Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2023-10-16 10:41:49
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 660.59 | 136.62 | 136.62 |
Net Site Energy | 660.59 | 136.62 | 136.62 |
Total Source Energy | 1620.42 | 335.13 | 335.13 |
Net Source Energy | 1620.42 | 335.13 | 335.13 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 226.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 152.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 92.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 25.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 434.15 | 226.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 226.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 152.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 92.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 25.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 226.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 0.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 152.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 92.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 25.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 26.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 10.87 | 46.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 89.79 | 46.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 10.87 | 46.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 89.79 | 46.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 434.150 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 434.150 | 100.00 |
Total On-Site and Utility Electric Sources | 434.150 | 100.00 |
Total Electricity End Uses | 434.150 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 60.33 |
Time Setpoint Not Met During Occupied Cooling | 0.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2592.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 68.38 |
Skylight-Roof Ratio [%] | 1.49 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.8432 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 10.2257 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 6.2431 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.6162 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.6162 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.8432 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 10.2257 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 6.2431 | 46.45 | 2.5587 | |
Total | 4835.13 | 7.6162 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 7.6162 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 7.6162 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-DEC-08:09 | 10-JAN-06:19 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 112746.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12813.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2423.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1648.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 33907.19 | 112746.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 112746.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 12813.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2423.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1648.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 245.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 482.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 293.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 82.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 82.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1374.95 | 245.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 50.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 99.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 16.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 284.37 | 50.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 50.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 99.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 16.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 284.37 | 50.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.989552 |
ZONE2 FINE STORAGE DIRECT AIR | 1.96 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 1.72 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 1.72 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 69725.94 |
PSZ-OFFICE HEATING COIL | 25594.48 |
PSZ-FINE STORAGE HEATING COIL | 67532.13 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 69725.94 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.989552 | 0.989552 | 0.989552 | 0.989552 | 0.989552 | 0.989552 | 1.00 | 1.00 | 0.989552 |
PSZ-FINE STORAGE | 1.96 | 1.96 | 1.96 | 1.96 | 1.96 | 1.96 | 1.00 | 1.00 | 1.96 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 0.989552 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 1.96 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.989552 | 1095.59 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.96 | 2100.37 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.989552 | 0.989552 | 0.989552 | 0.989552 | 16380.61 | 25594.48 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 1.96 | 1.96 | 1.96 | 1.30 | 37664.64 | 67532.13 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.989550 | 0.494776 | 0.659700 | 16380.61 | 8190.31 | 0.800660 | 0.800660 |
PSZ-FINE STORAGE COOLING COIL | 1.96 | 0.981438 | 1.31 | 37664.64 | 18832.32 | 0.793170 | 0.793170 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.843 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.917 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 10.226 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.226 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 6.243 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 8.802 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2568.536 | 10.843 | 201.474 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2568.536 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 14248.589 | 10.226 | 474.953 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 14248.589 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 20008.023 | 6.243 | 289.971 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20008.023 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2163 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.4974 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.3694 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.6534 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.6534 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.622 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.010 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.608 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.431 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.431 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.18741198E-13 | -0.13599760E-18 | 0.18147593E-18 | 0.0000000 |
2 | 1 | -5.2160601 | 0.51384690E-04 | -0.74050972E-04 | 0.35929797E-14 |
3 | 0 | 5.4323994 | 0.21628790 | 0.21641333 | |
4 | 2 | 0.53330648E-11 | 0.17872838E-15 | 0.22136589E-15 | 0.0000000 |
5 | 1 | -5.2159880 | 0.41449123E-04 | -0.32205733E-04 | 0.68736940E-11 |
6 | 0 | 5.7134214 | 0.49739196 | 0.49746561 | |
7 | 4 | 0.80462617E-12 | 0.82840410E-16 | -0.20078756E-14 | 0.11271485E-15 |
8 | 3 | -0.39242815E-03 | 0.26180773E-06 | -0.56999769E-04 | 0.15438257E-12 |
9 | 2 | 1.7577325 | 0.56772723E-02 | 1.1542901 | -0.75235290E-04 |
10 | 1 | -7.1048256 | 0.14632850 | -17.186369 | 0.33689683 |
11 | 0 | 5.5924660 | 0.92974441E-01 | 16.277116 | |
12 | 4 | 0.74747876E-12 | 0.20825084E-15 | -0.25659737E-14 | 0.12362927E-15 |
13 | 3 | -0.37328678E-03 | 0.45238042E-06 | -0.54038165E-04 | 0.14344535E-12 |
14 | 2 | 1.7123825 | 0.10013958E-01 | 1.1198054 | -0.71564441E-04 |
15 | 1 | -7.1648294 | 0.26145347 | -16.966117 | 0.32817431 |
16 | 0 | 5.8918369 | 0.16754891 | 16.285382 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.25659737E-14 | 0.20825084E-15 | 0.74747876E-12 | 0.12362927E-15 |
85 | 3 | -0.54038165E-04 | 0.45238042E-06 | -0.37328678E-03 | 0.14344535E-12 |
86 | 2 | 1.1198054 | 0.10013958E-01 | 1.7123825 | -0.71564441E-04 |
87 | 1 | -16.966117 | 0.26145347 | -7.1648294 | 0.32817431 |
88 | 0 | 16.285382 | 0.16754891 | 5.8918369 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.419_SHGC_SOUTH_0.4 | 34 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.419_SHGC_NORTH_0.4 | 35 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.419_SHGC_EAST_0.4 | 36 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.419_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
5 | SKYLIGHT_U_0.5_SHGC_0.4 | 38 | 1 | VerySmooth | 2.843 | 2.843 | 1.000 | 0.401 | ||
6 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | 39 | 1 | VerySmooth | 5.556 | 5.556 | 1.000 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.31435 | 0.46556 | 0.46556 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 0.10078 | 0.10078 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.14909 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | CurtainWall | 2.775 | 0.408 | 0.402 |
2 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.268 | 0.549 | 0.552 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.710 | 8.455E-004 | 5.523E-004 | 0.277 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.8381E-005 |
2 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5172E-004 |
3 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.7156E-005 |
4 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6875E-004 |
5 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.6500E-005 |
6 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.0058E-004 |
7 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5724E-005 |
8 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.5867E-004 |
9 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7141E-004 |
10 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.9799E-004 |
11 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4174E-004 |
12 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.2784E-004 |
13 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5769E-004 |
14 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6612E-004 |
15 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3414E-004 |
16 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4540E-004 |
17 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.7702E-004 |
18 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5117E-004 |
19 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1282E-004 |
20 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6765E-004 |
21 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.7738E-004 |
22 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1594E-004 |
23 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8792E-004 |
24 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6675E-005 |
25 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.3672E-004 |
26 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9545E-005 |
27 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.6689E-004 |
28 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.7042E-005 |
29 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0385E-003 |
30 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2447E-005 |
31 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3392E-003 |
32 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0724E-005 |
33 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0273E-004 |
34 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4802E-005 |
35 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0705E-004 |
36 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.8136E-005 |
37 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.2694E-004 |
38 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8781E-005 |
39 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9718E-004 |
40 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6272E-005 |
41 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.4543E-004 |
42 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4418E-005 |
43 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.7696E-004 |
44 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5905E-005 |
45 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.2882E-004 |
46 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.3905E-005 |
47 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7955E-004 |
48 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4789E-005 |
49 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.9451E-004 |
50 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8837E-005 |
51 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0790E-003 |
52 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1687E-005 |
53 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.5743E-004 |
54 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4558E-005 |
55 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3679E-004 |
56 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4861E-005 |
57 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5785E-003 |
58 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8000E-005 |
59 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7555E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.5429E-005 |
61 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7202E-003 |
62 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0864E-005 |
63 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1133E-003 |
64 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6508E-005 |
65 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4631E-003 |
66 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3664E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3505E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5886E-004 |
69 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3656E-003 |
70 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.0526E-005 |
71 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5808E-003 |
72 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1684E-005 |
73 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1575E-004 |
74 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.4446E-004 |
75 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.0901E-004 |
76 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.2150E-004 |
77 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.0022E-004 |
78 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5427E-004 |
79 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6286E-003 |
80 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1734E-005 |
81 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1899E-004 |
82 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6294E-004 |
83 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7855E-004 |
84 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.2703E-004 |
85 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0496E-004 |
86 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.3155E-004 |
87 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3102E-004 |
88 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8162E-004 |
89 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.7608E-005 |
90 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4526E-003 |
91 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.4139E-005 |
92 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6584E-003 |
93 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.3378E-005 |
94 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4005E-003 |
95 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0760E-004 |
96 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8446E-004 |
97 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.3004E-005 |
98 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6061E-003 |
99 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.7998E-005 |
100 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5452E-003 |
101 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9057E-005 |
102 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4782E-003 |
103 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7398E-005 |
104 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.1825E-003 |
105 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0922E-005 |
106 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6465E-004 |
107 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.6432E-005 |
108 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0613E-004 |
109 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.7771E-005 |
110 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0842E-003 |
111 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5431E-005 |
112 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2422E-003 |
113 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2172E-005 |
114 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.8737E-005 |
115 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4832E-005 |
116 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.4496E-005 |
117 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2555E-005 |
118 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.8147E-005 |
119 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1321E-005 |
120 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.9767E-005 |
121 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4771E-005 |
122 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1587E-005 |
123 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.1482E-005 |
124 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.2141E-005 |
125 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5153E-005 |
126 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0460E-005 |
127 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4814E-005 |
128 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2243E-005 |
129 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0778E-005 |
130 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0393E-005 |
131 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4158E-005 |
132 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8721E-005 |
133 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4304E-005 |
134 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0996E-005 |
135 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1298E-005 |
136 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2681E-005 |
137 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7866E-004 |
138 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2795E-004 |
139 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2363E-004 |
140 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6401E-004 |
141 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7853E-004 |
142 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4325E-004 |
143 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5955E-005 |
144 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2983E-005 |
145 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0259E-004 |
146 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7842E-004 |
147 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0671E-004 |
148 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8633E-004 |
149 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3629E-005 |
150 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1988E-004 |
151 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1757E-005 |
152 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1077E-005 |
153 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3689E-004 |
154 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8526E-005 |
155 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5091E-004 |
156 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8601E-005 |
157 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0320E-004 |
158 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7986E-005 |
159 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1734E-005 |
160 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2731E-005 |
161 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3396E-004 |
162 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3984E-005 |
163 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.3010E-004 |
164 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.8123E-005 |
165 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0216E-004 |
166 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2859E-005 |
167 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5935E-005 |
168 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1887E-005 |
169 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4490E-004 |
170 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9201E-004 |
171 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4600E-004 |
172 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2006E-003 |
173 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5472E-004 |
174 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9888E-004 |
175 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6979E-005 |
176 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3777E-004 |
177 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5397E-004 |
178 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6777E-004 |
179 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3303E-004 |
180 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1472E-004 |
181 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4812E-004 |
182 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9552E-004 |
183 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0720E-004 |
184 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4148E-004 |
185 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0107E-004 |
186 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0248E-004 |
187 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5941E-004 |
188 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0444E-004 |
189 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0677E-004 |
190 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0004E-004 |
191 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0708E-004 |
192 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6592E-005 |
193 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9136E-004 |
194 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1566E-005 |
195 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0446E-004 |
196 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0863E-005 |
197 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7431E-004 |
198 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2732E-005 |
199 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6898E-005 |
200 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5662E-005 |
201 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2686E-003 |
202 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1636E-004 |
203 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4231E-003 |
204 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1325E-004 |
205 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2939E-003 |
206 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3238E-004 |
207 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2032E-004 |
208 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0902E-005 |
209 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.8150E-004 |
210 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1581E-004 |
211 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0529E-003 |
212 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4257E-004 |
213 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1613E-003 |
214 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9728E-004 |
215 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2112E-004 |
216 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4671E-004 |
217 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4002E-004 |
218 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3346E-005 |
219 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4086E-004 |
220 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1679E-005 |
221 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8389E-004 |
222 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6732E-005 |
223 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7473E-004 |
224 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9066E-005 |
225 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9164E-004 |
226 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7307E-003 |
227 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8278E-004 |
228 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9735E-003 |
229 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4956E-004 |
230 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6919E-003 |
231 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7498E-004 |
232 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.5506E-004 |
233 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4379E-004 |
234 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3076E-005 |
235 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2612E-004 |
236 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0636E-005 |
237 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4956E-004 |
238 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7745E-005 |
239 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7446E-004 |
240 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1536E-005 |
241 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3634E-003 |
242 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1654E-004 |
243 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3257E-003 |
244 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0811E-004 |
245 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0802E-003 |
246 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4690E-004 |
247 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2227E-003 |
248 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1450E-004 |
249 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1907E-003 |
250 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3390E-004 |
251 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1214E-003 |
252 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0294E-004 |
253 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8942E-003 |
254 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.2875E-004 |
255 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2269E-003 |
256 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1533E-004 |
257 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1228E-004 |
258 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9934E-003 |
259 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9046E-004 |
260 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9550E-003 |
261 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0790E-004 |
262 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0029E-003 |
263 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7501E-004 |
264 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6479E-003 |
265 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9448E-004 |
266 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0774E-005 |
267 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7056E-004 |
268 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8037E-005 |
269 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7332E-004 |
270 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4817E-005 |
271 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7296E-004 |
272 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1506E-005 |
273 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8613E-004 |
274 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1280E-003 |
275 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5984E-004 |
276 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.5748E-004 |
277 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4380E-004 |
278 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6607E-003 |
279 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7351E-004 |
280 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5793E-003 |
281 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1839E-004 |
282 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0189E-004 |
283 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9999E-004 |
284 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1628E-005 |
285 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2590E-003 |
286 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2571E-004 |
287 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1889E-003 |
288 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1418E-004 |
289 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.9496E-004 |
290 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8008E-004 |
291 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7056E-004 |
292 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2857E-004 |
293 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1670E-003 |
294 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8539E-004 |
295 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1930E-003 |
296 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0887E-004 |
297 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3437E-004 |
298 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4180E-004 |
299 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1319E-004 |
300 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5437E-004 |
301 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3894E-004 |
302 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7801E-004 |
303 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7289E-004 |
304 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2588E-004 |
305 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6627E-004 |
306 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1574E-004 |
307 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9433E-004 |
308 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7977E-004 |
309 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8889E-004 |
310 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5371E-004 |
311 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0178E-004 |
312 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4028E-004 |
313 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3683E-005 |
314 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0754E-005 |
315 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0928E-005 |
316 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6642E-005 |
317 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6423E-005 |
318 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8023E-005 |
319 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4795E-005 |
320 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1676E-005 |
321 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3253E-004 |
322 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7270E-005 |
323 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1366E-004 |
324 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4689E-005 |
325 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5220E-004 |
326 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9604E-005 |
327 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7264E-004 |
328 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8999E-005 |
329 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9298E-005 |
330 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7820E-004 |
331 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6089E-005 |
332 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4316E-004 |
333 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7726E-005 |
334 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4706E-004 |
335 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5891E-005 |
336 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3195E-004 |
337 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6188E-004 |
338 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1758E-004 |
339 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3062E-004 |
340 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8425E-005 |
341 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3200E-004 |
342 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0754E-004 |
343 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0257E-004 |
344 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3913E-004 |
345 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6847E-005 |
346 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3577E-005 |
347 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5087E-005 |
348 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1413E-005 |
349 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2576E-005 |
350 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4592E-005 |
351 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5813E-005 |
352 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5594E-005 |
353 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6061E-004 |
354 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.1297E-005 |
355 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9282E-004 |
356 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2420E-005 |
357 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1121E-004 |
358 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.9004E-005 |
359 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0101E-004 |
360 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0338E-005 |
361 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5890E-004 |
362 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.3210E-005 |
363 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2920E-004 |
364 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6846E-005 |
365 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3693E-004 |
366 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.2041E-005 |
367 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0246E-004 |
368 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6189E-005 |
369 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 6.2293E-003 |
370 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 7.4317E-004 |
371 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.5889E-003 |
372 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.6902E-004 |
373 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.3184E-003 |
374 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.3428E-004 |
375 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 3.1458E-003 |
376 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.5232E-004 |
377 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 7.6385E-004 |
378 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 6.9674E-003 |
379 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 7.0931E-004 |
380 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.8765E-003 |
381 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.4768E-004 |
382 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.7641E-003 |
383 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.4603E-004 |
384 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.2309E-003 |
385 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 6.1079E-003 |
386 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 4.3630E-004 |
387 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 4.6158E-003 |
388 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.4398E-004 |
389 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.1020E-003 |
390 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.5543E-004 |
391 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.9456E-003 |
392 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.3643E-004 |
393 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.3756E-003 |
394 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.3724E-004 |
395 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.7505E-003 |
396 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.4448E-004 |
397 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.8537E-003 |
398 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.5489E-004 |
399 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.9455E-003 |
400 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.3643E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9917.18456 | 11900.62148 | 0.82463 | 0.98955 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 25.24733 | 8.40527E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 7727.58399 | 9273.10078 | 0.21908 | 0.26289 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -4.30000 | 2.65759E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 25235.59220 | 30282.71064 | 1.63573 | 1.96288 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.40000 | 8.40708E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 17808.96805 | 21370.76166 | 0.42563 | 0.51075 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -4.30000 | 2.65759E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 26.21800 | 8.40679E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 58104.95227 | 69725.94272 | 1.43496 | 1.72195 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 14269.23 | 0.98955 | 0.98955 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 9075.63 | 0.26289 | 0.26289 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 34389.24 | 1.96288 | 1.96288 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 25041.81 | 0.51075 | 0.51075 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98955 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.96288 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.72195 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 1.72195 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 69725.93874 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 69725.94272 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.98955 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.98955 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.98955 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.98955 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.98955 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.98955 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.96288 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.96288 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.96288 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.96288 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.96288 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.96288 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.98955 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.96288 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.98955 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.98955 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1095.59159 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.98955 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.98955 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.98955 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.98955 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.98955 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49478 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65970 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16380.61000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8190.30500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16380.61000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25594.47510 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 25594.47510 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.96288 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.96288 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2100.37080 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.96288 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.96288 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.96288 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.29550 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.96288 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.98144 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.30859 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 37664.64000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18832.32000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79317 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79317 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 37664.64000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 67532.12531 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 67532.12531 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 15612.8 | 12.15 | 11.88 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 36140.7 | 11.74 | 11.47 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1738581647 | 0.1714874924 | Pass | Pass | 2.7210017296 | 17.0281904426 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.3058310479 | 0.2837471481 | Pass | Pass | 1.2250728588 | 4.8896050211 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 8.4009801069E-005 | 2.2642705844E-004 | Pass | Pass | 6.5493637039E-002 | 7.2055613357E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7311.66 | 323.73 | 0.00 | 75.97 | 62.24 | 7773.66 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 42.00 | 35 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 40.00 | 22 | |||
Jun | 4.00 | 8 | |||
Jul | 5.00 | 4 | |||
Aug | 7.00 | 8 | |||
Sep | 17.00 | 10 | |||
Oct | 50.00 | 49 | |||
Nov | 69.00 | 59 | |||
Dec | 95.00 | 53 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.210 | 0.216 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.466 | 0.497 | 3204.84 | 3157.28 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.565 | 0.653 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.565 | 0.653 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.419_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.381 | 0.401 | 0.442 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.419_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.381 | 0.401 | 0.442 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.419_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.381 | 0.401 | 0.442 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.419_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.381 | 0.401 | 0.442 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_0.98_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.556 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 5.268 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 86.04 | 4.248 | 0.484 | 0.493 | |||||||||||||||||
North Total or Average | 6.51 | 2.381 | 0.401 | 0.442 | |||||||||||||||||
Non-North Total or Average | 79.53 | 4.401 | 0.490 | 0.497 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.8432 | 236.88 | 2568.54 | LightsWired | LTG_SCH_OFFICE | 52.33 | 168.00 | 44.17 | 0.0000 | Y | 21.30 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 10.2257 | 1393.41 | 14248.59 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 22.88 | 0.0000 | Y | 61.20 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 6.2431 | 3204.84 | 20008.02 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 18.60 | 0.0000 | Y | 69.85 |
Interior Lighting Total | 7.6162 | 4835.13 | 36825.15 | 152.34 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 14248.59 | 3562.15 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 14248.59 | 3562.15 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 20008.02 | 5002.01 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 20008.02 | 5002.01 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.29 | 2568.54 | 744.88 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.10 | 2568.54 | 256.85 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 125.92 | AstronomicalClock | - | 42.50 | 42.50 | 1.00 | |
EXTERIOR_LIGHTS_B | 6860.50 | AstronomicalClock | - | 83.54 | 71.23 | 91.73 | |
Exterior Lighting Total | 6986.42 | 92.73 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16380.61 | 13115.30 | 3265.31 | 0.80 | 4.12 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 37664.64 | 29874.46 | 7790.18 | 0.79 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 15612.8 | 12.15 | 11.88 | ||||
PSZ-FINE STORAGE COOLING COIL | 36140.7 | 11.74 | 11.47 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 69725.94 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 25594.48 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 67532.13 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 1.72 | 159.99 | 92.91 | 1.00 | 3.68 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 0.99 | 1095.59 | 1107.16 | 1.00 | 1.40 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 1.96 | 2100.37 | 1070.05 | 1.00 | 1.32 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9917.18 | 11900.62 | 50.24 | 0.825 | 0.990 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 23.90 | 23.90 | 0.00831 | 25.25 | 0.00841 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 25235.59 | 30282.71 | 21.73 | 1.636 | 1.963 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.70 | 26.70 | 0.00844 | 26.40 | 0.00841 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 0.00 | 29.45 | 0.00859 | 26.22 | 0.00841 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 7727.58 | 9273.10 | 39.15 | 0.219 | 0.263 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00799 | -4.30 | 0.00266 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 17808.97 | 21370.76 | 15.34 | 0.426 | 0.511 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00702 | -4.30 | 0.00266 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 58104.95 | 69725.94 | 21.76 | 1.435 | 1.722 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00633 | -4.30 | 0.00266 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.99 | 0.99 | 0.26 | 0.26 | 0.9896 | 0.9896 | 0.9896 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.96 | 1.96 | 0.51 | 0.51 | 1.9629 | 1.9629 | 1.9629 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 69725.939 | 69725.939 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 69725.94 | 69725.94 | 1.721946 | 10.00 | 8.47 | 0.00632671 | 43.33 | 22.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 10.00 | 0.00632671 | 82.1994 | 69725.94 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 16380.610 | 13115.299 | 0.989550 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 8190.31 | 7759.44 | 0.659700 | 24.96 | 16.47 | 0.00832064 | 12.00 | 11.16 | 0.00800000 | 25.37 | 0.00840546 | 16.68 | 15.5047 | 23.90 | 0.00831085 | 44.5442 | 9912.06 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 25594.475 | 25594.475 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 25594.48 | 25594.48 | 0.989552 | 18.39 | 13.22 | 0.00743475 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 10.3365 | 21.10 | 0.00798546 | 50.7640 | 7727.58 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 37664.640 | 29874.463 | 1.962880 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 18832.32 | 17698.76 | 1.308587 | 27.51 | 17.44 | 0.00843447 | 12.00 | 11.16 | 0.00800000 | 26.40 | 0.00840708 | 17.04 | 32.4557 | 26.70 | 0.00844203 | 38.2982 | 25235.59 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 67532.125 | 67532.125 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 67532.13 | 67532.13 | 1.962877 | 11.26 | 8.78 | 0.00607750 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 21.6372 | 15.56 | 0.00702179 | 63.3002 | 17808.97 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 69725.939 | 69725.939 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 1.721946 | 2.05147851 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 69725.94 | 69725.94 | 1.0000 | 2.05147851 | 1.721946 | 10.00 | 8.47 | 0.00632671 | 25987.6 | 43.33 | 22.02 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 69725.94 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 10.00 | 0.00632671 | 10.00 | 0.00632671 | 82.1994 | 69725.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16380.610 | 13115.299 | 0.989550 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3076 | 1004.8586 | 1.1914 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.989552 | 1.17892504 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | Sensible | 8190.31 | 7759.44 | 1.0000 | 0.78594812 | 0.659700 | 24.96 | 16.47 | 0.00832064 | 46278.4 | 12.00 | 11.16 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8190.31 | 25.37 | 0.00840546 | 16.68 | 0.10228463 | 15.5047 | 23.90 | 0.00831085 | 23.90 | 0.00831085 | 44.5442 | 9912.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25594.475 | 25594.475 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.989552 | 1.17892504 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 25594.48 | 25594.48 | 1.0000 | 1.17892504 | 0.989552 | 18.39 | 13.22 | 0.00743475 | 37332.1 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25594.48 | -4.30 | 0.00265759 | -4.30 | 0.10228463 | 10.3365 | 21.01 | 0.00798546 | 21.10 | 0.00798546 | 50.7640 | 7727.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 37664.640 | 29874.463 | 1.962880 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5193 | 1004.8586 | 1.1914 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.962877 | 2.33851629 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 18832.32 | 17698.76 | 1.0000 | 1.55901353 | 1.308587 | 27.51 | 17.44 | 0.00843447 | 49173.3 | 12.00 | 11.16 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18832.32 | 26.40 | 0.00840708 | 17.04 | 0.42471127 | 32.4557 | 26.70 | 0.00844203 | 26.70 | 0.00844203 | 38.2982 | 25235.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 67532.125 | 67532.125 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.962877 | 2.33851629 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 67532.13 | 67532.13 | 1.0000 | 2.33851629 | 1.962877 | 11.26 | 8.78 | 0.00607750 | 26642.6 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 67532.13 | -4.30 | 0.00265759 | -4.30 | 0.42471127 | 21.6372 | 15.56 | 0.00702179 | 15.56 | 0.00702179 | 63.3002 | 17808.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 0.99 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.96 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2096.33 | 3314.67 | 2007.67 |
ZONE2 FINE STORAGE | 2676.83 | 3236.67 | 2385.67 |
ZONE3 BULK STORAGE | 2737.83 | 3392.17 | 2587.67 |
Facility | 2879.50 | 3422.17 | 2592.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 58.83 | 0.33 | 57.17 | 0.33 |
ZONE2 FINE STORAGE | 146.83 | 0.17 | 8.67 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 200.17 | 0.50 | 60.33 | 0.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.599 | 0.256 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.434 | 0.135 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.43 | 69.00 | 35277.63 | 0.000 | 0.084 | 0.000 | 0.031 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.43 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.50 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.36 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.43 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.30 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2161827.20 | 0.00 | 2161827.20 | 1354166.93 | 3515994.13 | 3225648.14 | 5724.89 | 2126.42 | 908.69 | 0.00 |
ZONE2 FINE STORAGE | 4645640.90 | 0.00 | 4645640.90 | 3862596.58 | 8508237.48 | 13393694.68 | 5729.75 | 3019.67 | 10.58 | 0.25 |
ZONE3 BULK STORAGE | 0.00 | 9256655.69 | 9256655.69 | 22204480.09 | 31461135.78 | 30805497.77 | 8693.33 | 7.17 | 59.50 | 4172.83 |
Total Facility | 6807468.11 | 9256655.69 | 16064123.80 | 27421243.60 | 43485367.40 | 47424840.58 | 8717.17 | 3029.00 | 966.69 | 4172.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1652 | 0.0000 | 0.1652 | 0.0710 | 0.2361 | 0.1023 | 600.89 | 2126.42 | 908.69 |
ZONE2 FINE STORAGE | 0.3548 | 0.0000 | 0.3548 | 0.1100 | 0.4648 | 0.4247 | 606.00 | 3019.67 | 10.33 |
ZONE3 BULK STORAGE | 0.0000 | 0.3089 | 0.3089 | 0.8217 | 1.1307 | 0.9768 | 3592.00 | 4.50 | 39.50 |
Total Facility | 0.5200 | 0.3089 | 0.8289 | 1.0027 | 1.8316 | 1.5038 | 3593.17 | 3026.33 | 946.44 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 3068426.77 | 0.00 | 3068426.77 | 3225648.14 | 5722.89 | 0.17 | 3036.94 | 0.00 |
PSZ-FINE STORAGE | 6593780.34 | 0.00 | 6593780.34 | 13393694.68 | 5729.75 | 0.00 | 3030.25 | 0.25 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2344 | 0.0000 | 0.2344 | 0.1023 | 598.89 | 0.17 | 3036.94 |
PSZ-FINE STORAGE | 0.5037 | 0.0000 | 0.5037 | 0.4247 | 606.00 | 0.00 | 3030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2312.44 | 729.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 3025.25 | 5.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2129 | 0.4939 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6042 | 0.8199 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 429 |
Defaulted Fields | 391 |
Fields with Defaults | 1171 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 434.15 | 1924.59 | 29-MAY-13:50 | 33907.19 | 28-DEC-08:10 |
Electricity:Building | 288.85 | 1443.59 | 29-MAY-13:50 | 24347.90 | 02-JAN-09:10 |
Electricity:Zone:ZONE1 OFFICE | 50.46 | 694.23 | 19-FEB-15:30 | 3408.44 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 288.85 | 1443.59 | 29-MAY-13:50 | 24347.90 | 02-JAN-09:10 |
InteriorLights:Electricity | 152.34 | 973.71 | 29-MAY-13:50 | 14312.73 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 21.30 | 224.35 | 19-FEB-15:30 | 1573.38 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 152.34 | 973.71 | 29-MAY-13:50 | 14312.73 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 152.34 | 973.71 | 29-MAY-13:50 | 14312.73 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 21.30 | 224.35 | 19-FEB-15:30 | 1573.38 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 152.34 | 973.71 | 29-MAY-13:50 | 14312.73 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 61.20 | 311.69 | 02-APR-11:20 | 5298.77 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 61.20 | 311.69 | 02-APR-11:20 | 5298.77 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 61.20 | 311.69 | 02-APR-11:20 | 5298.77 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 177.19 | 437.68 | 16-JAN-12:00 | 15640.70 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 69.85 | 437.68 | 16-JAN-12:00 | 7440.58 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 69.85 | 437.68 | 16-JAN-12:00 | 7440.58 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 25.90 | 0.00 | 06-JAN-18:10 | 2494.82 | 10-JAN-18:00 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 434.15 | 1924.59 | 29-MAY-13:50 | 33907.19 | 28-DEC-08:10 |
ElectricityPurchased:Plant | 434.15 | 1924.59 | 29-MAY-13:50 | 33907.19 | 28-DEC-08:10 |
Cogeneration:ElectricityPurchased | 434.15 | 1924.59 | 29-MAY-13:50 | 33907.19 | 28-DEC-08:10 |
General:Cogeneration:ElectricityPurchased | 434.15 | 1924.59 | 29-MAY-13:50 | 33907.19 | 28-DEC-08:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 434.15 | 1924.59 | 29-MAY-13:50 | 33907.19 | 28-DEC-08:10 |
ElectricityNet:Plant | 434.15 | 1924.59 | 29-MAY-13:50 | 33907.19 | 28-DEC-08:10 |
Cogeneration:ElectricityNet | 434.15 | 1924.59 | 29-MAY-13:50 | 33907.19 | 28-DEC-08:10 |
General:Cogeneration:ElectricityNet | 434.15 | 1924.59 | 29-MAY-13:50 | 33907.19 | 28-DEC-08:10 |
Electricity:HVAC | 26.40 | 0.00 | 06-JAN-18:10 | 6227.35 | 22-JUL-15:10 |
General:Fans:Electricity | 25.90 | 0.00 | 06-JAN-18:10 | 2494.82 | 10-JAN-18:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 0.50 | 0.00 | 01-JAN-00:10 | 4316.39 | 23-JUL-16:00 |
General:Cooling:Electricity | 0.50 | 0.00 | 01-JAN-00:10 | 4316.39 | 23-JUL-16:00 |
ExteriorLights:Electricity | 92.73 | 0.00 | 01-JAN-08:20 | 6986.42 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 92.73 | 0.00 | 01-JAN-08:20 | 6986.42 | 01-JAN-06:10 |
Electricity:Plant | 26.17 | 481.00 | 19-APR-05:10 | 2431.33 | 16-FEB-12:10 |
WaterSystems:Electricity | 26.17 | 481.00 | 19-APR-05:10 | 2431.33 | 16-FEB-12:10 |
Water Heater:WaterSystems:Electricity | 26.17 | 481.00 | 19-APR-05:10 | 2431.33 | 16-FEB-12:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 226.44 | 0.00 | 06-JAN-18:10 | 112746.00 | 10-JAN-06:20 |
NaturalGas:HVAC | 226.44 | 0.00 | 06-JAN-18:10 | 112746.00 | 10-JAN-06:20 |
Heating:NaturalGas | 226.44 | 0.00 | 06-JAN-18:10 | 112746.00 | 10-JAN-06:20 |
General:Heating:NaturalGas | 226.44 | 0.00 | 06-JAN-18:10 | 112746.00 | 10-JAN-06:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 362.90 | 0.00 | 06-JAN-18:10 | 174743.70 | 10-JAN-06:20 |
EnergyTransfer:Building | 193.57 | 0.00 | 06-JAN-18:10 | 87754.94 | 10-JAN-06:20 |
EnergyTransfer:Zone:ZONE1 OFFICE | 30.34 | 0.00 | 01-JAN-00:40 | 17035.05 | 10-JAN-06:20 |
Heating:EnergyTransfer | 159.23 | 0.00 | 06-JAN-18:10 | 87754.94 | 10-JAN-06:20 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 22.27 | 0.00 | 01-JAN-00:40 | 17035.05 | 10-JAN-06:20 |
General:Heating:EnergyTransfer | 159.23 | 0.00 | 06-JAN-18:10 | 87754.94 | 10-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 22.27 | 0.00 | 01-JAN-00:40 | 17035.05 | 10-JAN-06:20 |
Cooling:EnergyTransfer | 34.34 | 0.00 | 01-JAN-00:10 | 14267.78 | 22-JUL-15:40 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 8.07 | 0.00 | 01-JAN-00:10 | 6325.79 | 22-JUL-16:00 |
General:Cooling:EnergyTransfer | 34.34 | 0.00 | 01-JAN-00:10 | 14267.78 | 22-JUL-15:40 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 8.07 | 0.00 | 01-JAN-00:10 | 6325.79 | 22-JUL-16:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 73.97 | 0.00 | 01-JAN-00:40 | 24971.76 | 10-JAN-06:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 47.71 | 0.00 | 01-JAN-00:40 | 24971.76 | 10-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 47.71 | 0.00 | 01-JAN-00:40 | 24971.76 | 10-JAN-06:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 26.26 | 0.00 | 01-JAN-00:10 | 12330.21 | 23-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 26.26 | 0.00 | 01-JAN-00:10 | 12330.21 | 23-JUL-13:30 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 89.25 | 0.00 | 02-JAN-08:40 | 54941.26 | 10-JAN-06:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 89.25 | 0.00 | 02-JAN-08:40 | 54941.26 | 10-JAN-06:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 89.25 | 0.00 | 02-JAN-08:40 | 54941.26 | 10-JAN-06:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 169.34 | 0.00 | 06-JAN-18:10 | 86988.76 | 10-JAN-06:20 |
HeatingCoils:EnergyTransfer | 167.02 | 0.00 | 06-JAN-18:10 | 86988.76 | 10-JAN-06:20 |
CoolingCoils:EnergyTransfer | 2.32 | 0.00 | 01-JAN-00:10 | 19934.88 | 23-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 22.267 | -8.074 | 0.000 | 0.000 | 10.140 | 21.297 | 29.165 | 10.171 | 0.000 | 0.018 | 0.000 | 0.000 | -8.008 | 0.000 | -18.258 | -58.718 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 47.709 | -26.262 | 0.000 | 0.000 | 27.624 | 61.202 | 0.000 | 26.950 | 0.000 | 0.011 | 0.000 | 0.000 | -12.549 | 0.000 | -41.044 | -83.640 |
ZONE3 BULK STORAGE | 89.254 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 68.985 | 69.846 | 107.344 | 373.347 | 0.000 | 0.333 | 0.000 | 0.000 | -137.308 | 0.000 | -235.006 | -336.795 |
Total Facility | 89.254 | 0.000 | 69.976 | -34.336 | 0.000 | 0.000 | 106.750 | 152.345 | 136.508 | 410.468 | 0.000 | 0.361 | 0.000 | 0.000 | -157.864 | 0.000 | -294.308 | -479.153 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 24-JUL-05:03 | 0.00 | 0.00 | 0.00 | -16678.62 | 0.00 | 0.00 | 93.14 | 469.96 | 550.52 | 0.00 | 0.00 | 0.00 | 16632.20 | 0.00 | -376.16 | 0.00 | -691.05 | 0.00 |
ZONE2 FINE STORAGE | 23-JUL-13:25 | 0.00 | 0.00 | 0.00 | -24657.60 | 0.00 | 0.00 | 0.00 | 363.64 | 0.00 | 5682.67 | 0.00 | 0.00 | 19894.27 | 0.00 | -0.00 | 0.00 | -1282.98 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 23-JUL-13:25 | 0.00 | 0.00 | 0.00 | -24657.60 | 0.00 | 0.00 | 0.00 | 1037.92 | 469.88 | 101130.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11241.69 | -66739.49 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 30-DEC-06:32 | 0.00 | 0.00 | 26689.61 | 0.00 | 0.00 | 0.00 | 133.15 | 469.96 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -643.18 | 0.00 | -483.60 | -26716.45 |
ZONE2 FINE STORAGE | 10-JAN-06:03 | 0.00 | 0.00 | 68428.91 | 0.00 | 0.00 | 0.00 | 365.46 | 623.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1122.20 | 0.00 | -4239.53 | -64056.01 |
ZONE3 BULK STORAGE | 10-JAN-05:53 | 54950.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -16705.91 | 0.00 | -22671.75 | -18498.70 |
Total Facility | 11-JAN-06:01 | 44078.26 | 0.00 | 94188.40 | 0.00 | 0.00 | 0.00 | 1426.87 | 1968.69 | 2600.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -15107.08 | 0.00 | -20113.04 | -109042.64 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9896 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9896 | 0.1034 | 1.0000 | Not calculated | 0.1023 | 0.1034 | ||
PSZ-FINE STORAGE | 1.9629 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.9629 | 0.2164 | 1.0000 | Not calculated | 0.4247 | 0.2164 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9896 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9896 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.1034 | ||
PSZ-FINE STORAGE | 1.9629 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.9629 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.2164 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9896 | 0.9896 | 0.9896 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9629 | 1.9629 | 1.9629 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9896 | 0.9896 | 0.9896 | 0.9896 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.9629 | 1.9629 | 1.9629 | 1.9629 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9896 | 0.9896 | 0.9896 | No | 0.1023 | 0.3891 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9629 | 1.9629 | 1.9629 | No | 0.4247 | 0.8315 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9896 | 0.9896 | 0.9896 | 0.9896 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.9629 | 1.9629 | 1.9629 | 1.9629 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 60.33 |
Number of hours cooling loads not met | 0.33 |
Number of hours not met | 60.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 226.44 | 112746.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 0.50 | 4316.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 152.34 | 14312.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 92.73 | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 25.90 | 2494.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.17 | 2431.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 434.15 |
Natural Gas | 0.00 | 226.44 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 660.59 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 31.51 |
Space Heating | 0.00 |
Space Cooling | 0.10 |
Fans (All) | 5.36 |
Service Water Heating | 5.41 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 89.79 |
Subtotal | 89.79 |
Natural Gas [MJ/m2] | |
Space Heating | 46.83 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 46.83 |
Subtotal | 46.83 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 23.06 |
Space Heating | 34.28 |
Space Cooling | 0.08 |
Fans (All) | 3.92 |
Service Water Heating | 3.96 |
Receptacle Equipment | 20.66 |
Miscellaneous | 14.04 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2729. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8749.67 | 10.33 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8743.00 | 17.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8745.83 | 14.17 | 0.00 | 0.00 | 0.00 |
Min | 8743.00 | 10.33 | 0.00 | 0.00 | 0.00 |
Max | 8749.67 | 17.00 | 0.00 | 0.00 | 0.00 |
Average | 8746.17 | 13.83 | 0.00 | 0.00 | 0.00 |
Sum | 26238.50 | 41.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 82435.50 | 283.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 190446.00 | 747.00 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 190446.00 | 747.00 | 0.00 | 0.00 | 0.00 |
Average | 101969.50 | 343.50 | 0.00 | 0.00 | 0.00 |
Sum | 305908.50 | 1030.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8743.00 | 17.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8676.67 | 83.33 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8726.67 | 33.33 | 0.00 | 0.00 | 0.00 |
Min | 8676.67 | 17.00 | 0.00 | 0.00 | 0.00 |
Max | 8743.00 | 83.33 | 0.00 | 0.00 | 0.00 |
Average | 8715.44 | 44.56 | 0.00 | 0.00 | 0.00 |
Sum | 26146.33 | 133.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 80832.00 | 1887.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 189465.33 | 1727.67 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 189465.33 | 1887.00 | 0.00 | 0.00 | 0.00 |
Average | 101108.11 | 1204.89 | 0.00 | 0.00 | 0.00 |
Sum | 303324.33 | 3614.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:49
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2046009.53 | 645.63 | 21-JAN-16:10 | 5.75 | 4.88 | 0.497222E+09 | 603.25 | 28-JAN-08:09 | 7.02 | 6.46 |
February | 1187793.85 | 301.54 | 04-FEB-15:30 | 8.00 | 6.08 | 0.457453E+09 | 603.25 | 04-FEB-08:09 | 8.00 | 6.08 |
March | 1471296.20 | 192.05 | 25-MAR-16:00 | 11.00 | 9.41 | 0.537310E+09 | 628.97 | 25-MAR-13:50 | 11.00 | 9.41 |
April | 0.201957E+09 | 2920.11 | 29-APR-15:50 | 20.00 | 12.39 | 0.533296E+09 | 768.97 | 28-APR-15:30 | 20.00 | 12.39 |
May | 0.427113E+09 | 2808.80 | 25-MAY-16:00 | 18.00 | 13.90 | 0.576673E+09 | 768.98 | 22-MAY-15:09 | 18.00 | 13.90 |
June | 0.136920E+10 | 5016.17 | 13-JUN-16:00 | 26.50 | 17.70 | 0.641362E+09 | 769.00 | 26-JUN-13:00 | 22.00 | 16.85 |
July | 0.230423E+10 | 16685.09 | 24-JUL-05:03 | 13.00 | 13.00 | 0.629707E+09 | 769.00 | 24-JUL-15:39 | 19.67 | 16.09 |
August | 0.249297E+10 | 4905.18 | 14-AUG-16:00 | 26.00 | 15.86 | 0.682236E+09 | 769.00 | 17-AUG-13:39 | 21.67 | 16.77 |
September | 0.116978E+10 | 3897.02 | 13-SEP-16:00 | 23.00 | 16.22 | 0.617784E+09 | 768.99 | 12-SEP-14:30 | 23.00 | 16.22 |
October | 94231021.78 | 1379.37 | 07-OCT-15:40 | 18.33 | 9.81 | 0.525226E+09 | 768.96 | 06-OCT-15:30 | 18.33 | 9.81 |
November | 9388589.21 | 557.91 | 10-NOV-17:00 | 7.00 | 6.47 | 0.477893E+09 | 634.43 | 10-NOV-15:39 | 7.00 | 6.47 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.00 | 3.53 | 0.497185E+09 | 603.25 | 02-DEC-08:09 | 6.17 | 5.65 |
Annual Sum or Average | 0.807358E+10 | 0.667335E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.00 | 3.53 | 0.457453E+09 | 603.25 | 6.17 | 5.65 | ||
Maximum of Months | 0.249297E+10 | 16685.09 | 26.50 | 17.70 | 0.682236E+09 | 769.00 | 23.00 | 16.85 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151709E+10 | 4949.62 | 21-JAN-17:00 | 4.00 | 3.53 | 0.667285E+09 | 952.63 | 19-JAN-15:09 | 4.00 | 3.53 |
February | 0.196942E+10 | 4951.61 | 23-FEB-15:20 | 4.33 | 4.17 | 0.613486E+09 | 938.45 | 04-FEB-14:00 | 4.33 | 4.17 |
March | 0.246135E+10 | 4610.53 | 14-MAR-14:00 | 5.00 | 2.42 | 0.737669E+09 | 1025.82 | 25-MAR-13:20 | 13.33 | 10.57 |
April | 0.256474E+10 | 5716.12 | 08-APR-07:10 | 2.50 | 1.05 | 0.914096E+09 | 1811.89 | 29-APR-15:09 | 20.00 | 12.69 |
May | 0.292483E+10 | 5656.35 | 01-MAY-15:00 | 8.00 | 6.98 | 0.105514E+10 | 1797.49 | 22-MAY-15:30 | 23.50 | 15.68 |
June | 0.272205E+10 | 5141.90 | 07-JUN-10:00 | 7.00 | 6.47 | 0.136563E+10 | 2246.80 | 13-JUN-15:50 | 26.42 | 17.72 |
July | 0.268066E+10 | 24660.41 | 23-JUL-13:25 | 21.50 | 16.21 | 0.150211E+10 | 2246.82 | 22-JUL-12:09 | 21.50 | 16.21 |
August | 0.221357E+10 | 4276.19 | 19-AUG-07:10 | 12.67 | 11.93 | 0.164358E+10 | 2246.72 | 14-AUG-15:00 | 12.67 | 11.93 |
September | 0.203080E+10 | 5286.22 | 28-SEP-07:05 | 8.17 | 7.16 | 0.128195E+10 | 2049.80 | 13-SEP-15:09 | 8.17 | 7.16 |
October | 0.213495E+10 | 5841.92 | 06-OCT-07:10 | 3.83 | 3.69 | 0.845940E+09 | 1509.31 | 07-OCT-15:09 | 18.83 | 10.03 |
November | 0.193650E+10 | 4393.89 | 28-NOV-11:30 | 5.35 | 3.26 | 0.660857E+09 | 1031.84 | 10-NOV-14:20 | 5.35 | 3.26 |
December | 0.110573E+10 | 4121.41 | 26-DEC-14:30 | 6.00 | 2.98 | 0.653644E+09 | 867.52 | 21-DEC-14:50 | 6.00 | 2.98 |
Annual Sum or Average | 0.262617E+11 | 0.119414E+11 | ||||||||
Minimum of Months | 0.110573E+10 | 4121.41 | 2.50 | 1.05 | 0.613486E+09 | 867.52 | 4.00 | 2.98 | ||
Maximum of Months | 0.292483E+10 | 24660.41 | 21.50 | 16.21 | 0.164358E+10 | 2246.82 | 26.42 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.92 | 1.45 | 0.771409E+09 | 1272.07 | 19-JAN-15:39 | 8.33 | 7.46 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 | 5.79 | 0.743653E+09 | 1258.17 | 27-FEB-16:19 | 8.00 | 6.64 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 3.80 | 3.71 | 0.979339E+09 | 1560.81 | 25-MAR-13:30 | 13.00 | 10.25 |
April | 0.00 | 0.00 | 01-APR-00:05 | 4.23 | 1.84 | 0.173047E+10 | 3641.13 | 29-APR-15:20 | 20.00 | 12.61 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 | 8.15 | 0.215036E+10 | 3583.70 | 23-MAY-14:39 | 18.33 | 14.52 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 | 7.39 | 0.290653E+10 | 4802.81 | 26-JUN-15:20 | 22.67 | 17.34 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 | 9.95 | 0.331999E+10 | 5679.72 | 22-JUL-15:30 | 29.00 | 16.79 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 | 9.82 | 0.361651E+10 | 4890.48 | 21-AUG-13:00 | 21.00 | 15.01 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 | 10.95 | 0.266430E+10 | 4174.49 | 13-SEP-15:09 | 23.00 | 16.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 | 5.83 | 0.155358E+10 | 2913.64 | 07-OCT-15:09 | 18.83 | 10.03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 | 4.29 | 0.866454E+09 | 1550.25 | 10-NOV-14:39 | 12.00 | 8.58 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.00 | 3.53 | 0.712468E+09 | 1068.95 | 21-DEC-14:50 | 8.00 | 6.98 |
Annual Sum or Average | 0.00 | 0.220151E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 1.92 | 1.45 | 0.712468E+09 | 1068.95 | 8.00 | 6.64 | ||
Maximum of Months | 0.00 | 0.00 | 12.43 | 10.95 | 0.361651E+10 | 5679.72 | 29.00 | 17.34 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.396666E+10 | 26196.47 | 10-JAN-06:22 | -4.0 |
February | 0.338647E+10 | 26183.65 | 13-FEB-06:12 | -1.0 |
March | 0.352842E+10 | 26041.62 | 13-MAR-05:12 | 2.07 |
April | 0.137277E+10 | 25897.27 | 14-APR-05:01 | 3.83 |
May | 0.887216E+09 | 25894.44 | 10-MAY-05:01 | 3.50 |
June | 0.197557E+09 | 25573.88 | 08-JUN-05:01 | 6.17 |
July | 0.102321E+09 | 25393.71 | 05-JUL-05:02 | 7.33 |
August | 92974030.29 | 1278.12 | 30-AUG-06:10 | 9.50 |
September | 0.193818E+09 | 24109.07 | 07-SEP-05:02 | 8.83 |
October | 0.147954E+10 | 25896.68 | 23-OCT-05:01 | 3.17 |
November | 0.292140E+10 | 26182.28 | 20-NOV-06:12 | -0.3 |
December | 0.413829E+10 | 26689.81 | 30-DEC-06:32 | -1.0 |
Annual Sum or Average | 0.222674E+11 | |||
Minimum of Months | 92974030.29 | 1278.12 | -4.0 | |
Maximum of Months | 0.413829E+10 | 26689.81 | 9.50 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103391E+11 | 68428.96 | 10-JAN-06:03 | -4.0 |
February | 0.910850E+10 | 68288.73 | 24-FEB-06:01 | -0.3 |
March | 0.623676E+10 | 62976.78 | 07-MAR-06:01 | 4.00 |
April | 0.630028E+09 | 65353.26 | 05-APR-05:01 | 5.00 |
May | 66276307.33 | 904.15 | 22-MAY-15:00 | 24.00 |
June | 61956667.42 | 898.65 | 28-JUN-07:00 | 11.00 |
July | 61099964.06 | 877.78 | 11-JUL-07:00 | 13.00 |
August | 65496894.41 | 1045.01 | 14-AUG-17:00 | 27.00 |
September | 61146515.99 | 866.36 | 27-SEP-06:50 | 9.67 |
October | 0.106913E+10 | 67756.30 | 25-OCT-05:01 | 7.00 |
November | 0.670423E+10 | 68316.83 | 28-NOV-06:01 | 1.00 |
December | 0.133052E+11 | 68305.00 | 28-DEC-06:01 | 1.00 |
Annual Sum or Average | 0.477089E+11 | |||
Minimum of Months | 61099964.06 | 866.36 | -4.0 | |
Maximum of Months | 0.133052E+11 | 68428.96 | 27.00 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232503E+11 | 54951.02 | 10-JAN-05:53 | -4.0 |
February | 0.170990E+11 | 41124.02 | 17-FEB-04:00 | -2.0 |
March | 0.394734E+10 | 22319.29 | 04-MAR-06:00 | 3.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.763201E+10 | 36530.33 | 29-NOV-03:57 | -1.0 |
December | 0.373256E+11 | 54497.51 | 30-DEC-01:00 | -2.0 |
Annual Sum or Average | 0.892543E+11 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 0.373256E+11 | 54951.02 | 12.43 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.195595E+10 | 1573.38 | 02-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.170132E+10 | 1573.38 | 01-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.189512E+10 | 1573.38 | 01-MAR-08:09 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.164374E+10 | 1573.38 | 10-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.166966E+10 | 1421.29 | 01-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.161801E+10 | 1421.29 | 05-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.162179E+10 | 1421.29 | 07-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.173137E+10 | 1573.38 | 08-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.169671E+10 | 1573.38 | 01-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.185023E+10 | 1573.38 | 02-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.188881E+10 | 1573.38 | 01-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.202423E+10 | 1573.38 | 01-DEC-08:09 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.212969E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.161801E+10 | 1421.29 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.202423E+10 | 1573.38 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.574101E+10 | 5298.77 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.497646E+10 | 5298.77 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.542481E+10 | 5298.77 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.465659E+10 | 5298.77 | 03-APR-08:09 | 0.00 | 0.00 |
May | 0.464616E+10 | 4857.20 | 02-MAY-08:09 | 0.00 | 0.00 |
June | 0.444821E+10 | 4857.20 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.448873E+10 | 4857.20 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.496702E+10 | 5298.77 | 08-AUG-08:09 | 0.00 | 0.00 |
September | 0.505666E+10 | 5298.77 | 02-SEP-08:09 | 0.00 | 0.00 |
October | 0.544023E+10 | 5298.77 | 03-OCT-08:09 | 0.00 | 0.00 |
November | 0.550395E+10 | 5298.77 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.585207E+10 | 5298.77 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.612019E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.444821E+10 | 4857.20 | 0.00 | 0.00 | |
Maximum of Months | 0.585207E+10 | 5298.77 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.706910E+10 | 7440.58 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.584575E+10 | 7440.58 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.593978E+10 | 6565.03 | 03-MAR-16:49 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.508014E+10 | 6565.03 | 10-APR-07:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.503957E+10 | 5252.11 | 01-MAY-06:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.489083E+10 | 5252.11 | 17-JUN-06:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.486225E+10 | 4923.77 | 07-JUL-07:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.534411E+10 | 6200.49 | 08-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.543092E+10 | 6565.03 | 08-SEP-07:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.613363E+10 | 7440.58 | 20-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.672058E+10 | 7440.58 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.748901E+10 | 7440.58 | 01-DEC-14:50 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.698457E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.486225E+10 | 4923.77 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.748901E+10 | 7440.58 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.195595E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163808E+10 |
February | 0.127628E+10 | 0.170132E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160194E+10 |
March | 0.149825E+10 | 0.189512E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156673E+10 |
April | 0.138726E+10 | 0.164374E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121251E+10 |
May | 0.144276E+10 | 0.166966E+10 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2434.91 | 0.186625E+10 |
June | 0.144276E+10 | 0.161801E+10 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4745288.36 | 0.150415E+10 |
July | 0.138726E+10 | 0.162179E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9998432.76 | 0.130349E+10 |
August | 0.149825E+10 | 0.173137E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3395324.90 | 0.116264E+10 |
September | 0.138726E+10 | 0.169671E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117419E+10 |
October | 0.138726E+10 | 0.185023E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137404E+10 |
November | 0.133177E+10 | 0.188881E+10 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172431E+10 |
December | 0.138726E+10 | 0.202423E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212998E+10 |
Annual Sum or Average | 0.168137E+11 | 0.212969E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18141480.93 | 0.182583E+11 |
Minimum of Months | 0.127628E+10 | 0.161801E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116264E+10 |
Maximum of Months | 0.149825E+10 | 0.202423E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9998432.76 | 0.212998E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.574101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205721E+10 |
February | 0.300332E+10 | 0.497646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285145E+10 |
March | 0.352563E+10 | 0.542481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181414E+10 |
April | 0.326447E+10 | 0.465659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314416.99 | 0.200314E+10 |
May | 0.339505E+10 | 0.464616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16425.32 | 0.516188E+10 |
June | 0.339505E+10 | 0.444821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 723273.73 | 0.463692E+10 |
July | 0.326447E+10 | 0.448873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8677585.34 | 0.456649E+10 |
August | 0.352563E+10 | 0.496702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 857438.49 | 0.373852E+10 |
September | 0.326447E+10 | 0.505666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320461E+10 |
October | 0.326447E+10 | 0.544023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259505E+10 |
November | 0.313390E+10 | 0.550395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339108E+10 |
December | 0.326447E+10 | 0.585207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502351E+10 |
Annual Sum or Average | 0.395654E+11 | 0.612019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10589139.86 | 0.410440E+11 |
Minimum of Months | 0.300332E+10 | 0.444821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181414E+10 |
Maximum of Months | 0.352563E+10 | 0.585207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8677585.34 | 0.516188E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.706910E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42337736.02 | 0.655211E+10 |
February | 0.690763E+10 | 0.584575E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.865821E+10 |
March | 0.810895E+10 | 0.593978E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1601941.61 | 0.561274E+10 |
April | 0.750829E+10 | 0.508014E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14453677.52 | 0.897484E+10 |
May | 0.780862E+10 | 0.503957E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29911459.01 | 0.241997E+11 |
June | 0.780862E+10 | 0.489083E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34861535.91 | 0.223063E+11 |
July | 0.750829E+10 | 0.486225E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31610301.91 | 0.223503E+11 |
August | 0.810895E+10 | 0.534411E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12168806.59 | 0.184878E+11 |
September | 0.750829E+10 | 0.543092E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5191418.85 | 0.148260E+11 |
October | 0.750829E+10 | 0.613363E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100590E+11 |
November | 0.720796E+10 | 0.672058E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46060790.59 | 0.908975E+10 |
December | 0.750829E+10 | 0.748901E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17605152.62 | 0.141391E+11 |
Annual Sum or Average | 0.910005E+11 | 0.698457E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235803E+09 | 0.165256E+12 |
Minimum of Months | 0.690763E+10 | 0.486225E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561274E+10 |
Maximum of Months | 0.810895E+10 | 0.748901E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46060790.59 | 0.241997E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1573.38 | 02-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 7046.75 | 10-JAN-18:00 |
February | 1680.92 | 01-FEB-08:09 | 1573.38 | 01-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 5790.09 | 17-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 1573.38 | 01-MAR-08:09 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 5493.02 | 31-MAR-07:00 |
April | 1680.92 | 01-APR-07:10 | 1573.38 | 10-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4380.14 | 11-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 1421.29 | 01-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 22-MAY-15:00 | 4981.65 | 01-MAY-16:03 |
June | 1680.92 | 01-JUN-07:10 | 1421.29 | 05-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 777.58 | 13-JUN-17:00 | 3993.49 | 08-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 1421.29 | 07-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1203.49 | 21-JUL-17:00 | 3119.60 | 20-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 1573.38 | 08-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 757.14 | 14-AUG-17:00 | 3168.54 | 24-AUG-06:10 |
September | 1680.92 | 01-SEP-07:10 | 1573.38 | 01-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 3931.31 | 20-SEP-06:10 |
October | 1680.92 | 02-OCT-07:10 | 1573.38 | 02-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4774.61 | 04-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 1573.38 | 01-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6200.24 | 29-NOV-08:00 |
December | 1680.92 | 01-DEC-08:09 | 1573.38 | 01-DEC-08:09 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6337.39 | 28-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1421.29 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3119.60 | |||||
Maximum of Months | 1680.92 | 1573.38 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 1203.49 | 7046.75 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 5298.77 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 7181.69 | 10-JAN-18:00 |
February | 3955.50 | 01-FEB-08:09 | 5298.77 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4535.64 | 01-FEB-16:10 |
March | 3955.50 | 01-MAR-08:09 | 5298.77 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 7242.05 | 31-MAR-08:00 |
April | 3955.50 | 01-APR-07:10 | 5298.77 | 03-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.48 | 30-APR-19:00 | 4055.60 | 24-APR-15:10 |
May | 3955.50 | 01-MAY-07:10 | 4857.20 | 02-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.32 | 22-MAY-15:00 | 9020.18 | 01-MAY-15:05 |
June | 3955.50 | 01-JUN-07:10 | 4857.20 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.83 | 12-JUN-18:00 | 6105.91 | 07-JUN-15:05 |
July | 3955.50 | 01-JUL-07:10 | 4857.20 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 584.09 | 22-JUL-15:10 | 5472.82 | 30-JUL-19:00 |
August | 3955.50 | 01-AUG-07:10 | 5298.77 | 08-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.38 | 14-AUG-18:00 | 5875.34 | 22-AUG-16:00 |
September | 3955.50 | 01-SEP-07:10 | 5298.77 | 02-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 5661.87 | 29-SEP-15:10 |
October | 3955.50 | 02-OCT-07:10 | 5298.77 | 03-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4602.63 | 01-OCT-24:00 |
November | 3955.50 | 01-NOV-07:10 | 5298.77 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6334.32 | 15-NOV-07:10 |
December | 3955.50 | 01-DEC-08:09 | 5298.77 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 10545.41 | 02-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 4857.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4055.60 | ||||
Maximum of Months | 3955.50 | 5298.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 584.09 | 10545.41 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 7440.58 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4185.62 | 29-JAN-06:00 | 24889.97 | 10-JAN-16:00 |
February | 9097.65 | 01-FEB-08:09 | 7440.58 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 12794.22 | 19-FEB-22:00 |
March | 9097.65 | 01-MAR-08:09 | 6565.03 | 03-MAR-16:49 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 333.08 | 19-MAR-12:00 | 20704.89 | 31-MAR-08:00 |
April | 9097.65 | 01-APR-07:10 | 6565.03 | 10-APR-07:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1222.61 | 30-APR-19:00 | 17085.41 | 24-APR-12:10 |
May | 9097.65 | 01-MAY-07:10 | 5252.11 | 01-MAY-06:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2430.31 | 22-MAY-15:00 | 39789.92 | 01-MAY-13:00 |
June | 9097.65 | 01-JUN-07:10 | 5252.11 | 17-JUN-06:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2145.25 | 13-JUN-17:00 | 27365.80 | 07-JUN-15:00 |
July | 9097.65 | 01-JUL-07:10 | 4923.77 | 07-JUL-07:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1803.99 | 22-JUL-19:00 | 23222.79 | 30-JUL-19:00 |
August | 9097.65 | 01-AUG-07:10 | 6200.49 | 08-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1792.18 | 14-AUG-18:00 | 25783.82 | 22-AUG-16:00 |
September | 9097.65 | 01-SEP-07:10 | 6565.03 | 08-SEP-07:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 643.96 | 24-SEP-16:00 | 19924.06 | 19-SEP-15:00 |
October | 9097.65 | 02-OCT-07:10 | 7440.58 | 20-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 17820.71 | 01-OCT-24:00 |
November | 9097.65 | 01-NOV-07:10 | 7440.58 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6204.66 | 24-NOV-11:50 | 14980.80 | 28-NOV-08:70 |
December | 9097.65 | 01-DEC-08:09 | 7440.58 | 01-DEC-14:50 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5755.87 | 23-DEC-11:00 | 20626.71 | 28-DEC-08:70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 4923.77 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12794.22 | |||||
Maximum of Months | 9097.65 | 7440.58 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 6204.66 | 39789.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 645.63 | 21-JAN-16:10 | 1680.92 | 1064.66 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.14 |
February | 301.54 | 04-FEB-15:30 | 1680.92 | 1012.21 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.04 |
March | 192.05 | 25-MAR-16:00 | 1680.92 | 1421.29 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2920.11 | 29-APR-15:50 | 1680.92 | 959.76 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.11 |
May | 2808.80 | 25-MAY-16:00 | 1680.92 | 959.76 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.71 |
June | 5016.17 | 13-JUN-16:00 | 1680.92 | 959.76 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 222.62 | 0.00 |
July | 16685.09 | 24-JUL-05:03 | 554.70 | 1409.89 | 1651.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 691.05 |
August | 4905.18 | 14-AUG-16:00 | 1680.92 | 959.76 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 165.62 | 0.00 |
September | 3897.02 | 13-SEP-16:00 | 1680.92 | 959.76 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.40 |
October | 1379.37 | 07-OCT-15:40 | 1680.92 | 959.76 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.92 |
November | 557.91 | 10-NOV-17:00 | 1680.92 | 1573.38 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413.44 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 735.58 | 939.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 735.58 | 939.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16685.09 | 1680.92 | 1573.38 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 222.62 | 691.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4949.62 | 21-JAN-17:00 | 3955.50 | 4675.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4951.61 | 23-FEB-15:20 | 3955.50 | 4415.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 791.25 |
March | 4610.53 | 14-MAR-14:00 | 3955.50 | 3090.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 837.64 |
April | 5716.12 | 08-APR-07:10 | 3955.50 | 4675.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5656.35 | 01-MAY-15:00 | 3955.50 | 3090.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3661.30 |
June | 5141.90 | 07-JUN-10:00 | 3955.50 | 3974.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2243.82 |
July | 24660.41 | 23-JUL-13:25 | 0.00 | 727.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1282.98 |
August | 4276.19 | 19-AUG-07:10 | 3955.50 | 4675.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2361.35 |
September | 5286.22 | 28-SEP-07:05 | 7911.00 | 9350.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5841.92 | 06-OCT-07:10 | 3955.50 | 4675.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4393.89 | 28-NOV-11:30 | 3955.50 | 4857.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.91 |
December | 4121.41 | 26-DEC-14:30 | 3955.50 | 5298.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 644.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4121.41 | 0.00 | 727.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24660.41 | 7911.00 | 9350.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3661.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 2626.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.06 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 1750.70 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2440.28 |
March | 0.00 | 01-MAR-00:05 | 0.00 | 1750.70 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 01-APR-00:05 | 0.00 | 1750.70 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3225.59 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7413.15 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9302.77 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15734.84 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7444.25 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8540.18 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 875.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11793.79 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 875.35 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4255.51 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 1750.70 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2490.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 875.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 2626.05 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15734.84 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.413552E+11 | 33846.01 | 10-JAN-16:00 | 0.540061E+11 | 112746.00 | 10-JAN-06:19 |
February | 0.357675E+11 | 28026.68 | 01-FEB-09:09 | 0.419134E+11 | 81837.82 | 18-FEB-06:10 |
March | 0.381948E+11 | 26855.20 | 15-MAR-08:20 | 0.210124E+11 | 56575.40 | 04-MAR-06:19 |
April | 0.333028E+11 | 26728.50 | 10-APR-08:20 | 0.289203E+10 | 26498.57 | 11-APR-05:10 |
May | 0.329751E+11 | 24636.83 | 04-MAY-07:19 | 0.119308E+10 | 14660.97 | 05-MAY-05:10 |
June | 0.317965E+11 | 23931.40 | 21-JUN-07:10 | 0.129044E+09 | 9051.04 | 08-JUN-05:10 |
July | 0.319160E+11 | 26189.74 | 22-JUL-14:00 | 29527152.36 | 6407.24 | 05-JUL-05:10 |
August | 0.347791E+11 | 26712.34 | 08-AUG-08:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.347945E+11 | 26713.14 | 08-SEP-08:30 | 0.128221E+09 | 6170.83 | 07-SEP-05:10 |
October | 0.377755E+11 | 27960.19 | 31-OCT-08:20 | 0.372030E+10 | 28712.21 | 23-OCT-05:10 |
November | 0.390693E+11 | 33529.61 | 28-NOV-16:49 | 0.251370E+11 | 83449.64 | 28-NOV-06:10 |
December | 0.424230E+11 | 33907.19 | 28-DEC-08:09 | 0.762824E+11 | 98298.01 | 28-DEC-06:49 |
Annual Sum or Average | 0.434150E+12 | 0.226444E+12 | ||||
Minimum of Months | 0.317965E+11 | 23931.40 | 0.00 | 0.00 | ||
Maximum of Months | 0.424230E+11 | 33907.19 | 0.762824E+11 | 112746.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.147661E+11 | 0.105137E+11 | 0.112984E+11 | 0.00 | 0.253273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224441E+10 | 0.00 |
February | 0.125235E+11 | 0.853412E+10 | 0.103734E+11 | 0.00 | 0.229067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204585E+10 | 0.00 |
March | 0.132597E+11 | 0.812850E+10 | 0.121089E+11 | 0.00 | 0.238986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230781E+10 | 0.00 |
April | 0.113805E+11 | 0.653247E+10 | 0.112578E+11 | 0.00 | 0.195312E+10 | 0.00 | 0.00 | 1205511.20 | 0.00 | 0.00 | 0.00 | 0.217780E+10 | 0.00 |
May | 0.113554E+11 | 0.567552E+10 | 0.117000E+11 | 0.00 | 0.200672E+10 | 0.00 | 0.00 | 6776064.68 | 0.00 | 0.00 | 0.00 | 0.223077E+10 | 0.00 |
June | 0.109570E+11 | 0.494907E+10 | 0.116594E+11 | 0.00 | 0.199511E+10 | 0.00 | 0.00 | 79662731.53 | 0.00 | 0.00 | 0.00 | 0.215627E+10 | 0.00 |
July | 0.109728E+11 | 0.532760E+10 | 0.112984E+11 | 0.00 | 0.191940E+10 | 0.00 | 0.00 | 0.243996E+09 | 0.00 | 0.00 | 0.00 | 0.215387E+10 | 0.00 |
August | 0.120425E+11 | 0.623615E+10 | 0.121016E+11 | 0.00 | 0.206969E+10 | 0.00 | 0.00 | 0.124139E+09 | 0.00 | 0.00 | 0.00 | 0.220509E+10 | 0.00 |
September | 0.121843E+11 | 0.728701E+10 | 0.112504E+11 | 0.00 | 0.191790E+10 | 0.00 | 0.00 | 44692899.63 | 0.00 | 0.00 | 0.00 | 0.211027E+10 | 0.00 |
October | 0.134241E+11 | 0.889980E+10 | 0.113057E+11 | 0.00 | 0.196663E+10 | 0.00 | 0.00 | 51.64 | 0.00 | 0.00 | 0.00 | 0.217924E+10 | 0.00 |
November | 0.141133E+11 | 0.981050E+10 | 0.108562E+11 | 0.00 | 0.216228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212695E+10 | 0.00 |
December | 0.153653E+11 | 0.108364E+11 | 0.112984E+11 | 0.00 | 0.269522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222768E+10 | 0.00 |
Annual Sum or Average | 0.152345E+12 | 0.927309E+11 | 0.136508E+12 | 0.00 | 0.258993E+11 | 0.00 | 0.00 | 0.500472E+09 | 0.00 | 0.00 | 0.00 | 0.261660E+11 | 0.00 |
Minimum of Months | 0.109570E+11 | 0.494907E+10 | 0.103734E+11 | 0.00 | 0.191790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204585E+10 | 0.00 |
Maximum of Months | 0.153653E+11 | 0.108364E+11 | 0.121089E+11 | 0.00 | 0.269522E+10 | 0.00 | 0.00 | 0.243996E+09 | 0.00 | 0.00 | 0.00 | 0.230781E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.540061E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.419134E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.210124E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.289203E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.119308E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.129044E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 29527152.36 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.128221E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.372030E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.251370E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.762824E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.226444E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.762824E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 14312.73 | 02-JAN-09:09 | 6986.42 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 2494.82 | 10-JAN-17:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 14312.73 | 01-FEB-09:09 | 6986.42 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 2349.95 | 18-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 13072.63 | 13-MAR-08:09 | 6986.42 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 2317.04 | 08-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 13072.63 | 10-APR-08:09 | 6986.42 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 2037.35 | 05-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 11020.31 | 03-MAY-07:10 | 6986.42 | 01-MAY-19:19 | 10035.17 | 01-MAY-07:10 | 0.00 | 1935.74 | 03-MAY-06:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 10321.13 | 01-JUN-07:10 | 6986.42 | 01-JUN-19:00 | 10035.17 | 01-JUN-07:10 | 0.00 | 1935.74 | 09-JUN-06:49 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 11020.31 | 07-JUL-07:10 | 6986.42 | 01-JUL-20:19 | 10035.17 | 01-JUL-07:10 | 0.00 | 1935.74 | 05-JUL-06:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 13072.63 | 08-AUG-08:09 | 6986.42 | 01-AUG-19:49 | 10035.17 | 01-AUG-07:10 | 0.00 | 1935.74 | 10-AUG-13:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 13072.63 | 08-SEP-08:09 | 6986.42 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 1935.74 | 25-SEP-10:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 14312.73 | 20-OCT-08:09 | 6986.42 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 2047.26 | 23-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 14312.73 | 01-NOV-08:09 | 6986.42 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 2373.09 | 29-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 14312.73 | 01-DEC-14:50 | 6986.42 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 2423.18 | 28-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 10321.13 | 6986.42 | 10035.17 | 0.00 | 1935.74 | 0.00 | 0.00 | |||||
Maximum of Months | 14312.73 | 6986.42 | 10035.17 | 0.00 | 2494.82 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2422.62 | 31-JAN-12:00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2431.33 | 16-FEB-12:09 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2421.47 | 02-MAR-12:00 | 0.00 |
April | 164.34 | 29-APR-15:50 | 0.00 | 0.00 | 0.00 | 2364.96 | 01-APR-11:00 | 0.00 |
May | 779.90 | 22-MAY-14:00 | 0.00 | 0.00 | 0.00 | 2261.99 | 01-MAY-11:30 | 0.00 |
June | 1891.30 | 13-JUN-15:00 | 0.00 | 0.00 | 0.00 | 2133.25 | 01-JUN-11:30 | 0.00 |
July | 4316.39 | 23-JUL-15:00 | 0.00 | 0.00 | 0.00 | 1999.54 | 07-JUL-11:00 | 0.00 |
August | 1388.95 | 14-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1948.79 | 01-AUG-11:39 | 0.00 |
September | 990.48 | 13-SEP-15:00 | 0.00 | 0.00 | 0.00 | 2013.60 | 29-SEP-11:00 | 0.00 |
October | 0.05 | 07-OCT-12:50 | 0.00 | 0.00 | 0.00 | 2126.41 | 28-OCT-11:20 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2240.22 | 25-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2363.62 | 30-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1948.79 | 0.00 | ||
Maximum of Months | 4316.39 | 0.00 | 0.00 | 0.00 | 2431.33 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 33846.01 | 10-JAN-16:00 | 12813.66 | 10035.17 | 6986.42 | 0.00 | 2395.24 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 28026.68 | 01-FEB-09:09 | 14312.73 | 10035.17 | 0.00 | 0.00 | 1990.24 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 26855.20 | 15-MAR-08:20 | 13072.63 | 10035.17 | 0.00 | 0.00 | 2059.65 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 26728.50 | 10-APR-08:20 | 13072.63 | 10035.17 | 0.00 | 0.00 | 1935.74 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24636.83 | 04-MAY-07:19 | 11020.31 | 10035.17 | 0.00 | 0.00 | 1935.74 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 23931.40 | 21-JUN-07:10 | 10321.13 | 10035.17 | 0.00 | 0.00 | 1935.74 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 26189.74 | 22-JUL-14:00 | 8212.57 | 10035.17 | 0.00 | 0.00 | 1935.74 | 0.00 | 0.00 | 4230.89 | 0.00 |
August | 26712.34 | 08-AUG-08:09 | 13072.63 | 10035.17 | 0.00 | 0.00 | 1935.74 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26713.14 | 08-SEP-08:30 | 13072.63 | 10035.17 | 0.00 | 0.00 | 1935.74 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 27960.19 | 31-OCT-08:20 | 14312.73 | 10035.17 | 0.00 | 0.00 | 1935.74 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 33529.61 | 28-NOV-16:49 | 12813.66 | 10035.17 | 6986.42 | 0.00 | 2082.01 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 33907.19 | 28-DEC-08:09 | 12813.66 | 10035.17 | 6986.42 | 0.00 | 2423.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 23931.40 | 8212.57 | 10035.17 | 0.00 | 0.00 | 1935.74 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33907.19 | 14312.73 | 10035.17 | 6986.42 | 0.00 | 2423.18 | 0.00 | 0.00 | 4230.89 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 112746.00 | 10-JAN-06:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 81837.82 | 18-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 56575.40 | 04-MAR-06:19 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 26498.57 | 11-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 14660.97 | 05-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 9051.04 | 08-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 6407.24 | 05-JUL-05:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 6170.83 | 07-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 28712.21 | 23-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 83449.64 | 28-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 98298.01 | 28-DEC-06:49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 112746.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.17 | 19.40 | 8.50 | 19.57 | 0.00 | 19.57 | 0.00 | 19.57 |
February | 8.00 | 19.60 | 7.67 | 19.70 | 0.00 | 19.70 | 0.00 | 19.70 |
March | 9.00 | 19.93 | 9.00 | 19.93 | 0.00 | 19.93 | 0.00 | 19.93 |
April | 5.67 | 20.24 | 5.67 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 |
May | 3.33 | 20.35 | 3.33 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
June | 0.33 | 20.47 | 0.33 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.52 | 0.33 | 24.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.50 | 20.50 | 0.50 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
October | 5.67 | 20.28 | 5.67 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
November | 7.83 | 20.00 | 7.83 | 20.00 | 0.00 | 20.00 | 0.00 | 20.00 |
December | 9.33 | 19.32 | 8.67 | 19.48 | 0.00 | 19.48 | 0.00 | 19.48 |
Annual Sum or Average | 58.83 | 19.81 | 57.17 | 19.88 | 0.33 | 19.89 | 0.33 | 19.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.33 | 20.50 | 9.00 | 20.50 | 0.33 | 24.52 | 0.33 | 24.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 28.33 | 14.86 | 2.17 | 14.87 | 0.00 | 14.87 | 0.00 | 14.87 |
February | 26.67 | 14.91 | 1.50 | 14.91 | 0.00 | 14.91 | 0.00 | 14.91 |
March | 9.00 | 14.97 | 0.33 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
April | 2.33 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.00 | 27.27 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6.00 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
November | 22.83 | 14.93 | 1.00 | 14.93 | 0.00 | 14.93 | 0.00 | 14.93 |
December | 51.67 | 14.87 | 3.67 | 14.87 | 0.00 | 14.87 | 0.00 | 14.87 |
Annual Sum or Average | 146.83 | 14.90 | 8.67 | 14.90 | 0.17 | 14.91 | 0.00 | 14.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 51.67 | 14.98 | 3.67 | 14.98 | 0.17 | 27.27 | 0.00 | 27.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.06 | 300.00 | 21.06 | 300.00 | 21.06 |
February | 276.00 | 21.06 | 276.00 | 21.06 | 276.00 | 21.06 |
March | 324.00 | 21.07 | 324.00 | 21.07 | 324.00 | 21.07 |
April | 300.00 | 21.74 | 193.83 | 21.51 | 193.83 | 21.41 |
May | 312.00 | 22.11 | 115.67 | 21.85 | 115.67 | 21.69 |
June | 271.50 | 23.23 | 16.67 | 23.17 | 9.67 | 23.10 |
July | 158.83 | 23.49 | 62.33 | 23.57 | 2.50 | 23.54 |
August | 200.50 | 23.62 | 21.83 | 23.65 | 0.00 | 23.65 |
September | 283.83 | 23.27 | 7.67 | 23.21 | 7.67 | 23.15 |
October | 300.00 | 21.58 | 193.83 | 21.39 | 193.83 | 21.31 |
November | 288.00 | 21.08 | 284.50 | 21.08 | 284.50 | 21.07 |
December | 300.00 | 21.06 | 300.00 | 21.06 | 300.00 | 21.06 |
Annual Sum or Average | 3314.67 | 21.91 | 2096.33 | 21.63 | 2007.67 | 21.48 |
Minimum of Months | 158.83 | 21.06 | 7.67 | 21.06 | 0.00 | 21.06 |
Maximum of Months | 324.00 | 23.62 | 324.00 | 23.65 | 324.00 | 23.65 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.73 | 300.00 | 15.73 | 300.00 | 15.73 |
February | 276.00 | 15.72 | 276.00 | 15.72 | 276.00 | 15.72 |
March | 324.00 | 15.90 | 324.00 | 15.90 | 324.00 | 15.90 |
April | 300.00 | 18.24 | 261.50 | 17.99 | 261.50 | 17.90 |
May | 312.00 | 19.27 | 230.67 | 18.87 | 230.67 | 18.70 |
June | 260.00 | 21.54 | 83.33 | 21.61 | 48.17 | 21.32 |
July | 149.50 | 22.29 | 139.67 | 23.54 | 16.50 | 23.43 |
August | 151.50 | 22.72 | 120.00 | 23.82 | 0.00 | 23.82 |
September | 275.67 | 21.56 | 76.00 | 21.30 | 63.17 | 21.01 |
October | 300.00 | 17.58 | 277.67 | 17.45 | 277.67 | 17.40 |
November | 288.00 | 15.94 | 288.00 | 15.94 | 288.00 | 15.94 |
December | 300.00 | 15.59 | 300.00 | 15.59 | 300.00 | 15.59 |
Annual Sum or Average | 3236.67 | 18.09 | 2676.83 | 17.85 | 2385.67 | 17.50 |
Minimum of Months | 149.50 | 15.59 | 76.00 | 15.59 | 0.00 | 15.59 |
Maximum of Months | 324.00 | 22.72 | 324.00 | 23.82 | 324.00 | 23.82 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 10.85 | 300.00 | 10.85 | 300.00 | 10.85 |
February | 276.00 | 11.10 | 276.00 | 11.10 | 276.00 | 11.10 |
March | 324.00 | 11.76 | 324.00 | 11.76 | 324.00 | 11.76 |
April | 300.00 | 16.33 | 287.17 | 16.21 | 287.17 | 16.17 |
May | 312.00 | 18.05 | 267.17 | 17.79 | 267.17 | 17.70 |
June | 292.50 | 20.93 | 109.67 | 20.55 | 97.00 | 20.21 |
July | 189.83 | 22.01 | 103.17 | 22.79 | 27.67 | 22.60 |
August | 209.83 | 22.48 | 66.50 | 23.04 | 4.50 | 22.99 |
September | 300.00 | 20.66 | 116.17 | 20.19 | 116.17 | 19.92 |
October | 300.00 | 15.52 | 300.00 | 15.52 | 300.00 | 15.52 |
November | 288.00 | 11.74 | 288.00 | 11.74 | 288.00 | 11.74 |
December | 300.00 | 10.46 | 300.00 | 10.46 | 300.00 | 10.46 |
Annual Sum or Average | 3392.17 | 15.64 | 2737.83 | 15.03 | 2587.67 | 14.62 |
Minimum of Months | 189.83 | 10.46 | 66.50 | 10.46 | 4.50 | 10.46 |
Maximum of Months | 324.00 | 22.48 | 324.00 | 23.04 | 324.00 | 22.99 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 5434521.19 | 1205511.20 | 4.50 | 5420596.10 | 13925.09 | 0.00 | 0.10 | 29-APR-15:50 | 0.00 | 01-APR-00:05 | 744.07 | 29-APR-15:50 | 744.07 | 29-APR-15:50 | 8.06 | 28-APR-15:00 | 164.34 | 29-APR-15:50 | 0.00 | 01-APR-00:05 |
May | 31959780.32 | 6776064.68 | 5.67 | 29613510.84 | 2346269.48 | 0.00 | 0.45 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 3735.71 | 22-MAY-15:00 | 3437.39 | 22-MAY-15:00 | 298.32 | 22-MAY-15:00 | 779.90 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.375960E+09 | 77968126.14 | 36.08 | 0.315199E+09 | 60761082.11 | 0.00 | 0.82 | 13-JUN-16:00 | 0.00 | 01-JUN-00:10 | 7275.53 | 13-JUN-16:00 | 6432.12 | 13-JUN-16:00 | 1523.14 | 26-JUN-16:00 | 1485.46 | 13-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.771214E+09 | 0.161724E+09 | 71.72 | 0.684176E+09 | 87038110.25 | 0.00 | 1.00 | 24-JUL-05:03 | 0.00 | 01-JUL-00:10 | 15979.61 | 24-JUL-05:03 | 9406.49 | 24-JUL-05:03 | 6573.12 | 24-JUL-05:03 | 3218.25 | 24-JUL-05:03 | 0.00 | 01-JUL-00:10 |
August | 0.588674E+09 | 0.124120E+09 | 90.33 | 0.499897E+09 | 88776772.13 | 0.00 | 0.77 | 14-AUG-16:00 | 0.00 | 01-AUG-00:10 | 6702.59 | 14-AUG-16:00 | 6258.23 | 14-AUG-16:00 | 1207.41 | 17-AUG-15:00 | 1372.40 | 14-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 0.210161E+09 | 44692899.63 | 33.83 | 0.188526E+09 | 21635192.44 | 0.00 | 0.56 | 13-SEP-16:00 | 0.00 | 01-SEP-00:10 | 4847.87 | 13-SEP-16:00 | 4231.95 | 13-SEP-16:00 | 641.66 | 13-SEP-15:40 | 990.48 | 13-SEP-16:00 | 0.00 | 01-SEP-00:10 |
October | 230.17 | 51.64 | 0.67 | 230.17 | 0.00 | 0.00 | 0.00 | 07-OCT-12:50 | 0.00 | 01-OCT-00:10 | 0.22 | 07-OCT-12:50 | 0.22 | 07-OCT-12:50 | 0.00 | 07-OCT-13:00 | 0.05 | 07-OCT-12:50 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.198340E+10 | 0.416487E+09 | 242.81 | 0.172283E+10 | 0.260571E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.771214E+09 | 0.161724E+09 | 90.33 | 0.684176E+09 | 88776772.13 | 0.00 | 1.00 | 0.00 | 15979.61 | 9406.49 | 6573.12 | 3218.25 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 6445557.98 | 1694605.39 | 2.33 | 5746522.25 | 699035.73 | 0.00 | 0.09 | 13-JUN-16:00 | 0.00 | 01-JUN-00:10 | 1551.66 | 13-JUN-16:00 | 1390.10 | 13-JUN-16:00 | 161.56 | 13-JUN-16:00 | 405.84 | 13-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.325954E+09 | 82271841.04 | 13.22 | 0.315378E+09 | 10575872.21 | 0.00 | 1.00 | 23-JUL-12:25 | 0.00 | 01-JUL-00:10 | 39869.75 | 23-JUL-15:55 | 31365.43 | 23-JUL-13:25 | 8958.25 | 23-JUL-15:55 | 8632.77 | 23-JUL-15:55 | 0.00 | 01-JUL-00:10 |
August | 73172.04 | 19377.97 | 0.33 | 72660.00 | 512.04 | 0.00 | 0.00 | 14-AUG-16:00 | 0.00 | 01-AUG-00:10 | 62.40 | 14-AUG-16:00 | 62.40 | 14-AUG-16:00 | 0.85 | 14-AUG-15:50 | 16.55 | 14-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.332473E+09 | 83985824.40 | 15.89 | 0.321198E+09 | 11275419.98 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.325954E+09 | 82271841.04 | 13.22 | 0.315378E+09 | 10575872.21 | 0.00 | 1.00 | 0.00 | 39869.75 | 31365.43 | 8958.25 | 8632.77 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 47.33 | 15.46 | 31.87 | 33.23 | 110.35 | 0.00 | 0.00 | 0.00 |
February | 83.73 | 35.57 | 48.17 | 73.32 | 103.25 | 0.00 | 0.00 | 0.00 |
March | 75.46 | 14.51 | 60.96 | 56.18 | 80.99 | 0.00 | 0.00 | 0.00 |
April | 177.57 | 70.35 | 107.22 | 196.87 | 70.17 | 0.00 | 0.00 | 0.00 |
May | 208.27 | 84.44 | 123.83 | 226.10 | 61.70 | 0.00 | 0.00 | 0.00 |
June | 225.34 | 92.98 | 132.36 | 254.60 | 54.20 | 0.00 | 0.00 | 0.00 |
July | 229.51 | 101.25 | 128.26 | 265.90 | 54.70 | 0.00 | 0.00 | 0.00 |
August | 192.62 | 83.31 | 109.31 | 224.34 | 61.19 | 0.00 | 0.00 | 0.00 |
September | 155.91 | 70.47 | 85.44 | 177.57 | 71.67 | 0.00 | 0.00 | 0.00 |
October | 82.79 | 29.87 | 52.92 | 79.53 | 80.73 | 0.00 | 0.00 | 0.00 |
November | 44.81 | 13.19 | 31.62 | 31.93 | 96.21 | 0.00 | 0.00 | 0.00 |
December | 25.17 | 5.24 | 19.93 | 10.88 | 125.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 129.18 | 51.40 | 77.77 | 136.06 | 80.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.17 | 5.24 | 19.93 | 10.88 | 54.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 229.51 | 101.25 | 132.36 | 265.90 | 125.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 47.33 | 15.46 | 31.87 | 33.23 | 110.35 | 0.00 | 0.00 | 0.00 |
February | 83.73 | 35.57 | 48.17 | 73.32 | 103.25 | 0.00 | 0.00 | 0.00 |
March | 75.46 | 14.51 | 60.96 | 56.18 | 80.99 | 0.00 | 0.00 | 0.00 |
April | 177.57 | 70.35 | 107.22 | 196.87 | 70.17 | 0.00 | 0.00 | 0.00 |
May | 208.27 | 84.44 | 123.83 | 226.10 | 61.70 | 0.00 | 0.00 | 0.00 |
June | 225.34 | 92.98 | 132.36 | 254.60 | 54.20 | 0.00 | 0.00 | 0.00 |
July | 229.51 | 101.25 | 128.26 | 265.90 | 54.70 | 0.00 | 0.00 | 0.00 |
August | 192.62 | 83.31 | 109.31 | 224.34 | 61.19 | 0.00 | 0.00 | 0.00 |
September | 155.91 | 70.47 | 85.44 | 177.57 | 71.67 | 0.00 | 0.00 | 0.00 |
October | 82.79 | 29.87 | 52.92 | 79.53 | 80.73 | 0.00 | 0.00 | 0.00 |
November | 44.81 | 13.19 | 31.62 | 31.93 | 96.21 | 0.00 | 0.00 | 0.00 |
December | 25.17 | 5.24 | 19.93 | 10.88 | 125.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 129.18 | 51.40 | 77.77 | 136.06 | 80.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.17 | 5.24 | 19.93 | 10.88 | 54.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 229.51 | 101.25 | 132.36 | 265.90 | 125.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.81 | 0.00 | 13.81 | 2.25 | 67.49 | 0.00 | 0.00 | 0.00 |
February | 21.57 | 0.00 | 21.57 | 5.76 | 62.21 | 0.00 | 0.00 | 0.00 |
March | 29.85 | 0.00 | 29.85 | 14.63 | 48.86 | 0.00 | 0.00 | 0.00 |
April | 48.67 | 0.26 | 48.40 | 38.02 | 40.62 | 0.00 | 0.00 | 0.00 |
May | 61.02 | 3.16 | 57.87 | 47.18 | 33.86 | 0.00 | 0.00 | 0.00 |
June | 66.99 | 4.10 | 62.89 | 59.24 | 30.09 | 0.00 | 0.00 | 0.00 |
July | 63.68 | 3.60 | 60.08 | 57.27 | 30.19 | 0.00 | 0.00 | 0.00 |
August | 50.31 | 0.97 | 49.34 | 43.69 | 34.46 | 0.00 | 0.00 | 0.00 |
September | 38.14 | 0.02 | 38.12 | 30.14 | 42.45 | 0.00 | 0.00 | 0.00 |
October | 24.43 | 0.00 | 24.43 | 13.45 | 47.87 | 0.00 | 0.00 | 0.00 |
November | 14.68 | 0.00 | 14.68 | 3.26 | 57.25 | 0.00 | 0.00 | 0.00 |
December | 9.99 | 0.00 | 9.99 | 0.43 | 73.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.00 | 1.02 | 35.98 | 26.38 | 47.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.99 | 0.00 | 9.99 | 0.43 | 30.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.99 | 4.10 | 62.89 | 59.24 | 73.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.81 | 0.00 | 13.81 | 2.25 | 67.49 | 0.00 | 0.00 | 0.00 |
February | 21.57 | 0.00 | 21.57 | 5.76 | 62.21 | 0.00 | 0.00 | 0.00 |
March | 29.85 | 0.00 | 29.85 | 14.63 | 48.86 | 0.00 | 0.00 | 0.00 |
April | 48.67 | 0.26 | 48.40 | 38.02 | 40.62 | 0.00 | 0.00 | 0.00 |
May | 61.02 | 3.16 | 57.87 | 47.18 | 33.86 | 0.00 | 0.00 | 0.00 |
June | 66.98 | 4.10 | 62.89 | 59.23 | 30.09 | 0.00 | 0.00 | 0.00 |
July | 63.68 | 3.60 | 60.08 | 57.26 | 30.19 | 0.00 | 0.00 | 0.00 |
August | 50.31 | 0.97 | 49.34 | 43.69 | 34.46 | 0.00 | 0.00 | 0.00 |
September | 38.14 | 0.02 | 38.12 | 30.14 | 42.45 | 0.00 | 0.00 | 0.00 |
October | 24.42 | 0.00 | 24.42 | 13.45 | 47.87 | 0.00 | 0.00 | 0.00 |
November | 14.68 | 0.00 | 14.68 | 3.26 | 57.25 | 0.00 | 0.00 | 0.00 |
December | 9.99 | 0.00 | 9.99 | 0.43 | 73.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.00 | 1.02 | 35.98 | 26.37 | 47.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.99 | 0.00 | 9.99 | 0.43 | 30.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.98 | 4.10 | 62.89 | 59.23 | 73.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.02 | 36.50 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.04 | 34.69 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.37 | 26.96 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 92.68 | 25.30 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 108.97 | 22.61 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 117.86 | 20.24 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 120.37 | 21.42 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 103.54 | 25.22 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.20 | 28.54 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.43 | 28.46 | 1.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 11.95 | 31.38 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.01 | 40.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.04 | 28.42 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.01 | 20.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 120.37 | 40.07 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.02 | 36.50 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.04 | 34.69 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.37 | 26.96 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 92.68 | 25.30 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 108.97 | 22.61 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 117.86 | 20.24 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 120.37 | 21.42 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 103.54 | 25.22 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.20 | 28.54 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.43 | 28.46 | 1.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 11.95 | 31.38 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.01 | 40.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.04 | 28.42 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.01 | 20.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 120.37 | 40.07 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.02 | 36.50 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.04 | 34.69 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.37 | 26.96 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 92.68 | 25.30 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 108.97 | 22.61 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 117.86 | 20.24 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 120.37 | 21.42 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 103.54 | 25.22 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.20 | 28.54 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.43 | 28.46 | 1.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 11.95 | 31.38 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.01 | 40.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.04 | 28.42 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.01 | 20.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 120.37 | 40.07 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.02 | 36.50 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.04 | 34.69 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.37 | 26.96 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 92.68 | 25.30 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 108.97 | 22.61 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 117.86 | 20.24 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 120.37 | 21.42 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 103.54 | 25.22 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.20 | 28.54 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.43 | 28.46 | 1.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 11.95 | 31.38 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.01 | 40.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.04 | 28.42 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.01 | 20.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 120.37 | 40.07 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.02 | 36.50 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.04 | 34.69 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.37 | 26.96 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 92.68 | 25.30 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 108.97 | 22.61 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 117.86 | 20.24 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 120.37 | 21.42 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 103.54 | 25.22 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.20 | 28.54 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.43 | 28.46 | 1.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 11.95 | 31.38 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.01 | 40.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.04 | 28.42 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.01 | 20.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 120.37 | 40.07 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.02 | 36.50 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.04 | 34.69 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.37 | 26.96 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 92.68 | 25.30 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 108.97 | 22.61 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 117.86 | 20.24 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 120.37 | 21.42 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 103.54 | 25.22 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.20 | 28.54 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.43 | 28.46 | 1.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 11.95 | 31.38 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.01 | 40.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.04 | 28.42 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.01 | 20.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 120.37 | 40.07 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.02 | 36.50 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.04 | 34.69 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.37 | 26.96 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 92.68 | 25.30 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 108.97 | 22.61 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 117.86 | 20.24 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 120.37 | 21.42 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 103.54 | 25.22 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.20 | 28.54 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.43 | 28.46 | 1.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 11.95 | 31.38 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.01 | 40.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.04 | 28.42 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.01 | 20.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 120.37 | 40.07 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.02 | 36.50 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.04 | 34.69 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.37 | 26.96 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 92.68 | 25.30 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 108.97 | 22.61 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 117.86 | 20.24 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 120.37 | 21.42 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 103.54 | 25.22 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.20 | 28.54 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.43 | 28.46 | 1.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 11.95 | 31.38 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.01 | 40.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.04 | 28.42 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.01 | 20.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 120.37 | 40.07 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.02 | 36.50 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.04 | 34.69 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.37 | 26.96 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 92.68 | 25.30 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 108.97 | 22.61 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 117.86 | 20.24 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 120.37 | 21.42 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 103.54 | 25.22 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.20 | 28.54 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.43 | 28.46 | 1.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 11.95 | 31.38 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.01 | 40.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.04 | 28.42 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.01 | 20.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 120.37 | 40.07 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.02 | 36.50 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.04 | 34.69 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.37 | 26.96 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 92.68 | 25.30 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 108.97 | 22.61 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 117.86 | 20.24 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 120.37 | 21.42 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 103.54 | 25.22 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.20 | 28.54 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.43 | 28.46 | 1.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 11.95 | 31.38 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.01 | 40.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.04 | 28.42 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.01 | 20.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 120.37 | 40.07 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.02 | 36.50 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.04 | 34.69 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.37 | 26.96 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 92.68 | 25.30 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 108.97 | 22.61 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 117.86 | 20.24 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 120.37 | 21.42 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 103.54 | 25.22 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.20 | 28.54 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.43 | 28.46 | 1.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 11.95 | 31.38 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.01 | 40.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.04 | 28.42 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.01 | 20.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 120.37 | 40.07 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.02 | 36.50 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.04 | 34.69 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.37 | 26.96 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 92.68 | 25.30 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 108.97 | 22.61 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 117.86 | 20.24 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 120.37 | 21.42 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 103.54 | 25.22 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.20 | 28.54 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.43 | 28.46 | 1.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 11.95 | 31.38 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.01 | 40.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.04 | 28.42 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.01 | 20.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 120.37 | 40.07 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.02 | 36.50 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.04 | 34.69 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.37 | 26.96 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 92.68 | 25.30 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 108.97 | 22.61 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 117.86 | 20.24 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 120.37 | 21.42 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 103.54 | 25.22 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.20 | 28.54 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.43 | 28.46 | 1.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 11.95 | 31.38 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.01 | 40.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.04 | 28.42 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.01 | 20.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 120.37 | 40.07 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.26 | 3.42 | 10.83 | 10.02 | 36.50 | 0.00 | 0.00 | 0.00 |
February | 25.15 | 8.37 | 16.78 | 22.04 | 34.69 | 0.00 | 0.00 | 0.00 |
March | 32.44 | 6.03 | 26.41 | 30.37 | 26.96 | 0.00 | 0.00 | 0.00 |
April | 79.26 | 42.44 | 36.82 | 92.68 | 25.30 | 0.00 | 0.00 | 0.00 |
May | 95.61 | 53.12 | 42.49 | 108.97 | 22.61 | 0.00 | 0.00 | 0.00 |
June | 101.94 | 55.33 | 46.61 | 117.86 | 20.24 | 0.00 | 0.00 | 0.00 |
July | 103.40 | 60.53 | 42.87 | 120.37 | 21.42 | 0.00 | 0.00 | 0.00 |
August | 88.82 | 53.78 | 35.04 | 103.54 | 25.22 | 0.00 | 0.00 | 0.00 |
September | 64.43 | 38.10 | 26.33 | 74.20 | 28.54 | 0.00 | 0.00 | 0.00 |
October | 32.69 | 13.95 | 18.74 | 33.43 | 28.46 | 1.83 | 0.00 | 0.00 |
November | 15.76 | 4.16 | 11.60 | 11.95 | 31.38 | 0.00 | 0.00 | 0.00 |
December | 9.95 | 2.09 | 7.86 | 5.01 | 40.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.45 | 28.54 | 26.91 | 61.04 | 28.42 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 9.95 | 2.09 | 7.86 | 5.01 | 20.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.40 | 60.53 | 46.61 | 120.37 | 40.07 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.16 | 5.71 | 14.46 | 21.35 | 37.89 | 163.00 | 0.00 | 0.00 |
February | 34.95 | 12.56 | 22.39 | 40.62 | 37.15 | 132.00 | 0.00 | 0.00 |
March | 43.52 | 8.27 | 35.25 | 52.77 | 28.11 | 55.67 | 0.00 | 0.00 |
April | 105.39 | 56.25 | 49.14 | 140.66 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 126.24 | 69.53 | 56.71 | 161.10 | 32.94 | 8.00 | 0.00 | 0.00 |
June | 134.50 | 72.29 | 62.21 | 174.00 | 29.70 | 5.50 | 0.00 | 0.00 |
July | 136.33 | 79.12 | 57.21 | 176.49 | 32.50 | 3.67 | 0.00 | 0.00 |
August | 117.47 | 70.70 | 46.76 | 152.28 | 38.21 | 1.50 | 0.00 | 0.00 |
September | 86.66 | 51.53 | 35.13 | 111.74 | 41.72 | 55.50 | 0.00 | 0.00 |
October | 44.53 | 19.52 | 25.01 | 53.22 | 37.69 | 123.50 | 0.00 | 0.00 |
November | 22.00 | 6.52 | 15.47 | 23.77 | 32.62 | 89.67 | 0.00 | 0.00 |
December | 14.04 | 3.55 | 10.49 | 12.28 | 41.21 | 54.67 | 0.00 | 0.00 |
Annual Sum or Average | 73.99 | 38.08 | 35.91 | 93.58 | 35.27 | 692.67 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 3.55 | 10.49 | 12.28 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.33 | 79.12 | 62.21 | 176.49 | 41.72 | 163.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126781E+09 | 41421035.00 | 85359724.23 | 88991750.27 | 0.295572E+09 |
February | 0.202565E+09 | 86042013.35 | 0.116523E+09 | 0.177375E+09 | 0.249788E+09 |
March | 0.202120E+09 | 38851759.88 | 0.163269E+09 | 0.150469E+09 | 0.216918E+09 |
April | 0.460258E+09 | 0.182350E+09 | 0.277908E+09 | 0.510299E+09 | 0.181882E+09 |
May | 0.557831E+09 | 0.226153E+09 | 0.331678E+09 | 0.605584E+09 | 0.165261E+09 |
June | 0.584093E+09 | 0.241003E+09 | 0.343090E+09 | 0.659919E+09 | 0.140498E+09 |
July | 0.614712E+09 | 0.271188E+09 | 0.343524E+09 | 0.712197E+09 | 0.146521E+09 |
August | 0.515907E+09 | 0.223125E+09 | 0.292783E+09 | 0.600879E+09 | 0.163895E+09 |
September | 0.404128E+09 | 0.182659E+09 | 0.221469E+09 | 0.460265E+09 | 0.185773E+09 |
October | 0.221745E+09 | 79998991.38 | 0.141746E+09 | 0.213026E+09 | 0.216216E+09 |
November | 0.116157E+09 | 34196504.77 | 81960929.17 | 82773938.60 | 0.249374E+09 |
December | 67413167.84 | 14032114.69 | 53381053.14 | 29145431.40 | 0.335720E+09 |
Annual Sum or Average | 0.407371E+10 | 0.162102E+10 | 0.245269E+10 | 0.429092E+10 | 0.254742E+10 |
Minimum of Months | 67413167.84 | 14032114.69 | 53381053.14 | 29145431.40 | 0.140498E+09 |
Maximum of Months | 0.614712E+09 | 0.271188E+09 | 0.343524E+09 | 0.712197E+09 | 0.335720E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126781E+09 | 41421035.00 | 85359724.23 | 88991750.27 | 0.295572E+09 |
February | 0.202565E+09 | 86042013.35 | 0.116523E+09 | 0.177375E+09 | 0.249788E+09 |
March | 0.202120E+09 | 38851759.88 | 0.163269E+09 | 0.150469E+09 | 0.216918E+09 |
April | 0.460258E+09 | 0.182350E+09 | 0.277908E+09 | 0.510299E+09 | 0.181882E+09 |
May | 0.557831E+09 | 0.226153E+09 | 0.331678E+09 | 0.605584E+09 | 0.165261E+09 |
June | 0.584093E+09 | 0.241003E+09 | 0.343090E+09 | 0.659919E+09 | 0.140498E+09 |
July | 0.614712E+09 | 0.271188E+09 | 0.343524E+09 | 0.712197E+09 | 0.146521E+09 |
August | 0.515907E+09 | 0.223125E+09 | 0.292783E+09 | 0.600879E+09 | 0.163895E+09 |
September | 0.404128E+09 | 0.182659E+09 | 0.221469E+09 | 0.460265E+09 | 0.185773E+09 |
October | 0.221745E+09 | 79998991.38 | 0.141746E+09 | 0.213026E+09 | 0.216216E+09 |
November | 0.116157E+09 | 34196504.77 | 81960929.17 | 82773938.60 | 0.249374E+09 |
December | 67413167.84 | 14032114.69 | 53381053.14 | 29145431.40 | 0.335720E+09 |
Annual Sum or Average | 0.407371E+10 | 0.162102E+10 | 0.245269E+10 | 0.429092E+10 | 0.254742E+10 |
Minimum of Months | 67413167.84 | 14032114.69 | 53381053.14 | 29145431.40 | 0.140498E+09 |
Maximum of Months | 0.614712E+09 | 0.271188E+09 | 0.343524E+09 | 0.712197E+09 | 0.335720E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36996128.09 | 0.00 | 36996128.09 | 6036307.77 | 0.180752E+09 |
February | 52180276.64 | 0.00 | 52180276.64 | 13930388.05 | 0.150494E+09 |
March | 79953231.58 | 1133.24 | 79952098.34 | 39197277.87 | 0.130866E+09 |
April | 0.126147E+09 | 682750.86 | 0.125465E+09 | 98546410.70 | 0.105288E+09 |
May | 0.163449E+09 | 8457423.59 | 0.154992E+09 | 0.126364E+09 | 90691369.05 |
June | 0.173628E+09 | 10620006.69 | 0.163008E+09 | 0.153539E+09 | 77987104.66 |
July | 0.170570E+09 | 9645341.69 | 0.160924E+09 | 0.153383E+09 | 80853495.34 |
August | 0.134754E+09 | 2610657.95 | 0.132144E+09 | 0.117023E+09 | 92303809.25 |
September | 98871495.97 | 59436.37 | 98812059.59 | 78133684.86 | 0.110036E+09 |
October | 65420331.74 | 0.00 | 65420331.74 | 36028714.55 | 0.128209E+09 |
November | 38039882.33 | 0.00 | 38039882.33 | 8455204.55 | 0.148393E+09 |
December | 26768561.36 | 0.00 | 26768561.36 | 1163401.71 | 0.197817E+09 |
Annual Sum or Average | 0.116678E+10 | 32076750.38 | 0.113470E+10 | 0.831801E+09 | 0.149369E+10 |
Minimum of Months | 26768561.36 | 0.00 | 26768561.36 | 1163401.71 | 77987104.66 |
Maximum of Months | 0.173628E+09 | 10620006.69 | 0.163008E+09 | 0.153539E+09 | 0.197817E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36994860.08 | 0.00 | 36994860.08 | 6035637.20 | 0.180752E+09 |
February | 52178534.12 | 0.00 | 52178534.12 | 13929005.39 | 0.150494E+09 |
March | 79950383.50 | 1133.19 | 79949250.31 | 39194353.68 | 0.130866E+09 |
April | 0.126144E+09 | 682718.86 | 0.125461E+09 | 98541995.16 | 0.105288E+09 |
May | 0.163444E+09 | 8457027.18 | 0.154987E+09 | 0.126358E+09 | 90691079.42 |
June | 0.173622E+09 | 10619508.92 | 0.163003E+09 | 0.153532E+09 | 77986831.28 |
July | 0.170564E+09 | 9644889.59 | 0.160919E+09 | 0.153377E+09 | 80853093.14 |
August | 0.134750E+09 | 2610535.58 | 0.132140E+09 | 0.117018E+09 | 92303247.84 |
September | 98868606.10 | 59433.59 | 98809172.51 | 78130603.75 | 0.110036E+09 |
October | 65418197.57 | 0.00 | 65418197.57 | 36026646.06 | 0.128209E+09 |
November | 38038575.26 | 0.00 | 38038575.26 | 8454349.78 | 0.148393E+09 |
December | 26767629.89 | 0.00 | 26767629.89 | 1163151.82 | 0.197817E+09 |
Annual Sum or Average | 0.116674E+10 | 32075246.90 | 0.113467E+10 | 0.831761E+09 | 0.149369E+10 |
Minimum of Months | 26767629.89 | 0.00 | 26767629.89 | 1163151.82 | 77986831.28 |
Maximum of Months | 0.173622E+09 | 10619508.92 | 0.163003E+09 | 0.153532E+09 | 0.197817E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26830181.66 | 97773433.00 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53321864.53 | 83932700.24 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81330250.39 | 72215794.96 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.240226E+09 | 65573351.10 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.291857E+09 | 60550924.24 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.305485E+09 | 52466028.21 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.322388E+09 | 57383463.42 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.277330E+09 | 67554994.21 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.192319E+09 | 73986643.87 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 89530922.64 | 76224890.22 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 30973897.63 | 81338795.06 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 0.107328E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.192500E+10 | 0.896329E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 52466028.21 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.322388E+09 | 0.107328E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26830181.66 | 97773433.00 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53321864.53 | 83932700.24 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81330250.39 | 72215794.96 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.240226E+09 | 65573351.10 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.291857E+09 | 60550924.24 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.305485E+09 | 52466028.21 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.322388E+09 | 57383463.42 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.277330E+09 | 67554994.21 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.192319E+09 | 73986643.87 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 89530922.64 | 76224890.22 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 30973897.63 | 81338795.06 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 0.107328E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.192500E+10 | 0.896329E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 52466028.21 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.322388E+09 | 0.107328E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26830181.66 | 97773433.00 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53321864.53 | 83932700.24 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81330250.39 | 72215794.96 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.240226E+09 | 65573351.10 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.291857E+09 | 60550924.24 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.305485E+09 | 52466028.21 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.322388E+09 | 57383463.42 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.277330E+09 | 67554994.21 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.192319E+09 | 73986643.87 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 89530922.64 | 76224890.22 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 30973897.63 | 81338795.06 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 0.107328E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.192500E+10 | 0.896329E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 52466028.21 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.322388E+09 | 0.107328E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26830181.66 | 97773433.00 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53321864.53 | 83932700.24 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81330250.39 | 72215794.96 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.240226E+09 | 65573351.10 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.291857E+09 | 60550924.24 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.305485E+09 | 52466028.21 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.322388E+09 | 57383463.42 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.277330E+09 | 67554994.21 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.192319E+09 | 73986643.87 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 89530922.64 | 76224890.22 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 30973897.63 | 81338795.06 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 0.107328E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.192500E+10 | 0.896329E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 52466028.21 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.322388E+09 | 0.107328E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26830181.66 | 97773433.00 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53321864.53 | 83932700.24 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81330250.39 | 72215794.96 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.240226E+09 | 65573351.10 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.291857E+09 | 60550924.24 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.305485E+09 | 52466028.21 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.322388E+09 | 57383463.42 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.277330E+09 | 67554994.21 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.192319E+09 | 73986643.87 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 89530922.64 | 76224890.22 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 30973897.63 | 81338795.06 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 0.107328E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.192500E+10 | 0.896329E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 52466028.21 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.322388E+09 | 0.107328E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26830181.66 | 97773433.00 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53321864.53 | 83932700.24 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81330250.39 | 72215794.96 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.240226E+09 | 65573351.10 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.291857E+09 | 60550924.24 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.305485E+09 | 52466028.21 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.322388E+09 | 57383463.42 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.277330E+09 | 67554994.21 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.192319E+09 | 73986643.87 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 89530922.64 | 76224890.22 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 30973897.63 | 81338795.06 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 0.107328E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.192500E+10 | 0.896329E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 52466028.21 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.322388E+09 | 0.107328E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26830181.66 | 97773433.00 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53321864.53 | 83932700.24 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81330250.39 | 72215794.96 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.240226E+09 | 65573351.10 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.291857E+09 | 60550924.24 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.305485E+09 | 52466028.21 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.322388E+09 | 57383463.42 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.277330E+09 | 67554994.21 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.192319E+09 | 73986643.87 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 89530922.64 | 76224890.22 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 30973897.63 | 81338795.06 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 0.107328E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.192500E+10 | 0.896329E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 52466028.21 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.322388E+09 | 0.107328E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26830181.66 | 97773433.00 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53321864.53 | 83932700.24 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81330250.39 | 72215794.96 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.240226E+09 | 65573351.10 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.291857E+09 | 60550924.24 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.305485E+09 | 52466028.21 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.322388E+09 | 57383463.42 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.277330E+09 | 67554994.21 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.192319E+09 | 73986643.87 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 89530922.64 | 76224890.22 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 30973897.63 | 81338795.06 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 0.107328E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.192500E+10 | 0.896329E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 52466028.21 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.322388E+09 | 0.107328E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26830181.66 | 97773433.00 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53321864.53 | 83932700.24 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81330250.39 | 72215794.96 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.240226E+09 | 65573351.10 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.291857E+09 | 60550924.24 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.305485E+09 | 52466028.21 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.322388E+09 | 57383463.42 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.277330E+09 | 67554994.21 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.192319E+09 | 73986643.87 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 89530922.64 | 76224890.22 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 30973897.63 | 81338795.06 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 0.107328E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.192500E+10 | 0.896329E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 52466028.21 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.322388E+09 | 0.107328E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26830181.66 | 97773433.00 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53321864.53 | 83932700.24 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81330250.39 | 72215794.96 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.240226E+09 | 65573351.10 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.291857E+09 | 60550924.24 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.305485E+09 | 52466028.21 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.322388E+09 | 57383463.42 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.277330E+09 | 67554994.21 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.192319E+09 | 73986643.87 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 89530922.64 | 76224890.22 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 30973897.63 | 81338795.06 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 0.107328E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.192500E+10 | 0.896329E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 52466028.21 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.322388E+09 | 0.107328E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26830181.66 | 97773433.00 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53321864.53 | 83932700.24 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81330250.39 | 72215794.96 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.240226E+09 | 65573351.10 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.291857E+09 | 60550924.24 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.305485E+09 | 52466028.21 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.322388E+09 | 57383463.42 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.277330E+09 | 67554994.21 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.192319E+09 | 73986643.87 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 89530922.64 | 76224890.22 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 30973897.63 | 81338795.06 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 0.107328E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.192500E+10 | 0.896329E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 52466028.21 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.322388E+09 | 0.107328E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26830181.66 | 97773433.00 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53321864.53 | 83932700.24 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81330250.39 | 72215794.96 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.240226E+09 | 65573351.10 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.291857E+09 | 60550924.24 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.305485E+09 | 52466028.21 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.322388E+09 | 57383463.42 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.277330E+09 | 67554994.21 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.192319E+09 | 73986643.87 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 89530922.64 | 76224890.22 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 30973897.63 | 81338795.06 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 0.107328E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.192500E+10 | 0.896329E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 52466028.21 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.322388E+09 | 0.107328E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26830181.66 | 97773433.00 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53321864.53 | 83932700.24 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81330250.39 | 72215794.96 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.240226E+09 | 65573351.10 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.291857E+09 | 60550924.24 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.305485E+09 | 52466028.21 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.322388E+09 | 57383463.42 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.277330E+09 | 67554994.21 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.192319E+09 | 73986643.87 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 89530922.64 | 76224890.22 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 30973897.63 | 81338795.06 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 0.107328E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.192500E+10 | 0.896329E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 52466028.21 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.322388E+09 | 0.107328E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38185704.70 | 9173497.30 | 29012207.41 | 26830181.66 | 97773433.00 |
February | 60837733.52 | 20251044.34 | 40586689.19 | 53321864.53 | 83932700.24 |
March | 86898645.57 | 16152345.49 | 70746300.08 | 81330250.39 | 72215794.96 |
April | 0.205453E+09 | 0.110014E+09 | 95439119.60 | 0.240226E+09 | 65573351.10 |
May | 0.256091E+09 | 0.142273E+09 | 0.113818E+09 | 0.291857E+09 | 60550924.24 |
June | 0.264232E+09 | 0.143407E+09 | 0.120825E+09 | 0.305485E+09 | 52466028.21 |
July | 0.276955E+09 | 0.162135E+09 | 0.114820E+09 | 0.322388E+09 | 57383463.42 |
August | 0.237900E+09 | 0.144045E+09 | 93855067.25 | 0.277330E+09 | 67554994.21 |
September | 0.166994E+09 | 98759618.45 | 68234460.25 | 0.192319E+09 | 73986643.87 |
October | 87560070.01 | 37369770.18 | 50190299.83 | 89530922.64 | 76224890.22 |
November | 40847068.61 | 10792764.82 | 30054303.79 | 30973897.63 | 81338795.06 |
December | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 0.107328E+09 |
Annual Sum or Average | 0.174861E+10 | 0.899967E+09 | 0.848640E+09 | 0.192500E+10 | 0.896329E+09 |
Minimum of Months | 26652813.04 | 5594260.70 | 21058552.34 | 13409155.23 | 52466028.21 |
Maximum of Months | 0.276955E+09 | 0.162135E+09 | 0.120825E+09 | 0.322388E+09 | 0.107328E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54002546.71 | 15286140.68 | 38716406.03 | 57177958.08 | 0.101489E+09 |
February | 84539819.62 | 30377421.15 | 54162398.47 | 98275231.68 | 89873933.37 |
March | 0.116560E+09 | 22150210.50 | 94409999.25 | 0.141339E+09 | 75286469.36 |
April | 0.273172E+09 | 0.145810E+09 | 0.127362E+09 | 0.364583E+09 | 86903109.75 |
May | 0.338115E+09 | 0.186227E+09 | 0.151889E+09 | 0.431502E+09 | 88224155.11 |
June | 0.348627E+09 | 0.187388E+09 | 0.161239E+09 | 0.451001E+09 | 76985701.36 |
July | 0.365143E+09 | 0.211917E+09 | 0.153226E+09 | 0.472712E+09 | 87053231.32 |
August | 0.314623E+09 | 0.189375E+09 | 0.125248E+09 | 0.407863E+09 | 0.102343E+09 |
September | 0.224635E+09 | 0.133577E+09 | 91057982.31 | 0.289642E+09 | 0.108143E+09 |
October | 0.119266E+09 | 52287417.73 | 66978289.53 | 0.142539E+09 | 0.100960E+09 |
November | 57014896.83 | 16907826.99 | 40107069.84 | 61603106.21 | 84547475.94 |
December | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 0.110378E+09 |
Annual Sum or Average | 0.233330E+10 | 0.120080E+10 | 0.113250E+10 | 0.295112E+10 | 0.111219E+10 |
Minimum of Months | 37602936.97 | 9500578.15 | 28102358.83 | 32878132.37 | 75286469.36 |
Maximum of Months | 0.365143E+09 | 0.211917E+09 | 0.161239E+09 | 0.472712E+09 | 0.110378E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 66.07 | 350.79 | 122.29 | 30.93 | 91.36 | 0.00 | 0.00 |
February | 154.84 | 327.60 | 210.60 | 71.13 | 139.47 | 0.00 | 0.00 |
March | 139.23 | 257.30 | 210.63 | 29.01 | 181.62 | 0.00 | 0.00 |
April | 468.51 | 220.30 | 452.47 | 141.23 | 311.24 | 0.00 | 0.00 |
May | 543.79 | 188.36 | 538.59 | 175.19 | 363.40 | 0.00 | 0.00 |
June | 624.91 | 165.83 | 584.66 | 194.15 | 390.51 | 0.00 | 0.00 |
July | 643.74 | 167.18 | 586.38 | 209.70 | 376.68 | 0.00 | 0.00 |
August | 534.81 | 190.05 | 485.86 | 168.56 | 317.30 | 0.00 | 0.00 |
September | 413.75 | 226.56 | 388.12 | 140.99 | 247.13 | 0.00 | 0.00 |
October | 184.32 | 255.54 | 214.43 | 59.74 | 154.69 | 0.00 | 0.00 |
November | 68.31 | 304.84 | 118.98 | 26.39 | 92.59 | 0.00 | 0.00 |
December | 21.03 | 396.80 | 70.33 | 10.48 | 59.85 | 0.00 | 0.00 |
Annual Sum or Average | 322.53 | 253.93 | 332.35 | 104.84 | 227.51 | 0.00 | 0.00 |
Minimum of Months | 21.03 | 165.83 | 70.33 | 10.48 | 59.85 | 0.00 | 0.00 |
Maximum of Months | 643.74 | 396.80 | 586.38 | 209.70 | 390.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 140.24 | 511.06 | 199.60 | 47.95 | 151.65 | 0.00 | 0.00 |
February | 308.58 | 485.72 | 352.07 | 117.19 | 234.88 | 0.00 | 0.00 |
March | 425.11 | 377.47 | 454.22 | 84.43 | 369.79 | 0.00 | 0.00 |
April | 1297.52 | 354.18 | 1109.70 | 594.21 | 515.49 | 0.00 | 0.00 |
May | 1525.53 | 316.50 | 1338.59 | 743.66 | 594.93 | 0.00 | 0.00 |
June | 1650.00 | 283.38 | 1427.18 | 774.57 | 652.60 | 0.00 | 0.00 |
July | 1685.12 | 299.94 | 1447.64 | 847.48 | 600.16 | 0.00 | 0.00 |
August | 1449.61 | 353.11 | 1243.51 | 752.92 | 490.58 | 0.00 | 0.00 |
September | 1038.76 | 399.62 | 901.97 | 533.42 | 368.55 | 0.00 | 0.00 |
October | 467.98 | 398.43 | 457.68 | 195.33 | 262.34 | 0.00 | 0.00 |
November | 167.30 | 439.33 | 220.62 | 58.29 | 162.33 | 0.00 | 0.00 |
December | 70.09 | 561.00 | 139.31 | 29.24 | 110.07 | 0.00 | 0.00 |
Annual Sum or Average | 854.58 | 397.91 | 776.27 | 399.53 | 376.74 | 0.00 | 0.00 |
Minimum of Months | 70.09 | 283.38 | 139.31 | 29.24 | 110.07 | 0.00 | 0.00 |
Maximum of Months | 1685.12 | 561.00 | 1447.64 | 847.48 | 652.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2882.29 | 6844.57 | 645.19 | 182.63 | 462.56 | 0.00 | 0.00 |
February | 5273.44 | 6706.53 | 1118.25 | 401.82 | 716.43 | 0.00 | 0.00 |
March | 6822.96 | 4836.18 | 1392.60 | 264.64 | 1127.96 | 0.00 | 0.00 |
April | 18474.66 | 3851.72 | 3372.49 | 1800.12 | 1572.37 | 0.00 | 0.00 |
May | 21014.79 | 3387.88 | 4039.61 | 2224.93 | 1814.68 | 0.00 | 0.00 |
June | 22624.65 | 2884.16 | 4304.04 | 2313.43 | 1990.61 | 0.00 | 0.00 |
July | 21712.17 | 3146.25 | 4362.52 | 2531.86 | 1830.65 | 0.00 | 0.00 |
August | 18907.79 | 3669.82 | 3758.94 | 2262.54 | 1496.40 | 0.00 | 0.00 |
September | 14114.68 | 4118.13 | 2773.27 | 1649.09 | 1124.17 | 0.00 | 0.00 |
October | 7091.77 | 4565.96 | 1424.92 | 624.70 | 800.22 | 0.00 | 0.00 |
November | 2956.26 | 5523.23 | 703.89 | 208.74 | 495.15 | 0.00 | 0.00 |
December | 1698.37 | 7557.63 | 449.26 | 113.51 | 335.75 | 0.00 | 0.00 |
Annual Sum or Average | 11991.23 | 4748.92 | 2367.63 | 1218.47 | 1149.16 | 0.00 | 0.00 |
Minimum of Months | 1698.37 | 2884.16 | 449.26 | 113.51 | 335.75 | 0.00 | 0.00 |
Maximum of Months | 22624.65 | 7557.63 | 4362.52 | 2531.86 | 1990.61 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.176952E+09 | 0.939545E+09 | 0.327553E+09 | 82842070.00 | 0.244710E+09 | 0.00 | 0.00 |
February | 0.374582E+09 | 0.792536E+09 | 0.509489E+09 | 0.172084E+09 | 0.337405E+09 | 0.00 | 0.00 |
March | 0.372909E+09 | 0.689147E+09 | 0.564145E+09 | 77705786.18 | 0.486439E+09 | 0.00 | 0.00 |
April | 0.121437E+10 | 0.571018E+09 | 0.117281E+10 | 0.366066E+09 | 0.806741E+09 | 0.00 | 0.00 |
May | 0.145648E+10 | 0.504496E+09 | 0.144256E+10 | 0.469220E+09 | 0.973335E+09 | 0.00 | 0.00 |
June | 0.161977E+10 | 0.429833E+09 | 0.151544E+10 | 0.503246E+09 | 0.101219E+10 | 0.00 | 0.00 |
July | 0.172419E+10 | 0.447781E+09 | 0.157056E+10 | 0.561666E+09 | 0.100889E+10 | 0.00 | 0.00 |
August | 0.143244E+10 | 0.509038E+09 | 0.130132E+10 | 0.451470E+09 | 0.849849E+09 | 0.00 | 0.00 |
September | 0.107243E+10 | 0.587253E+09 | 0.100600E+10 | 0.365437E+09 | 0.640559E+09 | 0.00 | 0.00 |
October | 0.493696E+09 | 0.684439E+09 | 0.574329E+09 | 0.159998E+09 | 0.414331E+09 | 0.00 | 0.00 |
November | 0.177062E+09 | 0.790139E+09 | 0.308393E+09 | 68393009.55 | 0.240000E+09 | 0.00 | 0.00 |
December | 56326831.07 | 0.106278E+10 | 0.188363E+09 | 28064229.39 | 0.160298E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101712E+11 | 0.800801E+10 | 0.104809E+11 | 0.330619E+10 | 0.717475E+10 | 0.00 | 0.00 |
Minimum of Months | 56326831.07 | 0.429833E+09 | 0.188363E+09 | 28064229.39 | 0.160298E+09 | 0.00 | 0.00 |
Maximum of Months | 0.172419E+10 | 0.106278E+10 | 0.157056E+10 | 0.561666E+09 | 0.101219E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.375623E+09 | 0.136883E+10 | 0.534600E+09 | 0.128429E+09 | 0.406171E+09 | 0.00 | 0.00 |
February | 0.746506E+09 | 0.117506E+10 | 0.851728E+09 | 0.283515E+09 | 0.568214E+09 | 0.00 | 0.00 |
March | 0.113862E+10 | 0.101102E+10 | 0.121658E+10 | 0.226133E+09 | 0.990448E+09 | 0.00 | 0.00 |
April | 0.336317E+10 | 0.918027E+09 | 0.287635E+10 | 0.154020E+10 | 0.133615E+10 | 0.00 | 0.00 |
May | 0.408599E+10 | 0.847713E+09 | 0.358528E+10 | 0.199183E+10 | 0.159345E+10 | 0.00 | 0.00 |
June | 0.427679E+10 | 0.734524E+09 | 0.369925E+10 | 0.200770E+10 | 0.169155E+10 | 0.00 | 0.00 |
July | 0.451343E+10 | 0.803368E+09 | 0.387737E+10 | 0.226989E+10 | 0.160748E+10 | 0.00 | 0.00 |
August | 0.388263E+10 | 0.945770E+09 | 0.333060E+10 | 0.201663E+10 | 0.131397E+10 | 0.00 | 0.00 |
September | 0.269247E+10 | 0.103581E+10 | 0.233792E+10 | 0.138263E+10 | 0.955282E+09 | 0.00 | 0.00 |
October | 0.125343E+10 | 0.106715E+10 | 0.122584E+10 | 0.523177E+09 | 0.702664E+09 | 0.00 | 0.00 |
November | 0.433635E+09 | 0.113874E+10 | 0.571859E+09 | 0.151099E+09 | 0.420760E+09 | 0.00 | 0.00 |
December | 0.187728E+09 | 0.150259E+10 | 0.373139E+09 | 78319649.82 | 0.294820E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.269500E+11 | 0.125486E+11 | 0.244805E+11 | 0.125995E+11 | 0.118810E+11 | 0.00 | 0.00 |
Minimum of Months | 0.187728E+09 | 0.734524E+09 | 0.373139E+09 | 78319649.82 | 0.294820E+09 | 0.00 | 0.00 |
Maximum of Months | 0.451343E+10 | 0.150259E+10 | 0.387737E+10 | 0.226989E+10 | 0.169155E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.771992E+10 | 0.183325E+11 | 0.172808E+10 | 0.489157E+09 | 0.123892E+10 | 0.00 | 0.00 |
February | 0.127575E+11 | 0.162244E+11 | 0.270527E+10 | 0.972077E+09 | 0.173320E+10 | 0.00 | 0.00 |
March | 0.182746E+11 | 0.129532E+11 | 0.372993E+10 | 0.708807E+09 | 0.302112E+10 | 0.00 | 0.00 |
April | 0.478863E+11 | 0.998366E+10 | 0.874150E+10 | 0.466590E+10 | 0.407559E+10 | 0.00 | 0.00 |
May | 0.562860E+11 | 0.907409E+10 | 0.108197E+11 | 0.595926E+10 | 0.486043E+10 | 0.00 | 0.00 |
June | 0.586431E+11 | 0.747574E+10 | 0.111561E+11 | 0.599642E+10 | 0.515966E+10 | 0.00 | 0.00 |
July | 0.581539E+11 | 0.842693E+10 | 0.116846E+11 | 0.678135E+10 | 0.490323E+10 | 0.00 | 0.00 |
August | 0.506426E+11 | 0.982925E+10 | 0.100679E+11 | 0.605999E+10 | 0.400795E+10 | 0.00 | 0.00 |
September | 0.365853E+11 | 0.106742E+11 | 0.718830E+10 | 0.427445E+10 | 0.291386E+10 | 0.00 | 0.00 |
October | 0.189946E+11 | 0.122295E+11 | 0.381650E+10 | 0.167320E+10 | 0.214331E+10 | 0.00 | 0.00 |
November | 0.766263E+10 | 0.143162E+11 | 0.182448E+10 | 0.541050E+09 | 0.128343E+10 | 0.00 | 0.00 |
December | 0.454890E+10 | 0.202423E+11 | 0.120329E+10 | 0.304019E+09 | 0.899275E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.378155E+12 | 0.149762E+12 | 0.746656E+11 | 0.384257E+11 | 0.362400E+11 | 0.00 | 0.00 |
Minimum of Months | 0.454890E+10 | 0.747574E+10 | 0.120329E+10 | 0.304019E+09 | 0.899275E+09 | 0.00 | 0.00 |
Maximum of Months | 0.586431E+11 | 0.202423E+11 | 0.116846E+11 | 0.678135E+10 | 0.515966E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.23 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -1.9 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.24 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.07 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.27 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.49 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.75 | 10.65 | 2.92 | 3.95 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.43 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.66 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.75 | 10.65 | 3.35 | 4.49 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.37 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.22 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.13 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.08 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.53 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.80 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.18 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.22 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.10 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.01 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.64 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.64 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.53 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -7.0 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.9 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.05 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.5 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -7.0 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.08 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.31 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.06 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.54 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.01 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.95 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.45 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.54 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.956166E+09 | -869200614.1 | 0.00 | 0.00 | 744.00 | 0.00 | -86965287.5 | 59.00 | 0.00 | 0.00 |
February | 0.882373E+09 | -803827098.7 | 0.00 | 0.00 | 672.00 | 0.00 | -78545838.6 | 58.99 | 0.00 | 0.00 |
March | 0.101926E+10 | -933137977.9 | 0.00 | 0.00 | 744.00 | 0.00 | -86118540.2 | 59.00 | 0.00 | 0.00 |
April | 0.930953E+09 | -850512116.5 | 0.00 | 0.00 | 720.00 | 0.00 | -80440598.6 | 58.99 | 0.00 | 0.00 |
May | 0.942655E+09 | -860907407.3 | 0.00 | 0.00 | 744.00 | 0.00 | -81747982.3 | 58.99 | 0.00 | 0.00 |
June | 0.909476E+09 | -834458639.2 | 0.00 | 0.00 | 720.00 | 0.00 | -75017624.0 | 58.99 | 0.00 | 0.00 |
July | 0.865307E+09 | -789599129.4 | 0.00 | 0.00 | 744.00 | 0.00 | -75707880.1 | 58.99 | 0.00 | 0.00 |
August | 0.916801E+09 | -841423223.3 | 0.00 | 0.00 | 744.00 | 0.00 | -75377923.4 | 58.99 | 0.00 | 0.00 |
September | 0.863463E+09 | -788056433.7 | 0.00 | 0.00 | 720.00 | 0.00 | -75406379.0 | 58.99 | 0.00 | 0.00 |
October | 0.890533E+09 | -806677782.7 | 0.00 | 0.00 | 744.00 | 0.00 | -83855174.2 | 58.99 | 0.00 | 0.00 |
November | 0.880247E+09 | -796610761.4 | 0.00 | 0.00 | 720.00 | 0.00 | -83635856.2 | 59.00 | 0.00 | 0.00 |
December | 0.939157E+09 | -851914763.4 | 0.00 | 0.00 | 744.00 | 0.00 | -87242265.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.109964E+11 | -0.100263E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -970061349.6 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.863463E+09 | -933137977.9 | 0.00 | 0.00 | 672.00 | 0.00 | -87242265.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.101926E+10 | -788056433.7 | 0.00 | 0.00 | 744.00 | 0.00 | -75017624.0 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.96 | 0.83 | 01-JAN-12:30 | 86.53 | 0.00 | 0.00 | 0.00 | 68.07 | 0.00 | 0.00 | 0.00 |
February | 217.00 | 0.88 | 0.58 | 10-FEB-13:30 | 119.55 | 0.00 | 0.00 | 0.00 | 648.14 | 0.00 | 0.00 | 38.17 |
March | 215.50 | 0.85 | 0.50 | 16-MAR-12:20 | 168.15 | 0.00 | 0.00 | 10.00 | 144.27 | 0.00 | 0.00 | 4.33 |
April | 359.67 | 0.80 | 0.50 | 02-APR-11:20 | 203.85 | 0.00 | 0.00 | 67.50 | 161.96 | 0.00 | 0.00 | 28.83 |
May | 417.17 | 0.78 | 0.50 | 01-MAY-11:50 | 220.25 | 0.00 | 0.00 | 98.33 | 170.12 | 0.00 | 0.00 | 38.83 |
June | 410.67 | 0.76 | 0.50 | 02-JUN-10:39 | 244.26 | 0.00 | 0.00 | 115.83 | 187.94 | 0.00 | 0.00 | 64.50 |
July | 429.00 | 0.78 | 0.50 | 01-JUL-12:30 | 221.86 | 0.00 | 0.00 | 95.17 | 172.36 | 0.00 | 0.00 | 44.33 |
August | 396.33 | 0.81 | 0.50 | 01-AUG-10:30 | 198.70 | 0.00 | 0.00 | 56.33 | 157.81 | 0.00 | 0.00 | 16.00 |
September | 337.67 | 0.85 | 0.50 | 03-SEP-11:50 | 161.99 | 0.00 | 0.00 | 20.17 | 132.15 | 0.00 | 0.00 | 6.17 |
October | 234.00 | 0.88 | 0.67 | 01-OCT-10:00 | 140.35 | 0.00 | 0.00 | 0.00 | 113.33 | 0.00 | 0.00 | 0.00 |
November | 171.33 | 0.94 | 0.83 | 01-NOV-12:20 | 98.38 | 0.00 | 0.00 | 0.00 | 78.46 | 0.00 | 0.00 | 0.00 |
December | 131.67 | 0.97 | 0.83 | 02-DEC-11:09 | 78.50 | 0.00 | 0.00 | 0.00 | 62.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3515.67 | 0.83 | 180.13 | 0.00 | 0.00 | 463.33 | 176.58 | 0.00 | 0.00 | 241.17 | ||
Minimum of Months | 131.67 | 0.76 | 0.50 | 78.50 | 0.00 | 0.00 | 0.00 | 62.84 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 429.00 | 0.97 | 0.83 | 244.26 | 0.00 | 0.00 | 115.83 | 648.14 | 0.00 | 0.00 | 64.50 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.78 | 0.50 | 09-JAN-11:20 | 144.17 | 11.06 | 0.00 | 38.50 | 117.32 | 14.37 | 0.00 | 10.33 |
February | 217.00 | 0.69 | 0.50 | 01-FEB-12:09 | 198.96 | 12.78 | 0.00 | 104.50 | 161.90 | 16.37 | 11.83 | 63.00 |
March | 215.50 | 0.64 | 0.50 | 01-MAR-11:39 | 482.36 | 14.55 | 8.67 | 206.33 | 402.55 | 17.22 | 33.83 | 161.33 |
April | 359.67 | 0.61 | 0.50 | 01-APR-08:09 | 604.72 | 15.58 | 16.50 | 277.50 | 512.16 | 18.81 | 124.17 | 228.67 |
May | 417.17 | 0.60 | 0.50 | 01-MAY-07:19 | 358.68 | 15.05 | 0.00 | 324.33 | 717.24 | 19.53 | 126.50 | 272.00 |
June | 410.67 | 0.58 | 0.50 | 01-JUN-07:30 | 394.78 | 15.58 | 0.17 | 335.83 | 1250.07 | 21.04 | 130.67 | 283.67 |
July | 429.00 | 0.59 | 0.50 | 01-JUL-07:40 | 362.65 | 15.12 | 0.00 | 338.17 | 867.33 | 20.05 | 134.50 | 279.83 |
August | 396.33 | 0.61 | 0.50 | 01-AUG-07:49 | 326.09 | 14.65 | 0.00 | 294.50 | 267.04 | 18.53 | 111.17 | 244.17 |
September | 337.67 | 0.63 | 0.50 | 01-SEP-08:20 | 270.57 | 14.15 | 0.00 | 227.33 | 222.94 | 18.14 | 91.00 | 174.50 |
October | 234.00 | 0.64 | 0.50 | 01-OCT-09:09 | 792.10 | 13.69 | 0.00 | 150.17 | 409.22 | 18.81 | 47.50 | 111.50 |
November | 171.33 | 0.73 | 0.50 | 01-NOV-12:30 | 164.45 | 11.94 | 0.00 | 50.17 | 134.33 | 15.31 | 0.00 | 18.67 |
December | 131.67 | 0.80 | 0.58 | 02-DEC-10:00 | 132.24 | 11.11 | 0.00 | 6.67 | 109.25 | 14.44 | 0.00 | 0.00 |
Annual Sum or Average | 3515.67 | 0.64 | 373.10 | 14.26 | 25.33 | 2354.00 | 519.95 | 18.38 | 811.17 | 1847.67 | ||
Minimum of Months | 131.67 | 0.58 | 0.50 | 132.24 | 11.06 | 0.00 | 6.67 | 109.25 | 14.37 | 0.00 | 0.00 | |
Maximum of Months | 429.00 | 0.80 | 0.58 | 792.10 | 15.58 | 16.50 | 338.17 | 1250.07 | 21.04 | 134.50 | 283.67 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.88 | 0.64 | 15-JAN-15:30 | 228.83 | 22.83 | 92.17 | 21.17 | 102.82 | 20.11 | 80.17 | 0.00 |
February | 217.00 | 0.82 | 0.61 | 09-FEB-15:39 | 534.06 | 24.62 | 128.67 | 53.33 | 151.94 | 21.52 | 128.00 | 10.67 |
March | 215.50 | 0.81 | 0.61 | 02-MAR-16:40 | 333.20 | 23.64 | 166.67 | 52.67 | 228.58 | 24.05 | 187.00 | 19.83 |
April | 359.67 | 0.75 | 0.61 | 01-APR-14:09 | 422.43 | 23.07 | 250.33 | 152.50 | 378.56 | 24.20 | 292.33 | 91.17 |
May | 417.17 | 0.74 | 0.61 | 01-MAY-13:50 | 385.58 | 22.42 | 283.33 | 174.67 | 419.49 | 23.48 | 337.67 | 110.67 |
June | 410.67 | 0.73 | 0.61 | 01-JUN-14:09 | 417.57 | 22.73 | 282.33 | 207.67 | 532.39 | 23.75 | 327.67 | 110.00 |
July | 429.00 | 0.74 | 0.61 | 01-JUL-14:00 | 406.10 | 22.50 | 287.33 | 197.83 | 545.77 | 23.58 | 343.00 | 120.83 |
August | 396.33 | 0.75 | 0.61 | 01-AUG-14:09 | 410.70 | 22.67 | 262.00 | 161.17 | 410.73 | 23.57 | 309.67 | 112.83 |
September | 337.67 | 0.77 | 0.61 | 01-SEP-14:20 | 499.06 | 24.37 | 211.33 | 129.17 | 384.20 | 24.84 | 255.83 | 80.83 |
October | 234.00 | 0.80 | 0.61 | 01-OCT-14:30 | 361.85 | 24.23 | 147.00 | 62.67 | 194.73 | 23.35 | 162.50 | 24.67 |
November | 171.33 | 0.87 | 0.64 | 02-NOV-14:09 | 227.39 | 22.54 | 85.17 | 21.33 | 113.27 | 20.57 | 78.33 | 0.00 |
December | 131.67 | 0.91 | 0.68 | 18-DEC-14:30 | 162.26 | 19.35 | 41.83 | 0.50 | 86.93 | 19.35 | 38.00 | 0.00 |
Annual Sum or Average | 3515.67 | 0.78 | 388.90 | 22.99 | 2238.17 | 1234.67 | 351.34 | 23.16 | 2540.17 | 681.50 | ||
Minimum of Months | 131.67 | 0.73 | 0.61 | 162.26 | 19.35 | 41.83 | 0.50 | 86.93 | 19.35 | 38.00 | 0.00 | |
Maximum of Months | 429.00 | 0.91 | 0.68 | 534.06 | 24.62 | 287.33 | 207.67 | 545.77 | 24.84 | 343.00 | 120.83 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.461078E+10 | 25594.48 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.389267E+10 | 25594.48 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.396863E+10 | 25594.48 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138295E+10 | 25594.48 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.810163E+09 | 25594.48 | 02-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 87698451.44 | 25594.48 | 06-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20152448.04 | 25594.48 | 05-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 85313155.35 | 24465.59 | 07-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146636E+10 | 25594.48 | 02-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.325759E+10 | 25594.48 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.476036E+10 | 25594.48 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.243427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.476036E+10 | 25594.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.125348E+11 | 67532.13 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102043E+11 | 67532.13 | 24-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.693944E+10 | 62207.27 | 07-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.575060E+09 | 64642.48 | 05-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104341E+10 | 67071.17 | 25-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.737759E+10 | 67532.13 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156721E+11 | 67532.13 | 12-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.543467E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.156721E+11 | 67532.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.230140E+11 | 54791.09 | 10-JAN-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168948E+11 | 40964.04 | 17-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.385866E+10 | 22159.37 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.754746E+10 | 36370.34 | 29-NOV-03:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.370156E+11 | 54337.26 | 30-DEC-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.883305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.370156E+11 | 54791.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 5434521.19 | 5420596.10 | 744.07 | 29-APR-15:50 | 744.07 | 0.00 |
May | 0.00 | 0.00 | 31959780.32 | 29613510.84 | 3735.71 | 22-MAY-15:00 | 3437.39 | 0.00 |
June | 0.00 | 0.00 | 0.375960E+09 | 0.315199E+09 | 7275.53 | 13-JUN-16:00 | 6432.12 | 0.00 |
July | 0.00 | 0.00 | 0.771214E+09 | 0.684176E+09 | 15979.61 | 24-JUL-05:03 | 9406.49 | 0.00 |
August | 0.00 | 0.00 | 0.588674E+09 | 0.499897E+09 | 6702.59 | 14-AUG-16:00 | 6258.23 | 0.00 |
September | 0.00 | 0.00 | 0.210161E+09 | 0.188526E+09 | 4847.87 | 13-SEP-16:00 | 4231.95 | 0.00 |
October | 0.00 | 0.00 | 230.17 | 230.17 | 0.22 | 07-OCT-12:50 | 0.22 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.198340E+10 | 0.172283E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.771214E+09 | 0.684176E+09 | 15979.61 | 9406.49 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 6445557.98 | 5746522.25 | 1551.66 | 13-JUN-16:00 | 1390.10 | 0.00 |
July | 0.00 | 0.00 | 0.325954E+09 | 0.315378E+09 | 39869.75 | 23-JUL-15:55 | 30911.50 | 0.00 |
August | 0.00 | 0.00 | 73172.04 | 72660.00 | 62.40 | 14-AUG-16:00 | 62.40 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.332473E+09 | 0.321198E+09 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.325954E+09 | 0.315378E+09 | 39869.75 | 30911.50 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.235661E+09 | 0.04 | 159.99 | 01-JAN-00:03 | 0.08 |
February | 0.203095E+09 | 0.04 | 159.99 | 01-FEB-00:05 | 0.08 |
March | 88520692.54 | 0.02 | 159.99 | 01-MAR-00:05 | 0.08 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 83921072.24 | 0.02 | 159.99 | 04-NOV-03:00 | 0.08 |
December | 0.308607E+09 | 0.06 | 159.99 | 01-DEC-00:05 | 0.08 |
Annual Sum or Average | 0.919804E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.308607E+09 | 0.06 | 159.99 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.112024E+10 | 0.38 | 1095.59 | 03-JAN-15:00 | 0.92 |
February | 0.102951E+10 | 0.38 | 1095.59 | 03-FEB-14:30 | 0.92 |
March | 0.120377E+10 | 0.39 | 1095.59 | 01-MAR-10:50 | 0.91 |
April | 0.110400E+10 | 0.37 | 1095.59 | 01-APR-16:40 | 0.91 |
May | 0.114171E+10 | 0.37 | 1095.59 | 03-MAY-07:00 | 0.92 |
June | 0.113010E+10 | 0.37 | 1095.59 | 09-JUN-06:50 | 0.91 |
July | 0.108630E+10 | 0.34 | 1095.59 | 05-JUL-07:00 | 0.91 |
August | 0.117141E+10 | 0.36 | 1095.59 | 10-AUG-13:30 | 0.91 |
September | 0.108616E+10 | 0.35 | 1095.59 | 25-SEP-10:50 | 0.91 |
October | 0.110394E+10 | 0.36 | 1095.59 | 06-OCT-06:40 | 0.92 |
November | 0.106862E+10 | 0.36 | 1095.59 | 02-NOV-10:40 | 0.91 |
December | 0.112217E+10 | 0.38 | 1095.59 | 02-DEC-12:00 | 0.91 |
Annual Sum or Average | 0.133679E+11 | 0.37 | |||
Minimum of Months | 0.102951E+10 | 0.34 | 1095.59 | 0.91 | |
Maximum of Months | 0.120377E+10 | 0.39 | 1095.59 | 0.92 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.117682E+10 | 0.51 | 2100.37 | 02-JAN-06:01 | 0.89 |
February | 0.105807E+10 | 0.52 | 2100.37 | 24-FEB-06:01 | 0.89 |
March | 0.109757E+10 | 0.45 | 1934.76 | 07-MAR-06:01 | 0.89 |
April | 0.849120E+09 | 0.23 | 2010.50 | 05-APR-05:01 | 0.89 |
May | 0.865017E+09 | 0.21 | 840.15 | 01-MAY-06:05 | 0.54 |
June | 0.865017E+09 | 0.21 | 840.15 | 13-JUN-16:40 | 0.53 |
July | 0.833092E+09 | 0.20 | 840.15 | 22-JUL-12:10 | 0.53 |
August | 0.898287E+09 | 0.21 | 840.15 | 01-AUG-06:10 | 0.53 |
September | 0.831747E+09 | 0.20 | 840.15 | 01-SEP-06:10 | 0.53 |
October | 0.862692E+09 | 0.24 | 2086.03 | 25-OCT-05:01 | 0.88 |
November | 0.100974E+10 | 0.43 | 2100.37 | 28-NOV-06:01 | 0.89 |
December | 0.126444E+10 | 0.55 | 2100.37 | 12-DEC-06:01 | 0.89 |
Annual Sum or Average | 0.116116E+11 | 0.33 | |||
Minimum of Months | 0.831747E+09 | 0.20 | 840.15 | 0.53 | |
Maximum of Months | 0.126444E+10 | 0.55 | 2100.37 | 0.89 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.112024E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.102951E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.120377E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.110520E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.114848E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.120806E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.124803E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.129553E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.113085E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.110394E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.106862E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.112217E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.137844E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.102951E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.129553E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.117682E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.105807E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.109757E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.849120E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.865017E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.866711E+09 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.915364E+09 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.898306E+09 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.831747E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.862692E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.100974E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.126444E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.116956E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.831747E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.126444E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.112024E+10 | 0.00 | 0.461078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102951E+10 | 0.00 | 0.389267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120377E+10 | 0.00 | 0.396863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110400E+10 | 5434521.19 | 0.138295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114171E+10 | 31959780.32 | 0.810163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.113010E+10 | 0.375960E+09 | 87698451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.108630E+10 | 0.771214E+09 | 20152448.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117141E+10 | 0.588674E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108616E+10 | 0.210161E+09 | 85313155.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110394E+10 | 230.17 | 0.146636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.106862E+10 | 0.00 | 0.325759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112217E+10 | 0.00 | 0.476036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133679E+11 | 0.198340E+10 | 0.243427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.102951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.120377E+10 | 0.771214E+09 | 0.476036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.117682E+10 | 0.00 | 0.125348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105807E+10 | 0.00 | 0.102043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109757E+10 | 0.00 | 0.693944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.849120E+09 | 0.00 | 0.575060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.865017E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.865017E+09 | 6445557.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.833092E+09 | 0.313885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.898287E+09 | 73172.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.831747E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.862692E+09 | 0.00 | 0.104341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100974E+10 | 0.00 | 0.737759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126444E+10 | 0.00 | 0.156721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116116E+11 | 0.320404E+09 | 0.543467E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.831747E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.126444E+10 | 0.313885E+09 | 0.156721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.112024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110400E+10 | 0.00 | 0.00 | 0.00 | 1205511.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114171E+10 | 0.00 | 0.00 | 0.00 | 6776064.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.113010E+10 | 0.00 | 0.00 | 0.00 | 77968126.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.108630E+10 | 0.00 | 0.00 | 0.00 | 0.161724E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117141E+10 | 0.00 | 0.00 | 0.00 | 0.124120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108616E+10 | 0.00 | 0.00 | 0.00 | 44692899.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110394E+10 | 0.00 | 0.00 | 0.00 | 51.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.106862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133679E+11 | 0.00 | 0.00 | 0.00 | 0.416487E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.102951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.120377E+10 | 0.00 | 0.00 | 0.00 | 0.161724E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.117682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.849120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.865017E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.865017E+09 | 0.00 | 0.00 | 0.00 | 1694605.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.833092E+09 | 0.00 | 0.00 | 0.00 | 82271841.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.898287E+09 | 0.00 | 0.00 | 0.00 | 19377.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.831747E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.862692E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116116E+11 | 0.00 | 0.00 | 0.00 | 83985824.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.831747E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.126444E+10 | 0.00 | 0.00 | 0.00 | 82271841.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 24205108.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198806E+10 | 0.00 | 0.00 | 0.12 |
February | 12775086.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173523E+10 | 0.00 | 0.00 | 0.13 |
March | 37207657.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187714E+10 | 0.00 | 0.00 | 0.13 |
April | 0.769769E+09 | 0.00 | 0.00 | 172410.61 | 288462.03 | 0.555360E+09 | 0.256989E+09 | 0.00 | 0.16 |
May | 0.989947E+09 | 0.00 | 0.00 | 395580.37 | 0.00 | 0.234387E+09 | 0.498447E+09 | 0.00 | 0.18 |
June | 0.425539E+09 | 4073236.23 | 0.00 | 2037655.69 | 0.00 | 7627843.92 | 0.198184E+10 | 0.00 | 0.35 |
July | 92347760.17 | 6896742.82 | 0.00 | 3461379.19 | 0.00 | 0.00 | 0.294233E+10 | 0.00 | 0.48 |
August | 26754031.28 | 0.00 | 0.00 | 4154254.13 | 0.00 | 0.00 | 0.347989E+10 | 0.00 | 0.66 |
September | 0.336538E+09 | 0.00 | 0.00 | 1857154.34 | 0.00 | 0.00 | 0.197942E+10 | 0.00 | 0.38 |
October | 0.647981E+09 | 0.00 | 0.00 | 48244.86 | 0.00 | 0.662458E+09 | 0.120180E+09 | 0.00 | 0.13 |
November | 96480091.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152754E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196227E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.345954E+10 | 10969979.05 | 0.00 | 12126679.18 | 288462.03 | 0.105501E+11 | 0.112591E+11 | 0.00 | 0.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.989947E+09 | 6896742.82 | 0.00 | 4154254.13 | 288462.03 | 0.198806E+10 | 0.347989E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.334464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196035E+10 | 0.00 | 0.00 | 0.17 |
February | 0.357978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.850939E+09 | 0.00 | 0.00 | 0.18 |
March | 0.430669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425621E+09 | 0.00 | 0.00 | 0.19 |
April | 0.391853E+10 | 0.00 | 0.00 | 0.00 | 4462520.07 | 0.00 | 0.00 | 0.00 | 0.18 |
May | 0.423588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
June | 0.421098E+10 | 0.00 | 0.00 | 3366.52 | 3750.39 | 0.00 | 15572908.61 | 0.00 | 0.19 |
July | 0.380231E+10 | 0.00 | 0.00 | 549930.20 | 853270.83 | 0.00 | 0.230208E+09 | 0.00 | 0.18 |
August | 0.394738E+10 | 0.00 | 0.00 | 193.50 | 0.00 | 0.00 | 7393745.69 | 0.00 | 0.19 |
September | 0.345961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
October | 0.345518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18399584.28 | 0.00 | 0.00 | 0.17 |
November | 0.327091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663116E+09 | 0.00 | 0.00 | 0.17 |
December | 0.259993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240244E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.441318E+11 | 0.00 | 0.00 | 553490.22 | 5319541.29 | 0.632087E+10 | 0.253174E+09 | 0.00 | 0.18 |
Minimum of Months | 0.259993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.430669E+10 | 0.00 | 0.00 | 549930.20 | 4462520.07 | 0.240244E+10 | 0.230208E+09 | 0.00 | 0.19 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:49
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.152129E+12 | 0.140011E+11 | 0.00 | 0.731725E+10 | 0.138448E+11 |
February | 0.260018E+12 | 0.181137E+11 | 0.00 | 0.617873E+10 | 0.109217E+11 |
March | 0.334710E+12 | 0.130209E+11 | 0.00 | 0.664666E+10 | 0.624567E+10 |
April | 0.949217E+12 | 0.178338E+11 | 0.00 | 0.549607E+10 | 0.940661E+09 |
May | 0.113777E+13 | 0.439985E+11 | 0.00 | 0.595906E+10 | 0.421656E+09 |
June | 0.116026E+13 | 0.412977E+11 | 0.00 | 0.663952E+10 | 0.503415E+09 |
July | 0.119070E+13 | 0.417636E+11 | 0.00 | 0.706690E+10 | 0.135054E+10 |
August | 0.985888E+12 | 0.353695E+11 | 0.00 | 0.746558E+10 | 0.712886E+09 |
September | 0.715197E+12 | 0.290943E+11 | 0.00 | 0.577743E+10 | 0.297762E+09 |
October | 0.316391E+12 | 0.206925E+11 | 0.00 | 0.490425E+10 | 0.121053E+10 |
November | 0.971998E+11 | 0.195422E+11 | 0.00 | 0.555805E+10 | 0.695439E+10 |
December | 0.121876E+11 | 0.290017E+11 | 0.00 | 0.696465E+10 | 0.188343E+11 |
Annual Sum or Average | 0.731166E+13 | 0.323729E+12 | 0.00 | 0.759741E+11 | 0.622383E+11 |
Minimum of Months | 0.121876E+11 | 0.130209E+11 | 0.00 | 0.490425E+10 | 0.297762E+09 |
Maximum of Months | 0.119070E+13 | 0.439985E+11 | 0.00 | 0.746558E+10 | 0.188343E+11 |