Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2023-10-16 10:43:06
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 345.79 | 71.52 | 71.52 |
Net Site Energy | 345.79 | 71.52 | 71.52 |
Total Source Energy | 1087.63 | 224.94 | 224.94 |
Net Source Energy | 1087.63 | 224.94 | 224.94 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 3.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 9.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 84.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 25.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 342.19 | 3.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 3.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 9.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 84.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 61.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 25.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 24.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 3.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 9.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 84.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 61.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 25.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 24.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 30.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 12.30 | 0.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 70.77 | 0.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 30.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 12.30 | 0.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 70.77 | 0.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 342.194 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 342.194 | 100.00 |
Total On-Site and Utility Electric Sources | 342.194 | 100.00 |
Total Electricity End Uses | 342.194 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 10.50 |
Time Setpoint Not Met During Occupied Cooling | 3.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1962.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 68.38 |
Skylight-Roof Ratio [%] | 1.49 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 6.9682 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 7.4271 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.5521 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8362 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8362 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 6.9682 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 7.4271 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.5521 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.8362 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.8362 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.8362 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-OCT-12:20 | 03-JAN-06:10 | - | - | - | - | - | - | - | - | - | - | 27-JUN-11:00 |
Heating | 0.00 | 28527.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 7525.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5701.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4395.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1741.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 29399.52 | 28527.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 28527.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 7525.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 5701.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2090.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1741.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 3.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 28.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 267.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 195.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 81.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 78.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1083.73 | 3.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 55.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 16.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 224.14 | 0.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 55.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 16.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 224.14 | 0.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.01 |
ZONE2 FINE STORAGE DIRECT AIR | 2.26 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 1.16 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 1.16 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 46556.44 |
PSZ-OFFICE HEATING COIL | 24933.00 |
PSZ-FINE STORAGE HEATING COIL | 71639.42 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 46556.44 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.01 | 1.01 | 1.01 | 1.01 | 1.01 | 1.01 | 1.00 | 1.00 | 1.01 |
PSZ-FINE STORAGE | 2.26 | 2.26 | 2.26 | 2.26 | 2.26 | 2.26 | 1.00 | 1.00 | 2.26 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.01 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.26 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.01 | 1121.59 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.26 | 2422.44 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.01 | 1.01 | 1.01 | 1.01 | 17343.51 | 24933.00 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.26 | 2.26 | 2.26 | 1.49 | 47006.45 | 71639.42 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.01 | 0.506516 | 0.675353 | 17343.51 | 8671.75 | 0.800480 | 0.800480 |
PSZ-FINE STORAGE COOLING COIL | 2.26 | 1.13 | 1.51 | 47006.45 | 23503.22 | 0.762110 | 0.762110 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 6.968 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 15.042 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 7.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.427 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.552 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 6.111 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1650.627 | 6.968 | 129.474 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1650.627 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 10348.979 | 7.427 | 344.966 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10348.979 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 11383.888 | 3.552 | 164.984 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11383.888 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2405 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5892 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.6534 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 1.134 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 2.044 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 1.134 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.158 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.697 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.431 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7826 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4892 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7826 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.77015739E-08 | 0.38457199E-13 | 0.23136523E-13 | 0.0000000 |
2 | 1 | -5.2160498 | 0.48395528E-04 | -0.66612159E-04 | 0.14765390E-08 |
3 | 0 | 5.4565497 | 0.24045158 | 0.24056658 | |
4 | 2 | 0.53319589E-11 | 0.95168195E-16 | 0.18684196E-15 | 0.0000000 |
5 | 1 | -5.2159738 | 0.43009049E-04 | -0.27188221E-04 | 0.68723469E-11 |
6 | 0 | 5.8052090 | 0.58919217 | 0.58926237 | |
7 | 4 | 0.74747876E-12 | 0.20825084E-15 | -0.25659737E-14 | 0.12362927E-15 |
8 | 3 | -0.37328678E-03 | 0.45238042E-06 | -0.54038165E-04 | 0.14344535E-12 |
9 | 2 | 1.7123825 | 0.10013958E-01 | 1.1198054 | -0.71564441E-04 |
10 | 1 | -7.1648294 | 0.26145347 | -16.966117 | 0.32817431 |
11 | 0 | 5.8918369 | 0.16754891 | 16.285382 | |
12 | 4 | 0.65556131E-12 | 0.57298371E-15 | -0.14028959E-14 | 0.12439065E-15 |
13 | 3 | -0.34087882E-03 | 0.75102955E-06 | -0.49042705E-04 | 0.12583838E-12 |
14 | 2 | 1.6337693 | 0.17263784E-01 | 1.0601096 | -0.65347397E-04 |
15 | 1 | -7.2734424 | 0.46143774 | -16.581274 | 0.31301327 |
16 | 0 | 6.4190060 | 0.30028979 | 16.300205 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.0441747 | 2.0441747 | 2.0441747 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.14028959E-14 | 0.57298371E-15 | 0.65556131E-12 | 0.12439065E-15 |
85 | 3 | -0.49042705E-04 | 0.75102955E-06 | -0.34087882E-03 | 0.12583838E-12 |
86 | 2 | 1.0601096 | 0.17263784E-01 | 1.6337693 | -0.65347397E-04 |
87 | 1 | -16.581274 | 0.46143774 | -7.2734424 | 0.31301327 |
88 | 0 | 16.300205 | 0.30028979 | 6.4190060 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.423_SHGC_SOUTH_0.249 | 34 | 1 | VerySmooth | 2.404 | 2.404 | 1.000 | 0.250 | ||
2 | NONRESWINDOW_U_0.423_SHGC_NORTH_0.249 | 35 | 1 | VerySmooth | 2.404 | 2.404 | 1.000 | 0.250 | ||
3 | NONRESWINDOW_U_0.423_SHGC_EAST_0.249 | 36 | 1 | VerySmooth | 2.404 | 2.404 | 1.000 | 0.250 | ||
4 | NONRESWINDOW_U_0.423_SHGC_WEST_0.249 | 37 | 1 | VerySmooth | 2.404 | 2.404 | 1.000 | 0.250 | ||
5 | SKYLIGHT_U_0.55_SHGC_0.3 | 38 | 1 | VerySmooth | 3.127 | 3.127 | 1.000 | 0.301 | ||
6 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | 39 | 1 | VerySmooth | 5.108 | 5.108 | 1.000 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.99333E-002 | 0.16038 | 0.62145 | 0.62145 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12244 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.99333E-002 | 0.16038 | 0.62145 | 0.62145 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12244 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.99333E-002 | 0.16038 | 0.62145 | 0.62145 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12244 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.99333E-002 | 0.16038 | 0.62145 | 0.62145 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12244 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 1.15759E-002 | 0.21195 | 0.55558 | 0.55558 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 7.71143E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 0.12500 | 0.12500 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | CurtainWall | 3.043 | 0.303 | 0.402 |
2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.867 | 0.549 | 0.401 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.331 | 7.274E-004 | 4.751E-004 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.3444E-005 |
2 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.7476E-004 |
3 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4799E-005 |
4 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.4381E-004 |
5 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4856E-005 |
6 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.3071E-004 |
7 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5724E-005 |
8 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.5867E-004 |
9 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5530E-004 |
10 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.8669E-004 |
11 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3153E-004 |
12 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.3804E-004 |
13 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5071E-004 |
14 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.0511E-004 |
15 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3414E-004 |
16 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4540E-004 |
17 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.6182E-004 |
18 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6456E-004 |
19 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0575E-004 |
20 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8307E-004 |
21 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.6517E-004 |
22 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2314E-004 |
23 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8792E-004 |
24 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6675E-005 |
25 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.5326E-004 |
26 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.8559E-005 |
27 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.9668E-004 |
28 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.4880E-005 |
29 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1169E-003 |
30 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.3782E-005 |
31 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3392E-003 |
32 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0724E-005 |
33 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.3753E-004 |
34 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3521E-005 |
35 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.9384E-004 |
36 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6011E-005 |
37 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.7452E-004 |
38 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9251E-005 |
39 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9718E-004 |
40 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6272E-005 |
41 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.6292E-004 |
42 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4373E-005 |
43 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.2331E-004 |
44 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5554E-005 |
45 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.8240E-004 |
46 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4298E-005 |
47 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7955E-004 |
48 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4789E-005 |
49 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.5382E-004 |
50 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4747E-005 |
51 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0082E-003 |
52 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5969E-005 |
53 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9092E-004 |
54 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4522E-005 |
55 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3679E-004 |
56 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4861E-005 |
57 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9223E-003 |
58 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4941E-005 |
59 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1749E-003 |
60 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.7641E-005 |
61 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9294E-003 |
62 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0037E-005 |
63 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1133E-003 |
64 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6508E-005 |
65 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6376E-003 |
66 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.5099E-005 |
67 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5465E-003 |
68 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0264E-004 |
69 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3158E-003 |
70 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.7183E-005 |
71 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5808E-003 |
72 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1684E-005 |
73 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8197E-004 |
74 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0332E-004 |
75 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.8370E-004 |
76 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.3033E-004 |
77 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.0280E-004 |
78 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4231E-004 |
79 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6286E-003 |
80 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1734E-005 |
81 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9832E-004 |
82 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.5641E-004 |
83 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6390E-004 |
84 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.7260E-004 |
85 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8313E-004 |
86 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.4268E-004 |
87 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3102E-004 |
88 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8162E-004 |
89 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.2145E-005 |
90 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7421E-003 |
91 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.1116E-005 |
92 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0094E-003 |
93 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.9223E-005 |
94 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5786E-003 |
95 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0760E-004 |
96 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8446E-004 |
97 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2538E-005 |
98 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8588E-003 |
99 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8735E-005 |
100 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8386E-003 |
101 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8366E-005 |
102 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5311E-003 |
103 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7398E-005 |
104 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.1825E-003 |
105 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0468E-005 |
106 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.2347E-004 |
107 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.7262E-005 |
108 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8676E-004 |
109 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.7625E-005 |
110 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1966E-003 |
111 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5431E-005 |
112 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2422E-003 |
113 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2543E-005 |
114 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9197E-005 |
115 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8412E-005 |
116 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0620E-005 |
117 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7740E-005 |
118 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6731E-005 |
119 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4598E-005 |
120 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5286E-005 |
121 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6327E-005 |
122 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9529E-005 |
123 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8565E-005 |
124 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3456E-005 |
125 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5517E-005 |
126 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0901E-005 |
127 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1685E-005 |
128 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2542E-005 |
129 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2887E-005 |
130 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9763E-005 |
131 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8538E-005 |
132 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8714E-005 |
133 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7036E-005 |
134 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9189E-005 |
135 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4582E-005 |
136 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1042E-005 |
137 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2116E-004 |
138 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1017E-004 |
139 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5601E-004 |
140 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1811E-004 |
141 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4147E-004 |
142 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.3849E-005 |
143 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2514E-005 |
144 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3080E-005 |
145 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4464E-005 |
146 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5521E-004 |
147 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9476E-005 |
148 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9822E-004 |
149 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2591E-005 |
150 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5669E-004 |
151 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4916E-005 |
152 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6240E-005 |
153 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2916E-005 |
154 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2864E-005 |
155 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5043E-005 |
156 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2427E-005 |
157 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8022E-005 |
158 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3530E-005 |
159 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4899E-005 |
160 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1079E-005 |
161 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8482E-004 |
162 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9625E-005 |
163 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0909E-004 |
164 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9559E-005 |
165 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3241E-004 |
166 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8865E-005 |
167 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2500E-005 |
168 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7738E-005 |
169 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2542E-004 |
170 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.4522E-004 |
171 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3028E-004 |
172 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0193E-003 |
173 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2279E-004 |
174 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0076E-004 |
175 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0532E-005 |
176 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7293E-004 |
177 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6830E-004 |
178 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9543E-004 |
179 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6794E-004 |
180 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0674E-004 |
181 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.9234E-004 |
182 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9364E-004 |
183 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5069E-004 |
184 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0290E-004 |
185 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3856E-004 |
186 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1628E-005 |
187 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0037E-004 |
188 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0095E-005 |
189 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5306E-004 |
190 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5367E-005 |
191 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5061E-004 |
192 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8433E-005 |
193 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0668E-004 |
194 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5040E-005 |
195 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0727E-004 |
196 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4150E-005 |
197 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1264E-004 |
198 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6309E-005 |
199 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0473E-005 |
200 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3210E-005 |
201 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8363E-004 |
202 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2891E-005 |
203 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.7337E-004 |
204 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.8612E-005 |
205 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.4530E-004 |
206 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.4455E-005 |
207 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2387E-004 |
208 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6113E-005 |
209 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0959E-003 |
210 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1144E-004 |
211 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2445E-003 |
212 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1326E-004 |
213 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0492E-003 |
214 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9041E-004 |
215 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2445E-004 |
216 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5215E-004 |
217 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4442E-004 |
218 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6707E-005 |
219 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3843E-004 |
220 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5289E-005 |
221 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7996E-004 |
222 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8571E-005 |
223 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2708E-004 |
224 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5686E-005 |
225 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6677E-004 |
226 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8059E-003 |
227 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6486E-004 |
228 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1221E-003 |
229 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9832E-004 |
230 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5028E-003 |
231 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2726E-004 |
232 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9459E-004 |
233 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5779E-004 |
234 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7197E-005 |
235 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4223E-004 |
236 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5366E-005 |
237 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1600E-004 |
238 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9019E-005 |
239 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9961E-004 |
240 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7482E-005 |
241 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0272E-003 |
242 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.6625E-005 |
243 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0018E-003 |
244 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9588E-005 |
245 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4476E-003 |
246 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2008E-005 |
247 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6165E-003 |
248 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3274E-005 |
249 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1487E-003 |
250 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5424E-004 |
251 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1472E-003 |
252 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2553E-004 |
253 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5707E-003 |
254 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2460E-004 |
255 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6195E-003 |
256 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2024E-004 |
257 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7400E-004 |
258 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8326E-003 |
259 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6025E-004 |
260 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8781E-003 |
261 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3768E-004 |
262 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3865E-003 |
263 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0001E-004 |
264 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6530E-003 |
265 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3150E-004 |
266 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6248E-005 |
267 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1339E-004 |
268 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4286E-005 |
269 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6578E-004 |
270 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7190E-005 |
271 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9852E-004 |
272 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7461E-005 |
273 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3728E-004 |
274 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3941E-004 |
275 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1982E-004 |
276 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2118E-004 |
277 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8012E-004 |
278 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1128E-003 |
279 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9891E-004 |
280 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6031E-003 |
281 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8144E-004 |
282 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9669E-005 |
283 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9598E-004 |
284 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1896E-005 |
285 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.9373E-004 |
286 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8467E-005 |
287 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5919E-003 |
288 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3045E-005 |
289 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0231E-004 |
290 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5941E-004 |
291 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1868E-004 |
292 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2095E-004 |
293 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4146E-004 |
294 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5550E-004 |
295 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5949E-003 |
296 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1554E-004 |
297 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1470E-005 |
298 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8911E-004 |
299 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8523E-005 |
300 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3402E-004 |
301 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.9602E-005 |
302 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0752E-004 |
303 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2574E-004 |
304 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7337E-004 |
305 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3949E-004 |
306 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4584E-004 |
307 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9563E-004 |
308 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2073E-004 |
309 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6414E-004 |
310 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5420E-004 |
311 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1039E-004 |
312 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4748E-004 |
313 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6603E-005 |
314 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6529E-005 |
315 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8681E-005 |
316 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3803E-005 |
317 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5028E-005 |
318 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3271E-005 |
319 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1671E-005 |
320 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7584E-005 |
321 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0956E-005 |
322 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4238E-005 |
323 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7402E-005 |
324 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2444E-005 |
325 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3628E-005 |
326 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4122E-005 |
327 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2556E-004 |
328 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5637E-005 |
329 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9778E-005 |
330 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1513E-004 |
331 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2128E-005 |
332 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.3769E-005 |
333 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5385E-005 |
334 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.6563E-005 |
335 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9741E-005 |
336 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6869E-004 |
337 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0401E-004 |
338 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.9655E-005 |
339 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5584E-005 |
340 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6894E-005 |
341 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9796E-005 |
342 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.8488E-005 |
343 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4732E-004 |
344 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0119E-004 |
345 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0227E-005 |
346 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1880E-005 |
347 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2159E-005 |
348 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0437E-005 |
349 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.3333E-005 |
350 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1237E-005 |
351 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9684E-005 |
352 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3161E-005 |
353 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3928E-004 |
354 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6885E-005 |
355 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9440E-004 |
356 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0432E-005 |
357 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5422E-004 |
358 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6796E-005 |
359 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0983E-004 |
360 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5702E-005 |
361 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0462E-004 |
362 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4879E-005 |
363 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5756E-005 |
364 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0446E-005 |
365 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7787E-005 |
366 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1279E-005 |
367 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4724E-004 |
368 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8139E-005 |
369 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 3.7477E-003 |
370 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 4.3416E-004 |
371 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 3.4139E-003 |
372 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 4.0071E-004 |
373 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 3.1360E-003 |
374 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.7717E-004 |
375 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.7866E-003 |
376 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1636E-004 |
377 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.4236E-004 |
378 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.9229E-003 |
379 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.1663E-004 |
380 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.3532E-003 |
381 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.8476E-004 |
382 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.3289E-003 |
383 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.1270E-004 |
384 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.3974E-003 |
385 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.0881E-003 |
386 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.2183E-004 |
387 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.3003E-003 |
388 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.7538E-004 |
389 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.4463E-003 |
390 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.3312E-004 |
391 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.2429E-003 |
392 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.9254E-004 |
393 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.0274E-003 |
394 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.2159E-004 |
395 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.2732E-003 |
396 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.7526E-004 |
397 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.5204E-003 |
398 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.3325E-004 |
399 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.2428E-003 |
400 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.9254E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10070.32905 | 12084.39486 | 0.84419 | 1.01303 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 30.64733 | 8.23245E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 7286.76406 | 8744.11687 | 0.20823 | 0.24987 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 3.80000 | 5.05843E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 28870.25515 | 34644.30618 | 1.88655 | 2.26387 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 31.30000 | 8.23349E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 15825.03275 | 18990.03930 | 0.38128 | 0.45754 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 3.80000 | 5.05843E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 31.30000 | 8.23349E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 38797.03588 | 46556.44306 | 0.96592 | 1.15910 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 15137.93 | 1.01303 | 1.01303 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 7724.92 | 0.24987 | 0.24987 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 41837.01 | 2.26387 | 2.26387 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 19210.35 | 0.45754 | 0.45754 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.01303 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.26387 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.15910 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 1.15910 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 46556.44151 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 46556.44306 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.01303 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.01303 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.01303 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.01303 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.01303 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.01303 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.26387 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.26387 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.26387 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.26387 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.26387 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.26387 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.01303 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.26387 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.01303 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.01303 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1121.58785 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.01303 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.01303 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.01303 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.01303 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.01303 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50652 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.67535 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17343.51000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8671.75500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80048 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80048 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17343.51000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 24932.99538 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 24932.99538 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.26387 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.26387 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2422.44351 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.26387 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.26387 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.26387 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.49415 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.26387 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.13193 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.50925 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 47006.45000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 23503.22500 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76211 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76211 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 47006.45000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 71639.41524 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 71639.41524 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 16557.3 | 12.24 | 11.97 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 45248.2 | 11.73 | 11.46 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 2.2392650358E-002 | 1.8695102311E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.1318060117 | 0.1730791948 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 3.4323983290E-002 | 3.6016096151E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 11736.90 | 335.61 | 0.00 | 62.55 | 52.14 | 12187.25 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.00 | 2 | |||
Feb | 59.00 | 53 | |||
Mar | 58.58 | 43 | |||
Apr | 46.42 | 14 | |||
May | 18.00 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 3.00 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 18.00 | 12 | |||
Dec | 4.00 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.233 | 0.240 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.545 | 0.589 | 3204.84 | 3157.28 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.892 | 1.134 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.892 | 1.134 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.423_SHGC_WEST_0.249 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.404 | 0.250 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.423_SHGC_WEST_0.249 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.404 | 0.250 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.423_SHGC_NORTH_0.249 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.404 | 0.250 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.423_SHGC_NORTH_0.249 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.404 | 0.250 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 86.04 | 4.074 | 0.429 | 0.370 | |||||||||||||||||
North Total or Average | 6.51 | 2.404 | 0.250 | 0.250 | |||||||||||||||||
Non-North Total or Average | 79.53 | 4.210 | 0.443 | 0.380 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 6.9682 | 236.88 | 1650.63 | LightsWired | LTG_SCH_OFFICE | 52.33 | 168.00 | 32.89 | 0.0000 | Y | 10.19 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 7.4271 | 1393.41 | 10348.98 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 18.91 | 0.0000 | Y | 36.74 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.5521 | 3204.84 | 11383.89 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 17.50 | 0.0000 | Y | 37.41 |
Interior Lighting Total | 4.8362 | 4835.13 | 23383.49 | 84.34 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10348.98 | 2587.24 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10348.98 | 2587.24 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 11383.89 | 2845.97 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 11383.89 | 2845.97 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.29 | 1650.63 | 478.68 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.10 | 1650.63 | 165.06 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 123.84 | AstronomicalClock | - | 42.14 | 42.14 | 0.98 | |
EXTERIOR_LIGHTS_B | 4305.62 | AstronomicalClock | - | 83.75 | 62.95 | 50.88 | |
EXTERIOR_LIGHTS_C | 1091.36 | AstronomicalClock | - | 83.75 | 48.95 | 10.03 | |
Exterior Lighting Total | 5520.82 | 61.88 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17343.51 | 13883.13 | 3460.38 | 0.80 | 4.12 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 47006.45 | 35824.09 | 11182.36 | 0.76 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 16557.3 | 12.24 | 11.97 | ||||
PSZ-FINE STORAGE COOLING COIL | 45248.2 | 11.73 | 11.46 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 46556.44 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 24933.00 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 71639.42 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 1.16 | 107.69 | 92.91 | 1.00 | 4.00 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.01 | 1121.59 | 1107.16 | 1.00 | 1.40 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.26 | 2422.44 | 1070.05 | 1.00 | 1.30 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10070.33 | 12084.39 | 51.01 | 0.844 | 1.013 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 23.90 | 23.90 | 0.00830 | 30.65 | 0.00823 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 28870.26 | 34644.31 | 24.86 | 1.887 | 2.264 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 26.70 | 26.70 | 0.00837 | 31.30 | 0.00823 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 0.00 | 31.96 | 0.00830 | 31.30 | 0.00823 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 7286.76 | 8744.12 | 36.91 | 0.208 | 0.250 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00788 | 3.80 | 0.00506 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 15825.03 | 18990.04 | 13.63 | 0.381 | 0.458 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 15.56 | 15.56 | 0.00689 | 3.80 | 0.00506 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 38797.04 | 46556.44 | 14.53 | 0.966 | 1.159 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00624 | 3.80 | 0.00506 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.01 | 1.01 | 0.25 | 0.25 | 1.0130 | 1.0130 | 1.0130 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.26 | 2.26 | 0.46 | 0.46 | 2.2639 | 2.2639 | 2.2639 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 46556.442 | 46556.442 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 46556.44 | 46556.44 | 1.159099 | 10.00 | 8.32 | 0.00624264 | 43.33 | 21.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 10.00 | 0.00624264 | 80.4630 | 46556.44 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 17343.510 | 13883.133 | 1.013030 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 8671.75 | 8270.09 | 0.675353 | 25.51 | 16.55 | 0.00829336 | 12.00 | 11.09 | 0.00800000 | 30.77 | 0.00823264 | 18.27 | 15.1454 | 23.90 | 0.00830019 | 44.1310 | 10062.91 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 24932.995 | 24932.995 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 24933.00 | 24933.00 | 1.013033 | 19.27 | 13.63 | 0.00759203 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 10.0969 | 21.10 | 0.00787658 | 49.6781 | 7286.76 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 47006.450 | 35824.086 | 2.263870 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 23503.22 | 22427.50 | 1.509247 | 28.45 | 17.60 | 0.00834537 | 12.00 | 11.09 | 0.00800000 | 31.30 | 0.00823349 | 18.45 | 28.1406 | 26.70 | 0.00837121 | 37.6761 | 28870.26 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 71639.415 | 71639.415 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 71639.42 | 71639.42 | 2.263866 | 13.35 | 10.16 | 0.00654751 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 18.7604 | 15.56 | 0.00689138 | 61.6373 | 15825.03 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 46556.442 | 46556.442 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 1.159099 | 1.36979821 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 46556.44 | 46556.44 | 1.0000 | 1.36979821 | 1.159099 | 10.00 | 8.32 | 0.00624264 | 25776.1 | 43.33 | 21.93 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 46556.44 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 10.00 | 0.00624264 | 10.00 | 0.00624264 | 80.4630 | 46556.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17343.510 | 13883.133 | 1.013030 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2569 | 1004.8586 | 1.1818 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.013033 | 1.19718026 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | Sensible | 8671.75 | 8270.09 | 1.0000 | 0.79811816 | 0.675353 | 25.51 | 16.55 | 0.00829336 | 46769.0 | 12.00 | 11.09 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8671.75 | 30.77 | 0.00823264 | 18.27 | 0.10228463 | 15.1454 | 23.90 | 0.00830019 | 23.90 | 0.00830019 | 44.1310 | 10062.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24932.995 | 24932.995 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.013033 | 1.19718026 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 24933.00 | 24933.00 | 1.0000 | 1.19718026 | 1.013033 | 19.27 | 13.63 | 0.00759203 | 38626.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24933.00 | 3.80 | 0.00505843 | 3.80 | 0.10228463 | 10.0969 | 21.01 | 0.00787658 | 21.10 | 0.00787658 | 49.6781 | 7286.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 47006.450 | 35824.086 | 2.263870 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3536 | 1004.8586 | 1.1818 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.263866 | 2.67538840 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | Sensible | 23503.22 | 22427.50 | 1.0000 | 1.78359551 | 1.509247 | 28.45 | 17.60 | 0.00834537 | 49899.8 | 12.00 | 11.09 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23503.22 | 31.30 | 0.00823349 | 18.45 | 0.42471127 | 28.1406 | 26.70 | 0.00837121 | 26.70 | 0.00837121 | 37.6761 | 28870.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 71639.415 | 71639.415 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.263866 | 2.67538840 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | Sensible | 71639.42 | 71639.42 | 1.0000 | 2.67538840 | 2.263866 | 13.35 | 10.16 | 0.00654751 | 29954.3 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 71639.42 | 3.80 | 0.00505843 | 3.80 | 0.42471127 | 18.7604 | 15.56 | 0.00689138 | 15.56 | 0.00689138 | 61.6373 | 15825.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.01 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 2.26 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 1425.50 | 2090.00 | 315.17 |
ZONE2 FINE STORAGE | 2276.83 | 2669.00 | 1437.67 |
ZONE3 BULK STORAGE | 2598.33 | 2872.00 | 1950.00 |
Facility | 2621.67 | 3124.00 | 1962.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 10.50 | 3.17 | 10.50 | 3.17 |
ZONE2 FINE STORAGE | 1.50 | 2.67 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 12.00 | 5.83 | 10.50 | 3.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 1.334 | 0.272 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.581 | 0.178 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.44 | 69.00 | 35277.63 | 0.000 | 0.099 | 0.000 | 0.084 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.44 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.50 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.36 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.44 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.30 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 4781540.73 | 0.00 | 4781540.73 | 1377013.49 | 6158554.22 | 3225648.14 | 5643.66 | 998.75 | 2117.59 | 0.00 |
ZONE2 FINE STORAGE | 6136602.04 | 0.00 | 6136602.04 | 4130661.33 | 10267263.37 | 13393694.68 | 5711.00 | 2347.75 | 701.25 | 20.58 |
ZONE3 BULK STORAGE | 0.00 | 15516319.00 | 15516319.00 | 21619758.02 | 37136077.01 | 30805497.77 | 8659.43 | 6.63 | 93.94 | 4402.96 |
Total Facility | 10918142.77 | 15516319.00 | 26434461.76 | 27127432.84 | 53561894.60 | 47424840.58 | 8675.23 | 2497.08 | 2340.16 | 4404.41 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.3653 | 0.0000 | 0.3653 | 0.0748 | 0.4401 | 0.1023 | 519.66 | 998.75 | 2117.59 |
ZONE2 FINE STORAGE | 0.4633 | 0.0000 | 0.4633 | 0.1429 | 0.6061 | 0.4247 | 606.00 | 2347.50 | 682.50 |
ZONE3 BULK STORAGE | 0.0000 | 0.7927 | 0.7927 | 0.9497 | 1.7423 | 0.9768 | 3548.90 | 5.30 | 81.80 |
Total Facility | 0.8285 | 0.7927 | 1.6212 | 1.1673 | 2.7885 | 1.5038 | 3551.23 | 2495.50 | 2309.93 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 6677903.65 | 0.00 | 6677903.65 | 3225648.14 | 5635.83 | 0.33 | 3123.84 | 0.00 |
PSZ-FINE STORAGE | 8570383.26 | 0.00 | 8570383.26 | 13393694.68 | 5710.25 | 0.00 | 3049.75 | 20.58 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.5102 | 0.0000 | 0.5102 | 0.1023 | 511.83 | 0.33 | 3123.84 |
PSZ-FINE STORAGE | 0.6470 | 0.0000 | 0.6470 | 0.4247 | 606.00 | 0.00 | 3030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2072.08 | 1063.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2819.32 | 231.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.6183 | 0.5398 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.7514 | 1.0885 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 446 |
Defaulted Fields | 391 |
Fields with Defaults | 1172 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 342.19 | 1550.86 | 01-JAN-09:20 | 29399.52 | 16-OCT-12:20 |
Electricity:Building | 221.18 | 1069.86 | 01-JAN-09:20 | 19967.13 | 17-OCT-15:00 |
Electricity:Zone:ZONE1 OFFICE | 39.35 | 520.87 | 01-JAN-00:10 | 2846.16 | 02-JAN-16:50 |
Electricity:SpaceType:GENERAL | 220.85 | 1069.86 | 01-JAN-09:20 | 18295.02 | 06-DEC-16:00 |
InteriorLights:Electricity | 84.34 | 599.99 | 01-JAN-09:20 | 8259.84 | 06-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.19 | 51.00 | 01-JAN-00:10 | 1011.11 | 02-JAN-16:50 |
InteriorLights:Electricity:SpaceType:GENERAL | 84.34 | 599.99 | 01-JAN-09:20 | 8259.84 | 06-DEC-16:00 |
LightsWired:InteriorLights:Electricity | 84.34 | 599.99 | 01-JAN-09:20 | 8259.84 | 06-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.19 | 51.00 | 01-JAN-00:10 | 1011.11 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 84.34 | 599.99 | 01-JAN-09:20 | 8259.84 | 06-DEC-16:00 |
Electricity:Zone:ZONE2 FINE STORAGE | 36.74 | 299.97 | 01-JAN-00:10 | 3668.31 | 18-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 36.74 | 299.97 | 01-JAN-00:10 | 3668.31 | 18-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 36.74 | 299.97 | 01-JAN-00:10 | 3668.31 | 18-DEC-16:00 |
Electricity:Zone:ZONE3 BULK STORAGE | 145.09 | 249.02 | 01-JAN-09:20 | 13937.64 | 17-OCT-15:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 37.41 | 249.02 | 01-JAN-09:20 | 3867.14 | 18-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 37.41 | 249.02 | 01-JAN-09:20 | 3867.14 | 18-DEC-16:00 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 25.67 | 0.00 | 01-JAN-00:10 | 4395.86 | 31-JUL-12:20 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.34 | 0.00 | 01-JAN-00:10 | 2305.29 | 31-JUL-12:20 |
Ventilation (simple):Fans:Electricity | 0.34 | 0.00 | 01-JAN-00:10 | 2305.29 | 31-JUL-12:20 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.34 | 0.00 | 01-JAN-00:10 | 2305.29 | 31-JUL-12:20 |
ElectricityPurchased:Facility | 342.19 | 1550.86 | 01-JAN-09:20 | 29399.52 | 16-OCT-12:20 |
ElectricityPurchased:Plant | 342.19 | 1550.86 | 01-JAN-09:20 | 29399.52 | 16-OCT-12:20 |
Cogeneration:ElectricityPurchased | 342.19 | 1550.86 | 01-JAN-09:20 | 29399.52 | 16-OCT-12:20 |
General:Cogeneration:ElectricityPurchased | 342.19 | 1550.86 | 01-JAN-09:20 | 29399.52 | 16-OCT-12:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 342.19 | 1550.86 | 01-JAN-09:20 | 29399.52 | 16-OCT-12:20 |
ElectricityNet:Plant | 342.19 | 1550.86 | 01-JAN-09:20 | 29399.52 | 16-OCT-12:20 |
Cogeneration:ElectricityNet | 342.19 | 1550.86 | 01-JAN-09:20 | 29399.52 | 16-OCT-12:20 |
General:Cogeneration:ElectricityNet | 342.19 | 1550.86 | 01-JAN-09:20 | 29399.52 | 16-OCT-12:20 |
Electricity:HVAC | 34.49 | 0.00 | 01-JAN-00:10 | 10036.95 | 16-OCT-12:00 |
General:Fans:Electricity | 25.33 | 0.00 | 01-JAN-00:10 | 2165.85 | 04-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 9.15 | 0.00 | 01-JAN-00:10 | 7946.39 | 16-OCT-12:00 |
General:Cooling:Electricity | 9.15 | 0.00 | 01-JAN-00:10 | 7946.39 | 16-OCT-12:00 |
ExteriorLights:Electricity | 61.88 | 0.00 | 01-JAN-07:00 | 5520.82 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 61.88 | 0.00 | 01-JAN-07:00 | 5520.82 | 01-JAN-06:10 |
Electricity:Plant | 24.64 | 481.00 | 12-JAN-06:10 | 1797.32 | 11-FEB-12:10 |
WaterSystems:Electricity | 24.64 | 481.00 | 12-JAN-06:10 | 1797.32 | 11-FEB-12:10 |
Water Heater:WaterSystems:Electricity | 24.64 | 481.00 | 12-JAN-06:10 | 1797.32 | 11-FEB-12:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 3.60 | 0.00 | 01-JAN-00:10 | 28527.10 | 03-JAN-06:10 |
NaturalGas:HVAC | 3.60 | 0.00 | 01-JAN-00:10 | 28527.10 | 03-JAN-06:10 |
Heating:NaturalGas | 3.60 | 0.00 | 01-JAN-00:10 | 28527.10 | 03-JAN-06:10 |
General:Heating:NaturalGas | 3.60 | 0.00 | 01-JAN-00:10 | 28527.10 | 03-JAN-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUN-12:00 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUN-12:00 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUN-12:00 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUN-12:00 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUN-12:00 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUN-12:00 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUN-12:00 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUN-12:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 112.42 | 0.00 | 01-JAN-00:10 | 51365.81 | 17-AUG-14:30 |
EnergyTransfer:Building | 68.11 | 0.00 | 01-JAN-00:10 | 21604.97 | 30-SEP-15:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 31.27 | 0.00 | 01-JAN-00:10 | 14574.78 | 03-JAN-06:10 |
Heating:EnergyTransfer | 5.29 | 0.00 | 01-JAN-00:10 | 21303.30 | 03-JAN-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 3.45 | 0.00 | 01-JAN-00:10 | 14574.78 | 03-JAN-06:10 |
General:Heating:EnergyTransfer | 5.29 | 0.00 | 01-JAN-00:10 | 21303.30 | 03-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 3.45 | 0.00 | 01-JAN-00:10 | 14574.78 | 03-JAN-06:10 |
Cooling:EnergyTransfer | 62.82 | 0.00 | 01-JAN-00:10 | 21604.97 | 30-SEP-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 27.82 | 0.00 | 01-JAN-00:10 | 8505.08 | 29-SEP-05:10 |
General:Cooling:EnergyTransfer | 62.82 | 0.00 | 01-JAN-00:10 | 21604.97 | 30-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 27.82 | 0.00 | 01-JAN-00:10 | 8505.08 | 29-SEP-05:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 36.84 | 0.00 | 01-JAN-00:10 | 15545.69 | 04-JUL-17:20 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 1.84 | 0.00 | 01-JAN-00:10 | 12441.79 | 03-JAN-04:00 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 1.84 | 0.00 | 01-JAN-00:10 | 12441.79 | 03-JAN-04:00 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 35.00 | 0.00 | 01-JAN-00:10 | 15545.69 | 04-JUL-17:20 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 35.00 | 0.00 | 01-JAN-00:10 | 15545.69 | 04-JUL-17:20 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 44.31 | 0.00 | 01-JAN-00:10 | 31516.44 | 17-AUG-15:00 |
HeatingCoils:EnergyTransfer | 2.46 | 0.00 | 01-JAN-00:10 | 21007.75 | 03-JAN-06:10 |
CoolingCoils:EnergyTransfer | 41.85 | 0.00 | 01-JAN-00:10 | 31516.44 | 17-AUG-15:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 3.452 | -27.819 | 0.000 | 0.000 | 9.326 | 10.190 | 29.165 | 10.120 | 0.000 | 0.170 | 0.000 | 0.000 | -6.134 | 0.000 | -10.443 | -18.027 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 1.835 | -35.002 | 0.000 | 0.000 | 21.565 | 36.742 | 0.000 | 33.612 | 0.000 | 0.255 | 0.001 | 0.000 | -11.847 | 0.000 | -31.424 | -15.734 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 47.566 | 37.405 | 107.344 | 601.245 | 0.000 | 5.212 | 0.004 | 0.000 | -120.447 | 0.000 | -251.617 | -426.708 |
Total Facility | 0.000 | 0.000 | 5.288 | -62.821 | 0.000 | 0.000 | 78.457 | 84.337 | 136.508 | 644.977 | 0.000 | 5.637 | 0.005 | 0.000 | -138.428 | 0.000 | -293.485 | -460.470 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 17-OCT-05:03 | 0.00 | 0.00 | 0.00 | -19880.02 | 0.00 | 0.00 | 94.07 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 19957.83 | 0.00 | -372.03 | 0.00 | -401.36 | 0.00 |
ZONE2 FINE STORAGE | 30-JUL-13:03 | 0.00 | 0.00 | 0.00 | -37732.20 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 5082.84 | 0.00 | 0.00 | 32544.72 | 0.00 | -0.00 | 0.00 | -195.34 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 30-JUL-13:03 | 0.00 | 0.00 | 0.00 | -37732.20 | 0.00 | 0.00 | 0.00 | 599.99 | 469.88 | 117055.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2201.34 | -78191.88 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 02-JAN-06:12 | 0.00 | 0.00 | 25366.78 | 0.00 | 0.00 | 0.00 | 118.54 | 302.02 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -269.87 | 0.00 | -674.68 | -25393.30 |
ZONE2 FINE STORAGE | 09-JAN-06:07 | 0.00 | 0.00 | 62714.94 | 0.00 | 0.00 | 0.00 | 353.18 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1059.20 | 0.00 | -3008.36 | -59300.53 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 09-JAN-06:07 | 0.00 | 0.00 | 67347.15 | 0.00 | 0.00 | 0.00 | 1347.13 | 849.01 | 2600.55 | 0.00 | 0.00 | 0.00 | 2800.10 | 0.00 | -54969.56 | 0.00 | -19974.38 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0130 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0130 | 0.1010 | 1.0000 | Not calculated | 0.1023 | 0.1010 | ||
PSZ-FINE STORAGE | 2.2639 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.2639 | 0.1876 | 1.0000 | Not calculated | 0.4247 | 0.1876 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0130 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0130 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.1010 | ||
PSZ-FINE STORAGE | 2.2639 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.2639 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1876 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0130 | 1.0130 | 1.0130 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2639 | 2.2639 | 2.2639 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0130 | 1.0130 | 1.0130 | 1.0130 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.2639 | 2.2639 | 2.2639 | 2.2639 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0130 | 1.0130 | 1.0130 | No | 0.1023 | 0.4093 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2639 | 2.2639 | 2.2639 | No | 0.4247 | 0.9283 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0130 | 1.0130 | 1.0130 | 1.0130 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.2639 | 2.2639 | 2.2639 | 2.2639 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 10.50 |
Number of hours cooling loads not met | 3.17 |
Number of hours not met | 13.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 3.60 | 28527.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 9.15 | 7946.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 84.34 | 8259.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 61.88 | 5520.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.34 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 25.33 | 2165.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 24.64 | 1797.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 342.19 |
Natural Gas | 0.00 | 3.60 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 345.79 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 17.44 |
Space Heating | 0.00 |
Space Cooling | 1.89 |
Fans (All) | 5.31 |
Service Water Heating | 5.10 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 70.77 |
Subtotal | 70.77 |
Natural Gas [MJ/m2] | |
Space Heating | 0.74 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.74 |
Subtotal | 0.74 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 24.39 |
Space Heating | 1.04 |
Space Cooling | 2.65 |
Fans (All) | 7.42 |
Service Water Heating | 7.12 |
Receptacle Equipment | 39.48 |
Miscellaneous | 17.90 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2729. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8558.33 | 201.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7886.33 | 873.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 6772.67 | 1987.33 | 0.00 | 0.00 | 0.00 |
Min | 6772.67 | 201.67 | 0.00 | 0.00 | 0.00 |
Max | 8558.33 | 1987.33 | 0.00 | 0.00 | 0.00 |
Average | 7739.11 | 1020.89 | 0.00 | 0.00 | 0.00 |
Sum | 23217.33 | 3062.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 63968.00 | 18751.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 128699.00 | 62494.00 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128699.00 | 62494.00 | 0.00 | 0.00 | 0.00 |
Average | 75231.33 | 27081.67 | 0.00 | 0.00 | 0.00 |
Sum | 225694.00 | 81245.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 7654.83 | 1105.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 6645.50 | 2114.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 6135.83 | 2624.17 | 0.00 | 0.00 | 0.00 |
Min | 6135.83 | 1105.17 | 0.00 | 0.00 | 0.00 |
Max | 7654.83 | 2624.17 | 0.00 | 0.00 | 0.00 |
Average | 6812.06 | 1947.94 | 0.00 | 0.00 | 0.00 |
Sum | 20436.17 | 5843.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 32610.50 | 416.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 54859.00 | 27860.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 120779.83 | 70413.17 | 0.00 | 0.00 | 0.00 |
Min | 32610.50 | 416.50 | 0.00 | 0.00 | 0.00 |
Max | 120779.83 | 70413.17 | 0.00 | 0.00 | 0.00 |
Average | 69416.44 | 32896.56 | 0.00 | 0.00 | 0.00 |
Sum | 208249.33 | 98689.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.388846E+09 | 2590.54 | 21-JAN-15:00 | 14.00 | 11.21 | 0.587741E+09 | 768.98 | 19-JAN-13:30 | 14.00 | 11.21 |
February | 0.327265E+09 | 2705.94 | 03-FEB-15:20 | 22.33 | 9.30 | 0.542322E+09 | 768.97 | 01-FEB-13:39 | 22.33 | 9.30 |
March | 0.454184E+09 | 3584.62 | 23-MAR-16:00 | 21.00 | 17.19 | 0.635213E+09 | 769.01 | 23-MAR-15:09 | 21.00 | 17.19 |
April | 0.189089E+10 | 4947.51 | 26-APR-15:40 | 22.33 | 16.35 | 0.625498E+09 | 769.00 | 25-APR-12:39 | 22.33 | 16.35 |
May | 0.245697E+10 | 5529.12 | 03-MAY-15:00 | 22.00 | 15.39 | 0.656042E+09 | 769.00 | 02-MAY-15:39 | 22.00 | 15.39 |
June | 0.365778E+10 | 18327.57 | 23-JUN-05:03 | 15.17 | 12.72 | 0.659493E+09 | 769.02 | 28-JUN-09:39 | 21.67 | 18.63 |
July | 0.497351E+10 | 18023.79 | 10-JUL-05:02 | 17.00 | 13.94 | 0.634705E+09 | 769.02 | 29-JUL-10:09 | 21.17 | 19.03 |
August | 0.516739E+10 | 17748.14 | 22-AUG-05:03 | 15.00 | 13.18 | 0.685475E+09 | 769.02 | 18-AUG-08:30 | 15.00 | 13.18 |
September | 0.375025E+10 | 17456.02 | 15-SEP-05:03 | 14.00 | 12.83 | 0.634573E+09 | 769.02 | 22-SEP-14:00 | 22.00 | 18.63 |
October | 0.332172E+10 | 19884.76 | 17-OCT-05:03 | 17.00 | 8.55 | 0.632317E+09 | 769.02 | 05-OCT-15:00 | 17.00 | 8.55 |
November | 0.923872E+09 | 2969.05 | 04-NOV-15:00 | 16.70 | 10.78 | 0.593111E+09 | 768.98 | 10-NOV-13:30 | 20.50 | 16.08 |
December | 0.505786E+09 | 2860.57 | 05-DEC-15:30 | 24.00 | 12.83 | 0.600774E+09 | 768.98 | 07-DEC-14:09 | 20.67 | 15.41 |
Annual Sum or Average | 0.278185E+11 | 0.748726E+10 | ||||||||
Minimum of Months | 0.327265E+09 | 2590.54 | 14.00 | 8.55 | 0.542322E+09 | 768.97 | 14.00 | 8.55 | ||
Maximum of Months | 0.516739E+10 | 19884.76 | 24.00 | 17.19 | 0.685475E+09 | 769.02 | 22.33 | 19.03 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111314E+10 | 3948.31 | 12-JAN-09:00 | 8.00 | 8.00 | 0.113062E+10 | 1862.73 | 18-JAN-14:20 | 24.07 | 14.82 |
February | 0.134571E+10 | 3630.93 | 25-FEB-12:55 | 10.00 | 9.41 | 0.104389E+10 | 1863.21 | 03-FEB-15:09 | 10.00 | 9.41 |
March | 0.182032E+10 | 4865.35 | 29-MAR-15:00 | 8.00 | 6.48 | 0.123477E+10 | 2042.95 | 23-MAR-14:00 | 8.00 | 6.48 |
April | 0.186808E+10 | 4212.75 | 26-APR-14:10 | 25.50 | 16.68 | 0.149231E+10 | 2246.83 | 26-APR-14:20 | 25.00 | 16.61 |
May | 0.224028E+10 | 6701.84 | 03-MAY-13:20 | 23.67 | 15.63 | 0.162995E+10 | 2246.85 | 04-MAY-12:30 | 23.50 | 16.62 |
June | 0.360644E+10 | 29673.04 | 25-JUN-16:02 | 21.00 | 16.52 | 0.179176E+10 | 2246.89 | 21-JUN-13:39 | 21.00 | 16.52 |
July | 0.738995E+10 | 37725.17 | 30-JUL-13:03 | 24.00 | 19.79 | 0.183198E+10 | 2246.91 | 24-JUL-14:39 | 24.00 | 19.79 |
August | 0.715750E+10 | 33446.32 | 20-AUG-15:12 | 22.67 | 18.09 | 0.196954E+10 | 2246.92 | 19-AUG-13:30 | 22.67 | 18.09 |
September | 0.338422E+10 | 29185.67 | 04-SEP-15:05 | 20.83 | 16.01 | 0.175141E+10 | 2246.87 | 11-SEP-13:50 | 23.00 | 17.26 |
October | 0.248904E+10 | 29585.76 | 01-OCT-12:50 | 25.17 | 20.35 | 0.168806E+10 | 2246.86 | 18-OCT-13:00 | 22.00 | 18.09 |
November | 0.140368E+10 | 4316.24 | 01-NOV-07:05 | 11.17 | 11.08 | 0.124914E+10 | 1932.17 | 18-NOV-14:20 | 25.33 | 14.85 |
December | 0.118386E+10 | 4315.78 | 01-DEC-08:65 | 9.33 | 9.16 | 0.118738E+10 | 1903.07 | 05-DEC-15:09 | 24.67 | 13.10 |
Annual Sum or Average | 0.350022E+11 | 0.180008E+11 | ||||||||
Minimum of Months | 0.111314E+10 | 3630.93 | 8.00 | 6.48 | 0.104389E+10 | 1862.73 | 8.00 | 6.48 | ||
Maximum of Months | 0.738995E+10 | 37725.17 | 25.50 | 20.35 | 0.196954E+10 | 2246.92 | 25.33 | 19.79 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 | 0.230413E+10 | 3746.33 | 24-JAN-15:39 | 24.33 | 15.19 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 | 0.226207E+10 | 3907.59 | 03-FEB-14:00 | 23.00 | 8.84 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.62 | 0.272464E+10 | 4512.45 | 23-MAR-14:39 | 22.33 | 17.37 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 | 0.348197E+10 | 5574.27 | 26-APR-14:09 | 25.50 | 16.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 | 0.395826E+10 | 6037.09 | 04-MAY-12:39 | 23.33 | 16.64 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 | 0.453617E+10 | 6342.16 | 29-JUN-10:39 | 24.67 | 19.30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 | 0.494902E+10 | 6368.32 | 19-JUL-09:00 | 27.00 | 20.18 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 | 0.530379E+10 | 6381.77 | 19-AUG-12:00 | 27.00 | 20.18 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.83 | 0.449003E+10 | 8413.98 | 29-SEP-13:09 | 35.67 | 18.16 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 | 0.415966E+10 | 8282.56 | 16-OCT-12:09 | 35.68 | 17.48 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.07 | 0.275908E+10 | 4369.56 | 01-NOV-14:30 | 17.00 | 13.18 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.44 | 0.250571E+10 | 3954.12 | 05-DEC-15:09 | 24.67 | 13.10 |
Annual Sum or Average | 0.00 | 0.434345E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 7.63 | 5.44 | 0.226207E+10 | 3746.33 | 17.00 | 8.84 | ||
Maximum of Months | 0.00 | 0.00 | 18.42 | 17.39 | 0.530379E+10 | 8413.98 | 35.68 | 20.18 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.924878E+09 | 25366.78 | 02-JAN-06:12 | 11.00 |
February | 0.555928E+09 | 25247.20 | 28-FEB-06:01 | 10.17 |
March | 0.694202E+09 | 25259.94 | 08-MAR-06:01 | 5.17 |
April | 0.150179E+09 | 25242.99 | 01-APR-05:01 | 7.83 |
May | 89782742.76 | 5060.03 | 15-MAY-05:05 | 8.50 |
June | 47326429.97 | 1278.67 | 19-JUN-06:10 | 17.17 |
July | 11033398.91 | 1232.71 | 14-JUL-06:10 | 17.00 |
August | 15220548.57 | 1321.59 | 23-AUG-06:10 | 16.17 |
September | 34843957.06 | 1357.95 | 15-SEP-06:10 | 14.00 |
October | 55614855.78 | 1327.72 | 19-OCT-06:20 | 11.67 |
November | 0.279012E+09 | 24942.04 | 24-NOV-06:01 | 8.92 |
December | 0.594467E+09 | 25259.89 | 15-DEC-06:01 | 6.00 |
Annual Sum or Average | 0.345249E+10 | |||
Minimum of Months | 11033398.91 | 1232.71 | 5.17 | |
Maximum of Months | 0.924878E+09 | 25366.78 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.630711E+09 | 62715.49 | 09-JAN-06:07 | 2.17 |
February | 90761825.69 | 1934.69 | 01-FEB-12:00 | 26.00 |
March | 0.108994E+09 | 3045.47 | 30-MAR-06:10 | 5.58 |
April | 0.102376E+09 | 1746.18 | 01-APR-12:00 | 24.00 |
May | 69354629.24 | 1021.54 | 25-MAY-07:00 | 14.00 |
June | 69373550.56 | 999.50 | 06-JUN-07:00 | 17.00 |
July | 68035566.24 | 928.35 | 11-JUL-06:13 | 17.00 |
August | 74208738.76 | 938.46 | 21-AUG-07:00 | 17.00 |
September | 79312361.16 | 1998.64 | 29-SEP-08:00 | 29.00 |
October | 0.129886E+09 | 3477.43 | 14-OCT-09:15 | 31.67 |
November | 0.136811E+09 | 1767.05 | 18-NOV-13:00 | 26.00 |
December | 0.275411E+09 | 2523.90 | 16-DEC-13:00 | 26.00 |
Annual Sum or Average | 0.183524E+10 | |||
Minimum of Months | 68035566.24 | 928.35 | 2.17 | |
Maximum of Months | 0.630711E+09 | 62715.49 | 31.67 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.890260E+09 | 1011.11 | 02-JAN-16:49 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.786531E+09 | 993.17 | 27-FEB-16:00 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.896377E+09 | 965.97 | 16-MAR-07:10 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.817626E+09 | 950.24 | 15-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.840851E+09 | 946.55 | 09-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.834075E+09 | 936.82 | 09-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.808413E+09 | 923.89 | 12-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.875078E+09 | 948.09 | 21-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.825094E+09 | 972.11 | 18-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.877472E+09 | 973.37 | 24-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.840575E+09 | 1011.11 | 06-NOV-16:00 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.897665E+09 | 1011.11 | 01-DEC-16:40 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.101900E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.786531E+09 | 923.89 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.897665E+09 | 1011.11 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.343986E+10 | 3643.14 | 21-JAN-15:00 | 0.00 | 0.00 |
February | 0.285412E+10 | 3402.78 | 25-FEB-15:00 | 0.00 | 0.00 |
March | 0.313383E+10 | 3338.55 | 30-MAR-08:09 | 0.00 | 0.00 |
April | 0.288138E+10 | 3255.13 | 03-APR-08:09 | 0.00 | 0.00 |
May | 0.281334E+10 | 3192.96 | 09-MAY-08:09 | 0.00 | 0.00 |
June | 0.282144E+10 | 3097.32 | 14-JUN-08:09 | 0.00 | 0.00 |
July | 0.280408E+10 | 3158.99 | 19-JUL-08:09 | 0.00 | 0.00 |
August | 0.307311E+10 | 3258.19 | 26-AUG-08:09 | 0.00 | 0.00 |
September | 0.297587E+10 | 3402.29 | 21-SEP-08:09 | 0.00 | 0.00 |
October | 0.323869E+10 | 3542.61 | 30-OCT-08:09 | 0.00 | 0.00 |
November | 0.320186E+10 | 3661.94 | 25-NOV-15:00 | 0.00 | 0.00 |
December | 0.350402E+10 | 3668.31 | 18-DEC-15:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.367416E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.280408E+10 | 3097.32 | 0.00 | 0.00 | |
Maximum of Months | 0.350402E+10 | 3668.31 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.352272E+10 | 3826.87 | 21-JAN-15:00 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.293905E+10 | 3507.13 | 27-FEB-16:00 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.320183E+10 | 3292.98 | 01-MAR-16:00 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.288387E+10 | 2976.44 | 21-APR-14:00 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.289206E+10 | 2819.95 | 09-MAY-07:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.284987E+10 | 2698.05 | 09-JUN-07:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.283384E+10 | 2598.71 | 12-JUL-06:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.305888E+10 | 2888.03 | 31-AUG-07:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.298465E+10 | 3290.25 | 21-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.330251E+10 | 3571.51 | 30-OCT-14:00 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.330547E+10 | 3854.45 | 25-NOV-15:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.363057E+10 | 3867.14 | 18-DEC-15:00 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.374053E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.283384E+10 | 2598.71 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.363057E+10 | 3867.14 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.890260E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3985605.30 | 0.994364E+09 |
February | 0.127628E+10 | 0.786531E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 945984.30 | 0.109365E+10 |
March | 0.149825E+10 | 0.896377E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60595.74 | 0.136632E+10 |
April | 0.138726E+10 | 0.817626E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4121576.81 | 0.918158E+09 |
May | 0.144276E+10 | 0.840851E+09 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44082.57 | 0.104415E+10 |
June | 0.144276E+10 | 0.834075E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 812316.22 | 0.712661E+09 |
July | 0.138726E+10 | 0.808413E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22594592.82 | 0.486170E+09 |
August | 0.149825E+10 | 0.875078E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22895591.73 | 0.557975E+09 |
September | 0.138726E+10 | 0.825094E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36190834.03 | 0.605156E+09 |
October | 0.138726E+10 | 0.877472E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71219930.25 | 0.686832E+09 |
November | 0.133177E+10 | 0.840575E+09 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2524488.48 | 0.995393E+09 |
December | 0.138726E+10 | 0.897665E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4425178.80 | 0.982645E+09 |
Annual Sum or Average | 0.168137E+11 | 0.101900E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169821E+09 | 0.104435E+11 |
Minimum of Months | 0.127628E+10 | 0.786531E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44082.57 | 0.486170E+09 |
Maximum of Months | 0.149825E+10 | 0.897665E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71219930.25 | 0.136632E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.343986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27263957.16 | 0.218858E+10 |
February | 0.300332E+10 | 0.285412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2469320.77 | 0.278592E+10 |
March | 0.352563E+10 | 0.313383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 747392.71 | 0.345018E+10 |
April | 0.326447E+10 | 0.288138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7242730.45 | 0.283878E+10 |
May | 0.339505E+10 | 0.281334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357659E+10 |
June | 0.339505E+10 | 0.282144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256618E+10 |
July | 0.326447E+10 | 0.280408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3407850.55 | 0.208995E+10 |
August | 0.352563E+10 | 0.307311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2089156.33 | 0.239159E+10 |
September | 0.326447E+10 | 0.297587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47047039.40 | 0.212298E+10 |
October | 0.326447E+10 | 0.323869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121624E+09 | 0.254035E+10 |
November | 0.313390E+10 | 0.320186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13310119.11 | 0.252466E+10 |
December | 0.326447E+10 | 0.350402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29680543.63 | 0.234841E+10 |
Annual Sum or Average | 0.395654E+11 | 0.367416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254883E+09 | 0.314242E+11 |
Minimum of Months | 0.300332E+10 | 0.280408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208995E+10 |
Maximum of Months | 0.352563E+10 | 0.350402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121624E+09 | 0.357659E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.352272E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469405E+09 | 0.812098E+10 |
February | 0.690763E+10 | 0.293905E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51172847.24 | 0.119512E+11 |
March | 0.810895E+10 | 0.320183E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38073556.30 | 0.155816E+11 |
April | 0.750829E+10 | 0.288387E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60599585.48 | 0.143472E+11 |
May | 0.780862E+10 | 0.289206E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188324E+11 |
June | 0.780862E+10 | 0.284987E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152761E+11 |
July | 0.750829E+10 | 0.283384E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144859E+11 |
August | 0.810895E+10 | 0.305888E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155683E+11 |
September | 0.750829E+10 | 0.298465E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66506455.58 | 0.127149E+11 |
October | 0.750829E+10 | 0.330251E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530569E+09 | 0.132689E+11 |
November | 0.720796E+10 | 0.330547E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166196E+09 | 0.111432E+11 |
December | 0.750829E+10 | 0.363057E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564773E+09 | 0.930058E+10 |
Annual Sum or Average | 0.910005E+11 | 0.374053E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194730E+10 | 0.160591E+12 |
Minimum of Months | 0.690763E+10 | 0.283384E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812098E+10 |
Maximum of Months | 0.810895E+10 | 0.363057E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564773E+09 | 0.188324E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1011.11 | 02-JAN-16:49 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 470.66 | 18-JAN-13:00 | 4622.54 | 09-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 993.17 | 27-FEB-16:00 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 407.30 | 01-FEB-12:10 | 3699.88 | 10-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 965.97 | 16-MAR-07:10 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.22 | 12-MAR-10:00 | 4410.11 | 30-MAR-06:10 |
April | 1680.92 | 01-APR-07:10 | 950.24 | 15-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 479.99 | 26-APR-11:10 | 3507.34 | 17-APR-16:13 |
May | 1680.92 | 01-MAY-07:10 | 946.55 | 09-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 03-MAY-12:00 | 3182.25 | 12-MAY-16:05 |
June | 1680.92 | 01-JUN-07:10 | 936.82 | 09-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.06 | 29-JUN-11:10 | 2421.66 | 05-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 923.89 | 12-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 945.39 | 19-JUL-12:00 | 2082.69 | 17-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 948.09 | 21-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 924.10 | 18-AUG-12:00 | 2261.21 | 28-AUG-07:00 |
September | 1680.92 | 01-SEP-07:10 | 972.11 | 18-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2665.85 | 29-SEP-12:00 | 2487.99 | 20-SEP-07:00 |
October | 1680.92 | 02-OCT-07:10 | 973.37 | 24-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2977.09 | 16-OCT-11:10 | 3213.04 | 19-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 1011.11 | 06-NOV-16:00 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.83 | 19-NOV-13:00 | 3634.14 | 30-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1011.11 | 01-DEC-16:40 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 475.80 | 19-DEC-13:00 | 3985.91 | 13-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 923.89 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 21.22 | 2082.69 | |||||
Maximum of Months | 1680.92 | 1011.11 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 2977.09 | 4622.54 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3643.14 | 21-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1180.83 | 15-JAN-10:00 | 4163.46 | 27-JAN-05:00 |
February | 3955.50 | 01-FEB-08:09 | 3402.78 | 25-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 307.23 | 01-FEB-12:00 | 4151.49 | 25-FEB-16:10 |
March | 3955.50 | 01-MAR-08:09 | 3338.55 | 30-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.50 | 12-MAR-10:00 | 6268.26 | 28-MAR-15:10 |
April | 3955.50 | 01-APR-07:10 | 3255.13 | 03-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.07 | 02-APR-13:00 | 7017.13 | 17-APR-16:25 |
May | 3955.50 | 01-MAY-07:10 | 3192.96 | 09-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 6190.25 | 12-MAY-16:00 |
June | 3955.50 | 01-JUN-07:10 | 3097.32 | 14-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 3541.71 | 12-JUN-16:00 |
July | 3955.50 | 01-JUL-07:10 | 3158.99 | 19-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.76 | 31-JUL-13:00 | 4004.46 | 20-JUL-18:00 |
August | 3955.50 | 01-AUG-07:10 | 3258.19 | 26-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.87 | 17-AUG-14:00 | 3048.04 | 21-AUG-17:00 |
September | 3955.50 | 01-SEP-07:10 | 3402.29 | 21-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2249.71 | 29-SEP-15:10 | 3726.41 | 02-SEP-15:10 |
October | 3955.50 | 02-OCT-07:10 | 3542.61 | 30-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2171.04 | 14-OCT-15:10 | 3906.24 | 07-OCT-08:00 |
November | 3955.50 | 01-NOV-07:10 | 3661.94 | 25-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 827.12 | 19-NOV-13:00 | 4142.70 | 30-NOV-07:10 |
December | 3955.50 | 01-DEC-08:09 | 3668.31 | 18-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 971.34 | 25-DEC-12:00 | 4118.11 | 13-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3097.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3048.04 | ||||
Maximum of Months | 3955.50 | 3668.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2249.71 | 7017.13 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 3826.87 | 21-JAN-15:00 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6664.50 | 14-JAN-11:00 | 15833.80 | 27-JAN-05:00 |
February | 9097.65 | 01-FEB-08:09 | 3507.13 | 27-FEB-16:00 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4594.64 | 01-FEB-12:00 | 21381.57 | 25-FEB-13:10 |
March | 9097.65 | 01-MAR-08:09 | 3292.98 | 01-MAR-16:00 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1908.07 | 11-MAR-13:10 | 25943.07 | 28-MAR-14:20 |
April | 9097.65 | 01-APR-07:10 | 2976.44 | 21-APR-14:00 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3661.08 | 01-APR-12:10 | 30093.60 | 17-APR-16:00 |
May | 9097.65 | 01-MAY-07:10 | 2819.95 | 09-MAY-07:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 28628.10 | 12-MAY-16:00 |
June | 9097.65 | 01-JUN-07:10 | 2698.05 | 09-JUN-07:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 17009.13 | 06-JUN-13:00 |
July | 9097.65 | 01-JUL-07:10 | 2598.71 | 12-JUL-06:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 20879.61 | 20-JUL-09:00 |
August | 9097.65 | 01-AUG-07:10 | 2888.03 | 31-AUG-07:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 15378.26 | 22-AUG-16:00 |
September | 9097.65 | 01-SEP-07:10 | 3290.25 | 21-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6852.10 | 29-SEP-10:42 | 19618.19 | 02-SEP-15:00 |
October | 9097.65 | 02-OCT-07:10 | 3571.51 | 30-OCT-14:00 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14567.49 | 16-OCT-10:00 | 19123.51 | 07-OCT-08:00 |
November | 9097.65 | 01-NOV-07:10 | 3854.45 | 25-NOV-15:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4035.21 | 19-NOV-13:00 | 15404.61 | 01-NOV-08:00 |
December | 9097.65 | 01-DEC-08:09 | 3867.14 | 18-DEC-15:00 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11336.14 | 18-DEC-11:00 | 17260.84 | 12-DEC-13:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 2598.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15378.26 | |||||
Maximum of Months | 9097.65 | 3867.14 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 14567.49 | 30093.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2590.54 | 21-JAN-15:00 | 1680.92 | 735.76 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.96 |
February | 2705.94 | 03-FEB-15:20 | 1680.92 | 644.94 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.57 |
March | 3584.62 | 23-MAR-16:00 | 1680.92 | 616.78 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.88 |
April | 4947.51 | 26-APR-15:40 | 1680.92 | 616.78 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.51 |
May | 5529.12 | 03-MAY-15:00 | 1680.92 | 616.78 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.83 |
June | 18327.57 | 23-JUN-05:03 | 739.61 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.14 |
July | 18023.79 | 10-JUL-05:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.86 |
August | 17748.14 | 22-AUG-05:03 | 739.61 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 511.43 |
September | 17456.02 | 15-SEP-05:03 | 554.70 | 152.99 | 1651.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.50 |
October | 19884.76 | 17-OCT-05:03 | 554.70 | 152.99 | 1651.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.36 |
November | 2969.05 | 04-NOV-15:00 | 1680.92 | 649.24 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.24 |
December | 2860.57 | 05-DEC-15:30 | 1680.92 | 651.52 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 4.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2590.54 | 554.70 | 152.99 | 1651.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19884.76 | 1680.92 | 735.76 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 4.32 | 511.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3948.31 | 12-JAN-09:00 | 3955.50 | 2966.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3630.93 | 25-FEB-12:55 | 4192.83 | 5256.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.32 |
March | 4865.35 | 29-MAR-15:00 | 3955.50 | 2233.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 613.42 |
April | 4212.75 | 26-APR-14:10 | 3955.50 | 2441.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.37 |
May | 6701.84 | 03-MAY-13:20 | 3955.50 | 2204.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.81 |
June | 29673.04 | 25-JUN-16:02 | 0.00 | 1499.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1391.79 |
July | 37725.17 | 30-JUL-13:03 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.34 |
August | 33446.32 | 20-AUG-15:12 | 0.00 | 1799.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1010.60 |
September | 29185.67 | 04-SEP-15:05 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1448.53 |
October | 29585.76 | 01-OCT-12:50 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 482.29 |
November | 4316.24 | 01-NOV-07:05 | 7911.00 | 6197.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3140.27 |
December | 4315.78 | 01-DEC-08:65 | 7911.00 | 5804.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3630.93 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37725.17 | 7911.00 | 6197.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3140.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.02 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5098.22 |
April | 0.00 | 01-APR-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8006.58 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5729.74 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4343.58 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3469.72 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4608.39 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5052.82 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7250.55 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5648.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8006.58 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.298238E+11 | 27389.76 | 10-JAN-16:00 | 0.150207E+10 | 28527.10 | 03-JAN-06:10 |
February | 0.261837E+11 | 21574.99 | 25-FEB-15:00 | 0.536578E+09 | 11657.03 | 28-FEB-06:10 |
March | 0.291386E+11 | 21254.23 | 11-MAR-15:00 | 0.748762E+09 | 15712.02 | 30-MAR-05:10 |
April | 0.267068E+11 | 21956.09 | 26-APR-12:00 | 58493591.88 | 12112.93 | 01-APR-05:10 |
May | 0.269634E+11 | 21205.77 | 03-MAY-12:39 | 4149365.36 | 3675.54 | 15-MAY-05:10 |
June | 0.272202E+11 | 23728.25 | 29-JUN-13:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.288642E+11 | 28133.24 | 31-JUL-13:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.309217E+11 | 28861.15 | 17-AUG-14:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.281731E+11 | 29124.30 | 30-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.297582E+11 | 29399.52 | 16-OCT-12:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.283109E+11 | 27387.78 | 28-NOV-16:00 | 0.190793E+09 | 8795.01 | 27-NOV-06:10 |
December | 0.301292E+11 | 27696.97 | 05-DEC-16:40 | 0.556826E+09 | 12292.31 | 15-DEC-06:10 |
Annual Sum or Average | 0.342194E+12 | 0.359768E+10 | ||||
Minimum of Months | 0.261837E+11 | 21205.77 | 0.00 | 0.00 | ||
Maximum of Months | 0.309217E+11 | 29399.52 | 0.150207E+10 | 28527.10 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.785285E+10 | 0.641943E+10 | 0.112984E+11 | 0.00 | 0.209581E+10 | 0.00 | 0.00 | 45654225.08 | 0.00 | 0.00 | 0.00 | 0.211165E+10 | 0.00 |
February | 0.657970E+10 | 0.538371E+10 | 0.103734E+11 | 0.00 | 0.191416E+10 | 0.00 | 0.00 | 13004121.02 | 0.00 | 0.00 | 0.00 | 0.191976E+10 | 0.00 |
March | 0.723204E+10 | 0.535943E+10 | 0.121089E+11 | 0.00 | 0.224729E+10 | 0.00 | 0.00 | 32413023.28 | 0.00 | 0.00 | 0.00 | 0.215849E+10 | 0.00 |
April | 0.658287E+10 | 0.459682E+10 | 0.112578E+11 | 0.00 | 0.207090E+10 | 0.00 | 0.00 | 0.159154E+09 | 0.00 | 0.00 | 0.00 | 0.203928E+10 | 0.00 |
May | 0.654625E+10 | 0.428414E+10 | 0.117000E+11 | 0.00 | 0.215269E+10 | 0.00 | 0.00 | 0.189048E+09 | 0.00 | 0.00 | 0.00 | 0.209136E+10 | 0.00 |
June | 0.650539E+10 | 0.393324E+10 | 0.116594E+11 | 0.00 | 0.217727E+10 | 0.00 | 0.00 | 0.918265E+09 | 0.00 | 0.00 | 0.00 | 0.202663E+10 | 0.00 |
July | 0.644633E+10 | 0.412160E+10 | 0.112984E+11 | 0.00 | 0.223110E+10 | 0.00 | 0.00 | 0.273209E+10 | 0.00 | 0.00 | 0.00 | 0.203472E+10 | 0.00 |
August | 0.700707E+10 | 0.451475E+10 | 0.121016E+11 | 0.00 | 0.236804E+10 | 0.00 | 0.00 | 0.284568E+10 | 0.00 | 0.00 | 0.00 | 0.208457E+10 | 0.00 |
September | 0.678561E+10 | 0.493469E+10 | 0.112504E+11 | 0.00 | 0.218828E+10 | 0.00 | 0.00 | 0.101520E+10 | 0.00 | 0.00 | 0.00 | 0.199892E+10 | 0.00 |
October | 0.741868E+10 | 0.571056E+10 | 0.113057E+11 | 0.00 | 0.215569E+10 | 0.00 | 0.00 | 0.110758E+10 | 0.00 | 0.00 | 0.00 | 0.205998E+10 | 0.00 |
November | 0.734791E+10 | 0.606094E+10 | 0.108562E+11 | 0.00 | 0.199115E+10 | 0.00 | 0.00 | 43535213.43 | 0.00 | 0.00 | 0.00 | 0.201116E+10 | 0.00 |
December | 0.803226E+10 | 0.656518E+10 | 0.112984E+11 | 0.00 | 0.207984E+10 | 0.00 | 0.00 | 52581545.03 | 0.00 | 0.00 | 0.00 | 0.210098E+10 | 0.00 |
Annual Sum or Average | 0.843370E+11 | 0.618845E+11 | 0.136508E+12 | 0.00 | 0.256722E+11 | 0.00 | 0.00 | 0.915419E+10 | 0.00 | 0.00 | 0.00 | 0.246375E+11 | 0.00 |
Minimum of Months | 0.644633E+10 | 0.393324E+10 | 0.103734E+11 | 0.00 | 0.191416E+10 | 0.00 | 0.00 | 13004121.02 | 0.00 | 0.00 | 0.00 | 0.191976E+10 | 0.00 |
Maximum of Months | 0.803226E+10 | 0.656518E+10 | 0.121089E+11 | 0.00 | 0.236804E+10 | 0.00 | 0.00 | 0.284568E+10 | 0.00 | 0.00 | 0.00 | 0.215849E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.150207E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.536578E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.748762E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 58493591.88 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 4149365.36 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.190793E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.556826E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.359768E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.150207E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 8152.55 | 21-JAN-15:00 | 5520.82 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 2165.85 | 04-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 7783.08 | 27-FEB-16:00 | 5520.82 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 2090.57 | 01-FEB-10:50 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 7242.53 | 28-MAR-08:09 | 5520.82 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 2141.06 | 30-MAR-06:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 7110.92 | 21-APR-14:00 | 5520.82 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 2090.57 | 04-APR-12:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 6935.89 | 09-MAY-08:09 | 5520.82 | 01-MAY-18:30 | 10035.17 | 01-MAY-07:10 | 0.00 | 2090.57 | 01-MAY-14:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 6563.24 | 09-JUN-07:10 | 5520.82 | 01-JUN-18:49 | 10035.17 | 01-JUN-07:10 | 0.00 | 2666.89 | 29-JUN-10:39 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 6418.72 | 19-JUL-07:10 | 5520.82 | 01-JUL-18:00 | 10035.17 | 01-JUL-07:10 | 0.00 | 4395.86 | 31-JUL-12:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 6919.19 | 31-AUG-07:10 | 5520.82 | 01-AUG-18:49 | 10035.17 | 01-AUG-07:10 | 0.00 | 4395.86 | 17-AUG-13:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 7649.02 | 21-SEP-08:09 | 5520.82 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 4395.86 | 29-SEP-10:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 7919.08 | 30-OCT-08:09 | 5520.82 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 4395.86 | 16-OCT-10:39 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 8195.29 | 25-NOV-15:00 | 5520.82 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 2090.57 | 22-NOV-10:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 8259.84 | 06-DEC-15:00 | 5520.82 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 2090.57 | 04-DEC-11:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 6418.72 | 5520.82 | 10035.17 | 0.00 | 2090.57 | 0.00 | 0.00 | |||||
Maximum of Months | 8259.84 | 5520.82 | 10035.17 | 0.00 | 4395.86 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 789.86 | 24-JAN-15:30 | 0.00 | 0.00 | 0.00 | 1797.23 | 30-JAN-12:39 | 0.00 |
February | 653.57 | 01-FEB-11:00 | 0.00 | 0.00 | 0.00 | 1797.32 | 11-FEB-12:09 | 0.00 |
March | 913.34 | 23-MAR-13:00 | 0.00 | 0.00 | 0.00 | 1795.48 | 01-MAR-12:30 | 0.00 |
April | 2734.93 | 26-APR-13:09 | 0.00 | 0.00 | 0.00 | 1789.74 | 01-APR-11:09 | 0.00 |
May | 2343.40 | 04-MAY-12:09 | 0.00 | 0.00 | 0.00 | 1781.58 | 02-MAY-11:50 | 0.00 |
June | 5696.10 | 29-JUN-18:10 | 0.00 | 0.00 | 0.00 | 1772.78 | 01-JUN-11:09 | 0.00 |
July | 6914.23 | 31-JUL-14:20 | 0.00 | 0.00 | 0.00 | 1767.47 | 01-JUL-11:20 | 0.00 |
August | 7065.43 | 17-AUG-13:00 | 0.00 | 0.00 | 0.00 | 1766.39 | 31-AUG-11:09 | 0.00 |
September | 7686.30 | 29-SEP-12:00 | 0.00 | 0.00 | 0.00 | 1771.97 | 30-SEP-11:20 | 0.00 |
October | 7946.39 | 16-OCT-11:00 | 0.00 | 0.00 | 0.00 | 1779.99 | 31-OCT-11:00 | 0.00 |
November | 885.62 | 18-NOV-13:00 | 0.00 | 0.00 | 0.00 | 1787.54 | 28-NOV-12:09 | 0.00 |
December | 870.83 | 05-DEC-14:00 | 0.00 | 0.00 | 0.00 | 1794.48 | 30-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 653.57 | 0.00 | 0.00 | 0.00 | 1766.39 | 0.00 | ||
Maximum of Months | 7946.39 | 0.00 | 0.00 | 0.00 | 1797.32 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 27389.76 | 10-JAN-16:00 | 8142.10 | 10035.17 | 5520.82 | 0.00 | 2090.57 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21574.99 | 25-FEB-15:00 | 7691.28 | 10035.17 | 0.00 | 0.00 | 2090.57 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21254.23 | 11-MAR-15:00 | 6889.89 | 10035.17 | 0.00 | 0.00 | 2090.57 | 0.00 | 0.00 | 482.39 | 0.00 |
April | 21956.09 | 26-APR-12:00 | 5385.04 | 10035.17 | 0.00 | 0.00 | 2090.57 | 0.00 | 0.00 | 2697.67 | 0.00 |
May | 21205.77 | 03-MAY-12:39 | 5138.95 | 10035.17 | 0.00 | 0.00 | 2090.57 | 0.00 | 0.00 | 2195.71 | 0.00 |
June | 23728.25 | 29-JUN-13:20 | 5130.93 | 10035.17 | 0.00 | 0.00 | 2551.62 | 0.00 | 0.00 | 4307.40 | 0.00 |
July | 28133.24 | 31-JUL-13:09 | 5131.37 | 10035.17 | 0.00 | 0.00 | 4395.86 | 0.00 | 0.00 | 6869.72 | 0.00 |
August | 28861.15 | 17-AUG-14:30 | 5705.11 | 10035.17 | 0.00 | 0.00 | 4395.86 | 0.00 | 0.00 | 6992.75 | 0.00 |
September | 29124.30 | 30-SEP-14:00 | 6125.85 | 10035.17 | 0.00 | 0.00 | 4395.86 | 0.00 | 0.00 | 6829.68 | 0.00 |
October | 29399.52 | 16-OCT-12:20 | 5701.43 | 10035.17 | 0.00 | 0.00 | 4395.86 | 0.00 | 0.00 | 7525.58 | 0.00 |
November | 27387.78 | 28-NOV-16:00 | 8142.10 | 10035.17 | 5520.82 | 0.00 | 2090.57 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 27696.97 | 05-DEC-16:40 | 8142.10 | 10035.17 | 5520.82 | 0.00 | 2090.57 | 0.00 | 0.00 | 308.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 21205.77 | 5130.93 | 10035.17 | 0.00 | 0.00 | 2090.57 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29399.52 | 8142.10 | 10035.17 | 5520.82 | 0.00 | 4395.86 | 0.00 | 0.00 | 7525.58 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 28527.10 | 03-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 11657.03 | 28-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 15712.02 | 30-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 12112.93 | 01-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 3675.54 | 15-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 8795.01 | 27-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 12292.31 | 15-DEC-06:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 28527.10 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.50 | 20.18 | 3.50 | 20.18 | 0.00 | 20.18 | 0.00 | 20.18 |
February | 1.83 | 20.46 | 1.83 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
March | 2.67 | 20.34 | 2.67 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
April | 0.17 | 20.31 | 0.17 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.50 | 0.33 | 24.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.51 | 0.33 | 24.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.55 | 0.83 | 24.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.50 | 1.50 | 24.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.50 | 0.17 | 24.50 |
November | 1.00 | 20.48 | 1.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
December | 1.33 | 20.42 | 1.33 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Annual Sum or Average | 10.50 | 20.33 | 10.50 | 20.33 | 3.17 | 20.88 | 3.17 | 21.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.50 | 20.48 | 3.50 | 20.48 | 1.50 | 24.55 | 1.50 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 14.94 | 0.00 | 14.94 | 0.00 | 14.94 | 0.00 | 14.94 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.34 | 0.00 | 27.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.28 | 0.00 | 27.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.38 | 0.00 | 27.38 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.37 | 0.00 | 27.37 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.50 | 14.94 | 0.00 | 14.94 | 2.67 | 22.87 | 0.00 | 22.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 14.94 | 0.00 | 14.94 | 1.67 | 27.38 | 0.00 | 27.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 22.69 | 76.00 | 22.39 | 76.00 | 22.18 |
February | 276.00 | 22.73 | 43.17 | 22.52 | 43.17 | 22.36 |
March | 313.00 | 22.67 | 48.50 | 22.47 | 46.83 | 22.31 |
April | 204.50 | 23.34 | 42.33 | 23.38 | 5.17 | 23.33 |
May | 161.17 | 23.49 | 54.83 | 23.60 | 0.00 | 23.60 |
June | 53.50 | 23.66 | 175.67 | 23.85 | 1.50 | 23.85 |
July | 11.33 | 23.78 | 291.17 | 23.90 | 10.33 | 23.90 |
August | 24.50 | 23.81 | 311.50 | 23.90 | 22.50 | 23.90 |
September | 33.00 | 23.71 | 210.50 | 23.88 | 14.50 | 23.88 |
October | 129.67 | 23.60 | 98.67 | 23.73 | 22.00 | 23.75 |
November | 283.33 | 23.24 | 16.17 | 23.12 | 16.17 | 23.02 |
December | 300.00 | 22.92 | 57.00 | 22.64 | 57.00 | 22.44 |
Annual Sum or Average | 2090.00 | 23.04 | 1425.50 | 23.20 | 315.17 | 23.08 |
Minimum of Months | 11.33 | 22.67 | 16.17 | 22.39 | 0.00 | 22.18 |
Maximum of Months | 313.00 | 23.81 | 311.50 | 23.90 | 76.00 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.20 | 166.33 | 19.66 | 166.33 | 19.40 |
February | 276.00 | 20.35 | 133.17 | 19.84 | 133.17 | 19.58 |
March | 306.67 | 20.19 | 153.50 | 19.84 | 139.50 | 19.55 |
April | 166.00 | 22.09 | 122.83 | 23.25 | 13.67 | 23.06 |
May | 133.50 | 22.64 | 158.67 | 24.18 | 6.00 | 24.16 |
June | 126.50 | 25.56 | 254.67 | 25.84 | 87.33 | 25.99 |
July | 234.67 | 26.62 | 300.00 | 26.50 | 234.67 | 26.54 |
August | 262.17 | 26.54 | 323.67 | 26.43 | 262.17 | 26.46 |
September | 148.67 | 26.00 | 261.50 | 26.00 | 132.00 | 26.08 |
October | 133.50 | 24.37 | 203.17 | 25.37 | 64.33 | 25.49 |
November | 281.33 | 21.77 | 64.83 | 21.35 | 64.00 | 21.06 |
December | 300.00 | 20.74 | 134.50 | 20.21 | 134.50 | 19.94 |
Annual Sum or Average | 2669.00 | 22.65 | 2276.83 | 23.27 | 1437.67 | 23.21 |
Minimum of Months | 126.50 | 20.19 | 64.83 | 19.66 | 6.00 | 19.40 |
Maximum of Months | 306.67 | 26.62 | 323.67 | 26.50 | 262.17 | 26.54 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 18.94 | 215.17 | 18.51 | 215.17 | 18.33 |
February | 276.00 | 19.73 | 174.67 | 19.31 | 174.67 | 19.13 |
March | 309.83 | 19.78 | 181.83 | 19.41 | 174.00 | 19.18 |
April | 169.33 | 22.34 | 124.17 | 23.45 | 26.17 | 23.36 |
May | 130.83 | 24.02 | 189.83 | 25.20 | 38.33 | 25.44 |
June | 170.67 | 27.66 | 275.83 | 27.32 | 149.33 | 27.57 |
July | 278.83 | 28.74 | 300.00 | 28.66 | 278.83 | 28.69 |
August | 299.50 | 28.62 | 324.00 | 28.52 | 299.50 | 28.55 |
September | 199.83 | 27.87 | 291.33 | 27.45 | 194.67 | 27.60 |
October | 151.83 | 26.23 | 223.67 | 26.64 | 101.50 | 26.96 |
November | 285.33 | 21.34 | 85.83 | 20.86 | 85.83 | 20.56 |
December | 300.00 | 19.85 | 212.00 | 19.54 | 212.00 | 19.41 |
Annual Sum or Average | 2872.00 | 23.36 | 2598.33 | 23.87 | 1950.00 | 23.90 |
Minimum of Months | 130.83 | 18.94 | 85.83 | 18.51 | 26.17 | 18.33 |
Maximum of Months | 309.83 | 28.74 | 324.00 | 28.66 | 299.50 | 28.69 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.210711E+09 | 45654225.08 | 33.92 | 0.205457E+09 | 5254338.33 | 0.00 | 0.43 | 24-JAN-15:30 | 0.00 | 01-JAN-00:10 | 3735.83 | 24-JAN-15:30 | 3622.38 | 24-JAN-15:30 | 443.42 | 17-JAN-14:00 | 789.86 | 24-JAN-15:30 | 0.00 | 01-JAN-00:10 |
February | 60094539.11 | 13004121.02 | 16.00 | 60027650.14 | 66888.97 | 0.00 | 0.38 | 03-FEB-15:00 | 0.00 | 01-FEB-00:10 | 2986.51 | 03-FEB-15:00 | 2986.51 | 03-FEB-15:00 | 81.07 | 01-FEB-13:30 | 653.57 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 |
March | 0.151485E+09 | 32413023.28 | 26.17 | 0.131120E+09 | 20365694.73 | 0.00 | 0.48 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 | 4428.87 | 23-MAR-14:00 | 3445.89 | 23-MAR-14:00 | 1132.57 | 23-MAR-15:00 | 913.34 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.707388E+09 | 0.148595E+09 | 80.25 | 0.589816E+09 | 0.117572E+09 | 0.00 | 0.73 | 26-APR-14:00 | 0.00 | 01-APR-00:10 | 6762.75 | 26-APR-14:20 | 6113.70 | 26-APR-14:00 | 1262.46 | 11-APR-15:00 | 1388.23 | 26-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.818251E+09 | 0.171923E+09 | 101.25 | 0.700375E+09 | 0.117876E+09 | 0.00 | 0.70 | 03-MAY-14:00 | 0.00 | 01-MAY-00:10 | 6522.38 | 03-MAY-14:00 | 6021.01 | 03-MAY-13:00 | 1094.49 | 02-MAY-15:00 | 1302.49 | 03-MAY-14:00 | 0.00 | 01-MAY-00:10 |
June | 0.298699E+10 | 0.603208E+09 | 190.96 | 0.226669E+10 | 0.720304E+09 | 0.00 | 1.00 | 06-JUN-05:03 | 0.00 | 01-JUN-00:10 | 18341.93 | 30-JUN-05:02 | 11796.24 | 21-JUN-05:03 | 8823.02 | 28-JUN-05:02 | 3664.97 | 30-JUN-05:02 | 0.00 | 01-JUN-00:10 |
July | 0.611187E+10 | 0.120481E+10 | 257.12 | 0.441000E+10 | 0.170188E+10 | 0.00 | 1.00 | 01-JUL-05:02 | 0.00 | 01-JUL-00:10 | 18916.11 | 29-JUL-05:02 | 12286.24 | 10-JUL-05:02 | 9537.83 | 24-JUL-05:03 | 3758.55 | 29-JUL-05:02 | 0.00 | 01-JUL-00:10 |
August | 0.672888E+10 | 0.132080E+10 | 272.53 | 0.475615E+10 | 0.197272E+10 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 19221.34 | 07-AUG-05:02 | 11612.94 | 30-AUG-05:03 | 10259.05 | 07-AUG-05:04 | 3805.96 | 07-AUG-05:02 | 0.00 | 01-AUG-00:10 |
September | 0.323928E+10 | 0.673193E+09 | 195.49 | 0.246512E+10 | 0.774162E+09 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 18245.22 | 09-SEP-05:03 | 17117.24 | 30-SEP-05:02 | 8444.51 | 14-SEP-05:03 | 3648.64 | 09-SEP-05:03 | 0.00 | 01-SEP-00:10 |
October | 0.319975E+10 | 0.672553E+09 | 199.27 | 0.267824E+10 | 0.521509E+09 | 0.00 | 1.00 | 02-OCT-05:02 | 0.00 | 01-OCT-00:10 | 19548.64 | 05-OCT-05:02 | 15954.39 | 16-OCT-05:03 | 9521.99 | 05-OCT-05:04 | 3855.00 | 05-OCT-05:02 | 0.00 | 01-OCT-00:10 |
November | 0.202242E+09 | 43535213.43 | 40.33 | 0.201118E+09 | 1124469.24 | 0.00 | 0.48 | 18-NOV-14:00 | 0.00 | 01-NOV-00:10 | 4106.16 | 18-NOV-14:30 | 4106.16 | 18-NOV-14:30 | 287.07 | 10-NOV-13:10 | 885.62 | 18-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.242786E+09 | 52581545.03 | 43.25 | 0.242291E+09 | 494371.44 | 0.00 | 0.49 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 | 4099.57 | 05-DEC-15:00 | 4099.57 | 05-DEC-15:00 | 199.83 | 07-DEC-14:00 | 870.83 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.246597E+11 | 0.498228E+10 | 1456.53 | 0.187064E+11 | 0.595333E+10 | 0.00 | ||||||||||||||
Minimum of Months | 60094539.11 | 13004121.02 | 16.00 | 60027650.14 | 66888.97 | 0.00 | 0.38 | 0.00 | 2986.51 | 2986.51 | 81.07 | 653.57 | 0.00 | |||||||
Maximum of Months | 0.672888E+10 | 0.132080E+10 | 272.53 | 0.475615E+10 | 0.197272E+10 | 0.00 | 1.00 | 0.00 | 19548.64 | 17117.24 | 10259.05 | 3855.00 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 40291121.75 | 10559256.84 | 3.50 | 35965000.49 | 4326121.27 | 0.00 | 0.24 | 26-APR-13:10 | 0.00 | 01-APR-00:10 | 5233.89 | 26-APR-13:10 | 4632.48 | 26-APR-13:10 | 601.41 | 26-APR-13:10 | 1371.91 | 26-APR-13:10 | 0.00 | 01-APR-00:10 |
May | 67177869.05 | 17125319.21 | 8.00 | 56744039.68 | 10433829.37 | 0.00 | 0.20 | 03-MAY-13:00 | 0.00 | 01-MAY-00:10 | 4197.99 | 04-MAY-12:10 | 3946.22 | 03-MAY-13:00 | 759.80 | 04-MAY-12:30 | 1059.71 | 04-MAY-12:10 | 0.00 | 01-MAY-00:10 |
June | 0.129710E+10 | 0.315058E+09 | 65.48 | 0.892555E+09 | 0.404550E+09 | 0.00 | 1.00 | 18-JUN-14:15 | 0.00 | 01-JUN-00:10 | 52354.93 | 29-JUN-17:22 | 38964.21 | 25-JUN-12:35 | 21029.35 | 29-JUN-18:05 | 11422.53 | 29-JUN-17:22 | 0.00 | 01-JUN-00:10 |
July | 0.646494E+10 | 0.152727E+10 | 186.03 | 0.436594E+10 | 0.209900E+10 | 0.00 | 1.00 | 01-JUL-17:25 | 0.00 | 01-JUL-00:10 | 54501.70 | 19-JUL-17:10 | 40241.11 | 19-JUL-17:10 | 23610.27 | 24-JUL-18:05 | 11922.36 | 23-JUL-11:05 | 0.00 | 01-JUL-00:10 |
August | 0.641032E+10 | 0.152487E+10 | 194.12 | 0.419939E+10 | 0.221093E+10 | 0.00 | 1.00 | 03-AUG-17:45 | 0.00 | 01-AUG-00:10 | 54250.68 | 06-AUG-10:25 | 37941.44 | 19-AUG-17:12 | 24618.94 | 18-AUG-17:25 | 11921.01 | 06-AUG-13:03 | 0.00 | 01-AUG-00:10 |
September | 0.128230E+10 | 0.342002E+09 | 51.53 | 0.115063E+10 | 0.131677E+09 | 0.00 | 1.00 | 04-SEP-13:25 | 0.00 | 01-SEP-00:10 | 52052.55 | 10-SEP-13:33 | 35695.90 | 04-SEP-15:05 | 19150.95 | 10-SEP-12:45 | 11371.83 | 10-SEP-13:33 | 0.00 | 01-SEP-00:10 |
October | 0.162433E+10 | 0.435027E+09 | 55.80 | 0.147458E+10 | 0.149750E+09 | 0.00 | 1.00 | 01-OCT-11:23 | 0.00 | 01-OCT-00:10 | 54384.21 | 01-OCT-12:05 | 34356.29 | 01-OCT-12:05 | 22492.85 | 01-OCT-15:40 | 12008.21 | 01-OCT-12:05 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.171865E+11 | 0.417191E+10 | 564.45 | 0.121758E+11 | 0.501067E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.646494E+10 | 0.152727E+10 | 194.12 | 0.436594E+10 | 0.221093E+10 | 0.00 | 1.00 | 0.00 | 54501.70 | 40241.11 | 24618.94 | 12008.21 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.01 | 32.28 | 31.73 | 89.05 | 71.74 | 0.00 | 0.00 | 0.00 |
February | 76.29 | 35.20 | 41.09 | 100.72 | 64.60 | 0.00 | 0.00 | 0.00 |
March | 87.43 | 38.66 | 48.76 | 116.64 | 67.59 | 0.00 | 0.00 | 0.00 |
April | 120.35 | 62.54 | 57.81 | 171.63 | 62.68 | 0.00 | 0.00 | 0.00 |
May | 118.26 | 54.49 | 63.77 | 161.96 | 60.29 | 0.00 | 0.00 | 0.00 |
June | 125.56 | 62.80 | 62.76 | 178.66 | 50.71 | 0.00 | 0.00 | 0.00 |
July | 132.93 | 71.15 | 61.78 | 196.22 | 49.71 | 0.00 | 0.00 | 0.00 |
August | 124.52 | 67.41 | 57.11 | 186.86 | 51.47 | 0.00 | 0.00 | 0.00 |
September | 106.62 | 56.99 | 49.63 | 156.27 | 56.15 | 0.00 | 0.00 | 0.00 |
October | 81.60 | 44.57 | 37.03 | 123.09 | 60.57 | 0.00 | 0.00 | 0.00 |
November | 73.58 | 38.42 | 35.15 | 101.16 | 71.04 | 0.00 | 0.00 | 0.00 |
December | 64.87 | 34.69 | 30.18 | 90.36 | 75.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98.09 | 50.00 | 48.09 | 139.57 | 61.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.01 | 32.28 | 30.18 | 89.05 | 49.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.93 | 71.15 | 63.77 | 196.22 | 75.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.01 | 32.28 | 31.73 | 89.05 | 71.74 | 0.00 | 0.00 | 0.00 |
February | 76.29 | 35.20 | 41.09 | 100.72 | 64.60 | 0.00 | 0.00 | 0.00 |
March | 87.43 | 38.66 | 48.76 | 116.64 | 67.59 | 0.00 | 0.00 | 0.00 |
April | 120.35 | 62.54 | 57.81 | 171.63 | 62.68 | 0.00 | 0.00 | 0.00 |
May | 118.26 | 54.49 | 63.77 | 161.96 | 60.29 | 0.00 | 0.00 | 0.00 |
June | 125.56 | 62.80 | 62.76 | 178.66 | 50.71 | 0.00 | 0.00 | 0.00 |
July | 132.93 | 71.15 | 61.78 | 196.22 | 49.71 | 0.00 | 0.00 | 0.00 |
August | 124.52 | 67.41 | 57.11 | 186.86 | 51.47 | 0.00 | 0.00 | 0.00 |
September | 106.62 | 56.99 | 49.63 | 156.27 | 56.15 | 0.00 | 0.00 | 0.00 |
October | 81.60 | 44.57 | 37.03 | 123.09 | 60.57 | 0.00 | 0.00 | 0.00 |
November | 73.58 | 38.42 | 35.15 | 101.16 | 71.04 | 0.00 | 0.00 | 0.00 |
December | 64.87 | 34.69 | 30.18 | 90.36 | 75.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98.09 | 50.00 | 48.09 | 139.57 | 61.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.01 | 32.28 | 30.18 | 89.05 | 49.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.93 | 71.15 | 63.77 | 196.22 | 75.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.54 | 0.00 | 14.54 | 12.32 | 42.89 | 0.00 | 0.00 | 0.00 |
February | 18.25 | 0.00 | 18.25 | 14.42 | 38.80 | 0.00 | 0.00 | 0.00 |
March | 22.36 | 0.00 | 22.36 | 19.81 | 40.54 | 0.00 | 0.00 | 0.00 |
April | 25.83 | 0.15 | 25.68 | 23.53 | 36.76 | 0.00 | 0.00 | 0.00 |
May | 31.15 | 1.62 | 29.53 | 29.38 | 33.94 | 0.00 | 0.00 | 0.00 |
June | 32.94 | 3.18 | 29.76 | 35.11 | 28.55 | 0.00 | 0.00 | 0.00 |
July | 31.20 | 2.57 | 28.62 | 34.59 | 28.35 | 0.00 | 0.00 | 0.00 |
August | 26.04 | 0.61 | 25.43 | 27.94 | 29.71 | 0.00 | 0.00 | 0.00 |
September | 21.96 | 0.01 | 21.95 | 22.21 | 33.87 | 0.00 | 0.00 | 0.00 |
October | 17.42 | 0.00 | 17.42 | 19.69 | 36.16 | 0.00 | 0.00 | 0.00 |
November | 15.77 | 0.00 | 15.77 | 12.47 | 42.80 | 0.00 | 0.00 | 0.00 |
December | 13.53 | 0.00 | 13.53 | 10.59 | 45.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.60 | 0.68 | 21.92 | 21.88 | 36.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.53 | 0.00 | 13.53 | 10.59 | 28.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.94 | 3.18 | 29.76 | 35.11 | 45.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.54 | 0.00 | 14.54 | 12.32 | 42.89 | 0.00 | 0.00 | 0.00 |
February | 18.25 | 0.00 | 18.25 | 14.42 | 38.80 | 0.00 | 0.00 | 0.00 |
March | 22.36 | 0.00 | 22.36 | 19.81 | 40.54 | 0.00 | 0.00 | 0.00 |
April | 25.83 | 0.15 | 25.68 | 23.53 | 36.76 | 0.00 | 0.00 | 0.00 |
May | 31.15 | 1.62 | 29.53 | 29.37 | 33.94 | 0.00 | 0.00 | 0.00 |
June | 32.94 | 3.18 | 29.76 | 35.11 | 28.55 | 0.00 | 0.00 | 0.00 |
July | 31.19 | 2.57 | 28.62 | 34.59 | 28.35 | 0.00 | 0.00 | 0.00 |
August | 26.04 | 0.61 | 25.43 | 27.94 | 29.71 | 0.00 | 0.00 | 0.00 |
September | 21.96 | 0.01 | 21.95 | 22.21 | 33.87 | 0.00 | 0.00 | 0.00 |
October | 17.41 | 0.00 | 17.41 | 19.69 | 36.16 | 0.00 | 0.00 | 0.00 |
November | 15.77 | 0.00 | 15.77 | 12.47 | 42.80 | 0.00 | 0.00 | 0.00 |
December | 13.53 | 0.00 | 13.53 | 10.59 | 45.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.60 | 0.68 | 21.92 | 21.88 | 36.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.53 | 0.00 | 13.53 | 10.59 | 28.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.94 | 3.18 | 29.76 | 35.11 | 45.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.36 | 21.68 | 11.67 | 42.82 | 31.01 | 0.67 | 0.00 | 0.00 |
February | 38.65 | 21.59 | 17.07 | 48.14 | 26.76 | 0.00 | 0.00 | 0.00 |
March | 50.77 | 28.84 | 21.93 | 65.43 | 26.58 | 0.00 | 0.00 | 0.00 |
April | 76.79 | 55.81 | 20.97 | 100.30 | 26.32 | 0.00 | 0.00 | 0.00 |
May | 76.73 | 49.40 | 27.33 | 98.32 | 25.25 | 0.00 | 0.00 | 0.00 |
June | 81.58 | 56.26 | 25.33 | 105.71 | 21.70 | 0.00 | 0.00 | 0.00 |
July | 89.55 | 67.20 | 22.35 | 117.55 | 22.67 | 0.00 | 0.00 | 0.00 |
August | 82.83 | 63.57 | 19.26 | 109.27 | 23.55 | 0.00 | 0.00 | 0.00 |
September | 63.49 | 45.21 | 18.27 | 82.53 | 25.34 | 0.00 | 0.00 | 0.00 |
October | 44.85 | 30.93 | 13.91 | 58.38 | 28.29 | 0.00 | 0.00 | 0.00 |
November | 35.77 | 22.66 | 13.11 | 44.75 | 31.20 | 0.00 | 0.00 | 0.00 |
December | 30.77 | 20.57 | 10.20 | 38.59 | 33.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.87 | 40.41 | 18.45 | 76.13 | 26.83 | 0.67 | 0.00 | 0.00 |
Minimum of Months | 30.77 | 20.57 | 10.20 | 38.59 | 21.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.55 | 67.20 | 27.33 | 117.55 | 33.24 | 0.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.36 | 21.68 | 11.67 | 42.82 | 31.01 | 0.67 | 0.00 | 0.00 |
February | 38.65 | 21.59 | 17.07 | 48.14 | 26.76 | 0.00 | 0.00 | 0.00 |
March | 50.77 | 28.84 | 21.93 | 65.43 | 26.58 | 0.00 | 0.00 | 0.00 |
April | 76.79 | 55.81 | 20.97 | 100.30 | 26.32 | 0.00 | 0.00 | 0.00 |
May | 76.73 | 49.40 | 27.33 | 98.32 | 25.25 | 0.00 | 0.00 | 0.00 |
June | 81.58 | 56.26 | 25.33 | 105.71 | 21.70 | 0.00 | 0.00 | 0.00 |
July | 89.55 | 67.20 | 22.35 | 117.55 | 22.67 | 0.00 | 0.00 | 0.00 |
August | 82.83 | 63.57 | 19.26 | 109.27 | 23.55 | 0.00 | 0.00 | 0.00 |
September | 63.49 | 45.21 | 18.27 | 82.53 | 25.34 | 0.00 | 0.00 | 0.00 |
October | 44.85 | 30.93 | 13.91 | 58.38 | 28.29 | 0.00 | 0.00 | 0.00 |
November | 35.77 | 22.66 | 13.11 | 44.75 | 31.20 | 0.00 | 0.00 | 0.00 |
December | 30.77 | 20.57 | 10.20 | 38.59 | 33.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.87 | 40.41 | 18.45 | 76.13 | 26.83 | 0.67 | 0.00 | 0.00 |
Minimum of Months | 30.77 | 20.57 | 10.20 | 38.59 | 21.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.55 | 67.20 | 27.33 | 117.55 | 33.24 | 0.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.36 | 21.68 | 11.67 | 42.82 | 31.01 | 0.67 | 0.00 | 0.00 |
February | 38.65 | 21.59 | 17.07 | 48.14 | 26.76 | 0.00 | 0.00 | 0.00 |
March | 50.77 | 28.84 | 21.93 | 65.43 | 26.58 | 0.00 | 0.00 | 0.00 |
April | 76.79 | 55.81 | 20.97 | 100.30 | 26.32 | 0.00 | 0.00 | 0.00 |
May | 76.73 | 49.40 | 27.33 | 98.32 | 25.25 | 0.00 | 0.00 | 0.00 |
June | 81.58 | 56.26 | 25.33 | 105.71 | 21.70 | 0.00 | 0.00 | 0.00 |
July | 89.55 | 67.20 | 22.35 | 117.55 | 22.67 | 0.00 | 0.00 | 0.00 |
August | 82.83 | 63.57 | 19.26 | 109.27 | 23.55 | 0.00 | 0.00 | 0.00 |
September | 63.49 | 45.21 | 18.27 | 82.53 | 25.34 | 0.00 | 0.00 | 0.00 |
October | 44.85 | 30.93 | 13.91 | 58.38 | 28.29 | 0.00 | 0.00 | 0.00 |
November | 35.77 | 22.66 | 13.11 | 44.75 | 31.20 | 0.00 | 0.00 | 0.00 |
December | 30.77 | 20.57 | 10.20 | 38.59 | 33.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.87 | 40.41 | 18.45 | 76.13 | 26.83 | 0.67 | 0.00 | 0.00 |
Minimum of Months | 30.77 | 20.57 | 10.20 | 38.59 | 21.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.55 | 67.20 | 27.33 | 117.55 | 33.24 | 0.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.36 | 21.68 | 11.67 | 42.82 | 31.01 | 0.67 | 0.00 | 0.00 |
February | 38.65 | 21.59 | 17.07 | 48.14 | 26.76 | 0.00 | 0.00 | 0.00 |
March | 50.77 | 28.84 | 21.93 | 65.43 | 26.58 | 0.00 | 0.00 | 0.00 |
April | 76.79 | 55.81 | 20.97 | 100.30 | 26.32 | 0.00 | 0.00 | 0.00 |
May | 76.73 | 49.40 | 27.33 | 98.32 | 25.25 | 0.00 | 0.00 | 0.00 |
June | 81.58 | 56.26 | 25.33 | 105.71 | 21.70 | 0.00 | 0.00 | 0.00 |
July | 89.55 | 67.20 | 22.35 | 117.55 | 22.67 | 0.00 | 0.00 | 0.00 |
August | 82.83 | 63.57 | 19.26 | 109.27 | 23.55 | 0.00 | 0.00 | 0.00 |
September | 63.49 | 45.21 | 18.27 | 82.53 | 25.34 | 0.00 | 0.00 | 0.00 |
October | 44.85 | 30.93 | 13.91 | 58.38 | 28.29 | 0.00 | 0.00 | 0.00 |
November | 35.77 | 22.66 | 13.11 | 44.75 | 31.20 | 0.00 | 0.00 | 0.00 |
December | 30.77 | 20.57 | 10.20 | 38.59 | 33.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.87 | 40.41 | 18.45 | 76.13 | 26.83 | 0.67 | 0.00 | 0.00 |
Minimum of Months | 30.77 | 20.57 | 10.20 | 38.59 | 21.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.55 | 67.20 | 27.33 | 117.55 | 33.24 | 0.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.36 | 21.68 | 11.67 | 42.82 | 31.01 | 0.67 | 0.00 | 0.00 |
February | 38.65 | 21.59 | 17.07 | 48.14 | 26.76 | 0.00 | 0.00 | 0.00 |
March | 50.77 | 28.84 | 21.93 | 65.43 | 26.58 | 0.00 | 0.00 | 0.00 |
April | 76.79 | 55.81 | 20.97 | 100.30 | 26.32 | 0.00 | 0.00 | 0.00 |
May | 76.73 | 49.40 | 27.33 | 98.32 | 25.25 | 0.00 | 0.00 | 0.00 |
June | 81.58 | 56.26 | 25.33 | 105.71 | 21.70 | 0.00 | 0.00 | 0.00 |
July | 89.55 | 67.20 | 22.35 | 117.55 | 22.67 | 0.00 | 0.00 | 0.00 |
August | 82.83 | 63.57 | 19.26 | 109.27 | 23.55 | 0.00 | 0.00 | 0.00 |
September | 63.49 | 45.21 | 18.27 | 82.53 | 25.34 | 0.00 | 0.00 | 0.00 |
October | 44.85 | 30.93 | 13.91 | 58.38 | 28.29 | 0.00 | 0.00 | 0.00 |
November | 35.77 | 22.66 | 13.11 | 44.75 | 31.20 | 0.00 | 0.00 | 0.00 |
December | 30.77 | 20.57 | 10.20 | 38.59 | 33.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.87 | 40.41 | 18.45 | 76.13 | 26.83 | 0.67 | 0.00 | 0.00 |
Minimum of Months | 30.77 | 20.57 | 10.20 | 38.59 | 21.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.55 | 67.20 | 27.33 | 117.55 | 33.24 | 0.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.36 | 21.68 | 11.67 | 42.82 | 31.01 | 0.67 | 0.00 | 0.00 |
February | 38.65 | 21.59 | 17.07 | 48.14 | 26.76 | 0.00 | 0.00 | 0.00 |
March | 50.77 | 28.84 | 21.93 | 65.43 | 26.58 | 0.00 | 0.00 | 0.00 |
April | 76.79 | 55.81 | 20.97 | 100.30 | 26.32 | 0.00 | 0.00 | 0.00 |
May | 76.73 | 49.40 | 27.33 | 98.32 | 25.25 | 0.00 | 0.00 | 0.00 |
June | 81.58 | 56.26 | 25.33 | 105.71 | 21.70 | 0.00 | 0.00 | 0.00 |
July | 89.55 | 67.20 | 22.35 | 117.55 | 22.67 | 0.00 | 0.00 | 0.00 |
August | 82.83 | 63.57 | 19.26 | 109.27 | 23.55 | 0.00 | 0.00 | 0.00 |
September | 63.49 | 45.21 | 18.27 | 82.53 | 25.34 | 0.00 | 0.00 | 0.00 |
October | 44.85 | 30.93 | 13.91 | 58.38 | 28.29 | 0.00 | 0.00 | 0.00 |
November | 35.77 | 22.66 | 13.11 | 44.75 | 31.20 | 0.00 | 0.00 | 0.00 |
December | 30.77 | 20.57 | 10.20 | 38.59 | 33.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.87 | 40.41 | 18.45 | 76.13 | 26.83 | 0.67 | 0.00 | 0.00 |
Minimum of Months | 30.77 | 20.57 | 10.20 | 38.59 | 21.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.55 | 67.20 | 27.33 | 117.55 | 33.24 | 0.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.36 | 21.68 | 11.67 | 42.82 | 31.01 | 0.67 | 0.00 | 0.00 |
February | 38.65 | 21.59 | 17.07 | 48.14 | 26.76 | 0.00 | 0.00 | 0.00 |
March | 50.77 | 28.84 | 21.93 | 65.43 | 26.58 | 0.00 | 0.00 | 0.00 |
April | 76.79 | 55.81 | 20.97 | 100.30 | 26.32 | 0.00 | 0.00 | 0.00 |
May | 76.73 | 49.40 | 27.33 | 98.32 | 25.25 | 0.00 | 0.00 | 0.00 |
June | 81.58 | 56.26 | 25.33 | 105.71 | 21.70 | 0.00 | 0.00 | 0.00 |
July | 89.55 | 67.20 | 22.35 | 117.55 | 22.67 | 0.00 | 0.00 | 0.00 |
August | 82.83 | 63.57 | 19.26 | 109.27 | 23.55 | 0.00 | 0.00 | 0.00 |
September | 63.49 | 45.21 | 18.27 | 82.53 | 25.34 | 0.00 | 0.00 | 0.00 |
October | 44.85 | 30.93 | 13.91 | 58.38 | 28.29 | 0.00 | 0.00 | 0.00 |
November | 35.77 | 22.66 | 13.11 | 44.75 | 31.20 | 0.00 | 0.00 | 0.00 |
December | 30.77 | 20.57 | 10.20 | 38.59 | 33.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.87 | 40.41 | 18.45 | 76.13 | 26.83 | 0.67 | 0.00 | 0.00 |
Minimum of Months | 30.77 | 20.57 | 10.20 | 38.59 | 21.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.55 | 67.20 | 27.33 | 117.55 | 33.24 | 0.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.36 | 21.68 | 11.67 | 42.82 | 31.01 | 0.67 | 0.00 | 0.00 |
February | 38.65 | 21.59 | 17.07 | 48.14 | 26.76 | 0.00 | 0.00 | 0.00 |
March | 50.77 | 28.84 | 21.93 | 65.43 | 26.58 | 0.00 | 0.00 | 0.00 |
April | 76.79 | 55.81 | 20.97 | 100.30 | 26.32 | 0.00 | 0.00 | 0.00 |
May | 76.73 | 49.40 | 27.33 | 98.32 | 25.25 | 0.00 | 0.00 | 0.00 |
June | 81.58 | 56.26 | 25.33 | 105.71 | 21.70 | 0.00 | 0.00 | 0.00 |
July | 89.55 | 67.20 | 22.35 | 117.55 | 22.67 | 0.00 | 0.00 | 0.00 |
August | 82.83 | 63.57 | 19.26 | 109.27 | 23.55 | 0.00 | 0.00 | 0.00 |
September | 63.49 | 45.21 | 18.27 | 82.53 | 25.34 | 0.00 | 0.00 | 0.00 |
October | 44.85 | 30.93 | 13.91 | 58.38 | 28.29 | 0.00 | 0.00 | 0.00 |
November | 35.77 | 22.66 | 13.11 | 44.75 | 31.20 | 0.00 | 0.00 | 0.00 |
December | 30.77 | 20.57 | 10.20 | 38.59 | 33.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.87 | 40.41 | 18.45 | 76.13 | 26.83 | 0.67 | 0.00 | 0.00 |
Minimum of Months | 30.77 | 20.57 | 10.20 | 38.59 | 21.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.55 | 67.20 | 27.33 | 117.55 | 33.24 | 0.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.36 | 21.68 | 11.67 | 42.82 | 31.01 | 0.67 | 0.00 | 0.00 |
February | 38.65 | 21.59 | 17.07 | 48.14 | 26.76 | 0.00 | 0.00 | 0.00 |
March | 50.77 | 28.84 | 21.93 | 65.43 | 26.58 | 0.00 | 0.00 | 0.00 |
April | 76.79 | 55.81 | 20.97 | 100.30 | 26.32 | 0.00 | 0.00 | 0.00 |
May | 76.73 | 49.40 | 27.33 | 98.32 | 25.25 | 0.00 | 0.00 | 0.00 |
June | 81.58 | 56.26 | 25.33 | 105.71 | 21.70 | 0.00 | 0.00 | 0.00 |
July | 89.55 | 67.20 | 22.35 | 117.55 | 22.67 | 0.00 | 0.00 | 0.00 |
August | 82.83 | 63.57 | 19.26 | 109.27 | 23.55 | 0.00 | 0.00 | 0.00 |
September | 63.49 | 45.21 | 18.27 | 82.53 | 25.34 | 0.00 | 0.00 | 0.00 |
October | 44.85 | 30.93 | 13.91 | 58.38 | 28.29 | 0.00 | 0.00 | 0.00 |
November | 35.77 | 22.66 | 13.11 | 44.75 | 31.20 | 0.00 | 0.00 | 0.00 |
December | 30.77 | 20.57 | 10.20 | 38.59 | 33.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.87 | 40.41 | 18.45 | 76.13 | 26.83 | 0.67 | 0.00 | 0.00 |
Minimum of Months | 30.77 | 20.57 | 10.20 | 38.59 | 21.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.55 | 67.20 | 27.33 | 117.55 | 33.24 | 0.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.36 | 21.68 | 11.67 | 42.82 | 31.01 | 0.67 | 0.00 | 0.00 |
February | 38.65 | 21.59 | 17.07 | 48.14 | 26.76 | 0.00 | 0.00 | 0.00 |
March | 50.77 | 28.84 | 21.93 | 65.43 | 26.58 | 0.00 | 0.00 | 0.00 |
April | 76.79 | 55.81 | 20.97 | 100.30 | 26.32 | 0.00 | 0.00 | 0.00 |
May | 76.73 | 49.40 | 27.33 | 98.32 | 25.25 | 0.00 | 0.00 | 0.00 |
June | 81.58 | 56.26 | 25.33 | 105.71 | 21.70 | 0.00 | 0.00 | 0.00 |
July | 89.55 | 67.20 | 22.35 | 117.55 | 22.67 | 0.00 | 0.00 | 0.00 |
August | 82.83 | 63.57 | 19.26 | 109.27 | 23.55 | 0.00 | 0.00 | 0.00 |
September | 63.49 | 45.21 | 18.27 | 82.53 | 25.34 | 0.00 | 0.00 | 0.00 |
October | 44.85 | 30.93 | 13.91 | 58.38 | 28.29 | 0.00 | 0.00 | 0.00 |
November | 35.77 | 22.66 | 13.11 | 44.75 | 31.20 | 0.00 | 0.00 | 0.00 |
December | 30.77 | 20.57 | 10.20 | 38.59 | 33.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.87 | 40.41 | 18.45 | 76.13 | 26.83 | 0.67 | 0.00 | 0.00 |
Minimum of Months | 30.77 | 20.57 | 10.20 | 38.59 | 21.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.55 | 67.20 | 27.33 | 117.55 | 33.24 | 0.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.36 | 21.68 | 11.67 | 42.82 | 31.01 | 0.67 | 0.00 | 0.00 |
February | 38.65 | 21.59 | 17.07 | 48.14 | 26.76 | 0.00 | 0.00 | 0.00 |
March | 50.77 | 28.84 | 21.93 | 65.43 | 26.58 | 0.00 | 0.00 | 0.00 |
April | 76.79 | 55.81 | 20.97 | 100.30 | 26.32 | 0.00 | 0.00 | 0.00 |
May | 76.73 | 49.40 | 27.33 | 98.32 | 25.25 | 0.00 | 0.00 | 0.00 |
June | 81.58 | 56.26 | 25.33 | 105.71 | 21.70 | 0.00 | 0.00 | 0.00 |
July | 89.55 | 67.20 | 22.35 | 117.55 | 22.67 | 0.00 | 0.00 | 0.00 |
August | 82.83 | 63.57 | 19.26 | 109.27 | 23.55 | 0.00 | 0.00 | 0.00 |
September | 63.49 | 45.21 | 18.27 | 82.53 | 25.34 | 0.00 | 0.00 | 0.00 |
October | 44.85 | 30.93 | 13.91 | 58.38 | 28.29 | 0.00 | 0.00 | 0.00 |
November | 35.77 | 22.66 | 13.11 | 44.75 | 31.20 | 0.00 | 0.00 | 0.00 |
December | 30.77 | 20.57 | 10.20 | 38.59 | 33.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.87 | 40.41 | 18.45 | 76.13 | 26.83 | 0.67 | 0.00 | 0.00 |
Minimum of Months | 30.77 | 20.57 | 10.20 | 38.59 | 21.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.55 | 67.20 | 27.33 | 117.55 | 33.24 | 0.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.36 | 21.68 | 11.67 | 42.82 | 31.01 | 0.67 | 0.00 | 0.00 |
February | 38.65 | 21.59 | 17.07 | 48.14 | 26.76 | 0.00 | 0.00 | 0.00 |
March | 50.77 | 28.84 | 21.93 | 65.43 | 26.58 | 0.00 | 0.00 | 0.00 |
April | 76.79 | 55.81 | 20.97 | 100.30 | 26.32 | 0.00 | 0.00 | 0.00 |
May | 76.73 | 49.40 | 27.33 | 98.32 | 25.25 | 0.00 | 0.00 | 0.00 |
June | 81.58 | 56.26 | 25.33 | 105.71 | 21.70 | 0.00 | 0.00 | 0.00 |
July | 89.55 | 67.20 | 22.35 | 117.55 | 22.67 | 0.00 | 0.00 | 0.00 |
August | 82.83 | 63.57 | 19.26 | 109.27 | 23.55 | 0.00 | 0.00 | 0.00 |
September | 63.49 | 45.21 | 18.27 | 82.53 | 25.34 | 0.00 | 0.00 | 0.00 |
October | 44.85 | 30.93 | 13.91 | 58.38 | 28.29 | 0.00 | 0.00 | 0.00 |
November | 35.77 | 22.66 | 13.11 | 44.75 | 31.20 | 0.00 | 0.00 | 0.00 |
December | 30.77 | 20.57 | 10.20 | 38.59 | 33.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.87 | 40.41 | 18.45 | 76.13 | 26.83 | 0.67 | 0.00 | 0.00 |
Minimum of Months | 30.77 | 20.57 | 10.20 | 38.59 | 21.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.55 | 67.20 | 27.33 | 117.55 | 33.24 | 0.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.36 | 21.68 | 11.67 | 42.82 | 31.01 | 0.67 | 0.00 | 0.00 |
February | 38.65 | 21.59 | 17.07 | 48.14 | 26.76 | 0.00 | 0.00 | 0.00 |
March | 50.77 | 28.84 | 21.93 | 65.43 | 26.58 | 0.00 | 0.00 | 0.00 |
April | 76.79 | 55.81 | 20.97 | 100.30 | 26.32 | 0.00 | 0.00 | 0.00 |
May | 76.73 | 49.40 | 27.33 | 98.32 | 25.25 | 0.00 | 0.00 | 0.00 |
June | 81.58 | 56.26 | 25.33 | 105.71 | 21.70 | 0.00 | 0.00 | 0.00 |
July | 89.55 | 67.20 | 22.35 | 117.55 | 22.67 | 0.00 | 0.00 | 0.00 |
August | 82.83 | 63.57 | 19.26 | 109.27 | 23.55 | 0.00 | 0.00 | 0.00 |
September | 63.49 | 45.21 | 18.27 | 82.53 | 25.34 | 0.00 | 0.00 | 0.00 |
October | 44.85 | 30.93 | 13.91 | 58.38 | 28.29 | 0.00 | 0.00 | 0.00 |
November | 35.77 | 22.66 | 13.11 | 44.75 | 31.20 | 0.00 | 0.00 | 0.00 |
December | 30.77 | 20.57 | 10.20 | 38.59 | 33.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.87 | 40.41 | 18.45 | 76.13 | 26.83 | 0.67 | 0.00 | 0.00 |
Minimum of Months | 30.77 | 20.57 | 10.20 | 38.59 | 21.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.55 | 67.20 | 27.33 | 117.55 | 33.24 | 0.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.36 | 21.68 | 11.67 | 42.82 | 31.01 | 0.67 | 0.00 | 0.00 |
February | 38.65 | 21.59 | 17.07 | 48.14 | 26.76 | 0.00 | 0.00 | 0.00 |
March | 50.77 | 28.84 | 21.93 | 65.43 | 26.58 | 0.00 | 0.00 | 0.00 |
April | 76.79 | 55.81 | 20.97 | 100.30 | 26.32 | 0.00 | 0.00 | 0.00 |
May | 76.73 | 49.40 | 27.33 | 98.32 | 25.25 | 0.00 | 0.00 | 0.00 |
June | 81.58 | 56.26 | 25.33 | 105.71 | 21.70 | 0.00 | 0.00 | 0.00 |
July | 89.55 | 67.20 | 22.35 | 117.55 | 22.67 | 0.00 | 0.00 | 0.00 |
August | 82.83 | 63.57 | 19.26 | 109.27 | 23.55 | 0.00 | 0.00 | 0.00 |
September | 63.49 | 45.21 | 18.27 | 82.53 | 25.34 | 0.00 | 0.00 | 0.00 |
October | 44.85 | 30.93 | 13.91 | 58.38 | 28.29 | 0.00 | 0.00 | 0.00 |
November | 35.77 | 22.66 | 13.11 | 44.75 | 31.20 | 0.00 | 0.00 | 0.00 |
December | 30.77 | 20.57 | 10.20 | 38.59 | 33.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.87 | 40.41 | 18.45 | 76.13 | 26.83 | 0.67 | 0.00 | 0.00 |
Minimum of Months | 30.77 | 20.57 | 10.20 | 38.59 | 21.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.55 | 67.20 | 27.33 | 117.55 | 33.24 | 0.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.96 | 44.85 | 23.11 | 91.89 | 38.82 | 26.17 | 0.00 | 0.00 |
February | 77.26 | 43.49 | 33.78 | 100.37 | 35.17 | 9.00 | 0.00 | 0.00 |
March | 99.87 | 56.47 | 43.40 | 132.88 | 35.63 | 37.33 | 0.00 | 0.00 |
April | 149.21 | 107.69 | 41.51 | 199.24 | 36.41 | 4.00 | 0.00 | 0.00 |
May | 148.87 | 94.78 | 54.09 | 194.09 | 35.95 | 0.00 | 0.00 | 0.00 |
June | 157.86 | 107.74 | 50.13 | 207.25 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 173.00 | 128.76 | 44.24 | 227.38 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 160.37 | 122.24 | 38.13 | 211.64 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 123.66 | 87.49 | 36.17 | 162.43 | 37.51 | 1.33 | 0.00 | 0.00 |
October | 88.79 | 61.25 | 27.54 | 117.04 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 72.40 | 46.45 | 25.94 | 94.60 | 41.59 | 13.83 | 0.00 | 0.00 |
December | 63.41 | 43.22 | 20.19 | 83.85 | 43.16 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.42 | 78.90 | 36.52 | 152.16 | 37.50 | 105.67 | 0.00 | 0.00 |
Minimum of Months | 63.41 | 43.22 | 20.19 | 83.85 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 128.76 | 54.09 | 227.38 | 43.16 | 37.33 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171444E+09 | 86465726.28 | 84978472.32 | 0.238504E+09 | 0.192147E+09 |
February | 0.184557E+09 | 85154354.87 | 99403141.61 | 0.243671E+09 | 0.156275E+09 |
March | 0.234161E+09 | 0.103554E+09 | 0.130607E+09 | 0.312411E+09 | 0.181021E+09 |
April | 0.311953E+09 | 0.162104E+09 | 0.149849E+09 | 0.444874E+09 | 0.162456E+09 |
May | 0.316746E+09 | 0.145935E+09 | 0.170812E+09 | 0.433793E+09 | 0.161475E+09 |
June | 0.325452E+09 | 0.162770E+09 | 0.162682E+09 | 0.463075E+09 | 0.131431E+09 |
July | 0.356032E+09 | 0.190556E+09 | 0.165477E+09 | 0.525559E+09 | 0.133135E+09 |
August | 0.333509E+09 | 0.180553E+09 | 0.152956E+09 | 0.500477E+09 | 0.137868E+09 |
September | 0.276348E+09 | 0.147712E+09 | 0.128635E+09 | 0.405045E+09 | 0.145551E+09 |
October | 0.218559E+09 | 0.119389E+09 | 99169353.00 | 0.329675E+09 | 0.162222E+09 |
November | 0.190714E+09 | 99595004.08 | 91118821.29 | 0.262209E+09 | 0.184137E+09 |
December | 0.173757E+09 | 92920345.46 | 80836858.27 | 0.242031E+09 | 0.201374E+09 |
Annual Sum or Average | 0.309323E+10 | 0.157671E+10 | 0.151652E+10 | 0.440132E+10 | 0.194909E+10 |
Minimum of Months | 0.171444E+09 | 85154354.87 | 80836858.27 | 0.238504E+09 | 0.131431E+09 |
Maximum of Months | 0.356032E+09 | 0.190556E+09 | 0.170812E+09 | 0.525559E+09 | 0.201374E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171444E+09 | 86465726.28 | 84978472.32 | 0.238504E+09 | 0.192147E+09 |
February | 0.184557E+09 | 85154354.87 | 99403141.61 | 0.243671E+09 | 0.156275E+09 |
March | 0.234161E+09 | 0.103554E+09 | 0.130607E+09 | 0.312411E+09 | 0.181021E+09 |
April | 0.311953E+09 | 0.162104E+09 | 0.149849E+09 | 0.444874E+09 | 0.162456E+09 |
May | 0.316746E+09 | 0.145935E+09 | 0.170812E+09 | 0.433793E+09 | 0.161475E+09 |
June | 0.325452E+09 | 0.162770E+09 | 0.162682E+09 | 0.463075E+09 | 0.131431E+09 |
July | 0.356032E+09 | 0.190556E+09 | 0.165477E+09 | 0.525559E+09 | 0.133135E+09 |
August | 0.333509E+09 | 0.180553E+09 | 0.152956E+09 | 0.500477E+09 | 0.137868E+09 |
September | 0.276348E+09 | 0.147712E+09 | 0.128635E+09 | 0.405045E+09 | 0.145551E+09 |
October | 0.218559E+09 | 0.119389E+09 | 99169353.00 | 0.329675E+09 | 0.162222E+09 |
November | 0.190714E+09 | 99595004.08 | 91118821.29 | 0.262209E+09 | 0.184137E+09 |
December | 0.173757E+09 | 92920345.46 | 80836858.27 | 0.242031E+09 | 0.201374E+09 |
Annual Sum or Average | 0.309323E+10 | 0.157671E+10 | 0.151652E+10 | 0.440132E+10 | 0.194909E+10 |
Minimum of Months | 0.171444E+09 | 85154354.87 | 80836858.27 | 0.238504E+09 | 0.131431E+09 |
Maximum of Months | 0.356032E+09 | 0.190556E+09 | 0.170812E+09 | 0.525559E+09 | 0.201374E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38936033.76 | 0.00 | 38936033.76 | 32991232.00 | 0.114872E+09 |
February | 44145242.95 | 0.00 | 44145242.95 | 34886425.45 | 93859372.70 |
March | 59899498.99 | 1880.12 | 59897618.87 | 53064116.35 | 0.108570E+09 |
April | 66956762.05 | 398903.32 | 66557858.73 | 60983802.61 | 95280375.13 |
May | 83435167.46 | 4336841.73 | 79098325.73 | 78678642.40 | 90905014.47 |
June | 85379322.61 | 8235742.78 | 77143579.84 | 91015244.41 | 73990383.09 |
July | 83554563.45 | 6888467.79 | 76666095.66 | 92655936.72 | 75928698.93 |
August | 69738145.90 | 1627149.27 | 68110996.63 | 74830497.09 | 79575813.05 |
September | 56921562.79 | 20070.67 | 56901492.12 | 57573393.48 | 87799193.00 |
October | 46645382.02 | 0.00 | 46645382.02 | 52737823.51 | 96850763.36 |
November | 40871639.54 | 0.00 | 40871639.54 | 32326082.73 | 0.110947E+09 |
December | 36246135.37 | 0.00 | 36246135.37 | 28354537.07 | 0.120873E+09 |
Annual Sum or Average | 0.712729E+09 | 21509055.66 | 0.691220E+09 | 0.690098E+09 | 0.114945E+10 |
Minimum of Months | 36246135.37 | 0.00 | 36246135.37 | 28354537.07 | 73990383.09 |
Maximum of Months | 85379322.61 | 8235742.78 | 79098325.73 | 92655936.72 | 0.120873E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38934953.00 | 0.00 | 38934953.00 | 32990160.02 | 0.114870E+09 |
February | 44143929.50 | 0.00 | 44143929.50 | 34884888.89 | 93858758.86 |
March | 59897723.64 | 1880.03 | 59895843.61 | 53061829.44 | 0.108569E+09 |
April | 66955085.76 | 398884.62 | 66556201.14 | 60981943.73 | 95279972.17 |
May | 83432750.79 | 4336638.45 | 79096112.34 | 78675266.29 | 90904640.62 |
June | 85376847.33 | 8235356.76 | 77141490.58 | 91011641.50 | 73990109.04 |
July | 83552367.86 | 6888144.92 | 76664222.94 | 92652927.38 | 75928281.56 |
August | 69736476.68 | 1627073.00 | 68109403.68 | 74828584.04 | 79575363.90 |
September | 56920108.05 | 20069.73 | 56900038.32 | 57571692.97 | 87798622.40 |
October | 46644134.41 | 0.00 | 46644134.41 | 52736482.13 | 96849914.12 |
November | 40870491.07 | 0.00 | 40870491.07 | 32324899.02 | 0.110946E+09 |
December | 36245148.47 | 0.00 | 36245148.47 | 28353702.84 | 0.120872E+09 |
Annual Sum or Average | 0.712710E+09 | 21508047.51 | 0.691202E+09 | 0.690074E+09 | 0.114944E+10 |
Minimum of Months | 36245148.47 | 0.00 | 36245148.47 | 28353702.84 | 73990109.04 |
Maximum of Months | 85376847.33 | 8235356.76 | 79096112.34 | 92652927.38 | 0.120872E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 89343578.36 | 58075949.06 | 31267629.30 | 0.114688E+09 | 83056646.52 |
February | 93512011.46 | 52228248.31 | 41283763.16 | 0.116454E+09 | 64729824.99 |
March | 0.135991E+09 | 77257017.02 | 58734429.67 | 0.175237E+09 | 71200246.54 |
April | 0.199032E+09 | 0.144668E+09 | 54364280.59 | 0.259969E+09 | 68208603.85 |
May | 0.205525E+09 | 0.132325E+09 | 73199587.90 | 0.263346E+09 | 67626204.97 |
June | 0.211464E+09 | 0.145818E+09 | 65645767.76 | 0.273999E+09 | 56252549.48 |
July | 0.239853E+09 | 0.179984E+09 | 59869317.62 | 0.314852E+09 | 60726573.13 |
August | 0.221854E+09 | 0.170255E+09 | 51598633.65 | 0.292679E+09 | 63086802.01 |
September | 0.164561E+09 | 0.117192E+09 | 47368590.56 | 0.213912E+09 | 65689146.68 |
October | 0.120124E+09 | 82855881.69 | 37268259.81 | 0.156356E+09 | 75759175.89 |
November | 92714939.67 | 58738049.16 | 33976890.51 | 0.115997E+09 | 80874198.25 |
December | 82424543.67 | 55107302.81 | 27317240.86 | 0.103355E+09 | 89025518.31 |
Annual Sum or Average | 0.185640E+10 | 0.127451E+10 | 0.581894E+09 | 0.240084E+10 | 0.846235E+09 |
Minimum of Months | 82424543.67 | 52228248.31 | 27317240.86 | 0.103355E+09 | 56252549.48 |
Maximum of Months | 0.239853E+09 | 0.179984E+09 | 73199587.90 | 0.314852E+09 | 89025518.31 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 89343578.36 | 58075949.06 | 31267629.30 | 0.114688E+09 | 83056646.52 |
February | 93512011.46 | 52228248.31 | 41283763.16 | 0.116454E+09 | 64729824.99 |
March | 0.135991E+09 | 77257017.02 | 58734429.67 | 0.175237E+09 | 71200246.54 |
April | 0.199032E+09 | 0.144668E+09 | 54364280.59 | 0.259969E+09 | 68208603.85 |
May | 0.205525E+09 | 0.132325E+09 | 73199587.90 | 0.263346E+09 | 67626204.97 |
June | 0.211464E+09 | 0.145818E+09 | 65645767.76 | 0.273999E+09 | 56252549.48 |
July | 0.239853E+09 | 0.179984E+09 | 59869317.62 | 0.314852E+09 | 60726573.13 |
August | 0.221854E+09 | 0.170255E+09 | 51598633.65 | 0.292679E+09 | 63086802.01 |
September | 0.164561E+09 | 0.117192E+09 | 47368590.56 | 0.213912E+09 | 65689146.68 |
October | 0.120124E+09 | 82855881.69 | 37268259.81 | 0.156356E+09 | 75759175.89 |
November | 92714939.67 | 58738049.16 | 33976890.51 | 0.115997E+09 | 80874198.25 |
December | 82424543.67 | 55107302.81 | 27317240.86 | 0.103355E+09 | 89025518.31 |
Annual Sum or Average | 0.185640E+10 | 0.127451E+10 | 0.581894E+09 | 0.240084E+10 | 0.846235E+09 |
Minimum of Months | 82424543.67 | 52228248.31 | 27317240.86 | 0.103355E+09 | 56252549.48 |
Maximum of Months | 0.239853E+09 | 0.179984E+09 | 73199587.90 | 0.314852E+09 | 89025518.31 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 89343578.36 | 58075949.06 | 31267629.30 | 0.114688E+09 | 83056646.52 |
February | 93512011.46 | 52228248.31 | 41283763.16 | 0.116454E+09 | 64729824.99 |
March | 0.135991E+09 | 77257017.02 | 58734429.67 | 0.175237E+09 | 71200246.54 |
April | 0.199032E+09 | 0.144668E+09 | 54364280.59 | 0.259969E+09 | 68208603.85 |
May | 0.205525E+09 | 0.132325E+09 | 73199587.90 | 0.263346E+09 | 67626204.97 |
June | 0.211464E+09 | 0.145818E+09 | 65645767.76 | 0.273999E+09 | 56252549.48 |
July | 0.239853E+09 | 0.179984E+09 | 59869317.62 | 0.314852E+09 | 60726573.13 |
August | 0.221854E+09 | 0.170255E+09 | 51598633.65 | 0.292679E+09 | 63086802.01 |
September | 0.164561E+09 | 0.117192E+09 | 47368590.56 | 0.213912E+09 | 65689146.68 |
October | 0.120124E+09 | 82855881.69 | 37268259.81 | 0.156356E+09 | 75759175.89 |
November | 92714939.67 | 58738049.16 | 33976890.51 | 0.115997E+09 | 80874198.25 |
December | 82424543.67 | 55107302.81 | 27317240.86 | 0.103355E+09 | 89025518.31 |
Annual Sum or Average | 0.185640E+10 | 0.127451E+10 | 0.581894E+09 | 0.240084E+10 | 0.846235E+09 |
Minimum of Months | 82424543.67 | 52228248.31 | 27317240.86 | 0.103355E+09 | 56252549.48 |
Maximum of Months | 0.239853E+09 | 0.179984E+09 | 73199587.90 | 0.314852E+09 | 89025518.31 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 89343578.36 | 58075949.06 | 31267629.30 | 0.114688E+09 | 83056646.52 |
February | 93512011.46 | 52228248.31 | 41283763.16 | 0.116454E+09 | 64729824.99 |
March | 0.135991E+09 | 77257017.02 | 58734429.67 | 0.175237E+09 | 71200246.54 |
April | 0.199032E+09 | 0.144668E+09 | 54364280.59 | 0.259969E+09 | 68208603.85 |
May | 0.205525E+09 | 0.132325E+09 | 73199587.90 | 0.263346E+09 | 67626204.97 |
June | 0.211464E+09 | 0.145818E+09 | 65645767.76 | 0.273999E+09 | 56252549.48 |
July | 0.239853E+09 | 0.179984E+09 | 59869317.62 | 0.314852E+09 | 60726573.13 |
August | 0.221854E+09 | 0.170255E+09 | 51598633.65 | 0.292679E+09 | 63086802.01 |
September | 0.164561E+09 | 0.117192E+09 | 47368590.56 | 0.213912E+09 | 65689146.68 |
October | 0.120124E+09 | 82855881.69 | 37268259.81 | 0.156356E+09 | 75759175.89 |
November | 92714939.67 | 58738049.16 | 33976890.51 | 0.115997E+09 | 80874198.25 |
December | 82424543.67 | 55107302.81 | 27317240.86 | 0.103355E+09 | 89025518.31 |
Annual Sum or Average | 0.185640E+10 | 0.127451E+10 | 0.581894E+09 | 0.240084E+10 | 0.846235E+09 |
Minimum of Months | 82424543.67 | 52228248.31 | 27317240.86 | 0.103355E+09 | 56252549.48 |
Maximum of Months | 0.239853E+09 | 0.179984E+09 | 73199587.90 | 0.314852E+09 | 89025518.31 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 89343578.36 | 58075949.06 | 31267629.30 | 0.114688E+09 | 83056646.52 |
February | 93512011.46 | 52228248.31 | 41283763.16 | 0.116454E+09 | 64729824.99 |
March | 0.135991E+09 | 77257017.02 | 58734429.67 | 0.175237E+09 | 71200246.54 |
April | 0.199032E+09 | 0.144668E+09 | 54364280.59 | 0.259969E+09 | 68208603.85 |
May | 0.205525E+09 | 0.132325E+09 | 73199587.90 | 0.263346E+09 | 67626204.97 |
June | 0.211464E+09 | 0.145818E+09 | 65645767.76 | 0.273999E+09 | 56252549.48 |
July | 0.239853E+09 | 0.179984E+09 | 59869317.62 | 0.314852E+09 | 60726573.13 |
August | 0.221854E+09 | 0.170255E+09 | 51598633.65 | 0.292679E+09 | 63086802.01 |
September | 0.164561E+09 | 0.117192E+09 | 47368590.56 | 0.213912E+09 | 65689146.68 |
October | 0.120124E+09 | 82855881.69 | 37268259.81 | 0.156356E+09 | 75759175.89 |
November | 92714939.67 | 58738049.16 | 33976890.51 | 0.115997E+09 | 80874198.25 |
December | 82424543.67 | 55107302.81 | 27317240.86 | 0.103355E+09 | 89025518.31 |
Annual Sum or Average | 0.185640E+10 | 0.127451E+10 | 0.581894E+09 | 0.240084E+10 | 0.846235E+09 |
Minimum of Months | 82424543.67 | 52228248.31 | 27317240.86 | 0.103355E+09 | 56252549.48 |
Maximum of Months | 0.239853E+09 | 0.179984E+09 | 73199587.90 | 0.314852E+09 | 89025518.31 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 89343578.36 | 58075949.06 | 31267629.30 | 0.114688E+09 | 83056646.52 |
February | 93512011.46 | 52228248.31 | 41283763.16 | 0.116454E+09 | 64729824.99 |
March | 0.135991E+09 | 77257017.02 | 58734429.67 | 0.175237E+09 | 71200246.54 |
April | 0.199032E+09 | 0.144668E+09 | 54364280.59 | 0.259969E+09 | 68208603.85 |
May | 0.205525E+09 | 0.132325E+09 | 73199587.90 | 0.263346E+09 | 67626204.97 |
June | 0.211464E+09 | 0.145818E+09 | 65645767.76 | 0.273999E+09 | 56252549.48 |
July | 0.239853E+09 | 0.179984E+09 | 59869317.62 | 0.314852E+09 | 60726573.13 |
August | 0.221854E+09 | 0.170255E+09 | 51598633.65 | 0.292679E+09 | 63086802.01 |
September | 0.164561E+09 | 0.117192E+09 | 47368590.56 | 0.213912E+09 | 65689146.68 |
October | 0.120124E+09 | 82855881.69 | 37268259.81 | 0.156356E+09 | 75759175.89 |
November | 92714939.67 | 58738049.16 | 33976890.51 | 0.115997E+09 | 80874198.25 |
December | 82424543.67 | 55107302.81 | 27317240.86 | 0.103355E+09 | 89025518.31 |
Annual Sum or Average | 0.185640E+10 | 0.127451E+10 | 0.581894E+09 | 0.240084E+10 | 0.846235E+09 |
Minimum of Months | 82424543.67 | 52228248.31 | 27317240.86 | 0.103355E+09 | 56252549.48 |
Maximum of Months | 0.239853E+09 | 0.179984E+09 | 73199587.90 | 0.314852E+09 | 89025518.31 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 89343578.36 | 58075949.06 | 31267629.30 | 0.114688E+09 | 83056646.52 |
February | 93512011.46 | 52228248.31 | 41283763.16 | 0.116454E+09 | 64729824.99 |
March | 0.135991E+09 | 77257017.02 | 58734429.67 | 0.175237E+09 | 71200246.54 |
April | 0.199032E+09 | 0.144668E+09 | 54364280.59 | 0.259969E+09 | 68208603.85 |
May | 0.205525E+09 | 0.132325E+09 | 73199587.90 | 0.263346E+09 | 67626204.97 |
June | 0.211464E+09 | 0.145818E+09 | 65645767.76 | 0.273999E+09 | 56252549.48 |
July | 0.239853E+09 | 0.179984E+09 | 59869317.62 | 0.314852E+09 | 60726573.13 |
August | 0.221854E+09 | 0.170255E+09 | 51598633.65 | 0.292679E+09 | 63086802.01 |
September | 0.164561E+09 | 0.117192E+09 | 47368590.56 | 0.213912E+09 | 65689146.68 |
October | 0.120124E+09 | 82855881.69 | 37268259.81 | 0.156356E+09 | 75759175.89 |
November | 92714939.67 | 58738049.16 | 33976890.51 | 0.115997E+09 | 80874198.25 |
December | 82424543.67 | 55107302.81 | 27317240.86 | 0.103355E+09 | 89025518.31 |
Annual Sum or Average | 0.185640E+10 | 0.127451E+10 | 0.581894E+09 | 0.240084E+10 | 0.846235E+09 |
Minimum of Months | 82424543.67 | 52228248.31 | 27317240.86 | 0.103355E+09 | 56252549.48 |
Maximum of Months | 0.239853E+09 | 0.179984E+09 | 73199587.90 | 0.314852E+09 | 89025518.31 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 89343578.36 | 58075949.06 | 31267629.30 | 0.114688E+09 | 83056646.52 |
February | 93512011.46 | 52228248.31 | 41283763.16 | 0.116454E+09 | 64729824.99 |
March | 0.135991E+09 | 77257017.02 | 58734429.67 | 0.175237E+09 | 71200246.54 |
April | 0.199032E+09 | 0.144668E+09 | 54364280.59 | 0.259969E+09 | 68208603.85 |
May | 0.205525E+09 | 0.132325E+09 | 73199587.90 | 0.263346E+09 | 67626204.97 |
June | 0.211464E+09 | 0.145818E+09 | 65645767.76 | 0.273999E+09 | 56252549.48 |
July | 0.239853E+09 | 0.179984E+09 | 59869317.62 | 0.314852E+09 | 60726573.13 |
August | 0.221854E+09 | 0.170255E+09 | 51598633.65 | 0.292679E+09 | 63086802.01 |
September | 0.164561E+09 | 0.117192E+09 | 47368590.56 | 0.213912E+09 | 65689146.68 |
October | 0.120124E+09 | 82855881.69 | 37268259.81 | 0.156356E+09 | 75759175.89 |
November | 92714939.67 | 58738049.16 | 33976890.51 | 0.115997E+09 | 80874198.25 |
December | 82424543.67 | 55107302.81 | 27317240.86 | 0.103355E+09 | 89025518.31 |
Annual Sum or Average | 0.185640E+10 | 0.127451E+10 | 0.581894E+09 | 0.240084E+10 | 0.846235E+09 |
Minimum of Months | 82424543.67 | 52228248.31 | 27317240.86 | 0.103355E+09 | 56252549.48 |
Maximum of Months | 0.239853E+09 | 0.179984E+09 | 73199587.90 | 0.314852E+09 | 89025518.31 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 89343578.36 | 58075949.06 | 31267629.30 | 0.114688E+09 | 83056646.52 |
February | 93512011.46 | 52228248.31 | 41283763.16 | 0.116454E+09 | 64729824.99 |
March | 0.135991E+09 | 77257017.02 | 58734429.67 | 0.175237E+09 | 71200246.54 |
April | 0.199032E+09 | 0.144668E+09 | 54364280.59 | 0.259969E+09 | 68208603.85 |
May | 0.205525E+09 | 0.132325E+09 | 73199587.90 | 0.263346E+09 | 67626204.97 |
June | 0.211464E+09 | 0.145818E+09 | 65645767.76 | 0.273999E+09 | 56252549.48 |
July | 0.239853E+09 | 0.179984E+09 | 59869317.62 | 0.314852E+09 | 60726573.13 |
August | 0.221854E+09 | 0.170255E+09 | 51598633.65 | 0.292679E+09 | 63086802.01 |
September | 0.164561E+09 | 0.117192E+09 | 47368590.56 | 0.213912E+09 | 65689146.68 |
October | 0.120124E+09 | 82855881.69 | 37268259.81 | 0.156356E+09 | 75759175.89 |
November | 92714939.67 | 58738049.16 | 33976890.51 | 0.115997E+09 | 80874198.25 |
December | 82424543.67 | 55107302.81 | 27317240.86 | 0.103355E+09 | 89025518.31 |
Annual Sum or Average | 0.185640E+10 | 0.127451E+10 | 0.581894E+09 | 0.240084E+10 | 0.846235E+09 |
Minimum of Months | 82424543.67 | 52228248.31 | 27317240.86 | 0.103355E+09 | 56252549.48 |
Maximum of Months | 0.239853E+09 | 0.179984E+09 | 73199587.90 | 0.314852E+09 | 89025518.31 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 89343578.36 | 58075949.06 | 31267629.30 | 0.114688E+09 | 83056646.52 |
February | 93512011.46 | 52228248.31 | 41283763.16 | 0.116454E+09 | 64729824.99 |
March | 0.135991E+09 | 77257017.02 | 58734429.67 | 0.175237E+09 | 71200246.54 |
April | 0.199032E+09 | 0.144668E+09 | 54364280.59 | 0.259969E+09 | 68208603.85 |
May | 0.205525E+09 | 0.132325E+09 | 73199587.90 | 0.263346E+09 | 67626204.97 |
June | 0.211464E+09 | 0.145818E+09 | 65645767.76 | 0.273999E+09 | 56252549.48 |
July | 0.239853E+09 | 0.179984E+09 | 59869317.62 | 0.314852E+09 | 60726573.13 |
August | 0.221854E+09 | 0.170255E+09 | 51598633.65 | 0.292679E+09 | 63086802.01 |
September | 0.164561E+09 | 0.117192E+09 | 47368590.56 | 0.213912E+09 | 65689146.68 |
October | 0.120124E+09 | 82855881.69 | 37268259.81 | 0.156356E+09 | 75759175.89 |
November | 92714939.67 | 58738049.16 | 33976890.51 | 0.115997E+09 | 80874198.25 |
December | 82424543.67 | 55107302.81 | 27317240.86 | 0.103355E+09 | 89025518.31 |
Annual Sum or Average | 0.185640E+10 | 0.127451E+10 | 0.581894E+09 | 0.240084E+10 | 0.846235E+09 |
Minimum of Months | 82424543.67 | 52228248.31 | 27317240.86 | 0.103355E+09 | 56252549.48 |
Maximum of Months | 0.239853E+09 | 0.179984E+09 | 73199587.90 | 0.314852E+09 | 89025518.31 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 89343578.36 | 58075949.06 | 31267629.30 | 0.114688E+09 | 83056646.52 |
February | 93512011.46 | 52228248.31 | 41283763.16 | 0.116454E+09 | 64729824.99 |
March | 0.135991E+09 | 77257017.02 | 58734429.67 | 0.175237E+09 | 71200246.54 |
April | 0.199032E+09 | 0.144668E+09 | 54364280.59 | 0.259969E+09 | 68208603.85 |
May | 0.205525E+09 | 0.132325E+09 | 73199587.90 | 0.263346E+09 | 67626204.97 |
June | 0.211464E+09 | 0.145818E+09 | 65645767.76 | 0.273999E+09 | 56252549.48 |
July | 0.239853E+09 | 0.179984E+09 | 59869317.62 | 0.314852E+09 | 60726573.13 |
August | 0.221854E+09 | 0.170255E+09 | 51598633.65 | 0.292679E+09 | 63086802.01 |
September | 0.164561E+09 | 0.117192E+09 | 47368590.56 | 0.213912E+09 | 65689146.68 |
October | 0.120124E+09 | 82855881.69 | 37268259.81 | 0.156356E+09 | 75759175.89 |
November | 92714939.67 | 58738049.16 | 33976890.51 | 0.115997E+09 | 80874198.25 |
December | 82424543.67 | 55107302.81 | 27317240.86 | 0.103355E+09 | 89025518.31 |
Annual Sum or Average | 0.185640E+10 | 0.127451E+10 | 0.581894E+09 | 0.240084E+10 | 0.846235E+09 |
Minimum of Months | 82424543.67 | 52228248.31 | 27317240.86 | 0.103355E+09 | 56252549.48 |
Maximum of Months | 0.239853E+09 | 0.179984E+09 | 73199587.90 | 0.314852E+09 | 89025518.31 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 89343578.36 | 58075949.06 | 31267629.30 | 0.114688E+09 | 83056646.52 |
February | 93512011.46 | 52228248.31 | 41283763.16 | 0.116454E+09 | 64729824.99 |
March | 0.135991E+09 | 77257017.02 | 58734429.67 | 0.175237E+09 | 71200246.54 |
April | 0.199032E+09 | 0.144668E+09 | 54364280.59 | 0.259969E+09 | 68208603.85 |
May | 0.205525E+09 | 0.132325E+09 | 73199587.90 | 0.263346E+09 | 67626204.97 |
June | 0.211464E+09 | 0.145818E+09 | 65645767.76 | 0.273999E+09 | 56252549.48 |
July | 0.239853E+09 | 0.179984E+09 | 59869317.62 | 0.314852E+09 | 60726573.13 |
August | 0.221854E+09 | 0.170255E+09 | 51598633.65 | 0.292679E+09 | 63086802.01 |
September | 0.164561E+09 | 0.117192E+09 | 47368590.56 | 0.213912E+09 | 65689146.68 |
October | 0.120124E+09 | 82855881.69 | 37268259.81 | 0.156356E+09 | 75759175.89 |
November | 92714939.67 | 58738049.16 | 33976890.51 | 0.115997E+09 | 80874198.25 |
December | 82424543.67 | 55107302.81 | 27317240.86 | 0.103355E+09 | 89025518.31 |
Annual Sum or Average | 0.185640E+10 | 0.127451E+10 | 0.581894E+09 | 0.240084E+10 | 0.846235E+09 |
Minimum of Months | 82424543.67 | 52228248.31 | 27317240.86 | 0.103355E+09 | 56252549.48 |
Maximum of Months | 0.239853E+09 | 0.179984E+09 | 73199587.90 | 0.314852E+09 | 89025518.31 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 89343578.36 | 58075949.06 | 31267629.30 | 0.114688E+09 | 83056646.52 |
February | 93512011.46 | 52228248.31 | 41283763.16 | 0.116454E+09 | 64729824.99 |
March | 0.135991E+09 | 77257017.02 | 58734429.67 | 0.175237E+09 | 71200246.54 |
April | 0.199032E+09 | 0.144668E+09 | 54364280.59 | 0.259969E+09 | 68208603.85 |
May | 0.205525E+09 | 0.132325E+09 | 73199587.90 | 0.263346E+09 | 67626204.97 |
June | 0.211464E+09 | 0.145818E+09 | 65645767.76 | 0.273999E+09 | 56252549.48 |
July | 0.239853E+09 | 0.179984E+09 | 59869317.62 | 0.314852E+09 | 60726573.13 |
August | 0.221854E+09 | 0.170255E+09 | 51598633.65 | 0.292679E+09 | 63086802.01 |
September | 0.164561E+09 | 0.117192E+09 | 47368590.56 | 0.213912E+09 | 65689146.68 |
October | 0.120124E+09 | 82855881.69 | 37268259.81 | 0.156356E+09 | 75759175.89 |
November | 92714939.67 | 58738049.16 | 33976890.51 | 0.115997E+09 | 80874198.25 |
December | 82424543.67 | 55107302.81 | 27317240.86 | 0.103355E+09 | 89025518.31 |
Annual Sum or Average | 0.185640E+10 | 0.127451E+10 | 0.581894E+09 | 0.240084E+10 | 0.846235E+09 |
Minimum of Months | 82424543.67 | 52228248.31 | 27317240.86 | 0.103355E+09 | 56252549.48 |
Maximum of Months | 0.239853E+09 | 0.179984E+09 | 73199587.90 | 0.314852E+09 | 89025518.31 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 89343578.36 | 58075949.06 | 31267629.30 | 0.114688E+09 | 83056646.52 |
February | 93512011.46 | 52228248.31 | 41283763.16 | 0.116454E+09 | 64729824.99 |
March | 0.135991E+09 | 77257017.02 | 58734429.67 | 0.175237E+09 | 71200246.54 |
April | 0.199032E+09 | 0.144668E+09 | 54364280.59 | 0.259969E+09 | 68208603.85 |
May | 0.205525E+09 | 0.132325E+09 | 73199587.90 | 0.263346E+09 | 67626204.97 |
June | 0.211464E+09 | 0.145818E+09 | 65645767.76 | 0.273999E+09 | 56252549.48 |
July | 0.239853E+09 | 0.179984E+09 | 59869317.62 | 0.314852E+09 | 60726573.13 |
August | 0.221854E+09 | 0.170255E+09 | 51598633.65 | 0.292679E+09 | 63086802.01 |
September | 0.164561E+09 | 0.117192E+09 | 47368590.56 | 0.213912E+09 | 65689146.68 |
October | 0.120124E+09 | 82855881.69 | 37268259.81 | 0.156356E+09 | 75759175.89 |
November | 92714939.67 | 58738049.16 | 33976890.51 | 0.115997E+09 | 80874198.25 |
December | 82424543.67 | 55107302.81 | 27317240.86 | 0.103355E+09 | 89025518.31 |
Annual Sum or Average | 0.185640E+10 | 0.127451E+10 | 0.581894E+09 | 0.240084E+10 | 0.846235E+09 |
Minimum of Months | 82424543.67 | 52228248.31 | 27317240.86 | 0.103355E+09 | 56252549.48 |
Maximum of Months | 0.239853E+09 | 0.179984E+09 | 73199587.90 | 0.314852E+09 | 89025518.31 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182014E+09 | 0.120128E+09 | 61885676.86 | 0.246111E+09 | 0.103973E+09 |
February | 0.186919E+09 | 0.105210E+09 | 81709860.44 | 0.242826E+09 | 85092398.80 |
March | 0.267498E+09 | 0.151249E+09 | 0.116249E+09 | 0.355916E+09 | 95423084.39 |
April | 0.386740E+09 | 0.279141E+09 | 0.107599E+09 | 0.516424E+09 | 94382172.24 |
May | 0.398741E+09 | 0.253863E+09 | 0.144878E+09 | 0.519858E+09 | 96275492.84 |
June | 0.409178E+09 | 0.279251E+09 | 0.129928E+09 | 0.537191E+09 | 82643286.81 |
July | 0.463365E+09 | 0.344870E+09 | 0.118495E+09 | 0.609003E+09 | 95306067.65 |
August | 0.429533E+09 | 0.327408E+09 | 0.102125E+09 | 0.566851E+09 | 98998032.16 |
September | 0.320532E+09 | 0.226779E+09 | 93753103.59 | 0.421027E+09 | 97230006.02 |
October | 0.237825E+09 | 0.164062E+09 | 73762275.40 | 0.313477E+09 | 0.109863E+09 |
November | 0.187652E+09 | 0.120404E+09 | 67247914.66 | 0.245215E+09 | 0.107792E+09 |
December | 0.169838E+09 | 0.115771E+09 | 54066968.89 | 0.224594E+09 | 0.115589E+09 |
Annual Sum or Average | 0.363984E+10 | 0.248814E+10 | 0.115170E+10 | 0.479849E+10 | 0.118257E+10 |
Minimum of Months | 0.169838E+09 | 0.105210E+09 | 54066968.89 | 0.224594E+09 | 82643286.81 |
Maximum of Months | 0.463365E+09 | 0.344870E+09 | 0.144878E+09 | 0.609003E+09 | 0.115589E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 200.53 | 227.05 | 157.09 | 64.57 | 92.53 | 0.00 | 0.00 |
February | 228.05 | 204.56 | 189.07 | 70.40 | 118.67 | 0.00 | 0.00 |
March | 270.57 | 213.91 | 219.58 | 77.33 | 142.25 | 0.00 | 0.00 |
April | 388.88 | 197.43 | 292.37 | 125.39 | 166.98 | 0.00 | 0.00 |
May | 380.98 | 186.77 | 298.82 | 112.21 | 186.61 | 0.00 | 0.00 |
June | 425.91 | 156.87 | 317.00 | 131.95 | 185.05 | 0.00 | 0.00 |
July | 460.10 | 154.58 | 328.24 | 147.43 | 180.81 | 0.00 | 0.00 |
August | 428.53 | 161.31 | 301.11 | 136.04 | 165.07 | 0.00 | 0.00 |
September | 354.57 | 177.67 | 257.15 | 113.99 | 143.16 | 0.00 | 0.00 |
October | 283.66 | 191.56 | 198.03 | 89.15 | 108.88 | 0.00 | 0.00 |
November | 224.34 | 224.77 | 178.69 | 76.85 | 101.84 | 0.00 | 0.00 |
December | 199.30 | 238.02 | 156.81 | 69.38 | 87.43 | 0.00 | 0.00 |
Annual Sum or Average | 320.91 | 194.52 | 241.37 | 101.36 | 140.01 | 0.00 | 0.00 |
Minimum of Months | 199.30 | 154.58 | 156.81 | 64.57 | 87.43 | 0.00 | 0.00 |
Maximum of Months | 460.10 | 238.02 | 328.24 | 147.43 | 186.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 599.47 | 434.14 | 467.00 | 303.56 | 163.44 | 0.00 | 0.00 |
February | 673.93 | 374.59 | 541.16 | 302.25 | 238.91 | 0.00 | 0.00 |
March | 915.96 | 372.16 | 710.83 | 403.82 | 307.00 | 0.00 | 0.00 |
April | 1404.16 | 368.41 | 1075.02 | 781.39 | 293.63 | 0.00 | 0.00 |
May | 1376.51 | 353.48 | 1074.28 | 691.66 | 382.61 | 0.00 | 0.00 |
June | 1479.93 | 303.83 | 1142.17 | 787.60 | 354.57 | 0.00 | 0.00 |
July | 1645.73 | 317.42 | 1253.71 | 940.78 | 312.94 | 0.00 | 0.00 |
August | 1529.83 | 329.75 | 1159.63 | 889.93 | 269.71 | 0.00 | 0.00 |
September | 1155.39 | 354.80 | 888.83 | 632.98 | 255.85 | 0.00 | 0.00 |
October | 817.27 | 395.99 | 627.89 | 433.09 | 194.80 | 0.00 | 0.00 |
November | 626.53 | 436.82 | 500.78 | 317.26 | 183.52 | 0.00 | 0.00 |
December | 540.24 | 465.34 | 430.83 | 288.05 | 142.79 | 0.00 | 0.00 |
Annual Sum or Average | 1065.82 | 375.68 | 824.12 | 565.80 | 258.32 | 0.00 | 0.00 |
Minimum of Months | 540.24 | 303.83 | 430.83 | 288.05 | 142.79 | 0.00 | 0.00 |
Maximum of Months | 1645.73 | 465.34 | 1253.71 | 940.78 | 382.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 11586.65 | 4554.67 | 2174.60 | 1435.23 | 739.37 | 0.00 | 0.00 |
February | 12637.17 | 3888.94 | 2472.48 | 1391.66 | 1080.82 | 0.00 | 0.00 |
March | 17590.29 | 3802.80 | 3195.91 | 1807.04 | 1388.87 | 0.00 | 0.00 |
April | 24627.75 | 3548.32 | 4774.56 | 3446.18 | 1328.38 | 0.00 | 0.00 |
May | 23574.11 | 3456.34 | 4763.94 | 3033.01 | 1730.93 | 0.00 | 0.00 |
June | 25464.72 | 3114.44 | 5051.59 | 3447.54 | 1604.05 | 0.00 | 0.00 |
July | 35958.65 | 3594.45 | 5536.02 | 4120.31 | 1415.71 | 0.00 | 0.00 |
August | 31741.78 | 3798.52 | 5131.82 | 3911.69 | 1220.14 | 0.00 | 0.00 |
September | 18368.72 | 3833.26 | 3957.19 | 2799.74 | 1157.45 | 0.00 | 0.00 |
October | 15041.60 | 4089.72 | 2841.39 | 1960.12 | 881.27 | 0.00 | 0.00 |
November | 12012.90 | 4356.60 | 2316.69 | 1486.46 | 830.22 | 0.00 | 0.00 |
December | 10827.04 | 4783.33 | 2029.13 | 1383.17 | 645.96 | 0.00 | 0.00 |
Annual Sum or Average | 20010.92 | 3903.95 | 3693.39 | 2524.74 | 1168.65 | 0.00 | 0.00 |
Minimum of Months | 10827.04 | 3114.44 | 2029.13 | 1383.17 | 645.96 | 0.00 | 0.00 |
Maximum of Months | 35958.65 | 4783.33 | 5536.02 | 4120.31 | 1730.93 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.537097E+09 | 0.608143E+09 | 0.420759E+09 | 0.172931E+09 | 0.247828E+09 | 0.00 | 0.00 |
February | 0.551706E+09 | 0.494861E+09 | 0.457404E+09 | 0.170309E+09 | 0.287095E+09 | 0.00 | 0.00 |
March | 0.724706E+09 | 0.572939E+09 | 0.588119E+09 | 0.207112E+09 | 0.381007E+09 | 0.00 | 0.00 |
April | 0.100799E+10 | 0.511746E+09 | 0.757818E+09 | 0.325005E+09 | 0.432813E+09 | 0.00 | 0.00 |
May | 0.102042E+10 | 0.500238E+09 | 0.800361E+09 | 0.300543E+09 | 0.499818E+09 | 0.00 | 0.00 |
June | 0.110395E+10 | 0.406615E+09 | 0.821660E+09 | 0.342011E+09 | 0.479649E+09 | 0.00 | 0.00 |
July | 0.123232E+10 | 0.414022E+09 | 0.879171E+09 | 0.394888E+09 | 0.484283E+09 | 0.00 | 0.00 |
August | 0.114778E+10 | 0.432051E+09 | 0.806493E+09 | 0.364361E+09 | 0.442132E+09 | 0.00 | 0.00 |
September | 0.919052E+09 | 0.460516E+09 | 0.666537E+09 | 0.295465E+09 | 0.371072E+09 | 0.00 | 0.00 |
October | 0.759765E+09 | 0.513085E+09 | 0.530407E+09 | 0.238779E+09 | 0.291628E+09 | 0.00 | 0.00 |
November | 0.581501E+09 | 0.582600E+09 | 0.463170E+09 | 0.199190E+09 | 0.263980E+09 | 0.00 | 0.00 |
December | 0.533800E+09 | 0.637522E+09 | 0.420006E+09 | 0.185841E+09 | 0.234165E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101201E+11 | 0.613434E+10 | 0.761190E+10 | 0.319643E+10 | 0.441547E+10 | 0.00 | 0.00 |
Minimum of Months | 0.533800E+09 | 0.406615E+09 | 0.420006E+09 | 0.170309E+09 | 0.234165E+09 | 0.00 | 0.00 |
Maximum of Months | 0.123232E+10 | 0.637522E+09 | 0.879171E+09 | 0.394888E+09 | 0.499818E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.160563E+10 | 0.116279E+10 | 0.125081E+10 | 0.813063E+09 | 0.437747E+09 | 0.00 | 0.00 |
February | 0.163036E+10 | 0.906218E+09 | 0.130917E+10 | 0.731195E+09 | 0.577973E+09 | 0.00 | 0.00 |
March | 0.245331E+10 | 0.996803E+09 | 0.190388E+10 | 0.108160E+10 | 0.822282E+09 | 0.00 | 0.00 |
April | 0.363957E+10 | 0.954920E+09 | 0.278645E+10 | 0.202535E+10 | 0.761100E+09 | 0.00 | 0.00 |
May | 0.368684E+10 | 0.946767E+09 | 0.287735E+10 | 0.185255E+10 | 0.102479E+10 | 0.00 | 0.00 |
June | 0.383598E+10 | 0.787536E+09 | 0.296050E+10 | 0.204146E+10 | 0.919041E+09 | 0.00 | 0.00 |
July | 0.440793E+10 | 0.850172E+09 | 0.335795E+10 | 0.251978E+10 | 0.838170E+09 | 0.00 | 0.00 |
August | 0.409750E+10 | 0.883215E+09 | 0.310596E+10 | 0.238358E+10 | 0.722381E+09 | 0.00 | 0.00 |
September | 0.299477E+10 | 0.919648E+09 | 0.230385E+10 | 0.164069E+10 | 0.663160E+09 | 0.00 | 0.00 |
October | 0.218899E+10 | 0.106063E+10 | 0.168174E+10 | 0.115998E+10 | 0.521756E+09 | 0.00 | 0.00 |
November | 0.162396E+10 | 0.113224E+10 | 0.129801E+10 | 0.822333E+09 | 0.475676E+09 | 0.00 | 0.00 |
December | 0.144697E+10 | 0.124636E+10 | 0.115394E+10 | 0.771502E+09 | 0.382441E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.336118E+11 | 0.118473E+11 | 0.259896E+11 | 0.178431E+11 | 0.814652E+10 | 0.00 | 0.00 |
Minimum of Months | 0.144697E+10 | 0.787536E+09 | 0.115394E+10 | 0.731195E+09 | 0.382441E+09 | 0.00 | 0.00 |
Maximum of Months | 0.440793E+10 | 0.124636E+10 | 0.335795E+10 | 0.251978E+10 | 0.102479E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.310337E+11 | 0.121992E+11 | 0.582445E+10 | 0.384411E+10 | 0.198034E+10 | 0.00 | 0.00 |
February | 0.305718E+11 | 0.940813E+10 | 0.598142E+10 | 0.336671E+10 | 0.261472E+10 | 0.00 | 0.00 |
March | 0.471138E+11 | 0.101854E+11 | 0.855993E+10 | 0.483997E+10 | 0.371996E+10 | 0.00 | 0.00 |
April | 0.638351E+11 | 0.919725E+10 | 0.123757E+11 | 0.893250E+10 | 0.344317E+10 | 0.00 | 0.00 |
May | 0.631409E+11 | 0.925747E+10 | 0.127597E+11 | 0.812362E+10 | 0.463611E+10 | 0.00 | 0.00 |
June | 0.660045E+11 | 0.807262E+10 | 0.130937E+11 | 0.893602E+10 | 0.415769E+10 | 0.00 | 0.00 |
July | 0.963116E+11 | 0.962737E+10 | 0.148277E+11 | 0.110358E+11 | 0.379184E+10 | 0.00 | 0.00 |
August | 0.850172E+11 | 0.101739E+11 | 0.137451E+11 | 0.104771E+11 | 0.326801E+10 | 0.00 | 0.00 |
September | 0.476117E+11 | 0.993581E+10 | 0.102570E+11 | 0.725693E+10 | 0.300010E+10 | 0.00 | 0.00 |
October | 0.402874E+11 | 0.109539E+11 | 0.761039E+10 | 0.525000E+10 | 0.236039E+10 | 0.00 | 0.00 |
November | 0.311374E+11 | 0.112923E+11 | 0.600485E+10 | 0.385292E+10 | 0.215193E+10 | 0.00 | 0.00 |
December | 0.289991E+11 | 0.128117E+11 | 0.543483E+10 | 0.370468E+10 | 0.173014E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.631064E+12 | 0.123115E+12 | 0.116475E+12 | 0.796204E+11 | 0.368544E+11 | 0.00 | 0.00 |
Minimum of Months | 0.289991E+11 | 0.807262E+10 | 0.543483E+10 | 0.336671E+10 | 0.173014E+10 | 0.00 | 0.00 |
Maximum of Months | 0.963116E+11 | 0.128117E+11 | 0.148277E+11 | 0.110358E+11 | 0.463611E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.823863E+09 | -742376696.2 | 0.00 | 0.00 | 744.00 | 0.00 | -81485835.2 | 58.99 | 0.00 | 0.00 |
February | 0.755875E+09 | -682805400.5 | 0.00 | 0.00 | 672.00 | 0.00 | -73069389.5 | 59.00 | 0.00 | 0.00 |
March | 0.869806E+09 | -789286970.6 | 0.00 | 0.00 | 744.00 | 0.00 | -80518591.4 | 59.00 | 0.00 | 0.00 |
April | 0.792290E+09 | -718023898.8 | 0.00 | 0.00 | 720.00 | 0.00 | -74265644.8 | 58.99 | 0.00 | 0.00 |
May | 0.803249E+09 | -727627059.2 | 0.00 | 0.00 | 744.00 | 0.00 | -75622134.7 | 58.99 | 0.00 | 0.00 |
June | 0.779786E+09 | -708293302.0 | 0.00 | 0.00 | 720.00 | 0.00 | -71492205.2 | 58.99 | 0.00 | 0.00 |
July | 0.746542E+09 | -674424720.6 | 0.00 | 0.00 | 744.00 | 0.00 | -72117398.8 | 58.99 | 0.00 | 0.00 |
August | 0.795945E+09 | -723280234.9 | 0.00 | 0.00 | 744.00 | 0.00 | -72665214.0 | 58.99 | 0.00 | 0.00 |
September | 0.751814E+09 | -680580892.8 | 0.00 | 0.00 | 720.00 | 0.00 | -71233529.3 | 58.99 | 0.00 | 0.00 |
October | 0.771985E+09 | -697608982.7 | 0.00 | 0.00 | 744.00 | 0.00 | -74376218.9 | 58.99 | 0.00 | 0.00 |
November | 0.764007E+09 | -687596641.2 | 0.00 | 0.00 | 720.00 | 0.00 | -76410655.5 | 58.99 | 0.00 | 0.00 |
December | 0.812667E+09 | -732058519.1 | 0.00 | 0.00 | 744.00 | 0.00 | -80608807.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.946783E+10 | -0.856396E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -903865624.3 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.746542E+09 | -789286970.6 | 0.00 | 0.00 | 672.00 | 0.00 | -81485835.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.869806E+09 | -674424720.6 | 0.00 | 0.00 | 744.00 | 0.00 | -71233529.3 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.81 | 0.50 | 16-JAN-11:09 | 131.98 | 0.00 | 0.00 | 4.33 | 110.87 | 0.00 | 0.00 | 0.00 |
February | 279.67 | 0.74 | 0.50 | 04-FEB-13:30 | 175.37 | 0.00 | 0.00 | 29.33 | 657.83 | 0.00 | 0.00 | 36.33 |
March | 338.17 | 0.71 | 0.50 | 02-MAR-10:39 | 857.08 | 0.00 | 0.00 | 94.67 | 224.94 | 0.00 | 0.00 | 36.50 |
April | 358.33 | 0.71 | 0.50 | 01-APR-10:00 | 206.60 | 0.00 | 0.00 | 40.00 | 168.00 | 0.00 | 0.00 | 24.83 |
May | 393.83 | 0.68 | 0.50 | 01-MAY-10:09 | 251.92 | 0.00 | 0.00 | 106.00 | 1917.16 | 0.00 | 0.00 | 80.17 |
June | 381.00 | 0.69 | 0.50 | 01-JUN-10:09 | 1642.08 | 0.00 | 0.00 | 101.83 | 695.34 | 0.00 | 0.00 | 38.33 |
July | 408.67 | 0.71 | 0.50 | 01-JUL-10:09 | 219.47 | 0.00 | 0.00 | 78.50 | 2331.13 | 0.00 | 0.00 | 66.33 |
August | 390.67 | 0.72 | 0.50 | 01-AUG-10:09 | 195.36 | 0.00 | 0.00 | 40.00 | 721.99 | 0.00 | 0.00 | 24.33 |
September | 328.83 | 0.72 | 0.50 | 05-SEP-09:00 | 194.94 | 0.00 | 0.00 | 34.00 | 159.40 | 0.00 | 0.00 | 10.67 |
October | 296.17 | 0.78 | 0.50 | 01-OCT-10:30 | 1387.55 | 0.00 | 0.00 | 48.17 | 125.10 | 0.00 | 0.00 | 8.17 |
November | 300.00 | 0.80 | 0.50 | 01-NOV-10:30 | 140.46 | 0.00 | 0.00 | 8.50 | 117.85 | 0.00 | 0.00 | 0.50 |
December | 297.00 | 0.84 | 0.50 | 01-DEC-11:30 | 114.28 | 0.00 | 0.00 | 0.00 | 96.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4065.67 | 0.74 | 465.76 | 0.00 | 0.00 | 585.33 | 679.10 | 0.00 | 0.00 | 326.17 | ||
Minimum of Months | 279.67 | 0.68 | 0.50 | 114.28 | 0.00 | 0.00 | 0.00 | 96.70 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 408.67 | 0.84 | 0.50 | 1642.08 | 0.00 | 0.00 | 106.00 | 2331.13 | 0.00 | 0.00 | 80.17 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.67 | 0.50 | 01-JAN-09:20 | 161.78 | 11.36 | 0.00 | 64.50 | 133.05 | 15.07 | 0.83 | 41.33 |
February | 279.67 | 0.63 | 0.50 | 01-FEB-09:20 | 208.93 | 12.45 | 0.00 | 128.67 | 849.68 | 16.10 | 20.33 | 89.33 |
March | 338.17 | 0.60 | 0.50 | 01-MAR-09:30 | 249.62 | 12.97 | 0.00 | 207.00 | 281.99 | 16.61 | 45.83 | 155.33 |
April | 358.33 | 0.59 | 0.50 | 01-APR-08:20 | 1462.67 | 14.31 | 34.83 | 230.33 | 206.92 | 16.67 | 60.67 | 171.17 |
May | 393.83 | 0.58 | 0.50 | 01-MAY-06:00 | 281.77 | 13.21 | 0.00 | 271.83 | 238.87 | 16.92 | 72.83 | 206.83 |
June | 381.00 | 0.59 | 0.50 | 01-JUN-06:00 | 265.66 | 12.78 | 0.00 | 262.17 | 222.66 | 16.47 | 58.50 | 198.83 |
July | 408.67 | 0.59 | 0.50 | 01-JUL-07:30 | 248.84 | 12.55 | 0.00 | 266.50 | 208.88 | 16.36 | 72.17 | 192.17 |
August | 390.67 | 0.60 | 0.50 | 01-AUG-07:19 | 1576.58 | 13.96 | 36.67 | 238.17 | 194.13 | 16.26 | 60.17 | 169.67 |
September | 328.83 | 0.60 | 0.50 | 01-SEP-07:10 | 231.54 | 12.23 | 0.00 | 200.50 | 191.08 | 15.98 | 31.00 | 137.50 |
October | 296.17 | 0.66 | 0.50 | 01-OCT-09:39 | 2383.48 | 13.25 | 36.17 | 138.00 | 899.19 | 16.87 | 42.83 | 97.17 |
November | 300.00 | 0.67 | 0.50 | 01-NOV-08:30 | 170.34 | 11.18 | 0.00 | 84.67 | 139.80 | 14.78 | 6.00 | 57.67 |
December | 297.00 | 0.71 | 0.50 | 01-DEC-08:50 | 140.81 | 10.55 | 0.00 | 46.67 | 115.28 | 14.22 | 0.17 | 23.67 |
Annual Sum or Average | 4065.67 | 0.62 | 619.63 | 12.65 | 107.67 | 2139.00 | 293.09 | 16.09 | 471.33 | 1540.67 | ||
Minimum of Months | 279.67 | 0.58 | 0.50 | 140.81 | 10.55 | 0.00 | 46.67 | 115.28 | 14.22 | 0.17 | 23.67 | |
Maximum of Months | 408.67 | 0.71 | 0.50 | 2383.48 | 14.31 | 36.67 | 271.83 | 899.19 | 16.92 | 72.83 | 206.83 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.83 | 0.64 | 30-JAN-15:50 | 301.35 | 22.47 | 111.17 | 36.33 | 100.64 | 19.86 | 85.50 | 0.00 |
February | 279.67 | 0.80 | 0.61 | 06-FEB-15:30 | 317.11 | 22.80 | 125.67 | 45.67 | 155.19 | 22.15 | 124.83 | 12.67 |
March | 338.17 | 0.79 | 0.61 | 01-MAR-15:09 | 268.49 | 21.97 | 143.67 | 54.33 | 218.60 | 23.04 | 155.83 | 35.83 |
April | 358.33 | 0.78 | 0.61 | 01-APR-14:30 | 236.96 | 20.49 | 131.00 | 64.00 | 337.70 | 22.12 | 154.67 | 63.17 |
May | 393.83 | 0.77 | 0.61 | 01-MAY-14:50 | 239.52 | 20.27 | 131.67 | 58.17 | 297.74 | 21.63 | 182.33 | 67.33 |
June | 381.00 | 0.77 | 0.61 | 01-JUN-14:50 | 241.89 | 20.20 | 130.50 | 58.67 | 231.59 | 21.79 | 168.17 | 71.33 |
July | 408.67 | 0.77 | 0.61 | 01-JUL-15:20 | 239.83 | 20.22 | 143.50 | 59.50 | 237.47 | 21.82 | 191.17 | 78.50 |
August | 390.67 | 0.78 | 0.61 | 01-AUG-14:00 | 229.11 | 20.21 | 140.67 | 59.00 | 341.57 | 21.68 | 173.83 | 72.33 |
September | 328.83 | 0.78 | 0.61 | 01-SEP-15:09 | 253.85 | 21.81 | 142.00 | 57.83 | 257.89 | 23.73 | 161.33 | 49.50 |
October | 296.17 | 0.81 | 0.61 | 01-OCT-15:09 | 353.27 | 22.65 | 110.33 | 40.00 | 257.00 | 22.47 | 102.67 | 25.83 |
November | 300.00 | 0.82 | 0.61 | 03-NOV-15:20 | 270.44 | 22.58 | 132.00 | 37.33 | 108.52 | 19.80 | 105.50 | 0.00 |
December | 297.00 | 0.83 | 0.64 | 02-DEC-15:30 | 246.31 | 22.23 | 113.67 | 30.50 | 94.72 | 19.42 | 82.00 | 0.00 |
Annual Sum or Average | 4065.67 | 0.79 | 262.98 | 21.36 | 1555.83 | 601.33 | 227.62 | 21.67 | 1687.83 | 476.50 | ||
Minimum of Months | 279.67 | 0.77 | 0.61 | 229.11 | 20.20 | 110.33 | 30.50 | 94.72 | 19.42 | 82.00 | 0.00 | |
Maximum of Months | 408.67 | 0.83 | 0.64 | 353.27 | 22.80 | 143.67 | 64.00 | 341.57 | 23.73 | 191.17 | 78.50 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.673149E+09 | 24933.00 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.367120E+09 | 24933.00 | 04-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511879E+09 | 24933.00 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 40260664.74 | 24933.00 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2766208.07 | 4937.61 | 15-MAY-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130783E+09 | 24933.00 | 18-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.382371E+09 | 24933.00 | 04-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.673149E+09 | 24933.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.353069E+09 | 61827.70 | 09-JAN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1493410.01 | 2489.02 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.354562E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.353069E+09 | 61827.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.210711E+09 | 0.205457E+09 | 3735.83 | 24-JAN-15:30 | 3622.38 | 0.00 |
February | 0.00 | 0.00 | 60094539.11 | 60027650.14 | 2986.51 | 03-FEB-15:00 | 2986.51 | 0.00 |
March | 0.00 | 0.00 | 0.151485E+09 | 0.131120E+09 | 4428.87 | 23-MAR-14:00 | 3445.89 | 0.00 |
April | 0.00 | 0.00 | 0.707388E+09 | 0.589816E+09 | 6762.75 | 26-APR-14:20 | 6077.55 | 0.00 |
May | 0.00 | 0.00 | 0.818251E+09 | 0.700375E+09 | 6522.38 | 03-MAY-14:00 | 5530.73 | 0.00 |
June | 0.00 | 0.00 | 0.298699E+10 | 0.226669E+10 | 18341.93 | 30-JUN-05:02 | 9830.25 | 0.00 |
July | 0.00 | 0.00 | 0.611187E+10 | 0.441000E+10 | 18916.11 | 29-JUL-05:02 | 9527.77 | 0.00 |
August | 0.00 | 0.00 | 0.672888E+10 | 0.475615E+10 | 19221.34 | 07-AUG-05:02 | 9001.66 | 0.00 |
September | 0.00 | 0.00 | 0.323928E+10 | 0.246512E+10 | 18245.22 | 09-SEP-05:03 | 10631.95 | 0.00 |
October | 0.00 | 0.00 | 0.319975E+10 | 0.267824E+10 | 19548.64 | 05-OCT-05:02 | 10062.39 | 0.00 |
November | 0.00 | 0.00 | 0.202242E+09 | 0.201118E+09 | 4106.16 | 18-NOV-14:30 | 4106.16 | 0.00 |
December | 0.00 | 0.00 | 0.242786E+09 | 0.242291E+09 | 4099.57 | 05-DEC-15:00 | 4099.57 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.246597E+11 | 0.187064E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 60094539.11 | 60027650.14 | 2986.51 | 2986.51 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.672888E+10 | 0.475615E+10 | 19548.64 | 10631.95 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 40291121.75 | 35965000.49 | 5233.89 | 26-APR-13:10 | 4632.48 | 0.00 |
May | 0.00 | 0.00 | 67177869.05 | 56744039.68 | 4197.99 | 04-MAY-12:10 | 3453.14 | 0.00 |
June | 0.00 | 0.00 | 0.129710E+10 | 0.892555E+09 | 52354.93 | 29-JUN-17:22 | 32797.71 | 0.00 |
July | 0.00 | 0.00 | 0.646494E+10 | 0.436594E+10 | 54501.70 | 19-JUL-17:10 | 40241.11 | 0.00 |
August | 0.00 | 0.00 | 0.641032E+10 | 0.419939E+10 | 54250.68 | 06-AUG-10:25 | 32799.69 | 0.00 |
September | 0.00 | 0.00 | 0.128230E+10 | 0.115063E+10 | 52052.55 | 10-SEP-13:33 | 33884.48 | 0.00 |
October | 0.00 | 0.00 | 0.162433E+10 | 0.147458E+10 | 54384.21 | 01-OCT-12:05 | 34356.29 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.171865E+11 | 0.121758E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.646494E+10 | 0.436594E+10 | 54501.70 | 40241.11 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.112480E+10 | 0.36 | 1121.59 | 02-JAN-07:50 | 0.92 |
February | 0.103161E+10 | 0.37 | 1121.59 | 01-FEB-10:50 | 0.92 |
March | 0.121123E+10 | 0.38 | 1121.59 | 23-MAR-06:30 | 0.92 |
April | 0.111162E+10 | 0.35 | 1121.59 | 04-APR-12:30 | 0.92 |
May | 0.115503E+10 | 0.35 | 1121.59 | 01-MAY-14:30 | 0.92 |
June | 0.116328E+10 | 0.37 | 1121.59 | 06-JUN-16:50 | 0.92 |
July | 0.113719E+10 | 0.35 | 1121.59 | 08-JUL-11:20 | 0.92 |
August | 0.122537E+10 | 0.38 | 1121.59 | 01-AUG-16:20 | 0.92 |
September | 0.111680E+10 | 0.35 | 1121.59 | 06-SEP-10:30 | 0.91 |
October | 0.111819E+10 | 0.34 | 1121.59 | 02-OCT-06:20 | 0.91 |
November | 0.107024E+10 | 0.35 | 1121.59 | 22-NOV-10:30 | 0.92 |
December | 0.112055E+10 | 0.36 | 1121.59 | 04-DEC-11:20 | 0.92 |
Annual Sum or Average | 0.135859E+11 | 0.36 | |||
Minimum of Months | 0.103161E+10 | 0.34 | 1121.59 | 0.91 | |
Maximum of Months | 0.122537E+10 | 0.38 | 1121.59 | 0.92 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.971014E+09 | 0.21 | 2090.67 | 09-JAN-06:07 | 0.89 |
February | 0.882545E+09 | 0.20 | 968.98 | 01-FEB-07:10 | 0.54 |
March | 0.103606E+10 | 0.21 | 1019.48 | 30-MAR-06:10 | 0.56 |
April | 0.959288E+09 | 0.21 | 968.98 | 26-APR-14:20 | 0.54 |
May | 0.997659E+09 | 0.21 | 968.98 | 03-MAY-11:50 | 0.54 |
June | 0.100489E+10 | 0.22 | 1561.18 | 29-JUN-17:20 | 0.71 |
July | 0.101445E+10 | 0.21 | 2422.44 | 19-JUL-17:10 | 0.88 |
August | 0.107094E+10 | 0.22 | 1848.63 | 20-AUG-15:12 | 0.78 |
September | 0.961053E+09 | 0.21 | 968.98 | 07-SEP-11:30 | 0.53 |
October | 0.969032E+09 | 0.20 | 1838.42 | 01-OCT-12:50 | 0.78 |
November | 0.920916E+09 | 0.20 | 968.98 | 01-NOV-06:10 | 0.54 |
December | 0.959288E+09 | 0.20 | 968.98 | 01-DEC-07:05 | 0.54 |
Annual Sum or Average | 0.117471E+11 | 0.21 | |||
Minimum of Months | 0.882545E+09 | 0.20 | 968.98 | 0.53 | |
Maximum of Months | 0.107094E+10 | 0.22 | 2422.44 | 0.89 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.117045E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.104462E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.124364E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.126021E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.132696E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.176649E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.234201E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.254617E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.178999E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.179074E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.111377E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.117313E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.185682E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.104462E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.254617E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.971014E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.882545E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.103606E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.969847E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.101478E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.131994E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.254172E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.259582E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.130306E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.140406E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.920916E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.959288E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.159190E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.882545E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.259582E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.112480E+10 | 0.210711E+09 | 0.673149E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103161E+10 | 60094539.11 | 0.367120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121123E+10 | 0.151485E+09 | 0.511879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111162E+10 | 0.707388E+09 | 40260664.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115503E+10 | 0.818251E+09 | 2766208.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.116328E+10 | 0.298699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.113719E+10 | 0.611187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.122537E+10 | 0.672888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111680E+10 | 0.323928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111819E+10 | 0.319975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107024E+10 | 0.202242E+09 | 0.130783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112055E+10 | 0.242786E+09 | 0.382371E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135859E+11 | 0.246597E+11 | 0.210833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103161E+10 | 60094539.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.122537E+10 | 0.672888E+10 | 0.673149E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.971014E+09 | 0.00 | 0.353069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.882545E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103606E+10 | 0.00 | 1493410.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.959288E+09 | 40291121.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.997659E+09 | 67177869.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100489E+10 | 0.124732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.101445E+10 | 0.605329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.107094E+10 | 0.614398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.961053E+09 | 0.125481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.969032E+09 | 0.157801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.920916E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.959288E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117471E+11 | 0.163849E+11 | 0.354562E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.882545E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.107094E+10 | 0.614398E+10 | 0.353069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.112480E+10 | 0.00 | 0.00 | 0.00 | 45654225.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103161E+10 | 0.00 | 0.00 | 0.00 | 13004121.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121123E+10 | 0.00 | 0.00 | 0.00 | 32413023.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111162E+10 | 0.00 | 0.00 | 0.00 | 0.148595E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115503E+10 | 0.00 | 0.00 | 0.00 | 0.171923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.116328E+10 | 0.00 | 0.00 | 0.00 | 0.603208E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.113719E+10 | 0.00 | 0.00 | 0.00 | 0.120481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.122537E+10 | 0.00 | 0.00 | 0.00 | 0.132080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111680E+10 | 0.00 | 0.00 | 0.00 | 0.673193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111819E+10 | 0.00 | 0.00 | 0.00 | 0.672553E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107024E+10 | 0.00 | 0.00 | 0.00 | 43535213.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112055E+10 | 0.00 | 0.00 | 0.00 | 52581545.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135859E+11 | 0.00 | 0.00 | 0.00 | 0.498228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103161E+10 | 0.00 | 0.00 | 0.00 | 13004121.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.122537E+10 | 0.00 | 0.00 | 0.00 | 0.132080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.971014E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.882545E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.959288E+09 | 0.00 | 0.00 | 0.00 | 10559256.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.997659E+09 | 0.00 | 0.00 | 0.00 | 17125319.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100489E+10 | 0.00 | 0.00 | 0.00 | 0.315058E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.101445E+10 | 0.00 | 0.00 | 0.00 | 0.152727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.107094E+10 | 0.00 | 0.00 | 0.00 | 0.152487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.961053E+09 | 0.00 | 0.00 | 0.00 | 0.342002E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.969032E+09 | 0.00 | 0.00 | 0.00 | 0.435027E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.920916E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.959288E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117471E+11 | 0.00 | 0.00 | 0.00 | 0.417191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.882545E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.107094E+10 | 0.00 | 0.00 | 0.00 | 0.152727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.510196E+09 | 1740050.98 | 0.00 | 584091.11 | 0.00 | 0.133388E+09 | 0.705482E+09 | 0.00 | 0.24 |
February | 0.639597E+09 | 2870900.18 | 0.00 | 487049.26 | 0.00 | 29491608.79 | 0.669620E+09 | 0.00 | 0.23 |
March | 0.737549E+09 | 0.00 | 0.00 | 688171.46 | 0.00 | 73680163.76 | 0.829884E+09 | 0.00 | 0.26 |
April | 0.151145E+09 | 3288188.84 | 0.00 | 3026469.25 | 0.00 | 2723282.44 | 0.253265E+10 | 0.00 | 0.60 |
May | 58799938.75 | 5009640.85 | 0.00 | 4020670.13 | 0.00 | 0.00 | 0.318700E+10 | 0.00 | 0.69 |
June | 13069970.43 | 0.100396E+09 | 0.00 | 5187663.98 | 0.00 | 0.00 | 0.253801E+10 | 0.00 | 0.89 |
July | 256479.69 | 0.447553E+09 | 0.00 | 6203843.93 | 0.00 | 0.00 | 0.128043E+10 | 0.00 | 0.76 |
August | 5671569.76 | 0.577491E+09 | 0.00 | 4127545.11 | 0.00 | 0.00 | 0.115688E+10 | 0.00 | 0.81 |
September | 28841473.28 | 0.105923E+09 | 0.00 | 4933498.65 | 0.00 | 0.00 | 0.230055E+10 | 0.00 | 0.82 |
October | 37426873.43 | 0.239339E+09 | 0.00 | 3526388.28 | 0.00 | 0.00 | 0.188047E+10 | 0.00 | 0.66 |
November | 0.310701E+09 | 1367085.52 | 0.00 | 1482746.70 | 0.00 | 0.00 | 0.168183E+10 | 0.00 | 0.37 |
December | 0.548223E+09 | 1421564.46 | 0.00 | 771491.11 | 0.00 | 30886278.40 | 0.855658E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.304148E+10 | 0.148640E+10 | 0.00 | 35039628.98 | 0.00 | 0.270169E+09 | 0.196185E+11 | 0.00 | 0.55 |
Minimum of Months | 256479.69 | 0.00 | 0.00 | 487049.26 | 0.00 | 0.00 | 0.669620E+09 | 0.00 | 0.23 |
Maximum of Months | 0.737549E+09 | 0.577491E+09 | 0.00 | 6203843.93 | 0.00 | 0.133388E+09 | 0.318700E+10 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.237653E+10 | 0.00 | 0.00 | 0.00 | 35639882.65 | 0.00 | 0.00 | 0.00 | 0.18 |
February | 0.256819E+10 | 0.00 | 0.00 | 0.00 | 6570067.99 | 0.00 | 0.00 | 0.00 | 0.18 |
March | 0.333807E+10 | 0.00 | 0.00 | 0.00 | 1401839.10 | 0.00 | 0.00 | 0.00 | 0.19 |
April | 0.331386E+10 | 0.00 | 0.00 | 198583.38 | 1644566.02 | 0.00 | 0.259119E+09 | 0.00 | 0.19 |
May | 0.353263E+10 | 0.00 | 0.00 | 569949.97 | 504338.65 | 0.00 | 0.536376E+09 | 0.00 | 0.20 |
June | 0.220704E+10 | 0.00 | 0.00 | 5284760.52 | 0.00 | 0.00 | 0.241397E+10 | 0.00 | 0.30 |
July | 0.528749E+09 | 0.190881E+09 | 0.00 | 14935210.56 | 0.00 | 0.00 | 0.390590E+10 | 0.00 | 0.42 |
August | 0.667777E+09 | 0.161628E+09 | 0.00 | 13762157.75 | 0.00 | 0.00 | 0.358853E+10 | 0.00 | 0.44 |
September | 0.188213E+10 | 93635737.42 | 0.00 | 2912310.83 | 0.00 | 0.00 | 0.248304E+10 | 0.00 | 0.26 |
October | 0.215371E+10 | 0.197365E+09 | 0.00 | 1205561.19 | 21051799.68 | 0.00 | 0.762458E+09 | 0.00 | 0.22 |
November | 0.283741E+10 | 0.00 | 0.00 | 0.00 | 1721924.23 | 0.00 | 0.00 | 0.00 | 0.18 |
December | 0.230633E+10 | 0.00 | 0.00 | 0.00 | 24281882.79 | 0.00 | 0.00 | 0.00 | 0.18 |
Annual Sum or Average | 0.277124E+11 | 0.643509E+09 | 0.00 | 38868534.21 | 92816301.12 | 0.00 | 0.139494E+11 | 0.00 | 0.24 |
Minimum of Months | 0.528749E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
Maximum of Months | 0.353263E+10 | 0.197365E+09 | 0.00 | 14935210.56 | 35639882.65 | 0.00 | 0.390590E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.577399E+12 | 0.175435E+11 | 0.00 | 0.368880E+10 | 0.732222E+09 |
February | 0.655652E+12 | 0.247670E+11 | 0.00 | 0.389795E+10 | 0.242557E+09 |
March | 0.924080E+12 | 0.314364E+11 | 0.00 | 0.497847E+10 | 0.419287E+09 |
April | 0.125307E+13 | 0.286165E+11 | 0.00 | 0.625779E+10 | 0.925067E+09 |
May | 0.131657E+13 | 0.371133E+11 | 0.00 | 0.731388E+10 | 0.107586E+10 |
June | 0.131307E+13 | 0.312595E+11 | 0.00 | 0.710743E+10 | 0.520236E+10 |
July | 0.143996E+13 | 0.337987E+11 | 0.00 | 0.512352E+10 | 0.153089E+11 |
August | 0.133559E+13 | 0.357866E+11 | 0.00 | 0.472403E+10 | 0.159849E+11 |
September | 0.103752E+13 | 0.255179E+11 | 0.00 | 0.653287E+10 | 0.553678E+10 |
October | 0.737824E+12 | 0.261817E+11 | 0.00 | 0.438562E+10 | 0.593166E+10 |
November | 0.618526E+12 | 0.238966E+11 | 0.00 | 0.482834E+10 | 0.305788E+09 |
December | 0.527643E+12 | 0.196891E+11 | 0.00 | 0.371617E+10 | 0.469823E+09 |
Annual Sum or Average | 0.117369E+14 | 0.335607E+12 | 0.00 | 0.625549E+11 | 0.521352E+11 |
Minimum of Months | 0.527643E+12 | 0.175435E+11 | 0.00 | 0.368880E+10 | 0.242557E+09 |