Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2023-10-16 10:41:43
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1312.89 | 271.53 | 271.53 |
Net Site Energy | 1312.89 | 271.53 | 271.53 |
Total Source Energy | 4157.55 | 859.86 | 859.86 |
Net Source Energy | 4157.55 | 859.86 | 859.86 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 239.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 134.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 152.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 23.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1312.71 | 0.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 239.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 134.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 26.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 126.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 23.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 239.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 134.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 152.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 23.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 85.95 | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 271.49 | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 85.95 | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 271.49 | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1312.712 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1312.712 | 100.00 |
Total On-Site and Utility Electric Sources | 1312.712 | 100.00 |
Total Electricity End Uses | 1312.712 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 26.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3426.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Latitude [deg] | 25.82 |
Longitude [deg] | -80.3 |
Elevation [m] | 11.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.61 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7186 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 15.0695 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 9.6875 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 11.2890 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 11.2890 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.7186 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 15.0695 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 9.6875 | 46.45 | 2.5587 | |
Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 11.2890 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUL-14:00 | 15-DEC-07:10 | - | - | - | - | - | - | - | - | - | - | 24-JAN-12:30 |
Heating | 0.00 | 8979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 30889.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 11783.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1678.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 100657.35 | 8979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 8979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 30889.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 9477.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1678.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 759.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1974.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 425.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 482.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 74.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4157.36 | 0.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 157.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 99.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 859.82 | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 157.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 99.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 859.82 | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.36 |
ZONE2 FINE STORAGE DIRECT AIR | 4.60 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 2.73 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 2.73 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 111463.50 |
PSZ-OFFICE HEATING COIL | 32819.95 |
PSZ-FINE STORAGE HEATING COIL | 139448.19 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 111463.50 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.36 | 1.36 | 1.36 | 1.36 | 1.36 | 1.36 | 1.00 | 1.00 | 1.36 |
PSZ-FINE STORAGE | 4.60 | 4.60 | 4.60 | 4.60 | 4.60 | 4.60 | 1.00 | 1.00 | 4.60 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.36 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 4.60 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.36 | 1554.96 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 4.60 | 7922.82 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.36 | 1.36 | 1.36 | 1.36 | 27853.81 | 32819.95 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 4.60 | 4.60 | 4.60 | 4.60 | 114269.45 | 139448.19 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.36 | 0.681934 | 1.36 | 27853.81 | 14271.00 | 27853.81 | 0.768000 | 0.768000 |
PSZ-FINE STORAGE COOLING COIL | 4.60 | 2.30 | 4.60 | 114269.45 | 57134.72 | 114269.45 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.30 | 23.60 | 20.30 | 19.40 | 20.90 | 21.60 | 24.10 | 26.40 | 27.70 | 28.10 | 28.00 | 27.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Miami Intl Ap FL USA TMY3 WMO#=722020 | 25.82 | -80.30 | -5.00 | 11.00 | 101193 | 1.2027 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.49 | 8.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.719 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.792 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 15.069 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15.069 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 9.688 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 12.246 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2539.013 | 10.719 | 199.158 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2539.013 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 20997.932 | 15.069 | 699.931 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20997.932 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 31046.942 | 9.688 | 449.956 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 31046.942 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 982.6 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.7823 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 3 | 0.167 | 7.732 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 3 | 0.167 | 7.732 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1000E-02 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.179 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.36859539E-11 | 0.84954153E-14 | 0.47616952E-16 | 0.0000000 |
5 | 1 | -5.1234640 | 0.46000535E-01 | -0.53498711E-03 | 0.47618904E-11 |
6 | 0 | 987.76235 | 982.59289 | 982.63942 | |
7 | 4 | 0.72249793E-12 | -0.16720573E-15 | 0.22015083E-14 | 0.12409536E-15 |
8 | 3 | -0.36459118E-03 | 0.53555631E-06 | -0.52695411E-04 | 0.13865996E-12 |
9 | 2 | 1.6915239 | 0.11971291E-01 | 1.1039557 | -0.69896550E-04 |
10 | 1 | -7.1930661 | 0.31446443 | -16.864389 | 0.32415671 |
11 | 0 | 6.0306730 | 0.20232993 | 16.289252 | |
12 | 3 | -0.11556429E-04 | 0.42115602E-06 | -0.11737956E-05 | 0.71542051E-15 |
13 | 2 | 0.42692330 | 0.53556778E-01 | 0.17992628 | -0.21068281E-05 |
14 | 1 | -10.558915 | 3.4986983 | -9.7344214 | 0.71768033E-01 |
15 | 0 | 17.309178 | 3.6249194 | 16.731671 | |
16 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
17 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
18 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
19 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
20 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
21 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
22 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
23 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
24 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
25 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
26 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
27 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
28 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
29 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
30 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
31 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
32 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
33 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
34 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
35 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
36 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
37 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
38 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
39 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
40 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
41 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
42 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
43 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
44 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
45 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
46 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
47 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
48 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
49 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
50 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
51 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
52 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
53 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
54 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
55 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
56 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
57 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
58 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
59 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
60 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
61 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
62 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
63 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
64 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
65 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
66 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
67 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
68 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
69 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
70 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
71 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
72 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
73 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
74 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
75 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
76 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
77 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
78 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
79 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
80 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
81 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
82 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
83 | 3 | -0.11737956E-05 | 0.42115602E-06 | -0.11556429E-04 | 0.71542051E-15 |
84 | 2 | 0.17992628 | 0.53556778E-01 | 0.42692330 | -0.21068281E-05 |
85 | 1 | -9.7344214 | 3.4986983 | -10.558915 | 0.71768033E-01 |
86 | 0 | 16.731671 | 3.6249194 | 17.309178 | |
87 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
88 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
89 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
90 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.2_SHGC_SOUTH_0.25 | 34 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
2 | NONRESWINDOW_U_1.2_SHGC_NORTH_0.25 | 35 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
3 | NONRESWINDOW_U_1.2_SHGC_EAST_0.25 | 36 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
4 | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
5 | SKYLIGHT_U_1.02_SHGC_0.36 | 38 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.361 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.19502 | 0.25365 | 0.25365 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.849 | 0.366 | 0.255 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 0.153 | 6.473E-004 | 9.992E-004 | 0.546 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.780 | 5.598E-004 | 3.565E-004 | 0.951 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 3.433 | 1.071E-003 | 6.996E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 13794.88981 | 16553.86777 | 1.13656 | 1.36387 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 32.44067 | 1.71658E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 7476.73524 | 8972.08229 | 0.20994 | 0.25193 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 8.70000 | 6.99286E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 59694.37640 | 71633.25168 | 3.83469 | 4.60163 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.20000 | 1.71672E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 18239.80992 | 21887.77190 | 0.43181 | 0.51818 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 8.70000 | 6.99286E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.20000 | 1.71672E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 92886.25079 | 111463.50095 | 2.27227 | 2.72673 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8.70000 | 6.99286E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 20665.68 | 1.36387 | 1.36387 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 7303.35 | 0.25193 | 0.25193 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 85052.94 | 4.60163 | 4.60163 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 18827.09 | 0.51818 | 0.51818 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.36387 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.60163 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.72673 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 2.72673 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 111463.50264 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 111463.50095 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.36387 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.36387 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.36387 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.36387 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.36387 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.36387 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.60163 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.60163 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.60163 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 4.60163 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.60163 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 4.60163 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.36387 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 4.60163 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.36387 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.36387 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1554.96007 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.36387 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.36387 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.36387 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.36387 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.36387 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.68193 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.36387 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 27853.81000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 14270.99978 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 27853.81000 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76800 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76800 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27853.81000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32819.94717 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 32819.94717 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.60163 |
47 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.60163 |
49 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 7922.81794 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.60163 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.60163 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.60163 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.60163 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.60163 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.30082 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.60163 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 114269.45000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 57134.71567 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 114269.45000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 114269.45000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 139448.19246 |
64 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
66 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 139448.19246 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 26794.7 | 11.04 | 10.40 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 110692.6 | 10.53 | 9.92 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 4.5590702368E-002 | 3.9655854293E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.1493809191 | 0.2472017768 | Pass | Pass | 0.1126120116 | 0.5262433137 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 0.1611935747 | 0.1877718317 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 9389.85 | 2191.53 | 0.00 | -91.2 | 1074.33 | 12564.55 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00 | 8.70 | Wetbulb [C] | 3.80 | 340.00 |
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 6.70 | 25.30 | Wetbulb [C] | 4.50 | 140.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 65.00 | 29 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 38.00 | 14 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 391.00 | 83 | |||
Sep | 0.00 | 0 | |||
Oct | 225.00 | 40 | |||
Nov | 0.00 | 0 | |||
Dec | 5.00 | 10 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 3.584 | 7.732 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 3.584 | 7.732 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 3.584 | 7.732 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 7.226 | 982.639 | 3204.84 | 3170.23 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 2.711 | 7.732 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 2.711 | 7.732 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 6.813 | 0.251 | 0.252 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 6.813 | 0.251 | 0.252 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_1.2_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 6.813 | 0.251 | 0.252 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_1.2_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 6.813 | 0.251 | 0.252 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.27 | 6.141 | 0.449 | 0.450 | |||||||||||||||||
North Total or Average | 6.51 | 6.813 | 0.251 | 0.252 | |||||||||||||||||
Non-North Total or Average | 45.76 | 6.046 | 0.478 | 0.478 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.7186 | 236.88 | 2539.01 | LightsWired | LTG_SCH_OFFICE | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.86 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 15.0695 | 1393.41 | 20997.93 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 239.15 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 9.6875 | 3204.84 | 31046.94 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 353.60 |
Interior Lighting Total | 11.2890 | 4835.13 | 54583.89 | 623.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 8532.22 | AstronomicalClock | - | 83.82 | 83.82 | 134.25 | |
Exterior Lighting Total | 8532.22 | 134.25 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 27853.81 | 21391.73 | 6462.08 | 0.77 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 114269.45 | 80112.03 | 34157.42 | 0.70 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 26794.7 | 11.04 | 10.40 | ||||
PSZ-FINE STORAGE COOLING COIL | 110692.6 | 10.53 | 9.92 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 111463.50 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 32819.95 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 139448.19 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.73 | 253.34 | 92.91 | 1.00 | 3.41 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.36 | 1554.96 | 1140.11 | 1.00 | 1.30 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.59 | 1018.41 | 4.60 | 7922.82 | 1721.74 | 1.00 | 1.16 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 13794.89 | 16553.87 | 69.88 | 1.137 | 1.364 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 23.90 | 23.90 | 0.00876 | 32.44 | 0.01717 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 59694.38 | 71633.25 | 51.41 | 3.835 | 4.602 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 26.70 | 26.69 | 0.00932 | 33.20 | 0.01717 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 0.00 | 39.52 | 0.01725 | 33.20 | 0.01717 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 7476.74 | 8972.08 | 37.88 | 0.210 | 0.252 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00810 | 8.70 | 0.00699 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 18239.81 | 21887.77 | 15.71 | 0.432 | 0.518 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00745 | 8.70 | 0.00699 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 92886.25 | 111463.50 | 34.78 | 2.272 | 2.727 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00750 | 8.70 | 0.00699 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.36 | 1.36 | 0.25 | 0.25 | 1.3639 | 1.3639 | 1.3639 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 4.60 | 4.60 | 0.52 | 0.52 | 4.6016 | 4.6016 | 4.6016 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 111463.503 | 111463.503 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 111463.50 | 111463.50 | 2.726728 | 10.00 | 9.85 | 0.00749732 | 43.33 | 22.13 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 10.00 | 0.00749732 | 98.1509 | 111463.50 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 27853.810 | 21391.726 | 1.363870 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 27853.81 | 22540.98 | 1.363870 | 25.46 | 17.63 | 0.00939446 | 12.00 | 11.25 | 0.00800000 | 32.44 | 0.01716576 | 25.13 | 7.4996 | 23.90 | 0.00876439 | 47.3978 | 13794.89 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 32819.947 | 32819.947 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 32819.95 | 32819.95 | 1.363869 | 20.09 | 14.51 | 0.00801252 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 7.4996 | 21.10 | 0.00809519 | 51.9425 | 7476.74 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 114269.450 | 80112.026 | 4.601630 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 114269.45 | 88999.22 | 4.601630 | 28.69 | 19.21 | 0.01004177 | 12.00 | 11.25 | 0.00800000 | 33.20 | 0.01716721 | 25.32 | 9.2296 | 26.69 | 0.00931725 | 42.6292 | 59694.38 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 139448.192 | 139448.192 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 139448.19 | 139448.19 | 4.601631 | 14.93 | 11.87 | 0.00741007 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 9.2296 | 15.56 | 0.00745250 | 67.7741 | 18239.81 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 111463.503 | 111463.503 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 2.726728 | 3.27954230 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 111463.50 | 111463.50 | 1.0000 | 3.27954230 | 2.726728 | 10.00 | 9.85 | 0.00749732 | 28937.6 | 43.33 | 22.13 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 111463.50 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 10.00 | 0.00749732 | 10.00 | 0.00749732 | 98.1509 | 111463.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27853.810 | 21391.726 | 1.363870 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.3038 | 1004.8586 | 1.2027 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.363869 | 1.64037786 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | Sensible | 27853.81 | 22540.98 | 1.0000 | 1.64037955 | 1.363870 | 25.46 | 17.63 | 0.00939446 | 49527.4 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27853.81 | 32.44 | 0.01716576 | 25.13 | 0.10228463 | 7.4996 | 23.90 | 0.00876439 | 23.90 | 0.00876439 | 47.3978 | 13794.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32819.947 | 32819.947 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.363869 | 1.64037786 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 32819.95 | 32819.95 | 1.0000 | 1.64037786 | 1.363869 | 20.09 | 14.51 | 0.00801252 | 40524.5 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32819.95 | 8.70 | 0.00699286 | 8.70 | 0.10228463 | 7.4996 | 21.01 | 0.00809519 | 21.10 | 0.00809519 | 51.9425 | 7476.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 114269.450 | 80112.026 | 4.601630 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.5071 | 1004.8586 | 1.2027 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 4.601631 | 5.53456051 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 114269.45 | 88999.22 | 1.0000 | 5.53455957 | 4.601630 | 28.69 | 19.21 | 0.01004177 | 54480.3 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 114269.45 | 33.20 | 0.01716721 | 25.32 | 0.42471127 | 9.2296 | 26.69 | 0.00931725 | 26.69 | 0.00931725 | 42.6292 | 59694.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 139448.192 | 139448.192 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 4.601631 | 5.53456051 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 139448.19 | 139448.19 | 1.0000 | 5.53456051 | 4.601631 | 14.93 | 11.87 | 0.00741007 | 33735.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 139448.19 | 8.70 | 0.00699286 | 8.70 | 0.42471127 | 9.2296 | 15.56 | 0.00745250 | 15.56 | 0.00745250 | 67.7741 | 18239.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 3226.17 | 487.00 | 279.83 |
ZONE2 FINE STORAGE | 3493.33 | 3194.17 | 3078.00 |
ZONE3 BULK STORAGE | 3522.33 | 3518.00 | 3421.67 |
Facility | 3591.83 | 3543.33 | 3426.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 0.00 | 609.00 | 0.00 | 26.17 |
ZONE2 FINE STORAGE | 0.00 | 338.50 | 0.00 | 0.67 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 763.00 | 0.00 | 26.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.344 | 0.520 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.42 | 30.00 | 2953.02 | 0.490 | 0.450 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.204 | 0.000 | 2.255 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.42 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.42 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.53 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1403740.27 | 0.00 | 1403740.27 | 3081126.43 | 4484866.70 | 3225648.14 | 5379.80 | 3380.20 | 0.00 | 2128.62 |
ZONE2 FINE STORAGE | 5546728.83 | 0.00 | 5546728.83 | 11739418.50 | 17286147.33 | 13393694.68 | 5414.05 | 3345.95 | 0.00 | 1732.82 |
ZONE3 BULK STORAGE | 0.00 | 0.42E+09 | 0.42E+09 | 48387127.55 | 0.47E+09 | 30805497.77 | 5407.73 | 24.89 | 3327.38 | 4869.93 |
Total Facility | 6950469.11 | 0.42E+09 | 0.43E+09 | 63207672.48 | 0.49E+09 | 47424840.58 | 6584.15 | 3401.84 | 3327.38 | 4996.38 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.0946 | 0.0000 | 0.0946 | 0.1428 | 0.2374 | 0.1023 | 301.33 | 3334.67 | 0.00 |
ZONE2 FINE STORAGE | 0.3900 | 0.0000 | 0.3900 | 0.3583 | 0.7482 | 0.4247 | 303.00 | 3333.00 | 0.00 |
ZONE3 BULK STORAGE | 0.0000 | 20.8227 | 20.8227 | 1.9057 | 22.7284 | 0.9768 | 1460.94 | 12.52 | 2162.54 |
Total Facility | 0.4846 | 20.8227 | 21.3073 | 2.4068 | 23.7141 | 1.5038 | 1464.67 | 3335.50 | 2162.54 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2030623.93 | 0.00 | 2030623.93 | 3225648.14 | 5326.75 | 2.65 | 3430.60 | 2109.23 |
PSZ-FINE STORAGE | 8023792.24 | 0.00 | 8023792.24 | 13393694.68 | 5395.92 | 0.90 | 3363.19 | 1726.16 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1368 | 0.0000 | 0.1368 | 0.1023 | 299.08 | 0.11 | 3336.81 |
PSZ-FINE STORAGE | 0.5641 | 0.0000 | 0.5641 | 0.4247 | 303.00 | 0.00 | 3333.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 5609.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 5121.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1422 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6041 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 383 |
Defaulted Fields | 319 |
Fields with Defaults | 1020 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1312.71 | 6718.26 | 01-JAN-07:20 | 100657.35 | 28-JUL-15:00 |
Electricity:Building | 789.17 | 6235.26 | 01-JAN-00:10 | 58611.10 | 02-JAN-10:00 |
Electricity:Zone:ZONE1 OFFICE | 62.81 | 1030.77 | 01-JAN-00:10 | 3867.54 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 762.90 | 6235.26 | 01-JAN-00:10 | 56305.80 | 02-JAN-09:10 |
InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 487.21 | 3104.69 | 01-JAN-00:10 | 36895.31 | 02-JAN-10:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 152.32 | 0.00 | 01-JAN-00:10 | 11783.07 | 02-JAN-13:20 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 26.27 | 0.00 | 01-JAN-00:10 | 2305.29 | 07-FEB-15:00 |
Ventilation (simple):Fans:Electricity | 26.27 | 0.00 | 01-JAN-00:10 | 2305.29 | 07-FEB-15:00 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 26.27 | 0.00 | 01-JAN-00:10 | 2305.29 | 07-FEB-15:00 |
ElectricityPurchased:Facility | 1312.71 | 6718.26 | 01-JAN-07:20 | 100657.35 | 28-JUL-15:00 |
ElectricityPurchased:Plant | 1312.71 | 6718.26 | 01-JAN-07:20 | 100657.35 | 28-JUL-15:00 |
Cogeneration:ElectricityPurchased | 1312.71 | 6718.26 | 01-JAN-07:20 | 100657.35 | 28-JUL-15:00 |
General:Cogeneration:ElectricityPurchased | 1312.71 | 6718.26 | 01-JAN-07:20 | 100657.35 | 28-JUL-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1312.71 | 6718.26 | 01-JAN-07:20 | 100657.35 | 28-JUL-15:00 |
ElectricityNet:Plant | 1312.71 | 6718.26 | 01-JAN-07:20 | 100657.35 | 28-JUL-15:00 |
Cogeneration:ElectricityNet | 1312.71 | 6718.26 | 01-JAN-07:20 | 100657.35 | 28-JUL-15:00 |
General:Cogeneration:ElectricityNet | 1312.71 | 6718.26 | 01-JAN-07:20 | 100657.35 | 28-JUL-15:00 |
Electricity:HVAC | 365.78 | 0.00 | 01-JAN-00:10 | 42433.06 | 27-JUL-16:00 |
General:Fans:Electricity | 126.05 | 0.00 | 01-JAN-00:10 | 9477.78 | 02-JAN-08:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 239.73 | 0.00 | 01-JAN-00:10 | 32955.28 | 27-JUL-16:00 |
General:Cooling:Electricity | 239.73 | 0.00 | 01-JAN-00:10 | 32955.28 | 27-JUL-16:00 |
ExteriorLights:Electricity | 134.25 | 0.00 | 01-JAN-07:20 | 8532.22 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 134.25 | 0.00 | 01-JAN-07:20 | 8532.22 | 01-JAN-00:10 |
Electricity:Plant | 23.51 | 483.00 | 06-MAR-00:10 | 1746.72 | 19-JAN-12:40 |
WaterSystems:Electricity | 23.51 | 483.00 | 06-MAR-00:10 | 1746.72 | 19-JAN-12:40 |
Water Heater:WaterSystems:Electricity | 23.51 | 483.00 | 06-MAR-00:10 | 1746.72 | 19-JAN-12:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 0.17 | 0.00 | 01-JAN-00:10 | 8979.84 | 15-DEC-07:10 |
NaturalGas:HVAC | 0.17 | 0.00 | 01-JAN-00:10 | 8979.84 | 15-DEC-07:10 |
Heating:NaturalGas | 0.17 | 0.00 | 01-JAN-00:10 | 8979.84 | 15-DEC-07:10 |
General:Heating:NaturalGas | 0.17 | 0.00 | 01-JAN-00:10 | 8979.84 | 15-DEC-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 24-JAN-12:30 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 24-JAN-12:30 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 24-JAN-12:30 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 24-JAN-12:30 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 24-JAN-12:30 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 24-JAN-12:30 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 24-JAN-12:30 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 24-JAN-12:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1313.18 | 0.00 | 01-JAN-00:10 | 170519.17 | 27-JUL-16:00 |
EnergyTransfer:Building | 478.52 | 0.00 | 01-JAN-00:10 | 66218.88 | 29-JUL-15:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 118.46 | 0.00 | 01-JAN-00:10 | 15014.41 | 10-SEP-23:10 |
Heating:EnergyTransfer | 2.28 | 0.00 | 01-JAN-00:10 | 6214.72 | 15-DEC-07:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.24 | 0.00 | 01-JAN-00:10 | 5632.97 | 15-DEC-07:10 |
General:Heating:EnergyTransfer | 2.28 | 0.00 | 01-JAN-00:10 | 6214.72 | 15-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.24 | 0.00 | 01-JAN-00:10 | 5632.97 | 15-DEC-07:10 |
Cooling:EnergyTransfer | 476.24 | 0.00 | 01-JAN-00:10 | 66218.88 | 29-JUL-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 118.23 | 0.00 | 01-JAN-00:10 | 15014.41 | 10-SEP-23:10 |
General:Cooling:EnergyTransfer | 476.24 | 0.00 | 01-JAN-00:10 | 66218.88 | 29-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 118.23 | 0.00 | 01-JAN-00:10 | 15014.41 | 10-SEP-23:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 360.06 | 0.00 | 01-JAN-00:10 | 54556.08 | 29-JUL-15:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 2.04 | 0.00 | 01-JAN-00:10 | 5513.42 | 23-DEC-08:00 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 2.04 | 0.00 | 01-JAN-00:10 | 5513.42 | 23-DEC-08:00 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 358.02 | 0.00 | 01-JAN-00:10 | 54556.08 | 29-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 358.02 | 0.00 | 01-JAN-00:10 | 54556.08 | 29-JUL-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 834.66 | 0.00 | 01-JAN-00:10 | 104761.84 | 27-JUL-16:00 |
HeatingCoils:EnergyTransfer | 0.12 | 0.00 | 01-JAN-00:10 | 6010.21 | 15-DEC-07:10 |
CoolingCoils:EnergyTransfer | 834.55 | 0.00 | 01-JAN-00:10 | 104761.84 | 27-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 0.236 | -118.225 | 0.000 | 0.000 | 9.133 | 30.864 | 31.946 | 13.583 | 0.000 | 7.515 | 36.060 | 0.000 | -5.154 | 0.000 | -5.957 | -0.000 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 2.042 | -358.006 | 0.000 | 0.000 | 17.254 | 239.148 | 0.000 | 0.000 | 0.000 | 9.685 | 126.341 | 0.000 | 0.000 | 0.000 | -36.466 | -0.005 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 22.711 | 353.598 | 107.344 | 189.406 | 0.000 | 0.089 | 1613.716 | 0.000 | -54.841 | 0.000 | -2232.023 | -0.025 |
Total Facility | 0.000 | 0.000 | 2.278 | -476.231 | 0.000 | 0.000 | 49.098 | 623.610 | 139.290 | 202.989 | 0.000 | 17.290 | 1776.117 | 0.000 | -59.995 | 0.000 | -2274.445 | -0.030 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 27-FEB-00:02 | 0.00 | 0.00 | 0.00 | -24604.25 | 0.00 | 0.00 | 0.00 | 457.02 | 573.75 | 0.00 | 0.00 | 0.00 | 24633.69 | 0.00 | -747.36 | 0.00 | -312.86 | 0.00 |
ZONE2 FINE STORAGE | 09-APR-12:32 | 0.00 | 0.00 | 0.00 | -98286.68 | 0.00 | 0.00 | 0.00 | 2099.79 | 0.00 | 0.00 | 0.00 | 76.21 | 96110.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-APR-17:06 | 0.00 | 0.00 | 0.00 | -114064.65 | 0.00 | 0.00 | 0.00 | 5661.51 | 2623.78 | 11877.54 | 0.00 | 3774.05 | 212567.95 | 0.00 | 0.00 | 0.00 | -122440.19 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 04-FEB-06:02 | 0.00 | 0.00 | 27307.16 | 0.00 | 0.00 | 0.00 | 127.18 | 583.97 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1268.39 | 0.00 | -2146.27 | -25177.40 |
ZONE2 FINE STORAGE | 23-DEC-07:13 | 0.00 | 0.00 | 6105.58 | 0.00 | 0.00 | 0.00 | 408.44 | 12598.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1406.95 | -17705.83 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 04-FEB-06:02 | 0.00 | 0.00 | 27307.16 | 0.00 | 0.00 | 0.00 | 1318.19 | 5788.46 | 2623.78 | 0.00 | 0.00 | 0.00 | 9256.02 | 0.00 | -7955.03 | 0.00 | -38338.59 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3639 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.3639 | 0.0750 | 1.0000 | Not calculated | 0.1023 | 0.0750 | ||
PSZ-FINE STORAGE | 4.6016 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 4.6016 | 0.0923 | 1.0000 | Not calculated | 0.4247 | 0.0923 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3639 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.3639 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0750 | ||
PSZ-FINE STORAGE | 4.6016 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 4.6016 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.0923 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3639 | 1.3639 | 1.3639 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6016 | 4.6016 | 4.6016 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3639 | 1.3639 | 1.3639 | 1.3639 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 4.6016 | 4.6016 | 4.6016 | 4.6016 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3639 | 1.3639 | 1.3639 | No | 0.1023 | 0.4060 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6016 | 4.6016 | 4.6016 | No | 0.4247 | 0.8196 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3639 | 1.3639 | 1.3639 | 1.3639 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 4.6016 | 4.6016 | 4.6016 | 4.6016 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 26.83 |
Number of hours not met | 26.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.17 | 8979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 239.73 | 32955.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 623.61 | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 134.25 | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 26.27 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 126.05 | 9477.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 23.51 | 1746.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 1312.71 |
Natural Gas | 0.00 | 0.17 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 1312.89 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 128.97 |
Space Heating | 0.00 |
Space Cooling | 49.58 |
Fans (All) | 31.50 |
Service Water Heating | 4.86 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 271.49 |
Subtotal | 271.49 |
Natural Gas [MJ/m2] | |
Space Heating | 0.04 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.04 |
Subtotal | 0.04 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 47.50 |
Space Heating | 0.01 |
Space Cooling | 18.26 |
Fans (All) | 11.60 |
Service Water Heating | 1.79 |
Receptacle Equipment | 10.61 |
Miscellaneous | 10.23 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 3430. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 7685.67 | 948.50 | 125.83 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 2402.83 | 6357.17 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 2431.33 | 2949.67 | 2748.17 | 630.83 | 0.00 |
Min | 2402.83 | 948.50 | 0.00 | 0.00 | 0.00 |
Max | 7685.67 | 6357.17 | 2748.17 | 630.83 | 0.00 |
Average | 4173.28 | 3418.44 | 958.00 | 210.28 | 0.00 |
Sum | 12519.83 | 10255.33 | 2874.00 | 630.83 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 14185.00 | 68534.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 18285.00 | 68419.00 | 71887.33 | 32601.67 | 0.00 |
Min | 14185.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 33027.00 | 68534.00 | 71887.33 | 32601.67 | 0.00 |
Average | 21832.33 | 45651.00 | 23962.44 | 10867.22 | 0.00 |
Sum | 65497.00 | 136953.00 | 71887.33 | 32601.67 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 6762.83 | 1990.50 | 6.67 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 1501.67 | 7258.33 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 1436.50 | 5107.67 | 1740.33 | 475.50 | 0.00 |
Min | 1436.50 | 1990.50 | 0.00 | 0.00 | 0.00 |
Max | 6762.83 | 7258.33 | 1740.33 | 475.50 | 0.00 |
Average | 3233.67 | 4785.50 | 582.33 | 158.50 | 0.00 |
Sum | 9701.00 | 14356.50 | 1747.00 | 475.50 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 30738.00 | 2289.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 11891.50 | 70827.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 16232.17 | 94906.50 | 55136.00 | 24918.33 | 0.00 |
Min | 11891.50 | 2289.00 | 0.00 | 0.00 | 0.00 |
Max | 30738.00 | 94906.50 | 55136.00 | 24918.33 | 0.00 |
Average | 19620.56 | 56007.67 | 18378.67 | 8306.11 | 0.00 |
Sum | 58861.67 | 168023.00 | 55136.00 | 24918.33 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.516183E+10 | 19309.72 | 02-JAN-00:01 | 20.50 | 19.41 | 0.631296E+09 | 769.05 | 17-JAN-16:40 | 21.87 | 15.52 |
February | 0.582335E+10 | 24605.72 | 27-FEB-00:02 | 17.20 | 14.26 | 0.581609E+09 | 769.05 | 28-FEB-14:09 | 25.10 | 16.60 |
March | 0.780305E+10 | 21846.24 | 14-MAR-17:08 | 25.40 | 16.50 | 0.682327E+09 | 769.04 | 01-MAR-15:09 | 25.40 | 16.50 |
April | 0.992986E+10 | 23686.33 | 09-APR-23:01 | 22.70 | 18.68 | 0.634733E+09 | 769.08 | 10-APR-15:00 | 27.20 | 19.18 |
May | 0.122564E+11 | 22347.74 | 07-MAY-23:01 | 23.80 | 18.79 | 0.660206E+09 | 768.97 | 10-MAY-07:30 | 26.65 | 23.43 |
June | 0.127220E+11 | 20970.88 | 10-JUN-19:03 | 29.40 | 23.18 | 0.660251E+09 | 768.97 | 28-JUN-12:30 | 28.90 | 25.29 |
July | 0.131825E+11 | 21377.55 | 01-JUL-18:23 | 26.95 | 22.12 | 0.634877E+09 | 769.10 | 28-JUL-15:00 | 35.00 | 24.83 |
August | 0.135416E+11 | 20778.15 | 07-AUG-05:43 | 25.68 | 24.34 | 0.685659E+09 | 768.97 | 04-AUG-07:30 | 25.68 | 24.34 |
September | 0.122794E+11 | 20391.33 | 05-SEP-05:03 | 23.12 | 21.64 | 0.634860E+09 | 768.97 | 20-SEP-07:30 | 25.55 | 24.39 |
October | 0.112010E+11 | 21871.43 | 17-OCT-17:06 | 26.02 | 18.39 | 0.634815E+09 | 768.97 | 04-OCT-07:30 | 26.02 | 18.39 |
November | 0.846558E+10 | 20321.06 | 20-NOV-00:01 | 24.40 | 20.57 | 0.608612E+09 | 770.04 | 14-NOV-08:09 | 24.40 | 20.57 |
December | 0.586055E+10 | 24066.12 | 04-DEC-00:01 | 18.80 | 15.28 | 0.631833E+09 | 769.03 | 26-DEC-16:10 | 18.12 | 13.69 |
Annual Sum or Average | 0.118227E+12 | 0.768108E+10 | ||||||||
Minimum of Months | 0.516183E+10 | 19309.72 | 17.20 | 14.26 | 0.581609E+09 | 768.97 | 18.12 | 13.69 | ||
Maximum of Months | 0.135416E+11 | 24605.72 | 29.40 | 24.34 | 0.685659E+09 | 770.04 | 35.00 | 25.29 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.911244E+10 | 58106.20 | 01-JAN-13:23 | 26.65 | 21.70 | 0.180872E+10 | 2246.90 | 20-JAN-15:09 | 19.32 | 12.58 |
February | 0.121567E+11 | 93054.26 | 20-FEB-15:13 | 26.70 | 17.88 | 0.167334E+10 | 2247.06 | 27-FEB-15:20 | 26.10 | 16.96 |
March | 0.185122E+11 | 84948.92 | 26-MAR-15:32 | 26.33 | 21.52 | 0.196758E+10 | 2246.97 | 11-MAR-14:30 | 26.33 | 21.52 |
April | 0.296452E+11 | 98290.46 | 09-APR-12:32 | 27.93 | 19.11 | 0.185314E+10 | 2247.15 | 17-APR-15:00 | 31.70 | 20.29 |
May | 0.403685E+11 | 89521.51 | 02-MAY-17:06 | 28.12 | 19.68 | 0.192870E+10 | 2246.88 | 22-MAY-13:00 | 33.90 | 23.74 |
June | 0.445358E+11 | 85450.32 | 11-JUN-13:42 | 31.78 | 23.81 | 0.192885E+10 | 2246.90 | 26-JUN-13:09 | 30.37 | 24.69 |
July | 0.502513E+11 | 85983.62 | 01-JUL-18:23 | 26.95 | 22.12 | 0.185463E+10 | 2247.27 | 29-JUL-15:00 | 35.60 | 24.39 |
August | 0.456663E+11 | 83599.14 | 01-AUG-18:23 | 28.60 | 24.16 | 0.200299E+10 | 2246.88 | 26-AUG-14:00 | 31.10 | 24.60 |
September | 0.426642E+11 | 86586.52 | 03-SEP-15:53 | 26.10 | 22.55 | 0.185474E+10 | 2246.91 | 02-SEP-14:00 | 26.10 | 22.55 |
October | 0.336541E+11 | 88318.11 | 15-OCT-16:42 | 28.40 | 20.77 | 0.185448E+10 | 2246.89 | 03-OCT-12:20 | 28.40 | 20.77 |
November | 0.197828E+11 | 83743.58 | 19-NOV-13:43 | 26.70 | 21.27 | 0.177080E+10 | 2246.86 | 10-NOV-14:00 | 26.70 | 21.27 |
December | 0.116669E+11 | 86134.28 | 03-DEC-12:22 | 23.60 | 18.56 | 0.181301E+10 | 2246.99 | 13-DEC-15:00 | 21.10 | 15.13 |
Annual Sum or Average | 0.358016E+12 | 0.223110E+11 | ||||||||
Minimum of Months | 0.911244E+10 | 58106.20 | 23.60 | 17.88 | 0.167334E+10 | 2246.86 | 19.32 | 12.58 | ||
Maximum of Months | 0.502513E+11 | 98290.46 | 31.78 | 24.16 | 0.200299E+10 | 2247.27 | 35.60 | 24.69 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 | 19.26 | 0.444514E+10 | 7543.18 | 02-JAN-14:39 | 28.90 | 23.86 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 | 13.10 | 0.441283E+10 | 8191.99 | 11-FEB-14:20 | 29.03 | 24.09 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 17.32 | 13.44 | 0.534133E+10 | 8034.98 | 27-MAR-13:39 | 27.07 | 21.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 | 18.63 | 0.568261E+10 | 9097.65 | 13-APR-12:09 | 29.90 | 23.97 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 | 20.01 | 0.651435E+10 | 9097.65 | 01-MAY-12:09 | 30.68 | 22.80 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 | 24.42 | 0.665805E+10 | 9097.65 | 01-JUN-12:30 | 30.00 | 23.99 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 26.83 | 23.72 | 0.670217E+10 | 9097.65 | 01-JUL-10:00 | 31.10 | 24.60 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 | 25.82 | 0.691417E+10 | 9097.65 | 01-AUG-12:09 | 31.20 | 26.12 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 | 24.00 | 0.630655E+10 | 9097.65 | 01-SEP-12:09 | 30.68 | 24.82 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 27.93 | 23.96 | 0.585881E+10 | 9097.65 | 03-OCT-12:09 | 31.70 | 25.11 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 | 21.03 | 0.494991E+10 | 8064.70 | 03-NOV-13:20 | 29.40 | 24.25 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 24.10 | 21.22 | 0.450400E+10 | 7238.91 | 08-DEC-14:09 | 27.70 | 22.74 |
Annual Sum or Average | 0.00 | 0.682899E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 16.65 | 13.10 | 0.441283E+10 | 7238.91 | 27.07 | 21.97 | ||
Maximum of Months | 0.00 | 0.00 | 28.60 | 25.82 | 0.691417E+10 | 9097.65 | 31.70 | 26.12 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 56593378.30 | 4378.44 | 25-JAN-07:10 | 9.50 |
February | 53189547.24 | 27307.23 | 04-FEB-06:02 | 5.50 |
March | 50435851.76 | 5525.21 | 16-MAR-06:10 | 6.70 |
April | 2222461.29 | 922.68 | 19-APR-06:15 | 15.77 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 27.93 |
November | 11485018.29 | 2362.58 | 13-NOV-07:15 | 12.40 |
December | 61886302.47 | 5632.97 | 15-DEC-07:10 | 7.88 |
Annual Sum or Average | 0.235813E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.50 | |
Maximum of Months | 61886302.47 | 27307.23 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.521314E+09 | 5854.63 | 06-JAN-07:13 | 22.97 |
February | 0.482582E+09 | 5905.04 | 02-FEB-07:13 | 22.97 |
March | 0.280244E+09 | 5195.48 | 23-MAR-06:30 | 21.70 |
April | 38520442.06 | 4422.44 | 21-APR-06:05 | 22.30 |
May | 5864489.19 | 4657.42 | 01-MAY-06:13 | 20.97 |
June | 236646.22 | 612.11 | 01-JUN-06:05 | 24.60 |
July | 90022.15 | 300.07 | 27-JUL-06:05 | 25.68 |
August | 110388.54 | 367.96 | 24-AUG-06:05 | 25.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 1801807.29 | 3865.30 | 28-OCT-06:05 | 21.70 |
November | 0.135128E+09 | 5232.71 | 28-NOV-07:13 | 20.77 |
December | 0.576419E+09 | 6105.49 | 23-DEC-07:13 | 22.97 |
Annual Sum or Average | 0.204231E+10 | |||
Minimum of Months | 0.00 | 0.00 | 20.77 | |
Maximum of Months | 0.576419E+09 | 6105.49 | 27.05 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.258145E+10 | 1955.04 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.235440E+10 | 1955.04 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.269003E+10 | 1955.04 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.254196E+10 | 1955.04 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.263574E+10 | 1955.04 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.259625E+10 | 1955.04 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.258145E+10 | 1955.04 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.269003E+10 | 1955.04 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.254196E+10 | 1955.04 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.258145E+10 | 1955.04 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.248766E+10 | 1955.04 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.258145E+10 | 1955.04 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.308638E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.235440E+10 | 1955.04 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.269003E+10 | 1955.04 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.198922E+11 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.182065E+11 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.210336E+11 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.197108E+11 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.204629E+11 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.202815E+11 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.198922E+11 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.210336E+11 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.197108E+11 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.198922E+11 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.191400E+11 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.198922E+11 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.239148E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.182065E+11 | 17848.24 | 0.00 | 0.00 | |
Maximum of Months | 0.210336E+11 | 17848.24 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.294120E+11 | 26389.90 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.269196E+11 | 26389.90 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.310997E+11 | 26389.90 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.291438E+11 | 26389.90 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.302559E+11 | 26389.90 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.299876E+11 | 26389.90 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.294120E+11 | 26389.90 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.310997E+11 | 26389.90 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.291438E+11 | 26389.90 | 01-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.294120E+11 | 26389.90 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.282999E+11 | 26389.90 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.294120E+11 | 26389.90 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.353598E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.269196E+11 | 26389.90 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.310997E+11 | 26389.90 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67793029.39 | 0.121274E+10 |
February | 0.127628E+10 | 0.235440E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146909E+09 | 0.107192E+10 |
March | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180936E+09 | 0.110033E+10 |
April | 0.138726E+10 | 0.254196E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391073E+09 | 0.396815E+09 |
May | 0.144276E+10 | 0.263574E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.986257E+09 | 0.112003E+09 |
June | 0.144276E+10 | 0.259625E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112212E+10 | 46833619.42 |
July | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108627E+10 | 44440829.83 |
August | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125718E+10 | 31501652.50 |
September | 0.138726E+10 | 0.254196E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101558E+10 | 32945996.94 |
October | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758235E+09 | 0.104430E+09 |
November | 0.133177E+10 | 0.248766E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420698E+09 | 0.588107E+09 |
December | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82340999.78 | 0.121467E+10 |
Annual Sum or Average | 0.168137E+11 | 0.308638E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.751539E+10 | 0.595674E+10 |
Minimum of Months | 0.127628E+10 | 0.235440E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67793029.39 | 31501652.50 |
Maximum of Months | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125718E+10 | 0.121467E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12416297.00 | 0.533029E+10 |
February | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28324779.16 | 0.655002E+10 |
March | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66787052.45 | 0.699760E+10 |
April | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309328E+09 | 0.371337E+10 |
May | 0.339505E+10 | 0.204629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121418E+10 | 0.170981E+10 |
June | 0.339505E+10 | 0.202815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163263E+10 | 0.486274E+09 |
July | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173398E+10 | 0.360074E+09 |
August | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193349E+10 | 0.347267E+09 |
September | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174193E+10 | 0.524502E+09 |
October | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839000E+09 | 0.114402E+10 |
November | 0.313390E+10 | 0.191400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141318E+09 | 0.369610E+10 |
December | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32046442.80 | 0.560654E+10 |
Annual Sum or Average | 0.395654E+11 | 0.239148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.968544E+10 | 0.364659E+11 |
Minimum of Months | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12416297.00 | 0.347267E+09 |
Maximum of Months | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193349E+10 | 0.699760E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6401829.43 | 0.193254E+11 |
February | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13349916.17 | 0.258999E+11 |
March | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 252838.99 | 0.334455E+11 |
April | 0.750829E+10 | 0.291438E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259143E+11 |
May | 0.780862E+10 | 0.302559E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244555E+11 |
June | 0.780862E+10 | 0.299876E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161880E+11 |
July | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135745E+11 |
August | 0.810895E+10 | 0.310997E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 322408.73 | 0.137667E+11 |
September | 0.750829E+10 | 0.291438E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130567E+11 |
October | 0.750829E+10 | 0.294120E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 224286.45 | 0.134060E+11 |
November | 0.720796E+10 | 0.282999E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24082057.22 | 0.174447E+11 |
December | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17086946.49 | 0.212375E+11 |
Annual Sum or Average | 0.910005E+11 | 0.353598E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 61720283.48 | 0.237715E+12 |
Minimum of Months | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130567E+11 |
Maximum of Months | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24082057.22 | 0.334455E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1955.04 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1257.16 | 02-JAN-12:10 | 5687.32 | 25-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 1955.04 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1668.38 | 02-FEB-13:00 | 6086.32 | 03-FEB-08:00 |
March | 1680.92 | 01-MAR-08:09 | 1955.04 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2893.27 | 13-MAR-16:55 | 7624.26 | 16-MAR-06:10 |
April | 1680.92 | 01-APR-07:10 | 1955.04 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3470.53 | 17-APR-17:00 | 3620.70 | 19-APR-06:05 |
May | 1680.92 | 01-MAY-07:10 | 1955.04 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4708.39 | 22-MAY-16:10 | 1179.72 | 01-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 1955.04 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3456.37 | 08-JUN-16:10 | 697.41 | 18-JUN-20:00 |
July | 1680.92 | 01-JUL-07:10 | 1955.04 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5222.39 | 27-JUL-16:10 | 657.56 | 02-JUL-15:15 |
August | 1680.92 | 01-AUG-07:10 | 1955.04 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3998.84 | 16-AUG-16:10 | 653.63 | 28-AUG-12:00 |
September | 1680.92 | 01-SEP-07:10 | 1955.04 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4028.59 | 18-SEP-16:10 | 636.62 | 05-SEP-06:10 |
October | 1680.92 | 02-OCT-07:10 | 1955.04 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3768.55 | 03-OCT-16:10 | 979.16 | 31-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 1955.04 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2144.00 | 03-NOV-16:10 | 5248.92 | 27-NOV-07:05 |
December | 1680.92 | 01-DEC-08:09 | 1955.04 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1276.00 | 08-DEC-13:00 | 6775.76 | 15-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1257.16 | 636.62 | |||||
Maximum of Months | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 5222.39 | 7624.26 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 758.22 | 07-JAN-13:00 | 13112.22 | 24-JAN-09:00 |
February | 3955.50 | 01-FEB-08:09 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 914.90 | 02-FEB-14:00 | 15364.94 | 03-FEB-09:00 |
March | 3955.50 | 01-MAR-08:09 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3133.44 | 13-MAR-16:55 | 15480.36 | 15-MAR-08:00 |
April | 3955.50 | 01-APR-07:10 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5108.41 | 15-APR-17:00 | 7733.46 | 18-APR-07:55 |
May | 3955.50 | 01-MAY-07:10 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8263.23 | 22-MAY-15:20 | 5573.26 | 10-MAY-15:07 |
June | 3955.50 | 01-JUN-07:10 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4314.71 | 08-JUN-16:00 | 3447.45 | 18-JUN-20:00 |
July | 3955.50 | 01-JUL-07:10 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7152.52 | 27-JUL-16:00 | 3036.40 | 02-JUL-15:40 |
August | 3955.50 | 01-AUG-07:10 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5526.79 | 16-AUG-16:00 | 4196.24 | 14-AUG-02:53 |
September | 3955.50 | 01-SEP-07:10 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5522.12 | 18-SEP-16:00 | 2507.23 | 19-SEP-23:00 |
October | 3955.50 | 02-OCT-07:10 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5442.60 | 03-OCT-15:10 | 4084.31 | 16-OCT-07:00 |
November | 3955.50 | 01-NOV-07:10 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1519.94 | 03-NOV-16:00 | 12663.95 | 11-NOV-09:00 |
December | 3955.50 | 01-DEC-08:09 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2202.05 | 10-DEC-14:25 | 12939.95 | 27-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 758.22 | 2507.23 | ||||
Maximum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8263.23 | 15480.36 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 26389.90 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 872.76 | 13-JAN-07:25 | 58990.09 | 24-JAN-13:50 |
February | 9097.65 | 01-FEB-08:09 | 26389.90 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 857.80 | 01-FEB-05:40 | 58850.56 | 03-FEB-15:00 |
March | 9097.65 | 01-MAR-08:09 | 26389.90 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 208.76 | 19-MAR-04:00 | 68522.47 | 15-MAR-12:08 |
April | 9097.65 | 01-APR-07:10 | 26389.90 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 39106.26 | 18-APR-08:50 |
May | 9097.65 | 01-MAY-07:10 | 26389.90 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 38025.21 | 10-MAY-14:53 |
June | 9097.65 | 01-JUN-07:10 | 26389.90 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 28561.39 | 17-JUN-14:00 |
July | 9097.65 | 01-JUL-07:10 | 26389.90 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 21680.66 | 30-JUL-15:53 |
August | 9097.65 | 01-AUG-07:10 | 26389.90 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 394.42 | 01-AUG-09:50 | 23584.87 | 11-AUG-11:00 |
September | 9097.65 | 01-SEP-07:10 | 26389.90 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 22279.88 | 16-SEP-13:00 |
October | 9097.65 | 02-OCT-07:10 | 26389.90 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 655.37 | 04-OCT-10:53 | 23418.78 | 16-OCT-13:50 |
November | 9097.65 | 01-NOV-07:10 | 26389.90 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1269.91 | 29-NOV-06:05 | 42372.21 | 11-NOV-09:00 |
December | 9097.65 | 01-DEC-08:09 | 26389.90 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1508.28 | 23-DEC-05:00 | 53179.37 | 26-DEC-11:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21680.66 | |||||
Maximum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 1508.28 | 68522.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19309.72 | 02-JAN-00:01 | 0.00 | 4570.22 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24605.72 | 27-FEB-00:02 | 0.00 | 2742.13 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.86 |
March | 21846.24 | 14-MAR-17:08 | 0.00 | 1828.09 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.39 | 0.00 |
April | 23686.33 | 09-APR-23:01 | 0.00 | 4570.22 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.41 |
May | 22347.74 | 07-MAY-23:01 | 0.00 | 4570.22 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395.89 |
June | 20970.88 | 10-JUN-19:03 | 0.00 | 1828.09 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.12 | 0.00 |
July | 21377.55 | 01-JUL-18:23 | 0.00 | 1828.09 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.69 | 0.00 |
August | 20778.15 | 07-AUG-05:43 | 554.70 | 1751.92 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 143.10 | 0.00 |
September | 20391.33 | 05-SEP-05:03 | 554.70 | 1751.92 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.23 |
October | 21871.43 | 17-OCT-17:06 | 0.00 | 2285.11 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 337.95 | 0.00 |
November | 20321.06 | 20-NOV-00:01 | 0.00 | 4570.22 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.76 |
December | 24066.12 | 04-DEC-00:01 | 0.00 | 3656.18 | 4590.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19309.72 | 0.00 | 1751.92 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24605.72 | 554.70 | 4570.22 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 337.95 | 395.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 58106.20 | 01-JAN-13:23 | 0.00 | 6299.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.65 |
February | 93054.26 | 20-FEB-15:13 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.80 |
March | 84948.92 | 26-MAR-15:32 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 637.50 |
April | 98290.46 | 09-APR-12:32 | 0.00 | 10498.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.21 | 0.00 |
May | 89521.51 | 02-MAY-17:06 | 0.00 | 10498.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 752.28 | 0.00 |
June | 85450.32 | 11-JUN-13:42 | 0.00 | 12598.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2419.59 | 0.00 |
July | 85983.62 | 01-JUL-18:23 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.77 |
August | 83599.14 | 01-AUG-18:23 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 614.92 | 0.00 |
September | 86586.52 | 03-SEP-15:53 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.05 |
October | 88318.11 | 15-OCT-16:42 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 709.39 | 0.00 |
November | 83743.58 | 19-NOV-13:43 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.90 |
December | 86134.28 | 03-DEC-12:22 | 0.00 | 10498.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1251.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 58106.20 | 0.00 | 6299.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 98290.46 | 0.00 | 12598.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2419.59 | 1251.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4212.74 |
March | 0.00 | 01-MAR-00:05 | 0.00 | 6209.39 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5080.60 |
April | 0.00 | 01-APR-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7118.99 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4543.57 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3163.47 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 6209.39 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1519.62 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1008.07 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3247.48 |
October | 0.00 | 01-OCT-00:05 | 0.00 | 6209.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1557.96 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4979.90 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 6209.39 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1517.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 6209.39 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7118.99 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.956101E+11 | 88968.96 | 02-JAN-14:50 | 31358952.32 | 6882.88 | 25-JAN-07:10 |
February | 0.896057E+11 | 91316.94 | 11-FEB-14:30 | 38308994.75 | 7524.54 | 04-FEB-06:10 |
March | 0.105169E+12 | 91292.55 | 27-MAR-14:00 | 50679900.53 | 8499.15 | 16-MAR-06:10 |
April | 0.105764E+12 | 94978.91 | 14-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.117495E+12 | 97334.66 | 31-MAY-14:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.120702E+12 | 97335.39 | 09-JUN-14:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.122690E+12 | 100657.35 | 28-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.125899E+12 | 99340.41 | 23-AUG-13:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.118342E+12 | 98993.31 | 20-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.113110E+12 | 96707.36 | 03-OCT-14:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.100835E+12 | 92282.27 | 03-NOV-13:30 | 5656798.44 | 1978.99 | 13-NOV-07:19 |
December | 0.974895E+11 | 89121.18 | 08-DEC-13:00 | 48604884.43 | 8979.84 | 15-DEC-07:10 |
Annual Sum or Average | 0.131271E+13 | 0.174610E+09 | ||||
Minimum of Months | 0.896057E+11 | 88968.96 | 0.00 | 0.00 | ||
Maximum of Months | 0.125899E+12 | 100657.35 | 50679900.53 | 8979.84 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.518856E+11 | 0.128086E+11 | 0.115358E+11 | 0.00 | 0.100468E+11 | 0.00 | 0.00 | 0.729506E+10 | 0.00 | 0.00 | 0.00 | 0.203831E+10 | 0.00 |
February | 0.474804E+11 | 0.110526E+11 | 0.105871E+11 | 0.00 | 0.972552E+10 | 0.00 | 0.00 | 0.891458E+10 | 0.00 | 0.00 | 0.00 | 0.184539E+10 | 0.00 |
March | 0.548234E+11 | 0.115390E+11 | 0.123431E+11 | 0.00 | 0.118075E+11 | 0.00 | 0.00 | 0.125981E+11 | 0.00 | 0.00 | 0.00 | 0.205779E+10 | 0.00 |
April | 0.513965E+11 | 0.104844E+11 | 0.114862E+11 | 0.00 | 0.122576E+11 | 0.00 | 0.00 | 0.182022E+11 | 0.00 | 0.00 | 0.00 | 0.193760E+10 | 0.00 |
May | 0.533545E+11 | 0.102182E+11 | 0.119357E+11 | 0.00 | 0.140025E+11 | 0.00 | 0.00 | 0.260069E+11 | 0.00 | 0.00 | 0.00 | 0.197750E+10 | 0.00 |
June | 0.528654E+11 | 0.960899E+10 | 0.118862E+11 | 0.00 | 0.151703E+11 | 0.00 | 0.00 | 0.292648E+11 | 0.00 | 0.00 | 0.00 | 0.190667E+10 | 0.00 |
July | 0.518856E+11 | 0.100185E+11 | 0.115358E+11 | 0.00 | 0.154427E+11 | 0.00 | 0.00 | 0.318824E+11 | 0.00 | 0.00 | 0.00 | 0.192539E+10 | 0.00 |
August | 0.548234E+11 | 0.105612E+11 | 0.123357E+11 | 0.00 | 0.153705E+11 | 0.00 | 0.00 | 0.308378E+11 | 0.00 | 0.00 | 0.00 | 0.197008E+10 | 0.00 |
September | 0.513965E+11 | 0.108786E+11 | 0.114788E+11 | 0.00 | 0.145484E+11 | 0.00 | 0.00 | 0.281350E+11 | 0.00 | 0.00 | 0.00 | 0.190429E+10 | 0.00 |
October | 0.518856E+11 | 0.119485E+11 | 0.115432E+11 | 0.00 | 0.128191E+11 | 0.00 | 0.00 | 0.229352E+11 | 0.00 | 0.00 | 0.00 | 0.197809E+10 | 0.00 |
November | 0.499276E+11 | 0.121942E+11 | 0.110862E+11 | 0.00 | 0.108368E+11 | 0.00 | 0.00 | 0.148509E+11 | 0.00 | 0.00 | 0.00 | 0.193921E+10 | 0.00 |
December | 0.518856E+11 | 0.129417E+11 | 0.115358E+11 | 0.00 | 0.102933E+11 | 0.00 | 0.00 | 0.880397E+10 | 0.00 | 0.00 | 0.00 | 0.202922E+10 | 0.00 |
Annual Sum or Average | 0.623610E+12 | 0.134254E+12 | 0.139290E+12 | 0.00 | 0.152321E+12 | 0.00 | 0.00 | 0.239727E+12 | 0.00 | 0.00 | 0.00 | 0.235095E+11 | 0.00 |
Minimum of Months | 0.474804E+11 | 0.960899E+10 | 0.105871E+11 | 0.00 | 0.972552E+10 | 0.00 | 0.00 | 0.729506E+10 | 0.00 | 0.00 | 0.00 | 0.184539E+10 | 0.00 |
Maximum of Months | 0.548234E+11 | 0.129417E+11 | 0.123431E+11 | 0.00 | 0.154427E+11 | 0.00 | 0.00 | 0.318824E+11 | 0.00 | 0.00 | 0.00 | 0.205779E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 31358952.32 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 38308994.75 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 50679900.53 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 5656798.44 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 48604884.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.174610E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 50679900.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 46193.18 | 02-JAN-09:09 | 8532.22 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 11783.07 | 02-JAN-13:20 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 46193.18 | 01-FEB-09:09 | 8532.22 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 11783.07 | 07-FEB-12:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 46193.18 | 01-MAR-09:09 | 8532.22 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 11783.07 | 02-MAR-09:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 46193.18 | 01-APR-08:09 | 8532.22 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 11783.07 | 01-APR-12:39 | 0.00 | 0.00 | 01-APR-00:10 |
May | 46193.18 | 01-MAY-08:09 | 8532.22 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 11783.07 | 01-MAY-09:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 46193.18 | 01-JUN-08:09 | 8532.22 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 11783.07 | 03-JUN-09:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 46193.18 | 01-JUL-08:09 | 8532.22 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 11783.07 | 03-JUL-09:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 46193.18 | 01-AUG-08:09 | 8532.22 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 11783.07 | 01-AUG-06:40 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 46193.18 | 01-SEP-08:09 | 8532.22 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 11783.07 | 01-SEP-07:19 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 46193.18 | 02-OCT-08:09 | 8532.22 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 11783.07 | 02-OCT-11:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 46193.18 | 01-NOV-08:09 | 8532.22 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 11783.07 | 01-NOV-11:50 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 46193.18 | 01-DEC-09:09 | 8532.22 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 11783.07 | 02-DEC-10:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 46193.18 | 8532.22 | 10112.62 | 0.00 | 11783.07 | 0.00 | 0.00 | |||||
Maximum of Months | 46193.18 | 8532.22 | 10112.62 | 0.00 | 11783.07 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 19247.13 | 02-JAN-14:39 | 0.00 | 0.00 | 0.00 | 1746.72 | 19-JAN-12:39 | 0.00 |
February | 21539.79 | 11-FEB-14:30 | 0.00 | 0.00 | 0.00 | 1745.89 | 01-FEB-12:39 | 0.00 |
March | 21498.06 | 27-MAR-14:00 | 0.00 | 0.00 | 0.00 | 1740.71 | 01-MAR-12:09 | 0.00 |
April | 26776.33 | 15-APR-15:00 | 0.00 | 0.00 | 0.00 | 1730.36 | 01-APR-11:00 | 0.00 |
May | 29243.32 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 | 1718.71 | 01-MAY-11:20 | 0.00 |
June | 29836.04 | 08-JUN-15:00 | 0.00 | 0.00 | 0.00 | 1708.11 | 01-JUN-11:00 | 0.00 |
July | 32955.28 | 27-JUL-15:00 | 0.00 | 0.00 | 0.00 | 1701.83 | 01-JUL-11:20 | 0.00 |
August | 30666.48 | 16-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1706.29 | 31-AUG-11:30 | 0.00 |
September | 29660.51 | 18-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1716.10 | 30-SEP-11:39 | 0.00 |
October | 27086.76 | 03-OCT-15:09 | 0.00 | 0.00 | 0.00 | 1728.07 | 31-OCT-11:50 | 0.00 |
November | 22520.11 | 03-NOV-13:39 | 0.00 | 0.00 | 0.00 | 1738.70 | 30-NOV-12:39 | 0.00 |
December | 19319.40 | 08-DEC-13:00 | 0.00 | 0.00 | 0.00 | 1745.29 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 19247.13 | 0.00 | 0.00 | 0.00 | 1701.83 | 0.00 | ||
Maximum of Months | 32955.28 | 0.00 | 0.00 | 0.00 | 1746.72 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 88968.96 | 02-JAN-14:50 | 46193.18 | 10112.62 | 0.00 | 0.00 | 11783.07 | 0.00 | 0.00 | 19241.31 | 0.00 |
February | 91316.94 | 11-FEB-14:30 | 46193.18 | 10112.62 | 0.00 | 0.00 | 11783.07 | 0.00 | 0.00 | 21539.79 | 0.00 |
March | 91292.55 | 27-MAR-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 11783.07 | 0.00 | 0.00 | 21498.06 | 0.00 |
April | 94978.91 | 14-APR-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 11783.07 | 0.00 | 0.00 | 25190.33 | 0.00 |
May | 97334.66 | 31-MAY-14:30 | 46193.18 | 10112.62 | 0.00 | 0.00 | 11783.07 | 0.00 | 0.00 | 27560.52 | 0.00 |
June | 97335.39 | 09-JUN-14:50 | 46193.18 | 10112.62 | 0.00 | 0.00 | 11783.07 | 0.00 | 0.00 | 27563.65 | 0.00 |
July | 100657.35 | 28-JUL-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 11783.07 | 0.00 | 0.00 | 30889.52 | 0.00 |
August | 99340.41 | 23-AUG-13:30 | 46193.18 | 10112.62 | 0.00 | 0.00 | 11783.07 | 0.00 | 0.00 | 29591.59 | 0.00 |
September | 98993.31 | 20-SEP-13:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 11783.07 | 0.00 | 0.00 | 29238.73 | 0.00 |
October | 96707.36 | 03-OCT-14:30 | 46193.18 | 10112.62 | 0.00 | 0.00 | 11783.07 | 0.00 | 0.00 | 26926.15 | 0.00 |
November | 92282.27 | 03-NOV-13:30 | 46193.18 | 10112.62 | 0.00 | 0.00 | 11783.07 | 0.00 | 0.00 | 22515.62 | 0.00 |
December | 89121.18 | 08-DEC-13:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 11783.07 | 0.00 | 0.00 | 19319.40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 88968.96 | 46193.18 | 10112.62 | 0.00 | 0.00 | 11783.07 | 0.00 | 0.00 | 19241.31 | 0.00 | |
Maximum of Months | 100657.35 | 46193.18 | 10112.62 | 0.00 | 0.00 | 11783.07 | 0.00 | 0.00 | 30889.52 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 6882.88 | 25-JAN-07:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 7524.54 | 04-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 8499.15 | 16-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 1978.99 | 13-NOV-07:19 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 8979.84 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 8979.84 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 24.52 | 0.00 | 24.52 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 24.51 | 0.67 | 24.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 24.59 | 0.17 | 24.59 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 43.83 | 24.67 | 0.83 | 24.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 76.00 | 24.74 | 3.33 | 24.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 83.50 | 24.78 | 4.33 | 24.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 79.83 | 24.81 | 4.17 | 24.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 86.00 | 24.79 | 4.33 | 24.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 79.67 | 24.82 | 4.00 | 24.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 73.50 | 24.71 | 3.00 | 24.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 38.17 | 24.58 | 1.00 | 24.58 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 24.54 | 0.33 | 24.54 |
Annual Sum or Average | 0.00 | 0.00 | 609.00 | 24.74 | 26.17 | 24.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 24.51 | 0.00 | 24.51 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 86.00 | 24.82 | 4.33 | 24.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.37 | 0.00 | 27.37 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.63 | 0.00 | 27.63 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.53 | 0.00 | 27.53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 27.72 | 0.00 | 27.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 36.17 | 27.67 | 0.17 | 27.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 53.67 | 27.63 | 0.00 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 64.17 | 27.76 | 0.00 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 53.33 | 27.64 | 0.17 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 55.67 | 27.65 | 0.00 | 27.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 27.65 | 0.33 | 27.64 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.52 | 0.00 | 27.52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.58 | 0.00 | 27.58 |
Annual Sum or Average | 0.00 | 0.00 | 338.50 | 27.66 | 0.67 | 27.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.37 | 0.00 | 27.37 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 64.17 | 27.76 | 0.33 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 68.33 | 23.25 | 179.83 | 23.73 | 2.83 | 23.73 |
February | 52.00 | 23.38 | 205.33 | 23.78 | 12.83 | 23.76 |
March | 62.00 | 23.31 | 243.00 | 23.78 | 14.83 | 23.79 |
April | 4.00 | 23.82 | 289.33 | 23.91 | 3.00 | 23.91 |
May | 23.67 | 23.91 | 312.00 | 23.91 | 23.67 | 23.91 |
June | 41.33 | 23.90 | 312.00 | 23.91 | 41.33 | 23.91 |
July | 34.17 | 23.90 | 300.00 | 23.91 | 34.17 | 23.91 |
August | 45.67 | 23.90 | 324.00 | 23.91 | 45.67 | 23.91 |
September | 34.17 | 23.90 | 300.00 | 23.91 | 34.17 | 23.91 |
October | 33.00 | 23.91 | 299.83 | 23.91 | 33.00 | 23.91 |
November | 34.83 | 23.61 | 265.50 | 23.87 | 24.83 | 23.88 |
December | 53.83 | 23.23 | 195.33 | 23.76 | 9.50 | 23.76 |
Annual Sum or Average | 487.00 | 23.59 | 3226.17 | 23.86 | 279.83 | 23.87 |
Minimum of Months | 4.00 | 23.23 | 179.83 | 23.73 | 2.83 | 23.73 |
Maximum of Months | 68.33 | 23.91 | 324.00 | 23.91 | 45.67 | 23.91 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 167.33 | 25.62 | 257.00 | 26.15 | 130.50 | 26.21 |
February | 214.50 | 26.08 | 248.50 | 26.28 | 192.67 | 26.33 |
March | 258.33 | 26.23 | 293.83 | 26.41 | 234.00 | 26.46 |
April | 274.67 | 26.69 | 299.00 | 26.68 | 274.67 | 26.68 |
May | 311.00 | 26.71 | 312.00 | 26.71 | 311.00 | 26.71 |
June | 311.83 | 26.71 | 312.00 | 26.71 | 311.83 | 26.71 |
July | 300.00 | 26.71 | 300.00 | 26.71 | 300.00 | 26.71 |
August | 322.17 | 26.71 | 324.00 | 26.71 | 322.17 | 26.71 |
September | 300.00 | 26.71 | 300.00 | 26.71 | 300.00 | 26.71 |
October | 294.33 | 26.71 | 300.00 | 26.71 | 294.33 | 26.71 |
November | 258.50 | 26.53 | 279.00 | 26.57 | 252.33 | 26.59 |
December | 181.50 | 25.89 | 268.00 | 26.24 | 154.50 | 26.30 |
Annual Sum or Average | 3194.17 | 26.51 | 3493.33 | 26.57 | 3078.00 | 26.60 |
Minimum of Months | 167.33 | 25.62 | 248.50 | 26.15 | 130.50 | 26.21 |
Maximum of Months | 322.17 | 26.71 | 324.00 | 26.71 | 322.17 | 26.71 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 271.17 | 26.11 | 272.83 | 26.29 | 248.50 | 26.36 |
February | 259.67 | 27.41 | 257.00 | 27.54 | 243.17 | 27.62 |
March | 313.50 | 28.00 | 307.00 | 28.12 | 298.50 | 28.18 |
April | 286.33 | 30.44 | 294.17 | 30.38 | 283.33 | 30.43 |
May | 310.17 | 31.99 | 312.00 | 31.97 | 310.17 | 31.98 |
June | 312.00 | 32.44 | 312.00 | 32.44 | 312.00 | 32.44 |
July | 300.00 | 33.66 | 300.00 | 33.66 | 300.00 | 33.66 |
August | 324.00 | 32.52 | 324.00 | 32.52 | 324.00 | 32.52 |
September | 300.00 | 32.10 | 300.00 | 32.10 | 300.00 | 32.10 |
October | 296.50 | 30.70 | 300.00 | 30.67 | 296.50 | 30.68 |
November | 279.83 | 28.64 | 280.17 | 28.69 | 272.50 | 28.74 |
December | 264.83 | 26.48 | 263.17 | 26.72 | 233.00 | 26.83 |
Annual Sum or Average | 3518.00 | 30.17 | 3522.33 | 30.22 | 3421.67 | 30.28 |
Minimum of Months | 259.67 | 26.11 | 257.00 | 26.29 | 233.00 | 26.36 |
Maximum of Months | 324.00 | 33.66 | 324.00 | 33.66 | 324.00 | 33.66 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.821261E+10 | 0.217356E+10 | 331.87 | 0.637825E+10 | 0.183436E+10 | 0.00 | 1.00 | 02-JAN-00:01 | 0.00 | 01-JAN-00:10 | 34524.16 | 02-JAN-00:01 | 20701.02 | 02-JAN-00:01 | 14775.16 | 30-JAN-00:04 | 7765.08 | 02-JAN-00:01 | 0.00 | 01-JAN-00:10 |
February | 0.930267E+10 | 0.246291E+10 | 331.49 | 0.721256E+10 | 0.209010E+10 | 0.00 | 1.00 | 13-FEB-00:02 | 0.00 | 01-FEB-00:10 | 33418.79 | 13-FEB-00:02 | 26852.05 | 27-FEB-00:02 | 14435.47 | 13-FEB-00:02 | 7609.13 | 13-FEB-00:02 | 0.00 | 01-FEB-00:10 |
March | 0.124577E+11 | 0.327681E+10 | 438.14 | 0.944786E+10 | 0.300980E+10 | 0.00 | 1.00 | 06-MAR-00:01 | 0.00 | 01-MAR-00:05 | 35674.18 | 06-MAR-00:01 | 24678.46 | 14-MAR-17:08 | 17067.35 | 06-MAR-00:04 | 7911.42 | 06-MAR-00:01 | 0.00 | 01-MAR-00:05 |
April | 0.155248E+11 | 0.413377E+10 | 490.88 | 0.119419E+11 | 0.358292E+10 | 0.00 | 1.00 | 01-APR-17:06 | 0.00 | 01-APR-00:15 | 34167.80 | 16-APR-23:01 | 25928.16 | 17-APR-18:23 | 12874.06 | 16-APR-23:05 | 7716.44 | 16-APR-23:01 | 0.00 | 01-APR-00:10 |
May | 0.206370E+11 | 0.555196E+10 | 527.14 | 0.148033E+11 | 0.583369E+10 | 0.00 | 1.00 | 01-MAY-17:06 | 0.00 | 01-MAY-00:15 | 35482.23 | 29-MAY-23:01 | 24904.69 | 02-MAY-17:42 | 17371.88 | 29-MAY-23:05 | 8075.19 | 29-MAY-23:01 | 0.00 | 01-MAY-00:10 |
June | 0.224238E+11 | 0.605484E+10 | 530.44 | 0.154433E+11 | 0.698049E+10 | 0.00 | 1.00 | 01-JUN-17:06 | 0.00 | 01-JUN-00:13 | 36347.91 | 18-JUN-23:01 | 23449.14 | 10-JUN-17:42 | 19003.39 | 18-JUN-23:03 | 8180.55 | 11-JUN-23:01 | 0.00 | 01-JUN-00:10 |
July | 0.227500E+11 | 0.623321E+10 | 522.52 | 0.160034E+11 | 0.674655E+10 | 0.00 | 1.00 | 01-JUL-17:05 | 0.00 | 01-JUL-00:13 | 35555.59 | 02-JUL-23:01 | 23541.88 | 29-JUL-17:42 | 16132.17 | 30-JUL-23:06 | 8144.36 | 09-JUL-23:01 | 0.00 | 01-JUL-00:05 |
August | 0.239214E+11 | 0.649830E+10 | 552.25 | 0.164630E+11 | 0.745840E+10 | 0.00 | 1.00 | 01-AUG-01:43 | 0.00 | 01-AUG-00:12 | 35979.25 | 06-AUG-23:01 | 23708.42 | 07-AUG-05:43 | 19341.92 | 27-AUG-23:04 | 8144.36 | 20-AUG-23:01 | 0.00 | 01-AUG-00:10 |
September | 0.214470E+11 | 0.580566E+10 | 518.03 | 0.148993E+11 | 0.654772E+10 | 0.00 | 1.00 | 01-SEP-17:05 | 0.00 | 01-SEP-00:13 | 35383.14 | 24-SEP-23:01 | 23452.88 | 30-SEP-21:43 | 15886.68 | 17-SEP-23:06 | 8184.47 | 10-SEP-23:01 | 0.00 | 01-SEP-00:10 |
October | 0.191198E+11 | 0.513056E+10 | 508.01 | 0.135999E+11 | 0.551996E+10 | 0.00 | 1.00 | 01-OCT-23:01 | 0.00 | 01-OCT-00:05 | 36007.54 | 01-OCT-23:02 | 24565.37 | 17-OCT-17:06 | 20085.95 | 29-OCT-23:06 | 8092.63 | 29-OCT-23:01 | 0.00 | 01-OCT-00:05 |
November | 0.145224E+11 | 0.385237E+10 | 441.22 | 0.103460E+11 | 0.417631E+10 | 0.00 | 1.00 | 02-NOV-17:08 | 0.00 | 01-NOV-00:15 | 35849.49 | 05-NOV-23:01 | 22263.45 | 20-NOV-00:01 | 18466.81 | 24-NOV-00:04 | 8035.02 | 24-NOV-00:01 | 0.00 | 01-NOV-00:10 |
December | 0.937033E+10 | 0.247494E+10 | 357.72 | 0.717130E+10 | 0.219903E+10 | 0.00 | 1.00 | 04-DEC-00:01 | 0.00 | 01-DEC-00:10 | 36347.91 | 26-DEC-00:01 | 25920.79 | 04-DEC-00:01 | 19628.35 | 26-DEC-00:02 | 7990.25 | 26-DEC-00:01 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.199689E+12 | 0.536489E+11 | 5549.72 | 0.143710E+12 | 0.559793E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.821261E+10 | 0.217356E+10 | 331.49 | 0.637825E+10 | 0.183436E+10 | 0.00 | 1.00 | 0.00 | 33418.79 | 20701.02 | 12874.06 | 7609.13 | 0.00 | |||||||
Maximum of Months | 0.239214E+11 | 0.649830E+10 | 552.25 | 0.164630E+11 | 0.745840E+10 | 0.00 | 1.00 | 0.00 | 36347.91 | 26852.05 | 20085.95 | 8184.47 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.177016E+11 | 0.512150E+10 | 234.10 | 0.135414E+11 | 0.416021E+10 | 0.00 | 0.73 | 01-JAN-13:23 | 0.00 | 01-JAN-00:10 | 89175.37 | 01-JAN-13:23 | 66311.93 | 01-JAN-13:23 | 23251.65 | 01-JAN-12:03 | 24306.36 | 01-JAN-13:23 | 0.00 | 01-JAN-00:10 |
February | 0.223016E+11 | 0.645167E+10 | 229.05 | 0.172452E+11 | 0.505648E+10 | 0.00 | 1.00 | 19-FEB-14:02 | 0.00 | 01-FEB-00:10 | 131090.75 | 19-FEB-14:02 | 105701.14 | 20-FEB-15:13 | 38856.06 | 19-FEB-14:02 | 34077.60 | 19-FEB-14:02 | 0.00 | 01-FEB-00:10 |
March | 0.325419E+11 | 0.932126E+10 | 301.53 | 0.245978E+11 | 0.794409E+10 | 0.00 | 1.00 | 26-MAR-15:32 | 0.00 | 01-MAR-00:05 | 129315.78 | 26-MAR-15:32 | 96408.33 | 26-MAR-15:32 | 43599.97 | 05-MAR-11:13 | 33423.02 | 26-MAR-15:32 | 0.00 | 01-MAR-00:05 |
April | 0.485172E+11 | 0.140685E+11 | 385.24 | 0.373874E+11 | 0.111298E+11 | 0.00 | 1.00 | 01-APR-17:06 | 0.00 | 01-APR-00:10 | 131700.12 | 23-APR-15:32 | 109835.44 | 09-APR-15:12 | 39699.89 | 01-APR-17:06 | 34547.85 | 15-APR-17:05 | 0.00 | 01-APR-00:10 |
May | 0.698332E+11 | 0.204549E+11 | 499.04 | 0.503373E+11 | 0.194959E+11 | 0.00 | 1.00 | 03-MAY-17:06 | 0.00 | 01-MAY-00:10 | 136484.81 | 28-MAY-12:53 | 102495.72 | 02-MAY-17:06 | 53666.52 | 29-MAY-09:13 | 36249.20 | 29-MAY-13:12 | 0.00 | 01-MAY-00:10 |
June | 0.791196E+11 | 0.232100E+11 | 555.19 | 0.552975E+11 | 0.238221E+11 | 0.00 | 1.00 | 01-JUN-17:06 | 0.00 | 01-JUN-00:13 | 136336.62 | 18-JUN-12:32 | 101212.71 | 11-JUN-13:42 | 52347.20 | 18-JUN-12:32 | 35350.22 | 25-JUN-13:52 | 0.00 | 01-JUN-00:10 |
July | 0.859622E+11 | 0.256491E+11 | 579.36 | 0.618586E+11 | 0.241036E+11 | 0.00 | 1.00 | 01-JUL-17:05 | 0.00 | 01-JUL-00:13 | 134394.34 | 30-JUL-17:42 | 101481.78 | 16-JUL-13:02 | 48339.70 | 09-JUL-23:01 | 35865.17 | 30-JUL-14:22 | 0.00 | 01-JUL-00:05 |
August | 0.823097E+11 | 0.243395E+11 | 569.07 | 0.571915E+11 | 0.251182E+11 | 0.00 | 1.00 | 01-AUG-17:06 | 0.00 | 01-AUG-00:12 | 134824.81 | 13-AUG-13:43 | 100852.05 | 06-AUG-12:42 | 50282.72 | 20-AUG-23:01 | 36123.17 | 20-AUG-11:42 | 0.00 | 01-AUG-00:10 |
September | 0.757657E+11 | 0.223294E+11 | 531.04 | 0.531466E+11 | 0.226191E+11 | 0.00 | 1.00 | 01-SEP-17:05 | 0.00 | 01-SEP-00:13 | 132983.83 | 22-SEP-17:42 | 97903.45 | 03-SEP-15:53 | 47722.12 | 22-SEP-17:42 | 35595.71 | 18-SEP-17:05 | 0.00 | 01-SEP-00:10 |
October | 0.607618E+11 | 0.178046E+11 | 472.13 | 0.430065E+11 | 0.177553E+11 | 0.00 | 1.00 | 02-OCT-17:06 | 0.00 | 01-OCT-00:13 | 133678.37 | 29-OCT-14:13 | 101351.05 | 15-OCT-15:22 | 57017.62 | 29-OCT-09:33 | 35928.41 | 29-OCT-10:53 | 0.00 | 01-OCT-00:05 |
November | 0.380565E+11 | 0.109985E+11 | 324.54 | 0.267709E+11 | 0.112857E+11 | 0.00 | 1.00 | 05-NOV-13:53 | 0.00 | 01-NOV-00:10 | 134423.48 | 23-NOV-14:32 | 95269.16 | 19-NOV-14:23 | 51611.48 | 23-NOV-11:13 | 34587.31 | 23-NOV-14:32 | 0.00 | 01-NOV-00:10 |
December | 0.219868E+11 | 0.632903E+10 | 251.71 | 0.163925E+11 | 0.559430E+10 | 0.00 | 1.00 | 10-DEC-12:23 | 0.00 | 01-DEC-00:05 | 134073.38 | 10-DEC-12:23 | 95707.44 | 03-DEC-12:22 | 47471.75 | 10-DEC-12:23 | 34884.10 | 10-DEC-12:23 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.634858E+12 | 0.186078E+12 | 4932.01 | 0.456773E+12 | 0.178085E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.177016E+11 | 0.512150E+10 | 229.05 | 0.135414E+11 | 0.416021E+10 | 0.00 | 0.73 | 0.00 | 89175.37 | 66311.93 | 23251.65 | 24306.36 | 0.00 | |||||||
Maximum of Months | 0.859622E+11 | 0.256491E+11 | 579.36 | 0.618586E+11 | 0.251182E+11 | 0.00 | 1.00 | 0.00 | 136484.81 | 109835.44 | 57017.62 | 36249.20 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.62 | 19.41 | 25.21 | 91.15 | 114.81 | 0.00 | 0.00 | 0.00 |
February | 55.47 | 25.16 | 30.32 | 133.58 | 91.86 | 0.00 | 0.00 | 0.00 |
March | 68.80 | 31.30 | 37.50 | 166.06 | 77.45 | 0.00 | 0.00 | 0.00 |
April | 75.20 | 34.47 | 40.74 | 205.76 | 51.65 | 0.00 | 0.00 | 0.00 |
May | 69.11 | 26.55 | 42.56 | 213.27 | 27.46 | 0.00 | 0.00 | 0.00 |
June | 58.69 | 16.48 | 42.21 | 196.45 | 12.38 | 0.00 | 0.00 | 0.00 |
July | 65.57 | 20.33 | 45.24 | 227.11 | 18.56 | 0.00 | 0.00 | 0.00 |
August | 65.27 | 21.18 | 44.09 | 209.04 | 15.32 | 0.00 | 0.00 | 0.00 |
September | 55.71 | 16.42 | 39.28 | 188.62 | 20.77 | 0.00 | 0.00 | 0.00 |
October | 55.38 | 21.57 | 33.81 | 165.39 | 35.14 | 0.33 | 0.00 | 0.00 |
November | 45.82 | 16.86 | 28.96 | 121.42 | 59.68 | 0.00 | 0.00 | 0.00 |
December | 46.08 | 20.74 | 25.34 | 102.50 | 97.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.84 | 22.53 | 36.30 | 168.54 | 51.71 | 0.33 | 0.00 | 0.00 |
Minimum of Months | 44.62 | 16.42 | 25.21 | 91.15 | 12.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.20 | 34.47 | 45.24 | 227.11 | 114.81 | 0.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.62 | 19.41 | 25.21 | 91.15 | 114.81 | 0.00 | 0.00 | 0.00 |
February | 55.47 | 25.16 | 30.32 | 133.58 | 91.86 | 0.00 | 0.00 | 0.00 |
March | 68.80 | 31.30 | 37.50 | 166.06 | 77.45 | 0.00 | 0.00 | 0.00 |
April | 75.20 | 34.47 | 40.74 | 205.76 | 51.65 | 0.00 | 0.00 | 0.00 |
May | 69.11 | 26.55 | 42.56 | 213.27 | 27.46 | 0.00 | 0.00 | 0.00 |
June | 58.69 | 16.48 | 42.21 | 196.45 | 12.38 | 0.00 | 0.00 | 0.00 |
July | 65.57 | 20.33 | 45.24 | 227.11 | 18.56 | 0.00 | 0.00 | 0.00 |
August | 65.27 | 21.18 | 44.09 | 209.04 | 15.32 | 0.00 | 0.00 | 0.00 |
September | 55.71 | 16.42 | 39.28 | 188.62 | 20.77 | 0.00 | 0.00 | 0.00 |
October | 55.38 | 21.57 | 33.81 | 165.39 | 35.14 | 0.33 | 0.00 | 0.00 |
November | 45.82 | 16.86 | 28.96 | 121.42 | 59.68 | 0.00 | 0.00 | 0.00 |
December | 46.08 | 20.74 | 25.34 | 102.50 | 97.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.84 | 22.53 | 36.30 | 168.54 | 51.71 | 0.33 | 0.00 | 0.00 |
Minimum of Months | 44.62 | 16.42 | 25.21 | 91.15 | 12.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.20 | 34.47 | 45.24 | 227.11 | 114.81 | 0.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.94 | 0.00 | 11.94 | 14.24 | 70.29 | 0.00 | 0.00 | 0.00 |
February | 14.13 | 0.00 | 14.13 | 23.88 | 55.86 | 0.00 | 0.00 | 0.00 |
March | 16.86 | 0.00 | 16.85 | 28.72 | 47.42 | 0.00 | 0.00 | 0.00 |
April | 18.99 | 0.17 | 18.82 | 43.76 | 30.63 | 0.00 | 0.00 | 0.00 |
May | 21.84 | 1.22 | 20.62 | 67.42 | 15.29 | 0.00 | 0.00 | 0.00 |
June | 23.51 | 2.13 | 21.39 | 81.12 | 6.53 | 0.00 | 0.00 | 0.00 |
July | 23.65 | 1.48 | 22.17 | 86.87 | 10.38 | 0.00 | 0.00 | 0.00 |
August | 20.81 | 0.35 | 20.46 | 69.63 | 8.68 | 0.00 | 0.00 | 0.00 |
September | 18.31 | 0.01 | 18.30 | 65.36 | 11.91 | 0.00 | 0.00 | 0.00 |
October | 15.33 | 0.00 | 15.33 | 44.83 | 20.56 | 0.33 | 0.00 | 0.00 |
November | 13.33 | 0.00 | 13.33 | 29.41 | 35.31 | 0.00 | 0.00 | 0.00 |
December | 11.81 | 0.00 | 11.81 | 16.68 | 60.05 | 0.17 | 0.00 | 0.00 |
Annual Sum or Average | 17.56 | 0.45 | 17.11 | 47.78 | 30.98 | 0.50 | 0.00 | 0.00 |
Minimum of Months | 11.81 | 0.00 | 11.81 | 14.24 | 6.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.65 | 2.13 | 22.17 | 86.87 | 70.29 | 0.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.94 | 0.00 | 11.94 | 14.24 | 70.29 | 0.00 | 0.00 | 0.00 |
February | 14.13 | 0.00 | 14.13 | 23.88 | 55.85 | 0.00 | 0.00 | 0.00 |
March | 16.86 | 0.00 | 16.85 | 28.72 | 47.42 | 0.00 | 0.00 | 0.00 |
April | 18.99 | 0.17 | 18.82 | 43.76 | 30.63 | 0.00 | 0.00 | 0.00 |
May | 21.84 | 1.22 | 20.62 | 67.42 | 15.29 | 0.00 | 0.00 | 0.00 |
June | 23.51 | 2.13 | 21.38 | 81.12 | 6.53 | 0.00 | 0.00 | 0.00 |
July | 23.65 | 1.48 | 22.17 | 86.87 | 10.38 | 0.00 | 0.00 | 0.00 |
August | 20.81 | 0.35 | 20.46 | 69.63 | 8.68 | 0.00 | 0.00 | 0.00 |
September | 18.31 | 0.01 | 18.30 | 65.36 | 11.91 | 0.00 | 0.00 | 0.00 |
October | 15.33 | 0.00 | 15.33 | 44.83 | 20.56 | 0.33 | 0.00 | 0.00 |
November | 13.33 | 0.00 | 13.33 | 29.41 | 35.31 | 0.00 | 0.00 | 0.00 |
December | 11.81 | 0.00 | 11.81 | 16.68 | 60.05 | 0.17 | 0.00 | 0.00 |
Annual Sum or Average | 17.56 | 0.45 | 17.11 | 47.78 | 30.98 | 0.50 | 0.00 | 0.00 |
Minimum of Months | 11.81 | 0.00 | 11.81 | 14.24 | 6.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.65 | 2.13 | 22.17 | 86.87 | 70.29 | 0.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 85.30 | 46.20 | 84.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 108.49 | 43.49 | 19.33 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 135.04 | 42.36 | 8.17 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 160.68 | 41.87 | 15.33 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 160.25 | 34.28 | 12.00 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 152.60 | 30.17 | 18.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 167.59 | 33.39 | 9.67 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 147.16 | 31.57 | 18.83 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 133.98 | 32.61 | 30.67 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 114.73 | 38.46 | 57.83 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 91.01 | 38.58 | 92.00 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 79.77 | 40.37 | 64.67 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 128.14 | 37.75 | 430.67 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 79.77 | 30.17 | 8.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 167.59 | 46.20 | 92.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 85.30 | 46.20 | 84.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 108.49 | 43.49 | 19.33 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 135.04 | 42.36 | 8.17 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 160.68 | 41.87 | 15.33 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 160.25 | 34.28 | 12.00 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 152.60 | 30.17 | 18.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 167.59 | 33.39 | 9.67 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 147.16 | 31.57 | 18.83 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 133.98 | 32.61 | 30.67 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 114.73 | 38.46 | 57.83 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 91.01 | 38.58 | 92.00 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 79.77 | 40.37 | 64.67 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 128.14 | 37.75 | 430.67 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 79.77 | 30.17 | 8.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 167.59 | 46.20 | 92.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 85.30 | 46.20 | 84.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 108.49 | 43.49 | 19.33 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 135.04 | 42.36 | 8.17 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 160.68 | 41.87 | 15.33 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 160.25 | 34.28 | 12.00 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 152.60 | 30.17 | 18.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 167.59 | 33.39 | 9.67 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 147.16 | 31.57 | 18.83 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 133.98 | 32.61 | 30.67 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 114.73 | 38.46 | 57.83 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 91.01 | 38.58 | 92.00 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 79.77 | 40.37 | 64.67 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 128.14 | 37.75 | 430.67 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 79.77 | 30.17 | 8.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 167.59 | 46.20 | 92.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 85.30 | 46.20 | 84.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 108.49 | 43.49 | 19.33 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 135.04 | 42.36 | 8.17 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 160.68 | 41.87 | 15.33 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 160.25 | 34.28 | 12.00 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 152.60 | 30.17 | 18.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 167.59 | 33.39 | 9.67 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 147.16 | 31.57 | 18.83 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 133.98 | 32.61 | 30.67 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 114.73 | 38.46 | 57.83 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 91.01 | 38.58 | 92.00 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 79.77 | 40.37 | 64.67 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 128.14 | 37.75 | 430.67 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 79.77 | 30.17 | 8.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 167.59 | 46.20 | 92.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 85.30 | 46.20 | 84.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 108.49 | 43.49 | 19.33 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 135.04 | 42.36 | 8.17 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 160.68 | 41.87 | 15.33 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 160.25 | 34.28 | 12.00 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 152.60 | 30.17 | 18.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 167.59 | 33.39 | 9.67 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 147.16 | 31.57 | 18.83 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 133.98 | 32.61 | 30.67 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 114.73 | 38.46 | 57.83 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 91.01 | 38.58 | 92.00 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 79.77 | 40.37 | 64.67 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 128.14 | 37.75 | 430.67 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 79.77 | 30.17 | 8.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 167.59 | 46.20 | 92.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 85.30 | 46.20 | 84.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 108.49 | 43.49 | 19.33 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 135.04 | 42.36 | 8.17 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 160.68 | 41.87 | 15.33 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 160.25 | 34.28 | 12.00 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 152.60 | 30.17 | 18.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 167.59 | 33.39 | 9.67 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 147.16 | 31.57 | 18.83 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 133.98 | 32.61 | 30.67 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 114.73 | 38.46 | 57.83 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 91.01 | 38.58 | 92.00 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 79.77 | 40.37 | 64.67 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 128.14 | 37.75 | 430.67 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 79.77 | 30.17 | 8.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 167.59 | 46.20 | 92.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 85.30 | 46.20 | 84.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 108.49 | 43.49 | 19.33 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 135.04 | 42.36 | 8.17 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 160.68 | 41.87 | 15.33 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 160.25 | 34.28 | 12.00 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 152.60 | 30.17 | 18.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 167.59 | 33.39 | 9.67 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 147.16 | 31.57 | 18.83 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 133.98 | 32.61 | 30.67 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 114.73 | 38.46 | 57.83 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 91.01 | 38.58 | 92.00 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 79.77 | 40.37 | 64.67 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 128.14 | 37.75 | 430.67 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 79.77 | 30.17 | 8.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 167.59 | 46.20 | 92.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 85.30 | 46.20 | 84.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 108.49 | 43.49 | 19.33 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 135.04 | 42.36 | 8.17 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 160.68 | 41.87 | 15.33 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 160.25 | 34.28 | 12.00 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 152.60 | 30.17 | 18.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 167.59 | 33.39 | 9.67 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 147.16 | 31.57 | 18.83 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 133.98 | 32.61 | 30.67 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 114.73 | 38.46 | 57.83 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 91.01 | 38.58 | 92.00 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 79.77 | 40.37 | 64.67 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 128.14 | 37.75 | 430.67 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 79.77 | 30.17 | 8.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 167.59 | 46.20 | 92.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 85.30 | 46.20 | 84.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 108.49 | 43.49 | 19.33 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 135.04 | 42.36 | 8.17 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 160.68 | 41.87 | 15.33 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 160.25 | 34.28 | 12.00 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 152.60 | 30.17 | 18.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 167.59 | 33.39 | 9.67 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 147.16 | 31.57 | 18.83 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 133.98 | 32.61 | 30.67 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 114.73 | 38.46 | 57.83 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 91.01 | 38.58 | 92.00 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 79.77 | 40.37 | 64.67 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 128.14 | 37.75 | 430.67 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 79.77 | 30.17 | 8.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 167.59 | 46.20 | 92.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.68 | 44.43 | 29.25 | 85.30 | 46.20 | 84.17 | 0.00 | 0.00 |
February | 90.07 | 54.80 | 35.27 | 108.49 | 43.49 | 19.33 | 0.00 | 0.00 |
March | 112.30 | 68.35 | 43.95 | 135.04 | 42.36 | 8.17 | 0.00 | 0.00 |
April | 130.78 | 81.16 | 49.62 | 160.68 | 41.87 | 15.33 | 0.00 | 0.00 |
May | 129.16 | 72.58 | 56.58 | 160.25 | 34.28 | 12.00 | 0.00 | 0.00 |
June | 122.81 | 61.28 | 61.53 | 152.60 | 30.17 | 18.00 | 0.00 | 0.00 |
July | 133.73 | 69.98 | 63.76 | 167.59 | 33.39 | 9.67 | 0.00 | 0.00 |
August | 121.61 | 60.13 | 61.49 | 147.16 | 31.57 | 18.83 | 0.00 | 0.00 |
September | 107.19 | 52.15 | 55.04 | 133.98 | 32.61 | 30.67 | 0.00 | 0.00 |
October | 94.27 | 52.64 | 41.63 | 114.73 | 38.46 | 57.83 | 0.00 | 0.00 |
November | 75.27 | 39.14 | 36.13 | 91.01 | 38.58 | 92.00 | 0.00 | 0.00 |
December | 67.54 | 37.13 | 30.41 | 79.77 | 40.37 | 64.67 | 0.00 | 0.00 |
Annual Sum or Average | 104.94 | 57.83 | 47.11 | 128.14 | 37.75 | 430.67 | 0.00 | 0.00 |
Minimum of Months | 67.54 | 37.13 | 29.25 | 79.77 | 30.17 | 8.17 | 0.00 | 0.00 |
Maximum of Months | 133.73 | 81.16 | 63.76 | 167.59 | 46.20 | 92.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119514E+09 | 51989820.64 | 67524471.88 | 0.244144E+09 | 0.307495E+09 |
February | 0.134200E+09 | 60857118.44 | 73342704.95 | 0.323147E+09 | 0.222222E+09 |
March | 0.184282E+09 | 83838571.27 | 0.100443E+09 | 0.444777E+09 | 0.207430E+09 |
April | 0.194930E+09 | 89339790.75 | 0.105590E+09 | 0.533333E+09 | 0.133888E+09 |
May | 0.185102E+09 | 71103770.22 | 0.113998E+09 | 0.571215E+09 | 73543559.72 |
June | 0.152126E+09 | 42716516.55 | 0.109409E+09 | 0.509200E+09 | 32077339.88 |
July | 0.175613E+09 | 54447372.73 | 0.121165E+09 | 0.608303E+09 | 49698566.80 |
August | 0.174829E+09 | 56727446.87 | 0.118102E+09 | 0.559890E+09 | 41034553.58 |
September | 0.144390E+09 | 42573599.93 | 0.101816E+09 | 0.488904E+09 | 53839614.99 |
October | 0.148334E+09 | 57777091.23 | 90557215.98 | 0.442991E+09 | 94105687.60 |
November | 0.118770E+09 | 43696238.03 | 75073278.39 | 0.314717E+09 | 0.154684E+09 |
December | 0.123420E+09 | 55560149.66 | 67860092.45 | 0.274548E+09 | 0.260632E+09 |
Annual Sum or Average | 0.185551E+10 | 0.710627E+09 | 0.114488E+10 | 0.531517E+10 | 0.163065E+10 |
Minimum of Months | 0.118770E+09 | 42573599.93 | 67524471.88 | 0.244144E+09 | 32077339.88 |
Maximum of Months | 0.194930E+09 | 89339790.75 | 0.121165E+09 | 0.608303E+09 | 0.307495E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119514E+09 | 51989820.64 | 67524471.88 | 0.244144E+09 | 0.307495E+09 |
February | 0.134200E+09 | 60857118.44 | 73342704.95 | 0.323147E+09 | 0.222222E+09 |
March | 0.184282E+09 | 83838571.27 | 0.100443E+09 | 0.444777E+09 | 0.207430E+09 |
April | 0.194930E+09 | 89339790.75 | 0.105590E+09 | 0.533333E+09 | 0.133888E+09 |
May | 0.185102E+09 | 71103770.22 | 0.113998E+09 | 0.571215E+09 | 73543559.72 |
June | 0.152126E+09 | 42716516.55 | 0.109409E+09 | 0.509200E+09 | 32077339.88 |
July | 0.175613E+09 | 54447372.73 | 0.121165E+09 | 0.608303E+09 | 49698566.80 |
August | 0.174829E+09 | 56727446.87 | 0.118102E+09 | 0.559890E+09 | 41034553.58 |
September | 0.144390E+09 | 42573599.93 | 0.101816E+09 | 0.488904E+09 | 53839614.99 |
October | 0.148334E+09 | 57777091.23 | 90557215.98 | 0.442991E+09 | 94105687.60 |
November | 0.118770E+09 | 43696238.03 | 75073278.39 | 0.314717E+09 | 0.154684E+09 |
December | 0.123420E+09 | 55560149.66 | 67860092.45 | 0.274548E+09 | 0.260632E+09 |
Annual Sum or Average | 0.185551E+10 | 0.710627E+09 | 0.114488E+10 | 0.531517E+10 | 0.163065E+10 |
Minimum of Months | 0.118770E+09 | 42573599.93 | 67524471.88 | 0.244144E+09 | 32077339.88 |
Maximum of Months | 0.194930E+09 | 89339790.75 | 0.121165E+09 | 0.608303E+09 | 0.307495E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 31970577.54 | 0.00 | 31970577.54 | 38151162.71 | 0.188258E+09 |
February | 34180133.89 | 0.00 | 34180133.89 | 57779405.96 | 0.135125E+09 |
March | 45149631.54 | 6085.77 | 45143545.78 | 76932998.90 | 0.127008E+09 |
April | 49225591.75 | 448589.94 | 48777001.81 | 0.113419E+09 | 79390331.65 |
May | 58488871.22 | 3271850.94 | 55217020.28 | 0.180575E+09 | 40964811.23 |
June | 60941883.82 | 5510456.11 | 55431427.71 | 0.210267E+09 | 16936116.62 |
July | 63350739.75 | 3962798.65 | 59387941.09 | 0.232677E+09 | 27814497.44 |
August | 55728085.89 | 935564.41 | 54792521.48 | 0.186507E+09 | 23242077.54 |
September | 47458565.99 | 17908.27 | 47440657.72 | 0.169415E+09 | 30881654.61 |
October | 41059420.72 | 0.00 | 41059420.72 | 0.120065E+09 | 55078246.68 |
November | 34549726.50 | 0.00 | 34549726.50 | 76237202.01 | 91523519.12 |
December | 31622888.14 | 0.00 | 31622888.14 | 44687577.57 | 0.160826E+09 |
Annual Sum or Average | 0.553726E+09 | 14153254.09 | 0.539573E+09 | 0.150671E+10 | 0.977049E+09 |
Minimum of Months | 31622888.14 | 0.00 | 31622888.14 | 38151162.71 | 16936116.62 |
Maximum of Months | 63350739.75 | 5510456.11 | 59387941.09 | 0.232677E+09 | 0.188258E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 31969646.60 | 0.00 | 31969646.60 | 38149834.29 | 0.188257E+09 |
February | 34179156.05 | 0.00 | 34179156.05 | 57777756.79 | 0.135124E+09 |
March | 45148353.52 | 6085.48 | 45142268.04 | 76930617.26 | 0.127007E+09 |
April | 49224220.79 | 448568.91 | 48775651.88 | 0.113416E+09 | 79389201.16 |
May | 58487079.46 | 3271697.58 | 55215381.88 | 0.180570E+09 | 40963732.91 |
June | 60939905.25 | 5510197.83 | 55429707.41 | 0.210262E+09 | 16935452.42 |
July | 63348754.24 | 3962612.91 | 59386141.33 | 0.232672E+09 | 27813532.52 |
August | 55726373.33 | 935520.56 | 54790852.77 | 0.186504E+09 | 23241323.31 |
September | 47457114.51 | 17907.43 | 47439207.08 | 0.169412E+09 | 30880800.88 |
October | 41058204.21 | 0.00 | 41058204.21 | 0.120063E+09 | 55076832.71 |
November | 34548666.66 | 0.00 | 34548666.66 | 76235167.46 | 91522177.56 |
December | 31621931.21 | 0.00 | 31621931.21 | 44685977.63 | 0.160825E+09 |
Annual Sum or Average | 0.553709E+09 | 14152590.71 | 0.539557E+09 | 0.150668E+10 | 0.977036E+09 |
Minimum of Months | 31621931.21 | 0.00 | 31621931.21 | 38149834.29 | 16935452.42 |
Maximum of Months | 63348754.24 | 5510197.83 | 59386141.33 | 0.232672E+09 | 0.188257E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.228470E+09 | 0.123743E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.262464E+09 | 0.105206E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.361692E+09 | 0.113447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.416488E+09 | 0.108525E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.429214E+09 | 91804448.55 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.395539E+09 | 78188845.77 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.448867E+09 | 89428855.59 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.394145E+09 | 84563276.90 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.347282E+09 | 84536616.86 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.307304E+09 | 0.103009E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.235910E+09 | 99998743.07 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.213669E+09 | 0.108117E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.404104E+10 | 0.119057E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.213669E+09 | 78188845.77 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.448867E+09 | 0.123743E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.228470E+09 | 0.123743E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.262464E+09 | 0.105206E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.361692E+09 | 0.113447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.416488E+09 | 0.108525E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.429214E+09 | 91804448.55 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.395539E+09 | 78188845.77 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.448867E+09 | 89428855.59 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.394145E+09 | 84563276.90 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.347282E+09 | 84536616.86 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.307304E+09 | 0.103009E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.235910E+09 | 99998743.07 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.213669E+09 | 0.108117E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.404104E+10 | 0.119057E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.213669E+09 | 78188845.77 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.448867E+09 | 0.123743E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.228470E+09 | 0.123743E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.262464E+09 | 0.105206E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.361692E+09 | 0.113447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.416488E+09 | 0.108525E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.429214E+09 | 91804448.55 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.395539E+09 | 78188845.77 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.448867E+09 | 89428855.59 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.394145E+09 | 84563276.90 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.347282E+09 | 84536616.86 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.307304E+09 | 0.103009E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.235910E+09 | 99998743.07 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.213669E+09 | 0.108117E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.404104E+10 | 0.119057E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.213669E+09 | 78188845.77 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.448867E+09 | 0.123743E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.228470E+09 | 0.123743E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.262464E+09 | 0.105206E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.361692E+09 | 0.113447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.416488E+09 | 0.108525E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.429214E+09 | 91804448.55 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.395539E+09 | 78188845.77 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.448867E+09 | 89428855.59 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.394145E+09 | 84563276.90 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.347282E+09 | 84536616.86 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.307304E+09 | 0.103009E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.235910E+09 | 99998743.07 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.213669E+09 | 0.108117E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.404104E+10 | 0.119057E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.213669E+09 | 78188845.77 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.448867E+09 | 0.123743E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.228470E+09 | 0.123743E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.262464E+09 | 0.105206E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.361692E+09 | 0.113447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.416488E+09 | 0.108525E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.429214E+09 | 91804448.55 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.395539E+09 | 78188845.77 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.448867E+09 | 89428855.59 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.394145E+09 | 84563276.90 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.347282E+09 | 84536616.86 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.307304E+09 | 0.103009E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.235910E+09 | 99998743.07 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.213669E+09 | 0.108117E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.404104E+10 | 0.119057E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.213669E+09 | 78188845.77 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.448867E+09 | 0.123743E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.228470E+09 | 0.123743E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.262464E+09 | 0.105206E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.361692E+09 | 0.113447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.416488E+09 | 0.108525E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.429214E+09 | 91804448.55 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.395539E+09 | 78188845.77 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.448867E+09 | 89428855.59 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.394145E+09 | 84563276.90 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.347282E+09 | 84536616.86 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.307304E+09 | 0.103009E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.235910E+09 | 99998743.07 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.213669E+09 | 0.108117E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.404104E+10 | 0.119057E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.213669E+09 | 78188845.77 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.448867E+09 | 0.123743E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.228470E+09 | 0.123743E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.262464E+09 | 0.105206E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.361692E+09 | 0.113447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.416488E+09 | 0.108525E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.429214E+09 | 91804448.55 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.395539E+09 | 78188845.77 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.448867E+09 | 89428855.59 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.394145E+09 | 84563276.90 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.347282E+09 | 84536616.86 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.307304E+09 | 0.103009E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.235910E+09 | 99998743.07 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.213669E+09 | 0.108117E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.404104E+10 | 0.119057E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.213669E+09 | 78188845.77 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.448867E+09 | 0.123743E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.228470E+09 | 0.123743E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.262464E+09 | 0.105206E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.361692E+09 | 0.113447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.416488E+09 | 0.108525E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.429214E+09 | 91804448.55 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.395539E+09 | 78188845.77 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.448867E+09 | 89428855.59 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.394145E+09 | 84563276.90 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.347282E+09 | 84536616.86 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.307304E+09 | 0.103009E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.235910E+09 | 99998743.07 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.213669E+09 | 0.108117E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.404104E+10 | 0.119057E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.213669E+09 | 78188845.77 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.448867E+09 | 0.123743E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.228470E+09 | 0.123743E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.262464E+09 | 0.105206E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.361692E+09 | 0.113447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.416488E+09 | 0.108525E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.429214E+09 | 91804448.55 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.395539E+09 | 78188845.77 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.448867E+09 | 89428855.59 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.394145E+09 | 84563276.90 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.347282E+09 | 84536616.86 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.307304E+09 | 0.103009E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.235910E+09 | 99998743.07 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.213669E+09 | 0.108117E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.404104E+10 | 0.119057E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.213669E+09 | 78188845.77 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.448867E+09 | 0.123743E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197342E+09 | 0.119003E+09 | 78338874.14 | 0.228470E+09 | 0.123743E+09 |
February | 0.217898E+09 | 0.132577E+09 | 85320750.32 | 0.262464E+09 | 0.105206E+09 |
March | 0.300796E+09 | 0.183075E+09 | 0.117722E+09 | 0.361692E+09 | 0.113447E+09 |
April | 0.338969E+09 | 0.210356E+09 | 0.128613E+09 | 0.416488E+09 | 0.108525E+09 |
May | 0.345937E+09 | 0.194394E+09 | 0.151543E+09 | 0.429214E+09 | 91804448.55 |
June | 0.318314E+09 | 0.158834E+09 | 0.159480E+09 | 0.395539E+09 | 78188845.77 |
July | 0.358190E+09 | 0.187426E+09 | 0.170763E+09 | 0.448867E+09 | 89428855.59 |
August | 0.325730E+09 | 0.161043E+09 | 0.164687E+09 | 0.394145E+09 | 84563276.90 |
September | 0.277842E+09 | 0.135176E+09 | 0.142666E+09 | 0.347282E+09 | 84536616.86 |
October | 0.252491E+09 | 0.140982E+09 | 0.111510E+09 | 0.307304E+09 | 0.103009E+09 |
November | 0.195094E+09 | 0.101454E+09 | 93640079.98 | 0.235910E+09 | 99998743.07 |
December | 0.180905E+09 | 99442787.20 | 81462474.57 | 0.213669E+09 | 0.108117E+09 |
Annual Sum or Average | 0.330951E+10 | 0.182376E+10 | 0.148575E+10 | 0.404104E+10 | 0.119057E+10 |
Minimum of Months | 0.180905E+09 | 99442787.20 | 78338874.14 | 0.213669E+09 | 78188845.77 |
Maximum of Months | 0.358190E+09 | 0.210356E+09 | 0.170763E+09 | 0.448867E+09 | 0.123743E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 205.33 | 364.72 | 113.12 | 38.82 | 74.29 | 0.00 | 0.00 |
February | 311.93 | 292.43 | 139.20 | 50.31 | 88.89 | 0.00 | 0.00 |
March | 385.55 | 245.71 | 171.32 | 62.61 | 108.71 | 0.00 | 0.00 |
April | 497.35 | 162.88 | 188.39 | 69.28 | 119.11 | 0.00 | 0.00 |
May | 560.58 | 84.71 | 181.89 | 55.54 | 126.35 | 0.00 | 0.00 |
June | 554.02 | 36.69 | 164.40 | 37.21 | 127.19 | 0.00 | 0.00 |
July | 627.43 | 57.34 | 178.44 | 43.62 | 134.82 | 0.00 | 0.00 |
August | 557.14 | 47.79 | 172.16 | 43.06 | 129.10 | 0.00 | 0.00 |
September | 507.83 | 65.24 | 148.03 | 32.86 | 115.17 | 0.00 | 0.00 |
October | 419.84 | 110.79 | 141.42 | 43.14 | 98.28 | 0.00 | 0.00 |
November | 300.57 | 188.88 | 118.30 | 33.72 | 84.59 | 0.00 | 0.00 |
December | 233.79 | 310.12 | 115.77 | 41.49 | 74.29 | 0.00 | 0.00 |
Annual Sum or Average | 430.70 | 163.44 | 152.79 | 45.97 | 106.83 | 0.00 | 0.00 |
Minimum of Months | 205.33 | 36.69 | 113.12 | 32.86 | 74.29 | 0.00 | 0.00 |
Maximum of Months | 627.43 | 364.72 | 188.39 | 69.28 | 134.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6526.30 | 2021.69 | 736.79 | 444.30 | 292.48 | 0.00 | 0.00 |
February | 6577.60 | 1943.33 | 900.70 | 548.02 | 352.68 | 0.00 | 0.00 |
March | 8995.42 | 1960.40 | 1123.05 | 683.52 | 439.52 | 0.00 | 0.00 |
April | 8275.53 | 2211.39 | 1307.75 | 811.56 | 496.19 | 0.00 | 0.00 |
May | 7644.01 | 2037.54 | 1291.58 | 725.78 | 565.80 | 0.00 | 0.00 |
June | 7243.97 | 1867.27 | 1228.06 | 612.79 | 615.28 | 0.00 | 0.00 |
July | 9089.59 | 2155.32 | 1337.33 | 699.77 | 637.56 | 0.00 | 0.00 |
August | 7288.23 | 1970.11 | 1216.14 | 601.26 | 614.87 | 0.00 | 0.00 |
September | 7022.07 | 1969.42 | 1071.92 | 521.51 | 550.41 | 0.00 | 0.00 |
October | 5801.89 | 2170.85 | 942.69 | 526.36 | 416.33 | 0.00 | 0.00 |
November | 4817.98 | 1878.83 | 752.68 | 391.41 | 361.27 | 0.00 | 0.00 |
December | 5485.57 | 1787.64 | 675.42 | 371.28 | 304.15 | 0.00 | 0.00 |
Annual Sum or Average | 7070.47 | 1998.44 | 1049.44 | 578.31 | 471.13 | 0.00 | 0.00 |
Minimum of Months | 4817.98 | 1787.64 | 675.42 | 371.28 | 292.48 | 0.00 | 0.00 |
Maximum of Months | 9089.59 | 2211.39 | 1337.33 | 811.56 | 637.56 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.549944E+09 | 0.976862E+09 | 0.302969E+09 | 0.103980E+09 | 0.198989E+09 | 0.00 | 0.00 |
February | 0.754613E+09 | 0.707454E+09 | 0.336759E+09 | 0.121714E+09 | 0.215045E+09 | 0.00 | 0.00 |
March | 0.103265E+10 | 0.658110E+09 | 0.458862E+09 | 0.167689E+09 | 0.291173E+09 | 0.00 | 0.00 |
April | 0.128913E+10 | 0.422185E+09 | 0.488310E+09 | 0.179577E+09 | 0.308733E+09 | 0.00 | 0.00 |
May | 0.150146E+10 | 0.226899E+09 | 0.487179E+09 | 0.148751E+09 | 0.338428E+09 | 0.00 | 0.00 |
June | 0.143601E+10 | 95109562.13 | 0.426133E+09 | 96453687.04 | 0.329679E+09 | 0.00 | 0.00 |
July | 0.168051E+10 | 0.153583E+09 | 0.477925E+09 | 0.116820E+09 | 0.361105E+09 | 0.00 | 0.00 |
August | 0.149223E+10 | 0.127994E+09 | 0.461113E+09 | 0.115326E+09 | 0.345787E+09 | 0.00 | 0.00 |
September | 0.131631E+10 | 0.169113E+09 | 0.383696E+09 | 85183015.56 | 0.298513E+09 | 0.00 | 0.00 |
October | 0.112449E+10 | 0.296748E+09 | 0.378786E+09 | 0.115554E+09 | 0.263232E+09 | 0.00 | 0.00 |
November | 0.779066E+09 | 0.489573E+09 | 0.306637E+09 | 87392476.06 | 0.219245E+09 | 0.00 | 0.00 |
December | 0.626186E+09 | 0.830633E+09 | 0.310085E+09 | 0.111120E+09 | 0.198965E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135826E+11 | 0.515426E+10 | 0.481845E+10 | 0.144956E+10 | 0.336889E+10 | 0.00 | 0.00 |
Minimum of Months | 0.549944E+09 | 95109562.13 | 0.302969E+09 | 85183015.56 | 0.198965E+09 | 0.00 | 0.00 |
Maximum of Months | 0.168051E+10 | 0.976862E+09 | 0.488310E+09 | 0.179577E+09 | 0.361105E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.174800E+11 | 0.541489E+10 | 0.197342E+10 | 0.119003E+10 | 0.783389E+09 | 0.00 | 0.00 |
February | 0.159125E+11 | 0.470130E+10 | 0.217898E+10 | 0.132577E+10 | 0.853208E+09 | 0.00 | 0.00 |
March | 0.240933E+11 | 0.525073E+10 | 0.300796E+10 | 0.183075E+10 | 0.117722E+10 | 0.00 | 0.00 |
April | 0.214502E+11 | 0.573191E+10 | 0.338969E+10 | 0.210356E+10 | 0.128613E+10 | 0.00 | 0.00 |
May | 0.204737E+11 | 0.545734E+10 | 0.345937E+10 | 0.194394E+10 | 0.151543E+10 | 0.00 | 0.00 |
June | 0.187764E+11 | 0.483996E+10 | 0.318314E+10 | 0.158834E+10 | 0.159480E+10 | 0.00 | 0.00 |
July | 0.243456E+11 | 0.577281E+10 | 0.358190E+10 | 0.187426E+10 | 0.170763E+10 | 0.00 | 0.00 |
August | 0.195208E+11 | 0.527674E+10 | 0.325730E+10 | 0.161043E+10 | 0.164687E+10 | 0.00 | 0.00 |
September | 0.182012E+11 | 0.510474E+10 | 0.277842E+10 | 0.135176E+10 | 0.142666E+10 | 0.00 | 0.00 |
October | 0.155398E+11 | 0.581441E+10 | 0.252491E+10 | 0.140982E+10 | 0.111510E+10 | 0.00 | 0.00 |
November | 0.124882E+11 | 0.486993E+10 | 0.195094E+10 | 0.101454E+10 | 0.936401E+09 | 0.00 | 0.00 |
December | 0.146926E+11 | 0.478800E+10 | 0.180905E+10 | 0.994428E+09 | 0.814625E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.222974E+12 | 0.630228E+11 | 0.330951E+11 | 0.182376E+11 | 0.148575E+11 | 0.00 | 0.00 |
Minimum of Months | 0.124882E+11 | 0.470130E+10 | 0.180905E+10 | 0.994428E+09 | 0.783389E+09 | 0.00 | 0.00 |
Maximum of Months | 0.243456E+11 | 0.581441E+10 | 0.358190E+10 | 0.210356E+10 | 0.170763E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.42 | 15.96 | 13.59 | 3.30 | 9.49 | 57.21 | 169.93 | 0.03 |
February | 20.87 | 16.70 | 13.89 | 5.53 | 11.19 | 68.99 | 182.59 | 0.00 |
March | 21.57 | 17.63 | 15.09 | 5.59 | 12.13 | 85.97 | 199.13 | 0.00 |
April | 24.11 | 19.68 | 17.40 | 4.69 | 15.31 | 97.05 | 212.67 | 0.01 |
May | 26.41 | 22.40 | 20.67 | 5.05 | 18.50 | 110.67 | 177.92 | 0.00 |
June | 27.68 | 24.06 | 22.67 | 3.87 | 20.33 | 120.35 | 147.07 | 0.00 |
July | 28.13 | 24.25 | 22.77 | 2.86 | 20.30 | 124.71 | 163.26 | 0.00 |
August | 27.97 | 24.38 | 23.03 | 3.45 | 20.36 | 120.27 | 145.14 | 0.08 |
September | 27.49 | 23.91 | 22.56 | 3.39 | 20.13 | 107.67 | 134.94 | 0.00 |
October | 26.35 | 22.68 | 21.10 | 3.72 | 17.49 | 81.44 | 160.40 | 0.04 |
November | 23.59 | 20.24 | 18.46 | 4.39 | 14.74 | 70.67 | 140.11 | 0.00 |
December | 20.30 | 17.47 | 15.75 | 3.70 | 12.21 | 59.50 | 147.31 | 0.00 |
Annual Sum or Average | 24.51 | 20.80 | 18.94 | 4.12 | 16.04 | 92.16 | 164.97 | 0.01 |
Minimum of Months | 19.42 | 15.96 | 13.59 | 2.86 | 9.49 | 57.21 | 134.94 | 0.00 |
Maximum of Months | 28.13 | 24.38 | 23.03 | 5.59 | 20.36 | 124.71 | 212.67 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.90 | 02-JAN-14:20 | 24.35 | 22.57 | 2.37 | 19.46 | 142.33 | 666.50 |
February | 29.40 | 11-FEB-13:00 | 24.15 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 29.40 | 13-MAR-15:00 | 22.41 | 19.40 | 6.20 | 21.27 | 178.00 | 499.00 |
April | 32.20 | 17-APR-14:00 | 19.76 | 12.80 | 5.20 | 21.27 | 367.00 | 219.50 |
May | 34.40 | 22-MAY-12:00 | 23.24 | 18.30 | 5.70 | 25.99 | 382.50 | 457.50 |
June | 32.20 | 11-JUN-12:00 | 23.83 | 20.60 | 3.60 | 23.15 | 181.50 | 762.50 |
July | 35.60 | 29-JUL-15:00 | 24.39 | 20.00 | 3.60 | 25.66 | 281.50 | 374.50 |
August | 33.90 | 23-AUG-12:00 | 25.44 | 22.20 | 5.70 | 24.50 | 261.50 | 640.00 |
September | 32.20 | 08-SEP-14:00 | 23.42 | 20.00 | 2.10 | 21.61 | 221.50 | 576.00 |
October | 32.20 | 09-OCT-10:00 | 23.83 | 20.60 | 3.10 | 25.16 | 286.50 | 457.50 |
November | 30.00 | 17-NOV-14:00 | 22.20 | 18.90 | 4.10 | 19.35 | 178.50 | 412.50 |
December | 28.90 | 10-DEC-14:20 | 22.91 | 20.40 | 7.87 | 19.82 | 162.67 | 585.17 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 19.76 | 12.80 | 2.10 | 19.35 | 142.33 | 219.50 | |
Maximum of Months | 35.60 | 25.44 | 22.57 | 7.87 | 25.99 | 382.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 25-JAN-04:00 | 4.59 | -1.7 | 3.10 | -7.3 | 0.00 | 0.00 |
February | 5.00 | 04-FEB-06:00 | 1.99 | -2.8 | 5.70 | -11.9 | 0.00 | 0.00 |
March | 6.70 | 16-MAR-04:00 | 4.49 | 1.70 | 4.60 | -9.2 | 0.00 | 0.00 |
April | 14.40 | 02-APR-05:49 | 13.38 | 12.70 | 1.60 | 0.69 | 0.00 | 0.00 |
May | 20.60 | 01-MAY-04:00 | 19.45 | 18.90 | 1.00 | 7.95 | 0.00 | 0.00 |
June | 22.80 | 05-JUN-14:00 | 20.57 | 19.40 | 2.10 | 18.46 | 245.00 | 55.00 |
July | 22.80 | 02-JUL-15:00 | 21.59 | 21.10 | 4.60 | 20.92 | 155.00 | 8.50 |
August | 22.20 | 12-AUG-06:00 | 21.85 | 21.70 | 2.60 | 20.40 | 65.50 | 0.00 |
September | 22.20 | 05-SEP-05:00 | 21.37 | 21.10 | 2.60 | 13.54 | 0.00 | 0.00 |
October | 21.10 | 28-OCT-02:00 | 20.29 | 20.00 | 2.60 | 8.54 | 0.00 | 0.00 |
November | 10.00 | 27-NOV-02:00 | 8.82 | 7.80 | 3.10 | -4.6 | 0.00 | 0.00 |
December | 7.80 | 15-DEC-05:40 | 5.61 | 3.13 | 6.37 | -7.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.00 | 1.99 | -2.8 | 1.00 | -11.9 | 0.00 | 0.00 | |
Maximum of Months | 22.80 | 21.85 | 21.70 | 6.37 | 20.92 | 245.00 | 55.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.83 | 02-JAN-13:00 | 28.90 | 23.30 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 24.15 | 11-FEB-13:00 | 29.40 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 23.83 | 14-MAR-09:00 | 26.70 | 22.80 | 11.30 | 19.52 | 243.50 | 478.00 |
April | 24.58 | 01-APR-15:00 | 28.30 | 23.30 | 3.60 | 16.30 | 93.50 | 759.50 |
May | 26.05 | 28-MAY-14:00 | 28.90 | 25.00 | 5.20 | 25.66 | 289.00 | 98.50 |
June | 26.06 | 28-JUN-11:00 | 28.90 | 25.00 | 1.50 | 22.98 | 404.50 | 373.50 |
July | 26.39 | 12-JUL-10:00 | 30.60 | 25.00 | 4.60 | 23.82 | 287.50 | 574.00 |
August | 26.46 | 21-AUG-15:00 | 32.20 | 24.40 | 3.60 | 24.50 | 205.50 | 366.00 |
September | 26.31 | 22-SEP-16:00 | 30.00 | 25.00 | 6.20 | 28.91 | 54.00 | 21.00 |
October | 26.52 | 01-OCT-11:00 | 29.40 | 25.60 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 25.31 | 04-NOV-13:00 | 27.80 | 24.40 | 2.10 | 26.48 | 199.00 | 3.00 |
December | 24.31 | 24-DEC-14:00 | 27.20 | 23.30 | 2.10 | 23.66 | 201.50 | 114.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.83 | 26.70 | 22.20 | 1.50 | 16.30 | 54.00 | 0.00 | |
Maximum of Months | 26.52 | 32.20 | 25.60 | 11.30 | 28.91 | 404.50 | 759.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.30 | 02-JAN-13:00 | 28.90 | 24.83 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 22.80 | 11-FEB-16:19 | 27.60 | 24.09 | 5.70 | 18.94 | 101.33 | 565.33 |
March | 22.80 | 14-MAR-09:20 | 25.57 | 23.60 | 9.63 | 22.18 | 176.17 | 527.17 |
April | 23.30 | 01-APR-14:00 | 27.80 | 24.57 | 5.70 | 15.76 | 108.00 | 831.00 |
May | 25.00 | 28-MAY-12:00 | 27.80 | 25.74 | 6.70 | 22.98 | 249.50 | 244.50 |
June | 25.00 | 06-JUN-18:00 | 27.20 | 25.59 | 3.60 | 23.99 | 17.50 | 0.00 |
July | 25.00 | 12-JUL-03:00 | 27.20 | 25.59 | 1.50 | 19.70 | 0.00 | 0.00 |
August | 25.60 | 21-AUG-11:00 | 28.90 | 26.35 | 2.60 | 23.15 | 567.00 | 173.50 |
September | 25.00 | 22-SEP-00:00 | 27.80 | 25.31 | 3.60 | 20.92 | 0.00 | 0.00 |
October | 25.60 | 01-OCT-11:00 | 29.40 | 26.52 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 24.40 | 05-NOV-01:19 | 26.10 | 24.93 | 2.03 | 16.37 | 0.00 | 0.00 |
December | 23.90 | 24-DEC-08:00 | 23.90 | 23.90 | 2.60 | 17.75 | 168.50 | 167.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.80 | 23.90 | 23.60 | 1.50 | 15.76 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 29.40 | 26.52 | 9.63 | 28.43 | 567.00 | 831.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.73 | 28.77 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.06 | 35.04 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 26.11 | 42.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.63 | 49.05 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.20 | 48.15 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 30.41 | 45.99 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.58 | 45.60 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.50 | 40.49 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 27.97 | 35.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 26.40 | 29.31 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.21 | 26.63 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 27.83 | 39.80 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.73 | 26.63 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.744758E+09 | -611941347.4 | 0.00 | 0.00 | 744.00 | 0.00 | -132816266.5 | 58.99 | 0.00 | 0.00 |
February | 0.677045E+09 | -556841166.8 | 0.00 | 0.00 | 672.00 | 0.00 | -120203374.1 | 58.99 | 0.00 | 0.00 |
March | 0.763397E+09 | -630611467.6 | 0.00 | 0.00 | 744.00 | 0.00 | -132785919.0 | 58.99 | 0.00 | 0.00 |
April | 0.686081E+09 | -558841784.3 | 0.00 | 0.00 | 720.00 | 0.00 | -127239509.0 | 58.99 | 0.00 | 0.00 |
May | 0.683181E+09 | -552218467.7 | 0.00 | 0.00 | 744.00 | 0.00 | -130962799.7 | 58.99 | 0.00 | 0.00 |
June | 0.654993E+09 | -527948055.5 | 0.00 | 0.00 | 720.00 | 0.00 | -127045098.7 | 58.99 | 0.00 | 0.00 |
July | 0.631353E+09 | -501269170.5 | 0.00 | 0.00 | 744.00 | 0.00 | -130084272.8 | 58.99 | 0.00 | 0.00 |
August | 0.676138E+09 | -544832400.1 | 0.00 | 0.00 | 744.00 | 0.00 | -131305329.0 | 58.99 | 0.00 | 0.00 |
September | 0.652270E+09 | -525949404.9 | 0.00 | 0.00 | 720.00 | 0.00 | -126320526.8 | 58.99 | 0.00 | 0.00 |
October | 0.684748E+09 | -554351497.8 | 0.00 | 0.00 | 744.00 | 0.00 | -130396367.9 | 58.99 | 0.00 | 0.00 |
November | 0.686654E+09 | -559014592.4 | 0.00 | 0.00 | 720.00 | 0.00 | -127639486.0 | 58.99 | 0.00 | 0.00 |
December | 0.735331E+09 | -603019761.3 | 0.00 | 0.00 | 744.00 | 0.00 | -132310789.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.827595E+10 | -0.672684E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.154911E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.631353E+09 | -630611467.6 | 0.00 | 0.00 | 672.00 | 0.00 | -132816266.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.763397E+09 | -501269170.5 | 0.00 | 0.00 | 744.00 | 0.00 | -120203374.1 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 287.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 304.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 362.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 357.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 389.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 388.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 403.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 348.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 349.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 323.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 314.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 282.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4111.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 282.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 403.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 20486158.20 | 4557.99 | 25-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 25652869.85 | 29486.83 | 04-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 33353466.29 | 5674.57 | 16-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3652876.66 | 1706.42 | 13-NOV-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 31991657.33 | 6010.21 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33353466.29 | 29486.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.821261E+10 | 0.637825E+10 | 34524.16 | 02-JAN-00:01 | 20701.02 | 0.00 |
February | 0.00 | 0.00 | 0.930267E+10 | 0.721256E+10 | 33418.79 | 13-FEB-00:02 | 18983.32 | 0.00 |
March | 0.00 | 0.00 | 0.124577E+11 | 0.944786E+10 | 35674.18 | 06-MAR-00:01 | 18744.70 | 0.00 |
April | 0.00 | 0.00 | 0.155248E+11 | 0.119419E+11 | 34167.80 | 16-APR-23:01 | 22363.21 | 0.00 |
May | 0.00 | 0.00 | 0.206370E+11 | 0.148033E+11 | 35482.23 | 29-MAY-23:01 | 19082.30 | 0.00 |
June | 0.00 | 0.00 | 0.224238E+11 | 0.154433E+11 | 36347.91 | 18-JUN-23:01 | 17678.44 | 0.00 |
July | 0.00 | 0.00 | 0.227500E+11 | 0.160034E+11 | 35555.59 | 02-JUL-23:01 | 20739.18 | 0.00 |
August | 0.00 | 0.00 | 0.239214E+11 | 0.164630E+11 | 35979.25 | 06-AUG-23:01 | 20162.35 | 0.00 |
September | 0.00 | 0.00 | 0.214470E+11 | 0.148993E+11 | 35383.14 | 24-SEP-23:01 | 20852.18 | 0.00 |
October | 0.00 | 0.00 | 0.191198E+11 | 0.135999E+11 | 36007.54 | 01-OCT-23:02 | 16905.52 | 0.00 |
November | 0.00 | 0.00 | 0.145224E+11 | 0.103460E+11 | 35849.49 | 05-NOV-23:01 | 19153.73 | 0.00 |
December | 0.00 | 0.00 | 0.937033E+10 | 0.717130E+10 | 36347.91 | 26-DEC-00:01 | 16903.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.199689E+12 | 0.143710E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.821261E+10 | 0.637825E+10 | 33418.79 | 16903.46 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.239214E+11 | 0.164630E+11 | 36347.91 | 22363.21 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.177016E+11 | 0.135414E+11 | 89175.37 | 01-JAN-13:23 | 66311.93 | 0.00 |
February | 0.00 | 0.00 | 0.223016E+11 | 0.172452E+11 | 131090.75 | 19-FEB-14:02 | 92234.69 | 0.00 |
March | 0.00 | 0.00 | 0.325419E+11 | 0.245978E+11 | 129315.78 | 26-MAR-15:32 | 96408.33 | 0.00 |
April | 0.00 | 0.00 | 0.485172E+11 | 0.373874E+11 | 131700.12 | 23-APR-15:32 | 93610.95 | 0.00 |
May | 0.00 | 0.00 | 0.698332E+11 | 0.503373E+11 | 136484.81 | 28-MAY-12:53 | 83417.70 | 0.00 |
June | 0.00 | 0.00 | 0.791196E+11 | 0.552975E+11 | 136336.62 | 18-JUN-12:32 | 83989.42 | 0.00 |
July | 0.00 | 0.00 | 0.859622E+11 | 0.618586E+11 | 134394.34 | 30-JUL-17:42 | 89171.50 | 0.00 |
August | 0.00 | 0.00 | 0.823097E+11 | 0.571915E+11 | 134824.81 | 13-AUG-13:43 | 85964.96 | 0.00 |
September | 0.00 | 0.00 | 0.757657E+11 | 0.531466E+11 | 132983.83 | 22-SEP-17:42 | 85261.71 | 0.00 |
October | 0.00 | 0.00 | 0.607618E+11 | 0.430065E+11 | 133678.37 | 29-OCT-14:13 | 86754.50 | 0.00 |
November | 0.00 | 0.00 | 0.380565E+11 | 0.267709E+11 | 134423.48 | 23-NOV-14:32 | 87621.55 | 0.00 |
December | 0.00 | 0.00 | 0.219868E+11 | 0.163925E+11 | 134073.38 | 10-DEC-12:23 | 86601.63 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.634858E+12 | 0.456773E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.177016E+11 | 0.135414E+11 | 89175.37 | 66311.93 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.859622E+11 | 0.618586E+11 | 136484.81 | 96408.33 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.161302E+10 | 0.46 | 1554.96 | 02-JAN-07:20 | 0.92 |
February | 0.150687E+10 | 0.50 | 1554.96 | 01-FEB-07:25 | 0.93 |
March | 0.182224E+10 | 0.60 | 1554.96 | 01-MAR-13:00 | 0.93 |
April | 0.177667E+10 | 0.67 | 1554.96 | 01-APR-06:10 | 0.93 |
May | 0.193170E+10 | 0.69 | 1554.96 | 01-MAY-07:03 | 0.92 |
June | 0.196523E+10 | 0.72 | 1554.96 | 01-JUN-06:10 | 0.92 |
July | 0.191203E+10 | 0.69 | 1554.96 | 01-JUL-06:40 | 0.93 |
August | 0.204686E+10 | 0.73 | 1554.96 | 01-AUG-06:20 | 0.92 |
September | 0.188647E+10 | 0.71 | 1554.96 | 01-SEP-06:50 | 0.92 |
October | 0.183617E+10 | 0.67 | 1554.96 | 02-OCT-06:30 | 0.92 |
November | 0.167580E+10 | 0.61 | 1554.96 | 01-NOV-06:05 | 0.93 |
December | 0.163879E+10 | 0.49 | 1554.96 | 01-DEC-08:70 | 0.93 |
Annual Sum or Average | 0.216119E+11 | 0.63 | |||
Minimum of Months | 0.150687E+10 | 0.46 | 1554.96 | 0.92 | |
Maximum of Months | 0.204686E+10 | 0.73 | 1554.96 | 0.93 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.789125E+10 | 0.55 | 7922.82 | 21-JAN-10:45 | 1.40 |
February | 0.729754E+10 | 0.57 | 7922.82 | 01-FEB-10:50 | 1.40 |
March | 0.865515E+10 | 0.64 | 7922.82 | 01-MAR-09:33 | 1.40 |
April | 0.840036E+10 | 0.79 | 7922.82 | 01-APR-07:10 | 1.39 |
May | 0.925205E+10 | 0.99 | 7922.82 | 01-MAY-07:10 | 1.39 |
June | 0.957663E+10 | 1.15 | 7922.82 | 01-JUN-06:57 | 1.39 |
July | 0.962965E+10 | 1.17 | 7922.82 | 01-JUL-06:20 | 1.39 |
August | 0.994042E+10 | 1.14 | 7922.82 | 01-AUG-06:40 | 1.39 |
September | 0.925372E+10 | 1.10 | 7922.82 | 02-SEP-06:15 | 1.39 |
October | 0.875473E+10 | 0.94 | 7922.82 | 02-OCT-06:20 | 1.38 |
November | 0.781179E+10 | 0.67 | 7922.82 | 01-NOV-07:45 | 1.39 |
December | 0.797834E+10 | 0.58 | 7922.82 | 18-DEC-11:47 | 1.40 |
Annual Sum or Average | 0.104442E+12 | 0.86 | |||
Minimum of Months | 0.729754E+10 | 0.55 | 7922.82 | 1.38 | |
Maximum of Months | 0.994042E+10 | 1.17 | 7922.82 | 1.40 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.378658E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.396978E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.509905E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.591044E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.748366E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.802007E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.814525E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.854516E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.769213E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.696672E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.552817E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.411374E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.752607E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.378658E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.854516E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.130127E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.137492E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.179764E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.224688E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.297070E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.327866E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.352788E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.342799E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.315831E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.265594E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.188103E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.143074E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.290520E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.130127E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.352788E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.161302E+10 | 0.821261E+10 | 20486158.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150687E+10 | 0.930267E+10 | 25652869.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182224E+10 | 0.124577E+11 | 33353466.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177667E+10 | 0.155248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.193170E+10 | 0.206370E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.196523E+10 | 0.224238E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.191203E+10 | 0.227500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.204686E+10 | 0.239214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.188647E+10 | 0.214470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.183617E+10 | 0.191198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167580E+10 | 0.145224E+11 | 3652876.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163879E+10 | 0.937033E+10 | 31991657.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216119E+11 | 0.199689E+12 | 0.115137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150687E+10 | 0.821261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.204686E+10 | 0.239214E+11 | 33353466.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.789125E+10 | 0.177016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.729754E+10 | 0.223016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.865515E+10 | 0.325419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.840036E+10 | 0.485172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.925205E+10 | 0.698332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.957663E+10 | 0.791196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.962965E+10 | 0.859622E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.994042E+10 | 0.823097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.925372E+10 | 0.757657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.875473E+10 | 0.607618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.781179E+10 | 0.380565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.797834E+10 | 0.219868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104442E+12 | 0.634858E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.729754E+10 | 0.177016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.994042E+10 | 0.859622E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.161302E+10 | 0.00 | 0.00 | 0.00 | 0.217356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150687E+10 | 0.00 | 0.00 | 0.00 | 0.246291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182224E+10 | 0.00 | 0.00 | 0.00 | 0.327681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177667E+10 | 0.00 | 0.00 | 0.00 | 0.413377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.193170E+10 | 0.00 | 0.00 | 0.00 | 0.555196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.196523E+10 | 0.00 | 0.00 | 0.00 | 0.605484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.191203E+10 | 0.00 | 0.00 | 0.00 | 0.623321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.204686E+10 | 0.00 | 0.00 | 0.00 | 0.649830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.188647E+10 | 0.00 | 0.00 | 0.00 | 0.580566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.183617E+10 | 0.00 | 0.00 | 0.00 | 0.513056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167580E+10 | 0.00 | 0.00 | 0.00 | 0.385237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163879E+10 | 0.00 | 0.00 | 0.00 | 0.247494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216119E+11 | 0.00 | 0.00 | 0.00 | 0.536489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150687E+10 | 0.00 | 0.00 | 0.00 | 0.217356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.204686E+10 | 0.00 | 0.00 | 0.00 | 0.649830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.789125E+10 | 0.00 | 0.00 | 0.00 | 0.512150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.729754E+10 | 0.00 | 0.00 | 0.00 | 0.645167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.865515E+10 | 0.00 | 0.00 | 0.00 | 0.932126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.840036E+10 | 0.00 | 0.00 | 0.00 | 0.140685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.925205E+10 | 0.00 | 0.00 | 0.00 | 0.204549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.957663E+10 | 0.00 | 0.00 | 0.00 | 0.232100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.962965E+10 | 0.00 | 0.00 | 0.00 | 0.256491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.994042E+10 | 0.00 | 0.00 | 0.00 | 0.243395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.925372E+10 | 0.00 | 0.00 | 0.00 | 0.223294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.875473E+10 | 0.00 | 0.00 | 0.00 | 0.178046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.781179E+10 | 0.00 | 0.00 | 0.00 | 0.109985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.797834E+10 | 0.00 | 0.00 | 0.00 | 0.632903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104442E+12 | 0.00 | 0.00 | 0.00 | 0.186078E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.729754E+10 | 0.00 | 0.00 | 0.00 | 0.512150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.994042E+10 | 0.00 | 0.00 | 0.00 | 0.256491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 87514690.72 | 0.479617E+09 | 0.00 | 6999060.36 | 63371.91 | 12767980.28 | 0.297883E+09 | 0.00 | 0.14 |
February | 62052730.76 | 0.557764E+09 | 0.00 | 5049199.57 | 257598.91 | 11906684.40 | 0.119303E+09 | 0.00 | 0.15 |
March | 68201128.05 | 0.799534E+09 | 0.00 | 6590766.40 | 175027.00 | 20950392.34 | 0.192529E+09 | 0.00 | 0.16 |
April | 3132003.28 | 0.128413E+10 | 0.00 | 2610732.88 | 0.00 | 0.00 | 33573152.89 | 0.00 | 0.16 |
May | 0.00 | 0.225689E+10 | 0.00 | 378702.81 | 0.00 | 0.00 | 135131.80 | 0.00 | 0.17 |
June | 0.00 | 0.308562E+10 | 0.00 | 102069.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
July | 0.00 | 0.339062E+10 | 0.00 | 58572.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
August | 0.00 | 0.345370E+10 | 0.00 | 52197.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
September | 0.00 | 0.301788E+10 | 0.00 | 93758.97 | 0.00 | 0.00 | 30608.93 | 0.00 | 0.17 |
October | 0.00 | 0.232814E+10 | 0.00 | 313999.12 | 0.00 | 0.00 | 129228.59 | 0.00 | 0.16 |
November | 12210484.20 | 0.152564E+10 | 0.00 | 1566988.22 | 284962.98 | 3375506.54 | 14091473.68 | 0.00 | 0.15 |
December | 75458186.87 | 0.646554E+09 | 0.00 | 6087945.49 | 294020.92 | 17032356.30 | 0.252857E+09 | 0.00 | 0.14 |
Annual Sum or Average | 0.308569E+09 | 0.228261E+11 | 0.00 | 29903994.02 | 1074981.72 | 66032919.86 | 0.910532E+09 | 0.00 | 0.16 |
Minimum of Months | 0.00 | 0.479617E+09 | 0.00 | 52197.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 87514690.72 | 0.345370E+10 | 0.00 | 6999060.36 | 294020.92 | 20950392.34 | 0.297883E+09 | 0.00 | 0.18 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105910E+10 | 0.878627E+09 | 0.00 | 16843433.73 | 2240.47 | 0.00 | 0.142589E+10 | 0.00 | 0.20 |
February | 0.693413E+09 | 0.106920E+10 | 0.00 | 13936904.05 | 0.00 | 0.00 | 0.661276E+09 | 0.00 | 0.20 |
March | 0.759919E+09 | 0.173826E+10 | 0.00 | 21897707.56 | 0.00 | 0.00 | 0.995197E+09 | 0.00 | 0.22 |
April | 73072159.32 | 0.343082E+10 | 0.00 | 8984826.78 | 0.00 | 0.00 | 0.328176E+09 | 0.00 | 0.22 |
May | 4838782.48 | 0.682395E+10 | 0.00 | 625659.79 | 0.00 | 0.00 | 22388580.37 | 0.00 | 0.23 |
June | 0.00 | 0.102835E+11 | 0.00 | 38523.56 | 0.00 | 0.00 | 2080048.01 | 0.00 | 0.25 |
July | 0.00 | 0.121571E+11 | 0.00 | 6615.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.115370E+11 | 0.00 | 26832.91 | 0.00 | 0.00 | 42348.90 | 0.00 | 0.25 |
September | 0.00 | 0.100436E+11 | 0.00 | 41021.17 | 0.00 | 0.00 | 2653409.06 | 0.00 | 0.24 |
October | 1860142.12 | 0.690949E+10 | 0.00 | 793686.20 | 0.00 | 0.00 | 41889303.42 | 0.00 | 0.22 |
November | 0.186371E+09 | 0.400199E+10 | 0.00 | 5928809.34 | 43704.20 | 0.00 | 0.247689E+09 | 0.00 | 0.20 |
December | 0.101803E+10 | 0.140054E+10 | 0.00 | 13044642.06 | 1687940.90 | 0.00 | 0.124904E+10 | 0.00 | 0.20 |
Annual Sum or Average | 0.379660E+10 | 0.702741E+11 | 0.00 | 82168663.04 | 1733885.57 | 0.00 | 0.497631E+10 | 0.00 | 0.22 |
Minimum of Months | 0.00 | 0.878627E+09 | 0.00 | 6615.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.105910E+10 | 0.121571E+11 | 0.00 | 21897707.56 | 1687940.90 | 0.00 | 0.142589E+10 | 0.00 | 0.25 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.608445E+12 | 0.846886E+11 | 0.00 | 0.717266E+10 | 0.332201E+11 |
February | 0.641162E+12 | 0.120883E+12 | 0.00 | 0.406136E+10 | 0.405315E+11 |
March | 0.879993E+12 | 0.183934E+12 | 0.00 | 0.277635E+10 | 0.576149E+11 |
April | 0.953472E+12 | 0.236166E+12 | 0.00 | -0.345695E+10 | 0.822442E+11 |
May | 0.923644E+12 | 0.247436E+12 | 0.00 | -0.113073E+11 | 0.116477E+12 |
June | 0.835247E+12 | 0.248692E+12 | 0.00 | -0.181512E+11 | 0.130808E+12 |
July | 0.912122E+12 | 0.280124E+12 | 0.00 | -0.212706E+11 | 0.140595E+12 |
August | 0.100866E+13 | 0.214592E+12 | 0.00 | -0.205508E+11 | 0.137069E+12 |
September | 0.745529E+12 | 0.212085E+12 | 0.00 | -0.181956E+11 | 0.125348E+12 |
October | 0.753465E+12 | 0.156298E+12 | 0.00 | -0.126325E+11 | 0.102817E+12 |
November | 0.555183E+12 | 0.115068E+12 | 0.00 | -0.406868E+10 | 0.674317E+11 |
December | 0.572933E+12 | 0.915625E+11 | 0.00 | 0.445118E+10 | 0.401777E+11 |
Annual Sum or Average | 0.938985E+13 | 0.219153E+13 | 0.00 | -0.911720E+11 | 0.107433E+13 |
Minimum of Months | 0.555183E+12 | 0.846886E+11 | 0.00 | -0.212706E+11 | 0.332201E+11 |
Maximum of Months | 0.100866E+13 | 0.280124E+12 | 0.00 | 0.717266E+10 | 0.140595E+12 |