Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2023-10-16 10:41:44
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3089.94 | 639.06 | 639.06 |
Net Site Energy | 3089.94 | 639.06 | 639.06 |
Total Source Energy | 5469.96 | 1131.29 | 1131.29 |
Net Source Energy | 5469.96 | 1131.29 | 1131.29 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2071.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 18.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 74.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 28.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1017.99 | 2071.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 2071.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 18.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 73.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 28.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 2071.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 18.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 74.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 28.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 25.09 | 428.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 210.54 | 428.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 25.09 | 428.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 210.54 | 428.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1017.986 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1017.986 | 100.00 |
Total On-Site and Utility Electric Sources | 1017.986 | 100.00 |
Total Electricity End Uses | 1017.986 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 94.83 |
Time Setpoint Not Met During Occupied Cooling | 1.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3023.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.61 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7186 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 15.0695 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 9.6875 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 11.2890 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 11.2890 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.7186 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 15.0695 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 9.6875 | 46.45 | 2.5587 | |
Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 11.2890 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 30-JUN-14:00 | 04-JAN-06:19 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 483150.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 19624.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6935.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1819.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 84686.23 | 483150.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 483150.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 19624.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 4630.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1819.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2245.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 59.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1974.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 423.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 235.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 89.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3223.96 | 2245.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 464.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 12.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 48.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 666.78 | 464.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 464.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 12.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 48.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 666.78 | 464.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.12 |
ZONE2 FINE STORAGE DIRECT AIR | 3.06 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 6.64 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 6.64 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 260360.66 |
PSZ-OFFICE HEATING COIL | 31022.11 |
PSZ-FINE STORAGE HEATING COIL | 110575.50 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 260360.67 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.12 | 1.12 | 1.12 | 1.12 | 1.12 | 1.12 | 1.00 | 1.00 | 1.12 |
PSZ-FINE STORAGE | 3.06 | 3.06 | 3.06 | 3.06 | 3.06 | 3.06 | 1.00 | 1.00 | 3.06 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.12 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 3.06 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.12 | 1278.78 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.06 | 3351.65 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.12 | 1.12 | 1.12 | 1.12 | 20252.67 | 31022.11 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 3.06 | 3.06 | 3.06 | 3.06 | 69601.68 | 110575.50 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.12 | 0.560813 | 1.12 | 20252.67 | 10413.03 | 20252.67 | 0.800050 | 0.800050 |
PSZ-FINE STORAGE COOLING COIL | 3.06 | 1.53 | 3.06 | 69601.68 | 34589.34 | 69601.68 | 0.729760 | 0.729760 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.719 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.792 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 15.069 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15.069 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 9.688 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 12.246 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2539.013 | 10.719 | 199.158 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2539.013 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 20997.932 | 15.069 | 699.931 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20997.932 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 31046.942 | 9.688 | 449.956 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 31046.942 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5959 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.4133 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.7823 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.7823 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.678 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.320 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.179 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.179 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53319041E-11 | 0.92099297E-16 | 0.18475806E-15 | 0.0000000 |
5 | 1 | -5.2159728 | 0.43155192E-04 | -0.26885250E-04 | 0.68722794E-11 |
6 | 0 | 5.8118483 | 0.59583229 | 0.59590233 | |
7 | 4 | 0.79569988E-12 | 0.97024197E-16 | -0.20560970E-14 | 0.11376788E-15 |
8 | 3 | -0.38947258E-03 | 0.29188957E-06 | -0.56541964E-04 | 0.15267338E-12 |
9 | 2 | 1.7507793 | 0.63492849E-02 | 1.1490006 | -0.74668540E-04 |
10 | 1 | -7.1139048 | 0.16396836 | -17.152679 | 0.33556055 |
11 | 0 | 5.6381505 | 0.10431759 | 16.278371 | |
12 | 4 | 0.72249793E-12 | -0.16720573E-15 | 0.22015083E-14 | 0.12409536E-15 |
13 | 3 | -0.36459118E-03 | 0.53555631E-06 | -0.52695411E-04 | 0.13865996E-12 |
14 | 2 | 1.6915239 | 0.11971291E-01 | 1.1039557 | -0.69896550E-04 |
15 | 1 | -7.1930661 | 0.31446443 | -16.864389 | 0.32415671 |
16 | 0 | 6.0306730 | 0.20232993 | 16.289252 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.22015083E-14 | -0.16720573E-15 | 0.72249793E-12 | 0.12409536E-15 |
85 | 3 | -0.52695411E-04 | 0.53555631E-06 | -0.36459118E-03 | 0.13865996E-12 |
86 | 2 | 1.1039557 | 0.11971291E-01 | 1.6915239 | -0.69896550E-04 |
87 | 1 | -16.864389 | 0.31446443 | -7.1930661 | 0.32415671 |
88 | 0 | 16.289252 | 0.20232993 | 6.0306730 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.4258_SHGC_SOUTH_0.45 | 34 | 1 | VerySmooth | 2.420 | 2.420 | 1.000 | 0.451 | ||
2 | NONRESWINDOW_U_0.4258_SHGC_NORTH_0.45 | 35 | 1 | VerySmooth | 2.420 | 2.420 | 1.000 | 0.451 | ||
3 | NONRESWINDOW_U_0.4258_SHGC_EAST_0.45 | 36 | 1 | VerySmooth | 2.420 | 2.420 | 1.000 | 0.451 | ||
4 | NONRESWINDOW_U_0.4258_SHGC_WEST_0.45 | 37 | 1 | VerySmooth | 2.420 | 2.420 | 1.000 | 0.451 | ||
5 | SKYLIGHT_U_1.02_SHGC_0.68 | 38 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.682 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.96080E-002 | 0.36619 | 0.42689 | 0.42689 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.12246 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.96080E-002 | 0.36619 | 0.42689 | 0.42689 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.12246 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.96080E-002 | 0.36619 | 0.42689 | 0.42689 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.12246 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.96080E-002 | 0.36619 | 0.42689 | 0.42689 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.12246 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.57291 | 6.11155E-002 | 6.11155E-002 | 0.68000 | 0.13462 | 0.14960 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.849 | 0.366 | 0.255 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 0.153 | 6.473E-004 | 9.992E-004 | 0.546 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.780 | 5.598E-004 | 3.565E-004 | 0.951 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 3.433 | 1.071E-003 | 6.996E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10885.55306 | 13062.66367 | 0.93469 | 1.12163 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 28.69467 | 1.27234E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 14472.57759 | 17367.09311 | 0.42417 | 0.50900 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -32.70000 | 1.83376E-004 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 38121.58211 | 45745.89853 | 2.55187 | 3.06225 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.10000 | 1.27259E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 63707.30992 | 76448.77191 | 1.57165 | 1.88598 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -32.70000 | 1.83376E-004 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 30.10000 | 1.27259E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 216967.22148 | 260360.66578 | 5.53152 | 6.63783 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 16053.70 | 1.12163 | 1.12163 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 17559.87 | 0.50900 | 0.50900 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 53857.62 | 3.06225 | 3.06225 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 77228.61 | 1.88598 | 1.88598 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.12163 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.06225 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.63783 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 6.63783 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 260360.66159 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 260360.66578 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.12163 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.12163 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.12163 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.12163 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.12163 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.12163 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.06225 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.06225 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.06225 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.06225 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.06225 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.06225 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.12163 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.06225 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.12163 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.12163 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1278.77618 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.12163 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.12163 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.12163 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.12163 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.12163 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.56081 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.12163 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20252.67000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 10413.02624 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20252.67000 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80005 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80005 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20252.67000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31022.11310 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 31022.11310 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.06225 |
47 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.06225 |
49 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3351.64934 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.06225 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.06225 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.06225 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.06225 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.06225 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.53112 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.06225 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 69601.68000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 34589.33784 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 69601.68000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72976 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72976 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 69601.68000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 110575.50273 |
64 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
66 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 110575.50273 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 19382.1 | 10.85 | 10.22 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 67222.5 | 10.62 | 10.01 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.7714187956 | 0.7557136172 | Pass | Pass | 0.6730534490 | 0.6331704830 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 1.5636332512 | 1.4398011294 | Pass | Pass | 0.6210095710 | 0.6107995503 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 1.7025324267E-004 | 3.5049176230E-004 | Pass | Pass | 1.7973894119E-002 | 1.5400116926E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7791.10 | 1224.13 | 0.00 | 136.91 | 571.76 | 9723.92 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.389 | 0.413 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.389 | 0.413 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.389 | 0.413 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.389 | 0.413 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.389 | 0.413 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.389 | 0.413 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.389 | 0.413 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.551 | 0.596 | 3204.84 | 3170.23 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.659 | 0.782 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.659 | 0.782 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.4258_SHGC_WEST_0.45 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.420 | 0.451 | 0.452 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.4258_SHGC_WEST_0.45 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.420 | 0.451 | 0.452 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.4258_SHGC_NORTH_0.45 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.420 | 0.451 | 0.452 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.4258_SHGC_NORTH_0.45 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.420 | 0.451 | 0.452 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.27 | 4.657 | 0.517 | 0.518 | |||||||||||||||||
North Total or Average | 6.51 | 2.420 | 0.451 | 0.452 | |||||||||||||||||
Non-North Total or Average | 45.76 | 4.975 | 0.526 | 0.527 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.7186 | 236.88 | 2539.01 | LightsWired | LTG_SCH_OFFICE | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.86 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 15.0695 | 1393.41 | 20997.93 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 239.15 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 9.6875 | 3204.84 | 31046.94 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 353.60 |
Interior Lighting Total | 11.2890 | 4835.13 | 54583.89 | 623.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 8532.22 | AstronomicalClock | - | 83.52 | 83.52 | 133.76 | |
Exterior Lighting Total | 8532.22 | 133.76 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20252.67 | 16203.15 | 4049.52 | 0.80 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 69601.68 | 50792.52 | 18809.16 | 0.73 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 19382.1 | 10.85 | 10.22 | ||||
PSZ-FINE STORAGE COOLING COIL | 67222.5 | 10.62 | 10.01 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 260360.66 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 31022.11 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 110575.50 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 6.64 | 616.72 | 92.91 | 1.00 | 3.07 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.12 | 1278.78 | 1140.11 | 1.00 | 1.34 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 3.06 | 3351.65 | 1094.51 | 1.00 | 1.23 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10885.55 | 13062.66 | 55.14 | 0.935 | 1.122 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 23.90 | 23.90 | 0.00862 | 28.69 | 0.01272 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 38121.58 | 45745.90 | 32.83 | 2.552 | 3.062 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 26.70 | 26.70 | 0.00912 | 30.10 | 0.01273 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 0.00 | 31.05 | 0.01279 | 30.10 | 0.01273 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 14472.58 | 17367.09 | 73.32 | 0.424 | 0.509 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00745 | -32.70 | 0.00018 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 63707.31 | 76448.77 | 54.86 | 1.572 | 1.886 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.55 | 0.00646 | -32.70 | 0.00018 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 216967.22 | 260360.67 | 81.24 | 5.532 | 6.638 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00616 | -32.70 | 0.00018 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.12 | 1.12 | 0.51 | 0.51 | 1.1216 | 1.1216 | 1.1216 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.06 | 3.06 | 1.89 | 1.89 | 3.0622 | 3.0622 | 3.0622 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 260360.662 | 260360.662 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 260360.66 | 260360.66 | 6.637827 | 10.00 | 8.03 | 0.00615749 | 43.33 | 21.64 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 10.00 | 0.00615749 | 77.5249 | 260360.67 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 20252.670 | 16203.149 | 1.121630 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 20252.67 | 17408.04 | 1.121630 | 25.33 | 16.83 | 0.00899885 | 12.00 | 10.89 | 0.00800000 | 29.03 | 0.01272398 | 20.82 | 9.1193 | 23.90 | 0.00862431 | 44.7542 | 10865.87 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 31022.113 | 31022.113 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 31022.11 | 31022.11 | 1.121625 | 16.15 | 11.39 | 0.00678884 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 9.1193 | 21.10 | 0.00745166 | 45.9279 | 14472.58 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 69601.680 | 50792.522 | 3.062250 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 69601.68 | 56796.76 | 3.062250 | 28.10 | 18.24 | 0.00962403 | 12.00 | 10.89 | 0.00800000 | 30.10 | 0.01272586 | 21.13 | 13.8693 | 26.70 | 0.00912455 | 40.0584 | 38121.58 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 110575.503 | 110575.503 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 110575.50 | 110575.50 | 3.062250 | 8.86 | 6.84 | 0.00559258 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 13.8693 | 15.55 | 0.00646360 | 56.5137 | 63707.31 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 260360.662 | 260360.662 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 6.637827 | 7.65955322 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 260360.66 | 260360.66 | 1.0000 | 7.65955322 | 6.637827 | 10.00 | 8.03 | 0.00615749 | 25557.8 | 43.33 | 21.64 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 260360.66 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 10.00 | 0.00615749 | 10.00 | 0.00615749 | 77.5249 | 260360.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20252.670 | 16203.149 | 1.121630 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5684 | 1004.8586 | 1.1539 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.121625 | 1.29427140 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | Sensible | 20252.67 | 17408.04 | 1.0000 | 1.29427674 | 1.121630 | 25.33 | 16.83 | 0.00899885 | 48385.2 | 12.00 | 10.89 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20252.67 | 29.03 | 0.01272398 | 20.82 | 0.10228463 | 9.1193 | 23.90 | 0.00862431 | 23.90 | 0.00862431 | 44.7542 | 10865.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31022.113 | 31022.113 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.121625 | 1.29427140 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 31022.11 | 31022.11 | 1.0000 | 1.29427140 | 1.121625 | 16.15 | 11.39 | 0.00678884 | 33407.5 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31022.11 | -32.70 | 0.00018338 | -32.70 | 0.10228463 | 9.1193 | 21.05 | 0.00745166 | 21.10 | 0.00745166 | 45.9279 | 14472.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 69601.680 | 50792.522 | 3.062250 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.7306 | 1004.8586 | 1.1539 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.062250 | 3.53360628 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 69601.68 | 56796.76 | 1.0000 | 3.53360639 | 3.062250 | 28.10 | 18.24 | 0.00962403 | 52803.0 | 12.00 | 10.89 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 69601.68 | 30.10 | 0.01272586 | 21.13 | 0.42471127 | 13.8693 | 26.70 | 0.00912455 | 26.70 | 0.00912455 | 40.0584 | 38121.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 110575.503 | 110575.503 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.062250 | 3.53360628 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 110575.50 | 110575.50 | 1.0000 | 3.53360628 | 3.062250 | 8.86 | 6.84 | 0.00559258 | 22980.5 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 110575.50 | -32.70 | 0.00018338 | -32.70 | 0.42471127 | 13.8693 | 15.55 | 0.00646360 | 15.55 | 0.00646360 | 56.5137 | 63707.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 3.06 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2660.17 | 2761.00 | 2050.17 |
ZONE2 FINE STORAGE | 3160.50 | 3103.50 | 2699.00 |
ZONE3 BULK STORAGE | 3226.50 | 3312.17 | 2960.50 |
Facility | 3445.17 | 3388.33 | 3023.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 384.67 | 50.83 | 78.83 | 1.50 |
ZONE2 FINE STORAGE | 655.33 | 6.67 | 33.83 | 0.00 |
ZONE3 BULK STORAGE | 1.67 | 0.00 | 1.67 | 0.00 |
Facility | 922.67 | 54.67 | 94.83 | 1.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.346 | 0.411 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.507 | 0.442 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.193 | 0.000 | 0.121 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.50 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.36 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.28 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1350041.15 | 0.00 | 1350041.15 | 2708210.07 | 4058251.22 | 3225648.14 | 5378.09 | 3381.91 | 0.00 | 1567.22 |
ZONE2 FINE STORAGE | 5381686.22 | 0.00 | 5381686.22 | 11891119.26 | 17272805.48 | 13393694.68 | 5725.58 | 2776.29 | 258.13 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 25306262.89 | 25306262.89 | 48769577.56 | 74075840.45 | 30805497.77 | 8200.05 | 55.50 | 504.45 | 4777.57 |
Total Facility | 6731727.36 | 25306262.89 | 32037990.25 | 63368906.89 | 95406897.14 | 47424840.58 | 8446.43 | 3410.00 | 756.91 | 4850.58 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.0958 | 0.0000 | 0.0958 | 0.1139 | 0.2097 | 0.1023 | 271.93 | 3364.07 | 0.00 |
ZONE2 FINE STORAGE | 0.4111 | 0.0000 | 0.4111 | 0.3606 | 0.7717 | 0.4247 | 601.58 | 2776.29 | 258.13 |
ZONE3 BULK STORAGE | 0.0000 | 1.1545 | 1.1545 | 1.9040 | 3.0585 | 0.9768 | 3306.93 | 27.67 | 301.40 |
Total Facility | 0.5070 | 1.1545 | 1.6615 | 2.3785 | 4.0400 | 1.5038 | 3322.43 | 3364.58 | 553.86 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 1797637.26 | 0.00 | 1797637.26 | 3225648.14 | 5354.91 | 1.88 | 3403.22 | 1538.93 |
PSZ-FINE STORAGE | 7165944.32 | 0.00 | 7165944.32 | 13393694.68 | 5724.25 | 0.25 | 3035.50 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1276 | 0.0000 | 0.1276 | 0.1023 | 266.10 | 0.36 | 3369.55 |
PSZ-FINE STORAGE | 0.5475 | 0.0000 | 0.5475 | 0.4247 | 600.25 | 0.25 | 3035.50 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 5027.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2776.04 | 261.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1330 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.5655 | 1.6116 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 383 |
Defaulted Fields | 319 |
Fields with Defaults | 1020 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1017.99 | 6718.26 | 12-MAR-12:00 | 84686.23 | 30-JUN-15:00 |
Electricity:Building | 763.51 | 6235.26 | 01-JAN-00:10 | 58611.10 | 27-JUN-12:10 |
Electricity:Zone:ZONE1 OFFICE | 62.81 | 1030.77 | 01-JAN-00:10 | 3867.54 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 762.90 | 6235.26 | 01-JAN-00:10 | 56305.80 | 02-JAN-09:10 |
InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 461.56 | 3104.69 | 01-JAN-00:10 | 36895.31 | 27-JUN-12:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 74.23 | 0.00 | 12-MAR-12:00 | 6935.72 | 29-JUN-16:50 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.62 | 0.00 | 01-JAN-00:10 | 2305.29 | 29-JUN-16:50 |
Ventilation (simple):Fans:Electricity | 0.62 | 0.00 | 01-JAN-00:10 | 2305.29 | 29-JUN-16:50 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.62 | 0.00 | 01-JAN-00:10 | 2305.29 | 29-JUN-16:50 |
ElectricityPurchased:Facility | 1017.99 | 6718.26 | 12-MAR-12:00 | 84686.23 | 30-JUN-15:00 |
ElectricityPurchased:Plant | 1017.99 | 6718.26 | 12-MAR-12:00 | 84686.23 | 30-JUN-15:00 |
Cogeneration:ElectricityPurchased | 1017.99 | 6718.26 | 12-MAR-12:00 | 84686.23 | 30-JUN-15:00 |
General:Cogeneration:ElectricityPurchased | 1017.99 | 6718.26 | 12-MAR-12:00 | 84686.23 | 30-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1017.99 | 6718.26 | 12-MAR-12:00 | 84686.23 | 30-JUN-15:00 |
ElectricityNet:Plant | 1017.99 | 6718.26 | 12-MAR-12:00 | 84686.23 | 30-JUN-15:00 |
Cogeneration:ElectricityNet | 1017.99 | 6718.26 | 12-MAR-12:00 | 84686.23 | 30-JUN-15:00 |
General:Cogeneration:ElectricityNet | 1017.99 | 6718.26 | 12-MAR-12:00 | 84686.23 | 30-JUN-15:00 |
Electricity:HVAC | 92.43 | 0.00 | 12-MAR-12:00 | 26925.02 | 29-JUN-16:00 |
General:Fans:Electricity | 73.61 | 0.00 | 12-MAR-12:00 | 5247.15 | 02-JAN-14:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 18.81 | 0.00 | 01-JAN-00:10 | 22294.59 | 29-JUN-16:00 |
General:Cooling:Electricity | 18.81 | 0.00 | 01-JAN-00:10 | 22294.59 | 29-JUN-16:00 |
ExteriorLights:Electricity | 133.76 | 0.00 | 01-JAN-08:20 | 8532.22 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 133.76 | 0.00 | 01-JAN-08:20 | 8532.22 | 01-JAN-00:10 |
Electricity:Plant | 28.28 | 483.00 | 01-JAN-01:30 | 3152.42 | 24-FEB-13:00 |
WaterSystems:Electricity | 28.28 | 483.00 | 01-JAN-01:30 | 3152.42 | 24-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 28.28 | 483.00 | 01-JAN-01:30 | 3152.42 | 24-FEB-13:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 2071.95 | 0.00 | 12-MAR-12:00 | 483150.45 | 04-JAN-06:20 |
NaturalGas:HVAC | 2071.95 | 0.00 | 12-MAR-12:00 | 483150.45 | 04-JAN-06:20 |
Heating:NaturalGas | 2071.95 | 0.00 | 12-MAR-12:00 | 483150.45 | 04-JAN-06:20 |
General:Heating:NaturalGas | 2071.95 | 0.00 | 12-MAR-12:00 | 483150.45 | 04-JAN-06:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3269.89 | 0.00 | 12-MAR-12:00 | 757287.25 | 04-JAN-06:20 |
EnergyTransfer:Building | 1614.90 | 0.00 | 12-MAR-12:00 | 377416.44 | 04-JAN-06:20 |
EnergyTransfer:Zone:ZONE1 OFFICE | 91.74 | 0.00 | 01-JAN-00:40 | 27816.21 | 12-JAN-07:10 |
Heating:EnergyTransfer | 1553.18 | 0.00 | 12-MAR-12:00 | 377416.44 | 04-JAN-06:20 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 71.29 | 0.00 | 01-JAN-00:40 | 27816.21 | 12-JAN-07:10 |
General:Heating:EnergyTransfer | 1553.18 | 0.00 | 12-MAR-12:00 | 377416.44 | 04-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 71.29 | 0.00 | 01-JAN-00:40 | 27816.21 | 12-JAN-07:10 |
Cooling:EnergyTransfer | 61.72 | 0.00 | 01-JAN-00:10 | 43916.14 | 30-JUN-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 20.45 | 0.00 | 01-JAN-00:10 | 10121.36 | 29-JUN-16:10 |
General:Cooling:EnergyTransfer | 61.72 | 0.00 | 01-JAN-00:10 | 43916.14 | 30-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 20.45 | 0.00 | 01-JAN-00:10 | 10121.36 | 29-JUN-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 342.90 | 0.00 | 01-JAN-00:40 | 103308.61 | 12-FEB-22:50 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 301.63 | 0.00 | 01-JAN-00:40 | 103308.61 | 12-FEB-22:50 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 301.63 | 0.00 | 01-JAN-00:40 | 103308.61 | 12-FEB-22:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 41.27 | 0.00 | 01-JAN-00:10 | 34363.57 | 30-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 41.27 | 0.00 | 01-JAN-00:10 | 34363.57 | 30-JUN-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 1180.27 | 0.00 | 17-JAN-12:50 | 262552.00 | 04-JAN-12:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 1180.27 | 0.00 | 17-JAN-12:50 | 262552.00 | 04-JAN-12:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 1180.27 | 0.00 | 17-JAN-12:50 | 262552.00 | 04-JAN-12:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1654.99 | 0.00 | 12-MAR-12:00 | 379870.81 | 04-JAN-06:20 |
HeatingCoils:EnergyTransfer | 1587.00 | 0.00 | 12-MAR-12:00 | 379870.81 | 04-JAN-06:20 |
CoolingCoils:EnergyTransfer | 67.99 | 0.00 | 01-JAN-00:10 | 73567.05 | 29-JUN-16:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 71.287 | -20.448 | 0.000 | 0.000 | 10.107 | 30.864 | 31.946 | 11.330 | 0.000 | 0.465 | 0.001 | 0.000 | -13.575 | 0.000 | -55.699 | -66.278 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 301.628 | -41.267 | 0.000 | 0.000 | 25.941 | 239.148 | 0.000 | 0.000 | 0.000 | 0.683 | 0.002 | 0.000 | 0.000 | 0.000 | -221.989 | -304.144 |
ZONE3 BULK STORAGE | 1180.265 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 67.224 | 353.598 | 107.344 | 88.653 | 0.000 | 5.049 | 0.000 | 0.000 | -216.798 | 0.000 | -924.239 | -661.095 |
Total Facility | 1180.265 | 0.000 | 372.915 | -61.715 | 0.000 | 0.000 | 103.272 | 623.610 | 139.290 | 99.983 | 0.000 | 6.197 | 0.002 | 0.000 | -230.373 | 0.000 | -1201.927 | -1031.517 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 05-AUG-18:23 | 0.00 | 0.00 | 0.00 | -18435.47 | 0.00 | 0.00 | 0.00 | 457.02 | 573.75 | 2200.65 | 0.00 | 0.00 | 15342.56 | 0.00 | -0.00 | 0.00 | -138.52 | 0.00 |
ZONE2 FINE STORAGE | 24-JUL-17:06 | 0.00 | 0.00 | 0.00 | -55795.04 | 0.00 | 0.00 | 0.00 | 2099.79 | 0.00 | 0.00 | 0.00 | 853.58 | 52841.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JUL-17:06 | 0.00 | 0.00 | 0.00 | -71999.58 | 0.00 | 0.00 | 0.00 | 5661.51 | 2623.78 | 25190.51 | 0.00 | 1278.97 | 65058.25 | 0.00 | 0.00 | 0.00 | -27813.43 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 18-APR-05:01 | 0.00 | 0.00 | 30631.57 | 0.00 | 0.00 | 0.00 | 143.48 | 583.97 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -187.38 | 0.00 | -782.23 | -30963.16 |
ZONE2 FINE STORAGE | 04-JAN-06:41 | 0.00 | 0.00 | 119632.56 | 0.00 | 0.00 | 0.00 | 403.29 | 2099.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -29101.86 | -93033.78 |
ZONE3 BULK STORAGE | 04-JAN-12:00 | 262551.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8450.84 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6406.34 | 0.00 | -266756.56 | -32429.52 |
Total Facility | 12-FEB-22:52 | 261102.01 | 0.00 | 140528.76 | 0.00 | 0.00 | 0.00 | 0.00 | 5661.51 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -17486.40 | 0.00 | -285325.69 | -105053.94 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1216 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.1216 | 0.0912 | 1.0000 | Not calculated | 0.1023 | 0.0912 | ||
PSZ-FINE STORAGE | 3.0622 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.0622 | 0.1387 | 1.0000 | Not calculated | 0.4247 | 0.1387 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1216 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.1216 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0912 | ||
PSZ-FINE STORAGE | 3.0622 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.0622 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1387 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1216 | 1.1216 | 1.1216 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.0622 | 3.0622 | 3.0622 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1216 | 1.1216 | 1.1216 | 1.1216 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.0622 | 3.0622 | 3.0622 | 3.0622 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1216 | 1.1216 | 1.1216 | No | 0.1023 | 0.2010 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.0622 | 3.0622 | 3.0622 | No | 0.4247 | 0.2252 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1216 | 1.1216 | 1.1216 | 1.1216 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.0622 | 3.0622 | 3.0622 | 3.0622 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 94.83 |
Number of hours cooling loads not met | 1.50 |
Number of hours not met | 96.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 2071.95 | 483150.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 18.81 | 22294.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 623.61 | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 133.76 | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.62 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 73.61 | 5247.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 28.28 | 3152.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 1017.99 |
Natural Gas | 0.00 | 2071.95 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 3089.94 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 128.97 |
Space Heating | 0.00 |
Space Cooling | 3.89 |
Fans (All) | 15.35 |
Service Water Heating | 5.85 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 210.54 |
Subtotal | 210.54 |
Natural Gas [MJ/m2] | |
Space Heating | 428.52 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 428.52 |
Subtotal | 428.52 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 20.18 |
Space Heating | 67.05 |
Space Cooling | 0.61 |
Fans (All) | 2.40 |
Service Water Heating | 0.92 |
Receptacle Equipment | 4.51 |
Miscellaneous | 4.33 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 3430. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8673.00 | 87.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8116.67 | 643.33 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8014.83 | 724.00 | 21.17 | 0.00 | 0.00 |
Min | 8014.83 | 87.00 | 0.00 | 0.00 | 0.00 |
Max | 8673.00 | 724.00 | 21.17 | 0.00 | 0.00 |
Average | 8268.17 | 484.78 | 7.06 | 0.00 | 0.00 |
Sum | 24804.50 | 1454.33 | 21.17 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 70874.50 | 11844.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 165709.17 | 24385.83 | 1098.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 165709.17 | 24385.83 | 1098.00 | 0.00 | 0.00 |
Average | 89870.22 | 12076.78 | 366.00 | 0.00 | 0.00 |
Sum | 269610.67 | 36230.33 | 1098.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8586.83 | 173.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7660.33 | 1099.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7586.83 | 1159.67 | 13.50 | 0.00 | 0.00 |
Min | 7586.83 | 173.17 | 0.00 | 0.00 | 0.00 |
Max | 8586.83 | 1159.67 | 13.50 | 0.00 | 0.00 |
Average | 7944.67 | 810.83 | 4.50 | 0.00 | 0.00 |
Sum | 23834.00 | 2432.50 | 13.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 33022.67 | 4.33 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 68209.00 | 14510.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 158162.17 | 32300.83 | 730.00 | 0.00 | 0.00 |
Min | 33022.67 | 4.33 | 0.00 | 0.00 | 0.00 |
Max | 158162.17 | 32300.83 | 730.00 | 0.00 | 0.00 |
Average | 86464.61 | 15605.06 | 243.33 | 0.00 | 0.00 |
Sum | 259393.83 | 46815.17 | 730.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 | -22.1 | 0.496299E+09 | 603.25 | 13-JAN-08:09 | -31.5 | -31.6 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -23.1 | -23.5 | 0.457034E+09 | 603.25 | 28-FEB-16:40 | 5.77 | 1.22 |
March | 924605.92 | 318.85 | 31-MAR-15:00 | 8.30 | 2.63 | 0.536741E+09 | 610.75 | 31-MAR-15:09 | 8.40 | 2.82 |
April | 22664410.65 | 824.12 | 22-APR-15:00 | 18.30 | 7.82 | 0.512684E+09 | 768.96 | 13-APR-15:00 | 18.30 | 7.82 |
May | 0.178167E+10 | 15857.08 | 25-MAY-18:23 | 28.30 | 18.90 | 0.619737E+09 | 775.14 | 02-MAY-15:30 | 28.30 | 18.90 |
June | 0.429250E+10 | 17178.92 | 21-JUN-18:23 | 23.60 | 17.05 | 0.654347E+09 | 769.08 | 30-JUN-15:00 | 31.70 | 24.66 |
July | 0.647827E+10 | 18374.86 | 07-JUL-17:43 | 21.20 | 13.08 | 0.634506E+09 | 769.06 | 29-JUL-15:50 | 30.50 | 21.35 |
August | 0.572250E+10 | 18435.73 | 05-AUG-18:23 | 21.40 | 13.96 | 0.683867E+09 | 769.06 | 11-AUG-15:00 | 26.70 | 19.53 |
September | 0.195935E+10 | 16672.98 | 01-SEP-17:43 | 23.98 | 17.84 | 0.608935E+09 | 769.05 | 01-SEP-15:09 | 23.98 | 17.84 |
October | 0.189916E+09 | 2581.30 | 21-OCT-15:00 | 20.00 | 11.16 | 0.526532E+09 | 768.98 | 19-OCT-15:09 | 20.00 | 11.16 |
November | 626775.70 | 389.72 | 16-NOV-15:50 | 6.20 | 1.27 | 0.478918E+09 | 724.68 | 01-NOV-15:20 | 6.20 | 1.27 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -8.8 | -9.9 | 0.496672E+09 | 603.25 | 02-DEC-08:09 | -26.6 | -26.8 |
Annual Sum or Average | 0.204484E+11 | 0.670627E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.5 | 0.457034E+09 | 603.25 | -31.5 | -31.6 | ||
Maximum of Months | 0.647827E+10 | 18435.73 | 28.30 | 18.90 | 0.683867E+09 | 775.14 | 31.70 | 24.66 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 98819348.18 | 4667.95 | 17-JAN-13:10 | -3.6 | -4.9 | 0.648696E+09 | 787.42 | 14-JAN-13:09 | -3.6 | -4.9 |
February | 0.479679E+09 | 7661.58 | 11-FEB-14:10 | -6.1 | -8.0 | 0.604795E+09 | 996.04 | 08-FEB-14:30 | -6.1 | -8.0 |
March | 0.145233E+10 | 7429.96 | 17-MAR-12:10 | -6.3 | -8.2 | 0.728996E+09 | 1185.78 | 31-MAR-15:09 | 8.40 | 2.82 |
April | 0.142898E+10 | 5555.79 | 05-APR-12:10 | -2.0 | -5.6 | 0.861122E+09 | 1774.73 | 13-APR-15:09 | 20.00 | 8.11 |
May | 0.291019E+10 | 17281.18 | 25-MAY-15:00 | 28.90 | 19.67 | 0.149643E+10 | 2246.93 | 18-MAY-12:50 | 28.90 | 19.67 |
June | 0.744831E+10 | 51966.07 | 30-JUN-17:06 | 30.92 | 21.22 | 0.181085E+10 | 2246.95 | 20-JUN-14:39 | 30.92 | 21.22 |
July | 0.131220E+11 | 55798.63 | 24-JUL-17:06 | 28.80 | 19.14 | 0.183560E+10 | 2246.97 | 26-JUL-13:39 | 22.60 | 14.77 |
August | 0.881001E+10 | 41724.01 | 25-AUG-17:10 | 27.52 | 19.45 | 0.194058E+10 | 2246.97 | 05-AUG-14:50 | 27.52 | 19.45 |
September | 0.252222E+10 | 32083.48 | 01-SEP-17:10 | 24.32 | 17.92 | 0.146179E+10 | 2246.85 | 07-SEP-15:09 | 23.72 | 14.98 |
October | 0.184369E+10 | 6472.48 | 25-OCT-08:70 | -2.3 | -2.3 | 0.912027E+09 | 1870.28 | 21-OCT-14:50 | -2.3 | -2.3 |
November | 0.106278E+10 | 5539.64 | 04-NOV-12:30 | -2.0 | -3.7 | 0.674643E+09 | 1386.10 | 01-NOV-15:09 | -2.0 | -3.7 |
December | 89227656.60 | 4109.95 | 05-DEC-13:30 | -0.6 | -0.6 | 0.648786E+09 | 787.42 | 09-DEC-11:00 | -14.4 | -15.2 |
Annual Sum or Average | 0.412682E+11 | 0.136243E+11 | ||||||||
Minimum of Months | 89227656.60 | 4109.95 | -6.3 | -8.2 | 0.604795E+09 | 787.42 | -14.4 | -15.2 | ||
Maximum of Months | 0.131220E+11 | 55798.63 | 30.92 | 21.22 | 0.194058E+10 | 2246.97 | 30.92 | 21.22 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 | -22.1 | 0.642957E+09 | 824.69 | 27-JAN-14:20 | -14.4 | -15.6 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -23.1 | -23.5 | 0.601982E+09 | 1023.96 | 08-FEB-14:39 | 5.00 | -0.5 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -1.3 | -3.3 | 0.745974E+09 | 1353.63 | 23-MAR-14:20 | 0.20 | -4.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.38 | 0.102794E+10 | 2372.34 | 18-APR-14:09 | 17.33 | 10.22 |
May | 0.00 | 0.00 | 01-MAY-00:03 | -0.0 | -1.4 | 0.257455E+10 | 5453.32 | 25-MAY-15:30 | 29.00 | 19.65 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 | 0.391401E+10 | 8312.43 | 29-JUN-15:00 | 35.00 | 24.72 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 | 13.57 | 0.472822E+10 | 6945.80 | 15-JUL-14:00 | 31.10 | 24.50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 | 0.441513E+10 | 6651.20 | 08-AUG-15:30 | 30.60 | 23.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 | 0.265059E+10 | 6262.44 | 01-SEP-14:39 | 25.93 | 17.92 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 | 0.114736E+10 | 2441.47 | 02-OCT-13:39 | 10.37 | 9.55 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.51 | 0.684295E+09 | 1669.55 | 01-NOV-14:39 | 18.13 | 13.38 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -8.8 | -9.9 | 0.643579E+09 | 780.62 | 02-DEC-16:10 | -18.7 | -19.4 |
Annual Sum or Average | 0.00 | 0.237766E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.5 | 0.601982E+09 | 780.62 | -18.7 | -19.4 | ||
Maximum of Months | 0.00 | 0.00 | 19.75 | 18.15 | 0.472822E+10 | 8312.43 | 35.00 | 24.72 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.166104E+11 | 29954.79 | 10-JAN-06:31 | -20.4 |
February | 0.127702E+11 | 29875.61 | 21-FEB-06:01 | 2.80 |
March | 0.106908E+11 | 29805.30 | 15-MAR-05:31 | -22.2 |
April | 0.524888E+10 | 30631.47 | 18-APR-05:01 | 11.78 |
May | 0.797695E+09 | 29932.92 | 15-MAY-05:01 | 6.87 |
June | 41957509.63 | 10194.12 | 01-JUN-05:03 | 14.08 |
July | 7801627.54 | 1031.09 | 29-JUL-06:05 | 19.87 |
August | 14754470.03 | 822.53 | 12-AUG-06:05 | 16.78 |
September | 0.305258E+09 | 29707.33 | 30-SEP-05:01 | 10.00 |
October | 0.249916E+10 | 30561.22 | 31-OCT-05:01 | 10.00 |
November | 0.735752E+10 | 30537.14 | 01-NOV-05:01 | 10.60 |
December | 0.149432E+11 | 30512.86 | 18-DEC-06:31 | -17.2 |
Annual Sum or Average | 0.712877E+11 | |||
Minimum of Months | 7801627.54 | 822.53 | -22.2 | |
Maximum of Months | 0.166104E+11 | 30631.47 | 19.87 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.775334E+11 | 119632.39 | 04-JAN-06:41 | -29.3 |
February | 0.554816E+11 | 119140.31 | 13-FEB-06:41 | -24.3 |
March | 0.390594E+11 | 118219.98 | 15-MAR-05:01 | -22.2 |
April | 0.158363E+11 | 113302.41 | 04-APR-17:42 | -5.4 |
May | 0.928377E+09 | 89695.91 | 01-MAY-04:12 | -3.0 |
June | 0.266664E+09 | 3512.45 | 09-JUN-07:00 | 11.70 |
July | 0.165247E+09 | 3029.17 | 08-JUL-07:00 | 13.30 |
August | 0.242389E+09 | 3471.00 | 07-AUG-07:00 | 13.90 |
September | 0.283708E+09 | 3459.15 | 23-SEP-07:00 | 3.90 |
October | 0.756201E+10 | 111498.56 | 31-OCT-21:02 | -1.9 |
November | 0.326027E+11 | 113327.74 | 23-NOV-12:42 | -9.4 |
December | 0.716667E+11 | 118423.29 | 20-DEC-06:01 | -28.9 |
Annual Sum or Average | 0.301629E+12 | |||
Minimum of Months | 0.165247E+09 | 3029.17 | -29.3 | |
Maximum of Months | 0.775334E+11 | 119632.39 | 13.90 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.325991E+12 | 262552.00 | 04-JAN-12:00 | -28.3 |
February | 0.232414E+12 | 261300.11 | 12-FEB-22:55 | -17.2 |
March | 0.148727E+12 | 191676.82 | 15-MAR-05:00 | -22.2 |
April | 0.376706E+11 | 109493.10 | 04-APR-18:53 | -7.2 |
May | 0.424605E+09 | 27083.08 | 01-MAY-04:00 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.101205E+11 | 59242.74 | 31-OCT-20:54 | -2.2 |
November | 0.119634E+12 | 159188.82 | 25-NOV-01:52 | -15.6 |
December | 0.305284E+12 | 261615.94 | 18-DEC-15:00 | -22.8 |
Annual Sum or Average | 0.118027E+13 | |||
Minimum of Months | 0.00 | 0.00 | -28.3 | |
Maximum of Months | 0.325991E+12 | 262552.00 | 19.75 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.258145E+10 | 1955.04 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.235440E+10 | 1955.04 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.269003E+10 | 1955.04 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.254196E+10 | 1955.04 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.263574E+10 | 1955.04 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.259625E+10 | 1955.04 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.258145E+10 | 1955.04 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.269003E+10 | 1955.04 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.254196E+10 | 1955.04 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.258145E+10 | 1955.04 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.248766E+10 | 1955.04 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.258145E+10 | 1955.04 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.308638E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.235440E+10 | 1955.04 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.269003E+10 | 1955.04 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.198922E+11 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.182065E+11 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.210336E+11 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.197108E+11 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.204629E+11 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.202815E+11 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.198922E+11 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.210336E+11 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.197108E+11 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.198922E+11 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.191400E+11 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.198922E+11 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.239148E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.182065E+11 | 17848.24 | 0.00 | 0.00 | |
Maximum of Months | 0.210336E+11 | 17848.24 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.294120E+11 | 26389.90 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.269196E+11 | 26389.90 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.310997E+11 | 26389.90 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.291438E+11 | 26389.90 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.302559E+11 | 26389.90 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.299876E+11 | 26389.90 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.294120E+11 | 26389.90 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.310997E+11 | 26389.90 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.291438E+11 | 26389.90 | 01-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.294120E+11 | 26389.90 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.282999E+11 | 26389.90 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.294120E+11 | 26389.90 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.353598E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.269196E+11 | 26389.90 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.310997E+11 | 26389.90 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.993247E+10 |
February | 0.127628E+10 | 0.235440E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.810643E+10 |
March | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641982E+10 |
April | 0.138726E+10 | 0.254196E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14892209.98 | 0.437530E+10 |
May | 0.144276E+10 | 0.263574E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56350705.42 | 0.206016E+10 |
June | 0.144276E+10 | 0.259625E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162162E+09 | 0.118743E+10 |
July | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153614E+09 | 0.877211E+09 |
August | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75056152.43 | 0.136391E+10 |
September | 0.138726E+10 | 0.254196E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2934199.30 | 0.241401E+10 |
October | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346762E+10 |
November | 0.133177E+10 | 0.248766E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.589087E+10 |
December | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.960419E+10 |
Annual Sum or Average | 0.168137E+11 | 0.308638E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465010E+09 | 0.556994E+11 |
Minimum of Months | 0.127628E+10 | 0.235440E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.877211E+09 |
Maximum of Months | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162162E+09 | 0.993247E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389045E+11 |
February | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324413E+11 |
March | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230315E+11 |
April | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98617371.88 | 0.168696E+11 |
May | 0.339505E+10 | 0.204629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43324391.01 | 0.826605E+10 |
June | 0.339505E+10 | 0.202815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275817E+09 | 0.601089E+10 |
July | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210246E+09 | 0.499995E+10 |
August | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54966623.72 | 0.691352E+10 |
September | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.981300E+10 |
October | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118196E+11 |
November | 0.313390E+10 | 0.191400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234572E+11 |
December | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394620E+11 |
Annual Sum or Average | 0.395654E+11 | 0.239148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682972E+09 | 0.221989E+12 |
Minimum of Months | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499995E+10 |
Maximum of Months | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275817E+09 | 0.394620E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129653E+12 |
February | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104627E+12 |
March | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703275E+11 |
April | 0.750829E+10 | 0.291438E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111117E+10 | 0.416411E+11 |
May | 0.780862E+10 | 0.302559E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135864E+10 | 0.227807E+11 |
June | 0.780862E+10 | 0.299876E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59203081.80 | 0.199165E+11 |
July | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4209835.39 | 0.236600E+11 |
August | 0.810895E+10 | 0.310997E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7839880.24 | 0.272755E+11 |
September | 0.750829E+10 | 0.291438E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59528711.48 | 0.312110E+11 |
October | 0.750829E+10 | 0.294120E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483484E+09 | 0.281693E+11 |
November | 0.720796E+10 | 0.282999E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249539E+09 | 0.637220E+11 |
December | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126557E+12 |
Annual Sum or Average | 0.910005E+11 | 0.353598E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333362E+10 | 0.689541E+12 |
Minimum of Months | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199165E+11 |
Maximum of Months | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135864E+10 | 0.129653E+12 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1955.04 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 20546.84 | 04-JAN-17:10 |
February | 1680.92 | 01-FEB-08:09 | 1955.04 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 18702.15 | 13-FEB-07:05 |
March | 1680.92 | 01-MAR-08:09 | 1955.04 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 16218.24 | 15-MAR-06:10 |
April | 1680.92 | 01-APR-07:10 | 1955.04 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 877.19 | 23-APR-16:00 | 11928.91 | 04-APR-17:00 |
May | 1680.92 | 01-MAY-07:10 | 1955.04 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1356.42 | 25-MAY-16:10 | 5830.20 | 09-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 1955.04 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3806.18 | 29-JUN-16:10 | 3716.33 | 02-JUN-07:00 |
July | 1680.92 | 01-JUL-07:10 | 1955.04 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1771.81 | 28-JUL-16:10 | 3257.46 | 27-JUL-06:05 |
August | 1680.92 | 01-AUG-07:10 | 1955.04 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2442.13 | 08-AUG-16:10 | 5367.82 | 17-AUG-16:05 |
September | 1680.92 | 01-SEP-07:10 | 1955.04 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 535.36 | 01-SEP-16:10 | 6215.26 | 20-SEP-06:10 |
October | 1680.92 | 02-OCT-07:10 | 1955.04 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 9742.69 | 30-OCT-07:00 |
November | 1680.92 | 01-NOV-07:10 | 1955.04 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 12645.95 | 29-NOV-08:00 |
December | 1680.92 | 01-DEC-08:09 | 1955.04 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 21218.18 | 18-DEC-17:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3257.46 | |||||
Maximum of Months | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 3806.18 | 21218.18 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 48167.78 | 04-JAN-16:10 |
February | 3955.50 | 01-FEB-08:09 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 58757.18 | 12-FEB-22:57 |
March | 3955.50 | 01-MAR-08:09 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 35876.76 | 14-MAR-15:10 |
April | 3955.50 | 01-APR-07:10 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5416.25 | 23-APR-16:00 | 29317.23 | 26-APR-15:10 |
May | 3955.50 | 01-MAY-07:10 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.82 | 10-MAY-18:00 | 14192.07 | 20-MAY-06:20 |
June | 3955.50 | 01-JUN-07:10 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8041.78 | 29-JUN-16:00 | 14013.01 | 09-JUN-08:00 |
July | 3955.50 | 01-JUL-07:10 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5498.45 | 15-JUL-15:10 | 10712.07 | 08-JUL-15:05 |
August | 3955.50 | 01-AUG-07:10 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4149.86 | 08-AUG-16:00 | 18845.39 | 17-AUG-15:05 |
September | 3955.50 | 01-SEP-07:10 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 14231.79 | 20-SEP-06:20 |
October | 3955.50 | 02-OCT-07:10 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 19284.55 | 31-OCT-17:00 |
November | 3955.50 | 01-NOV-07:10 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 28588.10 | 22-NOV-01:50 |
December | 3955.50 | 01-DEC-08:09 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 59151.19 | 18-DEC-16:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10712.07 | ||||
Maximum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8041.78 | 59151.19 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 26389.90 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 209225.75 | 04-JAN-12:00 |
February | 9097.65 | 01-FEB-08:09 | 26389.90 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 161003.33 | 12-FEB-22:52 |
March | 9097.65 | 01-MAR-08:09 | 26389.90 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 97636.55 | 14-MAR-16:00 |
April | 9097.65 | 01-APR-07:10 | 26389.90 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32036.74 | 23-APR-16:00 | 67892.50 | 26-APR-15:00 |
May | 9097.65 | 01-MAY-07:10 | 26389.90 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17117.01 | 10-MAY-15:00 | 39056.35 | 20-MAY-07:10 |
June | 9097.65 | 01-JUN-07:10 | 26389.90 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2989.26 | 29-JUN-16:00 | 49477.93 | 09-JUN-09:00 |
July | 9097.65 | 01-JUL-07:10 | 26389.90 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2718.69 | 15-JUL-13:55 | 58627.20 | 03-JUL-10:55 |
August | 9097.65 | 01-AUG-07:10 | 26389.90 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 898.34 | 08-AUG-15:00 | 66040.87 | 17-AUG-14:00 |
September | 9097.65 | 01-SEP-07:10 | 26389.90 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5171.48 | 24-SEP-15:00 | 36950.47 | 20-SEP-07:10 |
October | 9097.65 | 02-OCT-07:10 | 26389.90 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16648.92 | 19-OCT-15:00 | 43266.43 | 31-OCT-11:00 |
November | 9097.65 | 01-NOV-07:10 | 26389.90 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8951.25 | 01-NOV-13:00 | 82188.52 | 25-NOV-11:00 |
December | 9097.65 | 01-DEC-08:09 | 26389.90 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 188410.21 | 18-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36950.47 | |||||
Maximum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 32036.74 | 209225.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 4570.22 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2828.96 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 3656.18 | 4590.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4477.98 |
March | 318.85 | 31-MAR-15:00 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 993.98 |
April | 824.12 | 22-APR-15:00 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.60 |
May | 15857.08 | 25-MAY-18:23 | 0.00 | 1371.07 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 144.16 | 0.00 |
June | 17178.92 | 21-JUN-18:23 | 0.00 | 1371.07 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.49 |
July | 18374.86 | 07-JUL-17:43 | 0.00 | 1371.07 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.04 |
August | 18435.73 | 05-AUG-18:23 | 0.00 | 1371.07 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.52 |
September | 16672.98 | 01-SEP-17:43 | 0.00 | 1371.07 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.48 |
October | 2581.30 | 21-OCT-15:00 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.88 |
November | 389.72 | 16-NOV-15:50 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1212.62 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 2742.13 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2589.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 1371.07 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18435.73 | 1680.92 | 4570.22 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 144.16 | 4477.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4667.95 | 17-JAN-13:10 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.81 |
February | 7661.58 | 11-FEB-14:10 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7429.96 | 17-MAR-12:10 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2369.00 |
April | 5555.79 | 05-APR-12:10 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5019.87 |
May | 17281.18 | 25-MAY-15:00 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 400.17 | 0.00 |
June | 51966.07 | 30-JUN-17:06 | 0.00 | 10498.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2732.57 | 0.00 |
July | 55798.63 | 24-JUL-17:06 | 0.00 | 10498.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 853.58 | 0.00 |
August | 41724.01 | 25-AUG-17:10 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.14 | 0.00 |
September | 32083.48 | 01-SEP-17:10 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 976.98 |
October | 6472.48 | 25-OCT-08:70 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5539.64 | 04-NOV-12:30 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3057.40 |
December | 4109.95 | 05-DEC-13:30 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2174.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4109.95 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 55798.63 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2732.57 | 5019.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 31046.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48241.48 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 24837.55 | 16400.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76881.53 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 15523.47 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20375.98 |
April | 0.00 | 01-APR-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14251.02 |
May | 0.00 | 01-MAY-00:03 | 0.00 | 9314.08 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3302.10 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10968.11 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7519.14 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11096.48 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7080.26 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7698.72 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14240.56 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 18628.16 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39850.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3302.10 | |
Maximum of Months | 0.00 | 0.00 | 31046.94 | 16400.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76881.53 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.890127E+11 | 66562.38 | 10-JAN-08:09 | 0.560958E+12 | 483150.45 | 04-JAN-06:19 |
February | 0.796810E+11 | 64275.62 | 25-FEB-15:50 | 0.400977E+12 | 473976.00 | 12-FEB-22:00 |
March | 0.890201E+11 | 64274.30 | 02-MAR-13:00 | 0.266525E+12 | 373792.19 | 15-MAR-05:10 |
April | 0.807752E+11 | 64202.94 | 01-APR-14:50 | 0.787195E+11 | 198603.74 | 04-APR-18:30 |
May | 0.824074E+11 | 73304.43 | 25-MAY-14:00 | 0.237855E+10 | 71753.27 | 01-MAY-05:10 |
June | 0.841921E+11 | 84686.23 | 30-JUN-14:00 | 25206741.63 | 4969.46 | 01-JUN-05:10 |
July | 0.862666E+11 | 82571.84 | 15-JUL-14:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.886729E+11 | 80206.87 | 08-AUG-14:00 | 273651.31 | 240.13 | 18-AUG-06:49 |
September | 0.811810E+11 | 74106.83 | 01-SEP-14:39 | 0.481197E+09 | 10861.04 | 28-SEP-05:10 |
October | 0.836683E+11 | 63672.23 | 21-OCT-14:00 | 0.274274E+11 | 129278.65 | 30-OCT-05:00 |
November | 0.838545E+11 | 66511.60 | 30-NOV-16:00 | 0.211953E+12 | 284313.00 | 25-NOV-06:19 |
December | 0.892548E+11 | 66559.36 | 30-DEC-08:09 | 0.522507E+12 | 483088.04 | 18-DEC-17:10 |
Annual Sum or Average | 0.101799E+13 | 0.207195E+13 | ||||
Minimum of Months | 0.796810E+11 | 63672.23 | 0.00 | 0.00 | ||
Maximum of Months | 0.892548E+11 | 84686.23 | 0.560958E+12 | 483150.45 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.518856E+11 | 0.146771E+11 | 0.115358E+11 | 0.00 | 0.844312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247102E+10 | 0.00 |
February | 0.474804E+11 | 0.120560E+11 | 0.105871E+11 | 0.00 | 0.728851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226893E+10 | 0.00 |
March | 0.548234E+11 | 0.117182E+11 | 0.123431E+11 | 0.00 | 0.756941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256607E+10 | 0.00 |
April | 0.513965E+11 | 0.970113E+10 | 0.114862E+11 | 0.00 | 0.577886E+10 | 0.00 | 0.00 | 6257729.16 | 0.00 | 0.00 | 0.00 | 0.240627E+10 | 0.00 |
May | 0.533545E+11 | 0.854928E+10 | 0.119357E+11 | 0.00 | 0.483231E+10 | 0.00 | 0.00 | 0.130679E+10 | 0.00 | 0.00 | 0.00 | 0.242878E+10 | 0.00 |
June | 0.528654E+11 | 0.747422E+10 | 0.118862E+11 | 0.00 | 0.512662E+10 | 0.00 | 0.00 | 0.452634E+10 | 0.00 | 0.00 | 0.00 | 0.231336E+10 | 0.00 |
July | 0.518856E+11 | 0.809878E+10 | 0.115358E+11 | 0.00 | 0.512012E+10 | 0.00 | 0.00 | 0.734838E+10 | 0.00 | 0.00 | 0.00 | 0.227794E+10 | 0.00 |
August | 0.548234E+11 | 0.936326E+10 | 0.123357E+11 | 0.00 | 0.510352E+10 | 0.00 | 0.00 | 0.473094E+10 | 0.00 | 0.00 | 0.00 | 0.231608E+10 | 0.00 |
September | 0.513965E+11 | 0.106226E+11 | 0.114788E+11 | 0.00 | 0.460227E+10 | 0.00 | 0.00 | 0.864449E+09 | 0.00 | 0.00 | 0.00 | 0.221633E+10 | 0.00 |
October | 0.518856E+11 | 0.126755E+11 | 0.115432E+11 | 0.00 | 0.522350E+10 | 0.00 | 0.00 | 30708603.94 | 0.00 | 0.00 | 0.00 | 0.230980E+10 | 0.00 |
November | 0.499276E+11 | 0.137556E+11 | 0.110862E+11 | 0.00 | 0.680150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228347E+10 | 0.00 |
December | 0.518856E+11 | 0.150713E+11 | 0.115358E+11 | 0.00 | 0.833965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242242E+10 | 0.00 |
Annual Sum or Average | 0.623610E+12 | 0.133763E+12 | 0.139290E+12 | 0.00 | 0.742294E+11 | 0.00 | 0.00 | 0.188139E+11 | 0.00 | 0.00 | 0.00 | 0.282805E+11 | 0.00 |
Minimum of Months | 0.474804E+11 | 0.747422E+10 | 0.105871E+11 | 0.00 | 0.460227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221633E+10 | 0.00 |
Maximum of Months | 0.548234E+11 | 0.150713E+11 | 0.123431E+11 | 0.00 | 0.844312E+10 | 0.00 | 0.00 | 0.734838E+10 | 0.00 | 0.00 | 0.00 | 0.256607E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.560958E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.400977E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.266525E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.787195E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.237855E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 25206741.63 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 273651.31 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.481197E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.274274E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.211953E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.522507E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.207195E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.560958E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 46193.18 | 02-JAN-09:09 | 8532.22 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 5247.15 | 02-JAN-14:50 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 46193.18 | 01-FEB-09:09 | 8532.22 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 5247.15 | 01-FEB-07:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 46193.18 | 01-MAR-09:09 | 8532.22 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 5247.15 | 01-MAR-10:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 46193.18 | 01-APR-08:09 | 8532.22 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 5247.15 | 04-APR-14:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 46193.18 | 01-MAY-08:09 | 8532.22 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 4630.43 | 16-MAY-14:39 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 46193.18 | 01-JUN-08:09 | 8532.22 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 6935.72 | 29-JUN-16:49 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 46193.18 | 01-JUL-08:09 | 8532.22 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 6935.72 | 03-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 46193.18 | 01-AUG-08:09 | 8532.22 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 6935.72 | 08-AUG-13:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 46193.18 | 01-SEP-08:09 | 8532.22 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 5398.86 | 01-SEP-14:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 46193.18 | 02-OCT-08:09 | 8532.22 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 5247.15 | 10-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 46193.18 | 01-NOV-08:09 | 8532.22 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 5247.15 | 13-NOV-12:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 46193.18 | 01-DEC-09:09 | 8532.22 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 5247.15 | 01-DEC-15:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 46193.18 | 8532.22 | 10112.62 | 0.00 | 4630.43 | 0.00 | 0.00 | |||||
Maximum of Months | 46193.18 | 8532.22 | 10112.62 | 0.00 | 6935.72 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 3110.66 | 28-JAN-12:30 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 3152.42 | 24-FEB-12:00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 3151.40 | 01-MAR-12:09 | 0.00 |
April | 447.49 | 13-APR-14:00 | 0.00 | 0.00 | 0.00 | 3088.17 | 01-APR-11:09 | 0.00 |
May | 10520.82 | 25-MAY-14:00 | 0.00 | 0.00 | 0.00 | 2939.18 | 01-MAY-11:30 | 0.00 |
June | 22294.59 | 29-JUN-15:00 | 0.00 | 0.00 | 0.00 | 2703.15 | 02-JUN-11:00 | 0.00 |
July | 17519.81 | 15-JUL-14:30 | 0.00 | 0.00 | 0.00 | 2475.69 | 01-JUL-11:30 | 0.00 |
August | 16192.05 | 08-AUG-15:50 | 0.00 | 0.00 | 0.00 | 2289.20 | 02-AUG-11:09 | 0.00 |
September | 10745.80 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 | 2337.86 | 29-SEP-11:39 | 0.00 |
October | 918.13 | 21-OCT-14:00 | 0.00 | 0.00 | 0.00 | 2552.19 | 31-OCT-11:50 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2777.01 | 29-NOV-12:50 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2979.39 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2289.20 | 0.00 | ||
Maximum of Months | 22294.59 | 0.00 | 0.00 | 0.00 | 3152.42 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 66562.38 | 10-JAN-08:09 | 40988.70 | 10112.62 | 8532.22 | 0.00 | 5247.15 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 64275.62 | 25-FEB-15:50 | 46193.18 | 10112.62 | 0.00 | 0.00 | 5247.15 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 64274.30 | 02-MAR-13:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 5247.15 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 64202.94 | 01-APR-14:50 | 46193.18 | 10112.62 | 0.00 | 0.00 | 5247.15 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 73304.43 | 25-MAY-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 4630.43 | 0.00 | 0.00 | 10520.82 | 0.00 |
June | 84686.23 | 30-JUN-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 6935.72 | 0.00 | 0.00 | 19624.88 | 0.00 |
July | 82571.84 | 15-JUL-14:30 | 46193.18 | 10112.62 | 0.00 | 0.00 | 6935.72 | 0.00 | 0.00 | 17519.81 | 0.00 |
August | 80206.87 | 08-AUG-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 6935.72 | 0.00 | 0.00 | 15164.79 | 0.00 |
September | 74106.83 | 01-SEP-14:39 | 46193.18 | 10112.62 | 0.00 | 0.00 | 5398.86 | 0.00 | 0.00 | 10603.17 | 0.00 |
October | 63672.23 | 21-OCT-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 4630.43 | 0.00 | 0.00 | 918.13 | 0.00 |
November | 66511.60 | 30-NOV-16:00 | 40988.70 | 10112.62 | 8532.22 | 0.00 | 5247.15 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 66559.36 | 30-DEC-08:09 | 40988.70 | 10112.62 | 8532.22 | 0.00 | 5247.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 63672.23 | 40988.70 | 10112.62 | 0.00 | 0.00 | 4630.43 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 84686.23 | 46193.18 | 10112.62 | 8532.22 | 0.00 | 6935.72 | 0.00 | 0.00 | 19624.88 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 483150.45 | 04-JAN-06:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 473976.00 | 12-FEB-22:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 373792.19 | 15-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 198603.74 | 04-APR-18:30 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 71753.27 | 01-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 4969.46 | 01-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 240.13 | 18-AUG-06:49 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 10861.04 | 28-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 129278.65 | 30-OCT-05:00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 284313.00 | 25-NOV-06:19 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 483088.04 | 18-DEC-17:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 483150.45 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 102.00 | 15.17 | 16.17 | 15.64 | 0.00 | 15.64 | 0.00 | 15.64 |
February | 75.17 | 15.24 | 11.33 | 15.71 | 0.00 | 15.71 | 0.00 | 15.71 |
March | 46.17 | 15.73 | 10.33 | 16.31 | 0.00 | 16.31 | 0.00 | 16.31 |
April | 19.67 | 16.93 | 9.17 | 17.65 | 0.00 | 17.65 | 0.00 | 17.65 |
May | 3.00 | 19.82 | 2.83 | 19.96 | 2.83 | 21.46 | 0.17 | 21.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 24.62 | 0.00 | 24.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 24.62 | 0.67 | 24.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 24.57 | 0.67 | 24.57 |
September | 0.67 | 20.47 | 0.67 | 20.47 | 1.83 | 22.83 | 0.00 | 22.83 |
October | 6.67 | 19.44 | 6.00 | 19.67 | 0.00 | 19.67 | 0.00 | 19.67 |
November | 38.17 | 15.88 | 8.83 | 16.52 | 0.00 | 16.52 | 0.00 | 16.52 |
December | 93.17 | 15.15 | 13.50 | 15.60 | 0.00 | 15.60 | 0.00 | 15.60 |
Annual Sum or Average | 384.67 | 15.52 | 78.83 | 16.12 | 50.83 | 16.96 | 1.50 | 16.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.60 | 0.00 | 15.60 |
Maximum of Months | 102.00 | 20.47 | 16.17 | 20.47 | 20.50 | 24.62 | 0.67 | 24.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 121.33 | 13.19 | 5.83 | 13.20 | 0.00 | 13.20 | 0.00 | 13.20 |
February | 105.67 | 13.48 | 4.83 | 13.48 | 0.00 | 13.48 | 0.00 | 13.48 |
March | 102.83 | 14.00 | 5.83 | 13.99 | 0.00 | 13.99 | 0.00 | 13.99 |
April | 62.00 | 14.42 | 4.33 | 14.42 | 0.00 | 14.42 | 0.00 | 14.42 |
May | 2.17 | 14.77 | 0.33 | 14.78 | 0.00 | 14.78 | 0.00 | 14.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.50 | 0.00 | 27.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.46 | 0.00 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.28 | 0.00 | 27.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38.50 | 14.76 | 2.50 | 14.76 | 0.00 | 14.76 | 0.00 | 14.76 |
November | 103.50 | 14.14 | 4.67 | 14.14 | 0.00 | 14.14 | 0.00 | 14.14 |
December | 119.33 | 13.24 | 5.50 | 13.25 | 0.00 | 13.25 | 0.00 | 13.25 |
Annual Sum or Average | 655.33 | 13.74 | 33.83 | 13.74 | 6.67 | 13.88 | 0.00 | 13.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.33 | 14.77 | 5.83 | 14.78 | 4.67 | 27.50 | 0.00 | 27.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 9.23 | 1.67 | 9.23 | 0.00 | 9.23 | 0.00 | 9.23 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.67 | 9.23 | 1.67 | 9.23 | 0.00 | 9.23 | 0.00 | 9.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 9.23 | 1.67 | 9.23 | 0.00 | 9.23 | 0.00 | 9.23 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.96 | 300.00 | 20.96 | 300.00 | 20.96 |
February | 276.00 | 21.00 | 276.00 | 21.00 | 276.00 | 21.00 |
March | 324.00 | 21.02 | 324.00 | 21.02 | 324.00 | 21.02 |
April | 300.00 | 21.33 | 262.83 | 21.21 | 262.83 | 21.17 |
May | 249.67 | 22.70 | 94.00 | 22.46 | 70.83 | 22.24 |
June | 140.50 | 23.34 | 116.00 | 23.58 | 8.17 | 23.58 |
July | 19.83 | 23.75 | 240.00 | 23.89 | 4.83 | 23.89 |
August | 40.50 | 23.36 | 223.00 | 23.82 | 0.00 | 23.82 |
September | 222.50 | 22.90 | 38.67 | 22.86 | 17.83 | 22.74 |
October | 300.00 | 21.60 | 206.17 | 21.39 | 206.17 | 21.30 |
November | 288.00 | 21.07 | 279.50 | 21.06 | 279.50 | 21.05 |
December | 300.00 | 20.99 | 300.00 | 20.99 | 300.00 | 20.99 |
Annual Sum or Average | 2761.00 | 21.59 | 2660.17 | 21.64 | 2050.17 | 21.48 |
Minimum of Months | 19.83 | 20.96 | 38.67 | 20.96 | 0.00 | 20.96 |
Maximum of Months | 324.00 | 23.75 | 324.00 | 23.89 | 324.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.51 | 300.00 | 15.51 | 300.00 | 15.51 |
February | 276.00 | 15.60 | 276.00 | 15.60 | 276.00 | 15.60 |
March | 324.00 | 15.79 | 324.00 | 15.79 | 324.00 | 15.79 |
April | 300.00 | 17.60 | 273.50 | 17.38 | 273.50 | 17.30 |
May | 217.17 | 21.37 | 182.33 | 21.92 | 103.67 | 21.45 |
June | 179.00 | 25.03 | 233.67 | 25.72 | 115.50 | 25.82 |
July | 207.67 | 26.53 | 286.00 | 26.50 | 200.50 | 26.54 |
August | 197.67 | 26.11 | 280.67 | 26.28 | 171.67 | 26.36 |
September | 214.00 | 21.97 | 155.17 | 22.62 | 85.00 | 22.37 |
October | 300.00 | 18.11 | 261.17 | 17.82 | 261.17 | 17.71 |
November | 288.00 | 16.06 | 288.00 | 16.06 | 288.00 | 16.06 |
December | 300.00 | 15.52 | 300.00 | 15.52 | 300.00 | 15.52 |
Annual Sum or Average | 3103.50 | 18.87 | 3160.50 | 19.17 | 2699.00 | 18.90 |
Minimum of Months | 179.00 | 15.51 | 155.17 | 15.51 | 85.00 | 15.51 |
Maximum of Months | 324.00 | 26.53 | 324.00 | 26.50 | 324.00 | 26.54 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 9.99 | 300.00 | 9.99 | 300.00 | 9.99 |
February | 276.00 | 10.07 | 276.00 | 10.07 | 276.00 | 10.07 |
March | 324.00 | 10.32 | 324.00 | 10.32 | 324.00 | 10.32 |
April | 300.00 | 12.38 | 300.00 | 12.38 | 300.00 | 12.38 |
May | 271.67 | 18.58 | 224.67 | 18.50 | 191.33 | 18.11 |
June | 245.83 | 24.30 | 174.50 | 25.06 | 126.00 | 25.34 |
July | 235.00 | 28.48 | 293.17 | 28.17 | 231.50 | 28.29 |
August | 200.17 | 26.08 | 255.17 | 26.39 | 147.17 | 26.64 |
September | 271.50 | 19.93 | 191.00 | 19.69 | 176.50 | 19.45 |
October | 300.00 | 13.17 | 300.00 | 13.17 | 300.00 | 13.17 |
November | 288.00 | 10.45 | 288.00 | 10.45 | 288.00 | 10.45 |
December | 300.00 | 10.00 | 300.00 | 10.00 | 300.00 | 10.00 |
Annual Sum or Average | 3312.17 | 15.44 | 3226.50 | 15.49 | 2960.50 | 15.23 |
Minimum of Months | 200.17 | 9.99 | 174.50 | 9.99 | 126.00 | 9.99 |
Maximum of Months | 324.00 | 28.48 | 324.00 | 28.17 | 324.00 | 28.29 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 22716034.87 | 6257729.16 | 6.33 | 22716034.87 | 0.00 | 0.00 | 0.10 | 13-APR-15:00 | 0.00 | 01-APR-00:10 | 1630.94 | 13-APR-15:00 | 1630.94 | 13-APR-15:00 | 0.00 | 13-APR-15:40 | 447.49 | 13-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.240534E+10 | 0.651440E+09 | 169.72 | 0.218655E+10 | 0.218796E+09 | 0.00 | 1.00 | 25-MAY-17:43 | 0.00 | 01-MAY-00:03 | 20481.31 | 25-MAY-18:23 | 18283.21 | 25-MAY-18:23 | 2294.66 | 25-MAY-17:10 | 5270.57 | 25-MAY-17:43 | 0.00 | 01-MAY-00:03 |
June | 0.645341E+10 | 0.173004E+10 | 313.54 | 0.526693E+10 | 0.118648E+10 | 0.00 | 1.00 | 21-JUN-17:43 | 0.00 | 01-JUN-00:10 | 23537.15 | 25-JUN-23:02 | 19119.28 | 21-JUN-18:23 | 8696.09 | 25-JUN-23:02 | 5746.69 | 29-JUN-17:06 | 0.00 | 01-JUN-00:10 |
July | 0.952589E+10 | 0.251654E+10 | 395.66 | 0.767578E+10 | 0.185011E+10 | 0.00 | 1.00 | 01-JUL-17:43 | 0.00 | 01-JUL-00:15 | 24290.30 | 23-JUL-23:01 | 20193.40 | 07-JUL-17:43 | 9513.70 | 04-JUL-23:03 | 5531.35 | 23-JUL-23:01 | 0.00 | 01-JUL-00:10 |
August | 0.826783E+10 | 0.217226E+10 | 381.27 | 0.665065E+10 | 0.161718E+10 | 0.00 | 1.00 | 04-AUG-17:43 | 0.00 | 01-AUG-00:10 | 22453.20 | 27-AUG-23:02 | 20268.71 | 05-AUG-18:23 | 6533.12 | 31-AUG-17:10 | 5528.62 | 08-AUG-17:08 | 0.00 | 01-AUG-00:10 |
September | 0.233538E+10 | 0.623669E+09 | 179.76 | 0.210623E+10 | 0.229145E+09 | 0.00 | 1.00 | 01-SEP-17:08 | 0.00 | 01-SEP-00:15 | 21274.02 | 01-SEP-17:43 | 18586.78 | 01-SEP-17:43 | 2880.93 | 01-SEP-17:08 | 5033.32 | 01-SEP-17:08 | 0.00 | 01-SEP-00:10 |
October | 0.112515E+09 | 30708603.94 | 18.83 | 0.111361E+09 | 1154063.67 | 0.00 | 0.20 | 21-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3392.50 | 21-OCT-15:00 | 3392.50 | 21-OCT-15:00 | 111.88 | 19-OCT-15:00 | 918.13 | 21-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.291231E+11 | 0.773092E+10 | 1465.13 | 0.240202E+11 | 0.510286E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.952589E+10 | 0.251654E+10 | 395.66 | 0.767578E+10 | 0.185011E+10 | 0.00 | 1.00 | 0.00 | 24290.30 | 20268.71 | 9513.70 | 5746.69 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.222691E+10 | 0.655347E+09 | 45.50 | 0.191369E+10 | 0.313225E+09 | 0.00 | 0.40 | 25-MAY-15:00 | 0.00 | 01-MAY-00:03 | 26367.28 | 25-MAY-15:00 | 21723.63 | 25-MAY-15:00 | 5208.08 | 26-MAY-11:00 | 7857.65 | 25-MAY-15:00 | 0.00 | 01-MAY-00:03 |
June | 0.967154E+10 | 0.279629E+10 | 129.08 | 0.742795E+10 | 0.224359E+10 | 0.00 | 1.00 | 29-JUN-17:06 | 0.00 | 01-JUN-00:10 | 74131.63 | 30-JUN-17:06 | 56693.22 | 30-JUN-17:06 | 18309.11 | 30-JUN-16:00 | 21170.82 | 29-JUN-17:06 | 0.00 | 01-JUN-00:10 |
July | 0.170382E+11 | 0.483184E+10 | 204.92 | 0.129317E+11 | 0.410650E+10 | 0.00 | 1.00 | 23-JUL-10:53 | 0.00 | 01-JUL-00:10 | 79726.52 | 23-JUL-10:53 | 61032.76 | 24-JUL-17:06 | 27556.45 | 23-JUL-10:53 | 20601.45 | 23-JUL-10:53 | 0.00 | 01-JUL-00:10 |
August | 0.907822E+10 | 0.255868E+10 | 117.14 | 0.687155E+10 | 0.220666E+10 | 0.00 | 0.81 | 08-AUG-17:08 | 0.00 | 01-AUG-00:10 | 61328.79 | 08-AUG-17:08 | 46016.57 | 25-AUG-17:10 | 19457.06 | 08-AUG-17:08 | 16739.66 | 08-AUG-17:08 | 0.00 | 01-AUG-00:10 |
September | 0.854147E+09 | 0.240780E+09 | 17.76 | 0.711567E+09 | 0.142580E+09 | 0.00 | 0.58 | 01-SEP-17:10 | 0.00 | 01-SEP-00:10 | 40767.95 | 01-SEP-17:10 | 35009.20 | 01-SEP-17:10 | 6502.11 | 01-SEP-09:50 | 10940.77 | 01-SEP-17:10 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.388690E+11 | 0.110829E+11 | 514.40 | 0.298564E+11 | 0.901256E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.170382E+11 | 0.483184E+10 | 204.92 | 0.129317E+11 | 0.410650E+10 | 0.00 | 1.00 | 0.00 | 79726.52 | 61032.76 | 27556.45 | 21170.82 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.95 | 31.18 | 42.77 | 27.99 | 294.73 | 0.00 | 0.00 | 0.00 |
February | 119.55 | 54.64 | 64.92 | 76.14 | 230.09 | 0.00 | 0.00 | 0.00 |
March | 157.31 | 80.63 | 76.68 | 125.32 | 172.42 | 0.00 | 0.00 | 0.00 |
April | 200.46 | 101.51 | 98.95 | 198.92 | 96.66 | 0.00 | 0.00 | 0.00 |
May | 246.84 | 117.94 | 128.91 | 282.26 | 57.37 | 0.00 | 0.00 | 0.00 |
June | 237.82 | 102.89 | 134.94 | 283.10 | 44.71 | 0.00 | 0.00 | 0.00 |
July | 254.37 | 118.55 | 135.82 | 308.25 | 46.32 | 0.00 | 0.00 | 0.00 |
August | 208.32 | 94.34 | 113.99 | 243.10 | 54.20 | 0.00 | 0.00 | 0.00 |
September | 163.18 | 73.18 | 90.01 | 169.08 | 77.98 | 0.00 | 0.00 | 0.00 |
October | 103.25 | 41.48 | 61.77 | 86.27 | 103.81 | 0.00 | 0.00 | 0.00 |
November | 62.99 | 21.46 | 41.53 | 32.05 | 165.14 | 0.00 | 0.00 | 0.00 |
December | 55.63 | 19.35 | 36.28 | 14.71 | 285.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.18 | 71.53 | 85.65 | 154.39 | 135.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 55.63 | 19.35 | 36.28 | 14.71 | 44.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 254.37 | 118.55 | 135.82 | 308.25 | 294.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.95 | 31.18 | 42.77 | 27.99 | 294.73 | 0.00 | 0.00 | 0.00 |
February | 119.55 | 54.64 | 64.92 | 76.14 | 230.09 | 0.00 | 0.00 | 0.00 |
March | 157.31 | 80.63 | 76.68 | 125.32 | 172.42 | 0.00 | 0.00 | 0.00 |
April | 200.46 | 101.51 | 98.95 | 198.92 | 96.66 | 0.00 | 0.00 | 0.00 |
May | 246.84 | 117.94 | 128.91 | 282.26 | 57.37 | 0.00 | 0.00 | 0.00 |
June | 237.82 | 102.89 | 134.94 | 283.10 | 44.71 | 0.00 | 0.00 | 0.00 |
July | 254.37 | 118.55 | 135.82 | 308.25 | 46.32 | 0.00 | 0.00 | 0.00 |
August | 208.32 | 94.34 | 113.99 | 243.10 | 54.20 | 0.00 | 0.00 | 0.00 |
September | 163.18 | 73.18 | 90.01 | 169.08 | 77.98 | 0.00 | 0.00 | 0.00 |
October | 103.25 | 41.48 | 61.77 | 86.27 | 103.81 | 0.00 | 0.00 | 0.00 |
November | 62.99 | 21.46 | 41.53 | 32.05 | 165.14 | 0.00 | 0.00 | 0.00 |
December | 55.63 | 19.35 | 36.28 | 14.71 | 285.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.18 | 71.53 | 85.65 | 154.39 | 135.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 55.63 | 19.35 | 36.28 | 14.71 | 44.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 254.37 | 118.55 | 135.82 | 308.25 | 294.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.27 | 0.00 | 19.27 | 0.17 | 188.65 | 0.00 | 0.00 | 0.00 |
February | 29.60 | 0.00 | 29.60 | 2.25 | 146.79 | 0.00 | 0.00 | 0.00 |
March | 36.42 | 0.00 | 36.42 | 5.77 | 108.36 | 0.00 | 0.00 | 0.00 |
April | 47.84 | 0.47 | 47.37 | 25.23 | 57.53 | 0.00 | 0.00 | 0.00 |
May | 67.20 | 3.62 | 63.58 | 61.17 | 31.49 | 0.00 | 0.00 | 0.00 |
June | 74.90 | 8.20 | 66.70 | 80.33 | 24.54 | 0.00 | 0.00 | 0.00 |
July | 71.49 | 6.04 | 65.44 | 77.12 | 25.31 | 0.00 | 0.00 | 0.00 |
August | 54.56 | 1.10 | 53.45 | 51.92 | 30.71 | 0.00 | 0.00 | 0.00 |
September | 42.40 | 0.03 | 42.37 | 29.41 | 46.55 | 0.00 | 0.00 | 0.00 |
October | 29.41 | 0.00 | 29.41 | 10.95 | 62.93 | 0.00 | 0.00 | 0.00 |
November | 19.47 | 0.00 | 19.47 | 1.70 | 102.84 | 0.00 | 0.00 | 0.00 |
December | 16.33 | 0.00 | 16.33 | 0.01 | 180.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42.47 | 1.63 | 40.84 | 29.00 | 83.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.33 | 0.00 | 16.33 | 0.01 | 24.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.90 | 8.20 | 66.70 | 80.33 | 188.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.27 | 0.00 | 19.27 | 0.17 | 188.65 | 0.00 | 0.00 | 0.00 |
February | 29.60 | 0.00 | 29.60 | 2.25 | 146.79 | 0.00 | 0.00 | 0.00 |
March | 36.42 | 0.00 | 36.42 | 5.77 | 108.36 | 0.00 | 0.00 | 0.00 |
April | 47.84 | 0.47 | 47.37 | 25.23 | 57.53 | 0.00 | 0.00 | 0.00 |
May | 67.20 | 3.62 | 63.58 | 61.17 | 31.49 | 0.00 | 0.00 | 0.00 |
June | 74.90 | 8.19 | 66.70 | 80.33 | 24.54 | 0.00 | 0.00 | 0.00 |
July | 71.49 | 6.04 | 65.44 | 77.11 | 25.31 | 0.00 | 0.00 | 0.00 |
August | 54.55 | 1.10 | 53.45 | 51.92 | 30.71 | 0.00 | 0.00 | 0.00 |
September | 42.40 | 0.03 | 42.37 | 29.41 | 46.55 | 0.00 | 0.00 | 0.00 |
October | 29.41 | 0.00 | 29.41 | 10.95 | 62.93 | 0.00 | 0.00 | 0.00 |
November | 19.47 | 0.00 | 19.47 | 1.70 | 102.84 | 0.00 | 0.00 | 0.00 |
December | 16.32 | 0.00 | 16.32 | 0.01 | 180.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42.47 | 1.63 | 40.84 | 28.99 | 83.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.32 | 0.00 | 16.32 | 0.01 | 24.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.90 | 8.19 | 66.70 | 80.33 | 188.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 2.05 | 260.79 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 24.26 | 193.80 | 0.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 58.01 | 134.31 | 1.33 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 115.40 | 71.46 | 2.83 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 153.72 | 50.18 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 160.63 | 48.77 | 26.33 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 158.91 | 61.91 | 13.17 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 124.72 | 58.88 | 24.33 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 86.07 | 62.76 | 10.33 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 44.30 | 67.43 | 33.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 14.35 | 118.50 | 14.33 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 0.57 | 244.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 78.86 | 114.19 | 126.33 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 0.57 | 48.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 160.63 | 260.79 | 33.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 2.05 | 260.79 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 24.26 | 193.80 | 0.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 58.01 | 134.31 | 1.33 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 115.40 | 71.46 | 2.83 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 153.72 | 50.18 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 160.63 | 48.77 | 26.33 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 158.91 | 61.91 | 13.17 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 124.72 | 58.88 | 24.33 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 86.07 | 62.76 | 10.33 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 44.30 | 67.43 | 33.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 14.35 | 118.50 | 14.33 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 0.57 | 244.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 78.86 | 114.19 | 126.33 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 0.57 | 48.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 160.63 | 260.79 | 33.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 2.05 | 260.79 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 24.26 | 193.80 | 0.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 58.01 | 134.31 | 1.33 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 115.40 | 71.46 | 2.83 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 153.72 | 50.18 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 160.63 | 48.77 | 26.33 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 158.91 | 61.91 | 13.17 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 124.72 | 58.88 | 24.33 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 86.07 | 62.76 | 10.33 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 44.30 | 67.43 | 33.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 14.35 | 118.50 | 14.33 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 0.57 | 244.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 78.86 | 114.19 | 126.33 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 0.57 | 48.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 160.63 | 260.79 | 33.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 2.05 | 260.79 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 24.26 | 193.80 | 0.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 58.01 | 134.31 | 1.33 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 115.40 | 71.46 | 2.83 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 153.72 | 50.18 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 160.63 | 48.77 | 26.33 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 158.91 | 61.91 | 13.17 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 124.72 | 58.88 | 24.33 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 86.07 | 62.76 | 10.33 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 44.30 | 67.43 | 33.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 14.35 | 118.50 | 14.33 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 0.57 | 244.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 78.86 | 114.19 | 126.33 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 0.57 | 48.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 160.63 | 260.79 | 33.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 2.05 | 260.79 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 24.26 | 193.80 | 0.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 58.01 | 134.31 | 1.33 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 115.40 | 71.46 | 2.83 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 153.72 | 50.18 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 160.63 | 48.77 | 26.33 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 158.91 | 61.91 | 13.17 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 124.72 | 58.88 | 24.33 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 86.07 | 62.76 | 10.33 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 44.30 | 67.43 | 33.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 14.35 | 118.50 | 14.33 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 0.57 | 244.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 78.86 | 114.19 | 126.33 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 0.57 | 48.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 160.63 | 260.79 | 33.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 2.05 | 260.79 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 24.26 | 193.80 | 0.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 58.01 | 134.31 | 1.33 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 115.40 | 71.46 | 2.83 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 153.72 | 50.18 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 160.63 | 48.77 | 26.33 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 158.91 | 61.91 | 13.17 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 124.72 | 58.88 | 24.33 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 86.07 | 62.76 | 10.33 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 44.30 | 67.43 | 33.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 14.35 | 118.50 | 14.33 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 0.57 | 244.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 78.86 | 114.19 | 126.33 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 0.57 | 48.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 160.63 | 260.79 | 33.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 2.05 | 260.79 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 24.26 | 193.80 | 0.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 58.01 | 134.31 | 1.33 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 115.40 | 71.46 | 2.83 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 153.72 | 50.18 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 160.63 | 48.77 | 26.33 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 158.91 | 61.91 | 13.17 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 124.72 | 58.88 | 24.33 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 86.07 | 62.76 | 10.33 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 44.30 | 67.43 | 33.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 14.35 | 118.50 | 14.33 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 0.57 | 244.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 78.86 | 114.19 | 126.33 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 0.57 | 48.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 160.63 | 260.79 | 33.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 2.05 | 260.79 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 24.26 | 193.80 | 0.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 58.01 | 134.31 | 1.33 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 115.40 | 71.46 | 2.83 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 153.72 | 50.18 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 160.63 | 48.77 | 26.33 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 158.91 | 61.91 | 13.17 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 124.72 | 58.88 | 24.33 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 86.07 | 62.76 | 10.33 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 44.30 | 67.43 | 33.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 14.35 | 118.50 | 14.33 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 0.57 | 244.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 78.86 | 114.19 | 126.33 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 0.57 | 48.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 160.63 | 260.79 | 33.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 2.05 | 260.79 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 24.26 | 193.80 | 0.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 58.01 | 134.31 | 1.33 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 115.40 | 71.46 | 2.83 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 153.72 | 50.18 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 160.63 | 48.77 | 26.33 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 158.91 | 61.91 | 13.17 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 124.72 | 58.88 | 24.33 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 86.07 | 62.76 | 10.33 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 44.30 | 67.43 | 33.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 14.35 | 118.50 | 14.33 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 0.57 | 244.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 78.86 | 114.19 | 126.33 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 0.57 | 48.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 160.63 | 260.79 | 33.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 2.05 | 260.79 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 24.26 | 193.80 | 0.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 58.01 | 134.31 | 1.33 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 115.40 | 71.46 | 2.83 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 153.72 | 50.18 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 160.63 | 48.77 | 26.33 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 158.91 | 61.91 | 13.17 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 124.72 | 58.88 | 24.33 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 86.07 | 62.76 | 10.33 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 44.30 | 67.43 | 33.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 14.35 | 118.50 | 14.33 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 0.57 | 244.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 78.86 | 114.19 | 126.33 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 0.57 | 48.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 160.63 | 260.79 | 33.67 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198056E+09 | 83504024.34 | 0.114552E+09 | 74961670.98 | 0.789395E+09 |
February | 0.289227E+09 | 0.132178E+09 | 0.157049E+09 | 0.184207E+09 | 0.556635E+09 |
March | 0.421337E+09 | 0.215967E+09 | 0.205370E+09 | 0.335663E+09 | 0.461807E+09 |
April | 0.519600E+09 | 0.263122E+09 | 0.256478E+09 | 0.515592E+09 | 0.250550E+09 |
May | 0.661147E+09 | 0.315879E+09 | 0.345268E+09 | 0.755992E+09 | 0.153663E+09 |
June | 0.616438E+09 | 0.266683E+09 | 0.349755E+09 | 0.733806E+09 | 0.115888E+09 |
July | 0.681317E+09 | 0.317534E+09 | 0.363784E+09 | 0.825610E+09 | 0.124068E+09 |
August | 0.557977E+09 | 0.252677E+09 | 0.305299E+09 | 0.651129E+09 | 0.145176E+09 |
September | 0.422974E+09 | 0.189676E+09 | 0.233298E+09 | 0.438256E+09 | 0.202135E+09 |
October | 0.276554E+09 | 0.111113E+09 | 0.165441E+09 | 0.231064E+09 | 0.278035E+09 |
November | 0.163279E+09 | 55629203.46 | 0.107650E+09 | 83084006.46 | 0.428033E+09 |
December | 0.149007E+09 | 51834439.10 | 97172094.31 | 39407707.87 | 0.764062E+09 |
Annual Sum or Average | 0.495691E+10 | 0.225580E+10 | 0.270112E+10 | 0.486877E+10 | 0.426945E+10 |
Minimum of Months | 0.149007E+09 | 51834439.10 | 97172094.31 | 39407707.87 | 0.115888E+09 |
Maximum of Months | 0.681317E+09 | 0.317534E+09 | 0.363784E+09 | 0.825610E+09 | 0.789395E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198056E+09 | 83504024.34 | 0.114552E+09 | 74961670.98 | 0.789395E+09 |
February | 0.289227E+09 | 0.132178E+09 | 0.157049E+09 | 0.184207E+09 | 0.556635E+09 |
March | 0.421337E+09 | 0.215967E+09 | 0.205370E+09 | 0.335663E+09 | 0.461807E+09 |
April | 0.519600E+09 | 0.263122E+09 | 0.256478E+09 | 0.515592E+09 | 0.250550E+09 |
May | 0.661147E+09 | 0.315879E+09 | 0.345268E+09 | 0.755992E+09 | 0.153663E+09 |
June | 0.616438E+09 | 0.266683E+09 | 0.349755E+09 | 0.733806E+09 | 0.115888E+09 |
July | 0.681317E+09 | 0.317534E+09 | 0.363784E+09 | 0.825610E+09 | 0.124068E+09 |
August | 0.557977E+09 | 0.252677E+09 | 0.305299E+09 | 0.651129E+09 | 0.145176E+09 |
September | 0.422974E+09 | 0.189676E+09 | 0.233298E+09 | 0.438256E+09 | 0.202135E+09 |
October | 0.276554E+09 | 0.111113E+09 | 0.165441E+09 | 0.231064E+09 | 0.278035E+09 |
November | 0.163279E+09 | 55629203.46 | 0.107650E+09 | 83084006.46 | 0.428033E+09 |
December | 0.149007E+09 | 51834439.10 | 97172094.31 | 39407707.87 | 0.764062E+09 |
Annual Sum or Average | 0.495691E+10 | 0.225580E+10 | 0.270112E+10 | 0.486877E+10 | 0.426945E+10 |
Minimum of Months | 0.149007E+09 | 51834439.10 | 97172094.31 | 39407707.87 | 0.115888E+09 |
Maximum of Months | 0.681317E+09 | 0.317534E+09 | 0.363784E+09 | 0.825610E+09 | 0.789395E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51607008.66 | 0.00 | 51607008.66 | 455394.04 | 0.505274E+09 |
February | 71600876.49 | 0.00 | 71600876.49 | 5452795.64 | 0.355105E+09 |
March | 97556880.51 | 6990.70 | 97549889.82 | 15456158.45 | 0.290231E+09 |
April | 0.124006E+09 | 1215458.85 | 0.122790E+09 | 65400017.73 | 0.149121E+09 |
May | 0.179987E+09 | 9691789.75 | 0.170295E+09 | 0.163848E+09 | 84335687.83 |
June | 0.194135E+09 | 21241450.32 | 0.172894E+09 | 0.208213E+09 | 63620516.46 |
July | 0.191472E+09 | 16188327.23 | 0.175283E+09 | 0.206551E+09 | 67790270.63 |
August | 0.146121E+09 | 2953379.03 | 0.143168E+09 | 0.139054E+09 | 82248675.80 |
September | 0.109909E+09 | 79221.47 | 0.109830E+09 | 76227176.31 | 0.120655E+09 |
October | 78778790.27 | 0.00 | 78778790.27 | 29323779.09 | 0.168555E+09 |
November | 50478913.01 | 0.00 | 50478913.01 | 4394732.93 | 0.266569E+09 |
December | 43725560.62 | 0.00 | 43725560.62 | 13929.08 | 0.482268E+09 |
Annual Sum or Average | 0.133938E+10 | 51376617.36 | 0.128800E+10 | 0.914390E+09 | 0.263577E+10 |
Minimum of Months | 43725560.62 | 0.00 | 43725560.62 | 13929.08 | 63620516.46 |
Maximum of Months | 0.194135E+09 | 21241450.32 | 0.175283E+09 | 0.208213E+09 | 0.505274E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51605304.71 | 0.00 | 51605304.71 | 455301.10 | 0.505275E+09 |
February | 71598623.61 | 0.00 | 71598623.61 | 5452168.48 | 0.355106E+09 |
March | 97553940.55 | 6990.37 | 97546950.18 | 15454735.76 | 0.290232E+09 |
April | 0.124002E+09 | 1215401.88 | 0.122787E+09 | 65396881.85 | 0.149121E+09 |
May | 0.179982E+09 | 9691335.48 | 0.170290E+09 | 0.163841E+09 | 84335302.00 |
June | 0.194129E+09 | 21240454.70 | 0.172888E+09 | 0.208205E+09 | 63620108.81 |
July | 0.191466E+09 | 16187568.47 | 0.175278E+09 | 0.206544E+09 | 67789733.34 |
August | 0.146117E+09 | 2953240.61 | 0.143163E+09 | 0.139049E+09 | 82248324.13 |
September | 0.109906E+09 | 79217.76 | 0.109827E+09 | 76223535.49 | 0.120654E+09 |
October | 78776162.97 | 0.00 | 78776162.97 | 29321519.60 | 0.168555E+09 |
November | 50477193.11 | 0.00 | 50477193.11 | 4394301.60 | 0.266570E+09 |
December | 43724069.50 | 0.00 | 43724069.50 | 13918.40 | 0.482269E+09 |
Annual Sum or Average | 0.133934E+10 | 51374209.27 | 0.128796E+10 | 0.914352E+09 | 0.263578E+10 |
Minimum of Months | 43724069.50 | 0.00 | 43724069.50 | 13918.40 | 63620108.81 |
Maximum of Months | 0.194129E+09 | 21240454.70 | 0.175278E+09 | 0.208205E+09 | 0.505275E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 5500040.51 | 0.698492E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 58690264.33 | 0.468843E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.155383E+09 | 0.359748E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.299114E+09 | 0.185218E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.411715E+09 | 0.134410E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.416357E+09 | 0.126405E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.425616E+09 | 0.165825E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.334043E+09 | 0.157705E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.223086E+09 | 0.162663E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.118663E+09 | 0.180595E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 37185457.72 | 0.307154E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 1530264.71 | 0.654114E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.248688E+10 | 0.360117E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 1530264.71 | 0.126405E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.425616E+09 | 0.698492E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 5500040.51 | 0.698492E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 58690264.33 | 0.468843E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.155383E+09 | 0.359748E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.299114E+09 | 0.185218E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.411715E+09 | 0.134410E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.416357E+09 | 0.126405E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.425616E+09 | 0.165825E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.334043E+09 | 0.157705E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.223086E+09 | 0.162663E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.118663E+09 | 0.180595E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 37185457.72 | 0.307154E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 1530264.71 | 0.654114E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.248688E+10 | 0.360117E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 1530264.71 | 0.126405E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.425616E+09 | 0.698492E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 5500040.51 | 0.698492E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 58690264.33 | 0.468843E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.155383E+09 | 0.359748E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.299114E+09 | 0.185218E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.411715E+09 | 0.134410E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.416357E+09 | 0.126405E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.425616E+09 | 0.165825E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.334043E+09 | 0.157705E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.223086E+09 | 0.162663E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.118663E+09 | 0.180595E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 37185457.72 | 0.307154E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 1530264.71 | 0.654114E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.248688E+10 | 0.360117E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 1530264.71 | 0.126405E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.425616E+09 | 0.698492E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 5500040.51 | 0.698492E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 58690264.33 | 0.468843E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.155383E+09 | 0.359748E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.299114E+09 | 0.185218E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.411715E+09 | 0.134410E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.416357E+09 | 0.126405E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.425616E+09 | 0.165825E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.334043E+09 | 0.157705E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.223086E+09 | 0.162663E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.118663E+09 | 0.180595E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 37185457.72 | 0.307154E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 1530264.71 | 0.654114E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.248688E+10 | 0.360117E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 1530264.71 | 0.126405E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.425616E+09 | 0.698492E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 5500040.51 | 0.698492E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 58690264.33 | 0.468843E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.155383E+09 | 0.359748E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.299114E+09 | 0.185218E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.411715E+09 | 0.134410E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.416357E+09 | 0.126405E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.425616E+09 | 0.165825E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.334043E+09 | 0.157705E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.223086E+09 | 0.162663E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.118663E+09 | 0.180595E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 37185457.72 | 0.307154E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 1530264.71 | 0.654114E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.248688E+10 | 0.360117E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 1530264.71 | 0.126405E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.425616E+09 | 0.698492E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 5500040.51 | 0.698492E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 58690264.33 | 0.468843E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.155383E+09 | 0.359748E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.299114E+09 | 0.185218E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.411715E+09 | 0.134410E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.416357E+09 | 0.126405E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.425616E+09 | 0.165825E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.334043E+09 | 0.157705E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.223086E+09 | 0.162663E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.118663E+09 | 0.180595E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 37185457.72 | 0.307154E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 1530264.71 | 0.654114E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.248688E+10 | 0.360117E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 1530264.71 | 0.126405E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.425616E+09 | 0.698492E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 5500040.51 | 0.698492E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 58690264.33 | 0.468843E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.155383E+09 | 0.359748E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.299114E+09 | 0.185218E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.411715E+09 | 0.134410E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.416357E+09 | 0.126405E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.425616E+09 | 0.165825E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.334043E+09 | 0.157705E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.223086E+09 | 0.162663E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.118663E+09 | 0.180595E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 37185457.72 | 0.307154E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 1530264.71 | 0.654114E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.248688E+10 | 0.360117E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 1530264.71 | 0.126405E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.425616E+09 | 0.698492E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 5500040.51 | 0.698492E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 58690264.33 | 0.468843E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.155383E+09 | 0.359748E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.299114E+09 | 0.185218E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.411715E+09 | 0.134410E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.416357E+09 | 0.126405E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.425616E+09 | 0.165825E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.334043E+09 | 0.157705E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.223086E+09 | 0.162663E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.118663E+09 | 0.180595E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 37185457.72 | 0.307154E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 1530264.71 | 0.654114E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.248688E+10 | 0.360117E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 1530264.71 | 0.126405E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.425616E+09 | 0.698492E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 5500040.51 | 0.698492E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 58690264.33 | 0.468843E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.155383E+09 | 0.359748E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.299114E+09 | 0.185218E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.411715E+09 | 0.134410E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.416357E+09 | 0.126405E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.425616E+09 | 0.165825E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.334043E+09 | 0.157705E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.223086E+09 | 0.162663E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.118663E+09 | 0.180595E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 37185457.72 | 0.307154E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 1530264.71 | 0.654114E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.248688E+10 | 0.360117E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 1530264.71 | 0.126405E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.425616E+09 | 0.698492E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 5500040.51 | 0.698492E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 58690264.33 | 0.468843E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.155383E+09 | 0.359748E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.299114E+09 | 0.185218E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.411715E+09 | 0.134410E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.416357E+09 | 0.126405E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.425616E+09 | 0.165825E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.334043E+09 | 0.157705E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.223086E+09 | 0.162663E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.118663E+09 | 0.180595E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 37185457.72 | 0.307154E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 1530264.71 | 0.654114E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.248688E+10 | 0.360117E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 1530264.71 | 0.126405E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.425616E+09 | 0.698492E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 35.88 | 946.32 | 186.43 | 62.35 | 124.07 | 0.00 | 0.00 |
February | 138.98 | 735.94 | 298.30 | 109.27 | 189.03 | 0.00 | 0.00 |
March | 250.17 | 549.54 | 387.46 | 161.27 | 226.19 | 0.00 | 0.00 |
April | 445.58 | 305.67 | 496.61 | 203.96 | 292.64 | 0.00 | 0.00 |
May | 684.57 | 175.43 | 628.09 | 243.11 | 384.98 | 0.00 | 0.00 |
June | 723.42 | 135.06 | 625.44 | 222.16 | 403.28 | 0.00 | 0.00 |
July | 767.27 | 139.80 | 651.72 | 249.19 | 402.53 | 0.00 | 0.00 |
August | 589.37 | 169.16 | 525.76 | 190.88 | 334.88 | 0.00 | 0.00 |
September | 395.11 | 247.20 | 411.17 | 146.42 | 264.76 | 0.00 | 0.00 |
October | 191.28 | 330.32 | 265.33 | 82.97 | 182.36 | 0.00 | 0.00 |
November | 58.85 | 527.31 | 164.94 | 42.92 | 122.01 | 0.00 | 0.00 |
December | 15.61 | 916.83 | 143.92 | 38.71 | 105.21 | 0.00 | 0.00 |
Annual Sum or Average | 359.28 | 430.45 | 399.31 | 146.32 | 252.99 | 0.00 | 0.00 |
Minimum of Months | 15.61 | 135.06 | 143.92 | 38.71 | 105.21 | 0.00 | 0.00 |
Maximum of Months | 767.27 | 946.32 | 651.72 | 249.19 | 403.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 107.15 | 26621.74 | 263.87 | 93.87 | 170.00 | 0.00 | 0.00 |
February | 1011.12 | 19521.62 | 465.60 | 215.66 | 249.93 | 0.00 | 0.00 |
March | 1992.05 | 11995.60 | 667.44 | 377.68 | 289.76 | 0.00 | 0.00 |
April | 3976.91 | 4936.76 | 970.49 | 610.55 | 359.94 | 0.00 | 0.00 |
May | 5258.89 | 1759.66 | 1190.47 | 667.62 | 522.86 | 0.00 | 0.00 |
June | 6067.55 | 1734.94 | 1256.31 | 722.81 | 533.50 | 0.00 | 0.00 |
July | 7004.37 | 2764.75 | 1283.98 | 764.19 | 519.80 | 0.00 | 0.00 |
August | 4604.65 | 2490.56 | 1022.95 | 576.18 | 446.77 | 0.00 | 0.00 |
September | 2887.93 | 2127.09 | 744.02 | 384.83 | 359.19 | 0.00 | 0.00 |
October | 1460.67 | 3252.90 | 429.05 | 164.60 | 264.45 | 0.00 | 0.00 |
November | 502.45 | 9318.99 | 257.19 | 79.94 | 177.26 | 0.00 | 0.00 |
December | 31.64 | 24799.02 | 204.66 | 53.45 | 151.21 | 0.00 | 0.00 |
Annual Sum or Average | 2919.45 | 9244.79 | 730.99 | 393.45 | 337.55 | 0.00 | 0.00 |
Minimum of Months | 31.64 | 1734.94 | 204.66 | 53.45 | 151.21 | 0.00 | 0.00 |
Maximum of Months | 7004.37 | 26621.74 | 1283.98 | 764.19 | 533.50 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 96114118.40 | 0.253462E+10 | 0.499325E+09 | 0.167008E+09 | 0.332317E+09 | 0.00 | 0.00 |
February | 0.336213E+09 | 0.178038E+10 | 0.721654E+09 | 0.264356E+09 | 0.457298E+09 | 0.00 | 0.00 |
March | 0.670050E+09 | 0.147189E+10 | 0.103778E+10 | 0.431948E+09 | 0.605837E+09 | 0.00 | 0.00 |
April | 0.115493E+10 | 0.792293E+09 | 0.128721E+10 | 0.528674E+09 | 0.758533E+09 | 0.00 | 0.00 |
May | 0.183354E+10 | 0.469863E+09 | 0.168226E+10 | 0.651142E+09 | 0.103112E+10 | 0.00 | 0.00 |
June | 0.187510E+10 | 0.350083E+09 | 0.162114E+10 | 0.575848E+09 | 0.104529E+10 | 0.00 | 0.00 |
July | 0.205505E+10 | 0.374448E+09 | 0.174557E+10 | 0.667443E+09 | 0.107813E+10 | 0.00 | 0.00 |
August | 0.157858E+10 | 0.453066E+09 | 0.140819E+10 | 0.511261E+09 | 0.896930E+09 | 0.00 | 0.00 |
September | 0.102412E+10 | 0.640737E+09 | 0.106576E+10 | 0.379510E+09 | 0.686253E+09 | 0.00 | 0.00 |
October | 0.512328E+09 | 0.884737E+09 | 0.710663E+09 | 0.222227E+09 | 0.488436E+09 | 0.00 | 0.00 |
November | 0.152541E+09 | 0.136679E+10 | 0.427515E+09 | 0.111258E+09 | 0.316257E+09 | 0.00 | 0.00 |
December | 41818792.72 | 0.245564E+10 | 0.385463E+09 | 0.103669E+09 | 0.281794E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.113304E+11 | 0.135745E+11 | 0.125925E+11 | 0.461434E+10 | 0.797820E+10 | 0.00 | 0.00 |
Minimum of Months | 41818792.72 | 0.350083E+09 | 0.385463E+09 | 0.103669E+09 | 0.281794E+09 | 0.00 | 0.00 |
Maximum of Months | 0.205505E+10 | 0.253462E+10 | 0.174557E+10 | 0.667443E+09 | 0.107813E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.286996E+09 | 0.713037E+11 | 0.706745E+09 | 0.251420E+09 | 0.455325E+09 | 0.00 | 0.00 |
February | 0.244611E+10 | 0.472267E+11 | 0.112637E+10 | 0.521732E+09 | 0.604639E+09 | 0.00 | 0.00 |
March | 0.533552E+10 | 0.321290E+11 | 0.178768E+10 | 0.101158E+10 | 0.776105E+09 | 0.00 | 0.00 |
April | 0.103081E+11 | 0.127961E+11 | 0.251552E+10 | 0.158256E+10 | 0.932962E+09 | 0.00 | 0.00 |
May | 0.140854E+11 | 0.471307E+10 | 0.318856E+10 | 0.178814E+10 | 0.140042E+10 | 0.00 | 0.00 |
June | 0.157271E+11 | 0.449697E+10 | 0.325636E+10 | 0.187352E+10 | 0.138284E+10 | 0.00 | 0.00 |
July | 0.187605E+11 | 0.740510E+10 | 0.343902E+10 | 0.204680E+10 | 0.139222E+10 | 0.00 | 0.00 |
August | 0.123331E+11 | 0.667072E+10 | 0.273987E+10 | 0.154325E+10 | 0.119662E+10 | 0.00 | 0.00 |
September | 0.748552E+10 | 0.551341E+10 | 0.192851E+10 | 0.997484E+09 | 0.931024E+09 | 0.00 | 0.00 |
October | 0.391226E+10 | 0.871257E+10 | 0.114915E+10 | 0.440861E+09 | 0.708293E+09 | 0.00 | 0.00 |
November | 0.130235E+10 | 0.241548E+11 | 0.666639E+09 | 0.207193E+09 | 0.459446E+09 | 0.00 | 0.00 |
December | 84732488.19 | 0.664217E+11 | 0.548160E+09 | 0.143161E+09 | 0.404998E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.920677E+11 | 0.291544E+12 | 0.230526E+11 | 0.124077E+11 | 0.106449E+11 | 0.00 | 0.00 |
Minimum of Months | 84732488.19 | 0.449697E+10 | 0.548160E+09 | 0.143161E+09 | 0.404998E+09 | 0.00 | 0.00 |
Maximum of Months | 0.187605E+11 | 0.713037E+11 | 0.343902E+10 | 0.204680E+10 | 0.140042E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.117775E+10 | -0.102006E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -157696060.3 | 59.00 | 0.00 | 0.00 |
February | 0.110044E+10 | -958361496.3 | 0.00 | 0.00 | 672.00 | 0.00 | -142083500.6 | 58.99 | 0.00 | 0.00 |
March | 0.127213E+10 | -0.111574E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156389315.3 | 58.99 | 0.00 | 0.00 |
April | 0.115447E+10 | -0.100533E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149145904.3 | 58.99 | 0.00 | 0.00 |
May | 0.113440E+10 | -993226782.0 | 0.00 | 0.00 | 744.00 | 0.00 | -141174163.5 | 58.99 | 0.00 | 0.00 |
June | 0.106164E+10 | -930605985.8 | 0.00 | 0.00 | 720.00 | 0.00 | -131036538.7 | 59.00 | 0.00 | 0.00 |
July | 0.984161E+09 | -852041342.8 | 0.00 | 0.00 | 744.00 | 0.00 | -132119566.0 | 58.99 | 0.00 | 0.00 |
August | 0.102216E+10 | -888790936.5 | 0.00 | 0.00 | 744.00 | 0.00 | -133367633.4 | 58.99 | 0.00 | 0.00 |
September | 0.964218E+09 | -830473903.2 | 0.00 | 0.00 | 720.00 | 0.00 | -133743905.8 | 58.99 | 0.00 | 0.00 |
October | 0.101625E+10 | -864899219.2 | 0.00 | 0.00 | 744.00 | 0.00 | -151346962.3 | 58.99 | 0.00 | 0.00 |
November | 0.103121E+10 | -879473980.9 | 0.00 | 0.00 | 720.00 | 0.00 | -151736768.9 | 58.99 | 0.00 | 0.00 |
December | 0.112911E+10 | -971536904.8 | 0.00 | 0.00 | 744.00 | 0.00 | -157573468.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.130479E+11 | -0.113105E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.173741E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.964218E+09 | -0.111574E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -157696060.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.127213E+10 | -830473903.2 | 0.00 | 0.00 | 744.00 | 0.00 | -131036538.7 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 243.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 265.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 254.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 437.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 401.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 409.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 352.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 299.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 255.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 226.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3785.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 226.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 437.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.205880E+11 | 31022.11 | 01-JAN-00:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155026E+11 | 31022.11 | 01-FEB-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128754E+11 | 31022.11 | 01-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.590317E+10 | 31022.11 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.809387E+09 | 31022.11 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16608581.63 | 10336.13 | 01-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 175299.17 | 153.88 | 18-AUG-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.322938E+09 | 31022.11 | 23-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.292156E+10 | 31022.11 | 03-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.867191E+10 | 31022.11 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184590E+11 | 31022.11 | 01-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.860707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.205880E+11 | 31022.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.869623E+11 | 110575.50 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.613378E+11 | 110575.50 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.428649E+11 | 110575.50 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159672E+11 | 110575.50 | 01-APR-18:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.459038E+09 | 89683.99 | 01-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.729422E+10 | 110575.50 | 31-OCT-18:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.344293E+11 | 110575.50 | 04-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.798486E+11 | 110575.50 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.329163E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.869623E+11 | 110575.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.324348E+12 | 260360.66 | 04-JAN-01:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.230994E+12 | 260360.66 | 12-FEB-22:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147319E+12 | 191060.10 | 15-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.370306E+11 | 108876.32 | 04-APR-18:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.406240E+09 | 26466.64 | 01-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.974165E+10 | 58626.01 | 31-OCT-20:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118292E+12 | 158572.09 | 25-NOV-01:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.303633E+12 | 260360.66 | 18-DEC-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117176E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.324348E+12 | 260360.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 22716034.87 | 22716034.87 | 1630.94 | 13-APR-15:00 | 1630.94 | 0.00 |
May | 0.00 | 0.00 | 0.240534E+10 | 0.218655E+10 | 20481.31 | 25-MAY-18:23 | 18283.21 | 0.00 |
June | 0.00 | 0.00 | 0.645341E+10 | 0.526693E+10 | 23537.15 | 25-JUN-23:02 | 14841.06 | 0.00 |
July | 0.00 | 0.00 | 0.952589E+10 | 0.767578E+10 | 24290.30 | 23-JUL-23:01 | 15522.02 | 0.00 |
August | 0.00 | 0.00 | 0.826783E+10 | 0.665065E+10 | 22453.20 | 27-AUG-23:02 | 16616.28 | 0.00 |
September | 0.00 | 0.00 | 0.233538E+10 | 0.210623E+10 | 21274.02 | 01-SEP-17:43 | 18586.78 | 0.00 |
October | 0.00 | 0.00 | 0.112515E+09 | 0.111361E+09 | 3392.50 | 21-OCT-15:00 | 3392.50 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.291231E+11 | 0.240202E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.952589E+10 | 0.767578E+10 | 24290.30 | 18586.78 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.222691E+10 | 0.191369E+10 | 26367.28 | 25-MAY-15:00 | 21723.63 | 0.00 |
June | 0.00 | 0.00 | 0.967154E+10 | 0.742795E+10 | 74131.63 | 30-JUN-17:06 | 56693.22 | 0.00 |
July | 0.00 | 0.00 | 0.170382E+11 | 0.129317E+11 | 79726.52 | 23-JUL-10:53 | 52170.07 | 0.00 |
August | 0.00 | 0.00 | 0.907822E+10 | 0.687155E+10 | 61328.79 | 08-AUG-17:08 | 41871.73 | 0.00 |
September | 0.00 | 0.00 | 0.854147E+09 | 0.711567E+09 | 40767.95 | 01-SEP-17:10 | 35009.20 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.388690E+11 | 0.298564E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.170382E+11 | 0.129317E+11 | 79726.52 | 56693.22 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.164258E+10 | 0.08 | 616.72 | 01-JAN-00:01 | 0.08 |
February | 0.141686E+10 | 0.08 | 616.72 | 01-FEB-00:01 | 0.08 |
March | 0.140509E+10 | 0.07 | 616.72 | 01-MAR-00:02 | 0.08 |
April | 0.637587E+09 | 0.03 | 616.72 | 01-APR-00:10 | 0.08 |
May | 18316686.49 | 0.00 | 616.72 | 01-MAY-00:03 | 0.08 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.377873E+09 | 0.02 | 616.72 | 09-OCT-02:33 | 0.08 |
November | 0.134113E+10 | 0.07 | 616.72 | 01-NOV-00:10 | 0.08 |
December | 0.165183E+10 | 0.08 | 616.72 | 01-DEC-00:02 | 0.08 |
Annual Sum or Average | 0.849127E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.165183E+10 | 0.08 | 616.72 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.162398E+10 | 0.83 | 1278.78 | 02-JAN-10:50 | 0.98 |
February | 0.142919E+10 | 0.81 | 1278.78 | 21-FEB-11:00 | 0.98 |
March | 0.154953E+10 | 0.73 | 1278.78 | 01-MAR-10:30 | 0.98 |
April | 0.135652E+10 | 0.56 | 1278.78 | 01-APR-11:00 | 0.98 |
May | 0.134504E+10 | 0.42 | 1278.78 | 01-MAY-07:30 | 0.98 |
June | 0.138223E+10 | 0.48 | 1278.78 | 14-JUN-09:40 | 0.97 |
July | 0.139788E+10 | 0.55 | 1278.78 | 01-JUL-16:30 | 0.97 |
August | 0.146911E+10 | 0.54 | 1278.78 | 01-AUG-09:40 | 0.97 |
September | 0.128234E+10 | 0.40 | 1278.78 | 27-SEP-06:50 | 0.97 |
October | 0.129527E+10 | 0.40 | 1278.78 | 16-OCT-07:30 | 0.98 |
November | 0.135021E+10 | 0.65 | 1278.78 | 01-NOV-07:40 | 0.97 |
December | 0.159826E+10 | 0.83 | 1278.78 | 01-DEC-15:50 | 0.98 |
Annual Sum or Average | 0.170796E+11 | 0.60 | |||
Minimum of Months | 0.128234E+10 | 0.40 | 1278.78 | 0.97 | |
Maximum of Months | 0.162398E+10 | 0.83 | 1278.78 | 0.98 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.517656E+10 | 0.84 | 3351.65 | 02-JAN-07:20 | 0.94 |
February | 0.444246E+10 | 0.84 | 3351.65 | 01-FEB-08:00 | 0.94 |
March | 0.461479E+10 | 0.82 | 3351.65 | 01-MAR-07:40 | 0.94 |
April | 0.378475E+10 | 0.66 | 3351.65 | 26-APR-13:50 | 0.94 |
May | 0.346895E+10 | 0.38 | 3351.65 | 10-MAY-06:05 | 0.94 |
June | 0.348539E+10 | 0.39 | 3351.65 | 05-JUN-13:30 | 0.93 |
July | 0.340109E+10 | 0.39 | 3351.65 | 01-JUL-08:23 | 0.93 |
August | 0.359994E+10 | 0.38 | 3351.65 | 02-AUG-12:50 | 0.93 |
September | 0.331946E+10 | 0.36 | 3351.65 | 01-SEP-10:50 | 0.92 |
October | 0.355036E+10 | 0.56 | 3351.65 | 05-OCT-07:00 | 0.94 |
November | 0.411016E+10 | 0.81 | 3351.65 | 02-NOV-17:00 | 0.94 |
December | 0.508955E+10 | 0.84 | 3351.65 | 01-DEC-08:20 | 0.94 |
Annual Sum or Average | 0.480435E+11 | 0.60 | |||
Minimum of Months | 0.331946E+10 | 0.36 | 3351.65 | 0.92 | |
Maximum of Months | 0.517656E+10 | 0.84 | 3351.65 | 0.94 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.162398E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.142919E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.154953E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.136278E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.199648E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.311227E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.391441E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.364137E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.190601E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.132598E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.135021E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.159826E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.248105E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.132598E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.391441E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.517656E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.444246E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.461479E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.378475E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.412430E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.628168E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.823293E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.615862E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.356024E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.355036E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.411016E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.508955E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.591264E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.355036E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.823293E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.162398E+10 | 0.00 | 0.205880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142919E+10 | 0.00 | 0.155026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154953E+10 | 0.00 | 0.128754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135652E+10 | 22716034.87 | 0.590317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134504E+10 | 0.240534E+10 | 0.809387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138223E+10 | 0.645341E+10 | 16608581.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139788E+10 | 0.952589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146911E+10 | 0.826783E+10 | 175299.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128234E+10 | 0.233538E+10 | 0.322938E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129527E+10 | 0.112515E+09 | 0.292156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135021E+10 | 0.00 | 0.867191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159826E+10 | 0.00 | 0.184590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170796E+11 | 0.291231E+11 | 0.860707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.162398E+10 | 0.952589E+10 | 0.205880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.517656E+10 | 0.00 | 0.869623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.444246E+10 | 0.00 | 0.613378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.461479E+10 | 0.00 | 0.428649E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.378475E+10 | 0.00 | 0.159672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.346895E+10 | 0.222691E+10 | 0.459038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.348539E+10 | 0.967154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.340109E+10 | 0.170382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.359994E+10 | 0.907822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.331946E+10 | 0.854147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.355036E+10 | 0.00 | 0.729422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.411016E+10 | 0.00 | 0.344293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.508955E+10 | 0.00 | 0.798486E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.480435E+11 | 0.388690E+11 | 0.329163E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.331946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.517656E+10 | 0.170382E+11 | 0.869623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.162398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135652E+10 | 0.00 | 0.00 | 0.00 | 6257729.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134504E+10 | 0.00 | 0.00 | 0.00 | 0.651440E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138223E+10 | 0.00 | 0.00 | 0.00 | 0.173004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139788E+10 | 0.00 | 0.00 | 0.00 | 0.251654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146911E+10 | 0.00 | 0.00 | 0.00 | 0.217226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128234E+10 | 0.00 | 0.00 | 0.00 | 0.623669E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129527E+10 | 0.00 | 0.00 | 0.00 | 30708603.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170796E+11 | 0.00 | 0.00 | 0.00 | 0.773092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.162398E+10 | 0.00 | 0.00 | 0.00 | 0.251654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.517656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.444246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.461479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.378475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.346895E+10 | 0.00 | 0.00 | 0.00 | 0.655347E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.348539E+10 | 0.00 | 0.00 | 0.00 | 0.279629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.340109E+10 | 0.00 | 0.00 | 0.00 | 0.483184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.359994E+10 | 0.00 | 0.00 | 0.00 | 0.255868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.331946E+10 | 0.00 | 0.00 | 0.00 | 0.240780E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.355036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.411016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.508955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.480435E+11 | 0.00 | 0.00 | 0.00 | 0.110829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.331946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.517656E+10 | 0.00 | 0.00 | 0.00 | 0.483184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572873E+10 | 0.00 | 0.00 | 0.17 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428515E+10 | 0.00 | 0.00 | 0.16 |
March | 7257523.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390752E+10 | 0.00 | 0.00 | 0.16 |
April | 0.298517E+09 | 0.00 | 0.00 | 14578.10 | 0.00 | 0.187515E+10 | 16101578.97 | 0.00 | 0.15 |
May | 0.480821E+09 | 51351716.13 | 0.00 | 1772214.75 | 0.00 | 0.269600E+09 | 0.358199E+09 | 0.00 | 0.15 |
June | 0.119367E+09 | 0.391442E+09 | 0.00 | 3929526.46 | 0.00 | 15451547.92 | 0.420117E+09 | 0.00 | 0.16 |
July | 32974137.61 | 0.598168E+09 | 0.00 | 5762380.83 | 118720.59 | 0.00 | 0.226800E+09 | 0.00 | 0.15 |
August | 96484267.31 | 0.322630E+09 | 0.00 | 5791228.32 | 5112.35 | 2281501.70 | 0.355753E+09 | 0.00 | 0.16 |
September | 0.507845E+09 | 11738993.22 | 0.00 | 3001788.34 | 0.00 | 0.139381E+09 | 0.651239E+09 | 0.00 | 0.14 |
October | 0.664772E+09 | 0.00 | 0.00 | 128255.40 | 0.00 | 0.123535E+10 | 78902469.11 | 0.00 | 0.14 |
November | 48928683.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277841E+10 | 0.00 | 6191.21 | 0.15 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524896E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.225697E+10 | 0.137533E+10 | 0.00 | 20399972.21 | 123832.94 | 0.254860E+11 | 0.210711E+10 | 6191.21 | 0.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.664772E+09 | 0.598168E+09 | 0.00 | 5791228.32 | 118720.59 | 0.572873E+10 | 0.651239E+09 | 6191.21 | 0.17 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.529603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140035E+11 | 0.00 | 0.00 | 0.17 |
February | 0.138659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.924897E+10 | 0.00 | 0.00 | 0.17 |
March | 0.336004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.651965E+10 | 0.00 | 0.00 | 0.19 |
April | 0.428636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120394E+10 | 0.00 | 0.00 | 0.18 |
May | 0.333431E+10 | 43223694.39 | 0.00 | 2228721.13 | 0.00 | 0.00 | 0.907271E+09 | 0.00 | 0.22 |
June | 0.167470E+10 | 0.838085E+09 | 0.00 | 4776987.24 | 0.00 | 0.00 | 0.216009E+10 | 0.00 | 0.26 |
July | 0.431918E+09 | 0.113488E+10 | 0.00 | 8789847.48 | 0.00 | 0.00 | 0.305455E+10 | 0.00 | 0.28 |
August | 0.120334E+10 | 0.488313E+09 | 0.00 | 7719681.33 | 0.00 | 0.00 | 0.436820E+10 | 0.00 | 0.33 |
September | 0.421221E+10 | 7549139.65 | 0.00 | 1370433.13 | 0.00 | 0.00 | 0.110599E+10 | 0.00 | 0.21 |
October | 0.492483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408663E+09 | 0.00 | 0.00 | 0.17 |
November | 0.311188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391913E+10 | 0.00 | 0.00 | 0.17 |
December | 0.502879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126933E+11 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.289587E+11 | 0.251205E+10 | 0.00 | 24885670.31 | 0.00 | 0.479972E+11 | 0.115961E+11 | 0.00 | 0.21 |
Minimum of Months | 0.431918E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.492483E+10 | 0.113488E+10 | 0.00 | 8789847.48 | 0.00 | 0.140035E+11 | 0.436820E+10 | 0.00 | 0.33 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.309068E+12 | 0.222760E+12 | 0.00 | 0.226010E+11 | 0.129057E+12 |
February | 0.469864E+12 | 0.180742E+12 | 0.00 | 0.168509E+11 | 0.931419E+11 |
March | 0.678035E+12 | 0.124455E+12 | 0.00 | 0.159302E+11 | 0.634653E+11 |
April | 0.853699E+12 | 0.770365E+11 | 0.00 | 0.954747E+10 | 0.198475E+11 |
May | 0.102665E+13 | 0.419697E+11 | 0.00 | 0.717158E+10 | 0.664293E+10 |
June | 0.105439E+13 | 0.368914E+11 | 0.00 | 0.429738E+10 | 0.206599E+11 |
July | 0.109483E+13 | 0.449632E+11 | 0.00 | 0.278978E+10 | 0.339124E+11 |
August | 0.915515E+12 | 0.476845E+11 | 0.00 | 0.623149E+10 | 0.220771E+11 |
September | 0.661209E+12 | 0.578374E+11 | 0.00 | 0.873672E+10 | 0.421223E+10 |
October | 0.351011E+12 | 0.547317E+11 | 0.00 | 0.100569E+11 | 0.761320E+10 |
November | 0.171707E+12 | 0.115588E+12 | 0.00 | 0.120670E+11 | 0.505597E+11 |
December | 0.205119E+12 | 0.219470E+12 | 0.00 | 0.206294E+11 | 0.120566E+12 |
Annual Sum or Average | 0.779110E+13 | 0.122413E+13 | 0.00 | 0.136910E+12 | 0.571755E+12 |
Minimum of Months | 0.171707E+12 | 0.368914E+11 | 0.00 | 0.278978E+10 | 0.421223E+10 |
Maximum of Months | 0.109483E+13 | 0.222760E+12 | 0.00 | 0.226010E+11 | 0.129057E+12 |