Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2023-10-16 10:41:43
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2226.95 | 460.58 | 460.58 |
Net Site Energy | 2226.95 | 460.58 | 460.58 |
Total Source Energy | 4549.81 | 940.99 | 940.99 |
Net Source Energy | 4549.81 | 940.99 | 940.99 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1201.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 27.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 134.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 74.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 27.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1025.35 | 1201.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1201.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 27.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 134.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 73.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 27.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1201.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 27.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 134.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 74.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 27.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 26.56 | 248.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 212.06 | 248.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 26.56 | 248.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 212.06 | 248.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1025.347 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1025.347 | 100.00 |
Total On-Site and Utility Electric Sources | 1025.347 | 100.00 |
Total Electricity End Uses | 1025.347 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 80.33 |
Time Setpoint Not Met During Occupied Cooling | 1.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2997.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.61 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.7186 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 15.0695 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 9.6875 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 11.2890 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 11.2890 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.7186 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 15.0695 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 9.6875 | 46.45 | 2.5587 | |
Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 11.2890 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 19-JUL-14:39 | 13-FEB-06:10 | - | - | - | - | - | - | - | - | - | - | 03-JUL-11:09 |
Heating | 0.00 | 428576.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 19597.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7322.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1765.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 84992.16 | 428576.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 428576.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 19597.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 5017.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1765.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1302.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 85.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1974.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 424.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 235.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 85.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3247.27 | 1302.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 269.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 17.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 48.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 671.60 | 269.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 269.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 17.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 48.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 671.60 | 269.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.20 |
ZONE2 FINE STORAGE DIRECT AIR | 3.34 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 5.78 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 5.78 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 230789.87 |
PSZ-OFFICE HEATING COIL | 31258.88 |
PSZ-FINE STORAGE HEATING COIL | 112244.80 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 230789.87 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.20 | 1.20 | 1.20 | 1.20 | 1.20 | 1.20 | 1.00 | 1.00 | 1.20 |
PSZ-FINE STORAGE | 3.34 | 3.34 | 3.34 | 3.34 | 3.34 | 3.34 | 1.00 | 1.00 | 3.34 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.20 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 3.34 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.20 | 1364.20 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.34 | 3653.47 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.20 | 1.20 | 1.20 | 1.20 | 22221.04 | 31258.88 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 3.34 | 3.34 | 3.34 | 3.34 | 78196.12 | 112244.80 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.20 | 0.598277 | 1.20 | 22221.04 | 11413.47 | 22221.04 | 0.800720 | 0.800720 |
PSZ-FINE STORAGE COOLING COIL | 3.34 | 1.67 | 3.34 | 78196.12 | 38871.16 | 78196.12 | 0.719800 | 0.719800 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.719 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.792 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 15.069 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15.069 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 9.688 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 12.246 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2539.013 | 10.719 | 199.158 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2539.013 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 20997.932 | 15.069 | 699.931 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20997.932 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 31046.942 | 9.688 | 449.956 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 31046.942 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5959 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.7823 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.8517 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.8517 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.678 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.179 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.075 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.075 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.53319041E-11 | 0.92099297E-16 | 0.18475806E-15 | 0.0000000 |
5 | 1 | -5.2159728 | 0.43155192E-04 | -0.26885250E-04 | 0.68722794E-11 |
6 | 0 | 5.8118483 | 0.59583229 | 0.59590233 | |
7 | 4 | 0.72249793E-12 | -0.16720573E-15 | 0.22015083E-14 | 0.12409536E-15 |
8 | 3 | -0.36459118E-03 | 0.53555631E-06 | -0.52695411E-04 | 0.13865996E-12 |
9 | 2 | 1.6915239 | 0.11971291E-01 | 1.1039557 | -0.69896550E-04 |
10 | 1 | -7.1930661 | 0.31446443 | -16.864389 | 0.32415671 |
11 | 0 | 6.0306730 | 0.20232993 | 16.289252 | |
12 | 4 | 0.70899133E-12 | 0.18867256E-15 | 0.20714601E-14 | 0.12737467E-15 |
13 | 3 | -0.35990531E-03 | 0.57946993E-06 | -0.51972542E-04 | 0.13607632E-12 |
14 | 2 | 1.6802142 | 0.13022526E-01 | 1.0953649 | -0.68997686E-04 |
15 | 1 | -7.2085490 | 0.34322300 | -16.809118 | 0.32197680 |
16 | 0 | 6.1062597 | 0.22131885 | 16.291370 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.20714601E-14 | 0.18867256E-15 | 0.70899133E-12 | 0.12737467E-15 |
85 | 3 | -0.51972542E-04 | 0.57946993E-06 | -0.35990531E-03 | 0.13607632E-12 |
86 | 2 | 1.0953649 | 0.13022526E-01 | 1.6802142 | -0.68997686E-04 |
87 | 1 | -16.809118 | 0.34322300 | -7.2085490 | 0.32197680 |
88 | 0 | 16.291370 | 0.22131885 | 6.1062597 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5016_SHGC_SOUTH_0.4 | 34 | 1 | VerySmooth | 2.852 | 2.852 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.5016_SHGC_NORTH_0.4 | 35 | 1 | VerySmooth | 2.852 | 2.852 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.5016_SHGC_EAST_0.4 | 36 | 1 | VerySmooth | 2.852 | 2.852 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.5016_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.852 | 2.852 | 1.000 | 0.401 | ||
5 | SKYLIGHT_U_1.02_SHGC_0.49 | 38 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.491 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.95586E-002 | 0.31435 | 0.46537 | 0.46537 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10843 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.95586E-002 | 0.31435 | 0.46537 | 0.46537 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10843 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.95586E-002 | 0.31435 | 0.46537 | 0.46537 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10843 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.95586E-002 | 0.31435 | 0.46537 | 0.46537 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10843 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.32532 | 0.12431 | 0.12431 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.052 | 0.5205 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.849 | 0.366 | 0.255 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 0.153 | 6.473E-004 | 9.992E-004 | 0.546 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.780 | 5.598E-004 | 3.565E-004 | 0.951 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 3.433 | 1.071E-003 | 6.996E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11813.47635 | 14176.17162 | 0.99713 | 1.19655 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 29.24600 | 1.33651E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 15347.17229 | 18416.60675 | 0.44213 | 0.53056 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -16.30000 | 9.24091E-004 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 42271.14794 | 50725.37752 | 2.78167 | 3.33801 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 64102.13432 | 76922.56119 | 1.55423 | 1.86508 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -16.30000 | 9.24091E-004 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 30.30000 | 1.33670E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 192324.89194 | 230789.87033 | 4.81948 | 5.78337 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 17441.89 | 1.19655 | 1.19655 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 16368.48 | 0.53056 | 0.53056 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 59668.04 | 3.33801 | 3.33801 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 69756.04 | 1.86508 | 1.86508 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.19655 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.33801 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.78337 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 5.78337 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 230789.86854 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 230789.87033 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.19655 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.19655 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.19655 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.19655 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.19655 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.19655 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.33801 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.33801 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.33801 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.33801 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.33801 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.33801 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.19655 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.33801 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.19655 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.19655 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1364.20401 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.19655 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.19655 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.19655 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.19655 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.19655 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.59828 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.19655 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22221.04000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 11413.46604 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 22221.04000 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80072 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80072 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22221.04000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31258.88221 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 31258.88221 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.33801 |
47 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.33801 |
49 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3653.46888 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.33801 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.33801 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.33801 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.33801 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.33801 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.66900 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.33801 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 78196.12000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 38871.16319 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 78196.12000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71980 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71980 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 78196.12000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 112244.80291 |
64 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
66 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 112244.80291 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 21292.2 | 10.89 | 10.26 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 75602.3 | 10.46 | 9.86 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.3146533595 | 0.2843365137 | Pass | Pass | 1.7539026712 | 5.8352885875 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.6749943254 | 0.6315124811 | Pass | Pass | 0.9339454772 | 1.4011432826 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 4.9596887204E-005 | 8.1410182636E-005 | Pass | Pass | 3.1440440475E-002 | 2.3235123886E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8335.02 | 1128.52 | 0.00 | 101.58 | 413.52 | 9978.68 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.755 | 0.852 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.755 | 0.852 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.755 | 0.852 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.551 | 0.596 | 3204.84 | 3170.23 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.707 | 0.852 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.707 | 0.852 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.5016_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.852 | 0.401 | 0.402 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.5016_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.852 | 0.401 | 0.402 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.5016_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.852 | 0.401 | 0.402 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.5016_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.852 | 0.401 | 0.402 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.27 | 4.803 | 0.500 | 0.501 | |||||||||||||||||
North Total or Average | 6.51 | 2.852 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 45.76 | 5.080 | 0.514 | 0.515 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.7186 | 236.88 | 2539.01 | LightsWired | LTG_SCH_OFFICE | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.86 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 15.0695 | 1393.41 | 20997.93 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 239.15 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 9.6875 | 3204.84 | 31046.94 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 353.60 |
Interior Lighting Total | 11.2890 | 4835.13 | 54583.89 | 623.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 8532.22 | AstronomicalClock | - | 83.67 | 83.67 | 134.00 | |
Exterior Lighting Total | 8532.22 | 134.00 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22221.04 | 17792.83 | 4428.21 | 0.80 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 78196.12 | 56285.57 | 21910.55 | 0.72 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 21292.2 | 10.89 | 10.26 | ||||
PSZ-FINE STORAGE COOLING COIL | 75602.3 | 10.46 | 9.86 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 230789.87 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 31258.88 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 112244.80 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 5.78 | 537.34 | 92.91 | 1.00 | 3.11 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.20 | 1364.20 | 1140.11 | 1.00 | 1.32 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 3.34 | 3653.47 | 1094.51 | 1.00 | 1.23 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.05 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11813.48 | 14176.17 | 59.85 | 0.997 | 1.197 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 23.90 | 23.90 | 0.00870 | 29.25 | 0.01337 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 42271.15 | 50725.38 | 36.40 | 2.782 | 3.338 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 26.70 | 26.69 | 0.00930 | 30.30 | 0.01337 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 0.00 | 31.32 | 0.01343 | 30.30 | 0.01337 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 15347.17 | 18416.61 | 77.75 | 0.442 | 0.531 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.09 | 0.00694 | -16.30 | 0.00092 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 64102.13 | 76922.56 | 55.20 | 1.554 | 1.865 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.55 | 0.00567 | -16.30 | 0.00092 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 192324.89 | 230789.87 | 72.01 | 4.819 | 5.783 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 9.99 | 0.00508 | -16.30 | 0.00092 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.20 | 1.20 | 0.53 | 0.53 | 1.1966 | 1.1966 | 1.1966 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.34 | 3.34 | 1.87 | 1.87 | 3.3380 | 3.3380 | 3.3380 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 230789.869 | 230789.869 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 230789.87 | 230789.87 | 5.783371 | 9.99 | 6.91 | 0.00507837 | 43.33 | 21.85 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 9.99 | 0.00507837 | 65.1663 | 230789.87 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 22221.040 | 17792.831 | 1.196550 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 22221.04 | 18779.39 | 1.196550 | 25.32 | 17.09 | 0.00910013 | 12.00 | 11.04 | 0.00800000 | 29.37 | 0.01336531 | 21.56 | 8.5483 | 23.90 | 0.00870117 | 45.9313 | 11805.65 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 31258.882 | 31258.882 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 31258.88 | 31258.88 | 1.196555 | 17.85 | 11.88 | 0.00642804 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 8.5483 | 21.09 | 0.00694251 | 43.5738 | 15347.17 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 78196.120 | 56285.567 | 3.338010 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 78196.12 | 62215.58 | 3.338010 | 28.06 | 18.57 | 0.00982080 | 12.00 | 11.04 | 0.00800000 | 30.30 | 0.01336696 | 21.83 | 12.7235 | 26.69 | 0.00930383 | 41.5442 | 42271.15 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 112244.803 | 112244.803 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 112244.80 | 112244.80 | 3.338009 | 11.49 | 7.61 | 0.00506459 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 12.7235 | 15.55 | 0.00566821 | 50.4973 | 64102.13 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 230789.869 | 230789.869 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 5.783371 | 6.78924561 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 230789.87 | 230789.87 | 1.0000 | 6.78924561 | 5.783371 | 9.99 | 6.91 | 0.00507837 | 22837.1 | 43.33 | 21.85 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 230789.87 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 9.99 | 0.00507837 | 9.99 | 0.00507837 | 65.1663 | 230789.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22221.040 | 17792.831 | 1.196550 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.7567 | 1004.8586 | 1.1739 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.196555 | 1.40466602 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | Sensible | 22221.04 | 18779.39 | 1.0000 | 1.40466033 | 1.196550 | 25.32 | 17.09 | 0.00910013 | 48625.4 | 12.00 | 11.04 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22221.04 | 29.37 | 0.01336531 | 21.56 | 0.10228463 | 8.5483 | 23.90 | 0.00870117 | 23.90 | 0.00870117 | 45.9313 | 11805.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31258.882 | 31258.882 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.196555 | 1.40466602 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 31258.88 | 31258.88 | 1.0000 | 1.40466602 | 1.196555 | 17.85 | 11.88 | 0.00642804 | 34229.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31258.88 | -16.30 | 0.00092409 | -16.30 | 0.10228463 | 8.5483 | 21.05 | 0.00694251 | 21.09 | 0.00694251 | 43.5738 | 15347.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 78196.120 | 56285.567 | 3.338010 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.0964 | 1004.8586 | 1.1739 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.338009 | 3.91857293 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 78196.12 | 62215.58 | 1.0000 | 3.91857444 | 3.338010 | 28.06 | 18.57 | 0.00982080 | 53274.1 | 12.00 | 11.04 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 78196.12 | 30.30 | 0.01336696 | 21.83 | 0.42471127 | 12.7235 | 26.69 | 0.00930383 | 26.69 | 0.00930383 | 41.5442 | 42271.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 112244.803 | 112244.803 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.338009 | 3.91857293 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 112244.80 | 112244.80 | 1.0000 | 3.91857293 | 3.338009 | 11.49 | 7.61 | 0.00506459 | 24324.3 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 112244.80 | -16.30 | 0.00092409 | -16.30 | 0.42471127 | 12.7235 | 15.55 | 0.00566821 | 15.55 | 0.00566821 | 50.4973 | 64102.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 3.34 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2631.67 | 2613.33 | 1834.67 |
ZONE2 FINE STORAGE | 3125.83 | 3076.67 | 2638.33 |
ZONE3 BULK STORAGE | 3233.50 | 3307.33 | 2965.50 |
Facility | 3430.50 | 3378.33 | 2997.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 280.17 | 67.67 | 68.17 | 1.83 |
ZONE2 FINE STORAGE | 527.00 | 17.50 | 26.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 740.83 | 78.50 | 80.33 | 1.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.345 | 0.479 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.523 | 0.588 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.254 | 0.000 | 0.164 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.50 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.36 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.28 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1330243.77 | 0.00 | 1330243.77 | 3401561.05 | 4731804.82 | 3225648.14 | 5391.00 | 3369.00 | 0.00 | 1359.58 |
ZONE2 FINE STORAGE | 5540741.84 | 0.00 | 5540741.84 | 16138891.05 | 21679632.89 | 13393694.68 | 5721.67 | 2756.00 | 282.33 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 34178996.95 | 34178996.95 | 65484949.04 | 99663945.99 | 30805497.77 | 7017.94 | 127.08 | 1614.97 | 5048.67 |
Total Facility | 6870985.62 | 34178996.95 | 41049982.57 | 85025401.14 | 0.13E+09 | 47424840.58 | 7910.66 | 3433.60 | 1879.62 | 5058.25 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.0955 | 0.0000 | 0.0955 | 0.1326 | 0.2282 | 0.1023 | 278.09 | 3357.91 | 0.00 |
ZONE2 FINE STORAGE | 0.4233 | 0.0000 | 0.4233 | 0.4796 | 0.9029 | 0.4247 | 597.67 | 2756.00 | 282.33 |
ZONE3 BULK STORAGE | 0.0000 | 1.5680 | 1.5680 | 2.4978 | 4.0657 | 0.9768 | 2710.32 | 64.25 | 861.43 |
Total Facility | 0.5188 | 1.5680 | 2.0868 | 3.1100 | 5.1968 | 1.5038 | 2786.66 | 3359.84 | 1126.07 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 1833209.80 | 0.00 | 1833209.80 | 3225648.14 | 5372.43 | 1.88 | 3385.69 | 1324.19 |
PSZ-FINE STORAGE | 7635699.89 | 0.00 | 7635699.89 | 13393694.68 | 5719.50 | 0.17 | 3040.33 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1317 | 0.0000 | 0.1317 | 0.1023 | 273.68 | 0.46 | 3361.86 |
PSZ-FINE STORAGE | 0.5833 | 0.0000 | 0.5833 | 0.4247 | 595.50 | 0.17 | 3040.33 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 4810.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2755.50 | 288.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1374 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.5854 | 1.7647 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 383 |
Defaulted Fields | 319 |
Fields with Defaults | 1020 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1025.35 | 6718.26 | 12-MAR-08:50 | 84992.16 | 19-JUL-14:40 |
Electricity:Building | 763.73 | 6235.26 | 01-JAN-00:10 | 58611.10 | 12-JUN-14:00 |
Electricity:Zone:ZONE1 OFFICE | 62.81 | 1030.77 | 01-JAN-00:10 | 3867.54 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 762.90 | 6235.26 | 01-JAN-00:10 | 56305.80 | 02-JAN-09:10 |
InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 461.77 | 3104.69 | 01-JAN-00:10 | 36895.31 | 12-JUN-14:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 74.34 | 0.00 | 11-JAN-18:40 | 7322.97 | 12-JUN-14:00 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.83 | 0.00 | 01-JAN-00:10 | 2305.29 | 14-JUL-14:10 |
Ventilation (simple):Fans:Electricity | 0.83 | 0.00 | 01-JAN-00:10 | 2305.29 | 14-JUL-14:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.83 | 0.00 | 01-JAN-00:10 | 2305.29 | 14-JUL-14:10 |
ElectricityPurchased:Facility | 1025.35 | 6718.26 | 12-MAR-08:50 | 84992.16 | 19-JUL-14:40 |
ElectricityPurchased:Plant | 1025.35 | 6718.26 | 12-MAR-08:50 | 84992.16 | 19-JUL-14:40 |
Cogeneration:ElectricityPurchased | 1025.35 | 6718.26 | 12-MAR-08:50 | 84992.16 | 19-JUL-14:40 |
General:Cogeneration:ElectricityPurchased | 1025.35 | 6718.26 | 12-MAR-08:50 | 84992.16 | 19-JUL-14:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1025.35 | 6718.26 | 12-MAR-08:50 | 84992.16 | 19-JUL-14:40 |
ElectricityNet:Plant | 1025.35 | 6718.26 | 12-MAR-08:50 | 84992.16 | 19-JUL-14:40 |
Cogeneration:ElectricityNet | 1025.35 | 6718.26 | 12-MAR-08:50 | 84992.16 | 19-JUL-14:40 |
General:Cogeneration:ElectricityNet | 1025.35 | 6718.26 | 12-MAR-08:50 | 84992.16 | 19-JUL-14:40 |
Electricity:HVAC | 100.58 | 0.00 | 11-JAN-18:40 | 25412.63 | 19-JUL-15:10 |
General:Fans:Electricity | 73.51 | 0.00 | 11-JAN-18:40 | 5555.01 | 12-JAN-14:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 27.07 | 0.00 | 01-JAN-00:10 | 20394.96 | 19-JUL-15:10 |
General:Cooling:Electricity | 27.07 | 0.00 | 01-JAN-00:10 | 20394.96 | 19-JUL-15:10 |
ExteriorLights:Electricity | 134.00 | 0.00 | 01-JAN-08:00 | 8532.22 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 134.00 | 0.00 | 01-JAN-08:00 | 8532.22 | 01-JAN-00:10 |
Electricity:Plant | 27.04 | 483.00 | 02-JAN-06:40 | 2761.08 | 13-FEB-12:50 |
WaterSystems:Electricity | 27.04 | 483.00 | 02-JAN-06:40 | 2761.08 | 13-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 27.04 | 483.00 | 02-JAN-06:40 | 2761.08 | 13-FEB-12:50 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1201.60 | 0.00 | 11-JAN-18:40 | 428576.00 | 13-FEB-06:10 |
NaturalGas:HVAC | 1201.60 | 0.00 | 11-JAN-18:40 | 428576.00 | 13-FEB-06:10 |
Heating:NaturalGas | 1201.60 | 0.00 | 11-JAN-18:40 | 428576.00 | 13-FEB-06:10 |
General:Heating:NaturalGas | 1201.60 | 0.00 | 11-JAN-18:40 | 428576.00 | 13-FEB-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 03-JUL-11:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 03-JUL-11:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 03-JUL-11:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 03-JUL-11:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 03-JUL-11:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 03-JUL-11:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 03-JUL-11:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 03-JUL-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1992.77 | 0.00 | 11-JAN-18:40 | 675066.35 | 13-FEB-06:10 |
EnergyTransfer:Building | 984.20 | 0.00 | 11-JAN-18:40 | 337259.43 | 13-FEB-06:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 81.60 | 0.00 | 01-JAN-00:40 | 29187.78 | 13-FEB-07:10 |
Heating:EnergyTransfer | 903.28 | 0.00 | 11-JAN-18:40 | 337259.43 | 13-FEB-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 55.63 | 0.00 | 01-JAN-00:40 | 29187.78 | 13-FEB-07:10 |
General:Heating:EnergyTransfer | 903.28 | 0.00 | 11-JAN-18:40 | 337259.43 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 55.63 | 0.00 | 01-JAN-00:40 | 29187.78 | 13-FEB-07:10 |
Cooling:EnergyTransfer | 80.92 | 0.00 | 01-JAN-00:10 | 44893.67 | 19-JUL-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 25.97 | 0.00 | 01-JAN-00:10 | 10138.04 | 19-JUL-15:10 |
General:Cooling:EnergyTransfer | 80.92 | 0.00 | 01-JAN-00:10 | 44893.67 | 19-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 25.97 | 0.00 | 01-JAN-00:10 | 10138.04 | 19-JUL-15:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 267.96 | 0.00 | 01-JAN-00:40 | 98518.70 | 13-FEB-06:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 213.00 | 0.00 | 01-JAN-00:40 | 98518.70 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 213.00 | 0.00 | 01-JAN-00:40 | 98518.70 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 54.96 | 0.00 | 01-JAN-00:10 | 34755.62 | 19-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 54.96 | 0.00 | 01-JAN-00:10 | 34755.62 | 19-JUL-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 634.65 | 0.00 | 06-JAN-10:40 | 231360.32 | 06-FEB-10:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 634.65 | 0.00 | 06-JAN-10:40 | 231360.32 | 06-FEB-10:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 634.65 | 0.00 | 06-JAN-10:40 | 231360.32 | 06-FEB-10:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1008.56 | 0.00 | 11-JAN-18:40 | 337806.92 | 13-FEB-06:10 |
HeatingCoils:EnergyTransfer | 911.86 | 0.00 | 11-JAN-18:40 | 337806.92 | 13-FEB-06:10 |
CoolingCoils:EnergyTransfer | 96.71 | 0.00 | 01-JAN-00:10 | 69632.74 | 19-JUL-15:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 55.631 | -25.967 | 0.000 | 0.000 | 10.012 | 30.864 | 31.946 | 10.026 | 0.000 | 0.580 | 0.000 | 0.000 | -10.338 | 0.000 | -50.726 | -52.029 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 212.997 | -54.955 | 0.000 | 0.000 | 25.028 | 239.148 | 0.000 | 0.000 | 0.000 | 0.681 | 0.001 | 0.000 | 0.000 | 0.000 | -215.026 | -207.874 |
ZONE3 BULK STORAGE | 634.647 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 63.875 | 353.598 | 107.344 | 110.932 | 0.000 | 6.638 | 0.000 | 0.000 | -120.022 | 0.000 | -842.098 | -314.913 |
Total Facility | 634.647 | 0.000 | 268.629 | -80.922 | 0.000 | 0.000 | 98.915 | 623.610 | 139.290 | 120.958 | 0.000 | 7.899 | 0.002 | 0.000 | -130.360 | 0.000 | -1107.850 | -574.815 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 20-AUG-23:01 | 0.00 | 0.00 | 0.00 | -20565.09 | 0.00 | 0.00 | 0.00 | 457.02 | 573.75 | 0.00 | 0.00 | 0.00 | 20247.21 | 0.00 | -326.96 | 0.00 | -385.93 | 0.00 |
ZONE2 FINE STORAGE | 18-JUL-17:06 | 0.00 | 0.00 | 0.00 | -62981.86 | 0.00 | 0.00 | 0.00 | 2099.79 | 0.00 | 0.00 | 0.00 | 666.31 | 60215.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 18-JUL-17:06 | 0.00 | 0.00 | 0.00 | -80226.66 | 0.00 | 0.00 | 0.00 | 5661.51 | 2623.78 | 24660.95 | 0.00 | 1095.28 | 49675.99 | 0.00 | 0.00 | 0.00 | -3490.85 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 13-FEB-06:31 | 0.00 | 0.00 | 32261.81 | 0.00 | 0.00 | 0.00 | 154.31 | 583.97 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -993.73 | 0.00 | -8122.29 | -24457.82 |
ZONE2 FINE STORAGE | 13-FEB-06:01 | 0.00 | 0.00 | 121819.34 | 0.00 | 0.00 | 0.00 | 402.15 | 2099.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -36741.05 | -87580.23 |
ZONE3 BULK STORAGE | 06-FEB-10:00 | 231362.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8317.41 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4011.72 | 0.00 | -212882.78 | -57374.96 |
Total Facility | 06-FEB-18:52 | 230238.85 | 0.00 | 141863.61 | 0.00 | 0.00 | 0.00 | 0.00 | 5661.51 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -16464.35 | 0.00 | -224169.27 | -139754.12 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1966 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.1966 | 0.0855 | 1.0000 | Not calculated | 0.1023 | 0.0855 | ||
PSZ-FINE STORAGE | 3.3380 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.3380 | 0.1272 | 1.0000 | Not calculated | 0.4247 | 0.1272 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1966 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.1966 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0855 | ||
PSZ-FINE STORAGE | 3.3380 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.3380 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1272 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1966 | 1.1966 | 1.1966 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.3380 | 3.3380 | 3.3380 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1966 | 1.1966 | 1.1966 | 1.1966 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.3380 | 3.3380 | 3.3380 | 3.3380 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1966 | 1.1966 | 1.1966 | No | 0.1023 | 0.1928 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.3380 | 3.3380 | 3.3380 | No | 0.4247 | 0.2277 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1966 | 1.1966 | 1.1966 | 1.1966 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.3380 | 3.3380 | 3.3380 | 3.3380 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 80.33 |
Number of hours cooling loads not met | 1.83 |
Number of hours not met | 82.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1201.60 | 428576.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 27.07 | 20394.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 623.61 | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 134.00 | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.83 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 73.51 | 5555.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 27.04 | 2761.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 1025.35 |
Natural Gas | 0.00 | 1201.60 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 2226.95 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 128.97 |
Space Heating | 0.00 |
Space Cooling | 5.60 |
Fans (All) | 15.37 |
Service Water Heating | 5.59 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 212.06 |
Subtotal | 212.06 |
Natural Gas [MJ/m2] | |
Space Heating | 248.51 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 248.51 |
Subtotal | 248.51 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 28.00 |
Space Heating | 53.96 |
Space Cooling | 1.22 |
Fans (All) | 3.34 |
Service Water Heating | 1.21 |
Receptacle Equipment | 6.25 |
Miscellaneous | 6.02 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 3430. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8609.33 | 150.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7921.50 | 838.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7561.67 | 1175.83 | 22.50 | 0.00 | 0.00 |
Min | 7561.67 | 150.67 | 0.00 | 0.00 | 0.00 |
Max | 8609.33 | 1175.83 | 22.50 | 0.00 | 0.00 |
Average | 8030.83 | 721.67 | 7.50 | 0.00 | 0.00 |
Sum | 24092.50 | 2165.00 | 22.50 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 68752.00 | 13967.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 154881.00 | 35287.33 | 1024.67 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 154881.00 | 35287.33 | 1024.67 | 0.00 | 0.00 |
Average | 85553.33 | 16418.11 | 341.56 | 0.00 | 0.00 |
Sum | 256660.00 | 49254.33 | 1024.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8480.00 | 280.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7398.33 | 1361.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7186.17 | 1573.83 | 0.00 | 0.00 | 0.00 |
Min | 7186.17 | 280.00 | 0.00 | 0.00 | 0.00 |
Max | 8480.00 | 1573.83 | 0.00 | 0.00 | 0.00 |
Average | 7688.17 | 1071.83 | 0.00 | 0.00 | 0.00 |
Sum | 23064.50 | 3215.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 32951.67 | 75.33 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 66810.00 | 15909.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 149416.00 | 41777.00 | 0.00 | 0.00 | 0.00 |
Min | 32951.67 | 75.33 | 0.00 | 0.00 | 0.00 |
Max | 149416.00 | 41777.00 | 0.00 | 0.00 | 0.00 |
Average | 83059.22 | 19253.78 | 0.00 | 0.00 | 0.00 |
Sum | 249177.67 | 57761.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:43
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -1.0 | -1.6 | 0.496868E+09 | 603.25 | 17-JAN-16:30 | 7.80 | 6.69 |
February | 161311.10 | 1075.41 | 18-FEB-07:05 | -1.7 | -1.9 | 0.456874E+09 | 603.25 | 14-FEB-16:40 | -1.7 | -1.9 |
March | 85210656.76 | 2996.28 | 15-MAR-15:10 | 25.50 | 16.19 | 0.551462E+09 | 769.01 | 15-MAR-15:20 | 25.40 | 16.14 |
April | 64440399.19 | 2065.63 | 22-APR-15:00 | 15.60 | 7.04 | 0.525771E+09 | 768.98 | 08-APR-15:09 | 15.60 | 7.04 |
May | 0.122431E+10 | 9515.26 | 27-MAY-17:15 | 20.03 | 11.03 | 0.627122E+09 | 769.02 | 13-MAY-15:20 | 20.03 | 11.03 |
June | 0.505400E+10 | 19490.13 | 30-JUN-18:23 | 22.75 | 12.12 | 0.656295E+09 | 769.07 | 12-JUN-15:00 | 22.75 | 12.12 |
July | 0.782616E+10 | 19693.68 | 04-JUL-23:01 | 20.60 | 17.40 | 0.634575E+09 | 770.08 | 25-JUL-07:10 | 17.35 | 14.76 |
August | 0.758032E+10 | 20565.54 | 20-AUG-23:01 | 18.12 | 14.61 | 0.684988E+09 | 769.07 | 18-AUG-15:00 | 18.12 | 14.61 |
September | 0.374575E+10 | 18151.99 | 21-SEP-17:43 | 23.68 | 16.55 | 0.627981E+09 | 769.03 | 09-SEP-14:30 | 23.68 | 16.55 |
October | 0.375602E+09 | 3427.35 | 11-OCT-16:00 | 21.70 | 14.52 | 0.556940E+09 | 776.27 | 21-OCT-12:39 | 19.23 | 11.98 |
November | 10724937.16 | 617.31 | 18-NOV-15:30 | 5.00 | 2.10 | 0.485526E+09 | 768.73 | 04-NOV-15:09 | 5.00 | 2.10 |
December | 480424.25 | 1601.80 | 16-DEC-07:05 | -0.8 | -1.5 | 0.496904E+09 | 603.25 | 16-DEC-08:09 | 0.60 | -0.5 |
Annual Sum or Average | 0.259672E+11 | 0.680131E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -1.7 | -1.9 | 0.456874E+09 | 603.25 | -1.7 | -1.9 | ||
Maximum of Months | 0.782616E+10 | 20565.54 | 25.50 | 17.40 | 0.684988E+09 | 776.27 | 25.40 | 16.55 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.285271E+09 | 5092.31 | 06-JAN-14:20 | -2.6 | -5.2 | 0.652670E+09 | 931.60 | 11-JAN-16:10 | 11.60 | 10.09 |
February | 0.465135E+09 | 6908.71 | 10-FEB-13:10 | -4.5 | -6.4 | 0.601751E+09 | 987.08 | 22-FEB-16:10 | 10.78 | 5.11 |
March | 0.128285E+10 | 5963.89 | 04-MAR-13:10 | -5.4 | -7.3 | 0.873559E+09 | 2177.75 | 15-MAR-14:30 | 25.85 | 16.15 |
April | 0.122294E+10 | 4369.75 | 10-APR-08:15 | 4.07 | 3.01 | 0.966477E+09 | 1897.02 | 08-APR-14:09 | 4.07 | 3.01 |
May | 0.119443E+10 | 10875.43 | 27-MAY-15:00 | 21.70 | 12.18 | 0.151067E+10 | 2246.80 | 10-MAY-15:39 | 21.70 | 12.18 |
June | 0.905341E+10 | 42939.55 | 27-JUN-17:08 | 26.52 | 22.66 | 0.185419E+10 | 2246.97 | 20-JUN-13:50 | 26.52 | 22.66 |
July | 0.180681E+11 | 62989.47 | 18-JUL-17:06 | 28.03 | 19.76 | 0.184698E+10 | 2246.83 | 06-JUL-12:39 | 28.03 | 19.76 |
August | 0.158051E+11 | 61294.40 | 06-AUG-14:43 | 28.03 | 19.11 | 0.198547E+10 | 2247.04 | 09-AUG-13:09 | 28.98 | 18.14 |
September | 0.476769E+10 | 21650.07 | 16-SEP-13:40 | 27.20 | 19.70 | 0.171450E+10 | 2246.96 | 22-SEP-13:00 | 23.90 | 15.30 |
October | 0.118497E+10 | 4726.27 | 17-OCT-08:20 | 0.53 | -1.0 | 0.110642E+10 | 2115.76 | 05-OCT-14:00 | 0.53 | -1.0 |
November | 0.116634E+10 | 4603.32 | 24-NOV-11:00 | 1.10 | -0.6 | 0.762469E+09 | 1497.16 | 04-NOV-15:09 | 1.10 | -0.6 |
December | 0.460905E+09 | 4086.41 | 16-DEC-10:00 | 1.10 | 0.02 | 0.662003E+09 | 1124.18 | 01-DEC-13:20 | 1.10 | 0.02 |
Annual Sum or Average | 0.549571E+11 | 0.145372E+11 | ||||||||
Minimum of Months | 0.285271E+09 | 4086.41 | -5.4 | -7.3 | 0.601751E+09 | 931.60 | 0.53 | -1.0 | ||
Maximum of Months | 0.180681E+11 | 62989.47 | 28.03 | 22.66 | 0.198547E+10 | 2247.04 | 28.98 | 22.66 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -1.0 | -1.6 | 0.652052E+09 | 1052.40 | 11-JAN-16:40 | 11.30 | 9.94 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -3.3 | -4.7 | 0.598338E+09 | 1093.54 | 22-FEB-16:00 | 11.70 | 5.56 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -4.9 | -6.9 | 0.987025E+09 | 3056.64 | 15-MAR-14:20 | 25.93 | 16.12 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 | 0.126832E+10 | 2675.86 | 08-APR-14:20 | 20.20 | 13.55 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.260896E+10 | 4648.26 | 27-MAY-15:09 | 21.70 | 12.15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.410394E+10 | 6768.21 | 27-JUN-13:09 | 30.03 | 23.62 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.492843E+10 | 7413.67 | 21-JUL-14:20 | 31.33 | 22.12 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.513545E+10 | 6928.28 | 10-AUG-14:30 | 30.30 | 20.01 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.357304E+10 | 5909.97 | 16-SEP-14:09 | 27.12 | 19.78 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.172282E+10 | 3529.12 | 05-OCT-14:00 | 18.90 | 12.68 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.883336E+09 | 2000.58 | 04-NOV-15:09 | 18.30 | 13.69 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.95 | 3.07 | 0.663956E+09 | 1369.41 | 01-DEC-11:39 | 14.27 | 12.08 |
Annual Sum or Average | 0.00 | 0.271257E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.598338E+09 | 1052.40 | 11.30 | 5.56 | ||
Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.513545E+10 | 7413.67 | 31.33 | 23.62 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133096E+11 | 31984.60 | 12-JAN-06:31 | -7.9 |
February | 0.128405E+11 | 32261.77 | 13-FEB-06:31 | -9.4 |
March | 0.758652E+10 | 30870.33 | 14-MAR-05:01 | 11.78 |
April | 0.345598E+10 | 30828.69 | 07-APR-05:01 | 10.60 |
May | 0.613185E+09 | 30304.54 | 02-MAY-05:01 | 7.30 |
June | 39286151.22 | 6604.25 | 14-JUN-06:05 | 7.67 |
July | 5565934.19 | 1063.47 | 29-JUL-06:05 | 20.68 |
August | 9191882.45 | 683.26 | 16-AUG-06:10 | 15.68 |
September | 70855297.42 | 28718.21 | 30-SEP-05:02 | 7.20 |
October | 0.147347E+10 | 30753.10 | 26-OCT-05:01 | 15.50 |
November | 0.434364E+10 | 31314.74 | 27-NOV-06:01 | 18.30 |
December | 0.118837E+11 | 31203.84 | 12-DEC-06:31 | -9.4 |
Annual Sum or Average | 0.556314E+11 | |||
Minimum of Months | 5565934.19 | 683.26 | -9.4 | |
Maximum of Months | 0.133096E+11 | 32261.77 | 20.68 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.525565E+11 | 121000.15 | 12-JAN-06:01 | -7.4 |
February | 0.548651E+11 | 121819.38 | 13-FEB-06:01 | -9.4 |
March | 0.262804E+11 | 115375.07 | 07-MAR-00:02 | -11.8 |
April | 0.867978E+10 | 115039.91 | 16-APR-05:02 | -2.4 |
May | 0.427909E+09 | 59776.75 | 01-MAY-05:08 | 1.70 |
June | 0.251612E+09 | 3588.67 | 03-JUN-07:00 | 11.70 |
July | 0.132616E+09 | 3616.96 | 08-JUL-06:25 | 18.85 |
August | 0.205023E+09 | 3508.80 | 24-AUG-07:00 | 15.00 |
September | 0.290162E+09 | 3805.24 | 28-SEP-07:00 | 12.20 |
October | 0.291583E+10 | 112192.37 | 30-OCT-05:11 | -0.2 |
November | 0.151317E+11 | 113078.96 | 28-NOV-22:42 | 2.12 |
December | 0.512615E+11 | 119740.86 | 27-DEC-06:01 | -11.1 |
Annual Sum or Average | 0.212998E+12 | |||
Minimum of Months | 0.132616E+09 | 3508.80 | -11.8 | |
Maximum of Months | 0.548651E+11 | 121819.38 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.181508E+12 | 226650.12 | 12-JAN-09:00 | -11.1 |
February | 0.187427E+12 | 231360.32 | 06-FEB-10:00 | -15.0 |
March | 0.671811E+11 | 123226.14 | 05-MAR-00:53 | -7.2 |
April | 0.909863E+10 | 81300.02 | 16-APR-06:51 | -3.9 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 38150840.31 | 13134.74 | 30-OCT-05:00 | 0.00 |
November | 0.183801E+11 | 50671.66 | 25-NOV-05:52 | -1.7 |
December | 0.171017E+12 | 191826.00 | 09-DEC-17:00 | -7.2 |
Annual Sum or Average | 0.634649E+12 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.187427E+12 | 231360.32 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.258145E+10 | 1955.04 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.235440E+10 | 1955.04 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.269003E+10 | 1955.04 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.254196E+10 | 1955.04 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.263574E+10 | 1955.04 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.259625E+10 | 1955.04 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.258145E+10 | 1955.04 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.269003E+10 | 1955.04 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.254196E+10 | 1955.04 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.258145E+10 | 1955.04 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.248766E+10 | 1955.04 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.258145E+10 | 1955.04 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.308638E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.235440E+10 | 1955.04 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.269003E+10 | 1955.04 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.198922E+11 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.182065E+11 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.210336E+11 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.197108E+11 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.204629E+11 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.202815E+11 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.198922E+11 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.210336E+11 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.197108E+11 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.198922E+11 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.191400E+11 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.198922E+11 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.239148E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.182065E+11 | 17848.24 | 0.00 | 0.00 | |
Maximum of Months | 0.210336E+11 | 17848.24 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.294120E+11 | 26389.90 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.269196E+11 | 26389.90 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.310997E+11 | 26389.90 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.291438E+11 | 26389.90 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.302559E+11 | 26389.90 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.299876E+11 | 26389.90 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.294120E+11 | 26389.90 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.310997E+11 | 26389.90 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.291438E+11 | 26389.90 | 01-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.294120E+11 | 26389.90 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.282999E+11 | 26389.90 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.294120E+11 | 26389.90 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.353598E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.269196E+11 | 26389.90 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.310997E+11 | 26389.90 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.852906E+10 |
February | 0.127628E+10 | 0.235440E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.883708E+10 |
March | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5139890.23 | 0.572077E+10 |
April | 0.138726E+10 | 0.254196E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396858E+10 |
May | 0.144276E+10 | 0.263574E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3254214.77 | 0.241885E+10 |
June | 0.144276E+10 | 0.259625E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104493E+09 | 0.156002E+10 |
July | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269323E+09 | 0.737617E+09 |
August | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183034E+09 | 0.100104E+10 |
September | 0.138726E+10 | 0.254196E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14646816.20 | 0.169282E+10 |
October | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7153.04 | 0.316713E+10 |
November | 0.133177E+10 | 0.248766E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76436.30 | 0.447481E+10 |
December | 0.138726E+10 | 0.258145E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.861815E+10 |
Annual Sum or Average | 0.168137E+11 | 0.308638E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579975E+09 | 0.507259E+11 |
Minimum of Months | 0.127628E+10 | 0.235440E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.737617E+09 |
Maximum of Months | 0.149825E+10 | 0.269003E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269323E+09 | 0.883708E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355820E+11 |
February | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383199E+11 |
March | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5865568.95 | 0.223580E+11 |
April | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154724E+11 |
May | 0.339505E+10 | 0.204629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3341686.50 | 0.101478E+11 |
June | 0.339505E+10 | 0.202815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92608079.18 | 0.859271E+10 |
July | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305605E+09 | 0.512460E+10 |
August | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242552E+09 | 0.609772E+10 |
September | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1804010.34 | 0.824649E+10 |
October | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5978344.41 | 0.115234E+11 |
November | 0.313390E+10 | 0.191400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23274864.17 | 0.165913E+11 |
December | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369701E+11 |
Annual Sum or Average | 0.395654E+11 | 0.239148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681029E+09 | 0.215026E+12 |
Minimum of Months | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512460E+10 |
Maximum of Months | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305605E+09 | 0.383199E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101236E+12 |
February | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66027937.37 | 0.111852E+12 |
March | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145300E+10 | 0.586238E+11 |
April | 0.750829E+10 | 0.291438E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437360E+09 | 0.348229E+11 |
May | 0.780862E+10 | 0.302559E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273861E+09 | 0.279944E+11 |
June | 0.780862E+10 | 0.299876E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76508822.84 | 0.320330E+11 |
July | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1665068.12 | 0.269647E+11 |
August | 0.810895E+10 | 0.310997E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1036607.59 | 0.292433E+11 |
September | 0.750829E+10 | 0.291438E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286834E+11 |
October | 0.750829E+10 | 0.294120E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.661187E+09 | 0.308296E+11 |
November | 0.720796E+10 | 0.282999E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185574E+10 | 0.346596E+11 |
December | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102281E+09 | 0.102584E+12 |
Annual Sum or Average | 0.910005E+11 | 0.353598E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492867E+10 | 0.619527E+12 |
Minimum of Months | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269647E+11 |
Maximum of Months | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185574E+10 | 0.111852E+12 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1955.04 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 18464.01 | 12-JAN-08:00 |
February | 1680.92 | 01-FEB-08:09 | 1955.04 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 19243.04 | 06-FEB-17:10 |
March | 1680.92 | 01-MAR-08:09 | 1955.04 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 309.29 | 15-MAR-16:10 | 12338.24 | 03-MAR-18:00 |
April | 1680.92 | 01-APR-07:10 | 1955.04 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 10622.38 | 04-APR-17:00 |
May | 1680.92 | 01-MAY-07:10 | 1955.04 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 300.61 | 10-MAY-15:10 | 5397.14 | 08-MAY-07:00 |
June | 1680.92 | 01-JUN-07:10 | 1955.04 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1732.00 | 27-JUN-12:00 | 5333.39 | 13-JUN-16:05 |
July | 1680.92 | 01-JUL-07:10 | 1955.04 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2234.96 | 20-JUL-16:10 | 3316.22 | 06-JUL-06:05 |
August | 1680.92 | 01-AUG-07:10 | 1955.04 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2177.39 | 18-AUG-17:00 | 3582.07 | 30-AUG-17:00 |
September | 1680.92 | 01-SEP-07:10 | 1955.04 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 546.60 | 16-SEP-15:10 | 5066.61 | 29-SEP-06:10 |
October | 1680.92 | 02-OCT-07:10 | 1955.04 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.92 | 22-OCT-12:00 | 7155.06 | 30-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 1955.04 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.89 | 27-NOV-06:00 | 9501.91 | 17-NOV-18:00 |
December | 1680.92 | 01-DEC-08:09 | 1955.04 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 16657.92 | 26-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3316.22 | |||||
Maximum of Months | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 2234.96 | 19243.04 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 62532.35 | 12-JAN-09:00 |
February | 3955.50 | 01-FEB-08:09 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 56671.97 | 13-FEB-07:10 |
March | 3955.50 | 01-MAR-08:09 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.32 | 12-MAR-13:00 | 29610.96 | 03-MAR-18:00 |
April | 3955.50 | 01-APR-07:10 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 27785.15 | 04-APR-17:00 |
May | 3955.50 | 01-MAY-07:10 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 946.18 | 14-MAY-15:00 | 18471.77 | 11-MAY-15:03 |
June | 3955.50 | 01-JUN-07:10 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3500.12 | 12-JUN-15:10 | 20323.54 | 13-JUN-15:03 |
July | 3955.50 | 01-JUL-07:10 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7104.91 | 15-JUL-15:10 | 9704.64 | 06-JUL-02:00 |
August | 3955.50 | 01-AUG-07:10 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4340.15 | 13-AUG-13:07 | 11582.36 | 30-AUG-17:00 |
September | 3955.50 | 01-SEP-07:10 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.42 | 16-SEP-13:00 | 14905.39 | 29-SEP-15:25 |
October | 3955.50 | 02-OCT-07:10 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 675.51 | 22-OCT-12:00 | 18087.87 | 23-OCT-15:03 |
November | 3955.50 | 01-NOV-07:10 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2021.42 | 27-NOV-06:01 | 28224.86 | 17-NOV-09:00 |
December | 3955.50 | 01-DEC-08:09 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 55986.33 | 09-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9704.64 | ||||
Maximum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7104.91 | 62532.35 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 26389.90 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 172111.57 | 12-JAN-09:00 |
February | 9097.65 | 01-FEB-08:09 | 26389.90 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7619.12 | 22-FEB-19:00 | 169294.04 | 07-FEB-11:00 |
March | 9097.65 | 01-MAR-08:09 | 26389.90 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26803.50 | 14-MAR-14:00 | 79157.87 | 01-MAR-15:00 |
April | 9097.65 | 01-APR-07:10 | 26389.90 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11459.46 | 07-APR-14:00 | 58109.24 | 16-APR-06:51 |
May | 9097.65 | 01-MAY-07:10 | 26389.90 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13180.43 | 14-MAY-15:00 | 44229.25 | 11-MAY-15:00 |
June | 9097.65 | 01-JUN-07:10 | 26389.90 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4253.08 | 17-JUN-16:00 | 57704.65 | 13-JUN-16:00 |
July | 9097.65 | 01-JUL-07:10 | 26389.90 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1978.50 | 15-JUL-13:55 | 35313.35 | 06-JUL-02:00 |
August | 9097.65 | 01-AUG-07:10 | 26389.90 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.75 | 13-AUG-12:53 | 37617.73 | 30-AUG-15:55 |
September | 9097.65 | 01-SEP-07:10 | 26389.90 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 41129.37 | 28-SEP-14:00 |
October | 9097.65 | 02-OCT-07:10 | 26389.90 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13439.90 | 22-OCT-12:00 | 44487.38 | 23-OCT-15:00 |
November | 9097.65 | 01-NOV-07:10 | 26389.90 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20625.09 | 27-NOV-06:01 | 49320.09 | 17-NOV-09:00 |
December | 9097.65 | 01-DEC-08:09 | 26389.90 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11361.57 | 01-DEC-11:00 | 151280.62 | 09-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35313.35 | |||||
Maximum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 26803.50 | 172111.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 2742.13 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1598.55 |
February | 1075.41 | 18-FEB-07:05 | 1411.97 | 4265.54 | 3825.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2310.22 |
March | 2996.28 | 15-MAR-15:10 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 219.44 | 0.00 |
April | 2065.63 | 22-APR-15:00 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.10 |
May | 9515.26 | 27-MAY-17:15 | 0.00 | 914.04 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.64 |
June | 19490.13 | 30-JUN-18:23 | 0.00 | 1371.07 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.79 |
July | 19693.68 | 04-JUL-23:01 | 0.00 | 4113.20 | 5163.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.49 |
August | 20565.54 | 20-AUG-23:01 | 0.00 | 3199.16 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.93 |
September | 18151.99 | 21-SEP-17:43 | 0.00 | 1371.07 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.58 |
October | 3427.35 | 11-OCT-16:00 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.13 |
November | 617.31 | 18-NOV-15:30 | 1680.92 | 1955.04 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 929.62 |
December | 1601.80 | 16-DEC-07:05 | 1411.97 | 4265.54 | 3825.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1334.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 914.04 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20565.54 | 1680.92 | 4265.54 | 5163.75 | 0.00 | 0.00 | 0.00 | 0.00 | 219.44 | 2310.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5092.31 | 06-JAN-14:20 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3609.86 |
February | 6908.71 | 10-FEB-13:10 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 955.62 |
March | 5963.89 | 04-MAR-13:10 | 7911.00 | 35696.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7634.25 |
April | 4369.75 | 10-APR-08:15 | 7911.00 | 35696.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3523.80 |
May | 10875.43 | 27-MAY-15:00 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1441.68 |
June | 42939.55 | 27-JUN-17:08 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.01 |
July | 62989.47 | 18-JUL-17:06 | 0.00 | 10498.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 666.31 | 0.00 |
August | 61294.40 | 06-AUG-14:43 | 0.00 | 6299.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 923.76 | 0.00 |
September | 21650.07 | 16-SEP-13:40 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.27 | 0.00 |
October | 4726.27 | 17-OCT-08:20 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2356.60 |
November | 4603.32 | 24-NOV-11:00 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4086.41 | 16-DEC-10:00 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2548.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4086.41 | 0.00 | 6299.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 62989.47 | 7911.00 | 35696.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 923.76 | 7634.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 18628.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21351.69 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 18628.16 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28675.33 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 15523.47 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25272.41 |
April | 0.00 | 01-APR-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7067.79 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4510.43 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5067.01 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14493.13 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10117.37 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13215.67 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8753.34 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11989.61 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 9314.08 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13170.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4510.43 | |
Maximum of Months | 0.00 | 0.00 | 18628.16 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28675.33 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.879440E+11 | 66816.99 | 13-JAN-16:00 | 0.329941E+12 | 418968.31 | 12-JAN-08:00 |
February | 0.795770E+11 | 64145.25 | 13-FEB-15:00 | 0.338263E+12 | 428576.00 | 13-FEB-06:10 |
March | 0.884065E+11 | 64502.47 | 15-MAR-14:20 | 0.135421E+12 | 226411.64 | 05-MAR-01:10 |
April | 0.806341E+11 | 63956.71 | 08-APR-12:00 | 0.287325E+11 | 165468.75 | 16-APR-03:49 |
May | 0.823938E+11 | 68344.05 | 27-MAY-14:00 | 0.823152E+09 | 26406.43 | 01-MAY-05:10 |
June | 0.852633E+11 | 83073.98 | 27-JUN-12:00 | 37017988.94 | 6951.96 | 14-JUN-06:10 |
July | 0.906514E+11 | 84992.16 | 19-JUL-14:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.935565E+11 | 81708.60 | 10-AUG-14:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.832140E+11 | 75360.49 | 16-SEP-13:30 | 76361491.00 | 7752.23 | 30-SEP-05:10 |
October | 0.832911E+11 | 64318.99 | 11-OCT-14:00 | 0.586434E+10 | 70157.48 | 30-OCT-05:19 |
November | 0.822820E+11 | 66810.01 | 30-NOV-16:40 | 0.512108E+11 | 127764.58 | 25-NOV-06:10 |
December | 0.881334E+11 | 66815.11 | 29-DEC-16:49 | 0.311231E+12 | 367304.86 | 26-DEC-06:10 |
Annual Sum or Average | 0.102535E+13 | 0.120160E+13 | ||||
Minimum of Months | 0.795770E+11 | 63956.71 | 0.00 | 0.00 | ||
Maximum of Months | 0.935565E+11 | 84992.16 | 0.338263E+12 | 428576.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.518856E+11 | 0.140730E+11 | 0.115358E+11 | 0.00 | 0.807551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237400E+10 | 0.00 |
February | 0.474804E+11 | 0.117437E+11 | 0.105871E+11 | 0.00 | 0.759543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217028E+10 | 0.00 |
March | 0.548234E+11 | 0.116670E+11 | 0.123431E+11 | 0.00 | 0.708789E+10 | 0.00 | 0.00 | 45246340.15 | 0.00 | 0.00 | 0.00 | 0.243999E+10 | 0.00 |
April | 0.513965E+11 | 0.994174E+10 | 0.114862E+11 | 0.00 | 0.550210E+10 | 0.00 | 0.00 | 22746503.67 | 0.00 | 0.00 | 0.00 | 0.228478E+10 | 0.00 |
May | 0.533545E+11 | 0.908681E+10 | 0.119357E+11 | 0.00 | 0.518149E+10 | 0.00 | 0.00 | 0.531826E+09 | 0.00 | 0.00 | 0.00 | 0.230346E+10 | 0.00 |
June | 0.528654E+11 | 0.822165E+10 | 0.118862E+11 | 0.00 | 0.531785E+10 | 0.00 | 0.00 | 0.477936E+10 | 0.00 | 0.00 | 0.00 | 0.219296E+10 | 0.00 |
July | 0.518856E+11 | 0.872334E+10 | 0.115358E+11 | 0.00 | 0.574716E+10 | 0.00 | 0.00 | 0.105886E+11 | 0.00 | 0.00 | 0.00 | 0.217089E+10 | 0.00 |
August | 0.548234E+11 | 0.974209E+10 | 0.123357E+11 | 0.00 | 0.594770E+10 | 0.00 | 0.00 | 0.849532E+10 | 0.00 | 0.00 | 0.00 | 0.221231E+10 | 0.00 |
September | 0.513965E+11 | 0.107096E+11 | 0.114788E+11 | 0.00 | 0.500485E+10 | 0.00 | 0.00 | 0.249765E+10 | 0.00 | 0.00 | 0.00 | 0.212652E+10 | 0.00 |
October | 0.518856E+11 | 0.124502E+11 | 0.115432E+11 | 0.00 | 0.507832E+10 | 0.00 | 0.00 | 0.108569E+09 | 0.00 | 0.00 | 0.00 | 0.222524E+10 | 0.00 |
November | 0.499276E+11 | 0.132488E+11 | 0.110862E+11 | 0.00 | 0.581636E+10 | 0.00 | 0.00 | 70426.11 | 0.00 | 0.00 | 0.00 | 0.220293E+10 | 0.00 |
December | 0.518856E+11 | 0.143956E+11 | 0.115358E+11 | 0.00 | 0.798141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233503E+10 | 0.00 |
Annual Sum or Average | 0.623610E+12 | 0.134004E+12 | 0.139290E+12 | 0.00 | 0.743361E+11 | 0.00 | 0.00 | 0.270694E+11 | 0.00 | 0.00 | 0.00 | 0.270384E+11 | 0.00 |
Minimum of Months | 0.474804E+11 | 0.822165E+10 | 0.105871E+11 | 0.00 | 0.500485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212652E+10 | 0.00 |
Maximum of Months | 0.548234E+11 | 0.143956E+11 | 0.123431E+11 | 0.00 | 0.807551E+10 | 0.00 | 0.00 | 0.105886E+11 | 0.00 | 0.00 | 0.00 | 0.243999E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.329941E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.338263E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.135421E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.287325E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.823152E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 37017988.94 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 76361491.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.586434E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.512108E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.311231E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.120160E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.338263E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 46193.18 | 02-JAN-09:09 | 8532.22 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 5555.01 | 12-JAN-14:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 46193.18 | 01-FEB-09:09 | 8532.22 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 5555.01 | 14-FEB-10:20 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 46193.18 | 01-MAR-09:09 | 8532.22 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 5555.01 | 02-MAR-09:39 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 46193.18 | 01-APR-08:09 | 8532.22 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 5555.01 | 01-APR-06:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 46193.18 | 01-MAY-08:09 | 8532.22 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 5017.67 | 01-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 46193.18 | 01-JUN-08:09 | 8532.22 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 7322.97 | 12-JUN-13:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 46193.18 | 01-JUL-08:09 | 8532.22 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 7322.97 | 14-JUL-13:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 46193.18 | 01-AUG-08:09 | 8532.22 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 7322.97 | 04-AUG-12:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 46193.18 | 01-SEP-08:09 | 8532.22 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 5017.67 | 01-SEP-07:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 46193.18 | 02-OCT-08:09 | 8532.22 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 5017.67 | 02-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 46193.18 | 01-NOV-08:09 | 8532.22 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 5555.01 | 03-NOV-06:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 46193.18 | 01-DEC-09:09 | 8532.22 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 5555.01 | 19-DEC-15:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 46193.18 | 8532.22 | 10112.62 | 0.00 | 5017.67 | 0.00 | 0.00 | |||||
Maximum of Months | 46193.18 | 8532.22 | 10112.62 | 0.00 | 7322.97 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2745.44 | 30-JAN-12:20 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2761.08 | 13-FEB-12:50 | 0.00 |
March | 1351.24 | 15-MAR-15:09 | 0.00 | 0.00 | 0.00 | 2749.00 | 01-MAR-12:00 | 0.00 |
April | 743.13 | 08-APR-14:20 | 0.00 | 0.00 | 0.00 | 2627.41 | 03-APR-11:30 | 0.00 |
May | 5225.11 | 27-MAY-14:00 | 0.00 | 0.00 | 0.00 | 2435.38 | 01-MAY-11:39 | 0.00 |
June | 17669.86 | 27-JUN-12:00 | 0.00 | 0.00 | 0.00 | 2134.25 | 03-JUN-11:50 | 0.00 |
July | 20394.96 | 19-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1813.00 | 01-JUL-11:00 | 0.00 |
August | 16547.91 | 10-AUG-15:09 | 0.00 | 0.00 | 0.00 | 1800.35 | 01-AUG-11:09 | 0.00 |
September | 12363.01 | 16-SEP-13:39 | 0.00 | 0.00 | 0.00 | 1876.40 | 30-SEP-11:00 | 0.00 |
October | 1299.67 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 | 2148.25 | 30-OCT-11:20 | 0.00 |
November | 95.11 | 04-NOV-14:00 | 0.00 | 0.00 | 0.00 | 2406.00 | 28-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2628.69 | 30-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1800.35 | 0.00 | ||
Maximum of Months | 20394.96 | 0.00 | 0.00 | 0.00 | 2761.08 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 66816.99 | 13-JAN-16:00 | 40988.70 | 10112.62 | 8532.22 | 0.00 | 5555.01 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 64145.25 | 13-FEB-15:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 5555.01 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 64502.47 | 15-MAR-14:20 | 46193.18 | 10112.62 | 0.00 | 0.00 | 5017.67 | 0.00 | 0.00 | 1338.05 | 0.00 |
April | 63956.71 | 08-APR-12:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 5017.67 | 0.00 | 0.00 | 620.35 | 0.00 |
May | 68344.05 | 27-MAY-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 5017.67 | 0.00 | 0.00 | 5225.11 | 0.00 |
June | 83073.98 | 27-JUN-12:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 7322.97 | 0.00 | 0.00 | 17669.86 | 0.00 |
July | 84992.16 | 19-JUL-14:39 | 46193.18 | 10112.62 | 0.00 | 0.00 | 7322.97 | 0.00 | 0.00 | 19597.39 | 0.00 |
August | 81708.60 | 10-AUG-14:20 | 46193.18 | 10112.62 | 0.00 | 0.00 | 7322.97 | 0.00 | 0.00 | 16318.49 | 0.00 |
September | 75360.49 | 16-SEP-13:30 | 46193.18 | 10112.62 | 0.00 | 0.00 | 5017.67 | 0.00 | 0.00 | 12306.37 | 0.00 |
October | 64318.99 | 11-OCT-14:00 | 46193.18 | 10112.62 | 0.00 | 0.00 | 5017.67 | 0.00 | 0.00 | 1217.17 | 0.00 |
November | 66810.01 | 30-NOV-16:40 | 40988.70 | 10112.62 | 8532.22 | 0.00 | 5555.01 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 66815.11 | 29-DEC-16:49 | 40988.70 | 10112.62 | 8532.22 | 0.00 | 5555.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 63956.71 | 40988.70 | 10112.62 | 0.00 | 0.00 | 5017.67 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 84992.16 | 46193.18 | 10112.62 | 8532.22 | 0.00 | 7322.97 | 0.00 | 0.00 | 19597.39 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 418968.31 | 12-JAN-08:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 428576.00 | 13-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 226411.64 | 05-MAR-01:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 165468.75 | 16-APR-03:49 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 26406.43 | 01-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 6951.96 | 14-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 7752.23 | 30-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 70157.48 | 30-OCT-05:19 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 127764.58 | 25-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 367304.86 | 26-DEC-06:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 428576.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 76.33 | 15.32 | 10.67 | 15.76 | 0.00 | 15.76 | 0.00 | 15.76 |
February | 71.67 | 15.29 | 13.00 | 15.80 | 0.00 | 15.80 | 0.00 | 15.80 |
March | 37.50 | 15.99 | 10.33 | 16.63 | 0.00 | 16.63 | 0.00 | 16.63 |
April | 11.67 | 18.37 | 8.50 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
May | 1.83 | 20.27 | 1.83 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
June | 0.17 | 20.46 | 0.17 | 20.46 | 13.00 | 24.49 | 0.33 | 24.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 24.66 | 0.33 | 24.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 24.64 | 1.00 | 24.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 24.52 | 0.17 | 24.52 |
October | 5.17 | 19.93 | 5.17 | 19.93 | 0.00 | 19.93 | 0.00 | 19.93 |
November | 10.50 | 18.52 | 8.17 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
December | 65.33 | 15.35 | 10.33 | 15.84 | 0.00 | 15.84 | 0.00 | 15.84 |
Annual Sum or Average | 280.17 | 15.77 | 68.17 | 16.44 | 67.67 | 17.77 | 1.83 | 17.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.76 | 0.00 | 15.76 |
Maximum of Months | 76.33 | 20.46 | 13.00 | 20.46 | 26.17 | 24.66 | 1.00 | 24.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 114.67 | 13.72 | 4.50 | 13.71 | 0.00 | 13.71 | 0.00 | 13.71 |
February | 105.50 | 13.58 | 5.00 | 13.58 | 0.00 | 13.58 | 0.00 | 13.58 |
March | 76.67 | 14.17 | 5.00 | 14.17 | 0.00 | 14.17 | 0.00 | 14.17 |
April | 34.67 | 14.53 | 2.50 | 14.53 | 0.00 | 14.53 | 0.00 | 14.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.27 | 0.00 | 27.27 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.42 | 0.00 | 27.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.46 | 0.00 | 27.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.00 | 27.29 |
October | 11.83 | 14.82 | 1.33 | 14.81 | 0.00 | 14.81 | 0.00 | 14.81 |
November | 68.67 | 14.63 | 3.50 | 14.63 | 0.00 | 14.63 | 0.00 | 14.63 |
December | 115.00 | 13.81 | 4.17 | 13.80 | 0.00 | 13.80 | 0.00 | 13.80 |
Annual Sum or Average | 527.00 | 13.97 | 26.00 | 13.97 | 17.50 | 14.39 | 0.00 | 14.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.00 | 14.82 | 5.00 | 14.81 | 10.83 | 27.46 | 0.00 | 27.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.02 | 300.00 | 21.02 | 300.00 | 21.02 |
February | 276.00 | 20.98 | 276.00 | 20.98 | 276.00 | 20.98 |
March | 324.00 | 21.27 | 284.17 | 21.16 | 284.17 | 21.12 |
April | 300.00 | 21.58 | 219.33 | 21.37 | 219.33 | 21.29 |
May | 294.00 | 22.95 | 49.50 | 22.69 | 49.50 | 22.50 |
June | 83.00 | 23.27 | 163.67 | 23.69 | 6.83 | 23.69 |
July | 17.83 | 23.76 | 268.83 | 23.90 | 10.83 | 23.90 |
August | 20.17 | 23.56 | 264.33 | 23.88 | 2.50 | 23.88 |
September | 110.33 | 23.20 | 123.83 | 23.55 | 3.50 | 23.53 |
October | 300.00 | 22.15 | 119.50 | 21.85 | 119.50 | 21.69 |
November | 288.00 | 21.21 | 262.50 | 21.15 | 262.50 | 21.12 |
December | 300.00 | 21.02 | 300.00 | 21.02 | 300.00 | 21.02 |
Annual Sum or Average | 2613.33 | 21.68 | 2631.67 | 21.81 | 1834.67 | 21.62 |
Minimum of Months | 17.83 | 20.98 | 49.50 | 20.98 | 2.50 | 20.98 |
Maximum of Months | 324.00 | 23.76 | 300.00 | 23.90 | 300.00 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.56 | 300.00 | 15.56 | 300.00 | 15.56 |
February | 276.00 | 15.57 | 276.00 | 15.57 | 276.00 | 15.57 |
March | 319.17 | 16.94 | 296.83 | 16.74 | 293.67 | 16.64 |
April | 300.00 | 18.57 | 241.50 | 18.15 | 241.50 | 17.99 |
May | 205.50 | 21.44 | 147.50 | 22.03 | 66.50 | 21.53 |
June | 174.17 | 25.63 | 261.33 | 26.07 | 134.83 | 26.17 |
July | 253.50 | 26.62 | 291.50 | 26.60 | 249.33 | 26.62 |
August | 232.83 | 26.52 | 308.50 | 26.52 | 225.17 | 26.55 |
September | 140.00 | 24.07 | 214.50 | 25.31 | 66.33 | 25.34 |
October | 287.50 | 19.71 | 205.33 | 19.25 | 202.17 | 19.03 |
November | 288.00 | 16.97 | 282.83 | 16.93 | 282.83 | 16.91 |
December | 300.00 | 15.66 | 300.00 | 15.66 | 300.00 | 15.66 |
Annual Sum or Average | 3076.67 | 19.62 | 3125.83 | 19.92 | 2638.33 | 19.68 |
Minimum of Months | 140.00 | 15.56 | 147.50 | 15.56 | 66.33 | 15.56 |
Maximum of Months | 319.17 | 26.62 | 308.50 | 26.60 | 300.00 | 26.62 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 10.06 | 300.00 | 10.06 | 300.00 | 10.06 |
February | 276.00 | 10.04 | 276.00 | 10.04 | 276.00 | 10.04 |
March | 324.00 | 11.67 | 324.00 | 11.67 | 324.00 | 11.67 |
April | 300.00 | 13.82 | 300.00 | 13.82 | 300.00 | 13.82 |
May | 300.50 | 19.67 | 175.33 | 19.04 | 175.33 | 18.75 |
June | 212.00 | 25.27 | 203.83 | 25.92 | 127.83 | 26.23 |
July | 265.00 | 28.85 | 298.00 | 28.67 | 265.00 | 28.73 |
August | 267.50 | 28.41 | 317.83 | 28.19 | 264.67 | 28.27 |
September | 174.33 | 22.99 | 170.33 | 24.05 | 64.50 | 24.09 |
October | 300.00 | 16.33 | 280.17 | 16.16 | 280.17 | 16.10 |
November | 288.00 | 11.81 | 288.00 | 11.81 | 288.00 | 11.81 |
December | 300.00 | 10.13 | 300.00 | 10.13 | 300.00 | 10.13 |
Annual Sum or Average | 3307.33 | 16.80 | 3233.50 | 16.89 | 2965.50 | 16.67 |
Minimum of Months | 174.33 | 10.04 | 170.33 | 10.04 | 64.50 | 10.04 |
Maximum of Months | 324.00 | 28.85 | 324.00 | 28.67 | 324.00 | 28.73 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.164996E+09 | 45246340.15 | 17.08 | 0.143809E+09 | 21187080.95 | 0.00 | 0.25 | 15-MAR-15:10 | 0.00 | 01-MAR-00:02 | 4914.07 | 15-MAR-15:10 | 4555.19 | 15-MAR-15:10 | 778.67 | 14-MAR-14:00 | 1351.24 | 15-MAR-15:10 | 0.00 | 01-MAR-00:02 |
April | 82755858.13 | 22746503.67 | 20.17 | 81263069.67 | 1492788.45 | 0.00 | 0.14 | 08-APR-14:20 | 0.00 | 01-APR-00:10 | 2728.07 | 08-APR-14:20 | 2592.61 | 08-APR-14:20 | 148.11 | 08-APR-15:00 | 743.13 | 08-APR-14:20 | 0.00 | 01-APR-00:10 |
May | 0.163799E+10 | 0.442896E+09 | 158.75 | 0.153935E+10 | 98633130.75 | 0.00 | 0.51 | 27-MAY-17:15 | 0.00 | 01-MAY-00:10 | 10302.23 | 27-MAY-17:15 | 10302.23 | 27-MAY-17:15 | 1078.75 | 10-MAY-15:10 | 2652.22 | 27-MAY-17:15 | 0.00 | 01-MAY-00:10 |
June | 0.723500E+10 | 0.191470E+10 | 338.02 | 0.602927E+10 | 0.120573E+10 | 0.00 | 1.00 | 11-JUN-23:02 | 0.00 | 01-JUN-00:10 | 25396.27 | 18-JUN-23:02 | 21666.51 | 30-JUN-18:23 | 8539.86 | 27-JUN-17:08 | 6016.99 | 17-JUN-17:10 | 0.00 | 01-JUN-00:10 |
July | 0.119537E+11 | 0.315214E+10 | 436.78 | 0.935468E+10 | 0.259899E+10 | 0.00 | 1.00 | 02-JUL-23:01 | 0.00 | 01-JUL-00:10 | 27035.65 | 16-JUL-23:01 | 21520.24 | 13-JUL-17:08 | 10277.58 | 16-JUL-23:05 | 6124.73 | 16-JUL-23:01 | 0.00 | 01-JUL-00:10 |
August | 0.107179E+11 | 0.283757E+10 | 434.92 | 0.900366E+10 | 0.171426E+10 | 0.00 | 1.00 | 02-AUG-17:08 | 0.00 | 01-AUG-00:15 | 27930.19 | 13-AUG-23:01 | 22375.42 | 02-AUG-17:08 | 12675.93 | 13-AUG-23:06 | 6267.71 | 13-AUG-23:01 | 0.00 | 01-AUG-00:10 |
September | 0.520683E+10 | 0.137861E+10 | 274.96 | 0.444309E+10 | 0.763744E+09 | 0.00 | 1.00 | 16-SEP-17:08 | 0.00 | 01-SEP-00:10 | 23707.61 | 16-SEP-17:43 | 20285.50 | 21-SEP-17:43 | 4288.08 | 16-SEP-18:23 | 5694.78 | 16-SEP-17:08 | 0.00 | 01-SEP-00:10 |
October | 0.398954E+09 | 0.108569E+09 | 54.17 | 0.366383E+09 | 32570897.39 | 0.00 | 0.24 | 11-OCT-16:00 | 0.00 | 01-OCT-00:10 | 4851.74 | 11-OCT-16:00 | 4521.22 | 11-OCT-16:00 | 767.68 | 12-OCT-15:00 | 1299.67 | 11-OCT-16:00 | 0.00 | 01-OCT-00:10 |
November | 254713.00 | 70426.11 | 0.33 | 210573.53 | 44139.48 | 0.00 | 0.02 | 04-NOV-15:00 | 0.00 | 01-NOV-00:10 | 344.13 | 04-NOV-15:00 | 284.53 | 04-NOV-15:00 | 59.60 | 04-NOV-15:00 | 95.11 | 04-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.373984E+11 | 0.990254E+10 | 1735.17 | 0.309617E+11 | 0.643666E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.119537E+11 | 0.315214E+10 | 436.78 | 0.935468E+10 | 0.259899E+10 | 0.00 | 1.00 | 0.00 | 27930.19 | 22375.42 | 12675.93 | 6267.71 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.298205E+09 | 88930680.22 | 18.00 | 0.280755E+09 | 17450320.57 | 0.00 | 0.18 | 27-MAY-15:00 | 0.00 | 01-MAY-00:10 | 11998.88 | 27-MAY-15:00 | 11998.88 | 27-MAY-15:00 | 1589.75 | 10-MAY-14:40 | 3523.90 | 27-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.990066E+10 | 0.286466E+10 | 126.99 | 0.766394E+10 | 0.223672E+10 | 0.00 | 0.84 | 27-JUN-17:08 | 0.00 | 01-JUN-00:10 | 74612.84 | 27-JUN-17:08 | 47583.47 | 27-JUN-17:08 | 27029.36 | 27-JUN-17:08 | 19643.85 | 27-JUN-17:08 | 0.00 | 01-JUN-00:10 |
July | 0.258095E+11 | 0.743647E+10 | 277.52 | 0.192262E+11 | 0.658329E+10 | 0.00 | 1.00 | 16-JUL-10:03 | 0.00 | 01-JUL-00:10 | 89913.43 | 16-JUL-10:03 | 69087.73 | 18-JUL-17:06 | 32347.09 | 16-JUL-10:03 | 23824.76 | 16-JUL-10:03 | 0.00 | 01-JUL-00:10 |
August | 0.194309E+11 | 0.565775E+10 | 222.93 | 0.159676E+11 | 0.346320E+10 | 0.00 | 1.00 | 13-AUG-12:23 | 0.00 | 01-AUG-00:10 | 85996.89 | 13-AUG-12:23 | 67891.29 | 06-AUG-14:43 | 28582.63 | 13-AUG-16:23 | 23417.75 | 13-AUG-12:23 | 0.00 | 01-AUG-00:10 |
September | 0.386972E+10 | 0.111905E+10 | 69.11 | 0.300788E+10 | 0.861840E+09 | 0.00 | 0.43 | 16-SEP-13:40 | 0.00 | 01-SEP-00:10 | 32263.22 | 16-SEP-13:40 | 25536.56 | 16-SEP-13:40 | 8737.99 | 15-SEP-11:00 | 9462.22 | 16-SEP-13:40 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.593089E+11 | 0.171669E+11 | 714.55 | 0.461464E+11 | 0.131625E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.258095E+11 | 0.743647E+10 | 277.52 | 0.192262E+11 | 0.658329E+10 | 0.00 | 1.00 | 0.00 | 89913.43 | 69087.73 | 32347.09 | 23824.76 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.24 | 12.30 | 39.94 | 13.67 | 199.80 | 0.00 | 0.00 | 0.00 |
February | 84.65 | 21.85 | 62.80 | 34.23 | 186.32 | 0.00 | 0.00 | 0.00 |
March | 133.07 | 57.20 | 75.86 | 108.94 | 121.19 | 0.00 | 0.00 | 0.00 |
April | 161.87 | 66.25 | 95.62 | 159.18 | 82.03 | 0.00 | 0.00 | 0.00 |
May | 191.10 | 86.29 | 104.81 | 212.23 | 61.06 | 0.00 | 0.00 | 0.00 |
June | 230.87 | 108.62 | 122.26 | 279.15 | 48.91 | 0.00 | 0.00 | 0.00 |
July | 206.17 | 90.26 | 115.90 | 265.39 | 36.27 | 0.00 | 0.00 | 0.00 |
August | 186.26 | 78.99 | 107.27 | 234.97 | 47.13 | 0.00 | 0.00 | 0.00 |
September | 146.66 | 63.37 | 83.29 | 164.06 | 71.79 | 0.00 | 0.00 | 0.00 |
October | 95.04 | 33.48 | 61.56 | 84.48 | 89.86 | 0.00 | 0.00 | 0.00 |
November | 55.86 | 15.86 | 40.00 | 35.08 | 112.95 | 0.00 | 0.00 | 0.00 |
December | 48.73 | 10.56 | 38.17 | 12.85 | 190.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 132.93 | 53.91 | 79.02 | 134.22 | 103.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.73 | 10.56 | 38.17 | 12.85 | 36.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 230.87 | 108.62 | 122.26 | 279.15 | 199.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.24 | 12.30 | 39.94 | 13.67 | 199.80 | 0.00 | 0.00 | 0.00 |
February | 84.65 | 21.85 | 62.80 | 34.23 | 186.32 | 0.00 | 0.00 | 0.00 |
March | 133.07 | 57.20 | 75.86 | 108.94 | 121.19 | 0.00 | 0.00 | 0.00 |
April | 161.87 | 66.25 | 95.62 | 159.18 | 82.03 | 0.00 | 0.00 | 0.00 |
May | 191.10 | 86.29 | 104.81 | 212.23 | 61.06 | 0.00 | 0.00 | 0.00 |
June | 230.87 | 108.62 | 122.26 | 279.15 | 48.91 | 0.00 | 0.00 | 0.00 |
July | 206.17 | 90.26 | 115.90 | 265.39 | 36.27 | 0.00 | 0.00 | 0.00 |
August | 186.26 | 78.99 | 107.27 | 234.97 | 47.13 | 0.00 | 0.00 | 0.00 |
September | 146.66 | 63.37 | 83.29 | 164.06 | 71.79 | 0.00 | 0.00 | 0.00 |
October | 95.04 | 33.48 | 61.56 | 84.48 | 89.86 | 0.00 | 0.00 | 0.00 |
November | 55.86 | 15.86 | 40.00 | 35.08 | 112.95 | 0.00 | 0.00 | 0.00 |
December | 48.73 | 10.56 | 38.17 | 12.85 | 190.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 132.93 | 53.91 | 79.02 | 134.22 | 103.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.73 | 10.56 | 38.17 | 12.85 | 36.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 230.87 | 108.62 | 122.26 | 279.15 | 199.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.37 | 0.00 | 19.37 | 0.18 | 124.45 | 0.00 | 0.00 | 0.00 |
February | 29.51 | 0.00 | 29.51 | 1.27 | 116.04 | 0.00 | 0.00 | 0.00 |
March | 35.80 | 0.00 | 35.80 | 12.15 | 77.31 | 0.00 | 0.00 | 0.00 |
April | 45.64 | 0.22 | 45.42 | 26.77 | 48.96 | 0.00 | 0.00 | 0.00 |
May | 53.02 | 2.28 | 50.73 | 42.19 | 33.77 | 0.00 | 0.00 | 0.00 |
June | 63.74 | 5.42 | 58.32 | 64.36 | 26.46 | 0.00 | 0.00 | 0.00 |
July | 59.36 | 4.04 | 55.33 | 69.65 | 19.51 | 0.00 | 0.00 | 0.00 |
August | 51.40 | 0.99 | 50.40 | 56.04 | 26.57 | 0.00 | 0.00 | 0.00 |
September | 38.95 | 0.02 | 38.94 | 31.43 | 42.78 | 0.00 | 0.00 | 0.00 |
October | 29.11 | 0.00 | 29.11 | 14.21 | 54.32 | 0.00 | 0.00 | 0.00 |
November | 19.56 | 0.00 | 19.56 | 4.83 | 68.11 | 0.00 | 0.00 | 0.00 |
December | 18.13 | 0.00 | 18.13 | 0.26 | 117.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.67 | 1.09 | 37.58 | 27.10 | 62.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.13 | 0.00 | 18.13 | 0.18 | 19.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.74 | 5.42 | 58.32 | 69.65 | 124.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.37 | 0.00 | 19.37 | 0.18 | 124.45 | 0.00 | 0.00 | 0.00 |
February | 29.51 | 0.00 | 29.51 | 1.27 | 116.04 | 0.00 | 0.00 | 0.00 |
March | 35.80 | 0.00 | 35.80 | 12.15 | 77.31 | 0.00 | 0.00 | 0.00 |
April | 45.64 | 0.22 | 45.42 | 26.76 | 48.96 | 0.00 | 0.00 | 0.00 |
May | 53.01 | 2.28 | 50.73 | 42.19 | 33.77 | 0.00 | 0.00 | 0.00 |
June | 63.74 | 5.42 | 58.32 | 64.36 | 26.46 | 0.00 | 0.00 | 0.00 |
July | 59.36 | 4.04 | 55.32 | 69.65 | 19.51 | 0.00 | 0.00 | 0.00 |
August | 51.39 | 0.99 | 50.40 | 56.03 | 26.57 | 0.00 | 0.00 | 0.00 |
September | 38.95 | 0.02 | 38.93 | 31.43 | 42.78 | 0.00 | 0.00 | 0.00 |
October | 29.10 | 0.00 | 29.10 | 14.21 | 54.32 | 0.00 | 0.00 | 0.00 |
November | 19.56 | 0.00 | 19.56 | 4.83 | 68.11 | 0.00 | 0.00 | 0.00 |
December | 18.13 | 0.00 | 18.13 | 0.26 | 117.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.67 | 1.09 | 37.58 | 27.10 | 62.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.13 | 0.00 | 18.13 | 0.18 | 19.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.74 | 5.42 | 58.32 | 69.65 | 124.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.39 | 119.47 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 33.98 | 116.57 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 82.18 | 74.69 | 35.00 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 121.30 | 47.37 | 16.00 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 157.94 | 45.37 | 8.67 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 185.41 | 45.86 | 7.67 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 173.32 | 44.98 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 143.92 | 53.25 | 3.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 101.82 | 61.93 | 13.33 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 59.43 | 56.82 | 13.33 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.24 | 56.23 | 14.67 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.83 | 108.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 93.28 | 69.08 | 116.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.83 | 44.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 185.41 | 119.47 | 35.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.39 | 119.47 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 33.98 | 116.57 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 82.18 | 74.69 | 35.00 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 121.30 | 47.37 | 16.00 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 157.94 | 45.37 | 8.67 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 185.41 | 45.86 | 7.67 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 173.32 | 44.98 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 143.92 | 53.25 | 3.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 101.82 | 61.93 | 13.33 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 59.43 | 56.82 | 13.33 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.24 | 56.23 | 14.67 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.83 | 108.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 93.28 | 69.08 | 116.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.83 | 44.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 185.41 | 119.47 | 35.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.39 | 119.47 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 33.98 | 116.57 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 82.18 | 74.69 | 35.00 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 121.30 | 47.37 | 16.00 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 157.94 | 45.37 | 8.67 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 185.41 | 45.86 | 7.67 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 173.32 | 44.98 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 143.92 | 53.25 | 3.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 101.82 | 61.93 | 13.33 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 59.43 | 56.82 | 13.33 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.24 | 56.23 | 14.67 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.83 | 108.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 93.28 | 69.08 | 116.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.83 | 44.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 185.41 | 119.47 | 35.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.39 | 119.47 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 33.98 | 116.57 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 82.18 | 74.69 | 35.00 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 121.30 | 47.37 | 16.00 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 157.94 | 45.37 | 8.67 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 185.41 | 45.86 | 7.67 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 173.32 | 44.98 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 143.92 | 53.25 | 3.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 101.82 | 61.93 | 13.33 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 59.43 | 56.82 | 13.33 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.24 | 56.23 | 14.67 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.83 | 108.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 93.28 | 69.08 | 116.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.83 | 44.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 185.41 | 119.47 | 35.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.39 | 119.47 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 33.98 | 116.57 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 82.18 | 74.69 | 35.00 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 121.30 | 47.37 | 16.00 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 157.94 | 45.37 | 8.67 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 185.41 | 45.86 | 7.67 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 173.32 | 44.98 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 143.92 | 53.25 | 3.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 101.82 | 61.93 | 13.33 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 59.43 | 56.82 | 13.33 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.24 | 56.23 | 14.67 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.83 | 108.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 93.28 | 69.08 | 116.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.83 | 44.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 185.41 | 119.47 | 35.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.39 | 119.47 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 33.98 | 116.57 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 82.18 | 74.69 | 35.00 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 121.30 | 47.37 | 16.00 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 157.94 | 45.37 | 8.67 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 185.41 | 45.86 | 7.67 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 173.32 | 44.98 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 143.92 | 53.25 | 3.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 101.82 | 61.93 | 13.33 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 59.43 | 56.82 | 13.33 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.24 | 56.23 | 14.67 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.83 | 108.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 93.28 | 69.08 | 116.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.83 | 44.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 185.41 | 119.47 | 35.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.39 | 119.47 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 33.98 | 116.57 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 82.18 | 74.69 | 35.00 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 121.30 | 47.37 | 16.00 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 157.94 | 45.37 | 8.67 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 185.41 | 45.86 | 7.67 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 173.32 | 44.98 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 143.92 | 53.25 | 3.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 101.82 | 61.93 | 13.33 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 59.43 | 56.82 | 13.33 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.24 | 56.23 | 14.67 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.83 | 108.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 93.28 | 69.08 | 116.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.83 | 44.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 185.41 | 119.47 | 35.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.39 | 119.47 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 33.98 | 116.57 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 82.18 | 74.69 | 35.00 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 121.30 | 47.37 | 16.00 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 157.94 | 45.37 | 8.67 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 185.41 | 45.86 | 7.67 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 173.32 | 44.98 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 143.92 | 53.25 | 3.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 101.82 | 61.93 | 13.33 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 59.43 | 56.82 | 13.33 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.24 | 56.23 | 14.67 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.83 | 108.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 93.28 | 69.08 | 116.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.83 | 44.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 185.41 | 119.47 | 35.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.39 | 119.47 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 33.98 | 116.57 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 82.18 | 74.69 | 35.00 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 121.30 | 47.37 | 16.00 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 157.94 | 45.37 | 8.67 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 185.41 | 45.86 | 7.67 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 173.32 | 44.98 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 143.92 | 53.25 | 3.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 101.82 | 61.93 | 13.33 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 59.43 | 56.82 | 13.33 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.24 | 56.23 | 14.67 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.83 | 108.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 93.28 | 69.08 | 116.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.83 | 44.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 185.41 | 119.47 | 35.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.14 | 9.10 | 21.04 | 14.39 | 119.47 | 4.00 | 0.00 | 0.00 |
February | 47.58 | 14.00 | 33.59 | 33.98 | 116.57 | 0.00 | 0.00 | 0.00 |
March | 74.01 | 38.34 | 35.67 | 82.18 | 74.69 | 35.00 | 0.00 | 0.00 |
April | 97.36 | 51.70 | 45.65 | 121.30 | 47.37 | 16.00 | 0.00 | 0.00 |
May | 124.70 | 76.78 | 47.93 | 157.94 | 45.37 | 8.67 | 0.00 | 0.00 |
June | 144.30 | 90.41 | 53.89 | 185.41 | 45.86 | 7.67 | 0.00 | 0.00 |
July | 134.20 | 81.56 | 52.64 | 173.32 | 44.98 | 0.00 | 0.00 | 0.00 |
August | 114.12 | 63.39 | 50.73 | 143.92 | 53.25 | 3.67 | 0.00 | 0.00 |
September | 84.44 | 45.77 | 38.68 | 101.82 | 61.93 | 13.33 | 0.00 | 0.00 |
October | 52.81 | 22.80 | 30.00 | 59.43 | 56.82 | 13.33 | 0.00 | 0.00 |
November | 30.47 | 9.42 | 21.05 | 30.24 | 56.23 | 14.67 | 0.00 | 0.00 |
December | 26.49 | 5.78 | 20.71 | 11.83 | 108.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 42.58 | 37.64 | 93.28 | 69.08 | 116.33 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 5.78 | 20.71 | 11.83 | 44.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.30 | 90.41 | 53.89 | 185.41 | 119.47 | 35.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139919E+09 | 32952487.93 | 0.106966E+09 | 36615419.79 | 0.535158E+09 |
February | 0.204775E+09 | 52848294.32 | 0.151927E+09 | 82800126.91 | 0.450736E+09 |
March | 0.356407E+09 | 0.153211E+09 | 0.203196E+09 | 0.291779E+09 | 0.324590E+09 |
April | 0.419570E+09 | 0.171726E+09 | 0.247844E+09 | 0.412595E+09 | 0.212622E+09 |
May | 0.511831E+09 | 0.231114E+09 | 0.280717E+09 | 0.568432E+09 | 0.163550E+09 |
June | 0.598424E+09 | 0.281536E+09 | 0.316888E+09 | 0.723550E+09 | 0.126765E+09 |
July | 0.552197E+09 | 0.241761E+09 | 0.310436E+09 | 0.710827E+09 | 97141059.02 |
August | 0.498887E+09 | 0.211580E+09 | 0.287307E+09 | 0.629338E+09 | 0.126246E+09 |
September | 0.380150E+09 | 0.164254E+09 | 0.215896E+09 | 0.425232E+09 | 0.186091E+09 |
October | 0.254548E+09 | 89664914.14 | 0.164883E+09 | 0.226260E+09 | 0.240684E+09 |
November | 0.144786E+09 | 41102820.45 | 0.103683E+09 | 90928568.61 | 0.292765E+09 |
December | 0.130516E+09 | 28279684.90 | 0.102236E+09 | 34426511.07 | 0.510001E+09 |
Annual Sum or Average | 0.419201E+10 | 0.170003E+10 | 0.249198E+10 | 0.423279E+10 | 0.326635E+10 |
Minimum of Months | 0.130516E+09 | 28279684.90 | 0.102236E+09 | 34426511.07 | 97141059.02 |
Maximum of Months | 0.598424E+09 | 0.281536E+09 | 0.316888E+09 | 0.723550E+09 | 0.535158E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139919E+09 | 32952487.93 | 0.106966E+09 | 36615419.79 | 0.535158E+09 |
February | 0.204775E+09 | 52848294.32 | 0.151927E+09 | 82800126.91 | 0.450736E+09 |
March | 0.356407E+09 | 0.153211E+09 | 0.203196E+09 | 0.291779E+09 | 0.324590E+09 |
April | 0.419570E+09 | 0.171726E+09 | 0.247844E+09 | 0.412595E+09 | 0.212622E+09 |
May | 0.511831E+09 | 0.231114E+09 | 0.280717E+09 | 0.568432E+09 | 0.163550E+09 |
June | 0.598424E+09 | 0.281536E+09 | 0.316888E+09 | 0.723550E+09 | 0.126765E+09 |
July | 0.552197E+09 | 0.241761E+09 | 0.310436E+09 | 0.710827E+09 | 97141059.02 |
August | 0.498887E+09 | 0.211580E+09 | 0.287307E+09 | 0.629338E+09 | 0.126246E+09 |
September | 0.380150E+09 | 0.164254E+09 | 0.215896E+09 | 0.425232E+09 | 0.186091E+09 |
October | 0.254548E+09 | 89664914.14 | 0.164883E+09 | 0.226260E+09 | 0.240684E+09 |
November | 0.144786E+09 | 41102820.45 | 0.103683E+09 | 90928568.61 | 0.292765E+09 |
December | 0.130516E+09 | 28279684.90 | 0.102236E+09 | 34426511.07 | 0.510001E+09 |
Annual Sum or Average | 0.419201E+10 | 0.170003E+10 | 0.249198E+10 | 0.423279E+10 | 0.326635E+10 |
Minimum of Months | 0.130516E+09 | 28279684.90 | 0.102236E+09 | 34426511.07 | 97141059.02 |
Maximum of Months | 0.598424E+09 | 0.281536E+09 | 0.316888E+09 | 0.723550E+09 | 0.535158E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51883723.12 | 0.00 | 51883723.12 | 488281.26 | 0.333323E+09 |
February | 71401207.49 | 0.00 | 71401207.49 | 3065720.45 | 0.280719E+09 |
March | 95882380.03 | 3395.69 | 95878984.34 | 32543024.66 | 0.207069E+09 |
April | 0.118292E+09 | 570344.86 | 0.117722E+09 | 69376632.56 | 0.126909E+09 |
May | 0.141998E+09 | 6114251.01 | 0.135883E+09 | 0.112998E+09 | 90454457.76 |
June | 0.165215E+09 | 14048294.05 | 0.151167E+09 | 0.166817E+09 | 68588119.22 |
July | 0.159000E+09 | 10816116.12 | 0.148184E+09 | 0.186548E+09 | 52260422.40 |
August | 0.137658E+09 | 2657383.74 | 0.135001E+09 | 0.150086E+09 | 71153956.80 |
September | 0.100967E+09 | 44682.67 | 0.100922E+09 | 81468229.00 | 0.110898E+09 |
October | 77956163.66 | 0.00 | 77956163.66 | 38070795.39 | 0.145485E+09 |
November | 50694748.92 | 0.00 | 50694748.92 | 12512819.01 | 0.176541E+09 |
December | 48561592.26 | 0.00 | 48561592.26 | 683148.79 | 0.313624E+09 |
Annual Sum or Average | 0.121951E+10 | 34254468.14 | 0.118526E+10 | 0.854658E+09 | 0.197703E+10 |
Minimum of Months | 48561592.26 | 0.00 | 48561592.26 | 488281.26 | 52260422.40 |
Maximum of Months | 0.165215E+09 | 14048294.05 | 0.151167E+09 | 0.186548E+09 | 0.333323E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51881948.64 | 0.00 | 51881948.64 | 488146.61 | 0.333325E+09 |
February | 71398776.49 | 0.00 | 71398776.49 | 3064990.03 | 0.280720E+09 |
March | 95879392.80 | 3395.53 | 95875997.27 | 32540756.54 | 0.207070E+09 |
April | 0.118289E+09 | 570318.12 | 0.117718E+09 | 69372942.67 | 0.126909E+09 |
May | 0.141994E+09 | 6113964.42 | 0.135880E+09 | 0.112993E+09 | 90454192.38 |
June | 0.165210E+09 | 14047635.58 | 0.151163E+09 | 0.166811E+09 | 68587639.72 |
July | 0.158995E+09 | 10815609.16 | 0.148180E+09 | 0.186542E+09 | 52259884.44 |
August | 0.137654E+09 | 2657259.19 | 0.134996E+09 | 0.150081E+09 | 71153497.35 |
September | 0.100964E+09 | 44680.58 | 0.100919E+09 | 81464928.87 | 0.110897E+09 |
October | 77953629.82 | 0.00 | 77953629.82 | 38068474.69 | 0.145484E+09 |
November | 50693011.42 | 0.00 | 50693011.42 | 12511851.98 | 0.176541E+09 |
December | 48559892.96 | 0.00 | 48559892.96 | 683016.52 | 0.313625E+09 |
Annual Sum or Average | 0.121947E+10 | 34252862.59 | 0.118522E+10 | 0.854622E+09 | 0.197703E+10 |
Minimum of Months | 48559892.96 | 0.00 | 48559892.96 | 488146.61 | 52259884.44 |
Maximum of Months | 0.165210E+09 | 14047635.58 | 0.151163E+09 | 0.186542E+09 | 0.333325E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38554001.43 | 0.319986E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82194909.76 | 0.281997E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.220100E+09 | 0.200051E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.314406E+09 | 0.122792E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.423034E+09 | 0.121515E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.480576E+09 | 0.118882E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.464226E+09 | 0.120477E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.385487E+09 | 0.142623E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.263927E+09 | 0.160526E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.159173E+09 | 0.152197E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 78370725.22 | 0.145737E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31680599.05 | 0.291688E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.294173E+10 | 0.217847E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31680599.05 | 0.118882E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.480576E+09 | 0.319986E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38554001.43 | 0.319986E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82194909.76 | 0.281997E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.220100E+09 | 0.200051E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.314406E+09 | 0.122792E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.423034E+09 | 0.121515E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.480576E+09 | 0.118882E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.464226E+09 | 0.120477E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.385487E+09 | 0.142623E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.263927E+09 | 0.160526E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.159173E+09 | 0.152197E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 78370725.22 | 0.145737E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31680599.05 | 0.291688E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.294173E+10 | 0.217847E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31680599.05 | 0.118882E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.480576E+09 | 0.319986E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38554001.43 | 0.319986E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82194909.76 | 0.281997E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.220100E+09 | 0.200051E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.314406E+09 | 0.122792E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.423034E+09 | 0.121515E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.480576E+09 | 0.118882E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.464226E+09 | 0.120477E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.385487E+09 | 0.142623E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.263927E+09 | 0.160526E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.159173E+09 | 0.152197E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 78370725.22 | 0.145737E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31680599.05 | 0.291688E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.294173E+10 | 0.217847E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31680599.05 | 0.118882E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.480576E+09 | 0.319986E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38554001.43 | 0.319986E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82194909.76 | 0.281997E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.220100E+09 | 0.200051E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.314406E+09 | 0.122792E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.423034E+09 | 0.121515E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.480576E+09 | 0.118882E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.464226E+09 | 0.120477E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.385487E+09 | 0.142623E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.263927E+09 | 0.160526E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.159173E+09 | 0.152197E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 78370725.22 | 0.145737E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31680599.05 | 0.291688E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.294173E+10 | 0.217847E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31680599.05 | 0.118882E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.480576E+09 | 0.319986E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38554001.43 | 0.319986E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82194909.76 | 0.281997E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.220100E+09 | 0.200051E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.314406E+09 | 0.122792E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.423034E+09 | 0.121515E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.480576E+09 | 0.118882E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.464226E+09 | 0.120477E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.385487E+09 | 0.142623E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.263927E+09 | 0.160526E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.159173E+09 | 0.152197E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 78370725.22 | 0.145737E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31680599.05 | 0.291688E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.294173E+10 | 0.217847E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31680599.05 | 0.118882E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.480576E+09 | 0.319986E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38554001.43 | 0.319986E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82194909.76 | 0.281997E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.220100E+09 | 0.200051E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.314406E+09 | 0.122792E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.423034E+09 | 0.121515E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.480576E+09 | 0.118882E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.464226E+09 | 0.120477E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.385487E+09 | 0.142623E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.263927E+09 | 0.160526E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.159173E+09 | 0.152197E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 78370725.22 | 0.145737E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31680599.05 | 0.291688E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.294173E+10 | 0.217847E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31680599.05 | 0.118882E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.480576E+09 | 0.319986E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38554001.43 | 0.319986E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82194909.76 | 0.281997E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.220100E+09 | 0.200051E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.314406E+09 | 0.122792E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.423034E+09 | 0.121515E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.480576E+09 | 0.118882E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.464226E+09 | 0.120477E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.385487E+09 | 0.142623E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.263927E+09 | 0.160526E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.159173E+09 | 0.152197E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 78370725.22 | 0.145737E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31680599.05 | 0.291688E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.294173E+10 | 0.217847E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31680599.05 | 0.118882E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.480576E+09 | 0.319986E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38554001.43 | 0.319986E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82194909.76 | 0.281997E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.220100E+09 | 0.200051E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.314406E+09 | 0.122792E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.423034E+09 | 0.121515E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.480576E+09 | 0.118882E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.464226E+09 | 0.120477E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.385487E+09 | 0.142623E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.263927E+09 | 0.160526E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.159173E+09 | 0.152197E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 78370725.22 | 0.145737E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31680599.05 | 0.291688E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.294173E+10 | 0.217847E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31680599.05 | 0.118882E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.480576E+09 | 0.319986E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38554001.43 | 0.319986E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82194909.76 | 0.281997E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.220100E+09 | 0.200051E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.314406E+09 | 0.122792E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.423034E+09 | 0.121515E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.480576E+09 | 0.118882E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.464226E+09 | 0.120477E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.385487E+09 | 0.142623E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.263927E+09 | 0.160526E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.159173E+09 | 0.152197E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 78370725.22 | 0.145737E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31680599.05 | 0.291688E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.294173E+10 | 0.217847E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31680599.05 | 0.118882E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.480576E+09 | 0.319986E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80722398.66 | 24379665.69 | 56342732.98 | 38554001.43 | 0.319986E+09 |
February | 0.115117E+09 | 33859131.17 | 81258062.49 | 82194909.76 | 0.281997E+09 |
March | 0.198222E+09 | 0.102696E+09 | 95525801.06 | 0.220100E+09 | 0.200051E+09 |
April | 0.252350E+09 | 0.134015E+09 | 0.118336E+09 | 0.314406E+09 | 0.122792E+09 |
May | 0.334006E+09 | 0.205635E+09 | 0.128371E+09 | 0.423034E+09 | 0.121515E+09 |
June | 0.374019E+09 | 0.234332E+09 | 0.139687E+09 | 0.480576E+09 | 0.118882E+09 |
July | 0.359440E+09 | 0.218440E+09 | 0.141000E+09 | 0.464226E+09 | 0.120477E+09 |
August | 0.305652E+09 | 0.169775E+09 | 0.135877E+09 | 0.385487E+09 | 0.142623E+09 |
September | 0.218878E+09 | 0.118627E+09 | 0.100250E+09 | 0.263927E+09 | 0.160526E+09 |
October | 0.141444E+09 | 61079625.33 | 80363913.04 | 0.159173E+09 | 0.152197E+09 |
November | 78983626.23 | 24420837.30 | 54562788.92 | 78370725.22 | 0.145737E+09 |
December | 70953841.62 | 15470848.43 | 55482993.18 | 31680599.05 | 0.291688E+09 |
Annual Sum or Average | 0.252979E+10 | 0.134273E+10 | 0.118706E+10 | 0.294173E+10 | 0.217847E+10 |
Minimum of Months | 70953841.62 | 15470848.43 | 54562788.92 | 31680599.05 | 0.118882E+09 |
Maximum of Months | 0.374019E+09 | 0.234332E+09 | 0.141000E+09 | 0.480576E+09 | 0.319986E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 19.85 | 640.65 | 143.22 | 24.61 | 118.61 | 0.00 | 0.00 |
February | 60.95 | 594.67 | 228.32 | 43.69 | 184.63 | 0.00 | 0.00 |
March | 230.67 | 385.50 | 337.73 | 114.41 | 223.32 | 0.00 | 0.00 |
April | 369.00 | 259.09 | 415.02 | 132.94 | 282.07 | 0.00 | 0.00 |
May | 507.28 | 188.12 | 488.22 | 177.14 | 311.08 | 0.00 | 0.00 |
June | 683.33 | 147.05 | 589.23 | 228.07 | 361.15 | 0.00 | 0.00 |
July | 667.16 | 108.64 | 531.06 | 188.60 | 342.46 | 0.00 | 0.00 |
August | 581.16 | 146.55 | 475.32 | 159.97 | 315.34 | 0.00 | 0.00 |
September | 389.07 | 227.26 | 371.23 | 126.77 | 244.46 | 0.00 | 0.00 |
October | 194.56 | 285.54 | 248.28 | 66.95 | 181.33 | 0.00 | 0.00 |
November | 75.99 | 358.29 | 150.83 | 31.72 | 119.12 | 0.00 | 0.00 |
December | 19.23 | 608.03 | 133.72 | 21.12 | 112.60 | 0.00 | 0.00 |
Annual Sum or Average | 317.93 | 327.82 | 343.20 | 109.99 | 233.21 | 0.00 | 0.00 |
Minimum of Months | 19.23 | 108.64 | 133.72 | 21.12 | 112.60 | 0.00 | 0.00 |
Maximum of Months | 683.33 | 640.65 | 589.23 | 228.07 | 361.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 607.05 | 11628.03 | 301.38 | 91.02 | 210.36 | 0.00 | 0.00 |
February | 1263.71 | 12612.10 | 475.85 | 139.96 | 335.89 | 0.00 | 0.00 |
March | 2957.07 | 6589.66 | 740.08 | 383.42 | 356.65 | 0.00 | 0.00 |
April | 4181.95 | 2613.54 | 973.57 | 517.03 | 456.54 | 0.00 | 0.00 |
May | 5391.61 | 1494.32 | 1247.04 | 767.75 | 479.28 | 0.00 | 0.00 |
June | 7174.11 | 1723.72 | 1442.98 | 904.06 | 538.92 | 0.00 | 0.00 |
July | 9054.73 | 2123.48 | 1341.99 | 815.56 | 526.43 | 0.00 | 0.00 |
August | 6923.36 | 2476.74 | 1141.17 | 633.87 | 507.31 | 0.00 | 0.00 |
September | 3470.49 | 2186.81 | 844.44 | 457.67 | 386.77 | 0.00 | 0.00 |
October | 1890.89 | 2383.46 | 528.09 | 228.05 | 300.04 | 0.00 | 0.00 |
November | 1022.26 | 3445.53 | 304.72 | 94.22 | 210.50 | 0.00 | 0.00 |
December | 508.87 | 10169.62 | 264.91 | 57.76 | 207.15 | 0.00 | 0.00 |
Annual Sum or Average | 3721.07 | 4917.95 | 802.19 | 425.78 | 376.41 | 0.00 | 0.00 |
Minimum of Months | 508.87 | 1494.32 | 264.91 | 57.76 | 207.15 | 0.00 | 0.00 |
Maximum of Months | 9054.73 | 12612.10 | 1442.98 | 904.06 | 538.92 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 53154913.69 | 0.171591E+10 | 0.383603E+09 | 65904975.85 | 0.317698E+09 | 0.00 | 0.00 |
February | 0.147441E+09 | 0.143862E+10 | 0.552350E+09 | 0.105697E+09 | 0.446653E+09 | 0.00 | 0.00 |
March | 0.617834E+09 | 0.103251E+10 | 0.904575E+09 | 0.306429E+09 | 0.598146E+09 | 0.00 | 0.00 |
April | 0.956443E+09 | 0.671566E+09 | 0.107572E+10 | 0.344592E+09 | 0.731128E+09 | 0.00 | 0.00 |
May | 0.135870E+10 | 0.503851E+09 | 0.130765E+10 | 0.474456E+09 | 0.833198E+09 | 0.00 | 0.00 |
June | 0.177118E+10 | 0.381158E+09 | 0.152727E+10 | 0.591168E+09 | 0.936105E+09 | 0.00 | 0.00 |
July | 0.178693E+10 | 0.290990E+09 | 0.142239E+10 | 0.505155E+09 | 0.917235E+09 | 0.00 | 0.00 |
August | 0.155657E+10 | 0.392528E+09 | 0.127309E+10 | 0.428475E+09 | 0.844611E+09 | 0.00 | 0.00 |
September | 0.100847E+10 | 0.589052E+09 | 0.962232E+09 | 0.328598E+09 | 0.633634E+09 | 0.00 | 0.00 |
October | 0.521102E+09 | 0.764780E+09 | 0.665005E+09 | 0.179330E+09 | 0.485675E+09 | 0.00 | 0.00 |
November | 0.196971E+09 | 0.928700E+09 | 0.390959E+09 | 82205640.90 | 0.308753E+09 | 0.00 | 0.00 |
December | 51511266.65 | 0.162854E+10 | 0.358153E+09 | 56559369.81 | 0.301594E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100263E+11 | 0.103382E+11 | 0.108230E+11 | 0.346857E+10 | 0.735443E+10 | 0.00 | 0.00 |
Minimum of Months | 51511266.65 | 0.290990E+09 | 0.358153E+09 | 56559369.81 | 0.301594E+09 | 0.00 | 0.00 |
Maximum of Months | 0.178693E+10 | 0.171591E+10 | 0.152727E+10 | 0.591168E+09 | 0.936105E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.162593E+10 | 0.311445E+11 | 0.807224E+09 | 0.243797E+09 | 0.563427E+09 | 0.00 | 0.00 |
February | 0.305716E+10 | 0.305112E+11 | 0.115117E+10 | 0.338591E+09 | 0.812581E+09 | 0.00 | 0.00 |
March | 0.792020E+10 | 0.176497E+11 | 0.198222E+10 | 0.102696E+10 | 0.955258E+09 | 0.00 | 0.00 |
April | 0.108396E+11 | 0.677429E+10 | 0.252350E+10 | 0.134015E+10 | 0.118336E+10 | 0.00 | 0.00 |
May | 0.144409E+11 | 0.400239E+10 | 0.334006E+10 | 0.205635E+10 | 0.128371E+10 | 0.00 | 0.00 |
June | 0.185953E+11 | 0.446787E+10 | 0.374019E+10 | 0.234332E+10 | 0.139687E+10 | 0.00 | 0.00 |
July | 0.242522E+11 | 0.568752E+10 | 0.359440E+10 | 0.218440E+10 | 0.141000E+10 | 0.00 | 0.00 |
August | 0.185435E+11 | 0.663371E+10 | 0.305652E+10 | 0.169775E+10 | 0.135877E+10 | 0.00 | 0.00 |
September | 0.899552E+10 | 0.566822E+10 | 0.218878E+10 | 0.118627E+10 | 0.100250E+10 | 0.00 | 0.00 |
October | 0.506456E+10 | 0.638386E+10 | 0.141444E+10 | 0.610796E+09 | 0.803639E+09 | 0.00 | 0.00 |
November | 0.264969E+10 | 0.893081E+10 | 0.789836E+09 | 0.244208E+09 | 0.545628E+09 | 0.00 | 0.00 |
December | 0.136297E+10 | 0.272383E+11 | 0.709538E+09 | 0.154708E+09 | 0.554830E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.117348E+12 | 0.155092E+12 | 0.252979E+11 | 0.134273E+11 | 0.118706E+11 | 0.00 | 0.00 |
Minimum of Months | 0.136297E+10 | 0.400239E+10 | 0.709538E+09 | 0.154708E+09 | 0.545628E+09 | 0.00 | 0.00 |
Maximum of Months | 0.242522E+11 | 0.311445E+11 | 0.374019E+10 | 0.234332E+10 | 0.141000E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.108031E+10 | -922984524.9 | 0.00 | 0.00 | 744.00 | 0.00 | -157325789.2 | 58.99 | 0.00 | 0.00 |
February | 0.100224E+10 | -860088498.5 | 0.00 | 0.00 | 672.00 | 0.00 | -142146581.3 | 58.99 | 0.00 | 0.00 |
March | 0.114616E+10 | -991517960.2 | 0.00 | 0.00 | 744.00 | 0.00 | -154642381.8 | 58.99 | 0.00 | 0.00 |
April | 0.103236E+10 | -884831655.4 | 0.00 | 0.00 | 720.00 | 0.00 | -147523711.4 | 58.99 | 0.00 | 0.00 |
May | 0.100973E+10 | -868056774.3 | 0.00 | 0.00 | 744.00 | 0.00 | -141676072.9 | 58.99 | 0.00 | 0.00 |
June | 0.940848E+09 | -811339783.3 | 0.00 | 0.00 | 720.00 | 0.00 | -129507753.4 | 58.99 | 0.00 | 0.00 |
July | 0.877590E+09 | -745934271.4 | 0.00 | 0.00 | 744.00 | 0.00 | -131655729.6 | 59.00 | 0.00 | 0.00 |
August | 0.918564E+09 | -786007806.4 | 0.00 | 0.00 | 744.00 | 0.00 | -132556609.7 | 58.99 | 0.00 | 0.00 |
September | 0.874248E+09 | -744056934.8 | 0.00 | 0.00 | 720.00 | 0.00 | -130191170.8 | 58.99 | 0.00 | 0.00 |
October | 0.931307E+09 | -783079164.5 | 0.00 | 0.00 | 744.00 | 0.00 | -148227505.2 | 58.99 | 0.00 | 0.00 |
November | 0.950817E+09 | -800539821.1 | 0.00 | 0.00 | 720.00 | 0.00 | -150277089.0 | 58.99 | 0.00 | 0.00 |
December | 0.104142E+10 | -884021761.0 | 0.00 | 0.00 | 744.00 | 0.00 | -157401705.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.118056E+11 | -0.100825E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.172313E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.874248E+09 | -991517960.2 | 0.00 | 0.00 | 672.00 | 0.00 | -157401705.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.114616E+10 | -744056934.8 | 0.00 | 0.00 | 744.00 | 0.00 | -129507753.4 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 255.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 262.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 339.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 371.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 332.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 430.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 439.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 289.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 314.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 258.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3928.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 439.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.151422E+11 | 31258.88 | 02-JAN-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146435E+11 | 31258.88 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.856853E+10 | 31258.88 | 01-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.369742E+10 | 31258.88 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.546773E+09 | 31258.88 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 24180242.23 | 7582.82 | 14-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 50942935.27 | 30947.07 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150946E+10 | 31258.88 | 03-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.474343E+10 | 31258.88 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134964E+11 | 31258.88 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.624228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.151422E+11 | 31258.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.560839E+11 | 112244.80 | 01-JAN-00:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.579562E+11 | 112244.80 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.269292E+11 | 112244.80 | 01-MAR-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.820181E+10 | 112244.80 | 04-APR-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15903121.64 | 58700.17 | 01-MAY-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.240705E+10 | 112244.80 | 17-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146790E+11 | 112244.80 | 03-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.540005E+11 | 112244.80 | 02-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.220274E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.579562E+11 | 112244.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.180124E+12 | 226112.21 | 12-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.186178E+12 | 230789.87 | 06-FEB-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.663871E+11 | 122688.80 | 05-MAR-00:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.890200E+10 | 80762.69 | 16-APR-06:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35489934.12 | 12591.93 | 30-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178805E+11 | 50134.40 | 25-NOV-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169653E+12 | 191288.20 | 09-DEC-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.629160E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.186178E+12 | 230789.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.164996E+09 | 0.143809E+09 | 4914.07 | 15-MAR-15:10 | 4555.19 | 0.00 |
April | 0.00 | 0.00 | 82755858.13 | 81263069.67 | 2728.07 | 08-APR-14:20 | 2592.61 | 0.00 |
May | 0.00 | 0.00 | 0.163799E+10 | 0.153935E+10 | 10302.23 | 27-MAY-17:15 | 10302.23 | 0.00 |
June | 0.00 | 0.00 | 0.723500E+10 | 0.602927E+10 | 25396.27 | 18-JUN-23:02 | 17779.75 | 0.00 |
July | 0.00 | 0.00 | 0.119537E+11 | 0.935468E+10 | 27035.65 | 16-JUL-23:01 | 17609.34 | 0.00 |
August | 0.00 | 0.00 | 0.107179E+11 | 0.900366E+10 | 27930.19 | 13-AUG-23:01 | 15657.42 | 0.00 |
September | 0.00 | 0.00 | 0.520683E+10 | 0.444309E+10 | 23707.61 | 16-SEP-17:43 | 19476.89 | 0.00 |
October | 0.00 | 0.00 | 0.398954E+09 | 0.366383E+09 | 4851.74 | 11-OCT-16:00 | 4521.22 | 0.00 |
November | 0.00 | 0.00 | 254713.00 | 210573.53 | 344.13 | 04-NOV-15:00 | 284.53 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.373984E+11 | 0.309617E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.119537E+11 | 0.935468E+10 | 27930.19 | 19476.89 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.298205E+09 | 0.280755E+09 | 11998.88 | 27-MAY-15:00 | 11998.88 | 0.00 |
June | 0.00 | 0.00 | 0.990066E+10 | 0.766394E+10 | 74612.84 | 27-JUN-17:08 | 47583.47 | 0.00 |
July | 0.00 | 0.00 | 0.258095E+11 | 0.192262E+11 | 89913.43 | 16-JUL-10:03 | 57566.33 | 0.00 |
August | 0.00 | 0.00 | 0.194309E+11 | 0.159676E+11 | 85996.89 | 13-AUG-12:23 | 62243.01 | 0.00 |
September | 0.00 | 0.00 | 0.386972E+10 | 0.300788E+10 | 32263.22 | 16-SEP-13:40 | 25536.56 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.593089E+11 | 0.461464E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.258095E+11 | 0.192262E+11 | 89913.43 | 62243.01 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138227E+10 | 0.08 | 537.34 | 01-JAN-00:02 | 0.08 |
February | 0.124710E+10 | 0.08 | 537.34 | 01-FEB-00:02 | 0.08 |
March | 0.792382E+09 | 0.04 | 537.34 | 01-MAR-00:02 | 0.08 |
April | 0.195805E+09 | 0.01 | 537.34 | 01-APR-01:45 | 0.08 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 2579210.83 | 0.00 | 537.34 | 30-OCT-04:50 | 0.08 |
November | 0.498078E+09 | 0.03 | 537.34 | 03-NOV-00:30 | 0.08 |
December | 0.136279E+10 | 0.07 | 537.34 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.548101E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.138227E+10 | 0.08 | 537.34 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.163870E+10 | 0.78 | 1364.20 | 02-JAN-09:30 | 0.96 |
February | 0.152443E+10 | 0.79 | 1364.20 | 01-FEB-14:40 | 0.96 |
March | 0.159832E+10 | 0.61 | 1364.20 | 03-MAR-15:30 | 0.96 |
April | 0.141020E+10 | 0.46 | 1364.20 | 01-APR-08:40 | 0.96 |
May | 0.141925E+10 | 0.39 | 1364.20 | 04-MAY-13:40 | 0.96 |
June | 0.147979E+10 | 0.49 | 1364.20 | 05-JUN-15:00 | 0.95 |
July | 0.153220E+10 | 0.59 | 1364.20 | 01-JUL-06:50 | 0.95 |
August | 0.160632E+10 | 0.60 | 1364.20 | 01-AUG-13:30 | 0.95 |
September | 0.138710E+10 | 0.42 | 1364.20 | 01-SEP-14:10 | 0.95 |
October | 0.137262E+10 | 0.38 | 1364.20 | 16-OCT-16:50 | 0.96 |
November | 0.135570E+10 | 0.46 | 1364.20 | 02-NOV-06:20 | 0.96 |
December | 0.159655E+10 | 0.75 | 1364.20 | 04-DEC-12:00 | 0.96 |
Annual Sum or Average | 0.179212E+11 | 0.56 | |||
Minimum of Months | 0.135570E+10 | 0.38 | 1364.20 | 0.95 | |
Maximum of Months | 0.163870E+10 | 0.79 | 1364.20 | 0.96 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.505454E+10 | 0.83 | 3653.47 | 12-JAN-14:10 | 0.93 |
February | 0.482390E+10 | 0.82 | 3653.47 | 14-FEB-10:20 | 0.93 |
March | 0.469720E+10 | 0.73 | 3653.47 | 02-MAR-09:40 | 0.92 |
April | 0.389609E+10 | 0.55 | 3653.47 | 11-APR-06:20 | 0.92 |
May | 0.376223E+10 | 0.35 | 3653.47 | 23-MAY-15:30 | 0.92 |
June | 0.379808E+10 | 0.39 | 3653.47 | 02-JUN-08:30 | 0.91 |
July | 0.377856E+10 | 0.43 | 3653.47 | 01-JUL-06:05 | 0.91 |
August | 0.399046E+10 | 0.42 | 3653.47 | 01-AUG-06:05 | 0.91 |
September | 0.361775E+10 | 0.35 | 3653.47 | 15-SEP-14:20 | 0.91 |
October | 0.370312E+10 | 0.42 | 3653.47 | 02-OCT-06:05 | 0.92 |
November | 0.396258E+10 | 0.69 | 3653.47 | 01-NOV-06:10 | 0.92 |
December | 0.502206E+10 | 0.82 | 3653.47 | 04-DEC-10:10 | 0.92 |
Annual Sum or Average | 0.501066E+11 | 0.57 | |||
Minimum of Months | 0.361775E+10 | 0.35 | 3653.47 | 0.91 | |
Maximum of Months | 0.505454E+10 | 0.83 | 3653.47 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.163870E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.152443E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.164356E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.143295E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.186215E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.339449E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.468434E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.444389E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.276571E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.148119E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.135577E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.159655E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.278237E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.135577E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.468434E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.505454E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.482390E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.469720E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.389609E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.385116E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.666275E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.112150E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.964821E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.473680E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.370312E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.396258E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.502206E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.672734E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.370312E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.112150E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.163870E+10 | 0.00 | 0.151422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152443E+10 | 0.00 | 0.146435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159832E+10 | 0.164996E+09 | 0.856853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141020E+10 | 82755858.13 | 0.369742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141925E+10 | 0.163799E+10 | 0.546773E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147979E+10 | 0.723500E+10 | 24180242.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153220E+10 | 0.119537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160632E+10 | 0.107179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138710E+10 | 0.520683E+10 | 50942935.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137262E+10 | 0.398954E+09 | 0.150946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135570E+10 | 254713.00 | 0.474343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159655E+10 | 0.00 | 0.134964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179212E+11 | 0.373984E+11 | 0.624228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.163870E+10 | 0.119537E+11 | 0.151422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.505454E+10 | 0.00 | 0.560839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.482390E+10 | 0.00 | 0.579562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.469720E+10 | 0.00 | 0.269292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.389609E+10 | 0.00 | 0.820181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.376223E+10 | 0.298205E+09 | 15903121.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.379808E+10 | 0.990066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.377856E+10 | 0.258095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.399046E+10 | 0.194309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.361775E+10 | 0.386972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.370312E+10 | 0.00 | 0.240705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.396258E+10 | 0.00 | 0.146790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.502206E+10 | 0.00 | 0.540005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.501066E+11 | 0.593089E+11 | 0.220274E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.361775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.505454E+10 | 0.258095E+11 | 0.579562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.163870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159832E+10 | 0.00 | 0.00 | 0.00 | 45246340.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141020E+10 | 0.00 | 0.00 | 0.00 | 22746503.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141925E+10 | 0.00 | 0.00 | 0.00 | 0.442896E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147979E+10 | 0.00 | 0.00 | 0.00 | 0.191470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153220E+10 | 0.00 | 0.00 | 0.00 | 0.315214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160632E+10 | 0.00 | 0.00 | 0.00 | 0.283757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138710E+10 | 0.00 | 0.00 | 0.00 | 0.137861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137262E+10 | 0.00 | 0.00 | 0.00 | 0.108569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135570E+10 | 0.00 | 0.00 | 0.00 | 70426.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179212E+11 | 0.00 | 0.00 | 0.00 | 0.990254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.163870E+10 | 0.00 | 0.00 | 0.00 | 0.315214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.505454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.482390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.469720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.389609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.376223E+10 | 0.00 | 0.00 | 0.00 | 88930680.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.379808E+10 | 0.00 | 0.00 | 0.00 | 0.286466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.377856E+10 | 0.00 | 0.00 | 0.00 | 0.743647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.399046E+10 | 0.00 | 0.00 | 0.00 | 0.565775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.361775E+10 | 0.00 | 0.00 | 0.00 | 0.111905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.370312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.396258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.502206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.501066E+11 | 0.00 | 0.00 | 0.00 | 0.171669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.361775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.505454E+10 | 0.00 | 0.00 | 0.00 | 0.743647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358789E+10 | 0.00 | 0.00 | 0.16 |
February | 417368.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341990E+10 | 0.00 | 3407.61 | 0.16 |
March | 0.135881E+09 | 257414.78 | 0.00 | 95947.36 | 0.00 | 0.250616E+10 | 21292624.82 | 0.00 | 0.16 |
April | 0.503298E+09 | 0.00 | 0.00 | 80524.96 | 0.00 | 0.122331E+10 | 64660161.21 | 0.00 | 0.15 |
May | 0.532998E+09 | 4383352.45 | 0.00 | 1996256.45 | 0.00 | 0.173245E+09 | 0.534495E+09 | 0.00 | 0.14 |
June | 0.101589E+09 | 0.272391E+09 | 0.00 | 5294161.92 | 98826.57 | 19614286.11 | 0.501113E+09 | 0.00 | 0.16 |
July | 20993497.62 | 0.824467E+09 | 0.00 | 3506363.64 | 143221.78 | 0.00 | 98920256.76 | 0.00 | 0.16 |
August | 46655308.68 | 0.411472E+09 | 0.00 | 7053435.10 | 2310.23 | 0.00 | 0.233938E+09 | 0.00 | 0.16 |
September | 0.166229E+09 | 0.123343E+09 | 0.00 | 4538557.15 | 101047.03 | 32176063.15 | 0.549209E+09 | 0.00 | 0.15 |
October | 0.798925E+09 | 0.00 | 0.00 | 480702.82 | 0.00 | 0.582883E+09 | 0.220319E+09 | 0.00 | 0.14 |
November | 0.228162E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167378E+10 | 0.00 | 28956.85 | 0.14 |
December | 12672508.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331846E+10 | 0.00 | 0.00 | 0.16 |
Annual Sum or Average | 0.254782E+10 | 0.163631E+10 | 0.00 | 23045949.40 | 345405.60 | 0.165374E+11 | 0.222395E+10 | 32364.46 | 0.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.798925E+09 | 0.824467E+09 | 0.00 | 7053435.10 | 143221.78 | 0.358789E+10 | 0.549209E+09 | 28956.85 | 0.16 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.130234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.737003E+10 | 0.00 | 0.00 | 0.17 |
February | 0.164313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655061E+10 | 0.00 | 0.00 | 0.17 |
March | 0.411600E+10 | 0.00 | 0.00 | 0.00 | 2245943.51 | 0.249656E+10 | 0.00 | 0.00 | 0.19 |
April | 0.440211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331432E+09 | 0.00 | 0.00 | 0.18 |
May | 0.413577E+10 | 0.00 | 0.00 | 668673.24 | 0.00 | 0.00 | 0.650287E+09 | 0.00 | 0.20 |
June | 0.145030E+10 | 0.444470E+09 | 0.00 | 8442088.46 | 0.00 | 0.00 | 0.396702E+10 | 0.00 | 0.31 |
July | 95791264.50 | 0.151912E+10 | 0.00 | 9417468.06 | 0.00 | 0.00 | 0.221566E+10 | 0.00 | 0.27 |
August | 0.381904E+09 | 0.678310E+09 | 0.00 | 18208751.55 | 0.00 | 0.00 | 0.362017E+10 | 0.00 | 0.30 |
September | 0.196245E+10 | 0.100196E+09 | 0.00 | 5550834.88 | 0.00 | 0.00 | 0.355612E+10 | 0.00 | 0.29 |
October | 0.460286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76250999.21 | 0.00 | 0.00 | 0.18 |
November | 0.393510E+10 | 0.00 | 0.00 | 0.00 | 249581.84 | 0.799178E+09 | 0.00 | 0.00 | 0.17 |
December | 0.160040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646530E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.296281E+11 | 0.274209E+10 | 0.00 | 42287816.18 | 2495525.35 | 0.240894E+11 | 0.140093E+11 | 0.00 | 0.22 |
Minimum of Months | 95791264.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.460286E+10 | 0.151912E+10 | 0.00 | 18208751.55 | 2245943.51 | 0.737003E+10 | 0.396702E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:43
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.257861E+12 | 0.181290E+12 | 0.00 | 0.138916E+11 | 0.785889E+11 |
February | 0.438549E+12 | 0.197449E+12 | 0.00 | 0.130531E+11 | 0.794859E+11 |
March | 0.706908E+12 | 0.105612E+12 | 0.00 | 0.109504E+11 | 0.337467E+11 |
April | 0.861785E+12 | 0.674204E+11 | 0.00 | 0.834410E+10 | 0.803674E+10 |
May | 0.110038E+13 | 0.529707E+11 | 0.00 | 0.767621E+10 | 0.272849E+10 |
June | 0.122230E+13 | 0.562477E+11 | 0.00 | 0.627950E+10 | 0.219279E+11 |
July | 0.115593E+13 | 0.510848E+11 | 0.00 | 0.324847E+09 | 0.483518E+11 |
August | 0.983556E+12 | 0.561190E+11 | 0.00 | 0.371846E+10 | 0.386441E+11 |
September | 0.725505E+12 | 0.519570E+11 | 0.00 | 0.749791E+10 | 0.115996E+11 |
October | 0.455910E+12 | 0.577238E+11 | 0.00 | 0.832912E+10 | 0.241988E+10 |
November | 0.206196E+12 | 0.666352E+11 | 0.00 | 0.849575E+10 | 0.139082E+11 |
December | 0.220137E+12 | 0.184007E+12 | 0.00 | 0.130194E+11 | 0.740814E+11 |
Annual Sum or Average | 0.833502E+13 | 0.112852E+13 | 0.00 | 0.101580E+12 | 0.413520E+12 |
Minimum of Months | 0.206196E+12 | 0.510848E+11 | 0.00 | 0.324847E+09 | 0.241988E+10 |
Maximum of Months | 0.122230E+13 | 0.197449E+12 | 0.00 | 0.138916E+11 | 0.794859E+11 |