Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2023-10-16 10:43:19
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 377.55 | 78.08 | 78.08 |
Net Site Energy | 246.03 | 50.88 | 50.88 |
Total Source Energy | 1189.13 | 245.94 | 245.94 |
Net Source Energy | 772.63 | 159.80 | 159.80 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 3.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 64.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 73.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 42.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 34.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 23.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 374.40 | 3.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 3.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 64.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 73.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 42.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 13.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 20.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 23.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 3.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 64.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 73.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 42.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 34.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 23.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 23.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 25.25 | 0.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 77.43 | 0.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 23.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 25.25 | 0.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 77.43 | 0.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 137.285 | 36.67 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -5.77 | -1.5 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 131.513 | 35.13 |
Electricity Coming From Utility | 257.978 | 68.90 |
Surplus Electricity Going To Utility | 15.091 | 4.03 |
Net Electricity From Utility | 242.886 | 64.87 |
Total On-Site and Utility Electric Sources | 374.399 | 100.00 |
Total Electricity End Uses | 374.399 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 4.83 |
Time Setpoint Not Met During Occupied Cooling | 47.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2959.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 68.38 |
Skylight-Roof Ratio [%] | 1.49 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 6.1633 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 6.6844 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.1969 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.3473 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.3473 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 6.1633 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 6.6844 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.1969 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.3473 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.3473 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.3473 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 03-AUG-15:30 | 10-JAN-07:10 | - | - | - | - | - | - | - | - | - | - | 13-JUL-11:39 |
Heating | 0.00 | 20505.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 14580.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3674.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4712.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1577.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 34579.82 | 20505.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 20505.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 14580.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3674.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2407.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1577.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 3.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 233.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 133.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 108.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 73.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1185.72 | 3.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 42.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 48.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 22.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 245.23 | 0.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 42.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 48.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 22.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 245.23 | 0.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.06 |
ZONE2 FINE STORAGE DIRECT AIR | 2.48 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 0.992790 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 0.992790 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 40597.98 |
PSZ-OFFICE HEATING COIL | 26263.03 |
PSZ-FINE STORAGE HEATING COIL | 78825.08 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 40597.98 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.00 | 1.00 | 1.06 |
PSZ-FINE STORAGE | 2.48 | 2.48 | 2.48 | 2.48 | 2.48 | 2.48 | 1.00 | 1.00 | 2.48 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.06 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.48 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.06 | 1168.84 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.48 | 2650.60 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 0.696769 | 21775.91 | 26263.03 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.48 | 2.48 | 2.48 | 1.63 | 61512.02 | 78825.08 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.06 | 0.527855 | 0.703807 | 21775.91 | 10887.95 | 0.764050 | 0.764050 |
PSZ-FINE STORAGE COOLING COIL | 2.48 | 1.24 | 1.65 | 61512.02 | 30756.01 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 6.163 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 14.237 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 6.684 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.684 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.197 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 5.756 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1459.960 | 6.163 | 114.518 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1459.960 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 9314.081 | 6.684 | 310.469 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 9314.081 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 10245.499 | 3.197 | 148.485 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10245.499 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2405 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5892 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.6534 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 1.134 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 1.134 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.158 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.697 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.431 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7826 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7826 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.77015739E-08 | 0.38457199E-13 | 0.23136523E-13 | 0.0000000 |
2 | 1 | -5.2160498 | 0.48395528E-04 | -0.66612159E-04 | 0.14765390E-08 |
3 | 0 | 5.4565497 | 0.24045158 | 0.24056658 | |
4 | 2 | 0.53319589E-11 | 0.95168195E-16 | 0.18684196E-15 | 0.0000000 |
5 | 1 | -5.2159738 | 0.43009049E-04 | -0.27188221E-04 | 0.68723469E-11 |
6 | 0 | 5.8052090 | 0.58919217 | 0.58926237 | |
7 | 4 | 0.74747876E-12 | 0.20825084E-15 | -0.25659737E-14 | 0.12362927E-15 |
8 | 3 | -0.37328678E-03 | 0.45238042E-06 | -0.54038165E-04 | 0.14344535E-12 |
9 | 2 | 1.7123825 | 0.10013958E-01 | 1.1198054 | -0.71564441E-04 |
10 | 1 | -7.1648294 | 0.26145347 | -16.966117 | 0.32817431 |
11 | 0 | 5.8918369 | 0.16754891 | 16.285382 | |
12 | 4 | 0.65556131E-12 | 0.57298371E-15 | -0.14028959E-14 | 0.12439065E-15 |
13 | 3 | -0.34087882E-03 | 0.75102955E-06 | -0.49042705E-04 | 0.12583838E-12 |
14 | 2 | 1.6337693 | 0.17263784E-01 | 1.0601096 | -0.65347397E-04 |
15 | 1 | -7.2734424 | 0.46143774 | -16.581274 | 0.31301327 |
16 | 0 | 6.4190060 | 0.30028979 | 16.300205 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.14028959E-14 | 0.57298371E-15 | 0.65556131E-12 | 0.12439065E-15 |
85 | 3 | -0.49042705E-04 | 0.75102955E-06 | -0.34087882E-03 | 0.12583838E-12 |
86 | 2 | 1.0601096 | 0.17263784E-01 | 1.6337693 | -0.65347397E-04 |
87 | 1 | -16.581274 | 0.46143774 | -7.2734424 | 0.31301327 |
88 | 0 | 16.300205 | 0.30028979 | 6.4190060 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.454_SHGC_SOUTH_0.249 | 34 | 1 | VerySmooth | 2.580 | 2.580 | 1.000 | 0.250 | ||
2 | NONRESWINDOW_U_0.454_SHGC_NORTH_0.249 | 35 | 1 | VerySmooth | 2.580 | 2.580 | 1.000 | 0.250 | ||
3 | NONRESWINDOW_U_0.454_SHGC_EAST_0.249 | 36 | 1 | VerySmooth | 2.580 | 2.580 | 1.000 | 0.250 | ||
4 | NONRESWINDOW_U_0.454_SHGC_WEST_0.249 | 37 | 1 | VerySmooth | 2.580 | 2.580 | 1.000 | 0.250 | ||
5 | SKYLIGHT_U_0.65_SHGC_0.3 | 38 | 1 | VerySmooth | 3.695 | 3.695 | 1.000 | 0.302 | ||
6 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | 39 | 1 | VerySmooth | 5.108 | 5.108 | 1.000 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.61639E-002 | 0.16038 | 0.61778 | 0.61778 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12084 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.61639E-002 | 0.16038 | 0.61778 | 0.61778 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12084 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.61639E-002 | 0.16038 | 0.61778 | 0.61778 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12084 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.61639E-002 | 0.16038 | 0.61778 | 0.61778 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12084 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.19440 | 0.51093 | 0.51093 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.96142E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 0.12500 | 0.12500 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | CurtainWall | 3.575 | 0.301 | 0.402 |
2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.867 | 0.549 | 0.401 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.331 | 7.274E-004 | 4.751E-004 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.6220E-005 |
2 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4525E-004 |
3 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.7981E-005 |
4 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5447E-004 |
5 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4652E-005 |
6 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.7024E-004 |
7 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.8648E-005 |
8 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.6551E-004 |
9 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5640E-004 |
10 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4729E-004 |
11 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3307E-004 |
12 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5838E-004 |
13 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4024E-004 |
14 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5040E-004 |
15 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3945E-004 |
16 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4949E-004 |
17 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5520E-004 |
18 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1873E-004 |
19 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9860E-004 |
20 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2322E-004 |
21 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.0368E-004 |
22 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1078E-004 |
23 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.9614E-004 |
24 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8929E-005 |
25 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7840E-004 |
26 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.5905E-005 |
27 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1141E-004 |
28 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.7862E-005 |
29 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3954E-004 |
30 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.1940E-005 |
31 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3502E-003 |
32 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.2167E-005 |
33 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1640E-004 |
34 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0947E-005 |
35 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1781E-004 |
36 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.2073E-005 |
37 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.9141E-004 |
38 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9976E-005 |
39 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0462E-004 |
40 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7378E-005 |
41 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9599E-004 |
42 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5120E-005 |
43 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0879E-004 |
44 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5955E-005 |
45 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1018E-004 |
46 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5726E-005 |
47 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8419E-004 |
48 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5748E-005 |
49 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.6465E-004 |
50 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6344E-005 |
51 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0141E-003 |
52 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7414E-005 |
53 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1483E-004 |
54 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6226E-005 |
55 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4212E-004 |
56 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5828E-005 |
57 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0731E-003 |
58 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4494E-005 |
59 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.6376E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6320E-005 |
61 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4898E-003 |
62 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1518E-005 |
63 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1230E-003 |
64 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7635E-005 |
65 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0797E-003 |
66 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.8368E-005 |
67 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0669E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.2888E-005 |
69 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.7280E-003 |
70 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.7763E-005 |
71 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5923E-003 |
72 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3189E-005 |
73 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0890E-004 |
74 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7551E-004 |
75 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.1618E-004 |
76 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9236E-004 |
77 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.3656E-004 |
78 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3946E-004 |
79 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6412E-003 |
80 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.4188E-005 |
81 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9561E-004 |
82 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1102E-004 |
83 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6476E-004 |
84 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.0779E-004 |
85 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8565E-004 |
86 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.4490E-004 |
87 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3714E-004 |
88 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8629E-004 |
89 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3343E-005 |
90 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.9182E-003 |
91 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.3632E-005 |
92 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.5098E-003 |
93 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.1466E-005 |
94 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0639E-003 |
95 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1086E-004 |
96 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.9267E-004 |
97 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5174E-005 |
98 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4845E-003 |
99 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1991E-005 |
100 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5970E-003 |
101 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0436E-005 |
102 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.0696E-003 |
103 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.9227E-005 |
104 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.1977E-003 |
105 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.3589E-005 |
106 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.1590E-004 |
107 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0736E-005 |
108 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6126E-004 |
109 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9096E-005 |
110 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0005E-003 |
111 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7155E-005 |
112 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2526E-003 |
113 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2676E-005 |
114 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7216E-005 |
115 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8717E-005 |
116 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9784E-005 |
117 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6059E-005 |
118 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6106E-005 |
119 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4598E-005 |
120 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5286E-005 |
121 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5080E-005 |
122 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8003E-005 |
123 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8065E-005 |
124 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3075E-005 |
125 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3931E-005 |
126 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1788E-005 |
127 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1685E-005 |
128 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2542E-005 |
129 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2026E-005 |
130 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0199E-005 |
131 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8583E-005 |
132 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9501E-005 |
133 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8047E-005 |
134 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9805E-005 |
135 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4582E-005 |
136 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1042E-005 |
137 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3183E-004 |
138 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2926E-004 |
139 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4101E-004 |
140 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4190E-004 |
141 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1462E-004 |
142 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0024E-004 |
143 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2514E-005 |
144 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3080E-005 |
145 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1503E-005 |
146 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7938E-004 |
147 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1089E-005 |
148 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9957E-004 |
149 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1096E-005 |
150 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3773E-004 |
151 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4916E-005 |
152 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6240E-005 |
153 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7576E-005 |
154 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5836E-005 |
155 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3175E-005 |
156 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5950E-005 |
157 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.3350E-005 |
158 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4807E-005 |
159 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4899E-005 |
160 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1079E-005 |
161 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8018E-004 |
162 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7922E-005 |
163 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0228E-004 |
164 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9651E-005 |
165 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3191E-004 |
166 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2146E-005 |
167 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2500E-005 |
168 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7738E-005 |
169 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0343E-005 |
170 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8221E-004 |
171 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7707E-005 |
172 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7449E-004 |
173 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.8417E-005 |
174 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3904E-004 |
175 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0532E-005 |
176 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7293E-004 |
177 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1730E-004 |
178 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6864E-004 |
179 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4428E-004 |
180 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9840E-004 |
181 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0325E-004 |
182 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2391E-004 |
183 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5069E-004 |
184 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0290E-004 |
185 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5946E-004 |
186 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5127E-005 |
187 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5302E-004 |
188 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.6246E-005 |
189 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.9645E-004 |
190 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2000E-005 |
191 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5061E-004 |
192 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8433E-005 |
193 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3984E-004 |
194 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8582E-005 |
195 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4797E-004 |
196 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8267E-005 |
197 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2788E-004 |
198 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8090E-005 |
199 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0473E-005 |
200 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3210E-005 |
201 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5305E-003 |
202 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.9485E-005 |
203 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7956E-003 |
204 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.7857E-005 |
205 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2461E-003 |
206 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.5095E-005 |
207 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2387E-004 |
208 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6113E-005 |
209 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.4784E-004 |
210 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6433E-004 |
211 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.9947E-004 |
212 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0186E-004 |
213 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5562E-004 |
214 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8016E-004 |
215 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2445E-004 |
216 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5215E-004 |
217 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9480E-004 |
218 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0320E-005 |
219 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9864E-004 |
220 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9402E-005 |
221 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1179E-004 |
222 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0757E-005 |
223 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2708E-004 |
224 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5686E-005 |
225 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2749E-004 |
226 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0564E-003 |
227 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1896E-004 |
228 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4329E-003 |
229 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5545E-004 |
230 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6395E-003 |
231 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2726E-004 |
232 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9459E-004 |
233 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0015E-004 |
234 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0194E-005 |
235 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9023E-004 |
236 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8752E-005 |
237 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5404E-004 |
238 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1251E-005 |
239 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9961E-004 |
240 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7482E-005 |
241 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4990E-003 |
242 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0250E-005 |
243 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5747E-003 |
244 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.4791E-005 |
245 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8428E-003 |
246 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0372E-004 |
247 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6165E-003 |
248 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3274E-005 |
249 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0183E-003 |
250 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8474E-004 |
251 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.9030E-004 |
252 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7759E-004 |
253 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3798E-003 |
254 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.4227E-004 |
255 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6195E-003 |
256 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2024E-004 |
257 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4733E-004 |
258 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2495E-003 |
259 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3089E-004 |
260 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3895E-003 |
261 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8676E-004 |
262 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7135E-003 |
263 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0001E-004 |
264 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6530E-003 |
265 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4834E-004 |
266 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8220E-005 |
267 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3216E-004 |
268 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6605E-005 |
269 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8858E-004 |
270 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9056E-005 |
271 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9852E-004 |
272 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7461E-005 |
273 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2760E-004 |
274 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0953E-004 |
275 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0941E-004 |
276 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.9845E-004 |
277 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4503E-004 |
278 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1568E-003 |
279 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9891E-004 |
280 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6031E-003 |
281 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7011E-004 |
282 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.6329E-005 |
283 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9350E-004 |
284 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9445E-005 |
285 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0494E-004 |
286 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.6768E-005 |
287 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5919E-003 |
288 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3045E-005 |
289 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8779E-004 |
290 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9924E-004 |
291 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0366E-004 |
292 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6493E-004 |
293 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.4625E-004 |
294 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1057E-004 |
295 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5949E-003 |
296 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1554E-004 |
297 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9343E-005 |
298 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8334E-004 |
299 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6080E-005 |
300 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3255E-004 |
301 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4317E-005 |
302 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0129E-004 |
303 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2574E-004 |
304 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7337E-004 |
305 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3300E-004 |
306 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4721E-004 |
307 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9064E-004 |
308 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2508E-004 |
309 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3626E-004 |
310 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6732E-004 |
311 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1039E-004 |
312 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4748E-004 |
313 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4533E-005 |
314 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6324E-005 |
315 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7893E-005 |
316 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4239E-005 |
317 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5295E-005 |
318 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4179E-005 |
319 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1671E-005 |
320 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7584E-005 |
321 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2794E-005 |
322 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5310E-005 |
323 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0948E-005 |
324 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3883E-005 |
325 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0192E-004 |
326 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5457E-005 |
327 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2556E-004 |
328 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5637E-005 |
329 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9430E-005 |
330 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0997E-004 |
331 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1795E-005 |
332 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1020E-005 |
333 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0090E-005 |
334 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.3922E-005 |
335 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9741E-005 |
336 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6869E-004 |
337 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0063E-004 |
338 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.6793E-005 |
339 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3462E-005 |
340 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6108E-005 |
341 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3162E-005 |
342 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1381E-005 |
343 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4732E-004 |
344 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0119E-004 |
345 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8972E-005 |
346 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2462E-005 |
347 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2304E-005 |
348 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1397E-005 |
349 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5988E-005 |
350 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2131E-005 |
351 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9684E-005 |
352 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3161E-005 |
353 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3751E-004 |
354 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8453E-005 |
355 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9731E-004 |
356 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2895E-005 |
357 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6608E-004 |
358 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0989E-005 |
359 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0983E-004 |
360 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5702E-005 |
361 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.9761E-005 |
362 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4747E-005 |
363 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3581E-005 |
364 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1150E-005 |
365 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8907E-005 |
366 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3149E-005 |
367 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4724E-004 |
368 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8139E-005 |
369 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.9209E-003 |
370 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.6519E-004 |
371 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.4892E-003 |
372 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1921E-004 |
373 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.3591E-003 |
374 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.0748E-004 |
375 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.7866E-003 |
376 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1636E-004 |
377 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.6409E-004 |
378 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.4328E-003 |
379 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.2321E-004 |
380 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.7942E-003 |
381 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.1311E-004 |
382 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.5113E-003 |
383 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.1270E-004 |
384 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.3974E-003 |
385 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.7815E-003 |
386 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.0997E-004 |
387 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.1219E-003 |
388 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.6781E-004 |
389 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.5111E-003 |
390 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.2925E-004 |
391 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.2429E-003 |
392 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.9254E-004 |
393 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.9076E-003 |
394 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.1054E-004 |
395 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.1678E-003 |
396 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.6810E-004 |
397 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.3018E-003 |
398 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.2891E-004 |
399 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.2428E-003 |
400 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.9254E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10683.50147 | 12820.20177 | 0.87976 | 1.05571 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 33.00467 | 1.65347E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 6832.80419 | 8199.36503 | 0.19173 | 0.23008 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 4.60000 | 5.25715E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 32154.66388 | 38585.59665 | 2.06424 | 2.47709 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 33.82100 | 1.65362E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 14173.96847 | 17008.76216 | 0.33543 | 0.42471 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 4.60000 | 5.25715E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 33.90000 | 1.65364E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 33831.65340 | 40597.98409 | 0.82733 | 0.99279 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4.60000 | 5.25715E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 16316.28 | 1.05571 | 1.05571 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 7311.18 | 0.23008 | 0.23008 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 47678.83 | 2.47709 | 2.47709 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 18177.24 | 0.42471 | 0.42471 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05571 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.47709 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.99279 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 0.99279 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 40597.98297 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 40597.98409 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05571 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05571 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05571 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05571 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05571 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.05571 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.47709 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.47709 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.47709 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.47709 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.47709 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.47709 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.05571 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.47709 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05571 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05571 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1168.83962 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05571 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05571 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05571 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69677 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05571 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52786 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70381 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21775.91000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10887.95500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76405 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76405 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21775.91000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26263.03326 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 26263.03326 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.47709 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.47709 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2650.60228 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.47709 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.47709 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.47709 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.63488 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.47709 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.23854 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.65139 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 61512.02000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 30756.01000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 61512.02000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 78825.08409 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 78825.08409 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 20956.0 | 12.63 | 12.34 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 59586.6 | 12.83 | 12.54 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 4.4269864486E-002 | 3.4880719359E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.1095054904 | 0.1879414086 | Pass | Pass | 0.5776639846 | 4.3623717600 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 6.0205876046E-002 | 5.1323103421E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 10649.55 | 438.34 | 0.00 | -28.3 | 353.19 | 11412.81 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 66.00 | 12 | |||
Feb | 66.00 | 22 | |||
Mar | 126.00 | 32 | |||
Apr | 206.00 | 19 | |||
May | 144.00 | 46 | |||
Jun | 99.00 | 30 | |||
Jul | 192.00 | 52 | |||
Aug | 240.00 | 34 | |||
Sep | 310.00 | 44 | |||
Oct | 34.00 | 10 | |||
Nov | 63.00 | 12 | |||
Dec | 35.00 | 24 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.233 | 0.240 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.545 | 0.589 | 3204.84 | 3157.28 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.892 | 1.134 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.892 | 1.134 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.454_SHGC_WEST_0.249 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.580 | 0.250 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.454_SHGC_WEST_0.249 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.580 | 0.250 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.454_SHGC_NORTH_0.249 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.580 | 0.250 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.454_SHGC_NORTH_0.249 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.580 | 0.250 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 86.04 | 4.247 | 0.429 | 0.370 | |||||||||||||||||
North Total or Average | 6.51 | 2.580 | 0.250 | 0.250 | |||||||||||||||||
Non-North Total or Average | 79.53 | 4.384 | 0.444 | 0.380 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 6.1633 | 236.88 | 1459.96 | LightsWired | LTG_SCH_OFFICE | 44.65 | 168.00 | 28.88 | 0.0000 | Y | 7.92 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 6.6844 | 1393.41 | 9314.08 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 18.64 | 0.0000 | Y | 32.59 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.1969 | 3204.84 | 10245.50 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 17.26 | 0.0000 | Y | 33.19 |
Interior Lighting Total | 4.3473 | 4835.13 | 21019.54 | 73.69 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 9314.08 | 2328.52 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 9314.08 | 2328.52 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10245.50 | 2561.37 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10245.50 | 2561.37 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.29 | 1459.96 | 423.39 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.10 | 1459.96 | 146.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 119.03 | AstronomicalClock | - | 41.73 | 41.73 | 0.93 | |
EXTERIOR_LIGHTS_B | 2955.82 | AstronomicalClock | - | 83.73 | 62.73 | 34.80 | |
EXTERIOR_LIGHTS_C | 694.12 | AstronomicalClock | - | 83.73 | 48.93 | 6.38 | |
Exterior Lighting Total | 3768.97 | 42.11 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21775.91 | 16637.88 | 5138.03 | 0.76 | 4.08 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 61512.02 | 43124.85 | 18387.17 | 0.70 | 4.01 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 20956.0 | 12.63 | 12.34 | ||||
PSZ-FINE STORAGE COOLING COIL | 59586.6 | 12.83 | 12.54 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 40597.98 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 26263.03 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 78825.08 | 0.81 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.99 | 92.24 | 92.91 | 1.00 | 4.16 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.06 | 1168.84 | 1107.16 | 1.00 | 1.39 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.48 | 2650.60 | 1070.05 | 1.00 | 1.29 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10683.50 | 12820.20 | 54.12 | 0.880 | 1.056 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 23.90 | 23.90 | 0.00854 | 33.00 | 0.01653 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 32154.66 | 38585.60 | 27.69 | 2.064 | 2.477 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 26.70 | 26.70 | 0.00911 | 33.82 | 0.01654 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 0.00 | 34.34 | 0.01661 | 33.90 | 0.01654 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 6832.80 | 8199.37 | 34.61 | 0.192 | 0.230 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00793 | 4.60 | 0.00526 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 14173.97 | 17008.76 | 12.21 | 0.335 | 0.425 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00700 | 4.60 | 0.00526 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 33831.65 | 40597.98 | 12.67 | 0.827 | 0.993 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00638 | 4.60 | 0.00526 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.06 | 1.06 | 0.23 | 0.23 | 1.0557 | 1.0557 | 1.0557 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.48 | 2.48 | 0.42 | 0.42 | 2.4771 | 2.4771 | 2.4771 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 40597.983 | 40597.983 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 40597.98 | 40597.98 | 0.992790 | 10.00 | 8.61 | 0.00637564 | 43.33 | 22.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 10.00 | 0.00637564 | 83.6460 | 40597.98 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 21775.910 | 16637.884 | 1.055710 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 10887.95 | 8930.07 | 0.703807 | 25.69 | 17.65 | 0.00931635 | 12.00 | 11.25 | 0.00800000 | 33.11 | 0.01653489 | 24.92 | 14.5331 | 23.90 | 0.00854142 | 46.2205 | 10677.09 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 26263.033 | 26263.033 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 26263.03 | 26263.03 | 1.055711 | 19.42 | 13.93 | 0.00766853 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 9.6887 | 21.10 | 0.00792722 | 50.8978 | 6832.80 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 61512.020 | 43124.847 | 2.477090 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 30756.01 | 23123.54 | 1.651393 | 28.80 | 19.52 | 0.01038698 | 12.00 | 11.25 | 0.00800000 | 33.90 | 0.01653638 | 25.13 | 25.7184 | 26.70 | 0.00911328 | 41.7153 | 32130.32 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 78825.084 | 78825.084 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 78825.08 | 78825.08 | 2.477089 | 13.68 | 10.61 | 0.00669925 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 17.1456 | 15.56 | 0.00699768 | 63.7085 | 13923.22 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 40597.983 | 40597.983 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.992790 | 1.19449244 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 40597.98 | 40597.98 | 1.0000 | 1.19449244 | 0.992790 | 10.00 | 8.61 | 0.00637564 | 26111.4 | 43.33 | 22.14 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40597.98 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 10.00 | 0.00637564 | 10.00 | 0.00637564 | 83.6460 | 40597.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21775.910 | 16637.884 | 1.055710 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.1586 | 1004.8586 | 1.2032 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.055711 | 1.27019649 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | Sensible | 10887.95 | 8930.07 | 1.0000 | 0.84679688 | 0.703807 | 25.69 | 17.65 | 0.00931635 | 49560.2 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10887.95 | 33.11 | 0.01653489 | 24.92 | 0.10228463 | 14.5331 | 23.90 | 0.00854142 | 23.90 | 0.00854142 | 46.2205 | 10677.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26263.033 | 26263.033 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.055711 | 1.27019649 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 26263.03 | 26263.03 | 1.0000 | 1.27019649 | 1.055711 | 19.42 | 13.93 | 0.00766853 | 38973.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26263.03 | 4.60 | 0.00525715 | 4.60 | 0.10228463 | 9.6887 | 21.01 | 0.00792722 | 21.10 | 0.00792722 | 50.8978 | 6832.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 61512.020 | 43124.847 | 2.477090 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1489 | 1004.8586 | 1.2032 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.477089 | 2.98035143 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 30756.01 | 23123.54 | 1.0000 | 1.98690179 | 1.651393 | 28.80 | 19.52 | 0.01038698 | 55473.5 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30756.01 | 33.90 | 0.01653638 | 25.13 | 0.42471127 | 25.7184 | 26.70 | 0.00911328 | 26.70 | 0.00911328 | 41.7153 | 32130.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 78825.084 | 78825.084 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.477089 | 2.98035143 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 78825.08 | 78825.08 | 1.0000 | 2.98035143 | 2.477089 | 13.68 | 10.61 | 0.00669925 | 30670.6 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 78825.08 | 4.60 | 0.00525715 | 4.60 | 0.42471127 | 17.1456 | 15.56 | 0.00699768 | 15.56 | 0.00699768 | 63.7085 | 13923.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialEnthalpy | 0.10 | 1.06 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialEnthalpy | 0.42 | 2.48 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2688.17 | 1567.50 | 811.67 |
ZONE2 FINE STORAGE | 3061.50 | 3287.67 | 2782.33 |
ZONE3 BULK STORAGE | 3096.00 | 3361.83 | 2897.33 |
Facility | 3161.67 | 3480.00 | 2959.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 4.83 | 48.17 | 4.83 | 46.83 |
ZONE2 FINE STORAGE | 0.00 | 144.17 | 0.00 | 0.33 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 4.83 | 192.33 | 4.83 | 47.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.479 | 0.395 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.506 | 0.186 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.101 | 0.000 | 1.168 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.56 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1722194.15 | 0.00 | 1722194.15 | 1966467.98 | 3688662.13 | 3225648.14 | 5712.75 | 2524.67 | 522.59 | 0.33 |
ZONE2 FINE STORAGE | 5280282.30 | 0.00 | 5280282.30 | 4988068.29 | 10268350.59 | 13393694.68 | 5707.13 | 2789.17 | 263.70 | 2.29 |
ZONE3 BULK STORAGE | 0.00 | 0.22E+09 | 0.22E+09 | 24851933.40 | 0.25E+09 | 30805497.77 | 7021.13 | 21.49 | 1717.38 | 4952.74 |
Total Facility | 7002476.45 | 0.22E+09 | 0.23E+09 | 31806469.67 | 0.26E+09 | 47424840.58 | 7659.59 | 3009.46 | 2454.51 | 4952.74 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1315 | 0.0000 | 0.1315 | 0.1087 | 0.2402 | 0.1023 | 589.08 | 2524.67 | 522.26 |
ZONE2 FINE STORAGE | 0.4027 | 0.0000 | 0.4027 | 0.1486 | 0.5513 | 0.4247 | 585.42 | 2789.17 | 261.42 |
ZONE3 BULK STORAGE | 0.0000 | 10.8054 | 10.8054 | 0.9539 | 11.7592 | 0.9768 | 2526.82 | 6.61 | 1102.57 |
Total Facility | 0.5342 | 10.8054 | 11.3396 | 1.2112 | 12.5507 | 1.5038 | 2535.59 | 2994.58 | 1837.41 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2493064.15 | 0.00 | 2493064.15 | 3225648.14 | 5711.91 | 0.00 | 3048.09 | 0.33 |
PSZ-FINE STORAGE | 7643823.34 | 0.00 | 7643823.34 | 13393694.68 | 5703.46 | 0.67 | 3055.87 | 2.29 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1904 | 0.0000 | 0.1904 | 0.1023 | 588.24 | 0.00 | 3047.76 |
PSZ-FINE STORAGE | 0.5829 | 0.0000 | 0.5829 | 0.4247 | 581.75 | 0.67 | 3053.58 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2815.72 | 235.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2954.20 | 107.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2114 | 0.4135 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6791 | 1.0815 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 451 |
Defaulted Fields | 395 |
Fields with Defaults | 1183 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 374.40 | 1525.96 | 01-JAN-09:50 | 34579.82 | 03-AUG-15:30 |
Electricity:Building | 223.89 | 1044.96 | 01-JAN-09:50 | 18901.46 | 06-NOV-15:40 |
Electricity:Zone:ZONE1 OFFICE | 37.08 | 520.87 | 01-JAN-00:10 | 2587.02 | 25-OCT-07:10 |
Electricity:SpaceType:GENERAL | 210.20 | 1044.96 | 01-JAN-09:50 | 17243.46 | 27-NOV-15:30 |
InteriorLights:Electricity | 73.70 | 558.57 | 30-MAY-17:30 | 7208.28 | 27-NOV-15:30 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 7.92 | 51.00 | 01-JAN-00:10 | 751.96 | 25-OCT-07:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 73.70 | 558.57 | 30-MAY-17:30 | 7208.28 | 27-NOV-15:30 |
LightsWired:InteriorLights:Electricity | 73.70 | 558.57 | 30-MAY-17:30 | 7208.28 | 27-NOV-15:30 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 7.92 | 51.00 | 01-JAN-00:10 | 751.96 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 73.70 | 558.57 | 30-MAY-17:30 | 7208.28 | 27-NOV-15:30 |
Electricity:Zone:ZONE2 FINE STORAGE | 32.59 | 280.09 | 26-JUL-17:10 | 3192.29 | 27-NOV-15:30 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 32.59 | 280.09 | 26-JUL-17:10 | 3192.29 | 27-NOV-15:30 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 32.59 | 280.09 | 26-JUL-17:10 | 3192.29 | 27-NOV-15:30 |
Electricity:Zone:ZONE3 BULK STORAGE | 154.23 | 224.12 | 01-JAN-09:50 | 13524.94 | 06-NOV-15:40 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 33.19 | 224.12 | 01-JAN-09:50 | 3317.79 | 27-NOV-15:30 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 33.19 | 224.12 | 01-JAN-09:50 | 3317.79 | 27-NOV-15:30 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 34.36 | 0.00 | 01-JAN-00:10 | 4780.72 | 03-AUG-16:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 13.69 | 0.00 | 01-JAN-00:10 | 2305.29 | 07-MAY-14:30 |
Ventilation (simple):Fans:Electricity | 13.69 | 0.00 | 01-JAN-00:10 | 2305.29 | 07-MAY-14:30 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 13.69 | 0.00 | 01-JAN-00:10 | 2305.29 | 07-MAY-14:30 |
ElectricityProduced:Facility | 131.51 | -0.00 | 12-DEC-07:40 | 20920.24 | 10-APR-12:30 |
ElectricityProduced:Plant | 131.51 | -0.00 | 12-DEC-07:40 | 20920.24 | 10-APR-12:30 |
Photovoltaic:ElectricityProduced | 137.28 | 0.00 | 01-JAN-00:10 | 21783.77 | 10-APR-12:30 |
PowerConversion:ElectricityProduced | -5.77 | -863.53 | 10-APR-12:30 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 23.33 | 481.00 | 26-JAN-06:10 | 1773.06 | 24-JAN-12:40 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 257.98 | 0.00 | 01-JAN-08:20 | 26576.29 | 20-OCT-15:40 |
ElectricityPurchased:Plant | 257.98 | 0.00 | 01-JAN-08:20 | 26576.29 | 20-OCT-15:40 |
Cogeneration:ElectricityPurchased | 257.98 | 0.00 | 01-JAN-08:20 | 26576.29 | 20-OCT-15:40 |
General:Cogeneration:ElectricityPurchased | 257.98 | 0.00 | 01-JAN-08:20 | 26576.29 | 20-OCT-15:40 |
ElectricitySurplusSold:Facility | 15.09 | 0.00 | 01-JAN-00:10 | 19312.71 | 16-APR-12:30 |
ElectricitySurplusSold:Plant | 15.09 | 0.00 | 01-JAN-00:10 | 19312.71 | 16-APR-12:30 |
Cogeneration:ElectricitySurplusSold | 15.09 | 0.00 | 01-JAN-00:10 | 19312.71 | 16-APR-12:30 |
General:Cogeneration:ElectricitySurplusSold | 15.09 | 0.00 | 01-JAN-00:10 | 19312.71 | 16-APR-12:30 |
ElectricityNet:Facility | 242.89 | -19312.71 | 16-APR-12:30 | 26576.29 | 20-OCT-15:40 |
ElectricityNet:Plant | 242.89 | -19312.71 | 16-APR-12:30 | 26576.29 | 20-OCT-15:40 |
Cogeneration:ElectricityNet | 242.89 | -19312.71 | 16-APR-12:30 | 26576.29 | 20-OCT-15:40 |
General:Cogeneration:ElectricityNet | 242.89 | -19312.71 | 16-APR-12:30 | 26576.29 | 20-OCT-15:40 |
Electricity:HVAC | 85.06 | 0.00 | 01-JAN-00:10 | 17201.13 | 03-AUG-16:10 |
General:Fans:Electricity | 20.67 | 0.00 | 01-JAN-00:10 | 2475.42 | 03-AUG-16:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 64.39 | 0.00 | 01-JAN-00:10 | 14725.71 | 03-AUG-16:10 |
General:Cooling:Electricity | 64.39 | 0.00 | 01-JAN-00:10 | 14725.71 | 03-AUG-16:10 |
ExteriorLights:Electricity | 42.11 | 0.00 | 01-JAN-07:30 | 3768.97 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 42.11 | 0.00 | 01-JAN-07:30 | 3768.97 | 01-JAN-06:10 |
WaterSystems:Electricity | 23.33 | 481.00 | 26-JAN-06:10 | 1773.06 | 24-JAN-12:40 |
Water Heater:WaterSystems:Electricity | 23.33 | 481.00 | 26-JAN-06:10 | 1773.06 | 24-JAN-12:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 3.15 | 0.00 | 01-JAN-00:10 | 20505.42 | 10-JAN-07:10 |
NaturalGas:HVAC | 3.15 | 0.00 | 01-JAN-00:10 | 20505.42 | 10-JAN-07:10 |
Heating:NaturalGas | 3.15 | 0.00 | 01-JAN-00:10 | 20505.42 | 10-JAN-07:10 |
General:Heating:NaturalGas | 3.15 | 0.00 | 01-JAN-00:10 | 20505.42 | 10-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:40 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:40 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:40 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:40 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:40 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:40 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:40 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 467.04 | 0.00 | 01-JAN-00:10 | 96438.18 | 03-AUG-16:10 |
EnergyTransfer:Building | 177.12 | 0.00 | 01-JAN-00:10 | 36290.25 | 03-AUG-16:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 60.07 | 0.00 | 01-JAN-00:10 | 12798.14 | 06-FEB-06:10 |
Heating:EnergyTransfer | 3.15 | 0.00 | 01-JAN-00:10 | 15657.40 | 10-JAN-07:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 2.09 | 0.00 | 01-JAN-00:10 | 12798.14 | 06-FEB-06:10 |
General:Heating:EnergyTransfer | 3.15 | 0.00 | 01-JAN-00:10 | 15657.40 | 10-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 2.09 | 0.00 | 01-JAN-00:10 | 12798.14 | 06-FEB-06:10 |
Cooling:EnergyTransfer | 173.97 | 0.00 | 01-JAN-00:10 | 36290.25 | 03-AUG-16:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 57.98 | 0.00 | 01-JAN-00:10 | 11863.05 | 03-AUG-16:10 |
General:Cooling:EnergyTransfer | 173.97 | 0.00 | 01-JAN-00:10 | 36290.25 | 03-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 57.98 | 0.00 | 01-JAN-00:10 | 11863.05 | 03-AUG-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 117.05 | 0.00 | 01-JAN-00:10 | 26812.90 | 08-OCT-13:20 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 1.06 | 0.00 | 01-JAN-00:10 | 7230.79 | 05-FEB-07:40 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 1.06 | 0.00 | 01-JAN-00:10 | 7230.79 | 05-FEB-07:40 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 115.99 | 0.00 | 01-JAN-00:10 | 26812.90 | 08-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 115.99 | 0.00 | 01-JAN-00:10 | 26812.90 | 08-OCT-13:20 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 289.92 | 0.00 | 01-JAN-00:10 | 60147.93 | 03-AUG-16:10 |
HeatingCoils:EnergyTransfer | 2.13 | 0.00 | 01-JAN-00:10 | 14261.46 | 10-JAN-07:10 |
CoolingCoils:EnergyTransfer | 287.79 | 0.00 | 01-JAN-00:10 | 60147.93 | 03-AUG-16:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 2.089 | -57.976 | 0.000 | 0.000 | 9.295 | 7.916 | 29.165 | 10.734 | 0.000 | 4.175 | 6.949 | 0.000 | -4.275 | 0.000 | -8.071 | -0.001 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 1.065 | -115.981 | 0.000 | 0.000 | 19.440 | 32.585 | 0.000 | 33.921 | 0.000 | 3.767 | 57.946 | 0.000 | -9.826 | 0.000 | -22.915 | -0.001 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 36.757 | 33.194 | 107.344 | 692.689 | 0.000 | 4.775 | 0.015 | 0.000 | -106.611 | 0.000 | -408.870 | -359.278 |
Total Facility | 0.000 | 0.000 | 3.154 | -173.957 | 0.000 | 0.000 | 65.492 | 73.695 | 136.508 | 737.344 | 0.000 | 12.717 | 64.910 | 0.000 | -120.713 | 0.000 | -439.856 | -359.280 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 27-OCT-05:02 | 0.00 | 0.00 | 0.00 | -24186.66 | 0.00 | 0.00 | 90.78 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 24919.14 | 0.00 | -450.52 | 0.00 | -974.25 | 0.00 |
ZONE2 FINE STORAGE | 11-JUN-16:12 | 0.00 | 0.00 | 0.00 | -53596.18 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 3198.34 | 0.00 | 563.88 | 49534.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-AUG-05:01 | 0.00 | 0.00 | 0.00 | -68005.40 | 0.00 | 0.00 | 562.04 | 799.21 | 2600.55 | 0.00 | 0.00 | 0.00 | 74939.45 | 0.00 | -8520.73 | 0.00 | -2375.12 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 06-FEB-06:01 | 0.00 | 0.00 | 26587.95 | 0.00 | 0.00 | 0.00 | 141.46 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -552.45 | 0.00 | -1084.69 | -25693.78 |
ZONE2 FINE STORAGE | 05-FEB-07:35 | 0.00 | 0.00 | 14461.59 | 0.00 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1386.09 | 0.00 | -7360.52 | -6014.95 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-FEB-06:01 | 0.00 | 0.00 | 26587.95 | 0.00 | 0.00 | 0.00 | 1299.44 | 799.21 | 2600.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -15623.26 | 0.00 | -11383.57 | -4280.32 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0557 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0557 | 0.0969 | 1.0000 | Not calculated | 0.1023 | 0.0969 | ||
PSZ-FINE STORAGE | 2.4771 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.4771 | 0.1715 | 1.0000 | Not calculated | 0.4247 | 0.1715 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0557 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0557 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0969 | ||
PSZ-FINE STORAGE | 2.4771 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.4771 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1715 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0557 | 1.0557 | 1.0557 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4771 | 2.4771 | 2.4771 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0557 | 1.0557 | 1.0557 | 1.0557 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.4771 | 2.4771 | 2.4771 | 2.4771 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0557 | 1.0557 | 1.0557 | No | 0.1023 | 0.4446 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4771 | 2.4771 | 2.4771 | No | 0.4247 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0557 | 1.0557 | 1.0557 | 1.0557 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.4771 | 2.4771 | 2.4771 | 2.4771 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 4.83 |
Number of hours cooling loads not met | 47.17 |
Number of hours not met | 52.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 3.15 | 20505.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 64.39 | 14725.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 73.70 | 7208.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 42.11 | 3768.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 13.69 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 20.67 | 2475.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 23.33 | 1773.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 374.40 |
Natural Gas | 0.00 | 3.15 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 377.55 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 137.28 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 15.24 |
Space Heating | 0.00 |
Space Cooling | 13.32 |
Fans (All) | 7.11 |
Service Water Heating | 4.83 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 77.43 |
Subtotal | 77.43 |
Natural Gas [MJ/m2] | |
Space Heating | 0.65 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.65 |
Subtotal | 0.65 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 19.52 |
Space Heating | 0.83 |
Space Cooling | 17.05 |
Fans (All) | 9.10 |
Service Water Heating | 6.18 |
Receptacle Equipment | 36.16 |
Miscellaneous | 11.15 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
LTG_SCH_OFFICE | 2328. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 6179.50 | 2452.00 | 128.50 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 4254.17 | 4505.83 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3792.83 | 2059.67 | 2859.17 | 48.33 | 0.00 |
Min | 3792.83 | 2059.67 | 0.00 | 0.00 | 0.00 |
Max | 6179.50 | 4505.83 | 2859.17 | 48.33 | 0.00 |
Average | 4742.17 | 3005.83 | 995.89 | 16.11 | 0.00 |
Sum | 14226.50 | 9017.50 | 2987.67 | 48.33 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 32762.00 | 49957.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 73735.83 | 38957.83 | 76756.17 | 1743.17 | 0.00 |
Min | 32762.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 73735.83 | 49957.00 | 76756.17 | 1743.17 | 0.00 |
Average | 46508.28 | 29638.28 | 25585.39 | 581.06 | 0.00 |
Sum | 139524.83 | 88914.83 | 76756.17 | 1743.17 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 4848.50 | 3897.00 | 14.50 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 3133.33 | 5626.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3048.17 | 4224.17 | 1463.00 | 24.67 | 0.00 |
Min | 3048.17 | 3897.00 | 0.00 | 0.00 | 0.00 |
Max | 4848.50 | 5626.67 | 1463.00 | 24.67 | 0.00 |
Average | 3676.67 | 4582.61 | 492.50 | 8.22 | 0.00 |
Sum | 11030.00 | 13747.83 | 1477.50 | 24.67 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 28878.67 | 4148.33 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 25087.00 | 57632.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 59717.17 | 83614.33 | 47331.50 | 530.00 | 0.00 |
Min | 25087.00 | 4148.33 | 0.00 | 0.00 | 0.00 |
Max | 59717.17 | 83614.33 | 47331.50 | 530.00 | 0.00 |
Average | 37894.28 | 48464.89 | 15777.17 | 176.67 | 0.00 |
Sum | 113682.83 | 145394.67 | 47331.50 | 530.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.930871E+09 | 19101.96 | 02-JAN-06:02 | 16.00 | 15.39 | 0.575855E+09 | 769.02 | 02-JAN-13:20 | 26.00 | 18.72 |
February | 0.130179E+10 | 14828.80 | 28-FEB-06:03 | 18.38 | 17.90 | 0.546476E+09 | 769.03 | 28-FEB-16:00 | 23.80 | 20.44 |
March | 0.207088E+10 | 14444.07 | 30-MAR-05:03 | 20.83 | 19.77 | 0.652990E+09 | 769.03 | 28-MAR-14:50 | 20.83 | 19.77 |
April | 0.420648E+10 | 17811.60 | 25-APR-05:02 | 19.30 | 17.20 | 0.632678E+09 | 769.06 | 28-APR-14:39 | 33.10 | 23.05 |
May | 0.719748E+10 | 16596.48 | 05-MAY-05:01 | 23.30 | 20.65 | 0.660522E+09 | 769.06 | 04-MAY-15:30 | 23.30 | 20.65 |
June | 0.771928E+10 | 16961.06 | 14-JUN-05:01 | 25.00 | 22.88 | 0.660555E+09 | 769.06 | 12-JUN-14:50 | 25.00 | 22.88 |
July | 0.763482E+10 | 15693.21 | 19-JUL-05:01 | 27.12 | 24.30 | 0.635213E+09 | 769.06 | 08-JUL-15:09 | 27.12 | 24.30 |
August | 0.836726E+10 | 18694.30 | 31-AUG-05:01 | 24.13 | 22.97 | 0.686024E+09 | 769.06 | 25-AUG-15:39 | 24.13 | 22.97 |
September | 0.708634E+10 | 16767.85 | 22-SEP-05:01 | 21.70 | 19.78 | 0.635174E+09 | 769.05 | 21-SEP-15:00 | 21.70 | 19.78 |
October | 0.638238E+10 | 24189.03 | 27-OCT-05:02 | 15.00 | 7.96 | 0.634832E+09 | 769.07 | 11-OCT-14:39 | 15.00 | 7.96 |
November | 0.314910E+10 | 18149.81 | 06-NOV-06:01 | 18.80 | 17.70 | 0.603439E+09 | 769.04 | 07-NOV-13:30 | 28.30 | 24.43 |
December | 0.193101E+10 | 15160.04 | 16-DEC-06:02 | 20.83 | 19.18 | 0.594652E+09 | 769.03 | 12-DEC-16:49 | 20.83 | 19.18 |
Annual Sum or Average | 0.579777E+11 | 0.751841E+10 | ||||||||
Minimum of Months | 0.930871E+09 | 14444.07 | 15.00 | 7.96 | 0.546476E+09 | 769.02 | 15.00 | 7.96 | ||
Maximum of Months | 0.836726E+10 | 24189.03 | 27.12 | 24.30 | 0.686024E+09 | 769.07 | 33.10 | 24.43 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185361E+10 | 33041.53 | 01-JAN-13:43 | 25.83 | 18.00 | 0.120031E+10 | 2246.80 | 02-JAN-15:00 | 26.00 | 18.38 |
February | 0.138861E+10 | 6698.62 | 27-FEB-15:10 | 26.00 | 20.45 | 0.122976E+10 | 2246.82 | 28-FEB-16:49 | 23.90 | 20.41 |
March | 0.178731E+10 | 12681.50 | 26-MAR-14:05 | 28.97 | 20.05 | 0.156508E+10 | 2256.24 | 27-MAR-12:20 | 26.60 | 21.08 |
April | 0.537079E+10 | 48841.01 | 23-APR-14:03 | 27.88 | 21.09 | 0.176412E+10 | 2246.94 | 22-APR-13:39 | 27.88 | 21.09 |
May | 0.154426E+11 | 52797.13 | 29-MAY-16:23 | 31.70 | 23.61 | 0.192856E+10 | 2246.93 | 12-MAY-12:30 | 31.70 | 23.61 |
June | 0.187117E+11 | 53595.28 | 11-JUN-16:12 | 32.57 | 21.40 | 0.192883E+10 | 2247.00 | 14-JUN-14:20 | 34.43 | 24.69 |
July | 0.197923E+11 | 50939.27 | 23-JUL-14:23 | 32.50 | 25.44 | 0.185480E+10 | 2246.99 | 07-JUL-13:20 | 32.50 | 25.44 |
August | 0.196054E+11 | 51437.31 | 02-AUG-05:01 | 26.00 | 25.09 | 0.200313E+10 | 2247.00 | 01-AUG-14:00 | 26.00 | 25.09 |
September | 0.147243E+11 | 50669.65 | 10-SEP-17:03 | 32.73 | 26.54 | 0.185451E+10 | 2246.98 | 09-SEP-15:09 | 32.73 | 26.54 |
October | 0.123815E+11 | 53271.26 | 01-OCT-15:43 | 27.75 | 18.33 | 0.182129E+10 | 2246.99 | 05-OCT-15:20 | 33.33 | 23.87 |
November | 0.274978E+10 | 26762.00 | 05-NOV-14:05 | 27.20 | 20.62 | 0.158995E+10 | 2246.85 | 08-NOV-14:50 | 22.88 | 16.53 |
December | 0.218182E+10 | 9854.16 | 15-DEC-14:40 | 29.00 | 21.74 | 0.138554E+10 | 2246.82 | 02-DEC-14:00 | 29.00 | 21.74 |
Annual Sum or Average | 0.115990E+12 | 0.201259E+11 | ||||||||
Minimum of Months | 0.138861E+10 | 6698.62 | 25.83 | 18.00 | 0.120031E+10 | 2246.80 | 22.88 | 16.53 | ||
Maximum of Months | 0.197923E+11 | 53595.28 | 32.73 | 26.54 | 0.200313E+10 | 2256.24 | 34.43 | 26.54 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 | 0.262860E+10 | 5480.26 | 02-JAN-14:20 | 26.33 | 18.48 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 | 0.268086E+10 | 5558.74 | 27-FEB-15:20 | 25.90 | 20.46 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 | 0.361726E+10 | 5848.90 | 29-MAR-15:20 | 27.00 | 21.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 | 0.460008E+10 | 7885.46 | 28-APR-15:09 | 33.12 | 23.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.11 | 0.573692E+10 | 8038.74 | 18-MAY-15:20 | 33.30 | 23.34 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 | 0.590620E+10 | 8682.86 | 14-JUN-14:20 | 34.43 | 24.69 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 | 23.10 | 0.571144E+10 | 9028.93 | 22-JUL-15:00 | 36.10 | 27.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.55 | 0.605022E+10 | 8854.78 | 03-AUG-15:00 | 35.50 | 24.80 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 | 0.528353E+10 | 8551.14 | 09-SEP-15:00 | 35.60 | 26.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 | 0.509855E+10 | 8170.97 | 05-OCT-15:09 | 33.67 | 23.96 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 | 0.381081E+10 | 6519.54 | 02-NOV-13:20 | 29.80 | 24.39 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 | 0.311852E+10 | 6015.32 | 16-DEC-14:20 | 27.00 | 21.75 |
Annual Sum or Average | 0.00 | 0.542430E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 14.12 | 12.36 | 0.262860E+10 | 5480.26 | 25.90 | 18.48 | ||
Maximum of Months | 0.00 | 0.00 | 25.13 | 24.22 | 0.605022E+10 | 9028.93 | 36.10 | 27.07 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.769853E+09 | 26585.62 | 10-JAN-06:01 | 3.00 |
February | 0.457282E+09 | 26587.91 | 06-FEB-06:01 | 2.88 |
March | 0.336558E+09 | 26568.18 | 13-MAR-05:01 | 6.68 |
April | 29039030.31 | 2296.22 | 11-APR-06:30 | 10.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 36055.74 | 120.19 | 07-JUN-06:05 | 21.38 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 8806015.32 | 777.07 | 27-OCT-06:10 | 14.83 |
November | 54386040.62 | 3802.77 | 15-NOV-07:20 | 7.90 |
December | 0.433028E+09 | 26498.89 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.208899E+10 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 0.769853E+09 | 26587.91 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205607E+09 | 3744.35 | 10-JAN-07:10 | 3.17 |
February | 0.206584E+09 | 14461.58 | 05-FEB-07:35 | -3.4 |
March | 0.181529E+09 | 1394.45 | 24-MAR-17:00 | 26.60 |
April | 82955826.13 | 1067.70 | 10-APR-06:50 | 12.20 |
May | 5888112.99 | 1223.74 | 08-MAY-06:10 | 23.98 |
June | 9188329.36 | 1269.10 | 28-JUN-06:10 | 26.88 |
July | 4037523.97 | 1229.58 | 13-JUL-06:10 | 25.50 |
August | 4616863.01 | 1374.20 | 31-AUG-06:04 | 24.00 |
September | 5228645.64 | 1173.33 | 02-SEP-06:10 | 24.58 |
October | 42323122.52 | 1241.76 | 07-OCT-06:10 | 26.67 |
November | 0.143860E+09 | 2132.52 | 28-NOV-13:00 | 28.30 |
December | 0.172876E+09 | 1566.29 | 09-DEC-13:40 | 27.00 |
Annual Sum or Average | 0.106469E+10 | |||
Minimum of Months | 4037523.97 | 1067.70 | -3.4 | |
Maximum of Months | 0.206584E+09 | 14461.58 | 28.30 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.684269E+09 | 744.58 | 31-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.605881E+09 | 747.60 | 01-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.714404E+09 | 745.00 | 18-MAR-07:10 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.645695E+09 | 743.20 | 14-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.663390E+09 | 727.76 | 20-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.647522E+09 | 709.42 | 03-JUN-07:30 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.629733E+09 | 713.64 | 14-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.675848E+09 | 725.72 | 21-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.645169E+09 | 741.10 | 26-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.656616E+09 | 751.96 | 25-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.656464E+09 | 747.77 | 01-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.690753E+09 | 751.07 | 12-DEC-08:09 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.791574E+10 | 0.291647E+11 | ||||
Minimum of Months | 0.605881E+09 | 709.42 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.714404E+09 | 751.96 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.303648E+10 | 3140.71 | 04-JAN-09:09 | 0.00 | 0.00 |
February | 0.262526E+10 | 3143.02 | 14-FEB-09:09 | 0.00 | 0.00 |
March | 0.293522E+10 | 3188.71 | 13-MAR-08:09 | 0.00 | 0.00 |
April | 0.256092E+10 | 3118.86 | 03-APR-08:09 | 0.00 | 0.00 |
May | 0.258738E+10 | 3042.76 | 03-MAY-08:09 | 0.00 | 0.00 |
June | 0.254485E+10 | 2971.46 | 08-JUN-08:09 | 0.00 | 0.00 |
July | 0.246598E+10 | 2943.05 | 25-JUL-08:30 | 0.00 | 0.00 |
August | 0.261712E+10 | 3043.19 | 30-AUG-08:09 | 0.00 | 0.00 |
September | 0.252104E+10 | 3052.14 | 22-SEP-08:09 | 0.00 | 0.00 |
October | 0.271510E+10 | 3077.09 | 18-OCT-08:09 | 0.00 | 0.00 |
November | 0.288255E+10 | 3192.29 | 27-NOV-15:30 | 0.00 | 0.00 |
December | 0.309346E+10 | 3190.16 | 28-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.325854E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.246598E+10 | 2943.05 | 0.00 | 0.00 | |
Maximum of Months | 0.309346E+10 | 3192.29 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.309187E+10 | 3139.67 | 06-JAN-15:00 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.263749E+10 | 3091.74 | 01-FEB-08:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.292319E+10 | 3105.40 | 13-MAR-07:10 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.264142E+10 | 3027.53 | 14-APR-07:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.264281E+10 | 2791.50 | 20-MAY-07:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.257883E+10 | 2638.47 | 03-JUN-07:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.253893E+10 | 2628.07 | 14-JUL-07:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.272628E+10 | 2828.32 | 08-AUG-07:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.263697E+10 | 2996.48 | 26-SEP-07:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.277407E+10 | 3171.36 | 25-OCT-07:10 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.288644E+10 | 3317.79 | 27-NOV-15:30 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.311601E+10 | 3245.11 | 28-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.331943E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.253893E+10 | 2628.07 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.311601E+10 | 3317.79 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.684269E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15629672.81 | 0.171183E+10 |
February | 0.127628E+10 | 0.605881E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25807600.23 | 0.114134E+10 |
March | 0.149825E+10 | 0.714404E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66188744.68 | 0.132821E+10 |
April | 0.138726E+10 | 0.645695E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195158E+09 | 0.560917E+09 |
May | 0.144276E+10 | 0.663390E+09 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648781E+09 | 97317758.86 |
June | 0.144276E+10 | 0.647522E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.754471E+09 | 79348062.36 |
July | 0.138726E+10 | 0.629733E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687204E+09 | 54249652.62 |
August | 0.149825E+10 | 0.675848E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772685E+09 | 0.116373E+09 |
September | 0.138726E+10 | 0.645169E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419531E+09 | 0.176124E+09 |
October | 0.138726E+10 | 0.656616E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436621E+09 | 0.485035E+09 |
November | 0.133177E+10 | 0.656464E+09 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102528E+09 | 0.864192E+09 |
December | 0.138726E+10 | 0.690753E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50132679.12 | 0.145574E+10 |
Annual Sum or Average | 0.168137E+11 | 0.791574E+10 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417474E+10 | 0.807068E+10 |
Minimum of Months | 0.127628E+10 | 0.605881E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15629672.81 | 54249652.62 |
Maximum of Months | 0.149825E+10 | 0.714404E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772685E+09 | 0.171183E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.303648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15461717.47 | 0.380224E+10 |
February | 0.300332E+10 | 0.262526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15955040.88 | 0.279446E+10 |
March | 0.352563E+10 | 0.293522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19826038.38 | 0.352302E+10 |
April | 0.326447E+10 | 0.256092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100116E+09 | 0.194571E+10 |
May | 0.339505E+10 | 0.258738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521314E+09 | 0.610722E+09 |
June | 0.339505E+10 | 0.254485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.602542E+09 | 0.401839E+09 |
July | 0.326447E+10 | 0.246598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727998E+09 | 0.242958E+09 |
August | 0.352563E+10 | 0.261712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.774906E+09 | 0.592821E+09 |
September | 0.326447E+10 | 0.252104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508794E+09 | 0.911514E+09 |
October | 0.326447E+10 | 0.271510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437237E+09 | 0.204033E+10 |
November | 0.313390E+10 | 0.288255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24626271.05 | 0.249727E+10 |
December | 0.326447E+10 | 0.309346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18230271.35 | 0.355256E+10 |
Annual Sum or Average | 0.395654E+11 | 0.325854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376701E+10 | 0.229154E+11 |
Minimum of Months | 0.300332E+10 | 0.246598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15461717.47 | 0.242958E+09 |
Maximum of Months | 0.352563E+10 | 0.309346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.774906E+09 | 0.380224E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.309187E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284083E+09 | 0.167276E+11 |
February | 0.690763E+10 | 0.263749E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208890E+09 | 0.120117E+11 |
March | 0.810895E+10 | 0.292319E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106942E+09 | 0.164771E+11 |
April | 0.750829E+10 | 0.264142E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1681318.44 | 0.109987E+11 |
May | 0.780862E+10 | 0.264281E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4970087.85 | 0.681150E+10 |
June | 0.780862E+10 | 0.257883E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2006932.12 | 0.451054E+10 |
July | 0.750829E+10 | 0.253893E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6079780.00 | 0.406013E+10 |
August | 0.810895E+10 | 0.272628E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26688576.76 | 0.651718E+10 |
September | 0.750829E+10 | 0.263697E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37621000.68 | 0.833839E+10 |
October | 0.750829E+10 | 0.277407E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1474943.53 | 0.141705E+11 |
November | 0.720796E+10 | 0.288644E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66788038.21 | 0.120851E+11 |
December | 0.750829E+10 | 0.311601E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167983E+09 | 0.158957E+11 |
Annual Sum or Average | 0.910005E+11 | 0.331943E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.915208E+09 | 0.128604E+12 |
Minimum of Months | 0.690763E+10 | 0.253893E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1474943.53 | 0.406013E+10 |
Maximum of Months | 0.810895E+10 | 0.311601E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284083E+09 | 0.167276E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 744.58 | 31-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 741.07 | 02-JAN-13:00 | 8489.20 | 05-JAN-08:00 |
February | 1680.92 | 01-FEB-08:09 | 747.60 | 01-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1664.87 | 02-FEB-13:00 | 7960.52 | 17-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 745.00 | 18-MAR-07:10 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1591.41 | 30-MAR-12:00 | 8839.19 | 09-MAR-07:10 |
April | 1680.92 | 01-APR-07:10 | 743.20 | 14-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3147.24 | 28-APR-16:10 | 4945.28 | 11-APR-06:03 |
May | 1680.92 | 01-MAY-07:10 | 727.76 | 20-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3475.70 | 10-MAY-16:10 | 679.39 | 02-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 709.42 | 03-JUN-07:30 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3558.84 | 28-JUN-16:10 | 1019.64 | 07-JUN-06:05 |
July | 1680.92 | 01-JUL-07:10 | 713.64 | 14-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4172.41 | 21-JUL-16:10 | 373.89 | 13-JUL-11:05 |
August | 1680.92 | 01-AUG-07:10 | 725.72 | 21-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4638.10 | 03-AUG-16:10 | 830.15 | 16-AUG-17:00 |
September | 1680.92 | 01-SEP-07:10 | 741.10 | 26-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3143.20 | 06-SEP-16:10 | 1622.43 | 07-SEP-17:00 |
October | 1680.92 | 02-OCT-07:10 | 751.96 | 25-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3333.63 | 05-OCT-17:00 | 4075.79 | 27-OCT-07:00 |
November | 1680.92 | 01-NOV-07:10 | 747.77 | 01-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1942.61 | 02-NOV-12:00 | 5523.24 | 09-NOV-07:05 |
December | 1680.92 | 01-DEC-08:09 | 751.07 | 12-DEC-08:09 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1496.25 | 13-DEC-13:00 | 8911.99 | 20-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 709.42 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 741.07 | 373.89 | |||||
Maximum of Months | 1680.92 | 751.96 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 4638.10 | 8911.99 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3140.71 | 04-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 671.31 | 16-JAN-15:00 | 7530.70 | 03-JAN-09:00 |
February | 3955.50 | 01-FEB-08:09 | 3143.02 | 14-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 963.15 | 20-FEB-15:00 | 8594.99 | 16-FEB-18:00 |
March | 3955.50 | 01-MAR-08:09 | 3188.71 | 13-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 788.44 | 27-MAR-15:10 | 7945.15 | 09-MAR-09:00 |
April | 3955.50 | 01-APR-07:10 | 3118.86 | 03-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2186.25 | 28-APR-15:10 | 5455.65 | 15-APR-17:00 |
May | 3955.50 | 01-MAY-07:10 | 3042.76 | 03-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2351.46 | 18-MAY-16:35 | 1809.41 | 05-MAY-06:10 |
June | 3955.50 | 01-JUN-07:10 | 2971.46 | 08-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3239.49 | 08-JUN-15:10 | 2302.98 | 06-JUN-21:00 |
July | 3955.50 | 01-JUL-07:10 | 2943.05 | 25-JUL-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2969.51 | 06-JUL-15:10 | 1126.52 | 12-JUL-15:10 |
August | 3955.50 | 01-AUG-07:10 | 3043.19 | 30-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3742.20 | 03-AUG-16:40 | 2433.01 | 25-AUG-24:00 |
September | 3955.50 | 01-SEP-07:10 | 3052.14 | 22-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3588.90 | 09-SEP-17:00 | 2241.39 | 19-SEP-18:40 |
October | 3955.50 | 02-OCT-07:10 | 3077.09 | 18-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3332.19 | 09-OCT-14:00 | 5538.86 | 27-OCT-07:00 |
November | 3955.50 | 01-NOV-07:10 | 3192.29 | 27-NOV-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 779.37 | 02-NOV-15:10 | 5885.03 | 09-NOV-07:10 |
December | 3955.50 | 01-DEC-08:09 | 3190.16 | 28-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.90 | 13-DEC-16:10 | 6682.91 | 04-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 2943.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.90 | 1126.52 | ||||
Maximum of Months | 3955.50 | 3192.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3742.20 | 8594.99 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 3139.67 | 06-JAN-15:00 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3941.28 | 31-JAN-13:10 | 33375.69 | 03-JAN-09:00 |
February | 9097.65 | 01-FEB-08:09 | 3091.74 | 01-FEB-08:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6723.57 | 02-FEB-13:10 | 37009.77 | 04-FEB-11:00 |
March | 9097.65 | 01-MAR-08:09 | 3105.40 | 13-MAR-07:10 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3247.99 | 27-MAR-15:00 | 35722.18 | 09-MAR-09:00 |
April | 9097.65 | 01-APR-07:10 | 3027.53 | 14-APR-07:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 885.52 | 15-APR-12:00 | 24386.23 | 01-APR-16:00 |
May | 9097.65 | 01-MAY-07:10 | 2791.50 | 20-MAY-07:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1279.77 | 27-MAY-13:53 | 15478.03 | 26-MAY-15:00 |
June | 9097.65 | 01-JUN-07:10 | 2638.47 | 03-JUN-07:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 315.47 | 25-JUN-12:53 | 14119.71 | 01-JUN-13:00 |
July | 9097.65 | 01-JUL-07:10 | 2628.07 | 14-JUL-07:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 705.81 | 02-JUL-10:55 | 18017.51 | 31-JUL-11:00 |
August | 9097.65 | 01-AUG-07:10 | 2828.32 | 08-AUG-07:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 998.02 | 30-AUG-15:55 | 13080.44 | 25-AUG-24:00 |
September | 9097.65 | 01-SEP-07:10 | 2996.48 | 26-SEP-07:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1379.83 | 09-SEP-17:00 | 15000.76 | 12-SEP-20:00 |
October | 9097.65 | 02-OCT-07:10 | 3171.36 | 25-OCT-07:10 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 452.34 | 08-OCT-13:53 | 27829.01 | 27-OCT-11:00 |
November | 9097.65 | 01-NOV-07:10 | 3317.79 | 27-NOV-15:30 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4433.73 | 28-NOV-13:10 | 23884.64 | 09-NOV-08:10 |
December | 9097.65 | 01-DEC-08:09 | 3245.11 | 28-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2877.42 | 13-DEC-14:00 | 29902.74 | 19-DEC-12:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 2628.07 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 315.47 | 13080.44 | |||||
Maximum of Months | 9097.65 | 3317.79 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 6723.57 | 37009.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19101.96 | 02-JAN-06:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 563.73 |
February | 14828.80 | 28-FEB-06:03 | 739.61 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.32 |
March | 14444.07 | 30-MAR-05:03 | 739.61 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.81 |
April | 17811.60 | 25-APR-05:02 | 1109.41 | 305.97 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.40 |
May | 16596.48 | 05-MAY-05:01 | 1664.11 | 458.96 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.72 |
June | 16961.06 | 14-JUN-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.09 |
July | 15693.21 | 19-JUL-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.91 |
August | 18694.30 | 31-AUG-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.37 |
September | 16767.85 | 22-SEP-05:01 | 1664.11 | 458.96 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.93 |
October | 24189.03 | 27-OCT-05:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 974.25 |
November | 18149.81 | 06-NOV-06:01 | 1294.31 | 356.97 | 3853.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.74 |
December | 15160.04 | 16-DEC-06:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14444.07 | 739.61 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.91 | |
Maximum of Months | 24189.03 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 974.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 33041.53 | 01-JAN-13:43 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.50 |
February | 6698.62 | 27-FEB-15:10 | 3955.50 | 2540.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.34 |
March | 12681.50 | 26-MAR-14:05 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.35 | 0.00 |
April | 48841.01 | 23-APR-14:03 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.78 | 0.00 |
May | 52797.13 | 29-MAY-16:23 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 759.92 | 0.00 |
June | 53595.28 | 11-JUN-16:12 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 563.88 | 0.00 |
July | 50939.27 | 23-JUL-14:23 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1051.39 | 0.00 |
August | 51437.31 | 02-AUG-05:01 | 4351.05 | 2999.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.53 |
September | 50669.65 | 10-SEP-17:03 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 773.02 | 0.00 |
October | 53271.26 | 01-OCT-15:43 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.31 | 0.00 |
November | 26762.00 | 05-NOV-14:05 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.13 | 0.00 |
December | 9854.16 | 15-DEC-14:40 | 3955.50 | 2826.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6698.62 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 53595.28 | 4351.05 | 2999.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1051.39 | 80.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 448.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6488.16 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2137.28 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4216.18 |
April | 0.00 | 01-APR-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4693.92 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3065.74 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.72 |
July | 0.00 | 01-JUL-00:03 | 0.00 | 1344.72 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1927.16 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3080.70 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.10 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 448.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6004.47 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2651.36 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5622.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 448.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.10 | |
Maximum of Months | 0.00 | 0.00 | 1344.72 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6488.16 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.261617E+11 | 21903.87 | 02-JAN-16:49 | 0.121774E+10 | 20505.42 | 10-JAN-07:10 |
February | 0.235165E+11 | 23229.12 | 27-FEB-15:39 | 0.703077E+09 | 16421.34 | 06-FEB-06:10 |
March | 0.267999E+11 | 23220.66 | 06-MAR-15:00 | 0.497999E+09 | 13515.72 | 13-MAR-05:10 |
April | 0.272020E+11 | 30817.61 | 28-APR-15:39 | 2942099.78 | 2732.07 | 11-APR-06:30 |
May | 0.354921E+11 | 31282.52 | 10-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.371182E+11 | 33234.06 | 28-JUN-15:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.379189E+11 | 33903.16 | 18-JUL-15:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.392062E+11 | 34579.82 | 03-AUG-15:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.344918E+11 | 33400.25 | 09-SEP-15:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.332164E+11 | 32699.06 | 05-OCT-14:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.263873E+11 | 29369.91 | 02-NOV-14:00 | 35513175.04 | 4899.61 | 15-NOV-07:19 |
December | 0.268882E+11 | 26052.54 | 15-DEC-15:09 | 0.690326E+09 | 15471.87 | 21-DEC-07:10 |
Annual Sum or Average | 0.374399E+12 | 0.314760E+10 | ||||
Minimum of Months | 0.235165E+11 | 21903.87 | 0.00 | 0.00 | ||
Maximum of Months | 0.392062E+11 | 34579.82 | 0.121774E+10 | 20505.42 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.845710E+10 | 15218.55 | 23-JAN-12:50 | 0.00 | 0.00 |
February | 0.942986E+10 | 17618.75 | 13-FEB-12:30 | 0.00 | 0.00 |
March | 0.111177E+11 | 20446.60 | 22-MAR-12:30 | 0.00 | 0.00 |
April | 0.132574E+11 | 20920.24 | 10-APR-12:30 | 0.00 | 0.00 |
May | 0.128487E+11 | 20335.33 | 15-MAY-12:30 | 0.00 | 0.00 |
June | 0.136218E+11 | 20504.39 | 09-JUN-12:30 | 0.00 | 0.00 |
July | 0.132479E+11 | 19378.03 | 06-JUL-12:39 | 0.00 | 0.00 |
August | 0.125069E+11 | 19419.76 | 03-AUG-12:30 | 0.00 | 0.00 |
September | 0.104960E+11 | 18135.09 | 03-SEP-12:30 | 0.00 | 0.00 |
October | 0.104168E+11 | 17420.10 | 01-OCT-12:30 | 0.00 | 0.00 |
November | 0.843847E+10 | 15710.60 | 15-NOV-12:20 | 0.00 | 0.00 |
December | 0.767401E+10 | 14007.36 | 26-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.131513E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.767401E+10 | 14007.36 | 0.00 | 0.00 | |
Maximum of Months | 0.136218E+11 | 20920.24 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.681262E+10 | 0.423301E+10 | 0.112984E+11 | 0.00 | 0.154072E+10 | 0.00 | 0.00 | 0.220739E+09 | 0.00 | 0.00 | 0.00 | 0.205623E+10 | 0.00 |
February | 0.586862E+10 | 0.359832E+10 | 0.103734E+11 | 0.00 | 0.140692E+10 | 0.00 | 0.00 | 0.407152E+09 | 0.00 | 0.00 | 0.00 | 0.186206E+10 | 0.00 |
March | 0.657282E+10 | 0.364505E+10 | 0.121089E+11 | 0.00 | 0.164488E+10 | 0.00 | 0.00 | 0.757858E+09 | 0.00 | 0.00 | 0.00 | 0.207031E+10 | 0.00 |
April | 0.584803E+10 | 0.319905E+10 | 0.112578E+11 | 0.00 | 0.195854E+10 | 0.00 | 0.00 | 0.300632E+10 | 0.00 | 0.00 | 0.00 | 0.193224E+10 | 0.00 |
May | 0.589358E+10 | 0.301210E+10 | 0.117000E+11 | 0.00 | 0.396630E+10 | 0.00 | 0.00 | 0.896678E+10 | 0.00 | 0.00 | 0.00 | 0.195338E+10 | 0.00 |
June | 0.577121E+10 | 0.276234E+10 | 0.116594E+11 | 0.00 | 0.465599E+10 | 0.00 | 0.00 | 0.103987E+11 | 0.00 | 0.00 | 0.00 | 0.187055E+10 | 0.00 |
July | 0.563465E+10 | 0.293985E+10 | 0.112984E+11 | 0.00 | 0.491198E+10 | 0.00 | 0.00 | 0.112561E+11 | 0.00 | 0.00 | 0.00 | 0.187787E+10 | 0.00 |
August | 0.601925E+10 | 0.316977E+10 | 0.121016E+11 | 0.00 | 0.466176E+10 | 0.00 | 0.00 | 0.113315E+11 | 0.00 | 0.00 | 0.00 | 0.192241E+10 | 0.00 |
September | 0.580318E+10 | 0.338901E+10 | 0.112504E+11 | 0.00 | 0.352735E+10 | 0.00 | 0.00 | 0.865504E+10 | 0.00 | 0.00 | 0.00 | 0.186685E+10 | 0.00 |
October | 0.614579E+10 | 0.384631E+10 | 0.113057E+11 | 0.00 | 0.301566E+10 | 0.00 | 0.00 | 0.695055E+10 | 0.00 | 0.00 | 0.00 | 0.195231E+10 | 0.00 |
November | 0.642546E+10 | 0.400863E+10 | 0.108562E+11 | 0.00 | 0.154351E+10 | 0.00 | 0.00 | 0.162283E+10 | 0.00 | 0.00 | 0.00 | 0.193068E+10 | 0.00 |
December | 0.690023E+10 | 0.430763E+10 | 0.112984E+11 | 0.00 | 0.152905E+10 | 0.00 | 0.00 | 0.816002E+09 | 0.00 | 0.00 | 0.00 | 0.203698E+10 | 0.00 |
Annual Sum or Average | 0.736954E+11 | 0.421111E+11 | 0.136508E+12 | 0.00 | 0.343627E+11 | 0.00 | 0.00 | 0.643896E+11 | 0.00 | 0.00 | 0.00 | 0.233319E+11 | 0.00 |
Minimum of Months | 0.563465E+10 | 0.276234E+10 | 0.103734E+11 | 0.00 | 0.140692E+10 | 0.00 | 0.00 | 0.220739E+09 | 0.00 | 0.00 | 0.00 | 0.186206E+10 | 0.00 |
Maximum of Months | 0.690023E+10 | 0.430763E+10 | 0.121089E+11 | 0.00 | 0.491198E+10 | 0.00 | 0.00 | 0.113315E+11 | 0.00 | 0.00 | 0.00 | 0.207031E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.121774E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.703077E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.497999E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 2942099.78 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 35513175.04 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.690326E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.314760E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.121774E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 6826.95 | 06-JAN-15:00 | 3768.97 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 1888.28 | 10-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 6922.52 | 01-FEB-09:09 | 3768.97 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 1819.60 | 06-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 6865.20 | 13-MAR-08:09 | 3768.97 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 1762.27 | 13-MAR-06:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 6738.19 | 14-APR-08:09 | 3768.97 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 4104.82 | 28-APR-16:40 | 0.00 | 0.00 | 01-APR-00:10 |
May | 6359.47 | 03-MAY-08:09 | 3768.97 | 01-MAY-05:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 4138.00 | 30-MAY-11:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 6129.84 | 08-JUN-07:10 | 3768.97 | 01-JUN-05:10 | 10035.17 | 01-JUN-07:10 | 0.00 | 4464.85 | 28-JUN-15:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 6072.26 | 14-JUL-07:10 | 3768.97 | 01-JUL-05:10 | 10035.17 | 01-JUL-07:10 | 0.00 | 4574.70 | 18-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 6398.49 | 08-AUG-07:10 | 3768.97 | 01-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 4780.72 | 03-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 6626.19 | 30-SEP-07:10 | 3768.97 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 4523.74 | 09-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 6888.00 | 25-OCT-07:10 | 3768.97 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 4445.88 | 06-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 7208.28 | 27-NOV-15:30 | 3768.97 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 3939.69 | 07-NOV-12:50 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 7170.42 | 28-DEC-09:09 | 3768.97 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 1819.71 | 21-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 6072.26 | 3768.97 | 10035.17 | 0.00 | 1762.27 | 0.00 | 0.00 | |||||
Maximum of Months | 7208.28 | 3768.97 | 10035.17 | 0.00 | 4780.72 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 6937.53 | 01-JAN-12:39 | 0.00 | 0.00 | 0.00 | 1773.06 | 24-JAN-12:39 | 0.00 | 01-JAN-00:10 |
February | 4537.47 | 27-FEB-14:00 | 0.00 | 0.00 | 0.00 | 1772.24 | 03-FEB-12:00 | 0.00 | 01-FEB-00:10 |
March | 5154.75 | 29-MAR-14:00 | 0.00 | 0.00 | 0.00 | 1765.22 | 01-MAR-12:39 | 0.00 | 01-MAR-00:10 |
April | 11090.83 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 | 1749.46 | 01-APR-11:00 | 0.00 | 01-APR-00:10 |
May | 11228.74 | 25-MAY-15:09 | 0.00 | 0.00 | 0.00 | 1731.13 | 01-MAY-11:50 | 0.00 | 01-MAY-00:10 |
June | 13281.63 | 28-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1713.98 | 01-JUN-11:50 | 0.00 | 01-JUN-00:10 |
July | 13999.05 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | 1702.98 | 01-JUL-11:00 | 0.00 | 01-JUL-00:10 |
August | 14725.71 | 03-AUG-16:10 | 0.00 | 0.00 | 0.00 | 1707.49 | 31-AUG-11:50 | 0.00 | 01-AUG-00:10 |
September | 13965.06 | 09-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1721.48 | 30-SEP-11:20 | 0.00 | 01-SEP-00:10 |
October | 13058.57 | 06-OCT-11:00 | 0.00 | 0.00 | 0.00 | 1740.03 | 31-OCT-11:09 | 0.00 | 01-OCT-00:10 |
November | 8287.28 | 02-NOV-14:30 | 0.00 | 0.00 | 0.00 | 1757.57 | 30-NOV-12:30 | 0.00 | 01-NOV-00:10 |
December | 6694.26 | 15-DEC-14:09 | 0.00 | 0.00 | 0.00 | 1769.55 | 29-DEC-12:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4537.47 | 0.00 | 0.00 | 0.00 | 1702.98 | 0.00 | |||
Maximum of Months | 14725.71 | 0.00 | 0.00 | 0.00 | 1773.06 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 21903.87 | 02-JAN-16:49 | 6186.83 | 10035.17 | 0.00 | 0.00 | 1527.78 | 0.00 | 0.00 | 2559.40 | 0.00 |
February | 23229.12 | 27-FEB-15:39 | 5518.29 | 10035.17 | 0.00 | 0.00 | 1527.78 | 0.00 | 0.00 | 4415.52 | 0.00 |
March | 23220.66 | 06-MAR-15:00 | 6004.60 | 10035.17 | 0.00 | 0.00 | 1527.78 | 0.00 | 0.00 | 3923.07 | 0.00 |
April | 30817.61 | 28-APR-15:39 | 4108.10 | 10035.17 | 0.00 | 0.00 | 4029.02 | 0.00 | 0.00 | 11059.81 | 0.00 |
May | 31282.52 | 10-MAY-15:00 | 4410.72 | 10035.17 | 0.00 | 0.00 | 4081.35 | 0.00 | 0.00 | 11171.60 | 0.00 |
June | 33234.06 | 28-JUN-15:30 | 4033.55 | 10035.17 | 0.00 | 0.00 | 4436.56 | 0.00 | 0.00 | 13150.86 | 0.00 |
July | 33903.16 | 18-JUL-15:39 | 3842.20 | 10035.17 | 0.00 | 0.00 | 4570.17 | 0.00 | 0.00 | 13878.58 | 0.00 |
August | 34579.82 | 03-AUG-15:30 | 3674.37 | 10035.17 | 0.00 | 0.00 | 4712.90 | 0.00 | 0.00 | 14580.36 | 0.00 |
September | 33400.25 | 09-SEP-15:39 | 3876.23 | 10035.17 | 0.00 | 0.00 | 4441.99 | 0.00 | 0.00 | 13467.05 | 0.00 |
October | 32699.06 | 05-OCT-14:00 | 4876.59 | 10035.17 | 0.00 | 0.00 | 4192.66 | 0.00 | 0.00 | 11897.14 | 0.00 |
November | 29369.91 | 02-NOV-14:00 | 5542.22 | 10035.17 | 0.00 | 0.00 | 3868.36 | 0.00 | 0.00 | 8211.90 | 0.00 |
December | 26052.54 | 15-DEC-15:09 | 6344.66 | 10035.17 | 0.00 | 0.00 | 1527.78 | 0.00 | 0.00 | 6413.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 21903.87 | 3674.37 | 10035.17 | 0.00 | 0.00 | 1527.78 | 0.00 | 0.00 | 2559.40 | 0.00 | |
Maximum of Months | 34579.82 | 6344.66 | 10035.17 | 0.00 | 0.00 | 4712.90 | 0.00 | 0.00 | 14580.36 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 20505.42 | 10-JAN-07:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 16421.34 | 06-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 13515.72 | 13-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 2732.07 | 11-APR-06:30 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 4899.61 | 15-NOV-07:19 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 15471.87 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 20505.42 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 20.36 | 2.00 | 20.36 | 0.17 | 20.53 | 0.17 | 20.68 |
February | 1.17 | 20.30 | 1.17 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
March | 0.50 | 20.38 | 0.50 | 20.38 | 0.17 | 20.96 | 0.17 | 21.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.54 | 0.50 | 24.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 24.97 | 8.00 | 24.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 24.78 | 7.83 | 24.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 24.93 | 8.33 | 24.93 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 25.09 | 8.50 | 25.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 24.89 | 8.17 | 24.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 25.09 | 5.00 | 24.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.17 | 20.44 | 1.17 | 20.44 | 0.17 | 20.72 | 0.17 | 20.95 |
Annual Sum or Average | 4.83 | 20.37 | 4.83 | 20.37 | 48.17 | 24.18 | 46.83 | 24.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 20.44 | 2.00 | 20.44 | 8.83 | 25.09 | 8.50 | 25.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.34 | 0.00 | 27.34 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.36 | 0.00 | 27.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 19.83 | 27.44 | 0.00 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 25.50 | 27.43 | 0.00 | 27.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 | 27.45 | 0.17 | 27.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 27.43 | 0.17 | 27.43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 27.52 | 0.00 | 27.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 27.46 | 0.00 | 27.46 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.28 | 0.00 | 27.28 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 144.17 | 27.45 | 0.33 | 27.45 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 | 27.52 | 0.17 | 27.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 274.33 | 22.40 | 135.33 | 22.36 | 115.83 | 22.28 |
February | 222.83 | 22.68 | 142.50 | 22.80 | 96.33 | 22.75 |
March | 234.83 | 22.88 | 136.67 | 22.97 | 73.33 | 22.89 |
April | 72.17 | 23.59 | 215.33 | 23.83 | 29.67 | 23.84 |
May | 54.50 | 24.01 | 312.00 | 23.94 | 54.50 | 23.94 |
June | 55.50 | 24.02 | 312.00 | 23.94 | 55.50 | 23.95 |
July | 80.50 | 24.03 | 300.00 | 23.95 | 80.50 | 23.97 |
August | 78.67 | 24.03 | 324.00 | 23.95 | 78.67 | 23.97 |
September | 69.50 | 24.02 | 300.00 | 23.95 | 69.50 | 23.96 |
October | 55.17 | 23.96 | 262.67 | 23.93 | 44.50 | 23.94 |
November | 138.83 | 23.42 | 117.33 | 23.64 | 31.33 | 23.67 |
December | 230.67 | 22.66 | 130.33 | 22.80 | 82.00 | 22.75 |
Annual Sum or Average | 1567.50 | 23.10 | 2688.17 | 23.48 | 811.67 | 23.45 |
Minimum of Months | 54.50 | 22.40 | 117.33 | 22.36 | 29.67 | 22.28 |
Maximum of Months | 274.33 | 24.03 | 324.00 | 23.95 | 115.83 | 23.97 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 288.67 | 20.75 | 191.50 | 20.65 | 181.17 | 20.53 |
February | 269.83 | 22.07 | 191.67 | 22.11 | 189.00 | 22.12 |
March | 276.83 | 22.82 | 189.00 | 23.12 | 160.67 | 23.13 |
April | 220.67 | 25.89 | 262.50 | 26.07 | 192.33 | 26.14 |
May | 309.00 | 26.70 | 312.00 | 26.70 | 309.00 | 26.70 |
June | 306.67 | 26.71 | 312.00 | 26.71 | 306.67 | 26.71 |
July | 299.00 | 26.72 | 300.00 | 26.72 | 299.00 | 26.72 |
August | 319.00 | 26.72 | 324.00 | 26.72 | 319.00 | 26.72 |
September | 295.50 | 26.71 | 300.00 | 26.71 | 295.50 | 26.71 |
October | 248.67 | 26.56 | 284.17 | 26.56 | 240.67 | 26.60 |
November | 185.00 | 24.62 | 189.50 | 25.25 | 109.17 | 25.43 |
December | 268.83 | 22.20 | 205.17 | 22.39 | 180.17 | 22.34 |
Annual Sum or Average | 3287.67 | 24.93 | 3061.50 | 25.19 | 2782.33 | 25.26 |
Minimum of Months | 185.00 | 20.75 | 189.00 | 20.65 | 109.17 | 20.53 |
Maximum of Months | 319.00 | 26.72 | 324.00 | 26.72 | 319.00 | 26.72 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 288.50 | 20.21 | 211.83 | 20.06 | 205.50 | 19.95 |
February | 276.00 | 21.49 | 205.33 | 21.46 | 205.33 | 21.45 |
March | 276.83 | 22.85 | 182.33 | 23.14 | 155.17 | 23.16 |
April | 237.50 | 27.90 | 275.33 | 27.85 | 220.17 | 27.98 |
May | 312.00 | 30.27 | 312.00 | 30.27 | 312.00 | 30.27 |
June | 312.00 | 30.70 | 312.00 | 30.70 | 312.00 | 30.70 |
July | 300.00 | 30.78 | 300.00 | 30.78 | 300.00 | 30.78 |
August | 324.00 | 30.52 | 324.00 | 30.52 | 324.00 | 30.52 |
September | 300.00 | 29.64 | 300.00 | 29.64 | 300.00 | 29.64 |
October | 269.83 | 29.40 | 293.17 | 29.26 | 266.00 | 29.33 |
November | 192.50 | 25.35 | 180.83 | 25.97 | 117.17 | 26.25 |
December | 272.67 | 21.95 | 199.17 | 22.07 | 180.00 | 22.02 |
Annual Sum or Average | 3361.83 | 26.93 | 3096.00 | 27.24 | 2897.33 | 27.39 |
Minimum of Months | 192.50 | 20.21 | 180.83 | 20.06 | 117.17 | 19.95 |
Maximum of Months | 324.00 | 30.78 | 324.00 | 30.78 | 324.00 | 30.78 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.863383E+09 | 0.189337E+09 | 53.15 | 0.554217E+09 | 0.309166E+09 | 0.00 | 1.00 | 02-JAN-06:02 | 0.00 | 01-JAN-00:10 | 22533.06 | 02-JAN-06:02 | 12288.78 | 02-JAN-06:02 | 10244.28 | 02-JAN-06:02 | 4553.37 | 02-JAN-06:02 | 0.00 | 01-JAN-00:10 |
February | 0.153723E+10 | 0.337043E+09 | 90.04 | 0.100872E+10 | 0.528506E+09 | 0.00 | 1.00 | 27-FEB-06:05 | 0.00 | 01-FEB-00:10 | 22307.27 | 28-FEB-06:03 | 10918.61 | 28-FEB-06:03 | 11388.65 | 28-FEB-06:03 | 4461.66 | 28-FEB-06:03 | 0.00 | 01-FEB-00:10 |
March | 0.258121E+10 | 0.565278E+09 | 141.96 | 0.175956E+10 | 0.821651E+09 | 0.00 | 1.00 | 07-MAR-06:03 | 0.00 | 01-MAR-00:10 | 25585.67 | 07-MAR-06:03 | 16750.35 | 30-MAR-05:03 | 14612.54 | 07-MAR-06:03 | 5026.70 | 07-MAR-06:03 | 0.00 | 01-MAR-00:10 |
April | 0.582647E+10 | 0.128009E+10 | 241.80 | 0.418306E+10 | 0.164341E+10 | 0.00 | 1.00 | 01-APR-05:03 | 0.00 | 01-APR-00:10 | 26755.26 | 29-APR-05:01 | 17006.32 | 28-APR-05:01 | 14365.32 | 29-APR-05:02 | 5174.22 | 29-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.123911E+11 | 0.270996E+10 | 309.44 | 0.836651E+10 | 0.402461E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 28236.28 | 23-MAY-05:01 | 20251.11 | 28-MAY-15:23 | 17479.16 | 23-MAY-05:01 | 5683.55 | 28-MAY-15:23 | 0.00 | 01-MAY-00:10 |
June | 0.133349E+11 | 0.294296E+10 | 308.56 | 0.903497E+10 | 0.429992E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 27834.63 | 30-JUN-05:01 | 22161.41 | 11-JUN-15:40 | 15867.95 | 05-JUN-05:01 | 5378.66 | 11-JUN-15:40 | 0.00 | 01-JUN-00:10 |
July | 0.138563E+11 | 0.303738E+10 | 296.88 | 0.891269E+10 | 0.494366E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:03 | 28187.58 | 31-JUL-05:01 | 17322.65 | 19-JUL-05:01 | 16767.85 | 31-JUL-05:01 | 5394.04 | 03-JUL-05:01 | 0.00 | 01-JUL-00:03 |
August | 0.149399E+11 | 0.325415E+10 | 320.24 | 0.970522E+10 | 0.523470E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 28335.88 | 11-AUG-05:01 | 20464.44 | 31-AUG-05:01 | 17474.58 | 11-AUG-05:02 | 5551.97 | 06-AUG-15:05 | 0.00 | 01-AUG-00:10 |
September | 0.125826E+11 | 0.267815E+10 | 301.32 | 0.804667E+10 | 0.453597E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 28049.73 | 11-SEP-05:01 | 18048.94 | 01-SEP-05:01 | 17620.93 | 05-SEP-05:01 | 5378.67 | 19-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 0.102005E+11 | 0.220138E+10 | 267.56 | 0.686349E+10 | 0.333697E+10 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 28271.37 | 23-OCT-05:01 | 19810.98 | 26-OCT-05:01 | 17426.78 | 21-OCT-05:01 | 5404.12 | 25-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.406057E+10 | 0.879057E+09 | 189.77 | 0.278570E+10 | 0.127487E+10 | 0.00 | 1.00 | 01-NOV-05:02 | 0.00 | 01-NOV-00:10 | 27068.33 | 02-NOV-05:01 | 16874.27 | 03-NOV-05:01 | 14566.27 | 04-NOV-05:10 | 5210.58 | 02-NOV-05:01 | 0.00 | 01-NOV-00:10 |
December | 0.243495E+10 | 0.527748E+09 | 110.93 | 0.160598E+10 | 0.828965E+09 | 0.00 | 1.00 | 11-DEC-06:03 | 0.00 | 01-DEC-00:10 | 26156.59 | 15-DEC-06:02 | 12603.76 | 16-DEC-06:02 | 15381.21 | 15-DEC-06:02 | 5101.02 | 15-DEC-06:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.946092E+11 | 0.206025E+11 | 2631.66 | 0.628268E+11 | 0.317824E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.863383E+09 | 0.189337E+09 | 53.15 | 0.554217E+09 | 0.309166E+09 | 0.00 | 1.00 | 0.00 | 22307.27 | 10918.61 | 10244.28 | 4461.66 | 0.00 | |||||||
Maximum of Months | 0.149399E+11 | 0.325415E+10 | 320.24 | 0.970522E+10 | 0.523470E+10 | 0.00 | 1.00 | 0.00 | 28335.88 | 22161.41 | 17620.93 | 5683.55 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.137986E+09 | 31402064.64 | 6.39 | 0.103919E+09 | 34066626.41 | 0.00 | 1.00 | 01-JAN-12:35 | 0.00 | 01-JAN-00:10 | 67432.67 | 01-JAN-12:35 | 50639.29 | 01-JAN-13:43 | 20433.42 | 01-JAN-12:35 | 13875.06 | 01-JAN-12:35 | 0.00 | 01-JAN-00:10 |
February | 0.298857E+09 | 70108265.82 | 17.50 | 0.183026E+09 | 0.115831E+09 | 0.00 | 0.37 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 11702.75 | 27-FEB-15:00 | 7418.40 | 27-FEB-15:00 | 4284.36 | 27-FEB-15:00 | 2695.69 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.824297E+09 | 0.192580E+09 | 36.25 | 0.467990E+09 | 0.356308E+09 | 0.00 | 0.63 | 26-MAR-14:05 | 0.00 | 01-MAR-00:10 | 19845.21 | 26-MAR-14:05 | 13888.23 | 26-MAR-14:05 | 5956.98 | 26-MAR-14:05 | 4621.20 | 26-MAR-14:05 | 0.00 | 01-MAR-00:10 |
April | 0.751648E+10 | 0.172623E+10 | 143.26 | 0.512464E+10 | 0.239184E+10 | 0.00 | 1.00 | 16-APR-13:35 | 0.00 | 01-APR-00:10 | 75491.29 | 30-APR-14:25 | 54437.50 | 16-APR-14:55 | 39295.38 | 30-APR-14:25 | 15054.60 | 30-APR-14:25 | 0.00 | 01-APR-00:10 |
May | 0.273132E+11 | 0.625683E+10 | 388.36 | 0.178841E+11 | 0.942909E+10 | 0.00 | 1.00 | 01-MAY-17:10 | 0.00 | 01-MAY-00:10 | 77744.21 | 21-MAY-08:65 | 55745.20 | 29-MAY-16:23 | 43466.57 | 21-MAY-08:65 | 15411.58 | 21-MAY-08:65 | 0.00 | 01-MAY-00:10 |
June | 0.325864E+11 | 0.745575E+10 | 422.26 | 0.217358E+11 | 0.108506E+11 | 0.00 | 1.00 | 01-JUN-17:08 | 0.00 | 01-JUN-00:10 | 70360.58 | 19-JUN-17:10 | 56723.60 | 11-JUN-16:12 | 24806.13 | 20-JUN-17:08 | 15291.16 | 20-JUN-17:08 | 0.00 | 01-JUN-00:10 |
July | 0.362470E+11 | 0.821876E+10 | 463.96 | 0.227884E+11 | 0.134586E+11 | 0.00 | 1.00 | 01-JUL-17:08 | 0.00 | 01-JUL-00:07 | 74763.12 | 26-JUL-05:01 | 54761.19 | 23-JUL-11:03 | 33406.24 | 31-JUL-17:10 | 15533.12 | 03-JUL-17:08 | 0.00 | 01-JUL-00:03 |
August | 0.357955E+11 | 0.807733E+10 | 456.15 | 0.224955E+11 | 0.133000E+11 | 0.00 | 1.00 | 01-AUG-13:10 | 0.00 | 01-AUG-00:10 | 73715.63 | 12-AUG-17:10 | 55375.41 | 02-AUG-05:01 | 28738.75 | 12-AUG-17:10 | 15551.50 | 02-AUG-17:06 | 0.00 | 01-AUG-00:10 |
September | 0.267131E+11 | 0.597689E+10 | 370.62 | 0.161521E+11 | 0.105610E+11 | 0.00 | 1.00 | 01-SEP-12:10 | 0.00 | 01-SEP-00:10 | 75508.99 | 02-SEP-21:45 | 53449.34 | 10-SEP-17:03 | 40424.72 | 02-SEP-21:45 | 15959.07 | 09-SEP-17:06 | 0.00 | 01-SEP-00:10 |
October | 0.212046E+11 | 0.474916E+10 | 290.79 | 0.132291E+11 | 0.797554E+10 | 0.00 | 1.00 | 01-OCT-09:45 | 0.00 | 01-OCT-00:10 | 78947.99 | 08-OCT-07:45 | 57983.17 | 01-OCT-15:43 | 47591.97 | 08-OCT-07:45 | 15489.37 | 08-OCT-13:53 | 0.00 | 01-OCT-00:10 |
November | 0.329097E+10 | 0.743774E+09 | 65.83 | 0.195149E+10 | 0.133948E+10 | 0.00 | 1.00 | 05-NOV-13:25 | 0.00 | 01-NOV-00:10 | 37889.92 | 05-NOV-14:05 | 29000.26 | 05-NOV-14:05 | 14247.40 | 11-NOV-13:10 | 8111.28 | 05-NOV-14:05 | 0.00 | 01-NOV-00:10 |
December | 0.125141E+10 | 0.288255E+09 | 34.17 | 0.722332E+09 | 0.529083E+09 | 0.00 | 0.59 | 15-DEC-14:20 | 0.00 | 01-DEC-00:10 | 19059.92 | 15-DEC-14:10 | 12099.96 | 15-DEC-14:40 | 7897.81 | 15-DEC-13:10 | 4399.93 | 15-DEC-14:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.193180E+12 | 0.437871E+11 | 2695.53 | 0.122838E+12 | 0.703414E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.137986E+09 | 31402064.64 | 6.39 | 0.103919E+09 | 34066626.41 | 0.00 | 0.37 | 0.00 | 11702.75 | 7418.40 | 4284.36 | 2695.69 | 0.00 | |||||||
Maximum of Months | 0.362470E+11 | 0.821876E+10 | 463.96 | 0.227884E+11 | 0.134586E+11 | 0.00 | 1.00 | 0.00 | 78947.99 | 57983.17 | 47591.97 | 15959.07 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.66 | 39.24 | 33.42 | 100.27 | 78.89 | 0.00 | 0.00 | 0.00 |
February | 82.22 | 41.56 | 40.67 | 117.04 | 66.08 | 0.00 | 0.00 | 0.00 |
March | 81.19 | 35.92 | 45.27 | 117.41 | 60.24 | 0.00 | 0.00 | 0.00 |
April | 100.70 | 46.25 | 54.45 | 158.11 | 46.11 | 0.00 | 0.00 | 0.00 |
May | 83.88 | 27.30 | 56.58 | 155.25 | 19.14 | 0.00 | 0.00 | 0.00 |
June | 93.27 | 32.78 | 60.49 | 175.91 | 17.82 | 0.00 | 0.00 | 0.00 |
July | 84.98 | 23.55 | 61.44 | 159.18 | 14.10 | 0.00 | 0.00 | 0.00 |
August | 85.92 | 26.20 | 59.72 | 161.31 | 18.41 | 0.00 | 0.00 | 0.00 |
September | 79.21 | 27.20 | 52.02 | 141.28 | 23.96 | 0.00 | 0.00 | 0.00 |
October | 80.89 | 34.87 | 46.02 | 139.57 | 36.19 | 0.00 | 0.00 | 0.00 |
November | 69.45 | 34.89 | 34.56 | 102.39 | 62.45 | 0.00 | 0.00 | 0.00 |
December | 66.82 | 35.53 | 31.29 | 94.30 | 72.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 81.72 | 33.69 | 48.03 | 135.21 | 42.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.82 | 23.55 | 31.29 | 94.30 | 14.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.70 | 46.25 | 61.44 | 175.91 | 78.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.66 | 39.24 | 33.42 | 100.27 | 78.89 | 0.00 | 0.00 | 0.00 |
February | 82.22 | 41.56 | 40.67 | 117.04 | 66.08 | 0.00 | 0.00 | 0.00 |
March | 81.19 | 35.92 | 45.27 | 117.41 | 60.24 | 0.00 | 0.00 | 0.00 |
April | 100.70 | 46.25 | 54.45 | 158.11 | 46.11 | 0.00 | 0.00 | 0.00 |
May | 83.88 | 27.30 | 56.58 | 155.25 | 19.14 | 0.00 | 0.00 | 0.00 |
June | 93.27 | 32.78 | 60.49 | 175.91 | 17.82 | 0.00 | 0.00 | 0.00 |
July | 84.98 | 23.55 | 61.44 | 159.18 | 14.10 | 0.00 | 0.00 | 0.00 |
August | 85.92 | 26.20 | 59.72 | 161.31 | 18.41 | 0.00 | 0.00 | 0.00 |
September | 79.21 | 27.20 | 52.02 | 141.28 | 23.96 | 0.00 | 0.00 | 0.00 |
October | 80.89 | 34.87 | 46.02 | 139.57 | 36.19 | 0.00 | 0.00 | 0.00 |
November | 69.45 | 34.89 | 34.56 | 102.39 | 62.45 | 0.00 | 0.00 | 0.00 |
December | 66.82 | 35.53 | 31.29 | 94.30 | 72.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 81.72 | 33.69 | 48.03 | 135.21 | 42.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.82 | 23.55 | 31.29 | 94.30 | 14.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.70 | 46.25 | 61.44 | 175.91 | 78.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.50 | 0.00 | 15.50 | 13.13 | 48.72 | 0.00 | 0.00 | 0.00 |
February | 18.29 | 0.00 | 18.29 | 17.35 | 40.29 | 0.00 | 0.00 | 0.00 |
March | 21.22 | 0.00 | 21.22 | 23.39 | 36.32 | 0.00 | 0.00 | 0.00 |
April | 25.11 | 0.15 | 24.96 | 33.35 | 27.25 | 0.00 | 0.00 | 0.00 |
May | 28.42 | 1.07 | 27.35 | 54.08 | 10.76 | 0.00 | 0.00 | 0.00 |
June | 32.21 | 2.19 | 30.02 | 63.98 | 10.01 | 0.00 | 0.00 | 0.00 |
July | 31.28 | 1.17 | 30.12 | 60.76 | 8.09 | 0.00 | 0.00 | 0.00 |
August | 28.13 | 0.29 | 27.84 | 54.66 | 10.47 | 0.00 | 0.00 | 0.00 |
September | 24.22 | 0.00 | 24.22 | 43.05 | 13.98 | 0.00 | 0.00 | 0.00 |
October | 21.04 | 0.00 | 21.04 | 34.51 | 21.38 | 0.00 | 0.00 | 0.00 |
November | 15.97 | 0.00 | 15.97 | 16.53 | 37.71 | 0.00 | 0.00 | 0.00 |
December | 14.41 | 0.00 | 14.41 | 12.68 | 44.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.01 | 0.41 | 22.60 | 35.73 | 25.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.41 | 0.00 | 14.41 | 12.68 | 8.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.21 | 2.19 | 30.12 | 63.98 | 48.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.50 | 0.00 | 15.50 | 13.13 | 48.72 | 0.00 | 0.00 | 0.00 |
February | 18.29 | 0.00 | 18.29 | 17.35 | 40.29 | 0.00 | 0.00 | 0.00 |
March | 21.22 | 0.00 | 21.22 | 23.39 | 36.32 | 0.00 | 0.00 | 0.00 |
April | 25.11 | 0.15 | 24.96 | 33.34 | 27.25 | 0.00 | 0.00 | 0.00 |
May | 28.42 | 1.07 | 27.35 | 54.08 | 10.76 | 0.00 | 0.00 | 0.00 |
June | 32.21 | 2.19 | 30.02 | 63.97 | 10.01 | 0.00 | 0.00 | 0.00 |
July | 31.28 | 1.17 | 30.12 | 60.76 | 8.09 | 0.00 | 0.00 | 0.00 |
August | 28.13 | 0.29 | 27.84 | 54.66 | 10.47 | 0.00 | 0.00 | 0.00 |
September | 24.22 | 0.00 | 24.22 | 43.05 | 13.98 | 0.00 | 0.00 | 0.00 |
October | 21.04 | 0.00 | 21.04 | 34.51 | 21.38 | 0.00 | 0.00 | 0.00 |
November | 15.97 | 0.00 | 15.97 | 16.52 | 37.71 | 0.00 | 0.00 | 0.00 |
December | 14.41 | 0.00 | 14.41 | 12.68 | 44.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.01 | 0.41 | 22.60 | 35.73 | 25.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.41 | 0.00 | 14.41 | 12.68 | 8.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.21 | 2.19 | 30.12 | 63.97 | 48.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.51 | 34.35 | 22.83 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.91 | 31.10 | 52.00 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.31 | 28.13 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.11 | 24.94 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.72 | 13.26 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.49 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.52 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.23 | 12.63 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.77 | 15.14 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.77 | 19.99 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.40 | 31.63 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.68 | 32.73 | 6.33 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.83 | 22.26 | 81.17 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.68 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.49 | 34.35 | 52.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.51 | 34.35 | 22.83 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.91 | 31.10 | 52.00 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.31 | 28.13 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.11 | 24.94 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.72 | 13.26 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.49 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.52 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.23 | 12.63 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.77 | 15.14 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.77 | 19.99 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.40 | 31.63 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.68 | 32.73 | 6.33 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.83 | 22.26 | 81.17 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.68 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.49 | 34.35 | 52.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.51 | 34.35 | 22.83 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.91 | 31.10 | 52.00 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.31 | 28.13 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.11 | 24.94 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.72 | 13.26 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.49 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.52 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.23 | 12.63 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.77 | 15.14 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.77 | 19.99 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.40 | 31.63 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.68 | 32.73 | 6.33 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.83 | 22.26 | 81.17 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.68 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.49 | 34.35 | 52.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.51 | 34.35 | 22.83 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.91 | 31.10 | 52.00 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.31 | 28.13 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.11 | 24.94 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.72 | 13.26 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.49 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.52 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.23 | 12.63 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.77 | 15.14 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.77 | 19.99 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.40 | 31.63 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.68 | 32.73 | 6.33 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.83 | 22.26 | 81.17 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.68 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.49 | 34.35 | 52.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.51 | 34.35 | 22.83 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.91 | 31.10 | 52.00 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.31 | 28.13 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.11 | 24.94 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.72 | 13.26 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.49 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.52 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.23 | 12.63 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.77 | 15.14 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.77 | 19.99 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.40 | 31.63 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.68 | 32.73 | 6.33 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.83 | 22.26 | 81.17 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.68 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.49 | 34.35 | 52.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.51 | 34.35 | 22.83 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.91 | 31.10 | 52.00 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.31 | 28.13 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.11 | 24.94 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.72 | 13.26 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.49 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.52 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.23 | 12.63 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.77 | 15.14 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.77 | 19.99 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.40 | 31.63 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.68 | 32.73 | 6.33 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.83 | 22.26 | 81.17 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.68 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.49 | 34.35 | 52.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.51 | 34.35 | 22.83 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.91 | 31.10 | 52.00 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.31 | 28.13 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.11 | 24.94 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.72 | 13.26 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.49 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.52 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.23 | 12.63 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.77 | 15.14 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.77 | 19.99 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.40 | 31.63 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.68 | 32.73 | 6.33 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.83 | 22.26 | 81.17 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.68 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.49 | 34.35 | 52.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.51 | 34.35 | 22.83 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.91 | 31.10 | 52.00 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.31 | 28.13 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.11 | 24.94 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.72 | 13.26 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.49 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.52 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.23 | 12.63 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.77 | 15.14 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.77 | 19.99 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.40 | 31.63 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.68 | 32.73 | 6.33 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.83 | 22.26 | 81.17 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.68 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.49 | 34.35 | 52.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.51 | 34.35 | 22.83 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.91 | 31.10 | 52.00 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.31 | 28.13 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.11 | 24.94 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.72 | 13.26 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.49 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.52 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.23 | 12.63 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.77 | 15.14 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.77 | 19.99 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.40 | 31.63 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.68 | 32.73 | 6.33 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.83 | 22.26 | 81.17 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.68 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.49 | 34.35 | 52.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.51 | 34.35 | 22.83 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.91 | 31.10 | 52.00 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.31 | 28.13 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.11 | 24.94 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.72 | 13.26 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.49 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.52 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.23 | 12.63 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.77 | 15.14 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.77 | 19.99 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.40 | 31.63 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.68 | 32.73 | 6.33 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.83 | 22.26 | 81.17 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.68 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.49 | 34.35 | 52.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.51 | 34.35 | 22.83 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.91 | 31.10 | 52.00 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.31 | 28.13 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.11 | 24.94 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.72 | 13.26 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.49 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.52 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.23 | 12.63 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.77 | 15.14 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.77 | 19.99 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.40 | 31.63 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.68 | 32.73 | 6.33 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.83 | 22.26 | 81.17 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.68 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.49 | 34.35 | 52.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.51 | 34.35 | 22.83 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.91 | 31.10 | 52.00 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.31 | 28.13 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.11 | 24.94 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.72 | 13.26 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.49 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.52 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.23 | 12.63 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.77 | 15.14 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.77 | 19.99 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.40 | 31.63 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.68 | 32.73 | 6.33 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.83 | 22.26 | 81.17 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.68 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.49 | 34.35 | 52.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.51 | 34.35 | 22.83 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.91 | 31.10 | 52.00 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.31 | 28.13 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.11 | 24.94 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.72 | 13.26 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.49 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.52 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.23 | 12.63 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.77 | 15.14 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.77 | 19.99 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.40 | 31.63 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.68 | 32.73 | 6.33 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.83 | 22.26 | 81.17 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.68 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.49 | 34.35 | 52.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.51 | 34.35 | 22.83 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.91 | 31.10 | 52.00 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.31 | 28.13 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.11 | 24.94 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.72 | 13.26 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.49 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.52 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.23 | 12.63 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.77 | 15.14 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.77 | 19.99 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.40 | 31.63 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.68 | 32.73 | 6.33 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.83 | 22.26 | 81.17 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.68 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.49 | 34.35 | 52.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.68 | 40.38 | 68.67 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.73 | 35.72 | 130.33 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.90 | 34.21 | 19.33 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.47 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.19 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.98 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.44 | 19.96 | 4.17 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 9.67 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.21 | 25.21 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.47 | 30.01 | 18.67 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.12 | 39.09 | 37.83 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.95 | 38.87 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.76 | 30.24 | 349.67 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.95 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.98 | 40.38 | 130.33 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194611E+09 | 0.105110E+09 | 89501092.54 | 0.268558E+09 | 0.211292E+09 |
February | 0.198918E+09 | 0.100540E+09 | 98377706.66 | 0.283154E+09 | 0.159870E+09 |
March | 0.217457E+09 | 96218383.29 | 0.121239E+09 | 0.314482E+09 | 0.161336E+09 |
April | 0.261006E+09 | 0.119869E+09 | 0.141136E+09 | 0.409811E+09 | 0.119513E+09 |
May | 0.224677E+09 | 73120105.75 | 0.151557E+09 | 0.415813E+09 | 51255409.99 |
June | 0.241752E+09 | 84969007.38 | 0.156783E+09 | 0.455958E+09 | 46201226.58 |
July | 0.227617E+09 | 63068180.83 | 0.164548E+09 | 0.426351E+09 | 37753252.71 |
August | 0.230136E+09 | 70173695.79 | 0.159962E+09 | 0.432039E+09 | 49298037.28 |
September | 0.205325E+09 | 70495794.42 | 0.134829E+09 | 0.366192E+09 | 62108176.94 |
October | 0.216657E+09 | 93406824.73 | 0.123250E+09 | 0.373812E+09 | 96926901.20 |
November | 0.180008E+09 | 90429008.90 | 89578959.29 | 0.265384E+09 | 0.161863E+09 |
December | 0.178966E+09 | 95159512.64 | 83806726.57 | 0.252570E+09 | 0.193729E+09 |
Annual Sum or Average | 0.257713E+10 | 0.106256E+10 | 0.151457E+10 | 0.426412E+10 | 0.135115E+10 |
Minimum of Months | 0.178966E+09 | 63068180.83 | 83806726.57 | 0.252570E+09 | 37753252.71 |
Maximum of Months | 0.261006E+09 | 0.119869E+09 | 0.164548E+09 | 0.455958E+09 | 0.211292E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194611E+09 | 0.105110E+09 | 89501092.54 | 0.268558E+09 | 0.211292E+09 |
February | 0.198918E+09 | 0.100540E+09 | 98377706.66 | 0.283154E+09 | 0.159870E+09 |
March | 0.217457E+09 | 96218383.29 | 0.121239E+09 | 0.314482E+09 | 0.161336E+09 |
April | 0.261006E+09 | 0.119869E+09 | 0.141136E+09 | 0.409811E+09 | 0.119513E+09 |
May | 0.224677E+09 | 73120105.75 | 0.151557E+09 | 0.415813E+09 | 51255409.99 |
June | 0.241752E+09 | 84969007.38 | 0.156783E+09 | 0.455958E+09 | 46201226.58 |
July | 0.227617E+09 | 63068180.83 | 0.164548E+09 | 0.426351E+09 | 37753252.71 |
August | 0.230136E+09 | 70173695.79 | 0.159962E+09 | 0.432039E+09 | 49298037.28 |
September | 0.205325E+09 | 70495794.42 | 0.134829E+09 | 0.366192E+09 | 62108176.94 |
October | 0.216657E+09 | 93406824.73 | 0.123250E+09 | 0.373812E+09 | 96926901.20 |
November | 0.180008E+09 | 90429008.90 | 89578959.29 | 0.265384E+09 | 0.161863E+09 |
December | 0.178966E+09 | 95159512.64 | 83806726.57 | 0.252570E+09 | 0.193729E+09 |
Annual Sum or Average | 0.257713E+10 | 0.106256E+10 | 0.151457E+10 | 0.426412E+10 | 0.135115E+10 |
Minimum of Months | 0.178966E+09 | 63068180.83 | 83806726.57 | 0.252570E+09 | 37753252.71 |
Maximum of Months | 0.261006E+09 | 0.119869E+09 | 0.164548E+09 | 0.455958E+09 | 0.211292E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41523770.04 | 0.00 | 41523770.04 | 35163103.96 | 0.130479E+09 |
February | 44247244.57 | 0.00 | 44247244.57 | 41982071.83 | 97481246.43 |
March | 56842127.69 | 2657.73 | 56839469.96 | 62650915.80 | 97287267.14 |
April | 65080792.85 | 384956.40 | 64695836.45 | 86431319.61 | 70627417.89 |
May | 76109983.40 | 2865947.94 | 73244035.46 | 0.144854E+09 | 28820307.69 |
June | 83499391.23 | 5685212.29 | 77814178.95 | 0.165824E+09 | 25938348.91 |
July | 83793663.07 | 3127227.13 | 80666435.94 | 0.162746E+09 | 21656082.62 |
August | 75354197.92 | 775877.88 | 74578320.04 | 0.146411E+09 | 28038325.14 |
September | 62790968.62 | 12212.73 | 62778755.89 | 0.111576E+09 | 36232294.11 |
October | 56357047.91 | 0.00 | 56357047.91 | 92427792.72 | 57273471.44 |
November | 41403896.54 | 0.00 | 41403896.54 | 42833443.66 | 97753163.67 |
December | 38601065.29 | 0.00 | 38601065.29 | 33973933.11 | 0.119077E+09 |
Annual Sum or Average | 0.725604E+09 | 12854092.10 | 0.712750E+09 | 0.112687E+10 | 0.810665E+09 |
Minimum of Months | 38601065.29 | 0.00 | 38601065.29 | 33973933.11 | 21656082.62 |
Maximum of Months | 83793663.07 | 5685212.29 | 80666435.94 | 0.165824E+09 | 0.130479E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41522626.07 | 0.00 | 41522626.07 | 35161952.70 | 0.130479E+09 |
February | 44246067.70 | 0.00 | 44246067.70 | 41980866.70 | 97480549.72 |
March | 56840518.83 | 2657.60 | 56837861.22 | 62649062.34 | 97286728.72 |
April | 65079030.33 | 384938.36 | 64694091.98 | 86429093.18 | 70626752.45 |
May | 76107688.38 | 2865813.60 | 73241874.77 | 0.144850E+09 | 28819769.24 |
June | 83496833.73 | 5684945.81 | 77811887.91 | 0.165820E+09 | 25937803.98 |
July | 83791048.04 | 3127080.56 | 80663967.48 | 0.162742E+09 | 21655528.00 |
August | 75351899.12 | 775841.51 | 74576057.61 | 0.146408E+09 | 28037774.02 |
September | 62789054.11 | 12212.16 | 62776841.95 | 0.111573E+09 | 36231743.59 |
October | 56355422.90 | 0.00 | 56355422.90 | 92425524.84 | 57272862.61 |
November | 41402775.75 | 0.00 | 41402775.75 | 42832273.35 | 97752286.83 |
December | 38599992.55 | 0.00 | 38599992.55 | 33972873.70 | 0.119077E+09 |
Annual Sum or Average | 0.725583E+09 | 12853489.61 | 0.712729E+09 | 0.112685E+10 | 0.810657E+09 |
Minimum of Months | 38599992.55 | 0.00 | 38599992.55 | 33972873.70 | 21655528.00 |
Maximum of Months | 83791048.04 | 5684945.81 | 80663967.48 | 0.165820E+09 | 0.130479E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129922E+09 | 91999088.05 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.152186E+09 | 75233150.80 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188318E+09 | 75352669.08 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241333E+09 | 64645131.86 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259054E+09 | 35521158.59 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281214E+09 | 33562094.72 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269223E+09 | 29347618.25 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252373E+09 | 33830945.28 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201583E+09 | 39232781.57 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194901E+09 | 53540448.42 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135829E+09 | 81975806.33 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 87651214.80 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242293E+10 | 0.701892E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 29347618.25 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281214E+09 | 91999088.05 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129922E+09 | 91999088.05 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.152186E+09 | 75233150.80 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188318E+09 | 75352669.08 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241333E+09 | 64645131.86 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259054E+09 | 35521158.59 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281214E+09 | 33562094.72 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269223E+09 | 29347618.25 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252373E+09 | 33830945.28 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201583E+09 | 39232781.57 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194901E+09 | 53540448.42 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135829E+09 | 81975806.33 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 87651214.80 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242293E+10 | 0.701892E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 29347618.25 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281214E+09 | 91999088.05 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129922E+09 | 91999088.05 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.152186E+09 | 75233150.80 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188318E+09 | 75352669.08 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241333E+09 | 64645131.86 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259054E+09 | 35521158.59 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281214E+09 | 33562094.72 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269223E+09 | 29347618.25 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252373E+09 | 33830945.28 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201583E+09 | 39232781.57 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194901E+09 | 53540448.42 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135829E+09 | 81975806.33 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 87651214.80 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242293E+10 | 0.701892E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 29347618.25 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281214E+09 | 91999088.05 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129922E+09 | 91999088.05 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.152186E+09 | 75233150.80 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188318E+09 | 75352669.08 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241333E+09 | 64645131.86 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259054E+09 | 35521158.59 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281214E+09 | 33562094.72 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269223E+09 | 29347618.25 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252373E+09 | 33830945.28 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201583E+09 | 39232781.57 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194901E+09 | 53540448.42 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135829E+09 | 81975806.33 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 87651214.80 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242293E+10 | 0.701892E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 29347618.25 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281214E+09 | 91999088.05 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129922E+09 | 91999088.05 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.152186E+09 | 75233150.80 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188318E+09 | 75352669.08 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241333E+09 | 64645131.86 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259054E+09 | 35521158.59 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281214E+09 | 33562094.72 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269223E+09 | 29347618.25 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252373E+09 | 33830945.28 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201583E+09 | 39232781.57 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194901E+09 | 53540448.42 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135829E+09 | 81975806.33 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 87651214.80 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242293E+10 | 0.701892E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 29347618.25 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281214E+09 | 91999088.05 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129922E+09 | 91999088.05 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.152186E+09 | 75233150.80 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188318E+09 | 75352669.08 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241333E+09 | 64645131.86 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259054E+09 | 35521158.59 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281214E+09 | 33562094.72 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269223E+09 | 29347618.25 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252373E+09 | 33830945.28 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201583E+09 | 39232781.57 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194901E+09 | 53540448.42 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135829E+09 | 81975806.33 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 87651214.80 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242293E+10 | 0.701892E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 29347618.25 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281214E+09 | 91999088.05 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129922E+09 | 91999088.05 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.152186E+09 | 75233150.80 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188318E+09 | 75352669.08 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241333E+09 | 64645131.86 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259054E+09 | 35521158.59 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281214E+09 | 33562094.72 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269223E+09 | 29347618.25 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252373E+09 | 33830945.28 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201583E+09 | 39232781.57 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194901E+09 | 53540448.42 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135829E+09 | 81975806.33 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 87651214.80 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242293E+10 | 0.701892E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 29347618.25 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281214E+09 | 91999088.05 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129922E+09 | 91999088.05 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.152186E+09 | 75233150.80 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188318E+09 | 75352669.08 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241333E+09 | 64645131.86 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259054E+09 | 35521158.59 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281214E+09 | 33562094.72 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269223E+09 | 29347618.25 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252373E+09 | 33830945.28 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201583E+09 | 39232781.57 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194901E+09 | 53540448.42 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135829E+09 | 81975806.33 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 87651214.80 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242293E+10 | 0.701892E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 29347618.25 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281214E+09 | 91999088.05 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129922E+09 | 91999088.05 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.152186E+09 | 75233150.80 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188318E+09 | 75352669.08 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241333E+09 | 64645131.86 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259054E+09 | 35521158.59 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281214E+09 | 33562094.72 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269223E+09 | 29347618.25 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252373E+09 | 33830945.28 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201583E+09 | 39232781.57 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194901E+09 | 53540448.42 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135829E+09 | 81975806.33 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 87651214.80 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242293E+10 | 0.701892E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 29347618.25 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281214E+09 | 91999088.05 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129922E+09 | 91999088.05 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.152186E+09 | 75233150.80 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188318E+09 | 75352669.08 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241333E+09 | 64645131.86 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259054E+09 | 35521158.59 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281214E+09 | 33562094.72 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269223E+09 | 29347618.25 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252373E+09 | 33830945.28 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201583E+09 | 39232781.57 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194901E+09 | 53540448.42 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135829E+09 | 81975806.33 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 87651214.80 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242293E+10 | 0.701892E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 29347618.25 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281214E+09 | 91999088.05 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129922E+09 | 91999088.05 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.152186E+09 | 75233150.80 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188318E+09 | 75352669.08 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241333E+09 | 64645131.86 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259054E+09 | 35521158.59 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281214E+09 | 33562094.72 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269223E+09 | 29347618.25 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252373E+09 | 33830945.28 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201583E+09 | 39232781.57 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194901E+09 | 53540448.42 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135829E+09 | 81975806.33 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 87651214.80 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242293E+10 | 0.701892E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 29347618.25 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281214E+09 | 91999088.05 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129922E+09 | 91999088.05 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.152186E+09 | 75233150.80 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188318E+09 | 75352669.08 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241333E+09 | 64645131.86 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259054E+09 | 35521158.59 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281214E+09 | 33562094.72 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269223E+09 | 29347618.25 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252373E+09 | 33830945.28 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201583E+09 | 39232781.57 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194901E+09 | 53540448.42 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135829E+09 | 81975806.33 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 87651214.80 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242293E+10 | 0.701892E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 29347618.25 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281214E+09 | 91999088.05 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129922E+09 | 91999088.05 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.152186E+09 | 75233150.80 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188318E+09 | 75352669.08 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241333E+09 | 64645131.86 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259054E+09 | 35521158.59 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281214E+09 | 33562094.72 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269223E+09 | 29347618.25 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252373E+09 | 33830945.28 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201583E+09 | 39232781.57 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194901E+09 | 53540448.42 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135829E+09 | 81975806.33 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 87651214.80 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242293E+10 | 0.701892E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 29347618.25 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281214E+09 | 91999088.05 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129922E+09 | 91999088.05 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.152186E+09 | 75233150.80 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188318E+09 | 75352669.08 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241333E+09 | 64645131.86 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259054E+09 | 35521158.59 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281214E+09 | 33562094.72 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269223E+09 | 29347618.25 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252373E+09 | 33830945.28 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201583E+09 | 39232781.57 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194901E+09 | 53540448.42 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135829E+09 | 81975806.33 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 87651214.80 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242293E+10 | 0.701892E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116996E+09 | 29347618.25 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281214E+09 | 91999088.05 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266992E+09 | 0.108161E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306576E+09 | 86401984.66 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.372038E+09 | 91614865.28 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.460013E+09 | 86098324.42 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469239E+09 | 60285411.53 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507992E+09 | 57676956.86 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483296E+09 | 53459087.16 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454311E+09 | 58872445.92 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368601E+09 | 65347429.91 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362835E+09 | 80376609.34 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272468E+09 | 0.101309E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 0.104096E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456529E+10 | 0.953700E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240927E+09 | 53459087.16 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507992E+09 | 0.108161E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 222.13 | 250.54 | 176.33 | 78.49 | 97.84 | 0.00 | 0.00 |
February | 265.82 | 209.78 | 201.03 | 83.12 | 117.91 | 0.00 | 0.00 |
March | 279.87 | 191.38 | 204.82 | 71.85 | 132.97 | 0.00 | 0.00 |
April | 381.76 | 145.57 | 251.61 | 92.79 | 158.82 | 0.00 | 0.00 |
May | 418.16 | 59.29 | 224.60 | 56.74 | 167.86 | 0.00 | 0.00 |
June | 479.30 | 55.20 | 250.96 | 69.95 | 181.02 | 0.00 | 0.00 |
July | 439.60 | 44.07 | 232.53 | 49.43 | 183.10 | 0.00 | 0.00 |
August | 431.79 | 57.60 | 228.11 | 52.98 | 175.13 | 0.00 | 0.00 |
September | 368.43 | 75.66 | 206.88 | 54.40 | 152.47 | 0.00 | 0.00 |
October | 347.55 | 114.54 | 203.86 | 69.75 | 134.11 | 0.00 | 0.00 |
November | 235.56 | 198.06 | 170.84 | 69.78 | 101.07 | 0.00 | 0.00 |
December | 210.50 | 230.11 | 162.46 | 71.06 | 91.40 | 0.00 | 0.00 |
Annual Sum or Average | 340.36 | 135.57 | 209.46 | 68.20 | 141.26 | 0.00 | 0.00 |
Minimum of Months | 210.50 | 44.07 | 162.46 | 49.43 | 91.40 | 0.00 | 0.00 |
Maximum of Months | 479.30 | 250.54 | 251.61 | 92.79 | 183.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 679.10 | 480.88 | 490.24 | 327.00 | 163.24 | 0.00 | 0.00 |
February | 880.71 | 435.38 | 626.60 | 430.40 | 196.20 | 0.00 | 0.00 |
March | 984.34 | 393.87 | 692.24 | 433.37 | 258.88 | 0.00 | 0.00 |
April | 1303.50 | 349.16 | 883.14 | 578.08 | 305.07 | 0.00 | 0.00 |
May | 1354.08 | 185.67 | 846.47 | 487.92 | 358.55 | 0.00 | 0.00 |
June | 1518.90 | 181.28 | 935.25 | 545.28 | 389.97 | 0.00 | 0.00 |
July | 1407.23 | 153.40 | 870.09 | 452.80 | 417.29 | 0.00 | 0.00 |
August | 1319.15 | 176.83 | 811.94 | 411.49 | 400.45 | 0.00 | 0.00 |
September | 1088.80 | 211.91 | 691.20 | 347.45 | 343.75 | 0.00 | 0.00 |
October | 1018.75 | 279.86 | 654.60 | 390.23 | 264.37 | 0.00 | 0.00 |
November | 733.64 | 442.77 | 526.21 | 358.75 | 167.47 | 0.00 | 0.00 |
December | 611.54 | 458.15 | 443.71 | 291.38 | 152.33 | 0.00 | 0.00 |
Annual Sum or Average | 1075.63 | 311.60 | 706.05 | 420.70 | 285.34 | 0.00 | 0.00 |
Minimum of Months | 611.54 | 153.40 | 443.71 | 291.38 | 152.33 | 0.00 | 0.00 |
Maximum of Months | 1518.90 | 480.88 | 935.25 | 578.08 | 417.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 13288.37 | 4439.12 | 2398.89 | 1608.57 | 790.32 | 0.00 | 0.00 |
February | 16149.28 | 3707.97 | 3026.68 | 2076.81 | 949.88 | 0.00 | 0.00 |
March | 18242.14 | 3472.68 | 3322.57 | 2069.27 | 1253.31 | 0.00 | 0.00 |
April | 23633.14 | 3435.96 | 4217.31 | 2740.38 | 1476.93 | 0.00 | 0.00 |
May | 30649.02 | 2975.23 | 4042.81 | 2306.97 | 1735.84 | 0.00 | 0.00 |
June | 34665.17 | 3352.64 | 4461.72 | 2573.77 | 1887.96 | 0.00 | 0.00 |
July | 34909.33 | 3268.87 | 4156.52 | 2136.26 | 2020.26 | 0.00 | 0.00 |
August | 31958.47 | 3441.05 | 3884.23 | 1945.50 | 1938.73 | 0.00 | 0.00 |
September | 27595.73 | 3291.15 | 3314.85 | 1650.64 | 1664.21 | 0.00 | 0.00 |
October | 22427.96 | 3586.31 | 3150.42 | 1870.51 | 1279.91 | 0.00 | 0.00 |
November | 13584.92 | 3983.10 | 2559.64 | 1748.88 | 810.76 | 0.00 | 0.00 |
December | 11310.15 | 4160.62 | 2177.82 | 1440.33 | 737.48 | 0.00 | 0.00 |
Annual Sum or Average | 23240.82 | 3592.79 | 3393.11 | 2011.67 | 1381.43 | 0.00 | 0.00 |
Minimum of Months | 11310.15 | 2975.23 | 2177.82 | 1440.33 | 737.48 | 0.00 | 0.00 |
Maximum of Months | 34909.33 | 4439.12 | 4461.72 | 2740.38 | 2020.26 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.594950E+09 | 0.671052E+09 | 0.472269E+09 | 0.210221E+09 | 0.262049E+09 | 0.00 | 0.00 |
February | 0.643079E+09 | 0.507510E+09 | 0.486329E+09 | 0.201080E+09 | 0.285249E+09 | 0.00 | 0.00 |
March | 0.749604E+09 | 0.512588E+09 | 0.548597E+09 | 0.192442E+09 | 0.356155E+09 | 0.00 | 0.00 |
April | 0.989531E+09 | 0.377329E+09 | 0.652171E+09 | 0.240508E+09 | 0.411662E+09 | 0.00 | 0.00 |
May | 0.111999E+10 | 0.158812E+09 | 0.601571E+09 | 0.151972E+09 | 0.449600E+09 | 0.00 | 0.00 |
June | 0.124235E+10 | 0.143071E+09 | 0.650501E+09 | 0.181308E+09 | 0.469192E+09 | 0.00 | 0.00 |
July | 0.117742E+10 | 0.118045E+09 | 0.622818E+09 | 0.132391E+09 | 0.490427E+09 | 0.00 | 0.00 |
August | 0.115650E+10 | 0.154276E+09 | 0.610978E+09 | 0.141899E+09 | 0.469079E+09 | 0.00 | 0.00 |
September | 0.954974E+09 | 0.196122E+09 | 0.536231E+09 | 0.141016E+09 | 0.395214E+09 | 0.00 | 0.00 |
October | 0.930867E+09 | 0.306788E+09 | 0.546027E+09 | 0.186814E+09 | 0.359213E+09 | 0.00 | 0.00 |
November | 0.610573E+09 | 0.513372E+09 | 0.442823E+09 | 0.180858E+09 | 0.261965E+09 | 0.00 | 0.00 |
December | 0.563808E+09 | 0.616333E+09 | 0.435134E+09 | 0.190319E+09 | 0.244815E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107337E+11 | 0.427530E+10 | 0.660545E+10 | 0.215083E+10 | 0.445462E+10 | 0.00 | 0.00 |
Minimum of Months | 0.563808E+09 | 0.118045E+09 | 0.435134E+09 | 0.132391E+09 | 0.244815E+09 | 0.00 | 0.00 |
Maximum of Months | 0.124235E+10 | 0.671052E+09 | 0.652171E+09 | 0.240508E+09 | 0.490427E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.181891E+10 | 0.128799E+10 | 0.131306E+10 | 0.875824E+09 | 0.437233E+09 | 0.00 | 0.00 |
February | 0.213060E+10 | 0.105326E+10 | 0.151587E+10 | 0.104122E+10 | 0.474649E+09 | 0.00 | 0.00 |
March | 0.263646E+10 | 0.105494E+10 | 0.185410E+10 | 0.116073E+10 | 0.693372E+09 | 0.00 | 0.00 |
April | 0.337866E+10 | 0.905032E+09 | 0.228911E+10 | 0.149837E+10 | 0.790731E+09 | 0.00 | 0.00 |
May | 0.362676E+10 | 0.497296E+09 | 0.226717E+10 | 0.130685E+10 | 0.960327E+09 | 0.00 | 0.00 |
June | 0.393699E+10 | 0.469869E+09 | 0.242416E+10 | 0.141337E+10 | 0.101079E+10 | 0.00 | 0.00 |
July | 0.376912E+10 | 0.410867E+09 | 0.233045E+10 | 0.121277E+10 | 0.111768E+10 | 0.00 | 0.00 |
August | 0.353322E+10 | 0.473633E+09 | 0.217470E+10 | 0.110213E+10 | 0.107257E+10 | 0.00 | 0.00 |
September | 0.282217E+10 | 0.549259E+09 | 0.179158E+10 | 0.900580E+09 | 0.890999E+09 | 0.00 | 0.00 |
October | 0.272861E+10 | 0.749566E+09 | 0.175329E+10 | 0.104520E+10 | 0.708090E+09 | 0.00 | 0.00 |
November | 0.190160E+10 | 0.114766E+10 | 0.136395E+10 | 0.929875E+09 | 0.434070E+09 | 0.00 | 0.00 |
December | 0.163795E+10 | 0.122712E+10 | 0.118843E+10 | 0.780427E+09 | 0.408002E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.339211E+11 | 0.982649E+10 | 0.222658E+11 | 0.132673E+11 | 0.899851E+10 | 0.00 | 0.00 |
Minimum of Months | 0.163795E+10 | 0.410867E+09 | 0.118843E+10 | 0.780427E+09 | 0.408002E+09 | 0.00 | 0.00 |
Maximum of Months | 0.393699E+10 | 0.128799E+10 | 0.242416E+10 | 0.149837E+10 | 0.111768E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.355916E+11 | 0.118897E+11 | 0.642520E+10 | 0.430840E+10 | 0.211680E+10 | 0.00 | 0.00 |
February | 0.390683E+11 | 0.897032E+10 | 0.732215E+10 | 0.502421E+10 | 0.229794E+10 | 0.00 | 0.00 |
March | 0.488597E+11 | 0.930123E+10 | 0.889918E+10 | 0.554233E+10 | 0.335685E+10 | 0.00 | 0.00 |
April | 0.612571E+11 | 0.890602E+10 | 0.109313E+11 | 0.710307E+10 | 0.382820E+10 | 0.00 | 0.00 |
May | 0.820903E+11 | 0.796887E+10 | 0.108283E+11 | 0.617899E+10 | 0.464928E+10 | 0.00 | 0.00 |
June | 0.898521E+11 | 0.869003E+10 | 0.115648E+11 | 0.667121E+10 | 0.489358E+10 | 0.00 | 0.00 |
July | 0.935011E+11 | 0.875535E+10 | 0.111328E+11 | 0.572176E+10 | 0.541106E+10 | 0.00 | 0.00 |
August | 0.855976E+11 | 0.921650E+10 | 0.104035E+11 | 0.521083E+10 | 0.519268E+10 | 0.00 | 0.00 |
September | 0.715281E+11 | 0.853066E+10 | 0.859210E+10 | 0.427846E+10 | 0.431363E+10 | 0.00 | 0.00 |
October | 0.600711E+11 | 0.960558E+10 | 0.843808E+10 | 0.500997E+10 | 0.342811E+10 | 0.00 | 0.00 |
November | 0.352121E+11 | 0.103242E+11 | 0.663458E+10 | 0.453310E+10 | 0.210149E+10 | 0.00 | 0.00 |
December | 0.302931E+11 | 0.111438E+11 | 0.583307E+10 | 0.385779E+10 | 0.197528E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.732922E+12 | 0.113302E+12 | 0.107005E+12 | 0.634401E+11 | 0.435649E+11 | 0.00 | 0.00 |
Minimum of Months | 0.302931E+11 | 0.796887E+10 | 0.583307E+10 | 0.385779E+10 | 0.197528E+10 | 0.00 | 0.00 |
Maximum of Months | 0.935011E+11 | 0.118897E+11 | 0.115648E+11 | 0.710307E+10 | 0.541106E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.02 | 8.64 | 3.24 | 3.13 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.58 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.54 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.82 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.37 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.90 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.02 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.47 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.88 | 10.53 | 3.17 | 6.01 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.02 | 8.64 | 2.44 | 3.13 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.67 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.78 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.88 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.06 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.76 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.95 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.96 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.74 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.65 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.05 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.84 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.67 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.65 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.4 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -2.1 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.95 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.58 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 18.00 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.56 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.12 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.9 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.4 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.11 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.49 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.77 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.55 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.84 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.17 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.79 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.49 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.11 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.55 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.09 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.79 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.768087E+09 | -688260944.3 | 0.00 | 0.00 | 744.00 | 0.00 | -79826090.8 | 58.99 | 0.00 | 0.00 |
February | 0.698443E+09 | -627185648.8 | 0.00 | 0.00 | 672.00 | 0.00 | -71256905.7 | 58.99 | 0.00 | 0.00 |
March | 0.782000E+09 | -704950827.7 | 0.00 | 0.00 | 744.00 | 0.00 | -77049361.4 | 58.99 | 0.00 | 0.00 |
April | 0.685386E+09 | -614742839.3 | 0.00 | 0.00 | 720.00 | 0.00 | -70643191.5 | 58.99 | 0.00 | 0.00 |
May | 0.665005E+09 | -594412350.4 | 0.00 | 0.00 | 744.00 | 0.00 | -70593089.8 | 58.99 | 0.00 | 0.00 |
June | 0.623496E+09 | -555367767.9 | 0.00 | 0.00 | 720.00 | 0.00 | -68127898.7 | 58.98 | 0.00 | 0.00 |
July | 0.589300E+09 | -519488826.3 | 0.00 | 0.00 | 744.00 | 0.00 | -69811288.0 | 58.99 | 0.00 | 0.00 |
August | 0.634251E+09 | -564070890.0 | 0.00 | 0.00 | 744.00 | 0.00 | -70180585.2 | 58.99 | 0.00 | 0.00 |
September | 0.619586E+09 | -551590743.7 | 0.00 | 0.00 | 720.00 | 0.00 | -67995229.9 | 58.99 | 0.00 | 0.00 |
October | 0.664431E+09 | -593426796.6 | 0.00 | 0.00 | 744.00 | 0.00 | -71003956.7 | 58.99 | 0.00 | 0.00 |
November | 0.683413E+09 | -611318800.4 | 0.00 | 0.00 | 720.00 | 0.00 | -72094053.0 | 58.99 | 0.00 | 0.00 |
December | 0.748750E+09 | -671012981.7 | 0.00 | 0.00 | 744.00 | 0.00 | -77736912.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.816215E+10 | -0.729583E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -866318563.0 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.589300E+09 | -704950827.7 | 0.00 | 0.00 | 672.00 | 0.00 | -79826090.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.782000E+09 | -519488826.3 | 0.00 | 0.00 | 744.00 | 0.00 | -67995229.9 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.80 | 0.50 | 02-JAN-11:20 | 137.56 | 0.00 | 0.00 | 10.50 | 641.25 | 0.00 | 0.00 | 19.00 |
February | 295.50 | 0.75 | 0.50 | 01-FEB-11:00 | 1397.68 | 0.00 | 0.00 | 47.67 | 618.47 | 0.00 | 0.00 | 20.83 |
March | 296.00 | 0.73 | 0.50 | 02-MAR-12:50 | 198.49 | 0.00 | 0.00 | 58.67 | 163.22 | 0.00 | 0.00 | 29.00 |
April | 347.33 | 0.70 | 0.50 | 01-APR-09:50 | 229.24 | 0.00 | 0.00 | 94.50 | 1127.87 | 0.00 | 0.00 | 86.33 |
May | 353.67 | 0.68 | 0.50 | 01-MAY-09:20 | 1047.56 | 0.00 | 0.00 | 168.50 | 193.02 | 0.00 | 0.00 | 61.17 |
June | 394.00 | 0.68 | 0.50 | 01-JUN-10:20 | 695.53 | 0.00 | 0.00 | 169.50 | 194.26 | 0.00 | 0.00 | 67.50 |
July | 390.00 | 0.67 | 0.50 | 01-JUL-09:00 | 1458.95 | 0.00 | 0.00 | 181.00 | 216.42 | 0.00 | 0.00 | 94.17 |
August | 380.83 | 0.66 | 0.50 | 01-AUG-10:09 | 626.47 | 0.00 | 0.00 | 174.83 | 1295.26 | 0.00 | 0.00 | 135.00 |
September | 342.17 | 0.68 | 0.50 | 01-SEP-10:39 | 263.00 | 0.00 | 0.00 | 129.33 | 210.87 | 0.00 | 0.00 | 83.83 |
October | 330.00 | 0.70 | 0.50 | 04-OCT-10:00 | 219.22 | 0.00 | 0.00 | 75.17 | 179.40 | 0.00 | 0.00 | 42.17 |
November | 308.00 | 0.79 | 0.50 | 01-NOV-11:39 | 144.62 | 0.00 | 0.00 | 9.33 | 122.68 | 0.00 | 0.00 | 3.33 |
December | 282.83 | 0.80 | 0.50 | 03-DEC-12:09 | 135.43 | 0.00 | 0.00 | 4.33 | 114.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4027.67 | 0.72 | 568.80 | 0.00 | 0.00 | 1123.33 | 433.01 | 0.00 | 0.00 | 642.33 | ||
Minimum of Months | 282.83 | 0.66 | 0.50 | 135.43 | 0.00 | 0.00 | 4.33 | 114.97 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 394.00 | 0.80 | 0.50 | 1458.95 | 0.00 | 0.00 | 181.00 | 1295.26 | 0.00 | 0.00 | 135.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.68 | 0.50 | 01-JAN-09:50 | 164.96 | 10.89 | 0.00 | 89.33 | 137.75 | 14.54 | 11.50 | 58.00 |
February | 295.50 | 0.63 | 0.50 | 01-FEB-11:39 | 654.58 | 11.61 | 0.00 | 159.33 | 161.93 | 15.36 | 23.83 | 88.17 |
March | 296.00 | 0.62 | 0.50 | 02-MAR-12:39 | 234.13 | 12.68 | 0.00 | 191.00 | 198.28 | 16.58 | 55.50 | 137.17 |
April | 347.33 | 0.61 | 0.50 | 01-APR-08:09 | 264.90 | 12.55 | 0.00 | 231.17 | 222.96 | 16.24 | 61.50 | 179.17 |
May | 353.67 | 0.59 | 0.50 | 01-MAY-07:49 | 294.44 | 13.62 | 0.00 | 265.17 | 250.29 | 17.31 | 76.17 | 221.50 |
June | 394.00 | 0.59 | 0.50 | 01-JUN-07:19 | 306.40 | 13.58 | 0.00 | 271.00 | 265.68 | 17.16 | 91.83 | 224.83 |
July | 390.00 | 0.57 | 0.50 | 01-JUL-07:10 | 333.50 | 14.13 | 0.00 | 285.67 | 288.74 | 17.62 | 94.50 | 239.83 |
August | 380.83 | 0.58 | 0.50 | 01-AUG-07:30 | 504.88 | 13.96 | 0.00 | 272.50 | 288.89 | 17.45 | 93.83 | 231.83 |
September | 342.17 | 0.59 | 0.50 | 01-SEP-07:00 | 958.37 | 13.62 | 0.00 | 236.17 | 258.05 | 17.12 | 79.17 | 190.67 |
October | 330.00 | 0.60 | 0.50 | 01-OCT-08:30 | 385.95 | 13.62 | 7.33 | 206.00 | 378.87 | 16.87 | 63.67 | 156.83 |
November | 308.00 | 0.66 | 0.50 | 01-NOV-09:50 | 951.79 | 13.14 | 29.17 | 113.50 | 1029.63 | 14.94 | 11.00 | 73.50 |
December | 282.83 | 0.67 | 0.50 | 02-DEC-09:00 | 162.53 | 10.91 | 0.00 | 74.00 | 135.19 | 14.47 | 0.00 | 43.67 |
Annual Sum or Average | 4027.67 | 0.61 | 433.76 | 12.95 | 36.50 | 2394.83 | 300.63 | 16.41 | 662.50 | 1845.17 | ||
Minimum of Months | 282.83 | 0.57 | 0.50 | 162.53 | 10.89 | 0.00 | 74.00 | 135.19 | 14.47 | 0.00 | 43.67 | |
Maximum of Months | 394.00 | 0.68 | 0.50 | 958.37 | 14.13 | 29.17 | 285.67 | 1029.63 | 17.62 | 94.50 | 239.83 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.83 | 0.61 | 30-JAN-16:30 | 303.74 | 22.72 | 117.67 | 37.83 | 100.83 | 19.72 | 85.50 | 0.00 |
February | 295.50 | 0.80 | 0.61 | 08-FEB-16:30 | 416.59 | 23.71 | 134.00 | 53.50 | 145.89 | 22.01 | 127.17 | 11.50 |
March | 296.00 | 0.79 | 0.61 | 02-MAR-15:30 | 238.58 | 21.81 | 121.83 | 42.00 | 178.57 | 22.90 | 138.17 | 23.50 |
April | 347.33 | 0.78 | 0.61 | 01-APR-16:10 | 223.61 | 19.97 | 123.67 | 40.50 | 221.53 | 21.82 | 160.33 | 44.33 |
May | 353.67 | 0.78 | 0.61 | 01-MAY-15:20 | 234.11 | 20.16 | 114.50 | 36.83 | 195.90 | 21.40 | 162.50 | 34.33 |
June | 394.00 | 0.77 | 0.61 | 01-JUN-15:09 | 241.50 | 19.85 | 121.50 | 42.00 | 206.65 | 21.13 | 175.83 | 39.17 |
July | 390.00 | 0.77 | 0.61 | 01-JUL-14:00 | 248.00 | 20.12 | 126.83 | 49.50 | 185.48 | 21.30 | 182.50 | 33.00 |
August | 380.83 | 0.77 | 0.61 | 01-AUG-15:09 | 243.32 | 20.31 | 143.67 | 50.83 | 190.33 | 21.39 | 187.17 | 37.17 |
September | 342.17 | 0.78 | 0.61 | 01-SEP-14:00 | 271.53 | 21.26 | 146.33 | 48.33 | 208.46 | 22.42 | 178.50 | 34.50 |
October | 330.00 | 0.78 | 0.61 | 01-OCT-15:30 | 312.06 | 23.40 | 164.33 | 59.50 | 224.67 | 23.61 | 168.83 | 27.00 |
November | 308.00 | 0.83 | 0.63 | 02-NOV-16:19 | 228.17 | 21.93 | 119.17 | 30.50 | 104.69 | 19.91 | 92.67 | 0.00 |
December | 282.83 | 0.82 | 0.65 | 03-DEC-15:30 | 243.59 | 22.95 | 119.17 | 27.50 | 101.68 | 19.91 | 83.00 | 0.00 |
Annual Sum or Average | 4027.67 | 0.79 | 264.95 | 21.39 | 1552.67 | 518.83 | 175.26 | 21.48 | 1742.17 | 284.50 | ||
Minimum of Months | 282.83 | 0.77 | 0.61 | 223.61 | 19.85 | 114.50 | 27.50 | 100.83 | 19.72 | 83.00 | 0.00 | |
Maximum of Months | 394.00 | 0.83 | 0.65 | 416.59 | 23.71 | 164.33 | 59.50 | 224.67 | 23.61 | 187.17 | 44.33 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.825264E+09 | 26263.03 | 05-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.471512E+09 | 26263.03 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.335219E+09 | 26263.03 | 10-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1905422.85 | 1778.12 | 11-APR-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 23196400.57 | 3232.23 | 15-NOV-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.465611E+09 | 26263.03 | 20-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.825264E+09 | 26263.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 4285874.02 | 3113.63 | 10-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6646240.66 | 14259.17 | 05-FEB-07:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 10932114.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6646240.66 | 14259.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.863383E+09 | 0.554217E+09 | 22533.06 | 02-JAN-06:02 | 12288.78 | 0.00 |
February | 0.00 | 0.00 | 0.153723E+10 | 0.100872E+10 | 22307.27 | 28-FEB-06:03 | 10918.61 | 0.00 |
March | 0.00 | 0.00 | 0.258121E+10 | 0.175956E+10 | 25585.67 | 07-MAR-06:03 | 10973.12 | 0.00 |
April | 0.00 | 0.00 | 0.582647E+10 | 0.418306E+10 | 26755.26 | 29-APR-05:01 | 12407.74 | 0.00 |
May | 0.00 | 0.00 | 0.123911E+11 | 0.836651E+10 | 28236.28 | 23-MAY-05:01 | 10757.12 | 0.00 |
June | 0.00 | 0.00 | 0.133349E+11 | 0.903497E+10 | 27834.63 | 30-JUN-05:01 | 14613.80 | 0.00 |
July | 0.00 | 0.00 | 0.138563E+11 | 0.891269E+10 | 28187.58 | 31-JUL-05:01 | 11419.73 | 0.00 |
August | 0.00 | 0.00 | 0.149399E+11 | 0.970522E+10 | 28335.88 | 11-AUG-05:01 | 10899.08 | 0.00 |
September | 0.00 | 0.00 | 0.125826E+11 | 0.804667E+10 | 28049.73 | 11-SEP-05:01 | 15549.49 | 0.00 |
October | 0.00 | 0.00 | 0.102005E+11 | 0.686349E+10 | 28271.37 | 23-OCT-05:01 | 10859.25 | 0.00 |
November | 0.00 | 0.00 | 0.406057E+10 | 0.278570E+10 | 27068.33 | 02-NOV-05:01 | 14768.34 | 0.00 |
December | 0.00 | 0.00 | 0.243495E+10 | 0.160598E+10 | 26156.59 | 15-DEC-06:02 | 10775.38 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.946092E+11 | 0.628268E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.863383E+09 | 0.554217E+09 | 22307.27 | 10757.12 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.149399E+11 | 0.970522E+10 | 28335.88 | 15549.49 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.137986E+09 | 0.103919E+09 | 67432.67 | 01-JAN-12:35 | 46999.24 | 0.00 |
February | 0.00 | 0.00 | 0.298857E+09 | 0.183026E+09 | 11702.75 | 27-FEB-15:00 | 7418.40 | 0.00 |
March | 0.00 | 0.00 | 0.824297E+09 | 0.467990E+09 | 19845.21 | 26-MAR-14:05 | 13888.23 | 0.00 |
April | 0.00 | 0.00 | 0.751648E+10 | 0.512464E+10 | 75491.29 | 30-APR-14:25 | 36195.92 | 0.00 |
May | 0.00 | 0.00 | 0.273132E+11 | 0.178841E+11 | 77744.21 | 21-MAY-08:65 | 34277.65 | 0.00 |
June | 0.00 | 0.00 | 0.325864E+11 | 0.217358E+11 | 70360.58 | 19-JUN-17:10 | 48129.87 | 0.00 |
July | 0.00 | 0.00 | 0.362470E+11 | 0.227884E+11 | 74763.12 | 26-JUL-05:01 | 42077.14 | 0.00 |
August | 0.00 | 0.00 | 0.357955E+11 | 0.224955E+11 | 73715.63 | 12-AUG-17:10 | 44976.88 | 0.00 |
September | 0.00 | 0.00 | 0.267131E+11 | 0.161521E+11 | 75508.99 | 02-SEP-21:45 | 35084.27 | 0.00 |
October | 0.00 | 0.00 | 0.212046E+11 | 0.132291E+11 | 78947.99 | 08-OCT-07:45 | 31356.01 | 0.00 |
November | 0.00 | 0.00 | 0.329097E+10 | 0.195149E+10 | 37889.92 | 05-NOV-14:05 | 29000.26 | 0.00 |
December | 0.00 | 0.00 | 0.125141E+10 | 0.722332E+09 | 19059.92 | 15-DEC-14:10 | 11848.73 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.193180E+12 | 0.122838E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.137986E+09 | 0.103919E+09 | 11702.75 | 7418.40 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.362470E+11 | 0.227884E+11 | 78947.99 | 48129.87 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.488935E+09 | 0.22 | 1168.84 | 02-JAN-06:02 | 0.90 |
February | 0.441033E+09 | 0.22 | 1168.84 | 06-FEB-06:01 | 0.91 |
March | 0.510985E+09 | 0.23 | 1168.84 | 10-MAR-06:02 | 0.91 |
April | 0.474005E+09 | 0.22 | 1168.84 | 07-APR-05:03 | 0.89 |
May | 0.553109E+09 | 0.24 | 1168.84 | 01-MAY-05:01 | 0.89 |
June | 0.587697E+09 | 0.26 | 1168.84 | 01-JUN-05:01 | 0.89 |
July | 0.607040E+09 | 0.25 | 1168.84 | 01-JUL-05:01 | 0.89 |
August | 0.652465E+09 | 0.26 | 1168.84 | 01-AUG-05:01 | 0.89 |
September | 0.550950E+09 | 0.24 | 1168.84 | 01-SEP-05:01 | 0.89 |
October | 0.534722E+09 | 0.23 | 1168.84 | 02-OCT-05:01 | 0.90 |
November | 0.451633E+09 | 0.20 | 1168.84 | 01-NOV-05:02 | 0.89 |
December | 0.479410E+09 | 0.21 | 1168.84 | 14-DEC-06:03 | 0.89 |
Annual Sum or Average | 0.633198E+10 | 0.23 | |||
Minimum of Months | 0.441033E+09 | 0.20 | 1168.84 | 0.89 | |
Maximum of Months | 0.652465E+09 | 0.26 | 1168.84 | 0.91 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.105178E+10 | 0.20 | 1123.06 | 10-JAN-07:10 | 0.55 |
February | 0.965891E+09 | 0.20 | 1060.24 | 24-FEB-13:20 | 0.52 |
March | 0.113390E+10 | 0.21 | 1060.24 | 06-MAR-14:10 | 0.52 |
April | 0.108381E+10 | 0.22 | 2650.60 | 23-APR-14:03 | 0.87 |
May | 0.129110E+10 | 0.29 | 2650.60 | 02-MAY-17:08 | 0.87 |
June | 0.135326E+10 | 0.32 | 2650.60 | 04-JUN-10:23 | 0.87 |
July | 0.144208E+10 | 0.35 | 2650.60 | 02-JUL-16:33 | 0.87 |
August | 0.145187E+10 | 0.34 | 2650.60 | 01-AUG-17:06 | 0.87 |
September | 0.128295E+10 | 0.29 | 2650.60 | 02-SEP-17:10 | 0.87 |
October | 0.121851E+10 | 0.26 | 2650.60 | 01-OCT-13:43 | 0.87 |
November | 0.101718E+10 | 0.20 | 1285.80 | 05-NOV-14:05 | 0.60 |
December | 0.104964E+10 | 0.20 | 1060.24 | 02-DEC-15:00 | 0.53 |
Annual Sum or Average | 0.143420E+11 | 0.26 | |||
Minimum of Months | 0.965891E+09 | 0.20 | 1060.24 | 0.52 | |
Maximum of Months | 0.145187E+10 | 0.35 | 2650.60 | 0.87 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.678272E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.778077E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.107626E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.175410E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.326307E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.353066E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.364442E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.390662E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.322910E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.273611E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.133069E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.100716E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.269345E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.678272E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.390662E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.108319E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.103600E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.132648E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.281004E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.754792E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.880901E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.966084E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.952919E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.725984E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.596767E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.176096E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.133789E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.581290E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.103600E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.966084E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.488935E+09 | 0.863383E+09 | 0.825264E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.441033E+09 | 0.153723E+10 | 0.471512E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.510985E+09 | 0.257623E+10 | 0.335219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.474005E+09 | 0.581459E+10 | 1905422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.553109E+09 | 0.123885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.587697E+09 | 0.133305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.607040E+09 | 0.138563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.652465E+09 | 0.149372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.550950E+09 | 0.125826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.534722E+09 | 0.101858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.451633E+09 | 0.405238E+10 | 23196400.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.479410E+09 | 0.243136E+10 | 0.465611E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.633198E+10 | 0.945561E+11 | 0.212271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.441033E+09 | 0.863383E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.652465E+09 | 0.149372E+11 | 0.825264E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.105178E+10 | 0.126631E+09 | 4285874.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.965891E+09 | 0.298857E+09 | 6646240.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113390E+10 | 0.824297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108381E+10 | 0.747479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129110E+10 | 0.273052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135326E+10 | 0.325864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144208E+10 | 0.362470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145187E+10 | 0.357883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128295E+10 | 0.266979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121851E+10 | 0.211108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101718E+10 | 0.329097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104964E+10 | 0.125141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143420E+11 | 0.193003E+12 | 10932114.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.965891E+09 | 0.126631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145187E+10 | 0.362470E+11 | 6646240.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.488935E+09 | 0.00 | 0.00 | 0.00 | 0.189337E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.441033E+09 | 0.00 | 0.00 | 0.00 | 0.337043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.510985E+09 | 0.00 | 0.00 | 0.00 | 0.565278E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.474005E+09 | 0.00 | 0.00 | 0.00 | 0.128009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.553109E+09 | 0.00 | 0.00 | 0.00 | 0.270996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.587697E+09 | 0.00 | 0.00 | 0.00 | 0.294296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.607040E+09 | 0.00 | 0.00 | 0.00 | 0.303738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.652465E+09 | 0.00 | 0.00 | 0.00 | 0.325415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.550950E+09 | 0.00 | 0.00 | 0.00 | 0.267815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.534722E+09 | 0.00 | 0.00 | 0.00 | 0.220138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.451633E+09 | 0.00 | 0.00 | 0.00 | 0.879057E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.479410E+09 | 0.00 | 0.00 | 0.00 | 0.527748E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.633198E+10 | 0.00 | 0.00 | 0.00 | 0.206025E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.441033E+09 | 0.00 | 0.00 | 0.00 | 0.189337E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.652465E+09 | 0.00 | 0.00 | 0.00 | 0.325415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.105178E+10 | 0.00 | 0.00 | 0.00 | 31402064.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.965891E+09 | 0.00 | 0.00 | 0.00 | 70108265.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113390E+10 | 0.00 | 0.00 | 0.00 | 0.192580E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108381E+10 | 0.00 | 0.00 | 0.00 | 0.172623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129110E+10 | 0.00 | 0.00 | 0.00 | 0.625683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135326E+10 | 0.00 | 0.00 | 0.00 | 0.745575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144208E+10 | 0.00 | 0.00 | 0.00 | 0.821876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145187E+10 | 0.00 | 0.00 | 0.00 | 0.807733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128295E+10 | 0.00 | 0.00 | 0.00 | 0.597689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121851E+10 | 0.00 | 0.00 | 0.00 | 0.474916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101718E+10 | 0.00 | 0.00 | 0.00 | 0.743774E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104964E+10 | 0.00 | 0.00 | 0.00 | 0.288255E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143420E+11 | 0.00 | 0.00 | 0.00 | 0.437871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.965891E+09 | 0.00 | 0.00 | 0.00 | 31402064.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145187E+10 | 0.00 | 0.00 | 0.00 | 0.821876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.617287E+09 | 78088946.43 | 0.00 | 436417.68 | 0.00 | 0.158328E+09 | 0.356294E+09 | 0.00 | 0.17 |
February | 0.372260E+09 | 0.142700E+09 | 0.00 | 665237.42 | 0.00 | 96317814.87 | 0.429684E+09 | 0.00 | 0.22 |
March | 0.363244E+09 | 0.286313E+09 | 0.00 | 1145553.07 | 0.00 | 34566318.99 | 0.674584E+09 | 0.00 | 0.27 |
April | 16446964.83 | 0.647793E+09 | 0.00 | 2375323.23 | 0.00 | 0.00 | 0.682086E+09 | 0.00 | 0.30 |
May | 0.00 | 0.202132E+10 | 0.00 | 893931.93 | 0.00 | 0.00 | 969434.22 | 0.00 | 0.13 |
June | 0.00 | 0.232225E+10 | 0.00 | 954077.14 | 0.00 | 0.00 | 2452816.19 | 0.00 | 0.14 |
July | 0.00 | 0.260847E+10 | 0.00 | 1170270.20 | 0.00 | 0.00 | 1577182.27 | 0.00 | 0.13 |
August | 0.00 | 0.259527E+10 | 0.00 | 1715465.78 | 0.00 | 0.00 | 1098233.60 | 0.00 | 0.14 |
September | 0.00 | 0.211933E+10 | 0.00 | 2839604.20 | 0.00 | 0.00 | 2559783.69 | 0.00 | 0.13 |
October | 1110499.62 | 0.159275E+10 | 0.00 | 3719161.98 | 0.00 | 0.00 | 0.507127E+09 | 0.00 | 0.22 |
November | 79913606.30 | 0.479813E+09 | 0.00 | 2234812.76 | 0.00 | 953994.97 | 0.915601E+09 | 0.00 | 0.32 |
December | 0.479064E+09 | 0.317043E+09 | 0.00 | 840756.31 | 0.00 | 99320560.43 | 0.442931E+09 | 0.00 | 0.21 |
Annual Sum or Average | 0.192933E+10 | 0.152111E+11 | 0.00 | 18990611.70 | 0.00 | 0.389487E+09 | 0.401696E+10 | 0.00 | 0.20 |
Minimum of Months | 0.00 | 78088946.43 | 0.00 | 436417.68 | 0.00 | 0.00 | 969434.22 | 0.00 | 0.13 |
Maximum of Months | 0.617287E+09 | 0.260847E+10 | 0.00 | 3719161.98 | 0.00 | 0.158328E+09 | 0.915601E+09 | 0.00 | 0.32 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.319534E+10 | 0.00 | 0.00 | 110979.84 | 7461257.40 | 0.00 | 74029131.00 | 0.00 | 0.18 |
February | 0.241310E+10 | 4992480.17 | 0.00 | 293903.09 | 3056219.07 | 0.00 | 0.212467E+09 | 0.00 | 0.20 |
March | 0.266808E+10 | 70010176.08 | 0.00 | 336825.89 | 4225246.59 | 0.00 | 0.243263E+09 | 0.00 | 0.22 |
April | 0.116876E+10 | 0.955422E+09 | 0.00 | 1822650.17 | 2805518.18 | 0.00 | 0.104276E+10 | 0.00 | 0.26 |
May | 0.00 | 0.503384E+10 | 0.00 | 286917.58 | 0.00 | 0.00 | 59921235.51 | 0.00 | 0.20 |
June | 4046057.26 | 0.699696E+10 | 0.00 | 143793.98 | 0.00 | 0.00 | 45065038.32 | 0.00 | 0.20 |
July | 0.00 | 0.783658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
August | 0.00 | 0.742787E+10 | 0.00 | 188717.74 | 0.00 | 0.00 | 39628833.79 | 0.00 | 0.21 |
September | 639008.67 | 0.493150E+10 | 0.00 | 1050043.47 | 0.00 | 0.00 | 0.435748E+09 | 0.00 | 0.23 |
October | 0.552939E+09 | 0.377715E+10 | 0.00 | 2691126.01 | 0.00 | 0.00 | 0.704098E+09 | 0.00 | 0.24 |
November | 0.193789E+10 | 0.626386E+09 | 0.00 | 586059.04 | 16755193.32 | 0.00 | 0.503922E+09 | 0.00 | 0.20 |
December | 0.270092E+10 | 0.163563E+09 | 0.00 | 175103.32 | 11819342.38 | 0.00 | 0.200586E+09 | 0.00 | 0.19 |
Annual Sum or Average | 0.146417E+11 | 0.378243E+11 | 0.00 | 7686120.13 | 46122776.94 | 0.00 | 0.356149E+10 | 0.00 | 0.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
Maximum of Months | 0.319534E+10 | 0.783658E+10 | 0.00 | 2691126.01 | 16755193.32 | 0.00 | 0.104276E+10 | 0.00 | 0.26 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.701088E+12 | 0.327943E+11 | 0.00 | 0.435142E+10 | 0.161030E+10 |
February | 0.764707E+12 | 0.246376E+11 | 0.00 | 0.341640E+10 | 0.246815E+10 |
March | 0.887952E+12 | 0.330404E+11 | 0.00 | 0.364902E+10 | 0.432614E+10 |
April | 0.105490E+13 | 0.275932E+11 | 0.00 | 0.132014E+10 | 0.163503E+11 |
May | 0.104890E+13 | 0.397495E+11 | 0.00 | -0.694612E+10 | 0.486711E+11 |
June | 0.106211E+13 | 0.483242E+11 | 0.00 | -0.925257E+10 | 0.563200E+11 |
July | 0.108453E+13 | 0.493626E+11 | 0.00 | -0.104423E+11 | 0.613595E+11 |
August | 0.101951E+13 | 0.446861E+11 | 0.00 | -0.998022E+10 | 0.620669E+11 |
September | 0.854744E+12 | 0.381495E+11 | 0.00 | -0.660503E+10 | 0.479508E+11 |
October | 0.866886E+12 | 0.423350E+11 | 0.00 | -0.358179E+10 | 0.383556E+11 |
November | 0.665591E+12 | 0.259116E+11 | 0.00 | 0.231815E+10 | 0.898669E+10 |
December | 0.638631E+12 | 0.317577E+11 | 0.00 | 0.343805E+10 | 0.472708E+10 |
Annual Sum or Average | 0.106496E+14 | 0.438342E+12 | 0.00 | -0.283149E+11 | 0.353192E+12 |
Minimum of Months | 0.638631E+12 | 0.246376E+11 | 0.00 | -0.104423E+11 | 0.161030E+10 |
Maximum of Months | 0.108453E+13 | 0.493626E+11 | 0.00 | 0.435142E+10 | 0.620669E+11 |