Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2023-10-16 10:41:44
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2376.96 | 491.60 | 491.60 |
Net Site Energy | 2376.96 | 491.60 | 491.60 |
Total Source Energy | 4042.59 | 836.09 | 836.09 |
Net Source Energy | 4042.59 | 836.09 | 836.09 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1673.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 8.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 397.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 92.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 137.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 40.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 27.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 703.77 | 1673.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1673.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 8.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 397.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 92.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 137.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 39.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 27.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1673.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 8.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 397.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 92.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 137.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 40.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 27.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 101.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 15.77 | 346.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 145.55 | 346.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 101.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 15.77 | 346.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 145.55 | 346.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 703.772 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 703.772 | 100.00 |
Total On-Site and Utility Electric Sources | 703.772 | 100.00 |
Total Electricity End Uses | 703.772 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 81.67 |
Time Setpoint Not Met During Occupied Cooling | 1.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3032.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 34.61 |
Skylight-Roof Ratio [%] | 0.75 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 9.9957 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 10.2257 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 6.2431 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.5746 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.5746 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 9.9957 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 10.2257 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 6.2431 | 46.45 | 2.5587 | |
Total | 4835.13 | 7.5746 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 7.5746 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 7.5746 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 30-JUN-14:00 | 04-JAN-06:10 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 383620.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 12504.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 28376.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4943.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1893.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 57771.93 | 383620.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 383620.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 12504.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 28376.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2638.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1893.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1813.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 27.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1259.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 293.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 434.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 127.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 86.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2228.85 | 1813.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 375.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 260.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 26.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 460.97 | 375.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 375.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 260.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 26.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 460.97 | 375.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.04 |
ZONE2 FINE STORAGE DIRECT AIR | 2.22 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 5.36 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 5.36 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 210276.34 |
PSZ-OFFICE HEATING COIL | 29306.84 |
PSZ-FINE STORAGE HEATING COIL | 86742.66 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 210276.35 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.00 | 1.00 | 1.04 |
PSZ-FINE STORAGE | 2.22 | 2.22 | 2.22 | 2.22 | 2.22 | 2.22 | 1.00 | 1.00 | 2.22 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.04 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.22 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.04 | 1155.48 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.22 | 2377.48 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 1.04 | 18591.65 | 29306.84 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.22 | 2.22 | 2.22 | 1.47 | 51458.38 | 86742.66 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.04 | 0.521821 | 0.695760 | 18591.65 | 9295.83 | 0.800640 | 0.800640 |
PSZ-FINE STORAGE COOLING COIL | 2.22 | 1.11 | 1.48 | 51458.38 | 25729.19 | 0.722780 | 0.722780 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 9.996 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.069 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 10.226 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.226 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 6.243 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 8.802 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2367.778 | 9.996 | 185.726 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2367.778 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 14248.589 | 10.226 | 474.953 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 14248.589 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 20008.023 | 6.243 | 289.971 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20008.023 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2893 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.4332 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.4133 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.7823 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.7823 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.457 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.309 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.320 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.179 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.179 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.87112823E-12 | 0.85080972E-17 | 0.21755189E-17 | 0.0000000 |
2 | 1 | -5.2160329 | 0.44465164E-04 | -0.55377147E-04 | 0.16700973E-12 |
3 | 0 | 5.5053245 | 0.28924715 | 0.28934699 | |
4 | 2 | 0.53503428E-11 | 0.43487872E-15 | 0.25437469E-15 | 0.0000000 |
5 | 1 | -5.2159992 | 0.41060176E-04 | -0.36984335E-04 | 0.68788638E-11 |
6 | 0 | 5.6491605 | 0.43312021 | 0.43319826 | |
7 | 4 | 0.79569988E-12 | 0.97024197E-16 | -0.20560970E-14 | 0.11376788E-15 |
8 | 3 | -0.38947258E-03 | 0.29188957E-06 | -0.56541964E-04 | 0.15267338E-12 |
9 | 2 | 1.7507793 | 0.63492849E-02 | 1.1490006 | -0.74668540E-04 |
10 | 1 | -7.1139048 | 0.16396836 | -17.152679 | 0.33556055 |
11 | 0 | 5.6381505 | 0.10431759 | 16.278371 | |
12 | 4 | 0.72249793E-12 | -0.16720573E-15 | 0.22015083E-14 | 0.12409536E-15 |
13 | 3 | -0.36459118E-03 | 0.53555631E-06 | -0.52695411E-04 | 0.13865996E-12 |
14 | 2 | 1.6915239 | 0.11971291E-01 | 1.1039557 | -0.69896550E-04 |
15 | 1 | -7.1930661 | 0.31446443 | -16.864389 | 0.32415671 |
16 | 0 | 6.0306730 | 0.20232993 | 16.289252 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.22015083E-14 | -0.16720573E-15 | 0.72249793E-12 | 0.12409536E-15 |
85 | 3 | -0.52695411E-04 | 0.53555631E-06 | -0.36459118E-03 | 0.13865996E-12 |
86 | 2 | 1.1039557 | 0.11971291E-01 | 1.6915239 | -0.69896550E-04 |
87 | 1 | -16.864389 | 0.31446443 | -7.1930661 | 0.32415671 |
88 | 0 | 16.289252 | 0.20232993 | 6.0306730 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.4258_SHGC_SOUTH_0.45 | 34 | 1 | VerySmooth | 2.420 | 2.420 | 1.000 | 0.451 | ||
2 | NONRESWINDOW_U_0.4258_SHGC_NORTH_0.45 | 35 | 1 | VerySmooth | 2.420 | 2.420 | 1.000 | 0.451 | ||
3 | NONRESWINDOW_U_0.4258_SHGC_EAST_0.45 | 36 | 1 | VerySmooth | 2.420 | 2.420 | 1.000 | 0.451 | ||
4 | NONRESWINDOW_U_0.4258_SHGC_WEST_0.45 | 37 | 1 | VerySmooth | 2.420 | 2.420 | 1.000 | 0.451 | ||
5 | SKYLIGHT_U_1.02_SHGC_0.68 | 38 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.682 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.96080E-002 | 0.36619 | 0.42689 | 0.42689 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.12246 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.96080E-002 | 0.36619 | 0.42689 | 0.42689 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.12246 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.96080E-002 | 0.36619 | 0.42689 | 0.42689 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.12246 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.96080E-002 | 0.36619 | 0.42689 | 0.42689 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.12246 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.57291 | 6.11155E-002 | 6.11155E-002 | 0.68000 | 0.13462 | 0.14960 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE3 BULK STORAGE | 10 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.849 | 0.366 | 0.255 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.264 | 7.065E-004 | 4.615E-004 | 0.231 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0858E-004 |
2 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7830E-004 |
3 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7720E-004 |
4 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2079E-004 |
5 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9086E-004 |
6 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9726E-004 |
7 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6611E-004 |
8 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4320E-003 |
9 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0962E-003 |
10 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2677E-004 |
11 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5986E-003 |
12 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4692E-003 |
13 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1064E-004 |
14 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2272E-004 |
15 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5037E-004 |
16 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4320E-003 |
17 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1730E-004 |
18 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8965E-004 |
19 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1046E-004 |
20 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2079E-004 |
21 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4350E-004 |
22 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1941E-004 |
23 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6143E-004 |
24 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2079E-004 |
25 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3428E-004 |
26 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7714E-004 |
27 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3516E-003 |
28 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4320E-003 |
29 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9906E-003 |
30 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9675E-003 |
31 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9656E-003 |
32 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4692E-003 |
33 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.7963E-004 |
34 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.4764E-004 |
35 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5120E-003 |
36 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4320E-003 |
37 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8219E-004 |
38 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6332E-004 |
39 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1044E-004 |
40 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2079E-004 |
41 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.3216E-002 |
42 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 7.2479E-004 |
43 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.3031E-002 |
44 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.5979E-004 |
45 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.1446E-002 |
46 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.4118E-004 |
47 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.7641E-003 |
48 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.5353E-004 |
49 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 7.3730E-004 |
50 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.3432E-002 |
51 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.7682E-004 |
52 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.7862E-002 |
53 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.4577E-004 |
54 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.8286E-002 |
55 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.5331E-004 |
56 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.2395E-002 |
57 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.9883E-003 |
58 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 4.3897E-004 |
59 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.5817E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.4701E-004 |
61 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.3562E-003 |
62 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.6117E-004 |
63 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.3505E-003 |
64 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.4187E-004 |
65 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.6438E-002 |
66 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.4960E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.2281E-002 |
68 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.5435E-004 |
69 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 8.7351E-003 |
70 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.6212E-004 |
71 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.3353E-002 |
72 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.4435E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10129.26916 | 12155.12299 | 0.86970 | 1.04364 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 28.36400 | 1.27228E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 12776.69023 | 15332.02828 | 0.37440 | 0.44928 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -32.70000 | 1.83376E-004 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 27662.12634 | 33194.55160 | 1.85154 | 2.22184 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.10000 | 1.27259E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 48256.14569 | 57907.37483 | 1.19060 | 1.42872 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -32.70000 | 1.83376E-004 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 30.10000 | 1.27259E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 175230.29176 | 210276.35012 | 4.46760 | 5.36112 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 14955.79 | 1.04364 | 1.04364 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 16246.98 | 0.44928 | 0.44928 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 39539.54 | 2.22184 | 2.22184 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 64261.17 | 1.42872 | 1.42872 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.04364 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.22184 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.36112 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 5.36112 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 210276.34437 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 210276.35012 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.04364 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.04364 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.04364 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.04364 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04364 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.04364 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.22184 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.22184 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.22184 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.22184 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.22184 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.22184 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.04364 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.22184 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04364 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04364 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1155.47698 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04364 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04364 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04364 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.04364 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04364 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52182 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69576 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18591.65000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9295.82500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80064 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80064 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18591.65000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29306.83757 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 29306.83757 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.22184 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.22184 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2377.47730 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.22184 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.22184 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.22184 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.46642 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.22184 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.11092 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.48123 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 51458.38000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 25729.19000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72278 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72278 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 51458.38000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 86742.65645 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 86742.65645 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 17781.6 | 11.85 | 11.58 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 49732.0 | 11.94 | 11.67 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.6051042707 | 0.6030637142 | Pass | Pass | 0.8898155391 | 0.8022221780 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 1.1806572261 | 1.1027962066 | Pass | Pass | 0.6438732490 | 0.6252078886 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 1.6534272428E-004 | 2.9369098759E-004 | Pass | Pass | 1.6767509716E-002 | 1.4461462250E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7723.12 | 860.76 | 0.00 | 112.12 | 427.44 | 9123.46 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.389 | 0.413 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.389 | 0.413 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.389 | 0.413 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.389 | 0.413 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.389 | 0.413 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.389 | 0.413 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.389 | 0.413 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.278 | 0.289 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.700 | 0.782 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.409 | 0.433 | 3204.84 | 3170.23 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.659 | 0.782 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.659 | 0.782 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.4258_SHGC_WEST_0.45 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.420 | 0.451 | 0.452 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.4258_SHGC_WEST_0.45 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.420 | 0.451 | 0.452 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.4258_SHGC_NORTH_0.45 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.420 | 0.451 | 0.452 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.4258_SHGC_NORTH_0.45 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.420 | 0.451 | 0.452 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.97 | 0.00 | 3.46 | 3.46 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.849 | 0.366 | 0.255 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 52.27 | 4.657 | 0.517 | 0.518 | |||||||||||||||||
North Total or Average | 6.51 | 2.420 | 0.451 | 0.452 | |||||||||||||||||
Non-North Total or Average | 45.76 | 4.975 | 0.526 | 0.527 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 9.9957 | 236.88 | 2367.78 | LightsWired | LTG_SCH_OFFICE | 56.95 | 168.00 | 48.36 | 0.0000 | Y | 21.50 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 10.2257 | 1393.41 | 14248.59 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 162.28 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 6.2431 | 3204.84 | 20008.02 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 56.96 | 0.0000 | Y | 213.93 |
Interior Lighting Total | 7.5746 | 4835.13 | 36624.39 | 397.70 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.12 | 20008.02 | 2320.93 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.11 | 2367.78 | 260.46 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.11 | 2367.78 | 260.46 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 125.92 | AstronomicalClock | - | 42.55 | 42.55 | 1.01 | |
EXTERIOR_LIGHTS_B | 6860.50 | AstronomicalClock | - | 83.52 | 71.23 | 91.73 | |
Exterior Lighting Total | 6986.42 | 92.73 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18591.65 | 14885.22 | 3706.43 | 0.80 | 3.91 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 51458.38 | 37193.09 | 14265.29 | 0.72 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 17781.6 | 11.85 | 11.58 | ||||
PSZ-FINE STORAGE COOLING COIL | 49732.0 | 11.94 | 11.67 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 210276.34 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 29306.84 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 86742.66 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 5.36 | 498.10 | 92.91 | 1.00 | 3.13 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1155.48 | 1107.16 | 1.00 | 1.39 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.22 | 2377.48 | 1070.05 | 1.00 | 1.30 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10129.27 | 12155.12 | 51.31 | 0.870 | 1.044 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00851 | 28.36 | 0.01272 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 27662.13 | 33194.55 | 23.82 | 1.852 | 2.222 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 26.70 | 26.70 | 0.00906 | 30.10 | 0.01273 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 0.00 | 30.71 | 0.01279 | 30.10 | 0.01273 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 12776.69 | 15332.03 | 64.72 | 0.374 | 0.449 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00776 | -32.70 | 0.00018 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 48256.15 | 57907.37 | 41.56 | 1.191 | 1.429 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.55 | 0.00681 | -32.70 | 0.00018 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 175230.29 | 210276.35 | 65.61 | 4.468 | 5.361 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00629 | -32.70 | 0.00018 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.04 | 1.04 | 0.45 | 0.45 | 1.0436 | 1.0436 | 1.0436 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.22 | 2.22 | 1.43 | 1.43 | 2.2218 | 2.2218 | 2.2218 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 210276.344 | 210276.344 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 210276.34 | 210276.34 | 5.361117 | 10.00 | 8.18 | 0.00628899 | 43.33 | 21.64 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 10.00 | 0.00628899 | 79.1581 | 210276.35 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 18591.650 | 14885.219 | 1.043640 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 9295.83 | 8071.95 | 0.695760 | 25.31 | 16.76 | 0.00892528 | 12.00 | 10.89 | 0.00800000 | 28.69 | 0.01272339 | 20.72 | 14.7011 | 23.90 | 0.00851223 | 44.1790 | 10121.22 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 29306.838 | 29306.838 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 29306.84 | 29306.84 | 1.043642 | 15.78 | 11.47 | 0.00702031 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 9.8007 | 21.10 | 0.00776319 | 47.8196 | 12776.69 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 51458.380 | 37193.088 | 2.221840 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 25729.19 | 20716.30 | 1.481227 | 28.25 | 18.40 | 0.00975820 | 12.00 | 10.89 | 0.00800000 | 30.10 | 0.01272586 | 21.13 | 28.6729 | 26.70 | 0.00905686 | 39.7627 | 27662.13 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 86742.656 | 86742.656 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 86742.66 | 86742.66 | 2.221843 | 6.33 | 5.55 | 0.00554393 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 19.1153 | 15.55 | 0.00681077 | 59.5023 | 48256.15 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 210276.344 | 210276.344 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 5.361117 | 6.18632642 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 210276.34 | 210276.34 | 1.0000 | 6.18632642 | 5.361117 | 10.00 | 8.18 | 0.00628899 | 25890.2 | 43.33 | 21.64 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 210276.34 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 10.00 | 0.00628899 | 10.00 | 0.00628899 | 79.1581 | 210276.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18591.650 | 14885.219 | 1.043640 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4317 | 1004.8586 | 1.1539 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.043642 | 1.20428405 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | Sensible | 9295.83 | 8071.95 | 1.0000 | 0.80285476 | 0.695760 | 25.31 | 16.76 | 0.00892528 | 48171.9 | 12.00 | 10.89 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9295.83 | 28.69 | 0.01272339 | 20.72 | 0.10228463 | 14.7011 | 23.90 | 0.00851223 | 23.90 | 0.00851223 | 44.1790 | 10121.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29306.838 | 29306.838 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.043642 | 1.20428405 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 29306.84 | 29306.84 | 1.0000 | 1.20428405 | 1.043642 | 15.78 | 11.47 | 0.00702031 | 33621.9 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29306.84 | -32.70 | 0.00018338 | -32.70 | 0.10228463 | 9.8007 | 21.05 | 0.00776319 | 21.10 | 0.00776319 | 47.8196 | 12776.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 51458.380 | 37193.088 | 2.221840 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.9800 | 1004.8586 | 1.1539 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.221843 | 2.56384015 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 25729.19 | 20716.30 | 1.0000 | 1.70922427 | 1.481227 | 28.25 | 18.40 | 0.00975820 | 53307.9 | 12.00 | 10.89 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25729.19 | 30.10 | 0.01272586 | 21.13 | 0.42471127 | 28.6729 | 26.70 | 0.00905686 | 26.70 | 0.00905686 | 39.7627 | 27662.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 86742.656 | 86742.656 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.221843 | 2.56384015 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 86742.66 | 86742.66 | 1.0000 | 2.56384015 | 2.221843 | 6.33 | 5.55 | 0.00554393 | 20291.4 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 86742.66 | -32.70 | 0.00018338 | -32.70 | 0.42471127 | 19.1153 | 15.55 | 0.00681077 | 15.55 | 0.00681077 | 59.5023 | 48256.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.04 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 2.22 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2725.50 | 2989.17 | 2287.17 |
ZONE2 FINE STORAGE | 3180.17 | 3128.83 | 2743.50 |
ZONE3 BULK STORAGE | 3210.50 | 3337.83 | 2971.00 |
Facility | 3385.00 | 3419.50 | 3032.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 275.83 | 41.33 | 68.67 | 1.83 |
ZONE2 FINE STORAGE | 614.00 | 3.67 | 28.17 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 795.67 | 44.17 | 81.67 | 1.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.675 | 0.315 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.504 | 0.245 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.127 | 0.000 | 0.099 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.50 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.36 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.28 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2562916.81 | 0.00 | 2562916.81 | 1827265.85 | 4390182.66 | 3225648.14 | 5618.68 | 2274.58 | 866.74 | 81.85 |
ZONE2 FINE STORAGE | 5376652.07 | 0.00 | 5376652.07 | 6606177.37 | 11982829.44 | 13393694.68 | 5722.95 | 2640.50 | 396.55 | 5.09 |
ZONE3 BULK STORAGE | 0.00 | 22340465.54 | 22340465.54 | 32169310.86 | 54509776.40 | 30805497.77 | 8223.38 | 55.50 | 481.12 | 4777.50 |
Total Facility | 7939568.88 | 22340465.54 | 30280034.42 | 40602754.08 | 70882788.50 | 47424840.58 | 8467.52 | 2815.08 | 1467.83 | 4790.55 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1856 | 0.0000 | 0.1856 | 0.0872 | 0.2728 | 0.1023 | 568.61 | 2274.42 | 792.97 |
ZONE2 FINE STORAGE | 0.4094 | 0.0000 | 0.4094 | 0.2003 | 0.6097 | 0.4247 | 603.92 | 2640.50 | 391.58 |
ZONE3 BULK STORAGE | 0.0000 | 0.9495 | 0.9495 | 1.2559 | 2.2054 | 0.9768 | 3328.04 | 27.67 | 280.29 |
Total Facility | 0.5950 | 0.9495 | 1.5445 | 1.5434 | 3.0879 | 1.5038 | 3343.54 | 2787.08 | 1188.64 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 3412632.85 | 0.00 | 3412632.85 | 3225648.14 | 5613.18 | 0.33 | 3146.49 | 81.85 |
PSZ-FINE STORAGE | 7159450.62 | 0.00 | 7159450.62 | 13393694.68 | 5722.53 | 0.17 | 3037.30 | 5.09 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2471 | 0.0000 | 0.2471 | 0.1023 | 563.95 | 0.33 | 3071.72 |
PSZ-FINE STORAGE | 0.5452 | 0.0000 | 0.5452 | 0.4247 | 603.58 | 0.17 | 3032.25 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2719.52 | 442.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2918.47 | 120.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2594 | 0.5008 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6411 | 0.9626 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 389 |
Defaulted Fields | 319 |
Fields with Defaults | 1046 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 703.77 | 4450.93 | 16-APR-10:50 | 57771.93 | 30-JUN-15:00 |
Electricity:Building | 535.19 | 3969.93 | 08-JAN-11:20 | 41393.46 | 28-JUL-14:10 |
Electricity:Zone:ZONE1 OFFICE | 51.22 | 776.36 | 01-JAN-13:50 | 3432.39 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 534.77 | 3969.93 | 08-JAN-11:20 | 40750.63 | 15-NOV-15:50 |
InteriorLights:Electricity | 397.70 | 3481.38 | 08-JAN-11:20 | 30696.62 | 15-NOV-15:50 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 21.50 | 287.82 | 01-JAN-13:50 | 1578.50 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 397.70 | 3481.38 | 08-JAN-11:20 | 30696.62 | 15-NOV-15:50 |
LightsWired:InteriorLights:Electricity | 397.70 | 3481.38 | 08-JAN-11:20 | 30696.62 | 15-NOV-15:50 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 21.50 | 287.82 | 01-JAN-13:50 | 1578.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 397.70 | 3481.38 | 08-JAN-11:20 | 30696.62 | 15-NOV-15:50 |
Electricity:Zone:ZONE2 FINE STORAGE | 162.28 | 1424.86 | 01-JAN-00:10 | 12111.30 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 162.28 | 1424.86 | 01-JAN-00:10 | 12111.30 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 162.28 | 1424.86 | 01-JAN-00:10 | 12111.30 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 321.69 | 1768.71 | 08-JAN-11:20 | 26197.04 | 28-JUL-14:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 213.93 | 1768.71 | 08-JAN-11:20 | 17006.82 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 213.93 | 1768.71 | 08-JAN-11:20 | 17006.82 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.72 | 488.55 | 01-JAN-00:10 | 1853.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.72 | 488.55 | 01-JAN-00:10 | 1853.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 137.06 | 488.55 | 01-JAN-00:10 | 10054.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 40.29 | 0.00 | 19-MAR-11:40 | 5040.92 | 29-JUN-16:00 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.42 | 0.00 | 01-JAN-00:10 | 2305.29 | 29-JUN-16:50 |
Ventilation (simple):Fans:Electricity | 0.42 | 0.00 | 01-JAN-00:10 | 2305.29 | 29-JUN-16:50 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.42 | 0.00 | 01-JAN-00:10 | 2305.29 | 29-JUN-16:50 |
ElectricityPurchased:Facility | 703.77 | 4450.93 | 02-JUL-12:20 | 57771.93 | 30-JUN-15:00 |
ElectricityPurchased:Plant | 703.77 | 4450.93 | 02-JUL-12:20 | 57771.93 | 30-JUN-15:00 |
Cogeneration:ElectricityPurchased | 703.77 | 4450.93 | 02-JUL-12:20 | 57771.93 | 30-JUN-15:00 |
General:Cogeneration:ElectricityPurchased | 703.77 | 4450.93 | 02-JUL-12:20 | 57771.93 | 30-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 703.77 | 4450.93 | 02-JUL-12:20 | 57771.93 | 30-JUN-15:00 |
ElectricityNet:Plant | 703.77 | 4450.93 | 02-JUL-12:20 | 57771.93 | 30-JUN-15:00 |
Cogeneration:ElectricityNet | 703.77 | 4450.93 | 02-JUL-12:20 | 57771.93 | 30-JUN-15:00 |
General:Cogeneration:ElectricityNet | 703.77 | 4450.93 | 02-JUL-12:20 | 57771.93 | 30-JUN-15:00 |
Electricity:HVAC | 48.39 | 0.00 | 19-MAR-11:40 | 16554.99 | 29-JUN-16:00 |
General:Fans:Electricity | 39.86 | 0.00 | 19-MAR-11:40 | 3739.21 | 04-JAN-08:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 8.53 | 0.00 | 01-JAN-00:10 | 13819.36 | 29-JUN-16:00 |
General:Cooling:Electricity | 8.53 | 0.00 | 01-JAN-00:10 | 13819.36 | 29-JUN-16:00 |
ExteriorLights:Electricity | 92.73 | 0.00 | 01-JAN-08:20 | 6986.42 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 92.73 | 0.00 | 01-JAN-08:20 | 6986.42 | 01-JAN-06:10 |
Electricity:Plant | 27.45 | 481.00 | 01-JAN-02:40 | 3104.89 | 24-FEB-12:20 |
WaterSystems:Electricity | 27.45 | 481.00 | 01-JAN-02:40 | 3104.89 | 24-FEB-12:20 |
Water Heater:WaterSystems:Electricity | 27.45 | 481.00 | 01-JAN-02:40 | 3104.89 | 24-FEB-12:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1673.19 | 0.00 | 19-MAR-11:40 | 383620.20 | 04-JAN-06:10 |
NaturalGas:HVAC | 1673.19 | 0.00 | 19-MAR-11:40 | 383620.20 | 04-JAN-06:10 |
Heating:NaturalGas | 1673.19 | 0.00 | 19-MAR-11:40 | 383620.20 | 04-JAN-06:10 |
General:Heating:NaturalGas | 1673.19 | 0.00 | 19-MAR-11:40 | 383620.20 | 04-JAN-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2625.52 | 0.00 | 19-MAR-11:40 | 611082.61 | 04-JAN-06:10 |
EnergyTransfer:Building | 1296.77 | 0.00 | 19-MAR-11:40 | 306538.13 | 04-JAN-06:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 80.08 | 0.00 | 01-JAN-00:40 | 29951.29 | 05-JAN-07:20 |
Heating:EnergyTransfer | 1246.36 | 0.00 | 19-MAR-11:40 | 306538.13 | 04-JAN-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 63.41 | 0.00 | 01-JAN-00:40 | 29951.29 | 05-JAN-07:20 |
General:Heating:EnergyTransfer | 1246.36 | 0.00 | 19-MAR-11:40 | 306538.13 | 04-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 63.41 | 0.00 | 01-JAN-00:40 | 29951.29 | 05-JAN-07:20 |
Cooling:EnergyTransfer | 50.41 | 0.00 | 01-JAN-00:10 | 31453.74 | 30-JUN-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 16.67 | 0.00 | 01-JAN-00:10 | 10146.07 | 05-SEP-17:20 |
General:Cooling:EnergyTransfer | 50.41 | 0.00 | 01-JAN-00:10 | 31453.74 | 30-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 16.67 | 0.00 | 01-JAN-00:10 | 10146.07 | 05-SEP-17:20 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 260.12 | 0.00 | 01-JAN-00:40 | 70368.90 | 04-JAN-06:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 226.38 | 0.00 | 01-JAN-00:40 | 70368.90 | 04-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 226.38 | 0.00 | 01-JAN-00:40 | 70368.90 | 04-JAN-06:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 33.75 | 0.00 | 01-JAN-00:10 | 23563.54 | 30-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 33.75 | 0.00 | 01-JAN-00:10 | 23563.54 | 30-JUN-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 956.58 | 0.00 | 17-JAN-13:00 | 211665.05 | 04-JAN-12:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 956.58 | 0.00 | 17-JAN-13:00 | 211665.05 | 04-JAN-12:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 956.58 | 0.00 | 17-JAN-13:00 | 211665.05 | 04-JAN-12:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1328.75 | 0.00 | 19-MAR-11:40 | 304544.49 | 04-JAN-06:10 |
HeatingCoils:EnergyTransfer | 1291.52 | 0.00 | 19-MAR-11:40 | 304544.49 | 04-JAN-06:10 |
CoolingCoils:EnergyTransfer | 37.23 | 0.00 | 01-JAN-00:10 | 54047.05 | 30-JUN-15:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 63.408 | -16.667 | 0.000 | 0.000 | 10.146 | 21.496 | 29.720 | 11.427 | 0.000 | 0.347 | 0.000 | 0.000 | -13.534 | 0.000 | -37.805 | -68.537 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 226.375 | -33.745 | 0.000 | 0.000 | 26.593 | 162.279 | 0.000 | 0.000 | 0.000 | 0.439 | 0.001 | 0.000 | 0.000 | 0.000 | -122.259 | -259.682 |
ZONE3 BULK STORAGE | 956.575 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 68.031 | 213.929 | 107.344 | 97.981 | 0.000 | 6.635 | 0.000 | 0.000 | -211.617 | 0.000 | -678.570 | -560.308 |
Total Facility | 956.575 | 0.000 | 289.783 | -50.412 | 0.000 | 0.000 | 104.770 | 397.704 | 137.063 | 109.408 | 0.000 | 7.421 | 0.002 | 0.000 | -225.151 | 0.000 | -838.634 | -888.527 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 05-SEP-17:15 | 0.00 | 0.00 | 0.00 | -20290.97 | 0.00 | 0.00 | 0.00 | 287.82 | 488.55 | 3389.27 | 0.00 | 0.00 | 16544.83 | 0.00 | -0.00 | 0.00 | -419.49 | 0.00 |
ZONE2 FINE STORAGE | 07-JUL-17:29 | 0.00 | 0.00 | 0.00 | -47791.34 | 0.00 | 0.00 | 0.00 | 1424.86 | 0.00 | 0.00 | 0.00 | 0.00 | 48339.11 | 0.00 | -0.00 | 0.00 | -1972.63 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JUL-17:08 | 0.00 | 0.00 | 0.00 | -53997.13 | 0.00 | 0.00 | 0.00 | 3636.11 | 2538.58 | 25424.52 | 0.00 | 767.56 | 49568.80 | 0.00 | 0.00 | 0.00 | -27938.44 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 04-JAN-06:31 | 0.00 | 0.00 | 32422.43 | 0.00 | 0.00 | 0.00 | 148.99 | 471.50 | 556.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1608.70 | 0.00 | -4827.37 | -27163.02 |
ZONE2 FINE STORAGE | 04-JAN-06:01 | 0.00 | 0.00 | 92753.30 | 0.00 | 0.00 | 0.00 | 395.68 | 1424.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -22022.37 | -72551.47 |
ZONE3 BULK STORAGE | 04-JAN-12:00 | 211664.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8359.03 | 16349.22 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11100.85 | 0.00 | -199359.15 | -34112.88 |
Total Facility | 04-JAN-06:01 | 211347.06 | 0.00 | 122468.73 | 0.00 | 0.00 | 0.00 | 1462.88 | 3897.16 | 2606.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -24921.05 | 0.00 | -158167.33 | -158693.64 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0436 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0436 | 0.0980 | 1.0000 | Not calculated | 0.1023 | 0.0980 | ||
PSZ-FINE STORAGE | 2.2218 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.2218 | 0.1912 | 1.0000 | Not calculated | 0.4247 | 0.1912 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0436 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0436 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0980 | ||
PSZ-FINE STORAGE | 2.2218 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.2218 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1912 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0436 | 1.0436 | 1.0436 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2218 | 2.2218 | 2.2218 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0436 | 1.0436 | 1.0436 | 1.0436 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.2218 | 2.2218 | 2.2218 | 2.2218 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0436 | 1.0436 | 1.0436 | No | 0.1023 | 0.2277 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2218 | 2.2218 | 2.2218 | No | 0.4247 | 0.2973 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0436 | 1.0436 | 1.0436 | 1.0436 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.2218 | 2.2218 | 2.2218 | 2.2218 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 81.67 |
Number of hours cooling loads not met | 1.83 |
Number of hours not met | 83.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1673.19 | 383620.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 8.53 | 13819.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 397.70 | 30696.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 92.73 | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 137.06 | 10054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.42 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 39.86 | 3739.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 27.45 | 3104.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 137.06 | 703.77 |
Natural Gas | 0.00 | 1673.19 |
Additional | 0.00 | 0.00 |
Total | 137.06 | 2376.96 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 82.25 |
Space Heating | 0.00 |
Space Cooling | 1.76 |
Fans (All) | 8.33 |
Service Water Heating | 5.68 |
Receptacle Equipment | 28.35 |
Miscellaneous (All) | 145.55 |
Subtotal | 145.55 |
Natural Gas [MJ/m2] | |
Space Heating | 346.05 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 346.05 |
Subtotal | 346.05 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 16.73 |
Space Heating | 70.39 |
Space Cooling | 0.36 |
Fans (All) | 1.69 |
Service Water Heating | 1.16 |
Receptacle Equipment | 5.77 |
Miscellaneous | 3.90 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2970. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4378. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 23.90 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8697.50 | 62.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8220.17 | 539.83 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8102.17 | 640.00 | 17.83 | 0.00 | 0.00 |
Min | 8102.17 | 62.50 | 0.00 | 0.00 | 0.00 |
Max | 8697.50 | 640.00 | 17.83 | 0.00 | 0.00 |
Average | 8339.94 | 414.11 | 5.94 | 0.00 | 0.00 |
Sum | 25019.83 | 1242.33 | 17.83 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 72245.00 | 10474.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 168748.00 | 21533.33 | 911.67 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 168748.00 | 21533.33 | 911.67 | 0.00 | 0.00 |
Average | 91340.00 | 10669.11 | 303.89 | 0.00 | 0.00 |
Sum | 274020.00 | 32007.33 | 911.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8494.00 | 266.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7675.33 | 1084.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7627.67 | 1121.17 | 11.17 | 0.00 | 0.00 |
Min | 7627.67 | 266.00 | 0.00 | 0.00 | 0.00 |
Max | 8494.00 | 1121.17 | 11.17 | 0.00 | 0.00 |
Average | 7932.33 | 823.94 | 3.72 | 0.00 | 0.00 |
Sum | 23797.00 | 2471.83 | 11.17 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 31983.50 | 1043.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 68427.50 | 14291.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 159774.33 | 30796.83 | 621.83 | 0.00 | 0.00 |
Min | 31983.50 | 1043.50 | 0.00 | 0.00 | 0.00 |
Max | 159774.33 | 30796.83 | 621.83 | 0.00 | 0.00 |
Average | 86728.44 | 15377.28 | 207.28 | 0.00 | 0.00 |
Sum | 260185.33 | 46131.83 | 621.83 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:41:44
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 2920.00 | 0.00 |
Sum | 0.00 | 8760.00 | 8760.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 33027.00 | 0.00 |
Average | 0.00 | 63731.00 | 11009.00 | 0.00 |
Sum | 0.00 | 191193.00 | 33027.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 | -22.1 | 0.496807E+09 | 603.25 | 14-JAN-08:09 | -19.9 | -20.3 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -23.1 | -23.5 | 0.457136E+09 | 603.25 | 25-FEB-08:09 | -28.1 | -28.4 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.3 | -3.3 | 0.536674E+09 | 603.25 | 17-MAR-07:10 | -11.0 | -11.6 |
April | 4237234.43 | 364.45 | 24-APR-14:10 | 8.40 | 4.64 | 0.504801E+09 | 763.89 | 13-APR-15:00 | 8.40 | 4.64 |
May | 0.117082E+10 | 17218.97 | 18-MAY-19:21 | 22.80 | 14.72 | 0.605743E+09 | 769.02 | 26-MAY-13:30 | 22.50 | 17.44 |
June | 0.333572E+10 | 18729.56 | 08-JUN-19:21 | 20.80 | 13.46 | 0.653681E+09 | 769.02 | 23-JUN-14:50 | 23.12 | 20.51 |
July | 0.552993E+10 | 20147.26 | 16-JUL-23:02 | 12.88 | 11.57 | 0.634664E+09 | 769.02 | 25-JUL-14:00 | 21.10 | 19.55 |
August | 0.491668E+10 | 19723.22 | 13-AUG-23:02 | 15.50 | 12.59 | 0.684602E+09 | 769.02 | 07-AUG-14:39 | 15.50 | 12.59 |
September | 0.160335E+10 | 20292.13 | 05-SEP-17:15 | 16.33 | 9.57 | 0.602931E+09 | 769.02 | 01-SEP-09:50 | 16.33 | 9.57 |
October | 0.106661E+09 | 1355.19 | 21-OCT-15:00 | 20.00 | 11.16 | 0.515378E+09 | 768.96 | 19-OCT-15:00 | 20.00 | 11.16 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.51 | 0.478065E+09 | 680.45 | 01-NOV-15:00 | 17.80 | 13.26 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -8.8 | -9.9 | 0.496859E+09 | 603.25 | 16-DEC-08:09 | -14.0 | -14.5 |
Annual Sum or Average | 0.166674E+11 | 0.666734E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.5 | 0.457136E+09 | 603.25 | -28.1 | -28.4 | ||
Maximum of Months | 0.552993E+10 | 20292.13 | 22.80 | 14.72 | 0.684602E+09 | 769.02 | 23.12 | 20.51 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 32734954.99 | 2150.33 | 17-JAN-13:10 | -3.6 | -4.9 | 0.648915E+09 | 787.42 | 24-JAN-11:00 | -13.3 | -13.8 |
February | 0.508741E+09 | 5936.43 | 22-FEB-14:00 | -0.6 | -3.9 | 0.598803E+09 | 872.31 | 08-FEB-14:30 | -0.6 | -3.9 |
March | 0.143940E+10 | 9464.52 | 02-MAR-11:45 | -6.8 | -8.1 | 0.709597E+09 | 1025.26 | 31-MAR-15:09 | 8.40 | 2.82 |
April | 0.225520E+10 | 6332.39 | 27-APR-13:00 | 1.10 | -2.1 | 0.775284E+09 | 1483.69 | 13-APR-15:09 | 1.10 | -2.1 |
May | 0.245461E+10 | 8402.57 | 25-MAY-15:00 | 28.90 | 19.67 | 0.134325E+10 | 2246.85 | 18-MAY-14:30 | 28.90 | 19.67 |
June | 0.463177E+10 | 37793.85 | 30-JUN-17:08 | 30.92 | 21.22 | 0.171321E+10 | 2246.97 | 30-JUN-10:50 | 30.92 | 21.22 |
July | 0.861413E+10 | 47791.97 | 07-JUL-17:29 | 21.40 | 13.39 | 0.182030E+10 | 2246.95 | 13-JUL-14:00 | 26.10 | 20.34 |
August | 0.597295E+10 | 32241.98 | 13-AUG-14:05 | 23.22 | 14.47 | 0.189551E+10 | 2246.95 | 11-AUG-14:39 | 23.22 | 14.47 |
September | 0.335974E+10 | 28302.45 | 01-SEP-17:32 | 24.07 | 17.86 | 0.135316E+10 | 2246.94 | 01-SEP-14:30 | 24.07 | 17.86 |
October | 0.303059E+10 | 8160.69 | 25-OCT-07:05 | -3.2 | -3.4 | 0.817728E+09 | 1601.64 | 21-OCT-14:00 | -3.2 | -3.4 |
November | 0.140547E+10 | 5906.92 | 03-NOV-12:20 | 1.70 | -1.4 | 0.647994E+09 | 1206.11 | 01-NOV-15:09 | 1.70 | -1.4 |
December | 40322174.27 | 9341.82 | 06-DEC-13:45 | -6.5 | -6.6 | 0.649002E+09 | 787.42 | 09-DEC-11:00 | -14.4 | -15.2 |
Annual Sum or Average | 0.337457E+11 | 0.129728E+11 | ||||||||
Minimum of Months | 32734954.99 | 2150.33 | -6.8 | -8.1 | 0.598803E+09 | 787.42 | -14.4 | -15.2 | ||
Maximum of Months | 0.861413E+10 | 47791.97 | 30.92 | 21.22 | 0.189551E+10 | 2246.97 | 30.92 | 21.22 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 | -22.1 | 0.643992E+09 | 799.25 | 27-JAN-14:20 | -14.4 | -15.6 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -23.1 | -23.5 | 0.600309E+09 | 982.14 | 08-FEB-14:39 | 5.00 | -0.5 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.3 | -3.3 | 0.734130E+09 | 1219.59 | 31-MAR-15:09 | 8.40 | 2.82 |
April | 0.00 | 0.00 | 01-APR-00:03 | 3.52 | 0.38 | 0.965765E+09 | 2126.75 | 18-APR-14:09 | 17.33 | 10.22 |
May | 0.00 | 0.00 | 01-MAY-00:03 | -0.0 | -1.4 | 0.233907E+10 | 4819.66 | 25-MAY-15:30 | 29.00 | 19.65 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 | 0.369012E+10 | 8096.01 | 29-JUN-15:00 | 35.00 | 24.72 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 | 13.57 | 0.463277E+10 | 6815.56 | 15-JUL-14:50 | 31.10 | 24.71 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 | 0.428856E+10 | 6136.62 | 08-AUG-15:39 | 30.60 | 23.11 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 | 0.263265E+10 | 5921.45 | 01-SEP-15:50 | 26.10 | 17.67 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 | 0.112200E+10 | 2363.57 | 02-OCT-13:39 | 10.37 | 9.55 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.51 | 0.676084E+09 | 1526.14 | 01-NOV-14:39 | 18.13 | 13.38 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -8.8 | -9.9 | 0.644013E+09 | 780.60 | 02-DEC-16:30 | -19.1 | -19.7 |
Annual Sum or Average | 0.00 | 0.229695E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.5 | 0.600309E+09 | 780.60 | -19.1 | -19.7 | ||
Maximum of Months | 0.00 | 0.00 | 19.75 | 18.15 | 0.463277E+10 | 8096.01 | 35.00 | 24.72 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143493E+11 | 32422.32 | 04-JAN-06:31 | -29.2 |
February | 0.110941E+11 | 30164.76 | 13-FEB-06:11 | -24.1 |
March | 0.988430E+10 | 30131.39 | 06-MAR-06:11 | -19.1 |
April | 0.503196E+10 | 29799.98 | 03-APR-05:22 | -4.2 |
May | 0.961070E+09 | 29690.01 | 01-MAY-05:12 | -3.5 |
June | 88271556.02 | 15581.87 | 01-JUN-05:03 | 14.08 |
July | 25849049.76 | 1373.00 | 17-JUL-06:10 | 13.07 |
August | 59921890.69 | 1384.94 | 28-AUG-06:10 | 14.08 |
September | 0.306316E+09 | 29283.00 | 28-SEP-05:01 | 6.70 |
October | 0.255706E+10 | 29604.66 | 30-OCT-05:01 | -9.9 |
November | 0.638779E+10 | 29786.82 | 13-NOV-06:12 | -8.5 |
December | 0.126621E+11 | 30301.80 | 19-DEC-07:13 | -25.8 |
Annual Sum or Average | 0.634081E+11 | |||
Minimum of Months | 25849049.76 | 1373.00 | -29.2 | |
Maximum of Months | 0.143493E+11 | 32422.32 | 14.08 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.569584E+11 | 92753.27 | 04-JAN-06:01 | -29.0 |
February | 0.417666E+11 | 90440.45 | 25-FEB-02:61 | -25.8 |
March | 0.308534E+11 | 89514.71 | 07-MAR-00:42 | -23.8 |
April | 0.125087E+11 | 88387.55 | 04-APR-23:42 | -10.5 |
May | 0.641289E+09 | 61264.16 | 01-MAY-04:13 | -3.0 |
June | 60604831.36 | 1004.52 | 09-JUN-07:00 | 11.70 |
July | 53572347.70 | 860.55 | 29-JUL-06:13 | 20.33 |
August | 65390864.71 | 987.21 | 31-AUG-07:00 | 17.20 |
September | 62836405.89 | 965.60 | 23-SEP-07:00 | 3.90 |
October | 0.559241E+10 | 86977.40 | 30-OCT-05:33 | -9.6 |
November | 0.242345E+11 | 89433.68 | 28-NOV-22:02 | -13.9 |
December | 0.535779E+11 | 90443.79 | 21-DEC-02:41 | -26.0 |
Annual Sum or Average | 0.226376E+12 | |||
Minimum of Months | 53572347.70 | 860.55 | -29.0 | |
Maximum of Months | 0.569584E+11 | 92753.27 | 20.33 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.265075E+12 | 211665.05 | 04-JAN-12:00 | -28.3 |
February | 0.188503E+12 | 211151.42 | 12-FEB-23:00 | -17.2 |
March | 0.123645E+12 | 154227.96 | 15-MAR-05:00 | -22.2 |
April | 0.308032E+11 | 86950.03 | 04-APR-18:54 | -7.2 |
May | 0.395735E+09 | 22771.13 | 01-MAY-04:00 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.608737E+10 | 44262.17 | 31-OCT-20:55 | -2.2 |
November | 0.951514E+11 | 125921.31 | 25-NOV-02:00 | -15.6 |
December | 0.246916E+12 | 209402.98 | 18-DEC-15:00 | -22.8 |
Annual Sum or Average | 0.956576E+12 | |||
Minimum of Months | 0.00 | 0.00 | -28.3 | |
Maximum of Months | 0.265075E+12 | 211665.05 | 19.75 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187915E+10 | 1578.50 | 02-JAN-08:09 | 0.248944E+10 | 1853.89 | 02-JAN-08:09 |
February | 0.166325E+10 | 1578.50 | 02-FEB-16:00 | 0.226834E+10 | 1853.89 | 01-FEB-08:09 |
March | 0.187396E+10 | 1578.50 | 13-MAR-07:10 | 0.258391E+10 | 1853.89 | 01-MAR-08:09 |
April | 0.174404E+10 | 1578.50 | 01-APR-07:10 | 0.244723E+10 | 1853.89 | 01-APR-07:10 |
May | 0.176846E+10 | 1346.99 | 01-MAY-07:10 | 0.253668E+10 | 1853.89 | 01-MAY-07:10 |
June | 0.173354E+10 | 1404.87 | 09-JUN-07:10 | 0.249447E+10 | 1853.89 | 01-JUN-07:10 |
July | 0.172781E+10 | 1404.87 | 08-JUL-07:10 | 0.248944E+10 | 1853.89 | 01-JUL-07:10 |
August | 0.182448E+10 | 1520.62 | 28-AUG-07:10 | 0.258391E+10 | 1853.89 | 01-AUG-07:10 |
September | 0.175380E+10 | 1520.62 | 16-SEP-07:10 | 0.244723E+10 | 1853.89 | 01-SEP-07:10 |
October | 0.182133E+10 | 1578.50 | 23-OCT-07:10 | 0.248944E+10 | 1853.89 | 02-OCT-07:10 |
November | 0.180527E+10 | 1578.50 | 01-NOV-07:10 | 0.239999E+10 | 1853.89 | 01-NOV-07:10 |
December | 0.190071E+10 | 1578.50 | 01-DEC-08:09 | 0.248944E+10 | 1853.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.214958E+11 | 0.297195E+11 | ||||
Minimum of Months | 0.166325E+10 | 1346.99 | 0.226834E+10 | 1853.89 | ||
Maximum of Months | 0.190071E+10 | 1578.50 | 0.258391E+10 | 1853.89 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.134983E+11 | 12111.30 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.123544E+11 | 12111.30 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.142728E+11 | 12111.30 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.133752E+11 | 12111.30 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.138855E+11 | 12111.30 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.137624E+11 | 12111.30 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.134983E+11 | 12111.30 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.142728E+11 | 12111.30 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.133752E+11 | 12111.30 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.134983E+11 | 12111.30 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.129879E+11 | 12111.30 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.134983E+11 | 12111.30 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.162279E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.123544E+11 | 12111.30 | 0.00 | 0.00 | |
Maximum of Months | 0.142728E+11 | 12111.30 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.184420E+11 | 17006.82 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.166105E+11 | 17006.82 | 01-FEB-10:20 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.188911E+11 | 17006.82 | 06-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.174752E+11 | 16349.22 | 04-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.177493E+11 | 16349.22 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.175398E+11 | 15691.63 | 09-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.172308E+11 | 15691.63 | 03-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.183534E+11 | 16349.22 | 03-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.175134E+11 | 17006.82 | 09-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.179864E+11 | 17006.82 | 17-OCT-13:50 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.176591E+11 | 17006.82 | 02-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.184781E+11 | 17006.82 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.213929E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.166105E+11 | 15691.63 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.188911E+11 | 17006.82 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.187915E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686126E+10 |
February | 0.127628E+10 | 0.166325E+10 | 0.226834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549771E+10 |
March | 0.149825E+10 | 0.187396E+10 | 0.258391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450103E+10 |
April | 0.138726E+10 | 0.174404E+10 | 0.244723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12067147.05 | 0.290313E+10 |
May | 0.144276E+10 | 0.176846E+10 | 0.253668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44272756.14 | 0.134563E+10 |
June | 0.144276E+10 | 0.173354E+10 | 0.249447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119214E+09 | 0.771572E+09 |
July | 0.138726E+10 | 0.172781E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112379E+09 | 0.571807E+09 |
August | 0.149825E+10 | 0.182448E+10 | 0.258391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56340223.30 | 0.918789E+09 |
September | 0.138726E+10 | 0.175380E+10 | 0.244723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2347363.28 | 0.161889E+10 |
October | 0.138726E+10 | 0.182133E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239062E+10 |
November | 0.133177E+10 | 0.180527E+10 | 0.239999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394056E+10 |
December | 0.138726E+10 | 0.190071E+10 | 0.248944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648380E+10 |
Annual Sum or Average | 0.168137E+11 | 0.214958E+11 | 0.297195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346621E+09 | 0.378048E+11 |
Minimum of Months | 0.127628E+10 | 0.166325E+10 | 0.226834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571807E+09 |
Maximum of Months | 0.149825E+10 | 0.190071E+10 | 0.258391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119214E+09 | 0.686126E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.134983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217014E+11 |
February | 0.300332E+10 | 0.123544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180864E+11 |
March | 0.352563E+10 | 0.142728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127912E+11 |
April | 0.326447E+10 | 0.133752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83177498.54 | 0.915003E+10 |
May | 0.339505E+10 | 0.138855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54001802.20 | 0.419986E+10 |
June | 0.339505E+10 | 0.137624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152901E+09 | 0.306323E+10 |
July | 0.326447E+10 | 0.134983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117761E+09 | 0.275622E+10 |
August | 0.352563E+10 | 0.142728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30512825.94 | 0.379269E+10 |
September | 0.326447E+10 | 0.133752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148951.89 | 0.530055E+10 |
October | 0.326447E+10 | 0.134983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268555.45 | 0.637664E+10 |
November | 0.313390E+10 | 0.129879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130246E+11 |
December | 0.326447E+10 | 0.134983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220163E+11 |
Annual Sum or Average | 0.395654E+11 | 0.162279E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438771E+09 | 0.122259E+12 |
Minimum of Months | 0.300332E+10 | 0.123544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275622E+10 |
Maximum of Months | 0.352563E+10 | 0.142728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152901E+09 | 0.220163E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.184420E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.855569E+11 |
February | 0.690763E+10 | 0.166105E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689993E+11 |
March | 0.810895E+10 | 0.188911E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462860E+11 |
April | 0.750829E+10 | 0.174752E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108529E+10 | 0.268994E+11 |
May | 0.780862E+10 | 0.177493E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159754E+10 | 0.135813E+11 |
June | 0.780862E+10 | 0.175398E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173679E+09 | 0.115530E+11 |
July | 0.750829E+10 | 0.172308E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13411979.23 | 0.151787E+11 |
August | 0.810895E+10 | 0.183534E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51019783.65 | 0.174888E+11 |
September | 0.750829E+10 | 0.175134E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57197358.06 | 0.208187E+11 |
October | 0.750829E+10 | 0.179864E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449807E+09 | 0.187056E+11 |
November | 0.720796E+10 | 0.176591E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212056E+09 | 0.419943E+11 |
December | 0.750829E+10 | 0.184781E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.834906E+11 |
Annual Sum or Average | 0.910005E+11 | 0.213929E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364000E+10 | 0.450553E+12 |
Minimum of Months | 0.690763E+10 | 0.166105E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115530E+11 |
Maximum of Months | 0.810895E+10 | 0.188911E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159754E+10 | 0.855569E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1578.50 | 02-JAN-08:09 | 1853.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 17409.89 | 04-JAN-08:00 |
February | 1680.92 | 01-FEB-08:09 | 1578.50 | 02-FEB-16:00 | 1853.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 15715.72 | 14-FEB-08:00 |
March | 1680.92 | 01-MAR-08:09 | 1578.50 | 13-MAR-07:10 | 1853.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 13686.34 | 15-MAR-06:10 |
April | 1680.92 | 01-APR-07:10 | 1578.50 | 01-APR-07:10 | 1853.89 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 641.77 | 23-APR-16:00 | 9161.23 | 04-APR-17:00 |
May | 1680.92 | 01-MAY-07:10 | 1346.99 | 01-MAY-07:10 | 1853.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.59 | 25-MAY-16:10 | 5581.39 | 01-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 1404.87 | 09-JUN-07:10 | 1853.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3066.29 | 29-JUN-16:10 | 3116.06 | 02-JUN-07:00 |
July | 1680.92 | 01-JUL-07:10 | 1404.87 | 08-JUL-07:10 | 1853.89 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1460.01 | 28-JUL-16:10 | 2924.01 | 27-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 1520.62 | 28-AUG-07:10 | 1853.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.99 | 08-AUG-16:10 | 4065.85 | 17-AUG-16:05 |
September | 1680.92 | 01-SEP-07:10 | 1520.62 | 16-SEP-07:10 | 1853.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 468.22 | 01-SEP-16:10 | 4919.72 | 20-SEP-06:10 |
October | 1680.92 | 02-OCT-07:10 | 1578.50 | 23-OCT-07:10 | 1853.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 8539.59 | 30-OCT-07:00 |
November | 1680.92 | 01-NOV-07:10 | 1578.50 | 01-NOV-07:10 | 1853.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 10918.22 | 29-NOV-07:40 |
December | 1680.92 | 01-DEC-08:09 | 1578.50 | 01-DEC-08:09 | 1853.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 16593.06 | 18-DEC-17:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1346.99 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2924.01 | |||||
Maximum of Months | 1680.92 | 1578.50 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 3066.29 | 17409.89 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 12111.30 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 26759.88 | 04-JAN-16:10 |
February | 3955.50 | 01-FEB-08:09 | 12111.30 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 32644.03 | 12-FEB-23:00 |
March | 3955.50 | 01-MAR-08:09 | 12111.30 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 19931.53 | 14-MAR-15:10 |
April | 3955.50 | 01-APR-07:10 | 12111.30 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4143.49 | 23-APR-16:00 | 16287.34 | 26-APR-15:10 |
May | 3955.50 | 01-MAY-07:10 | 12111.30 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1658.82 | 10-MAY-18:00 | 7954.45 | 20-MAY-06:10 |
June | 3955.50 | 01-JUN-07:10 | 12111.30 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4467.65 | 29-JUN-16:00 | 7584.83 | 09-JUN-08:00 |
July | 3955.50 | 01-JUL-07:10 | 12111.30 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3054.14 | 15-JUL-15:10 | 5378.11 | 08-JUL-15:10 |
August | 3955.50 | 01-AUG-07:10 | 12111.30 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2305.40 | 08-AUG-16:00 | 10101.76 | 17-AUG-15:05 |
September | 3955.50 | 01-SEP-07:10 | 12111.30 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.73 | 24-SEP-15:00 | 8227.55 | 20-SEP-06:10 |
October | 3955.50 | 02-OCT-07:10 | 12111.30 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.88 | 19-OCT-15:10 | 10713.64 | 31-OCT-17:00 |
November | 3955.50 | 01-NOV-07:10 | 12111.30 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 15882.26 | 22-NOV-01:45 |
December | 3955.50 | 01-DEC-08:09 | 12111.30 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 32861.77 | 18-DEC-16:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 12111.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5378.11 | ||||
Maximum of Months | 3955.50 | 12111.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4467.65 | 32861.77 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 17006.82 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 140704.68 | 04-JAN-12:00 |
February | 9097.65 | 01-FEB-08:09 | 17006.82 | 01-FEB-10:20 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 106680.44 | 12-FEB-22:55 |
March | 9097.65 | 01-MAR-08:09 | 17006.82 | 06-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 64402.46 | 14-MAR-16:00 |
April | 9097.65 | 01-APR-07:10 | 16349.22 | 04-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24762.93 | 23-APR-16:00 | 44783.12 | 26-APR-15:00 |
May | 9097.65 | 01-MAY-07:10 | 16349.22 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14620.41 | 10-MAY-15:00 | 24781.06 | 20-MAY-07:10 |
June | 9097.65 | 01-JUN-07:10 | 15691.63 | 09-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4361.23 | 06-JUN-12:10 | 32373.87 | 09-JUN-09:00 |
July | 9097.65 | 01-JUL-07:10 | 15691.63 | 03-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4004.50 | 15-JUL-14:00 | 40690.70 | 03-JUL-10:55 |
August | 9097.65 | 01-AUG-07:10 | 16349.22 | 03-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3535.12 | 08-AUG-16:00 | 45692.20 | 17-AUG-14:00 |
September | 9097.65 | 01-SEP-07:10 | 17006.82 | 09-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3887.86 | 24-SEP-15:00 | 25470.39 | 20-SEP-07:10 |
October | 9097.65 | 02-OCT-07:10 | 17006.82 | 17-OCT-13:50 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13180.72 | 19-OCT-15:00 | 30113.25 | 05-OCT-08:00 |
November | 9097.65 | 01-NOV-07:10 | 17006.82 | 02-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7129.94 | 01-NOV-14:00 | 54213.26 | 25-NOV-11:00 |
December | 9097.65 | 01-DEC-08:09 | 17006.82 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 125335.92 | 18-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 15691.63 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24781.06 | |||||
Maximum of Months | 9097.65 | 17006.82 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 24762.93 | 140704.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 2951.96 | 3908.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1571.81 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 2582.96 | 3419.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2502.08 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 1475.98 | 1954.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 824.16 |
April | 364.45 | 24-APR-14:10 | 1680.92 | 1231.23 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 596.24 |
May | 17218.97 | 18-MAY-19:21 | 0.00 | 3554.65 | 4885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.71 |
June | 18729.56 | 08-JUN-19:21 | 0.00 | 3689.95 | 4885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.80 |
July | 20147.26 | 16-JUL-23:02 | 0.00 | 1844.97 | 2442.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.30 |
August | 19723.22 | 13-AUG-23:02 | 0.00 | 1844.97 | 2442.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.35 |
September | 20292.13 | 05-SEP-17:15 | 0.00 | 575.63 | 977.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.49 |
October | 1355.19 | 21-OCT-15:00 | 1680.92 | 1231.23 | 1853.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.04 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 368.99 | 488.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 738.71 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 1844.97 | 2442.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1406.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 368.99 | 488.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.71 | |
Maximum of Months | 20292.13 | 1680.92 | 3689.95 | 4885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2502.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2150.33 | 17-JAN-13:10 | 3955.50 | 12111.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.12 |
February | 5936.43 | 22-FEB-14:00 | 3955.50 | 12111.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2712.41 |
March | 9464.52 | 02-MAR-11:45 | 7911.00 | 24222.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3373.69 |
April | 6332.39 | 27-APR-13:00 | 3955.50 | 12111.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1659.77 |
May | 8402.57 | 25-MAY-15:00 | 3955.50 | 12111.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.32 | 0.00 |
June | 37793.85 | 30-JUN-17:08 | 0.00 | 5699.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1564.98 | 0.00 |
July | 47791.97 | 07-JUL-17:29 | 0.00 | 12823.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1972.63 |
August | 32241.98 | 13-AUG-14:05 | 0.00 | 2849.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 994.05 |
September | 28302.45 | 01-SEP-17:32 | 0.00 | 8549.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.33 |
October | 8160.69 | 25-OCT-07:05 | 7911.00 | 21372.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5906.92 | 03-NOV-12:20 | 3955.50 | 12111.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2071.12 |
December | 9341.82 | 06-DEC-13:45 | 7911.00 | 24222.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2699.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2150.33 | 0.00 | 2849.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 47791.97 | 7911.00 | 24222.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1564.98 | 3373.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 16006.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31820.97 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 14005.62 | 14350.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50712.47 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 8003.21 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13440.37 |
April | 0.00 | 01-APR-00:03 | 0.00 | 6002.41 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9400.43 |
May | 0.00 | 01-MAY-00:03 | 0.00 | 6002.41 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2178.13 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7190.37 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4841.91 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7428.85 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4459.05 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2000.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5151.48 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2000.80 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9393.34 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 10004.01 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26286.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 2000.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2178.13 | |
Maximum of Months | 0.00 | 0.00 | 16006.42 | 14350.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50712.47 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.633407E+11 | 49723.08 | 04-JAN-08:09 | 0.450415E+12 | 383620.20 | 04-JAN-06:10 |
February | 0.561983E+11 | 46108.20 | 13-FEB-15:00 | 0.323195E+12 | 361562.35 | 12-FEB-22:49 |
March | 0.622178E+11 | 45472.73 | 15-MAR-08:09 | 0.223009E+12 | 277430.81 | 15-MAR-05:10 |
April | 0.557681E+11 | 44990.26 | 04-APR-14:00 | 0.658042E+11 | 153593.27 | 04-APR-05:10 |
May | 0.557603E+11 | 48349.85 | 25-MAY-14:00 | 0.239223E+10 | 63108.32 | 01-MAY-05:10 |
June | 0.563496E+11 | 57771.93 | 30-JUN-14:00 | 21164389.67 | 5371.89 | 01-JUN-05:10 |
July | 0.576762E+11 | 55430.18 | 15-JUL-14:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.596303E+11 | 51511.47 | 08-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.556854E+11 | 49473.19 | 01-SEP-13:39 | 0.310560E+09 | 9523.11 | 29-SEP-05:10 |
October | 0.583222E+11 | 45081.45 | 30-OCT-08:20 | 0.204808E+11 | 99861.45 | 30-OCT-05:40 |
November | 0.592566E+11 | 49011.95 | 25-NOV-16:19 | 0.168655E+12 | 222924.81 | 25-NOV-06:10 |
December | 0.635669E+11 | 49386.50 | 18-DEC-16:30 | 0.418910E+12 | 361201.97 | 18-DEC-16:19 |
Annual Sum or Average | 0.703772E+12 | 0.167319E+13 | ||||
Minimum of Months | 0.556854E+11 | 44990.26 | 0.00 | 0.00 | ||
Maximum of Months | 0.635669E+11 | 57771.93 | 0.450415E+12 | 383620.20 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.338194E+11 | 0.105556E+11 | 0.113456E+11 | 0.00 | 0.522406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239612E+10 | 0.00 |
February | 0.306282E+11 | 0.855089E+10 | 0.104160E+11 | 0.00 | 0.440120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220202E+10 | 0.00 |
March | 0.350379E+11 | 0.813270E+10 | 0.121559E+11 | 0.00 | 0.439953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249172E+10 | 0.00 |
April | 0.325944E+11 | 0.652828E+10 | 0.113034E+11 | 0.00 | 0.300624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233583E+10 | 0.00 |
May | 0.334033E+11 | 0.564146E+10 | 0.117471E+11 | 0.00 | 0.222920E+10 | 0.00 | 0.00 | 0.377931E+09 | 0.00 | 0.00 | 0.00 | 0.236137E+10 | 0.00 |
June | 0.330358E+11 | 0.489484E+10 | 0.117048E+11 | 0.00 | 0.246779E+10 | 0.00 | 0.00 | 0.199516E+10 | 0.00 | 0.00 | 0.00 | 0.225116E+10 | 0.00 |
July | 0.324569E+11 | 0.529224E+10 | 0.113456E+11 | 0.00 | 0.255673E+10 | 0.00 | 0.00 | 0.380989E+10 | 0.00 | 0.00 | 0.00 | 0.221491E+10 | 0.00 |
August | 0.344507E+11 | 0.621231E+10 | 0.121485E+11 | 0.00 | 0.242348E+10 | 0.00 | 0.00 | 0.214344E+10 | 0.00 | 0.00 | 0.00 | 0.225181E+10 | 0.00 |
September | 0.326423E+11 | 0.728282E+10 | 0.112960E+11 | 0.00 | 0.210796E+10 | 0.00 | 0.00 | 0.203991E+09 | 0.00 | 0.00 | 0.00 | 0.215233E+10 | 0.00 |
October | 0.333060E+11 | 0.891657E+10 | 0.113530E+11 | 0.00 | 0.250833E+10 | 0.00 | 0.00 | 91075.45 | 0.00 | 0.00 | 0.00 | 0.223825E+10 | 0.00 |
November | 0.324522E+11 | 0.984823E+10 | 0.109019E+11 | 0.00 | 0.384314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221118E+10 | 0.00 |
December | 0.338771E+11 | 0.108784E+11 | 0.113456E+11 | 0.00 | 0.511776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234813E+10 | 0.00 |
Annual Sum or Average | 0.397704E+12 | 0.927343E+11 | 0.137063E+12 | 0.00 | 0.402854E+11 | 0.00 | 0.00 | 0.853051E+10 | 0.00 | 0.00 | 0.00 | 0.274548E+11 | 0.00 |
Minimum of Months | 0.306282E+11 | 0.489484E+10 | 0.104160E+11 | 0.00 | 0.210796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215233E+10 | 0.00 |
Maximum of Months | 0.350379E+11 | 0.108784E+11 | 0.121559E+11 | 0.00 | 0.522406E+10 | 0.00 | 0.00 | 0.380989E+10 | 0.00 | 0.00 | 0.00 | 0.249172E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.450415E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.323195E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.223009E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.658042E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.239223E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 21164389.67 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.310560E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.204808E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.168655E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.418910E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.167319E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.450415E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 30638.74 | 05-JAN-09:09 | 6986.42 | 01-JAN-06:10 | 10054.01 | 02-JAN-08:09 | 0.00 | 3739.21 | 04-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 30522.99 | 01-FEB-10:20 | 6986.42 | 01-FEB-06:10 | 10054.01 | 01-FEB-08:09 | 0.00 | 3518.01 | 13-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 30522.99 | 06-MAR-09:09 | 6986.42 | 01-MAR-06:10 | 10054.01 | 01-MAR-08:09 | 0.00 | 3394.56 | 15-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 29865.39 | 06-APR-08:20 | 6986.42 | 01-APR-05:10 | 10054.01 | 01-APR-07:10 | 0.00 | 3071.44 | 04-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 29749.63 | 01-MAY-08:09 | 6986.42 | 01-MAY-19:30 | 10054.01 | 01-MAY-07:10 | 0.00 | 2205.38 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 29149.92 | 09-JUN-08:09 | 6986.42 | 01-JUN-19:00 | 10054.01 | 01-JUN-07:10 | 0.00 | 5040.92 | 29-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 29092.04 | 03-JUL-08:09 | 6986.42 | 01-JUL-20:19 | 10054.01 | 01-JUL-07:10 | 0.00 | 4590.21 | 15-JUL-14:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 29865.39 | 15-AUG-08:09 | 6986.42 | 01-AUG-19:49 | 10054.01 | 01-AUG-07:10 | 0.00 | 2106.47 | 01-AUG-13:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 30580.87 | 13-SEP-08:30 | 6986.42 | 01-SEP-05:10 | 10054.01 | 01-SEP-07:10 | 0.00 | 2106.47 | 01-SEP-09:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 30580.87 | 18-OCT-08:09 | 6986.42 | 01-OCT-05:10 | 10054.01 | 02-OCT-07:10 | 0.00 | 2998.18 | 30-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 30696.62 | 15-NOV-15:50 | 6986.42 | 01-NOV-05:10 | 10054.01 | 01-NOV-07:10 | 0.00 | 3261.10 | 25-NOV-08:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 30696.62 | 13-DEC-15:00 | 6986.42 | 01-DEC-06:10 | 10054.01 | 01-DEC-08:09 | 0.00 | 3655.54 | 18-DEC-17:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 29092.04 | 6986.42 | 10054.01 | 0.00 | 2106.47 | 0.00 | 0.00 | |||||
Maximum of Months | 30696.62 | 6986.42 | 10054.01 | 0.00 | 5040.92 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 3070.58 | 31-JAN-12:30 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 3104.89 | 24-FEB-12:20 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 3100.37 | 06-MAR-12:30 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 3038.78 | 01-APR-11:50 | 0.00 |
May | 5316.18 | 25-MAY-14:00 | 0.00 | 0.00 | 0.00 | 2885.84 | 01-MAY-11:30 | 0.00 |
June | 13819.36 | 29-JUN-15:00 | 0.00 | 0.00 | 0.00 | 2652.10 | 01-JUN-11:39 | 0.00 |
July | 10607.27 | 15-JUL-14:30 | 0.00 | 0.00 | 0.00 | 2414.23 | 01-JUL-11:50 | 0.00 |
August | 9562.70 | 08-AUG-15:39 | 0.00 | 0.00 | 0.00 | 2221.06 | 02-AUG-11:50 | 0.00 |
September | 6241.33 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 | 2252.48 | 26-SEP-11:39 | 0.00 |
October | 49.67 | 19-OCT-14:00 | 0.00 | 0.00 | 0.00 | 2478.02 | 30-OCT-11:00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2726.11 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2921.31 | 28-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2221.06 | 0.00 | ||
Maximum of Months | 13819.36 | 0.00 | 0.00 | 0.00 | 3104.89 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 49723.08 | 04-JAN-08:09 | 27270.96 | 10054.01 | 6986.42 | 0.00 | 3739.21 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 46108.20 | 13-FEB-15:00 | 30349.35 | 10054.01 | 0.00 | 0.00 | 3051.18 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 45472.73 | 15-MAR-08:09 | 30522.99 | 10054.01 | 0.00 | 0.00 | 3170.48 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 44990.26 | 04-APR-14:00 | 29691.76 | 10054.01 | 0.00 | 0.00 | 2668.48 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 48349.85 | 25-MAY-14:00 | 29034.16 | 10054.01 | 0.00 | 0.00 | 2106.47 | 0.00 | 0.00 | 5316.18 | 0.00 |
June | 57771.93 | 30-JUN-14:00 | 28376.56 | 10054.01 | 0.00 | 0.00 | 4943.36 | 0.00 | 0.00 | 12504.04 | 0.00 |
July | 55430.18 | 15-JUL-14:30 | 28376.56 | 10054.01 | 0.00 | 0.00 | 4590.21 | 0.00 | 0.00 | 10607.27 | 0.00 |
August | 51511.47 | 08-AUG-14:00 | 28376.56 | 10054.01 | 0.00 | 0.00 | 2106.47 | 0.00 | 0.00 | 9181.36 | 0.00 |
September | 49473.19 | 01-SEP-13:39 | 29691.76 | 10054.01 | 0.00 | 0.00 | 2106.47 | 0.00 | 0.00 | 5871.58 | 0.00 |
October | 45081.45 | 30-OCT-08:20 | 30522.99 | 10054.01 | 0.00 | 0.00 | 2813.20 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 49011.95 | 25-NOV-16:19 | 27270.96 | 10054.01 | 6986.42 | 0.00 | 3077.37 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 49386.50 | 18-DEC-16:30 | 27270.96 | 10054.01 | 6986.42 | 0.00 | 3619.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 44990.26 | 27270.96 | 10054.01 | 0.00 | 0.00 | 2106.47 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 57771.93 | 30522.99 | 10054.01 | 6986.42 | 0.00 | 4943.36 | 0.00 | 0.00 | 12504.04 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 383620.20 | 04-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 361562.35 | 12-FEB-22:49 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 277430.81 | 15-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 153593.27 | 04-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 63108.32 | 01-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 5371.89 | 01-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 9523.11 | 29-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 99861.45 | 30-OCT-05:40 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 222924.81 | 25-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 361201.97 | 18-DEC-16:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 383620.20 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 76.00 | 15.33 | 11.00 | 15.79 | 0.00 | 15.79 | 0.00 | 15.79 |
February | 56.00 | 15.50 | 9.17 | 16.00 | 0.00 | 16.00 | 0.00 | 16.00 |
March | 31.67 | 16.22 | 10.50 | 16.89 | 0.00 | 16.89 | 0.00 | 16.89 |
April | 14.33 | 17.82 | 9.00 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 |
May | 3.33 | 19.84 | 3.17 | 19.97 | 1.50 | 20.82 | 0.00 | 20.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 24.57 | 0.00 | 24.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 24.56 | 0.67 | 24.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 24.53 | 1.00 | 24.53 |
September | 0.50 | 20.50 | 0.50 | 20.50 | 2.83 | 23.48 | 0.17 | 23.52 |
October | 6.67 | 19.72 | 6.33 | 19.84 | 0.00 | 19.84 | 0.00 | 19.84 |
November | 17.67 | 17.12 | 8.33 | 17.88 | 0.00 | 17.88 | 0.00 | 17.88 |
December | 69.67 | 15.40 | 10.67 | 15.89 | 0.00 | 15.89 | 0.00 | 15.89 |
Annual Sum or Average | 275.83 | 15.90 | 68.67 | 16.57 | 41.33 | 17.43 | 1.83 | 17.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.79 | 0.00 | 15.79 |
Maximum of Months | 76.00 | 20.50 | 11.00 | 20.50 | 17.00 | 24.57 | 1.00 | 24.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 115.83 | 13.68 | 4.33 | 13.67 | 0.00 | 13.67 | 0.00 | 13.67 |
February | 102.50 | 13.93 | 3.83 | 13.93 | 0.00 | 13.93 | 0.00 | 13.93 |
March | 100.50 | 14.29 | 5.50 | 14.28 | 0.00 | 14.28 | 0.00 | 14.28 |
April | 57.17 | 14.63 | 3.67 | 14.62 | 0.00 | 14.62 | 0.00 | 14.62 |
May | 2.00 | 14.83 | 0.17 | 14.83 | 0.00 | 14.83 | 0.00 | 14.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.40 | 0.00 | 27.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.37 | 0.00 | 27.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.32 | 0.00 | 27.32 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22.67 | 14.88 | 1.83 | 14.88 | 0.00 | 14.88 | 0.00 | 14.88 |
November | 97.67 | 14.46 | 4.67 | 14.46 | 0.00 | 14.46 | 0.00 | 14.46 |
December | 115.67 | 13.77 | 4.17 | 13.77 | 0.00 | 13.77 | 0.00 | 13.77 |
Annual Sum or Average | 614.00 | 14.10 | 28.17 | 14.10 | 3.67 | 14.17 | 0.00 | 14.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.83 | 14.88 | 5.50 | 14.88 | 2.50 | 27.40 | 0.00 | 27.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.02 | 300.00 | 21.02 | 300.00 | 21.02 |
February | 276.00 | 21.03 | 276.00 | 21.03 | 276.00 | 21.03 |
March | 324.00 | 21.02 | 324.00 | 21.02 | 324.00 | 21.02 |
April | 300.00 | 21.19 | 281.83 | 21.14 | 281.83 | 21.13 |
May | 271.83 | 22.51 | 109.67 | 22.22 | 96.67 | 22.01 |
June | 218.00 | 23.51 | 119.33 | 23.61 | 59.00 | 23.62 |
July | 60.00 | 23.85 | 225.67 | 23.90 | 45.67 | 23.90 |
August | 99.17 | 23.76 | 219.00 | 23.86 | 52.00 | 23.87 |
September | 252.17 | 22.91 | 52.83 | 22.87 | 34.83 | 22.78 |
October | 300.00 | 21.40 | 235.33 | 21.26 | 235.33 | 21.21 |
November | 288.00 | 21.07 | 281.83 | 21.06 | 281.83 | 21.06 |
December | 300.00 | 21.02 | 300.00 | 21.02 | 300.00 | 21.02 |
Annual Sum or Average | 2989.17 | 21.71 | 2725.50 | 21.69 | 2287.17 | 21.57 |
Minimum of Months | 60.00 | 21.02 | 52.83 | 21.02 | 34.83 | 21.02 |
Maximum of Months | 324.00 | 23.85 | 324.00 | 23.90 | 324.00 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.53 | 300.00 | 15.53 | 300.00 | 15.53 |
February | 276.00 | 15.55 | 276.00 | 15.55 | 276.00 | 15.55 |
March | 324.00 | 15.62 | 324.00 | 15.62 | 324.00 | 15.62 |
April | 300.00 | 16.81 | 300.00 | 16.81 | 300.00 | 16.81 |
May | 242.83 | 20.41 | 199.33 | 20.73 | 137.83 | 20.28 |
June | 205.67 | 24.28 | 199.17 | 25.03 | 112.17 | 25.15 |
July | 177.17 | 26.47 | 285.50 | 26.41 | 169.67 | 26.46 |
August | 182.00 | 25.80 | 269.33 | 26.04 | 147.33 | 26.15 |
September | 233.17 | 21.38 | 155.17 | 21.73 | 104.83 | 21.47 |
October | 300.00 | 17.26 | 283.67 | 17.13 | 283.67 | 17.09 |
November | 288.00 | 15.80 | 288.00 | 15.80 | 288.00 | 15.80 |
December | 300.00 | 15.53 | 300.00 | 15.53 | 300.00 | 15.53 |
Annual Sum or Average | 3128.83 | 18.46 | 3180.17 | 18.74 | 2743.50 | 18.49 |
Minimum of Months | 177.17 | 15.53 | 155.17 | 15.53 | 104.83 | 15.53 |
Maximum of Months | 324.00 | 26.47 | 324.00 | 26.41 | 324.00 | 26.46 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 10.00 | 300.00 | 10.00 | 300.00 | 10.00 |
February | 276.00 | 10.06 | 276.00 | 10.06 | 276.00 | 10.06 |
March | 324.00 | 10.25 | 324.00 | 10.25 | 324.00 | 10.25 |
April | 300.00 | 12.05 | 300.00 | 12.05 | 300.00 | 12.05 |
May | 287.33 | 18.07 | 230.67 | 17.74 | 212.67 | 17.43 |
June | 267.50 | 23.63 | 161.83 | 24.18 | 132.00 | 24.37 |
July | 228.83 | 28.17 | 294.50 | 27.87 | 225.67 | 27.98 |
August | 195.83 | 25.64 | 251.00 | 25.96 | 142.83 | 26.16 |
September | 270.33 | 19.89 | 184.50 | 19.63 | 169.83 | 19.36 |
October | 300.00 | 13.07 | 300.00 | 13.07 | 300.00 | 13.07 |
November | 288.00 | 10.40 | 288.00 | 10.40 | 288.00 | 10.40 |
December | 300.00 | 10.00 | 300.00 | 10.00 | 300.00 | 10.00 |
Annual Sum or Average | 3337.83 | 15.27 | 3210.50 | 15.26 | 2971.00 | 15.00 |
Minimum of Months | 195.83 | 10.00 | 161.83 | 10.00 | 132.00 | 10.00 |
Maximum of Months | 324.00 | 28.17 | 324.00 | 27.87 | 324.00 | 27.98 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 |
May | 0.115628E+10 | 0.258171E+09 | 81.71 | 0.102671E+10 | 0.129572E+09 | 0.00 | 1.00 | 17-MAY-19:35 | 0.00 | 01-MAY-00:03 | 19491.95 | 25-MAY-20:31 | 17659.28 | 18-MAY-19:21 | 6286.13 | 26-MAY-18:07 | 4104.88 | 25-MAY-20:31 | 0.00 | 01-MAY-00:03 |
June | 0.391004E+10 | 0.856680E+09 | 196.72 | 0.305113E+10 | 0.858915E+09 | 0.00 | 1.00 | 06-JUN-17:35 | 0.00 | 01-JUN-00:10 | 21970.38 | 19-JUN-17:21 | 18186.19 | 08-JUN-17:15 | 11497.59 | 19-JUN-19:05 | 4678.16 | 29-JUN-17:08 | 0.00 | 01-JUN-00:10 |
July | 0.681373E+10 | 0.145203E+10 | 288.01 | 0.511125E+10 | 0.170248E+10 | 0.00 | 1.00 | 01-JUL-00:13 | 0.00 | 01-JUL-00:10 | 22515.76 | 03-JUL-22:25 | 17753.39 | 07-JUL-17:11 | 11523.08 | 03-JUL-22:25 | 4582.11 | 03-JUL-22:25 | 0.00 | 01-JUL-00:10 |
August | 0.486705E+10 | 0.103420E+10 | 234.84 | 0.362147E+10 | 0.124558E+10 | 0.00 | 1.00 | 01-AUG-05:55 | 0.00 | 01-AUG-00:10 | 21880.03 | 31-AUG-18:35 | 18104.50 | 05-AUG-17:11 | 10562.28 | 28-AUG-17:31 | 4503.36 | 31-AUG-18:35 | 0.00 | 01-AUG-00:10 |
September | 0.535763E+09 | 0.115679E+09 | 54.77 | 0.458703E+09 | 77060469.97 | 0.00 | 1.00 | 01-SEP-00:45 | 0.00 | 01-SEP-00:10 | 20666.64 | 01-SEP-00:45 | 17146.84 | 06-SEP-17:15 | 10400.89 | 01-SEP-00:45 | 4304.20 | 01-SEP-00:45 | 0.00 | 01-SEP-00:10 |
October | 386562.46 | 91075.45 | 2.67 | 386562.46 | 0.00 | 0.00 | 0.03 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 211.15 | 19-OCT-15:00 | 211.15 | 19-OCT-15:00 | 0.00 | 19-OCT-15:10 | 49.67 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.172833E+11 | 0.371685E+10 | 858.72 | 0.132696E+11 | 0.401361E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.681373E+10 | 0.145203E+10 | 288.01 | 0.511125E+10 | 0.170248E+10 | 0.00 | 1.00 | 0.00 | 22515.76 | 18186.19 | 11523.08 | 4678.16 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 |
May | 0.458361E+09 | 0.119760E+09 | 21.00 | 0.364623E+09 | 93737798.61 | 0.00 | 0.54 | 25-MAY-15:00 | 0.00 | 01-MAY-00:03 | 13751.71 | 25-MAY-15:00 | 10446.49 | 25-MAY-15:00 | 3316.82 | 25-MAY-14:40 | 3522.83 | 25-MAY-15:00 | 0.00 | 01-MAY-00:03 |
June | 0.463685E+10 | 0.113848E+10 | 85.88 | 0.321060E+10 | 0.142625E+10 | 0.00 | 1.00 | 25-JUN-11:20 | 0.00 | 01-JUN-00:10 | 60223.98 | 25-JUN-12:05 | 42009.00 | 30-JUN-19:20 | 25449.42 | 25-JUN-12:05 | 13841.47 | 29-JUN-17:08 | 0.00 | 01-JUN-00:10 |
July | 0.987212E+10 | 0.235786E+10 | 192.20 | 0.671556E+10 | 0.315656E+10 | 0.00 | 1.00 | 01-JUL-17:19 | 0.00 | 01-JUL-00:10 | 62960.47 | 23-JUL-08:55 | 51408.00 | 07-JUL-17:29 | 32866.88 | 23-JUL-08:55 | 13674.63 | 03-JUL-18:53 | 0.00 | 01-JUL-00:10 |
August | 0.461436E+10 | 0.110924E+10 | 111.67 | 0.308480E+10 | 0.152955E+10 | 0.00 | 1.00 | 08-AUG-17:10 | 0.00 | 01-AUG-00:10 | 58859.01 | 09-AUG-18:13 | 46286.00 | 13-AUG-14:05 | 22386.30 | 09-AUG-18:33 | 13127.71 | 09-AUG-18:13 | 0.00 | 01-AUG-00:10 |
September | 0.367638E+09 | 88312450.15 | 9.22 | 0.267036E+09 | 0.100602E+09 | 0.00 | 1.00 | 01-SEP-17:32 | 0.00 | 01-SEP-00:10 | 55602.21 | 01-SEP-17:32 | 39846.30 | 01-SEP-17:32 | 15755.92 | 01-SEP-17:32 | 12239.34 | 01-SEP-17:32 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.199493E+11 | 0.481366E+10 | 419.97 | 0.136426E+11 | 0.630671E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.987212E+10 | 0.235786E+10 | 192.20 | 0.671556E+10 | 0.315656E+10 | 0.00 | 1.00 | 0.00 | 62960.47 | 51408.00 | 32866.88 | 13841.47 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.95 | 31.18 | 42.77 | 27.91 | 296.10 | 0.00 | 0.00 | 0.00 |
February | 119.55 | 54.64 | 64.92 | 76.08 | 231.01 | 0.00 | 0.00 | 0.00 |
March | 157.31 | 80.63 | 76.68 | 125.45 | 172.64 | 0.00 | 0.00 | 0.00 |
April | 200.46 | 101.51 | 98.95 | 200.28 | 95.53 | 0.00 | 0.00 | 0.00 |
May | 246.84 | 117.94 | 128.91 | 285.42 | 54.91 | 0.00 | 0.00 | 0.00 |
June | 237.82 | 102.89 | 134.94 | 285.56 | 42.87 | 0.00 | 0.00 | 0.00 |
July | 254.37 | 118.55 | 135.82 | 309.42 | 45.46 | 0.00 | 0.00 | 0.00 |
August | 208.32 | 94.34 | 113.99 | 244.04 | 53.46 | 0.00 | 0.00 | 0.00 |
September | 163.18 | 73.18 | 90.01 | 170.31 | 77.05 | 0.00 | 0.00 | 0.00 |
October | 103.25 | 41.48 | 61.77 | 87.34 | 102.58 | 0.00 | 0.00 | 0.00 |
November | 62.99 | 21.46 | 41.53 | 32.13 | 165.57 | 0.00 | 0.00 | 0.00 |
December | 55.63 | 19.35 | 36.28 | 14.65 | 286.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.18 | 71.53 | 85.65 | 155.34 | 134.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 55.63 | 19.35 | 36.28 | 14.65 | 42.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 254.37 | 118.55 | 135.82 | 309.42 | 296.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.95 | 31.18 | 42.77 | 27.91 | 296.10 | 0.00 | 0.00 | 0.00 |
February | 119.55 | 54.64 | 64.92 | 76.08 | 231.01 | 0.00 | 0.00 | 0.00 |
March | 157.31 | 80.63 | 76.68 | 125.45 | 172.64 | 0.00 | 0.00 | 0.00 |
April | 200.46 | 101.51 | 98.95 | 200.28 | 95.53 | 0.00 | 0.00 | 0.00 |
May | 246.84 | 117.94 | 128.91 | 285.42 | 54.91 | 0.00 | 0.00 | 0.00 |
June | 237.82 | 102.89 | 134.94 | 285.56 | 42.87 | 0.00 | 0.00 | 0.00 |
July | 254.37 | 118.55 | 135.82 | 309.42 | 45.46 | 0.00 | 0.00 | 0.00 |
August | 208.32 | 94.34 | 113.99 | 244.04 | 53.46 | 0.00 | 0.00 | 0.00 |
September | 163.18 | 73.18 | 90.01 | 170.31 | 77.05 | 0.00 | 0.00 | 0.00 |
October | 103.25 | 41.48 | 61.77 | 87.34 | 102.58 | 0.00 | 0.00 | 0.00 |
November | 62.99 | 21.46 | 41.53 | 32.13 | 165.57 | 0.00 | 0.00 | 0.00 |
December | 55.63 | 19.35 | 36.28 | 14.65 | 286.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.18 | 71.53 | 85.65 | 155.34 | 134.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 55.63 | 19.35 | 36.28 | 14.65 | 42.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 254.37 | 118.55 | 135.82 | 309.42 | 296.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.27 | 0.00 | 19.27 | 0.17 | 189.49 | 0.00 | 0.00 | 0.00 |
February | 29.60 | 0.00 | 29.60 | 2.23 | 147.34 | 0.00 | 0.00 | 0.00 |
March | 36.42 | 0.00 | 36.42 | 5.82 | 108.47 | 0.00 | 0.00 | 0.00 |
April | 47.84 | 0.47 | 47.37 | 25.97 | 56.83 | 0.00 | 0.00 | 0.00 |
May | 67.20 | 3.62 | 63.58 | 63.10 | 30.11 | 0.00 | 0.00 | 0.00 |
June | 74.90 | 8.20 | 66.70 | 81.85 | 23.55 | 0.00 | 0.00 | 0.00 |
July | 71.49 | 6.04 | 65.44 | 77.82 | 24.83 | 0.00 | 0.00 | 0.00 |
August | 54.56 | 1.10 | 53.45 | 52.45 | 30.26 | 0.00 | 0.00 | 0.00 |
September | 42.40 | 0.03 | 42.37 | 30.04 | 45.92 | 0.00 | 0.00 | 0.00 |
October | 29.41 | 0.00 | 29.41 | 11.45 | 62.11 | 0.00 | 0.00 | 0.00 |
November | 19.47 | 0.00 | 19.47 | 1.73 | 103.10 | 0.00 | 0.00 | 0.00 |
December | 16.33 | 0.00 | 16.33 | 0.00 | 180.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42.47 | 1.63 | 40.84 | 29.55 | 83.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.33 | 0.00 | 16.33 | 0.00 | 23.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.90 | 8.20 | 66.70 | 81.85 | 189.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.27 | 0.00 | 19.27 | 0.17 | 189.49 | 0.00 | 0.00 | 0.00 |
February | 29.60 | 0.00 | 29.60 | 2.23 | 147.34 | 0.00 | 0.00 | 0.00 |
March | 36.42 | 0.00 | 36.42 | 5.82 | 108.47 | 0.00 | 0.00 | 0.00 |
April | 47.84 | 0.47 | 47.37 | 25.96 | 56.83 | 0.00 | 0.00 | 0.00 |
May | 67.20 | 3.62 | 63.58 | 63.10 | 30.11 | 0.00 | 0.00 | 0.00 |
June | 74.90 | 8.19 | 66.70 | 81.85 | 23.55 | 0.00 | 0.00 | 0.00 |
July | 71.49 | 6.04 | 65.44 | 77.82 | 24.83 | 0.00 | 0.00 | 0.00 |
August | 54.55 | 1.10 | 53.45 | 52.45 | 30.26 | 0.00 | 0.00 | 0.00 |
September | 42.40 | 0.03 | 42.37 | 30.04 | 45.92 | 0.00 | 0.00 | 0.00 |
October | 29.41 | 0.00 | 29.41 | 11.45 | 62.11 | 0.00 | 0.00 | 0.00 |
November | 19.47 | 0.00 | 19.47 | 1.73 | 103.10 | 0.00 | 0.00 | 0.00 |
December | 16.32 | 0.00 | 16.32 | 0.00 | 180.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42.47 | 1.63 | 40.84 | 29.55 | 83.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.32 | 0.00 | 16.32 | 0.00 | 23.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.90 | 8.19 | 66.70 | 81.85 | 189.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 2.05 | 261.00 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 24.28 | 193.91 | 0.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 58.26 | 134.33 | 2.33 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 116.59 | 70.85 | 4.00 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 156.96 | 47.79 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 163.40 | 46.74 | 33.67 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 160.23 | 61.51 | 24.83 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 125.93 | 58.55 | 29.50 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 86.37 | 63.90 | 12.33 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 44.53 | 67.84 | 42.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 14.41 | 118.56 | 17.83 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 0.57 | 244.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 79.75 | 113.89 | 167.17 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 0.57 | 46.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 163.40 | 261.00 | 42.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 2.05 | 261.00 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 24.28 | 193.91 | 0.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 58.26 | 134.33 | 2.33 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 116.59 | 70.85 | 4.00 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 156.96 | 47.79 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 163.40 | 46.74 | 33.67 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 160.23 | 61.51 | 24.83 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 125.93 | 58.55 | 29.50 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 86.37 | 63.90 | 12.33 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 44.53 | 67.84 | 42.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 14.41 | 118.56 | 17.83 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 0.57 | 244.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 79.75 | 113.89 | 167.17 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 0.57 | 46.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 163.40 | 261.00 | 42.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 2.05 | 261.00 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 24.28 | 193.91 | 0.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 58.26 | 134.33 | 2.33 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 116.59 | 70.85 | 4.00 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 156.96 | 47.79 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 163.40 | 46.74 | 33.67 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 160.23 | 61.51 | 24.83 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 125.93 | 58.55 | 29.50 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 86.37 | 63.90 | 12.33 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 44.53 | 67.84 | 42.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 14.41 | 118.56 | 17.83 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 0.57 | 244.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 79.75 | 113.89 | 167.17 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 0.57 | 46.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 163.40 | 261.00 | 42.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 2.05 | 261.00 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 24.28 | 193.91 | 0.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 58.26 | 134.33 | 2.33 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 116.59 | 70.85 | 4.00 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 156.96 | 47.79 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 163.40 | 46.74 | 33.67 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 160.23 | 61.51 | 24.83 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 125.93 | 58.55 | 29.50 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 86.37 | 63.90 | 12.33 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 44.53 | 67.84 | 42.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 14.41 | 118.56 | 17.83 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 0.57 | 244.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 79.75 | 113.89 | 167.17 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 0.57 | 46.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 163.40 | 261.00 | 42.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 2.05 | 261.00 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 24.28 | 193.91 | 0.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 58.26 | 134.33 | 2.33 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 116.59 | 70.85 | 4.00 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 156.96 | 47.79 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 163.40 | 46.74 | 33.67 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 160.23 | 61.51 | 24.83 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 125.93 | 58.55 | 29.50 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 86.37 | 63.90 | 12.33 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 44.53 | 67.84 | 42.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 14.41 | 118.56 | 17.83 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 0.57 | 244.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 79.75 | 113.89 | 167.17 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 0.57 | 46.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 163.40 | 261.00 | 42.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 2.05 | 261.00 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 24.28 | 193.91 | 0.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 58.26 | 134.33 | 2.33 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 116.59 | 70.85 | 4.00 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 156.96 | 47.79 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 163.40 | 46.74 | 33.67 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 160.23 | 61.51 | 24.83 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 125.93 | 58.55 | 29.50 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 86.37 | 63.90 | 12.33 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 44.53 | 67.84 | 42.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 14.41 | 118.56 | 17.83 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 0.57 | 244.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 79.75 | 113.89 | 167.17 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 0.57 | 46.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 163.40 | 261.00 | 42.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 2.05 | 261.00 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 24.28 | 193.91 | 0.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 58.26 | 134.33 | 2.33 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 116.59 | 70.85 | 4.00 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 156.96 | 47.79 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 163.40 | 46.74 | 33.67 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 160.23 | 61.51 | 24.83 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 125.93 | 58.55 | 29.50 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 86.37 | 63.90 | 12.33 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 44.53 | 67.84 | 42.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 14.41 | 118.56 | 17.83 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 0.57 | 244.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 79.75 | 113.89 | 167.17 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 0.57 | 46.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 163.40 | 261.00 | 42.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 2.05 | 261.00 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 24.28 | 193.91 | 0.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 58.26 | 134.33 | 2.33 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 116.59 | 70.85 | 4.00 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 156.96 | 47.79 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 163.40 | 46.74 | 33.67 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 160.23 | 61.51 | 24.83 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 125.93 | 58.55 | 29.50 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 86.37 | 63.90 | 12.33 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 44.53 | 67.84 | 42.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 14.41 | 118.56 | 17.83 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 0.57 | 244.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 79.75 | 113.89 | 167.17 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 0.57 | 46.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 163.40 | 261.00 | 42.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 2.05 | 261.00 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 24.28 | 193.91 | 0.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 58.26 | 134.33 | 2.33 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 116.59 | 70.85 | 4.00 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 156.96 | 47.79 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 163.40 | 46.74 | 33.67 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 160.23 | 61.51 | 24.83 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 125.93 | 58.55 | 29.50 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 86.37 | 63.90 | 12.33 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 44.53 | 67.84 | 42.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 14.41 | 118.56 | 17.83 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 0.57 | 244.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 79.75 | 113.89 | 167.17 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 0.57 | 46.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 163.40 | 261.00 | 42.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 2.05 | 261.00 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 24.28 | 193.91 | 0.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 58.26 | 134.33 | 2.33 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 116.59 | 70.85 | 4.00 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 156.96 | 47.79 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 163.40 | 46.74 | 33.67 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 160.23 | 61.51 | 24.83 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 125.93 | 58.55 | 29.50 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 86.37 | 63.90 | 12.33 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 44.53 | 67.84 | 42.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 14.41 | 118.56 | 17.83 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 0.57 | 244.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 79.75 | 113.89 | 167.17 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 0.57 | 46.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 163.40 | 261.00 | 42.67 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198056E+09 | 83504024.34 | 0.114552E+09 | 74743425.66 | 0.793084E+09 |
February | 0.289227E+09 | 0.132178E+09 | 0.157049E+09 | 0.184058E+09 | 0.558858E+09 |
March | 0.421337E+09 | 0.215967E+09 | 0.205370E+09 | 0.335995E+09 | 0.462396E+09 |
April | 0.519600E+09 | 0.263122E+09 | 0.256478E+09 | 0.519132E+09 | 0.247624E+09 |
May | 0.661147E+09 | 0.315879E+09 | 0.345268E+09 | 0.764471E+09 | 0.147064E+09 |
June | 0.616438E+09 | 0.266683E+09 | 0.349755E+09 | 0.740182E+09 | 0.111128E+09 |
July | 0.681317E+09 | 0.317534E+09 | 0.363784E+09 | 0.828753E+09 | 0.121757E+09 |
August | 0.557977E+09 | 0.252677E+09 | 0.305299E+09 | 0.653645E+09 | 0.143175E+09 |
September | 0.422974E+09 | 0.189676E+09 | 0.233298E+09 | 0.441437E+09 | 0.199709E+09 |
October | 0.276554E+09 | 0.111113E+09 | 0.165441E+09 | 0.233927E+09 | 0.274738E+09 |
November | 0.163279E+09 | 55629203.46 | 0.107650E+09 | 83277333.14 | 0.429161E+09 |
December | 0.149007E+09 | 51834439.10 | 97172094.31 | 39249450.35 | 0.767479E+09 |
Annual Sum or Average | 0.495691E+10 | 0.225580E+10 | 0.270112E+10 | 0.489887E+10 | 0.425617E+10 |
Minimum of Months | 0.149007E+09 | 51834439.10 | 97172094.31 | 39249450.35 | 0.111128E+09 |
Maximum of Months | 0.681317E+09 | 0.317534E+09 | 0.363784E+09 | 0.828753E+09 | 0.793084E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198056E+09 | 83504024.34 | 0.114552E+09 | 74743425.66 | 0.793084E+09 |
February | 0.289227E+09 | 0.132178E+09 | 0.157049E+09 | 0.184058E+09 | 0.558858E+09 |
March | 0.421337E+09 | 0.215967E+09 | 0.205370E+09 | 0.335995E+09 | 0.462396E+09 |
April | 0.519600E+09 | 0.263122E+09 | 0.256478E+09 | 0.519132E+09 | 0.247624E+09 |
May | 0.661147E+09 | 0.315879E+09 | 0.345268E+09 | 0.764471E+09 | 0.147064E+09 |
June | 0.616438E+09 | 0.266683E+09 | 0.349755E+09 | 0.740182E+09 | 0.111128E+09 |
July | 0.681317E+09 | 0.317534E+09 | 0.363784E+09 | 0.828753E+09 | 0.121757E+09 |
August | 0.557977E+09 | 0.252677E+09 | 0.305299E+09 | 0.653645E+09 | 0.143175E+09 |
September | 0.422974E+09 | 0.189676E+09 | 0.233298E+09 | 0.441437E+09 | 0.199709E+09 |
October | 0.276554E+09 | 0.111113E+09 | 0.165441E+09 | 0.233927E+09 | 0.274738E+09 |
November | 0.163279E+09 | 55629203.46 | 0.107650E+09 | 83277333.14 | 0.429161E+09 |
December | 0.149007E+09 | 51834439.10 | 97172094.31 | 39249450.35 | 0.767479E+09 |
Annual Sum or Average | 0.495691E+10 | 0.225580E+10 | 0.270112E+10 | 0.489887E+10 | 0.425617E+10 |
Minimum of Months | 0.149007E+09 | 51834439.10 | 97172094.31 | 39249450.35 | 0.111128E+09 |
Maximum of Months | 0.681317E+09 | 0.317534E+09 | 0.363784E+09 | 0.828753E+09 | 0.793084E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51607008.66 | 0.00 | 51607008.66 | 449605.68 | 0.507521E+09 |
February | 71600876.49 | 0.00 | 71600876.49 | 5404679.72 | 0.356440E+09 |
March | 97556880.51 | 6990.70 | 97549889.82 | 15590668.07 | 0.290531E+09 |
April | 0.124006E+09 | 1215458.85 | 0.122790E+09 | 67302790.11 | 0.147308E+09 |
May | 0.179987E+09 | 9691789.75 | 0.170295E+09 | 0.169017E+09 | 80634960.11 |
June | 0.194135E+09 | 21241450.32 | 0.172894E+09 | 0.212152E+09 | 61047378.88 |
July | 0.191472E+09 | 16188327.23 | 0.175283E+09 | 0.208429E+09 | 66512010.52 |
August | 0.146121E+09 | 2953379.03 | 0.143168E+09 | 0.140477E+09 | 81060890.67 |
September | 0.109909E+09 | 79221.47 | 0.109830E+09 | 77864764.87 | 0.119036E+09 |
October | 78778790.27 | 0.00 | 78778790.27 | 30660320.57 | 0.166349E+09 |
November | 50478913.01 | 0.00 | 50478913.01 | 4496745.29 | 0.267230E+09 |
December | 43725560.62 | 0.00 | 43725560.62 | 11780.99 | 0.484328E+09 |
Annual Sum or Average | 0.133938E+10 | 51376617.36 | 0.128800E+10 | 0.931857E+09 | 0.262800E+10 |
Minimum of Months | 43725560.62 | 0.00 | 43725560.62 | 11780.99 | 61047378.88 |
Maximum of Months | 0.194135E+09 | 21241450.32 | 0.175283E+09 | 0.212152E+09 | 0.507521E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51605304.71 | 0.00 | 51605304.71 | 449514.67 | 0.507522E+09 |
February | 71598623.61 | 0.00 | 71598623.61 | 5404047.77 | 0.356441E+09 |
March | 97553940.55 | 6990.37 | 97546950.18 | 15589245.62 | 0.290532E+09 |
April | 0.124002E+09 | 1215401.88 | 0.122787E+09 | 67299642.66 | 0.147308E+09 |
May | 0.179982E+09 | 9691335.48 | 0.170290E+09 | 0.169011E+09 | 80634602.34 |
June | 0.194129E+09 | 21240454.70 | 0.172888E+09 | 0.212144E+09 | 61046954.64 |
July | 0.191466E+09 | 16187568.47 | 0.175278E+09 | 0.208422E+09 | 66511574.94 |
August | 0.146117E+09 | 2953240.61 | 0.143163E+09 | 0.140472E+09 | 81060531.68 |
September | 0.109906E+09 | 79217.76 | 0.109827E+09 | 77861024.34 | 0.119036E+09 |
October | 78776162.97 | 0.00 | 78776162.97 | 30658039.11 | 0.166349E+09 |
November | 50477193.11 | 0.00 | 50477193.11 | 4496311.45 | 0.267230E+09 |
December | 43724069.50 | 0.00 | 43724069.50 | 11770.31 | 0.484328E+09 |
Annual Sum or Average | 0.133934E+10 | 51374209.27 | 0.128796E+10 | 0.931818E+09 | 0.262800E+10 |
Minimum of Months | 43724069.50 | 0.00 | 43724069.50 | 11770.31 | 61046954.64 |
Maximum of Months | 0.194129E+09 | 21240454.70 | 0.175278E+09 | 0.212144E+09 | 0.507522E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 5483238.59 | 0.699056E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 58750116.42 | 0.469097E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.156040E+09 | 0.359785E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.302196E+09 | 0.183640E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.420399E+09 | 0.127998E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.423534E+09 | 0.121140E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.429153E+09 | 0.164747E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.337295E+09 | 0.156827E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.223875E+09 | 0.165634E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.119278E+09 | 0.181690E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 37359895.62 | 0.307299E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 1519821.89 | 0.654608E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.251488E+10 | 0.359152E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 1519821.89 | 0.121140E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.429153E+09 | 0.699056E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 5483238.59 | 0.699056E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 58750116.42 | 0.469097E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.156040E+09 | 0.359785E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.302196E+09 | 0.183640E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.420399E+09 | 0.127998E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.423534E+09 | 0.121140E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.429153E+09 | 0.164747E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.337295E+09 | 0.156827E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.223875E+09 | 0.165634E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.119278E+09 | 0.181690E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 37359895.62 | 0.307299E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 1519821.89 | 0.654608E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.251488E+10 | 0.359152E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 1519821.89 | 0.121140E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.429153E+09 | 0.699056E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 5483238.59 | 0.699056E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 58750116.42 | 0.469097E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.156040E+09 | 0.359785E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.302196E+09 | 0.183640E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.420399E+09 | 0.127998E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.423534E+09 | 0.121140E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.429153E+09 | 0.164747E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.337295E+09 | 0.156827E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.223875E+09 | 0.165634E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.119278E+09 | 0.181690E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 37359895.62 | 0.307299E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 1519821.89 | 0.654608E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.251488E+10 | 0.359152E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 1519821.89 | 0.121140E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.429153E+09 | 0.699056E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 5483238.59 | 0.699056E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 58750116.42 | 0.469097E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.156040E+09 | 0.359785E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.302196E+09 | 0.183640E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.420399E+09 | 0.127998E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.423534E+09 | 0.121140E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.429153E+09 | 0.164747E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.337295E+09 | 0.156827E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.223875E+09 | 0.165634E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.119278E+09 | 0.181690E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 37359895.62 | 0.307299E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 1519821.89 | 0.654608E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.251488E+10 | 0.359152E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 1519821.89 | 0.121140E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.429153E+09 | 0.699056E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 5483238.59 | 0.699056E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 58750116.42 | 0.469097E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.156040E+09 | 0.359785E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.302196E+09 | 0.183640E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.420399E+09 | 0.127998E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.423534E+09 | 0.121140E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.429153E+09 | 0.164747E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.337295E+09 | 0.156827E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.223875E+09 | 0.165634E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.119278E+09 | 0.181690E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 37359895.62 | 0.307299E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 1519821.89 | 0.654608E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.251488E+10 | 0.359152E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 1519821.89 | 0.121140E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.429153E+09 | 0.699056E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 5483238.59 | 0.699056E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 58750116.42 | 0.469097E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.156040E+09 | 0.359785E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.302196E+09 | 0.183640E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.420399E+09 | 0.127998E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.423534E+09 | 0.121140E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.429153E+09 | 0.164747E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.337295E+09 | 0.156827E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.223875E+09 | 0.165634E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.119278E+09 | 0.181690E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 37359895.62 | 0.307299E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 1519821.89 | 0.654608E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.251488E+10 | 0.359152E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 1519821.89 | 0.121140E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.429153E+09 | 0.699056E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 5483238.59 | 0.699056E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 58750116.42 | 0.469097E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.156040E+09 | 0.359785E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.302196E+09 | 0.183640E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.420399E+09 | 0.127998E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.423534E+09 | 0.121140E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.429153E+09 | 0.164747E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.337295E+09 | 0.156827E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.223875E+09 | 0.165634E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.119278E+09 | 0.181690E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 37359895.62 | 0.307299E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 1519821.89 | 0.654608E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.251488E+10 | 0.359152E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 1519821.89 | 0.121140E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.429153E+09 | 0.699056E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 5483238.59 | 0.699056E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 58750116.42 | 0.469097E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.156040E+09 | 0.359785E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.302196E+09 | 0.183640E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.420399E+09 | 0.127998E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.423534E+09 | 0.121140E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.429153E+09 | 0.164747E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.337295E+09 | 0.156827E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.223875E+09 | 0.165634E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.119278E+09 | 0.181690E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 37359895.62 | 0.307299E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 1519821.89 | 0.654608E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.251488E+10 | 0.359152E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 1519821.89 | 0.121140E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.429153E+09 | 0.699056E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 5483238.59 | 0.699056E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 58750116.42 | 0.469097E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.156040E+09 | 0.359785E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.302196E+09 | 0.183640E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.420399E+09 | 0.127998E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.423534E+09 | 0.121140E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.429153E+09 | 0.164747E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.337295E+09 | 0.156827E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.223875E+09 | 0.165634E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.119278E+09 | 0.181690E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 37359895.62 | 0.307299E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 1519821.89 | 0.654608E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.251488E+10 | 0.359152E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 1519821.89 | 0.121140E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.429153E+09 | 0.699056E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 5483238.59 | 0.699056E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 58750116.42 | 0.469097E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.156040E+09 | 0.359785E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.302196E+09 | 0.183640E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.420399E+09 | 0.127998E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.423534E+09 | 0.121140E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.429153E+09 | 0.164747E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.337295E+09 | 0.156827E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.223875E+09 | 0.165634E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.119278E+09 | 0.181690E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 37359895.62 | 0.307299E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 1519821.89 | 0.654608E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.251488E+10 | 0.359152E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 1519821.89 | 0.121140E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.429153E+09 | 0.699056E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 35.72 | 950.75 | 186.43 | 62.35 | 124.07 | 0.00 | 0.00 |
February | 138.79 | 738.85 | 298.30 | 109.27 | 189.03 | 0.00 | 0.00 |
March | 250.55 | 550.23 | 387.46 | 161.27 | 226.19 | 0.00 | 0.00 |
April | 449.86 | 302.09 | 496.61 | 203.96 | 292.64 | 0.00 | 0.00 |
May | 694.73 | 167.71 | 628.09 | 243.11 | 384.98 | 0.00 | 0.00 |
June | 731.54 | 129.57 | 625.44 | 222.16 | 403.28 | 0.00 | 0.00 |
July | 771.07 | 137.17 | 651.72 | 249.19 | 402.53 | 0.00 | 0.00 |
August | 592.33 | 166.79 | 525.76 | 190.88 | 334.88 | 0.00 | 0.00 |
September | 398.95 | 244.20 | 411.17 | 146.42 | 264.76 | 0.00 | 0.00 |
October | 194.60 | 326.40 | 265.33 | 82.97 | 182.36 | 0.00 | 0.00 |
November | 59.09 | 528.70 | 164.94 | 42.92 | 122.01 | 0.00 | 0.00 |
December | 15.49 | 920.92 | 143.92 | 38.71 | 105.21 | 0.00 | 0.00 |
Annual Sum or Average | 362.35 | 429.16 | 399.31 | 146.32 | 252.99 | 0.00 | 0.00 |
Minimum of Months | 15.49 | 129.57 | 143.92 | 38.71 | 105.21 | 0.00 | 0.00 |
Maximum of Months | 771.07 | 950.75 | 651.72 | 249.19 | 403.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 117.33 | 24785.40 | 263.87 | 93.87 | 170.00 | 0.00 | 0.00 |
February | 1313.96 | 18094.83 | 465.60 | 215.66 | 249.93 | 0.00 | 0.00 |
March | 2693.26 | 11042.22 | 667.44 | 377.68 | 289.76 | 0.00 | 0.00 |
April | 4908.42 | 4468.86 | 970.49 | 610.55 | 359.94 | 0.00 | 0.00 |
May | 6251.17 | 1672.86 | 1190.47 | 667.62 | 522.86 | 0.00 | 0.00 |
June | 6491.11 | 1722.51 | 1256.31 | 722.81 | 533.50 | 0.00 | 0.00 |
July | 6201.33 | 2904.81 | 1283.98 | 764.19 | 519.80 | 0.00 | 0.00 |
August | 4314.05 | 2573.44 | 1022.95 | 576.18 | 446.77 | 0.00 | 0.00 |
September | 3405.39 | 2112.17 | 744.02 | 384.83 | 359.19 | 0.00 | 0.00 |
October | 1773.62 | 3154.17 | 429.05 | 164.60 | 264.45 | 0.00 | 0.00 |
November | 653.93 | 8517.31 | 257.19 | 79.94 | 177.26 | 0.00 | 0.00 |
December | 33.30 | 23059.64 | 204.66 | 53.45 | 151.21 | 0.00 | 0.00 |
Annual Sum or Average | 3187.57 | 8647.26 | 730.99 | 393.45 | 337.55 | 0.00 | 0.00 |
Minimum of Months | 33.30 | 1672.86 | 204.66 | 53.45 | 151.21 | 0.00 | 0.00 |
Maximum of Months | 6491.11 | 24785.40 | 1283.98 | 764.19 | 533.50 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 95660032.91 | 0.254648E+10 | 0.499325E+09 | 0.167008E+09 | 0.332317E+09 | 0.00 | 0.00 |
February | 0.335764E+09 | 0.178744E+10 | 0.721654E+09 | 0.264356E+09 | 0.457298E+09 | 0.00 | 0.00 |
March | 0.671061E+09 | 0.147375E+10 | 0.103778E+10 | 0.431948E+09 | 0.605837E+09 | 0.00 | 0.00 |
April | 0.116603E+10 | 0.783028E+09 | 0.128721E+10 | 0.528674E+09 | 0.758533E+09 | 0.00 | 0.00 |
May | 0.186077E+10 | 0.449195E+09 | 0.168226E+10 | 0.651142E+09 | 0.103112E+10 | 0.00 | 0.00 |
June | 0.189615E+10 | 0.335843E+09 | 0.162114E+10 | 0.575848E+09 | 0.104529E+10 | 0.00 | 0.00 |
July | 0.206522E+10 | 0.367405E+09 | 0.174557E+10 | 0.667443E+09 | 0.107813E+10 | 0.00 | 0.00 |
August | 0.158649E+10 | 0.446718E+09 | 0.140819E+10 | 0.511261E+09 | 0.896930E+09 | 0.00 | 0.00 |
September | 0.103408E+10 | 0.632970E+09 | 0.106576E+10 | 0.379510E+09 | 0.686253E+09 | 0.00 | 0.00 |
October | 0.521220E+09 | 0.874222E+09 | 0.710663E+09 | 0.222227E+09 | 0.488436E+09 | 0.00 | 0.00 |
November | 0.153168E+09 | 0.137040E+10 | 0.427515E+09 | 0.111258E+09 | 0.316257E+09 | 0.00 | 0.00 |
December | 41491015.27 | 0.246658E+10 | 0.385463E+09 | 0.103669E+09 | 0.281794E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.114271E+11 | 0.135340E+11 | 0.125925E+11 | 0.461434E+10 | 0.797820E+10 | 0.00 | 0.00 |
Minimum of Months | 41491015.27 | 0.335843E+09 | 0.385463E+09 | 0.103669E+09 | 0.281794E+09 | 0.00 | 0.00 |
Maximum of Months | 0.206522E+10 | 0.254648E+10 | 0.174557E+10 | 0.667443E+09 | 0.107813E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.314255E+09 | 0.663852E+11 | 0.706745E+09 | 0.251420E+09 | 0.455325E+09 | 0.00 | 0.00 |
February | 0.317872E+10 | 0.437750E+11 | 0.112637E+10 | 0.521732E+09 | 0.604639E+09 | 0.00 | 0.00 |
March | 0.721362E+10 | 0.295755E+11 | 0.178768E+10 | 0.101158E+10 | 0.776105E+09 | 0.00 | 0.00 |
April | 0.127226E+11 | 0.115833E+11 | 0.251552E+10 | 0.158256E+10 | 0.932962E+09 | 0.00 | 0.00 |
May | 0.167431E+11 | 0.448059E+10 | 0.318856E+10 | 0.178814E+10 | 0.140042E+10 | 0.00 | 0.00 |
June | 0.168249E+11 | 0.446475E+10 | 0.325636E+10 | 0.187352E+10 | 0.138284E+10 | 0.00 | 0.00 |
July | 0.166096E+11 | 0.778024E+10 | 0.343902E+10 | 0.204680E+10 | 0.139222E+10 | 0.00 | 0.00 |
August | 0.115547E+11 | 0.689270E+10 | 0.273987E+10 | 0.154325E+10 | 0.119662E+10 | 0.00 | 0.00 |
September | 0.882678E+10 | 0.547474E+10 | 0.192851E+10 | 0.997484E+09 | 0.931024E+09 | 0.00 | 0.00 |
October | 0.475047E+10 | 0.844814E+10 | 0.114915E+10 | 0.440861E+09 | 0.708293E+09 | 0.00 | 0.00 |
November | 0.169499E+10 | 0.220769E+11 | 0.666639E+09 | 0.207193E+09 | 0.459446E+09 | 0.00 | 0.00 |
December | 89181698.80 | 0.617629E+11 | 0.548160E+09 | 0.143161E+09 | 0.404998E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100523E+12 | 0.272700E+12 | 0.230526E+11 | 0.124077E+11 | 0.106449E+11 | 0.00 | 0.00 |
Minimum of Months | 89181698.80 | 0.446475E+10 | 0.548160E+09 | 0.143161E+09 | 0.404998E+09 | 0.00 | 0.00 |
Maximum of Months | 0.168249E+11 | 0.663852E+11 | 0.343902E+10 | 0.204680E+10 | 0.140042E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.110824E+10 | -0.102007E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -88172502.7 | 58.99 | 0.00 | 0.00 |
February | 0.103786E+10 | -958355750.0 | 0.00 | 0.00 | 672.00 | 0.00 | -79500307.6 | 58.99 | 0.00 | 0.00 |
March | 0.120331E+10 | -0.111573E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -87574439.3 | 58.99 | 0.00 | 0.00 |
April | 0.108918E+10 | -0.100535E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -83838834.8 | 58.99 | 0.00 | 0.00 |
May | 0.107304E+10 | -993230464.7 | 0.00 | 0.00 | 744.00 | 0.00 | -79808132.8 | 58.99 | 0.00 | 0.00 |
June | 0.100440E+10 | -930609544.9 | 0.00 | 0.00 | 720.00 | 0.00 | -73788250.5 | 58.99 | 0.00 | 0.00 |
July | 0.926261E+09 | -852035047.3 | 0.00 | 0.00 | 744.00 | 0.00 | -74225782.2 | 58.99 | 0.00 | 0.00 |
August | 0.963593E+09 | -888786978.6 | 0.00 | 0.00 | 744.00 | 0.00 | -74806451.5 | 58.99 | 0.00 | 0.00 |
September | 0.905590E+09 | -830468918.0 | 0.00 | 0.00 | 720.00 | 0.00 | -75121153.4 | 58.99 | 0.00 | 0.00 |
October | 0.949963E+09 | -864899042.1 | 0.00 | 0.00 | 744.00 | 0.00 | -85064396.4 | 58.99 | 0.00 | 0.00 |
November | 0.964423E+09 | -879472372.6 | 0.00 | 0.00 | 720.00 | 0.00 | -84950276.1 | 58.99 | 0.00 | 0.00 |
December | 0.105967E+10 | -971526280.8 | 0.00 | 0.00 | 744.00 | 0.00 | -88143945.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.122855E+11 | -0.113105E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -974994472.4 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.905590E+09 | -0.111573E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -88172502.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.120331E+10 | -830468918.0 | 0.00 | 0.00 | 744.00 | 0.00 | -73788250.5 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 243.33 | 0.96 | 0.88 | 08-JAN-11:20 | 114.13 | 8.46 | 0.00 | 28.67 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 265.33 | 0.95 | 0.88 | 02-FEB-11:09 | 142.08 | 9.75 | 0.00 | 64.50 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 254.17 | 0.94 | 0.88 | 02-MAR-10:39 | 153.72 | 10.03 | 0.00 | 98.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.33 | 0.93 | 0.88 | 01-APR-10:39 | 181.17 | 10.57 | 0.00 | 142.67 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 437.50 | 0.92 | 0.88 | 01-MAY-15:09 | 885.69 | 12.13 | 0.00 | 258.83 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 401.83 | 0.91 | 0.88 | 01-JUN-07:00 | 372.05 | 12.47 | 1.83 | 266.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 409.17 | 0.91 | 0.88 | 01-JUL-07:00 | 962.83 | 13.64 | 27.67 | 272.33 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 352.83 | 0.91 | 0.88 | 01-AUG-07:00 | 260.66 | 12.27 | 0.00 | 222.50 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.17 | 0.93 | 0.88 | 02-SEP-09:20 | 195.16 | 11.13 | 0.00 | 139.67 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 299.00 | 0.94 | 0.88 | 01-OCT-09:50 | 159.28 | 10.11 | 0.00 | 94.50 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 255.50 | 0.96 | 0.88 | 01-NOV-10:09 | 119.29 | 8.86 | 0.00 | 21.83 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 226.33 | 0.96 | 0.88 | 04-DEC-10:30 | 110.62 | 8.36 | 0.00 | 8.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3785.50 | 0.93 | 357.01 | 10.98 | 29.50 | 1617.83 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 226.33 | 0.91 | 0.88 | 110.62 | 8.36 | 0.00 | 8.33 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 437.50 | 0.96 | 0.88 | 962.83 | 13.64 | 27.67 | 272.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.83 | 0.78 | 01-JAN-13:50 | 646.80 | 22.28 | 71.83 | 124.17 | 725.63 | 22.21 | 105.83 | 182.33 |
February | 265.33 | 0.82 | 0.78 | 01-FEB-12:30 | 1185.92 | 23.00 | 91.83 | 161.67 | 1139.73 | 24.07 | 143.83 | 218.83 |
March | 254.17 | 0.82 | 0.78 | 02-MAR-10:39 | 859.18 | 20.11 | 58.17 | 190.50 | 2755.20 | 26.51 | 159.50 | 279.50 |
April | 296.33 | 0.82 | 0.78 | 01-APR-10:39 | 464.24 | 17.50 | 26.67 | 217.83 | 3364.39 | 25.87 | 178.33 | 318.00 |
May | 437.50 | 0.80 | 0.78 | 01-MAY-12:20 | 524.27 | 17.56 | 7.50 | 321.83 | 2603.07 | 23.74 | 233.33 | 389.83 |
June | 401.83 | 0.80 | 0.78 | 01-JUN-05:30 | 579.19 | 17.58 | 17.00 | 351.67 | 2831.81 | 23.15 | 215.83 | 404.00 |
July | 409.17 | 0.80 | 0.78 | 01-JUL-05:40 | 582.29 | 17.95 | 27.00 | 355.50 | 3054.85 | 24.00 | 227.33 | 406.67 |
August | 352.83 | 0.80 | 0.78 | 01-AUG-07:49 | 566.81 | 18.36 | 41.00 | 280.00 | 2685.95 | 25.01 | 210.83 | 356.67 |
September | 344.17 | 0.81 | 0.78 | 01-SEP-13:09 | 607.41 | 18.57 | 51.83 | 217.17 | 2275.53 | 25.15 | 191.17 | 294.17 |
October | 299.00 | 0.82 | 0.78 | 01-OCT-08:39 | 827.90 | 21.46 | 80.50 | 174.17 | 1312.69 | 24.17 | 157.17 | 248.17 |
November | 255.50 | 0.83 | 0.78 | 01-NOV-09:50 | 531.67 | 21.54 | 79.17 | 112.00 | 768.23 | 22.73 | 105.50 | 188.50 |
December | 226.33 | 0.84 | 0.78 | 01-DEC-10:00 | 451.93 | 20.46 | 52.17 | 84.17 | 612.06 | 19.95 | 47.00 | 166.50 |
Annual Sum or Average | 3785.50 | 0.81 | 640.09 | 19.37 | 604.67 | 2590.67 | 2155.88 | 23.97 | 1975.67 | 3453.17 | ||
Minimum of Months | 226.33 | 0.80 | 0.78 | 451.93 | 17.50 | 7.50 | 84.17 | 612.06 | 19.95 | 47.00 | 166.50 | |
Maximum of Months | 437.50 | 0.84 | 0.78 | 1185.92 | 23.00 | 91.83 | 355.50 | 3364.39 | 26.51 | 233.33 | 406.67 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.170480E+11 | 29306.84 | 01-JAN-00:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129524E+11 | 29306.84 | 01-FEB-01:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114666E+11 | 29306.84 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.542825E+10 | 29306.84 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.827150E+09 | 29306.84 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14149984.21 | 15579.72 | 01-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.208071E+09 | 29306.84 | 23-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.285580E+10 | 29306.84 | 03-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.735588E+10 | 29306.84 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150673E+11 | 29306.84 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.732237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.170480E+11 | 29306.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.689182E+11 | 86742.66 | 01-JAN-00:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.498405E+11 | 86742.66 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.371874E+11 | 86742.66 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137753E+11 | 86742.66 | 01-APR-18:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.482725E+09 | 61122.23 | 01-MAY-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.603736E+10 | 86742.66 | 30-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.279892E+11 | 86742.66 | 04-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.642936E+11 | 86742.66 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.268524E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.689182E+11 | 86742.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.263747E+12 | 210276.34 | 04-JAN-01:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.187357E+12 | 210276.34 | 12-FEB-22:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122500E+12 | 153729.86 | 15-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.302889E+11 | 86451.88 | 04-APR-18:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.377046E+09 | 22273.02 | 01-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.584185E+10 | 43764.07 | 31-OCT-20:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.940751E+11 | 125423.20 | 25-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.245581E+12 | 208904.92 | 18-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.949768E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.263747E+12 | 210276.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.115628E+10 | 0.102671E+10 | 19491.95 | 25-MAY-20:31 | 16078.76 | 0.00 |
June | 0.00 | 0.00 | 0.391004E+10 | 0.305113E+10 | 21970.38 | 19-JUN-17:21 | 10892.17 | 0.00 |
July | 0.00 | 0.00 | 0.681373E+10 | 0.511125E+10 | 22515.76 | 03-JUL-22:25 | 10992.68 | 0.00 |
August | 0.00 | 0.00 | 0.486705E+10 | 0.362147E+10 | 21880.03 | 31-AUG-18:35 | 12160.77 | 0.00 |
September | 0.00 | 0.00 | 0.535763E+09 | 0.458703E+09 | 20666.64 | 01-SEP-00:45 | 10265.75 | 0.00 |
October | 0.00 | 0.00 | 386562.46 | 386562.46 | 211.15 | 19-OCT-15:00 | 211.15 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.172833E+11 | 0.132696E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.681373E+10 | 0.511125E+10 | 22515.76 | 16078.76 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.458361E+09 | 0.364623E+09 | 13751.71 | 25-MAY-15:00 | 10446.49 | 0.00 |
June | 0.00 | 0.00 | 0.463685E+10 | 0.321060E+10 | 60223.98 | 25-JUN-12:05 | 34774.56 | 0.00 |
July | 0.00 | 0.00 | 0.987212E+10 | 0.671556E+10 | 62960.47 | 23-JUL-08:55 | 30093.59 | 0.00 |
August | 0.00 | 0.00 | 0.461436E+10 | 0.308480E+10 | 58859.01 | 09-AUG-18:13 | 37112.40 | 0.00 |
September | 0.00 | 0.00 | 0.367638E+09 | 0.267036E+09 | 55602.21 | 01-SEP-17:32 | 39846.30 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.199493E+11 | 0.136426E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.987212E+10 | 0.671556E+10 | 62960.47 | 39846.30 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.132844E+10 | 0.08 | 498.10 | 01-JAN-00:01 | 0.08 |
February | 0.114345E+10 | 0.08 | 498.10 | 01-FEB-00:01 | 0.08 |
March | 0.114284E+10 | 0.07 | 498.10 | 01-MAR-00:03 | 0.08 |
April | 0.512172E+09 | 0.03 | 498.10 | 01-APR-00:03 | 0.08 |
May | 18678892.54 | 0.00 | 498.10 | 01-MAY-00:03 | 0.08 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.244619E+09 | 0.01 | 498.10 | 10-OCT-00:30 | 0.08 |
November | 0.107504E+10 | 0.07 | 498.10 | 01-NOV-00:10 | 0.08 |
December | 0.133412E+10 | 0.08 | 498.10 | 01-DEC-00:02 | 0.08 |
Annual Sum or Average | 0.679936E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.133412E+10 | 0.08 | 498.10 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.137746E+10 | 0.77 | 1155.48 | 03-JAN-11:00 | 0.95 |
February | 0.122936E+10 | 0.74 | 1155.48 | 04-FEB-11:40 | 0.95 |
March | 0.136572E+10 | 0.67 | 1155.48 | 07-MAR-13:10 | 0.95 |
April | 0.120721E+10 | 0.50 | 1155.48 | 01-APR-13:50 | 0.95 |
May | 0.121850E+10 | 0.39 | 1155.48 | 01-MAY-13:00 | 0.95 |
June | 0.127565E+10 | 0.42 | 1155.48 | 01-JUN-08:50 | 0.94 |
July | 0.133951E+10 | 0.46 | 1155.48 | 01-JUL-06:30 | 0.94 |
August | 0.140187E+10 | 0.47 | 1155.48 | 03-AUG-15:20 | 0.94 |
September | 0.116590E+10 | 0.38 | 1155.48 | 05-SEP-11:40 | 0.94 |
October | 0.116774E+10 | 0.38 | 1155.48 | 02-OCT-06:20 | 0.94 |
November | 0.118242E+10 | 0.55 | 1155.48 | 01-NOV-07:40 | 0.94 |
December | 0.135245E+10 | 0.76 | 1155.48 | 04-DEC-10:00 | 0.95 |
Annual Sum or Average | 0.152838E+11 | 0.54 | |||
Minimum of Months | 0.116590E+10 | 0.38 | 1155.48 | 0.94 | |
Maximum of Months | 0.140187E+10 | 0.77 | 1155.48 | 0.95 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.251815E+10 | 0.68 | 2377.48 | 01-JAN-00:04 | 0.92 |
February | 0.202840E+10 | 0.65 | 2377.48 | 01-FEB-00:01 | 0.92 |
March | 0.189097E+10 | 0.60 | 2377.48 | 01-MAR-00:03 | 0.92 |
April | 0.128686E+10 | 0.46 | 2377.48 | 01-APR-18:23 | 0.92 |
May | 0.992023E+09 | 0.23 | 1675.26 | 01-MAY-04:13 | 0.92 |
June | 0.100622E+10 | 0.23 | 2377.48 | 29-JUN-17:08 | 0.90 |
July | 0.981630E+09 | 0.22 | 2377.48 | 01-JUL-17:19 | 0.91 |
August | 0.102160E+10 | 0.22 | 2135.72 | 08-AUG-17:10 | 0.86 |
September | 0.942055E+09 | 0.21 | 950.99 | 01-SEP-14:10 | 0.55 |
October | 0.109597E+10 | 0.37 | 2377.48 | 30-OCT-04:12 | 0.92 |
November | 0.158567E+10 | 0.59 | 2377.48 | 04-NOV-05:01 | 0.92 |
December | 0.243119E+10 | 0.67 | 2377.48 | 01-DEC-00:02 | 0.92 |
Annual Sum or Average | 0.177807E+11 | 0.43 | |||
Minimum of Months | 0.942055E+09 | 0.21 | 950.99 | 0.55 | |
Maximum of Months | 0.251815E+10 | 0.68 | 2377.48 | 0.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.137746E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.122936E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.136572E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.120721E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.147667E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.213233E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.279154E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.243607E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.128158E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.116783E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.118242E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.135245E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.190006E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.116783E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.279154E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.251815E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.202840E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.189097E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.128686E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.111178E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.214470E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.333949E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.213085E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.103037E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.109597E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.158567E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.243119E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.225944E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.103037E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.333949E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.137746E+10 | 0.00 | 0.170480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122936E+10 | 0.00 | 0.129524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136572E+10 | 0.00 | 0.114666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120721E+10 | 0.00 | 0.542825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121850E+10 | 0.115628E+10 | 0.827150E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.127565E+10 | 0.391004E+10 | 14149984.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133951E+10 | 0.681373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140187E+10 | 0.486705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.116590E+10 | 0.535763E+09 | 0.208071E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.116774E+10 | 386562.46 | 0.285580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118242E+10 | 0.00 | 0.735588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135245E+10 | 0.00 | 0.150673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152838E+11 | 0.172833E+11 | 0.732237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.116590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140187E+10 | 0.681373E+10 | 0.170480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.251815E+10 | 0.00 | 0.689182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202840E+10 | 0.00 | 0.498405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189097E+10 | 0.00 | 0.371874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128686E+10 | 0.00 | 0.137753E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.992023E+09 | 0.458361E+09 | 0.482725E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100622E+10 | 0.462336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.981630E+09 | 0.966822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.102160E+10 | 0.455481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.942055E+09 | 0.365748E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109597E+10 | 0.00 | 0.603736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158567E+10 | 0.00 | 0.279892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.243119E+10 | 0.00 | 0.642936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177807E+11 | 0.196705E+11 | 0.268524E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.942055E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.251815E+10 | 0.966822E+10 | 0.689182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.137746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121850E+10 | 0.00 | 0.00 | 0.00 | 0.258171E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.127565E+10 | 0.00 | 0.00 | 0.00 | 0.856680E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133951E+10 | 0.00 | 0.00 | 0.00 | 0.145203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140187E+10 | 0.00 | 0.00 | 0.00 | 0.103420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.116590E+10 | 0.00 | 0.00 | 0.00 | 0.115679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.116774E+10 | 0.00 | 0.00 | 0.00 | 91075.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152838E+11 | 0.00 | 0.00 | 0.00 | 0.371685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.116590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140187E+10 | 0.00 | 0.00 | 0.00 | 0.145203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.251815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.992023E+09 | 0.00 | 0.00 | 0.00 | 0.119760E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100622E+10 | 0.00 | 0.00 | 0.00 | 0.113848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.981630E+09 | 0.00 | 0.00 | 0.00 | 0.235786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.102160E+10 | 0.00 | 0.00 | 0.00 | 0.110924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.942055E+09 | 0.00 | 0.00 | 0.00 | 88312450.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.243119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177807E+11 | 0.00 | 0.00 | 0.00 | 0.481366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.942055E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.251815E+10 | 0.00 | 0.00 | 0.00 | 0.235786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425219E+10 | 0.00 | 0.00 | 0.12 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324536E+10 | 0.00 | 0.00 | 0.13 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315505E+10 | 0.00 | 0.00 | 0.13 |
April | 0.171036E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164323E+10 | 0.00 | 0.00 | 0.13 |
May | 0.508976E+09 | 35782602.45 | 0.00 | 1044482.16 | 0.00 | 0.208365E+09 | 0.759462E+09 | 0.00 | 0.29 |
June | 0.107501E+09 | 0.367700E+09 | 0.00 | 2873128.92 | 1313262.78 | 0.00 | 0.175829E+10 | 0.00 | 0.59 |
July | 14736265.15 | 0.675559E+09 | 0.00 | 4668938.17 | 418552.28 | 0.00 | 0.173796E+10 | 0.00 | 0.63 |
August | 42862158.53 | 0.312903E+09 | 0.00 | 5304788.46 | 0.00 | 0.00 | 0.259099E+10 | 0.00 | 0.74 |
September | 0.554895E+09 | 11215718.64 | 0.00 | 2230310.08 | 0.00 | 38965049.22 | 0.196669E+10 | 0.00 | 0.40 |
October | 0.529996E+09 | 0.00 | 0.00 | 34705.76 | 0.00 | 0.118008E+10 | 86113599.04 | 0.00 | 0.14 |
November | 17332726.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232686E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393118E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.194733E+10 | 0.140316E+10 | 0.00 | 16156353.56 | 1731815.06 | 0.199813E+11 | 0.889950E+10 | 0.00 | 0.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.554895E+09 | 0.675559E+09 | 0.00 | 5304788.46 | 1313262.78 | 0.425219E+10 | 0.259099E+10 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.357254E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142585E+11 | 0.00 | 0.00 | 0.17 |
February | 0.125476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.943184E+10 | 0.00 | 0.00 | 0.17 |
March | 0.291625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694792E+10 | 0.00 | 0.00 | 0.19 |
April | 0.391737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121352E+10 | 0.00 | 0.00 | 0.18 |
May | 0.309183E+10 | 17397989.35 | 0.00 | 576011.33 | 1905057.89 | 0.00 | 0.381511E+09 | 0.00 | 0.20 |
June | 0.224950E+10 | 0.713142E+09 | 0.00 | 1810454.59 | 0.00 | 0.00 | 0.997583E+09 | 0.00 | 0.25 |
July | 0.584654E+09 | 0.107803E+10 | 0.00 | 6311513.29 | 0.00 | 0.00 | 0.269028E+10 | 0.00 | 0.33 |
August | 0.186829E+10 | 0.433572E+09 | 0.00 | 4581936.99 | 0.00 | 0.00 | 0.253426E+10 | 0.00 | 0.31 |
September | 0.423667E+10 | 2125710.31 | 0.00 | 810843.02 | 0.00 | 0.00 | 0.411178E+09 | 0.00 | 0.20 |
October | 0.456541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380309E+09 | 0.00 | 0.00 | 0.17 |
November | 0.303706E+10 | 0.00 | 0.00 | 0.00 | 65131.64 | 0.391950E+10 | 0.00 | 0.00 | 0.17 |
December | 0.308817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129655E+11 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.283878E+11 | 0.224427E+10 | 0.00 | 14090759.22 | 1970189.53 | 0.491171E+11 | 0.701481E+10 | 0.00 | 0.21 |
Minimum of Months | 0.308817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.456541E+10 | 0.107803E+10 | 0.00 | 6311513.29 | 1905057.89 | 0.142585E+11 | 0.269028E+10 | 0.00 | 0.33 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:41:44
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.290793E+12 | 0.158411E+12 | 0.00 | 0.188680E+11 | 0.100700E+12 |
February | 0.457873E+12 | 0.128119E+12 | 0.00 | 0.139320E+11 | 0.730446E+11 |
March | 0.670250E+12 | 0.879209E+11 | 0.00 | 0.130192E+11 | 0.518551E+11 |
April | 0.851823E+12 | 0.523930E+11 | 0.00 | 0.694516E+10 | 0.163117E+11 |
May | 0.102662E+13 | 0.263592E+11 | 0.00 | 0.490370E+10 | 0.269788E+10 |
June | 0.105508E+13 | 0.229703E+11 | 0.00 | 0.404798E+10 | 0.105491E+11 |
July | 0.109656E+13 | 0.321907E+11 | 0.00 | 0.343821E+10 | 0.204957E+11 |
August | 0.915765E+12 | 0.348356E+11 | 0.00 | 0.648814E+10 | 0.116248E+11 |
September | 0.660260E+12 | 0.421108E+11 | 0.00 | 0.722717E+10 | 0.120988E+10 |
October | 0.347059E+12 | 0.385736E+11 | 0.00 | 0.674194E+10 | 0.574624E+10 |
November | 0.163247E+12 | 0.812276E+11 | 0.00 | 0.930068E+10 | 0.392343E+11 |
December | 0.187793E+12 | 0.155647E+12 | 0.00 | 0.172055E+11 | 0.939675E+11 |
Annual Sum or Average | 0.772312E+13 | 0.860759E+12 | 0.00 | 0.112118E+12 | 0.427437E+12 |
Minimum of Months | 0.163247E+12 | 0.229703E+11 | 0.00 | 0.343821E+10 | 0.120988E+10 |
Maximum of Months | 0.109656E+13 | 0.158411E+12 | 0.00 | 0.188680E+11 | 0.100700E+12 |