.00 |
November | 60.22 | 25.65 | 34.57 | 97.81 | 79.58 | 0.00 | 0.00 | 0.00 |
December | 51.60 | 19.70 | 31.89 | 68.76 | 91.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 69.12 | 25.39 | 43.74 | 138.73 | 40.57 | 0.33 | 0.00 | 0.00 |
Minimum of Months | 51.60 | 10.19 | 31.89 | 68.76 | 2.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 95.86 | 44.87 | 52.35 | 219.82 | 91.71 | 0.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 53.26 | 20.71 | 32.56 | 72.36 | 83.77 | 0.33 | 0.00 | 0.00 |
February | 60.84 | 22.39 | 38.46 | 91.56 | 72.11 | 0.00 | 0.00 | 0.00 |
March | 79.31 | 31.87 | 47.44 | 138.41 | 51.87 | 0.00 | 0.00 | 0.00 |
April | 95.86 | 44.87 | 50.99 | 202.82 | 23.08 | 0.00 | 0.00 | 0.00 |
May | 90.80 | 38.45 | 52.35 | 219.82 | 7.02 | 0.00 | 0.00 | 0.00 |
June | 85.65 | 33.44 | 52.22 | 216.52 | 5.03 | 0.00 | 0.00 | 0.00 |
July | 63.32 | 12.28 | 51.04 | 157.17 | 2.82 | 0.00 | 0.00 | 0.00 |
August | 58.07 | 10.19 | 47.87 | 135.93 | 6.30 | 0.00 | 0.00 | 0.00 |
September | 64.14 | 18.98 | 45.16 | 134.15 | 16.26 | 0.00 | 0.00 | 0.00 |
October | 66.57 | 26.49 | 40.09 | 128.04 | 49.04 | 0.00 | 0.00 | 0.00 |
November | 60.22 | 25.65 | 34.57 | 97.81 | 79.58 | 0.00 | 0.00 | 0.00 |
December | 51.60 | 19.70 | 31.89 | 68.76 | 91.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 69.12 | 25.39 | 43.74 | 138.73 | 40.57 | 0.33 | 0.00 | 0.00 |
Minimum of Months | 51.60 | 10.19 | 31.89 | 68.76 | 2.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 95.86 | 44.87 | 52.35 | 219.82 | 91.71 | 0.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.83 | 0.00 | 14.83 | 11.86 | 49.86 | 0.50 | 0.00 | 0.00 |
February | 17.58 | 0.00 | 17.58 | 19.22 | 42.43 | 0.00 | 0.00 | 0.00 |
March | 21.19 | 0.00 | 21.19 | 32.88 | 30.32 | 0.00 | 0.00 | 0.00 |
April | 23.05 | 0.11 | 22.93 | 55.19 | 13.20 | 0.00 | 0.00 | 0.00 |
May | 25.55 | 0.79 | 24.76 | 75.76 | 4.00 | 0.00 | 0.00 | 0.00 |
June | 26.30 | 0.91 | 25.39 | 80.88 | 2.91 | 0.00 | 0.00 | 0.00 |
July | 26.05 | 0.45 | 25.60 | 70.96 | 1.58 | 0.00 | 0.00 | 0.00 |
August | 23.95 | 0.13 | 23.82 | 60.07 | 3.62 | 0.00 | 0.00 | 0.00 |
September | 21.27 | 0.00 | 21.27 | 47.11 | 9.38 | 0.00 | 0.00 | 0.00 |
October | 18.43 | 0.00 | 18.43 | 34.43 | 28.51 | 0.00 | 0.00 | 0.00 |
November | 15.61 | 0.00 | 15.61 | 18.70 | 46.72 | 0.00 | 0.00 | 0.00 |
December | 14.46 | 0.00 | 14.46 | 11.06 | 54.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20.71 | 0.20 | 20.50 | 43.29 | 23.87 | 0.50 | 0.00 | 0.00 |
Minimum of Months | 14.46 | 0.00 | 14.46 | 11.06 | 1.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 26.30 | 0.91 | 25.60 | 80.88 | 54.96 | 0.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.83 | 0.00 | 14.83 | 11.86 | 49.86 | 0.50 | 0.00 | 0.00 |
February | 17.58 | 0.00 | 17.58 | 19.22 | 42.43 | 0.00 | 0.00 | 0.00 |
March | 21.19 | 0.00 | 21.19 | 32.88 | 30.32 | 0.00 | 0.00 | 0.00 |
April | 23.04 | 0.11 | 22.93 | 55.19 | 13.20 | 0.00 | 0.00 | 0.00 |
May | 25.55 | 0.79 | 24.76 | 75.76 | 4.00 | 0.00 | 0.00 | 0.00 |
June | 26.30 | 0.91 | 25.39 | 80.88 | 2.91 | 0.00 | 0.00 | 0.00 |
July | 26.05 | 0.45 | 25.60 | 70.96 | 1.58 | 0.00 | 0.00 | 0.00 |
August | 23.95 | 0.13 | 23.82 | 60.06 | 3.62 | 0.00 | 0.00 | 0.00 |
September | 21.27 | 0.00 | 21.27 | 47.11 | 9.38 | 0.00 | 0.00 | 0.00 |
October | 18.43 | 0.00 | 18.43 | 34.43 | 28.51 | 0.00 | 0.00 | 0.00 |
November | 15.61 | 0.00 | 15.61 | 18.70 | 46.72 | 0.00 | 0.00 | 0.00 |
December | 14.46 | 0.00 | 14.46 | 11.06 | 54.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20.70 | 0.20 | 20.50 | 43.29 | 23.87 | 0.50 | 0.00 | 0.00 |
Minimum of Months | 14.46 | 0.00 | 14.46 | 11.06 | 1.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 26.30 | 0.91 | 25.60 | 80.88 | 54.96 | 0.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.35 | 16.15 | 14.20 | 44.48 | 38.10 | 60.33 | 0.00 | 0.00 |
February | 38.36 | 21.34 | 17.02 | 59.02 | 34.91 | 0.00 | 0.00 | 0.00 |
March | 51.92 | 31.14 | 20.78 | 85.01 | 29.82 | 0.00 | 0.00 | 0.00 |
April | 66.86 | 46.87 | 19.99 | 120.13 | 20.08 | 0.00 | 0.00 | 0.00 |
May | 71.00 | 49.18 | 21.81 | 133.39 | 10.79 | 0.00 | 0.00 | 0.00 |
June | 66.45 | 42.41 | 24.04 | 126.94 | 7.35 | 0.00 | 0.00 | 0.00 |
July | 46.44 | 16.77 | 29.67 | 90.03 | 5.04 | 0.00 | 0.00 | 0.00 |
August | 40.10 | 11.53 | 28.57 | 76.82 | 7.27 | 0.00 | 0.00 | 0.00 |
September | 41.11 | 17.43 | 23.67 | 73.14 | 13.50 | 0.00 | 0.00 | 0.00 |
October | 46.15 | 29.31 | 16.83 | 78.80 | 29.76 | 0.00 | 0.00 | 0.00 |
November | 38.15 | 25.03 | 13.12 | 59.16 | 41.21 | 0.00 | 0.00 | 0.00 |
December | 29.40 | 15.74 | 13.65 | 41.96 | 42.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.20 | 26.89 | 20.31 | 82.46 | 23.33 | 60.33 | 0.00 | 0.00 |
Minimum of Months | 29.40 | 11.53 | 13.12 | 41.96 | 5.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.00 | 49.18 | 29.67 | 133.39 | 42.88 | 60.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.35 | 16.15 | 14.20 | 44.48 | 38.10 | 60.33 | 0.00 | 0.00 |
February | 38.36 | 21.34 | 17.02 | 59.02 | 34.91 | 0.00 | 0.00 | 0.00 |
March | 51.92 | 31.14 | 20.78 | 85.01 | 29.82 | 0.00 | 0.00 | 0.00 |
April | 66.86 | 46.87 | 19.99 | 120.13 | 20.08 | 0.00 | 0.00 | 0.00 |
May | 71.00 | 49.18 | 21.81 | 133.39 | 10.79 | 0.00 | 0.00 | 0.00 |
June | 66.45 | 42.41 | 24.04 | 126.94 | 7.35 | 0.00 | 0.00 | 0.00 |
July | 46.44 | 16.77 | 29.67 | 90.03 | 5.04 | 0.00 | 0.00 | 0.00 |
August | 40.10 | 11.53 | 28.57 | 76.82 | 7.27 | 0.00 | 0.00 | 0.00 |
September | 41.11 | 17.43 | 23.67 | 73.14 | 13.50 | 0.00 | 0.00 | 0.00 |
October | 46.15 | 29.31 | 16.83 | 78.80 | 29.76 | 0.00 | 0.00 | 0.00 |
November | 38.15 | 25.03 | 13.12 | 59.16 | 41.21 | 0.00 | 0.00 | 0.00 |
December | 29.40 | 15.74 | 13.65 | 41.96 | 42.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.20 | 26.89 | 20.31 | 82.46 | 23.33 | 60.33 | 0.00 | 0.00 |
Minimum of Months | 29.40 | 11.53 | 13.12 | 41.96 | 5.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.00 | 49.18 | 29.67 | 133.39 | 42.88 | 60.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.35 | 16.15 | 14.20 | 44.48 | 38.10 | 60.33 | 0.00 | 0.00 |
February | 38.36 | 21.34 | 17.02 | 59.02 | 34.91 | 0.00 | 0.00 | 0.00 |
March | 51.92 | 31.14 | 20.78 | 85.01 | 29.82 | 0.00 | 0.00 | 0.00 |
April | 66.86 | 46.87 | 19.99 | 120.13 | 20.08 | 0.00 | 0.00 | 0.00 |
May | 71.00 | 49.18 | 21.81 | 133.39 | 10.79 | 0.00 | 0.00 | 0.00 |
June | 66.45 | 42.41 | 24.04 | 126.94 | 7.35 | 0.00 | 0.00 | 0.00 |
July | 46.44 | 16.77 | 29.67 | 90.03 | 5.04 | 0.00 | 0.00 | 0.00 |
August | 40.10 | 11.53 | 28.57 | 76.82 | 7.27 | 0.00 | 0.00 | 0.00 |
September | 41.11 | 17.43 | 23.67 | 73.14 | 13.50 | 0.00 | 0.00 | 0.00 |
October | 46.15 | 29.31 | 16.83 | 78.80 | 29.76 | 0.00 | 0.00 | 0.00 |
November | 38.15 | 25.03 | 13.12 | 59.16 | 41.21 | 0.00 | 0.00 | 0.00 |
December | 29.40 | 15.74 | 13.65 | 41.96 | 42.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.20 | 26.89 | 20.31 | 82.46 | 23.33 | 60.33 | 0.00 | 0.00 |
Minimum of Months | 29.40 | 11.53 | 13.12 | 41.96 | 5.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.00 | 49.18 | 29.67 | 133.39 | 42.88 | 60.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.35 | 16.15 | 14.20 | 44.48 | 38.10 | 60.33 | 0.00 | 0.00 |
February | 38.36 | 21.34 | 17.02 | 59.02 | 34.91 | 0.00 | 0.00 | 0.00 |
March | 51.92 | 31.14 | 20.78 | 85.01 | 29.82 | 0.00 | 0.00 | 0.00 |
April | 66.86 | 46.87 | 19.99 | 120.13 | 20.08 | 0.00 | 0.00 | 0.00 |
May | 71.00 | 49.18 | 21.81 | 133.39 | 10.79 | 0.00 | 0.00 | 0.00 |
June | 66.45 | 42.41 | 24.04 | 126.94 | 7.35 | 0.00 | 0.00 | 0.00 |
July | 46.44 | 16.77 | 29.67 | 90.03 | 5.04 | 0.00 | 0.00 | 0.00 |
August | 40.10 | 11.53 | 28.57 | 76.82 | 7.27 | 0.00 | 0.00 | 0.00 |
September | 41.11 | 17.43 | 23.67 | 73.14 | 13.50 | 0.00 | 0.00 | 0.00 |
October | 46.15 | 29.31 | 16.83 | 78.80 | 29.76 | 0.00 | 0.00 | 0.00 |
November | 38.15 | 25.03 | 13.12 | 59.16 | 41.21 | 0.00 | 0.00 | 0.00 |
December | 29.40 | 15.74 | 13.65 | 41.96 | 42.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.20 | 26.89 | 20.31 | 82.46 | 23.33 | 60.33 | 0.00 | 0.00 |
Minimum of Months | 29.40 | 11.53 | 13.12 | 41.96 | 5.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.00 | 49.18 | 29.67 | 133.39 | 42.88 | 60.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.35 | 16.15 | 14.20 | 44.48 | 38.10 | 60.33 | 0.00 | 0.00 |
February | 38.36 | 21.34 | 17.02 | 59.02 | 34.91 | 0.00 | 0.00 | 0.00 |
March | 51.92 | 31.14 | 20.78 | 85.01 | 29.82 | 0.00 | 0.00 | 0.00 |
April | 66.86 | 46.87 | 19.99 | 120.13 | 20.08 | 0.00 | 0.00 | 0.00 |
May | 71.00 | 49.18 | 21.81 | 133.39 | 10.79 | 0.00 | 0.00 | 0.00 |
June | 66.45 | 42.41 | 24.04 | 126.94 | 7.35 | 0.00 | 0.00 | 0.00 |
July | 46.44 | 16.77 | 29.67 | 90.03 | 5.04 | 0.00 | 0.00 | 0.00 |
August | 40.10 | 11.53 | 28.57 | 76.82 | 7.27 | 0.00 | 0.00 | 0.00 |
September | 41.11 | 17.43 | 23.67 | 73.14 | 13.50 | 0.00 | 0.00 | 0.00 |
October | 46.15 | 29.31 | 16.83 | 78.80 | 29.76 | 0.00 | 0.00 | 0.00 |
November | 38.15 | 25.03 | 13.12 | 59.16 | 41.21 | 0.00 | 0.00 | 0.00 |
December | 29.40 | 15.74 | 13.65 | 41.96 | 42.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.20 | 26.89 | 20.31 | 82.46 | 23.33 | 60.33 | 0.00 | 0.00 |
Minimum of Months | 29.40 | 11.53 | 13.12 | 41.96 | 5.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.00 | 49.18 | 29.67 | 133.39 | 42.88 | 60.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.35 | 16.15 | 14.20 | 44.48 | 38.10 | 60.33 | 0.00 | 0.00 |
February | 38.36 | 21.34 | 17.02 | 59.02 | 34.91 | 0.00 | 0.00 | 0.00 |
March | 51.92 | 31.14 | 20.78 | 85.01 | 29.82 | 0.00 | 0.00 | 0.00 |
April | 66.86 | 46.87 | 19.99 | 120.13 | 20.08 | 0.00 | 0.00 | 0.00 |
May | 71.00 | 49.18 | 21.81 | 133.39 | 10.79 | 0.00 | 0.00 | 0.00 |
June | 66.45 | 42.41 | 24.04 | 126.94 | 7.35 | 0.00 | 0.00 | 0.00 |
July | 46.44 | 16.77 | 29.67 | 90.03 | 5.04 | 0.00 | 0.00 | 0.00 |
August | 40.10 | 11.53 | 28.57 | 76.82 | 7.27 | 0.00 | 0.00 | 0.00 |
September | 41.11 | 17.43 | 23.67 | 73.14 | 13.50 | 0.00 | 0.00 | 0.00 |
October | 46.15 | 29.31 | 16.83 | 78.80 | 29.76 | 0.00 | 0.00 | 0.00 |
November | 38.15 | 25.03 | 13.12 | 59.16 | 41.21 | 0.00 | 0.00 | 0.00 |
December | 29.40 | 15.74 | 13.65 | 41.96 | 42.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.20 | 26.89 | 20.31 | 82.46 | 23.33 | 60.33 | 0.00 | 0.00 |
Minimum of Months | 29.40 | 11.53 | 13.12 | 41.96 | 5.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.00 | 49.18 | 29.67 | 133.39 | 42.88 | 60.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.35 | 16.15 | 14.20 | 44.48 | 38.10 | 60.33 | 0.00 | 0.00 |
February | 38.36 | 21.34 | 17.02 | 59.02 | 34.91 | 0.00 | 0.00 | 0.00 |
March | 51.92 | 31.14 | 20.78 | 85.01 | 29.82 | 0.00 | 0.00 | 0.00 |
April | 66.86 | 46.87 | 19.99 | 120.13 | 20.08 | 0.00 | 0.00 | 0.00 |
May | 71.00 | 49.18 | 21.81 | 133.39 | 10.79 | 0.00 | 0.00 | 0.00 |
June | 66.45 | 42.41 | 24.04 | 126.94 | 7.35 | 0.00 | 0.00 | 0.00 |
July | 46.44 | 16.77 | 29.67 | 90.03 | 5.04 | 0.00 | 0.00 | 0.00 |
August | 40.10 | 11.53 | 28.57 | 76.82 | 7.27 | 0.00 | 0.00 | 0.00 |
September | 41.11 | 17.43 | 23.67 | 73.14 | 13.50 | 0.00 | 0.00 | 0.00 |
October | 46.15 | 29.31 | 16.83 | 78.80 | 29.76 | 0.00 | 0.00 | 0.00 |
November | 38.15 | 25.03 | 13.12 | 59.16 | 41.21 | 0.00 | 0.00 | 0.00 |
December | 29.40 | 15.74 | 13.65 | 41.96 | 42.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.20 | 26.89 | 20.31 | 82.46 | 23.33 | 60.33 | 0.00 | 0.00 |
Minimum of Months | 29.40 | 11.53 | 13.12 | 41.96 | 5.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.00 | 49.18 | 29.67 | 133.39 | 42.88 | 60.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.35 | 16.15 | 14.20 | 44.48 | 38.10 | 60.33 | 0.00 | 0.00 |
February | 38.36 | 21.34 | 17.02 | 59.02 | 34.91 | 0.00 | 0.00 | 0.00 |
March | 51.92 | 31.14 | 20.78 | 85.01 | 29.82 | 0.00 | 0.00 | 0.00 |
April | 66.86 | 46.87 | 19.99 | 120.13 | 20.08 | 0.00 | 0.00 | 0.00 |
May | 71.00 | 49.18 | 21.81 | 133.39 | 10.79 | 0.00 | 0.00 | 0.00 |
June | 66.45 | 42.41 | 24.04 | 126.94 | 7.35 | 0.00 | 0.00 | 0.00 |
July | 46.44 | 16.77 | 29.67 | 90.03 | 5.04 | 0.00 | 0.00 | 0.00 |
August | 40.10 | 11.53 | 28.57 | 76.82 | 7.27 | 0.00 | 0.00 | 0.00 |
September | 41.11 | 17.43 | 23.67 | 73.14 | 13.50 | 0.00 | 0.00 | 0.00 |
October | 46.15 | 29.31 | 16.83 | 78.80 | 29.76 | 0.00 | 0.00 | 0.00 |
November | 38.15 | 25.03 | 13.12 | 59.16 | 41.21 | 0.00 | 0.00 | 0.00 |
December | 29.40 | 15.74 | 13.65 | 41.96 | 42.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.20 | 26.89 | 20.31 | 82.46 | 23.33 | 60.33 | 0.00 | 0.00 |
Minimum of Months | 29.40 | 11.53 | 13.12 | 41.96 | 5.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.00 | 49.18 | 29.67 | 133.39 | 42.88 | 60.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.35 | 16.15 | 14.20 | 44.48 | 38.10 | 60.33 | 0.00 | 0.00 |
February | 38.36 | 21.34 | 17.02 | 59.02 | 34.91 | 0.00 | 0.00 | 0.00 |
March | 51.92 | 31.14 | 20.78 | 85.01 | 29.82 | 0.00 | 0.00 | 0.00 |
April | 66.86 | 46.87 | 19.99 | 120.13 | 20.08 | 0.00 | 0.00 | 0.00 |
May | 71.00 | 49.18 | 21.81 | 133.39 | 10.79 | 0.00 | 0.00 | 0.00 |
June | 66.45 | 42.41 | 24.04 | 126.94 | 7.35 | 0.00 | 0.00 | 0.00 |
July | 46.44 | 16.77 | 29.67 | 90.03 | 5.04 | 0.00 | 0.00 | 0.00 |
August | 40.10 | 11.53 | 28.57 | 76.82 | 7.27 | 0.00 | 0.00 | 0.00 |
September | 41.11 | 17.43 | 23.67 | 73.14 | 13.50 | 0.00 | 0.00 | 0.00 |
October | 46.15 | 29.31 | 16.83 | 78.80 | 29.76 | 0.00 | 0.00 | 0.00 |
November | 38.15 | 25.03 | 13.12 | 59.16 | 41.21 | 0.00 | 0.00 | 0.00 |
December | 29.40 | 15.74 | 13.65 | 41.96 | 42.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.20 | 26.89 | 20.31 | 82.46 | 23.33 | 60.33 | 0.00 | 0.00 |
Minimum of Months | 29.40 | 11.53 | 13.12 | 41.96 | 5.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.00 | 49.18 | 29.67 | 133.39 | 42.88 | 60.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.35 | 16.15 | 14.20 | 44.48 | 38.10 | 60.33 | 0.00 | 0.00 |
February | 38.36 | 21.34 | 17.02 | 59.02 | 34.91 | 0.00 | 0.00 | 0.00 |
March | 51.92 | 31.14 | 20.78 | 85.01 | 29.82 | 0.00 | 0.00 | 0.00 |
April | 66.86 | 46.87 | 19.99 | 120.13 | 20.08 | 0.00 | 0.00 | 0.00 |
May | 71.00 | 49.18 | 21.81 | 133.39 | 10.79 | 0.00 | 0.00 | 0.00 |
June | 66.45 | 42.41 | 24.04 | 126.94 | 7.35 | 0.00 | 0.00 | 0.00 |
July | 46.44 | 16.77 | 29.67 | 90.03 | 5.04 | 0.00 | 0.00 | 0.00 |
August | 40.10 | 11.53 | 28.57 | 76.82 | 7.27 | 0.00 | 0.00 | 0.00 |
September | 41.11 | 17.43 | 23.67 | 73.14 | 13.50 | 0.00 | 0.00 | 0.00 |
October | 46.15 | 29.31 | 16.83 | 78.80 | 29.76 | 0.00 | 0.00 | 0.00 |
November | 38.15 | 25.03 | 13.12 | 59.16 | 41.21 | 0.00 | 0.00 | 0.00 |
December | 29.40 | 15.74 | 13.65 | 41.96 | 42.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.20 | 26.89 | 20.31 | 82.46 | 23.33 | 60.33 | 0.00 | 0.00 |
Minimum of Months | 29.40 | 11.53 | 13.12 | 41.96 | 5.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.00 | 49.18 | 29.67 | 133.39 | 42.88 | 60.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.35 | 16.15 | 14.20 | 44.48 | 38.10 | 60.33 | 0.00 | 0.00 |
February | 38.36 | 21.34 | 17.02 | 59.02 | 34.91 | 0.00 | 0.00 | 0.00 |
March | 51.92 | 31.14 | 20.78 | 85.01 | 29.82 | 0.00 | 0.00 | 0.00 |
April | 66.86 | 46.87 | 19.99 | 120.13 | 20.08 | 0.00 | 0.00 | 0.00 |
May | 71.00 | 49.18 | 21.81 | 133.39 | 10.79 | 0.00 | 0.00 | 0.00 |
June | 66.45 | 42.41 | 24.04 | 126.94 | 7.35 | 0.00 | 0.00 | 0.00 |
July | 46.44 | 16.77 | 29.67 | 90.03 | 5.04 | 0.00 | 0.00 | 0.00 |
August | 40.10 | 11.53 | 28.57 | 76.82 | 7.27 | 0.00 | 0.00 | 0.00 |
September | 41.11 | 17.43 | 23.67 | 73.14 | 13.50 | 0.00 | 0.00 | 0.00 |
October | 46.15 | 29.31 | 16.83 | 78.80 | 29.76 | 0.00 | 0.00 | 0.00 |
November | 38.15 | 25.03 | 13.12 | 59.16 | 41.21 | 0.00 | 0.00 | 0.00 |
December | 29.40 | 15.74 | 13.65 | 41.96 | 42.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.20 | 26.89 | 20.31 | 82.46 | 23.33 | 60.33 | 0.00 | 0.00 |
Minimum of Months | 29.40 | 11.53 | 13.12 | 41.96 | 5.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.00 | 49.18 | 29.67 | 133.39 | 42.88 | 60.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.35 | 16.15 | 14.20 | 44.48 | 38.10 | 60.33 | 0.00 | 0.00 |
February | 38.36 | 21.34 | 17.02 | 59.02 | 34.91 | 0.00 | 0.00 | 0.00 |
March | 51.92 | 31.14 | 20.78 | 85.01 | 29.82 | 0.00 | 0.00 | 0.00 |
April | 66.86 | 46.87 | 19.99 | 120.13 | 20.08 | 0.00 | 0.00 | 0.00 |
May | 71.00 | 49.18 | 21.81 | 133.39 | 10.79 | 0.00 | 0.00 | 0.00 |
June | 66.45 | 42.41 | 24.04 | 126.94 | 7.35 | 0.00 | 0.00 | 0.00 |
July | 46.44 | 16.77 | 29.67 | 90.03 | 5.04 | 0.00 | 0.00 | 0.00 |
August | 40.10 | 11.53 | 28.57 | 76.82 | 7.27 | 0.00 | 0.00 | 0.00 |
September | 41.11 | 17.43 | 23.67 | 73.14 | 13.50 | 0.00 | 0.00 | 0.00 |
October | 46.15 | 29.31 | 16.83 | 78.80 | 29.76 | 0.00 | 0.00 | 0.00 |
November | 38.15 | 25.03 | 13.12 | 59.16 | 41.21 | 0.00 | 0.00 | 0.00 |
December | 29.40 | 15.74 | 13.65 | 41.96 | 42.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.20 | 26.89 | 20.31 | 82.46 | 23.33 | 60.33 | 0.00 | 0.00 |
Minimum of Months | 29.40 | 11.53 | 13.12 | 41.96 | 5.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.00 | 49.18 | 29.67 | 133.39 | 42.88 | 60.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.35 | 16.15 | 14.20 | 44.48 | 38.10 | 60.33 | 0.00 | 0.00 |
February | 38.36 | 21.34 | 17.02 | 59.02 | 34.91 | 0.00 | 0.00 | 0.00 |
March | 51.92 | 31.14 | 20.78 | 85.01 | 29.82 | 0.00 | 0.00 | 0.00 |
April | 66.86 | 46.87 | 19.99 | 120.13 | 20.08 | 0.00 | 0.00 | 0.00 |
May | 71.00 | 49.18 | 21.81 | 133.39 | 10.79 | 0.00 | 0.00 | 0.00 |
June | 66.45 | 42.41 | 24.04 | 126.94 | 7.35 | 0.00 | 0.00 | 0.00 |
July | 46.44 | 16.77 | 29.67 | 90.03 | 5.04 | 0.00 | 0.00 | 0.00 |
August | 40.10 | 11.53 | 28.57 | 76.82 | 7.27 | 0.00 | 0.00 | 0.00 |
September | 41.11 | 17.43 | 23.67 | 73.14 | 13.50 | 0.00 | 0.00 | 0.00 |
October | 46.15 | 29.31 | 16.83 | 78.80 | 29.76 | 0.00 | 0.00 | 0.00 |
November | 38.15 | 25.03 | 13.12 | 59.16 | 41.21 | 0.00 | 0.00 | 0.00 |
December | 29.40 | 15.74 | 13.65 | 41.96 | 42.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.20 | 26.89 | 20.31 | 82.46 | 23.33 | 60.33 | 0.00 | 0.00 |
Minimum of Months | 29.40 | 11.53 | 13.12 | 41.96 | 5.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.00 | 49.18 | 29.67 | 133.39 | 42.88 | 60.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.35 | 16.15 | 14.20 | 44.48 | 38.10 | 60.33 | 0.00 | 0.00 |
February | 38.36 | 21.34 | 17.02 | 59.02 | 34.91 | 0.00 | 0.00 | 0.00 |
March | 51.92 | 31.14 | 20.78 | 85.01 | 29.82 | 0.00 | 0.00 | 0.00 |
April | 66.86 | 46.87 | 19.99 | 120.13 | 20.08 | 0.00 | 0.00 | 0.00 |
May | 71.00 | 49.18 | 21.81 | 133.39 | 10.79 | 0.00 | 0.00 | 0.00 |
June | 66.45 | 42.41 | 24.04 | 126.94 | 7.35 | 0.00 | 0.00 | 0.00 |
July | 46.44 | 16.77 | 29.67 | 90.03 | 5.04 | 0.00 | 0.00 | 0.00 |
August | 40.10 | 11.53 | 28.57 | 76.82 | 7.27 | 0.00 | 0.00 | 0.00 |
September | 41.11 | 17.43 | 23.67 | 73.14 | 13.50 | 0.00 | 0.00 | 0.00 |
October | 46.15 | 29.31 | 16.83 | 78.80 | 29.76 | 0.00 | 0.00 | 0.00 |
November | 38.15 | 25.03 | 13.12 | 59.16 | 41.21 | 0.00 | 0.00 | 0.00 |
December | 29.40 | 15.74 | 13.65 | 41.96 | 42.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.20 | 26.89 | 20.31 | 82.46 | 23.33 | 60.33 | 0.00 | 0.00 |
Minimum of Months | 29.40 | 11.53 | 13.12 | 41.96 | 5.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.00 | 49.18 | 29.67 | 133.39 | 42.88 | 60.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.52 | 37.14 | 32.38 | 88.27 | 62.14 | 195.17 | 0.00 | 0.00 |
February | 87.40 | 48.58 | 38.82 | 113.29 | 59.60 | 29.33 | 0.00 | 0.00 |
March | 117.64 | 70.25 | 47.39 | 155.38 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 150.97 | 105.36 | 45.60 | 208.31 | 47.39 | 0.00 | 0.00 | 0.00 |
May | 160.07 | 110.32 | 49.75 | 221.20 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 149.82 | 95.00 | 54.82 | 208.33 | 33.91 | 10.17 | 0.00 | 0.00 |
July | 105.26 | 37.59 | 67.66 | 147.39 | 22.03 | 5.50 | 0.00 | 0.00 |
August | 91.04 | 25.89 | 65.15 | 129.23 | 22.43 | 37.67 | 0.00 | 0.00 |
September | 93.29 | 39.29 | 54.00 | 125.27 | 33.63 | 43.50 | 0.00 | 0.00 |
October | 104.67 | 66.28 | 38.39 | 140.84 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 87.14 | 57.21 | 29.93 | 111.26 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 67.50 | 36.37 | 31.14 | 82.98 | 72.77 | 112.67 | 0.00 | 0.00 |
Annual Sum or Average | 107.04 | 60.73 | 46.31 | 144.36 | 48.45 | 434.00 | 0.00 | 0.00 |
Minimum of Months | 67.50 | 25.89 | 29.93 | 82.98 | 22.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.07 | 110.32 | 67.66 | 221.20 | 74.92 | 195.17 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.142663E+09 | 55467988.46 | 87195445.04 | 0.193809E+09 | 0.224375E+09 |
February | 0.147187E+09 | 54155977.63 | 93030905.49 | 0.221505E+09 | 0.174451E+09 |
March | 0.212425E+09 | 85364302.52 | 0.127061E+09 | 0.370705E+09 | 0.138922E+09 |
April | 0.248463E+09 | 0.116301E+09 | 0.132162E+09 | 0.525710E+09 | 59834360.42 |
May | 0.243196E+09 | 0.102995E+09 | 0.140202E+09 | 0.588766E+09 | 18805858.85 |
June | 0.222012E+09 | 86666310.93 | 0.135346E+09 | 0.561225E+09 | 13043728.79 |
July | 0.169609E+09 | 32894975.93 | 0.136714E+09 | 0.420976E+09 | 7547091.85 |
August | 0.155522E+09 | 27296491.78 | 0.128226E+09 | 0.364071E+09 | 16884712.01 |
September | 0.166243E+09 | 49190310.25 | 0.117052E+09 | 0.347709E+09 | 42151073.47 |
October | 0.178313E+09 | 70945497.85 | 0.107368E+09 | 0.342935E+09 | 0.131359E+09 |
November | 0.156086E+09 | 66490600.86 | 89594966.12 | 0.253516E+09 | 0.206266E+09 |
December | 0.138194E+09 | 52776738.31 | 85416871.88 | 0.184170E+09 | 0.245625E+09 |
Annual Sum or Average | 0.217991E+10 | 0.800545E+09 | 0.137937E+10 | 0.437510E+10 | 0.127926E+10 |
Minimum of Months | 0.138194E+09 | 27296491.78 | 85416871.88 | 0.184170E+09 | 7547091.85 |
Maximum of Months | 0.248463E+09 | 0.116301E+09 | 0.140202E+09 | 0.588766E+09 | 0.245625E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.142663E+09 | 55467988.46 | 87195445.04 | 0.193809E+09 | 0.224375E+09 |
February | 0.147187E+09 | 54155977.63 | 93030905.49 | 0.221505E+09 | 0.174451E+09 |
March | 0.212425E+09 | 85364302.52 | 0.127061E+09 | 0.370705E+09 | 0.138922E+09 |
April | 0.248463E+09 | 0.116301E+09 | 0.132162E+09 | 0.525710E+09 | 59834360.42 |
May | 0.243196E+09 | 0.102995E+09 | 0.140202E+09 | 0.588766E+09 | 18805858.85 |
June | 0.222012E+09 | 86666310.93 | 0.135346E+09 | 0.561225E+09 | 13043728.79 |
July | 0.169609E+09 | 32894975.93 | 0.136714E+09 | 0.420976E+09 | 7547091.85 |
August | 0.155522E+09 | 27296491.78 | 0.128226E+09 | 0.364071E+09 | 16884712.01 |
September | 0.166243E+09 | 49190310.25 | 0.117052E+09 | 0.347709E+09 | 42151073.47 |
October | 0.178313E+09 | 70945497.85 | 0.107368E+09 | 0.342935E+09 | 0.131359E+09 |
November | 0.156086E+09 | 66490600.86 | 89594966.12 | 0.253516E+09 | 0.206266E+09 |
December | 0.138194E+09 | 52776738.31 | 85416871.88 | 0.184170E+09 | 0.245625E+09 |
Annual Sum or Average | 0.217991E+10 | 0.800545E+09 | 0.137937E+10 | 0.437510E+10 | 0.127926E+10 |
Minimum of Months | 0.138194E+09 | 27296491.78 | 85416871.88 | 0.184170E+09 | 7547091.85 |
Maximum of Months | 0.248463E+09 | 0.116301E+09 | 0.140202E+09 | 0.588766E+09 | 0.245625E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 39713872.23 | 0.00 | 39713872.23 | 31778160.55 | 0.133556E+09 |
February | 42536443.42 | 0.00 | 42536443.42 | 46494055.07 | 0.102640E+09 |
March | 56763039.75 | 5415.53 | 56757624.22 | 88071259.50 | 81207579.04 |
April | 59733439.25 | 297130.45 | 59436308.80 | 0.143061E+09 | 34219242.55 |
May | 68440029.73 | 2117785.07 | 66322244.66 | 0.202924E+09 | 10709319.81 |
June | 68167320.25 | 2365450.22 | 65801870.03 | 0.209637E+09 | 7554160.99 |
July | 69763683.39 | 1199598.16 | 68564085.23 | 0.190055E+09 | 4220704.25 |
August | 64156189.64 | 357755.44 | 63798434.21 | 0.160881E+09 | 9686491.83 |
September | 55139986.50 | 7000.62 | 55132985.88 | 0.122113E+09 | 24308614.07 |
October | 49356041.73 | 0.00 | 49356041.73 | 92208210.64 | 76371902.52 |
November | 40456503.93 | 0.00 | 40456503.93 | 48472133.70 | 0.121111E+09 |
December | 38741591.70 | 0.00 | 38741591.70 | 29620630.62 | 0.147198E+09 |
Annual Sum or Average | 0.652968E+09 | 6350135.48 | 0.646618E+09 | 0.136532E+10 | 0.752783E+09 |
Minimum of Months | 38741591.70 | 0.00 | 38741591.70 | 29620630.62 | 4220704.25 |
Maximum of Months | 69763683.39 | 2365450.22 | 68564085.23 | 0.209637E+09 | 0.147198E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 39712656.98 | 0.00 | 39712656.98 | 31776942.77 | 0.133555E+09 |
February | 42535175.77 | 0.00 | 42535175.77 | 46492613.12 | 0.102639E+09 |
March | 56761423.09 | 5415.28 | 56756007.81 | 88069301.50 | 81206424.53 |
April | 59731921.93 | 297116.53 | 59434805.40 | 0.143060E+09 | 34218265.80 |
May | 68438206.87 | 2117685.81 | 66320521.06 | 0.202922E+09 | 10708737.87 |
June | 68165382.70 | 2365339.34 | 65800043.36 | 0.209635E+09 | 7553900.50 |
July | 69761355.68 | 1199541.93 | 68561813.75 | 0.190052E+09 | 4220450.47 |
August | 64154004.53 | 357738.67 | 63796265.86 | 0.160878E+09 | 9686082.27 |
September | 55138217.49 | 7000.29 | 55131217.20 | 0.122110E+09 | 24307881.43 |
October | 49354663.26 | 0.00 | 49354663.26 | 92206673.63 | 76370546.61 |
November | 40455384.29 | 0.00 | 40455384.29 | 48471135.96 | 0.121109E+09 |
December | 38740410.78 | 0.00 | 38740410.78 | 29619489.69 | 0.147197E+09 |
Annual Sum or Average | 0.652949E+09 | 6349837.84 | 0.646599E+09 | 0.136529E+10 | 0.752772E+09 |
Minimum of Months | 38740410.78 | 0.00 | 38740410.78 | 29619489.69 | 4220450.47 |
Maximum of Months | 69761355.68 | 2365339.34 | 68561813.75 | 0.209635E+09 | 0.147197E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 81291323.10 | 43267846.19 | 38023476.91 | 0.119142E+09 | 0.102060E+09 |
February | 92805287.20 | 51629812.20 | 41175475.00 | 0.142782E+09 | 84447002.72 |
March | 0.139068E+09 | 83410739.97 | 55657365.45 | 0.227689E+09 | 79878161.11 |
April | 0.173310E+09 | 0.121485E+09 | 51825347.18 | 0.311371E+09 | 52057818.96 |
May | 0.190158E+09 | 0.131733E+09 | 58424833.50 | 0.357266E+09 | 28887678.77 |
June | 0.172230E+09 | 0.109930E+09 | 62299923.15 | 0.329026E+09 | 19039899.42 |
July | 0.124377E+09 | 44914866.76 | 79462309.43 | 0.241143E+09 | 13487672.49 |
August | 0.107399E+09 | 30883500.88 | 76515107.29 | 0.205752E+09 | 19463128.49 |
September | 0.106544E+09 | 45179281.39 | 61364993.50 | 0.189576E+09 | 34987977.99 |
October | 0.123600E+09 | 78514771.99 | 45085175.18 | 0.211051E+09 | 79722124.36 |
November | 98890467.49 | 64878717.59 | 34011749.90 | 0.153335E+09 | 0.106820E+09 |
December | 78733017.97 | 42167953.38 | 36565064.59 | 0.112379E+09 | 0.114842E+09 |
Annual Sum or Average | 0.148841E+10 | 0.847995E+09 | 0.640411E+09 | 0.260051E+10 | 0.735694E+09 |
Minimum of Months | 78733017.97 | 30883500.88 | 34011749.90 | 0.112379E+09 | 13487672.49 |
Maximum of Months | 0.190158E+09 | 0.131733E+09 | 79462309.43 | 0.357266E+09 | 0.114842E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 81291323.10 | 43267846.19 | 38023476.91 | 0.119142E+09 | 0.102060E+09 |
February | 92805287.20 | 51629812.20 | 41175475.00 | 0.142782E+09 | 84447002.72 |
March | 0.139068E+09 | 83410739.97 | 55657365.45 | 0.227689E+09 | 79878161.11 |
April | 0.173310E+09 | 0.121485E+09 | 51825347.18 | 0.311371E+09 | 52057818.96 |
May | 0.190158E+09 | 0.131733E+09 | 58424833.50 | 0.357266E+09 | 28887678.77 |
June | 0.172230E+09 | 0.109930E+09 | 62299923.15 | 0.329026E+09 | 19039899.42 |
July | 0.124377E+09 | 44914866.76 | 79462309.43 | 0.241143E+09 | 13487672.49 |
August | 0.107399E+09 | 30883500.88 | 76515107.29 | 0.205752E+09 | 19463128.49 |
September | 0.106544E+09 | 45179281.39 | 61364993.50 | 0.189576E+09 | 34987977.99 |
October | 0.123600E+09 | 78514771.99 | 45085175.18 | 0.211051E+09 | 79722124.36 |
November | 98890467.49 | 64878717.59 | 34011749.90 | 0.153335E+09 | 0.106820E+09 |
December | 78733017.97 | 42167953.38 | 36565064.59 | 0.112379E+09 | 0.114842E+09 |
Annual Sum or Average | 0.148841E+10 | 0.847995E+09 | 0.640411E+09 | 0.260051E+10 | 0.735694E+09 |
Minimum of Months | 78733017.97 | 30883500.88 | 34011749.90 | 0.112379E+09 | 13487672.49 |
Maximum of Months | 0.190158E+09 | 0.131733E+09 | 79462309.43 | 0.357266E+09 | 0.114842E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 81291323.10 | 43267846.19 | 38023476.91 | 0.119142E+09 | 0.102060E+09 |
February | 92805287.20 | 51629812.20 | 41175475.00 | 0.142782E+09 | 84447002.72 |
March | 0.139068E+09 | 83410739.97 | 55657365.45 | 0.227689E+09 | 79878161.11 |
April | 0.173310E+09 | 0.121485E+09 | 51825347.18 | 0.311371E+09 | 52057818.96 |
May | 0.190158E+09 | 0.131733E+09 | 58424833.50 | 0.357266E+09 | 28887678.77 |
June | 0.172230E+09 | 0.109930E+09 | 62299923.15 | 0.329026E+09 | 19039899.42 |
July | 0.124377E+09 | 44914866.76 | 79462309.43 | 0.241143E+09 | 13487672.49 |
August | 0.107399E+09 | 30883500.88 | 76515107.29 | 0.205752E+09 | 19463128.49 |
September | 0.106544E+09 | 45179281.39 | 61364993.50 | 0.189576E+09 | 34987977.99 |
October | 0.123600E+09 | 78514771.99 | 45085175.18 | 0.211051E+09 | 79722124.36 |
November | 98890467.49 | 64878717.59 | 34011749.90 | 0.153335E+09 | 0.106820E+09 |
December | 78733017.97 | 42167953.38 | 36565064.59 | 0.112379E+09 | 0.114842E+09 |
Annual Sum or Average | 0.148841E+10 | 0.847995E+09 | 0.640411E+09 | 0.260051E+10 | 0.735694E+09 |
Minimum of Months | 78733017.97 | 30883500.88 | 34011749.90 | 0.112379E+09 | 13487672.49 |
Maximum of Months | 0.190158E+09 | 0.131733E+09 | 79462309.43 | 0.357266E+09 | 0.114842E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 81291323.10 | 43267846.19 | 38023476.91 | 0.119142E+09 | 0.102060E+09 |
February | 92805287.20 | 51629812.20 | 41175475.00 | 0.142782E+09 | 84447002.72 |
March | 0.139068E+09 | 83410739.97 | 55657365.45 | 0.227689E+09 | 79878161.11 |
April | 0.173310E+09 | 0.121485E+09 | 51825347.18 | 0.311371E+09 | 52057818.96 |
May | 0.190158E+09 | 0.131733E+09 | 58424833.50 | 0.357266E+09 | 28887678.77 |
June | 0.172230E+09 | 0.109930E+09 | 62299923.15 | 0.329026E+09 | 19039899.42 |
July | 0.124377E+09 | 44914866.76 | 79462309.43 | 0.241143E+09 | 13487672.49 |
August | 0.107399E+09 | 30883500.88 | 76515107.29 | 0.205752E+09 | 19463128.49 |
September | 0.106544E+09 | 45179281.39 | 61364993.50 | 0.189576E+09 | 34987977.99 |
October | 0.123600E+09 | 78514771.99 | 45085175.18 | 0.211051E+09 | 79722124.36 |
November | 98890467.49 | 64878717.59 | 34011749.90 | 0.153335E+09 | 0.106820E+09 |
December | 78733017.97 | 42167953.38 | 36565064.59 | 0.112379E+09 | 0.114842E+09 |
Annual Sum or Average | 0.148841E+10 | 0.847995E+09 | 0.640411E+09 | 0.260051E+10 | 0.735694E+09 |
Minimum of Months | 78733017.97 | 30883500.88 | 34011749.90 | 0.112379E+09 | 13487672.49 |
Maximum of Months | 0.190158E+09 | 0.131733E+09 | 79462309.43 | 0.357266E+09 | 0.114842E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 81291323.10 | 43267846.19 | 38023476.91 | 0.119142E+09 | 0.102060E+09 |
February | 92805287.20 | 51629812.20 | 41175475.00 | 0.142782E+09 | 84447002.72 |
March | 0.139068E+09 | 83410739.97 | 55657365.45 | 0.227689E+09 | 79878161.11 |
April | 0.173310E+09 | 0.121485E+09 | 51825347.18 | 0.311371E+09 | 52057818.96 |
May | 0.190158E+09 | 0.131733E+09 | 58424833.50 | 0.357266E+09 | 28887678.77 |
June | 0.172230E+09 | 0.109930E+09 | 62299923.15 | 0.329026E+09 | 19039899.42 |
July | 0.124377E+09 | 44914866.76 | 79462309.43 | 0.241143E+09 | 13487672.49 |
August | 0.107399E+09 | 30883500.88 | 76515107.29 | 0.205752E+09 | 19463128.49 |
September | 0.106544E+09 | 45179281.39 | 61364993.50 | 0.189576E+09 | 34987977.99 |
October | 0.123600E+09 | 78514771.99 | 45085175.18 | 0.211051E+09 | 79722124.36 |
November | 98890467.49 | 64878717.59 | 34011749.90 | 0.153335E+09 | 0.106820E+09 |
December | 78733017.97 | 42167953.38 | 36565064.59 | 0.112379E+09 | 0.114842E+09 |
Annual Sum or Average | 0.148841E+10 | 0.847995E+09 | 0.640411E+09 | 0.260051E+10 | 0.735694E+09 |
Minimum of Months | 78733017.97 | 30883500.88 | 34011749.90 | 0.112379E+09 | 13487672.49 |
Maximum of Months | 0.190158E+09 | 0.131733E+09 | 79462309.43 | 0.357266E+09 | 0.114842E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 81291323.10 | 43267846.19 | 38023476.91 | 0.119142E+09 | 0.102060E+09 |
February | 92805287.20 | 51629812.20 | 41175475.00 | 0.142782E+09 | 84447002.72 |
March | 0.139068E+09 | 83410739.97 | 55657365.45 | 0.227689E+09 | 79878161.11 |
April | 0.173310E+09 | 0.121485E+09 | 51825347.18 | 0.311371E+09 | 52057818.96 |
May | 0.190158E+09 | 0.131733E+09 | 58424833.50 | 0.357266E+09 | 28887678.77 |
June | 0.172230E+09 | 0.109930E+09 | 62299923.15 | 0.329026E+09 | 19039899.42 |
July | 0.124377E+09 | 44914866.76 | 79462309.43 | 0.241143E+09 | 13487672.49 |
August | 0.107399E+09 | 30883500.88 | 76515107.29 | 0.205752E+09 | 19463128.49 |
September | 0.106544E+09 | 45179281.39 | 61364993.50 | 0.189576E+09 | 34987977.99 |
October | 0.123600E+09 | 78514771.99 | 45085175.18 | 0.211051E+09 | 79722124.36 |
November | 98890467.49 | 64878717.59 | 34011749.90 | 0.153335E+09 | 0.106820E+09 |
December | 78733017.97 | 42167953.38 | 36565064.59 | 0.112379E+09 | 0.114842E+09 |
Annual Sum or Average | 0.148841E+10 | 0.847995E+09 | 0.640411E+09 | 0.260051E+10 | 0.735694E+09 |
Minimum of Months | 78733017.97 | 30883500.88 | 34011749.90 | 0.112379E+09 | 13487672.49 |
Maximum of Months | 0.190158E+09 | 0.131733E+09 | 79462309.43 | 0.357266E+09 | 0.114842E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 81291323.10 | 43267846.19 | 38023476.91 | 0.119142E+09 | 0.102060E+09 |
February | 92805287.20 | 51629812.20 | 41175475.00 | 0.142782E+09 | 84447002.72 |
March | 0.139068E+09 | 83410739.97 | 55657365.45 | 0.227689E+09 | 79878161.11 |
April | 0.173310E+09 | 0.121485E+09 | 51825347.18 | 0.311371E+09 | 52057818.96 |
May | 0.190158E+09 | 0.131733E+09 | 58424833.50 | 0.357266E+09 | 28887678.77 |
June | 0.172230E+09 | 0.109930E+09 | 62299923.15 | 0.329026E+09 | 19039899.42 |
July | 0.124377E+09 | 44914866.76 | 79462309.43 | 0.241143E+09 | 13487672.49 |
August | 0.107399E+09 | 30883500.88 | 76515107.29 | 0.205752E+09 | 19463128.49 |
September | 0.106544E+09 | 45179281.39 | 61364993.50 | 0.189576E+09 | 34987977.99 |
October | 0.123600E+09 | 78514771.99 | 45085175.18 | 0.211051E+09 | 79722124.36 |
November | 98890467.49 | 64878717.59 | 34011749.90 | 0.153335E+09 | 0.106820E+09 |
December | 78733017.97 | 42167953.38 | 36565064.59 | 0.112379E+09 | 0.114842E+09 |
Annual Sum or Average | 0.148841E+10 | 0.847995E+09 | 0.640411E+09 | 0.260051E+10 | 0.735694E+09 |
Minimum of Months | 78733017.97 | 30883500.88 | 34011749.90 | 0.112379E+09 | 13487672.49 |
Maximum of Months | 0.190158E+09 | 0.131733E+09 | 79462309.43 | 0.357266E+09 | 0.114842E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 81291323.10 | 43267846.19 | 38023476.91 | 0.119142E+09 | 0.102060E+09 |
February | 92805287.20 | 51629812.20 | 41175475.00 | 0.142782E+09 | 84447002.72 |
March | 0.139068E+09 | 83410739.97 | 55657365.45 | 0.227689E+09 | 79878161.11 |
April | 0.173310E+09 | 0.121485E+09 | 51825347.18 | 0.311371E+09 | 52057818.96 |
May | 0.190158E+09 | 0.131733E+09 | 58424833.50 | 0.357266E+09 | 28887678.77 |
June | 0.172230E+09 | 0.109930E+09 | 62299923.15 | 0.329026E+09 | 19039899.42 |
July | 0.124377E+09 | 44914866.76 | 79462309.43 | 0.241143E+09 | 13487672.49 |
August | 0.107399E+09 | 30883500.88 | 76515107.29 | 0.205752E+09 | 19463128.49 |
September | 0.106544E+09 | 45179281.39 | 61364993.50 | 0.189576E+09 | 34987977.99 |
October | 0.123600E+09 | 78514771.99 | 45085175.18 | 0.211051E+09 | 79722124.36 |
November | 98890467.49 | 64878717.59 | 34011749.90 | 0.153335E+09 | 0.106820E+09 |
December | 78733017.97 | 42167953.38 | 36565064.59 | 0.112379E+09 | 0.114842E+09 |
Annual Sum or Average | 0.148841E+10 | 0.847995E+09 | 0.640411E+09 | 0.260051E+10 | 0.735694E+09 |
Minimum of Months | 78733017.97 | 30883500.88 | 34011749.90 | 0.112379E+09 | 13487672.49 |
Maximum of Months | 0.190158E+09 | 0.131733E+09 | 79462309.43 | 0.357266E+09 | 0.114842E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 81291323.10 | 43267846.19 | 38023476.91 | 0.119142E+09 | 0.102060E+09 |
February | 92805287.20 | 51629812.20 | 41175475.00 | 0.142782E+09 | 84447002.72 |
March | 0.139068E+09 | 83410739.97 | 55657365.45 | 0.227689E+09 | 79878161.11 |
April | 0.173310E+09 | 0.121485E+09 | 51825347.18 | 0.311371E+09 | 52057818.96 |
May | 0.190158E+09 | 0.131733E+09 | 58424833.50 | 0.357266E+09 | 28887678.77 |
June | 0.172230E+09 | 0.109930E+09 | 62299923.15 | 0.329026E+09 | 19039899.42 |
July | 0.124377E+09 | 44914866.76 | 79462309.43 | 0.241143E+09 | 13487672.49 |
August | 0.107399E+09 | 30883500.88 | 76515107.29 | 0.205752E+09 | 19463128.49 |
September | 0.106544E+09 | 45179281.39 | 61364993.50 | 0.189576E+09 | 34987977.99 |
October | 0.123600E+09 | 78514771.99 | 45085175.18 | 0.211051E+09 | 79722124.36 |
November | 98890467.49 | 64878717.59 | 34011749.90 | 0.153335E+09 | 0.106820E+09 |
December | 78733017.97 | 42167953.38 | 36565064.59 | 0.112379E+09 | 0.114842E+09 |
Annual Sum or Average | 0.148841E+10 | 0.847995E+09 | 0.640411E+09 | 0.260051E+10 | 0.735694E+09 |
Minimum of Months | 78733017.97 | 30883500.88 | 34011749.90 | 0.112379E+09 | 13487672.49 |
Maximum of Months | 0.190158E+09 | 0.131733E+09 | 79462309.43 | 0.357266E+09 | 0.114842E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 81291323.10 | 43267846.19 | 38023476.91 | 0.119142E+09 | 0.102060E+09 |
February | 92805287.20 | 51629812.20 | 41175475.00 | 0.142782E+09 | 84447002.72 |
March | 0.139068E+09 | 83410739.97 | 55657365.45 | 0.227689E+09 | 79878161.11 |
April | 0.173310E+09 | 0.121485E+09 | 51825347.18 | 0.311371E+09 | 52057818.96 |
May | 0.190158E+09 | 0.131733E+09 | 58424833.50 | 0.357266E+09 | 28887678.77 |
June | 0.172230E+09 | 0.109930E+09 | 62299923.15 | 0.329026E+09 | 19039899.42 |
July | 0.124377E+09 | 44914866.76 | 79462309.43 | 0.241143E+09 | 13487672.49 |
August | 0.107399E+09 | 30883500.88 | 76515107.29 | 0.205752E+09 | 19463128.49 |
September | 0.106544E+09 | 45179281.39 | 61364993.50 | 0.189576E+09 | 34987977.99 |
October | 0.123600E+09 | 78514771.99 | 45085175.18 | 0.211051E+09 | 79722124.36 |
November | 98890467.49 | 64878717.59 | 34011749.90 | 0.153335E+09 | 0.106820E+09 |
December | 78733017.97 | 42167953.38 | 36565064.59 | 0.112379E+09 | 0.114842E+09 |
Annual Sum or Average | 0.148841E+10 | 0.847995E+09 | 0.640411E+09 | 0.260051E+10 | 0.735694E+09 |
Minimum of Months | 78733017.97 | 30883500.88 | 34011749.90 | 0.112379E+09 | 13487672.49 |
Maximum of Months | 0.190158E+09 | 0.131733E+09 | 79462309.43 | 0.357266E+09 | 0.114842E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 81291323.10 | 43267846.19 | 38023476.91 | 0.119142E+09 | 0.102060E+09 |
February | 92805287.20 | 51629812.20 | 41175475.00 | 0.142782E+09 | 84447002.72 |
March | 0.139068E+09 | 83410739.97 | 55657365.45 | 0.227689E+09 | 79878161.11 |
April | 0.173310E+09 | 0.121485E+09 | 51825347.18 | 0.311371E+09 | 52057818.96 |
May | 0.190158E+09 | 0.131733E+09 | 58424833.50 | 0.357266E+09 | 28887678.77 |
June | 0.172230E+09 | 0.109930E+09 | 62299923.15 | 0.329026E+09 | 19039899.42 |
July | 0.124377E+09 | 44914866.76 | 79462309.43 | 0.241143E+09 | 13487672.49 |
August | 0.107399E+09 | 30883500.88 | 76515107.29 | 0.205752E+09 | 19463128.49 |
September | 0.106544E+09 | 45179281.39 | 61364993.50 | 0.189576E+09 | 34987977.99 |
October | 0.123600E+09 | 78514771.99 | 45085175.18 | 0.211051E+09 | 79722124.36 |
November | 98890467.49 | 64878717.59 | 34011749.90 | 0.153335E+09 | 0.106820E+09 |
December | 78733017.97 | 42167953.38 | 36565064.59 | 0.112379E+09 | 0.114842E+09 |
Annual Sum or Average | 0.148841E+10 | 0.847995E+09 | 0.640411E+09 | 0.260051E+10 | 0.735694E+09 |
Minimum of Months | 78733017.97 | 30883500.88 | 34011749.90 | 0.112379E+09 | 13487672.49 |
Maximum of Months | 0.190158E+09 | 0.131733E+09 | 79462309.43 | 0.357266E+09 | 0.114842E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 81291323.10 | 43267846.19 | 38023476.91 | 0.119142E+09 | 0.102060E+09 |
February | 92805287.20 | 51629812.20 | 41175475.00 | 0.142782E+09 | 84447002.72 |
March | 0.139068E+09 | 83410739.97 | 55657365.45 | 0.227689E+09 | 79878161.11 |
April | 0.173310E+09 | 0.121485E+09 | 51825347.18 | 0.311371E+09 | 52057818.96 |
May | 0.190158E+09 | 0.131733E+09 | 58424833.50 | 0.357266E+09 | 28887678.77 |
June | 0.172230E+09 | 0.109930E+09 | 62299923.15 | 0.329026E+09 | 19039899.42 |
July | 0.124377E+09 | 44914866.76 | 79462309.43 | 0.241143E+09 | 13487672.49 |
August | 0.107399E+09 | 30883500.88 | 76515107.29 | 0.205752E+09 | 19463128.49 |
September | 0.106544E+09 | 45179281.39 | 61364993.50 | 0.189576E+09 | 34987977.99 |
October | 0.123600E+09 | 78514771.99 | 45085175.18 | 0.211051E+09 | 79722124.36 |
November | 98890467.49 | 64878717.59 | 34011749.90 | 0.153335E+09 | 0.106820E+09 |
December | 78733017.97 | 42167953.38 | 36565064.59 | 0.112379E+09 | 0.114842E+09 |
Annual Sum or Average | 0.148841E+10 | 0.847995E+09 | 0.640411E+09 | 0.260051E+10 | 0.735694E+09 |
Minimum of Months | 78733017.97 | 30883500.88 | 34011749.90 | 0.112379E+09 | 13487672.49 |
Maximum of Months | 0.190158E+09 | 0.131733E+09 | 79462309.43 | 0.357266E+09 | 0.114842E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 81291323.10 | 43267846.19 | 38023476.91 | 0.119142E+09 | 0.102060E+09 |
February | 92805287.20 | 51629812.20 | 41175475.00 | 0.142782E+09 | 84447002.72 |
March | 0.139068E+09 | 83410739.97 | 55657365.45 | 0.227689E+09 | 79878161.11 |
April | 0.173310E+09 | 0.121485E+09 | 51825347.18 | 0.311371E+09 | 52057818.96 |
May | 0.190158E+09 | 0.131733E+09 | 58424833.50 | 0.357266E+09 | 28887678.77 |
June | 0.172230E+09 | 0.109930E+09 | 62299923.15 | 0.329026E+09 | 19039899.42 |
July | 0.124377E+09 | 44914866.76 | 79462309.43 | 0.241143E+09 | 13487672.49 |
August | 0.107399E+09 | 30883500.88 | 76515107.29 | 0.205752E+09 | 19463128.49 |
September | 0.106544E+09 | 45179281.39 | 61364993.50 | 0.189576E+09 | 34987977.99 |
October | 0.123600E+09 | 78514771.99 | 45085175.18 | 0.211051E+09 | 79722124.36 |
November | 98890467.49 | 64878717.59 | 34011749.90 | 0.153335E+09 | 0.106820E+09 |
December | 78733017.97 | 42167953.38 | 36565064.59 | 0.112379E+09 | 0.114842E+09 |
Annual Sum or Average | 0.148841E+10 | 0.847995E+09 | 0.640411E+09 | 0.260051E+10 | 0.735694E+09 |
Minimum of Months | 78733017.97 | 30883500.88 | 34011749.90 | 0.112379E+09 | 13487672.49 |
Maximum of Months | 0.190158E+09 | 0.131733E+09 | 79462309.43 | 0.357266E+09 | 0.114842E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 81291323.10 | 43267846.19 | 38023476.91 | 0.119142E+09 | 0.102060E+09 |
February | 92805287.20 | 51629812.20 | 41175475.00 | 0.142782E+09 | 84447002.72 |
March | 0.139068E+09 | 83410739.97 | 55657365.45 | 0.227689E+09 | 79878161.11 |
April | 0.173310E+09 | 0.121485E+09 | 51825347.18 | 0.311371E+09 | 52057818.96 |
May | 0.190158E+09 | 0.131733E+09 | 58424833.50 | 0.357266E+09 | 28887678.77 |
June | 0.172230E+09 | 0.109930E+09 | 62299923.15 | 0.329026E+09 | 19039899.42 |
July | 0.124377E+09 | 44914866.76 | 79462309.43 | 0.241143E+09 | 13487672.49 |
August | 0.107399E+09 | 30883500.88 | 76515107.29 | 0.205752E+09 | 19463128.49 |
September | 0.106544E+09 | 45179281.39 | 61364993.50 | 0.189576E+09 | 34987977.99 |
October | 0.123600E+09 | 78514771.99 | 45085175.18 | 0.211051E+09 | 79722124.36 |
November | 98890467.49 | 64878717.59 | 34011749.90 | 0.153335E+09 | 0.106820E+09 |
December | 78733017.97 | 42167953.38 | 36565064.59 | 0.112379E+09 | 0.114842E+09 |
Annual Sum or Average | 0.148841E+10 | 0.847995E+09 | 0.640411E+09 | 0.260051E+10 | 0.735694E+09 |
Minimum of Months | 78733017.97 | 30883500.88 | 34011749.90 | 0.112379E+09 | 13487672.49 |
Maximum of Months | 0.190158E+09 | 0.131733E+09 | 79462309.43 | 0.357266E+09 | 0.114842E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186209E+09 | 99488542.42 | 86720134.26 | 0.236431E+09 | 0.166446E+09 |
February | 0.211443E+09 | 0.117534E+09 | 93908895.51 | 0.274062E+09 | 0.144186E+09 |
March | 0.315090E+09 | 0.188152E+09 | 0.126938E+09 | 0.416157E+09 | 0.152639E+09 |
April | 0.391302E+09 | 0.273104E+09 | 0.118198E+09 | 0.539952E+09 | 0.122840E+09 |
May | 0.428742E+09 | 0.295493E+09 | 0.133250E+09 | 0.592452E+09 | 96322208.60 |
June | 0.388323E+09 | 0.246236E+09 | 0.142087E+09 | 0.539979E+09 | 87888340.36 |
July | 0.281924E+09 | 0.100694E+09 | 0.181230E+09 | 0.394782E+09 | 59014529.89 |
August | 0.243840E+09 | 69332276.75 | 0.174508E+09 | 0.346122E+09 | 60066992.58 |
September | 0.241799E+09 | 0.101844E+09 | 0.139955E+09 | 0.324698E+09 | 87167301.93 |
October | 0.280341E+09 | 0.177515E+09 | 0.102826E+09 | 0.377228E+09 | 0.162339E+09 |
November | 0.225865E+09 | 0.148294E+09 | 77570589.47 | 0.288374E+09 | 0.194187E+09 |
December | 0.180799E+09 | 97404942.62 | 83393933.65 | 0.222258E+09 | 0.194895E+09 |
Annual Sum or Average | 0.337568E+10 | 0.191509E+10 | 0.146058E+10 | 0.455250E+10 | 0.152799E+10 |
Minimum of Months | 0.180799E+09 | 69332276.75 | 77570589.47 | 0.222258E+09 | 59014529.89 |
Maximum of Months | 0.428742E+09 | 0.295493E+09 | 0.181230E+09 | 0.592452E+09 | 0.194895E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 166.39 | 265.21 | 136.18 | 41.42 | 94.76 | 0.00 | 0.00 |
February | 220.65 | 228.16 | 156.85 | 44.77 | 112.08 | 0.00 | 0.00 |
March | 342.14 | 163.94 | 201.01 | 63.75 | 137.26 | 0.00 | 0.00 |
April | 515.95 | 72.50 | 237.81 | 89.97 | 147.84 | 0.00 | 0.00 |
May | 591.09 | 21.97 | 232.70 | 78.49 | 154.21 | 0.00 | 0.00 |
June | 594.78 | 15.87 | 223.90 | 68.70 | 155.21 | 0.00 | 0.00 |
July | 456.26 | 8.78 | 178.74 | 25.46 | 153.28 | 0.00 | 0.00 |
August | 391.97 | 19.82 | 164.04 | 20.65 | 143.39 | 0.00 | 0.00 |
September | 362.51 | 51.28 | 170.82 | 37.96 | 132.86 | 0.00 | 0.00 |
October | 324.88 | 155.07 | 170.00 | 52.98 | 117.03 | 0.00 | 0.00 |
November | 232.15 | 251.74 | 151.65 | 51.30 | 100.35 | 0.00 | 0.00 |
December | 156.60 | 290.28 | 132.12 | 39.41 | 92.71 | 0.00 | 0.00 |
Annual Sum or Average | 363.42 | 128.24 | 179.66 | 51.17 | 128.49 | 0.00 | 0.00 |
Minimum of Months | 156.60 | 8.78 | 132.12 | 20.65 | 92.71 | 0.00 | 0.00 |
Maximum of Months | 594.78 | 290.28 | 237.81 | 89.97 | 155.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 622.75 | 533.47 | 424.91 | 226.16 | 198.75 | 0.00 | 0.00 |
February | 826.29 | 488.70 | 537.07 | 298.78 | 238.28 | 0.00 | 0.00 |
March | 1190.13 | 417.52 | 726.91 | 435.99 | 290.92 | 0.00 | 0.00 |
April | 1681.79 | 281.18 | 936.09 | 656.17 | 279.92 | 0.00 | 0.00 |
May | 1867.43 | 151.00 | 993.95 | 688.57 | 305.39 | 0.00 | 0.00 |
June | 1777.15 | 102.84 | 930.25 | 593.76 | 336.50 | 0.00 | 0.00 |
July | 1260.46 | 70.50 | 650.12 | 234.77 | 415.35 | 0.00 | 0.00 |
August | 1075.46 | 101.73 | 561.37 | 161.43 | 399.94 | 0.00 | 0.00 |
September | 1023.94 | 188.98 | 575.47 | 244.02 | 331.45 | 0.00 | 0.00 |
October | 1103.16 | 416.71 | 646.06 | 410.40 | 235.66 | 0.00 | 0.00 |
November | 828.20 | 576.96 | 534.13 | 350.43 | 183.71 | 0.00 | 0.00 |
December | 587.40 | 600.28 | 411.54 | 220.41 | 191.13 | 0.00 | 0.00 |
Annual Sum or Average | 1154.46 | 326.60 | 660.76 | 376.46 | 284.30 | 0.00 | 0.00 |
Minimum of Months | 587.40 | 70.50 | 411.54 | 161.43 | 183.71 | 0.00 | 0.00 |
Maximum of Months | 1867.43 | 600.28 | 993.95 | 688.57 | 415.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 11787.06 | 6939.31 | 2224.72 | 1188.63 | 1036.08 | 0.00 | 0.00 |
February | 14374.59 | 6131.24 | 2796.86 | 1554.68 | 1242.18 | 0.00 | 0.00 |
March | 23992.49 | 6216.08 | 3764.52 | 2247.94 | 1516.58 | 0.00 | 0.00 |
April | 38234.73 | 8102.28 | 4830.89 | 3371.65 | 1459.24 | 0.00 | 0.00 |
May | 46477.86 | 7982.18 | 5122.37 | 3530.38 | 1591.99 | 0.00 | 0.00 |
June | 40169.39 | 7803.80 | 4794.12 | 3039.95 | 1754.17 | 0.00 | 0.00 |
July | 29498.34 | 4842.18 | 3368.26 | 1203.03 | 2165.23 | 0.00 | 0.00 |
August | 23717.72 | 4822.19 | 2913.26 | 828.34 | 2084.92 | 0.00 | 0.00 |
September | 21932.21 | 6802.38 | 2985.17 | 1257.33 | 1727.84 | 0.00 | 0.00 |
October | 24407.77 | 8313.29 | 3349.35 | 2120.85 | 1228.50 | 0.00 | 0.00 |
November | 16383.04 | 8131.22 | 2788.45 | 1830.79 | 957.66 | 0.00 | 0.00 |
December | 10540.76 | 7450.29 | 2160.08 | 1163.74 | 996.34 | 0.00 | 0.00 |
Annual Sum or Average | 25170.28 | 6959.99 | 3425.34 | 1943.27 | 1482.07 | 0.00 | 0.00 |
Minimum of Months | 10540.76 | 4822.19 | 2160.08 | 828.34 | 957.66 | 0.00 | 0.00 |
Maximum of Months | 46477.86 | 8313.29 | 5122.37 | 3530.38 | 2165.23 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.445648E+09 | 0.710335E+09 | 0.364753E+09 | 0.110936E+09 | 0.253817E+09 | 0.00 | 0.00 |
February | 0.533787E+09 | 0.551969E+09 | 0.379445E+09 | 0.108312E+09 | 0.271133E+09 | 0.00 | 0.00 |
March | 0.916398E+09 | 0.439106E+09 | 0.538374E+09 | 0.170739E+09 | 0.367635E+09 | 0.00 | 0.00 |
April | 0.133736E+10 | 0.187920E+09 | 0.616391E+09 | 0.233196E+09 | 0.383195E+09 | 0.00 | 0.00 |
May | 0.158319E+10 | 58841315.10 | 0.623271E+09 | 0.210225E+09 | 0.413046E+09 | 0.00 | 0.00 |
June | 0.154166E+10 | 41136773.45 | 0.580357E+09 | 0.178063E+09 | 0.402293E+09 | 0.00 | 0.00 |
July | 0.122204E+10 | 23515206.10 | 0.478742E+09 | 68189091.94 | 0.410553E+09 | 0.00 | 0.00 |
August | 0.104986E+10 | 53099024.12 | 0.439354E+09 | 55308477.66 | 0.384046E+09 | 0.00 | 0.00 |
September | 0.939628E+09 | 0.132906E+09 | 0.442764E+09 | 98394621.40 | 0.344369E+09 | 0.00 | 0.00 |
October | 0.870156E+09 | 0.415330E+09 | 0.455337E+09 | 0.141891E+09 | 0.313446E+09 | 0.00 | 0.00 |
November | 0.601728E+09 | 0.652506E+09 | 0.393083E+09 | 0.132981E+09 | 0.260102E+09 | 0.00 | 0.00 |
December | 0.419431E+09 | 0.777496E+09 | 0.353869E+09 | 0.105553E+09 | 0.248316E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.114609E+11 | 0.404416E+10 | 0.566574E+10 | 0.161379E+10 | 0.405195E+10 | 0.00 | 0.00 |
Minimum of Months | 0.419431E+09 | 23515206.10 | 0.353869E+09 | 55308477.66 | 0.248316E+09 | 0.00 | 0.00 |
Maximum of Months | 0.158319E+10 | 0.777496E+09 | 0.623271E+09 | 0.233196E+09 | 0.413046E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.166799E+10 | 0.142884E+10 | 0.113808E+10 | 0.605750E+09 | 0.532329E+09 | 0.00 | 0.00 |
February | 0.199895E+10 | 0.118226E+10 | 0.129927E+10 | 0.722817E+09 | 0.576457E+09 | 0.00 | 0.00 |
March | 0.318765E+10 | 0.111829E+10 | 0.194695E+10 | 0.116775E+10 | 0.779203E+09 | 0.00 | 0.00 |
April | 0.435919E+10 | 0.728809E+09 | 0.242634E+10 | 0.170079E+10 | 0.725555E+09 | 0.00 | 0.00 |
May | 0.500172E+10 | 0.404428E+09 | 0.266221E+10 | 0.184426E+10 | 0.817948E+09 | 0.00 | 0.00 |
June | 0.460636E+10 | 0.266559E+09 | 0.241122E+10 | 0.153902E+10 | 0.872199E+09 | 0.00 | 0.00 |
July | 0.337601E+10 | 0.188827E+09 | 0.174128E+10 | 0.628808E+09 | 0.111247E+10 | 0.00 | 0.00 |
August | 0.288052E+10 | 0.272484E+09 | 0.150358E+10 | 0.432369E+09 | 0.107121E+10 | 0.00 | 0.00 |
September | 0.265406E+10 | 0.489832E+09 | 0.149162E+10 | 0.632510E+09 | 0.859110E+09 | 0.00 | 0.00 |
October | 0.295471E+10 | 0.111611E+10 | 0.173040E+10 | 0.109921E+10 | 0.631192E+09 | 0.00 | 0.00 |
November | 0.214669E+10 | 0.149549E+10 | 0.138447E+10 | 0.908302E+09 | 0.476164E+09 | 0.00 | 0.00 |
December | 0.157330E+10 | 0.160779E+10 | 0.110226E+10 | 0.590351E+09 | 0.511911E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.364071E+11 | 0.102997E+11 | 0.208377E+11 | 0.118719E+11 | 0.896575E+10 | 0.00 | 0.00 |
Minimum of Months | 0.157330E+10 | 0.188827E+09 | 0.110226E+10 | 0.432369E+09 | 0.476164E+09 | 0.00 | 0.00 |
Maximum of Months | 0.500172E+10 | 0.160779E+10 | 0.266221E+10 | 0.184426E+10 | 0.111247E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.315705E+11 | 0.185863E+11 | 0.595868E+10 | 0.318363E+10 | 0.277504E+10 | 0.00 | 0.00 |
February | 0.347750E+11 | 0.148327E+11 | 0.676617E+10 | 0.376108E+10 | 0.300508E+10 | 0.00 | 0.00 |
March | 0.642615E+11 | 0.166491E+11 | 0.100829E+11 | 0.602088E+10 | 0.406201E+10 | 0.00 | 0.00 |
April | 0.991044E+11 | 0.210011E+11 | 0.125217E+11 | 0.873932E+10 | 0.378234E+10 | 0.00 | 0.00 |
May | 0.124486E+12 | 0.213795E+11 | 0.137198E+11 | 0.945577E+10 | 0.426398E+10 | 0.00 | 0.00 |
June | 0.104119E+12 | 0.202274E+11 | 0.124263E+11 | 0.787955E+10 | 0.454680E+10 | 0.00 | 0.00 |
July | 0.790084E+11 | 0.129693E+11 | 0.902156E+10 | 0.322221E+10 | 0.579935E+10 | 0.00 | 0.00 |
August | 0.635255E+11 | 0.129157E+11 | 0.780289E+10 | 0.221863E+10 | 0.558426E+10 | 0.00 | 0.00 |
September | 0.568483E+11 | 0.176318E+11 | 0.773756E+10 | 0.325900E+10 | 0.447856E+10 | 0.00 | 0.00 |
October | 0.653738E+11 | 0.222663E+11 | 0.897091E+10 | 0.568049E+10 | 0.329042E+10 | 0.00 | 0.00 |
November | 0.424648E+11 | 0.210761E+11 | 0.722767E+10 | 0.474541E+10 | 0.248226E+10 | 0.00 | 0.00 |
December | 0.282324E+11 | 0.199549E+11 | 0.578556E+10 | 0.311696E+10 | 0.266861E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.793770E+12 | 0.219490E+12 | 0.108022E+12 | 0.612829E+11 | 0.467387E+11 | 0.00 | 0.00 |
Minimum of Months | 0.282324E+11 | 0.129157E+11 | 0.578556E+10 | 0.221863E+10 | 0.248226E+10 | 0.00 | 0.00 |
Maximum of Months | 0.124486E+12 | 0.222663E+11 | 0.137198E+11 | 0.945577E+10 | 0.579935E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.38 | 7.87 | 1.20 | 0.38 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.78 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.60 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.33 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.97 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.39 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.29 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.70 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.74 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.46 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.88 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.77 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.38 | 7.87 | 0.66 | 0.38 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.20 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.20 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.50 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.67 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.64 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.53 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.36 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.58 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.68 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.05 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.17 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.30 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.20 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.68 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.56 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.58 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.74 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.62 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.38 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.42 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.18 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.17 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.06 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.93 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.62 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.18 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.48 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.26 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.04 | 0.00 | 15.61 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.70 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.41 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.59 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.48 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.760771E+09 | -679991254.4 | 0.00 | 0.00 | 744.00 | 0.00 | -80779609.9 | 58.99 | 0.00 | 0.00 |
February | 0.681077E+09 | -611534711.7 | 0.00 | 0.00 | 672.00 | 0.00 | -69542370.5 | 58.99 | 0.00 | 0.00 |
March | 0.739648E+09 | -666818269.6 | 0.00 | 0.00 | 744.00 | 0.00 | -72829945.7 | 58.99 | 0.00 | 0.00 |
April | 0.623907E+09 | -556035993.6 | 0.00 | 0.00 | 720.00 | 0.00 | -67870794.1 | 58.99 | 0.00 | 0.00 |
May | 0.580092E+09 | -510945572.5 | 0.00 | 0.00 | 744.00 | 0.00 | -69146392.6 | 58.98 | 0.00 | 0.00 |
June | 0.523306E+09 | -456438828.5 | 0.00 | 0.00 | 720.00 | 0.00 | -66867291.9 | 58.99 | 0.00 | 0.00 |
July | 0.489482E+09 | -420668475.3 | 0.00 | 0.00 | 744.00 | 0.00 | -68813667.0 | 58.99 | 0.00 | 0.00 |
August | 0.537259E+09 | -467778694.0 | 0.00 | 0.00 | 744.00 | 0.00 | -69480462.5 | 58.99 | 0.00 | 0.00 |
September | 0.548844E+09 | -481496141.9 | 0.00 | 0.00 | 720.00 | 0.00 | -67347468.6 | 58.99 | 0.00 | 0.00 |
October | 0.616955E+09 | -546560620.7 | 0.00 | 0.00 | 744.00 | 0.00 | -70394426.6 | 58.99 | 0.00 | 0.00 |
November | 0.657565E+09 | -586876674.1 | 0.00 | 0.00 | 720.00 | 0.00 | -70688816.7 | 58.99 | 0.00 | 0.00 |
December | 0.737750E+09 | -659814089.6 | 0.00 | 0.00 | 744.00 | 0.00 | -77935458.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.749666E+10 | -0.664496E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -851696704.6 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.489482E+09 | -679991254.4 | 0.00 | 0.00 | 672.00 | 0.00 | -80779609.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.760771E+09 | -420668475.3 | 0.00 | 0.00 | 744.00 | 0.00 | -66867291.9 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.75 | 0.50 | 01-JAN-11:30 | 169.44 | 0.00 | 0.00 | 13.00 | 585.27 | 0.00 | 0.00 | 20.17 |
February | 303.83 | 0.71 | 0.50 | 01-FEB-11:09 | 1067.62 | 0.00 | 0.00 | 57.83 | 589.64 | 0.00 | 0.00 | 32.83 |
March | 364.50 | 0.68 | 0.50 | 01-MAR-10:00 | 283.26 | 0.00 | 0.00 | 106.00 | 190.38 | 0.00 | 0.00 | 50.00 |
April | 379.83 | 0.69 | 0.50 | 01-APR-10:30 | 221.85 | 0.00 | 0.00 | 77.67 | 1107.02 | 0.00 | 0.00 | 72.00 |
May | 406.00 | 0.69 | 0.50 | 02-MAY-10:00 | 1515.96 | 0.00 | 0.00 | 142.67 | 180.41 | 0.00 | 0.00 | 43.83 |
June | 386.67 | 0.68 | 0.50 | 01-JUN-09:39 | 856.02 | 0.00 | 0.00 | 152.33 | 189.44 | 0.00 | 0.00 | 53.33 |
July | 379.83 | 0.65 | 0.50 | 01-JUL-10:30 | 768.96 | 0.00 | 0.00 | 196.50 | 235.97 | 0.00 | 0.00 | 107.33 |
August | 372.50 | 0.65 | 0.50 | 01-AUG-09:39 | 497.80 | 0.00 | 0.00 | 184.17 | 350.67 | 0.00 | 0.00 | 134.00 |
September | 344.33 | 0.66 | 0.50 | 01-SEP-09:39 | 278.67 | 0.00 | 0.00 | 143.83 | 218.06 | 0.00 | 0.00 | 91.50 |
October | 347.33 | 0.70 | 0.50 | 01-OCT-10:00 | 204.79 | 0.00 | 0.00 | 44.83 | 323.99 | 0.00 | 0.00 | 22.50 |
November | 317.83 | 0.75 | 0.50 | 06-NOV-10:00 | 165.25 | 0.00 | 0.00 | 0.00 | 803.91 | 0.00 | 0.00 | 29.33 |
December | 315.50 | 0.76 | 0.50 | 05-DEC-11:00 | 164.31 | 0.00 | 0.00 | 0.33 | 139.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4237.50 | 0.69 | 533.67 | 0.00 | 0.00 | 1119.17 | 403.48 | 0.00 | 0.00 | 656.83 | ||
Minimum of Months | 303.83 | 0.65 | 0.50 | 164.31 | 0.00 | 0.00 | 0.00 | 139.32 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 406.00 | 0.76 | 0.50 | 1515.96 | 0.00 | 0.00 | 196.50 | 1107.02 | 0.00 | 0.00 | 134.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.64 | 0.50 | 01-JAN-09:20 | 198.76 | 12.14 | 0.00 | 159.00 | 164.47 | 15.62 | 11.00 | 112.67 |
February | 303.83 | 0.61 | 0.50 | 01-FEB-09:09 | 233.09 | 12.97 | 0.00 | 177.33 | 720.80 | 18.38 | 56.50 | 137.67 |
March | 364.50 | 0.60 | 0.50 | 01-MAR-08:50 | 270.70 | 13.39 | 0.00 | 242.00 | 255.76 | 17.18 | 82.00 | 192.67 |
April | 379.83 | 0.60 | 0.50 | 01-APR-07:00 | 1536.68 | 12.91 | 0.00 | 253.17 | 1754.62 | 16.71 | 85.83 | 194.33 |
May | 406.00 | 0.59 | 0.50 | 01-MAY-07:30 | 273.53 | 12.95 | 0.00 | 282.33 | 230.83 | 16.56 | 86.17 | 219.83 |
June | 386.67 | 0.58 | 0.50 | 01-JUN-07:40 | 299.25 | 13.00 | 0.00 | 279.83 | 253.13 | 16.38 | 79.00 | 216.67 |
July | 379.83 | 0.57 | 0.50 | 01-JUL-07:19 | 354.64 | 14.09 | 0.00 | 280.83 | 311.00 | 17.24 | 71.83 | 244.50 |
August | 372.50 | 0.58 | 0.50 | 01-AUG-07:30 | 505.12 | 14.00 | 0.00 | 263.33 | 452.67 | 17.33 | 71.50 | 230.67 |
September | 344.33 | 0.58 | 0.50 | 01-SEP-07:40 | 393.64 | 13.80 | 0.00 | 243.33 | 302.02 | 18.56 | 91.17 | 208.00 |
October | 347.33 | 0.61 | 0.50 | 01-OCT-07:00 | 237.86 | 12.75 | 0.00 | 220.00 | 437.72 | 16.72 | 69.33 | 170.83 |
November | 317.83 | 0.62 | 0.50 | 01-NOV-08:30 | 195.73 | 12.12 | 0.00 | 167.33 | 1191.46 | 17.79 | 51.33 | 129.17 |
December | 315.50 | 0.63 | 0.50 | 01-DEC-09:20 | 193.80 | 12.23 | 0.00 | 158.50 | 160.16 | 15.74 | 0.00 | 105.00 |
Annual Sum or Average | 4237.50 | 0.60 | 403.02 | 13.06 | 0.00 | 2727.00 | 517.95 | 17.00 | 755.67 | 2162.00 | ||
Minimum of Months | 303.83 | 0.57 | 0.50 | 193.80 | 12.12 | 0.00 | 158.50 | 160.16 | 15.62 | 0.00 | 105.00 | |
Maximum of Months | 406.00 | 0.64 | 0.50 | 1536.68 | 14.09 | 0.00 | 282.33 | 1754.62 | 18.56 | 91.17 | 244.50 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.83 | 0.65 | 31-JAN-16:10 | 208.22 | 21.96 | 140.50 | 24.00 | 96.60 | 19.60 | 109.67 | 0.00 |
February | 303.83 | 0.81 | 0.61 | 20-FEB-16:30 | 259.60 | 22.65 | 135.17 | 33.50 | 113.02 | 20.46 | 116.67 | 0.00 |
March | 364.50 | 0.79 | 0.61 | 01-MAR-16:19 | 294.01 | 22.55 | 164.17 | 54.50 | 225.38 | 23.08 | 176.67 | 37.83 |
April | 379.83 | 0.79 | 0.61 | 01-APR-15:09 | 214.34 | 19.85 | 126.83 | 39.67 | 185.41 | 21.01 | 155.00 | 47.50 |
May | 406.00 | 0.79 | 0.61 | 01-MAY-15:09 | 214.54 | 19.25 | 112.17 | 36.17 | 176.88 | 20.53 | 150.00 | 41.83 |
June | 386.67 | 0.79 | 0.61 | 01-JUN-15:20 | 223.29 | 19.10 | 107.33 | 39.33 | 173.68 | 20.36 | 146.50 | 32.00 |
July | 379.83 | 0.80 | 0.61 | 01-JUL-14:00 | 214.86 | 19.17 | 98.17 | 26.50 | 137.60 | 20.28 | 135.17 | 11.33 |
August | 372.50 | 0.81 | 0.61 | 04-AUG-15:09 | 202.69 | 18.98 | 92.33 | 22.33 | 125.97 | 19.96 | 130.17 | 6.33 |
September | 344.33 | 0.80 | 0.61 | 01-SEP-14:50 | 241.85 | 20.83 | 126.33 | 45.50 | 163.60 | 21.50 | 146.83 | 17.50 |
October | 347.33 | 0.80 | 0.61 | 01-OCT-15:09 | 225.10 | 22.02 | 148.50 | 40.67 | 149.74 | 22.32 | 147.83 | 20.50 |
November | 317.83 | 0.81 | 0.61 | 01-NOV-16:10 | 249.89 | 22.80 | 138.00 | 28.33 | 112.38 | 21.17 | 114.67 | 2.33 |
December | 315.50 | 0.82 | 0.65 | 02-DEC-15:30 | 278.35 | 23.33 | 144.67 | 42.00 | 96.06 | 19.85 | 106.83 | 0.00 |
Annual Sum or Average | 4237.50 | 0.80 | 234.39 | 20.92 | 1534.17 | 432.50 | 148.74 | 20.85 | 1636.00 | 217.17 | ||
Minimum of Months | 303.83 | 0.79 | 0.61 | 202.69 | 18.98 | 92.33 | 22.33 | 96.06 | 19.60 | 106.83 | 0.00 | |
Maximum of Months | 406.00 | 0.83 | 0.65 | 294.01 | 23.33 | 164.17 | 54.50 | 225.38 | 23.08 | 176.67 | 47.50 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.862988E+09 | 28386.52 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.196533E+09 | 20785.57 | 02-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3783861.29 | 2534.34 | 27-NOV-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.244990E+09 | 28260.54 | 23-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.862988E+09 | 28386.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.278880E+09 | 62709.34 | 03-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.278880E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.278880E+09 | 62709.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.457707E+09 | 0.411411E+09 | 3370.61 | 14-JAN-16:00 | 2729.68 | 0.00 |
February | 0.00 | 0.00 | 0.199961E+10 | 0.175448E+10 | 6647.63 | 24-FEB-15:50 | 5695.12 | 0.00 |
March | 0.00 | 0.00 | 0.643047E+10 | 0.567563E+10 | 27343.88 | 11-MAR-06:01 | 20800.70 | 0.00 |
April | 0.00 | 0.00 | 0.102172E+11 | 0.929081E+10 | 27511.39 | 03-APR-05:01 | 22039.22 | 0.00 |
May | 0.00 | 0.00 | 0.148543E+11 | 0.122641E+11 | 30215.49 | 24-MAY-05:01 | 17415.01 | 0.00 |
June | 0.00 | 0.00 | 0.167448E+11 | 0.126112E+11 | 30945.82 | 26-JUN-05:01 | 14952.98 | 0.00 |
July | 0.00 | 0.00 | 0.175205E+11 | 0.113425E+11 | 31311.43 | 19-JUL-05:01 | 14991.88 | 0.00 |
August | 0.00 | 0.00 | 0.182784E+11 | 0.113911E+11 | 31524.79 | 16-AUG-05:01 | 16333.00 | 0.00 |
September | 0.00 | 0.00 | 0.146385E+11 | 0.976983E+10 | 31609.68 | 09-SEP-05:01 | 15251.11 | 0.00 |
October | 0.00 | 0.00 | 0.992299E+10 | 0.816181E+10 | 29306.40 | 12-OCT-05:01 | 18254.18 | 0.00 |
November | 0.00 | 0.00 | 0.518801E+10 | 0.462315E+10 | 26204.41 | 09-NOV-06:02 | 21228.75 | 0.00 |
December | 0.00 | 0.00 | 0.145065E+10 | 0.130274E+10 | 5198.80 | 02-DEC-15:10 | 5007.51 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.117703E+12 | 0.885987E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.457707E+09 | 0.411411E+09 | 3370.61 | 2729.68 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.182784E+11 | 0.126112E+11 | 31609.68 | 22039.22 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.234194E+09 | 0.202746E+09 | 5676.78 | 22-FEB-15:00 | 4948.30 | 0.00 |
March | 0.00 | 0.00 | 0.902371E+10 | 0.778762E+10 | 72683.27 | 12-MAR-14:53 | 68721.28 | 0.00 |
April | 0.00 | 0.00 | 0.307554E+11 | 0.280660E+11 | 83020.92 | 18-APR-17:06 | 71699.78 | 0.00 |
May | 0.00 | 0.00 | 0.529430E+11 | 0.445910E+11 | 93703.03 | 24-MAY-05:01 | 54263.20 | 0.00 |
June | 0.00 | 0.00 | 0.587199E+11 | 0.453628E+11 | 97290.17 | 29-JUN-05:07 | 60418.28 | 0.00 |
July | 0.00 | 0.00 | 0.587135E+11 | 0.380550E+11 | 100697.10 | 25-JUL-05:06 | 53161.29 | 0.00 |
August | 0.00 | 0.00 | 0.525284E+11 | 0.322460E+11 | 98076.74 | 18-AUG-17:08 | 56944.93 | 0.00 |
September | 0.00 | 0.00 | 0.383490E+11 | 0.252359E+11 | 101832.24 | 06-SEP-05:01 | 58061.83 | 0.00 |
October | 0.00 | 0.00 | 0.217834E+11 | 0.178560E+11 | 81610.54 | 09-OCT-13:02 | 80323.48 | 0.00 |
November | 0.00 | 0.00 | 0.525757E+10 | 0.451899E+10 | 34087.37 | 11-NOV-14:45 | 31599.44 | 0.00 |
December | 0.00 | 0.00 | 14474898.31 | 13723307.58 | 1461.27 | 01-DEC-14:40 | 1385.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.328323E+12 | 0.243936E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.587199E+11 | 0.453628E+11 | 101832.24 | 80323.48 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.549433E+09 | 0.23 | 1315.83 | 02-JAN-06:01 | 0.93 |
February | 0.485551E+09 | 0.22 | 963.50 | 02-FEB-06:03 | 0.93 |
March | 0.570357E+09 | 0.23 | 1315.83 | 10-MAR-06:02 | 0.92 |
April | 0.580049E+09 | 0.24 | 1315.83 | 01-APR-05:01 | 0.92 |
May | 0.744609E+09 | 0.28 | 1315.83 | 01-MAY-05:01 | 0.93 |
June | 0.819581E+09 | 0.31 | 1315.83 | 01-JUN-05:01 | 0.92 |
July | 0.796414E+09 | 0.29 | 1315.83 | 01-JUL-05:01 | 0.92 |
August | 0.807246E+09 | 0.29 | 1315.83 | 01-AUG-05:01 | 0.91 |
September | 0.651635E+09 | 0.26 | 1315.83 | 01-SEP-05:01 | 0.91 |
October | 0.555216E+09 | 0.23 | 1315.83 | 02-OCT-05:01 | 0.92 |
November | 0.505237E+09 | 0.21 | 1315.83 | 01-NOV-05:02 | 0.92 |
December | 0.528447E+09 | 0.21 | 1309.99 | 23-DEC-06:02 | 0.93 |
Annual Sum or Average | 0.759378E+10 | 0.25 | |||
Minimum of Months | 0.485551E+09 | 0.21 | 963.50 | 0.91 | |
Maximum of Months | 0.819581E+09 | 0.31 | 1315.83 | 0.93 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.146090E+10 | 0.21 | 2223.33 | 03-JAN-06:01 | 0.89 |
February | 0.133562E+10 | 0.20 | 1466.43 | 22-FEB-14:30 | 0.54 |
March | 0.160669E+10 | 0.24 | 3131.63 | 12-MAR-14:53 | 0.83 |
April | 0.179444E+10 | 0.35 | 3666.07 | 13-APR-17:06 | 0.89 |
May | 0.232586E+10 | 0.44 | 3666.07 | 01-MAY-17:05 | 0.89 |
June | 0.242662E+10 | 0.45 | 3666.07 | 01-JUN-17:06 | 0.89 |
July | 0.231970E+10 | 0.44 | 3666.07 | 01-JUL-17:06 | 0.88 |
August | 0.216480E+10 | 0.42 | 3666.07 | 01-AUG-17:06 | 0.89 |
September | 0.184598E+10 | 0.38 | 3666.07 | 01-SEP-05:06 | 0.89 |
October | 0.162557E+10 | 0.28 | 3666.07 | 01-OCT-14:02 | 0.89 |
November | 0.141037E+10 | 0.21 | 1466.43 | 04-NOV-11:40 | 0.54 |
December | 0.145176E+10 | 0.20 | 1466.43 | 02-DEC-14:30 | 0.54 |
Annual Sum or Average | 0.217683E+11 | 0.32 | |||
Minimum of Months | 0.133562E+10 | 0.20 | 1466.43 | 0.54 | |
Maximum of Months | 0.242662E+10 | 0.45 | 3666.07 | 0.89 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.663747E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.975697E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.215981E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.326914E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.480357E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.530113E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.515145E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.520844E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.416525E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.298202E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.176786E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.885434E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.373336E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.663747E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.530113E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.146090E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.140399E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.425570E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.112329E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.188693E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.204265E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.191134E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.167574E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.125914E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.793373E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.293087E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.145590E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.118432E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.140399E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.204265E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.549433E+09 | 0.457707E+09 | 0.862988E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.485551E+09 | 0.199961E+10 | 0.196533E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.570357E+09 | 0.643047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.580049E+09 | 0.102172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.744609E+09 | 0.148543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.819581E+09 | 0.167448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.796414E+09 | 0.175205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.807246E+09 | 0.182784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.651635E+09 | 0.146385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.555216E+09 | 0.992299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.505237E+09 | 0.518801E+10 | 3783861.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.528447E+09 | 0.145065E+10 | 0.244990E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.759378E+10 | 0.117703E+12 | 0.130829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.485551E+09 | 0.457707E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.819581E+09 | 0.182784E+11 | 0.862988E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.146090E+10 | 0.00 | 0.278880E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133562E+10 | 0.234194E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160669E+10 | 0.902371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.179444E+10 | 0.307554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.232586E+10 | 0.529430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.242662E+10 | 0.587199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.231970E+10 | 0.587135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.216480E+10 | 0.525284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.184598E+10 | 0.383490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162557E+10 | 0.217834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141037E+10 | 0.525757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145176E+10 | 14474898.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217683E+11 | 0.328323E+12 | 0.278880E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.242662E+10 | 0.587199E+11 | 0.278880E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.549433E+09 | 0.00 | 0.00 | 0.00 | 0.114313E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.485551E+09 | 0.00 | 0.00 | 0.00 | 0.490146E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.570357E+09 | 0.00 | 0.00 | 0.00 | 0.158945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.580049E+09 | 0.00 | 0.00 | 0.00 | 0.268909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.744609E+09 | 0.00 | 0.00 | 0.00 | 0.405897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.819581E+09 | 0.00 | 0.00 | 0.00 | 0.448155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.796414E+09 | 0.00 | 0.00 | 0.00 | 0.435504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.807246E+09 | 0.00 | 0.00 | 0.00 | 0.440120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.651635E+09 | 0.00 | 0.00 | 0.00 | 0.351362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.555216E+09 | 0.00 | 0.00 | 0.00 | 0.242681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.505237E+09 | 0.00 | 0.00 | 0.00 | 0.126262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.528447E+09 | 0.00 | 0.00 | 0.00 | 0.356987E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.759378E+10 | 0.00 | 0.00 | 0.00 | 0.297398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.485551E+09 | 0.00 | 0.00 | 0.00 | 0.114313E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.819581E+09 | 0.00 | 0.00 | 0.00 | 0.448155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.146090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133562E+10 | 0.00 | 0.00 | 0.00 | 68372790.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160669E+10 | 0.00 | 0.00 | 0.00 | 0.264901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.179444E+10 | 0.00 | 0.00 | 0.00 | 0.943844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.232586E+10 | 0.00 | 0.00 | 0.00 | 0.165435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.242662E+10 | 0.00 | 0.00 | 0.00 | 0.179998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.231970E+10 | 0.00 | 0.00 | 0.00 | 0.167937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.216480E+10 | 0.00 | 0.00 | 0.00 | 0.145926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.184598E+10 | 0.00 | 0.00 | 0.00 | 0.107455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162557E+10 | 0.00 | 0.00 | 0.00 | 0.630816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141037E+10 | 0.00 | 0.00 | 0.00 | 0.152050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145176E+10 | 0.00 | 0.00 | 0.00 | 4137329.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217683E+11 | 0.00 | 0.00 | 0.00 | 0.966636E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.242662E+10 | 0.00 | 0.00 | 0.00 | 0.179998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.540676E+09 | 0.00 | 0.00 | 662124.38 | 0.00 | 0.247242E+09 | 0.272003E+09 | 0.00 | 0.14 |
February | 0.243038E+09 | 17098266.24 | 0.00 | 2019682.51 | 0.00 | 67462276.34 | 0.299213E+09 | 0.00 | 0.14 |
March | 44675368.80 | 0.328688E+09 | 0.00 | 4322854.02 | 126943.60 | 0.00 | 0.179825E+09 | 0.00 | 0.15 |
April | 0.00 | 0.103921E+10 | 0.00 | 864641.95 | 0.00 | 0.00 | 7082869.41 | 0.00 | 0.15 |
May | 0.00 | 0.234838E+10 | 0.00 | 109393.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
June | 0.00 | 0.318188E+10 | 0.00 | 29595.84 | 0.00 | 0.00 | 18240.69 | 0.00 | 0.16 |
July | 0.00 | 0.377548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
August | 0.00 | 0.400725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
September | 0.00 | 0.293616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
October | 1737934.25 | 0.104037E+10 | 0.00 | 2224554.05 | 0.00 | 0.00 | 26564965.32 | 0.00 | 0.14 |
November | 83935070.66 | 0.172728E+09 | 0.00 | 3210208.40 | 0.00 | 3165741.95 | 0.211039E+09 | 0.00 | 0.14 |
December | 0.374717E+09 | 0.00 | 0.00 | 2163936.50 | 0.00 | 0.102362E+09 | 0.466685E+09 | 0.00 | 0.14 |
Annual Sum or Average | 0.128878E+10 | 0.188472E+11 | 0.00 | 15606990.85 | 126943.60 | 0.420233E+09 | 0.146243E+10 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.540676E+09 | 0.400725E+10 | 0.00 | 4322854.02 | 126943.60 | 0.247242E+09 | 0.466685E+09 | 0.00 | 0.16 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.302415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72309003.21 | 0.00 | 0.00 | 0.19 |
February | 0.255319E+10 | 0.00 | 0.00 | 213072.12 | 0.00 | 0.00 | 0.134237E+09 | 0.00 | 0.20 |
March | 0.111274E+10 | 0.556224E+09 | 0.00 | 5495703.81 | 5970148.92 | 0.00 | 0.926451E+09 | 0.00 | 0.22 |
April | 43940783.45 | 0.350208E+10 | 0.00 | 2572056.63 | 17766710.11 | 0.00 | 0.102038E+09 | 0.00 | 0.23 |
May | 0.00 | 0.992925E+10 | 0.00 | 107432.03 | 8580196.25 | 0.00 | 2545109.15 | 0.00 | 0.27 |
June | 0.00 | 0.143770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
July | 0.00 | 0.166908E+11 | 0.00 | 0.00 | 2153887.89 | 0.00 | 0.00 | 0.00 | 0.27 |
August | 0.00 | 0.164170E+11 | 0.00 | 0.00 | 8566293.17 | 0.00 | 0.00 | 0.00 | 0.27 |
September | 0.00 | 0.106600E+11 | 0.00 | 0.00 | 19001291.20 | 0.00 | 0.00 | 0.00 | 0.24 |
October | 0.195849E+09 | 0.275106E+10 | 0.00 | 2137850.85 | 33629067.29 | 0.00 | 0.210573E+09 | 0.00 | 0.21 |
November | 0.152626E+10 | 96369918.00 | 0.00 | 4689503.84 | 0.00 | 0.00 | 0.735884E+09 | 0.00 | 0.20 |
December | 0.358669E+10 | 0.00 | 0.00 | 27089.98 | 0.00 | 0.00 | 55051663.46 | 0.00 | 0.19 |
Annual Sum or Average | 0.120428E+11 | 0.749798E+11 | 0.00 | 15242709.27 | 95667594.84 | 72309003.21 | 0.216678E+10 | 0.00 | 0.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
Maximum of Months | 0.358669E+10 | 0.166908E+11 | 0.00 | 5495703.81 | 33629067.29 | 72309003.21 | 0.926451E+09 | 0.00 | 0.28 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:02
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.526253E+12 | 0.995307E+10 | 0.00 | 0.130587E+11 | 0.111407E+10 |
February | 0.610895E+12 | 0.130520E+11 | 0.00 | 0.945456E+10 | 0.289004E+10 |
March | 0.883745E+12 | 0.215274E+11 | 0.00 | 0.431432E+10 | 0.196926E+11 |
April | 0.102091E+13 | 0.470245E+11 | 0.00 | -0.719630E+10 | 0.531001E+11 |
May | 0.111987E+13 | 0.634909E+11 | 0.00 | -0.182583E+11 | 0.883997E+11 |
June | 0.102658E+13 | 0.610852E+11 | 0.00 | -0.263516E+11 | 0.979461E+11 |
July | 0.813340E+12 | 0.604777E+11 | 0.00 | -0.312023E+11 | 0.973827E+11 |
August | 0.688994E+12 | 0.598030E+11 | 0.00 | -0.318534E+11 | 0.898005E+11 |
September | 0.736319E+12 | 0.431917E+11 | 0.00 | -0.239617E+11 | 0.672465E+11 |
October | 0.741137E+12 | 0.361060E+11 | 0.00 | -0.609498E+10 | 0.404414E+11 |
November | 0.620312E+12 | 0.137328E+11 | 0.00 | 0.860631E+10 | 0.132307E+11 |
December | 0.494228E+12 | 0.111030E+11 | 0.00 | 0.149828E+11 | 0.194997E+10 |
Annual Sum or Average | 0.928259E+13 | 0.440547E+12 | 0.00 | -0.945018E+11 | 0.573195E+12 |
Minimum of Months | 0.494228E+12 | 0.995307E+10 | 0.00 | -0.318534E+11 | 0.111407E+10 |
Maximum of Months | 0.111987E+13 | 0.634909E+11 | 0.00 | 0.149828E+11 | 0.979461E+11 |