Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:42
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2023-10-16 10:42:55
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:55
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1877.36 | 388.28 | 388.28 |
Net Site Energy | 1877.36 | 388.28 | 388.28 |
Total Source Energy | 2807.55 | 580.66 | 580.66 |
Net Source Energy | 2807.55 | 580.66 | 580.66 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1506.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 113.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 63.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 28.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 28.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 370.85 | 1506.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1506.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 1.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 113.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 63.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 28.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 28.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1506.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 113.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 63.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 28.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 28.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 36.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 11.89 | 311.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 76.70 | 311.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 36.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 11.89 | 311.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 76.70 | 311.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 370.852 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 370.852 | 100.00 |
Total On-Site and Utility Electric Sources | 370.852 | 100.00 |
Total Electricity End Uses | 370.852 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 128.00 |
Time Setpoint Not Met During Occupied Cooling | 0.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2948.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:55
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:42 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 6.9682 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 7.4271 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.5521 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8362 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8362 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 6.9682 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 7.4271 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.5521 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.8362 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.8362 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.8362 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:55
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 11-JAN-15:50 | 28-JAN-17:10 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 232296.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 9093.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5520.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2278.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2689.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 29617.44 | 232296.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 232296.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 9093.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5520.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2278.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 2689.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:55
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1633.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 358.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 202.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 88.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 89.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1174.49 | 1633.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 337.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 74.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 41.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 18.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 242.91 | 337.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 337.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 74.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 41.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 18.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 242.91 | 337.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:55
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.850799 |
ZONE2 FINE STORAGE DIRECT AIR | 1.29 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 2.55 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 2.55 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 102865.05 |
PSZ-OFFICE HEATING COIL | 26873.36 |
PSZ-FINE STORAGE HEATING COIL | 66598.52 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 102865.04 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.850799 | 0.850799 | 0.850799 | 0.850799 | 0.850799 | 0.850799 | 1.00 | 1.00 | 0.850799 |
PSZ-FINE STORAGE | 1.29 | 1.29 | 1.29 | 1.29 | 1.29 | 1.29 | 1.00 | 1.00 | 1.29 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 0.850799 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 1.29 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.850799 | 941.97 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.29 | 1427.17 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.850799 | 0.850799 | 0.850799 | 0.850799 | 14083.74 | 26873.36 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 1.29 | 1.29 | 1.29 | 0.850767 | 23857.43 | 66598.52 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.850800 | 0.425399 | 0.567200 | 14083.74 | 7041.87 | 0.800660 | 0.800660 |
PSZ-FINE STORAGE COOLING COIL | 1.29 | 0.644520 | 0.859360 | 23857.43 | 11928.72 | 0.800830 | 0.800830 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:55
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:55
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:55
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 6.968 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 15.042 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 7.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.427 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.552 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 6.111 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1650.627 | 6.968 | 129.474 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1650.627 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 10348.979 | 7.427 | 344.966 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10348.979 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 11383.888 | 3.552 | 164.984 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11383.888 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.1507 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.2163 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.3014 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.4322 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1413 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.5841E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.5469E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.4322 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.636 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.622 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 3.219 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.214 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.998 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 17.04 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 18.21 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.214 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.68857323E-13 | 0.53233684E-18 | 0.39256197E-18 | 0.0000000 |
2 | 1 | -5.2161015 | 0.66198115E-04 | -0.10631122E-03 | 0.13200917E-13 |
3 | 0 | 5.3667923 | 0.15062465 | 0.15079716 | |
4 | 2 | 0.18741198E-13 | -0.13599760E-18 | 0.18147593E-18 | 0.0000000 |
5 | 1 | -5.2160601 | 0.51384690E-04 | -0.74050972E-04 | 0.35929797E-14 |
6 | 0 | 5.4323994 | 0.21628790 | 0.21641333 | |
7 | 4 | 0.81851857E-12 | -0.56297919E-16 | 0.55082493E-14 | 0.11126616E-15 |
8 | 3 | -0.39700657E-03 | 0.21474572E-06 | -0.57709306E-04 | 0.15704290E-12 |
9 | 2 | 1.7684693 | 0.46346224E-02 | 1.1624592 | -0.76113193E-04 |
10 | 1 | -7.0908904 | 0.11909837 | -17.238334 | 0.33895947 |
11 | 0 | 5.5220737 | 0.75522404E-01 | 16.275188 | |
12 | 4 | 0.79186034E-12 | 0.10405078E-15 | -0.20960309E-14 | 0.11445272E-15 |
13 | 3 | -0.38819576E-03 | 0.30481201E-06 | -0.56344247E-04 | 0.15193845E-12 |
14 | 2 | 1.7477700 | 0.66393353E-02 | 1.1467116 | -0.74423695E-04 |
15 | 1 | -7.1178476 | 0.17160399 | -17.138090 | 0.33498210 |
16 | 0 | 5.6579463 | 0.10923685 | 16.278915 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.30042996E-08 | -0.19492532E-14 | 0.18571942E-14 | -0.50265421E-16 |
55 | 6 | 0.40686135E-05 | 0.27025218E-08 | 0.31944093E-02 | -0.26797382E-04 |
56 | 5 | -0.28598357E-03 | 0.15982348E-05 | -0.22398257 | 0.19584275E-02 |
57 | 4 | 0.65354345E-02 | 0.72696005E-04 | 4.8338424 | -0.45306284E-01 |
58 | 3 | -0.57256805E-01 | 0.57768437E-03 | -38.045688 | 0.39892203 |
59 | 2 | 0.20312160 | 0.96045137E-03 | 116.53119 | -1.4185711 |
60 | 1 | -0.29305691 | 0.29236276E-03 | -143.93511 | 2.0494970 |
61 | 0 | 0.14285049 | 0.70905046E-05 | 60.838472 | |
62 | 7 | -0.73310212E-08 | 0.16277859E-15 | -0.15558641E-14 | 0.17403554E-16 |
63 | 6 | 0.21213446E-05 | 0.11327280E-08 | 0.32008460E-02 | -0.26851379E-04 |
64 | 5 | -0.12816801E-03 | 0.66411688E-06 | -0.22434819 | 0.19616548E-02 |
65 | 4 | 0.27852559E-02 | 0.30072908E-04 | 4.8399282 | -0.45364789E-01 |
66 | 3 | -0.23934818E-01 | 0.23808113E-03 | -38.080046 | 0.39930184 |
67 | 2 | 0.84241938E-01 | 0.39442809E-03 | 116.59803 | -1.4194653 |
68 | 1 | -0.12110434 | 0.11951395E-03 | -143.97445 | 2.0501436 |
69 | 0 | 0.58923671E-01 | 0.28881054E-05 | 60.838472 | |
70 | 7 | -0.78336681E-08 | 0.23380828E-15 | -0.37470831E-14 | 0.17001158E-16 |
71 | 6 | 0.20573783E-05 | 0.10635783E-08 | 0.32011355E-02 | -0.26853807E-04 |
72 | 5 | -0.12166809E-03 | 0.62270931E-06 | -0.22436462 | 0.19617998E-02 |
73 | 4 | 0.26229018E-02 | 0.28177105E-04 | 4.8402013 | -0.45367414E-01 |
74 | 3 | -0.22467346E-01 | 0.22293819E-03 | -38.081586 | 0.39931887 |
75 | 2 | 0.78971204E-01 | 0.36912476E-03 | 116.60102 | -1.4195054 |
76 | 1 | -0.11345740 | 0.11176675E-03 | -143.97621 | 2.0501725 |
77 | 0 | 0.55185584E-01 | 0.26976542E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.20960309E-14 | 0.10405078E-15 | 0.79186034E-12 | 0.11445272E-15 |
85 | 3 | -0.56344247E-04 | 0.30481201E-06 | -0.38819576E-03 | 0.15193845E-12 |
86 | 2 | 1.1467116 | 0.66393353E-02 | 1.7477700 | -0.74423695E-04 |
87 | 1 | -17.138090 | 0.17160399 | -7.1178476 | 0.33498210 |
88 | 0 | 16.278915 | 0.10923685 | 5.6579463 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.262_SHGC_SOUTH_0.399 | 34 | 1 | VerySmooth | 1.488 | 1.488 | 1.000 | 0.400 | ||
2 | NONRESWINDOW_U_0.262_SHGC_NORTH_0.399 | 35 | 1 | VerySmooth | 1.488 | 1.488 | 1.000 | 0.400 | ||
3 | NONRESWINDOW_U_0.262_SHGC_EAST_0.399 | 36 | 1 | VerySmooth | 1.488 | 1.488 | 1.000 | 0.400 | ||
4 | NONRESWINDOW_U_0.262_SHGC_WEST_0.399 | 37 | 1 | VerySmooth | 1.488 | 1.488 | 1.000 | 0.400 | ||
5 | SKYLIGHT_U_0.41_SHGC_0.55 | 38 | 1 | VerySmooth | 2.330 | 2.330 | 1.000 | 0.551 | ||
6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 39 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.555 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 4.47720E-002 | 0.31332 | 0.49252 | 0.49252 | 0.39900 | 0.13770 | 0.17988 | 0.00000 | 0.84000 | 0.84000 | 9.00957E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 4.47720E-002 | 0.31332 | 0.49252 | 0.49252 | 0.39900 | 0.13770 | 0.17988 | 0.00000 | 0.84000 | 0.84000 | 9.00957E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 4.47720E-002 | 0.31332 | 0.49252 | 0.49252 | 0.39900 | 0.13770 | 0.17988 | 0.00000 | 0.84000 | 0.84000 | 9.00957E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 4.47720E-002 | 0.31332 | 0.49252 | 0.49252 | 0.39900 | 0.13770 | 0.17988 | 0.00000 | 0.84000 | 0.84000 | 9.00957E-002 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 3.14065E-002 | 0.47116 | 0.33556 | 0.33556 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.12199 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.41263 | 0.18041 | 0.18041 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE3 BULK STORAGE | 10 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.099 | 0.553 | 0.552 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.264 | 7.065E-004 | 4.615E-004 | 0.231 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4173E-004 |
2 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0766E-004 |
3 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8710E-004 |
4 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
5 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9714E-004 |
6 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9073E-004 |
7 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0026E-003 |
8 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
9 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2553E-003 |
10 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0764E-003 |
11 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1348E-003 |
12 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4690E-003 |
13 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8955E-004 |
14 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0972E-004 |
15 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1634E-003 |
16 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
17 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4574E-004 |
18 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2310E-004 |
19 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4733E-004 |
20 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
21 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4434E-004 |
22 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2123E-004 |
23 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4422E-004 |
24 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
25 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5499E-004 |
26 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9543E-004 |
27 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3279E-003 |
28 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
29 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6327E-003 |
30 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5713E-003 |
31 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0429E-003 |
32 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4690E-003 |
33 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6460E-004 |
34 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.4759E-004 |
35 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5512E-003 |
36 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
37 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1556E-004 |
38 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0753E-004 |
39 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1965E-004 |
40 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
41 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.9288E-003 |
42 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 7.2258E-004 |
43 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.4257E-003 |
44 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.4941E-004 |
45 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 4.4321E-003 |
46 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.5339E-004 |
47 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.8465E-003 |
48 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 4.9717E-004 |
49 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 7.3562E-004 |
50 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 7.2667E-003 |
51 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.8474E-004 |
52 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 6.2701E-003 |
53 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.6079E-004 |
54 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.0611E-003 |
55 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.9163E-004 |
56 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.8253E-003 |
57 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 6.7133E-003 |
58 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 4.7747E-004 |
59 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 5.3495E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.8751E-004 |
61 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.4599E-003 |
62 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.6461E-004 |
63 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.5755E-003 |
64 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.0321E-004 |
65 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 7.5526E-003 |
66 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.8009E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.8162E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.8901E-004 |
69 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.8941E-003 |
70 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.6298E-004 |
71 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.5754E-003 |
72 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.0321E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 8484.05382 | 10180.86458 | 0.70900 | 0.85080 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 25.97200 | 7.00497E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 10306.29174 | 12367.55009 | 0.29385 | 0.35262 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90000 | 6.45023E-005 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 16490.13875 | 19788.16650 | 1.07420 | 1.28904 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 26.99200 | 7.00652E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 29527.37842 | 35432.85411 | 0.70924 | 0.85109 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -41.90000 | 6.45023E-005 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 27.40000 | 7.00714E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 85720.86973 | 102865.04367 | 2.12759 | 2.55311 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 12312.06 | 0.85080 | 0.85080 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 15629.17 | 0.35262 | 0.35262 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 22766.54 | 1.28904 | 1.28904 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 53848.04 | 0.85109 | 0.85109 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.85080 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.28904 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.55311 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 2.55311 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 102865.04687 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 102865.04367 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.85080 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.85080 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.85080 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.85080 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.85080 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.85080 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.28904 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.28904 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.28904 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.28904 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.28904 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.28904 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.85080 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.28904 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.85080 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.85080 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 941.96932 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.85080 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.85080 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.85080 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.85080 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.85080 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.42540 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.56720 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 14083.74000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 7041.87000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 14083.74000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26873.35678 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 26873.35678 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.28904 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.28904 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1427.17262 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.28904 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.28904 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.28904 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.85077 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.28904 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.64452 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.85936 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23857.43000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11928.71500 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80083 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80083 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23857.43000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 66598.52191 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 66598.52191 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 13423.6 | 12.15 | 11.88 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 22856.8 | 11.66 | 11.39 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.4396203916 | 0.3830401551 | Pass | Pass | 2.3824399654 | 5.3326595167 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.7149307636 | 0.6413263338 | Pass | Pass | 0.7647592298 | 0.6795926357 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 1.3414211019E-005 | 1.9127028955E-005 | Pass | Pass | 2.8009741540E-002 | 2.7505951185E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:55
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4975.01 | 562.64 | 0.00 | 135.94 | 357.94 | 6031.55 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:55
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:55
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.288 | 0.301 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.288 | 0.301 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.138 | 0.141 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.288 | 0.301 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.288 | 0.301 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.288 | 0.301 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.288 | 0.301 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.288 | 0.301 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.058 | 0.058 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.148 | 0.151 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.406 | 0.432 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.406 | 0.432 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.406 | 0.432 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.054 | 0.055 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.210 | 0.216 | 3204.84 | 3189.98 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.392 | 0.432 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.392 | 0.432 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.262_SHGC_WEST_0.399 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.488 | 0.400 | 0.400 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.262_SHGC_WEST_0.399 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.488 | 0.400 | 0.400 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.262_SHGC_NORTH_0.399 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.488 | 0.400 | 0.400 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.262_SHGC_NORTH_0.399 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.488 | 0.400 | 0.400 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 2.756 | 0.471 | 0.469 | |||||||||||||||||
North Total or Average | 6.51 | 1.488 | 0.400 | 0.400 | |||||||||||||||||
Non-North Total or Average | 26.02 | 3.073 | 0.489 | 0.487 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:55
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:55
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 6.9682 | 236.88 | 1650.63 | LightsWired | LTG_SCH_OFFICE | 52.33 | 168.00 | 34.30 | 0.0000 | Y | 10.63 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 7.4271 | 1393.41 | 10348.98 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 25.09 | 0.0000 | Y | 48.75 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.5521 | 3204.84 | 11383.89 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 25.11 | 0.0000 | Y | 53.67 |
Interior Lighting Total | 4.8362 | 4835.13 | 23383.49 | 113.05 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.12 | 11383.89 | 1320.53 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.29 | 1650.63 | 478.68 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.10 | 1650.63 | 165.06 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 123.84 | AstronomicalClock | - | 44.84 | 44.84 | 1.04 | |
EXTERIOR_LIGHTS_B | 4305.62 | AstronomicalClock | - | 83.06 | 63.95 | 51.69 | |
EXTERIOR_LIGHTS_C | 1091.36 | AstronomicalClock | - | 83.06 | 54.03 | 11.07 | |
Exterior Lighting Total | 5520.82 | 63.80 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:55
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 14083.74 | 11276.29 | 2807.45 | 0.80 | 4.12 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23857.43 | 19105.75 | 4751.68 | 0.80 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 13423.6 | 12.15 | 11.88 | ||||
PSZ-FINE STORAGE COOLING COIL | 22856.8 | 11.66 | 11.39 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 102865.05 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 26873.36 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 66598.52 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.55 | 237.21 | 92.91 | 1.00 | 3.44 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 0.85 | 941.97 | 1107.16 | 1.00 | 1.45 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.29 | 1427.17 | 1107.16 | 1.00 | 1.35 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:55
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8484.05 | 10180.86 | 42.98 | 0.709 | 0.851 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00831 | 25.97 | 0.00700 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 16490.14 | 19788.17 | 14.20 | 1.074 | 1.289 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 26.70 | 26.70 | 0.00840 | 26.99 | 0.00701 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 0.00 | 29.40 | 0.00757 | 27.40 | 0.00701 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10306.29 | 12367.55 | 52.21 | 0.294 | 0.353 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00828 | -41.90 | 0.00006 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 29527.38 | 35432.85 | 25.43 | 0.709 | 0.851 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00770 | -41.90 | 0.00006 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 85720.87 | 102865.04 | 32.10 | 2.128 | 2.553 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00745 | -41.90 | 0.00006 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.85 | 0.85 | 0.35 | 0.35 | 0.8508 | 0.8508 | 0.8508 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.29 | 1.29 | 0.85 | 0.85 | 1.2890 | 1.2890 | 1.2890 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 102865.047 | 102865.047 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 102865.05 | 102865.05 | 2.553105 | 10.00 | 9.67 | 0.00744531 | 43.33 | 21.96 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 10.00 | 0.00744531 | 96.0762 | 102865.04 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 14083.740 | 11276.287 | 0.850800 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 7041.87 | 6865.06 | 0.567200 | 25.06 | 16.30 | 0.00815053 | 12.00 | 11.12 | 0.00800000 | 25.97 | 0.00700497 | 15.63 | 18.0333 | 23.90 | 0.00830707 | 44.3036 | 8484.05 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 26873.357 | 26873.357 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 26873.36 | 26873.36 | 0.850799 | 13.48 | 11.02 | 0.00729471 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 12.0222 | 21.10 | 0.00828272 | 52.3636 | 10306.29 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 23857.430 | 19105.746 | 1.289040 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 11928.72 | 11928.71 | 0.859360 | 27.78 | 17.07 | 0.00793671 | 12.00 | 11.05 | 0.00793671 | 27.20 | 0.00700683 | 16.07 | 49.4218 | 26.70 | 0.00839531 | 37.8990 | 16449.50 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 66598.522 | 66598.522 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 66598.52 | 66598.52 | 1.289041 | -3.37 | -3.37 | 0.00518474 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 32.9479 | 15.56 | 0.00770070 | 68.9962 | 29527.38 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:42:55
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 102865.047 | 102865.047 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 2.553105 | 3.02655125 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 102865.05 | 102865.05 | 1.0000 | 3.02655125 | 2.553105 | 10.00 | 9.67 | 0.00744531 | 28806.5 | 43.33 | 21.96 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 102865.05 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 10.00 | 0.00744531 | 10.00 | 0.00744531 | 96.0762 | 102865.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 14083.740 | 11276.287 | 0.850800 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9914 | 1004.8586 | 1.1854 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.850799 | 1.00857033 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | Sensible | 7041.87 | 6865.06 | 1.0000 | 0.67238117 | 0.567200 | 25.06 | 16.30 | 0.00815053 | 45949.1 | 12.00 | 11.12 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7041.87 | 25.97 | 0.00700497 | 15.63 | 0.10228463 | 18.0333 | 23.90 | 0.00830707 | 23.90 | 0.00830707 | 44.3036 | 8484.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26873.357 | 26873.357 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.850799 | 1.00857033 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 26873.36 | 26873.36 | 1.0000 | 1.00857033 | 0.850799 | 13.48 | 11.02 | 0.00729471 | 31975.6 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26873.36 | -41.90 | 0.00006450 | -41.90 | 0.10228463 | 12.0222 | 21.05 | 0.00828272 | 21.10 | 0.00828272 | 52.3636 | 10306.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23857.430 | 19105.746 | 1.289040 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5939 | 1004.8586 | 1.1854 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.289041 | 1.52807944 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 11928.72 | 11928.71 | 1.0000 | 1.01871911 | 0.859360 | 27.78 | 17.07 | 0.00793671 | 48173.0 | 12.00 | 11.05 | 0.00793671 | 32084.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11928.72 | 27.20 | 0.00700683 | 16.07 | 0.42471127 | 49.4218 | 26.70 | 0.00839531 | 26.70 | 0.00839531 | 37.8990 | 16449.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 66598.522 | 66598.522 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.289041 | 1.52807944 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 66598.52 | 66598.52 | 1.0000 | 1.52807944 | 1.289041 | -3.37 | -3.37 | 0.00518474 | 9545.5 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 66598.52 | -41.90 | 0.00006450 | -41.90 | 0.42471127 | 32.9479 | 15.56 | 0.00770070 | 15.56 | 0.00770070 | 68.9962 | 29527.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:55
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.29 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2691.83 | 3508.33 | 2688.00 |
ZONE2 FINE STORAGE | 2972.83 | 3443.67 | 2859.17 |
ZONE3 BULK STORAGE | 2999.00 | 3514.17 | 2946.00 |
Facility | 3062.67 | 3539.33 | 2948.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 188.67 | 0.17 | 81.33 | 0.17 |
ZONE2 FINE STORAGE | 696.83 | 0.00 | 30.83 | 0.00 |
ZONE3 BULK STORAGE | 115.33 | 0.00 | 38.17 | 0.00 |
Facility | 903.17 | 0.17 | 128.00 | 0.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:55
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.309 | 0.270 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.29 | 30.00 | 2953.02 | 0.433 | 0.146 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.28 | 69.00 | 35277.63 | 0.000 | 0.073 | 0.000 | 0.033 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.29 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.28 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:42:55
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.47 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.29 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.28 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.04 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1115720.76 | 0.00 | 1115720.76 | 1465120.67 | 2580841.43 | 3225648.14 | 5730.00 | 3030.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 4632295.56 | 0.00 | 4632295.56 | 4361427.52 | 8993723.07 | 13393694.68 | 5730.00 | 3030.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 10266576.17 | 10266576.17 | 20447806.03 | 30714382.19 | 30805497.77 | 8651.17 | 10.50 | 98.33 | 4375.33 |
Total Facility | 5748016.32 | 10266576.17 | 16014592.48 | 26274354.21 | 42288946.69 | 47424840.58 | 8717.83 | 3037.00 | 98.33 | 4375.33 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.0852 | 0.0000 | 0.0852 | 0.0746 | 0.1598 | 0.1023 | 606.00 | 3030.00 | 0.00 |
ZONE2 FINE STORAGE | 0.3539 | 0.0000 | 0.3539 | 0.1192 | 0.4731 | 0.4247 | 606.00 | 3030.00 | 0.00 |
ZONE3 BULK STORAGE | 0.0000 | 0.3240 | 0.3240 | 0.7173 | 1.0413 | 0.9768 | 3593.83 | 3.50 | 38.67 |
Total Facility | 0.4391 | 0.3240 | 0.7631 | 0.9111 | 1.6742 | 1.5038 | 3593.83 | 3030.00 | 38.67 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 1567884.80 | 0.00 | 1567884.80 | 3225648.14 | 5730.00 | 0.00 | 3030.00 | 0.00 |
PSZ-FINE STORAGE | 6510248.32 | 0.00 | 6510248.32 | 13393694.68 | 5730.00 | 0.00 | 3030.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1198 | 0.0000 | 0.1198 | 0.1023 | 606.00 | 0.00 | 3030.00 |
PSZ-FINE STORAGE | 0.4974 | 0.0000 | 0.4974 | 0.4247 | 606.00 | 0.00 | 3030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 3030.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 3030.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1438 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.5970 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:55
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 406 |
Defaulted Fields | 319 |
Fields with Defaults | 1047 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:42:55
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 370.85 | 1742.11 | 16-APR-13:20 | 29617.44 | 11-JAN-15:50 |
Electricity:Building | 249.55 | 1261.11 | 05-MAR-10:20 | 19128.30 | 02-JAN-09:10 |
Electricity:Zone:ZONE1 OFFICE | 39.79 | 520.87 | 01-JAN-00:10 | 2846.16 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 249.55 | 1261.11 | 05-MAR-10:20 | 19128.30 | 02-JAN-09:10 |
InteriorLights:Electricity | 113.05 | 791.24 | 05-MAR-10:20 | 9093.13 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.63 | 51.00 | 01-JAN-00:10 | 1011.11 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 113.05 | 791.24 | 05-MAR-10:20 | 9093.13 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 113.05 | 791.24 | 05-MAR-10:20 | 9093.13 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.63 | 51.00 | 01-JAN-00:10 | 1011.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 113.05 | 791.24 | 05-MAR-10:20 | 9093.13 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 48.75 | 299.97 | 01-JAN-00:10 | 3848.58 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 48.75 | 299.97 | 01-JAN-00:10 | 3848.58 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 48.75 | 299.97 | 01-JAN-00:10 | 3848.58 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 161.01 | 440.27 | 05-MAR-10:20 | 12433.56 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 53.67 | 440.27 | 05-MAR-10:20 | 4233.44 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 53.67 | 440.27 | 05-MAR-10:20 | 4233.44 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 28.05 | 0.00 | 22-MAR-17:10 | 2585.62 | 28-JAN-17:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 370.85 | 1742.11 | 16-APR-13:20 | 29617.44 | 11-JAN-15:50 |
ElectricityPurchased:Plant | 370.85 | 1742.11 | 16-APR-13:20 | 29617.44 | 11-JAN-15:50 |
Cogeneration:ElectricityPurchased | 370.85 | 1742.11 | 16-APR-13:20 | 29617.44 | 11-JAN-15:50 |
General:Cogeneration:ElectricityPurchased | 370.85 | 1742.11 | 16-APR-13:20 | 29617.44 | 11-JAN-15:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 370.85 | 1742.11 | 16-APR-13:20 | 29617.44 | 11-JAN-15:50 |
ElectricityNet:Plant | 370.85 | 1742.11 | 16-APR-13:20 | 29617.44 | 11-JAN-15:50 |
Cogeneration:ElectricityNet | 370.85 | 1742.11 | 16-APR-13:20 | 29617.44 | 11-JAN-15:50 |
General:Cogeneration:ElectricityNet | 370.85 | 1742.11 | 16-APR-13:20 | 29617.44 | 11-JAN-15:50 |
Electricity:HVAC | 29.13 | 0.00 | 22-MAR-17:10 | 3578.16 | 29-JUL-16:00 |
General:Fans:Electricity | 28.05 | 0.00 | 22-MAR-17:10 | 2585.62 | 28-JAN-17:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1.08 | 0.00 | 01-JAN-00:10 | 2065.32 | 29-JUL-16:00 |
General:Cooling:Electricity | 1.08 | 0.00 | 01-JAN-00:10 | 2065.32 | 29-JUL-16:00 |
ExteriorLights:Electricity | 63.80 | 0.00 | 01-JAN-11:20 | 5520.82 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 63.80 | 0.00 | 01-JAN-11:20 | 5520.82 | 01-JAN-06:10 |
Electricity:Plant | 28.37 | 481.00 | 02-JAN-06:40 | 3129.64 | 02-FEB-12:10 |
WaterSystems:Electricity | 28.37 | 481.00 | 02-JAN-06:40 | 3129.64 | 02-FEB-12:10 |
Water Heater:WaterSystems:Electricity | 28.37 | 481.00 | 02-JAN-06:40 | 3129.64 | 02-FEB-12:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1506.51 | 0.00 | 22-MAR-17:10 | 232296.51 | 28-JAN-17:10 |
NaturalGas:HVAC | 1506.51 | 0.00 | 22-MAR-17:10 | 232296.51 | 28-JAN-17:10 |
Heating:NaturalGas | 1506.51 | 0.00 | 22-MAR-17:10 | 232296.51 | 28-JAN-17:10 |
General:Heating:NaturalGas | 1506.51 | 0.00 | 22-MAR-17:10 | 232296.51 | 28-JAN-17:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2242.39 | 0.00 | 22-MAR-17:10 | 351796.10 | 29-JAN-00:10 |
EnergyTransfer:Building | 1082.48 | 0.00 | 22-MAR-17:10 | 175965.46 | 29-JAN-00:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 75.99 | 0.00 | 01-JAN-00:40 | 27866.73 | 27-FEB-07:20 |
Heating:EnergyTransfer | 1066.82 | 0.00 | 22-MAR-17:10 | 175965.46 | 29-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 71.75 | 0.00 | 01-JAN-00:40 | 27866.73 | 27-FEB-07:20 |
General:Heating:EnergyTransfer | 1066.82 | 0.00 | 22-MAR-17:10 | 175965.46 | 29-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 71.75 | 0.00 | 01-JAN-00:40 | 27866.73 | 27-FEB-07:20 |
Cooling:EnergyTransfer | 15.66 | 0.00 | 01-JAN-00:10 | 8297.48 | 30-AUG-07:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 4.24 | 0.00 | 01-JAN-00:10 | 4903.77 | 21-JUL-16:00 |
General:Cooling:EnergyTransfer | 15.66 | 0.00 | 01-JAN-00:10 | 8297.48 | 30-AUG-07:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 4.24 | 0.00 | 01-JAN-00:10 | 4903.77 | 21-JUL-16:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 237.06 | 0.00 | 01-JAN-00:40 | 66043.71 | 29-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 225.64 | 0.00 | 01-JAN-00:40 | 66043.71 | 29-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 225.64 | 0.00 | 01-JAN-00:40 | 66043.71 | 29-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 11.42 | 0.00 | 01-JAN-00:10 | 7987.35 | 30-AUG-07:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 11.42 | 0.00 | 01-JAN-00:10 | 7987.35 | 30-AUG-07:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 769.43 | 0.00 | 09-FEB-12:00 | 103790.64 | 28-JAN-09:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 769.43 | 0.00 | 09-FEB-12:00 | 103790.64 | 28-JAN-09:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 769.43 | 0.00 | 09-FEB-12:00 | 103790.64 | 28-JAN-09:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1159.92 | 0.00 | 22-MAR-17:10 | 184127.43 | 28-JAN-17:10 |
HeatingCoils:EnergyTransfer | 1154.78 | 0.00 | 22-MAR-17:10 | 184127.43 | 28-JAN-17:10 |
CoolingCoils:EnergyTransfer | 5.13 | 0.00 | 01-JAN-00:10 | 8938.69 | 29-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:55
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 71.753 | -4.239 | 0.000 | 0.000 | 10.401 | 10.629 | 29.165 | 8.110 | 0.000 | 0.040 | 0.000 | 0.000 | -11.667 | 0.000 | -35.288 | -78.903 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 225.641 | -11.416 | 0.000 | 0.000 | 29.251 | 48.748 | 0.000 | 0.000 | 0.000 | 0.106 | 0.001 | 0.000 | 0.000 | 0.000 | -78.751 | -213.579 |
ZONE3 BULK STORAGE | 769.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 74.312 | 53.669 | 107.344 | 76.568 | 0.000 | 3.069 | 0.000 | 0.000 | -120.573 | 0.000 | -428.025 | -535.789 |
Total Facility | 769.425 | 0.000 | 297.394 | -15.656 | 0.000 | 0.000 | 113.965 | 113.046 | 136.508 | 84.677 | 0.000 | 3.215 | 0.002 | 0.000 | -132.239 | 0.000 | -542.064 | -828.271 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 21-JUL-16:00 | 0.00 | 0.00 | 0.00 | -4902.90 | 0.00 | 0.00 | 911.96 | 616.78 | 1835.05 | 1527.67 | 0.00 | 1089.43 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1077.99 |
ZONE2 FINE STORAGE | 28-MAR-12:03 | 0.00 | 0.00 | 0.00 | -10876.81 | 0.00 | 0.00 | 3168.08 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 3860.15 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 28-MAR-12:03 | -4088.56 | 4088.56 | 4088.56 | -10876.81 | 0.00 | 0.00 | 12552.78 | 8335.55 | 10035.17 | 18992.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -867.78 | -42260.34 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 04-MAR-06:31 | 0.00 | 0.00 | 28583.17 | 0.00 | 0.00 | 0.00 | 140.49 | 302.02 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1003.11 | 0.00 | -1516.11 | -27056.97 |
ZONE2 FINE STORAGE | 24-FEB-02:41 | 0.00 | 0.00 | 69172.58 | 0.00 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -13968.31 | -55504.24 |
ZONE3 BULK STORAGE | 28-JAN-09:00 | 103788.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8460.49 | 3735.28 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8189.04 | 0.00 | -112840.75 | -3154.35 |
Total Facility | 25-FEB-05:21 | 103432.42 | 0.00 | 96812.68 | 0.00 | 0.00 | 0.00 | 0.00 | 849.01 | 2519.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9401.17 | 0.00 | -92004.61 | -102208.24 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:55
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.8508 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.8508 | 0.1202 | 1.0000 | Not calculated | 0.1023 | 0.1202 | ||
PSZ-FINE STORAGE | 1.2890 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.2890 | 0.3295 | 1.0000 | Not calculated | 0.4247 | 0.3295 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.8508 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.8508 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.1202 | ||
PSZ-FINE STORAGE | 1.2890 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.2890 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.3295 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8508 | 0.8508 | 0.8508 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2890 | 1.2890 | 1.2890 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.8508 | 0.8508 | 0.8508 | 0.8508 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.2890 | 1.2890 | 1.2890 | 1.2890 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8508 | 0.8508 | 0.8508 | No | 0.1023 | 0.2901 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2890 | 1.2890 | 1.2890 | No | 0.4247 | 0.4990 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.8508 | 0.8508 | 0.8508 | 0.8508 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.2890 | 1.2890 | 1.2890 | 1.2890 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:55
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 128.00 |
Number of hours cooling loads not met | 0.17 |
Number of hours not met | 128.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1506.51 | 232296.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1.08 | 2065.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 113.05 | 9093.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 63.80 | 5520.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 28.05 | 2585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 28.37 | 3129.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 370.85 |
Natural Gas | 0.00 | 1506.51 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 1877.36 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 23.38 |
Space Heating | 0.00 |
Space Cooling | 0.22 |
Fans (All) | 5.80 |
Service Water Heating | 5.87 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 76.70 |
Subtotal | 76.70 |
Natural Gas [MJ/m2] | |
Space Heating | 311.58 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 311.58 |
Subtotal | 311.58 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.02 |
Space Heating | 80.25 |
Space Cooling | 0.06 |
Fans (All) | 1.49 |
Service Water Heating | 1.51 |
Receptacle Equipment | 7.27 |
Miscellaneous | 3.40 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2729. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:55
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8757.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 3.00 | 0.00 | 0.00 | 0.00 |
Average | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Sum | 26277.00 | 3.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 82650.00 | 69.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 191193.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 191193.00 | 69.00 | 0.00 | 0.00 | 0.00 |
Average | 102290.00 | 23.00 | 0.00 | 0.00 | 0.00 |
Sum | 306870.00 | 69.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8750.50 | 9.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
Min | 8750.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 9.50 | 0.00 | 0.00 | 0.00 |
Average | 8756.28 | 3.72 | 0.00 | 0.00 | 0.00 |
Sum | 26268.83 | 11.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 82470.00 | 249.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 191085.83 | 107.17 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 191085.83 | 249.00 | 0.00 | 0.00 | 0.00 |
Average | 102194.28 | 118.72 | 0.00 | 0.00 | 0.00 |
Sum | 306582.83 | 356.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:55
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:55
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 2920.00 | 0.00 |
Sum | 0.00 | 8760.00 | 8760.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 33027.00 | 0.00 |
Average | 0.00 | 63731.00 | 11009.00 | 0.00 |
Sum | 0.00 | 191193.00 | 33027.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Environment
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Environment
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 | -15.4 | 0.496960E+09 | 603.25 | 14-JAN-08:09 | -19.5 | -19.6 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -20.2 | -20.7 | 0.457191E+09 | 603.25 | 18-FEB-08:09 | -21.1 | -21.7 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -28.9 | -29.2 | 0.536705E+09 | 603.25 | 25-MAR-07:10 | -12.8 | -13.5 |
April | 504.26 | 0.84 | 21-APR-15:00 | 13.90 | 5.62 | 0.497213E+09 | 629.77 | 22-APR-15:00 | 15.00 | 6.60 |
May | 5174134.25 | 313.18 | 20-MAY-14:20 | 10.53 | 6.51 | 0.530662E+09 | 760.73 | 13-MAY-15:00 | 10.53 | 6.51 |
June | 0.871599E+09 | 3366.05 | 30-JUN-15:10 | 27.38 | 17.05 | 0.632825E+09 | 768.99 | 30-JUN-10:00 | 27.38 | 17.05 |
July | 0.198489E+10 | 4903.77 | 21-JUL-16:00 | 29.40 | 15.16 | 0.627662E+09 | 769.00 | 26-JUL-15:09 | 18.40 | 16.31 |
August | 0.133648E+10 | 4219.42 | 05-AUG-06:05 | 14.32 | 11.90 | 0.657212E+09 | 768.99 | 04-AUG-10:39 | 14.32 | 11.90 |
September | 41207232.63 | 837.39 | 02-SEP-08:20 | 7.20 | 6.67 | 0.505043E+09 | 760.34 | 02-SEP-15:00 | 16.70 | 10.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 1.42 | 0.12 | 0.497131E+09 | 603.25 | 28-OCT-07:10 | -9.3 | -10.4 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 0.477183E+09 | 603.25 | 20-NOV-08:09 | -18.8 | -19.1 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -25.8 | -26.0 | 0.497048E+09 | 603.25 | 08-DEC-08:09 | -22.1 | -22.4 |
Annual Sum or Average | 0.423935E+10 | 0.641283E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -28.9 | -29.2 | 0.457191E+09 | 603.25 | -22.1 | -22.4 | ||
Maximum of Months | 0.198489E+10 | 4903.77 | 29.40 | 17.05 | 0.657212E+09 | 769.00 | 27.38 | 17.05 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 | -15.4 | 0.649225E+09 | 787.42 | 19-JAN-11:09 | -7.1 | -7.8 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -20.2 | -20.7 | 0.597285E+09 | 787.42 | 09-FEB-10:09 | -4.2 | -4.4 |
March | 0.117705E+09 | 10876.72 | 28-MAR-12:03 | -7.6 | -10.2 | 0.701154E+09 | 787.46 | 28-MAR-12:20 | -7.4 | -10.1 |
April | 0.124803E+10 | 4915.19 | 24-APR-13:40 | 4.40 | -1.0 | 0.675777E+09 | 1067.96 | 22-APR-14:30 | 4.40 | -1.0 |
May | 0.147216E+10 | 5009.17 | 16-MAY-08:20 | 5.20 | 3.93 | 0.863266E+09 | 1377.85 | 13-MAY-15:09 | 5.20 | 3.93 |
June | 0.151098E+10 | 5221.64 | 17-JUN-07:10 | 10.18 | 8.41 | 0.130627E+10 | 2067.21 | 30-JUN-15:09 | 27.38 | 17.05 |
July | 0.157999E+10 | 5753.98 | 13-JUL-07:05 | 11.38 | 8.77 | 0.147394E+10 | 2246.80 | 29-JUL-15:50 | 29.90 | 18.27 |
August | 0.260367E+10 | 8088.30 | 30-AUG-07:05 | 0.78 | -1.1 | 0.137724E+10 | 2104.54 | 04-AUG-14:00 | 0.78 | -1.1 |
September | 0.239616E+10 | 6867.31 | 09-SEP-07:10 | 1.05 | 0.55 | 0.743425E+09 | 1333.94 | 02-SEP-15:09 | 1.05 | 0.55 |
October | 0.487315E+09 | 7370.12 | 16-OCT-13:45 | -0.6 | -1.2 | 0.653814E+09 | 923.30 | 03-OCT-15:09 | -0.6 | -1.2 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 0.623338E+09 | 787.42 | 28-NOV-10:00 | -28.9 | -29.1 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -25.8 | -26.0 | 0.649241E+09 | 787.42 | 05-DEC-11:39 | -28.5 | -28.7 |
Annual Sum or Average | 0.114160E+11 | 0.103140E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.597285E+09 | 787.42 | -28.9 | -29.1 | ||
Maximum of Months | 0.260367E+10 | 10876.72 | 11.38 | 8.77 | 0.147394E+10 | 2246.80 | 29.90 | 18.27 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 | -15.4 | 0.625415E+09 | 780.39 | 31-JAN-14:20 | -20.0 | -20.6 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -20.2 | -20.7 | 0.586709E+09 | 780.42 | 27-FEB-14:20 | -28.7 | -28.9 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -28.9 | -29.2 | 0.703122E+09 | 1006.45 | 22-MAR-15:20 | 5.60 | 2.35 |
April | 0.00 | 0.00 | 01-APR-00:05 | -11.7 | -13.3 | 0.771144E+09 | 1449.97 | 22-APR-15:00 | 15.00 | 6.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 | 2.18 | 0.149571E+10 | 2392.28 | 13-MAY-15:30 | 20.00 | 9.32 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.14 | 0.268324E+10 | 4335.37 | 30-JUN-15:20 | 26.47 | 16.78 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 | 0.329301E+10 | 5006.72 | 29-JUL-15:00 | 30.00 | 18.34 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.83 | 0.312552E+10 | 4791.28 | 04-AUG-15:09 | 22.70 | 14.61 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 | 0.145684E+10 | 2895.18 | 02-SEP-15:30 | 16.70 | 10.62 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 1.42 | 0.12 | 0.685456E+09 | 1174.32 | 03-OCT-15:30 | 12.25 | 6.65 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 0.618260E+09 | 780.41 | 08-NOV-16:19 | -16.8 | -17.1 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -25.8 | -26.0 | 0.643787E+09 | 780.38 | 27-DEC-13:09 | -23.4 | -23.6 |
Annual Sum or Average | 0.00 | 0.166882E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -28.9 | -29.2 | 0.586709E+09 | 780.38 | -28.7 | -28.9 | ||
Maximum of Months | 0.00 | 0.00 | 16.35 | 13.77 | 0.329301E+10 | 5006.72 | 30.00 | 18.34 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121804E+11 | 28552.14 | 26-JAN-06:31 | -24.2 |
February | 0.105769E+11 | 28571.28 | 14-FEB-06:31 | -16.1 |
March | 0.106913E+11 | 28583.07 | 04-MAR-06:31 | -26.8 |
April | 0.597283E+10 | 28489.31 | 05-APR-05:31 | -12.6 |
May | 0.223488E+10 | 27638.79 | 02-MAY-05:42 | 4.82 |
June | 0.263957E+09 | 27019.92 | 02-JUN-05:01 | 5.78 |
July | 93956816.44 | 15805.46 | 06-JUL-05:03 | 8.77 |
August | 0.244881E+09 | 27036.58 | 31-AUG-05:01 | -1.2 |
September | 0.238061E+10 | 27211.66 | 25-SEP-05:12 | -1.3 |
October | 0.633528E+10 | 28574.15 | 31-OCT-05:31 | -18.0 |
November | 0.942801E+10 | 28529.17 | 10-NOV-06:31 | -16.1 |
December | 0.113510E+11 | 27514.88 | 04-DEC-06:11 | -19.4 |
Annual Sum or Average | 0.717540E+11 | |||
Minimum of Months | 93956816.44 | 15805.46 | -26.8 | |
Maximum of Months | 0.121804E+11 | 28583.07 | 8.77 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.427741E+11 | 69168.05 | 29-JAN-07:21 | -25.9 |
February | 0.365081E+11 | 69172.47 | 24-FEB-02:41 | -24.9 |
March | 0.325972E+11 | 68685.19 | 02-MAR-05:22 | -26.7 |
April | 0.166836E+11 | 68675.00 | 02-APR-20:22 | -12.8 |
May | 0.176183E+10 | 59870.46 | 05-MAY-05:09 | 3.40 |
June | 0.131357E+09 | 1954.83 | 30-JUN-15:00 | 28.30 |
July | 0.109330E+09 | 2044.82 | 29-JUL-17:00 | 30.00 |
August | 85101104.83 | 1511.63 | 23-AUG-17:00 | 25.00 |
September | 0.227228E+10 | 65759.35 | 29-SEP-05:01 | -4.0 |
October | 0.192547E+11 | 68164.99 | 27-OCT-03:42 | -17.8 |
November | 0.322617E+11 | 68155.47 | 09-NOV-21:22 | -22.2 |
December | 0.412020E+11 | 68636.29 | 15-DEC-02:62 | -31.2 |
Annual Sum or Average | 0.225641E+12 | |||
Minimum of Months | 85101104.83 | 1511.63 | -31.2 | |
Maximum of Months | 0.427741E+11 | 69172.47 | 30.00 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151639E+12 | 103790.64 | 28-JAN-09:00 | -20.0 |
February | 0.126380E+12 | 103679.07 | 25-FEB-12:00 | -23.9 |
March | 0.118546E+12 | 103197.27 | 02-MAR-05:00 | -26.7 |
April | 0.522705E+11 | 103208.13 | 02-APR-20:03 | -12.4 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.673716E+09 | 21450.97 | 30-SEP-05:00 | -4.4 |
October | 0.655093E+11 | 89332.29 | 27-OCT-04:00 | -17.8 |
November | 0.105838E+12 | 95174.82 | 10-NOV-01:52 | -20.0 |
December | 0.148569E+12 | 103355.55 | 22-DEC-14:10 | -23.7 |
Annual Sum or Average | 0.769425E+12 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.151639E+12 | 103790.64 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.102306E+10 | 1011.11 | 02-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.893950E+09 | 1011.11 | 01-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.926641E+09 | 1011.11 | 01-MAR-08:09 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.795627E+09 | 957.74 | 04-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.801778E+09 | 884.84 | 20-MAY-08:30 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.766257E+09 | 880.60 | 08-JUN-07:30 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.765639E+09 | 909.40 | 01-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.852920E+09 | 902.49 | 18-AUG-15:00 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.852133E+09 | 973.90 | 21-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.946883E+09 | 1011.11 | 03-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.970237E+09 | 1011.11 | 01-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.103365E+10 | 1011.11 | 01-DEC-08:09 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.106288E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.765639E+09 | 880.60 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.103365E+10 | 1011.11 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.404504E+10 | 3848.58 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.370796E+10 | 3848.58 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.430437E+10 | 3848.58 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.401913E+10 | 3848.58 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.417471E+10 | 3848.58 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.414879E+10 | 3848.58 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.404504E+10 | 3848.58 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.430437E+10 | 3848.58 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.401913E+10 | 3848.58 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.404504E+10 | 3848.58 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.388946E+10 | 3848.58 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.404504E+10 | 3848.58 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.487481E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.370796E+10 | 3848.58 | 0.00 | 0.00 | |
Maximum of Months | 0.430437E+10 | 3848.58 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.469358E+10 | 4233.44 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.422205E+10 | 4233.44 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.471528E+10 | 4167.87 | 03-MAR-15:00 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.431867E+10 | 4061.67 | 13-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.441628E+10 | 4040.12 | 09-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.432690E+10 | 3973.20 | 07-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.427258E+10 | 4024.42 | 29-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.456739E+10 | 4088.55 | 31-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.437783E+10 | 4122.76 | 30-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.455535E+10 | 4233.44 | 23-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.449193E+10 | 4233.44 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.471095E+10 | 4233.44 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.536688E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.422205E+10 | 3973.20 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.471528E+10 | 4233.44 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.102306E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493519E+10 |
February | 0.127628E+10 | 0.893950E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391001E+10 |
March | 0.149825E+10 | 0.926641E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473517E+10 |
April | 0.138726E+10 | 0.795627E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327674E+10 |
May | 0.144276E+10 | 0.801778E+09 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 184013.94 | 0.165902E+10 |
June | 0.144276E+10 | 0.766257E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12010010.76 | 0.102175E+10 |
July | 0.138726E+10 | 0.765639E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22997302.51 | 0.850307E+09 |
August | 0.149825E+10 | 0.852920E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5065488.75 | 0.133374E+10 |
September | 0.138726E+10 | 0.852133E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168355E+10 |
October | 0.138726E+10 | 0.946883E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353430E+10 |
November | 0.133177E+10 | 0.970237E+09 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374988E+10 |
December | 0.138726E+10 | 0.103365E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459874E+10 |
Annual Sum or Average | 0.168137E+11 | 0.106288E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40256815.97 | 0.352884E+11 |
Minimum of Months | 0.127628E+10 | 0.765639E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.850307E+09 |
Maximum of Months | 0.149825E+10 | 0.103365E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22997302.51 | 0.493519E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.404504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101001E+11 |
February | 0.300332E+10 | 0.370796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.835745E+10 |
March | 0.352563E+10 | 0.430437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120437E+11 |
April | 0.326447E+10 | 0.401913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105434E+11 |
May | 0.339505E+10 | 0.417471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17114103.12 | 0.436144E+10 |
June | 0.339505E+10 | 0.414879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30174962.91 | 0.287677E+10 |
July | 0.326447E+10 | 0.404504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36885508.00 | 0.269655E+10 |
August | 0.352563E+10 | 0.430437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21710289.74 | 0.356261E+10 |
September | 0.326447E+10 | 0.401913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338836E+10 |
October | 0.326447E+10 | 0.404504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.934190E+10 |
November | 0.313390E+10 | 0.388946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377914E+10 |
December | 0.326447E+10 | 0.404504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769965E+10 |
Annual Sum or Average | 0.395654E+11 | 0.487481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105885E+09 | 0.787510E+11 |
Minimum of Months | 0.300332E+10 | 0.370796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269655E+10 |
Maximum of Months | 0.352563E+10 | 0.430437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36885508.00 | 0.120437E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.469358E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383290E+11 |
February | 0.690763E+10 | 0.422205E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313552E+11 |
March | 0.810895E+10 | 0.471528E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434839E+11 |
April | 0.750829E+10 | 0.431867E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87541348.25 | 0.313547E+11 |
May | 0.780862E+10 | 0.441628E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.936438E+09 | 0.127805E+11 |
June | 0.780862E+10 | 0.432690E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526001E+09 | 0.987988E+10 |
July | 0.750829E+10 | 0.427258E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281074E+09 | 0.113977E+11 |
August | 0.810895E+10 | 0.456739E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191101E+09 | 0.162411E+11 |
September | 0.750829E+10 | 0.437783E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1586729.19 | 0.131082E+11 |
October | 0.750829E+10 | 0.455535E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28807771.15 | 0.308229E+11 |
November | 0.720796E+10 | 0.449193E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143210E+11 |
December | 0.750829E+10 | 0.471095E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312646E+11 |
Annual Sum or Average | 0.910005E+11 | 0.536688E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205255E+10 | 0.284339E+12 |
Minimum of Months | 0.690763E+10 | 0.422205E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.987988E+10 |
Maximum of Months | 0.810895E+10 | 0.471528E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.936438E+09 | 0.434839E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1011.11 | 02-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 15694.61 | 12-JAN-08:00 |
February | 1680.92 | 01-FEB-08:09 | 1011.11 | 01-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 15810.47 | 27-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 1011.11 | 01-MAR-08:09 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 13764.82 | 02-MAR-08:00 |
April | 1680.92 | 01-APR-07:10 | 957.74 | 04-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 12293.45 | 03-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 884.84 | 20-MAY-08:30 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.81 | 30-MAY-18:00 | 5754.29 | 16-MAY-07:00 |
June | 1680.92 | 01-JUN-07:10 | 880.60 | 08-JUN-07:30 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 552.67 | 29-JUN-16:10 | 3365.49 | 06-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 909.40 | 01-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1793.28 | 21-JUL-16:10 | 3531.28 | 17-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 902.49 | 18-AUG-15:00 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 497.93 | 11-AUG-16:10 | 6133.55 | 31-AUG-06:10 |
September | 1680.92 | 01-SEP-07:10 | 973.90 | 21-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 7124.94 | 29-SEP-07:00 |
October | 1680.92 | 02-OCT-07:10 | 1011.11 | 03-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 12034.51 | 31-OCT-07:00 |
November | 1680.92 | 01-NOV-07:10 | 1011.11 | 01-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 14426.71 | 29-NOV-08:00 |
December | 1680.92 | 01-DEC-08:09 | 1011.11 | 01-DEC-08:09 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 14761.16 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 880.60 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3365.49 | |||||
Maximum of Months | 1680.92 | 1011.11 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 1793.28 | 15810.47 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3848.58 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 34932.16 | 28-JAN-17:00 |
February | 3955.50 | 01-FEB-08:09 | 3848.58 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 21109.00 | 23-FEB-17:00 |
March | 3955.50 | 01-MAR-08:09 | 3848.58 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 16048.16 | 25-MAR-15:10 |
April | 3955.50 | 01-APR-07:10 | 3848.58 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 18077.11 | 01-APR-18:52 |
May | 3955.50 | 01-MAY-07:10 | 3848.58 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1237.55 | 30-MAY-18:00 | 9276.49 | 27-MAY-08:00 |
June | 3955.50 | 01-JUN-07:10 | 3848.58 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 916.40 | 30-JUN-15:10 | 7131.40 | 24-JUN-21:00 |
July | 3955.50 | 01-JUL-07:10 | 3848.58 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2764.03 | 21-JUL-16:00 | 4313.18 | 04-JUL-17:00 |
August | 3955.50 | 01-AUG-07:10 | 3848.58 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1140.79 | 23-AUG-18:00 | 7200.94 | 29-AUG-20:00 |
September | 3955.50 | 01-SEP-07:10 | 3848.58 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 5153.64 | 29-SEP-07:00 |
October | 3955.50 | 02-OCT-07:10 | 3848.58 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 11980.71 | 27-OCT-06:10 |
November | 3955.50 | 01-NOV-07:10 | 3848.58 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 11730.60 | 03-NOV-20:00 |
December | 3955.50 | 01-DEC-08:09 | 3848.58 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 13620.67 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4313.18 | ||||
Maximum of Months | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2764.03 | 34932.16 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 4233.44 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 110335.49 | 28-JAN-15:00 |
February | 9097.65 | 01-FEB-08:09 | 4233.44 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 76042.10 | 25-FEB-12:00 |
March | 9097.65 | 01-MAR-08:09 | 4167.87 | 03-MAR-15:00 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 57078.15 | 25-MAR-09:00 |
April | 9097.65 | 01-APR-07:10 | 4061.67 | 13-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2784.26 | 22-APR-14:00 | 54448.83 | 01-APR-18:52 |
May | 9097.65 | 01-MAY-07:10 | 4040.12 | 09-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9756.71 | 30-MAY-18:00 | 35470.46 | 27-MAY-11:00 |
June | 9097.65 | 01-JUN-07:10 | 3973.20 | 07-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8376.78 | 30-JUN-15:00 | 25617.92 | 24-JUN-21:00 |
July | 9097.65 | 01-JUL-07:10 | 4024.42 | 29-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14264.73 | 21-JUL-16:00 | 15795.29 | 04-JUL-17:00 |
August | 9097.65 | 01-AUG-07:10 | 4088.55 | 31-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5644.56 | 23-AUG-18:00 | 32721.65 | 31-AUG-09:00 |
September | 9097.65 | 01-SEP-07:10 | 4122.76 | 30-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 278.41 | 17-SEP-16:00 | 16204.28 | 21-SEP-14:00 |
October | 9097.65 | 02-OCT-07:10 | 4233.44 | 23-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3037.12 | 01-OCT-17:00 | 40572.99 | 31-OCT-09:00 |
November | 9097.65 | 01-NOV-07:10 | 4233.44 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 41199.83 | 01-NOV-09:00 |
December | 9097.65 | 01-DEC-08:09 | 4233.44 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 58577.74 | 22-DEC-14:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 3973.20 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15795.29 | |||||
Maximum of Months | 9097.65 | 4233.44 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 14264.73 | 110335.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 254.98 | 2349.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1102.65 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 254.98 | 2349.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 841.06 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 254.98 | 2349.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 406.07 |
April | 0.84 | 21-APR-15:00 | 1680.92 | 648.70 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.80 |
May | 313.18 | 20-MAY-14:20 | 1680.92 | 645.71 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.49 |
June | 3366.05 | 30-JUN-15:10 | 1680.92 | 640.98 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 388.96 | 0.00 |
July | 4903.77 | 21-JUL-16:00 | 1680.92 | 616.78 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 1089.43 | 0.00 |
August | 4219.42 | 05-AUG-06:05 | 705.99 | 835.89 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.22 |
September | 837.39 | 02-SEP-08:20 | 1680.92 | 910.26 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.91 |
October | 0.00 | 01-OCT-00:05 | 0.00 | 101.99 | 939.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 651.31 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 51.00 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 926.03 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 203.98 | 1879.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 51.00 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4903.77 | 1680.92 | 910.26 | 2349.38 | 0.00 | 0.00 | 0.00 | 0.00 | 1089.43 | 1102.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 1499.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6558.77 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 1499.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4860.13 |
March | 10876.72 | 28-MAR-12:03 | 11866.50 | 11545.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4915.19 | 24-APR-13:40 | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1450.71 |
May | 5009.17 | 16-MAY-08:20 | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2554.25 |
June | 5221.64 | 17-JUN-07:10 | 3955.50 | 3395.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5753.98 | 13-JUL-07:05 | 7911.00 | 6791.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8088.30 | 30-AUG-07:05 | 7911.00 | 6791.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3844.43 |
September | 6867.31 | 09-SEP-07:10 | 3955.50 | 3395.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.46 |
October | 7370.12 | 16-OCT-13:45 | 7911.00 | 7697.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1290.51 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5550.09 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10876.72 | 11866.50 | 11545.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6558.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 2490.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21463.35 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 2490.23 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16870.79 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 2490.23 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8411.51 |
April | 0.00 | 01-APR-00:05 | 0.00 | 996.09 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29194.10 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3672.76 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2174.16 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3601.74 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7216.77 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4821.83 |
October | 0.00 | 01-OCT-00:05 | 0.00 | 996.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9138.89 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17154.17 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1992.18 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 2490.23 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29194.10 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.364794E+11 | 29617.44 | 11-JAN-15:50 | 0.289247E+12 | 232296.51 | 28-JAN-17:10 |
February | 0.312780E+11 | 28519.89 | 04-FEB-09:20 | 0.241880E+12 | 226262.74 | 24-FEB-17:00 |
March | 0.332819E+11 | 27687.23 | 15-MAR-07:10 | 0.226918E+12 | 207972.75 | 16-MAR-07:00 |
April | 0.285640E+11 | 23131.42 | 01-APR-14:30 | 0.103985E+12 | 188323.16 | 02-APR-19:49 |
May | 0.272096E+11 | 22948.99 | 09-MAY-12:00 | 0.605967E+10 | 33148.75 | 27-MAY-05:10 |
June | 0.260398E+11 | 23265.57 | 30-JUN-14:20 | 0.187728E+09 | 10535.98 | 01-JUN-05:10 |
July | 0.262039E+11 | 23757.87 | 29-JUL-14:00 | 26116178.17 | 5384.79 | 06-JUL-05:10 |
August | 0.290018E+11 | 23101.35 | 25-AUG-14:00 | 0.246207E+09 | 11373.25 | 31-AUG-05:10 |
September | 0.289446E+11 | 22637.71 | 30-SEP-12:00 | 0.102322E+11 | 56821.88 | 30-SEP-05:19 |
October | 0.324974E+11 | 28482.36 | 31-OCT-08:20 | 0.130350E+12 | 164538.45 | 31-OCT-05:10 |
November | 0.340673E+11 | 29369.72 | 29-NOV-15:09 | 0.213387E+12 | 182836.02 | 29-NOV-07:00 |
December | 0.372843E+11 | 29522.80 | 22-DEC-15:09 | 0.283993E+12 | 211950.98 | 15-DEC-12:09 |
Annual Sum or Average | 0.370852E+12 | 0.150651E+13 | ||||
Minimum of Months | 0.260398E+11 | 22637.71 | 26116178.17 | 5384.79 | ||
Maximum of Months | 0.372843E+11 | 29617.44 | 0.289247E+12 | 232296.51 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.976168E+10 | 0.974517E+10 | 0.112984E+11 | 0.00 | 0.324423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242994E+10 | 0.00 |
February | 0.882396E+10 | 0.696045E+10 | 0.103734E+11 | 0.00 | 0.290895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221122E+10 | 0.00 |
March | 0.994629E+10 | 0.562439E+10 | 0.121089E+11 | 0.00 | 0.309504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250720E+10 | 0.00 |
April | 0.913343E+10 | 0.349050E+10 | 0.112578E+11 | 0.00 | 0.229989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238243E+10 | 0.00 |
May | 0.939276E+10 | 0.204155E+10 | 0.117000E+11 | 0.00 | 0.161675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245857E+10 | 0.00 |
June | 0.924195E+10 | 0.982384E+09 | 0.116594E+11 | 0.00 | 0.156005E+10 | 0.00 | 0.00 | 0.232087E+09 | 0.00 | 0.00 | 0.00 | 0.236398E+10 | 0.00 |
July | 0.908326E+10 | 0.145141E+10 | 0.112984E+11 | 0.00 | 0.149814E+10 | 0.00 | 0.00 | 0.540052E+09 | 0.00 | 0.00 | 0.00 | 0.233268E+10 | 0.00 |
August | 0.972468E+10 | 0.287026E+10 | 0.121016E+11 | 0.00 | 0.161913E+10 | 0.00 | 0.00 | 0.305939E+09 | 0.00 | 0.00 | 0.00 | 0.238027E+10 | 0.00 |
September | 0.924909E+10 | 0.458137E+10 | 0.112504E+11 | 0.00 | 0.159450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226927E+10 | 0.00 |
October | 0.954728E+10 | 0.680699E+10 | 0.113057E+11 | 0.00 | 0.250054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233690E+10 | 0.00 |
November | 0.935163E+10 | 0.865793E+10 | 0.108562E+11 | 0.00 | 0.291381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228778E+10 | 0.00 |
December | 0.978964E+10 | 0.105865E+11 | 0.112984E+11 | 0.00 | 0.319688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241286E+10 | 0.00 |
Annual Sum or Average | 0.113046E+12 | 0.637990E+11 | 0.136508E+12 | 0.00 | 0.280479E+11 | 0.00 | 0.00 | 0.107808E+10 | 0.00 | 0.00 | 0.00 | 0.283731E+11 | 0.00 |
Minimum of Months | 0.882396E+10 | 0.982384E+09 | 0.103734E+11 | 0.00 | 0.149814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221122E+10 | 0.00 |
Maximum of Months | 0.994629E+10 | 0.105865E+11 | 0.121089E+11 | 0.00 | 0.324423E+10 | 0.00 | 0.00 | 0.540052E+09 | 0.00 | 0.00 | 0.00 | 0.250720E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.289247E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.241880E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.226918E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.103985E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.605967E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.187728E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 26116178.17 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.246207E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.102322E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.130350E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.213387E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.283993E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.150651E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 26116178.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.289247E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 9093.13 | 02-JAN-09:09 | 5520.82 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 2585.62 | 28-JAN-17:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 9093.13 | 01-FEB-09:09 | 5520.82 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 2446.11 | 24-FEB-08:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 8904.04 | 03-MAR-09:09 | 5520.82 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 2337.67 | 02-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 8796.42 | 13-APR-08:09 | 5520.82 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 2248.84 | 03-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 8770.59 | 09-MAY-08:09 | 4975.14 | 01-MAY-21:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 1680.84 | 27-MAY-07:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 8670.64 | 07-JUN-08:09 | 4975.14 | 01-JUN-22:49 | 10035.17 | 01-JUN-07:10 | 0.00 | 1512.84 | 01-JUN-16:40 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 8742.51 | 29-JUL-08:09 | 4975.14 | 11-JUL-22:00 | 10035.17 | 01-JUL-07:10 | 0.00 | 1512.84 | 01-JUL-08:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 8826.08 | 31-AUG-08:09 | 5520.82 | 24-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 1512.84 | 01-AUG-12:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 8884.30 | 30-SEP-08:09 | 5520.82 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 1870.09 | 29-SEP-06:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 9093.13 | 23-OCT-08:09 | 5520.82 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 2240.42 | 31-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 9093.13 | 01-NOV-08:09 | 5520.82 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 2338.36 | 29-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 9093.13 | 01-DEC-09:09 | 5520.82 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 2377.60 | 15-DEC-08:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 8670.64 | 4975.14 | 10035.17 | 0.00 | 1512.84 | 0.00 | 0.00 | |||||
Maximum of Months | 9093.13 | 5520.82 | 10035.17 | 0.00 | 2585.62 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 3129.53 | 13-JAN-12:09 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 3129.64 | 02-FEB-12:09 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 3129.56 | 06-MAR-12:39 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 3129.54 | 24-APR-11:20 | 0.00 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 3129.55 | 03-MAY-11:09 | 0.00 |
June | 1107.56 | 30-JUN-14:00 | 0.00 | 0.00 | 0.00 | 3026.49 | 03-JUN-11:50 | 0.00 |
July | 2065.32 | 29-JUL-15:00 | 0.00 | 0.00 | 0.00 | 2888.50 | 01-JUL-11:39 | 0.00 |
August | 1031.18 | 11-AUG-15:00 | 0.00 | 0.00 | 0.00 | 2762.56 | 01-AUG-11:30 | 0.00 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 2744.58 | 30-SEP-11:30 | 0.00 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 2854.29 | 31-OCT-11:00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2997.46 | 30-NOV-12:20 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 3129.04 | 30-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2744.58 | 0.00 | ||
Maximum of Months | 2065.32 | 0.00 | 0.00 | 0.00 | 3129.64 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 29617.44 | 11-JAN-15:50 | 9093.13 | 10035.17 | 5520.82 | 0.00 | 2278.42 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 28519.89 | 04-FEB-09:20 | 9093.13 | 10035.17 | 5520.82 | 0.00 | 2142.04 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 27687.23 | 15-MAR-07:10 | 8142.10 | 10035.17 | 5520.82 | 0.00 | 2308.28 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23131.42 | 01-APR-14:30 | 8502.95 | 10035.17 | 0.00 | 0.00 | 1904.16 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22948.99 | 09-MAY-12:00 | 8711.64 | 10035.17 | 0.00 | 0.00 | 1512.84 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 23265.57 | 30-JUN-14:20 | 8232.05 | 10035.17 | 0.00 | 0.00 | 1512.84 | 0.00 | 0.00 | 1061.58 | 0.00 |
July | 23757.87 | 29-JUL-14:00 | 8369.74 | 10035.17 | 0.00 | 0.00 | 1512.84 | 0.00 | 0.00 | 1551.21 | 0.00 |
August | 23101.35 | 25-AUG-14:00 | 8569.67 | 10035.17 | 0.00 | 0.00 | 1512.84 | 0.00 | 0.00 | 763.96 | 0.00 |
September | 22637.71 | 30-SEP-12:00 | 8801.09 | 10035.17 | 0.00 | 0.00 | 1544.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 28482.36 | 31-OCT-08:20 | 9093.13 | 10035.17 | 5520.82 | 0.00 | 2122.64 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 29369.72 | 29-NOV-15:09 | 9093.13 | 10035.17 | 5520.82 | 0.00 | 2183.06 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 29522.80 | 22-DEC-15:09 | 9093.13 | 10035.17 | 5520.82 | 0.00 | 2213.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 22637.71 | 8142.10 | 10035.17 | 0.00 | 0.00 | 1512.84 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29617.44 | 9093.13 | 10035.17 | 5520.82 | 0.00 | 2308.28 | 0.00 | 0.00 | 1551.21 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 232296.51 | 28-JAN-17:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 226262.74 | 24-FEB-17:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 207972.75 | 16-MAR-07:00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 188323.16 | 02-APR-19:49 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 33148.75 | 27-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 10535.98 | 01-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 5384.79 | 06-JUL-05:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 11373.25 | 31-AUG-05:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 56821.88 | 30-SEP-05:19 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 164538.45 | 31-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 182836.02 | 29-NOV-07:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 211950.98 | 15-DEC-12:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 5384.79 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 232296.51 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 39.83 | 15.91 | 9.83 | 16.55 | 0.00 | 16.55 | 0.00 | 16.55 |
February | 38.33 | 15.82 | 9.00 | 16.42 | 0.00 | 16.42 | 0.00 | 16.42 |
March | 31.50 | 16.39 | 10.83 | 17.09 | 0.00 | 17.09 | 0.00 | 17.09 |
April | 18.50 | 17.23 | 10.33 | 17.88 | 0.00 | 17.88 | 0.00 | 17.88 |
May | 8.17 | 20.01 | 8.00 | 20.06 | 0.00 | 20.06 | 0.00 | 20.06 |
June | 0.33 | 20.50 | 0.33 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
July | 0.17 | 20.54 | 0.17 | 20.54 | 0.17 | 21.86 | 0.17 | 22.52 |
August | 0.33 | 20.42 | 0.33 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
September | 6.33 | 20.11 | 6.33 | 20.11 | 0.00 | 20.11 | 0.00 | 20.11 |
October | 12.33 | 18.27 | 8.83 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
November | 12.83 | 17.95 | 8.67 | 18.52 | 0.00 | 18.52 | 0.00 | 18.52 |
December | 20.00 | 16.80 | 8.67 | 17.52 | 0.00 | 17.52 | 0.00 | 17.52 |
Annual Sum or Average | 188.67 | 16.83 | 81.33 | 17.59 | 0.17 | 17.60 | 0.17 | 17.60 |
Minimum of Months | 0.17 | 15.82 | 0.17 | 16.42 | 0.00 | 16.42 | 0.00 | 16.42 |
Maximum of Months | 39.83 | 20.54 | 10.83 | 20.54 | 0.17 | 21.86 | 0.17 | 22.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 116.83 | 14.28 | 4.17 | 14.27 | 0.00 | 14.27 | 0.00 | 14.27 |
February | 103.67 | 14.31 | 3.83 | 14.31 | 0.00 | 14.31 | 0.00 | 14.31 |
March | 104.00 | 14.40 | 5.17 | 14.39 | 0.00 | 14.39 | 0.00 | 14.39 |
April | 60.83 | 14.57 | 5.00 | 14.57 | 0.00 | 14.57 | 0.00 | 14.57 |
May | 5.00 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6.67 | 14.95 | 0.67 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
October | 72.50 | 14.67 | 3.67 | 14.67 | 0.00 | 14.67 | 0.00 | 14.67 |
November | 112.17 | 14.52 | 4.17 | 14.52 | 0.00 | 14.52 | 0.00 | 14.52 |
December | 115.17 | 14.35 | 4.17 | 14.35 | 0.00 | 14.35 | 0.00 | 14.35 |
Annual Sum or Average | 696.83 | 14.43 | 30.83 | 14.43 | 0.00 | 14.43 | 0.00 | 14.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 116.83 | 14.95 | 5.17 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 70.50 | 7.92 | 25.83 | 7.95 | 0.00 | 7.95 | 0.00 | 7.95 |
February | 44.83 | 8.64 | 12.33 | 8.64 | 0.00 | 8.64 | 0.00 | 8.64 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.33 | 8.20 | 38.17 | 8.21 | 0.00 | 8.21 | 0.00 | 8.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.50 | 8.64 | 25.83 | 8.64 | 0.00 | 8.64 | 0.00 | 8.64 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.03 | 300.00 | 21.03 | 300.00 | 21.03 |
February | 276.00 | 21.02 | 276.00 | 21.02 | 276.00 | 21.02 |
March | 324.00 | 21.03 | 324.00 | 21.03 | 324.00 | 21.03 |
April | 300.00 | 21.03 | 300.00 | 21.03 | 300.00 | 21.03 |
May | 312.00 | 21.32 | 282.67 | 21.25 | 282.67 | 21.23 |
June | 311.33 | 23.16 | 27.83 | 23.00 | 27.83 | 22.86 |
July | 215.67 | 23.56 | 4.33 | 23.56 | 0.50 | 23.55 |
August | 281.33 | 23.09 | 21.00 | 22.95 | 21.00 | 22.84 |
September | 300.00 | 21.22 | 268.00 | 21.17 | 268.00 | 21.15 |
October | 300.00 | 21.05 | 300.00 | 21.05 | 300.00 | 21.05 |
November | 288.00 | 21.04 | 288.00 | 21.04 | 288.00 | 21.04 |
December | 300.00 | 21.04 | 300.00 | 21.04 | 300.00 | 21.04 |
Annual Sum or Average | 3508.33 | 21.58 | 2691.83 | 21.36 | 2688.00 | 21.27 |
Minimum of Months | 215.67 | 21.02 | 4.33 | 21.02 | 0.50 | 21.02 |
Maximum of Months | 324.00 | 23.56 | 324.00 | 23.56 | 324.00 | 23.55 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.54 | 300.00 | 15.54 | 300.00 | 15.54 |
February | 276.00 | 15.54 | 276.00 | 15.54 | 276.00 | 15.54 |
March | 324.00 | 15.54 | 324.00 | 15.54 | 324.00 | 15.54 |
April | 300.00 | 15.82 | 300.00 | 15.82 | 300.00 | 15.82 |
May | 312.00 | 17.43 | 312.00 | 17.43 | 312.00 | 17.43 |
June | 290.17 | 21.41 | 80.00 | 21.05 | 76.00 | 20.77 |
July | 177.33 | 22.53 | 93.67 | 23.26 | 13.17 | 23.09 |
August | 276.17 | 21.34 | 99.17 | 21.21 | 70.00 | 20.87 |
September | 300.00 | 16.57 | 300.00 | 16.57 | 300.00 | 16.57 |
October | 300.00 | 15.59 | 300.00 | 15.59 | 300.00 | 15.59 |
November | 288.00 | 15.54 | 288.00 | 15.54 | 288.00 | 15.54 |
December | 300.00 | 15.54 | 300.00 | 15.54 | 300.00 | 15.54 |
Annual Sum or Average | 3443.67 | 17.15 | 2972.83 | 16.83 | 2859.17 | 16.60 |
Minimum of Months | 177.33 | 15.54 | 80.00 | 15.54 | 13.17 | 15.54 |
Maximum of Months | 324.00 | 22.53 | 324.00 | 23.26 | 324.00 | 23.09 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 9.83 | 300.00 | 9.83 | 300.00 | 9.83 |
February | 276.00 | 9.93 | 276.00 | 9.93 | 276.00 | 9.93 |
March | 324.00 | 10.05 | 324.00 | 10.05 | 324.00 | 10.05 |
April | 300.00 | 10.86 | 300.00 | 10.86 | 300.00 | 10.86 |
May | 312.00 | 14.94 | 312.00 | 14.94 | 312.00 | 14.94 |
June | 312.00 | 20.36 | 146.50 | 19.81 | 146.50 | 19.53 |
July | 214.83 | 22.58 | 47.17 | 22.78 | 13.67 | 22.64 |
August | 287.33 | 21.26 | 105.33 | 21.00 | 85.83 | 20.68 |
September | 300.00 | 15.06 | 300.00 | 15.06 | 300.00 | 15.06 |
October | 300.00 | 10.29 | 300.00 | 10.29 | 300.00 | 10.29 |
November | 288.00 | 10.00 | 288.00 | 10.00 | 288.00 | 10.00 |
December | 300.00 | 10.00 | 300.00 | 10.00 | 300.00 | 10.00 |
Annual Sum or Average | 3514.17 | 13.56 | 2999.00 | 12.90 | 2946.00 | 12.58 |
Minimum of Months | 214.83 | 9.83 | 47.17 | 9.83 | 13.67 | 9.83 |
Maximum of Months | 324.00 | 22.58 | 324.00 | 22.78 | 324.00 | 22.64 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 0.109065E+10 | 0.232087E+09 | 157.33 | 0.104160E+10 | 49054223.27 | 0.00 | 0.70 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 | 5174.54 | 30-JUN-15:10 | 4743.80 | 30-JUN-15:00 | 791.87 | 30-JUN-12:10 | 1107.56 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.257055E+10 | 0.536436E+09 | 230.75 | 0.235429E+10 | 0.216266E+09 | 0.00 | 0.91 | 21-JUL-16:00 | 0.00 | 01-JUL-00:10 | 6575.30 | 29-JUL-16:00 | 6520.25 | 21-JUL-16:00 | 828.97 | 26-JUL-15:00 | 1420.00 | 29-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 0.145906E+10 | 0.305939E+09 | 170.92 | 0.133945E+10 | 0.119605E+09 | 0.00 | 0.76 | 05-AUG-06:05 | 0.00 | 01-AUG-00:10 | 5639.56 | 05-AUG-06:05 | 5639.56 | 05-AUG-06:05 | 812.84 | 03-AUG-15:00 | 1118.74 | 05-AUG-06:05 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.512026E+10 | 0.107446E+10 | 559.00 | 0.473534E+10 | 0.384925E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.257055E+10 | 0.536436E+09 | 230.75 | 0.235429E+10 | 0.216266E+09 | 0.00 | 0.91 | 0.00 | 6575.30 | 6520.25 | 828.97 | 1420.00 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 |
July | 13124214.21 | 3615707.17 | 3.50 | 13122630.95 | 1583.26 | 0.00 | 0.23 | 21-JUL-16:00 | 0.00 | 01-JUL-00:10 | 2363.39 | 29-JUL-16:00 | 2363.39 | 29-JUL-16:00 | 1.77 | 22-JUL-13:00 | 645.31 | 29-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 13124214.21 | 3615707.17 | 3.50 | 13122630.95 | 1583.26 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 13124214.21 | 3615707.17 | 3.50 | 13122630.95 | 1583.26 | 0.00 | 0.23 | 0.00 | 2363.39 | 2363.39 | 1.77 | 645.31 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4.70 | 0.80 | 3.90 | 0.00 | 239.86 | 0.00 | 0.00 | 0.00 |
February | 28.02 | 9.76 | 18.26 | 6.68 | 199.12 | 0.00 | 0.00 | 0.00 |
March | 84.43 | 36.54 | 47.89 | 54.89 | 137.26 | 0.00 | 0.00 | 0.00 |
April | 199.45 | 103.48 | 95.97 | 213.94 | 69.88 | 0.00 | 0.00 | 0.00 |
May | 193.74 | 88.37 | 105.37 | 226.11 | 28.11 | 0.00 | 0.00 | 0.00 |
June | 212.44 | 90.81 | 121.63 | 255.69 | 16.48 | 0.00 | 0.00 | 0.00 |
July | 177.48 | 67.17 | 110.30 | 210.47 | 22.46 | 0.00 | 0.00 | 0.00 |
August | 146.28 | 62.21 | 84.07 | 165.64 | 34.16 | 0.00 | 0.00 | 0.00 |
September | 88.13 | 36.81 | 51.32 | 84.19 | 56.39 | 0.00 | 0.00 | 0.00 |
October | 34.44 | 10.27 | 24.17 | 15.94 | 119.56 | 0.00 | 0.00 | 0.00 |
November | 13.76 | 4.94 | 8.82 | 1.63 | 228.62 | 0.00 | 0.00 | 0.00 |
December | 1.24 | 0.13 | 1.11 | 0.00 | 256.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98.93 | 42.70 | 56.23 | 103.33 | 116.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1.24 | 0.13 | 1.11 | 0.00 | 16.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 212.44 | 103.48 | 121.63 | 255.69 | 256.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4.70 | 0.80 | 3.90 | 0.00 | 239.86 | 0.00 | 0.00 | 0.00 |
February | 28.02 | 9.76 | 18.26 | 6.68 | 199.12 | 0.00 | 0.00 | 0.00 |
March | 84.43 | 36.54 | 47.89 | 54.89 | 137.26 | 0.00 | 0.00 | 0.00 |
April | 199.45 | 103.48 | 95.97 | 213.94 | 69.88 | 0.00 | 0.00 | 0.00 |
May | 193.74 | 88.37 | 105.37 | 226.11 | 28.11 | 0.00 | 0.00 | 0.00 |
June | 212.44 | 90.81 | 121.63 | 255.69 | 16.48 | 0.00 | 0.00 | 0.00 |
July | 177.48 | 67.17 | 110.30 | 210.47 | 22.46 | 0.00 | 0.00 | 0.00 |
August | 146.28 | 62.21 | 84.07 | 165.64 | 34.16 | 0.00 | 0.00 | 0.00 |
September | 88.13 | 36.81 | 51.32 | 84.19 | 56.39 | 0.00 | 0.00 | 0.00 |
October | 34.44 | 10.27 | 24.17 | 15.94 | 119.56 | 0.00 | 0.00 | 0.00 |
November | 13.76 | 4.94 | 8.82 | 1.63 | 228.62 | 0.00 | 0.00 | 0.00 |
December | 1.24 | 0.13 | 1.11 | 0.00 | 256.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98.93 | 42.70 | 56.23 | 103.33 | 116.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1.24 | 0.13 | 1.11 | 0.00 | 16.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 212.44 | 103.48 | 121.63 | 255.69 | 256.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.99 | 0.00 | 1.99 | 0.00 | 141.63 | 0.00 | 0.00 | 0.00 |
February | 8.81 | 0.00 | 8.81 | 0.00 | 124.22 | 0.00 | 0.00 | 0.00 |
March | 23.62 | 0.01 | 23.62 | 3.08 | 87.78 | 0.00 | 0.00 | 0.00 |
April | 42.94 | 1.16 | 41.78 | 24.72 | 41.08 | 0.00 | 0.00 | 0.00 |
May | 65.75 | 10.51 | 55.24 | 67.06 | 14.65 | 0.00 | 0.00 | 0.00 |
June | 84.86 | 18.56 | 66.30 | 95.04 | 7.57 | 0.00 | 0.00 | 0.00 |
July | 71.60 | 11.71 | 59.89 | 78.29 | 11.29 | 0.00 | 0.00 | 0.00 |
August | 45.99 | 2.43 | 43.56 | 42.18 | 18.86 | 0.00 | 0.00 | 0.00 |
September | 25.61 | 0.07 | 25.54 | 14.31 | 33.99 | 0.00 | 0.00 | 0.00 |
October | 12.40 | 0.00 | 12.40 | 1.78 | 73.80 | 0.00 | 0.00 | 0.00 |
November | 3.85 | 0.00 | 3.85 | 0.00 | 139.16 | 0.00 | 0.00 | 0.00 |
December | 0.60 | 0.00 | 0.60 | 0.00 | 150.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.45 | 3.72 | 28.73 | 27.36 | 70.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.60 | 0.00 | 0.60 | 0.00 | 7.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.86 | 18.56 | 66.30 | 95.04 | 150.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.99 | 0.00 | 1.99 | 0.00 | 141.63 | 0.00 | 0.00 | 0.00 |
February | 8.81 | 0.00 | 8.81 | 0.00 | 124.22 | 0.00 | 0.00 | 0.00 |
March | 23.62 | 0.01 | 23.62 | 3.08 | 87.79 | 0.00 | 0.00 | 0.00 |
April | 42.93 | 1.16 | 41.78 | 24.72 | 41.08 | 0.00 | 0.00 | 0.00 |
May | 65.75 | 10.51 | 55.24 | 67.06 | 14.65 | 0.00 | 0.00 | 0.00 |
June | 84.85 | 18.56 | 66.29 | 95.03 | 7.57 | 0.00 | 0.00 | 0.00 |
July | 71.60 | 11.71 | 59.89 | 78.29 | 11.29 | 0.00 | 0.00 | 0.00 |
August | 45.99 | 2.43 | 43.56 | 42.17 | 18.86 | 0.00 | 0.00 | 0.00 |
September | 25.61 | 0.07 | 25.54 | 14.31 | 33.99 | 0.00 | 0.00 | 0.00 |
October | 12.40 | 0.00 | 12.40 | 1.78 | 73.80 | 0.00 | 0.00 | 0.00 |
November | 3.85 | 0.00 | 3.85 | 0.00 | 139.16 | 0.00 | 0.00 | 0.00 |
December | 0.60 | 0.00 | 0.60 | 0.00 | 150.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.45 | 3.72 | 28.73 | 27.36 | 70.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.60 | 0.00 | 0.60 | 0.00 | 7.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.85 | 18.56 | 66.29 | 95.03 | 150.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.44 | 0.22 | 2.22 | 0.00 | 138.33 | 0.00 | 0.00 | 0.00 |
February | 12.37 | 3.03 | 9.35 | 0.17 | 115.50 | 0.00 | 0.00 | 0.00 |
March | 43.44 | 18.47 | 24.97 | 31.85 | 76.90 | 0.00 | 0.00 | 0.00 |
April | 87.39 | 47.15 | 40.24 | 100.24 | 39.72 | 0.00 | 0.00 | 0.00 |
May | 113.99 | 64.86 | 49.13 | 144.03 | 19.20 | 0.00 | 0.00 | 0.00 |
June | 123.66 | 61.66 | 62.00 | 155.41 | 12.99 | 0.00 | 0.00 | 0.00 |
July | 110.94 | 53.65 | 57.29 | 135.49 | 18.20 | 0.00 | 0.00 | 0.00 |
August | 83.52 | 40.52 | 43.00 | 96.80 | 26.36 | 0.00 | 0.00 | 0.00 |
September | 45.12 | 17.86 | 27.26 | 45.58 | 35.42 | 0.00 | 0.00 | 0.00 |
October | 18.52 | 4.49 | 14.03 | 10.43 | 60.11 | 9.33 | 0.00 | 0.00 |
November | 4.64 | 0.39 | 4.26 | 0.00 | 135.66 | 0.00 | 0.00 | 0.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 148.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.11 | 26.15 | 27.96 | 60.33 | 68.70 | 9.33 | 0.00 | 0.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 12.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.66 | 64.86 | 62.00 | 155.41 | 148.85 | 9.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.44 | 0.22 | 2.22 | 0.00 | 138.33 | 0.00 | 0.00 | 0.00 |
February | 12.37 | 3.03 | 9.35 | 0.17 | 115.50 | 0.00 | 0.00 | 0.00 |
March | 43.44 | 18.47 | 24.97 | 31.85 | 76.90 | 0.00 | 0.00 | 0.00 |
April | 87.39 | 47.15 | 40.24 | 100.24 | 39.72 | 0.00 | 0.00 | 0.00 |
May | 113.99 | 64.86 | 49.13 | 144.03 | 19.20 | 0.00 | 0.00 | 0.00 |
June | 123.66 | 61.66 | 62.00 | 155.41 | 12.99 | 0.00 | 0.00 | 0.00 |
July | 110.94 | 53.65 | 57.29 | 135.49 | 18.20 | 0.00 | 0.00 | 0.00 |
August | 83.52 | 40.52 | 43.00 | 96.80 | 26.36 | 0.00 | 0.00 | 0.00 |
September | 45.12 | 17.86 | 27.26 | 45.58 | 35.42 | 0.00 | 0.00 | 0.00 |
October | 18.52 | 4.49 | 14.03 | 10.43 | 60.11 | 9.33 | 0.00 | 0.00 |
November | 4.64 | 0.39 | 4.26 | 0.00 | 135.66 | 0.00 | 0.00 | 0.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 148.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.11 | 26.15 | 27.96 | 60.33 | 68.70 | 9.33 | 0.00 | 0.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 12.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.66 | 64.86 | 62.00 | 155.41 | 148.85 | 9.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.44 | 0.22 | 2.22 | 0.00 | 138.33 | 0.00 | 0.00 | 0.00 |
February | 12.37 | 3.03 | 9.35 | 0.17 | 115.50 | 0.00 | 0.00 | 0.00 |
March | 43.44 | 18.47 | 24.97 | 31.85 | 76.90 | 0.00 | 0.00 | 0.00 |
April | 87.39 | 47.15 | 40.24 | 100.24 | 39.72 | 0.00 | 0.00 | 0.00 |
May | 113.99 | 64.86 | 49.13 | 144.03 | 19.20 | 0.00 | 0.00 | 0.00 |
June | 123.66 | 61.66 | 62.00 | 155.41 | 12.99 | 0.00 | 0.00 | 0.00 |
July | 110.94 | 53.65 | 57.29 | 135.49 | 18.20 | 0.00 | 0.00 | 0.00 |
August | 83.52 | 40.52 | 43.00 | 96.80 | 26.36 | 0.00 | 0.00 | 0.00 |
September | 45.12 | 17.86 | 27.26 | 45.58 | 35.42 | 0.00 | 0.00 | 0.00 |
October | 18.52 | 4.49 | 14.03 | 10.43 | 60.11 | 9.33 | 0.00 | 0.00 |
November | 4.64 | 0.39 | 4.26 | 0.00 | 135.66 | 0.00 | 0.00 | 0.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 148.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.11 | 26.15 | 27.96 | 60.33 | 68.70 | 9.33 | 0.00 | 0.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 12.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.66 | 64.86 | 62.00 | 155.41 | 148.85 | 9.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.44 | 0.22 | 2.22 | 0.00 | 138.33 | 0.00 | 0.00 | 0.00 |
February | 12.37 | 3.03 | 9.35 | 0.17 | 115.50 | 0.00 | 0.00 | 0.00 |
March | 43.44 | 18.47 | 24.97 | 31.85 | 76.90 | 0.00 | 0.00 | 0.00 |
April | 87.39 | 47.15 | 40.24 | 100.24 | 39.72 | 0.00 | 0.00 | 0.00 |
May | 113.99 | 64.86 | 49.13 | 144.03 | 19.20 | 0.00 | 0.00 | 0.00 |
June | 123.66 | 61.66 | 62.00 | 155.41 | 12.99 | 0.00 | 0.00 | 0.00 |
July | 110.94 | 53.65 | 57.29 | 135.49 | 18.20 | 0.00 | 0.00 | 0.00 |
August | 83.52 | 40.52 | 43.00 | 96.80 | 26.36 | 0.00 | 0.00 | 0.00 |
September | 45.12 | 17.86 | 27.26 | 45.58 | 35.42 | 0.00 | 0.00 | 0.00 |
October | 18.52 | 4.49 | 14.03 | 10.43 | 60.11 | 9.33 | 0.00 | 0.00 |
November | 4.64 | 0.39 | 4.26 | 0.00 | 135.66 | 0.00 | 0.00 | 0.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 148.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.11 | 26.15 | 27.96 | 60.33 | 68.70 | 9.33 | 0.00 | 0.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 12.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.66 | 64.86 | 62.00 | 155.41 | 148.85 | 9.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.44 | 0.22 | 2.22 | 0.00 | 138.33 | 0.00 | 0.00 | 0.00 |
February | 12.37 | 3.03 | 9.35 | 0.17 | 115.50 | 0.00 | 0.00 | 0.00 |
March | 43.44 | 18.47 | 24.97 | 31.85 | 76.90 | 0.00 | 0.00 | 0.00 |
April | 87.39 | 47.15 | 40.24 | 100.24 | 39.72 | 0.00 | 0.00 | 0.00 |
May | 113.99 | 64.86 | 49.13 | 144.03 | 19.20 | 0.00 | 0.00 | 0.00 |
June | 123.66 | 61.66 | 62.00 | 155.41 | 12.99 | 0.00 | 0.00 | 0.00 |
July | 110.94 | 53.65 | 57.29 | 135.49 | 18.20 | 0.00 | 0.00 | 0.00 |
August | 83.52 | 40.52 | 43.00 | 96.80 | 26.36 | 0.00 | 0.00 | 0.00 |
September | 45.12 | 17.86 | 27.26 | 45.58 | 35.42 | 0.00 | 0.00 | 0.00 |
October | 18.52 | 4.49 | 14.03 | 10.43 | 60.11 | 9.33 | 0.00 | 0.00 |
November | 4.64 | 0.39 | 4.26 | 0.00 | 135.66 | 0.00 | 0.00 | 0.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 148.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.11 | 26.15 | 27.96 | 60.33 | 68.70 | 9.33 | 0.00 | 0.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 12.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.66 | 64.86 | 62.00 | 155.41 | 148.85 | 9.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.44 | 0.22 | 2.22 | 0.00 | 138.33 | 0.00 | 0.00 | 0.00 |
February | 12.37 | 3.03 | 9.35 | 0.17 | 115.50 | 0.00 | 0.00 | 0.00 |
March | 43.44 | 18.47 | 24.97 | 31.85 | 76.90 | 0.00 | 0.00 | 0.00 |
April | 87.39 | 47.15 | 40.24 | 100.24 | 39.72 | 0.00 | 0.00 | 0.00 |
May | 113.99 | 64.86 | 49.13 | 144.03 | 19.20 | 0.00 | 0.00 | 0.00 |
June | 123.66 | 61.66 | 62.00 | 155.41 | 12.99 | 0.00 | 0.00 | 0.00 |
July | 110.94 | 53.65 | 57.29 | 135.49 | 18.20 | 0.00 | 0.00 | 0.00 |
August | 83.52 | 40.52 | 43.00 | 96.80 | 26.36 | 0.00 | 0.00 | 0.00 |
September | 45.12 | 17.86 | 27.26 | 45.58 | 35.42 | 0.00 | 0.00 | 0.00 |
October | 18.52 | 4.49 | 14.03 | 10.43 | 60.11 | 9.33 | 0.00 | 0.00 |
November | 4.64 | 0.39 | 4.26 | 0.00 | 135.66 | 0.00 | 0.00 | 0.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 148.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.11 | 26.15 | 27.96 | 60.33 | 68.70 | 9.33 | 0.00 | 0.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 12.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.66 | 64.86 | 62.00 | 155.41 | 148.85 | 9.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.44 | 0.22 | 2.22 | 0.00 | 138.33 | 0.00 | 0.00 | 0.00 |
February | 12.37 | 3.03 | 9.35 | 0.17 | 115.50 | 0.00 | 0.00 | 0.00 |
March | 43.44 | 18.47 | 24.97 | 31.85 | 76.90 | 0.00 | 0.00 | 0.00 |
April | 87.39 | 47.15 | 40.24 | 100.24 | 39.72 | 0.00 | 0.00 | 0.00 |
May | 113.99 | 64.86 | 49.13 | 144.03 | 19.20 | 0.00 | 0.00 | 0.00 |
June | 123.66 | 61.66 | 62.00 | 155.41 | 12.99 | 0.00 | 0.00 | 0.00 |
July | 110.94 | 53.65 | 57.29 | 135.49 | 18.20 | 0.00 | 0.00 | 0.00 |
August | 83.52 | 40.52 | 43.00 | 96.80 | 26.36 | 0.00 | 0.00 | 0.00 |
September | 45.12 | 17.86 | 27.26 | 45.58 | 35.42 | 0.00 | 0.00 | 0.00 |
October | 18.52 | 4.49 | 14.03 | 10.43 | 60.11 | 9.33 | 0.00 | 0.00 |
November | 4.64 | 0.39 | 4.26 | 0.00 | 135.66 | 0.00 | 0.00 | 0.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 148.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.11 | 26.15 | 27.96 | 60.33 | 68.70 | 9.33 | 0.00 | 0.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 12.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.66 | 64.86 | 62.00 | 155.41 | 148.85 | 9.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.44 | 0.22 | 2.22 | 0.00 | 138.33 | 0.00 | 0.00 | 0.00 |
February | 12.37 | 3.03 | 9.35 | 0.17 | 115.50 | 0.00 | 0.00 | 0.00 |
March | 43.44 | 18.47 | 24.97 | 31.85 | 76.90 | 0.00 | 0.00 | 0.00 |
April | 87.39 | 47.15 | 40.24 | 100.24 | 39.72 | 0.00 | 0.00 | 0.00 |
May | 113.99 | 64.86 | 49.13 | 144.03 | 19.20 | 0.00 | 0.00 | 0.00 |
June | 123.66 | 61.66 | 62.00 | 155.41 | 12.99 | 0.00 | 0.00 | 0.00 |
July | 110.94 | 53.65 | 57.29 | 135.49 | 18.20 | 0.00 | 0.00 | 0.00 |
August | 83.52 | 40.52 | 43.00 | 96.80 | 26.36 | 0.00 | 0.00 | 0.00 |
September | 45.12 | 17.86 | 27.26 | 45.58 | 35.42 | 0.00 | 0.00 | 0.00 |
October | 18.52 | 4.49 | 14.03 | 10.43 | 60.11 | 9.33 | 0.00 | 0.00 |
November | 4.64 | 0.39 | 4.26 | 0.00 | 135.66 | 0.00 | 0.00 | 0.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 148.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.11 | 26.15 | 27.96 | 60.33 | 68.70 | 9.33 | 0.00 | 0.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 12.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.66 | 64.86 | 62.00 | 155.41 | 148.85 | 9.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.44 | 0.22 | 2.22 | 0.00 | 138.33 | 0.00 | 0.00 | 0.00 |
February | 12.37 | 3.03 | 9.35 | 0.17 | 115.50 | 0.00 | 0.00 | 0.00 |
March | 43.44 | 18.47 | 24.97 | 31.85 | 76.90 | 0.00 | 0.00 | 0.00 |
April | 87.39 | 47.15 | 40.24 | 100.24 | 39.72 | 0.00 | 0.00 | 0.00 |
May | 113.99 | 64.86 | 49.13 | 144.03 | 19.20 | 0.00 | 0.00 | 0.00 |
June | 123.66 | 61.66 | 62.00 | 155.41 | 12.99 | 0.00 | 0.00 | 0.00 |
July | 110.94 | 53.65 | 57.29 | 135.49 | 18.20 | 0.00 | 0.00 | 0.00 |
August | 83.52 | 40.52 | 43.00 | 96.80 | 26.36 | 0.00 | 0.00 | 0.00 |
September | 45.12 | 17.86 | 27.26 | 45.58 | 35.42 | 0.00 | 0.00 | 0.00 |
October | 18.52 | 4.49 | 14.03 | 10.43 | 60.11 | 9.33 | 0.00 | 0.00 |
November | 4.64 | 0.39 | 4.26 | 0.00 | 135.66 | 0.00 | 0.00 | 0.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 148.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.11 | 26.15 | 27.96 | 60.33 | 68.70 | 9.33 | 0.00 | 0.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 12.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.66 | 64.86 | 62.00 | 155.41 | 148.85 | 9.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.44 | 0.22 | 2.22 | 0.00 | 138.33 | 0.00 | 0.00 | 0.00 |
February | 12.37 | 3.03 | 9.35 | 0.17 | 115.50 | 0.00 | 0.00 | 0.00 |
March | 43.44 | 18.47 | 24.97 | 31.85 | 76.90 | 0.00 | 0.00 | 0.00 |
April | 87.39 | 47.15 | 40.24 | 100.24 | 39.72 | 0.00 | 0.00 | 0.00 |
May | 113.99 | 64.86 | 49.13 | 144.03 | 19.20 | 0.00 | 0.00 | 0.00 |
June | 123.66 | 61.66 | 62.00 | 155.41 | 12.99 | 0.00 | 0.00 | 0.00 |
July | 110.94 | 53.65 | 57.29 | 135.49 | 18.20 | 0.00 | 0.00 | 0.00 |
August | 83.52 | 40.52 | 43.00 | 96.80 | 26.36 | 0.00 | 0.00 | 0.00 |
September | 45.12 | 17.86 | 27.26 | 45.58 | 35.42 | 0.00 | 0.00 | 0.00 |
October | 18.52 | 4.49 | 14.03 | 10.43 | 60.11 | 9.33 | 0.00 | 0.00 |
November | 4.64 | 0.39 | 4.26 | 0.00 | 135.66 | 0.00 | 0.00 | 0.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 148.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.11 | 26.15 | 27.96 | 60.33 | 68.70 | 9.33 | 0.00 | 0.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 12.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.66 | 64.86 | 62.00 | 155.41 | 148.85 | 9.33 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 12585264.08 | 2137577.42 | 10447686.66 | 0.00 | 0.642436E+09 |
February | 67777076.39 | 23606070.59 | 44171005.80 | 16150367.62 | 0.481707E+09 |
March | 0.226135E+09 | 97857243.62 | 0.128278E+09 | 0.147015E+09 | 0.367634E+09 |
April | 0.516980E+09 | 0.268222E+09 | 0.248758E+09 | 0.554525E+09 | 0.181121E+09 |
May | 0.518912E+09 | 0.236697E+09 | 0.282215E+09 | 0.605600E+09 | 75289100.52 |
June | 0.550646E+09 | 0.235377E+09 | 0.315269E+09 | 0.662748E+09 | 42728400.14 |
July | 0.475353E+09 | 0.179913E+09 | 0.295440E+09 | 0.563726E+09 | 60149174.01 |
August | 0.391792E+09 | 0.166611E+09 | 0.225181E+09 | 0.443662E+09 | 91499879.56 |
September | 0.228433E+09 | 95403472.71 | 0.133030E+09 | 0.218213E+09 | 0.146156E+09 |
October | 92235753.62 | 27501698.32 | 64734055.30 | 42706341.07 | 0.320240E+09 |
November | 35674091.01 | 12812997.12 | 22861093.89 | 4224538.47 | 0.592583E+09 |
December | 3316086.03 | 340650.64 | 2975435.39 | 0.00 | 0.687955E+09 |
Annual Sum or Average | 0.311984E+10 | 0.134648E+10 | 0.177336E+10 | 0.325857E+10 | 0.368950E+10 |
Minimum of Months | 3316086.03 | 340650.64 | 2975435.39 | 0.00 | 42728400.14 |
Maximum of Months | 0.550646E+09 | 0.268222E+09 | 0.315269E+09 | 0.662748E+09 | 0.687955E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 12585264.08 | 2137577.42 | 10447686.66 | 0.00 | 0.642436E+09 |
February | 67777076.39 | 23606070.59 | 44171005.80 | 16150367.62 | 0.481707E+09 |
March | 0.226135E+09 | 97857243.62 | 0.128278E+09 | 0.147015E+09 | 0.367634E+09 |
April | 0.516980E+09 | 0.268222E+09 | 0.248758E+09 | 0.554525E+09 | 0.181121E+09 |
May | 0.518912E+09 | 0.236697E+09 | 0.282215E+09 | 0.605600E+09 | 75289100.52 |
June | 0.550646E+09 | 0.235377E+09 | 0.315269E+09 | 0.662748E+09 | 42728400.14 |
July | 0.475353E+09 | 0.179913E+09 | 0.295440E+09 | 0.563726E+09 | 60149174.01 |
August | 0.391792E+09 | 0.166611E+09 | 0.225181E+09 | 0.443662E+09 | 91499879.56 |
September | 0.228433E+09 | 95403472.71 | 0.133030E+09 | 0.218213E+09 | 0.146156E+09 |
October | 92235753.62 | 27501698.32 | 64734055.30 | 42706341.07 | 0.320240E+09 |
November | 35674091.01 | 12812997.12 | 22861093.89 | 4224538.47 | 0.592583E+09 |
December | 3316086.03 | 340650.64 | 2975435.39 | 0.00 | 0.687955E+09 |
Annual Sum or Average | 0.311984E+10 | 0.134648E+10 | 0.177336E+10 | 0.325857E+10 | 0.368950E+10 |
Minimum of Months | 3316086.03 | 340650.64 | 2975435.39 | 0.00 | 42728400.14 |
Maximum of Months | 0.550646E+09 | 0.268222E+09 | 0.315269E+09 | 0.662748E+09 | 0.687955E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 5336011.68 | 0.00 | 5336011.68 | 0.00 | 0.379349E+09 |
February | 21305066.83 | 0.00 | 21305066.83 | 0.00 | 0.300521E+09 |
March | 63272979.64 | 18892.60 | 63254087.04 | 8252518.19 | 0.235123E+09 |
April | 0.111289E+09 | 3001191.94 | 0.108288E+09 | 64078973.16 | 0.106486E+09 |
May | 0.176115E+09 | 28157904.89 | 0.147957E+09 | 0.179619E+09 | 39240580.75 |
June | 0.219951E+09 | 48108939.50 | 0.171842E+09 | 0.246335E+09 | 19608739.67 |
July | 0.191773E+09 | 31367267.56 | 0.160406E+09 | 0.209689E+09 | 30236022.40 |
August | 0.123179E+09 | 6500140.13 | 0.116679E+09 | 0.112965E+09 | 50501909.08 |
September | 66389520.56 | 178450.79 | 66211069.77 | 37083067.53 | 88103995.34 |
October | 33206161.12 | 0.00 | 33206161.12 | 4755031.13 | 0.197654E+09 |
November | 9972625.53 | 0.00 | 9972625.53 | 0.00 | 0.360702E+09 |
December | 1618666.00 | 0.00 | 1618666.00 | 0.00 | 0.402710E+09 |
Annual Sum or Average | 0.102341E+10 | 0.117333E+09 | 0.906075E+09 | 0.862778E+09 | 0.221023E+10 |
Minimum of Months | 1618666.00 | 0.00 | 1618666.00 | 0.00 | 19608739.67 |
Maximum of Months | 0.219951E+09 | 48108939.50 | 0.171842E+09 | 0.246335E+09 | 0.402710E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 5335818.80 | 0.00 | 5335818.80 | 0.00 | 0.379348E+09 |
February | 21304345.52 | 0.00 | 21304345.52 | 0.00 | 0.300521E+09 |
March | 63270965.05 | 18891.72 | 63252073.33 | 8251540.63 | 0.235123E+09 |
April | 0.111285E+09 | 3001051.27 | 0.108284E+09 | 64075559.99 | 0.106486E+09 |
May | 0.176109E+09 | 28156585.09 | 0.147953E+09 | 0.179611E+09 | 39240374.74 |
June | 0.219943E+09 | 48106684.57 | 0.171836E+09 | 0.246325E+09 | 19608644.44 |
July | 0.191766E+09 | 31365797.34 | 0.160400E+09 | 0.209680E+09 | 30235915.02 |
August | 0.123175E+09 | 6499835.46 | 0.116675E+09 | 0.112960E+09 | 50501662.22 |
September | 66387327.10 | 178442.42 | 66208884.68 | 37080910.30 | 88103915.14 |
October | 33205023.58 | 0.00 | 33205023.58 | 4754598.49 | 0.197654E+09 |
November | 9972265.08 | 0.00 | 9972265.08 | 0.00 | 0.360701E+09 |
December | 1618604.93 | 0.00 | 1618604.93 | 0.00 | 0.402709E+09 |
Annual Sum or Average | 0.102337E+10 | 0.117327E+09 | 0.906046E+09 | 0.862739E+09 | 0.221023E+10 |
Minimum of Months | 1618604.93 | 0.00 | 1618604.93 | 0.00 | 19608644.44 |
Maximum of Months | 0.219943E+09 | 48106684.57 | 0.171836E+09 | 0.246325E+09 | 0.402709E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6546105.47 | 597225.44 | 5948880.03 | 0.00 | 0.370505E+09 |
February | 29934670.29 | 7325881.42 | 22608788.87 | 401741.07 | 0.279423E+09 |
March | 0.116348E+09 | 49472675.65 | 66874972.33 | 85310602.35 | 0.205982E+09 |
April | 0.226510E+09 | 0.122207E+09 | 0.104303E+09 | 0.259833E+09 | 0.102959E+09 |
May | 0.305308E+09 | 0.173722E+09 | 0.131586E+09 | 0.385775E+09 | 51423613.48 |
June | 0.320521E+09 | 0.159811E+09 | 0.160711E+09 | 0.402834E+09 | 33672365.39 |
July | 0.297144E+09 | 0.143687E+09 | 0.153457E+09 | 0.362902E+09 | 48746545.71 |
August | 0.223692E+09 | 0.108530E+09 | 0.115162E+09 | 0.259280E+09 | 70603433.09 |
September | 0.116950E+09 | 46298188.78 | 70651973.15 | 0.118153E+09 | 91797976.53 |
October | 49603267.26 | 12029681.11 | 37573586.15 | 27944290.55 | 0.161009E+09 |
November | 12036261.84 | 999940.01 | 11036321.83 | 0.00 | 0.351622E+09 |
December | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 0.398686E+09 |
Annual Sum or Average | 0.170643E+10 | 0.824715E+09 | 0.881713E+09 | 0.190243E+10 | 0.216643E+10 |
Minimum of Months | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 33672365.39 |
Maximum of Months | 0.320521E+09 | 0.173722E+09 | 0.160711E+09 | 0.402834E+09 | 0.398686E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6546105.47 | 597225.44 | 5948880.03 | 0.00 | 0.370505E+09 |
February | 29934670.29 | 7325881.42 | 22608788.87 | 401741.07 | 0.279423E+09 |
March | 0.116348E+09 | 49472675.65 | 66874972.33 | 85310602.35 | 0.205982E+09 |
April | 0.226510E+09 | 0.122207E+09 | 0.104303E+09 | 0.259833E+09 | 0.102959E+09 |
May | 0.305308E+09 | 0.173722E+09 | 0.131586E+09 | 0.385775E+09 | 51423613.48 |
June | 0.320521E+09 | 0.159811E+09 | 0.160711E+09 | 0.402834E+09 | 33672365.39 |
July | 0.297144E+09 | 0.143687E+09 | 0.153457E+09 | 0.362902E+09 | 48746545.71 |
August | 0.223692E+09 | 0.108530E+09 | 0.115162E+09 | 0.259280E+09 | 70603433.09 |
September | 0.116950E+09 | 46298188.78 | 70651973.15 | 0.118153E+09 | 91797976.53 |
October | 49603267.26 | 12029681.11 | 37573586.15 | 27944290.55 | 0.161009E+09 |
November | 12036261.84 | 999940.01 | 11036321.83 | 0.00 | 0.351622E+09 |
December | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 0.398686E+09 |
Annual Sum or Average | 0.170643E+10 | 0.824715E+09 | 0.881713E+09 | 0.190243E+10 | 0.216643E+10 |
Minimum of Months | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 33672365.39 |
Maximum of Months | 0.320521E+09 | 0.173722E+09 | 0.160711E+09 | 0.402834E+09 | 0.398686E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6546105.47 | 597225.44 | 5948880.03 | 0.00 | 0.370505E+09 |
February | 29934670.29 | 7325881.42 | 22608788.87 | 401741.07 | 0.279423E+09 |
March | 0.116348E+09 | 49472675.65 | 66874972.33 | 85310602.35 | 0.205982E+09 |
April | 0.226510E+09 | 0.122207E+09 | 0.104303E+09 | 0.259833E+09 | 0.102959E+09 |
May | 0.305308E+09 | 0.173722E+09 | 0.131586E+09 | 0.385775E+09 | 51423613.48 |
June | 0.320521E+09 | 0.159811E+09 | 0.160711E+09 | 0.402834E+09 | 33672365.39 |
July | 0.297144E+09 | 0.143687E+09 | 0.153457E+09 | 0.362902E+09 | 48746545.71 |
August | 0.223692E+09 | 0.108530E+09 | 0.115162E+09 | 0.259280E+09 | 70603433.09 |
September | 0.116950E+09 | 46298188.78 | 70651973.15 | 0.118153E+09 | 91797976.53 |
October | 49603267.26 | 12029681.11 | 37573586.15 | 27944290.55 | 0.161009E+09 |
November | 12036261.84 | 999940.01 | 11036321.83 | 0.00 | 0.351622E+09 |
December | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 0.398686E+09 |
Annual Sum or Average | 0.170643E+10 | 0.824715E+09 | 0.881713E+09 | 0.190243E+10 | 0.216643E+10 |
Minimum of Months | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 33672365.39 |
Maximum of Months | 0.320521E+09 | 0.173722E+09 | 0.160711E+09 | 0.402834E+09 | 0.398686E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6546105.47 | 597225.44 | 5948880.03 | 0.00 | 0.370505E+09 |
February | 29934670.29 | 7325881.42 | 22608788.87 | 401741.07 | 0.279423E+09 |
March | 0.116348E+09 | 49472675.65 | 66874972.33 | 85310602.35 | 0.205982E+09 |
April | 0.226510E+09 | 0.122207E+09 | 0.104303E+09 | 0.259833E+09 | 0.102959E+09 |
May | 0.305308E+09 | 0.173722E+09 | 0.131586E+09 | 0.385775E+09 | 51423613.48 |
June | 0.320521E+09 | 0.159811E+09 | 0.160711E+09 | 0.402834E+09 | 33672365.39 |
July | 0.297144E+09 | 0.143687E+09 | 0.153457E+09 | 0.362902E+09 | 48746545.71 |
August | 0.223692E+09 | 0.108530E+09 | 0.115162E+09 | 0.259280E+09 | 70603433.09 |
September | 0.116950E+09 | 46298188.78 | 70651973.15 | 0.118153E+09 | 91797976.53 |
October | 49603267.26 | 12029681.11 | 37573586.15 | 27944290.55 | 0.161009E+09 |
November | 12036261.84 | 999940.01 | 11036321.83 | 0.00 | 0.351622E+09 |
December | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 0.398686E+09 |
Annual Sum or Average | 0.170643E+10 | 0.824715E+09 | 0.881713E+09 | 0.190243E+10 | 0.216643E+10 |
Minimum of Months | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 33672365.39 |
Maximum of Months | 0.320521E+09 | 0.173722E+09 | 0.160711E+09 | 0.402834E+09 | 0.398686E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6546105.47 | 597225.44 | 5948880.03 | 0.00 | 0.370505E+09 |
February | 29934670.29 | 7325881.42 | 22608788.87 | 401741.07 | 0.279423E+09 |
March | 0.116348E+09 | 49472675.65 | 66874972.33 | 85310602.35 | 0.205982E+09 |
April | 0.226510E+09 | 0.122207E+09 | 0.104303E+09 | 0.259833E+09 | 0.102959E+09 |
May | 0.305308E+09 | 0.173722E+09 | 0.131586E+09 | 0.385775E+09 | 51423613.48 |
June | 0.320521E+09 | 0.159811E+09 | 0.160711E+09 | 0.402834E+09 | 33672365.39 |
July | 0.297144E+09 | 0.143687E+09 | 0.153457E+09 | 0.362902E+09 | 48746545.71 |
August | 0.223692E+09 | 0.108530E+09 | 0.115162E+09 | 0.259280E+09 | 70603433.09 |
September | 0.116950E+09 | 46298188.78 | 70651973.15 | 0.118153E+09 | 91797976.53 |
October | 49603267.26 | 12029681.11 | 37573586.15 | 27944290.55 | 0.161009E+09 |
November | 12036261.84 | 999940.01 | 11036321.83 | 0.00 | 0.351622E+09 |
December | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 0.398686E+09 |
Annual Sum or Average | 0.170643E+10 | 0.824715E+09 | 0.881713E+09 | 0.190243E+10 | 0.216643E+10 |
Minimum of Months | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 33672365.39 |
Maximum of Months | 0.320521E+09 | 0.173722E+09 | 0.160711E+09 | 0.402834E+09 | 0.398686E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6546105.47 | 597225.44 | 5948880.03 | 0.00 | 0.370505E+09 |
February | 29934670.29 | 7325881.42 | 22608788.87 | 401741.07 | 0.279423E+09 |
March | 0.116348E+09 | 49472675.65 | 66874972.33 | 85310602.35 | 0.205982E+09 |
April | 0.226510E+09 | 0.122207E+09 | 0.104303E+09 | 0.259833E+09 | 0.102959E+09 |
May | 0.305308E+09 | 0.173722E+09 | 0.131586E+09 | 0.385775E+09 | 51423613.48 |
June | 0.320521E+09 | 0.159811E+09 | 0.160711E+09 | 0.402834E+09 | 33672365.39 |
July | 0.297144E+09 | 0.143687E+09 | 0.153457E+09 | 0.362902E+09 | 48746545.71 |
August | 0.223692E+09 | 0.108530E+09 | 0.115162E+09 | 0.259280E+09 | 70603433.09 |
September | 0.116950E+09 | 46298188.78 | 70651973.15 | 0.118153E+09 | 91797976.53 |
October | 49603267.26 | 12029681.11 | 37573586.15 | 27944290.55 | 0.161009E+09 |
November | 12036261.84 | 999940.01 | 11036321.83 | 0.00 | 0.351622E+09 |
December | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 0.398686E+09 |
Annual Sum or Average | 0.170643E+10 | 0.824715E+09 | 0.881713E+09 | 0.190243E+10 | 0.216643E+10 |
Minimum of Months | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 33672365.39 |
Maximum of Months | 0.320521E+09 | 0.173722E+09 | 0.160711E+09 | 0.402834E+09 | 0.398686E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6546105.47 | 597225.44 | 5948880.03 | 0.00 | 0.370505E+09 |
February | 29934670.29 | 7325881.42 | 22608788.87 | 401741.07 | 0.279423E+09 |
March | 0.116348E+09 | 49472675.65 | 66874972.33 | 85310602.35 | 0.205982E+09 |
April | 0.226510E+09 | 0.122207E+09 | 0.104303E+09 | 0.259833E+09 | 0.102959E+09 |
May | 0.305308E+09 | 0.173722E+09 | 0.131586E+09 | 0.385775E+09 | 51423613.48 |
June | 0.320521E+09 | 0.159811E+09 | 0.160711E+09 | 0.402834E+09 | 33672365.39 |
July | 0.297144E+09 | 0.143687E+09 | 0.153457E+09 | 0.362902E+09 | 48746545.71 |
August | 0.223692E+09 | 0.108530E+09 | 0.115162E+09 | 0.259280E+09 | 70603433.09 |
September | 0.116950E+09 | 46298188.78 | 70651973.15 | 0.118153E+09 | 91797976.53 |
October | 49603267.26 | 12029681.11 | 37573586.15 | 27944290.55 | 0.161009E+09 |
November | 12036261.84 | 999940.01 | 11036321.83 | 0.00 | 0.351622E+09 |
December | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 0.398686E+09 |
Annual Sum or Average | 0.170643E+10 | 0.824715E+09 | 0.881713E+09 | 0.190243E+10 | 0.216643E+10 |
Minimum of Months | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 33672365.39 |
Maximum of Months | 0.320521E+09 | 0.173722E+09 | 0.160711E+09 | 0.402834E+09 | 0.398686E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6546105.47 | 597225.44 | 5948880.03 | 0.00 | 0.370505E+09 |
February | 29934670.29 | 7325881.42 | 22608788.87 | 401741.07 | 0.279423E+09 |
March | 0.116348E+09 | 49472675.65 | 66874972.33 | 85310602.35 | 0.205982E+09 |
April | 0.226510E+09 | 0.122207E+09 | 0.104303E+09 | 0.259833E+09 | 0.102959E+09 |
May | 0.305308E+09 | 0.173722E+09 | 0.131586E+09 | 0.385775E+09 | 51423613.48 |
June | 0.320521E+09 | 0.159811E+09 | 0.160711E+09 | 0.402834E+09 | 33672365.39 |
July | 0.297144E+09 | 0.143687E+09 | 0.153457E+09 | 0.362902E+09 | 48746545.71 |
August | 0.223692E+09 | 0.108530E+09 | 0.115162E+09 | 0.259280E+09 | 70603433.09 |
September | 0.116950E+09 | 46298188.78 | 70651973.15 | 0.118153E+09 | 91797976.53 |
October | 49603267.26 | 12029681.11 | 37573586.15 | 27944290.55 | 0.161009E+09 |
November | 12036261.84 | 999940.01 | 11036321.83 | 0.00 | 0.351622E+09 |
December | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 0.398686E+09 |
Annual Sum or Average | 0.170643E+10 | 0.824715E+09 | 0.881713E+09 | 0.190243E+10 | 0.216643E+10 |
Minimum of Months | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 33672365.39 |
Maximum of Months | 0.320521E+09 | 0.173722E+09 | 0.160711E+09 | 0.402834E+09 | 0.398686E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6546105.47 | 597225.44 | 5948880.03 | 0.00 | 0.370505E+09 |
February | 29934670.29 | 7325881.42 | 22608788.87 | 401741.07 | 0.279423E+09 |
March | 0.116348E+09 | 49472675.65 | 66874972.33 | 85310602.35 | 0.205982E+09 |
April | 0.226510E+09 | 0.122207E+09 | 0.104303E+09 | 0.259833E+09 | 0.102959E+09 |
May | 0.305308E+09 | 0.173722E+09 | 0.131586E+09 | 0.385775E+09 | 51423613.48 |
June | 0.320521E+09 | 0.159811E+09 | 0.160711E+09 | 0.402834E+09 | 33672365.39 |
July | 0.297144E+09 | 0.143687E+09 | 0.153457E+09 | 0.362902E+09 | 48746545.71 |
August | 0.223692E+09 | 0.108530E+09 | 0.115162E+09 | 0.259280E+09 | 70603433.09 |
September | 0.116950E+09 | 46298188.78 | 70651973.15 | 0.118153E+09 | 91797976.53 |
October | 49603267.26 | 12029681.11 | 37573586.15 | 27944290.55 | 0.161009E+09 |
November | 12036261.84 | 999940.01 | 11036321.83 | 0.00 | 0.351622E+09 |
December | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 0.398686E+09 |
Annual Sum or Average | 0.170643E+10 | 0.824715E+09 | 0.881713E+09 | 0.190243E+10 | 0.216643E+10 |
Minimum of Months | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 33672365.39 |
Maximum of Months | 0.320521E+09 | 0.173722E+09 | 0.160711E+09 | 0.402834E+09 | 0.398686E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6546105.47 | 597225.44 | 5948880.03 | 0.00 | 0.370505E+09 |
February | 29934670.29 | 7325881.42 | 22608788.87 | 401741.07 | 0.279423E+09 |
March | 0.116348E+09 | 49472675.65 | 66874972.33 | 85310602.35 | 0.205982E+09 |
April | 0.226510E+09 | 0.122207E+09 | 0.104303E+09 | 0.259833E+09 | 0.102959E+09 |
May | 0.305308E+09 | 0.173722E+09 | 0.131586E+09 | 0.385775E+09 | 51423613.48 |
June | 0.320521E+09 | 0.159811E+09 | 0.160711E+09 | 0.402834E+09 | 33672365.39 |
July | 0.297144E+09 | 0.143687E+09 | 0.153457E+09 | 0.362902E+09 | 48746545.71 |
August | 0.223692E+09 | 0.108530E+09 | 0.115162E+09 | 0.259280E+09 | 70603433.09 |
September | 0.116950E+09 | 46298188.78 | 70651973.15 | 0.118153E+09 | 91797976.53 |
October | 49603267.26 | 12029681.11 | 37573586.15 | 27944290.55 | 0.161009E+09 |
November | 12036261.84 | 999940.01 | 11036321.83 | 0.00 | 0.351622E+09 |
December | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 0.398686E+09 |
Annual Sum or Average | 0.170643E+10 | 0.824715E+09 | 0.881713E+09 | 0.190243E+10 | 0.216643E+10 |
Minimum of Months | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 33672365.39 |
Maximum of Months | 0.320521E+09 | 0.173722E+09 | 0.160711E+09 | 0.402834E+09 | 0.398686E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 762.98 | 13.38 | 1.60 | 11.79 | 0.00 | 0.00 |
February | 6.23 | 639.56 | 73.65 | 19.52 | 54.13 | 0.00 | 0.00 |
March | 105.07 | 439.21 | 216.10 | 73.09 | 143.02 | 0.00 | 0.00 |
April | 473.66 | 218.26 | 484.77 | 209.28 | 275.50 | 0.00 | 0.00 |
May | 580.53 | 79.72 | 518.98 | 197.77 | 321.21 | 0.00 | 0.00 |
June | 695.94 | 42.60 | 594.59 | 218.74 | 375.85 | 0.00 | 0.00 |
July | 572.71 | 62.68 | 498.15 | 157.77 | 340.38 | 0.00 | 0.00 |
August | 411.49 | 101.88 | 384.53 | 129.26 | 255.27 | 0.00 | 0.00 |
September | 194.66 | 178.43 | 227.49 | 73.75 | 153.73 | 0.00 | 0.00 |
October | 31.15 | 382.43 | 93.67 | 20.54 | 73.13 | 0.00 | 0.00 |
November | 1.03 | 733.33 | 35.22 | 9.89 | 25.33 | 0.00 | 0.00 |
December | 0.00 | 814.41 | 3.68 | 0.25 | 3.43 | 0.00 | 0.00 |
Annual Sum or Average | 257.16 | 369.94 | 262.76 | 92.83 | 169.93 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 42.60 | 3.68 | 0.25 | 3.43 | 0.00 | 0.00 |
Maximum of Months | 695.94 | 814.41 | 594.59 | 218.74 | 375.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 10412.18 | 24.44 | 2.23 | 22.21 | 0.00 | 0.00 |
February | 8.44 | 9318.61 | 123.74 | 30.28 | 93.46 | 0.00 | 0.00 |
March | 1636.10 | 6276.30 | 434.39 | 184.71 | 249.68 | 0.00 | 0.00 |
April | 4574.66 | 2837.53 | 873.88 | 471.48 | 402.41 | 0.00 | 0.00 |
May | 5642.93 | 702.87 | 1139.89 | 648.60 | 491.29 | 0.00 | 0.00 |
June | 6092.28 | 389.94 | 1236.58 | 616.55 | 620.03 | 0.00 | 0.00 |
July | 5241.78 | 546.20 | 1109.41 | 536.47 | 572.94 | 0.00 | 0.00 |
August | 3891.86 | 814.51 | 835.17 | 405.20 | 429.97 | 0.00 | 0.00 |
September | 1843.20 | 1486.67 | 451.20 | 178.62 | 272.58 | 0.00 | 0.00 |
October | 470.75 | 3891.40 | 185.20 | 44.91 | 140.28 | 0.00 | 0.00 |
November | 0.00 | 9213.03 | 46.44 | 3.86 | 42.58 | 0.00 | 0.00 |
December | 0.00 | 10551.84 | 6.85 | 0.13 | 6.72 | 0.00 | 0.00 |
Annual Sum or Average | 2462.81 | 4678.88 | 541.10 | 261.52 | 279.59 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 389.94 | 6.85 | 0.13 | 6.72 | 0.00 | 0.00 |
Maximum of Months | 6092.28 | 10551.84 | 1236.58 | 648.60 | 620.03 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.204357E+10 | 35842358.65 | 4275154.85 | 31567203.80 | 0.00 | 0.00 |
February | 15080243.79 | 0.154724E+10 | 0.178164E+09 | 47212141.19 | 0.130951E+09 | 0.00 | 0.00 |
March | 0.281409E+09 | 0.117639E+10 | 0.578814E+09 | 0.195752E+09 | 0.383061E+09 | 0.00 | 0.00 |
April | 0.122773E+10 | 0.565742E+09 | 0.125653E+10 | 0.542445E+09 | 0.714088E+09 | 0.00 | 0.00 |
May | 0.155489E+10 | 0.213522E+09 | 0.139005E+10 | 0.529709E+09 | 0.860339E+09 | 0.00 | 0.00 |
June | 0.180389E+10 | 0.110407E+09 | 0.154119E+10 | 0.566970E+09 | 0.974216E+09 | 0.00 | 0.00 |
July | 0.153394E+10 | 0.167891E+09 | 0.133425E+10 | 0.422559E+09 | 0.911687E+09 | 0.00 | 0.00 |
August | 0.110213E+10 | 0.272883E+09 | 0.102994E+10 | 0.346222E+09 | 0.683716E+09 | 0.00 | 0.00 |
September | 0.504559E+09 | 0.462489E+09 | 0.589644E+09 | 0.191164E+09 | 0.398480E+09 | 0.00 | 0.00 |
October | 83436925.80 | 0.102430E+10 | 0.250883E+09 | 55003396.64 | 0.195879E+09 | 0.00 | 0.00 |
November | 2673287.92 | 0.190079E+10 | 91293072.63 | 25625994.25 | 65667078.39 | 0.00 | 0.00 |
December | 0.00 | 0.218133E+10 | 9869442.99 | 681301.28 | 9188141.71 | 0.00 | 0.00 |
Annual Sum or Average | 0.810974E+10 | 0.116665E+11 | 0.828646E+10 | 0.292762E+10 | 0.535884E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.110407E+09 | 9869442.99 | 681301.28 | 9188141.71 | 0.00 | 0.00 |
Maximum of Months | 0.180389E+10 | 0.218133E+10 | 0.154119E+10 | 0.566970E+09 | 0.974216E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.278880E+11 | 65461054.70 | 5972254.40 | 59488800.30 | 0.00 | 0.00 |
February | 20414840.73 | 0.225436E+11 | 0.299347E+09 | 73258814.24 | 0.226088E+09 | 0.00 | 0.00 |
March | 0.438213E+10 | 0.168104E+11 | 0.116348E+10 | 0.494727E+09 | 0.668750E+09 | 0.00 | 0.00 |
April | 0.118575E+11 | 0.735488E+10 | 0.226510E+10 | 0.122207E+10 | 0.104303E+10 | 0.00 | 0.00 |
May | 0.151140E+11 | 0.188257E+10 | 0.305308E+10 | 0.173722E+10 | 0.131586E+10 | 0.00 | 0.00 |
June | 0.157912E+11 | 0.101073E+10 | 0.320521E+10 | 0.159811E+10 | 0.160711E+10 | 0.00 | 0.00 |
July | 0.140396E+11 | 0.146294E+10 | 0.297144E+10 | 0.143687E+10 | 0.153457E+10 | 0.00 | 0.00 |
August | 0.104239E+11 | 0.218158E+10 | 0.223692E+10 | 0.108530E+10 | 0.115162E+10 | 0.00 | 0.00 |
September | 0.477758E+10 | 0.385345E+10 | 0.116950E+10 | 0.462982E+09 | 0.706520E+09 | 0.00 | 0.00 |
October | 0.126085E+10 | 0.104227E+11 | 0.496033E+09 | 0.120297E+09 | 0.375736E+09 | 0.00 | 0.00 |
November | 0.00 | 0.238802E+11 | 0.120363E+09 | 9999400.12 | 0.110363E+09 | 0.00 | 0.00 |
December | 0.00 | 0.282620E+11 | 18345670.88 | 349673.56 | 17995997.32 | 0.00 | 0.00 |
Annual Sum or Average | 0.776672E+11 | 0.147553E+12 | 0.170643E+11 | 0.824715E+10 | 0.881713E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.101073E+10 | 18345670.88 | 349673.56 | 17995997.32 | 0.00 | 0.00 |
Maximum of Months | 0.157912E+11 | 0.282620E+11 | 0.320521E+10 | 0.173722E+10 | 0.160711E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.6 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.7 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.25 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.88 | 6.41 | 3.45 | 5.66 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.85 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.70 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.45 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.85 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.7 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.7 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.60 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.03 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.79 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.30 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.34 | 11.70 | 4.67 | 18.88 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.77 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.91 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 8.01 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.6 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.1 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.6 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.34 | 11.70 | 6.20 | 18.88 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.2 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.3 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.1 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.9 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.7 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.24 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.65 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.03 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.97 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.33 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.36 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.29 | 141.00 | 225.33 |
August | 16.14 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.82 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 8.01 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.6 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.1 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.36 | 29.07 | 14.40 | 8.80 | 19.29 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.7 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.78 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.75 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.41 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.30 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.1 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.5 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.1 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.114175E+10 | -0.105362E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -88124900.2 | 59.00 | 0.00 | 0.00 |
February | 0.104749E+10 | -967993834.2 | 0.00 | 0.00 | 672.00 | 0.00 | -79494718.0 | 59.00 | 0.00 | 0.00 |
March | 0.121906E+10 | -0.113140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -87665933.5 | 59.00 | 0.00 | 0.00 |
April | 0.113547E+10 | -0.105103E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -84439794.7 | 59.00 | 0.00 | 0.00 |
May | 0.117004E+10 | -0.108504E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -85005956.0 | 59.00 | 0.00 | 0.00 |
June | 0.111716E+10 | -0.104139E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -75762976.3 | 59.00 | 0.00 | 0.00 |
July | 0.104423E+10 | -968520952.8 | 0.00 | 0.00 | 744.00 | 0.00 | -75708522.0 | 58.99 | 0.00 | 0.00 |
August | 0.109226E+10 | -0.101498E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -77280607.8 | 58.99 | 0.00 | 0.00 |
September | 0.102217E+10 | -940058299.6 | 0.00 | 0.00 | 720.00 | 0.00 | -82109293.3 | 58.99 | 0.00 | 0.00 |
October | 0.104842E+10 | -960832849.6 | 0.00 | 0.00 | 744.00 | 0.00 | -87590186.0 | 58.99 | 0.00 | 0.00 |
November | 0.104118E+10 | -955931213.1 | 0.00 | 0.00 | 720.00 | 0.00 | -85244444.6 | 59.00 | 0.00 | 0.00 |
December | 0.112432E+10 | -0.103624E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -88073815.0 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132035E+11 | -0.122070E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -996501147.4 | 59.00 | 0.00 | 0.00 |
Minimum of Months | 0.102217E+10 | -0.113140E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -88124900.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.121906E+10 | -940058299.6 | 0.00 | 0.00 | 744.00 | 0.00 | -75708522.0 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 108.67 | 0.98 | 0.94 | 31-JAN-11:30 | 27.87 | 2.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 205.83 | 0.96 | 0.88 | 23-FEB-11:09 | 64.78 | 6.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 329.50 | 0.94 | 0.88 | 05-MAR-10:20 | 121.25 | 9.31 | 0.00 | 54.83 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 421.83 | 0.93 | 0.88 | 01-APR-09:39 | 149.93 | 10.18 | 0.00 | 92.83 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 545.00 | 0.92 | 0.88 | 01-MAY-06:00 | 169.43 | 10.47 | 0.00 | 181.17 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 583.50 | 0.92 | 0.88 | 01-JUN-06:19 | 518.28 | 10.76 | 0.00 | 282.17 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 562.83 | 0.92 | 0.88 | 01-JUL-05:30 | 195.34 | 10.93 | 0.00 | 244.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 467.17 | 0.92 | 0.88 | 01-AUG-06:40 | 168.42 | 10.61 | 0.00 | 155.33 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 356.33 | 0.93 | 0.88 | 01-SEP-07:49 | 126.00 | 9.51 | 0.00 | 42.50 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 265.50 | 0.95 | 0.88 | 01-OCT-09:20 | 89.65 | 7.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 135.83 | 0.98 | 0.92 | 06-NOV-13:30 | 38.36 | 2.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71.17 | 1.00 | 0.98 | 04-DEC-11:30 | 8.80 | 0.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.93 | 191.82 | 9.31 | 0.00 | 1052.83 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 71.17 | 0.92 | 0.88 | 8.80 | 0.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 1.00 | 0.98 | 518.28 | 10.93 | 0.00 | 282.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.96 | 0.90 | 31-JAN-11:30 | 46.37 | 12.74 | 0.00 | 0.00 | 22.64 | 12.41 | 0.00 | 0.00 |
February | 205.83 | 0.90 | 0.77 | 28-FEB-15:20 | 109.31 | 17.90 | 16.83 | 0.00 | 56.52 | 17.62 | 4.50 | 0.00 |
March | 329.50 | 0.81 | 0.61 | 12-MAR-17:10 | 316.11 | 23.30 | 152.17 | 31.17 | 132.40 | 22.17 | 139.00 | 8.50 |
April | 421.83 | 0.75 | 0.61 | 01-APR-15:30 | 549.72 | 23.67 | 230.17 | 133.00 | 427.47 | 23.81 | 259.17 | 87.33 |
May | 545.00 | 0.76 | 0.61 | 01-MAY-16:00 | 267.28 | 20.43 | 231.67 | 98.17 | 268.87 | 21.48 | 294.50 | 83.17 |
June | 583.50 | 0.74 | 0.61 | 01-JUN-15:09 | 287.28 | 20.25 | 254.00 | 118.17 | 205.78 | 21.19 | 322.67 | 73.00 |
July | 562.83 | 0.75 | 0.61 | 02-JUL-15:09 | 277.67 | 20.24 | 233.00 | 117.17 | 254.88 | 21.19 | 287.00 | 68.67 |
August | 467.17 | 0.77 | 0.61 | 01-AUG-16:10 | 381.78 | 22.10 | 207.67 | 86.50 | 315.46 | 22.68 | 240.67 | 59.67 |
September | 356.33 | 0.81 | 0.61 | 02-SEP-16:19 | 387.61 | 23.98 | 163.50 | 50.50 | 141.65 | 22.34 | 155.17 | 11.50 |
October | 265.50 | 0.88 | 0.66 | 01-OCT-15:30 | 152.04 | 20.65 | 47.17 | 10.00 | 63.60 | 18.44 | 13.17 | 0.00 |
November | 135.83 | 0.94 | 0.85 | 06-NOV-13:30 | 64.58 | 14.93 | 0.00 | 0.00 | 33.24 | 14.55 | 0.00 | 0.00 |
December | 71.17 | 0.99 | 0.96 | 05-DEC-11:30 | 16.37 | 6.52 | 0.00 | 0.00 | 7.71 | 6.18 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.79 | 296.05 | 20.70 | 1536.17 | 644.67 | 214.13 | 20.77 | 1715.83 | 391.83 | ||
Minimum of Months | 71.17 | 0.74 | 0.61 | 16.37 | 6.52 | 0.00 | 0.00 | 7.71 | 6.18 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.99 | 0.96 | 549.72 | 23.98 | 254.00 | 133.00 | 427.47 | 23.81 | 322.67 | 87.33 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.154276E+11 | 26873.36 | 01-JAN-06:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130629E+11 | 26873.36 | 01-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130695E+11 | 26873.36 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.693364E+10 | 26873.36 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.220437E+10 | 26873.36 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.127337E+09 | 26873.36 | 01-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17298001.48 | 15812.92 | 06-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.165106E+09 | 26873.36 | 21-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.290240E+10 | 26873.36 | 01-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.795728E+10 | 26873.36 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125246E+11 | 26873.36 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148570E+11 | 26873.36 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.892491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 17298001.48 | 15812.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.154276E+11 | 26873.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.566607E+11 | 66598.52 | 01-JAN-00:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.472548E+11 | 66598.52 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.429331E+11 | 66598.52 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202311E+11 | 66598.52 | 01-APR-00:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.189789E+10 | 59286.88 | 05-MAY-05:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.342631E+10 | 65222.53 | 29-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.260687E+11 | 66598.52 | 12-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.454778E+11 | 66598.52 | 01-NOV-00:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.560921E+11 | 66598.52 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.300042E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.566607E+11 | 66598.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.151002E+12 | 102865.05 | 02-JAN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125808E+12 | 102865.05 | 01-FEB-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117940E+12 | 102865.05 | 02-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.519084E+11 | 102865.05 | 02-APR-19:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.656806E+09 | 21213.75 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.650206E+11 | 89095.09 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105223E+12 | 94937.61 | 10-NOV-01:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147934E+12 | 102865.05 | 01-DEC-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.765493E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.151002E+12 | 102865.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.109065E+10 | 0.104160E+10 | 5174.54 | 30-JUN-15:10 | 4736.56 | 0.00 |
July | 0.00 | 0.00 | 0.257055E+10 | 0.235429E+10 | 6575.30 | 29-JUL-16:00 | 6167.38 | 0.00 |
August | 0.00 | 0.00 | 0.145906E+10 | 0.133945E+10 | 5639.56 | 05-AUG-06:05 | 5639.56 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.512026E+10 | 0.473534E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.257055E+10 | 0.235429E+10 | 6575.30 | 6167.38 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 13124214.21 | 13122630.95 | 2363.39 | 29-JUL-16:00 | 2363.39 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 13124214.21 | 13122630.95 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 13124214.21 | 13122630.95 | 2363.39 | 2363.39 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.635344E+09 | 0.08 | 237.21 | 01-JAN-00:02 | 0.08 |
February | 0.573716E+09 | 0.08 | 237.21 | 01-FEB-00:02 | 0.08 |
March | 0.604815E+09 | 0.07 | 237.21 | 01-MAR-00:02 | 0.08 |
April | 0.360844E+09 | 0.05 | 237.21 | 01-APR-00:05 | 0.08 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 16794478.59 | 0.00 | 237.21 | 29-SEP-01:45 | 0.08 |
October | 0.488250E+09 | 0.06 | 237.21 | 01-OCT-00:05 | 0.08 |
November | 0.614849E+09 | 0.08 | 237.21 | 01-NOV-00:10 | 0.08 |
December | 0.635344E+09 | 0.08 | 237.21 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.392996E+10 | 0.04 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.635344E+09 | 0.08 | 237.21 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.107647E+10 | 0.69 | 941.97 | 07-JAN-16:10 | 0.92 |
February | 0.990946E+09 | 0.70 | 941.97 | 01-FEB-10:00 | 0.93 |
March | 0.112823E+10 | 0.68 | 941.97 | 01-MAR-09:20 | 0.93 |
April | 0.998741E+09 | 0.50 | 941.97 | 01-APR-06:30 | 0.93 |
May | 0.991272E+09 | 0.38 | 941.97 | 06-MAY-07:40 | 0.92 |
June | 0.972279E+09 | 0.37 | 941.97 | 07-JUN-06:50 | 0.92 |
July | 0.932980E+09 | 0.34 | 941.97 | 03-JUL-14:10 | 0.92 |
August | 0.100876E+10 | 0.37 | 941.97 | 08-AUG-15:40 | 0.92 |
September | 0.952007E+09 | 0.38 | 941.97 | 07-SEP-10:10 | 0.92 |
October | 0.987569E+09 | 0.47 | 941.97 | 04-OCT-10:10 | 0.92 |
November | 0.984035E+09 | 0.61 | 941.97 | 01-NOV-08:30 | 0.93 |
December | 0.105077E+10 | 0.66 | 941.97 | 02-DEC-15:50 | 0.93 |
Annual Sum or Average | 0.120741E+11 | 0.51 | |||
Minimum of Months | 0.932980E+09 | 0.34 | 941.97 | 0.92 | |
Maximum of Months | 0.112823E+10 | 0.70 | 941.97 | 0.93 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.153241E+10 | 0.69 | 1427.17 | 01-JAN-00:06 | 0.93 |
February | 0.134429E+10 | 0.68 | 1427.17 | 01-FEB-00:02 | 0.93 |
March | 0.136199E+10 | 0.66 | 1427.17 | 01-MAR-00:02 | 0.93 |
April | 0.940300E+09 | 0.54 | 1427.17 | 01-APR-00:22 | 0.93 |
May | 0.625474E+09 | 0.28 | 1270.49 | 05-MAY-05:09 | 0.92 |
June | 0.587767E+09 | 0.22 | 570.87 | 01-JUN-06:10 | 0.56 |
July | 0.565160E+09 | 0.21 | 570.87 | 29-JUL-16:10 | 0.55 |
August | 0.610373E+09 | 0.22 | 570.87 | 01-AUG-06:10 | 0.56 |
September | 0.625699E+09 | 0.30 | 1397.69 | 29-SEP-05:01 | 0.92 |
October | 0.102472E+10 | 0.59 | 1427.17 | 12-OCT-05:01 | 0.92 |
November | 0.131493E+10 | 0.67 | 1427.17 | 01-NOV-00:23 | 0.93 |
December | 0.151076E+10 | 0.70 | 1427.17 | 01-DEC-00:03 | 0.93 |
Annual Sum or Average | 0.120439E+11 | 0.48 | |||
Minimum of Months | 0.565160E+09 | 0.21 | 570.87 | 0.55 | |
Maximum of Months | 0.153241E+10 | 0.70 | 1427.17 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.107647E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.990946E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.112823E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.998741E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.991272E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.120437E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.146942E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.131469E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.952007E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.987569E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.984035E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.105077E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.131485E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.952007E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.146942E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.153241E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.134429E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.136199E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.940300E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.625474E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.587767E+09 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.568776E+09 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.610373E+09 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.625699E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.102472E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.131493E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.151076E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.120475E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.568776E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.153241E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.107647E+10 | 0.00 | 0.154276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.990946E+09 | 0.00 | 0.130629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112823E+10 | 0.00 | 0.130695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.998741E+09 | 0.00 | 0.693364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.991272E+09 | 0.00 | 0.220437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.972279E+09 | 0.109065E+10 | 0.127337E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.932980E+09 | 0.257055E+10 | 17298001.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.100876E+10 | 0.145906E+10 | 0.165106E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.952007E+09 | 0.00 | 0.290240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.987569E+09 | 0.00 | 0.795728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.984035E+09 | 0.00 | 0.125246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105077E+10 | 0.00 | 0.148570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120741E+11 | 0.512026E+10 | 0.892491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.932980E+09 | 0.00 | 17298001.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.112823E+10 | 0.257055E+10 | 0.154276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.153241E+10 | 0.00 | 0.566607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134429E+10 | 0.00 | 0.472548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136199E+10 | 0.00 | 0.429331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.940300E+09 | 0.00 | 0.202311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.625474E+09 | 0.00 | 0.189789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.587767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.565160E+09 | 13124214.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.610373E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.625699E+09 | 0.00 | 0.342631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.102472E+10 | 0.00 | 0.260687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131493E+10 | 0.00 | 0.454778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151076E+10 | 0.00 | 0.560921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120439E+11 | 13124214.21 | 0.300042E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.565160E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153241E+10 | 13124214.21 | 0.566607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.107647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.990946E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.998741E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.991272E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.972279E+09 | 0.00 | 0.00 | 0.00 | 0.232087E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.932980E+09 | 0.00 | 0.00 | 0.00 | 0.536436E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.100876E+10 | 0.00 | 0.00 | 0.00 | 0.305939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.952007E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.987569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.984035E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120741E+11 | 0.00 | 0.00 | 0.00 | 0.107446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.932980E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.112823E+10 | 0.00 | 0.00 | 0.00 | 0.536436E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.153241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.940300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.625474E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.587767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.565160E+09 | 0.00 | 0.00 | 0.00 | 3615707.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.610373E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.625699E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.102472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120439E+11 | 0.00 | 0.00 | 0.00 | 3615707.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.565160E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153241E+10 | 0.00 | 0.00 | 0.00 | 3615707.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455758E+10 | 0.00 | 0.00 | 0.12 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368179E+10 | 0.00 | 0.00 | 0.13 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373126E+10 | 0.00 | 0.00 | 0.13 |
April | 27699581.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214277E+10 | 0.00 | 0.00 | 0.13 |
May | 0.369060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.825245E+09 | 0.00 | 0.00 | 0.13 |
June | 0.444778E+09 | 1506282.48 | 0.00 | 1322930.57 | 0.00 | 9188867.49 | 0.518556E+09 | 0.00 | 0.13 |
July | 0.122182E+09 | 8440682.93 | 0.00 | 3070118.88 | 0.00 | 5431809.76 | 0.574465E+09 | 0.00 | 0.13 |
August | 0.543913E+09 | 0.00 | 0.00 | 1975199.82 | 0.00 | 37514633.42 | 0.602662E+09 | 0.00 | 0.13 |
September | 0.369560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139273E+10 | 0.00 | 0.00 | 0.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283418E+10 | 0.00 | 0.00 | 0.12 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432789E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479971E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.187719E+10 | 9946965.42 | 0.00 | 6368249.26 | 0.00 | 0.283453E+11 | 0.169568E+10 | 0.00 | 0.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5431809.76 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.543913E+09 | 8440682.93 | 0.00 | 3070118.88 | 0.00 | 0.479971E+10 | 0.602662E+09 | 0.00 | 0.13 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157866E+11 | 0.00 | 0.00 | 0.17 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123821E+11 | 0.00 | 0.00 | 0.18 |
March | 0.427519E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116854E+11 | 0.00 | 0.00 | 0.19 |
April | 0.253018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351342E+10 | 0.00 | 0.00 | 0.18 |
May | 0.255355E+10 | 0.00 | 0.00 | 0.00 | 7496.61 | 0.134961E+09 | 0.00 | 0.00 | 0.18 |
June | 0.293438E+10 | 0.00 | 0.00 | 0.00 | 83853.92 | 0.00 | 0.00 | 0.00 | 0.19 |
July | 0.301248E+10 | 626406.31 | 0.00 | 371.40 | 8697706.09 | 0.00 | 229831.63 | 0.00 | 0.18 |
August | 0.403133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
September | 0.415657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482863E+09 | 0.00 | 0.00 | 0.18 |
October | 0.131184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.734186E+10 | 0.00 | 0.00 | 0.17 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149698E+11 | 0.00 | 0.00 | 0.17 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167746E+11 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.209578E+11 | 626406.31 | 0.00 | 371.40 | 8789056.63 | 0.830717E+11 | 229831.63 | 0.00 | 0.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.415657E+10 | 626406.31 | 0.00 | 371.40 | 8697706.09 | 0.167746E+11 | 229831.63 | 0.00 | 0.19 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:42:55
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | -0.140214E+12 | 0.737770E+11 | 0.00 | 0.203442E+11 | 0.661542E+11 |
February | 0.678047E+10 | 0.607173E+11 | 0.00 | 0.160639E+11 | 0.557549E+11 |
March | 0.404201E+12 | 0.837762E+11 | 0.00 | 0.158442E+11 | 0.529752E+11 |
April | 0.781450E+12 | 0.622915E+11 | 0.00 | 0.821417E+10 | 0.249116E+11 |
May | 0.101399E+13 | 0.259284E+11 | 0.00 | 0.388284E+10 | 0.195742E+10 |
June | 0.106883E+13 | 0.206806E+11 | 0.00 | 0.390663E+10 | 0.138313E+10 |
July | 0.979803E+12 | 0.244547E+11 | 0.00 | 0.370009E+10 | 0.313255E+10 |
August | 0.725782E+12 | 0.332345E+11 | 0.00 | 0.521740E+10 | 0.184610E+10 |
September | 0.323060E+12 | 0.268089E+11 | 0.00 | 0.640179E+10 | 0.324672E+10 |
October | 0.726777E+11 | 0.607442E+11 | 0.00 | 0.114879E+11 | 0.313038E+11 |
November | -0.951097E+11 | 0.299930E+11 | 0.00 | 0.192977E+11 | 0.501619E+11 |
December | -0.166240E+12 | 0.602293E+11 | 0.00 | 0.215744E+11 | 0.651106E+11 |
Annual Sum or Average | 0.497501E+13 | 0.562636E+12 | 0.00 | 0.135935E+12 | 0.357938E+12 |
Minimum of Months | -0.166240E+12 | 0.206806E+11 | 0.00 | 0.370009E+10 | 0.138313E+10 |