Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2023-10-16 10:41:43
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1015.97 | 210.12 | 210.12 |
Net Site Energy | 1015.97 | 210.12 | 210.12 |
Total Source Energy | 3214.01 | 664.72 | 664.72 |
Net Source Energy | 3214.01 | 664.72 | 664.72 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 27.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 134.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 64.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1014.26 | 1.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 27.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 134.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 63.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 25.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 27.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 134.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 64.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 25.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 24.24 | 0.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 209.77 | 0.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 24.24 | 0.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 209.77 | 0.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1014.261 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1014.261 | 100.00 |
Total On-Site and Utility Electric Sources | 1014.261 | 100.00 |
Total Electricity End Uses | 1014.261 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 3.83 |
Time Setpoint Not Met During Occupied Cooling | 4.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1848.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.61 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7186 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 15.0695 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 9.6875 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 11.2890 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 11.2890 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.7186 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 15.0695 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 9.6875 | 46.45 | 2.5587 | |
Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 11.2890 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-SEP-12:00 | 03-JAN-06:10 | - | - | - | - | - | - | - | - | - | - | 04-MAY-11:50 |
Heating | 0.00 | 25805.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 17550.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7456.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1744.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 83057.90 | 25805.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 25805.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 17550.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 5151.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1744.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 87.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1974.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 424.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 203.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 80.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3212.16 | 1.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 18.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 42.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 664.34 | 0.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 18.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 42.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 664.34 | 0.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.20 |
ZONE2 FINE STORAGE DIRECT AIR | 3.46 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 1.31 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 1.31 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 52687.26 |
PSZ-OFFICE HEATING COIL | 29103.52 |
PSZ-FINE STORAGE HEATING COIL | 106322.32 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 52687.26 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.20 | 1.20 | 1.20 | 1.20 | 1.20 | 1.20 | 1.00 | 1.00 | 1.20 |
PSZ-FINE STORAGE | 3.46 | 3.46 | 3.46 | 3.46 | 3.46 | 3.46 | 1.00 | 1.00 | 3.46 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.20 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 3.46 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.20 | 1365.62 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.46 | 3785.52 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.20 | 1.20 | 1.20 | 1.20 | 20254.06 | 29103.52 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 3.46 | 3.46 | 3.46 | 3.46 | 70126.33 | 106322.32 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.20 | 0.598898 | 1.20 | 20254.06 | 10447.46 | 20254.06 | 0.800920 | 0.800920 |
PSZ-FINE STORAGE COOLING COIL | 3.46 | 1.73 | 3.46 | 70126.33 | 34806.61 | 70126.33 | 0.771160 | 0.771160 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.719 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.792 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 15.069 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15.069 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 9.688 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 12.246 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2539.013 | 10.719 | 199.158 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2539.013 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 20997.932 | 15.069 | 699.931 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20997.932 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 31046.942 | 9.688 | 449.956 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 31046.942 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5959 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.7823 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 1.301 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 1.301 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.678 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.179 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6691 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6691 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53319041E-11 | 0.92099297E-16 | 0.18475806E-15 | 0.0000000 |
5 | 1 | -5.2159728 | 0.43155192E-04 | -0.26885250E-04 | 0.68722794E-11 |
6 | 0 | 5.8118483 | 0.59583229 | 0.59590233 | |
7 | 4 | 0.72249793E-12 | -0.16720573E-15 | 0.22015083E-14 | 0.12409536E-15 |
8 | 3 | -0.36459118E-03 | 0.53555631E-06 | -0.52695411E-04 | 0.13865996E-12 |
9 | 2 | 1.6915239 | 0.11971291E-01 | 1.1039557 | -0.69896550E-04 |
10 | 1 | -7.1930661 | 0.31446443 | -16.864389 | 0.32415671 |
11 | 0 | 6.0306730 | 0.20232993 | 16.289252 | |
12 | 4 | 0.62407051E-12 | 0.80447548E-15 | -0.19405657E-14 | 0.12807081E-15 |
13 | 3 | -0.32959465E-03 | 0.84747600E-06 | -0.47309261E-04 | 0.11981323E-12 |
14 | 2 | 1.6058071 | 0.19756964E-01 | 1.0389034 | -0.63182077E-04 |
15 | 1 | -7.3135607 | 0.53269638 | -16.443412 | 0.30760774 |
16 | 0 | 6.6091660 | 0.34862863 | 16.305639 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.19405657E-14 | 0.80447548E-15 | 0.62407051E-12 | 0.12807081E-15 |
85 | 3 | -0.47309261E-04 | 0.84747600E-06 | -0.32959465E-03 | 0.11981323E-12 |
86 | 2 | 1.0389034 | 0.19756964E-01 | 1.6058071 | -0.63182077E-04 |
87 | 1 | -16.443412 | 0.53269638 | -7.3135607 | 0.30760774 |
88 | 0 | 16.305639 | 0.34862863 | 6.6091660 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.6283_SHGC_SOUTH_0.25 | 34 | 1 | VerySmooth | 3.572 | 3.572 | 1.000 | 0.252 | ||
2 | NONRESWINDOW_U_0.6283_SHGC_NORTH_0.25 | 35 | 1 | VerySmooth | 3.572 | 3.572 | 1.000 | 0.252 | ||
3 | NONRESWINDOW_U_0.6283_SHGC_EAST_0.25 | 36 | 1 | VerySmooth | 3.572 | 3.572 | 1.000 | 0.252 | ||
4 | NONRESWINDOW_U_0.6283_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 3.572 | 3.572 | 1.000 | 0.252 | ||
5 | SKYLIGHT_U_1.02_SHGC_0.39 | 38 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.391 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.15349 | 0.58024 | 0.58024 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.80019E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.15349 | 0.58024 | 0.58024 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.80019E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.15349 | 0.58024 | 0.58024 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.80019E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.15349 | 0.58024 | 0.58024 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.80019E-002 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.22227 | 0.21773 | 0.21773 | 0.39000 | 0.13867 | 0.18233 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.849 | 0.366 | 0.255 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 0.153 | 6.473E-004 | 9.992E-004 | 0.546 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.780 | 5.598E-004 | 3.565E-004 | 0.951 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 3.433 | 1.071E-003 | 6.996E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11907.03813 | 14288.44575 | 0.99816 | 1.19780 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 30.64733 | 8.23245E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 8366.02020 | 10039.22424 | 0.23915 | 0.28698 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 3.80000 | 5.05843E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 44106.97695 | 52928.37234 | 2.88222 | 3.45866 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 31.30000 | 8.23349E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 22088.67079 | 26506.40494 | 0.53218 | 0.63861 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 3.80000 | 5.05843E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 31.30000 | 8.23349E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 43906.04856 | 52687.25827 | 1.09311 | 1.31173 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 17748.61 | 1.19780 | 1.19780 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 8562.34 | 0.28698 | 0.28698 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 62692.45 | 3.45866 | 3.45866 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 24466.39 | 0.63861 | 0.63861 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.19780 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.45866 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.31173 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 1.31173 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 52687.25673 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 52687.25827 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.19780 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.19780 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.19780 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.19780 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.19780 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.19780 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.45866 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.45866 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.45866 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.45866 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.45866 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.45866 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.19780 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.45866 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.19780 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.19780 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1365.61869 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.19780 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.19780 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.19780 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.19780 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.19780 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.59890 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.19780 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20254.06000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 10447.46484 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20254.06000 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80092 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80092 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20254.06000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29103.51528 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 29103.51528 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.45866 |
47 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.45866 |
49 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3785.52306 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.45866 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.45866 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.45866 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.45866 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.45866 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.72933 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.45866 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 70126.33000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 34806.60676 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 70126.33000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.77116 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.77116 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 70126.33000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 106322.32087 |
64 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
66 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 106322.32087 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 19324.5 | 10.74 | 10.12 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 67440.5 | 10.47 | 9.87 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 2.9226186105E-002 | 2.3613664624E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.1193516913 | 0.1473954975 | Pass | Pass | 0.1867795625 | 1.5812883965 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 3.7256736410E-002 | 3.9692491030E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 11832.91 | 506.17 | 0.00 | 128.56 | 130.18 | 12597.88 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.00 | 2 | |||
Feb | 59.00 | 53 | |||
Mar | 58.58 | 43 | |||
Apr | 46.42 | 14 | |||
May | 18.00 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 3.00 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 18.00 | 12 | |||
Dec | 4.00 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.089 | 1.301 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.089 | 1.301 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.089 | 1.301 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.551 | 0.596 | 3204.84 | 3170.23 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.992 | 1.301 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.992 | 1.301 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.6283_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.572 | 0.252 | 0.251 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.6283_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.572 | 0.252 | 0.251 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.6283_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.572 | 0.252 | 0.251 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.6283_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.572 | 0.252 | 0.251 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.27 | 5.046 | 0.450 | 0.450 | |||||||||||||||||
North Total or Average | 6.51 | 3.572 | 0.252 | 0.251 | |||||||||||||||||
Non-North Total or Average | 45.76 | 5.256 | 0.478 | 0.478 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.7186 | 236.88 | 2539.01 | LightsWired | LTG_SCH_OFFICE | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.86 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 15.0695 | 1393.41 | 20997.93 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 239.15 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 9.6875 | 3204.84 | 31046.94 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 353.60 |
Interior Lighting Total | 11.2890 | 4835.13 | 54583.89 | 623.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 8532.22 | AstronomicalClock | - | 83.75 | 83.75 | 134.14 | |
Exterior Lighting Total | 8532.22 | 134.14 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20254.06 | 16221.88 | 4032.18 | 0.80 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 70126.33 | 54078.62 | 16047.71 | 0.77 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 19324.5 | 10.74 | 10.12 | ||||
PSZ-FINE STORAGE COOLING COIL | 67440.5 | 10.47 | 9.87 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 52687.26 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 29103.52 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 106322.32 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 1.31 | 121.87 | 92.91 | 1.00 | 3.89 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.20 | 1365.62 | 1140.11 | 1.00 | 1.32 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 3.46 | 3785.52 | 1094.51 | 1.00 | 1.22 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11907.04 | 14288.45 | 60.32 | 0.998 | 1.198 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 23.90 | 23.90 | 0.00825 | 30.65 | 0.00823 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 44106.98 | 52928.37 | 37.98 | 2.882 | 3.459 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 26.70 | 26.70 | 0.00825 | 31.30 | 0.00823 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 0.00 | 32.19 | 0.00830 | 31.30 | 0.00823 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8366.02 | 10039.22 | 42.38 | 0.239 | 0.287 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00772 | 3.80 | 0.00506 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 22088.67 | 26506.40 | 19.02 | 0.532 | 0.639 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 15.56 | 15.56 | 0.00671 | 3.80 | 0.00506 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 43906.05 | 52687.26 | 16.44 | 1.093 | 1.312 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00614 | 3.80 | 0.00506 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.20 | 1.20 | 0.29 | 0.29 | 1.1978 | 1.1978 | 1.1978 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.46 | 3.46 | 0.64 | 0.64 | 3.4587 | 3.4587 | 3.4587 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 52687.257 | 52687.257 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 52687.26 | 52687.26 | 1.311729 | 10.00 | 8.20 | 0.00613784 | 43.33 | 21.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 10.00 | 0.00613784 | 79.1263 | 52687.26 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 20254.060 | 16221.882 | 1.197800 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 20254.06 | 19436.23 | 1.197800 | 25.43 | 16.49 | 0.00825283 | 12.00 | 11.09 | 0.00800000 | 30.77 | 0.00823264 | 18.27 | 8.5394 | 23.90 | 0.00825472 | 43.8924 | 11899.56 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 29103.515 | 29103.515 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 29103.52 | 29103.52 | 1.197796 | 19.54 | 13.64 | 0.00748977 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 8.5394 | 21.10 | 0.00771678 | 48.6840 | 8366.02 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 70126.330 | 54078.621 | 3.458660 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 70126.33 | 67722.47 | 3.458660 | 28.17 | 17.43 | 0.00825170 | 12.00 | 11.09 | 0.00800000 | 31.30 | 0.00823349 | 18.45 | 12.2796 | 26.70 | 0.00825425 | 37.1566 | 44106.98 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 106322.321 | 106322.321 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 106322.32 | 106322.32 | 3.458661 | 14.11 | 10.45 | 0.00650912 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 12.2796 | 15.56 | 0.00671219 | 60.0558 | 22088.67 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 52687.257 | 52687.257 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 1.311729 | 1.55017375 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 52687.26 | 52687.26 | 1.0000 | 1.55017375 | 1.311729 | 10.00 | 8.20 | 0.00613784 | 25511.9 | 43.33 | 21.93 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 52687.26 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 10.00 | 0.00613784 | 10.00 | 0.00613784 | 79.1263 | 52687.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20254.060 | 16221.882 | 1.197800 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1816 | 1004.8586 | 1.1818 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.197796 | 1.41552937 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | Sensible | 20254.06 | 19436.23 | 1.0000 | 1.41553448 | 1.197800 | 25.43 | 16.49 | 0.00825283 | 46584.4 | 12.00 | 11.09 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20254.06 | 30.77 | 0.00823264 | 18.27 | 0.10228463 | 8.5394 | 23.90 | 0.00825472 | 23.90 | 0.00825472 | 43.8924 | 11899.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29103.515 | 29103.515 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.197796 | 1.41552937 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 29103.52 | 29103.52 | 1.0000 | 1.41552937 | 1.197796 | 19.54 | 13.64 | 0.00748977 | 38637.3 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29103.52 | 3.80 | 0.00505843 | 3.80 | 0.10228463 | 8.5394 | 21.01 | 0.00771678 | 21.10 | 0.00771678 | 48.6840 | 8366.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 70126.330 | 54078.621 | 3.458660 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1795 | 1004.8586 | 1.1818 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.458661 | 4.08737134 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | Sensible | 70126.33 | 67722.47 | 1.0000 | 4.08737059 | 3.458660 | 28.17 | 17.43 | 0.00825170 | 49377.3 | 12.00 | 11.09 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 70126.33 | 31.30 | 0.00823349 | 18.45 | 0.42471127 | 12.2796 | 26.70 | 0.00825425 | 26.70 | 0.00825425 | 37.1566 | 44106.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 106322.321 | 106322.321 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.458661 | 4.08737134 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | Sensible | 106322.32 | 106322.32 | 1.0000 | 4.08737134 | 3.458661 | 14.11 | 10.45 | 0.00650912 | 30631.4 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 106322.32 | 3.80 | 0.00505843 | 3.80 | 0.42471127 | 12.2796 | 15.56 | 0.00671219 | 15.56 | 0.00671219 | 60.0558 | 22088.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.20 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 3.46 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 1608.83 | 1542.67 | 154.17 |
ZONE2 FINE STORAGE | 2765.67 | 2058.00 | 1390.67 |
ZONE3 BULK STORAGE | 2415.17 | 2858.67 | 1757.67 |
Facility | 3114.67 | 3038.50 | 1848.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 3.67 | 65.83 | 3.67 | 4.17 |
ZONE2 FINE STORAGE | 0.67 | 7.33 | 0.17 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 4.33 | 73.17 | 3.83 | 4.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 1.767 | 0.342 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1.334 | 0.322 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.147 | 0.000 | 0.115 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.55 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 6771838.19 | 0.00 | 6771838.19 | 1927845.26 | 8699683.45 | 3225648.14 | 5364.84 | 548.17 | 2847.00 | 270.71 |
ZONE2 FINE STORAGE | 14101061.72 | 0.00 | 14101061.72 | 7435190.39 | 21536252.11 | 13393694.68 | 5655.16 | 1229.67 | 1875.17 | 45.30 |
ZONE3 BULK STORAGE | 0.00 | 19901917.55 | 19901917.55 | 31836630.61 | 51738548.17 | 30805497.77 | 8625.42 | 6.63 | 127.96 | 4402.89 |
Total Facility | 20872899.91 | 19901917.55 | 40774817.46 | 41199666.26 | 81974483.72 | 47424840.58 | 8645.43 | 1438.25 | 3158.34 | 4450.20 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.4843 | 0.0000 | 0.4843 | 0.0939 | 0.5781 | 0.1023 | 483.74 | 547.17 | 2605.09 |
ZONE2 FINE STORAGE | 1.0571 | 0.0000 | 1.0571 | 0.2571 | 1.3142 | 0.4247 | 573.56 | 1229.67 | 1832.78 |
ZONE3 BULK STORAGE | 0.0000 | 1.0865 | 1.0865 | 1.3984 | 2.4849 | 0.9768 | 3519.10 | 5.29 | 111.61 |
Total Facility | 1.5414 | 1.0865 | 2.6278 | 1.7494 | 4.3772 | 1.5038 | 3521.43 | 1435.92 | 2863.83 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 9457554.70 | 0.00 | 9457554.70 | 3225648.14 | 5345.83 | 0.78 | 3413.39 | 270.71 |
PSZ-FINE STORAGE | 19693554.22 | 0.00 | 19693554.22 | 13393694.68 | 5647.54 | 0.17 | 3112.30 | 45.30 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.6763 | 0.0000 | 0.6763 | 0.1023 | 475.32 | 0.19 | 3160.49 |
PSZ-FINE STORAGE | 1.4763 | 0.0000 | 1.4763 | 0.4247 | 566.81 | 0.17 | 3069.03 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2050.24 | 1393.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2133.45 | 988.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.8696 | 0.6390 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 1.7534 | 1.7271 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 383 |
Defaulted Fields | 319 |
Fields with Defaults | 1020 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1014.26 | 6718.26 | 01-JAN-07:00 | 83057.90 | 29-SEP-13:00 |
Electricity:Building | 763.52 | 6235.26 | 01-JAN-00:10 | 58611.10 | 19-JUL-09:50 |
Electricity:Zone:ZONE1 OFFICE | 62.81 | 1030.77 | 01-JAN-00:10 | 3867.54 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 762.90 | 6235.26 | 01-JAN-00:10 | 56305.80 | 02-JAN-09:10 |
InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 461.56 | 3104.69 | 01-JAN-00:10 | 36895.31 | 19-JUL-09:50 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 64.13 | 0.00 | 01-JAN-00:10 | 7456.44 | 31-JUL-12:20 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.62 | 0.00 | 01-JAN-00:10 | 2305.29 | 31-JUL-12:20 |
Ventilation (simple):Fans:Electricity | 0.62 | 0.00 | 01-JAN-00:10 | 2305.29 | 31-JUL-12:20 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.62 | 0.00 | 01-JAN-00:10 | 2305.29 | 31-JUL-12:20 |
ElectricityPurchased:Facility | 1014.26 | 6718.26 | 01-JAN-07:00 | 83057.90 | 29-SEP-13:00 |
ElectricityPurchased:Plant | 1014.26 | 6718.26 | 01-JAN-07:00 | 83057.90 | 29-SEP-13:00 |
Cogeneration:ElectricityPurchased | 1014.26 | 6718.26 | 01-JAN-07:00 | 83057.90 | 29-SEP-13:00 |
General:Cogeneration:ElectricityPurchased | 1014.26 | 6718.26 | 01-JAN-07:00 | 83057.90 | 29-SEP-13:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1014.26 | 6718.26 | 01-JAN-07:00 | 83057.90 | 29-SEP-13:00 |
ElectricityNet:Plant | 1014.26 | 6718.26 | 01-JAN-07:00 | 83057.90 | 29-SEP-13:00 |
Cogeneration:ElectricityNet | 1014.26 | 6718.26 | 01-JAN-07:00 | 83057.90 | 29-SEP-13:00 |
General:Cogeneration:ElectricityNet | 1014.26 | 6718.26 | 01-JAN-07:00 | 83057.90 | 29-SEP-13:00 |
Electricity:HVAC | 91.20 | 0.00 | 01-JAN-00:10 | 22702.06 | 29-SEP-13:00 |
General:Fans:Electricity | 63.51 | 0.00 | 01-JAN-00:10 | 5151.14 | 24-AUG-14:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 27.70 | 0.00 | 01-JAN-00:10 | 17550.92 | 29-SEP-13:00 |
General:Cooling:Electricity | 27.70 | 0.00 | 01-JAN-00:10 | 17550.92 | 29-SEP-13:00 |
ExteriorLights:Electricity | 134.14 | 0.00 | 01-JAN-07:00 | 8532.22 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 134.14 | 0.00 | 01-JAN-07:00 | 8532.22 | 01-JAN-00:10 |
Electricity:Plant | 25.40 | 483.00 | 10-JAN-06:10 | 1805.13 | 07-FEB-12:10 |
WaterSystems:Electricity | 25.40 | 483.00 | 10-JAN-06:10 | 1805.13 | 07-FEB-12:10 |
Water Heater:WaterSystems:Electricity | 25.40 | 483.00 | 10-JAN-06:10 | 1805.13 | 07-FEB-12:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1.70 | 0.00 | 01-JAN-00:10 | 25805.45 | 03-JAN-06:10 |
NaturalGas:HVAC | 1.70 | 0.00 | 01-JAN-00:10 | 25805.45 | 03-JAN-06:10 |
Heating:NaturalGas | 1.70 | 0.00 | 01-JAN-00:10 | 25805.45 | 03-JAN-06:10 |
General:Heating:NaturalGas | 1.70 | 0.00 | 01-JAN-00:10 | 25805.45 | 03-JAN-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 04-MAY-11:50 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 04-MAY-11:50 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 04-MAY-11:50 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 04-MAY-11:50 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 04-MAY-11:50 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 04-MAY-11:50 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 04-MAY-11:50 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 04-MAY-11:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 256.24 | 0.00 | 01-JAN-00:10 | 94072.05 | 29-SEP-13:30 |
EnergyTransfer:Building | 153.16 | 0.00 | 01-JAN-00:10 | 41849.96 | 30-SEP-14:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 52.47 | 0.00 | 01-JAN-00:10 | 13812.44 | 02-JAN-06:10 |
Heating:EnergyTransfer | 5.39 | 0.00 | 01-JAN-00:10 | 19201.80 | 03-JAN-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 1.97 | 0.00 | 01-JAN-00:10 | 13812.44 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 5.39 | 0.00 | 01-JAN-00:10 | 19201.80 | 03-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 1.97 | 0.00 | 01-JAN-00:10 | 13812.44 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 147.77 | 0.00 | 01-JAN-00:10 | 41849.96 | 30-SEP-14:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 50.50 | 0.00 | 01-JAN-00:10 | 11114.95 | 26-MAY-17:20 |
General:Cooling:EnergyTransfer | 147.77 | 0.00 | 01-JAN-00:10 | 41849.96 | 30-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 50.50 | 0.00 | 01-JAN-00:10 | 11114.95 | 26-MAY-17:20 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 100.69 | 0.00 | 01-JAN-00:10 | 34157.32 | 09-JUL-14:40 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 3.42 | 0.00 | 01-JAN-00:10 | 11274.04 | 03-JAN-03:50 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 3.42 | 0.00 | 01-JAN-00:10 | 11274.04 | 03-JAN-03:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 97.27 | 0.00 | 01-JAN-00:10 | 34157.32 | 09-JUL-14:40 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 97.27 | 0.00 | 01-JAN-00:10 | 34157.32 | 09-JUL-14:40 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 103.08 | 0.00 | 01-JAN-00:10 | 57938.61 | 18-AUG-14:40 |
HeatingCoils:EnergyTransfer | 1.15 | 0.00 | 01-JAN-00:10 | 18950.78 | 03-JAN-06:10 |
CoolingCoils:EnergyTransfer | 101.93 | 0.00 | 01-JAN-00:10 | 57938.61 | 18-AUG-14:40 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 1.968 | -50.505 | 0.000 | 0.000 | 9.200 | 30.864 | 31.946 | 9.255 | 0.000 | 0.214 | 0.000 | 0.000 | -9.099 | 0.000 | -15.756 | -8.086 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 3.418 | -97.269 | 0.000 | 0.000 | 18.521 | 239.148 | 0.000 | 0.000 | 0.000 | 0.313 | 0.000 | 0.000 | 0.000 | 0.000 | -69.479 | -94.652 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 44.294 | 353.598 | 107.344 | 168.924 | 0.000 | 4.560 | 0.013 | 0.000 | -78.916 | 0.000 | -376.203 | -223.601 |
Total Facility | 0.000 | 0.000 | 5.386 | -147.774 | 0.000 | 0.000 | 72.015 | 623.610 | 139.290 | 178.179 | 0.000 | 5.087 | 0.014 | 0.000 | -88.015 | 0.000 | -461.438 | -326.340 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 15-OCT-23:01 | 0.00 | 0.00 | 0.00 | -22246.59 | 0.00 | 0.00 | 0.00 | 457.02 | 573.75 | 0.00 | 0.00 | 0.00 | 21890.91 | 0.00 | -408.08 | 0.00 | -267.02 | 0.00 |
ZONE2 FINE STORAGE | 20-JUN-17:11 | 0.00 | 0.00 | 0.00 | -70230.59 | 0.00 | 0.00 | 0.00 | 2099.79 | 0.00 | 0.00 | 0.00 | 0.00 | 71698.79 | 0.00 | -0.00 | 0.00 | -3567.99 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-JUL-17:11 | 0.00 | 0.00 | 0.00 | -88860.64 | 0.00 | 0.00 | 0.00 | 5661.51 | 2623.78 | 4840.43 | 0.00 | 0.00 | 102718.31 | 0.00 | 0.00 | 0.00 | -26983.39 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 09-JAN-06:01 | 0.00 | 0.00 | 29383.44 | 0.00 | 0.00 | 0.00 | 138.81 | 583.97 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -809.08 | 0.00 | -1556.45 | -28314.45 |
ZONE2 FINE STORAGE | 03-JAN-06:32 | 0.00 | 0.00 | 33225.17 | 0.00 | 0.00 | 0.00 | 354.51 | 2099.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1115.60 | -34563.88 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-JAN-06:01 | 0.00 | 0.00 | 34585.57 | 0.00 | 0.00 | 0.00 | 1351.71 | 5788.46 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7651.63 | 0.00 | -12246.11 | -24451.78 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1978 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.1978 | 0.0854 | 1.0000 | Not calculated | 0.1023 | 0.0854 | ||
PSZ-FINE STORAGE | 3.4587 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.4587 | 0.1228 | 1.0000 | Not calculated | 0.4247 | 0.1228 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1978 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.1978 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0854 | ||
PSZ-FINE STORAGE | 3.4587 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.4587 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1228 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1978 | 1.1978 | 1.1978 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.4587 | 3.4587 | 3.4587 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1978 | 1.1978 | 1.1978 | 1.1978 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.4587 | 3.4587 | 3.4587 | 3.4587 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1978 | 1.1978 | 1.1978 | No | 0.1023 | 0.3564 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.4587 | 3.4587 | 3.4587 | No | 0.4247 | 0.6651 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1978 | 1.1978 | 1.1978 | 1.1978 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.4587 | 3.4587 | 3.4587 | 3.4587 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 3.83 |
Number of hours cooling loads not met | 4.17 |
Number of hours not met | 8.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1.70 | 25805.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 27.70 | 17550.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 623.61 | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 134.14 | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.62 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 63.51 | 5151.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 25.40 | 1805.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 1014.26 |
Natural Gas | 0.00 | 1.70 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 1015.97 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 128.97 |
Space Heating | 0.00 |
Space Cooling | 5.73 |
Fans (All) | 13.26 |
Service Water Heating | 5.25 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 209.77 |
Subtotal | 209.77 |
Natural Gas [MJ/m2] | |
Space Heating | 0.35 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.35 |
Subtotal | 0.35 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 61.38 |
Space Heating | 0.17 |
Space Cooling | 2.73 |
Fans (All) | 6.31 |
Service Water Heating | 2.50 |
Receptacle Equipment | 13.71 |
Miscellaneous | 13.20 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 3430. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8558.00 | 202.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7279.67 | 1480.33 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 6495.50 | 2261.00 | 3.50 | 0.00 | 0.00 |
Min | 6495.50 | 202.00 | 0.00 | 0.00 | 0.00 |
Max | 8558.00 | 2261.00 | 3.50 | 0.00 | 0.00 |
Average | 7444.39 | 1314.44 | 1.17 | 0.00 | 0.00 |
Sum | 22333.17 | 3943.33 | 3.50 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 50408.00 | 32311.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 116329.50 | 74677.00 | 186.50 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 116329.50 | 74677.00 | 186.50 | 0.00 | 0.00 |
Average | 66588.17 | 35662.67 | 62.17 | 0.00 | 0.00 |
Sum | 199764.50 | 106988.00 | 186.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8414.00 | 346.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 6179.50 | 2580.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 5894.33 | 2865.67 | 0.00 | 0.00 | 0.00 |
Min | 5894.33 | 346.00 | 0.00 | 0.00 | 0.00 |
Max | 8414.00 | 2865.67 | 0.00 | 0.00 | 0.00 |
Average | 6829.28 | 1930.72 | 0.00 | 0.00 | 0.00 |
Sum | 20487.83 | 5792.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 32734.33 | 292.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 45439.00 | 37280.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 112099.67 | 79093.33 | 0.00 | 0.00 | 0.00 |
Min | 32734.33 | 292.67 | 0.00 | 0.00 | 0.00 |
Max | 112099.67 | 79093.33 | 0.00 | 0.00 | 0.00 |
Average | 63424.33 | 38888.67 | 0.00 | 0.00 | 0.00 |
Sum | 190273.00 | 116666.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.173908E+10 | 5059.45 | 18-JAN-14:50 | 23.27 | 14.80 | 0.614398E+09 | 769.02 | 19-JAN-14:50 | 20.17 | 15.18 |
February | 0.155980E+10 | 5199.69 | 03-FEB-15:20 | 22.33 | 9.30 | 0.569987E+09 | 769.02 | 01-FEB-16:10 | 22.33 | 9.30 |
March | 0.194377E+10 | 16786.62 | 22-MAR-17:15 | 17.33 | 15.24 | 0.666629E+09 | 769.03 | 24-MAR-14:09 | 18.83 | 15.81 |
April | 0.377364E+10 | 20624.42 | 28-APR-17:15 | 14.33 | 11.68 | 0.631238E+09 | 769.05 | 26-APR-15:20 | 14.33 | 11.68 |
May | 0.434610E+10 | 22229.90 | 26-MAY-17:15 | 15.33 | 10.34 | 0.658687E+09 | 769.05 | 03-MAY-14:50 | 15.33 | 10.34 |
June | 0.604673E+10 | 21587.82 | 04-JUN-23:02 | 14.00 | 12.74 | 0.660012E+09 | 769.05 | 20-JUN-15:09 | 21.83 | 15.76 |
July | 0.756713E+10 | 22126.47 | 04-JUL-23:01 | 16.00 | 14.12 | 0.634621E+09 | 769.06 | 19-JUL-15:30 | 26.00 | 20.22 |
August | 0.769291E+10 | 20375.81 | 27-AUG-23:01 | 15.02 | 14.97 | 0.685494E+09 | 769.06 | 14-AUG-15:50 | 15.02 | 14.97 |
September | 0.601390E+10 | 20269.27 | 04-SEP-23:02 | 15.83 | 14.07 | 0.634691E+09 | 769.05 | 15-SEP-15:09 | 19.83 | 15.05 |
October | 0.534799E+10 | 22247.14 | 15-OCT-23:01 | 20.33 | 10.84 | 0.633323E+09 | 769.04 | 20-OCT-14:20 | 19.67 | 15.00 |
November | 0.243742E+10 | 5438.15 | 18-NOV-14:50 | 24.33 | 14.49 | 0.602574E+09 | 769.02 | 10-NOV-15:20 | 24.33 | 14.49 |
December | 0.203635E+10 | 18460.24 | 05-DEC-18:45 | 20.00 | 10.85 | 0.622475E+09 | 769.02 | 07-DEC-14:50 | 19.33 | 15.31 |
Annual Sum or Average | 0.505048E+11 | 0.761413E+10 | ||||||||
Minimum of Months | 0.155980E+10 | 5059.45 | 14.00 | 9.30 | 0.569987E+09 | 769.02 | 14.33 | 9.30 | ||
Maximum of Months | 0.769291E+10 | 22247.14 | 24.33 | 15.24 | 0.685494E+09 | 769.06 | 26.00 | 20.22 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125460E+10 | 8408.20 | 18-JAN-14:10 | 24.33 | 14.82 | 0.155973E+10 | 2246.80 | 18-JAN-14:00 | 23.00 | 14.79 |
February | 0.134065E+10 | 8390.72 | 03-FEB-15:00 | 23.00 | 8.84 | 0.144136E+10 | 2246.80 | 01-FEB-11:00 | 23.00 | 8.84 |
March | 0.228413E+10 | 15015.75 | 23-MAR-14:20 | 22.67 | 17.32 | 0.169205E+10 | 2246.91 | 23-MAR-13:20 | 22.67 | 17.32 |
April | 0.688070E+10 | 67472.93 | 30-APR-15:11 | 22.67 | 16.39 | 0.177849E+10 | 2247.00 | 26-APR-15:09 | 22.67 | 16.39 |
May | 0.746177E+10 | 21970.37 | 03-MAY-13:10 | 23.83 | 15.35 | 0.187542E+10 | 2247.00 | 04-MAY-12:20 | 23.67 | 16.60 |
June | 0.129014E+11 | 70239.51 | 20-JUN-17:11 | 19.33 | 15.09 | 0.191485E+10 | 2246.99 | 20-JUN-14:39 | 19.33 | 15.09 |
July | 0.192209E+11 | 70196.33 | 05-JUL-17:11 | 18.67 | 14.96 | 0.185111E+10 | 2246.98 | 10-JUL-10:50 | 21.83 | 16.25 |
August | 0.193364E+11 | 67506.96 | 01-AUG-17:11 | 18.67 | 15.74 | 0.199807E+10 | 2247.00 | 22-AUG-14:00 | 21.00 | 15.98 |
September | 0.128107E+11 | 63861.33 | 30-SEP-17:11 | 25.00 | 17.45 | 0.184263E+10 | 2246.99 | 01-SEP-14:39 | 25.00 | 17.45 |
October | 0.103311E+11 | 65833.22 | 16-OCT-17:11 | 26.00 | 14.54 | 0.181572E+10 | 2246.96 | 19-OCT-10:50 | 21.83 | 16.70 |
November | 0.211935E+10 | 10500.96 | 18-NOV-14:00 | 26.00 | 15.08 | 0.164593E+10 | 2246.80 | 28-NOV-13:39 | 24.67 | 10.76 |
December | 0.132744E+10 | 8916.06 | 05-DEC-14:40 | 24.67 | 13.00 | 0.162895E+10 | 2246.80 | 18-DEC-13:09 | 24.00 | 10.26 |
Annual Sum or Average | 0.972691E+11 | 0.210443E+11 | ||||||||
Minimum of Months | 0.125460E+10 | 8390.72 | 18.67 | 8.84 | 0.144136E+10 | 2246.80 | 19.33 | 8.84 | ||
Maximum of Months | 0.193364E+11 | 70239.51 | 26.00 | 17.45 | 0.199807E+10 | 2247.00 | 25.00 | 17.45 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 | 0.269293E+10 | 4439.88 | 24-JAN-15:39 | 24.33 | 15.19 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 | 0.257968E+10 | 4480.28 | 03-FEB-15:20 | 22.33 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.62 | 0.307036E+10 | 5058.63 | 23-MAR-14:39 | 22.33 | 17.37 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 | 0.377131E+10 | 6038.35 | 26-APR-14:09 | 25.50 | 16.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 | 14.50 | 0.419401E+10 | 6276.16 | 03-MAY-12:30 | 24.00 | 15.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 | 0.472681E+10 | 6377.54 | 30-JUN-10:20 | 23.67 | 18.04 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 | 0.498393E+10 | 6405.32 | 24-JUL-14:30 | 26.50 | 20.09 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 | 17.20 | 0.536317E+10 | 6401.37 | 15-AUG-10:00 | 27.00 | 20.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.83 | 0.476446E+10 | 8709.96 | 29-SEP-13:09 | 35.67 | 18.16 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 | 0.451512E+10 | 8634.14 | 16-OCT-12:09 | 35.68 | 17.48 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.07 | 0.311790E+10 | 4854.35 | 01-NOV-14:30 | 17.00 | 13.18 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.44 | 0.292671E+10 | 4604.64 | 05-DEC-15:09 | 24.67 | 13.10 |
Annual Sum or Average | 0.00 | 0.467064E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 7.63 | 5.44 | 0.257968E+10 | 4439.88 | 17.00 | 9.30 | ||
Maximum of Months | 0.00 | 0.00 | 18.42 | 17.39 | 0.536317E+10 | 8709.96 | 35.68 | 20.85 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.524258E+09 | 29383.48 | 09-JAN-06:01 | 2.17 |
February | 0.279628E+09 | 28687.32 | 28-FEB-06:02 | 10.17 |
March | 0.395677E+09 | 29375.85 | 30-MAR-05:01 | 4.97 |
April | 0.110578E+09 | 28917.26 | 01-APR-05:01 | 7.83 |
May | 87304912.75 | 1474.98 | 03-MAY-06:10 | 15.33 |
June | 25968313.62 | 1537.04 | 08-JUN-06:10 | 14.17 |
July | 5667077.37 | 1520.57 | 14-JUL-06:10 | 17.00 |
August | 3718412.49 | 1492.22 | 31-AUG-06:10 | 16.33 |
September | 16912590.53 | 1542.48 | 05-SEP-06:10 | 16.00 |
October | 56388196.19 | 1896.37 | 05-OCT-06:05 | 20.00 |
November | 0.152927E+09 | 23938.90 | 24-NOV-06:02 | 8.92 |
December | 0.309194E+09 | 28943.87 | 14-DEC-06:01 | 7.17 |
Annual Sum or Average | 0.196822E+10 | |||
Minimum of Months | 3718412.49 | 1474.98 | 2.17 | |
Maximum of Months | 0.524258E+09 | 29383.48 | 20.00 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.713314E+09 | 33225.15 | 03-JAN-06:32 | 3.67 |
February | 0.272162E+09 | 3990.73 | 27-FEB-08:00 | 9.00 |
March | 0.289250E+09 | 3742.36 | 28-MAR-07:00 | 11.00 |
April | 0.279752E+09 | 3488.66 | 21-APR-07:00 | 13.00 |
May | 0.253557E+09 | 3788.53 | 25-MAY-07:00 | 14.00 |
June | 0.186659E+09 | 3632.07 | 06-JUN-07:00 | 17.00 |
July | 87593301.10 | 3340.66 | 15-JUL-06:13 | 17.33 |
August | 0.120261E+09 | 3616.74 | 24-AUG-06:25 | 16.75 |
September | 0.218796E+09 | 3620.00 | 27-SEP-07:00 | 16.00 |
October | 0.218749E+09 | 3429.86 | 07-OCT-07:00 | 17.00 |
November | 0.302367E+09 | 3676.26 | 01-NOV-07:00 | 11.00 |
December | 0.475062E+09 | 3406.48 | 13-DEC-08:00 | 8.00 |
Annual Sum or Average | 0.341752E+10 | |||
Minimum of Months | 87593301.10 | 3340.66 | 3.67 | |
Maximum of Months | 0.713314E+09 | 33225.15 | 17.33 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.258145E+10 | 1955.04 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.235440E+10 | 1955.04 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.269003E+10 | 1955.04 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.254196E+10 | 1955.04 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.263574E+10 | 1955.04 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.259625E+10 | 1955.04 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.258145E+10 | 1955.04 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.269003E+10 | 1955.04 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.254196E+10 | 1955.04 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.258145E+10 | 1955.04 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.248766E+10 | 1955.04 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.258145E+10 | 1955.04 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.308638E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.235440E+10 | 1955.04 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.269003E+10 | 1955.04 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.198922E+11 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.182065E+11 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.210336E+11 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.197108E+11 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.204629E+11 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.202815E+11 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.198922E+11 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.210336E+11 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.197108E+11 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.198922E+11 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.191400E+11 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.198922E+11 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.239148E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.182065E+11 | 17848.24 | 0.00 | 0.00 | |
Maximum of Months | 0.210336E+11 | 17848.24 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.294120E+11 | 26389.90 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.269196E+11 | 26389.90 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.310997E+11 | 26389.90 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.291438E+11 | 26389.90 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.302559E+11 | 26389.90 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.299876E+11 | 26389.90 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.294120E+11 | 26389.90 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.310997E+11 | 26389.90 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.291438E+11 | 26389.90 | 01-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.294120E+11 | 26389.90 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.282999E+11 | 26389.90 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.294120E+11 | 26389.90 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.353598E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.269196E+11 | 26389.90 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.310997E+11 | 26389.90 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3370864.60 | 0.154008E+10 |
February | 0.127628E+10 | 0.235440E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1077693.03 | 0.177930E+10 |
March | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43351.21 | 0.213834E+10 |
April | 0.138726E+10 | 0.254196E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3555916.11 | 0.139418E+10 |
May | 0.144276E+10 | 0.263574E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52523.93 | 0.157724E+10 |
June | 0.144276E+10 | 0.259625E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 942035.95 | 0.987084E+09 |
July | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28970019.59 | 0.639882E+09 |
August | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29278088.66 | 0.734386E+09 |
September | 0.138726E+10 | 0.254196E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47749399.12 | 0.831117E+09 |
October | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93506518.40 | 0.102798E+10 |
November | 0.133177E+10 | 0.248766E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1707664.26 | 0.154035E+10 |
December | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3802337.55 | 0.156600E+10 |
Annual Sum or Average | 0.168137E+11 | 0.308638E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214056E+09 | 0.157559E+11 |
Minimum of Months | 0.127628E+10 | 0.235440E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43351.21 | 0.639882E+09 |
Maximum of Months | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93506518.40 | 0.213834E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4210715.42 | 0.544814E+10 |
February | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703558E+10 |
March | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.830039E+10 |
April | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 806777.68 | 0.635021E+10 |
May | 0.339505E+10 | 0.204629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761367E+10 |
June | 0.339505E+10 | 0.202815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513125E+10 |
July | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6389699.89 | 0.380423E+10 |
August | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4047401.07 | 0.440363E+10 |
September | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84762149.59 | 0.409234E+10 |
October | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211571E+09 | 0.522780E+10 |
November | 0.313390E+10 | 0.191400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1222132.21 | 0.607185E+10 |
December | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11945.91 | 0.599964E+10 |
Annual Sum or Average | 0.395654E+11 | 0.239148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313021E+09 | 0.694787E+11 |
Minimum of Months | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380423E+10 |
Maximum of Months | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211571E+09 | 0.830039E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259612E+09 | 0.150584E+11 |
February | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8255332.81 | 0.214130E+11 |
March | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1483433.09 | 0.264643E+11 |
April | 0.750829E+10 | 0.291438E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21676621.91 | 0.235023E+11 |
May | 0.780862E+10 | 0.302559E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296665E+11 |
June | 0.780862E+10 | 0.299876E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239737E+11 |
July | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214108E+11 |
August | 0.810895E+10 | 0.310997E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231689E+11 |
September | 0.750829E+10 | 0.291438E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34842845.50 | 0.202531E+11 |
October | 0.750829E+10 | 0.294120E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302109E+09 | 0.220889E+11 |
November | 0.720796E+10 | 0.282999E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57955485.57 | 0.195706E+11 |
December | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197523E+09 | 0.173080E+11 |
Annual Sum or Average | 0.910005E+11 | 0.353598E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.883458E+09 | 0.263878E+12 |
Minimum of Months | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150584E+11 |
Maximum of Months | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302109E+09 | 0.296665E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1955.04 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 500.32 | 18-JAN-13:00 | 5256.83 | 10-JAN-07:05 |
February | 1680.92 | 01-FEB-08:09 | 1955.04 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 442.32 | 01-FEB-12:10 | 4288.50 | 10-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 1955.04 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.03 | 11-MAR-14:00 | 5187.68 | 30-MAR-06:05 |
April | 1680.92 | 01-APR-07:10 | 1955.04 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 518.39 | 26-APR-11:10 | 4621.82 | 17-APR-16:05 |
May | 1680.92 | 01-MAY-07:10 | 1955.04 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.88 | 03-MAY-12:00 | 4200.69 | 12-MAY-16:10 |
June | 1680.92 | 01-JUN-07:10 | 1955.04 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.02 | 29-JUN-11:08 | 2705.88 | 12-JUN-07:00 |
July | 1680.92 | 01-JUL-07:10 | 1955.04 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1030.55 | 19-JUL-12:00 | 2260.56 | 17-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 1955.04 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 990.88 | 18-AUG-12:00 | 2377.90 | 28-AUG-07:00 |
September | 1680.92 | 01-SEP-07:10 | 1955.04 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2872.97 | 29-SEP-12:00 | 2901.12 | 20-SEP-07:00 |
October | 1680.92 | 02-OCT-07:10 | 1955.04 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3300.64 | 16-OCT-11:10 | 3787.32 | 12-OCT-06:05 |
November | 1680.92 | 01-NOV-07:10 | 1955.04 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.01 | 19-NOV-13:00 | 4364.23 | 30-NOV-07:05 |
December | 1680.92 | 01-DEC-08:09 | 1955.04 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 510.18 | 19-DEC-13:00 | 4717.56 | 13-DEC-07:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 5.03 | 2260.56 | |||||
Maximum of Months | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 3300.64 | 5256.83 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 956.77 | 15-JAN-10:00 | 8664.95 | 21-JAN-16:05 |
February | 3955.50 | 01-FEB-08:09 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 11174.15 | 25-FEB-16:05 |
March | 3955.50 | 01-MAR-08:09 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 16252.17 | 28-MAR-15:05 |
April | 3955.50 | 01-APR-07:10 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557.51 | 30-APR-10:20 | 15329.61 | 17-APR-15:55 |
May | 3955.50 | 01-MAY-07:10 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 15056.98 | 12-MAY-16:00 |
June | 3955.50 | 01-JUN-07:10 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 8541.78 | 12-JUN-16:00 |
July | 3955.50 | 01-JUL-07:10 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.11 | 23-JUL-10:45 | 7362.71 | 20-JUL-18:00 |
August | 3955.50 | 01-AUG-07:10 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.90 | 06-AUG-13:05 | 5645.94 | 22-AUG-17:00 |
September | 3955.50 | 01-SEP-07:10 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4049.47 | 29-SEP-15:10 | 6718.30 | 02-SEP-15:10 |
October | 3955.50 | 02-OCT-07:10 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3907.88 | 14-OCT-15:10 | 8902.70 | 11-OCT-16:00 |
November | 3955.50 | 01-NOV-07:10 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.76 | 19-NOV-10:00 | 9479.74 | 27-NOV-16:05 |
December | 3955.50 | 01-DEC-08:09 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.91 | 25-DEC-12:00 | 9855.38 | 12-DEC-16:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5645.94 | ||||
Maximum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4049.47 | 16252.17 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 26389.90 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7464.56 | 15-JAN-10:00 | 25000.10 | 27-JAN-05:00 |
February | 9097.65 | 01-FEB-08:09 | 26389.90 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2593.82 | 01-FEB-12:00 | 35270.70 | 25-FEB-13:05 |
March | 9097.65 | 01-MAR-08:09 | 26389.90 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 783.06 | 12-MAR-09:55 | 41267.17 | 28-MAR-14:20 |
April | 9097.65 | 01-APR-07:10 | 26389.90 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1897.35 | 01-APR-12:00 | 46410.42 | 17-APR-15:55 |
May | 9097.65 | 01-MAY-07:10 | 26389.90 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 44586.79 | 12-MAY-16:00 |
June | 9097.65 | 01-JUN-07:10 | 26389.90 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 27088.60 | 12-JUN-16:00 |
July | 9097.65 | 01-JUL-07:10 | 26389.90 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 32013.79 | 20-JUL-09:00 |
August | 9097.65 | 01-AUG-07:10 | 26389.90 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 22953.75 | 22-AUG-16:00 |
September | 9097.65 | 01-SEP-07:10 | 26389.90 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2935.34 | 29-SEP-11:00 | 29927.39 | 02-SEP-15:00 |
October | 9097.65 | 02-OCT-07:10 | 26389.90 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14476.07 | 14-OCT-10:00 | 30705.18 | 07-OCT-08:00 |
November | 9097.65 | 01-NOV-07:10 | 26389.90 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3831.42 | 19-NOV-13:00 | 24765.09 | 01-NOV-08:00 |
December | 9097.65 | 01-DEC-08:09 | 26389.90 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6478.11 | 18-DEC-11:00 | 31662.52 | 12-DEC-13:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22953.75 | |||||
Maximum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 14476.07 | 46410.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5059.45 | 18-JAN-14:50 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.99 |
February | 5199.69 | 03-FEB-15:20 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.46 |
March | 16786.62 | 22-MAR-17:15 | 0.00 | 914.04 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 491.61 |
April | 20624.42 | 28-APR-17:15 | 0.00 | 914.04 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 923.63 |
May | 22229.90 | 26-MAY-17:15 | 0.00 | 914.04 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 941.90 |
June | 21587.82 | 04-JUN-23:02 | 0.00 | 2285.11 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432.37 |
July | 22126.47 | 04-JUL-23:01 | 0.00 | 3656.18 | 4590.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20375.81 | 27-AUG-23:01 | 0.00 | 3199.16 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.05 |
September | 20269.27 | 04-SEP-23:02 | 0.00 | 2285.11 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22247.14 | 15-OCT-23:01 | 0.00 | 3199.16 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.02 |
November | 5438.15 | 18-NOV-14:50 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 22.97 | 0.00 |
December | 18460.24 | 05-DEC-18:45 | 0.00 | 914.04 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5059.45 | 0.00 | 914.04 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22247.14 | 1680.92 | 3656.18 | 4590.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.97 | 941.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8408.20 | 18-JAN-14:10 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 544.69 |
February | 8390.72 | 03-FEB-15:00 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1061.62 |
March | 15015.75 | 23-MAR-14:20 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1031.97 |
April | 67472.93 | 30-APR-15:11 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2338.44 |
May | 21970.37 | 03-MAY-13:10 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 795.92 |
June | 70239.51 | 20-JUN-17:11 | 0.00 | 16798.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3567.99 |
July | 70196.33 | 05-JUL-17:11 | 0.00 | 16798.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3776.95 |
August | 67506.96 | 01-AUG-17:11 | 0.00 | 16798.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3503.38 |
September | 63861.33 | 30-SEP-17:11 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.96 |
October | 65833.22 | 16-OCT-17:11 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.35 |
November | 10500.96 | 18-NOV-14:00 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.29 |
December | 8916.06 | 05-DEC-14:40 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 8390.72 | 0.00 | 16798.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.35 | |
Maximum of Months | 70239.51 | 3955.50 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3776.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7083.26 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8133.73 |
April | 0.00 | 01-APR-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12514.69 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 6209.39 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8727.21 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6501.68 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5123.57 |
August | 0.00 | 01-AUG-00:05 | 0.00 | 6209.39 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6763.84 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7491.51 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11755.52 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9386.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 6209.39 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12514.69 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.841461E+11 | 67436.07 | 18-JAN-13:09 | 0.855915E+09 | 25805.45 | 03-JAN-06:10 |
February | 0.761066E+11 | 67295.72 | 01-FEB-11:00 | 0.205313E+09 | 7332.24 | 28-FEB-06:10 |
March | 0.866473E+11 | 68160.23 | 23-MAR-13:00 | 0.345477E+09 | 13669.14 | 30-MAR-05:10 |
April | 0.813343E+11 | 73527.40 | 26-APR-12:00 | 18366423.69 | 8132.18 | 01-APR-05:10 |
May | 0.834868E+11 | 70830.10 | 04-MAY-12:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.847000E+11 | 74214.97 | 29-JUN-12:39 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.879701E+11 | 80038.92 | 31-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.932487E+11 | 80814.14 | 17-AUG-13:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.847363E+11 | 83057.90 | 29-SEP-12:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.867579E+11 | 82645.11 | 16-OCT-10:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.807399E+11 | 68725.11 | 18-NOV-13:00 | 39096774.25 | 6261.98 | 24-NOV-06:10 |
December | 0.843869E+11 | 67317.01 | 05-DEC-16:40 | 0.240393E+09 | 8384.24 | 14-DEC-06:10 |
Annual Sum or Average | 0.101426E+13 | 0.170456E+10 | ||||
Minimum of Months | 0.761066E+11 | 67295.72 | 0.00 | 0.00 | ||
Maximum of Months | 0.932487E+11 | 83057.90 | 0.855915E+09 | 25805.45 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.518856E+11 | 0.132181E+11 | 0.115358E+11 | 0.00 | 0.511840E+10 | 0.00 | 0.00 | 0.211578E+09 | 0.00 | 0.00 | 0.00 | 0.217656E+10 | 0.00 |
February | 0.474804E+11 | 0.112984E+11 | 0.105871E+11 | 0.00 | 0.469592E+10 | 0.00 | 0.00 | 66758029.99 | 0.00 | 0.00 | 0.00 | 0.197800E+10 | 0.00 |
March | 0.548234E+11 | 0.115799E+11 | 0.123431E+11 | 0.00 | 0.551603E+10 | 0.00 | 0.00 | 0.162272E+09 | 0.00 | 0.00 | 0.00 | 0.222261E+10 | 0.00 |
April | 0.513965E+11 | 0.102950E+11 | 0.114862E+11 | 0.00 | 0.514838E+10 | 0.00 | 0.00 | 0.907963E+09 | 0.00 | 0.00 | 0.00 | 0.210028E+10 | 0.00 |
May | 0.533545E+11 | 0.982912E+10 | 0.119357E+11 | 0.00 | 0.536997E+10 | 0.00 | 0.00 | 0.842258E+09 | 0.00 | 0.00 | 0.00 | 0.215522E+10 | 0.00 |
June | 0.528654E+11 | 0.911241E+10 | 0.118862E+11 | 0.00 | 0.556033E+10 | 0.00 | 0.00 | 0.318699E+10 | 0.00 | 0.00 | 0.00 | 0.208873E+10 | 0.00 |
July | 0.518856E+11 | 0.959363E+10 | 0.115358E+11 | 0.00 | 0.577701E+10 | 0.00 | 0.00 | 0.707763E+10 | 0.00 | 0.00 | 0.00 | 0.210044E+10 | 0.00 |
August | 0.548234E+11 | 0.102745E+11 | 0.123357E+11 | 0.00 | 0.601171E+10 | 0.00 | 0.00 | 0.765342E+10 | 0.00 | 0.00 | 0.00 | 0.215001E+10 | 0.00 |
September | 0.513965E+11 | 0.108171E+11 | 0.114788E+11 | 0.00 | 0.544940E+10 | 0.00 | 0.00 | 0.353368E+10 | 0.00 | 0.00 | 0.00 | 0.206076E+10 | 0.00 |
October | 0.518856E+11 | 0.121226E+11 | 0.115432E+11 | 0.00 | 0.547750E+10 | 0.00 | 0.00 | 0.360419E+10 | 0.00 | 0.00 | 0.00 | 0.212488E+10 | 0.00 |
November | 0.499276E+11 | 0.125577E+11 | 0.110862E+11 | 0.00 | 0.489788E+10 | 0.00 | 0.00 | 0.198444E+09 | 0.00 | 0.00 | 0.00 | 0.207197E+10 | 0.00 |
December | 0.518856E+11 | 0.134434E+11 | 0.115358E+11 | 0.00 | 0.510439E+10 | 0.00 | 0.00 | 0.252167E+09 | 0.00 | 0.00 | 0.00 | 0.216559E+10 | 0.00 |
Annual Sum or Average | 0.623610E+12 | 0.134142E+12 | 0.139290E+12 | 0.00 | 0.641269E+11 | 0.00 | 0.00 | 0.276973E+11 | 0.00 | 0.00 | 0.00 | 0.253950E+11 | 0.00 |
Minimum of Months | 0.474804E+11 | 0.911241E+10 | 0.105871E+11 | 0.00 | 0.469592E+10 | 0.00 | 0.00 | 66758029.99 | 0.00 | 0.00 | 0.00 | 0.197800E+10 | 0.00 |
Maximum of Months | 0.548234E+11 | 0.134434E+11 | 0.123431E+11 | 0.00 | 0.601171E+10 | 0.00 | 0.00 | 0.765342E+10 | 0.00 | 0.00 | 0.00 | 0.222261E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.855915E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.205313E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.345477E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 18366423.69 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 39096774.25 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.240393E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.170456E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.855915E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 46193.18 | 02-JAN-09:09 | 8532.22 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 5151.14 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 46193.18 | 01-FEB-09:09 | 8532.22 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 5151.14 | 01-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 46193.18 | 01-MAR-09:09 | 8532.22 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 5151.14 | 01-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 46193.18 | 01-APR-08:09 | 8532.22 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 5151.14 | 13-APR-11:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 46193.18 | 01-MAY-08:09 | 8532.22 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 5612.20 | 03-MAY-12:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 46193.18 | 01-JUN-08:09 | 8532.22 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 5727.47 | 26-JUN-09:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 46193.18 | 01-JUL-08:09 | 8532.22 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 7456.44 | 31-JUL-12:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 46193.18 | 01-AUG-08:09 | 8532.22 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 7456.44 | 14-AUG-10:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 46193.18 | 01-SEP-08:09 | 8532.22 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 7456.44 | 29-SEP-09:20 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 46193.18 | 02-OCT-08:09 | 8532.22 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 7456.44 | 16-OCT-10:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 46193.18 | 01-NOV-08:09 | 8532.22 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 5151.14 | 01-NOV-06:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 46193.18 | 01-DEC-09:09 | 8532.22 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 5151.14 | 01-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 46193.18 | 8532.22 | 10112.62 | 0.00 | 5151.14 | 0.00 | 0.00 | |||||
Maximum of Months | 46193.18 | 8532.22 | 10112.62 | 0.00 | 7456.44 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 4212.61 | 18-JAN-13:09 | 0.00 | 0.00 | 0.00 | 1805.03 | 26-JAN-12:09 | 0.00 |
February | 4108.17 | 01-FEB-11:00 | 0.00 | 0.00 | 0.00 | 1805.13 | 07-FEB-12:09 | 0.00 |
March | 4976.67 | 23-MAR-13:00 | 0.00 | 0.00 | 0.00 | 1803.53 | 01-MAR-12:30 | 0.00 |
April | 10348.33 | 26-APR-13:09 | 0.00 | 0.00 | 0.00 | 1796.89 | 03-APR-11:09 | 0.00 |
May | 7667.01 | 04-MAY-12:09 | 0.00 | 0.00 | 0.00 | 1789.22 | 01-MAY-11:09 | 0.00 |
June | 10946.59 | 29-JUN-13:09 | 0.00 | 0.00 | 0.00 | 1781.05 | 02-JUN-11:39 | 0.00 |
July | 15320.90 | 31-JUL-14:20 | 0.00 | 0.00 | 0.00 | 1775.21 | 01-JUL-11:09 | 0.00 |
August | 15577.60 | 18-AUG-14:39 | 0.00 | 0.00 | 0.00 | 1774.23 | 31-AUG-11:09 | 0.00 |
September | 17550.92 | 29-SEP-12:00 | 0.00 | 0.00 | 0.00 | 1779.71 | 30-SEP-11:30 | 0.00 |
October | 17521.71 | 16-OCT-11:20 | 0.00 | 0.00 | 0.00 | 1787.30 | 30-OCT-11:09 | 0.00 |
November | 5511.58 | 18-NOV-13:00 | 0.00 | 0.00 | 0.00 | 1795.83 | 29-NOV-12:39 | 0.00 |
December | 4128.96 | 19-DEC-12:00 | 0.00 | 0.00 | 0.00 | 1801.94 | 27-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4108.17 | 0.00 | 0.00 | 0.00 | 1774.23 | 0.00 | ||
Maximum of Months | 17550.92 | 0.00 | 0.00 | 0.00 | 1805.13 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 67436.07 | 18-JAN-13:09 | 46193.18 | 10112.62 | 0.00 | 0.00 | 5151.14 | 0.00 | 0.00 | 4212.61 | 0.00 |
February | 67295.72 | 01-FEB-11:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 5151.14 | 0.00 | 0.00 | 4108.17 | 0.00 |
March | 68160.23 | 23-MAR-13:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 5151.14 | 0.00 | 0.00 | 4976.67 | 0.00 |
April | 73527.40 | 26-APR-12:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 5151.14 | 0.00 | 0.00 | 10315.37 | 0.00 |
May | 70830.10 | 04-MAY-12:09 | 46193.18 | 10112.62 | 0.00 | 0.00 | 5151.14 | 0.00 | 0.00 | 7667.01 | 0.00 |
June | 74214.97 | 29-JUN-12:39 | 46193.18 | 10112.62 | 0.00 | 0.00 | 5727.47 | 0.00 | 0.00 | 10600.12 | 0.00 |
July | 80038.92 | 31-JUL-12:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 7456.44 | 0.00 | 0.00 | 14536.94 | 0.00 |
August | 80814.14 | 17-AUG-13:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 7456.44 | 0.00 | 0.00 | 15343.65 | 0.00 |
September | 83057.90 | 29-SEP-12:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 7456.44 | 0.00 | 0.00 | 17550.92 | 0.00 |
October | 82645.11 | 16-OCT-10:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 7456.44 | 0.00 | 0.00 | 17166.86 | 0.00 |
November | 68725.11 | 18-NOV-13:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 5151.14 | 0.00 | 0.00 | 5511.58 | 0.00 |
December | 67317.01 | 05-DEC-16:40 | 40988.70 | 10112.62 | 8532.22 | 0.00 | 5151.14 | 0.00 | 0.00 | 926.55 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 67295.72 | 40988.70 | 10112.62 | 0.00 | 0.00 | 5151.14 | 0.00 | 0.00 | 926.55 | 0.00 | |
Maximum of Months | 83057.90 | 46193.18 | 10112.62 | 8532.22 | 0.00 | 7456.44 | 0.00 | 0.00 | 17550.92 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 25805.45 | 03-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 7332.24 | 28-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 13669.14 | 30-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 8132.18 | 01-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 6261.98 | 24-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 8384.24 | 14-DEC-06:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 25805.45 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 20.20 | 1.67 | 20.20 | 0.00 | 20.20 | 0.00 | 20.20 |
February | 0.33 | 20.51 | 0.33 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
March | 1.00 | 20.41 | 1.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 24.51 | 0.00 | 24.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 24.50 | 0.00 | 24.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 24.54 | 0.67 | 24.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 24.58 | 1.00 | 24.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 24.55 | 1.00 | 24.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 24.52 | 1.17 | 24.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 24.51 | 0.33 | 24.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 20.50 | 0.67 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Annual Sum or Average | 3.67 | 20.34 | 3.67 | 20.34 | 65.83 | 24.11 | 4.17 | 24.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 20.51 | 1.67 | 20.51 | 14.00 | 24.58 | 1.17 | 24.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 14.97 | 0.17 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.00 | 27.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.28 | 0.00 | 27.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.31 | 0.00 | 27.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.34 | 0.00 | 27.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.30 | 0.00 | 27.30 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.55 | 0.00 | 27.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 14.97 | 0.17 | 14.98 | 7.33 | 26.13 | 0.00 | 26.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 14.97 | 0.17 | 14.98 | 2.67 | 27.55 | 0.00 | 27.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 255.33 | 23.10 | 44.17 | 22.87 | 37.83 | 22.68 |
February | 238.00 | 23.21 | 20.50 | 23.09 | 17.00 | 22.97 |
March | 253.17 | 23.11 | 41.17 | 23.02 | 20.67 | 22.89 |
April | 103.50 | 23.38 | 114.33 | 23.62 | 2.17 | 23.60 |
May | 75.17 | 23.50 | 137.33 | 23.76 | 0.00 | 23.76 |
June | 20.50 | 23.77 | 233.67 | 23.89 | 1.00 | 23.89 |
July | 10.00 | 23.47 | 272.33 | 23.89 | 6.67 | 23.89 |
August | 16.17 | 23.89 | 300.33 | 23.91 | 15.83 | 23.91 |
September | 20.00 | 23.75 | 235.83 | 23.89 | 8.17 | 23.89 |
October | 86.00 | 23.60 | 152.00 | 23.80 | 10.33 | 23.80 |
November | 191.33 | 23.32 | 26.83 | 23.29 | 7.83 | 23.21 |
December | 273.50 | 23.32 | 30.33 | 23.14 | 26.67 | 22.97 |
Annual Sum or Average | 1542.67 | 23.28 | 1608.83 | 23.50 | 154.17 | 23.42 |
Minimum of Months | 10.00 | 23.10 | 20.50 | 22.87 | 0.00 | 22.68 |
Maximum of Months | 273.50 | 23.89 | 300.33 | 23.91 | 37.83 | 23.91 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 171.33 | 21.83 | 156.17 | 22.71 | 53.33 | 22.15 |
February | 146.17 | 21.95 | 134.50 | 23.10 | 36.33 | 22.68 |
March | 173.17 | 22.14 | 169.83 | 23.28 | 51.83 | 22.96 |
April | 134.83 | 25.03 | 235.67 | 25.89 | 84.67 | 25.97 |
May | 125.50 | 25.49 | 258.83 | 26.15 | 86.33 | 26.24 |
June | 191.50 | 26.52 | 296.50 | 26.54 | 181.50 | 26.58 |
July | 248.00 | 26.69 | 300.00 | 26.63 | 248.00 | 26.65 |
August | 274.50 | 26.65 | 324.00 | 26.59 | 274.50 | 26.61 |
September | 207.67 | 26.62 | 286.83 | 26.56 | 204.17 | 26.59 |
October | 143.67 | 25.73 | 255.50 | 26.27 | 108.17 | 26.35 |
November | 97.17 | 22.48 | 188.83 | 24.62 | 19.33 | 24.31 |
December | 144.50 | 22.15 | 159.00 | 23.39 | 42.50 | 22.90 |
Annual Sum or Average | 2058.00 | 24.77 | 2765.67 | 25.45 | 1390.67 | 25.49 |
Minimum of Months | 97.17 | 21.83 | 134.50 | 22.71 | 19.33 | 22.15 |
Maximum of Months | 274.50 | 26.69 | 324.00 | 26.63 | 274.50 | 26.65 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 298.67 | 20.44 | 158.17 | 19.75 | 158.17 | 19.42 |
February | 274.00 | 21.03 | 104.50 | 20.42 | 104.50 | 20.07 |
March | 295.67 | 20.79 | 135.17 | 20.49 | 111.67 | 20.11 |
April | 154.33 | 23.80 | 170.67 | 24.89 | 54.83 | 25.09 |
May | 131.00 | 25.32 | 221.50 | 26.06 | 66.00 | 26.36 |
June | 192.00 | 28.15 | 291.50 | 27.76 | 180.33 | 27.95 |
July | 279.67 | 28.83 | 300.00 | 28.74 | 279.67 | 28.77 |
August | 300.50 | 28.75 | 324.00 | 28.66 | 300.50 | 28.69 |
September | 221.17 | 28.62 | 295.83 | 28.21 | 218.83 | 28.35 |
October | 177.67 | 27.59 | 254.17 | 27.68 | 142.00 | 27.97 |
November | 239.50 | 22.27 | 61.67 | 22.02 | 43.17 | 21.67 |
December | 294.50 | 21.38 | 98.00 | 20.78 | 98.00 | 20.42 |
Annual Sum or Average | 2858.67 | 24.48 | 2415.17 | 25.06 | 1757.67 | 25.22 |
Minimum of Months | 131.00 | 20.44 | 61.67 | 19.75 | 43.17 | 19.42 |
Maximum of Months | 300.50 | 28.83 | 324.00 | 28.74 | 300.50 | 28.77 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.632959E+09 | 0.170762E+09 | 54.47 | 0.599130E+09 | 33829150.07 | 0.00 | 0.37 | 14-JAN-15:00 | 0.00 | 01-JAN-00:10 | 6622.59 | 24-JAN-15:30 | 6454.07 | 14-JAN-15:00 | 1089.08 | 17-JAN-14:00 | 1771.99 | 14-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.206848E+09 | 55944370.34 | 33.58 | 0.201428E+09 | 5419546.22 | 0.00 | 0.34 | 03-FEB-15:00 | 0.00 | 01-FEB-00:10 | 5656.41 | 01-FEB-12:00 | 5656.41 | 01-FEB-12:00 | 596.92 | 01-FEB-16:00 | 1562.11 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 |
March | 0.475835E+09 | 0.126699E+09 | 42.42 | 0.402284E+09 | 73551173.29 | 0.00 | 1.00 | 22-MAR-17:15 | 0.00 | 01-MAR-00:10 | 20876.98 | 23-MAR-17:15 | 13879.01 | 23-MAR-17:15 | 7531.92 | 22-MAR-17:15 | 4925.85 | 23-MAR-17:15 | 0.00 | 01-MAR-00:10 |
April | 0.179272E+10 | 0.474386E+09 | 140.92 | 0.146073E+10 | 0.331996E+09 | 0.00 | 1.00 | 08-APR-17:15 | 0.00 | 01-APR-00:10 | 21135.69 | 26-APR-17:11 | 16652.44 | 26-APR-17:10 | 8953.48 | 27-APR-01:43 | 4978.93 | 26-APR-17:11 | 0.00 | 01-APR-00:10 |
May | 0.191927E+10 | 0.507229E+09 | 156.09 | 0.159994E+10 | 0.319327E+09 | 0.00 | 1.00 | 01-MAY-17:45 | 0.00 | 01-MAY-00:05 | 20912.82 | 02-MAY-17:15 | 17548.71 | 26-MAY-17:15 | 7569.88 | 05-MAY-17:55 | 4933.28 | 02-MAY-17:15 | 0.00 | 01-MAY-00:05 |
June | 0.527338E+10 | 0.136154E+10 | 251.68 | 0.399139E+10 | 0.128199E+10 | 0.00 | 1.00 | 01-JUN-17:11 | 0.00 | 01-JUN-00:10 | 22508.42 | 27-JUN-17:10 | 18123.12 | 24-JUN-17:10 | 10042.88 | 29-JUN-23:45 | 5240.60 | 27-JUN-17:10 | 0.00 | 01-JUN-00:10 |
July | 0.932957E+10 | 0.237198E+10 | 305.25 | 0.662957E+10 | 0.269999E+10 | 0.00 | 1.00 | 01-JUL-05:45 | 0.00 | 01-JUL-00:10 | 23258.81 | 28-JUL-17:10 | 18661.69 | 05-JUL-17:10 | 11171.04 | 19-JUL-21:05 | 5369.72 | 28-JUL-17:10 | 0.00 | 01-JUL-00:10 |
August | 0.100653E+11 | 0.255935E+10 | 325.07 | 0.704922E+10 | 0.301604E+10 | 0.00 | 1.00 | 01-AUG-00:15 | 0.00 | 01-AUG-00:05 | 22871.48 | 18-AUG-17:10 | 18882.14 | 19-AUG-17:08 | 11372.84 | 06-AUG-23:45 | 5304.28 | 18-AUG-17:10 | 0.00 | 01-AUG-00:05 |
September | 0.559181E+10 | 0.147429E+10 | 258.62 | 0.419095E+10 | 0.140086E+10 | 0.00 | 1.00 | 01-SEP-17:11 | 0.00 | 01-SEP-00:10 | 23048.76 | 21-SEP-22:05 | 19862.99 | 30-SEP-02:65 | 10631.68 | 22-SEP-02:25 | 5334.55 | 21-SEP-22:05 | 0.00 | 01-SEP-00:10 |
October | 0.527984E+10 | 0.140864E+10 | 241.63 | 0.436514E+10 | 0.914704E+09 | 0.00 | 1.00 | 01-OCT-23:01 | 0.00 | 01-OCT-00:10 | 22952.94 | 01-OCT-23:13 | 19975.04 | 16-OCT-17:43 | 11228.41 | 01-OCT-23:08 | 5318.26 | 01-OCT-23:13 | 0.00 | 01-OCT-00:10 |
November | 0.575031E+09 | 0.155175E+09 | 64.50 | 0.552114E+09 | 22917406.94 | 0.00 | 0.38 | 18-NOV-14:30 | 0.00 | 01-NOV-00:10 | 6981.50 | 18-NOV-14:40 | 6908.13 | 18-NOV-14:30 | 1138.18 | 10-NOV-13:10 | 1866.52 | 18-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.803527E+09 | 0.217034E+09 | 89.17 | 0.796638E+09 | 6889102.51 | 0.00 | 1.00 | 05-DEC-18:45 | 0.00 | 01-DEC-00:10 | 18696.03 | 05-DEC-18:45 | 18696.03 | 05-DEC-18:45 | 758.95 | 07-DEC-14:00 | 4426.84 | 05-DEC-18:45 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.419460E+11 | 0.108830E+11 | 1963.40 | 0.318385E+11 | 0.101075E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.206848E+09 | 55944370.34 | 33.58 | 0.201428E+09 | 5419546.22 | 0.00 | 0.34 | 0.00 | 5656.41 | 5656.41 | 596.92 | 1562.11 | 0.00 | |||||||
Maximum of Months | 0.100653E+11 | 0.255935E+10 | 325.07 | 0.704922E+10 | 0.301604E+10 | 0.00 | 1.00 | 0.00 | 23258.81 | 19975.04 | 11372.84 | 5369.72 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.136594E+09 | 40815263.12 | 11.83 | 0.136566E+09 | 28438.50 | 0.00 | 0.14 | 18-JAN-13:10 | 0.00 | 01-JAN-00:10 | 8622.13 | 18-JAN-13:10 | 8622.13 | 18-JAN-13:10 | 23.53 | 18-JAN-14:50 | 2581.54 | 18-JAN-13:10 | 0.00 | 01-JAN-00:10 |
February | 36295607.37 | 10813659.65 | 6.17 | 36295152.50 | 454.86 | 0.00 | 0.14 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 | 8463.33 | 01-FEB-12:00 | 8463.33 | 01-FEB-12:00 | 0.20 | 01-FEB-14:10 | 2546.05 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 |
March | 0.122724E+09 | 35572648.27 | 10.33 | 0.101315E+09 | 21409090.79 | 0.00 | 0.16 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 | 10299.56 | 23-MAR-14:00 | 7839.28 | 23-MAR-14:00 | 2460.28 | 23-MAR-14:00 | 2940.67 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.152781E+10 | 0.433577E+09 | 49.28 | 0.128626E+10 | 0.241553E+09 | 0.00 | 1.00 | 30-APR-10:15 | 0.00 | 01-APR-00:10 | 74174.52 | 30-APR-12:59 | 68292.36 | 30-APR-10:15 | 12583.13 | 30-APR-15:19 | 18705.30 | 30-APR-11:21 | 0.00 | 01-APR-00:10 |
May | 0.116770E+10 | 0.335029E+09 | 50.58 | 0.995345E+09 | 0.172358E+09 | 0.00 | 0.30 | 04-MAY-12:10 | 0.00 | 01-MAY-00:05 | 19522.50 | 04-MAY-12:10 | 17857.83 | 03-MAY-13:00 | 3109.75 | 04-MAY-13:10 | 5477.13 | 04-MAY-12:10 | 0.00 | 01-MAY-00:05 |
June | 0.655222E+10 | 0.182544E+10 | 145.04 | 0.486793E+10 | 0.168429E+10 | 0.00 | 1.00 | 04-JUN-13:05 | 0.00 | 01-JUN-00:10 | 78231.92 | 29-JUN-17:12 | 60380.09 | 04-JUN-13:05 | 30436.87 | 29-JUN-18:31 | 19299.93 | 29-JUN-17:12 | 0.00 | 01-JUN-00:10 |
July | 0.172124E+11 | 0.470565E+10 | 226.03 | 0.121582E+11 | 0.505418E+10 | 0.00 | 1.00 | 01-JUL-17:11 | 0.00 | 01-JUL-00:10 | 81060.05 | 31-JUL-17:15 | 68595.47 | 10-JUL-17:06 | 37184.84 | 28-JUL-17:12 | 20095.40 | 23-JUL-11:03 | 0.00 | 01-JUL-00:10 |
August | 0.186192E+11 | 0.509406E+10 | 234.69 | 0.128271E+11 | 0.579216E+10 | 0.00 | 1.00 | 01-AUG-17:11 | 0.00 | 01-AUG-00:05 | 80736.26 | 13-AUG-10:25 | 59168.36 | 20-AUG-11:58 | 34448.48 | 18-AUG-17:12 | 20131.08 | 06-AUG-12:51 | 0.00 | 01-AUG-00:05 |
September | 0.703193E+10 | 0.205939E+10 | 142.76 | 0.566621E+10 | 0.136572E+10 | 0.00 | 1.00 | 03-SEP-10:45 | 0.00 | 01-SEP-00:10 | 77770.68 | 10-SEP-10:45 | 63973.64 | 30-SEP-17:11 | 26554.69 | 24-SEP-11:55 | 19212.75 | 10-SEP-10:45 | 0.00 | 01-SEP-00:10 |
October | 0.731356E+10 | 0.219556E+10 | 132.65 | 0.654304E+10 | 0.770522E+09 | 0.00 | 1.00 | 01-OCT-10:25 | 0.00 | 01-OCT-00:10 | 81360.12 | 01-OCT-10:25 | 69229.07 | 16-OCT-17:11 | 32998.46 | 01-OCT-15:55 | 20254.32 | 01-OCT-12:01 | 0.00 | 01-OCT-00:10 |
November | 0.145793E+09 | 43269337.56 | 13.00 | 0.145793E+09 | 282.81 | 0.00 | 0.20 | 18-NOV-14:00 | 0.00 | 01-NOV-00:10 | 12246.88 | 18-NOV-14:00 | 12246.88 | 18-NOV-14:00 | 0.24 | 10-NOV-09:50 | 3645.06 | 18-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.117808E+09 | 35133124.83 | 11.50 | 0.117808E+09 | 108.74 | 0.00 | 0.15 | 19-DEC-13:00 | 0.00 | 01-DEC-00:10 | 8427.54 | 19-DEC-13:00 | 8427.54 | 19-DEC-13:00 | 0.14 | 07-DEC-13:10 | 2543.35 | 19-DEC-13:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.599841E+11 | 0.168143E+11 | 1033.87 | 0.448819E+11 | 0.151022E+11 | 0.00 | ||||||||||||||
Minimum of Months | 36295607.37 | 10813659.65 | 6.17 | 36295152.50 | 108.74 | 0.00 | 0.14 | 0.00 | 8427.54 | 7839.28 | 0.14 | 2543.35 | 0.00 | |||||||
Maximum of Months | 0.186192E+11 | 0.509406E+10 | 234.69 | 0.128271E+11 | 0.579216E+10 | 0.00 | 1.00 | 0.00 | 81360.12 | 69229.07 | 37184.84 | 20254.32 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.89 | 31.24 | 30.65 | 80.62 | 112.59 | 0.00 | 0.00 | 0.00 |
February | 73.66 | 33.97 | 39.69 | 88.90 | 105.17 | 0.00 | 0.00 | 0.00 |
March | 84.39 | 37.29 | 47.10 | 103.99 | 108.64 | 0.00 | 0.00 | 0.00 |
April | 116.16 | 60.32 | 55.84 | 161.81 | 95.68 | 0.00 | 0.00 | 0.00 |
May | 114.15 | 52.55 | 61.60 | 150.95 | 88.92 | 0.00 | 0.00 | 0.00 |
June | 121.18 | 60.56 | 60.62 | 172.08 | 70.01 | 0.00 | 0.00 | 0.00 |
July | 128.29 | 68.62 | 59.67 | 194.84 | 62.77 | 0.00 | 0.00 | 0.00 |
August | 120.17 | 65.02 | 55.16 | 186.15 | 65.43 | 0.00 | 0.00 | 0.00 |
September | 102.90 | 54.96 | 47.94 | 152.63 | 75.89 | 0.00 | 0.00 | 0.00 |
October | 78.80 | 43.04 | 35.76 | 120.79 | 84.33 | 0.00 | 0.00 | 0.00 |
November | 71.10 | 37.14 | 33.95 | 92.42 | 111.13 | 0.00 | 0.00 | 0.00 |
December | 62.73 | 33.58 | 29.15 | 82.37 | 118.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.70 | 48.25 | 46.45 | 132.52 | 91.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 61.89 | 31.24 | 29.15 | 80.62 | 62.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.29 | 68.62 | 61.60 | 194.84 | 118.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.89 | 31.24 | 30.65 | 80.62 | 112.59 | 0.00 | 0.00 | 0.00 |
February | 73.66 | 33.97 | 39.69 | 88.90 | 105.17 | 0.00 | 0.00 | 0.00 |
March | 84.39 | 37.29 | 47.10 | 103.99 | 108.64 | 0.00 | 0.00 | 0.00 |
April | 116.16 | 60.32 | 55.84 | 161.81 | 95.68 | 0.00 | 0.00 | 0.00 |
May | 114.15 | 52.55 | 61.60 | 150.95 | 88.92 | 0.00 | 0.00 | 0.00 |
June | 121.18 | 60.56 | 60.62 | 172.08 | 70.01 | 0.00 | 0.00 | 0.00 |
July | 128.29 | 68.62 | 59.67 | 194.84 | 62.77 | 0.00 | 0.00 | 0.00 |
August | 120.17 | 65.02 | 55.16 | 186.15 | 65.43 | 0.00 | 0.00 | 0.00 |
September | 102.90 | 54.96 | 47.94 | 152.63 | 75.89 | 0.00 | 0.00 | 0.00 |
October | 78.80 | 43.04 | 35.76 | 120.79 | 84.33 | 0.00 | 0.00 | 0.00 |
November | 71.10 | 37.14 | 33.95 | 92.42 | 111.13 | 0.00 | 0.00 | 0.00 |
December | 62.73 | 33.58 | 29.15 | 82.37 | 118.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.70 | 48.25 | 46.45 | 132.52 | 91.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 61.89 | 31.24 | 29.15 | 80.62 | 62.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.29 | 68.62 | 61.60 | 194.84 | 118.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 0.00 | 14.04 | 7.28 | 68.54 | 0.00 | 0.00 | 0.00 |
February | 17.63 | 0.00 | 17.63 | 7.98 | 64.45 | 0.00 | 0.00 | 0.00 |
March | 21.60 | 0.00 | 21.60 | 12.42 | 66.22 | 0.00 | 0.00 | 0.00 |
April | 24.96 | 0.16 | 24.80 | 16.29 | 57.62 | 0.00 | 0.00 | 0.00 |
May | 30.17 | 1.64 | 28.52 | 20.60 | 50.28 | 0.00 | 0.00 | 0.00 |
June | 31.94 | 3.19 | 28.75 | 28.07 | 39.36 | 0.00 | 0.00 | 0.00 |
July | 30.25 | 2.60 | 27.65 | 29.86 | 35.59 | 0.00 | 0.00 | 0.00 |
August | 25.19 | 0.63 | 24.56 | 24.08 | 38.01 | 0.00 | 0.00 | 0.00 |
September | 21.21 | 0.01 | 21.20 | 18.16 | 46.48 | 0.00 | 0.00 | 0.00 |
October | 16.82 | 0.00 | 16.82 | 16.88 | 51.02 | 0.00 | 0.00 | 0.00 |
November | 15.23 | 0.00 | 15.23 | 7.27 | 68.18 | 0.00 | 0.00 | 0.00 |
December | 13.07 | 0.00 | 13.07 | 5.98 | 72.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21.86 | 0.69 | 21.17 | 16.29 | 54.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.07 | 0.00 | 13.07 | 5.98 | 35.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 31.94 | 3.19 | 28.75 | 29.86 | 72.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 0.00 | 14.04 | 7.28 | 68.54 | 0.00 | 0.00 | 0.00 |
February | 17.62 | 0.00 | 17.62 | 7.98 | 64.45 | 0.00 | 0.00 | 0.00 |
March | 21.60 | 0.00 | 21.60 | 12.42 | 66.22 | 0.00 | 0.00 | 0.00 |
April | 24.96 | 0.16 | 24.80 | 16.29 | 57.62 | 0.00 | 0.00 | 0.00 |
May | 30.17 | 1.64 | 28.52 | 20.60 | 50.28 | 0.00 | 0.00 | 0.00 |
June | 31.94 | 3.19 | 28.75 | 28.07 | 39.36 | 0.00 | 0.00 | 0.00 |
July | 30.25 | 2.60 | 27.65 | 29.86 | 35.59 | 0.00 | 0.00 | 0.00 |
August | 25.19 | 0.63 | 24.56 | 24.08 | 38.01 | 0.00 | 0.00 | 0.00 |
September | 21.21 | 0.01 | 21.20 | 18.16 | 46.48 | 0.00 | 0.00 | 0.00 |
October | 16.82 | 0.00 | 16.82 | 16.88 | 51.02 | 0.00 | 0.00 | 0.00 |
November | 15.23 | 0.00 | 15.23 | 7.27 | 68.18 | 0.00 | 0.00 | 0.00 |
December | 13.07 | 0.00 | 13.07 | 5.98 | 72.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21.86 | 0.69 | 21.17 | 16.29 | 54.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.07 | 0.00 | 13.07 | 5.98 | 35.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 31.94 | 3.19 | 28.75 | 29.86 | 72.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 86.04 | 71.66 | 16.00 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 93.19 | 64.87 | 6.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 126.08 | 64.92 | 33.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 191.56 | 64.65 | 3.83 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 185.91 | 62.71 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.76 | 55.21 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 221.04 | 59.47 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.53 | 61.60 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 155.49 | 65.02 | 1.00 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 110.90 | 72.87 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 88.01 | 75.57 | 11.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 77.35 | 80.26 | 11.67 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 145.35 | 66.60 | 83.33 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 77.35 | 55.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 221.04 | 80.26 | 33.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 86.04 | 71.66 | 16.00 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 93.19 | 64.87 | 6.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 126.08 | 64.92 | 33.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 191.56 | 64.65 | 3.83 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 185.91 | 62.71 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.76 | 55.21 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 221.04 | 59.47 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.53 | 61.60 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 155.49 | 65.02 | 1.00 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 110.90 | 72.87 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 88.01 | 75.57 | 11.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 77.35 | 80.26 | 11.67 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 145.35 | 66.60 | 83.33 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 77.35 | 55.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 221.04 | 80.26 | 33.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 86.04 | 71.66 | 16.00 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 93.19 | 64.87 | 6.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 126.08 | 64.92 | 33.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 191.56 | 64.65 | 3.83 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 185.91 | 62.71 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.76 | 55.21 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 221.04 | 59.47 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.53 | 61.60 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 155.49 | 65.02 | 1.00 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 110.90 | 72.87 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 88.01 | 75.57 | 11.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 77.35 | 80.26 | 11.67 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 145.35 | 66.60 | 83.33 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 77.35 | 55.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 221.04 | 80.26 | 33.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 86.04 | 71.66 | 16.00 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 93.19 | 64.87 | 6.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 126.08 | 64.92 | 33.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 191.56 | 64.65 | 3.83 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 185.91 | 62.71 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.76 | 55.21 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 221.04 | 59.47 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.53 | 61.60 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 155.49 | 65.02 | 1.00 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 110.90 | 72.87 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 88.01 | 75.57 | 11.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 77.35 | 80.26 | 11.67 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 145.35 | 66.60 | 83.33 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 77.35 | 55.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 221.04 | 80.26 | 33.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 86.04 | 71.66 | 16.00 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 93.19 | 64.87 | 6.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 126.08 | 64.92 | 33.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 191.56 | 64.65 | 3.83 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 185.91 | 62.71 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.76 | 55.21 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 221.04 | 59.47 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.53 | 61.60 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 155.49 | 65.02 | 1.00 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 110.90 | 72.87 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 88.01 | 75.57 | 11.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 77.35 | 80.26 | 11.67 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 145.35 | 66.60 | 83.33 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 77.35 | 55.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 221.04 | 80.26 | 33.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 86.04 | 71.66 | 16.00 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 93.19 | 64.87 | 6.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 126.08 | 64.92 | 33.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 191.56 | 64.65 | 3.83 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 185.91 | 62.71 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.76 | 55.21 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 221.04 | 59.47 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.53 | 61.60 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 155.49 | 65.02 | 1.00 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 110.90 | 72.87 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 88.01 | 75.57 | 11.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 77.35 | 80.26 | 11.67 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 145.35 | 66.60 | 83.33 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 77.35 | 55.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 221.04 | 80.26 | 33.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 86.04 | 71.66 | 16.00 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 93.19 | 64.87 | 6.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 126.08 | 64.92 | 33.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 191.56 | 64.65 | 3.83 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 185.91 | 62.71 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.76 | 55.21 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 221.04 | 59.47 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.53 | 61.60 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 155.49 | 65.02 | 1.00 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 110.90 | 72.87 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 88.01 | 75.57 | 11.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 77.35 | 80.26 | 11.67 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 145.35 | 66.60 | 83.33 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 77.35 | 55.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 221.04 | 80.26 | 33.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 86.04 | 71.66 | 16.00 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 93.19 | 64.87 | 6.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 126.08 | 64.92 | 33.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 191.56 | 64.65 | 3.83 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 185.91 | 62.71 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.76 | 55.21 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 221.04 | 59.47 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.53 | 61.60 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 155.49 | 65.02 | 1.00 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 110.90 | 72.87 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 88.01 | 75.57 | 11.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 77.35 | 80.26 | 11.67 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 145.35 | 66.60 | 83.33 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 77.35 | 55.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 221.04 | 80.26 | 33.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 86.04 | 71.66 | 16.00 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 93.19 | 64.87 | 6.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 126.08 | 64.92 | 33.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 191.56 | 64.65 | 3.83 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 185.91 | 62.71 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.76 | 55.21 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 221.04 | 59.47 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.53 | 61.60 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 155.49 | 65.02 | 1.00 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 110.90 | 72.87 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 88.01 | 75.57 | 11.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 77.35 | 80.26 | 11.67 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 145.35 | 66.60 | 83.33 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 77.35 | 55.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 221.04 | 80.26 | 33.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 86.04 | 71.66 | 16.00 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 93.19 | 64.87 | 6.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 126.08 | 64.92 | 33.00 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 191.56 | 64.65 | 3.83 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 185.91 | 62.71 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 199.76 | 55.21 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 221.04 | 59.47 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 205.53 | 61.60 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 155.49 | 65.02 | 1.00 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 110.90 | 72.87 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 88.01 | 75.57 | 11.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 77.35 | 80.26 | 11.67 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 145.35 | 66.60 | 83.33 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 77.35 | 55.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 221.04 | 80.26 | 33.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.165761E+09 | 83680416.58 | 82080089.53 | 0.215920E+09 | 0.301557E+09 |
February | 0.178200E+09 | 82187440.48 | 96012772.88 | 0.215073E+09 | 0.254428E+09 |
March | 0.226023E+09 | 99871076.63 | 0.126152E+09 | 0.278517E+09 | 0.290969E+09 |
April | 0.301091E+09 | 0.156353E+09 | 0.144738E+09 | 0.419421E+09 | 0.248001E+09 |
May | 0.305741E+09 | 0.140755E+09 | 0.164986E+09 | 0.404300E+09 | 0.238150E+09 |
June | 0.314096E+09 | 0.156963E+09 | 0.157133E+09 | 0.446021E+09 | 0.181464E+09 |
July | 0.343622E+09 | 0.183789E+09 | 0.159833E+09 | 0.521858E+09 | 0.168136E+09 |
August | 0.321876E+09 | 0.174137E+09 | 0.147739E+09 | 0.498594E+09 | 0.175243E+09 |
September | 0.266712E+09 | 0.142464E+09 | 0.124248E+09 | 0.395618E+09 | 0.196713E+09 |
October | 0.211053E+09 | 0.115266E+09 | 95786958.15 | 0.323514E+09 | 0.225880E+09 |
November | 0.184282E+09 | 96271190.46 | 88011008.02 | 0.239561E+09 | 0.288060E+09 |
December | 0.168009E+09 | 89929742.44 | 78079734.58 | 0.220618E+09 | 0.317689E+09 |
Annual Sum or Average | 0.298647E+10 | 0.152167E+10 | 0.146480E+10 | 0.417901E+10 | 0.288629E+10 |
Minimum of Months | 0.165761E+09 | 82187440.48 | 78079734.58 | 0.215073E+09 | 0.168136E+09 |
Maximum of Months | 0.343622E+09 | 0.183789E+09 | 0.164986E+09 | 0.521858E+09 | 0.317689E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.165761E+09 | 83680416.58 | 82080089.53 | 0.215920E+09 | 0.301557E+09 |
February | 0.178200E+09 | 82187440.48 | 96012772.88 | 0.215073E+09 | 0.254428E+09 |
March | 0.226023E+09 | 99871076.63 | 0.126152E+09 | 0.278517E+09 | 0.290969E+09 |
April | 0.301091E+09 | 0.156353E+09 | 0.144738E+09 | 0.419421E+09 | 0.248001E+09 |
May | 0.305741E+09 | 0.140755E+09 | 0.164986E+09 | 0.404300E+09 | 0.238150E+09 |
June | 0.314096E+09 | 0.156963E+09 | 0.157133E+09 | 0.446021E+09 | 0.181464E+09 |
July | 0.343622E+09 | 0.183789E+09 | 0.159833E+09 | 0.521858E+09 | 0.168136E+09 |
August | 0.321876E+09 | 0.174137E+09 | 0.147739E+09 | 0.498594E+09 | 0.175243E+09 |
September | 0.266712E+09 | 0.142464E+09 | 0.124248E+09 | 0.395618E+09 | 0.196713E+09 |
October | 0.211053E+09 | 0.115266E+09 | 95786958.15 | 0.323514E+09 | 0.225880E+09 |
November | 0.184282E+09 | 96271190.46 | 88011008.02 | 0.239561E+09 | 0.288060E+09 |
December | 0.168009E+09 | 89929742.44 | 78079734.58 | 0.220618E+09 | 0.317689E+09 |
Annual Sum or Average | 0.298647E+10 | 0.152167E+10 | 0.146480E+10 | 0.417901E+10 | 0.288629E+10 |
Minimum of Months | 0.165761E+09 | 82187440.48 | 78079734.58 | 0.215073E+09 | 0.168136E+09 |
Maximum of Months | 0.343622E+09 | 0.183789E+09 | 0.164986E+09 | 0.521858E+09 | 0.317689E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37608032.36 | 0.00 | 37608032.36 | 19497006.85 | 0.183585E+09 |
February | 42639569.70 | 0.00 | 42639569.70 | 19298283.62 | 0.155914E+09 |
March | 57856777.19 | 2101.94 | 57854675.25 | 33278215.50 | 0.177356E+09 |
April | 64706737.07 | 418984.49 | 64287752.58 | 42214959.03 | 0.149346E+09 |
May | 80799630.00 | 4399131.38 | 76400498.62 | 55169326.15 | 0.134668E+09 |
June | 82791055.08 | 8278631.33 | 74512423.75 | 72757990.18 | 0.102010E+09 |
July | 81014815.76 | 6963590.51 | 74051225.25 | 79973200.66 | 95326698.07 |
August | 67463903.85 | 1675986.65 | 65787917.20 | 64491868.57 | 0.101813E+09 |
September | 54982697.04 | 21958.86 | 54960738.17 | 47059234.70 | 0.120489E+09 |
October | 45054435.88 | 0.00 | 45054435.88 | 45201829.09 | 0.136653E+09 |
November | 39477619.92 | 0.00 | 39477619.92 | 18835588.25 | 0.176729E+09 |
December | 35009879.03 | 0.00 | 35009879.03 | 16006389.58 | 0.194686E+09 |
Annual Sum or Average | 0.689405E+09 | 21760385.16 | 0.667645E+09 | 0.513784E+09 | 0.172858E+10 |
Minimum of Months | 35009879.03 | 0.00 | 35009879.03 | 16006389.58 | 95326698.07 |
Maximum of Months | 82791055.08 | 8278631.33 | 76400498.62 | 79973200.66 | 0.194686E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37606988.46 | 0.00 | 37606988.46 | 19496192.00 | 0.183583E+09 |
February | 42638301.05 | 0.00 | 42638301.05 | 19297111.52 | 0.155913E+09 |
March | 57855062.38 | 2101.84 | 57852960.54 | 33276320.50 | 0.177356E+09 |
April | 64705116.38 | 418964.85 | 64286151.52 | 42213473.44 | 0.149346E+09 |
May | 80797285.91 | 4398925.19 | 76398360.72 | 55166388.47 | 0.134668E+09 |
June | 82788649.05 | 8278243.30 | 74510405.75 | 72754612.04 | 0.102010E+09 |
July | 81012680.52 | 6963264.11 | 74049416.40 | 79970370.45 | 95326202.03 |
August | 67462286.67 | 1675908.09 | 65786378.58 | 64490223.73 | 0.101812E+09 |
September | 54981291.79 | 21957.84 | 54959333.96 | 47057761.52 | 0.120488E+09 |
October | 45053230.82 | 0.00 | 45053230.82 | 45200684.77 | 0.136651E+09 |
November | 39476510.63 | 0.00 | 39476510.63 | 18834680.89 | 0.176728E+09 |
December | 35008925.79 | 0.00 | 35008925.79 | 16005904.00 | 0.194685E+09 |
Annual Sum or Average | 0.689386E+09 | 21759365.22 | 0.667627E+09 | 0.513764E+09 | 0.172857E+10 |
Minimum of Months | 35008925.79 | 0.00 | 35008925.79 | 16005904.00 | 95326202.03 |
Maximum of Months | 82788649.05 | 8278243.30 | 76398360.72 | 79970370.45 | 0.194685E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.230447E+09 | 0.191943E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.225439E+09 | 0.156925E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.337695E+09 | 0.173893E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.496512E+09 | 0.167582E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.497931E+09 | 0.167960E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.517768E+09 | 0.143109E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.592024E+09 | 0.159298E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.550479E+09 | 0.164989E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.403030E+09 | 0.168544E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.297046E+09 | 0.195167E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.228123E+09 | 0.195889E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.207174E+09 | 0.214956E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.458367E+10 | 0.210026E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.207174E+09 | 0.143109E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.592024E+09 | 0.214956E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.230447E+09 | 0.191943E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.225439E+09 | 0.156925E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.337695E+09 | 0.173893E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.496512E+09 | 0.167582E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.497931E+09 | 0.167960E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.517768E+09 | 0.143109E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.592024E+09 | 0.159298E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.550479E+09 | 0.164989E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.403030E+09 | 0.168544E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.297046E+09 | 0.195167E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.228123E+09 | 0.195889E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.207174E+09 | 0.214956E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.458367E+10 | 0.210026E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.207174E+09 | 0.143109E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.592024E+09 | 0.214956E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.230447E+09 | 0.191943E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.225439E+09 | 0.156925E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.337695E+09 | 0.173893E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.496512E+09 | 0.167582E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.497931E+09 | 0.167960E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.517768E+09 | 0.143109E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.592024E+09 | 0.159298E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.550479E+09 | 0.164989E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.403030E+09 | 0.168544E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.297046E+09 | 0.195167E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.228123E+09 | 0.195889E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.207174E+09 | 0.214956E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.458367E+10 | 0.210026E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.207174E+09 | 0.143109E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.592024E+09 | 0.214956E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.230447E+09 | 0.191943E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.225439E+09 | 0.156925E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.337695E+09 | 0.173893E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.496512E+09 | 0.167582E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.497931E+09 | 0.167960E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.517768E+09 | 0.143109E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.592024E+09 | 0.159298E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.550479E+09 | 0.164989E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.403030E+09 | 0.168544E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.297046E+09 | 0.195167E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.228123E+09 | 0.195889E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.207174E+09 | 0.214956E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.458367E+10 | 0.210026E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.207174E+09 | 0.143109E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.592024E+09 | 0.214956E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.230447E+09 | 0.191943E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.225439E+09 | 0.156925E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.337695E+09 | 0.173893E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.496512E+09 | 0.167582E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.497931E+09 | 0.167960E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.517768E+09 | 0.143109E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.592024E+09 | 0.159298E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.550479E+09 | 0.164989E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.403030E+09 | 0.168544E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.297046E+09 | 0.195167E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.228123E+09 | 0.195889E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.207174E+09 | 0.214956E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.458367E+10 | 0.210026E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.207174E+09 | 0.143109E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.592024E+09 | 0.214956E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.230447E+09 | 0.191943E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.225439E+09 | 0.156925E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.337695E+09 | 0.173893E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.496512E+09 | 0.167582E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.497931E+09 | 0.167960E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.517768E+09 | 0.143109E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.592024E+09 | 0.159298E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.550479E+09 | 0.164989E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.403030E+09 | 0.168544E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.297046E+09 | 0.195167E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.228123E+09 | 0.195889E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.207174E+09 | 0.214956E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.458367E+10 | 0.210026E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.207174E+09 | 0.143109E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.592024E+09 | 0.214956E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.230447E+09 | 0.191943E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.225439E+09 | 0.156925E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.337695E+09 | 0.173893E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.496512E+09 | 0.167582E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.497931E+09 | 0.167960E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.517768E+09 | 0.143109E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.592024E+09 | 0.159298E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.550479E+09 | 0.164989E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.403030E+09 | 0.168544E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.297046E+09 | 0.195167E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.228123E+09 | 0.195889E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.207174E+09 | 0.214956E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.458367E+10 | 0.210026E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.207174E+09 | 0.143109E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.592024E+09 | 0.214956E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.230447E+09 | 0.191943E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.225439E+09 | 0.156925E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.337695E+09 | 0.173893E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.496512E+09 | 0.167582E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.497931E+09 | 0.167960E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.517768E+09 | 0.143109E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.592024E+09 | 0.159298E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.550479E+09 | 0.164989E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.403030E+09 | 0.168544E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.297046E+09 | 0.195167E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.228123E+09 | 0.195889E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.207174E+09 | 0.214956E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.458367E+10 | 0.210026E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.207174E+09 | 0.143109E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.592024E+09 | 0.214956E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.230447E+09 | 0.191943E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.225439E+09 | 0.156925E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.337695E+09 | 0.173893E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.496512E+09 | 0.167582E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.497931E+09 | 0.167960E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.517768E+09 | 0.143109E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.592024E+09 | 0.159298E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.550479E+09 | 0.164989E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.403030E+09 | 0.168544E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.297046E+09 | 0.195167E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.228123E+09 | 0.195889E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.207174E+09 | 0.214956E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.458367E+10 | 0.210026E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.207174E+09 | 0.143109E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.592024E+09 | 0.214956E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.230447E+09 | 0.191943E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.225439E+09 | 0.156925E+09 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.337695E+09 | 0.173893E+09 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.496512E+09 | 0.167582E+09 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.497931E+09 | 0.167960E+09 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.517768E+09 | 0.143109E+09 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.592024E+09 | 0.159298E+09 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.550479E+09 | 0.164989E+09 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.403030E+09 | 0.168544E+09 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.297046E+09 | 0.195167E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.228123E+09 | 0.195889E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.207174E+09 | 0.214956E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.458367E+10 | 0.210026E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.207174E+09 | 0.143109E+09 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.592024E+09 | 0.214956E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 170.46 | 356.94 | 151.86 | 62.49 | 89.37 | 0.00 | 0.00 |
February | 188.01 | 333.49 | 182.57 | 67.95 | 114.63 | 0.00 | 0.00 |
March | 227.30 | 344.18 | 211.98 | 74.58 | 137.40 | 0.00 | 0.00 |
April | 352.00 | 302.39 | 282.25 | 120.97 | 161.29 | 0.00 | 0.00 |
May | 341.30 | 276.59 | 288.63 | 108.39 | 180.25 | 0.00 | 0.00 |
June | 397.98 | 216.42 | 306.24 | 127.50 | 178.74 | 0.00 | 0.00 |
July | 446.97 | 194.30 | 317.08 | 142.44 | 174.64 | 0.00 | 0.00 |
August | 418.67 | 205.09 | 290.73 | 131.28 | 159.44 | 0.00 | 0.00 |
September | 337.14 | 240.33 | 248.22 | 109.94 | 138.28 | 0.00 | 0.00 |
October | 271.60 | 266.99 | 191.24 | 86.07 | 105.17 | 0.00 | 0.00 |
November | 192.88 | 352.13 | 172.65 | 74.28 | 98.37 | 0.00 | 0.00 |
December | 170.59 | 376.50 | 151.60 | 67.15 | 84.45 | 0.00 | 0.00 |
Annual Sum or Average | 293.47 | 288.53 | 233.12 | 97.88 | 135.24 | 0.00 | 0.00 |
Minimum of Months | 170.46 | 194.30 | 151.60 | 62.49 | 84.45 | 0.00 | 0.00 |
Maximum of Months | 446.97 | 376.50 | 317.08 | 142.44 | 180.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2877.32 | 2519.30 | 679.56 | 448.51 | 231.05 | 0.00 | 0.00 |
February | 3134.82 | 2198.68 | 772.65 | 434.89 | 337.76 | 0.00 | 0.00 |
March | 4203.00 | 2176.07 | 998.72 | 564.70 | 434.02 | 0.00 | 0.00 |
April | 6419.51 | 2251.20 | 1492.05 | 1076.93 | 415.12 | 0.00 | 0.00 |
May | 5921.58 | 2201.67 | 1488.73 | 947.82 | 540.91 | 0.00 | 0.00 |
June | 8200.04 | 2644.80 | 1578.62 | 1077.36 | 501.26 | 0.00 | 0.00 |
July | 12572.70 | 3361.60 | 1730.01 | 1287.60 | 442.41 | 0.00 | 0.00 |
August | 11398.18 | 3512.67 | 1603.69 | 1222.40 | 381.29 | 0.00 | 0.00 |
September | 5686.99 | 3250.71 | 1236.62 | 874.92 | 361.70 | 0.00 | 0.00 |
October | 4243.48 | 3188.38 | 887.94 | 612.54 | 275.40 | 0.00 | 0.00 |
November | 3005.87 | 2429.63 | 723.96 | 464.52 | 259.44 | 0.00 | 0.00 |
December | 2597.33 | 2729.19 | 634.10 | 432.24 | 201.86 | 0.00 | 0.00 |
Annual Sum or Average | 5877.72 | 2710.16 | 1154.18 | 788.98 | 365.20 | 0.00 | 0.00 |
Minimum of Months | 2597.33 | 2176.07 | 634.10 | 432.24 | 201.86 | 0.00 | 0.00 |
Maximum of Months | 12572.70 | 3512.67 | 1730.01 | 1287.60 | 540.91 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.456573E+09 | 0.956022E+09 | 0.406736E+09 | 0.167361E+09 | 0.239375E+09 | 0.00 | 0.00 |
February | 0.454843E+09 | 0.806786E+09 | 0.441678E+09 | 0.164375E+09 | 0.277303E+09 | 0.00 | 0.00 |
March | 0.608796E+09 | 0.921859E+09 | 0.567758E+09 | 0.199746E+09 | 0.368011E+09 | 0.00 | 0.00 |
April | 0.912373E+09 | 0.783798E+09 | 0.731594E+09 | 0.313543E+09 | 0.418051E+09 | 0.00 | 0.00 |
May | 0.914125E+09 | 0.740824E+09 | 0.773078E+09 | 0.290308E+09 | 0.482770E+09 | 0.00 | 0.00 |
June | 0.103157E+10 | 0.560961E+09 | 0.793772E+09 | 0.330483E+09 | 0.463289E+09 | 0.00 | 0.00 |
July | 0.119715E+10 | 0.520416E+09 | 0.849271E+09 | 0.381505E+09 | 0.467766E+09 | 0.00 | 0.00 |
August | 0.112137E+10 | 0.549313E+09 | 0.778678E+09 | 0.351626E+09 | 0.427052E+09 | 0.00 | 0.00 |
September | 0.873877E+09 | 0.622927E+09 | 0.643388E+09 | 0.284973E+09 | 0.358416E+09 | 0.00 | 0.00 |
October | 0.727462E+09 | 0.715096E+09 | 0.512214E+09 | 0.230532E+09 | 0.281682E+09 | 0.00 | 0.00 |
November | 0.499940E+09 | 0.912724E+09 | 0.447519E+09 | 0.192542E+09 | 0.254976E+09 | 0.00 | 0.00 |
December | 0.456916E+09 | 0.100842E+10 | 0.406038E+09 | 0.179859E+09 | 0.226178E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.925499E+10 | 0.909914E+10 | 0.735172E+10 | 0.308685E+10 | 0.426487E+10 | 0.00 | 0.00 |
Minimum of Months | 0.454843E+09 | 0.520416E+09 | 0.406038E+09 | 0.164375E+09 | 0.226178E+09 | 0.00 | 0.00 |
Maximum of Months | 0.119715E+10 | 0.100842E+10 | 0.849271E+09 | 0.381505E+09 | 0.482770E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.770660E+10 | 0.674770E+10 | 0.182014E+10 | 0.120128E+10 | 0.618857E+09 | 0.00 | 0.00 |
February | 0.758376E+10 | 0.531904E+10 | 0.186919E+10 | 0.105210E+10 | 0.817099E+09 | 0.00 | 0.00 |
March | 0.112573E+11 | 0.582839E+10 | 0.267498E+10 | 0.151249E+10 | 0.116249E+10 | 0.00 | 0.00 |
April | 0.166394E+11 | 0.583511E+10 | 0.386740E+10 | 0.279141E+10 | 0.107599E+10 | 0.00 | 0.00 |
May | 0.158604E+11 | 0.589695E+10 | 0.398741E+10 | 0.253863E+10 | 0.144878E+10 | 0.00 | 0.00 |
June | 0.212545E+11 | 0.685532E+10 | 0.409178E+10 | 0.279251E+10 | 0.129928E+10 | 0.00 | 0.00 |
July | 0.336747E+11 | 0.900372E+10 | 0.463365E+10 | 0.344870E+10 | 0.118495E+10 | 0.00 | 0.00 |
August | 0.305289E+11 | 0.940833E+10 | 0.429533E+10 | 0.327408E+10 | 0.102125E+10 | 0.00 | 0.00 |
September | 0.147407E+11 | 0.842583E+10 | 0.320532E+10 | 0.226779E+10 | 0.937531E+09 | 0.00 | 0.00 |
October | 0.113657E+11 | 0.853975E+10 | 0.237825E+10 | 0.164062E+10 | 0.737623E+09 | 0.00 | 0.00 |
November | 0.779121E+10 | 0.629761E+10 | 0.187652E+10 | 0.120404E+10 | 0.672479E+09 | 0.00 | 0.00 |
December | 0.695668E+10 | 0.730985E+10 | 0.169838E+10 | 0.115771E+10 | 0.540670E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.185360E+12 | 0.854676E+11 | 0.363984E+11 | 0.248814E+11 | 0.115170E+11 | 0.00 | 0.00 |
Minimum of Months | 0.695668E+10 | 0.531904E+10 | 0.169838E+10 | 0.105210E+10 | 0.540670E+09 | 0.00 | 0.00 |
Maximum of Months | 0.336747E+11 | 0.940833E+10 | 0.463365E+10 | 0.344870E+10 | 0.144878E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.883343E+09 | -742386654.4 | 0.00 | 0.00 | 744.00 | 0.00 | -140956812.0 | 58.99 | 0.00 | 0.00 |
February | 0.809127E+09 | -682815381.5 | 0.00 | 0.00 | 672.00 | 0.00 | -126312019.5 | 58.99 | 0.00 | 0.00 |
March | 0.928681E+09 | -789300060.1 | 0.00 | 0.00 | 744.00 | 0.00 | -139380914.5 | 58.99 | 0.00 | 0.00 |
April | 0.848224E+09 | -718017767.2 | 0.00 | 0.00 | 720.00 | 0.00 | -130206110.0 | 58.99 | 0.00 | 0.00 |
May | 0.861446E+09 | -727621986.7 | 0.00 | 0.00 | 744.00 | 0.00 | -133824397.8 | 58.99 | 0.00 | 0.00 |
June | 0.837037E+09 | -708290890.8 | 0.00 | 0.00 | 720.00 | 0.00 | -128746069.5 | 58.99 | 0.00 | 0.00 |
July | 0.806425E+09 | -674416990.4 | 0.00 | 0.00 | 744.00 | 0.00 | -132008296.6 | 58.99 | 0.00 | 0.00 |
August | 0.856055E+09 | -723271835.8 | 0.00 | 0.00 | 744.00 | 0.00 | -132783482.1 | 58.99 | 0.00 | 0.00 |
September | 0.809100E+09 | -680577153.2 | 0.00 | 0.00 | 720.00 | 0.00 | -128522594.6 | 58.99 | 0.00 | 0.00 |
October | 0.830729E+09 | -697622893.6 | 0.00 | 0.00 | 744.00 | 0.00 | -133105832.7 | 58.99 | 0.00 | 0.00 |
November | 0.820274E+09 | -687598223.7 | 0.00 | 0.00 | 720.00 | 0.00 | -132675894.8 | 58.99 | 0.00 | 0.00 |
December | 0.871442E+09 | -732052779.5 | 0.00 | 0.00 | 744.00 | 0.00 | -139389458.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.101619E+11 | -0.856397E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.159791E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.806425E+09 | -789300060.1 | 0.00 | 0.00 | 672.00 | 0.00 | -140956812.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.928681E+09 | -674416990.4 | 0.00 | 0.00 | 744.00 | 0.00 | -126312019.5 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 293.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 279.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 338.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 358.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 393.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 381.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 390.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 328.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 296.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 300.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 297.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4065.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 279.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.349337E+09 | 29103.52 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138809E+09 | 29103.52 | 27-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.235355E+09 | 29103.52 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12681892.42 | 29103.52 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 26320507.21 | 24204.70 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161818E+09 | 29103.52 | 13-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.924322E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.349337E+09 | 29103.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.226872E+09 | 32589.99 | 03-JAN-06:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226872E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.226872E+09 | 32589.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.632959E+09 | 0.599130E+09 | 6622.59 | 24-JAN-15:30 | 6330.87 | 0.00 |
February | 0.00 | 0.00 | 0.206848E+09 | 0.201428E+09 | 5656.41 | 01-FEB-12:00 | 5656.41 | 0.00 |
March | 0.00 | 0.00 | 0.475835E+09 | 0.402284E+09 | 20876.98 | 23-MAR-17:15 | 13879.01 | 0.00 |
April | 0.00 | 0.00 | 0.179272E+10 | 0.146073E+10 | 21135.69 | 26-APR-17:11 | 15763.76 | 0.00 |
May | 0.00 | 0.00 | 0.191927E+10 | 0.159994E+10 | 20912.82 | 02-MAY-17:15 | 13873.79 | 0.00 |
June | 0.00 | 0.00 | 0.527338E+10 | 0.399139E+10 | 22508.42 | 27-JUN-17:10 | 16689.69 | 0.00 |
July | 0.00 | 0.00 | 0.932957E+10 | 0.662957E+10 | 23258.81 | 28-JUL-17:10 | 15229.54 | 0.00 |
August | 0.00 | 0.00 | 0.100653E+11 | 0.704922E+10 | 22871.48 | 18-AUG-17:10 | 13151.62 | 0.00 |
September | 0.00 | 0.00 | 0.559181E+10 | 0.419095E+10 | 23048.76 | 21-SEP-22:05 | 13025.76 | 0.00 |
October | 0.00 | 0.00 | 0.527984E+10 | 0.436514E+10 | 22952.94 | 01-OCT-23:13 | 15449.42 | 0.00 |
November | 0.00 | 0.00 | 0.575031E+09 | 0.552114E+09 | 6981.50 | 18-NOV-14:40 | 6889.63 | 0.00 |
December | 0.00 | 0.00 | 0.803527E+09 | 0.796638E+09 | 18696.03 | 05-DEC-18:45 | 18696.03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.419460E+11 | 0.318385E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.206848E+09 | 0.201428E+09 | 5656.41 | 5656.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.100653E+11 | 0.704922E+10 | 23258.81 | 18696.03 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.136594E+09 | 0.136566E+09 | 8622.13 | 18-JAN-13:10 | 8622.13 | 0.00 |
February | 0.00 | 0.00 | 36295607.37 | 36295152.50 | 8463.33 | 01-FEB-12:00 | 8463.33 | 0.00 |
March | 0.00 | 0.00 | 0.122724E+09 | 0.101315E+09 | 10299.56 | 23-MAR-14:00 | 7839.28 | 0.00 |
April | 0.00 | 0.00 | 0.152781E+10 | 0.128626E+10 | 74174.52 | 30-APR-12:59 | 62881.89 | 0.00 |
May | 0.00 | 0.00 | 0.116770E+10 | 0.995345E+09 | 19522.50 | 04-MAY-12:10 | 16900.29 | 0.00 |
June | 0.00 | 0.00 | 0.655222E+10 | 0.486793E+10 | 78231.92 | 29-JUN-17:12 | 51956.30 | 0.00 |
July | 0.00 | 0.00 | 0.172124E+11 | 0.121582E+11 | 81060.05 | 31-JUL-17:15 | 50037.52 | 0.00 |
August | 0.00 | 0.00 | 0.186192E+11 | 0.128271E+11 | 80736.26 | 13-AUG-10:25 | 51853.57 | 0.00 |
September | 0.00 | 0.00 | 0.703193E+10 | 0.566621E+10 | 77770.68 | 10-SEP-10:45 | 54138.09 | 0.00 |
October | 0.00 | 0.00 | 0.731356E+10 | 0.654304E+10 | 81360.12 | 01-OCT-10:25 | 49504.09 | 0.00 |
November | 0.00 | 0.00 | 0.145793E+09 | 0.145793E+09 | 12246.88 | 18-NOV-14:00 | 12246.88 | 0.00 |
December | 0.00 | 0.00 | 0.117808E+09 | 0.117808E+09 | 8427.54 | 19-DEC-13:00 | 8427.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.599841E+11 | 0.448819E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 36295607.37 | 36295152.50 | 8427.54 | 7839.28 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.186192E+11 | 0.128271E+11 | 81360.12 | 62881.89 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.136100E+10 | 0.36 | 1365.62 | 02-JAN-09:05 | 0.95 |
February | 0.124806E+10 | 0.37 | 1365.62 | 01-FEB-09:20 | 0.95 |
March | 0.146855E+10 | 0.39 | 1365.62 | 01-MAR-07:17 | 0.95 |
April | 0.139056E+10 | 0.39 | 1365.62 | 03-APR-16:20 | 0.95 |
May | 0.147161E+10 | 0.41 | 1365.62 | 01-MAY-11:30 | 0.95 |
June | 0.156980E+10 | 0.48 | 1365.62 | 01-JUN-11:50 | 0.94 |
July | 0.163414E+10 | 0.50 | 1365.62 | 03-JUL-07:50 | 0.94 |
August | 0.169576E+10 | 0.51 | 1365.62 | 08-AUG-08:20 | 0.94 |
September | 0.152145E+10 | 0.48 | 1365.62 | 01-SEP-09:30 | 0.94 |
October | 0.147020E+10 | 0.41 | 1365.62 | 02-OCT-06:15 | 0.94 |
November | 0.130012E+10 | 0.35 | 1365.62 | 08-NOV-13:20 | 0.95 |
December | 0.135672E+10 | 0.36 | 1365.62 | 04-DEC-14:20 | 0.95 |
Annual Sum or Average | 0.174880E+11 | 0.42 | |||
Minimum of Months | 0.124806E+10 | 0.35 | 1365.62 | 0.94 | |
Maximum of Months | 0.169576E+10 | 0.51 | 1365.62 | 0.95 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.375740E+10 | 0.35 | 3785.52 | 14-JAN-14:20 | 0.91 |
February | 0.344785E+10 | 0.34 | 3785.52 | 01-FEB-11:20 | 0.91 |
March | 0.404748E+10 | 0.36 | 3785.52 | 11-MAR-11:10 | 0.91 |
April | 0.375782E+10 | 0.35 | 3785.52 | 01-APR-12:10 | 0.91 |
May | 0.389757E+10 | 0.35 | 3785.52 | 01-MAY-11:50 | 0.91 |
June | 0.397377E+10 | 0.37 | 3785.52 | 01-JUN-12:30 | 0.91 |
July | 0.400779E+10 | 0.37 | 3785.52 | 03-JUL-06:15 | 0.90 |
August | 0.419116E+10 | 0.38 | 3785.52 | 01-AUG-13:20 | 0.91 |
September | 0.379481E+10 | 0.36 | 3785.52 | 01-SEP-15:20 | 0.91 |
October | 0.379611E+10 | 0.35 | 3785.52 | 03-OCT-09:40 | 0.90 |
November | 0.359776E+10 | 0.33 | 3785.52 | 18-NOV-10:30 | 0.91 |
December | 0.374767E+10 | 0.34 | 3785.52 | 05-DEC-10:10 | 0.91 |
Annual Sum or Average | 0.460172E+11 | 0.35 | |||
Minimum of Months | 0.344785E+10 | 0.33 | 3785.52 | 0.90 | |
Maximum of Months | 0.419116E+10 | 0.38 | 3785.52 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.153176E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.130401E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.159525E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.186495E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.197884E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.293134E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.400612E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.425511E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.299574E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.287883E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.145529E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.157376E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.283710E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.130401E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.425511E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.379822E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.345867E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.408305E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.419140E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.423260E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.579921E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.871344E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.928522E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.585420E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.599166E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.364103E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.378280E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.628315E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.345867E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.928522E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.136100E+10 | 0.632959E+09 | 0.349337E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124806E+10 | 0.206848E+09 | 0.138809E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146855E+10 | 0.475835E+09 | 0.235355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139056E+10 | 0.179272E+10 | 12681892.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147161E+10 | 0.191927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156980E+10 | 0.527338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163414E+10 | 0.932957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169576E+10 | 0.100653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152145E+10 | 0.559181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147020E+10 | 0.527984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130012E+10 | 0.575031E+09 | 26320507.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135672E+10 | 0.803527E+09 | 0.161818E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174880E+11 | 0.419460E+11 | 0.924322E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124806E+10 | 0.206848E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169576E+10 | 0.100653E+11 | 0.349337E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.375740E+10 | 0.136594E+09 | 0.226872E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.344785E+10 | 36295607.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.404748E+10 | 0.122724E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.375782E+10 | 0.152781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.389757E+10 | 0.116770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.397377E+10 | 0.655222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.400779E+10 | 0.172124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.419116E+10 | 0.186192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.379481E+10 | 0.703193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.379611E+10 | 0.731356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.359776E+10 | 0.145793E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.374767E+10 | 0.117808E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.460172E+11 | 0.599841E+11 | 0.226872E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.344785E+10 | 36295607.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.419116E+10 | 0.186192E+11 | 0.226872E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.136100E+10 | 0.00 | 0.00 | 0.00 | 0.170762E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124806E+10 | 0.00 | 0.00 | 0.00 | 55944370.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146855E+10 | 0.00 | 0.00 | 0.00 | 0.126699E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139056E+10 | 0.00 | 0.00 | 0.00 | 0.474386E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147161E+10 | 0.00 | 0.00 | 0.00 | 0.507229E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156980E+10 | 0.00 | 0.00 | 0.00 | 0.136154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163414E+10 | 0.00 | 0.00 | 0.00 | 0.237198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169576E+10 | 0.00 | 0.00 | 0.00 | 0.255935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152145E+10 | 0.00 | 0.00 | 0.00 | 0.147429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147020E+10 | 0.00 | 0.00 | 0.00 | 0.140864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130012E+10 | 0.00 | 0.00 | 0.00 | 0.155175E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135672E+10 | 0.00 | 0.00 | 0.00 | 0.217034E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174880E+11 | 0.00 | 0.00 | 0.00 | 0.108830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124806E+10 | 0.00 | 0.00 | 0.00 | 55944370.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169576E+10 | 0.00 | 0.00 | 0.00 | 0.255935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.375740E+10 | 0.00 | 0.00 | 0.00 | 40815263.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.344785E+10 | 0.00 | 0.00 | 0.00 | 10813659.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.404748E+10 | 0.00 | 0.00 | 0.00 | 35572648.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.375782E+10 | 0.00 | 0.00 | 0.00 | 0.433577E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.389757E+10 | 0.00 | 0.00 | 0.00 | 0.335029E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.397377E+10 | 0.00 | 0.00 | 0.00 | 0.182544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.400779E+10 | 0.00 | 0.00 | 0.00 | 0.470565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.419116E+10 | 0.00 | 0.00 | 0.00 | 0.509406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.379481E+10 | 0.00 | 0.00 | 0.00 | 0.205939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.379611E+10 | 0.00 | 0.00 | 0.00 | 0.219556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.359776E+10 | 0.00 | 0.00 | 0.00 | 43269337.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.374767E+10 | 0.00 | 0.00 | 0.00 | 35133124.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.460172E+11 | 0.00 | 0.00 | 0.00 | 0.168143E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.344785E+10 | 0.00 | 0.00 | 0.00 | 10813659.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.419116E+10 | 0.00 | 0.00 | 0.00 | 0.509406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.308137E+09 | 7416625.30 | 0.00 | 2826063.99 | 0.00 | 24083321.97 | 0.229017E+10 | 0.00 | 0.46 |
February | 0.279053E+09 | 3686727.08 | 0.00 | 2638258.53 | 0.00 | 463365.81 | 0.245159E+10 | 0.00 | 0.46 |
March | 0.352682E+09 | 516113.15 | 0.00 | 3286894.18 | 0.00 | 8099406.49 | 0.280562E+10 | 0.00 | 0.49 |
April | 45313756.83 | 8712200.50 | 0.00 | 6399921.99 | 0.00 | 0.00 | 0.380982E+10 | 0.00 | 0.85 |
May | 28921014.36 | 8002859.15 | 0.00 | 7529442.73 | 0.00 | 0.00 | 0.440249E+10 | 0.00 | 0.93 |
June | 23401776.98 | 0.165867E+09 | 0.00 | 9238114.12 | 0.00 | 0.00 | 0.329686E+10 | 0.00 | 1.14 |
July | 1874245.59 | 0.648942E+09 | 0.00 | 9620617.94 | 0.00 | 0.00 | 0.162233E+10 | 0.00 | 0.99 |
August | 6174979.01 | 0.827920E+09 | 0.00 | 6553143.63 | 0.00 | 0.00 | 0.140725E+10 | 0.00 | 1.02 |
September | 23350095.34 | 0.196519E+09 | 0.00 | 7813102.63 | 0.00 | 0.00 | 0.290290E+10 | 0.00 | 1.04 |
October | 20578182.28 | 0.332632E+09 | 0.00 | 6189866.88 | 0.00 | 0.00 | 0.238480E+10 | 0.00 | 0.84 |
November | 0.110091E+09 | 1791598.39 | 0.00 | 4260092.07 | 0.00 | 0.00 | 0.328863E+10 | 0.00 | 0.63 |
December | 0.222873E+09 | 2216473.26 | 0.00 | 3516782.08 | 0.00 | 0.00 | 0.249284E+10 | 0.00 | 0.54 |
Annual Sum or Average | 0.142245E+10 | 0.220422E+10 | 0.00 | 69872300.77 | 0.00 | 32646094.27 | 0.331553E+11 | 0.00 | 0.78 |
Minimum of Months | 1874245.59 | 516113.15 | 0.00 | 2638258.53 | 0.00 | 0.00 | 0.140725E+10 | 0.00 | 0.46 |
Maximum of Months | 0.352682E+09 | 0.827920E+09 | 0.00 | 9620617.94 | 0.00 | 24083321.97 | 0.440249E+10 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.336503E+10 | 0.00 | 0.00 | 1250303.25 | 0.00 | 0.00 | 0.149238E+10 | 0.00 | 0.25 |
February | 0.351367E+10 | 0.00 | 0.00 | 1084464.64 | 0.00 | 0.00 | 0.133761E+10 | 0.00 | 0.23 |
March | 0.448498E+10 | 0.00 | 0.00 | 2032829.78 | 0.00 | 0.00 | 0.200054E+10 | 0.00 | 0.28 |
April | 0.143647E+10 | 941696.71 | 0.00 | 10703799.59 | 0.00 | 0.00 | 0.850009E+10 | 0.00 | 0.53 |
May | 0.120693E+10 | 0.00 | 0.00 | 12201424.17 | 0.00 | 0.00 | 0.987342E+10 | 0.00 | 0.57 |
June | 0.308766E+09 | 5953772.30 | 0.00 | 27627027.97 | 0.00 | 0.00 | 0.115437E+11 | 0.00 | 0.87 |
July | 25083958.00 | 0.585340E+09 | 0.00 | 43361943.96 | 0.00 | 0.00 | 0.905239E+10 | 0.00 | 1.00 |
August | 42854257.21 | 0.702618E+09 | 0.00 | 42204278.37 | 0.00 | 0.00 | 0.815988E+10 | 0.00 | 1.04 |
September | 0.238732E+09 | 0.144833E+09 | 0.00 | 19217418.91 | 0.00 | 0.00 | 0.108744E+11 | 0.00 | 0.79 |
October | 0.603175E+09 | 0.325368E+09 | 0.00 | 12470882.63 | 0.00 | 0.00 | 0.727849E+10 | 0.00 | 0.64 |
November | 0.259894E+10 | 0.00 | 0.00 | 2695084.50 | 0.00 | 0.00 | 0.331051E+10 | 0.00 | 0.29 |
December | 0.334167E+10 | 0.00 | 0.00 | 1100148.94 | 0.00 | 0.00 | 0.151934E+10 | 0.00 | 0.26 |
Annual Sum or Average | 0.211663E+11 | 0.176506E+10 | 0.00 | 0.175950E+09 | 0.00 | 0.00 | 0.749427E+11 | 0.00 | 0.56 |
Minimum of Months | 25083958.00 | 0.00 | 0.00 | 1084464.64 | 0.00 | 0.00 | 0.133761E+10 | 0.00 | 0.23 |
Maximum of Months | 0.448498E+10 | 0.702618E+09 | 0.00 | 43361943.96 | 0.00 | 0.00 | 0.115437E+11 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.587405E+12 | 0.302135E+11 | 0.00 | 0.747742E+10 | 0.126084E+10 |
February | 0.665940E+12 | 0.409181E+11 | 0.00 | 0.758242E+10 | 0.376405E+09 |
March | 0.935117E+12 | 0.495849E+11 | 0.00 | 0.966128E+10 | 0.870953E+09 |
April | 0.126146E+13 | 0.427827E+11 | 0.00 | 0.138937E+11 | 0.423418E+10 |
May | 0.132479E+13 | 0.534224E+11 | 0.00 | 0.157119E+11 | 0.392923E+10 |
June | 0.131923E+13 | 0.439858E+11 | 0.00 | 0.153369E+11 | 0.150126E+11 |
July | 0.144383E+13 | 0.470278E+11 | 0.00 | 0.964089E+10 | 0.336196E+11 |
August | 0.133969E+13 | 0.493448E+11 | 0.00 | 0.831293E+10 | 0.363379E+11 |
September | 0.104331E+13 | 0.370583E+11 | 0.00 | 0.141450E+11 | 0.161574E+11 |
October | 0.745064E+12 | 0.395493E+11 | 0.00 | 0.990365E+10 | 0.161976E+11 |
November | 0.628281E+12 | 0.380471E+11 | 0.00 | 0.931346E+10 | 0.932044E+09 |
December | 0.538792E+12 | 0.342400E+11 | 0.00 | 0.758102E+10 | 0.125208E+10 |
Annual Sum or Average | 0.118329E+14 | 0.506175E+12 | 0.00 | 0.128561E+12 | 0.130181E+12 |
Minimum of Months | 0.538792E+12 | 0.302135E+11 | 0.00 | 0.747742E+10 | 0.376405E+09 |
Maximum of Months | 0.144383E+13 | 0.534224E+11 | 0.00 | 0.157119E+11 | 0.363379E+11 |