Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Simulation Timestamp: 2023-10-16 10:41:45
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:45
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 838.71 | 173.46 | 173.46 |
Net Site Energy | 838.71 | 173.46 | 173.46 |
Total Source Energy | 2656.19 | 549.35 | 549.35 |
Net Source Energy | 2656.19 | 549.35 | 549.35 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 219.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 285.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 92.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 137.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 81.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 838.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 219.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 285.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 92.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 137.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 34.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 46.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 22.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 219.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 285.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 92.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 137.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 81.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 22.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 78.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 66.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 173.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 78.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 66.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 173.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 838.710 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 838.710 | 100.00 |
Total On-Site and Utility Electric Sources | 838.710 | 100.00 |
Total Electricity End Uses | 838.710 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 45.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3636.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:45
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Latitude [deg] | 10.82 |
Longitude [deg] | 106.67 |
Elevation [m] | 5.00 |
Time Zone | 7.00 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 159.21 |
Skylight-Roof Ratio [%] | 3.46 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 9.9957 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 10.2257 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 6.2431 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.5746 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.5746 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 9.9957 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 10.2257 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 6.2431 | 46.45 | 2.5587 | |
Total | 4835.13 | 7.5746 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 7.5746 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 7.5746 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:45
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 06-MAY-14:00 | - | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 23658.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 19573.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6133.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1668.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 61088.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 23658.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 19573.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 3828.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1668.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:45
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 695.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 903.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 293.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 434.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 258.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 69.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2656.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 143.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 53.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 549.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 143.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 53.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 549.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:45
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.29 |
ZONE2 FINE STORAGE DIRECT AIR | 3.43 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 0.976836 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 0.976836 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 39959.00 |
PSZ-OFFICE HEATING COIL | 29544.17 |
PSZ-FINE STORAGE HEATING COIL | 155627.65 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 0.000000 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.29 | 1.29 | 1.29 | 1.29 | 1.29 | 1.29 | 1.00 | 1.00 | 1.29 |
PSZ-FINE STORAGE | 3.43 | 3.43 | 3.43 | 3.43 | 3.43 | 3.43 | 1.00 | 1.00 | 3.43 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.29 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 3.43 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.29 | 1425.21 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.43 | 3670.63 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.29 | 1.29 | 1.29 | 1.29 | 26708.57 | 29544.17 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 3.43 | 3.43 | 3.43 | 2.26 | 85183.67 | 155627.65 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.29 | 0.643634 | 0.858180 | 26708.57 | 13354.28 | 0.762330 | 0.762330 |
PSZ-FINE STORAGE COOLING COIL | 3.43 | 1.72 | 2.29 | 85183.67 | 42591.83 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:45
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:45
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:45
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.90 | 26.70 | 26.00 | 26.40 | 27.50 | 28.30 | 29.20 | 29.00 | 28.90 | 27.20 | 27.50 | 27.60 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 | 10.82 | 106.67 | 7.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.60 | 3.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 9.996 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.069 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 10.226 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.226 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 6.243 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 8.802 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2367.778 | 9.996 | 185.726 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2367.778 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 14248.589 | 10.226 | 474.953 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 14248.589 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 20008.023 | 6.243 | 289.971 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20008.023 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 1.090 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.6467 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.7823 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.7823 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9172 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.447 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.179 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.179 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53297977E-11 | 0.35762577E-16 | 0.10093676E-15 | 0.0000000 |
5 | 1 | -5.2159127 | 0.59796011E-04 | -0.14694131E-04 | 0.68696372E-11 |
6 | 0 | 6.3062040 | 1.0902315 | 1.0903060 | |
7 | 4 | 0.74880472E-12 | 0.20419263E-15 | -0.25455326E-14 | 0.12325945E-15 |
8 | 3 | -0.37373706E-03 | 0.44801458E-06 | -0.54107741E-04 | 0.14369897E-12 |
9 | 2 | 1.7134581 | 0.99123779E-02 | 1.1206230 | -0.71650803E-04 |
10 | 1 | -7.1633844 | 0.25872086 | -16.971355 | 0.32838139 |
11 | 0 | 5.8846973 | 0.16576370 | 16.285184 | |
12 | 4 | 0.72249793E-12 | -0.16720573E-15 | 0.22015083E-14 | 0.12409536E-15 |
13 | 3 | -0.36459118E-03 | 0.53555631E-06 | -0.52695411E-04 | 0.13865996E-12 |
14 | 2 | 1.6915239 | 0.11971291E-01 | 1.1039557 | -0.69896550E-04 |
15 | 1 | -7.1930661 | 0.31446443 | -16.864389 | 0.32415671 |
16 | 0 | 6.0306730 | 0.20232993 | 16.289252 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.22015083E-14 | -0.16720573E-15 | 0.72249793E-12 | 0.12409536E-15 |
85 | 3 | -0.52695411E-04 | 0.53555631E-06 | -0.36459118E-03 | 0.13865996E-12 |
86 | 2 | 1.1039557 | 0.11971291E-01 | 1.6915239 | -0.69896550E-04 |
87 | 1 | -16.864389 | 0.31446443 | -7.1930661 | 0.32415671 |
88 | 0 | 16.289252 | 0.20232993 | 6.0306730 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.2_SHGC_SOUTH_0.25 | 34 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
2 | NONRESWINDOW_U_1.2_SHGC_NORTH_0.25 | 35 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
3 | NONRESWINDOW_U_1.2_SHGC_EAST_0.25 | 36 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
4 | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
5 | SKYLIGHT_U_1.02_SHGC_0.36 | 38 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.361 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.19502 | 0.25365 | 0.25365 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE2 FINE STORAGE | 14 | 0 |
2 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE2 FINE STORAGE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_1.02_SHGC_0.36 | SKYLIGHT_FRAME_NONRES | CurtainWall | 5.849 | 0.276 | 0.186 |
2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.849 | 0.366 | 0.185 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.710 | 8.455E-004 | 5.523E-004 | 0.277 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.1851E-005 |
2 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.3678E-004 |
3 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.4340E-005 |
4 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8412E-004 |
5 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.9870E-005 |
6 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6677E-004 |
7 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0671E-004 |
8 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.8311E-004 |
9 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6487E-004 |
10 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6963E-004 |
11 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4385E-004 |
12 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.8116E-004 |
13 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4798E-004 |
14 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5249E-004 |
15 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5370E-004 |
16 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6066E-004 |
17 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.1156E-004 |
18 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2187E-004 |
19 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5965E-004 |
20 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2407E-004 |
21 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.5408E-004 |
22 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1188E-004 |
23 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.1622E-004 |
24 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.5142E-005 |
25 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.7141E-004 |
26 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.9160E-005 |
27 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.4531E-004 |
28 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.9888E-005 |
29 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2135E-003 |
30 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.5077E-005 |
31 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3751E-003 |
32 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6091E-005 |
33 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.7391E-004 |
34 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4876E-005 |
35 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.2747E-004 |
36 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.5437E-005 |
37 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.4231E-004 |
38 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3743E-005 |
39 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2334E-004 |
40 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0335E-005 |
41 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3373E-004 |
42 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9338E-005 |
43 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5020E-004 |
44 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9927E-005 |
45 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1721E-004 |
46 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9637E-005 |
47 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9679E-004 |
48 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8282E-005 |
49 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.0096E-004 |
50 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9617E-005 |
51 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.4201E-004 |
52 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0201E-005 |
53 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.6165E-004 |
54 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9839E-005 |
55 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5644E-004 |
56 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8384E-005 |
57 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5085E-003 |
58 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.5726E-005 |
59 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8883E-003 |
60 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6293E-005 |
61 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3558E-003 |
62 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4385E-005 |
63 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1457E-003 |
64 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0653E-005 |
65 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.6968E-003 |
66 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.2296E-005 |
67 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8115E-003 |
68 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.3144E-005 |
69 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3999E-003 |
70 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.7570E-005 |
71 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.6144E-003 |
72 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.7289E-005 |
73 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7981E-004 |
74 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3695E-004 |
75 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9222E-004 |
76 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4034E-004 |
77 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.6029E-004 |
78 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2450E-004 |
79 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6692E-003 |
80 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.0953E-005 |
81 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0315E-004 |
82 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.7424E-004 |
83 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7427E-004 |
84 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.9975E-004 |
85 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7965E-004 |
86 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.4281E-004 |
87 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5326E-004 |
88 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9897E-004 |
89 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.9260E-005 |
90 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7838E-003 |
91 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.0006E-005 |
92 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0332E-003 |
93 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.4181E-005 |
94 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6602E-003 |
95 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1984E-004 |
96 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1272E-004 |
97 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.0757E-005 |
98 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.2587E-003 |
99 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7620E-005 |
100 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.5461E-003 |
101 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.4500E-005 |
102 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.9193E-003 |
103 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4246E-005 |
104 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.2281E-003 |
105 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.8920E-005 |
106 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0568E-003 |
107 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.6247E-005 |
108 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0576E-003 |
109 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.3696E-005 |
110 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3007E-003 |
111 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.1879E-005 |
112 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2766E-003 |
113 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1729E-005 |
114 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5140E-005 |
115 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8675E-005 |
116 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8978E-005 |
117 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6344E-005 |
118 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4187E-005 |
119 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4598E-005 |
120 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5286E-005 |
121 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2964E-005 |
122 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7173E-005 |
123 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7330E-005 |
124 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2807E-005 |
125 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3040E-005 |
126 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9195E-005 |
127 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1685E-005 |
128 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2542E-005 |
129 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1702E-005 |
130 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0598E-005 |
131 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8582E-005 |
132 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9983E-005 |
133 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5916E-005 |
134 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9484E-005 |
135 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4582E-005 |
136 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1042E-005 |
137 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0976E-004 |
138 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8747E-005 |
139 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1334E-004 |
140 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8914E-005 |
141 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.7139E-005 |
142 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2640E-005 |
143 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2514E-005 |
144 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3080E-005 |
145 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2697E-005 |
146 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1954E-004 |
147 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2470E-005 |
148 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2404E-004 |
149 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7968E-005 |
150 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0539E-004 |
151 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4916E-005 |
152 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6240E-005 |
153 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9545E-005 |
154 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2841E-005 |
155 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8750E-005 |
156 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2475E-005 |
157 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5931E-005 |
158 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2332E-005 |
159 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4899E-005 |
160 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1079E-005 |
161 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0570E-004 |
162 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4978E-005 |
163 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0838E-004 |
164 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4083E-005 |
165 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.4856E-005 |
166 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2969E-005 |
167 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2500E-005 |
168 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7738E-005 |
169 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.9382E-005 |
170 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6450E-004 |
171 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.8360E-005 |
172 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9586E-004 |
173 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5562E-005 |
174 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2863E-004 |
175 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0532E-005 |
176 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7293E-004 |
177 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9722E-004 |
178 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5274E-004 |
179 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1815E-004 |
180 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5368E-004 |
181 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7238E-004 |
182 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4948E-004 |
183 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5069E-004 |
184 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0290E-004 |
185 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7587E-004 |
186 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7334E-005 |
187 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9173E-004 |
188 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5195E-005 |
189 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5966E-004 |
190 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5490E-005 |
191 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5061E-004 |
192 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8433E-005 |
193 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2068E-005 |
194 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5218E-005 |
195 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9756E-005 |
196 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4460E-005 |
197 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0087E-005 |
198 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4435E-005 |
199 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0473E-005 |
200 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3210E-005 |
201 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6592E-004 |
202 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1305E-005 |
203 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.4441E-004 |
204 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6991E-005 |
205 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9245E-004 |
206 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0856E-005 |
207 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2387E-004 |
208 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6113E-005 |
209 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.9862E-004 |
210 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0008E-004 |
211 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1106E-003 |
212 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9911E-004 |
213 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.7987E-004 |
214 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2884E-004 |
215 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2445E-004 |
216 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5215E-004 |
217 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3927E-004 |
218 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7278E-005 |
219 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3257E-004 |
220 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6065E-005 |
221 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4681E-004 |
222 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6225E-005 |
223 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2708E-004 |
224 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5686E-005 |
225 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5237E-004 |
226 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8106E-003 |
227 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4773E-004 |
228 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1033E-003 |
229 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5890E-004 |
230 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5847E-003 |
231 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2726E-004 |
232 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9459E-004 |
233 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6573E-004 |
234 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8103E-005 |
235 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5139E-004 |
236 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6542E-005 |
237 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8216E-004 |
238 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6697E-005 |
239 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9961E-004 |
240 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7482E-005 |
241 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4623E-003 |
242 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7982E-005 |
243 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5267E-003 |
244 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1343E-005 |
245 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7894E-003 |
246 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7853E-005 |
247 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6165E-003 |
248 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3274E-005 |
249 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6573E-003 |
250 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0196E-004 |
251 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7667E-003 |
252 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8054E-004 |
253 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9796E-003 |
254 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8396E-004 |
255 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6195E-003 |
256 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2024E-004 |
257 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7909E-004 |
258 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5815E-003 |
259 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6627E-004 |
260 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0506E-003 |
261 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9821E-004 |
262 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0355E-003 |
263 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0001E-004 |
264 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6530E-003 |
265 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3750E-004 |
266 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7224E-005 |
267 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2079E-004 |
268 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5599E-005 |
269 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4190E-004 |
270 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5439E-005 |
271 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9852E-004 |
272 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7461E-005 |
273 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4411E-004 |
274 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1301E-003 |
275 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2784E-004 |
276 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0463E-003 |
277 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5244E-004 |
278 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3848E-003 |
279 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9891E-004 |
280 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6031E-003 |
281 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2212E-004 |
282 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1064E-005 |
283 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5222E-004 |
284 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.3946E-005 |
285 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7674E-004 |
286 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7929E-005 |
287 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5919E-003 |
288 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3045E-005 |
289 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5679E-004 |
290 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8682E-004 |
291 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9079E-004 |
292 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5201E-004 |
293 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3066E-004 |
294 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2473E-004 |
295 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5949E-003 |
296 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1554E-004 |
297 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1946E-005 |
298 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9360E-004 |
299 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0455E-005 |
300 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4715E-004 |
301 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5933E-005 |
302 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9225E-004 |
303 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2574E-004 |
304 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7337E-004 |
305 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4363E-004 |
306 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4474E-004 |
307 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0600E-004 |
308 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2329E-004 |
309 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4276E-004 |
310 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3591E-004 |
311 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1039E-004 |
312 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4748E-004 |
313 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2958E-005 |
314 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6385E-005 |
315 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7278E-005 |
316 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4471E-005 |
317 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2745E-005 |
318 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2789E-005 |
319 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1671E-005 |
320 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7584E-005 |
321 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0134E-005 |
322 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5104E-005 |
323 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8472E-005 |
324 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3714E-005 |
325 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1842E-005 |
326 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3194E-005 |
327 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2556E-004 |
328 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5637E-005 |
329 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8355E-005 |
330 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0633E-004 |
331 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2146E-005 |
332 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.9981E-005 |
333 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0337E-005 |
334 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.6987E-005 |
335 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9741E-005 |
336 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6869E-004 |
337 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.7208E-005 |
338 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5107E-005 |
339 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2864E-005 |
340 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5201E-005 |
341 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0450E-005 |
342 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1999E-005 |
343 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4732E-004 |
344 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0119E-004 |
345 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8025E-005 |
346 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2673E-005 |
347 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1701E-005 |
348 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1672E-005 |
349 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9027E-005 |
350 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1038E-005 |
351 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9684E-005 |
352 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3161E-005 |
353 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4030E-004 |
354 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6859E-005 |
355 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0244E-004 |
356 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1341E-005 |
357 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3496E-004 |
358 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1154E-005 |
359 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0983E-004 |
360 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5702E-005 |
361 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6922E-005 |
362 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4383E-005 |
363 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2471E-005 |
364 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0924E-005 |
365 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.9131E-005 |
366 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9062E-005 |
367 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4724E-004 |
368 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8139E-005 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 13030.95563 | 15637.14676 | 1.07272 | 1.28727 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | 34.77500 | 1.71573E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 1898.38435 | 2278.06121 | 5.27880E-002 | 0.10228 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 20.10000 | 1.47983E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 44541.57922 | 53449.89506 | 2.85862 | 3.43035 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | 35.20000 | 1.71581E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 0.00000 | 0.00000 | 0.00000 | 0.42471 | 00:10:00 | 20.10000 | 1.47983E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 | |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | 35.20000 | 1.71581E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 0.00000 | 0.00000 | 0.00000 | 0.97684 | 00:10:00 | 20.10000 | 1.47983E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 19868.74 | 1.28727 | 1.28727 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 2461.78 | 0.10228 | 0.10228 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 65337.40 | 3.43035 | 3.43035 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 10221.91 | 0.42471 | 0.42471 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.28727 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.43035 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.97684 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 0.97684 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 39959.00499 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 0.00000 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.28727 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.28727 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.28727 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.28727 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.28727 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.28727 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.43035 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.43035 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.43035 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.43035 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.43035 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.43035 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.28727 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.43035 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.28727 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.28727 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1425.21008 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.28727 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.28727 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.28727 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.28727 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.28727 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.64363 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.85818 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 26708.57000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13354.28500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76233 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76233 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26708.57000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29544.17380 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 29544.17380 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.43035 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.43035 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3670.63268 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.43035 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.43035 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.43035 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.26403 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.43035 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.71517 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.28690 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 85183.67000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 42591.83500 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 85183.67000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 155627.65277 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 155627.65277 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 25708.8 | 11.90 | 11.63 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 82517.3 | 11.12 | 10.87 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 4.2835227525E-002 | 9.5386893628E-002 | Pass | Pass | 1.4592779540E-002 | 0.1216776308 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.2525779944 | 0.2631416628 | Pass | Pass | 0.5960672900 | 2.7127989757 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 4.4955521487E-002 | 4.9689958697E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:45
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 11204.96 | 768.49 | 0.00 | -271.7 | 1074.36 | 12776.12 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:45
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10 | 0.00 | 20.10 | Wetbulb [C] | 1.80 | 0.00 |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20 | 8.50 | 25.80 | Wetbulb [C] | 4.10 | 160.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 57.00 | 12 | |||
Feb | 0.00 | 0 | |||
Mar | 153.60 | 31 | |||
Apr | 87.00 | 59 | |||
May | 227.22 | 128 | |||
Jun | 144.58 | 109 | |||
Jul | 42.40 | 24 | |||
Aug | 164.90 | 163 | |||
Sep | 119.60 | 50 | |||
Oct | 365.70 | 188 | |||
Nov | 70.90 | 67 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:45
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.590 | 0.647 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.590 | 0.647 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.590 | 0.647 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.590 | 0.647 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.590 | 0.647 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.590 | 0.647 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.590 | 0.647 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1344.96 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.948 | 1.090 | 3204.84 | 3094.09 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.659 | 0.782 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.659 | 0.782 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 6.813 | 0.251 | 0.252 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 6.813 | 0.251 | 0.252 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_1.2_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 6.813 | 0.251 | 0.252 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_1.2_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 6.813 | 0.251 | 0.252 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_1.02_SHGC_0.36 | SKYLIGHT_FRAME_NONRES | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.361 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.276 | 0.186 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_1.02_SHGC_0.36 | SKYLIGHT_FRAME_NONRES | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.361 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.276 | 0.186 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_1.02_SHGC_0.36 | SKYLIGHT_FRAME_NONRES | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.361 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.276 | 0.186 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_1.02_SHGC_0.36 | SKYLIGHT_FRAME_NONRES | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.361 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.276 | 0.186 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_1.02_SHGC_0.36 | SKYLIGHT_FRAME_NONRES | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.361 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.276 | 0.186 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_1.02_SHGC_0.36 | SKYLIGHT_FRAME_NONRES | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.361 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.276 | 0.186 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_1.02_SHGC_0.36 | SKYLIGHT_FRAME_NONRES | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.361 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.276 | 0.186 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_1.02_SHGC_0.36 | SKYLIGHT_FRAME_NONRES | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.361 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.276 | 0.186 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_1.02_SHGC_0.36 | SKYLIGHT_FRAME_NONRES | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.361 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.276 | 0.186 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_1.02_SHGC_0.36 | SKYLIGHT_FRAME_NONRES | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.361 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.276 | 0.186 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_1.02_SHGC_0.36 | SKYLIGHT_FRAME_NONRES | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.361 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.276 | 0.186 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_1.02_SHGC_0.36 | SKYLIGHT_FRAME_NONRES | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.361 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.276 | 0.186 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_1.02_SHGC_0.36 | SKYLIGHT_FRAME_NONRES | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.361 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.276 | 0.186 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_1.02_SHGC_0.36 | SKYLIGHT_FRAME_NONRES | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.361 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.276 | 0.186 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.185 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 176.87 | 5.900 | 0.469 | 0.386 | |||||||||||||||||
North Total or Average | 6.51 | 6.813 | 0.251 | 0.252 | |||||||||||||||||
Non-North Total or Average | 170.36 | 5.865 | 0.477 | 0.392 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:45
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:45
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 9.9957 | 236.88 | 2367.78 | LightsWired | LTG_SCH_OFFICE | 56.95 | 168.00 | 56.07 | 0.0000 | Y | 24.92 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 10.2257 | 1393.41 | 14248.59 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 43.46 | 0.0000 | Y | 116.25 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 6.2431 | 3204.84 | 20008.02 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 38.40 | 0.0000 | Y | 144.24 |
Interior Lighting Total | 7.5746 | 4835.13 | 36624.39 | 285.40 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 14248.59 | 3562.15 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 14248.59 | 3562.15 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 20008.02 | 5002.01 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 20008.02 | 5002.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 125.92 | AstronomicalClock | - | 41.93 | 41.93 | 0.99 | |
EXTERIOR_LIGHTS_B | 6860.50 | AstronomicalClock | - | 83.83 | 71.26 | 91.77 | |
Exterior Lighting Total | 6986.42 | 92.76 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:45
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 26708.57 | 20360.74 | 6347.83 | 0.76 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 85183.67 | 59720.57 | 25463.10 | 0.70 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 25708.8 | 11.90 | 11.63 | ||||
PSZ-FINE STORAGE COOLING COIL | 82517.3 | 11.12 | 10.87 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 39959.00 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 29544.17 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 155627.65 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.98 | 90.76 | 92.91 | 1.00 | 4.17 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.29 | 1425.21 | 1107.16 | 1.00 | 1.35 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 3.43 | 3670.63 | 1070.05 | 1.00 | 1.25 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:45
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 13030.96 | 15637.15 | 66.01 | 1.073 | 1.287 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | 23.90 | 23.90 | 0.00853 | 34.78 | 0.01716 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 44541.58 | 53449.90 | 38.36 | 2.859 | 3.430 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | 26.70 | 26.70 | 0.00904 | 35.20 | 0.01716 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | 0.00 | 35.90 | 0.01724 | 35.20 | 0.01716 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 1898.38 | 2278.06 | 9.62 | 0.053 | 0.102 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.01347 | 20.10 | 0.01480 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.425 | 00:10:00 | 15.56 | 17.97 | 0.01292 | 20.10 | 0.01480 | 0.425 | 0.00 | |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | 00:10:00 | 10.00 | 17.79 | 0.01277 | 20.10 | 0.01480 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.29 | 1.29 | 0.10 | 0.10 | 1.2873 | 1.2873 | 1.2873 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.43 | 3.43 | 0.42 | 0.42 | 3.4303 | 3.4303 | 3.4303 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 39959.005 | 39959.005 | -999.0 | -999.0 | -999.000 | 12/21 00:10:00 | 12/21 00:10:00 | 39959.00 | 39959.00 | 0.976836 | 10.00 | 10.00 | 0.00800000 | 43.33 | 22.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 10.00 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | ||
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 26708.570 | 20360.744 | 1.287270 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | 13354.28 | 11100.24 | 0.858180 | 25.66 | 17.56 | 0.00921640 | 12.00 | 11.25 | 0.00800000 | 34.78 | 0.01715734 | 25.72 | 11.9188 | 23.90 | 0.00853095 | 46.1820 | 13030.96 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 29544.174 | 29544.174 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 29544.17 | 29544.17 | 1.287268 | 21.02 | 19.84 | 0.01406007 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 7.9459 | 19.22 | 0.01399635 | 99.9999 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 85183.670 | 59720.567 | 3.430350 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | 42591.83 | 33123.29 | 2.286900 | 28.62 | 19.20 | 0.01004592 | 12.00 | 11.25 | 0.00800000 | 35.20 | 0.01715815 | 25.83 | 18.5715 | 26.70 | 0.00904093 | 41.4058 | 44541.58 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 155627.653 | 155627.653 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 155627.65 | 155627.65 | 3.430346 | 2.49 | 2.49 | 0.01315422 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 12.3810 | 17.97 | 0.01292190 | 99.9999 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:45
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 39959.005 | 39959.005 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.976836 | 1.17571482 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 39959.00 | 39959.00 | 1.0000 | 1.17571482 | 0.976836 | 10.00 | 10.00 | 0.00800000 | 30204.6 | 43.33 | 22.14 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39959.00 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 10.00 | 0.00800000 | 10.00 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26708.570 | 20360.744 | 1.287270 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.9728 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.287268 | 1.54934938 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | Sensible | 13354.28 | 11100.24 | 1.0000 | 1.03290114 | 0.858180 | 25.66 | 17.56 | 0.00921640 | 49275.5 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13354.28 | 34.78 | 0.01715734 | 25.72 | 0.10228463 | 11.9188 | 23.90 | 0.00853095 | 23.90 | 0.00853095 | 46.1820 | 13030.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29544.174 | 29544.174 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.287268 | 1.54934938 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 29544.17 | 29544.17 | 1.0000 | 1.54934938 | 1.287268 | 21.02 | 19.84 | 0.01406007 | 56838.1 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29544.17 | 20.10 | 0.01479830 | 20.10 | 0.10228463 | 7.9459 | 21.10 | 0.01399635 | 19.22 | 0.01399635 | 99.9999 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 85183.670 | 59720.567 | 3.430350 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.5149 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.430346 | 4.12874758 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | Sensible | 42591.83 | 33123.29 | 1.0000 | 2.75250136 | 2.286900 | 28.62 | 19.20 | 0.01004592 | 54414.3 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 42591.83 | 35.20 | 0.01715815 | 25.83 | 0.42471127 | 18.5715 | 26.70 | 0.00904093 | 26.70 | 0.00904093 | 41.4058 | 44541.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 155627.653 | 155627.653 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.430346 | 4.12874758 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 155627.65 | 155627.65 | 1.0000 | 4.12874758 | 3.430346 | 2.49 | 2.49 | 0.01315422 | 35459.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 155627.65 | 20.10 | 0.01479830 | 20.10 | 0.42471127 | 12.3810 | 0.00 | 0.01292190 | 17.97 | 0.01292190 | 99.9999 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:45
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 3635.50 | 871.17 | 871.17 |
ZONE2 FINE STORAGE | 3636.00 | 3621.33 | 3621.33 |
ZONE3 BULK STORAGE | 3636.00 | 3636.00 | 3636.00 |
Facility | 3636.00 | 3636.00 | 3636.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 0.00 | 876.33 | 0.00 | 41.33 |
ZONE2 FINE STORAGE | 0.00 | 293.33 | 0.00 | 3.67 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 1079.33 | 0.00 | 45.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:45
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.354 | 0.374 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.498 | 0.157 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.100 | 0.000 | 2.807 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:45
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.55 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1668986.57 | 0.00 | 1668986.57 | 1771116.47 | 3440103.04 | 3225648.14 | 5310.00 | 3450.00 | 0.00 | 2757.64 |
ZONE2 FINE STORAGE | 5943243.43 | 0.00 | 5943243.43 | 4070082.89 | 10013326.31 | 13393694.68 | 5405.82 | 3354.18 | 0.00 | 2486.72 |
ZONE3 BULK STORAGE | 0.00 | 0.54E+09 | 0.54E+09 | 23593493.67 | 0.56E+09 | 30805497.77 | 4567.56 | 0.00 | 4192.44 | 4941.16 |
Total Facility | 7612230.00 | 0.54E+09 | 0.54E+09 | 29434693.03 | 0.57E+09 | 47424840.58 | 6136.31 | 3467.17 | 4192.44 | 5057.46 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.0962 | 0.0000 | 0.0962 | 0.1013 | 0.1975 | 0.1023 | 298.79 | 3337.21 | 0.00 |
ZONE2 FINE STORAGE | 0.3905 | 0.0000 | 0.3905 | 0.1235 | 0.5140 | 0.4247 | 303.00 | 3333.00 | 0.00 |
ZONE3 BULK STORAGE | 0.0000 | 25.6112 | 25.6112 | 0.9167 | 26.5279 | 0.9768 | 1000.26 | 0.00 | 2635.74 |
Total Facility | 0.4867 | 25.6112 | 26.0979 | 1.1415 | 27.2394 | 1.5038 | 1016.19 | 3337.21 | 2635.74 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2417762.17 | 0.00 | 2417762.17 | 3225648.14 | 4948.40 | 22.59 | 3789.01 | 2755.20 |
PSZ-FINE STORAGE | 8609689.28 | 0.00 | 8609689.28 | 13393694.68 | 5348.41 | 8.19 | 3403.40 | 2480.90 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1393 | 0.0000 | 0.1393 | 0.1023 | 266.85 | 2.14 | 3367.01 |
PSZ-FINE STORAGE | 0.5658 | 0.0000 | 0.5658 | 0.4247 | 302.92 | 0.03 | 3333.04 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 6322.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 5882.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1420 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6049 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:45
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 426 |
Defaulted Fields | 391 |
Fields with Defaults | 1157 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:41:45
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 838.71 | 3051.37 | 01-JAN-12:00 | 61088.33 | 06-MAY-15:00 |
Electricity:Building | 457.23 | 2570.37 | 01-JAN-12:00 | 39630.27 | 11-JAN-17:00 |
Electricity:Zone:ZONE1 OFFICE | 54.64 | 857.54 | 01-JAN-00:10 | 3432.39 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 422.47 | 2570.37 | 01-JAN-12:00 | 37916.16 | 18-DEC-16:00 |
InteriorLights:Electricity | 285.41 | 2081.83 | 01-JAN-12:00 | 27862.15 | 18-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 24.92 | 368.99 | 01-JAN-00:10 | 1578.50 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 285.41 | 2081.83 | 01-JAN-12:00 | 27862.15 | 18-DEC-16:00 |
LightsWired:InteriorLights:Electricity | 285.41 | 2081.83 | 01-JAN-12:00 | 27862.15 | 18-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 24.92 | 368.99 | 01-JAN-00:10 | 1578.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 285.41 | 2081.83 | 01-JAN-12:00 | 27862.15 | 18-DEC-16:00 |
Electricity:Zone:ZONE2 FINE STORAGE | 116.25 | 712.43 | 01-JAN-12:00 | 12111.30 | 18-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 116.25 | 712.43 | 01-JAN-12:00 | 12111.30 | 18-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 116.25 | 712.43 | 01-JAN-12:00 | 12111.30 | 18-DEC-16:00 |
Electricity:Zone:ZONE3 BULK STORAGE | 286.35 | 1000.40 | 01-JAN-08:30 | 25511.43 | 02-JAN-17:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 144.24 | 1000.40 | 01-JAN-08:30 | 15006.02 | 02-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 144.24 | 1000.40 | 01-JAN-08:30 | 15006.02 | 02-JAN-17:00 |
InteriorEquipment:Electricity | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.72 | 488.55 | 01-JAN-00:10 | 1853.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.72 | 488.55 | 01-JAN-00:10 | 1853.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 81.73 | 0.00 | 01-JAN-00:10 | 6342.09 | 06-MAY-15:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 34.76 | 0.00 | 01-JAN-00:10 | 2305.29 | 02-JAN-15:20 |
Ventilation (simple):Fans:Electricity | 34.76 | 0.00 | 01-JAN-00:10 | 2305.29 | 02-JAN-15:20 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 34.76 | 0.00 | 01-JAN-00:10 | 2305.29 | 02-JAN-15:20 |
ElectricityPurchased:Facility | 838.71 | 3051.37 | 20-AUG-10:20 | 61088.33 | 06-MAY-15:00 |
ElectricityPurchased:Plant | 838.71 | 3051.37 | 20-AUG-10:20 | 61088.33 | 06-MAY-15:00 |
Cogeneration:ElectricityPurchased | 838.71 | 3051.37 | 20-AUG-10:20 | 61088.33 | 06-MAY-15:00 |
General:Cogeneration:ElectricityPurchased | 838.71 | 3051.37 | 20-AUG-10:20 | 61088.33 | 06-MAY-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 838.71 | 3051.37 | 20-AUG-10:20 | 61088.33 | 06-MAY-15:00 |
ElectricityNet:Plant | 838.71 | 3051.37 | 20-AUG-10:20 | 61088.33 | 06-MAY-15:00 |
Cogeneration:ElectricityNet | 838.71 | 3051.37 | 20-AUG-10:20 | 61088.33 | 06-MAY-15:00 |
General:Cogeneration:ElectricityNet | 838.71 | 3051.37 | 20-AUG-10:20 | 61088.33 | 06-MAY-15:00 |
Electricity:HVAC | 266.62 | 0.00 | 01-JAN-00:10 | 29124.89 | 06-MAY-15:10 |
General:Fans:Electricity | 46.96 | 0.00 | 01-JAN-00:10 | 4036.80 | 06-MAY-15:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 219.66 | 0.00 | 01-JAN-00:10 | 25088.09 | 06-MAY-15:10 |
General:Cooling:Electricity | 219.66 | 0.00 | 01-JAN-00:10 | 25088.09 | 06-MAY-15:10 |
ExteriorLights:Electricity | 92.76 | 0.00 | 01-JAN-06:20 | 6986.42 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 92.76 | 0.00 | 01-JAN-06:20 | 6986.42 | 01-JAN-06:10 |
Electricity:Plant | 22.09 | 481.00 | 24-JAN-09:00 | 1702.66 | 11-JAN-12:30 |
WaterSystems:Electricity | 22.09 | 481.00 | 24-JAN-09:00 | 1702.66 | 11-JAN-12:30 |
Water Heater:WaterSystems:Electricity | 22.09 | 481.00 | 24-JAN-09:00 | 1702.66 | 11-JAN-12:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1329.83 | 0.00 | 01-JAN-00:10 | 138783.01 | 06-MAY-15:10 |
EnergyTransfer:Building | 475.13 | 0.00 | 01-JAN-00:10 | 52356.48 | 06-MAY-15:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 136.43 | 0.00 | 01-JAN-00:10 | 14421.31 | 18-JUN-23:10 |
Heating:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 695.02 | 21-DEC-07:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.00 | 0.00 | 01-JAN-00:10 | 695.02 | 21-DEC-07:10 |
General:Heating:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 695.02 | 21-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.00 | 0.00 | 01-JAN-00:10 | 695.02 | 21-DEC-07:10 |
Cooling:EnergyTransfer | 475.12 | 0.00 | 01-JAN-00:10 | 52356.48 | 06-MAY-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 136.43 | 0.00 | 01-JAN-00:10 | 14421.31 | 18-JUN-23:10 |
General:Cooling:EnergyTransfer | 475.12 | 0.00 | 01-JAN-00:10 | 52356.48 | 06-MAY-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 136.43 | 0.00 | 01-JAN-00:10 | 14421.31 | 18-JUN-23:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 338.70 | 0.00 | 01-JAN-00:10 | 40696.20 | 06-MAY-15:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 488.03 | 14-NOV-07:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 488.03 | 14-NOV-07:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 338.69 | 0.00 | 01-JAN-00:10 | 40696.20 | 06-MAY-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 338.69 | 0.00 | 01-JAN-00:10 | 40696.20 | 06-MAY-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 854.70 | 0.00 | 01-JAN-00:10 | 87170.60 | 13-JUN-15:40 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 854.70 | 0.00 | 01-JAN-00:10 | 87170.60 | 13-JUN-15:40 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:45
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 0.000 | -136.428 | 0.000 | 0.000 | 9.119 | 24.919 | 29.720 | 18.410 | 0.000 | 9.711 | 46.880 | 0.000 | -2.000 | 0.000 | -0.333 | -0.002 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 0.002 | -338.678 | 0.000 | 0.000 | 17.086 | 116.249 | 0.000 | 49.355 | 0.000 | 9.442 | 160.035 | 0.000 | -10.117 | 0.000 | -3.373 | -0.001 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20.603 | 144.239 | 107.344 | 805.581 | 0.000 | 2.272 | 0.006 | 0.000 | -187.020 | 0.000 | -835.546 | -57.473 |
Total Facility | 0.000 | 0.000 | 0.003 | -475.106 | 0.000 | 0.000 | 46.809 | 285.407 | 137.063 | 873.347 | 0.000 | 21.425 | 206.921 | 0.000 | -199.137 | 0.000 | -839.252 | -57.476 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 17-JAN-00:01 | 0.00 | 0.00 | 0.00 | -20640.26 | 0.00 | 0.00 | 0.00 | 368.99 | 488.55 | 0.00 | 0.00 | 0.00 | 20293.45 | 0.00 | -414.22 | 0.00 | -96.52 | 0.00 |
ZONE2 FINE STORAGE | 16-JAN-16:33 | 0.00 | 0.00 | 0.00 | -69970.84 | 0.00 | 0.00 | 0.00 | 1424.86 | 0.00 | 874.37 | 0.00 | 639.78 | 67031.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 29-MAR-17:06 | 0.00 | 0.00 | 0.00 | -81032.05 | 0.00 | 0.00 | 0.00 | 3627.92 | 2538.58 | 14987.76 | 0.00 | 2270.08 | 121515.87 | 0.00 | 0.00 | 0.00 | -63908.16 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 21-DEC-07:10 | 0.00 | 0.00 | 695.33 | 0.00 | 0.00 | 0.00 | 191.52 | 861.00 | 926.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -243.44 | 0.00 | -2012.41 | -418.94 |
ZONE2 FINE STORAGE | 14-NOV-07:07 | 0.00 | 0.00 | 1464.33 | 0.00 | 0.00 | 0.00 | 337.54 | 7836.72 | 0.00 | 796.07 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -33.08 | -10401.58 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 14-NOV-07:07 | -5120.58 | 5120.58 | 1464.33 | -5120.58 | 0.00 | 0.00 | 1124.94 | 17701.33 | 2976.98 | 25607.82 | 0.00 | 910.74 | 0.00 | 0.00 | 0.00 | 0.00 | -1696.59 | -42968.96 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:45
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2873 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.2873 | 0.0795 | 1.0000 | Not calculated | 0.1023 | 0.0795 | ||
PSZ-FINE STORAGE | 3.4303 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.4303 | 0.1238 | 1.0000 | Not calculated | 0.4247 | 0.1238 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2873 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.2873 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0795 | ||
PSZ-FINE STORAGE | 3.4303 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.4303 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1238 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2873 | 1.2873 | 1.2873 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.4303 | 3.4303 | 3.4303 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2873 | 1.2873 | 1.2873 | 1.2873 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.4303 | 3.4303 | 3.4303 | 3.4303 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2873 | 1.2873 | 1.2873 | No | 0.1023 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.4303 | 3.4303 | 3.4303 | No | 0.4247 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2873 | 1.2873 | 1.2873 | 1.2873 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.4303 | 3.4303 | 3.4303 | 3.4303 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:45
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Total gross floor area [m2] | 4835.13 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 45.00 |
Number of hours not met | 45.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 219.66 | 25088.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 285.41 | 27862.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 92.76 | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 137.06 | 10054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 34.76 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 46.96 | 4036.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 22.09 | 1702.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 137.06 | 838.71 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 137.06 | 838.71 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 59.03 |
Space Heating | 0.00 |
Space Cooling | 45.43 |
Fans (All) | 16.90 |
Service Water Heating | 4.57 |
Receptacle Equipment | 28.35 |
Miscellaneous (All) | 173.46 |
Subtotal | 173.46 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 34.03 |
Space Heating | 0.00 |
Space Cooling | 26.19 |
Fans (All) | 9.74 |
Service Water Heating | 2.63 |
Receptacle Equipment | 16.34 |
Miscellaneous | 11.06 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2970. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4378. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:45
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 7327.33 | 1248.33 | 184.33 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 175.83 | 8584.17 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 1255.83 | 6597.83 | 906.33 | 0.00 |
Min | 0.00 | 1248.33 | 0.00 | 0.00 | 0.00 |
Max | 7327.33 | 8584.17 | 6597.83 | 906.33 | 0.00 |
Average | 2501.06 | 3696.11 | 2260.72 | 302.11 | 0.00 |
Sum | 7503.17 | 11088.33 | 6782.17 | 906.33 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 613.50 | 82105.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 13401.67 | 134887.17 | 42904.17 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 33027.00 | 82105.50 | 134887.17 | 42904.17 | 0.00 |
Average | 11213.50 | 31835.72 | 44962.39 | 14301.39 | 0.00 |
Sum | 33640.50 | 95507.17 | 134887.17 | 42904.17 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 5705.00 | 3014.00 | 41.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 20.00 | 8740.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 2833.83 | 5154.83 | 768.67 | 2.67 |
Min | 0.00 | 2833.83 | 0.00 | 0.00 | 0.00 |
Max | 5705.00 | 8740.00 | 5154.83 | 768.67 | 2.67 |
Average | 1908.33 | 4862.61 | 1731.94 | 256.22 | 0.89 |
Sum | 5725.00 | 14587.83 | 5195.83 | 768.67 | 2.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 25820.50 | 7206.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 214.00 | 82505.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 41383.17 | 113352.50 | 36284.33 | 173.00 |
Min | 0.00 | 7206.50 | 0.00 | 0.00 | 0.00 |
Max | 25820.50 | 82505.00 | 113352.50 | 36284.33 | 173.00 |
Average | 8678.17 | 43698.22 | 37784.17 | 12094.78 | 57.67 |
Sum | 26034.50 | 131094.67 | 113352.50 | 36284.33 | 173.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:45
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:45
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 2920.00 | 0.00 |
Sum | 0.00 | 8760.00 | 8760.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 27573.00 | 0.00 |
Sum | 0.00 | 191193.00 | 82719.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
For: Environment
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
For: Environment
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
For: Environment
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106450E+11 | 20644.08 | 17-JAN-00:01 | 23.75 | 21.25 | 0.634802E+09 | 769.03 | 25-JAN-09:09 | 23.90 | 20.27 |
February | 0.103005E+11 | 20437.45 | 21-FEB-00:01 | 27.32 | 22.78 | 0.584037E+09 | 769.03 | 09-FEB-08:39 | 27.32 | 22.78 |
March | 0.126898E+11 | 18608.11 | 06-MAR-00:01 | 24.87 | 22.77 | 0.685645E+09 | 769.02 | 16-MAR-07:30 | 26.20 | 24.00 |
April | 0.121315E+11 | 18069.84 | 23-APR-23:01 | 27.42 | 24.87 | 0.634883E+09 | 769.03 | 14-APR-15:50 | 27.42 | 24.87 |
May | 0.126061E+11 | 18326.30 | 14-MAY-23:01 | 28.83 | 26.83 | 0.660285E+09 | 769.04 | 17-MAY-10:50 | 25.03 | 25.03 |
June | 0.128924E+11 | 18207.25 | 20-JUN-00:23 | 24.70 | 24.39 | 0.660295E+09 | 769.03 | 30-JUN-12:00 | 23.40 | 23.40 |
July | 0.113115E+11 | 20560.60 | 16-JUL-23:01 | 25.92 | 23.80 | 0.634864E+09 | 769.03 | 22-JUL-07:40 | 24.50 | 23.36 |
August | 0.120079E+11 | 18068.03 | 29-AUG-00:23 | 25.75 | 25.37 | 0.685650E+09 | 769.04 | 19-AUG-15:39 | 25.75 | 25.37 |
September | 0.110713E+11 | 18079.11 | 25-SEP-04:23 | 26.00 | 25.61 | 0.634867E+09 | 769.03 | 16-SEP-13:20 | 26.00 | 25.61 |
October | 0.104732E+11 | 17924.25 | 07-OCT-18:23 | 25.80 | 23.82 | 0.634838E+09 | 769.04 | 11-OCT-15:00 | 24.50 | 24.50 |
November | 0.101461E+11 | 18762.58 | 05-NOV-23:01 | 25.42 | 23.30 | 0.609444E+09 | 769.04 | 27-NOV-08:50 | 24.25 | 22.21 |
December | 0.101536E+11 | 19226.75 | 04-DEC-00:01 | 23.95 | 23.79 | 0.634791E+09 | 769.03 | 19-DEC-08:00 | 26.00 | 22.46 |
Annual Sum or Average | 0.136429E+12 | 0.769440E+10 | ||||||||
Minimum of Months | 0.101461E+11 | 17924.25 | 23.75 | 21.25 | 0.584037E+09 | 769.02 | 23.40 | 20.27 | ||
Maximum of Months | 0.128924E+11 | 20644.08 | 28.83 | 26.83 | 0.685650E+09 | 769.04 | 27.42 | 25.61 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.251935E+11 | 69975.19 | 16-JAN-16:33 | 29.77 | 22.11 | 0.185440E+10 | 2246.99 | 07-JAN-14:30 | 29.77 | 22.11 |
February | 0.262833E+11 | 64770.31 | 20-FEB-16:53 | 30.00 | 23.63 | 0.170648E+10 | 2247.09 | 28-FEB-14:09 | 35.00 | 24.83 |
March | 0.329985E+11 | 63132.48 | 19-MAR-14:22 | 35.50 | 24.18 | 0.200320E+10 | 2247.10 | 29-MAR-13:30 | 35.80 | 23.34 |
April | 0.333287E+11 | 61095.22 | 23-APR-13:43 | 33.02 | 24.66 | 0.185471E+10 | 2247.08 | 27-APR-13:39 | 33.67 | 25.36 |
May | 0.327755E+11 | 61189.25 | 29-MAY-17:33 | 33.33 | 26.83 | 0.192890E+10 | 2247.06 | 27-MAY-12:50 | 33.33 | 26.83 |
June | 0.344253E+11 | 58317.41 | 25-JUN-14:02 | 28.17 | 27.24 | 0.192891E+10 | 2247.07 | 21-JUN-13:39 | 28.17 | 27.24 |
July | 0.283452E+11 | 61804.17 | 14-JUL-17:06 | 32.78 | 25.08 | 0.185493E+10 | 2247.02 | 14-JUL-14:00 | 32.78 | 25.08 |
August | 0.274088E+11 | 59165.72 | 13-AUG-16:42 | 28.38 | 26.56 | 0.200320E+10 | 2247.06 | 14-AUG-12:09 | 33.13 | 27.67 |
September | 0.272812E+11 | 61019.68 | 10-SEP-10:13 | 31.40 | 26.21 | 0.185484E+10 | 2247.08 | 12-SEP-13:50 | 33.70 | 26.65 |
October | 0.238293E+11 | 59992.75 | 09-OCT-14:02 | 29.17 | 26.15 | 0.185487E+10 | 2247.06 | 04-OCT-15:50 | 29.17 | 26.15 |
November | 0.235283E+11 | 66205.72 | 05-NOV-14:53 | 30.50 | 24.59 | 0.178056E+10 | 2247.00 | 28-NOV-15:50 | 28.83 | 24.65 |
December | 0.232966E+11 | 65329.45 | 24-DEC-15:32 | 31.33 | 23.86 | 0.185414E+10 | 2247.00 | 23-DEC-15:30 | 31.33 | 23.86 |
Annual Sum or Average | 0.338694E+12 | 0.224791E+11 | ||||||||
Minimum of Months | 0.232966E+11 | 58317.41 | 28.17 | 22.11 | 0.170648E+10 | 2246.99 | 28.17 | 22.11 | ||
Maximum of Months | 0.344253E+11 | 69975.19 | 35.50 | 27.24 | 0.200320E+10 | 2247.10 | 35.80 | 27.67 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 | 23.60 | 0.564376E+10 | 8428.96 | 04-JAN-13:39 | 34.03 | 23.47 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 26.43 | 22.46 | 0.541673E+10 | 8907.43 | 28-FEB-14:39 | 35.00 | 24.83 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 | 22.97 | 0.658664E+10 | 9097.65 | 21-MAR-12:39 | 35.93 | 23.10 |
April | 0.00 | 0.00 | 01-APR-00:05 | 27.53 | 25.10 | 0.617955E+10 | 9097.65 | 01-APR-13:39 | 35.40 | 26.88 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 | 26.40 | 0.638215E+10 | 9097.65 | 01-MAY-12:09 | 34.40 | 26.31 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 | 23.91 | 0.643987E+10 | 9097.65 | 12-JUN-14:00 | 36.00 | 27.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 | 24.33 | 0.560953E+10 | 8113.15 | 15-JUL-15:00 | 33.20 | 25.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 | 24.75 | 0.614322E+10 | 8472.50 | 14-AUG-13:20 | 33.53 | 27.57 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 26.53 | 25.66 | 0.570715E+10 | 8544.12 | 06-SEP-14:20 | 33.67 | 26.68 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.27 | 25.35 | 0.548488E+10 | 8085.87 | 04-OCT-14:20 | 32.83 | 26.21 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 | 24.37 | 0.529191E+10 | 8351.95 | 18-NOV-13:20 | 33.20 | 25.24 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 23.80 | 23.43 | 0.551197E+10 | 8097.56 | 08-DEC-14:39 | 33.00 | 23.51 |
Annual Sum or Average | 0.00 | 0.703974E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 23.80 | 22.46 | 0.529191E+10 | 8085.87 | 32.83 | 23.10 | ||
Maximum of Months | 0.00 | 0.00 | 28.62 | 26.40 | 0.658664E+10 | 9097.65 | 36.00 | 27.60 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:05 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 417010.75 | 695.02 | 21-DEC-07:10 | 18.83 |
Annual Sum or Average | 417010.75 | |||
Minimum of Months | 0.00 | 0.00 | 18.83 | |
Maximum of Months | 417010.75 | 695.02 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 26.43 |
March | 208874.81 | 853.63 | 27-MAR-06:07 | 26.20 |
April | 408255.15 | 368.47 | 26-APR-06:05 | 27.05 |
May | 210533.10 | 1052.67 | 27-MAY-06:07 | 25.53 |
June | 133495.32 | 889.97 | 30-JUN-06:05 | 24.87 |
July | 261041.42 | 1048.78 | 03-JUL-06:07 | 25.52 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 331337.48 | 858.10 | 12-SEP-06:05 | 25.10 |
October | 257124.30 | 1285.62 | 03-OCT-06:07 | 26.03 |
November | 398137.61 | 1464.10 | 14-NOV-07:07 | 26.42 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 23.80 |
Annual Sum or Average | 2208799.18 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 408255.15 | 1464.10 | 27.05 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:05 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.208425E+10 | 1578.50 | 02-JAN-08:09 | 0.248944E+10 | 1853.89 | 02-JAN-08:09 |
February | 0.190093E+10 | 1578.50 | 01-FEB-08:09 | 0.226834E+10 | 1853.89 | 01-FEB-08:09 |
March | 0.217193E+10 | 1578.50 | 01-MAR-08:09 | 0.258391E+10 | 1853.89 | 01-MAR-08:09 |
April | 0.205237E+10 | 1578.50 | 01-APR-07:10 | 0.244723E+10 | 1853.89 | 01-APR-07:10 |
May | 0.212809E+10 | 1578.50 | 01-MAY-07:10 | 0.253668E+10 | 1853.89 | 01-MAY-07:10 |
June | 0.209621E+10 | 1578.50 | 01-JUN-07:10 | 0.249447E+10 | 1853.89 | 01-JUN-07:10 |
July | 0.208425E+10 | 1578.50 | 01-JUL-07:10 | 0.248944E+10 | 1853.89 | 01-JUL-07:10 |
August | 0.217193E+10 | 1578.50 | 01-AUG-07:10 | 0.258391E+10 | 1853.89 | 01-AUG-07:10 |
September | 0.205237E+10 | 1578.50 | 01-SEP-07:10 | 0.244723E+10 | 1853.89 | 01-SEP-07:10 |
October | 0.208425E+10 | 1578.50 | 02-OCT-07:10 | 0.248944E+10 | 1853.89 | 02-OCT-07:10 |
November | 0.200853E+10 | 1578.50 | 01-NOV-07:10 | 0.239999E+10 | 1853.89 | 01-NOV-07:10 |
December | 0.208425E+10 | 1578.50 | 01-DEC-08:09 | 0.248944E+10 | 1853.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.249194E+11 | 0.297195E+11 | ||||
Minimum of Months | 0.190093E+10 | 1578.50 | 0.226834E+10 | 1853.89 | ||
Maximum of Months | 0.217193E+10 | 1578.50 | 0.258391E+10 | 1853.89 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.987121E+10 | 10686.44 | 02-JAN-16:30 | 0.00 | 0.00 |
February | 0.886779E+10 | 10686.44 | 01-FEB-16:00 | 0.00 | 0.00 |
March | 0.100658E+11 | 10686.44 | 01-MAR-16:00 | 0.00 | 0.00 |
April | 0.948336E+10 | 10092.75 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.999471E+10 | 10092.75 | 05-MAY-08:09 | 0.00 | 0.00 |
June | 0.100065E+11 | 9795.91 | 01-JUN-07:10 | 0.00 | 0.00 |
July | 0.973546E+10 | 9795.91 | 01-JUL-07:10 | 0.00 | 0.00 |
August | 0.100336E+11 | 10092.75 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.934084E+10 | 9795.91 | 01-SEP-07:10 | 0.00 | 0.00 |
October | 0.952821E+10 | 10092.75 | 23-OCT-08:09 | 0.00 | 0.00 |
November | 0.938540E+10 | 11102.03 | 07-NOV-15:00 | 0.00 | 0.00 |
December | 0.993608E+10 | 12111.30 | 18-DEC-15:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116249E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.886779E+10 | 9795.91 | 0.00 | 0.00 | |
Maximum of Months | 0.100658E+11 | 12111.30 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124439E+11 | 15006.02 | 02-JAN-16:00 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.111713E+11 | 13755.52 | 02-FEB-16:00 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.126057E+11 | 12505.01 | 01-MAR-16:40 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.116679E+11 | 12004.81 | 01-APR-06:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.120359E+11 | 12505.01 | 17-MAY-07:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.118443E+11 | 12505.01 | 20-JUN-07:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.117753E+11 | 12505.01 | 11-JUL-07:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.123694E+11 | 12505.01 | 08-AUG-07:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.117117E+11 | 12004.81 | 01-SEP-06:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.120536E+11 | 12505.01 | 11-OCT-15:00 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.119697E+11 | 15006.02 | 06-NOV-16:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.125901E+11 | 15006.02 | 01-DEC-16:00 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.144239E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.111713E+11 | 12004.81 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.126057E+11 | 15006.02 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.208425E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.660858E+09 | 78250997.23 |
February | 0.127628E+10 | 0.190093E+10 | 0.226834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731960E+09 | 33291302.89 |
March | 0.149825E+10 | 0.217193E+10 | 0.258391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110111E+10 | 19227601.98 |
April | 0.138726E+10 | 0.205237E+10 | 0.244723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104472E+10 | 7027741.93 |
May | 0.144276E+10 | 0.212809E+10 | 0.253668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111588E+10 | 5133213.69 |
June | 0.144276E+10 | 0.209621E+10 | 0.249447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112209E+10 | 11378418.95 |
July | 0.138726E+10 | 0.208425E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.652903E+09 | 14966686.03 |
August | 0.149825E+10 | 0.217193E+10 | 0.258391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.869053E+09 | 18187505.72 |
September | 0.138726E+10 | 0.205237E+10 | 0.244723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697973E+09 | 13911010.03 |
October | 0.138726E+10 | 0.208425E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.594665E+09 | 26014744.02 |
November | 0.133177E+10 | 0.200853E+10 | 0.239999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593970E+09 | 30737771.37 |
December | 0.138726E+10 | 0.208425E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526256E+09 | 74500635.97 |
Annual Sum or Average | 0.168137E+11 | 0.249194E+11 | 0.297195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.971144E+10 | 0.332628E+09 |
Minimum of Months | 0.127628E+10 | 0.190093E+10 | 0.226834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526256E+09 | 5133213.69 |
Maximum of Months | 0.149825E+10 | 0.217193E+10 | 0.258391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112209E+10 | 78250997.23 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.987121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434646E+09 | 0.526107E+09 |
February | 0.300332E+10 | 0.886779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708981E+09 | 0.205890E+09 |
March | 0.352563E+10 | 0.100658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120472E+10 | 0.305378E+09 |
April | 0.326447E+10 | 0.948336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122638E+10 | 63381823.36 |
May | 0.339505E+10 | 0.999471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141717E+10 | 0.156789E+09 |
June | 0.339505E+10 | 0.100065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129131E+10 | 0.141347E+09 |
July | 0.326447E+10 | 0.973546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697823E+09 | 0.188838E+09 |
August | 0.352563E+10 | 0.100336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794672E+09 | 0.342785E+09 |
September | 0.326447E+10 | 0.934084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612031E+09 | 0.200753E+09 |
October | 0.326447E+10 | 0.952821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431834E+09 | 0.308112E+09 |
November | 0.313390E+10 | 0.938540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323115E+09 | 0.341676E+09 |
December | 0.326447E+10 | 0.993608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298896E+09 | 0.592165E+09 |
Annual Sum or Average | 0.395654E+11 | 0.116249E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.944159E+10 | 0.337322E+10 |
Minimum of Months | 0.300332E+10 | 0.886779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298896E+09 | 63381823.36 |
Maximum of Months | 0.352563E+10 | 0.100658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141717E+10 | 0.592165E+09 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.124439E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 471862.16 | 0.596139E+10 |
February | 0.690763E+10 | 0.111713E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1544559.27 | 0.400523E+10 |
March | 0.810895E+10 | 0.126057E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10430444.47 | 0.684586E+10 |
April | 0.750829E+10 | 0.116679E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7707370.81 | 0.389164E+10 |
May | 0.780862E+10 | 0.120359E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16185572.83 | 0.451567E+10 |
June | 0.780862E+10 | 0.118443E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2506453.47 | 0.452453E+10 |
July | 0.750829E+10 | 0.117753E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 377343.12 | 0.416524E+10 |
August | 0.810895E+10 | 0.123694E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11034182.77 | 0.652905E+10 |
September | 0.750829E+10 | 0.117117E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1222243.04 | 0.415075E+10 |
October | 0.750829E+10 | 0.120536E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 416355.81 | 0.490225E+10 |
November | 0.720796E+10 | 0.119697E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1134165.46 | 0.466054E+10 |
December | 0.750829E+10 | 0.125901E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 837578.60 | 0.601784E+10 |
Annual Sum or Average | 0.910005E+11 | 0.144239E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 53868131.79 | 0.601700E+11 |
Minimum of Months | 0.690763E+10 | 0.111713E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 377343.12 | 0.389164E+10 |
Maximum of Months | 0.810895E+10 | 0.126057E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16185572.83 | 0.684586E+10 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1578.50 | 02-JAN-08:09 | 1853.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3687.13 | 04-JAN-13:00 | 1621.80 | 24-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 1578.50 | 01-FEB-08:09 | 1853.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3752.71 | 28-FEB-13:00 | 976.60 | 01-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 1578.50 | 01-MAR-08:09 | 1853.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4050.50 | 20-MAR-16:10 | 250.07 | 15-MAR-06:10 |
April | 1680.92 | 01-APR-07:10 | 1578.50 | 01-APR-07:10 | 1853.89 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4167.56 | 11-APR-16:10 | 181.31 | 09-APR-15:55 |
May | 1680.92 | 01-MAY-07:10 | 1578.50 | 01-MAY-07:10 | 1853.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4692.48 | 05-MAY-16:10 | 181.12 | 21-MAY-13:00 |
June | 1680.92 | 01-JUN-07:10 | 1578.50 | 01-JUN-07:10 | 1853.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4359.75 | 13-JUN-16:10 | 327.87 | 25-JUN-20:55 |
July | 1680.92 | 01-JUL-07:10 | 1578.50 | 01-JUL-07:10 | 1853.89 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3560.20 | 26-JUL-17:00 | 258.43 | 02-JUL-14:00 |
August | 1680.92 | 01-AUG-07:10 | 1578.50 | 01-AUG-07:10 | 1853.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3594.88 | 09-AUG-16:10 | 306.20 | 20-AUG-10:50 |
September | 1680.92 | 01-SEP-07:10 | 1578.50 | 01-SEP-07:10 | 1853.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3201.84 | 12-SEP-12:00 | 430.49 | 15-SEP-17:00 |
October | 1680.92 | 02-OCT-07:10 | 1578.50 | 02-OCT-07:10 | 1853.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3080.34 | 04-OCT-12:00 | 364.82 | 30-OCT-17:00 |
November | 1680.92 | 01-NOV-07:10 | 1578.50 | 01-NOV-07:10 | 1853.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2899.66 | 10-NOV-12:10 | 666.29 | 27-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1578.50 | 01-DEC-08:09 | 1853.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2877.97 | 26-DEC-13:00 | 2012.41 | 21-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1578.50 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 2877.97 | 181.12 | |||||
Maximum of Months | 1680.92 | 1578.50 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 4692.48 | 2012.41 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 10686.44 | 02-JAN-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2057.31 | 31-JAN-16:10 | 4943.56 | 07-JAN-04:55 |
February | 3955.50 | 01-FEB-08:09 | 10686.44 | 01-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3181.92 | 28-FEB-16:05 | 1419.30 | 01-FEB-07:10 |
March | 3955.50 | 01-MAR-08:09 | 10686.44 | 01-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4818.05 | 19-MAR-16:00 | 1166.91 | 14-MAR-22:00 |
April | 3955.50 | 01-APR-07:10 | 10092.75 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3303.95 | 11-APR-16:00 | 1001.52 | 14-APR-16:00 |
May | 3955.50 | 01-MAY-07:10 | 10092.75 | 05-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5657.62 | 06-MAY-15:10 | 1855.67 | 08-MAY-22:00 |
June | 3955.50 | 01-JUN-07:10 | 9795.91 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4531.02 | 16-JUN-15:30 | 2179.97 | 20-JUN-23:00 |
July | 3955.50 | 01-JUL-07:10 | 9795.91 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2779.65 | 13-JUL-16:00 | 1512.27 | 19-JUL-19:00 |
August | 3955.50 | 01-AUG-07:10 | 10092.75 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3174.55 | 09-AUG-16:00 | 1823.18 | 23-AUG-19:52 |
September | 3955.50 | 01-SEP-07:10 | 9795.91 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3225.99 | 10-SEP-14:58 | 2921.37 | 15-SEP-17:00 |
October | 3955.50 | 02-OCT-07:10 | 10092.75 | 23-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2807.72 | 29-OCT-13:00 | 1322.12 | 30-OCT-16:20 |
November | 3955.50 | 01-NOV-07:10 | 11102.03 | 07-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1462.44 | 04-NOV-15:10 | 1242.39 | 25-NOV-08:00 |
December | 3955.50 | 01-DEC-08:09 | 12111.30 | 18-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1321.98 | 13-DEC-16:10 | 1899.05 | 21-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 9795.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1321.98 | 1001.52 | ||||
Maximum of Months | 3955.50 | 12111.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5657.62 | 4943.56 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 15006.02 | 02-JAN-16:00 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 747.55 | 11-JAN-10:55 | 34824.79 | 07-JAN-04:55 |
February | 9097.65 | 01-FEB-08:09 | 13755.52 | 02-FEB-16:00 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 680.01 | 12-FEB-12:53 | 8066.94 | 01-FEB-07:00 |
March | 9097.65 | 01-MAR-08:09 | 12505.01 | 01-MAR-16:40 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1366.90 | 19-MAR-11:55 | 9681.77 | 14-MAR-22:00 |
April | 9097.65 | 01-APR-07:10 | 12004.81 | 01-APR-06:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1133.07 | 17-APR-09:43 | 7768.73 | 14-APR-16:00 |
May | 9097.65 | 01-MAY-07:10 | 12505.01 | 17-MAY-07:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3394.72 | 01-MAY-13:53 | 15653.73 | 08-MAY-22:00 |
June | 9097.65 | 01-JUN-07:10 | 12505.01 | 20-JUN-07:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 616.10 | 18-JUN-13:55 | 17513.94 | 20-JUN-23:00 |
July | 9097.65 | 01-JUL-07:10 | 12505.01 | 11-JUL-07:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 481.82 | 27-JUL-16:55 | 18118.00 | 03-JUL-13:00 |
August | 9097.65 | 01-AUG-07:10 | 12505.01 | 08-AUG-07:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1450.35 | 06-AUG-11:55 | 20866.85 | 25-AUG-11:00 |
September | 9097.65 | 01-SEP-07:10 | 12004.81 | 01-SEP-06:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1201.25 | 22-SEP-15:55 | 19586.14 | 15-SEP-17:00 |
October | 9097.65 | 02-OCT-07:10 | 12505.01 | 11-OCT-15:00 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 867.12 | 06-OCT-10:53 | 14140.10 | 11-OCT-13:00 |
November | 9097.65 | 01-NOV-07:10 | 15006.02 | 06-NOV-16:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 459.17 | 17-NOV-18:55 | 9181.81 | 25-NOV-08:70 |
December | 9097.65 | 01-DEC-08:09 | 15006.02 | 01-DEC-16:00 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 598.37 | 29-DEC-18:55 | 13603.48 | 20-DEC-08:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 12004.81 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 459.17 | 7768.73 | |||||
Maximum of Months | 9097.65 | 15006.02 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 3394.72 | 34824.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20644.08 | 17-JAN-00:01 | 0.00 | 3689.95 | 4885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.52 |
February | 20437.45 | 21-FEB-00:01 | 0.00 | 3689.95 | 4885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.21 |
March | 18608.11 | 06-MAR-00:01 | 0.00 | 3689.95 | 4885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.32 |
April | 18069.84 | 23-APR-23:01 | 0.00 | 3689.95 | 4885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.58 |
May | 18326.30 | 14-MAY-23:01 | 0.00 | 3689.95 | 4885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.26 |
June | 18207.25 | 20-JUN-00:23 | 0.00 | 1106.98 | 1465.64 | 0.00 | 0.00 | 0.00 | 0.00 | 16.34 | 0.00 |
July | 20560.60 | 16-JUL-23:01 | 0.00 | 3689.95 | 4885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.09 |
August | 18068.03 | 29-AUG-00:23 | 0.00 | 1106.98 | 1465.64 | 0.00 | 0.00 | 0.00 | 0.00 | 20.13 | 0.00 |
September | 18079.11 | 25-SEP-04:23 | 0.00 | 1106.98 | 1465.64 | 0.00 | 0.00 | 0.00 | 0.00 | 21.76 | 0.00 |
October | 17924.25 | 07-OCT-18:23 | 0.00 | 1106.98 | 1465.64 | 0.00 | 0.00 | 0.00 | 0.00 | 70.59 | 0.00 |
November | 18762.58 | 05-NOV-23:01 | 0.00 | 3689.95 | 4885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.25 |
December | 19226.75 | 04-DEC-00:01 | 0.00 | 3689.95 | 4885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17924.25 | 0.00 | 1106.98 | 1465.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20644.08 | 0.00 | 3689.95 | 4885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 70.59 | 96.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 69975.19 | 16-JAN-16:33 | 0.00 | 5699.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 639.78 | 0.00 |
February | 64770.31 | 20-FEB-16:53 | 0.00 | 5699.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 841.76 | 0.00 |
March | 63132.48 | 19-MAR-14:22 | 0.00 | 4749.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3360.57 | 0.00 |
April | 61095.22 | 23-APR-13:43 | 0.00 | 3324.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1518.27 | 0.00 |
May | 61189.25 | 29-MAY-17:33 | 0.00 | 5699.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1269.80 | 0.00 |
June | 58317.41 | 25-JUN-14:02 | 0.00 | 3324.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.61 | 0.00 |
July | 61804.17 | 14-JUL-17:06 | 0.00 | 7124.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 490.08 | 0.00 |
August | 59165.72 | 13-AUG-16:42 | 0.00 | 5224.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.69 | 0.00 |
September | 61019.68 | 10-SEP-10:13 | 0.00 | 2849.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 667.61 | 0.00 |
October | 59992.75 | 09-OCT-14:02 | 0.00 | 3324.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 514.45 | 0.00 |
November | 66205.72 | 05-NOV-14:53 | 0.00 | 3799.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.77 | 0.00 |
December | 65329.45 | 24-DEC-15:32 | 0.00 | 4749.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 58317.41 | 0.00 | 2849.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.69 | 0.00 | |
Maximum of Months | 69975.19 | 0.00 | 7124.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3360.57 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 2000.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1499.84 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 4001.60 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2276.87 |
March | 0.00 | 01-MAR-00:05 | 0.00 | 4001.60 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3369.20 |
April | 0.00 | 01-APR-00:05 | 0.00 | 4001.60 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2933.91 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1194.52 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3528.55 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2773.32 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4056.62 |
September | 0.00 | 01-SEP-00:03 | 0.00 | 6002.41 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2166.12 |
October | 0.00 | 01-OCT-00:05 | 0.00 | 4001.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1068.68 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1423.08 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 4001.60 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2051.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 2000.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1068.68 | |
Maximum of Months | 0.00 | 0.00 | 6002.41 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4056.62 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.668622E+11 | 57113.82 | 03-JAN-16:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.628439E+11 | 58020.07 | 03-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.744511E+11 | 56487.15 | 09-MAR-16:40 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.731610E+11 | 58263.54 | 17-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.764095E+11 | 61088.33 | 06-MAY-14:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.764659E+11 | 60920.08 | 16-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.684759E+11 | 55435.85 | 19-JUL-14:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.727885E+11 | 56087.89 | 11-AUG-15:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.687612E+11 | 57054.88 | 13-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.673458E+11 | 55778.57 | 04-OCT-15:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.649587E+11 | 57765.56 | 20-NOV-16:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.661863E+11 | 57522.32 | 13-DEC-16:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.838710E+12 | 0.00 | ||||
Minimum of Months | 0.628439E+11 | 55435.85 | 0.00 | 0.00 | ||
Maximum of Months | 0.764659E+11 | 61088.33 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.243994E+11 | 0.832971E+10 | 0.113456E+11 | 0.00 | 0.590783E+10 | 0.00 | 0.00 | 0.149954E+11 | 0.00 | 0.00 | 0.00 | 0.188424E+10 | 0.00 |
February | 0.219401E+11 | 0.738555E+10 | 0.104160E+11 | 0.00 | 0.599912E+10 | 0.00 | 0.00 | 0.153958E+11 | 0.00 | 0.00 | 0.00 | 0.170739E+10 | 0.00 |
March | 0.248434E+11 | 0.788118E+10 | 0.121559E+11 | 0.00 | 0.754451E+10 | 0.00 | 0.00 | 0.201149E+11 | 0.00 | 0.00 | 0.00 | 0.191115E+10 | 0.00 |
April | 0.232036E+11 | 0.741276E+10 | 0.113034E+11 | 0.00 | 0.814385E+10 | 0.00 | 0.00 | 0.212808E+11 | 0.00 | 0.00 | 0.00 | 0.181661E+10 | 0.00 |
May | 0.241587E+11 | 0.750392E+10 | 0.117471E+11 | 0.00 | 0.833156E+10 | 0.00 | 0.00 | 0.227990E+11 | 0.00 | 0.00 | 0.00 | 0.186930E+10 | 0.00 |
June | 0.239470E+11 | 0.716125E+10 | 0.117048E+11 | 0.00 | 0.829632E+10 | 0.00 | 0.00 | 0.235402E+11 | 0.00 | 0.00 | 0.00 | 0.181631E+10 | 0.00 |
July | 0.235950E+11 | 0.747038E+10 | 0.113456E+11 | 0.00 | 0.659892E+10 | 0.00 | 0.00 | 0.176254E+11 | 0.00 | 0.00 | 0.00 | 0.184057E+10 | 0.00 |
August | 0.245750E+11 | 0.758356E+10 | 0.121485E+11 | 0.00 | 0.686532E+10 | 0.00 | 0.00 | 0.197356E+11 | 0.00 | 0.00 | 0.00 | 0.188045E+10 | 0.00 |
September | 0.231050E+11 | 0.756367E+10 | 0.112960E+11 | 0.00 | 0.663983E+10 | 0.00 | 0.00 | 0.183489E+11 | 0.00 | 0.00 | 0.00 | 0.180784E+10 | 0.00 |
October | 0.236660E+11 | 0.805724E+10 | 0.113530E+11 | 0.00 | 0.605745E+10 | 0.00 | 0.00 | 0.163486E+11 | 0.00 | 0.00 | 0.00 | 0.186345E+10 | 0.00 |
November | 0.233636E+11 | 0.801955E+10 | 0.109019E+11 | 0.00 | 0.568167E+10 | 0.00 | 0.00 | 0.151819E+11 | 0.00 | 0.00 | 0.00 | 0.181015E+10 | 0.00 |
December | 0.246104E+11 | 0.839390E+10 | 0.113456E+11 | 0.00 | 0.565969E+10 | 0.00 | 0.00 | 0.142947E+11 | 0.00 | 0.00 | 0.00 | 0.188198E+10 | 0.00 |
Annual Sum or Average | 0.285407E+12 | 0.927627E+11 | 0.137063E+12 | 0.00 | 0.817261E+11 | 0.00 | 0.00 | 0.219661E+12 | 0.00 | 0.00 | 0.00 | 0.220894E+11 | 0.00 |
Minimum of Months | 0.219401E+11 | 0.716125E+10 | 0.104160E+11 | 0.00 | 0.565969E+10 | 0.00 | 0.00 | 0.142947E+11 | 0.00 | 0.00 | 0.00 | 0.170739E+10 | 0.00 |
Maximum of Months | 0.248434E+11 | 0.839390E+10 | 0.121559E+11 | 0.00 | 0.833156E+10 | 0.00 | 0.00 | 0.235402E+11 | 0.00 | 0.00 | 0.00 | 0.191115E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 27270.96 | 02-JAN-16:00 | 6986.42 | 01-JAN-06:10 | 10054.01 | 02-JAN-08:09 | 0.00 | 5337.30 | 05-JAN-14:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 26020.46 | 02-FEB-16:00 | 6986.42 | 01-FEB-06:10 | 10054.01 | 01-FEB-08:09 | 0.00 | 5573.96 | 28-FEB-14:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 24769.96 | 01-MAR-16:00 | 6986.42 | 01-MAR-06:10 | 10054.01 | 01-MAR-08:09 | 0.00 | 5748.40 | 20-MAR-15:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 22628.92 | 21-APR-07:10 | 6986.42 | 01-APR-05:10 | 10054.01 | 01-APR-07:10 | 0.00 | 5829.24 | 18-APR-15:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 23879.42 | 17-MAY-07:10 | 6986.42 | 01-MAY-05:10 | 10054.01 | 01-MAY-07:10 | 0.00 | 6342.09 | 06-MAY-15:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 23879.42 | 20-JUN-07:10 | 6986.42 | 01-JUN-05:10 | 10054.01 | 01-JUN-07:10 | 0.00 | 6172.17 | 13-JUN-15:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 23879.42 | 11-JUL-07:10 | 6986.42 | 01-JUL-05:10 | 10054.01 | 01-JUL-07:10 | 0.00 | 5439.56 | 14-JUL-14:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 23879.42 | 08-AUG-07:10 | 6986.42 | 01-AUG-05:10 | 10054.01 | 01-AUG-07:10 | 0.00 | 5730.95 | 01-AUG-15:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 22628.92 | 07-SEP-07:10 | 6986.42 | 01-SEP-05:10 | 10054.01 | 01-SEP-07:10 | 0.00 | 5662.88 | 06-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 23879.42 | 11-OCT-15:00 | 6986.42 | 01-OCT-05:10 | 10054.01 | 02-OCT-07:10 | 0.00 | 5524.12 | 04-OCT-15:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 27270.96 | 06-NOV-16:00 | 6986.42 | 01-NOV-05:10 | 10054.01 | 01-NOV-07:10 | 0.00 | 5332.12 | 18-NOV-13:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 27862.15 | 18-DEC-15:00 | 6986.42 | 01-DEC-17:30 | 10054.01 | 01-DEC-08:09 | 0.00 | 5234.13 | 08-DEC-13:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 22628.92 | 6986.42 | 10054.01 | 0.00 | 5234.13 | 0.00 | 0.00 | |||||
Maximum of Months | 27862.15 | 6986.42 | 10054.01 | 0.00 | 6342.09 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 17520.52 | 04-JAN-12:00 | 0.00 | 0.00 | 0.00 | 1702.66 | 11-JAN-12:30 | 0.00 |
February | 19100.89 | 28-FEB-14:39 | 0.00 | 0.00 | 0.00 | 1702.21 | 01-FEB-12:09 | 0.00 |
March | 20438.55 | 20-MAR-15:39 | 0.00 | 0.00 | 0.00 | 1699.75 | 01-MAR-12:39 | 0.00 |
April | 21112.82 | 18-APR-15:09 | 0.00 | 0.00 | 0.00 | 1695.62 | 01-APR-11:30 | 0.00 |
May | 25088.09 | 06-MAY-15:09 | 0.00 | 0.00 | 0.00 | 1691.25 | 01-MAY-11:30 | 0.00 |
June | 24483.07 | 13-JUN-15:30 | 0.00 | 0.00 | 0.00 | 1687.41 | 01-JUN-11:00 | 0.00 |
July | 17782.92 | 19-JUL-14:00 | 0.00 | 0.00 | 0.00 | 1685.69 | 31-JUL-11:09 | 0.00 |
August | 20566.55 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 1687.90 | 30-AUG-11:00 | 0.00 |
September | 19830.82 | 06-SEP-13:00 | 0.00 | 0.00 | 0.00 | 1691.92 | 30-SEP-11:20 | 0.00 |
October | 18727.41 | 04-OCT-15:09 | 0.00 | 0.00 | 0.00 | 1696.43 | 30-OCT-11:00 | 0.00 |
November | 16843.03 | 18-NOV-13:09 | 0.00 | 0.00 | 0.00 | 1700.24 | 30-NOV-12:30 | 0.00 |
December | 16236.33 | 12-DEC-12:00 | 0.00 | 0.00 | 0.00 | 1702.44 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 16236.33 | 0.00 | 0.00 | 0.00 | 1685.69 | 0.00 | ||
Maximum of Months | 25088.09 | 0.00 | 0.00 | 0.00 | 1702.66 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 57113.82 | 03-JAN-16:00 | 26020.46 | 10054.01 | 0.00 | 0.00 | 5198.76 | 0.00 | 0.00 | 14263.13 | 0.00 |
February | 58020.07 | 03-FEB-16:00 | 26020.46 | 10054.01 | 0.00 | 0.00 | 5198.76 | 0.00 | 0.00 | 15169.55 | 0.00 |
March | 56487.15 | 09-MAR-16:40 | 22628.92 | 10054.01 | 0.00 | 0.00 | 5297.05 | 0.00 | 0.00 | 16930.53 | 0.00 |
April | 58263.54 | 17-APR-15:00 | 20487.88 | 10054.01 | 0.00 | 0.00 | 5714.90 | 0.00 | 0.00 | 20431.67 | 0.00 |
May | 61088.33 | 06-MAY-14:00 | 19573.35 | 10054.01 | 0.00 | 0.00 | 6133.57 | 0.00 | 0.00 | 23658.41 | 0.00 |
June | 60920.08 | 16-JUN-15:00 | 20487.88 | 10054.01 | 0.00 | 0.00 | 6022.66 | 0.00 | 0.00 | 22782.45 | 0.00 |
July | 55435.85 | 19-JUL-14:50 | 20582.62 | 10054.01 | 0.00 | 0.00 | 5421.79 | 0.00 | 0.00 | 17712.92 | 0.00 |
August | 56087.89 | 11-AUG-15:30 | 18346.84 | 10054.01 | 0.00 | 0.00 | 5716.29 | 0.00 | 0.00 | 20397.54 | 0.00 |
September | 57054.88 | 13-SEP-15:00 | 21738.38 | 10054.01 | 0.00 | 0.00 | 5436.76 | 0.00 | 0.00 | 18251.63 | 0.00 |
October | 55778.57 | 04-OCT-15:50 | 20487.88 | 10054.01 | 0.00 | 0.00 | 5442.06 | 0.00 | 0.00 | 18219.75 | 0.00 |
November | 57765.56 | 20-NOV-16:00 | 27270.96 | 10054.01 | 0.00 | 0.00 | 5198.76 | 0.00 | 0.00 | 13665.20 | 0.00 |
December | 57522.32 | 13-DEC-16:00 | 27270.96 | 10054.01 | 0.00 | 0.00 | 5198.76 | 0.00 | 0.00 | 13421.40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 55435.85 | 18346.84 | 10054.01 | 0.00 | 0.00 | 5198.76 | 0.00 | 0.00 | 13421.40 | 0.00 | |
Maximum of Months | 61088.33 | 27270.96 | 10054.01 | 0.00 | 0.00 | 6133.57 | 0.00 | 0.00 | 23658.41 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 62.33 | 24.65 | 1.83 | 24.65 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 64.33 | 24.65 | 2.50 | 24.64 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 81.17 | 24.71 | 3.83 | 24.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 80.00 | 24.72 | 4.17 | 24.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 80.67 | 24.74 | 4.00 | 24.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 83.50 | 24.74 | 4.33 | 24.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 78.83 | 24.67 | 4.00 | 24.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 82.00 | 24.65 | 4.17 | 24.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 78.17 | 24.70 | 4.17 | 24.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 70.83 | 24.64 | 3.67 | 24.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 64.83 | 24.61 | 3.50 | 24.61 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 49.67 | 24.66 | 1.17 | 24.66 |
Annual Sum or Average | 0.00 | 0.00 | 876.33 | 24.68 | 41.33 | 24.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 49.67 | 24.61 | 1.17 | 24.61 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 83.50 | 24.74 | 4.33 | 24.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 27.64 | 0.00 | 27.64 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 27.68 | 0.17 | 27.67 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 27.70 | 0.17 | 27.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 | 27.62 | 0.67 | 27.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 32.33 | 27.62 | 0.00 | 27.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 27.62 | 0.50 | 27.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 31.17 | 27.56 | 0.33 | 27.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 27.58 | 0.50 | 27.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 27.60 | 0.17 | 27.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 27.59 | 0.00 | 27.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 27.60 | 1.17 | 27.59 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 27.67 | 0.00 | 27.67 |
Annual Sum or Average | 0.00 | 0.00 | 293.33 | 27.62 | 3.67 | 27.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 27.56 | 0.00 | 27.56 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 | 27.70 | 1.17 | 27.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.17 | 23.90 | 299.67 | 23.91 | 16.17 | 23.91 |
February | 9.83 | 23.90 | 276.00 | 23.91 | 9.83 | 23.91 |
March | 27.50 | 23.90 | 324.00 | 23.91 | 27.50 | 23.91 |
April | 58.50 | 23.90 | 300.00 | 23.91 | 58.50 | 23.91 |
May | 141.33 | 23.90 | 312.00 | 23.91 | 141.33 | 23.91 |
June | 132.17 | 23.91 | 312.00 | 23.91 | 132.17 | 23.91 |
July | 49.50 | 23.90 | 300.00 | 23.91 | 49.50 | 23.91 |
August | 157.17 | 23.90 | 324.00 | 23.91 | 157.17 | 23.91 |
September | 101.17 | 23.90 | 300.00 | 23.91 | 101.17 | 23.91 |
October | 100.00 | 23.90 | 300.00 | 23.91 | 100.00 | 23.91 |
November | 57.67 | 23.90 | 288.00 | 23.91 | 57.67 | 23.91 |
December | 20.17 | 23.90 | 299.83 | 23.91 | 20.17 | 23.91 |
Annual Sum or Average | 871.17 | 23.90 | 3635.50 | 23.91 | 871.17 | 23.91 |
Minimum of Months | 9.83 | 23.90 | 276.00 | 23.91 | 9.83 | 23.91 |
Maximum of Months | 157.17 | 23.91 | 324.00 | 23.91 | 157.17 | 23.91 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 294.67 | 26.71 | 300.00 | 26.71 | 294.67 | 26.71 |
February | 272.17 | 26.72 | 276.00 | 26.72 | 272.17 | 26.72 |
March | 324.00 | 26.72 | 324.00 | 26.72 | 324.00 | 26.72 |
April | 300.00 | 26.72 | 300.00 | 26.72 | 300.00 | 26.72 |
May | 312.00 | 26.71 | 312.00 | 26.71 | 312.00 | 26.71 |
June | 312.00 | 26.71 | 312.00 | 26.71 | 312.00 | 26.71 |
July | 296.00 | 26.72 | 300.00 | 26.72 | 296.00 | 26.72 |
August | 324.00 | 26.72 | 324.00 | 26.72 | 324.00 | 26.72 |
September | 299.83 | 26.72 | 300.00 | 26.72 | 299.83 | 26.72 |
October | 300.00 | 26.72 | 300.00 | 26.72 | 300.00 | 26.72 |
November | 288.00 | 26.72 | 288.00 | 26.72 | 288.00 | 26.72 |
December | 298.67 | 26.70 | 300.00 | 26.70 | 298.67 | 26.70 |
Annual Sum or Average | 3621.33 | 26.72 | 3636.00 | 26.72 | 3621.33 | 26.72 |
Minimum of Months | 272.17 | 26.70 | 276.00 | 26.70 | 272.17 | 26.70 |
Maximum of Months | 324.00 | 26.72 | 324.00 | 26.72 | 324.00 | 26.72 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 30.50 | 300.00 | 30.50 | 300.00 | 30.50 |
February | 276.00 | 31.15 | 276.00 | 31.15 | 276.00 | 31.15 |
March | 324.00 | 31.65 | 324.00 | 31.65 | 324.00 | 31.65 |
April | 300.00 | 31.87 | 300.00 | 31.87 | 300.00 | 31.87 |
May | 312.00 | 31.81 | 312.00 | 31.81 | 312.00 | 31.81 |
June | 312.00 | 31.93 | 312.00 | 31.93 | 312.00 | 31.93 |
July | 300.00 | 30.52 | 300.00 | 30.52 | 300.00 | 30.52 |
August | 324.00 | 30.69 | 324.00 | 30.69 | 324.00 | 30.69 |
September | 300.00 | 30.74 | 300.00 | 30.74 | 300.00 | 30.74 |
October | 300.00 | 30.18 | 300.00 | 30.18 | 300.00 | 30.18 |
November | 288.00 | 30.23 | 288.00 | 30.23 | 288.00 | 30.23 |
December | 300.00 | 30.16 | 300.00 | 30.16 | 300.00 | 30.16 |
Annual Sum or Average | 3636.00 | 30.96 | 3636.00 | 30.96 | 3636.00 | 30.96 |
Minimum of Months | 276.00 | 30.16 | 276.00 | 30.16 | 276.00 | 30.16 |
Maximum of Months | 324.00 | 31.93 | 324.00 | 31.93 | 324.00 | 31.93 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.178451E+11 | 0.405967E+10 | 515.09 | 0.132724E+11 | 0.457266E+10 | 0.00 | 1.00 | 02-JAN-00:01 | 0.00 | 01-JAN-00:10 | 34551.76 | 02-JAN-00:01 | 22238.80 | 17-JAN-00:01 | 16228.77 | 02-JAN-00:05 | 7078.73 | 02-JAN-00:01 | 0.00 | 01-JAN-00:10 |
February | 0.171678E+11 | 0.396120E+10 | 479.51 | 0.128780E+11 | 0.428980E+10 | 0.00 | 1.00 | 01-FEB-12:35 | 0.00 | 01-FEB-00:33 | 33532.71 | 06-FEB-00:01 | 22816.53 | 22-FEB-18:08 | 14524.16 | 06-FEB-00:06 | 6987.49 | 06-FEB-00:01 | 0.00 | 01-FEB-00:05 |
March | 0.219733E+11 | 0.510965E+10 | 566.85 | 0.159685E+11 | 0.600480E+10 | 0.00 | 1.00 | 01-MAR-12:10 | 0.00 | 01-MAR-00:33 | 33738.38 | 26-MAR-23:01 | 21138.74 | 25-MAR-17:08 | 14972.30 | 26-MAR-23:07 | 7124.32 | 26-MAR-23:01 | 0.00 | 01-MAR-00:05 |
April | 0.224390E+11 | 0.522288E+10 | 530.94 | 0.153782E+11 | 0.706077E+10 | 0.00 | 1.00 | 01-APR-12:30 | 0.00 | 01-APR-00:13 | 34255.34 | 09-APR-23:01 | 20534.82 | 15-APR-17:06 | 16873.45 | 09-APR-23:05 | 7203.32 | 30-APR-23:01 | 0.00 | 01-APR-00:05 |
May | 0.249970E+11 | 0.577202E+10 | 551.65 | 0.159866E+11 | 0.901041E+10 | 0.00 | 1.00 | 01-MAY-00:23 | 0.00 | 01-MAY-00:12 | 33934.53 | 21-MAY-23:04 | 20587.05 | 31-MAY-01:03 | 21133.08 | 21-MAY-23:07 | 7230.35 | 07-MAY-23:01 | 0.00 | 01-MAY-00:10 |
June | 0.254031E+11 | 0.588074E+10 | 554.57 | 0.162980E+11 | 0.910512E+10 | 0.00 | 1.00 | 01-JUN-11:20 | 0.00 | 01-JUN-00:13 | 34447.82 | 25-JUN-23:01 | 20675.19 | 20-JUN-00:23 | 18402.92 | 04-JUN-23:06 | 7183.90 | 11-JUN-23:01 | 0.00 | 01-JUN-00:10 |
July | 0.202662E+11 | 0.456853E+10 | 523.13 | 0.140904E+11 | 0.617581E+10 | 0.00 | 1.00 | 01-JUL-00:25 | 0.00 | 01-JUL-00:15 | 34184.09 | 02-JUL-23:01 | 22423.10 | 16-JUL-23:01 | 15561.25 | 02-JUL-23:05 | 7102.34 | 02-JUL-23:01 | 0.00 | 01-JUL-00:10 |
August | 0.240325E+11 | 0.540099E+10 | 562.38 | 0.151296E+11 | 0.890290E+10 | 0.00 | 1.00 | 01-AUG-08:40 | 0.00 | 01-AUG-00:13 | 34823.74 | 20-AUG-23:01 | 20649.90 | 29-AUG-00:23 | 20238.68 | 06-AUG-23:06 | 7176.73 | 27-AUG-23:01 | 0.00 | 01-AUG-00:10 |
September | 0.213148E+11 | 0.480821E+10 | 524.03 | 0.139356E+11 | 0.737914E+10 | 0.00 | 1.00 | 01-SEP-10:20 | 0.00 | 01-SEP-00:13 | 34527.05 | 24-SEP-23:01 | 20599.67 | 25-SEP-04:23 | 18483.44 | 24-SEP-23:04 | 7180.30 | 04-SEP-23:01 | 0.00 | 01-SEP-00:03 |
October | 0.201696E+11 | 0.449027E+10 | 517.70 | 0.131581E+11 | 0.701142E+10 | 0.00 | 1.00 | 01-OCT-23:01 | 0.00 | 01-OCT-00:05 | 34823.74 | 01-OCT-23:02 | 20456.22 | 07-OCT-18:23 | 18501.68 | 29-OCT-23:04 | 7156.99 | 15-OCT-23:01 | 0.00 | 01-OCT-00:05 |
November | 0.185152E+11 | 0.414295E+10 | 492.18 | 0.126870E+11 | 0.582823E+10 | 0.00 | 1.00 | 01-NOV-00:25 | 0.00 | 01-NOV-00:15 | 34314.60 | 13-NOV-00:02 | 20534.28 | 04-NOV-17:08 | 18123.29 | 13-NOV-00:04 | 7100.30 | 13-NOV-00:01 | 0.00 | 01-NOV-00:10 |
December | 0.173574E+11 | 0.391395E+10 | 507.07 | 0.126715E+11 | 0.468593E+10 | 0.00 | 1.00 | 01-DEC-12:30 | 0.00 | 01-DEC-00:10 | 34442.41 | 11-DEC-00:01 | 20820.23 | 04-DEC-00:01 | 16047.29 | 11-DEC-00:06 | 7055.24 | 26-DEC-00:01 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.251481E+12 | 0.573311E+11 | 6325.10 | 0.171454E+12 | 0.800270E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.171678E+11 | 0.391395E+10 | 479.51 | 0.126715E+11 | 0.428980E+10 | 0.00 | 1.00 | 0.00 | 33532.71 | 20456.22 | 14524.16 | 6987.49 | 0.00 | |||||||
Maximum of Months | 0.254031E+11 | 0.588074E+10 | 566.85 | 0.162980E+11 | 0.910512E+10 | 0.00 | 1.00 | 0.00 | 34823.74 | 22816.53 | 21133.08 | 7230.35 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.401994E+11 | 0.109357E+11 | 427.78 | 0.281768E+11 | 0.120226E+11 | 0.00 | 1.00 | 01-JAN-12:43 | 0.00 | 01-JAN-00:10 | 101614.98 | 09-JAN-00:01 | 78210.89 | 16-JAN-15:13 | 41679.61 | 09-JAN-00:01 | 24559.69 | 08-JAN-12:13 | 0.00 | 01-JAN-00:10 |
February | 0.417661E+11 | 0.114346E+11 | 421.82 | 0.295816E+11 | 0.121845E+11 | 0.00 | 1.00 | 01-FEB-18:08 | 0.00 | 01-FEB-00:05 | 98239.18 | 06-FEB-00:01 | 74673.57 | 26-FEB-14:32 | 39491.35 | 06-FEB-00:01 | 25259.69 | 26-FEB-14:32 | 0.00 | 01-FEB-00:05 |
March | 0.546689E+11 | 0.150053E+11 | 527.99 | 0.375902E+11 | 0.170787E+11 | 0.00 | 1.00 | 01-MAR-18:10 | 0.00 | 01-MAR-00:05 | 97805.87 | 05-MAR-09:23 | 74704.00 | 19-MAR-13:42 | 35805.86 | 26-MAR-08:43 | 25633.91 | 19-MAR-13:42 | 0.00 | 01-MAR-00:05 |
April | 0.589171E+11 | 0.160579E+11 | 554.83 | 0.381259E+11 | 0.207912E+11 | 0.00 | 1.00 | 01-APR-10:10 | 0.00 | 01-APR-00:13 | 100760.54 | 02-APR-23:01 | 72202.60 | 23-APR-13:43 | 42237.71 | 02-APR-23:01 | 25706.71 | 02-APR-15:02 | 0.00 | 01-APR-00:05 |
May | 0.630714E+11 | 0.170269E+11 | 560.47 | 0.377623E+11 | 0.253091E+11 | 0.00 | 1.00 | 01-MAY-08:40 | 0.00 | 01-MAY-00:23 | 101384.31 | 07-MAY-23:01 | 71665.15 | 07-MAY-13:02 | 44910.05 | 21-MAY-08:43 | 25864.50 | 14-MAY-14:22 | 0.00 | 01-MAY-00:10 |
June | 0.656059E+11 | 0.176594E+11 | 564.82 | 0.394925E+11 | 0.261133E+11 | 0.00 | 1.00 | 01-JUN-01:20 | 0.00 | 01-JUN-00:25 | 101433.67 | 26-JUN-17:42 | 67665.81 | 18-JUN-14:22 | 41028.34 | 11-JUN-23:01 | 26360.05 | 18-JUN-13:42 | 0.00 | 01-JUN-00:10 |
July | 0.488355E+11 | 0.130569E+11 | 516.83 | 0.315469E+11 | 0.172886E+11 | 0.00 | 1.00 | 01-JUL-17:08 | 0.00 | 01-JUL-00:10 | 98005.05 | 02-JUL-09:23 | 70380.36 | 14-JUL-17:06 | 35492.50 | 02-JUL-09:23 | 25326.99 | 26-JUL-17:06 | 0.00 | 01-JUL-00:10 |
August | 0.544323E+11 | 0.143346E+11 | 500.64 | 0.311163E+11 | 0.233160E+11 | 0.00 | 1.00 | 01-AUG-10:30 | 0.00 | 01-AUG-00:10 | 104031.96 | 06-AUG-09:13 | 67860.98 | 27-AUG-15:43 | 50210.18 | 06-AUG-09:13 | 26176.20 | 06-AUG-12:33 | 0.00 | 01-AUG-00:10 |
September | 0.510009E+11 | 0.135407E+11 | 503.60 | 0.307573E+11 | 0.202436E+11 | 0.00 | 1.00 | 01-SEP-12:10 | 0.00 | 01-SEP-00:07 | 100817.00 | 17-SEP-09:33 | 70724.05 | 10-SEP-13:32 | 41388.45 | 17-SEP-09:33 | 25542.44 | 24-SEP-12:53 | 0.00 | 01-SEP-00:03 |
October | 0.448873E+11 | 0.118584E+11 | 470.21 | 0.267521E+11 | 0.181352E+11 | 0.00 | 1.00 | 01-OCT-09:23 | 0.00 | 01-OCT-00:15 | 102943.17 | 01-OCT-23:01 | 69710.63 | 08-OCT-14:23 | 42718.57 | 01-OCT-23:01 | 25417.69 | 29-OCT-12:43 | 0.00 | 01-OCT-00:05 |
November | 0.414046E+11 | 0.110389E+11 | 432.61 | 0.263060E+11 | 0.150986E+11 | 0.00 | 1.00 | 01-NOV-17:08 | 0.00 | 01-NOV-00:10 | 99348.65 | 11-NOV-09:23 | 72858.22 | 05-NOV-14:53 | 38156.81 | 11-NOV-09:23 | 24914.97 | 11-NOV-14:02 | 0.00 | 01-NOV-00:10 |
December | 0.384300E+11 | 0.103808E+11 | 404.44 | 0.260526E+11 | 0.123774E+11 | 0.00 | 1.00 | 03-DEC-09:23 | 0.00 | 01-DEC-00:05 | 99022.10 | 24-DEC-10:13 | 75504.20 | 03-DEC-14:02 | 39185.14 | 24-DEC-10:13 | 24746.16 | 31-DEC-13:13 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.603219E+12 | 0.162330E+12 | 5886.03 | 0.383261E+12 | 0.219959E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.384300E+11 | 0.103808E+11 | 404.44 | 0.260526E+11 | 0.120226E+11 | 0.00 | 1.00 | 0.00 | 97805.87 | 67665.81 | 35492.50 | 24559.69 | 0.00 | |||||||
Maximum of Months | 0.656059E+11 | 0.176594E+11 | 564.82 | 0.394925E+11 | 0.261133E+11 | 0.00 | 1.00 | 0.00 | 104031.96 | 78210.89 | 50210.18 | 26360.05 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 59.81 | 21.08 | 38.72 | 197.67 | 34.93 | 0.00 | 0.00 | 0.00 |
February | 65.49 | 23.12 | 42.37 | 224.10 | 26.19 | 0.00 | 0.00 | 0.00 |
March | 73.34 | 28.86 | 44.47 | 257.84 | 17.92 | 0.00 | 0.00 | 0.00 |
April | 73.53 | 27.95 | 45.58 | 258.34 | 8.07 | 0.00 | 0.00 | 0.00 |
May | 62.72 | 18.48 | 44.23 | 226.54 | 9.53 | 0.17 | 0.00 | 0.00 |
June | 67.95 | 23.32 | 44.63 | 242.36 | 10.35 | 0.00 | 0.00 | 0.00 |
July | 57.99 | 13.61 | 44.38 | 193.97 | 19.19 | 0.00 | 0.00 | 0.00 |
August | 63.04 | 18.58 | 44.46 | 197.78 | 14.89 | 0.00 | 0.00 | 0.00 |
September | 58.89 | 16.16 | 42.73 | 198.19 | 15.85 | 0.00 | 0.00 | 0.00 |
October | 55.40 | 14.17 | 41.23 | 171.93 | 21.49 | 0.00 | 0.00 | 0.00 |
November | 54.03 | 14.65 | 39.39 | 173.75 | 24.77 | 0.00 | 0.00 | 0.00 |
December | 55.46 | 18.16 | 37.30 | 182.01 | 38.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.26 | 19.81 | 42.45 | 210.18 | 20.13 | 0.17 | 0.00 | 0.00 |
Minimum of Months | 54.03 | 13.61 | 37.30 | 171.93 | 8.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.53 | 28.86 | 45.58 | 258.34 | 38.26 | 0.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 59.81 | 21.08 | 38.72 | 197.67 | 34.93 | 0.00 | 0.00 | 0.00 |
February | 65.49 | 23.12 | 42.37 | 224.10 | 26.19 | 0.00 | 0.00 | 0.00 |
March | 73.34 | 28.86 | 44.47 | 257.84 | 17.92 | 0.00 | 0.00 | 0.00 |
April | 73.53 | 27.95 | 45.58 | 258.34 | 8.07 | 0.00 | 0.00 | 0.00 |
May | 62.72 | 18.48 | 44.23 | 226.54 | 9.53 | 0.17 | 0.00 | 0.00 |
June | 67.95 | 23.32 | 44.63 | 242.36 | 10.35 | 0.00 | 0.00 | 0.00 |
July | 57.99 | 13.61 | 44.38 | 193.97 | 19.19 | 0.00 | 0.00 | 0.00 |
August | 63.04 | 18.58 | 44.46 | 197.78 | 14.89 | 0.00 | 0.00 | 0.00 |
September | 58.89 | 16.16 | 42.73 | 198.19 | 15.85 | 0.00 | 0.00 | 0.00 |
October | 55.40 | 14.17 | 41.23 | 171.93 | 21.49 | 0.00 | 0.00 | 0.00 |
November | 54.03 | 14.65 | 39.39 | 173.75 | 24.77 | 0.00 | 0.00 | 0.00 |
December | 55.46 | 18.16 | 37.30 | 182.01 | 38.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.26 | 19.81 | 42.45 | 210.18 | 20.13 | 0.17 | 0.00 | 0.00 |
Minimum of Months | 54.03 | 13.61 | 37.30 | 171.93 | 8.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.53 | 28.86 | 45.58 | 258.34 | 38.26 | 0.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.83 | 0.00 | 17.83 | 60.51 | 20.31 | 0.00 | 0.00 | 0.00 |
February | 19.02 | 0.00 | 19.02 | 69.46 | 15.14 | 0.00 | 0.00 | 0.00 |
March | 19.54 | 0.01 | 19.53 | 77.17 | 10.22 | 0.00 | 0.00 | 0.00 |
April | 21.79 | 0.68 | 21.11 | 87.77 | 4.65 | 0.00 | 0.00 | 0.00 |
May | 28.43 | 4.10 | 24.33 | 111.67 | 5.51 | 0.17 | 0.00 | 0.00 |
June | 34.95 | 8.42 | 26.54 | 135.06 | 6.05 | 0.00 | 0.00 | 0.00 |
July | 29.42 | 3.82 | 25.60 | 102.15 | 10.91 | 0.00 | 0.00 | 0.00 |
August | 24.30 | 1.74 | 22.56 | 82.72 | 8.69 | 0.00 | 0.00 | 0.00 |
September | 20.11 | 0.05 | 20.05 | 74.06 | 9.28 | 0.00 | 0.00 | 0.00 |
October | 19.32 | 0.00 | 19.32 | 62.14 | 12.62 | 0.00 | 0.00 | 0.00 |
November | 18.28 | 0.00 | 18.28 | 60.82 | 14.50 | 0.00 | 0.00 | 0.00 |
December | 17.32 | 0.00 | 17.32 | 58.08 | 22.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.54 | 1.57 | 20.97 | 81.82 | 11.68 | 0.17 | 0.00 | 0.00 |
Minimum of Months | 17.32 | 0.00 | 17.32 | 58.08 | 4.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.95 | 8.42 | 26.54 | 135.06 | 22.25 | 0.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.83 | 0.00 | 17.83 | 60.51 | 20.31 | 0.00 | 0.00 | 0.00 |
February | 19.02 | 0.00 | 19.02 | 69.46 | 15.14 | 0.00 | 0.00 | 0.00 |
March | 19.54 | 0.01 | 19.53 | 77.16 | 10.22 | 0.00 | 0.00 | 0.00 |
April | 21.79 | 0.68 | 21.11 | 87.77 | 4.65 | 0.00 | 0.00 | 0.00 |
May | 28.43 | 4.10 | 24.33 | 111.67 | 5.51 | 0.17 | 0.00 | 0.00 |
June | 34.95 | 8.42 | 26.54 | 135.06 | 6.05 | 0.00 | 0.00 | 0.00 |
July | 29.42 | 3.82 | 25.60 | 102.14 | 10.91 | 0.00 | 0.00 | 0.00 |
August | 24.30 | 1.74 | 22.56 | 82.71 | 8.69 | 0.00 | 0.00 | 0.00 |
September | 20.11 | 0.05 | 20.05 | 74.05 | 9.28 | 0.00 | 0.00 | 0.00 |
October | 19.32 | 0.00 | 19.32 | 62.14 | 12.62 | 0.00 | 0.00 | 0.00 |
November | 18.28 | 0.00 | 18.28 | 60.82 | 14.50 | 0.00 | 0.00 | 0.00 |
December | 17.32 | 0.00 | 17.32 | 58.08 | 22.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.54 | 1.57 | 20.97 | 81.82 | 11.68 | 0.17 | 0.00 | 0.00 |
Minimum of Months | 17.32 | 0.00 | 17.32 | 58.08 | 4.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.95 | 8.42 | 26.54 | 135.06 | 22.25 | 0.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.56 | 24.19 | 26.38 | 100.47 | 31.55 | 0.00 | 0.00 | 0.00 |
February | 58.18 | 30.09 | 28.09 | 117.80 | 31.69 | 0.00 | 0.00 | 0.00 |
March | 67.48 | 39.46 | 28.02 | 137.16 | 25.77 | 0.00 | 0.00 | 0.00 |
April | 68.17 | 38.03 | 30.14 | 139.54 | 18.02 | 0.00 | 0.00 | 0.00 |
May | 57.18 | 24.74 | 32.44 | 118.45 | 15.80 | 0.00 | 0.00 | 0.00 |
June | 61.81 | 30.47 | 31.34 | 128.03 | 15.25 | 0.00 | 0.00 | 0.00 |
July | 52.07 | 17.18 | 34.89 | 106.13 | 20.23 | 0.00 | 0.00 | 0.00 |
August | 57.44 | 24.54 | 32.90 | 109.72 | 19.47 | 0.00 | 0.00 | 0.00 |
September | 53.14 | 20.55 | 32.59 | 108.07 | 18.75 | 0.00 | 0.00 | 0.00 |
October | 48.63 | 17.19 | 31.44 | 92.80 | 21.13 | 0.00 | 0.00 | 0.00 |
November | 46.33 | 17.45 | 28.88 | 91.55 | 24.97 | 0.00 | 0.00 | 0.00 |
December | 46.88 | 21.02 | 25.86 | 92.97 | 32.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.62 | 25.36 | 30.26 | 111.79 | 22.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 46.33 | 17.18 | 25.86 | 91.55 | 15.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.17 | 39.46 | 34.89 | 139.54 | 32.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.56 | 24.19 | 26.38 | 100.47 | 31.55 | 0.00 | 0.00 | 0.00 |
February | 58.18 | 30.09 | 28.09 | 117.80 | 31.69 | 0.00 | 0.00 | 0.00 |
March | 67.48 | 39.46 | 28.02 | 137.16 | 25.77 | 0.00 | 0.00 | 0.00 |
April | 68.17 | 38.03 | 30.14 | 139.54 | 18.02 | 0.00 | 0.00 | 0.00 |
May | 57.18 | 24.74 | 32.44 | 118.45 | 15.80 | 0.00 | 0.00 | 0.00 |
June | 61.81 | 30.47 | 31.34 | 128.03 | 15.25 | 0.00 | 0.00 | 0.00 |
July | 52.07 | 17.18 | 34.89 | 106.13 | 20.23 | 0.00 | 0.00 | 0.00 |
August | 57.44 | 24.54 | 32.90 | 109.72 | 19.47 | 0.00 | 0.00 | 0.00 |
September | 53.14 | 20.55 | 32.59 | 108.07 | 18.75 | 0.00 | 0.00 | 0.00 |
October | 48.63 | 17.19 | 31.44 | 92.80 | 21.13 | 0.00 | 0.00 | 0.00 |
November | 46.33 | 17.45 | 28.88 | 91.55 | 24.97 | 0.00 | 0.00 | 0.00 |
December | 46.88 | 21.02 | 25.86 | 92.97 | 32.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.62 | 25.36 | 30.26 | 111.79 | 22.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 46.33 | 17.18 | 25.86 | 91.55 | 15.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.17 | 39.46 | 34.89 | 139.54 | 32.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.56 | 24.19 | 26.38 | 100.47 | 31.55 | 0.00 | 0.00 | 0.00 |
February | 58.18 | 30.09 | 28.09 | 117.80 | 31.69 | 0.00 | 0.00 | 0.00 |
March | 67.48 | 39.46 | 28.02 | 137.16 | 25.77 | 0.00 | 0.00 | 0.00 |
April | 68.17 | 38.03 | 30.14 | 139.54 | 18.02 | 0.00 | 0.00 | 0.00 |
May | 57.18 | 24.74 | 32.44 | 118.45 | 15.80 | 0.00 | 0.00 | 0.00 |
June | 61.81 | 30.47 | 31.34 | 128.03 | 15.25 | 0.00 | 0.00 | 0.00 |
July | 52.07 | 17.18 | 34.89 | 106.13 | 20.23 | 0.00 | 0.00 | 0.00 |
August | 57.44 | 24.54 | 32.90 | 109.72 | 19.47 | 0.00 | 0.00 | 0.00 |
September | 53.14 | 20.55 | 32.59 | 108.07 | 18.75 | 0.00 | 0.00 | 0.00 |
October | 48.63 | 17.19 | 31.44 | 92.80 | 21.13 | 0.00 | 0.00 | 0.00 |
November | 46.33 | 17.45 | 28.88 | 91.55 | 24.97 | 0.00 | 0.00 | 0.00 |
December | 46.88 | 21.02 | 25.86 | 92.97 | 32.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.62 | 25.36 | 30.26 | 111.79 | 22.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 46.33 | 17.18 | 25.86 | 91.55 | 15.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.17 | 39.46 | 34.89 | 139.54 | 32.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.56 | 24.19 | 26.38 | 100.47 | 31.55 | 0.00 | 0.00 | 0.00 |
February | 58.18 | 30.09 | 28.09 | 117.80 | 31.69 | 0.00 | 0.00 | 0.00 |
March | 67.48 | 39.46 | 28.02 | 137.16 | 25.77 | 0.00 | 0.00 | 0.00 |
April | 68.17 | 38.03 | 30.14 | 139.54 | 18.02 | 0.00 | 0.00 | 0.00 |
May | 57.18 | 24.74 | 32.44 | 118.45 | 15.80 | 0.00 | 0.00 | 0.00 |
June | 61.81 | 30.47 | 31.34 | 128.03 | 15.25 | 0.00 | 0.00 | 0.00 |
July | 52.07 | 17.18 | 34.89 | 106.13 | 20.23 | 0.00 | 0.00 | 0.00 |
August | 57.44 | 24.54 | 32.90 | 109.72 | 19.47 | 0.00 | 0.00 | 0.00 |
September | 53.14 | 20.55 | 32.59 | 108.07 | 18.75 | 0.00 | 0.00 | 0.00 |
October | 48.63 | 17.19 | 31.44 | 92.80 | 21.13 | 0.00 | 0.00 | 0.00 |
November | 46.33 | 17.45 | 28.88 | 91.55 | 24.97 | 0.00 | 0.00 | 0.00 |
December | 46.88 | 21.02 | 25.86 | 92.97 | 32.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.62 | 25.36 | 30.26 | 111.79 | 22.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 46.33 | 17.18 | 25.86 | 91.55 | 15.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.17 | 39.46 | 34.89 | 139.54 | 32.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.56 | 24.19 | 26.38 | 100.47 | 31.55 | 0.00 | 0.00 | 0.00 |
February | 58.18 | 30.09 | 28.09 | 117.80 | 31.69 | 0.00 | 0.00 | 0.00 |
March | 67.48 | 39.46 | 28.02 | 137.16 | 25.77 | 0.00 | 0.00 | 0.00 |
April | 68.17 | 38.03 | 30.14 | 139.54 | 18.02 | 0.00 | 0.00 | 0.00 |
May | 57.18 | 24.74 | 32.44 | 118.45 | 15.80 | 0.00 | 0.00 | 0.00 |
June | 61.81 | 30.47 | 31.34 | 128.03 | 15.25 | 0.00 | 0.00 | 0.00 |
July | 52.07 | 17.18 | 34.89 | 106.13 | 20.23 | 0.00 | 0.00 | 0.00 |
August | 57.44 | 24.54 | 32.90 | 109.72 | 19.47 | 0.00 | 0.00 | 0.00 |
September | 53.14 | 20.55 | 32.59 | 108.07 | 18.75 | 0.00 | 0.00 | 0.00 |
October | 48.63 | 17.19 | 31.44 | 92.80 | 21.13 | 0.00 | 0.00 | 0.00 |
November | 46.33 | 17.45 | 28.88 | 91.55 | 24.97 | 0.00 | 0.00 | 0.00 |
December | 46.88 | 21.02 | 25.86 | 92.97 | 32.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.62 | 25.36 | 30.26 | 111.79 | 22.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 46.33 | 17.18 | 25.86 | 91.55 | 15.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.17 | 39.46 | 34.89 | 139.54 | 32.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.56 | 24.19 | 26.38 | 100.47 | 31.55 | 0.00 | 0.00 | 0.00 |
February | 58.18 | 30.09 | 28.09 | 117.80 | 31.69 | 0.00 | 0.00 | 0.00 |
March | 67.48 | 39.46 | 28.02 | 137.16 | 25.77 | 0.00 | 0.00 | 0.00 |
April | 68.17 | 38.03 | 30.14 | 139.54 | 18.02 | 0.00 | 0.00 | 0.00 |
May | 57.18 | 24.74 | 32.44 | 118.45 | 15.80 | 0.00 | 0.00 | 0.00 |
June | 61.81 | 30.47 | 31.34 | 128.03 | 15.25 | 0.00 | 0.00 | 0.00 |
July | 52.07 | 17.18 | 34.89 | 106.13 | 20.23 | 0.00 | 0.00 | 0.00 |
August | 57.44 | 24.54 | 32.90 | 109.72 | 19.47 | 0.00 | 0.00 | 0.00 |
September | 53.14 | 20.55 | 32.59 | 108.07 | 18.75 | 0.00 | 0.00 | 0.00 |
October | 48.63 | 17.19 | 31.44 | 92.80 | 21.13 | 0.00 | 0.00 | 0.00 |
November | 46.33 | 17.45 | 28.88 | 91.55 | 24.97 | 0.00 | 0.00 | 0.00 |
December | 46.88 | 21.02 | 25.86 | 92.97 | 32.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.62 | 25.36 | 30.26 | 111.79 | 22.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 46.33 | 17.18 | 25.86 | 91.55 | 15.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.17 | 39.46 | 34.89 | 139.54 | 32.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.56 | 24.19 | 26.38 | 100.47 | 31.55 | 0.00 | 0.00 | 0.00 |
February | 58.18 | 30.09 | 28.09 | 117.80 | 31.69 | 0.00 | 0.00 | 0.00 |
March | 67.48 | 39.46 | 28.02 | 137.16 | 25.77 | 0.00 | 0.00 | 0.00 |
April | 68.17 | 38.03 | 30.14 | 139.54 | 18.02 | 0.00 | 0.00 | 0.00 |
May | 57.18 | 24.74 | 32.44 | 118.45 | 15.80 | 0.00 | 0.00 | 0.00 |
June | 61.81 | 30.47 | 31.34 | 128.03 | 15.25 | 0.00 | 0.00 | 0.00 |
July | 52.07 | 17.18 | 34.89 | 106.13 | 20.23 | 0.00 | 0.00 | 0.00 |
August | 57.44 | 24.54 | 32.90 | 109.72 | 19.47 | 0.00 | 0.00 | 0.00 |
September | 53.14 | 20.55 | 32.59 | 108.07 | 18.75 | 0.00 | 0.00 | 0.00 |
October | 48.63 | 17.19 | 31.44 | 92.80 | 21.13 | 0.00 | 0.00 | 0.00 |
November | 46.33 | 17.45 | 28.88 | 91.55 | 24.97 | 0.00 | 0.00 | 0.00 |
December | 46.88 | 21.02 | 25.86 | 92.97 | 32.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.62 | 25.36 | 30.26 | 111.79 | 22.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 46.33 | 17.18 | 25.86 | 91.55 | 15.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.17 | 39.46 | 34.89 | 139.54 | 32.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.56 | 24.19 | 26.38 | 100.47 | 31.55 | 0.00 | 0.00 | 0.00 |
February | 58.18 | 30.09 | 28.09 | 117.80 | 31.69 | 0.00 | 0.00 | 0.00 |
March | 67.48 | 39.46 | 28.02 | 137.16 | 25.77 | 0.00 | 0.00 | 0.00 |
April | 68.17 | 38.03 | 30.14 | 139.54 | 18.02 | 0.00 | 0.00 | 0.00 |
May | 57.18 | 24.74 | 32.44 | 118.45 | 15.80 | 0.00 | 0.00 | 0.00 |
June | 61.81 | 30.47 | 31.34 | 128.03 | 15.25 | 0.00 | 0.00 | 0.00 |
July | 52.07 | 17.18 | 34.89 | 106.13 | 20.23 | 0.00 | 0.00 | 0.00 |
August | 57.44 | 24.54 | 32.90 | 109.72 | 19.47 | 0.00 | 0.00 | 0.00 |
September | 53.14 | 20.55 | 32.59 | 108.07 | 18.75 | 0.00 | 0.00 | 0.00 |
October | 48.63 | 17.19 | 31.44 | 92.80 | 21.13 | 0.00 | 0.00 | 0.00 |
November | 46.33 | 17.45 | 28.88 | 91.55 | 24.97 | 0.00 | 0.00 | 0.00 |
December | 46.88 | 21.02 | 25.86 | 92.97 | 32.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.62 | 25.36 | 30.26 | 111.79 | 22.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 46.33 | 17.18 | 25.86 | 91.55 | 15.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.17 | 39.46 | 34.89 | 139.54 | 32.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.56 | 24.19 | 26.38 | 100.47 | 31.55 | 0.00 | 0.00 | 0.00 |
February | 58.18 | 30.09 | 28.09 | 117.80 | 31.69 | 0.00 | 0.00 | 0.00 |
March | 67.48 | 39.46 | 28.02 | 137.16 | 25.77 | 0.00 | 0.00 | 0.00 |
April | 68.17 | 38.03 | 30.14 | 139.54 | 18.02 | 0.00 | 0.00 | 0.00 |
May | 57.18 | 24.74 | 32.44 | 118.45 | 15.80 | 0.00 | 0.00 | 0.00 |
June | 61.81 | 30.47 | 31.34 | 128.03 | 15.25 | 0.00 | 0.00 | 0.00 |
July | 52.07 | 17.18 | 34.89 | 106.13 | 20.23 | 0.00 | 0.00 | 0.00 |
August | 57.44 | 24.54 | 32.90 | 109.72 | 19.47 | 0.00 | 0.00 | 0.00 |
September | 53.14 | 20.55 | 32.59 | 108.07 | 18.75 | 0.00 | 0.00 | 0.00 |
October | 48.63 | 17.19 | 31.44 | 92.80 | 21.13 | 0.00 | 0.00 | 0.00 |
November | 46.33 | 17.45 | 28.88 | 91.55 | 24.97 | 0.00 | 0.00 | 0.00 |
December | 46.88 | 21.02 | 25.86 | 92.97 | 32.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.62 | 25.36 | 30.26 | 111.79 | 22.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 46.33 | 17.18 | 25.86 | 91.55 | 15.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.17 | 39.46 | 34.89 | 139.54 | 32.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.56 | 24.19 | 26.38 | 100.47 | 31.55 | 0.00 | 0.00 | 0.00 |
February | 58.18 | 30.09 | 28.09 | 117.80 | 31.69 | 0.00 | 0.00 | 0.00 |
March | 67.48 | 39.46 | 28.02 | 137.16 | 25.77 | 0.00 | 0.00 | 0.00 |
April | 68.17 | 38.03 | 30.14 | 139.54 | 18.02 | 0.00 | 0.00 | 0.00 |
May | 57.18 | 24.74 | 32.44 | 118.45 | 15.80 | 0.00 | 0.00 | 0.00 |
June | 61.81 | 30.47 | 31.34 | 128.03 | 15.25 | 0.00 | 0.00 | 0.00 |
July | 52.07 | 17.18 | 34.89 | 106.13 | 20.23 | 0.00 | 0.00 | 0.00 |
August | 57.44 | 24.54 | 32.90 | 109.72 | 19.47 | 0.00 | 0.00 | 0.00 |
September | 53.14 | 20.55 | 32.59 | 108.07 | 18.75 | 0.00 | 0.00 | 0.00 |
October | 48.63 | 17.19 | 31.44 | 92.80 | 21.13 | 0.00 | 0.00 | 0.00 |
November | 46.33 | 17.45 | 28.88 | 91.55 | 24.97 | 0.00 | 0.00 | 0.00 |
December | 46.88 | 21.02 | 25.86 | 92.97 | 32.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.62 | 25.36 | 30.26 | 111.79 | 22.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 46.33 | 17.18 | 25.86 | 91.55 | 15.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.17 | 39.46 | 34.89 | 139.54 | 32.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.56 | 24.19 | 26.38 | 100.47 | 31.55 | 0.00 | 0.00 | 0.00 |
February | 58.18 | 30.09 | 28.09 | 117.80 | 31.69 | 0.00 | 0.00 | 0.00 |
March | 67.48 | 39.46 | 28.02 | 137.16 | 25.77 | 0.00 | 0.00 | 0.00 |
April | 68.17 | 38.03 | 30.14 | 139.54 | 18.02 | 0.00 | 0.00 | 0.00 |
May | 57.18 | 24.74 | 32.44 | 118.45 | 15.80 | 0.00 | 0.00 | 0.00 |
June | 61.81 | 30.47 | 31.34 | 128.03 | 15.25 | 0.00 | 0.00 | 0.00 |
July | 52.07 | 17.18 | 34.89 | 106.13 | 20.23 | 0.00 | 0.00 | 0.00 |
August | 57.44 | 24.54 | 32.90 | 109.72 | 19.47 | 0.00 | 0.00 | 0.00 |
September | 53.14 | 20.55 | 32.59 | 108.07 | 18.75 | 0.00 | 0.00 | 0.00 |
October | 48.63 | 17.19 | 31.44 | 92.80 | 21.13 | 0.00 | 0.00 | 0.00 |
November | 46.33 | 17.45 | 28.88 | 91.55 | 24.97 | 0.00 | 0.00 | 0.00 |
December | 46.88 | 21.02 | 25.86 | 92.97 | 32.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.62 | 25.36 | 30.26 | 111.79 | 22.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 46.33 | 17.18 | 25.86 | 91.55 | 15.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.17 | 39.46 | 34.89 | 139.54 | 32.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.56 | 24.19 | 26.38 | 100.47 | 31.55 | 0.00 | 0.00 | 0.00 |
February | 58.18 | 30.09 | 28.09 | 117.80 | 31.69 | 0.00 | 0.00 | 0.00 |
March | 67.48 | 39.46 | 28.02 | 137.16 | 25.77 | 0.00 | 0.00 | 0.00 |
April | 68.17 | 38.03 | 30.14 | 139.54 | 18.02 | 0.00 | 0.00 | 0.00 |
May | 57.18 | 24.74 | 32.44 | 118.45 | 15.80 | 0.00 | 0.00 | 0.00 |
June | 61.81 | 30.47 | 31.34 | 128.03 | 15.25 | 0.00 | 0.00 | 0.00 |
July | 52.07 | 17.18 | 34.89 | 106.13 | 20.23 | 0.00 | 0.00 | 0.00 |
August | 57.44 | 24.54 | 32.90 | 109.72 | 19.47 | 0.00 | 0.00 | 0.00 |
September | 53.14 | 20.55 | 32.59 | 108.07 | 18.75 | 0.00 | 0.00 | 0.00 |
October | 48.63 | 17.19 | 31.44 | 92.80 | 21.13 | 0.00 | 0.00 | 0.00 |
November | 46.33 | 17.45 | 28.88 | 91.55 | 24.97 | 0.00 | 0.00 | 0.00 |
December | 46.88 | 21.02 | 25.86 | 92.97 | 32.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.62 | 25.36 | 30.26 | 111.79 | 22.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 46.33 | 17.18 | 25.86 | 91.55 | 15.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.17 | 39.46 | 34.89 | 139.54 | 32.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.56 | 24.19 | 26.38 | 100.47 | 31.55 | 0.00 | 0.00 | 0.00 |
February | 58.18 | 30.09 | 28.09 | 117.80 | 31.69 | 0.00 | 0.00 | 0.00 |
March | 67.48 | 39.46 | 28.02 | 137.16 | 25.77 | 0.00 | 0.00 | 0.00 |
April | 68.17 | 38.03 | 30.14 | 139.54 | 18.02 | 0.00 | 0.00 | 0.00 |
May | 57.18 | 24.74 | 32.44 | 118.45 | 15.80 | 0.00 | 0.00 | 0.00 |
June | 61.81 | 30.47 | 31.34 | 128.03 | 15.25 | 0.00 | 0.00 | 0.00 |
July | 52.07 | 17.18 | 34.89 | 106.13 | 20.23 | 0.00 | 0.00 | 0.00 |
August | 57.44 | 24.54 | 32.90 | 109.72 | 19.47 | 0.00 | 0.00 | 0.00 |
September | 53.14 | 20.55 | 32.59 | 108.07 | 18.75 | 0.00 | 0.00 | 0.00 |
October | 48.63 | 17.19 | 31.44 | 92.80 | 21.13 | 0.00 | 0.00 | 0.00 |
November | 46.33 | 17.45 | 28.88 | 91.55 | 24.97 | 0.00 | 0.00 | 0.00 |
December | 46.88 | 21.02 | 25.86 | 92.97 | 32.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.62 | 25.36 | 30.26 | 111.79 | 22.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 46.33 | 17.18 | 25.86 | 91.55 | 15.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.17 | 39.46 | 34.89 | 139.54 | 32.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.56 | 24.19 | 26.38 | 100.47 | 31.55 | 0.00 | 0.00 | 0.00 |
February | 58.18 | 30.09 | 28.09 | 117.80 | 31.69 | 0.00 | 0.00 | 0.00 |
March | 67.48 | 39.46 | 28.02 | 137.16 | 25.77 | 0.00 | 0.00 | 0.00 |
April | 68.17 | 38.03 | 30.14 | 139.54 | 18.02 | 0.00 | 0.00 | 0.00 |
May | 57.18 | 24.74 | 32.44 | 118.45 | 15.80 | 0.00 | 0.00 | 0.00 |
June | 61.81 | 30.47 | 31.34 | 128.03 | 15.25 | 0.00 | 0.00 | 0.00 |
July | 52.07 | 17.18 | 34.89 | 106.13 | 20.23 | 0.00 | 0.00 | 0.00 |
August | 57.44 | 24.54 | 32.90 | 109.72 | 19.47 | 0.00 | 0.00 | 0.00 |
September | 53.14 | 20.55 | 32.59 | 108.07 | 18.75 | 0.00 | 0.00 | 0.00 |
October | 48.63 | 17.19 | 31.44 | 92.80 | 21.13 | 0.00 | 0.00 | 0.00 |
November | 46.33 | 17.45 | 28.88 | 91.55 | 24.97 | 0.00 | 0.00 | 0.00 |
December | 46.88 | 21.02 | 25.86 | 92.97 | 32.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.62 | 25.36 | 30.26 | 111.79 | 22.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 46.33 | 17.18 | 25.86 | 91.55 | 15.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.17 | 39.46 | 34.89 | 139.54 | 32.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 140.33 | 42.08 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 162.88 | 43.31 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 188.72 | 37.36 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 190.38 | 29.86 | 0.17 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 158.61 | 28.10 | 143.67 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 172.51 | 26.88 | 56.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 146.08 | 30.46 | 3.00 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 153.48 | 29.62 | 65.00 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 148.34 | 29.61 | 14.33 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 129.88 | 32.35 | 49.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 127.32 | 35.35 | 12.00 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 129.81 | 42.84 | 26.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 153.89 | 33.95 | 370.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 127.32 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 190.38 | 43.31 | 143.67 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.160183E+09 | 56464177.07 | 0.103718E+09 | 0.529445E+09 | 93546699.95 |
February | 0.158445E+09 | 55943282.54 | 0.102502E+09 | 0.542152E+09 | 63370208.38 |
March | 0.196426E+09 | 77307481.65 | 0.119118E+09 | 0.690589E+09 | 48009850.71 |
April | 0.190584E+09 | 72450718.58 | 0.118134E+09 | 0.669630E+09 | 20909556.55 |
May | 0.167983E+09 | 49508252.99 | 0.118475E+09 | 0.606753E+09 | 25530263.13 |
June | 0.176132E+09 | 60446102.92 | 0.115686E+09 | 0.628200E+09 | 26828998.79 |
July | 0.155331E+09 | 36456004.75 | 0.118875E+09 | 0.519526E+09 | 51394595.16 |
August | 0.168841E+09 | 49761367.87 | 0.119080E+09 | 0.529747E+09 | 39873247.39 |
September | 0.152646E+09 | 41881113.76 | 0.110765E+09 | 0.513705E+09 | 41073684.43 |
October | 0.148382E+09 | 37954641.81 | 0.110427E+09 | 0.460498E+09 | 57566503.86 |
November | 0.140057E+09 | 37964215.03 | 0.102092E+09 | 0.450363E+09 | 64215009.92 |
December | 0.148539E+09 | 48643958.35 | 99894560.41 | 0.487505E+09 | 0.102469E+09 |
Annual Sum or Average | 0.196355E+10 | 0.624781E+09 | 0.133877E+10 | 0.662811E+10 | 0.634788E+09 |
Minimum of Months | 0.140057E+09 | 36456004.75 | 99894560.41 | 0.450363E+09 | 20909556.55 |
Maximum of Months | 0.196426E+09 | 77307481.65 | 0.119118E+09 | 0.690589E+09 | 0.102469E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.160183E+09 | 56464177.07 | 0.103718E+09 | 0.529445E+09 | 93546699.95 |
February | 0.158445E+09 | 55943282.54 | 0.102502E+09 | 0.542152E+09 | 63370208.38 |
March | 0.196426E+09 | 77307481.65 | 0.119118E+09 | 0.690589E+09 | 48009850.71 |
April | 0.190584E+09 | 72450718.58 | 0.118134E+09 | 0.669630E+09 | 20909556.55 |
May | 0.167983E+09 | 49508252.99 | 0.118475E+09 | 0.606753E+09 | 25530263.13 |
June | 0.176132E+09 | 60446102.92 | 0.115686E+09 | 0.628200E+09 | 26828998.79 |
July | 0.155331E+09 | 36456004.75 | 0.118875E+09 | 0.519526E+09 | 51394595.16 |
August | 0.168841E+09 | 49761367.87 | 0.119080E+09 | 0.529747E+09 | 39873247.39 |
September | 0.152646E+09 | 41881113.76 | 0.110765E+09 | 0.513705E+09 | 41073684.43 |
October | 0.148382E+09 | 37954641.81 | 0.110427E+09 | 0.460498E+09 | 57566503.86 |
November | 0.140057E+09 | 37964215.03 | 0.102092E+09 | 0.450363E+09 | 64215009.92 |
December | 0.148539E+09 | 48643958.35 | 99894560.41 | 0.487505E+09 | 0.102469E+09 |
Annual Sum or Average | 0.196355E+10 | 0.624781E+09 | 0.133877E+10 | 0.662811E+10 | 0.634788E+09 |
Minimum of Months | 0.140057E+09 | 36456004.75 | 99894560.41 | 0.450363E+09 | 20909556.55 |
Maximum of Months | 0.196426E+09 | 77307481.65 | 0.119118E+09 | 0.690589E+09 | 0.102469E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 47748057.29 | 0.00 | 47748057.29 | 0.162067E+09 | 54403270.30 |
February | 46004999.23 | 0.00 | 46004999.23 | 0.168038E+09 | 36620696.70 |
March | 52326367.82 | 18874.78 | 52307493.04 | 0.206680E+09 | 27363149.35 |
April | 56475441.49 | 1763161.89 | 54712279.61 | 0.227508E+09 | 12046347.64 |
May | 76146473.30 | 10991589.21 | 65154884.10 | 0.299107E+09 | 14751538.29 |
June | 90602054.03 | 21820182.33 | 68781871.70 | 0.350080E+09 | 15676440.96 |
July | 78803421.40 | 10228708.06 | 68574713.34 | 0.273587E+09 | 29229881.09 |
August | 65076898.96 | 4653101.47 | 60423797.49 | 0.221547E+09 | 23265313.87 |
September | 52116266.33 | 136019.12 | 51980247.21 | 0.191953E+09 | 24050276.07 |
October | 51736133.32 | 0.00 | 51736133.32 | 0.166440E+09 | 33792172.35 |
November | 47374622.65 | 0.00 | 47374622.65 | 0.157638E+09 | 37596005.92 |
December | 46386575.36 | 0.00 | 46386575.36 | 0.155552E+09 | 59594613.57 |
Annual Sum or Average | 0.710797E+09 | 49611636.84 | 0.661186E+09 | 0.258020E+10 | 0.368390E+09 |
Minimum of Months | 46004999.23 | 0.00 | 46004999.23 | 0.155552E+09 | 12046347.64 |
Maximum of Months | 90602054.03 | 21820182.33 | 68781871.70 | 0.350080E+09 | 59594613.57 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 47746584.96 | 0.00 | 47746584.96 | 0.162064E+09 | 54402156.07 |
February | 46003632.84 | 0.00 | 46003632.84 | 0.168035E+09 | 36619436.80 |
March | 52324911.05 | 18873.89 | 52306037.16 | 0.206677E+09 | 27361982.07 |
April | 56473771.29 | 1763079.25 | 54710692.04 | 0.227504E+09 | 12045685.19 |
May | 76143761.65 | 10991074.02 | 65152687.63 | 0.299100E+09 | 14751035.51 |
June | 90598700.26 | 21819159.59 | 68779540.67 | 0.350071E+09 | 15675964.17 |
July | 78800515.76 | 10228228.63 | 68572287.13 | 0.273579E+09 | 29229065.54 |
August | 65074709.73 | 4652883.37 | 60421826.36 | 0.221542E+09 | 23264571.62 |
September | 52114597.21 | 136012.74 | 51978584.47 | 0.191949E+09 | 24049606.69 |
October | 51734445.03 | 0.00 | 51734445.03 | 0.166436E+09 | 33791529.68 |
November | 47373084.98 | 0.00 | 47373084.98 | 0.157635E+09 | 37595143.68 |
December | 46385115.07 | 0.00 | 46385115.07 | 0.155548E+09 | 59593507.07 |
Annual Sum or Average | 0.710774E+09 | 49609311.48 | 0.661165E+09 | 0.258014E+10 | 0.368380E+09 |
Minimum of Months | 46003632.84 | 0.00 | 46003632.84 | 0.155548E+09 | 12045685.19 |
Maximum of Months | 90598700.26 | 21819159.59 | 68779540.67 | 0.350071E+09 | 59593507.07 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135423E+09 | 64778677.13 | 70644125.35 | 0.269094E+09 | 84500005.77 |
February | 0.140749E+09 | 72800307.74 | 67948528.39 | 0.284980E+09 | 76659124.36 |
March | 0.180735E+09 | 0.105686E+09 | 75049357.50 | 0.367373E+09 | 69017954.59 |
April | 0.176702E+09 | 98566070.93 | 78135833.25 | 0.361687E+09 | 46712617.46 |
May | 0.153149E+09 | 66275179.04 | 86874054.99 | 0.317255E+09 | 42312727.18 |
June | 0.160207E+09 | 78983694.85 | 81223512.56 | 0.331850E+09 | 39521561.50 |
July | 0.139470E+09 | 46014049.80 | 93455789.18 | 0.284247E+09 | 54185368.85 |
August | 0.153840E+09 | 65717903.04 | 88122537.44 | 0.293887E+09 | 52138843.35 |
September | 0.137732E+09 | 53268984.88 | 84462702.79 | 0.280123E+09 | 48603579.33 |
October | 0.130250E+09 | 46045529.54 | 84204619.07 | 0.248564E+09 | 56602584.78 |
November | 0.120079E+09 | 45231519.46 | 74847954.85 | 0.237291E+09 | 64723125.24 |
December | 0.125556E+09 | 56291817.72 | 69264466.92 | 0.249014E+09 | 87681780.79 |
Annual Sum or Average | 0.175389E+10 | 0.799659E+09 | 0.954233E+09 | 0.352537E+10 | 0.722659E+09 |
Minimum of Months | 0.120079E+09 | 45231519.46 | 67948528.39 | 0.237291E+09 | 39521561.50 |
Maximum of Months | 0.180735E+09 | 0.105686E+09 | 93455789.18 | 0.367373E+09 | 87681780.79 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135423E+09 | 64778677.13 | 70644125.35 | 0.269094E+09 | 84500005.77 |
February | 0.140749E+09 | 72800307.74 | 67948528.39 | 0.284980E+09 | 76659124.36 |
March | 0.180735E+09 | 0.105686E+09 | 75049357.50 | 0.367373E+09 | 69017954.59 |
April | 0.176702E+09 | 98566070.93 | 78135833.25 | 0.361687E+09 | 46712617.46 |
May | 0.153149E+09 | 66275179.04 | 86874054.99 | 0.317255E+09 | 42312727.18 |
June | 0.160207E+09 | 78983694.85 | 81223512.56 | 0.331850E+09 | 39521561.50 |
July | 0.139470E+09 | 46014049.80 | 93455789.18 | 0.284247E+09 | 54185368.85 |
August | 0.153840E+09 | 65717903.04 | 88122537.44 | 0.293887E+09 | 52138843.35 |
September | 0.137732E+09 | 53268984.88 | 84462702.79 | 0.280123E+09 | 48603579.33 |
October | 0.130250E+09 | 46045529.54 | 84204619.07 | 0.248564E+09 | 56602584.78 |
November | 0.120079E+09 | 45231519.46 | 74847954.85 | 0.237291E+09 | 64723125.24 |
December | 0.125556E+09 | 56291817.72 | 69264466.92 | 0.249014E+09 | 87681780.79 |
Annual Sum or Average | 0.175389E+10 | 0.799659E+09 | 0.954233E+09 | 0.352537E+10 | 0.722659E+09 |
Minimum of Months | 0.120079E+09 | 45231519.46 | 67948528.39 | 0.237291E+09 | 39521561.50 |
Maximum of Months | 0.180735E+09 | 0.105686E+09 | 93455789.18 | 0.367373E+09 | 87681780.79 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135423E+09 | 64778677.13 | 70644125.35 | 0.269094E+09 | 84500005.77 |
February | 0.140749E+09 | 72800307.74 | 67948528.39 | 0.284980E+09 | 76659124.36 |
March | 0.180735E+09 | 0.105686E+09 | 75049357.50 | 0.367373E+09 | 69017954.59 |
April | 0.176702E+09 | 98566070.93 | 78135833.25 | 0.361687E+09 | 46712617.46 |
May | 0.153149E+09 | 66275179.04 | 86874054.99 | 0.317255E+09 | 42312727.18 |
June | 0.160207E+09 | 78983694.85 | 81223512.56 | 0.331850E+09 | 39521561.50 |
July | 0.139470E+09 | 46014049.80 | 93455789.18 | 0.284247E+09 | 54185368.85 |
August | 0.153840E+09 | 65717903.04 | 88122537.44 | 0.293887E+09 | 52138843.35 |
September | 0.137732E+09 | 53268984.88 | 84462702.79 | 0.280123E+09 | 48603579.33 |
October | 0.130250E+09 | 46045529.54 | 84204619.07 | 0.248564E+09 | 56602584.78 |
November | 0.120079E+09 | 45231519.46 | 74847954.85 | 0.237291E+09 | 64723125.24 |
December | 0.125556E+09 | 56291817.72 | 69264466.92 | 0.249014E+09 | 87681780.79 |
Annual Sum or Average | 0.175389E+10 | 0.799659E+09 | 0.954233E+09 | 0.352537E+10 | 0.722659E+09 |
Minimum of Months | 0.120079E+09 | 45231519.46 | 67948528.39 | 0.237291E+09 | 39521561.50 |
Maximum of Months | 0.180735E+09 | 0.105686E+09 | 93455789.18 | 0.367373E+09 | 87681780.79 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135423E+09 | 64778677.13 | 70644125.35 | 0.269094E+09 | 84500005.77 |
February | 0.140749E+09 | 72800307.74 | 67948528.39 | 0.284980E+09 | 76659124.36 |
March | 0.180735E+09 | 0.105686E+09 | 75049357.50 | 0.367373E+09 | 69017954.59 |
April | 0.176702E+09 | 98566070.93 | 78135833.25 | 0.361687E+09 | 46712617.46 |
May | 0.153149E+09 | 66275179.04 | 86874054.99 | 0.317255E+09 | 42312727.18 |
June | 0.160207E+09 | 78983694.85 | 81223512.56 | 0.331850E+09 | 39521561.50 |
July | 0.139470E+09 | 46014049.80 | 93455789.18 | 0.284247E+09 | 54185368.85 |
August | 0.153840E+09 | 65717903.04 | 88122537.44 | 0.293887E+09 | 52138843.35 |
September | 0.137732E+09 | 53268984.88 | 84462702.79 | 0.280123E+09 | 48603579.33 |
October | 0.130250E+09 | 46045529.54 | 84204619.07 | 0.248564E+09 | 56602584.78 |
November | 0.120079E+09 | 45231519.46 | 74847954.85 | 0.237291E+09 | 64723125.24 |
December | 0.125556E+09 | 56291817.72 | 69264466.92 | 0.249014E+09 | 87681780.79 |
Annual Sum or Average | 0.175389E+10 | 0.799659E+09 | 0.954233E+09 | 0.352537E+10 | 0.722659E+09 |
Minimum of Months | 0.120079E+09 | 45231519.46 | 67948528.39 | 0.237291E+09 | 39521561.50 |
Maximum of Months | 0.180735E+09 | 0.105686E+09 | 93455789.18 | 0.367373E+09 | 87681780.79 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135423E+09 | 64778677.13 | 70644125.35 | 0.269094E+09 | 84500005.77 |
February | 0.140749E+09 | 72800307.74 | 67948528.39 | 0.284980E+09 | 76659124.36 |
March | 0.180735E+09 | 0.105686E+09 | 75049357.50 | 0.367373E+09 | 69017954.59 |
April | 0.176702E+09 | 98566070.93 | 78135833.25 | 0.361687E+09 | 46712617.46 |
May | 0.153149E+09 | 66275179.04 | 86874054.99 | 0.317255E+09 | 42312727.18 |
June | 0.160207E+09 | 78983694.85 | 81223512.56 | 0.331850E+09 | 39521561.50 |
July | 0.139470E+09 | 46014049.80 | 93455789.18 | 0.284247E+09 | 54185368.85 |
August | 0.153840E+09 | 65717903.04 | 88122537.44 | 0.293887E+09 | 52138843.35 |
September | 0.137732E+09 | 53268984.88 | 84462702.79 | 0.280123E+09 | 48603579.33 |
October | 0.130250E+09 | 46045529.54 | 84204619.07 | 0.248564E+09 | 56602584.78 |
November | 0.120079E+09 | 45231519.46 | 74847954.85 | 0.237291E+09 | 64723125.24 |
December | 0.125556E+09 | 56291817.72 | 69264466.92 | 0.249014E+09 | 87681780.79 |
Annual Sum or Average | 0.175389E+10 | 0.799659E+09 | 0.954233E+09 | 0.352537E+10 | 0.722659E+09 |
Minimum of Months | 0.120079E+09 | 45231519.46 | 67948528.39 | 0.237291E+09 | 39521561.50 |
Maximum of Months | 0.180735E+09 | 0.105686E+09 | 93455789.18 | 0.367373E+09 | 87681780.79 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135423E+09 | 64778677.13 | 70644125.35 | 0.269094E+09 | 84500005.77 |
February | 0.140749E+09 | 72800307.74 | 67948528.39 | 0.284980E+09 | 76659124.36 |
March | 0.180735E+09 | 0.105686E+09 | 75049357.50 | 0.367373E+09 | 69017954.59 |
April | 0.176702E+09 | 98566070.93 | 78135833.25 | 0.361687E+09 | 46712617.46 |
May | 0.153149E+09 | 66275179.04 | 86874054.99 | 0.317255E+09 | 42312727.18 |
June | 0.160207E+09 | 78983694.85 | 81223512.56 | 0.331850E+09 | 39521561.50 |
July | 0.139470E+09 | 46014049.80 | 93455789.18 | 0.284247E+09 | 54185368.85 |
August | 0.153840E+09 | 65717903.04 | 88122537.44 | 0.293887E+09 | 52138843.35 |
September | 0.137732E+09 | 53268984.88 | 84462702.79 | 0.280123E+09 | 48603579.33 |
October | 0.130250E+09 | 46045529.54 | 84204619.07 | 0.248564E+09 | 56602584.78 |
November | 0.120079E+09 | 45231519.46 | 74847954.85 | 0.237291E+09 | 64723125.24 |
December | 0.125556E+09 | 56291817.72 | 69264466.92 | 0.249014E+09 | 87681780.79 |
Annual Sum or Average | 0.175389E+10 | 0.799659E+09 | 0.954233E+09 | 0.352537E+10 | 0.722659E+09 |
Minimum of Months | 0.120079E+09 | 45231519.46 | 67948528.39 | 0.237291E+09 | 39521561.50 |
Maximum of Months | 0.180735E+09 | 0.105686E+09 | 93455789.18 | 0.367373E+09 | 87681780.79 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135423E+09 | 64778677.13 | 70644125.35 | 0.269094E+09 | 84500005.77 |
February | 0.140749E+09 | 72800307.74 | 67948528.39 | 0.284980E+09 | 76659124.36 |
March | 0.180735E+09 | 0.105686E+09 | 75049357.50 | 0.367373E+09 | 69017954.59 |
April | 0.176702E+09 | 98566070.93 | 78135833.25 | 0.361687E+09 | 46712617.46 |
May | 0.153149E+09 | 66275179.04 | 86874054.99 | 0.317255E+09 | 42312727.18 |
June | 0.160207E+09 | 78983694.85 | 81223512.56 | 0.331850E+09 | 39521561.50 |
July | 0.139470E+09 | 46014049.80 | 93455789.18 | 0.284247E+09 | 54185368.85 |
August | 0.153840E+09 | 65717903.04 | 88122537.44 | 0.293887E+09 | 52138843.35 |
September | 0.137732E+09 | 53268984.88 | 84462702.79 | 0.280123E+09 | 48603579.33 |
October | 0.130250E+09 | 46045529.54 | 84204619.07 | 0.248564E+09 | 56602584.78 |
November | 0.120079E+09 | 45231519.46 | 74847954.85 | 0.237291E+09 | 64723125.24 |
December | 0.125556E+09 | 56291817.72 | 69264466.92 | 0.249014E+09 | 87681780.79 |
Annual Sum or Average | 0.175389E+10 | 0.799659E+09 | 0.954233E+09 | 0.352537E+10 | 0.722659E+09 |
Minimum of Months | 0.120079E+09 | 45231519.46 | 67948528.39 | 0.237291E+09 | 39521561.50 |
Maximum of Months | 0.180735E+09 | 0.105686E+09 | 93455789.18 | 0.367373E+09 | 87681780.79 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135423E+09 | 64778677.13 | 70644125.35 | 0.269094E+09 | 84500005.77 |
February | 0.140749E+09 | 72800307.74 | 67948528.39 | 0.284980E+09 | 76659124.36 |
March | 0.180735E+09 | 0.105686E+09 | 75049357.50 | 0.367373E+09 | 69017954.59 |
April | 0.176702E+09 | 98566070.93 | 78135833.25 | 0.361687E+09 | 46712617.46 |
May | 0.153149E+09 | 66275179.04 | 86874054.99 | 0.317255E+09 | 42312727.18 |
June | 0.160207E+09 | 78983694.85 | 81223512.56 | 0.331850E+09 | 39521561.50 |
July | 0.139470E+09 | 46014049.80 | 93455789.18 | 0.284247E+09 | 54185368.85 |
August | 0.153840E+09 | 65717903.04 | 88122537.44 | 0.293887E+09 | 52138843.35 |
September | 0.137732E+09 | 53268984.88 | 84462702.79 | 0.280123E+09 | 48603579.33 |
October | 0.130250E+09 | 46045529.54 | 84204619.07 | 0.248564E+09 | 56602584.78 |
November | 0.120079E+09 | 45231519.46 | 74847954.85 | 0.237291E+09 | 64723125.24 |
December | 0.125556E+09 | 56291817.72 | 69264466.92 | 0.249014E+09 | 87681780.79 |
Annual Sum or Average | 0.175389E+10 | 0.799659E+09 | 0.954233E+09 | 0.352537E+10 | 0.722659E+09 |
Minimum of Months | 0.120079E+09 | 45231519.46 | 67948528.39 | 0.237291E+09 | 39521561.50 |
Maximum of Months | 0.180735E+09 | 0.105686E+09 | 93455789.18 | 0.367373E+09 | 87681780.79 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135423E+09 | 64778677.13 | 70644125.35 | 0.269094E+09 | 84500005.77 |
February | 0.140749E+09 | 72800307.74 | 67948528.39 | 0.284980E+09 | 76659124.36 |
March | 0.180735E+09 | 0.105686E+09 | 75049357.50 | 0.367373E+09 | 69017954.59 |
April | 0.176702E+09 | 98566070.93 | 78135833.25 | 0.361687E+09 | 46712617.46 |
May | 0.153149E+09 | 66275179.04 | 86874054.99 | 0.317255E+09 | 42312727.18 |
June | 0.160207E+09 | 78983694.85 | 81223512.56 | 0.331850E+09 | 39521561.50 |
July | 0.139470E+09 | 46014049.80 | 93455789.18 | 0.284247E+09 | 54185368.85 |
August | 0.153840E+09 | 65717903.04 | 88122537.44 | 0.293887E+09 | 52138843.35 |
September | 0.137732E+09 | 53268984.88 | 84462702.79 | 0.280123E+09 | 48603579.33 |
October | 0.130250E+09 | 46045529.54 | 84204619.07 | 0.248564E+09 | 56602584.78 |
November | 0.120079E+09 | 45231519.46 | 74847954.85 | 0.237291E+09 | 64723125.24 |
December | 0.125556E+09 | 56291817.72 | 69264466.92 | 0.249014E+09 | 87681780.79 |
Annual Sum or Average | 0.175389E+10 | 0.799659E+09 | 0.954233E+09 | 0.352537E+10 | 0.722659E+09 |
Minimum of Months | 0.120079E+09 | 45231519.46 | 67948528.39 | 0.237291E+09 | 39521561.50 |
Maximum of Months | 0.180735E+09 | 0.105686E+09 | 93455789.18 | 0.367373E+09 | 87681780.79 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135423E+09 | 64778677.13 | 70644125.35 | 0.269094E+09 | 84500005.77 |
February | 0.140749E+09 | 72800307.74 | 67948528.39 | 0.284980E+09 | 76659124.36 |
March | 0.180735E+09 | 0.105686E+09 | 75049357.50 | 0.367373E+09 | 69017954.59 |
April | 0.176702E+09 | 98566070.93 | 78135833.25 | 0.361687E+09 | 46712617.46 |
May | 0.153149E+09 | 66275179.04 | 86874054.99 | 0.317255E+09 | 42312727.18 |
June | 0.160207E+09 | 78983694.85 | 81223512.56 | 0.331850E+09 | 39521561.50 |
July | 0.139470E+09 | 46014049.80 | 93455789.18 | 0.284247E+09 | 54185368.85 |
August | 0.153840E+09 | 65717903.04 | 88122537.44 | 0.293887E+09 | 52138843.35 |
September | 0.137732E+09 | 53268984.88 | 84462702.79 | 0.280123E+09 | 48603579.33 |
October | 0.130250E+09 | 46045529.54 | 84204619.07 | 0.248564E+09 | 56602584.78 |
November | 0.120079E+09 | 45231519.46 | 74847954.85 | 0.237291E+09 | 64723125.24 |
December | 0.125556E+09 | 56291817.72 | 69264466.92 | 0.249014E+09 | 87681780.79 |
Annual Sum or Average | 0.175389E+10 | 0.799659E+09 | 0.954233E+09 | 0.352537E+10 | 0.722659E+09 |
Minimum of Months | 0.120079E+09 | 45231519.46 | 67948528.39 | 0.237291E+09 | 39521561.50 |
Maximum of Months | 0.180735E+09 | 0.105686E+09 | 93455789.18 | 0.367373E+09 | 87681780.79 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135423E+09 | 64778677.13 | 70644125.35 | 0.269094E+09 | 84500005.77 |
February | 0.140749E+09 | 72800307.74 | 67948528.39 | 0.284980E+09 | 76659124.36 |
March | 0.180735E+09 | 0.105686E+09 | 75049357.50 | 0.367373E+09 | 69017954.59 |
April | 0.176702E+09 | 98566070.93 | 78135833.25 | 0.361687E+09 | 46712617.46 |
May | 0.153149E+09 | 66275179.04 | 86874054.99 | 0.317255E+09 | 42312727.18 |
June | 0.160207E+09 | 78983694.85 | 81223512.56 | 0.331850E+09 | 39521561.50 |
July | 0.139470E+09 | 46014049.80 | 93455789.18 | 0.284247E+09 | 54185368.85 |
August | 0.153840E+09 | 65717903.04 | 88122537.44 | 0.293887E+09 | 52138843.35 |
September | 0.137732E+09 | 53268984.88 | 84462702.79 | 0.280123E+09 | 48603579.33 |
October | 0.130250E+09 | 46045529.54 | 84204619.07 | 0.248564E+09 | 56602584.78 |
November | 0.120079E+09 | 45231519.46 | 74847954.85 | 0.237291E+09 | 64723125.24 |
December | 0.125556E+09 | 56291817.72 | 69264466.92 | 0.249014E+09 | 87681780.79 |
Annual Sum or Average | 0.175389E+10 | 0.799659E+09 | 0.954233E+09 | 0.352537E+10 | 0.722659E+09 |
Minimum of Months | 0.120079E+09 | 45231519.46 | 67948528.39 | 0.237291E+09 | 39521561.50 |
Maximum of Months | 0.180735E+09 | 0.105686E+09 | 93455789.18 | 0.367373E+09 | 87681780.79 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135423E+09 | 64778677.13 | 70644125.35 | 0.269094E+09 | 84500005.77 |
February | 0.140749E+09 | 72800307.74 | 67948528.39 | 0.284980E+09 | 76659124.36 |
March | 0.180735E+09 | 0.105686E+09 | 75049357.50 | 0.367373E+09 | 69017954.59 |
April | 0.176702E+09 | 98566070.93 | 78135833.25 | 0.361687E+09 | 46712617.46 |
May | 0.153149E+09 | 66275179.04 | 86874054.99 | 0.317255E+09 | 42312727.18 |
June | 0.160207E+09 | 78983694.85 | 81223512.56 | 0.331850E+09 | 39521561.50 |
July | 0.139470E+09 | 46014049.80 | 93455789.18 | 0.284247E+09 | 54185368.85 |
August | 0.153840E+09 | 65717903.04 | 88122537.44 | 0.293887E+09 | 52138843.35 |
September | 0.137732E+09 | 53268984.88 | 84462702.79 | 0.280123E+09 | 48603579.33 |
October | 0.130250E+09 | 46045529.54 | 84204619.07 | 0.248564E+09 | 56602584.78 |
November | 0.120079E+09 | 45231519.46 | 74847954.85 | 0.237291E+09 | 64723125.24 |
December | 0.125556E+09 | 56291817.72 | 69264466.92 | 0.249014E+09 | 87681780.79 |
Annual Sum or Average | 0.175389E+10 | 0.799659E+09 | 0.954233E+09 | 0.352537E+10 | 0.722659E+09 |
Minimum of Months | 0.120079E+09 | 45231519.46 | 67948528.39 | 0.237291E+09 | 39521561.50 |
Maximum of Months | 0.180735E+09 | 0.105686E+09 | 93455789.18 | 0.367373E+09 | 87681780.79 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135423E+09 | 64778677.13 | 70644125.35 | 0.269094E+09 | 84500005.77 |
February | 0.140749E+09 | 72800307.74 | 67948528.39 | 0.284980E+09 | 76659124.36 |
March | 0.180735E+09 | 0.105686E+09 | 75049357.50 | 0.367373E+09 | 69017954.59 |
April | 0.176702E+09 | 98566070.93 | 78135833.25 | 0.361687E+09 | 46712617.46 |
May | 0.153149E+09 | 66275179.04 | 86874054.99 | 0.317255E+09 | 42312727.18 |
June | 0.160207E+09 | 78983694.85 | 81223512.56 | 0.331850E+09 | 39521561.50 |
July | 0.139470E+09 | 46014049.80 | 93455789.18 | 0.284247E+09 | 54185368.85 |
August | 0.153840E+09 | 65717903.04 | 88122537.44 | 0.293887E+09 | 52138843.35 |
September | 0.137732E+09 | 53268984.88 | 84462702.79 | 0.280123E+09 | 48603579.33 |
October | 0.130250E+09 | 46045529.54 | 84204619.07 | 0.248564E+09 | 56602584.78 |
November | 0.120079E+09 | 45231519.46 | 74847954.85 | 0.237291E+09 | 64723125.24 |
December | 0.125556E+09 | 56291817.72 | 69264466.92 | 0.249014E+09 | 87681780.79 |
Annual Sum or Average | 0.175389E+10 | 0.799659E+09 | 0.954233E+09 | 0.352537E+10 | 0.722659E+09 |
Minimum of Months | 0.120079E+09 | 45231519.46 | 67948528.39 | 0.237291E+09 | 39521561.50 |
Maximum of Months | 0.180735E+09 | 0.105686E+09 | 93455789.18 | 0.367373E+09 | 87681780.79 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135423E+09 | 64778677.13 | 70644125.35 | 0.269094E+09 | 84500005.77 |
February | 0.140749E+09 | 72800307.74 | 67948528.39 | 0.284980E+09 | 76659124.36 |
March | 0.180735E+09 | 0.105686E+09 | 75049357.50 | 0.367373E+09 | 69017954.59 |
April | 0.176702E+09 | 98566070.93 | 78135833.25 | 0.361687E+09 | 46712617.46 |
May | 0.153149E+09 | 66275179.04 | 86874054.99 | 0.317255E+09 | 42312727.18 |
June | 0.160207E+09 | 78983694.85 | 81223512.56 | 0.331850E+09 | 39521561.50 |
July | 0.139470E+09 | 46014049.80 | 93455789.18 | 0.284247E+09 | 54185368.85 |
August | 0.153840E+09 | 65717903.04 | 88122537.44 | 0.293887E+09 | 52138843.35 |
September | 0.137732E+09 | 53268984.88 | 84462702.79 | 0.280123E+09 | 48603579.33 |
October | 0.130250E+09 | 46045529.54 | 84204619.07 | 0.248564E+09 | 56602584.78 |
November | 0.120079E+09 | 45231519.46 | 74847954.85 | 0.237291E+09 | 64723125.24 |
December | 0.125556E+09 | 56291817.72 | 69264466.92 | 0.249014E+09 | 87681780.79 |
Annual Sum or Average | 0.175389E+10 | 0.799659E+09 | 0.954233E+09 | 0.352537E+10 | 0.722659E+09 |
Minimum of Months | 0.120079E+09 | 45231519.46 | 67948528.39 | 0.237291E+09 | 39521561.50 |
Maximum of Months | 0.180735E+09 | 0.105686E+09 | 93455789.18 | 0.367373E+09 | 87681780.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.375858E+09 | 0.112710E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.394039E+09 | 0.104776E+09 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.505463E+09 | 0.100055E+09 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.493458E+09 | 77391103.50 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.424822E+09 | 75249788.24 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.447147E+09 | 69672956.52 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.391269E+09 | 81589883.47 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.411069E+09 | 79344293.66 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.384500E+09 | 76744992.95 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.347881E+09 | 86655893.27 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.330020E+09 | 91635259.81 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.347687E+09 | 0.114738E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.485321E+10 | 0.107056E+10 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.330020E+09 | 69672956.52 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.505463E+09 | 0.114738E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 516.27 | 110.39 | 155.26 | 42.16 | 113.10 | 0.00 | 0.00 |
February | 587.12 | 82.66 | 169.02 | 46.25 | 122.77 | 0.00 | 0.00 |
March | 669.94 | 56.22 | 185.75 | 57.74 | 128.01 | 0.00 | 0.00 |
April | 692.04 | 25.24 | 190.63 | 57.26 | 133.37 | 0.00 | 0.00 |
May | 676.24 | 29.90 | 182.29 | 45.18 | 137.12 | 0.00 | 0.00 |
June | 754.56 | 32.52 | 205.81 | 63.48 | 142.34 | 0.00 | 0.00 |
July | 591.75 | 59.73 | 174.83 | 34.86 | 139.97 | 0.00 | 0.00 |
August | 560.67 | 46.82 | 174.67 | 40.63 | 134.04 | 0.00 | 0.00 |
September | 544.31 | 50.07 | 158.00 | 32.42 | 125.57 | 0.00 | 0.00 |
October | 467.88 | 67.96 | 149.43 | 28.34 | 121.09 | 0.00 | 0.00 |
November | 468.81 | 78.23 | 144.62 | 29.29 | 115.33 | 0.00 | 0.00 |
December | 480.10 | 120.94 | 145.55 | 36.32 | 109.23 | 0.00 | 0.00 |
Annual Sum or Average | 583.78 | 63.42 | 169.61 | 42.77 | 126.84 | 0.00 | 0.00 |
Minimum of Months | 467.88 | 25.24 | 144.62 | 28.34 | 109.23 | 0.00 | 0.00 |
Maximum of Months | 754.56 | 120.94 | 205.81 | 63.48 | 142.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1406.56 | 441.68 | 707.86 | 338.60 | 369.26 | 0.00 | 0.00 |
February | 1649.19 | 443.63 | 814.52 | 421.30 | 393.22 | 0.00 | 0.00 |
March | 1920.26 | 360.76 | 944.70 | 552.42 | 392.28 | 0.00 | 0.00 |
April | 1953.56 | 252.31 | 954.41 | 532.38 | 422.03 | 0.00 | 0.00 |
May | 1658.29 | 221.17 | 800.51 | 346.42 | 454.09 | 0.00 | 0.00 |
June | 1792.40 | 213.47 | 865.32 | 426.61 | 438.71 | 0.00 | 0.00 |
July | 1485.76 | 283.23 | 729.01 | 240.52 | 488.49 | 0.00 | 0.00 |
August | 1536.15 | 272.53 | 804.12 | 343.51 | 460.62 | 0.00 | 0.00 |
September | 1513.01 | 262.52 | 743.92 | 287.72 | 456.20 | 0.00 | 0.00 |
October | 1299.24 | 295.86 | 680.82 | 240.68 | 440.14 | 0.00 | 0.00 |
November | 1281.66 | 349.58 | 648.58 | 244.31 | 404.27 | 0.00 | 0.00 |
December | 1301.60 | 458.31 | 656.28 | 294.24 | 362.05 | 0.00 | 0.00 |
Annual Sum or Average | 1565.04 | 320.82 | 778.62 | 355.00 | 423.62 | 0.00 | 0.00 |
Minimum of Months | 1281.66 | 213.47 | 648.58 | 240.52 | 362.05 | 0.00 | 0.00 |
Maximum of Months | 1953.56 | 458.31 | 954.41 | 552.42 | 488.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 23577.92 | 7702.02 | 3256.85 | 1557.85 | 1699.00 | 0.00 | 0.00 |
February | 29676.74 | 8676.18 | 3747.86 | 1938.60 | 1809.26 | 0.00 | 0.00 |
March | 32859.73 | 8114.42 | 4349.68 | 2544.73 | 1804.95 | 0.00 | 0.00 |
April | 33730.58 | 6661.14 | 4396.21 | 2454.40 | 1941.82 | 0.00 | 0.00 |
May | 32129.59 | 6253.96 | 3685.73 | 1596.40 | 2089.33 | 0.00 | 0.00 |
June | 34754.96 | 6292.08 | 3983.63 | 1965.08 | 2018.55 | 0.00 | 0.00 |
July | 25687.09 | 6618.48 | 3355.77 | 1108.14 | 2247.63 | 0.00 | 0.00 |
August | 28840.60 | 6203.43 | 3702.89 | 1583.53 | 2119.36 | 0.00 | 0.00 |
September | 26798.88 | 6344.92 | 3425.04 | 1325.98 | 2099.05 | 0.00 | 0.00 |
October | 21296.41 | 6383.73 | 3133.04 | 1107.91 | 2025.13 | 0.00 | 0.00 |
November | 22208.85 | 6645.46 | 2984.12 | 1124.01 | 1860.11 | 0.00 | 0.00 |
December | 22204.27 | 7631.80 | 3019.59 | 1353.77 | 1665.82 | 0.00 | 0.00 |
Annual Sum or Average | 27781.40 | 6951.74 | 3584.17 | 1635.03 | 1949.13 | 0.00 | 0.00 |
Minimum of Months | 21296.41 | 6203.43 | 2984.12 | 1107.91 | 1665.82 | 0.00 | 0.00 |
Maximum of Months | 34754.96 | 8676.18 | 4396.21 | 2544.73 | 2247.63 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.138279E+10 | 0.295668E+09 | 0.415860E+09 | 0.112928E+09 | 0.302932E+09 | 0.00 | 0.00 |
February | 0.142036E+10 | 0.199962E+09 | 0.408899E+09 | 0.111887E+09 | 0.297012E+09 | 0.00 | 0.00 |
March | 0.179436E+10 | 0.150569E+09 | 0.497502E+09 | 0.154653E+09 | 0.342850E+09 | 0.00 | 0.00 |
April | 0.179377E+10 | 65413731.26 | 0.494118E+09 | 0.148428E+09 | 0.345690E+09 | 0.00 | 0.00 |
May | 0.181123E+10 | 80077282.97 | 0.488257E+09 | 0.120999E+09 | 0.367258E+09 | 0.00 | 0.00 |
June | 0.195582E+10 | 84280159.51 | 0.533464E+09 | 0.164532E+09 | 0.368933E+09 | 0.00 | 0.00 |
July | 0.158494E+10 | 0.159972E+09 | 0.468266E+09 | 93368946.19 | 0.374897E+09 | 0.00 | 0.00 |
August | 0.150170E+10 | 0.125396E+09 | 0.467834E+09 | 0.108829E+09 | 0.359005E+09 | 0.00 | 0.00 |
September | 0.141086E+10 | 0.129792E+09 | 0.409523E+09 | 84034259.38 | 0.325489E+09 | 0.00 | 0.00 |
October | 0.125318E+10 | 0.182025E+09 | 0.400234E+09 | 75909283.62 | 0.324325E+09 | 0.00 | 0.00 |
November | 0.121516E+10 | 0.202785E+09 | 0.374861E+09 | 75928430.06 | 0.298932E+09 | 0.00 | 0.00 |
December | 0.128591E+10 | 0.323923E+09 | 0.389849E+09 | 97287916.71 | 0.292561E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.184101E+11 | 0.199986E+10 | 0.534867E+10 | 0.134878E+10 | 0.399988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.121516E+10 | 65413731.26 | 0.374861E+09 | 75909283.62 | 0.292561E+09 | 0.00 | 0.00 |
Maximum of Months | 0.195582E+10 | 0.323923E+09 | 0.533464E+09 | 0.164532E+09 | 0.374897E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.376732E+10 | 0.118300E+10 | 0.189592E+10 | 0.906901E+09 | 0.989018E+09 | 0.00 | 0.00 |
February | 0.398972E+10 | 0.107323E+10 | 0.197048E+10 | 0.101920E+10 | 0.951279E+09 | 0.00 | 0.00 |
March | 0.514323E+10 | 0.966251E+09 | 0.253029E+10 | 0.147960E+10 | 0.105069E+10 | 0.00 | 0.00 |
April | 0.506362E+10 | 0.653977E+09 | 0.247383E+10 | 0.137992E+10 | 0.109390E+10 | 0.00 | 0.00 |
May | 0.444157E+10 | 0.592378E+09 | 0.214409E+10 | 0.927853E+09 | 0.121624E+10 | 0.00 | 0.00 |
June | 0.464589E+10 | 0.553302E+09 | 0.224290E+10 | 0.110577E+10 | 0.113713E+10 | 0.00 | 0.00 |
July | 0.397945E+10 | 0.758595E+09 | 0.195258E+10 | 0.644197E+09 | 0.130838E+10 | 0.00 | 0.00 |
August | 0.411442E+10 | 0.729944E+09 | 0.215377E+10 | 0.920051E+09 | 0.123372E+10 | 0.00 | 0.00 |
September | 0.392172E+10 | 0.680450E+09 | 0.192824E+10 | 0.745766E+09 | 0.118248E+10 | 0.00 | 0.00 |
October | 0.347990E+10 | 0.792436E+09 | 0.182350E+10 | 0.644637E+09 | 0.117886E+10 | 0.00 | 0.00 |
November | 0.332207E+10 | 0.906124E+09 | 0.168111E+10 | 0.633241E+09 | 0.104787E+10 | 0.00 | 0.00 |
December | 0.348619E+10 | 0.122754E+10 | 0.175779E+10 | 0.788085E+09 | 0.969703E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.493551E+11 | 0.101172E+11 | 0.245545E+11 | 0.111952E+11 | 0.133593E+11 | 0.00 | 0.00 |
Minimum of Months | 0.332207E+10 | 0.553302E+09 | 0.168111E+10 | 0.633241E+09 | 0.951279E+09 | 0.00 | 0.00 |
Maximum of Months | 0.514323E+10 | 0.122754E+10 | 0.253029E+10 | 0.147960E+10 | 0.130838E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.631511E+11 | 0.206291E+11 | 0.872315E+10 | 0.417254E+10 | 0.455061E+10 | 0.00 | 0.00 |
February | 0.717940E+11 | 0.209894E+11 | 0.906683E+10 | 0.468986E+10 | 0.437697E+10 | 0.00 | 0.00 |
March | 0.880115E+11 | 0.217337E+11 | 0.116502E+11 | 0.681580E+10 | 0.483438E+10 | 0.00 | 0.00 |
April | 0.874297E+11 | 0.172657E+11 | 0.113950E+11 | 0.636179E+10 | 0.503319E+10 | 0.00 | 0.00 |
May | 0.860559E+11 | 0.167506E+11 | 0.987187E+10 | 0.427579E+10 | 0.559607E+10 | 0.00 | 0.00 |
June | 0.900849E+11 | 0.163091E+11 | 0.103256E+11 | 0.509349E+10 | 0.523209E+10 | 0.00 | 0.00 |
July | 0.688003E+11 | 0.177269E+11 | 0.898809E+10 | 0.296805E+10 | 0.602004E+10 | 0.00 | 0.00 |
August | 0.772467E+11 | 0.166153E+11 | 0.991783E+10 | 0.424133E+10 | 0.567650E+10 | 0.00 | 0.00 |
September | 0.694627E+11 | 0.164460E+11 | 0.887769E+10 | 0.343695E+10 | 0.544074E+10 | 0.00 | 0.00 |
October | 0.570403E+11 | 0.170982E+11 | 0.839154E+10 | 0.296742E+10 | 0.542412E+10 | 0.00 | 0.00 |
November | 0.575653E+11 | 0.172250E+11 | 0.773484E+10 | 0.291344E+10 | 0.482140E+10 | 0.00 | 0.00 |
December | 0.594719E+11 | 0.204410E+11 | 0.808767E+10 | 0.362593E+10 | 0.446174E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.876114E+12 | 0.219230E+12 | 0.113030E+12 | 0.515624E+11 | 0.614679E+11 | 0.00 | 0.00 |
Minimum of Months | 0.570403E+11 | 0.163091E+11 | 0.773484E+10 | 0.291344E+10 | 0.437697E+10 | 0.00 | 0.00 |
Maximum of Months | 0.900849E+11 | 0.217337E+11 | 0.116502E+11 | 0.681580E+10 | 0.602004E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 26.42 | 22.38 | 20.70 | 2.25 | 18.66 | 103.85 | 146.57 | 0.01 |
February | 27.50 | 22.91 | 21.01 | 2.37 | 18.54 | 110.59 | 164.59 | 0.00 |
March | 28.33 | 23.63 | 21.77 | 3.67 | 19.85 | 110.33 | 194.39 | 0.01 |
April | 29.15 | 25.37 | 24.04 | 2.98 | 21.51 | 118.69 | 185.56 | 0.03 |
May | 29.01 | 26.53 | 25.72 | 3.19 | 23.00 | 127.71 | 124.87 | 0.08 |
June | 28.86 | 26.50 | 25.74 | 3.10 | 22.78 | 123.38 | 156.09 | 0.05 |
July | 27.25 | 24.29 | 23.20 | 2.32 | 21.53 | 137.39 | 88.28 | 0.02 |
August | 27.54 | 25.86 | 25.31 | 3.22 | 21.55 | 129.55 | 122.00 | 0.07 |
September | 27.58 | 25.59 | 24.93 | 2.22 | 22.01 | 128.30 | 103.37 | 0.04 |
October | 26.89 | 25.07 | 24.46 | 2.18 | 21.39 | 123.79 | 92.41 | 0.11 |
November | 26.68 | 24.14 | 23.20 | 1.94 | 20.29 | 113.70 | 103.30 | 0.02 |
December | 25.97 | 22.85 | 21.57 | 2.00 | 18.63 | 101.83 | 131.96 | 0.00 |
Annual Sum or Average | 27.59 | 24.60 | 23.48 | 2.62 | 20.82 | 119.14 | 134.17 | 0.04 |
Minimum of Months | 25.97 | 22.38 | 20.70 | 1.94 | 18.54 | 101.83 | 88.28 | 0.00 |
Maximum of Months | 29.15 | 26.53 | 25.74 | 3.67 | 23.00 | 137.39 | 194.39 | 0.11 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 34.10 | 04-JAN-12:00 | 23.67 | 19.40 | 5.00 | 24.66 | 266.50 | 576.50 |
February | 35.00 | 21-FEB-13:00 | 22.02 | 16.00 | 2.10 | 24.16 | 230.00 | 672.50 |
March | 36.40 | 21-MAR-12:00 | 23.01 | 17.00 | 5.00 | 26.97 | 269.50 | 658.50 |
April | 35.50 | 01-APR-13:00 | 26.96 | 24.00 | 2.50 | 27.14 | 295.50 | 519.50 |
May | 37.60 | 06-MAY-12:00 | 26.43 | 22.60 | 4.00 | 29.39 | 317.00 | 525.50 |
June | 36.00 | 12-JUN-14:00 | 27.60 | 25.00 | 4.00 | 28.43 | 235.00 | 472.00 |
July | 33.20 | 15-JUL-15:00 | 25.63 | 23.00 | 2.00 | 27.95 | 219.00 | 181.00 |
August | 34.00 | 10-AUG-13:00 | 27.86 | 26.00 | 5.00 | 26.65 | 344.50 | 278.50 |
September | 34.00 | 06-SEP-13:00 | 26.51 | 24.00 | 4.00 | 25.00 | 258.00 | 581.50 |
October | 33.00 | 04-OCT-13:00 | 26.23 | 24.00 | 4.00 | 25.16 | 303.00 | 428.50 |
November | 34.30 | 18-NOV-12:00 | 25.34 | 22.20 | 3.00 | 25.49 | 289.50 | 511.50 |
December | 33.00 | 07-DEC-13:00 | 23.23 | 19.00 | 3.00 | 22.98 | 215.00 | 596.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 33.00 | 22.02 | 16.00 | 2.00 | 22.98 | 215.00 | 181.00 | |
Maximum of Months | 37.60 | 27.86 | 26.00 | 5.00 | 29.39 | 344.50 | 672.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 18.70 | 23-JAN-05:00 | 16.92 | 16.00 | 2.00 | 7.75 | 0.00 | 0.00 |
February | 20.30 | 21-FEB-09:00 | 19.04 | 18.40 | 2.00 | 10.50 | 258.50 | 564.00 |
March | 22.00 | 03-MAR-05:00 | 19.94 | 19.00 | 3.00 | 13.35 | 0.00 | 0.00 |
April | 22.90 | 14-APR-15:00 | 22.90 | 22.90 | 3.00 | 14.65 | 199.50 | 264.50 |
May | 22.00 | 10-MAY-19:00 | 22.00 | 22.00 | 2.00 | 18.28 | 0.00 | 0.00 |
June | 23.00 | 20-JUN-23:00 | 23.00 | 23.00 | 2.00 | 19.35 | 0.00 | 0.00 |
July | 23.00 | 13-JUL-04:00 | 22.27 | 22.00 | 0.00 | 13.91 | 0.00 | 0.00 |
August | 22.00 | 20-AUG-10:00 | 22.00 | 22.00 | 5.00 | 18.28 | 430.50 | 41.50 |
September | 22.90 | 19-SEP-03:00 | 22.78 | 22.78 | 0.00 | 21.27 | 0.00 | 0.00 |
October | 22.50 | 23-OCT-04:00 | 22.50 | 22.50 | 2.80 | 18.82 | 0.00 | 0.00 |
November | 20.00 | 25-NOV-04:00 | 18.63 | 18.00 | 2.00 | 10.69 | 0.00 | 0.00 |
December | 18.00 | 21-DEC-04:00 | 17.36 | 17.00 | 3.00 | 9.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.00 | 16.92 | 16.00 | 0.00 | 7.75 | 0.00 | 0.00 | |
Maximum of Months | 23.00 | 23.00 | 23.00 | 5.00 | 21.27 | 430.50 | 564.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 25.53 | 12-JAN-12:00 | 32.40 | 23.10 | 2.00 | 25.00 | 353.00 | 347.00 |
February | 26.17 | 14-FEB-15:00 | 32.30 | 24.20 | 2.00 | 25.16 | 200.00 | 199.00 |
March | 26.28 | 27-MAR-12:00 | 34.20 | 23.60 | 4.00 | 26.32 | 326.00 | 535.00 |
April | 27.93 | 10-APR-16:49 | 31.52 | 26.85 | 4.08 | 27.70 | 110.67 | 57.00 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 30.11 | 15-JUN-09:00 | 33.20 | 29.20 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.43 | 20-JUL-14:00 | 32.80 | 24.20 | 1.00 | 26.65 | 305.00 | 253.00 |
August | 28.81 | 14-AUG-16:00 | 32.00 | 28.00 | 1.00 | 25.16 | 107.50 | 223.00 |
September | 30.06 | 30-SEP-10:00 | 32.80 | 29.40 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 27.36 | 16-OCT-14:00 | 31.50 | 26.00 | 3.00 | 24.16 | 239.00 | 346.50 |
November | 27.56 | 10-NOV-12:00 | 31.00 | 26.40 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.86 | 03-DEC-12:00 | 31.50 | 25.30 | 1.00 | 23.49 | 301.00 | 468.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 25.53 | 29.00 | 23.10 | 1.00 | 22.47 | 0.00 | 0.00 | |
Maximum of Months | 30.11 | 34.20 | 29.40 | 6.00 | 28.11 | 398.00 | 535.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.20 | 09-JAN-21:00 | 26.50 | 24.77 | 4.00 | 25.16 | 0.00 | 0.00 |
February | 24.40 | 15-FEB-18:00 | 28.30 | 25.33 | 4.00 | 20.75 | 0.00 | 0.00 |
March | 25.30 | 28-MAR-06:00 | 27.20 | 25.72 | 3.00 | 19.87 | 103.00 | 28.00 |
April | 27.00 | 10-APR-17:00 | 30.50 | 27.87 | 4.50 | 25.00 | 20.00 | 20.50 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 29.20 | 15-JUN-09:00 | 33.20 | 30.11 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.00 | 10-JUL-14:00 | 26.50 | 26.11 | 2.30 | 23.49 | 286.00 | 36.50 |
August | 28.00 | 02-AUG-10:00 | 31.00 | 28.65 | 4.00 | 24.16 | 419.00 | 195.50 |
September | 29.40 | 30-SEP-10:00 | 32.80 | 30.06 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 26.50 | 16-OCT-08:00 | 29.00 | 27.04 | 2.50 | 21.78 | 300.00 | 326.00 |
November | 26.40 | 10-NOV-12:00 | 31.00 | 27.56 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.00 | 10-DEC-17:00 | 29.00 | 26.74 | 3.00 | 21.78 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.20 | 26.50 | 24.77 | 2.30 | 19.87 | 0.00 | 0.00 | |
Maximum of Months | 29.40 | 33.20 | 30.11 | 6.00 | 28.11 | 419.00 | 421.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 29.71 | 38.82 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 29.90 | 44.34 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 30.35 | 50.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 30.97 | 51.18 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.58 | 43.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 32.02 | 46.77 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 32.16 | 39.95 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 31.97 | 43.65 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 31.50 | 40.53 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.87 | 37.35 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 30.27 | 35.77 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 29.84 | 36.19 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 30.93 | 42.35 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 29.71 | 35.77 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 32.16 | 51.18 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.596046E+09 | -522963982.2 | 0.00 | 0.00 | 744.00 | 0.00 | -73081693.5 | 58.99 | 0.00 | 0.00 |
February | 0.543475E+09 | -477407581.1 | 0.00 | 0.00 | 672.00 | 0.00 | -66067773.4 | 58.99 | 0.00 | 0.00 |
March | 0.622768E+09 | -549160737.4 | 0.00 | 0.00 | 744.00 | 0.00 | -73607636.3 | 58.99 | 0.00 | 0.00 |
April | 0.569965E+09 | -499156991.0 | 0.00 | 0.00 | 720.00 | 0.00 | -70807940.2 | 58.99 | 0.00 | 0.00 |
May | 0.580936E+09 | -507774314.6 | 0.00 | 0.00 | 744.00 | 0.00 | -73161816.9 | 58.99 | 0.00 | 0.00 |
June | 0.569359E+09 | -498266585.4 | 0.00 | 0.00 | 720.00 | 0.00 | -71092478.8 | 58.99 | 0.00 | 0.00 |
July | 0.552039E+09 | -479124059.4 | 0.00 | 0.00 | 744.00 | 0.00 | -72914788.7 | 58.99 | 0.00 | 0.00 |
August | 0.591930E+09 | -518258782.3 | 0.00 | 0.00 | 744.00 | 0.00 | -73671098.9 | 58.99 | 0.00 | 0.00 |
September | 0.560922E+09 | -490101132.1 | 0.00 | 0.00 | 720.00 | 0.00 | -70820876.2 | 58.99 | 0.00 | 0.00 |
October | 0.575284E+09 | -502265738.1 | 0.00 | 0.00 | 744.00 | 0.00 | -73018591.7 | 58.99 | 0.00 | 0.00 |
November | 0.563392E+09 | -492726810.3 | 0.00 | 0.00 | 720.00 | 0.00 | -70665277.3 | 58.99 | 0.00 | 0.00 |
December | 0.593684E+09 | -520530855.6 | 0.00 | 0.00 | 744.00 | 0.00 | -73153144.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.691980E+10 | -0.605774E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -862063116.3 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.543475E+09 | -549160737.4 | 0.00 | 0.00 | 672.00 | 0.00 | -73671098.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.622768E+09 | -477407581.1 | 0.00 | 0.00 | 744.00 | 0.00 | -66067773.4 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.71 | 0.50 | 01-JAN-11:00 | 281.42 | 0.00 | 0.00 | 157.00 | 229.89 | 0.00 | 0.00 | 114.00 |
February | 321.17 | 0.70 | 0.50 | 01-FEB-10:30 | 302.50 | 0.00 | 0.00 | 154.50 | 248.88 | 0.00 | 0.00 | 117.50 |
March | 361.17 | 0.69 | 0.50 | 01-MAR-09:00 | 772.31 | 0.00 | 0.00 | 183.83 | 1359.89 | 0.00 | 0.00 | 131.83 |
April | 358.33 | 0.70 | 0.50 | 01-APR-10:20 | 784.81 | 0.00 | 0.00 | 188.17 | 229.76 | 0.00 | 0.00 | 104.33 |
May | 376.33 | 0.72 | 0.50 | 01-MAY-11:50 | 347.24 | 0.00 | 0.00 | 201.33 | 197.88 | 0.00 | 0.00 | 60.00 |
June | 370.50 | 0.73 | 0.50 | 01-JUN-10:00 | 338.71 | 0.00 | 0.00 | 197.33 | 182.85 | 0.00 | 0.00 | 28.83 |
July | 383.17 | 0.72 | 0.50 | 01-JUL-10:50 | 350.01 | 0.00 | 0.00 | 202.67 | 193.75 | 0.00 | 0.00 | 67.67 |
August | 369.33 | 0.70 | 0.50 | 01-AUG-10:00 | 419.78 | 0.00 | 0.00 | 205.33 | 225.10 | 0.00 | 0.00 | 108.00 |
September | 357.83 | 0.69 | 0.50 | 01-SEP-09:39 | 848.01 | 0.00 | 0.00 | 191.67 | 630.45 | 0.00 | 0.00 | 143.00 |
October | 356.83 | 0.69 | 0.50 | 01-OCT-09:39 | 344.59 | 0.00 | 0.00 | 187.33 | 596.49 | 0.00 | 0.00 | 147.83 |
November | 337.67 | 0.70 | 0.50 | 01-NOV-09:39 | 309.04 | 0.00 | 0.00 | 165.00 | 248.44 | 0.00 | 0.00 | 125.67 |
December | 349.33 | 0.71 | 0.50 | 01-DEC-09:39 | 657.68 | 0.00 | 0.00 | 164.83 | 223.85 | 0.00 | 0.00 | 109.33 |
Annual Sum or Average | 4292.33 | 0.70 | 480.35 | 0.00 | 0.00 | 2199.00 | 380.71 | 0.00 | 0.00 | 1258.00 | ||
Minimum of Months | 321.17 | 0.69 | 0.50 | 281.42 | 0.00 | 0.00 | 154.50 | 182.85 | 0.00 | 0.00 | 28.83 | |
Maximum of Months | 383.17 | 0.73 | 0.50 | 848.01 | 0.00 | 0.00 | 205.33 | 1359.89 | 0.00 | 0.00 | 147.83 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.62 | 0.50 | 01-JAN-08:30 | 314.32 | 14.19 | 0.00 | 242.83 | 266.15 | 17.73 | 88.33 | 205.83 |
February | 321.17 | 0.61 | 0.50 | 01-FEB-08:20 | 340.85 | 14.34 | 0.00 | 231.17 | 290.82 | 17.98 | 90.67 | 198.00 |
March | 361.17 | 0.60 | 0.50 | 01-MAR-08:09 | 1165.77 | 14.49 | 0.00 | 269.33 | 1986.33 | 19.79 | 104.00 | 228.33 |
April | 358.33 | 0.60 | 0.50 | 01-APR-07:40 | 363.05 | 14.73 | 0.00 | 268.50 | 310.69 | 18.53 | 105.67 | 228.50 |
May | 376.33 | 0.60 | 0.50 | 01-MAY-07:30 | 370.46 | 14.56 | 0.00 | 277.17 | 322.64 | 18.02 | 93.00 | 243.67 |
June | 370.50 | 0.60 | 0.50 | 01-JUN-07:49 | 1512.88 | 15.80 | 36.67 | 271.67 | 325.37 | 18.32 | 105.67 | 237.83 |
July | 383.17 | 0.61 | 0.50 | 01-JUL-07:30 | 371.96 | 14.32 | 0.00 | 275.83 | 329.20 | 17.62 | 92.17 | 242.17 |
August | 369.33 | 0.60 | 0.50 | 01-AUG-07:30 | 384.67 | 14.82 | 0.00 | 276.83 | 335.30 | 18.31 | 100.00 | 243.83 |
September | 357.83 | 0.60 | 0.50 | 01-SEP-07:30 | 370.78 | 14.32 | 0.00 | 259.67 | 340.15 | 19.06 | 111.33 | 239.17 |
October | 356.83 | 0.60 | 0.50 | 01-OCT-07:40 | 691.01 | 15.61 | 35.50 | 257.83 | 342.78 | 18.76 | 96.33 | 232.67 |
November | 337.67 | 0.61 | 0.50 | 01-NOV-07:49 | 341.31 | 14.64 | 0.00 | 239.33 | 290.58 | 18.08 | 87.50 | 207.83 |
December | 349.33 | 0.62 | 0.50 | 01-DEC-07:49 | 306.89 | 14.11 | 0.00 | 238.67 | 258.66 | 17.60 | 75.67 | 203.33 |
Annual Sum or Average | 4292.33 | 0.61 | 549.13 | 14.67 | 72.17 | 3108.83 | 451.95 | 18.32 | 1150.33 | 2711.17 | ||
Minimum of Months | 321.17 | 0.60 | 0.50 | 306.89 | 14.11 | 0.00 | 231.17 | 258.66 | 17.60 | 75.67 | 198.00 | |
Maximum of Months | 383.17 | 0.62 | 0.50 | 1512.88 | 15.80 | 36.67 | 277.17 | 1986.33 | 19.79 | 111.33 | 243.83 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.178451E+11 | 0.132724E+11 | 34551.76 | 02-JAN-00:01 | 18748.47 | 0.00 |
February | 0.00 | 0.00 | 0.171678E+11 | 0.128780E+11 | 33532.71 | 06-FEB-00:01 | 19635.17 | 0.00 |
March | 0.00 | 0.00 | 0.219733E+11 | 0.159685E+11 | 33738.38 | 26-MAR-23:01 | 19565.49 | 0.00 |
April | 0.00 | 0.00 | 0.224390E+11 | 0.153782E+11 | 34255.34 | 09-APR-23:01 | 17737.35 | 0.00 |
May | 0.00 | 0.00 | 0.249970E+11 | 0.159866E+11 | 33934.53 | 21-MAY-23:04 | 12991.95 | 0.00 |
June | 0.00 | 0.00 | 0.254031E+11 | 0.162980E+11 | 34447.82 | 25-JUN-23:01 | 19060.83 | 0.00 |
July | 0.00 | 0.00 | 0.202662E+11 | 0.140904E+11 | 34184.09 | 02-JUL-23:01 | 18998.94 | 0.00 |
August | 0.00 | 0.00 | 0.240325E+11 | 0.151296E+11 | 34823.74 | 20-AUG-23:01 | 16259.30 | 0.00 |
September | 0.00 | 0.00 | 0.213148E+11 | 0.139356E+11 | 34527.05 | 24-SEP-23:01 | 16838.52 | 0.00 |
October | 0.00 | 0.00 | 0.201696E+11 | 0.131581E+11 | 34823.74 | 01-OCT-23:02 | 17508.40 | 0.00 |
November | 0.00 | 0.00 | 0.185152E+11 | 0.126870E+11 | 34314.60 | 13-NOV-00:02 | 16783.92 | 0.00 |
December | 0.00 | 0.00 | 0.173574E+11 | 0.126715E+11 | 34442.41 | 11-DEC-00:01 | 18844.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.251481E+12 | 0.171454E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.171678E+11 | 0.126715E+11 | 33532.71 | 12991.95 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.254031E+11 | 0.162980E+11 | 34823.74 | 19635.17 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.401994E+11 | 0.281768E+11 | 101614.98 | 09-JAN-00:01 | 59935.37 | 0.00 |
February | 0.00 | 0.00 | 0.417661E+11 | 0.295816E+11 | 98239.18 | 06-FEB-00:01 | 58747.83 | 0.00 |
March | 0.00 | 0.00 | 0.546689E+11 | 0.375902E+11 | 97805.87 | 05-MAR-09:23 | 63374.33 | 0.00 |
April | 0.00 | 0.00 | 0.589171E+11 | 0.381259E+11 | 100760.54 | 02-APR-23:01 | 58522.84 | 0.00 |
May | 0.00 | 0.00 | 0.630714E+11 | 0.377623E+11 | 101384.31 | 07-MAY-23:01 | 57189.66 | 0.00 |
June | 0.00 | 0.00 | 0.656059E+11 | 0.394925E+11 | 101433.67 | 26-JUN-17:42 | 62002.15 | 0.00 |
July | 0.00 | 0.00 | 0.488355E+11 | 0.315469E+11 | 98005.05 | 02-JUL-09:23 | 62512.55 | 0.00 |
August | 0.00 | 0.00 | 0.544323E+11 | 0.311163E+11 | 104031.96 | 06-AUG-09:13 | 53821.79 | 0.00 |
September | 0.00 | 0.00 | 0.510009E+11 | 0.307573E+11 | 100817.00 | 17-SEP-09:33 | 59428.55 | 0.00 |
October | 0.00 | 0.00 | 0.448873E+11 | 0.267521E+11 | 102943.17 | 01-OCT-23:01 | 60224.60 | 0.00 |
November | 0.00 | 0.00 | 0.414046E+11 | 0.263060E+11 | 99348.65 | 11-NOV-09:23 | 61191.85 | 0.00 |
December | 0.00 | 0.00 | 0.384300E+11 | 0.260526E+11 | 99022.10 | 24-DEC-10:13 | 59836.96 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.603219E+12 | 0.383261E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.384300E+11 | 0.260526E+11 | 97805.87 | 53821.79 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.656059E+11 | 0.394925E+11 | 104031.96 | 63374.33 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.187301E+10 | 0.65 | 1425.21 | 02-JAN-00:15 | 0.89 |
February | 0.174912E+10 | 0.67 | 1425.21 | 01-FEB-07:47 | 0.90 |
March | 0.211579E+10 | 0.72 | 1425.21 | 01-MAR-07:05 | 0.90 |
April | 0.203100E+10 | 0.69 | 1425.21 | 01-APR-06:30 | 0.90 |
May | 0.213316E+10 | 0.69 | 1425.21 | 01-MAY-05:05 | 0.90 |
June | 0.214168E+10 | 0.72 | 1425.21 | 01-JUN-06:30 | 0.89 |
July | 0.195688E+10 | 0.66 | 1425.21 | 01-JUL-07:40 | 0.90 |
August | 0.214408E+10 | 0.71 | 1425.21 | 01-AUG-07:00 | 0.89 |
September | 0.196363E+10 | 0.68 | 1425.21 | 01-SEP-06:40 | 0.89 |
October | 0.192735E+10 | 0.65 | 1425.21 | 02-OCT-07:10 | 0.89 |
November | 0.182479E+10 | 0.64 | 1425.21 | 01-NOV-07:45 | 0.89 |
December | 0.184711E+10 | 0.64 | 1425.21 | 01-DEC-07:50 | 0.89 |
Annual Sum or Average | 0.237076E+11 | 0.68 | |||
Minimum of Months | 0.174912E+10 | 0.64 | 1425.21 | 0.89 | |
Maximum of Months | 0.214408E+10 | 0.72 | 1425.21 | 0.90 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.172966E+10 | 0.32 | 3670.63 | 02-JAN-00:01 | 0.86 |
February | 0.167073E+10 | 0.35 | 3670.63 | 05-FEB-13:02 | 0.87 |
March | 0.209114E+10 | 0.40 | 3670.63 | 05-MAR-09:23 | 0.86 |
April | 0.212797E+10 | 0.44 | 3670.63 | 01-APR-17:06 | 0.86 |
May | 0.223751E+10 | 0.43 | 3670.63 | 01-MAY-17:06 | 0.86 |
June | 0.230493E+10 | 0.45 | 3670.63 | 04-JUN-10:43 | 0.86 |
July | 0.191370E+10 | 0.38 | 3670.63 | 02-JUL-09:23 | 0.86 |
August | 0.203126E+10 | 0.37 | 3670.63 | 01-AUG-17:06 | 0.86 |
September | 0.192175E+10 | 0.39 | 3670.63 | 02-SEP-17:06 | 0.86 |
October | 0.182107E+10 | 0.35 | 3670.63 | 01-OCT-10:03 | 0.86 |
November | 0.169915E+10 | 0.33 | 3670.63 | 05-NOV-11:32 | 0.87 |
December | 0.170588E+10 | 0.30 | 3670.63 | 03-DEC-12:43 | 0.87 |
Annual Sum or Average | 0.232547E+11 | 0.37 | |||
Minimum of Months | 0.167073E+10 | 0.30 | 3670.63 | 0.86 | |
Maximum of Months | 0.230493E+10 | 0.45 | 3670.63 | 0.87 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.593269E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.571032E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.722544E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.725388E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.790518E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.802242E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.652541E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.754507E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.677184E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.641762E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.596774E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.576106E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.810387E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.571032E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.802242E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.126654E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.131054E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.170964E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.181859E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.192644E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.199644E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.149706E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.163659E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.154624E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.136794E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.127381E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.120867E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.185585E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.120867E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.199644E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.187301E+10 | 0.178451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174912E+10 | 0.171678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.211579E+10 | 0.219733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.203100E+10 | 0.224390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.213316E+10 | 0.249970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.214168E+10 | 0.254031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195688E+10 | 0.202662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.214408E+10 | 0.240325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.196363E+10 | 0.213148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.192735E+10 | 0.201696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182479E+10 | 0.185152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184711E+10 | 0.173574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237076E+11 | 0.251481E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.174912E+10 | 0.171678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.214408E+10 | 0.254031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.172966E+10 | 0.401994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167073E+10 | 0.417661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.209114E+10 | 0.546689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.212797E+10 | 0.589171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.223751E+10 | 0.630714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.230493E+10 | 0.656059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.191370E+10 | 0.488355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.203126E+10 | 0.544323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.192175E+10 | 0.510009E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.182107E+10 | 0.448873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169915E+10 | 0.414046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170588E+10 | 0.384300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232547E+11 | 0.603219E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.167073E+10 | 0.384300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.230493E+10 | 0.656059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.187301E+10 | 0.00 | 0.00 | 0.00 | 0.405967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174912E+10 | 0.00 | 0.00 | 0.00 | 0.396120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.211579E+10 | 0.00 | 0.00 | 0.00 | 0.510965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.203100E+10 | 0.00 | 0.00 | 0.00 | 0.522288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.213316E+10 | 0.00 | 0.00 | 0.00 | 0.577202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.214168E+10 | 0.00 | 0.00 | 0.00 | 0.588074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195688E+10 | 0.00 | 0.00 | 0.00 | 0.456853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.214408E+10 | 0.00 | 0.00 | 0.00 | 0.540099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.196363E+10 | 0.00 | 0.00 | 0.00 | 0.480821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.192735E+10 | 0.00 | 0.00 | 0.00 | 0.449027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182479E+10 | 0.00 | 0.00 | 0.00 | 0.414295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184711E+10 | 0.00 | 0.00 | 0.00 | 0.391395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237076E+11 | 0.00 | 0.00 | 0.00 | 0.573311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.174912E+10 | 0.00 | 0.00 | 0.00 | 0.391395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.214408E+10 | 0.00 | 0.00 | 0.00 | 0.588074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.172966E+10 | 0.00 | 0.00 | 0.00 | 0.109357E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167073E+10 | 0.00 | 0.00 | 0.00 | 0.114346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.209114E+10 | 0.00 | 0.00 | 0.00 | 0.150053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.212797E+10 | 0.00 | 0.00 | 0.00 | 0.160579E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.223751E+10 | 0.00 | 0.00 | 0.00 | 0.170269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.230493E+10 | 0.00 | 0.00 | 0.00 | 0.176594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.191370E+10 | 0.00 | 0.00 | 0.00 | 0.130569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.203126E+10 | 0.00 | 0.00 | 0.00 | 0.143346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.192175E+10 | 0.00 | 0.00 | 0.00 | 0.135407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.182107E+10 | 0.00 | 0.00 | 0.00 | 0.118584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169915E+10 | 0.00 | 0.00 | 0.00 | 0.110389E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170588E+10 | 0.00 | 0.00 | 0.00 | 0.103808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232547E+11 | 0.00 | 0.00 | 0.00 | 0.162330E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.167073E+10 | 0.00 | 0.00 | 0.00 | 0.103808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.230493E+10 | 0.00 | 0.00 | 0.00 | 0.176594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.261602E+10 | 0.00 | 287986.46 | 0.00 | 0.00 | 388089.06 | 0.00 | 0.18 |
February | 0.00 | 0.265974E+10 | 0.00 | 16704.10 | 0.00 | 0.00 | 53850.32 | 0.00 | 0.19 |
March | 0.00 | 0.356555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
April | 0.00 | 0.438959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
May | 0.00 | 0.532454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
June | 0.00 | 0.547606E+10 | 0.00 | 1975.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
July | 0.00 | 0.364866E+10 | 0.00 | 92374.79 | 0.00 | 0.00 | 14390.61 | 0.00 | 0.19 |
August | 0.00 | 0.500019E+10 | 0.00 | 86827.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
September | 0.00 | 0.443596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
October | 0.00 | 0.399150E+10 | 0.00 | 56104.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
November | 0.00 | 0.332130E+10 | 0.00 | 67893.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
December | 0.00 | 0.273585E+10 | 0.00 | 29440.28 | 125859.04 | 0.00 | 20913.44 | 0.00 | 0.18 |
Annual Sum or Average | 0.00 | 0.471650E+11 | 0.00 | 639306.65 | 125859.04 | 0.00 | 477243.42 | 0.00 | 0.19 |
Minimum of Months | 0.00 | 0.261602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
Maximum of Months | 0.00 | 0.547606E+10 | 0.00 | 287986.46 | 125859.04 | 0.00 | 388089.06 | 0.00 | 0.21 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 8530542.38 | 0.763370E+10 | 0.00 | 1107928.34 | 0.00 | 0.00 | 76872404.55 | 0.00 | 0.22 |
February | 499848.42 | 0.827515E+10 | 0.00 | 523810.99 | 0.00 | 0.00 | 20526268.94 | 0.00 | 0.23 |
March | 0.00 | 0.107632E+11 | 0.00 | 119249.98 | 1203157.00 | 0.00 | 2871385.44 | 0.00 | 0.25 |
April | 0.00 | 0.140434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
May | 0.00 | 0.167190E+11 | 0.00 | 0.00 | 1432018.84 | 0.00 | 0.00 | 0.00 | 0.26 |
June | 0.00 | 0.177323E+11 | 0.00 | 0.00 | 1448220.10 | 0.00 | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.113036E+11 | 0.00 | 0.00 | 2590647.20 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.147417E+11 | 0.00 | 18892.28 | 0.00 | 0.00 | 416273.77 | 0.00 | 0.25 |
September | 0.00 | 0.138692E+11 | 0.00 | 0.00 | 3048489.86 | 0.00 | 0.00 | 0.00 | 0.24 |
October | 0.00 | 0.117820E+11 | 0.00 | 8712.09 | 2148773.33 | 0.00 | 360085.72 | 0.00 | 0.23 |
November | 0.00 | 0.100490E+11 | 0.00 | 144635.96 | 2561177.16 | 0.00 | 9415004.92 | 0.00 | 0.22 |
December | 6721647.75 | 0.801081E+10 | 0.00 | 686604.78 | 0.00 | 0.00 | 48465930.01 | 0.00 | 0.22 |
Annual Sum or Average | 15752038.55 | 0.144923E+12 | 0.00 | 2609834.41 | 14432483.50 | 0.00 | 0.158927E+09 | 0.00 | 0.24 |
Minimum of Months | 0.00 | 0.763370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
Maximum of Months | 8530542.38 | 0.177323E+11 | 0.00 | 1107928.34 | 3048489.86 | 0.00 | 76872404.55 | 0.00 | 0.27 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:45
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.823079E+12 | 0.541601E+11 | 0.00 | -0.145205E+11 | 0.730399E+11 |
February | 0.820619E+12 | 0.587884E+11 | 0.00 | -0.158337E+11 | 0.743297E+11 |
March | 0.107336E+13 | 0.767896E+11 | 0.00 | -0.191100E+11 | 0.967571E+11 |
April | 0.106552E+13 | 0.797115E+11 | 0.00 | -0.251058E+11 | 0.102637E+12 |
May | 0.102797E+13 | 0.691620E+11 | 0.00 | -0.300872E+11 | 0.110867E+12 |
June | 0.105425E+13 | 0.793979E+11 | 0.00 | -0.304462E+11 | 0.114549E+12 |
July | 0.874819E+12 | 0.676985E+11 | 0.00 | -0.229214E+11 | 0.867271E+11 |
August | 0.110932E+13 | 0.603133E+11 | 0.00 | -0.265707E+11 | 0.982004E+11 |
September | 0.872104E+12 | 0.635340E+11 | 0.00 | -0.264417E+11 | 0.906646E+11 |
October | 0.937301E+12 | 0.546467E+11 | 0.00 | -0.241103E+11 | 0.814055E+11 |
November | 0.774495E+12 | 0.519673E+11 | 0.00 | -0.206190E+11 | 0.751016E+11 |
December | 0.772115E+12 | 0.523183E+11 | 0.00 | -0.159257E+11 | 0.700822E+11 |
Annual Sum or Average | 0.112050E+14 | 0.768488E+12 | 0.00 | -0.271692E+12 | 0.107436E+13 |
Minimum of Months | 0.772115E+12 | 0.519673E+11 | 0.00 | -0.304462E+11 | 0.700822E+11 |
Maximum of Months | 0.110932E+13 | 0.797115E+11 | 0.00 | -0.145205E+11 | 0.114549E+12 |