Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2023-10-16 10:41:48
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1675.62 | 346.55 | 346.55 |
Net Site Energy | 1675.62 | 346.55 | 346.55 |
Total Source Energy | 3099.84 | 641.11 | 641.11 |
Net Source Energy | 3099.84 | 641.11 | 641.11 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1059.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 13.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 305.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 92.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 137.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 40.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 616.16 | 1059.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1059.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 13.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 305.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 92.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 137.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 40.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1059.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 13.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 305.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 92.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 137.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 40.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 26.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 82.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 16.71 | 219.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 127.43 | 219.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 82.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 16.71 | 219.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 127.43 | 219.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 616.163 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 616.163 | 100.00 |
Total On-Site and Utility Electric Sources | 616.163 | 100.00 |
Total Electricity End Uses | 616.163 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 68.33 |
Time Setpoint Not Met During Occupied Cooling | 3.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3023.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 135.81 |
Skylight-Roof Ratio [%] | 2.95 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 9.9957 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 10.2257 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 6.2431 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.5746 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.5746 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 9.9957 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 10.2257 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 6.2431 | 46.45 | 2.5587 | |
Total | 4835.13 | 7.5746 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 7.5746 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 7.5746 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-DEC-16:00 | 12-JAN-08:00 | - | - | - | - | - | - | - | - | - | - | 16-AUG-11:20 |
Heating | 0.00 | 341343.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 27270.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3551.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1619.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 49482.24 | 341343.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 341343.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 27270.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 3551.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1619.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1148.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 43.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 967.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 293.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 434.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 128.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 83.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1951.39 | 1148.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 237.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 9.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 200.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 26.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 403.59 | 237.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 237.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 9.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 200.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 26.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 403.59 | 237.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.09 |
ZONE2 FINE STORAGE DIRECT AIR | 2.78 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 5.16 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 5.16 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 205986.40 |
PSZ-OFFICE HEATING COIL | 28883.48 |
PSZ-FINE STORAGE HEATING COIL | 96109.25 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 205986.40 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.09 | 1.09 | 1.09 | 1.09 | 1.09 | 1.09 | 1.00 | 1.000000 | 1.09 |
PSZ-FINE STORAGE | 2.78 | 2.78 | 2.78 | 2.78 | 2.78 | 2.78 | 1.00 | 1.00 | 2.78 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.09 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.78 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.09 | 1207.28 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.78 | 2973.82 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.09 | 1.09 | 1.09 | 1.09 | 20104.73 | 28883.48 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.78 | 2.78 | 2.78 | 1.83 | 64674.72 | 96109.25 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.09 | 0.545213 | 0.726953 | 20104.73 | 10052.36 | 0.800090 | 0.800090 |
PSZ-FINE STORAGE COOLING COIL | 2.78 | 1.39 | 1.85 | 64674.72 | 32337.36 | 0.721520 | 0.721520 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 9.996 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.069 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 10.226 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.226 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 6.243 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 8.802 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2367.778 | 9.996 | 185.726 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2367.778 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 14248.589 | 10.226 | 474.953 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 14248.589 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 20008.023 | 6.243 | 289.971 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20008.023 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3263 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5039 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.4896 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.7823 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.7823 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.065 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.984 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.943 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.179 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.179 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.38866262E-07 | 0.77198350E-12 | 0.86409618E-13 | 0.0000000 |
2 | 1 | -5.2160226 | 0.42725752E-04 | -0.49098391E-04 | 0.74579932E-08 |
3 | 0 | 5.5423254 | 0.32626013 | 0.32635195 | |
4 | 2 | 0.53329527E-11 | 0.16835480E-15 | 0.21851247E-15 | 0.0000000 |
5 | 1 | -5.2159869 | 0.41525994E-04 | -0.31791204E-04 | 0.68735589E-11 |
6 | 0 | 5.7199065 | 0.50387806 | 0.50395137 | |
7 | 4 | 0.78026225E-12 | 0.12659145E-15 | -0.22020359E-14 | 0.11649932E-15 |
8 | 3 | -0.38432829E-03 | 0.34368276E-06 | -0.55745575E-04 | 0.14971848E-12 |
9 | 2 | 1.7386347 | 0.75169100E-02 | 1.1397638 | -0.73682039E-04 |
10 | 1 | -7.1298666 | 0.19478837 | -17.093767 | 0.33322565 |
11 | 0 | 5.7181297 | 0.12420785 | 16.280573 | |
12 | 4 | 0.72249793E-12 | -0.16720573E-15 | 0.22015083E-14 | 0.12409536E-15 |
13 | 3 | -0.36459118E-03 | 0.53555631E-06 | -0.52695411E-04 | 0.13865996E-12 |
14 | 2 | 1.6915239 | 0.11971291E-01 | 1.1039557 | -0.69896550E-04 |
15 | 1 | -7.1930661 | 0.31446443 | -16.864389 | 0.32415671 |
16 | 0 | 6.0306730 | 0.20232993 | 16.289252 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.22015083E-14 | -0.16720573E-15 | 0.72249793E-12 | 0.12409536E-15 |
85 | 3 | -0.52695411E-04 | 0.53555631E-06 | -0.36459118E-03 | 0.13865996E-12 |
86 | 2 | 1.1039557 | 0.11971291E-01 | 1.6915239 | -0.69896550E-04 |
87 | 1 | -16.864389 | 0.31446443 | -7.1930661 | 0.32415671 |
88 | 0 | 16.289252 | 0.20232993 | 6.0306730 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5016_SHGC_SOUTH_0.4 | 34 | 1 | VerySmooth | 2.852 | 2.852 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.5016_SHGC_NORTH_0.4 | 35 | 1 | VerySmooth | 2.852 | 2.852 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.5016_SHGC_EAST_0.4 | 36 | 1 | VerySmooth | 2.852 | 2.852 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.5016_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.852 | 2.852 | 1.000 | 0.401 | ||
5 | SKYLIGHT_U_1.02_SHGC_0.49 | 38 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.491 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.95586E-002 | 0.31435 | 0.46537 | 0.46537 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10843 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.95586E-002 | 0.31435 | 0.46537 | 0.46537 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10843 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.95586E-002 | 0.31435 | 0.46537 | 0.46537 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10843 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.95586E-002 | 0.31435 | 0.46537 | 0.46537 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10843 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.32532 | 0.12431 | 0.12431 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | CurtainWall | 5.547 | 0.455 | 0.435 |
2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.849 | 0.366 | 0.255 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.710 | 8.455E-004 | 5.523E-004 | 0.277 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1992E-004 |
2 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2861E-004 |
3 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0520E-004 |
4 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.5288E-004 |
5 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0154E-004 |
6 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.1058E-004 |
7 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2942E-004 |
8 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8650E-004 |
9 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1826E-004 |
10 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.0589E-004 |
11 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8182E-004 |
12 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.4414E-004 |
13 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9966E-004 |
14 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.6795E-004 |
15 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0772E-004 |
16 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9482E-004 |
17 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.6196E-004 |
18 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1094E-004 |
19 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.8471E-004 |
20 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.3185E-004 |
21 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.7308E-004 |
22 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6521E-004 |
23 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.9148E-004 |
24 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0330E-004 |
25 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.0748E-004 |
26 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2645E-004 |
27 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.2105E-004 |
28 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3616E-004 |
29 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2647E-003 |
30 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0185E-004 |
31 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6700E-003 |
32 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.0218E-005 |
33 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.9097E-004 |
34 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.1528E-005 |
35 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.9963E-004 |
36 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.6110E-005 |
37 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0611E-003 |
38 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.0556E-005 |
39 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.5701E-004 |
40 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.3249E-005 |
41 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.6752E-004 |
42 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6410E-005 |
43 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.0818E-004 |
44 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8713E-005 |
45 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.4919E-004 |
46 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2493E-005 |
47 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3864E-004 |
48 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.0764E-005 |
49 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4125E-003 |
50 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1566E-005 |
51 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7174E-003 |
52 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.5315E-005 |
53 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.1235E-004 |
54 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.3535E-005 |
55 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1104E-004 |
56 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.0887E-005 |
57 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.2772E-003 |
58 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0619E-004 |
59 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5734E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1493E-004 |
61 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3164E-003 |
62 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.3694E-005 |
63 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3917E-003 |
64 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.3634E-005 |
65 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9164E-003 |
66 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7632E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7914E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0035E-004 |
69 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9073E-003 |
70 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1332E-004 |
71 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.4048E-003 |
72 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1670E-005 |
73 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4700E-004 |
74 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.2487E-004 |
75 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2017E-004 |
76 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.0830E-004 |
77 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.4988E-004 |
78 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1870E-004 |
79 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0267E-003 |
80 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1033E-004 |
81 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.7251E-004 |
82 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2302E-003 |
83 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.2401E-004 |
84 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5054E-003 |
85 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5538E-004 |
86 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3965E-004 |
87 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.2865E-004 |
88 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4129E-004 |
89 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3107E-004 |
90 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1319E-003 |
91 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1367E-004 |
92 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4682E-003 |
93 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1032E-004 |
94 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9150E-003 |
95 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4533E-004 |
96 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.8723E-004 |
97 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.7738E-005 |
98 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1544E-003 |
99 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.0908E-005 |
100 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1065E-003 |
101 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8819E-005 |
102 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.1161E-003 |
103 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.0097E-005 |
104 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.9266E-003 |
105 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.5006E-005 |
106 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.5046E-004 |
107 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8845E-005 |
108 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.7865E-004 |
109 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.7015E-005 |
110 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3336E-003 |
111 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.7229E-005 |
112 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5505E-003 |
113 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0819E-005 |
114 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.5280E-005 |
115 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4026E-005 |
116 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2151E-005 |
117 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1648E-005 |
118 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6486E-005 |
119 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1321E-005 |
120 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.9767E-005 |
121 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1630E-005 |
122 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9577E-005 |
123 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9367E-005 |
124 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0841E-005 |
125 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3609E-005 |
126 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9251E-005 |
127 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4814E-005 |
128 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2243E-005 |
129 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9601E-005 |
130 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0569E-005 |
131 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.3475E-005 |
132 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9085E-005 |
133 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.3436E-005 |
134 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0830E-005 |
135 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1298E-005 |
136 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2681E-005 |
137 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6564E-004 |
138 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2096E-004 |
139 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0445E-004 |
140 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5312E-004 |
141 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8084E-004 |
142 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4578E-004 |
143 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5955E-005 |
144 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2983E-005 |
145 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.9727E-005 |
146 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4710E-004 |
147 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0281E-004 |
148 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3994E-004 |
149 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3313E-005 |
150 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2479E-004 |
151 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1757E-005 |
152 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1077E-005 |
153 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3364E-004 |
154 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8510E-005 |
155 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4598E-004 |
156 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8548E-005 |
157 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0419E-004 |
158 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7981E-005 |
159 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1734E-005 |
160 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2731E-005 |
161 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1302E-004 |
162 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.2699E-005 |
163 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9797E-004 |
164 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.6225E-005 |
165 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0756E-004 |
166 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.3108E-005 |
167 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5935E-005 |
168 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1887E-005 |
169 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4246E-004 |
170 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1351E-003 |
171 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4266E-004 |
172 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3792E-003 |
173 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5386E-004 |
174 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5250E-004 |
175 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6979E-005 |
176 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3777E-004 |
177 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6250E-004 |
178 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7489E-004 |
179 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.4014E-004 |
180 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2153E-004 |
181 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6227E-004 |
182 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0462E-004 |
183 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0720E-004 |
184 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4148E-004 |
185 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8257E-004 |
186 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0196E-004 |
187 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0590E-003 |
188 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0355E-004 |
189 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4365E-004 |
190 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0034E-004 |
191 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0708E-004 |
192 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6592E-005 |
193 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9144E-004 |
194 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1638E-005 |
195 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0373E-004 |
196 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0939E-005 |
197 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7668E-004 |
198 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2643E-005 |
199 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6898E-005 |
200 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5662E-005 |
201 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4241E-003 |
202 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1652E-004 |
203 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6157E-003 |
204 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1327E-004 |
205 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3819E-003 |
206 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3213E-004 |
207 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2032E-004 |
208 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0902E-005 |
209 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0406E-003 |
210 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3828E-004 |
211 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1230E-003 |
212 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6864E-004 |
213 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2016E-003 |
214 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1378E-004 |
215 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2112E-004 |
216 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4671E-004 |
217 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4342E-004 |
218 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3490E-005 |
219 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4436E-004 |
220 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1864E-005 |
221 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8636E-004 |
222 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6490E-005 |
223 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7473E-004 |
224 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9066E-005 |
225 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9027E-004 |
226 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0098E-003 |
227 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8087E-004 |
228 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3237E-003 |
229 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4630E-004 |
230 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8356E-003 |
231 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7498E-004 |
232 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.5506E-004 |
233 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4634E-004 |
234 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3228E-005 |
235 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2868E-004 |
236 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0860E-005 |
237 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4723E-004 |
238 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7330E-005 |
239 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7446E-004 |
240 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1536E-005 |
241 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4684E-003 |
242 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1659E-004 |
243 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4478E-003 |
244 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0810E-004 |
245 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1253E-003 |
246 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4528E-004 |
247 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2227E-003 |
248 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1450E-004 |
249 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2475E-003 |
250 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5102E-004 |
251 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1851E-003 |
252 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2176E-004 |
253 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8940E-003 |
254 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3133E-004 |
255 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2269E-003 |
256 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1533E-004 |
257 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1055E-004 |
258 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1859E-003 |
259 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8845E-004 |
260 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1816E-003 |
261 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9958E-004 |
262 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0827E-003 |
263 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7501E-004 |
264 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6479E-003 |
265 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9295E-004 |
266 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0877E-005 |
267 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6914E-004 |
268 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8250E-005 |
269 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6672E-004 |
270 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4320E-005 |
271 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7296E-004 |
272 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1506E-005 |
273 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8210E-004 |
274 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1277E-003 |
275 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5618E-004 |
276 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.6060E-004 |
277 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3406E-004 |
278 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5878E-003 |
279 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7351E-004 |
280 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5793E-003 |
281 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1942E-004 |
282 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0117E-004 |
283 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0280E-004 |
284 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0983E-005 |
285 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2168E-003 |
286 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2320E-004 |
287 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1889E-003 |
288 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1418E-004 |
289 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8518E-004 |
290 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7835E-004 |
291 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6321E-004 |
292 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2725E-004 |
293 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1136E-003 |
294 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6971E-004 |
295 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1930E-003 |
296 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0887E-004 |
297 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2992E-004 |
298 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1907E-004 |
299 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0966E-004 |
300 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3721E-004 |
301 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3318E-004 |
302 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5296E-004 |
303 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7289E-004 |
304 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2588E-004 |
305 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4775E-004 |
306 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0835E-004 |
307 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8019E-004 |
308 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7391E-004 |
309 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6823E-004 |
310 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4383E-004 |
311 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0178E-004 |
312 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4028E-004 |
313 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0672E-005 |
314 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0286E-005 |
315 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8901E-005 |
316 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6497E-005 |
317 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.4876E-005 |
318 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7495E-005 |
319 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4795E-005 |
320 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1676E-005 |
321 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2923E-004 |
322 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7337E-005 |
323 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1101E-004 |
324 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4907E-005 |
325 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4738E-004 |
326 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9167E-005 |
327 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7264E-004 |
328 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8999E-005 |
329 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6452E-005 |
330 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6861E-004 |
331 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.4053E-005 |
332 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3617E-004 |
333 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5318E-005 |
334 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4093E-004 |
335 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5891E-005 |
336 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3195E-004 |
337 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5353E-004 |
338 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1303E-004 |
339 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2453E-004 |
340 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.5087E-005 |
341 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2652E-004 |
342 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0395E-004 |
343 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0257E-004 |
344 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3913E-004 |
345 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4458E-005 |
346 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3672E-005 |
347 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.3380E-005 |
348 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1689E-005 |
349 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0379E-005 |
350 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4293E-005 |
351 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5813E-005 |
352 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5594E-005 |
353 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4432E-004 |
354 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.0134E-005 |
355 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8032E-004 |
356 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1545E-005 |
357 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.9181E-004 |
358 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.6982E-005 |
359 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0101E-004 |
360 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0338E-005 |
361 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5105E-004 |
362 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.2280E-005 |
363 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2345E-004 |
364 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6277E-005 |
365 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3156E-004 |
366 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0910E-005 |
367 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0246E-004 |
368 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6189E-005 |
369 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.1081E-002 |
370 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.1941E-004 |
371 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.0744E-002 |
372 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.5928E-004 |
373 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 9.9500E-003 |
374 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.5404E-004 |
375 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.1238E-003 |
376 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 4.9215E-004 |
377 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.2763E-004 |
378 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.7291E-002 |
379 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.7034E-004 |
380 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.2292E-002 |
381 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.5797E-004 |
382 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.1313E-002 |
383 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.9195E-004 |
384 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.7684E-002 |
385 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.6772E-003 |
386 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.6885E-004 |
387 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.3279E-003 |
388 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.9152E-004 |
389 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.1498E-003 |
390 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.2262E-004 |
391 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.2005E-003 |
392 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.0398E-004 |
393 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.3532E-002 |
394 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.7759E-004 |
395 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.0088E-002 |
396 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.9751E-004 |
397 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 7.3247E-003 |
398 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.2348E-004 |
399 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.1869E-002 |
400 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.0618E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10766.49605 | 12919.79527 | 0.90869 | 1.09043 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 29.24600 | 1.33651E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 12252.47100 | 14702.96520 | 0.35287 | 0.42344 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -16.30000 | 9.24091E-004 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 35198.52743 | 42238.23291 | 2.31596 | 2.77915 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 30.30000 | 1.33670E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 46941.15437 | 56329.38524 | 1.13832 | 1.36598 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -16.30000 | 9.24091E-004 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 30.30000 | 1.33670E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 171655.33368 | 205986.40041 | 4.30163 | 5.16195 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 15961.67 | 1.09043 | 1.09043 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 13972.63 | 0.42344 | 0.42344 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 49985.20 | 2.77915 | 2.77915 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 55352.96 | 1.36598 | 1.36598 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.09043 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.77915 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.16195 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 5.16195 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 205986.39640 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 205986.40041 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.09043 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.09043 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.09043 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.09043 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.09043 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.09043 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.77915 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.77915 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.77915 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.77915 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.77915 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.77915 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.09043 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.77915 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.09043 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.09043 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1207.27545 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.09043 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.09043 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.09043 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.09043 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.09043 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.54521 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.72695 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20104.73000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10052.36500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80009 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80009 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20104.73000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28883.47920 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 28883.47920 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.77915 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.77915 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2973.82010 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.77915 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.77915 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.77915 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.83424 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.77915 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.38957 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.85277 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 64674.72000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 32337.36000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72152 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72152 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 64674.72000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 96109.25424 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 96109.25424 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 19258.3 | 11.65 | 11.39 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 62515.2 | 11.94 | 11.67 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.2346310981 | 0.2022488881 | Pass | Pass | 0.5094296310 | 2.6674861808 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.5862760151 | 0.5286900612 | Pass | Pass | 0.6672445081 | 0.9015251923 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 4.7345961162E-005 | 7.2491564164E-005 | Pass | Pass | 2.7487440708E-002 | 2.0032205380E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8203.35 | 856.28 | 0.00 | 85.44 | 319.98 | 9465.09 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.456 | 0.490 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.456 | 0.490 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.456 | 0.490 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.456 | 0.490 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.456 | 0.490 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.456 | 0.490 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.456 | 0.490 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.312 | 0.326 | 1393.41 | 1368.35 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.471 | 0.504 | 3204.84 | 3094.09 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.659 | 0.782 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.659 | 0.782 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.5016_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.852 | 0.401 | 0.402 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.5016_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.852 | 0.401 | 0.402 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.5016_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.852 | 0.401 | 0.402 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.5016_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.852 | 0.401 | 0.402 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_1.02_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.30 | 0.00 | 1.79 | 1.79 | 5.799 | 0.491 | 0.491 | 283.913 | 0.000 | CurtainWall | 5.547 | 0.455 | 0.435 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 153.47 | 5.459 | 0.524 | 0.525 | |||||||||||||||||
North Total or Average | 6.51 | 2.852 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 146.96 | 5.575 | 0.529 | 0.530 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 9.9957 | 236.88 | 2367.78 | LightsWired | LTG_SCH_OFFICE | 56.95 | 168.00 | 48.38 | 0.0000 | Y | 21.50 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 10.2257 | 1393.41 | 14248.59 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 48.54 | 0.0000 | Y | 129.83 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 6.2431 | 3204.84 | 20008.02 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 41.08 | 0.0000 | Y | 154.30 |
Interior Lighting Total | 7.5746 | 4835.13 | 36624.39 | 305.64 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 14248.59 | 3562.15 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 14248.59 | 3562.15 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 20008.02 | 5002.01 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 20008.02 | 5002.01 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.11 | 2367.78 | 260.46 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.11 | 2367.78 | 260.46 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 125.92 | AstronomicalClock | - | 42.04 | 42.04 | 0.99 | |
EXTERIOR_LIGHTS_B | 6860.50 | AstronomicalClock | - | 83.67 | 71.18 | 91.67 | |
Exterior Lighting Total | 6986.42 | 92.66 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20104.73 | 16085.59 | 4019.14 | 0.80 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 64674.72 | 46664.10 | 18010.62 | 0.72 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 19258.3 | 11.65 | 11.39 | ||||
PSZ-FINE STORAGE COOLING COIL | 62515.2 | 11.94 | 11.67 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 205986.40 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 28883.48 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 96109.25 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 5.16 | 479.60 | 92.91 | 1.00 | 3.15 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.09 | 1207.28 | 1107.16 | 1.00 | 1.38 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.78 | 2973.82 | 1070.05 | 1.00 | 1.27 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10766.50 | 12919.80 | 54.54 | 0.909 | 1.090 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 23.90 | 23.90 | 0.00856 | 29.25 | 0.01337 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 35198.53 | 42238.23 | 30.31 | 2.316 | 2.779 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 26.70 | 26.70 | 0.00906 | 30.30 | 0.01337 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 0.00 | 31.14 | 0.01343 | 30.30 | 0.01337 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 12252.47 | 14702.97 | 62.07 | 0.353 | 0.423 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00730 | -16.30 | 0.00092 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 46941.15 | 56329.39 | 40.43 | 1.138 | 1.366 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.55 | 0.00608 | -16.30 | 0.00092 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 171655.33 | 205986.40 | 64.27 | 4.302 | 5.162 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 9.99 | 0.00519 | -16.30 | 0.00092 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.09 | 1.09 | 0.42 | 0.42 | 1.0904 | 1.0904 | 1.0904 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.78 | 2.78 | 1.37 | 1.37 | 2.7791 | 2.7791 | 2.7791 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 205986.396 | 205986.396 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 205986.40 | 205986.40 | 5.161953 | 9.99 | 7.05 | 0.00519137 | 43.33 | 21.85 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 9.99 | 0.00519137 | 66.6005 | 205986.40 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 20104.730 | 16085.593 | 1.090430 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 10052.36 | 8603.44 | 0.726953 | 25.35 | 17.03 | 0.00901301 | 12.00 | 11.04 | 0.00800000 | 29.49 | 0.01336553 | 21.60 | 14.0703 | 23.90 | 0.00856190 | 45.2041 | 10754.01 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 28883.479 | 28883.479 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 28883.48 | 28883.48 | 1.090427 | 17.55 | 12.03 | 0.00670512 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 9.3802 | 21.10 | 0.00730353 | 45.8065 | 12252.47 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 64674.720 | 46664.104 | 2.779150 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 32337.36 | 26058.96 | 1.852767 | 28.14 | 18.52 | 0.00971488 | 12.00 | 11.04 | 0.00800000 | 30.30 | 0.01336696 | 21.83 | 22.9231 | 26.70 | 0.00905609 | 40.4500 | 35198.53 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 96109.254 | 96109.254 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 96109.25 | 96109.25 | 2.779148 | 10.68 | 7.49 | 0.00529045 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 15.2821 | 15.55 | 0.00607809 | 54.0955 | 46941.15 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 205986.396 | 205986.396 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 5.161953 | 6.05974769 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 205986.40 | 205986.40 | 1.0000 | 6.05974769 | 5.161953 | 9.99 | 7.05 | 0.00519137 | 23122.7 | 43.33 | 21.85 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 205986.40 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 9.99 | 0.00519137 | 9.99 | 0.00519137 | 66.6005 | 205986.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20104.730 | 16085.593 | 1.090430 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5947 | 1004.8586 | 1.1739 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.090427 | 1.28007951 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | Sensible | 10052.36 | 8603.44 | 1.0000 | 0.85338892 | 0.726953 | 25.35 | 17.03 | 0.00901301 | 48434.9 | 12.00 | 11.04 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10052.36 | 29.49 | 0.01336553 | 21.60 | 0.10228463 | 14.0703 | 23.90 | 0.00856190 | 23.90 | 0.00856190 | 45.2041 | 10754.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28883.479 | 28883.479 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.090427 | 1.28007951 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 28883.48 | 28883.48 | 1.0000 | 1.28007951 | 1.090427 | 17.55 | 12.03 | 0.00670512 | 34618.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28883.48 | -16.30 | 0.00092409 | -16.30 | 0.10228463 | 9.3802 | 21.05 | 0.00730353 | 21.10 | 0.00730353 | 45.8065 | 12252.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 64674.720 | 46664.104 | 2.779150 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.8995 | 1004.8586 | 1.1739 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.779148 | 3.26251259 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 32337.36 | 26058.96 | 1.0000 | 2.17500969 | 1.852767 | 28.14 | 18.52 | 0.00971488 | 53078.8 | 12.00 | 11.04 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32337.36 | 30.30 | 0.01336696 | 21.83 | 0.42471127 | 22.9231 | 26.70 | 0.00905609 | 26.70 | 0.00905609 | 40.4500 | 35198.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 96109.254 | 96109.254 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.779148 | 3.26251259 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 96109.25 | 96109.25 | 1.0000 | 3.26251259 | 2.779148 | 10.68 | 7.49 | 0.00529045 | 24071.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 96109.25 | -16.30 | 0.00092409 | -16.30 | 0.42471127 | 15.2821 | 15.55 | 0.00607809 | 15.55 | 0.00607809 | 54.0955 | 46941.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.09 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 2.78 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2637.50 | 2798.00 | 2046.67 |
ZONE2 FINE STORAGE | 3150.17 | 3149.83 | 2737.83 |
ZONE3 BULK STORAGE | 3213.83 | 3344.83 | 2978.33 |
Facility | 3380.50 | 3402.83 | 3023.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 149.67 | 52.83 | 59.17 | 3.17 |
ZONE2 FINE STORAGE | 486.17 | 12.33 | 23.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 589.67 | 62.83 | 68.33 | 3.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.757 | 0.351 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.573 | 0.326 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.200 | 0.000 | 0.145 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.50 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.36 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.28 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2934063.43 | 0.00 | 2934063.43 | 2205922.67 | 5139986.10 | 3225648.14 | 5576.71 | 2186.11 | 997.18 | 109.32 |
ZONE2 FINE STORAGE | 6148423.54 | 0.00 | 6148423.54 | 8966050.58 | 15114474.12 | 13393694.68 | 5702.03 | 2493.72 | 564.24 | 19.78 |
ZONE3 BULK STORAGE | 0.00 | 31426778.57 | 31426778.57 | 51693260.18 | 83120038.74 | 30805497.77 | 7035.74 | 128.17 | 1596.10 | 5048.67 |
Total Facility | 9082486.97 | 31426778.57 | 40509265.54 | 62865233.43 | 0.10E+09 | 47424840.58 | 7925.79 | 2761.08 | 2682.64 | 5050.50 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.2082 | 0.0000 | 0.2082 | 0.0971 | 0.3053 | 0.1023 | 553.37 | 2185.94 | 896.69 |
ZONE2 FINE STORAGE | 0.4630 | 0.0000 | 0.4630 | 0.2664 | 0.7294 | 0.4247 | 597.58 | 2493.72 | 544.69 |
ZONE3 BULK STORAGE | 0.0000 | 1.3923 | 1.3923 | 1.9717 | 3.3641 | 0.9768 | 2725.46 | 65.33 | 845.21 |
Total Facility | 0.6712 | 1.3923 | 2.0635 | 2.3353 | 4.3988 | 1.5038 | 2801.79 | 2698.08 | 1817.05 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 4043434.70 | 0.00 | 4043434.70 | 3225648.14 | 5571.46 | 0.42 | 3188.12 | 109.32 |
PSZ-FINE STORAGE | 8473161.63 | 0.00 | 8473161.63 | 13393694.68 | 5700.08 | 0.17 | 3059.75 | 19.78 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2869 | 0.0000 | 0.2869 | 0.1023 | 549.37 | 0.25 | 3086.38 |
PSZ-FINE STORAGE | 0.6380 | 0.0000 | 0.6380 | 0.4247 | 595.78 | 0.17 | 3040.06 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2745.27 | 462.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2885.16 | 177.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.3051 | 0.5332 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.7394 | 1.1413 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 429 |
Defaulted Fields | 391 |
Fields with Defaults | 1171 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 616.16 | 2970.19 | 12-MAR-12:20 | 49482.24 | 26-DEC-17:00 |
Electricity:Building | 443.35 | 2489.19 | 29-JAN-12:20 | 40750.63 | 27-NOV-15:50 |
Electricity:Zone:ZONE1 OFFICE | 51.22 | 776.36 | 01-JAN-12:10 | 3432.39 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 442.70 | 2489.19 | 29-JAN-12:20 | 40750.63 | 27-NOV-15:50 |
InteriorLights:Electricity | 305.64 | 2000.65 | 29-JAN-12:20 | 30696.62 | 27-NOV-15:50 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 21.50 | 287.82 | 01-JAN-12:10 | 1578.50 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 305.64 | 2000.65 | 29-JAN-12:20 | 30696.62 | 27-NOV-15:50 |
LightsWired:InteriorLights:Electricity | 305.64 | 2000.65 | 29-JAN-12:20 | 30696.62 | 27-NOV-15:50 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 21.50 | 287.82 | 01-JAN-12:10 | 1578.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 305.64 | 2000.65 | 29-JAN-12:20 | 30696.62 | 27-NOV-15:50 |
Electricity:Zone:ZONE2 FINE STORAGE | 129.83 | 712.43 | 29-JAN-12:20 | 12111.30 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 129.83 | 712.43 | 29-JAN-12:20 | 12111.30 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 129.83 | 712.43 | 29-JAN-12:20 | 12111.30 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 262.30 | 1000.40 | 01-JAN-11:30 | 25206.94 | 02-JAN-16:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 154.31 | 1000.40 | 01-JAN-11:30 | 17006.82 | 02-JAN-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 154.31 | 1000.40 | 01-JAN-11:30 | 17006.82 | 02-JAN-16:00 |
InteriorEquipment:Electricity | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.72 | 488.55 | 01-JAN-00:10 | 1853.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.72 | 488.55 | 01-JAN-00:10 | 1853.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 40.72 | 0.00 | 11-JAN-18:40 | 4851.21 | 19-JUL-15:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.65 | 0.00 | 01-JAN-00:10 | 2305.29 | 15-JUL-14:20 |
Ventilation (simple):Fans:Electricity | 0.65 | 0.00 | 01-JAN-00:10 | 2305.29 | 15-JUL-14:20 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.65 | 0.00 | 01-JAN-00:10 | 2305.29 | 15-JUL-14:20 |
ElectricityPurchased:Facility | 616.16 | 2970.19 | 11-JUN-13:40 | 49482.24 | 26-DEC-17:00 |
ElectricityPurchased:Plant | 616.16 | 2970.19 | 11-JUN-13:40 | 49482.24 | 26-DEC-17:00 |
Cogeneration:ElectricityPurchased | 616.16 | 2970.19 | 11-JUN-13:40 | 49482.24 | 26-DEC-17:00 |
General:Cogeneration:ElectricityPurchased | 616.16 | 2970.19 | 11-JUN-13:40 | 49482.24 | 26-DEC-17:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 616.16 | 2970.19 | 11-JUN-13:40 | 49482.24 | 26-DEC-17:00 |
ElectricityNet:Plant | 616.16 | 2970.19 | 11-JUN-13:40 | 49482.24 | 26-DEC-17:00 |
Cogeneration:ElectricityNet | 616.16 | 2970.19 | 11-JUN-13:40 | 49482.24 | 26-DEC-17:00 |
General:Cogeneration:ElectricityNet | 616.16 | 2970.19 | 11-JUN-13:40 | 49482.24 | 26-DEC-17:00 |
Electricity:HVAC | 53.94 | 0.00 | 11-JAN-18:40 | 14798.73 | 19-JUL-15:10 |
General:Fans:Electricity | 40.07 | 0.00 | 11-JAN-18:40 | 3959.97 | 07-FEB-08:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 13.86 | 0.00 | 01-JAN-00:10 | 12252.82 | 19-JUL-15:10 |
General:Cooling:Electricity | 13.86 | 0.00 | 01-JAN-00:10 | 12252.82 | 19-JUL-15:10 |
ExteriorLights:Electricity | 92.66 | 0.00 | 01-JAN-08:00 | 6986.42 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 92.66 | 0.00 | 01-JAN-08:00 | 6986.42 | 01-JAN-06:10 |
Electricity:Plant | 26.22 | 481.00 | 09-JAN-06:50 | 2702.53 | 17-FEB-13:00 |
WaterSystems:Electricity | 26.22 | 481.00 | 09-JAN-06:50 | 2702.53 | 17-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 26.22 | 481.00 | 09-JAN-06:50 | 2702.53 | 17-FEB-13:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1059.46 | 0.00 | 11-JAN-18:40 | 341343.67 | 12-JAN-09:00 |
NaturalGas:HVAC | 1059.46 | 0.00 | 11-JAN-18:40 | 341343.67 | 12-JAN-09:00 |
Heating:NaturalGas | 1059.46 | 0.00 | 11-JAN-18:40 | 341343.67 | 12-JAN-09:00 |
General:Heating:NaturalGas | 1059.46 | 0.00 | 11-JAN-18:40 | 341343.67 | 12-JAN-09:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 16-AUG-11:20 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 16-AUG-11:20 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 16-AUG-11:20 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 16-AUG-11:20 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 16-AUG-11:20 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 16-AUG-11:20 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 16-AUG-11:20 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 16-AUG-11:20 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1734.42 | 0.00 | 11-JAN-18:40 | 536069.80 | 13-FEB-06:10 |
EnergyTransfer:Building | 861.23 | 0.00 | 11-JAN-18:40 | 268910.02 | 13-FEB-06:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 66.54 | 0.00 | 01-JAN-00:40 | 24195.25 | 13-FEB-06:10 |
Heating:EnergyTransfer | 793.82 | 0.00 | 11-JAN-18:40 | 268910.02 | 13-FEB-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 43.75 | 0.00 | 01-JAN-00:40 | 24195.25 | 13-FEB-06:10 |
General:Heating:EnergyTransfer | 793.82 | 0.00 | 11-JAN-18:40 | 268910.02 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 43.75 | 0.00 | 01-JAN-00:40 | 24195.25 | 13-FEB-06:10 |
Cooling:EnergyTransfer | 67.40 | 0.00 | 01-JAN-00:10 | 32163.41 | 19-JUL-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 22.79 | 0.00 | 01-JAN-00:10 | 10579.98 | 05-JUN-18:00 |
General:Cooling:EnergyTransfer | 67.40 | 0.00 | 01-JAN-00:10 | 32163.41 | 19-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 22.79 | 0.00 | 01-JAN-00:10 | 10579.98 | 05-JUN-18:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 198.10 | 0.00 | 01-JAN-00:40 | 59770.10 | 13-FEB-06:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 153.49 | 0.00 | 01-JAN-00:40 | 59770.10 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 153.49 | 0.00 | 01-JAN-00:40 | 59770.10 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 44.61 | 0.00 | 01-JAN-00:10 | 23963.91 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 44.61 | 0.00 | 01-JAN-00:10 | 23963.91 | 21-JUL-13:30 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 596.59 | 0.00 | 06-JAN-10:50 | 206495.23 | 06-FEB-10:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 596.59 | 0.00 | 06-JAN-10:50 | 206495.23 | 06-FEB-10:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 596.59 | 0.00 | 06-JAN-10:50 | 206495.23 | 06-FEB-10:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 873.19 | 0.00 | 11-JAN-18:40 | 267159.78 | 13-FEB-06:10 |
HeatingCoils:EnergyTransfer | 813.27 | 0.00 | 11-JAN-18:40 | 267159.78 | 13-FEB-06:10 |
CoolingCoils:EnergyTransfer | 59.93 | 0.00 | 01-JAN-00:10 | 51133.96 | 17-JUL-17:50 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 43.745 | -22.792 | 0.000 | 0.000 | 10.045 | 21.505 | 29.720 | 10.091 | 0.000 | 0.422 | 0.000 | 0.000 | -10.408 | 0.000 | -33.101 | -49.226 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 153.486 | -44.609 | 0.000 | 0.000 | 25.757 | 129.827 | 0.000 | 35.797 | 0.000 | 0.454 | 0.002 | 0.000 | -26.035 | 0.000 | -118.299 | -156.378 |
ZONE3 BULK STORAGE | 596.588 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 65.039 | 154.305 | 107.344 | 379.601 | 0.000 | 7.947 | 0.000 | 0.000 | -362.532 | 0.000 | -684.287 | -264.005 |
Total Facility | 596.588 | 0.000 | 197.231 | -67.402 | 0.000 | 0.000 | 100.841 | 305.637 | 137.063 | 425.489 | 0.000 | 8.823 | 0.002 | 0.000 | -398.975 | 0.000 | -835.687 | -469.610 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 05-JUN-19:13 | 0.00 | 0.00 | 0.00 | -22674.48 | 0.00 | 0.00 | 0.00 | 328.41 | 488.55 | 711.84 | 0.00 | 0.00 | 21553.93 | 0.00 | -0.00 | 0.00 | -408.24 | 0.00 |
ZONE2 FINE STORAGE | 06-JUL-17:18 | 0.00 | 0.00 | 0.00 | -53731.52 | 0.00 | 0.00 | 0.00 | 1306.12 | 0.00 | 2532.02 | 0.00 | 0.00 | 52005.44 | 0.00 | -0.00 | 0.00 | -2112.06 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-AUG-18:31 | 0.00 | 0.00 | 0.00 | -68849.76 | 0.00 | 0.00 | 0.00 | 3573.80 | 2538.58 | 833.53 | 0.00 | 0.00 | 87780.99 | 0.00 | -11793.40 | 0.00 | -14083.75 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 07-FEB-06:31 | 0.00 | 0.00 | 31783.45 | 0.00 | 0.00 | 0.00 | 145.82 | 471.50 | 556.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1328.16 | 0.00 | -3932.07 | -27696.69 |
ZONE2 FINE STORAGE | 10-JAN-04:02 | 0.00 | 0.00 | 99268.70 | 0.00 | 0.00 | 0.00 | 0.00 | 1424.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2900.12 | 0.00 | -7226.38 | -90567.05 |
ZONE3 BULK STORAGE | 06-FEB-10:00 | 206496.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8317.41 | 8503.41 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21469.68 | 0.00 | -177718.06 | -32329.66 |
Total Facility | 13-FEB-06:01 | 184950.89 | 0.00 | 126078.27 | 0.00 | 0.00 | 0.00 | 1452.41 | 3897.16 | 2606.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -38239.06 | 0.00 | -168847.07 | -111898.80 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0904 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0904 | 0.0938 | 1.0000 | Not calculated | 0.1023 | 0.0938 | ||
PSZ-FINE STORAGE | 2.7791 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.7791 | 0.1528 | 1.0000 | Not calculated | 0.4247 | 0.1528 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0904 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0904 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0938 | ||
PSZ-FINE STORAGE | 2.7791 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.7791 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1528 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0904 | 1.0904 | 1.0904 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.7791 | 2.7791 | 2.7791 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0904 | 1.0904 | 1.0904 | 1.0904 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.7791 | 2.7791 | 2.7791 | 2.7791 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0904 | 1.0904 | 1.0904 | No | 0.1023 | 0.2416 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.7791 | 2.7791 | 2.7791 | No | 0.4247 | 0.3109 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0904 | 1.0904 | 1.0904 | 1.0904 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.7791 | 2.7791 | 2.7791 | 2.7791 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 68.33 |
Number of hours cooling loads not met | 3.17 |
Number of hours not met | 71.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1059.46 | 341343.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 13.86 | 12252.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 305.64 | 30696.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 92.66 | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 137.06 | 10054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.65 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 40.07 | 3959.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.22 | 2702.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 137.06 | 616.16 |
Natural Gas | 0.00 | 1059.46 |
Additional | 0.00 | 0.00 |
Total | 137.06 | 1675.62 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 63.21 |
Space Heating | 0.00 |
Space Cooling | 2.87 |
Fans (All) | 8.42 |
Service Water Heating | 5.42 |
Receptacle Equipment | 28.35 |
Miscellaneous (All) | 127.43 |
Subtotal | 127.43 |
Natural Gas [MJ/m2] | |
Space Heating | 219.12 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 219.12 |
Subtotal | 219.12 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 18.24 |
Space Heating | 63.23 |
Space Cooling | 0.83 |
Fans (All) | 2.43 |
Service Water Heating | 1.56 |
Receptacle Equipment | 8.18 |
Miscellaneous | 5.53 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2970. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4378. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8619.17 | 140.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8029.33 | 730.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7639.83 | 1100.50 | 19.67 | 0.00 | 0.00 |
Min | 7639.83 | 140.83 | 0.00 | 0.00 | 0.00 |
Max | 8619.17 | 1100.50 | 19.67 | 0.00 | 0.00 |
Average | 8096.11 | 657.33 | 6.56 | 0.00 | 0.00 |
Sum | 24288.33 | 1972.00 | 19.67 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 70405.00 | 12314.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 158455.33 | 31795.33 | 942.33 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 158455.33 | 31795.33 | 942.33 | 0.00 | 0.00 |
Average | 87295.78 | 14703.11 | 314.11 | 0.00 | 0.00 |
Sum | 261887.33 | 44109.33 | 942.33 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8351.00 | 409.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7435.33 | 1324.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7243.33 | 1516.67 | 0.00 | 0.00 | 0.00 |
Min | 7243.33 | 409.00 | 0.00 | 0.00 | 0.00 |
Max | 8351.00 | 1516.67 | 0.00 | 0.00 | 0.00 |
Average | 7676.56 | 1083.44 | 0.00 | 0.00 | 0.00 |
Sum | 23029.67 | 3250.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 31648.17 | 1378.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 67260.50 | 15458.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 151842.83 | 39350.17 | 0.00 | 0.00 | 0.00 |
Min | 31648.17 | 1378.83 | 0.00 | 0.00 | 0.00 |
Max | 151842.83 | 39350.17 | 0.00 | 0.00 | 0.00 |
Average | 83583.83 | 18729.17 | 0.00 | 0.00 | 0.00 |
Sum | 250751.50 | 56187.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:48
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 | -1.6 | 0.496994E+09 | 603.25 | 23-JAN-08:09 | -6.2 | -8.2 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -3.3 | -4.7 | 0.457205E+09 | 603.25 | 01-FEB-08:09 | 5.10 | 5.05 |
March | 21893943.87 | 1323.57 | 15-MAR-15:10 | 25.50 | 16.19 | 0.547969E+09 | 782.55 | 15-MAR-12:20 | 25.50 | 16.19 |
April | 18221034.11 | 767.77 | 22-APR-15:00 | 15.60 | 7.04 | 0.515941E+09 | 768.96 | 08-APR-15:50 | 15.60 | 7.04 |
May | 0.825584E+09 | 19503.06 | 27-MAY-18:35 | 18.50 | 9.91 | 0.616773E+09 | 769.00 | 10-MAY-15:00 | 18.50 | 9.91 |
June | 0.452954E+10 | 22676.36 | 05-JUN-19:13 | 15.37 | 9.80 | 0.657649E+09 | 769.03 | 21-JUN-14:50 | 21.60 | 19.08 |
July | 0.699984E+10 | 21108.20 | 06-JUL-20:21 | 18.90 | 12.76 | 0.634650E+09 | 769.03 | 22-JUL-15:00 | 21.70 | 20.14 |
August | 0.680826E+10 | 20487.86 | 20-AUG-23:02 | 18.12 | 14.61 | 0.685308E+09 | 769.03 | 07-AUG-08:39 | 18.12 | 14.61 |
September | 0.331738E+10 | 20790.58 | 01-SEP-18:33 | 15.97 | 11.63 | 0.630029E+09 | 769.02 | 08-SEP-13:50 | 22.70 | 18.06 |
October | 0.264527E+09 | 2430.94 | 05-OCT-15:00 | 18.90 | 12.68 | 0.547283E+09 | 768.97 | 11-OCT-15:00 | 21.70 | 14.52 |
November | 7943305.29 | 590.45 | 18-NOV-14:20 | 5.00 | 2.00 | 0.481668E+09 | 719.34 | 04-NOV-15:09 | 5.00 | 2.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.95 | 3.07 | 0.497007E+09 | 603.25 | 28-DEC-08:09 | -12.1 | -12.5 |
Annual Sum or Average | 0.227932E+11 | 0.676848E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.3 | -4.7 | 0.457205E+09 | 603.25 | -12.1 | -12.5 | ||
Maximum of Months | 0.699984E+10 | 22676.36 | 25.50 | 16.19 | 0.685308E+09 | 782.55 | 25.50 | 20.14 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174379E+09 | 3303.81 | 17-JAN-15:00 | 6.70 | 5.64 | 0.649519E+09 | 858.00 | 11-JAN-16:10 | 6.70 | 5.64 |
February | 0.301707E+09 | 5668.65 | 28-FEB-15:30 | 0.30 | -2.5 | 0.598146E+09 | 892.34 | 22-FEB-16:10 | 0.30 | -2.5 |
March | 0.184137E+10 | 6941.57 | 07-MAR-15:00 | -2.2 | -5.2 | 0.795755E+09 | 1766.63 | 15-MAR-14:30 | 25.85 | 16.15 |
April | 0.238564E+10 | 5702.56 | 17-APR-09:50 | 1.93 | -0.4 | 0.845773E+09 | 1573.91 | 22-APR-15:09 | 15.68 | 7.07 |
May | 0.205206E+10 | 4704.61 | 18-MAY-08:20 | 9.40 | 6.18 | 0.133305E+10 | 2246.78 | 27-MAY-14:30 | 21.70 | 12.26 |
June | 0.613573E+10 | 44459.24 | 30-JUN-18:21 | 22.75 | 12.12 | 0.180631E+10 | 2246.96 | 27-JUN-14:20 | 22.75 | 12.12 |
July | 0.128801E+11 | 53731.57 | 06-JUL-17:18 | 22.57 | 13.34 | 0.184417E+10 | 2246.95 | 26-JUL-15:30 | 26.65 | 21.66 |
August | 0.108141E+11 | 53654.58 | 06-AUG-14:33 | 27.77 | 18.96 | 0.196837E+10 | 2246.95 | 11-AUG-12:00 | 23.90 | 16.62 |
September | 0.308504E+10 | 13226.49 | 16-SEP-13:40 | 27.20 | 19.70 | 0.164075E+10 | 2246.91 | 21-SEP-15:50 | 26.10 | 17.09 |
October | 0.248680E+10 | 6107.40 | 17-OCT-08:30 | 1.10 | -0.8 | 0.974305E+09 | 1783.48 | 11-OCT-15:09 | 1.10 | -0.8 |
November | 0.202979E+10 | 5640.60 | 24-NOV-11:20 | 2.03 | -0.2 | 0.698170E+09 | 1278.76 | 04-NOV-15:09 | 2.03 | -0.2 |
December | 0.424164E+09 | 5874.04 | 19-DEC-11:15 | 0.60 | 0.13 | 0.653996E+09 | 993.51 | 01-DEC-13:20 | 0.60 | 0.13 |
Annual Sum or Average | 0.446109E+11 | 0.138083E+11 | ||||||||
Minimum of Months | 0.174379E+09 | 3303.81 | -2.2 | -5.2 | 0.598146E+09 | 858.00 | 0.30 | -2.5 | ||
Maximum of Months | 0.128801E+11 | 53731.57 | 27.77 | 19.70 | 0.196837E+10 | 2246.96 | 26.65 | 21.66 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 | -1.6 | 0.648514E+09 | 999.86 | 11-JAN-16:40 | 11.30 | 9.94 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -3.3 | -4.7 | 0.595813E+09 | 1036.72 | 22-FEB-16:00 | 11.70 | 5.56 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -4.9 | -6.9 | 0.923675E+09 | 2692.07 | 15-MAR-14:20 | 25.93 | 16.12 |
April | 0.00 | 0.00 | 01-APR-00:05 | 4.10 | 3.72 | 0.115988E+10 | 2403.41 | 08-APR-14:20 | 20.20 | 13.55 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.240432E+10 | 4280.31 | 27-MAY-15:20 | 21.70 | 12.12 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.391186E+10 | 6633.84 | 27-JUN-13:09 | 30.03 | 23.62 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.484750E+10 | 7313.37 | 21-JUL-14:20 | 31.33 | 22.12 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 | 16.93 | 0.501479E+10 | 6830.90 | 10-AUG-14:30 | 30.30 | 20.01 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.336842E+10 | 5514.95 | 16-SEP-14:09 | 27.12 | 19.78 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.160178E+10 | 3256.75 | 05-OCT-15:09 | 18.90 | 12.72 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.827522E+09 | 1797.55 | 04-NOV-15:20 | 18.30 | 13.65 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.95 | 3.07 | 0.657797E+09 | 1276.88 | 01-DEC-11:39 | 14.27 | 12.08 |
Annual Sum or Average | 0.00 | 0.259619E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.595813E+09 | 999.86 | 11.30 | 5.56 | ||
Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.501479E+10 | 7313.37 | 31.33 | 23.62 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.999650E+10 | 29694.87 | 24-JAN-06:11 | -12.0 |
February | 0.976367E+10 | 31783.34 | 07-FEB-06:31 | -16.5 |
March | 0.627157E+10 | 29529.95 | 01-MAR-06:12 | -7.9 |
April | 0.307455E+10 | 29346.73 | 17-APR-05:12 | -4.1 |
May | 0.614791E+09 | 29110.73 | 08-MAY-05:01 | 3.40 |
June | 56049610.71 | 2030.28 | 14-JUN-06:20 | 8.13 |
July | 15326009.46 | 1739.85 | 31-JUL-06:05 | 17.30 |
August | 30347182.06 | 1410.77 | 29-AUG-06:10 | 13.98 |
September | 95121698.25 | 14094.50 | 30-SEP-05:03 | 7.20 |
October | 0.133464E+10 | 29170.36 | 30-OCT-05:01 | -0.1 |
November | 0.360739E+10 | 29328.72 | 24-NOV-06:12 | -3.7 |
December | 0.888535E+10 | 29789.25 | 26-DEC-06:31 | -12.2 |
Annual Sum or Average | 0.437453E+11 | |||
Minimum of Months | 15326009.46 | 1410.77 | -16.5 | |
Maximum of Months | 0.999650E+10 | 31783.34 | 17.30 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.395893E+11 | 99268.50 | 10-JAN-04:02 | -12.4 |
February | 0.383976E+11 | 99200.14 | 09-FEB-02:62 | -14.3 |
March | 0.191716E+11 | 99211.45 | 06-MAR-05:22 | -11.1 |
April | 0.621482E+10 | 97599.83 | 16-APR-07:02 | -3.7 |
May | 0.139590E+09 | 64547.06 | 01-MAY-05:06 | 1.70 |
June | 73913114.13 | 1141.14 | 03-JUN-07:00 | 11.70 |
July | 42966580.30 | 1067.05 | 08-JUL-07:00 | 19.40 |
August | 66689286.01 | 1139.43 | 24-AUG-07:00 | 15.00 |
September | 76835358.00 | 1229.47 | 28-SEP-07:00 | 12.20 |
October | 0.179485E+10 | 61906.06 | 30-OCT-04:13 | -0.4 |
November | 0.109425E+11 | 96436.58 | 25-NOV-06:01 | -1.7 |
December | 0.369761E+11 | 99192.58 | 10-DEC-04:42 | -12.8 |
Annual Sum or Average | 0.153487E+12 | |||
Minimum of Months | 42966580.30 | 1067.05 | -14.3 | |
Maximum of Months | 0.395893E+11 | 99268.50 | 19.40 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169851E+12 | 198410.60 | 12-JAN-09:00 | -11.1 |
February | 0.173712E+12 | 206495.23 | 06-FEB-10:00 | -15.0 |
March | 0.646698E+11 | 111698.14 | 05-MAR-01:00 | -7.2 |
April | 0.944461E+10 | 73965.01 | 16-APR-06:52 | -3.9 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 63902773.53 | 12791.81 | 30-OCT-04:53 | 0.00 |
November | 0.195398E+11 | 48560.96 | 25-NOV-05:53 | -1.7 |
December | 0.159309E+12 | 167551.76 | 09-DEC-17:00 | -7.2 |
Annual Sum or Average | 0.596590E+12 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.173712E+12 | 206495.23 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187341E+10 | 1578.50 | 02-JAN-08:09 | 0.248944E+10 | 1853.89 | 02-JAN-08:09 |
February | 0.166079E+10 | 1578.50 | 01-FEB-08:09 | 0.226834E+10 | 1853.89 | 01-FEB-08:09 |
March | 0.186774E+10 | 1520.62 | 13-MAR-07:10 | 0.258391E+10 | 1853.89 | 01-MAR-08:09 |
April | 0.174376E+10 | 1520.62 | 12-APR-07:10 | 0.244723E+10 | 1853.89 | 01-APR-07:10 |
May | 0.178698E+10 | 1404.87 | 10-MAY-07:10 | 0.253668E+10 | 1853.89 | 01-MAY-07:10 |
June | 0.174378E+10 | 1404.87 | 14-JUN-08:50 | 0.249447E+10 | 1853.89 | 01-JUN-07:10 |
July | 0.174056E+10 | 1404.87 | 11-JUL-07:10 | 0.248944E+10 | 1853.89 | 01-JUL-07:10 |
August | 0.182313E+10 | 1404.87 | 17-AUG-07:10 | 0.258391E+10 | 1853.89 | 01-AUG-07:10 |
September | 0.175346E+10 | 1520.62 | 26-SEP-07:10 | 0.244723E+10 | 1853.89 | 01-SEP-07:10 |
October | 0.182018E+10 | 1578.50 | 07-OCT-07:10 | 0.248944E+10 | 1853.89 | 02-OCT-07:10 |
November | 0.180491E+10 | 1578.50 | 01-NOV-07:10 | 0.239999E+10 | 1853.89 | 01-NOV-07:10 |
December | 0.188623E+10 | 1578.50 | 01-DEC-16:19 | 0.248944E+10 | 1853.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.215049E+11 | 0.297195E+11 | ||||
Minimum of Months | 0.166079E+10 | 1404.87 | 0.226834E+10 | 1853.89 | ||
Maximum of Months | 0.188623E+10 | 1578.50 | 0.258391E+10 | 1853.89 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.122394E+11 | 12111.30 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.102717E+11 | 12111.30 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.114934E+11 | 12111.30 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.101723E+11 | 12111.30 | 03-APR-08:09 | 0.00 | 0.00 |
May | 0.101867E+11 | 11102.03 | 11-MAY-08:09 | 0.00 | 0.00 |
June | 0.957071E+10 | 11102.03 | 14-JUN-08:09 | 0.00 | 0.00 |
July | 0.955254E+10 | 11102.03 | 03-JUL-08:09 | 0.00 | 0.00 |
August | 0.103101E+11 | 11102.03 | 02-AUG-08:09 | 0.00 | 0.00 |
September | 0.103800E+11 | 12111.30 | 19-SEP-08:09 | 0.00 | 0.00 |
October | 0.113952E+11 | 12111.30 | 10-OCT-08:09 | 0.00 | 0.00 |
November | 0.118878E+11 | 12111.30 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.123673E+11 | 12111.30 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.129827E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.955254E+10 | 11102.03 | 0.00 | 0.00 | |
Maximum of Months | 0.123673E+11 | 12111.30 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.148671E+11 | 17006.82 | 02-JAN-15:00 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.122682E+11 | 15589.58 | 01-FEB-15:00 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.134431E+11 | 15006.02 | 06-MAR-16:00 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.118468E+11 | 12505.01 | 01-APR-07:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.118677E+11 | 12505.01 | 01-MAY-07:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.114376E+11 | 12505.01 | 14-JUN-07:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.113789E+11 | 12505.01 | 11-JUL-07:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.122380E+11 | 12505.01 | 02-AUG-07:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.122502E+11 | 15006.02 | 26-SEP-07:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.134317E+11 | 17006.82 | 31-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.142745E+11 | 17006.82 | 02-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.150015E+11 | 17006.82 | 01-DEC-15:50 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.154305E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.113789E+11 | 12505.01 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.150015E+11 | 17006.82 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.187341E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557599E+10 |
February | 0.127628E+10 | 0.166079E+10 | 0.226834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567782E+10 |
March | 0.149825E+10 | 0.186774E+10 | 0.258391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4693716.38 | 0.379127E+10 |
April | 0.138726E+10 | 0.174376E+10 | 0.244723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259047E+10 |
May | 0.144276E+10 | 0.178698E+10 | 0.253668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3244997.78 | 0.158604E+10 |
June | 0.144276E+10 | 0.174378E+10 | 0.249447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74379542.69 | 0.101718E+10 |
July | 0.138726E+10 | 0.174056E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192566E+09 | 0.456676E+09 |
August | 0.149825E+10 | 0.182313E+10 | 0.258391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136065E+09 | 0.653312E+09 |
September | 0.138726E+10 | 0.175346E+10 | 0.244723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10374286.83 | 0.112645E+10 |
October | 0.138726E+10 | 0.182018E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 471539.46 | 0.210937E+10 |
November | 0.133177E+10 | 0.180491E+10 | 0.239999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 195493.81 | 0.297608E+10 |
December | 0.138726E+10 | 0.188623E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554010E+10 |
Annual Sum or Average | 0.168137E+11 | 0.215049E+11 | 0.297195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421990E+09 | 0.331008E+11 |
Minimum of Months | 0.127628E+10 | 0.166079E+10 | 0.226834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456676E+09 |
Maximum of Months | 0.149825E+10 | 0.188623E+10 | 0.258391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192566E+09 | 0.567782E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.122394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198603E+11 |
February | 0.300332E+10 | 0.102717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214011E+11 |
March | 0.352563E+10 | 0.114934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36143734.33 | 0.122591E+11 |
April | 0.326447E+10 | 0.101723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826632E+10 |
May | 0.339505E+10 | 0.101867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8529424.10 | 0.524529E+10 |
June | 0.339505E+10 | 0.957071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53686165.50 | 0.475195E+10 |
July | 0.326447E+10 | 0.955254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173470E+09 | 0.287108E+10 |
August | 0.352563E+10 | 0.103101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138789E+09 | 0.340303E+10 |
September | 0.326447E+10 | 0.103800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1002238.09 | 0.449459E+10 |
October | 0.326447E+10 | 0.113952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15461326.02 | 0.608620E+10 |
November | 0.313390E+10 | 0.118878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26963975.68 | 0.903163E+10 |
December | 0.326447E+10 | 0.123673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206284E+11 |
Annual Sum or Average | 0.395654E+11 | 0.129827E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454046E+09 | 0.118299E+12 |
Minimum of Months | 0.300332E+10 | 0.955254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287108E+10 |
Maximum of Months | 0.352563E+10 | 0.123673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173470E+09 | 0.214011E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.148671E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5208853.74 | 0.798410E+11 |
February | 0.690763E+10 | 0.122682E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66150588.64 | 0.882411E+11 |
March | 0.810895E+10 | 0.134431E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149680E+10 | 0.454248E+11 |
April | 0.750829E+10 | 0.118468E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.636339E+09 | 0.256595E+11 |
May | 0.780862E+10 | 0.118677E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373094E+09 | 0.194185E+11 |
June | 0.780862E+10 | 0.114376E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200820E+09 | 0.232730E+11 |
July | 0.750829E+10 | 0.113789E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4183313.17 | 0.207079E+11 |
August | 0.810895E+10 | 0.122380E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4221261.31 | 0.222945E+11 |
September | 0.750829E+10 | 0.122502E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206184E+11 |
October | 0.750829E+10 | 0.134317E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.816891E+09 | 0.225233E+11 |
November | 0.720796E+10 | 0.142745E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183897E+10 | 0.263304E+11 |
December | 0.750829E+10 | 0.150015E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115560E+09 | 0.809075E+11 |
Annual Sum or Average | 0.910005E+11 | 0.154305E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555824E+10 | 0.475240E+12 |
Minimum of Months | 0.690763E+10 | 0.113789E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194185E+11 |
Maximum of Months | 0.810895E+10 | 0.150015E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183897E+10 | 0.882411E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1578.50 | 02-JAN-08:09 | 1853.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 13412.76 | 12-JAN-08:00 |
February | 1680.92 | 01-FEB-08:09 | 1578.50 | 01-FEB-08:09 | 1853.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 14410.59 | 06-FEB-17:10 |
March | 1680.92 | 01-MAR-08:09 | 1520.62 | 13-MAR-07:10 | 1853.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 271.84 | 15-MAR-16:10 | 9812.27 | 07-MAR-07:10 |
April | 1680.92 | 01-APR-07:10 | 1520.62 | 12-APR-07:10 | 1853.89 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 7674.09 | 04-APR-17:00 |
May | 1680.92 | 01-MAY-07:10 | 1404.87 | 10-MAY-07:10 | 1853.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.37 | 14-MAY-15:00 | 4525.37 | 08-MAY-07:00 |
June | 1680.92 | 01-JUN-07:10 | 1404.87 | 14-JUN-08:50 | 1853.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1509.28 | 27-JUN-12:00 | 4355.34 | 13-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 1404.87 | 11-JUL-07:10 | 1853.89 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1736.97 | 20-JUL-16:10 | 2985.32 | 06-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 1404.87 | 17-AUG-07:10 | 1853.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1704.47 | 18-AUG-17:00 | 3262.52 | 03-AUG-06:10 |
September | 1680.92 | 01-SEP-07:10 | 1520.62 | 26-SEP-07:10 | 1853.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 496.53 | 15-SEP-12:00 | 3964.79 | 05-SEP-06:10 |
October | 1680.92 | 02-OCT-07:10 | 1578.50 | 07-OCT-07:10 | 1853.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.08 | 22-OCT-12:00 | 6290.97 | 17-OCT-07:00 |
November | 1680.92 | 01-NOV-07:10 | 1578.50 | 01-NOV-07:10 | 1853.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.98 | 27-NOV-06:00 | 6794.00 | 17-NOV-18:00 |
December | 1680.92 | 01-DEC-08:09 | 1578.50 | 01-DEC-16:19 | 1853.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 12711.67 | 26-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1404.87 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2985.32 | |||||
Maximum of Months | 1680.92 | 1578.50 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 1736.97 | 14410.59 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 12111.30 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 34740.20 | 12-JAN-09:00 |
February | 3955.50 | 01-FEB-08:09 | 12111.30 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 31484.58 | 13-FEB-07:10 |
March | 3955.50 | 01-MAR-08:09 | 12111.30 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1295.21 | 14-MAR-15:10 | 16450.53 | 03-MAR-18:00 |
April | 3955.50 | 01-APR-07:10 | 12111.30 | 03-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 15436.20 | 04-APR-17:00 |
May | 3955.50 | 01-MAY-07:10 | 11102.03 | 11-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1112.03 | 14-MAY-15:00 | 9086.94 | 11-MAY-15:05 |
June | 3955.50 | 01-JUN-07:10 | 11102.03 | 14-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1944.02 | 12-JUN-15:10 | 10611.97 | 13-JUN-16:00 |
July | 3955.50 | 01-JUL-07:10 | 11102.03 | 03-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3947.04 | 15-JUL-15:10 | 5894.94 | 06-JUL-02:00 |
August | 3955.50 | 01-AUG-07:10 | 11102.03 | 02-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2478.45 | 13-AUG-13:07 | 6218.90 | 30-AUG-17:00 |
September | 3955.50 | 01-SEP-07:10 | 12111.30 | 19-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.01 | 16-SEP-13:00 | 7782.62 | 29-SEP-16:00 |
October | 3955.50 | 02-OCT-07:10 | 12111.30 | 10-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 862.60 | 22-OCT-12:00 | 9225.48 | 23-OCT-15:05 |
November | 3955.50 | 01-NOV-07:10 | 12111.30 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1450.43 | 27-NOV-06:01 | 15680.48 | 17-NOV-09:00 |
December | 3955.50 | 01-DEC-08:09 | 12111.30 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 31103.52 | 09-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 11102.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5894.94 | ||||
Maximum of Months | 3955.50 | 12111.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3947.04 | 34740.20 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 17006.82 | 02-JAN-15:00 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2042.16 | 11-JAN-16:00 | 135863.74 | 12-JAN-09:00 |
February | 9097.65 | 01-FEB-08:09 | 15589.58 | 01-FEB-15:00 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7102.24 | 22-FEB-18:20 | 133639.36 | 07-FEB-11:00 |
March | 9097.65 | 01-MAR-08:09 | 15006.02 | 06-MAR-16:00 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25154.99 | 14-MAR-14:00 | 62485.74 | 01-MAR-15:00 |
April | 9097.65 | 01-APR-07:10 | 12505.01 | 01-APR-07:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12893.16 | 07-APR-14:00 | 45870.94 | 16-APR-06:54 |
May | 9097.65 | 01-MAY-07:10 | 12505.01 | 01-MAY-07:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12705.04 | 14-MAY-15:00 | 32345.93 | 11-MAY-15:00 |
June | 9097.65 | 01-JUN-07:10 | 12505.01 | 14-JUN-07:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6414.26 | 12-JUN-14:00 | 44528.43 | 13-JUN-16:00 |
July | 9097.65 | 01-JUL-07:10 | 12505.01 | 11-JUL-07:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2910.49 | 15-JUL-13:55 | 28285.53 | 06-JUL-02:00 |
August | 9097.65 | 01-AUG-07:10 | 12505.01 | 02-AUG-07:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2064.93 | 13-AUG-12:53 | 27023.98 | 30-AUG-18:00 |
September | 9097.65 | 01-SEP-07:10 | 15006.02 | 26-SEP-07:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 29946.40 | 29-SEP-16:00 |
October | 9097.65 | 02-OCT-07:10 | 17006.82 | 31-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12534.58 | 22-OCT-12:00 | 33375.41 | 23-OCT-15:00 |
November | 9097.65 | 01-NOV-07:10 | 17006.82 | 02-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17737.50 | 27-NOV-06:43 | 38932.95 | 17-NOV-09:00 |
December | 9097.65 | 01-DEC-08:09 | 17006.82 | 01-DEC-15:50 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11595.58 | 01-DEC-11:00 | 119419.54 | 09-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 12505.01 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27023.98 | |||||
Maximum of Months | 9097.65 | 17006.82 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 25154.99 | 135863.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 1475.98 | 1954.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 887.84 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 1844.97 | 2442.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1132.71 |
March | 1323.57 | 15-MAR-15:10 | 1680.92 | 1231.23 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 141.00 | 0.00 |
April | 767.77 | 22-APR-15:00 | 1680.92 | 1231.23 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.94 |
May | 19503.06 | 27-MAY-18:35 | 0.00 | 629.75 | 977.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.17 |
June | 22676.36 | 05-JUN-19:13 | 0.00 | 985.22 | 1465.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.24 |
July | 21108.20 | 06-JUL-20:21 | 0.00 | 3689.95 | 4885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.94 |
August | 20487.86 | 20-AUG-23:02 | 0.00 | 2213.97 | 2931.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.56 |
September | 20790.58 | 01-SEP-18:33 | 0.00 | 1106.98 | 1465.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.72 |
October | 2430.94 | 05-OCT-15:00 | 1680.92 | 1231.23 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.70 |
November | 590.45 | 18-NOV-14:20 | 1680.92 | 1231.23 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 511.23 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1106.98 | 1465.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 789.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 629.75 | 977.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22676.36 | 1680.92 | 3689.95 | 4885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 141.00 | 1132.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3303.81 | 17-JAN-15:00 | 3955.50 | 12111.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1478.79 |
February | 5668.65 | 28-FEB-15:30 | 3955.50 | 11102.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3508.84 |
March | 6941.57 | 07-MAR-15:00 | 3955.50 | 10092.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2455.00 |
April | 5702.56 | 17-APR-09:50 | 3955.50 | 10092.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2859.63 |
May | 4704.61 | 18-MAY-08:20 | 3955.50 | 9083.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1216.92 |
June | 44459.24 | 30-JUN-18:21 | 0.00 | 12823.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1642.64 |
July | 53731.57 | 06-JUL-17:18 | 0.00 | 11755.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2112.06 |
August | 53654.58 | 06-AUG-14:33 | 0.00 | 2137.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 410.45 | 0.00 |
September | 13226.49 | 16-SEP-13:40 | 3955.50 | 8074.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.93 | 0.00 |
October | 6107.40 | 17-OCT-08:30 | 3955.50 | 12111.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1277.72 |
November | 5640.60 | 24-NOV-11:20 | 3955.50 | 10092.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.98 |
December | 5874.04 | 19-DEC-11:15 | 7911.00 | 18166.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2805.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3303.81 | 0.00 | 2137.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 53731.57 | 7911.00 | 18166.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 410.45 | 3508.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 8003.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16854.84 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 10004.01 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22636.07 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 8003.21 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19949.83 |
April | 0.00 | 01-APR-00:05 | 0.00 | 4001.60 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5412.84 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3339.61 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3661.34 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11256.44 |
August | 0.00 | 01-AUG-00:05 | 0.00 | 4001.60 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8010.76 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10073.43 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2000.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6464.56 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8990.73 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 6002.41 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10396.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 2000.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3339.61 | |
Maximum of Months | 0.00 | 0.00 | 10004.01 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22636.07 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.576781E+11 | 49409.30 | 09-JAN-16:00 | 0.292853E+12 | 341343.67 | 12-JAN-08:00 |
February | 0.496688E+11 | 43964.90 | 01-FEB-15:00 | 0.294538E+12 | 341284.85 | 07-FEB-08:09 |
March | 0.534295E+11 | 42811.59 | 06-MAR-15:00 | 0.121396E+12 | 195810.94 | 06-MAR-06:10 |
April | 0.468116E+11 | 39420.68 | 05-APR-07:10 | 0.255999E+11 | 139746.53 | 16-APR-03:49 |
May | 0.463995E+11 | 38693.73 | 11-MAY-07:19 | 0.693290E+09 | 25729.91 | 01-MAY-05:10 |
June | 0.468061E+11 | 42827.72 | 27-JUN-12:00 | 1199233.00 | 792.71 | 14-JUN-06:19 |
July | 0.511525E+11 | 46322.40 | 15-JUL-13:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.528961E+11 | 44994.38 | 10-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.483268E+11 | 43437.30 | 21-SEP-14:00 | 14471755.84 | 4883.31 | 30-SEP-05:10 |
October | 0.513357E+11 | 43512.68 | 31-OCT-08:09 | 0.453380E+10 | 60279.44 | 30-OCT-05:10 |
November | 0.536016E+11 | 48992.52 | 30-NOV-16:40 | 0.468274E+11 | 113118.70 | 25-NOV-06:10 |
December | 0.580568E+11 | 49482.24 | 26-DEC-16:00 | 0.273002E+12 | 297543.34 | 26-DEC-06:10 |
Annual Sum or Average | 0.616163E+12 | 0.105946E+13 | ||||
Minimum of Months | 0.463995E+11 | 38693.73 | 0.00 | 0.00 | ||
Maximum of Months | 0.580568E+11 | 49482.24 | 0.294538E+12 | 341343.67 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.289799E+11 | 0.100609E+11 | 0.113456E+11 | 0.00 | 0.499275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229890E+10 | 0.00 |
February | 0.242007E+11 | 0.829518E+10 | 0.104160E+11 | 0.00 | 0.465353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210342E+10 | 0.00 |
March | 0.268043E+11 | 0.809078E+10 | 0.121559E+11 | 0.00 | 0.400005E+10 | 0.00 | 0.00 | 12041571.41 | 0.00 | 0.00 | 0.00 | 0.236641E+10 | 0.00 |
April | 0.237629E+11 | 0.672530E+10 | 0.113034E+11 | 0.00 | 0.280548E+10 | 0.00 | 0.00 | 7.18 | 0.00 | 0.00 | 0.00 | 0.221457E+10 | 0.00 |
May | 0.238413E+11 | 0.601347E+10 | 0.117471E+11 | 0.00 | 0.248079E+10 | 0.00 | 0.00 | 80406798.28 | 0.00 | 0.00 | 0.00 | 0.223644E+10 | 0.00 |
June | 0.227521E+11 | 0.539546E+10 | 0.117048E+11 | 0.00 | 0.261968E+10 | 0.00 | 0.00 | 0.220357E+10 | 0.00 | 0.00 | 0.00 | 0.213039E+10 | 0.00 |
July | 0.226720E+11 | 0.571978E+10 | 0.113456E+11 | 0.00 | 0.311403E+10 | 0.00 | 0.00 | 0.619273E+10 | 0.00 | 0.00 | 0.00 | 0.210842E+10 | 0.00 |
August | 0.243712E+11 | 0.651464E+10 | 0.121485E+11 | 0.00 | 0.314437E+10 | 0.00 | 0.00 | 0.456872E+10 | 0.00 | 0.00 | 0.00 | 0.214863E+10 | 0.00 |
September | 0.243836E+11 | 0.735408E+10 | 0.112960E+11 | 0.00 | 0.242893E+10 | 0.00 | 0.00 | 0.800358E+09 | 0.00 | 0.00 | 0.00 | 0.206383E+10 | 0.00 |
October | 0.266471E+11 | 0.873213E+10 | 0.113530E+11 | 0.00 | 0.244540E+10 | 0.00 | 0.00 | 3731043.47 | 0.00 | 0.00 | 0.00 | 0.215434E+10 | 0.00 |
November | 0.279672E+11 | 0.943324E+10 | 0.109019E+11 | 0.00 | 0.316740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213185E+10 | 0.00 |
December | 0.292551E+11 | 0.103250E+11 | 0.113456E+11 | 0.00 | 0.487119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225994E+10 | 0.00 |
Annual Sum or Average | 0.305637E+12 | 0.926600E+11 | 0.137063E+12 | 0.00 | 0.407236E+11 | 0.00 | 0.00 | 0.138616E+11 | 0.00 | 0.00 | 0.00 | 0.262171E+11 | 0.00 |
Minimum of Months | 0.226720E+11 | 0.539546E+10 | 0.104160E+11 | 0.00 | 0.242893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206383E+10 | 0.00 |
Maximum of Months | 0.292551E+11 | 0.103250E+11 | 0.121559E+11 | 0.00 | 0.499275E+10 | 0.00 | 0.00 | 0.619273E+10 | 0.00 | 0.00 | 0.00 | 0.236641E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.292853E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.294538E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.121396E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.255999E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.693290E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 1199233.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 14471755.84 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.453380E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.468274E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.273002E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.105946E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.294538E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 30638.74 | 03-JAN-15:50 | 6986.42 | 01-JAN-06:10 | 10054.01 | 02-JAN-08:09 | 0.00 | 3870.18 | 12-JAN-08:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 29105.75 | 01-FEB-15:00 | 6986.42 | 01-FEB-06:10 | 10054.01 | 01-FEB-08:09 | 0.00 | 3959.97 | 07-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 27688.52 | 01-MAR-09:09 | 6986.42 | 01-MAR-06:10 | 10054.01 | 01-MAR-08:09 | 0.00 | 3458.81 | 06-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 24854.05 | 03-APR-08:09 | 6986.42 | 01-APR-05:10 | 10054.01 | 01-APR-07:10 | 0.00 | 3197.51 | 03-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 24596.32 | 11-MAY-07:10 | 6986.42 | 01-MAY-05:10 | 10054.01 | 01-MAY-07:10 | 0.00 | 2462.55 | 01-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 24538.45 | 14-JUN-07:10 | 6986.42 | 01-JUN-19:49 | 10054.01 | 01-JUN-07:10 | 0.00 | 4702.10 | 27-JUN-12:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 24596.32 | 11-JUL-07:10 | 6986.42 | 01-JUL-19:00 | 10054.01 | 01-JUL-07:10 | 0.00 | 4851.21 | 19-JUL-15:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 24596.32 | 17-AUG-07:10 | 6986.42 | 01-AUG-19:40 | 10054.01 | 01-AUG-07:10 | 0.00 | 4702.10 | 04-AUG-15:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 27213.08 | 26-SEP-07:10 | 6986.42 | 01-SEP-05:10 | 10054.01 | 01-SEP-07:10 | 0.00 | 2396.80 | 01-SEP-14:20 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 30580.87 | 31-OCT-08:09 | 6986.42 | 01-OCT-05:10 | 10054.01 | 02-OCT-07:10 | 0.00 | 3071.94 | 30-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 30696.62 | 27-NOV-15:50 | 6986.42 | 01-NOV-05:10 | 10054.01 | 01-NOV-07:10 | 0.00 | 3192.93 | 24-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 30638.74 | 01-DEC-15:00 | 6986.42 | 01-DEC-06:10 | 10054.01 | 01-DEC-08:09 | 0.00 | 3808.00 | 26-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 24538.45 | 6986.42 | 10054.01 | 0.00 | 2396.80 | 0.00 | 0.00 | |||||
Maximum of Months | 30696.62 | 6986.42 | 10054.01 | 0.00 | 4851.21 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2688.19 | 31-JAN-12:20 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2702.53 | 17-FEB-12:00 | 0.00 |
March | 697.31 | 15-MAR-14:20 | 0.00 | 0.00 | 0.00 | 2685.15 | 03-MAR-12:09 | 0.00 |
April | 0.01 | 22-APR-14:09 | 0.00 | 0.00 | 0.00 | 2575.99 | 01-APR-11:20 | 0.00 |
May | 2143.75 | 31-MAY-17:30 | 0.00 | 0.00 | 0.00 | 2368.46 | 01-MAY-11:39 | 0.00 |
June | 10513.78 | 27-JUN-12:00 | 0.00 | 0.00 | 0.00 | 2080.71 | 01-JUN-11:20 | 0.00 |
July | 12252.82 | 19-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1805.17 | 01-JUL-11:00 | 0.00 |
August | 11014.39 | 14-AUG-17:30 | 0.00 | 0.00 | 0.00 | 1792.67 | 01-AUG-11:00 | 0.00 |
September | 6894.89 | 16-SEP-13:39 | 0.00 | 0.00 | 0.00 | 1803.84 | 29-SEP-11:20 | 0.00 |
October | 415.70 | 11-OCT-14:00 | 0.00 | 0.00 | 0.00 | 2070.69 | 30-OCT-11:39 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2352.42 | 30-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2567.30 | 30-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1792.67 | 0.00 | ||
Maximum of Months | 12252.82 | 0.00 | 0.00 | 0.00 | 2702.53 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 49409.30 | 09-JAN-16:00 | 27270.96 | 10054.01 | 6986.42 | 0.00 | 3476.64 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 43964.90 | 01-FEB-15:00 | 29105.75 | 10054.01 | 0.00 | 0.00 | 2967.41 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 42811.59 | 06-MAR-15:00 | 27514.88 | 10054.01 | 0.00 | 0.00 | 3057.13 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 39420.68 | 05-APR-07:10 | 24596.32 | 10054.01 | 0.00 | 0.00 | 3114.44 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 38693.73 | 11-MAY-07:19 | 24596.32 | 10054.01 | 0.00 | 0.00 | 2396.80 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 42827.72 | 27-JUN-12:00 | 15790.29 | 10054.01 | 0.00 | 0.00 | 4702.10 | 0.00 | 0.00 | 10513.78 | 0.00 |
July | 46322.40 | 15-JUL-13:39 | 18818.12 | 10054.01 | 0.00 | 0.00 | 4702.10 | 0.00 | 0.00 | 11024.23 | 0.00 |
August | 44994.38 | 10-AUG-15:00 | 18890.11 | 10054.01 | 0.00 | 0.00 | 4702.10 | 0.00 | 0.00 | 9748.35 | 0.00 |
September | 43437.30 | 21-SEP-14:00 | 24079.10 | 10054.01 | 0.00 | 0.00 | 2396.80 | 0.00 | 0.00 | 5146.36 | 0.00 |
October | 43512.68 | 31-OCT-08:09 | 30580.87 | 10054.01 | 0.00 | 0.00 | 2396.80 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 48992.52 | 30-NOV-16:40 | 27270.96 | 10054.01 | 6986.42 | 0.00 | 3066.48 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 49482.24 | 26-DEC-16:00 | 27270.96 | 10054.01 | 6986.42 | 0.00 | 3551.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 38693.73 | 15790.29 | 10054.01 | 0.00 | 0.00 | 2396.80 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 49482.24 | 30580.87 | 10054.01 | 6986.42 | 0.00 | 4702.10 | 0.00 | 0.00 | 11024.23 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 341343.67 | 12-JAN-08:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 341284.85 | 07-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 195810.94 | 06-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 139746.53 | 16-APR-03:49 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 25729.91 | 01-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 792.71 | 14-JUN-06:19 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 4883.31 | 30-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 60279.44 | 30-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 113118.70 | 25-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 297543.34 | 26-DEC-06:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 341343.67 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 36.00 | 15.98 | 9.17 | 16.62 | 0.00 | 16.62 | 0.00 | 16.62 |
February | 41.67 | 15.69 | 8.83 | 16.29 | 0.00 | 16.29 | 0.00 | 16.29 |
March | 13.83 | 17.67 | 8.67 | 18.29 | 0.00 | 18.29 | 0.00 | 18.29 |
April | 9.00 | 19.34 | 8.00 | 19.59 | 0.00 | 19.59 | 0.00 | 19.59 |
May | 2.33 | 20.32 | 2.33 | 20.32 | 0.67 | 20.84 | 0.00 | 20.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 24.53 | 0.83 | 24.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 24.61 | 0.83 | 24.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 24.60 | 1.17 | 24.59 |
September | 0.17 | 20.40 | 0.17 | 20.40 | 8.17 | 24.37 | 0.33 | 24.37 |
October | 4.67 | 20.11 | 4.67 | 20.11 | 0.00 | 20.11 | 0.00 | 20.11 |
November | 8.33 | 19.49 | 7.83 | 19.62 | 0.00 | 19.62 | 0.00 | 19.62 |
December | 33.67 | 16.14 | 9.50 | 16.84 | 0.00 | 16.84 | 0.00 | 16.84 |
Annual Sum or Average | 149.67 | 16.69 | 59.17 | 17.48 | 52.83 | 18.92 | 3.17 | 18.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.29 | 0.00 | 16.29 |
Maximum of Months | 41.67 | 20.40 | 9.50 | 20.40 | 18.83 | 24.61 | 1.17 | 24.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 113.00 | 14.15 | 4.17 | 14.14 | 0.00 | 14.14 | 0.00 | 14.14 |
February | 101.67 | 14.04 | 4.00 | 14.03 | 0.00 | 14.03 | 0.00 | 14.03 |
March | 68.17 | 14.42 | 4.33 | 14.42 | 0.00 | 14.42 | 0.00 | 14.42 |
April | 29.00 | 14.73 | 2.50 | 14.73 | 0.00 | 14.73 | 0.00 | 14.73 |
May | 0.33 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.29 | 0.00 | 27.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.39 | 0.00 | 27.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.40 | 0.00 | 27.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6.33 | 14.87 | 0.50 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
November | 55.17 | 14.80 | 3.50 | 14.80 | 0.00 | 14.80 | 0.00 | 14.80 |
December | 112.50 | 14.23 | 4.00 | 14.23 | 0.00 | 14.23 | 0.00 | 14.23 |
Annual Sum or Average | 486.17 | 14.30 | 23.00 | 14.30 | 12.33 | 14.61 | 0.00 | 14.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 113.00 | 14.98 | 4.33 | 14.98 | 7.33 | 27.40 | 0.00 | 27.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.04 | 300.00 | 21.04 | 300.00 | 21.04 |
February | 276.00 | 21.03 | 276.00 | 21.03 | 276.00 | 21.03 |
March | 324.00 | 21.23 | 288.17 | 21.15 | 288.17 | 21.12 |
April | 300.00 | 21.41 | 243.83 | 21.27 | 243.83 | 21.22 |
May | 308.17 | 22.81 | 59.50 | 22.56 | 59.50 | 22.37 |
June | 131.17 | 23.62 | 146.83 | 23.77 | 37.67 | 23.79 |
July | 74.33 | 23.88 | 265.83 | 23.90 | 69.00 | 23.90 |
August | 55.50 | 23.81 | 248.83 | 23.89 | 40.17 | 23.89 |
September | 140.83 | 23.52 | 98.50 | 23.66 | 22.33 | 23.67 |
October | 300.00 | 21.98 | 136.67 | 21.71 | 136.67 | 21.57 |
November | 288.00 | 21.15 | 273.33 | 21.11 | 273.33 | 21.10 |
December | 300.00 | 21.04 | 300.00 | 21.04 | 300.00 | 21.04 |
Annual Sum or Average | 2798.00 | 21.78 | 2637.50 | 21.83 | 2046.67 | 21.68 |
Minimum of Months | 55.50 | 21.03 | 59.50 | 21.03 | 22.33 | 21.03 |
Maximum of Months | 324.00 | 23.88 | 300.00 | 23.90 | 300.00 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.54 | 300.00 | 15.54 | 300.00 | 15.54 |
February | 276.00 | 15.54 | 276.00 | 15.54 | 276.00 | 15.54 |
March | 324.00 | 16.41 | 303.83 | 16.24 | 303.83 | 16.18 |
April | 300.00 | 17.50 | 278.83 | 17.36 | 278.83 | 17.31 |
May | 259.67 | 20.91 | 140.17 | 20.75 | 109.83 | 20.38 |
June | 172.33 | 25.41 | 244.67 | 25.87 | 125.17 | 25.99 |
July | 249.67 | 26.64 | 294.50 | 26.59 | 248.00 | 26.61 |
August | 224.83 | 26.51 | 309.83 | 26.45 | 219.00 | 26.49 |
September | 155.33 | 23.76 | 188.33 | 24.91 | 63.17 | 25.00 |
October | 300.00 | 18.82 | 226.00 | 18.41 | 226.00 | 18.25 |
November | 288.00 | 16.33 | 288.00 | 16.33 | 288.00 | 16.33 |
December | 300.00 | 15.59 | 300.00 | 15.59 | 300.00 | 15.59 |
Annual Sum or Average | 3149.83 | 19.26 | 3150.17 | 19.50 | 2737.83 | 19.29 |
Minimum of Months | 155.33 | 15.54 | 140.17 | 15.54 | 63.17 | 15.54 |
Maximum of Months | 324.00 | 26.64 | 309.83 | 26.59 | 303.83 | 26.61 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 10.03 | 300.00 | 10.03 | 300.00 | 10.03 |
February | 276.00 | 10.03 | 276.00 | 10.03 | 276.00 | 10.03 |
March | 324.00 | 11.34 | 324.00 | 11.34 | 324.00 | 11.34 |
April | 300.00 | 13.24 | 300.00 | 13.24 | 300.00 | 13.24 |
May | 312.00 | 19.07 | 198.17 | 18.48 | 198.17 | 18.22 |
June | 228.50 | 24.50 | 177.83 | 25.22 | 119.17 | 25.51 |
July | 259.83 | 28.67 | 298.33 | 28.46 | 259.83 | 28.53 |
August | 260.17 | 28.09 | 315.33 | 27.89 | 255.50 | 27.98 |
September | 196.33 | 22.47 | 144.50 | 23.21 | 66.00 | 23.17 |
October | 300.00 | 15.76 | 291.67 | 15.69 | 291.67 | 15.66 |
November | 288.00 | 11.45 | 288.00 | 11.45 | 288.00 | 11.45 |
December | 300.00 | 10.09 | 300.00 | 10.09 | 300.00 | 10.09 |
Annual Sum or Average | 3344.83 | 16.50 | 3213.83 | 16.51 | 2978.33 | 16.29 |
Minimum of Months | 196.33 | 10.03 | 144.50 | 10.03 | 66.00 | 10.03 |
Maximum of Months | 324.00 | 28.67 | 324.00 | 28.46 | 324.00 | 28.53 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 50339586.77 | 12041571.41 | 8.67 | 46011742.54 | 4327844.24 | 0.00 | 0.30 | 15-MAR-14:20 | 0.00 | 01-MAR-00:03 | 2919.24 | 15-MAR-15:10 | 2755.78 | 15-MAR-14:20 | 243.58 | 14-MAR-14:20 | 697.31 | 15-MAR-14:20 | 0.00 | 01-MAR-00:03 |
April | 29.54 | 7.18 | 0.17 | 29.54 | 0.00 | 0.00 | 0.00 | 22-APR-14:10 | 0.00 | 01-APR-00:05 | 0.05 | 22-APR-14:10 | 0.05 | 22-APR-14:10 | 0.00 | 22-APR-14:10 | 0.01 | 22-APR-14:10 | 0.00 | 01-APR-00:05 |
May | 0.348946E+09 | 80406798.28 | 43.81 | 0.334985E+09 | 13960969.31 | 0.00 | 1.00 | 23-MAY-17:33 | 0.00 | 01-MAY-00:10 | 19644.05 | 31-MAY-17:25 | 19414.13 | 23-MAY-17:33 | 1956.23 | 31-MAY-19:25 | 4287.50 | 31-MAY-17:25 | 0.00 | 01-MAY-00:10 |
June | 0.449187E+10 | 0.988141E+09 | 205.38 | 0.353826E+10 | 0.953615E+09 | 0.00 | 1.00 | 01-JUN-17:10 | 0.00 | 01-JUN-00:10 | 24111.31 | 27-JUN-19:45 | 19844.99 | 24-JUN-17:45 | 12003.76 | 27-JUN-20:40 | 5062.28 | 27-JUN-19:45 | 0.00 | 01-JUN-00:10 |
July | 0.101087E+11 | 0.220351E+10 | 349.13 | 0.735085E+10 | 0.275781E+10 | 0.00 | 1.00 | 01-JUL-17:10 | 0.00 | 01-JUL-00:10 | 24121.93 | 20-JUL-05:45 | 19533.06 | 06-JUL-17:45 | 13035.71 | 17-JUL-17:12 | 5059.60 | 20-JUL-05:45 | 0.00 | 01-JUL-00:10 |
August | 0.824621E+10 | 0.181188E+10 | 318.80 | 0.661042E+10 | 0.163579E+10 | 0.00 | 1.00 | 01-AUG-00:05 | 0.00 | 01-AUG-00:10 | 24895.32 | 13-AUG-23:01 | 19910.15 | 01-AUG-17:11 | 12726.02 | 13-AUG-23:15 | 5179.03 | 13-AUG-23:01 | 0.00 | 01-AUG-00:05 |
September | 0.260280E+10 | 0.574091E+09 | 142.55 | 0.198041E+10 | 0.622391E+09 | 0.00 | 1.00 | 01-SEP-17:15 | 0.00 | 01-SEP-00:10 | 23358.25 | 15-SEP-20:11 | 19563.04 | 22-SEP-17:15 | 11725.16 | 15-SEP-23:40 | 4950.43 | 15-SEP-20:11 | 0.00 | 01-SEP-00:10 |
October | 15707688.47 | 3731043.47 | 5.33 | 15509264.25 | 198424.23 | 0.00 | 0.19 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1760.16 | 11-OCT-15:00 | 1736.09 | 11-OCT-15:00 | 63.36 | 11-OCT-16:00 | 415.70 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.258645E+11 | 0.567380E+10 | 1073.83 | 0.198765E+11 | 0.598809E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.101087E+11 | 0.220351E+10 | 349.13 | 0.735085E+10 | 0.275781E+10 | 0.00 | 1.00 | 0.00 | 24895.32 | 19910.15 | 13035.71 | 5179.03 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 0.504263E+10 | 0.121543E+10 | 101.53 | 0.356689E+10 | 0.147573E+10 | 0.00 | 1.00 | 11-JUN-13:15 | 0.00 | 01-JUN-00:10 | 78249.85 | 27-JUN-18:53 | 61270.66 | 30-JUN-17:11 | 39402.57 | 27-JUN-18:53 | 17061.40 | 27-JUN-17:20 | 0.00 | 01-JUN-00:10 |
July | 0.168143E+11 | 0.398922E+10 | 245.27 | 0.114560E+11 | 0.535829E+10 | 0.00 | 1.00 | 01-JUL-17:11 | 0.00 | 01-JUL-00:10 | 82030.64 | 20-JUL-22:45 | 61499.79 | 06-JUL-17:38 | 47060.34 | 20-JUL-22:45 | 17455.11 | 21-JUL-04:15 | 0.00 | 01-JUL-00:10 |
August | 0.112963E+11 | 0.275685E+10 | 202.76 | 0.885468E+10 | 0.244166E+10 | 0.00 | 1.00 | 01-AUG-17:11 | 0.00 | 01-AUG-00:05 | 77868.34 | 13-AUG-18:45 | 62740.44 | 03-AUG-18:53 | 36886.90 | 13-AUG-18:45 | 17059.59 | 13-AUG-17:05 | 0.00 | 01-AUG-00:05 |
September | 0.907336E+09 | 0.226267E+09 | 30.83 | 0.660073E+09 | 0.247263E+09 | 0.00 | 0.61 | 16-SEP-13:30 | 0.00 | 01-SEP-00:10 | 19835.82 | 16-SEP-13:30 | 14652.68 | 16-SEP-13:40 | 6539.77 | 15-SEP-12:10 | 4878.65 | 16-SEP-13:30 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.340606E+11 | 0.818777E+10 | 580.40 | 0.245376E+11 | 0.952295E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.168143E+11 | 0.398922E+10 | 245.27 | 0.114560E+11 | 0.535829E+10 | 0.00 | 1.00 | 0.00 | 82030.64 | 62740.44 | 47060.34 | 17455.11 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.24 | 12.30 | 39.94 | 13.55 | 202.34 | 0.00 | 0.00 | 0.00 |
February | 84.65 | 21.85 | 62.80 | 33.97 | 188.96 | 0.00 | 0.00 | 0.00 |
March | 133.07 | 57.20 | 75.86 | 109.41 | 121.93 | 0.00 | 0.00 | 0.00 |
April | 161.87 | 66.25 | 95.62 | 160.57 | 81.99 | 0.00 | 0.00 | 0.00 |
May | 191.10 | 86.29 | 104.81 | 214.35 | 59.82 | 0.00 | 0.00 | 0.00 |
June | 230.87 | 108.62 | 122.26 | 279.96 | 48.99 | 0.00 | 0.00 | 0.00 |
July | 206.17 | 90.26 | 115.90 | 266.29 | 35.60 | 0.00 | 0.00 | 0.00 |
August | 186.26 | 78.99 | 107.27 | 235.74 | 46.50 | 0.00 | 0.00 | 0.00 |
September | 146.66 | 63.37 | 83.29 | 164.59 | 72.10 | 0.00 | 0.00 | 0.00 |
October | 95.04 | 33.48 | 61.56 | 85.29 | 90.15 | 0.00 | 0.00 | 0.00 |
November | 55.86 | 15.86 | 40.00 | 35.36 | 114.33 | 0.00 | 0.00 | 0.00 |
December | 48.73 | 10.56 | 38.17 | 12.74 | 193.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 132.93 | 53.91 | 79.02 | 134.86 | 104.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.73 | 10.56 | 38.17 | 12.74 | 35.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 230.87 | 108.62 | 122.26 | 279.96 | 202.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.24 | 12.30 | 39.94 | 13.55 | 202.34 | 0.00 | 0.00 | 0.00 |
February | 84.65 | 21.85 | 62.80 | 33.97 | 188.96 | 0.00 | 0.00 | 0.00 |
March | 133.07 | 57.20 | 75.86 | 109.41 | 121.93 | 0.00 | 0.00 | 0.00 |
April | 161.87 | 66.25 | 95.62 | 160.57 | 81.99 | 0.00 | 0.00 | 0.00 |
May | 191.10 | 86.29 | 104.81 | 214.35 | 59.82 | 0.00 | 0.00 | 0.00 |
June | 230.87 | 108.62 | 122.26 | 279.96 | 48.99 | 0.00 | 0.00 | 0.00 |
July | 206.17 | 90.26 | 115.90 | 266.29 | 35.60 | 0.00 | 0.00 | 0.00 |
August | 186.26 | 78.99 | 107.27 | 235.74 | 46.50 | 0.00 | 0.00 | 0.00 |
September | 146.66 | 63.37 | 83.29 | 164.59 | 72.10 | 0.00 | 0.00 | 0.00 |
October | 95.04 | 33.48 | 61.56 | 85.29 | 90.15 | 0.00 | 0.00 | 0.00 |
November | 55.86 | 15.86 | 40.00 | 35.36 | 114.33 | 0.00 | 0.00 | 0.00 |
December | 48.73 | 10.56 | 38.17 | 12.74 | 193.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 132.93 | 53.91 | 79.02 | 134.86 | 104.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.73 | 10.56 | 38.17 | 12.74 | 35.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 230.87 | 108.62 | 122.26 | 279.96 | 202.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.37 | 0.00 | 19.37 | 0.16 | 126.13 | 0.00 | 0.00 | 0.00 |
February | 29.51 | 0.00 | 29.51 | 1.19 | 117.78 | 0.00 | 0.00 | 0.00 |
March | 35.80 | 0.00 | 35.80 | 12.43 | 77.85 | 0.00 | 0.00 | 0.00 |
April | 45.64 | 0.22 | 45.42 | 27.49 | 48.92 | 0.00 | 0.00 | 0.00 |
May | 53.02 | 2.28 | 50.73 | 43.43 | 33.07 | 0.00 | 0.00 | 0.00 |
June | 63.74 | 5.42 | 58.32 | 64.81 | 26.48 | 0.00 | 0.00 | 0.00 |
July | 59.36 | 4.04 | 55.33 | 70.20 | 19.14 | 0.00 | 0.00 | 0.00 |
August | 51.40 | 0.99 | 50.40 | 56.52 | 26.21 | 0.00 | 0.00 | 0.00 |
September | 38.95 | 0.02 | 38.94 | 31.71 | 42.97 | 0.00 | 0.00 | 0.00 |
October | 29.11 | 0.00 | 29.11 | 14.57 | 54.47 | 0.00 | 0.00 | 0.00 |
November | 19.56 | 0.00 | 19.56 | 4.94 | 68.97 | 0.00 | 0.00 | 0.00 |
December | 18.13 | 0.00 | 18.13 | 0.25 | 118.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.67 | 1.09 | 37.58 | 27.47 | 63.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.13 | 0.00 | 18.13 | 0.16 | 19.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.74 | 5.42 | 58.32 | 70.20 | 126.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.37 | 0.00 | 19.37 | 0.16 | 126.13 | 0.00 | 0.00 | 0.00 |
February | 29.51 | 0.00 | 29.51 | 1.19 | 117.78 | 0.00 | 0.00 | 0.00 |
March | 35.80 | 0.00 | 35.80 | 12.42 | 77.85 | 0.00 | 0.00 | 0.00 |
April | 45.64 | 0.22 | 45.42 | 27.49 | 48.92 | 0.00 | 0.00 | 0.00 |
May | 53.01 | 2.28 | 50.73 | 43.43 | 33.07 | 0.00 | 0.00 | 0.00 |
June | 63.74 | 5.42 | 58.32 | 64.81 | 26.48 | 0.00 | 0.00 | 0.00 |
July | 59.36 | 4.04 | 55.32 | 70.19 | 19.14 | 0.00 | 0.00 | 0.00 |
August | 51.39 | 0.99 | 50.40 | 56.52 | 26.21 | 0.00 | 0.00 | 0.00 |
September | 38.95 | 0.02 | 38.93 | 31.71 | 42.97 | 0.00 | 0.00 | 0.00 |
October | 29.10 | 0.00 | 29.10 | 14.57 | 54.47 | 0.00 | 0.00 | 0.00 |
November | 19.56 | 0.00 | 19.56 | 4.94 | 68.97 | 0.00 | 0.00 | 0.00 |
December | 18.13 | 0.00 | 18.13 | 0.25 | 118.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.67 | 1.09 | 37.58 | 27.47 | 63.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.13 | 0.00 | 18.13 | 0.16 | 19.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.74 | 5.42 | 58.32 | 70.19 | 126.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.75 | 7.47 | 17.27 | 9.22 | 105.48 | 0.00 | 0.00 | 0.00 |
February | 39.07 | 11.49 | 27.58 | 24.79 | 101.11 | 0.00 | 0.00 | 0.00 |
March | 60.77 | 31.48 | 29.29 | 65.63 | 68.51 | 8.83 | 0.00 | 0.00 |
April | 79.95 | 42.46 | 37.49 | 101.36 | 45.79 | 0.00 | 0.00 | 0.00 |
May | 102.40 | 63.04 | 39.36 | 138.29 | 36.81 | 8.67 | 0.00 | 0.00 |
June | 118.49 | 74.24 | 44.25 | 165.86 | 34.48 | 1.00 | 0.00 | 0.00 |
July | 110.20 | 66.97 | 43.23 | 160.99 | 28.80 | 0.00 | 0.00 | 0.00 |
August | 93.71 | 52.05 | 41.66 | 133.79 | 34.83 | 2.50 | 0.00 | 0.00 |
September | 69.34 | 37.58 | 31.76 | 90.83 | 46.30 | 6.33 | 0.00 | 0.00 |
October | 43.36 | 18.73 | 24.64 | 49.94 | 48.78 | 0.00 | 0.00 | 0.00 |
November | 25.02 | 7.74 | 17.29 | 21.32 | 59.56 | 0.00 | 0.00 | 0.00 |
December | 21.75 | 4.74 | 17.01 | 7.27 | 99.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.87 | 34.96 | 30.91 | 81.08 | 58.97 | 27.33 | 0.00 | 0.00 |
Minimum of Months | 21.75 | 4.74 | 17.01 | 7.27 | 28.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.49 | 74.24 | 44.25 | 165.86 | 105.48 | 8.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.75 | 7.47 | 17.27 | 9.22 | 105.48 | 0.00 | 0.00 | 0.00 |
February | 39.07 | 11.49 | 27.58 | 24.79 | 101.11 | 0.00 | 0.00 | 0.00 |
March | 60.77 | 31.48 | 29.29 | 65.63 | 68.51 | 8.83 | 0.00 | 0.00 |
April | 79.95 | 42.46 | 37.49 | 101.36 | 45.79 | 0.00 | 0.00 | 0.00 |
May | 102.40 | 63.04 | 39.36 | 138.29 | 36.81 | 8.67 | 0.00 | 0.00 |
June | 118.49 | 74.24 | 44.25 | 165.86 | 34.48 | 1.00 | 0.00 | 0.00 |
July | 110.20 | 66.97 | 43.23 | 160.99 | 28.80 | 0.00 | 0.00 | 0.00 |
August | 93.71 | 52.05 | 41.66 | 133.79 | 34.83 | 2.50 | 0.00 | 0.00 |
September | 69.34 | 37.58 | 31.76 | 90.83 | 46.30 | 6.33 | 0.00 | 0.00 |
October | 43.36 | 18.73 | 24.64 | 49.94 | 48.78 | 0.00 | 0.00 | 0.00 |
November | 25.02 | 7.74 | 17.29 | 21.32 | 59.56 | 0.00 | 0.00 | 0.00 |
December | 21.75 | 4.74 | 17.01 | 7.27 | 99.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.87 | 34.96 | 30.91 | 81.08 | 58.97 | 27.33 | 0.00 | 0.00 |
Minimum of Months | 21.75 | 4.74 | 17.01 | 7.27 | 28.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.49 | 74.24 | 44.25 | 165.86 | 105.48 | 8.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.75 | 7.47 | 17.27 | 9.22 | 105.48 | 0.00 | 0.00 | 0.00 |
February | 39.07 | 11.49 | 27.58 | 24.79 | 101.11 | 0.00 | 0.00 | 0.00 |
March | 60.77 | 31.48 | 29.29 | 65.63 | 68.51 | 8.83 | 0.00 | 0.00 |
April | 79.95 | 42.46 | 37.49 | 101.36 | 45.79 | 0.00 | 0.00 | 0.00 |
May | 102.40 | 63.04 | 39.36 | 138.29 | 36.81 | 8.67 | 0.00 | 0.00 |
June | 118.49 | 74.24 | 44.25 | 165.86 | 34.48 | 1.00 | 0.00 | 0.00 |
July | 110.20 | 66.97 | 43.23 | 160.99 | 28.80 | 0.00 | 0.00 | 0.00 |
August | 93.71 | 52.05 | 41.66 | 133.79 | 34.83 | 2.50 | 0.00 | 0.00 |
September | 69.34 | 37.58 | 31.76 | 90.83 | 46.30 | 6.33 | 0.00 | 0.00 |
October | 43.36 | 18.73 | 24.64 | 49.94 | 48.78 | 0.00 | 0.00 | 0.00 |
November | 25.02 | 7.74 | 17.29 | 21.32 | 59.56 | 0.00 | 0.00 | 0.00 |
December | 21.75 | 4.74 | 17.01 | 7.27 | 99.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.87 | 34.96 | 30.91 | 81.08 | 58.97 | 27.33 | 0.00 | 0.00 |
Minimum of Months | 21.75 | 4.74 | 17.01 | 7.27 | 28.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.49 | 74.24 | 44.25 | 165.86 | 105.48 | 8.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.75 | 7.47 | 17.27 | 9.22 | 105.48 | 0.00 | 0.00 | 0.00 |
February | 39.07 | 11.49 | 27.58 | 24.79 | 101.11 | 0.00 | 0.00 | 0.00 |
March | 60.77 | 31.48 | 29.29 | 65.63 | 68.51 | 8.83 | 0.00 | 0.00 |
April | 79.95 | 42.46 | 37.49 | 101.36 | 45.79 | 0.00 | 0.00 | 0.00 |
May | 102.40 | 63.04 | 39.36 | 138.29 | 36.81 | 8.67 | 0.00 | 0.00 |
June | 118.49 | 74.24 | 44.25 | 165.86 | 34.48 | 1.00 | 0.00 | 0.00 |
July | 110.20 | 66.97 | 43.23 | 160.99 | 28.80 | 0.00 | 0.00 | 0.00 |
August | 93.71 | 52.05 | 41.66 | 133.79 | 34.83 | 2.50 | 0.00 | 0.00 |
September | 69.34 | 37.58 | 31.76 | 90.83 | 46.30 | 6.33 | 0.00 | 0.00 |
October | 43.36 | 18.73 | 24.64 | 49.94 | 48.78 | 0.00 | 0.00 | 0.00 |
November | 25.02 | 7.74 | 17.29 | 21.32 | 59.56 | 0.00 | 0.00 | 0.00 |
December | 21.75 | 4.74 | 17.01 | 7.27 | 99.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.87 | 34.96 | 30.91 | 81.08 | 58.97 | 27.33 | 0.00 | 0.00 |
Minimum of Months | 21.75 | 4.74 | 17.01 | 7.27 | 28.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.49 | 74.24 | 44.25 | 165.86 | 105.48 | 8.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.75 | 7.47 | 17.27 | 9.22 | 105.48 | 0.00 | 0.00 | 0.00 |
February | 39.07 | 11.49 | 27.58 | 24.79 | 101.11 | 0.00 | 0.00 | 0.00 |
March | 60.77 | 31.48 | 29.29 | 65.63 | 68.51 | 8.83 | 0.00 | 0.00 |
April | 79.95 | 42.46 | 37.49 | 101.36 | 45.79 | 0.00 | 0.00 | 0.00 |
May | 102.40 | 63.04 | 39.36 | 138.29 | 36.81 | 8.67 | 0.00 | 0.00 |
June | 118.49 | 74.24 | 44.25 | 165.86 | 34.48 | 1.00 | 0.00 | 0.00 |
July | 110.20 | 66.97 | 43.23 | 160.99 | 28.80 | 0.00 | 0.00 | 0.00 |
August | 93.71 | 52.05 | 41.66 | 133.79 | 34.83 | 2.50 | 0.00 | 0.00 |
September | 69.34 | 37.58 | 31.76 | 90.83 | 46.30 | 6.33 | 0.00 | 0.00 |
October | 43.36 | 18.73 | 24.64 | 49.94 | 48.78 | 0.00 | 0.00 | 0.00 |
November | 25.02 | 7.74 | 17.29 | 21.32 | 59.56 | 0.00 | 0.00 | 0.00 |
December | 21.75 | 4.74 | 17.01 | 7.27 | 99.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.87 | 34.96 | 30.91 | 81.08 | 58.97 | 27.33 | 0.00 | 0.00 |
Minimum of Months | 21.75 | 4.74 | 17.01 | 7.27 | 28.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.49 | 74.24 | 44.25 | 165.86 | 105.48 | 8.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.75 | 7.47 | 17.27 | 9.22 | 105.48 | 0.00 | 0.00 | 0.00 |
February | 39.07 | 11.49 | 27.58 | 24.79 | 101.11 | 0.00 | 0.00 | 0.00 |
March | 60.77 | 31.48 | 29.29 | 65.63 | 68.51 | 8.83 | 0.00 | 0.00 |
April | 79.95 | 42.46 | 37.49 | 101.36 | 45.79 | 0.00 | 0.00 | 0.00 |
May | 102.40 | 63.04 | 39.36 | 138.29 | 36.81 | 8.67 | 0.00 | 0.00 |
June | 118.49 | 74.24 | 44.25 | 165.86 | 34.48 | 1.00 | 0.00 | 0.00 |
July | 110.20 | 66.97 | 43.23 | 160.99 | 28.80 | 0.00 | 0.00 | 0.00 |
August | 93.71 | 52.05 | 41.66 | 133.79 | 34.83 | 2.50 | 0.00 | 0.00 |
September | 69.34 | 37.58 | 31.76 | 90.83 | 46.30 | 6.33 | 0.00 | 0.00 |
October | 43.36 | 18.73 | 24.64 | 49.94 | 48.78 | 0.00 | 0.00 | 0.00 |
November | 25.02 | 7.74 | 17.29 | 21.32 | 59.56 | 0.00 | 0.00 | 0.00 |
December | 21.75 | 4.74 | 17.01 | 7.27 | 99.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.87 | 34.96 | 30.91 | 81.08 | 58.97 | 27.33 | 0.00 | 0.00 |
Minimum of Months | 21.75 | 4.74 | 17.01 | 7.27 | 28.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.49 | 74.24 | 44.25 | 165.86 | 105.48 | 8.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.75 | 7.47 | 17.27 | 9.22 | 105.48 | 0.00 | 0.00 | 0.00 |
February | 39.07 | 11.49 | 27.58 | 24.79 | 101.11 | 0.00 | 0.00 | 0.00 |
March | 60.77 | 31.48 | 29.29 | 65.63 | 68.51 | 8.83 | 0.00 | 0.00 |
April | 79.95 | 42.46 | 37.49 | 101.36 | 45.79 | 0.00 | 0.00 | 0.00 |
May | 102.40 | 63.04 | 39.36 | 138.29 | 36.81 | 8.67 | 0.00 | 0.00 |
June | 118.49 | 74.24 | 44.25 | 165.86 | 34.48 | 1.00 | 0.00 | 0.00 |
July | 110.20 | 66.97 | 43.23 | 160.99 | 28.80 | 0.00 | 0.00 | 0.00 |
August | 93.71 | 52.05 | 41.66 | 133.79 | 34.83 | 2.50 | 0.00 | 0.00 |
September | 69.34 | 37.58 | 31.76 | 90.83 | 46.30 | 6.33 | 0.00 | 0.00 |
October | 43.36 | 18.73 | 24.64 | 49.94 | 48.78 | 0.00 | 0.00 | 0.00 |
November | 25.02 | 7.74 | 17.29 | 21.32 | 59.56 | 0.00 | 0.00 | 0.00 |
December | 21.75 | 4.74 | 17.01 | 7.27 | 99.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.87 | 34.96 | 30.91 | 81.08 | 58.97 | 27.33 | 0.00 | 0.00 |
Minimum of Months | 21.75 | 4.74 | 17.01 | 7.27 | 28.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.49 | 74.24 | 44.25 | 165.86 | 105.48 | 8.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.75 | 7.47 | 17.27 | 9.22 | 105.48 | 0.00 | 0.00 | 0.00 |
February | 39.07 | 11.49 | 27.58 | 24.79 | 101.11 | 0.00 | 0.00 | 0.00 |
March | 60.77 | 31.48 | 29.29 | 65.63 | 68.51 | 8.83 | 0.00 | 0.00 |
April | 79.95 | 42.46 | 37.49 | 101.36 | 45.79 | 0.00 | 0.00 | 0.00 |
May | 102.40 | 63.04 | 39.36 | 138.29 | 36.81 | 8.67 | 0.00 | 0.00 |
June | 118.49 | 74.24 | 44.25 | 165.86 | 34.48 | 1.00 | 0.00 | 0.00 |
July | 110.20 | 66.97 | 43.23 | 160.99 | 28.80 | 0.00 | 0.00 | 0.00 |
August | 93.71 | 52.05 | 41.66 | 133.79 | 34.83 | 2.50 | 0.00 | 0.00 |
September | 69.34 | 37.58 | 31.76 | 90.83 | 46.30 | 6.33 | 0.00 | 0.00 |
October | 43.36 | 18.73 | 24.64 | 49.94 | 48.78 | 0.00 | 0.00 | 0.00 |
November | 25.02 | 7.74 | 17.29 | 21.32 | 59.56 | 0.00 | 0.00 | 0.00 |
December | 21.75 | 4.74 | 17.01 | 7.27 | 99.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.87 | 34.96 | 30.91 | 81.08 | 58.97 | 27.33 | 0.00 | 0.00 |
Minimum of Months | 21.75 | 4.74 | 17.01 | 7.27 | 28.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.49 | 74.24 | 44.25 | 165.86 | 105.48 | 8.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.75 | 7.47 | 17.27 | 9.22 | 105.48 | 0.00 | 0.00 | 0.00 |
February | 39.07 | 11.49 | 27.58 | 24.79 | 101.11 | 0.00 | 0.00 | 0.00 |
March | 60.77 | 31.48 | 29.29 | 65.63 | 68.51 | 8.83 | 0.00 | 0.00 |
April | 79.95 | 42.46 | 37.49 | 101.36 | 45.79 | 0.00 | 0.00 | 0.00 |
May | 102.40 | 63.04 | 39.36 | 138.29 | 36.81 | 8.67 | 0.00 | 0.00 |
June | 118.49 | 74.24 | 44.25 | 165.86 | 34.48 | 1.00 | 0.00 | 0.00 |
July | 110.20 | 66.97 | 43.23 | 160.99 | 28.80 | 0.00 | 0.00 | 0.00 |
August | 93.71 | 52.05 | 41.66 | 133.79 | 34.83 | 2.50 | 0.00 | 0.00 |
September | 69.34 | 37.58 | 31.76 | 90.83 | 46.30 | 6.33 | 0.00 | 0.00 |
October | 43.36 | 18.73 | 24.64 | 49.94 | 48.78 | 0.00 | 0.00 | 0.00 |
November | 25.02 | 7.74 | 17.29 | 21.32 | 59.56 | 0.00 | 0.00 | 0.00 |
December | 21.75 | 4.74 | 17.01 | 7.27 | 99.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.87 | 34.96 | 30.91 | 81.08 | 58.97 | 27.33 | 0.00 | 0.00 |
Minimum of Months | 21.75 | 4.74 | 17.01 | 7.27 | 28.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.49 | 74.24 | 44.25 | 165.86 | 105.48 | 8.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.75 | 7.47 | 17.27 | 9.22 | 105.48 | 0.00 | 0.00 | 0.00 |
February | 39.07 | 11.49 | 27.58 | 24.79 | 101.11 | 0.00 | 0.00 | 0.00 |
March | 60.77 | 31.48 | 29.29 | 65.63 | 68.51 | 8.83 | 0.00 | 0.00 |
April | 79.95 | 42.46 | 37.49 | 101.36 | 45.79 | 0.00 | 0.00 | 0.00 |
May | 102.40 | 63.04 | 39.36 | 138.29 | 36.81 | 8.67 | 0.00 | 0.00 |
June | 118.49 | 74.24 | 44.25 | 165.86 | 34.48 | 1.00 | 0.00 | 0.00 |
July | 110.20 | 66.97 | 43.23 | 160.99 | 28.80 | 0.00 | 0.00 | 0.00 |
August | 93.71 | 52.05 | 41.66 | 133.79 | 34.83 | 2.50 | 0.00 | 0.00 |
September | 69.34 | 37.58 | 31.76 | 90.83 | 46.30 | 6.33 | 0.00 | 0.00 |
October | 43.36 | 18.73 | 24.64 | 49.94 | 48.78 | 0.00 | 0.00 | 0.00 |
November | 25.02 | 7.74 | 17.29 | 21.32 | 59.56 | 0.00 | 0.00 | 0.00 |
December | 21.75 | 4.74 | 17.01 | 7.27 | 99.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.87 | 34.96 | 30.91 | 81.08 | 58.97 | 27.33 | 0.00 | 0.00 |
Minimum of Months | 21.75 | 4.74 | 17.01 | 7.27 | 28.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.49 | 74.24 | 44.25 | 165.86 | 105.48 | 8.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.75 | 7.47 | 17.27 | 9.22 | 105.48 | 0.00 | 0.00 | 0.00 |
February | 39.07 | 11.49 | 27.58 | 24.79 | 101.11 | 0.00 | 0.00 | 0.00 |
March | 60.77 | 31.48 | 29.29 | 65.63 | 68.51 | 8.83 | 0.00 | 0.00 |
April | 79.95 | 42.46 | 37.49 | 101.36 | 45.79 | 0.00 | 0.00 | 0.00 |
May | 102.40 | 63.04 | 39.36 | 138.29 | 36.81 | 8.67 | 0.00 | 0.00 |
June | 118.49 | 74.24 | 44.25 | 165.86 | 34.48 | 1.00 | 0.00 | 0.00 |
July | 110.20 | 66.97 | 43.23 | 160.99 | 28.80 | 0.00 | 0.00 | 0.00 |
August | 93.71 | 52.05 | 41.66 | 133.79 | 34.83 | 2.50 | 0.00 | 0.00 |
September | 69.34 | 37.58 | 31.76 | 90.83 | 46.30 | 6.33 | 0.00 | 0.00 |
October | 43.36 | 18.73 | 24.64 | 49.94 | 48.78 | 0.00 | 0.00 | 0.00 |
November | 25.02 | 7.74 | 17.29 | 21.32 | 59.56 | 0.00 | 0.00 | 0.00 |
December | 21.75 | 4.74 | 17.01 | 7.27 | 99.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.87 | 34.96 | 30.91 | 81.08 | 58.97 | 27.33 | 0.00 | 0.00 |
Minimum of Months | 21.75 | 4.74 | 17.01 | 7.27 | 28.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.49 | 74.24 | 44.25 | 165.86 | 105.48 | 8.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.75 | 7.47 | 17.27 | 9.22 | 105.48 | 0.00 | 0.00 | 0.00 |
February | 39.07 | 11.49 | 27.58 | 24.79 | 101.11 | 0.00 | 0.00 | 0.00 |
March | 60.77 | 31.48 | 29.29 | 65.63 | 68.51 | 8.83 | 0.00 | 0.00 |
April | 79.95 | 42.46 | 37.49 | 101.36 | 45.79 | 0.00 | 0.00 | 0.00 |
May | 102.40 | 63.04 | 39.36 | 138.29 | 36.81 | 8.67 | 0.00 | 0.00 |
June | 118.49 | 74.24 | 44.25 | 165.86 | 34.48 | 1.00 | 0.00 | 0.00 |
July | 110.20 | 66.97 | 43.23 | 160.99 | 28.80 | 0.00 | 0.00 | 0.00 |
August | 93.71 | 52.05 | 41.66 | 133.79 | 34.83 | 2.50 | 0.00 | 0.00 |
September | 69.34 | 37.58 | 31.76 | 90.83 | 46.30 | 6.33 | 0.00 | 0.00 |
October | 43.36 | 18.73 | 24.64 | 49.94 | 48.78 | 0.00 | 0.00 | 0.00 |
November | 25.02 | 7.74 | 17.29 | 21.32 | 59.56 | 0.00 | 0.00 | 0.00 |
December | 21.75 | 4.74 | 17.01 | 7.27 | 99.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.87 | 34.96 | 30.91 | 81.08 | 58.97 | 27.33 | 0.00 | 0.00 |
Minimum of Months | 21.75 | 4.74 | 17.01 | 7.27 | 28.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.49 | 74.24 | 44.25 | 165.86 | 105.48 | 8.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.75 | 7.47 | 17.27 | 9.22 | 105.48 | 0.00 | 0.00 | 0.00 |
February | 39.07 | 11.49 | 27.58 | 24.79 | 101.11 | 0.00 | 0.00 | 0.00 |
March | 60.77 | 31.48 | 29.29 | 65.63 | 68.51 | 8.83 | 0.00 | 0.00 |
April | 79.95 | 42.46 | 37.49 | 101.36 | 45.79 | 0.00 | 0.00 | 0.00 |
May | 102.40 | 63.04 | 39.36 | 138.29 | 36.81 | 8.67 | 0.00 | 0.00 |
June | 118.49 | 74.24 | 44.25 | 165.86 | 34.48 | 1.00 | 0.00 | 0.00 |
July | 110.20 | 66.97 | 43.23 | 160.99 | 28.80 | 0.00 | 0.00 | 0.00 |
August | 93.71 | 52.05 | 41.66 | 133.79 | 34.83 | 2.50 | 0.00 | 0.00 |
September | 69.34 | 37.58 | 31.76 | 90.83 | 46.30 | 6.33 | 0.00 | 0.00 |
October | 43.36 | 18.73 | 24.64 | 49.94 | 48.78 | 0.00 | 0.00 | 0.00 |
November | 25.02 | 7.74 | 17.29 | 21.32 | 59.56 | 0.00 | 0.00 | 0.00 |
December | 21.75 | 4.74 | 17.01 | 7.27 | 99.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.87 | 34.96 | 30.91 | 81.08 | 58.97 | 27.33 | 0.00 | 0.00 |
Minimum of Months | 21.75 | 4.74 | 17.01 | 7.27 | 28.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.49 | 74.24 | 44.25 | 165.86 | 105.48 | 8.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.75 | 7.47 | 17.27 | 9.22 | 105.48 | 0.00 | 0.00 | 0.00 |
February | 39.07 | 11.49 | 27.58 | 24.79 | 101.11 | 0.00 | 0.00 | 0.00 |
March | 60.77 | 31.48 | 29.29 | 65.63 | 68.51 | 8.83 | 0.00 | 0.00 |
April | 79.95 | 42.46 | 37.49 | 101.36 | 45.79 | 0.00 | 0.00 | 0.00 |
May | 102.40 | 63.04 | 39.36 | 138.29 | 36.81 | 8.67 | 0.00 | 0.00 |
June | 118.49 | 74.24 | 44.25 | 165.86 | 34.48 | 1.00 | 0.00 | 0.00 |
July | 110.20 | 66.97 | 43.23 | 160.99 | 28.80 | 0.00 | 0.00 | 0.00 |
August | 93.71 | 52.05 | 41.66 | 133.79 | 34.83 | 2.50 | 0.00 | 0.00 |
September | 69.34 | 37.58 | 31.76 | 90.83 | 46.30 | 6.33 | 0.00 | 0.00 |
October | 43.36 | 18.73 | 24.64 | 49.94 | 48.78 | 0.00 | 0.00 | 0.00 |
November | 25.02 | 7.74 | 17.29 | 21.32 | 59.56 | 0.00 | 0.00 | 0.00 |
December | 21.75 | 4.74 | 17.01 | 7.27 | 99.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.87 | 34.96 | 30.91 | 81.08 | 58.97 | 27.33 | 0.00 | 0.00 |
Minimum of Months | 21.75 | 4.74 | 17.01 | 7.27 | 28.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.49 | 74.24 | 44.25 | 165.86 | 105.48 | 8.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.42 | 119.51 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 34.02 | 116.60 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 83.05 | 73.99 | 37.17 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 122.91 | 46.12 | 22.83 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 160.29 | 43.11 | 9.00 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 187.33 | 44.60 | 13.00 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 174.13 | 44.75 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 144.86 | 52.79 | 4.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 103.53 | 59.64 | 18.00 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 60.73 | 54.99 | 15.50 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.98 | 55.35 | 15.33 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.89 | 108.92 | 0.83 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 94.32 | 68.15 | 140.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.89 | 43.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 187.33 | 119.51 | 37.17 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139919E+09 | 32952487.93 | 0.106966E+09 | 36299377.56 | 0.541955E+09 |
February | 0.204775E+09 | 52848294.32 | 0.151927E+09 | 82173132.23 | 0.457124E+09 |
March | 0.356407E+09 | 0.153211E+09 | 0.203196E+09 | 0.293043E+09 | 0.326564E+09 |
April | 0.419570E+09 | 0.171726E+09 | 0.247844E+09 | 0.416187E+09 | 0.212526E+09 |
May | 0.511831E+09 | 0.231114E+09 | 0.280717E+09 | 0.574116E+09 | 0.160215E+09 |
June | 0.598424E+09 | 0.281536E+09 | 0.316888E+09 | 0.725667E+09 | 0.126976E+09 |
July | 0.552197E+09 | 0.241761E+09 | 0.310436E+09 | 0.713232E+09 | 95357693.82 |
August | 0.498887E+09 | 0.211580E+09 | 0.287307E+09 | 0.631406E+09 | 0.124533E+09 |
September | 0.380150E+09 | 0.164254E+09 | 0.215896E+09 | 0.426622E+09 | 0.186877E+09 |
October | 0.254548E+09 | 89664914.14 | 0.164883E+09 | 0.228429E+09 | 0.241446E+09 |
November | 0.144786E+09 | 41102820.45 | 0.103683E+09 | 91659883.87 | 0.296341E+09 |
December | 0.130516E+09 | 28279684.90 | 0.102236E+09 | 34131123.52 | 0.517061E+09 |
Annual Sum or Average | 0.419201E+10 | 0.170003E+10 | 0.249198E+10 | 0.425296E+10 | 0.328698E+10 |
Minimum of Months | 0.130516E+09 | 28279684.90 | 0.102236E+09 | 34131123.52 | 95357693.82 |
Maximum of Months | 0.598424E+09 | 0.281536E+09 | 0.316888E+09 | 0.725667E+09 | 0.541955E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139919E+09 | 32952487.93 | 0.106966E+09 | 36299377.56 | 0.541955E+09 |
February | 0.204775E+09 | 52848294.32 | 0.151927E+09 | 82173132.23 | 0.457124E+09 |
March | 0.356407E+09 | 0.153211E+09 | 0.203196E+09 | 0.293043E+09 | 0.326564E+09 |
April | 0.419570E+09 | 0.171726E+09 | 0.247844E+09 | 0.416187E+09 | 0.212526E+09 |
May | 0.511831E+09 | 0.231114E+09 | 0.280717E+09 | 0.574116E+09 | 0.160215E+09 |
June | 0.598424E+09 | 0.281536E+09 | 0.316888E+09 | 0.725667E+09 | 0.126976E+09 |
July | 0.552197E+09 | 0.241761E+09 | 0.310436E+09 | 0.713232E+09 | 95357693.82 |
August | 0.498887E+09 | 0.211580E+09 | 0.287307E+09 | 0.631406E+09 | 0.124533E+09 |
September | 0.380150E+09 | 0.164254E+09 | 0.215896E+09 | 0.426622E+09 | 0.186877E+09 |
October | 0.254548E+09 | 89664914.14 | 0.164883E+09 | 0.228429E+09 | 0.241446E+09 |
November | 0.144786E+09 | 41102820.45 | 0.103683E+09 | 91659883.87 | 0.296341E+09 |
December | 0.130516E+09 | 28279684.90 | 0.102236E+09 | 34131123.52 | 0.517061E+09 |
Annual Sum or Average | 0.419201E+10 | 0.170003E+10 | 0.249198E+10 | 0.425296E+10 | 0.328698E+10 |
Minimum of Months | 0.130516E+09 | 28279684.90 | 0.102236E+09 | 34131123.52 | 95357693.82 |
Maximum of Months | 0.598424E+09 | 0.281536E+09 | 0.316888E+09 | 0.725667E+09 | 0.541955E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51883723.12 | 0.00 | 51883723.12 | 441068.99 | 0.337818E+09 |
February | 71401207.49 | 0.00 | 71401207.49 | 2890729.18 | 0.284930E+09 |
March | 95882380.03 | 3395.69 | 95878984.34 | 33279507.83 | 0.208506E+09 |
April | 0.118292E+09 | 570344.86 | 0.117722E+09 | 71265669.54 | 0.126810E+09 |
May | 0.141998E+09 | 6114251.01 | 0.135883E+09 | 0.116331E+09 | 88571336.03 |
June | 0.165215E+09 | 14048294.05 | 0.151167E+09 | 0.167987E+09 | 68634665.86 |
July | 0.159000E+09 | 10816116.12 | 0.148184E+09 | 0.188015E+09 | 51258573.55 |
August | 0.137658E+09 | 2657383.74 | 0.135001E+09 | 0.151377E+09 | 70203822.91 |
September | 0.100967E+09 | 44682.67 | 0.100922E+09 | 82199873.04 | 0.111367E+09 |
October | 77956163.66 | 0.00 | 77956163.66 | 39021667.13 | 0.145880E+09 |
November | 50694748.92 | 0.00 | 50694748.92 | 12803204.60 | 0.178763E+09 |
December | 48561592.26 | 0.00 | 48561592.26 | 658867.65 | 0.318251E+09 |
Annual Sum or Average | 0.121951E+10 | 34254468.14 | 0.118526E+10 | 0.866271E+09 | 0.199099E+10 |
Minimum of Months | 48561592.26 | 0.00 | 48561592.26 | 441068.99 | 51258573.55 |
Maximum of Months | 0.165215E+09 | 14048294.05 | 0.151167E+09 | 0.188015E+09 | 0.337818E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51881948.64 | 0.00 | 51881948.64 | 440951.10 | 0.337819E+09 |
February | 71398776.49 | 0.00 | 71398776.49 | 2890021.86 | 0.284931E+09 |
March | 95879392.80 | 3395.53 | 95875997.27 | 33277234.35 | 0.208507E+09 |
April | 0.118289E+09 | 570318.12 | 0.117718E+09 | 71261965.85 | 0.126810E+09 |
May | 0.141994E+09 | 6113964.42 | 0.135880E+09 | 0.116326E+09 | 88571037.17 |
June | 0.165210E+09 | 14047635.58 | 0.151163E+09 | 0.167981E+09 | 68634202.17 |
July | 0.158995E+09 | 10815609.16 | 0.148180E+09 | 0.188009E+09 | 51258034.30 |
August | 0.137654E+09 | 2657259.19 | 0.134996E+09 | 0.151372E+09 | 70203360.54 |
September | 0.100964E+09 | 44680.58 | 0.100919E+09 | 82196574.71 | 0.111366E+09 |
October | 77953629.82 | 0.00 | 77953629.82 | 39019322.28 | 0.145879E+09 |
November | 50693011.42 | 0.00 | 50693011.42 | 12802242.69 | 0.178763E+09 |
December | 48559892.96 | 0.00 | 48559892.96 | 658752.36 | 0.318252E+09 |
Annual Sum or Average | 0.121947E+10 | 34252862.59 | 0.118522E+10 | 0.866235E+09 | 0.199099E+10 |
Minimum of Months | 48559892.96 | 0.00 | 48559892.96 | 440951.10 | 51258034.30 |
Maximum of Months | 0.165210E+09 | 14047635.58 | 0.151163E+09 | 0.188009E+09 | 0.337819E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66285379.86 | 20019417.51 | 46265962.35 | 24693382.33 | 0.282530E+09 |
February | 94528743.40 | 27803501.98 | 66725241.42 | 59962625.63 | 0.244604E+09 |
March | 0.162771E+09 | 84329378.75 | 78441227.15 | 0.175781E+09 | 0.183506E+09 |
April | 0.207218E+09 | 0.110046E+09 | 97171581.20 | 0.262724E+09 | 0.118695E+09 |
May | 0.274270E+09 | 0.168858E+09 | 0.105412E+09 | 0.370391E+09 | 98596910.54 |
June | 0.307127E+09 | 0.192423E+09 | 0.114704E+09 | 0.429908E+09 | 89377103.72 |
July | 0.295155E+09 | 0.179373E+09 | 0.115782E+09 | 0.431200E+09 | 77135503.67 |
August | 0.250987E+09 | 0.139411E+09 | 0.111576E+09 | 0.358347E+09 | 93276871.14 |
September | 0.179732E+09 | 97411211.62 | 82320752.00 | 0.235429E+09 | 0.119997E+09 |
October | 0.116147E+09 | 50155672.20 | 65991008.58 | 0.133755E+09 | 0.130661E+09 |
November | 64857582.95 | 20053225.67 | 44804357.28 | 55265225.48 | 0.154384E+09 |
December | 58263907.19 | 12703922.11 | 45559985.08 | 19465042.67 | 0.266879E+09 |
Annual Sum or Average | 0.207734E+10 | 0.110259E+10 | 0.974754E+09 | 0.255692E+10 | 0.185964E+10 |
Minimum of Months | 58263907.19 | 12703922.11 | 44804357.28 | 19465042.67 | 77135503.67 |
Maximum of Months | 0.307127E+09 | 0.192423E+09 | 0.115782E+09 | 0.431200E+09 | 0.282530E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66285379.86 | 20019417.51 | 46265962.35 | 24693382.33 | 0.282530E+09 |
February | 94528743.40 | 27803501.98 | 66725241.42 | 59962625.63 | 0.244604E+09 |
March | 0.162771E+09 | 84329378.75 | 78441227.15 | 0.175781E+09 | 0.183506E+09 |
April | 0.207218E+09 | 0.110046E+09 | 97171581.20 | 0.262724E+09 | 0.118695E+09 |
May | 0.274270E+09 | 0.168858E+09 | 0.105412E+09 | 0.370391E+09 | 98596910.54 |
June | 0.307127E+09 | 0.192423E+09 | 0.114704E+09 | 0.429908E+09 | 89377103.72 |
July | 0.295155E+09 | 0.179373E+09 | 0.115782E+09 | 0.431200E+09 | 77135503.67 |
August | 0.250987E+09 | 0.139411E+09 | 0.111576E+09 | 0.358347E+09 | 93276871.14 |
September | 0.179732E+09 | 97411211.62 | 82320752.00 | 0.235429E+09 | 0.119997E+09 |
October | 0.116147E+09 | 50155672.20 | 65991008.58 | 0.133755E+09 | 0.130661E+09 |
November | 64857582.95 | 20053225.67 | 44804357.28 | 55265225.48 | 0.154384E+09 |
December | 58263907.19 | 12703922.11 | 45559985.08 | 19465042.67 | 0.266879E+09 |
Annual Sum or Average | 0.207734E+10 | 0.110259E+10 | 0.974754E+09 | 0.255692E+10 | 0.185964E+10 |
Minimum of Months | 58263907.19 | 12703922.11 | 44804357.28 | 19465042.67 | 77135503.67 |
Maximum of Months | 0.307127E+09 | 0.192423E+09 | 0.115782E+09 | 0.431200E+09 | 0.282530E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66285379.86 | 20019417.51 | 46265962.35 | 24693382.33 | 0.282530E+09 |
February | 94528743.40 | 27803501.98 | 66725241.42 | 59962625.63 | 0.244604E+09 |
March | 0.162771E+09 | 84329378.75 | 78441227.15 | 0.175781E+09 | 0.183506E+09 |
April | 0.207218E+09 | 0.110046E+09 | 97171581.20 | 0.262724E+09 | 0.118695E+09 |
May | 0.274270E+09 | 0.168858E+09 | 0.105412E+09 | 0.370391E+09 | 98596910.54 |
June | 0.307127E+09 | 0.192423E+09 | 0.114704E+09 | 0.429908E+09 | 89377103.72 |
July | 0.295155E+09 | 0.179373E+09 | 0.115782E+09 | 0.431200E+09 | 77135503.67 |
August | 0.250987E+09 | 0.139411E+09 | 0.111576E+09 | 0.358347E+09 | 93276871.14 |
September | 0.179732E+09 | 97411211.62 | 82320752.00 | 0.235429E+09 | 0.119997E+09 |
October | 0.116147E+09 | 50155672.20 | 65991008.58 | 0.133755E+09 | 0.130661E+09 |
November | 64857582.95 | 20053225.67 | 44804357.28 | 55265225.48 | 0.154384E+09 |
December | 58263907.19 | 12703922.11 | 45559985.08 | 19465042.67 | 0.266879E+09 |
Annual Sum or Average | 0.207734E+10 | 0.110259E+10 | 0.974754E+09 | 0.255692E+10 | 0.185964E+10 |
Minimum of Months | 58263907.19 | 12703922.11 | 44804357.28 | 19465042.67 | 77135503.67 |
Maximum of Months | 0.307127E+09 | 0.192423E+09 | 0.115782E+09 | 0.431200E+09 | 0.282530E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66285379.86 | 20019417.51 | 46265962.35 | 24693382.33 | 0.282530E+09 |
February | 94528743.40 | 27803501.98 | 66725241.42 | 59962625.63 | 0.244604E+09 |
March | 0.162771E+09 | 84329378.75 | 78441227.15 | 0.175781E+09 | 0.183506E+09 |
April | 0.207218E+09 | 0.110046E+09 | 97171581.20 | 0.262724E+09 | 0.118695E+09 |
May | 0.274270E+09 | 0.168858E+09 | 0.105412E+09 | 0.370391E+09 | 98596910.54 |
June | 0.307127E+09 | 0.192423E+09 | 0.114704E+09 | 0.429908E+09 | 89377103.72 |
July | 0.295155E+09 | 0.179373E+09 | 0.115782E+09 | 0.431200E+09 | 77135503.67 |
August | 0.250987E+09 | 0.139411E+09 | 0.111576E+09 | 0.358347E+09 | 93276871.14 |
September | 0.179732E+09 | 97411211.62 | 82320752.00 | 0.235429E+09 | 0.119997E+09 |
October | 0.116147E+09 | 50155672.20 | 65991008.58 | 0.133755E+09 | 0.130661E+09 |
November | 64857582.95 | 20053225.67 | 44804357.28 | 55265225.48 | 0.154384E+09 |
December | 58263907.19 | 12703922.11 | 45559985.08 | 19465042.67 | 0.266879E+09 |
Annual Sum or Average | 0.207734E+10 | 0.110259E+10 | 0.974754E+09 | 0.255692E+10 | 0.185964E+10 |
Minimum of Months | 58263907.19 | 12703922.11 | 44804357.28 | 19465042.67 | 77135503.67 |
Maximum of Months | 0.307127E+09 | 0.192423E+09 | 0.115782E+09 | 0.431200E+09 | 0.282530E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66285379.86 | 20019417.51 | 46265962.35 | 24693382.33 | 0.282530E+09 |
February | 94528743.40 | 27803501.98 | 66725241.42 | 59962625.63 | 0.244604E+09 |
March | 0.162771E+09 | 84329378.75 | 78441227.15 | 0.175781E+09 | 0.183506E+09 |
April | 0.207218E+09 | 0.110046E+09 | 97171581.20 | 0.262724E+09 | 0.118695E+09 |
May | 0.274270E+09 | 0.168858E+09 | 0.105412E+09 | 0.370391E+09 | 98596910.54 |
June | 0.307127E+09 | 0.192423E+09 | 0.114704E+09 | 0.429908E+09 | 89377103.72 |
July | 0.295155E+09 | 0.179373E+09 | 0.115782E+09 | 0.431200E+09 | 77135503.67 |
August | 0.250987E+09 | 0.139411E+09 | 0.111576E+09 | 0.358347E+09 | 93276871.14 |
September | 0.179732E+09 | 97411211.62 | 82320752.00 | 0.235429E+09 | 0.119997E+09 |
October | 0.116147E+09 | 50155672.20 | 65991008.58 | 0.133755E+09 | 0.130661E+09 |
November | 64857582.95 | 20053225.67 | 44804357.28 | 55265225.48 | 0.154384E+09 |
December | 58263907.19 | 12703922.11 | 45559985.08 | 19465042.67 | 0.266879E+09 |
Annual Sum or Average | 0.207734E+10 | 0.110259E+10 | 0.974754E+09 | 0.255692E+10 | 0.185964E+10 |
Minimum of Months | 58263907.19 | 12703922.11 | 44804357.28 | 19465042.67 | 77135503.67 |
Maximum of Months | 0.307127E+09 | 0.192423E+09 | 0.115782E+09 | 0.431200E+09 | 0.282530E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66285379.86 | 20019417.51 | 46265962.35 | 24693382.33 | 0.282530E+09 |
February | 94528743.40 | 27803501.98 | 66725241.42 | 59962625.63 | 0.244604E+09 |
March | 0.162771E+09 | 84329378.75 | 78441227.15 | 0.175781E+09 | 0.183506E+09 |
April | 0.207218E+09 | 0.110046E+09 | 97171581.20 | 0.262724E+09 | 0.118695E+09 |
May | 0.274270E+09 | 0.168858E+09 | 0.105412E+09 | 0.370391E+09 | 98596910.54 |
June | 0.307127E+09 | 0.192423E+09 | 0.114704E+09 | 0.429908E+09 | 89377103.72 |
July | 0.295155E+09 | 0.179373E+09 | 0.115782E+09 | 0.431200E+09 | 77135503.67 |
August | 0.250987E+09 | 0.139411E+09 | 0.111576E+09 | 0.358347E+09 | 93276871.14 |
September | 0.179732E+09 | 97411211.62 | 82320752.00 | 0.235429E+09 | 0.119997E+09 |
October | 0.116147E+09 | 50155672.20 | 65991008.58 | 0.133755E+09 | 0.130661E+09 |
November | 64857582.95 | 20053225.67 | 44804357.28 | 55265225.48 | 0.154384E+09 |
December | 58263907.19 | 12703922.11 | 45559985.08 | 19465042.67 | 0.266879E+09 |
Annual Sum or Average | 0.207734E+10 | 0.110259E+10 | 0.974754E+09 | 0.255692E+10 | 0.185964E+10 |
Minimum of Months | 58263907.19 | 12703922.11 | 44804357.28 | 19465042.67 | 77135503.67 |
Maximum of Months | 0.307127E+09 | 0.192423E+09 | 0.115782E+09 | 0.431200E+09 | 0.282530E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66285379.86 | 20019417.51 | 46265962.35 | 24693382.33 | 0.282530E+09 |
February | 94528743.40 | 27803501.98 | 66725241.42 | 59962625.63 | 0.244604E+09 |
March | 0.162771E+09 | 84329378.75 | 78441227.15 | 0.175781E+09 | 0.183506E+09 |
April | 0.207218E+09 | 0.110046E+09 | 97171581.20 | 0.262724E+09 | 0.118695E+09 |
May | 0.274270E+09 | 0.168858E+09 | 0.105412E+09 | 0.370391E+09 | 98596910.54 |
June | 0.307127E+09 | 0.192423E+09 | 0.114704E+09 | 0.429908E+09 | 89377103.72 |
July | 0.295155E+09 | 0.179373E+09 | 0.115782E+09 | 0.431200E+09 | 77135503.67 |
August | 0.250987E+09 | 0.139411E+09 | 0.111576E+09 | 0.358347E+09 | 93276871.14 |
September | 0.179732E+09 | 97411211.62 | 82320752.00 | 0.235429E+09 | 0.119997E+09 |
October | 0.116147E+09 | 50155672.20 | 65991008.58 | 0.133755E+09 | 0.130661E+09 |
November | 64857582.95 | 20053225.67 | 44804357.28 | 55265225.48 | 0.154384E+09 |
December | 58263907.19 | 12703922.11 | 45559985.08 | 19465042.67 | 0.266879E+09 |
Annual Sum or Average | 0.207734E+10 | 0.110259E+10 | 0.974754E+09 | 0.255692E+10 | 0.185964E+10 |
Minimum of Months | 58263907.19 | 12703922.11 | 44804357.28 | 19465042.67 | 77135503.67 |
Maximum of Months | 0.307127E+09 | 0.192423E+09 | 0.115782E+09 | 0.431200E+09 | 0.282530E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66285379.86 | 20019417.51 | 46265962.35 | 24693382.33 | 0.282530E+09 |
February | 94528743.40 | 27803501.98 | 66725241.42 | 59962625.63 | 0.244604E+09 |
March | 0.162771E+09 | 84329378.75 | 78441227.15 | 0.175781E+09 | 0.183506E+09 |
April | 0.207218E+09 | 0.110046E+09 | 97171581.20 | 0.262724E+09 | 0.118695E+09 |
May | 0.274270E+09 | 0.168858E+09 | 0.105412E+09 | 0.370391E+09 | 98596910.54 |
June | 0.307127E+09 | 0.192423E+09 | 0.114704E+09 | 0.429908E+09 | 89377103.72 |
July | 0.295155E+09 | 0.179373E+09 | 0.115782E+09 | 0.431200E+09 | 77135503.67 |
August | 0.250987E+09 | 0.139411E+09 | 0.111576E+09 | 0.358347E+09 | 93276871.14 |
September | 0.179732E+09 | 97411211.62 | 82320752.00 | 0.235429E+09 | 0.119997E+09 |
October | 0.116147E+09 | 50155672.20 | 65991008.58 | 0.133755E+09 | 0.130661E+09 |
November | 64857582.95 | 20053225.67 | 44804357.28 | 55265225.48 | 0.154384E+09 |
December | 58263907.19 | 12703922.11 | 45559985.08 | 19465042.67 | 0.266879E+09 |
Annual Sum or Average | 0.207734E+10 | 0.110259E+10 | 0.974754E+09 | 0.255692E+10 | 0.185964E+10 |
Minimum of Months | 58263907.19 | 12703922.11 | 44804357.28 | 19465042.67 | 77135503.67 |
Maximum of Months | 0.307127E+09 | 0.192423E+09 | 0.115782E+09 | 0.431200E+09 | 0.282530E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66285379.86 | 20019417.51 | 46265962.35 | 24693382.33 | 0.282530E+09 |
February | 94528743.40 | 27803501.98 | 66725241.42 | 59962625.63 | 0.244604E+09 |
March | 0.162771E+09 | 84329378.75 | 78441227.15 | 0.175781E+09 | 0.183506E+09 |
April | 0.207218E+09 | 0.110046E+09 | 97171581.20 | 0.262724E+09 | 0.118695E+09 |
May | 0.274270E+09 | 0.168858E+09 | 0.105412E+09 | 0.370391E+09 | 98596910.54 |
June | 0.307127E+09 | 0.192423E+09 | 0.114704E+09 | 0.429908E+09 | 89377103.72 |
July | 0.295155E+09 | 0.179373E+09 | 0.115782E+09 | 0.431200E+09 | 77135503.67 |
August | 0.250987E+09 | 0.139411E+09 | 0.111576E+09 | 0.358347E+09 | 93276871.14 |
September | 0.179732E+09 | 97411211.62 | 82320752.00 | 0.235429E+09 | 0.119997E+09 |
October | 0.116147E+09 | 50155672.20 | 65991008.58 | 0.133755E+09 | 0.130661E+09 |
November | 64857582.95 | 20053225.67 | 44804357.28 | 55265225.48 | 0.154384E+09 |
December | 58263907.19 | 12703922.11 | 45559985.08 | 19465042.67 | 0.266879E+09 |
Annual Sum or Average | 0.207734E+10 | 0.110259E+10 | 0.974754E+09 | 0.255692E+10 | 0.185964E+10 |
Minimum of Months | 58263907.19 | 12703922.11 | 44804357.28 | 19465042.67 | 77135503.67 |
Maximum of Months | 0.307127E+09 | 0.192423E+09 | 0.115782E+09 | 0.431200E+09 | 0.282530E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66285379.86 | 20019417.51 | 46265962.35 | 24693382.33 | 0.282530E+09 |
February | 94528743.40 | 27803501.98 | 66725241.42 | 59962625.63 | 0.244604E+09 |
March | 0.162771E+09 | 84329378.75 | 78441227.15 | 0.175781E+09 | 0.183506E+09 |
April | 0.207218E+09 | 0.110046E+09 | 97171581.20 | 0.262724E+09 | 0.118695E+09 |
May | 0.274270E+09 | 0.168858E+09 | 0.105412E+09 | 0.370391E+09 | 98596910.54 |
June | 0.307127E+09 | 0.192423E+09 | 0.114704E+09 | 0.429908E+09 | 89377103.72 |
July | 0.295155E+09 | 0.179373E+09 | 0.115782E+09 | 0.431200E+09 | 77135503.67 |
August | 0.250987E+09 | 0.139411E+09 | 0.111576E+09 | 0.358347E+09 | 93276871.14 |
September | 0.179732E+09 | 97411211.62 | 82320752.00 | 0.235429E+09 | 0.119997E+09 |
October | 0.116147E+09 | 50155672.20 | 65991008.58 | 0.133755E+09 | 0.130661E+09 |
November | 64857582.95 | 20053225.67 | 44804357.28 | 55265225.48 | 0.154384E+09 |
December | 58263907.19 | 12703922.11 | 45559985.08 | 19465042.67 | 0.266879E+09 |
Annual Sum or Average | 0.207734E+10 | 0.110259E+10 | 0.974754E+09 | 0.255692E+10 | 0.185964E+10 |
Minimum of Months | 58263907.19 | 12703922.11 | 44804357.28 | 19465042.67 | 77135503.67 |
Maximum of Months | 0.307127E+09 | 0.192423E+09 | 0.115782E+09 | 0.431200E+09 | 0.282530E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66285379.86 | 20019417.51 | 46265962.35 | 24693382.33 | 0.282530E+09 |
February | 94528743.40 | 27803501.98 | 66725241.42 | 59962625.63 | 0.244604E+09 |
March | 0.162771E+09 | 84329378.75 | 78441227.15 | 0.175781E+09 | 0.183506E+09 |
April | 0.207218E+09 | 0.110046E+09 | 97171581.20 | 0.262724E+09 | 0.118695E+09 |
May | 0.274270E+09 | 0.168858E+09 | 0.105412E+09 | 0.370391E+09 | 98596910.54 |
June | 0.307127E+09 | 0.192423E+09 | 0.114704E+09 | 0.429908E+09 | 89377103.72 |
July | 0.295155E+09 | 0.179373E+09 | 0.115782E+09 | 0.431200E+09 | 77135503.67 |
August | 0.250987E+09 | 0.139411E+09 | 0.111576E+09 | 0.358347E+09 | 93276871.14 |
September | 0.179732E+09 | 97411211.62 | 82320752.00 | 0.235429E+09 | 0.119997E+09 |
October | 0.116147E+09 | 50155672.20 | 65991008.58 | 0.133755E+09 | 0.130661E+09 |
November | 64857582.95 | 20053225.67 | 44804357.28 | 55265225.48 | 0.154384E+09 |
December | 58263907.19 | 12703922.11 | 45559985.08 | 19465042.67 | 0.266879E+09 |
Annual Sum or Average | 0.207734E+10 | 0.110259E+10 | 0.974754E+09 | 0.255692E+10 | 0.185964E+10 |
Minimum of Months | 58263907.19 | 12703922.11 | 44804357.28 | 19465042.67 | 77135503.67 |
Maximum of Months | 0.307127E+09 | 0.192423E+09 | 0.115782E+09 | 0.431200E+09 | 0.282530E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66285379.86 | 20019417.51 | 46265962.35 | 24693382.33 | 0.282530E+09 |
February | 94528743.40 | 27803501.98 | 66725241.42 | 59962625.63 | 0.244604E+09 |
March | 0.162771E+09 | 84329378.75 | 78441227.15 | 0.175781E+09 | 0.183506E+09 |
April | 0.207218E+09 | 0.110046E+09 | 97171581.20 | 0.262724E+09 | 0.118695E+09 |
May | 0.274270E+09 | 0.168858E+09 | 0.105412E+09 | 0.370391E+09 | 98596910.54 |
June | 0.307127E+09 | 0.192423E+09 | 0.114704E+09 | 0.429908E+09 | 89377103.72 |
July | 0.295155E+09 | 0.179373E+09 | 0.115782E+09 | 0.431200E+09 | 77135503.67 |
August | 0.250987E+09 | 0.139411E+09 | 0.111576E+09 | 0.358347E+09 | 93276871.14 |
September | 0.179732E+09 | 97411211.62 | 82320752.00 | 0.235429E+09 | 0.119997E+09 |
October | 0.116147E+09 | 50155672.20 | 65991008.58 | 0.133755E+09 | 0.130661E+09 |
November | 64857582.95 | 20053225.67 | 44804357.28 | 55265225.48 | 0.154384E+09 |
December | 58263907.19 | 12703922.11 | 45559985.08 | 19465042.67 | 0.266879E+09 |
Annual Sum or Average | 0.207734E+10 | 0.110259E+10 | 0.974754E+09 | 0.255692E+10 | 0.185964E+10 |
Minimum of Months | 58263907.19 | 12703922.11 | 44804357.28 | 19465042.67 | 77135503.67 |
Maximum of Months | 0.307127E+09 | 0.192423E+09 | 0.115782E+09 | 0.431200E+09 | 0.282530E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66285379.86 | 20019417.51 | 46265962.35 | 24693382.33 | 0.282530E+09 |
February | 94528743.40 | 27803501.98 | 66725241.42 | 59962625.63 | 0.244604E+09 |
March | 0.162771E+09 | 84329378.75 | 78441227.15 | 0.175781E+09 | 0.183506E+09 |
April | 0.207218E+09 | 0.110046E+09 | 97171581.20 | 0.262724E+09 | 0.118695E+09 |
May | 0.274270E+09 | 0.168858E+09 | 0.105412E+09 | 0.370391E+09 | 98596910.54 |
June | 0.307127E+09 | 0.192423E+09 | 0.114704E+09 | 0.429908E+09 | 89377103.72 |
July | 0.295155E+09 | 0.179373E+09 | 0.115782E+09 | 0.431200E+09 | 77135503.67 |
August | 0.250987E+09 | 0.139411E+09 | 0.111576E+09 | 0.358347E+09 | 93276871.14 |
September | 0.179732E+09 | 97411211.62 | 82320752.00 | 0.235429E+09 | 0.119997E+09 |
October | 0.116147E+09 | 50155672.20 | 65991008.58 | 0.133755E+09 | 0.130661E+09 |
November | 64857582.95 | 20053225.67 | 44804357.28 | 55265225.48 | 0.154384E+09 |
December | 58263907.19 | 12703922.11 | 45559985.08 | 19465042.67 | 0.266879E+09 |
Annual Sum or Average | 0.207734E+10 | 0.110259E+10 | 0.974754E+09 | 0.255692E+10 | 0.185964E+10 |
Minimum of Months | 58263907.19 | 12703922.11 | 44804357.28 | 19465042.67 | 77135503.67 |
Maximum of Months | 0.307127E+09 | 0.192423E+09 | 0.115782E+09 | 0.431200E+09 | 0.282530E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66285379.86 | 20019417.51 | 46265962.35 | 24693382.33 | 0.282530E+09 |
February | 94528743.40 | 27803501.98 | 66725241.42 | 59962625.63 | 0.244604E+09 |
March | 0.162771E+09 | 84329378.75 | 78441227.15 | 0.175781E+09 | 0.183506E+09 |
April | 0.207218E+09 | 0.110046E+09 | 97171581.20 | 0.262724E+09 | 0.118695E+09 |
May | 0.274270E+09 | 0.168858E+09 | 0.105412E+09 | 0.370391E+09 | 98596910.54 |
June | 0.307127E+09 | 0.192423E+09 | 0.114704E+09 | 0.429908E+09 | 89377103.72 |
July | 0.295155E+09 | 0.179373E+09 | 0.115782E+09 | 0.431200E+09 | 77135503.67 |
August | 0.250987E+09 | 0.139411E+09 | 0.111576E+09 | 0.358347E+09 | 93276871.14 |
September | 0.179732E+09 | 97411211.62 | 82320752.00 | 0.235429E+09 | 0.119997E+09 |
October | 0.116147E+09 | 50155672.20 | 65991008.58 | 0.133755E+09 | 0.130661E+09 |
November | 64857582.95 | 20053225.67 | 44804357.28 | 55265225.48 | 0.154384E+09 |
December | 58263907.19 | 12703922.11 | 45559985.08 | 19465042.67 | 0.266879E+09 |
Annual Sum or Average | 0.207734E+10 | 0.110259E+10 | 0.974754E+09 | 0.255692E+10 | 0.185964E+10 |
Minimum of Months | 58263907.19 | 12703922.11 | 44804357.28 | 19465042.67 | 77135503.67 |
Maximum of Months | 0.307127E+09 | 0.192423E+09 | 0.115782E+09 | 0.431200E+09 | 0.282530E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38614120.99 | 0.320085E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82300530.75 | 0.282069E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.222445E+09 | 0.198175E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.318579E+09 | 0.119538E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.429318E+09 | 0.115470E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.485549E+09 | 0.115593E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.466391E+09 | 0.119861E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.387994E+09 | 0.141404E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.268362E+09 | 0.154581E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.162673E+09 | 0.147285E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 80306050.49 | 0.143467E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31848288.03 | 0.291721E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.297438E+10 | 0.214925E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31848288.03 | 0.115470E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.485549E+09 | 0.320085E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 19.54 | 649.05 | 143.22 | 24.61 | 118.61 | 0.00 | 0.00 |
February | 60.22 | 603.37 | 228.32 | 43.69 | 184.63 | 0.00 | 0.00 |
March | 232.16 | 388.03 | 337.73 | 114.41 | 223.32 | 0.00 | 0.00 |
April | 373.37 | 259.08 | 415.02 | 132.94 | 282.07 | 0.00 | 0.00 |
May | 514.04 | 184.25 | 488.22 | 177.14 | 311.08 | 0.00 | 0.00 |
June | 685.82 | 147.21 | 589.23 | 228.07 | 361.15 | 0.00 | 0.00 |
July | 670.05 | 106.56 | 531.06 | 188.60 | 342.46 | 0.00 | 0.00 |
August | 583.69 | 144.59 | 475.32 | 159.97 | 315.34 | 0.00 | 0.00 |
September | 390.82 | 228.34 | 371.23 | 126.77 | 244.46 | 0.00 | 0.00 |
October | 197.03 | 286.55 | 248.28 | 66.95 | 181.33 | 0.00 | 0.00 |
November | 76.87 | 362.86 | 150.83 | 31.72 | 119.12 | 0.00 | 0.00 |
December | 18.96 | 616.72 | 133.72 | 21.12 | 112.60 | 0.00 | 0.00 |
Annual Sum or Average | 319.98 | 330.05 | 343.20 | 109.99 | 233.21 | 0.00 | 0.00 |
Minimum of Months | 18.96 | 106.56 | 133.72 | 21.12 | 112.60 | 0.00 | 0.00 |
Maximum of Months | 685.82 | 649.05 | 589.23 | 228.07 | 361.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 129.07 | 1476.78 | 346.47 | 104.64 | 241.83 | 0.00 | 0.00 |
February | 347.01 | 1415.53 | 547.04 | 160.90 | 386.14 | 0.00 | 0.00 |
March | 918.81 | 959.19 | 850.80 | 440.79 | 410.01 | 0.00 | 0.00 |
April | 1419.03 | 641.10 | 1119.23 | 594.39 | 524.85 | 0.00 | 0.00 |
May | 1936.03 | 515.37 | 1433.61 | 882.62 | 550.99 | 0.00 | 0.00 |
June | 2322.03 | 482.75 | 1658.86 | 1039.32 | 619.54 | 0.00 | 0.00 |
July | 2253.88 | 403.19 | 1542.77 | 937.58 | 605.19 | 0.00 | 0.00 |
August | 1873.08 | 487.56 | 1311.91 | 728.70 | 583.21 | 0.00 | 0.00 |
September | 1271.61 | 648.13 | 970.77 | 526.14 | 444.63 | 0.00 | 0.00 |
October | 699.14 | 682.96 | 607.10 | 262.16 | 344.94 | 0.00 | 0.00 |
November | 298.50 | 833.86 | 350.31 | 108.31 | 242.00 | 0.00 | 0.00 |
December | 101.74 | 1394.98 | 304.55 | 66.40 | 238.14 | 0.00 | 0.00 |
Annual Sum or Average | 1135.11 | 825.56 | 922.21 | 489.48 | 432.73 | 0.00 | 0.00 |
Minimum of Months | 101.74 | 403.19 | 304.55 | 66.40 | 238.14 | 0.00 | 0.00 |
Maximum of Months | 2322.03 | 1476.78 | 1658.86 | 1039.32 | 619.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2453.46 | 32133.03 | 964.43 | 291.27 | 673.15 | 0.00 | 0.00 |
February | 5618.49 | 34021.03 | 1522.71 | 447.87 | 1074.84 | 0.00 | 0.00 |
March | 12135.68 | 17732.05 | 2368.25 | 1226.96 | 1141.29 | 0.00 | 0.00 |
April | 16340.61 | 7526.74 | 3115.44 | 1654.50 | 1460.93 | 0.00 | 0.00 |
May | 20866.07 | 4532.97 | 3990.51 | 2456.81 | 1533.70 | 0.00 | 0.00 |
June | 23113.07 | 6078.94 | 4617.52 | 2892.99 | 1724.53 | 0.00 | 0.00 |
July | 24715.76 | 8373.36 | 4294.38 | 2609.80 | 1684.58 | 0.00 | 0.00 |
August | 18824.55 | 9249.85 | 3651.76 | 2028.38 | 1623.38 | 0.00 | 0.00 |
September | 11888.25 | 6992.19 | 2702.19 | 1464.54 | 1237.66 | 0.00 | 0.00 |
October | 7683.34 | 6976.05 | 1689.89 | 729.74 | 960.14 | 0.00 | 0.00 |
November | 4051.38 | 10271.49 | 975.11 | 301.49 | 673.61 | 0.00 | 0.00 |
December | 1981.32 | 29013.87 | 847.72 | 184.84 | 662.88 | 0.00 | 0.00 |
Annual Sum or Average | 12513.93 | 14320.59 | 2567.01 | 1362.49 | 1204.52 | 0.00 | 0.00 |
Minimum of Months | 1981.32 | 4532.97 | 847.72 | 184.84 | 662.88 | 0.00 | 0.00 |
Maximum of Months | 24715.76 | 34021.03 | 4617.52 | 2892.99 | 1724.53 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 52347529.19 | 0.173841E+10 | 0.383603E+09 | 65904975.85 | 0.317698E+09 | 0.00 | 0.00 |
February | 0.145696E+09 | 0.145968E+10 | 0.552350E+09 | 0.105697E+09 | 0.446653E+09 | 0.00 | 0.00 |
March | 0.621813E+09 | 0.103931E+10 | 0.904575E+09 | 0.306429E+09 | 0.598146E+09 | 0.00 | 0.00 |
April | 0.967768E+09 | 0.671538E+09 | 0.107572E+10 | 0.344592E+09 | 0.731128E+09 | 0.00 | 0.00 |
May | 0.137681E+10 | 0.493490E+09 | 0.130765E+10 | 0.474456E+09 | 0.833198E+09 | 0.00 | 0.00 |
June | 0.177765E+10 | 0.381565E+09 | 0.152727E+10 | 0.591168E+09 | 0.936105E+09 | 0.00 | 0.00 |
July | 0.179465E+10 | 0.285399E+09 | 0.142239E+10 | 0.505155E+09 | 0.917235E+09 | 0.00 | 0.00 |
August | 0.156335E+10 | 0.387265E+09 | 0.127309E+10 | 0.428475E+09 | 0.844611E+09 | 0.00 | 0.00 |
September | 0.101300E+10 | 0.591850E+09 | 0.962232E+09 | 0.328598E+09 | 0.633634E+09 | 0.00 | 0.00 |
October | 0.527733E+09 | 0.767484E+09 | 0.665005E+09 | 0.179330E+09 | 0.485675E+09 | 0.00 | 0.00 |
November | 0.199237E+09 | 0.940521E+09 | 0.390959E+09 | 82205640.90 | 0.308753E+09 | 0.00 | 0.00 |
December | 50787558.99 | 0.165183E+10 | 0.358153E+09 | 56559369.81 | 0.301594E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100908E+11 | 0.104083E+11 | 0.108230E+11 | 0.346857E+10 | 0.735443E+10 | 0.00 | 0.00 |
Minimum of Months | 50787558.99 | 0.285399E+09 | 0.358153E+09 | 56559369.81 | 0.301594E+09 | 0.00 | 0.00 |
Maximum of Months | 0.179465E+10 | 0.173841E+10 | 0.152727E+10 | 0.591168E+09 | 0.936105E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.345707E+09 | 0.395542E+10 | 0.927995E+09 | 0.280272E+09 | 0.647723E+09 | 0.00 | 0.00 |
February | 0.839477E+09 | 0.342446E+10 | 0.132340E+10 | 0.389249E+09 | 0.934153E+09 | 0.00 | 0.00 |
March | 0.246093E+10 | 0.256909E+10 | 0.227879E+10 | 0.118061E+10 | 0.109818E+10 | 0.00 | 0.00 |
April | 0.367814E+10 | 0.166172E+10 | 0.290105E+10 | 0.154065E+10 | 0.136040E+10 | 0.00 | 0.00 |
May | 0.518547E+10 | 0.138036E+10 | 0.383978E+10 | 0.236401E+10 | 0.147576E+10 | 0.00 | 0.00 |
June | 0.601871E+10 | 0.125128E+10 | 0.429977E+10 | 0.269392E+10 | 0.160586E+10 | 0.00 | 0.00 |
July | 0.603680E+10 | 0.107990E+10 | 0.413217E+10 | 0.251122E+10 | 0.162095E+10 | 0.00 | 0.00 |
August | 0.501685E+10 | 0.130588E+10 | 0.351382E+10 | 0.195176E+10 | 0.156206E+10 | 0.00 | 0.00 |
September | 0.329600E+10 | 0.167995E+10 | 0.251625E+10 | 0.136376E+10 | 0.115249E+10 | 0.00 | 0.00 |
October | 0.187257E+10 | 0.182925E+10 | 0.162605E+10 | 0.702179E+09 | 0.923874E+09 | 0.00 | 0.00 |
November | 0.773713E+09 | 0.216138E+10 | 0.908006E+09 | 0.280745E+09 | 0.627261E+09 | 0.00 | 0.00 |
December | 0.272511E+09 | 0.373630E+10 | 0.815695E+09 | 0.177855E+09 | 0.637840E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.357969E+11 | 0.260350E+11 | 0.290828E+11 | 0.154362E+11 | 0.136466E+11 | 0.00 | 0.00 |
Minimum of Months | 0.272511E+09 | 0.107990E+10 | 0.815695E+09 | 0.177855E+09 | 0.627261E+09 | 0.00 | 0.00 |
Maximum of Months | 0.603680E+10 | 0.395542E+10 | 0.429977E+10 | 0.269392E+10 | 0.162095E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.657135E+10 | 0.860651E+11 | 0.258312E+10 | 0.780149E+09 | 0.180297E+10 | 0.00 | 0.00 |
February | 0.135923E+11 | 0.823037E+11 | 0.368375E+10 | 0.108349E+10 | 0.260026E+10 | 0.00 | 0.00 |
March | 0.325042E+11 | 0.474935E+11 | 0.634311E+10 | 0.328628E+10 | 0.305683E+10 | 0.00 | 0.00 |
April | 0.423549E+11 | 0.195093E+11 | 0.807521E+10 | 0.428847E+10 | 0.378674E+10 | 0.00 | 0.00 |
May | 0.558877E+11 | 0.121411E+11 | 0.106882E+11 | 0.658033E+10 | 0.410786E+10 | 0.00 | 0.00 |
June | 0.599091E+11 | 0.157566E+11 | 0.119686E+11 | 0.749864E+10 | 0.446998E+10 | 0.00 | 0.00 |
July | 0.661987E+11 | 0.224272E+11 | 0.115021E+11 | 0.699008E+10 | 0.451199E+10 | 0.00 | 0.00 |
August | 0.504197E+11 | 0.247748E+11 | 0.978087E+10 | 0.543281E+10 | 0.434806E+10 | 0.00 | 0.00 |
September | 0.308144E+11 | 0.181238E+11 | 0.700409E+10 | 0.379608E+10 | 0.320801E+10 | 0.00 | 0.00 |
October | 0.205791E+11 | 0.186846E+11 | 0.452619E+10 | 0.195455E+10 | 0.257165E+10 | 0.00 | 0.00 |
November | 0.105012E+11 | 0.266237E+11 | 0.252748E+10 | 0.781467E+09 | 0.174601E+10 | 0.00 | 0.00 |
December | 0.530677E+10 | 0.777107E+11 | 0.227052E+10 | 0.495067E+09 | 0.177546E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.394639E+12 | 0.451614E+12 | 0.809532E+11 | 0.429674E+11 | 0.379858E+11 | 0.00 | 0.00 |
Minimum of Months | 0.530677E+10 | 0.121411E+11 | 0.227052E+10 | 0.495067E+09 | 0.174601E+10 | 0.00 | 0.00 |
Maximum of Months | 0.661987E+11 | 0.860651E+11 | 0.119686E+11 | 0.749864E+10 | 0.451199E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.101106E+10 | -922989168.5 | 0.00 | 0.00 | 744.00 | 0.00 | -88066353.0 | 58.99 | 0.00 | 0.00 |
February | 0.939597E+09 | -860112832.3 | 0.00 | 0.00 | 672.00 | 0.00 | -79483876.0 | 58.99 | 0.00 | 0.00 |
March | 0.107815E+10 | -991502041.5 | 0.00 | 0.00 | 744.00 | 0.00 | -86650367.9 | 58.99 | 0.00 | 0.00 |
April | 0.967584E+09 | -884844239.1 | 0.00 | 0.00 | 720.00 | 0.00 | -82739265.6 | 58.99 | 0.00 | 0.00 |
May | 0.947709E+09 | -868057589.2 | 0.00 | 0.00 | 744.00 | 0.00 | -79651642.4 | 58.99 | 0.00 | 0.00 |
June | 0.883893E+09 | -811349998.1 | 0.00 | 0.00 | 720.00 | 0.00 | -72542582.8 | 58.99 | 0.00 | 0.00 |
July | 0.819911E+09 | -745943247.5 | 0.00 | 0.00 | 744.00 | 0.00 | -73968227.0 | 58.99 | 0.00 | 0.00 |
August | 0.860455E+09 | -786007114.6 | 0.00 | 0.00 | 744.00 | 0.00 | -74448269.6 | 58.99 | 0.00 | 0.00 |
September | 0.816886E+09 | -744043418.0 | 0.00 | 0.00 | 720.00 | 0.00 | -72842681.4 | 58.99 | 0.00 | 0.00 |
October | 0.866021E+09 | -783072187.4 | 0.00 | 0.00 | 744.00 | 0.00 | -82948689.8 | 58.99 | 0.00 | 0.00 |
November | 0.884509E+09 | -800535898.6 | 0.00 | 0.00 | 720.00 | 0.00 | -83973058.1 | 58.99 | 0.00 | 0.00 |
December | 0.972063E+09 | -884028349.5 | 0.00 | 0.00 | 744.00 | 0.00 | -88034510.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.110478E+11 | -0.100825E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -965349524.0 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.816886E+09 | -991502041.5 | 0.00 | 0.00 | 672.00 | 0.00 | -88066353.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.107815E+10 | -744043418.0 | 0.00 | 0.00 | 744.00 | 0.00 | -72542582.8 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.87 | 0.50 | 27-JAN-12:20 | 149.23 | 0.00 | 0.00 | 1.17 | 299.85 | 0.00 | 0.00 | 15.17 |
February | 262.50 | 0.79 | 0.50 | 04-FEB-11:30 | 208.90 | 0.00 | 0.00 | 44.17 | 275.52 | 0.00 | 0.00 | 20.67 |
March | 339.33 | 0.79 | 0.50 | 10-MAR-11:39 | 214.81 | 0.00 | 0.00 | 74.83 | 169.64 | 0.00 | 0.00 | 32.50 |
April | 371.17 | 0.76 | 0.50 | 01-APR-11:20 | 244.31 | 0.00 | 0.00 | 119.67 | 190.39 | 0.00 | 0.00 | 71.17 |
May | 332.17 | 0.74 | 0.50 | 01-MAY-10:39 | 260.95 | 0.00 | 0.00 | 140.00 | 728.61 | 0.00 | 0.00 | 97.17 |
June | 430.67 | 0.73 | 0.50 | 01-JUN-09:00 | 278.64 | 0.00 | 0.00 | 168.50 | 1399.50 | 0.00 | 0.00 | 142.83 |
July | 439.00 | 0.73 | 0.50 | 01-JUL-10:20 | 276.47 | 0.00 | 0.00 | 171.83 | 1001.40 | 0.00 | 0.00 | 129.33 |
August | 406.00 | 0.74 | 0.50 | 01-AUG-09:50 | 272.95 | 0.00 | 0.00 | 156.67 | 216.10 | 0.00 | 0.00 | 111.67 |
September | 289.17 | 0.76 | 0.50 | 01-SEP-10:30 | 234.39 | 0.00 | 0.00 | 87.50 | 564.06 | 0.00 | 0.00 | 68.33 |
October | 314.33 | 0.81 | 0.50 | 01-OCT-12:30 | 188.42 | 0.00 | 0.00 | 36.17 | 272.66 | 0.00 | 0.00 | 14.83 |
November | 258.33 | 0.88 | 0.58 | 05-NOV-11:20 | 147.94 | 0.00 | 0.00 | 0.67 | 115.45 | 0.00 | 0.00 | 0.00 |
December | 230.67 | 0.87 | 0.58 | 09-DEC-12:39 | 153.26 | 0.00 | 0.00 | 1.17 | 119.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3928.50 | 0.78 | 228.06 | 0.00 | 0.00 | 1002.33 | 497.73 | 0.00 | 0.00 | 703.67 | ||
Minimum of Months | 230.67 | 0.73 | 0.50 | 147.94 | 0.00 | 0.00 | 0.67 | 115.45 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 439.00 | 0.88 | 0.58 | 278.64 | 0.00 | 0.00 | 171.83 | 1399.50 | 0.00 | 0.00 | 142.83 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.69 | 0.50 | 01-JAN-11:30 | 192.47 | 12.76 | 0.00 | 109.50 | 159.80 | 16.02 | 0.67 | 71.00 |
February | 262.50 | 0.63 | 0.50 | 01-FEB-12:50 | 268.66 | 14.18 | 0.00 | 170.17 | 221.07 | 17.54 | 38.33 | 140.00 |
March | 339.33 | 0.63 | 0.50 | 01-MAR-12:39 | 274.44 | 13.83 | 0.00 | 218.50 | 228.18 | 17.46 | 60.67 | 172.00 |
April | 371.17 | 0.62 | 0.50 | 01-APR-08:09 | 311.32 | 14.06 | 0.00 | 255.50 | 259.88 | 17.70 | 90.00 | 213.17 |
May | 332.17 | 0.62 | 0.50 | 01-MAY-07:00 | 1027.65 | 14.15 | 0.83 | 288.33 | 1841.03 | 19.34 | 99.00 | 245.33 |
June | 430.67 | 0.61 | 0.50 | 01-JUN-06:49 | 2009.54 | 14.31 | 0.17 | 305.33 | 2177.40 | 18.11 | 111.67 | 259.17 |
July | 439.00 | 0.61 | 0.50 | 01-JUL-07:30 | 1476.50 | 14.32 | 1.67 | 308.67 | 1802.33 | 18.66 | 113.00 | 267.83 |
August | 406.00 | 0.61 | 0.50 | 01-AUG-07:10 | 350.51 | 14.62 | 0.17 | 287.50 | 635.20 | 18.94 | 120.00 | 245.83 |
September | 289.17 | 0.63 | 0.50 | 01-SEP-08:09 | 653.16 | 15.77 | 17.67 | 231.67 | 939.19 | 18.28 | 87.00 | 190.00 |
October | 314.33 | 0.65 | 0.50 | 01-OCT-08:30 | 587.97 | 14.21 | 12.83 | 190.83 | 477.93 | 16.89 | 35.33 | 144.00 |
November | 258.33 | 0.69 | 0.50 | 01-NOV-09:50 | 728.56 | 12.33 | 0.00 | 117.67 | 463.27 | 15.52 | 0.50 | 73.67 |
December | 230.67 | 0.68 | 0.50 | 01-DEC-12:20 | 478.02 | 12.79 | 0.00 | 108.00 | 422.86 | 16.00 | 0.00 | 74.50 |
Annual Sum or Average | 3928.50 | 0.64 | 763.08 | 14.03 | 33.33 | 2591.67 | 893.50 | 17.71 | 756.17 | 2096.50 | ||
Minimum of Months | 230.67 | 0.61 | 0.50 | 192.47 | 12.33 | 0.00 | 108.00 | 159.80 | 15.52 | 0.00 | 71.00 | |
Maximum of Months | 439.00 | 0.69 | 0.50 | 2009.54 | 15.77 | 17.67 | 308.67 | 2177.40 | 19.34 | 120.00 | 267.83 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.83 | 0.78 | 01-JAN-12:09 | 492.88 | 21.07 | 71.00 | 109.83 | 678.15 | 21.72 | 99.83 | 196.17 |
February | 262.50 | 0.82 | 0.78 | 01-FEB-12:00 | 634.68 | 20.88 | 70.33 | 163.00 | 1293.04 | 24.22 | 153.50 | 224.83 |
March | 339.33 | 0.82 | 0.78 | 01-MAR-12:39 | 650.36 | 19.24 | 54.67 | 201.50 | 2044.94 | 25.06 | 178.83 | 283.83 |
April | 371.17 | 0.82 | 0.78 | 01-APR-10:39 | 452.63 | 17.12 | 20.83 | 233.83 | 2492.31 | 24.67 | 197.00 | 311.17 |
May | 332.17 | 0.81 | 0.78 | 01-MAY-10:09 | 473.53 | 17.16 | 0.17 | 270.83 | 2565.03 | 22.94 | 176.50 | 358.17 |
June | 430.67 | 0.81 | 0.78 | 01-JUN-06:40 | 499.15 | 16.99 | 0.00 | 313.17 | 2784.76 | 22.96 | 210.67 | 369.00 |
July | 439.00 | 0.81 | 0.78 | 01-JUL-07:10 | 486.28 | 17.03 | 1.50 | 312.50 | 2448.63 | 22.78 | 211.67 | 375.17 |
August | 406.00 | 0.81 | 0.78 | 01-AUG-06:49 | 492.12 | 17.52 | 14.67 | 283.67 | 2262.18 | 23.74 | 209.17 | 349.67 |
September | 289.17 | 0.81 | 0.78 | 01-SEP-08:20 | 484.72 | 18.05 | 33.83 | 215.50 | 2550.26 | 25.71 | 169.67 | 295.00 |
October | 314.33 | 0.82 | 0.78 | 01-OCT-08:50 | 771.88 | 20.63 | 76.67 | 170.50 | 1303.43 | 24.01 | 153.50 | 252.67 |
November | 258.33 | 0.84 | 0.78 | 01-NOV-10:39 | 489.84 | 20.51 | 67.50 | 102.50 | 805.55 | 22.51 | 104.83 | 196.17 |
December | 230.67 | 0.83 | 0.78 | 01-DEC-12:30 | 445.26 | 20.67 | 58.50 | 97.00 | 700.73 | 21.70 | 92.00 | 188.83 |
Annual Sum or Average | 3928.50 | 0.82 | 529.12 | 18.61 | 469.67 | 2473.83 | 1958.27 | 23.55 | 1957.17 | 3400.67 | ||
Minimum of Months | 230.67 | 0.81 | 0.78 | 445.26 | 16.99 | 0.00 | 97.00 | 678.15 | 21.70 | 92.00 | 188.83 | |
Maximum of Months | 439.00 | 0.84 | 0.78 | 771.88 | 21.07 | 76.67 | 313.17 | 2784.76 | 25.71 | 211.67 | 375.17 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113199E+11 | 28883.48 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110115E+11 | 28883.48 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.695242E+10 | 28883.48 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.317990E+10 | 28883.48 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.439189E+09 | 28883.48 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 770481.31 | 818.75 | 14-JUN-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9633400.52 | 14018.09 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126346E+10 | 28883.48 | 03-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.393135E+10 | 28883.48 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100666E+11 | 28883.48 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.481747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113199E+11 | 28883.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.457649E+11 | 96109.25 | 01-JAN-00:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.440663E+11 | 96109.25 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.215967E+11 | 96109.25 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.640175E+10 | 96109.25 | 05-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 33935479.26 | 63736.71 | 01-MAY-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.173899E+10 | 61693.25 | 30-OCT-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117092E+11 | 96109.25 | 03-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.422990E+11 | 96109.25 | 02-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173611E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.457649E+11 | 96109.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.168604E+12 | 197930.95 | 12-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172576E+12 | 205986.40 | 06-FEB-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.639125E+11 | 111219.38 | 05-MAR-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.923646E+10 | 73485.60 | 16-APR-06:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 59176770.20 | 12312.21 | 30-OCT-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.190197E+11 | 48081.54 | 25-NOV-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158072E+12 | 167071.83 | 09-DEC-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.591480E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.172576E+12 | 205986.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 50339586.77 | 46011742.54 | 2919.24 | 15-MAR-15:10 | 2726.20 | 0.00 |
April | 0.00 | 0.00 | 29.54 | 29.54 | 0.05 | 22-APR-14:10 | 0.05 | 0.00 |
May | 0.00 | 0.00 | 0.348946E+09 | 0.334985E+09 | 19644.05 | 31-MAY-17:25 | 18537.49 | 0.00 |
June | 0.00 | 0.00 | 0.449187E+10 | 0.353826E+10 | 24111.31 | 27-JUN-19:45 | 12417.90 | 0.00 |
July | 0.00 | 0.00 | 0.101087E+11 | 0.735085E+10 | 24121.93 | 20-JUL-05:45 | 12366.18 | 0.00 |
August | 0.00 | 0.00 | 0.824621E+10 | 0.661042E+10 | 24895.32 | 13-AUG-23:01 | 12373.72 | 0.00 |
September | 0.00 | 0.00 | 0.260280E+10 | 0.198041E+10 | 23358.25 | 15-SEP-20:11 | 12025.01 | 0.00 |
October | 0.00 | 0.00 | 15707688.47 | 15509264.25 | 1760.16 | 11-OCT-15:00 | 1736.09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.258645E+11 | 0.198765E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.101087E+11 | 0.735085E+10 | 24895.32 | 18537.49 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.504263E+10 | 0.356689E+10 | 78249.85 | 27-JUN-18:53 | 38847.28 | 0.00 |
July | 0.00 | 0.00 | 0.168143E+11 | 0.114560E+11 | 82030.64 | 20-JUL-22:45 | 34970.30 | 0.00 |
August | 0.00 | 0.00 | 0.112963E+11 | 0.885468E+10 | 77868.34 | 13-AUG-18:45 | 40981.43 | 0.00 |
September | 0.00 | 0.00 | 0.907336E+09 | 0.660073E+09 | 19835.82 | 16-SEP-13:30 | 14644.39 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.340606E+11 | 0.245376E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.168143E+11 | 0.114560E+11 | 82030.64 | 40981.43 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.124614E+10 | 0.08 | 479.60 | 01-JAN-00:03 | 0.08 |
February | 0.113531E+10 | 0.08 | 479.60 | 01-FEB-00:02 | 0.08 |
March | 0.756448E+09 | 0.05 | 479.60 | 01-MAR-00:03 | 0.08 |
April | 0.207235E+09 | 0.01 | 479.60 | 01-APR-00:05 | 0.08 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 4700074.08 | 0.00 | 479.60 | 30-OCT-04:20 | 0.08 |
November | 0.519075E+09 | 0.03 | 479.60 | 02-NOV-22:40 | 0.08 |
December | 0.123535E+10 | 0.08 | 479.60 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.510426E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.124614E+10 | 0.08 | 479.60 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135249E+10 | 0.70 | 1207.28 | 02-JAN-11:20 | 0.93 |
February | 0.126233E+10 | 0.70 | 1207.28 | 03-FEB-11:10 | 0.93 |
March | 0.137434E+10 | 0.54 | 1207.28 | 08-MAR-09:20 | 0.94 |
April | 0.123373E+10 | 0.42 | 1207.28 | 03-APR-09:40 | 0.93 |
May | 0.125503E+10 | 0.37 | 1207.28 | 04-MAY-07:10 | 0.93 |
June | 0.136276E+10 | 0.43 | 1207.28 | 03-JUN-06:30 | 0.93 |
July | 0.147173E+10 | 0.49 | 1207.28 | 08-JUL-06:50 | 0.92 |
August | 0.154214E+10 | 0.50 | 1207.28 | 11-AUG-07:40 | 0.92 |
September | 0.125130E+10 | 0.38 | 1207.28 | 01-SEP-14:20 | 0.93 |
October | 0.121175E+10 | 0.36 | 1207.28 | 07-OCT-06:20 | 0.93 |
November | 0.118090E+10 | 0.38 | 1207.28 | 02-NOV-08:30 | 0.93 |
December | 0.132890E+10 | 0.63 | 1207.28 | 01-DEC-15:00 | 0.93 |
Annual Sum or Average | 0.158274E+11 | 0.49 | |||
Minimum of Months | 0.118090E+10 | 0.36 | 1207.28 | 0.92 | |
Maximum of Months | 0.154214E+10 | 0.70 | 1207.28 | 0.94 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.239412E+10 | 0.62 | 2973.82 | 01-JAN-00:42 | 0.90 |
February | 0.225589E+10 | 0.62 | 2973.82 | 01-FEB-00:02 | 0.91 |
March | 0.186926E+10 | 0.52 | 2973.82 | 01-MAR-00:03 | 0.90 |
April | 0.136451E+10 | 0.36 | 2973.82 | 05-APR-05:01 | 0.90 |
May | 0.122576E+10 | 0.21 | 1972.15 | 01-MAY-05:06 | 0.90 |
June | 0.124608E+10 | 0.22 | 2973.82 | 27-JUN-17:10 | 0.88 |
July | 0.128193E+10 | 0.23 | 2973.82 | 16-JUL-10:43 | 0.89 |
August | 0.132461E+10 | 0.23 | 2973.82 | 13-AUG-13:03 | 0.89 |
September | 0.117763E+10 | 0.21 | 1189.53 | 16-SEP-11:40 | 0.54 |
October | 0.122895E+10 | 0.25 | 1908.92 | 30-OCT-04:13 | 0.90 |
November | 0.146743E+10 | 0.47 | 2973.82 | 03-NOV-05:01 | 0.90 |
December | 0.230694E+10 | 0.61 | 2973.82 | 02-DEC-06:01 | 0.90 |
Annual Sum or Average | 0.191431E+11 | 0.38 | |||
Minimum of Months | 0.117763E+10 | 0.21 | 1189.53 | 0.54 | |
Maximum of Months | 0.239412E+10 | 0.62 | 2973.82 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.135249E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.126233E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.138639E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.123373E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.133544E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.235090E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.367524E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.335402E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.182539E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.121548E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.118090E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.132890E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.215012E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.118090E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.367524E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.239412E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.225589E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.186926E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.136451E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.122576E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.246151E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.527115E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.408145E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.140390E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.122895E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.146743E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.230694E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.273309E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.122576E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.527115E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.135249E+10 | 0.00 | 0.113199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126233E+10 | 0.00 | 0.110115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137434E+10 | 50339586.77 | 0.695242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123373E+10 | 29.54 | 0.317990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125503E+10 | 0.348946E+09 | 0.439189E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136276E+10 | 0.449187E+10 | 770481.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147173E+10 | 0.101087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.154214E+10 | 0.824621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.125130E+10 | 0.260280E+10 | 9633400.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121175E+10 | 15707688.47 | 0.126346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118090E+10 | 0.00 | 0.393135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132890E+10 | 0.00 | 0.100666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158274E+11 | 0.258645E+11 | 0.481747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154214E+10 | 0.101087E+11 | 0.113199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.239412E+10 | 0.00 | 0.457649E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.225589E+10 | 0.00 | 0.440663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.186926E+10 | 0.00 | 0.215967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136451E+10 | 0.00 | 0.640175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122576E+10 | 0.00 | 33935479.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124608E+10 | 0.479418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.128193E+10 | 0.159070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132461E+10 | 0.109594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.117763E+10 | 0.907336E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.122895E+10 | 0.00 | 0.173899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146743E+10 | 0.00 | 0.117092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.230694E+10 | 0.00 | 0.422990E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191431E+11 | 0.325679E+11 | 0.173611E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.239412E+10 | 0.159070E+11 | 0.457649E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.135249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137434E+10 | 0.00 | 0.00 | 0.00 | 12041571.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123373E+10 | 0.00 | 0.00 | 0.00 | 7.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125503E+10 | 0.00 | 0.00 | 0.00 | 80406798.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136276E+10 | 0.00 | 0.00 | 0.00 | 0.988141E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147173E+10 | 0.00 | 0.00 | 0.00 | 0.220351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.154214E+10 | 0.00 | 0.00 | 0.00 | 0.181188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.125130E+10 | 0.00 | 0.00 | 0.00 | 0.574091E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121175E+10 | 0.00 | 0.00 | 0.00 | 3731043.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158274E+11 | 0.00 | 0.00 | 0.00 | 0.567380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154214E+10 | 0.00 | 0.00 | 0.00 | 0.220351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.239412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.225589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.186926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124608E+10 | 0.00 | 0.00 | 0.00 | 0.121543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.128193E+10 | 0.00 | 0.00 | 0.00 | 0.398922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132461E+10 | 0.00 | 0.00 | 0.00 | 0.275685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.117763E+10 | 0.00 | 0.00 | 0.00 | 0.226267E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.122895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.230694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191431E+11 | 0.00 | 0.00 | 0.00 | 0.818777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.239412E+10 | 0.00 | 0.00 | 0.00 | 0.398922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283764E+10 | 0.00 | 0.00 | 0.12 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266273E+10 | 0.00 | 0.00 | 0.13 |
March | 0.116344E+09 | 0.00 | 0.00 | 24300.48 | 74630.52 | 0.210020E+10 | 7234149.92 | 0.00 | 0.13 |
April | 0.406635E+09 | 0.00 | 0.00 | 8179.88 | 0.00 | 0.111807E+10 | 29646510.21 | 0.00 | 0.13 |
May | 0.592921E+09 | 2287698.59 | 0.00 | 1217509.77 | 0.00 | 79832645.78 | 0.127122E+10 | 0.00 | 0.33 |
June | 51831278.61 | 0.311011E+09 | 0.00 | 4788091.80 | 323426.86 | 0.00 | 0.255668E+10 | 0.00 | 0.70 |
July | 10890357.51 | 0.111034E+10 | 0.00 | 3975490.87 | 318756.52 | 0.00 | 0.886100E+09 | 0.00 | 0.66 |
August | 15966165.93 | 0.636622E+09 | 0.00 | 6279548.40 | 52251.58 | 0.00 | 0.181538E+10 | 0.00 | 0.74 |
September | 94646072.06 | 0.166465E+09 | 0.00 | 4117635.93 | 764088.66 | 0.00 | 0.264141E+10 | 0.00 | 0.69 |
October | 0.827349E+09 | 0.00 | 0.00 | 241365.58 | 0.00 | 0.467741E+09 | 0.352372E+09 | 0.00 | 0.17 |
November | 0.158539E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152366E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268089E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.227512E+10 | 0.222673E+10 | 0.00 | 20652122.71 | 1533154.15 | 0.134708E+11 | 0.956004E+10 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.827349E+09 | 0.111034E+10 | 0.00 | 6279548.40 | 764088.66 | 0.283764E+10 | 0.264141E+10 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.733461E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.800188E+10 | 0.00 | 0.00 | 0.17 |
February | 0.102283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.721749E+10 | 0.00 | 0.00 | 0.17 |
March | 0.361203E+10 | 0.00 | 0.00 | 0.00 | 18803661.09 | 0.271469E+10 | 0.00 | 0.00 | 0.19 |
April | 0.388085E+10 | 0.00 | 0.00 | 0.00 | 617389.80 | 0.328094E+09 | 0.00 | 0.00 | 0.18 |
May | 0.381378E+10 | 0.00 | 0.00 | 29849.57 | 0.00 | 0.00 | 51674754.66 | 0.00 | 0.18 |
June | 0.214565E+10 | 0.413464E+09 | 0.00 | 5050884.38 | 787840.34 | 0.00 | 0.259517E+10 | 0.00 | 0.34 |
July | 0.154700E+09 | 0.164710E+10 | 0.00 | 9008179.69 | 242656.90 | 0.00 | 0.313375E+10 | 0.00 | 0.46 |
August | 0.737442E+09 | 0.561126E+09 | 0.00 | 12369919.21 | 0.00 | 0.00 | 0.343860E+10 | 0.00 | 0.42 |
September | 0.286503E+10 | 55503899.13 | 0.00 | 1812825.29 | 0.00 | 0.00 | 0.150309E+10 | 0.00 | 0.25 |
October | 0.409039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54373430.46 | 0.00 | 0.00 | 0.17 |
November | 0.367451E+10 | 0.00 | 0.00 | 0.00 | 2495498.21 | 0.788524E+09 | 0.00 | 0.00 | 0.17 |
December | 0.137618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671685E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.281069E+11 | 0.267719E+10 | 0.00 | 28271658.15 | 22947046.34 | 0.258219E+11 | 0.107223E+11 | 0.00 | 0.24 |
Minimum of Months | 0.154700E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.409039E+10 | 0.164710E+10 | 0.00 | 12369919.21 | 18803661.09 | 0.800188E+10 | 0.343860E+10 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:48
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.248642E+12 | 0.140979E+12 | 0.00 | 0.115730E+11 | 0.671623E+11 |
February | 0.428339E+12 | 0.153533E+12 | 0.00 | 0.109031E+11 | 0.668847E+11 |
March | 0.695228E+12 | 0.794847E+11 | 0.00 | 0.853164E+10 | 0.289970E+11 |
April | 0.849506E+12 | 0.483356E+11 | 0.00 | 0.576268E+10 | 0.678175E+10 |
May | 0.108495E+13 | 0.369334E+11 | 0.00 | 0.581560E+10 | 0.649519E+09 |
June | 0.120756E+13 | 0.423106E+11 | 0.00 | 0.672263E+10 | 0.117385E+11 |
July | 0.114344E+13 | 0.400058E+11 | 0.00 | 0.152177E+10 | 0.331157E+11 |
August | 0.972241E+12 | 0.431922E+11 | 0.00 | 0.497967E+10 | 0.241113E+11 |
September | 0.714780E+12 | 0.388482E+11 | 0.00 | 0.692489E+10 | 0.431534E+10 |
October | 0.447257E+12 | 0.415419E+11 | 0.00 | 0.579263E+10 | 0.149162E+10 |
November | 0.199874E+12 | 0.484725E+11 | 0.00 | 0.614273E+10 | 0.121671E+11 |
December | 0.211527E+12 | 0.142641E+12 | 0.00 | 0.107739E+11 | 0.625638E+11 |
Annual Sum or Average | 0.820335E+13 | 0.856278E+12 | 0.00 | 0.854442E+11 | 0.319979E+12 |
Minimum of Months | 0.199874E+12 | 0.369334E+11 | 0.00 | 0.152177E+10 | 0.649519E+09 |
Maximum of Months | 0.120756E+13 | 0.153533E+12 | 0.00 | 0.115730E+11 | 0.671623E+11 |