Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:42
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2023-10-16 10:43:00
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:00
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 435.00 | 89.97 | 89.97 |
Net Site Energy | 435.00 | 89.97 | 89.97 |
Total Source Energy | 1377.22 | 284.84 | 284.84 |
Net Source Energy | 1377.22 | 284.84 | 284.84 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 93.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 81.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 38.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 434.80 | 0.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 93.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 81.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 61.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 16.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 22.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 22.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 93.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 81.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 61.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 38.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 22.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 29.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 32.12 | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 89.92 | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 29.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 32.12 | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 89.92 | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 434.798 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 434.798 | 100.00 |
Total On-Site and Utility Electric Sources | 434.798 | 100.00 |
Total Electricity End Uses | 434.798 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.17 |
Time Setpoint Not Met During Occupied Cooling | 58.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3140.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:00
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:42 |
RunPeriod | RUNPERIOD 1 |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Latitude [deg] | 25.82 |
Longitude [deg] | -80.3 |
Elevation [m] | 11.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 119.93 |
Skylight-Roof Ratio [%] | 2.61 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 6.9682 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 7.4271 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.5521 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8362 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8362 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 6.9682 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 7.4271 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.5521 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.8362 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.8362 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.8362 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:00
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 27-JUL-15:39 | 15-DEC-07:19 | - | - | - | - | - | - | - | - | - | - | 19-APR-11:39 |
Heating | 0.00 | 7730.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 15718.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4367.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4687.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1575.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 36383.27 | 7730.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 7730.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 15718.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 4367.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2381.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1575.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:00
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 297.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 257.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 195.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 122.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 72.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1377.00 | 0.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 61.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 53.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 25.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 284.79 | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 61.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 53.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 25.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 284.79 | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:00
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.08 |
ZONE2 FINE STORAGE DIRECT AIR | 2.63 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 0.976836 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 0.976836 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 39930.81 |
PSZ-OFFICE HEATING COIL | 26400.95 |
PSZ-FINE STORAGE HEATING COIL | 81097.21 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 24569.42 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.00 | 1.00 | 1.08 |
PSZ-FINE STORAGE | 2.63 | 2.63 | 2.63 | 2.63 | 2.63 | 2.63 | 1.00 | 1.00 | 2.63 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.08 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.63 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.08 | 1200.53 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.63 | 2810.24 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.08 | 1.08 | 1.08 | 0.715658 | 22502.06 | 26400.95 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.63 | 2.63 | 2.63 | 1.73 | 65216.71 | 81097.21 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.08 | 0.542165 | 0.722887 | 22502.06 | 11251.03 | 0.762270 | 0.762270 |
PSZ-FINE STORAGE COOLING COIL | 2.63 | 1.31 | 1.75 | 65216.71 | 32608.35 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:00
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:00
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:00
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.30 | 23.60 | 20.30 | 19.40 | 20.90 | 21.60 | 24.10 | 26.40 | 27.70 | 28.10 | 28.00 | 27.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Miami Intl Ap FL USA TMY3 WMO#=722020 | 25.82 | -80.30 | -5.00 | 11.00 | 101193 | 1.2027 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.49 | 8.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 6.968 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 15.042 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 7.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.427 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.552 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 6.111 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1650.627 | 6.968 | 129.474 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1650.627 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 10348.979 | 7.427 | 344.966 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10348.979 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 11383.888 | 3.552 | 164.984 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11383.888 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2405 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.7173 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.6534 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 2.825 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 2.825 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.158 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.394 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.431 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2546 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2546 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.77015739E-08 | 0.38457199E-13 | 0.23136523E-13 | 0.0000000 |
2 | 1 | -5.2160498 | 0.48395528E-04 | -0.66612159E-04 | 0.14765390E-08 |
3 | 0 | 5.4565497 | 0.24045158 | 0.24056658 | |
4 | 2 | 0.53311453E-11 | 0.59398160E-16 | 0.15345153E-15 | 0.0000000 |
5 | 1 | -5.2159564 | 0.46378490E-04 | -0.22332804E-04 | 0.68713370E-11 |
6 | 0 | 5.9333026 | 0.71729982 | 0.71736853 | |
7 | 4 | 0.74747876E-12 | 0.20825084E-15 | -0.25659737E-14 | 0.12362927E-15 |
8 | 3 | -0.37328678E-03 | 0.45238042E-06 | -0.54038165E-04 | 0.14344535E-12 |
9 | 2 | 1.7123825 | 0.10013958E-01 | 1.1198054 | -0.71564441E-04 |
10 | 1 | -7.1648294 | 0.26145347 | -16.966117 | 0.32817431 |
11 | 0 | 5.8918369 | 0.16754891 | 16.285382 | |
12 | 4 | 0.33466332E-12 | 0.89461943E-14 | -0.12859024E-13 | 0.20877214E-15 |
13 | 3 | -0.22871403E-03 | 0.15053116E-05 | -0.31975464E-04 | 0.68322840E-13 |
14 | 2 | 1.3386772 | 0.41030944E-01 | 0.83718830 | -0.43809927E-04 |
15 | 1 | -7.7424045 | 1.2165027 | -15.097018 | 0.25560053 |
16 | 0 | 8.5066984 | 0.84520726 | 16.362604 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.12859024E-13 | 0.89461943E-14 | 0.33466332E-12 | 0.20877214E-15 |
85 | 3 | -0.31975464E-04 | 0.15053116E-05 | -0.22871403E-03 | 0.68322840E-13 |
86 | 2 | 0.83718830 | 0.41030944E-01 | 1.3386772 | -0.43809927E-04 |
87 | 1 | -15.097018 | 1.2165027 | -7.7424045 | 0.25560053 |
88 | 0 | 16.362604 | 0.84520726 | 8.5066984 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.503_SHGC_SOUTH_0.229 | 34 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.230 | ||
2 | NONRESWINDOW_U_0.503_SHGC_NORTH_0.229 | 35 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.230 | ||
3 | NONRESWINDOW_U_0.503_SHGC_EAST_0.229 | 36 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.230 | ||
4 | NONRESWINDOW_U_0.503_SHGC_WEST_0.229 | 37 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.230 | ||
5 | SKYLIGHT_U_0.7_SHGC_0.3 | 38 | 1 | VerySmooth | 3.979 | 3.979 | 1.000 | 0.303 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.93472E-002 | 0.14029 | 0.63161 | 0.63161 | 0.22900 | 0.16611 | 0.25065 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.93472E-002 | 0.14029 | 0.63161 | 0.63161 | 0.22900 | 0.16611 | 0.25065 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.93472E-002 | 0.14029 | 0.63161 | 0.63161 | 0.22900 | 0.16611 | 0.25065 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.93472E-002 | 0.14029 | 0.63161 | 0.63161 | 0.22900 | 0.16611 | 0.25065 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.17728 | 0.47032 | 0.47032 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 2.40661E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | CurtainWall | 3.838 | 0.300 | 0.402 |
2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.799 | 0.390 | 0.214 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.331 | 7.274E-004 | 4.751E-004 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.8563E-005 |
2 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8461E-004 |
3 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.0249E-005 |
4 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0062E-004 |
5 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.6534E-005 |
6 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.9699E-004 |
7 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0157E-004 |
8 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.7234E-004 |
9 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5889E-004 |
10 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6115E-004 |
11 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3577E-004 |
12 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.7387E-004 |
13 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4271E-004 |
14 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5948E-004 |
15 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4476E-004 |
16 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5357E-004 |
17 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.6240E-004 |
18 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2409E-004 |
19 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0634E-004 |
20 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2876E-004 |
21 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.1069E-004 |
22 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1479E-004 |
23 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.0436E-004 |
24 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1182E-005 |
25 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.1630E-004 |
26 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8925E-005 |
27 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5257E-004 |
28 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.0874E-005 |
29 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.7490E-004 |
30 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.4347E-005 |
31 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3611E-003 |
32 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3609E-005 |
33 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.6180E-004 |
34 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3142E-005 |
35 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7097E-004 |
36 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4253E-005 |
37 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.2399E-004 |
38 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1751E-005 |
39 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1206E-004 |
40 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8484E-005 |
41 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1363E-004 |
42 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6955E-005 |
43 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.2882E-004 |
44 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7787E-005 |
45 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.2150E-004 |
46 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7219E-005 |
47 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8883E-004 |
48 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6707E-005 |
49 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.1927E-004 |
50 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8042E-005 |
51 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5221E-004 |
52 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9066E-005 |
53 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0981E-004 |
54 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7702E-005 |
55 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4746E-004 |
56 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6794E-005 |
57 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3226E-003 |
58 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6276E-005 |
59 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.9504E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.7960E-005 |
61 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.6278E-003 |
62 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3229E-005 |
63 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1327E-003 |
64 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8762E-005 |
65 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1749E-003 |
66 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9887E-005 |
67 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1797E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.3943E-005 |
69 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8098E-003 |
70 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.9880E-005 |
71 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.6038E-003 |
72 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4693E-005 |
73 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1928E-004 |
74 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7396E-004 |
75 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.2678E-004 |
76 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8893E-004 |
77 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.3602E-004 |
78 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4184E-004 |
79 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6538E-003 |
80 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6639E-005 |
81 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9828E-004 |
82 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8328E-004 |
83 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6748E-004 |
84 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6927E-004 |
85 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8570E-004 |
86 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.4303E-004 |
87 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.4325E-004 |
88 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9096E-004 |
89 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5897E-005 |
90 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.1708E-003 |
91 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.6020E-005 |
92 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.8271E-003 |
93 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.2998E-005 |
94 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1830E-003 |
95 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1412E-004 |
96 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.0087E-004 |
97 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7334E-005 |
98 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6215E-003 |
99 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.4015E-005 |
100 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.7628E-003 |
101 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1919E-005 |
102 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.1921E-003 |
103 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.1055E-005 |
104 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.2128E-003 |
105 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5646E-005 |
106 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6099E-004 |
107 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2695E-005 |
108 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.1140E-004 |
109 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0635E-005 |
110 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0411E-003 |
111 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.8879E-005 |
112 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2630E-003 |
113 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2400E-005 |
114 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6758E-005 |
115 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8623E-005 |
116 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9550E-005 |
117 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6055E-005 |
118 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5652E-005 |
119 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4598E-005 |
120 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5286E-005 |
121 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4578E-005 |
122 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7839E-005 |
123 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7822E-005 |
124 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2998E-005 |
125 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3675E-005 |
126 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1243E-005 |
127 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1685E-005 |
128 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2542E-005 |
129 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1964E-005 |
130 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0270E-005 |
131 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8568E-005 |
132 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9587E-005 |
133 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7604E-005 |
134 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9717E-005 |
135 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4582E-005 |
136 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1042E-005 |
137 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3099E-004 |
138 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1745E-004 |
139 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3988E-004 |
140 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2687E-004 |
141 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1366E-004 |
142 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.5771E-005 |
143 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2514E-005 |
144 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3080E-005 |
145 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2321E-005 |
146 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7078E-004 |
147 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2055E-005 |
148 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8848E-004 |
149 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1104E-005 |
150 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3439E-004 |
151 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4916E-005 |
152 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6240E-005 |
153 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1043E-005 |
154 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5148E-005 |
155 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4959E-005 |
156 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5127E-005 |
157 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0471E-005 |
158 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4376E-005 |
159 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4899E-005 |
160 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1079E-005 |
161 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6456E-004 |
162 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4952E-005 |
163 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8222E-004 |
164 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5981E-005 |
165 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2658E-004 |
166 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0610E-005 |
167 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2500E-005 |
168 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7738E-005 |
169 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2533E-005 |
170 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6184E-004 |
171 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0274E-005 |
172 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.4762E-004 |
173 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.8837E-005 |
174 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3233E-004 |
175 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0532E-005 |
176 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7293E-004 |
177 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2479E-004 |
178 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4198E-004 |
179 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5346E-004 |
180 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6445E-004 |
181 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0513E-004 |
182 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1190E-004 |
183 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5069E-004 |
184 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0290E-004 |
185 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9377E-004 |
186 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1215E-005 |
187 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6809E-004 |
188 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1490E-005 |
189 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7524E-004 |
190 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9265E-005 |
191 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5061E-004 |
192 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8433E-005 |
193 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2917E-004 |
194 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7834E-005 |
195 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3465E-004 |
196 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7396E-005 |
197 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2173E-004 |
198 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7459E-005 |
199 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0473E-005 |
200 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3210E-005 |
201 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4227E-003 |
202 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.5699E-005 |
203 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6552E-003 |
204 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3398E-005 |
205 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2083E-003 |
206 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1093E-005 |
207 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2387E-004 |
208 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6113E-005 |
209 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0070E-004 |
210 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3181E-004 |
211 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6508E-004 |
212 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6090E-004 |
213 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8535E-004 |
214 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5755E-004 |
215 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2445E-004 |
216 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5215E-004 |
217 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8345E-004 |
218 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9661E-005 |
219 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8481E-004 |
220 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8660E-005 |
221 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0144E-004 |
222 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9974E-005 |
223 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2708E-004 |
224 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5686E-005 |
225 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3154E-004 |
226 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2919E-003 |
227 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2358E-004 |
228 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7322E-003 |
229 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5687E-004 |
230 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7440E-003 |
231 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2726E-004 |
232 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9459E-004 |
233 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9358E-004 |
234 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9744E-005 |
235 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8267E-004 |
236 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8267E-005 |
237 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4236E-004 |
238 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0452E-005 |
239 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9961E-004 |
240 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7482E-005 |
241 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5105E-003 |
242 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.7783E-005 |
243 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5882E-003 |
244 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.2032E-005 |
245 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8457E-003 |
246 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9374E-005 |
247 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6165E-003 |
248 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3274E-005 |
249 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0923E-003 |
250 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7070E-004 |
251 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0782E-003 |
252 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6085E-004 |
253 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4449E-003 |
254 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1830E-004 |
255 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6195E-003 |
256 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2024E-004 |
257 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5136E-004 |
258 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4245E-003 |
259 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3531E-004 |
260 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6063E-003 |
261 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8865E-004 |
262 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8638E-003 |
263 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0001E-004 |
264 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6530E-003 |
265 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4617E-004 |
266 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7997E-005 |
267 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2985E-004 |
268 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6377E-005 |
269 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8050E-004 |
270 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8404E-005 |
271 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9852E-004 |
272 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7461E-005 |
273 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2902E-004 |
274 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.3448E-004 |
275 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1116E-004 |
276 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.2605E-004 |
277 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4585E-004 |
278 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1721E-003 |
279 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9891E-004 |
280 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6031E-003 |
281 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7615E-004 |
282 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5253E-005 |
283 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0031E-004 |
284 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.8307E-005 |
285 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9354E-004 |
286 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3487E-005 |
287 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5919E-003 |
288 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3045E-005 |
289 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0501E-004 |
290 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9659E-004 |
291 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2255E-004 |
292 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6213E-004 |
293 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6203E-004 |
294 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9545E-004 |
295 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5949E-003 |
296 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1554E-004 |
297 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9034E-005 |
298 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8292E-004 |
299 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6171E-005 |
300 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3298E-004 |
301 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4353E-005 |
302 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9709E-004 |
303 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2574E-004 |
304 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7337E-004 |
305 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3240E-004 |
306 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4646E-004 |
307 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9105E-004 |
308 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2441E-004 |
309 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3533E-004 |
310 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6137E-004 |
311 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1039E-004 |
312 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4748E-004 |
313 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4204E-005 |
314 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6335E-005 |
315 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7724E-005 |
316 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4274E-005 |
317 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4735E-005 |
318 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3885E-005 |
319 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1671E-005 |
320 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7584E-005 |
321 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2194E-005 |
322 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5251E-005 |
323 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0360E-005 |
324 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3831E-005 |
325 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.8243E-005 |
326 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5030E-005 |
327 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2556E-004 |
328 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5637E-005 |
329 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8939E-005 |
330 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0891E-004 |
331 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1607E-005 |
332 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0443E-005 |
333 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0030E-005 |
334 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2303E-005 |
335 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9741E-005 |
336 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6869E-004 |
337 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.9495E-005 |
338 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.6406E-005 |
339 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2895E-005 |
340 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5837E-005 |
341 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2352E-005 |
342 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9534E-005 |
343 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4732E-004 |
344 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0119E-004 |
345 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8766E-005 |
346 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2493E-005 |
347 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2143E-005 |
348 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1439E-005 |
349 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4649E-005 |
350 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1906E-005 |
351 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9684E-005 |
352 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3161E-005 |
353 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3693E-004 |
354 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8108E-005 |
355 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9712E-004 |
356 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2549E-005 |
357 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5913E-004 |
358 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9201E-005 |
359 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0983E-004 |
360 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5702E-005 |
361 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.9024E-005 |
362 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4665E-005 |
363 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3139E-005 |
364 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1084E-005 |
365 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6858E-005 |
366 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2366E-005 |
367 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4724E-004 |
368 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8139E-005 |
369 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.7177E-003 |
370 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.3808E-004 |
371 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.3264E-003 |
372 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 2.9732E-004 |
373 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.1678E-003 |
374 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 2.8432E-004 |
375 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.6432E-003 |
376 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 2.9102E-004 |
377 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.3705E-004 |
378 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.1618E-003 |
379 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.0071E-004 |
380 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.5865E-003 |
381 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.8931E-004 |
382 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.3095E-003 |
383 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.8766E-004 |
384 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.2049E-003 |
385 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.5259E-003 |
386 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.9063E-004 |
387 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.9262E-003 |
388 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.5274E-004 |
389 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.3324E-003 |
390 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.1690E-004 |
391 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.0628E-003 |
392 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.7713E-004 |
393 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.6084E-003 |
394 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.9103E-004 |
395 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.9537E-003 |
396 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.5293E-004 |
397 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.1829E-003 |
398 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.1666E-004 |
399 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.0627E-003 |
400 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.7713E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10968.65588 | 13162.38705 | 0.90361 | 1.08433 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 32.35133 | 1.71656E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 6244.77246 | 7493.72696 | 0.17524 | 0.21029 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 8.70000 | 6.99286E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 34075.85118 | 40891.02141 | 2.18856 | 2.62628 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.13300 | 1.71671E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 11693.97407 | 14032.76889 | 0.27685 | 0.42471 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 8.70000 | 6.99286E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.20000 | 1.71672E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 20474.51535 | 24569.41842 | 0.50087 | 0.97684 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8.70000 | 6.99286E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 16644.24 | 1.08433 | 1.08433 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 6347.28 | 0.21029 | 0.21029 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 49948.08 | 2.62628 | 2.62628 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 16066.25 | 0.42471 | 0.42471 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.08433 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.62628 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.97684 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 0.97684 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 39930.80840 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 24569.41842 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.08433 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.08433 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.08433 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.08433 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.08433 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.08433 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.62628 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.62628 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.62628 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.62628 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.62628 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.62628 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.08433 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.62628 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.08433 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.08433 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1200.52561 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.08433 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.08433 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.08433 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.71566 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.08433 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.54217 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.72289 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22502.06000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11251.03000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76227 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76227 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22502.06000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26400.95177 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 26400.95177 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.62628 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.62628 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2810.24033 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.62628 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.62628 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.62628 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.73334 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.62628 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.31314 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.75085 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 65216.71000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 32608.35500 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 65216.71000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 81097.20900 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 81097.20900 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 21659.9 | 11.90 | 11.63 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 63175.3 | 12.06 | 11.79 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 3.4256059267E-002 | 2.5398392338E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 9.5375021396E-002 | 0.1371355750 | Pass | Pass | 0.7176112449 | 5.9252877112 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 6.7232136085E-002 | 6.9342066659E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:00
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 10322.08 | 514.65 | 0.00 | -70.3 | 488.65 | 11255.11 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:00
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00 | 8.70 | Wetbulb [C] | 3.80 | 340.00 |
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 6.70 | 25.30 | Wetbulb [C] | 4.50 | 140.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 65.00 | 29 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 38.00 | 14 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 391.00 | 83 | |||
Sep | 0.00 | 0 | |||
Oct | 225.00 | 40 | |||
Nov | 0.00 | 0 | |||
Dec | 5.00 | 10 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:00
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.233 | 0.240 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.985 | 2.825 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.985 | 2.825 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.985 | 2.825 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.653 | 0.717 | 3204.84 | 3105.72 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.685 | 2.825 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.685 | 2.825 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.503_SHGC_WEST_0.229 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.860 | 0.230 | 0.230 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.503_SHGC_WEST_0.229 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.860 | 0.230 | 0.230 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.503_SHGC_NORTH_0.229 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.860 | 0.230 | 0.230 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.503_SHGC_NORTH_0.229 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.860 | 0.230 | 0.230 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 137.59 | 5.146 | 0.472 | 0.379 | |||||||||||||||||
North Total or Average | 6.51 | 2.860 | 0.230 | 0.230 | |||||||||||||||||
Non-North Total or Average | 131.09 | 5.260 | 0.484 | 0.387 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:00
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:00
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 6.9682 | 236.88 | 1650.63 | LightsWired | LTG_SCH_OFFICE | 52.33 | 168.00 | 33.00 | 0.0000 | Y | 10.22 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 7.4271 | 1393.41 | 10348.98 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 17.85 | 0.0000 | Y | 34.68 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.5521 | 3204.84 | 11383.89 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 17.01 | 0.0000 | Y | 36.34 |
Interior Lighting Total | 4.8362 | 4835.13 | 23383.49 | 81.24 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10348.98 | 2587.24 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10348.98 | 2587.24 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 11383.89 | 2845.97 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 11383.89 | 2845.97 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.29 | 1650.63 | 478.68 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.10 | 1650.63 | 165.06 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 123.84 | AstronomicalClock | - | 41.82 | 41.82 | 0.97 | |
EXTERIOR_LIGHTS_B | 4305.62 | AstronomicalClock | - | 83.82 | 62.82 | 50.78 | |
EXTERIOR_LIGHTS_C | 1091.36 | AstronomicalClock | - | 83.82 | 48.88 | 10.01 | |
Exterior Lighting Total | 5520.82 | 61.76 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:00
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22502.06 | 17152.65 | 5349.41 | 0.76 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 65216.71 | 45722.13 | 19494.58 | 0.70 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 21659.9 | 11.90 | 11.63 | ||||
PSZ-FINE STORAGE COOLING COIL | 63175.3 | 12.06 | 11.79 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 39930.81 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 26400.95 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 81097.21 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.98 | 90.76 | 92.91 | 1.00 | 4.17 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.08 | 1200.53 | 1107.16 | 1.00 | 1.38 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.63 | 2810.24 | 1070.05 | 1.00 | 1.28 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:00
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10968.66 | 13162.39 | 55.57 | 0.904 | 1.084 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 23.90 | 23.90 | 0.00866 | 32.35 | 0.01717 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 34075.85 | 40891.02 | 29.35 | 2.189 | 2.626 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 26.70 | 26.70 | 0.00942 | 33.13 | 0.01717 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 0.00 | 33.93 | 0.01724 | 33.20 | 0.01717 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 6244.77 | 7493.73 | 31.64 | 0.175 | 0.210 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00817 | 8.70 | 0.00699 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 11693.97 | 14032.77 | 10.07 | 0.277 | 0.425 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00749 | 8.70 | 0.00699 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 20474.52 | 24569.42 | 7.67 | 0.501 | 0.977 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00722 | 8.70 | 0.00699 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.08 | 1.08 | 0.21 | 0.21 | 1.0843 | 1.0843 | 1.0843 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.63 | 2.63 | 0.42 | 0.42 | 2.6263 | 2.6263 | 2.6263 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 39930.808 | 39930.808 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 39930.81 | 39930.81 | 0.976836 | 10.00 | 9.55 | 0.00722405 | 43.33 | 22.13 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 10.00 | 0.00722405 | 94.6124 | 24569.42 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 22502.060 | 17152.645 | 1.084330 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 11251.03 | 9034.51 | 0.722887 | 25.60 | 17.74 | 0.00946504 | 12.00 | 11.25 | 0.00800000 | 32.44 | 0.01716576 | 25.13 | 14.1495 | 23.90 | 0.00866278 | 46.8529 | 10966.17 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 26400.952 | 26400.952 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 26400.95 | 26400.95 | 1.084330 | 19.85 | 14.46 | 0.00806296 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 9.4330 | 21.10 | 0.00817442 | 52.4438 | 6244.77 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 65216.710 | 45722.131 | 2.626280 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 32608.35 | 23745.11 | 1.750853 | 28.60 | 19.67 | 0.01067126 | 12.00 | 11.25 | 0.00800000 | 33.13 | 0.01716709 | 25.31 | 24.2574 | 26.70 | 0.00941813 | 43.0777 | 34050.60 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 81097.209 | 81097.209 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 81097.21 | 81097.21 | 2.626277 | 14.45 | 11.67 | 0.00740868 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 16.1716 | 15.56 | 0.00748890 | 68.0995 | 11445.30 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:00
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 39930.808 | 39930.808 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.976836 | 1.17487860 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 39930.81 | 39930.81 | 1.0000 | 1.17487860 | 0.976836 | 10.00 | 9.55 | 0.00722405 | 28249.4 | 43.33 | 22.13 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39930.81 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 10.00 | 0.00722405 | 10.00 | 0.00722405 | 94.6124 | 24569.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22502.060 | 17152.645 | 1.084330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.4350 | 1004.8586 | 1.2027 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.084330 | 1.30416610 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | Sensible | 11251.03 | 9034.51 | 1.0000 | 0.86944394 | 0.722887 | 25.60 | 17.74 | 0.00946504 | 49849.8 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11251.03 | 32.44 | 0.01716576 | 25.13 | 0.10228463 | 14.1495 | 23.90 | 0.00866278 | 23.90 | 0.00866278 | 46.8529 | 10966.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26400.952 | 26400.952 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.084330 | 1.30416610 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 26400.95 | 26400.95 | 1.0000 | 1.30416610 | 1.084330 | 19.85 | 14.46 | 0.00806296 | 40413.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26400.95 | 8.70 | 0.00699286 | 8.70 | 0.10228463 | 9.4330 | 21.02 | 0.00817442 | 21.10 | 0.00817442 | 52.4438 | 6244.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 65216.710 | 45722.131 | 2.626280 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.6773 | 1004.8586 | 1.2027 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.626277 | 3.15872537 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 32608.35 | 23745.11 | 1.0000 | 2.10581947 | 1.750853 | 28.60 | 19.67 | 0.01067126 | 55998.6 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32608.35 | 33.13 | 0.01716709 | 25.31 | 0.42471127 | 24.2574 | 26.70 | 0.00941813 | 26.70 | 0.00941813 | 43.0777 | 34050.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 81097.209 | 81097.209 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.626277 | 3.15872537 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 81097.21 | 81097.21 | 1.0000 | 3.15872537 | 2.626277 | 14.45 | 11.67 | 0.00740868 | 33247.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 81097.21 | 8.70 | 0.00699286 | 8.70 | 0.42471127 | 16.1716 | 15.56 | 0.00748890 | 15.56 | 0.00748890 | 68.0995 | 11445.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:00
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 3149.67 | 870.50 | 586.17 |
ZONE2 FINE STORAGE | 3348.67 | 3198.67 | 2968.00 |
ZONE3 BULK STORAGE | 3372.67 | 3329.33 | 3116.83 |
Facility | 3383.83 | 3422.00 | 3140.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 0.17 | 59.33 | 0.17 | 58.17 |
ZONE2 FINE STORAGE | 0.00 | 186.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.17 | 245.33 | 0.17 | 58.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:00
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.351 | 0.424 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.492 | 0.251 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.60 | 69.00 | 35277.63 | 0.000 | 0.138 | 0.000 | 1.376 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.60 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:00
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.60 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.56 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1261614.49 | 0.00 | 1261614.49 | 2211417.14 | 3473031.64 | 3225648.14 | 5389.43 | 3370.57 | 0.00 | 18.02 |
ZONE2 FINE STORAGE | 5598884.20 | 0.00 | 5598884.20 | 6521899.17 | 12120783.37 | 13393694.68 | 5407.70 | 3352.30 | 0.00 | 1134.02 |
ZONE3 BULK STORAGE | 0.00 | 0.26E+09 | 0.26E+09 | 32858941.69 | 0.30E+09 | 30805497.77 | 6500.98 | 41.86 | 2217.16 | 4867.22 |
Total Facility | 6860498.70 | 0.26E+09 | 0.27E+09 | 41592257.99 | 0.31E+09 | 47424840.58 | 7304.90 | 3404.01 | 2217.16 | 4892.33 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.0963 | 0.0000 | 0.0963 | 0.1163 | 0.2126 | 0.1023 | 265.43 | 3370.57 | 0.00 |
ZONE2 FINE STORAGE | 0.3899 | 0.0000 | 0.3899 | 0.1990 | 0.5890 | 0.4247 | 302.51 | 3333.49 | 0.00 |
ZONE3 BULK STORAGE | 0.0000 | 12.7375 | 12.7375 | 1.2941 | 14.0317 | 0.9768 | 2176.40 | 28.03 | 1431.58 |
Total Facility | 0.4862 | 12.7375 | 13.2238 | 1.6095 | 14.8332 | 1.5038 | 2180.90 | 3371.36 | 1431.58 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 1825033.10 | 0.00 | 1825033.10 | 3225648.14 | 5371.35 | 1.90 | 3386.75 | 17.63 |
PSZ-FINE STORAGE | 8099274.39 | 0.00 | 8099274.39 | 13393694.68 | 5354.01 | 9.25 | 3396.74 | 1133.21 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1393 | 0.0000 | 0.1393 | 0.1023 | 248.44 | 1.74 | 3385.82 |
PSZ-FINE STORAGE | 0.5640 | 0.0000 | 0.5640 | 0.4247 | 301.64 | 0.13 | 3334.23 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 3532.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 4491.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1441 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6107 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:00
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 446 |
Defaulted Fields | 391 |
Fields with Defaults | 1172 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:00
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 434.80 | 1550.86 | 01-JAN-10:10 | 36383.27 | 27-JUL-15:40 |
Electricity:Building | 233.90 | 1069.86 | 01-JAN-10:10 | 19913.95 | 07-NOV-16:00 |
Electricity:Zone:ZONE1 OFFICE | 39.39 | 520.87 | 01-JAN-00:10 | 2846.16 | 27-SEP-07:10 |
Electricity:SpaceType:GENERAL | 217.75 | 1069.86 | 01-JAN-10:10 | 18177.27 | 27-SEP-07:10 |
InteriorLights:Electricity | 81.24 | 599.99 | 01-JAN-10:10 | 8142.10 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.22 | 51.00 | 01-JAN-00:10 | 1011.11 | 27-SEP-07:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 81.24 | 599.99 | 01-JAN-10:10 | 8142.10 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity | 81.24 | 599.99 | 01-JAN-10:10 | 8142.10 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.22 | 51.00 | 01-JAN-00:10 | 1011.11 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 81.24 | 599.99 | 01-JAN-10:10 | 8142.10 | 27-SEP-07:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 34.68 | 287.23 | 05-JUN-17:10 | 3572.81 | 15-MAR-08:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 34.68 | 287.23 | 05-JUN-17:10 | 3572.81 | 15-MAR-08:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 34.68 | 287.23 | 05-JUN-17:10 | 3572.81 | 15-MAR-08:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 159.83 | 249.02 | 01-JAN-10:10 | 13976.01 | 07-NOV-16:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 36.34 | 249.02 | 01-JAN-10:10 | 3735.28 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 36.34 | 249.02 | 01-JAN-10:10 | 3735.28 | 27-SEP-07:10 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 38.56 | 0.00 | 01-JAN-00:10 | 4791.28 | 27-JUL-16:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 16.14 | 0.00 | 01-JAN-00:10 | 2305.29 | 11-APR-10:40 |
Ventilation (simple):Fans:Electricity | 16.14 | 0.00 | 01-JAN-00:10 | 2305.29 | 11-APR-10:40 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 16.14 | 0.00 | 01-JAN-00:10 | 2305.29 | 11-APR-10:40 |
ElectricityPurchased:Facility | 434.80 | 1550.86 | 01-JAN-10:10 | 36383.27 | 27-JUL-15:40 |
ElectricityPurchased:Plant | 434.80 | 1550.86 | 01-JAN-10:10 | 36383.27 | 27-JUL-15:40 |
Cogeneration:ElectricityPurchased | 434.80 | 1550.86 | 01-JAN-10:10 | 36383.27 | 27-JUL-15:40 |
General:Cogeneration:ElectricityPurchased | 434.80 | 1550.86 | 01-JAN-10:10 | 36383.27 | 27-JUL-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 434.80 | 1550.86 | 01-JAN-10:10 | 36383.27 | 27-JUL-15:40 |
ElectricityNet:Plant | 434.80 | 1550.86 | 01-JAN-10:10 | 36383.27 | 27-JUL-15:40 |
Cogeneration:ElectricityNet | 434.80 | 1550.86 | 01-JAN-10:10 | 36383.27 | 27-JUL-15:40 |
General:Cogeneration:ElectricityNet | 434.80 | 1550.86 | 01-JAN-10:10 | 36383.27 | 27-JUL-15:40 |
Electricity:HVAC | 116.40 | 0.00 | 01-JAN-00:10 | 18601.14 | 27-JUL-16:10 |
General:Fans:Electricity | 22.41 | 0.00 | 01-JAN-00:10 | 2485.99 | 27-JUL-16:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 93.99 | 0.00 | 01-JAN-00:10 | 16115.15 | 27-JUL-16:10 |
General:Cooling:Electricity | 93.99 | 0.00 | 01-JAN-00:10 | 16115.15 | 27-JUL-16:10 |
ExteriorLights:Electricity | 61.76 | 0.00 | 01-JAN-07:20 | 5520.82 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 61.76 | 0.00 | 01-JAN-07:20 | 5520.82 | 01-JAN-06:10 |
Electricity:Plant | 22.74 | 481.00 | 10-APR-05:10 | 1739.35 | 24-JAN-12:30 |
WaterSystems:Electricity | 22.74 | 481.00 | 10-APR-05:10 | 1739.35 | 24-JAN-12:30 |
Water Heater:WaterSystems:Electricity | 22.74 | 481.00 | 10-APR-05:10 | 1739.35 | 24-JAN-12:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 0.20 | 0.00 | 01-JAN-00:10 | 7730.39 | 15-DEC-07:20 |
NaturalGas:HVAC | 0.20 | 0.00 | 01-JAN-00:10 | 7730.39 | 15-DEC-07:20 |
Heating:NaturalGas | 0.20 | 0.00 | 01-JAN-00:10 | 7730.39 | 15-DEC-07:20 |
General:Heating:NaturalGas | 0.20 | 0.00 | 01-JAN-00:10 | 7730.39 | 15-DEC-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-APR-11:40 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-APR-11:40 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-APR-11:40 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-APR-11:40 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-APR-11:40 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-APR-11:40 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-APR-11:40 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-APR-11:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 621.56 | 0.00 | 01-JAN-00:10 | 98150.14 | 27-JUL-16:10 |
EnergyTransfer:Building | 226.83 | 0.00 | 01-JAN-00:10 | 36240.99 | 27-JUL-16:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 75.05 | 0.00 | 01-JAN-00:10 | 12372.04 | 11-SEP-05:10 |
Heating:EnergyTransfer | 0.25 | 0.00 | 01-JAN-00:10 | 4177.40 | 15-DEC-07:20 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.10 | 0.00 | 01-JAN-00:10 | 4177.40 | 15-DEC-07:20 |
General:Heating:EnergyTransfer | 0.25 | 0.00 | 01-JAN-00:10 | 4177.40 | 15-DEC-07:20 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.10 | 0.00 | 01-JAN-00:10 | 4177.40 | 15-DEC-07:20 |
Cooling:EnergyTransfer | 226.58 | 0.00 | 01-JAN-00:10 | 36240.99 | 27-JUL-16:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 74.95 | 0.00 | 01-JAN-00:10 | 12372.04 | 11-SEP-05:10 |
General:Cooling:EnergyTransfer | 226.58 | 0.00 | 01-JAN-00:10 | 36240.99 | 27-JUL-16:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 74.95 | 0.00 | 01-JAN-00:10 | 12372.04 | 11-SEP-05:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 151.79 | 0.00 | 01-JAN-00:10 | 26936.48 | 29-MAY-15:40 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.15 | 0.00 | 01-JAN-00:10 | 1449.06 | 08-FEB-12:20 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.15 | 0.00 | 01-JAN-00:10 | 1449.06 | 08-FEB-12:20 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 151.63 | 0.00 | 01-JAN-00:10 | 26936.48 | 29-MAY-15:40 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 151.63 | 0.00 | 01-JAN-00:10 | 26936.48 | 29-MAY-15:40 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 394.72 | 0.00 | 01-JAN-00:10 | 61909.15 | 27-JUL-16:10 |
HeatingCoils:EnergyTransfer | 0.13 | 0.00 | 01-JAN-00:10 | 5190.63 | 15-DEC-07:20 |
CoolingCoils:EnergyTransfer | 394.59 | 0.00 | 01-JAN-00:10 | 61909.15 | 27-JUL-16:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:00
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 0.099 | -74.946 | 0.000 | 0.000 | 9.136 | 10.225 | 29.165 | 10.357 | 0.000 | 5.086 | 18.946 | 0.000 | -3.348 | 0.000 | -4.719 | -0.000 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 0.154 | -151.623 | 0.000 | 0.000 | 17.716 | 34.678 | 0.000 | 34.560 | 0.000 | 5.476 | 86.264 | 0.000 | -8.753 | 0.000 | -18.472 | -0.001 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.746 | 36.340 | 107.344 | 702.837 | 0.000 | 0.445 | 0.011 | 0.000 | -152.261 | 0.000 | -502.825 | -222.626 |
Total Facility | 0.000 | 0.000 | 0.253 | -226.569 | 0.000 | 0.000 | 57.599 | 81.242 | 136.508 | 747.753 | 0.000 | 11.006 | 105.221 | 0.000 | -164.362 | 0.000 | -526.016 | -222.627 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 19-APR-05:02 | 0.00 | 0.00 | 0.00 | -20700.09 | 0.00 | 0.00 | 90.33 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 21227.62 | 0.00 | -498.09 | 0.00 | -721.28 | 0.00 |
ZONE2 FINE STORAGE | 09-APR-16:03 | 0.00 | 0.00 | 0.00 | -55141.60 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 2463.40 | 0.00 | 49.52 | 52328.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 09-AUG-05:03 | 0.00 | 0.00 | 0.00 | -60814.54 | 0.00 | 0.00 | 572.50 | 849.01 | 2600.55 | 0.00 | 0.00 | 13.78 | 80726.99 | 0.00 | -23948.28 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 04-FEB-06:03 | 0.00 | 0.00 | 8948.55 | 0.00 | 0.00 | 0.00 | 123.17 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -717.54 | 0.00 | -1197.80 | -7757.89 |
ZONE2 FINE STORAGE | 15-AUG-06:10 | 0.00 | 0.00 | 1571.62 | 0.00 | 0.00 | 0.00 | 339.77 | 2622.12 | 0.00 | 0.00 | 0.00 | 274.01 | 0.00 | 0.00 | -129.40 | 0.00 | 0.00 | -4678.13 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 04-FEB-06:03 | 0.00 | 0.00 | 8948.55 | 0.00 | 0.00 | 0.00 | 1178.88 | 849.01 | 2600.55 | 0.00 | 0.00 | 0.00 | 58287.13 | 0.00 | -29650.28 | 0.00 | -42213.85 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:00
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0843 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0843 | 0.0943 | 1.0000 | Not calculated | 0.1023 | 0.0943 | ||
PSZ-FINE STORAGE | 2.6263 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.6263 | 0.1617 | 1.0000 | Not calculated | 0.4247 | 0.1617 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0843 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0843 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0943 | ||
PSZ-FINE STORAGE | 2.6263 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.6263 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1617 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0843 | 1.0843 | 1.0843 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6263 | 2.6263 | 2.6263 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0843 | 1.0843 | 1.0843 | 1.0843 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.6263 | 2.6263 | 2.6263 | 2.6263 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0843 | 1.0843 | 1.0843 | No | 0.1023 | 0.4864 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6263 | 2.6263 | 2.6263 | No | 0.4247 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0843 | 1.0843 | 1.0843 | 1.0843 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.6263 | 2.6263 | 2.6263 | 2.6263 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:00
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 0.17 |
Number of hours cooling loads not met | 58.17 |
Number of hours not met | 58.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.20 | 7730.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 93.99 | 16115.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 81.24 | 8142.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 61.76 | 5520.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 16.14 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 22.41 | 2485.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 22.74 | 1739.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 434.80 |
Natural Gas | 0.00 | 0.20 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 435.00 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 16.80 |
Space Heating | 0.00 |
Space Cooling | 19.44 |
Fans (All) | 7.97 |
Service Water Heating | 4.70 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 89.92 |
Subtotal | 89.92 |
Natural Gas [MJ/m2] | |
Space Heating | 0.04 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.04 |
Subtotal | 0.04 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 18.68 |
Space Heating | 0.05 |
Space Cooling | 21.61 |
Fans (All) | 8.86 |
Service Water Heating | 5.23 |
Receptacle Equipment | 31.38 |
Miscellaneous | 14.20 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2729. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:00
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 5424.50 | 3253.83 | 81.67 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 2848.50 | 5911.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 2255.17 | 3361.33 | 3142.67 | 0.83 | 0.00 |
Min | 2255.17 | 3253.83 | 0.00 | 0.00 | 0.00 |
Max | 5424.50 | 5911.50 | 3142.67 | 0.83 | 0.00 |
Average | 3509.39 | 4175.56 | 1074.78 | 0.28 | 0.00 |
Sum | 10528.17 | 12526.67 | 3224.33 | 0.83 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33026.67 | 0.33 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 17391.00 | 65328.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 31697.17 | 74927.00 | 84511.33 | 57.50 | 0.00 |
Min | 17391.00 | 0.33 | 0.00 | 0.00 | 0.00 |
Max | 33026.67 | 74927.00 | 84511.33 | 57.50 | 0.00 |
Average | 27371.61 | 46751.78 | 28170.44 | 19.17 | 0.00 |
Sum | 82114.83 | 140255.33 | 84511.33 | 57.50 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 3898.67 | 4858.17 | 3.17 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 1485.33 | 7274.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 1385.67 | 5808.50 | 1565.83 | 0.00 | 0.00 |
Min | 1385.67 | 4858.17 | 0.00 | 0.00 | 0.00 |
Max | 3898.67 | 7274.67 | 1565.83 | 0.00 | 0.00 |
Average | 2256.56 | 5980.44 | 523.00 | 0.00 | 0.00 |
Sum | 6769.67 | 17941.33 | 1569.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 30029.33 | 2997.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 11135.00 | 71584.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 23069.33 | 116293.67 | 51830.00 | 0.00 | 0.00 |
Min | 11135.00 | 2997.67 | 0.00 | 0.00 | 0.00 |
Max | 30029.33 | 116293.67 | 51830.00 | 0.00 | 0.00 |
Average | 21411.22 | 63625.11 | 17276.67 | 0.00 | 0.00 |
Sum | 64233.67 | 190875.33 | 51830.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:00
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:00
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Environment
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
For: Environment
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.326774E+10 | 15263.49 | 06-JAN-06:02 | 22.80 | 19.86 | 0.628963E+09 | 769.03 | 04-JAN-15:30 | 22.80 | 19.86 |
February | 0.358517E+10 | 17399.86 | 21-FEB-06:02 | 15.60 | 15.30 | 0.580227E+09 | 769.03 | 14-FEB-14:39 | 15.60 | 15.30 |
March | 0.477288E+10 | 16400.82 | 31-MAR-05:01 | 22.20 | 18.84 | 0.681314E+09 | 769.03 | 14-MAR-13:39 | 22.20 | 18.84 |
April | 0.622272E+10 | 20700.36 | 19-APR-05:02 | 15.10 | 11.88 | 0.634964E+09 | 769.06 | 11-APR-15:00 | 15.10 | 11.88 |
May | 0.765724E+10 | 17653.30 | 08-MAY-05:01 | 23.90 | 19.12 | 0.660540E+09 | 769.07 | 16-MAY-14:00 | 30.60 | 21.55 |
June | 0.801269E+10 | 15299.59 | 14-JUN-05:01 | 24.22 | 22.42 | 0.660621E+09 | 769.06 | 03-JUN-13:00 | 24.22 | 22.42 |
July | 0.826504E+10 | 15749.59 | 06-JUL-05:01 | 23.90 | 22.23 | 0.635244E+09 | 769.06 | 08-JUL-13:39 | 31.87 | 24.96 |
August | 0.868512E+10 | 16170.18 | 30-AUG-05:01 | 24.90 | 22.92 | 0.686071E+09 | 769.06 | 30-AUG-14:09 | 30.00 | 23.70 |
September | 0.788758E+10 | 15570.83 | 06-SEP-05:01 | 22.88 | 22.46 | 0.635236E+09 | 769.06 | 23-SEP-14:39 | 30.60 | 24.16 |
October | 0.729935E+10 | 18471.75 | 18-OCT-05:01 | 24.50 | 18.64 | 0.635174E+09 | 769.07 | 07-OCT-15:00 | 24.50 | 18.64 |
November | 0.553587E+10 | 16850.95 | 07-NOV-06:01 | 20.10 | 19.76 | 0.608856E+09 | 769.05 | 10-NOV-14:39 | 28.90 | 24.35 |
December | 0.375725E+10 | 18145.20 | 04-DEC-06:02 | 17.20 | 15.50 | 0.630330E+09 | 769.03 | 11-DEC-09:20 | 22.40 | 19.32 |
Annual Sum or Average | 0.749486E+11 | 0.767754E+10 | ||||||||
Minimum of Months | 0.326774E+10 | 15263.49 | 15.10 | 11.88 | 0.580227E+09 | 769.03 | 15.10 | 11.88 | ||
Maximum of Months | 0.868512E+10 | 20700.36 | 24.90 | 22.92 | 0.686071E+09 | 769.07 | 31.87 | 24.96 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241110E+10 | 21625.54 | 01-JAN-13:35 | 26.47 | 21.74 | 0.166740E+10 | 2246.83 | 09-JAN-14:09 | 21.10 | 14.90 |
February | 0.292003E+10 | 29237.94 | 19-FEB-16:25 | 26.95 | 21.80 | 0.158518E+10 | 2246.89 | 21-FEB-13:30 | 25.00 | 14.70 |
March | 0.553782E+10 | 41164.35 | 28-MAR-17:10 | 25.92 | 20.77 | 0.189331E+10 | 2246.87 | 11-MAR-14:20 | 25.92 | 20.77 |
April | 0.115600E+11 | 55141.95 | 09-APR-16:03 | 27.12 | 18.61 | 0.184595E+10 | 2246.96 | 08-APR-14:20 | 27.12 | 18.61 |
May | 0.173013E+11 | 49101.39 | 20-MAY-17:43 | 28.48 | 21.59 | 0.192801E+10 | 2246.95 | 02-MAY-15:50 | 28.48 | 21.59 |
June | 0.201872E+11 | 48994.26 | 11-JUN-12:23 | 31.65 | 23.57 | 0.192902E+10 | 2247.01 | 10-JUN-15:30 | 31.65 | 23.57 |
July | 0.239097E+11 | 49315.92 | 16-JUL-13:13 | 31.10 | 24.24 | 0.185474E+10 | 2247.01 | 28-JUL-13:00 | 34.40 | 24.35 |
August | 0.214665E+11 | 47226.91 | 20-AUG-16:23 | 30.60 | 24.86 | 0.200317E+10 | 2247.01 | 31-AUG-15:30 | 31.95 | 24.87 |
September | 0.202786E+11 | 49324.97 | 03-SEP-13:53 | 24.40 | 21.27 | 0.185470E+10 | 2247.00 | 20-SEP-15:30 | 31.95 | 24.96 |
October | 0.150486E+11 | 50323.13 | 15-OCT-16:13 | 28.70 | 20.75 | 0.185391E+10 | 2246.95 | 23-OCT-14:50 | 28.40 | 23.14 |
November | 0.705229E+10 | 30289.18 | 19-NOV-13:25 | 26.70 | 21.27 | 0.175278E+10 | 2246.95 | 10-NOV-14:39 | 26.70 | 21.27 |
December | 0.395874E+10 | 44765.16 | 10-DEC-15:33 | 28.50 | 22.56 | 0.168087E+10 | 2246.83 | 12-DEC-14:50 | 18.40 | 12.96 |
Annual Sum or Average | 0.151632E+12 | 0.218490E+11 | ||||||||
Minimum of Months | 0.241110E+10 | 21625.54 | 24.40 | 18.61 | 0.158518E+10 | 2246.83 | 18.40 | 12.96 | ||
Maximum of Months | 0.239097E+11 | 55141.95 | 31.65 | 24.86 | 0.200317E+10 | 2247.01 | 34.40 | 24.96 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 | 19.26 | 0.400534E+10 | 6322.58 | 02-JAN-13:20 | 27.77 | 21.10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 | 13.10 | 0.387591E+10 | 6370.80 | 22-FEB-14:39 | 27.60 | 14.24 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 | 13.44 | 0.480556E+10 | 6376.37 | 28-MAR-15:30 | 26.40 | 20.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 | 18.63 | 0.503616E+10 | 7600.54 | 17-APR-15:20 | 32.03 | 19.94 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 | 20.01 | 0.554713E+10 | 8450.71 | 22-MAY-13:20 | 34.23 | 23.41 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 | 24.42 | 0.566661E+10 | 7570.62 | 10-JUN-15:30 | 31.70 | 24.28 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 | 23.72 | 0.577307E+10 | 9034.37 | 29-JUL-15:00 | 35.60 | 24.39 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 | 25.82 | 0.605122E+10 | 8392.84 | 23-AUG-13:09 | 33.62 | 25.44 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 | 24.00 | 0.550684E+10 | 7768.65 | 13-SEP-14:09 | 32.12 | 24.21 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 | 23.96 | 0.525723E+10 | 7630.87 | 14-OCT-13:30 | 31.95 | 24.19 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 | 21.03 | 0.460820E+10 | 6579.58 | 03-NOV-13:39 | 29.40 | 24.36 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 | 21.22 | 0.412118E+10 | 6387.35 | 02-DEC-14:09 | 26.70 | 20.57 |
Annual Sum or Average | 0.00 | 0.602545E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 16.65 | 13.10 | 0.387591E+10 | 6322.58 | 26.40 | 14.24 | ||
Maximum of Months | 0.00 | 0.00 | 28.60 | 25.82 | 0.605122E+10 | 9034.37 | 35.60 | 25.44 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 27622107.87 | 3270.78 | 25-JAN-07:20 | 9.60 |
February | 15293748.12 | 8948.56 | 04-FEB-06:03 | 5.50 |
March | 26904788.60 | 5624.66 | 16-MAR-06:10 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 944118.46 | 979.42 | 13-NOV-07:30 | 12.50 |
December | 27967747.75 | 5113.23 | 15-DEC-07:10 | 7.88 |
Annual Sum or Average | 98732510.80 | |||
Minimum of Months | 0.00 | 0.00 | 5.50 | |
Maximum of Months | 27967747.75 | 8948.56 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28227639.70 | 1291.89 | 23-JAN-17:10 | 26.32 |
February | 64845728.57 | 1449.06 | 08-FEB-12:20 | 27.40 |
March | 2489839.73 | 440.11 | 18-MAR-17:00 | 25.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 1163425.33 | 759.60 | 20-MAY-06:10 | 25.78 |
June | 1380735.39 | 1257.26 | 23-JUN-06:10 | 26.70 |
July | 625215.07 | 643.73 | 29-JUL-06:10 | 25.68 |
August | 2988790.16 | 1571.16 | 15-AUG-06:10 | 27.38 |
September | 120646.83 | 127.29 | 20-SEP-06:10 | 24.40 |
October | 1046378.40 | 967.77 | 04-OCT-06:10 | 26.20 |
November | 6478955.02 | 590.91 | 28-NOV-17:50 | 25.68 |
December | 44759900.29 | 817.68 | 22-DEC-12:30 | 25.00 |
Annual Sum or Average | 0.154127E+09 | |||
Minimum of Months | 0.00 | 0.00 | 22.57 | |
Maximum of Months | 64845728.57 | 1571.16 | 27.40 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.895057E+09 | 984.24 | 04-JAN-16:00 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.791534E+09 | 957.81 | 07-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.901091E+09 | 972.30 | 14-MAR-07:10 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.834828E+09 | 971.68 | 12-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.857685E+09 | 954.96 | 27-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.854006E+09 | 989.86 | 15-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.811814E+09 | 947.61 | 05-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.874512E+09 | 972.20 | 28-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.834364E+09 | 1011.11 | 27-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.847306E+09 | 990.67 | 31-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.834687E+09 | 980.61 | 24-NOV-08:09 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.887660E+09 | 1001.85 | 15-DEC-16:00 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.102245E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.791534E+09 | 947.61 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.901091E+09 | 1011.11 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.321044E+10 | 3531.05 | 09-JAN-15:00 | 0.00 | 0.00 |
February | 0.277507E+10 | 3426.86 | 25-FEB-09:09 | 0.00 | 0.00 |
March | 0.309354E+10 | 3572.81 | 15-MAR-08:09 | 0.00 | 0.00 |
April | 0.275431E+10 | 3311.00 | 03-APR-08:09 | 0.00 | 0.00 |
May | 0.282241E+10 | 3322.57 | 02-MAY-08:09 | 0.00 | 0.00 |
June | 0.277983E+10 | 3377.58 | 13-JUN-08:09 | 0.00 | 0.00 |
July | 0.265825E+10 | 3232.31 | 25-JUL-08:09 | 0.00 | 0.00 |
August | 0.282609E+10 | 3295.39 | 30-AUG-08:09 | 0.00 | 0.00 |
September | 0.272638E+10 | 3441.86 | 27-SEP-08:09 | 0.00 | 0.00 |
October | 0.292111E+10 | 3512.42 | 25-OCT-08:09 | 0.00 | 0.00 |
November | 0.290522E+10 | 3442.56 | 07-NOV-15:00 | 0.00 | 0.00 |
December | 0.320538E+10 | 3540.18 | 06-DEC-15:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.346780E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.265825E+10 | 3232.31 | 0.00 | 0.00 | |
Maximum of Months | 0.321044E+10 | 3572.81 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.329600E+10 | 3627.73 | 09-JAN-15:00 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.288251E+10 | 3311.03 | 07-FEB-08:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.321309E+10 | 3502.07 | 15-MAR-08:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.288491E+10 | 3154.88 | 12-APR-07:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.293731E+10 | 3041.81 | 06-MAY-07:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.291183E+10 | 3432.75 | 15-JUN-07:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.281995E+10 | 2864.77 | 05-JUL-07:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.301108E+10 | 3164.72 | 28-AUG-07:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.290412E+10 | 3735.28 | 27-SEP-07:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.308219E+10 | 3415.86 | 31-OCT-07:10 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.307337E+10 | 3470.59 | 07-NOV-15:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.332351E+10 | 3638.71 | 06-DEC-15:00 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.363399E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.281995E+10 | 2864.77 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.332351E+10 | 3735.28 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.895057E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53608156.13 | 0.894226E+09 |
February | 0.127628E+10 | 0.791534E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114033E+09 | 0.733995E+09 |
March | 0.149825E+10 | 0.901091E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130225E+09 | 0.849694E+09 |
April | 0.138726E+10 | 0.834828E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283859E+09 | 0.378983E+09 |
May | 0.144276E+10 | 0.857685E+09 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644701E+09 | 0.180760E+09 |
June | 0.144276E+10 | 0.854006E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.704754E+09 | 54491803.54 |
July | 0.138726E+10 | 0.811814E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.774171E+09 | 58821222.60 |
August | 0.149825E+10 | 0.874512E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.846839E+09 | 44161517.05 |
September | 0.138726E+10 | 0.834364E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.660132E+09 | 59213366.67 |
October | 0.138726E+10 | 0.847306E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522100E+09 | 0.135491E+09 |
November | 0.133177E+10 | 0.834687E+09 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287378E+09 | 0.456018E+09 |
December | 0.138726E+10 | 0.887660E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63788788.52 | 0.872959E+09 |
Annual Sum or Average | 0.168137E+11 | 0.102245E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508559E+10 | 0.471881E+10 |
Minimum of Months | 0.127628E+10 | 0.791534E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53608156.13 | 44161517.05 |
Maximum of Months | 0.149825E+10 | 0.901091E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.846839E+09 | 0.894226E+09 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.321044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12832044.46 | 0.261717E+10 |
February | 0.300332E+10 | 0.277507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15965848.45 | 0.314854E+10 |
March | 0.352563E+10 | 0.309354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37883938.75 | 0.348483E+10 |
April | 0.326447E+10 | 0.275431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174553E+09 | 0.196719E+10 |
May | 0.339505E+10 | 0.282241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684124E+09 | 0.936691E+09 |
June | 0.339505E+10 | 0.277983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.921700E+09 | 0.279760E+09 |
July | 0.326447E+10 | 0.265825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.981114E+09 | 0.204017E+09 |
August | 0.352563E+10 | 0.282609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108919E+10 | 0.196874E+09 |
September | 0.326447E+10 | 0.272638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.985618E+09 | 0.295520E+09 |
October | 0.326447E+10 | 0.292111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472794E+09 | 0.644031E+09 |
November | 0.313390E+10 | 0.290522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78757398.06 | 0.203358E+10 |
December | 0.326447E+10 | 0.320538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21186376.85 | 0.266388E+10 |
Annual Sum or Average | 0.395654E+11 | 0.346780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547572E+10 | 0.184721E+11 |
Minimum of Months | 0.300332E+10 | 0.265825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12832044.46 | 0.196874E+09 |
Maximum of Months | 0.352563E+10 | 0.321044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108919E+10 | 0.348483E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.329600E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21731345.86 | 0.132643E+11 |
February | 0.690763E+10 | 0.288251E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28990124.24 | 0.155298E+11 |
March | 0.810895E+10 | 0.321309E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206227E+11 |
April | 0.750829E+10 | 0.288491E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147947E+11 |
May | 0.780862E+10 | 0.293731E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8332275.81 | 0.105417E+11 |
June | 0.780862E+10 | 0.291183E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557195E+10 |
July | 0.750829E+10 | 0.281995E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1594801.84 | 0.400329E+10 |
August | 0.810895E+10 | 0.301108E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 530128.84 | 0.454736E+10 |
September | 0.750829E+10 | 0.290412E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 407650.70 | 0.479423E+10 |
October | 0.750829E+10 | 0.308219E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 707469.45 | 0.729112E+10 |
November | 0.720796E+10 | 0.307337E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124245E+11 |
December | 0.750829E+10 | 0.332351E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16636867.09 | 0.139304E+11 |
Annual Sum or Average | 0.910005E+11 | 0.363399E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 78930663.84 | 0.127316E+12 |
Minimum of Months | 0.690763E+10 | 0.281995E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400329E+10 |
Maximum of Months | 0.810895E+10 | 0.332351E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28990124.24 | 0.206227E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 984.24 | 04-JAN-16:00 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1203.09 | 02-JAN-12:10 | 5074.77 | 25-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 957.81 | 07-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1520.34 | 02-FEB-13:00 | 5189.04 | 03-FEB-07:03 |
March | 1680.92 | 01-MAR-08:09 | 972.30 | 14-MAR-07:10 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2362.13 | 13-MAR-16:50 | 6613.77 | 16-MAR-06:05 |
April | 1680.92 | 01-APR-07:10 | 971.68 | 12-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3004.99 | 17-APR-17:00 | 3220.69 | 19-APR-06:05 |
May | 1680.92 | 01-MAY-07:10 | 954.96 | 27-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3916.88 | 22-MAY-16:10 | 1142.67 | 01-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 989.86 | 15-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2946.52 | 09-JUN-16:10 | 367.19 | 18-JUN-20:00 |
July | 1680.92 | 01-JUL-07:10 | 947.61 | 05-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4529.71 | 27-JUL-16:10 | 419.96 | 14-JUL-17:00 |
August | 1680.92 | 01-AUG-07:10 | 972.20 | 28-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3412.97 | 23-AUG-12:00 | 628.65 | 28-AUG-12:00 |
September | 1680.92 | 01-SEP-07:10 | 1011.11 | 27-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3396.17 | 18-SEP-16:10 | 588.94 | 05-SEP-06:10 |
October | 1680.92 | 02-OCT-07:10 | 990.67 | 31-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3159.52 | 03-OCT-16:10 | 857.98 | 31-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 980.61 | 24-NOV-08:09 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1844.66 | 03-NOV-16:05 | 5227.86 | 27-NOV-07:03 |
December | 1680.92 | 01-DEC-08:09 | 1001.85 | 15-DEC-16:00 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.23 | 08-DEC-13:00 | 5970.71 | 15-DEC-07:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 947.61 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 1203.09 | 367.19 | |||||
Maximum of Months | 1680.92 | 1011.11 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 4529.71 | 6613.77 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3531.05 | 09-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.24 | 29-JAN-12:00 | 6308.58 | 24-JAN-09:00 |
February | 3955.50 | 01-FEB-08:09 | 3426.86 | 25-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.29 | 02-FEB-14:00 | 7506.30 | 03-FEB-09:00 |
March | 3955.50 | 01-MAR-08:09 | 3572.81 | 15-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1740.71 | 13-MAR-17:00 | 8029.99 | 15-MAR-08:00 |
April | 3955.50 | 01-APR-07:10 | 3311.00 | 03-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2837.97 | 15-APR-17:00 | 3897.22 | 18-APR-08:00 |
May | 3955.50 | 01-MAY-07:10 | 3322.57 | 02-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4590.08 | 22-MAY-15:20 | 3096.15 | 10-MAY-15:10 |
June | 3955.50 | 01-JUN-07:10 | 3377.58 | 13-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2397.16 | 08-JUN-16:00 | 1848.35 | 18-JUN-20:00 |
July | 3955.50 | 01-JUL-07:10 | 3232.31 | 25-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3973.78 | 27-JUL-16:00 | 1537.38 | 04-JUL-03:00 |
August | 3955.50 | 01-AUG-07:10 | 3295.39 | 30-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3070.58 | 16-AUG-16:00 | 2143.21 | 12-AUG-08:00 |
September | 3955.50 | 01-SEP-07:10 | 3441.86 | 27-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3068.00 | 18-SEP-16:00 | 1320.86 | 19-SEP-23:10 |
October | 3955.50 | 02-OCT-07:10 | 3512.42 | 25-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3023.61 | 03-OCT-15:10 | 2115.82 | 16-OCT-07:00 |
November | 3955.50 | 01-NOV-07:10 | 3442.56 | 07-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 844.47 | 03-NOV-16:00 | 7611.93 | 11-NOV-09:00 |
December | 3955.50 | 01-DEC-08:09 | 3540.18 | 06-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1246.59 | 10-DEC-14:57 | 7041.67 | 27-DEC-07:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3232.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.29 | 1320.86 | ||||
Maximum of Months | 3955.50 | 3572.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4590.08 | 8029.99 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 3627.73 | 09-JAN-15:00 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1577.95 | 29-JAN-13:00 | 26589.26 | 24-JAN-09:00 |
February | 9097.65 | 01-FEB-08:09 | 3311.03 | 07-FEB-08:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2330.93 | 08-FEB-13:10 | 30524.75 | 03-FEB-09:00 |
March | 9097.65 | 01-MAR-08:09 | 3502.07 | 15-MAR-08:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 36410.27 | 15-MAR-09:00 |
April | 9097.65 | 01-APR-07:10 | 3154.88 | 12-APR-07:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 23379.54 | 18-APR-09:00 |
May | 9097.65 | 01-MAY-07:10 | 3041.81 | 06-MAY-07:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1340.12 | 29-MAY-12:53 | 24875.00 | 10-MAY-15:00 |
June | 9097.65 | 01-JUN-07:10 | 3432.75 | 15-JUN-07:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 18114.48 | 22-JUN-09:00 |
July | 9097.65 | 01-JUL-07:10 | 2864.77 | 05-JUL-07:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 661.51 | 23-JUL-10:53 | 12119.58 | 14-JUL-14:55 |
August | 9097.65 | 01-AUG-07:10 | 3164.72 | 28-AUG-07:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 717.32 | 07-AUG-14:55 | 13370.19 | 12-AUG-08:00 |
September | 9097.65 | 01-SEP-07:10 | 3735.28 | 27-SEP-07:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 352.06 | 07-SEP-18:00 | 10437.84 | 02-SEP-12:00 |
October | 9097.65 | 02-OCT-07:10 | 3415.86 | 31-OCT-07:10 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 581.17 | 09-OCT-10:53 | 14150.93 | 10-OCT-13:00 |
November | 9097.65 | 01-NOV-07:10 | 3470.59 | 07-NOV-15:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 31954.10 | 11-NOV-09:00 |
December | 9097.65 | 01-DEC-08:09 | 3638.71 | 06-DEC-15:00 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1026.15 | 24-DEC-11:00 | 26408.19 | 27-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 2864.77 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10437.84 | |||||
Maximum of Months | 9097.65 | 3735.28 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 2330.93 | 36410.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15263.49 | 06-JAN-06:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.11 |
February | 17399.86 | 21-FEB-06:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 851.89 |
March | 16400.82 | 31-MAR-05:01 | 1294.31 | 356.97 | 3853.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.23 |
April | 20700.36 | 19-APR-05:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 721.28 |
May | 17653.30 | 08-MAY-05:01 | 1664.11 | 458.96 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.95 |
June | 15299.59 | 14-JUN-05:01 | 1664.11 | 458.96 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.38 |
July | 15749.59 | 06-JUL-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.59 |
August | 16170.18 | 30-AUG-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.70 |
September | 15570.83 | 06-SEP-05:01 | 1664.11 | 458.96 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.19 |
October | 18471.75 | 18-OCT-05:01 | 1664.11 | 458.96 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.88 |
November | 16850.95 | 07-NOV-06:01 | 1479.21 | 407.96 | 4404.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.50 |
December | 18145.20 | 04-DEC-06:02 | 1109.41 | 305.97 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 524.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15263.49 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.38 | |
Maximum of Months | 20700.36 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 851.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21625.54 | 01-JAN-13:35 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.88 |
February | 29237.94 | 19-FEB-16:25 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.16 | 0.00 |
March | 41164.35 | 28-MAR-17:10 | 0.00 | 1599.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.44 |
April | 55141.95 | 09-APR-16:03 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.52 | 0.00 |
May | 49101.39 | 20-MAY-17:43 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.48 | 0.00 |
June | 48994.26 | 11-JUN-12:23 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1251.03 | 0.00 |
July | 49315.92 | 16-JUL-13:13 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 845.18 | 0.00 |
August | 47226.91 | 20-AUG-16:23 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 884.83 | 0.00 |
September | 49324.97 | 03-SEP-13:53 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 727.18 |
October | 50323.13 | 15-OCT-16:13 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 605.79 | 0.00 |
November | 30289.18 | 19-NOV-13:25 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.49 |
December | 44765.16 | 10-DEC-15:33 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 707.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 21625.54 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 55141.95 | 0.00 | 1599.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1251.03 | 727.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6347.86 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5472.13 |
April | 0.00 | 01-APR-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5925.94 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4317.62 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2154.78 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1107.47 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 731.87 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2321.04 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 886.27 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5624.08 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2416.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6347.86 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.300624E+11 | 29446.50 | 02-JAN-14:20 | 56336244.47 | 6168.04 | 25-JAN-07:19 |
February | 0.275248E+11 | 29354.37 | 11-FEB-15:20 | 30120482.78 | 5328.14 | 03-FEB-07:19 |
March | 0.319860E+11 | 29136.31 | 27-MAR-15:20 | 55362534.69 | 7004.03 | 16-MAR-06:40 |
April | 0.333452E+11 | 33264.73 | 15-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.387994E+11 | 33729.70 | 22-MAY-15:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.415332E+11 | 35832.89 | 09-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.434496E+11 | 36383.27 | 27-JUL-15:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.441585E+11 | 35352.44 | 22-AUG-12:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.416882E+11 | 34823.94 | 20-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.386727E+11 | 33453.35 | 03-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.325247E+11 | 31655.25 | 07-NOV-15:39 | 3226901.01 | 2338.52 | 13-NOV-07:30 |
December | 0.310528E+11 | 29864.96 | 08-DEC-14:39 | 56067781.21 | 7730.39 | 15-DEC-07:19 |
Annual Sum or Average | 0.434798E+12 | 0.201114E+09 | ||||
Minimum of Months | 0.275248E+11 | 29136.31 | 0.00 | 0.00 | ||
Maximum of Months | 0.441585E+11 | 36383.27 | 56336244.47 | 7730.39 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.740150E+10 | 0.615443E+10 | 0.112984E+11 | 0.00 | 0.161508E+10 | 0.00 | 0.00 | 0.161877E+10 | 0.00 | 0.00 | 0.00 | 0.197425E+10 | 0.00 |
February | 0.644911E+10 | 0.522471E+10 | 0.103734E+11 | 0.00 | 0.150758E+10 | 0.00 | 0.00 | 0.218279E+10 | 0.00 | 0.00 | 0.00 | 0.178725E+10 | 0.00 |
March | 0.720772E+10 | 0.533293E+10 | 0.121089E+11 | 0.00 | 0.182578E+10 | 0.00 | 0.00 | 0.351896E+10 | 0.00 | 0.00 | 0.00 | 0.199171E+10 | 0.00 |
April | 0.647405E+10 | 0.471938E+10 | 0.112578E+11 | 0.00 | 0.245467E+10 | 0.00 | 0.00 | 0.656410E+10 | 0.00 | 0.00 | 0.00 | 0.187519E+10 | 0.00 |
May | 0.661741E+10 | 0.447831E+10 | 0.117000E+11 | 0.00 | 0.374332E+10 | 0.00 | 0.00 | 0.103496E+11 | 0.00 | 0.00 | 0.00 | 0.191078E+10 | 0.00 |
June | 0.654567E+10 | 0.415720E+10 | 0.116594E+11 | 0.00 | 0.487832E+10 | 0.00 | 0.00 | 0.124499E+11 | 0.00 | 0.00 | 0.00 | 0.184276E+10 | 0.00 |
July | 0.629001E+10 | 0.435534E+10 | 0.112984E+11 | 0.00 | 0.547607E+10 | 0.00 | 0.00 | 0.141707E+11 | 0.00 | 0.00 | 0.00 | 0.185911E+10 | 0.00 |
August | 0.671168E+10 | 0.470025E+10 | 0.121016E+11 | 0.00 | 0.518108E+10 | 0.00 | 0.00 | 0.135605E+11 | 0.00 | 0.00 | 0.00 | 0.190343E+10 | 0.00 |
September | 0.646486E+10 | 0.497444E+10 | 0.112504E+11 | 0.00 | 0.478380E+10 | 0.00 | 0.00 | 0.123743E+11 | 0.00 | 0.00 | 0.00 | 0.184050E+10 | 0.00 |
October | 0.685061E+10 | 0.559793E+10 | 0.113057E+11 | 0.00 | 0.349263E+10 | 0.00 | 0.00 | 0.951264E+10 | 0.00 | 0.00 | 0.00 | 0.191315E+10 | 0.00 |
November | 0.681328E+10 | 0.582575E+10 | 0.108562E+11 | 0.00 | 0.192149E+10 | 0.00 | 0.00 | 0.523256E+10 | 0.00 | 0.00 | 0.00 | 0.187550E+10 | 0.00 |
December | 0.741655E+10 | 0.624056E+10 | 0.112984E+11 | 0.00 | 0.167689E+10 | 0.00 | 0.00 | 0.245584E+10 | 0.00 | 0.00 | 0.00 | 0.196456E+10 | 0.00 |
Annual Sum or Average | 0.812424E+11 | 0.617612E+11 | 0.136508E+12 | 0.00 | 0.385567E+11 | 0.00 | 0.00 | 0.939907E+11 | 0.00 | 0.00 | 0.00 | 0.227382E+11 | 0.00 |
Minimum of Months | 0.629001E+10 | 0.415720E+10 | 0.103734E+11 | 0.00 | 0.150758E+10 | 0.00 | 0.00 | 0.161877E+10 | 0.00 | 0.00 | 0.00 | 0.178725E+10 | 0.00 |
Maximum of Months | 0.741655E+10 | 0.624056E+10 | 0.121089E+11 | 0.00 | 0.547607E+10 | 0.00 | 0.00 | 0.141707E+11 | 0.00 | 0.00 | 0.00 | 0.199171E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 56336244.47 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 30120482.78 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 55362534.69 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 3226901.01 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 56067781.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.201114E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 56336244.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 7968.30 | 09-JAN-15:00 | 5520.82 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 3909.60 | 02-JAN-14:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 7568.71 | 25-FEB-09:09 | 5520.82 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 3909.60 | 11-FEB-13:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 8019.39 | 15-MAR-08:09 | 5520.82 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 3964.52 | 13-MAR-16:40 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 7253.26 | 12-APR-07:10 | 5520.82 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 4111.70 | 13-APR-11:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 7121.52 | 06-MAY-07:10 | 5520.82 | 01-MAY-05:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 4285.18 | 22-MAY-15:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 7679.28 | 15-JUN-07:10 | 5520.82 | 01-JUN-05:10 | 10035.17 | 01-JUN-07:10 | 0.00 | 4419.37 | 08-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 6866.54 | 25-JUL-07:10 | 5520.82 | 01-JUL-05:10 | 10035.17 | 01-JUL-07:10 | 0.00 | 4791.28 | 27-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 7267.62 | 28-AUG-07:10 | 5520.82 | 01-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 4546.85 | 16-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 8142.10 | 27-SEP-07:10 | 5520.82 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 4467.39 | 18-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 7794.07 | 25-OCT-08:09 | 5520.82 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 4280.88 | 03-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 7625.34 | 22-NOV-09:09 | 5520.82 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 4037.44 | 03-NOV-11:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 8072.04 | 29-DEC-09:09 | 5520.82 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 3909.60 | 08-DEC-13:39 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 6866.54 | 5520.82 | 10035.17 | 0.00 | 3909.60 | 0.00 | 0.00 | |||||
Maximum of Months | 8142.10 | 5520.82 | 10035.17 | 0.00 | 4791.28 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 8215.63 | 02-JAN-14:39 | 0.00 | 0.00 | 0.00 | 1739.35 | 24-JAN-12:30 | 0.00 |
February | 8328.66 | 11-FEB-14:30 | 0.00 | 0.00 | 0.00 | 1738.53 | 01-FEB-12:00 | 0.00 |
March | 8954.67 | 27-MAR-15:09 | 0.00 | 0.00 | 0.00 | 1733.24 | 01-MAR-12:50 | 0.00 |
April | 12102.51 | 15-APR-15:00 | 0.00 | 0.00 | 0.00 | 1723.03 | 01-APR-11:00 | 0.00 |
May | 13394.14 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 | 1711.51 | 01-MAY-11:09 | 0.00 |
June | 14026.41 | 08-JUN-15:00 | 0.00 | 0.00 | 0.00 | 1700.93 | 01-JUN-11:09 | 0.00 |
July | 16115.15 | 27-JUL-16:10 | 0.00 | 0.00 | 0.00 | 1694.65 | 01-JUL-11:39 | 0.00 |
August | 14690.78 | 16-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1699.34 | 31-AUG-11:30 | 0.00 |
September | 14289.59 | 18-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1708.85 | 30-SEP-11:39 | 0.00 |
October | 12932.73 | 03-OCT-11:39 | 0.00 | 0.00 | 0.00 | 1720.75 | 31-OCT-11:39 | 0.00 |
November | 10368.74 | 10-NOV-13:00 | 0.00 | 0.00 | 0.00 | 1731.38 | 30-NOV-12:50 | 0.00 |
December | 8396.05 | 08-DEC-14:09 | 0.00 | 0.00 | 0.00 | 1737.78 | 30-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8215.63 | 0.00 | 0.00 | 0.00 | 1694.65 | 0.00 | ||
Maximum of Months | 16115.15 | 0.00 | 0.00 | 0.00 | 1739.35 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 29446.50 | 02-JAN-14:20 | 5786.66 | 10035.17 | 0.00 | 0.00 | 3909.60 | 0.00 | 0.00 | 8032.68 | 0.00 |
February | 29354.37 | 11-FEB-15:20 | 5704.80 | 10035.17 | 0.00 | 0.00 | 3909.60 | 0.00 | 0.00 | 7996.50 | 0.00 |
March | 29136.31 | 27-MAR-15:20 | 4653.21 | 10035.17 | 0.00 | 0.00 | 3931.18 | 0.00 | 0.00 | 8933.48 | 0.00 |
April | 33264.73 | 15-APR-15:00 | 5475.50 | 10035.17 | 0.00 | 0.00 | 4069.96 | 0.00 | 0.00 | 12102.51 | 0.00 |
May | 33729.70 | 22-MAY-15:50 | 4442.53 | 10035.17 | 0.00 | 0.00 | 4285.18 | 0.00 | 0.00 | 13388.85 | 0.00 |
June | 35832.89 | 09-JUN-15:00 | 6268.14 | 10035.17 | 0.00 | 0.00 | 4364.75 | 0.00 | 0.00 | 13588.24 | 0.00 |
July | 36383.27 | 27-JUL-15:39 | 4367.11 | 10035.17 | 0.00 | 0.00 | 4687.01 | 0.00 | 0.00 | 15718.78 | 0.00 |
August | 35352.44 | 22-AUG-12:00 | 4815.48 | 10035.17 | 0.00 | 0.00 | 4442.26 | 0.00 | 0.00 | 14384.74 | 0.00 |
September | 34823.94 | 20-SEP-15:00 | 5174.22 | 10035.17 | 0.00 | 0.00 | 4337.39 | 0.00 | 0.00 | 13698.94 | 0.00 |
October | 33453.35 | 03-OCT-15:00 | 5285.64 | 10035.17 | 0.00 | 0.00 | 4116.83 | 0.00 | 0.00 | 12436.29 | 0.00 |
November | 31655.25 | 07-NOV-15:39 | 7425.04 | 10035.17 | 0.00 | 0.00 | 3909.60 | 0.00 | 0.00 | 8588.62 | 0.00 |
December | 29864.96 | 08-DEC-14:39 | 6035.79 | 10035.17 | 0.00 | 0.00 | 3909.60 | 0.00 | 0.00 | 8295.84 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 29136.31 | 4367.11 | 10035.17 | 0.00 | 0.00 | 3909.60 | 0.00 | 0.00 | 7996.50 | 0.00 | |
Maximum of Months | 36383.27 | 7425.04 | 10035.17 | 0.00 | 0.00 | 4687.01 | 0.00 | 0.00 | 15718.78 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 6168.04 | 25-JAN-07:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 5328.14 | 03-FEB-07:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 7004.03 | 16-MAR-06:40 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 2338.52 | 13-NOV-07:30 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 7730.39 | 15-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 7730.39 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.49 | 0.50 | 24.49 |
February | 0.17 | 20.54 | 0.17 | 20.54 | 0.33 | 22.56 | 0.33 | 23.23 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.58 | 0.33 | 24.58 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.89 | 3.00 | 24.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 24.83 | 7.83 | 24.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 24.94 | 8.33 | 24.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 25.20 | 8.50 | 25.11 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 25.11 | 8.50 | 25.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 25.06 | 8.50 | 25.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 24.92 | 8.17 | 24.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.64 | 3.00 | 24.64 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.59 | 1.17 | 24.59 |
Annual Sum or Average | 0.17 | 20.54 | 0.17 | 20.54 | 59.33 | 24.95 | 58.17 | 24.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.56 | 0.33 | 23.23 |
Maximum of Months | 0.17 | 20.54 | 0.17 | 20.54 | 8.83 | 25.20 | 8.50 | 25.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.00 | 27.27 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.30 | 0.00 | 27.30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.31 | 0.00 | 27.31 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.42 | 0.00 | 27.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 27.40 | 0.00 | 27.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 27.42 | 0.00 | 27.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 38.00 | 27.51 | 0.00 | 27.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 27.45 | 0.00 | 27.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 27.48 | 0.00 | 27.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 27.41 | 0.00 | 27.41 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.33 | 0.00 | 27.33 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.37 | 0.00 | 27.37 |
Annual Sum or Average | 0.00 | 0.00 | 186.00 | 27.44 | 0.00 | 27.44 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.00 | 27.27 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 38.00 | 27.51 | 0.00 | 27.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 108.67 | 23.35 | 152.50 | 23.67 | 18.33 | 23.69 |
February | 86.17 | 23.46 | 189.67 | 23.74 | 29.83 | 23.73 |
March | 87.83 | 23.45 | 226.83 | 23.78 | 28.33 | 23.79 |
April | 15.83 | 24.00 | 293.67 | 23.92 | 15.00 | 23.92 |
May | 50.83 | 24.04 | 312.00 | 23.94 | 50.83 | 23.95 |
June | 81.00 | 24.04 | 312.00 | 23.96 | 81.00 | 23.97 |
July | 73.17 | 24.05 | 300.00 | 23.96 | 73.17 | 23.97 |
August | 86.17 | 24.04 | 324.00 | 23.96 | 86.17 | 23.97 |
September | 72.83 | 24.05 | 300.00 | 23.96 | 72.83 | 23.97 |
October | 56.83 | 24.03 | 300.00 | 23.95 | 56.83 | 23.96 |
November | 56.33 | 23.82 | 267.17 | 23.90 | 47.33 | 23.91 |
December | 94.83 | 23.41 | 171.83 | 23.73 | 26.50 | 23.74 |
Annual Sum or Average | 870.50 | 23.76 | 3149.67 | 23.89 | 586.17 | 23.90 |
Minimum of Months | 15.83 | 23.35 | 152.50 | 23.67 | 15.00 | 23.69 |
Maximum of Months | 108.67 | 24.05 | 324.00 | 23.96 | 86.17 | 23.97 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 194.83 | 24.70 | 214.17 | 25.26 | 125.50 | 25.39 |
February | 202.67 | 25.21 | 220.67 | 25.63 | 156.50 | 25.71 |
March | 238.83 | 25.71 | 269.67 | 26.03 | 195.00 | 26.15 |
April | 267.83 | 26.65 | 300.00 | 26.61 | 267.83 | 26.62 |
May | 309.67 | 26.70 | 312.00 | 26.70 | 309.67 | 26.70 |
June | 312.00 | 26.72 | 312.00 | 26.72 | 312.00 | 26.72 |
July | 300.00 | 26.72 | 300.00 | 26.72 | 300.00 | 26.72 |
August | 323.33 | 26.72 | 324.00 | 26.72 | 323.33 | 26.72 |
September | 300.00 | 26.72 | 300.00 | 26.72 | 300.00 | 26.72 |
October | 294.17 | 26.70 | 300.00 | 26.70 | 294.17 | 26.70 |
November | 246.50 | 26.43 | 276.17 | 26.47 | 237.67 | 26.50 |
December | 208.83 | 25.07 | 220.00 | 25.52 | 146.33 | 25.67 |
Annual Sum or Average | 3198.67 | 26.28 | 3348.67 | 26.39 | 2968.00 | 26.45 |
Minimum of Months | 194.83 | 24.70 | 214.17 | 25.26 | 125.50 | 25.39 |
Maximum of Months | 323.33 | 26.72 | 324.00 | 26.72 | 323.33 | 26.72 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 199.17 | 25.24 | 219.83 | 25.80 | 135.67 | 25.98 |
February | 242.00 | 26.15 | 222.50 | 26.46 | 196.67 | 26.61 |
March | 261.83 | 27.17 | 281.00 | 27.37 | 226.33 | 27.54 |
April | 287.67 | 28.93 | 300.00 | 28.88 | 287.67 | 28.89 |
May | 312.00 | 29.70 | 312.00 | 29.70 | 312.00 | 29.70 |
June | 312.00 | 30.11 | 312.00 | 30.11 | 312.00 | 30.11 |
July | 300.00 | 30.93 | 300.00 | 30.93 | 300.00 | 30.93 |
August | 324.00 | 30.49 | 324.00 | 30.49 | 324.00 | 30.49 |
September | 300.00 | 30.24 | 300.00 | 30.24 | 300.00 | 30.24 |
October | 300.00 | 29.50 | 300.00 | 29.50 | 300.00 | 29.50 |
November | 262.00 | 28.24 | 277.17 | 28.24 | 253.17 | 28.30 |
December | 228.67 | 25.99 | 224.17 | 26.37 | 169.33 | 26.59 |
Annual Sum or Average | 3329.33 | 28.80 | 3372.67 | 28.88 | 3116.83 | 28.99 |
Minimum of Months | 199.17 | 25.24 | 219.83 | 25.80 | 135.67 | 25.98 |
Maximum of Months | 324.00 | 30.93 | 324.00 | 30.93 | 324.00 | 30.93 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.471681E+10 | 0.110541E+10 | 240.77 | 0.340266E+10 | 0.131415E+10 | 0.00 | 1.00 | 02-JAN-06:02 | 0.00 | 01-JAN-00:10 | 28133.25 | 07-JAN-06:02 | 17091.24 | 06-JAN-06:02 | 14155.39 | 07-JAN-06:03 | 5807.87 | 07-JAN-06:02 | 0.00 | 01-JAN-00:10 |
February | 0.535223E+10 | 0.125281E+10 | 232.31 | 0.393989E+10 | 0.141234E+10 | 0.00 | 1.00 | 02-FEB-06:03 | 0.00 | 01-FEB-00:10 | 28192.19 | 11-FEB-06:02 | 18529.83 | 21-FEB-06:02 | 14290.61 | 11-FEB-06:02 | 5815.47 | 11-FEB-06:02 | 0.00 | 01-FEB-00:10 |
March | 0.722072E+10 | 0.166325E+10 | 283.07 | 0.513336E+10 | 0.208736E+10 | 0.00 | 1.00 | 03-MAR-06:03 | 0.00 | 01-MAR-00:10 | 28650.51 | 06-MAR-06:01 | 17826.51 | 31-MAR-05:01 | 14767.52 | 06-MAR-06:01 | 5868.24 | 06-MAR-06:01 | 0.00 | 01-MAR-00:10 |
April | 0.955227E+10 | 0.220630E+10 | 291.47 | 0.692127E+10 | 0.263101E+10 | 0.00 | 1.00 | 01-APR-05:01 | 0.00 | 01-APR-00:10 | 28511.62 | 13-APR-05:01 | 22063.26 | 19-APR-05:02 | 13418.37 | 13-APR-05:04 | 5876.28 | 13-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.128965E+11 | 0.298972E+10 | 307.95 | 0.873887E+10 | 0.415767E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 29284.95 | 30-MAY-05:01 | 19069.41 | 08-MAY-05:01 | 16224.09 | 27-MAY-05:02 | 5955.78 | 27-MAY-05:01 | 0.00 | 01-MAY-00:10 |
June | 0.145152E+11 | 0.334820E+10 | 308.51 | 0.923216E+10 | 0.528303E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 29239.11 | 19-JUN-05:02 | 16652.49 | 17-JUN-05:01 | 15472.39 | 19-JUN-05:04 | 6063.69 | 08-JUN-05:01 | 0.00 | 01-JUN-00:10 |
July | 0.148964E+11 | 0.351193E+10 | 301.54 | 0.966493E+10 | 0.523152E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 29263.89 | 24-JUL-05:01 | 16955.93 | 06-JUL-05:01 | 14602.25 | 31-JUL-05:05 | 6011.58 | 10-JUL-05:01 | 0.00 | 01-JUL-00:10 |
August | 0.158203E+11 | 0.369127E+10 | 322.14 | 0.100822E+11 | 0.573810E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 29366.91 | 14-AUG-05:02 | 17538.82 | 30-AUG-05:01 | 15870.46 | 28-AUG-05:06 | 6046.81 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.141283E+11 | 0.327371E+10 | 300.48 | 0.908732E+10 | 0.504100E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 29117.78 | 25-SEP-05:01 | 16734.32 | 06-SEP-05:01 | 15633.13 | 23-SEP-05:06 | 6045.23 | 22-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 0.125251E+11 | 0.288692E+10 | 295.70 | 0.832366E+10 | 0.420139E+10 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 29000.60 | 10-OCT-05:01 | 20001.45 | 18-OCT-05:01 | 16767.71 | 30-OCT-05:09 | 6022.03 | 30-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.927879E+10 | 0.212303E+10 | 272.21 | 0.618740E+10 | 0.309139E+10 | 0.00 | 1.00 | 01-NOV-05:01 | 0.00 | 01-NOV-00:10 | 29064.18 | 04-NOV-05:01 | 18185.70 | 28-NOV-06:03 | 16372.88 | 30-NOV-06:04 | 5979.16 | 30-NOV-06:01 | 0.00 | 01-NOV-00:10 |
December | 0.553642E+10 | 0.128388E+10 | 249.39 | 0.395388E+10 | 0.158254E+10 | 0.00 | 1.00 | 01-DEC-06:01 | 0.00 | 01-DEC-00:10 | 28750.38 | 11-DEC-06:01 | 19256.93 | 04-DEC-06:02 | 14698.71 | 26-DEC-06:02 | 5889.67 | 09-DEC-06:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.126439E+12 | 0.293364E+11 | 3405.54 | 0.846676E+11 | 0.417715E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.471681E+10 | 0.110541E+10 | 232.31 | 0.340266E+10 | 0.131415E+10 | 0.00 | 1.00 | 0.00 | 28133.25 | 16652.49 | 13418.37 | 5807.87 | 0.00 | |||||||
Maximum of Months | 0.158203E+11 | 0.369127E+10 | 322.14 | 0.100822E+11 | 0.573810E+10 | 0.00 | 1.00 | 0.00 | 29366.91 | 22063.26 | 16767.71 | 6063.69 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.207998E+10 | 0.513364E+09 | 71.75 | 0.125382E+10 | 0.826160E+09 | 0.00 | 0.97 | 01-JAN-13:35 | 0.00 | 01-JAN-00:10 | 35874.38 | 01-JAN-13:35 | 23213.04 | 01-JAN-13:35 | 12806.83 | 01-JAN-12:20 | 8070.80 | 01-JAN-13:35 | 0.00 | 01-JAN-00:10 |
February | 0.372896E+10 | 0.929980E+09 | 130.75 | 0.261272E+10 | 0.111624E+10 | 0.00 | 1.00 | 19-FEB-13:05 | 0.00 | 01-FEB-00:10 | 51096.32 | 19-FEB-13:45 | 31904.93 | 19-FEB-16:25 | 20538.21 | 19-FEB-13:45 | 11380.71 | 19-FEB-13:45 | 0.00 | 01-FEB-00:10 |
March | 0.764003E+10 | 0.185571E+10 | 179.37 | 0.484292E+10 | 0.279711E+10 | 0.00 | 1.00 | 05-MAR-11:35 | 0.00 | 01-MAR-00:10 | 65210.27 | 27-MAR-17:10 | 44534.17 | 28-MAR-17:10 | 23779.08 | 05-MAR-11:35 | 14547.78 | 27-MAR-17:10 | 0.00 | 01-MAR-00:10 |
April | 0.179707E+11 | 0.435780E+10 | 295.60 | 0.122181E+11 | 0.575260E+10 | 0.00 | 1.00 | 01-APR-17:08 | 0.00 | 01-APR-00:10 | 75519.73 | 13-APR-17:43 | 59850.13 | 09-APR-16:03 | 28587.84 | 01-APR-17:08 | 17192.87 | 15-APR-17:08 | 0.00 | 01-APR-00:10 |
May | 0.304692E+11 | 0.735987E+10 | 402.70 | 0.194298E+11 | 0.110394E+11 | 0.00 | 1.00 | 01-MAY-17:08 | 0.00 | 01-MAY-00:10 | 78527.55 | 20-MAY-05:06 | 54133.41 | 20-MAY-17:43 | 33729.83 | 20-MAY-05:06 | 17927.01 | 29-MAY-12:53 | 0.00 | 01-MAY-00:10 |
June | 0.380177E+11 | 0.910169E+10 | 469.48 | 0.229100E+11 | 0.151078E+11 | 0.00 | 1.00 | 01-JUN-00:23 | 0.00 | 01-JUN-00:10 | 79724.31 | 08-JUN-05:10 | 54119.13 | 11-JUN-13:43 | 37971.85 | 08-JUN-05:10 | 17665.44 | 08-JUN-05:10 | 0.00 | 01-JUN-00:10 |
July | 0.440228E+11 | 0.106588E+11 | 502.98 | 0.275303E+11 | 0.164925E+11 | 0.00 | 1.00 | 01-JUL-12:10 | 0.00 | 01-JUL-00:10 | 78927.54 | 26-JUL-05:01 | 53839.98 | 16-JUL-13:13 | 34510.88 | 26-JUL-05:01 | 17896.33 | 27-JUL-17:06 | 0.00 | 01-JUL-00:10 |
August | 0.410821E+11 | 0.986926E+10 | 494.71 | 0.246937E+11 | 0.163884E+11 | 0.00 | 1.00 | 01-AUG-00:30 | 0.00 | 01-AUG-00:15 | 79424.51 | 05-AUG-05:09 | 53209.95 | 06-AUG-13:32 | 36225.84 | 18-AUG-05:09 | 17896.18 | 20-AUG-11:43 | 0.00 | 01-AUG-00:10 |
September | 0.378982E+11 | 0.910055E+10 | 461.39 | 0.230430E+11 | 0.148552E+11 | 0.00 | 1.00 | 01-SEP-05:40 | 0.00 | 01-SEP-00:15 | 79523.36 | 23-SEP-05:09 | 53564.37 | 04-SEP-11:03 | 37109.62 | 22-SEP-05:09 | 17725.45 | 18-SEP-17:06 | 0.00 | 01-SEP-00:10 |
October | 0.275052E+11 | 0.662572E+10 | 376.04 | 0.169834E+11 | 0.105217E+11 | 0.00 | 1.00 | 01-OCT-10:00 | 0.00 | 01-OCT-00:15 | 83265.12 | 04-OCT-05:01 | 55533.59 | 15-OCT-16:13 | 44889.11 | 04-OCT-05:01 | 17708.25 | 29-OCT-11:33 | 0.00 | 01-OCT-00:10 |
November | 0.129017E+11 | 0.310953E+10 | 231.89 | 0.759135E+10 | 0.531032E+10 | 0.00 | 1.00 | 03-NOV-17:12 | 0.00 | 01-NOV-00:10 | 60514.37 | 23-NOV-11:45 | 32958.26 | 19-NOV-13:25 | 29453.72 | 05-NOV-11:35 | 13268.91 | 23-NOV-11:45 | 0.00 | 01-NOV-00:10 |
December | 0.483437E+10 | 0.117196E+10 | 107.22 | 0.301998E+10 | 0.181439E+10 | 0.00 | 1.00 | 03-DEC-12:32 | 0.00 | 01-DEC-00:10 | 74516.30 | 10-DEC-14:13 | 49681.59 | 10-DEC-15:33 | 25960.83 | 10-DEC-14:13 | 17172.08 | 10-DEC-14:13 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.268151E+12 | 0.646542E+11 | 3723.87 | 0.166129E+12 | 0.102022E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.207998E+10 | 0.513364E+09 | 71.75 | 0.125382E+10 | 0.826160E+09 | 0.00 | 0.97 | 0.00 | 35874.38 | 23213.04 | 12806.83 | 8070.80 | 0.00 | |||||||
Maximum of Months | 0.440228E+11 | 0.106588E+11 | 502.98 | 0.275303E+11 | 0.164925E+11 | 0.00 | 1.00 | 0.00 | 83265.12 | 59850.13 | 44889.11 | 17927.01 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 53.47 | 23.17 | 30.30 | 78.23 | 63.16 | 0.00 | 0.00 | 0.00 |
February | 66.74 | 30.30 | 36.43 | 109.34 | 52.34 | 0.00 | 0.00 | 0.00 |
March | 83.07 | 38.00 | 45.07 | 135.38 | 45.97 | 0.00 | 0.00 | 0.00 |
April | 90.98 | 42.02 | 48.96 | 159.45 | 35.77 | 0.00 | 0.00 | 0.00 |
May | 83.31 | 32.16 | 51.15 | 158.62 | 22.35 | 0.00 | 0.00 | 0.00 |
June | 70.55 | 19.82 | 50.73 | 140.54 | 13.07 | 0.00 | 0.00 | 0.00 |
July | 78.78 | 24.42 | 54.36 | 161.84 | 17.30 | 0.00 | 0.00 | 0.00 |
August | 78.54 | 25.55 | 52.99 | 154.73 | 15.02 | 0.00 | 0.00 | 0.00 |
September | 66.97 | 19.77 | 47.21 | 134.54 | 18.30 | 0.00 | 0.00 | 0.00 |
October | 66.60 | 25.97 | 40.63 | 125.26 | 27.32 | 0.00 | 0.00 | 0.00 |
November | 54.89 | 20.08 | 34.81 | 94.24 | 39.65 | 0.00 | 0.00 | 0.00 |
December | 55.17 | 24.72 | 30.45 | 85.67 | 55.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 70.79 | 27.16 | 43.63 | 128.26 | 33.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.47 | 19.77 | 30.30 | 78.23 | 13.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.98 | 42.02 | 54.36 | 161.84 | 63.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 53.47 | 23.17 | 30.30 | 78.23 | 63.16 | 0.00 | 0.00 | 0.00 |
February | 66.74 | 30.30 | 36.43 | 109.34 | 52.34 | 0.00 | 0.00 | 0.00 |
March | 83.07 | 38.00 | 45.07 | 135.38 | 45.97 | 0.00 | 0.00 | 0.00 |
April | 90.98 | 42.02 | 48.96 | 159.45 | 35.77 | 0.00 | 0.00 | 0.00 |
May | 83.31 | 32.16 | 51.15 | 158.62 | 22.35 | 0.00 | 0.00 | 0.00 |
June | 70.55 | 19.82 | 50.73 | 140.54 | 13.07 | 0.00 | 0.00 | 0.00 |
July | 78.78 | 24.42 | 54.36 | 161.84 | 17.30 | 0.00 | 0.00 | 0.00 |
August | 78.54 | 25.55 | 52.99 | 154.73 | 15.02 | 0.00 | 0.00 | 0.00 |
September | 66.97 | 19.77 | 47.21 | 134.54 | 18.30 | 0.00 | 0.00 | 0.00 |
October | 66.60 | 25.97 | 40.63 | 125.26 | 27.32 | 0.00 | 0.00 | 0.00 |
November | 54.89 | 20.08 | 34.81 | 94.24 | 39.65 | 0.00 | 0.00 | 0.00 |
December | 55.17 | 24.72 | 30.45 | 85.67 | 55.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 70.79 | 27.16 | 43.63 | 128.26 | 33.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.47 | 19.77 | 30.30 | 78.23 | 13.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.98 | 42.02 | 54.36 | 161.84 | 63.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.34 | 0.00 | 14.34 | 14.36 | 37.93 | 0.00 | 0.00 | 0.00 |
February | 16.98 | 0.00 | 16.98 | 22.22 | 31.02 | 0.00 | 0.00 | 0.00 |
March | 20.26 | 0.00 | 20.26 | 26.24 | 27.43 | 0.00 | 0.00 | 0.00 |
April | 22.74 | 0.13 | 22.61 | 35.67 | 20.89 | 0.00 | 0.00 | 0.00 |
May | 25.81 | 1.04 | 24.77 | 49.59 | 12.64 | 0.00 | 0.00 | 0.00 |
June | 27.63 | 1.93 | 25.70 | 56.90 | 7.10 | 0.00 | 0.00 | 0.00 |
July | 27.95 | 1.30 | 26.65 | 60.41 | 9.85 | 0.00 | 0.00 | 0.00 |
August | 24.86 | 0.28 | 24.58 | 50.45 | 8.55 | 0.00 | 0.00 | 0.00 |
September | 22.00 | 0.00 | 22.00 | 45.50 | 10.48 | 0.00 | 0.00 | 0.00 |
October | 18.42 | 0.00 | 18.42 | 34.00 | 15.80 | 0.00 | 0.00 | 0.00 |
November | 16.02 | 0.00 | 16.02 | 24.04 | 23.16 | 0.00 | 0.00 | 0.00 |
December | 14.19 | 0.00 | 14.19 | 16.08 | 33.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20.95 | 0.39 | 20.56 | 36.36 | 19.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.19 | 0.00 | 14.19 | 14.36 | 7.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 27.95 | 1.93 | 26.65 | 60.41 | 37.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.34 | 0.00 | 14.34 | 14.36 | 37.93 | 0.00 | 0.00 | 0.00 |
February | 16.98 | 0.00 | 16.98 | 22.22 | 31.02 | 0.00 | 0.00 | 0.00 |
March | 20.26 | 0.00 | 20.25 | 26.24 | 27.42 | 0.00 | 0.00 | 0.00 |
April | 22.74 | 0.13 | 22.61 | 35.67 | 20.89 | 0.00 | 0.00 | 0.00 |
May | 25.81 | 1.04 | 24.77 | 49.58 | 12.64 | 0.00 | 0.00 | 0.00 |
June | 27.63 | 1.93 | 25.70 | 56.90 | 7.10 | 0.00 | 0.00 | 0.00 |
July | 27.94 | 1.30 | 26.65 | 60.41 | 9.85 | 0.00 | 0.00 | 0.00 |
August | 24.86 | 0.28 | 24.58 | 50.45 | 8.55 | 0.00 | 0.00 | 0.00 |
September | 22.00 | 0.00 | 21.99 | 45.50 | 10.48 | 0.00 | 0.00 | 0.00 |
October | 18.42 | 0.00 | 18.42 | 34.00 | 15.80 | 0.00 | 0.00 | 0.00 |
November | 16.02 | 0.00 | 16.02 | 24.04 | 23.16 | 0.00 | 0.00 | 0.00 |
December | 14.19 | 0.00 | 14.19 | 16.08 | 33.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20.95 | 0.39 | 20.56 | 36.36 | 19.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.19 | 0.00 | 14.19 | 14.36 | 7.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 27.94 | 1.93 | 26.65 | 60.41 | 37.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 19.37 | 12.82 | 48.50 | 30.96 | 0.17 | 0.00 | 0.00 |
February | 39.56 | 24.10 | 15.46 | 63.24 | 26.71 | 0.00 | 0.00 | 0.00 |
March | 49.51 | 30.24 | 19.27 | 79.12 | 24.35 | 0.83 | 0.00 | 0.00 |
April | 57.77 | 36.02 | 21.76 | 96.74 | 21.33 | 0.00 | 0.00 | 0.00 |
May | 57.08 | 32.28 | 24.81 | 99.40 | 15.24 | 0.00 | 0.00 | 0.00 |
June | 54.24 | 27.26 | 26.98 | 96.21 | 11.57 | 0.00 | 0.00 | 0.00 |
July | 59.12 | 31.16 | 27.95 | 107.20 | 13.17 | 0.00 | 0.00 | 0.00 |
August | 53.71 | 26.75 | 26.96 | 93.77 | 12.38 | 0.00 | 0.00 | 0.00 |
September | 47.29 | 23.16 | 24.13 | 84.60 | 13.65 | 0.00 | 0.00 | 0.00 |
October | 41.48 | 23.23 | 18.25 | 70.79 | 19.18 | 0.00 | 0.00 | 0.00 |
November | 32.98 | 17.14 | 15.84 | 53.29 | 23.21 | 0.00 | 0.00 | 0.00 |
December | 29.47 | 16.14 | 13.34 | 45.59 | 26.53 | 18.17 | 0.00 | 0.00 |
Annual Sum or Average | 46.24 | 25.58 | 20.66 | 78.28 | 19.83 | 19.17 | 0.00 | 0.00 |
Minimum of Months | 29.47 | 16.14 | 12.82 | 45.59 | 11.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.12 | 36.02 | 27.95 | 107.20 | 30.96 | 18.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 19.37 | 12.82 | 48.50 | 30.96 | 0.17 | 0.00 | 0.00 |
February | 39.56 | 24.10 | 15.46 | 63.24 | 26.71 | 0.00 | 0.00 | 0.00 |
March | 49.51 | 30.24 | 19.27 | 79.12 | 24.35 | 0.83 | 0.00 | 0.00 |
April | 57.77 | 36.02 | 21.76 | 96.74 | 21.33 | 0.00 | 0.00 | 0.00 |
May | 57.08 | 32.28 | 24.81 | 99.40 | 15.24 | 0.00 | 0.00 | 0.00 |
June | 54.24 | 27.26 | 26.98 | 96.21 | 11.57 | 0.00 | 0.00 | 0.00 |
July | 59.12 | 31.16 | 27.95 | 107.20 | 13.17 | 0.00 | 0.00 | 0.00 |
August | 53.71 | 26.75 | 26.96 | 93.77 | 12.38 | 0.00 | 0.00 | 0.00 |
September | 47.29 | 23.16 | 24.13 | 84.60 | 13.65 | 0.00 | 0.00 | 0.00 |
October | 41.48 | 23.23 | 18.25 | 70.79 | 19.18 | 0.00 | 0.00 | 0.00 |
November | 32.98 | 17.14 | 15.84 | 53.29 | 23.21 | 0.00 | 0.00 | 0.00 |
December | 29.47 | 16.14 | 13.34 | 45.59 | 26.53 | 18.17 | 0.00 | 0.00 |
Annual Sum or Average | 46.24 | 25.58 | 20.66 | 78.28 | 19.83 | 19.17 | 0.00 | 0.00 |
Minimum of Months | 29.47 | 16.14 | 12.82 | 45.59 | 11.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.12 | 36.02 | 27.95 | 107.20 | 30.96 | 18.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 19.37 | 12.82 | 48.50 | 30.96 | 0.17 | 0.00 | 0.00 |
February | 39.56 | 24.10 | 15.46 | 63.24 | 26.71 | 0.00 | 0.00 | 0.00 |
March | 49.51 | 30.24 | 19.27 | 79.12 | 24.35 | 0.83 | 0.00 | 0.00 |
April | 57.77 | 36.02 | 21.76 | 96.74 | 21.33 | 0.00 | 0.00 | 0.00 |
May | 57.08 | 32.28 | 24.81 | 99.40 | 15.24 | 0.00 | 0.00 | 0.00 |
June | 54.24 | 27.26 | 26.98 | 96.21 | 11.57 | 0.00 | 0.00 | 0.00 |
July | 59.12 | 31.16 | 27.95 | 107.20 | 13.17 | 0.00 | 0.00 | 0.00 |
August | 53.71 | 26.75 | 26.96 | 93.77 | 12.38 | 0.00 | 0.00 | 0.00 |
September | 47.29 | 23.16 | 24.13 | 84.60 | 13.65 | 0.00 | 0.00 | 0.00 |
October | 41.48 | 23.23 | 18.25 | 70.79 | 19.18 | 0.00 | 0.00 | 0.00 |
November | 32.98 | 17.14 | 15.84 | 53.29 | 23.21 | 0.00 | 0.00 | 0.00 |
December | 29.47 | 16.14 | 13.34 | 45.59 | 26.53 | 18.17 | 0.00 | 0.00 |
Annual Sum or Average | 46.24 | 25.58 | 20.66 | 78.28 | 19.83 | 19.17 | 0.00 | 0.00 |
Minimum of Months | 29.47 | 16.14 | 12.82 | 45.59 | 11.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.12 | 36.02 | 27.95 | 107.20 | 30.96 | 18.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 19.37 | 12.82 | 48.50 | 30.96 | 0.17 | 0.00 | 0.00 |
February | 39.56 | 24.10 | 15.46 | 63.24 | 26.71 | 0.00 | 0.00 | 0.00 |
March | 49.51 | 30.24 | 19.27 | 79.12 | 24.35 | 0.83 | 0.00 | 0.00 |
April | 57.77 | 36.02 | 21.76 | 96.74 | 21.33 | 0.00 | 0.00 | 0.00 |
May | 57.08 | 32.28 | 24.81 | 99.40 | 15.24 | 0.00 | 0.00 | 0.00 |
June | 54.24 | 27.26 | 26.98 | 96.21 | 11.57 | 0.00 | 0.00 | 0.00 |
July | 59.12 | 31.16 | 27.95 | 107.20 | 13.17 | 0.00 | 0.00 | 0.00 |
August | 53.71 | 26.75 | 26.96 | 93.77 | 12.38 | 0.00 | 0.00 | 0.00 |
September | 47.29 | 23.16 | 24.13 | 84.60 | 13.65 | 0.00 | 0.00 | 0.00 |
October | 41.48 | 23.23 | 18.25 | 70.79 | 19.18 | 0.00 | 0.00 | 0.00 |
November | 32.98 | 17.14 | 15.84 | 53.29 | 23.21 | 0.00 | 0.00 | 0.00 |
December | 29.47 | 16.14 | 13.34 | 45.59 | 26.53 | 18.17 | 0.00 | 0.00 |
Annual Sum or Average | 46.24 | 25.58 | 20.66 | 78.28 | 19.83 | 19.17 | 0.00 | 0.00 |
Minimum of Months | 29.47 | 16.14 | 12.82 | 45.59 | 11.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.12 | 36.02 | 27.95 | 107.20 | 30.96 | 18.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 19.37 | 12.82 | 48.50 | 30.96 | 0.17 | 0.00 | 0.00 |
February | 39.56 | 24.10 | 15.46 | 63.24 | 26.71 | 0.00 | 0.00 | 0.00 |
March | 49.51 | 30.24 | 19.27 | 79.12 | 24.35 | 0.83 | 0.00 | 0.00 |
April | 57.77 | 36.02 | 21.76 | 96.74 | 21.33 | 0.00 | 0.00 | 0.00 |
May | 57.08 | 32.28 | 24.81 | 99.40 | 15.24 | 0.00 | 0.00 | 0.00 |
June | 54.24 | 27.26 | 26.98 | 96.21 | 11.57 | 0.00 | 0.00 | 0.00 |
July | 59.12 | 31.16 | 27.95 | 107.20 | 13.17 | 0.00 | 0.00 | 0.00 |
August | 53.71 | 26.75 | 26.96 | 93.77 | 12.38 | 0.00 | 0.00 | 0.00 |
September | 47.29 | 23.16 | 24.13 | 84.60 | 13.65 | 0.00 | 0.00 | 0.00 |
October | 41.48 | 23.23 | 18.25 | 70.79 | 19.18 | 0.00 | 0.00 | 0.00 |
November | 32.98 | 17.14 | 15.84 | 53.29 | 23.21 | 0.00 | 0.00 | 0.00 |
December | 29.47 | 16.14 | 13.34 | 45.59 | 26.53 | 18.17 | 0.00 | 0.00 |
Annual Sum or Average | 46.24 | 25.58 | 20.66 | 78.28 | 19.83 | 19.17 | 0.00 | 0.00 |
Minimum of Months | 29.47 | 16.14 | 12.82 | 45.59 | 11.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.12 | 36.02 | 27.95 | 107.20 | 30.96 | 18.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 19.37 | 12.82 | 48.50 | 30.96 | 0.17 | 0.00 | 0.00 |
February | 39.56 | 24.10 | 15.46 | 63.24 | 26.71 | 0.00 | 0.00 | 0.00 |
March | 49.51 | 30.24 | 19.27 | 79.12 | 24.35 | 0.83 | 0.00 | 0.00 |
April | 57.77 | 36.02 | 21.76 | 96.74 | 21.33 | 0.00 | 0.00 | 0.00 |
May | 57.08 | 32.28 | 24.81 | 99.40 | 15.24 | 0.00 | 0.00 | 0.00 |
June | 54.24 | 27.26 | 26.98 | 96.21 | 11.57 | 0.00 | 0.00 | 0.00 |
July | 59.12 | 31.16 | 27.95 | 107.20 | 13.17 | 0.00 | 0.00 | 0.00 |
August | 53.71 | 26.75 | 26.96 | 93.77 | 12.38 | 0.00 | 0.00 | 0.00 |
September | 47.29 | 23.16 | 24.13 | 84.60 | 13.65 | 0.00 | 0.00 | 0.00 |
October | 41.48 | 23.23 | 18.25 | 70.79 | 19.18 | 0.00 | 0.00 | 0.00 |
November | 32.98 | 17.14 | 15.84 | 53.29 | 23.21 | 0.00 | 0.00 | 0.00 |
December | 29.47 | 16.14 | 13.34 | 45.59 | 26.53 | 18.17 | 0.00 | 0.00 |
Annual Sum or Average | 46.24 | 25.58 | 20.66 | 78.28 | 19.83 | 19.17 | 0.00 | 0.00 |
Minimum of Months | 29.47 | 16.14 | 12.82 | 45.59 | 11.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.12 | 36.02 | 27.95 | 107.20 | 30.96 | 18.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 19.37 | 12.82 | 48.50 | 30.96 | 0.17 | 0.00 | 0.00 |
February | 39.56 | 24.10 | 15.46 | 63.24 | 26.71 | 0.00 | 0.00 | 0.00 |
March | 49.51 | 30.24 | 19.27 | 79.12 | 24.35 | 0.83 | 0.00 | 0.00 |
April | 57.77 | 36.02 | 21.76 | 96.74 | 21.33 | 0.00 | 0.00 | 0.00 |
May | 57.08 | 32.28 | 24.81 | 99.40 | 15.24 | 0.00 | 0.00 | 0.00 |
June | 54.24 | 27.26 | 26.98 | 96.21 | 11.57 | 0.00 | 0.00 | 0.00 |
July | 59.12 | 31.16 | 27.95 | 107.20 | 13.17 | 0.00 | 0.00 | 0.00 |
August | 53.71 | 26.75 | 26.96 | 93.77 | 12.38 | 0.00 | 0.00 | 0.00 |
September | 47.29 | 23.16 | 24.13 | 84.60 | 13.65 | 0.00 | 0.00 | 0.00 |
October | 41.48 | 23.23 | 18.25 | 70.79 | 19.18 | 0.00 | 0.00 | 0.00 |
November | 32.98 | 17.14 | 15.84 | 53.29 | 23.21 | 0.00 | 0.00 | 0.00 |
December | 29.47 | 16.14 | 13.34 | 45.59 | 26.53 | 18.17 | 0.00 | 0.00 |
Annual Sum or Average | 46.24 | 25.58 | 20.66 | 78.28 | 19.83 | 19.17 | 0.00 | 0.00 |
Minimum of Months | 29.47 | 16.14 | 12.82 | 45.59 | 11.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.12 | 36.02 | 27.95 | 107.20 | 30.96 | 18.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 19.37 | 12.82 | 48.50 | 30.96 | 0.17 | 0.00 | 0.00 |
February | 39.56 | 24.10 | 15.46 | 63.24 | 26.71 | 0.00 | 0.00 | 0.00 |
March | 49.51 | 30.24 | 19.27 | 79.12 | 24.35 | 0.83 | 0.00 | 0.00 |
April | 57.77 | 36.02 | 21.76 | 96.74 | 21.33 | 0.00 | 0.00 | 0.00 |
May | 57.08 | 32.28 | 24.81 | 99.40 | 15.24 | 0.00 | 0.00 | 0.00 |
June | 54.24 | 27.26 | 26.98 | 96.21 | 11.57 | 0.00 | 0.00 | 0.00 |
July | 59.12 | 31.16 | 27.95 | 107.20 | 13.17 | 0.00 | 0.00 | 0.00 |
August | 53.71 | 26.75 | 26.96 | 93.77 | 12.38 | 0.00 | 0.00 | 0.00 |
September | 47.29 | 23.16 | 24.13 | 84.60 | 13.65 | 0.00 | 0.00 | 0.00 |
October | 41.48 | 23.23 | 18.25 | 70.79 | 19.18 | 0.00 | 0.00 | 0.00 |
November | 32.98 | 17.14 | 15.84 | 53.29 | 23.21 | 0.00 | 0.00 | 0.00 |
December | 29.47 | 16.14 | 13.34 | 45.59 | 26.53 | 18.17 | 0.00 | 0.00 |
Annual Sum or Average | 46.24 | 25.58 | 20.66 | 78.28 | 19.83 | 19.17 | 0.00 | 0.00 |
Minimum of Months | 29.47 | 16.14 | 12.82 | 45.59 | 11.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.12 | 36.02 | 27.95 | 107.20 | 30.96 | 18.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 19.37 | 12.82 | 48.50 | 30.96 | 0.17 | 0.00 | 0.00 |
February | 39.56 | 24.10 | 15.46 | 63.24 | 26.71 | 0.00 | 0.00 | 0.00 |
March | 49.51 | 30.24 | 19.27 | 79.12 | 24.35 | 0.83 | 0.00 | 0.00 |
April | 57.77 | 36.02 | 21.76 | 96.74 | 21.33 | 0.00 | 0.00 | 0.00 |
May | 57.08 | 32.28 | 24.81 | 99.40 | 15.24 | 0.00 | 0.00 | 0.00 |
June | 54.24 | 27.26 | 26.98 | 96.21 | 11.57 | 0.00 | 0.00 | 0.00 |
July | 59.12 | 31.16 | 27.95 | 107.20 | 13.17 | 0.00 | 0.00 | 0.00 |
August | 53.71 | 26.75 | 26.96 | 93.77 | 12.38 | 0.00 | 0.00 | 0.00 |
September | 47.29 | 23.16 | 24.13 | 84.60 | 13.65 | 0.00 | 0.00 | 0.00 |
October | 41.48 | 23.23 | 18.25 | 70.79 | 19.18 | 0.00 | 0.00 | 0.00 |
November | 32.98 | 17.14 | 15.84 | 53.29 | 23.21 | 0.00 | 0.00 | 0.00 |
December | 29.47 | 16.14 | 13.34 | 45.59 | 26.53 | 18.17 | 0.00 | 0.00 |
Annual Sum or Average | 46.24 | 25.58 | 20.66 | 78.28 | 19.83 | 19.17 | 0.00 | 0.00 |
Minimum of Months | 29.47 | 16.14 | 12.82 | 45.59 | 11.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.12 | 36.02 | 27.95 | 107.20 | 30.96 | 18.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 19.37 | 12.82 | 48.50 | 30.96 | 0.17 | 0.00 | 0.00 |
February | 39.56 | 24.10 | 15.46 | 63.24 | 26.71 | 0.00 | 0.00 | 0.00 |
March | 49.51 | 30.24 | 19.27 | 79.12 | 24.35 | 0.83 | 0.00 | 0.00 |
April | 57.77 | 36.02 | 21.76 | 96.74 | 21.33 | 0.00 | 0.00 | 0.00 |
May | 57.08 | 32.28 | 24.81 | 99.40 | 15.24 | 0.00 | 0.00 | 0.00 |
June | 54.24 | 27.26 | 26.98 | 96.21 | 11.57 | 0.00 | 0.00 | 0.00 |
July | 59.12 | 31.16 | 27.95 | 107.20 | 13.17 | 0.00 | 0.00 | 0.00 |
August | 53.71 | 26.75 | 26.96 | 93.77 | 12.38 | 0.00 | 0.00 | 0.00 |
September | 47.29 | 23.16 | 24.13 | 84.60 | 13.65 | 0.00 | 0.00 | 0.00 |
October | 41.48 | 23.23 | 18.25 | 70.79 | 19.18 | 0.00 | 0.00 | 0.00 |
November | 32.98 | 17.14 | 15.84 | 53.29 | 23.21 | 0.00 | 0.00 | 0.00 |
December | 29.47 | 16.14 | 13.34 | 45.59 | 26.53 | 18.17 | 0.00 | 0.00 |
Annual Sum or Average | 46.24 | 25.58 | 20.66 | 78.28 | 19.83 | 19.17 | 0.00 | 0.00 |
Minimum of Months | 29.47 | 16.14 | 12.82 | 45.59 | 11.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.12 | 36.02 | 27.95 | 107.20 | 30.96 | 18.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 19.37 | 12.82 | 48.50 | 30.96 | 0.17 | 0.00 | 0.00 |
February | 39.56 | 24.10 | 15.46 | 63.24 | 26.71 | 0.00 | 0.00 | 0.00 |
March | 49.51 | 30.24 | 19.27 | 79.12 | 24.35 | 0.83 | 0.00 | 0.00 |
April | 57.77 | 36.02 | 21.76 | 96.74 | 21.33 | 0.00 | 0.00 | 0.00 |
May | 57.08 | 32.28 | 24.81 | 99.40 | 15.24 | 0.00 | 0.00 | 0.00 |
June | 54.24 | 27.26 | 26.98 | 96.21 | 11.57 | 0.00 | 0.00 | 0.00 |
July | 59.12 | 31.16 | 27.95 | 107.20 | 13.17 | 0.00 | 0.00 | 0.00 |
August | 53.71 | 26.75 | 26.96 | 93.77 | 12.38 | 0.00 | 0.00 | 0.00 |
September | 47.29 | 23.16 | 24.13 | 84.60 | 13.65 | 0.00 | 0.00 | 0.00 |
October | 41.48 | 23.23 | 18.25 | 70.79 | 19.18 | 0.00 | 0.00 | 0.00 |
November | 32.98 | 17.14 | 15.84 | 53.29 | 23.21 | 0.00 | 0.00 | 0.00 |
December | 29.47 | 16.14 | 13.34 | 45.59 | 26.53 | 18.17 | 0.00 | 0.00 |
Annual Sum or Average | 46.24 | 25.58 | 20.66 | 78.28 | 19.83 | 19.17 | 0.00 | 0.00 |
Minimum of Months | 29.47 | 16.14 | 12.82 | 45.59 | 11.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.12 | 36.02 | 27.95 | 107.20 | 30.96 | 18.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 19.37 | 12.82 | 48.50 | 30.96 | 0.17 | 0.00 | 0.00 |
February | 39.56 | 24.10 | 15.46 | 63.24 | 26.71 | 0.00 | 0.00 | 0.00 |
March | 49.51 | 30.24 | 19.27 | 79.12 | 24.35 | 0.83 | 0.00 | 0.00 |
April | 57.77 | 36.02 | 21.76 | 96.74 | 21.33 | 0.00 | 0.00 | 0.00 |
May | 57.08 | 32.28 | 24.81 | 99.40 | 15.24 | 0.00 | 0.00 | 0.00 |
June | 54.24 | 27.26 | 26.98 | 96.21 | 11.57 | 0.00 | 0.00 | 0.00 |
July | 59.12 | 31.16 | 27.95 | 107.20 | 13.17 | 0.00 | 0.00 | 0.00 |
August | 53.71 | 26.75 | 26.96 | 93.77 | 12.38 | 0.00 | 0.00 | 0.00 |
September | 47.29 | 23.16 | 24.13 | 84.60 | 13.65 | 0.00 | 0.00 | 0.00 |
October | 41.48 | 23.23 | 18.25 | 70.79 | 19.18 | 0.00 | 0.00 | 0.00 |
November | 32.98 | 17.14 | 15.84 | 53.29 | 23.21 | 0.00 | 0.00 | 0.00 |
December | 29.47 | 16.14 | 13.34 | 45.59 | 26.53 | 18.17 | 0.00 | 0.00 |
Annual Sum or Average | 46.24 | 25.58 | 20.66 | 78.28 | 19.83 | 19.17 | 0.00 | 0.00 |
Minimum of Months | 29.47 | 16.14 | 12.82 | 45.59 | 11.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.12 | 36.02 | 27.95 | 107.20 | 30.96 | 18.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 19.37 | 12.82 | 48.50 | 30.96 | 0.17 | 0.00 | 0.00 |
February | 39.56 | 24.10 | 15.46 | 63.24 | 26.71 | 0.00 | 0.00 | 0.00 |
March | 49.51 | 30.24 | 19.27 | 79.12 | 24.35 | 0.83 | 0.00 | 0.00 |
April | 57.77 | 36.02 | 21.76 | 96.74 | 21.33 | 0.00 | 0.00 | 0.00 |
May | 57.08 | 32.28 | 24.81 | 99.40 | 15.24 | 0.00 | 0.00 | 0.00 |
June | 54.24 | 27.26 | 26.98 | 96.21 | 11.57 | 0.00 | 0.00 | 0.00 |
July | 59.12 | 31.16 | 27.95 | 107.20 | 13.17 | 0.00 | 0.00 | 0.00 |
August | 53.71 | 26.75 | 26.96 | 93.77 | 12.38 | 0.00 | 0.00 | 0.00 |
September | 47.29 | 23.16 | 24.13 | 84.60 | 13.65 | 0.00 | 0.00 | 0.00 |
October | 41.48 | 23.23 | 18.25 | 70.79 | 19.18 | 0.00 | 0.00 | 0.00 |
November | 32.98 | 17.14 | 15.84 | 53.29 | 23.21 | 0.00 | 0.00 | 0.00 |
December | 29.47 | 16.14 | 13.34 | 45.59 | 26.53 | 18.17 | 0.00 | 0.00 |
Annual Sum or Average | 46.24 | 25.58 | 20.66 | 78.28 | 19.83 | 19.17 | 0.00 | 0.00 |
Minimum of Months | 29.47 | 16.14 | 12.82 | 45.59 | 11.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.12 | 36.02 | 27.95 | 107.20 | 30.96 | 18.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.20 | 19.37 | 12.82 | 48.50 | 30.96 | 0.17 | 0.00 | 0.00 |
February | 39.56 | 24.10 | 15.46 | 63.24 | 26.71 | 0.00 | 0.00 | 0.00 |
March | 49.51 | 30.24 | 19.27 | 79.12 | 24.35 | 0.83 | 0.00 | 0.00 |
April | 57.77 | 36.02 | 21.76 | 96.74 | 21.33 | 0.00 | 0.00 | 0.00 |
May | 57.08 | 32.28 | 24.81 | 99.40 | 15.24 | 0.00 | 0.00 | 0.00 |
June | 54.24 | 27.26 | 26.98 | 96.21 | 11.57 | 0.00 | 0.00 | 0.00 |
July | 59.12 | 31.16 | 27.95 | 107.20 | 13.17 | 0.00 | 0.00 | 0.00 |
August | 53.71 | 26.75 | 26.96 | 93.77 | 12.38 | 0.00 | 0.00 | 0.00 |
September | 47.29 | 23.16 | 24.13 | 84.60 | 13.65 | 0.00 | 0.00 | 0.00 |
October | 41.48 | 23.23 | 18.25 | 70.79 | 19.18 | 0.00 | 0.00 | 0.00 |
November | 32.98 | 17.14 | 15.84 | 53.29 | 23.21 | 0.00 | 0.00 | 0.00 |
December | 29.47 | 16.14 | 13.34 | 45.59 | 26.53 | 18.17 | 0.00 | 0.00 |
Annual Sum or Average | 46.24 | 25.58 | 20.66 | 78.28 | 19.83 | 19.17 | 0.00 | 0.00 |
Minimum of Months | 29.47 | 16.14 | 12.82 | 45.59 | 11.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.12 | 36.02 | 27.95 | 107.20 | 30.96 | 18.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 92.68 | 54.67 | 48.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 119.01 | 47.18 | 15.00 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 147.44 | 44.60 | 3.33 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 175.96 | 42.70 | 9.50 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 177.98 | 33.32 | 2.83 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 170.34 | 28.21 | 8.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 188.01 | 31.06 | 1.17 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 162.71 | 30.95 | 13.17 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 149.04 | 32.14 | 8.17 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 125.60 | 41.59 | 14.33 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 98.47 | 44.34 | 45.67 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 86.71 | 46.93 | 38.83 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 141.26 | 39.78 | 208.17 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 86.71 | 28.21 | 1.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 188.01 | 54.67 | 48.17 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.143204E+09 | 62056343.76 | 81147441.06 | 0.209541E+09 | 0.169157E+09 |
February | 0.161448E+09 | 73308834.75 | 88139494.63 | 0.264504E+09 | 0.126627E+09 |
March | 0.222490E+09 | 0.101783E+09 | 0.120708E+09 | 0.362597E+09 | 0.123117E+09 |
April | 0.235821E+09 | 0.108928E+09 | 0.126893E+09 | 0.413300E+09 | 92714063.01 |
May | 0.223142E+09 | 86145546.91 | 0.136997E+09 | 0.424853E+09 | 59869944.17 |
June | 0.182863E+09 | 51381336.63 | 0.131482E+09 | 0.364280E+09 | 33873667.53 |
July | 0.211013E+09 | 65402856.36 | 0.145610E+09 | 0.433476E+09 | 46342714.86 |
August | 0.210371E+09 | 68441710.47 | 0.141929E+09 | 0.414416E+09 | 40217581.30 |
September | 0.173595E+09 | 51236781.26 | 0.122358E+09 | 0.348720E+09 | 47429896.93 |
October | 0.178384E+09 | 69556742.30 | 0.108827E+09 | 0.335487E+09 | 73166575.69 |
November | 0.142268E+09 | 52048292.05 | 90219208.88 | 0.244271E+09 | 0.102782E+09 |
December | 0.147759E+09 | 66208298.57 | 81550772.61 | 0.229446E+09 | 0.147452E+09 |
Annual Sum or Average | 0.223236E+10 | 0.856497E+09 | 0.137586E+10 | 0.404489E+10 | 0.106275E+10 |
Minimum of Months | 0.142268E+09 | 51236781.26 | 81147441.06 | 0.209541E+09 | 33873667.53 |
Maximum of Months | 0.235821E+09 | 0.108928E+09 | 0.145610E+09 | 0.433476E+09 | 0.169157E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.143204E+09 | 62056343.76 | 81147441.06 | 0.209541E+09 | 0.169157E+09 |
February | 0.161448E+09 | 73308834.75 | 88139494.63 | 0.264504E+09 | 0.126627E+09 |
March | 0.222490E+09 | 0.101783E+09 | 0.120708E+09 | 0.362597E+09 | 0.123117E+09 |
April | 0.235821E+09 | 0.108928E+09 | 0.126893E+09 | 0.413300E+09 | 92714063.01 |
May | 0.223142E+09 | 86145546.91 | 0.136997E+09 | 0.424853E+09 | 59869944.17 |
June | 0.182863E+09 | 51381336.63 | 0.131482E+09 | 0.364280E+09 | 33873667.53 |
July | 0.211013E+09 | 65402856.36 | 0.145610E+09 | 0.433476E+09 | 46342714.86 |
August | 0.210371E+09 | 68441710.47 | 0.141929E+09 | 0.414416E+09 | 40217581.30 |
September | 0.173595E+09 | 51236781.26 | 0.122358E+09 | 0.348720E+09 | 47429896.93 |
October | 0.178384E+09 | 69556742.30 | 0.108827E+09 | 0.335487E+09 | 73166575.69 |
November | 0.142268E+09 | 52048292.05 | 90219208.88 | 0.244271E+09 | 0.102782E+09 |
December | 0.147759E+09 | 66208298.57 | 81550772.61 | 0.229446E+09 | 0.147452E+09 |
Annual Sum or Average | 0.223236E+10 | 0.856497E+09 | 0.137586E+10 | 0.404489E+10 | 0.106275E+10 |
Minimum of Months | 0.142268E+09 | 51236781.26 | 81147441.06 | 0.209541E+09 | 33873667.53 |
Maximum of Months | 0.235821E+09 | 0.108928E+09 | 0.145610E+09 | 0.433476E+09 | 0.169157E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38420597.51 | 0.00 | 38420597.51 | 38474119.77 | 0.101594E+09 |
February | 41075928.81 | 0.00 | 41075928.81 | 53762449.95 | 75055316.00 |
March | 54254793.76 | 3599.82 | 54251193.94 | 70270462.84 | 73455132.80 |
April | 58947007.10 | 329312.38 | 58617694.73 | 92454971.24 | 54140061.17 |
May | 69136368.73 | 2779390.68 | 66356978.05 | 0.132809E+09 | 33867805.58 |
June | 71623943.79 | 5009301.91 | 66614641.87 | 0.147490E+09 | 18410748.24 |
July | 74849223.10 | 3479846.71 | 71369376.39 | 0.161796E+09 | 26375556.51 |
August | 66597168.22 | 750331.02 | 65846837.20 | 0.135120E+09 | 22888594.66 |
September | 57023179.18 | 11434.12 | 57011745.05 | 0.117928E+09 | 27155263.47 |
October | 49343102.28 | 0.00 | 49343102.28 | 91059568.84 | 42324476.03 |
November | 41520086.22 | 0.00 | 41520086.22 | 62303775.58 | 60031773.94 |
December | 38002762.25 | 0.00 | 38002762.25 | 43068454.99 | 88519819.79 |
Annual Sum or Average | 0.660794E+09 | 12363216.65 | 0.648431E+09 | 0.114654E+10 | 0.623818E+09 |
Minimum of Months | 38002762.25 | 0.00 | 38002762.25 | 38474119.77 | 18410748.24 |
Maximum of Months | 74849223.10 | 5009301.91 | 71369376.39 | 0.161796E+09 | 0.101594E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38419478.76 | 0.00 | 38419478.76 | 38472843.04 | 0.101593E+09 |
February | 41074753.69 | 0.00 | 41074753.69 | 53760942.87 | 75054551.40 |
March | 54253258.07 | 3599.65 | 54249658.42 | 70268358.13 | 73454326.71 |
April | 58945369.39 | 329296.94 | 58616072.45 | 92452663.43 | 54139332.00 |
May | 69134269.51 | 2779260.41 | 66355009.10 | 0.132806E+09 | 33867119.08 |
June | 71621641.64 | 5009067.12 | 66612574.52 | 0.147486E+09 | 18410122.94 |
July | 74846897.13 | 3479683.61 | 71367213.53 | 0.161792E+09 | 26374847.59 |
August | 66595127.68 | 750295.85 | 65844831.83 | 0.135117E+09 | 22887905.68 |
September | 57021435.34 | 11433.59 | 57010001.75 | 0.117925E+09 | 27154572.56 |
October | 49341640.34 | 0.00 | 49341640.34 | 91057499.27 | 42323560.27 |
November | 41518812.55 | 0.00 | 41518812.55 | 62302021.55 | 60030918.97 |
December | 38001612.27 | 0.00 | 38001612.27 | 43066983.47 | 88519103.90 |
Annual Sum or Average | 0.660774E+09 | 12362637.17 | 0.648412E+09 | 0.114651E+10 | 0.623809E+09 |
Minimum of Months | 38001612.27 | 0.00 | 38001612.27 | 38472843.04 | 18410122.94 |
Maximum of Months | 74846897.13 | 5009067.12 | 71367213.53 | 0.161792E+09 | 0.101593E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86240002.80 | 51891389.33 | 34348613.47 | 0.129902E+09 | 82928257.09 |
February | 95703363.64 | 58293463.31 | 37409900.34 | 0.152995E+09 | 64608138.12 |
March | 0.132601E+09 | 80984415.02 | 51616502.27 | 0.211913E+09 | 65206834.26 |
April | 0.149750E+09 | 93358605.70 | 56391857.43 | 0.250745E+09 | 55293529.92 |
May | 0.152896E+09 | 86450556.94 | 66445705.35 | 0.266235E+09 | 40818149.12 |
June | 0.140590E+09 | 70664732.72 | 69925700.16 | 0.249364E+09 | 29991176.62 |
July | 0.158342E+09 | 83468299.47 | 74873253.82 | 0.287124E+09 | 35264436.94 |
August | 0.143860E+09 | 71650813.20 | 72209042.63 | 0.251160E+09 | 33167364.07 |
September | 0.122580E+09 | 60026664.10 | 62553754.64 | 0.219273E+09 | 35371765.33 |
October | 0.111109E+09 | 62215848.66 | 48892812.79 | 0.189601E+09 | 51359787.59 |
November | 85472818.47 | 44415208.84 | 41057609.63 | 0.138127E+09 | 60166289.42 |
December | 78934774.83 | 43216581.50 | 35718193.33 | 0.122104E+09 | 71068799.09 |
Annual Sum or Average | 0.145808E+10 | 0.806637E+09 | 0.651443E+09 | 0.246854E+10 | 0.625245E+09 |
Minimum of Months | 78934774.83 | 43216581.50 | 34348613.47 | 0.122104E+09 | 29991176.62 |
Maximum of Months | 0.158342E+09 | 93358605.70 | 74873253.82 | 0.287124E+09 | 82928257.09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86240002.80 | 51891389.33 | 34348613.47 | 0.129902E+09 | 82928257.09 |
February | 95703363.64 | 58293463.31 | 37409900.34 | 0.152995E+09 | 64608138.12 |
March | 0.132601E+09 | 80984415.02 | 51616502.27 | 0.211913E+09 | 65206834.26 |
April | 0.149750E+09 | 93358605.70 | 56391857.43 | 0.250745E+09 | 55293529.92 |
May | 0.152896E+09 | 86450556.94 | 66445705.35 | 0.266235E+09 | 40818149.12 |
June | 0.140590E+09 | 70664732.72 | 69925700.16 | 0.249364E+09 | 29991176.62 |
July | 0.158342E+09 | 83468299.47 | 74873253.82 | 0.287124E+09 | 35264436.94 |
August | 0.143860E+09 | 71650813.20 | 72209042.63 | 0.251160E+09 | 33167364.07 |
September | 0.122580E+09 | 60026664.10 | 62553754.64 | 0.219273E+09 | 35371765.33 |
October | 0.111109E+09 | 62215848.66 | 48892812.79 | 0.189601E+09 | 51359787.59 |
November | 85472818.47 | 44415208.84 | 41057609.63 | 0.138127E+09 | 60166289.42 |
December | 78934774.83 | 43216581.50 | 35718193.33 | 0.122104E+09 | 71068799.09 |
Annual Sum or Average | 0.145808E+10 | 0.806637E+09 | 0.651443E+09 | 0.246854E+10 | 0.625245E+09 |
Minimum of Months | 78934774.83 | 43216581.50 | 34348613.47 | 0.122104E+09 | 29991176.62 |
Maximum of Months | 0.158342E+09 | 93358605.70 | 74873253.82 | 0.287124E+09 | 82928257.09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86240002.80 | 51891389.33 | 34348613.47 | 0.129902E+09 | 82928257.09 |
February | 95703363.64 | 58293463.31 | 37409900.34 | 0.152995E+09 | 64608138.12 |
March | 0.132601E+09 | 80984415.02 | 51616502.27 | 0.211913E+09 | 65206834.26 |
April | 0.149750E+09 | 93358605.70 | 56391857.43 | 0.250745E+09 | 55293529.92 |
May | 0.152896E+09 | 86450556.94 | 66445705.35 | 0.266235E+09 | 40818149.12 |
June | 0.140590E+09 | 70664732.72 | 69925700.16 | 0.249364E+09 | 29991176.62 |
July | 0.158342E+09 | 83468299.47 | 74873253.82 | 0.287124E+09 | 35264436.94 |
August | 0.143860E+09 | 71650813.20 | 72209042.63 | 0.251160E+09 | 33167364.07 |
September | 0.122580E+09 | 60026664.10 | 62553754.64 | 0.219273E+09 | 35371765.33 |
October | 0.111109E+09 | 62215848.66 | 48892812.79 | 0.189601E+09 | 51359787.59 |
November | 85472818.47 | 44415208.84 | 41057609.63 | 0.138127E+09 | 60166289.42 |
December | 78934774.83 | 43216581.50 | 35718193.33 | 0.122104E+09 | 71068799.09 |
Annual Sum or Average | 0.145808E+10 | 0.806637E+09 | 0.651443E+09 | 0.246854E+10 | 0.625245E+09 |
Minimum of Months | 78934774.83 | 43216581.50 | 34348613.47 | 0.122104E+09 | 29991176.62 |
Maximum of Months | 0.158342E+09 | 93358605.70 | 74873253.82 | 0.287124E+09 | 82928257.09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86240002.80 | 51891389.33 | 34348613.47 | 0.129902E+09 | 82928257.09 |
February | 95703363.64 | 58293463.31 | 37409900.34 | 0.152995E+09 | 64608138.12 |
March | 0.132601E+09 | 80984415.02 | 51616502.27 | 0.211913E+09 | 65206834.26 |
April | 0.149750E+09 | 93358605.70 | 56391857.43 | 0.250745E+09 | 55293529.92 |
May | 0.152896E+09 | 86450556.94 | 66445705.35 | 0.266235E+09 | 40818149.12 |
June | 0.140590E+09 | 70664732.72 | 69925700.16 | 0.249364E+09 | 29991176.62 |
July | 0.158342E+09 | 83468299.47 | 74873253.82 | 0.287124E+09 | 35264436.94 |
August | 0.143860E+09 | 71650813.20 | 72209042.63 | 0.251160E+09 | 33167364.07 |
September | 0.122580E+09 | 60026664.10 | 62553754.64 | 0.219273E+09 | 35371765.33 |
October | 0.111109E+09 | 62215848.66 | 48892812.79 | 0.189601E+09 | 51359787.59 |
November | 85472818.47 | 44415208.84 | 41057609.63 | 0.138127E+09 | 60166289.42 |
December | 78934774.83 | 43216581.50 | 35718193.33 | 0.122104E+09 | 71068799.09 |
Annual Sum or Average | 0.145808E+10 | 0.806637E+09 | 0.651443E+09 | 0.246854E+10 | 0.625245E+09 |
Minimum of Months | 78934774.83 | 43216581.50 | 34348613.47 | 0.122104E+09 | 29991176.62 |
Maximum of Months | 0.158342E+09 | 93358605.70 | 74873253.82 | 0.287124E+09 | 82928257.09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86240002.80 | 51891389.33 | 34348613.47 | 0.129902E+09 | 82928257.09 |
February | 95703363.64 | 58293463.31 | 37409900.34 | 0.152995E+09 | 64608138.12 |
March | 0.132601E+09 | 80984415.02 | 51616502.27 | 0.211913E+09 | 65206834.26 |
April | 0.149750E+09 | 93358605.70 | 56391857.43 | 0.250745E+09 | 55293529.92 |
May | 0.152896E+09 | 86450556.94 | 66445705.35 | 0.266235E+09 | 40818149.12 |
June | 0.140590E+09 | 70664732.72 | 69925700.16 | 0.249364E+09 | 29991176.62 |
July | 0.158342E+09 | 83468299.47 | 74873253.82 | 0.287124E+09 | 35264436.94 |
August | 0.143860E+09 | 71650813.20 | 72209042.63 | 0.251160E+09 | 33167364.07 |
September | 0.122580E+09 | 60026664.10 | 62553754.64 | 0.219273E+09 | 35371765.33 |
October | 0.111109E+09 | 62215848.66 | 48892812.79 | 0.189601E+09 | 51359787.59 |
November | 85472818.47 | 44415208.84 | 41057609.63 | 0.138127E+09 | 60166289.42 |
December | 78934774.83 | 43216581.50 | 35718193.33 | 0.122104E+09 | 71068799.09 |
Annual Sum or Average | 0.145808E+10 | 0.806637E+09 | 0.651443E+09 | 0.246854E+10 | 0.625245E+09 |
Minimum of Months | 78934774.83 | 43216581.50 | 34348613.47 | 0.122104E+09 | 29991176.62 |
Maximum of Months | 0.158342E+09 | 93358605.70 | 74873253.82 | 0.287124E+09 | 82928257.09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86240002.80 | 51891389.33 | 34348613.47 | 0.129902E+09 | 82928257.09 |
February | 95703363.64 | 58293463.31 | 37409900.34 | 0.152995E+09 | 64608138.12 |
March | 0.132601E+09 | 80984415.02 | 51616502.27 | 0.211913E+09 | 65206834.26 |
April | 0.149750E+09 | 93358605.70 | 56391857.43 | 0.250745E+09 | 55293529.92 |
May | 0.152896E+09 | 86450556.94 | 66445705.35 | 0.266235E+09 | 40818149.12 |
June | 0.140590E+09 | 70664732.72 | 69925700.16 | 0.249364E+09 | 29991176.62 |
July | 0.158342E+09 | 83468299.47 | 74873253.82 | 0.287124E+09 | 35264436.94 |
August | 0.143860E+09 | 71650813.20 | 72209042.63 | 0.251160E+09 | 33167364.07 |
September | 0.122580E+09 | 60026664.10 | 62553754.64 | 0.219273E+09 | 35371765.33 |
October | 0.111109E+09 | 62215848.66 | 48892812.79 | 0.189601E+09 | 51359787.59 |
November | 85472818.47 | 44415208.84 | 41057609.63 | 0.138127E+09 | 60166289.42 |
December | 78934774.83 | 43216581.50 | 35718193.33 | 0.122104E+09 | 71068799.09 |
Annual Sum or Average | 0.145808E+10 | 0.806637E+09 | 0.651443E+09 | 0.246854E+10 | 0.625245E+09 |
Minimum of Months | 78934774.83 | 43216581.50 | 34348613.47 | 0.122104E+09 | 29991176.62 |
Maximum of Months | 0.158342E+09 | 93358605.70 | 74873253.82 | 0.287124E+09 | 82928257.09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86240002.80 | 51891389.33 | 34348613.47 | 0.129902E+09 | 82928257.09 |
February | 95703363.64 | 58293463.31 | 37409900.34 | 0.152995E+09 | 64608138.12 |
March | 0.132601E+09 | 80984415.02 | 51616502.27 | 0.211913E+09 | 65206834.26 |
April | 0.149750E+09 | 93358605.70 | 56391857.43 | 0.250745E+09 | 55293529.92 |
May | 0.152896E+09 | 86450556.94 | 66445705.35 | 0.266235E+09 | 40818149.12 |
June | 0.140590E+09 | 70664732.72 | 69925700.16 | 0.249364E+09 | 29991176.62 |
July | 0.158342E+09 | 83468299.47 | 74873253.82 | 0.287124E+09 | 35264436.94 |
August | 0.143860E+09 | 71650813.20 | 72209042.63 | 0.251160E+09 | 33167364.07 |
September | 0.122580E+09 | 60026664.10 | 62553754.64 | 0.219273E+09 | 35371765.33 |
October | 0.111109E+09 | 62215848.66 | 48892812.79 | 0.189601E+09 | 51359787.59 |
November | 85472818.47 | 44415208.84 | 41057609.63 | 0.138127E+09 | 60166289.42 |
December | 78934774.83 | 43216581.50 | 35718193.33 | 0.122104E+09 | 71068799.09 |
Annual Sum or Average | 0.145808E+10 | 0.806637E+09 | 0.651443E+09 | 0.246854E+10 | 0.625245E+09 |
Minimum of Months | 78934774.83 | 43216581.50 | 34348613.47 | 0.122104E+09 | 29991176.62 |
Maximum of Months | 0.158342E+09 | 93358605.70 | 74873253.82 | 0.287124E+09 | 82928257.09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86240002.80 | 51891389.33 | 34348613.47 | 0.129902E+09 | 82928257.09 |
February | 95703363.64 | 58293463.31 | 37409900.34 | 0.152995E+09 | 64608138.12 |
March | 0.132601E+09 | 80984415.02 | 51616502.27 | 0.211913E+09 | 65206834.26 |
April | 0.149750E+09 | 93358605.70 | 56391857.43 | 0.250745E+09 | 55293529.92 |
May | 0.152896E+09 | 86450556.94 | 66445705.35 | 0.266235E+09 | 40818149.12 |
June | 0.140590E+09 | 70664732.72 | 69925700.16 | 0.249364E+09 | 29991176.62 |
July | 0.158342E+09 | 83468299.47 | 74873253.82 | 0.287124E+09 | 35264436.94 |
August | 0.143860E+09 | 71650813.20 | 72209042.63 | 0.251160E+09 | 33167364.07 |
September | 0.122580E+09 | 60026664.10 | 62553754.64 | 0.219273E+09 | 35371765.33 |
October | 0.111109E+09 | 62215848.66 | 48892812.79 | 0.189601E+09 | 51359787.59 |
November | 85472818.47 | 44415208.84 | 41057609.63 | 0.138127E+09 | 60166289.42 |
December | 78934774.83 | 43216581.50 | 35718193.33 | 0.122104E+09 | 71068799.09 |
Annual Sum or Average | 0.145808E+10 | 0.806637E+09 | 0.651443E+09 | 0.246854E+10 | 0.625245E+09 |
Minimum of Months | 78934774.83 | 43216581.50 | 34348613.47 | 0.122104E+09 | 29991176.62 |
Maximum of Months | 0.158342E+09 | 93358605.70 | 74873253.82 | 0.287124E+09 | 82928257.09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86240002.80 | 51891389.33 | 34348613.47 | 0.129902E+09 | 82928257.09 |
February | 95703363.64 | 58293463.31 | 37409900.34 | 0.152995E+09 | 64608138.12 |
March | 0.132601E+09 | 80984415.02 | 51616502.27 | 0.211913E+09 | 65206834.26 |
April | 0.149750E+09 | 93358605.70 | 56391857.43 | 0.250745E+09 | 55293529.92 |
May | 0.152896E+09 | 86450556.94 | 66445705.35 | 0.266235E+09 | 40818149.12 |
June | 0.140590E+09 | 70664732.72 | 69925700.16 | 0.249364E+09 | 29991176.62 |
July | 0.158342E+09 | 83468299.47 | 74873253.82 | 0.287124E+09 | 35264436.94 |
August | 0.143860E+09 | 71650813.20 | 72209042.63 | 0.251160E+09 | 33167364.07 |
September | 0.122580E+09 | 60026664.10 | 62553754.64 | 0.219273E+09 | 35371765.33 |
October | 0.111109E+09 | 62215848.66 | 48892812.79 | 0.189601E+09 | 51359787.59 |
November | 85472818.47 | 44415208.84 | 41057609.63 | 0.138127E+09 | 60166289.42 |
December | 78934774.83 | 43216581.50 | 35718193.33 | 0.122104E+09 | 71068799.09 |
Annual Sum or Average | 0.145808E+10 | 0.806637E+09 | 0.651443E+09 | 0.246854E+10 | 0.625245E+09 |
Minimum of Months | 78934774.83 | 43216581.50 | 34348613.47 | 0.122104E+09 | 29991176.62 |
Maximum of Months | 0.158342E+09 | 93358605.70 | 74873253.82 | 0.287124E+09 | 82928257.09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86240002.80 | 51891389.33 | 34348613.47 | 0.129902E+09 | 82928257.09 |
February | 95703363.64 | 58293463.31 | 37409900.34 | 0.152995E+09 | 64608138.12 |
March | 0.132601E+09 | 80984415.02 | 51616502.27 | 0.211913E+09 | 65206834.26 |
April | 0.149750E+09 | 93358605.70 | 56391857.43 | 0.250745E+09 | 55293529.92 |
May | 0.152896E+09 | 86450556.94 | 66445705.35 | 0.266235E+09 | 40818149.12 |
June | 0.140590E+09 | 70664732.72 | 69925700.16 | 0.249364E+09 | 29991176.62 |
July | 0.158342E+09 | 83468299.47 | 74873253.82 | 0.287124E+09 | 35264436.94 |
August | 0.143860E+09 | 71650813.20 | 72209042.63 | 0.251160E+09 | 33167364.07 |
September | 0.122580E+09 | 60026664.10 | 62553754.64 | 0.219273E+09 | 35371765.33 |
October | 0.111109E+09 | 62215848.66 | 48892812.79 | 0.189601E+09 | 51359787.59 |
November | 85472818.47 | 44415208.84 | 41057609.63 | 0.138127E+09 | 60166289.42 |
December | 78934774.83 | 43216581.50 | 35718193.33 | 0.122104E+09 | 71068799.09 |
Annual Sum or Average | 0.145808E+10 | 0.806637E+09 | 0.651443E+09 | 0.246854E+10 | 0.625245E+09 |
Minimum of Months | 78934774.83 | 43216581.50 | 34348613.47 | 0.122104E+09 | 29991176.62 |
Maximum of Months | 0.158342E+09 | 93358605.70 | 74873253.82 | 0.287124E+09 | 82928257.09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86240002.80 | 51891389.33 | 34348613.47 | 0.129902E+09 | 82928257.09 |
February | 95703363.64 | 58293463.31 | 37409900.34 | 0.152995E+09 | 64608138.12 |
March | 0.132601E+09 | 80984415.02 | 51616502.27 | 0.211913E+09 | 65206834.26 |
April | 0.149750E+09 | 93358605.70 | 56391857.43 | 0.250745E+09 | 55293529.92 |
May | 0.152896E+09 | 86450556.94 | 66445705.35 | 0.266235E+09 | 40818149.12 |
June | 0.140590E+09 | 70664732.72 | 69925700.16 | 0.249364E+09 | 29991176.62 |
July | 0.158342E+09 | 83468299.47 | 74873253.82 | 0.287124E+09 | 35264436.94 |
August | 0.143860E+09 | 71650813.20 | 72209042.63 | 0.251160E+09 | 33167364.07 |
September | 0.122580E+09 | 60026664.10 | 62553754.64 | 0.219273E+09 | 35371765.33 |
October | 0.111109E+09 | 62215848.66 | 48892812.79 | 0.189601E+09 | 51359787.59 |
November | 85472818.47 | 44415208.84 | 41057609.63 | 0.138127E+09 | 60166289.42 |
December | 78934774.83 | 43216581.50 | 35718193.33 | 0.122104E+09 | 71068799.09 |
Annual Sum or Average | 0.145808E+10 | 0.806637E+09 | 0.651443E+09 | 0.246854E+10 | 0.625245E+09 |
Minimum of Months | 78934774.83 | 43216581.50 | 34348613.47 | 0.122104E+09 | 29991176.62 |
Maximum of Months | 0.158342E+09 | 93358605.70 | 74873253.82 | 0.287124E+09 | 82928257.09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86240002.80 | 51891389.33 | 34348613.47 | 0.129902E+09 | 82928257.09 |
February | 95703363.64 | 58293463.31 | 37409900.34 | 0.152995E+09 | 64608138.12 |
March | 0.132601E+09 | 80984415.02 | 51616502.27 | 0.211913E+09 | 65206834.26 |
April | 0.149750E+09 | 93358605.70 | 56391857.43 | 0.250745E+09 | 55293529.92 |
May | 0.152896E+09 | 86450556.94 | 66445705.35 | 0.266235E+09 | 40818149.12 |
June | 0.140590E+09 | 70664732.72 | 69925700.16 | 0.249364E+09 | 29991176.62 |
July | 0.158342E+09 | 83468299.47 | 74873253.82 | 0.287124E+09 | 35264436.94 |
August | 0.143860E+09 | 71650813.20 | 72209042.63 | 0.251160E+09 | 33167364.07 |
September | 0.122580E+09 | 60026664.10 | 62553754.64 | 0.219273E+09 | 35371765.33 |
October | 0.111109E+09 | 62215848.66 | 48892812.79 | 0.189601E+09 | 51359787.59 |
November | 85472818.47 | 44415208.84 | 41057609.63 | 0.138127E+09 | 60166289.42 |
December | 78934774.83 | 43216581.50 | 35718193.33 | 0.122104E+09 | 71068799.09 |
Annual Sum or Average | 0.145808E+10 | 0.806637E+09 | 0.651443E+09 | 0.246854E+10 | 0.625245E+09 |
Minimum of Months | 78934774.83 | 43216581.50 | 34348613.47 | 0.122104E+09 | 29991176.62 |
Maximum of Months | 0.158342E+09 | 93358605.70 | 74873253.82 | 0.287124E+09 | 82928257.09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86240002.80 | 51891389.33 | 34348613.47 | 0.129902E+09 | 82928257.09 |
February | 95703363.64 | 58293463.31 | 37409900.34 | 0.152995E+09 | 64608138.12 |
March | 0.132601E+09 | 80984415.02 | 51616502.27 | 0.211913E+09 | 65206834.26 |
April | 0.149750E+09 | 93358605.70 | 56391857.43 | 0.250745E+09 | 55293529.92 |
May | 0.152896E+09 | 86450556.94 | 66445705.35 | 0.266235E+09 | 40818149.12 |
June | 0.140590E+09 | 70664732.72 | 69925700.16 | 0.249364E+09 | 29991176.62 |
July | 0.158342E+09 | 83468299.47 | 74873253.82 | 0.287124E+09 | 35264436.94 |
August | 0.143860E+09 | 71650813.20 | 72209042.63 | 0.251160E+09 | 33167364.07 |
September | 0.122580E+09 | 60026664.10 | 62553754.64 | 0.219273E+09 | 35371765.33 |
October | 0.111109E+09 | 62215848.66 | 48892812.79 | 0.189601E+09 | 51359787.59 |
November | 85472818.47 | 44415208.84 | 41057609.63 | 0.138127E+09 | 60166289.42 |
December | 78934774.83 | 43216581.50 | 35718193.33 | 0.122104E+09 | 71068799.09 |
Annual Sum or Average | 0.145808E+10 | 0.806637E+09 | 0.651443E+09 | 0.246854E+10 | 0.625245E+09 |
Minimum of Months | 78934774.83 | 43216581.50 | 34348613.47 | 0.122104E+09 | 29991176.62 |
Maximum of Months | 0.158342E+09 | 93358605.70 | 74873253.82 | 0.287124E+09 | 82928257.09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86240002.80 | 51891389.33 | 34348613.47 | 0.129902E+09 | 82928257.09 |
February | 95703363.64 | 58293463.31 | 37409900.34 | 0.152995E+09 | 64608138.12 |
March | 0.132601E+09 | 80984415.02 | 51616502.27 | 0.211913E+09 | 65206834.26 |
April | 0.149750E+09 | 93358605.70 | 56391857.43 | 0.250745E+09 | 55293529.92 |
May | 0.152896E+09 | 86450556.94 | 66445705.35 | 0.266235E+09 | 40818149.12 |
June | 0.140590E+09 | 70664732.72 | 69925700.16 | 0.249364E+09 | 29991176.62 |
July | 0.158342E+09 | 83468299.47 | 74873253.82 | 0.287124E+09 | 35264436.94 |
August | 0.143860E+09 | 71650813.20 | 72209042.63 | 0.251160E+09 | 33167364.07 |
September | 0.122580E+09 | 60026664.10 | 62553754.64 | 0.219273E+09 | 35371765.33 |
October | 0.111109E+09 | 62215848.66 | 48892812.79 | 0.189601E+09 | 51359787.59 |
November | 85472818.47 | 44415208.84 | 41057609.63 | 0.138127E+09 | 60166289.42 |
December | 78934774.83 | 43216581.50 | 35718193.33 | 0.122104E+09 | 71068799.09 |
Annual Sum or Average | 0.145808E+10 | 0.806637E+09 | 0.651443E+09 | 0.246854E+10 | 0.625245E+09 |
Minimum of Months | 78934774.83 | 43216581.50 | 34348613.47 | 0.122104E+09 | 29991176.62 |
Maximum of Months | 0.158342E+09 | 93358605.70 | 74873253.82 | 0.287124E+09 | 82928257.09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.248221E+09 | 0.146434E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.287899E+09 | 0.114142E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.394907E+09 | 0.119447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.456083E+09 | 0.110686E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.476707E+09 | 89246871.92 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.441522E+09 | 73128549.40 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.503574E+09 | 83178334.39 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.435790E+09 | 82906043.21 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.386312E+09 | 83298042.06 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.336404E+09 | 0.111388E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.255225E+09 | 0.114931E+09 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.232252E+09 | 0.125699E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.445490E+10 | 0.125449E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.232252E+09 | 73128549.40 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.503574E+09 | 0.146434E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 183.08 | 200.06 | 135.62 | 46.34 | 89.28 | 0.00 | 0.00 |
February | 262.08 | 165.70 | 167.43 | 60.61 | 106.82 | 0.00 | 0.00 |
March | 321.67 | 145.23 | 206.65 | 76.01 | 130.64 | 0.00 | 0.00 |
April | 389.34 | 112.41 | 227.44 | 84.30 | 143.14 | 0.00 | 0.00 |
May | 415.88 | 69.46 | 218.25 | 66.40 | 151.85 | 0.00 | 0.00 |
June | 394.15 | 39.61 | 196.36 | 43.51 | 152.85 | 0.00 | 0.00 |
July | 444.14 | 53.95 | 213.46 | 51.44 | 162.02 | 0.00 | 0.00 |
August | 410.21 | 46.99 | 206.82 | 51.67 | 155.15 | 0.00 | 0.00 |
September | 360.01 | 57.50 | 177.95 | 39.54 | 138.40 | 0.00 | 0.00 |
October | 318.31 | 86.04 | 170.05 | 51.94 | 118.11 | 0.00 | 0.00 |
November | 236.15 | 125.22 | 141.81 | 40.16 | 101.65 | 0.00 | 0.00 |
December | 201.78 | 174.49 | 138.71 | 49.44 | 89.27 | 0.00 | 0.00 |
Annual Sum or Average | 328.42 | 106.15 | 183.48 | 55.10 | 128.38 | 0.00 | 0.00 |
Minimum of Months | 183.08 | 39.61 | 135.62 | 39.54 | 89.27 | 0.00 | 0.00 |
Maximum of Months | 444.14 | 200.06 | 227.44 | 84.30 | 162.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 679.00 | 433.47 | 450.78 | 271.24 | 179.54 | 0.00 | 0.00 |
February | 885.39 | 373.89 | 553.84 | 337.35 | 216.49 | 0.00 | 0.00 |
March | 1107.67 | 340.84 | 693.11 | 423.31 | 269.80 | 0.00 | 0.00 |
April | 1354.34 | 298.65 | 808.84 | 504.25 | 304.59 | 0.00 | 0.00 |
May | 1391.61 | 213.36 | 799.19 | 451.88 | 347.31 | 0.00 | 0.00 |
June | 1346.87 | 161.99 | 759.36 | 381.68 | 377.69 | 0.00 | 0.00 |
July | 1500.80 | 184.33 | 827.65 | 436.29 | 391.36 | 0.00 | 0.00 |
August | 1312.82 | 173.37 | 751.96 | 374.52 | 377.44 | 0.00 | 0.00 |
September | 1184.35 | 191.05 | 662.09 | 324.22 | 337.87 | 0.00 | 0.00 |
October | 991.04 | 268.46 | 580.77 | 325.20 | 255.56 | 0.00 | 0.00 |
November | 746.06 | 324.97 | 461.66 | 239.90 | 221.76 | 0.00 | 0.00 |
December | 638.24 | 371.48 | 412.59 | 225.89 | 186.70 | 0.00 | 0.00 |
Annual Sum or Average | 1095.88 | 277.57 | 647.30 | 358.10 | 289.20 | 0.00 | 0.00 |
Minimum of Months | 638.24 | 161.99 | 412.59 | 225.89 | 179.54 | 0.00 | 0.00 |
Maximum of Months | 1500.80 | 433.47 | 827.65 | 504.25 | 391.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 12069.99 | 5796.10 | 2357.72 | 1421.78 | 935.95 | 0.00 | 0.00 |
February | 16179.73 | 4980.01 | 2882.25 | 1753.66 | 1128.58 | 0.00 | 0.00 |
March | 21245.47 | 4822.11 | 3593.74 | 2187.27 | 1406.47 | 0.00 | 0.00 |
April | 31824.83 | 4951.79 | 4184.81 | 2596.99 | 1587.81 | 0.00 | 0.00 |
May | 29905.15 | 4588.23 | 4133.06 | 2322.51 | 1810.55 | 0.00 | 0.00 |
June | 30476.13 | 4813.47 | 3929.80 | 1960.91 | 1968.88 | 0.00 | 0.00 |
July | 35860.68 | 5760.84 | 4279.45 | 2239.26 | 2040.18 | 0.00 | 0.00 |
August | 29766.24 | 5586.09 | 3891.64 | 1924.05 | 1967.59 | 0.00 | 0.00 |
September | 28163.08 | 5224.60 | 3430.15 | 1668.84 | 1761.31 | 0.00 | 0.00 |
October | 21117.61 | 5604.64 | 3016.62 | 1684.37 | 1332.26 | 0.00 | 0.00 |
November | 15587.60 | 4968.28 | 2408.57 | 1252.52 | 1156.05 | 0.00 | 0.00 |
December | 12684.94 | 5024.10 | 2161.35 | 1188.09 | 973.27 | 0.00 | 0.00 |
Annual Sum or Average | 23771.87 | 5180.36 | 3358.20 | 1850.60 | 1507.61 | 0.00 | 0.00 |
Minimum of Months | 12069.99 | 4588.23 | 2161.35 | 1188.09 | 935.95 | 0.00 | 0.00 |
Maximum of Months | 35860.68 | 5796.10 | 4279.45 | 2596.99 | 2040.18 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.490370E+09 | 0.535841E+09 | 0.363248E+09 | 0.124113E+09 | 0.239135E+09 | 0.00 | 0.00 |
February | 0.634028E+09 | 0.400862E+09 | 0.405047E+09 | 0.146618E+09 | 0.258430E+09 | 0.00 | 0.00 |
March | 0.861571E+09 | 0.388982E+09 | 0.553489E+09 | 0.203573E+09 | 0.349916E+09 | 0.00 | 0.00 |
April | 0.100917E+10 | 0.291369E+09 | 0.589534E+09 | 0.218515E+09 | 0.371019E+09 | 0.00 | 0.00 |
May | 0.111389E+10 | 0.186043E+09 | 0.584555E+09 | 0.177850E+09 | 0.406705E+09 | 0.00 | 0.00 |
June | 0.102164E+10 | 0.102672E+09 | 0.508972E+09 | 0.112781E+09 | 0.396191E+09 | 0.00 | 0.00 |
July | 0.118960E+10 | 0.144491E+09 | 0.571722E+09 | 0.137765E+09 | 0.433957E+09 | 0.00 | 0.00 |
August | 0.109870E+10 | 0.125847E+09 | 0.553933E+09 | 0.138384E+09 | 0.415549E+09 | 0.00 | 0.00 |
September | 0.933151E+09 | 0.149028E+09 | 0.461234E+09 | 0.102496E+09 | 0.358737E+09 | 0.00 | 0.00 |
October | 0.852551E+09 | 0.230442E+09 | 0.455452E+09 | 0.139113E+09 | 0.316339E+09 | 0.00 | 0.00 |
November | 0.612096E+09 | 0.324575E+09 | 0.367574E+09 | 0.104097E+09 | 0.263477E+09 | 0.00 | 0.00 |
December | 0.540443E+09 | 0.467359E+09 | 0.371523E+09 | 0.132417E+09 | 0.239106E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.103572E+11 | 0.334751E+10 | 0.578628E+10 | 0.173772E+10 | 0.404856E+10 | 0.00 | 0.00 |
Minimum of Months | 0.490370E+09 | 0.102672E+09 | 0.363248E+09 | 0.102496E+09 | 0.239106E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118960E+10 | 0.535841E+09 | 0.589534E+09 | 0.218515E+09 | 0.433957E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.181862E+10 | 0.116100E+10 | 0.120736E+10 | 0.726479E+09 | 0.480881E+09 | 0.00 | 0.00 |
February | 0.214193E+10 | 0.904514E+09 | 0.133985E+10 | 0.816108E+09 | 0.523739E+09 | 0.00 | 0.00 |
March | 0.296678E+10 | 0.912896E+09 | 0.185641E+10 | 0.113378E+10 | 0.722631E+09 | 0.00 | 0.00 |
April | 0.351044E+10 | 0.774109E+09 | 0.209651E+10 | 0.130702E+10 | 0.789486E+09 | 0.00 | 0.00 |
May | 0.372729E+10 | 0.571454E+09 | 0.214055E+10 | 0.121031E+10 | 0.930240E+09 | 0.00 | 0.00 |
June | 0.349109E+10 | 0.419876E+09 | 0.196827E+10 | 0.989306E+09 | 0.978960E+09 | 0.00 | 0.00 |
July | 0.401974E+10 | 0.493702E+09 | 0.221678E+10 | 0.116856E+10 | 0.104823E+10 | 0.00 | 0.00 |
August | 0.351624E+10 | 0.464343E+09 | 0.201404E+10 | 0.100311E+10 | 0.101093E+10 | 0.00 | 0.00 |
September | 0.306982E+10 | 0.495205E+09 | 0.171613E+10 | 0.840373E+09 | 0.875753E+09 | 0.00 | 0.00 |
October | 0.265441E+10 | 0.719037E+09 | 0.155552E+10 | 0.871022E+09 | 0.684499E+09 | 0.00 | 0.00 |
November | 0.193378E+10 | 0.842328E+09 | 0.119662E+10 | 0.621813E+09 | 0.574807E+09 | 0.00 | 0.00 |
December | 0.170945E+10 | 0.994963E+09 | 0.110509E+10 | 0.605032E+09 | 0.500055E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.345596E+11 | 0.875342E+10 | 0.204131E+11 | 0.112929E+11 | 0.912020E+10 | 0.00 | 0.00 |
Minimum of Months | 0.170945E+10 | 0.419876E+09 | 0.110509E+10 | 0.605032E+09 | 0.480881E+09 | 0.00 | 0.00 |
Maximum of Months | 0.401974E+10 | 0.116100E+10 | 0.221678E+10 | 0.130702E+10 | 0.104823E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.323282E+11 | 0.155243E+11 | 0.631493E+10 | 0.380808E+10 | 0.250684E+10 | 0.00 | 0.00 |
February | 0.391420E+11 | 0.120476E+11 | 0.697273E+10 | 0.424246E+10 | 0.273026E+10 | 0.00 | 0.00 |
March | 0.569039E+11 | 0.129155E+11 | 0.962548E+10 | 0.585839E+10 | 0.376710E+10 | 0.00 | 0.00 |
April | 0.824900E+11 | 0.128350E+11 | 0.108470E+11 | 0.673141E+10 | 0.411561E+10 | 0.00 | 0.00 |
May | 0.800980E+11 | 0.122891E+11 | 0.110700E+11 | 0.622061E+10 | 0.484937E+10 | 0.00 | 0.00 |
June | 0.789941E+11 | 0.124765E+11 | 0.101860E+11 | 0.508269E+10 | 0.510334E+10 | 0.00 | 0.00 |
July | 0.960493E+11 | 0.154298E+11 | 0.114621E+11 | 0.599764E+10 | 0.546443E+10 | 0.00 | 0.00 |
August | 0.797259E+11 | 0.149618E+11 | 0.104234E+11 | 0.515337E+10 | 0.526999E+10 | 0.00 | 0.00 |
September | 0.729987E+11 | 0.135422E+11 | 0.889095E+10 | 0.432562E+10 | 0.456532E+10 | 0.00 | 0.00 |
October | 0.565614E+11 | 0.150115E+11 | 0.807973E+10 | 0.451141E+10 | 0.356831E+10 | 0.00 | 0.00 |
November | 0.404031E+11 | 0.128778E+11 | 0.624302E+10 | 0.324654E+10 | 0.299648E+10 | 0.00 | 0.00 |
December | 0.339753E+11 | 0.134566E+11 | 0.578897E+10 | 0.318217E+10 | 0.260680E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.749670E+12 | 0.163368E+12 | 0.105904E+12 | 0.583604E+11 | 0.475439E+11 | 0.00 | 0.00 |
Minimum of Months | 0.323282E+11 | 0.120476E+11 | 0.578897E+10 | 0.318217E+10 | 0.250684E+10 | 0.00 | 0.00 |
Maximum of Months | 0.960493E+11 | 0.155243E+11 | 0.114621E+11 | 0.673141E+10 | 0.546443E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.42 | 15.96 | 13.59 | 3.30 | 9.49 | 57.21 | 169.93 | 0.03 |
February | 20.87 | 16.70 | 13.89 | 5.53 | 11.19 | 68.99 | 182.59 | 0.00 |
March | 21.57 | 17.63 | 15.09 | 5.59 | 12.13 | 85.97 | 199.13 | 0.00 |
April | 24.11 | 19.68 | 17.40 | 4.69 | 15.31 | 97.05 | 212.67 | 0.01 |
May | 26.41 | 22.40 | 20.67 | 5.05 | 18.50 | 110.67 | 177.92 | 0.00 |
June | 27.68 | 24.06 | 22.67 | 3.87 | 20.33 | 120.35 | 147.07 | 0.00 |
July | 28.13 | 24.25 | 22.77 | 2.86 | 20.30 | 124.71 | 163.26 | 0.00 |
August | 27.97 | 24.38 | 23.03 | 3.45 | 20.36 | 120.27 | 145.14 | 0.08 |
September | 27.49 | 23.91 | 22.56 | 3.39 | 20.13 | 107.67 | 134.94 | 0.00 |
October | 26.35 | 22.68 | 21.10 | 3.72 | 17.49 | 81.44 | 160.40 | 0.04 |
November | 23.59 | 20.24 | 18.46 | 4.39 | 14.74 | 70.67 | 140.11 | 0.00 |
December | 20.30 | 17.47 | 15.75 | 3.70 | 12.21 | 59.50 | 147.31 | 0.00 |
Annual Sum or Average | 24.51 | 20.80 | 18.94 | 4.12 | 16.04 | 92.16 | 164.97 | 0.01 |
Minimum of Months | 19.42 | 15.96 | 13.59 | 2.86 | 9.49 | 57.21 | 134.94 | 0.00 |
Maximum of Months | 28.13 | 24.38 | 23.03 | 5.59 | 20.36 | 124.71 | 212.67 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.90 | 02-JAN-14:20 | 24.35 | 22.57 | 2.37 | 19.46 | 142.33 | 666.50 |
February | 29.40 | 11-FEB-13:00 | 24.15 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 29.40 | 13-MAR-15:00 | 22.41 | 19.40 | 6.20 | 21.27 | 178.00 | 499.00 |
April | 32.20 | 17-APR-14:00 | 19.76 | 12.80 | 5.20 | 21.27 | 367.00 | 219.50 |
May | 34.40 | 22-MAY-12:00 | 23.24 | 18.30 | 5.70 | 25.99 | 382.50 | 457.50 |
June | 32.20 | 11-JUN-12:00 | 23.83 | 20.60 | 3.60 | 23.15 | 181.50 | 762.50 |
July | 35.60 | 29-JUL-15:00 | 24.39 | 20.00 | 3.60 | 25.66 | 281.50 | 374.50 |
August | 33.90 | 23-AUG-12:00 | 25.44 | 22.20 | 5.70 | 24.50 | 261.50 | 640.00 |
September | 32.20 | 08-SEP-14:00 | 23.42 | 20.00 | 2.10 | 21.61 | 221.50 | 576.00 |
October | 32.20 | 09-OCT-10:00 | 23.83 | 20.60 | 3.10 | 25.16 | 286.50 | 457.50 |
November | 30.00 | 17-NOV-14:00 | 22.20 | 18.90 | 4.10 | 19.35 | 178.50 | 412.50 |
December | 28.90 | 10-DEC-14:20 | 22.91 | 20.40 | 7.87 | 19.82 | 162.67 | 585.17 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 19.76 | 12.80 | 2.10 | 19.35 | 142.33 | 219.50 | |
Maximum of Months | 35.60 | 25.44 | 22.57 | 7.87 | 25.99 | 382.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 25-JAN-04:00 | 4.59 | -1.7 | 3.10 | -7.3 | 0.00 | 0.00 |
February | 5.00 | 04-FEB-06:00 | 1.99 | -2.8 | 5.70 | -11.9 | 0.00 | 0.00 |
March | 6.70 | 16-MAR-04:00 | 4.49 | 1.70 | 4.60 | -9.2 | 0.00 | 0.00 |
April | 14.40 | 02-APR-05:49 | 13.38 | 12.70 | 1.60 | 0.69 | 0.00 | 0.00 |
May | 20.60 | 01-MAY-04:00 | 19.45 | 18.90 | 1.00 | 7.95 | 0.00 | 0.00 |
June | 22.80 | 05-JUN-14:00 | 20.57 | 19.40 | 2.10 | 18.46 | 245.00 | 55.00 |
July | 22.80 | 02-JUL-15:00 | 21.59 | 21.10 | 4.60 | 20.92 | 155.00 | 8.50 |
August | 22.20 | 12-AUG-06:00 | 21.85 | 21.70 | 2.60 | 20.40 | 65.50 | 0.00 |
September | 22.20 | 05-SEP-05:00 | 21.37 | 21.10 | 2.60 | 13.54 | 0.00 | 0.00 |
October | 21.10 | 28-OCT-02:00 | 20.29 | 20.00 | 2.60 | 8.54 | 0.00 | 0.00 |
November | 10.00 | 27-NOV-02:00 | 8.82 | 7.80 | 3.10 | -4.6 | 0.00 | 0.00 |
December | 7.80 | 15-DEC-05:40 | 5.61 | 3.13 | 6.37 | -7.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.00 | 1.99 | -2.8 | 1.00 | -11.9 | 0.00 | 0.00 | |
Maximum of Months | 22.80 | 21.85 | 21.70 | 6.37 | 20.92 | 245.00 | 55.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.83 | 02-JAN-13:00 | 28.90 | 23.30 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 24.15 | 11-FEB-13:00 | 29.40 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 23.83 | 14-MAR-09:00 | 26.70 | 22.80 | 11.30 | 19.52 | 243.50 | 478.00 |
April | 24.58 | 01-APR-15:00 | 28.30 | 23.30 | 3.60 | 16.30 | 93.50 | 759.50 |
May | 26.05 | 28-MAY-14:00 | 28.90 | 25.00 | 5.20 | 25.66 | 289.00 | 98.50 |
June | 26.06 | 28-JUN-11:00 | 28.90 | 25.00 | 1.50 | 22.98 | 404.50 | 373.50 |
July | 26.39 | 12-JUL-10:00 | 30.60 | 25.00 | 4.60 | 23.82 | 287.50 | 574.00 |
August | 26.46 | 21-AUG-15:00 | 32.20 | 24.40 | 3.60 | 24.50 | 205.50 | 366.00 |
September | 26.31 | 22-SEP-16:00 | 30.00 | 25.00 | 6.20 | 28.91 | 54.00 | 21.00 |
October | 26.52 | 01-OCT-11:00 | 29.40 | 25.60 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 25.31 | 04-NOV-13:00 | 27.80 | 24.40 | 2.10 | 26.48 | 199.00 | 3.00 |
December | 24.31 | 24-DEC-14:00 | 27.20 | 23.30 | 2.10 | 23.66 | 201.50 | 114.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.83 | 26.70 | 22.20 | 1.50 | 16.30 | 54.00 | 0.00 | |
Maximum of Months | 26.52 | 32.20 | 25.60 | 11.30 | 28.91 | 404.50 | 759.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.30 | 02-JAN-13:00 | 28.90 | 24.83 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 22.80 | 11-FEB-16:19 | 27.60 | 24.09 | 5.70 | 18.94 | 101.33 | 565.33 |
March | 22.80 | 14-MAR-09:20 | 25.57 | 23.60 | 9.63 | 22.18 | 176.17 | 527.17 |
April | 23.30 | 01-APR-14:00 | 27.80 | 24.57 | 5.70 | 15.76 | 108.00 | 831.00 |
May | 25.00 | 28-MAY-12:00 | 27.80 | 25.74 | 6.70 | 22.98 | 249.50 | 244.50 |
June | 25.00 | 06-JUN-18:00 | 27.20 | 25.59 | 3.60 | 23.99 | 17.50 | 0.00 |
July | 25.00 | 12-JUL-03:00 | 27.20 | 25.59 | 1.50 | 19.70 | 0.00 | 0.00 |
August | 25.60 | 21-AUG-11:00 | 28.90 | 26.35 | 2.60 | 23.15 | 567.00 | 173.50 |
September | 25.00 | 22-SEP-00:00 | 27.80 | 25.31 | 3.60 | 20.92 | 0.00 | 0.00 |
October | 25.60 | 01-OCT-11:00 | 29.40 | 26.52 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 24.40 | 05-NOV-01:19 | 26.10 | 24.93 | 2.03 | 16.37 | 0.00 | 0.00 |
December | 23.90 | 24-DEC-08:00 | 23.90 | 23.90 | 2.60 | 17.75 | 168.50 | 167.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.80 | 23.90 | 23.60 | 1.50 | 15.76 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 29.40 | 26.52 | 9.63 | 28.43 | 567.00 | 831.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.73 | 28.77 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.06 | 35.04 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 26.11 | 42.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.63 | 49.05 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.20 | 48.15 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 30.41 | 45.99 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.58 | 45.60 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.50 | 40.49 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 27.97 | 35.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 26.40 | 29.31 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.21 | 26.63 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 27.83 | 39.80 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.73 | 26.63 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.686004E+09 | -611938511.3 | 0.00 | 0.00 | 744.00 | 0.00 | -74065283.1 | 58.99 | 0.00 | 0.00 |
February | 0.623587E+09 | -556839834.2 | 0.00 | 0.00 | 672.00 | 0.00 | -66747604.5 | 58.99 | 0.00 | 0.00 |
March | 0.703646E+09 | -630606444.7 | 0.00 | 0.00 | 744.00 | 0.00 | -73039827.0 | 58.99 | 0.00 | 0.00 |
April | 0.627745E+09 | -558833808.2 | 0.00 | 0.00 | 720.00 | 0.00 | -68910868.5 | 58.99 | 0.00 | 0.00 |
May | 0.622695E+09 | -552228375.9 | 0.00 | 0.00 | 744.00 | 0.00 | -70466221.6 | 58.99 | 0.00 | 0.00 |
June | 0.595890E+09 | -527947202.1 | 0.00 | 0.00 | 720.00 | 0.00 | -67943275.0 | 58.99 | 0.00 | 0.00 |
July | 0.570853E+09 | -501263809.6 | 0.00 | 0.00 | 744.00 | 0.00 | -69588936.0 | 58.99 | 0.00 | 0.00 |
August | 0.614900E+09 | -544828543.1 | 0.00 | 0.00 | 744.00 | 0.00 | -70071378.0 | 58.99 | 0.00 | 0.00 |
September | 0.593569E+09 | -525944263.3 | 0.00 | 0.00 | 720.00 | 0.00 | -67625069.4 | 58.99 | 0.00 | 0.00 |
October | 0.624560E+09 | -554353639.9 | 0.00 | 0.00 | 744.00 | 0.00 | -70206428.1 | 58.99 | 0.00 | 0.00 |
November | 0.628459E+09 | -559013173.3 | 0.00 | 0.00 | 720.00 | 0.00 | -69446165.3 | 58.99 | 0.00 | 0.00 |
December | 0.676561E+09 | -603020369.8 | 0.00 | 0.00 | 744.00 | 0.00 | -73540366.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.756847E+10 | -0.672682E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -841651423.1 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.570853E+09 | -630606444.7 | 0.00 | 0.00 | 672.00 | 0.00 | -74065283.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.703646E+09 | -501263809.6 | 0.00 | 0.00 | 744.00 | 0.00 | -66747604.5 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.76 | 0.50 | 01-JAN-11:20 | 162.62 | 0.00 | 0.00 | 27.17 | 663.57 | 0.00 | 0.00 | 19.83 |
February | 304.33 | 0.73 | 0.50 | 01-FEB-11:09 | 1193.93 | 0.00 | 0.00 | 61.00 | 472.17 | 0.00 | 0.00 | 35.00 |
March | 362.67 | 0.71 | 0.50 | 02-MAR-13:30 | 310.52 | 0.00 | 0.00 | 104.33 | 181.97 | 0.00 | 0.00 | 56.67 |
April | 357.50 | 0.68 | 0.50 | 01-APR-11:09 | 257.83 | 0.00 | 0.00 | 117.33 | 764.58 | 0.00 | 0.00 | 98.00 |
May | 389.00 | 0.68 | 0.50 | 01-MAY-10:30 | 1077.49 | 0.00 | 0.00 | 176.33 | 199.46 | 0.00 | 0.00 | 71.67 |
June | 388.17 | 0.68 | 0.50 | 01-JUN-09:00 | 313.36 | 0.00 | 0.00 | 169.50 | 200.38 | 0.00 | 0.00 | 87.17 |
July | 403.83 | 0.66 | 0.50 | 01-JUL-09:30 | 659.91 | 0.00 | 0.00 | 192.83 | 215.98 | 0.00 | 0.00 | 105.67 |
August | 348.33 | 0.65 | 0.50 | 01-AUG-10:09 | 1030.32 | 0.00 | 0.00 | 193.00 | 241.14 | 0.00 | 0.00 | 115.17 |
September | 349.67 | 0.66 | 0.50 | 01-SEP-09:50 | 286.95 | 0.00 | 0.00 | 149.50 | 229.53 | 0.00 | 0.00 | 104.00 |
October | 323.50 | 0.70 | 0.50 | 02-OCT-11:39 | 225.44 | 0.00 | 0.00 | 96.00 | 260.41 | 0.00 | 0.00 | 53.50 |
November | 314.83 | 0.71 | 0.50 | 01-NOV-10:09 | 198.07 | 0.00 | 0.00 | 53.50 | 606.16 | 0.00 | 0.00 | 43.83 |
December | 282.67 | 0.74 | 0.50 | 01-DEC-11:30 | 179.94 | 0.00 | 0.00 | 20.83 | 150.21 | 0.00 | 0.00 | 2.50 |
Annual Sum or Average | 4111.50 | 0.69 | 502.85 | 0.00 | 0.00 | 1361.33 | 339.99 | 0.00 | 0.00 | 793.00 | ||
Minimum of Months | 282.67 | 0.65 | 0.50 | 162.62 | 0.00 | 0.00 | 20.83 | 150.21 | 0.00 | 0.00 | 2.50 | |
Maximum of Months | 403.83 | 0.76 | 0.50 | 1193.93 | 0.00 | 0.00 | 193.00 | 764.58 | 0.00 | 0.00 | 115.17 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.64 | 0.50 | 01-JAN-10:09 | 639.80 | 11.75 | 0.00 | 129.17 | 403.75 | 18.01 | 42.50 | 122.00 |
February | 304.33 | 0.62 | 0.50 | 01-FEB-09:30 | 486.88 | 12.46 | 0.00 | 148.00 | 184.01 | 16.11 | 32.17 | 114.00 |
March | 362.67 | 0.61 | 0.50 | 01-MAR-11:20 | 259.85 | 12.87 | 0.00 | 208.00 | 218.33 | 16.66 | 62.17 | 162.17 |
April | 357.50 | 0.59 | 0.50 | 01-APR-08:39 | 289.09 | 13.41 | 0.00 | 237.33 | 1043.71 | 17.15 | 83.33 | 195.17 |
May | 389.00 | 0.59 | 0.50 | 01-MAY-07:49 | 304.40 | 13.60 | 0.00 | 262.17 | 263.16 | 17.21 | 82.33 | 216.17 |
June | 388.17 | 0.60 | 0.50 | 01-JUN-07:40 | 318.55 | 13.38 | 0.00 | 259.50 | 278.79 | 16.86 | 80.33 | 223.00 |
July | 403.83 | 0.58 | 0.50 | 01-JUL-07:10 | 337.08 | 14.13 | 0.00 | 285.33 | 291.65 | 17.68 | 100.17 | 240.00 |
August | 348.33 | 0.58 | 0.50 | 01-AUG-07:40 | 539.89 | 14.12 | 0.00 | 275.50 | 449.40 | 17.70 | 94.17 | 230.50 |
September | 349.67 | 0.58 | 0.50 | 01-SEP-07:40 | 962.62 | 14.17 | 0.00 | 248.50 | 832.41 | 17.68 | 94.83 | 205.00 |
October | 323.50 | 0.61 | 0.50 | 02-OCT-11:39 | 259.74 | 13.26 | 0.00 | 208.50 | 215.54 | 16.93 | 60.50 | 166.33 |
November | 314.83 | 0.62 | 0.50 | 01-NOV-08:30 | 228.24 | 12.92 | 0.00 | 168.00 | 189.58 | 16.44 | 35.67 | 125.33 |
December | 282.67 | 0.62 | 0.50 | 01-DEC-08:00 | 209.98 | 12.36 | 0.00 | 140.50 | 173.87 | 15.81 | 19.50 | 99.00 |
Annual Sum or Average | 4111.50 | 0.60 | 400.70 | 13.27 | 0.00 | 2570.50 | 383.98 | 17.05 | 787.67 | 2098.67 | ||
Minimum of Months | 282.67 | 0.58 | 0.50 | 209.98 | 11.75 | 0.00 | 129.17 | 173.87 | 15.81 | 19.50 | 99.00 | |
Maximum of Months | 403.83 | 0.64 | 0.50 | 962.62 | 14.17 | 0.00 | 285.33 | 1043.71 | 18.01 | 100.17 | 240.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.84 | 0.65 | 22-JAN-15:39 | 231.89 | 21.85 | 114.00 | 22.17 | 93.99 | 19.41 | 84.17 | 0.00 |
February | 304.33 | 0.82 | 0.61 | 10-FEB-16:10 | 305.94 | 22.28 | 123.67 | 33.33 | 211.38 | 21.82 | 117.00 | 20.33 |
March | 362.67 | 0.79 | 0.61 | 01-MAR-16:10 | 339.20 | 22.40 | 146.83 | 51.50 | 281.24 | 23.10 | 162.50 | 43.33 |
April | 357.50 | 0.79 | 0.61 | 01-APR-16:10 | 217.72 | 20.33 | 117.00 | 19.50 | 200.76 | 21.57 | 152.17 | 39.50 |
May | 389.00 | 0.79 | 0.61 | 01-MAY-15:20 | 218.47 | 19.72 | 104.00 | 24.33 | 177.91 | 21.06 | 154.67 | 31.00 |
June | 388.17 | 0.80 | 0.61 | 01-JUN-14:20 | 214.88 | 19.00 | 89.33 | 32.50 | 157.49 | 20.31 | 141.33 | 19.00 |
July | 403.83 | 0.78 | 0.61 | 01-JUL-15:30 | 236.94 | 19.89 | 124.67 | 46.50 | 177.63 | 21.15 | 174.83 | 31.00 |
August | 348.33 | 0.77 | 0.61 | 01-AUG-16:30 | 240.75 | 20.29 | 130.17 | 46.17 | 181.90 | 21.46 | 172.33 | 30.33 |
September | 349.67 | 0.79 | 0.61 | 01-SEP-14:50 | 238.22 | 20.94 | 130.33 | 38.00 | 162.07 | 21.68 | 159.67 | 21.00 |
October | 323.50 | 0.79 | 0.61 | 02-OCT-15:09 | 258.53 | 22.89 | 158.00 | 45.50 | 182.80 | 23.30 | 164.00 | 22.00 |
November | 314.83 | 0.82 | 0.61 | 01-NOV-16:10 | 199.01 | 22.05 | 135.83 | 15.67 | 118.53 | 21.40 | 127.83 | 6.50 |
December | 282.67 | 0.82 | 0.65 | 05-DEC-15:09 | 216.50 | 22.94 | 126.00 | 19.50 | 105.17 | 20.48 | 96.83 | 0.00 |
Annual Sum or Average | 4111.50 | 0.80 | 243.04 | 21.10 | 1499.83 | 394.67 | 173.50 | 21.41 | 1707.33 | 264.00 | ||
Minimum of Months | 282.67 | 0.77 | 0.61 | 199.01 | 19.00 | 89.33 | 15.67 | 93.99 | 19.41 | 84.17 | 0.00 | |
Maximum of Months | 403.83 | 0.84 | 0.65 | 339.20 | 22.94 | 158.00 | 51.50 | 281.24 | 23.30 | 174.83 | 43.33 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 37041983.19 | 4100.84 | 25-JAN-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 19936959.20 | 9532.25 | 04-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 36624210.59 | 6723.06 | 16-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2085393.72 | 1518.17 | 13-NOV-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 37061913.44 | 6082.07 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132750E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37061913.44 | 9532.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.471681E+10 | 0.340266E+10 | 28133.25 | 07-JAN-06:02 | 13982.54 | 0.00 |
February | 0.00 | 0.00 | 0.535223E+10 | 0.393989E+10 | 28192.19 | 11-FEB-06:02 | 13901.58 | 0.00 |
March | 0.00 | 0.00 | 0.722072E+10 | 0.513336E+10 | 28650.51 | 06-MAR-06:01 | 13882.99 | 0.00 |
April | 0.00 | 0.00 | 0.955227E+10 | 0.692127E+10 | 28511.62 | 13-APR-05:01 | 15230.26 | 0.00 |
May | 0.00 | 0.00 | 0.128965E+11 | 0.873887E+10 | 29284.95 | 30-MAY-05:01 | 14287.09 | 0.00 |
June | 0.00 | 0.00 | 0.145152E+11 | 0.923216E+10 | 29239.11 | 19-JUN-05:02 | 13766.82 | 0.00 |
July | 0.00 | 0.00 | 0.148964E+11 | 0.966493E+10 | 29263.89 | 24-JUL-05:01 | 15106.05 | 0.00 |
August | 0.00 | 0.00 | 0.158203E+11 | 0.100822E+11 | 29366.91 | 14-AUG-05:02 | 13877.37 | 0.00 |
September | 0.00 | 0.00 | 0.141283E+11 | 0.908732E+10 | 29117.78 | 25-SEP-05:01 | 15495.82 | 0.00 |
October | 0.00 | 0.00 | 0.125251E+11 | 0.832366E+10 | 29000.60 | 10-OCT-05:01 | 15707.05 | 0.00 |
November | 0.00 | 0.00 | 0.927879E+10 | 0.618740E+10 | 29064.18 | 04-NOV-05:01 | 13817.78 | 0.00 |
December | 0.00 | 0.00 | 0.553642E+10 | 0.395388E+10 | 28750.38 | 11-DEC-06:01 | 14607.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.126439E+12 | 0.846676E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.471681E+10 | 0.340266E+10 | 28133.25 | 13766.82 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.158203E+11 | 0.100822E+11 | 29366.91 | 15707.05 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.207998E+10 | 0.125382E+10 | 35874.38 | 01-JAN-13:35 | 23213.04 | 0.00 |
February | 0.00 | 0.00 | 0.372896E+10 | 0.261272E+10 | 51096.32 | 19-FEB-13:45 | 30558.11 | 0.00 |
March | 0.00 | 0.00 | 0.764003E+10 | 0.484292E+10 | 65210.27 | 27-MAR-17:10 | 42865.10 | 0.00 |
April | 0.00 | 0.00 | 0.179707E+11 | 0.122181E+11 | 75519.73 | 13-APR-17:43 | 48800.94 | 0.00 |
May | 0.00 | 0.00 | 0.304692E+11 | 0.194298E+11 | 78527.55 | 20-MAY-05:06 | 44797.71 | 0.00 |
June | 0.00 | 0.00 | 0.380177E+11 | 0.229100E+11 | 79724.31 | 08-JUN-05:10 | 41752.46 | 0.00 |
July | 0.00 | 0.00 | 0.440228E+11 | 0.275303E+11 | 78927.54 | 26-JUL-05:01 | 44416.66 | 0.00 |
August | 0.00 | 0.00 | 0.410821E+11 | 0.246937E+11 | 79424.51 | 05-AUG-05:09 | 43568.49 | 0.00 |
September | 0.00 | 0.00 | 0.378982E+11 | 0.230430E+11 | 79523.36 | 23-SEP-05:09 | 42656.57 | 0.00 |
October | 0.00 | 0.00 | 0.275052E+11 | 0.169834E+11 | 83265.12 | 04-OCT-05:01 | 38376.01 | 0.00 |
November | 0.00 | 0.00 | 0.129017E+11 | 0.759135E+10 | 60514.37 | 23-NOV-11:45 | 32466.05 | 0.00 |
December | 0.00 | 0.00 | 0.483437E+10 | 0.301998E+10 | 74516.30 | 10-DEC-14:13 | 48555.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.268151E+12 | 0.166129E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.207998E+10 | 0.125382E+10 | 35874.38 | 23213.04 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.440228E+11 | 0.275303E+11 | 83265.12 | 48800.94 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.481536E+09 | 0.21 | 1200.53 | 02-JAN-06:02 | 0.89 |
February | 0.442986E+09 | 0.21 | 1200.53 | 11-FEB-06:02 | 0.89 |
March | 0.526026E+09 | 0.23 | 1200.53 | 04-MAR-06:02 | 0.89 |
April | 0.504678E+09 | 0.23 | 1200.53 | 01-APR-05:01 | 0.90 |
May | 0.569249E+09 | 0.24 | 1200.53 | 01-MAY-05:01 | 0.89 |
June | 0.613786E+09 | 0.26 | 1200.53 | 01-JUN-05:01 | 0.89 |
July | 0.642788E+09 | 0.25 | 1200.53 | 01-JUL-05:01 | 0.89 |
August | 0.681641E+09 | 0.27 | 1200.53 | 01-AUG-05:01 | 0.89 |
September | 0.603339E+09 | 0.25 | 1200.53 | 01-SEP-05:01 | 0.89 |
October | 0.551562E+09 | 0.23 | 1200.53 | 02-OCT-05:01 | 0.89 |
November | 0.479066E+09 | 0.21 | 1200.53 | 01-NOV-05:01 | 0.89 |
December | 0.485402E+09 | 0.21 | 1200.53 | 01-DEC-06:01 | 0.89 |
Annual Sum or Average | 0.658206E+10 | 0.23 | |||
Minimum of Months | 0.442986E+09 | 0.21 | 1200.53 | 0.89 | |
Maximum of Months | 0.681641E+09 | 0.27 | 1200.53 | 0.90 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.111787E+10 | 0.20 | 1124.10 | 04-JAN-15:20 | 0.52 |
February | 0.103751E+10 | 0.21 | 1690.69 | 19-FEB-13:45 | 0.67 |
March | 0.122806E+10 | 0.22 | 2369.36 | 27-MAR-17:10 | 0.80 |
April | 0.122495E+10 | 0.25 | 2810.24 | 02-APR-13:53 | 0.87 |
May | 0.139695E+10 | 0.30 | 2810.24 | 05-MAY-17:08 | 0.87 |
June | 0.151370E+10 | 0.36 | 2810.24 | 01-JUN-17:08 | 0.87 |
July | 0.162212E+10 | 0.38 | 2810.24 | 01-JUL-17:08 | 0.87 |
August | 0.161394E+10 | 0.37 | 2810.24 | 01-AUG-05:06 | 0.86 |
September | 0.150517E+10 | 0.35 | 2810.24 | 01-SEP-17:06 | 0.87 |
October | 0.132405E+10 | 0.28 | 2810.24 | 02-OCT-17:08 | 0.86 |
November | 0.111438E+10 | 0.21 | 2008.43 | 23-NOV-11:45 | 0.73 |
December | 0.113169E+10 | 0.20 | 2810.24 | 10-DEC-14:13 | 0.86 |
Annual Sum or Average | 0.158304E+11 | 0.28 | |||
Minimum of Months | 0.103751E+10 | 0.20 | 1124.10 | 0.52 | |
Maximum of Months | 0.162212E+10 | 0.38 | 2810.24 | 0.87 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.158695E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.169579E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.218928E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.271098E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.355897E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.396199E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.415472E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.437291E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.387705E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.343849E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.260210E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.176928E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.359185E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.158695E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.437291E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.163124E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.196749E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.308377E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.558275E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.875681E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.106154E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.122809E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.114832E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.106057E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.794976E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.422391E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.230365E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.804846E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.163124E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.122809E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.481536E+09 | 0.471681E+10 | 37041983.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.442986E+09 | 0.535223E+10 | 19936959.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.526026E+09 | 0.722072E+10 | 36624210.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.504678E+09 | 0.955227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.569249E+09 | 0.128965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.613786E+09 | 0.145152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.642788E+09 | 0.148964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.681641E+09 | 0.158203E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.603339E+09 | 0.141283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.551562E+09 | 0.125251E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.479066E+09 | 0.927879E+10 | 2085393.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.485402E+09 | 0.553642E+10 | 37061913.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.658206E+10 | 0.126439E+12 | 0.132750E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.442986E+09 | 0.471681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.681641E+09 | 0.158203E+11 | 37061913.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.111787E+10 | 0.207998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103751E+10 | 0.372896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122806E+10 | 0.764003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122495E+10 | 0.179707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139695E+10 | 0.304692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151370E+10 | 0.380177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162212E+10 | 0.440228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161394E+10 | 0.410821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150517E+10 | 0.378982E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132405E+10 | 0.275052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111438E+10 | 0.129017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.113169E+10 | 0.483437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158304E+11 | 0.268151E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103751E+10 | 0.207998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.162212E+10 | 0.440228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.481536E+09 | 0.00 | 0.00 | 0.00 | 0.110541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.442986E+09 | 0.00 | 0.00 | 0.00 | 0.125281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.526026E+09 | 0.00 | 0.00 | 0.00 | 0.166325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.504678E+09 | 0.00 | 0.00 | 0.00 | 0.220630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.569249E+09 | 0.00 | 0.00 | 0.00 | 0.298972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.613786E+09 | 0.00 | 0.00 | 0.00 | 0.334820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.642788E+09 | 0.00 | 0.00 | 0.00 | 0.351193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.681641E+09 | 0.00 | 0.00 | 0.00 | 0.369127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.603339E+09 | 0.00 | 0.00 | 0.00 | 0.327371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.551562E+09 | 0.00 | 0.00 | 0.00 | 0.288692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.479066E+09 | 0.00 | 0.00 | 0.00 | 0.212303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.485402E+09 | 0.00 | 0.00 | 0.00 | 0.128388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.658206E+10 | 0.00 | 0.00 | 0.00 | 0.293364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.442986E+09 | 0.00 | 0.00 | 0.00 | 0.110541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.681641E+09 | 0.00 | 0.00 | 0.00 | 0.369127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.111787E+10 | 0.00 | 0.00 | 0.00 | 0.513364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103751E+10 | 0.00 | 0.00 | 0.00 | 0.929980E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122806E+10 | 0.00 | 0.00 | 0.00 | 0.185571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122495E+10 | 0.00 | 0.00 | 0.00 | 0.435780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139695E+10 | 0.00 | 0.00 | 0.00 | 0.735987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151370E+10 | 0.00 | 0.00 | 0.00 | 0.910169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162212E+10 | 0.00 | 0.00 | 0.00 | 0.106588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161394E+10 | 0.00 | 0.00 | 0.00 | 0.986926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150517E+10 | 0.00 | 0.00 | 0.00 | 0.910055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132405E+10 | 0.00 | 0.00 | 0.00 | 0.662572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111438E+10 | 0.00 | 0.00 | 0.00 | 0.310953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.113169E+10 | 0.00 | 0.00 | 0.00 | 0.117196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158304E+11 | 0.00 | 0.00 | 0.00 | 0.646542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103751E+10 | 0.00 | 0.00 | 0.00 | 0.513364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.162212E+10 | 0.00 | 0.00 | 0.00 | 0.106588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.127144E+09 | 0.404818E+09 | 0.00 | 2036639.53 | 87881.76 | 19553430.56 | 0.273178E+09 | 0.00 | 0.14 |
February | 75557064.71 | 0.481399E+09 | 0.00 | 1858764.45 | 467381.56 | 10849798.33 | 0.119233E+09 | 0.00 | 0.14 |
March | 91495458.56 | 0.689387E+09 | 0.00 | 2503826.92 | 0.00 | 18761054.66 | 0.186221E+09 | 0.00 | 0.15 |
April | 3186778.55 | 0.112433E+10 | 0.00 | 2472710.20 | 0.00 | 0.00 | 35175045.99 | 0.00 | 0.15 |
May | 0.00 | 0.193586E+10 | 0.00 | 1178607.49 | 0.00 | 0.00 | 42323.06 | 0.00 | 0.15 |
June | 0.00 | 0.257723E+10 | 0.00 | 168690.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
July | 0.00 | 0.286541E+10 | 0.00 | 29737.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
August | 0.00 | 0.291510E+10 | 0.00 | 168896.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
September | 0.00 | 0.255618E+10 | 0.00 | 275203.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
October | 0.00 | 0.201296E+10 | 0.00 | 764659.24 | 0.00 | 0.00 | 187208.96 | 0.00 | 0.14 |
November | 14162457.27 | 0.132554E+10 | 0.00 | 2055491.25 | 142805.71 | 2463223.59 | 20535802.05 | 0.00 | 0.14 |
December | 0.103105E+09 | 0.542035E+09 | 0.00 | 2554110.88 | 0.00 | 16378698.60 | 0.258003E+09 | 0.00 | 0.14 |
Annual Sum or Average | 0.414651E+09 | 0.194302E+11 | 0.00 | 16067338.62 | 698069.03 | 68006205.74 | 0.892575E+09 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.404818E+09 | 0.00 | 29737.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.127144E+09 | 0.291510E+10 | 0.00 | 2554110.88 | 467381.56 | 19553430.56 | 0.273178E+09 | 0.00 | 0.16 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.258164E+10 | 0.158039E+09 | 0.00 | 875714.52 | 11540889.70 | 0.00 | 0.257609E+09 | 0.00 | 0.20 |
February | 0.116138E+10 | 0.204747E+09 | 0.00 | 2861800.70 | 1957504.69 | 0.00 | 0.571188E+09 | 0.00 | 0.20 |
March | 0.157729E+10 | 0.553726E+09 | 0.00 | 2916264.51 | 53156.56 | 0.00 | 0.598949E+09 | 0.00 | 0.22 |
April | 0.275047E+09 | 0.200546E+10 | 0.00 | 4746924.07 | 538814.90 | 0.00 | 0.445646E+09 | 0.00 | 0.22 |
May | 28788159.56 | 0.497266E+10 | 0.00 | 557041.88 | 5128259.92 | 0.00 | 63074069.20 | 0.00 | 0.23 |
June | 115012.92 | 0.839571E+10 | 0.00 | 115129.55 | 12516120.06 | 0.00 | 10809366.95 | 0.00 | 0.25 |
July | 0.00 | 0.106867E+11 | 0.00 | 0.00 | 21703688.98 | 0.00 | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.966301E+10 | 0.00 | 255180.74 | 36977288.10 | 0.00 | 37192681.23 | 0.00 | 0.26 |
September | 0.00 | 0.835810E+10 | 0.00 | 68223.53 | 13906786.68 | 0.00 | 14054106.58 | 0.00 | 0.25 |
October | 48006360.60 | 0.510132E+10 | 0.00 | 579076.74 | 11936808.69 | 0.00 | 72361937.03 | 0.00 | 0.22 |
November | 0.457270E+09 | 0.219180E+10 | 0.00 | 1180267.71 | 7886608.66 | 0.00 | 0.270844E+09 | 0.00 | 0.20 |
December | 0.210696E+10 | 0.493239E+09 | 0.00 | 1788530.64 | 4998770.68 | 0.00 | 0.363448E+09 | 0.00 | 0.20 |
Annual Sum or Average | 0.823650E+10 | 0.527845E+11 | 0.00 | 15944154.57 | 0.129145E+09 | 0.00 | 0.270517E+10 | 0.00 | 0.22 |
Minimum of Months | 0.00 | 0.158039E+09 | 0.00 | 0.00 | 53156.56 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.258164E+10 | 0.106867E+11 | 0.00 | 4746924.07 | 36977288.10 | 0.00 | 0.598949E+09 | 0.00 | 0.26 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:00
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.639232E+12 | 0.281378E+11 | 0.00 | 0.885111E+10 | 0.843486E+10 |
February | 0.693928E+12 | 0.308788E+11 | 0.00 | 0.565154E+10 | 0.112742E+11 |
March | 0.961387E+12 | 0.401881E+11 | 0.00 | 0.478143E+10 | 0.183985E+11 |
April | 0.105610E+13 | 0.462741E+11 | 0.00 | -0.102600E+10 | 0.340871E+11 |
May | 0.103672E+13 | 0.481688E+11 | 0.00 | -0.919951E+10 | 0.537153E+11 |
June | 0.943486E+12 | 0.548202E+11 | 0.00 | -0.169622E+11 | 0.649828E+11 |
July | 0.103581E+13 | 0.618719E+11 | 0.00 | -0.207278E+11 | 0.730900E+11 |
August | 0.108427E+13 | 0.513369E+11 | 0.00 | -0.194354E+11 | 0.704630E+11 |
September | 0.839728E+12 | 0.507439E+11 | 0.00 | -0.168320E+11 | 0.644008E+11 |
October | 0.813246E+12 | 0.406127E+11 | 0.00 | -0.109168E+11 | 0.495429E+11 |
November | 0.606018E+12 | 0.315777E+11 | 0.00 | -815096901.2 | 0.274142E+11 |
December | 0.612155E+12 | 0.300441E+11 | 0.00 | 0.634326E+10 | 0.128456E+11 |
Annual Sum or Average | 0.103221E+14 | 0.514655E+12 | 0.00 | -0.702876E+11 | 0.488649E+12 |
Minimum of Months | 0.606018E+12 | 0.281378E+11 | 0.00 | -0.207278E+11 | 0.843486E+10 |
Maximum of Months | 0.108427E+13 | 0.618719E+11 | 0.00 | 0.885111E+10 | 0.730900E+11 |